Acoustic Canopy

Applications Notes
ISTIQ ACOUSTIC CANOPY is designed to comply to the
DOE regulation. The canopy are equipped with Discharge,
Intake and Exhaust silencers. The noise level is designed to
achieved 70 to 75 dB(A) measured at 3 meter away.
In selecting a silencer for a canopy, a balance between
noise reduction, pressure drop and heat rejection need
to be calculated cautiously By using internally developed
software, ISTIQ NOISE CONTROL can help to make the
right choice quickly and most importantly, accurately.
Introduction
Canopy application for housing a generator set has gaining its popularity over the years. This is due to a portability
of the set to be from one place to another and furthermore the cost for housing a generator set is cheaper as
compare to a normal concrete house.

Construction
T internal construction of the canopy panel uses only rockwool and protected with
The
perforated G.I. This construction has proven to be the most cost effective in the long
run.
ISTIQ NOISE CONTROL has developed the modular system panel which provides great
fflexibility at low cost. The panel are standard 65mm thickness, formed from 2.3mm
mild steel, inert acoustic infill and galvanised perforated inner sheet steel. The finest
quality materials and workmanship ensure that a final solution gives the best in noise
control without affecting airflow, operation, maintenance or inspection.
Exhaust pipe which is inside the canopy must be insulated to avoid overheating
problem. The exhaust lagging is done by using rockwool as thermal insulation wrapped
with aluminium jacketing.
w
Fuel tank is located at the base frame. The designed therefore will serve dual purposes - acting as a supporting
base and fuel tank. The body and the base can be separated for maintenance (genset overhaul) in the future.
Windows, exhaust penetrations, radiators and electrical cables, fitting and fixtures are all standard.

Standard Material Specification


a) Outer casing 2.3mm thk. M.S Plate
b) Inner casing 0.4mm thk. Perf G.I
c) Percentage of perforation 30% to 40%
d) Panel thickness 65mm thk.
e) Frame and support 2.3 - 3.2mm M.S Hollow Section
f) Acoustic Infill 40kg/m3 density Rockwool
g) Rockwool Thermal Conductivity 0.034 W/mK at 20 deg C
h) Observation Panel 5mm thk transparent plexiglass
i) Glass panel rubber 14 ‘L Normal type
j) Lock set Slam Paddle with Lock
k) Door hinges Lift-Off Flag Hinge
l) Acoustic Seal Rubber c/w magnetic seal
m) Painting One coat primer and two coats finishing

pg. 01 Acoustic Canopy


Standard Canopy Dimensions
Rating
kVA A B C D E E1 F G G1
40 1000 2500 1350 150 700 800 450 200 1000
56 1000 2500 1350 150 700 800 450 200 1000
66 1000 2500 1350 150 700 800 450 200 1000
90 300 3800 1700 150 900 1000 550 250 1200
110 1300 3800 1700 150 900 1000 550 250 1200
147 1300 3800 1700 150 900 1000 550 250 1200
212 1500 4300 2000 200 900 1200 600 300 1500
253 1500 4300 2000 200 900 1200 600 300 1500
281 1500 4300 2000 200 900 1200 600 300 1500
313 1500 4300 2000 200 900 1200 600 300 1500
330 1500 4300 2300 250 1000 1200 600 300 1800
345 1500 4300 2300 250 1000 1200 600 300 1800
390 1500 4300 2300 250 1000 1200 600 300 1800
416 1800 5100 2300 250 1000 1200 900 450 1800
500 1800 5100 2300 250 1000 1200 900 450 1800
562 1800 5100 2300 250 1000 1200 900 450 1800