Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Calculation and Dimensioning Criteria

Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

Calculation and dimensioning criteria

Calculation method-standard IEC 61363

Standard for cable dimensioning IEC 60092

Overload Overload verifications are made according the following relations: IB <= In <= Iz and I2 <= 1.45*Iz

Legenda:

IB = the current for which the circuit is designed

In = nominal current of the protective device (For adjustable protective devices, the nominal current In is the current setting selected)

I2 = current ensuring effective operation in the conventional time of the protective device

Iz = cable carrying capacity according the chosen standard

Short Circuit Circuit breakers and fuses are dimensioned with a breaking capacity higher than the maximum short circuit current in the point of installation

Circuit breakers dimensioned according to IEC 60497-2 are also chosen with the making capacity Icm higher than the maximum peak current

The protection against short circuit must satisfy the rule I²t <= K²S²

Legenda:

I²t = let-through energy at the maximum short circuit current (defined by the producer)

S = section of the conductors

K = factor defined in IEC60364-4-43 table 43A and IEC60364-5-54 tables A.54.2, A.54.4 and A-54.5

Indirect contact TT systems: the verification is Idn * Ra <= Vo, or Im <= Ib min

TN systems: the verification is Im <= Ib min

Legenda:

Idn = sensitivity of the residual current device

Ra = earthing resistance

Uo = max admitted contact voltage

Im = tripping value of the protective device at time limit

Ib min = minimum short circuit current at line end

Discrimination and Back-up The discrimination and back-up values are determined by the producer with laboratory tests

Discrimination not required in the installation

Backup not required in the installation

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short-circuit calculation hypothesis for IEC 60909-0

Calculation algorithm

The calculation of maximum and minimum, balanced and unbalanced, short-circuit currents is made by application of symmetrical components.

General conditions

The calculation of maximum and minimum short-circuit currents is based on the following simplifications.

a) For the duration of the short circuit, there is no change in the type of short circuit involved (a three-phase short circuit remains three-phase)

b) For the duration of the short circuit, there is no change in the network involved.

c) The impedance of the transformers is referred to the tap-changer in main position.

d) Arc resistances are not taken into account.

e) All line capacitances and shunt admittances and non-rotating loads, except those of the zero-sequence system, are neglected.

Maximum short-circuit currents

In the calculation of maximum short-circuit currents, the following conditions have been considered:

- it is applied the voltage factor cmax according to table 1, IEC 60909-0

- it is chosen the network configuration which leads to the maximum value of short-circuit current at the short-circuit location

- the contribution of asynchronous motors is considered if their contribution is higher than 5% of the initial short-circuit current calculated without motors

- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 20°C

Minimum short-circuit currents

In the calculation of minimum short-circuit currents, the following conditions have been considered:

- it is applied the voltage factor cmin according to table 1, IEC 60909-0

- it is chosen the network confguration which lead to the minimum value of short-circuit current at the short-circuit location

- the contribution of asynchronous motors is neglected

- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 250°C (EPR),160°C (PVC) or 140°C (PVC >300m²)

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


-BW1
2500A Cu Busway
A QF17
L = 23 m
du = 0.00
IB = 693.2 A
Iz = 2650.0 A

-QF1
E2.2N 2500 Ekip Dip LSI 2500
Un [V] 415 QF17
LLLN / TN-S
Ik LLL [kA] 61.2
Ik LN [kA] 0.1
Ik LPE [kA] 0.1
B P [kW] 426.5 -B1
Q [kvar] 257.6 -B3
FU = 1.00
U=414.3 V
IB = 693.2 A
    Cosphi = 0.86
-QF3 -QF4 -QF5 -QF6 Ik max = 57.6 kA
XT2S 160 TMA 40-400 E2.2N 2500 Ekip Dip LSI 2500 XT2S 160 TMA 40-400 E2.2N 800 Ekip Dip LSI 800
PDB-Q1-204 MDB-Q1-501 PDB-Q1-205

   
-WC2 -BW2 -WC3 -WC4
PDB-Q1-204 2500A Cu Busway PDB-Q1-205 2x 5G300
5G16 L = 13 m 5G16 Ib = 0.0 A
Ib = 7.3 A du = 0.00 Ib = 7.6 A Iz = 784.0 A
Iz = 63.0 A IB = 678.3 A Iz = 63.0 A dV = 0.00 %
dV = 0.12 % Iz = 2650.0 A dV = 0.09 % L = 20 m
L = 34 m L = 25 m
1
 MDB-Q1-501  
-L2 -L3 -C1
D PDB-Q1-204 PDB-Q1-205 Sn = 0.00 kVA
Sn = 5.23 [kVA] Sn = 5.49 [kVA] Q = 0.00 kvar
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 IB = 0.0 A
In = 7.3 [A] In = 7.6 [A]
U = 413.8 [V] U = 413.9 [V]
dU = 0.30 % dU = 0.27 %
P = 4.70 [kW] P = 4.93 [kW]
Q = 2.27 [kvar] Q = 2.39 [kvar]

(*) The circuit-breaker is in discrimination relations with other circuit-breakers


(!) Important notice about coordination to be verified in Discrimination report
(**) The circuit-breaker is in back-up relations with other circuit-breakers
F

G
Rev. n°1 Date: Description Customer: Drawing number:
Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A 1


-QF7
E2.2N 2500 Ekip Dip LSI 2500

B
-B2
FU = 1.00
U=413.9 V
IB = 678.3 A
Cosphi = 0.85
    Ik max = 54.9 kA
-QF8 -QF9 -QF10 -QF11
T5S 630 PR221DS-LS/I 630A XT2S 160 TMA 63-630 XT2S 160 TMA 100-1000 T5S 400 PR221DS-LS/I 400A
MCC-Q1-503 EALFP2 SSLFP RETRACTABLE ROOF

   
-WC5 -WC6 -WC7 -WC8
MCC-Q1-503 EALFP2 SSLFP RETRACTABLE ROOF
2x 5G300 5G70/35 5G120/70 2x 5G150
Ib = 401.8 A Ib = 22.8 A Ib = 37.1 A Ib = 218.7 A
Iz = 784.0 A Iz = 157.5 A Iz = 224.0 A Iz = 511.0 A
dV = 1.13 % dV = 0.54 % dV = 0.46 % dV = 0.96 %
L = 135 m L = 190 m L = 159 m L = 133 m
2
MCC-Q1-503   
-L4 -L5 -L8
D EALFP2 SSLFP RETRACTABLE ROOF
Sn = 16.41 [kVA] Sn = 26.63 [kVA] Sn = 157.22 [kVA]
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90
In = 22.8 [A] In = 37.1 [A] In = 218.7 [A]
U = 411.6 [V] U = 412.0 [V] U = 409.9 [V]
dU = 0.81 % dU = 0.73 % dU = 1.23 %
P = 14.65 [kW] P = 23.79 [kW] P = 139.76 [kW]
Q = 7.10 [kvar] Q = 11.52 [kvar] Q = 67.69 [kvar]

(*) The circuit-breaker is in discrimination relations with other circuit-breakers


(!) Important notice about coordination to be verified in Discrimination report
(**) The circuit-breaker is in back-up relations with other circuit-breakers
F

G
Rev. n°1 Date: Description Customer: Drawing number:
Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

B 2
MCC-Q1-503


-QS3
MCC-Q1-503

C
-B3
FU = 1.00
U=409.2 V
IB = 401.8 A
Cosphi = 0.82
   Ik max = 23.8 kA
-QF12 -QF13 -QF14
XT3N 250 TMD 200-2000 XT3N 250 TMD 200-2000 XT3N 250 TMD 200-2000
HPP-Q1-001 HPP-Q1-002 HPP-Q1-003

  
-WC9 -WC10 -WC11
HPP-Q1-001 HPP-Q1-002 HPP-Q1-003
5G70/35 5G70/35 5G70/35
Ib = 133.9 A Ib = 133.9 A Ib = 133.9 A
Iz = 157.5 A Iz = 157.5 A Iz = 157.5 A
dV = 0.21 % dV = 0.21 % dV = 0.21 %
L = 12 m L = 12 m L = 12 m

M M M
E

(*) The circuit-breaker is in discrimination relations with other circuit-breakers


(!) Important notice about coordination to be verified in Discrimination report
(**) The circuit-breaker is in back-up relations with other circuit-breakers
F

G
Rev. n°1 Date: Description Customer: Drawing number:
Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 3
Distribution

Reference voltage [V] 415 Symmetrical short circuit current LLL [kA] 61.21
Phases LLLN Line-Neutral short circuit current LN [kA] 0.06
Distribution system TN-S Line-Ground short circuit current LPE [kA] 0.06

Active power P [kW] 426.54 Cmax


Reactive power Q [kvar] 257.55 Resistance at Reference voltage [mOhm]
Ib (A) [A] 693.19 Reactance at Reference voltage [mOhm]
Power factor Cosphi 0.86 Impedance at Reference voltage [mOhm]

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short circuit calculation

Switchboard Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Switchboard1

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short circuit currents (IEC61363)

Switchboard Ib LLL (kA) Ip LLL (kA) Ip LLL (kA)


Switchboard1 58.70 56.55 123.07

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Protection of Lv Cables

-WC2 PDB-Q1-204
Phases - Distribution System LLLN / TN-S Overload: protected by -QF3 XT2S 160 TMA 40-400
Load data

Passed
Voltage [V] 415 IB ( 7.28[A]) <= Ith (28.00[A]) <= Iz (63.00[A]) and If (36.40[A]) <= 1.45*Iz (91.35[A]); Uref=415V
IB (A) [A] 7.3
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF3 XT2S 160 TMA 40-400

Protection checks
Cosphi 0.90 Failed
Icu ( 50.0) < Ikmax ( 57.6) -> not adeguate breaking capacity, device is not suitable
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF3 XT2S 160 TMA 40-400
Passed
Length (m) [m] 34 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 63.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.12
Work Temp (°C) [°C] 45.5
Power loss [W] 6.89 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 5428171 2

-WC3 PDB-Q1-205
Phases - Distribution System LLLN / TN-S Overload: protected by -QF5 XT2S 160 TMA 40-400
Load data

Passed
Voltage [V] 415 IB ( 7.64[A]) <= Ith (28.00[A]) <= Iz (63.00[A]) and If (36.40[A]) <= 1.45*Iz (91.35[A]); Uref=415V
IB (A) [A] 7.6
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF5 XT2S 160 TMA 40-400
Protection checks

Cosphi 0.90 Failed


Icu ( 50.0) < Ikmax ( 57.6) -> not adeguate breaking capacity, device is not suitable
Cable cross-sections 5G16
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF5 XT2S 160 TMA 40-400
Passed
Length (m) [m] 25 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 63.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.09
Work Temp (°C) [°C] 45.6
Power loss [W] 5.58 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 5428171 2

-WC4
Phases - Distribution System LLLN / TN-S Overload: protected by -QF6 E2.2N 800 Ekip Dip LSI 800
Load data

Passed
Voltage [V] 415 OL - Load current could not be calculated
IB (A) [A] 0.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF6 E2.2N 800 Ekip Dip LSI 800
Protection checks

Cosphi 0.73 Passed


SC - Max IkLN could not be calculated
Cable cross-sections 2x 5G300
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF6 E2.2N 800 Ekip Dip LSI 800
Passed
Length (m) [m] 20 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 784.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.00
Work Temp (°C) [°C] 45.0
Power loss [W] 0.00 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 1908341538 2

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 4
Protection of Lv Cables

-WC5 MCC-Q1-503
Phases - Distribution System LLLN / TN-S Overload: protected by -QF8 T5S 630 PR221DS-LS/I 630A
Load data

Passed
Voltage [V] 415 IB (401.82[A]) <= Ith (403.20[A]) <= Iz (784.00[A]) and If (524.16[A]) <= 1.45*Iz (1136.80[A]); Uref=415V
IB (A) [A] 401.8
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF8 T5S 630 PR221DS-LS/I 630A

Protection checks
Cosphi 0.82 Failed
Icu ( 50.0) < Ikmax ( 53.8) -> not adeguate breaking capacity, device is not suitable
Cable cross-sections 2x 5G300
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF8 T5S 630 PR221DS-LS/I 630A
Passed
Length (m) [m] 135 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 784.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 1.13
Work Temp (°C) [°C] 55.5
Power loss [W] 2303.88 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 1908341538 2

-WC6 EALFP2
Phases - Distribution System LLLN / TN-S Overload: protected by -QF9 XT2S 160 TMA 63-630
Load data

Passed
Voltage [V] 415 IB (22.83[A]) <= Ith (44.10[A]) <= Iz (157.50[A]) and If (57.33[A]) <= 1.45*Iz (228.38[A]); Uref=415V
IB (A) [A] 22.8
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF9 XT2S 160 TMA 63-630
Protection checks

Cosphi 0.90 Failed


Icu ( 50.0) < Ikmax ( 54.9) -> not adeguate breaking capacity, device is not suitable
Cable cross-sections 5G70/35
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF9 XT2S 160 TMA 63-630
Passed
Length (m) [m] 190 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 157.5


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.54
Work Temp (°C) [°C] 45.8
Power loss [W] 86.69 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 103898595 2

-WC7 SSLFP
Phases - Distribution System LLLN / TN-S Overload: protected by -QF10 XT2S 160 TMA 100-1000
Load data

Passed
Voltage [V] 415 IB (37.05[A]) <= Ith (70.00[A]) <= Iz (224.00[A]) and If (91.00[A]) <= 1.45*Iz (324.80[A]); Uref=415V
IB (A) [A] 37.1
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF10 XT2S 160 TMA 100-1000
Protection checks

Cosphi 0.90 Failed


Icu ( 50.0) < Ikmax ( 54.9) -> not adeguate breaking capacity, device is not suitable
Cable cross-sections 5G120/70
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF10 XT2S 160 TMA 100-1000
Passed
Length (m) [m] 159 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 224.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.46
Work Temp (°C) [°C] 46.1
Power loss [W] 111.56 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 305334646 2

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 4
Protection of Lv Cables

-WC8 RETRACTABLE ROOF


Phases - Distribution System LLLN / TN-S Overload: protected by -QF11 T5S 400 PR221DS-LS/I 400A
Load data

Passed
Voltage [V] 415 IB (218.73[A]) <= Ith (224.00[A]) <= Iz (511.00[A]) and If (291.20[A]) <= 1.45*Iz (740.95[A]); Uref=415V
IB (A) [A] 218.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF11 T5S 400 PR221DS-LS/I 400A

Protection checks
Cosphi 0.90 Failed
Icu ( 50.0) < Ikmax ( 54.9) -> not adeguate breaking capacity, device is not suitable
Cable cross-sections 2x 5G150
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF11 T5S 400 PR221DS-LS/I 400A
Passed
Length (m) [m] 133 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 511.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.96
Work Temp (°C) [°C] 52.3
Power loss [W] 1330.10 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 477085385 2

-WC9 HPP-Q1-001
Phases - Distribution System LLLN / TN-S Overload: protected by -QF12 XT3N 250 TMD 200-2000
Load data

Passed
Voltage [V] 415 IB (133.94[A]) <= Ith (140.00[A]) <= Iz (157.50[A]) and If (182.00[A]) <= 1.45*Iz (228.38[A]); Uref=415V
IB (A) [A] 133.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF12 XT3N 250 TMD 200-2000
Protection checks

Cosphi 0.82 Passed


SC - Max IkLN could not be calculated
Cable cross-sections 5G70/35
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF12 XT3N 250 TMD 200-2000
Passed
Length (m) [m] 12 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 157.5


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.21
Work Temp (°C) [°C] 73.9
Power loss [W] 207.62 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 103898595 2

-WC10 HPP-Q1-002
Phases - Distribution System LLLN / TN-S Overload: protected by -QF13 XT3N 250 TMD 200-2000
Load data

Passed
Voltage [V] 415 IB (133.94[A]) <= Ith (140.00[A]) <= Iz (157.50[A]) and If (182.00[A]) <= 1.45*Iz (228.38[A]); Uref=415V
IB (A) [A] 133.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF13 XT3N 250 TMD 200-2000
Protection checks

Cosphi 0.82 Passed


SC - Max IkLN could not be calculated
Cable cross-sections 5G70/35
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF13 XT3N 250 TMD 200-2000
Passed
Length (m) [m] 12 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 157.5


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.21
Work Temp (°C) [°C] 73.9
Power loss [W] 207.62 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 103898595 2

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 4 4
Protection of Lv Cables

-WC11 HPP-Q1-003
Phases - Distribution System LLLN / TN-S Overload: protected by -QF14 XT3N 250 TMD 200-2000
Load data

Passed
Voltage [V] 415 IB (133.94[A]) <= Ith (140.00[A]) <= Iz (157.50[A]) and If (182.00[A]) <= 1.45*Iz (228.38[A]); Uref=415V
IB (A) [A] 133.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF14 XT3N 250 TMD 200-2000

Protection checks
Cosphi 0.82 Passed
SC - Max IkLN could not be calculated
Cable cross-sections 5G70/35
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF14 XT3N 250 TMD 200-2000
Passed
Length (m) [m] 12 2 NDT - Ikmin could not be calculated
Cable

Iz (A) [A] 157.5


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.21
Work Temp (°C) [°C] 73.9
Power loss [W] 207.62 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 103898595 2

Phases - Distribution System Overload: protected by


Load data

Voltage [V]
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks

Cosphi
Cable cross-sections
Conductor - Insulator Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 2
Cable

Iz (A) [A]
1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%)
Work Temp (°C) [°C]
Power loss [W] Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 2

Phases - Distribution System Overload: protected by


Load data

Voltage [V]
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks

Cosphi
Cable cross-sections
Conductor - Insulator Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 2
Cable

Iz (A) [A]
1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%)
Work Temp (°C) [°C]
Power loss [W] Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 2

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 4 4
Protection of busways

-BW1 QF17
Phases - Distribution System LLLN / TN-S Overload
Load data

Voltage [V] 415 -QF1 E2.2N 2500 Ekip Dip LSI 2500 Passed

Protective device
IB (A) [A] 693.2 IB (693.19[A]) <= Ith (1000.00[A]) <= Iz (2650.00[A]) and If (1300.00[A]) <= 1.45*Iz (3842.50[A]); Uref=415V
Cosphi 0.86 Short circuit
Model 2500A Cu Busway
Cable

Length (m) [m] 23 Indirect contact


Iz (A) [A] 2650.0 Passed
dU (%) 0.00

-BW2
Phases - Distribution System LLLN / TN-S Overload
Load data

Voltage [V] 415 -QF4 E2.2N 2500 Ekip Dip LSI 2500 Passed

Protective device
IB (A) [A] 678.3 IB (678.34[A]) <= Ith (1000.00[A]) <= Iz (2650.00[A]) and If (1300.00[A]) <= 1.45*Iz (3842.50[A]); Uref=415V
Cosphi 0.85 Short circuit
Model 2500A Cu Busway -QF4 E2.2N 2500 Ekip Dip LSI 2500 Passed
SC - Max IkLN could not be calculated
Cable

Length (m) [m] 13 Indirect contact


Iz (A) [A] 2650.0 -QF4 E2.2N 2500 Ekip Dip LSI 2500 Passed
dU (%) 0.00 NDT - Ikmin could not be calculated

Phases - Distribution System Overload


Load data

Voltage [V]
Protective device

IB (A) [A]
Cosphi Short circuit
Model
Cable

Length (m) [m] Indirect contact


Iz (A) [A]
dU (%)

Phases - Distribution System Overload


Load data

Voltage [V]
Protective device

IB (A) [A]
Cosphi Short circuit
Model
Cable

Length (m) [m] Indirect contact


Iz (A) [A]
dU (%)

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
List of LV devices

Sign Part code Type RCD code RCD type User description 1 User description 2
-QF1 1SDA071692R1 E2.2N 2500 Ekip Dip LSI 2500 QF17 MDB-200
-QF3 1SDA067575R1 XT2S 160 TMA 40-400 PDB-Q1-204
-QF4 1SDA071692R1 E2.2N 2500 Ekip Dip LSI 2500 MDB-Q1-501
-QF5 1SDA067575R1 XT2S 160 TMA 40-400 PDB-Q1-205
-QF6 1SDA071522R1 E2.2N 800 Ekip Dip LSI 800
-QF7 1SDA071692R1 E2.2N 2500 Ekip Dip LSI 2500
-QF8 1SDA054408R1 T5S 630 PR221DS-LS/I 630A MCC-Q1-503
-QF9 1SDA067577R1 XT2S 160 TMA 63-630 EALFP2
-QF10 1SDA067579R1 XT2S 160 TMA 100-1000 SSLFP
-QF11 1SDA054341R1 T5S 400 PR221DS-LS/I 400A RETRACTABLE ROOF
-QF12 1SDA068069R1 XT3N 250 TMD 200-2000 HPP-Q1-001
-QF13 1SDA068069R1 XT3N 250 TMD 200-2000 HPP-Q1-002
-QF14 1SDA068069R1 XT3N 250 TMD 200-2000 HPP-Q1-003
-QS3 1SDA060344R1 T6D 630 MCC-Q1-503

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF1 Switchboard1 4P 2500 66.0 0.0 On 0.40 On 0.60 On (null)

E2.2N 2500 Ekip Dip LSI 2500 QF17 12s I2t const. 0.20s 5.00

D -QF3 Switchboard1 4P 40 50.0 0.0 28.0

XT2S 160 TMA 40-400 PDB-Q1-204 360.0

E -QF4 Switchboard1 2500 66.0 0.0 On 0.40 Off On (null)

E2.2N 2500 Ekip Dip LSI 2500 MDB-Q1-501 3s I2t const. 4.00

F -QF5 Switchboard1 4P 40 50.0 0.0 28.0

XT2S 160 TMA 40-400 PDB-Q1-205 360.0

G -QF6 Switchboard1 4P 800 66.0 0.0 On 0.40 Off On (null)

E2.2N 800 Ekip Dip LSI 800 3s I2t const. 4.00

H -QF7 Switchboard1 4P 2500 66.0 66.0 On 0.40 Off On (null)

E2.2N 2500 Ekip Dip LSI 2500 3s I2t const. 4.00

I -QF8 Switchboard1 630 50.0 0.0 On 0.64 Off On (null)

T5S 630 PR221DS-LS/I 630A MCC-Q1-503 3s 4.50

J -QF9 Switchboard1 4P 63 50.0 0.0 44.1

XT2S 160 TMA 63-630 EALFP2 472.5

K
-QF10 Switchboard1 4P 100 50.0 0.0 70.0

XT2S 160 TMA 100-1000 SSLFP 750.0

L
-QF11 Switchboard1 4P 400 50.0 0.0 On 0.56 Off On (null)

T5S 400 PR221DS-LS/I 400A RETRACTABLE ROOF 3s 4.50

Rev. n°1 Date: Description Customer: Drawing number:


N Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF12 Switchboard1 4P 200 36.0 0.0 140.0

XT3N 250 TMD 200-2000 HPP-Q1-001 2000.0

D -QF13 Switchboard1 4P 200 36.0 0.0 140.0

XT3N 250 TMD 200-2000 HPP-Q1-002 2000.0

E -QF14 Switchboard1 4P 200 36.0 0.0 140.0

XT3N 250 TMD 200-2000 HPP-Q1-003 2000.0

Rev. n°1 Date: Description Customer: Drawing number:


N Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 2
List of Lv Cables

-WC2 PDB-Q1-204
Phases - Distribution System LLLN / TN-S IB L1 [A] 7.3 R Ph 20°C [mOhm] 39.33
Voltage [V] 415 IB L2 [A] 7.3 R Ph 160-250°C [mOhm] 75.52
Cable cross-sections 5G16 IB L3 [A] 7.3 X Ph [mOhm] 2.79
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 39.33
Method - Cosphi 0.90 R N 160-250°C [mOhm] 75.52
K factor 1.00 Iz (A) [A] 63.0 XN [mOhm] 2.79
Length (m) [m] 34 dU (%) [%] 0.12 R PE 20°C [mOhm] 39.33
Ib max (kA) [kA] 57.64 Power Loss (W) [W] 6.9 R PE 160-250°C [mOhm] 75.52
Ib min (kA) [kA] 3.14 Work Temp (°C) [°C] 45.5 X PE [mOhm] 2.79

-WC3 PDB-Q1-205
Phases - Distribution System LLLN / TN-S IB L1 [A] 7.6 R Ph 20°C [mOhm] 28.92
Voltage [V] 415 IB L2 [A] 7.6 R Ph 160-250°C [mOhm] 55.53
Cable cross-sections 5G16 IB L3 [A] 7.6 X Ph [mOhm] 2.05
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 28.92
Method - Cosphi 0.90 R N 160-250°C [mOhm] 55.53
K factor 1.00 Iz (A) [A] 63.0 XN [mOhm] 2.05
Length (m) [m] 25 dU (%) [%] 0.09 R PE 20°C [mOhm] 28.92
Ib max (kA) [kA] 57.64 Power Loss (W) [W] 5.6 R PE 160-250°C [mOhm] 55.53
Ib min (kA) [kA] 4.25 Work Temp (°C) [°C] 45.6 X PE [mOhm] 2.05

-WC4
Phases - Distribution System LLLN / TN-S IB L1 [A] 0.0 R Ph 20°C [mOhm] 0.62
Voltage [V] 415 IB L2 [A] 0.0 R Ph 160-250°C [mOhm] 1.18
Cable cross-sections 2x 5G300 IB L3 [A] 0.0 X Ph [mOhm] 0.73
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 0.62
Method - Cosphi 0.73 R N 160-250°C [mOhm] 1.18
K factor 1.00 Iz (A) [A] 784.0 XN [mOhm] 0.73
Length (m) [m] 20 dU (%) [%] 0.00 R PE 20°C [mOhm] 1.23
Ib max (kA) [kA] 57.64 Power Loss (W) [W] 0.0 R PE 160-250°C [mOhm] 2.37
Ib min (kA) [kA] 45.16 Work Temp (°C) [°C] 45.0 X PE [mOhm] 1.46

-WC5 MCC-Q1-503
Phases - Distribution System LLLN / TN-S IB L1 [A] 401.8 R Ph 20°C [mOhm] 4.16
Voltage [V] 415 IB L2 [A] 401.8 R Ph 160-250°C [mOhm] 8.00
Cable cross-sections 2x 5G300 IB L3 [A] 401.8 X Ph [mOhm] 4.93
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 4.16
Method - Cosphi 0.82 R N 160-250°C [mOhm] 8.00
K factor 1.00 Iz (A) [A] 784.0 XN [mOhm] 4.93
Length (m) [m] 135 dU (%) [%] 1.13 R PE 20°C [mOhm] 8.33
Ib max (kA) [kA] 53.78 Power Loss (W) [W] 2303.9 R PE 160-250°C [mOhm] 15.99
Ib min (kA) [kA] 18.44 Work Temp (°C) [°C] 55.5 X PE [mOhm] 9.85

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 3
List of Lv Cables

-WC6 EALFP2
Phases - Distribution System LLLN / TN-S IB L1 [A] 22.8 R Ph 20°C [mOhm] 50.24
Voltage [V] 415 IB L2 [A] 22.8 R Ph 160-250°C [mOhm] 96.46
Cable cross-sections 5G70/35 IB L3 [A] 22.8 X Ph [mOhm] 14.44
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 50.24
Method - Cosphi 0.90 R N 160-250°C [mOhm] 96.46
K factor 1.00 Iz (A) [A] 157.5 XN [mOhm] 14.44
Length (m) [m] 190 dU (%) [%] 0.54 R PE 20°C [mOhm] 100.48
Ib max (kA) [kA] 54.89 Power Loss (W) [W] 86.7 R PE 160-250°C [mOhm] 192.93
Ib min (kA) [kA] 2.42 Work Temp (°C) [°C] 45.8 X PE [mOhm] 15.01

-WC7 SSLFP
Phases - Distribution System LLLN / TN-S IB L1 [A] 37.1 R Ph 20°C [mOhm] 24.53
Voltage [V] 415 IB L2 [A] 37.1 R Ph 160-250°C [mOhm] 47.09
Cable cross-sections 5G120/70 IB L3 [A] 37.1 X Ph [mOhm] 11.77
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 24.53
Method - Cosphi 0.90 R N 160-250°C [mOhm] 47.09
K factor 1.00 Iz (A) [A] 224.0 XN [mOhm] 11.77
Length (m) [m] 159 dU (%) [%] 0.46 R PE 20°C [mOhm] 42.04
Ib max (kA) [kA] 54.89 Power Loss (W) [W] 111.6 R PE 160-250°C [mOhm] 80.72
Ib min (kA) [kA] 4.74 Work Temp (°C) [°C] 46.1 X PE [mOhm] 12.08

-WC8 RETRACTABLE ROOF


Phases - Distribution System LLLN / TN-S IB L1 [A] 218.7 R Ph 20°C [mOhm] 8.21
Voltage [V] 415 IB L2 [A] 218.7 R Ph 160-250°C [mOhm] 15.76
Cable cross-sections 2x 5G150 IB L3 [A] 218.7 X Ph [mOhm] 4.92
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 8.21
Method - Cosphi 0.90 R N 160-250°C [mOhm] 15.76
K factor 1.00 Iz (A) [A] 511.0 XN [mOhm] 4.92
Length (m) [m] 133 dU (%) [%] 0.96 R PE 20°C [mOhm] 16.41
Ib max (kA) [kA] 54.89 Power Loss (W) [W] 1330.1 R PE 160-250°C [mOhm] 31.51
Ib min (kA) [kA] 12.46 Work Temp (°C) [°C] 52.3 X PE [mOhm] 9.84

-WC9 HPP-Q1-001
Phases - Distribution System LLLN / TN-S IB L1 [A] 133.9 R Ph 20°C [mOhm] 3.17
Voltage [V] 415 IB L2 [A] 133.9 R Ph 160-250°C [mOhm] 6.09
Cable cross-sections 5G70/35 IB L3 [A] 133.9 X Ph [mOhm] 0.91
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 3.17
Method - Cosphi 0.82 R N 160-250°C [mOhm] 6.09
K factor 1.00 Iz (A) [A] 157.5 XN [mOhm] 0.91
Length (m) [m] 12 dU (%) [%] 0.21 R PE 20°C [mOhm] 6.35
Ib max (kA) [kA] 23.38 Power Loss (W) [W] 207.6 R PE 160-250°C [mOhm] 12.18
Ib min (kA) [kA] 13.11 Work Temp (°C) [°C] 73.9 X PE [mOhm] 0.95

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 3 3
List of Lv Cables

-WC10 HPP-Q1-002
Phases - Distribution System LLLN / TN-S IB L1 [A] 133.9 R Ph 20°C [mOhm] 3.17
Voltage [V] 415 IB L2 [A] 133.9 R Ph 160-250°C [mOhm] 6.09
Cable cross-sections 5G70/35 IB L3 [A] 133.9 X Ph [mOhm] 0.91
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 3.17
Method - Cosphi 0.82 R N 160-250°C [mOhm] 6.09
K factor 1.00 Iz (A) [A] 157.5 XN [mOhm] 0.91
Length (m) [m] 12 dU (%) [%] 0.21 R PE 20°C [mOhm] 6.35
Ib max (kA) [kA] 23.38 Power Loss (W) [W] 207.6 R PE 160-250°C [mOhm] 12.18
Ib min (kA) [kA] 13.11 Work Temp (°C) [°C] 73.9 X PE [mOhm] 0.95

-WC11 HPP-Q1-003
Phases - Distribution System LLLN / TN-S IB L1 [A] 133.9 R Ph 20°C [mOhm] 3.17
Voltage [V] 415 IB L2 [A] 133.9 R Ph 160-250°C [mOhm] 6.09
Cable cross-sections 5G70/35 IB L3 [A] 133.9 X Ph [mOhm] 0.91
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 3.17
Method - Cosphi 0.82 R N 160-250°C [mOhm] 6.09
K factor 1.00 Iz (A) [A] 157.5 XN [mOhm] 0.91
Length (m) [m] 12 dU (%) [%] 0.21 R PE 20°C [mOhm] 6.35
Ib max (kA) [kA] 23.38 Power Loss (W) [W] 207.6 R PE 160-250°C [mOhm] 12.18
Ib min (kA) [kA] 13.11 Work Temp (°C) [°C] 73.9 X PE [mOhm] 0.95

Phases - Distribution System IB L1 [A] R Ph 20°C [mOhm]


Voltage [V] IB L2 [A] R Ph 160-250°C [mOhm]
Cable cross-sections IB L3 [A] X Ph [mOhm]
Conductor - Insulator IB N [A] R N 20°C [mOhm]
Method Cosphi R N 160-250°C [mOhm]
K factor Iz (A) [A] XN [mOhm]
Length (m) [m] dU (%) [%] R PE 20°C [mOhm]
Ib max (kA) [kA] Power Loss (W) [W] R PE 160-250°C [mOhm]
Ib min (kA) [kA] Work Temp (°C) [°C] X PE [mOhm]

Phases - Distribution System IB L1 [A] R Ph 20°C [mOhm]


Voltage [V] IB L2 [A] R Ph 160-250°C [mOhm]
Cable cross-sections IB L3 [A] X Ph [mOhm]
Conductor - Insulator IB N [A] R N 20°C [mOhm]
Method Cosphi R N 160-250°C [mOhm]
K factor Iz (A) [A] XN [mOhm]
Length (m) [m] dU (%) [%] R PE 20°C [mOhm]
Ib max (kA) [kA] Power Loss (W) [W] R PE 160-250°C [mOhm]
Ib min (kA) [kA] Work Temp (°C) [°C] X PE [mOhm]

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 3 3
List of busways

-BW1 QF17 MDB-200


Phases - Distribution System LLLN / TN-S IB L1 [A] 693.2 R0 Ph Ik max [mOhm] 0.51
Voltage [V] 415 IB L2 [A] 693.2 R0 Ph Ik min [mOhm] 0.73
Model 2500A Cu Busway IB L3 [A] 693.2 X Ph [mOhm] 0.28
IB N [A] 0.0 R0 N Ik max [mOhm] 0.51
Cosphi 0.86 R0 N Ik min [mOhm] 0.73
XN [mOhm] 0.28
Length (m) [m] 23 Iz (A) [A] 2650.0 R0 PE Ik max [mOhm] 1.01
Ib max (kA) [kA] 61.6 dU (%) [%] 0.00 R0 PE Ik min [mOhm] 1.46
Ib min (kA) [kA] Power Loss (W) [W] 0.0 X PE [mOhm] 0.81

-BW2
Phases - Distribution System LLLN / TN-S IB L1 [A] 678.3 R0 Ph Ik max [mOhm] 0.29
Voltage [V] 415 IB L2 [A] 678.3 R0 Ph Ik min [mOhm] 0.41
Model 2500A Cu Busway IB L3 [A] 678.3 X Ph [mOhm] 0.16
IB N [A] 0.0 R0 N Ik max [mOhm] 0.29
Cosphi 0.85 R0 N Ik min [mOhm] 0.41
XN [mOhm] 0.16
Length (m) [m] 13 Iz (A) [A] 2650.0 R0 PE Ik max [mOhm] 0.57
Ib max (kA) [kA] 56.5 dU (%) [%] 0.00 R0 PE Ik min [mOhm] 0.82
Ib min (kA) [kA] 53.566 Power Loss (W) [W] 0.0 X PE [mOhm] 0.46

Phases - Distribution System IB L1 [A] R0 Ph Ik max [mOhm]


Voltage [V] IB L2 [A] R0 Ph Ik min [mOhm]
Model IB L3 [A] X Ph [mOhm]
IB N [A] R0 N Ik max [mOhm]
Cosphi R0 N Ik min [mOhm]
XN [mOhm]
Length (m) [m] Iz (A) [A] R0 PE Ik max [mOhm]
Ib max (kA) [kA] dU (%) [%] R0 PE Ik min [mOhm]
Ib min (kA) [kA] Power Loss (W) [W] X PE [mOhm]

Phases - Distribution System IB L1 [A] R0 Ph Ik max [mOhm]


Voltage [V] IB L2 [A] R0 Ph Ik min [mOhm]
Model IB L3 [A] X Ph [mOhm]
IB N [A] R0 N Ik max [mOhm]
Cosphi R0 N Ik min [mOhm]
XN [mOhm]
Length (m) [m] Iz (A) [A] R0 PE Ik max [mOhm]
Ib max (kA) [kA] dU (%) [%] R0 PE Ik min [mOhm]
Ib min (kA) [kA] Power Loss (W) [W] X PE [mOhm]

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
List of Loads

-L2 PDB-Q1-204
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 413.8
Rated voltage [V] 415 Active power P [kW] 4.70 Max allowed voltage drop by Standard [%] 4.0
IB [A] 7.3 Reactive power Q [kvar] 2.27 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.30

-L3 PDB-Q1-205
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 413.9
Rated voltage [V] 415 Active power P [kW] 4.93 Max allowed voltage drop by Standard [%] 4.0
IB [A] 7.6 Reactive power Q [kvar] 2.39 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.27

-L4 EALFP2
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 411.6
Rated voltage [V] 415 Active power P [kW] 14.65 Max allowed voltage drop by Standard [%] 4.0
IB [A] 22.8 Reactive power Q [kvar] 7.10 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.81

-L5 SSLFP
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 412.0
Rated voltage [V] 415 Active power P [kW] 23.79 Max allowed voltage drop by Standard [%] 4.0
IB [A] 37.1 Reactive power Q [kvar] 11.52 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.73

-L8 RETRACTABLE ROOF


Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 409.9
Rated voltage [V] 415 Active power P [kW] 139.76 Max allowed voltage drop by Standard [%] 4.0
IB [A] 218.7 Reactive power Q [kvar] 67.69 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 1.23

Phases - Distribution System Utilization factor [%] Computed voltage [V]


Rated voltage [V] Active power P [kW] Max allowed voltage drop by Standard [%] 4.0
IB [A] Reactive power Q [kvar] Max allowed voltage drop by user [%]
Cosphi Computed voltage drop [%]

Phases - Distribution System Utilization factor [%] Computed voltage [V]


Rated voltage [V] Active power P [kW] Max allowed voltage drop by Standard [%] 4.0
IB [A] Reactive power Q [kvar] Max allowed voltage drop by user [%]
Cosphi Computed voltage drop [%]

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
List of Busbars

-B1 -B3
Phases - Distribution System LLLN / TN-S Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor 1.00
Load data

Rated voltage [V] 415


Computed voltage [V] 414.3
IB [A] 693.2 Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi 0.86

-B2
Phases - Distribution System LLLN / TN-S Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor 1.00
Load data

Rated voltage [V] 415


Computed voltage [V] 413.9
IB [A] 678.3 Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi 0.85

-B3
Phases - Distribution System LLLN / TN-S Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor 1.00
Load data

Rated voltage [V] 415


Computed voltage [V] 409.2
IB [A] 401.8 Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi 0.82

Phases - Distribution System S.C. currents Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)
Demand factor
Load data

Rated voltage [V]


Computed voltage [V]
IB [A] Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi

Phases - Distribution System Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)
S.C. currents

Demand factor
Load data

Rated voltage [V]


Computed voltage [V]
IB [A] Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi

Rev. n°1 Date: Description Customer: Drawing number:


Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
List of Motor feeders

-MS2 HPP-Q1-001
Rated voltage [V] 400 Function Description Device Type
Rated current [A] 139.0

Coordination
Rated active power [kW] 75.0 Short-circuit protection -QF12 XT3N 250 TMD 200-2000
Motor

Efficiency 0.95 Overload protection -QF12 XT3N 250 TMD 200-2000


Cosphi 0.82 Line contactor -QF12 XT3N 250 TMD 200-2000
Starting method Direct starting (DOL) Star contactor
Coordination Type Type 2 Delta contactor

-MS3 HPP-Q1-002
Rated voltage [V] 400 Function Description Device Type
Rated current [A] 139.0

Coordination
Rated active power [kW] 75.0 Short-circuit protection -QF13 XT3N 250 TMD 200-2000
Motor

Efficiency 0.95 Overload protection -QF13 XT3N 250 TMD 200-2000


Cosphi 0.82 Line contactor -QF13 XT3N 250 TMD 200-2000
Starting method Direct starting (DOL) Star contactor
Coordination Type Type 2 Delta contactor

-MS4 HPP-Q1-003
Rated voltage [V] 400 Function Description Device Type
Rated current [A] 139.0

Coordination
Rated active power [kW] 75.0 Short-circuit protection -QF14 XT3N 250 TMD 200-2000
Motor

Efficiency 0.95 Overload protection -QF14 XT3N 250 TMD 200-2000


Cosphi 0.82 Line contactor -QF14 XT3N 250 TMD 200-2000
Starting method Direct starting (DOL) Star contactor
Coordination Type Type 2 Delta contactor

Rated voltage [V] Function Description Device Type


Rated current [A]
Coordination

Rated active power [kW] Short-circuit protection


Motor

Efficiency Overload protection


Cosphi Line contactor
Starting method Star contactor
Coordination Type Delta contactor

Rated voltage [V] Function Description Device Type


Rated current [A]
Coordination

Rated active power [kW] Short-circuit protection


Motor

Efficiency Overload protection


Cosphi Line contactor
Starting method Star contactor
Coordination Type Delta contactor
Rev. n°1 Date: Description Customer: Drawing number:
Rev. n°2 Drafter: Project:
Rev. n°3 Design.: File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1