34 TT 25 13 STT750 Manual
34 TT 25 13 STT750 Manual
34 TT 25 13 STT750 Manual
Temperature Transmitter
User’s Manual
34-TT-25-13
Revision 4
September 2017
While the information in this document is presented in good faith and believed to be
accurate, Honeywell disclaims any implied warranties of merchantability and fitness for a
particular purpose and makes no express warranties except as may be stated in the written
agreement with and for its customers. In no event is Honeywell liable to anyone for any
indirect, special, or consequential damages. The information and specifications in this
document are subject to change without notice.
Honeywell, TDC 3000, SFC, SmartLine, PlantScape, Experion PKS, and TotalPlant are
registered trademarks of Honeywell International Inc. Other brand or product names are
trademarks of their respective owners.
This manual is a detailed how to reference for installing, piping, wiring, configuring, starting up,
operating, maintaining, calibrating, and servicing Honeywell’s family of STT750 Temperature
Transmitters. Users who have a Honeywell STT750 SmartLine Temperature Transmitter
configured for HART protocol are referred to the STT750 SmartLine Series HART Option User’s
Manual, document number 34-TT-25-15.
The configuration of your Transmitter depends on the mode of operation and the options selected
for it with respect to operating controls, displays and mechanical installation. This manual
provides detailed procedures to assist first-time users, and it further includes keystroke
summaries, where appropriate, as quick reference or refreshers for experienced personnel.
For the Experion PKS, you will need to supplement the information in this document with the
data and procedures in the Experion Knowledge Builder.
For Honeywell’s TotalPlant Solutions (TPS), you will need to supplement the information in this
document with the data in the PM/APM SmartLine Transmitter Integration Manual, which is
supplied with the TDC 3000 book set. (TPS is the evolution of the TDC 3000).
Release Information:
Patent Notice
The Honeywell STT750 SmartLine Temperature Transmitter family is covered by one or more of the
following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other
patents pending.
For Europe, Asia Pacific, North and South America contact details, refer to the back page of this
manual or the appropriate Honeywell Solution Support web site:
Symbol Definition
TIP: Identifies advice or hints for the user, often in terms of performing a
task.
CAUTION Indicates a situation which, if not avoided, may result in equipment or work
(data) on the system being damaged or lost, or may result in the inability to
properly operate the process.
continued
The Canadian Standards mark means the equipment has been tested and meets
applicable standards for safety and/or performance.
The Ex mark means the equipment complies with the requirements of the
European standards that are harmonized with the 94/9/EC Directive (ATEX
Directive, named after the French "ATmosphere EXplosible").
1. Introduction .................................................................................................................................... 1
1.1. Overview ................................................................................................................................ 1
1.2. Features and Options .............................................................................................................. 1
1.2.1. Physical Characteristics .................................................................................................. 1
1.2.2. Functional Characteristics .............................................................................................. 2
1.3. STT750 SmartLine Transmitter Nameplate ........................................................................... 3
1.4. Safety Certification Information............................................................................................. 3
1.5. Transmitter Adjustments ........................................................................................................ 3
1.6. Display.................................................................................................................................... 4
1.7. Optional 3-Button Assembly .................................................................................................. 4
2. Application Design ......................................................................................................................... 5
2.1. Overview ................................................................................................................................ 5
2.2. Safety ...................................................................................................................................... 5
2.2.1. Accuracy ......................................................................................................................... 5
2.2.2. Diagnostic Messages ...................................................................................................... 5
3. Installation and Startup ................................................................................................................... 7
3.1. Installation Site Evaluation..................................................................................................... 7
3.2. Honeywell MC Toolkit........................................................................................................... 7
3.3. Display Installation Precautions ............................................................................................. 7
3.4. Mounting STT750 SmartLine Temperature Transmitters ...................................................... 8
3.4.1. Summary......................................................................................................................... 8
3.4.2. Mounting Dimensions .................................................................................................. 10
3.4.3. Bracket Mounting Procedure ........................................................................................ 12
3.5. Wiring a Transmitter ............................................................................................................ 13
3.5.1. Loop Power Overview .................................................................................................. 13
3.5.2. Wiring Variations ......................................................................................................... 15
3.5.3. Loop Wiring Procedure ................................................................................................ 15
3.5.4. Grounding and Lightning Protection ............................................................................ 16
3.5.5. Explosion-Proof Conduit Seal ...................................................................................... 16
3.5.6. Input Sensor Wiring ..................................................................................................... 17
3.6. Startup .................................................................................................................................. 18
3.6.1. Overview ...................................................................................................................... 18
3.6.2. Startup Tasks ................................................................................................................ 18
3.6.3. Output Check Procedures ............................................................................................. 18
3.6.4. Constant Current Source Mode Procedure ................................................................... 19
4. Operation ...................................................................................................................................... 20
4.1. Overview .............................................................................................................................. 20
4.2. Three-Button Operation........................................................................................................ 20
4.2.1. Menu Navigation .......................................................................................................... 21
4.2.2. Data Entry..................................................................................................................... 21
4.2.3. Editing a Numeric Value .............................................................................................. 22
4.2.4. Selecting a new setting from a list of choices .............................................................. 22
4.2.5. The Display Menu ........................................................................................................ 23
4.3. Three Button Operation with no Display Installed ............................................................... 27
4.3.1. Zero Adjustment ........................................................................................................... 27
4.3.2. Span Adjustment .......................................................................................................... 27
An optional 3-button assembly is available to set up and make adjustments to the Transmitter. In
addition, a Honeywell Multi-Communication (MC) Toolkit (not supplied with the Transmitter) can
facilitate setup and adjustment procedures.
You can readily identify the series and basic Transmitter type from the key number. The letter in the
third digit represents one of these basic transmitter types:
T = Temperature
For a complete selection breakdown, refer to the appropriate Specification and Model Selection
Guide provided as a separate document.
The user can also use the Honeywell MC Toolkit or other third-party hand-held to make any
adjustments to an STT750 SmartLine Temperature Transmitter.
Safety
Input and output data
Reliability
Environmental limits
Installation considerations
Operation and maintenance
Repair and replacement
2.2. Safety
2.2.1. Accuracy
The STT750 SmartLine Temperature Transmitter (Transmitter) measures the temperature of a process
and reports the measurement to a receiving device. Refer to STT750 Specification,
34-TT-03-16.
Critical Diagnostics
(Failure Conditions)
Temperature Sensor Module Failure
Communication Module Failure
Sensor Comm. Timeout
Input Fault
Environmental Conditions:
o Ambient Temperature
o Relative Humidity
Potential Noise Sources:
o Radio Frequency Interference (RFI)
o Electromagnetic Interference (EMI)
Vibration Sources
o Pumps
o Motorized System Devices (e.g., pumps)
o Valve Cavitation
Process Parameters
o Temperature
o Maximum Sensor Input Ratings
The display update rate may increase at cold temperature extremes, but as with readability, normal
updating resumes when temperatures are within limits for full operability.
*Note 1: Figure 6 and 7. The housing adapter may not be present on all transmitter models. If the
housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.
1. Align the two mounting holes in the transmitter with the two slots in the mounting bracket
and assemble the (2) M8 hex cap screws, (2) lockwashers and (2) flat washers provided.
Rotate transmitter assembly to the desired position and torque the M8 hex cap screws to 27,0
Nm/20,0 Lb-ft maximum.
2. Pipe Mount Option: Refer to Figure 10. Position the bracket on a 2-inch (50.8 mm) horizontal
or vertical pipe, and install a “U” bolt around the pipe and through the holes in the bracket.
Secure the bracket with the nuts, flat washers and lock washers provided.
3. Wall Mount Option: Position the bracket on the mounting surface at the desired location and
secure the bracket to the mounting surface using the appropriate hardware (Wall mounting
hardware requirements to be determined and supplied by the end user).
Figure 10 – Pipe Mounting Bracket Secured to a Horizontal or Vertical Flat Pipe and Angle pipe
Loop wiring is connected to the Transmitter by simply attaching the positive (+) and negative (–) loop
wires to the positive (+) and negative (–) terminals on the Transmitter terminal block in the
Electronics Housing. Connect the Loop Power wiring shield to earth ground only at the power supply
end. Note that the Transmitter is not polarity-sensitive.
As shown in Figure 12, each Transmitter has an internal terminal to connect it to earth ground.
Optionally, a ground terminal can be added to the outside of the Electronics Housing. Grounding the
Transmitter for proper operation is required, as doing so tends to minimize the possible effects of
noise on the output signal and affords protection against lightning and static discharge. An optional
lightning terminal block can be installed in place of the non-lightning terminal block for Transmitters
that will be installed in areas that are highly susceptible to lightning strikes. As noted above, the Loop
Power wiring shield should only be connected to earth ground at the power supply end.
Note: Pin 9 is not used.
Wiring must comply with local codes, regulations and ordinances. Grounding may be
required to meet various approval body certification, for example CE conformity. Refer to
Appendix A of this document for details.
For HART the Transmitter is designed to operate in a two-wire power/current loop with loop
resistance and power supply voltage within the operating range; see Figure 11.
Figure 11. With an optional remote meter, the voltage drop for this must be added to the basic power
supply voltage requirements to determine the required Transmitter voltage (VXMTR) and maximum
loop resistance (RLOOP MAX). Additional consideration is required when selecting intrinsic safety
barriers to ensure that they will supply at least minimum Transmitter voltage (VXMTR MIN), including
the required 250 ohms of resistance (typically within the barriers) needed for digital communications.
In this calculation:
VXMTR MIN = 11.8 V (HART) VSM = 2.3 V, remote meter
Note that VSM should only be considered if a remote meter will be connected to the transmitter.
The positive and negative loop wires are connected to the positive (+) and negative (–) terminals on
the terminal block in the Transmitter Electronics Housing.
Barriers can be installed per Honeywell’s instructions for Transmitters to be used in intrinsically safe
applications.
For grounded Thermocouple inputs, connect the Internal Ground Connection shown in Figure 12 to
the same earth ground as used by the thermocouple.
As noted above, the Loop Power wiring shield should only be connected to earth ground at the power
supply end.
The actual steps in a startup procedure vary based on the type of Transmitter and the measurement
application. In general, the procedures in this section are based on using Honeywell MC Toolkit, with
a HART variant, to check the Transmitter input and output under static process conditions, and make
adjustments as required initiating full operation with the running process.
Note: Checks can be made using the optional three-button assembly, if your Transmitter is so
equipped. Operation with the three-button assembly is discussed in the “Operation” section of this
manual.
The Loop Test procedure checks for continuity and the condition of components in the output
current loop.
The Trim DAC Current procedure calibrates the output of the Digital-to-Analog converter for
minimum (0%) and maximum (100%) values of 4 mA and 20 mA, respectively. This
procedure is used for Transmitters operating online in analog mode to ensure proper
operation with associated circuit components (for example, wiring, power supply, control
equipment). Precision test equipment (an ammeter or a voltmeter in parallel with precision
resistor) is required for the Trim DAC Current procedure.
The Apply Values procedure uses actual Process Variable (PV) input levels for calibrating
the range of a Transmitter. The PV is carefully adjusted to stable minimum and maximum
levels, and the Lower Range Limit Value (LRV) and Upper Range Limit Value (URV) are
then set by commands from the MC Toolkit.
The Transmitter does not measure the given PV input or update the PV output while it
operates in the Output mode.
1. Refer to Figure 14 for test connections. Verify the integrity of electrical components in the output
current loop.
2. Establish communication with the Transmitter. For these procedures, the values of components in
the current loop are not critical if they support reliable communication between the Transmitter
and the Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
5. Select the desired constant-level Output: 0 %, 100 %, or Other (any between 0 % - 100 %).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the Transmitter in Analog mode, you can observe the output on an externally-
connected meter or on a local meter.
7. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
8. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
9. Select Yes to continue. This concludes the Startup procedure.
Use the and buttons to scroll through or wrap around the list of menu items. Press the button
to select an item for data entry or activation. When an item is selected for data entry or activation, the
cursor will appear on the lower line of the LCD (Display) to allow editing of the value.
No action is taken against a menu item until the button is pressed.
After a user presses the button to begin a data entry operation, another button must be pressed
within 10 seconds or data entry will time out and the original value of the parameter will be
preserved.
If no button presses occur within 60 seconds, menu access will time out and the transmitter will exit
the menu and return to the PV display.
All numeric entries are clamped at the low or high limit if needed. You can determine the low and
high limit for a parameter by selecting either the H or L character while the cursor is positioned over
the left-most digit and press button. The Display will show the selected limit.
Screen
Numeric data entry Text entry
Symbol
Display the high limit for this parameter.
H This symbol only appears in the left-most Not Available
position of the data entry field.
Display the low limit for this parameter.
L This symbol only appears in the left-most Not Available
position of the data entry field.
↑ and ↓ to
Executing this selection corrects the select entry.
Do Sensor Cal Lo
Confirm Cal Low Point based on the input ↵ to enter
measurement
Executing this selection corrects the
Do Sensor Cal Hi
Confirm Cal High Point based on the input
measurement
Sensor LRV Lower Range Value representing 0% Read Only
####.##
output Parameter
Sensor URV Upper Range Value representing Read Only
####.##
100% output Parameter
Press ↵ to
enter menu
Executing this selection Resets the selection
Reset Sensor Cal
Confirm LRV, and URV Corrects back to
Factory values ↑ and ↓ to
select entry.
↵ to enter
Sensor CVD
(Applicable for Pt50, Callendar - Van Dusen RTD Read Only
Enabled, Disabled
Pt100, Pt200, Pt500 coefficients for Sensor Parameter
and Pt1000 RTDs only)
Enable or disable detection of Input
Break Detect Enable, Disable
wire break
When enabled, causes all critical
sensor input failures to latch to the
Critical Fault state. The fault may
Latching
Enabled, Disabled only be cleared by device reset.
When disabled, the critical sensor
input failure will be cleared if the
input recovers. Press ↵ to
enter menu
Determines the source of the Cold selection
CJ Type
Internal, Fixed Junction compensation for
thermocouple Sensor types. ↑ and ↓ to
When CJ Type is Fixed, specifies the select entry.
Fixed CJ Value Cold Junction temperature value for ↵ to enter
(Visible for TC input thermocouple Sensor types.
####.##
only) Degrees Celsius. Fixed CJ
temperatures below -50 degrees
have no effect on measured values.
The limits are:
LRV #. ## the Lower Range Limit (LRL) and the
URV #. ## Upper Range Limit (URL) of the
selected Sensor ID
Note: Loop must be DAC Span Trim Note: You must connect a current
removed from meter to the transmitter to monitor
Automatic Control the loop output.
1. Connect a current meter or voltmeter as shown in Figure 14 to monitor the PV output of the
Transmitter.
2. Using an accurate input source, apply a signal equivalent to the Transmitter LRV.
3. Press the Down (↓ ) and Zero ( ) buttons together to set the Zero.
4. Verify that the output is now 4 mA.
1. Connect a current meter or voltmeter as shown in Figure 14 to monitor the PV output of the
Transmitter.
2. Using an accurate input source, apply a signal equivalent to the desired Upper Range Value
of the transmitter.
3. Press the Down (↓) and Span ( ) buttons together to set the span.
4. Verify that the PV output is now 20 mA.
You can also use the MCT 202 and MCT404 Toolkit to make any adjustments to an
STT750 SmartLine Temperature Transmitter.
The Transmitter electronics module interprets either signal as not-a-number and initiates its own
configured failsafe action for the control system.
The failsafe direction display accessible via the Toolkit shows only the state of the
jumper as it correlates to analog Transmitter operation.
The integrated circuits in the Transmitter PWA are vunerable to damage by stray
static discharges when removed from the Electronics Housing. Minimize the possibility of
static discharge damage when handling the PWA as follows:
Do not touch terminals, connectors, component leads, or circuits when handling the PWA.
When removing or installing the PWA, handle it by its edges or bracket section only. If you
need to touch the PWA circuits, be sure you are grounded by staying in contact with a
grounded surface or by wearing a grounded wrist strap.
When the PWA is removed from the Transmitter, put it in an electrically conductive bag, or
wrap it in aluminum foil to protect it.
The following procedure outlines the steps for positioning the write protect and failsafe jumpers on
the electronics module. See Figure 16 for the locations of the failsafe and write protect jumpers.
Failsafe = UP (High)
Write Protect = OFF (Not Protected)
Failsafe = UP (High)
Write Protect = ON (Protected)
1. Turn OFF Transmitter power (Power removal is only required in accordance with
area safety approvals. Power removal is only required in Class 1 Div 1 Explosion
proof and Class 1 Div 2 environments).
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the
Transmitter housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
4. If necessary, unplug the interface connector from the Communication module. Do not
discard the connector.
5. Set the Failsafe Jumper (top jumper) to the desired position (UP or DOWN). See
Table 8 and Figure 16 for jumper positioning.
6. If applicable, re-install the Display module as follows:
Orient the display as desired.
Install the Interface Connector in the Display module such that it will mate
with the socket for the display in the Communication module.
Carefully line up the display, and snap it into place. Verify that the two tabs
on the sides of the display latch.
NOTE: Installing a Display Module into a powered transmitter may cause a temporary upset
to the loop output value.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
7. Restore transmitter power if removed.
4.5.1. Display
Figure 17
Figure 17 illustrates the Display format with Process Variable (PV).
The PV value is user-configurable. This field has 7 characters. The maximum allowable
numeric value is 9999999 or -999999. If fractional decimals are configured, the fractional
positions will be dropped, as required. If the PV value exceeds the above limits, it is divided
by 1000 and “K” is appended to the result, allowing a maximum value with multiplier of
999999K or -99999K.
Process Variable Tag is user-configurable from a HART Host. This field has 14 characters.
Engineering Units. This field is user-configurable when measuring temperature.
The transmitter does not have to be removed from service to replace the Comm
Module
Please take appropriate steps to avoid ESD damage when handling the
Communication and Display Module assemblies
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the
Transmitter housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
4. If necessary, unplug the Display interface connector from the Communication
module. Do not discard the connector.
5. Loosen the two retaining screws, and carefully pull the Communication module from
the Electronics compartment.
6. Carefully, insert the Communication module into the Electronics compartment.
7. Tighten the two Communication module retaining screws.
8. Refer to the SmartLine User's Manual to change the Failsafe and Write Protect
Jumper configuration settings.
9. If applicable, re-install the Display module as follows:
a) Orient the display as desired.
b) Install the Interface Connector in the Display module such that it will mate with the
socket for the display in the Communication module.
c) Carefully line up the display, and snap it into place. Verify that the two tabs on the
sides of the display latch.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
10. Apply Parker Super O-ring Lubricant or equivalent to the end cap O-ring before
installing the end cap. Reinstall the End Cap and tighten the End Cap locking screw.
11. Installing Optional External Configuration Button Assembly.
a) Loosen (Do Not Remove) both top nameplate screws and pivot nameplate 90°.
b) Align the protrusion on the button assembly with the matching opening in the
housing and snap the button assembly into the housing.
c) Rotate the nameplate back to the original position, and tighten the nameplate screws.
12. Loosen the End Cap locking screw and unscrew the End Cap from the Field Wiring
side of the transmitter housing.
13. Select the proper Communication/External Configuration upgrade kit label from the
label strip provided and adhere to the inside of the Field Wiring compartment End
Cap.
14. Apply Parker Super O-ring Lubricant or equivalent to the end cap o-ring before
installing the end cap. Reinstall the End Cap and tighten the end cap locking screw
15. Install external upgrade label (i.e. DEVICE MODIFIED…..) provided on outside of
housing as shown in Figure 18.
16. Restore power if removed.
17. Check the settings of the Transmitter Setup and Display Setup parameters to make
sure that the transmitter is configured correctly for your application. Refer to the
STT750 HART manual (34-TT-25-15) for details on HART transmitters.
18. If applicable, verify External Button Configuration operation.
Installation is complete.
One calibration option is to use the Honeywell MC Toolkit (MCT). Refer to the MC Toolkit
(MCT202) User Manual, # 34-ST-25-20 or (MCT404) User Manual, Document # 34-ST-25-50.
Calibration information and procedures for a Transmitter operating in the HART mode are provided
in the STT750 Series HART Option User’s manual, document number 34-TT-25-15, Section on
“Calibration.”
When a Critical Diagnostic is present in the Transmitter, the Display will display the message
CRITICAL FAULT on the top line of the LCD and the appropriate diagnostic text on the lower line.
Individually saleable parts are indicated in each figure by key number callout.
Parts that are supplied in kits are indicated in each illustration by key number callout with the
letter K prefix.
3 50092363-501 Carbon Steel Wall Bracket Mounting kit for all models 1
4 50092363-503 316 Stainless Steel Wall Bracket Mounting kit for all models 1
5 30752770-007 Carbon Steel Angle Pipe Bracket Mounting kit for all models 1
6 30752770-407 316 Stainless Steel Angle Pipe Bracket Mounting kit for all models 1
Non-Incendive, Certificate:
FM16US0157X:
Class I, Division 2, Groups A, B, 4-20 mA/
-50oC to 85oC
C, D; T4 DE/HART Note 1
Class I Zone 2 AEx nA IIC T4 Gc /FF/ PROFIBUS
AEx nA IIC T4
Zone 1 Ex d IIC T4 Gb
Ex tb IIIC T 95oC IP 66 Db
DIP A21 Class II, III
Intrinsically Safe, Certificate:
2689056:
Class I, II, III, Division 1, Groups
A, B, C,
D, E, F, G; T4 4-20 mA/
Note 2 -50oC to 70oC
DE/HART/FF
Ex ia IIC T4 Ga
FISCO Field Device (Only for FF
Option)
Ex ia IIC T4
Non-Incendive, Certificate:
2689056:
B CSA-Canada Class I, Division 2, Groups A, B,
4-20 mA/
C, D; T4 Note 1 -50oC to 85oC
DE/HART/FF
Class I Zone 2 Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67 ALL ALL ALL
Standards:
CSA C22.2 No. 0-10; CSA 22.2 No. 25-1966 (reaffirmed 2009);
CSA C22.2 No. 30-M1986 (reaffirmed 2012); CSA C22.2 No. 94-M91;
CSA C22.2 No. 142-M1987 (reaffirmed 2009); CSA-C22.2No.157-92 (reaffirmed
2012);
C22.2 No. 213-M1987(reaffirmed 2012); C22.2 No. 60529-05
C22.2 No. CSA 60079-0:2011; C22.2 No. 60079-1: 2011; C22.2 No. 60079-11:
2011;
C22.2 No. 60079-15: 2012; C22.2 No. 60079-31: 2012;
SIL 2/3 IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to
Certification EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the following standards:
IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3: 2010.
MID Approval Issued by NMi Certin B.V. in accordance with WELMEC guide 8.8, OIML R117.1
Edition 2007 (E), and EN 12405-1+A2 Edition 2006. Applicable to Pt100 sensor only.
• For complete model number, see the Model Selection Guide for the particular model of
Temperature Transmitter.
• The serial number of the transmitter is located on the Housing data-plate. The first two
digits of the serial number identify the year (02) and the second two digits identify the week
of the year (23); for example, 0223xxxxxxxx indicates that the product was manufactured in
2002, in the 23rd week.
Explosion-Proof/ Flameproof:
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
Non-Incendive Equipment:
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAYBE PRESENT
Painted surface of the STT750 may store electrostatic charge and become a source of
ignition in applications with a low relative humidity less than approximately30% relative
humidity where the painted surface is relatively free of surface contamination such as dirt,
dust or oil. Cleaning of the painted surface should only be done with a damp cloth.
The installer shall provide transient over-voltage protection external to the equipment such
that the voltage at the supply terminal of the equipment does not exceed 140% of the
voltage rating of the equipment.
The enclosure is manufactured from low copper aluminium alloy. In rare cases, ignition
sources due to impact and friction sparks could occur. This shall be considered during
Installation, particularly if equipment is installed a Zone 0 location.
Or
• Contact your local Honeywell Process Solutions Customer Contact Centre (CCC) or Honeywell
Technical Assistance Centre (TAC) listed in the “Support and Contact information” section of this
document.
A I
About This Manual ..................................... iii Input Sensor Wiring .................................. 17
Accuracy .....................................................5 Installation and Startup...............................7
Application Design ......................................5 Display Installation Precautions ................................ 7
Mounting STT750 Temperature Transmitters ........... 7
Site evaluation ........................................................... 7
B Installation Site Evaluation
Bracket Mounting ..................................... 12 Site Evaluation ........................................................... 7
Introduction ...............................................1
C
M
Calibration Procedures .............................. 34
Changing the Default Failsafe Direction ..... 28 Maintenance ............................................ 31
Failsafe Operation ....................................................28 Preventive Maintenance Practices and Schedules .. 31
Replacing the Communication Module ................... 31
Copyrights, Notices and Trademarks ............ii
MCToolkit ...................................................7
Monitoring the Display ............................. 30
D
Monitoring the Displays
Diagnostic Messages ...................................5 Display ..................................................................... 30
Display Installation Precautions...................7 Mounting Dimensions ............................... 10
Display Options...........................................4 Mounting STT 750 Temperature Transmitters
...............................................................8
E Bracket Mounting Procedure .................................. 12
Mounting Dimentsions .............................................. 8
Explosion-Proof Conduit Seal .................... 16 Summary ................................................................... 8
F N
Features and Options ..................................1 Name Plate .................................................3
Functional Characteristics ..........................................2
Physical Characteristics ..............................................1 O
G Operation ................................................. 20
Changing the Default Failsafe Direction .................. 28
Glossary.................................................... 58 Three Button Operation with no Display Installed .. 27
Three-Button Operation .......................................... 20
Grounding and Lightning Protection .......... 16
Optional 3-Button Assembly........................4
H
P
Honeywell MC Toolkit .................................7
Parts List ................................................... 36
Patent Notice............................................. iv
PRODUCT CERTIFICATIONS ........................ 40
W
Wiring a Transmitter ................................. 13
Wiring Procedure .................................................... 15
Wiring Variations ..................................................... 15
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042