Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Application SLSD-TH: Linear Slot Diffusers Thin

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

LINEAR SLOT DIFFUSERS THIN

AIR MOVEMENT PRODUCTS


SLSD-TH
APPLICATION
SLSD-THseries supply & return linear slot diffusers offer
high performance in a VAV outlet with pattern control and
complete blank-off true design flexibility.
Designed for efficient air distribution at cooling differentials
up to 30°F.
FEATURED STANDARD CONSTRUCTION
SLSD-TH with deflector & damper as supply linear slot diffuser.
• FRAME:
- Constructed from extruded aluminum alloy 6063-T5 of 1.2 mm thickness.
• Surface/Flush mounting - Wide border . Please check under “Dimensions and Borders type”sheet for more info.
• Angle end cap is provided. Please check under “End Cap and Mitered Corners Configurations” sheet.
• FRAME PARTITION:
- Constructed from extruded aluminum alloy 6063-T5 of 1.2 mm thickness.
• FIXED & SLIDING DAMPER:
- Constructed of aluminum sheet of 0.5 mm thickness of 3/4” & 1”slot spacing.
- By offseting the holes,the airflow rate can be reduced or can even work as blank off
for dummy parts.
- Damper works also as equalizing
. grid.
- Damper color : Black.
- The sliding damper controls the distribution of the airflow.
• DEFLECTORS:
- The fully adjustable deflection blades allow for air pattern to be controlled from vertical
straight down to horizontal along the ceiling.
• SIZES:
- Minimum length of 8”.
- Length up to 114” full section for slot number between 1 and 6.
- Length up to 80” full section for slot number greater than or equal to 7.
- Multi-sections are joined with alignment strips for continuous appearance.
• FINISHING:
- Standard finish is white color ( RAL 9010) for frame, frame partition and blades.
- Join strip provided for continu.ous slots
OPTIONS
• Frame is available in surface, lay-in T-bar & narrow borders. Please check under “Dimensions and
Borders Type”sheet.
• Insulated or non-insulated plenum box.
• Mounting Bracket.
• Open end, Flush end & Mitered cap are available. Please check under “End Cap and Mitered Corners
Configurations” sheet.
• Mitered corner for ceiling & wall application ( 90° angle or any special angle ).
• Curved for ceiling application. Please check under “End Cap and Mitered Corners Configurations”sheet.
• FC field cut.
• BO metal blank-off. Please check the “Accessories” sheet for more info.
• Alignment Strips
• LS light shield.
• D: with damper w/o deflector (return).
• DF: with deflector w/o damper (return).
• W/O deflector nor damper (return).

SAP
www.kbeinternational.com PAGE: 1/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
*Join *Join
strip
*Join strip
provide
strip provide
provide for
for for continuous
continuous
continuous slots.
slots.
slots.
ures *Matching
*Matching
*Matching return return
return RLSD-TH(supplied
RLSD-TH
RLSD-TH (supplied
(supplied without
without Damper
Damper
without oror or
Damper
patternpattern controllers)
controllers)
pattern controllers)
er with deflection
on is constructed is
of constructed of LINEAR SLOT DIFFUSERS THIN
AIR MOVEMENT PRODUCTS
lloy
nd are6063-T5
deflection andpowder
are polyester
is constructed
polyester of powder SLSD-TH
63-T5 and are polyester powder
deflection
s allow forblades allowtofor air pattern to
air pattern
,//8675$7,216
on blades
rtical
ontal allow
to Horizontal
along for airalong
the ceiling pattern MODELS
, thetoceiling MODELS
MODELS
, && PATTERN
PATTERN
PATTERN ADJUSTMENTS
ADJUSTMENTS
ADJUSTMENTS
o same
Horizontal
ediate along the
intermediate
setting. ceiling ,
setting.
6XSSO\VORWGLIIXVHUVZLWKGDPSHU GHIOHFWRU
intermediate
control
ribution the setting.
of distribution
the airflow on of the airflow on
ethe
SD-TH distribution
design of SLSD-TH
Series. of the Series.
airflow on
neet
of of SLSD-TH
aluminum
has 22x18mm Series.
sheet has 22x18mm
& inum
center sheet
1” slotof opening
3/4” 1” slot opening Product Options
has&22x18mm Product Options
ofes 3/4”
atethe & 1”
canairflow slot
be reduced opening
rate can
or be reduced or
* BracketsProduct Options
* Brackets
airflow
off rate
forDamper
parts. can
dummy work be reduced
parts.also or
Damper work also* available
Brackets *Frame available for T-bar
surface, lay-in T-bar & narrow
*Frame for surface, lay-in & narrow
dummy parts. Damper work also *Frame available for surface, lay-in T-bar & narrow
border. border.
border.
SLSD-TH-D-DF SLSD-TH-D-DF SLSD-TH-D-DF
ble in 3/4" or 1" width.
" width. One
SLSD-TH
SLSD-TH
*Plenum SLSD-TH
way box3800 *Plenum
-3800
3800
insulated One
One
One
One
orWay
box Wayinsulated orTwo
-Way
non-insulated.
way
Two
Two
Ways
Two Ways
Ways
non-insulated.
ways
RLSD-TH RLSD-T
3800 3
RLSD-TH
/4" or 1" width. *Plenum
SLSD-TH
SLSD-TH SLSD-TH
3900 box
3900
3900 - insulated
Parallel
Parallel
Parallel or
Throw
Throw
Throw non-insulated.
Opposite
Opposite
Opposite Throw
Throw
Throw RLSD-TH RLSD-T
3900 3
RLSD-TH
hite
9010) color (Raldiffuser
for slot 9010) for slot diffuser
*Mitered
vertical throwcorner*Mitered
for ceiling corner
parallel &throwfor application
wall ceilingopposite
& wall application
throw
lor (Ral 9010) for slot diffuser *Mitered corner for ceiling & wall application
or available
on request. upon request. *Blank-off
SUPPLY
SUPPLY SUPPLY *Blank-off
baffles baffles RETURN
RETURN
RETURN
lable upon request. *Blank-off baffles
ation
ble. are available. 3/4”3/4”
3/4”slot
slot slotspacing
spacingspacing SLSD-TH
SLSD-TH
SLSD-TH 3800
3800 3800 slot3/4”
3/4”3/4” slotslot spac
spacing
spacing
re available.
r continuous slots.
ots. 1”1”
1” slot slot
slotspacing
spacingspacing SLSD-TH
SLSD-TH
SLSD-TH 3900
3900 3900 1” slot
1” spacing
1” slot slot spacin
spacing
nuous slots.
SD-TH
ed without (supplied
Damper without
H (supplied without Damper or or Damper or
Note: Throw can be adjusted on site.
Email:
Email:
Email: kbe@kbeinternational.com
kbe@kbeinternational.com
kbe@kbeinternational.com -- www
-- www.kb
-- www.kbeintern
RefRef : SLD
: SLD
Ref : SLD ALLALL
ALL STATED
STATED
STATED SPECIFICATION
SPECIFICATION
SPECIFICATION AREARE ARE SUBJECTED
SUBJECTED
SUBJECTED TO CHANGE
TO CHANGE
TO CHANGE WIT
WITHOU
WITHOUT NOTIC

Return slot diffusers


ADJUSTMENTS
PATTERN
TERN ADJUSTMENTS
ADJUSTMENTS

e WayOne Way Two WaysTwo Ways SLSD-TH-D


Two Ways RLSD-TH
RLSD-TH 3800
3800 RLSD-TH RLSD-TH
RLSD-TH 3810 3810 RLSD-TH
RLSD-TH
RLSD-TH
SLSD-TH-DF
3800 3820 3820
3810 RLSD-TH
SLSD-TH3820
el Throw
Parallel ThrowOpposite
Opposite Throw Throw RLSD-TH
RLSD-TH
Opposite Throw 3900
3900 RLSD-TH RLSD-TH
RLSD-TH 3910 3910
3900 RLSD-TH
RLSD-TH 3920
RLSD-TH 3910 3920
RLSD-TH 3920
Return slot with damper Return slot w/o damper
RETURN RETURNRETURN w/o damper
SLSD-TH
SLSD-TH 3800
3800 SLSD-TH 3/4” slot3/4”
3800 slot spacing
spacing RLSD-TH
3/4” slot spacing RLSD-TH 3800,or
3800, RLSD-TH
3810 3810 or 3820
3820
3800, 3810 or 3820
SLSD-TH 3900
SLSD-TH 3900 SLSD-TH 3900 1” slot spacing
1” slot spacing 1” slot spacing RLSD-TH 3900,
RLSD-TH 3900, RLSD-TH 3910
3910 or 3920or 3920
3900, 3910 or 3920

Email: kbe@kbeinternational.com
Email: kbe@kbeinternational.com -- www.kbeinternational.com
-- www.kbeinternational.com
Email: kbe@kbeinternational.com -- www.kbeinternational.com
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION. KBE 2017
ALL STATED SPECIFICATION ARE SUBJECTED
ALL STATED TO CHANGE
SPECIFICATION WITHOUT NOTICE
ARE SUBJECTED OR OBLIGATION
TO CHANGE .
WITHOUT NOTICE OR OBLIGATION. KBE 2017 KBE 2017

SAP
www.kbeinternational.com PAGE: 2/10
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION
REV:4.0 2024
Date:12/02/2024
AIR MOVEMENT PRODUCTS

AIR MOVEMENT PRODUCTS MODEL SLSD-TH


MODEL SLSD-TH
AIR MOVEMENT PRODUCTS

MODEL LINEAR
LINEAR
DIMENSIONS
SLSD-TH
SLOT
AND
SLOT DIFFUSERS THIN
DIFFUSERS
BORDERS TYPE
AIR MOVEMENT PRODUCTS
LINEAR SLOT DIFFUSERS
AIR MOVEMENT PRODUCTS
MODEL
DIMENSIONS SLSD-TH
LINEAR SLOT DIFFUSERS
AND
SLSD-TH
BORDERS TYPE
DIMENSIONS AND BORDERS TYPE
DIMENSIONS
LINEAR AND BORDERS TYPE
SLOT DIFFUSERS
SURFACE/ FLUSH MOUNTING- WIDE BORDER
DIMENSIONS AND BORDERS TYPE
SURFACE/
SURFACE/FLUSH MOUNTING-
FLUSH WIDEWIDE
MOUNTING- BORDER
BORDER
SURFACE/ FLUSH MOUNTING- WIDE BORDER
3/4 " SLSD-TH 3800 No. of Slots S=20m
D=F-18
SURFACE/ FLUSH MOUNTING- WIDE BORDER 3/4 "SlotSLSD-TH
1 3800
2 3No. of
4 Slots
5 S=20mm
6 7
D=F-18N 3/4 " SLSD-TH 3800 No. of Slots S=20m
D=F-18 SlotN mm1 372 733 1094 145 5 1816 217
7 253
8 2
N Slot 1 2 3 4 5 6 7
N N3/4
mm" SLSD-TH
37 73 3800 No. of
109 145 181Slots
217 S=20mm
253 289
D=F-18 F mm 62 9873 134 170 206 242 278 3
SlotN mm1 37 2 3 1094 145 5 181
6 217
7 253
8
N F mm 62 98 134 170 206 242 278 314
50 F mm37 62
N mm 73 98
109 134
145 170
181 206 242 289
217 253 278
50
1" No. of Slots S=25m
50 F mm 62 SLSD-TH
98 134 3900
170 206 242 278 314
1 " Slot SLSD-TH
1 3900
2 3No. of
4 Slots
5 S=25mm
6 7
50 1"
SlotN mm SLSD-TH 3900 No. of Slots S=25m
16 S 21 1 422 833 124 4 165 5 206 6 2477 2888 3
16 S 21 "
N 1mm
Slot 1
SLSD-TH 2
42 83 3900
3
No. of
124 165
4Slots
206
5 6
247 S=25mm
7
288 329
F mm 67 108 149 190 231 272 313 3
16 S 21 N mm1 42 83
3 124 165 206 247 288
F FSlot
mm 67 108 2 149 4 231
190 5 272 6 3137 3548
F
16 S 21 F mm42
N mm 67
83 108
124 149
165 190
206 231 272 329
247 288 313
F
F mm 67 108 149 190 231 272 313 354
F
LAY-IN MOUNTING - NARROW BORDER
LAY-IN MOUNTING - NARROW BORDER
LAY-IN MOUNTING - NARROW BORDER
LAY-IN MOUNTING - NARROW BORDER
3/4 " SLSD-TH 3800 No. of Slots S=20m
LAY-IN MOUNTING - D =F
NARROW BORDER 3/4 " SLSD-TH 3800 No. of Slots S=20mm
Slot 1 2 3 4 5 6 7
D=F Slot 3/4 " 1 SLSD-TH
N 2 3 3800
4 No.
5 of6Slots7 S=20m
8
ND = F
N mm 50 86 122 158 194 230 266 3
N3/4
mm"SlotSLSD-TH
50 86 3800
1 122
2 158No.
3 of 4Slots
194 5 S=20mm
230 6 302
266 7
D=FN F mm 52 88 124 160 196 232 268 3
FSlot
mm N mm 1
52 502 124
88 3 122
86 4 158
160 5 194
196 6 268
232 7 304
230 8
266
N N mm
F mm
50 86
52 122
88 158
124 194
160 230
196 266
232 302
268
50 F mm1 " 52 SLSD-TH
88 124 3900 No. of
160 196 Slots
232 268 S=25m
304
50 1" SLSD-TH 3900 No. of Slots S=25mm
Slot 1 2 3 4 5 6 7
50 Slot 1 " 1 SLSD-TH
2 3 3900
4 5No. of6 Slots
7 S=25m
8
N mm 55 96 137 178 219 260 301 3
50 " SlotSLSD-TH
N 1mm 55 96 3900
1 137
2 1783No. 219
of4 Slots
260 S=25mm
5 301 6 342
7
F mm 57 98 139 180 221 262 303 3
16 S 16 FSlot
mm 1
57
N mm 2 139
98
55 3 137
96 4 178
180 5 219
221 6 303
262 7 344
260 8
301
16 S 16 N mm 55 96 137
F mm 57 98 178
139 219
180 260
221 301
262 342
303
16
F S 16 F mm 57 98 139 180 221 262 303 344
16
F S 16
F
F

Note: Tolerance in Dimensions are: +/- 1mm


Note: Tolerance in Dimensions are: +/- 1mm
Email: kbe@kbeinternational.com -- www.kbeinternational.com
Ref : SLD Email: kbe@kbeinternational.com
ALL STATED --TOwww.kbeinternational.com
SPECIFICATION ARE SUBJECTED Note:
CHANGE Tolerance
WITHOUT in Dimensions
NOTICE OR OBLIGATION . are: +/- 1mm
Ref : SLD ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION. K
Note: Tolerance in Dimensions are: +/- 1mm
Email: kbe@kbeinternational.com -- www.kbeinternational.com
Ref : SLD Email: kbe@kbeinternational.com
ALL STATED -- TO
SPECIFICATION ARE SUBJECTED www.kbeinternational.com
CHANGE WITHOUT NOTICE OR OBLIGATION.
Ref : SLD ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION. K

Note: Tolerance in Dimensions are: +/- 1mm

SAP
www.kbeinternational.com PAGE: 3/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
AIR MOVEMENT PRODUCTS
MODEL SLSD
LINEAR SLOT DIFFUSERS THIN
LINEAR SLOT DIFFUSERS
AIR MOVEMENT PRODUCTS SLSD-TH
END CONFIGURATIONS AND MITERED CORNERS

END CAP AND MITERED CORNERS CONFIGURATIONS


END CONFIGURATIONS
END CONFIGURATIONS
TypeEA Type O
Type E Type Type C TypeType
F F
Angle
Angle End Cap EndCap
Cap Open End Open End Flush End Cap

Face Overall Face Overall Face Overall


*STD end cap for wide border Face Overall *STD end cap for narrow border

End plate for type EType M F are removable for field end trim.
& Type
Mitered Cap
MITERED CORNERS
Factory assembled mitered corner sections are available with 90° angle or any special angle.
Mitered corners are provided with standard length of 40cm external dimension, other lengths
are provided upon request.
Factory assembled mitered corners reduce field installation time and assure precise cutting and
Face Overall
proper fit.
CORNERS (C)
Factory assembled mitered corner sections are available with 90° angle or any special angle.
Mitered corners are provided with standard length of 40cm internal dimension, other lengths
DUCT Variable
are provided upon request.
Factory assembled WIDTH
mitered corners reduce field installation time and assure precise cutting and
90°
proper fit.
Corners are fabricated with Open end cap.
400mm

135°

CURVED SLOT
Factory curved linear slot diffuser manufac-
tured as arc or full circle for various radius &
CURVED CEILING SLOT (CU-CE)
number of slots.Curved slots are provided
without air pattern.
Factory curved linear slot diffuser manufactured
as arc or full circle for various radius & number
of slots. Curved slots are provided without
damper & air pattern.
Curved slots with wide borders are
manufactured with a standard of Angle end cap.
Curved slots with narrow borders are
Email: kbe@kbeinternational.com -- www.kbeinternational.com
Ref : SLD manufacturedALL with a standard of Flush end cap.
STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION. KBE 201

SAP
www.kbeinternational.com PAGE: 4/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
AIR MOVEMENT PRODUCTS
MODEL SLSD-TH
AIR MOVEMENT PRODUCTS
MODEL LINEAR SLSD-TH
SLOT DIFFUSERS
LINEAR SLOT DIFFUSERS THIN
ACCESSORIES
MODEL SLSD-TH
LINEAR SLOT DIFFUSERS
SLSD-TH
MODEL SLSD-TH
AIR MOVEMENT PRODUCTS
AIR MOVEMENT PRODUCTS
AIR MOVEMENT PRODUCTS
ACCESSORIES
LINEAR SLOT DIFFUSERS
ACCESSORIES
LINEAR SLOT DIFFUSERS
ACCESSORIES
ACCESSORIES

ALIGNMENT STRIPS
Join strips
ALIGNMENT and
ALIGNMENT
STRIPS Pins areSTRIPS provided on all units FCFC This option
FIELD CUT allows the linear slot diffuser to
FIELD CUT
over 2400mm (96”) with no extra cost. Provid- to size at the job site. The diffuser is suppli
Join strips and Pins are provided on all units This option allows the linear slot diffuser to be c
ing linear alignment ofPins
continuous linearon slot 150mm (6”) longer with the slot spacers se
over ALIGNMENT
2400mm
ALIGNMENT Join strips
(96”) STRIPS
with
STRIPSandno extraarecost.
provided
Provid- all to This
size
FC
FCoption
at FIELD
the
FIELD joballows
CUT
CUT
site. the
Thelinear slot
diffuser isdiffuser
suppliedto
diffuser, the
unitsand join
over strip
2800mm slides into
(112") the
withoutside
slotno
& be allow
150mm to trimming.
cut(6”) size at the
longer
Field
jobthe
with
cutThe
site. would be specifie
diffuser setisback
ing linear
Joinalignment
strips of continuous
Pins linear
are provided on all units This option allows the slot spacers
linear slot diffuser
inside
Join stripschannels
and Pins
extra cost.ofProviding
the diffuser
are provided frame.
linear allTypical
onalignment
units a continuous
This option
supplied 150mm run
allows (6”) oflonger
the diffuser
linearwith or room
slot diffuser
the slot layout
to b
diffuser,
overthe2400mm
join strip slideswith
(96”) intonothe outside
extra cost.&Provid- allow trimming.
to size at the Field
jobcutsite.would be specified
The diffuser wh
is suppl
for2400mm
over all frame types.
(96”)
of continuous with no
linear extra cost. Provid-
slot diffuser, to required
size
spacers at
settheand
job
back where
site.
to allowthere
The may
diffuser
trimming. be isa duct
supplied
Field len
cut
inside ing
channels
linear of the diffuser
alignment frame.
of continuous linearthe
Typical slot a continuous
150mmrun oflonger
(6”) diffuser or room
with the slotlayout
spacersis s
ing linearjoin alignment
strip of
slidescontinuous
into the linear
outside slot
& variation.
150mm
would be (6”) longerwhere
specified with thea slot spacersrun
continuous set b
for all diffuser,
frame types. the join strip slides into the outside & required andtrimming.
allow where there maycut
Field bewould
a ductbe lenght
specif
diffuser, the joinchannels
strip slides intodiffuser
the outside & allow
of trimming.
diffuser or room Field cut would
layout be specified
is required and
insideinside
channels of the of the
diffuser frame.frame.
Typical variation.
a continuous run of diffuser or room layou
inside channels offor
thealldiffuser
frame frame.
types. Typical a continuous
where there may run beof adiffuser or room
duct length layout is
variation.
for allTypical
frame types. required and where there may be a duct le
for all frame types. required and where there may be a duct lengh
variation.
variation.

BO METAL BLANK-OFF LS LIGHT SHIELD


BO METAL
Blank-offsBLANK-OFF
are used to cover inactive sections of LS LIGHT SHIELD
Light Shield is used to cover non plenum r
the linear slot diffuser. sections of the linear slot diffuser from ligh
Blank-offs are used to
BO METAL cover inactive sections of
BLANK-OFF Light LS
Shield is usedSHIELD
LIGHT to cover non plenum return
BO METAL
the linear slot BLANK-OFF LStion. Shipped
LIGHT loose for field cutting and ins
SHIELD
BOdiffuser.
METAL BLANK-OFF LS LIGHT
sections of theSHIELD
linear slot diffuser from light refl
Blank-offs are used to cover inactive sections of tion. Shipped loose isforused
Light Shield fieldtocutting and plenum
cover non installa
Blank-offs are used to cover inactive sections of Light Shield is used to cover non plenum retu
the linear slot diffuser. Lightsections
Shield isofused to cover
the linear slotnon plenum
diffuser from lig
the linearBlank-offs are used to cover inactive
slot diffuser. sections of the linear slot diffuser from light r
sections of the linear slot diffuser. return
MB sections
tion. Shipped
MOUNTING of the
looselinear
for slot
BRACKETfielddiffuser
cutting from
and in
tion. Shipped loose for field cutting and insta
A drawing specifying the area of light reflec tion. Shipped loose for field
MB MOUNTING BRACKET
concern should be provided. cutting and installation.
MB MOUNTING BRACKET
MB MOUNTING BRACKET

Email: kbe@kbeinternational.com -- www.kbeinternational.com


Ref : SLD ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION.
24 Email: kbe@kbeinternational.com -- www.kbeinternational.com
Ref : SLD ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION.
24
Email: kbe@kbeinternational.com -- www.kbeinternational.com SAP
www.kbeinternational.com
Ref : SLD Email: kbe@kbeinternational.com
SPECIFICATION ARE SUBJECTED--TOwww.kbeinternational.com PAGE:. 5/10
24
Ref : SLD
ALL STATED CHANGE WITHOUT NOTICE OR OBLIGATION
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION.REV:4.0 2024
24 ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION
Date:12/02/2024
LINEAR SLOT DIFFUSERS THIN
AIR MOVEMENT PRODUCTS SLSD-TH
MODEL SLSD-TH34
PERFORMANCE DATA

AREA
No.
THROW FACTOR
Of
DIRECTION AK (Ft²) per FACE VELOCITY (FPM) 500 700 900 1100 1300 1500 1700 1900 2100 2300
Slots Meter of
Length
AIRFLOW (CFM/M) 41 57 73 89 105 122 138 154 170 186
SP (Inch. Wg) 0.014 0.028 0.046 0.069 0.096 0.128 0.164 0.205 0.250 0.300
VERTICAL 0.081 FT²
NC <15 <15 <15 16 22 27 32 36 40 43
Throw(Ft)@50,100,150Fpm 13,5,2 17,8,3 21,10,5 23,12,7 26,13,9 27,15,10 29,16,12 31,17,13 32,18,14 33,18,15
1 AIRFLOW (CFM/M) 44 61 78 96 113 131 148 165 183 200
SP (Inch. Wg) 0.054 0.106 0.175 0.261 0.365 0.486 0.624 0.779 0.952 1.142
HORIZONTAL 0.087 FT²
NC 16 26 34 40 45 49 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 13,3,2 23,9,3 30,13,5 36,17,7 41,20,8 45,22,10 49,24,11 52,26,12 55,28,12 58,29,13
AIRFLOW (CFM/M) 76 106 137 167 198 228 258 289 319 350
SP (Inch. Wg) 0.015 0.030 0.050 0.075 0.105 0.140 0.180 0.225 0.275 0.330
VERTICAL 0.152 FT²
NC <15 <15 <15 18 24 29 34 38 42 45
Throw(Ft)@50,100,150Fpm 19,8,3 23,12,6 27,15,9 30,17,11 33,20,13 35,22,15 37,23,17 39,24,18, 40,25,19 41,27,20
2 AIRFLOW (CFM/M) 76 106 136 166 196 227 257 287 317 347
SP (Inch. Wg) 0.040 0.078 0.129 0.193 0.270 0.359 0.461 0.576 0.704 0.844
HORIZONTAL 0.151FT²
NC 15 25 32 37 42 46 49 >50 >50 >50
Throw(Ft)@50,100,150Fpm 18,8,5 24,13,7 29,16,9 33,19,11 36,21,13 39,23,14 41,25,15 44,26,16 6,28,17 48,29,18
AIRFLOW (CFM/M) 110 153 197 241 285 329 372 416 460 504
SP (Inch. Wg) 0.017 0.033 0.055 0.082 0.114 0.152 0.195 0.244 0.298 0.357
VERTICAL 0.219 FT²
NC <15 <15 <15 21 27 32 37 40 44 47
Throw(Ft)@50,100,150Fpm 22,10,5 27,15,9 31,19,12 34,21,14 37,24,16 39,26,18 41,28,20 43,29,21 45,30,22 46,32,23
3 AIRFLOW (CFM/M) 104 146 187 229 270 312 354 395 437 478
SP (Inch. Wg) 0.030 0.059 0.098 0.146 0.204 0.272 0.349 0.436 0.533 0.639
HORIZONTAL 0.208 FT²
NC <15 23 30 35 40 44 47 >50 >50 >50
Throw(Ft)@50,100,150Fpm 21,11,7 25,15,10 29,18,12 31,20,14 34,22,16 34,24,17 37,25,18 39,26,19 40,27,20 42,28,21
AIRFLOW (CFM/M) 143 200 257 314 371 428 485 542 599 656
SP (Inch. Wg) 0.019 0.037 0.061 0.091 0.127 0.169 0.217 0.271 0.331 0.397
VERTICAL 0.285FT²
NC <15 <15 17 24 30 35 40 44 47 >50
Throw(Ft)@50,100,150Fpm 23,12,7 28,17,11 32,21,14 35,25,16 38,26,18 40,28,20 42,30,21 44,31,22 46,32,23 47,34,24
4 AIRFLOW (CFM/M) 131 183 235 287 339 392 444 496 548 600
SP (Inch. Wg) 0.025 0.050 0.082 0.122 0.170 0.226 0.290 0.362 0.442 0.530
HORIZONTAL 0.261 FT²
NC <15 22 29 35 39 43 47 >50 >50 >50
Throw(Ft)@50,100,150Fpm 21,11,7 25,15,10 29,18,12 31,20,14 34,22,16 34,24,17 37,25,18 39,26,19 40,27,20 42,28,21
AIRFLOW (CFM/M) 175 244 314 384 454 524 593 663 733 803
SP (Inch. Wg) 0.021 0.041 0.068 0.102 0.142 0.189 0.243 0.304 0.371 0.445
VERTICAL 0.349 FT²
NC <15 <15 21 28 34 39 44 48 >50 >50
Throw(Ft)@50,100,150Fpm 22,13,9 27,17,12 30,21,14 33,23,16 35,26,18 38,27,20 39,29,21 41,30,22 43,31,23 44,33,24
5 AIRFLOW (CFM/M) 156 218 280 342 404 467 529 591 653 715
SP (Inch. Wg) 0.025 0.049 0.082 0.122 0.170 0.226 0.290 0.362 0.442 0.530
HORIZONTAL 0.311 FT²
NC <15 20 28 35 40 44 48 >50 >50 >50
Throw(Ft)@50,100,150Fpm 25,13,8 28,16,11 31,18,13 33,20,15 35,21,17 37,23,18 38,24,19 40,25,19 41,26,21 42,27,22

SAP
www.kbeinternational.com PAGE: 6/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
LINEAR SLOT DIFFUSERS THIN
AIR MOVEMENT PRODUCTS SLSD-TH
MODEL SLSD-TH34
PERFORMANCE DATA
AREA
No.
THROW FACTOR
Of FACE VELOCITY (FPM) 500 700 900 1100 1300 1500 1700 1900 2100 2300
DIRECTION AK (Ft²) per
Slots Meter of
Length
AIRFLOW (CFM/M) 206 288 371 453 536 618 700 783 865 948
SP (Inch. Wg) 0.024 0.047 0.077 0.115 0.161 0.214 0.275 0.344 0.420 0.504
VERTICAL 0.412 FT²
NC <15 15 25 32 39 44 48 >50 >50 >50
Throw(Ft)@50,100,150Fpm 19,13,1023,16,12 26,18,14 28,21,16 30,23,17 32,24,18 33,25,19 35,26,20 36,27,21 37,28,22
6 AIRFLOW (CFM/M) 180 252 324 396 468 540 612 684 756 828
SP (Inch. Wg) 0.030 0.058 0.096 0.143 0.200 0.266 0.342 0.427 0.522 0.626
HORIZONTAL 0.36 FT²
NC <15 19 28 36 42 47 47 >50 >50 >50
Throw(Ft)@50,100,150Fpm 25,11,7 30,14,10 34,17,12 37,19,13 39,20,15 42,21,16 44,23,17 45,24,17 47,25,18 48,26,19
AIRFLOW (CFM/M) 237 331 426 520 615 710 804 899 993 1088
SP (Inch. Wg) 0.027 0.053 0.087 0.130 0.182 0.242 0.311 0.388 0.474 0.569
VERTICAL 0.473 FT²
NC <15 19 29 37 43 49 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 14,13,1117,14,11 19,15,12 20,17,14 21,18,15 23,18,15 23,18,15 25,19,16 25,20,17 26,20,18
7 AIRFLOW (CFM/M) 203 284 365 447 528 609 690 771 853 934
SP (Inch. Wg) 0.039 0.076 0.126 0.188 0.263 0.350 0.450 0.562 0.687 0.824
HORIZONTAL 0.406 FT² NC
<15 18 29 37 45 >50 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 24,8,5 32,11,7 37,14,9 43,17,10 45,18,11 49,18,13 53,21,14 54,23,13 57,24,14 58,25,15
AIRFLOW (CFM/M) 267 374 481 587 694 801 908 1015 1121 1228
SP (Inch. Wg) 0.031 0.060 0.099 0.148 0.207 0.276 0.355 0.443 0.541 0.649
VERTICAL 0.534 FT²
NC <15 23 33 42 49 >50 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 14,13,1117,14,11 19,15,12 20,17,14 21,18,15 23,18,15 23,18,15 25,19,16 25,20,17 26,20,18
8 AIRFLOW (CFM/M) 226 316 407 497 588 678 768 859 949 1040
SP (Inch. Wg) 0.053 0.103 0.171 0.255 0.356 0.474 0.609 0.761 0.930 1.116
HORIZONTAL 0.452 FT²
NC <15 17 30 40 49 >50 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 23,3,2 35,7,3 42,11,5 50,15,5 53,15,6 59,15,8 65,19,9 66,21,7 71,23,7 72,24,8

NOTES:
1- Performance Data is Based on ASHREA 70-06
2- CFM: Standard air density and ISOTHERMAL conditions.
3- AIRFLOW: based on CFM per Linear Meter of Grille
4- static pressure (SP): Inches of Water Gauge
5- Face Velocity: Face discharge velocity in feet per minute (fpm)
6- Noise Criteria: NC Level is based on room attenutaion of 10db ( sound power level Re: 10-12Watts)
7- Throw: Projection distance in FEET from diffuser discharge at which the maximum velocity has been
reduced to specifyied terminal velocity (Vt). Data show are for 50,100,150 Terminal velocity (fpm)
8- Vertical Throw: tested as diffuser installed in wall throwing horizontaly in the room
9- Horizontal Throw: tested as diffuser installed in Ceiling throwing in the room

SAP
www.kbeinternational.com PAGE: 7/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
LINEAR SLOT DIFFUSERS THIN
AIR MOVEMENT PRODUCTS SLSD-TH
MODEL SLSD-TH10
PERFORMANCE DATA
AREA
No. THROW FACTOR
Of DIRECTION AK (Ft²) per FACE VELOCITY (FPM) 500 700 900 1100 1300 1500 1700 1900 2100 2300
Slots Meter of
Length
AIRFLOW (CFM/M) 49 68 87 107 126 146 165 184 204 223
SP (Inch. Wg) 0.008 0.016 0.026 0.039 0.055 0.073 0.094 0.117 0.143 0.172
VERTICAL 0.097 FT²
NC <15 <15 <15 <15 <15 18 22 25 29 32
Throw(Ft)@50,100,150Fpm 11,2,2 15,6,2 18,10,5 20,12,7 22,15,9 24,17,10 25,18,12 26,20,13 28,21,14 29,22,15
1 AIRFLOW (CFM/M) 54 75 96 118 139 161 182 203 225 246
SP (Inch. Wg) 0.019 0.037 0.060 0.090 0.126 0.168 0.216 0.270 0.330 0.396
HORIZONTAL 0.107 FT²
NC <15 <15 17 22 27 31 34 37 40 43
Throw(Ft)@50,100,150Fpm 12,6,2 19,11,5 24,14,7 28,17,9 32,19,11 35,21,12 38,22,13 40,24,14 42,25,15 44,26,16
AIRFLOW (CFM/M) 100 139 179 219 259 299 338 378 418 458
SP (Inch. Wg) 0.014 0.027 0.045 0.067 0.094 0.125 0.161 0.201 0.246 0.295
VERTICAL 0.199 FT²
NC <15 <15 <15 18 24 28 33 36 40 43
Throw(Ft)@50,100,150Fpm 20,7,3 25,12,7 28,16,10 31,19,13 34,22,15 36,24,16 38,26,18 39,28,20 41,29,21 42,30,23
2 AIRFLOW (CFM/M) 91 127 164 200 237 273 309 346 382 419
SP (Inch. Wg) 0.015 0.030 0.050 0.075 0.105 0.140 0.180 0.225 0.275 0.330
HORIZONTAL 0.182FT²
NC <15 <15 16 21 26 30 33 37 39 42
Throw(Ft)@50,100,150Fpm 18,7,2 25,11,5 30,13,6 35,15,8 38,17,9 41,18,9 43,19,10 46,21,11 48,22,12 50,22,13
AIRFLOW (CFM/M) 151 211 272 332 393 453 513 574 634 695
SP (Inch. Wg) 0.020 0.038 0.063 0.094 0.114 0.152 0.195 0.244 0.298 0.357
VERTICAL 0.302 FT²
NC <15 <15 19 26 32 37 41 45 48 >50
Throw(Ft)@50,100,150Fpm 25,10,5 31,16,10 35,20,13 38,23,16 41,26,18 44,29,20 46,31,22 48,33,24 49,34,25 51,36,27
3 AIRFLOW (CFM/M) 124 174 223 273 322 372 422 471 521 570
SP (Inch. Wg) 0.014 0.027 0.045 0.067 0.094 0.125 0.161 0.201 0.246 0.295
HORIZONTAL 0.248 FT²
NC <15 <15 16 21 26 30 34 37 40 42
Throw(Ft)@50,100,150Fpm 23,9,4 30,12,6 35,14,7 40,16,8 43,17,9 46,19,9 48,20,10 51,21,11 53,22,11 55,22,12
AIRFLOW (CFM/M) 203 284 365 447 528 609 690 771 853 934
SP (Inch. Wg) 0.025 0.049 0.081 0.121 0.169 0.225 0.289 0.361 0.441 0.529
VERTICAL 0.406FT²
NC <15 17 26 32 38 43 47 >50 >50 >50
Throw(Ft)@50,100,150Fpm 27,11,6 33,18,11 38,22,14 41,25,17 44,28,19 47,31,21 50,34,23 52,36,25 53,37,25 55,39,28
4 AIRFLOW (CFM/M) 155 216 278 340 402 464 525 587 649 711
SP (Inch. Wg) 0.014 0.027 0.045 0.067 0.094 0.125 0.161 0.201 0.246 0.295
HORIZONTAL 0.309FT²
NC <15 <15 16 22 27 31 35 38 41 44
Throw(Ft)@50,100,150Fpm 26,12,6 33,15,7 39,17,9 44,19,10 47,20,10 50,23,11 52,24,12 55,25,13 57,26,13 59,26,14
AIRFLOW (CFM/M) 256 358 460 562 664 767 869 971 1073 1175
SP (Inch. Wg) 0.030 0.059 0.098 0.146 0.204 0.272 0.349 0.436 0.533 0.639
VERTICAL 0.511 FT²
NC <15 21 30 36 42 47 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 25,11,5 32,17,9 36,21,12 40,25,15 43,28,17 46,31,19 49,34,21 51,36,23 53,37,24 55,39,26
5
AIRFLOW (CFM/M) 183 256 329 403 476 549 622 695 769 842
SP (Inch. Wg) 0.016 0.031 0.051 0.076 0.106 0.141 0.181 0.226 0.276 0.331
HORIZONTAL 0.366 FT²
NC <15 <15 18 24 29 33 37 41 44 46
Throw(Ft)@50,100,150Fpm 28,15,7 35,19,9 41,22,11 46,25,13 49,27,13 52,29,14 55,31,15 57,32,16 59,34,17 62,34,18

SAP
www.kbeinternational.com PAGE: 8/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
LINEAR SLOT DIFFUSERS THIN
AIR MOVEMENT PRODUCTS SLSD-TH
MODEL SLSD-TH10
PERFORMANCE DATA

AREA
No. FACTOR
THROW FACE VELOCITY (FPM) 500 700 900 1100 1300 1500 1700 1900 2100 2300
Of AK (Ft²) per
DIRECTION
Slots Meter of
Length
AIRFLOW (CFM/M) 308 431 554 678 801 924 1047 1170 1294 1417
SP (Inch. Wg) 0.035 0.068 0.113 0.169 0.236 0.314 0.403 0.503 0.614 0.737
VERTICAL 0 .616 FT²
NC <15 23 31 38 43 48 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 19,8,2 26,14,6 31,19,9 35,22,11 38,26,13 41,28,15 44,31,17 46,33,18 48,34,19 50,36,20
6 AIRFLOW (CFM/M) 211 295 379 463 547 632 716 800 884 968
SP (Inch. Wg) 0.019 0.037 0.062 0.093 0.130 0.173 0.222 0.277 0.338 0.405
HORIZONTAL 0.421 FT²
NC <15 <15 20 27 32 37 41 44 47 >50
Throw(Ft)@50,100,150Fpm 29,19,9 36,25,12 42,29,15 47,33,17 50,36,18 54,39,20 57,41,21 59,43,22 61,45,23 64,46,24
AIRFLOW (CFM/M) 362 506 651 795 940 1085 1229 1374 1518 1663
SP (Inch. Wg) 0.039 0.077 0.127 0.190 0.265 0.353 0.453 0.566 0.691 0.829
VERTICAL 0.723 FT²
NC <15 23 31 38 43 47 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 10,4,2 17,9,3 22,14,3 26,17,4 29,22,6 31,23,8 34,26,10 36,28,10 39,29,11 41,30,11
7 AIRFLOW (CFM/M) 237 332 427 521 616 711 806 901 995 1090
SP (Inch. Wg) 0.240 0.047 0.078 0.117 0.163 0.217 0.279 0.349 0.426 0.511
HORIZONTAL 0.474 FT²
NC <15 15 23 30 36 41 45 49 >50 >50
Throw(Ft)@50,100,150Fpm 28,24,11 35,32,15 42,38,20 46,44,23 50,48,24 54,52,28 58,54,29 59,57,30 61,60,32 65,62,33
AIRFLOW (CFM/M) 415 580 746 912 1078 1244 1409 1575 1741 1907
SP (Inch. Wg) 0.044 0.086 0.142 0.212 0.296 0.394 0.506 0.632 0.772 0.926
VERTICAL 0.829 FT²
NC <15 21 29 35 40 44 48 >50 >50 >50
Throw(Ft)@50,100,150Fpm 10,4,2 17,9,3 22,14,3 26,17,4 29,22,6 31,23,8 34,26,10 36,28,10 39,29,11 41,30,11
8 AIRFLOW (CFM/M) 263 368 473 578 683 788 893 998 1103 1208
SP (Inch. Wg) 0.031 0.060 0.099 0.148 0.207 0.276 0.355 0.443 0.541 0.649
HORIZONTAL 0.525 FT²
NC <15 19 28 35 41 46 >50 >50 >50 >50
Throw(Ft)@50,100,150Fpm 29,26,13 41,33,19 49,40,26 57,44,30 63,48,32 68,54,38 71,59,39 75,59,40 79,61,43 82,65,44

NOTES:
1- Performance Data is Based on ASHREA 70-06
2- CFM: Standard air density and ISOTHERMAL conditions.
3- AIRFLOW: based on CFM per Linear Meter of Grille
4- static pressure (SP): Inches of Water Gauge
5- Face Velocity: Face discharge velocity in feet per minute (fpm)
6- Noise Criteria: NC Level is based on room attenutaion of 10db ( sound power level Re: 10-12Watts)
7- Throw: Projection distance in FEET from diffuser discharge at which the maximum velocity has been
reduced to specifyied terminal velocity (Vt). Data show are for 50,100,150 Terminal velocity (fpm)
8- Vertical Throw: tested as diffuser installed in wall throwing horizontaly in the room
9- Horizontal Throw: tested as diffuser installed in Ceiling throwing in the room

SAP
www.kbeinternational.com PAGE: 9/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024
LINEAR SLOT DIFFUSERS THIN
AIR MOVEMENT PRODUCTS
SLSD-TH

ORDERING INFORMATION

MODEL SPACING BORDERS TYPE END FINISHING NUMBER OF LENGTH


TYPE
(inch) CONFIGURATION SLOTS SIZES
(inch)

-- - - D-DF - -- A - RAL 9010 - -

8”
A: Angle end cap 10”
SLSD-TH10: 1 in (Std for wide border)
SLSD-TH34: 3/4 in 12”
O: Open end cap 14”
(Std for corner) ˚
F: Flush end cap
˚
(Std for narrow border)
M: Mitered end cap 1: One Slot ˚
D-DF: with damper & deflector ˚
(supply) (std) 2: Two Slots
200”
DF: Deflector (return) 3: Three Slots
D: Damper (return) 4: Four Slots
--- : without damper & without 5: Five Slots
deflector (return)
6: Six Slots
--: Standard
7: Seven Slots
CU-CE: Curved Ceiling
C : Corner 8: Eight Slots
--: Flush Mounting
Wide Border (std) RAL 9010: Pure White
NB: Lay-in Mounting Semi Matt (std)
Narrow Border RAL"num":Other Ral color
B: Brut

N.B: - For more information, please check the submittal sheet.


- Sizes: minimum length 8”.
- For special design, a drawing should be provided.

SAP
www.kbeinternational.com PAGE: 10/10
REV:4.0 2024
ALL STATED SPECIFICATION ARE SUBJECTED TO CHANGE WITHOUT NOTICE OR OBLIGATION Date:12/02/2024