MDB Report With Generator Feeding

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Customer: M/S ABC ELECTRICALS

Project: TOWER-1
Notes: MDB SS1

Designer:

Rev. n°1 Date: Calculated by: DOC


Rev. n°2 Drafter:
Design.: File name:
Rev. n°3
REVISIONS Date: Signatures Approval: Record #:
Calculation and dimensioning criteria

Calculation method-standard IEC 60909-1

Standard for cable dimensioning IEC 60364

Overload Overload verifications are made according the following relations: IB <= In <= Iz and I2 <= 1.45*Iz

Legenda:

IB = the current for which the circuit is designed

In = nominal current of the protective device (For adjustable protective devices, the nominal current In is the current setting selected)

I2 = current ensuring effective operation in the conventional time of the protective device

Iz = cable carrying capacity according the chosen standard

Short Circuit Circuit breakers and fuses are dimensioned with a breaking capacity higher than the maximum short circuit current in the point of installation

Circuit breakers dimensioned according to IEC 60497-2 are also chosen with the making capacity Icm higher than the maxiimum peak current

The protection against short circuit must satisfy the rule I²t <= K²S²

Legenda:

I²t = let-through energy at the maximum short circuit current (defined by the producer)

S = section of the conductors

K = factor defined in IEC60364-4-43 table 43A and IEC60364-5-54 tables A.54.2, A.54.4 and A-54.5

Indirect contact TT systems: the verification is Idn * Ra <= Vo, or Im <= Ib min

TN systems: the verification is Im <= Ib min

Legenda:

Idn = sensitivity of the residual current device

Ra = earthing resistance

Uo = max admitted contact voltage

Im = tripping value of the protective device at time limit

Ib min = minimum short circuit current at line end

Discrimination and Back-up The discrimination and back-up values are determined by the producer with laboratory tests

Discrimination required in the installation (see indications on the single-line and the Discrimination report

Backup not required in the installation

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short-circuit calculation hypothesis for IEC 60909-0

Calculation algorithm

The calculation of maximum and minimum, balanced and unbalanced, short-circuit currents is made by application of symmetrical components.

General conditions

The calculation of maximum and minimum short-circuit currents is based on the following simplifications.

a) For the duration of the short circuit, there is no change in the type of short circuit involved (a three-phase short circuit remains three-phase)

b) For the duration of the short circuit, there is no change in the network involved.

c) The impedance of the transformers is referred to the tap-changer in main position.

d) Arc resistances are not taken into account.

e) All line capacitances and shunt admittances and non-rotating loads, except those of the zero-sequence system, are neglected.

Maximum short-circuit currents

In the calculation of maximum short-circuit currents, the following conditions have been considered:

- it is applied the voltage factor cmax according to table 1, IEC 60909-0

- it is chosen the network configuration which leads to the maximum value of short-circuit current at the short-circuit location

- the contribution of asynchronous motors is considered if their contribution is higher than 5% of the initial short-circuit current calculated without motors

- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 20°C

Minimum short-circuit currents

In the calculation of minimum short-circuit currents, the following conditions have been considered:

- it is applied the voltage factor cmin according to table 1, IEC 60909-0

- it is chosen the network confguration which lead to the minimum value of short-circuit current at the short-circuit location

- the contribution of asynchronous motors is neglected

- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 250°C (EPR),160°C (PVC) or 140°C PVC >300m²)

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Un [V] 11000
Ik LLL [kA] 18.4 OFF -G1
P [kW] 
-QF1
Salient pole generator (4 poles) 400V 1000kVA G
Q [kvar] 1VCF338184R0132 LLLN / TN-S
A
VD4/UniMix-R 24.06.20 P230 Un = 400 V
KECA250B1 (80A)
<none> Sn = 1000 kVA
REF601 CEI 0-16 P = 725.7 kW
Q = 232.8 kvar

  
-WC2 -WC3 -WC32
MV CABLE TR-1 GENERATOR INCOMER
3x120/16 11x(1x630)+2G240 8x(1x630)+2G240
Iz = 255.0 A Iz = 2742.4 A Ib = 1113.5 A
du = 0.00 dV = 0.27 % Iz = 2094.8 A
L = 15 m L = 20 m dV = 0.26 %
B L = 20 m
 OFF
-TM1  
TR-1 -QF2 -QF38
Un2 = 400 V E2.2N 2500 Ekip Dip LSIG 2500 E1.2C 1600 Ekip Dip LSIG 1600
Sn = 1600 kVA LV INCOMER GENERATOR INCOMER
Sec.: LLLN / TN-S *

-B1
MDB
FU = 1.00
C U=399.0 V
IB = 1113.5 A
   Cosphi = 0.95
-QF3 -QF4 -QF9 Ik max = 3.4 kA
T4S 320 PR221DS-LS/I 320A E1.2C 1000 Ekip Dip LSIG 1000 T5S 630 PR222DS-LSI 630A Ik LLL = 3.2 kA
* SMDB MCC
* *

D
     
-WC4 -BW1 -BW2 -BW3 -BW4 -WC9
3x(1x240)+1x(1x120)+1G120 1600A Cu Busway 1600A Cu Busway 1600A Cu Busway 1600A Cu Busway MCC
Ib = 176.7 A SMDB SMDB-F1 SMDB-F2 SMDB-F3 2x 5G240/120
Iz = 346.0 A L = 54 m L=5m L=5m L=5m Ib = 257.0 A
dV = 0.06 % du = 1.09 du = 0.09 du = 0.06 du = 0.04 Iz = 581.3 A
L = 10 m IB = 922.3 A IB = 786.6 A IB = 582.1 A IB = 327.2 A dV = 0.73 %
Iz = 1600.0 A Iz = 1600.0 A Iz = 1600.0 A Iz = 1600.0 A L = 120 m
2
     MCC
-C1 -QF5 -QF6 -QF7 -QF8
Sn = 122.45 kVA XT4N 250 Ekip LSI R250 XT4N 250 Ekip LS/I R250 T4N 320 PR221DS-LS/I 320A T5N 400 PR221DS-LS/I 400A
Q = 122.20 kvar SMDB SMDB-F1 SMDB-F2 SMDB-F3
IB = 176.7 A * * * *
E

(*) The circuit-breaker is in discrimination relations with other circuit-breakers


(!) Important notice about coordination to be verified in Discrimination report
(**) The circuit-breaker is in back-up relations with other circuit-breakers
   
-WC5 -WC6 -WC7 -WC8
SMDB SMDB-F1 SMDB-F2 SMDB-F3
5G50/25 5G95/50 5G120/70 5G150/95
Ib = 135.7 A Ib = 204.5 A Ib = 254.9 A Ib = 327.2 A
Iz = 192.0 A Iz = 272.0 A Iz = 315.9 A Iz = 399.0 A
dV = 0.17 % dV = 0.11 % dV = 0.11 % dV = 0.12 %
F L=7m L=5m L=5m L=5m
1
SMDB   
-L2 -L3 -L4
SMDB-F1 SMDB-F2 SMDB-F3
Sn = 166.67 [kVA] Sn = 207.78 [kVA] Sn = 266.67 [kVA]
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90
In = 240.6 [A] In = 299.9 [A] In = 384.9 [A]
U = 393.8 [V] U = 393.6 [V] U = 393.4 [V]
dU = 1.54 % dU = 1.61 % dU = 1.65 %
P = 125.56 [kW] P = 156.42 [kW] P = 200.67 [kW]
Q = 60.81 [kvar] Q = 75.76 [kvar] Q = 97.19 [kvar]

G
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2
SMDB MCC

A
 
-QS1 -QF14
SMDB T5N 630 TMA500-5000
MCC
*
-B3
MCC
FU = 1.00
U=396.0 V
IB = 257.0 A
Cosphi = 0.90
-B2 Ik max = 3.2 kA
SMDB Ik LLL = 3.2 kA
FU = 1.00
B U=393.9 V
IB = 135.7 A
    Cosphi = 0.90      
-QF10 -QF11 -QF12 -QF13 Ik max = 3.2 kA -QF15 -QF16 -QF17 -QF19 -QF21 -QF23
XT2N 160 Ekip LS/I R160 XT2N 160 TMD 32-320 XT2N 160 TMD 32-320 XT2N 160 TMD 32-320
Ik LLL = 3.2 kA XT2N 160 TMA 160-1600 XT2N 160 TMA 80-800 XT4N 160 Ekip LSI R40 XT2N 160 MA 52 Im=314...728 XT2N 160 MF 8,5 Im=120 XT2N 160 MF 4 Im=56
DB DB-G2 DB-G3 DB-G4 CHWP-1 CHWP-2 CHWP-3 MW PUMP IRRIGATION PUMP WATER PUMP
* * * * * * *

C
  
-WC14 -WC15 -WC16
CHWP-1 CHWP-2 CHWP-3
5G95/50 5G50/25 5G16   
    Ib = 106.0 A Ib = 73.0 A Ib = 32.0 A -K1 -K2 -K3
-WC10 -WC11 -WC12 -WC13 Iz = 258.1 A Iz = 166.3 A Iz = 86.6 A
DB DB-G2 DB-G3 DB-G4 dV = 0.36 % dV = 0.57 % dV = 0.90 %
5G150 5G16 5G16 5G16 L = 35 m L = 45 m L = 55 m   
Ib = 58.7 A Ib = 28.9 A Ib = 22.5 A Ib = 25.7 A -FR18 -FR20 -FR22
Iz = 364.2 A Iz = 100.0 A Iz = 100.0 A Iz = 100.0 A
dV = 0.16 % dV = 0.50 % dV = 0.49 % dV = 0.63 %
L = 40 m L = 35 m L = 45 m L = 50 m
3 f2 f2 f2
DB   
-L6 -L7 -L8
D DB-G2 DB-G3 DB-G4   
Sn = 20.00 [kVA] Sn = 15.56 [kVA] Sn = 17.78 [kVA] -DS9 -DS10 -DS11   
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 CHWP-1 CHWP-2 CHWP-3 -WC17 -WC18 -WC19
In = 28.9 [A] In = 22.5 [A] In = 25.7 [A] Sn = 73.44 kVA Sn = 50.58 kVA Sn = 22.17 kVA MW PUMP IRRIGATION PUMP WATER PUMP
U = 391.9 [V] U = 391.9 [V] U = 391.4 [V] M Cosphi = 0.90 M Cosphi = 0.90 M Cosphi = 0.90 4G25/16 4G6/6 4G6/6
dU = 2.02 % dU = 2.02 % dU = 2.15 % In = 106.0 A In = 73.0 A In = 32.0 A IB = 38.4 A IB = 4.5 A IB = 3.1 A
P = 17.64 [kW] P = 13.72 [kW] P = 15.66 [kW] I1 act = 64.2 A I1 act = 44.5 A I1 act = 18.7 A Iz = 127.0 A Iz = 54.0 A Iz = 54.0 A
Q = 8.54 [kvar] Q = 6.65 [kvar] Q = 7.59 [kvar] P = 55.0 kW P = 37.0 kW P = 15.0 kW du = 0.36 du = 0.11 du = 0.06
Pn = 75.0 kW Pn = 45.0 kW Pn = 18.5 kW L = 30 m L = 20 m L = 15 m
In = 130.0 A In = 80.2 A In = 34.5 A M2BA 180 M - 22 kW  
Rpm = 1487 Rpm = 1482 Rpm = 1477 M2BA 90 L2 A - 2,2 kW M2BA 90 S2 A - 1,5 kW
FU = 100% FU = 100% FU = 100% M MW PUMP
M IRRIGATION PUMP M WATER PUMP
dV = 1.36 % dV = 1.56 % dV = 1.89 % YD Un = 400 V Un = 400 V Un = 400 V
Pn = 22.00 kW Pn = 2.20 kW Pn = 1.50 kW
du = 1.36 du = 1.10 du = 1.05
E

(*) The circuit-breaker is in discrimination relations with other circuit-breakers


(!) Important notice about coordination to be verified in Discrimination report
(**) The circuit-breaker is in back-up relations with other circuit-breakers
F

G
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

3
DB

A

-QS2
DB

-B4
FINAL DB
FU = 1.00
B U=393.3 V
IB = 58.7 A
  Cosphi = 0.90
-QD24 -QD31 Ik max = 3.0 kA
F204 AC-40/0,1 F204 AC-63/0,03 Ik LLL = 2.8 kA
RCCB-1 RCCB-2

I d I d
-B7
U=393.3 V
-B6 IB = 40.5 A
U=393.3 V Cosphi = 0.90
IB = 18.8 A Ik max = 3.0 kA
Cosphi = 0.90 Ik LLL = 2.8 kA
Ik max = 3.0 kA
C Ik LLL = 2.8 kA

           
-QF25 -QF26 -QF27 -QF28 -QF29 -QF30 -QF32 -QF33 -QF34 -QF35 -QF36 -QF37
S201-C16 S201-C16 S201-C10 S201-C10 S201-C10 S201-C6 S201-C16 S201-C20 S201-C16 S201-C16 S201-C50 S201-C20
LIGHT-1 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 SOCKET-1 SOCKET-2 SOCKET-3 SOCKET-4 SOCKET-5 SOCKET-6
* * * * * * * * * * * *

           
-WC20 -WC21 -WC22 -WC23 -WC24 -WC25 -WC26 -WC27 -WC28 -WC29 -WC30 -WC31
LIGHT-1 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 SOCKET-1 SOCKET-2 SOCKET-3 SOCKET-4 SOCKET-5 SOCKET-6
2x(1x6)+1G6 2x(1x16)+1G16 2x(1x6)+1G6 2x(1x4)+1G4 2x(1x6)+1G6 2x(1x4)+1G4 2x(1x6)+1G6 2x(1x10)+1G10 2x(1x6)+1G6 2x(1x16)+1G16 2x(1x10)+1G10 2x(1x6)+1G6
IB = 13.0 A IB = 12.3 A IB = 8.7 A IB = 6.5 A IB = 8.7 A IB = 5.2 A IB = 13.0 A IB = 14.3 A IB = 12.3 A IB = 10.2 A IB = 14.3 A IB = 17.3 A
Iz = 43.7 A Iz = 69.9 A Iz = 43.7 A Iz = 34.2 A Iz = 43.7 A Iz = 34.2 A Iz = 43.7 A Iz = 59.8 A Iz = 46.0 A Iz = 80.8 A Iz = 57.0 A Iz = 43.7 A
du = 0.51 du = 0.23 du = 0.40 du = 0.45 du = 0.40 du = 0.36 du = 0.51 du = 0.41 du = 0.63 du = 0.41 du = 0.22 du = 0.36
L = 15 m L = 18 m L = 18 m L = 18 m L = 18 m L = 18 m L = 15 m L = 18 m L = 20 m L = 40 m L = 10 m L=8m

E
   
-L12    -L18   

(*) The circuit-breaker is in discrimination relations with other circuit-breakers


-L16  -L22 

(!) Important notice about coordination to be verified in Discrimination report


LIGHT-1 -L13 -L14 -L15 SOCKET-1 -L19 -L20 -L21
Sn = 3.33 [kVA] LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 -L17 Sn = 3.33 [kVA] SOCKET-2 SOCKET-3 SOCKET-4 SOCKET-5 -L23

(**) The circuit-breaker is in back-up relations with other circuit-breakers


Cosphi (nominal) = 0.90 Sn = 3.33 [kVA] Sn = 2.22 [kVA] Sn = 1.67 [kVA] Sn = 2.22 [kVA] LIGHT-5 Cosphi (nominal) = 0.90 Sn = 3.89 [kVA] Sn = 3.33 [kVA] Sn = 2.78 [kVA] Sn = 3.89 [kVA] SOCKET-6
In = 14.4 [A] Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Sn = 1.33 [kVA] In = 14.4 [A] Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Sn = 4.44 [kVA]
U = 225.9 [V] In = 14.4 [A] In = 9.6 [A] In = 7.2 [A] In = 9.6 [A] Cosphi (nominal) = 0.90 U = 225.9 [V] In = 16.8 [A] In = 14.4 [A] In = 12.0 [A] In = 16.8 [A] Cosphi (nominal) = 0.90
dU = 2.18 % U = 226.7 [V] U = 226.5 [V] U = 226.2 [V] U = 226.5 [V] In = 5.8 [A] dU = 2.18 % U = 226.3 [V] U = 225.8 [V] U = 226.1 [V] U = 226.9 [V] In = 19.2 [A]
P = 2.64 [kW] dU = 1.83 % dU = 1.93 % dU = 2.05 % dU = 1.93 % U = 226.2 [V] P = 2.64 [kW] dU = 2.01 % dU = 2.23 % dU = 2.09 % dU = 1.75 % U = 226.2 [V]
Q = 1.28 [kvar] P = 2.50 [kW] P = 1.77 [kW] P = 1.32 [kW] P = 1.77 [kW] dU = 2.04 % Q = 1.28 [kvar] P = 2.92 [kW] P = 2.49 [kW] P = 2.08 [kW] P = 2.92 [kW] dU = 2.04 %
Q = 1.21 [kvar] Q = 0.85 [kvar] Q = 0.64 [kvar] Q = 0.85 [kvar] P = 1.06 [kW] Q = 1.41 [kvar] Q = 1.21 [kvar] Q = 1.01 [kvar] Q = 1.42 [kvar] P = 3.53 [kW]
Q = 0.51 [kvar] Q = 1.71 [kvar]

G
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 3
Distribution

Reference voltage [V] 11000 Symmetrical short circuit current LLL [kA] 18.37
Phases LLL Line-Neutral short circuit current LN [kA]
Distribution system IT Line-Ground short circuit current LPE [kA]

Active power P [kW] Cmax 1.10


Reactive power Q [kvar] Resistance at Reference voltage [mOhm] 38.029
Ib (A) [A] 40.00 Reactance at Reference voltage [mOhm] 378.380
Power factor Cosphi 0.95 Impedance at Reference voltage [mOhm] 380.286

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short circuit calculation

Switchboard Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
SMDB 3.26 5.47 2.82 4.74 3.03 5.08 2.88 4.83
FINAL DB 3.37 5.66 2.92 4.90 3.23 5.42 3.10 5.21
MCC 3.28 5.04 2.84 4.36 3.01 4.63 2.85 4.38
MDB 3.49 5.78 3.02 5.00 3.45 5.71 3.43 5.68

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Protection of Lv Cables

-WC3 TR-1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF2 E2.2N 2500 Ekip Dip LSIG 2500
Load data

Passed
Voltage [V] 400 OL - Load current could not be calculated
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by

Protection checks
Cosphi
Cable cross-sections 11x(1x630)+2G240
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 20 2
Cable

Iz (A) [A] 2742.4


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.27
Work Temp (°C) [°C] 75.5
Power loss [W] 3829.19 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 8101917208 2

-WC4
Phases - Distribution System LLLN / TN-S Overload: protected by -QF3 T4S 320 PR221DS-LS/I 320A
Load data

Passed
Voltage [V] 400 IB (176.74[A]) <= Ith (179.20[A]) <= Iz (346.00[A]) and If (232.96[A]) <= 1.45*Iz (501.70[A]); Uref=400V
IB (A) [A] 252.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF3 T4S 320 PR221DS-LS/I 320A
Cosphi 0.00 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.45[kA]), Ik LN ( 3.45[kA]), Ik L-PE ( 3.43[kA]); Uref=400V
Cable cross-sections 3x(1x240)+1x(1x120)+1G120
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF3 T4S 320 PR221DS-LS/I 320A
Passed
Length (m) [m] 10 2 I@Max tripping time ( 0.91[kA])<=Ikmin L-PE ( 2.63[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 346.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.06
Work Temp (°C) [°C] 51.3
Power loss [W] 166.31 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 759590568 2

-WC5 SMDB
Phases - Distribution System LLLN / TN-S Overload: protected by -QF5 XT4N 250 Ekip LSI R250
Load data

Passed
Voltage [V] 400 IB (135.70[A]) <= Ith (150.00[A]) <= Iz (192.00[A]) and If (195.00[A]) <= 1.45*Iz (278.40[A]); Uref=400V
IB (A) [A] 135.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF5 XT4N 250 Ekip LSI R250
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LLL ( 3.29[kA]), Ik LN ( 3.23[kA]), Ik L-PE ( 3.10[kA]); Uref=400V
Cable cross-sections 5G50/25
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF5 XT4N 250 Ekip LSI R250
Passed
Length (m) [m] 7 2 I@Max tripping time ( 1.71[kA])<=Ikmin L-PE ( 2.26[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 192.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.17
Work Temp (°C) [°C] 60.0
Power loss [W] 166.05 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 51032484 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 10
Protection of Lv Cables

-WC6 SMDB-F1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF6 XT4N 250 Ekip LS/I R250
Load data

Passed
Voltage [V] 400 IB (204.48[A]) <= Ith (210.00[A]) <= Iz (272.04[A]) and If (273.00[A]) <= 1.45*Iz (394.45[A]); Uref=400V
IB (A) [A] 204.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF6 XT4N 250 Ekip LS/I R250

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.28[kA]), Ik LN ( 3.21[kA]), Ik L-PE ( 3.07[kA]); Uref=400V
Cable cross-sections 5G95/50
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF6 XT4N 250 Ekip LS/I R250
Passed
Length (m) [m] 5 2 I@Max tripping time ( 1.07[kA])<=Ikmin L-PE ( 2.40[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 272.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.11
Work Temp (°C) [°C] 68.2
Power loss [W] 145.78 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 184227268 2

-WC7 SMDB-F2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF7 T4N 320 PR221DS-LS/I 320A
Load data

Passed
Voltage [V] 400 IB (254.92[A]) <= Ith (256.00[A]) <= Iz (315.85[A]) and If (332.80[A]) <= 1.45*Iz (457.99[A]); Uref=400V
IB (A) [A] 254.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF7 T4N 320 PR221DS-LS/I 320A
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.27[kA]), Ik LN ( 3.19[kA]), Ik L-PE ( 3.05[kA]); Uref=400V
Cable cross-sections 5G120/70
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF7 T4N 320 PR221DS-LS/I 320A
Passed
Length (m) [m] 5 2 I@Max tripping time ( 1.30[kA])<=Ikmin L-PE ( 2.42[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 315.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.11
Work Temp (°C) [°C] 72.6
Power loss [W] 181.97 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 293947110 2

-WC8 SMDB-F3
Phases - Distribution System LLLN / TN-S Overload: protected by -QF8 T5N 400 PR221DS-LS/I 400A
Load data

Passed
Voltage [V] 400 IB (327.17[A]) <= Ith (336.00[A]) <= Iz (399.00[A]) and If (436.80[A]) <= 1.45*Iz (578.55[A]); Uref=400V
IB (A) [A] 327.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF8 T5N 400 PR221DS-LS/I 400A
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LLL ( 3.26[kA]), Ik LN ( 3.17[kA]), Ik L-PE ( 3.02[kA]); Uref=400V
Cable cross-sections 5G150/95
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF8 T5N 400 PR221DS-LS/I 400A
Passed
Length (m) [m] 5 2 I@Max tripping time ( 1.71[kA])<=Ikmin L-PE ( 2.43[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 399.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.12
Work Temp (°C) [°C] 70.3
Power loss [W] 238.02 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 459292359 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 10
Protection of Lv Cables

-WC9 MCC
Phases - Distribution System LLLN / TN-S Overload: protected by -QF9 T5S 630 PR222DS-LSI 630A
Load data

Passed
Voltage [V] 400 IB (257.00[A]) <= Ith (264.60[A]) <= Iz (581.32[A]) and If (343.98[A]) <= 1.45*Iz (842.91[A]); Uref=400V
IB (A) [A] 257.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF9 T5S 630 PR222DS-LSI 630A

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.27[kA]), Ik LN ( 3.27[kA]), Ik L-PE ( 3.25[kA]); Uref=400V
Cable cross-sections 2x 5G240/120
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF9 T5S 630 PR222DS-LSI 630A
Passed
Length (m) [m] 120 2 I@Max tripping time ( 1.35[kA])<=Ikmin L-PE ( 2.04[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 581.3


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.73
Work Temp (°C) [°C] 49.8
Power loss [W] 1026.15 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 1175788438 2

-WC10 DB
Phases - Distribution System LLLN / TN-S Overload: protected by -QF10 XT2N 160 Ekip LS/I R160
Load data

Passed
Voltage [V] 400 IB (58.72[A]) <= Ith (89.60[A]) <= Iz (364.24[A]) and If (116.48[A]) <= 1.45*Iz (528.14[A]); Uref=400V
IB (A) [A] 58.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF10 XT2N 160 Ekip LS/I R160
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G150
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF10 XT2N 160 Ekip LS/I R160
Passed
Length (m) [m] 40 2 I@Max tripping time ( 0.46[kA])<=Ikmin L-PE ( 1.87[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 364.2


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.16
Work Temp (°C) [°C] 41.3
Power loss [W] 55.41 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 459292359 2

-WC11 DB-G2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF11 XT2N 160 TMD 32-320
Load data

Passed
Voltage [V] 400 IB (28.87[A]) <= Ith (28.87[A]) <= Iz (100.00[A]) and If (37.53[A]) <= 1.45*Iz (145.00[A]); Uref=400V
IB (A) [A] 28.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF11 XT2N 160 TMD 32-320
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF11 XT2N 160 TMD 32-320
Passed
Length (m) [m] 35 2 I@Max tripping time ( 0.38[kA])<=Ikmin L-PE ( 1.12[kA]); Trip time=0.40[s]; Uref=400V
Cable

Iz (A) [A] 100.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.50
Work Temp (°C) [°C] 35.0
Power loss [W] 107.30 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 5225726 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 4 10
Protection of Lv Cables

-WC12 DB-G3
Phases - Distribution System LLLN / TN-S Overload: protected by -QF12 XT2N 160 TMD 32-320
Load data

Passed
Voltage [V] 400 IB (22.45[A]) <= Ith (22.45[A]) <= Iz (100.00[A]) and If (29.19[A]) <= 1.45*Iz (145.00[A]); Uref=400V
IB (A) [A] 22.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF12 XT2N 160 TMD 32-320

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF12 XT2N 160 TMD 32-320
Passed
Length (m) [m] 45 2 I@Max tripping time ( 0.38[kA])<=Ikmin L-PE ( 1.00[kA]); Trip time=0.40[s]; Uref=400V
Cable

Iz (A) [A] 100.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.49
Work Temp (°C) [°C] 33.0
Power loss [W] 82.83 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 5225726 2

-WC13 DB-G4
Phases - Distribution System LLLN / TN-S Overload: protected by -QF13 XT2N 160 TMD 32-320
Load data

Passed
Voltage [V] 400 IB (25.66[A]) <= Ith (25.66[A]) <= Iz (100.00[A]) and If (33.36[A]) <= 1.45*Iz (145.00[A]); Uref=400V
IB (A) [A] 25.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF13 XT2N 160 TMD 32-320
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF13 XT2N 160 TMD 32-320
Passed
Length (m) [m] 50 2 I@Max tripping time ( 0.38[kA])<=Ikmin L-PE ( 0.96[kA]); Trip time=0.40[s]; Uref=400V
Cable

Iz (A) [A] 100.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.63
Work Temp (°C) [°C] 34.0
Power loss [W] 120.64 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 5225726 2

-WC14 CHWP-1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF15 XT2N 160 TMA 160-1600
Load data

Passed
Voltage [V] 400 IB (106.00[A]) <= Ith (112.00[A]) <= Iz (258.08[A]) and If (145.60[A]) <= 1.45*Iz (374.21[A]); Uref=400V
IB (A) [A] 106.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF15 XT2N 160 TMA 160-1600
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LLL ( 3.19[kA]), Ik LN ( 3.01[kA]), Ik L-PE ( 2.85[kA]); Uref=400V
Cable cross-sections 5G95/50
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF15 XT2N 160 TMA 160-1600
Passed
Length (m) [m] 35 2 I@Max tripping time ( 1.44[kA])<=Ikmin L-PE ( 1.58[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 258.1


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.36
Work Temp (°C) [°C] 45.1
Power loss [W] 252.91 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 119015710 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 4 5 10
Protection of Lv Cables

-WC15 CHWP-2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF16 XT2N 160 TMA 80-800
Load data

Passed
Voltage [V] 400 IB (73.00[A]) <= Ith (73.00[A]) <= Iz (166.28[A]) and If (94.90[A]) <= 1.45*Iz (241.10[A]); Uref=400V
IB (A) [A] 73.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF16 XT2N 160 TMA 80-800

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.19[kA]), Ik LN ( 3.01[kA]), Ik L-PE ( 2.85[kA]); Uref=400V
Cable cross-sections 5G50/25
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF16 XT2N 160 TMA 80-800
Passed
Length (m) [m] 45 2 I@Max tripping time ( 0.55[kA])<=Ikmin L-PE ( 1.18[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 166.3


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.57
Work Temp (°C) [°C] 45.8
Power loss [W] 293.79 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 32968341 2

-WC16 CHWP-3
Phases - Distribution System LLLN / TN-S Overload: protected by -QF17 XT4N 160 Ekip LSI R40
Load data

Passed
Voltage [V] 400 IB (32.00[A]) <= Ith (32.00[A]) <= Iz (86.60[A]) and If (41.60[A]) <= 1.45*Iz (125.57[A]); Uref=400V
IB (A) [A] 32.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF17 XT4N 160 Ekip LSI R40
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.19[kA]), Ik LN ( 3.01[kA]), Ik L-PE ( 2.85[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF17 XT4N 160 Ekip LSI R40
Passed
Length (m) [m] 55 2 I@Max tripping time ( 0.22[kA])<=Ikmin L-PE ( 0.72[kA]); Trip time=0.40[s]; Uref=400V
Cable

Iz (A) [A] 86.6


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.90
Work Temp (°C) [°C] 44.1
Power loss [W] 214.31 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 3375958 2

-WC17 MW PUMP
Phases - Distribution System LLL / TN-S Overload: protected by -FR18 EF65-56
Load data

Passed
Voltage [V] 400 IB (22.20[A]) <= Ith (22.20[A]) <= Iz (127.00[A]) and If (28.86[A]) <= 1.45*Iz (184.15[A]); Uref=400V
IB (A) [A] 22.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF19 XT2N 160 MA 52 Im=314...728
Protection checks

Cosphi 0.89 Passed


Protection guaranteed up to Ik LLL ( 3.02[kA]), Ik L-PE ( 2.71[kA]); Uref=400V
Cable cross-sections 4G25/16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF19 XT2N 160 MA 52 Im=314...728
Passed
Length (m) [m] 30 2 I@Max tripping time ( 0.63[kA])<=Ikmin L-PE ( 1.02[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 127.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.36
Work Temp (°C) [°C] 31.8
Power loss [W] 34.39 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 12758121 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 5 6 10
Protection of Lv Cables

-WC18 IRRIGATION PUMP


Phases - Distribution System LLL / TN-S Overload: protected by -FR20 EF19-6.3
Load data

Passed
Voltage [V] 400 IB ( 4.49[A]) <= Ith ( 4.49[A]) <= Iz (54.00[A]) and If ( 5.84[A]) <= 1.45*Iz (78.30[A]); Uref=400V
IB (A) [A] 4.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF21 XT2N 160 MF 8,5 Im=120

Protection checks
Cosphi 0.84 Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik L-PE ( 2.84[kA]); Uref=400V
Cable cross-sections 4G6/6
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF21 XT2N 160 MF 8,5 Im=120
Passed
Length (m) [m] 20 2 I@Max tripping time ( 0.14[kA])<=Ikmin L-PE ( 0.64[kA]); Trip time=0.40[s]; Uref=400V
Cable

Iz (A) [A] 54.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.11
Work Temp (°C) [°C] 30.4
Power loss [W] 3.89 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 734868 2

-WC19 WATER PUMP


Phases - Distribution System LLL / TN-S Overload: protected by -FR22 EF19-6.3
Load data

Passed
Voltage [V] 400 IB ( 3.12[A]) <= Ith ( 3.12[A]) <= Iz (54.00[A]) and If ( 4.06[A]) <= 1.45*Iz (78.30[A]); Uref=400V
IB (A) [A] 3.1
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF23 XT2N 160 MF 4 Im=56
Cosphi 0.85 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik L-PE ( 2.84[kA]); Uref=400V
Cable cross-sections 4G6/6
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF23 XT2N 160 MF 4 Im=56
Passed
Length (m) [m] 15 2 I@Max tripping time ( 0.07[kA])<=Ikmin L-PE ( 0.77[kA]); Trip time=0.40[s]; Uref=400V
Cable

Iz (A) [A] 54.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.06
Work Temp (°C) [°C] 30.2
Power loss [W] 1.41 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 734868 2

-WC20 LIGHT-1
Phases - Distribution System LN / TN-S Overload: protected by -QF25 S201-C16
Load data

(L2-N)
Passed
Voltage [V] 230.94 IB (12.99[A]) <= Ith (16.00[A]) <= Iz (43.70[A]) and If (23.20[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 13.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF25 S201-C16
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 15 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 43.7


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.51
Work Temp (°C) [°C] 33.5
Power loss [W] 16.46 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 474744 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 6 7 10
Protection of Lv Cables

-WC21 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF26 S201-C16
Load data

(L3-N)
Passed
Voltage [V] 230.94 IB (12.27[A]) <= Ith (16.00[A]) <= Iz (69.93[A]) and If (23.20[A]) <= 1.45*Iz (101.40[A]); Uref=400V
IB (A) [A] 12.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF26 S201-C16

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x16)+1G16
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 69.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.23
Work Temp (°C) [°C] 40.9
Power loss [W] 6.79 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 3375958 2

-WC22 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF27 S201-C10
Load data

(L1-N)
Passed
Voltage [V] 230.94 IB ( 8.66[A]) <= Ith (10.00[A]) <= Iz (43.70[A]) and If (14.50[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 8.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF27 S201-C10
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 43.7


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.40
Work Temp (°C) [°C] 31.6
Power loss [W] 8.72 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 474744 2

-WC23 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF28 S201-C10
Load data

(L3-N)
Passed
Voltage [V] 230.94 IB ( 6.50[A]) <= Ith (10.00[A]) <= Iz (34.20[A]) and If (14.50[A]) <= 1.45*Iz (49.59[A]); Uref=400V
IB (A) [A] 6.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF28 S201-C10
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x4)+1G4
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 34.2


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.45
Work Temp (°C) [°C] 31.4
Power loss [W] 7.35 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 210997 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 7 8 10
Protection of Lv Cables

-WC24 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF29 S201-C10
Load data

(L1-N)
Passed
Voltage [V] 230.94 IB ( 8.66[A]) <= Ith (10.00[A]) <= Iz (43.70[A]) and If (14.50[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 8.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF29 S201-C10

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 43.7


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.40
Work Temp (°C) [°C] 31.6
Power loss [W] 8.72 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 474744 2

-WC25 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF30 S201-C6
Load data

(L2-N)
Passed
Voltage [V] 230.94 IB ( 5.20[A]) <= Ith ( 6.00[A]) <= Iz (34.20[A]) and If ( 8.70[A]) <= 1.45*Iz (49.59[A]); Uref=400V
IB (A) [A] 5.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF30 S201-C6
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x4)+1G4
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 34.2


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.36
Work Temp (°C) [°C] 30.9
Power loss [W] 4.69 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 210997 2

-WC26 SOCKET-1
Phases - Distribution System LN / TN-S Overload: protected by -QF32 S201-C16
Load data

(L2-N)
Passed
Voltage [V] 230.94 IB (12.99[A]) <= Ith (16.00[A]) <= Iz (43.70[A]) and If (23.20[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 13.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF32 S201-C16
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 15 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 43.7


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.51
Work Temp (°C) [°C] 33.5
Power loss [W] 16.46 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 474744 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 8 9 10
Protection of Lv Cables

-WC27 SOCKET-2
Phases - Distribution System LN / TN-S Overload: protected by -QF33 S201-C20
Load data

(L3-N)
Passed
Voltage [V] 230.94 IB (14.31[A]) <= Ith (20.00[A]) <= Iz (59.85[A]) and If (29.00[A]) <= 1.45*Iz (86.78[A]); Uref=400V
IB (A) [A] 14.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF33 S201-C20

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x10)+1G10
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 18 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 59.8


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.41
Work Temp (°C) [°C] 32.3
Power loss [W] 14.32 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 1318734 2

-WC28 SOCKET-3
Phases - Distribution System LN / TN-S Overload: protected by -QF34 S201-C16
Load data

(L3-N)
Passed
Voltage [V] 230.94 IB (12.27[A]) <= Ith (16.00[A]) <= Iz (46.00[A]) and If (23.20[A]) <= 1.45*Iz (66.70[A]); Uref=400V
IB (A) [A] 12.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF34 S201-C16
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 20 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 46.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.63
Work Temp (°C) [°C] 32.8
Power loss [W] 19.53 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 474744 2

-WC29 SOCKET-4
Phases - Distribution System LN / TN-S Overload: protected by -QF35 S201-C16
Load data

(L2-N)
Passed
Voltage [V] 230.94 IB (10.22[A]) <= Ith (16.00[A]) <= Iz (80.75[A]) and If (23.20[A]) <= 1.45*Iz (117.09[A]); Uref=400V
IB (A) [A] 10.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF35 S201-C16
Protection checks

Cosphi 0.90 Passed


Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x16)+1G16
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 40 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 80.8


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.41
Work Temp (°C) [°C] 30.6
Power loss [W] 10.09 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 3375958 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 9 10 10
Protection of Lv Cables

-WC30 SOCKET-5
Phases - Distribution System LN / TN-S Overload: protected by -QF36 S201-C50
Load data

(L1-N)
Passed
Voltage [V] 230.94 IB (14.31[A]) <= Ith (50.00[A]) <= Iz (57.00[A]) and If (72.50[A]) <= 1.45*Iz (82.65[A]); Uref=400V
IB (A) [A] 14.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF36 S201-C50

Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x10)+1G10
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 10 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 57.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.22
Work Temp (°C) [°C] 32.5
Power loss [W] 7.96 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 1318734 2

-WC31 SOCKET-6
Phases - Distribution System LN / TN-S Overload: protected by -QF37 S201-C20
Load data

(L2-N)
Passed
Voltage [V] 230.94 IB (17.32[A]) <= Ith (20.00[A]) <= Iz (43.70[A]) and If (29.00[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 17.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF37 S201-C20
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 8 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable

Iz (A) [A] 43.7


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.36
Work Temp (°C) [°C] 36.3
Power loss [W] 15.77 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 474744 2

-WC32 GENERATOR INCOMER


Phases - Distribution System LLLN / TN-S Overload: protected by -QF38 E1.2C 1600 Ekip Dip LSIG 1600
Load data

Passed
Voltage [V] 400 IB (1113.47[A]) <= Ith (1280.00[A]) <= Iz (2094.82[A]) and If (1664.00[A]) <= 1.45*Iz (3037.49[A]); Uref=400V
IB (A) [A] 1443.4
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks

Cosphi 0.95
Cable cross-sections 8x(1x630)+2G240
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 20 2
Cable

Iz (A) [A] 2094.8


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.26
Work Temp (°C) [°C] 58.5
Power loss [W] 2118.99 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 8101917208 2

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 10 10
Protection of busways

-BW1 SMDB
Phases - Distribution System LLLN / TN-S Overload
Load data

Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed

Protective device
IB (A) [A] 922.3 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.45[kA]), Ik LN ( 3.45[kA]); Uref=400V
Cable

Length (m) [m] 54 Indirect contact


Iz (A) [A] 1600.0 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
dU (%) 1.09 I4xIn ( 0.10[A]) <= Ikmin L-PE ( 2.52[kA]) and T4 (0.10[s]) <= Max tripping time (5.00[s]); Uref=400V

-BW2 SMDB-F1
Phases - Distribution System LLLN / TN-S Overload
Load data

Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed

Protective device
IB (A) [A] 786.6 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.29[kA]), Ik LN ( 3.23[kA]); Uref=400V
Cable

Length (m) [m] 5 Indirect contact


Iz (A) [A] 1600.0 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
dU (%) 0.09 I4xIn ( 0.10[A]) <= Ikmin L-PE ( 2.52[kA]) and T4 (0.10[s]) <= Max tripping time (5.00[s]); Uref=400V

-BW3 SMDB-F2
Phases - Distribution System LLLN / TN-S Overload
Load data

Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protective device

IB (A) [A] 582.1 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.28[kA]), Ik LN ( 3.21[kA]); Uref=400V
Cable

Length (m) [m] 5 Indirect contact


Iz (A) [A] 1600.0 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
dU (%) 0.06 I4xIn ( 0.10[A]) <= Ikmin L-PE ( 2.52[kA]) and T4 (0.10[s]) <= Max tripping time (5.00[s]); Uref=400V

-BW4 SMDB-F3
Phases - Distribution System LLLN / TN-S Overload
Load data

Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protective device

IB (A) [A] 327.2 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.27[kA]), Ik LN ( 3.19[kA]); Uref=400V
Cable

Length (m) [m] 5 Indirect contact


Iz (A) [A] 1600.0 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
dU (%) 0.04 I4xIn ( 0.10[A]) <= Ikmin L-PE ( 2.52[kA]) and T4 (0.10[s]) <= Max tripping time (5.00[s]); Uref=400V

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF2 MDB 4P 2500 66.0 66.0 On 0.62 On 6.00 Off Off (null)

E2.2N 2500 Ekip Dip LSIG 2500 LV INCOMER 24s I2t const. 0.30s 4.00 I2t const.

D -QF3 MDB 3P 320 50.0 50.0 On 0.56 Off On (null)

T4S 320 PR221DS-LS/I 320A 3s 4.50

E -QF4 MDB 3P 1000 50.0 0.0 On 0.95 On 3.50 On On 0.10 (null)

E1.2C 1000 Ekip Dip LSIG 1000 SMDB 3s t const. 0.10s 4.00 I2t const. 0.10s

F -QF5 MDB 3P 250 36.0 36.0 On 0.60 On 6.50 Off (null)

XT4N 250 Ekip LSI R250 SMDB 60s I2t const. 0.1s 4.50

G -QF6 MDB 3P 250 36.0 36.0 On 0.84 Off On (null)

XT4N 250 Ekip LS/I R250 SMDB-F1 12s t const. 4.50

H -QF7 MDB 3P 320 36.0 36.0 On 0.80 Off On (null)

T4N 320 PR221DS-LS/I 320A SMDB-F2 3s 4.50

I -QF8 MDB 3P 400 36.0 36.0 On 0.84 Off On (null)

T5N 400 PR221DS-LS/I 400A SMDB-F3 3s 4.50

J -QF9 MDB 3P 630 50.0 0.0 On 0.42 Off On Off (null)

T5S 630 PR222DS-LSI 630A MCC 3s I2t const. 4.00

K
-QF10 SMDB 3P 160 36.0 36.0 On 0.56 On 3.50 Off (null)

XT2N 160 Ekip LS/I R160 DB 12s t const. 0.10s 4.50

L
-QF11 SMDB 3P 32 36.0 36.0 28.9

XT2N 160 TMD 32-320 DB-G2 320.0

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF12 SMDB 3P 32 36.0 36.0 22.5

XT2N 160 TMD 32-320 DB-G3 320.0

D -QF13 SMDB 3P 32 36.0 36.0 25.7

XT2N 160 TMD 32-320 DB-G4 320.0

E -QF14 MCC 3P 500 36.0 0.0 350.0 On Off

T5N 630 TMA500-5000 MCC 5000.0

F -QF15 MCC 3P 160 36.0 0.0 112.0 On Off

XT2N 160 TMA 160-1600 CHWP-1 1200.0

G -QF16 MCC 3P 80 36.0 36.0 73.0

XT2N 160 TMA 80-800 CHWP-2 600.0

H -QF17 MCC 3P 40 36.0 36.0 On 0.80 Off On (null)

XT4N 160 Ekip LSI R40 CHWP-3 3s I2t const. 4.50

I -QF19 MCC 3P 52 36.0 36.0

XT2N 160 MA 52 Im=314...728 MW PUMP 521.0

J -QF21 MCC 3P 9 36.0 36.0

XT2N 160 MF 8,5 Im=120 IRRIGATION PUMP 120.0

K
-QF23 MCC 3P 4 36.0 36.0

XT2N 160 MF 4 Im=56 WATER PUMP 56.0

L
-QF25 FINAL DB 1P 16 10.0 7.5 16.0

S201-C16 LIGHT-1 160.0

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF26 FINAL DB 1P 16 10.0 7.5 16.0

S201-C16 LIGHT-5 160.0

D -QF27 FINAL DB 1P 10 10.0 7.5 10.0

S201-C10 LIGHT-5 100.0

E -QF28 FINAL DB 1P 10 10.0 7.5 10.0

S201-C10 LIGHT-5 100.0

F -QF29 FINAL DB 1P 10 10.0 7.5 10.0

S201-C10 LIGHT-5 100.0

G -QF30 FINAL DB 1P 6 10.0 7.5 6.0

S201-C6 LIGHT-5 60.0

H -QF32 FINAL DB 1P 16 10.0 7.5 16.0

S201-C16 SOCKET-1 160.0

I -QF33 FINAL DB 1P 20 10.0 7.5 20.0

S201-C20 SOCKET-2 200.0

J -QF34 FINAL DB 1P 16 10.0 7.5 16.0

S201-C16 SOCKET-3 160.0

K
-QF35 FINAL DB 1P 16 10.0 7.5 16.0

S201-C16 SOCKET-4 160.0

L
-QF36 FINAL DB 1P 50 10.0 0.0 50.0

S201-C50 SOCKET-5 500.0

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF37 FINAL DB 1P 20 10.0 7.5 20.0

S201-C20 SOCKET-6 200.0

D -QF38 MDB 3P 1600 50.0 50.0 On 0.80 On 3.00 Off Off (null)

E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER 3s t const. 0.20s 4.00 I2t const.

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 4 4
Discrimination

Upstream device Downstream device

Sign Model User description 1 Sign Model User description 1 Check

Guaranteed up to 42.00[kA] >= requested value ( 3.45[kA]); Uref=400V


-QF38 E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER -QF3 T4S 320 PR221DS-LS/I 320A Passed

Guaranteed up to 42.00[kA] >= requested value ( 3.45[kA]); Uref=400V


-QF38 E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER -QF3 T4S 320 PR221DS-LS/I 320A Passed

Guaranteed up to 4.32[kA] >= requested value ( 3.45[kA]); Uref=400V


-QF38 E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER -QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB Passed

Guaranteed up to 4.32[kA] >= requested value ( 3.45[kA]); Uref=400V


-QF38 E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER -QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.29[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF5 XT4N 250 Ekip LSI R250 SMDB Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.29[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF5 XT4N 250 Ekip LSI R250 SMDB Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.28[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF6 XT4N 250 Ekip LS/I R250 SMDB-F1 Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.28[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF6 XT4N 250 Ekip LS/I R250 SMDB-F1 Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.27[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF7 T4N 320 PR221DS-LS/I 320A SMDB-F2 Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.27[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF7 T4N 320 PR221DS-LS/I 320A SMDB-F2 Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.26[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF8 T5N 400 PR221DS-LS/I 400A SMDB-F3 Passed

Guaranteed up to 3.60[kA] >= requested value ( 3.26[kA]); Uref=400V


-QF4 E1.2C 1000 Ekip Dip LSIG 1000 SMDB -QF8 T5N 400 PR221DS-LS/I 400A SMDB-F3 Passed

Guaranteed up to 42.00[kA] >= requested value ( 3.27[kA]); Uref=400V


-QF38 E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER -QF9 T5S 630 PR222DS-LSI 630A MCC Passed

Guaranteed up to 42.00[kA] >= requested value ( 3.27[kA]); Uref=400V


-QF38 E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER -QF9 T5S 630 PR222DS-LSI 630A MCC Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF10 XT2N 160 Ekip LS/I R160 DB Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF10 XT2N 160 Ekip LS/I R160 DB Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF11 XT2N 160 TMD 32-320 DB-G2 Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF11 XT2N 160 TMD 32-320 DB-G2 Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF12 XT2N 160 TMD 32-320 DB-G3 Passed

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 3
Discrimination

Upstream device Downstream device

Sign Model User description 1 Sign Model User description 1 Check

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF12 XT2N 160 TMD 32-320 DB-G3 Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF13 XT2N 160 TMD 32-320 DB-G4 Passed

Guaranteed up to 50.00[kA] >= requested value ( 3.18[kA]); Uref=400V


-QF5 XT4N 250 Ekip LSI R250 SMDB -QF13 XT2N 160 TMD 32-320 DB-G4 Passed

Guaranteed up to 36.00[kA] >= requested value ( 3.19[kA]); Uref=400V


-QF14 T5N 630 TMA500-5000 MCC -QF15 XT2N 160 TMA 160-1600 CHWP-1 Passed

Guaranteed up to 36.00[kA] >= requested value ( 3.19[kA]); Uref=400V


-QF14 T5N 630 TMA500-5000 MCC -QF15 XT2N 160 TMA 160-1600 CHWP-1 Passed

Guaranteed up to 36.00[kA] >= requested value ( 3.19[kA]); Uref=400V


-QF14 T5N 630 TMA500-5000 MCC -QF16 XT2N 160 TMA 80-800 CHWP-2 Passed

Guaranteed up to 36.00[kA] >= requested value ( 3.19[kA]); Uref=400V


-QF14 T5N 630 TMA500-5000 MCC -QF16 XT2N 160 TMA 80-800 CHWP-2 Passed

Guaranteed up to 36.00[kA] >= requested value ( 3.19[kA]); Uref=400V


-QF14 T5N 630 TMA500-5000 MCC -QF17 XT4N 160 Ekip LSI R40 CHWP-3 Passed

Guaranteed up to 36.00[kA] >= requested value ( 3.19[kA]); Uref=400V


-QF14 T5N 630 TMA500-5000 MCC -QF17 XT4N 160 Ekip LSI R40 CHWP-3 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF25 S201-C16 LIGHT-1 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF25 S201-C16 LIGHT-1 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF26 S201-C16 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF26 S201-C16 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF27 S201-C10 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF27 S201-C10 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF28 S201-C10 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF28 S201-C10 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF29 S201-C10 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF29 S201-C10 LIGHT-5 Passed

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 3
Discrimination

Upstream device Downstream device

Sign Model User description 1 Sign Model User description 1 Check

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF30 S201-C6 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF30 S201-C6 LIGHT-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF32 S201-C16 SOCKET-1 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF32 S201-C16 SOCKET-1 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF33 S201-C20 SOCKET-2 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF33 S201-C20 SOCKET-2 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF34 S201-C16 SOCKET-3 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF34 S201-C16 SOCKET-3 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF35 S201-C16 SOCKET-4 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF35 S201-C16 SOCKET-4 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF36 S201-C50 SOCKET-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF36 S201-C50 SOCKET-5 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF37 S201-C20 SOCKET-6 Passed

Guaranteed up to 10.00[kA] >= requested value ( 2.67[kA]); Uref=400V


-QF10 XT2N 160 Ekip LS/I R160 DB -QF37 S201-C20 SOCKET-6 Passed

Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 3