Smv800 Smartline Multivariable Transmitter User'S Manual: Honeywell Process Solutions
Smv800 Smartline Multivariable Transmitter User'S Manual: Honeywell Process Solutions
Smv800 Smartline Multivariable Transmitter User'S Manual: Honeywell Process Solutions
While the information in this document is presented in good faith and believed to be accurate,
Honeywell disclaims any implied warranties of merchantability and fitness for a particular
purpose and makes no express warranties except as may be stated in the written agreement
with and for its customers. In event is Honeywell liable to anyone for any indirect, special, or
consequential damages. The information and specifications in this document are subject to
change without notice.
Honeywell, TDC 3000, SFC, SmartLine, PlantScape, Experion PKS, and TotalPlant are
registered trademarks of Honeywell International Inc. Other brand or product names are
trademarks of their respective owners.
ii
About This Manual
This manual is a detailed how to reference for installing, piping, wiring, configuring, starting up,
operating, maintaining, calibrating, and servicing Honeywell’s family of SMV800 SmartLine
MultiVariable Transmitters. Users who have a Honeywell SMV800 SmartLine MultiVariable
Transmitters configured for HART protocol or Honeywell’s Digitally Enhanced (DE) are referred to
the SMV800 SmartLine Multivariable Transmitter HART/DE Option User’s manual, document
number 34-SM-25-06.
The configuration of your Transmitter depends on the mode of operation and the options selected for
it with respect to operating controls, displays and mechanical installation. This manual provides
detailed procedures to assist first-time users, and it further includes keystroke summaries, where
appropriate, as quick reference or refreshers for experienced personnel.
For the Experion PKS, you will need to supplement the information in this document with the
data and procedures in the Experion Knowledge Builder.
For Honeywell’s TotalPlant Solutions (TPS), you will need to supplement the information in this
document with the data in the PM/APM SmartLine Transmitter Integration Manual, which is
supplied with the TDC 3000 book set. (TPS is the evolution of the TDC 3000).
Release Information:
SMV800 SmartLine Multivariable Transmitter User Manual, Document # 34-SM-25-03.
Rev. 1, October 2015 – First Release (RQUP)
Rev. 2, December 2015 – Prod Release
Rev. 3, September 2016 – Agency Approval updates
Rev. 4, March 2017 – SAEx / INMETRO / NEPSI / KOSHA / SIL Approval updates
Rev.5, December 2017 – Totalizer functionality added (R120)
SMV800 SmartLine Multivariable Transmitter Quick Start Installation Guide, Document # 34-SM-25-04
SMV800 SmartLine Multivariable Transmitter with HART Communications Options Safety Manual, #
34-SM-25-05
SMV800 SmartLine Multivariable Transmitter HART/DE Option User’s Manual, Document
# 34-SM-25-06
SmartLine Configuration Toolkit (SCT) Installation and startup Guide, 34-ST-10-08
MC Tookit User Manual (MCT404), Document # 34-ST-25-50. MC Tookit User Manual (MCT202),
Document # 34-ST-25-20
PM/APM SmartLine Transmitter Integration Manual, Document # PM 12-410
ST 800 Series Pressure, Analog, HART and DE Communications form, Honeywell drawing 50049892
Smart Field Communicator Model STS 103 Operating Guide, Document # 34-ST-11-14
Patent Notice
The Honeywell SMV800 SmartLine Multivariable Transmitter family is covered by one or more of the
following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other
patents pending.
For Europe, Asia Pacific, North and South America contact details, refer to the back page of this manual
or the appropriate Honeywell Solution Support web site:
Symbol Definition
TIP: Identifies advice or hints for the user, often in terms of performing a
task.
CAUTION Indicates a situation which, if not avoided, may result in equipment or work
(data) on the system being damaged or lost, or may result in the inability to
properly operate the process.
continued
The Ex mark means the equipment complies with the requirements of the
European standards that are harmonized with the 94/9/EC Directive (ATEX
Directive, named after the French "ATmosphere EXplosible").
Approvals (See Appendix for details.) FM, ATEX, CSA, IECEx, NEPSI
Mounting Brackets Angle/flat carbon steel/304 stainless steel, Marine 304
stainless steel, 316 Stainless Steel
1. Differential Pressure
2. Static Pressure
3. Process Temperature
4. Calculated Flow Rate
5. Totalizer (HART only)
6. Meter Body Temperature.
Honeywell SMV800 supports Dynamic Compensation Mode for Industrial Flow Standards according
to ASME-MFC-3-2004, ISO5167-2003, Gost8.586-2005, AGA3-2003 and flow calculations for
Averaging Pitot Tube, Integral Orifice, VCone, and Wedge and Fixed Parameters.
Honeywell SMV800 also supports Standard Compensation Mode for Only Density Compensation.
An optional 3-button assembly is available to set up and configure the transmitter via the Display. In
addition, a Honeywell MCT404/MCT202 Toolkit is available for configuration of HART models.
The SCT SmartLine Configuration Tool (not supplied with the Transmitter) can facilitate setup and
configuration for DE devices.
Certain adjustments can be made through an Experion Station or a Universal Station if the Transmitter
is digitally integrated with Honeywell’s Experion or TPS/TDC 3000 control system for HART and
DE transmitters.
For a complete selection breakdown, refer to the appropriate Specification and Model Selection Guide
provided as a separate document.
You can also use the Honeywell MCT404/MCT202 Configuration Tool – FDC application to make
any adjustments to an SMV800 Transmitter with HART.
For DE models the SCT3000 PC tool application can be used to configure the device. STS103 can be
used to Zero and Span adjustments.
Certain adjustments can also be made through the Experion or Universal Station if the Transmitter is
digitally integrated with a Honeywell Experion or TPS system.
Safety
Input and output data
Reliability
Environmental limits
Installation considerations
Operation and maintenance
Repair and replacement
2.2. Safety
2.2.1. Accuracy
The SMV800 SmartLine MultiVariable transmitter measures Differential Pressure, Static Pressure
(Absolute or Gauge), and Process Temperature. These measurements are used to calculate volumetric
or mass flow rates. The measured values and calculated flow may be read by a connected Host.
Refer to Table 8 for the more detail on status of Critical Diagnostics Menu
Refer to Table 8 for the more detail on status of Non-Critical Diagnostics Menu
The SMV800 provides several features designed to prevent accidental changes to the device
configuration or calibration data. These features include a local display password (HART
option), a communication password (HART option), a Hardware Write Protect Jumper and a
Software Write Protect configuration parameter. These features can be used in combination to
provide multiple layers of change protection.
For both the local display and communication passwords, the initial user passwords are defined
as "0000". A "0000" password indicates that the user has not set a user- defined password and
the password protection is disabled. The password used on the local keyboard display is
separate from the password provided for communication. Password protection from the local
keyboard display does not inhibit changes by way of communication over the current loop.
Reset / Forgot password option is supported where user can send the serial number of the
device to Honeywell Technical Assistance Center and get the password code. Then user can
enter this code to reset the password.
A hardware write-protect locks out changes regardless of the entry of a password. The
hardware jumper requires physical access to the device as well as partial disassembly and
should not be modified where the electronics are exposed to harsh conditions or where unsafe
conditions exist. For configuration or calibration changes without changing the hardware
jumper position the user may choose to rely on the password and software lockout features.
Environmental Conditions:
o Ambient Temperature
o Relative Humidity
Potential Noise Sources:
o Radio Frequency Interference (RFI)
o Electromagnetic Interference (EMI)
Vibration Sources
o Pumps
o Motorized System Devices (e.g., pumps)
o Valve Cavitation
Process Parameters
o Temperature
o Maximum Pressure Rating
The display update rate may increase at cold temperature extremes, but as with readability, normal
updating resumes when temperatures are within limits for full operability.
1. Refer to Figure 5. Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe, and
install a “U” bolt around the pipe and through the holes in the bracket. Secure the bracket with
the nuts and lock washers provided.
Nuts and
Nuts and Lockwashers
Lockwashers
Mounting
Bracket
U-Bolt
Mounting
Bracket
Horizontal Pipe
Vertical Pipe
U-Bolt
2. Align the appropriate mounting holes in the Transmitter with the holes in the bracket. Use the
bolts and washers provided to secure the Transmitter to the bracket.
3. Loosen the set screw on the outside neck of the Transmitter one (1) full turn.
4. Rotate the Electronics housing a maximum of 180o left or right from the center to the position
you require, and tighten the set screw 13 to 15 lb-in (1.46 to 1.68 Newton meters), using a
4mm metric hex key wrench. See the following example and Figure 6.
EXAMPLE: Rotating the Electronics Housing
The most common type of impulse pipe used is 1/2 inch schedule 40 steel pipe. Many piping
arrangements use a 3-valve or 5-valve manifold to connect the process piping to the transmitter. A
manifold makes it easy to install and remove a transmitter without interrupting the process. It also
accommodates the installation of blow-down valves to clear debris from pressure lines to the
transmitter.
Figure 7 shows a diagram of a typical piping arrangement using a 3-valve manifold and blow-down
lines for a flow measurement application.
Figure 9 shows the transmitter located below the tap for liquid or steam flow measurement. This arrangement
minimizes the static head effect of the condensate. Although the transmitter can be located level with or above
the tap, this arrangement requires a siphon to protect the transmitter from process steam. (The siphon retains
water as a “fill fluid.”)
ATTENTION For liquid or steam, the piping should slope a minimum of 25.4 mm (1 inch) per
305 mm (1 foot). Slope the piping down towards the transmitter if the
transmitter is below the process connection so the bubbles may rise back into
the piping through the liquid. If the transmitter is located above the process
connection, the piping should rise vertically above the transmitter; then slope
down towards the flow line with a vent valve at the high point. For gas
measurement, use a condensate leg and drain at the low point (freeze protection
may be required here).
This procedure does not require that the Meter Body be removed from the Electronics
Housing. If flange adapters are being replaced with parts from other kits (for example, process
heads), follow the procedures for the kits and incorporate the following procedure.
NOTE: The threaded hole in each Flange Adapter is offset from center. To ensure proper
orientation for re-assembly, note the orientation of the offset relative to each Process Head
before removing any adapter.
Refer to the instructions included with the kit for removal and replacement procedures.
Loop wiring is connected to the Transmitter by simply attaching the positive (+) and negative (–) loop
wires to the positive (+) and negative (–) terminals on the Transmitter terminal block in the Electronics
Housing shown in Figure 12. Connect the Loop Power wiring shield to earth ground only at the power
supply end.
As shown in Figure 12, each Transmitter has an internal terminal to connect it to earth ground. Optionally,
a ground terminal can be added to the outside of the Electronics Housing.
Screw terminals 1 to 8 only required for single input, terminals 4 and 9 are not used. Grounding the
Transmitter for proper operation is required, as doing so tends to minimize the possible effects of noise on
the output signal and affords protection against lightning and static discharge. An optional lightning
terminal block can be installed in place of the non-lightning terminal block for Transmitters that will be
installed in areas that are highly susceptible to lightning strikes. As noted above, the Loop Power wiring
shield should only be connected to earth ground at the power supply end.
Wiring must comply with local codes, regulations and ordinances. Grounding may be
required to meet various approval body certification, for example CE conformity. Refer to
Appendix A of this document for details.
For HART and DE the Transmitter is designed to operate in a 2-wire power/current loop with loop
resistance and power supply voltage within the operating range; see Figure 11.
With optional lightning protection and/or a remote meter and/or any peripheral device, the voltage drop
for these options must be added to the basic 10.8-volt (for HART) & 15-volt (for DE) supply requirements
to determine the required Transmitter voltage (VXMTR) and maximum loop resistance (RLOOP MAX).
Additional consideration is required when selecting intrinsic safety barriers to ensure that they will supply
at least minimum Transmitter voltage (VXMTR MIN), including the required 250 ohms of resistance
(typically within the barriers) needed for digital communications.
o To minimize common noise problems in the application, a strap/jumper should be wired between
terminals 6 and 8. Applicable for Universal input modes only.
In this calculation:
VXMTR MIN (HART) = 10.8 V + VSM
VXMTR MIN (DE) = 15 V + VSM
Note that VSM should only be considered if a remote meter will be connected to the transmitter.
The positive and negative loop wires are connected to the positive (+) and negative (–) terminals on the
terminal block in the Transmitter Electronics Housing.
Barriers can be installed per Honeywell’s instructions for Transmitters to be used in intrinsically safe
applications.
If you are digitally integrating a Transmitter in an Allen Bradley Programmable Logic Controller (PLC)
process system, the same Field Terminal Assembly (FTA) and wiring procedures used with Honeywell’s
TPS system are also used with the Allen-Bradley 1771 and 1746 platforms.
3.7. Startup
3.7.1. Overview
This section identifies typical start up tasks associated with several generic pressure measurement
applications. It also includes the procedure for running an optional analog output check.
You can also run an optional output check to wring out an analog loop and check out individual Process
Variable (PV) outputs in Digitally Enhanced (DE) mode before startup.
The actual steps in a startup procedure vary based on the type of Transmitter and the measurement
application. In general, the procedures in this section are based on using Honeywell SmartLine
Configuration Toolkit for a DE transmitter or MCT404/MCT202 for a HART version, to check the
Transmitter input and output under static process conditions, and make adjustments as required initiating
full operation with the running process.
Note: checks can be made using the optional three-button assembly, if your Transmitter is so equipped.
Operation with the three-button assembly is discussed in the “Operation” section of this manual.
The SMV800 device power-up sequence (with the loop current mode Disabled) as measured across the
250 ohm loop resistor and/or the TEST terminals:
The device skips all initializations and goes directly to the fixed 1 volt (loop current of 4 ma).
The Loop Test procedure checks for continuity and the condition of components in the output
current loop.
The Trim DAC Current procedure calibrates the output of the Digital-to-Analog converter for
minimum (0%) and maximum (100%) values of 4 mA and 20 mA, respectively. This procedure is
used for Transmitters operating online in analog mode to ensure proper operation with associated
circuit components (for example, wiring, power supply,…, control equipment). Precision test
equipment (an ammeter or a voltmeter in parallel with precision resistor) is required for the Trim
DAC Current procedure.
The Apply Values procedure uses actual Process Variable (PV) input levels for calibrating the
range of a Transmitter. To measure a liquid level for example, a sight-glass can be used to
determine the minimum (0%) and maximum (100%) level in a vessel. The PV is carefully
adjusted to stable minimum and maximum levels, and the Lower Range Limit Value (LRV) and
Upper Range Limit Value (URV) are then set by commands from the Host applications (For
HART use MCT404 and for DE use SCT tool).
The Transmitter does not measure the given PV input or update the PV output while it
operates in the Output mode.
1. Refer to Figure 15 for test connections. Verify the integrity of electrical components in the output
current loop.
2. Establish communication with the Transmitter. For these procedures, the values of components in the
current loop are not critical if they support reliable communication between the Transmitter and the
Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be displayed.
5. Select the desired constant-level Output: 0 %, 100 %, or Other (any between 0 % - 100 %).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the Transmitter in Analog mode, you can observe the output on an externally-
connected meter or on a local meter. In DE mode, you can observe the output on the local
meter or on the SCT Monitor display.
7. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
8. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
9. Select Yes to continue. This concludes the Startup procedure.
When on a lower level menu, return to the menu above by selecting <Return>. Alternately, the (up) and
(down) buttons can be pressed simultaneously to return to the menu above. When on the highest level
menu, pressing the (up) and (down) buttons simultaneously will exit the menu and return to the PV
display.
Use the and buttons to scroll through the list of menu items. Press the button to select an item for
data entry or activation. When an item is selected for data entry or activation, the cursor will call up a pop-
up window to allow editing of the value. No action is taken against a menu item until the button is
pressed.
If a user presses the button to begin a data entry operation, they must press another button within 10
seconds or the transmitter firmware will assume that the user wants to abort the operation or has walked
away from the transmitter. After 10 seconds with no action, the data entry will time out and the original
value of the parameter will be preserved.
If no button presses occur within 60 seconds, menu access will time out and the transmitter will exit the
menu and return to the PV display.
All numeric entries are clamped at the low or high limit if needed. You can determine the low and high
limit for a parameter by selecting either the ▲ or ▼ character while the cursor is positioned over the left-
most digit and press button. The Display will show the selected limit.
Screen
Numeric data entry Text entry
Symbol
Display the high limit for this parameter.
▲ This symbol only appears in the left-most Not Available
position of the data entry field.
Display the low limit for this parameter.
▼ This symbol only appears in the left-most Not Available
position of the data entry field.
((PV value – input low limit) / input span) x (Scaling High – Scaling Low) + Scaling Low
If the PV Selection is Pressure, the input low and high limits are the LRV and URV respectively. If the
PV Selection is Percent Output, the input low and high limits are 0 and 100%. If the PV Selection is
Square Root, the input low and high limits are 0 and 100 %Flow.
For example:
PV Selection: Differential Pressure
PV Scaling: Square Root
Scaling Low: 0.0
Scaling High: 2500.0
Display Units: gal/h
LRV: 0.0
URV: set as required by the process
The Display will calculate 0-100 %Flow from the Differential Pressure and then scale this to 0
to 2500 gal/h.
Note that the Square Root calculation is referenced to the LRV and URV settings of the transmitter and its
uses the LRV and URV to calculate the %DP input into the Square Root flow algorithm. For normal flow
applications, it is assumed that the LRV is set to zero and that zero pressure equals zero flow. If the LRV
is less than zero, the Square Root calculation will calculate the flow as bi-directional flow.
##. #
T Damping sec Selection applies digital filtering to
suppress noise effects on the PV.
The limits for this value are 0.0 to
32.0 seconds
When enabled, adds a constant Press to
bias value to the Sensor 2 enter menu
Enable,
Break Detect measured value to equate it to selection
Disable
the Sensor 1 measured value at and to
the moment selected. select
Temperature
When enabled, causes all critical Alphanumeric
Sensor
sensor input failures to latch to to enter
the Critical Fault state. The fault and shift to
Enabled,
Latching may only be cleared by device next
Disabled
reset. When disabled, the critical character to
sensor input failure will be cleared the right.
if the input recovers.
Internal, Determines the source of the
CJ Source External, Cold Junction compensation for
Fixed Thermocouple Sensor types.
When CJ Type is Fixed, specifies
the Cold Junction temperature
value for thermocouple Sensor
Fixed CJ Value ####.## types. Degrees Celsius. Fixed CJ
temperatures below -50 degrees
have no effect on measured
values.
mV, TC, Select Sensor Type1
Sensor Type
RTD, Ohm Press ↵ to
Sensor ID for Select Sensor ID for Input n for enter menu
Sensor ID*
Input 1 selected Sensor Type. selection
Temperature
2-Wire, 3- Select the RTD Type according to
Sensor RTD Type*
Wire, 4-Wire the number of lead wires ↑ and ↓ to
Resistance valve of the sensor select entry.
RTD Lead Res* ####.##
lead wire ↵ to enter
Sensor Bias* ####.## Bias on the measured value
The limit for the Lower Range Value is the Lower
Temp LRV
###. ## Range Limit (LRL) of the selected Sensor ID.
The limit for the Upper Range Value is the Upper
Temp URV ###. ## Press to
Range Limit (URL) of the selected Sensor ID.
enter menu
ATTENTION: Executing this service will set the
selection
Set Temp LRV Set Temp LRV Lower Range Value (LRV) equal to the Input 1
to execute
measurement
ATTENTION: Executing this service will set the
Set Temp URV Set Temp URV Upper Range Value (URV) equal to the Input 1
measurement
Write Date CAUTION: The Install Date can only be written once in the life of
the transmitter. You cannot erase or overwrite the Install Date
once it has been written.
Enter the current year.
Year
#### This item will only be visible if no Install Date has
been written to the transmitter.
Select the current month.
Month January thru
Sens Instl This item will only be visible if no Install Date has
December
Date* been written to the transmitter.
Enter the day of the month.
Day
## This item will only be visible if no Install Date has
been written to the transmitter.
Write Date Press ENTER to write the Install Date to the transmitter.
* Applicable to HART only, not DE
1. Connect a current meter or voltmeter as shown in Figure 15 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the Transmitter LRV.
3. Press the Down (↓ ) and Zero ( ) buttons together to set the Zero.
4. Verify that the output is now 4 mA.
1. Connect a current meter or voltmeter as shown in Figure 15 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the desired Upper Range Value of
the transmitter.
3. Press the Down (↓) and Span ( ) buttons together to set the span.
4. Verify that the PV output is now 20 mA.
You can also use the SCT3000 toolkit to make any adjustments to an SMV800 SmartLine
Multivariable Transmitter for DE models and the MCT404/MCT202 for HART. Alternately,
certain adjustments are possible through an Experion Station or Universal Station, if the
SMV800 is digitally integrated with either of these stations.
Analog operation – Upscale failsafe drives the Transmitter output to 21.8 mA. Downscale
failsafe drives the Transmitter output to 3.8 mA.
DE operation – Upscale failsafe causes the Transmitter to generate a + infinity digital signal
(HEX +FFFF). Downscale failsafe causes the Transmitter to generate a – infinity digital
signal(HEX +FFFF).
The Transmitter electronics module interprets either signal as not-a-number and initiates its own
configured failsafe action for the control system.
The failsafe direction display accessible via the Toolkit shows only the state of the jumper
as it correlates to analog Transmitter operation. Failsafe action for the DE control system may
be configured to operate in a manner different from analog, as indicated by the state of the
Transmitter jumper.
The integrated circuits in the Transmitter PWA are vulnerable to damage by stray static
discharges when removed from the Electronics Housing. Minimize the possibility of static
discharge damage when handling the PWA as follows:
Do not touch terminals, connectors, component leads, or circuits when handling the PWA.
When removing or installing the PWA, handle it by its edges or bracket section only. If you need
to touch the PWA circuits, be sure you are grounded by staying in contact with a grounded
surface or by wearing a grounded wrist strap.
When the PWA is removed from the Transmitter, put it in an electrically conductive bag, or wrap
it in aluminum foil to protect it.
The following procedure outlines the steps for positioning the write protect and failsafe jumpers on the
electronics module. See Figure 17 for the locations of the failsafe and write protect jumpers.
Failsafe = UP (High)
Write Protect = OFF (Not Protected)
Failsafe = UP (High)
Write Protect = ON (Protected)
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the
Transmitter housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
4. If necessary, unplug the interface connector from the Communication module. Do not
discard the connector.
5. Set the Failsafe Jumper (top jumper) to the desired position (UP or DOWN).
See Table 18 for jumper positioning.
6. If applicable, re-install the Display module as follows:
Orient the display as desired.
Install the Interface Connector in the Display module such that it will mate with
the socket for the display in the Communication module.
Carefully line up the display, and snap it into place. Verify that the two tabs on the
sides of the display latch.
NOTE: Installing a Display Module into a powered transmitter may cause a temporary upset to
the loop output value.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
4.4.1. Displays
As shown in Figure 18, the Display provides three formats.
Table 19 lists and describes the fields in each of the three Display formats. Essentially, all three formats
provide the same information, but with the following differences:
Bar Graph. User Configurable 126 segment Bar Graph with range settings. The Bar Graph
displays the current value of the configured PV.
PV Trend. User-configurable display period from one hour to 24 hours. The chart displays
minimum, maximum, and average of the configured PV over the selected trend period.
Square Root Output This indicator is displayed when the Transfer Function of the transmitter is
set to “Square Root”.
Trend Graph The limits of the trend graph are user-configurable for each screen.
The amount of time visible on the Trend graph is also configurable.
When the operator screens are active on the display, the Increment and Decrement buttons ( and ) can
be used to move to the next or previous operator screen without waiting for the rotation time to expire.
Pressing the Enter button ( ) will call up the Main Menu.
● g/sec ● m3/h
● g/min ● m3/min
● g/h ● m3/sec
● kg/sec ● m3/day
● kg/min ● gal/min
● kg/h ● gal/h
● t/min [Metric tons] ● gal/day
● t/h [Metric tons] ● l/min
● lb/sec ● l/h
● lb/min ● ft3/min
● lb/h ● ft3/sec
● lb/d ● ft3/h
● STon/min ● bbl/day
● STon/h ● gal/s
● STon/d ● L/S
● LTon/h ● Cuft/d
● LTon/d ● NmlCum/h
● Kg/d ● NmlL/h
● MetTon/d ● StdCuft/min
● Custom ● Bbl/s
● Bbl/min
● Bbl/h
● Nml m3/d
● Nml m3/min
● Std ft3/d
● Std Ft3/h
● Std m3/d
● Std m3/h
● Std M3/min
● Custom
Preventive maintenance of the meter body barrier diaphragms and process piping to the
Transmitter.
Replacement of damaged parts such as the Transmitter Printed Wiring Assembly (PWA) and
meter body
In many cases, you can readily remove the process head(s) from the Transmitter meter body to clean the
process head cavity and inspect the barrier diaphragm(s).
The following procedure comprises the general steps for inspecting and cleaning barrier diaphragms.
It is recommended that you remove the Transmitter from service and move it to a clean
area before disassembling it.
The transmitter does not have to be removed from service to replace the Comm Module
Please take appropriate steps to avoid ESD damage when handling the Communication
and Display Module assemblies
1. Turn OFF Transmitter power (Power removal is only required in accordance with area safety
approvals. Power removal is only required in Class 1 Div 1 Explosionproof and Class 1 Div 2
environments).
When removing the Communications Module with power applied, the loop will go to 0V.
Likewise, installing a Communications Module into a transmitter with power applied will
cause the loop output value to go to 12 ma for several seconds then the loop output value
will go to the configured value based on the PV input.
Installing a Display Module into a powered transmitter may cause a temporary upset to
the loop output value.
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the Transmitter
housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the Display
Module, and pull it off.
4. If necessary, unplug the interface connector from the Communication module. Do not discard
the connector.
6. Carefully align and connect the Sensor Ribbon Cable to the connector “J4” at the bottom of the
Communication module. When installing the Communication module in the next step, be careful
not to pinch the Sensor Ribbon Cable.
7. Carefully, insert the Communication module into the Electronics compartment. Ensure that the
Sensor Ribbon Cable is not pinched.
9. Refer to the Section 4.3 to change the FAILSAFE, READ/WRITE, and SIM-ON/SIM-OFF
(Fieldbus only) configuration settings.
c) Carefully line up the display, and snap it into place. Verify that the two tabs on the sides
of the display latch.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
11. Apply Parker Super O-ring Lubricant or equivalent to the end cap O-ring before installing the end
cap. Reinstall the End Cap and tighten the End Cap locking screw.
a) Loosen (Do Not Remove) both top nameplate screws and pivot nameplate 90°.
b) Align the protrusion on the button assembly with the matching opening in the housing and
snap the button assembly into the housing.
c) Rotate the nameplate back to the original position, and tighten the nameplate screws.
13. Loosen the End Cap locking screw and unscrew the End Cap from the Field Wiring side of the
transmitter housing.
14. Select the proper Communication/External Configuration upgrade kit label from the label strip
provided and adhere to the inside of the Field Wiring compartment End Cap.
15. Apply Parker Super O-ring Lubricant or equivalent to the end cap o-ring before installing the end
cap. Reinstall the End Cap and tighten the end cap locking screw.
16. Install external upgrade label (i.e. DEVICE MODIFIED…..) provided on outside of housing as
shown in Figure 21.
18. Check the settings of the Transmitter Setup and Display Setup parameters to make sure that the
transmitter is configured correctly for your application. See the HART and DE User's Manual
(SMV800 #34-SM-25-06) for details on HART and DE transmitters.
Please take appropriate steps to avoid ESD damage when handling the Communication
and Display Module assemblies
9. Carefully turn the complete meter body counterclockwise to unscrew it from the electronics
housing.
10. Remove the nuts from bolts that hold the process head(s) to the Meter Body.
11. Remove process heads and bolts.
12. Remove the gaskets or O-rings from the process heads.
13. Clean the interior of the process head(s) with a soft bristle brush and suitable solvent.
CAUTION
To prevent damage to the diaphragm in the Meter Body, use extreme care when
handling or placing the Meter Body on any surface. Carefully assemble gaskets or O-
rings to the meter body. If installing O-rings, lubricate with water or leave dry.
14. Coat threads on process head bolts with anti-seize compound such as “Neverseize” or equivalent.
15. Refer to Figure 24. Apply Parker Super O-Lube O-Ring lubricant to the meter body adapter O-
ring and carefully assemble the O-ring to the meter body. Assemble the process head(s) and bolts
to the new meter body. For now, make the bolts only finger-tight.
16. Use a torque wrench to gradually tighten nuts to torque rating in sequence shown in Figure 25.
Tighten head bolts in stages of 1/3 full torque, 2/3 full torque, and then full torque.
CAUTION
To prevent damage to the ribbon cable, use care when assembling the Meter Body
to the electronics housing.
18. Screw the new meter body into the housing until the bottom of the Meter Body adapter is flush
with the neck of the electronics housing.
19. Tighten the outside set screw to be sure it is fully seated in the slot in the header.
20. Loosen the set screw ½- turn.
21. Rotate the housing to the desired position (Max. 180o in either direction), and tighten the set
screw.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90o increments.
26. Connect the bracket to the Transmitter housing.
27. Recalibrate the Transmitter per Section 6 Calibration, of this document.
28. Return the Transmitter to service, and turn ON power
29. Verify the Transmitter configuration data. Restore the saved database if necessary.
30. Lubricate the end-cap O-ring with Parker Super O-ring silicone lubricant or equivalent before
replacing the end caps.
The SMV800 SmartLine Multivariable Transmitter does not require periodic calibration to maintain
accuracy. Typically, calibration of a process-connected Transmitter will degrade, rather than augment the
capability of a smart Transmitter. For this reason, it is recommended that a Transmitter be removed from
service before calibration. Moreover, calibration will be accomplished in a controlled, laboratory-type
environment, using certified precision equipment.
One calibration option for DE transmitters is to use the Honeywell SmartLine Configuration Toolkit
(SCT3000). Please use the SMV800 HART/DE manual or SCT3000 manual which has the Calibration
procedure. If 34-ST-10-08 SCT manual does not have calibration procedure then please refer 34-25-06
manual.
Calibration information and procedures for a Transmitter operating in the HART/DE mode are provided in
the SMV800 SmartLine Multivariable Transmitter HART/DE Option Manual document number.34-SM-
25-06, Section on “Calibration”
These screens will be inserted into the normal screen rotation and displayed between the user-defined
operator screens. A description of the diagnostic conditions is given in Table 22, along with
suggested actions for resolving the problem.
Individually saleable parts are indicated in each figure by key number callout.
Parts that are supplied in kits are indicated in each illustration by key number callout with the
letter K prefix.
Table 23Error! Reference source not found. is a summarized list of recommended spare parts.
Table 23 – Summary List of Recommended Spare Parts
Key
Part Number Description Quantity
Number
50062206-006 Coplanar Adapter Glass-Filled PTFE Gasket Kit
K1 Transmitter-side glass-filled PTFE Gaskets 2
K2 Manifold-side glass-filled PTFE Gaskets 2
Standards: ABNT NBR IEC 60079-0:2013 (IEC 60079-0:2011); ABNT NBR IEC 60079-1:2009
(IEC 60079-1:2007); ABNT NBR IEC 60079-11:2013 (IEC 60079-11:2011); ABNT NBR IEC
60079-15:2012 (IEC 60079-15:2010); ABNT NBR IEC 60079-26:2008 (IEC 60079-26:2006);
ABNT NBR IEC 60079-31:2014 (IEC 60079-31:2013).
Intrinsically Safe:
Ex ia IIC T4 Ga
Note 2 T4: -50oC to 70oC
Non Sparking:
Ex nA IIC T4 Gc
Note 1 T4: -50oC to 85oC
NEPSI
G Flameproof:
(CHINA) T5: -50 ºC to 85ºC
Ex d IIC T6..T5 Ga/Gb Note 1
T6: -50 ºC to 65ºC
Ex tb IIIC Db T95oC..T125 oC Db
Enclosure: IP66/ IP67
Flameproof:
T5: -50 ºC to 85ºC
Ex d IIC T6..T5 Note 1
KOSHA T6: -50 ºC to 65ºC
H Ex tD A21 T 95oC..T125 oC
(Korea)
Intrinsically Safe:
Ex ia IIC Ga
Note 2 T4: -50oC to 70oC
Painted surface of the SMV800 may store electrostatic charge and become a source of ignition in
applications with a low relative humidity less than approximately30% relative humidity where the
painted surface is relatively free of surface contamination such as dirt, dust or oil. Cleaning of the
painted surface should only be done with a damp cloth.
Flame-proof Installations: The Transmitter can installed in the boundary wall between an area of
EPL Ga/ Class I Zone 0/ Category 1 and the less hazardous area, EPL Gb/ Class I Zone 1/ Category
2. In this configuration, the process connection is installed in EPL Ga/ Class I Zone 0/ Category 1,
while the transmitter housing is located in EPL Gb/ Class I Zone 1/ Category 2.
Consult the manufacturer for dimensional information on the flameproof joints for repair.
Non-Incendive Equipment:
Division 2: This equipment is suitable for use in a Class I, Division 2, Groups A, B, C, D; T4 or Non-
Hazardous Locations Only
The enclosure is manufactured from low copper aluminum alloy. In rare cases, ignition sources due to
impact and friction sparks could occur. This shall be considered during Installation, particularly if
equipment is installed a Zone 0 location.
If a charge-generating mechanism is present, the exposed metallic part on the enclosure is capable
of storing a level of electrostatic that could become Incendive for IIC gases. Therefore, the user/
installer shall implement precautions to prevent the buildup of electrostatic charge, e.g. earthing the
metallic part. This is particularly important if equipment is installed a Zone 0 location.
A G
About This Manual..................................... iii General Piping Guidelines ......................... 16
Accuracy ..................................................... 7 Glossary .................................................... 89
Application Design ...................................... 7
H
B
Honeywell MC Toolkit ............................... 10
Bracket Mounting ..................................... 12
Button operation during monitoring ......... 53 I
Install Flange Adapters .............................. 16
C
Installation and Startup ............................. 10
Calibration ................................................ 64 Display Installation Precautions .............................. 10
Calibration Procedures .............................. 64 Mounting SMV800 SmartLine Multivariable
Transmitters ....................................................... 10
Changing the Default Failsafe Direction..... 48 Site evaluation ......................................................... 10
DE and Analog Differences ....................................... 48
Failsafe Operation .................................................... 48
Installation Site Evaluation
Site Evaluation ......................................................... 10
COPLANAR ADAPTER ................................ 74
Introduction ................................................ 1
Copyrights, Notices and Trademarks .. ii
L
D
Lightning Protection .................................. 20
Diagnostic Messages ................................... 7
Diagnostics Menu ..................................... 29
M
Digital System Integration Information ..... 20
Display Installation Precautions ................ 10 Maintenance ............................................. 55
Display Menus .......................................... 27 Inspecting and Cleaning Barrier Diaphragms .......... 55
Calibration Menus .................................................... 37 Preventive Maintenance Practices and Schedules .. 55
Diagnostics Menu..................................................... 29 Replacing the Communication Module ................... 58
Information Menus .................................................. 46 Replacing the Meter Body ....................................... 60
Transmitter Setup Menus .......... 38, 39, 41, 42, 44, 45 Monitoring the Displays ............................ 51
Display Menus Monitoring the Displays ............................ 51
Display Setup Menus................................................ 31 Mounting Dimensions ............................... 11
Display Options ........................................... 6 Mounting SMV800 SmartLine Multivariable
Display Setup Menus ................................ 31 Transmitters .......................................... 11
Dual/Triple Cal .......................................... 64 Bracket Mounting Procedure .................................. 12
Mounting Dimentsions ............................................ 11
Summary ................................................................. 11
E
Multivariable, Analog, HART and DE
Editing a Numeric Value ............................ 26 Communication ..................................... 75
Explosion-Proof Conduit Seal .................... 21
N
F
Name Plate ................................................. 4
Fault Conditions ........................................ 66
Features and Options .................................. 1
Functional Characteristics .......................................... 3
Physical Characteristics .............................................. 1
References .................................................. iv
W
S Wiring a Transmitter ................................. 17
Wiring Procedure .................................................... 20
Safety ......................................................... 7 Wiring Variations ..................................................... 18
Accuracy .....................................................................7
Diagnosis Messages ...................................................7
Safety Integrity Level..................................................9
Safety Certification ..................................... 5
Startup ......................................................21
Constant Current Source Mode Procedure ..............23
Output Check Procedures ........................................22
Supply Voltage Limiting Requirements .......20
Support and Contact Information ............... iv
Symbol Descriptions and Definitions ............v
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042
www.honeywellprocess.com