Grundfosliterature 6206216
Grundfosliterature 6206216
Grundfosliterature 6206216
CUE
Installation and operating instructions
English (US) Installation and operating instructions
English (US)
2
2. General information 2.3 References
English (US)
Technical documentation for Grundfos CUE:
2.1 Hazard statements
• The manual contains all information required for putting CUE
The symbols and hazard statements below may appear in into operation.
Grundfos installation and operating instructions, safety
• The data booklet contains all technical information about the
instructions and service instructions.
construction and applications of CUE.
• The service instructions contain all required instructions for
DANGER
dismantling and repairing the frequency converter.
Indicates a hazardous situation which, if not avoided,
Technical documentation is available on Grundfos Product Center
will result in death or serious personal injury.
at www.grundfos.com.
If you have any questions, please contact the nearest Grundfos
WARNING company or service workshop.
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury. 3. Product introduction
3.1 Product description
CAUTION CUE is a series of external frequency converters especially
Indicates a hazardous situation which, if not avoided, designed for pumps.
could result in minor or moderate personal injury. With the startup guide in CUE, the installer can quickly set central
parameters and put CUE into operation.
The hazard statements are structured in the following way:
Connected to a sensor or an external control signal, CUE will
SIGNAL WORD quickly adapt the pump speed to the actual demand.
Description of hazard The operating panel displays any alarms or warnings.
Consequence of ignoring the warning.
- Action to avoid the hazard.
If the pump speed exceeds the rated speed, the
2.2 Notes pump will be overloaded.
The symbols and notes below may appear in Grundfos
installation and operating instructions, safety instructions and 3.2 Intended use
service instructions.
CUE frequency converters can be used in both new and existing
installations. Local operation is performed via the operating panel
Observe these instructions for explosion-proof which has a graphic display showing the menu structure. The
products. menu structure uses the same system as Grundfos E-pumps.
Remote operation is performed via external signals, for instance
via digital inputs or GENIbus.
3
3.4 Identification 4.1 Transporting the product
English (US)
3.4.1 Nameplate To prevent damage during the transport, CUE must only be
unpacked at the installation site.
CUE can be identified by means of the nameplate. An example is
shown below. 4.2 Inspecting the product
Check on receipt that the packaging is intact and the unit is
complete. In case of damage during transport, contact the
transport company to complain.
Note that CUE is delivered in packaging which is not suitable for
T/C: CUE202P1M2T5E20H1BXCXXXSXXXXAXBXCXXXXDX outdoor storage.
Prod. no: 12345678 S/N: 123456G234
1.5 kW (400V)
IN: 3x380-500 V 50/60Hz 3.7A
4.3 Scope of delivery
OUT: 3x0-Vin 0-100Hz 4.1 A 2.8 kVA The packaging contains one or more accessory bags,
CHASSIS/IP20 Tamb. 45C/122F
documentation and the unit itself. See fig. 2.
IIIIIIIIIIIBAR CODEIIIIIIIIIII MADE IN DENMARK
CAUTION:
SEE MANUAL / VOIR MANUEL
WARNING:
Text Description
CAUTION
Heavy lifting
Minor or moderate personal injury
- Use proper lifting equipment when handling the
product.
- Follow local regulations.
4
5. Installation requirements The general safety necessitates special considerations as to
English (US)
these aspects:
• fuses and switches for overcurrent and short-circuit protection
Any installation, maintenance and inspection must be • selection of cables (mains current, motor, load distribution and
carried out by trained persons. relay)
• net configuration (IT, TN, earthing)
• safety on connecting inputs and outputs (PELV).
WARNING
Sharp element 5.1 IT mains
Death or serious personal injury
- Use safety knives and protective gloves when Do not connect 380-500 V CUE frequency converters
unpacking the product. to mains supplies with a voltage between phase and
protective earth of more than 440 V.
WARNING
Heavy lifting In connection with IT mains and earthed delta mains, the mains
Death or serious personal injury voltage may exceed 440 V between phase and protective earth.
- Use proper lifting equipment when handling the
product. 5.2 Aggressive environment
- Follow local regulations.
CUE must not be installed in an environment where
WARNING
the air contains liquids, particles or gases which may
Electric shock affect and damage the electronic components.
Death or serious personal injury
- Before starting any work on the product, make CUE contains a large number of mechanical and electronic
sure that the power supply has been switched off components. They are all vulnerable to environmental impact.
at least for as long as stated below and that it
cannot be accidentally switched on. 5.3 Reduced performance under certain conditions
- Touching the electrical parts may be fatal, even CUE reduces its performance under these conditions:
after CUE has been switched off. • low air pressure (at high altitude)
• long motor cables.
Voltage Min. waiting time
The required measures are described in the next two sections.
4 minutes 15 minutes 20 minutes
5.3.1 Reduction at low air pressure
0.75 - 3.7 kW 5.5 - 45 kW
200-240 V
(1-5 hp) (7.5 - 60 hp)
0.55 - 7.5 kW 11-90 kW 110-250 kW At altitudes above 2000 m (6600 ft), the PELV
380-500 V
(0.75 - 10 hp) (15-125 hp) (150-350 hp) requirements cannot be met.
0.75 - 7.5 kW
525-600 V
(1-10 hp) PELV = Protective Extra Low Voltage.
11-250 kW At low air pressure, the cooling capacity of air is reduced, and
525-690 V
(15-350 hp) CUE automatically reduces the performance to prevent overload.
It may be necessary to select a CUE unit with a higher
Only wait for a shorter period of time if stated on the nameplate of
performance.
the product in question.
5.3.2 Reduction in connection with long motor cables
Safety regulations
• The OFF button of the operating panel does not disconnect The maximum cable length is 300 m (1000 ft) for unscreened and
CUE from the power supply and must therefore not be used as 150 m (500 ft) for screened cables. In case of longer cables,
a safety switch. contact Grundfos.
• CUE must be earthed correctly and protected against indirect CUE is designed for a motor cable with a maximum cross-section
contact according to local regulations. as stated in section 13.3.4 Non-UL fuses and conductor cross-
section to mains and motor, for installations outside North
• The leakage current to protective earth exceeds 3.5 mA.
America and 13.3.5 UL fuses and conductor cross-section to
• Enclosure class IP20/21 must not be installed freely mains and motor, for installations in North America.
accessible, but only in a panel.
• Enclosure class IP54/55 must not be installed outdoors
without additional protection against weather conditions and
the sun.
• The STO function does not disconnect CUE from the power
supply and must therefore not be used as a safety switch.
• The STO function does not prevent unwanted movement from
external forces on the motor, for example, back pressure, and
the motor shaft must be covered.
Always observe local regulations concerning cable cross-section,
short-circuit protection and overcurrent protection.
5
6. Mechanical installation 6.3 Mounting
English (US)
WARNING
TM03 8859 2607
Crushing of feet
Death or serious personal injury
- CUE is very heavy and may fall if the pedestal is
not anchored to the floor.
6
7. Electrical connection
English (US)
WARNING
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off
and that it cannot be accidentally switched on. See
5. Installation requirements.
1 - Touching the electrical parts may be fatal, even
after CUE has been switched off.
ELCB
7
7.1.2 Protection against short circuit, fuses • Avoid unscreened motor and signal cables in electrical
English (US)
CUE and the supply system must be protected against short cabinets with frequency converters.
circuit. • Make the motor cable as short as possible in applications
Grundfos requires that the backup fuses mentioned in section without output filter to limit the noise level and minimise
13.3.3 Cable cross-section to signal terminals are used for leakage currents.
protection against short circuit. • Screws for frame connections must always be tightened
CUE offers complete short-circuit protection in case of a short whether a cable is connected or not.
circuit on the motor output. • Keep mains cables, motor cables and signal cables separated
in the installation if possible.
7.1.3 Additional protection
Other installation methods may give similar EMC results if the
WARNING above guidelines for good practice are followed.
Electric shock
Death or serious personal injury
- The leakage current to protective earth exceeds
3.5 mA.
8
7.3 RFI filters 7.3.1 Output filters
English (US)
To meet the EMC requirements, CUE comes with the following Output filters are used for reducing the voltage stress on the
types of built-in radio-frequency interference filter (RFI). motor windings and the stress on the motor insulation system as
well as for decreasing acoustic noise from the frequency
Voltage Typical shaft power P2 converter-driven motor.
RFI filter type
[V] [kW (hp)] Two types of output filters are available as accessories for CUE:
1.1 - 7.5 • dU/dt filters
1 x 200-240* C1
(1.5 - 10 hp) • sine-wave filters.
0.75 - 45 Use of output filters
3 x 200-240 C1
(1-60 hp) The table below shows when we recommend an output filter and
0.55 - 90 the type to use. The selection depends on the following:
3 x 380-500 C1
(0.75 - 125 hp) • pump type
110-250 • motor cable length
3 x 380-500 C3
(150-350 hp) • the required reduction of the acoustic noise from the motor.
0.75 - 7.5
3 x 525-600 C3
(1-10 hp)
11-250
3 x 525-690 C3
(15-350 hp)
SP, BM, BMB with motor voltage from 380 V and up - 0-300 m* (0-984 ft)
Pumps with Grundfos motor ML71 and ML80 up to and including 1.5 kW (2 hp) - 0-300 m* (0-984 ft)
Applications with desired reduction of dU/dt and noise emission, low reduction 0-150 m* -
Applications with desired reduction of dU/dt, voltage peaks and noise emission,
- 0-300 m* (0-984 ft)
high reduction
Applications with motors of 500 V and up - 0-300 m* (0-984 ft)
* The lengths stated apply to the motor cable.
9
7.4 Motor cable 7.5 Mains and motor connection
English (US)
Terminal Function
Fig. 15 Submersible pump with connection box and screened 91 (L1)
cable. Frequency converter and filter installed far away
from the well and connection box installed close to the 92 (L2) Three-phase mains supply
well 93 (L3)
95/99 (PE) Protective earth connection
Symbol Designation 96 (U)
Three-phase motor connection, 0-100 % of
1 CUE 97 (V)
mains voltage
2 Filter 98 (W)
3 Connection box
4 Standard motor
For single-phase connection, use L1 and L2.
5 Submersible motor
One line Unscreened cable
Double line Screened cable
10
7.5.3 Mains connection, enclosures A2 and A3 3. Fix the mains cable to the mounting plate.
English (US)
Check that the mains voltage and frequency
correspond to the values on the nameplate of CUE
and the motor.
11
7.5.5 Mains connection, enclosures A4 and A5 7.5.7 Mains connection, enclosures B1 and B2
English (US)
12
7.5.9 Mains connection, enclosures B3 and B4 7.5.11 Mains connection, enclosures C1 and C2
English (US)
Torque Nm [ft (lb)] Torque Nm [ft (lb)]
Enclosure Protective Enclosure Protective
Mains Motor Relay Mains Motor Relay
earth earth
B3 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4) C1 10 (7.4) 10 (7.4) 3 (2.2) 0.6 (0.4)
B4 4.5 (3.3) 4.5 (3.3) 3 (2.2) 0.6 (0.4) 141)/242) 141)/242)
C2 3 (2.2) 0.6 (0.4)
(10.3 /17.7 ) (10.31)/17.72))
1) 2)
1. Connect the earth conductor to terminal 95 (PE). See figs 25
1)
and 26. Conductor cross-section ≤ 95 mm2 ( ≤ 4/0 AWG)
2. Connect the mains conductors to terminals 91 (L1), 92 (L2), 2)
Conductor cross-section ≥ 95 mm2 ( ≥ 4/0 AWG).
93 (L3).
1. Connect the earth conductor to terminal 95 (PE). See fig. 27.
3. Fix the mains cable with a cable clamp.
2. Connect the mains conductors to terminals 91 (L1), 92 (L2),
7.5.10 Motor connection, enclosures B3 and B4 93 (L3).
1. Connect the earth conductor to terminal 99 (PE). See figs 25 7.5.12 Motor connection, enclosures C1 and C2
and 26.
1. Connect the earth conductor to terminal 99 (PE). See fig. 27.
2. Connect the motor conductors to terminals 96 (U), 97 (V), 98
2. Connect the motor conductors to terminals 96 (U), 97 (V), 98
(W).
(W).
3. Fix the screened cable with a cable clamp.
3. Fix the screened cable with a cable clamp.
2
TM03 9446 4007
93 (L3).
3. Fix the mains cable with a cable clamp.
13
7.5.14 Motor connection, enclosures C3 and C4 7.5.16 Mains connection, enclosures D1h and D2h
English (US)
Fig. 31 Earth, mains and motor connection for D1h and D2h
14
7.6 STO installation, optional
English (US)
Pos. Description
DANGER 1 Reset button
Exposure to high pressure or toxic liquids
2 Safety relay (category 3, PL d or SIL2)
Death or serious personal injury
- Failure to remove the jumper will disable the STO 3 Emergency stop button
function and the motor might not stop as intended Short-circuit protected cable if the product is not
4
and can cause severe injury or death. installed inside an IP54 cabinet.
- Failure to use safety-monitoring relay compliant
7.6.1 Restart behavior after STO activation
with Category 3 /PL "d", ISO 13849-1 or SIL 2, EN
62061 and IEC 61508. Perform a functional test By default the STO function is set to unintended-restart
every 12 months to ensure that the system works prevention behavior. To terminate STO and resume normal
properly. operation with manual reset, do the following:
To enable the integrated STO, follow these steps: • Reapply 24 V DC supply to terminal 37.
1. Remove the jumper wire between control terminals 37 and 12 • Send a reset signal via bus, Digital I/O or the reset button.
or 13. Cutting or breaking the jumper is not sufficient to avoid • Set the STO function to automatic restart by changing the
short-circuiting. value of 5-19 terminal 37 "Safe Stop" from default value 1,
"Safe Stop Alarm" to value 3, "Safe Stop Warning".
Automatic restart means that STO is terminated, and normal
operation is resumed, as soon as the 24 V DC is applied to
12/13 terminal 37. No reset signal is required.
7.6.2 Restart settings
• Remove the 24 V DC voltage supply to terminal 37 using the
interrupt device while the frequency converter drives the
motor, that is the mains supply is not interrupted.
37
• Check that the motor coasts and that the alarm Safe Stop
TM07 4595 1919
2. Connect an external safety-monitoring relay via a NO safety 7.7 Connecting the signal terminals
function to terminal 37 (STO) and either terminal 12 or 13, 24
V DC.
As a precaution, signal cables must be separated
Select and apply the components in the safety control system from other groups by reinforced insulation in their
appropriately to achieve the desired level of operational safety. entire lengths.
Before integrating and using STO in an installation, carry out a
thorough risk analysis on the installation to determine whether the Connect the signal cables according to the guidelines for good
STO functionality and safety levels are appropriate and sufficient. practice to ensure EMC-correct installation. See section
7.6.1 Restart behavior after STO activation.
FC
• Use screened signal cables with a conductor cross-section of
1
minimum 0.5 mm2 and maximum 1.5 mm2.
• Use a 3-conductor screened bus cable in new systems.
12
2
TM07 4594 1919
37
4 3
Fig. 33 STO wiring
15
7.7.1 Wiring diagram, signal terminals
English (US)
0/4-20 mA Terminals
0-10 V Terminals External setpoint,
External setpoint, current input
voltage input
U: 0-10 V
U: 0-10 V I: 0/4-20 mA
I: 0/4-20 mA
Ext. setpoint
GND
AO 1
+10 V out
Sensor 1
GND
RS-485 GND Y
RS-485 A
RS-485 B
GND
DI 4 Ext. setpoint
Sensor 1
RS-485 GND Y
1
+10 V out
GND
RS-485 A
RS-485 B
AO
+24 V out
+24 V out
Safe stop
+24 V out
+24 V out
Safe stop
DI/O 1
DI/O 2
DI/O 1
DI/O 2
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 1
DI 2
DI 3
U: 0-10 V U: 0-10 V
I: 0/4-20 mA I: 0/4-20 mA
61 68 69
61 68 69 39 42 50 53 54 55
Ext. setpoint
GND
AO 1
+10 V out
Sensor 1
GND
RS-485 GND Y
RS-485 A
RS-485 B
RS-485 GND Y
GND
Ext. setpoint
Sensor
+10 V out
GND
RS-485 A
RS-485 B
AO 1
+24 V out
+24 V out
Safe stop
+24 V out
+24 V out
Safe stop
DI/O 1
DI/O 2
DI/O 1
DI/O 2
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 1
DI 2
DI 3
DI 4
12 13 18 19 27 29 32 33 20 37
16
7.7.2 Connection of a thermistor (PTC) to CUE
English (US)
The connection of a thermistor (PTC) in a motor to CUE requires
an external PTC relay.
The requirement is based on the fact that the thermistor in the
motor only has one layer of insulation to the windings. The
terminals in CUE require two layers of insulation since they are
part of a PELV circuit.
A PELV circuit provides protection against electric shock. Special
connection requirements apply to this type of circuit. The
requirements are described in EN 61800-5-1.
In order to maintain PELV, all connections made to the control
terminals must be PELV. For example, the thermistor must have
reinforced or double insulation.
Access to signal terminals
All signal terminals are behind the terminal cover of the CUE
front. Remove the terminal cover as shown in figs 34 and 35.
Fig. 35 Access to signal terminals, A4, A5, B1, B2, B3, B4, C1,
C2, C3 and C4
17
Fitting the conductor RS-485 GENIbus network connection
English (US)
1. Remove the insulation at a length of 9 to 10 mm. One or more CUE units can be connected to a control unit via
2. Insert a screwdriver with a tip of maximum 0.4 x 2.5 mm into GENIbus.
the square hole. The reference potential, GND, for RS-485 (Y) communication
3. Insert the conductor into the corresponding round hole. must be connected to terminal 61.
Remove the screwdriver. The conductor is now fixed in the If more than one CUE unit is connected to a GENIbus network,
terminal. the termination contact of the last CUE must be set to "ON"
(termination of the RS-485 port).
The factory setting of the termination contact is "OFF" (not
terminated).
Remove the operating panel to set the contact. See fig. 40.
NO 1
NO 2
NC 1
C1
NC 2
C2
Terminal Function
C1 C2 Common
NO 1 NO 2 Normally open contact
NC 1 NC 2 Normally closed contact
18
7.8.1 Access to signal relays
English (US)
The relay outputs are positioned as shown in figs 42 to 47.
19
7.8.2 Connecting the MCB 114 sensor input module 7.8.3 Fitting MCB 114 in CUE
English (US)
The MCB 114 is an option offering additional analog inputs for Enclosures A2, A3 and B3
CUE. 1. Switch off the power to CUE. See section 7.5 Mains and
Configuration of MCB 114 motor connection.
MCB 114 is equipped with three analog inputs for the following 2. Remove the operating panel, the terminal cover and the frame
sensors: from CUE. See fig. 49.
• One additional sensor 0/4-20 mA. 3. Fit MCB 114 into port B.
• Two Pt100/Pt1000 temperature sensors for measurement of 4. Connect the signal cables, and fasten the cables with the
motor bearing temperature or an alternative temperature, such enclosed cable strips.
as liquid temperature. 5. Remove the knock-out plate in the extended frame so that
When MCB 114 has been installed, CUE automatically detects if MCB 114 fits under the extended frame.
the sensor is Pt100 or Pt1000 when it is switched on. 6. Fit the extended frame and the terminal cover.
Wiring diagram, MCB 114 7. Fit the operating panel in the extended frame.
8. Connect power to CUE.
TEMP
WIRE
GND
GND
GND
VDO
I IN
1 1 1
1 2 3 4 5 6 7 8 9
0 1 2
Port B
20
Enclosures A5, B1, B2, B4, C1, C2, C3, C4, D1 and D2 8. Starting up the product
English (US)
1. Switch off the power to CUE. See section 7.5 Mains and
motor connection.
2. Remove the operating panel and the cradle from CUE. See Any installation, maintenance and inspection must be
fig. 50. carried out by trained persons.
3. Fit MCB 114 into port B.
4. Connect the signal cables, and fasten the cables with the Before you switch on the power supply, you must do the following:
enclosed cable strips. See fig. 50. • Close the cover.
5. Fit the cradle and the operating panel. • Ensure that all cable glands are tightened properly.
6. Connect power to CUE. • Ensure that there is no voltage on output terminals, phase-to-
phase and phase-to-ground.
Cradle • Confirm continuity of the motor by measuring Ω values on U-V,
V-W and W-U.
• Check for proper grounding of the frequency converter and the
CUE
motor.
• Check that there are no loose connections on the terminals.
• Confirm that the supply voltage matches the voltage of the
Port B frequency converter and the motor.
21
9. Control functions
English (US)
17
[Favorites]: allows access to
4 programming parameters for initial set-
5 17
up instructions and many detailed
16 application instructions.
On
6
15
Warn. 18 [Status]: shows operational information.
7
TM07 4597 2119
14 Alarm
13 19 Frequency
Hand Auto Reset
Off
on on
8 20 Motor current
12 11 10 9 21 Speed, RPM
Fig. 51 Operating panel
22
9.2 Menu overview 9.3 Operating modes
English (US)
Overview of the main menus. The ** represents a number to a The following operating modes are set on the operating panel
submenu. using the [Favorites] menu.
• "0-** Operation / Display"
Operating mode Description
• "1-** Load and Motor"
• "2-** Brakes" The pump is running in the operating mode
Normal
• "3-** Reference / Ramps" selected
• "4-** Limits / Warnings" The pump has been stopped, and the green
Stop
indicator light is flashing
• "5-** Digital In/Out"
• "6-** Analog In/Out" Min. The pump is running at minimum speed
• "8-** Comm. and Options" Max. The pump is running at maximum speed
• "14-** Special Functions" User curve The pump is running at user-defined speed
• "15-** Drive Information"
• "16-** Data Readouts"
• "18-** Info & Readouts" Max.
• "20-** Drive Closed Loop" Minimum and maximum curves.
23
9.4.2 Controlled operation (closed loop)
English (US)
Constant
Proportional temperature.
CUE
differential The liquid
pressure is kept
Δp constant,
independently of
the flow rate.
Constant pressure.
CUE The pressure is
TM03 8476 1607
kept constant,
p independently of
the flow rate.
Constant pressure
with stop function.
CUE The outlet pressure
TM03 8477 1607
is kept constant at
p high flow rate. On/
off operation at low
flow rate.
Constant level.
CUE
The liquid level is
TM03 8482 1607
L kept constant,
independently of
the flow rate.
L kept constant at
high flow rate.
On/off operation at
low flow rate.
kept constant,
Q independently of
the head.
24
10. Setting the product 10.4 Checking the motor rotation
English (US)
To make a correct programming, it is often necessary to make
There is a risk of damage to the pumps or the
settings in several submenus. The programmed data is saved
compressors if the motor is running in the wrong
internally in the frequency converter.
direction. Before starting the frequency converter,
It is possible to make a backup of the data by uploading the data check the motor rotation.
to the operating panel’s memory.
1. Navigate to "1-28 Motor Rotation Check", and press [OK].
The menus are accessed or changed from [Main Menu] or
[Favorites] on the operating panel. However, not all menus are 2. Scroll to "[1] Enable".
available in [Favorites]. The following text appears: "Note! Motor may run in wrong
All settings that have been made are visible in [Favorites] > "Q5 - direction".
Changes Made". 3. Press [OK].
See 9.1 Operating panel and 9.2 Menu overview. 4. Follow the on-screen instructions.
To change the direction of rotation, remove power to the
10.1 First-time setup via the startup guide frequency converter and wait before touching the product. See
The startup guide starts automatically the first time the product is waiting time in section 5. Installation requirements.
switched on or after startup of the frequency converter. The guide • Reverse the connection of any 2 of the 3 motor wires on the
enables quick configuration of basic pump- and application motor or frequency-converter side of the connection.
parameters.
1. Follow the on-screen instructions to complete the 10.5 Permanent-magnet motor setup
commissioning of the frequency converter. Some data from
To set a permanent-magnet motor manually in [Main menu], enter
the motor nameplate is needed.
the motor data available on the motor nameplate.
1. Activate PM motor operation "1-10 Motor Construction", select
Reactivate the start-up guide by pressing [Favorites] "[1] PM, non salient SPM."
> "Q4" - "Run start-up guide". 2. Set "0-02 Motor Speed Unit" to "[0] RPM".
Programme the following parameters in the listed order:
1. "1-24 Motor Current"
10.2 Uploading or downloading of data
2. "1-26 Motor Cont. Rated Torque"
It is possible to download stored data to another frequency
3. "1-25 Motor Nominal Speed"
converter.
4. "1-39 Motor Poles"
2. Navigate to "0-5* Copy/Save", and press [OK].
5. "1-30 Stator Resistance (Rs)". Enter line to common stator
3. Press [OK] to activate "0-50 LCP Copy".
winding resistance (Rs). If only line-line data is available,
4. Press [Up] to select "[1] All to LCP" to upload data to the divide the line-line value by 2 to achieve the line-common
operating panel, or (starpoint) value.
5. select "[2] All from LCP" to download data from the operating 6. "1-37 d-axis Inductance (Ld)". Enter line to common direct
panel. axis inductance of the PM motor. If only line-line data is
6. Press [OK]. A progress bar shows the uploading or available, divide the line-line value by 2 to achieve the line-
downloading progress. common (starpoint) value.
7. "1-40 Back EMF at 1000 RPM". Enter line-to-line back EMF of
10.3 Asynchronous motor setup
the PM motor at 1000 RPM mechanical speed (RMS value).
To set an asynchronous motor manually in [Main menu], enter the Back EMF is the voltage generated by a PM motor when no
following motor data available on the motor nameplate. frequency converter is connected and the shaft is turned
• "1-20 Motor Power [kW]" or "1-21 Motor Power [HP]" externally. Back EMF is normally specified for nominal motor
• "1-22 Motor Voltage" speed or for 1000 RPM measured between 2 lines. If the
• "1-23 Motor Frequency" value is not available for a motor speed of 1000 RPM,
calculate the correct value as follows: If back EMF is for
• "1-24 Motor Current"
example 320 V at 1800 RPM, it can be calculated at 1000
• "1-25 Motor Nominal Speed" RPM as follows: Back EMF = (Voltage / RPM)*1000 = (320/
• "1-29 Automatic Motor Adaptation (AMA)". 1800)*1000 = 178. This is the value that must be programmed
for "1-40 Back EMF at 1000 RPM".
10.5.1 Test motor operation
1. Start the motor at low speed (100-200 RPM). If the motor does
not turn, check the installation, general programming, and
motor data to ensure that it is correct.
2. Check if the start function in "1-70 PM Start Mode" fits the
application requirements.
25
10.6 Synchronous reluctance motor setup 1. Navigate to "14-** Special Functions", and press [OK].
English (US)
To set a synchronous reluctance motor manually in [Main menu], 2. Select "14-22 Operation Mode", and press [OK].
enter the following motor data available on the motor nameplate: 3. Use [Up] and [Down] to navigate to "[2] Initialization", and
• "1-10 Motor Construction" press [OK].
• "1-23 Motor Frequency" 4. Switch off the power to the unit, and wait for the display to
switch off.
• "1-24 Motor Current"
5. Reconnect the power.
• "1-25 Motor Nominal Speed"
6. Alarm 80, "Drive initialized to default value", is displayed.
• "1-26 Motor Cont. Rated Torque"
7. Press [Reset] to return to operating mode.
• "1-29 Automatic Motor Adaptation (AMA)".
10.10.2 Manual reset
10.7 Automatic Energy Optimization (AEO)
You can also manually reset to default settings, but this deletes
all motor-, programming-, localization-, and monitoring data. It will
not reset settings for "15-00 Operating hours", "15-03 Power
AEO is not relevant for permanent-magnet motors. Up’s", "15-04 Over Temp’s" and "15-05 Over Volt’s".
1. Switch off the power to the unit, and wait for the display to
switch off.
AEO is a procedure which minimizes voltage to the motor,
2. Press and hold [Status], [Main Menu] and [OK] at the same
thereby reducing energy consumption, heat, and noise.
time while switching on the power to the unit. It takes
To activate AEO, set "1-03 Torque Characteristics" to "[2] Auto approximately 5 seconds or until you hear an audible click and
Energy Optim. CT" or "[3] Auto Energy Optim. VT". the fan starts.
10.8 Local-control test
11. Servicing the product
1. Press [Hand On] to provide a local start command to the
frequency converter. CAUTION
2. Accelerate the frequency converter to full speed by pressing Electric shock
[Up]. Moving the cursor left of the decimal point provides
Minor or moderate personal injury
quicker input changes.
- Before starting any work on the product, make
3. Note any acceleration problems. sure that the power supply has been switched off
4. Press [Off]. Note any deceleration problems. and that it cannot be accidentally switched on. See
5. Installation requirements
10.9 System startup - Touching the electrical parts may be fatal, even
The below steps require wiring and application programming to after CUE has been switched off.
be completed. We recommend that you follow this procedure Conduct a functional test every 12 months to detect any failure or
after application setup is completed. malfunction of the STO functionality.
1. Press [Auto On]. To conduct the functional test, perform the following steps:
2. Apply an external run command. • Remove the 24 V DC voltage supply at terminal 37.
3. Adjust the speed reference throughout the speed range. • Check if the operating panel displays the alarm "Safe Stop
4. Remove the external run command. A68"
5. Check the sound and vibration levels of the motor to ensure • Verify that the frequency converter trips the unit.
that the system is working as intended. If warnings or alarms • Verify that the motor is coasting and comes to a complete
occur, see 12.1 Overview of warnings and alarms or refer to stop.
the service instructions for the frequency converter.
• Verify that the motor cannot be started.
10.10 Resetting to default settings • Reconnect the 24 V DC voltage supply to terminal 37.
• Verify that the motor is not started automatically and restarts
only by giving a reset signal (via bus, Digital I/O, or the [Reset]
You can make a backup of the changed settings first button).
by uploading them to the operating panel.
26
12. Fault finding the product
English (US)
12.1 Overview of warnings and alarms
Alarm, trip
Number Description Warning Alarm
lock
1 10 V low ● - -
2 Live zero error (●) (●) -
3 No motor (●) - -
4 Mains phase loss (●) (●) (●)
5 DC voltage high ● - -
6 DC voltage low ● - -
7 DC overvoltage ● ● -
8 DC undervoltage ● ● -
9 Inverter overloaded ● ● -
10 Motor overtemperature (●) (●) -
11 Motor thermistor overtemperature (●) (●) -
12 Torque limit ● ● -
13 Overcurrent ● ● ●
14 Protective earth fault - ● ●
15 Hardware mismatch - ● ●
16 Short circuit - ● ●
17 Control word timeout (●) (●) -
18 Start failed - ● -
21 Parameter error ● ● -
23 Internal fan fault ● - -
24 External fan fault ● - -
25 Brake resistor short circuit ● - -
26 Brake resistor power limit (●) (●) -
27 Brake chopper fault ● ● -
28 Brake check failed (●) (●) -
29 Heat sink temperature ● ● ●
30 Motor phase U missing (●) (●) (●)
31 Motor phase V missing (●) (●) (●)
32 Motor phase W missing (●) (●) (●)
33 Inrush fault - ● ●
34 Fieldbus communication fault ● ● -
35 Option fault (●) - -
36 Mains failure ● ● -
38 Internal fault - ● ●
39 Heat sink sensor - ● ●
40 Overload of digital output terminal 27 (●) - -
41 Overload of digital output terminal 29 (●) - -
42 Overload X30/6 or X30/7 (●) - -
45 Protective earth fault 2 ● ● ●
46 Power card supply - ● ●
47 24 V supply low ● ● ●
48 1.8 V supply low - ● ●
49 Speed limit ● - -
27
English (US)
Alarm, trip
Number Description Warning Alarm
lock
50 AMA calibration failed - ● -
51 AMA check Unom and Inom - ● -
52 AMA low Inom - ● -
53 AMA motor too large - ● -
54 AMA motor too small - ● -
55 AMA parameter out of range - ● -
56 AMA interrupted by user - ● -
57 AMA timeout - ● -
58 AMA internal fault ● ● -
59 Current limit ● - -
60 External interlock ● ● -
61 Feedback error (●) (●) -
62 Output frequency at maximum limit ● - -
64 Voltage limit ● - -
65 Control card overtemperature ● ● ●
66 Heat sink temperature low ● - -
67 Option configuration has changed - ● -
68 Safe stop activated (●) ( ● )1 -
69 Power card temperature - ● ●
70 Illegal FC configuration - - ●
71 PTC 1 safe stop ● ● -
72 Dangerous failure ● ● ●
76 Power unit setup ● - -
77 Reduced power mode ● - -
79 Illegal power section configuration - ● -
80 Drive initialized to default value - ● -
81 CSIV corrupt - ● -
82 CSIV parameter error - ● -
90 Feedback monitor (●) (●) -
91 Analog input 54 wrong settings - - ●
92 No flow (●) (●) -
93 Dry pump (●) (●) -
94 End of curve (●) (●) -
95 Broken belt (●) (●) -
96 Start delayed (●) - -
97 Stop delayed (●) - -
98 Clock fault ● - -
99 Locked rotor - ● -
100 Derag limit fault - ● (●)
104 Mixing fan fault (●) (●) -
148 System temperature ● ● -
200 Fire mode (●) - -
201 Fire mode was active (●) - -
243 Brake IGBT ● ● -
244 Heat sink temperature ● ● ●
245 Heat sink sensor - ● ●
246 Power card supply - ● ●
247 Power card temperature - ● ●
248 Illegal power section configuration - ● ●
249 Temperature of the rectifier heat sink ● - -
250 New spare part - - ●
28
English (US)
Alarm, trip
Number Description Warning Alarm
lock
251 New type code - ● ●
274 The flow is not confirmed - ● -
275 Flow switch failure - ● -
2004 External fault - ● -
2007 Too high bearing temperature ● ●
2008 Too high bearing temperature ● ● -
2010 Setpoint signal outside range - ● -
2011 Sensor 1 is outside range - ● -
2012 Sensor 2 is outside range - ● -
2013 Temperature sensor 1 is outside range - ● -
2014 Temperature sensor 2 is outside range - ● -
2016 Limit 1 is exceeded ● ● -
2017 Limit 2 is exceeded ● ● -
( ● )This warning or alarm is programmable. Warnings and alarms depend on the parameter settings.
1 This warning or alarm cannot be auto reset via parameter selection.
29
13. Technical data
English (US)
13.1 Enclosure
The individual CUE cabinet sizes are characterized by their
enclosures. The table shows the relationship of enclosure class
and enclosure type.
Example:
Read from the nameplate:
• Supply voltage = 3 x 380-500 V.
• Typical shaft power = 1.5 kW (2 hp).
• Enclosure class = IP20.
The table shows that the CUE enclosure is A2.
[kW] [hp] IP20 IP21 IP55 IP20 IP55 IP20 IP55 IP20 IP55 IP21 IP55
0.55 0.75
0.75 1
1.1 1.5 A3 A5
A2 A4 A2 A4
1.5 2 A3 A5
2.2 3
B1 B1
3 4
A3 A5
3.7 5
4 5 A2 A4
5.5 7.5 B1 B1 A3 A5
A3 A5
7.5 10 B2 B2 B3 B1
11 15
15 20 B2 B3 B1
B4
18.5 25 B2 B2
22 30 C1
C3 B2
30 40 B4
37 50
C4 C2
45 60 C1
C3
55 75 C2 C2
75 100
C4 C2
90 125
30
13.2 Operating conditions 13.3.2 Cable requirements
English (US)
Relative humidity 5-95 % RH Maximum length, screened motor cable 150 m (500 ft)
Max. 50 °C Maximum length, unscreened motor cable 300 m (1000 ft)
Ambient temperature
(122 °F) Maximum length, signal cable 300 m (1000 ft)
Max. 45 °C
Average ambient temperature over 24 hours
(113 °F)
Minimum ambient temperature at full Always comply with local regulations as to cable
0 °C (32 °F) cross-sections.
operation
Minimum ambient temperature at reduced
-10 °C (14 °F)
operation 13.3.3 Cable cross-section to signal terminals
-25 to 65 °C
Temperature during storage and transport
(-13 to 149 °F) Maximum cable cross-section to signal terminals, 1.5 mm2
rigid conductor (14 AWG)
Storage duration Max. 6 months
Maximum cable cross-section to signal terminals, 1.0 mm2
Maximum altitude above sea level without flexible conductor (18 AWG)
1000 m (3280 ft)
performance reduction
0.5 mm2
Maximum altitude above sea level with Minimum cable cross-section to signal terminals
3000 m (9840 ft) (20 AWG)
performance reduction
31
13.3.4 Non-UL fuses and conductor cross-section to mains
English (US)
32
13.3.5 UL fuses and conductor cross-section to mains and motor, for installations in North America
English (US)
Fuse type Maximum
Typical shaft
conductor
power P2
Bussmann Bussmann Bussmann
SIBA RK1/ Littel Fuse
Ferraz-Shawmut cross-section 1
Bussmann RK1/SIBA Ferraz-Shawmut
RK1/E1958/ J/E4273 T/ T/E4274 H/ CC/Littel Fuse
E125085 E180276 RK1/E60314 JFHR2
[kW (hp)] JFHR2 JDDZ JDDZ E71611 JFHR2 [AWG] 2
JFHR2 RKI/JDDZ
1 x 200-240 V
1.1 (1.5) KTN-R20 - - - - - - 10
1.5 (2) KTN-R30 - - - - - - 7
2.2 (3) KTN-R40 - - - - - - 7
3 (4) KTN-R40 - - - - - - 7
3.7 (5) KTN-R60 - - - - - - 7
5.5 (7.5) - - - - - - - 7
7.5 (10) - - - - - - - 2
3 x 200-240 V
0.75 (1) KTN-R10 JKS-10 JJN-10 5017906-010 KTN-R10 ATM-R10 A2K-10R 10
1.1 (1.5) KTN-R20 JKS-20 JJN-20 5017906-020 KTN-R20 ATM-R20 A2K-20R 10
1.5 (2) KTN-R20 JKS-20 JJN-20 5017906-020 KTN-R20 ATM-R20 A2K-20R 10
2.2 (3) KTN-R20 JKS-20 JJN-20 5017906-020 KTN-R20 ATM-R20 A2K-20R 10
3 (4) KTN-R30 JKS-30 JJN-30 5012406-032 KTN-R30 ATM-R30 A2K-30R 10
3.7 (5) KTN-R30 JKS-30 JJN-30 5012406-032 KTN-R30 ATM-R30 A2K-30R 10
5.5 (7.5) KTN-R50 JKS-50 JJN-50 5012406-050 KLN-R50 - A2K-50R 7
7.5 (10) KTN-R50 JKS-60 JJN-60 5012406-050 KLN-R60 - A2K-50R 7
11 (15) KTN-R60 JKS-60 JJN-60 5014006-063 KLN-R60 A2K-60R A2K-60R 7
15 (20) KTN-R80 JKS-80 JJN-80 5014006-080 KLN-R80 A2K-80R A2K-80R 2
18.5 (25) KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R A2K-125R 1/0
22 (30) KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R A2K-125R 1/0
30 (40) FWX-150 - - 2028220-150 L25S-150 A25X-150 A25X-150 1/0
37 (50) FWX-200 - - 2028220-200 L25S-200 A25X-200 A25X-200 4/0
45 (60) FWX-250 - - 2028220-250 L25S-250 A25X-250 A25X-250 250 MCM
3 x 380-500 V
0.55 (0.75) KTS-R10 JKS-10 JJS-10 5017906-010 KTN-R10 ATM-R10 A2K-10R 10
0.75 (1) KTS-R10 JKS-10 JJS-10 5017906-010 KTN-R10 ATM-R10 A2K-10R 10
1.1 (1.5) KTS-R10 JKS-10 JJS-10 5017906-010 KTN-R10 ATM-R10 A2K-10R 10
1.5 (2) KTS-R10 JKS-10 JJS-10 5017906-010 KTN-R10 ATM-R10 A2K-10R 10
2.2 (3) KTS-R20 JKS-20 JJS-20 5017906-020 KTN-R20 ATM-R20 A2K-20R 10
3 (4) KTS-R20 JKS-20 JJS-20 5017906-020 KTN-R20 ATM-R20 A2K-20R 10
4 (5) KTS-R20 JKS-20 JJS-20 5017906-020 KTN-R20 ATM-R20 A2K-20R 10
5.5 (7.5) KTS-R30 JKS-30 JJS-30 5012406-032 KTN-R30 ATM-R30 A2K-30R 10
7.5 (10) KTS-R30 JKS-30 JJS-30 5012406-032 KTN-R30 ATM-R30 A2K-30R 10
11 (15) KTS-R40 JKS-40 JJS-40 5014006-040 KLS-R40 - A6K-40R 7
15 (20) KTS-R40 JKS-40 JJS-40 5014006-040 KLS-R40 - A6K-40R 7
18.5 (25) KTS-R50 JKS-50 JJS-50 5014006-050 KLS-R50 - A6K-50R 7
22 (30) KTS-R60 JKS-60 JJS-60 5014006-063 KLS-R60 - A6K-60R 2
30 (40) KTS-R80 JKS-80 JJS-80 2028220-100 KLS-R80 - A6K-80R 2
37 (50) KTS-R100 JKS-100 JJS-100 2028220-125 KLS-R100 - A6K-100R 1/0
45 (60) KTS-R125 JKS-150 JJS-150 2028220-125 KLS-R125 - A6K-125R 1/0
55 (75) KTS-R150 JKS-150 JJS-150 2028220-160 KLS-R150 - A6K-150R 1/0
75 (100) FWH-220 - - 2028220-200 L50S-225 - A50-P225 4/0
90 (125) FWH-250 - - 2028220-250 L50S-250 - A50-P250 250 MCM
110 (150) FWH-300 JJS-300 NOS-300 170M3017 2028220-38 L50S-300 A50-P300 2 x 2/0
132 (200) FWH-350 JJS-350 NOS-350 170M3018 2028220-38 L50S-350 A50-P350 2 x 2/0
160 (250) FWH-400 JJS-400 NOS-400 170M4012 206xx32-400 L50S-400 A50-P400 2 x 350 MCM
200 (300) FWH-500 JJS-500 NOS-500 170M4014 206xx32-500 L50S-500 A50-P500 2 x 350 MCM
250 (350) FWH-600 JJS-600 NOS-600 170M4016 206xx32-600 L50S-600 A50-P600 2 x 350 MCM
Bussmann SIBA Ferraz-Shawmut
- - - - E125085 E180276 - E76491 -
JFHR2 JFHR2 JFHR2
33
English (US)
34
13.4 Electrical data Analog inputs
English (US)
Mains supply (L1, L2, L3) Analog input 1, terminal number 53
Supply voltage 200-240 V ± 10 % Voltage signal A53 = "U" 1)
Supply voltage 380-500 V ± 10 % Voltage range 0-10 V
Supply voltage 525-600 V ± 10 % Input resistance, Ri Approx. 10 kΩ
Supply voltage 525-690 V ± 10 % Maximum voltage ± 20 V
Supply frequency 50/60 Hz Current signal A53 = "I" 1)
Maximum temporary imbalance between Current range 0-20, 4-20 mA
3 % of rated value
phases Input resistance, Ri Approx. 200 Ω
Leakage current to protective earth > 3.5 mA Maximum current 30 mA
Number of cut-ins, enclosure A Max. 2 times/min. Maximum fault, terminals 53, 54 0.5 % of full scale
Number of cut-ins, enclosures B and C Max. 1 time/min. Analog input 2, terminal number 54
Current signal A54 = "I" 1)
Current range 0-20, 4-20 mA
Do not use the power supply for switching CUE on
and off. Input resistance, Ri Approx. 200 Ω
Maximum current 30 mA
Motor output (U, V, W) Maximum fault, terminals 53, 54 0.5 % of full scale
1)
Output voltage 0-100 % 1) The factory setting is voltage signal "U".
Output frequency 0-590 Hz 2) All analog inputs are galvanically separated from the supply
voltage (PELV) and other high-voltage terminals.
Switching on output Not recommended
1)
Analog output
Output voltage in percentage of supply voltage.
2)
Depending on the pump family selected. Analog output 1, terminal number 42
Current range 0-20 mA
RS-485 GENIbus connection
Maximum load to frame 500 Ω
Terminal number 68 (A), 69 (B), 61 GND (Y) Maximum fault 0.8 % of full scale
The RS-485 circuit is functionally separated from other central The analog output is galvanically separated from the supply
circuits and galvanically separated from the supply voltage voltage (PELV) and other high-voltage terminals.
(PELV).
MCB 114 sensor input module
Digital inputs
Analog input 3, terminal number 2
Terminal number 18, 19, 32, 33
Current range 0/4-20 mA
Voltage level 0-24 VDC
Input resistance < 200 Ω
Voltage level, open contact > 19 VDC
Analog inputs 4 and 5, terminal number 4, 5 and 7, 8
Voltage level, closed contact < 14 VDC
Signal type, 2- or 3-wire Pt100/Pt1000
Maximum voltage on input 28 VDC
Input resistance, Ri Approx. 4 kΩ
C Common
NO Normally open
NC Normally closed
The relay contacts are galvanically separated from other circuits
by reinforced insulation (PELV).
35
13.5 Dimensions and weights
English (US)
B4, C3, C4
36
13.5.2 Enclosures D1h and D2h
English (US)
TM05 9331 3713
Fig. 54 Dimensions for enclosures D1h and D2h
Shipping dimensions
37
13.6 Miscellaneous data 14. Disposal
English (US)
38
USA Canada México
Grundfos companies
GRUNDFOS Chicago GRUNDFOS Canada GRUNDFOS México
3905 Enterprise Court 2941 Brighton Road Boulevard TLC No. 15
P.O. Box 6620 Oakville, Ontario L6H 6C9 Canada Parque Industrial Stiva Aeropuerto
Aurora, IL 60598-0620 Phone: +1-905 829 9533 C.P. 66600 Apodaca, N.L Mexico
Phone: +1-630-236-5500 Fax: +1-905 829 9512 Phone: +011-52-81-8144 4000
Fax: +1-630-236-5511 Fax: +011-52-81-8144 4010
www.grundfos.ca
GRUNDFOS Kansas City www.grundfos.mx
9300 Loiret Blvd.
Lenexa, Kansas 66219
Phone: +1-913-227-3400
Fax: +1-913-227-3500
www.grundfos.us
ECM: 1269700
99735239 0919
www.grundfos.com
www.grundfos.us
Trademarks displayed in this material, including but not limited to Grundfos, the Grundfos logo and “be think innovate” are registered trademarks owned by The Grundfos Group. All rights reserved. © 2019 Grundfos Holding A/S, all rights reserved.