Pages From Diffusers - 2022 - V1
Pages From Diffusers - 2022 - V1
Pages From Diffusers - 2022 - V1
F
See website for Specifications
MODELS:
Supply Models:
ML-37 / ½” Slot
ML-38 / ¾” Slot
ML-39 / 1” Slot
ML-TZ / ¾” Slot Horizontal Dampered Angular Down Vertical Fully Dampered
Horizontal
Return Models:
MLR-37 / ½” Slot
MLR-38 / ¾” Slot
MLR-39 / 1” Slot
MLR-TZ / ¾” Slot One Way Opposed Vertical & Horizontal Opposed Unequal Flow
(One Slot Dampered)
F15
DIMENSIONS diffusers
ML / MLR UNIT DIMENSIONS
Redefine your comfort zone. ™ | www.titus-hvac.com
Frame & Border Type 3 with Frame & Border Type 4 with Frame & Border Type 6 with
F
D'=Duct Size
• Concealed Mounting
D'=Duct Size D' plus 1¼"
D' plus ½"
D'=Duct Size
35/16" 35/16"
1⅞" 115/16" 35/16"
1⅞"
1"
¾" ½"
¾" S ⅛" ¾"
S 1⅛" S
¾" O' = D' plus ¾" ¾"
O' = D' minus ⅛" O' = D' minus ⅛"
Frame & Border Types 7A, 7B with Border Types 9A, 9B with Border Type 11 with
35/16" ¾"
35/16"
115/16" 1¾"
11/16" 1⅞"
9/16"
3⅛" 3⅛"
1¾" 1¾"
13/16"
7/16"
11/16"
¾" ¾"
S S
7/16" 7/16"
F
• Curved Flange Border • Tape & Spackle Border
• Concealed Mounting • H9 Hard Ceiling Clip
• Equalizing Grid
½x½x½
Aluminum
Equalizing Grid
Duct 1⅛"
by Others
¾"
DIMENSIONS
C D = Duct Size
D =CDuct Size
O O
O
O
F Frame
and/or
Border Type
X
C
X-X
X
O
X
C
X-Y
Y
O C
X
X-Z
O
Z Y
C
Y-Y
Y
O C
Y
Y-Z
Z
O
Z
C
Z-Z
O
Z
S=½ S=¾ S=1 S=½ S=¾ S=1 S=½ S=¾ S=1 S=½ S=¾ S=1
1 17/8 21/8 23/8 2 2¼ 2½ 2⅛ 23/8 25/8 13/8 15/8 17/8
2 31/8 35/8 41/8 3¼ 3¾ 4¼ 33/8 37/8 43/8 25/8 31/8 35/8
3 43/8 51/8 57/8 4½ 5¼ 6 45/8 53/8 61/8 37/8 45/8 53/8
4 55/8 65/8 75/8 5¾ 6¾ 7¾ 57/8 67/8 77/8 51/8 61/8 71/8
5 67/8 81/8 93/8 7 8¼ 9½ 71/8 83/8 95/8 63/8 75/8 87/8
6 81/8 95/8 111/8 8¼ 9¾ 11¼ 83/8 97/8 113/8 75/8 91/8 105/8
7 93/8 111/8 127/8 9½ 11¼ 13 95/8 113/8 131/8 87/8 105/8 123/8
8 105/8 125/8 145/8 10¾ 12¾ 14¾ 107/8 127/8 147/8 101/8 121/8 141/8
ML / MLR-37 Not Available in Type 22
1 7/8"
1 7/8" 1 7/8"
9/16"
3/4" 9/16"
3/4" 3/4"
3/4" 9/16"
5 3/4" 5 3/4" 5 3/4" 5 3/4"
2 11/16" 4"
1 3/8" 5 5/16"
F
BORDER LT (LAY-IN T-BAR) FOR 4" NOMINAL WIDTH
1 3/8" 2 11/16"
3 3/4" 3 3/4"
9/16" TYP
3/4" TYP REF
3 3/8" 3 3/8"
3 13/16" 3 13/16"
DIMENSIONS
LT Border NT Border
D = Duct Size
C
C
D = Duct Size
O
O
F Nominal Length
(inches)
Border LT NT Border
C O C O
24 22 /85
23 /16
13
23 /8
3
233/8
30 285/8 2913/16 293/8 293/8
36 345/8 3513/16 353/8 353/8
48 465/8 4713/16 473/8 473/8
60 585/8 5913/16 593/8 593/8
72 705/8 7113/16 713/8 713/8
DIMENSIONS
• Ideal when the exact length of an ML or MLR diffuser is not known • The field cut ML or MLR diffuser is 72 inches long, with the sides pre-
until it is being installed punched to assure the proper alignment of field installed spacers.
• Standard factory cut diffusers can be trimmed up to 6 inches. If more These field installed spacers provide additional rigidity during and
than 6 inches are to be removed, use the optional field cut diffuser. after cutting.
MITERED CORNERS
Available Models:
MC-37 / ½” Slot
MC-38 / ¾” Slot
MC-39 / 1” Slot
DIMENSIONS FOR 90° MIITERED CORNERS
F
No. of 1A, 1B 2A, 4, 7A 2B, 7B 3, 6, 11 9A 9B 12, 15 22
Slots O D O D O D O D O D O D O D O D
D = Duct Size
D = Duct Size
O
PLENUMS W 1⅛" L
Available Uninsulated Models: A
Optional
MP-37 / ½” Slot
Internal
MP-38 / ¾” Slot ½" B Insulation
MP-39 / 1” Slot H (MPI Models)
MP-37-SP / ½” Slot Optional
MP-38-SP / ¾” Slot (MP-SP
MP-39-SP / 1” Slot Note: End caps are not insulated. Design)
ACCESSORIES
BLANK-OFFS
Available Insulated Models:
MPI-37 / ½” Slot BLKS / Cold Rolled Steel
MPI-38 / ¾” Slot / Fits over Neck
MPI-39 / 1” Slot / Black Finish
Furnished in 6-foot lengths.
Field installed.
BLKV / Vinyl
MPI-37-SP / ½” Slot / Fits in Slot
MPI-38-SP / ¾” Slot / Black Finish
MPI-39-SP / 1” Slot
Field
Side Rail
Field
Assembled
Corners
Alignment
Strips Temporary
Gauge
• Mounting frame for Titus Modulinear diffusers • Diffusers can be removed and replaced
assures a clean, accurately dimensioned easily, without disfiguring the ceiling
Temporary
Gauge
ceiling opening to receive the diffuser • Furnished with the diffusers in Frame &
• Choice of designs for wet plaster Border Types 3, 4, 6, 7A, 7B and 11
End Frame
and other types of ceilings • Cut to length in the field
(Factory Welded)
• Allows the diffusers to be unpacked and
installed after construction is finished
Mitered
Corner
F
Spring Clip
Factory
Blade Spacer
Optional Support (Welded) Optional
End Border Bar Blank-Offs
Optional Alignment
End Cap Pins
• Diffusers can be joined together end- • Factory-made mitered corners are
to-end to form long, continuous slots accurately welded and carefully
#8 x 1¼ Oval Head Screw
(Border Type 1A only)
• End borders and end caps close off finished for a smooth, unbroken
the ends of the diffusers and simplify corner treatment. Mitered corners
Pattern installations ending at walls and are rendered inactive with factory-
Controller
other stopping points (see page F17) installed blank-offs. (see page F20)
• Alignment pins maintain close
#6 x ½ SMS joints between sections
(Border 22)
Align Y-Y ends using supplied SS1 Spline Support Clips
INSTALLATIONS
F22
INSTALLATIONS diffusers
• Titus Modulinear diffusers are so simple and rugged they are • Field-cut diffuser Model MLF (above) or MLRF is shipped in standard
routinely cut to length in the field with a fine tooth, high-speed 6-foot lengths
carbon steel metal cutting blade • Model MLF or MLRF diffuser can be cut to any length. Field-installed
• Factory-cut diffuser Model ML (above) or MLR is ordered for a spacers and other hardware are furnished with the diffuser for one
specified length from the factory, but can be trimmed as much as 3 field cut. Additional field cut kits are available at additional cost.
inches from each end in the field • Unit is shipped without end caps or end borders
Hanger Bracket
for Border Types 9A, 9B, 12, 15
Hanger Bracket
for Border Types 2A, 2B
Hanger Bracket
for Frame & Border
Types 3, 4, 6, 7A, 7B, 11
F
Duct
By Others
INSTALLATIONS
Ceiling
These hanger brackets are a convenient Here the diffuser is simply pushed up into the For installation in a Titus mounting frame,
means of attaching hanger wires to sup- duct until the outer legs of the hanger brack- these hanger brackets function like the duct
port the diffuser from the structural mem- ets snap into the hems of the duct. Screws type brackets at the left. The outer legs of the
bers of the building. then snug the diffuser against the ceiling. brackets engage the side rails of the mount-
ing frame.
F23
PERFORMANCE DATA diffusers
ML-37 / ½" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM
Redefine your comfort zone. ™ | www.titus-hvac.com
Airflow, cfm/ft. 5 10 16 21 26 31 36 42 47
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
1-Slot NC (Noise Criteria) - - 20 27 32 37 40 44 46
Horizontal 1-1-6 3-6-12 6-11-15 10-12-17 11-14-19 12-15-21 13-16-23 14-17-25 15-18-26
Vertical 2 6 9 11 12 14 15 16 17
Airflow, cfm/ft. 10 21 31 42 52 62 73 83 94
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
2-Slot NC (Noise Criteria) - 13 23 30 35 40 43 47 49
Horizontal 1-3-10 5-10-17 10-15-21 14-17-25 16-19-28 17-21-30 19-23-33 20-25-35 21-26-37
Vertical 4 8 13 16 17 19 20 22 24
Airflow, cfm/ft. 16 31 47 62 78 94 109 125 140
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
3-Slot NC (Noise Criteria) - 15 25 32 37 41 45 48 51
Horizontal 2-4-13 7-13-21 13-18-26 17-21-30 19-24-34 21-26-37 23-28-40 25-30-43 26-32-45
Vertical 5 10 15 19 21 23 25 27 28
Airflow, cfm/ft. 21 42 62 83 104 125 146 166 187
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
4-Slot NC (Noise Criteria) - 16 26 33 38 43 46 50 52
Horizontal 3-6-14 10-14-25 14-21-30 19-25-35 22-28-39 25-30-43 27-33-46 28-35-49 30-37-52
Vertical 7 12 18 22 25 27 29 31 33
Airflow, cfm/ft. 26 52 78 104 130 156 182 208 234
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
5-Slot NC (Noise Criteria) - 17 27 34 39 44 47 51 53
Horizontal 3-7-16 11-16-28 16-24-34 22-28-39 25-31-44 28-34-48 30-36-52 32-39-55 34-41-58
Vertical 7 14 20 25 28 30 32 35 37
Airflow, cfm/ft. 31 62 94 125 156 187 218 250 281
F
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
6-Slot NC (Noise Criteria) - 18 28 35 40 44 48 51 54
Horizontal 4-9-18 12-18-30 18-26-37 24-30-43 28-34-48 30-37-52 33-40-56 35-43-60 37-45-64
Vertical 7 16 22 27 30 33 35 38 40
Airflow, cfm/ft. 36 73 109 146 182 218 255 291 328
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
7-Slot NC (Noise Criteria) - 19 29 35 41 45 49 52 55
Horizontal 6-10-19 13-19-33 19-28-40 25-33-46 30-36-52 33-40-56 35-43-61 38-46-65 40-49-69
Vertical 8 16 24 29 32 35 38 41 43
Airflow, cfm/ft. 42 83 125 166 208 250 291 333 374
Static Pressure 0.006 0.023 0.051 0.090 0.141 0.203 0.277 0.362 0.458
8-Slot NC (Noise Criteria) - 19 29 36 41 46 49 53 55
Horizontal 7-10-20 14-20-35 20-30-43 27-35-49 32-39-55 35-43-60 38-46-65 40-49-70 43-52-74
Vertical 8 17 26 31 35 38 41 43 45
NC corrections for various diffuser lengths Throw correction multiplier for length
Length 2 4 6 8 10 Length 2 4 8 10
PERFORMANCE DATA
F
Static Pressure 0.004 0.016 0.037 0.065 0.102 0.146 0.199 0.260 0.330
6-Slot NC (Noise Criteria) - 12 21 28 34 38 42 45 48
Horizontal 5-10-19 13-19-39 19-29-49 26-39-57 32-45-64 39-49-70 43-53-75 46-57-81 49-60-85
Vertical 8 15 24 30 33 36 39 42 45
Airflow, cfm/ft. 43 87 130 174 217 260 304 347 391
Static Pressure 0.004 0.016 0.037 0.065 0.102 0.146 0.199 0.260 0.330
7-Slot NC (Noise Criteria) - 12 22 29 34 39 42 45 48
Horizontal 6-10-21 14-21-42 21-31-53 28-42-61 35-49-69 42-53-75 47-58-81 50-61-87 53-65-92
Vertical 8 16 24 32 36 39 42 45 48
Airflow, cfm/ft. 50 99 149 198 248 298 347 397 446
Static Pressure 0.004 0.016 0.037 0.065 0.102 0.146 0.199 0.260 0.330
8-Slot NC (Noise Criteria) - 13 23 29 35 39 43 46 49
Horizontal 7-11-22 15-22-45 22-33-57 30-45-66 37-52-73 45-57-81 50-61-87 54-66-93 57-70-99
Vertical 8 16 24 33 38 42 45 48 51
NC corrections for various diffuser lengths Throw correction multiplier for length
Length 2 4 6 8 10 Length 2 4 8 10 PERFORMANCE DATA
Supply -3 0 +2 +3 +5 Throw Correction 0.72 1.0 1.5 1.7
Return 0 +3 +5 +6 +8
Airflow, cfm/ft. 7 13 20 26 33 40 46 53 59
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
1-Slot NC (Noise Criteria) - - 13 20 26 30 34 37 40
Horizontal 1-2-6 3-6-16 6-12-21 11-16-24 14-19-27 16-21-29 18-22-32 20-24-34 21-25-36
Vertical 2 8 12 14 15 17 18 19 20
Airflow, cfm/ft. 13 26 40 53 66 79 92 106 119
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
2-Slot NC (Noise Criteria) - - 16 23 29 33 37 40 43
Horizontal 1-3-12 5-12-23 12-17-29 15-23-34 19-27-38 23-29-42 26-32-45 28-34-48 29-36-51
Vertical 5 11 16 19 22 24 26 28 30
Airflow, cfm/ft. 20 40 59 79 99 119 139 158 178
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
3-Slot NC (Noise Criteria) - - 18 25 30 35 39 42 45
Horizontal 2-5-14 8-14-28 14-21-36 19-28-42 23-33-46 28-36-51 32-39-55 34-42-59 36-44-62
Vertical 7 13 20 24 27 29 32 34 36
Airflow, cfm/ft. 26 53 79 106 132 158 185 211 238
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
4-Slot NC (Noise Criteria) - - 19 26 32 36 40 43 46
Horizontal 3-6-16 11-16-33 16-24-42 22-33-48 27-38-54 33-42-59 37-45-63 39-48-68 42-51-72
Vertical 8 15 23 28 31 34 36 39 42
Airflow, cfm/ft. 33 66 99 132 165 198 231 264 297
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
5-Slot NC (Noise Criteria) - - 20 27 33 37 41 44 47
Horizontal 4-8-18 12-18-36 18-27-46 24-36-54 30-42-60 36-46-66 41-50-71 44-54-76 46-57-80
Vertical 9 17 25 31 34 38 41 43 45
Airflow, cfm/ft. 40 79 119 158 198 238 277 317 356
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
F
6-Slot NC (Noise Criteria) - 12 21 28 33 38 42 45 48
Horizontal 5-10-20 13-20-40 20-30-51 27-40-59 33-46-66 40-51-72 45-55-78 48-59-83 51-62-88
Vertical 9 19 28 34 38 41 45 48 51
Airflow, cfm/ft. 46 92 139 185 231 277 323 370 416
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
7-Slot NC (Noise Criteria) - 12 22 29 34 38 42 45 48
Horizontal 6-11-22 14-22-43 22-32-55 29-43-63 36-50-71 43-55-78 48-59-84 52-63-90 55-67-95
Vertical 10 20 30 36 41 45 48 52 55
Airflow, cfm/ft. 53 106 158 211 264 317 370 422 475
Static Pressure 0.004 0.014 0.032 0.057 0.089 0.128 0.174 0.228 0.288
8-Slot NC (Noise Criteria) - 13 23 29 35 39 43 46 49
Horizontal 8-12-23 15-23-46 23-35-59 31-46-68 38-54-76 46-59-83 52-63-90 55-68-96 59-72-102
Vertical 11 22 32 39 43 48 52 55 58
NC corrections for various diffuser lengths Throw correction multiplier for length
Length 2 4 6 8 10 Length 2 4 8 10
Supply -3 0 +2 +3 +5 Throw Correction 0.72 1.0 1.5 1.7
Return 0 +3 +5 +6 +8
PERFORMANCE DATA
• Data obtained from tests conducted in accordance with ANSI/ • Each NC value represents the noise criteria curve which will not be
ASHRAE Standard 70-2006. Actual performance, with flexible duct exceeded by the sound pressure in any of the octave bands, 2nd
inlet, may vary in the field. See the engineering section of this through 7th, with a room absorption of 10 dB, re 10-12 watts
catalog for additional information. • For vertical throw, deduct 11 NC
• Horizontal throw values given are for terminal velocities of 150, 100 • Dash (-) in space denotes an NC value of less than 10
and 50 fpm • NC is based on 4-foot lengths; for other lengths use the NC
• Throw values given are for isothermal conditions, and are based on correction table
4-foot active section. For other lengths, see the Throw Correction • Throws listed are for the 1-way pattern. For divided airflow, select
Table. the airflow in each direction according to the number of slots aimed
• Pressure is given in inches of WG for ML only in that direction, with the total airflow apportioned between slots.
• Vertical throw values are given for terminal velocities of 50 fpm For an explanation of catalog throw data, see the Engineering
• For divided throw, use the cfm-per-foot value for the number of Guidelines section of the catalog.
slots in each direction. For sound, use the NC values for cfm-per- • Data obtained using plenums with duct velocities less than 800
foot for the total number of slots. fpm. See model MP (pages F34-F45) for data with Titus plenums.
• For continuous lengths it is recommended that maximum active
lengths are no longer than 10 feet
F26
PERFORMANCE DATA diffusers
RETURN PERFORMANCE DATA FOR PLENUM MLR-37
F
cfm per ft. 20 40 60 80 100 120 140 160
2
NC — 10 21 29 35 40 44 48
cfm per ft. 30 60 90 120 150 180 210 240
3
NC — 12 23 31 37 42 46 50
cfm per ft. 40 80 120 160 200 240 280 320
4
NC — 13 24 32 38 43 47 51
cfm per ft. 50 100 150 200 250 300 350 400
5
NC — 14 25 33 39 44 48 52
cfm per ft. 60 120 180 240 300 360 420 480
6
NC — 15 26 34 40 45 49 53
cfm per ft. 70 140 210 280 350 420 490 560
7
NC — 16 27 35 41 46 50 54
cfm per ft. 80 160 240 320 400 480 560 640
8
NC — 16 27 35 41 46 50 54
MLR-39
No. of PERFORMANCE DATA
Negative SP 0.018 0.040 0.070 0.108 0.160 0.215 0.280 0.450
Slots
cfm per ft. 20 30 40 50 60 70 80 100
1
NC — 11 19 25 30 34 38 44
cfm per ft. 40 60 80 100 120 140 160 200
2
NC — 14 22 28 33 37 41 47
cfm per ft. 60 90 120 150 180 210 240 300
3
NC — 16 24 30 35 39 43 49
cfm per ft. 80 120 160 200 240 280 320 400
4
NC — 17 25 31 36 40 44 50
cfm per ft. 100 150 200 250 300 350 400 500
5
NC — 18 26 32 37 41 45 51
cfm per ft. 120 180 240 300 360 420 480 600
6
NC — 19 27 33 38 42 46 52
cfm per ft. 140 210 280 350 420 490 560 700
7
NC — 20 28 34 39 43 47 53
cfm per ft. 160 240 320 400 480 560 640 800
8
NC — 20 28 34 39 43 47 53
F27