34 TT 25 03
34 TT 25 03
34 TT 25 03
Temperature Transmitter
User’s Manual
34-TT-25-03
Revision 6
November 2020
While the information in this document is presented in good faith and believed to be
accurate, Honeywell disclaims any implied warranties of merchantability and fitness for a
particular purpose and makes no express warranties except as may be stated in the written
agreement with and for its customers. In no event is Honeywell liable to anyone for any
indirect, special, or consequential damages. The information and specifications in this
document are subject to change without notice.
Honeywell, TDC 3000, SFC, Smartline, PlantScape, Experion PKS, and TotalPlant are
registered trademarks of Honeywell International Inc. Other brand or product names are
trademarks of their respective owners.
This manual is a detailed how to reference for installing, piping, wiring, configuring, starting up,
operating, maintaining, calibrating, and servicing Honeywell’s family of STT850 Temperature
Transmitters. Users who have a Honeywell STT850 SmartLine Temperature Transmitter
configured for HART protocol or Honeywell’s Digitally Enhanced (DE) are referred to the
STT850 SmartLine Series HART/DE Option User’s Manual, document number 34-TT-25-06.
Users who have a Honeywell STT850 SmartLine Temperature Transmitter configured for
Fieldbus operation are referred to the STT850 SmartLine Series Fieldbus Option User’s Manual,
document number (34-TT-25-07).
The configuration of your transmitter depends on the mode of operation and the options selected
for it with respect to operating controls, displays and mechanical installation. This manual
provides detailed procedures to assist first-time users, and it further includes keystroke
summaries, where appropriate, as quick reference or refreshers for experienced personnel.
• For the Experion PKS, you will need to supplement the information in this document with the
data and procedures in the Experion Knowledge Builder.
• For Honeywell’s TotalPlant Solutions (TPS), you will need to supplement the information in this
document with the data in the PM/APM SmartLine Transmitter Integration Manual, which is
supplied with the TDC 3000 book set. (TPS is the evolution of the TDC 3000).
Release Information:
Patent Notice
The Honeywell STT850 SmartLine Temperature Transmitter family is covered by one or more of the
following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other
patents pending.
For Europe, Asia Pacific, North and South America contact details, refer to the back page of this
manual or the appropriate Honeywell Solution Support web site:
Symbol Definition
TIP: Identifies advice or hints for the user, often in terms of performing a
task.
CAUTION Indicates a situation which, if not avoided, may result in equipment or work
(data) on the system being damaged or lost, or may result in the inability to
properly operate the process.
continued
The Canadian Standards mark means the equipment has been tested and meets
applicable standards for safety and/or performance.
The Ex mark means the equipment complies with the requirements of the
European standards that are harmonized with the 94/9/EC Directive (ATEX
Directive, named after the French "ATmosphere EXplosible").
An optional 3-button assembly is available to set up and make adjustments to the transmitter. In
addition, a Honeywell Multi-Communication (MC) Toolkit (not supplied with the transmitter) can
facilitate setup and adjustment procedures in the case of HART and DE. Certain adjustments can be
made through an Experion Station or a Universal Station if the transmitter is digitally integrated with
Honeywell’s Experion or TPS/TDC 3000 control system for HART and DE transmitters.
You can readily identify the series and basic transmitter type from the key number. The letter in the
third digit represents one of these basic transmitter types:
• T = Temperature
For a complete selection breakdown, refer to the appropriate specification and model selection guide
provided as a separate document.
For HART and DE you can also use the Honeywell MC Toolkit or other third-party hand-held to
make any adjustments to an STT850 SmartLine Temperature Transmitter. Alternately, certain
adjustments can be made through the Experion or Universal Station, if the transmitter is digitally
integrated with a Honeywell Experion or TPS system. In case of Fieldbus (FF) variants, adjustments
can be made using any Fieldbus compliant DCS or Asset management system including Honeywell
Experion PKS and Honeywell FDM. Any Fieldbus compliant third party handheld configuration may
also be used.
• Safety
• Input and output data
• Reliability
• Environmental limits
• Installation considerations
• Operation and maintenance
• Repair and replacement
2.2. Safety
2.1.1 Accuracy
The STT850 SmartLine Temperature Transmitter measures the temperature of a process and reports
the measurement to a receiving device. Refer to STT850 Specification, 34-TT-03-14.
• Environmental Conditions:
o Ambient Temperature
o Relative Humidity
• Potential Noise Sources:
o Radio Frequency Interference (RFI)
o Electromagnetic Interference (EMI)
• Vibration Sources
o Pumps
o Motorized System Devices (e.g., pumps)
o Valve Cavitation
• Process Parameters
o Temperature
o Maximum Sensor Input Ratings
The display update rate may increase at cold temperature extremes, but as with readability, normal
updating resumes when temperatures are within limits for full operability.
*Note 1: Figures 4 and 5. The housing adapter may not be present on all transmitter models. If the
housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.
Figure 6 – STT850 Pipe Mount with adapter housing - Horizontal & Vertical
* Note 1: In Figure 6 and 7 the housing adapter may not be present on all transmitter models. If the
housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.
1. Align the two mounting holes in the transmitter with the two slots in the mounting bracket
and assemble the (2) M8 hex cap screws, (2) lockwashers and (2) flat washers provided.
Rotate transmitter assembly to the desired position and torque the M8 hex cap screws to 27,0
Nm/20,0 Lb-ft maximum.
2. Pipe Mount Option: Refer to Figure 8. Position the bracket on a 2-inch (50.8 mm) horizontal
or vertical pipe, and install a “U” bolt around the pipe and through the holes in the bracket.
Secure the bracket with the nuts, flat washers and lock washers provided.
3. Wall Mount Option: Position the bracket on the mounting surface at the desired location and
secure the bracket to the mounting surface using the appropriate hardware (Wall mounting
hardware requirements to be determined and supplied by the end user).
For DE operation, add 2.0 V to these values. The Fieldbus transmitter operates from 9-32 V and does
not require a loop resistance.
Loop wiring is connected to the transmitter by simply attaching the positive (+) and negative (–) loop
wires to the positive (+) and negative (–) terminals on the transmitter terminal block in the Electronics
Housing. Connect the Loop Power wiring shield to earth ground only at the power supply end.
Note that the transmitter is not polarity-sensitive.
An optional lightning terminal block can be installed in place of the non-lightning terminal block for
transmitters that will be installed in areas that are highly susceptible to lightning strikes. As noted
above, the Loop Power wiring shield should only be connected to earth ground at the power supply
end.
As shown in Figure 12, each transmitter has an internal terminal to connect it to earth ground.
Optionally, a ground terminal can be added to the outside of the Electronics Housing.
Wiring must comply with local codes, regulations and ordinances. Grounding may be
required to meet various approval body certification, for example CE conformity. Refer to
Appendix A of this document for details.
CAUTION:
For proper operation of the transmitter, grounding of the transmitter is
mandatory. This minimizes the possible effects of noise on the output
signal and affords protection against lightning and static discharge.
Note: Terminal #3 is for loop test and is not applicable for Fieldbus option.
Terminal #4 is for Digital Output and is not applicable for Fieldbus option.
For HART and DE, the transmitter is designed to operate in a two-wire power/current loop with loop
resistance and power supply voltage within the operating range; see Figure 11. With an optional
remote meter, the voltage drop for this must be added to the basic power supply voltage requirements
to determine the required transmitter voltage (VXMTR) and maximum loop resistance (RLOOP MAX).
Additional consideration is required when selecting intrinsic safety barriers to ensure that they will
supply at least minimum transmitter voltage (VXMTR MIN), including the required 250 ohms of
resistance (typically within the barriers) needed for digital communications.
NOTE: 1) After wiring, torque the screws to around 4 to 5(lb-in). Maximum should not exceed
1.1 Nm (10 lb-in). Don’t pull the wires after connecting to the screw terminals.
2) Terminal Screw#6 has thermal paste on the tip of screw intentionally to improve the
performance of the transmitter. Do not remove or clean the thermal paste.
In this calculation:
VXMTR MIN = 11.8 V (HART) or 13.8V (DE) VSM = 2.3 V, remote meter
Note that VSM should only be considered if a remote meter will be connected to the transmitter.
The positive and negative loop wires are connected to the positive (+) and negative (–) terminals on
the terminal block in the transmitter Electronics Housing.
Barriers can be installed per Honeywell’s instructions for transmitters to be used in intrinsically safe
applications.
If you are digitally integrating a transmitter in an Allen Bradley Programmable Logic Controller
(PLC) process system, the same Field Terminal Assembly (FTA) and wiring procedures used with
Honeywell’s TPS system are also used with the Allen-Bradley 1771 and 1746 platforms.
For grounded Thermocouple inputs, connect the Internal Ground Connection shown in Figure 12 to
the same earth ground as used by the thermocouple.
As noted above, the Loop Power wiring shield should only be connected to earth ground at the power
supply end.
Figure 19 – Digital Output Connections for PLC Counting Pulse (HART only)
AWG 16 - Resistance vs. Wire Diameter [Resistance in ohms per double foot @ 20°C (68°F)].
Diameter - 0.051 inches (1.3 mm)
Honeywell recommends total resistance of thermocouple loop resistance under 100 Ohms. Beyond
100 Ohms and up to 4 K Ohms of thermocouple resistance device will be in operation with the
compromised accuracy.
You can also run an optional output check to wring out an analog loop and check out individual
Process Variable (PV) outputs in Digitally Enhanced (DE) mode before startup.
The actual steps in a startup procedure vary based on the type of transmitter and the measurement
application. In general, the procedures in this section are based on using Honeywell MC Toolkit, with
a HART or DE variant, to check the transmitter input and output under static process conditions, and
make adjustments as required initiating full operation with the running process.
Note: Checks can be made using the optional three-button assembly, if your transmitter is so
equipped. Operation with the three-button assembly is discussed in the “Operation” section of this
manual.
• The Loop Test procedure checks for continuity and the condition of components in the output
current loop.
• The Trim DAC Current procedure calibrates the output of the Digital-to-Analog converter for
minimum (0%) and maximum (100%) values of 4 mA and 20 mA, respectively. This
procedure is used for transmitters operating online in analog mode to ensure proper operation
with associated circuit components (for example, wiring, power supply, control equipment).
Precision test equipment (an ammeter or a voltmeter in parallel with precision resistor) is
required for the Trim DAC Current procedure.
• The Apply Values procedure uses actual Process Variable (PV) input levels for calibrating
the range of a transmitter. The PV is carefully adjusted to stable minimum and maximum
levels, and the Lower Range Limit Value (LRV) and Upper Range Limit Value (URV) are
then set by commands from the MC Toolkit.
The transmitter does not measure the given PV input or update the PV output while it
operates in the Output mode.
1. Refer to Figure 20 for test connections. Verify the integrity of electrical components in the output
current loop.
2. Establish communication with the transmitter. For these procedures, the values of components in
the current loop are not critical if they support reliable communication between the transmitter
and the Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
5. Select the desired constant-level Output: 0 %, 100 %, or Other (any between 0 % - 100 %).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the transmitter in Analog mode, you can observe the output on an externally-
connected meter or on a local meter.
7. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
8. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
9. Select Yes to continue. This concludes the Startup procedure.
When on a lower level menu, return to the menu above by selecting <Return>. Alternately, the (up
symbol) and (down symbol) buttons can be pressed simultaneously to return to the menu above.
When on the highest level menu, or when using the basic display menu, pressing the (up symbol) and
(down symbol) buttons simultaneously will exit the menu and return to the PV display. Use the and
buttons to scroll through the list of menu items. Press the ↵ button to select an item for data entry
or activation. When an item is selected for data entry or activation, the cursor will jump to the lower
line of the LCD (Basic Display) or call up a pop-up window (Advanced Display) to allow editing of
the value. No action is taken against a menu item until the ↵ button is pressed.
If a user presses the ↵ button to begin a data entry operation, they must press another button within
10 seconds or the transmitter firmware will assume that the user wants to abort the operation or has
walked away from the transmitter. After 10 seconds with no action, the data entry will time out and
the original value of the parameter will be preserved.
If no button presses occur within 60 seconds, menu access will time out and the transmitter will exit
the menu and return to the PV display.
Screen
Numeric data entry Text entry
Symbol
Display the high limit for this parameter.
▲ This symbol only appears in the left-most Not Available
position of the data entry field.
Display the low limit for this parameter.
▼ This symbol only appears in the left-most Not Available
position of the data entry field.
Critical
Diagnostics For details go to the Diagnostics Menu table
Non-Critical
LCD Contrast
For details go to the Display Setup Menu
Common Setup
table.
Screen 1
Display Setup
Screen 2
Note that the Advanced Display supports the
…
configuration of up to 8 different screens.
Screen 8
Cal Points
Set Time Stamp
S1 CVD Cal Pts
S2 CVD Cal Pts
S1 Cal Hi/Lo (HART only)
S2 Cal Hi/Lo (HART only)
Calibration For details go to the Calibration Menu table.
Reset Cal 1&2 Corr
(HART only)
LRV/URV Reset Correct
(DE only)
DAC Trim (HART/DE)
Loop Test (HART/DE)
Device Setup
HART Setup
HART Date
Sensor Setup
Sensor 1 CVD (HART/FF)
Sensor 2 CVD (HART/FF)
Digital Output (HART only)
Range values (FF only) For details go to the Transmitter Setup Menu
Transmtr Setup
LRV (HART/DE) table.
URV (HART/DE)
MRV (HART only)
Set LRV (HART/DE)
Set URV (HART/DE)
Dev Install Date (HART/FF)
S1 Install Date (HART/FF)
S2 Install Date (HART/FF)
Display
Information Comm Module For details go to the Information Menu table.
Sensor Module
<Return>
Active Diags ## Description
OK
Sensor Module FAULT FAULT: There is a problem with the
Sensor Module
OK
FAULT FAULT: There is a problem with the
Comm Module
Electronics Module (HART, DE, or
Fieldbus)
Critical OK
FAULT FAULT: There is a problem with the
Sensor Comm
interface between the Sensor Module
and the Electronics Module.
OK
Input 1 FAULT FAULT: There is a problem with the
Input 1 sensor
OK
Input 2 (Dual Inputs
FAULT FAULT: There is a problem with the
only)
Input 2 sensor
<Return>
Shows the number of Non-Critical
Active Diags ##
Diagnostics that are currently active
OK
Cal 1 Correct EXCESSIVE EXCESSIVE: Input applied exceeds
5% of expected value
Cal 2 Correct (Dual OK
Inputs only) EXCESSIVE EXCESSIVE: Input applied exceeds
(HART/FF only) 5% of expected value
OK
Sensor Temp OUT OF RANGE Electronics temperature is greater
than 85 °C
OK OUT OF RANGE: Input 1
Input 1 Range OUT OF RANGE temperature is greater than Sensor 1
URL or less than Sensor 1 LRL
Non-Critical OK
Input 2 Range (Dual OUT OF RANGE OUT OF RANGE: Input 2
Inputs only) temperature is greater than Sensor 2
URL or less than Sensor 2 LRL
OK OUT OF RANGE: Cold Junction
CJ Range OUT OF RANGE temperature is greater than 85C or
less than -40C.
OK
Input 1
OPEN OPEN: Input 1 is open.
Input 2 OK
(Dual Inputs only) OPEN OPEN: Input 2 is open.
OK
Input 1 TB5 OPEN: Input 1 Terminal TB5 is open.
OPEN
Press ↵ to enter
This selection allows the loop to be returned to menu selection
Set DAC
its Normal mode (Automatic Control) after Scroll to Set DAC
Normal
performing the Trim operation. Normal
Press ↵ to initiate
<Return>
Press ↵ to enter
menu selection
Loop Test Scroll to Set DAC
This selection allows the user to force the DAC
Output
Set DAC output to any value between 3.8 and 20.8 mA.
Note: Loop Press ↵ to initiate
Output Note: This selection will put the DAC into Fixed
must be
Output Mode. ↑ and ↓ to select
removed from number.
Automatic ↵ to enter and
Control shift to next digit
(HART/DE Press ↵ to enter
only) This selection allows the loop to be returned to menu selection
Set DAC
its Normal mode (Automatic Control) after Scroll to Set DAC
Normal
performing the Set DAC Output operation Normal
Press ↵ to initiate
Note 2: The Setpoint for the Rate of Change Alarm is configured in terms of PV change per minute. The STT850
monitors the PV change as a rolling window two seconds long and pro-rates this value in terms of PV change per
minute. If the rate of change measured during any two second window exceeds the configured Setpoint value
then the alarm will turn on. If Alarm Latching is disabled, then once the rate of change value falls below the
configured Setpoint and Hysteresis values, the alarm will turn off. If latching is enabled, then the alarm will not
turn off until the unit is reset or the alarm is cleared via the Alarm Latching Clear function.
The Basic Display Menu is implemented as one long single-level menu and will “wrap around” when
it reaches the start or end of the menu. Operation is as follows:
1. Connect a current meter or voltmeter as shown in Figure 20 to monitor the PV output of the
transmitter.
2. Using an accurate input source, apply a signal equivalent to the transmitter LRV.
3. Press the Down (↓ ) and Zero ( ↑ ) buttons together to set the Zero.
4. Verify that the output is now 4 mA.
1. Connect a current meter or voltmeter as shown in Figure 20 to monitor the PV output of the
Transmitter.
2. Using an accurate input source, apply a signal equivalent to the desired Upper Range Value
of the transmitter.
3. Press the Down (↓) and Span ( ) buttons together to set the span.
4. Verify that the PV output is now 20 mA.
You can also use the MCT 202 Toolkit to make any adjustments to an STT850
SmartLine Temperature Transmitter. Alternately, certain adjustments are possible through
an Experion Station or Universal Station, if the STT850 is digitally integrated with either of
these stations.
• Analog operation – Upscale failsafe drives the transmitter output to 21.8 mA. Downscale
failsafe drives the transmitter output to 3.6 mA.
• DE operation – Upscale failsafe causes the transmitter to generate a + infinity digital signal.
Downscale failsafe causes the transmitter to generate a – infinity digital signal.
The transmitter electronics module interprets either signal as not-a-number and initiates its own
configured failsafe action for the control system.
The failsafe direction display accessible via the Toolkit shows only the state of the
jumper as it correlates to analog transmitter operation. Failsafe action for the DE control
system may be configured to operate in a manner different from analog, as indicated by the
state of the transmitter jumper.
The integrated circuits in the transmitter PWA are vunerable to damage by stray
static discharges when removed from the Electronics Housing. Minimize the possibility of
static discharge damage when handling the PWA as follows:
Do not touch terminals, connectors, component leads, or circuits when handling the PWA.
When removing or installing the PWA, handle it by its edges or bracket section only. If you
need to touch the PWA circuits, be sure you are grounded by staying in contact with a
grounded surface or by wearing a grounded wrist strap.
When the PWA is removed from the transmitter, put it in an electrically conductive bag, or
wrap it in aluminum foil to protect it.
The following procedure outlines the steps for positioning the write protect and failsafe jumpers on
the electronics module. See Figure 22 for the locations of the failsafe and write protect jumpers.
Note: The Fieldbus variant has simulation and write protect jumpers in the same location and their
positions are described in Table 15 – Fieldbus Simulation and Write Protect Jumpers. See Section
4.4.3, Write Protect Jumper on Foundation Fieldbus (FF)
Failsafe = UP (High)
Write Protect = OFF (Not Protected)
Failsafe = UP (High)
Write Protect = ON (Protected)
1. Turn OFF transmitter power (Power removal is only required in accordance with area
safety approvals. Power removal is only required in Class 1 Div 1 Explosionproof
and Class 1 Div 2 environments).
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the
transmitter housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
NOTE: Installing a Display Module into a powered transmitter may cause a temporary upset
to the loop output value.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
7. Restore transmitter power if removed.
Set the Write Protect jumper (Bottom jumper) to the desired behavior (Protected or
4 Unprotected). See Table 15 for jumper positioning.
• The PV value is user-configurable. This field has 7 characters. The maximum allowable
numeric value is 9999999 or -999999. If fractional decimals are configured, the fractional
positions will be dropped, as required. If the PV value exceeds the above limits, it is divided
by 1000 and “K” is appended to the result, allowing a maximum value with multiplier of
999999K or -99999K.
• Process Variable Tag is user-configurable from a HART Host. This field has 14 characters.
• Engineering Units. This field is user-configurable when measuring temperature.
(Custom Units option is available for Fieldbus only)
• Bar Graph. User Configurable 126 segment Bar Graph with range settings. The Bar Graph
displays the current value of the configured PV.
• PV Trend. User-configurable display period from one hour to 999 hours (allowing 31 days).
The chart displays minimum, maximum, and average of the configured PV over the selected
trend period.
Bar Graph The limits of the bar graph are user-configurable for each screen.
Trend graph The limits of the trend graph are user-configurable for each screen.
The amount of time visible on the Trend graph is also configurable.
When the operator screens are active on the Advanced Display, the Increment and Decrement buttons
( and ) can be used to move to the next or previous operator screen without waiting for the rotation
time to expire. Pressing the Enter button ( ↵ ) will call up the Main Menu.
The transmitter does not have to be removed from service to replace the Comm
Module
Please take appropriate steps to avoid ESD damage when handling the
Communication and Display Module assemblies
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the
transmitter housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
4. If necessary, unplug the Display interface connector from the Communication
module. Do not discard the connector.
5. Loosen the two retaining screws, and carefully pull the Communication module from
the Electronics compartment.
6. Carefully, insert the Communication module into the Electronics compartment.
7. Tighten the two Communication module retaining screws.
8. Refer to the SmartLine User's Manual to change the FAILSAFE (HART and DE
only), READ/WRITE, and SIM-OFF/SIM-ON configuration settings.
9. If applicable, re-install the Display module as follows:
a) Orient the display as desired.
b) Install the Interface Connector in the Display module such that it will mate with the
socket for the display in the Communication module.
c) Carefully line up the display, and snap it into place. Verify that the two tabs on the
sides of the display latch.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
10. Apply Parker Super O-ring Lubricant or equivalent to the end cap O-ring before
installing the end cap. Reinstall the End Cap and tighten the End Cap locking screw.
11. Installing Optional External Configuration Button Assembly.
a) Loosen (Do Not Remove) both top nameplate screws and pivot nameplate 90°.
b) Align the protrusion on the button assembly with the matching opening in the
housing and snap the button assembly into the housing.
c) Rotate the nameplate back to the original position, and tighten the nameplate screws.
12. Loosen the End Cap locking screw and unscrew the End Cap from the Field Wiring
side of the transmitter housing.
13. Select the proper Communication/External Configuration upgrade kit label from the
label strip provided and adhere to the inside of the Field Wiring compartment End
Cap.
14. Apply Parker Super O-ring Lubricant or equivalent to the end cap o-ring before
installing the end cap. Reinstall the End Cap and tighten the end cap locking screw
15. Install external upgrade label (i.e. DEVICE MODIFIED…..) provided on outside of
housing as shown in Figure 25.
16. Restore power if removed.
17. Check the settings of the Transmitter Setup and Display Setup parameters to make
sure that the transmitter is configured correctly for your application. Refer to the
STT850 HART/DE manual (34-TT-25-06) for details on HART and DE transmitters.
Refer to STT850 Fieldbus manual (34-TT-25-07) for additional information about
Fieldbus transmitters.
18. If applicable, verify External Button Configuration operation.
Installation is complete.
One calibration option is to use the Honeywell MC Toolkit (MCT). Refer to the MC Toolkit User
Manual, Document # 34-ST-25-50.
Calibration information and procedures for a transmitter operating in the HART/DE mode are
provided in the STT850 Series HART/DE Option User’s Manual, document number 34-TT-25-06,
Section on “Calibration.” For Foundation Fieldbus calibration information refer to Foundation
Fieldbus STT850 Temperature Transmitter User’s Guide, 34-TT-25-07
Temperature Sensor fault Comm Module fault Temperature Sensor Comm fault
The Basic Display will display the message CRITICAL FAULT on the top line of the LCD and the
appropriate diagnostic text on the lower line.
• Individually saleable parts are indicated in each figure by key number callout.
• Parts that are supplied in kits are indicated in each illustration by key number callout with the
letter K prefix.
Table 18 is a summarized list of recommended spare parts.
SIL 2/3 Certification IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to
EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the following standards:
IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3: 2010.
MID Approval Issued by NMi Certin B.V. in accordance with WELMEC guide 8.8, OIML R117.1
Edition 2007 (E), and EN 12405-1+A2 Edition 2006. Applicable to Pt100 sensor only.
• For complete model number, see the Model Selection Guide for the particular model of
Temperature Transmitter.
• The serial number of the transmitter is located on the Housing data-plate. The first two
digits of the serial number identify the year (02) and the second two digits identify the week
of the year (23); for example, 0223xxxxxxxx indicates that the product was manufactured in
2002, in the 23 rd week.
Explosion-Proof/ Flameproof:
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
Non-Incendive Equipment:
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAYBE PRESENT
Painted surface of the STT850 may store electrostatic charge and become a source of
ignition in applications with a low relative humidity less than approximately30% relative
humidity where the painted surface is relatively free of surface contamination such as dirt,
dust or oil. Cleaning of the painted surface should only be done with a damp cloth.
The installer shall provide transient over-voltage protection external to the equipment such
that the voltage at the supply terminal of the equipment does not exceed 140% of the
voltage rating of the equipment.
The enclosure is manufactured from low copper aluminium alloy. In rare cases, ignition
sources due to impact and friction sparks could occur. This shall be considered during
Installation, particularly if equipment is installed a Zone 0 location.
A I
About This Manual..................................... iii Installation and Startup ..............................7
Accuracy .....................................................5 Display Installation Precautions ................................ 7
Advanced Display Menus .......................... 28 Mounting STT850 Temperature Transmitters ........... 7
Site evaluation ........................................................... 7
Calibration Menus .................................................... 32
Diagnostics Menu ..................................................... 29 Installation Site Evaluation
Display Setup Menus ................................................ 31 Site Evaluation ........................................................... 7
Information Menus .................................................. 41 Introduction ...............................................1
Transmitter Setup Menus ........................................35
Application Design ......................................5 M
B Maintenance ............................................ 55
Preventive Maintenance Practices and Schedules .. 55
Basic Display Menus ................................. 42 Replacing the Communication Module ................... 55
Bracket Mounting ..................................... 11 Monitoring the Basic and Advanced Displays
............................................................. 51
Advanced Displays ................................................... 51
C Basic Display ............................................................ 51
Changing the Default Failsafe Direction ..... 48 Mounting Dimensions ............................... 11
DE and Analog Differences .......................................48 Mounting STT850 Temperature Transmitters
Failsafe Operation .................................................... 48 ...............................................................8
Copyrights, Notices and Trademarks............ ii Bracket Mounting Procedure .................................. 11
Mounting Dimentsions .............................................. 8
D Summary ................................................................... 8
G P
Parts List................................................... 61
Glossary ................................................... 82
Patent Notice............................................. iv
H
R
Honeywell MC Toolkit .................................7
References................................................. iv
Release Information................................... iii
T
Telephone and Email Contacts ................... iv
Temperature, Analog, HART and DE
Communication..................................... 65
Three Button Operation with no Display
Installed................................................ 47
Span Adjustments .................................................... 47
Zero Adjustments ..................................................... 47
Three-Button Operation ............................ 25
Advanced Display Entries ......................................... 28
Basic Display menu .................................................. 42
Data Entry ................................................................ 26
Menu Navigation ..................................................... 26
Transmitter Adjustments ............................3
Troubleshooting ....................................... 59
Critical Diagnostics Screens ...................................... 59
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
Process Solutions
Honeywell
2101 City West Blvd
Houston, TX 77042