MDB Report With Generator Feeding
MDB Report With Generator Feeding
MDB Report With Generator Feeding
Project: TOWER-1
Notes: MDB SS1
Designer:
Overload Overload verifications are made according the following relations: IB <= In <= Iz and I2 <= 1.45*Iz
Legenda:
In = nominal current of the protective device (For adjustable protective devices, the nominal current In is the current setting selected)
I2 = current ensuring effective operation in the conventional time of the protective device
Short Circuit Circuit breakers and fuses are dimensioned with a breaking capacity higher than the maximum short circuit current in the point of installation
Circuit breakers dimensioned according to IEC 60497-2 are also chosen with the making capacity Icm higher than the maxiimum peak current
The protection against short circuit must satisfy the rule I²t <= K²S²
Legenda:
I²t = let-through energy at the maximum short circuit current (defined by the producer)
K = factor defined in IEC60364-4-43 table 43A and IEC60364-5-54 tables A.54.2, A.54.4 and A-54.5
Indirect contact TT systems: the verification is Idn * Ra <= Vo, or Im <= Ib min
Legenda:
Ra = earthing resistance
Discrimination and Back-up The discrimination and back-up values are determined by the producer with laboratory tests
Discrimination required in the installation (see indications on the single-line and the Discrimination report
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short-circuit calculation hypothesis for IEC 60909-0
Calculation algorithm
The calculation of maximum and minimum, balanced and unbalanced, short-circuit currents is made by application of symmetrical components.
General conditions
The calculation of maximum and minimum short-circuit currents is based on the following simplifications.
a) For the duration of the short circuit, there is no change in the type of short circuit involved (a three-phase short circuit remains three-phase)
b) For the duration of the short circuit, there is no change in the network involved.
e) All line capacitances and shunt admittances and non-rotating loads, except those of the zero-sequence system, are neglected.
In the calculation of maximum short-circuit currents, the following conditions have been considered:
- it is chosen the network configuration which leads to the maximum value of short-circuit current at the short-circuit location
- the contribution of asynchronous motors is considered if their contribution is higher than 5% of the initial short-circuit current calculated without motors
- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 20°C
In the calculation of minimum short-circuit currents, the following conditions have been considered:
- it is chosen the network confguration which lead to the minimum value of short-circuit current at the short-circuit location
- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 250°C (EPR),160°C (PVC) or 140°C PVC >300m²)
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Un [V] 11000
Ik LLL [kA] 18.4 OFF -G1
P [kW]
-QF1
Salient pole generator (4 poles) 400V 1000kVA G
Q [kvar] 1VCF338184R0132 LLLN / TN-S
A
VD4/UniMix-R 24.06.20 P230 Un = 400 V
KECA250B1 (80A)
<none> Sn = 1000 kVA
REF601 CEI 0-16 P = 725.7 kW
Q = 232.8 kvar
-WC2 -WC3 -WC32
MV CABLE TR-1 GENERATOR INCOMER
3x120/16 11x(1x630)+2G240 8x(1x630)+2G240
Iz = 255.0 A Iz = 2742.4 A Ib = 1113.5 A
du = 0.00 dV = 0.27 % Iz = 2094.8 A
L = 15 m L = 20 m dV = 0.26 %
B L = 20 m
OFF
-TM1
TR-1 -QF2 -QF38
Un2 = 400 V E2.2N 2500 Ekip Dip LSIG 2500 E1.2C 1600 Ekip Dip LSIG 1600
Sn = 1600 kVA LV INCOMER GENERATOR INCOMER
Sec.: LLLN / TN-S *
-B1
MDB
FU = 1.00
C U=399.0 V
IB = 1113.5 A
Cosphi = 0.95
-QF3 -QF4 -QF9 Ik max = 3.4 kA
T4S 320 PR221DS-LS/I 320A E1.2C 1000 Ekip Dip LSIG 1000 T5S 630 PR222DS-LSI 630A Ik LLL = 3.2 kA
* SMDB MCC
* *
D
-WC4 -BW1 -BW2 -BW3 -BW4 -WC9
3x(1x240)+1x(1x120)+1G120 1600A Cu Busway 1600A Cu Busway 1600A Cu Busway 1600A Cu Busway MCC
Ib = 176.7 A SMDB SMDB-F1 SMDB-F2 SMDB-F3 2x 5G240/120
Iz = 346.0 A L = 54 m L=5m L=5m L=5m Ib = 257.0 A
dV = 0.06 % du = 1.09 du = 0.09 du = 0.06 du = 0.04 Iz = 581.3 A
L = 10 m IB = 922.3 A IB = 786.6 A IB = 582.1 A IB = 327.2 A dV = 0.73 %
Iz = 1600.0 A Iz = 1600.0 A Iz = 1600.0 A Iz = 1600.0 A L = 120 m
2
MCC
-C1 -QF5 -QF6 -QF7 -QF8
Sn = 122.45 kVA XT4N 250 Ekip LSI R250 XT4N 250 Ekip LS/I R250 T4N 320 PR221DS-LS/I 320A T5N 400 PR221DS-LS/I 400A
Q = 122.20 kvar SMDB SMDB-F1 SMDB-F2 SMDB-F3
IB = 176.7 A * * * *
E
G
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2
SMDB MCC
A
-QS1 -QF14
SMDB T5N 630 TMA500-5000
MCC
*
-B3
MCC
FU = 1.00
U=396.0 V
IB = 257.0 A
Cosphi = 0.90
-B2 Ik max = 3.2 kA
SMDB Ik LLL = 3.2 kA
FU = 1.00
B U=393.9 V
IB = 135.7 A
Cosphi = 0.90
-QF10 -QF11 -QF12 -QF13 Ik max = 3.2 kA -QF15 -QF16 -QF17 -QF19 -QF21 -QF23
XT2N 160 Ekip LS/I R160 XT2N 160 TMD 32-320 XT2N 160 TMD 32-320 XT2N 160 TMD 32-320
Ik LLL = 3.2 kA XT2N 160 TMA 160-1600 XT2N 160 TMA 80-800 XT4N 160 Ekip LSI R40 XT2N 160 MA 52 Im=314...728 XT2N 160 MF 8,5 Im=120 XT2N 160 MF 4 Im=56
DB DB-G2 DB-G3 DB-G4 CHWP-1 CHWP-2 CHWP-3 MW PUMP IRRIGATION PUMP WATER PUMP
* * * * * * *
C
-WC14 -WC15 -WC16
CHWP-1 CHWP-2 CHWP-3
5G95/50 5G50/25 5G16
Ib = 106.0 A Ib = 73.0 A Ib = 32.0 A -K1 -K2 -K3
-WC10 -WC11 -WC12 -WC13 Iz = 258.1 A Iz = 166.3 A Iz = 86.6 A
DB DB-G2 DB-G3 DB-G4 dV = 0.36 % dV = 0.57 % dV = 0.90 %
5G150 5G16 5G16 5G16 L = 35 m L = 45 m L = 55 m
Ib = 58.7 A Ib = 28.9 A Ib = 22.5 A Ib = 25.7 A -FR18 -FR20 -FR22
Iz = 364.2 A Iz = 100.0 A Iz = 100.0 A Iz = 100.0 A
dV = 0.16 % dV = 0.50 % dV = 0.49 % dV = 0.63 %
L = 40 m L = 35 m L = 45 m L = 50 m
3 f2 f2 f2
DB
-L6 -L7 -L8
D DB-G2 DB-G3 DB-G4
Sn = 20.00 [kVA] Sn = 15.56 [kVA] Sn = 17.78 [kVA] -DS9 -DS10 -DS11
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 CHWP-1 CHWP-2 CHWP-3 -WC17 -WC18 -WC19
In = 28.9 [A] In = 22.5 [A] In = 25.7 [A] Sn = 73.44 kVA Sn = 50.58 kVA Sn = 22.17 kVA MW PUMP IRRIGATION PUMP WATER PUMP
U = 391.9 [V] U = 391.9 [V] U = 391.4 [V] M Cosphi = 0.90 M Cosphi = 0.90 M Cosphi = 0.90 4G25/16 4G6/6 4G6/6
dU = 2.02 % dU = 2.02 % dU = 2.15 % In = 106.0 A In = 73.0 A In = 32.0 A IB = 38.4 A IB = 4.5 A IB = 3.1 A
P = 17.64 [kW] P = 13.72 [kW] P = 15.66 [kW] I1 act = 64.2 A I1 act = 44.5 A I1 act = 18.7 A Iz = 127.0 A Iz = 54.0 A Iz = 54.0 A
Q = 8.54 [kvar] Q = 6.65 [kvar] Q = 7.59 [kvar] P = 55.0 kW P = 37.0 kW P = 15.0 kW du = 0.36 du = 0.11 du = 0.06
Pn = 75.0 kW Pn = 45.0 kW Pn = 18.5 kW L = 30 m L = 20 m L = 15 m
In = 130.0 A In = 80.2 A In = 34.5 A M2BA 180 M - 22 kW
Rpm = 1487 Rpm = 1482 Rpm = 1477 M2BA 90 L2 A - 2,2 kW M2BA 90 S2 A - 1,5 kW
FU = 100% FU = 100% FU = 100% M MW PUMP
M IRRIGATION PUMP M WATER PUMP
dV = 1.36 % dV = 1.56 % dV = 1.89 % YD Un = 400 V Un = 400 V Un = 400 V
Pn = 22.00 kW Pn = 2.20 kW Pn = 1.50 kW
du = 1.36 du = 1.10 du = 1.05
E
G
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
3
DB
A
-QS2
DB
-B4
FINAL DB
FU = 1.00
B U=393.3 V
IB = 58.7 A
Cosphi = 0.90
-QD24 -QD31 Ik max = 3.0 kA
F204 AC-40/0,1 F204 AC-63/0,03 Ik LLL = 2.8 kA
RCCB-1 RCCB-2
I d I d
-B7
U=393.3 V
-B6 IB = 40.5 A
U=393.3 V Cosphi = 0.90
IB = 18.8 A Ik max = 3.0 kA
Cosphi = 0.90 Ik LLL = 2.8 kA
Ik max = 3.0 kA
C Ik LLL = 2.8 kA
-QF25 -QF26 -QF27 -QF28 -QF29 -QF30 -QF32 -QF33 -QF34 -QF35 -QF36 -QF37
S201-C16 S201-C16 S201-C10 S201-C10 S201-C10 S201-C6 S201-C16 S201-C20 S201-C16 S201-C16 S201-C50 S201-C20
LIGHT-1 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 SOCKET-1 SOCKET-2 SOCKET-3 SOCKET-4 SOCKET-5 SOCKET-6
* * * * * * * * * * * *
-WC20 -WC21 -WC22 -WC23 -WC24 -WC25 -WC26 -WC27 -WC28 -WC29 -WC30 -WC31
LIGHT-1 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 LIGHT-5 SOCKET-1 SOCKET-2 SOCKET-3 SOCKET-4 SOCKET-5 SOCKET-6
2x(1x6)+1G6 2x(1x16)+1G16 2x(1x6)+1G6 2x(1x4)+1G4 2x(1x6)+1G6 2x(1x4)+1G4 2x(1x6)+1G6 2x(1x10)+1G10 2x(1x6)+1G6 2x(1x16)+1G16 2x(1x10)+1G10 2x(1x6)+1G6
IB = 13.0 A IB = 12.3 A IB = 8.7 A IB = 6.5 A IB = 8.7 A IB = 5.2 A IB = 13.0 A IB = 14.3 A IB = 12.3 A IB = 10.2 A IB = 14.3 A IB = 17.3 A
Iz = 43.7 A Iz = 69.9 A Iz = 43.7 A Iz = 34.2 A Iz = 43.7 A Iz = 34.2 A Iz = 43.7 A Iz = 59.8 A Iz = 46.0 A Iz = 80.8 A Iz = 57.0 A Iz = 43.7 A
du = 0.51 du = 0.23 du = 0.40 du = 0.45 du = 0.40 du = 0.36 du = 0.51 du = 0.41 du = 0.63 du = 0.41 du = 0.22 du = 0.36
L = 15 m L = 18 m L = 18 m L = 18 m L = 18 m L = 18 m L = 15 m L = 18 m L = 20 m L = 40 m L = 10 m L=8m
E
-L12 -L18
G
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 3
Distribution
Reference voltage [V] 11000 Symmetrical short circuit current LLL [kA] 18.37
Phases LLL Line-Neutral short circuit current LN [kA]
Distribution system IT Line-Ground short circuit current LPE [kA]
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short circuit calculation
Switchboard Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
SMDB 3.26 5.47 2.82 4.74 3.03 5.08 2.88 4.83
FINAL DB 3.37 5.66 2.92 4.90 3.23 5.42 3.10 5.21
MCC 3.28 5.04 2.84 4.36 3.01 4.63 2.85 4.38
MDB 3.49 5.78 3.02 5.00 3.45 5.71 3.43 5.68
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Protection of Lv Cables
-WC3 TR-1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF2 E2.2N 2500 Ekip Dip LSIG 2500
Load data
Passed
Voltage [V] 400 OL - Load current could not be calculated
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks
Cosphi
Cable cross-sections 11x(1x630)+2G240
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 20 2
Cable
-WC4
Phases - Distribution System LLLN / TN-S Overload: protected by -QF3 T4S 320 PR221DS-LS/I 320A
Load data
Passed
Voltage [V] 400 IB (176.74[A]) <= Ith (179.20[A]) <= Iz (346.00[A]) and If (232.96[A]) <= 1.45*Iz (501.70[A]); Uref=400V
IB (A) [A] 252.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF3 T4S 320 PR221DS-LS/I 320A
Cosphi 0.00 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.45[kA]), Ik LN ( 3.45[kA]), Ik L-PE ( 3.43[kA]); Uref=400V
Cable cross-sections 3x(1x240)+1x(1x120)+1G120
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF3 T4S 320 PR221DS-LS/I 320A
Passed
Length (m) [m] 10 2 I@Max tripping time ( 0.91[kA])<=Ikmin L-PE ( 2.63[kA]); Trip time=5.00[s]; Uref=400V
Cable
-WC5 SMDB
Phases - Distribution System LLLN / TN-S Overload: protected by -QF5 XT4N 250 Ekip LSI R250
Load data
Passed
Voltage [V] 400 IB (135.70[A]) <= Ith (150.00[A]) <= Iz (192.00[A]) and If (195.00[A]) <= 1.45*Iz (278.40[A]); Uref=400V
IB (A) [A] 135.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF5 XT4N 250 Ekip LSI R250
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 10
Protection of Lv Cables
-WC6 SMDB-F1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF6 XT4N 250 Ekip LS/I R250
Load data
Passed
Voltage [V] 400 IB (204.48[A]) <= Ith (210.00[A]) <= Iz (272.04[A]) and If (273.00[A]) <= 1.45*Iz (394.45[A]); Uref=400V
IB (A) [A] 204.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF6 XT4N 250 Ekip LS/I R250
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.28[kA]), Ik LN ( 3.21[kA]), Ik L-PE ( 3.07[kA]); Uref=400V
Cable cross-sections 5G95/50
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF6 XT4N 250 Ekip LS/I R250
Passed
Length (m) [m] 5 2 I@Max tripping time ( 1.07[kA])<=Ikmin L-PE ( 2.40[kA]); Trip time=5.00[s]; Uref=400V
Cable
-WC7 SMDB-F2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF7 T4N 320 PR221DS-LS/I 320A
Load data
Passed
Voltage [V] 400 IB (254.92[A]) <= Ith (256.00[A]) <= Iz (315.85[A]) and If (332.80[A]) <= 1.45*Iz (457.99[A]); Uref=400V
IB (A) [A] 254.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF7 T4N 320 PR221DS-LS/I 320A
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.27[kA]), Ik LN ( 3.19[kA]), Ik L-PE ( 3.05[kA]); Uref=400V
Cable cross-sections 5G120/70
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF7 T4N 320 PR221DS-LS/I 320A
Passed
Length (m) [m] 5 2 I@Max tripping time ( 1.30[kA])<=Ikmin L-PE ( 2.42[kA]); Trip time=5.00[s]; Uref=400V
Cable
-WC8 SMDB-F3
Phases - Distribution System LLLN / TN-S Overload: protected by -QF8 T5N 400 PR221DS-LS/I 400A
Load data
Passed
Voltage [V] 400 IB (327.17[A]) <= Ith (336.00[A]) <= Iz (399.00[A]) and If (436.80[A]) <= 1.45*Iz (578.55[A]); Uref=400V
IB (A) [A] 327.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF8 T5N 400 PR221DS-LS/I 400A
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 10
Protection of Lv Cables
-WC9 MCC
Phases - Distribution System LLLN / TN-S Overload: protected by -QF9 T5S 630 PR222DS-LSI 630A
Load data
Passed
Voltage [V] 400 IB (257.00[A]) <= Ith (264.60[A]) <= Iz (581.32[A]) and If (343.98[A]) <= 1.45*Iz (842.91[A]); Uref=400V
IB (A) [A] 257.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF9 T5S 630 PR222DS-LSI 630A
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.27[kA]), Ik LN ( 3.27[kA]), Ik L-PE ( 3.25[kA]); Uref=400V
Cable cross-sections 2x 5G240/120
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF9 T5S 630 PR222DS-LSI 630A
Passed
Length (m) [m] 120 2 I@Max tripping time ( 1.35[kA])<=Ikmin L-PE ( 2.04[kA]); Trip time=5.00[s]; Uref=400V
Cable
-WC10 DB
Phases - Distribution System LLLN / TN-S Overload: protected by -QF10 XT2N 160 Ekip LS/I R160
Load data
Passed
Voltage [V] 400 IB (58.72[A]) <= Ith (89.60[A]) <= Iz (364.24[A]) and If (116.48[A]) <= 1.45*Iz (528.14[A]); Uref=400V
IB (A) [A] 58.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF10 XT2N 160 Ekip LS/I R160
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G150
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF10 XT2N 160 Ekip LS/I R160
Passed
Length (m) [m] 40 2 I@Max tripping time ( 0.46[kA])<=Ikmin L-PE ( 1.87[kA]); Trip time=5.00[s]; Uref=400V
Cable
-WC11 DB-G2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF11 XT2N 160 TMD 32-320
Load data
Passed
Voltage [V] 400 IB (28.87[A]) <= Ith (28.87[A]) <= Iz (100.00[A]) and If (37.53[A]) <= 1.45*Iz (145.00[A]); Uref=400V
IB (A) [A] 28.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF11 XT2N 160 TMD 32-320
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 4 10
Protection of Lv Cables
-WC12 DB-G3
Phases - Distribution System LLLN / TN-S Overload: protected by -QF12 XT2N 160 TMD 32-320
Load data
Passed
Voltage [V] 400 IB (22.45[A]) <= Ith (22.45[A]) <= Iz (100.00[A]) and If (29.19[A]) <= 1.45*Iz (145.00[A]); Uref=400V
IB (A) [A] 22.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF12 XT2N 160 TMD 32-320
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF12 XT2N 160 TMD 32-320
Passed
Length (m) [m] 45 2 I@Max tripping time ( 0.38[kA])<=Ikmin L-PE ( 1.00[kA]); Trip time=0.40[s]; Uref=400V
Cable
-WC13 DB-G4
Phases - Distribution System LLLN / TN-S Overload: protected by -QF13 XT2N 160 TMD 32-320
Load data
Passed
Voltage [V] 400 IB (25.66[A]) <= Ith (25.66[A]) <= Iz (100.00[A]) and If (33.36[A]) <= 1.45*Iz (145.00[A]); Uref=400V
IB (A) [A] 25.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF13 XT2N 160 TMD 32-320
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik LN ( 3.03[kA]), Ik L-PE ( 2.88[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF13 XT2N 160 TMD 32-320
Passed
Length (m) [m] 50 2 I@Max tripping time ( 0.38[kA])<=Ikmin L-PE ( 0.96[kA]); Trip time=0.40[s]; Uref=400V
Cable
-WC14 CHWP-1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF15 XT2N 160 TMA 160-1600
Load data
Passed
Voltage [V] 400 IB (106.00[A]) <= Ith (112.00[A]) <= Iz (258.08[A]) and If (145.60[A]) <= 1.45*Iz (374.21[A]); Uref=400V
IB (A) [A] 106.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF15 XT2N 160 TMA 160-1600
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 4 5 10
Protection of Lv Cables
-WC15 CHWP-2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF16 XT2N 160 TMA 80-800
Load data
Passed
Voltage [V] 400 IB (73.00[A]) <= Ith (73.00[A]) <= Iz (166.28[A]) and If (94.90[A]) <= 1.45*Iz (241.10[A]); Uref=400V
IB (A) [A] 73.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF16 XT2N 160 TMA 80-800
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LLL ( 3.19[kA]), Ik LN ( 3.01[kA]), Ik L-PE ( 2.85[kA]); Uref=400V
Cable cross-sections 5G50/25
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF16 XT2N 160 TMA 80-800
Passed
Length (m) [m] 45 2 I@Max tripping time ( 0.55[kA])<=Ikmin L-PE ( 1.18[kA]); Trip time=5.00[s]; Uref=400V
Cable
-WC16 CHWP-3
Phases - Distribution System LLLN / TN-S Overload: protected by -QF17 XT4N 160 Ekip LSI R40
Load data
Passed
Voltage [V] 400 IB (32.00[A]) <= Ith (32.00[A]) <= Iz (86.60[A]) and If (41.60[A]) <= 1.45*Iz (125.57[A]); Uref=400V
IB (A) [A] 32.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF17 XT4N 160 Ekip LSI R40
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.19[kA]), Ik LN ( 3.01[kA]), Ik L-PE ( 2.85[kA]); Uref=400V
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF17 XT4N 160 Ekip LSI R40
Passed
Length (m) [m] 55 2 I@Max tripping time ( 0.22[kA])<=Ikmin L-PE ( 0.72[kA]); Trip time=0.40[s]; Uref=400V
Cable
-WC17 MW PUMP
Phases - Distribution System LLL / TN-S Overload: protected by -FR18 EF65-56
Load data
Passed
Voltage [V] 400 IB (22.20[A]) <= Ith (22.20[A]) <= Iz (127.00[A]) and If (28.86[A]) <= 1.45*Iz (184.15[A]); Uref=400V
IB (A) [A] 22.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF19 XT2N 160 MA 52 Im=314...728
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 5 6 10
Protection of Lv Cables
Passed
Voltage [V] 400 IB ( 4.49[A]) <= Ith ( 4.49[A]) <= Iz (54.00[A]) and If ( 5.84[A]) <= 1.45*Iz (78.30[A]); Uref=400V
IB (A) [A] 4.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF21 XT2N 160 MF 8,5 Im=120
Protection checks
Cosphi 0.84 Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik L-PE ( 2.84[kA]); Uref=400V
Cable cross-sections 4G6/6
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF21 XT2N 160 MF 8,5 Im=120
Passed
Length (m) [m] 20 2 I@Max tripping time ( 0.14[kA])<=Ikmin L-PE ( 0.64[kA]); Trip time=0.40[s]; Uref=400V
Cable
Passed
Voltage [V] 400 IB ( 3.12[A]) <= Ith ( 3.12[A]) <= Iz (54.00[A]) and If ( 4.06[A]) <= 1.45*Iz (78.30[A]); Uref=400V
IB (A) [A] 3.1
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF23 XT2N 160 MF 4 Im=56
Cosphi 0.85 Protection checks Passed
Protection guaranteed up to Ik LLL ( 3.18[kA]), Ik L-PE ( 2.84[kA]); Uref=400V
Cable cross-sections 4G6/6
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF23 XT2N 160 MF 4 Im=56
Passed
Length (m) [m] 15 2 I@Max tripping time ( 0.07[kA])<=Ikmin L-PE ( 0.77[kA]); Trip time=0.40[s]; Uref=400V
Cable
-WC20 LIGHT-1
Phases - Distribution System LN / TN-S Overload: protected by -QF25 S201-C16
Load data
(L2-N)
Passed
Voltage [V] 230.94 IB (12.99[A]) <= Ith (16.00[A]) <= Iz (43.70[A]) and If (23.20[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 13.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF25 S201-C16
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 6 7 10
Protection of Lv Cables
-WC21 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF26 S201-C16
Load data
(L3-N)
Passed
Voltage [V] 230.94 IB (12.27[A]) <= Ith (16.00[A]) <= Iz (69.93[A]) and If (23.20[A]) <= 1.45*Iz (101.40[A]); Uref=400V
IB (A) [A] 12.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF26 S201-C16
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x16)+1G16
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC22 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF27 S201-C10
Load data
(L1-N)
Passed
Voltage [V] 230.94 IB ( 8.66[A]) <= Ith (10.00[A]) <= Iz (43.70[A]) and If (14.50[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 8.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF27 S201-C10
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC23 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF28 S201-C10
Load data
(L3-N)
Passed
Voltage [V] 230.94 IB ( 6.50[A]) <= Ith (10.00[A]) <= Iz (34.20[A]) and If (14.50[A]) <= 1.45*Iz (49.59[A]); Uref=400V
IB (A) [A] 6.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF28 S201-C10
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 7 8 10
Protection of Lv Cables
-WC24 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF29 S201-C10
Load data
(L1-N)
Passed
Voltage [V] 230.94 IB ( 8.66[A]) <= Ith (10.00[A]) <= Iz (43.70[A]) and If (14.50[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 8.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF29 S201-C10
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC25 LIGHT-5
Phases - Distribution System LN / TN-S Overload: protected by -QF30 S201-C6
Load data
(L2-N)
Passed
Voltage [V] 230.94 IB ( 5.20[A]) <= Ith ( 6.00[A]) <= Iz (34.20[A]) and If ( 8.70[A]) <= 1.45*Iz (49.59[A]); Uref=400V
IB (A) [A] 5.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF30 S201-C6
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x4)+1G4
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD24 F204 AC-40/0,1
Passed
Length (m) [m] 18 2 Id ( 0.10[A]) <= Ikmin L-PE ( 0.59[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC26 SOCKET-1
Phases - Distribution System LN / TN-S Overload: protected by -QF32 S201-C16
Load data
(L2-N)
Passed
Voltage [V] 230.94 IB (12.99[A]) <= Ith (16.00[A]) <= Iz (43.70[A]) and If (23.20[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 13.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF32 S201-C16
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 8 9 10
Protection of Lv Cables
-WC27 SOCKET-2
Phases - Distribution System LN / TN-S Overload: protected by -QF33 S201-C20
Load data
(L3-N)
Passed
Voltage [V] 230.94 IB (14.31[A]) <= Ith (20.00[A]) <= Iz (59.85[A]) and If (29.00[A]) <= 1.45*Iz (86.78[A]); Uref=400V
IB (A) [A] 14.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF33 S201-C20
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x10)+1G10
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 18 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC28 SOCKET-3
Phases - Distribution System LN / TN-S Overload: protected by -QF34 S201-C16
Load data
(L3-N)
Passed
Voltage [V] 230.94 IB (12.27[A]) <= Ith (16.00[A]) <= Iz (46.00[A]) and If (23.20[A]) <= 1.45*Iz (66.70[A]); Uref=400V
IB (A) [A] 12.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF34 S201-C16
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 20 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC29 SOCKET-4
Phases - Distribution System LN / TN-S Overload: protected by -QF35 S201-C16
Load data
(L2-N)
Passed
Voltage [V] 230.94 IB (10.22[A]) <= Ith (16.00[A]) <= Iz (80.75[A]) and If (23.20[A]) <= 1.45*Iz (117.09[A]); Uref=400V
IB (A) [A] 10.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF35 S201-C16
Protection checks
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 9 10 10
Protection of Lv Cables
-WC30 SOCKET-5
Phases - Distribution System LN / TN-S Overload: protected by -QF36 S201-C50
Load data
(L1-N)
Passed
Voltage [V] 230.94 IB (14.31[A]) <= Ith (50.00[A]) <= Iz (57.00[A]) and If (72.50[A]) <= 1.45*Iz (82.65[A]); Uref=400V
IB (A) [A] 14.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF36 S201-C50
Protection checks
Cosphi 0.90 Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x10)+1G10
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 10 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
-WC31 SOCKET-6
Phases - Distribution System LN / TN-S Overload: protected by -QF37 S201-C20
Load data
(L2-N)
Passed
Voltage [V] 230.94 IB (17.32[A]) <= Ith (20.00[A]) <= Iz (43.70[A]) and If (29.00[A]) <= 1.45*Iz (63.36[A]); Uref=400V
IB (A) [A] 17.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF37 S201-C20
Cosphi 0.90 Protection checks Passed
Protection guaranteed up to Ik LN ( 2.67[kA]), Ik L-PE ( 2.55[kA]); Uref=400V
Cable cross-sections 2x(1x6)+1G6
Conductor - Insulator Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QD31 F204 AC-63/0,03
Passed
Length (m) [m] 8 2 Id ( 0.03[A]) <= Ikmin L-PE ( 0.71[kA]) and Td (0.04[s]) <= Max tripping time (0.40[s]); Uref=400V
Cable
Passed
Voltage [V] 400 IB (1113.47[A]) <= Ith (1280.00[A]) <= Iz (2094.82[A]) and If (1664.00[A]) <= 1.45*Iz (3037.49[A]); Uref=400V
IB (A) [A] 1443.4
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks
Cosphi 0.95
Cable cross-sections 8x(1x630)+2G240
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 20 2
Cable
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 10 10
Protection of busways
-BW1 SMDB
Phases - Distribution System LLLN / TN-S Overload
Load data
Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protective device
IB (A) [A] 922.3 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.45[kA]), Ik LN ( 3.45[kA]); Uref=400V
Cable
-BW2 SMDB-F1
Phases - Distribution System LLLN / TN-S Overload
Load data
Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protective device
IB (A) [A] 786.6 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.29[kA]), Ik LN ( 3.23[kA]); Uref=400V
Cable
-BW3 SMDB-F2
Phases - Distribution System LLLN / TN-S Overload
Load data
Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protective device
IB (A) [A] 582.1 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.28[kA]), Ik LN ( 3.21[kA]); Uref=400V
Cable
-BW4 SMDB-F3
Phases - Distribution System LLLN / TN-S Overload
Load data
Voltage [V] 400 -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protective device
IB (A) [A] 327.2 IB (922.26[A]) <= Ith (950.00[A]) <= Iz (1600.00[A]) and If (1235.00[A]) <= 1.45*Iz (2320.00[A]); Uref=400V
Cosphi 0.90 Short circuit
Model 1600A Cu Busway -QF4 E1.2C 1000 Ekip Dip LSIG 1000 Passed
Protection guaranteed up to Ik LLL ( 3.27[kA]), Ik LN ( 3.19[kA]); Uref=400V
Cable
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
Report of LV circuit breakers
B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)
Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type
C -QF2 MDB 4P 2500 66.0 66.0 On 0.62 On 6.00 Off Off (null)
E2.2N 2500 Ekip Dip LSIG 2500 LV INCOMER 24s I2t const. 0.30s 4.00 I2t const.
E1.2C 1000 Ekip Dip LSIG 1000 SMDB 3s t const. 0.10s 4.00 I2t const. 0.10s
XT4N 250 Ekip LSI R250 SMDB 60s I2t const. 0.1s 4.50
K
-QF10 SMDB 3P 160 36.0 36.0 On 0.56 On 3.50 Off (null)
L
-QF11 SMDB 3P 32 36.0 36.0 28.9
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
Report of LV circuit breakers
B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)
Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type
K
-QF23 MCC 3P 4 36.0 36.0
L
-QF25 FINAL DB 1P 16 10.0 7.5 16.0
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
Report of LV circuit breakers
B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)
Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type
K
-QF35 FINAL DB 1P 16 10.0 7.5 16.0
L
-QF36 FINAL DB 1P 50 10.0 0.0 50.0
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
Report of LV circuit breakers
B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)
Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type
D -QF38 MDB 3P 1600 50.0 50.0 On 0.80 On 3.00 Off Off (null)
E1.2C 1600 Ekip Dip LSIG 1600 GENERATOR INCOMER 3s t const. 0.20s 4.00 I2t const.
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
N Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 4 4
Discrimination
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 3
Discrimination
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 3
Discrimination
Rev. n°1 Date: Description Customer: M/S ABC ELECTRICALS Drawing number:
Rev. n°2 Drafter: MDB SS1 Project: TOWER-1
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 3