Industrial Electrical System Notes
Industrial Electrical System Notes
Industrial Electrical System Notes
Electrical Wiring
• A process of connecting various accessories
for distribution of electrical energy from
supplier’s meter board to home appliances
such as lamps, fans and other domestic
appliances is known as Electrical Wiring.
3
Switches
Switch is used to make or break the electric
circuit. It should so operate that it must
make the circuit firm. At the instant of
breaking the switch, it should break the
current so that there is no formation of arc
between switch blades and contact
terminals. Formation of arc damage the
switch contacts. Such an arc is avoided
usually by means of providing a spring. To
Movable blade so as to have a quick action.
4
Types of Switches
(a) Surface switches or Tumbler switch.
(b) Flush switches.
(c) Pull switches or Ceiling switches.
(d) Grid switches.
(e)Rotary switch.
(f) Push button switch,
(g) Iron-clad water-tight switch.
(h) Knife switch
5
Flush Switch
The flush switches are fixed in flush with the wall and do
not project out. Such types of switches are used where
high quality performance and appearance are desired.
Sometimes these switches are called Piano type switches.
Grid Switch
The grid switches are similar to tumbler switches, except
that they are lighter and are portable type, so that
they are quite useful for the portable machines such as
hand-drill, portable grinder etc. They are
manufactured either in single-way or two-way
pattern.
Knife Switches
The knife switch consists of blades hinged at one end and
are arranged to go into forked terminals or jaws at
the other end. These are available as single throw
switches or double throw switches.
10
Lamp Holders
As the name shows, a lamp-holder is used to
hold the lamp required for lighting
purposes. Earlier, brass lamp-holders were
quite popular, but now-a-days these have
been superseded by the all insulated
pattern. A lamp-holder has either moulded
or porcelain interior with a solid or spring
plunger and easily wired terminals.
11
12
• Swivel Lamp-holder
The swivel lamp holders are designed for controlled
wide angle directional lighting which are used for
lighting of shop windows, show cases etc.
16
Ceiling Roses
These are used to provide a tapping to the -
pendant lamp-holders, fan or fluorescent tube
According to Indian slandered
a) A ceiling rose of any other similar attachment shall
not be used on a circuit , the voltage of which
normally exceeds 250 volts.
b) Normally only one flexible cord shall be attached to a
ceiling rose. Specially designed ceiling roses shall be
used for multiple pendants.
c) A ceiling rose shall not embody fuse terminal as
integral part of it.
19
20
Socket Outlet
The socket outlets have all insulated base with
moulded or socket base having 3 terminal sleeves.
The two thin terminal sleeves are meant for
making connection to the cable, with the third
terminal sleeve, thicker in cross-section, is used
for an earth connection.
The cover is again moulded and has corresponding 3
holes. These are made for 5 amp and 15 amp
loads.
21
22
Plugs
For taking power from socket outlets, 3-pin plugs are
used. The thicker pin is used for an earth
connection to the portable appliances. They are
also made for 5 amps and 15amps load.
23
Terminal Blocks
Terminal blocks used for termination and connection
to the other circuits. A single-way terminal block is
used for differentiating the live line from the
neutral when the domestic connection is given and
is called as Connector.
24
Main Switch
The main switches are used to control the whole
supply for a house or office. These are of following
types:
ICDP- use for single phase supply control (15 A,
30A, 60A, 100A, 250 V)
ICTP- use for three phase-three wire and three
phase four wire supply control (15A, 30A, 60A,
100A, 150A, 200A, and 500V)
25
26
Wires
Types of wires
V.I.R. (Vulcanized Indian rubber) wire
CTS/TRS(Cab tyre sheathed, tough rubber sheath)
wires
Lead sheathes wire
PVC wires
Weather proof wires
Flexible wires
27
Selection of cables
Important factors that determine the selection of
cables
Rated Voltage- the rated voltage of cable should always
be equal to or grater than the system voltage.
Current Carrying Capacity- Each power cable is
designed to operate under certain temperature
conditions. Current carrying capacity of power cable
is also dependent on conductor material (Copper /
Aluminium) and insulation type. The current carrying
capacity is also dependent on operating temperature.
Higher the temperature, lower is the current carrying
capacity of the cable and vice versa.
28
Selection of cables
Derating Factor- A power cable designed with
standard operating conditions may not operate so in
practical. Therefore, the current carrying capacity
may get impacted due to this.
For example: Cables installed deep under the ground
will have reduced current carrying capacity than
cables installed in air. This is impacted due to
multiple factors like soil temperature, soil thermal
resistivity etc.
Actual Current Carrying Capacity = Derating Factor x
Cable current carrying capacity under std. conditions.
29
Selection of cables
Voltage Drop- A power cable manufacturer provides
this as part of their data sheet. A voltage drop across
the length of the power cable is very important. It is
expressed as: mV / A-m.
The voltage drop per unit length of cable should as
minimum as possible so as to get voltage at delivery
end approximately same as supply side.
Short circuit Withstand - A power cable in case of
short circuit event should be able to withstand the
high current values without any damage to the cable
and insulation.
30
Selection of cables
Availability of Cables-This needs to be checked with
manufacturer or the dealer of a particular cable.
Cables are manufactured in certain minimum length
segments. Therefore, it will be difficult to procure a
30 meter length of 300 sq-mm cable than a 300 meter
length of same cable. Also, the costing may vary
largely between the two quantities.
Bending Radius- This can be a practical problem
during installation. Large sized multi-core cables have
bigger bending radius than small sized. Therefore a
same size of multi-core XLPE cable has more bending
radius than a PVC. In order to overcome this, a
contractor might have to opt separate single core
cables.
31
Protective Devices
When a failure occurs on any part of the electrical power
system, it must be quickly detected and disconnected from
the system. There are two reason for it. Firstly, if the fault
not cleared quickly , it may cause unnecessary interruption
of the service to the customer. Secondly, rapid disconnection
of faulty apparatus limit the amount of damage to it and
prevent the effects of fault from spreading into the system.
The detection of fault and disconnection of faulty part can
be achieved by using fuses or relays in connection with
circuit breakers. A fuse can perform both the function but
for low voltage circuit only. For high voltage circuits, relays
and circuit breakers are employed to serve the desire
function for automatic protective gear.
34
Protective Relays
Protective relay is a device that detect the fault and
initiate the operation of the circuit breaker to isolate the
faulty element from the rest of the system.
The relay circuit can be divided in three parts:
1. First is primary winding of the CT which is
connected in series with the line to be protected.
2. Second part is secondary of CT and the relay
operating coil.
3. Third is the tripping circuit which may be either ac
or dc. It consists of a source of supply, the trip coil of
the CB and the relay stationary contacts.
35
Protective Relays
36
Protective Relays
The main features of protective devices :
1. Selectivity: It is the ability of the protective system
to select correctly that part of the system in trouble
and disconnect the faulty part without disturbing
the rest of the system
2. Speed: The relay system should disconnect the
faulty section as fast as possible
3. Sensitivity: It is the ability of the relay system to
operate with low value of actuating quantity.
4. Reliability: It is the ability of the relay system to
operate under the pre-determined conditions.
Fundamental Requirement of
38
Protective Relays
5. Simplicity: The relaying system should be simple so that
it can be easily maintained. Reliability is closely related
to simplicity. The simpler the protection scheme, the
greater will be its reliability.
6. Economy: The most important factor in the choice of a
particular protection scheme is the economic aspect.
Sometimes it is economically unjustified to use an ideal
scheme of protection and a compromise method has to
be adopted. As a rule, the protective gear should not cost
more than 5% of total cost. However, when the
apparatus to be protected is of utmost importance (e.g.
generator, main transmission line etc.), economic
considerations are often subordinated to reliability.
39
According to applications
1. Over Voltage/Over Current/Over Power Relay
2. Under Voltage /Under Current /Under Power relay
3. Directional or Reverse Power Relay
4. Directional or Reverse Current Relay
5. Differential Relay
6. Distance Relay
According to time characteristics
1. Instantaneous Relay
2. Definite Time Lag Relay
3. Inverse Time Lag-Relay
41
Fuses
A fuse is a short piece of metal, inserted in the circuit, which
melts when excessive current flows through it and thus
breaks the circuit.
The fuse element is generally made of materials having low
melting point, high conductivity and least deterioration due
to oxidation e.g., silver, copper etc. It is inserted in series
with the circuit to be protected. Under normal operating
conditions, the fuse element is at a temperature below its
melting point. Therefore, it carries the normal current
without overheating. However, when a short-circuit or
overload occurs, the current through the fuse increases
beyond its rated value. This raises the temperature and fuse
element melts (or blows out), disconnecting the circuit
protected by it.
42
Advantages
1. It is the cheapest form of protection available.
2. It requires no maintenance.
3. Its operation is inherently completely automatic
unlike a circuit breaker which requires an elaborate
equipment for automatic action.
4. It can break heavy short-circuit currents without
noise or smoke.
5. The smaller sizes of fuse element impose a current
limiting effect under short-circuit conditions.
6. The inverse time-current characteristic of a fuse
makes it suitable for overcurrent protection.
7. The minimum time of operation can be made much
shorter than with the circuit breakers.
43
Disadvantages
1. Considerable time is lost in rewiring or replacing a
fuse after operation.
2. On heavy short-circuits, *discrimination between
fuses in series cannot be obtained unless there is
sufficient difference in the sizes of the fuses
concerned.
3. The current-time characteristic of a fuse cannot
always be co-related with that of the protected
apparatus.
44
Operation of MCB
The operation of the MCB includes two stages, i.e.,
thermal operation and short circuit operation.
With the use of bimetallic strip, thermal operation is
achieved in case overload conditions. When overload
current flows through the MCB, the bimetallic strip gets
heated and causes to deflect. In doing so, it moves the
trip lever and releases the latch mechanism and hence
the contacts open under spring mechanism.
56
MPCB
Functions of MPCB
75
Electric Shock
Definition
• The rate at which electrical energy is supplied
to a consumer is known as tariff.
• Although tariff should include the total cost of
producing and supplying electrical energy
plus the profit , yet it cannot be the same for
all types of consumer.
96
Objective
• Recovery of cost of producing electrical
energy at the power station.
• Recovery of cost on the capital investment in
transmission and distribution system.
• Recovery of cost of operation and
maintenance of supply of electrical energy e.g.
metering equipment, billing etc.
• A suitable profit on the capital investment.
97
Types of Tariff
• Simple tariff
• Flat rate tariff
• Block rate tariff
• Two part tariff
• Maximum demand tariff
• Power factor tariff
• Three part tariff
100
Simple Tariff
When there is a fixed rate per unit of energy
consumed, it is called a simple tariff or uniform
rate tariff.
In this type of tariff, the price charged per unit
is constant i.e., it does not vary with increase or
decrease in number of units consumed. The
consumption of electrical energy at the
consumer’s terminals is recorded by means of
an energy meter.
Advantages: 101
• Simplest method
• Easily understandable and easy to apply
• Each consumer has to pay according to his utilization
Disadvantages
• There is no discrimination according to the different
types of consumers.
• The cost per unit is high.
• There are no incentives (an attractive feature that
makes the consumers use more electricity.)
• If a consumer does not consume any energy in a
particular month, the supplier cannot charge any
money even though the connection provided to the
consumer has its own costs.
102
Application
Generally applied to tube wells used for
irrigation purposes.
103
Advantages:
• More fair to different consumers.
• Simple calculations.
Disadvantages
• A particular consumer is charged at a particular rate.
But there are no incentives for the consumer.
• Since different rates are decided according to different
loads, separate meters need to be installed for different
loads such as light loads, power loads, etc. This makes
the whole arrangement complicated and expensive.
• All the consumers in a particular “category” are
charged at the same rates. However, it is fairer if the
consumers that utilize more energy be charged at
lower fixed rates.
105
Advantages:
• Only one energy meter is required.
• Incentives are provided for the consumers due
to reduced rates. Hence consumers use more
energy. This improves load factor and reduces
cost of generation.
Application
Generally applied to domestic consumers and
small commercial consumers.
108
Advantages
(i) It is easily understood by the consumers.
(ii) It recovers the fixed charges which depend
upon the maximum demand of the consumer but
are independent of the units consumed.
Disadvantages
(i) The consumer has to pay the fixed charges
irrespective of the fact whether he has consumed
or not consumed the electrical energy.
(ii) There is always error in assessing the maximum
demand of the consumer.
111
Three-part tariff
When the total charge to be made from the
consumer is split into three parts viz., fixed
charge, semi-fixed charge and running charge, it
is known as a three-part tariff.
i.e.,
Total charge = Rs (a + b × kW + c × kWh)
Where,
a = fixed charge made during each billing period. It
includes interest and depreciation on the cost of
secondary distribution and labor cost of
collecting revenues,
b = charge per kW of maximum demand,
c = charge per kWh of energy consumed.
117
Solution-1
119
Solution-2
120
121
Electrical Wiring
• A process of connecting various accessories
for distribution of electrical energy from
supplier’s meter board to home appliances
such as lamps, fans and other domestic
appliances is known as Electrical Wiring.
• The wiring system selected will depend to a
large extent on the types of service required.
122
Factors Affecting the Selection of
Wiring
1. Durability
2. Safety
3. Appearance
4. Cost
5. Accessibility
6. Maintenance Cost
123
Cleat Wiring
• In this system of wiring, cables are supported
and gripped between porcelain cleats and
6mm. above the wall or roof.
• The main part is base, which is grooved to
accommodate the cables, the other part is the
cap which is put over the base
125
126
• Cleats are placed above the wall or roof at an
interval of 30 to 60 cm.
• The cables recommended for this type of
wiring are VIR or PVC cables and any other
approved insulated cables.
Advantages
1. It is the cheapest system.
2. Installation and dismantling is easy.
3. Less skilled persons are required.
4. Inspection is easy.
5. Alterations and additions are easy.
127
Disadvantages
1. It is purely temporary wiring system.
2. Appearance is not good.
3. Cables are exposed to atmosphere and there
is a possibility of mechanical injury.
4. This system should not be used in damp
places other wise insulation gets damaged.
128
Advantages
1. It provides good insulation as conductors are
apart.
2. It provides good mechanical strength.
3. Easy to inspect by opening the capping.
132
Disadvantages
1. It is costly system now – a – days because it
needs seasoned, knot free wood.
2. There is every risk of fire.
3. The labor cost is more because it requires
skilled carpenters.
4. This system can not be used in damp places.
133
Installation
a) Layout wiring
b) Conductors
c) Rating of lamp, fan and socket outlet point
d) Joint box and looping in system
e) Reception and distribution of main supply
f) Arrangement of apparatus on switchboards
g) Single phase supply
h) Three phase, four wire supply
i) Sub distribution board
j) Sub circuits
k) Diversity
l) Diversity factor for sub circuit
151
Layout Wiring
152
Conductors
153
Rating of lamp, fan and socket outlet point
154
Service Connection
The line bringing electric power from supplier’s low voltage
distribution up to the energy meter installed at the consumer’s
premises is called the service connection.
The electric supply authority supplies power to the consumers
through a low voltage three phase four wire distribution system
called the secondary distribution system.
Large consumers supplied at higher voltages through three-wire
high voltage distribution system called the primary distribution
system (6.6, 11, 33 kV)
Service connection may be by mean of underground cables or by
mean of overhead conductors or cables.
165
Service Mains
171
Sub Circuits
-After the main switch the supply is taken to the various load
points.
-In the given circuit same circuit contains light, fan and power
circuit which has various drawbacks.
-Dividing the wiring into a number of smaller circuit is called sub-
circuit.
172
Sub Circuits
Sub-circuit divided into two parts:
a) Light and fan sub-circuit
b) Power Sub-circuit
173
174
Location of Outlets.
Location of Control Switches
Location of Main Board and Distribution Board
175
Load Assessment
Estimating and Costing
177
of Electrical
Installation
• Quantity and specification of material
• Price list
• Labour charges
• Overhead charges
• Contingencies
• Profit purchase system
178
UNIT-3
Illumination System
Contents: Understanding various terms regarding light, lumen, intensity, candle power,
lamp efficiency, specific consumption, glare, space to height ratio, waste light factor,
depreciation factor, various illumination schemes, Incandescent lamps and modern luminaries
like CFL, LED and their operation, energy saving in illumination systems, design of a lighting
scheme for a residential and commercial premises, flood lighting.
Important Terms:
Light: It is defined as the radiation energy from a hot body which produces the visual
sensation upon the human eye. It is usually denoted by Q, expressed in lumen-hours and
is analogous to watt-hour.
Luminous flux: it is defined as the total quantity of light energy emitted per second
form a luminous body. It is represented by symbol F and is measured in lumens. The
concept of luminous flux helps us to specify the output and efficiency of a given light
source.
Luminous intensity: luminous intensity in any given direction is the luminous flux
emitted by the source per unit solid angle, measured in the direction in which the
intensity is required. It is denoted by symbol I and is measured in candela(cd) or
lumens/steradian.
If F is the luminous flux radiated out by source within a solid angle of ω steradian in
any particular direction then I =F/ ω lumens/steradian or candela (cd).
Lumen: The lumen is the unit of luminous flux and is defined as the amount of luminous
flux given out in a space represented by one unit of solid angle by a source having an
intensity of one candle power in all directions.
Lumens = candle power X solid angle = cp X ω
Total lumens given out by source of one candela are 4π lumens.
Candle power: Candle power is the light radiating capacity of a source in a given
direction and is defined as the number of lumens given out by the source in a unit solid
angle in a given direction. It is denoted by a symbol C.P.
C.P. = lumens/ω
Illumination: When the light falls upon any surface, the phenomenon is called the
illumination. It is defined as the number of lumens, falling on the surface, per unit area.
It is denoted by symbol E and is measured in lumens per square meter or meter-candle
or lux.
187
If a flux of F lumens falls on a surface of area A, then the illumination of that surface is
E =F/A lumens/m2 or lux
Lux or meter candle: It is the unit of illumination and is defined as the luminous flux
falling per square meter on the surface which is everywhere perpendicular to the rays
of light from a source of one candle power and one meter away from it.
Foot candle: It is also the unit of illumination and is defined as the luminous flux falling
per square foot on the surface which is everywhere perpendicular to the rays of light
from a source of one candle power and one foot away from it.
1 foot-candle = 1 lumen/ft2 =10.76 meter candle or lux
Candle: It is the unit of luminous intensity. It is defined as 1/60th of the luminous
intensity per cm2 of a black body radiator at the temperature of solidification of
platinum (2,0430K).
Mean horizontal candle power: (M.H.C.P) It is defined as the mean of candle powers
in all directions in the horizontal plane containing the source of light.
Mean spherical candle power: ( M.S.C.P) It is defined as the mean of the candle
powers in all directions and in all planes from the source of light.
Mean hemi-spherical candle power: (M.H.S.C.P) It is defined as the mean of candle
powers in all directions above or below the horizontal plane passing through the source
of light.
Reduction factor: Reduction factor of a source of light is the ratio of its mean spherical
candle power to its mean horizontal candle power.
reduction factor = M.S.C.P./M.H.C.P.
Lamp efficiency: It is defined as the ratio of the luminous flux to the power input. It is
expressed in lumens per watt.
Specific consumption: It is defined as the ratio of the power input to the average
candle power. It is expressed in watt per candela.
Brightness : When the eye receives a great deal of light from an object we say it is
bright, and brightness is an important quantity in illumination. It is all the same
whether the light is produced by the object or reflected from it.
Brightness is defined as the luminous intensity per unit projected area of either a
surface source of light or a reflecting surface and is denoted by L.
If a surface area A has an effective luminous intensity of I candelas in a direction θ to the
normal, than the brightness (luminance) of that surface is
L = I/a cosθ
The unit of brightness is candela/m2 (nits), candela/cm2 (stilb) or candela/ft2
Glare:- The size of the opening of the pupil in the human eye is controlled by its iris. If
the eye is exposed to a very bright source of light the iris automatically contacts in order
to produce the amount of light admitted and prevent damaged to retina this reduces the
sensitivity, so that other objects within the field of vision can be only imperfectly seen.
In other words glare maybe defined as brightness with in the field of vision of such a
character as the cause annoyance discomfort interference with vision.
Space height ratio:- it is defined as the ratio of distance between adjacent lamps and
height of their mountains.
188
Maintenance factor: Due to accumulation of dust, dirt and smoke on the lamps, they
emit less light than that they emit when they are new ones and similarly the walls and
ceilings e.t.c. after being covered with dust, dirt and smoke do not reflect the same
output of light, which is reflected when they are new. Lumens
The ratio of illumination under normal working conditions to the illumination when the
things are perfectly clean is known as maintenance factor.
Depreciation factor: this is merely reverse of the maintenance factor and is defined as
the ratio of the initial meter-candles to the ultimate maintained metre-candles on the
working plane. Its value is more than unity.
Waste light factor: Whenever a surface is illuminated by a number of sources of light,
there is always a certain amount of waste of light on account of over-lapping and falling
of light outside at the edges of the surface. The effect is taken into account by
multiplying the theoretical value of lumens required by 1.2 for rectangular areas and 1.5
for irregular areas and objects such as statues, monuments etc.
Absorption factor: In the places where atmosphere is full of smoke fumes, such as in
foundries, there is a possibility of absorption of light. The ratio of total lumens available
after absorption to the total lumens emitted by the source of light is called the
absorption factor. Its value varies from unity for clean atmosphere to 0.5 for foundries.
Beam factor: the ratio of lumens in the beam of a projector to the lumens given out by
lamps is called the beam factor. This factor takes into the account the absorption of light
by reflector and front glass of the projector lamp. Its value varies from 0.3 to 0.6.
Reflection factor: When a ray of light impinges on a surface it is reflected from the
surface at an angle of incidence, as shown in the fallowing figure. A certain portion of
incident light is absorbed by the surface. The ratio of reflected light to the incident light
is called the reflection factor. It’s value always less than unity.
Plane angle: A plane angle is the angle subtended at a point in a plane by two
converging lines. It is denoted by the Greek letter ‘θ’ (theta) and is usually measured in
degrees or radians.
189
𝑎𝑟𝑐
𝜃= 𝑟𝑎𝑑𝑖𝑎𝑛𝑠
𝑟𝑎𝑑𝑖𝑜𝑢𝑠
One radian is defined as the angle subtended by an arc of a circle whose length by an arc
of a circle whose length is equals to the radius of the circle.
Solid angle: Solid angle is the angle subtended at a point in space by an area, i.e., the
angle enclosed in the volume formed by numerous lines lying on the surface and
meeting at the point. It is usually denoted by symbol ‘ω’ and is measured in steradian.
𝑎𝑟𝑒𝑎 𝐴
𝜔= =
(𝑟𝑎𝑑𝑖𝑜𝑢𝑠)2 𝑟2
The largest solid angle subtended at a point is that due to a sphere at its centre. If r is
the radius of any sphere, its surface area is 4π2 and the distance of its surface area from
the centre is r, therefore, solid angle subtended at its centre by its surface,
4𝜋𝑟 2
𝜔= = 4𝜋 𝒔𝒕𝒆𝒓𝒂𝒅𝒊𝒂𝒏𝒔
(𝑟)2
Steradian: It is the unit of solid angle and is defined as the solid angle that subtends a
surface on the sphere equivalent to the square of the radius.
Example 1: A 200-V lamp takes a current of 1.2 A, it produces a total flux of 2,860
lumens. Calculate:
1. the MSCP of the lamp and
2. the efficiency of the lamp.
Solution:
Given V = 200 V, I = 1.2 A, flux = 2,860 lumens.
Solution:
Room area = 6 × 9 = 54 m .
Total wattage = 80 × 10 = 800 W.
Total flux emitted by ten lamps = 80 × 800 = 64,000 lumens.
Flux reaching the working plane = 64,000 × 0.65 = 41,600 lumens.
Laws of Illumination
Mainly there are two laws of illumination.
1. Inverse square law.
2. Lambert's cosine law.
1. Inverse square law: This law states that ‘the illumination of a surface is inversely
proportional to the square of distance of the surface from the source of light.
Let, ‘S’ be a point source of luminous intensity ‘I’ candela, the luminous flux emitting
from source crossing the three parallel plates having areas A A , and A square meters,
which are separated by a distances of d, 2d, and 3d from the point source respectively as
shown in Fig.
2. Lambert's cosine law: This law states that illumination, E at any point on a surface
is directly proportional to the cosine of the angle between the line of flux AND the
normal at that point.
Let us assume that the surface is inclined at an angle ‘θ’ to the lines of flux as shown
in Fig. (a)
PQ = The surface area normal to the source and inclined at ‘θ’ to the vertical axis.
RS = The surface area normal to the vertical axis and inclined at an angle θ to the source ‘O’.
192
cosθ = h/d
or d = h/cosθ
where d is the distance between the source and the surface in m, h is the height of
source from the surface in m, and I is the luminous intensity in candela.
Hence, above Equation is also known as ‘cosine cube’ law. This law states that the
illumination at any point on a surface is dependent on the cube of cosine of the angle
between line of flux and normal at that point.
Note - From the above laws of illumination, it is to be noted that inverse square law is only
applicable for the surfaces if the surface is normal to the line of flux. And Lambert's cosine
law is applicable for the surfaces if the surface is inclined an angle ‘θ’ to the line of flux.
193
Scanned by CamScanner
194
Scanned by CamScanner
195
Scanned by CamScanner
196
Scanned by CamScanner
197
Scanned by CamScanner
198
Scanned by CamScanner
199
Scanned by CamScanner
200
Scanned by CamScanner
201
Scanned by CamScanner
202
Scanned by CamScanner
203
Scanned by CamScanner
204
Scanned by CamScanner
205
Industrial Substation
At many places in the line of the power system, it may be desirable and necessary to
change some characteristic (e.g. voltage, a.c. to d.c., frequency, p.f. etc.) of electric supply.
This is accomplished by suitable apparatus called substation.
For example, generation voltage (11 kV or 6·6 kV) at the power station is stepped up to
high voltage (say 220 kV or 132 kV) for transmission of electric power. The assembly of
apparatus (e.g. transformer etc.) used for this purpose is the sub-station. Similarly, near
the consumers localities, the voltage may have to be stepped down to utilization level.
This job is again accomplished by a suitable apparatus called substation. At some places
in the line of the power system, it may be desirable to convert large quantities of a.c.
power to d.c. power e.g. for traction, electroplating, *d.c. motors etc. This job is again
performed by suitable apparatus (e.g. ignitron) called sub-station. It is clear that type of
equipment needed in a sub-station will depend upon the service requirement.
The following are the important points which must be kept in view while laying out a
sub-station:
(i) It should be located at a proper site. As far as possible, it should be located at the
centre of gravity of load.
(ii) It should provide safe and reliable arrangement. For safety, consideration must be
given to the maintenance of regulation clearances, facilities for carrying out repairs
and maintenance, abnormal occurrences such as possibility of explosion or fire etc.
(iii) It should be easily operated and maintained.
(iv) It should involve minimum capital cost.
The comparison between outdoor and indoor sub-stations is given below in the tabular
form:
From the above comparison, it is clear that each type has its own advantages and
disadvantages.
207
2. According to service requirement. A sub-station may be called upon to change
voltage level or improve power factor or convert a.c. power into d.c. power etc.
According to the service requirement, sub-stations may be classified into:
(i) Transformer sub-stations. Those sub-stations which change the voltage level of
electric supply are called transformer sub-stations. These sub-stations receive power at
some voltage and deliver it at some other voltage. Obviously, transformer will be the
main component in such substations. Most of the sub-stations in the power system are
of this type.
(ii) Switching sub-stations. These sub-stations do not change the voltage level i.e.
incoming and outgoing lines have the same voltage. However, they simply perform the
switching operations of power lines.
(iii) Power factor correction sub-stations. Those sub-stations which improve the
power factor of the system are called power factor correction sub-stations. Such sub-
stations are generally located at the receiving end of transmission lines. These sub
stations generally use synchronous condensers as the power factor improvement
equipment.
(iv) Frequency changer sub-stations. Those sub-stations which change the supply
frequency are known as frequency changer sub-stations. Such a frequency change may
be required for industrial utilisation.
(v) Converting sub-stations. Those sub-stations which change a.c. power into d.c.
power are called converting sub-stations. These sub-stations receive a.c. power and
convert it into d.c. power with suitable apparatus (e.g. ignitron) to supply for such
purposes as traction, electroplating, electric welding etc.
(vi) Industrial sub-stations. Those sub-stations which supply power to individual
industrial concerns are known as industrial sub-stations.
Fig. 4.1 shows the block diagram of a typical electric supply system indicating the
position of above types of sub-stations. It may be noted that it is not necessary that all
electric supply schemes include all the stages shown in the figure. For example, in a
certain supply scheme there may not be secondary sub-stations and in another case, the
scheme may be so small that there are only distribution sub-stations.
208
Selection of Transformer
In order to select the correct three phase transformer we must first determine:
(1) The equipment being installed operates on a three phase supply- If both
single phase and three phase equipment are connected at the load end; the single
phase equipment is connected to only one phase of the transformer.
(2) The Primary Voltage of the transformer- This is the same as the line input
(or source) voltage.
(3) The Secondary Voltage of the transformer- This is the transformer's output
voltage and must be the same as the voltage required by the equipment being
installed (see equipment nameplate).
(4) Frequency- The Frequency of the input (source) voltage must be the same as
the operating frequency of the equipment being supplied. The transformer
selected must operate at the same frequency. Typical operating frequency is 50
Hz.
(5) Rating- The rating of the load is determined by the product of the voltage
supplied across the load and the current passing through it. This is normally
expressed in VA or kVA on the equipment nameplate. The total load is often as
combination of various loads (i.e. lights, heaters, motors). We must calculate
these individual loads and add them together to obtain the total load of the
transformer.
The transformer must have a kVA rating greater than the load
requirement. The three phase transformer must be selected in a way that any
one phase is not overloaded.
215
Full Load Current Table - 3 Phase Transformer
216
Industrial load consists of small, medium, large and heavy scale industries.
The induction motor forms a high proportion of the industrial load. The
industrial load is a function of frequency and voltage and it cover a major part of
the system load.
The three different types of industrial loads under which electric motors are
required to work are as under:
(i) Continuous Load: In such cases, the calculation of motor size is simpler
because the loads like pumps and fans require a constant power input to keep
them operating. However, it is essential to calculate the KW rating of the motor
correctly. If the KW rating of the motor is less than what is required, the motor
will overheat and consequently burn out. If, on the other hand, KW rating is
more than what is needed by the load, the motor will remain cool but will
operate at lower efficiency and power.
(ii) Intermittent Loads: Such loads can be of the following two types:
(a) In this type of load, motor is loaded for a short time and then shut off for a
long time, allowing the motor to cool down to room temperature as shown in
Fig 1. In such cases, a motor with a short time rating is used.
(b) In this type of load, motor is loaded for a short time and then it is shut off for
a short time. The shut off time is so short that the motor cannot cool down to the
room temperature as shown in Fig.2. In such cases, a suitable continuous or
short-time rated motor is chosen which, when operating on a given load cycle,
will not exceed the specified temperature limit.
Fig: 1 Fig: 2
218
(iii) Variable Loads: In the case of such loads, the most accurate method of
selecting a suitable motor is to draw the heating and cooling curves as per the
load fluctuations for a number of motors. The motor which does not exceed the
permitted temperature rise when operating on the particular load cycle should be
chosen for the purpose.
Selection of a Motor
The selection of a motor depends primarily on the conditions under which it has
to operate and the type of load it has to handle. Main factors for such a selection
are as follows:
In fact, heating is proportional to square of the current but since load can be
expressed in terms of the current drawn, the proportionality can be taken for
load instead of the current.
222
Starting of Motors:
The induction motor, the most common type of motor utilized in building and
industry processes. Induction motors work by generating rotation power through
electrical conversion. This is with interacting magnetic fields. The back
electromagnetic force (EMF), which is coupled with magnetic field build-up at
the time of motor start, injects transient events that happen in the electrical
system. Such transitory conditions affect all equipment connected to the system
and its electrical supply. Motor starting is carefully studied and inspected in
industrial applications to limit such transient influence and to correctly
accelerate the mechanical load of the motor.
Direct-on-Line
Direct-on-line (DOL) is a straightforward method that is done by connecting the
motor to the supplier directly at a specific voltage. Not every system can use this
method; the most common examples are in well-dimensioned and mechanically
stiff shaft systems. It can also be used for pumps and other equipment that have
a stable supply. Direct-on-line is the most common method particularly since it
is the cheapest and simplest. It also causes the tiniest rise in temperature out of
all the techniques in motor starting. The issue with DOL is that the current can
be as high as eight times or more than its normal load.
Star-delta
Star-delta starting method is used in three-phase motors. It is applied to
minimize the starting current. At the motor start-up, the supply is connected to
the star end for the stator windings to commence. As soon as it achieves running
223
position, the current supply is reattached to the delta windings. The advantage of
using star-delta is the reduced starting voltage. The current at start-up for this
technique is only a third of the DOL method. This system is applied to high
inertia models wherein loads are initiated at the time full loading speed is
achieved. The setback to using star-delta is that around 33% reduction in
starting torque occurs. The effective changeover is required from star to delta so
that the speed is maintained. If this fails or happens at a low speed, the current
surge rises as much as in DOL, which can be detrimental to the entire system.
Auto-transformer
The auto-transformer starting is perhaps the fanciest of these three methods
since it uses an auto-transformer that is coupled with the induction motor at the
start-up. This technique utilizes dual voltage reductions brought about by
transformers, which also minimizes the voltage (around 50-80% of the full
voltage) using the secondary auto-transformer voltage. This system causes
reduced torque and locked-rotor current. It also causes a concurrent increase in
possible torque per ampere line. The auto-transformer start may also cause a
pulsing current due switching from secondary voltage to the main one.
……………………………………………………………………………………
Assignment: Explain different methods of starting induction motor.
……………………………………………………………………………………
224
Selection of Cable
Conductors: A cable may have one or more than one core (conductor). The
conductors are made of copper or aluminum and are usually stranded in order to
provide flexibility to the cable.
Insulation: Each core or conductor is provided with a suitable thickness of
insulation, the thickness of layer depending upon the voltage to be withstood by
the cable. The insulating materials used in cables are rubber, vulcanized India
rubber, impregnated paper, varnished cambric and polyvinyl chloride.
Metallic sheath: In order to protect the cable from moisture, gases or other
damaging liquids (acids or alkalies) in the soil and atmosphere, a metallic sheath
of lead or aluminum is provided over the insulation.
Bedding: Over the metallic sheath is applied a layer of bedding which consists
of a fibrous material like jute or hessian tape. The purpose of bedding is to
protect the metallic sheath against corrosion and from mechanical injury due to
armoring.
225
Armoring: Over the bedding, armoring is provided which consists of one or two
layers of galvanized steel wire or steel tape. Its purpose is to protect the cable
from mechanical injury.
Serving: In order to protect armoring from atmospheric conditions, a layer of
fibrous material (like jute) similar to bedding is provided over the armoring.
This is known as serving.
…………………………………………………………………………………..
The selection and satisfactory operation of a cable depends to a great extent
upon the characteristics of insulation used. The insulating materials used in
cables should have the following properties:
High insulation resistance to avoid leakage current.
High dielectric strength to avoid electrical breakdown of the cable.
High mechanical strength to withstand the mechanical handling of cables.
It should not absorb moisture from air or soil. The moisture tends to
decrease the insulation resistance and hastens the breakdown of the cable.
Non-inflammable
Low cost
Classification of Cables:
(i) Low-tension (L.T.) cables — upto 1000 V
(ii) High-tension (H.T.) cables — upto 11,000 V
(iii) Super-tension (S.T.) cables — from 22 kV to 33 kV
(iv) Extra high-tension (E.H.T.) cables — from 33 kV to 66 kV
(v) Extra super voltage cables — beyond 132 kV
A cable may have one or more than one core depending upon the type of service
for which it is intended. It may be (i) single-core (ii) two-core (iii) three-core
(iv) four-core etc. For a 3-phase service, either 3-single-core cables or three-core
cable can be used depending upon the operating voltage and load demand.
226
Switchgear selection
The apparatus used for switching, controlling and protecting the electrical
circuits and equipment is known as switchgear. The switchgear equipment is
essentially concerned with switching and interrupting currents either under
normal or abnormal operating conditions.
(i) Complete reliability: With the continued trend of interconnection and the
increasing capacity of generating stations, the need for reliable switchgear has
increased. When fault occurs on any part of the power system, the switchgear
must operate to isolate the faulty section from the rest of the circuit.
(ii) Absolute discrimination: When fault occurs on any section of the power
system, the switchgear must be able to discriminate between the faulty section
and the healthy section. It should isolate the faulty section from the system
without affecting the healthy section. This will ensure continuity of supply.
(iii) Quick operation: When fault occurs on any part of the power system, the
switchgear must operate quickly so that no damage is done to generators,
transformers and other equipment by the short-circuit currents. If fault is not
cleared by switchgear quickly, it is likely to spread into healthy parts, thus
complete shutdown of the system may occur.
229
(iv) Provision for manual control: Switchgear must have provision for manual
control. In case the electrical (or electronics) control fails, the necessary
operation can be carried out through manual control.
Lightning Protection
A direct stroke to a phase (line) conductor is the most severe lightning stroke as
it produces the highest overvoltage for a given stroke current. Direct lightning
stroke approximates to a constant current source.
Methods of protection:
(i) Ground wires: The most generally accepted and effective method of
protecting lines against direct strokes is by the use of overhead ground wires
(also called earth wire). This method of protection is known as shielding
method which does not allow an arc path to form between the line conductor
and ground.
(ii) Lightning Arresters or Surge Diverters: They are connected between the
line and ground at the substation and always act in shunt (parallel) with the
equipment to be protected.
Earthing
The process of connecting the metallic frame (i.e. non-current carrying part) of
electrical equipment or some electrical part of the system (e.g. neutral point in a
star-connected system, one conductor of the secondary of a transformer etc.) to
earth (i.e. soil) is called grounding or earthing.
Equipment grounding deals with earthing the non-current carrying metal parts
of the electrical equipment.
Above fig shows a 3-phase, star-connected system with neutral earthed (i.e.
neutral point is connected to soil). Suppose a single line to ground fault occurs
in line R at point F, this will cause the current to flow through ground path as
shown in fig. The current flows from R phase to earth, then to neutral point N
and back to R-phase. Since the impedance of the current path is low, a large
current flows through this path. This large current will blow the fuse in R-phase
and isolate the faulty line R. This will protect the system from the harmful
effects (e.g. damage to equipment, electric shock to personnel etc.) of the fault.
It is a core type transformer having three limbs built in the same fashion as that
of the power transformer. Each limb of the transformer has two identical
windings wound differentially (i.e. directions of current in the two windings on
each limb are opposite to each other) as shown in fig. Under normal operating
conditions, the total flux in each limb is negligibly small. Therefore, the
transformer draws very small magnetizing current.
235
If we connect a single-phase load between one line and neutral, the load current
I divide into three equal currents in each winding. Because the currents are
equal, the neutral point stays fixed and the line to neutral voltages remain
balanced as they would be on a regular 4-wire system. In practice, the single-
phase loads are distributed as evenly as possible between the three phases and
neutral so that unbalanced load current I is relatively small.
There are different types of earthing system mostly used, which are
Earth pit: Excavate and make an earth pit of size 900 mm x 900 mm x
minimum 3.0 meter deep. Level the bottom surface.
Plate electrode: Use GI plate of minimum size 600 Mm x 600 Mm x 6 mm
thickness. In case of a Copper plate, a minimum thickness of 3.15 mm can
be used.
Earthing connection: Fix two numbers of 50 mm x 6 mm GI strips to GI
plate with GI nuts, bolts and washer with each strip fixed to GI plate at two
locations. Weld the GI strips to GI plate. Join the two strips at the top with a
237
GI strip of the same size. Any loose earthing connection with the earth plate
will have an adverse effect on the electrode system resistivity.
Make a borehole of 500 mm diameter and 3.5 meters deep or as per the
approved design and drawing.
Lower the Pipe electrode made of a 65 mm diameter GI perforated pipe of
3.0-meter length attached at the top with a funnel covered with wire mesh. A
G.I. strip is fixed to the electrode to act as an earthing connection. For rod
earthing, a copper rod of required diameter is used in place of the pipe.
Fill the annular space between the electrode and borehole walls with
alternating layers of coke or charcoal and common salt.
Inspection chamber: Construct brick chamber of size 450 x 450 x 450 mm
with 100 mm thick brick walls over a P.C.C. layer. Keep 100 mm of the
chamber above ground level. Cover the top with a cast iron (CI) cover.
Follow the approved design and drawing for fixing and laying of earth wires
or GI/copper strips between the earth electrode and the electrical room.
239
Comparison between pipe and plate earthing:
Reference:
1. “Principles of Power System” by V.K.Mehta, Rohit Mehta, S Chand & Co Ltd, 2005
2. https://www.google.com/
240
Power Factor- The cosine of angle between voltage and current in an a.c.
circuit is known as power factor. In an a.c. circuit, there is generally a phase
difference φ between voltage and current & the term cos φ is called the power
factor of the circuit.
The 3φ load takes current IL at low lagging power factor cosφL. The
synchronous condenser takes a current Im which leads the voltage by an angle
φm. The resultant current I is the phasor sum of Im and IL and lags behind the
voltage by an angle φ. It is clear that φ is less than φL so that cosφ is greater than
cosφL. Thus the power factor is increased from cosφL to cosφ.
Synchronous condensers are generally used at major bulk supply substations for
power factor improvement.
(3) Phase advancers: Phase advancers are used to improve the power factor of
induction motors. The low power factor of an induction motor is due to the fact
that its stator winding draws exciting current which lags behind the supply
voltage by 90o. If the exciting ampere turns can be provided from some other
a.c. source, then the stator winding will be relieved of exciting current and the
power factor of the motor can be improved. This job is accomplished by the
phase advancer which is simply an a.c. exciter.
243
The phase advancer is mounted on the same shaft as the main motor and is
connected in the rotor circuit of the motor. By providing more ampere turns to
the rotor circuit (at slip frequency) than required, lagging kVAR drawn by the
motor are considerably reduced therefore the induction motor can be made to
operate on leading power factor like an over-excited synchronous motor.
However, the major disadvantage of phase advancers is that they are not
economical for motors below 200 H.P.
kVAR calculation
Consider an inductive load taking a lagging current I at a power factor cos φ1. In
order to improve the power factor of this circuit, the remedy is to connect such
equipment in parallel with the load which takes a leading reactive component
and partly cancels the lagging reactive component of the load. Fig (i) shows a
capacitor connected across the load. The capacitor takes a current IC which leads
the supply voltage V by 90o. The current IC partly cancels the lagging reactive
component of the load current as shown in the phasor diagram in fig. (ii). The
resultant circuit current becomes I′ and its angle of lag is φ2. It is clear that φ2 is
less than φ1so that new p.f. cos φ2 is more than the previous p.f. cos φ1.
244
From the phasor diagram (fig ii), it is clear that after p.f. correction, the lagging
reactive component of the load is reduced to I′sin φ2.
The power factor correction can also be illustrated from power triangle (fig iii).
The power triangle OAB is for the power factor cos φ1, whereas power triangle
OAC is for the improved power factor cos φ2.
Type of compensation
There are mainly two types of compensations carried out in the power system
Load Compensation;
Line Compensation
Load Compensation:
Load compensation is the management of reactive power to improve the quality
of supply especially the voltage and p.f. levels. The reactive power is adjusted
with respect to an individual load and the compensating device is connected to
the load itself. There are three main objectives in Load Compensation: (i) Better
voltage profile (ii) p.f. correction (iii) Load balancing.
(i) Better voltage profile: Variation in voltage occurs due to imbalance in the
generation and consumption of reactive power in the system. If the generated
reactive power is more than consumption, voltage levels go up and vice versa.
The voltage profile must remain within ± 5% of the rated value for better and
efficient operation of various electrical equipments. The reactive power in a
system keeps on varying and hence if the reactive power generation is also
simultaneously controlled, a more or less near flat voltage profile could be
maintained.
In order to minimize the fault, the network should be designed based on active
power transfer capability and the reactive power should be met locally by
installing shunt compensating elements (capacitor and inductors). These
elements do not contribute to the fault level and yet provide and maintain proper
balance between the generated and consumed reactive power.
246
(ii) p.f. correction: It is desirable both economically and technically to operate
the system at near unity p.f. Usually p.f. correction means to generate reactive
power as close as possible to the load which requires it rather than generate it
at a distance and transmit it to the load, as this results not only in large
conductor size but also in increased losses. In fact, in order to operate the
system at near unity p.f., some of the electric utilities impose certain penalty on
account of operating loads at low p.f.
(iii) Load balancing: It is desirable to operate the three phase system under
balanced condition as unbalanced operation results in flow of negative sequence
current in the system and is highly dangerous especially for the rotating
machines. An ideal load compensator would perform the following functions:
Some loads like arc furnaces, induction furnaces, steel rolling mills, very large
induction motors, arc welders, induction welders etc requires load compensator.
The non-linear loads such as arc furnace generate harmonics in the system and
hence arc furnace compensators usually have harmonic filters to filter out these
harmonics, so that the voltage remains mostly of fundamental frequency.
Line Compensation:
Ideal voltage profile for a transmission line is flat, which can only be achieved
by loading the line with its surge impedance loading while this may not be
achievable, the characteristics of the line can be modified by line compensators.
By compensation of lines is meant the use of electrical circuits to modify the
electrical characteristics of the lines such that the compensated lines will
achieve the following objectives:
(i) Ferranti effect is minimized so that a flat voltage profile will exist on
the line for all loading condition.
247
(ii) Under excited operation of alternator will be avoided and an
economical means of reactive power management will be achieved.
(iii) The power transfer capability of the system will be enhanced and
hence stability margins increase.
Flat voltage profile on the line can be achieved if the loading of the line
corresponds to its surge impedance loading. Since in actual practice the actual
load keeps on changing with time, the compensating devices should also vary
without delay so that every time the effective surge impedance matches with
the actual loading i.e., P’c = Vr2 /Z’c = PL where PL is the actual load and Z’c is
the surge impedance compensation.
Under-excited operation of the alternator or charging current problem of the
line can be avoided by dividing the line into shorter sections and this is
known as compensation by sectioning. It is achieved by connecting constant
voltage compensators at intervals along the line. Since the power transmitted
will be same through all sections, the maximum power will be decided by the
smallest section and, therefore, there is increase in power transfer capability
of the system and hence stability limit is increased.
The third aspect of the compensation i.e., to increase power transfer
capability of the system is achieved by inserting capacitor at suitable location
in series with the line so that the net inductive reactance of the line is reduced
which is equivalent to reducing the effective length of the line. This method
of compensation is known as line-length compensation.
Various compensating devices are:
Capacitors: When a number of capacitors are connected in parallel to get
the desired capacitance, it is known as a bank of capacitors. A bank of
capacitors can be adjusted in steps by switching (mechanical).
Capacitors and inductors: Capacitors and inductors as such are passive
line compensators. When solid-state devices are used for switching off
capacitors and inductors, this is regarded as active compensation.
Active voltage source (synchronous generator): synchronous generator is
an active compensator.
248
Series and Shunt Compensation: A device that is connected in parallel
with a transmission line is called a shunt compensator, while a device that is
connected in series with the transmission line is called a series compensator.
These are referred to as compensators since they compensate the reactive power
in the ac system.
The shunt compensator is always connected at the midpoint of
transmission system. The ideal shunt compensator is an ideal current source.
An ideal series compensator is represented by an ideal voltage source. We call
this an ideal series/shunt compensator because we assume that it only supplies
reactive power and no real power to the system.
A static var compensator (SVC) is the first generation shunt compensator. In the
beginning (around 1960) it was used for load compensation such as to provide
var support for large industrial loads. However with the advancement of
semiconductor technology, the SVC started appearing in the transmission
systems in 1970s. Today a large number of SVCs are connected to many
transmission systems all over the world. An SVC is constructed using the
thyristors technology and therefore does not have gate turn off capability.
249
A static compensator or STATCOM contains a synchronous voltage
source (SVS) that is driven from a dc storage capacitor and the SVS is
connected to the ac bus system through an interface transformer. The
transformer steps down the ac system voltage such that the voltage rating of the
SVS switches are within specified limit. A synchronous voltage source (SVS) is
constructed using a voltage source converter (VSC). Such a shunt compensating
device is called STATCOM.
A thyristors controlled series compensator (TCSC) is a thyristors based
series compensator that connects a thyristors controlled reactor (TCR) in
parallel with a fixed capacitor. By varying the firing angle of the anti-parallel
thyristors that are connected in series with a reactor in the TCR, the fundamental
frequency inductive reactance of the TCR can be changed. This effect a change
in the reactance of the TCSC and it can be controlled to produce either inductive
or capacitive reactance.
A static synchronous series compensator or SSSC can be used for series
compensation. An SSSC is an SVS (synchronous voltage source) based device
which contains a voltage source converter (VSC). The VSC is driven by a dc
capacitor. The output of the VSC is connected to a three-phase transformer. The
other end of the transformer is connected in series with the transmission line.
Unlike the TCSC, which changes the impedance of the line, an SSSC injects a
voltage in the line in quadrature with the line current. By making the SSSC
voltage to lead or lag the line current by 90° the SSSC can emulate the behavior
of an inductance or capacitance.
250
It consists of multiple enclosed sections having a common power bus and with
each section containing
A starter
Fuses or circuit breaker
Push buttons
Indicator lights
A motor control center (MCC) also having
Variable-frequency drives
Programmable logic controllers and
Metering equipment.
Motor control centers are usually used for low voltage three-phase alternating
current motors from 208 V to 600 V. Medium-voltage motor control centers are
made for large motors running at 2300 V to around 15000 V, using vacuum
contactors for switching and with separate compartments for power switching
and control.
252
Magnetic Starter: It is designed for remote control of electric motors. It
includes thermal overload relays and electrical interlocks (contactors). Each
relay consists of two closely bonded strips of different alloys with different
temperature coefficients of expansion. When the current flowing through such a
relay exceeds its setting, it heats the bimetal element and makes it bend because
two strips increases its length by different amounts. By bending, the bimetal
element opens the holding coil circuit and thus trips open the starter. The
connection of three pole magnetic starters is shown below which incorporates
two built-in thermal overload relays and one electrical interlock.
253
Motor Control Circuit: One of the most common types of starting method
of squirrel cage induction motor (upto 3.7 kW) is Direct-On-Line starting. In
this method direct switching of three phase squirrel cage induction motor
to supply main is done using push button type direct-on-line starter. The
control circuit and power circuit diagram for DOL starting method is shown
below.
Fig (a) Control Circuit Fig (b) Control circuit with power circuit
The motor is started by pressing push button ‘S’. On pressing the start push
button, contact ‘A’ gets energized and the magnetic action on the iron
pieces lying in the relay will pull auxiliary contactor ‘a’ towards it. Since the
three phase power contactors and auxiliary or relay contactor are
interlocked and mounted on an insulating link, all the four contactors will
be made to move towards their terminals. Thus, the motor gets 3 phase
supply through the contacts of the electromagnetic contactor which are
normally open (NO).
For stopping the motor, OFF push button should be pressed which de-
energized the control circuit. Thus the main contacts through which the
motor was getting supply and also the auxiliary contacts (hold on contact)
get opened. The motor can be restarted again by pressing the start push
button ‘S’. In case of failure of power supply, the contactor becomes de-
energized and the motor stops automatically and will not start on
restoration of power supply.
255
ON STATE
OFF STATE
258
During short circuits, a transient current flowing through the solenoid
forces the plunger towards the latch. This action instantaneous releases the
mechanical latch and opens the contacts immediately. When we switch it
on, we reset the displaced operating latch to its previous on position and
the MCB is ready for another switch off or trip operation.
(https://youtu.be/9Xgn40eGcqY)
Types of MCB:
MCBs are available with different current ratings of 0.5, 1.2, 2.5, 3, 4, 5, 6,
7.5, 10, 16, 20, 25, 32, 35, 40, 63, 100, 125, 160 A and voltage rating of
240/415 V AC and up to 220 V DC. Operating time is very short (less than 5
ms). They are suitable for the protection of important and sophisticated
equipment, such as air-conditioners, refrigerators, computers etc. MCBs are
available in single, two, three and four-pole versions. MCB is also
categorized based on trip current, which is the minimum current at which a
MCB will trip instantaneously.
Trip class Trip Current
CLASS B Above 3 to 5 times rated current. Suitable for cable protection
Above 5 to 10 times the rated current. Suitable Domestic and
CLASS C resiential applications and electromagnetic starting loads with
medium starting currents
Above 10(excluding 10) to 20 times the rated current. Suitable
CLASS D
for inductive and motor loads with high starting currents.
Above 8 to 12 times the rated current. Suitable for inductive
CLASS K
and motor loads with high inrush currents
Above 2 to 3 times the rated current. These types of MCBs are
CLASS Z highly sensitive to short circuit and are used for the protection
of highly sensitive devices such as semiconductor devices.
Reference:
1. “Principles of Power System” by V.K.Mehta, Rohit Mehta, S Chand & Co Ltd, 2005
2. https://www.google.com/
259
DG System
Components of Micro-Grid:
(1) Distributed Generator: is an electric power source connected directly to the
distribution network or on the customer side of the meter to fulfil the power
demand. This DG may be of any rating/size depending upon various factors. Also
it may be either conventional or non-conventional type of power source. Some of
the examples are Wind Power, Solar PV, Solar Thermal, Natural Gas, Bio Gas, Fuel
Cell, Combined Heat & Power, and Micro Turbine.
(2) Load Centre: the power generated from distributed generator shall be
distributed to the load centre for the utilization.
(3) Electric Power Storage: Microgrid can have storage as backup while operating
in stand-alone mode of operation. When there is renewable source of power,
excess power from renewable (after the load demand is fulfilled), can be stored
in batteries. This can then be used as backup when needed. Therefore, the
electric power storage in microgrid is able to improve the power quality,
flexibility and reliability by providing grid support functions. The electric power
storage system may be classified as Electrochemical: Battery (Lead Acid, Li-ion);
Electromagnetic: Super Capacitor, Super Conductor; Mechanical: Pumped
Hydro, Compressed Air, Flywheel; Chemical: Hydrogen, Synthetic Natural Gas;
and Thermal: Water Tank.
(4) Controller: Control unit is one of major component of microgrid. The flow of
power from generation to the load centers should be monitored, controlled and
managed properly. Even before, the generation of electric power must have
controller to maintain power quality (voltage, frequency and sin wave within
limit).
(5) Point of common coupling: A micro-grid can be connected or disconnected
from the grid to enable it to operate from either disconnected or islanded mode
thus preventing power outage. It may be connected or disconnected from point
of common coupling, which is basically a power electronic interface.
261
DG
1 Watt to 5 kW to 5 5 MW to 50 MW to
5 kW MW 50 MW 300 MW
Classification from electrical point of view: This will help to study their
impact on the electric system. Different classifications can be obtained to
differentiate between DG types according to their electrical applications,
262
supply duration, generated power types, electric ratings and renewable and
non-renewable technologies. Several types of DG classification are
mentioned below:
(i) Standby: DG can be used as a standby to supply the required power
for sensitive loads, such as process industries and hospitals, during
grid outages.
(ii) Stand alone: Usually, isolated areas use DGs as a power provider
instead of connecting to the grid. These areas have geographical
obstacles, which make it expensive to be connected to the grid.
(iii) Peak load shaving: The electric power cost varies according to the
load demand curves and the corresponding available generation at
the same time. Hence, DGs can be used to supply some loads at peak
periods, which reduce the electricity cost for large industrial
customers who used to pay time-of-use rates (TOU).
(iv) Rural and remote applications: DG can provide the stand-alone
remote applications with the required power. These applications
include lighting, heating, cooling, communication, and small
industrial processes. Even more, DGs can support and regulate the
system voltage at rural applications (sensitive loads) connected to the
grid.
(v) Providing combined heat and power (CHP): DGs providing CHP as a
cogeneration has a high overall energy utilization efficiency. The
produced heat, from converting fuel into electric power process, is
used onsite for a wide range of applications in hospitals, large
commercial areas and process industries.
(vi) Base load: Utility owned-DGs are usually used as a base load to
provide part of the main required power and support the grid by
enhancing the system voltage profile, reducing the power losses and
improving the system power quality.
DG
Non-Fossil
Fossil Fuels
Fuels
Technology
Technology
(iv) Cooling system: The heat released by the burning of fuel in the engine cylinder is
partially converted into work. The remainder part of the heat passes through the
cylinder walls, piston, rings etc. and may cause damage to the system. In order to keep
the temperature of the engine parts within the safe operating limits, cooling is provided.
The cooling system consists of a water source, pump and cooling towers. The pump
267
circulates water through cylinder and head jacket. The water takes away heat form the
engine and itself becomes hot. The hot water is cooled by cooling towers and is
recirculated for cooling.
(v) Lubricating system: This system minimizes the wear of rubbing surfaces of the
engine. It comprises of lubricating oil tank, pump, filter and oil cooler. The lubricating oil
is drawn from the lubricating oil tank by the pump and is passed through filters to
remove impurities. The clean lubricating oil is delivered to the points which require
lubrication. The oil coolers incorporated in the system keep the temperature of the oil
low.
(vi) Engine starting system: This is an arrangement to rotate the engine initially, while
starting, until firing starts and the unit runs with its own power. Small sets are started
manually by handles but for larger units, compressed air is used for starting. In the
latter case, air at high pressure is admitted to a few of the cylinders, making them to act
as reciprocating air motors to turn over the engine shaft. The fuel is admitted to the
remaining cylinders which makes the engine to start under its own power.
(vii) Alternator: Alternator is salient pole type synchronous generator, self excited and
self regulated by an excitation unit. The excitation unit consists of choke, CT, diodes and
condenser. Voltage is adjustable to within 2.5% of the nominal voltage from no-load to
full load at rated pf. The choke is meant for adjusting the terminal voltage at no load. The
CT is meant for adjusting the terminal voltage at load condition.
268
Sizing of a DG Set
(a) If the DG set is required for 100% standby, then the entire connected load in HP /
kVA should be added. After finding out the diversity factor, the correct capacity of a DG
set can be found out.
Example :
Connected Load = 650 kW
Diversity Factor = 0.54
(Demand / connected load)
Max. Demand = 650 x 0.54 = 350 kW
% Loading = 70
Set rating = 350/0.7 = 500 kW
At 0.8 PF, rating = 625 kVA
(b) For an existing installation, record the current, voltage and power factors (kWh /
kVAh) reading at the main bus-bar of the system at every half-an-hour interval for a
period of 2–3 days and during this period the factory should be having its normal
operations. The non-essential loads should be switched off to find the realistic current
taken for running essential equipment. This will give a fair idea about the current taken
from which the rating of the set can be calculated.
(c) For a new installation, an approximate method of estimating the capacity of a DG set
is to add full load currents of all the proposed loads to be run in DG set. Then, applying a
diversity factor depending on the industry, process involved and guidelines obtained
from other similar units, correct capacity can be arrived at.
Reference:
1. Distributed generation: a definition, Thomas Ackermann, Goran Andersson,
Lennart Soder, Electric Power Systems Research 57 (2001) 195–204, 05
December 2000
2. “Principles of Power System” by V.K.Mehta, Rohit Mehta, S Chand & Co Ltd, 2005
3. https://www.google.com/
269
(i) Standby UPS/Offline UPS: It is the most common type of UPS system used
on a day to day basis for our personal and office computers.
Design: Here, the primary source is the filtered AC mains. The input line
voltage is routed through a surge suppressor, filter, and transfer switch
before finally being routed to the output of the UPS device.
Fig 5: (a) 12V, 18AH, VRLA Gel Type Battery (b) Battery Bank
Most commonly used batteries (at home for UPS) are usually of the sealed
lead acid or gel cell type which prevents spilling of any dangerous and
harmful chemicals from inside the battery into the UPS device itself. If the
acids from inside the battery leaked out into the device cabinet they would
destroy the electronic components inside the system rendering it useless.
274
Other than the internal make up of the battery they can differ in two other
ways.
The first is the actual physical size of the battery. Most are shaped like
the battery in figure 5 above, but the dimensions of length, width, and
height can be almost any combination.
Another key specification of the battery is its current capacity. This is
usually rated in milliamp-hours/amp-hours. The amp hour rating tells
the amount of current the battery will supply in an hour. Example: If
the current capacity of a battery is 20 amp hour and the load is drawing
0.5 amps then this battery is able to supply its rated voltage to the load
for 40 hours.
Three stages of the battery charging is: (i) Normal or Bulk stage (ii)
Absorption/Equalization stage and (iii) Float stage.
Bulk/ Normal stage: It is the initial portion of a charging cycle performed
at any charge rate and it involves 80 % state of charge, hence called bulk
stage of charging. In this case the charger current is held constant (in a
constant current charger), and voltage increases. The properly sized
charger will give the battery as much current as it will accept up to charger
capacity.
Absorption/Equalization stage: The absorption/equalization has the
charger holding the voltage and decreasing the current until the battery is
charged nearly up to 95-97%. The portion of charging cycle covered in this
stage is called “cool-down” cycle.
276
Float Stage: The float stage is where the charge voltage is reduced and held
constant, while the current is reduced to less than 1% of battery capacity
(i.e supplying steady current). This mode can be used to maintain a fully
charged battery indefinitely. At that time, the charger will continue to
monitor the battery and apply a charge if it detects any loss.
Battery Discharging
Depth of Discharge (DOD): It is defined as the percentage of capacity that
has been withdrawn from a battery compared to the total fully charged
capacity. OR, Depth of Discharge is defined as the total amount of energy
that is discharged from a battery, divided by the battery nominal capacity.
Depth of discharge is normally expressed as a percentage.
Example: If a 90 Ah battery is discharged for 20 minute at a constant
current of 50 A, then find the value of depth of discharge.
Ans: DoD = (50 amps * (20 mins / 60 mins) / 90Ah
= (50A * 0.33333h)) / 90Ah
= 16.67Ah / 90Ah = 0.18522 can be written as 18.522%
277
State of Charge (SOC): The state of charge (SOC) is defined as the amount
of energy as a percentage of the energy stored in a fully charged battery.
Discharging a battery results in a decrease in state of charge, while charging
results in an increase in state of charge. Ex: If a battery that has had three
quarters of its capacity removed, or been discharged 75 %, is said to be at
25 % state of charge.
Geared Machine:
It used in low and mid rise applications. This design utilizes a
mechanical speed reduction gear set to reduce the rpm of the drive
motor (input speed) to suit the required speed of the drive sheave and
elevator (output speed).
Generally, geared machines are used for speeds between 0.1 m/s and
2.5 m/s and are suitable for loads from 5 Kg up to 50,000 Kg and above.
Their sizes and shapes vary with load, speed and manufacture but the
underlying principles and components are the same.
288
Main Component of Machine Drive System:
Electrical Motor: Electrical Motor is used to raise and lower the elevator
cab, the direction of motor rotation and speed (revolutions per minute) are
directed and supervised by devices located within the elevator controller,
The motor component of the elevator machine can be either a DC motor or
an AC motor as follows:
…………………………………………………………………………………………………
PLCs are widely used in a variety of industries because they’re fast, easy to
operate and are considered easy to program. PLCs can be programmed in
several ways, from ladder logic, which is based on electromechanical relays, to
specially adapted programming languages of BASIC and C. Most PLCs today
use one of the following 5 programming languages: Ladder Diagram, Structured
Text, Function Block Diagram, Instruction List, or Sequential Function Charts.
PLC act as the physical interfaces between device on the plant or manufacturing
floor and a SCADA system. PLCs communicate, monitor and control automated
processes like assembly lines, machine functions, or robotic devices.
Programming the PLC is easier than wiring physical components; the only
wiring required is that of connecting the I/O terminals.
291
The PLC can be reprogrammed using user-friendly programming devices.
Controls must be physically rewired.
PLCs take up much less space.
Installation and maintenance of PLCs is easier, and in present day reliability
is grater compared with solid-state technology.
The PLC can be connected to a distributed plant automation system,
supervised and monitored.
Ability of PLCs to accept digital data in serial, parallel and network modes
imply a drastic reduction in plant sensor and actuator wirings, since single
cable runs to remote terminal I/O units can be made. Wiring only need to be
made locally from that point
Application of PLC:
Logic/Sequence control
PID control and computing
Coordination and communication
Operator control and monitoring
Plant start-up, shut-down
A PLC’s functions are divided into three main categories: inputs, outputs and the CPU. PLCs
capture data from the plant floor by monitoring inputs that machines and devices are
connected to. The input data is then processed by the CPU, which applies logic to the data,
based on the input state. The CPU then executes the user-created program logic and outputs
data or commands to the machines and devices it is connected to.
293
Central Processing units
The CPUs are generally micro programmed processors sometimes capable of handling
multiple data width of either 8, 16 or 24 bits. In addition sometimes additional circuitry is
provided, since much of the computing involves logical operations involving digital inputs
and auxiliary quantities. Memory with battery backup is also provided for the following:
A. Direct program entry to the program memory (RAM) plugged into the central controller.
For this purpose, the programmer is connected to the processor or to the programmer
interface modules.
B. Programming the EPROM sub modules in the programmer without connecting it to the PC
(off-line). The memory sub modules are then plugged into the central controller.
Other units such as Power Supply Units (mainly 24 V DC), Bus Units etc. can also be
connected to the PLC system.
PLCs operate in cycles. First, the PLC detects the state of all input devices that are connected
to it. The PLC applies the user-created logic, and then executes it based on the input
states. The PLC then outputs commands to any output device connected to the PLC either
turning them on or off. The PLC resumes the cycle each time the process is completed.
295
Need of programmable logic controller (PLC) in automation:
1. PLCs are similar to industrial computers. PLCs can work as standalone units that can
continuously monitor and automate a process. PLCs can be networked; such a network can
control an entire production line. PLCs can be adapted to monitor and control many sensors
and actuators; they process electrical signals and use them to carry out preprogrammed
commands for almost any application. PLCs are used in industrial automation to increase
reliability, system stability and performance, minimizing the need for human operators and
the chances of human error.
2. PLC is used in the fully automated industries or plants or process, the actual processes
handled and controlled by the controllers which are nothing but the programming logic
controllers that means PLC plays a very important role in automation section.
2. PLCs constantly monitor the state of the systems through input devices and generate the
control actions according to the logic given in the user program.
3. It is a heart of control systems, PLC monitors the state of the system through field input
devices, feedback signals and based on the feedback signal PLC determine the type of action
to be carried out at field output devices.
4. PLC provides easy and economic solution for many automation tasks like
Operates control and monitoring
Co-ordination and communication
PID computing and control
Logic / sequence control
Industrial Automation
Industrial Automation is a process of operating machines and other industrial equipment with
the help of digital logical programming and reducing human intervention in decision making
and manual command process with the help of mechanized equipment. The automation
process typically uses devices such as PLCs, PCs, PACs, etc. and various types of industrial
communication technologies.
Some of the examples of automated industrial processes are:
Packaging and material handling
Quality control and inspection
Metal fabrication; machining, welding, cutting, cladding etc.
Food and beverage processing
Planning and decision making
296
Industrial Automation Advantages
Reduction in production time – having a machine that is automated definitely speeds
up the production time since no thinking is needed by the machine; there is better
repeatability, and less human error.
Increase in accuracy and repeatability – when an automated machine is programmed
to perform a task over and over again, the accuracy and repeatability compared to an
employee is far greater.
Less human error – no one is perfect, and we are all prone to making mistakes. Which
is why a machine that performs repeated tasks is less likely to make mistakes than an
employee?
Less employee costs – by adding automated machines to an operation, means less
employees are needed to get the job done. It also indicates less safety issues, which
leads to financial savings. With having less employees, there are numerous costs that
are diminished or reduced such as payroll, benefits, sick days, etcetera.
Increased safety – having automated machines means having fewer employees who
perform tasks that can be dangerous and prone to injury, which can make the work
environment safer.
Higher volume production – investing in automated equipment creates a valuable
resource for large production volumes, which in turn, will increase profitability.
297
Nowadays, computer control is one of the most cost effective solutions for improving
reliability, optimum operation, intelligent control and protection of a power system
network. Having advanced data collection capabilities, SCADA system plays a
significant role in power system operation.
Typically, at distribution side SCADA does more than simply collecting data by
automating entire distribution network and facilitating remote monitoring, coordinate,
control and operating distribution components just like in Smart Grid System.
SCADA (Supervisory Control and Data Acquisition)
Supervisory control is a general term for control of many individual controllers or
control loops, such as within a distributed control system. It refers to a high level of
overall monitoring of individual process controllers, and allows integration of operation
between controllers.
Data Acquisition (DAQ) is the process of sampling signals that measure real world
physical conditions and converting the resulting samples into digital numeric values
that can be manipulated by a computer. The components of data acquisition systems
include:
Sensors, to convert physical parameters to electrical signals.
Signal conditioning circuitry, to convert sensor signals into a form that can be
converted to digital values.
Analog-to-digital converters, to convert conditioned sensor signals to digital values.
In this system, measurements are made under field or process level in a plant by
number of remote terminal units and then data are transferred/communicated to the
SCADA central host computer so that more complete process or manufacturing
information can be provided remotely.
RTU Vs PLC
“RTU” stands for “Remote Terminal Units.” It is also referred to as “Remote Telemetry
Unit”; “PLC” stands for “programmable logic controller.”
RTUs are considered more suitable for wider geographical telemetry, the reason being
that RTUs use wireless communication; PLCs are more suitable for local control, for
example, for assembly lines in factories, light fixtures, amusement rides, etc. PLCs are
specially designed for output arrangements and multiple inputs.
300
The central control or master unit receives and logs the information, displays on HMI
and generate the control actions based on received data. This central controller also
responsible for generating trend analysis, centralized alarming, and reporting.
The data historian, workstations, master terminal unit and communications servers are
connected by LAN at the control center. A Wide Area Network (WAN) connection with
standard protocol communication is used to transfer the information between field sites
and central controller.
Thus, by implementing SCADA for substation control eventually improves the reliability
of the network and minimizes the downtime with high speed transfer of measurements
and control commands.