Intelineo 6000 1.5.0 Global Guide
Intelineo 6000 1.5.0 Global Guide
Intelineo 6000 1.5.0 Global Guide
6000
Controller for parallel hybrid
microgrid applications
SW version 1.5.0
1 Document information 6
2 System overview 14
3 Applications overview 40
4 Installation and wiring 43
5 Controller setup 82
6 Grid Codes 299
7 Communication 311
8 Technical data 335
9 Appendix 337
4.4.10 CAN bus and RS485 wiring 71 5.4.18 Forced Value 158
5.2 Controller configuration and PC tools 5.4.28 Power Formats And Units 196
connection 112 5.4.29 Protections 197
5.2.1 USB 112 5.4.30 Pulse Counters 211
5.2.2 Ethernet 113 5.4.31 PV Inverter Slots 212
5.3 Default configuration 118 5.4.32 SD Card Storage 215
5.3.1 Binary inputs 118 5.4.33 Sensor Curves 216
5.3.2 Binary outputs 119 5.4.34 Service Timers 218
5.3.3 Analog inputs 119 5.4.35 Sunrise/Sunset 219
5.3.4 Analog Outputs 119 5.4.36 Sunspec 219
5.4 General Functions 119 5.4.37 System Start/Stop 219
5.4.1 3V3 Reference Voltage Measurement121 5.4.38 SW Key Features 219
5.4.2 Access lock 121 5.4.39 Universal Genset support 220
5.4.3 Alarm Management 122 5.4.40 User Buttons 224
5.4.4 AMF Function 125 5.4.41 User Management And Data Access
5.4.5 Breaker Control 126 Control 226
5.4.7 CAN Intercontroller Communication 132 5.4.43 Voltage Phase Sequence Detection 235
5.5.3 BESS Forced power 241 6.6.4 Overvoltage failure ride through -
OVRT 305
5.5.4 BESS Operation States 241
6.6.5 Post VRT 306
5.5.5 BESS Output Control 244
6.7 P For Q 306
5.5.6 BESS Precharge Types 245
6.7.1 UQ Area 306
5.5.7 BESS Stabilization 246
6.7.2 PQ Area 306
5.5.8 BESS/PV PF/Q Control 247
6.8 Q&U Protection 307
5.5.9 Connecting To Load 248
6.9 Synchronization & Connection Conditions 307
5.5.10 Curtailment Counter 254
6.9.1 Network connection/reconnection
5.5.11 Multiple Island Operation 256
conditions 307
5.5.12 Output Control – Frequency/Load 256
6.9.2 Network connection/reconnection
5.5.13 Output Control - Voltage/PF 259
conditions after Mains Fail 308
5.5.14 Parallel To Mains Operation - MINT
6.10 After Mains Trip Period 308
Application 261
6.11 Pave 309
5.5.15 Parallel To Mains Operation - MPTM
6.12 Moving Average 309
Application 263
6.12.1 10-minutes averages 309
5.5.16 Power Management 274
6.12.2 1-minute averages 310
5.5.17 PV Curtailment 295
6.13 BESS Operation Area 310
5.5.18 Regulation Loops 295
7 Communication 311
6 Grid Codes 299
7.1 PC 311
6.1 What are Grid Codes 299
7.1.1 Direct communication 311
6.2 Testing of Grid Codes 299
7.1.2 Remote communication 312
6.3 Power Regulation Based On Over/Under
Frequency 299 7.2 Connection to 3rd party systems 314
6.6.2 2-pole undervoltage failure ride 9.1.7 Logical binary outputs 1048
305
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
IMPORTANT: Controller issues Wrn Default Password (page 1251) alarm, if the factory default
password is used. It is necessary to change the factory default settings of password to be able to
clear the alarm.
Embedded
Copyright (c) 2016 jwellbelove
Template MIT license
www.etlcpp.com
Library
STM32Cube_
BSD 3 license
FW_H7
Copyright (C) 20xx, ChaN, all right
reserved.
Modify This software is provided by the copyright holder and
FatFs license contributors "AS IS" and any warranties related to this
BSD
software are DISCLAIMED. The copyright owner or
contributors be NOT LIABLE for any damages caused
by use of this software.
license
GCC Runtime GCC Runtime Library Exception - GNU
– GPL 3 exception,
Library Project - Free Software Foundationd
license
Note: The controller contains a large number of configurable setpoints, because of this it is impossible to
describe all of its functions. Some functions can be changed or have different behavior in different SW versions.
Always check the Global guide and New feature list for SW version which is used in controller. This manual only
describes the product and is not guaranteed to be set for your application.
IMPORTANT: Be aware that the binary outputs can change state during and after software
reprogramming (before the controller is used again ensure that the proper configuration and
setpoint settings are set in the controller).
The following instructions are for qualified personnel only. To avoid personal injury do not perform any action not
specified in related guides for product.
ANSI
Description ANSI code Description ANSI code Description
code
Master unit 1 Load shedding 32P AC circuit breaker 52
Stopping device 5 Master sequence device 34 Power factor 55
Multi-function device 11 Undercurrent 37 Overvoltage 59
Speed and frequency matching
15 Unit sequence starting 44 Alarm relay * 74
device
16EFT
Data communications device Current unbalance 46 Vector shift 78
16SC
Starting-to-running transition
19 Voltage unbalance 47 Reclosing relay 79
contractor
Distance relay 21 Incomplete sequence relay 48 Overfrequency 81H
Synchronizing-check 25 Temperature monitoring 49T Underfrequency 81U
Thermal relay 26 Overcurrent 50/50TD ROCOF 81R
Undervoltage 27 Earth fault current 50N+64 Auto selective control/transfer 83
Annunciator 30 Overcurrent IDMT 51 Regulating device 90
Overload 32 Earth fault current IDMT 51+64
EN 60255-1 g)
2
EN 60529 (IP20) EN 60068-2-27 (a=500 m/s ; T=6 ms)
Passive
Fuel
3 x Phases Coil current
solenoid
sensor
Active
Connector -
current Fuse Pick - up
female
sensor
Connector -
Fuse switch Relay coil
AirGate male
Relay coil of
Contact Generator slow-
Alternating
current operating
Generator
Contactor Renewable
Analog schematic
modem s
Controller
Grounding
simplified
Battery Resistor
Module
Battery GSM
simplified Resistor
Energy
adjustable
Storage
Current GSM
System Resistive
measuring modem
sensor
Binary
RPTC
output Current
IG-AVRi
measuring RS 232
Breaker male
contact IG-AVRi
Danger
TRANS RS 232
Breaker female
Danger -
contact Jumper
Electric
Shaft
Hazard
Generator
Breaker
DC to AC Load
Inverter Starter
Breaker
Mains Switch -
Diode
manually
Breaker operated
Ethernet Mains
male Transformer
Capacitor Mobile
Ethernet provider USB type B
female
male
Voltage
measuring
Wifi / WAN /
LAN
6 back to Document
information
2.4 AC measurement
With InteliNeo 6000 it is possible to easily set the parameters for measuring.
The controller is shipped with a Default configuration (page 118), which should be suitable for most
standard applications. This configuration can be changed only by using a PC with the InteliConfig software.
See InteliConfig documentation for details.
Once the configuration is modified, it can be saved to a file for later usage with another controller or for
backup purposes. The file is called archive and has the file extension .aig3. An archive contains a full image of
the controller at the time of saving (if the controller is online for the PC) except the firmware. Besides
configuration it also contains current adjustment of all setpoints, all measured values, a copy of the history log
and a copy of the alarm list.
The archive can be simply used for cloning controllers, i.e. preparing controllers with identical configuration
and settings.
2.7.2 WebSupervisor
Cloud-based system designed for monitoring and management of ComAp and 3rd party devices via the
internet. See more in the WebSupervisor Global Guide.
2.7.4 InteliSCADA
InteliSCADA is a Windows based software for monitoring of multiple controllers. See more in the InteliSCADA
Global Guide.
2.8 Displays
Remote Displays / Panel PC Displays
2.9.2 CM-4G-GPS
GSM/4G Internet module and GPS locator
Wireless integrated solution
Quick and easy installation
Support of WebSupervisor
Instant alarm SMS notification
System control over SMS
Quad Band GPRS/EDGE modem,
850/900/1800/1900 MHz, FDD LTE: Band 1,
Band 2, Band 3, Band 4, Band 5, Band 7, Band
8, Band 20, all bands with diversity,
WCDMA/HSDPA/HSUPA/HSPA+: Band 1,
Band 2, Band 5, Band 8, all bands with
diversity
GPRS multi-slot class 10
Tracking via GNSS (GPS,GLONASS) module
2.9.3 EM-BIO8-EFCP
Input and binary input/output extension module.
Up to 8 additional configurable binary inputs or
outputs
Supported sensors:
Resistor 3-wire input
Common resistor: 0-250Ω, 0-2400Ω, 0-10kΩ
Temperature sensor: Pt100, Pt1000, Ni100, Ni1000
Current (active or passive sensors)
±20mA , 0-20mA, 4-20mA
Voltage
±1V, 0-2,4V, 0-5V, 0-10V
Lambda probes
Thermocouples are not supported (the measuring loop was
designed for lambda probes, what caused non-support of
thermocouples)
Impulse/RPM sensor:
RPM measuring pulses with frequency 4Hz – 10kHz
Impulse
Possibility to measure pulses from electrometer, flowmeter,
etc.
Configuration 8/8
8 Binary inputs (options: pull up or pull down logic)
8 Binary outputs (options: Low side switch (LSS) or High side switch
(HSS))
2 Analog outputs (options: voltage (0-10V), current (0-20mA) and
PWM (5V, adjustable frequency 200Hz-2,4kHz))
Configuration 16/0
16 Binary inputs (options: pull up or pull down logic)
0 Binary outputs
2 Analog outputs (options: voltage (0-10V), current (0-20mA) and
PWM (5V, adjustable frequency 200Hz-2,4kHz))
6 back to CAN Extension Modules
2.10.3 IGL-RA15
Remote annunciator. See more information on web page IGL-RA15.
15 programmable LEDs with configurable
colors red-green-yellow
Lamp test function with status LED
Customizable labels
Local horn output
Maximal distance 200 m from the controller
Up to 4 units can be connected to the controller
UL certified
IMPORTANT: This module is not compatible with different than 250 kbps communication speed. If
the ECU module with 125 kbps communication speed is connected the whole system will
automatically switch to the 125 kbps, and IGL-RA15 module will stop communicating.
Supported sensors:
J, K or L thermocouples
Thermocouples with and without cold junction compensation are
supported
2.10.7 I-AOUT8
The module allows customers to configure up to 8 analog outputs. AGND terminals are on the same potential.
See more information on web page I-AOUT8.
2.10.8 IS-AIN8
The module is equipped with 8 analog inputs. This module is compatible with MTU ECU-7 at communication
speed 125 kbps when uploaded with firmware 1.2.0 and higher. See more information on web page IS-AIN8.
2.10.9 IS-AIN8TC
The module is equipped with 8 analog inputs dedicated for thermocouple sensors only. See more information
on web page Inteli AIN8TC.
J, K or L thermocouples
Thermocouples with and without cold junction compensation are
supported
2.10.10 IS-BIN16/8
The module allows users to expand the amount of binary inputs and outputs, and add 2 impulse inputs. It is
possible to configure the unit to have 16 binary inputs (galvanic separated) and 8 binary outputs (galvanic
separated), 2 pulse inputs (frequency measurement or pulse counting). See more information on web page
IS-BIN16/8.
Note: CAN address 0 disables corresponding CAN message (Group data are not send).
2.11.2 I-CR
If the distance between units is too high to fit into the 200 m limit (or 900 m for 8 controllers), CAN repeater
module (I-CR) can be used to extend it. See more information on web page I-CR.
Proper alarm from a range DISTIN 01 (page 1325) to DISTIN 64 (page 1340) is activated in case that data are
not received from the Controller Unit.
Binary Inputs
32 binary states are paired by eight to two shared values:
Binary inputs 1 1-8 (page 942)
Binary inputs 1 9-16 (page 942)
Binary inputs 1 17-24 (page 943)
Binary inputs 1 25-32 (page 943)
Note: Values above are related to virtual module DIST-IN 1. See values for other modules here:
GROUP: DIST-IN 1-32 (PAGE 942)
GROUP: DIST-IN 33-64 (PAGE 949)
IMPORTANT: Binary inputs X 9-16 and higher can be shared only if CAN Intercontroller Comm Mode
(page 397) = 64C CAN FD or 32C CAN FD or 8C CAN FD.
Analog Inputs
Up to 4 analog values are shared:
DISTAIN-1 1 (page 944)
DISTAIN-1 2 (page 944)
DISTAIN-1 3 (page 944)
DISTAIN-1 4 (page 945)
Note: Values above are related to virtual module DIST-IN 1. See values for other modules here:
GROUP: DIST-IN 1-32 (PAGE 942)
GROUP: DIST-IN 33-64 (PAGE 949)
IMPORTANT: Analog values can be shared only if CAN Intercontroller Comm Mode (page 397) = 64C
CAN FD or 32C CAN FD or 8C CAN FD.
Note: If the CAN communication is lost, the DIST-IN analog inputs become invalid and the values are shown as
'####'.
Configuration
Configuration of the virtual module itself, binary and analog outputs is done via InteliConfig. As with other
modules, you can choose whether history columns and display screens are added as well as select type of
DIST-OUT
This virtual module shares binary and analog values to other controller units via CAN Intercontroller
Communication (page 132).
In case that there is detected module failure, alarm DISTOUT (page 1341) is activated. The CAN connection is
lost with another CU or this module is not configured.
Binary Outputs
32 binary states are paired by eight to four shared values:
Binary outputs 1-8 (page 964)
Binary outputs 9-16 (page 964)
Binary outputs 17-24 (page 965)
Binary outputs 25-32 (page 965)
IMPORTANT: Binary outputs 9-16 and higher can be shared only if CAN Intercontroller Comm Mode
(page 397) = 64C CAN FD or 32C CAN FD or 8C CAN FD.
Analog Outputs
Up to 4 analog values can be shared.
IMPORTANT: Analog values can be shared only if CAN Intercontroller Comm Mode (page 397) = 64C
CAN FD or 32C CAN FD or 8C CAN FD.
Configuration
Configuration of the virtual module itself, binary and analog outputs is done via InteliConfig. As with other
modules, you can choose whether history columns and display screens are added as well as select type of
protection upon module failure.
An alarm Wrn SHBIN Collision (page 1349)- is activated in case that more than just one controller has
configured SHBOUT module with same module index in CAN topology.
IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.
Proper alarm from a range SHBIN 1 (page 1347) to SHBIN 6 (page 1349) is activated in case that data are not
received.
Binary Inputs
SHBIN-1 (page 956)
Note: Value above is related to virtual module SHBIN-1. See values for other modules here: Group: SH
Modules (page 956)
SHBOUT
SHBOUT virtual modules share binary values to other controllers via CAN Intercontroller Communication
(page 132). There are 6 modules, SHBOUT-1 to SHBOUT-6, which are firmly connected with SHBIN-1 to
SHBIN-6.
IMPORTANT: This means that you need to use module SHBOUT-1 if you wish to send data to SHBIN-
1.
IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.
Binary Outputs
SHBOUT-1 (page 959)
Note: Value above is related to virtual module SHBIN-1. See values for other modules here: Group: SH
Modules (page 956)
An alarm Wrn SHAIN Collision (page 1347) is activated in case that more than just one controller has
configured SHAOUT module with same module index in CAN topology.
IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.
Proper alarm from a range SHAIN 1 (page 1347) to SHAIN 2 (page 1347) is activated in case that data are not
received.
Analog Inputs
SHAIN-1 1 (page 962)
SHAIN-1 2 (page 962)
SHAIN-1 3 (page 962)
SHAIN-1 4 (page 962)
Note: Value above is related to virtual module SHAIN-1. See values for other modules here: Group: SH
Modules (page 956)
SHAOUT
SHAOUT virtual modules share analog values to other controllers via CAN Intercontroller Communication
(page 132). There are 2 modules, SHAOUT-1 and SHAOUT-2, whicha re firmly connected with SHAIN-1 and
SHAIN-2.
IMPORTANT: This means that you need to use module SHAOUT-1 if you wish to send data to SHAIN-
1.
IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.
IMPORTANT: In the MPTM scheme dashed line at BCB breaker is for AC precharge and full line is
for DC precharge.
IMPORTANT: The InteliNeo6000 can work together with multiple Gen-set and Mains controllers,
but it cannot work with any other Microgrid/BESS controller. Only one InteliNeo6000 per site is
supported.
IMPORTANT: In the MINT scheme dashed line at BCB breaker is for AC precharge and full line is
for DC precharge.
Note: The package does not contain a communication or extension modules. The required modules should be
ordered separately.
Note: The controller is mounted into panel doors as a standalone unit using provided holders. The requested
cutout size is 187 × 132 mm. Use the screw holders delivered with the controller to fix the controller into the
door.
4.2.2 Mounting
The controller unit should be mounted onto the backside of the switchboard door and after the installation it
should be inaccessible for nonauthorized people. There are two ways how to mount the CU.
max 600 V
BESS voltage inputs Voltage measurement wiring (page 56)
AC Ph-Ph
max 600 V
Mains/Bus voltage inputs Voltage measurement wiring (page 56)
AC Ph-Ph
max ± 10 V
Analog Output Analog Outputs (page 70)
DC
max ± 10 V
Analog Output Analog Outputs (page 70)
DC
max 36 V
Binary inputs Binary Inputs (page 64)
DC
max 10 V
Analog inputs Analog Inputs (page 67)
DC
5 V DC
Sensor power supply max 100
mA
+, N/A, -
Power supply 8 - 36 V DC Power supply (page 51)
max 7,5 A
Improves resistance to electrical interference if
Grounding
connected to the ground.
max 36 V;
Binary outputs Binary Outputs (page 65)
0,5 A
Tightening torque and allowable wire size and type for the Field-Wiring Terminals:
For BESS Voltage and Mains Voltage terminals
4.4.2 Grounding
2
The shortest possible length of wire should be used for controller grounding. Use cable min 2.5 mm .
The negative " - " battery terminal used as power supply for CU must be properly grounded.
Switchboard must be grounded at common point. Use as short cable as possible to the grounding point.
The controller includes internal capacitors that allows the controller to continue in operation if the voltage dip
occurs. The capacitors are useful mainly during short cranking voltage dips for the connections with 12 V battery
power supply. If the voltage dip goes during cranking to 0 V and after 50 ms it recovers to 8 V, the controller
continues operating. When this situation occurs the binary outputs are temporarily switched off and after
recovering to 8 V back on. This cycle can be repeated several times.
Note: It is also possible to further support the controller by connecting the external capacitor and separating
diode. The capacitor size depends on required time. It shall be approximately thousands of μF. The capacitor
size should be 5 000 μF to withstand 150 ms voltage dip under following conditions: Voltage before dip is 12 V,
after 150 ms the voltage recovers to min. allowed voltage, i.e. 8 V.
Image 4.4 Controllers power supply with external capacitor, separating diode and fusing
Note: Suitable conductor protection shall be provided in accordance with NFPA 70, Article 240.
IMPORTANT: 8 A fuse is calculated without BOUT consumption nor extension modules. Real value
of fuse depends on consumption of binary outputs and modules.
IMPORTANT: Risk of personal injury due to electric shock when manipulating voltage
terminals under voltage. Be sure the terminals are not under voltage before touching
them.
Do not open the secondary circuit of current transformers when the primary circuit is
closed. Open the primary circuit first.
Image 4.6 BESS current measurement Image 4.7 AUX Mains/Bus current measurement
wiring wiring
ConnectionType: SplitPhase
Connection type (page 378) = SplitPhase
Image 4.8 BESS current measurement Image 4.9 AUX Mains/Bus current measurement
wiring wiring
Image 4.10 BESS current measurement Image 4.11 AUX Mains/Bus current measurement
wiring wiring
Image 4.14 AUX EFC measurement wiring for load network only
Image 4.15 AUX EFC measurement wiring for restricted earth protection
Image 4.16 Controller wiring for voltage measurement of 3 phase application with neutral
Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.
Image 4.18 Controller wiring for voltage measurement of High Leg Delta application
Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.
Image 4.19 3 Controller wiring for voltage measurement of 3 phase application without neutral
Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.
Note: Terminals marked by Tx in the pictures above are BESS's terminals. These markers are not the same
as markers for the controller wiring.
Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.
Image 4.26 Wiring binary inputs - Pull Up Image 4.27 Wiring binary inputs - Pull Down
4.4.7 E-Stop
The E-Stop is commonly used for quick emergency stop of the BESS. It has dedicated terminal T04 which
should be wired trough the Emergency Stop button to the battery voltage. The E-Stop is also used as power
supply for binary output 1 (T05) and binary output 2 (T06). . So, these binary outputs will not work if the E-Stop
is not powered up, that means higher security and faster disconnection of these outputs. For more information
about E-Stop functions see chapter E-STOP (page 143).
Note: Grey dashed line symbolizes internal connection between E-Stop and binary outputs 1 and 2.
Note: For proper functionality of E-Stop, the terminal T04 must be always wired. Terminal can be connected
to battery+ or to terminal T03 (BATT+)
IMPORTANT: Use suppression diodes on all relays and other inductive loads even if they are not
connected directly to the controller Binary Outputs.
Resistive sensors
The analog inputs for resistive automotive type sensors like VDO or DATCON are connected either by one wire
(the second pole is the sensor body) or by two wires.
In the case of grounded sensors, connect the ACOM terminal to the ground as near to the sensors as
possible.
In the case of isolated sensors, connect the ACOM terminal to the negative power supply terminal of the
controller as well as one pole of each sensor.
Note: Schemes show only analog input connection overview, not actual wiring.
Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Voltage sensors
Recommended wiring for the voltage measurement with voltage divider. The voltage sensor is displayed as
voltage source which is usually powered from battery or any external DC power source. The ACOM terminal is
connected to the negative power supply terminal of the controller as well as negative pole of each sensor.
Note: The voltage divider is only relevant for sensors which are outside the 0-10 VDC range.
Current sensors
Recommended wiring connections for the active and passive current sensors. The active sensor is displayed as
current source which is usually powered from battery or any external DC power source. The passive sensor is
displayed as resistive load which is placed between battery + and AIN. The passive sensor does not require
additional power supply.
Image 4.35 Wiring of analog input with active Image 4.36 Wiring of analog input with passive
current sensor current sensor
Image 4.37 Analog inputs as tristate Image 4.38 Analog inputs as binary
Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Analog outputs can be used for any purpose and their outputs can be switched according to options below.
Note: The jumper switch next to the terminal 61 is a short switch of 10k serial resistor at analog output 2. By
default, the jumper is switched off (the resistor is included in the circuit).
Voltage
Output range: -10 to +10 V
Maximum load: 5 mA
Output accuracy: 1 % from set value ±100 mV (measured at load 10 kΩ)
Minimum step: 1/10000 of full range (approx. 14bit resolution)
Step response: 10 ms max. (measured between 10 and 90 %)
Output ripple: 30 mV max. (measured at 50% duty cycle at 3000 Hz PWM)
Current
Output range -20 to +20 mA
Maximum load: 500 Ω
Output accuracy: 1 % from set value ±200 µA
Minimum step: 1/10000 of full range (approx. 14bit resolution)
Step response: 10 ms max. (measured between 10 and 90 %)
Output ripple: 60 µA max. (measured at 50% duty cycle at 3000 Hz PWM)
PWM
Output voltage levels: 0 V / 5 V
Maximum load: 10 mA
Output High level: >4 V @ 10 mA
Output Low level: <1 V @ 10 mA
Minimum step: 1/10000 of full range (approx. 14bit resolution)
Frequency range: 500 to 3000 Hz (settable during configuration)
Note: A termination resistor at the CAN (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the appropriate CAN terminal.
1Recommended data cables: BELDEN (http://www.belden.com) - for shorter distances: 3105A Paired - EIA
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)
Note: Shielding shall be grounded at one end only. Shielding shall not be connected to CAN COM terminal.
Note: In case of surge hazard (long distances, connection out of building, storms, etc.), consider using surge
protection1.
RS485 wiring
The wiring of the RS485 communication should be provided in such a way that the following rules are observed:
Note: A termination resistor at the RS485 (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the RS485 terminal.
① Recommended PT5HF-5DC-ST1
Note: Communication circuits shall be connected to communication circuits of Listed equipment.
Balancing resistors
The transmission bus into the RS-485 port enters an indeterminate state when it is not being transmitted to. This
indeterminate state can cause the receivers to receive invalid data bits from the noise picked up on the cable. To
prevent these data bits, you should force the transmission line into a known state. By installing two 560 Ohm
balancing resistors at one node on the transmission line, you can create a voltage divider that forces the voltage
between the differential pair to be less than 200 mili-Volts, the threshold for the receiver. You should install these
resistors on only one node. The figure below shows a transmission line using bias resistors. Balancing resistors
are placed directly on the PCB of controller. Use jumpers PULL UP/PULL DOWN to connect the balancing
resistors.
4.4.11 USB
The USB can be used for direct computer connection. Use the shielded USB A-B cable. See the chapter
Connection via USB (page 311) for more information.
The USB cannot be used instead of power supply. The controller will not be turned on when the USB is
connected and the controller is not powered from power supply.
IMPORTANT: The InteliNeo6000 is using same MAC address for all Ethernet ports so it is not
possible to use more than one Ethernet port in the same network. If you connect for example
Ethernet 1 and 2 to the same network the communication will breakdown.
In the image below you can see the topology using all 3 Ethernet ports with one Modbus Client. The ETH1 is
used for connection of displays (IV5.2) or it can be also used for remote LAN connection. The ETH2 is used
for remote connection using the internet (WAN). The ETH3 is used for Modbus Server and Client which are
connected to the LAN with Modbus Devices.
Note: The IP address of each device in the same network must vary.
Note: InteliVision 5.2 is used for illustrative purposes, the same wiring diagrams apply for all supported displays
mentioned in Displays (page 23).
Note: The picture above is only an example of the topology. An additional switch/switches may be needed to
match the required network topology (i.e. number and location of the LAN connection points). Please consult
this topic with ethernet network specialist.
Technology Description
Current, most advanced, technology. It is being deployed rapidly in some
areas it may replace the legacy 2G networks. We recommend using this
4G (LTE) technology if it is available in the target area
Provides highest data throughput rate and lowest latency
Best user experience – like a wired connection
Successor of 2G. It is in operation in some areas, but it is not expanding
anymore.
3G (UMTS, HSPA, CDMA)
Provides lower throughput rate and higher latency then 4G*
Still quite good user experience
Very first digital cellular network technology. It is still available in many
areas, however it is slowly starting to decline.
2G (GSM, GPRS, EDGE) Provides lowest throughput rate and quite high latency
Generally not suitable for connection of multiple ComAp devices
via a router
Frequency bands
It is very important that selected cellular router matches the frequency bands used by providers in the target
country or area. 4G networks worldwide use many of frequency bands and manufacturers of cellular modules
and routers sell their devices in multiple variants according to the region. A useful overview of LTE frequency
bands is available at Wikipedia page.
Note: Consult the technical documentation and/or technical support of the router's manufacturer to get more
information about ordering proper regional version of your selected router.
IMPORTANT: When configuring a router, the very first step to do should be changing the
username and password for administration access.
Cellular network
Usually the only setpoint that needs to be adjusted is the APN name. A frequent APN name is "internet", but if
you are not sure ask your SIM card provider for proper APN name.
WAN interface
If the router contains also ethernet socket for WAN connection it may be required to select cellular module as
the main WAN interface.
LAN setup
Most routers do not require any changes in the LAN configuration as their default configuration contains
DHCP server activated. Clients will get IP settings automatically.
For display connection it is recommended to use Ethernet 1 (trusted interface in default). Direct connection of
InteliVision display to InteliNeo 6000 via ethernet cable can be used only for connection of single device.
Using switch for connection allows you to connect multiple devices such as display, computer and Modbus to
InteliNeo 6000 at one time.
Note: The IP address of each device in the same network must vary.
Note: InteliVision 5.2 is used for illustrative purposes, the same wiring diagrams apply for all supported displays
mentioned in Displays (page 23).
The battery is located in a holder on the circuit board. Remove the old battery with a small sharp
screwdriver and push with a finger the new battery into the holder.
Warning – Risk of fire if battery is replaced with incorrect type or polarity. Dispose of used batteries
according to instructions. The CR1632 3V Lithium battery have to be used."
Note: The picture above is only illustrative and actual battery placement may vary.
Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention that the
cover is in correct position and not upside down!
Put back the back cover.
Power the controller on, adjust date and time and check all setpoints.
Note: The images used in the Operator Guide are only illustrative. The screens shown in the images are
compatible with the InteliGen 1000 Controller, but the functionality of the IV 5.2 Display such as Connection,
Login, Setpoints Settings, Display Settings, etc. remains the same.
Navigation buttons
Arrow buttons on the front panel are mainly used for navigation inside the entire graphical user interface. In
addition the arrows left and right are used for changing the controller mode if the actual position is any
metering screen.
Enter
Menu
Function buttons
Function buttons are dedicated for the performing of the concrete function. By pressing the button the
controller action or controller command is performed (see bellow).
Image 5.6 : Function buttons (Start, Stop, Alarm/Horn reset, Horn reset)
+
Image 5.8 : Shortcut (jump to the administration)
Enter + Menu : performs the jump to the administration. Enter button has to be pressed first.
Long press of the arrow up or down button
in the menus : performs the cyclical listing
in the dialog : velocity of the changing value is increased
based on special algorithm
Status LED
There is one multicolor (RGB) LED on the front panel of the unit. The specified color and flashing function
describes the actual state of the unit.
LED intensity is directly connected with the actual setting of the backlight intensity in Administration menu
"Settings" accessible by shortcut Enter + Menu
the intensity respects the value of the Manual or External brigness control
The flashing of the status LED and indicative Alarm icon in the top statusbar have the same period
Meaning of the status LED colors is described below
Page Structure
Pages
There are several screens called pages in the graphical user interface (GUI), which are accessible by
pressing the Menu button or concrete user button in the bottom status bar. Each page has a different function
and different structure. Pages are described in special chapters in this manual.
The actual GUI consists of 6 different pages :
Setpoints
Metering screen
Alarmlist
History
Trends
Administration
Page administration is accessible only by pressing the combination of the Enter and Menu buttons
from only Metering screen.
Screens
Each type of controller has special set of screens stored in the controller configuration. The description of the
each metering screens is by default predefined by ComAp. Scrolling between the screens is performed using
the arrow up and down buttons.
Note: The metering screens are adjustable using the Screen Editor (in InteliConfig). See chapter Screen
Editor for more information. The Screen Editor tool also has its own manual.
Note: Concrete status bar views for concrete page are described in specific chapters in this manual.
Note: Inactive buttons are visually indicated as grayed button. It means that the button is not available for any
reason (e.g. password protected button).
1. Mode selector - Mode selector is dedicated for the controller mode selection. Using arrow left and right
the controller mode is changed (only on the metering screens). The choice must be always confirmed by
enter button. There is 5s timer for the automatic mode selector dialog cancellation. The mode selector
dialog can be also canceled by menu button.
2. Page title - Each page and each metering screen has its own title. The first number in square brackets
describes the actual metering screen position. The second number describes the total available number of
metering screens.
3. Trending - The icon is active when the trending is running. Icon is inactive when the trending is stopped.
4. USB Stick - The icon is active if the USB stick is plugged in the display unit. Icon is inactive if there is no
USB stick plugged in.
5. Access Lock - Access lock icon is active if the display is locked for security reasons. Icon is inactive if the
controller unit is not locked.
InteliNeo 6000 - the function in InteliNeo 6000 is connected to the specific user account. It means only
the user with sufficient rights can operate the controller or deactivate access lock function.
Icon ( - Single Lock) is displayed if the controller is locked and actually logged-in user is the lock
owner. User is able to operate the controller or to deactivate the access lock function.
Icon ( - Double Lock) is displayed if the controller is locked and actually logged-in user is NOT
the lock owner. Also the Access Lock function can not be deactivatedbecause of insufficient access
rights. See chapter Access Lock for more information.
6. PC connection - PC connection icon is not supported in InteliVision 5.2.
7. Alarm indication - The alarm icon is flashing red if there is at least one unconfirmed alarm (shutdown or
warning) in the alarmlist. The icon lights red if there is at least one confirmed active alarm and no
unconfirmed alarm in the alarmlist. The icon is inactive if the alarmlist is empty.
8. User - The user icon lights green if the user is logged in to the controller. The icon is inactive if the user is
logged out.
StartUp screen
The StartUp screen is defined in firmware and can not be adjusted. The screen is used as a default point in
user interface. The main purpose of the screen is to handle all the necessary messages from the display to
Note: Connecting and connected state are marked red because at that moment the user is not logged in yet.
Login procedure is automatic to InteliNeo 6000 controller on StartUp screen (user with access rights 0 is
always loged in). Due to this fact the connecting and connected state are the transition states only on StartUp
screen.
Password item - the item dedicated for the login and logout to the controller.
Currently Logged-in User - the information about actually logged in user or his ID if loged using ID and PIN.
Access Rights - Access rights of the actually logged in user
0 - user has access rights 0, which means "logged-out" user
0,1 - user has access rights 0 + 1 access rights
0,1,2 - user has access rights 0 + 1 + 2 access rights
0,1,2,3 - user has access rights 0 + 1 + 2 + 3, which means administrator rights
Login and Logout buttons
Login button calls the login dialog.
Logout button performs the logout action.
Enter Password
The dialog password is dedicated for password insertion. When the dialog is active the buttons arrow up and
down are used for number selection. Enter button confirms the option. Menu button cancels the dialog without
saving.
Password Change
The dialog password change is dedicated for password change. When the dialog is active the buttons arrow
up and down are used for number selection. Enter button confirms the first option and the same password
Note: The user must be logged in with respective rights to be able to change password for respective rights.
Setpoints
The setpoint page is intended for setting the controller values. Each type of controller has specific setpoints to
be set. The setpoints also depend on the type of application like MPTMMCB and MINT. Availability of the
setpoint item also depends on configuration level settings in Administration page. Setpoint is set in 2 steps.
1st step - Setpoint group is selected using buttons arrow up and down and confirmed using enter button
1. Setpoints group - the column setpoint group displays the available groups based on the controller,
application type and configuration level settings. Respective setpoint group is selected using enter button.
2. Available setpoints in actually selected group - each setpoint group contains specific setpoints. The
informative column Setpoint name displays the available set of setpoints to be set in each Setpoint group.
1. Setpoint name - Setpoint is set using the enter button. Specific dialog is displayed and the value can be
set. There are several types of dialogs (text, numeric, stringlist) and the type of called dialog depends on
the setpoint type. The dialogs are described in the chapter Dialogs.
2. Actual value - Informative actual value for specific setpoint is displayed. Value range, original value and
default value for the selected setpoint are displayed inside the dialog.
IMPORTANT: If the controller is locked (Access Lock function is active) then the attempt for
setpoint editation is denied and the information dialog is displayed (Controller is Locked). See
chapter Administration and Access Lock.
Numeric change
Value
The dialog value is dedicated for number setting. When the dialog is active the buttons arrow up and down are
used for number selection. Enter button confirms the option. Menu button cancels the dialog without saving.
Value Extended
The dialog value extended is dedicated for number setting with combination with one or more string value.
When the dialog is active the buttons arrow up and down are used for number/item selection. Enter button
confirms the option. Menu button cancels the dialog without saving.
IP address
The dialog IP address is dedicated for IP address insertion. When the dialog is active the buttons arrow up
and down are used for number selection. Arrows left and right are used for moving between the IP cells. Enter
button confirms the option. Menu button cancels the dialog without saving.
Text Edit
The dialog text is dedicated for text inserting or modification. When the dialog is active the buttons arrow up
and down are used for letter selection. Arrow up means the selection in left direction, arrow down means the
selection in right direction. Arrows right/left are used for moving between the letters to the next/previous letter
position in the text field. If actual position is very right letter then the arrow right inserts new letter to the right.
Letter DEL deletes actualy selected letter (using left or right arrow). Insert letter (empty letter - just behind the
DEL letter) inserts the letter to the actual position (using left or right arrow) Enter button confirms the text
modification. Menu button cancels the dialog without saving.
Note: Enter button is used for dialog confirmation and saving the entire text to the configuration and because
of this the DEL and INS letter is inserted using the left or right arrow button.
Date
The dialog date is dedicated for date setting. When the dialog is active the buttons arrow up and down are
used for number selection. Arrows left and right are used for moving between the date cells. Enter button
confirms the option. Menu button cancels the dialog without saving.
Time
The dialog time is dedicated for date setting. When the dialog is active the buttons arrow up and down are
used for number selection. Arrows left and right are used for moving between the time cells. Enter button
confirms the option. Menu button cancels the dialog without saving.
Timer settings
The dialog timer is dedicated for timer setting. When the dialog is active the buttons arrow left and right are
used for the line option selection. Enter button confirms the actual option in the line and the next option can be
performed. Enter button on the last line confirms all the option in dialog and save the timer settings to the
controller. Menu button cancels the dialog without saving.
Metering screens
InteliNeo 6000 Controller screens
InteliNeo 6000 metering screens are predefined by ComAp and covers all the application types.
the movement between the metering screens is done using the arrow up and down buttons in the front
panel
the entire screens and instruments on the screens are dynamically displayed or hidden based on the
following state of the controller unit :
Application type
Wiring controller settings
Configured CAN modules
ECU list settings
Alarmlist
The alarmlist page is intended for displaying the controller alarms. If any of the following type of the controller
alarm occurs The alarmlist page is displayed and also the alarm icon in the Top status bar starts flashing
RED, even if it is not the shutdown alarm. The Automatic jump to the Alarmlist page is performed only in case
the actual GUI position is the Home metering screen. The alarm icon in the top status bar is informative icon
where the display unit informs the user that there is any alarm stored in the controller unit. Pressing the User
Note: The alarmlist page is automatically displayed and backlight is turned on if the new alarm appears (only
in case the actual GUI position is the Home metering screen).
IMPORTANT: Alarm reset button confirms all the unconfirmed alarms stored in controller and
resets the horn. Horn reset button resets only the horn.
IMPORTANT: If the actual GUI position is Alarmlist page and there is at least one uncofirmed
alarm in the Alarmlist the jump to the home metering screen and backlight timeout are ignored.
History
The history page displays the records of the important moments in the controller history.
There are 2 types of history records :
Event records - are also known as standard history records. This type of record appears in case the
controller event has been made. The time stamp history also belongs in the event history. The time record
is stored for a specified period of time.
System records - are also known as text history record. These type of records are generated during the
user login/off, controller programming or other system actions.
1. Fixed column - has a different shade of colour. Fixed column is always merged and anchored on the left
side of the history page.
Note: Pressing the enter button on the actually selected row the dialog with detailed information for selected
record is displayed.
IMPORTANT: Each controller unit supports the specific number of history records. E.g. controller
InteliNeo 6000 supports 1000 history records. Default configuration consists of 33 columns.
Maximal column amount is approximately 100 columns based on the type of the observed value.
1. X axis -X axis displays the time stamps. The view of X axis is fully automatic.
2. Y axis - If the default range is not suitable for the displaying of the value it can be adjusted in settings
option. See bellow for more information.
3. Grid - the grid is displayed behind the trends charts. The grid is fully automatic.
4. Trend line - each channel have different colour for better value identification. The color of the trend line
match to the Value color in channel panel.
5. Actual period - Actual period settings. The period can be adjusted in settings option.
6. Actual channel value panels - display the values of the newest (actual) sample.
Administration
Administration menu screen is accessible by using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.
+
Image 5.37 : Shortcut (jump to the administration)
Configuration Level
Standard - Limited amount of settings are available for configuration. The description which settings are
available in chapters concerning to controller functions.
Advanced - Set by factory default. All the settings are available for configuration. Be aware that only
experiences users should perform the settings of extended functions.
Note: By default the Advanced settings is selected which means all the setpoints are available by default. To
restrict the availability the Standard setting must be performed. The advanced and standard category are set
in InteliConfig PC application.
Note: Configuration Level screen is accessible using the buttons combination Enter + Menu just only from
the metering screens. Enter button has to be pressed first.
1. Backlight Time - if the cell area is pressed the dialog for time settings is displayed. The user is able to set
the period from 1 up to 241 minutes. There is also the option to set NO Timeout which means the display
unit is backlighted forever. Note that in remote displays like IntelIVision 5.2 the Backlight Timeout option is
not mirrored with controller setpoint Backlight Timeout (it is mirrored in Integrated Color Display).
2. Brightness Control :
a. Manual (by default) - the value of the backlight is set manually using the value dialog (point 3)
b. External - the value of the backlight is controlled by the external resistor or potentiometer. Resistor 5-
2400 Ω corresponds to 0-100% backlight. If the resistor value is out of range, the manual option is
used.
3. Brightness intensity - the value is selected using the value dialog. Note the value is applied immediately
during the change of the value.
4. Internal Temperature information- gives the actual inside temperature of the unit. There is implemented
automatic mechanism for lowering the backlight intensity based the internal derating backlight curve. If the
inside temperature exceeds 35 °C the area behind the temperature lights yellow. The yellow color
indicates that the display backlight curve is applied and automatically starts derate the backlight intensity.
The backlight intensity returns to normal when the temperature is decreased bellow 35 °C. This feature
saves the lifetime of the internal components.
IMPORTANT: It is strongly recommended to use backlight on the standard level max. 60%.
Maximal backlight intensity level of 100% is suitable only for application with higher amount of
the ambient light. Be aware that higher intensity level means higher surface front glass
temperature and lower lifetime.
IMPORTANT: It is strongly recommended to use Backlight Time (timer) set on the reasonable
amount of time (approximately 30 minutes) during the normal running BESS phase. It is because
of saving lifetime of the display unit. The display unit is still running if the backlight is off. For
switching on the LCD backlight the simple pressing any button is necessary.
Note: Settings screen is accessible using the buttons combination Enter + Menu just only from the metering
screens. Enter button has to be pressed first.
Language settings - the list of languages stored in the controller configuration is displayed in the list of
possible languages.
The InteliVision 5.2 and Integrated Color Display units support the following languages
English
Chinese
Japanese
The InteliVision 5.2 and Integrated Color Display units partially support the following languages
Bulgarian, Taiwan, Czech, German, Greek, Spanish, Finnish, French, Hungarian, Icelandic, Italian,
Korean, Dutch - Netherlands, Norwegian, Polish, Roman, Russian, Croatian, Slovak, Swedish,
Turkish, Ukrainian, Slovenian, Estonian, Latvian, Lithunian, Vietnamese, Italian, Portuguese, Bosnian
The InteliVision 5.2 and Integrated Color Display units support the following Unicode standard character
sets
Basic Latin, Latin-1 Supplement, Latin Extended-A, Latin Extended-B, Latin Extended Additional,
Cyrillic, Greek, Greek Extended, Arabic, Arabic Supplement, General Punctuation, Superscripts and
Subscripts, Currency Symbols, Arrows, CJK Unified Ideographs, Kanji, Hiragana (full width), Katakana
(full width), Hangul Jamo, Thai
IMPORTANT: Even the language is configured in InteliConfig the specific language is unavailable
if the language is empty or the language is not supported by the display unit.
Note: The flag is not displayed if the language is supported but the flag icon does not exist in the integrated
color display unit.
Note: Languages screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.
Note: Similar values with similar structure can be displayed using InteliConfig PC tool.
Note: Controller Info screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.
IMPORTANT: Integrated Color Display information in Controller Info screen is not available in
remote displays.
Note: The availability of the connected module depends on the type of controller unit.
Note: Modules Info screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.
Note: The availability of the connected ECU module depends on the type of controller unit.
Note: ECU Modules screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.
OFF mode
No start of the BESS is possible and starting command cannot be issued.
No reaction if buttons START , STOP , MCB ON/OFF , BCB ON/OFF are pressed.
Note: When the BESS is running, it is not possible to switch the controller to OFF mode.
MAN mode
To start the BESS press START.
When the BESS voltage is within limits, the BESS icon will light green.
Press BCB ON/OFF to close the BCB. If the BESS voltage is out of the limits, controller does not respond
to the BCB ON/OFF .
If controller detects dead bus, immediately closes output.
If controller detects voltage on the bus, starts synchronizing.
When the breaker is closed, the breaker icon will light green.
AUTO mode
BESS is controlled based on external signals GENERIC GENSET START/STOP (PAGE 1004) or conditions
(AMF, Peak shaving, Power management system, etc.).
When one condition deactivates the BESS, it will not stop if another condition for automatic starts is active.
Controller does not respond to BCB ON/OFF, MCB ON/OFF, STOP, START buttons and corresponding
remote InteliScada or Modbus commands.
IMPORTANT: If a red alarm is present and the controller is in the AUT mode, the BESS can start
by itself after all red alarms become inactive and are acknowledged (fault reset is pressed)! To
avoid this situation, adjust the setpoint Fault Reset To Manual (page 386) to the Enabled position.
5.2.1 USB
You may connect to the controller using the ⑭ USB (page 46) Port. In this case standard USB A to B cable
should be used - USB (page 74) connection.
Select your controller from the list of Detected controllers. You need to know your contoller's serial number.
Note: You do not need to be using user account while connecting via USB.
Image 5.46 WinScope screen - Select your controller from list of Detected controllers.
Select your controller from the list of Detected controllers. You need to know your contoller's serial number.
Note: You do not need to be using user account while using WinScope1000 connected via USB.
5.2.2 Ethernet
You may connect to the controller using any of the Ethernet 1 (page 49), Ethernet 2 (page 49), or Ethernet 3
(page 49) ports, if correct Ethernet Port Configuration settings are applied (Ethernet port 1 (page 403),
Ethernet port 2 (page 404), Ethernet port 3 (page 405)).
Note: See Communication peripherals (page 18) to see differences between these peripherals.
Direct connection
When you use direct connection the controller needs to be reachable directly from the PC you use (i.e. one
LAN or WAN without any firewalls and other points that may not allow the connection). The following settings
need to be checked in the controller:
Direct Connection Port (page 411) has to be set to the same value as in the PC tool.
IP Address Mode (page 406) can be set to AUTOMATIC when there is DHCP service is available.
Otherwise it needs to be set to FIXED.
IP Address (page 407) is either set automatically or it can be adjusted to a specific requested value.
Subnet Mask (page 407) is either set automatically or it can be adjusted to a specific requested.
Gateway IP (page 408) can be set here when it is used.
Note: The connection speed might be significantly limited when you connect the controller directly from the
PC and your Ethernet card is setup to Energy-Efficient Ethernet option.
Use IP address which is stored in proper value (based on selected Ethernet peripheral) and fill Controller
address - this needs to be same as value of Terminal Comm Address (page 393).
IMPORTANT: Never fill Access code!
IMPORTANT: In case of using Ethernet 2 (page 19) you need to fill Username and Password of
actual user account.
You can also select controller from "Detected controllers" feature. If this controller is connected via Ethernet 2
(page 19) you will be prompted to fill Username and Password of actual user account.
Use IP address which is stored in proper value (based on selected Ethernet peripheral) and fill Controller
address - this needs to be same as value of Terminal Comm Address (page 393).
IMPORTANT: Never fill Access code!
IMPORTANT: In case of using Ethernet 2 (page 19) you need to fill Username and Password of
actual user account.
AirGate connection
You may connect to the controller using AirGate which works only via Ethernet 2 (page 19). If the AirGate key in
the Access Administration is empty the controller will not connect to the AirGate despite the function is enabled.
Access Administration is available in Tools of the InteliConfig.
Setpoints and values related to connection via AirGate:
AirGate Connection (page 416) - has to be ENABLED
AirGate Address (page 678) - manually adjusted address of AirGate server
AirGate Port (page 417) - manually adjusted port for communication between Controller and AirGate
server
AirGate Status (page 911) - has to be connected, operable
AirGate ID (page 911) - 9 numbers long ID of the controller
Use AirGate ID, AirGate server with proper port (54441 for global.airgate.link), AirGate Key and Controller
address - this needs to be same as value of Terminal Comm Address (page 393). Valid user account -
Username and Password - is required for the connection.
IMPORTANT: Never fill Access code!
Note: Ask your administrator for AirGate Key. Administrator can always change the key via InteliConfig using
"Tools -> Access administration -> Change AirGate key"
Use AirGate ID, AirGate Server with proper port (54441 for global.airgate.link), Device Access Key and
Controller Address - this needs to be same as value of Terminal Comm Address (page 393). Valid user
account - Username and Password - is required for the connection.
IMPORTANT: Never fill Access code!
General commands for Access lock can be found in List of commands and arguments (page 324)
Alarm states
An alarm can have following states:
Active alarm: the alarm condition persists, alarm delay has elapsed.
Inactive alarm: the alarm condition has disappeared, but the alarm has not been confirmed.
Confirmed alarm: the alarm condition persists, but the alarm has already been confirmed.
Visual interpretation of alarm is decided by terminal side. Commonly for active alarms whole row background
is colored (yellow/red/blue). Inactive alarms have transparent background color and text is colored
(yellow/red/blue)
Alarm Level 1
The level 1 alarm indicates that a value or parameter is out of normal limits, but has still not reached critical level.
This alarm does not cause any actions regarding the BESS control. For whole list see Alarms level 1 (page
1245)
Alarm Level 2
The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached. For
whole list see Alarms level 2 (page 1278)
Note: It is not possible to start the BESS if any red level protection is active or not confirmed.
IMPORTANT: The BESS can start by itself after acknowledging the alarms if there is no longer an
active red alarm and the controller is in AUTO mode!
Terminal Event message Alarm messages (Subgroup: Messages Settings (page 685))
RS485 NO NO
USB NO NO
Ethernet YES YES
Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a new
alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms
ECU alarms
ECU alarms
The ECU alarms are received from the Electronic Control Unit. The alarms are represented by the Diagnostic
Trouble Code, which contains information about the subsystem where the alarm occurred, the alarm type and the
alarm occurrence counter.
The most common fault codes are translated into text form. Other fault codes are displayed as a numeric code
and the ECU fault codes list must be used to determine the reason.
For the InteliNeo6000 the AMF function is used only for automatic Mains failure and healthy detection. There is
no emergency start related to the technology when Mains fails because it is expected that renewables and BESS
are already running.
Related setpoints are:
An output for control of a contactor. Its state represents the breaker position requested
Close/Open by the controller. The breaker must react within 2 seconds to a close or open command,
otherwise an alarm is issued.
An output giving a 2 second pulse in the moment the breaker has to be closed. The
ON coil
output is intended for control of close coils of circuit breakers.
An output giving a pulse in the moment the breaker has to be opened. The pulse lasts
OFF coil until the feedback deactivates, but at least for 2 seconds. The output is intended for
control of open coils of circuit breakers.
The BCB UV coil output is active the whole time the BESS is running. The MCB and
PVCB UV coil output is active when the controller is switched on. The output is
UV coil
deactivated for at least 2 seconds in the moment the breaker has to be switched off. The
output is intended for cont rol of undervoltage coils of circuit breakers.
When binary output breaker close/open is opened, there is 2 seconds waiting time for feedback If
feedback doesn't match, the alarm Sd BCB Fail To Open (page 1291)/Wrn MCB Fail To Open (page
1256) is issued.
When binary output breaker close/open is closed there is 2 seconds waiting time for feedback. If the
feedback doesn't match the output, close/open is opened and closed again after delay defined by setpoint
Delay Between Closing Attempts (page 370). If feedback doesn't match after second try and 2 seconds
delay elapsed, the alarm Sd BCB Fail To Close (page 1291)/Wrn MCB Fail To Close (page 1255) is
issued.
Note: In case of using both feedbacks (standard and negative), both of them have to be in correct position,
otherwise breaker fail is issued after 500 ms.
A new alarm ALI GCB Closing Is Blocked (page 1) is activated in case Setpoint BCB Control Mode
(page 369) is set to Internal and any of following generator protections are switched to Disabled
Generator <f Protection
Generator >f Protection
Generator <V Protection
Generator >V and >>V Protection (both overvoltage must be disabled)
Short Circuit Protection
EACH
The EACH option should be used if each Gen-set has its own neutral contactor. The NCB CLOSE/OPEN (PAGE
1094) output on each Gen-set is given by an internal algorithm, which ensures, that always exactly one Gen-
set connected to the bus with the lowest CAN address has the neutral contactor closed.
Four-pole MCB, MGCB, and GCBs have to be used in this case - all running Gen-sets that are not
connected to the bus have their own NCB closed.
The output is always opened while the Gen-set is not running.
The output is always opened while the MCB + MGCB (only for MGCB application) + GCB are closed
(Genset is running parallel to Mains).
The output is closed while the Gen-set is running and at least one Generator Ph-Ph voltage exceeds 85%
of the nominal voltage. It opens when the generator voltage in all phases drops below 50% of the nominal
voltage.
Note: LBI NCB FEEDBACK (PAGE 1015) and LBO NCB CLOSE/OPEN (PAGE 1094) has to be configured for
proper functionality.
Note: For both option the MGCB is taken in account only if there is any extra breaker between GCB and the
MCB.
To activate the CAN bus log function, go to the Tools in InteliConfig and press the button CAN Bus Log to open
the settings. You need to log in as at least a level 2 user. In the settings, you will choose the Output directory in
your PC, the Logging option (CAN for modules + communication speed or type of the Intercontroller CAN), and
press Start. The Logging status will be changed from Logging is stopped to Logging is running.
Relevant setpoints
CAN Controller Address (page 392)
CAN Intercontroller Comm Mode (page 397)
Usage
Power Management (page 274)
Power Management (page 274)
Power Management (page 274)
Power Management (page 274)
MINT - Load Sharing, Var Sharing, and Shared signals
This function duplicates whole Intercontroller communication, which is on CAN2A (page 19) and sends it via
CAN2B (page 19).
The same wiring principles apply to CAN2B (page 19) as to CAN2A (page 19) (see CAN bus wiring (page
71)).
If the setpoint CAN1 ECU/IOModules Split (page 402) is enabled, the behavior of CAN1A terminal is changed:
CAN1A terminal can be used only for communication with ECU
CAN1B terminal can be used only for communication with IO Modules
IMPORTANT: In case that CAN1 ECU/IOModules Split (page 402) is enabled, the Hot Swap
Redundancy (page 371) is disabled (and vice versa).
Note: The splitting of CAN1 enables to prevent overloading the bus line.
The physical group of the controllers (i.e. the site) can be separated into smaller logical groups, which can work
independently even if they are interconnected by the CAN2 bus. The logical groups are intended to reflect the
real topology of the site when the site is divided into smaller groups separated from each other by bus-tie
breakers. If the bus-tie breakers are closed the sub-groups have to work as one large group (system) and if the
bus-tie breakers are open, the sub-groups have to work independently.
The group which the particular controller belongs to is adjusted by the Control Group (page 516). Use
the default setting 1 with all controllers, if there is no bus-tie breaker.
The information which groups are currently linked together is being distributed via the CAN. Each
controller can provide information about one BTB breaker. The breaker position is detected by the input
function GroupLink (i.e. this input is to be connected to the breaker feedback).
The two groups which are connected together by the BTB, are defined with parameters Group Link L
(page 517) and Group Link R (page 517).
Controller sends via CAN2A (page 19) (CAN2B (page 19)) bus information that controllers from groups
Group Link L and Group Link R are linked together.
If external BTB is used (there is no CAN communication between external BTB and other controllers) or in
case of redudant information about BTB position is required , the Group link function in any ComAp
controller can be used. If the LBI GROUP LINK (PAGE 1004) is activated the controller will send information
to all controllers on CAN that the groups defined by setpoints Group Link L (page 517) and Group Link
R (page 517) are connected together.
A history record is written into every controller that is affected by the group link whenever the BTB is
closed / opened (control groups are linked / unlinked).
Note: The "group link" function is independent on the group, where the controller itself belongs to. The controller
can provide "group link" information about any two groups and it may not belong to one of the groups.
All controllers in linked groups cooperate with each other and perform Power Management, Load sharing
and VAr sharing together. Thementioned functions are performed independently in each group, when the
groups are separated.
Once the BTB breaker is closed, the control groups 2 and 3 become new group 2+3. Power management, Load
sharing and VAr sharing are performed within newly established group 2+3. Merging of the groups may result in
a BESS/BESS stopping, if power management evaluates that available Actual Reserve is high enough to stop a
BESS/BESS.
In top right corner click wrench icon and select "Collect logs".
InteliConfig begins to collect Crash Dump data from the controller and also adds its own crash logs. User
is informed about the ongoing process in InteliConfig, before prompt to save *.zip file appears.
Note: It is recommended to use connection via Ethernet to reduce time required for data collection.
Note: In case the InteliNeo6000 cooperates with controllers which CAN Intercontroller Comm Mode (page
397) doesn't support 64C CAN FD, the maximum units in power management is 32.
Signals which are considered to be visible the same way for every controller on CAN. Synchronization of these
signals is the internal part of the Power management function.
Basic principle:
For every signal, there is a LBI with the same function as the signal.
If the LBI is not configured on any input (physical binary, virtual in PLC etc.), its value is taken from CAN
and the value is not being shared back on CAN.
If the LBI is configured, its value is taken from the input and the value is shared on CAN.
The relevant function is activated only by the state of the signal, which is configured on LBI. That
means that function cannot be activated by the state of relevant CAN signal.
In case of the collision, there is a predefined behavior. If any controller with configured LBI receives a
logical "1", it then activates the signal on CAN.
Distributed Power Management Signals are shared only in the scope of logical Control Groups (page
136). If you merge Control Groups together (GROUP LINK (PAGE 1004)), signals are applied in both groups.
The BTB controller is used to connect the groups together. When the Bus Tie Breaker is closed the BTB
informs appropriate controllers that their groups has been connected.
System
Start/Stop
Min Run
Power 1, 2, 3
Load Res 1,
2, 3, 4
Sharing of multiple Logical Binary Input (LBI) functions is critical for power management system operation,
because several power management functionality require simultaneous activation of LBI functions in controllers,
which are involved in power management operation. It can be done either automatically using CAN2A (page 19)
(CAN2B (page 19)) bus link between controllers or using dedicated LBI functions.
These LBI functions are shared automatically:
System Start/Stop
Min Run Power Act
Load Res Active
MCB Feedback
The following rules applies to the automatic sharing of the selected signals between Mains / Gen-set /
Microgrid controllers.
2. LBI state received from CAN2A (page 19) (CAN2B (page 19)) bus is automatically used, if corresponding
LBI function is not configured in a controller.
Example: LBI Remote Start/Stop is not configured with a controller, but automatically shared System
Start/Stop is received from CAN2A (page 19) (CAN2B (page 19)) bus. Controller follows state of the
shared LBI signal then.
5. LBI function can be configured with multiple controllers, which transmit through CAN2A (page 19) (CAN2B
(page 19)) bus state of the function. Or function applies to the function evaluation in controllers, in which the
function is not configured. It means that function is activated by shared signal coming from any controller (rule
4. applies).
5.4.14 E-STOP
The E-Stop is mainly used for emergency stop of the BESS but it is also used as power supply for binary outputs
1 and 2. These binary outputs are designated for some essential functions and they are internally wired as "safe".
It means, that their deactivation is directly binded with the dedicated Input ㉓ E-STOP (page 47) (not evaluated
as the LBI in the controller). These outputs are fully configurable and in the default configuration are used for the
BESS Run Request.
The emergency stop circuit must be secured.
No accidental activation on the PCB can disable the operation of the emergency stop.
The power supply of the associated binary outputs (BOUT1 and BOUT2) is supplied by the ㉓ E-STOP
(page 47) input, not by the + battery voltage.
The CU is measuring actual input voltage of the E-STOP which activation level depends on the actual controller
supply voltage (battery voltage). The E-STOP is activated if input voltage drops below approximately 60 % of the
Controller supply voltage.
If the input voltage of E-stop is higher than high comparison level (for ex. higher than 80% of the supply
voltage), then E-stop is not activated.
If the input voltage of E-stop is lower than low comparison level (for ex. lower than 60% of the supply
voltage), then E-stop is activated.
If the input voltage of E-stop is located somewhere between low and high comparison levels (for ex.
between 60 and 80 %of the supply voltage, then E-stop binary value will stay on its previous state (means
E-stop binary value will not change).
Visualization on CU screen
1
㉓ E-STOP (page 47) has voltage - state is OK, BO1 and BO2 can be activated
0
㉓ E-STOP (page 47) has no voltage - E-STOP (page 1280) is active, BO1 and BO2 cannot be
activated
For wiring information see E-Stop on page 66.
Modifying a setpoint
Fault Reset
Horn Reset
Start/Stop
Configurable history
It is possible to configure the columns (values) which will be displayed in the History window. The
configuration can be found in the Controller Configuration → Others → History. See the picture below.
In the left part of the configuration window there are all available binary and analog values (columns) which
can be configured to history event log. In the right side of the configuration window there is a table with all
already configured columns. By buttons Add and Remove in the middle of the configuration window or by
Premortem History
The fast history running in background is mirrored into the controller history records when a second level alarm
occurs. Premortem history contains the same values in the history as the configuration done by configuration
tool. When any new alarm appears for the second time, only the new history records are added into the controller
history log. Premortem History is filled in to internal buffer (16kB) and number of premortem records depends on
how many history columns is configured. Example: for default History columns it can be up to 85 premortem
records, for maximal History columns can be saved in to buffer at least 32 records.
The time of the premortem history is adjustable by a setpoint Premortem History Period (page 631)
Related setpoints for choosing of the timer function: Related setpoints for the timer setup:
Timer 1 Function (page 633) Timer 1 Setup (page 634)
Related LBOs:
Exercise Timer 1 (page 1077) Exercise Timer 7 (page 1078)
Exercise Timer 2 (page 1077) Exercise Timer 9 (page 1079)
Exercise Timer 3 (page 1077) Exercise Timer 9 (page 1079)
Exercise Timer 4 (page 1078) Exercise Timer 10 (page 1079)
Exercise Timer 5 (page 1078) Exercise Timer 11 (page 1080)
Exercise Timer 6 (page 1078) Exercise Timer 12 (page 1080)
Exercise Timer 7 (page 1078)
Exercise Timer 9 (page 1079)
Related Values:
Exercise Timer 1 (page 902) Exercise Timer 7 (page 904)
Exercise Timer 2 (page 903) Exercise Timer 9 (page 1079)
Exercise Timer 3 (page 903) Exercise Timer 9 (page 904)
Exercise Timer 4 (page 903) Exercise Timer 10 (page 905)
Exercise Timer 5 (page 903) Exercise Timer 11 (page 905)
Exercise Timer 6 (page 904) Exercise Timer 12 (page 905)
Mode Once
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.
Mode Daily
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634)
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.
In timer mode select Repeat. In repetition type select Daily. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th day of repetition
and behavior of timer on weekends.
Example: On image example first start of timer will be 2015-01-01 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 3rd day at 12:00 for 5 minutes including weekends.
Mode Weekly
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.
In timer mode select Repeat. In repetition type select Weekly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th week of repetition
and days when timer should be active.
Example: On image example first start of timer will be 2015-01-12 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 2nd week on Monday, Wednesday and Friday at 12:00 for 5 minutes.
Monthly mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.
There are two types of monthly repetition. First of them is based on repeating one day in month.
In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition and the x-th day of repetition. Than select the x-th month of repetition.
Example: On image example first start of timer will be 2015-01-02 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 2nd day in 2nd month at 12:00 for 5 minutes.
In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition, the x-th week of repetition and days in week. Than select the x-th month of repetition.
Example: On image example first start of timer will be 2015-01-05 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 2nd week in 2nd month on Monday, Wednesday and Friday at 12:00
for 5 minutes.
In timer mode select Repeat. In repetition type select Short period. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the interval of repetition
(shorter than 1 day).
Example: On image example first start of timer will be 2015-01-01 at 12:00. Duration will be 1 hours.
Timer will be again activated every 4th hour for 1 hour.
Example:
Adress: 192.168.1.100
Netmask: 255.255.255.255
Port: 502
Only the single computer with IP address 192.168.1.100 can connect to MODBUS/TCP server
IMPORTANT: When enabling the firewall, If the rules are not set up properly and the connection is
made remotely, loss of connection can happen.
IMPORTANT: You cannot change value of setpoint which has active Forced Value function.
InteliConfig
Note: Setpoints that are currently being forced their arrow turns to green color and they also have the option
for writing of different value manually disabled.
InteliConfig
Note: Setpoints that are currently being forced their arrow turns to green color and they also have the option
for writing of different value manually disabled.
List of already configured Forced Values for specific setpoint. First row has highest priorit.
Options for adding, removing and editing Forced Values and options for changing order.
Hot Swap Redundancy is a feature designed to increase the reliability of the control system. Its principle is
based on the fact that the control system consists of two pair controllers, "MASTER" and "BACKUP". The
BACKUP controller is ready to take over the control of the BESS anytime when MASTER controller fails.
Assumptions: We assume that both pair controllers have the same information about the controlled system that
they obtain through their inputs and communication lines. This information is supplemented by so-called
synchronization data, which the MASTER controller sends via the Hot Swap Synchronization Line. The second
fundamental assumption is that both controllers have the same configuration in terms of control functions.
Detection of failure of the pair controller and speed of the transition: The BACKUP controller evaluates
the competence of the MASTER controller via a heartbeat signal. Due to its high frequency BACKUP is able to
detect MASTER failure quickly enough to be able to respond in a way that the entire system does not register the
transition to BACKUP at all. This usually happens approximately in 3 ms. The LBO Hot Swap Heart Beat of
MASTER controller must be interconnected with the LBI Hot Swap Heart Beat Detect of the pair BACKUP
controller and vice versa. So, both controllers monitor each other and they are ready to respond accordingly.
Polarity of binary inputs: The polarity of the Hot Swap Heartbeat pulse signal requires that the controller
binary inputs has to be set to the "Pull Down" configuration.
Powering
We recommend a 24V power supply system for the Hot Swap system. The MASTER and BACKUP
controllers should be powered from an independent source.
Binary inputs
The binary inputs (with the exception of the control binary inputs of the Hot Swap function) always lead to
both pair controllers at the same time, in the same position without the need of separation by relays. It is
recommended to separate the inputs by diodes to avoid wrong input activation when one controller is
switched off - see Binary Inputs on page 64.
The binary inputs must be set to "Pull Down" polarity on both controllers.
Binary outputs
It is strongly recommend to connect the binary outputs controlling the technology via a pair of relays with a
disconnecting function. This ensures that a controller that is defective cannot disturb the operation of the
application under any circumstances.
Analog inputs
The analog inputs must be connected via paired relays with a switching function. The exception is the
configuration where the analog inputs are set as voltage 0-10 V.
Analog outputs
The analog outputs controlling the technology, namely AOUT1 and AOUT2, must be connected via a pair
of relays with a switching function.
Communication lines
Technological lines CAN1A (ECU and I/O modules), CAN2A (Intercontroller Communication), CAN2B
(Rendundant Intercontroller Communication). These lines are recommended to be connected to both pair
controllers via relays with disconnecting function.
The ETHERNET 3 (technology line with function Modbus Client) is connected to both controllers in the
classic way at the same time. The IP address of the pair controllers on this line must be different. In the
case of using the hotswap function, it will happen that when the master controller fails, backup controller
will start taking care of the device on the modbus. Hotswap function is only possible if the Modbus master
is connected via Ethernet (TCP). Both controllers read the same values via modbus, but only one writes.
At the moment of switching to backup controller, the roles of writing and controlling are changed.
Terminal lines ETHERNET 1, ETHERNET 2 are connected to both controllers in the classic way at the
same time.
RS485 (Modbus Server/Master communication) is connected to both controllers in the classic way at the
same time. Both pair controllers has different device address on this line. In case of connection via RS485
Display
The Hot Swap system does not support a common display for both paired controllers. Each controller is
equipped with its own display.
Fault Reset
The Fault Reset button signal is propagated from the controller which is currently in active role to the
controller which is currently in listening mode via the Hot Swap Synchronisation Line.
Note: This is only quick illustration for I/O configuration, see the InteliConfig manual for more information
about configuration via PC tool InteliConfig.
Binary Inputs
The configuration of the binary input consists of:
1. Name - the name identification of the binary input
2. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)
3. Functions - the set of functions see Functions Configuration on page 170
4. Protections - the set of protections see Protections Configuration on page 170
Binary Outputs
The configuration of the binary output consists of:
Analog Inputs
The configuration of the analog input consists of:
1. Name - the identification name of the analog input
2. Sensor - sensor used for the analog input see Sensor Curves on page 216
3. Dimension - dimension used for analog input (Can be set directly in form if the electronic sensor is
configured, otherwise it can be set in sensor configuration.)
4. Resolution - resolution used for analog input (Can be set directly in form if the electronic sensor is
configured, otherwise it can be set in sensor configuration.)
5. Sensor Range - range used for linear sensor (Range for measured values is defined by Offset + Sensor
Range)
6. Offset - offset used for linear sensor
7. Bargraph 0% - lower bargraph limit displayed on the controller display
8. Bargraph 100% - upper bargraph limit displayed on the controller display
9. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)
10. History Abbreviation - shortcut used in the History.
11. Functions - the collection of functions see Functions Configuration on page 170
12. Protections - the collection of protections see Protections Configuration on page 170
Analog Outputs
The configuration of the analog output consists of:
1. Source - the source value for the analog output
2. Output Curve - definition of the transferring output curve
a. The output curve is not available if the "No Conversion" parameter is checked.
3. No Conversion - Define whether the source value is converted by the output curve or not
4. PWM Frequency - setting of the PWM frequency
a. The PWM frequency can be set only if the output curve is a type of PWM.
5. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)
IMPORTANT: Output Curves are in Int16 format (range -32768 to 32767). Therefore if the source
value is a decimal value, the range is reduced accordingly.
Example: When BESS Frequency (page 713) (0.001 resolution) is used as a source value, it has to be
converted to a lower resolution in PLC (e.g. 0.01) in order to work correctly. Otherwise the upper level of
the curve's input would be cut to 32.767.
Each function (LBI) has the link to the help through button
Protections Configuration
It is possible to assign one level 1 and level 2 protection to the specific input or output (BINT, BOUT, AIN).
Remove protection
Edit protection
For more information about protections see Protections on page 197
Stage LBO
Stage 1 LOAD SHEDDING STAGE 1 (PAGE 1085)
Stage 2 LOAD SHEDDING STAGE 2 (PAGE 1085)-
Stage 3 LOAD SHEDDING STAGE 3 (PAGE 1086)
Stage 4 LOAD SHEDDING STAGE 4 (PAGE 1086)
Stage 5 LOAD SHEDDING STAGE 5 (PAGE 1086)
Stage 6 LOAD SHEDDING STAGE 6 (PAGE 1087)
Stage 7 LOAD SHEDDING STAGE 7 (PAGE 1087)
Stage 8 LOAD SHEDDING STAGE 8 (PAGE 1087)
Reconnection of load
Disconnected load can be also reconnected. Reconnecting of stages is in descending order and begins with
highest disconnected stage. Behavior of this function is adjusted via setpoints Auto Load Reconnection (page
602), Power Load Reconnection Level (page 604) and Load Reconnection Delay (page 602).
Manual reconnection
Conditions:
Setpoint Auto Load Reconnection (page 602) = Manual
LBI MANUAL LOAD RECONNECTION (PAGE 1011) has to be configured
When relative BESS P (page 707) drops below Power Load Reconnection Level (page 604) rising edge of
LBI MANUAL LOAD RECONNECTION (PAGE 1011) reconnects the highest disconnected stage.
Note: Setpoint Load Reconnection Delay (page 602) is not considered
MCB BCB
Vector Vector Shift
STATUS STATUS
Shift/ROCOF CB Protection Action
(PAGE (PAGE
Selector (page 522) (page 593)
1092) 1060)
Enabled or Opens MCB or BCB based on
1 1 MCB or BCB Parallel Only(no Vector Shift/ROCOF CB Selector
influence) (page 522)
Enabled or
MCB or BCB (no No action (BCB stays always
0 1 Parallel Only(no
influence) closed)
influence)
MCB or BCB (no
1 0 Parallel Only No action (MCB stays closed)
influence)
If a vector shift is detected and consequently the MCB is opened, however Mains voltage and frequency remain
in limits, the MCB is then closed again (synchronized) as the Mains is evaluated as healthy.
If a vector shift is detected and consequently the BCB is opened, however Mainsvoltage and frequency remain in
limits, the BCB is then closed again (synchronized) immediately (no delay).
ROCOF
The Rate of Change of Frequency function is the fast protection for Mains decoupling (loss of Mains). It monitors
the change of frequency and if it gets changed dramatically, the protection is issued.
There are in total 4 independent ROCOF protections devided to 2 kinds.
Common behavior
Protections are enabled/disabled by setpoints ROCOF1 Protection (page 594), ROCOF2 Protection (page
595), ROCOF3 Protection (page 596) and ROCOF4 Protection (page 597).
Vector Shift/ROCOF CB
Option Behavior
Selector (page 522)
MCB Protection is reactivated with closing of MCB
Enabled
BCB Protection is reactivated with closing of BCB
Parallel Protection is reactivated with entering Parallel Operation
Not relevant
Only Mode Breaker state (page 886) = ParalOper
Mains Measurement P
If Mains Measurement P (page 364) = Mains CT then Mains Import P (page 842) is counted from the
current which is measured on ⑰ AUX CURRENT (page 47) .
If Mains Measurement P (page 364) = Analog Input then Mains Import P (page 842) is taken from LAI
MAINS MEASUREMENT P (PAGE 1124). Mains current can still be measured if Mains Measurement Q
(page 365) = Mains CT.
If Mains Measurement P (page 364) = None then Mains Import P (page 842) is not counted because
there is no current measurement. This affects load transfering.
Note: When Mains Measurement P (page 364) is set to None or Analog Input (and LAI MAINS
MEASUREMENT P (PAGE 1124) is not configured or has invalid value) alarm Wrn Load IMP/EXP Fail (page
1253) is activated if Import/Export P is required and alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated
if Import/Export Q is required.
MainsMeasurement Q
If Mains Measurement Q (page 365) = MainsCT then Mains Import Q (page 843) is counted from the
current which is measured on ⑰ AUX CURRENT (page 47) .
If Mains Measurement Q (page 365) = Analog Input then Mains Import Q (page 843) is taken from the
LAI MAINS MEASUREMENT P (PAGE 1124). Mains current can be still measured if Mains Measurement P
(page 364) = Mains CT.
If Mains Measurement Q (page 365) = None then Mains Import Q (page 843) is not counted because
there is no current measurement. This affects load transferring.
Once the device is added into the configuration there are the same options for extending the definitions of
inputs and outputs configuration as for user device. All custom inputs and outputs will be always signed by "
(User)" suffix after the name of the signal. This is the way how to recognize custom definitions from ComAp
definitions which can not be edited and how to prevent creating duplicity signals by user definitions.
Insert the name and select the target folder for exporting data. You will be informed about successful
exporting of your device definition.
After that select the icon for importing data in a new configuration.
Select one of your Modbus Server Device definition files and Import it into the configuration for a new instance
of your device.
For each ECU there is LBO which gets activated when communication issue with respective ECU is detected.
For easier detection whether all configured ECUs are communicating, there is LBO ECU COMM OK (PAGE 1074).
During detected communication issue an alarm is issued for respective ECU.
All protections which evaluation depends on values from the ECU with communication error are blocked in order
to pervent showing of invalid protections in the Alarm list.
The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
Remote OFF (page 1027)
Remote MAN (page 1027)
LBI
Dedicated LBIs to change mode have higher priority than the setpoint. When LBI is activated th setpoint is
unchanged.
When all LBIs are deactivated controller mode is changed to one that is in Setpoint Controller Mode (page
385).
LBO
There is a dedicated LBO for each mode.
MODE OFF (PAGE 1094)
MODE MAN (PAGE 1093)
MODE AUTO (PAGE 1093)
OFF
Start of the BESS is blocked, the controller will stay in Not Ready state, and starting command cannot be issued.
If the BESS is already running, it is not possible to switch directly to the OFF mode. Firstly you have to stop the
BESS and after that switch to the OFF mode.
For MPTM application, if Mains is healthy and MCB is opened, then MCB is automatically closed after the delay
given by setpoint MCB Close Delay.
No Power management function will be performed. The buttons MCB ON/OFF , BCB ON/OFF , START
, and STOP including the appropriate binary inputs for external buttons are not active.
Note: When BESS is running, it is not possible to switch the controller to OFF mode.
AUTO
BESS is controlled based on external signal (GENERIC GENSET START/STOP (PAGE 1004) ) or by conditions (Peak
shaving, Power management system, etc.). When one condition deactivates the BESS does not stop if another
condition for automatic starts is active. System Start/Stop can be received from other controllers via Intecontroller
Communication.
The controller does not respond to the buttons START, STOP, MCB ON/OFF, and BCB ON/OFF.
If peak shaving stop condition occurs, but GENERIC GENSET START/STOP (PAGE 1004) is active, BESS stays
running.
IMPORTANT: If a red alarm is present and the controller is in the AUT mode, the BESS can start by
itself after all red alarms become inactive and are acknowledged (fault reset is pressed)! To avoid
this situation, adjust the setpoint Fault Reset To Manual (page 386) to the Enabled position.
IMPORTANT: BESS will start if at least one external signal or condition is fulfilled.
The Programmable Logic Controller (PLC) built into the ComAp controllers is generally a simple process unit
used for the automation of processes. The major benefit of the PLC is you don’t need any extra control
devices in your control system. The PLC is tightly integrated with the standard line of controllers. That allows
the PLC editor to be a seamless experience directly in the programming software. Flexibility is at the core of
ComAp's software design and the PLC meets both simple and complex application requirements while using
the same intuitive interface. PLC Editor is a powerful tool that helps you to create your own PLC scheme. It
has a user-friendly graphical interface which makes it easy to use.
ComAp PLC Editor has been developed to help you deal with even the most demanding applications. It
allows you to add control logic, additional alarm functions, or even new features to meet complex or unique
requirements. This easy-to-use PLC Editor means you can customize the way the controller works to match
the application precisely without compromise or limitation.
Toolbar
In the upper part of the PLC editor panel there is a toolbar with buttons for working with PLC blocks and PLC
sheets.
Note: To see context help for selected PLC block just press F1 button.
Inputs
Sheet inputs are located at the left side of a sheet. Follow the procedure below to add or edit an input.
Double-click on a free input position or existing input to add new input or edit the existing one.
Select the source for the input.
If you create a binary input, you can select a source from following categories:
Bin. Values - this category contains all binary values available in the controller as binary inputs, logical
binary outputs etc.
PLC Outputs - You can connect any PLC Output to another PLC Input.
If you create an analog input, you can select a source from following categories:
Ana. Values - this category contains all analog values available in the controller as analog inputs,
electrical values, values from ECU etc.
All Setpoints - this category contains all setpoints of the controller except the dedicated PLC setpoints.
Names, resolutions and dimensions of these setpoints can not be modified.
Note: It is necessary to click on the Connect button after selecting the output. Otherwise PLC output is not
connected to output.
Creating wires
Wires can be created between PLC inputs and PLC block inputs, PLC block outputs nad PLC block inputs, or
PLC block outputs and PLC outputs.
Follow the procedure below to create wire.
Locate the mouse pointer over the starting point of the wire (dot). If the area under the mouse pointer is a
connection point, the connection point changes to bold dot.
Press and hold the left mouse button and drag the wire to the destination of required connection point
(from dot to dot connection). If you point over a valid connection point, the connection point changes to
bold dot.
Note: To delete wire just click on it and press delete button. Also delete selection function can be used.
IMPORTANT: In case that values on inputs have different decimal numbers than the values are
converted and the name of block is displayed as red in the PLC Monitor. It is strongly
recommended to fix the configuration = use the signals/values with the same range and decimal
numbers.
IMPORTANT: Please always check that the blocks are ordered correctly, especially if you use direct
feedbacks from outputs to inputs within one sheet. Wrong order may lead to incorrect results!
The execution order is Item 1 → Item 2 → Item 3, so in the second case the AND block evaluation will use
Timer block output before the update.
PLC monitor
PLC monitor is a powerful tool for monitoring your PLC. Just click on PLC Monitor button on main InteliConfig
page to see you PLC in the run time. The refresh rate is given by the system integration. The PLC Monitor is
available in InteliConfig Control tab.
PLC monitor supports working with multiple controllers - on the left side of the panel there is a selection tree for
choosing the desired controller for PLC monitoring.
Note: In the PLC Monitor it is not possible to modify the PLC, not even the position of the blocks.
Active binary inputs, outputs and wires are blue, analog inputs, outputs and values are green. The values of
analog signals (as well as constants set in the blocks configuration) are also visible.
Note: If the analog signal have an invalid value, the red "####" string is displayed and the connecting wire is
also red.
The PLC monitor also supports multi-sheet monitoring - individual sheets can be hidden/expanded using the
button in the top title bar.
Other functions
Consistency check
This performs a check of the PLC schematic
for the validity of the block interconnection = all inputs that are in internal design rules marked as
mandatory are connected and/or configured
for the consistency of the dimensions (setting attribute Dimension) and the number of decimal place
(setting attribute Resolution) at both ends of the interconnection wire
Use this function during the design phase to check if all inputs and outputs of PLC block are connected
properly, and the design is consistent. The check is also performed automatically when the configuration may
be written to controller.
If the Consistency Check detect any problems, all findings will be displayed in the message window.
Note: The Consistency Check checks whole configuration so it can report findings outside the PLC
configuration.
Hints
Use this function to enable or disable quick hints for blocks (controller help is not affected by this function).
Note: Each PLC block has help which is opened by selecting the block and pressing "F1".
Units
Metric 20 °C 10.0 bar 11.4 l/h
US 68 °F 145 psi 3.01 gph
Power Format
Small 0.1 kW / kVA / kVAr 1V
Standard 1 kW / kVA / kVAr 1V
Large HV 0.01 MW / MVA / MVAr 0.01 kV
Large LV 0.01 MW / MVA / MVAr 1V
Note: Range of some setpoints and values is changed significantly when different Power Formats are selected.
Affected setpoint are displayed during selection of power format.
InteliNeo 6000 combines Fixed protections (page 200) with User protections (page 205) which allows
users to configure their own protections to any analog or binary input. Multiple protections can be configured
on each analog input, number of configured protections are not limited. Only one protection of 1st level
and/or one protection of 2nd level can be configured on logical binary output. The maximum number of
configured User protections (page 205) is limited to 200. The maximum number of configured fast User
protections (page 205) is limited to 50.
Action: CB open
SD Override blocking
Alarm List +
History Alarm List
Name Warning Alarm Only History Record
Record Only Indication
Indication
Abbreviation Wrn Al Hst ALI AHI
Alarm List indication
History record
LBO COMMON ALARM ACTIVE LEVEL 2 (PAGE 1065) ; except Mains Protection
History record
Action: CB open
SD Override blocking
6 back to Protections
* Fault state can occur if there is loss of communication with configured CAN module.
6 back to Protections
Protection blocking
It is possible to configure one Protection Blocking to any User protections (page 205). This function is used to
block certain protections when their function is unwanted or meaningless. Each user protection has an option to
set the blocking condition.
The blocking conditions can be also applied on the Fixed protections (page 200).
General protections
Each of the LBI Protection Force Disable 1 is paired with an option of protection condition "Force Block 1–3" and
can be used for Blocking / Disabling of protections, however on user defined protections the option causes
protection Blocking instead of Disabling.
Fixed protections
Some selected fixed protections has an option to DISABLE the protection.
The setting is done by using the setpoint which is associated to the fixed protection. Each setpoint offers these
options.
Setpoint options
Alarms Fixed Protection States
Enable Protection is enabled
Disable Protection is disabled
PROTECTION FORCE DISABLE 1 (PAGE 1016)
Disabling of the protection can be forced by LBI
PROTECTION FORCE DISABLE 2 (PAGE 1017)
User protections
Source upon which the protection is configured can be selected. It can be any analog value or binary state.
Source
Analog values Binary states
Analog inputs Binary inputs
Controller, Modules Controller, Modules, ECU, Shared I/O
Values Modbus server, Modbus Master
ECU, Measured values, Application, Binary outputs
PLC, Shared I/O PLC
Modbus server, Modbus Master Protection states
Statistics LBOs
Selecting if the occurrence of a protection is recorded every time or only once after a Fault
Reset.
If Protection State is checked the protection is then shown in setpoints under the group User
setpoints.
6 back to Protections
Protection states
Protection states is a new feature introduced inInteliNeo 6000, which helps with better management of alarms.
Until now, you could only use LBO ALARM (PAGE 1053) which did not specify what is going on. Protection states
work in similar way, like any other LBO. The difference is, that protection state gets active only when there is
specific alarm present in the alarm list. Thanks to this, you can create PLC logic, which will react to specific
alarms only.
6 back to Protections
Note: Value of the internal counters remains even if the controller is unplugged from power.
Each of these sets can be seen as a separate channel (slot) through which InteliNeo6000 aggregates signals
from individual inverters as PV quantities. InteliNeo6000 supports up to 16 PV inverters in this way. The
configuration, i.e. the binding of these LAI values to the datapoints read from the individual inverters, must be
done manually (the binding is done automatically only in case of a single PV inverter configuration).
Aggregation of all acquired signals into common quantities is already automatic and therefore it is not
necessary to aggregate the common quantities using user logic in the PLC. The common PV quantities can
then be monitored in the controller as PV Aggregated quantities. Incidentally, the quantities integrated by the
individual PV channels can also be monitored in the PV quantity group.
In the case of WT support, the situation is very similar. InteliNeo6000 supports up to 8 WT inverters. The
system aggregates the total quantities of all data which are available. Thus, even just one channel (slot) is
enough to provide valid data. If the device, that is configured to a particular slot, is not communicating, is out
of service or in error (device error and subsequent inability to supply to the common bus is detected by LBI PV
X operable), then its values are simply not included in the aggregated data.
Note: 16 GB Industrial memory card is also available in ComAp portfolio (ComAp product number
OT1C16GBXQX)
The controller is equipped with a ⑤ SD Card (page 46) slot for a possibility of storing large amount of data.
Formatting process
Alarm ALI SD Card Formatting/Mounting (page 1274) is displayed during the formatting process.
After changing the setpoint SD Card File System (page 401) to Format, the controller checks whether the
inserted SD card is supported - ALI SD Card Not Compatible (page 1273) alarm is displayed if it is not. If the
formatting is not successful, the value SD Card Status (page 889) shows Formatting Failed, the alarm ALI
SD Card Not Compatible (page 1273) is activated, and controller will not try formatting process again SD Card
File System (page 401) is automatically set to Mounted).
If the formatting is successful, the SD Card File System (page 401) is automatically changed to Mounted and
the card is ready for operation.
Alarm ALI SD Card Formatting/Mounting (page 1274) is displayed during the mounting process.
In case that it is not possible to read or write to the SD Card, alarm Wrn SD Card Failed (page 1265) is
activated. The alarm is also activated in case the SD card is not inserted. See the value SD Card Status (page
889) for further information about the fail.
Alarm ALI SD Card Full (page 1274) is displayed if value SD Card Free Space drops below 10 %.
In case that the card has a wrong file system, alarm Wrn SD Card File System Failed (page 1265) is displayed.
Therefore formatting process should be performed again.
Note: Curves can be modified via InteliConfig. In InteliConfig are also prepared some standard curves.
2. Use the adjusted sensor with an analog input and the requested HW configuration will be used with the analog
input automatically. There is no need to use a jumper, configured Input HW type is used by controller
automatically.
5.4.35 Sunrise/Sunset
Based on GPS coordinates, date and actual timezone can controller calculate real sunrise and sunset time.
This functionality is enabled/disabled by setpoint Sunrise/Sunset Function (page 631) and works in all
controller modes. Setpoint Sunrise/Sunset Latitude (page 632) and setpoint Sunrise/Sunset Longtitude
(page 632) are automatically set from GPS module. If coordinates are valid. they will be written on the rising
edge of LBI SUNRISE/SUNSET HOME POSITION (PAGE 1029). Otherwise, these setpoints need to be set
manually. Values Sunrise Time (page 901), Sunset Time (page 902), Time To Sunrise (page 902),
Time To Sunset (page 902) are calculated from setpoints Sunrise/Sunset Latitude (page 632) and
Sunrise/Sunset Longtitude (page 632). LBO DAY/NIGHT (PAGE 1069) is active during the day (between
Sunrise and Sunset Time).
5.4.36 Sunspec
SunSpec is an application-layer communications protocol designed to achieve interoperability between
Distributed Energy Resource (DER) components and smart grid applications. SunSpec has not static Modbus
registers, it uses block of registers in predefined order, but for each device is necessary to calculate Modbus
address. Register blocks are in row (where first ends, second starts).
Using of SW Key
Insert your SW Key into setpoint SW Key (page 388)
Restart the controller
Check value SW Key Feature List (page 891) whether functions were unlocked
IMPORTANT: Activation of deep Sea CAN software key will replace ComAp communication protocol
on intercontroller CAN line. This will prevent communication to ComAp controllers connected via
CAN2.
IMPORTANT: Combining third-party genset controllers via Universal Genset Support in IN6000
and IN5500 with InteliGen/InteliSys over CAN communication within one system is NOT
RECOMMENDED.
There can be only one control unit inside the system integrating UGS. That is, single Neo with UGS active
within a system.
For systems where UGS is used with InteliMains, the slip synchronization method in InteliMains is
required for reverse synchronization. Refer to InteliMains Global Guide for on-grid application.
The total group power supported by UGS is limited to 32.8 MW.
All gensets must operate on a common bus.
Communication
InteliNeo 6000 controllers have a Modbus client onboard that can interface over RTU or ethernet to third-party
generator controllers, which will operate in a Modbus server position.
IMPORTANT: For UGS, values need to be written periodically and repeatedly by InteliNeo Modbus
client to genset controllers. Users must check that the relevant Modbus registers can be written
long-term without damage to the device memory.
For communication between third-party genset controller and InteliNeo 6000, the genset controller can be
integrated into the configuration of InteliNeo via the ECU library as a User Defined Modbus device or selected
from the list of available devices.
LAI: Uni Gen The format (resolution) of this value must correspond to
Actual Active Power P, kW R Analog 1…16 Actual the Power Format selected in InteliNeo (0,1 kW, 1kW, 0,01
P MW).
LAI: Uni Gen The format (resolution) of this value must correspond to
Actual Reactive Power Q, kVar R Analog 1…16 Actual the Power Format selected in InteliNeo (0,1 kVAr, 1kVAr,
Q 0,01 MVAr).
LAI: Uni Gen The format (resolution) of this value must correspond to
Nominal Power Rating, kW R Analog 1…16 the Power Format selected in InteliNeo (0,1 kW, 1kW, 0,01
Nominal P MW).
GCB closed - GCB Connected to LBI: Uni Gen
This is information about the UG GCB status. This signal is
the bus and Loaded (in load R Binary 1…16 GCB
supposed to be active anytime the GCB is closed.
sharing) Closed
Genset Loaded - GCB Connected
LBI: Uni Gen This signal notifies InteliNeo that UG loading process has
to the bus but genset is not in soft R Binary
1…16 Loaded finished or is not in unloading process.
load/soft unload process.
This signal is crucial for safe operation if the UG is
supposed to perform energizing of the dead bus. In
InteliNeo it is used as signal blocking closing of the BCB to
the dead bus. InteliNeo propagates this information to all
LBI: Uni Gen other controllers in the system. The closing of the breaker
Closing GCB to dead bus R Binary 1…16 GCB to the dead bus is blocked in all the controllers within the
Closing system until this signal is active.Important: InteliNeo does
not propagate this information towards to other UGS. UGS
must manage this function themselves within the group. It
is strongly recommended to use the hard wiring of this
signal between InteliNeo and UG.
UG Run Request is influenced by Power Management
(Load demand start/Stop) in AUTO mode and is issued
Value: Uni
only if the system needs to start UGS to cover the
UG Run Request W Binary Gen 1…16
requested load reserve.
Run Request
This signal is connected to LBI Universal Genset
Start/Stop must be configured.
This signal is crucial for safe operation in case that UGS is
enabled to close its GCB to the dead bus and make it
energized. The InteliNeo generates a 200ms long pulse
Value: Uni
any time when any controller in the system is about to
Gen 1…16
Block GCB from closing W Binary close the CB to the dead bus. This information must be
Stop GCB
used in UGS to prevent the closing of the GCB to the dead
Closing
bus. It is strongly recommended to hardwire this signal
between InteliNeo and UGS. This signal is connected to
LBI Uni Gen 1...16 GCB Closed.
MCB Status
Feedback – inform
This signal requests UG to switch to P/Q control mode based on
genset it is in
W Binary LBO: MCB Status MCB status signaling on-grid operation. In the UG it should be
parallel to mains
connected to the MCB feedback input.
and operate in P-Q
mode
This LBO is used if UGS is to be reversely synchronized to the
Mains. InteliMains cannot influence UGS directly, so we need to use
the slip synchronization process.LBO Reverse Sync in InteliMains
Frequency offset LBO: Reverse
makes the UGs run with certain slip frequency, and InteliNeo writes
request/nominal W ANA/BIN Synchronization in
offset to the Nominal Frequency setpoint or sends Binary input to
frequency setpoint InteliMains
switch the nominal frequency to the offset value. Configuration must
be via DISTIN/DISTOut modules for sharing this information
between InteliMains and InteliNeo.
This value is to be used as total baseload active power request for
Value: Uni Gen
the group of universal gensets. This value is also distributed to all
Requested P (rel. Requested P or
W Analog universal genset channels as baseload P for each genset e.g. Uni
% / abs kW) Uni Gen Relative
Gen 1 Requested P. Alternatively, it can be associated with the
Requested P
relative value: Uni Gen Relative Requested P.
This value is to be used as total baseload reactive power request for
Value: Uni Gen
the group of universal gensets. This value is also distributed to all
Requested Q (rel. Requested Q or
W Analog universal genset channels as baseload Q for each genset e.g. Uni
% / abs kW) Uni Gen Relative
Gen 1 Requested Q. Alternatively, it can be associated with the
Requested Q
relative value: Uni Gen Relative Requested Q.
Setpoints
When the Universal Gensets (UG) are connected to InteliNeo with setpoint "Universal Genset Address", UG
is recognized as a virtual source in the system. The information about this virtual genset, recognized as a
singular group, can be seen in all genset related information inside the system like CAN 16, CAN 32, GL 16,
GL 32, Reg 16, Reg 32 Values.
Setpoint Group Setpoint Name Recommended Value Description
Universal A unique numerical value must be set for UGS function to be active
Communication Set value +1 to InteliNeo
Genset and recognized as virtual genset by InteliNeo.Values> Universal
Settings Controller Address
Address Gensets will only be visible once this setpoint ≠ OFF.
Option Description
COMMAND The relative User Button is controlled by command from External display (page 79).
The relative User Button is controlled manually via the setpoint. Value of the user button
MAN OFF
is still 0.
The relative User Button is controlled manually via the setpoint. Value of the user button
is still 1.
MAN ON
Note: You should always switch from MAN ON to MAN OFF before switching to
COMMAND, otherwise value of the User Button will be 1 until command is received.
Commands
If relative setpoint is set to COMMAND, the User Button will react to commands sent via button from External
display (page 79). Type of command is selected during controller configuration in Screen Editor.
There are following commands:
Command Description
While this command is selected, pressing the button negate the actual value of the user
ON/OFF
button
While this command is selected, pressing the button sets the actual value of the user
ON
button to 1.
See list of MODBUS comands in chapter List of commands and arguments (page 324).
Types of interfaces
The controller communication interfaces are split into three categories according to what kind of environment the
interface is exposed.
Trusted
Are USB Type B (page 19) and in the default configuration Ethernet 1 (page 19) terminals.
It is expected that these interfaces are operated locally inside a closed environment / infrastructure where
additional measures against misuse or attack take place (e.g. physical access limitation).
Due to nature of this interface less strict cyber-security rules apply at it and that is why Implicit account is
introduced here to make working with the controller simpler.
Untrusted
Is in the default configuration Ethernet 2 (page 19) terminal.
This interface is a general-purpose one and it is expected that it may be exposed to public networks, such
as Internet, which are not under control of the entity operating the controller.
Thus, strict cyber-security rules apply for this type of interface.
The correct user account with password has to be used in order to connect to the controller.
This interface can be also used for SMTP and SNMP protocols.
Modbus
Is in the default configuration Ethernet 3 (page 19) terminal.
This interface is used for Modbus Client (Master) (page 176) or server.
It is expected that this interface is operated locally inside a closed environment / infrastructure where
additional measures against misuse or attack take place (e.g. physical access limitation).
Due to nature of this interface and fact that it is not possible to use it for connection to the controller, less
strict cyber-security rules apply at it.
Example: If Ethernet 1 (page 19) = Trusted, Ethernet 2 (page 19) = Trusted, Ethernet 3 (page 19) =
Trusted, then it is possible to connect 6 ComAp clients and 3 Modbus clients on all three ports in sum.
Example: If Ethernet 1 (page 19) = Trusted, Ethernet 2 (page 19) = Untrusted, Ethernet 3 (page 19) =
Modbus client, then 6 ComAp clients and 3 Modbus clients can be connected to Ethernet 1 (page 19), 8
ComAp clients and 3 Modbus clients can be connected to Ethernet 2 (page 19) and 3 Modbus clients can
be connected to Ethernet 3 (page 19).
User accounts
User account must be created in the controller by administrator before the particular user can login to the
controller.
Note: User accounts must be created for each controller separately and manually. It is not possible to transfer
the accounts from one controller to another.
User login
To login to the controller the username and password must be provided into the login form of the
application (InteliConfig (page 22), WebSupervisor (page 22), External display (page 79) etc.).
Alternatively, at trusted interfaces, it is possible to login using UID and PIN instead of username and
password. This method of login is designed to simplify the login procedure at devices without alphanumeric
keyboard (e.g. InteliVision).
Note: The controller is featured with a protection against brute force attack to user account credentials. For
details please refer to the - Account break protection (page 231)
Implicit account
There is one implicit user account in the system. This user account can not be deleted. This account is
automatically logged in at a trusted interfacewhile communication channel is open and there is not any other
user logged in. The account is fixedly assigned to role 1.
Production mode
The Production mode is intended to simplify manufacturing process for OEMs. While production mode is active
the implicit user is fixedly member of role 0 (administrator role) and alarm Wrn Production Mode (page 1) is
displayed. Practically it means that while production mode is active it is possible to perform any operation with the
controller without any user needed to login.
WARNING: Production mode must be disabled before the controller is put into regular operation.
Note: Production mode can be turned off either from InteliConfig or from InteliVision 5.2.
Administrator account
There may be multiple accounts which are members of the administrator role. There must always remain at least
one account with administrator role.
Note: there must always remain at least one administrator account in the system. The controller will not allow
deleting last administrator account.
Managing accounts
User accounts can be managed from InteliConfig while an online connection to the controller is established. The
right to manage accounts is explicitly and fixedly given only to administrator role (index 0). This right can not be
granted to any other role. The administrator must be logged with username/password and is prompted to re-enter
accounts password before the user management dialog is opened.
IMPORTANT: The total available number of accounts in the controller is 30.
Deleting account
Select the account that has to be deleted and click on “-“ button in the lower left part of the user management
window.
Note: you can not delete your own administrator account unless there is another administrator account present
in the controller.
Password protection
1. If an user performs five consecutive attempts to login using username/password, providing correct
username but incorrect password, the respective user account is blocked for a time period of 1
minute. The attempts count regardless of the interface from which it is performed.
2. During the blocking period it is not possible to login with the respective account (username) from any
interface even if correct password is provided.
3. After the blocking period elapsed next attempt to login with the respective account (username) is possible.
If this attempt fails again the account is blocked again, now for period of 2 minutes.
4. The points 1-3 repeats further, the blocking period is multiplied by 2 in each next cycle. However, the
maximal blocking time is 20 minutes, the blocking time is never higher.
PIN protection
If an user performs ten consecutive attempts to login using UID/PIN, providing correct UID but incorrect PIN,
the user account is permanently blocked for login using UID/PIN. The user must login with username/password
and change the PIN to unblock this login method again.
Interface protection
If anyone performs twenty consecutive attempts to login via one particular interface (e.g.Ethernet 1 (page
19)) and does not neither provide a valid username nor a valid uid the respective interface is blocked for 2
minutes. During this period it is not possible to use that interface for any login. The blocking period is not
progressive in this case.
Note:
Modbus and SNMP clients do not have implicit access to all objects. The access is limited by mapping
tables present in configuration. So, successful writing of an object require that object 1) to be present in
the respective mapping table, 2) to be assigned to the respective role.
Example: If a setpoint X shall be adjustable by Modbus this setpoint must be 1) mapped to a holding
register, 2) assigned to role 8.
Reading data
For each object the Access right "Read" (R) is fixedly granted to each role*. That means reading of data (except
some system objects) is available for any user.
Writing data
For each object the Access right "Write" (W) can be granted to one or more roles (indexes 1..9). For each object
the Access right "Write" (W) is fixedly granted to administrator role (index 0).
Special situations
There are several operations that require administrator role:
Programming firmware
Programming configuration
Managing user accounts. This right can not be granted to any other role.
Functions directly related to the Microgrid application are described in this chapter.
6 back to Controller setup
Setpoints Values
Group: BESS (page 707)
Group: BESS settings (page 434)
Group: Frequency/Load Control (page
Group: BESS Protections (page 570)
861)
Group: Frequency/Load Control (page 466)
Group: Voltage/PF Control (page 864)
Group: Voltage/PF Control (page 479)
The BESS statistics in the Group:
The most of the setpoints in the Group: BESS
Statistics (page 870)
Protections (page 446)
Group: Synchronization (page 485)
PV
The controller directly controls only the PVCB, the Modbus Client (Master) (page 176) is used to interact with
the PV inverter. In case there are not any renewables installed or the controller should not use any functions
related to the renewables the setpoint PV (page 372) should be set to Not Installed option and the following
groups will be hidden.
Note: This settings is related to the MINT and MPTM applications.
Setpoints Values
Group: PV Settings (page 460) Group: PV (page 718)
The PV statistics in the Group: Statistics (page 870)
Gensets
The controller is not used to control Gen-sets in any way, instead the Gen-set controllers must be used. In case
the Gen-sets are not part of the system the setpoint Gensets (page 373) should be set to Not Installed option.
The HMI will be changed and Gen-sets statistics in the Group: Statistics (page 870) will be hidden.
Note: This settings is related only to the MINT application.
Mains
In case the system is working as island microgrid the setpoint Mains (page 373) should be set to Not Installed
option and Mains will be removed from the HMI.
Note: This settings is related only to the MINT application.
State of Charge
The charging and discharging process of the BESS also depends on the State Of Charge (SOC). When the
value BESS SOC (page 716) reach limit given by the setpoint SOC Low Target (page 440) the discharging
process is stopped and the LBO SOC DISCHARGE DISABLED (PAGE 1106) is activated. When the value BESS
SOC (page 716) reach limit given by the setpoint SOC High Target (page 439) the charging process is
stopped and the LBO SOC CHARGE DISABLED (PAGE 1106)is activated. The charging/discharing process can
be activated again after the value BESS SOC (page 716) leave the hysteresis which are defined by the
setpoints SOC Low Hysteresis (page 440) and SOC High Hysteresis (page 439). So, once the SOC
Actual reach the low target then the BESS cannot be discharged anymore until the BESS is cahrged at least
on the level of SOC Hysterezis.
Note: Charging and discharging is influenced all the time by the LBIs BATT CHARGE ENABLE (PAGE 989) and
BATT DISCHARGE ENABLE (PAGE 989).
Note: All relative setpoints/values are related to the LAI/Value BESSCAPACITY (PAGE 1115)BESS Nominal
Capacity (page 716).
In the picture below you can see the red and orange (Sd and Wrn) alarm areas. The aopropirate alarm is
activated when SOC Actual trips the SOC alarm level given by setpoints in the Subgroup: SOC Protection
(page 598). The green area is Safety Operation Area and SOC targets should be placed in it. The battery
should cycle between these targets in the green area.
Note: If the BESS is connected to the Grid alone after Gen-set/Mains is disconnected, the BCB is opened
because of anti islanding protection (Hst BESS Anti Islanding (page 1280)).
Note: The values described above are send to the BESS inverter via Modbus Client (Master) (page 176)
function for both cases.
DC Precharge
DC precharge start sequence applies to PCS with the ability to black start itself from the DC bus of the
batteries.
InteliNeo uses two signals to coordinate DC precharge, the LBO PRECHARGE REQUEST (PAGE 1099) and
LBI PRECHARGE FINISHED (PAGE 1016). Both signals are mandatory.
Once the internal DC contactor between batteries and PCS are closed, the inverter can energize its AC
output.
LBI INVERTER START DISABLED (PAGE 1006) is to be sent once the precharge procedure has been
finished.
Controller then waits for confirmation LBI BESS READY TO LOAD (PAGE 995) (if this LBI is configured as
not all battery inverters have an idle mode), or the BESS is ready once the period set in Timer BESS
Ready To load elapses (only if LBI BESS READY TO LOAD (PAGE 995) is not configured).
BESS protections unlocks and BCB can be closed to allow BESS to energize the dead bus.
AC Precharge
AC precharge start sequence applies to PCS that requires energization from the AC side to close the internal
DC circuit to the batteries. The AC bus must be healthy with voltage and frequency within the acceptable
range of the PCS.
InteliNeo uses two signals to coordinate AC precharge, the LBO PRECHARGE REQUEST (PAGE 1099) and
LBI PRECHARGE FINISHED (PAGE 1016). Both signals are mandatory.
AC precharge starts by closing the BCB to the bus. The inverter must be able to moderate the inrush
current when connected to the AC bus via the BCB.
Once the DC voltage for the batteries and PCS are level and the internal DC circuit is closed, the
precharge of the inverter is complete.
InteliNeo provides LBO Inverter Run Request to the inverter to begin operation.
When theBESS start is finished, the BESS goes into the stabilization phase. There are two timers (setpoints) in
this phase:
Minimal Stabilization Time (page 441) starts to count down just after the idle period has finished. BESS
voltage and frequency are not checked (respective protections are not evaluated) and the BCB cannot be
closed even if the BESS voltage and frequency are within limits.
Maximal Stabilization Time (page 442) starts to count down just after the idle period has finished. BESS
voltage and frequency are not checked (respective protections are not evaluated) but, opposite to the
previous timer, the BCB can be closed if BESS voltage and frequency are within limits.
In situations where the BCB is closed automatically (AUTO mode), the closing of BCB or starting of
synchronization will occur in the first moment when the BESS voltage and frequency will get into limits and the
Minimal Stabilization Time (page 441) has already elapsed.
In the event that the BESS voltage or frequency are not within limits within the Maximal Stabilization Time
(page 442) period, the appropriate protection(s) will be activated and the BESS will be cooled down and stopped.
Note: The limits for the BESS voltage and frequency are given by setpoints in the Group: BESS settings (page
434).
Note: The value of the Minimal Stabilization Time (page 441) setpoint has to be lower than the value of
Maximal Stabilization Time (page 442) setpoint.
BESS
Before connecting of the BESS to the load the LBI GENERIC GENSET START/STOP (PAGE 1004) must be activated
in case of AUT mode or start button must be pressed in case of MAN mode.
The connection of the BESS to the bus/load differs according to the setpoint BESS Precharge Type (page 435).
In case the AC option is set, the BCB breaker can be closed immediately after the BESS is in the running phase.
No stabilization time is counted because the inverter with AC precharge is not able to generate AC voltage on its
output without being connected to the healthy bus. In this case the synchronization and connecting to the
deadbus options are not available.
In case the DC option is set , connecting of the BESS to the load is same as for the Gen-set. See the text below.
When the BESS Stabilization (page 246) phase is finished, the BESS can be connected to the load. The
command for connecting the BESS to the load is issued either automatically (AUTO mode) or manually by
pressing the BCB button. The following conditions must be valid:
The BESS is running and the Minimal Stabilization Time (page 441) timer has elapsed.
The BESS voltage and frequency are within limits.
Note: The frequency governor and AVR must be adjusted properly to achieve these limits as the controller does
not perform any regulation and the regulation outputs have constant values given by the Voltage Regulator
Bias (page 480) and Frequency Governor Bias (page 467) setpoints.
Connecting to load depends on the state of MCB FEEDBACK (PAGE 1012) and on the measured bus voltage. In
case the Load is without power (bus voltage is below 2 % of nominal voltage and MCB is opened) the
Connecting To Dead Bus (page 249) is applied, in other case the Synchronization (page 249) process is
needed.
PV
The connection of the PV to the bus/load is not related to the LBI GENERIC GENSET START/STOP (PAGE 1004) or
start button in any way. Instead the LBO PV/WT RUN REQUEST (PAGE 1100) is activated always when the CU is
in the AUT or MAN mode and the controller expect activation of the LBI PV Operable. It is expected that PV
inverter is always using AC precharge so the PVCB can be closed once the LBI is active an the bus is healthy. So
in this point behavior is the same as it is for the BESS with AC precharge. The PVCB cannot be closed to the
deadbus or synchronized because PV inverter is not able to generate AC voltage on its own.
Connecting Mains to Load
Connecting to load depends on application, for BCB application it depends on the state of BCB FEEDBACK (PAGE
991) and on the measured bus voltage. In case of MCB application depends only on measured bus voltage. In
case the Load is without power (bus voltage is below 2 % of nominal voltage or BCB is opened) the connecting to
dead bus is applied, in other case the synchronization process (reverse synchronization) is needed. See more
information about synchronization process in chapter Synchronization (page 249).
Connecting to load (closing BTB) depends on the measured Bus Left and Bus Right voltage. In case one of the
side of BTB is without power (Bus Left or Bus Right voltage is below 2 % of nominal voltage) the connecting to
MINT
The measured bus voltage is taken in account, it must be below 2% of the nominal bus voltage together with the
open MCB (evaluated by LBI MCB Feedback (page 1012) or internally via CAN intercontroller communication if
the LBI is not configured), and also others BCB have to be opened, to close the BCB without synchronization.
Note: If the group of / multiple BESSs have to start simultaneously and connect to the empty bus bar, there is an
internal logic to prevent closing of more BCBs to the bus bar at the same moment without synchronization. One
of the BESSs will close the BCB, the others will wait and then they will synchronize to the first one.
IMPORTANT: The function described above works only if all controllers can see each other on
CAN intercontroller line. You can use Emergency Droop function to detect missing controller
on CAN.
Note: There also is a protection of “Bus power loss sensing”. The “Bus Measure Error” is detected in MINT
application when the voltage on the controller’s bus terminals is out of limits 20 seconds after:
BCB (own) was closed in MAN or AUT mode
MCB (feedback) was closed in AUT mode
Any other BCB in power management group (on CAN bus) was closed.
The alarm is activated after 20s. However, the BCB (own) closing is blocked immediately for safety reasons. This
protection can avoid e.g. potential direct closing of BCB while the controller’s bus conductors are unintentionally
unplugged from the terminals.
Synchronization
Synchronization Process 249
Synchronization Types 251
Synchronization Process
Behavior of synchronization process depends on, which breaker is used for synchronization and on which
Controller Mode (page 385) is controller switched to.
Note: When the controller starts to synchronize and the main measuring screen is displayed, it will be
automatically changed to the synchroscope screen for the entire duration of synchronization. The screen will
also show value Voltage Match 321 to inform you better about synchronization process. After synchronization
the synchroscope screen is automatically changed back to the main measuring screen. It is also possible to
change screens manually (arrows up and down) after displaying the synchroscope screen. In this case there is
no automatic return to the main measuring screen after synchronization is finished.
Synchronization Types
There are two types of synchronization. Type of synchronization is adjusted via setpoint Synchronization Type
(page 485).
Phase Match
The phase match synchronization consists of voltage matching and frequency/angle matching. The maximum
duration of synchronization is given by the setpoint Synchronization Timeout (page 486). If the
synchronization is not successful within this period of time, the Stp Synchronization Fail (page 1294) alarm will
be issued.
Voltage matching
The BESS voltage is regulated to match the Mains/Bus voltage with tolerance given by the setpoint Voltage
Window (page 486). The regulation is adjusted by the setpoints Voltage Gain (page 482) and Voltage Int
(page 482).
Frequency/angle matching
The BESS frequency is regulated to match the Mains/Bus frequency first. The frequency regulation loop is active
(setpoints Frequency Gain (page 469) and Frequency Int (page 470)). Once the frequency is matched, the
regulation loop is switched to match the angle (setpoint Angle Gain (page 470)). When the angle is matched
with tolerance +/- Phase Window (page 487) for a time given by the setpoint Dwell Time (page 487) and the
voltage is matched too, then the BCB or MCB is closed.
Note: The matching loop will continue to run even if the BCB or MCB close command has been already issued
until the controller receives BCB FEEDBACK (PAGE 991)/MCB FEEDBACK (PAGE 1012) or Sd BCB Fail To Close
(page 1291)/Wrn MCB Fail To Close (page 1255) alarm occurs. After the feedback has been received, the
control loops are switched to load and power factor loops respectively to load and power factor sharing.
Whenever the BESS Frequency (page 713) leaves off the Slip Frequency Window (page 488) (either
because of BESS Frequency (page 713), Mains/Bus Frequency (page 839) or setpoint Slip Frequency
Window (page 488) changes) the controller will reactivate frequency regulation loop and try to reach the target
value again. The Synchronization Timeout (page 486) timer runs regardless of this while whole slip
synchronization process is repeated. If the BESS Frequency (page 713) reaches the target frequency again the
regulations are frozen and if the BESS Frequency (page 713) remains in the window for the time longer than
setpoint Dwell Time (page 487) the controller will continue in the standard sequence as seen in the previous
case. *If the Synchronization Timeout (page 486) elapses the controller will immediately stop synchronization
and issue alarm Stp Synchronization Fail (page 1294).
The window is limited by the actual measured Mains/Bus Frequency (page 839) if one of the window limits is
below this value (e.g. for setting where setpoint Slip Frequency (page 717) is set to 0.1Hz and setpoint Slip
Frequency Window (page 488) is set to 0.5Hz).
Slip synchronization has a dead band. When the dead band is reached the frequency regulation is disabled.
Once it is disabled it will be enabled again only when the frequency goes out of the slip frequency window. Dead
band is introduced to allow the controller to detect the match.
Note: Due to the nature of this function it is possible that in limit cases the controller will regulate the BESS
frequency outside of protection limits. Example: Mains/Bus frequency is high but within its protection limits (e.g.
50.9 Hz, limit is 51 Hz). Slip Frequency (page 488) is set to 0.5Hz. This will cause regulation loop of the
controller can push the BESS frequency to 51.4 Hz and eventually the controller will issue overfrequency alarm.
It is recommended to set the setpoint Slip Frequency (page 488) as low as possible that still enables succesfull
synchronization. This minimizes the risk of this problem happening. Furthermore when slip synchronization is
used it is recommended to set Mains/Bus Frequency protection limits to more rigid values than the BESS
frequency protection limits. In this case the setpoint Slip Frequency (page 488) can be set to 0.1Hz and the
Mains/Bus Frequency overfrequency protection limit is set to 50.9Hz instead of 51Hz. This will ensure that
problematic state cannot be reached.
6 back to Synchronization
Inputs
These sensors provide data on the amount of sunlight received at different points within the microgrid.
IRRADIATION OF PV ARRAY 1 (PAGE 1122)
IRRADIATION OF PV ARRAY 2 (PAGE 1122)
IRRADIATION OF PV ARRAY 3 (PAGE 1123)
IRRADIATION OF PV ARRAY 4 (PAGE 1123)
Corrections
Output of Each particular PV Array in kW can be corrected using the offset which is defined setpoints:
PV Calib. Offset 1 (page 462)
PV Calib. Offset 2 (page 462)
PV Calib. Offset 3 (page 463)
PV Calib. Offset 4 (page 463)
Statistical Outputs
PV Total Curtailed kWh (page 871)
PV Curtailed Annual kWh (page 871)
PV Curtailed Monthly kWh (page 871)
PV Curtailed Weekly kWh (page 872)
PV Curtailed Daily kWh (page 872)
Curtailed Power
PV Max P (page 720)
PV Curtailed P (page 721)
PV Curtailed P Relative (page 721)
These statistical outputs provide valuable insights into the efficiency of the microgrid's PV system, enabling
operators and system administrators to make informed decisions to optimize energy utilization and
curtailment strategies within the microgrid.
IMPORTANT: The controller in MINT application does not control the MCB! Only the MCB position is
evaluated from the binary input MCB FEEDBACK (PAGE 1012) and the position is the basic source of
information for switching between island and parallel to mains operation. If MCB Feedback is not
configured the state is automatically shared via intercontroller CAN.
Note: The following description is common for Gen-set and BESS only in case the BESS Precharge Types
(page 245) is set to DC. Otherwise the BESS cannot synchronize and it must be firstly precharged by closing
the BCB and connecting dead output of the inverter to the healthy bus.
If the bus bar is empty, the first Gen-set/BESS will close its GCB/BCB without synchronization. Following Gen-
sets will synchronize to the already energized bus bar. In the event that multiple Gen-sets start simultaneously
and the bus bar is empty, the system will prevent closing of multiple GCBs to the bus bar without synchronization.
Instead of this, one of the Gen-sets/BESS will close the GCB/BCB and energize the bus bar and the others will
wait and then synchronize to the bus bar.
When a stop command is received, e.g. from the power management or binary input GENERIC GENSET
START/STOP (PAGE 1004) is deactivated or the STOP button is pressed, the GCB/BCB will be opened, the BESS
will be stopped and Gen-sets will go to cool down phase.
Behavior of controllers is adjusted via Power Management (page 274) settings. Please see this chapter for
more information.
MINT application
Load control loop is active in parallel to Mains mode only (MCB FEEDBACK (PAGE 1012) is closed). Switch off
other parts of the system (BESSs) while adjusting.
1. Set #System Baseload (page 355) setpoint to 30 % of one BESS.
2. Set Load Gain (page 471) to the same value as Angle Gain (page 470) and Load Int (page 471) to 0.
3. Start theBESS in MAN Mode, press BCB ON/OFF button to synchronize and close BESS to Mains.
4. When BCB is closed, BESS load slowly increases to the #System Baseload (page 355) value. Check
that BESS power is positive (CT polarity).
5. Increase Load Int (page 471) to unstable load control and decrease value by 30 % to insure stable
performance. When Load Int (page 471) factor is set to zero BESS load can differ from required
#System Baseload (page 355).
6. To adjust and optimize Load Int (page 471) change #System Baseload (page 355) several times
between 30 and 70 % of Nominal power (page 375).
7. When BESS is running under full load check if
a. Speed regulator output voltage value is not limited (it does not reach Frequency Governor Low
Limit (page 467) or Frequency Governor High Limit (page 467)).
b. Speed governor actuator is not mechanically limited or operates in a small section of the throttle
range.
8. Now your Load regulation loop setup is done.
MPTM application
Load control loop is active in parallel to Mains mode only (MCB FEEDBACK (PAGE 1012) is closed).
1. Set Load Control PTM Mode (page 352) = BASELOAD, BESS P request source (page 436) =
Setpoint, BESS Charge Power (page 436)/BESS Discharge Power (page 437) setpoint to 30 %
Nominal power (page 375) of BESS and activate LBI BATT CHARGE ENABLE (PAGE 989)/BATT
DISCHARGE ENABLE (PAGE 989).
2. Set Load Gain (page 471) to the same value as Angle Gain (page 470). Set Load Int (page 471) to
zero.
3. Start the BESS in MAN Mode, press BCB ON/OFF button to synchronize and close BESS to Mains.
4. When BCB is closed, BESS load slowly increases to BESS Charge Power (page 436)/BESS Discharge
Power (page 437) value.
5. Increase Load Gain (page 471) to unstable load control and decrease value by 30 % to insure stable
performance. When Load Int (page 471) factor is set to zero BESS load can differ from required
BESS Charge Power (page 436)/BESS Discharge Power (page 437).
6. To adjust and optimize Load Int (page 471) change BESS Charge Power (page 436)/BESS Discharge
Power (page 437) several times between 30 and 70 % of Nominal power (page 375). Usually setting
Load Int (page 471) to 100% gives optimal performance.
7. When BESS is running under full load check if speed governor output voltage value is not limited (it does
not reach Frequency Governor Low Limit (page 467) or Frequency Governor High Limit (page
467)).
8. Now your Load regulation loop setup is done.
PF Adjustment
MINT application
Power factor control loop is active in parallel to mains mode only (MCB FEEDBACK (PAGE 1012) is closed). Switch
off other parts of the system (Gen-sets) while adjusting.
1. Set PF Gain (page 483) to the same value as parameters Voltage Gain (page 482) and Voltage Int
(page 482) to 0.
2. Set #System Baseload (page 355) = 30 % of Nominal power (page 375) and #System Power Factor
(page 360) = 1.0.
3. Start and synchronize the BESS in MAN Mode by pressing BCB ON/OFF.
4. When running in parallel to mains loaded on 30%, increase slowly PF Gain (page 483) to unstable point
and then decrease the value by 30 % to insure stable performance.
5. Increase Load Int (page 471) to unstable load control and decrease value by 30 % to insure stable
performance. When Load Int (page 471) factor is set to zero BESS load can differ from required
#System Power Factor (page 360).
6. Now your PF/Q regulation loop setup is done.
MPTM application
Power factor control loop is active in parallel to mains mode only (MCB FEEDBACK (PAGE 1012) is closed).
1. Set the same values to PF Gain (page 483) and PF Int (page 483) as in the chapter Voltage
Adjustment (page 259) for parameters Voltage Gain (page 482) and Voltage Int (page 482).
2. Set BESS Charge Power (page 436)/BESS Discharge Power (page 437) = 30 % of Nominal power
(page 375) and Base Power Factor (page 359) = 1.0.
3. Start and synchronize the BESS in MAN Mode by pressing BCB ON/OFF.
4. When running in parallel to mains loaded on 30%, increase slowly PF Gain (page 483) to unstable point
and then decrease the value by 30 % to insure stable performance.
5. Adjust PF Int (page 483) (usually setting to 100% gives optimal performance).
6. Now your PF/Q regulation loop setup is done.
Note: To judge optimal adjusting of the power factor induce BESS power jumps by Voltage Regulator Bias
(page 480) change or by BESS Charge Power (page 436)/BESS Discharge Power (page 437) change.
The InteliNeo6000 Load and PF/Q control is different from Gen-set controllers. It is expected that renewables
(PV) and BESS should run with maximal priority so the Load Sharing is applied only in some critical cases. Se the
chapters BESS Charging/Discharging Control (page 239), BESS/PV PF/Q Control (page 247), and PV
Curtailment (page 295) for more information.
Power down
Ramp down starts when value BESS Required P Target (page 861) drops, value BESS Required P (page
861) is ramped from BESS P (page 707) down to the new value of BESS Required P Target (page 861) based
on Load Ramp (page 477). Setpoint Load Ramp (page 477) determines how long it shall take to ramp down
from Nominal power (page 375)/Installed Power (page 375) of the BESS to 0 kW.
Soft unload
When BCB is about to be opened (BCB open command or stop command have been received), controller uses
Soft Unload Ramp (page 479) for ramp BESS P (page 707) to Generator Unload BCBOpen Level (page
476). Setpoint Soft Unload Ramp (page 479) determines how long it shall take to ramp down from Nominal
power (page 375)/Installed Power (page 375) of the gen-set to 0 kW.
6 back to Parallel To Mains Operation - MINT Application
Load control
If MCB FEEDBACK (PAGE 1012) is active (parallel to Mains operation) the load of Gen-set group is controlled to
reach the power defined by setpoint #System Baseload (page 355) or by Load Sharing line. If the setpoint
#System Load Control PTM (page 354) = Load Shar the system load is regulated by the InteliMains supervisor
controller, otherwise the load is controlled locally in each controller by load control regulation loop. The regulation
loop is adjusted via setpoints Load Gain (page 471) and Load Int (page 471).
Current Load control mode is always showed in System Load Control (page 863) value (SPTM only).
Load Shar
If #System Load Control PTM (page 354) is Load Shar the system Load is controlled by InteliMains controller.
Note: Mains controller plays active role in case of load control only in case that the sepoint #System Load
Control PTM (page 354) is set to Load sharing . If this setpoint is set to Baseload the load control is controlled
from gen-set controllers and their load control loops.
InteliNeo 6000 offers 2 modes for controlling of load. Load control ensures that the system keeps the certain
Actual Active Power In PM (page 858) value in parallel to Mains operation MCB STATUS (PAGE 1092) and
BCB STATUS (PAGE 1060) are closed, i.e. Breaker state (page 886) = ParalOper and at least one gen-set is
excited.
6 back to Parallel To Mains Operation - MINT Application
PF/Q control
If MCB FEEDBACK (PAGE 1012) is active (Parallel To Mains Operation) the PF/Q of Gen-set is controlled to reach
the PF/Q defined by setpoint #System Power Factor (page 360)/#System Base Q (page 361).Var Sharing
line is used automatically if Load Sharing is active or while island operation. If the setpoint #System PF Control
PTM (page 358) = Var Shar the system PF/Q is regulated by the InteliMains supervisor controller, otherwise the
load is controlled locally in each controller by var control regulation loop. The regulation loop is adjusted via
setpoints PF Gain (page 483) and PF Int (page 483).
Current PF/Q control mode is always showed in System PF/Q Control (page 864) value (SPTM only).
Base PF
#System PF Control PTM (page 358) has to be adjusted to Base PF. The BESS Required PF (page 865) with
BESS Required PF Character (page 865) are based on:
PF/Q Request Source (page 357) = Setpoint, requested PF is given by the Setpoint #System Power
Factor (page 360) or
PF/Q Request Source (page 357) = Analog External Value, requested PF is given by value from LAI PF
CONTROL: ANEXT BASE PF (PAGE 1124).
Base Q
#System PF Control PTM (page 358) has to be adjusted to Base Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by #System
Base Q (page 361) or
PF/Q Request Source (page 357) = Analog External Value, BESS Required Q (page 865) is given by
value from LAI Q Control: ANEXT Base Q (page 1147).
Note: Alarm Wrn Q Control Fail (page 1261) is activated if LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is
not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.
Var Shar
If #System PF Control PTM (page 358) is Var Shar the Gen-set PF/Q is controlled by InteliMains controller.
6 back to Parallel To Mains Operation - MINT Application
After the BESS has been synchronized to the mains, the parallel to mains operation follows.
The InteliNeo6000 Load and PF/Q control is different from Gen-set controllers. It is expected that renewables
(PV) and BESS should run with maximal priority so the Load Sharing is applied only in some critical cases. Se the
chapters BESS Charging/Discharging Control (page 239), BESS/PV PF/Q Control (page 247), and PV
Curtailment (page 295) for more information.
Power up
The first phase of the parallel to mains operation is the ramp of the BESS up to the desired power level. Ramp up
starts when value BESS Required P Target (page 861) rises. If the BCB has been just closed, value BESS
Required P (page 861) is ramped from Ramp Start Level (page 478) up to the new value of BESS Required P
Target (page 861) based on Load Ramp (page 477), otherwise is value BESS Required P (page 861) ramped
from BESS P (page 707). Setpoint Load Ramp (page 477) determines how long it shall take to ramp up from 0
kW to Installed Power (page 375) of the BESS.
Note: Ramp Start Level (page 478) and Load Ramp (page 477) are related to Installed Power (page 375)
only if Installed Power (page 375) != OFF, otherwise they relate to Nominal power (page 375).
Power down
Ramp down starts when value BESS Required P Target (page 861) drops, value BESS Required P (page
861) is ramped from BESS P (page 707) down to the new value of BESS Required P Target (page 861) based
on Load Ramp (page 477). Setpoint Load Ramp (page 477) determines how long it shall take to ramp down
from Installed Power (page 375) of theBESS to 0 kW.
Note: Setpoint Load Ramp (page 477) is related to Installed Power (page 375) only if Installed Power (page
375) != OFF, otherwise it relates to Nominal power (page 375).
Soft unload
When BCB is about to be opened (BCB open command or stop command have been received), controller uses
for ramping BESS P (page 707) to Generator Unload BCBOpen Level (page 476). Setpoint determines how
long it shall take to ramp down from Installed Power (page 375) of the BESS to 0 kW.
Note: Setpoint Load Ramp (page 477) is related to Installed Power (page 375) only if Installed Power (page
375) != OFF, otherwise it relates to Nominal power (page 375).
Load control
InteliNeo 6000 offers 2 modes for controlling of load. Load control ensures that the BESS keeps the certain
BESS P (page 707) value in parallel to Mains operation MCB STATUS (PAGE 1092) and BCB STATUS (PAGE
1060) are closed, i.e. Breaker state (page 886) = ParalOper.
Current Load control mode is always showed in the value System Load Control (page 863).
Baseload
Baseload ensures that the BESS keeps certain BESS P (page 707), which is given by BESS Required P (page
861). BESS Required P (page 861) is ramped to BESS Required P Target (page 861) using Load Ramp
(page 477) or actual active ramp based on Grid Codes (page 299).
If Load Request Source (page 353) = Analog External Value, BESS Required P Target (page 861) is
equal to value from LAI LOAD CONTROL: ANEXT BASELOAD (PAGE 1121).
Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).
Note: In case LAI LOAD CONTROL: ANEXT BASELOAD (PAGE 1121) is not configured or has Invalid flag (page
691), function is evaluated as if Load Request Source (page 353) = Setpoint.
Import/Export
Import/Export ensures that the Gen-set regulates its BESS P (page 707) to keep certain Mains Import P (page
842). BESS P (page 707) is given by BESS Required P (page 861) which is ramped to BESS Required P
Target (page 861) using Load Ramp (page 477) or actual active ramp based on Grid Codes (page 299).
Load Control PTM Mode (page 352) has to be adjusted to Import/Export and BESS Required P Target (page
861) is given by:
If Load Request Source (page 353) = Setpoint, Mains Import P (page 842) = Import Load (page
355).
Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).
If Load Request Source (page 353) = Analog External Value, Mains Import P (page 842) is equal to
value from LAI LOAD CONTROL: ANEXT IMP/EXP LOAD (PAGE 1122).
Note: Alarm Wrn Load IMP/EXP Fail (page 1253) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).
Note: In case LAI LOAD CONTROL: ANEXT IMP/EXP LOAD (PAGE 1122) is not configured or has Invalid flag
(page 691), function is evaluated as if Load Request Source (page 353) = Setpoint.
PF/Q Control
PF Control 266
PF(Pm) 267
Q Control 267
Q(Um) 268
PF Control
PF Control ensures that the Gen-set keeps certain BESS Q (page 708) to provide required BESS Power Factor
(page 710). To enable this control, adjust PF/Q Control PTM Mode (page 356) to PF Control.
Base PF
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF Control BASE and
PF/Q Request Source (page 357) = Setpoint, requested PF is given by the Setpoint #System
Power Factor (page 360) or
PF/Q Request Source (page 357) = Analog External Value, requested PF is given by value from LAI
PF CONTROL: ANEXT BASE PF (PAGE 1124).
Note: Alarm Wrn PF Control Fail (page 1258) is activated if LAI PF CONTROL: ANEXT BASE PF (PAGE 1124)
is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.
Import/Export PF
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF Control IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, requested Mains PF (page 845) is given by Import
Power Factor (page 359) or
PF/Q Request Source (page 357) = Analog External Value, Mains PF (page 845) is given by value
from LAI PF CONTROL: ANEXT IMP/EXP PF (PAGE 1125).
Note: Alarm Wrn PF Control Fail (page 1258) is activated if LAI PF CONTROL: ANEXT IMP/EXP PF (PAGE
1125) is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page
357) = Setpoint.
Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).
Base PF(Pm)
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF (Pm) BASE and
PF/Q Request Source (page 357) = Setpoint, requested PF is given by PF(P) (PAGE 970) curve in x-
axe range 0 to 100 %. Actual value of the curve is stored in PF(P) Curve (page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn PF(Pm) Fail (page 1259) is
immediately activated because this control mode does not support external analog value. Power is
controlled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn PF(Pm) Fail (page 1259) is activated if PF(P) (PAGE 970) curve is not configured or invalid.
Power is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.
Import/Export PF(Pm)
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF (Pm) IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, requested Mains PF (page 845) is given by PF(P)
(PAGE 970) curve in x-axe range -100 to 100 %. Actual value of the curve is stored in PF(P) Curve
(page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn PF(Pm) Fail (page 1259) is
immediatelly activated because this control mode does not support external analog value. Power is
controlled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn PF(Pm) Fail (page 1259) is activated if PF(P) (PAGE 970) curve is not configured or invalid.
Power is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.
Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).
Q Control
BESS Power Factor (page 710) is adjusted to reach BESS Required Q (page 865). To enable this control,
adjust PF/Q Control PTM Mode (page 356) to Q Control.
Import/Export Q
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q Control IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by Import Q
(page 361) or
PF/Q Request Source (page 357) = Analog External Value, Mains Import Q (page 843) is given by
value from LAI Q CONTROL: ANEXT IMP/EXP Q (PAGE 1147).
Note: Alarm Wrn Q Control Fail (page 1261) is activated if LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is
not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.
Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).
Q(Um)
BESS Q (page 708) is automatically adjusted to correspond with predefined BESS Required Q (page 865)
upon change of relative Mains voltage. The predefined BESS Required Q (page 865) is adjusted by application
curve Q(UM) (PAGE 967) To enable this control, adjust PF/Q Control PTM Mode (page 356) to Q(Um).
Base Q(Um)
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q(Um) BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by Q(UM)
(PAGE 967) curve. The curve can be offset horizontally by Q(Um) 0 Reference (page 565) and in case
of Mains Voltage changes too fast, there is Q(Um) Deadband (page 565). Actual value of the curve is
Import/Export Q(Um)
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q(Um) IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by Q(UM) (PAGE
967) curve. The curve can be offset horizontally by Q(Um) 0 Reference (page 565) and in case of too
fast Mains Voltage changes, there is Q(Um) Deadband (page 565). Actual value of the curve is stored
in Q(Um) Curve (page 830). Or
PF/Q Request Source (page 357) = Analog External Value, Mains Import Q (page 843) is given by
Q(UM) (PAGE 967) curve, but the horizontal offset is given by value of LAI Q(UM): 0 REF ANEXT
IMP/EXP Q (PAGE 1149)System PF/Q Control (page 864) Q(Um) Deadband (page 565) can also be
applied. Actual value of the curve is stored in Q(Um) Curve (page 830).
Note: Alarm Wrn Q(Um) Fail (page 1263) is activated if LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148) is not
configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.
Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).
Q(P)
BESS Q (page 708) is automatically adjusted to correspond with predefined BESS Required Q (page 865)
based on BESS P (page 707). The predefined BESS Required Q (page 865) is adjusted by application curve Q
(P) (PAGE 969) To enable this control, adjust PF/Q Control PTM Mode (page 356) to Q(P).
Base Q(P)
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Q (page 708) is based
on:
System PF/Q Control (page 864) = Q(P) BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by Q(P) (PAGE
969) curve in x-axe range 0 to 100 %. To prevent oscilation use Q(P) Deadband (page 567) Actual
Import/Export Q(P)
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required Q
(page 865)is based on:
System PF/Q Control (page 864) = Q(P) IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by Q(P) (PAGE
969) curve in x-axe range -100 to 100 %. To prevent oscilation use Q(P) Deadband (page 567) Actual
value of the curve is stored in Q(P) Curve (page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn Q(P) Fail (page 1262) is
immediately activated because this control mode does not support external analog value. Power is
controled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn Q(P) Fail (page 1262) is activated if Q(P) (PAGE 969) curve is not configured or invalid. Power
is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.
Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).
Qref/Ulim
BESS Q (page 708) is automatically adjusted to correspond with predefined BESS Required Q (page 865)
upon change of relative Mains voltage. The predefined BESS Required Q (page 865) is adjusted by application
curve QREF/ULIM (PAGE 968). To enable this control, adjust PF/Q Control PTM Mode (page 356) to Qref/Ulim.
Base Qref/Ulim
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864)= Qref/Ulim BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by QREF/ULIM
(PAGE 968) curve. The curve can be offset vertically by Qref/Pnom Shift (page 566) and in case of too
fast Mains Voltage changes, there is Qref/Ulim Deadband (page 566) Actual value of the curve is
stored in Qref/Ulim Curve (page 830). Or
PF/Q Request Source (page 357) = Analog External Value, BESS Required Q (page 865) is still
given by QREF/ULIM (PAGE 968) curve, but the horizontal offset is given by value of LAI QREF/ULIM:
Import/Export Qref/Ulim
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required Q
(page 865) is based on:
System PF/Q Control (page 864) = Qref/Ulim IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by QREF/ULIM
(PAGE 968) curve. The curve can be offset vertically by Qref/Pnom Shift (page 566) and in case of too
fast Mains Voltage changes, there is Qref/Ulim Deadband (page 566) Actual value of the curve is
stored in Qref/Ulim Curve (page 830). Or
PF/Q Request Source (page 357) = Analog External Value, Mains Import Q (page 843) is given by
QREF/ULIM (PAGE 968) curve, but the offset is given by value of LAI QREF/ULIM: ANEXT QREF/PNOM
I/E Q (PAGE 1151)System PF/Q Control (page 864) Qref/Ulim Deadband (page 566) can also be
applied. Actual value of the curve is stored in Qref/Ulim Curve (page 830).
Note: Alarm Wrn Qref/Ulim Fail (page 1263) is activated if LAI QREF/ULIM: ANEXT QREF/PNOM I/E Q (PAGE
1151) is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page
357) = Setpoint.
Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).
Transfers of load
Type of transfer of load between mains and BESS and vice versa is adjusted via setpoints Transfer BESS To
Mains (page 475) and Transfer Mains To BESS (page 474).
Transfer of the load from BESS to mains and vice versa without parallel work and
Open synchronization (one breaker opens and second is closed - checking feedbacks). The
setpoint Open Transfer Min Break (page 473) sets the minimal duration of break.
Transfer of the load from BESS to mains and vice versa with synchronization and
parallel work. The maximal time of parallel work is given by setpoint Close Transfer
Close Only
Max Duration (page 473).
In case of synchronization fail, MCB stays close and BESS is stopped.
Transfer of the load from BESS to mains and vice versa with synchronization and
parallel work. The time of parallel work is given by setpoint Close Transfer Max
Close Primarily
Duration (page 473).
In case of synchronization fail, open transfer is done.
Transfer of the load from BESS to mains and vice versa with parallel work and soft
loading/unloading of the BESS. This function is proceeded like the closed transfer, but
there is time limitation of loading/unloading of the BESS adjusted via setpoint Load
Ramp (page 477). The transfer is succeed only when the BESS is fully
Soft Transfer
loaded/unloaded (level of load when mains is considered as unloaded - BESS is loaded
is adjusted via setpoint Mains Unload MCB Open Window (page 476)), level of load
when BESS is considered as unloaded is adjusted via setpoint Generator Unload
BCBOpen Level (page 476)).
FORCE ISLAND (PAGE the transfer of load from mains to BESS is done
997) When deactivated:
the transfer of load from BESS to mains is done
stopping of the BESS
When activated:
starts BESS
GENERIC GENSET if mains parameters ok - synchronize, run in parallel
START/STOP (PAGE
if mains parameters not ok - run in island
1004)
When deactivated:
unloading (if BESS was in parallel) and stopping of the BESS
When activated:
check mains parameters - if not ok no action, if ok the procedure follows
starts the BESS, synchronize, parallel operation
FORCE PARALLEL
in case of mains fail - BESS is stopped (if AMF function is disabled,
(PAGE 997)
otherwise it goes to island operation)
When deactivated:
unloading and stopping of the BESS
Type of transfer of load between mains and BESS and vice versa is adjusted via setpoints Transfer BESS To
Mains (page 475) and Transfer Mains To BESS (page 474).
6 back to Parallel To Mains Operation - MPTM Application
IMPORTANT: The Mains and BESS will take part of the power management (will be active) only if the
controller is in AUTO mode!
The Power management function decides how many BESSs should run and selects particular BESSs to run. The
power management is applicable in cases multiple BESSs run in parallel to Mains or in the island operation. The
function is based on the load evaluation in order to provide enough of available running power. Since it allows the
system to start and stop BESSs based on the load demand, it can vastly improve the system fuel efficiency. In
other words, an additional BESS starts when the load of the system raises above certain level. The additional
BESS stops, when the load of the system drops down below a certain level. The process of determining BESS
start and stop is done in each controller; there is no "master slave" system. Therefore, the system is very robust
and resistant to failures of any unit in the system. Each of the controllers can be switched off without influencing
the whole system. Except the situation the respective BESS is not available for the power management.
The power management evaluates so called Load reserve (page 276). The load reserve is calculated as
difference between actual load and nominal power of running BESSs. The reserve is calculated as absolute
value (in kW / kVA) or relatively to the nominal power of BESS(s) (in %). The setpoint #Power Management
Mode (page 491) is used to select the absolute or relative mode.
The Load Reserve can be influenced by the Dynamic Spinning Reserve (page 277) which is used to provide
the system with extra power (running BESSs) in case of anticipated output drop of a renewable source of energy.
The function Priority auto swap (page 286) focuses on efficient run of BESS in regards to running hours and
BESS size (power).
IMPORTANT: The function of the controller is designed to handle the maximum sum of nominal
power at 32000 kW (or 3200,0 with decimal number).
Example: There are 20 BESSs each with 1000 kW of nominal power. The sum of the nominal power is
20000 kW. Therefore the decimal power format in 0.1 kW cannot be used because the sum exceeds
32000. Therefore power format in kW needs to be chosen.
Function of power management can be temporarily blocked after GENERIC GENSET START/STOP (PAGE 1004)
activation a count down of #System Start Delay (page 494). The delay is given by setpoint Power
Management Delay (page 490). In this delay all BESSs where power management is enabled are running. After
this period elapses, only the BESSs needed according to the Power Management calculation stay running and
the rest is stopped.
6 back to Power Management
Setpoint #Overload Next Start Delay (page 514) is used in case that #Overload Next Start Protection (page
513) is enabled and BESSs are running at #Overload Next Start Level (page 513) or more of their nominal
power.
6 back to Power Management
Load reserve
The power management is based on the load reserve concept. The load reserve is defined as a difference of the
running nominal power of the group within power management and the total load of the system. In the
InteliNeo6000 controller the running nominal power is given by the actual power of the renewables (if they are
used) and by the nominal power of the BESS. There are two ways how to determine the load reserve. The
absolute power management allows the system to keep the load reserve higher or equal to value in kW given by
a relevant setpoint. The relative power management assures that load reserve is kept higher or equal to relative
portion in % of the nominal power of the group given by a relevant setpoint. Depending of the situation, load
reserves are calculated differently in two cases:
List of abbreviations:
ARstrt .. Actual Absolute reserve in kW or kVA - for BESS start calculation.
ARstp .. Actual Absolute reserves in kW or kVA - for BESS stop calculation.
RRstrt .. Actual Relative reserve in % - for BESS start calculation.
RRstp .. Actual Relative reserves in % - for BESS stop calculation.
ΣPgNom .. Sum of Nominal power of all Mains on the bus.
ΣPg*Nom .. Sum of Nominal power of all Mains on the bus apart of the one, which is going to be stopped.
ΣPgAct .. Sum of Actual power of all Mains on the bus = system load.
BaseLd .. Baseload is given by the setpoint #System Baseload (page 355)
Note: System starting sequences may be very different due to their complexity (i.e. Mains which do not take part
in power management, various nominal powers etc.). Each system should be considered individually.
Starting sequence
As written above, the power management is based on the load evaluation in order to provide enough of available
running power. An additional Mains starts when the load of the system raises above certain level to keep the load
reserve big enough. Following figure depicts the situation when an additional Mains is requested to join the
already running Mains(s) to the bus.
Stopping sequence
As it is written above, the power management is based on the load evaluation in order to provide enough of
available running power. An additional BESS stops when the load of the system drops below certain level to
avoid inefficient run of the BESS. Following figure depicts the situation when a BESS is requested to stop due to
the power management.
As shown above, the system load has decreased below the level defined by the stop condition – i.e. the load
reserve is over a limit given by the appropriate setpoint. Further explanation is provided in chapters Absolute
power management (page 280) and Relative power management (page 282).
The level is illustrated by the red dashed line. If the load reserve keeps over this limit for longer time than defined
by setpoint #Next Engine Stop Delay (page 511), the next BESS is actually requested to stop. Once the BESS
is unloaded, the BCB breaker is opened. Please note the sum of nominal power of all BESSs on the bus is
decreased by the nominal power of the stopped BESS. The cooling sequence follows before the BESS is actually
stopped. The BESS is ready to be started if the system load increases again.
Example: An example of absolute power management is shown on the figure below. There are three
BESSs with following choice of setpoints:
As it is shown on both figures above, the additional BESS is added once the actual load reserve is below the level
given by the appropriate setpoint of load reserve. The additional BESS is removed once the actual load reserve
is above the level set by appropriate setpoint of load reserve.
Example: An example of relative power management is shown on the figure below. There are three
BESSs with following choice of setpoints:
#Starting
#Power #Priority #Stopping
Nominal Power Rel Load
BESS management Priority Auto Rel Load
power management Reserve
mode Swap Reserve X
X
BESS
200 kW Enabled REL (%) 1 Disabled 35 % 40 %
#1
BESS
500 kW Enabled REL (%) 2 Disabled 35 % 40 %
#2
BESS
1 000 kW Enabled REL (%) 3 Disabled 35 % 40 %
#3
As it is shown on both figures above, the additional BESS is added once the actual load reserve is below the level
given by the appropriate setpoint of load reserve. The additional BESS is removed once the actual load reserve
is above the level set by appropriate setpoint of load reserve.
The green dashed line depicts the value of load at which the additional BESS is requested to start. This value of
the load value is linked with the setpoint #Starting Rel Load Reserve 1 (page 499) (or other selected reserve
set) in following way:
(100 % - #Starting Rel Load Reserve 1 (page 499) (or other selected reserve set)) * Sum of Nominal power =
Value of load when additional BESS requested to start in kW (in % of nominal power), e.g.: (100 % – 35 %) * 700
kW = 455 kW (65 % of nominal power).
The red dashed line depicts the value of load at which the additional BESS is requested to stop. This value of the
load value is linked with the setpoint #Stopping Rel Load Reserve 1 (page 499) (or other selected reserve set)
in following way:
Priorities
The priority of the BESS within the group is given by the setpoint Priority (page 492). Lower number represents
"higher" priority, i.e. a BESS with lower number starts before another one with higher number. In other words, the
setpoint Priority (page 492) means order in which BESSs are started and connected to the bus. An example is
shown on the figure below. There are four BESSs with following choice of setpoints:
#Starting
#Power #Priority #Stopping
Nominal Power Load
BESS management Priority Auto Load
power management Reserve
mode Swap Reserve X
X
BESS
200 kW Enabled ABS (kW) 4 Disabled 50 kW 70 kW
#1
BESS
200 kW Enabled ABS (kW) 3 Disabled 50 kW 70 kW
#2
BESS
200 kW Enabled ABS (kW) 2 Disabled 50 kW 70 kW
#3
BESS
200 kW Enabled ABS (kW) 1 Disabled 50 kW 70 kW
#4
By choosing the setpoint Priority (page 492) = 1, the BESS #4 is running all the time in the example shown on
the figure above (AUTO mode selected, Power management enabled and LBI GENERIC GENSET START/STOP
(PAGE 1004) activated).
The LBI TOP PRIORITY (PAGE 1030) can be used to force priority 0 into the setpoint Priority (page 492). Priority 0
is the "highest" one, which means the BESS will be running all the time while the power management is switched
on.
If more than one BESS have the same priority, they will act as "one big" BESS. There are methods of automatic
optimization of the priorities to achieve specific behavior of the group such as equalizing engine hours of the
BESSs or selection of optimal BESSs to run according to their size and current load demand.
6 back to Power Management
Case #1:
BESS 1 running hours = 250 -> running hours considered in RHE = 100 (150 - Run Hours Base (page
514))
The BESS 1 runs for 100 hours to equalize the RHE of both BESSs. The BESS 1 keeps running until the
difference between RHE1 and RHE2 exceeds #Run Hours Max Difference (page 515) (i.e. 10h). The BESS 1
runs 100 + #Run Hours Max Difference (page 515) + 1 = 100 + 10 + 1 = 111 hours. After 111 hours the BESSs
2 has the lowest RHE and the difference between RHE1 and RHE2 is higher than #Run Hours Max Difference
(page 515). The BESS 2 runs 11 hours to equalize the RHE of both BESSs and then additional #Run Hours
Max Difference (page 515) + 1 hours (i.e. 11 + 10 + 1 = 22 hours). The evaluation of RHE1 and RHE2 is shown
on the figure below.
Step 0 1 2 3 4 5
RHE1 100 211 211 233 233 255
RHE2 200 200 222 222 244 244
Run G1 (ΔRHE1) 0 111 0 22 0 22
Run G2 (ΔRHE2) 0 0 22 0 22 0
From the example of the case #1, it can be concluded that the BESSs are swapped after the duration determined
by following formula:
SwapTime = Second lowest considered running hours – Current lowest considered running hours + #Run Hours
Max Difference (page 515) +1
step 0 1 2 3 4 5 6 7 8 9 10 11 12 13
RHE1 0 11 11 11 11 33 33 33 33 55 55 55 55 77
RHE2 0 0 11 11 22 22 33 33 44 44 55 55 66 66
RHE3 0 0 0 22 22 22 22 44 44 44 44 66 66 66
Run G1
0 11 0 0 0 22 0 0 0 22 0 0 0 22
(ΔRHE1)
Run G2
0 0 11 0 11 0 11 0 11 0 11 0 11 0
(ΔRHE2)
Run G3
0 0 0 22 0 0 0 22 0 0 0 22 0 0
(ΔRHE3)
Case #3:
BESS 1 running hours = 250 -> running hours considered in RHE = 100 (150-RunHoursBase)
BESS 2 running hours = 450 -> running hours considered in RHE = 200 (250-RunHoursBase)
BESS 3 running hours = 750 -> running hours considered in RHE = 250 (500-RunHoursBase)
The BESS 1 has the lowest RHE1 = 100 h. By applying the SwapTime formula, we get the run time of BESS 2
before next swapping:
step 0 1 2 3 4 5 6 7 8 9 10 11 12 13
RHE1 100 211 211 232 233 255 255 255 272 272 272 288 288 288
RHE2 200 200 222 222 244 244 261 261 261 277 277 277 294 294
RHE3 250 250 250 250 250 250 250 266 266 266 283 283 283 299
Run G1
(ΔRHE 0 111 0 22 0 22 0 0 17 0 0 16 0 0
1)
Run G2
(ΔRHE 0 0 22 0 22 0 17 0 0 16 0 0 17 0
2)
Run G3
(ΔRHE 0 0 0 0 0 0 0 16 0 0 17 0 0 16
3)
Note: Setting #Run Hours Max Difference (page 515) = 5 does not mean that BESSs swap every 5 hours. The
Swap time is determined by the formula stated above. Please read the entire chapter Running hours
equalization for better understanding.
Note: In the case #Run Hours Max Difference (page 515) is set to 0 and all BESS in the group are at the same
initial point (RHE are equal), the BESS swapping happens every hour.
Efficiency
The BESSs engine priorities are automatically swapped to best fit to the actual load demand (load demand swap
- LDS). Also engine running hours are taken to the calculation (run hours equalization - RHE). This function is
activated via setpoint #Priority Auto Swap (page 493) = Efficiency.
The BESSs which should be currently running with actual load are shown in the values Actual Power Band 32
(page 860) and Actual Power Band 64 (page 860). The BESSs which should be running after #Power Band
Following table provide an example of BESS selection in function of system load evaluation. The table is an
example of Efficiency priority optimization function (#Power Management Mode (page 491) = ABS (kW) and
#Starting Load Reserve 1 (page 497) = 20 kW).
Total Running
System Relative load
Running BESSs Description power within PM
Load [kW] of BESSs [%]
[kW]
40 5 100 40
60 5 100 60
5 2 start
80 LDS 300 26
2 [0h] 5 stop
Setpoints #Min Run Power (page 509), #Min Run Power 2 (page 509) or #Min Run Power 3 (page 510) are
adjusted to 400 kW. Once the #Min Run Power (page 509), #Min Run Power 2 (page 509) or #Min Run
Power 3 (page 510) is activated, the available nominal running power has to be equal or higher to 400 kW. Even
if the load reserve is big enough to stop the Controller #2 (nominal power 500 kW), the Controller keeps running
as at least 400 kW has to be available. The Controller#1 (nominal power 200 kW) is not enough.
6 back to Power Management
Related
Loop type Related setpoints Related Operation
applications
Unloaded Run
Frequency Gain (page 469)
Frequency MINT, MPTM Synchronization
Frequency Int (page 470)
Single Island
Unloaded Run
Voltage Gain (page 482)
Voltage MINT, MPTM Synchronization
Voltage Int (page 482)
Single Island
Angle
MINT, MPTM Angle Gain (page 470) Phase Match Synchronization
regulation
Load Gain (page 471)
Load MINT, MPTM Parallel To Mains
Load Int (page 471)
PF Gain (page 483)
PF control MINT, MPTM Parallel To Mains
PF Int (page 483)
Load Sharing Gain (page 472)
Load sharing MINT Multiple Island
Load Sharing Int (page 472)
VAr Sharing Gain (page 484)
VAr sharing MINT Multiple Island
VAr Sharing Int (page 484)
Voltage, PF, VAr sharing have one common output = Voltage Request (page 866). The value of this output is
always composed from the contribution of each of the regulation loop.
Each of the regulation loops is active in some certain time during the process, which is given by the state of the
electronic state machine. If no regulation loop is active the Frequency Regulator Output (page 862) and
Power reduction is defined by Application Curve POWER OVER FREQUENCY (PAGE 975) which shall be adjusted
according to this formula:
After Mains/Bus Frequency (page 839) reaches (Nominal Frequency (page 384) + 0,2 Hz), BESS P (page
707) is stored in Pmom (page 829) and from this value is the power decreased.
Power is decreased/increased based on ramp (BESS Required P (page 861) is ramped to BESS Required P
Target (page 861)) that is corresponding with actual active event.
Note: If representative priority setpoint of actual active event is adjusted to OFF, then BESS Required P
(page 861) is ramped to BESS Required P Target (page 861) based on Load Ramp (page 477).
While power is reduced due to over frequency, LBO P OVER FREQUENCY ACTIVE (PAGE 1096) is closed.
Power increase is defined by Application Curve POWER UNDER FREQUENCY (PAGE 976) which shall be adjusted
according to this formula:
While power is increased due to under frequency, LBO P UNDER FREQUENCY ACTIVE (PAGE 1096) is closed.
The activation of the Load Reduction event is being signalized by closing the LBO EVENT LOAD REDUCTION (PAGE
1075). Once the LBO is closed the BESS Required P (page 861) will be ramped to the BESS Required P
Target (page 861) according to the ramp which maximum is given by the setpoint Installed Power (page 375)
or by the setpoint Nominal power (page 375) if the Installed Power is OFF. The duration of the whole ramp
(from the maximum to the 0) is given by the setpoint Load Reduction Ramp (page 552).
The event and LBO EVENT LOAD REDUCTION (PAGE 1075) stays active after deactivation of all LBIs until BESS
Required P (page 861) is ramped to the new unreduced BESS Required P Target (page 861) according to
Load Reduction Ramp (page 552). So, the event Load Reduction is active for both reducing and increasing the
power.
Each Grid Code has its priority over the other Grid Codes. The priority of the Load Reduction is given by the
setpoint Load Reduction Priority (page 551). If this priority is set to OFF, then BESS Required P (page 861)
will be ramped to the BESS Required P Target (page 861) according to the Load Ramp (page 477).
IMPORTANT: LBI LOAD REDUCTION ENABLE (PAGE 1007) has to be closed and setpoint Load Reduction
(page 549) has to be Enabled, otherwise Load Reduction is not activated by any of LBIs mentioned
bellow.
Example: When LBI LOAD REDUCTION 1 (PAGE 1006) is activated and setpoint Load Reduction 1 (page
549) = 50%, then BESS's load will be limited to 50% of Installed Power (page 375) or Nominal power
(page 375).
6.7 P For Q
The Grid codes connection requirements, namely for the medium voltage system, require a possibility of BESS
BESS P (page 707) reduction in order to achieve required BESS Q (page 708).
The function is enabled/disabled by setpoint P For Q Limitation (page 556) and behavior is adjusted by P For
Q Deadband (page 556).
If relative value of BESS Required Q (page 865) will be over limit, BESS P (page 707) will be decreased to
reach BESS Required Q (page 865). To prevent oscilation of BESS P (page 707) adjust properly P For Q
Deadband (page 556).
6.7.1 UQ Area
UQ area defines maximal reachable BESS Q (page 708) based on actual Mains voltage (Um). This area is
adjusted by P FOR Q UQ L (PAGE 977) - inductive part, and P FOR Q UQ C (PAGE 978) - capacity part.
Note: Um is counted as average of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page
839) and Mains/Bus Voltage L3-N (page 840) related to Mains/Bus Nominal Voltage Ph-N (page 381).
The area is used while BESS P (page 707) = +-5% of Installed Power (page 375) and BESS P (page 707) can
be reduced only if the required BESS Q (page 708) is inside this area, otherwise LBO UQ-C AREA LIMIT (PAGE
1109) respectively LBO UQ-L AREA LIMIT (PAGE 1109) is closed and BESS P (page 707) is not reduced. In case
this is fulfilled, LBO P FOR Q ACTIVE (PAGE 1096) is closed and BESS P (page 707) begins to be reduced using
P For Q Ramp (page 557). LBO EVENT P FOR Q (PAGE 1076) is closed while P For Q Ramp (page 557) is
being used.
Note: P For Q Ramp (page 557) has priority given by P For Q Priority (page 557), different ramp with
higher priority can be active.
6.7.2 PQ Area
PQ area defines maximal reachable BESS Q (page 708) based on actual BESS P (page 707) related to
Installed Power (page 375). This area is adjusted by P FOR Q PQ L (PAGE 979) - inductive part, and P FOR Q
PQ C (PAGE 980) - capacity part.
If the BESS starts to being unloaded in order to transfer Load to Mains and the LBO EVENT MAINS TRIP (PAGE
1076) is closed, the BESS Required P (page 861) will be ramped to the BESS Required P Target (page 861)
according to the ramp. So, the Mains is loaded according to the ramp which maximum is given by the setpoint
Installed Power (page 375) or by the setpoint Nominal power (page 375) if the Installed Power is OFF and the
duration of the ramp is given by the setpoint After Mains Trip Period Ramp (page 543).
Each Grid Code has its priority over the other Grid Codes. The priority of the After Mains Trip Period is given by
the setpoint After Mains Trip Period Priority (page 543).
7.1 PC
7.1.1 Direct communication 311
7.1.2 Remote communication 312
6 back to Communication
The second way is to switch the Ethernet to manual IP address mode. Adjust the setpoint IP Address Mode to
Manual option. In this moment values for related Ethernet port are immediately changed to values given by
the DHCP server for the LAN. If you are using this Ethernet port for connection to the controller you will lost
the connection. It is possible to configure the DHCP server to assign always the same IP address (i.e. static
IP address) to the particular controller according to it's MAC address.
6 back to Communication
7.2.1 SNMP
SNMP is an UDP-based client-server protocol used for providing data and events into a supervisory system
(building management system). The controller plays the role of a "SNMP Agent" while the supervisory system
plays the role of a "SNMP Manager".
Supported versions – SNMP v1, SNMP v2c and SNMP v3
The SNMP Agent function is to be enabled by the setpoint SNMP Agent (page 426). The setpoints SNMP
RD Community String (page 427) and SNMP WR Community String (page 427) in the same group can
be used to customize the "community strings" for the read and write operations which have function like
"passwords". All requests sent from the SNMP Manager have to contain community string which match with
the community string adjusted in the controller otherwise the controller refuses the operation.
MIB table
The "MIB table" (Management Information Base) is a table which gives to the Manager description of all
objects provided by the Agent.
The MIB table is specific for each controller type and configuration
The MIB table is to be exported from the controller configuration using InteliConfig
Controllers with identical firmware and configuration share also identical MIB table, however if the
configuration and/or firmware is not identical the MIB table is different and must be exported separately for
each controller.
The root node of the MIB table of InteliLite controller is enterprises.comapProjekt.il, which is
1.3.6.1.4.1.28634.14. Under this node there are following sub-nodes :
Notifications group (SMI v2 only) contains definitions of all notification-type objects that the Agent may
send to the Manager.
GroupRdFix contains read-only objects that exist in all controller regardless of the firmware version/type
and configuration.
GroupRdCfg contains read-only objects that depend on the firmware version/type and configuration.
GroupWrFix contains read-write objects that exist in all controller regardless of the firmware version/type
and configuration.
SMI version
In InteliConfig the MIB table may be exported in two different formats – SMI v1 and SMI v2. The format which
shall be used for export depends on the SNMP Manager and SMI version that it does support.
Typically, SMI v1 is used for SNMP v1 and vice versa, but it is not a rule and SMI v2 may be also used for
SNMP v1.
1) For list of commands, arguments and description of the procedure of invoking commands see the
description of the MODBUS protocol.
SNMP notifications
Except the request-response communication model, in which the communication is controlled by the
Manager, there are also messages that the Agent sends without any requests. These messages are called
„Notifications“ and inform the Manager about significant events occurred in the Agent.
The controller can send notifications to two different SNMP Managers (two different IP addresses). The
addresses are to be adjusted in the Group: ETH Interface 2 - Untrusted (page 412) by the setpoints SNMP
Traps IP Address 1 (page 427) and SNMP Traps IP Address 2 (page 428). If the Manager address is not
adjusted the particular notification channel is off. The controller will send the notifications in format adjusted
by the setpoint SNMP Trap Format (page 426).
Each notification (kind of event) is identified by an unique identifier (Trap ID in SNMPv1 or Notification OID
in SNMPv2/v3). This unique identifier gives the specific meaning to the notification message, e.g.
Protection 1. level - Fuel Level - alarm activated.
All possible notifications and their identifiers are listed in the MIB table.
The notification message also contains controller name, serial number and textual description of the
event.
Operational events
This events are used for SNMP traps. See the list below:
Start commands
Start button
Remote start
Modbus protocol is used for integration of the controller into a building management system or for remote
monitoring via 3rd party monitoring tools.
Modbus-RTU can be used via ⑮ RS 485 (page 47) . The serial speed for Modbus-RTU communication is
adjusted by the setpoint RS485 Modbus Speed (page 394) and the serial mode is adjusted by the
setpoint RS485 Modbus Mode (page 394). Only 1 client can be connected at once through this type of
connection.
Modbus/TCP (Modbus server) can be used with the Ethernet 1 (page 19) / Ethernet 2 (page 19) /
Ethernet 3 (page 19). Up to 3 clients can be connected simultaneously through each Ethernet interface.
The Modbus Server must be activated by the appropriate setpoint Modbus Server related to the
respective Ethernet interface. Timeout after which controller would terminate an inactive connection
(when client is not sending any requests) is set by setpoint ComAp Client Inactivity Timeout (page
679).
Note: Setpoint Modbus Client Inactivity Timeout (page 434) is common for both Ethernet 1 (page
19), Ethernet 2 (page 19) and Ethernet 3 (page 19) interfaces.
DO NOT READ ALARM LIST FROM MORE THAN 1 CLIENT! LOSS OF INFORMATION MAY OCCUR.
Modbus, Modbus/TCP protocol can be used simultaneously with direct Ethernet connection and the SNMP
agent.
Note: Recommended timeout for Modbus client is 300 ms.
IMPORTANT: Do not use setpoints for real-time control from super-ordinate systems. Frequent
repeated writing of setpoints would cause the history file getting overwritten and losing
important records.
In the image below you can see the topology using all 3 Ethernet ports. The ETH1 is used for Modbus Server,
connection of displays (IV5.2), or it can be also used for remote LAN connection. The ETH2 is used for
remote connection using the internet (WAN). The ETH3 is used for Modbus Client which is connected to the
LAN.
In the image below you can see the topology using all 3 Ethernet ports with one Modbus Client. The ETH1 is
used for connection of displays (IV5.2) or it can be also used for remote LAN connection. The ETH2 is used
for remote connection using the internet (WAN). The ETH3 is used for Modbus Server and Client which are
connected to the LAN with Modbus Devices.
In the image below you can see the topology using all 3 Ethernet ports with multiple Modbus Clients (CU 1 is
the first level client, CU 2 and CU 3 are second level clients). The ETH1 is used for Modbus Server,
connection of displays (IV5.2), or it can be also used for remote LAN connection. The ETH2 is used for
remote connection using the internet (WAN). The ETH3 is used for Modbus Clients which are connected
between CU 1 and other CUs, and between other CUs and Modbus Devices.
Note: The IP address of each device in the same network must vary.
Note: InteliVision 5.2 is used for illustrative purposes, the same wiring diagrams apply for all supported displays
mentioned in Displays (page 23).
Address space
The object address space is separated into several areas as described in the table below. The actual
mapping of specific controller data objects to specific Modbus addresses, which depends on configuration,
can be exported into a text file from the appropriate controller archive using InteliConfig. There are several
special registers with fixed meaning (reserved registers) which are listed in a separate table in this chapter.
Discrete inputs
The discrete inputs are read-only objects located in the address range 0-999. The source ComAp objects for
discrete inputs can be:
Single bit of any value of any binary type.
Protection (e.g. 2nd-level protection of the state "xyz"). The input is high if the protection is active
regardless of if it is configured or not.
Input registers
The input registers are read-only numeric values located in the address range 1000-2999. The source
ComAp objects can be:
Any controller value of any data type. The mapping of the particular data type into registers is described in
Mapping data types to registers (page 319).
Holding registers
The holding registers are read-write numeric values located in the address range 3000-3999. The source
ComAp objects can be:
Any controller setpoint of a primitive data type. The mapping of the particular data type into registers is
described in Mapping data types to registers (page 319).
Note: Setpoint must be configured with access level 0 to allow writing it via MODBUS.
Number of
Data type Meaning Data maping
registers
MSB = sign extension
Integer8 1-byte signed integer 1
LSB = value
MSB = 0
Unsigned8 1-byte unsigned integer 1
LSB = value
MSB = value, MSB
Integer16 2-byte signed integer 1
LSB = value, LSB
MSB = value, MSB
Unsigned16 2-byte unsigned integer 1
LSB = value, LSB
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
Integer32 4-byte signed integer 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
Unsigned32 4-byte unsigned integer 2 MSB1 = value, byte 3 (MSB)
Reserved registers
There are several registers with specific meaning. These registers are available in all controllers regardless of
the configuration.
Register Number of
Access Data type Meaning
addresses registers
4200 - 4201 2 read/write Time RTC Time in BCD code
4202 - 4203 2 read/write Date RTC Date in BCD code
Index of the language that is used for
4204 1 read/write Unsigned8 text data provided by Modbus (e.g.
alarmlist messages).
Last application error. To be read after
the device returns the exception code
4205 - 4206 2 read Unsigned32
04. It contains specific information about
the error.
Writing:command argument
4207 - 4208 2 read/write Unsigned32
Reading: command return value
4209 1 write Unsigned16 Command code
4010 1 - - Not implemented
4211 1 write Unsigned16 Password
4212 - 4213 2 read Unsigned32 Communication status
MSB 3 FC[3]
error ID (SPN) high word
LSB 3 FC[2]
MSB 4 FC[1]
error ID (SPN) low word
LSB 4 FC[0]
MSB 5 0
LSB 5 FMI failure mode identifier
MSB 6 0
LSB 6 OC occurence
MSB 7 0
LSB 7 SRC_ADDR ECU address
MSB 8 0
LSB 8 SRC_IDX ECU unit index
If Alarm format = ComAp Binary:
"Commands" are used to invoke a specific action in the controller via the communication channel. The list of
available actions is in the table below. The general procedure of writing a command via Modbus is as follows:
1. Write the command argument into the registers 44208-44209 (register addresses 4207-4208). Use
function 16.
2. Write the command code into the register 44210 (register address 4209). Use function 6.
3. (Optional) Read the command return value from the registers 44208-44209 (register addresses 4207-
4208). Use function 3.
4. If the command was executed the return value is as listed in the table. If the command was accepted but
there was an error during execution the return value indicates the reason:
a. 0x00000001 – invalid argument
b. 0x00000002 – command refused (e.g. controller not in MAN, breaker can not be closed in the
specific situation etc.)
Table: Values
Allowed MODBUS functions: 03, 04
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
BatteryVoltag Controller
01036 8213 V Integer 2 1 0 400
e I/O
We read value 240 from register 01036. From table of modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is 24.0 V.
Table: Values
Allowed MODBUS functions: 03, 04
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
Nominal Basic
01228 9018 kW Integer 2 0 0 32767
Power Settings
Table: Values
Allowed MODBUS functions: 03, 04
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
Binary Controller
01068 8235 Binary#2 2 0 - -
Inputs I/O
Binary inputs is 00010010. It means Binary input 2 and binary input 5 are active.
Note: You can use Modbus function 4 instead of 3, rest of data remain same (CRC differs).
Table: Binaries
Allowed MODBUS functions: 01, 02
Addresses Source Name of Bit Name
C.O.#
Modbus Addr. = Value Value Bit # Activated by protection Group
State #
Prot. Addr. = State Name of State (s):
00000 Value 8235 Binary Inputs 0 BCB Feedback Controller I/O
00001 Value 8235 Binary Inputs 1 MCB Controller I/O
00002 Value 8235 Binary Inputs 2 BESS Ready To Load Controller I/O
Note: Command and argument may be written as one "packet" (function 16) or you can split it and write
argument (function 16) and after that write command code (function 6).
Table: Setpoints
Allowed MODBUS functions: 03, 04, 06, 16
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
Nominal Basic
03008 8276 kW Unsigned 2 0 1 5000
Power Settings
Operating conditions
Operating temperature -40 °C to +70 °C
Storage temperature -40 ˚C to +80 ˚C
25/55°C, 48hours,95 % non-condensing
Operating humidity (norm 60068-2-30)
(EN 60068-2-30)
Protection degree IP20
5-25 Hz, ± 1.6 mm
Vibration
25-100 Hz, a = 4 g
2
Shocks a = 500 m/s
Surrounding air temperature rating 70 °C.
Suitable for pollution degree 2.
AC Current measurement
3ph BESS current
Measurement inputs
1ph Mains current (Auxiliary current)
Measurement range 1A/5A
Maximum continuous current 2 A / 10 A
Allowed overload 18 A for 15 sec.
Accuracy ±3 mA / ±15 mA for 0.0 to 0.4 A / 0.0 to 2.0 A0.75 % of value for 0.4 to 1.0 A / 2.0 to 5.0 A
Frequency range 40-70 Hz (accuracy 0.002 %)
Input impedance 0.68 MΩ ph-ph , 0.34 MΩ ph-n
AC Voltage measurement
3ph-n BESS voltage
Measurement inputs
3ph-n Mains voltage
115 V ph-N / 200 V ph-ph
suitable also for VTs output
Measurement range
231 V ph-N / 400 V ph-ph
UL, cUL: 346 V ph-N / 600 V ph-ph
Linear measurement and protection
433 V ph-N / 750 V ph-ph
range (maximal voltage)
Accuracy 0.25 %
Frequency range 40-70 Hz (accuracy 0.002 %)
Input impedance 0.72 MΩ ph-ph , 0.36 MΩ ph-n
Upper-harmonics filtering Active Low-Pass filter, Cutoff frequency 3100Hz (-3bB)
Measurement category CAT III, overvoltage category III
E-Stop
Dedicated terminal for safe Emergency Stop input.
Physically disconnects BO 1 & BO 2 from power supply.
Binary outputs
Number 12, non-isolated
Max. current 0.5 A
Switching to Positive supply terminal
Analog inputs
Number 4, switchable (R/U/I)
Range R = 0-10000 Ω; U = 0-10 V; I = 0-20 mA
R: 2 % from value for 0-250 Ω
R: 4% from value for 250-2500 Ω
Accuracy R: 6 % from value for 5000-10000 Ω
U: 1% from value ±100 mV
I: 1% from value ±200 uA
Analog output 1
Protection Reinforced isolation
Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
U: 1 % from value ±100 mV
Accuracy
I: 1 % from value ±200 uA
Analog output 2
Protection Basic isolation
Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
U: 1 % from value ±100 mV
Accuracy
I: 1 % from value ±200 uA
Communications
USB Device Basic isolation, USB type B
RS 485 Basic isolation
ETH1
ETH2 10/100 Mbit
ETH3
CAN 1A
CAN 2A Basic isolation, 1000/250/50 kbps
CAN 1B , nominal impedance 120 Ω
CAN 2B
Weight
Controller 750 g
Package 920 g
Controller handles 300 million records into the History, which represents roughly 1 record per second during 9,5 years. Shall be the History recording faster,
the controller lifetime will become smaller.
9.1.3 Setpoints
What setpoints are:
Setpoints are analog, binary or special data objects which are used for adjusting the controller to the specific
environment. Setpoints are organized into groups according to their meaning. Setpoints can be adjusted from
the controller front panel, PC, MODBUS, etc.
All setpoints can be protected by a password against unauthorized changes. Password protection can be
assigned to the setpoints during the configuration procedure.
IMPORTANT: Do not write setpoints repeatedly (e.g. power control from a PLC by repeated
writing of baseload setpoint via Modbus). The setpoints are stored in FRAM memory, which is
14
designed to withstand up to 10 read/write cycles without risk of damage or data loss, but it may
become damaged, when the allowed number of reading/writing cycles is exceeded.
For full list of setpoints go to the chapter List of setpoints (page 340).
SNMP Traps IP Address 2 428 Max Battery Cycles Per Day 441
Modbus Client Inactivity Timeout 429 Run Only Block Delay 1 443
Subgroup: ComAp Client Settings 429 Run Only Block Delay 2 444
Subgroup: Bus Meas Error 457 Frequency Governor Low Limit 467
Subgroup: Earth Fault Current Protection 457 Tau Frequency Governor Actuator 468
IDMT Earth Fault Current Sd 457 BESS Frequency Droop Slope 468
IDMT Earth Fault Current Delay 458 Subgroup: Regulation Loops 469
Subgroup: Earth Fault Current Protection 591 Battery SOC Shedding Level 1 609
Earth Fault Current Protection 592 Battery SOC Shedding Level 1 Delay 609
Subgroup: Loss of Mains Protections 593 Battery SOC Shedding Level 2 610
Vector Shift Protection 593 Battery SOC Shedding Level 2 Delay 610
Single parallel to mains application. The controller controls up to three breakers – a mains
MPTM breaker (MCB), BESS breaker (BCB), and/or PV breaker (PVCB). Feedbacks from all used
breakers are required.
Multiple island-parallel application without mains and multiple parallel application with mains.
MINT The controller controls up to two breakers – a BESS breaker and/or PV breaker. For parallel
to mains operation also mains breaker feedback is required.
Note: For more information about Applications, see chapter Applications overview (page 40).
Note: The controller also controls the NCB, check the chapter Breaker Control (page 126) for more
information about breakers.
Example: Baseload = 1000 kW, load = 700 kW, Import load = -100. Then
the Baseload request will be limited to 800 kW to prevent the Import power
go below -100 kW (actually it is limitation of the export).
The load of the BESS is controlled to keep constant level of base load of the whole
system. The level is adjusted by the setpoint #System Baseload (page 355).
BESS produces the certain amount of power to keep constant import/export from
Imp/Exp the Mains regardless the demand of the load. The source of requested
import/export is given by setpoint Load Request Source (page 353).
The total power of the group is controlled to constant level given by the setpoint
#System Baseload (page 355). Each loaded unit takes equal part (relative to
their nominal power) from this requested value. The load is regulated locally in
Baseload
each controller by Load control regulation loop, load-sharing is not active. The
setpoint #System Baseload (page 355) is also used for determining which unit
have to run or not.
The load is controlled by the supervisor (IM1010) controller to share the total load
(given by the setpoint #System Baseload (page 355)) with other loaded units in
Load Shar
such a way, that all loaded units will be loaded at the same level (relative to their
nominal power). Load-sharing regulation loop is active.
Note: The Load Shar mode shall be used in case the supervisor (IM1010) controller is present in the
system. In systems without the supervisor (IM1010) controller the setpoint must be setup to the
Baseload option.
Note: The power factor (PF) is regulated to constant level given by the setpoint #System PF
Control PTM (page 358) in parallel to Mains operation and does not depend on active load control
mode.
#System Baseload
The BESS Power Factor (page 710) is controlled according to preset required
PF Control
value. See PF Control (page 266)PF/Q control (page 262) for more information.
Grid Codes specific functionality where the power factor depends on the actual
PF(Pm) power of the BESS. See PF(Pm) (page 267)PF/Q control (page 262) for more
information.
The BESS Q (page 708) is controlled according to preset required value. See PF
Q Control
Control (page 266)PF/Q control (page 262) for more information.
Grid Codes specific functionality where the BESS Required Q (page 865) depends
on the mains voltage (Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage
Q(Um)
L2-N (page 839) and Mains/Bus Voltage L3-N (page 840)). See Q(Um) (page
268)PF/Q control (page 262) for more information.
Grid Codes specific functionality where the BESS Required Q (page 865) depends
Q(P) on the BESS P (page 707). See Q(P) (page 269)PF/Q control (page 262) for
more information.
Grid Codes specific functionality where the BESS Required Q (page 865) depends
on the mains voltage (Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage
Qref/Ulim L2-N (page 839) and Mains/Bus Voltage L3-N (page 840)) with a modified
behavior. See Qref/Ulim (page 270)PF/Q control (page 262) for more
information.
Actual selected control mode is available in System PF/Q Control (page 864).
PF/Q
PF/Q Regulation Type PF/Q Control PTM
Request Source
(page 358) Mode (page 356)
Source
Base Power Factor (page
PF Control
Base PF/ Q Control 359)
Q Control Base Q (page 360)
Setpoint
Import Power Factor (page
PF Control
Imp/Exp PF/ Q Control 359)
Q Control Import Q (page 361)
PF CONTROL: ANEXT BASE
PF Control
PF (PAGE 1124)
Base PF/ Q Control
Q CONTROL: ANEXT BASE Q
Q Control
Analog (PAGE 1147)
External Value PF CONTROL: ANEXT
PF Control
IMP/EXP PF (PAGE 1125)
Imp/Exp PF/ Q Control
Q CONTROL: ANEXT IMP/EXP
Q Control
Q (PAGE 1147)
See PF Control (page 266)PF/Q control (page 262) for more information.
Application Mode (page 885) = MINT
PF/Q
#System PF Control
Request Source
PTM (page 358)
Source
Base PF #System Power Factor (page 360)
Setpoint
Base Q #System Base Q (page 361)
Analog Base PF PF CONTROL: ANEXT BASE PF (PAGE 1124)
External Value Base Q Q CONTROL: ANEXT BASE Q (PAGE 1147)
See PF/Q control (page 262) for more information.
Note: If the setpoint value is >1 the BESS Load Character is C, if the setpoint value is <0 the BESS
Load Character is L.
Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.
Base Q
#System Base Q
Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.
Note: This setpoint is available only for the MINT application, in case of the MPTM application the
NCB automatically behaves like this setpoint is set to COMMON option.
Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.
Note: Open transfer is performed, if the Open option is selected with Transfer
BESS To Mains (page 475) or Transfer Mains To BESS (page 474)
Behaves like the full manual control but the Island operation is disabled.
Example: When MCB is opened and BCB is pressed, controller does not
Islnd Disl go to island.
Mains Measurement P
The value Mains Import P (page 842) is not measured. The duration of the load
None transfer in direction Mains to BESS is given exactly by the setpoint Close
Transfer Max Duration (page 473).
The value Mains Import P (page 842) is measured via Mains CT which is located
Mains CT on phase L1. The load transfer in direction Mains to BESS is considered to be
finished when the Mains is unloaded under certain level.
The value Mains Import P (page 842) is measured via analog input, accordingly
Analog
LAI: MAINS MEASUREMENT P (PAGE 1124). The load transfer in direction Mains to
Input
BESS is considered to be finished when the Mains is unloaded under certain level.
The value Mains Import Q (page 843) is not measured. The duration of the load
None transfer in direction Mains to BESS is given exactly by the setpoint Close
Transfer Max Duration (page 473).
The value Mains Import Q (page 843) is measured via Mains CT which is located
Mains CT on phase L1. The load transfer in direction Mains to BESS is considered to be
finished when the Mains is unloaded under certain level.
The value Mains Import Q (page 843) is measured via analog input, accordingly
Analog
LAI: MAINS MEASUREMENT Q (PAGE 1124). The load transfer in direction Mains to
Input
BESS is considered to be finished when the Mains is unloaded under certain level.
Peak Shaving
The Peak shaving (page 1) function is active and its behaviour is set by setpoints
Enabled Peak Shaving Start Level (page 366), Peak Shaving Stop Level (page 366)
and Peak Shaving Start/Stop Delay (page 367).
The Peak shaving (page 1) function is BLOCKED and the start command can not
Disabled
be activated even the conditions for Peaks Shaving activation were fulfilled.
The value of the load consumption Load P (page 828) exceeds the value given
Starts when
by the setpoint Peak Shaving Start Level (page 366).
The value of the load consumption Load P (page 828) decreases under the
Stop when
value given by the setpoint Peak Shaving Stop Level (page 366)
MCB Logic
Note: LBO MCB CLOSE/OPEN (PAGE 1090) as well as this setpoint is used only for contactors.
The breaker is controlled only from controller. Any unexpected change of BCB
FEEDBACK (PAGE 991) causes Stp BCB Fail (page 1290) immediately.
Internal
Incorrect reaction of the BCB FEEDBACK (PAGE 991) on internal BCB
Close/Open command causes Stp BCB Fail (page 1290)
BCB Openning BCB FEEDBACK (PAGE 991) = 0 is accepted from external
devices with history record "BCB Opened Externally".
Follow
Incorrect reaction of the BCB FEEDBACK (PAGE 991) to internal BCB
Close/Open command causes Stp BCB Fail (page 1290)
Controller does not control the BCB is controlled externally, when the BCB
FEEDBACK (PAGE 991) get changed, then the event "BCB Opened" or "BCB
Closed" is recorded to the history log.
Controller always accept the BCB FEEDBACK (PAGE 991) without of issuing
External any alarm.
When the Sd protection shuts down the BESS, the BCB stays closed. BCB
stays closed until it is opened externally.
IMPORTANT: BESS with closed BCB is not blocked against starting.
IMPORTANT: Anytime when the controller is synchronizing via BCB the External BCB
closing is being accepted in all BCB control modes.
The controller takes full control of the PV Circuit Breaker (PVCB), using its built-in
Internal
settings and logic. It doesn't listen to external commands; it operates by itself.
The controller still manages the PVCB, just like in "Internal" mode. However, it can
Follow
also listen to external command for opening the circuit breaker.
Not The PV Circuit Breaker isn't part of your system. In this case, the controller runs
Installed your PV system on its own, as if the PVCB doesn't exist.
Note: Hot Swap Redundancy function can be enabled only if you have correct SW Key (page 388).
BESS
PV
WT
Mains
Gensets
Subgroup: Name
Samax
Installed Power
Nominal Current
Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1
Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1
Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1
Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1
3Ph CT Location
Connection type
BESS VT Ratio
Note: If MonoPhase wiring is used the ranges are approximately corresponding to 116 V, 231 V, and
346 V Ph-N.
IMPORTANT: The range has to be set to fit the expected range of the AC voltage.
Bus
Example:
No VT is in use - voltage conversion is 1/1
Bus VT Ratio = 1.00
VT 22kV/100V - voltage conversion is 22000/100
Bus VT Ratio = 220.00
VT 3.3kV/110V - voltage conversion is 3300/110
Bus VT Ratio = 30.00
Note: If MonoPhase wiring is used the ranges are approximately corresponding to 116 V, 231 V, and
346 V Ph-N.
IMPORTANT: The range has to be set to fit the expected range of the AC voltage.
Phase Rotation
Nominal Frequency
Controller Mode
Power On Mode
Previous Controller is switched into the last mode before power off.
OFF Controller is switched into OFF mode.
Note: Remote modes - In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint - controller mode is forced into mode selected via
LBI. After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode
Horn Timeout
Note: Horn timeout starts again from the beginning if any new alarm appears before previous Horn
timeout has elapsed.
Battery Undervoltage
Battery Overvoltage
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 1 .. 64 [-]
Default value 1 [-] Force value NO
Step 1 [-]
Comm object 23999 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts Controller's CAN Address which is used for CAN Intercontroller Communication
(page 132).
This type of communication is used to share information between other ComAp controllers via CAN
interface (Communication peripherals (page 18)).
Note: Each controller connected via CAN has to have unique address, i.e. maximally 64 controllers
can be connected together.
Note: There is an exception, if the function Hot Swap Redundancy (page 160) is used, the Master
and Backup controllers has to have same address because they act like one controller unit for the
rest of the site.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] OFF; 1 .. 64 [-]
Default value 0 Force value NO
Step 1
Comm object 23832 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This Setpoint has to be set to the specific address. The Universal Gensets will be then represented
across the whole system as a genset with this address.
It is recommended to set the Address as CAN Address of InteliNeo + 1. The default settings 0=OFF
means that the Universal Genset Support Function is not in use. The InteliNeo actually creates the virtual
genset inside the system. The information about this virtual genset can be observed in all genset related
information inside the system like CAN 16, CAN32, GL 16, GL 32, Reg 16, Reg 32 Values. Universal
genset is always located in the same group as InteliNeo which integrates it into the system.
6 back to List of setpoints
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 1 .. 32 [-]
Default value 1 [-] Force value NO
Step 1 [-]
Comm object 24019 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts Controller’s Terminal Address which is used for communication with other devices
using terminals ETH1, ETH2, and RS485 (Communication peripherals (page 18)). This type of
communication is used fore remote or local connection of the computer (InteliConfig), Display, Modbus
Server, etc.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Force value NO
Step [-]
Comm object 24141 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts communication speed ofModbus-RTU, Modbus/TCP (page 316).
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 8N1 / 8N2 / 8E1 [-]
Default value 8N1 Force value NO
Step [-]
Comm object 24020 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts communication mode of Modbus-RTU, Modbus/TCP (page 316).
Possible options
8N1 8 data bits, 1 stop bit, no parity
8N2 8 data bits, 2 stop bits, no parity
8E1 8 data bits, 1 stop bit, even parity
LB/UART Log
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 11327 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables/disables logging of connection/disconnection of each remote terminal. The record
is written to the history.
Note: The terminal is disconnected automatically after 1 min of inactivity and next communication
request from the same terminal is considered as a new connection. When logging is enabled in
certain conditions the history may be filled up with large number of records related to the
communication and important record may be overwritten quite fast.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Enabled / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24026 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables CAN Intercontroller Communication Redundancy (page 132).
Note: In case that there is a mismatch between this setpoint and actual state of ⑦ CAN2B (page 46)
alarm ALI Redundant CAN Error (page 1273) is activated.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 32C / 16C / 8C / 64C CAN FD / 32C CAN FD / 8C CAN FD [-]
Default value 8C Force value NO
Step [-]
Comm object 24499 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects the mode of intercontroller communication. Options 32C or 8C are necessary to use
in order to ensure the communication between InteliNeo6000 and older controllers such as IGS-NT,
IG2GSC, IG200, IG500. Options 64C CAN FD, 32C CAN FD and 8C CAN FD are compatible only with
controllers which support the CAN FD communication.
Note: It is strongly recommended to use CAN FD modes if all controllers on-site support the CAN FD
communication.
Mode Arbitration Bit-Rate Data Bit-Rate Maximal Bus Length Max Bus Length With Repeater
32C 250 kbit 250 kbit 200 m 800 m
16C 125 kbit 125 kbit 400 m 1600 m
8C 50 kbit 50 kbit 900 m 3600 m
64C CAN FD 250 kb 2 Mbit 200 m Not tested
32C CAN FD 125 kb 1 Mbit 400 m Not tested
8C CAN FD 50 kb 400 kbit 900 m Not tested
IMPORTANT: All controllers communicating on common CAN have to use the same mode of
this setpoint.
IMPORTANT: All changes made to the setpoint takes effect after the restart of the controller.
Note: In case that there is a mismatch between this setpoint and value CAN Intercontroller Comm
Mode (page 888), alarm ALI CAN Mode Inconsistency (page 1271) is activated.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Enabled / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 9921 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable CAN2 Intercontroller Empty Check.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Optional/ Required[-]
Default value Optional Force value NO
Step [-]
Comm object 23842 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Switching the Access Lock mode of operation so that the lock can be forced to be used to control the
controller.
Option Optional = Locking the lock does not condition the ability to operate the machine, it only allows
you to cut off other users if necessary.
Option Required = The lock is required for control, i.e. I have to lock with my account to control the
controller.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled/ Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 23840 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Option to automatically unlock Access Lock if the owner of the lock is no longer logged into any active
session on the controller.
when the controller detects that the lock is locked but its owner is no longer
ENABLED
logged in any session, it automatically unlocks the lock
the lock remains locked regardless of whether the owner is logged in or not, it is
DISABLED
only unlocked manually (by the owner or administrator)
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled; 1 .. 10 [-]
Default value Disabled Force value NO
Step [-]
Comm object 23841 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
The number of concurrent sessions in which the same user is allowed to log in.
In the DISABLED state the controller behaves as it does in standard version, i.e. does not limit the
number of connections in which the same user is logged in. A user can log in with several connections at
the same time.
In the active state, each individual user can log into as many connections as is set by this setpoint.
Note: This feature does not apply to users in the administrator role and does not apply to the implicit
user.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Unmount / Mount / Format [-]
Default value Unmount Force value NO
Step [-]
Comm object 23997 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint determines whether the SD card is mounted, unmounted, or should be formatted. After
formatting, the setpoint is automatically switched to the mount option. If the setpoint is set to unmount no
interaction with the SD card is allowed, the controller will only detect that the SD card is inserted.
IMPORTANT: This setpoint has to be set to Mount in order to allow any writing function to
the SD card.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 23995 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables/disables writing of long term history onto the SD card.
Note: Setpoint SD Card File System (page 401) - has to be adjusted to Mount.
Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled/Enabled
Default value Disabled Force value NO
Step -
Comm object 17339 Related applications MINT, MPTM
Config level Standard
Setpoint visibility When setpoint Hot Swap Redundancy (page 371) = Disabled
Description
This setpoint allows to change the behavior on CAN1 communication terminals.
By default, CAN1A terminal is used for communication with ECU and IO Modules, CAN1B terminal is
used for Hot Swap Redundancy (page 160). By enabling this setpoint, the CAN1A terminal can be
used only for ECU, the CAN1B can be used only for IO Modules.
Note: In case that CAN1 ECU/IOModules Split (page 402) is enabled, the Hot Swap Redundancy
(page 160) is disabled (and vice versa).
Ethernet port 1
Ethernet Port
Setpoint group Related FW 1.5.0
Configuration
Trusted Interface / Untrusted Interface / Modbus Interface / Trusted
Range [units]
Mirroring / Untrusted Mirroring / Modbus Mirroring [-]
Trusted
Default value Force value NO
Interface
Step [-]
Comm object 23873 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the interface type on ethernet slot 1.
Trusted Interface - It is expected that these interfaces are operated locally inside a closed
environment / infrastructure where additional measures against misuse or attack take place (e.g.
physical access limitation). Due to nature of this interface less strict cybersecurity rules apply at it and
that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted Interface - This interface is a general-purpose one and it is expected that it may be
exposed to public networks, such as Internet, which are not under control of the entity operating the
controller. Thus, strict cybersecurity rules apply for this type of interface.
Modbus Interface - This type of interface is used for Modbus communication. It is not possible to
connect to the controller using this interface.
Trusted Mirroring/Untrusted Mirroring/Modbus Mirroring - If mirroring mode is selected for a
socket, the switch will be configured that except sending traffic belonging normally to that socket, it
will also copy to that socket all traffic from other sockets assigned to the same network.
Note: Only one socket can be adjusted to mirroring function. If multiple sockets are adjusted to
mirroring function the alarm ALI Ethernet Port Inconsistency will be still displayed after the CU restart.
Ethernet Port
Setpoint group Related FW 1.5.0
Configuration
Trusted Interface / Untrusted Interface / Modbus Interface / Trusted Mirroring /
Range [units]
Untrusted Mirroring / Modbus Mirroring [-]
Default value Trusted Interface Force value NO
Step [-]
Comm object 23872 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the interface type on ethernet slot 2.
Trusted Interface - It is expected that these interfaces are operated locally inside a closed
environment / infrastructure where additional measures against misuse or attack take place (e.g.
physical access limitation). Due to nature of this interface less strict cybersecurity rules apply at it and
that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted Interface - This interface is a general-purpose one and it is expected that it may be
exposed to public networks, such as Internet, which are not under control of the entity operating the
controller. Thus, strict cybersecurity rules apply for this type of interface.
Modbus Interface - This type of interface is used for Modbus communication. It is not possible to
connect to the controller using this interface.
Trusted Mirroring/Untrusted Mirroring/Modbus Mirroring - If mirroring mode is selected for a
socket, the switch will be configured that except sending traffic belonging normally to that socket, it
will also copy to that socket all traffic from other sockets assigned to the same network.
Note: Only one socket can be adjusted to mirroring function. If multiple sockets are adjusted to
mirroring function the alarm ALI Ethernet Port Inconsistency will be still displayed after the CU restart.
Ethernet Port
Setpoint group Related FW 1.5.0
Configuration
Trusted Interface / Untrusted Interface / Modbus Interface / Trusted Mirroring /
Range [units]
Untrusted Mirroring / Modbus Mirroring [-]
Default value Modbus Interface Force value NO
Step [-]
Comm object 23871 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the interface type on ethernet slot 3.
Trusted Interface - It is expected that these interfaces are operated locally inside a closed
environment / infrastructure where additional measures against misuse or attack take place (e.g.
physical access limitation). Due to nature of this interface less strict cybersecurity rules apply at it and
that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted Interface - This interface is a general-purpose one and it is expected that it may be
exposed to public networks, such as Internet, which are not under control of the entity operating the
controller. Thus, strict cybersecurity rules apply for this type of interface.
Modbus Interface -This type of interface is used for Modbus communication. It is not possible to
connect to the controller using this interface.
Trusted Mirroring/Untrusted Mirroring/Modbus Mirroring - If mirroring mode is selected for a
socket, the switch will be configured that except sending traffic belonging normally to that socket, it
will also copy to that socket all traffic from other sockets assigned to the same network.
Note: Only one socket can be adjusted to mirroring function. If multiple sockets are adjusted to
mirroring function the alarm ALI Ethernet Port Inconsistency will be still displayed after the CU restart.
IP Address Mode
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] Manual / Automatic / Disabled [-]
Default value Automatic Force value YES
Step [-]
Comm object 24063 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the method how the ethernet connection is adjusted on Ethernet 1 (page
19).
IMPORTANT: When the mode is switched from Automatic to Manual the TCP/IP settings
will be changed to the values in the related setpoints. In case you are using Ethernet 1 to
connect the CU you will be disconnected. Turn off the setpoint hiding function to
manually change the TCP/IP settings to same values obtained via DHCP so you will not be
disconnected when changing mode.
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.1.1 Force value NO
Step [-]
Comm object 24061 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 406) = Manual
Description
The setpoint is used to select the method how the IP Address is adjusted on Ethernet 1 (page 19).
If IP Address Mode (page 406) = Manual, this setpoint is used to adjust the IP address of the Ethernet
1 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 406) = Automatic this setpoint is inactive. The IP address is assigned by the
DHCP server.
Note: Only valid IP address can be inserted.
Subnet Mask
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 15 characters [-]
Default value 255.255.255.0 Force value NO
Step [-]
Comm object 24059 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
The setpoint is used to select the method how the Subnet Mask is adjusted on Ethernet 1 (page 19).
If IP Address Mode (page 406) = Manual, this setpoint is used to adjust the Subnet Mask. Ask your IT
specialist for help.
If IP Address Mode (page 406) = Automatic this setpoint is inactive. The Subnet Mask is assigned by
the DHCP server.
Note: Only valid IP address can be inserted.
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.1.1 Force value NO
Step [-]
Comm object 24057 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 406) = Manual
Description
This setpoint is used to select the method how the Gateway IP is adjusted on Ethernet 1 (page 19) .
If IP Address Mode (page 406) = Manual, this setpoint is used to adjust the IP address of the gateway
of the network segment where the controller is connected.
If IP Address Mode (page 406) = Automatic this setpoint is used to display the gateway IP which has
been assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or the
internet.
Note: Only valid IP address can be inserted.
IP Firewall
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] Enabled / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24029 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints enables or disables the built-in Firewall (page 157) functionality for Ethernet 1 (page
19).
IMPORTANT: Loss of connection can happen when enabling the firewall and using remote
connection via Internet
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] DES / 3DES / AES128 / AES256 [-]
Default value AES128 Force value NO
Step [-]
Comm object 23856 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Selects SNMP v3 Privacy Protocol.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] MD5 / SHA / SHA256[-]
Default value SHA Force value NO
Step [-]
Comm object 23857 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Selects SNMP v3 Authentication Protocol.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] NONE/ AUTH-NOPRIV / AUTH-PRIV [-]
Default value NONE Force value NO
Step [-]
Comm object 23855 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Selects SNMP v3 security level. If NONE the agent will work in SNMP v2c mode..
Modbus Server
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24034 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables Modbus communication via Ethernet 1 (page 19).
ETH Interface 1 -
Trusted
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
ETH Interface 3 -
Modbus
Range [units] 0 .. 65535 [s]
Default value 60 s Force value NO
Step 1s
Comm object 24097 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Modbus connection (TCP socket) is closed by controller, if a Modbus client does not communicate for
this time.
Note: This setpoint is shared with other Modbus Client Inactivity Timeout setpoints.
ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 65535 [-]
Default value 23 [-] Force value YES
Step 1 [-]
Comm object 24035 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This port is used to listen for an incoming TCP connection on Ethernet 1 (page 19).
ETH Interface 1 -
Setpoint group TrustedETH Interface 2 Related FW 1.5.0
- Untrusted
Range [units] 0 .. 65535 [s]
Default value 60 s Force value YES
Step 1s
Comm object 24098 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Connection (TCP socket) is closed by controller, if a client (e.g. InteliConfig) does not communicate for
this time. This timeout applies to both direct and AirGate connection.
Note: This setpoint is shared with ComAp Client Inactivity Timeout (page 411).
IP Address Mode
ETH Interface 2 -
Setpoint group Untrusted Related FW 1.5.0
Ethernet
Range [units] Manual / Automatic / Disabled [-]
Default value Automatic Force value NO
Step [-]
Comm object 24259 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the method how the ethernet connection is adjusted on Ethernet 2 (page
19).
Manual: The Ethernet connection is fixed by means of the setpoints IP Address (page
413), Subnet Mask (page 413), Gateway IP (page 414), DNS IP Address 1
(page 415), DNS IP Address 2 (page 416). This method should be used for a
classic Ethernet or internet connection. When this type of connection opens,
the controller is specified by its IP address. This means that it would be
inconvenient if the IP address were not fixed (static).
Automatic: The Ethernet connection settings is obtained automatically from the DHCP
server. The obtained settings is shown in related values. If the process of
obtaining the settings from the DHCP server is not successful, the values
000.000.000.000 are shown.
Disabled: The Ethernet terminal is disabled.
IMPORTANT: When the mode is switched from Automatic to Manual the TCP/IP settings
will be changed to the values in the related setpoints. In case you are using Ethernet 2 to
connect the CU you will be disconnected. Turn off the setpoint hiding function to
manually change the TCP/IP settings to same values obtained via DHCP so you will not be
disconnected when changing mode.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.2.254 Force value NO
Step [-]
Comm object 24376 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
The setpoint is used to select the method how the IP Address is adjusted on Ethernet 2 (page 19).
If IP Address Mode (page 412) = Manual, this setpoint is used to adjust the IP address of the Ethernet
2 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 412) = Automatic this setpoint is inactive. The IP address is assigned by the
DHCP server.
Note: Only valid IP address can be inserted.
Subnet Mask
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 255.255.255.0 Force value NO
Step [-]
Comm object 24375 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
The setpoint is used to select the method how the Subnet Mask is adjusted on Ethernet 2 (page 19).
If IP Address Mode (page 412) = Manual this setpoint is used to adjust the Subnet Mask. Ask your IT
specialist for help with this setting.
If IP Address Mode (page 412) = Automatic this setpoint is inactive. The Subnet Mask is assigned by
the DHCP server.
Note: Only valid IP address can be inserted.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.2.1 Force value NO
Step [-]
Comm object 24373 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
This setpoint is used to select the method how the Gateway IP is adjusted.
If IP Address Mode (page 412) = Manual, this setpoint is used to adjust the Gateway IP address of the
Ethernet 2 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 412) = Automatic this setpoint is inactive. The Gateway IP address is
assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or Internet.
Note: Only valid IP address can be inserted.
IP Firewall
ETH Interface 2 -
Setpoint group Untrusted Related FW 1.5.0
Ethernet
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Related
Comm object 24092 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
This setpoints enables or disables the built-in Firewall (page 157) functionality for Ethernet 2 (page
19).
IMPORTANT: Loss of connection can happen when enabling the firewall and using remote
connection via Internet
ETH Interface 2 -
Setpoint group Untrusted Related FW 1.5.0
Ethernet
Range [units] Manual / Automatic [-]
Default value Automatic Force value
Step [-]
Comm object 24101 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Automatic
Description
This setpoint enables to enter DNS server addresses for Ethernet 2 (page 19) manually, even with the
IP Address Mode (page 412) set to Automatic.
Automatic: DNS server addresses are automatically obtained from a DHCP server.
DNS IP Address 1 (page 415) and DNS IP Address 2 (page 416) can be
adjusted manually. Use this option to resolve e.g. internet access policy related
Manual:
issue, if local DNS server addresses automatically obtained from a DHCP server
do not work
DNS IP Address 1
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 8.8.8.8 Force value NO
Step [-]
Comm object 24362 Related applications MINT, MPTM
Config level Standard
Only if IP Address Mode (page 412) = Manual OR (IP Address Mode (page 412)
Setpoint visibility
= Automatic AND DNS Mode (page 415) = Manual)
Description
This setpoint allows to set DNS IP Address 1 for Ethernet 2 (page 19) manually.
Note: Only valid IP address can be inserted.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 4.4.4.4 Force value NO
Step [-]
Comm object 24331 Related applications MINT, MPTM
Config level Standard
Only if IP Address Mode (page 412) = Manual OR (IP Address Mode (page 412)
Setpoint visibility
= Automatic AND DNS Mode (page 415) = Manual)
Description
This setpoint allows to set DNS IP Address 2 for Ethernet 2 (page 19) manually.
Note: Only valid IP address can be inserted.
AirGate Connection
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 24365 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables AirGate connection (page 116) function.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 31 characters [-]
Default value global.airgate.link Force value NO
Step [-]
Comm object 24364 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free
AirGate server provided by ComAp at global.airgate.link.
AirGate Port
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 65535 [-]
Default value 54440 [-] Force value NO
Step 1 [-]
Comm object 24096 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This port is used for TCP communication with the AirGate server.
Note: Use port 5440 for standard ComAp AirGate service.
Event Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 18971 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Event Messages.
Wrn Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8482 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Warning Messages.
Al Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10567 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Alarm Only messages.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10568 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of History Record Only messages.
ALI Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 18993 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Alarm List Indication messages.
AHI Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 18994 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
XYZ.
ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8484 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Shutdown Messages.
Sd Override Message
ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 11413 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Shutdown Override Messages.
MP Message
ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10117 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Mains Protection messages.
PVBO Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10926 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of PVBO Messages.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Depends on controller’s supported languages. [-]
Default value English Force value NO
Step [-]
Comm object 24299 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to set the language of Event, Warning, etc. e-mails.
E-mail Address 1
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24298 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.
E-mail Address 2
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24297 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.
E-mail Address 4
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24144 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Related
Comm object 23877 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the username for the SMTP server. Leave the setpoint blank if the SMTP
server does not require authentication.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..15 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23876 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the password for the SMTP server. Leave the setpoint blank if the SMTP server
does not require authentication.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value global.airgate.link:9925 Force value NO
Step [-]
Comm object 24093 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name (e.g. smtp.yourprovider.com) or IP address (e.g.
74.125.39.109) and port number (e.g. :9925) of the SMTP server. Ask your internet provider or IT
manager for this information.
Example: Enter the IP address "74.125.39.109" and port number "9925" as
"74.125.39.109:9925".
Note: You may use also any public SMTP server which does not require connection over SSL/TLS
channels.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23878 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter an existing email address into this setpoint. This address will be used as sender address in active
e-mails that will be sent from the controller.
Note: It is not needed to enter an existing email address, nevertheless valid email format needs to be
followed.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] NONE / SSL/TLS / STARTTLS [-]
Default value NONE Force value NO
Step [-]
Comm object 24076 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects encryption type for SMTP session.
SNMP Agent
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / SNMP v1/v2c / SNMP v3 [-]
Default value Disabled Force value NO
Step [-]
Comm object 24336 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints Enables or disables Simple Network Management Protocol (SNMP) Agent.
Note: SNMP v3 has upgraded encryption, remote configuration, and security (extra setpoints are
available).
Note: It is supported only User-Based security model (USM, RFC-3414). View-based Access
Control Model (VACM, RFC-3415) is not supported.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] v1 Trap / v2 Notific / v2 Inform [-]
Default value v2 Inform Force value NO
Step [-]
Comm object 24136 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
This setpoint selects format of the SNMP trap messages.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value public Force value NO
Step [-]
Comm object 24335 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
SNMP Community String only for reading.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value private Force value NO
Step [-]
Comm object 24334 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v1/v2c
Description
SNMP Community String for writing and reading.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 63 characters [-]
Default value - Force value NO
Step [-]
Comm object 24095 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
IP address 1 for receiving SNMP Traps. Leave this setpoint blank if SNMP traps should not be send.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Valid IP address [-]
Default value - Force value NO
Step [-]
Comm object 24094 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
IP address 2 for receiving SNMP Traps. Leave this setpoint blank if SNMP traps should not be send.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 31 characters [-]
Default value - Force value NO
Step [-]
Comm object 23851 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Defines SNMP v3 Engine User Name.
Modbus Server
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24337 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enables or disables Modbus communication via Ethernet 2 (page 19).
ETH Interface 1 -
Trusted
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
ETH Interface 3 -
Modbus
Range [units] 0 .. 65535 [s]
Default value 60 s Force value NO
Step 1s
Comm object 24097 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Modbus connection (TCP socket) is closed by controller, if a Modbus client does not communicate for
this time.
Note: This setpoint is shared with other Modbus Client Inactivity Timeout setpoints.
Direct Connection
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 24099 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enable/disable direct connection of a ComAp client (e.g. InteliConfig) to the IP
address of the controller.
Note: For Direct connection the controller IP address must be reachable from the client IP
address.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 65535 [-]
Default value 23 [-] Force value NO
Step 1 [-]
Comm object 24374 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This port is used to listen for an incoming TCP connection on Ethernet 2 (page 19).
ETH Interface 1 -
Setpoint group TrustedETH Interface 2 Related FW 1.5.0
- Untrusted
Range [units] 0 .. 65535 [s]
Default value 60 s Force value YES
Step 1s
Comm object 24098 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Connection (TCP socket) is closed by controller, if a client (e.g. InteliConfig) does not communicate for
this time. This timeout applies to both direct and AirGate connection.
Note: This setpoint is shared with ComAp Client Inactivity Timeout (page 430).
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24075 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to enable/disable synchronization of the controller's time with the exact time from a
NTP server.
NTP Server
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 63 characters [-]
Default value pool.ntp.org Force value NO
Step [-]
Comm object 24074 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
NTP server address for time synchronization.
Note: Only valid IP address or domain can be inserted.
IP Address Mode
ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] Manual / Automatic / Disabled [-]
Default value Automatic Force value NO
Step [-]
Comm object 24049 Related applications MINT, MPTM
Manual: The Ethernet connection is fixed by means of the setpoints IP Address (page
432), Subnet Mask (page 432) and Gateway IP (page 433). This method
should be used for a classic Ethernet or internet connection. When this type of
connection opens, the controller is specified by its IP address. This means that
it would be inconvenient if the IP address were not fixed (static).
Automatic: The Ethernet connection settings is obtained automatically from the DHCP
server. The obtained settings is shown in related values. If the process of
obtaining the settings from the DHCP server is not successful, the values
000.000.000.000 are shown.
Disabled: The Ethernet terminal is disabled.
IP Address
ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] 0 .. 15 characters [-]
Default value 192.168.3.254 Force value NO
Step [-]
Comm object 24047 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 431) = Manual
Description
The setpoint is used to select the method how the IP Address is adjusted on Ethernet 3 (page 19).
If IP Address Mode (page 431) = Manual, this setpoint is used to adjust the IP address of the Ethernet
3 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 431) = Automatic this setpoint is inactive. The IP address is assigned by the
DHCP server.
Note: Only valid IP address can be inserted.
Subnet Mask
ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] 0 .. 15 characters [-]
Default value 255.255.255.0 Force value NO
Gateway IP
ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] 0 .. 15 characters [-]
Default value 192.168.3.1 Force value NO
Step [-]
Comm object 24043 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 431) = Manual
Description
This setpoint is used to select the method how the Gateway IP is adjusted.
If IP Address Mode (page 431) = Manual, this setpoint is used to adjust the Gateway IP address of the
Ethernet 3 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 431) = Automatic this setpoint is inactive. The Gateway IP address is
assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or Internet.
Note: Only valid IP address can be inserted.
Modbus Type
ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] Modbus Client / Modbus Server / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 23868 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables the Modbus Client or Server on the Modbus Interface.
ETH Interface 1 -
Trusted
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
ETH Interface 3 -
Modbus
Range [units] 0 .. 65535 [s]
Default value 60 s Force value NO
Step 1s
Comm object 24097 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Modbus connection (TCP socket) is closed by controller, if a Modbus client does not communicate for
this time.
Note: This setpoint is shared with other Modbus Client Inactivity Timeout setpoints.
The BESS inverter cannot produce AC voltage on its output without being
connected to the healthy bus. The BESS must be precharged by AC voltage
AC Precharge
for time given by the setpoint Precharge Time (page 1). The BCB is allowed
to be closed only if the bus is helthy.
The BCB is allowed to be closed and connect healthy output of the BESS to
DC Precharge the dead bus. But If the bus is healthy and output of the BESS inverter is dead,
BCB cannot be closed.
BESSReady to Load TO
The controller receives a BESS P REQUEST (PAGE 1116) from the LAI
Analog
BESS P REQUEST (PAGE 1116) which is used as direct BESS Power Request.
The value of BESS P REQUEST (PAGE 1116) is given by setpoints BESS Charge
Setpoint
Power (page 436) or BESS Discharge Power (page 437).
The BESS P REQUEST (PAGE 1116) is calculated using internal controller's
Balance
algorithms. This calculation maintain the balance of energy flow trough the system.
Gen P Min
The reactive power is regulated according to the the LAI BESS Q REQUEST (PAGE
Analog
1116) which is used as direct BESS Power Request.
The PF of the BESS is regulated so the Gen-sets (system) has the constant PF
Balance
which is defined by the setpoint Gensets PF Required (page 438).
Gensets PF Required
Stop Time
Power Switch On
Short Circuit
Note: Reaction time is limited to 3600 s = 60 minutes. IDMT protection is not active for Reaction time
values longer than 60 minutes.
BESS >V
Value Alarm
BESS Voltage L1-N (page 713) Sd BESS >V L1-N (page 1283)
BESS Voltage L2-N (page 713) Sd BESS >V L2-N (page 1283)
BESS Voltage L3-N (page 713) Sd BESS >V L3-N (page 1283)
BESS Voltage L1-L2 (page 713) Sd BESS >V L1-L2 (page 1283)
BESS Voltage L2-L3 (page 714) Sd BESS >V L2-L3 (page 1284)
BESS Voltage L3-L1 (page 714) Sd BESS >V L3-L1 (page 1284)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
BESS >>V
BESS <V
BESS V Unbalance
BESS >f
Group: PV Settings
Subgroup: PF Control
PV Array Area 1
PV Array Area 2
PV Array Area 3
PV Calib. Offset 1
PV Calib. Offset 2
PV Calib. Offset 4
Group: WT Settings
Subgroup: PF Control
Group: Curtailment
Subgroup: Curtailment
Curtailment
Gain
Gen P Min
PV/WT Ramp Up
Raising the voltage on the BESS inverter regulator causes BESS frequency
Positive
to rise.
Raising the voltage on the BESS inverter regulator causes BESS frequency
Negative
to go down.
Frequency/Load
Setpoint group Related FW 1.5.0
Control
Range [units] 0 .. 20 [%]
Default value 2 Force value NO
Step 0.01
Comm object 19450 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the slope of the load droop correlation. The slope is set as a droop of frequency in
percentages of the requested system frequency (Nominal Frequency (page 384)) on the range of the
requested power from 0 to 100% of Nominal power (page 375).
Frequency Gain
Angle Gain
Note: See the chapter Regulation Loops (page 295) for more information.
Load Int
Transfer of the load from Mains to BESS without parallel work and
synchronization (one breaker opens and second is closed - checking
Open
feedbacks). The setpoint Open Transfer Min Break (page 473) sets the
minimal duration of break.
Transfer of the load from Mains to BESS with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Only
Duration (page 473).
In case of synchronization fail, MCB stays close and BESS is stopped.
Transfer of the load from Mains to BESS with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Prim
Duration (page 473).
In case of synchronization fail, open transfer is done.
Transfer of the load from Mains to BESS with parallel work and soft loading of
the BESS. This function is proceeded like the closed transfer, but there is time
limitation of loading of theBESS adjusted via setpoint Load Ramp (page
SoftTransf
477). The transfer is succeed only when theBESS is fully loaded – Mains is
fully unloaded (level of load when Mains is considered as unloaded is adjusted
via setpoint Mains Unload MCB Open Window (page 476)).
Note: Close transfer of load is also affected by setpoint Mains Measurement P (page 364).
Note: The behavior of transition of load in MAN mode is adjusted via setpoint CB Control In MAN
Mode (page 362).
Transfer of the load from BESS to Mains without parallel work and
synchronization (one breaker opens and second is closed - checking
Open
feedbacks). The setpoint Open Transfer Min Break (page 473) sets the
minimal duration of break.
Transfer of the load from BESS to Mains with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Only
Duration (page 473).
In case of synchronization fail, BCB stays closed and BESS keeps running.
Transfer of the load from BESS to Mains with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Prim
Duration (page 473).
In case of synchronization fail, open transfer is done.
Transfer of the load from BESS to Mains with parallel work and soft unloading
of the BESS. This function is proceeded like the closed transfer, but there is
time limitation of unloading of the BESS adjusted via setpoint Load Ramp
SoftTransf
(page 477). The transfer is succeed only when the BESS is fully unloaded
(level of load when BESS is considered as unloaded is adjusted via setpoint
Generator Unload BCBOpen Level (page 476)).
Note: The behavior of transition of load in SEM mode is adjusted via setpoint CB Control In MAN
Mode (page 362).
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).
IMPORTANT: This window and the setpoint Minimal Power PTM (page 1) must be set in
the way where MCB opening will not be blocked by Minimal Power PTM level while all
available BESSs are running in Load Shar.
Note: This setpoint is window. It means that when you adjust this setpoint to 10%, there is window
from -10% to +10%. The reason is Import/Export function.
Note: This setpoint is shared with Soft Unload Ramp (page 568)
Raising the voltage on the remote voltage adjustment input causes the BESS
Positive
voltage to raise.
Raising the voltage on the remote voltage adjustment input causes the BESS
Negative
voltage to go down.
Frequency/Load
Setpoint group Related FW 1.5.0
Control
Range [units] 0 .. 20 [%]
Default value 1 Force value NO
Step 0.001
Comm object 19449 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the slope of the droop correlation. The slope is set as a droop of voltage in
percentages of the generator nominal voltage (BESS Nominal Voltage Ph-N (page 380)) on the range
of the requested reactive power from 0 to 100% of nominal reactive power (value of nominal reactive
power is not given by setpoint but it is calculated from setpoint BESS Nominal Voltage Ph-Ph (page
380) whilst the PF=0,8).
Voltage Gain
Voltage Int
PF Int
Subgroup: Synchronization
Synchronization Type
Note: Synchronization is not allowed if there is any already synchronized Mains Controller in the
control group.
Voltage Window
Dwell Time
BCB Latency
Power Management
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).
Note: If more than one unit have the same priority they will act as “one big” unit.
Note: The main idea of renewables is to run with the maximal priority. So it is expect the Microgrid
site will not be influenced by the power management because BESS and renewables shloud always
run.
Note: The setpoint is relevant with function Universal Genset in InteliNeo and does not affects the
BESS.
IMPORTANT: LBI Top Priority (page 1030) can be used only if #Priority Auto Swap =
Disabled.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
The Source with active Slow Stop protection regulates its power to value 20% of its
Nominal Power but only in if does not lead to overloading of other gensets or running
No them under 20%. Then it stays in load sharing. This mode is ended once the capacity of
other genset with lowest priority is available (load reserve is sufficient) or latest when
Slow Stop Delay elapsed.
The Source with active Slow Stop protection stay in load sharing until another gen-set is
Yes
connected to the bus or after the Slow Stop Delay is elapsed.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.
Control Group
Group Link R
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 1 .. 45 [°]
Default value 10 ° Force value YES
Step 1°
Comm object 9843 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Vector Shift Protection (page 593) is not Disabled
Description
This setpoint adjusts the threshold level for the Vector Shift Protection (page 593).
Note: To adjust this setpoint properly, check the value Max Vector Shift (page 848). The value is
available in InteliConfig, contains the maximal measured vector shift value since the BESS has been
synchronized to the mains and after opening of BCB or MCB it is "frozen". In normal conditions the
value should not be higher than 3 º and the most common setting of the threshold is about 7 º.
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 3 .. 30 [-]
Default value 5 Force value YES
Step 1 [-]
Comm object 9990 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF1 Protection (page 594) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF1 Protection (page 594).
It defines the number of periods of the Mains voltage in which the ROCOF protection is evaluated. The
higher length of the ROCOF window means less sensitive protection for short oscillations of the
frequency to both directions from the nominal value. Also, the delay of evaluation is higher.
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 1.00 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 9844 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF1 Protection (page 594) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF1 Protection (page 594).
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.1 .. 2.5 [s]
Default value 0.5 s Force value YES
Step 0.1 s
Comm object 16137 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF2 Protection (page 595) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF2 Protection (page 595).
It defines the time interval for which the ROCOF protection is evaluated. The higher length of the ROCOF
window means less sensitive protection for short oscillations of the frequency to both directions from the
nominal value. Also, the delay of evaluation is higher.
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 2.00 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 16141 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF2 Protection (page 595) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF2 Protection (page 595).
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.1 .. 2.5 [s]
Default value 1.0 s Force value YES
Step 0.1 s
Comm object 16138 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF3 Protection (page 596) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF3 Protection (page 596).
It defines the time interval for which the ROCOF protection is evaluated. The higher length of the ROCOF
window means less sensitive protection for short oscillations of the frequency to both directions from the
nominal value. Also, the delay of evaluation is higher.
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 1.50 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 16142 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF3 Protection (page 596) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF3 Protection (page 596).
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.1 .. 2.5 [s]
Default value 2.0 s Force value YES
Step 0.1 s
Comm object 16139 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF4 Protection (page 597) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF4 Protection (page 597).
It defines the time interval for which the ROCOF protection is evaluated. The higher length of the ROCOF
window means less sensitive protection for short oscillations of the frequency to both directions from the
nominal value. Also, the delay of evaluation is higher.
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 1.25 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 16143 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF4 Protection (page 597) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF4 Protection (page 597).
Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] MCB / BCB [-]
Default value MCB Force value YES
Step [-]
Comm object 10552 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and
Vector Shift Protection (page 593)!= Disabled or
ROCOF1 Protection (page 594)!= Disabled or
Setpoint visibility
ROCOF2 Protection (page 595)!= Disabled or
ROCOF3 Protection (page 596)!= Disabled or
ROCOF4 Protection (page 597)!= Disabled .
Description
This setpoint adjusts which breaker will be opened when Vector Shift Protection (page 593), ROCOF1
Protection (page 594), ROCOF2 Protection (page 595), ROCOF3 Protection (page 596) or
ROCOF4 Protection (page 597) is detected.
Note: If the BCB is selected and a mains failure occurs the BCB will be opened immediately when
the vector shift or ROCOF is detected, however MCB will be also opened due to other mains
protections such as Mains <f Protection (page 588) or Mains <V Protection (page 581).
Mains >V
Mains >>V
Mains <<V
Mains >f
Load Reduction
Note: LBI Load Reduction Enable (page 1007) has to be closed, otherwise this Setpoint has no
effect.
Load Reduction 1
Load Reduction 3
Note: If priority is set to OFF, Load Reduction Ramp (page 552) is not applied.
P(Um)
Disabled
Enabled
P(Um) Ramp
P For Q Limitation
P For Q Deadband
Note: If priority is set to OFF, P For Q Ramp (page 557) is not applied.
P For Q Ramp
Q&U Protection
Note: This protection is evaluated only if Application Mode (page 885) = MPTM and Breaker state
(page 886) = ParalOper.
Q&U < Q
Q&U CB Selector
MCB When Q&U Protection (page 558) is activated, MCB breaker opens.
BCB When Q&U Protection (page 558) is activated, BCB breaker opens.
Note: Reclosing of breaker is forbidden if Wrn Q&U Protection (page 1262) is present in the alarm list.
Dynamic Support
Q Ramp
Q Deadband
Q(Um) 0 Reference
Q(Um) Deadband
Qref/Pnom Shift
Qref/Ulim Deadband
Q(P) Deadband
Note: This setpoint is shared with Soft Unload Ramp (page 479)
Pave Protection
Pave
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
Overcurrent
Overcurrent IDMT Delay
≤100 % 101 % 110 %
0.2 s No action 20 s 2s
Reaction Time
2s No action 200 s 20 s
20 s No action 2000 s 200 s
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Connection
type (page Compared values (maximum difference)
378)
3Ph4Wire
High Leg D
(BESS Current L1 (page 715),BESS Current L1 (page 715)
3Ph3Wire
SplitPhase
MonoPhase No protection is evaluated.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
BESS >V
Value Alarm
BESS Voltage L1-N (page 713) Sd BESS >V L1-N (page 1283)
BESS Voltage L2-N (page 713) Sd BESS >V L2-N (page 1283)
BESS Voltage L3-N (page 713) Sd BESS >V L3-N (page 1283)
BESS Voltage L1-L2 (page 713) Sd BESS >V L1-L2 (page 1283)
BESS Voltage L2-L3 (page 714) Sd BESS >V L2-L3 (page 1284)
BESS Voltage L3-L1 (page 714) Sd BESS >V L3-L1 (page 1284)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Value Alarm
BESS Voltage L1-N (page 713) Sd BESS >>V L1-N (page 1281)
BESS Voltage L2-N (page 713) Sd Mains/Bus >>V L2-N (page 1281)
BESS Voltage L3-N (page 713) Sd BESS >>V L3-N (page 1282)
BESS Voltage L1-L2 (page 713) WRN BESS >>V L1-L2 (page 1282)
BESS Voltage L2-L3 (page 714) WRN BESS >>V L2-L3 (page 1282)
BESS Voltage L3-L1 (page 714) WRN BESS >>V L3-L1 (page 1282)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Value Alarm
BESS Voltage L1-N (page 713) Sd BESS <V L1-N (page 1284)
BESS Voltage L2-N (page 713) Sd BESS <V L2-N (page 1284)
BESS Voltage L3-N (page 713) Sd BESS <V L3-N (page 1285)
BESS Voltage L1-L2 (page 713) Sd BESS <V L1-L2 (page 1285)
BESS Voltage L2-L3 (page 714) Sd BESS <V L2-L3 (page 1285)
BESS Voltage L3-L1 (page 714) Sd BESS >V L3-L1 (page 1284)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Connection
type (page Compared values (maximum difference)
378)
BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS
Voltage L3-N (page 713)
3Ph4Wire OR
BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and
BESS Voltage L3-L1 (page 714)
BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and
High Leg D
BESS Voltage L3-L1 (page 714)
BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and
3Ph3Wire
BESS Voltage L3-L1 (page 714)
BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS
SplitPhase
Voltage L3-N (page 713)
MonoPhase No protection is evaluated.
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Connection type
Compared values (maximum difference)
(page 378)
Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page
839) and Mains/Bus Voltage L3-N (page 840)
3Ph4Wire OR
Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
840) and Mains/Bus Voltage L3-L1 (page 840)
Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
High Leg D
840) and Mains/Bus Voltage L3-L1 (page 840)
Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
3Ph3Wire
840) and Mains/Bus Voltage L3-L1 (page 840)
Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page
SplitPhase
839) and Mains/Bus Voltage L3-N (page 840)
MonoPhase No protection is evaluated.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
Igen = Maximum (BESS Current L1 (page 715), BESS Current L2 (page 715), BESS Current L3
(page 715))
Example:
IDMT Earth Fault Current Sd (page 457) = 10 A
Igen [A]
Delay [s]
≤10 A 11 A 20 A
0.1 No Reaction 1 0.1
Reaction Time
1 No Reaction 10 1
[s]
10 No Reaction 100 10
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
Rising edge of LBI MANUAL LOAD RECONNECTION (PAGE 1011) lowers the load
Disabled reduction stage by one while BESS P (page 707) drops under Power Load
Reconnection Level (page 604).
Load reduction stage is lowered by one when BESS P (page 707) drops under
Enabled Power Load Reconnection Level (page 604) and period of Load Reconnection
Delay (page 602) elapsed from last load reduction stage lowering.
Load shedding LBO is deactivated if and only if the Source Frequency remains
Enabled smaller than the specified value for the duration given by the setpoint Battery SOC
Shedding Level 1 Delay (page 609).
Load is reconnected only if rising edge on LBI MANUAL LOAD RECONNECTION (PAGE
1011) is received and the Source Frequency is smaller than Frequency Load
Disabled
Reconnection Level, Battery SOC Shedding Level 1 Delay (page 609) is
disregarded.
User Button 1
COMMAND User Button 1 is controlled by command from External display (page 79).
Value of the User Button 1 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 1 is still 0.
User Button 2
COMMAND User Button 2 is controlled by command from External display (page 79).
Value of the User Button 2 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 2 is still 0.
COMMAND User Button 3 is controlled by command from External display (page 79).
Value of the User Button 3 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 3 is still 0.
User Button 4
COMMAND User Button 4 is controlled by command from External display (page 79).
Value of the User Button 4 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 4 is still 0.
COMMAND User Button 5 is controlled by command from External display (page 79).
Value of the User Button 5 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 5 is still 0.
User Button 6
COMMAND User Button 7 is controlled by command from External display (page 79).
Value of the User Button 7 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 7 is still 0.
User Button 8
COMMAND User Button 8 is controlled by command from External display (page 79).
Value of the User Button 8 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 8 is still 0.
COMMAND User Button 9 is controlled by command from External display (page 79).
Value of the User Button 9 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 9 is still 0.
User Button 10
COMMAND User Button 10 is controlled by command from External display (page 79).
Value of the User Button 10 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 10 is still 0.
COMMAND User Button 11 is controlled by command from External display (page 79).
Value of the User Button 11 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 11 is still 0.
User Button 12
COMMAND User Button 12 is controlled by command from External display (page 79).
Value of the User Button 12 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 12 is still 0.
COMMAND User Button 13 is controlled by command from External display (page 79).
Value of the User Button 13 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 13 is still 0.
User Button 14
COMMAND User Button 14 is controlled by command from External display (page 79).
Value of the User Button 14 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 14 is still 0.
COMMAND User Button 15 is controlled by command from External display (page 79).
Value of the User Button 15 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 15 is still 0.
User Button 16
COMMAND User Button 16 is controlled by command from External display (page 79).
Value of the User Button 16 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 16 is still 0.
COMMAND User Button 17 is controlled by command from External display (page 79).
Value of the User Button 17 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 17 is still 0.
User Button 18
COMMAND User Button 18 is controlled by command from External display (page 79).
Value of the User Button 18 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 18 is still 0.
COMMAND User Button 19 is controlled by command from External display (page 79).
Value of the User Button 19 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 19 is still 0.
User Button 20
COMMAND User Button 20 is controlled by command from External display (page 79).
Value of the User Button 20 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 20 is still 0.
COMMAND User Button 21 is controlled by command from External display (page 79).
Value of the User Button 21 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 21 is still 0.
User Button 22
COMMAND User Button 22 is controlled by command from External display (page 79).
Value of the User Button 22 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 22 is still 0.
COMMAND User Button 23 is controlled by command from External display (page 79).
Value of the User Button 23 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 23 is still 0.
User Button 24
COMMAND User Button 24 is controlled by command from External display (page 79).
Value of the User Button 24 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 24 is still 0.
COMMAND User Button 25 is controlled by command from External display (page 79).
Value of the User Button 25 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 25 is still 0.
User Button 26
COMMAND User Button 26 is controlled by command from External display (page 79).
Value of the User Button 26 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 26 is still 0.
COMMAND User Button 27 is controlled by command from External display (page 79).
Value of the User Button 27 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 27 is still 0.
User Button 28
COMMAND User Button 28 is controlled by command from External display (page 79).
Value of the User Button 28 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 28 is still 0.
COMMAND User Button 29 is controlled by command from External display (page 79).
Value of the User Button 29 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 29 is still 0.
User Button 30
COMMAND User Button 30 is controlled by command from External display (page 79).
Value of the User Button 30 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 30 is still 0.
COMMAND User Button 31 is controlled by command from External display (page 79).
Value of the User Button 31 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 31 is still 0.
User Button 32
COMMAND User Button 32 is controlled by command from External display (page 79).
Value of the User Button 32 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 32 is still 0.
Time
Date
Scheduler; CM-4G-
Setpoint group Related FW 1.5.0
GPS
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 Force value NO
Step [-]
Comm object 24366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information
about sending time, which may result in confusion when the respective problem actually occurred.
The fast history running in background is mirrored into the controller history records when a second level
alarm occurs. Alarms that initialized flipping of the post-mortem history are: Shut down (SD), Slow stop
(STP), Overspeed, Short Current, Breaker open & cool-down (BOC), Low power (LOP), Off load (OFL).
Premortem history contains the same values in the history as the configuration done by configuration tool
(GenConfig, InteliConfig). When any new alarm (SD, BOC, LOP, OFL, STP, Overspeed, short current)
appears for the second time, only the new history records are added into the controller history log.
Subgroup: Sunrise/Sunset
Sunrise/Sunset Function
Sunrise/Sunset Longtitude
Timer 1 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 2 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 3 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 4 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 5 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 6 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 7 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 8 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 9 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 10 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 11 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Timer 12 Function
IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.
Group: Geo-Fencing
Subgroup: Geo-Fencing
Geo-Fencing
Home Latitude
Note: This value can be also obtained automatically via logical binary input Geo Home Position. In
case of activation of this binary input for at least 2 seconds, setpoint will be adjusted automatically
from actual coordinates from GPS signal.
Home Longitude
Note: This value can be also obtained automatically via logical binary input Geo Home Position. In
case of activation of this binary input for at least 2 seconds, setpoint will be adjusted automatically
from actual coordinates from GPS signal.
Fence 1 Protection
Fence 1 Radius
Subgroup: Fence 2
Fence 2 Protection
Fence 2 Delay
Time Zone
Scheduler; CM-4G-
Setpoint group Related FW 1.5.0
GPS
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 Force value NO
Step [-]
Comm object 24366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information
about sending time, which may result in confusion when the respective problem actually occurred.
Subgroup: Slot A
Slot A
Subgroup: Slot B
Slot B
Group: CM-RS232-485
COM1 Mode
Possible options
8N1 8 data bits, 1 stop bit, no parity
8N2 8 data bits, 2 stop bits, no parity
8E1 8 data bits, 1 stop bit, even parity
COM2 Mode
Possible options
8N1 8 data bits, 1 stop bit, no parity
8N2 8 data bits, 2 stop bits, no parity
8E1 8 data bits, 1 stop bit, even parity
Internet Connection
Network Mode
DNS Mode
Automatic DNS server addresses automatically obtained from a DHCP server are used
DNS IP Address 1 (page 676) and DNS IP Address 2 (page 677) can be
adjusted manually. Use this option to resolve e.g. internet access policy related
Manual
issue, if local DNS server addresses automatically obtained from a DHCP server
do not work
DNS IP Address 1
IP Firewall
AirGate Connection
DISABLED: Only SMS are sent. Internet-enabled SIM card is not required. AirGate is not used.
ENABLED This mode uses the "AirGate" service. Internet-enabled SIM card must be used.
The AirGate server address is adjusted by the setpoint AirGate Address (page
678).
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
AirGate Address
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 31 characters [-]
Default value global.airgate.link Force value NO
Step [-]
Comm object 24364 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free
AirGate server provided by ComAp at global.airgate.link.
ETH Interface 1 -
Setpoint group TrustedETH Interface 2 Related FW 1.5.0
- Untrusted
Range [units] 0 .. 65535 [s]
Default value 60 s Force value YES
Step 1s
Comm object 24098 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Connection (TCP socket) is closed by controller, if a client (e.g. InteliConfig) does not communicate for
this time. This timeout applies to both direct and AirGate connection.
Note: This setpoint is shared with ComAp Client Inactivity Timeout (page 679).
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 23961 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this to enable/disable direct connection of a ComAp client (e.g. InteliConfig) to the IP address of the
controller.
Note: For Direct connection the controller IP address must be reachable from the client IP address.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 1 .. 65535 [-]
Default value 23 Force value NO
Step [-]
Comm object 23960 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This port is used to listen for an incoming TCP connection if Direct Connection is ENABLED.
6 back to List of setpoints
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value global.airgate.link:9925 Force value NO
Step [-]
Comm object 23962 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name (e.g. smtp.yourprovider.com) or IP address (e.g.
74.125.39.109) or number of port (with colon like a first mark) of the SMTP server. Ask your internet
provider or IT manager for this information.
Note: You may use also any public SMTP server which does not require connection over SSL/TLS
channels.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23884 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter an existing email address into this setpoint. This address will be used as sender address in active
e-mails that will be sent from the controller.
Note: It is not needed to enter an existing email address, nevertheless valid email format needs to be
followed.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Related
Comm object 23883 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the username for the SMTP server. Leave the setpoint blank if the SMTP
server does not require authentication.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..15 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23882 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the password for the SMTP server. Leave the setpoint blank if the SMTP server
does not require authentication.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] NONE / SSL/TLS / STARTTLS [-]
Default value NONE Force value NO
Step [-]
Comm object 23965 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects encryption type for SMTP session.
E-mail Address 1
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24298 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24144 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.
E-mail Address 3
E-mail Address 2
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24297 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.
Telephone Number 1
Telephone Number 2
Telephone Number 4
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Depends on controller’s supported languages. [-]
Default value English Force value NO
Step [-]
Comm object 24299 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to set the language of Event, Warning, etc. e-mails.
PVBO Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10926 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of PVBO Messages.
Sd Message
ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8484 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Shutdown Messages.
Wrn Message
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8482 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Warning Messages.
GPS Tracking
Time Zone
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 Force value YES
Step [-]
Comm object 24366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information
about sending time, which may result in confusion when the respective problem actually occurred.
Invalid flag
If valid data is not available for a particular value, the invalid flag is set to it. This situation may be due to the
following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as “####” in InteliConfig and on the controller screen. If such a
value is read out via MODBUS, it will contain the data 32768 in the case of signed values and 65535 in the
case of unsigned values.
Mains Voltage 1min Avg L2-N 850 BESS Required Relative P 862
Mains Voltage 1min Avg L3-N 850 Frequency Regulator Output 862
Mains Voltage 10min Avg L1-L2 851 BESS Frequency Required 862
Mains Voltage 10min Avg L2-L3 851 BESS Frequency Offset 862
Mains Voltage 1min Avg L1-L2 851 System Load Control 863
Mains Voltage 1min Avg L2-L3 852 Group: Voltage/PF Control 864
Mains Voltage 1min Avg L3-L1 852 System PF/Q Control 864
BESS P
BESS P L1
BESS P L2
BESS P L3
BESS Q L1
BESS Q L2
BESS Q L3
BESS S L1
BESS S L2
BESS S L3
BESS Voltage
BESS Current L1
BESS Current L2
BESS Current L3
BESS SOC
Slip Frequency
Slip Angle
Group: PV
Subgroup: PV Aggregated
PV Nominal P
PV Actual Q
PV Actual S
Curtailment Output
PV Max P
PV Curtailed P Relative
Subgroup: PV 1
PV 1 Nominal P
PV 1 Actual P
PV 1 Actual Q
Subgroup: PV 2
PV 2 Nominal P
PV 2 Actual Q
PV 2 Actual S
Subgroup: PV 3
PV 3 Nominal P
PV 3 Actual P
PV 3 Actual Q
Subgroup: PV 4
PV 4 Nominal P
PV 4 Actual Q
PV 4 Actual S
Subgroup: PV 5
PV 5 Nominal P
PV 5 Actual P
PV 5 Actual Q
Subgroup: PV 6
PV 6 Nominal P
PV 6 Actual Q
PV 6 Actual S
Subgroup: PV 7
PV 7 Nominal P
PV 7 Actual P
PV 7 Actual Q
Subgroup: PV 8
PV 8 Nominal P
PV 8 Actual Q
PV 8 Actual S
Subgroup: PV 9
PV 9 Actual P
PV 9 Nominal P
PV 9 Actual Q
Subgroup: PV 10
PV 10 Nominal P
PV 10 Actual Q
PV 10 Actual S
Subgroup: PV 11
PV 11 Nominal P
PV 11 Actual P
PV 11 Actual Q
Subgroup: PV 12
PV 12 Nominal P
PV 12 Actual Q
PV 12 Actual S
Subgroup: PV 13
PV 13 Nominal P
PV 13 Actual P
PV 13 Actual Q
Subgroup: PV 14
PV 14 Nominal P
PV 14 Actual Q
PV 14 Actual S
Subgroup: PV 15
PV 15 Nominal P
PV 15 Actual P
PV 15 Actual Q
Subgroup: PV 16
PV 16 Nominal P
PV 16 Actual Q
PV 16 Actual S
Subgroup: PV 17
PV 17 Nominal P
PV 17 Actual P
PV 17 Actual Q
Subgroup: PV 18
PV 18 Nominal P
PV 18 Actual Q
PV 18 Actual S
Subgroup: PV 19
PV 19 Nominal P
PV 19 Actual P
PV 19 Actual Q
Subgroup: PV 20
PV 20 Nominal P
PV 20 Actual Q
PV 20 Actual S
Subgroup: PV 21
PV 21 Nominal P
PV 21 Actual P
PV 21 Actual Q
Subgroup: PV 22
PV 22 Nominal P
PV 22 Actual Q
PV 22 Actual S
Subgroup: PV 23
PV 23 Nominal P
PV 23 Actual P
PV 23 Actual Q
Subgroup: PV 24
PV 24 Nominal P
PV 24 Actual Q
PV 24 Actual S
Subgroup: PV 25
PV 25 Nominal P
PV 25 Actual P
PV 25 Actual Q
Subgroup: PV 26
PV 26 Nominal P
PV 26 Actual Q
PV 26 Actual S
Subgroup: PV 27
PV 27 Nominal P
PV 27 Actual P
PV 27 Actual Q
Subgroup: PV 28
PV 28 Nominal P
PV 28 Actual Q
PV 28 Actual S
Subgroup: PV 29
PV 29 Nominal P
PV 29 Actual P
PV 29 Actual Q
Subgroup: PV 30
PV 30 Nominal P
PV 30 Actual Q
PV 30 Actual S
Subgroup: PV 31
PV 31 Nominal P
PV 31 Actual P
PV 31 Actual Q
Subgroup: PV 32
PV 32 Nominal P
PV 32 Actual Q
PV 32 Actual S
Group: WT
Subgroup: WT Aggregated
WT Nominal P
WT Actual P
WT Actual Q
Curtailment Output
WT 1 Nominal P
WT 1 Actual P
WT 1 Actual Q
WT 1 Actual S
Subgroup: WT 2
WT 2 Nominal P
WT 2 Actual P
WT 2 Actual S
WT 3 Nominal P
WT 3 Actual P
WT 3 Actual Q
WT 3 Actual S
Subgroup: WT 4
WT 4 Nominal P
WT 4 Actual P
WT 4 Actual S
WT 5 Nominal P
WT 5 Actual P
WT 5 Actual Q
WT 5 Actual S
Subgroup: WT 6
WT 6 Nominal P
WT 6 Actual P
WT 6 Actual S
WT 7 Nominal P
WT 7 Actual P
WT 7 Actual Q
WT 7 Actual S
Subgroup: WT 8
WT 8 Nominal P
WT 8 Actual P
WT 8 Actual S
Group: Renewables
REN Nominal P
REN Actual Q
REN Actual S
Total P
Total Q
Total S
Group: Gensets
Gensets P
Gensets Q
Group: Mains
Load P
Load Q
Load Character
Pmom
Test Frequency
Q(Um) Curve
Qref/Ulim Curve
PF(P) Curve
P(Um) Curve
Grid
Value group Related FW 1.5.0
Codes
Units min
Comm object 16100 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 4 (PAGE 1007) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.
Group: Mains/Bus
Mains/Bus Frequency
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 8195 Related applications MINT, MPTM
Description
Value of Mains/Bus voltage on phase 1.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 8196 Related applications MINT, MPTM
Description
Value of Mains/Bus voltage on phase 2.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 8197 Related applications MINT, MPTM
Description
Value of Mains/Bus voltage on phase 3.
Mains/Bus Voltage
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 10549 Related applications MINT, MPTM
Description
This value contains the maximum difference of values Mains/Bus Voltage L1-N (page 839),
Mains/Bus Voltage L2-N (page 839), Mains/Bus Voltage L3-N (page 840) at a given moment.
Note: Difference of the values and the evaluation of the protection is influenced by the setpoint
Connection type (page 378).
+Mains/Bus Voltage
Mains L1 Current
Mains L2 Current
Mains L2 Current
Mains Import P
Mains P L2
Mains P L3
Mains Import Q
Mains Import Q L1
Mains Import Q L3
Mains S L1
Mains S L2
Mains PF
Value
Mains/Bus Related FW 1.5.0
group
Units [-]
Comm
20580 Related applications MINT, MPTM
object
Description
Power factor of the L1 phase of the Mains/Bus.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16651 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L1-N (page 839).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16652 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L2-N (page 839).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16653 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L3-N (page 840).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16654 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L1-N (page 839).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16655 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L2-N (page 839).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.
Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16656 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L3-N (page 840).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.
ROCOF1
ROCOF2
ROCOF3
ROCOF4
Engine Priority
Actual Reserve
Stop Reserve
Note: Actual power band = group of Controllers which should be running with actual load.
Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.
Note: Actual power band = group of Gen-sets which should be running with actual load.
Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.
Note: Next power band = group of Gen-sets which should be running after load change.
Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.
Note: Next power band = group of Gen-sets which should be running after load change.
Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.
Frequency/Load
Value group Related FW 1.5.0
Control
Units kW
Comm object 8663 Related applications MINT, MPTM
Description
This value shows required active power at the end of ramping.
BESS Required P
Frequency/Load
Value group Related FW 1.5.0
Control
Units kW
Comm object 13105 Related applications MINT, MPTM
Description
This value shows required active power relative to the ramping procedure i.e. required active power right
now.
Frequency/Load
Value group Related FW 1.5.0
Control
Units % of Nominal power (page 375)
Comm object 15900 Related applications MINT, MPTM
Description
Relative value of required power of the BESS.
Frequency/Load
Value group Related FW 1.5.0
Control
Units V
Comm object 9052 Related applications MINT, MPTM
Description
This is the actual voltage on the frequency regulator output of the controller.
In case the Analog Output (page 257) is switched to PWM mode, the relation is:
10 V = ~100 % PWM.
-10 V = 0 % PWM
Frequency/Load
Value group Related FW 1.5.0
Control
Units Hz
Comm object 19446 Related applications MPTM
Description
Requested BESS frequency in Hz.
Frequency/Load
Value group Related FW 1.5.0
Control
Units Hz
Comm object 19447 Related applications MPTM
Description
Relative value of requested power of the BESS.
Frequency/Load
Value group Related FW 1.5.0
Control
Units %
Comm object 19448 Related applications MPTM
Description
Relative request for BESS kW/Hz output in %.
Frequency/Load
Value group Related FW 1.5.0
Control
Units [-]
Comm object 10792 Related applications MPTM
Description
This value contains the actual LoadControl mode that the BESS is currently using. This value may differ
from setpoint Load Control PTM Mode (page 352) which contains requested Load Control mode.
List of possible states:
BESS Required PF
Voltage Request
Battery Voltage
CU-AIN-01
CU-AIN-02
CU-AIN-04
Binary Inputs
Binary Outputs
PV kWh
PV Annual kWh
PV Monthly kWh
PV Weekly kWh
Maximal PV kWh
WT kWh
WT Annual kWh
WT Weekly kWh
WT Daily kWh
Hours Of Silent
Fuel Annual
Fuel Monthly
Fuel Weekly
Fuel Daily
PCC kVArh
PCC kVAh
Mains kWh
Running Hours
Num E-Stops
Shutdowns
Pulse Counter 1
Pulse Counter 2
Application Mode
IMPORTANT: Application Mode can be changed only if Controller Mode (page 885) = OFF.
Controller Mode
Breaker state
Timer Text
Connection Type
Timer Value
FW Version
Application
FW Branch
Value Meaning
Mount In Progress The SD Card is being booted.
Not Inserted There is no SD Card in the SD card slot detected.
The SD card is inserted but the setpoint SD Card File System
Unmount
(page 401) is set to Unmount option.
Ready To Use SD Card is mounted and ready to be used.
Format Required The wrong file system format of the SD Card is detected.
Formatting The formatting process of the SD Card is active.
Formatting Failed The formatting process failed.
Write Protected It is not possible to write data on SD Card (Read Only mode).
Used SD Card is not supported (wrong parameters of the SD
Not Supported
card).
This status is used for any other errors which are not covered by
Error
the states above.
SD Card Capacity
CAN32
CAN48
Reg16
Reg32
Reg64
Gen Loaded 16
Gen Loaded 48
Gen Loaded 64
SPI Module B
User Buttons
1. User Button 1 11. User Button 11 21. User Button 21 31. User Button 31
2. User Button 2 12. User Button 12 22. User Button 22 32. User Button 32
3. User Button 3 13. User Button 13 23. User Button 23
4. User Button 4 14. User Button 14 24. User Button 24
5. User Button 5 15. User Button 15 25. User Button 25
6. User Button 6 16. User Button 16 26. User Button 26
7. User Button 7 17. User Button 17 27. User Button 27
8. User Button 8 18. User Button 18 28. User Button 28
9. User Button 9 19. User Button 19 29. User Button 29
10. User Button 10 20. User Button 20 30. User Button 30
Log Bout 1
Log Bout 2
Log Bout 3
Log Bout 4
Log Bout 5
Log Bout 7
Log Bout 8
Log Bout 9
Log Bout 10
Log Bout 12
Log Bout 13
Log Bout 14
Log Bout 15
Time
Date
Time Mode
Sunrise Time
Time To Sunrise
Time To Sunset
Exercise Timer 1
Exercise Timer 3
Exercise Timer 4
Exercise Timer 5
Exercise Timer 7
Exercise Timer 8
Exercise Timer 9
Exercise Timer 11
Exercise Timer 12
Link Down There is no connected cable to the Ethernet Port (socket) or the cable is broken.
10- HD 10 Mbit Half-Duplex
10- FD 10 Mbit Full-Duplex
100- HD 100 Mbit Half-Duplex
100- FD 100 Mbit Full-Duplex
Note: Note: At one time the Half-Duplex can only send or receive the information whereas Full-
Duplex can do both at once.
Link Down There is no connected cable to the Ethernet Port (socket) or the cable is broken.
10- HD 10 Mbit Half-Duplex
10- FD 10 Mbit Full-Duplex
100- HD 100 Mbit Half-Duplex
100- FD 100 Mbit Full-Duplex
Note: Note: At one time the Half-Duplex can only send or receive the information whereas Full-
Duplex can do both at once.
Link Down There is no connected cable to the Ethernet Port (socket) or the cable is broken.
10- HD 10 Mbit Half-Duplex
10- FD 10 Mbit Full-Duplex
100- HD 100 Mbit Half-Duplex
100- FD 100 Mbit Full-Duplex
Note: Note: At one time the Half-Duplex can only send or receive the information whereas Full-
Duplex can do both at once.
MAC Address
Current IP Address
Current Gateway
MAC Address
Current Gateway
Primary DNS
AirGate ID
Code Description
0 Email was successfully sent.
1 SIMCom declined connection request.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
4 Maximum transmitted data length not defined.
5 No response from SMTP server.
6 Command to SMTP server not sent.
7 Did not receive data from SMTP server.
8 HELO command was refused.
9 EHLO command was refused.
10 SMTP server does not support 8-bit encoding.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
18 SMTP server rejected email data.
19 SMTP server rejected email data.
20 QUIT command was refused.
21 There is no valid server IP address.
22 Process of sending email aborted.
23 Closing connection error.
24 Failed to accept server response after connection is established.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
27 Email address can???t be read.
28 Error during encoding process.
29 Error during HMAC MD5 encoding process.
30 There is no attempt for sending email yet.
MAC Address
Current IP Address
ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24046 Related applications MINT, MPTM
Description
Current IP address of the Ethernet 3 (page 19) interface.
ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24044 Related applications MINT, MPTM
Description
Current subnet mask of the Ethernet 3 (page 19) interface.
ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24042 Related applications MINT, MPTM
Description
Current IP gateway address of the Ethernet 3 (page 19) communications.
Primary DNS
ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24039 Related applications MINT, MPTM
Description
Current domain name server of the Ethernet 3 (page 19) interface.
Secondary DNS
ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24037 Related applications MINT, MPTM
Description
Backup domain name server of the Ethernet 3 (page 19) interface.
ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24048 Related applications MINT, MPTM
Description
Current status of the Ethernet 3 (page 19) communication.
PLC-AOUT 1
PLC-AOUT 2
PLC-AOUT 3
PLC-AOUT 4
PLC-AOUT 5
PLC-AOUT 7
PLC-AOUT 8
PLC-AOUT 9
PLC-AOUT 10
PLC-AOUT 12
PLC-AOUT 13
PLC-AOUT 14
PLC-AOUT 15
PLC-AOUT 17
PLC-AOUT 18
PLC-AOUT 19
PLC-AOUT 20
PLC-AOUT 22
PLC-AOUT 23
PLC-AOUT 24
PLC-AOUT 25
PLC-AOUT 27
PLC-AOUT 28
PLC-AOUT 29
PLC-AOUT 30
PLC-AOUT 32
PLC-AOUT 33
PLC-AOUT 34
PLC-AOUT 35
PLC-AOUT 37
PLC-AOUT 38
PLC-AOUT 39
PLC-AOUT 40
PLC-AOUT 42
PLC-AOUT 43
PLC-AOUT 44
PLC-AOUT 45
PLC-AOUT 47
PLC-AOUT 48
PLC-AOUT 49
PLC-AOUT 50
PLC-AOUT 52
PLC-AOUT 53
PLC-AOUT 54
PLC-AOUT 55
PLC-AOUT 57
PLC-AOUT 58
PLC-AOUT 59
PLC-AOUT 60
PLC-AOUT 62
PLC-AOUT 63
PLC-AOUT 64
PLC-BOUT 1
PLC-BOUT 3
PLC-BOUT 4
PLC-BOUT 5
PLC-BOUT 6
PLC-BOUT 8
PLC-BOUT 9
PLC-BOUT 10
PLC-BOUT 11
PLC-BOUT 13
PLC-BOUT 14
PLC-BOUT 15
PLC-BOUT 16
PLC-BOUT 18
PLC-BOUT 19
PLC-BOUT 20
PLC-BOUT 21
PLC-BOUT 23
PLC-BOUT 24
PLC-BOUT 25
PLC-BOUT 26
PLC-BOUT 28
PLC-BOUT 29
PLC-BOUT 30
PLC-BOUT 31
PLC Resource 1
PLC Resource 2
PLC Resource 3
PLC Resource 4
PLC Resource 6
PLC Resource 7
PLC Resource 8
PLC Resource 9
PLC Resource 11
PLC Resource 12
PLC Resource 13
PLC Resource 14
PLC Resource 16
RemoteControl2B 1
RemoteControl2B 2
RemoteControl2B 4
RemoteControl2B 5
RemoteControl2B 6
RemoteControl2B 8
RemoteControl4B 1
RemoteControl4B 2
RemoteControl4B 4
RemoteControlBin
Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 9
2. DISTBIN-1 10
3. DISTBIN-1 11
4. DISTBIN-1 12
5. DISTBIN-1 13
6. DISTBIN-1 14
7. DISTBIN-1 15
8. DISTBIN-1 16
Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 17
2. DISTBIN-1 18
3. DISTBIN-1 19
4. DISTBIN-1 20
5. DISTBIN-1 21
6. DISTBIN-1 22
7. DISTBIN-1 23
8. DISTBIN-1 24
Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 25
2. DISTBIN-1 26
3. DISTBIN-1 27
4. DISTBIN-1 28
5. DISTBIN-1 29
6. DISTBIN-1 30
7. DISTBIN-1 31
8. DISTBIN-1 32
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
DISTAIN-1 2
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
DISTAIN-1 3
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 9
2. DISTBIN-2 10
3. DISTBIN-2 11
4. DISTBIN-2 12
5. DISTBIN-2 13
6. DISTBIN-2 14
7. DISTBIN-2 15
8. DISTBIN-2 16
Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 17
2. DISTBIN-2 18
3. DISTBIN-2 19
4. DISTBIN-2 20
5. DISTBIN-2 21
6. DISTBIN-2 22
7. DISTBIN-2 23
8. DISTBIN-2 24
Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 25
2. DISTBIN-2 26
3. DISTBIN-2 27
4. DISTBIN-2 28
5. DISTBIN-2 29
6. DISTBIN-2 30
7. DISTBIN-2 31
8. DISTBIN-2 32
DISTAIN-2 1
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
DISTAIN-2 3
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
DISTAIN-2 4
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!
Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 9
2. DISTBIN-33 10
3. DISTBIN-33 11
4. DISTBIN-33 12
5. DISTBIN-33 13
6. DISTBIN-33 14
7. DISTBIN-33 15
8. DISTBIN-33 16
Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 17
2. DISTBIN-33 18
3. DISTBIN-33 19
4. DISTBIN-33 20
5. DISTBIN-33 21
6. DISTBIN-33 22
7. DISTBIN-33 23
8. DISTBIN-33 24
Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 25
2. DISTBIN-33 26
3. DISTBIN-33 27
4. DISTBIN-33 28
5. DISTBIN-33 29
6. DISTBIN-33 30
7. DISTBIN-33 31
8. DISTBIN-33 32
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
DISTAIN-33 2
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
DISTAIN-33 3
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 9
2. DISTBIN-34 10
3. DISTBIN-34 11
4. DISTBIN-34 12
5. DISTBIN-34 13
6. DISTBIN-34 14
7. DISTBIN-34 15
8. DISTBIN-34 16
Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 17
2. DISTBIN-34 18
3. DISTBIN-34 19
4. DISTBIN-34 20
5. DISTBIN-34 21
6. DISTBIN-34 22
7. DISTBIN-34 23
8. DISTBIN-34 24
Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 25
2. DISTBIN-34 26
3. DISTBIN-34 27
4. DISTBIN-34 28
5. DISTBIN-34 29
6. DISTBIN-34 30
7. DISTBIN-34 31
8. DISTBIN-34 32
DISTAIN-34 1
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
DISTAIN-34 3
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
DISTAIN-34 4
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!
SHBIN-1
SHBIN-2
SHBIN-4
SHBIN-6
SHBOUT-2
SHBOUT-4
SHBOUT-6
SHAIN-1 2
SHAIN-1 3
SHAIN-1 4
SHAIN-2 2
SHAIN-2 3
SHAIN-2 4
1. DISTBOUT 9
2. DISTBOUT 10
3. DISTBOUT 11
4. DISTBOUT 12
5. DISTBOUT 13
6. DISTBOUT 14
7. DISTBOUT 15
8. DISTBOUT 16
1. DISTBOUT 17
2. DISTBOUT 18
3. DISTBOUT 19
4. DISTBOUT 20
5. DISTBOUT 21
6. DISTBOUT 22
7. DISTBOUT 23
8. DISTBOUT 24
1. DISTBOUT 25
2. DISTBOUT 26
3. DISTBOUT 27
4. DISTBOUT 28
5. DISTBOUT 29
6. DISTBOUT 30
7. DISTBOUT 31
8. DISTBOUT 32
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Note: The samax value is counted from Nominal Current (page 376) and BESS Nominal Voltage Ph-
N (page 380) (or BESS Nominal Voltage Ph-Ph (page 380)) in case that Samax (page 374) = OFF.
Default values
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
Default appearance
For full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically (page 986).
Application MINT
Note: This binary input has lower priority than LBI APPLICATION MPTM (PAGE 989).
Application MPTM
Note: This binary input has higher priority than LBI APPLICATION MINT (PAGE 989).
LBI: B
Binary input has the same function as BCB button on an External display (page 79)Internal display.
BCB Disable
This input is used for connection of the normally open feedback contact from the generator circuit
breaker or contactor. If the input is active, the controller will consider the BCB as closed and vice versa.
If the feedback does not respond to a change of the control output LBO BCB CLOSE/OPEN (PAGE
1055) within time adjusted in Setpoint Waiting For Breaker Feedback (page 1), and it was
already last attempt the specific alarm based on current breaker position is issued.
If the feedback changes it's position unexpectedly without any command given by the control
output, the Alarm Stp BCB Fail (page 1290) will be issued immediately.
Note: There is no BCB control limitation when BCB Control Mode (page 369) = External.
LBI: C
Emergency MAN
Emergency Stop
LBI: F
Binary input has the same function as Fault Reset button on an External display (page 79)Internal
display.
Force Parallel
Group link
Geo-Fencing Enable
LBI: H
Binary input has the same function as Horn reset button on an External display (page 79)Internal
display.
IMPORTANT: This input has to be configured on both Master and Backup controllers.
IMPORTANT: This input has to be configured on both Master and Backup controllers.
LBI: I
LBI: L
Load Reduction 1
Load Reduction 2
Load Reduction 4
Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus.
Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus.
Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus.
LBI: M
MCB Button
This binary input has the same function as MCB button on an External display (page 79)Internal
display.
MCB Disable
Note: If more then one binary input for Min Run Power is activated, the one with the higher index has
higher priority and it is used.
IMPORTANT: All controllers cooperating together in Power management must have the same
minimal running power selected.
Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus. See the diagram of such
distribution in the description of the input LOAD RES 2 ACTIVE (PAGE 1008).
Note: If more then one binary input for Min Run Power is activated, the one with the higher index has
higher priority and it is used.
IMPORTANT: All controllers cooperating together in Power management must have the same
minimal running power selected.
Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus. See the diagram of such
distribution in the description of the input LOAD RES 2 ACTIVE (PAGE 1008).
Note: If more then one binary input for Min Run Power is activated, the one with the higher index has
higher priority and it is used.
IMPORTANT: All controllers cooperating together in Power management must have the same
minimal running power selected.
Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus. See the diagram of such
distribution in the description of the input LOAD RES 2 ACTIVE (PAGE 1008).
LBI: N
NCB Feedback
LBI: P
Post VRT
Pulse Counter 2
PV 01 Operable
PV 02 Operable
PV 03 Operable
PV 05 Operable
PV 06 Operable
PV 07 Operable
PV 08 Operable
PV 10 Operable
PV 11 Operable
PV 12 Operable
PV 13 Operable
PV 15 Operable
PV 16 Operable
PV 17 Operable
PV 18 Operable
PV 20 Operable
PV 21 Operable
PV 22 Operable
PV 23 Operable
PV 25 Operable
PV 26 Operable
PV 27 Operable
PV 28 Operable
PV 30 Operable
PV 31 Operable
PV 32 Operable
PVCB Button
PVCB Feedback
LBI: R
Remote AUTO
Remote OFF
LBI: S
Sd Override
Note: User protections (page 205) with protection type Shutdown Override (page 199) are also NOT
suppressed.
Start Blocking
Start Button
Binary input has the same function as Start Button on an External display (page 79)Internal display.
Binary input has the same function as Stop Button on an External display (page 79)Internal display.
Synchronization Disabled
LBI: T
TEST ROCOF
LBI: U
LBI: W
WT 01 Operable
WT 02 Operable
WT 03 Operable
WT 04 Operable
WT 06 Operable
WT 07 Operable
WT 08 Operable
For full list of Logical binary outputs go to the chapter Logical binary outputs alphabetically (page 1049).
LBO: A 1052 BESS Parallel Oper 1065 ECU 11 Comm Fail 1071
Access Locked 1052 BESS Ready To Load 1065 ECU 12 Comm Fail 1071
AL Maintenance 1 1052 LBO: C 1065 ECU 13 Comm Fail 1071
AL Maintenance 2 1052 Common Alarm Active ECU 14 Comm Fail 1071
AL Maintenance 3 1052 Level 1 1065 ECU 15 Comm Fail 1071
AL Maintenance 4 1052 Common Alarm Active ECU 16 Comm Fail 1072
Level 2 1065
Alarm 1053 ECU 17 Comm Fail 1072
Common Alarm Level 1 1066
Alarm BESS Frequency 1053 ECU 18 Comm Fail 1072
Common Alarm Level 2 1066
Alarm BESS Overcurrent 1053 ECU 19 Comm Fail 1072
Common Alarm Only 1066
Alarm BESS Voltage 1053 ECU 20 Comm Fail 1072
Common History Record 1066
Alarm Flashing 1053 ECU 21 Comm Fail 1072
Common Mains
Alarm BESS 1054 ECU 22 Comm Fail 1073
Protection 1066
Alarm BESS Frequency 1054 ECU 23 Comm Fail 1073
Common PVCB Open 1067
Alarm BESS Voltage 1054 ECU 24 Comm Fail 1073
Common Shutdown 1067
All Available Gen-sets ECU 25 Comm Fail 1073
Common Shutdown
Run 1054 ECU 26 Comm Fail 1073
Override 1067
Any GCB Closed 1055 ECU 27 Comm Fail 1073
Common Slow Stop 1067
Any Other GCB Closed 1055 ECU 28 Comm Fail 1074
Common Warning 1068
LBO: B 1055 ECU Comm OK 1074
Curtailment Enable 1068
BCB Button Echo 1055
ECU Power Relay 1074
LBO: D 1068
BCB Close/Open 1055
Daily Batt Cycles ECU Run Stop 1074
BCB Close/Open
Reached 1068 Energized 1075
Secondary 1056
DC Circuit Closed 1068 Engines Swapped 1075
BCB OFF Coil 1057
Deadbus 1068 Event Load Reduction 1075
BCB OFF Coil Secondary 1058
Day/Night 1069 Event Mains Frequency
BCB ON Coil 1059
LBO: E 1069 Fall 1075
BCB ON Coil Secondary 1060
ECU Comm Fail 1069 Event Mains Frequency
BCB Status 1060 Rise 1075
ECU 1 Comm Fail 1069
BCB Primary Status 1061 Event Mains Trip 1076
ECU 2 Comm Fail 1069
BCB Secondary Status 1061 Event P for Q 1076
ECU 3 Comm Fail 1069
BCB UV Coil 1061 Event P(Um) 1076
ECU 4 Comm Fail 1070
BCB UV Coil Secondary 1063 Event Post VRT 1076
ECU 5 Comm Fail 1070
BESS Active 1063 Event Return Over/Under
ECU 6 Comm Fail 1070
BESS Capability C Limit 1064 Frequency 1076
ECU 7 Comm Fail 1070
BESS Capability L Limit 1064 Event Soft Unload 1077
ECU 8 Comm Fail 1070
BESS Healthy 1064 Exercise Timer 1 1077
ECU 9 Comm Fail 1070
BESS In Loadsharing 1064 Exercise Timer 2 1077
ECU 10 Comm Fail 1071
Access Locked
AL Maintenance 1
AL Maintenance 2
AL Maintenance 3
AL Maintenance 4
Alarm Flashing
LBO: B
BCB Close/Open
BCB Status
BCB UV Coil
BESS Active
BESS Healthy
BESS In Loadsharing
LBO: C
Common Shutdown
Curtailment Enable
LBO: D
DC Circuit Closed
Deadbus
LBO: E
ECU Comm OK
Note: This output can be also activated by LBI ECU KEY SWITCH (PAGE 996). In that case alarms related
to ECU Communication Fail alarms are not evaluated.
Engines Swapped
Event P for Q
Event P(Um)
Exercise Timer 1
Exercise Timer 2
Exercise Timer 3
Exercise Timer 5
Exercise Timer 6
Exercise Timer 7
Exercise Timer 9
Exercise Timer 10
Exercise Timer 12
LBO: F
Forward Synchronization
Frequency Up
LBO: G
Heartbeat
Horn
Horn Flashing
IMPORTANT: This output has to be configured on both Master and Backup controllers.
IMPORTANT: This output has to be configured on both Master and Backup controllers.
In Synchronism
Initialized
LBO: K
kWh Pulse
Logical 0
Logical 1
LVRT Active
LVRT Severe
LVRTCurveTrip
Note: BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS Voltage L3-N
(page 713) are considered.
Mains/Bus Healthy
Manual Ready
MCB Close/Open
MCB Status
Mode AUTO
Mode MAN
LBO: N
NCB Close/Open
Not In Auto
Not Ready
Not Used
Operational
OVRT Active
OVRT Invalid
OVRTCurveTrip
P for Q Active
Pave FLS
Note: Setpoints Power Switch On (page 446) and Power Switch Off (page 446) are invisible until
configuration of this LBO.
Prestart
Precharge
Precharge Request
PV Operable
PVCB Close/Open
PVCB Status
Ready
Reverse Synchronization
ROCOF 1 Active
ROCOF 2 Active
ROCOF 3 Active
LBO: S
Sd Override
Soft Load
Start Blocked
Starting
MPTM
Related FW 1.5.0 Related applications
LBO ID 1057
Description
This output is closed when synchronization to the mains is allowed or Breaker state (page 886) =
ParalOper.
See Synchronization & Connection Conditions (page 307) for more information.
System Ready
System Reserve OK
LBO: V
Voltage Down
LBO: W
WT Operable
For full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically (page 1112).
BESSCapacity
BESS P Request
BESS Q Request
BESS SOC
BESS Temperature
Cold Temp 1
Cold Temp 2
Cold Temp 3
Cold Temp 5
Cold Temp 6
Cold Temp 8
Cold Temp 9
LAI: D
LAI: I
Irradiation of PV Array 1
Irradiation of PV Array 3
Irradiation of PV Array 4
LAI: L
Load Reduction
Irradiation of PV Array 1
Irradiation of PV Array 2
Irradiation of PV Array 4
LAI: M
Mains Measurement Q
LAI: P
Note: Always use a three decimal number for this LAI. Thus the range for this LAI is 0.600 to 1.200.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, alarm Wrn PF Control Fail (page 1258) is activated.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, alarm Wrn PF Control Fail (page 1258) is activated.
Pmom
PV 01 Actual P
PV 01 Actual Q
PV 01 Nominal P
PV 02 Actual P
PV 02 Actual Q
PV 02 kWh
PV 02 Nominal P
PV 03 Actual Q
PV 03 kWh
PV 03 Nominal P
PV 04 Actual P
PV 04 Actual Q
PV 04 Nominal P
PV 05 Actual P
PV 05 Actual Q
PV 05 kWh
PV 05 Nominal P
PV 06 Actual Q
PV 06 kWh
PV 06 Nominal P
PV 07 Actual P
PV 07 Actual Q
PV 07 Nominal P
PV 08 Actual P
PV 08 Actual Q
PV 08 kWh
PV 08 Nominal P
PV 09 Actual Q
PV 09 kWh
PV 09 Nominal P
PV 10 Actual P
PV 10 Actual Q
PV 10 Nominal P
PV 11 Actual P
PV 11 Actual Q
PV 11 kWh
PV 11 Nominal P
PV 12 Actual Q
PV 12 kWh
PV 12 Nominal P
PV 13 Actual P
PV 13 Actual Q
PV 13 Nominal P
PV 14 Actual P
PV 14 Actual Q
PV 14 kWh
PV 14 Nominal P
PV 15 Actual Q
PV 15 kWh
PV 15 Nominal P
PV 16 Actual P
PV 16 Actual Q
PV 16 Nominal P
PV 17 Actual P
PV 17 Actual Q
PV 17 kWh
PV 17 Nominal P
PV 18 Actual Q
PV 18 kWh
PV 18 Nominal P
PV 19 Actual P
PV 19 Actual Q
PV 19 Nominal P
PV 20 Actual P
PV 20 Actual Q
PV 20 kWh
PV 20 Nominal P
PV 21 Actual Q
PV 21 kWh
PV 21 Nominal P
PV 22 Actual P
PV 22 Actual Q
PV 22 Nominal P
PV 23 Actual P
PV 23 Actual Q
PV 23 kWh
PV 23 Nominal P
PV 24 Actual Q
PV 24 kWh
PV 24 Nominal P
PV 25 Actual P
PV 25 Actual Q
PV 25 Nominal P
PV 26 Actual P
PV 26 Actual Q
PV 26 kWh
PV 26 Nominal P
PV 27 Actual Q
PV 27 kWh
PV 27 Nominal P
PV 28 Actual P
PV 28 Actual Q
PV 28 Nominal P
PV 29 Actual P
PV 29 Actual Q
PV 29 kWh
PV 29 Nominal P
PV 30 Actual Q
PV 30 kWh
PV 30 Nominal P
PV 31 Actual P
PV 31 Actual Q
PV 31 Nominal P
PV 32 Actual P
PV 32 Actual Q
PV 32 kWh
PV 32 Nominal P
MINT,
Related FW 1.5.0 Related applications
MPTM
LAI ID 326
Description
This LAI is used to shift Q(UM) (PAGE 967) curve left or right if PF/Q Control PTM Mode (page 356) = Q
(Um), PF/Q Request Source (page 357) = Analog External Value and PF/Q Regulation Type (page
358) = Base PF/Q Control.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range alarm Wrn Q(Um) Fail (page 1263) is activated.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range alarm Wrn Q(Um) Fail (page 1263) is activated.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range, alarm Wrn Qref/Ulim Fail (page 1263) is activated.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range, alarm Wrn Qref/Ulim Fail (page 1263) is activated.
LAI: T
TestF
TestQ
TestU
WT 01 Actual P
WT 01 Actual Q
WT 01 kWh
WT 01 Nominal P
WT 02 Actual P
WT 02 kWh
WT 02 Nominal P
WT 03 Actual P
WT 03 Actual Q
WT 03 kWh
WT 04 Actual P
WT 04 Actual Q
WT 04 kWh
WT 04 Nominal P
WT 05 Nominal P
WT 05 Actual P
WT 05 kWh
WT 06 Actual P
WT 06 Actual Q
WT 06 kWh
WT 07 Actual P
WT 07 Actual Q
WT 07 kWh
WT 07 Nominal P
WT 08 Actual P
WT 08 kWh
WT 08 Nominal P
OR/AND
Related FW 1.5.0
PLC Block ID 1
Inputs
There have to be at least 2 inputs every time. There may be up to 8 inputs configured.
Related FW 1.5.0
PLC Block ID 39
Inputs
The result of XOR operation between two binary inputs (Input 1 and Input 2) is defined by table below.
Function type RS
R-latch S-latch E-latch JK-latch
Input 2 (R) Input 1 (S)
Q
-1 -1 -1 -1
0 0 Q Q Q Q
0 1 1 1 1 1
1 0 0 0 0 0
-1 -1
1 1 0 1 Q NOT(Q )
-1
The Q denotes the state of the RS block output in the last evaluation cycle.
The block Output value is given by the selected RS flip-flop variant evaluation:
R-latch: When both inputs (R, S) are set the Reset input is dominant.
S-latch: When both inputs (R, S) are set the Set input is dominant.
E-latch: When both inputs (R, S) are set the previous output is preserved.
JK-latch: When both inputs (R, S) are set the block output is negated.
The block has the setting for the variant functions of the RS flip-flop circuit. This setting is
Group: Comparators
Comp Delay
Relation Name
">" (default) greater than
">=" greater than equal
"==" equal
"<=" less than equal
"<" less than
Comp Hyst
Comp Win
Delay
Related FW 1.5.0
PLC Block ID 33
Inputs
Note: If Input time up or Input time down value is <0, this input is internally set to zero.
Note: Use Pulse on edge option to choose between delay and pulse mode.
Timer
Related FW 1.5.0
PLC Block ID 38
Inputs
Timer mode TP
IMPORTANT: For ComAp Timer mode: if no inputs are connected and the First down option
is not checked, the Output is active.
Interpolation
PLC group
Related FW 1.5.0
PLC Block ID 34
Inputs
AxB/C±D
PLC group
Related FW 1.5.0
PLC Block ID 51
Inputs
Output O Binary
32 32
-2 -1 .. +2 -1 Result of the
operation
Set when Output is out of
Data
Err Binary 0/1 range or when dividing by zero
invalid
occurrs
Description
The block realizes the mathematical operation AxB/C±D. The operation ± is selected by Function
typeselector. In case of any invalid data on any of the inputs, the Output is set to invalid value and Data
Invalid is closed. The Output has resolution and dimension based on setting of the block.
Math Fc.
PLC group
Related FW 1.5.0
PLC Block ID 17
Inputs
Function Output
ADD - Addition Input 1 + Input 2 + … + Input N
SUB - Substraction Input 1 - Input 2 - … - Input N
|SUB| - Absolute value of substraction ABS(Input 1 - Input 2 - … - Input N)
AVG - Average Input 1 + Input 2 + … + Input N) / N
MIN - Minimal value MIN(Input 1, Input 2, … ,Input N)
MAX - Maximal value MAX(Input 1, Input 2, … ,Input N)
Note: In case of AVG operation type the N is number of inputs with valid value.
Group: Regulators
PID
PLC group
Related FW 1.5.0
PLC Block ID 41
Inputs
Note: There is a difference between Init Value (inactive PID block) and Manual Value - Manual Value
is available only while the PID Enable is true, MAN mode is enabled and is limited by the High Limit
and low Limit.
PLC group
Related FW 1.5.0
PLC Block ID 42
Inc/Dec
PLC group
Related FW 1.5.0
PLC Block ID 22
Inputs
32 32
Maximum Analog No -2 .. 2 Maximum value of Output
32 32
Default Analog No -2 .. 2 Initial value of Output
Outputs
IMPORTANT: When the controller is powered off the Output value is not preserved.
LowPassFlt
PLC group
Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 40
Inputs
Mov Avg
PLC group
Related FW 1.5.0
PLC Block ID 7
Inputs
Ramp
PLC group
Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 19
Inputs
Up/Down
PLC group
Related FW 1.5.0
PLC Block ID 20
Inputs
Analog Switch 8
Related FW 1.5.0
Inputs
32 32 Input value 3
Input 3 Analog No -2 .. 2
(optional)
32 32
Input 4 Analog No -2 .. 2 Input value 4
32 32 Input value 5
Input 5 Analog No -2 .. 2
(optional)
32 32 Input value 6
Input 6 Analog No -2 .. 2
(optional)
32 32 Input value 7
Input 7 Analog No -2 .. 2
(optional)
32 32 Input value 8
Input 8 Analog No -2 .. 2
(optional)
Input SW 1 Binary No 0/1 Switch input 1
Input SW 2 Binary No 0/1 Switch input 2
Input SW 3 Binary No 0/1 Switch input 3
Outputs
Bit Sum 16
Related FW 1.5.0
PLC Block ID 53
Inputs
Circuit Breaker
Related FW 1.5.0
PLC Block ID 58
Inputs
32 32 Converted Input
Output Analog No -2 .. 2
value
The attribute of
Output Binary Yes 0/1 invalid data on
output
Description
The block converts the Input based on selected resolution and dimension, and reflects it to the Output.
Dimension is converted based on user configuration without any extra recalculation. Resolution is
converted and recalculation is used.
Example: If the input is 100,5 W and the convert block is used to convert dimensions to kW with
resolution 1, the output shows 101 kW.
Note: Conversion is done to Integer32, if the input value is out of Integer32 range, output value is set to
invalid status and error output is activated.
Related FW 1.5.0
PLC Block ID 49
Inputs
Related FW 1.5.0
PLC Block ID 50
Inputs
Decomp. 4
Related FW 1.5.0
PLC Block ID 24
Inputs
Decomp. 16
Related FW 1.5.0
PLC Block ID 48
Inputs
Related FW 1.5.0
PLC Block ID 43
Inputs
Mode Description
The block behaves like analog memory. Input Hold behaves like the reload trigger and
Edge
reacts on rising edge. The initial value of the Output after restart of the controller is 0.
The block is like a mirror of the Input while the Hold is inactive. The value of Output is
Level
latched at the last value while Hold is active.
PF Conv
Related FW 1.5.0
PLC Block ID 57
Inputs
The Output has a Resolution and Dimension according to the block settings.
Poly Appx
Related FW 1.5.0
PLC Block ID 47
Inputs
PWR Calc
Related FW 1.5.0
PLC Block ID 56
Inputs
The Output has a Resolution and Dimension according to the block settings.
Note: The block performs the Resolution conversion.
Oper P Q S PF D
In
P,Q
P Q not valid
Out
S,PF
In
P,S
P S not valid
Out
Q, PF
In
P,PF
P PF not valid
Out
Q,S
Function Validate
Input Validate Input Force Output O Output Err
Valid value 0 Validate 0
Invalid value 0 Replace 1
Valid value 1 Replace 0
Invalid value 1 Replace 1
Wrn Load IMP/EXP Fail 1253 Wrn SW Key CAN ALI Mains Ph L2 Inverted 1275
Redundancy Error 1267 ALI Mains Ph L3 Inverted 1275
Wrn Long Term History
Fail 1254 Wrn SW Key Hot Swap ALI Mains Ph Rotation
Error 1267 Opposite 1275
Wrn Master Controller
Failed 1254 Wrn Test UPQF 1268 ALI Start Blocking 1276
Wrn MCB Fail 1254 Wrn Unsupported PMS ALI Wrong Power Format 1276
Mode 1268
Wrn MCB Fail To Close 1255 Alarm List + History
Wrn Universal Genset Indication 1276
Wrn MCB Fail To Open 1256
Overflow 1268 AHI SyncNotAllowed 1276
Wrn Override All Sd 1256
Wrn Voltage Regulation
History Record Only 1277
Wrn Password reset e- Limit 1268
mail addr is not set 1257 Hst Pave 1277
Wrong PLC Configuration1269
Wrn P for Q Fail 1257 Hst ROCOF 1 1277
Description
Description
Description
Alarm Only
AHI SyncNotAllowed
Hst Pave
Hst ROCOF 1
Hst ROCOF2
Hst ROCOF3
Hst ROCOF4
Emergency Stop
E-STOP
Sd BESS <f
Sd IDMT Overload
Description
Description
Description
Related
MINT, MPTM
applications
Alarm ID 451
This alarm is activated when there is a problem with position of the circuit breaker.
LBI BCB SECONDARY FEEDBACK (PAGE 994) does not match expected position
Description given by LBO BCB CLOSE/OPEN SECONDARY (PAGE 1056).
There is a mismatch between LBI BCB SECONDARY FEEDBACK (PAGE 994) and
BCB SECONDARY FEEDBACK NEGATIVE (PAGE 993).
Related
MINT, MPTM
applications
Alarm ID 1557
This alarm is activated when there is a problem with circuit breaker position while
closing.
Description LBO BCB CLOSE/OPEN SECONDARY (PAGE 1056) closed but LBI BCB
SECONDARY FEEDBACK (PAGE 994) did not closed in Waiting For Breaker
Feedback (page 1) seconds.
Related
MINT, MPTM
applications
Alarm ID 1556
This alarm is activated when there is a problem with circuit breaker position while
opening.
LBO BCB CLOSE/OPEN SECONDARY (PAGE 1056) opened but LBI BCB
SECONDARY FEEDBACK (PAGE 994) did not opened in 2 seconds.
Description
PV Breaker Open
6 back to Alarms
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-L3
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
Description (page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-N
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
(page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
Description (page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
Description (page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-L3
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-N
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >f Protection (page 586) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains >f Protection (page
MPTM
586)
Protection is always active. Alarm is activated
when Mains/Bus Frequency (page 839) rises
MINT
over BESS >f (page 455) for period longer than
BESS >f Delay (page 455).
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).
Mains/Bus >>f
Alarm Type
Alarmlist message Mains/Bus >>f
Alarm evaluated Only if Mains >>f Protection (page 587) != Disabled
Related applications MPTM
Alarm ID 1092
This alarm is activated by Mains >>f Protection (page 587).
This alarm is activated when Mains/Bus Frequency (page 839), rises over
Description
preset value.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <f Protection (page 588) !=
MPTM
Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains <f Protection (page
MPTM
588)
Protection is always active. Alarm is activated
when Mains/Bus Frequency (page 839) drops
MINT
below BESS <f (page 456) for period longer than
BESS <f Delay (page 456).
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).
Mains/Bus <<f
Alarm Type
Alarmlist message Mains/Bus <<f
Alarm evaluated Only if Mains <<f Protection (page 589) != Disabled
Related applications MINT, MPTM
Alarm ID 1093
This alarm is activated by Mains <<f Protection (page 589).
This alarm is activated when Mains/Bus Frequency (page 839), drops below
Description
preset value.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains V Unbalance Protection (page
MPTM
583) != Disabled
MINT All the time
Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains V Unbalance
MPTM
Protection (page 583)
Protection is always active. Alarm is activated
when relative difference between bus voltages
MINT rises over BESS V Unbalance (page 454) for
period longer than BESS V Unbalance Delay
(page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)
Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains V Unbalance
MPTM
Protection (page 583)
Protection is always active. Alarm is activated
when relative difference between bus voltages
MINT rises over BESS V Unbalance (page 454) for
period longer than BESS V Unbalance Delay
(page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).
Maintenance 1 Interval
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 1 Interval (page 657) != Disabled
Related applications MINT, MPTM
Alarm ID 1072
This alarm is activated when setpoint Maintenance Timer 1 Interval (page
657) elapses i.e. the value Maintenance Timer 1 Interval (page 881) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
Maintenance 1 RunHours
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Protection
Alarm evaluated Only if Maintenance Timer 1 RunHours (page 656) != Disabled
Related applications MINT, MPTM
Alarm ID 585
Maintenance 2 Interval
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 2 Interval (page 658) != Disabled
Related applications MINT, MPTM
Alarm ID 1073
This alarm is activated when setpoint Maintenance Timer 2 Interval (page
658) elapses i.e. the value Maintenance Timer 2 Interval (page 882) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
Maintenance 2 RunHours
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 2 Protection
Alarm evaluated Only if Maintenance Timer 2 RunHours (page 658) != Disabled
Related applications MINT, MPTM
Alarm ID 586
This warning is activated when setpoint Maintenance Timer 2 RunHours
(page 658) elapses i.e. the value Maintenance Timer 2 RunHours (page
Description
881) = 0 and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
Maintenance 3 Interval
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 3 Interval (page 660) != Disabled
Related applications MINT, MPTM
Alarm ID 1074
This alarm is activated when setpoint Maintenance Timer 3 Interval (page
660) elapses i.e. the value Maintenance Timer 3 Interval (page 882) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 3 Protection
Alarm evaluated Only if Maintenance Timer 3 RunHours (page 659) != Disabled
Related applications MINT, MPTM
Alarm ID 587
This warning is activated when setpoint Maintenance Timer 3 RunHours
(page 659) elapses i.e. the value Maintenance Timer 3 RunHours (page
Description
882) = 0 and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
Maintenance 4 Interval
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 4 Interval (page 661) != Disabled
Related applications MINT, MPTM
Alarm ID 1519
This alarm is activated when setpoint Maintenance Timer 4 Interval (page
661) elapses i.e. the value Maintenance Timer 4 Interval (page 883) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
Maintenance 4 RunHours
Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 4 Protection
Alarm evaluated Only if Maintenance Timer 4 RunHours (page 661) or != Disabled
Related applications MINT, MPTM
Alarm ID 1518
This warning is activated when setpoint Maintenance Timer 4 RunHours
(page 661) elapses i.e. the value Maintenance Timer 4 RunHours (page
Description
882) = 0 and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).
DISTIN 02
DISTIN 03
DISTIN 04
DISTIN 06
DISTIN 07
DISTIN 08
DISTIN 10
DISTIN 11
DISTIN 12
DISTIN 14
DISTIN 15
DISTIN 16
DISTIN 18
DISTIN 19
DISTIN 20
DISTIN 22
DISTIN 23
DISTIN 24
DISTIN 26
DISTIN 27
DISTIN 28
DISTIN 30
DISTIN 31
DISTIN 32
DISTIN 34
DISTIN 35
DISTIN 36
DISTIN 38
DISTIN 39
DISTIN 40
DISTIN 42
DISTIN 43
DISTIN 44
DISTIN 46
DISTIN 47
DISTIN 48
DISTIN 50
DISTIN 51
DISTIN 52
DISTIN 54
DISTIN 55
DISTIN 56
DISTIN 58
DISTIN 59
DISTIN 60
DISTIN 62
DISTIN 63
DISTIN 64
SHAIN 1
SHAIN 2
SHBIN 1
SHBIN 2
SHBIN 3
SHBIN 4
SHBIN 5
SHBIN 6
CM-Ethernet
CM-4G-GPS
CM-RS232-485
EM-BIO8-EFCP
Communication modules
CM2-4G-GPS 1350
CM2-4G-GPS
CM2-4G-GPS plug-in module containing a GPS receiver and GSM/WCDMA/LTE modem which can work in
two modes of operation.
Note: Cellular data service must be enabled in your SIM card by your mobile operator for successful
operation.
4G module types
If the anthenna is CELLULAR only and has 1 cable (OT1A4GXXMCX), it is connected to the 4G-MAIN
connector.
If the anthenna is CELLULAR only and has 2 cables, cables are connected to the 4G-MAIN or 4G-DIV
connectors (does not matter which cable to which connector).
If the anthenna is a combination of CELLULAR/GPS and has 2 cables (OT1A4GGPSCX), then cable
"4G/LTE" needs to be connected to the 4G-MAIN connector and "GPS" cable to the GPS connector.
If the anthenna is a combination of CELLULAR/GPS and has 3 cables (OT2A4GGPSCX), then cables
"4G/LTE" need to be connected to the 4G-MAIN and 4G-DIV connectors (does not matter which cable to
which connector) and "GPS" cable to the GPS connector.
Note: Type of the cable is labeled on its side.
Technical data
General
Width × Height × Depth 73.8 × 50.3 × 15
Weight ~35 g
Power supply 8-36 V DC
Power consumption 1.7 W
Peak power consumption 10 W
Operating temperature -30 ˚C to +70 ˚C
Storage temperature -40 ˚C to +80 ˚C
Cellular
2G (GSM/GPRS/EDGE) Quad band,
850/900/1800/1900 MHz
3G (UMTS/HSPA+) Seven band, 800
(BdXIX) / 850 (BdV) / 900 (BdVIII) / AWS
(BdIV) / 1800 (BdIX) / 1900 (BdII) /
Supported networks and frequency bands
2100MHz (BdI)
4G (LTE) Twelve band, 700 (Bd12 <MFBI
Bd17>, Bd28) 800 (Bd18, Bd19, Bd20) 850
(Bd5) / 900 (Bd8) / AWS (Bd4) / 1800 (Bd3)
/ 1900 (Bd2) / 2100 (Bd1) / 2600MHz (Bd7)
Antenna interface 2x SMA female (Main and Diversity)
Contact your mobile operator for getting packet data APN (APN = Access Point Name), username and
password.
Example: APN Name = "internet", UserName = [blank], Password = [blank].
Make sure SIM card does not require PIN code. Use any mobile phone to switch the SIM PIN security off.
Place the SIM card into slot on CM2-4G-GPS card
Connect the antenna to Cellular module antenna connector.
If you want to use the built-in GPS receiver, also connect an active GPS antenna to the GPS antenna
connector.
Switch off the controller.
Insert CM2-4G-GPS module into controller
Power up the controller.
Select the mode of CM2-4G-GPS module by adjusting setpoint Internet Connection (page 672).
Activate CM2-4G-GPS module by switching the setpoint Internet Connection (page 672) to enabled.
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Install package to computer or open PSI to install it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate
firmware you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is re-established again automatically when the
update process is finished.
Extension modules
EM-BIO8-EFCP 1353
EM-BIO8-EFCP
EM-BIO8-EFCP is optional plug-in card. Through this card, the controller can accommodate one AC current
(CT) measuring input (1A or 5A input) and up to 8 binary inputs or outputs. In InteliConfig PC configuration
tool it is possible to easily choose whether particular I/O will be binary input or output.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Power supply
Power supply range 8-36 VDC
40 mA / 8 VDC
27 mA / 12 VDC
Power consumption
22 mA / 24 VDC
19 mA / 36 VDC
Binary outputs
Number Up to 8 , non-isolated
Max. current 0,5A
Switching to positive supply terminal
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Install package to computer or open PSI to install it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate
firmware you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is re-established again automatically when the
update process is finished.
Each generic module has 8 "terminals" (inputs/outputs) and the InteliNeo 6000 has the following amount of
the generic modules:
AI generic: 10
AO generic: 8
BI generic: 16
BO generic: 12
In the table below, you can see how many generic modules are necessary for each CAN module and how
many indexes are available for each type of CAN module in the InteliNeo 6000.
Max number of
CAN Module AI generic AO generic BI generic BO generic
indexes
Inteli AIN8 10 1 0 0 0
Inteli IO 8/8 12 0 1 1 1
Inteli IO 16/0 8 0 1 2 0
IGL-RA15 4 0 0 0 2
IGS-PTM 4 1 1 1 1
Inteli AIO9/1 5 2 1 0 0
Inteli AIN8TC 10 1 0 0 0
I-AOUT8 4 0 1 0 0
IS-AIN8 10 1 0 0 0
IS-AIN8TC 10 1 0 0 0
IS-BIN16/8 7 0 0 2 1
Note: When configuring modules do not forget to let first 4 indexes free for modules which can't use high
addresses such as IGL-RA15, IGS-PTM, AIO9/1, I-AOUT8.
Note: Module Inteli IO8/8 has available AOUT only if it is configured with index number below 9 and Inteli
AIO9/1 has available AOUT only if it is configured with index number below 5.
Note: Module Inteli IO8/8 with older FW than 1.3.1.2 has available AOUT only if it is configured with index
number below 5.
Module's protections
Each configured CAN module can has it's own protection and protection state. For setup: connect the
controller via InteliConfig → Control → Controller Configuration → Modules → Module Settings.
Protection Upon Module Failure
None - No alarm will be activated if module fails. It is not possible to use the User Protection State.
Warning - Wrn alarm is activated if module fails.
Shutdown - Sd alarm is activated if module fails.
Protection State - If you check the check box the new User Protection State will be displayed in the User
Protection States group in the Values after the configuration is imported to the CU.
Note: The name of the User Protection State is automatically generated according to the options Protection
Upon Module Failure, Module Name, and Module Index. The module name is automatically generated or
renamed by the user.
Example: Wrn Inteli AIN8 10 = Warning upon module failure of the Inteli AIN8 module with index 10.
Binary inputs
Pull Down
The pull-down logic is used when it is required to ensure that the logical value of inputs settles at the expected
logical level whenever external devices are turned off, or they are at a high impedance state. It ensures that
input is at a defined low logic level when the connection with external devices is lost. In the controller
(module), the pull-down resistor is used to connect the input to the -BAT (0 V), so the log 0 (open state) is
represented by 0 V. This connection is used as prevention against fluctuations and an undefined state at the
input.
The principle of internal connection is shown in the picture below.
The bulb represents internal state of binary input.
In case the “COM” (+Ucc) is not connected to the input terminal “BIN” then the internal state is logical 0.
In case the “COM” (+Ucc) is connected to the input terminal “BIN” then the internal state is logical 1.
Pull Up
The pull-up logic is used when it is required to establish an additional loop over the critical components while
making sure that the voltage is well-defined even when the switch is open. It ensures that input and wiring is
at a defined high logical level in the absence of an input signal. In the controller (module), the pull-up resistor
is used to connect the input to the +BAT (+Ucc), so the log 0 (open state) is represented by +Ucc. This
connection is used as prevention against fluctuations and an undefined state at the input.
The principle of internal connection is shown in the picture below.
The bulb represents internal state of binary input.
In case the input terminal “BIN” (+Ucc) is not connected to the “COM” (GND) then the internal state is
logical 0.
In case the input terminal “BIN” (+Ucc) is connected to the “COM” (GND) then the internal state is logical
1.
Binary outputs
Extension modules
Inteli AIN8 1361
Inteli IO8/8 1367
IGL-RA15 1374
IGS-PTM 1379
Inteli AIO9/1 1384
Inteli AIN8TC 1389
I-AOUT8 1393
IS-AIN8 1397
IS-AIN8TC 1407
IS-BIN16/8 1411
Inteli AIN8
Inteli AIN8 module is extension module equipped with analog inputs and Impulse/RPM input. The module is
connected to controller by CAN1A (page 19) bus. It is possible to connect up to 10 Inteli AIN8 external units
to one controller.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.
Analog inputs
8 channels
can be configured as:
resistor three wire input
current input
voltage input
All inputs can be configured to any logical function or protection.
Supported sensors
Sensors
PT100 [°C] (fix) PT100 [°F] (fix) +-1V 4-20mA passive 0-250 ohm
PT1000 [°C] (fix) PT1000 [°F] (fix) 0-2.4V 4-20mA active 0-2400 ohm
NI100 [°C] (fix) NI100 [°F] (fix) 0-5V 0-20mA passive 0-10k ohm
NI1000 [°C] (fix) NI1000 [°F] (fix) 0-10V +-20mA active
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
4. Connect the unit with PC via RS232-null modem cable and AT-Link conv
LED indication
Wiring
The following diagrams show the correct connection of sensors.
Terminator
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 110x110x46 mm (4,3”x4,3”x1,8”)
Weight 221,5 grams
Analog inputs
Number of channels 8
Range 0-10 V
Voltage
Accuracy: ± 0,25 % of actual value + ± 25 mV
Range: ±20 mA
Current
Accuracy: ± 0,25 % of actual value + ± 50 µA
Range: 0- 10 kΩ
Resistive
Accuracy: ± 0,5 % of actual value + ± 2 Ω
Inteli IO8/8
Inteli IO8/8 module is an extension module equipped with binary inputs, binary outputs and analog outputs.
The module is connected to controller by CAN1A (page 19) bus.
Inteli IO8/8 is the name of the module, but it is possible to configure the module (by internal switch) to two
configurations:
Inteli IO8/8 - 8 binary inputs, 8 binary outputs and 2 analog outputs
Inteli IO16/0 - 16 binary inputs, 0 binary outputs and 2 analog outputs
It is possible to connect up to 12 Inteli IO8/8 or 8 Inteli IO 16/0 external units to one controller.
CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set. When this LED is shining, then module is configured as 8 binary inputs and 8 binary outputs. When this
LED is dark, then the module is configured as 16 binary inputs.
LED at power connector - status LED
Wiring
The following diagrams show the correct connection of inputs and outputs.
Binary inputs - pull up
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the GND (-) - dashed line).
On lower picture is case of wiring between BIN2 and GND (-). Both ways are correct.
Binary inputs - pull down
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the Ucc (+) - dashed line).
On lower picture is case of wiring between BIN2 and Ucc (+). Both ways are correct.
When high side setting of outputs is chosen - binary output must be connected to the minus potential directly
Terminal VHS (voltage High side) has to be connected to positive potential directly. Maximal current of each
binary output is 500 mA. Size of fuse depends on load.
Binary outputs - low side
When low side setting of outputs is chosen - binary output must be connected to the plus potential of power
supply directly. Minus potential is connected internally - dashed line.
Analog outputs
IMPORTANT: Terminator for analog output has special analog ground (AGND), which must not be
connected to the GND.
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Analog outputs
Number of channels 2
Range 0-10 V
Voltage Accuracy: ± 20 mV + ±0,5 % of actual value
Imax 5 mA
Range: 0-20 mA
Current Accuracy: ± 100 µA + ±0,5 % of actual value
Rmax 500 Ω
Level 5 V
PWM Frequency - adjustable 200÷2400 Hz
Imax 20 mA
Binary inputs
Number of channels 8 for Inteli IO8/8, 16 for Inteli IO16/0
Input resistance 4400 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact
6 to 36 V DC
indication
Binary outputs
Number of channels 8 for Inteli IO8/8, 0 for Inteli IO16/0
Max current 500 mA
Max switching voltage 36 V DC
IGL-RA15
Remote annunciator (IGL-RA15) is designed as an extension signaling unit. The module is connected to
controller by CAN1A (page 19) bus. It is possible to connect up to 4 IGL-RA15 external units to one
controller.
The unit is equipped with a fully configurable tri-color (red, orange, green) LED for intuitive operation
together with high functionality.
Terminals
Horn Horn
CAN CAN1A (page 19) line
Power Power supply
CAN address
SW changing of CAN1A (page 19) address is enabled only when both jumpers are closed. Any one of these
addresses (1+2 or 3+4 or 5+6 or 7+8) can be set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
LED indication
Each LED color is adjusted independently of controller output settings. If controller output 1 is set as
“Common Shutdown” it doesn’t mean red LED1 color for iGL-RA15. The LEDs color can by adjust by
following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
Press Horn reset to change the LED1 color (green, yellow, red)
Press Lamp test to switch to the next LED color adjusting
Continue to adjust all LEDs color
After LED15 color adjusting press three times Lamp test
Note: If there is no operator action during address setting, color adjusting or timeout setting, the unit returns
to normal operation without changes saving.
Status LED
The signals LEDs are handled like binary outputs. It means all what can be configured to binary outputs can
be also configured to the LEDs of IGL-RA15.
Power LED
Horn setting
The horn output is activated if any of red or yellow LED is on. Output is on until pressing Horn reset or horn
timeout counts down. The timeout can by set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
Press Lamp test fifteen times
Note: If there is no operator action during address setting, color adjusting or timeout setting, the unit returns
to normal operation without changes saving.
Wiring
* use terminator resistor only when IGL-RA 15 is the last unit on the CAN1A bus.
Note: The shielding of the CAN bus cable has to be grounded at one point only!
Note: See the section Technical data (page 1378) for recommended CAN bus cable type
General data
Power supply 8 to 36 V DC
0.35-0.1A (+1Amax horn output) depends on supply
Current consumption
voltage
Protection IP65
Interface to controller CAN1A (page 19)
Humidity 85%
Storage temperature - 30 °C to + 80 °C
Operating temperature - 20 °C to + 70 °C
Dimensions (WxHxD) 180x120x55 mm
Weight 950 g
Horn output
Maximum current 1.0 A
Maximum switching voltage 36 V DC
IGS-PTM
IGS-PTM module is extension module equipped with binary inputs, binary outputs, analog inputs and analog
output. The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to 4 IGS-
PTM external units to one controller.
Analog inputs
Analog inputs can be configured for:
Resistance measurement
Current measurement
Voltage measurement
The type of analog inputs is configured via jumpers RUI located on lower PCB.
Supported sensors
Sensors
PT100 [°C] (fix) User curves
NI100 [°C] (fix) 0-100 mV
PT100 [°F] (fix) 0-2400 ohm
NI100 [°F] (fix) ±20 mA
Address configuration
If InteliLite controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labeled ADR1 and ADR2.
Programing firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper BOOT. RESET jumper
is used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set.
LED at power connector - status LED
Binary outputs
Resistance sensor
Voltage sensor
Analog outputs
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 100 mA at 24V ÷ 500 mA
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 95×96×43 mm (3.7’×3.8’×1.7’)
Analog inputs
Number of channels 4
Range 0-100 mV
Voltage
Accuracy: 1,5 % ± 1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0,5 ohm out of measured value
Range: 0- 250 Ω
Resistive
Accuracy: 1 % ± 2 ohm out of measured value
Binary inputs
Number of channels 8
Input resistance 4700 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact
8 to 36 V DC
indication
Binary outputs
Number of channels 8
Max current 500 mA
Max switching voltage 36 V DC
Number of channels 8
Range 0-100 mV
Voltage
Accuracy: 1,5 % ± 1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0,5 ohm out of measured value
Range: 0- 250 Ω
Resistive
Accuracy: 1 % ± 2 ohm out of measured value
Inteli AIO9/1
Inteli AIO9/1 module is an extension module equipped with analog inputs and outputs – designed for DC
measurement. The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to
5 Inteli AIO9/1 external units to one controller.
The detection of communication speed is indicated by rapid flashing of status LED. Once the speed is
detected the module remains set for this speed even when the communication is lost. Renewal of
communication speed detection is done by resetting of the module.
Analog inputs
4 channels AIN1 – AIN4 can be configured as:
Sensor ±65V (determined for measurement of battery voltage)
4 channels AIN5 – AIN8 can be configured as:
Thermocouples – type J,K or L (in °C or °F)
Sensor ±75mV DC – (for connecting current shunts)
1 channel AIN9 can be configured as:
RTD (Pt1000, Ni1000)
Common resistance 0-2400Ω
Supported sensors
Sensors
User curves ±65 V DC (fix linear) Thermocpl (nc) K [°C] (fix)
PT1000 [°C] (fix) ±75 mV (fix linear) Thermocpl (nc) L [°C] (fix)
NI1000 [°C] (fix) Thermocpl J [°C] (fix) Thermocpl (nc) J [°F] (fix)
PT1000 [°F] (fix) Thermocpl K [°C] (fix) Thermocpl (nc) K [°F] (fix)
NI1000 [°F] (fix) Thermocpl L [°C] (fix) Thermocpl (nc) L [°F] (fix)
0-2400 Ω (fix linear) Thermocpl (nc) J [°C] (fix)
LED indication
Technical data
General data
Dimension (W × H × D) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 248 grams
CAN1 – galvanic separated from power
Interface to controller
supply and measurement,
Analog output
I 0-20mA /500Rmax. ± 1 % of actual value + ± 200 uA
U 0-10V ± 0.5 % of actual value + ± 50 mV
PWM – 5 V, 200 Hz-2.4kHz 15 mA max.
Galvanic separated from power supply
Galvanic
CAN bus is galvanic separated from the measurement and power supply
separation
Power supply 8 to 36 V DC
Protection IP20
Current consumption 150 mA at 24 V ÷ 400 mA at 8 V
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 80 °C
Inteli AIN8TC
Inteli AIN8TC module is extension module equipped with 8 analog inputs dedicated for thermocouple sensors
only. The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to 10 Inteli
AIO9/1 external units to one controller.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.
Analog inputs
8 channels
Can be configured as thermocouple sensors only
All inputs can be configured to any logical function or protection
Supported sensors
Sensors
Thermocpl J [°C] (fix) Thermocpl (nc) J [°C] (fix)
Thermocpl K [°C] (fix) Thermocpl (nc) K [°C] (fix)
Thermocpl L [°C] (fix) Thermocpl (nc) L [°C] (fix)
Thermocpl J [°F] (fix) Thermocpl (nc) J [°F] (fix)
Thermocpl K [°F] (fix) Thermocpl (nc) K [°F] (fix)
Thermocpl L [°F] (fix) Thermocpl (nc) L [°F] (fix)
CAN address
DIP switch determinates CAN address for analog inputs.
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware is upgraded via AT-link (TTL). For programming it is necessary to close jumper TEST.
For programming FlashProg PC tool version 4.2 or higher must be used.
LED indication
Wiring
The following diagrams show the correct connection of sensors.
Thermocouple
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 237.5 grams
Analog inputs
Number of channels 8, no galvanic separated
Range: ± 100 mV
Voltage Accuracy: ± 0.1 % of actual value + ± 100 µV
(± 3 °C)
I-AOUT8
I-AOUT8 is an extension unit with 8 analog outputs. Each analog output can be switched to
0 to 20 mA DC
0 to 10 V DC
PWM (Pulse With Modulation on 1,2 kHz)
The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to 4 I-AOUT8
external units to one controller. The corresponding module Address 1 to 4 (default 1) must be set on module
(by Adr.1 and Adr.2 jumpers) and in controller configuration. CAN1 terminating 120 ohm resistor jumper is
connected as default. AGND terminals are on the same potential.
Connectors
CAN Address
The module CAN address is set by jumpers A1 and A2. Set module CAN address correspondingly to
configuration according table below.
CAN Address A1 A2
1 Open Open
2 Close Open
3 Open Close
4 Close Close
Output mode
Follow the p – I – I – U symbols on the module sticker. There are two equivalent positions for current output.
PWM
p
Pulse-Width-Modulation
l 0 to 20 mA DC
U 0 to 10 V DC
Programming firmware
Firmware upgrade is via AT-link (TTL). For programming it is necessary to close jumper BOOT. RESET
jumper is used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC
tool.
CAN1 termination
I-AOUT8 has own CAN terminating resistor (120 ohm). Close jumper CAN-R to connect terminating resistor
to CAN bus, open jumper CAN-R disconnecting terminating resistor.
PWM output
PWM output
1200 Hz
Current
Current output 0 to 20
output 0 to
mA DC
20 mA DC
Current
Current output 0 to 20
output 0 to
mA DC
20 mA DC
Voltage
Voltage output 0 to 10
output 0 to
V DC
10 V DC
Image 7.110 Possible output modes
Technical data
Power supply 8 to 36 V DC
Analog output refreshment 320 ms
Current consumption max 300 mA (100 mA at 24 V)
RS232 interface TTL, firmware upgrade via AT-link.
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2.5 W
IS-AIN8
IS-AIN8 is input extension module equipped with 8 analog inputs which can be configured to:
Resistor two wire input
Resistor three wire input
Current input
Supported sensors
Sensors
PT100 [°C] (fix) PT100 [°F] (fix) +-1V 4-20mA passive 0-250 ohm
PT1000 [°C] (fix) PT1000 [°F] (fix) 0-2.4V 4-20mA active 0-2400 ohm
NI100 [°C] (fix) NI100 [°F] (fix) 0-5V 0-20mA passive 0-10k ohm
NI1000 [°C] (fix) NI1000 [°F] (fix) 0-10V +-20mA active
TC Sensors
Thermocpl J [°C] (fix) Thermocpl (nc) J [°C] (fix)
Thermocpl K [°C] (fix) Thermocpl (nc) K [°C] (fix)
Thermocpl L [°C] (fix) Thermocpl (nc) L [°C] (fix)
Thermocpl J [°F] (fix) Thermocpl (nc) J [°F] (fix)
Thermocpl K [°F] (fix) Thermocpl (nc) K [°F] (fix)
Thermocpl L [°F] (fix) Thermocpl (nc) L [°F] (fix)
Note: “nc” means“ not cold junction compensation (by external sensor).In this case is used internal
temperature sensor on the PCB
CAN Address
CAN 1 address is set by following procedure:
1. Press Address button during IS-AIN8 power supply on to switch to addressing mode.
2. Then repeatedly press or keep pressed address button to adjust required address according to controller
configuration.
3. After setting requested address, release the buttons and wait until the digits blink – it indicates writing of
the change address to EEPROM memory.
CAN 1 Address
1. IS-AIN8 1
2. IS-AIN8 2
3. IS-AIN8 3
4. IS-AIN8 4
5. IS-AIN8 5
6. IS-AIN8 6
7. IS-AIN8 7
SW version check
Let suppose IS-AIN8 of SW version 1.4. Shortly press address button. Following sequence appears on the
display: number “1”, one second pause, number “4”, two second pause, number “1”, one second pause,
number “4”, two second pause and finally IS-AIN8 actual address. Error message (e.g. SD BOUT2) appears
on Controller screen when Binary input or output Address x is configured but corresponding unit is not
recognized (no message is received from CAN bus). Check IS configuration and corresponding external IS-
AIN8, IS-BIN8/16 unit address setting.
LED indication
Tx Rx
Lighting Blink Lighting Blink
Any data are
Any data are transmitted Data are transmitted on the CAN1 Data are received
received on the
on the CAN1 line line on the CAN1 line
CAN1 line
Wiring
Select sensor characteristic from the list or define user sensor characteristic in PC configuration tool.
D terminal is shielding
Note: If the thermocouples are connected to IS-AIN8, appropriate jumpers must be removed (see rear
sticker). (jumpers are placed under the cover)
Example 1 shows the correct temperature measurement. The 3rd metal (the cable between IS-AIN8 and
thermocouple) is connected in cold bath which temperature is 0°C. This is very difficult to provide in real
application.
Example 2 shows the correct temperature measurement. The 3rd metal (the cable between IS-AIN8 and
thermocouple) is connected in ambient environment which temperature is not 0°C, but T1°C. Resultant
temperature is correct, because is compensated by internal IS-AIN8 temperature sensor. The
temperature of IS-AIN8 and junction is the same T-T1+T1 (reduced and compensated by T1).
Example 3 shows the incorrect temperature measurement. The 3rd metal (the cable between IS-AIN8
and thermocouple) is connected in ambient environment which temperature is not 0°C, but T1°C.
Resultant temperature is T-T1 (reduced by T1). Internal IS-AIN8 compensation should not by used
because measures T2 temperature, not T1!
Example 4 shows the correct temperature measurement. The 3rd metal (the cable between IS-AIN8 and
thermocouple) is connected in ambient environment which temperature is not 0°C, but T1°C. Resultant
temperature is correct, because is compensated by external temperature sensor, T+T1 (reduced and
compensated by T1).
Example 2 is a standard wiring between thermocouple sensor and IS-AIN8. IS-AIN8 is placed in the
same ambient temperature as thermocouple terminal; it means IS-AIN8’s internal temperature sensor
measures the same temperature as is on thermocouple terminal. In this case, could junction
compensation is done by IS-AIN8 itself. Any of standard (compensated) sensors should be selected.
Example 3 is a standard wiring between thermocouple sensor and IS-AIN8. Regardless selected type of
sensor the resultant temperature will be incorrect
Not compensated sensor – temperature T1 is not calculated
Compensated sensor – IS-AIN8 measures different T2 temperature, not T1
Example 4 External temperature T1sensor is included. Resultant temperature is correct if
Any of not compensated sensors (nc) is selected
External sensor has a function Cold Temp 1
Technical data
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
EN 50081-1:94, EN 50081-2:96
Electromagnetic Compatibility
EN 50082-1:99, EN 50082-2:97
Supported sensors
Sensors
Thermocpl J [°C] (fix) Thermocpl (nc) J [°C] (fix)
Thermocpl K [°C] (fix) Thermocpl (nc) K [°C] (fix)
Thermocpl L [°C] (fix) Thermocpl (nc) L [°C] (fix)
Thermocpl J [°F] (fix) Thermocpl (nc) J [°F] (fix)
Thermocpl K [°F] (fix) Thermocpl (nc) K [°F] (fix)
Thermocpl L [°F] (fix) Thermocpl (nc) L [°F] (fix)
Note: “nc” means“ not cold junction compensation (by external sensor).In this case is used internal
temperature sensor on the PCB
CAN Address
CAN1 address is set by following procedure:
CAN11 Address
1. IS-AIN8TC 1
2. IS-AIN8TC 2
3. IS-AIN8TC 3
4. IS-AIN8TC 4
5. IS-AIN8TC 5
6. IS-AIN8TC 6
7. IS-AIN8TC 7
8. IS-AIN8TC 8
9. IS-AIN8TC 9
10. IS-AIN8TC 0
Table 7.7 Table of recommended CAN1 address setting
SW version check
Shortly press address button. Following sequence appears on the display: number “1”, one second pause,
number “4”, two second pause, number “1”, one second pause, number “4”, two second pause and finally IS-
AIN8TC actual address.
Error message (e.g. SD BOUT2) appears on Controller screen when Binary input or output Address x is
configured but corresponding unit is not recognized (no message is received from CAN bus). Check IS
configuration and corresponding external IS-AIN8TC, IS-BIN8/16 unit address setting.
LED indication
Tx Rx
Dark Blink Dark Blink
Any data are transmitted Data are transmitted on Any data are received Data are received on
on the CAN1 line the CAN1 line on the CAN1 line the CAN1 line
Table 7.9 Tx/Rx LED status
Note: CAN bus line has to be terminated by 120 ohm resistors on the both ends.
For longer distances is recommended to connect CAN COM terminals between all controllers and cable
shielding to the ground in one point!
External units can be connected on the CAN bus line in any order, but line arrangement (no tails no star) is
necessary.
Recommended CAN bus data cables see in Chapter Technical data.
IG-MU and IG-IB units are connected to CONTROLLER CAN2 bus.
Select sensor characteristic from the list or define user sensor characteristic in PC configuration tool.
Technical data
Power supply 8 to 36 V DC
Protection IP20
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2W
IS-BIN16/8
IS-BIN16/8 is an extension module with 16 binary inputs (galvanic separated) and 8 binary output (galvanic
separated), 2 pulse inputs (frequency measurement or pulse counting). All I/O can be configured to any
logical function or protection. It is possible to connect up to 7 IS-BIN16/8 external units to one controller.
External modules IS-BIN16/8 is connected to controller CAN1A (page 19) bus. To operate external modules:
Connect all external modules to CAN1 bus line
On each module adjust I/O CAN1 address in the range of 1 to 7 for IS-BIN16/8 output, 1,3,5,7,9,11,13 for
IS-BIN18/8 inputs
In case of use generic module in configuration you can set CAN address from 1 – 12
In case of set 0 CAN address - inputs/ outputs are deactivated
Input output address is displayed on the front panel LCD’s
Use PC configuration tool to configure controller according external modules setting
IS-BIN16/8 module has two separate CAN1 addresses for binary inputs Group 1, Group 2 and binary output
Group (total three addresses). The CAN1 address for BI Group 1 and for BO Group 2 can be adjusted on the
IS-BIN16/8. The address for BI Group 2 is set automatically to the address following BI Group 1.
Note: CAN address 0 disables corresponding CAN message (Group data are not send).
CAN Address
CAN 1 address is setting by following procedure:
Press Address buttons (for INPUTS address and OUTPUT address) during IS-BIN8 power supply on to
switch to addressing mode.
Then repeatedly press or keep pressed address button to adjust required address according to
CONTROLLER configuration.
After setting requested address, release the buttons and wait until the digits blink – it indicates write the
changed address to EEPROM memory.
CAN 1 Address
Inputs Output
1. IS-BIN16/8 1 1
2. IS-BIN16/8 3 2
3. IS-BIN16/8 5 3
SW version check
Let suppose IS-AIN8 of SW version 1.4. Shortly press address button. Following sequence appears on the
display: number “1”, one second pause, number “4”, two second pause, number “1”, one second pause,
number “4”, two second pause and finally IS-AIN8 actual address.
Error message (e.g. SD BOUT2) appears on Controller screen when Binary input or output Address x is
configured but corresponding unit is not recognized (no message is received from CAN bus). Check IS
configuration and corresponding external IS-AIN, IS-BIN unit address setting.
LED indication
Tx Rx
Dark Blink Light Dark Blink Light
Any data are Data are Any data are Data are
transmitted on the transmitted on the received on the received on the
CAN1 line CAN1 line CAN1 line CAN1 line
Wiring
Image 7.111 CAN bus line has to be terminated by 120 ohm resistors on the both ends.
Note: CAN bus line has to be terminated by 120 ohm resistors on the both ends.
For longer distances is recommended to connect CAN COM terminals between all controllers and cable
shielding to the ground in one point!
Recommended CAN bus data cables see in Chapter Technical data.
External units can be connected on the CAN bus line in any order, but line arrangement (no tails no star) is
necessary-
Recommended CAN bus data cables see in Chapter Technical data.
Binary inputs Common terminal is connected to Binary inputs common terminal is connected to
positive supply terminal, Binary inputs contacts are negative supply terminal, Binary inputs contacts are
closed to negative supply terminals. closed to positive supply terminals.
Input voltage range for opened contact is from 8 VDC to Power supply VDC. Input voltage range for closed
contact is from 0 to 2 VDC. Voltage level is defined between Binary input and Binary input COM terminal and
does not depend on “positive” or “negative” connection.
IMPORTANT: Impulse inputs are not supported by the controller.
Binary output
The Common terminal can be connected to positive or negative pole (HW3.0 only) – see following drawing.
Binary outputs are galvanic separated from IS-BIN16/8 power supply (have a look at technical data). The
maximum load values are 0.5 A / 36V for one output.
Binary output common terminal is connected to Binary output common terminal is connected to
negative supply terminal, Binary output contacts are positive supply terminal, Binary output contacts are
closed to positive supply terminals. closed to negative supply terminals.
For more extension units use separate fusing according to the table above.
Controller power supply should never be connected to starter terminals.
Technical data
Relays outputs (galvanic separated) only HW 3.0 (non galvanic separated) HW 2.1
Number of output 8
Maximum current 0.5A DC
Maximum switching voltage 36 VDC
Power supply 8 to 36 V DC
Protection front panel IP20
Current consumption 250 mA** at 24 V
Humidity 95% without condensation
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2W
Standard conformity
Number of output 8
Low Voltage Directive EN 61010-1:95 +A1:97
EN 50081-1:94, EN 50081-2:96
Electromagnetic Compatibility
EN 50082-1:99, EN 50082-2:97
*RPM1, RPM2 are available in IS-CU only **During powering up current can be up to 1.5A
6 back to Extension modules