A06-001 - Building Elevator Systems - US
A06-001 - Building Elevator Systems - US
A06-001 - Building Elevator Systems - US
A. Bhatia
P: (877) 322-5800
info@cedengineering.com
www.cedengineering.com
Building Elevator Systems – A06-001
For most people residing in urban cities, elevators have become an integral part of their daily life.
Simply stated, an elevator is a hoisting or lowering mechanism, designed to carry passengers or
freight, and is equipped with a car and platform that typically moves in fixed guides and serves
two or more landings. The elevators can be broadly classified as either electric traction type or
hydraulic type.
• Traction elevators have an elevator car and counterweight attached to opposite ends of
hoist ropes. The hoist ropes pass over a driving machine that raises and lowers the car.
Traction elevators run on load-bearing rails in the elevator hoistway. Traction elevators
are most often used in mid-rise and high-rise buildings with five or more floors.
• Hydraulic elevators, on the other hand, are raised by forcing pressurized oil through a
valve into a steel cylinder located above ground or underground. The pressure forces a
piston to rise, lifting the elevator platform and car enclosure mounted on it. The car is
lowered by opening the valve and allowing the weight of the car to force oil from the
cylinder in a controlled manner. When the valve is closed the car is stopped. Since the
weight of hydraulic elevator cars is borne by the piston, there is no need for a structural
framework or load-bearing rails. Hydraulic elevators are commonly found in low-rise
buildings with two to five floors.
The main design considerations for choosing either electric traction drive or hydraulic for a
particular project are the number of floors, the height of the building, the number of people to be
transported, desired passenger waiting times and frequency of use.
The other mode of vertical building transportation is “Escalator”. It can be described as moving
stairs typically used to carry large number of people at high volumes through a limited no of
floors. These are commonly used in high density areas or where sudden traffic surges are
expected at times; for example at discharge times from offices, railways underground stations,
airport terminals, theaters, shopping malls and departmental stores. In such applications,
escalators will provide shorter travel time than elevators because elevator cars are limited in
size and passengers have to wait longer for the service.
In this course we will discuss the key notions pertaining to elevator systems.
i
Building Elevator Systems – A06-001
Several factors combine to influence the cost of an elevator installation, including the
passenger handling capacity, waiting interval, speed, location, finishes, intelligent group control
safety, and reliability. There are also risks associated with the use of elevators. To ensure that
persons are not stuck in elevators for longer periods of time, or worse that the elevator does not
loose stability and plummet to the basement from a high floor, the engineers responsible for
designing elevators must comply with all statutory codes and standards.
Circulation Efficiency
1
Building Elevator Systems – A06-001
And so on. There could be over a hundred different possible configurations for your building's
elevators, and each will have its advantages and disadvantages compared with the others.
DEVELOPMENT PROCESS
The design, installation, and use of an elevator system is dictated according to various
standards (aka elevator codes), which may typically be international, national, state, regional or
city based. Building codes, fire regulations, the American Disabilities Act (ADA) and other
Uniform Federal Accessibility Standards (UFAS) are a few examples of these rules to which the
engineers and architects must submit. As far as the specific rules governing the design of
elevators; American Society of Mechanical Engineer's Standard A17.1 (ASME/ANSI A17.1),
CAN/CSA B44 in Canada and EN81 (European standard) provide the detailed criteria.
Note that in most US Jurisdictions, ASME/ANSI A17.1, A17.2, A17.3, A17.5, A18.1 usually take
precedence over all other codes unless specifically advised.
Traffic Planning
Elevators’ planning in building projects is dependant on the “traffic analysis” study which varies
according to the type and usage of the building. For example, an office building typically
requires more elevators than an apartment building due to heavier loads & traffic. Elevator
professionals often use building type to assist in recommending solutions based on different
types of building traffic.
Traffic analysis is the study of the population distribution and their predicted pattern of flow
within the day. It helps in selecting:
2
Building Elevator Systems – A06-001
• The proper control systems and features to optimize and synchronize traffic flow;
• The optimum layout for the transportation devices and correct positioning in the building
and in relation to one another;
The efficiency of an elevator system is defined in terms of the quantity of service (handling
capacity) and quality of service (passenger waiting time).
Handling Capacity:
The handling capacity of elevator system is the total number of passengers that the system can
transport within a certain period of time, (usually 5 minutes i.e. 300 seconds) during the peak
traffic conditions (usually the morning up-peak*) with a specified average car loading (usually
80% of the rated capacity of the elevator). The handling capacity is usually expressed in
percentage and is calculated as:
Where
• I = Interval (seconds)
Acceptable five-minute handling capacities during peak periods for general passenger elevator
service can be taken as 10 to 16%. The criteria differs depending on the building type —
residential apartments or offices. As a rough guide, the following is acceptable:
3
Building Elevator Systems – A06-001
• Premises without specific distribution traffic, such as mixed-tenancy office buildings with
different working hours: 12 to 16%.
• Premises with excessive distribution traffic, such as single tenancy office buildings with
the same working hours: 16 to 25%.
*The up-peak mode is defined as elevator travel from lobby to upper floors. This is considered
the worst case traffic scenario in elevator planning, typically in the morning as people arrive for
work or at the conclusion of a lunch-time period. The reason for employing the up peak model
for sizing the lift is because during up- peak period, the “handling capacity” of the lift system
dominates the degree to which the traffic demand is fulfilled. It is also believed that systems that
can cope with the up-peak period are also sufficient to handle other traffic conditions.
Since the building space particularly in downtown skyscrapers is precious, the architects desire
to ensure the elevator size fit for the purpose. The purpose of the Handling Capacity
requirement is to allow designer to experiment with different lift system configurations and to
determine the optimum size, speed and number of elevators for a building based on its peak
use periods. Note that the use of smaller lift car will reduce system’s handling capacity unless
more lift cars are installed. The requirement of the handling capacity ensures that the capacity
of the lift system is not being traded off for the interval figures.
If the handling capacity of a lift system is too small, there will be lot of people queuing for the lifts
during up peak. Also, the lift cars will have to go more round trips in order to clear off the queue.
Thus system with too small handling capacity will degrade the quality of service.
Interval:
Interval or waiting interval is the average time, in seconds, between successive lift car arrivals at
the main terminal floor with cars loaded to any level. The interval represents the theoretical
longest time between elevator dispatches from the main lobby.
The interval is directly related to passenger waiting times and inversely related to the number
of elevators in a group and is calculated by the following equation:
4
Building Elevator Systems – A06-001
Where
• I = Interval
An acceptable interval during peak periods for ordinary occupancies can be taken as 25 to 30
seconds. An interval of 30 seconds means that a car will be leaving the lobby every 30 seconds
with a load of passengers.
For a fixed handling capacity, large interval means small number of lift cars and large lift car
rated capacity. Lift system with small number of lift cars but large rated capacity will result in
inefficient use of energy during off peak hour. Imagine how energy is wasted during off peak
hours when there are frequent occasions of only a few people traveling in a large lift car.
It is the time in seconds for a single car trip around a building, from the time the car doors open
at the main terminal, until the car doors reopen, when the car has returned to the main terminal
after its trip around the building.
The round trip time is estimated by adding together such factors as acceleration and
deceleration rates, full-speed running time, door opening time, door closing time, and passenger
entrance and egress times, multiplied by the probable number of stops.
Average waiting time is the average period of time, in seconds that an average passenger waits
for a lift measured from the instant that the passenger registers a landing call (or arrives at a
landing), until the instant the passenger can enter the lift. Typically this would be the sum of the
waiting times of all the passengers divided by the total number of passengers. It needs to be
clearly recognized that Interval is NOT EQUAL TO Average Waiting Time. Average waiting time
can be realistically established only through a simulation.
5
Building Elevator Systems – A06-001
Other Factors
Once the traffic analysis is done and the handling capacity determined, the next step is to select
and specify the most appropriate type of elevator. The first question to answer here is "what
exactly do we expect the elevator to accomplish for us?"
Next, we have to determine the building structure that will support the elevator:
• How many car openings are required to suit the floor plan?
6
Building Elevator Systems – A06-001
Elevator Capacity
The elevators capacity is derived from up-peak traffic analysis. The nominal capacity of the
elevator and the rated maximum passenger capacity is than known from manufacturer’s
catalogues. Table below provides standard nominal capacities and passenger relationship:
The normal peak or number of passengers per trip is generally assumed as 80% of the rated
capacity of the lift car. This does not mean cars are assumed to fill only to 80% each trip but that
the average load is 80% of rated capacity. The reason for assuming this 80% is that the
passenger transfer times are longer for a crowded lift car. For example, the last person usually
takes a longer time to enter a fully loaded lift car. Studies indicate that an 80% filled up car has
the best performance in terms of round trip times.
Table 207.1 of ASME/ANSI A17.1 Standard provides the net cab area as it relates to the
capacity
7
Building Elevator Systems – A06-001
Maximum* inside Net Platform Areas for the Various Rated Loads
Rated Load (lb) Inside Net Rated Load (lb) Inside Net
2
Platform Area (ft ) Platform Area (ft2)
500 7.0 4500 46.2
600 8.3 5000 50.0
700 9.6 6000 57.7
1000 13.25 7000 65.3
1200 15.6 8000 72.9
1500 18.9 9000 80.5
1800 22.1 10000 88.0
2000 24.2 12000 103.0
2500 29.1 15000 125.1
3000 33.7 18000 146.9
3500 38.0 20000 161.2
4000 42.2 25000 196.5
This table can be used to develop the inside dimensions of car enclosures. Note - To allow for
variations in cab designs, an increase in the maximum inside net platform area are not
exceeding 5% shall be permitted for the various rated loads.
8
Building Elevator Systems – A06-001
Number of Elevators
Several numbers of passenger elevators are usually required in most buildings in order to cope
with the traffic density. The number of elevators is derived from a traditional traffic calculation
during morning up peak. In this scenario, an elevator loads at the lobby, delivers passengers to
their floors, and returns empty for the next trip. The number of elevators required shall be
selected on the basis of a 25 to 30 second response waiting time interval between elevators.
The general rules of thumb for estimating the number of elevators are:
• For buildings with 3 or less elevator stops and gross area of less than 5,000 m2, provide
a single elevator. (Note however, if one elevator would normally meet the requirements
in the facility where elevator service is essential, two elevators shall be installed to
ensure continuity of service. If financial limitations restrict the inclusion of a second
elevator, as a minimum, a hoistway for a future elevator is recommended).
• For buildings with 4 or more elevator stops and the gross area above 6000 m2 provide
two elevators. If the gross area of the building exceeds 10,000 m2 provide a group of
three elevators.
• If distributed elevator configurations are used then the total number of elevators required
shall be increased by approximately 60% to account for the inefficiencies of the
distributed arrangement and imbalances in demand.
Two lifts of 680 kg provide a better service than one 1360 kg. The large single lift would run only
partly loaded during the major part of the day with a resulting decrease in efficiency and
increased running cost. The offset is that although 2 lifts may be costly, require more foot print
(space) and have less tenable area; the advantage is the lower operating costs and better
quality of service.
Speed of Elevators
Elevator speed is determined by travel distance and standard of service. The speed should be
selected such that it will provide short round time and 25 to 30 second interval, along with least
number of elevators to handle the peak loads. The taller buildings above 20 floors may have
high-speed lifts that do not stop at the first 10 floors. Car speed is chosen so that the driving
motor can be run at full speed for much of the running time to maximize the efficiency of power
9
Building Elevator Systems – A06-001
consumption. The overall speed of operation is determined by the acceleration time, braking
time; maximum car speed; speed of door opening; degree of advanced door opening; floor-
leveling accuracy required; switch timing and variation of car performance with car load.
The general rules of thumb, for the recommended elevator speeds for various travel distances
are:
The table above applies principally to commercial buildings; speeds in residential and
institutional buildings may be subject to local design regulations.
Zoning of Elevators
Zoning implies subdivision of the floors of the premises into clusters of stops to be served by
different elevator cars. This creates the need for people traveling to floors within that zone to
use the same lifts, thereby reducing the probable number of stops made by the lifts. This in turn
reduces the overall time lifts are accelerating and decelerating. With the reduction in time spent
in obtaining full speed or stopping from full speed, the efficiency of the overall system is
increased and so energy savings can be made.
For office buildings, a single elevator group can generally serve all floors in buildings up to 15 to
20 floors depending on the building population. The taller building more than 20 floors (up to
about 35 floors), are best served by two different elevator groups; one serving the low rise and
the other the higher floors. Such a zoning arrangement would cut down on the number of stops
per elevator, thus reducing round trip times and increasing the handling capacity of each group.
Other advantage is that the low rise group won’t need high speed elevators, thus providing an
economical and energy efficiency solution.
The same principle can also be deployed for low rise buildings of say 10 floors in a different way.
A typical example is separating elevator systems to serve even number floors and odd number
10
Building Elevator Systems – A06-001
floors. If the average waiting time is too long, passengers will call for both lift systems and travel
one floor by stair.
Location of Elevators
The location of elevators shall be such that they are easily accessible and convenient to
circulation routes. When planning the location of elevators, the following principles shall be
observed:
• Elevators should be located so that the building entrances with the heaviest traffic shall
have adequate elevator service. Elevators should be as near to the center of the
building area served as practicable, taking into consideration the distance from the
elevator bank or banks to the most distant functional areas do not exceed a maximum of
45 meters.
• Congestion at peak travel times is minimized by arranging the lift lobbies in a cul-de-sac
of, say, two lift doors on either side of a walkway, rather than in a line of four doors along
one wall. For passenger cars, three across are preferred, and not more than four in a
row shall be used. Where four or more cars are required within a group, cars shall be
placed in opposite banks, opening into a common lobby.
• As a general guide, the lobby width between two banks of passenger elevators shall not
be less than 3600 mm (~12 ft) and the lobby width between two banks of service
elevators should not be less than 4200 mm (~14’).
• When designing the service core in relation to the floor plate, the designer must ensure
that the elevator lobby should not be used as a common or public thoroughfare at
ground-floor level.
• Where elevators are accessed from corridors, they shall be located on one side of the
corridor only and shall be set back from the line of circulating corridors. Elevator
ingress/egress shall be from a distinct elevator lobby and not directly from a corridor.
• Elevator lobbies generate noise and shall be acoustically isolated from areas sensitive to
noise and vibration. Elevators shall not be placed over occupied spaces as this shall
require counter-weight safeties and reinforced pits.
11
Building Elevator Systems – A06-001
• Egress stairs shall preferably be located adjacent to elevator lobbies when possible.
• Elevators shall preferably provide positive separation between passenger and freight
/service traffic flows.
• In facilities that utilize interstitial floors and mechanical penthouses, at least one elevator
shall stop on these floors to facilitate equipment maintenance and removal.
Elevator Doors
The doors protect riders from falling into the shaft. The door opening shall be capable of
opening doors at the rate of 0.9 m/s. This is a capability speed, with actual speed being
adjusted to meet the requirements of the specific installation. The closing speed shall be set per
ASME/ANSI A17.1. All power operated doors shall be equipped with an automatic reopen
device for passenger protection.
The most common configuration is to have two panels that meet in the middle, and slide open
laterally.
• Single-speed bi-parting doors are typically used in the larger capacity ranges and when
dictated by the shaft and platform arrangement. Their operating speed is generally faster
than side-acting doors.
• Two-speed bi-parting doors have the fastest action and are used where a wide opening
is required; they are common on large passenger elevators and service elevators.
A cascading configuration is sometimes used for wider opening of service elevators where the
doors are tucked behind one another, and while closed, they form cascading layers on one side.
The clear opening (width and height) of an entrance depends on its application.
• For passenger elevators and handicap access, a minimum door opening width of 1070
mm (3'-6") and height of 2135mm (7’) is recommended.
12
Building Elevator Systems – A06-001
• Combined passenger/ service elevators typically have doors at least 1220 to 1320 mm
(4'-0" to 4'-4") wide and 2135 to 2440 mm (7'-0" to 8'-0") high.
13
Building Elevator Systems – A06-001
Selection of the best-suited type of elevator considers initial cost of the elevator plus the
building structure needed to house the lift, maintenance costs over the life of the building and
running costs.
TRACTION ELEVATORS
Traction elevators are the most popular form of elevator designs used widely across the world.
These consist of the elevator car and a counterweight held together by steel ropes looped
around the sheave. The sheave is a pulley with grooves around its circumference. The sheave
is driven by the AC or DC motor. The sheave grips the hoist ropes so that when it rotates, the
ropes move, too. This gripping is due to traction.
Roping Arrangements
14
Building Elevator Systems – A06-001
A roping system is used to attach the motor/gear reducer, the elevator car and the
counterweight. There are many different kinds of arrangements that can be used; the two most
common are:
In a One to One roping (1:1) arrangement, the hoist ropes runs from the elevator car hitch over
the machine sheaves to the counterweight hitch. The elevator car and the counterweight each
run in their own sets of guide rails. A second governor cable runs from the car up to a governor
pulley, then down to a tension pulley at the bottom of the elevator shaft, and up to the car again.
This cable rotates the governor pulley at a speed directly proportional to the speed of the car. In
15
Building Elevator Systems – A06-001
the event of excessive car speed, the governor uses another cable to activate the emergency
brake jaws which grip the guide rails and slow the car to a stop.
Arrangement of hoist ropes in which one end of each hoist rope passes from a dead-end hitch
in the overhead, under a car sheave, up over the drive sheave, down around a counterweight
shave and up to another dead-end hitch in the overhead. The car speed is one-half the rope
speed.
Counterweight
When the traction drive is rotated, power is transferred from the traction drive to the elevator car
and counterweight. The counterweight adds accelerating force when the elevator car is
ascending and provides a retarding effort when the car is descending. The counterweight is
normally sized equal to the weight of the car plus approximately half its maximum rated capacity.
It saves energy equivalent to the unbalanced load between the elevator and the counterweight
both when the car is travelling full and empty. The counterweight also ensures that the elevator
cannot fall out of control while the cable is intact.
Hoist Mechanisms
An elevator's function is to convert the electrical power, which runs the motor, into mechanical
power. There are two types of hoisting mechanisms: Geared and Gearless types.
Geared type:
In a geared machine, the motor turns a gear train that rotates the sheave. Geared traction
machines are used for medium-speed applications and have effective speeds from 0.5 m/s (100
fpm) to 2.0 m/s (400 fpm). The slower speeds are for freight operation, while the higher speeds
are typically used for passenger service in mid-rise buildings of ten stories or less.
The geared elevator system most commonly use a worm gear reducer, which is composed of a
worm gear, typically called the worm, and a larger round gear, typically called the worm gear.
These two gears which have rotational axes perpendicular to each other that not only decreases
the rotational speed of the traction pulley, but also change the plane of rotation. By decreasing
the rotation speed, we are also increasing the output torque, therefore, adding the ability to lift
larger objects for a given pulley diameter. A worm gear is chosen over other types of gearing
possibilities because of its compactness, precise speed control, quite operation and its ability to
16
Building Elevator Systems – A06-001
withstand higher shock loads. It can also be easily attached to the motor shaft and has high
resistance to reverse shaft rotation.
The efficiency of the gear train is a consideration in the selection of the type of hoisting machine.
Following key facts should be noted, when specifying geared machines:
1. The efficiency of the gear train depends on the lead angle of the gears and the
coefficient of friction of the gear materials. The lead angle is the angle of the worm tooth
or thread with respect to a line perpendicular to the worm axis. As this angle approaches
zero degrees, the reduction ratio increases and the efficiency decreases due to
increased sliding along the gear teeth. For optimum efficiency, the lead angle should be
high usually in the range of 50% to 94%.
2. The efficiency also depends on the operating parameters of the gear train. Usually,
smaller reduction ratios, higher input speeds, and larger gear reducer sizes shall result
in greater efficiencies. However, it does not mean to intent ally over-size the gear train
because the large gear train will operate less efficiently at partial load condition. The
gear reduction ratios typically vary between 12:1 and 30:1.
Geared Traction machines can be driven by AC or DC motors. The machines are normally
located overhead, directly over the hoistway but can be mounted to the side and below; and
when this is done, it is termed as "basement traction" application.
The disadvantage of geared hoisting is that the gear train will loose some energy due to friction
and thus the transmission efficiency of geared elevator is inferior to gearless machine.
Gearless type:
In gearless elevators the motor turns the sheave directly. A brake is mounted between the
motor and drive sheave to hold the elevator stationary at a floor. This brake is usually an
external drum type, which is actuated by spring force.
Gearless traction elevators are specified for high-speed applications having effective speeds
varying from 2.5 m/s (400 fpm) to 10.0 m/s (2000 fpm). These are generally used on taller
structures with more than 10 stories. In terms of energy performance, gearless drive has no
gear transmission loss thus have a transmission efficiency of 100%.
17
Building Elevator Systems – A06-001
Gearless traction machines use low torque electric motors (generally DC motors) driven by
motor generator (MG) drive or silicon-controlled rectifiers (SCR). Modern gearless traction
machines use variable-voltage; variable frequency (VVVF) drives systems.
ENGINEERING DESIGN
The traction drive depends on the friction, or traction, between the hoisting ropes and the drum.
The hoisting ropes are wound over the drum (possibly several turns are made) and down to the
counter weight, which compensates for the weight of the empty elevator car and vastly reduces
the power needed by the hoisting motor.
The friction between the ropes and the sheave grooves, which are cut on the pulley, initiates the
traction force between the traction drive and the rope. ASME A17.1 mentions that sufficient
traction shall be provided between the rope and groove to safely stop and hold the car with
rated load in the down direction. In most mechanical systems, considerable emphasis is placed
on reducing friction between parts; the reverse is the case in elevators. A lot more importance is
given to utilizing friction for traction-driven machines. In layman’s terms, traction is the gripping
force along the surface. In technical terms, traction is the frictional force.
Traction Calculation
Consider a rope passing over a driving sheave. Let T1 be the tension in the car side, and T2 in
the counterweight side.
18
Building Elevator Systems – A06-001
T1 is the addition of all weights (i.e.125% of rated load, car weight and traveling cable weight),
whereas T2 is the tension at counterweight.
The maximum available traction that can be developed is a function of the actual coefficient of
friction between the rope and groove, the shape of groove and angle of contact. Maximum
available traction = efӨ
Where
• f = coefficient of friction
• Ө = angle of contact
Hence the condition so that the elevator does not lose traction is given by:
Where
Obviously, from the above expressions, we can conclude that the maximum traction can be
achieved when the value of fӨ is increased.
1. Sheave Diameter: Available traction can be increased by increasing the arc of contact
that the rope subtends with the sheave. The ratio of rope diameter to sheave diameter
plays an important role in traction. As a good engineering practice, the sheave diameter
should be equal to 40 times the rope diameter. The larger the sheave diameter, the
more the contact area between the rope and sheave is achieved. The sheave diameter
19
Building Elevator Systems – A06-001
should also be large enough to account for the bending stresses exerted by the ropes.
However, cost is also to be considered while setting the final diameter. It will also result
in a larger machine assembly, which will create problems during installation.
2. Shape of the Groove: Available traction can be increased by changing the shape of the
groove.
• The V-groove is the most widely used type of groove. These provide the greatest
amount of bearing pressures, hence maximum traction. The angle of the groove is
kept between 32º and 40º. Traction increases with decreasing angle of the groove,
but it also leads to shorter rope life.
• The U-groove is the sheave of choice for optimum life. Its large size, in combination
with its supportive grooves, minimizes abrasion and fatigue. The groove cradles the
rope, resulting in low groove pressures, allowing the wires and strands to move
about freely while the rope is operating. Unfortunately, however, the U-grooved
sheave provides the least amount of traction.
3. Coefficient of Friction: Lastly but not the least, the available traction can be increased
by increasing the actual coefficient of friction of the material.
Note that all the above parameters are dependent on one another. Compromising on any of the
above factors should not change the final traction value. With this background, elevator system
designers need to be very careful in estimating traction and establishing their designs.
The elevator car itself is constructed with a steel framework for durability and strength. A set of
steel beams above the car, called the crosshead, span the elevator shaft from side to side and
hold the pulley for the hoist cable. A steel structure, called the sling, extends down the sides of
the car from the crosshead and cradles the floor, or platform. The sides of a passenger elevator
car are usually made from steel sheet and are trimmed on the inside with decorative paneling.
The floor of the car may be tiled or carpeted. Handrails and other interior trim may be made
from stainless steel for appearance and wearability. A suspended ceiling is usually hung below
the actual top of the car and may contain fluorescent lighting above plastic diffuser panels. The
20
Building Elevator Systems – A06-001
elevator controls, alarm buttons, and emergency telephone are contained behind panels in the
front of the car, next to the doors.
In a simple installation, the lift shaft of concrete or masonry forms the part of service core. Guide
rails run the length of the shaft to keep the car and counterweight from swaying or twisting
during their travel. Steel guide rollers or guide shoes are attached to the top and bottom of the
sling structure to provide smooth travel along the guide rails. The emergency brake mechanism
consists of two clamping faces which can be driven together by a wedge to squeeze on the
guide rail. The wedge is activated by a screw turned by a drum attached to the emergency cable.
HYDRAULIC ELEVATORS
Hydraulic elevator systems lift a car using a hydraulic ram, a fluid-driven piston mounted inside
a cylinder. All the weight of the elevator cab is supported on the piston.
The cylinder is connected to a fluid-pumping system (typically, hydraulic systems like this use oil,
but other incompressible fluids would also work). The hydraulic system has three parts:
The pump forces fluid from the tank into a pipe leading to the cylinder. When the valve is
opened, the pressurized fluid will take the path of least resistance and return to the fluid
reservoir. But when the valve is closed, the pressurized fluid has nowhere to go except into the
cylinder. As the fluid collects in the cylinder, it pushes the piston up, lifting the elevator car.
When the car approaches the correct floor, the control system sends a signal to the electric
motor to gradually shut off the pump. With the pump off, there is no more fluid flowing into the
cylinder, but the fluid that is already in the cylinder cannot escape (it can't flow backward
through the pump, and the valve is still closed). The piston rests on the fluid, and the car stays
where it is.
To lower the car, the elevator control system sends a signal to the valve. The valve is operated
electrically by a basic solenoid switch. When the solenoid opens the valve, the fluid that has
collected in the cylinder can flow out into the fluid reservoir. The weight of the car and the cargo
21
Building Elevator Systems – A06-001
pushes down on the piston, which drives the fluid into the reservoir. The car gradually descends.
To stop the car at a lower floor, the control system closes the valve again. The electric motor is
redundant during descend.
This system is incredibly simple and highly effective, but it does have some drawbacks.
• Hydraulic elevators are usually not provided with a counterweight. Thus the lift motor has
to be large enough to raise the rated load plus the dead weight of the car cage. In
traction lift, the maximum weight to be raised under normal operation is only about half
of its rated load.
• Hydraulic elevators are used in buildings up to 5 floors (14 meters rise) and have rated
speeds of 0.25 m/s (50 fpm) to 0.75 m/s (150 fpm).
22
Building Elevator Systems – A06-001
The system consists of a ram which slides inside a fixed cylinder. The cylinder has suitable
openings at the bottom for the hydraulic fluid to enter and also suitably designed to allow the
ram to slide up and down. The ram is attached to the top of the car, which acts as a capsule
carrying people or goods. The ram is pushed up by the pressure of hydraulic fluid acting
beneath. Thus the cage moves up to various floors as per the need. The cage is moved in
downward direction by allowing oil to get drained from the cylinder back to the oil reservoir.
Guide rails are required to guide the ram in a vertical plane. Car speed up to 125 feet per
minute (38.1 meters per minute) is attained and maximum travel length is 12 feet (3.6m).
Working: When the pump delivers oil to the bottom of the cylinder, as the valve meant for the
re-circulation remains closed, the oil beneath the bottom of the ram gets pressurized and this
pressurized oil lifts the ram (cage). When the cage has to be lowered, the oil is drained back to
the oil reservoir by keeping the valve open. The time for which the valve is kept open is decided
by the electro-magnetic switch, which gets its signal from the people who use the lift.
It has a cage (on which people can stand or goods can be placed), which is suspended from a
wire cable, and a jigger consisting of a fixed cylinder, a sliding ram, and a set of two pulley
blocks, which is provided at the foot of the hole of the cage. One pulley block is movable while
the other one is fixed. The sliding ram end is connected to the movable pulley block. The cage
is suspended from the other end of the rope. The raising or lowering of the cage of the lift is
done by the jigger. This arrangement is used to increase the speed of the lift by a 2:1 roping
ratio. Car speed up to 150 feet per minute is attained and maximum travel length is 48 feet
(14m).
Working: Water or any hydraulic fluid at a high pressure is admitted into the fixed cylinder of
the jigger. This high pressure hydraulic fluid pushes the sliding ram to move towards left side as
shown in the figure. When the sliding ram moves towards the left side, the distance between the
fixed and movable pulleys increases and thus the cage is lifted up. When the water or the
hydraulic fluid under high pressure inside the cylinder is released, then the distance between
the two pulleys decreases and thus the cage comes down. Thus the suspended-type hydraulic
lifts are more popular than direct type lifts.
23
Building Elevator Systems – A06-001
Besides the above basic arrangements, hydraulic elevators can also be installed with more than
one cylinder. On some, the hydraulic piston (plunger) consists of telescoping concentric tubes,
allowing a shallow tube to contain the mechanism below the lowest floor. On others, the piston
requires a deeper hole below the bottom landing, usually with a PVC casing (also known as a
caisson) for protection.
HOIST DRIVES
The motor component of the elevator machine can be either a direct current (DC) motor or an
alternating current (AC) motor. A DC motor had a good starting torque and ease of speed
control. An AC motor is more regularly used because of its ruggedness and simplicity. A motor
is chosen depending on design intent for the elevator. Power required to start the car in motion
is equal to the power to overcome static, or stationary friction, and to accelerate the mass from
rest to full speed. Considerations that must be included in the choice of an acceptable motor are
good speed regulation and good starting torque. In addition, heating of various electrical
components in continuous service should not be excessive.
• AC motor drive with variable voltage and variable frequency controller (ACVVVF).
DCMG has large energy losses in the motor and generator arrangement, which converts
electrical energy into mechanical energy and finally back to electrical energy again. DCMG drive
is NOT recommended, due to its low inherent efficiency and also because its application
requires it to be kept running when the elevator is idle.
The two speed AC motors are also considered energy inefficient. These two speed motors are
usually started up with resistance in the high-speed winding, whilst smooth deceleration is
obtained by inserting a buffer resistance, either in the low- or high-speed winding during
24
Building Elevator Systems – A06-001
transition to low speed. The insertion of buffer resistance and choke wastes much energy during
the start up and deceleration.
ACVV and ACVVVF systems are the most energy efficient option. ACVV requires approximately
70% of the input energy for the same output whereas ACVVVF will only require 50%. If the
energy to be fed back into the mains supply is taken into account, a further reduction of 5% (i.e.
45%) of energy can be achieved for the ACVVVF.
In principle:
Hydraulic elevator
Hydraulic elevators operate at slower speeds and serve up to 14 meter of travel. These are
recommended for light usage – low height installations.
Benefits
• Quick installation;
25
Building Elevator Systems – A06-001
• Upon power failure the lift lowers to the ground floor and releases the door.
Drawbacks
Traction Elevator
Roped traction elevators are much more efficient and safer. Geared traction elevators typically
serve mid-rise buildings with speeds ranging 0.5 to 2.0 m/s and gearless traction elevators can
serve buildings of any height with speeds of 2.5 m/s and higher.
Benefits
Speed Comparison
The speed of the elevator shall be within the following ranges and chosen to suit the specific
building requirements as part of the elevator traffic analysis:
Lift Comparison
The lift of the elevator shall be within the following ranges and chosen to suit the specific
building requirements as part of the elevator traffic analysis:
26
Building Elevator Systems – A06-001
All elevators, whether traction or hydraulic, require a machine room to store large electric
motors (or hydraulic pumps) and a controller cabinet. This room is located above the hoistway
(or below, for hydraulic elevators) and may contain machinery for a single or a group of
elevators.
The most significant development in the recent history of elevators has been the introduction of
Motor Room Less (MRL) elevators. Most MRL solutions are based on gearless technology.
Traditionally in motor room configurations the sheave, motor and control system are all housed
in a machine room above the elevator shaft but in MRL elevators, the machinery is installed in
the elevator shaft itself.
This was made possible by the development and application of permanent magnet (PM) system
technology in the lift motor that reduced the size of the motor by up to four times. For example,
a 6.5kW motor used in a MRL configuration can perform the same task as a conventional
16.8kW traction machine. Smaller motors also use less energy. Technical developments such
as increasing the density of the armature winding in the PM and applying their own proprietary
joint-lapped core, further reduced the motor dimensions while improving its power output. To
date the focus from all manufacturers has been on maximising the power output of the motor
while reducing its physical size.
MRL installations are generally cheaper to install, give greater architectural flexibility and
increased lettable space. Presently the speed and number of floors limit their installation - MRL
solutions range up to 30 floors and can reach up to speeds of 2.5m/s.
Since the application of MRL technology is relatively new and due to the very fact that each of
the major manufacturers provides propriety products, maintenance needs careful consideration.
Therefore when evaluating the technical aspects the end-user or building owner should be
aware of the potential pitfalls of being trapped into a high cost maintenance contract and left
with no alternative.
NOTE that the ASME A17.1 code does not specifically address MRL design.
27
Building Elevator Systems – A06-001
Governing Codes:
Elevators design shall comply with the latest edition of ASME A17.1, “Safety Code for Elevators
and Escalators” with amendments and Uniform Building Code (UBC). Other equally important
standards that govern the design of an elevator include:
1. ADA/ABA - American with Disabilities Act (ADA) Accessibility Guide Lines for Building and
Facilities; Architectural Barriers Act (ABA) Accessibility Guide Lines.
3. ASCE-7 - America Society of Civil Engineers (Minimum Design Loads for Buildings and
Other Structures)
4. ASME A17.1 - American Society of Mechanical Engineers Safety Code for Elevators and
Escalators.
8. ASME A17.3 - Safety Code for Existing Elevators and Escalators (For designing changes to
existing Elevator/Escalator Systems)
28
Building Elevator Systems – A06-001
• Australia - AS1735
The various codes may have conflicting requirements or have many potential pitfalls. But by
understanding how these fit together and what purpose they serve, you can have a successful
project. Always verify all conditions and requirements with the state and the AHJ where the
installation is taking place. ASME/ANSI A17.1, A17.2, A17.3, and A17.5 usually take
precedence over all other codes in US unless specifically advised.
Elevator runs in a hoistway built within the “Service core”. Service core is one of the most
important aspects of high rise buildings - the design of this is predominantly governed by the
fundamental requirements of meeting fire-egress regulations, achieving basic efficiency in
human movement, and creating an efficient internal layout. Typically the service core provides
the principal structural element for both the gravity load-resisting system and lateral load-
resisting system, with the latter becoming increasingly important as the height of the building
increases. The core provides the stiffness to restrict deflections and accelerations to acceptable
levels at the top of the building. The cost of a core for a typical high rise building is estimated to
be around 35 to 40 percent of the total structural cost, or 4 to 5 percent of the total development
cost.
Once the location of the service core is determined, the exact size of the core (internal shaft
dimensions, wall thickness, etc.) needs to be established.
It is next necessary to define design criteria for the services shaft and the elevator system. Early
liaison with the fire officer is important in establishing life-safety requirements.
The fire department may require fire compartmentation between the elevator lobby and elevator
shafts. A separate fire-fighting elevator — capable of moving firefighters around a burning
building when all other lifts have returned to their neutral position — is often required.
29
Building Elevator Systems – A06-001
In organizing the configuration of elevator banks in the service core, it is necessary to ensure
that a bank of two, three, or four elevators in line shares a common fire-protected shaft without a
dividing structure, so avoiding a single enclosed elevator shaft. If single enclosed elevator wells
are necessary for structural reasons, the designer must ensure that air relief slots (ideally, full-
height vertical slots) to allow adequate air relief.
Note - The core configuration is normally finalized at an early stage of design development
because of its implications for the functional layout of the building. Traditionally, the
configuration is greatly influenced by the architect. The design optimization process is
subsequently carried out by the structural and building services engineers. A large bank of
elevators is the main element in a service core design and all other elements are designed
around it.
The elevator cars are built at the elevator manufacturer's plant using standard metal cutting,
welding, and forming techniques. The rest of the elevator is assembled on the building site.
Elevator shafts are sized according to car shapes and sizes and door sizes, with due
consideration given to space requirements for guide rails and brackets, counterweight systems,
running clearances, and ancillary equipment. Sufficient air space should always be provided
around cars and elevator counterweights to minimize buffeting and airborne noise during
operation.
The building design integrates the elevator shaft from the beginning, and the shaft grows as the
building is erected. The walls of the shaft are poured concrete, and the shaft straightness and
other dimensions are carefully monitored as each floor goes up.
Guide rails, switch ramps, service ladders, and similar support equipment are bolted into the
shaft after the shaft walls are complete, but before the shaft is roofed. While the shaft is still
open at the top, a crane raises the counterweight to the top of the building and lowers it into the
shaft along its rails. The crane then lifts the elevator car and inserts it partly into the shaft. The
guide wheels connect the car to the guide rails, and the car is carefully lowered to the bottom of
the shaft.
The shaft is then roofed over, leaving a machine room above the shaft. The hoist motor,
governor, controller, and other equipment are mounted in this room, with the motor located
30
Building Elevator Systems – A06-001
directly over the elevator car pulley. The elevator and governor cables are strung and attached,
the electrical connections completed, and the controller programmed.
The structural design of elevator is goverened by ASME 17.1 and ASCE-7, in addition to local
codes and standards. The following key points should be noted:
Hoistway:
1. Construction of the hoistway enclosure should be fire resistant, generally 2-hour fire
rating and in accordance with the applicable building regulations. All penetrations for
services through the walls of the service core need to be designed to maintain fire
integrity for the prescribed period of time.
2. All elements that are part of the elevator system, particularly guide rail tie brackets,
intermediate spreader brackets and framing, as well as supports and attachments for
driving machinery shall be spaced dictated by seismic conditions, design particulars and
codes. It is important to avoid the use of tile or brick hoistway walls.
3. Beveling of the top surface of projections and setbacks in the hoistway enclosures shall
be in accordance with Rule 100.6 of ASME 17.1.
4. A vertical surface is needed for attachment of sill angles to the floor slab on each landing
where an entrance is required; or otherwise consider a notch on the top edge of each
floor slab on the entire width of the hoistway to accommodate landing sills.
5. Where the hoistway enclosure is concrete construction, provide rough openings for
hoistway entrances and grouting following installation. Where drywall hoistway
construction is utilized, erect walls around previously installed hoistway entrances.
Deviation from plumb for the hoistway enclosure should not exceed ±25 mm (1 inch) per
20 stories of height.
6. Provide rough openings for control/signal fixture recessed mounting boxes and grouting
thereof as required to maintain fire resistive characteristics of the hoistway enclosure.
7. On hydraulic elevators, sprinkler protection is required at the top of the hoistway when
the hydraulic cylinder or supply piping extends above the second finished floor elevation.
On hydraulic elevators, the hydraulic oil lines shall remain in or under conditioned space
31
Building Elevator Systems – A06-001
within the building footprint. Consider straight pipe run in PVC pipe sleeves for oil spill
containment of all buried hydraulic lines between machine room and the hoistway.
Don’ts
• Avoid locating building expansion joints between the elevator hoistway and elevator
room.
• The elevator code does NOT allow anything to be installed in the hoistway not related to
the elevator operation. Pipes, ducts and conduit not related to the elevator system are
NOT allowed to penetrate the hoistway.
Elevator Pit:
1. Elevator pit shall meet the ASME A17.1 Code requirements. Elevator pit shall be
waterproofed as required by site conditions and codes.
2. Pit shall have a concrete floor reinforced as necessary to withstand vertical forces of
elevator car or counterweight buffer impact, application of car or counterweight safeties
to guide rails, or operation of the hydraulic jack.
3. Pit shall have a sump in a front corner with a removable steel subway-type grating
installed level with the pit floor. The sump shall be constructed to minimum dimensions
of 610 mm (2 ft) cubed.
4. Where the difference in depth between adjacent pits is more than 610 mm (2 ft) provide
a means of separation extending from the pit floor to a height of not less than 1830 mm
(6 ft). Perforated materials used for the separation of pits shall reject passage of a 50
mm (2.0 inch) diameter ball.
5. Where pit access is greater than 915 mm (3 ft) in depth and is via the lowest hoistway
entrance, provide a permanently installed pit access ladder, accessible from the
hoistway entrance, extending from the pit floor to no less that 1065 mm (3'-6") above the
bottom landing sill.
6. Where conditions allow and pit depth is 2440 mm (8 ft) or greater, provide a walk-in
access door with clear opening dimensions of not less than 760 mm (2'-6") wide by 1830
32
Building Elevator Systems – A06-001
mm (6 ft) high. This door shall be equipped with a self latching lock mechanism (key-
entry only), automatic closing device, and signage to prohibit unauthorized entry.
7. A buffer access ladder shall be provided whenever the buffer oil level gauge is located
more than 1525 mm (5 ft) above the pit floor. A buffer inspection platform and access
ladder shall be provided whenever that dimension is greater than 2135 mm (7 ft).
Don’ts
• An elevator pit floor drain is NOT acceptable by codes. Elevator pit must have floor
sump pit and pump sized for a minimum 20 gallons per minute. Permanent drainage
installations require consideration of environmental regulations governing the discharge.
Pump to sanitary sewer through a 2” (50 mm) air gap or directly through an oil/water
separator to storm sewer, or to grade outside the building line is sometimes permissible
in accordance with discharge permits, regulations, and statutes.
Machine Room:
1. Elevator machine rooms shall be large enough for the elevator equipment, including
space for controllers. Machine rooms and secondary machinery spaces shall provide
required clearances around the equipment and it should be possible to remove major
equipment components of each elevator for repair without dismantling components of an
adjacent elevator. Minimum headroom shall be 2300 mm (7'6").
3. Elevator machine rooms access doors shall conform to ASME A17.1 Code. Access
doors to elevator machine rooms and secondary machinery spaces shall be of the self-
closing and self locking type. They should be provided with spring-type locks arranged to
permit the doors to be opened from the inside without a key.
33
Building Elevator Systems – A06-001
4. Where machine room and/or secondary machinery space floor levels is above or below
the point of access, provide fixed, permanent, noncombustible stairs with a maximum
angle of 60 from horizontal.
5. Provide support for machine beams and grouting thereof after installation. Whenever
possible, place machine beams on top of building steel in such manner as to be flush
with the machine room floor.
6. Provide an overhead hoisting beam in the machine room, installed directly above the
hoistway, sized in accordance with the requirements of the elevator manufacturer.
7. All openings in the floor for passage of hoist ropes, etc. shall have a 50 mm (2 inch) high
concrete curb or 50 mm (2 inch) high metal sleeves.
Don’ts
• Machine room door shall NOT contain ventilation louvers or undercuts in excess of
NFPA 80, Section 1- 11.4 requirements.
• Drains or sumps shall NOT be provided in elevator machine rooms. The room should be
made reasonably watertight. Curbs may be provided at the doors to prevent the ingress
of water. Overhead fluid piping shall not be permitted in the machine room, except for
sprinkler piping, if required. Pipes, ducts and conduit not related to the elevator system
are not allowed to penetrate the machine room. Refer ASME A17.1 (Rule 101.2,
Equipment in Machine Rooms).
Clearances:
The design of elevator systems is dependent on providing proper clearances around equipment
and at the top and bottom of the hoistway. Most clearances are dictated by the Elevator Code,
ASME A17.1. Other clearances have been established by elevator manufacturers based on
their equipment. Care shall be taken to consider several elevator manufacturers' requirements
and design for the "worst case" to allow maximum opportunity for competitive bidding. The
34
Building Elevator Systems – A06-001
following represents some of the elevator code-related clearances which shall be considered in
design:
1. Pit depth is based on the thickness of the platform, the safety plank, the run-by (set by
code), and the buffer stroke (set by code based on speed), plus a minimum bottom-of-
car clearance when the car is on compressed buffer.
2. Top terminal over-travel is based on the cab height (determined by designer), shackle
clearance (determined by elevator industry), crosshead thickness (determined by
elevator industry), and run-by (determined by code).
3. Clearances for items such as counterweight space, rail space, machine and controller
size, machine room height, top & side emergency exits and area of safe refuge on top of
cab shall be based on the manufacturers' recommendations and are also related to
control and operation.
1. Each elevator shall be provided with a separate three phase supply through a lockable
safety disconnect device, located adjacent to the door of the equipment room. This
device must be either a fused disconnect or a circuit breaker because ANSI/ASME
A17.1 requires to install an additional over-current protection device (OCPD) in the
elevator equipment room.
2. Each elevator machine room shall be provided with a minimum of one ground type
duplex receptacle outlet per elevator, and one receptacle for the master intercom panel;
NEC 620-23 and NEC 620-85. Machine room shall be equipped with a 120 volt/20
ampere minimum, ground fault circuit interrupter (GFI) – protected duplex receptacle
capable of locking in the off position. The circuit breaker panel shall contain:
35
Building Elevator Systems – A06-001
• Each hydraulic elevator shall be provided with a separate circuit for the
scavenger pump in the pit.
3. Provide a separate insulated feeder and grounding conductor from the electrical source
to the elevator controller. The conduit alone can NOT act as the grounding means.
4. All conductors and optical fibers located in the machine room shall be in conduit.
5. Where a feeder powers more than one elevator, the OCPDs must be series-designed so
a fault at one of the elevators shall be cleared by only the OCPD serving it. The feeder
OCPD needs to remain closed so the remaining elevators have power and continue to
function.
6. Designer shall consider types of hoist drives specified, i.e., Silicon Controlled Rectifier
(SCR), Variable Frequency Drive (VFD), motor generator, etc., and size service and wire
for the worse case. Consider individual isolation transformers and individual choke
reactors for each hoist motor and harmonic distortion filter units when SCR or Variable
Voltage Variable Frequency (VVVF) AC controllers are utilized.
7. The elevator supply shall be dedicated main feeder utilizing the shortest practical run
and continuous ground conductor. The supply should terminate at the respective
elevator controller.
1. Sump pump shall be provided with a twist lock simplex receptacle with matching plug,
without GFI protection. Provide pilot lamp to verify circuit is energized. NEC 620-85.
2. A separate branch circuit shall be provided for the hoistway pit lighting and at least one
duplex receptacle in the pit. All duplex receptacles in the pit shall be GFI. NEC-24, NEC
620-85.
3. Locate permanent vapor tight light with wire guard at a centerline height of 2440 mm (8 ft)
above the pit floor and capable of producing at least 54 lux (5 footcandles) of illumination
36
Building Elevator Systems – A06-001
at floor level, and a light switch inside the pit, accessible from the pit access door and
adjacent to the pit access ladder, if used.
Don’ts
• When sprinklers are provided in the elevator pit, activation of the sprinkler is not required
to initiate shutdown of elevator power.
Elevator Hoistway:
1. Only electric wiring, raceways, and cables used directly in connection with the elevator
shall be permitted inside the hoistway (Refer NEC 620-37).
2. All conductors and optical fibers located in the hoistway, except for the traveling cable,
shall be in conduit.
4. Light switch shall be located on wall inside the hoistway adjacent to the top of the pit
ladder in accordance with NEC 620-24.
5. When sprinkler protection is required at the top of the hydraulic elevator hoistway,
actuation of that sprinkler(s) shall initiate operation of the elevator power shunt trip
breaker(s). Provide smoke detection at the top of the hoistway whenever sprinklers are
installed in the hoistway.
Emergency Power:
Elevator cab lights require emergency back-up power. If the building has emergency power
available, use it to supply the cab lights. Otherwise, specify that the elevator supplier provide a
battery back-up unit to power the lights in the event of an outage.
The new ADAAG guidelines require that emergency power be available to elevators that have
four or more stories of travel above or below the accessible floor. If emergency power is used:
37
Building Elevator Systems – A06-001
1. The disconnecting means required by NEC 620-51 must disconnect the elevator from
normal power and from emergency power.
2. If more than one elevator is provided, determine (with activity input) how many elevators
are to operate on emergency power.
3. Design the emergency power to be able to operate selected elevator(s) at rated loads
and rated speeds.
4. System design must accommodate automatic sequential operation in order to bring all
elevators to the designated floor level, as required by ASME A17.1 (Rule 211.3b Smoke
Detectors) and provide selected elevator(s) with emergency power operations.
5. Provide manual override switch in main elevator lobby area(s) to override the automatic
emergency power selection.
6. Provide emergency power for machine room cooling/ventilation equipment and hoistway
7. Ventilating equipment, if the elevator is on emergency power circuit. Provide an extra set
of contacts on transfer switch (when emergency power is provided) and two-conductor
120-volt ac circuit in conduit from these contacts to junction box in machine room.
2. Heating, ventilation and cooling shall be provided in the machine room as necessary to
maintain temperature within a range of 10-32°C (50-90°F) and relative humidity
sufficiently low to prevent condensation in sensitive equipment. The most cost-effective
HVAC design that shall accommodate these requirements should be selected.
3. Cooling is typically provided through the use of return air from adjacent air conditioned
spaces as exhaust for the machine room, or via dedicated cooling units. Designs shall
provide an ambient environment which maintains the temperature and humidity within
the tolerances of the elevator equipment specified.
38
Building Elevator Systems – A06-001
4. Where elevator control systems or equipment shall remain energized during the
building's unoccupied hours, means should be provided to maintain machine room
temperature and humidity without depending on main HVAC systems that could
otherwise be shut down or set back.
5. If the elevator equipment has an emergency power supply, the machine room HVAC
should also be on emergency power circuit.
6. The National Building Codes require that all elevator hoistways be vented to prevent
accumulation of hot gases and smoke inside the hoistway. This requirement includes
non-personnel elevators if equipped with the means for top of car operation by service
personnel. The required vent shall be controlled by a motorized louver that is powered
closed. This louver shall open upon loss of electrical power or by a signal from either a
smoke detector or activation of the Fire Emergency Service in any other manner.
7. Where hydraulic elevators are installed in cold climates and subject to intermittent use,
provide means to maintain the oil temperature within acceptable operating limits.
Communication:
The Americans with Disabilities Act Accessibility Guidelines for Buildings and Facilities (ADAAG)
require the cab to have a special phone accessible by individuals with disabilities. In the event
of a breakdown, that phone must automatically call a location staffed 24 hours a day.
High-rise buildings pose additional concerns. The Uniform Building Code requires two-way
communications between the central command center and the elevators, each elevator lobby,
emergency power rooms, and by entries into enclosed stairways (Section 403.5.3). Fireman
telephone jacks and telephone cabling are typically sufficient for each of these locations.
Firefighters can then use portable telephone handsets in combination with the jacks and cabling.
The vertical transportation of people within a high rise building also depends on local fire
regulations. The fire department may require fire compartmentation between the elevator lobby
and elevator shafts. A separate fire-fighting elevator — capable of moving firefighters around a
burning building when all other lifts have returned to their neutral position — is often required.
39
Building Elevator Systems – A06-001
Dual-contact smoke detectors or addressable fire alarm system smoke detectors and control
modules shall be provided at:
• Top of the hoistway (only if sprinklers are provided at the top of the hoistway);
Smoke detectors, which are required in all elevator lobbies and elevator equipment rooms, must
be connected to the elevator controllers directly by means of auxiliary contacts and wiring, or
indirectly by means of output signals from the fire alarm control panel. If a smoke detector goes
into alarm, it signals the elevator to go into “Fire Recall Function,” at which point the controller
directs the elevator cab to travel to its pre-programmed designated landing, open its doors, and
remain stopped there until the alarm clears;(as required by ASME A17.1 (Rule 211.3b, Smoke
Detectors).
If the smoke detector at the designated landing goes into alarm, the elevator shall stop at a
predetermined alternate floor, which is usually the floor above the designated floor. However,
this can vary depending on building conditions and exterior grade. Therefore, there shall be two
signals to the elevator control panel related to smoke detectors: one from the “designated floor”
smoke detector and another combined signal from the smoke detectors at the other lobby
landings and in the equipment room.
Regardless of the number of elevators, only one smoke detector is required at each floor lobby,
but it must be located within 21 feet of every elevator door. Be sure to provide a horn/strobe
alarm in large equipment rooms because they can be noisy, isolated places.
If a hydraulic elevator loses power because a heat detector goes off — or for any other reason
— it could trap occupants for an unpleasant amount of time. To avoid this situation, designers
can specify elevator controls with a safety feature commonly called a rescuvator. Upon loss of
power, the rescuvator controls the cab, lowers it to the designated floor, and opens its doors. If
you specify a rescuvator, you must also specify a disconnect switch with an auxiliary contact
that opens when the disconnect arm moves to the open position, but stays closed when the
40
Building Elevator Systems – A06-001
OCPD trips. This switch shall ensure that the elevator won't descend into the elevator pit and
allow maintenance people to work safely in the area beneath the cab.
Detectors shall be connected to building fire alarm system in accordance with NFPA 72. Only
elevator smoke detectors shall initiate automatic emergency recall.
Key Features
1. A waterflow switch, outside stem and yoke (O.S& Y) control valve and check valve
assembly shall be provided for the elevator sprinklers.
2. The control valves shall be located outside of and adjacent to the protected elevator
machine room or hoistway.
3. A separate waterflow switch, O.S& Y valve and check valve assembly shall be provided
for each floor level where elevator machine room or hoistway sprinklers are located.
4. Control valves shall be readily accessible to qualified personnel, but should NOT be
readily accessible to the general public.
5. An inspector's test connection with outside discharge shall be provided for each
waterflow switch. Sprinkler heads shall be standard heads with intermediate temperature
classification.
41
Building Elevator Systems – A06-001
Heat Detectors:
To safeguard the passengers and electrical equipment, ASME A17.12.8.2.3.2 requires the
power source to the elevator control panel to shut down prior to the discharge of water from a
sprinkler head. The shut down shall be activated by operation of a shunt-trip breaker in the main
line power supply. Depending on your local codes, this can be achieved by installing heat or
smoke detectors within 24 inches of the sprinkler heads. Actuation of such heat detector or
sprinkler head shall cause the following sequence of operation for the affected elevators:
• Elevators which are in motion shall proceed to the nearest available landing away from
the fire floors. Upon arrival and stopping at landing, power operated doors shall open
and remain open.
• Elevators which are standing at a landing with open doors shall remain open at that floor.
If power-operated doors are closed, the system shall cause the doors to open.
• Shutdown shall occur only after the elevators are stopped at a landing, and power-
operated doors are opened.
• Automatic shutdown shall override Phase I emergency recall operation, but shall not
override Phase II emergency in-car operation per ASME A17.1, if Phase II operation is in
effect.
• Actuation of the pit sprinkler shall NOT disconnect power to the elevator.
42
Building Elevator Systems – A06-001
Fireman’s Lift:
Firefighting or fireman’s lift is an essential provision in all the high-rise buildings. The important
requirements for design and installation of such a lift are:
6. A two-way intercom;
ELEVATOR CONTROLLERS
Electromechanical switching is the oldest controller technology for elevator drive systems.
Modern installations use microprocessor and relay logic controllers.
1. Microprocessor: Computer logic control is the standard for both electric traction and
hydraulic elevators.
2. Relay logic: Mechanical electro-magnetic controller relays control the operation of the
elevator.
Microprocessors are typical in most installations. However, if you have a base that is located in
a remote location or subject to erratic building power supply, a relay logic controller may be the
best choice.
43
Building Elevator Systems – A06-001
ENVIRONMENTAL FACTORS:
The design shall consider the need to prevent or minimize environmental impacts, such as
ground oil contamination and noise pollution.
1. Noise levels above 60 DBA should not be accepted outside of elevator machine rooms
or inside of elevator cabs.
2. Oil leaks must be contained. In-ground pistons for hydraulic elevators should be
protected by a sealed, schedule 80 PVC watertight cylinder with a water-stop ring
embedded in the pit floor.
SECURITY CONSIDERATIONS:
These will be developed in conjunction with the user. In general, it is better to provide security
access control independent of the elevator system. Security in an elevator system, if necessary,
can be provided by conventional key lockouts or by card keys.
1. Conventional keys are least desirable because they are easily duplicated and usually
require considerable time to insert and actuate, thereby slowing the operation of the
elevator.
2. Card keys shall be used. These should be applied in conjunction with a security
computer so that the elevator system only passes the signal through and does not have
to process it.
44
Building Elevator Systems – A06-001
The modern elevator control systems include a logic controller that takes the user’s input and
translates it into meaningful actions. The logic controller's central processing unit (CPU) must be
given at least three critical pieces of information, namely:
The first input “where people want to go” comes directly from the users and the elevator controls
must interface with user’s requests. In its simplest form when the users desire to ride the
elevator they press a button located in the elevator lobby. The lobby is defined as the area of
the building, adjacent to the elevator, on a given floor. The user presses the either of two
buttons, up or down, correlating to the direction they want to move. The elevator logic controller
receives the signal and responds by traveling via the path of predetermined travel routes or
cycles. An elevator that is initially idle will dispatch immediately to the floor of the user request.
The elevator will stop only for other requests for moving in its current direction of travel. Once all
requests have been serviced in one direction of a cycle, the elevator will reverse and begin
responding to requests in the same manner as before. An elevator that is idle for several
minutes will return to the ground, or bottom, floor.
The second input "where each floor is" can often be determined by the addition of holes located
on a long vertical tape inside the elevator shaft. The elevator car is equipped with a light or
magnetic sensor that reads the number of and which holes are being passed by the elevator car
as it ascends and descends. The elevator controller is equipped with a means of varying the
motor’s speed based on a set of feedback signals that indicate the car’s position in the shaftway.
As the car approaches its destination, a sensor near the landing, signals the controls to stop the
car at floor level. Additional shaftway limit sensors are installed to monitor over travel & under
travel.
The third input "where the elevator car is” related to the elevator scheduling operations. When a
user presses the ‘Up’ or ‘Down’ button outside the elevator car, the elevator should begin
moving towards them. Logic controllers must have some way to determine in what order riders
should be picked up and dropped off. Many elevator systems will move in one direction (e.g.,
upward) and only pick up riders that are also signaling to go in that direction (e.g., upward).
45
Building Elevator Systems – A06-001
When the final floor that has been requested in that direction (e.g., upward) is reached the
elevator will turn around and pick up all riders signaling the opposite direction (e.g., downward).
Of course, the elevator car also stops at all floors for which riders, already inside the car, have
input a requested. A more sophisticated system, often used in hotels and other large buildings
with a lot of foot traffic, involves the traffic patterns that reoccur. These systems have logic
controllers that are programmed with information about the demand on each floor with respect
to the time of day and they route the elevator cars accordingly so as to minimize the wait for all
riders. When there are multiple elevator cars, the logic controller bases the movement on each
car on that of the others. Often, the elevator car is equipped with a load sensor so that if the
elevator is full to capacity it sends a signal to the control system and the logic controller signals
the car not to pick up any more passengers until the load is lowered.
SIMPLEX CONTROLS
Many different types of systems may be applied to control elevators. All new elevators will be
microprocessor-controlled. A single-car system is referred to as "simplex", a two-car system as
"duplex", and a system having three or more cars as "group supervisory operation". There are a
number of sub-systems such as independent service; attendant service; inspect service; fire
service etc. that can be added to the main control system.
Independent service:
Independent service allows the elevator to be run from within the car without responding to hall
calls. (In a bank of elevators, traffic would be rerouted to the other elevators, while in a single
elevator; the hall buttons will be disabled). The elevator will remain parked on a floor with its
doors open until a floor is selected and the door close button is held until the elevator starts to
travel. Independent service is useful when transporting large goods or moving groups of people
between certain floors. This service shall be included on all cars.
Attendant service:
Attendant service is activated from a key switch in the car. It allows an attendant in the car to
control the opening and closing of the doors, the direction of travel, and whether to stop or
bypass hall calls. When there is more than one car in a group, a car on attendant service is
usually called by a separate, inconspicuous corridor push-button riser. Attendant service
operation is frequently used for combined passenger/service applications.
46
Building Elevator Systems – A06-001
Inspect service:
When an elevator is placed in inspect mode, the elevator will no longer respond to calls and
comes immediately to a halt. In theory, this mode could be used as a way to stop the car in mid
flight if one did not have a stop switch key. The elevator car will continue to remain idle until
given a command from a corresponding access key switch. Key switches for access are usually
located at the bottom floor and top floor. This enables the Elevator Mechanic to gain access to
the pit of the elevator or the car top. Since this key allows entry into the hoist way of the elevator,
this key is not given out and is restricted only for use by qualified elevator technicians.
Fire service:
Fire service is usually split up into two modes; ‘phase-I’ and ‘phase-II’.
Phase-I mode is activated by smoke sensor or heat sensor in the building. Once the fire alarm is
activated, the elevator will wait an amount of time, and then proceed to go into nudging mode to
tell everyone the elevator is leaving the floor. Once the elevator has left the floor, depending on
where the alarm was set off, the elevator will go to the Fire Recall Floor. However, if the alarm is
activated on the fire recall floor, the elevator will have an alternate floor to recall to. When the
elevator is recalled, it proceeds to the recall floor and stops with its doors open. The elevator will
no longer respond to calls or move in direction.
Phase-II mode can only be activated by a key switch located inside the elevator, on the
centralized control panel (CCP). This mode is created for firefighters so that they may rescue
people from a burning building. The phase-II key switch located on the CCP has three positions:
off, on, and hold. By turning phase-II on, you enable the car to move in direction. However, like
independent service mode, the car will not respond to a car call unless you manually push and
hold the door close button. Once the elevator gets to the desired floor, it will not open its doors
unless you hold door open. This is in case the floor is burning and the firefighter can feel the
heat and knows not to open the door. You must hold door open until the door is completely
opened. For any reason the firefighter wishes to leave the elevator, they will use the hold
position on the key switch to make sure the elevator remains at that floor. At anytime the
firefighter wishes to return to the recall floor, they simply turn the key off and close the doors.
Modern commercial buildings commonly have multiple elevators with a unified control system.
The objective here is to minimize the average time any passenger spends from the time the
47
Building Elevator Systems – A06-001
elevator call button is pushed to the arrival of the first available elevator. Different systems use
different levels of sophistication. The simplest systems use a single up and down button on
each floor regardless of the number of elevators. When a passenger calls for an elevator, the
controller sends the nearest elevator that is traveling in the desired direction. The approach of
an elevator car is signaled by an illuminated arrow above the elevators doors pointing up or
down.
In more sophisticated systems, the controller monitors the elevator call system for a set, or bank,
of elevators operating side by side. The operation zone of these elevators is divided into sectors,
with each sector being made up of adjacent floors. When a car has answered a call and
completed the designated run, it becomes available to answer another call. At this point,
depending on the controller's programming, the car may be returned to a designated "home"
floor, or may be sent to the sector furthest from other operating or available cars to cover that
sector. When a call is received, the controller automatically compares the location of all the cars
in the bank and sends the nearest one.
Controllers can also be programmed to respond differently at different times of the day. For
example, the elevator controller in a busy office building will receive a preponderance of calls
from the ground floor in the morning, when workers are arriving and need to go to their
workplaces on the upper floors. In that case, the controller will be programmed to send all
unassigned cars to the ground floor, rather than have them return to a home floor in their sector.
Later in the day, a different set of instructions can be used to send unassigned elevators to
different sectors, since passengers leaving the building will be much more evenly distributed
among the floors than in the morning.
ELEVATOR SAFETY
A major attribute of an elevator system is safety and reliability. Lack of an effective safety
system could lead to injury, or possibly death of users or maintenance personnel. The elevator
system must be designed so as to protect riders with multiple backup systems for use in the
event of failure of one or more than one critical mechanism. Today's elevator systems
incorporate a wide variety of features designed to help reduce the chances of accidents and
give passengers a quick, dependable ride. The basic features include:
48
Building Elevator Systems – A06-001
Brakes
The most common elevator brake is made up of a compressive spring assembly, brake shoes
with linings, and a solenoid assembly. When the solenoid is not energized, the spring forces the
brake shoes to grip the brake drum and induce a braking torque. The magnet can exert a
horizontal force for the break release. This can be done directly on one of the operating arms or
through a linkage system. In either case, the result is the same. The break is pulled away from
the shaft and the velocity of the elevator is resumed.
In order to improve the stopping ability, a material with a high coefficient of friction is used within
the breaks, such as zinc bonded asbestos. A material with too high a coefficient of friction can
result in a jerky motion of the car. This material must be chosen carefully.
The safety brake, together with a speed-sensing governor, acts to stop an elevator, if it should
over-speed in the down direction. If an elevator over-speeds, it opens a switch, which cuts off
power to the drive motor and brake if the car travels at a preset over-speed in the down
direction. Some types of governors will also open the governor switch and cut off power to the
drive motor and brake if the car over-speeds in the up direction.
Safety Edge:
Older elevator systems use mechanical "safety edges" which cause the doors to stop or retract
when they make contact with a person or object. This device is used with the component Photo
Eye.
Photo Eye:
This device is mounted on the elevator doors and two light beams are used to detect any
obstacles that may be in the doors opening. If the beam is interrupted the doors will not close
and will automatically re-open if already closing. This device is used with Safety Edge.
Micro Light:
Modern elevator systems use a large number of invisible light rays to detect people or objects in
the doorway and reverse or stop the doors without having to make physical contact. If one of
these rays becomes interrupted the doors will not close or will not open automatically. Micro
Light door protection system replaces both the Safety Edge and Photo Eye systems.
49
Building Elevator Systems – A06-001
Door Operations:
When a user presses the Door Open or Door Close button, the door react as conditions permit.
The amount of time for which the doors are held open is programmed into the logic controller.
The elevator car doors also have a sensor that detects if someone or something is caught in the
door and stops the door closing mechanism from closing the door with the large force that is
required. This is also part of the safety system since it ensures that people are not hurt when
trying to enter or exit the elevator car.
Other than sensors that detect passengers or objects in the door opening, door operators
contain devices which limit the amount of closing force. Newer systems are better able to keep
the closing force consistent even under unusual conditions such as the "stack effect" which can
cause heavy air movement in elevator shafts.
Interlocks on the hoistway doors help assure that the elevator cannot leave a landing unless the
doors are fully closed and secured. Should the doors be forced open, the interlock circuit will be
broken, causing the elevator to immediately stop.
Various switches in the elevator shaft detect the presence of the car at certain stages of its
journey. They initiate slowdowns and stops at the proper points, and help prevent over travel in
the up or down direction.
To discourage the very dangerous practice of passengers trying to open the door of a stalled
elevator, door restraints will restrict forcible movement of the door when the car is away from the
floor. If the door is held open by the door protective devices or otherwise by the door open
button for more than a predetermined time, it will sound a warning signal and close the doors at
a reduced speed and torque. This is called “Nudging” - a system used with automatic door
operation.
This device allows access to the hoistway, if the elevator is not located at the landing. The
emergency evacuation hatch on most elevators is designed to be opened only from the outside,
by trained emergency personnel. This too is intended to help prevent any passenger from
gaining access to the dangerous elevator shaftway.
Vent Slots:
These vents are equipped in the elevator to ensure that the air is evenly distributed throughout
the car.
50
Building Elevator Systems – A06-001
In the elevator cab you'll find several items to help increase safety. For example:
Door open and door close buttons to instruct the elevator to close immediately or remain
open longer. In some elevators, holding the door open for too long will trigger an audible alarm
(This alarm might confuse some people to think that the elevator is overloaded).
A stop switch (this is not allowed under British regulations) to halt the elevator (often used to
hold an elevator open while freight is loaded). Keeping an elevator stopped for too long may
trigger an alarm. Often, this will be a key switch.
An alarm button or switch – safety switch for passengers to signal that they have been
trapped in the elevator.
Call buttons to choose a floor. Some of these may be key switches (to control access). In some
elevators, certain floors are inaccessible unless one swipe a security card or enters a pass-code
(or both). In the United States and other countries, call button text & icons are raised to allow
blind users to operate the elevator; many have Braille text besides.
Control Philosophy during Power Black Out / Emergency power operation (EPR)
When power is lost in a traction elevator system, all elevators will initially come to a halt. One
by one, each car in the group will return to the lobby floor, open its doors and shut down. People
in the remaining elevators may see an indicator light or hear a voice announcement informing
them that the elevator will return to the lobby shortly. Once all cars have successfully returned,
the system will then automatically select one or more cars to be used for normal operations and
these cars will return to service. The car(s) selected to run under emergency power can be
manually overridden by a key or strip switch in the lobby. In order to help prevent entrapment,
when the system detects that it is running low on power, it will bring the running cars to the
lobby or nearest floor, open the doors and shut down.
In hydraulic elevator systems, emergency power will lower the elevators to the lowest landing
and open the doors to allow passengers to exit. The doors then close after an adjustable time
period and the car remains unusable until reset, usually by cycling the elevator main power
switch. Typically, due to the high current draw when starting the pump motor, hydraulic
elevators aren’t run using standard emergency power systems. Buildings like hospitals and
nursing homes usually size their emergency generators to accommodate this draw. However,
51
Building Elevator Systems – A06-001
the increasing use of current limiting motor starters, commonly known as “Soft-Start” contactors,
avoid much of this problem and the current draw of the pump motor is less of a limiting concern.
Myth: Many people believe elevators are held up by only one rope that can break, leaving
passengers trapped in a falling car.
Truth: Elevators are supported by multiple steel cables. Each cable alone can support a fully
loaded car.
Truth: This will not happen. An overloaded elevator will usually not move. The doors will stay
open and a buzzer may ring until enough people get off the elevator to reduce the weight.
Myth: Some people believe they have been in an elevator where the elevator car fell several
floors and then "caught itself".
Truth: This feeling is a mystery. Elevator experts believe people may think this happened
because they 1) got on an elevator going in a different direction than expected, or 2) saw the
elevator floor indicator lights flash by quickly which gave the visual impression of falling.
Myth: Some people believe the hall doors will open when an elevator is not there.
Truth: The truth is that the elevator car controls whether the hall doors open. If the car is not at
the landing, the hall doors can't open because their opening can only be triggered by the
arriving car engaging an unlocking device after the elevator has stopped at the landing.
Myth: Some people believe that if an elevator is stuck between floors that they are in danger of
falling and should try to get out.
Truth: Absolutely not! Leaving the car on your own could result in injury. Elevator cars are
designed as "safe rooms". The safest place is inside the car. Ring the alarm and wait for help.
Leave the car only with the assistance of professional rescuers.
Myth: Pushing the CALL button repeatedly will make the elevator appear faster.
Truth: The call is registered just once; movement is in response to the elevator controllers.
Myth: Pushing the DOOR CLOSE button closes the doors faster.
52
Building Elevator Systems – A06-001
Truth: It may cause the doors to close sooner, but not faster. However, if a buzzer sounds, the
doors may close slower, it is important to get out of the doorway as quickly as possible.
53
Building Elevator Systems – A06-001
2) Acceleration - A period which the elevator moves at an ever increasing rate of speed,
usually referring to that period from standstill to full speed.
3) AC System - A control system for an AC motor which has a single synchronous speed or
two different synchronous speeds.
4) ADA (Americans with Disabilities Act) - The Americans with Disabilities Act of 1990 was
signed into law by President Bush on July 26, 1990. The ADA is designed to give civil
rights protection to people with disabilities, similar to those granted by the Civil Rights Act.
5) Anchor bolts - Bolt designed to fasten rail brackets, door sills, headers or other objects to
beams or hoistway walls.
6) Astragal - Rubber molding on the leading edge of car and hoistway doors. It is furnished
to quiet the operation of the doors as they reach their fully closed position.
7) Babbitt - A soft metal used to fill scratching of a plunger surface. It is also used to secure
hoist ropes to shackles.
8) Baked Enamel - An enamel paint that must be baked to adhere to the surface.
9) Balustrade - The side of an escalator extending above the steps. It includes skirt panels,
interior panels, decks and handrails.
10) Bolster - The bottom horizontal member of a hydraulic car sling, to which the platen plate
attaches.
11) Brace Rod - A rod extending from the elevator platform framing to another part of the
elevator car frame or sling for the purpose of supporting the platform or holding it securely
in position. Brace robs are supports for the outer corners of the platform, each of which tie
to upper portions of the stile.
12) Brackets (Guide Rail) - The steel plates, angles, or beams used to attach the rails firmly
to the hoistway.
13) Brake - A spring loaded clamping device that prevents the elevator from moving when the
car is at rest and no power is applied to the hoistway motor.
54
Building Elevator Systems – A06-001
14) Brake Drum - A round, machined surface on the motor shaft which the brake clams for
stopping.
15) Brake shoe - Moving member(s) of a brake, lined with friction material which, when in
contact with the brake drum, holds the elevator at floor level. On some types of control, it
will stop the elevator when power is removed from the hoist motor.
16) Building Type - Required to determine the requirements for service. For example, an
office building typically requires more elevators than an apartment building due to heavier
loads & traffic. Elevator professionals often use building type to assist in recommending
solutions based on different types of building traffic.
17) Brush - A device, usually of carbon or graphite composition, used to connect a circuit with
the rotating or moving portion of a DC motor, generator or other electrical device. It carries
current to and from the non-moving parts of connections.
18) Buffer - A device designed to stop a descending car or counterweight beyond its normal
limit and to soften the force with which the elevator runs into the pit during an emergency.
19) Buffer channel - A channel in the pit floor of a traction elevator that supports buffers and
guide rails.
20) Buffer springs - Large diameter springs that are permanently placed in a traction elevator
pit for the purpose of stopping a descending car or counterweight beyond its normal limit
of travel.
22) Cab - The decorative room in which people ride in a passenger elevator.
23) Cable (Rope) - Usually 4 to 6 in number, it is used to support the car and (passing over
the drive sheave to the counterweight) pull the car.
24) Cable Wrap - That amount of the drive sheave actually in contact
25) Calculated Interval - Measured in seconds, this is the time between elevator departures
from the lobby during morning up peak. An interval of 30 seconds means that a car will be
leaving the lobby every 30 seconds with a load of passengers. Traditional elevator theory
can be used to show that the interval is equal to the calculated round trip time divided by
the number of elevators.
55
Building Elevator Systems – A06-001
26) Calculated 5 Minute Handling Capacity - The number of people that can be transported
from the lobby in a five minute period, expressed as a percentage of the population.
Elevator systems with a handling capacity of 12% can handle incoming passenger traffic
up to a rate of 12% before lobby crowding occurs. Although traffic handling capacity
guidelines have been debated for years, typically this measurement is an estimate of how
many people arrive to use the elevators during the heaviest five minutes of morning rush
hour.
27) Callback - In contract elevator service, a customer request which requires a check of an
elevator other than the regularly scheduled maintenance.
28) Call Cancellation - The circuitry that clears a registered call using selector switching,
hoistway switches, or moveable brushes or contacts.
29) Capacity - The load rating, measured in pounds, for which an elevator is designed and
powered. The actual weight on the elevator should never exceed its rated capacity.
30) Car (elevator) - The load-carrying unit, including its platform, frame, enclosure, and car
door or gate.
31) Car call - Indication of the passenger's destination floor as entered from the car operating
station by pushing the corresponding floor push button.
32) Car Operating Panel - A panel mounted in the car containing the car operating controls,
such as call register buttons, door open and close, alarm, emergency stop and whatever
other buttons or key switches are required for operating.
33) Car Operating Station - A panel mounted in the car containing the car operating controls,
such as call register buttons, door open and close, alarm emergency stop and whatever
other buttons or key switches are required for operation.
34) Car Riding Lantern - A fixture mounted in the entry column, soffit or back wall which
shows the direction of car travel.
35) Car Top Inspection Station - A control panel on top of an elevator car which, when
activated, removes the car from normal service and allows the car to run at inspection
speed from the car top station only.
36) Center Opening Doors - A door type, which consists of two horizontal sliding panels,
which move in opposite directions.
56
Building Elevator Systems – A06-001
37) Clips, Rail - Special clip designed to fasten guide rails to guide rail brackets; clamps rails
firmly in place.
38) Clutch - A device mounted on the car door which pulls the hoistway doors as the car door
moves open or closed.
39) Code - A system of regulations pertaining to the design, manufacture, installation and
maintenance of elevators, dumbwaiters, escalators and moving walks. The most widely
recognized and used is ANSI A-17.1 sponsored by the National Bureau of Standards, The
American Institute of Architects, The American Society of Mechanical Engineers, and
published by ASME. It has been adopted by many states. Some states and cities have
written their own codes, most of which are based on the ANSI A-17.1. In California, the
governing code is Title 8 and 24.
41) Compensation - Using ropes, chain or other design to counterbalance transfer of hoist
rope weight from one side of the hoisting machine to the other as the car moves within the
hoistway.
42) Compensating chain - Welded-link chain used to compensate the weight of hoist rope.
One end of the chain attaches under the elevator and one end is fastened to the
counterweight.
43) Compensating rope - Wire roping installed to obtain hoist rope weight compensation.
Again, one end attached to the underside of the car and one end fastens to the
counterweight.
44) Compounding Sheave - A pulley located on the car, and on the counterweight, under
which the hoist cables run to double the capacity and reduce the speed of an elevator.
45) Control Valve - The device which on hydraulic elevators controls the oil flow to and from
the jack.
46) Controller - An electrical panel which performs many computer functions by which it
operates an elevator.
47) Corner Post - A method of mounting rails in opposite corners of the hoistway, usually to
accommodate doors in adjacent hoistway walls
48) Conventional Car Station - A car-operating panel with a faceplate that is mounted in a
fixed (non-swing) panel or sidewall.
57
Building Elevator Systems – A06-001
49) Corner Post - A method of mounting rails in opposite corners of the hoistway, usually to
accommodate doors in adjacent hoistway walls.
50) Counterweight - A weight which counterbalances the weight of an elevator car plus
approximately 50% of the capacity load.
51) Crosshead - (1) The upper member of the car frame. (2) The traveling member of a
selector.
54) Deceleration - A period during which the elevator moves at an ever decreasing rate of
speed, usually referring to that period from full speed to leveling speed.
55) Deflector Sheave - A pulley, aligned with the drive sheave, which provides a path for the
cables to drop straight to the counterweight.
56) Direct Current (DC) - An electric current flowing in one direction only and substantially
constant in value.
57) Dispatch Control System - A system that controls two or more elevators by governing
assignments in response to hall calls. Also controls zoning, peak traffic demands and
parking.
58) Door Gibs - Devices at the bottom of horizontal sliding door panels, which stick into sill
grooves and eliminate door panels swinging in or out.
59) Door Hanger - A rolling assembly fastened to the top of a door panel which supports and
allows horizontal sliding movement of the door panel. The door track on which the hanger
rolls is part of the door hanger assembly.
60) Door Lock - Any type of mechanical lock designed to prevent the opening of a hoistway
door from the landing side.
61) Door Open Time - Length of time doors stand open after reaching full open position, until
doors start to close provided no signal is received to shorten door time.
62) Door Operator - A motor-driven device mounted on the car which opens and closes the
car doors.
63) Door Panel - A portion of the door or gate, which covers the opening and moves to
uncover the opening.
58
Building Elevator Systems – A06-001
64) Door Protective Device - Any type of device used with automatic power operated doors
that detects obstructions to the normal closing of the elevator doors and either causes the
doors to reopen or go into some other mode of operation, such as nudging. A safe edge, a
safety astragal, a photoelectric device (safe ray), and electrostatic field device are
examples of door protective devices.
65) Door Sill - The threshold of a door opening with grooves to guide the bottom of the car
door.
66) Door Track - A rail which accepts the rolling assembly of the door hanger and allows the
horizontal movement required to open and close the doors. The door track is a part of the
door hanger assembly.
67) Dot Matrix Position Indicator - Position indicator with a display that uses small light
emitting diodes (LED) to display a character.
68) Drip Ring - A flange on the guide used to collect oil from the plunger so it can drain into a
container.
69) Drive - The pulley or wheel, grooved for each hoist cable, which drives the elevator up or
down.
70) Drive Machine - The power unit which applies the energy necessary to raise and lower an
elevator, material lift, or dumb waiter car or to drive an escalator, an inclined lift or a
moving walk.
71) Drive Sheave - The grooved wheel of a traction-type hoisting machine over which the
hoist ropes pass, and by which motion is imparted to the car and counterweight by the
hoist ropes.
72) Dust covers (hanger cover) - Sheet metal cover that protects the door hangar track
assembly.
73) Double-wrapped - Roping arrangement on (gearless) traction elevators, where the hoist
ropes pass around a secondary sheave and back over the drive sheave again, so the
traction (friction) of the ropes on the drive sheave is increased
74) Electric Eye - A light beam (or beams), which spans a door opening and, when
interrupted, causes the door to reopen.
59
Building Elevator Systems – A06-001
75) Emergency exit - The removable opening in the car top panel of the cab. Removable only
from the top of the car, the emergency exit permits passengers to be evacuated from the
elevator during emergency.
76) Emergency Stop Switch - A hand-operated switch in the car push button station which,
when thrown to the off position, stops the elevator and prohibits its running.
77) Enclosure - The ruggedly built room on a freight elevator in which the material being
carried is located.
78) Encoder - A device used to convert an analog signal into digital information.
79) End Post - A method of mounting the two stacks of rails on a common wall at the end of
the hoistway.
80) Escalator - A power-driven, inclined, continuous stairway used for raising or lowering
passengers.
81) Faceplate - The decorative cover which houses control devices such as position
indicators, pushbuttons, key switches, etc.
82) Fascia - Steel plate installed in the hoistway vertically to extend from the top of the
hoistway door hanger header to the sill at the landing above, which connects the hoistway
door hanger to the sill to prevents pinch points and ledges.
83) Feedback - The transmission of current or voltage from the output of a circuit or device
back to the input, where it interacts with the input signal to modify the operation of the
circuit or device.
84) Firefighter's Service - A device or group of devices which provide (1) a signal for
immediate recall to a designated landing in order to remove cars from normal use, and (2)
to permit special operation for firefighters or other authorized emergency personnel.
85) Fishplate - A steel plate, which spans the joint where two lengths of guide rails in a stack
meet.
86) Floor Selector - A mechanical, electrical, or microprocessor driven device which initiates
and/or controls some or all of these functions: establish direction of travel, acceleration,
deceleration, leveling, stopping, call cancellation, door operation, position indicators, and
hall lanterns for an individual elevator.
60
Building Elevator Systems – A06-001
88) Freight Elevator - An elevator used to carry material rather than people and provided with
vertical bi-parting doors.
89) Full Speed - The contract speed at which the elevator should run.
90) Gates (Double Blade Gate) - A vertical sliding, counterweighted device used to provide
entrance protection on freight elevators. It consists of two panels usually made of
expanded metal. The blades telescope to reduce overhead space requirements.
91) Gear - A toothed wheel designed to mesh or engage with another wheel or part for
transmitting or changing motion.
92) Geared Traction Machine - A traction machine in which the power from the motor is
transmitted to the drive sheave through reduction gears.
93) Gearless Traction Machine - A type of elevator hoisting machine on which the hoist
ropes pass over a traction drive sheave, which is an integral part of the armature. Called
gearless because no geared reduction unit is utilized.
95) Governor - (1) A mechanical speed control mechanism. For elevator, it is a wire rope
driven centrifugal device used to stop and hold the movement of its driving rope. This
initiates the activation of the car safety device. It opens a switch, which cuts off power to
the drive motor and brake if the car travels at a preset overspeed in the down direction.
Some types of governors will also open the governor switch and cut off power to the drive
motor and brake if the car overspeeds in the up direction.
96) Governor Rope - A wire rope attached to an elevator car frame that drives the governor
and, when stopped by the governor, initiates setting of the car safety.
97) Groove - "Vee" - A groove in the drive sheave which produces a pinching or wedging
effect on the cable, used on gearless machines.
98) Groove – “U" - A groove in the drive sheave, which relies on friction between groove and
cable, used on gearless machines.
99) Gross load - The combined weight of the platform, sling, cab, and rated capacity.
100) Group operation - Scanning a system of two or more cars for hall calls then dispatching
cars appropriately based on calculated estimated time of arrival.
61
Building Elevator Systems – A06-001
101) Guide - An assembly, bolted to the upper end of the cylinder, which centers the plunger in
the cylinder.
102) Guide Rails - Steel T-, round, or formed sections with guiding surfaces installed vertically
in a hoistway to guide and direct the course of travel of an elevator car and elevator
counterweights.
103) Guide Rollers - Guide shoes with rollers which rotate on the guide rails.
104) Guide Shoes - (1) Devices used mainly to guide the car and counterweight along the path
of the guide rails. They also assure that the lateral motion of the car and counterweight is
kept at a minimum as they travel along the guide rails. (2) Guiding projections mounted on
the bottom edge of horizontally sliding doors or gates, or on the sides of vertically sliding
doors or gates to guide them.
105) Group Supervisory Control System - A system that controls two or more elevators by
governing assignments in response to hall calls. Also controls zoning, peak traffic
demands and parking.
107) Hall Lantern - A corridor mounted signal light indicating that an elevator car is
approaching that landing and the direction in which the car is to travel.
108) Hall Station - Device located in hall usually near the elevator to be used when calling the
elevator to that floor.
109) Handling Capacity - The number of people that can be transported from the lobby in a
five minute period, expressed as a percentage of the population. Elevator systems with a
handling capacity of 12% can handle incoming passenger traffic up to a rate of 12% before
lobby crowding occurs. Although traffic handling capacity guidelines have been debated
for years, typically this measurement is an estimate of how many people arrive to use the
elevators during the heaviest five minutes of morning rush hour.
110) Handrail - (1) The moving handhold provided for escalator passengers, which moves over
the top of the balustrade and newels. (2) A railing serving as a support.
111) Handrail Guard - A guard, usually made of rubber, that fits over the outside of the
handrail at a point where the handrail enters or leaves the balustrade. It is designed to
keep a person's fingers out of the handrail opening.
62
Building Elevator Systems – A06-001
112) Hanger Rollers - Rollers (two per panel) from which horizontal door panels are
suspended.
113) Hitch Plate - A plate (on traction elevators) clamped to the underside of the crosshead
and to which the shackles are attached.
114) Hoist Rope - The wire ropes used to raise and lower an elevator car.
115) Hoistway - The space enclosed by fireproof walls and hoistway doors in which the
elevator travels, extending from the pit floor to the roof. (Hoistway is sometimes called
"hatchway" or "hatch".)
116) Hoistway Access - An option which allows access to the hoistway from the lowest and
uppermost landing through a spring return key switch at each access landing. Depressing
the key switch moves the car up and down the hoistway at leveling speed and enables
access to the top of the car or the pit.
117) Hoistway Door - The side of the elevator door visible in the lobby or hallway which may
be opened only when the car is at that landing and the door operator engages both the
hoistway and the car doors.
118) Hydraulic - One of two methods by which an elevator is moved, whereby the elevator is
"pushed" up by oil.
119) Hydraulic Elevator - A power elevator where the energy is applied, by means of a liquid
under pressure, in a cylinder equipped with a plunger or piston.
120) Hydraulic Valve - In the construction of hydraulic elevators, a valve used to regulate the
flow of the fluid used to raise and lower the elevator, usually a low viscosity oil.
121) Independent service - When activated through a key switch, the car is removed from
group operation and will bypass all landing calls, deactivate hall/car riding lanterns, and
respond only to car calls. Also known as hospital emergency operation.
122) Interlock - A device having two related and interdependent functions which are:
• To prevent the operation of the driving machine by the normal operating device unless
the hoistway door is locked in the closed position. An electro-mechanical device that
prevents operation of an elevator unless the hoistway doors are in the closed and locked
position;
63
Building Elevator Systems – A06-001
• To prevent opening of a hoistway door from the landing side unless the elevator is in the
landing zone and is either stopped or being stopped.
123) Intermediate Landing - Any landing served by an elevator between its upper and lower
terminal landings.
124) Interval - The time (in seconds) between elevator departures from the lobby during
morning up peak. An interval of 30 seconds means that a car will be leaving the lobby
every 30 seconds with a load of passengers. Traditional Elevatoring theory can be used to
show that the interval is equal to the calculated round trip time divided by the number of
elevators.
125) “In Use” lights - Signal on freight elevators used to indicate that the elevator is either
running or has the doors open. This is only used on freight elevators with manual bi-
parting doors.
126) Isolated platform - Car platform that is mounted on rubber vibration absorbing material to
reduce the transmission of noise and vibration. Isolated platforms are not applicable to
holeless or telescoping jacks.
127) Induction Motor - An AC motor having two parts: a rotor and a stator. The stator creates
a rotating magnetic field that induces a voltage into the rotor causing it to rotate.
129) Jamb - Any one of the three members constituting an elevator entrance frame: head jamb,
strike jamb and return jamb.
130) Junction box - Box with a cover that serves the purpose of joining different runs of cables
and providing space for the connection of conductors.
131) Landing - That portion of a floor, balcony, or platform used to receive and discharge
passengers or freight.
132) Landing Door - The movable door at the entrance of an elevator which provides access
to the hoistway.
133) Landing Zone - A zone extending from a point 18” below an elevator or material lift
landing to a point 18” above the landing.
64
Building Elevator Systems – A06-001
134) Layout - A scaled mechanical drawing showing dimensioned plan views and elevations of
an elevator hoistway and machine room to indicate space conditions, pertinent dimensions,
sizes and location of components of the installation.
135) Leveling - The movement of an elevator toward the landing sill when it is within the
leveling zone. When the word leveling is used, the inference is that the process of
attaining a level stop or position (the platform level with the landing sill) is performed
completely automatically.
136) Leveling Zone - The limited distance above or below an elevator or material lift landing
within which the leveling device is permitted to cause movement of the car toward the
landing.
• Car Call Lockout – a feature which allows the user to prevent car calls from being
registered at specific floors. Car calls are typically locked out by using keyswitches, card
readers, key pads and computer-based monitoring systems.
• Hall Call Lockout – a feature which allows the user to prevent hall calls from being
registered at specific floors. Hall calls are typically locked out by using keyswitches,
card readers, key pads and computer-based monitoring systems.
138) Load - Capacity rating in pounds which an elevator is designed to safely handle.
139) Lobby Floor Height - The main lobby is often taller than other floors. Lobby height should
be entered separately as the distance from the top of the lobby's finished floor to the top of
the finished floor of the next landing. Small express zones may be accommodated by
using the distance from the lobby to the next landing served by the elevator. For example,
if the cars do not stop at floors 2 and 3, then you may enter a lobby height of 42 feet (18'
for lobby and 12' for each of floors 2 and 3).
140) Lubricator - A device, which feeds oil to the rail and provides lubrication for sliding shoes.
141) Machine Room - The space in which the driving machine for an elevator or group of
elevators, dumbwaiter, escalator or group of escalators is located.
142) Main (Car) Guide Rails - Steel T-sections with machined guarding surfaces installed
vertically in a hoistway to guide and direct the course of travel of an elevator car.
65
Building Elevator Systems – A06-001
143) Max Car Loading - The percentage of total capacity that the car carries on each round trip.
Even though the nameplate on a 3500 pound car lists the capacity as 21 persons, it is very
unusual that 21 people will crowd into the car. This averages about 80% but can vary
depending upon tenant behavior and culture.
144) Motor Control - That portion of a control system that governs the acceleration, speed,
retardation, and stopping of the moving elevator.
145) Net Travel - The distance from the top to the bottom floor.
146) Nudging - A system used with automatic door operation which, if the door is held open by
the door protective devices or the door open button for more than a predetermined time,
will sound a warning signal and close the doors at a reduced speed and torque.
147) Number of Elevators - The number of elevators necessary to meet your requirements.
This number is derived from a traditional traffic calculation during morning up peak. In this
scenario, an elevator loads at the lobby, delivers passengers to their floors, and returns
empty for the next trip. Request a full simulation to analyze more complicated situations
where a group of cars controlled by specific dispatcher logic serves lunchtime or down
peak passenger traffic.
148) Number of Openings - Most elevators feature doors on one side of the car. Some
applications will require two sets of doors - front and rear doors. On floors where both sets
of doors open, the time the car remains at that floor is diminished since passengers may
disembark more rapidly.
149) Oil Buffer - One type of buffer (for elevators with speeds of more than 200 feet per
minute), which uses a combination of oil and spring to cushion the elevator. It is located in
the elevator pit.
150) Oil Line - The pipe that channels the oil from the power unit to the jack.
151) One to One roping (1:1) - Arrangement of elevator hoist ropes in which one end of each
hoist rope passes from the car hitch over the machine sheaves to the counterweight hitch.
With 1:1 roping, the car, counterweights, and hoist ropes all travel at the same speed.
153) Overhead - The upper portion of the elevator hoistway. Overhead is determined by the
elevator application.
66
Building Elevator Systems – A06-001
154) Overhead machine - Standard machine room location on a traction elevator, the machine
room is located above the elevator hoistway
155) Over Travel - A short distance beyond the terminal floor as allowance for building
inaccuracies, manufacturing or installation inaccuracies.
157) Packing Gland - (1) The substance, usually of elastic or flexible material formed in rings
used in the stuffing box of the worm shaft of a geared machine or of a hydraulic elevator to
prevent excessive leakage. (2) Strips or blocks of material used for shimming.
158) Parking - A feature incorporated into the signal system of an elevator or elevators by
which and elevator receives a signal to always return to a preselected landing after all its
car or landing signals have been answered and canceled.
159) Passenger Elevator - An elevator used to carry people and provided with horizontal
sliding doors.
161) Penthouse - The machine room above the hoistway on traction elevators.
162) Pickup Rollers - Devices on the hoistway door which mate with the clutch on the car door
to allow the hoistway doors to be pulled open and closed.
163) Pit - That portion of the hoistway extending from the sill level of the lowest landing to the
floor at the bottom of the hoistway.
164) Pit Channels - Steel channels on the pit floor to anchor the guide rails and other pit-
mounted devices.
166) Platform - The entire floor assembly of an elevator on which passengers stand or the load
is carried.
167) Plunger - The inside moveable part of a hydraulic jack that attaches to an elevator car
frame on direct drive application or drive sheave on a cabled hydraulic system.
67
Building Elevator Systems – A06-001
168) Position Indicator - A device that indicates the position of the elevator car in the hoistway.
It is called a hall position indicator when placed at a landing, or car position indicator when
placed in the car.
169) Power Unit - That device on hydraulic elevators which supplies the motive force to run the
car.
170) Pump - That device which draws oil from the tank and pushes it through the oil line to the
jack to move the elevator up.
171) Push Button Station - A decorative device containing one or more hand-operated
devices (buttons or switches) by which the passenger tells the controller what action is
desired.
172) Rail Clips - Devices bolted to guide rail brackets to clamp rails firmly in place.
173) Rated speed - The elevator speed in the up direction with the rated load in the car.
174) Registered call - A signal initiated by pressing a car or landing pushbutton, indicating a
demand for service at or to the landing for which the button was pressed.
175) Relay - An electric device that is designed to interpret input conditions in a prescribed
manner and after specified conditions are met, to respond and cause contact operation or
create change in associated electric control circuits.
176) Retardation - The operation of reducing the elevator drive motor speed from normal
operating speed to stop. Also referred to as Deceleration.
177) Revolutions Per Minute (RPM) - The number of completed turns per minute that an
object revolves around its axis.
179) Rise - Vertical distance from the finished floor level of the terminal landing to the finished
floor of the top landing. See also: Travel
181) Roller Guides - Guide shoes which use rollers that rotate on guide rails rather than sliding
on the rails.
182) Ropes (Hoist) - For traction elevators, a strong cord of twisted fibers such as steel which
connects the elevator car sling assembly and the counterweight passing over or around
the drive sheave. The ropes are used to raise and lower an elevator.
68
Building Elevator Systems – A06-001
184) Safe Edge - A mechanical door protective and automatic door reopening device, used
with automatic power door operators. It is arranged so that in the event the door either
approaches or meets an obstruction when closing, the safe edge will actuate an edge
safety switch that will automatically cause the doors to stop and reopen. It is vertically
mounted to extend from the bottom to the top of a horizontally sliding panel and projects
forward of the leading edge of the panel.
185) Safe Ray - A photoelectric door protective and automatic door reopening device for
automatic power door operators. It consists of a photoelectric receiving unit and light
source device arranged to project a light ray across the elevator door entrance. The
interruption of the light ray will cause the doors to remain open as long as the ray is
interrupted, or cause the reversal and reopening of doors that are closing.
186) Safety - A large clamp that anchors the car to the building to keep the elevator from falling.
187) Safety Astragal - A resilient, non-crushing member installed on the bottom of the upper
section of a biparting freight elevator hoistway door.
188) Safety Plank - The bottom member of a sling for a traction elevator, which contains the
safety.
189) Seal - A device mounted on the guide to minimize oil escaping around the plunger.
190) Secondary Sheave - A pulley on a gearless machine which serves two purposes: (1) To
allow each cable to second pass over the drive sheave and (2) To deflect the cable for a
straight drop to the counterweight.
191) Selector - An electrical device, driven by the elevator, which simulates elevator
movements.
192) Setting the Safety - The act of triggering the safety to stop the elevator from falling.
193) Shackle - Threaded rods to which the hoist cables are socketed and which bolt to the
hitch plate and the counterweight.
194) Shaft - That part of a rotor that carries other rotating members and that is supported by
bearings.
195) Sheave - A wheel mounted in bearings and having one or more grooves over which a
rope or ropes may pass.
69
Building Elevator Systems – A06-001
196) Shim - A piece of metal or other material used to fill out a space.
197) Side Post - The normal practice of mounting rails on opposite hoistway walls midways,
front-to-back.
198) Sill - The bottom horizontal member of an entrance which provides the foundation and
footing for the entrance frame. The sill extends the full width of the door travel.
199) Single Blade Gate - A vertical sliding, counterweighted device used to provide entrance
protection on freight elevators and consisting of one panel, usually made of expanded
metal.
200) Single Speed AC - A type of traction machine powered by an AC-driven motor of one
fixed speed.
201) Single Speed Door - A type of door consisting of one horizontal sliding panel.
202) Sling - The basic structural frame, which consists of two stiles, a crosshead and a bolster
or safety plant, which supports the platform and cab of an elevator.
203) Soffit - The top horizontal piece of the entrance, which is the underside of the transom.
204) Specifications - A detailed itemized description of the plans, materials, dimensions and
all other requirements proposed for the installation of the equipment.
205) Spring Buffer - One type of buffer, for elevators with speeds less then 200 feet per minute,
which cushions the elevator. It is located in the elevator pit.
206) Stack - An accurate, vertical line of rails located in the hoistway. "Stack" may also be used
when referring to conduit and electric wiring.
207) Stator - The non-rotating part of the magnetic structure in an induction motor.
209) Stile - The vertical member of the sling, one for each side.
210) Stopping - The action of final motion of the elevator from leveling speed to an accurate
floor level.
211) Strike Column - Column located inside the car, which extends the full height of the
elevator door opening. This is the column against which the sliding door closes.
212) Stuffing Box - The part of a machine or cylinder in which seals or packing is installed to
prevent leakage.
70
Building Elevator Systems – A06-001
213) Swing Return Panel - A car-operating panel that extends the full height of the car
entrance.
214) Tachometer - A device which measures the revolutions per minute of a revolving shaft. To
tach means to measure speed with a tachometer.
215) Tank (Reservoir) - A container to store the oil used to move the elevator.
216) Thrust Bearing - A bearing designed to withstand an axial load placed on a shaft such as
that imposed by a worm and worm gear.
217) Top-of-car Inspection Station - Controls on the top of the car used by an elevator
constructor to operate the car at inspection speed. It provides a means of operating an
elevator from on top of the car at slow speed during adjustment, inspection, maintenance
and repair.
218) Torque - (1) A force that produces or tends to produce rotation or torsion. The pressure,
measured in foot pounds, exerted by a rotating shaft. (2) The turning power of a motor. (3)
The turning effort a brake is designed to stop.
219) Traction Machine - An electric machine in which the friction between the hoist ropes and
the machine sheave is used to move the elevator car with the cable.
220) Traction - One of two methods by which the elevator is moved, whereby the elevator is
"pulled" up by cables.
221) Traveling Cable - A cable made up of electric conductors, which provides electrical
connection between an elevator or dumbwaiter car, or material lift, and a fixed outlet in the
hoistway or machine room.
222) Two Speed AC - A type of traction machine powered by an AC-driven motor (actually 2
motors built into one), which has 2 distinct speeds.
223) Two Speed Door - A type of door consisting of two horizontal sliding panels, which move,
in the same direction.
224) Two to One Roping (2:1) - Arrangement of hoist ropes in which one end of each hoist
rope passes from a dead-end hitch in the overhead, under a car sheave, up over the drive
sheave, down around a counterweight shave and up to another dead-end hitch in the
overhead. The car speed is one-half the rope speed.
71
Building Elevator Systems – A06-001
225) Variable Voltage - A method of controlling a DC-driven machine, which produces many
different speeds.
227) Valve - A hydraulic elevator mechanism that regulates the motion of the elevator by
regulating the flow of oil.
228) Vertical transportation - The class of transport for moving people or equipment in the
vertical direction.
229) V-Groove - A groove in the drive sheave which produces a pinching or wedging effect on
the cable, used on geared machines.
230) Wainscoting - Walls extending from the platform to the handrail or in some cases to the
underside of the car top. Typically referred to as the finish of walls in a freight elevator.
232) Worm Gear - The gear wheel which engages the revolving worm. The rotating motion of
the worm is transmitted through the worm gear to the drive sheave.
233) Zoning - The procedure which involves parking designated elevators to serve a specified
floor or group of floors.
DO’S
72
Building Elevator Systems – A06-001
73
Building Elevator Systems – A06-001
DONT’S
74
Building Elevator Systems – A06-001
75