Intelineo 6000 1.5.0 Global Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1417

InteliNeo

6000
Controller for parallel hybrid
microgrid applications

SW version 1.5.0
1 Document information 6
2 System overview 14
3 Applications overview 40
4 Installation and wiring 43
5 Controller setup 82
6 Grid Codes 299
7 Communication 311
8 Technical data 335
9 Appendix 337

Copyright © 2023 ComAp a.s.


Written by ComAp
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: info@comap-control.com, www.comap-control.com Global Guide
Table of contents
1 Document information 6 2.7.4 InteliSCADA 23
1.1 Clarification of Notation 6 2.8 Displays 23
1.2 About this Global Guide 6 2.8.1 InteliVision 5.2 24
1.3 Legal notice 6 2.8.2 InteliVision 10Touch 24
1.4 Used open source software: 8 2.8.3 InteliVision 13Touch 25
1.5 General warnings 9 2.8.4 InteliVision 18Touch G1/G2 25
1.5.1 Remote control and programming 9 2.9 Plug-in Modules 25
1.5.2 SW and HW versions compatibility 9 2.9.1 CM2-4G-GPS 26
1.5.3 Dangerous voltage 10 2.9.2 CM-4G-GPS 26
1.5.4 Adjust the setpoints 10 2.9.3 EM-BIO8-EFCP 26
1.6 Functions and protections 10 2.10 CAN Extension Modules 27
1.7 Certifications and standards 11 2.10.1 Inteli AIN8 27
1.8 Document history 11 2.10.2 Inteli IO8/8 28
1.9 Symbols in this manual 12 2.10.3 IGL-RA15 28
2.10.4 IGS-PTM 29
2 System overview 14
2.10.5 Inteli AIO9/1 29
2.1 General description 14
2.10.6 Inteli AIN8TC 30
2.1.1 The key features of InteliNeo 6000 14
2.10.7 I-AOUT8 30
2.2 Getting Started 15
2.10.8 IS-AIN8 30
2.3 Measurement methods 16
2.10.9 IS-AIN8TC 31
2.3.1 True RMS measurement 16
2.10.10 IS-BIN16/8 31
2.3.2 Symmetrical components 16
2.11 CAN Communication Modules 32
2.4 AC measurement 17
2.11.1 InteliGateway 300 32
2.4.1 AC measurement settings 17
2.11.2 I-CR 32
2.4.2 Frequency measurement accuracy
2.12 Virtual modules 32
and resolution 17
2.12.1 Distributed modules 33
2.4.3 PF measurement and evaluation 17
2.12.2 Shared modules 35
2.4.4 Waveform distortion measurements 18
2.5 Communication peripherals 18 3 Applications overview 40
2.6 Configurability and monitoring 20 3.1 MPTM 41
2.6.1 Supported configuration and 3.2 MINT 42
monitoring tools 20
2.6.2 Configuration parts 20 4 Installation and wiring 43
2.7 PC tools 22 4.1 Package content 43
2.7.1 InteliConfig 22 4.2 Controller installation 44
2.7.2 WebSupervisor 22 4.2.1 Dimensions 44
2.7.3 WinScope 1000 23 4.2.2 Mounting 44

InteliNeo 6000 1.5.0 Global Guide 2


4.3 Terminal Diagram 46 5.4.8 CAN1 ECU/IO Modules Splitting 133
4.4 Recommended wiring 48 5.4.9 Configuration Lock 135
4.4.1 General 50 5.4.10 Configuration Override 135
4.4.2 Grounding 50 5.4.11 Control Groups 136
4.4.3 Power supply 51 5.4.12 Crash Dump 137
4.4.4 Measurement wiring 52 5.4.13 Distributed Power Management
4.4.5 Binary Inputs 64 Signals 138

4.4.6 Binary Outputs 65 5.4.14 E-STOP 143

4.4.7 E-Stop 66 5.4.15 Event History 145

4.4.8 Analog Inputs 67 5.4.16 Exercise Timers 149

4.4.9 Analog Outputs 70 5.4.17 Firewall 157

4.4.10 CAN bus and RS485 wiring 71 5.4.18 Forced Value 158

4.4.11 USB 74 5.4.19 Hot Swap Redundancy 160

4.4.12 Ethernet 75 5.4.20 I/O Configuration 166

4.4.13 Cellular Connection 76 5.4.21 Load Shedding 171

4.5 External display 79 5.4.22 Loss of Mains (Decoupling)


Protections 173
4.5.1 InteliVision Displays 79
5.4.23 Mains Import Measurement 175
4.6 Maintenance 81
5.4.24 Modbus Client (Master) 176
4.6.1 Backup battery replacement 81
5.4.25 Multiple ECU 180
5 Controller setup 82 5.4.26 Operating Modes 181
5.1 Operator Guide 82 5.4.27 PLC - Programmable Logic
5.1.1 InteliVision 5.2 82 Controller 183

5.2 Controller configuration and PC tools 5.4.28 Power Formats And Units 196
connection 112 5.4.29 Protections 197
5.2.1 USB 112 5.4.30 Pulse Counters 211
5.2.2 Ethernet 113 5.4.31 PV Inverter Slots 212
5.3 Default configuration 118 5.4.32 SD Card Storage 215
5.3.1 Binary inputs 118 5.4.33 Sensor Curves 216
5.3.2 Binary outputs 119 5.4.34 Service Timers 218
5.3.3 Analog inputs 119 5.4.35 Sunrise/Sunset 219
5.3.4 Analog Outputs 119 5.4.36 Sunspec 219
5.4 General Functions 119 5.4.37 System Start/Stop 219
5.4.1 3V3 Reference Voltage Measurement121 5.4.38 SW Key Features 219
5.4.2 Access lock 121 5.4.39 Universal Genset support 220
5.4.3 Alarm Management 122 5.4.40 User Buttons 224
5.4.4 AMF Function 125 5.4.41 User Management And Data Access
5.4.5 Breaker Control 126 Control 226

5.4.6 CAN Bus Log 131 5.4.42 User Setpoints 232

5.4.7 CAN Intercontroller Communication 132 5.4.43 Voltage Phase Sequence Detection 235

InteliNeo 6000 1.5.0 Global Guide 3


5.5 Application related functions 235 through - LVRT-2ph
5.5.1 Application & System Variability 237 6.6.3 1-pole undervoltage failure ride
5.5.2 BESS Charging/Discharging Control 239 through - LVRT-1ph 305

5.5.3 BESS Forced power 241 6.6.4 Overvoltage failure ride through -
OVRT 305
5.5.4 BESS Operation States 241
6.6.5 Post VRT 306
5.5.5 BESS Output Control 244
6.7 P For Q 306
5.5.6 BESS Precharge Types 245
6.7.1 UQ Area 306
5.5.7 BESS Stabilization 246
6.7.2 PQ Area 306
5.5.8 BESS/PV PF/Q Control 247
6.8 Q&U Protection 307
5.5.9 Connecting To Load 248
6.9 Synchronization & Connection Conditions 307
5.5.10 Curtailment Counter 254
6.9.1 Network connection/reconnection
5.5.11 Multiple Island Operation 256
conditions 307
5.5.12 Output Control – Frequency/Load 256
6.9.2 Network connection/reconnection
5.5.13 Output Control - Voltage/PF 259
conditions after Mains Fail 308
5.5.14 Parallel To Mains Operation - MINT
6.10 After Mains Trip Period 308
Application 261
6.11 Pave 309
5.5.15 Parallel To Mains Operation - MPTM
6.12 Moving Average 309
Application 263
6.12.1 10-minutes averages 309
5.5.16 Power Management 274
6.12.2 1-minute averages 310
5.5.17 PV Curtailment 295
6.13 BESS Operation Area 310
5.5.18 Regulation Loops 295

7 Communication 311
6 Grid Codes 299
7.1 PC 311
6.1 What are Grid Codes 299
7.1.1 Direct communication 311
6.2 Testing of Grid Codes 299
7.1.2 Remote communication 312
6.3 Power Regulation Based On Over/Under
Frequency 299 7.2 Connection to 3rd party systems 314

6.3.1 Power reduction by over frequency - 7.2.1 SNMP 314


PoF 299 7.2.2 Modbus-RTU, Modbus/TCP 316
6.3.2 Power increase by under frequency -
PuF 300 8 Technical data 335

6.3.3 Return from over/under frequency 301


9 Appendix 337
6.4 Power Regulation Based On Actual Mains
9.1 Controller objects 337
Voltage 302
9.1.1 List of controller objects types 337
6.4.1 P Instal (Um) 302
9.1.2 Renameable controller objects 338
6.4.2 P Actual (Um) 302
9.1.3 Setpoints 338
6.5 Load Reduction 303
9.1.4 Values 691
6.6 Dynamic Support - VRT 304
9.1.5 Application Curves 966
6.6.1 3-pole undervoltage failure ride
through - LVRT-3ph 304 9.1.6 Logical binary inputs 985

6.6.2 2-pole undervoltage failure ride 9.1.7 Logical binary outputs 1048
305

InteliNeo 6000 1.5.0 Global Guide 4


9.1.8 Logical analog inputs 1111
9.1.9 Fixed Protection States 1179
9.1.10 User Protection States 1188
9.1.11 PLC 1191
9.2 Alarms 1245
9.2.1 Alarm levels in the controller 1245
9.2.2 Alarms level 1 1245
9.2.3 Alarms level 2 1278
9.2.4 Other alarms 1298
9.3 Modules 1350
9.3.1 Plug-in modules 1350
9.3.2 CAN modules 1355
6 back to Table of contents

InteliNeo 6000 1.5.0 Global Guide 5


1 Document information
1.1 Clarification of Notation 6
1.2 About this Global Guide 6
1.3 Legal notice 6
1.4 Used open source software: 8
1.5 General warnings 9
1.6 Functions and protections 10
1.7 Certifications and standards 11
1.8 Document history 11
1.9 Symbols in this manual 12

6 back to Table of contents

1.1 Clarification of Notation


Note: This type of paragraph calls the reader’s attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

1.2 About this Global Guide


This manual contains important instructions for InteliNeo 6000 controllers family that shall be followed during
installation and maintenance of the controllers.
This manual provides general information how to install and operate InteliNeo 6000 controllers.
This manual is dedicated for:
Operators
Control panel builders
For everybody who is concerned with installation, operation and maintenance

1.3 Legal notice


This End User's Guide/Manual as part of the Documentation is an inseparable part of ComAp’s Product
and may be used exclusively according to the conditions defined in the “END USER or Distributor LICENSE
AGREEMENT CONDITIONS – COMAP CONTROL SYSTEMS SOFTWARE” (License Agreement) and/or in
the “ComAp a.s. Global terms and conditions for sale of Products and provision of Services” (Terms) and/or in
the “Standardní podmínky projektů komplexního řešení ke smlouvě o dílo, Standard Conditions for Supply of
Complete Solutions” (Conditions) as applicable.

InteliNeo 6000 1.5.0 Global Guide 6


ComAp’s License Agreement is governed by the Czech Civil Code 89/2012 Col., by the Authorship Act
121/2000 Col., by international treaties and by other relevant legal documents regulating protection of the
intellectual properties (TRIPS).
The End User and/or ComAp’s Distributor shall only be permitted to use this End User's Guide/Manual with
ComAp Control System Registered Products. The Documentation is not intended and applicable for any
other purpose.
Official version of the ComAp’s End User's Guide/Manual is the version published in English. ComAp
reserves the right to update this End User's Guide/Manual at any time. ComAp does not assume any
responsibility for its use outside of the scope of the Terms or the Conditions and the License Agreement.
Licensed End User is entitled to make only necessary number of copies of the End User's Guide/Manual. Any
translation of this End User's Guide/Manual without the prior written consent of ComAp is expressly
prohibited!
Even if the prior written consent from ComAp is acquired, ComAp does not take any responsibility for the
content, trustworthiness and quality of any such translation. ComAp will deem a translation equal to this End
User's Guide/Manual only if it agrees to verify such translation. The terms and conditions of such verification
must be agreed in the written form and in advance.
For more details relating to the Ownership, Extent of Permitted Reproductions Term of Use of the
Documentation and to the Confidentiality rules please review and comply with the ComAp’s License
Agreement, Terms and Conditions available on www.comap-control.com.
Security Risk Disclaimer
Pay attention to the following recommendations and measures to increase the level of security of ComAp
products and services.
Please note that possible cyber-attacks cannot be fully avoided by the below mentioned recommendations
and set of measures already performed by ComAp, but by following them the cyber-attacks can be
considerably reduced and thereby to reduce the risk of damage. ComAp does not take any responsibility for
the actions of persons responsible for cyber-attacks, nor for any damage caused by the cyber-attack.
However, ComAp is prepared to provide technical support to resolve problems arising from such actions,
including but not limited to restoring settings prior to the cyber-attacks, backing up data, recommending other
preventive measures against any further attacks.
Warning: Some forms of technical support may be provided against payment. There is no legal or factual
entitlement for technical services provided in connection to resolving problems arising from cyber-attack or
other unauthorized accesses to ComAp's Products or Services.
General security recommendations and set of measures
1. Production mode
Disable production mode BEFORE the controller is put into regular operation.
2. User accounts
Change password for the existing default administrator account or replace that account with a
completely new one BEFORE the controller is put into regular operation mode.
Do not leave PC tools (e.g. InteliConfig) unattended while a user, especially administrator, is logged in.
3. AirGate Key
Change the AirGate Key BEFORE the device is connected to the network.
Use a secure AirGate Key – preferably a random string of 8 characters containing lowercase,
uppercase letters and digits.
Use a different AirGate Key for each device.

InteliNeo 6000 1.5.0 Global Guide 7


4. MODBUS/TCP
The MODBUS/TCP protocol (port TCP/502) is an instrumentation protocol designed to exchange data
between locally connected devices like sensors, I/O modules, controllers etc. By it's nature it does not
contain any kind of security – neither encryption nor authentication. Thus it is intended to be used only
in closed private network infrastructures.
Avoid using MODBUS/TCP in unprotected networks (e.g. Internet).
5. SNMP
The SNMP protocol (port UDP/161) version 1 and version 2 are not encrypted. They are intended to be
used only in closed private network infrastructures.
Avoid using SNMP v1 and v2 in unprotected networks (e.g. Internet).

IMPORTANT: Controller issues Wrn Default Password (page 1251) alarm, if the factory default
password is used. It is necessary to change the factory default settings of password to be able to
clear the alarm.

1.4 Used open source software:


Name of
Modified Type License condition web address
software
CMSIS Copyright (C) 2020 Amazon.com, Inc. or
MIT license
FreeRTOS its affiliates. All Rights Reserved.
Copyright (C) Amazon Web Services, Inc.
FreeRTOS MIT license
or its affiliates. All rights reserved.
Copyright (C) 2006-2015, ARM Limited,
Mbed TLS Apache 2.0 license
All Rights Reserved
Copyright (c) 2001-2004 Swedish Institute
lwIP BSD 3 license
of Computer Science. All rights reserved.
Copyright (C) 1991-2, RSA Data Security,
Free ad-
MD5 – license Inc. Created 1991. All rights reserved
hoc license
RSA Data Security, Inc. MD5 Message-Digest Algorithm

Embedded
Copyright (c) 2016 jwellbelove
Template MIT license
www.etlcpp.com
Library
STM32Cube_
BSD 3 license
FW_H7
Copyright (C) 20xx, ChaN, all right
reserved.
Modify This software is provided by the copyright holder and
FatFs license contributors "AS IS" and any warranties related to this
BSD
software are DISCLAIMED. The copyright owner or
contributors be NOT LIABLE for any damages caused
by use of this software.

Copyright (c) 2011, 2013 Mutsuo Saito,


Tiny Mersenne Makoto Matsumoto, Hiroshima University
– BSD 3 license
Twister and The University of Tokyo All rights
reserved.

InteliNeo 6000 1.5.0 Global Guide 8


Copyright (c) 2018 STMicroelectronics
International N.V. All rights reserved
THIS SOFTWARE IS PROVIDED BY
STMICROELECTRONICS AND CONTRIBUTORS "AS
IS" AND ANY EXPRESS, IMPLIED OR STATUTORY
WARRANTIES, INCLUDING, BUT NOT LIMITED TO,
THE IMPLIED WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE AND NON-
INFRINGEMENT OF THIRD PARTY INTELLECTUAL
PROPERTY RIGHTS ARE DISCLAIMED TO THE
FULLEST EXTENT PERMITTED BY LAW. IN NO
USB SLA0044 license EVENT SHALL STMICROELECTRONICS OR
CONTRIBUTORS BE LIABLE FOR ANY DIRECT,
INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR
CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT
LIMITED TO, PROCUREMENT OF SUBSTITUTE
GOODS OR SERVICES; LOSS OF USE, DATA, OR
PROFITS; OR BUSINESS INTERRUPTION)
HOWEVER CAUSED AND ON ANY THEORY OF
LIABILITY, WHETHER IN CONTRACT, STRICT
LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
OTHERWISE) ARISING IN ANY WAY OUT OF THE
USE OF THIS SOFTWARE, EVEN IF ADVISED OF
THE POSSIBILITY OF SUCH DAMAGE.

Copyright (c) 2013-2015, Scott Vokes


<vokes.s@gmail.com> All rights reserved
heatshrink – ISC license Permission to use, copy, modify, and/or distribute this
software for any purpose with or without fee is hereby
granted, provided that the above copyright notice and
this permission notice appear in all copies.

license
GCC Runtime GCC Runtime Library Exception - GNU
– GPL 3 exception,
Library Project - Free Software Foundationd
license

1.5 General warnings


1.5.1 Remote control and programming
The controller can be controlled remotely. In the event that maintenance of the site has to be done, or the
controller has to be programmed, check the following points to ensure that any part of the site will not react
unpredictably (unwanted/random start of the BESS or any other part of the system).
To be sure:
Disconnect remote control
Disconnect binary outputs

1.5.2 SW and HW versions compatibility


Be aware to use the proper combination of SW and HW versions. The compatibility check is performed on two
levels.
The controller itself checks its hardware identification against the uploaded configuration at start up and
evaluates the match.

InteliNeo 6000 1.5.0 Global Guide 9


The configuration tool InteliConfig performs a compatibility check when the firmware upload menu is opened and
displays the compatible software for the connected controller.

1.5.3 Dangerous voltage


In no case touch the terminals for voltage and current measurement!
Always connect grounding terminals!
In no case do not disconnect controller CT terminals!

1.5.4 Adjust the setpoints


All parameters are adjusted to their typical values. However, the setpoints have to be checked and adjusted to
their real values before the first starting of the BESS .
IMPORTANT: Wrong adjustment of setpoints can destroy the BESS.

Note: The controller contains a large number of configurable setpoints, because of this it is impossible to
describe all of its functions. Some functions can be changed or have different behavior in different SW versions.
Always check the Global guide and New feature list for SW version which is used in controller. This manual only
describes the product and is not guaranteed to be set for your application.

IMPORTANT: Be aware that the binary outputs can change state during and after software
reprogramming (before the controller is used again ensure that the proper configuration and
setpoint settings are set in the controller).

The following instructions are for qualified personnel only. To avoid personal injury do not perform any action not
specified in related guides for product.

1.6 Functions and protections


Support of functions and protections as defined by ANSI (American National Standards Institute):

ANSI
Description ANSI code Description ANSI code Description
code
Master unit 1 Load shedding 32P AC circuit breaker 52
Stopping device 5 Master sequence device 34 Power factor 55
Multi-function device 11 Undercurrent 37 Overvoltage 59
Speed and frequency matching
15 Unit sequence starting 44 Alarm relay * 74
device
16EFT
Data communications device Current unbalance 46 Vector shift 78
16SC
Starting-to-running transition
19 Voltage unbalance 47 Reclosing relay 79
contractor
Distance relay 21 Incomplete sequence relay 48 Overfrequency 81H
Synchronizing-check 25 Temperature monitoring 49T Underfrequency 81U
Thermal relay 26 Overcurrent 50/50TD ROCOF 81R
Undervoltage 27 Earth fault current 50N+64 Auto selective control/transfer 83
Annunciator 30 Overcurrent IDMT 51 Regulating device 90
Overload 32 Earth fault current IDMT 51+64

* extension module IGL-RA15 required

InteliNeo 6000 1.5.0 Global Guide 10


1.7 Certifications and standards
EN 61000-6-2 EN 60068-2-1 (-40 °C/16 h) UL6200 *

EN 61000-6-4 EN 60068-2-2 (70 °C/16 h) UKCA

EN 61010-1 EN 60068-2-6 (2÷25 Hz / ±1,6 mm; 25÷100 Hz / 4,0

EN 60255-1 g)
2
EN 60529 (IP20) EN 60068-2-27 (a=500 m/s ; T=6 ms)

EN 60068-2-30 (25/55 °C, RH 95%, 48 h)


* ULC 6200:2019 Certified (see the NFL File for the FW version with the Witness test if it is required by the certification of the end product)

1.8 Document history


Revision number Related sw. version Date Author
8 1.5.0 12.04.2024 ComAp
7 1.4.0 14.02.2024 ComAp
6 1.4.0 31.01.2024 ComAp
5 1.3.0 27.11.2023 ComAp
4 1.2.0 24.10.2023 ComAp
3 1.1.1.1 20.9.2023 ComAp
Adam Stocek
2 1.1.0 10.2.2023
Jakub Slavata
1 1.0.0 14.10.2022 Jakub Slavata

InteliNeo 6000 1.5.0 Global Guide 11


1.9 Symbols in this manual

Passive
Fuel
3 x Phases Coil current
solenoid
sensor
Active
Connector -
current Fuse Pick - up
female
sensor
Connector -
Fuse switch Relay coil
AirGate male

Relay coil of
Contact Generator slow-
Alternating
current operating
Generator
Contactor Renewable
Analog schematic
modem s
Controller
Grounding
simplified
Battery Resistor

Module
Battery GSM
simplified Resistor
Energy
adjustable
Storage
Current GSM
System Resistive
measuring modem
sensor
Binary
RPTC
output Current
IG-AVRi
measuring RS 232
Breaker male
contact IG-AVRi
Danger
TRANS RS 232
Breaker female
Danger -
contact Jumper
Electric
Shaft
Hazard
Generator
Breaker
DC to AC Load
Inverter Starter
Breaker
Mains Switch -
Diode
manually
Breaker operated
Ethernet Mains
male Transformer
Capacitor Mobile
Ethernet provider USB type B
female
male

InteliNeo 6000 1.5.0 Global Guide 12


USB type B
female

Voltage
measuring

Wifi / WAN /
LAN

6 back to Document
information

InteliNeo 6000 1.5.0 Global Guide 13


2 System overview
2.1 General description 14
2.2 Getting Started 15
2.3 Measurement methods 16
2.4 AC measurement 17
2.5 Communication peripherals 18
2.6 Configurability and monitoring 20
2.7 PC tools 22
2.8 Displays 23
2.9 Plug-in Modules 25
2.10 CAN Extension Modules 27
2.11 CAN Communication Modules 32
2.12 Virtual modules 32

6 back to Table of contents

2.1 General description


InteliNeo 6000 is a comprehensive Battery Energy Storage System (BESS) controller containing predefined
control loops for typical applications of microgrid systems connected in parallel to on-grid and off-grid primary
power sources.
The controller is user configurable and has expanded PLC capabilities to suit different levels of complexity to
allow for greater flexibility in meeting various customer applications. The Modbus client (master) capability allows
for modular connection of renewable energy sources such as BESS and PV to Gen-sets and Mains without
compromising power stability.
Built within the ComAp ecosystem, the InteliNeo 6000 is compatible to ComAp controllers via CAN2 line. ComAp
controllers may require firmware updates to support compatibility with the InteliNeo 6000.

2.1.1 The key features of InteliNeo 6000


Hot Swap - Controller Redundancy function
CAN Intercontroller Communication Redundancy
Up to 64 controllers on CAN
Grid Codes
MPTM and MINT can be switched without controller restart needed
Easy-to-use operation and installation
Various customizations are possible thanks to its configurability
Excellent remote communication capabilities
Support of Modbus Client (Master) allowing connection of up to 16 devices
Sunspec Modbus compatible with additional predefined Modbus Server Device list for PV & BESS
inverters
High reliability

InteliNeo 6000 1.5.0 Global Guide 14


2.2 Getting Started
Congratulations to your new InteliNeo 6000 ComAp BESS controller. Follow these steps bellow for first run of
your controller.
Note: For a better experience with our controller, do not forget to see the InteliConfig manual before starting
the configuration.

1. Connect controller to power supply


Controller requires power supply between 8-36 V DC. Plug +BAT to the terminal no. 03 and GND to
the terminal no. 01.
See Terminal Diagram (page 46) for more information
2. Connect your computer to the controller
We suggest you to use USB or ETH 1 - Trusted Interface for the first connection to your new controller.
Plug the USB/ETH cable to USB type B/Ethernet 1 terminal on the controller. Open InteliConfig and
select "Connect to controller". Now you can use "Detected controllers" feature, which should offer you
the controller.
3. Authorizing as Administrator
The alarmlist should show Wrn Default Password (page 1251). If this alarm is not present, this
procedure bellow will not work. You will need to use your changed password or Reset accounts to
factory default (page 228). If you see the warning, use function "Enter password" which is located in
tab "Control".
Username = administrator

Password = serial number of your controller


Serial number is located at the front of your controller or you can see it in left top corner of InteliConfig
when connected to the controller.
You can verify that you have been successfully logged in by seeing opened lock with number "3". This
means that you verified on the highest level - administrator and you have all possible rights.
4. Changing Administrator Password
You should change the default password as soon as possible via InteliConfig. In the InteliConfig select
tab "Tools", function "User administration" and "Change password". Do not forget to add your email
address which is used in case of lost access to the account.

5. Adding another users


If you are loged in as any account with permissions level 3, you can add another user. The whole
procedure is explained in chapter Adding account (page 230).

InteliNeo 6000 1.5.0 Global Guide 15


6. Connecting external display
For InteliVision displays wiring diagram see the chapter InteliVision Displays (page 79).
See more information about using the display in the chapter Operator Guide (page 82).

2.3 Measurement methods


The InteliNeo 6000 contains two methods for measuring physical quantities. The method of Symmetrical
components is measured all the time and the values are used whenever Grid Codes standard requires them.
In all other cases True RMS method is used.
Only values from Symmetrical components, visible to user, are +Mains/Bus Voltage (page 841) and
+Mains/Bus Voltage Relative (page 841).

2.3.1 True RMS measurement


This controller measures AC values based on True RMS principle. This principle corresponds exactly to the
physical definition of alternating voltage effective values. Under normal circumstances the Mains voltage
should have a pure sinusoidal waveform. However some nonlinear elements connected to the Mains produce
harmonic waveforms with frequencies of multiples of the basic Mains frequency and this may result in
deformation of the voltage waveforms. The True RMS measurement gives accurate readings of effective
values not only for pure sinusoidal waveforms, but also for deformed waveforms.
Note: The harmonic deformation causes that the Power Factor of a BESS working parallel with the Mains
cannot reach values in a certain range around the PF 1.00. The higher the deformation, the wider the power
factor dead range. If the requested power factor is adjusted inside the dead range, the controller cannot
reach the requested value because of this fact.

2.3.2 Symmetrical components


The method of symmetrical components simplifies analysis of unbalanced three-phase power systems under
both normal and abnormal conditions. The basic idea is that an asymmetrical set of N phasors can be
expressed as a linear combination of N symmetrical sets of phasors by means of a complex linear
transformation.In the most common case of three-phase systems, the resulting "symmetrical" components
are referred to as direct (or positive), inverse (or negative) and zero (or homopolar). The analysis of power
system is much simpler in the domain of symmetrical components, because the resulting equations are
mutually linearly independent if the circuit itself is balanced.

InteliNeo 6000 1.5.0 Global Guide 16


Note:
These images are based on:
https://upload.wikimedia.org/wikipedia/commons/e/e0/Unbalanced_symmetrical_components.pdf
Which has license: https://creativecommons.org/publicdomain/zero/1.0/deed.en

2.4 AC measurement
With InteliNeo 6000 it is possible to easily set the parameters for measuring.

2.4.1 AC measurement settings


AC Voltage measurement settings
The value of the AC voltage measured on the terminals of the controller can be adapted according to the used
meas voltage. For measuring AC voltage use setpoints BESS VT Ratio (page 381) and Bus Voltage Input
Range (page 383).

AC Current measurement settings


The value of the AC current measured on the terminals of the controller can be adapted phase application with
neutral according to the used meas current. For measuring AC current use setpoints BESS CT Ratio Prim
(page 376), BESS CT Ratio Sec (page 377), Mains/Bus CT Ratio Prim / EFC (page 377) and Mains/Bus CT
Ratio Sec / EFC (page 378).

2.4.2 Frequency measurement accuracy and resolution


The resolution of the measurement is in mHz within a 45–75 Hz range. Values Mains/Bus Frequency (page
839) and BESS Frequency (page 713) are used for visualization of measured frequency.

2.4.3 PF measurement and evaluation


Power factor of BESS and mains is measured with a resolution of 0.001.
Setpoints used for setting the Power factor regulation are Base Power Factor (page 359), Import Power
Factor (page 359) with a 0.001 resolution and #System Power Factor (page 360) with a 0.01 resolution.
Values for the Power factor are:

InteliNeo 6000 1.5.0 Global Guide 17


BESS Power Factor (page 710), BESS Load Character (page 710)
BESS Power Factor L1 (page 710), BESS Load Character L1 (page 710)
BESS Power Factor L2 (page 710), BESS Load Character L2 (page 711)
BESS Power Factor L3 (page 711), BESS Load Character L3 (page 711)
Load Power Factor (page 828), Load Character (page 828)
Mains PF (page 845), Mains Load Character (page 845)

2.4.4 Waveform distortion measurements


The controller also measures Total Harmonic Distortion (THD) for current and voltage using formulas bellow.

Voltage Total Harmonic Distortion

Where Vk is the True RMS voltage of kth harmonic.


Related values:
BESS Voltage THD L1 (page 711)
BESS Voltage THD L2 (page 712)
BESS Voltage THD L3 (page 712)

Current Total Harmonic Distortion

where Ik is the True RMS current of kth harmonic.


Related values:
BESS Current THD L1 (page 712)
BESS Current THD L2 (page 712)
BESS Current THD L3 (page 712)

2.5 Communication peripherals


InteliNeo 6000 contains 3x Ethernet terminals, 4x CAN terminals, 1x RS485 terminal and 1x USB type B
terminal. Each terminal functions are slightly different, which depends on the purpose of usage.
IMPORTANT: Use correct terminal according to your purpose of usage for correct function.

InteliNeo 6000 1.5.0 Global Guide 18


Peripherals Description Relevant links
This terminal is used for connecting of external modules and
Electronic Control Units. See the chapters Supported
combinations of modules (page 1355) and Multiple ECU (page
CAN1A 180) for more information.
Note: In case the function CAN1 ECU/IO Modules Splitting
(page 133) is used this terminal is used only for communication
with ECU.
This terminal is used for communication between Master and
CAN bus wiring
Backup Controller if the Hot Swap Redundancy (page 160)
(page 71)
function is used.
CAN1B
Note: In case the function CAN1 ECU/IO Modules Splitting
(page 133) is used this terminal is used only for communication
with external modules.
This terminal is used for CAN Intercontroller Communication
CAN2A
(page 132).
This terminal is used for CAN Intercontroller Communication
CAN2B
Redundancy (page 132).
This terminal is used for Modbus-RTU, Modbus/TCP (page 316) RS485 wiring
RS485
communication. (page 72)
Controller
This terminal is used for UART communication eg. InteliConfig, configuration
USB Type B WinScope1000, etc. It is considered as Trusted (page 226) and PC tools
terminal and the default account is used for connection. connection
(page 112)
In the default configuration port Ethernet 1 is configured as Trusted
(page 226) interface. It is used for LAN communication eg. Display,
Ethernet port 1
Ethernet 1 InteliConfig, WinScope1000, Modbus Server. The default account is
(page 403)
used for connection. Use this interface for local connection
only.
In the default configuration port Ethernet 2 is configured as
Untrusted (page 226) interface. It is used for remote
Ethernet port 2
Ethernet 2 communication eg. InteliConfig, WinScope1000, etc. The user
(page 404)
account with password has to be used in order to connect to the
controller.
In the default configuration port Ethernet 3 is configured as Modbus
(page 226) interface. It is used for Modbus Client (Master) (page Ethernet port 3
Ethernet 3
176) or Modbus server. It is not possible to use Modbus interface as (page 405)
a terminal connection (Inteliconfig, WinScope 1000, etc.).
You can see layout of the peripherals in the chapter Terminal Diagram (page 46).
Note: The controller has one common MAC address. Do not connect more than 1 Ethernet into the same
internet network.

InteliNeo 6000 1.5.0 Global Guide 19


2.6 Configurability and monitoring
One of the key features of the controller is the system’s high level of adaptability to the needs of each
individual application and wide possibilities for monitoring. This can be achieved by configuring and using the
powerful PC/mobile tools.

2.6.1 Supported configuration and monitoring tools


InteliConfig - complete configuration and single/multi controller monitoring
WebSupervisor - web-based system for monitoring and controlling
WebSupervisor mobile - supporting application for smart-phones
WinScope 1000 - special graphical monitoring software
InteliSCADA - customizable SCADA diagram for monitoring
The firmware of controller contains a large number of binary inputs and outputs needed for all necessary
functions available. However, not all functions are required at the same time on the same controller and also
the controller hardware does not have so many input and output terminals. One of the main tasks of the
configuration is mapping of “logical” firmware inputs and outputs to the “physical” hardware inputs and
outputs.

2.6.2 Configuration parts


Mapping of logical binary inputs (functions) or assigning alarms to physical binary input terminals
Mapping of logical binary outputs (functions) to physical binary output terminals
Mapping of logical analog inputs (functions) to physical analog input terminals, assigning sensor
characteristics (curves) or assigning alarms to analog inputs
Mapping of values to physical analog outputs, assigning output HW type with conversion characteristic
Selection of peripheral modules, which are connected to the controller, and doing the same (as mentioned
above) for them
Selection of ECU (electronic control unit) type
Changing the language of the controller interface

InteliNeo 6000 1.5.0 Global Guide 20


Image 2.1 Principle of inputs and outputs configuration

The controller is shipped with a Default configuration (page 118), which should be suitable for most
standard applications. This configuration can be changed only by using a PC with the InteliConfig software.
See InteliConfig documentation for details.
Once the configuration is modified, it can be saved to a file for later usage with another controller or for
backup purposes. The file is called archive and has the file extension .aig3. An archive contains a full image of
the controller at the time of saving (if the controller is online for the PC) except the firmware. Besides
configuration it also contains current adjustment of all setpoints, all measured values, a copy of the history log
and a copy of the alarm list.
The archive can be simply used for cloning controllers, i.e. preparing controllers with identical configuration
and settings.

InteliNeo 6000 1.5.0 Global Guide 21


2.7 PC tools
2.7.1 InteliConfig
PC Tool for configuration and monitoring of controllers. See more in the InteliConfig Global Guide.

This tool provides the following functions:


Direct or remote internet communication
with the controller
Offline or online controller configuration
Controller and module configuration,
programming and cloning
Remote display programming
Reading/writing/adjustment of setpoints
Reading of measured values
Controllers and ECU Alarm monitoring +
complete real time history
Exporting data into a XLS file
Controller language translation
Power format and ECU unit selection
Embedded manuals and F1 helps
Auto-hiding of unused setpoints and values

2.7.2 WebSupervisor
Cloud-based system designed for monitoring and management of ComAp and 3rd party devices via the
internet. See more in the WebSupervisor Global Guide.

This tool provides the following functions:


Site and fleet monitoring
Reading of measured values
Browsing of controller history records
On-line notification of alarms
Email notification
Also available as a smart-phone application

WebSupervisor available at: www.websupervisor.net


Demo account:
Login: comaptest
Password: ComAp123

InteliNeo 6000 1.5.0 Global Guide 22


2.7.3 WinScope 1000
Special graphical controller monitoring software used mainly for commissioning and BESS troubleshooting.
See more in the WinScope 1000 Global Guide.

This tool provides the following functions:


Monitoring and archiving of ComAp controller’s
parameters and values
View of actual/historic trends in the controller
On-line change of controller's parameters for
easy regulator setup

2.7.4 InteliSCADA
InteliSCADA is a Windows based software for monitoring of multiple controllers. See more in the InteliSCADA
Global Guide.

This tool provides the following functions:


Basic (auto-generated) SCADA in a few minutes
Broad range of instruments with easy and fast
configuration
Fully customizable SCADA diagram
Browsing of all measured and computed values
Browsing of controllers' history records

2.8 Displays
Remote Displays / Panel PC Displays

InteliNeo 6000 1.5.0 Global Guide 23


2.8.1 InteliVision 5.2
Remote colour display for ComAp controllers, designed as an easy-to-use Plug & Play display for monitoring
and control of single BESS in various applications. See more in the InteliVision 5.2 Global Guide.

This Display unit provides the following


functions:
5" colour screen with a resolution of 800 × 480
pixels
Plug & Play operation (auto configuration
based on the controller application)
Easy screen customization using Screen
Editor in InteliConfig)
5 configurable user buttons under the screen
Multi-language support
Trends monitoring screen (up to 4 channels)
Communication with controller via Ethernet
Front face protection compliant with IP65

2.8.2 InteliVision 10Touch


Panel PC Display equipped with a projective capacitive touch display. See more in the InteliVision 10Touch
Global Guide.

This Panel PC Display provides the following


functions:
10.1” touch screen with a resolution 1280 x 800
pixels
ComAp PC tools pre-installed
Direct monitoring (and control) of 3rd party
devices via Modbus (using InteliFieldbus
Gateway)
Possibility to remotely connect to the display
using for example Remote Desktop
2 Ethernet ports
Support of IP camera
Front face protection compliant with IP66

InteliNeo 6000 1.5.0 Global Guide 24


2.8.3 InteliVision 13Touch
Marine certified Panel PC Display with multi-controller support and buttons for brightness change on its front
face. See more in the InteliVision 13Touch Global Guide.

This Panel PC Display provides the following


functions:
13.3" touch screen with a resolution 1920 ×
1080 pixels
ComAp PC tools pre-installed
Multi-controller support for up to 4 controllers
Buttons for brightness change on front face
Possibility to remotely connect to the display
using for example Remote Desktop
2 Ethernet ports
Front face protection compliant with IP66

2.8.4 InteliVision 18Touch G1/G2


Panel PC Display perfectly suitable for the most complex applications and also the simple ones. With
InteliVision 18Touch you can easily monitor and control sites consisting of many controllers, or you can use it
for your CHP or Hybrid application. See more in the InteliVision 18Touch Global Guide G1 / InteliVision
18Touch Global Guide G2.

This Panel PC Display unit provides the


following functions:
18,5“ touch screen with a resolution 1366 × 768
pixels
ComAp PC tools preinstalled
Display for monitoring and control of the entire
site
History logs of all controllers
Multi-controller support for up to 32 controllers
Onscreen keyboard
Possibility to remotely connect to the display
using for example Remote Desktop
2 Ethernet ports
Front face protection compliant with IP66

2.9 Plug-in Modules


(missing or bad snippet)

InteliNeo 6000 1.5.0 Global Guide 25


2.9.1 CM2-4G-GPS
GSM/4G module
GSM/4G Internet module and GPS locator
Global 4G (LTE) module with 3G/2G backup
Remote control and monitoring of the controller
via InteliConfig, WebSupervisor
Active e-mail and SMS support
AirGate 2 technology support for easy
connection – no need of public and static IP
address
Tracking via GNSS (GPS,GLONASS) module

2.9.2 CM-4G-GPS
GSM/4G Internet module and GPS locator
Wireless integrated solution
Quick and easy installation
Support of WebSupervisor
Instant alarm SMS notification
System control over SMS
Quad Band GPRS/EDGE modem,
850/900/1800/1900 MHz, FDD LTE: Band 1,
Band 2, Band 3, Band 4, Band 5, Band 7, Band
8, Band 20, all bands with diversity,
WCDMA/HSDPA/HSUPA/HSPA+: Band 1,
Band 2, Band 5, Band 8, all bands with
diversity
GPRS multi-slot class 10
Tracking via GNSS (GPS,GLONASS) module

2.9.3 EM-BIO8-EFCP
Input and binary input/output extension module.
Up to 8 additional configurable binary inputs or
outputs

InteliNeo 6000 1.5.0 Global Guide 26


2.10 CAN Extension Modules
2.10.1 Inteli AIN8
The module allows users to expand the amount of analog inputs for sensors and add Impulse/RPM input that can
be attached to a controller. Up to 8 configurable inputs (sensors) can be attached to the module. See more
information on web page Inteli AIN8.

Supported sensors:
Resistor 3-wire input
Common resistor: 0-250Ω, 0-2400Ω, 0-10kΩ
Temperature sensor: Pt100, Pt1000, Ni100, Ni1000
Current (active or passive sensors)
±20mA , 0-20mA, 4-20mA
Voltage
±1V, 0-2,4V, 0-5V, 0-10V
Lambda probes
Thermocouples are not supported (the measuring loop was
designed for lambda probes, what caused non-support of
thermocouples)
Impulse/RPM sensor:
RPM measuring pulses with frequency 4Hz – 10kHz
Impulse
Possibility to measure pulses from electrometer, flowmeter,
etc.

IMPORTANT: Impulse input is not supported by the controller.

6 back to CAN Extension Modules

InteliNeo 6000 1.5.0 Global Guide 27


2.10.2 Inteli IO8/8
The module to expand the amount of binary inputs and outputs for ComAp controllers. It is possible to
configure the unit to have 8 binary inputs, 8 binary outputs, and 2 analog outputs, or 16 binary inputs, 0 binary
outputs and 2 analog outputs via switches inside the controller. See more information on web page Inteli
IO8/8.

Configuration 8/8
8 Binary inputs (options: pull up or pull down logic)
8 Binary outputs (options: Low side switch (LSS) or High side switch
(HSS))
2 Analog outputs (options: voltage (0-10V), current (0-20mA) and
PWM (5V, adjustable frequency 200Hz-2,4kHz))
Configuration 16/0
16 Binary inputs (options: pull up or pull down logic)
0 Binary outputs
2 Analog outputs (options: voltage (0-10V), current (0-20mA) and
PWM (5V, adjustable frequency 200Hz-2,4kHz))
6 back to CAN Extension Modules

2.10.3 IGL-RA15
Remote annunciator. See more information on web page IGL-RA15.
15 programmable LEDs with configurable
colors red-green-yellow
Lamp test function with status LED
Customizable labels
Local horn output
Maximal distance 200 m from the controller
Up to 4 units can be connected to the controller
UL certified

IMPORTANT: This module is not compatible with different than 250 kbps communication speed. If
the ECU module with 125 kbps communication speed is connected the whole system will
automatically switch to the 125 kbps, and IGL-RA15 module will stop communicating.

6 back to CAN Extension Modules

InteliNeo 6000 1.5.0 Global Guide 28


2.10.4 IGS-PTM
The module expands the amount of binary/analog inputs and outputs for ComAp controllers. It is possible to
configure the unit to have 8 binary inputs, 8 binary outputs, 4 analog inputs and 1 analog output. See more
information on web page IGS-PTM.
Configurable 8 binary and 4 analog inputs
Configurable 8 binary and 1 analog output
LEDs indicate the state of binary inputs/outputs
Measures values from Pt100 and Ni100
sensors
Analog inputs (resistance range 0-250 Ohms,
voltage range 0-100mV, current range 0-20mA
- selectable via jumper)
UL certified

6 back to CAN Extension Modules

2.10.5 Inteli AIO9/1


The module is suitable for measurement and control of analog inputs and output through CAN interface. It is
possible to configure the unit to have 9 analog inputs and 1 analog output. See more information on web page
Inteli AIO9/1.
4x differential voltage inputs for measurement in range of ±65 V
DC
4x shielded, galvanic separated sensors: thermocouples J,K,L,
±75 mV inputs
Resistance analog input (sensors: 0-2400Ω, PT1000 or NI1000)
Analog output with options : 0-20mA, 0-10V or PWMt

6 back to CAN Extension Modules

InteliNeo 6000 1.5.0 Global Guide 29


2.10.6 Inteli AIN8TC
The module allows customers to configure up to 8 analog input channels for measuring temperature by
thermocouples. The Inteli AIN8TC is useful in situations where extremely accurate temperature readings is
required. See more information on web page Inteli AIN8TC.

Supported sensors:
J, K or L thermocouples
Thermocouples with and without cold junction compensation are
supported

6 back to CAN Extension Modules

2.10.7 I-AOUT8
The module allows customers to configure up to 8 analog outputs. AGND terminals are on the same potential.
See more information on web page I-AOUT8.

Each analog output can be switched to


0 to 10 V DC
0/4 to 20 mA DC
1,2 kHz PWM (Pulse With Modulatio)

6 back to CAN Extension Modules

2.10.8 IS-AIN8
The module is equipped with 8 analog inputs. This module is compatible with MTU ECU-7 at communication
speed 125 kbps when uploaded with firmware 1.2.0 and higher. See more information on web page IS-AIN8.

InteliNeo 6000 1.5.0 Global Guide 30


Precision of inputs is 1%
2/3 wire resistive, current, voltage sensors
Predefined sensors (Pt100, Pt1000, Ni100, Ni1000, thermocouple
type J/K/L)
Current and voltage inputs 0-20mA and 0-10V

6 back to CAN Extension Modules

2.10.9 IS-AIN8TC
The module is equipped with 8 analog inputs dedicated for thermocouple sensors only. See more information
on web page Inteli AIN8TC.

J, K or L thermocouples
Thermocouples with and without cold junction compensation are
supported

6 back to CAN Extension Modules

2.10.10 IS-BIN16/8
The module allows users to expand the amount of binary inputs and outputs, and add 2 impulse inputs. It is
possible to configure the unit to have 16 binary inputs (galvanic separated) and 8 binary outputs (galvanic
separated), 2 pulse inputs (frequency measurement or pulse counting). See more information on web page
IS-BIN16/8.

To operate external modules:


Configurable 16 galvanically separated inputs
Configurable 8 outputs
2 pulse inputs (frequency measurement or pulse counting)
LEDs indicate the state of binary inputs and outputs

Note: CAN address 0 disables corresponding CAN message (Group data are not send).

InteliNeo 6000 1.5.0 Global Guide 31


IMPORTANT: Impulse inputs are not supported by the controller.

6 back to CAN Extension Modules

2.11 CAN Communication Modules


2.11.1 InteliGateway 300
IFG is communication gateway with configurable interfaces between Modbus TCP/RTU, ComAp CAN,
WebSupervisor and InteliScada protocols allowing user-defined interconnection of all attached devices. See
more information on web page InteliGateway.
Bidirectional connectivity of 3rd party Modbus devices to ComAp
controllers
Data buffering capability for avoiding loss of data during
connectivity outage
Inbuilt support of energy industry Modbus controlled devices
such as Inverters, BESS, from leading manufacturers
Support for customizable user templates for any additional
Modbus devices that are not inbuilt
Dual ethernet interfaces decoupling trusted (private) and
untrusted (public) network segments for enhanced cyber security
Terminals: 2x Ethernet, 2x RS485, 3x CAN

6 back to CAN Extension Modules

2.11.2 I-CR
If the distance between units is too high to fit into the 200 m limit (or 900 m for 8 controllers), CAN repeater
module (I-CR) can be used to extend it. See more information on web page I-CR.

Intercontroller CAN bus repeater


Supported CAN modes: CAN8C and CAN32C
CAN bus redundancy
One or more I-CR modules can be used
Intercontroller CAN bus bus-tie bridging - makes groups of controllers
in CAN segments A and B "invisible" one for another depending on
bus-tie breaker state

6 back to CAN Extension Modules

2.12 Virtual modules


Note: The protection for all virtual modules' values is working only if the User protection is set for the specific
bit of the virtual module. If the protection is set and communication with virtual module is lost, all bits with user
protection will show ####.

InteliNeo 6000 1.5.0 Global Guide 32


Note: When communication with any virtual module is lost the behavior of the value is defined according to
the setpoint Fail Safe Binary State (page 387).

2.12.1 Distributed modules


DIST-IN
DIST-IN virtual modules receives binary and analog values from other controllers via CAN Intercontroller
Communication (page 132). There are 64 modules, DIST-IN 1 to DIST-IN64, which are firmly connected with
CAN Controller Address (page 392).
IMPORTANT: This means that if you need to receive data from Controller Unit with CAN Controller
Address (page 392) = 5, you need to use module DIST-IN 5.

Proper alarm from a range DISTIN 01 (page 1325) to DISTIN 64 (page 1340) is activated in case that data are
not received from the Controller Unit.

Binary Inputs
32 binary states are paired by eight to two shared values:
Binary inputs 1 1-8 (page 942)
Binary inputs 1 9-16 (page 942)
Binary inputs 1 17-24 (page 943)
Binary inputs 1 25-32 (page 943)

Note: Values above are related to virtual module DIST-IN 1. See values for other modules here:
GROUP: DIST-IN 1-32 (PAGE 942)
GROUP: DIST-IN 33-64 (PAGE 949)

IMPORTANT: Binary inputs X 9-16 and higher can be shared only if CAN Intercontroller Comm Mode
(page 397) = 64C CAN FD or 32C CAN FD or 8C CAN FD.

Analog Inputs
Up to 4 analog values are shared:
DISTAIN-1 1 (page 944)
DISTAIN-1 2 (page 944)
DISTAIN-1 3 (page 944)
DISTAIN-1 4 (page 945)

Note: Values above are related to virtual module DIST-IN 1. See values for other modules here:
GROUP: DIST-IN 1-32 (PAGE 942)
GROUP: DIST-IN 33-64 (PAGE 949)

IMPORTANT: Analog values can be shared only if CAN Intercontroller Comm Mode (page 397) = 64C
CAN FD or 32C CAN FD or 8C CAN FD.

Note: If the CAN communication is lost, the DIST-IN analog inputs become invalid and the values are shown as
'####'.

Configuration
Configuration of the virtual module itself, binary and analog outputs is done via InteliConfig. As with other
modules, you can choose whether history columns and display screens are added as well as select type of

InteliNeo 6000 1.5.0 Global Guide 33


protection upon module failure.

Image 2.2 Configuration of virtual module DIST-IN

DIST-OUT
This virtual module shares binary and analog values to other controller units via CAN Intercontroller
Communication (page 132).
In case that there is detected module failure, alarm DISTOUT (page 1341) is activated. The CAN connection is
lost with another CU or this module is not configured.

Binary Outputs
32 binary states are paired by eight to four shared values:
Binary outputs 1-8 (page 964)
Binary outputs 9-16 (page 964)
Binary outputs 17-24 (page 965)
Binary outputs 25-32 (page 965)

IMPORTANT: Binary outputs 9-16 and higher can be shared only if CAN Intercontroller Comm Mode
(page 397) = 64C CAN FD or 32C CAN FD or 8C CAN FD.

Analog Outputs
Up to 4 analog values can be shared.
IMPORTANT: Analog values can be shared only if CAN Intercontroller Comm Mode (page 397) = 64C
CAN FD or 32C CAN FD or 8C CAN FD.

Configuration
Configuration of the virtual module itself, binary and analog outputs is done via InteliConfig. As with other
modules, you can choose whether history columns and display screens are added as well as select type of
protection upon module failure.

InteliNeo 6000 1.5.0 Global Guide 34


Image 2.3 Configuration of virtual module DIST-OUT

2.12.2 Shared modules


Shared modules are not connected with CAN Controller Address (page 392), which means that you need to
pay close attention during configuration so that you do not create collision. Each SHBOUT and SHAOUT module
index can be used only once in CAN topology.

Binary shared modules


SHBIN
SHBIN virtual modules receives binary values from other controllers via CAN Intercontroller Communication
(page 132). There are 6 modules, SHBIN-1 to SHBIN-6, which are firmly connected with SHBOUT-1 to
SHBOUT-6.
IMPORTANT: This means that you need to use module SHBIN-1 if you wish to receive data from
SHBOUT-1.

An alarm Wrn SHBIN Collision (page 1349)- is activated in case that more than just one controller has
configured SHBOUT module with same module index in CAN topology.
IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.

Proper alarm from a range SHBIN 1 (page 1347) to SHBIN 6 (page 1349) is activated in case that data are not
received.

Binary Inputs
SHBIN-1 (page 956)

Note: Value above is related to virtual module SHBIN-1. See values for other modules here: Group: SH
Modules (page 956)

InteliNeo 6000 1.5.0 Global Guide 35


Configuration

Image 2.4 Configuration of shared module SHBIN

SHBOUT
SHBOUT virtual modules share binary values to other controllers via CAN Intercontroller Communication
(page 132). There are 6 modules, SHBOUT-1 to SHBOUT-6, which are firmly connected with SHBIN-1 to
SHBIN-6.
IMPORTANT: This means that you need to use module SHBOUT-1 if you wish to send data to SHBIN-
1.

IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.

Binary Outputs
SHBOUT-1 (page 959)

Note: Value above is related to virtual module SHBIN-1. See values for other modules here: Group: SH
Modules (page 956)

InteliNeo 6000 1.5.0 Global Guide 36


Configuration

Image 2.5 Configuration of shared module SHBOUT

Analog shared modules


SHAIN
SHAIN virtual modules receives analog values from other controllers via CAN Intercontroller Communication
(page 132). There are 2 modules, SHAIN-1 and SHAIN-2, which are firmly connected with SHAOUT-1 and
SHAOUT-2.
IMPORTANT: This means that you need to use module SHAIN-1 if you wish to receive data from
SHAOUT-1.

An alarm Wrn SHAIN Collision (page 1347) is activated in case that more than just one controller has
configured SHAOUT module with same module index in CAN topology.
IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.

Proper alarm from a range SHAIN 1 (page 1347) to SHAIN 2 (page 1347) is activated in case that data are not
received.

Analog Inputs
SHAIN-1 1 (page 962)
SHAIN-1 2 (page 962)
SHAIN-1 3 (page 962)
SHAIN-1 4 (page 962)

Note: Value above is related to virtual module SHAIN-1. See values for other modules here: Group: SH
Modules (page 956)

InteliNeo 6000 1.5.0 Global Guide 37


Configuration

Image 2.6 Configuration of shared module SHAIN

SHAOUT
SHAOUT virtual modules share analog values to other controllers via CAN Intercontroller Communication
(page 132). There are 2 modules, SHAOUT-1 and SHAOUT-2, whicha re firmly connected with SHAIN-1 and
SHAIN-2.
IMPORTANT: This means that you need to use module SHAOUT-1 if you wish to send data to SHAIN-
1.

IMPORTANT: Shared modules work only if CAN Intercontroller Comm Mode (page 397) = 8C, 16C or
32C.

InteliNeo 6000 1.5.0 Global Guide 38


Configuration

Image 2.7 Configuration of shared module SHAOUT

6 back to System overview

InteliNeo 6000 1.5.0 Global Guide 39


3 Applications overview
3.1 MPTM 41
3.2 MINT 42

6 back to Table of contents

InteliNeo 6000 1.5.0 Global Guide 40


3.1 MPTM
The typical scheme of a Microgrid Parallel To Mains application is shown below. The InteliNeo6000 controller
controls up to three breakers – a mains breaker, battery energy storage system breaker and a photovoltaic
(renewable source) breaker. Feedback from all breakers is required.
Note: The Application & System Variability (page 237) allows user to configure the system in following
variants: BESS only, PV (renewables) only, or BESS + PV (renewables).

IMPORTANT: In the MPTM scheme dashed line at BCB breaker is for AC precharge and full line is
for DC precharge.

Image 3.1 Microgrid Parallel To Mains application

InteliNeo 6000 1.5.0 Global Guide 41


3.2 MINT
The typical scheme of Multiple Island-Parallel application for on grid is shown below. The cooperation of
Microgrid, Gen-set, and Mains controllers can be seen in the picture below. The InteliNeo6000 controller
controls up to two breakers, the battery energy storage system breaker and photovoltaic (renewable source)
breaker. Feedback from the both breakers is required.
Note: The Application & System Variability (page 237) allows user to configure whether the microgrid
contains BESS, PV (renewables), Gen-sets or Mains.

IMPORTANT: The InteliNeo6000 can work together with multiple Gen-set and Mains controllers,
but it cannot work with any other Microgrid/BESS controller. Only one InteliNeo6000 per site is
supported.

IMPORTANT: In the MINT scheme dashed line at BCB breaker is for AC precharge and full line is
for DC precharge.

Image 3.2 Multiple island-parallel application with mains

6 back to Applications overview

InteliNeo 6000 1.5.0 Global Guide 42


4 Installation and wiring
4.1 Package content 43
4.2 Controller installation 44
4.3 Terminal Diagram 46
4.4 Recommended wiring 48
4.5 External display 79
4.6 Maintenance 81

6 back to Table of contents

4.1 Package content


The package contains:
Controller InteliNeo6000
Terminal blocks

Note: The package does not contain a communication or extension modules. The required modules should be
ordered separately.

InteliNeo 6000 1.5.0 Global Guide 43


4.2 Controller installation
4.2.1 Dimensions

Image 4.1 Controller dimensions

Note: Dimensions are in millimeters.

Note: The controller is mounted into panel doors as a standalone unit using provided holders. The requested
cutout size is 187 × 132 mm. Use the screw holders delivered with the controller to fix the controller into the
door.

4.2.2 Mounting
The controller unit should be mounted onto the backside of the switchboard door and after the installation it
should be inaccessible for nonauthorized people. There are two ways how to mount the CU.

InteliNeo 6000 1.5.0 Global Guide 44


Mounting on DIN rail
Mount the controller on the DIN rail as described on the picture below.

Image 4.2 Controller mounting on DIN rail

Mounting in switchboard doors


The upper part of the back side of the controller cover is not same as the lower part, the spacers have to be
placed between switchboard doors and the controller cover. Use the 10 mm spacers for the upper part of the
CU cover and the 5 mm spacers for the lower part of the CU cover. Use the screws and spacers to fix the
controller into the door as described on the picture below.

Image 4.3 Controller mounting in the switchboard doors

InteliNeo 6000 1.5.0 Global Guide 45


4.3 Terminal Diagram
46 N 65 BI1 89 H
① 47 L1 66 BI2
⑧ 88 COM
BESS CAN2A
48 L2 67 BI3 87 L
VOLTAGE
49 L3 68 BI4 86 H
50 N 69 BI5
⑨ 85 COM
② 51 L1 ⑥ 70 BI6
CAN1B
84 L
MAINS/BUS BINARY
52 L2 71 BI7 83 H
VOLTAGE
53 L3
INPUTS
72 BI8
⑩ 82 COM
CAN1A
58 AO1 COM 73 BI9 81 L
③④ 59 AO1 OUT 74 BI10 E1 Ethernet 1
ANALOG
60 AO2 COM 75 BI11
⑪⑫⑬ E2 Ethernet 2
OUTPUTS ETHERNET
61 AO2 OUT 76 BI12 E3 Ethernet 3
92 H
⑤ SD SD Card
⑦ 91 COM
⑭ U1 USB
SD Card CAN2B USB
90 L

InteliNeo 6000 1.5.0 Global Guide 46


93 B 31 AI4 16 BO12
⑮ RS 485 94 COM ⑱ 30 AI3 15 BO11
95 A ANALOG 29 AI2 14 BO10
45 L1k INPUTS 28 AI1 13 BO9
44 L1l 27 ACOM 12 BO8
⑯ 43 L2k 11 BO7
⑲ 26
+5V
㉒ BINARY
BESS
42 L2l +5V SENSOR SENSOR 10 BO6
CURRENT OUTPUTS
41 L3k ⑳ 09 BO5
40 L3l GROUNDING 00 GROUND 08 BO4
07 BO3
39 LAk
03 + 06 BO2
⑰ AUX
02 D+ 05 BO1
CURRENT ㉑ POWER
38 LAl E-
SUPPLY, D+ 01 - ㉓ E-STOP 04
STOP

InteliNeo 6000 1.5.0 Global Guide 47


4.4 Recommended wiring
4.4.1 General 50
4.4.2 Grounding 50
4.4.3 Power supply 51
4.4.4 Measurement wiring 52
4.4.5 Binary Inputs 64
4.4.6 Binary Outputs 65
4.4.7 E-Stop 66
4.4.8 Analog Inputs 67
4.4.9 Analog Outputs 70
4.4.10 CAN bus and RS485 wiring 71
4.4.11 USB 74
4.4.12 Ethernet 75
4.4.13 Cellular Connection 76

max 600 V
BESS voltage inputs Voltage measurement wiring (page 56)
AC Ph-Ph
max 600 V
Mains/Bus voltage inputs Voltage measurement wiring (page 56)
AC Ph-Ph
max ± 10 V
Analog Output Analog Outputs (page 70)
DC
max ± 10 V
Analog Output Analog Outputs (page 70)
DC

InteliNeo 6000 1.5.0 Global Guide 48


SD card slot

max 36 V
Binary inputs Binary Inputs (page 64)
DC

CAN2B H, COM, L CAN bus and RS485 wiring (page 71)

CAN2A H, COM, L CAN bus and RS485 wiring (page 71)

CAN1B H, COM, L CAN bus and RS485 wiring (page 71)

CAN1A H, COM, L CAN bus and RS485 wiring (page 71)

Ethernet 1 ETH 1 Ethernet (page 75)

Ethernet 2 ETH 2 Ethernet (page 75)

Ethernet 3 ETH 3 Ethernet (page 75)

USB USB (page 74)

RS485 A, COM, B CAN bus and RS485 wiring (page 71)

BESS current max 5 A AC Current measurement wiring (page 52)

Aux current max 5 A AC Current measurement wiring (page 52)

max 10 V
Analog inputs Analog Inputs (page 67)
DC
5 V DC
Sensor power supply max 100
mA
+, N/A, -
Power supply 8 - 36 V DC Power supply (page 51)
max 7,5 A
Improves resistance to electrical interference if
Grounding
connected to the ground.
max 36 V;
Binary outputs Binary Outputs (page 65)
0,5 A

E-stop max 1 A E-Stop (page 66)

InteliNeo 6000 1.5.0 Global Guide 49


4.4.1 General
To ensure proper function:
Use grounding terminals.
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when the length is more than 3 m.

Tightening torque and allowable wire size and type for the Field-Wiring Terminals:
For BESS Voltage and Mains Voltage terminals

Specified tightening torque is 0.5 Nm (4.425 In-lbs).

Use only diameter 2.0 - 0.5 mm (12 - 26 AWG) copper


conductor rated for 90 °C minimum.

For Current terminals

Specified tightening torque is 0.5 Nm (4.425 In-lbs).

Use only diameter 2.0 - 0.5 mm (12 - 26 AWG) copper


conductor rated for 90 °C minimum.

For other controller field wiring terminals

Specified tightening torque is 0.5 Nm (4.425 In-lbs).

Use only diameter 2.0 - 0.5 mm (12 - 26 AWG) copper


conductor rated for 75 °C minimum.

4.4.2 Grounding
2
The shortest possible length of wire should be used for controller grounding. Use cable min 2.5 mm .
The negative " - " battery terminal used as power supply for CU must be properly grounded.
Switchboard must be grounded at common point. Use as short cable as possible to the grounding point.

InteliNeo 6000 1.5.0 Global Guide 50


4.4.3 Power supply
To ensure proper function:
Use power supply cable min. 1.5 mm2
Maximum continuous DC power supply voltage is 36 V DC
Minimum continuous DC power supply voltage is 8 V DC
It is strongly recommended to use 8 A fusing (12xBOUT 0.5 A)
The controller’s power supply terminals are protected against large pulse power disturbances. When there is a
potential risk of the controller being subjected to conditions outside its capabilities, an outside protection device
should be used.
Note: The controller should be grounded properly in order to protect against lighting strikes. The maximum
allowable current through the controller’s negative terminal is 4 A (without consumption of the binary outputs).

The controller includes internal capacitors that allows the controller to continue in operation if the voltage dip
occurs. The capacitors are useful mainly during short cranking voltage dips for the connections with 12 V battery
power supply. If the voltage dip goes during cranking to 0 V and after 50 ms it recovers to 8 V, the controller
continues operating. When this situation occurs the binary outputs are temporarily switched off and after
recovering to 8 V back on. This cycle can be repeated several times.
Note: It is also possible to further support the controller by connecting the external capacitor and separating
diode. The capacitor size depends on required time. It shall be approximately thousands of μF. The capacitor
size should be 5 000 μF to withstand 150 ms voltage dip under following conditions: Voltage before dip is 12 V,
after 150 ms the voltage recovers to min. allowed voltage, i.e. 8 V.

Image 4.4 Controllers power supply with external capacitor, separating diode and fusing

InteliNeo 6000 1.5.0 Global Guide 51


IMPORTANT: It is strongly recommended to use fusing in-line with the battery positive terminal to
the controller and modules.

Note: Suitable conductor protection shall be provided in accordance with NFPA 70, Article 240.

Power supply fusing


It is strongly recommended to use 4 A fuse in-line with the battery positive terminal to the controller and modules.
These electronics should never be connected directly to the starting battery. Fuse value and type depends on
number of connected devices and wire length. It is recommended to use slow blow fuse T4 A. The fast blow fuse
is inappropriate due to internal capacitors charging during power up.

Image 4.5 Controllers power supply fusing

IMPORTANT: 8 A fuse is calculated without BOUT consumption nor extension modules. Real value
of fuse depends on consumption of binary outputs and modules.

Example: Maximal consumption of binary outputs can be 22 A


2 x 10 A on high current outputs (for 10 seconds)
2 A on all others binary outputs

4.4.4 Measurement wiring


2 2
Use 1.5 mm cables for voltage connection and 2.5 mm for current transformers connection. Adjust Connection
type (page 378), Mains/Bus Nominal Voltage Ph-N (page 381), Mains/Bus Nominal Voltage Ph-Ph (page
381), BESS Nominal Voltage Ph-N (page 380), BESS Nominal Voltage Ph-Ph (page 380) and Nominal
Current (page 376) by appropriate setpoints in the Basic Settings group.

IMPORTANT: Risk of personal injury due to electric shock when manipulating voltage
terminals under voltage. Be sure the terminals are not under voltage before touching
them.
Do not open the secondary circuit of current transformers when the primary circuit is
closed. Open the primary circuit first.

Current measurement wiring


The number of CT's is automatically selected based on selected value of setpoint Connection type (page 378).
Current and power measurement is suppressed if current level is bellow 1 % of CT range.
The auxiliary current measurement (T38, T39) is used for the Mains/Bus measurement.

InteliNeo 6000 1.5.0 Global Guide 52


ConnectionType: 3Ph4Wire / High Leg D / 3Ph3Wire
Connection type (page 378) = 3Ph4Wire / High Leg D / 3Ph3Wire

Image 4.6 BESS current measurement Image 4.7 AUX Mains/Bus current measurement
wiring wiring

ConnectionType: SplitPhase
Connection type (page 378) = SplitPhase

Image 4.8 BESS current measurement Image 4.9 AUX Mains/Bus current measurement
wiring wiring

InteliNeo 6000 1.5.0 Global Guide 53


ConnectionType: MonoPhase
Connection type (page 378) = MonoPhase

Image 4.10 BESS current measurement Image 4.11 AUX Mains/Bus current measurement
wiring wiring

Principle of two transformers measuring for 3 phase connections

Image 4.12 Principle of two current transformers measuring


IMPORTANT: Check measurement connections carefully! Failure is possible if phases are
connected in wrong order (WrongPh Sequence detected by the controller) but this is not
detected if the phases are just rotated (i.e. instead of phase sequence L1, L2, L3, phase
sequence is e.g. L2, L3, L1.

EFC measurement wiring


The auxiliary current measurement (T38, T39) is used for the Earth Fault Current measurement.

InteliNeo 6000 1.5.0 Global Guide 54


Simple earth fault current measurement wiring
The simple earth fault current arrangement covers all zones from the BESS inverter to the final circuits in the load
network.

Image 4.13 AUX Simple EFC measurement wiring

EFC measurement wiring for load network only


This arrangement covers earth faults in the load network only.

Image 4.14 AUX EFC measurement wiring for load network only

InteliNeo 6000 1.5.0 Global Guide 55


EFC measurement wiring for restricted earth protection
This arrangement is necessary for restricted earth fault protection. The location of the neutral earthing point in
relation to the protection current transformers in the neutral conductor determines whether four or five current
transformers are employed.

Image 4.15 AUX EFC measurement wiring for restricted earth protection

Voltage measurement wiring


The BESS and Bus protections are evaluated from different voltages based on Connection type (page 378)
setting:
3Ph4Wire – Ph-Ph voltage, Ph-N voltage
High Leg D – Ph-N voltage, Ph-N voltage
3Ph3Wire – Ph-Ph voltage
SplitPhase – Ph-N voltage, Ph-N voltage
MonoPhase – Ph-N voltage

InteliNeo 6000 1.5.0 Global Guide 56


ConnectionType: 3 Phase 4 Wires
Connection type (page 378) = 3Ph4Wire

Image 4.16 Controller wiring for voltage measurement of 3 phase application with neutral

Note: Fuse on "N" wire is not obligatory but recommended.

Image 4.17 Typical BESS wiring of 3 phase application with neutral

Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.

InteliNeo 6000 1.5.0 Global Guide 57


ConnectionType: High Leg D
Connection type (page 378) = High Leg D

Image 4.18 Controller wiring for voltage measurement of High Leg Delta application

Note: Fuse on "N" wire is not obligatory but recommended.

Table 4.1 Typical BESS wiring of High Leg Delta application

Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.

InteliNeo 6000 1.5.0 Global Guide 58


ConnectionType: 3 Phase 3 Wires
Connection type (page 378) = 3Ph3Wire

Image 4.19 3 Controller wiring for voltage measurement of 3 phase application without neutral

Image 4.20 Typical BESS wiring of 3 phase application without neutral

Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.

InteliNeo 6000 1.5.0 Global Guide 59


ConnectionType: SplitPhase
Connection type (page 378) = SplitPhase

Image 4.21 Controller wiring for voltage measurement of SplitPhase application

Note: Fuse on "N" wire is not obligatory but recommended.

InteliNeo 6000 1.5.0 Global Guide 60


Image 4.22 Typical BESS wiring of SplitPhase application

Note: Terminals marked by Tx in the pictures above are BESS's terminals. These markers are not the same
as markers for the controller wiring.

InteliNeo 6000 1.5.0 Global Guide 61


ConnectionType: Mono Phase
Connection type (page 378) = MonoPhase

Image 4.23 Controller wiring for voltage measurement of MonoPhase application

Note: Fuse on "N" wire is not obligatory but recommended.

InteliNeo 6000 1.5.0 Global Guide 62


Image 4.24 Typical BESS wiring of MonoPhase application

Note: Terminals marked by Tx in the picture above are BESS's terminals. These markers are not the same
as markers for the controller wiring.

Principle of two transformers measuring for 3 phase connections

Image 4.25 Principle of two voltage transformers measuring

InteliNeo 6000 1.5.0 Global Guide 63


4.4.5 Binary Inputs
InteliNeo 6000 offers switchable types of inputs. You can select from Pull Up and Pull Down settings. Use
2
minimally 1 mm cables for wiring of Binary inputs. It is recommended to separate inputs by diodes when two or
more binary inputs are connected in parallel to avoid wrong input activation when one controller is switched off.
See the chapter Binary inputs (page 1357) for more information about Pull Up and Pull Down settings.
Note: The name and function or alarm type for each binary input have to be assigned during the
configuration.

Image 4.26 Wiring binary inputs - Pull Up Image 4.27 Wiring binary inputs - Pull Down

InteliNeo 6000 1.5.0 Global Guide 64


Image 4.28 Separation of connected binary inputs by diodes (pull up)

Image 4.29 Separation of connected binary inputs by diodes (pull down)

4.4.6 Binary Outputs


2
Use min. 1 mm cables for wiring of binary outputs. Use external relays as indicated on the schematic below for
all outputs except those where low-current loads are connected (LED signalization etc.). There are two Binary
Output groups, the first one is powered by E-STOP (BO1 and BO2) and second one is powered by the controllers
main power supply connector (BO3 .. BO12). Every group of outputs can provide steady current of up to 2 A.
Every single binary output can provide up to 0.5 A of steady current unless the total current of the group of
outputs does not exceed 2 A.
IMPORTANT: Use suppression diodes on all relays and other inductive loads even if they are not
connected directly to the controller Binary Outputs.

InteliNeo 6000 1.5.0 Global Guide 65


Image 4.30 Binary outputs wiring

4.4.7 E-Stop
The E-Stop is commonly used for quick emergency stop of the BESS. It has dedicated terminal T04 which
should be wired trough the Emergency Stop button to the battery voltage. The E-Stop is also used as power
supply for binary output 1 (T05) and binary output 2 (T06). . So, these binary outputs will not work if the E-Stop
is not powered up, that means higher security and faster disconnection of these outputs. For more information
about E-Stop functions see chapter E-STOP (page 143).

Image 4.31 E-Stop wiring

Note: Recommended fusing is 1 A fuse.

Note: Grey dashed line symbolizes internal connection between E-Stop and binary outputs 1 and 2.

Note: For proper functionality of E-Stop, the terminal T04 must be always wired. Terminal can be connected
to battery+ or to terminal T03 (BATT+)

IMPORTANT: Use suppression diodes on all relays and other inductive loads even if they are not
connected directly to the controller Binary Outputs.

InteliNeo 6000 1.5.0 Global Guide 66


4.4.8 Analog Inputs
On each analog input there is possibility to connect a voltage, current, or resistive sensor.

Resistive sensors
The analog inputs for resistive automotive type sensors like VDO or DATCON are connected either by one wire
(the second pole is the sensor body) or by two wires.
In the case of grounded sensors, connect the ACOM terminal to the ground as near to the sensors as
possible.
In the case of isolated sensors, connect the ACOM terminal to the negative power supply terminal of the
controller as well as one pole of each sensor.

Image 4.32 Grounded sensors Image 4.33 Isolated sensors

Note: Schemes show only analog input connection overview, not actual wiring.

Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.

Voltage sensors
Recommended wiring for the voltage measurement with voltage divider. The voltage sensor is displayed as
voltage source which is usually powered from battery or any external DC power source. The ACOM terminal is
connected to the negative power supply terminal of the controller as well as negative pole of each sensor.

InteliNeo 6000 1.5.0 Global Guide 67


Image 4.34 Wiring of analog input with voltage sensor

Note: The voltage divider is only relevant for sensors which are outside the 0-10 VDC range.

Current sensors
Recommended wiring connections for the active and passive current sensors. The active sensor is displayed as
current source which is usually powered from battery or any external DC power source. The passive sensor is
displayed as resistive load which is placed between battery + and AIN. The passive sensor does not require
additional power supply.

Image 4.35 Wiring of analog input with active Image 4.36 Wiring of analog input with passive
current sensor current sensor

InteliNeo 6000 1.5.0 Global Guide 68


Analog as binary or tristate inputs
Analog inputs can be used also as binary or tri-state, i.e. for contact sensors without or with circuit check. The
threshold level is 750 Ω. In the case of tri-state, values lower than 10 Ω and values over 2500 Ω are evaluated as
sensor failure (short or open circuit), values over 750 Ω are evaluated as log 0 and values below 750 Ω are
evaluated as log 1. This can be used for example to prevent running the engine with failed temperature sensor,
so it wont be overheated.

Image 4.37 Analog inputs as tristate Image 4.38 Analog inputs as binary

Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.

Curve of tristate sensor is prepared for resistive analog inputs 0 .. 2500 Ω.


Tristate sensor has 3 states:
Fls – fail of sensor
1 – value is in logical 1
0 – value is in logical 0
Curve of sensor:
< 10 Ω – fail of sensor
10 .. 750 Ω – logical 1
750 .. 2500 Ω – logical 0
> 2500 – fail of sensor

InteliNeo 6000 1.5.0 Global Guide 69


4.4.9 Analog Outputs

Image 4.39 Analog outputs - Wiring

Analog outputs can be used for any purpose and their outputs can be switched according to options below.
Note: The jumper switch next to the terminal 61 is a short switch of 10k serial resistor at analog output 2. By
default, the jumper is switched off (the resistor is included in the circuit).

Voltage
Output range: -10 to +10 V
Maximum load: 5 mA
Output accuracy: 1 % from set value ±100 mV (measured at load 10 kΩ)
Minimum step: 1/10000 of full range (approx. 14bit resolution)
Step response: 10 ms max. (measured between 10 and 90 %)
Output ripple: 30 mV max. (measured at 50% duty cycle at 3000 Hz PWM)
Current
Output range -20 to +20 mA
Maximum load: 500 Ω
Output accuracy: 1 % from set value ±200 µA
Minimum step: 1/10000 of full range (approx. 14bit resolution)
Step response: 10 ms max. (measured between 10 and 90 %)
Output ripple: 60 µA max. (measured at 50% duty cycle at 3000 Hz PWM)
PWM
Output voltage levels: 0 V / 5 V
Maximum load: 10 mA
Output High level: >4 V @ 10 mA
Output Low level: <1 V @ 10 mA
Minimum step: 1/10000 of full range (approx. 14bit resolution)
Frequency range: 500 to 3000 Hz (settable during configuration)

InteliNeo 6000 1.5.0 Global Guide 70


4.4.10 CAN bus and RS485 wiring
CAN bus wiring
The wiring of the CAN bus should be provided in such a way that the following rules are observed:
The maximum length of the CAN bus depends on the communication speed. For a speed of 250 kbps,
which is used on the CAN1A (page 19) bus (extension modules, ECU) and CAN2A (page 19) (CAN2B
(page 19)) bus, the maximum length is 200 m.
The bus must be wired in linear form with termination resistors at both ends. No nodes are allowed except
on the controller terminals.
Shielded cable1 has to be used, shielding has to be connected to the terminal T01 (Grounding).
External units can be connected on the CAN bus line in any order, but keeping line arrangement (no tails,
no star) is necessary.
The CAN bus has to be terminated by 120 Ohm resistors at both ends use a cable with following
parameters:

Cable type Shielded twisted pair


Impedance 120 Ω
Propagation velocity ≥ 75% (delay ≤ 4.4 ns/m)
2
Wire crosscut ≥ 0.25 mm
Attenuation (@1MHz) ≤ 2 dB/100 m

Note: Communication circuits shall be connected to communication circuits of Listed equipment.

Note: A termination resistor at the CAN (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the appropriate CAN terminal.

Image 4.40 CAN bus topology

1Recommended data cables: BELDEN (http://www.belden.com) - for shorter distances: 3105A Paired - EIA
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)

InteliNeo 6000 1.5.0 Global Guide 71


Image 4.41 CAN bus wiring for shorter distances

Note: Shielding shall be grounded at one end only. Shielding shall not be connected to CAN COM terminal.

Note: In case of surge hazard (long distances, connection out of building, storms, etc.), consider using surge
protection1.

RS485 wiring
The wiring of the RS485 communication should be provided in such a way that the following rules are observed:
Note: A termination resistor at the RS485 (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the RS485 terminal.

Standard maximum bus length is 1000 m.


Shielded cable2 has to be used, shielding has to be connected to the terminal T00 (Grounding).
External units can be connected on the RS485 line in any order, but keeping line arrangement (no tails, no
star) is necessary.
The line has to be terminated by 120 Ohm resistors at both ends.
For shorter distances (connection within one building).

Image 4.42 RS485 wiring for shorter distances

1Protections recommended: Phoenix Contact (http://www.phoenixcontact.com): PT 5-HF-12DC-ST with PT2x2-


BE (base element) or Saltek (http://www.saltek.cz): DM-012/2 R DJ
2Recommended data cables: BELDEN (http://www.belden.com) - for shorter distances: 3105A Paired - EIA
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)

InteliNeo 6000 1.5.0 Global Guide 72


For longer distances or in case of surge hazard (connection out of building, in case of storm etc.)

Image 4.43 RS485 wiring for longer distances

① Recommended PT5HF-5DC-ST1
Note: Communication circuits shall be connected to communication circuits of Listed equipment.

1Recommended protections: Phoenix Contact (http://www.phoenixcontact.com): PT 5-HF-5DC-ST with PT2x2-


BE (base element)(or MT-RS485-TTL) or Saltek (http://www.saltek.cz): DM-006/2 R DJ

InteliNeo 6000 1.5.0 Global Guide 73


On board RS485 description

Balancing resistors
The transmission bus into the RS-485 port enters an indeterminate state when it is not being transmitted to. This
indeterminate state can cause the receivers to receive invalid data bits from the noise picked up on the cable. To
prevent these data bits, you should force the transmission line into a known state. By installing two 560 Ohm
balancing resistors at one node on the transmission line, you can create a voltage divider that forces the voltage
between the differential pair to be less than 200 mili-Volts, the threshold for the receiver. You should install these
resistors on only one node. The figure below shows a transmission line using bias resistors. Balancing resistors
are placed directly on the PCB of controller. Use jumpers PULL UP/PULL DOWN to connect the balancing
resistors.

Image 4.44 Balancing resistors

Image 4.45 RS485 on board

4.4.11 USB
The USB can be used for direct computer connection. Use the shielded USB A-B cable. See the chapter
Connection via USB (page 311) for more information.

Image 4.46 USB connection

The USB cannot be used instead of power supply. The controller will not be turned on when the USB is
connected and the controller is not powered from power supply.

InteliNeo 6000 1.5.0 Global Guide 74


4.4.12 Ethernet
Ethernet Cat5/Cat6 cable fitted with the RJ45 connector can be connected to the ethernet interface. The
ethernet can be used for direct computer connection. See the chapter Connection via Ethernet (page 312)
for more information.

Image 4.47 Ethernet Connection

IMPORTANT: The InteliNeo6000 is using same MAC address for all Ethernet ports so it is not
possible to use more than one Ethernet port in the same network. If you connect for example
Ethernet 1 and 2 to the same network the communication will breakdown.

In the image below you can see the topology using all 3 Ethernet ports with one Modbus Client. The ETH1 is
used for connection of displays (IV5.2) or it can be also used for remote LAN connection. The ETH2 is used
for remote connection using the internet (WAN). The ETH3 is used for Modbus Server and Client which are
connected to the LAN with Modbus Devices.

Image 4.48 Advanced Ethernet Topology With One Modbus Client

InteliNeo 6000 1.5.0 Global Guide 75


In the image below you can see the topology using all 3 Ethernet ports with multiple Modbus Clients (CU 1 is
the first level client, CU 2 and CU 3 are second level clients). The ETH1 is used for Modbus Server,
connection of displays (IV5.2), or it can be also used for remote LAN connection. The ETH2 is used for
remote connection using the internet (WAN). The ETH3 is used for Modbus Clients which are connected
between CU 1 and other CUs, and between other CUs and Modbus Devices.

Image 4.49 Advanced Ethernet Topology With Multiple Modbus Clients

Note: The IP address of each device in the same network must vary.

Note: InteliVision 5.2 is used for illustrative purposes, the same wiring diagrams apply for all supported displays
mentioned in Displays (page 23).

4.4.13 Cellular Connection


Cellular connection of controllers can be created by using a router, which is a device that represents the
gateway between the controllers and the Internet.
It creates a Local Area Network (LAN) in which the controllers are connected
On the opposite side it is connected to Internet (Wide Area Network, WAN)

InteliNeo 6000 1.5.0 Global Guide 76


Image 4.50 Example of a topology

Note: The picture above is only an example of the topology. An additional switch/switches may be needed to
match the required network topology (i.e. number and location of the LAN connection points). Please consult
this topic with ethernet network specialist.

While selecting a suitable cellular router following aspects should be considered:


What cellular network technology and frequency bands are available in the target region?
Is the cellular connection the primary Internet connection or just a backup connection while the primary
one is wired ethernet?
Power supply and operating conditions

Note: We recommend to only use devices designed for industrial applications.

InteliNeo 6000 1.5.0 Global Guide 77


Cellular network technology
There are multiple cellular technologies available on the market. They are called either as "generations" (G)
or abbreviations are used.

Technology Description
Current, most advanced, technology. It is being deployed rapidly in some
areas it may replace the legacy 2G networks. We recommend using this
4G (LTE) technology if it is available in the target area
Provides highest data throughput rate and lowest latency
Best user experience – like a wired connection
Successor of 2G. It is in operation in some areas, but it is not expanding
anymore.
3G (UMTS, HSPA, CDMA)
Provides lower throughput rate and higher latency then 4G*
Still quite good user experience
Very first digital cellular network technology. It is still available in many
areas, however it is slowly starting to decline.
2G (GSM, GPRS, EDGE) Provides lowest throughput rate and quite high latency
Generally not suitable for connection of multiple ComAp devices
via a router

Frequency bands
It is very important that selected cellular router matches the frequency bands used by providers in the target
country or area. 4G networks worldwide use many of frequency bands and manufacturers of cellular modules
and routers sell their devices in multiple variants according to the region. A useful overview of LTE frequency
bands is available at Wikipedia page.
Note: Consult the technical documentation and/or technical support of the router's manufacturer to get more
information about ordering proper regional version of your selected router.

Additional router functions


Backup WAN connection
Router may provides secondary SIM card slot which is used as a backup connection when the main
connection is lost. You can also combine cellular and wired Internet connection as the main and backup one.

Connection alive check


Router may periodically checks whether the cellular connection is alive - has access to the Internet. When
there is not access to the Internet, router may perform automatic reboot to reinitialize the connection or switch
to backup SIM card.

Automatic scheduled reboot


Router may perform periodically scheduled reboot. This function is a bit "harder" alternative to the
Connection alive check (page 78).
Note: It may be very helpful at remote sites where freezing of the connection would require traveling to the
site.

InteliNeo 6000 1.5.0 Global Guide 78


Typical router configuration
Note: Please always refer to the documentation of the specific router for detailed setup procedure.

IMPORTANT: When configuring a router, the very first step to do should be changing the
username and password for administration access.

Cellular network
Usually the only setpoint that needs to be adjusted is the APN name. A frequent APN name is "internet", but if
you are not sure ask your SIM card provider for proper APN name.

WAN interface
If the router contains also ethernet socket for WAN connection it may be required to select cellular module as
the main WAN interface.

LAN setup
Most routers do not require any changes in the LAN configuration as their default configuration contains
DHCP server activated. Clients will get IP settings automatically.

Cellular router examples


Teltonika RUT955 – comprehensive industrial LTE router based on Linux and customized OpenWRT
distribution.
Gemalto ELS61T – industrial cellular modem with LTE router function based on Linux and OpenWRT
distribution.

4.5 External display


InteliNeo 6000 does not have an integrated display. External Remote Displays or PC Panel Displays are used
when needed. InteliNeo 6000 package does not include any external displays. External displays must be
acquired separately, see the chapter Displays (page 23).

4.5.1 InteliVision Displays


Wiring diagrams
IMPORTANT: Fixed IP address must be configured if the terminal is not connected to the DHCP
server.

For display connection it is recommended to use Ethernet 1 (trusted interface in default). Direct connection of
InteliVision display to InteliNeo 6000 via ethernet cable can be used only for connection of single device.
Using switch for connection allows you to connect multiple devices such as display, computer and Modbus to
InteliNeo 6000 at one time.

InteliNeo 6000 1.5.0 Global Guide 79


Image 4.51 Connection of InteliVision display to InteliNeo 6000

Image 4.52 Multiple connection to a single controller via switch

Note: The IP address of each device in the same network must vary.

Note: InteliVision 5.2 is used for illustrative purposes, the same wiring diagrams apply for all supported displays
mentioned in Displays (page 23).

InteliNeo 6000 1.5.0 Global Guide 80


4.6 Maintenance
4.6.1 Backup battery replacement
The internal backup battery lifetime is approx. 6 years. If alarm Wrn RTC Battery Flat (page 1264) is present,
replacement of backup battery is needed. Follow these instructions:
Connect the controller to a PC and save an archive for backup purposes (not necessary but
recommended).
Disconnect all terminals from the controller and remove the controller from the switchboard.
Release the rear cover using a flat screwdriver or another suitable tool.

The battery is located in a holder on the circuit board. Remove the old battery with a small sharp
screwdriver and push with a finger the new battery into the holder.

Warning – Risk of fire if battery is replaced with incorrect type or polarity. Dispose of used batteries
according to instructions. The CR1632 3V Lithium battery have to be used."

Note: The picture above is only illustrative and actual battery placement may vary.

Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention that the
cover is in correct position and not upside down!
Put back the back cover.
Power the controller on, adjust date and time and check all setpoints.

6 back to Installation and wiring

InteliNeo 6000 1.5.0 Global Guide 81


5 Controller setup
5.1 Operator Guide 82
5.2 Controller configuration and PC tools connection 112
5.3 Default configuration 118
5.4 General Functions 119
5.5 Application related functions 235

6 back to Table of contents

5.1 Operator Guide


Note: This chapter is relevant only for users who want to use external displays. If you want to operate /
monitor / configure your site using the computer with installed PC tool see the chapter PC tools (page 22).
See the chapter Displays (page 23) if you want to use any PC panel display, for example with installed
InteliSCADA PC tool. In above mentioned chapters you can find links to Global Guide for each product.

5.1.1 InteliVision 5.2


Front panel elements 82
Page Structure 86
StartUp screen 88
Connecting to the controller 90
Login to the controller 91
Setpoints 94
Metering screens 101
Alarmlist 101
History 103
Trends 105
Administration 106
Basic operating modes description 111

Note: The images used in the Operator Guide are only illustrative. The screens shown in the images are
compatible with the InteliGen 1000 Controller, but the functionality of the IV 5.2 Display such as Connection,
Login, Setpoints Settings, Display Settings, etc. remains the same.

Front panel elements


Front panel of the unit uses hardware buttons for configuring, moving, scrolling, commands and other
functions.

InteliNeo 6000 1.5.0 Global Guide 82


Image 5.1 : Front panel overview

Navigation buttons
Arrow buttons on the front panel are mainly used for navigation inside the entire graphical user interface. In
addition the arrows left and right are used for changing the controller mode if the actual position is any
metering screen.

Arrow left and right

Image 5.2 : Arrow left and right

The buttons are used for :


Changing the controller mode (only on metering screens)
Movement between history columns
Movement in the dialogs

Arrow up and down

Image 5.3 : Arrow up and down

InteliNeo 6000 1.5.0 Global Guide 83


The buttons are used for :
Cyclical movement between the metering Screens
Movement in the dialogs
Changing the value in the dialogs
Movement in menus
Listing on pages

Enter

Image 5.4 : Enter button

The button is used for :


Confirming the values
Confirming the selections
Confirming the listing options

Menu

Image 5.5 : Menu button

The button is used for :


Escape function
Step back function
Cyclical change of the page (from any metering screen)

Function buttons
Function buttons are dedicated for the performing of the concrete function. By pressing the button the
controller action or controller command is performed (see bellow).

Image 5.6 : Function buttons (Start, Stop, Alarm/Horn reset, Horn reset)

Start : starting of the BESS


Stop : stoping of the BESS
Alarm/Horn reset : resets the horn and confirms all the alarms in the alarmlist
Horn reset : resets only the horn

InteliNeo 6000 1.5.0 Global Guide 84


User buttons

Image 5.7 : User button

User button is dedicated for predefined user function.


Performing the controller command
Jump to the specific page or metering screen
special function on the pages

Special and button combination


In this manual the shortcut is a term for the combination of the buttons or long press of the button.

+
Image 5.8 : Shortcut (jump to the administration)

Enter + Menu : performs the jump to the administration. Enter button has to be pressed first.
Long press of the arrow up or down button
in the menus : performs the cyclical listing
in the dialog : velocity of the changing value is increased
based on special algorithm

Status LED
There is one multicolor (RGB) LED on the front panel of the unit. The specified color and flashing function
describes the actual state of the unit.

Image 5.9 : Status LED

LED intensity is directly connected with the actual setting of the backlight intensity in Administration menu
"Settings" accessible by shortcut Enter + Menu
the intensity respects the value of the Manual or External brigness control
The flashing of the status LED and indicative Alarm icon in the top statusbar have the same period
Meaning of the status LED colors is described below

InteliNeo 6000 1.5.0 Global Guide 85


Priority LED State Description
Active unconfirmed level2 (shutdown) alarm
Inactive unconfirmed level2 (shutdown) alarm
1 Red is flashing
Lost of internal communication line
Controller unit in init state
Active confirmed level2 (shutdown) alarm
Display unit in init state
2 Red lights
Display unit booting procedure
Lost of communication line with controller unit
3 Cyan lights temperature inside the housing exceeded the 85°C (185°F)
Active unconfirmed level1 (warning) alarm
Inactive unconfirmed level1 (warning) alarm
Active confirmed level1 (warning) alarm
4 Yellow lights
Active unconfirmed fail sensor alarm
Inactive unconfirmed fail sensor alarm
Active confirmed fail sensor alarm
5 Green lights unit is running correctly without any errors or alarms

Page Structure
Pages
There are several screens called pages in the graphical user interface (GUI), which are accessible by
pressing the Menu button or concrete user button in the bottom status bar. Each page has a different function
and different structure. Pages are described in special chapters in this manual.
The actual GUI consists of 6 different pages :
Setpoints
Metering screen
Alarmlist
History
Trends
Administration
Page administration is accessible only by pressing the combination of the Enter and Menu buttons
from only Metering screen.

Screens
Each type of controller has special set of screens stored in the controller configuration. The description of the
each metering screens is by default predefined by ComAp. Scrolling between the screens is performed using
the arrow up and down buttons.
Note: The metering screens are adjustable using the Screen Editor (in InteliConfig). See chapter Screen
Editor for more information. The Screen Editor tool also has its own manual.

InteliNeo 6000 1.5.0 Global Guide 86


Status bars

Bottom status bar


The bottom status bar is used for the user button functions. There are several status bars in the GUI. Bottom
status bar consists of 5 areas (user buttons) dedicated for emitting the command to the controller unit (e.g.
MCB and BCB Close/Open), jump to the specified page (e.g. alarmlist, history) or special functions on some
pages.

Image 5.10 : Bottom status bar on Home metering screen

1. User button 1 - MCB Close/Open


2. User button 2 - BCB
3. User button 3 - Show Alarm List
4. User button 4 - Show History
5. User button 5 - Show Home Screen
Note: The button press is visually indicated by black frame around the button area. The indication does not
mean that requested command is performed, it is only press indication.

Note: Concrete status bar views for concrete page are described in specific chapters in this manual.

Note: Inactive buttons are visually indicated as grayed button. It means that the button is not available for any
reason (e.g. password protected button).

Top status bar


The top status bar can NOT be adjusted. Information in the top status bar is fixed and controlled by ComAp.

Image 5.11 Top Status Bar description

InteliNeo 6000 1.5.0 Global Guide 87


Image 5.12 : Top Status Bar - Mode selector dialog

1. Mode selector - Mode selector is dedicated for the controller mode selection. Using arrow left and right
the controller mode is changed (only on the metering screens). The choice must be always confirmed by
enter button. There is 5s timer for the automatic mode selector dialog cancellation. The mode selector
dialog can be also canceled by menu button.
2. Page title - Each page and each metering screen has its own title. The first number in square brackets
describes the actual metering screen position. The second number describes the total available number of
metering screens.
3. Trending - The icon is active when the trending is running. Icon is inactive when the trending is stopped.
4. USB Stick - The icon is active if the USB stick is plugged in the display unit. Icon is inactive if there is no
USB stick plugged in.
5. Access Lock - Access lock icon is active if the display is locked for security reasons. Icon is inactive if the
controller unit is not locked.
InteliNeo 6000 - the function in InteliNeo 6000 is connected to the specific user account. It means only
the user with sufficient rights can operate the controller or deactivate access lock function.
Icon ( - Single Lock) is displayed if the controller is locked and actually logged-in user is the lock
owner. User is able to operate the controller or to deactivate the access lock function.
Icon ( - Double Lock) is displayed if the controller is locked and actually logged-in user is NOT
the lock owner. Also the Access Lock function can not be deactivatedbecause of insufficient access
rights. See chapter Access Lock for more information.
6. PC connection - PC connection icon is not supported in InteliVision 5.2.
7. Alarm indication - The alarm icon is flashing red if there is at least one unconfirmed alarm (shutdown or
warning) in the alarmlist. The icon lights red if there is at least one confirmed active alarm and no
unconfirmed alarm in the alarmlist. The icon is inactive if the alarmlist is empty.
8. User - The user icon lights green if the user is logged in to the controller. The icon is inactive if the user is
logged out.

StartUp screen
The StartUp screen is defined in firmware and can not be adjusted. The screen is used as a default point in
user interface. The main purpose of the screen is to handle all the necessary messages from the display to

InteliNeo 6000 1.5.0 Global Guide 88


the user. If the StartUp screen is displayed it is possible to Import the new display firmware, to see the
InteliVision Info screen, to set new communication parameters or to set other display parameters.
StartUp screen is displayed :
during the booting procedure
if the connection with controller is not established or interrupted

Image 5.13 : StartUp screen

1. Init logo - Init screen logo


2. Status panel with message - see Messages table below for more info
green - if the device is running, initialization, controller programming
red - other than running state (communication error, connecting to the controller)
3. User button 1 - Import - Firmware Import
4. User button 2 - IV Info- InteliVision Info screen
5. User button 3 - Comm- Communication settings screen
6. User button 4 - Settings- Display settings screen
7. User button 5 - Login- Login to the controller
Inactive if comm. channel between display and controller is not established
Active if comm. channel between display and controller is established

Status panel message table

Message / color Message description


Running The device is running without any issue.
Initialize control unit Booting procedure and handshaking of internal processes.
Control unit is
Connected controller is programmed.
programmed
Detecting main CU
Internal communication error.
failed
Not compatible
Unsupported display or controller branch. Display and communication bridge
application branch in
are not compatible.
CU

InteliNeo 6000 1.5.0 Global Guide 89


Firmware is corrupted Display firmware or bootloader is corrupted.
Display does not support configuration in controller. Configuration reading
Unsupported
failed for any reason. Issues with controller configuration. Issues with display
configuration format
memory allocation for controller configuration.
Unsupported screen Display does not support screen format in controller configuration controller.
format Language identicator has not been found in controller configuration
Wrong configuration Issues with the content of the controller configuration. Corrupted content of
content controller configuration.
Controller unit is (has been) disconnected for any reason. Transition state
Disconnected
when the contoller unit is programmed.
Connecting Display tries to establish the secured communiction channel with controller.
Secured communication channel between display and controller is
Connected
established.
Controller
TCP/IP socket can not be created for any reason.
unreachable
Controller TCP/IP socket was established but the communication inside the socket does
identification timeout not run.
Controller
Display unit acquired unknown public key from the controller unit.
authentication failed
Secure connection
Secured connection with controller can not be established.
was not established
Attempt to login to the controller is refused. The wrong credentials has been
Wrong Credentials
inserted (Username, Passeword, UID or PIN)
Brute force protection. Controller is temporary blocked because of to many
Access Blocked
attempt of inccorect login.
Attempt for login using UID/PIN on untrasted interface. Only controlller
Wrong Interface
Ethernet 1 port accepts the login using UID and PIN.

Note: Connecting and connected state are marked red because at that moment the user is not logged in yet.
Login procedure is automatic to InteliNeo 6000 controller on StartUp screen (user with access rights 0 is
always loged in). Due to this fact the connecting and connected state are the transition states only on StartUp
screen.

Connecting to the controller


The procedure of connecting display to the controller slightly differ based on which Ethernet terminal is used. In
case of using Ethernet 1 (page 19) will not be required user login for connection and basic operations because
the terminal is considered as Trusted. Any other terminal is considered as Untrusted and before actual
connection user login is required.
Note: If display is not used (button is not pressed) for longer period, the user is logged out. This would cause
disconnection from the controller if an Untrusted terminal is being used.

InteliNeo 6000 1.5.0 Global Guide 90


1. Accept Unknown Certificate - Connection acceptation of the unknown devices (with unknown public
keys) or not supported branches.
a. Never (by default) - display unit never accepts the unknown devices.
b. Always - display unit always accepts the unknown devices.
2. IP Controller - IP address of the controller unit to be connected.
3. IP Port - IP port of the controller unit to be connected. Default IP Port is 23.
4. Address - Terminal Comm Address (page 393) of the controller.
5. IP Mode - there are two modes :
a. Automatic - display unit ethernet communication parameters are acquired automatically from the
DHCP server (which must exist in the network infrastructure).
b. Manual (by default) - display unit ethernet communication parameters are configured manually by
user.
6. IP InteliVision (by default 192.168.1.101) - The IP address of the display. Note that IP InteliVision
address and IP Controller address must be in the same network to establish the connection.
7. IP Subnet Mask (by default 255.255.255.0) - Mask of the network where the ethernet communication is
established.
8. IP Gateway (by default 192.168.1.101) - The gateway in network on which the packets are directed.
9. User button 1 : Connect - By pressing the button the communication automat is restarted to newly set
parameters. Until the button is not pressed the previous communictaion channel is still in progress.

Login to the controller


Login via Untrusted terminal
If an Untrusted terminal is being used, the display stays connected to the controller but awaits user login,
otherwise the controller does not provide any data. Login with an user to proceed to measurement screens.

InteliNeo 6000 1.5.0 Global Guide 91


Login via Trusted terminal
If the Trusted terminal is being used, the display automatically logs on to the controller with inbuilt user account
level 0. The measurement screens are immediately showed and an user login is required only for specific
functions which are set in configuration.
The group Password is not setpoint group. This Password item is manually placed to the first group position on
the program code level just for this controller unit.

Image 5.14 : Main Setpoints Page

Password item - the item dedicated for the login and logout to the controller.

Image 5.15 : Setpoints Password Page

InteliNeo 6000 1.5.0 Global Guide 92


Image 5.16 : Login Dialog

Currently Logged-in User - the information about actually logged in user or his ID if loged using ID and PIN.
Access Rights - Access rights of the actually logged in user
0 - user has access rights 0, which means "logged-out" user
0,1 - user has access rights 0 + 1 access rights
0,1,2 - user has access rights 0 + 1 + 2 access rights
0,1,2,3 - user has access rights 0 + 1 + 2 + 3, which means administrator rights
Login and Logout buttons
Login button calls the login dialog.
Logout button performs the logout action.

Enter Password
The dialog password is dedicated for password insertion. When the dialog is active the buttons arrow up and
down are used for number selection. Enter button confirms the option. Menu button cancels the dialog without
saving.

Image 5.17 : Dialog Password overview

Password Change
The dialog password change is dedicated for password change. When the dialog is active the buttons arrow
up and down are used for number selection. Enter button confirms the first option and the same password

InteliNeo 6000 1.5.0 Global Guide 93


must be inserted again. Enter button after insertion the second cell performs the password change (in case
the password are same). Menu button cancels the dialog without saving.

Image 5.18 : Dialog Password Change overview

Note: The user must be logged in with respective rights to be able to change password for respective rights.

Setpoints
The setpoint page is intended for setting the controller values. Each type of controller has specific setpoints to
be set. The setpoints also depend on the type of application like MPTMMCB and MINT. Availability of the
setpoint item also depends on configuration level settings in Administration page. Setpoint is set in 2 steps.
1st step - Setpoint group is selected using buttons arrow up and down and confirmed using enter button

Image 5.19 : Setpoints Page overview

1. Setpoints group - the column setpoint group displays the available groups based on the controller,
application type and configuration level settings. Respective setpoint group is selected using enter button.
2. Available setpoints in actually selected group - each setpoint group contains specific setpoints. The
informative column Setpoint name displays the available set of setpoints to be set in each Setpoint group.

InteliNeo 6000 1.5.0 Global Guide 94


This column is only informative and can NOT be set using the arrow left and right. The setpoint setting is
done using the 2nd step - see below.
2nd step - Setpoint item is selected using the buttons arrow up and down and the dialog for value setting is
called using the enter button. The dialogs are described in the chapter Dialogs.

Image 5.20 : Group Setpoints Page

1. Setpoint name - Setpoint is set using the enter button. Specific dialog is displayed and the value can be
set. There are several types of dialogs (text, numeric, stringlist) and the type of called dialog depends on
the setpoint type. The dialogs are described in the chapter Dialogs.
2. Actual value - Informative actual value for specific setpoint is displayed. Value range, original value and
default value for the selected setpoint are displayed inside the dialog.

Protected Setpoint Indication


If the setpoint is protected by password then the icon (crossed hand) is displayed just behind the setpoint
value. The setpoint protection is set using PC Tool InteliConfig.

Force Value Indication


If the setpoint is forced by another setpoint then the icon (double right arrow) is displayed just behind the
setpoint value.
Green Icon - Forcing is active
Grey Icon - Force Value is set to the specific setpoint and forcing is inactive

InteliNeo 6000 1.5.0 Global Guide 95


Image 5.21 : Force Value and Protected Setpoint Indication

IMPORTANT: If the controller is locked (Access Lock function is active) then the attempt for
setpoint editation is denied and the information dialog is displayed (Controller is Locked). See
chapter Administration and Access Lock.

Numeric change

Value
The dialog value is dedicated for number setting. When the dialog is active the buttons arrow up and down are
used for number selection. Enter button confirms the option. Menu button cancels the dialog without saving.

Image 5.22 : Dialog Value overview

Value Extended
The dialog value extended is dedicated for number setting with combination with one or more string value.
When the dialog is active the buttons arrow up and down are used for number/item selection. Enter button
confirms the option. Menu button cancels the dialog without saving.

InteliNeo 6000 1.5.0 Global Guide 96


Image 5.23 : Dialog Value Extended overview

IP address
The dialog IP address is dedicated for IP address insertion. When the dialog is active the buttons arrow up
and down are used for number selection. Arrows left and right are used for moving between the IP cells. Enter
button confirms the option. Menu button cancels the dialog without saving.

Image 5.24 : Dialog IP address overview

String List Selection


The dialog string list is dedicated for list item selection. When the dialog is active the buttons arrow up and
down are used for item selection. Enter button confirms the option. Menu button cancels the dialog without
saving.

InteliNeo 6000 1.5.0 Global Guide 97


Image 5.25 : Dialog String List overview

Text Edit
The dialog text is dedicated for text inserting or modification. When the dialog is active the buttons arrow up
and down are used for letter selection. Arrow up means the selection in left direction, arrow down means the
selection in right direction. Arrows right/left are used for moving between the letters to the next/previous letter
position in the text field. If actual position is very right letter then the arrow right inserts new letter to the right.
Letter DEL deletes actualy selected letter (using left or right arrow). Insert letter (empty letter - just behind the
DEL letter) inserts the letter to the actual position (using left or right arrow) Enter button confirms the text
modification. Menu button cancels the dialog without saving.

Image 5.26 : Dialog Text overview

Note: Enter button is used for dialog confirmation and saving the entire text to the configuration and because
of this the DEL and INS letter is inserted using the left or right arrow button.

Time and date edit

Date
The dialog date is dedicated for date setting. When the dialog is active the buttons arrow up and down are
used for number selection. Arrows left and right are used for moving between the date cells. Enter button
confirms the option. Menu button cancels the dialog without saving.

InteliNeo 6000 1.5.0 Global Guide 98


Image 5.27 : Dialog Date overview

Time
The dialog time is dedicated for date setting. When the dialog is active the buttons arrow up and down are
used for number selection. Arrows left and right are used for moving between the time cells. Enter button
confirms the option. Menu button cancels the dialog without saving.

Image 5.28 : Dialog Time overview

Timer settings
The dialog timer is dedicated for timer setting. When the dialog is active the buttons arrow left and right are
used for the line option selection. Enter button confirms the actual option in the line and the next option can be
performed. Enter button on the last line confirms all the option in dialog and save the timer settings to the
controller. Menu button cancels the dialog without saving.

InteliNeo 6000 1.5.0 Global Guide 99


Image 5.29 : Dialog Timer (Off) overview

Image 5.30 : Dialog Timer (Once) overview

InteliNeo 6000 1.5.0 Global Guide 100


Image 5.31 : Dialog Timer (Repeated) overview

Metering screens
InteliNeo 6000 Controller screens
InteliNeo 6000 metering screens are predefined by ComAp and covers all the application types.
the movement between the metering screens is done using the arrow up and down buttons in the front
panel
the entire screens and instruments on the screens are dynamically displayed or hidden based on the
following state of the controller unit :
Application type
Wiring controller settings
Configured CAN modules
ECU list settings

InteliNeo 6000 metering screens


Home Statistics
Power Ethernet 1
BESS Ethernet 2
Mains Ethernet 3
Bus Hot Swap Redundancy
Synchronization CAN modules
Power Management ECU modules
Analog inputs Modbus Master Devices
Binary Outputs Virtual modules
Binary Inputs
Grid Codes

Alarmlist
The alarmlist page is intended for displaying the controller alarms. If any of the following type of the controller
alarm occurs The alarmlist page is displayed and also the alarm icon in the Top status bar starts flashing
RED, even if it is not the shutdown alarm. The Automatic jump to the Alarmlist page is performed only in case
the actual GUI position is the Home metering screen. The alarm icon in the top status bar is informative icon
where the display unit informs the user that there is any alarm stored in the controller unit. Pressing the User

InteliNeo 6000 1.5.0 Global Guide 101


button 3 opens the alarmlist page. The alarmlist page is displayed until the alarmlist contains at least one
unconfirmed alarm.
There are 4 different types of controller alarms :
Warning (often also known as 1st level alarm) - represented by the YELLOW colour. These types of
alarms inform the user that something is wrong and need to be checked and confirmed.
Shutdown (often also known as 2nd level alarm) - represented by the RED colour. These types of
alarms protects the BESS during the wrong state.
ECU alarm - represented by the BLUE colour. This type of alarm comes from the connected external ECU
units.

Image 5.32 : Alarmlist Page

1. Alarm item number - displays the number of the concrete alarm.


2. Alarm item star - describes if the alarm is CONFIRMED or NOT COFIRMED. The confirmation action is
performed by the Alarm reset button in the front panel
a. Star is displayed - alarm is NOT CONFIRMED
b. Star is not displayed - alarm is CONFIRMED (using alarm reset button)
3. Alarm description - The short description of the alarm
4. Alarm coloring - There are specified the color and asterix combination
level 1 (warning) alarm

Active/unconfirmed : * / yellow background / dark text (asterix active)

Active/confirmed : yellow background / dark text (asterix inactive)

Inactive/unconfirmed : * / dark background / yellow text / asterix active


level 2 (shutdown) alarm

Active/unconfirmed : * / red background / white text (asterix active)

Active/confirmed : red background / white text (asterix inactive)

Inactive/unconfirmed : * / dark background / red text (asterix active)


ECU alarm

Active/unconfirmed : * / blue background / white text (asterix active)

Active/confirmed : blue background / white text (asterix inactive)

InteliNeo 6000 1.5.0 Global Guide 102


Inactive/unconfirmed : * / dark background / blue text (asterix active)
5. Topstatus bar Alarmlist icon - The alarm icon is fashing red if there is at least one unconfirmed alarm
(shutdown or warning) in the alarmlist. The icon lights red if there is at least one confirmed active alarm
and no unconfirmed alarm in the alarmlist. The icon is inactive if the alarmlist is empty. This is information
that something is wrong and need to be checked and resolved.
Note: The Alarmlist displays maximum 8 alarm items at the same time. If there is more than 8 alarms in the
alarmlist it is possible to list in the page to another alarm items by arrow up and down buttons.

Note: The alarmlist page is automatically displayed and backlight is turned on if the new alarm appears (only
in case the actual GUI position is the Home metering screen).

IMPORTANT: InteliVision 5.2 displays maximum 16 alarms.

IMPORTANT: Alarm reset button confirms all the unconfirmed alarms stored in controller and
resets the horn. Horn reset button resets only the horn.

IMPORTANT: If the actual GUI position is Alarmlist page and there is at least one uncofirmed
alarm in the Alarmlist the jump to the home metering screen and backlight timeout are ignored.

History
The history page displays the records of the important moments in the controller history.
There are 2 types of history records :
Event records - are also known as standard history records. This type of record appears in case the
controller event has been made. The time stamp history also belongs in the event history. The time record
is stored for a specified period of time.
System records - are also known as text history record. These type of records are generated during the
user login/off, controller programming or other system actions.

Image 5.33 : History page overview

1. Fixed column - has a different shade of colour. Fixed column is always merged and anchored on the left
side of the history page.

InteliNeo 6000 1.5.0 Global Guide 103


2. Event history record - this type of record appears in case the controller event has been made.The time
stamp history also belongs in the event history. The time record is stored for a specified period of time.
Pressing the enter button the dialog with detailed information for selected record is displayed.
3. System history record - this type of record appears in case the controller system action has been
made.The time stamp history also belongs in the event history. The time record is stored for a specified
period of time. Pressing the enter button the dialog with detailed information for selected record is
displayed.
4. Jump to first row and column - the jump to the first row and first column is performed if the button is
pressed.
5. Listing mode - by pressing this button the listing mode is changed. There are available 3 modes : listing
by 1 item, listing by 1 page, listing by 10 page. The mode is useful if the history is full of records. Listing
mode is also automatically changed if the listing buttons arrow up and down are pressed for longer time.
Original mode is set when the listing buttons are released.

Image 5.34 : History page - Item detail dialog

Note: Pressing the enter button on the actually selected row the dialog with detailed information for selected
record is displayed.

IMPORTANT: Each controller unit supports the specific number of history records. E.g. controller
InteliNeo 6000 supports 1000 history records. Default configuration consists of 33 columns.
Maximal column amount is approximately 100 columns based on the type of the observed value.

InteliNeo 6000 1.5.0 Global Guide 104


Trends

Image 5.35 : Trends page overview

The Trends page is divided on to 3 main blocks :


Main Trends Window is intended to display all trends. The view and chart movement is fully automatic.
Channel panel displays the actual values and sample period.
Function buttons is intended for start, stop and settings of the trends.

Image 5.36 : Trends page description

1. X axis -X axis displays the time stamps. The view of X axis is fully automatic.
2. Y axis - If the default range is not suitable for the displaying of the value it can be adjusted in settings
option. See bellow for more information.
3. Grid - the grid is displayed behind the trends charts. The grid is fully automatic.
4. Trend line - each channel have different colour for better value identification. The color of the trend line
match to the Value color in channel panel.
5. Actual period - Actual period settings. The period can be adjusted in settings option.
6. Actual channel value panels - display the values of the newest (actual) sample.

InteliNeo 6000 1.5.0 Global Guide 105


7. Trend Icon (Top Status bar) -if the trends are running the informative icon is shown in the top status bar
8. Start / Stop button - the button is dedicated for manual start and stop of the trends. It is possible to setup
the automatic start of trending based on the trigger. There are 2 triggers : Return to Home metering screen
and the specified bit of the available binary value.
9. Channel settings button - There are some settings available for the trends. See more information
bellow.

Administration
Administration menu screen is accessible by using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.

+
Image 5.37 : Shortcut (jump to the administration)

Configuration Level

Image 5.38 : Administration Page - Configuration Level

Standard - Limited amount of settings are available for configuration. The description which settings are
available in chapters concerning to controller functions.
Advanced - Set by factory default. All the settings are available for configuration. Be aware that only
experiences users should perform the settings of extended functions.
Note: By default the Advanced settings is selected which means all the setpoints are available by default. To
restrict the availability the Standard setting must be performed. The advanced and standard category are set
in InteliConfig PC application.

Note: Configuration Level screen is accessible using the buttons combination Enter + Menu just only from
the metering screens. Enter button has to be pressed first.

InteliNeo 6000 1.5.0 Global Guide 106


Display settings

Image 5.39 : Administration Page - Settings

1. Backlight Time - if the cell area is pressed the dialog for time settings is displayed. The user is able to set
the period from 1 up to 241 minutes. There is also the option to set NO Timeout which means the display
unit is backlighted forever. Note that in remote displays like IntelIVision 5.2 the Backlight Timeout option is
not mirrored with controller setpoint Backlight Timeout (it is mirrored in Integrated Color Display).
2. Brightness Control :
a. Manual (by default) - the value of the backlight is set manually using the value dialog (point 3)
b. External - the value of the backlight is controlled by the external resistor or potentiometer. Resistor 5-
2400 Ω corresponds to 0-100% backlight. If the resistor value is out of range, the manual option is
used.
3. Brightness intensity - the value is selected using the value dialog. Note the value is applied immediately
during the change of the value.
4. Internal Temperature information- gives the actual inside temperature of the unit. There is implemented
automatic mechanism for lowering the backlight intensity based the internal derating backlight curve. If the
inside temperature exceeds 35 °C the area behind the temperature lights yellow. The yellow color
indicates that the display backlight curve is applied and automatically starts derate the backlight intensity.
The backlight intensity returns to normal when the temperature is decreased bellow 35 °C. This feature
saves the lifetime of the internal components.
IMPORTANT: It is strongly recommended to use backlight on the standard level max. 60%.
Maximal backlight intensity level of 100% is suitable only for application with higher amount of
the ambient light. Be aware that higher intensity level means higher surface front glass
temperature and lower lifetime.

IMPORTANT: It is strongly recommended to use Backlight Time (timer) set on the reasonable
amount of time (approximately 30 minutes) during the normal running BESS phase. It is because
of saving lifetime of the display unit. The display unit is still running if the backlight is off. For
switching on the LCD backlight the simple pressing any button is necessary.

Note: Settings screen is accessible using the buttons combination Enter + Menu just only from the metering
screens. Enter button has to be pressed first.

InteliNeo 6000 1.5.0 Global Guide 107


Languages

Image 5.40 : Administration Page - Languages

Language settings - the list of languages stored in the controller configuration is displayed in the list of
possible languages.
The InteliVision 5.2 and Integrated Color Display units support the following languages
English
Chinese
Japanese
The InteliVision 5.2 and Integrated Color Display units partially support the following languages
Bulgarian, Taiwan, Czech, German, Greek, Spanish, Finnish, French, Hungarian, Icelandic, Italian,
Korean, Dutch - Netherlands, Norwegian, Polish, Roman, Russian, Croatian, Slovak, Swedish,
Turkish, Ukrainian, Slovenian, Estonian, Latvian, Lithunian, Vietnamese, Italian, Portuguese, Bosnian
The InteliVision 5.2 and Integrated Color Display units support the following Unicode standard character
sets
Basic Latin, Latin-1 Supplement, Latin Extended-A, Latin Extended-B, Latin Extended Additional,
Cyrillic, Greek, Greek Extended, Arabic, Arabic Supplement, General Punctuation, Superscripts and
Subscripts, Currency Symbols, Arrows, CJK Unified Ideographs, Kanji, Hiragana (full width), Katakana
(full width), Hangul Jamo, Thai
IMPORTANT: Even the language is configured in InteliConfig the specific language is unavailable
if the language is empty or the language is not supported by the display unit.

Note: The flag is not displayed if the language is supported but the flag icon does not exist in the integrated
color display unit.

Note: Languages screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.

InteliNeo 6000 1.5.0 Global Guide 108


Controller Info
Controller Info screen in InteliVision 5.2 is dedicated for important information about the connected controller
unit. These information is useful mainly for issues troubleshooting.
Controller info page is divided into 2 main blocks of information :
Controller unit
ID String
Software Version
Serial Number
Controller Type (HW)
Application Type (HW)
Application Branch (HW)
Hardware Type (PCB)
Hardware Version
ID Chip Version
Hardware Features
Configuration
Application Version
Controller Type (SW)
Application Type (SW)
Application Branch (SW)
Application
Configuration Format / Configuration Terminal Format
Configured by

Image 5.41 : Administration Page - Controller Info

Note: Similar values with similar structure can be displayed using InteliConfig PC tool.

Note: Controller Info screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.

IMPORTANT: Integrated Color Display information in Controller Info screen is not available in
remote displays.

InteliNeo 6000 1.5.0 Global Guide 109


Modules Info
Modules Info screen is dedicated for important information about the connected CAN and Plug-In modules
information. The page Modules Info displays the information from the following type of connected modules :
Plug-In modules
CAN peripheral extension modules

Image 5.42 : Administration Page - Modules Info

Note: The availability of the connected module depends on the type of controller unit.

Note: Modules Info screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.

InteliNeo 6000 1.5.0 Global Guide 110


ECU Modules Info
Electronic Control Unit Modules screen is dedicated for important information about the connected modules
information.
The screen ECU Modules displays the information from the following type of connected modules :
ECU Modules

Image 5.43 : Administration Page - ECU Modules

Note: The availability of the connected ECU module depends on the type of controller unit.

Note: ECU Modules screen is accessible using the buttons combination Enter + Menu just only from the
metering screens. Enter button has to be pressed first.

Basic operating modes description


This chapter contains brief information on how the controller behaves in different modes of operation. If you
require more information on separate functions of the controller please go to the chapter Operating Modes
(page 181)
The InteliNeo6000 has the following controller operation modes: OFF, MAN , and AUT .

OFF mode
No start of the BESS is possible and starting command cannot be issued.

No reaction if buttons START , STOP , MCB ON/OFF , BCB ON/OFF are pressed.

Note: When the BESS is running, it is not possible to switch the controller to OFF mode.

MAN mode
To start the BESS press START.
When the BESS voltage is within limits, the BESS icon will light green.
Press BCB ON/OFF to close the BCB. If the BESS voltage is out of the limits, controller does not respond
to the BCB ON/OFF .
If controller detects dead bus, immediately closes output.
If controller detects voltage on the bus, starts synchronizing.
When the breaker is closed, the breaker icon will light green.

InteliNeo 6000 1.5.0 Global Guide 111


To stop the BESS press STOP
Controller unloads the BESS, opens BCB CLOSE/OPEN (PAGE 1055). Unloading is active only when
binary input MCB FEEDBACK (PAGE 1012) is closed or other BESS is connected to bus. In other case
BCB CLOSE/OPEN (PAGE 1055) opens immediately.

AUTO mode
BESS is controlled based on external signals GENERIC GENSET START/STOP (PAGE 1004) or conditions
(AMF, Peak shaving, Power management system, etc.).
When one condition deactivates the BESS, it will not stop if another condition for automatic starts is active.
Controller does not respond to BCB ON/OFF, MCB ON/OFF, STOP, START buttons and corresponding
remote InteliScada or Modbus commands.
IMPORTANT: If a red alarm is present and the controller is in the AUT mode, the BESS can start
by itself after all red alarms become inactive and are acknowledged (fault reset is pressed)! To
avoid this situation, adjust the setpoint Fault Reset To Manual (page 386) to the Enabled position.

5.2 Controller configuration and PC tools


connection
5.2.1 USB 112
5.2.2 Ethernet 113

6 back to Controller setup


This chapter contains brief introduction into the specifics of firmware and archive upload and connection of
various PC tools to the controller. If you require detailed information on each PC tool please use the included
Help in those PC tools or download their Reference Guides.

5.2.1 USB
You may connect to the controller using the ⑭ USB (page 46) Port. In this case standard USB A to B cable
should be used - USB (page 74) connection.

Connection using InteliConfig

Image 5.44 First screen of InteliConfig - select connect to controller

InteliNeo 6000 1.5.0 Global Guide 112


Image 5.45 Second screen of InteliConfig - Select your controller from list of Detected
controllers.

Select your controller from the list of Detected controllers. You need to know your contoller's serial number.
Note: You do not need to be using user account while connecting via USB.

Connection using WinScope

Image 5.46 WinScope screen - Select your controller from list of Detected controllers.

Select your controller from the list of Detected controllers. You need to know your contoller's serial number.
Note: You do not need to be using user account while using WinScope1000 connected via USB.

5.2.2 Ethernet
You may connect to the controller using any of the Ethernet 1 (page 49), Ethernet 2 (page 49), or Ethernet 3
(page 49) ports, if correct Ethernet Port Configuration settings are applied (Ethernet port 1 (page 403),
Ethernet port 2 (page 404), Ethernet port 3 (page 405)).
Note: See Communication peripherals (page 18) to see differences between these peripherals.

InteliNeo 6000 1.5.0 Global Guide 113


Note: Go to Types of interfaces (page 226) to see types of ethernet interfaces and possibilities of
connections.

Direct connection
When you use direct connection the controller needs to be reachable directly from the PC you use (i.e. one
LAN or WAN without any firewalls and other points that may not allow the connection). The following settings
need to be checked in the controller:
Direct Connection Port (page 411) has to be set to the same value as in the PC tool.
IP Address Mode (page 406) can be set to AUTOMATIC when there is DHCP service is available.
Otherwise it needs to be set to FIXED.
IP Address (page 407) is either set automatically or it can be adjusted to a specific requested value.
Subnet Mask (page 407) is either set automatically or it can be adjusted to a specific requested.
Gateway IP (page 408) can be set here when it is used.

Note: The connection speed might be significantly limited when you connect the controller directly from the
PC and your Ethernet card is setup to Energy-Efficient Ethernet option.

Connection using InteliConfig

Image 5.47 First screen of InteliConfig - select connect to controller

InteliNeo 6000 1.5.0 Global Guide 114


Image 5.48 Second screen of InteliConfig - select Ethernet

Use IP address which is stored in proper value (based on selected Ethernet peripheral) and fill Controller
address - this needs to be same as value of Terminal Comm Address (page 393).
IMPORTANT: Never fill Access code!

IMPORTANT: In case of using Ethernet 2 (page 19) you need to fill Username and Password of
actual user account.

Image 5.49 Second option of connection via InteliConfig

You can also select controller from "Detected controllers" feature. If this controller is connected via Ethernet 2
(page 19) you will be prompted to fill Username and Password of actual user account.

InteliNeo 6000 1.5.0 Global Guide 115


Connection using WinScope

Image 5.50 WinScope screen - select Ethernet

Use IP address which is stored in proper value (based on selected Ethernet peripheral) and fill Controller
address - this needs to be same as value of Terminal Comm Address (page 393).
IMPORTANT: Never fill Access code!

IMPORTANT: In case of using Ethernet 2 (page 19) you need to fill Username and Password of
actual user account.

AirGate connection
You may connect to the controller using AirGate which works only via Ethernet 2 (page 19). If the AirGate key in
the Access Administration is empty the controller will not connect to the AirGate despite the function is enabled.
Access Administration is available in Tools of the InteliConfig.
Setpoints and values related to connection via AirGate:
AirGate Connection (page 416) - has to be ENABLED
AirGate Address (page 678) - manually adjusted address of AirGate server
AirGate Port (page 417) - manually adjusted port for communication between Controller and AirGate
server
AirGate Status (page 911) - has to be connected, operable
AirGate ID (page 911) - 9 numbers long ID of the controller

IMPORTANT: Controller has to be connected to the Internet.

InteliNeo 6000 1.5.0 Global Guide 116


Connection using InteliConfig

Image 5.51 First screen of InteliConfig - select connect to controller

Image 5.52 Second screen of InteliConfig - AirGate

Use AirGate ID, AirGate server with proper port (54441 for global.airgate.link), AirGate Key and Controller
address - this needs to be same as value of Terminal Comm Address (page 393). Valid user account -
Username and Password - is required for the connection.
IMPORTANT: Never fill Access code!

Note: Ask your administrator for AirGate Key. Administrator can always change the key via InteliConfig using
"Tools -> Access administration -> Change AirGate key"

InteliNeo 6000 1.5.0 Global Guide 117


Connection using WinScope

Image 5.53 WinScope1000 screen - select AirGate

Use AirGate ID, AirGate Server with proper port (54441 for global.airgate.link), Device Access Key and
Controller Address - this needs to be same as value of Terminal Comm Address (page 393). Valid user
account - Username and Password - is required for the connection.
IMPORTANT: Never fill Access code!

5.3 Default configuration


5.3.1 Binary inputs
Number Name Description Configured function
BIN1 BCB Feedback BESS circuit breaker feedback BCB FEEDBACK (PAGE 991)
BIN2 MCB Feedback Mains circuit breaker feedback MCB FEEDBACK (PAGE 1012)
BESS Ready To BESS READY TO LOAD (PAGE
BIN3 BESS is ready to be loaded
Load 995)
Photovoltaic (renewables) circuit PVCB FEEDBACK (PAGE
BIN4 PVCB Feedback
breaker feedback 1025)
BIN5 Remote OFF Switch controller to OFF mode REMOTE OFF (PAGE 1027)
BIN6 CU-BIN-06 Free slot Not Used
BIN7 Sd Override Suppression of alarms SD OVERRIDE (PAGE 1027)
BIN8 CU-BIN-08 Free slot Not Used
BIN9 CU-BIN-09 Free slot Not Used
BIN10 CU-BIN-10 Free slot Not Used
BIN11 CU-BIN-11 Free slot Not Used
BIN12 CU-BIN-12 Free slot Not Used

InteliNeo 6000 1.5.0 Global Guide 118


5.3.2 Binary outputs
Number Name Description Configured function
BOUT1 CU-BOUT-01 Free slot Not Used
INVERTER RUN REQUEST
BOUT2 BESS Run Request Request to start BESS
(PAGE 1084)
Indication of required BESS Circuit BCB CLOSE/OPEN (PAGE
BOUT3 BCB Close/Open
Breaker state 1055)
Indication of required Mains Circuit MCB CLOSE/OPEN (PAGE
BOUT4 MCB Close/Open
Breaker state 1090)
Activation of any devices before
BOUT5 Prestart PRESTART (PAGE 1098)
BESS start
BESS READY TO LOAD
BOUT6 Ready To Load BESS can be connected to load
(PAGE 1065)
BOUT7 Alarm Indication of unconfirmed alarm ALARM (PAGE 1053)
BOUT8 CU-BOUT-08 Free slot Not Used
BOUT9 CU-BOUT-09 Free slot Not Used
BOUT10 CU-BOUT-10 Free slot Not Used
BOUT11 CU-BOUT-11 Free slot Not Used
BOUT12 CU-BOUT-12 Free slot Not Used

5.3.3 Analog inputs


Configured
Number Configured sensor Configured function
sensor
AIN1 CU-AIN-01 Not configured Not Used
AIN2 CU-AIN-02 Not configured Not Used
AIN3 CU-AIN-03 Not configured Not Used
AIN4 CU-AIN-04 Not configured Not Used

5.3.4 Analog Outputs


Number Name Output HW type Configured function
AOUT1 CU-AOUT-01 U [-10 V, 10 V] VRO
AOUT2 CU-AOUT-02 U [-10 V, 10 V] FRO

5.4 General Functions


5.4.1 3V3 Reference Voltage Measurement 121
5.4.2 Access lock 121
5.4.3 Alarm Management 122
5.4.4 AMF Function 125
5.4.5 Breaker Control 126

InteliNeo 6000 1.5.0 Global Guide 119


5.4.6 CAN Bus Log 131
5.4.7 CAN Intercontroller Communication 132
5.4.8 CAN1 ECU/IO Modules Splitting 133
5.4.9 Configuration Lock 135
5.4.10 Configuration Override 135
5.4.11 Control Groups 136
5.4.12 Crash Dump 137
5.4.13 Distributed Power Management Signals 138
5.4.14 E-STOP 143
5.4.15 Event History 145
5.4.16 Exercise Timers 149
5.4.17 Firewall 157
5.4.18 Forced Value 158
5.4.19 Hot Swap Redundancy 160
5.4.20 I/O Configuration 166
5.4.21 Load Shedding 171
5.4.22 Loss of Mains (Decoupling) Protections 173
5.4.23 Mains Import Measurement 175
5.4.24 Modbus Client (Master) 176
5.4.25 Multiple ECU 180
5.4.26 Operating Modes 181
5.4.27 PLC - Programmable Logic Controller 183
5.4.28 Power Formats And Units 196
5.4.29 Protections 197
5.4.30 Pulse Counters 211
5.4.31 PV Inverter Slots 212
5.4.32 SD Card Storage 215
5.4.33 Sensor Curves 216
5.4.34 Service Timers 218
5.4.35 Sunrise/Sunset 219
5.4.36 Sunspec 219
5.4.37 System Start/Stop 219
5.4.38 SW Key Features 219
5.4.39 Universal Genset support 220
5.4.40 User Buttons 224
5.4.41 User Management And Data Access Control 226
5.4.42 User Setpoints 232
5.4.43 Voltage Phase Sequence Detection 235
General functions which are not directly related to the Microgrid application are described in this chapter.
6 back to Controller setup

InteliNeo 6000 1.5.0 Global Guide 120


5.4.1 3V3 Reference Voltage Measurement
The 3V3 reference voltage is critical for the right functionality of analog/digital converters (ADC). If the 3V3
reference is out of the limit (less than 3.2 V or more than 3.4 V) all voltage measurements will be distorted. In this
case, the LBO HW AC VOLTAGE MEASUREMENT ERROR (PAGE 1083) is activated. It is recommended to use this
LBO to activate user protection which will open the BCB and turn off the BESS to prevent any damage to
theBESS, load, or Mains.
The input value for the LBO is given by the average of all 3 measured reference voltages which increases the
robustness of the protection. The reference voltage should be always fixed and within the limit. Wrong reference
voltage might mean the controller unit is going to fail. The LBO HW AC VOLTAGE MEASUREMENT ERROR (PAGE
1083) is deactivated immediately after the average value of the reference voltage is back within the limit. If the
LBO is still being active, you can try to power off and power on the controller unit. If it doesn't help, it is
recommended to contact the technical support.

5.4.2 Access lock


The Access lock function allows any user with Access level 1 and higher to Lock the controller configuration for
other users. There access lock can work in 2 modes - the mode is defined by setpoint Access Lock Mode (page
399). So, only the user who locked the controller will be able to use the controller buttons, change setpoints or
write configuration into the locked controller. All LBIs will be still operable, using the PLC the LBO ACCESS
LOCKED (PAGE 1052) can be used to block any LBIs. The configuration can be unlocked only by the user who
locked it or by the administrator. This function can be especially useful if more people are remotely connected to
the same controller. The access lock works the same way for configuration via the InteliVision display.
There are 5 types of buttons in the InteliConfig that signalize the actual state of the Access lock.
1. Default state: The controller configuration is unlocked and the user has permission to lock it for other
users.
2. The controller configuration is locked by you.
3. The controller configuration is locked by another user and you can unlock it because you are logged in as
administrator.
4. The controller configuration is locked by another user and you cannot unlock it.
5. The controller configuration is unlocked and your Access level is too low to lock it.

Configurable Access Lock behavior


The extension of functionality is based on the requirement that the machinery is equipped with more operator
stations and the control must have only one of them at any time.
The lock is required for control in Exclusive mode, i.e. user have to activate Access lock with his account to
control the controller.

InteliNeo 6000 1.5.0 Global Guide 121


Access Lock release request
Any user with permission to control the lock will be able to send a request to hand over control when the control is
locked by another user. The request is automatically deactivated when the lock is unlocked.
The user who is the owner of the locked lock will see on the display that the unlock request is active and the lock
icon will change. The icon will also change on the side of the user who sent the request.
In case of emergency, you can use the option to unlock the Access Lock by a user with an administrator role.
The owner of the lock may hand over control to the applicant by confirming the release of the lock.
The release request indication is canceled by unlocking the lock and this occurs in 3 cases:
The owner of the lock will unlock it
The administrator will unlock it
Automatic unlocking if the owner of the lock no longer has any sessions. Applies to setpoint Automatic
Access Lock Release (page 400) settings Enabled.

Concurrent sessions limit


You can set the number of concurrent sessions for a logged-in user. It is possible not to limit this number and this
option does not apply to the administrator role or implicit user.
For more details see User sessions limit (page 400)

Access lock activation


The user as several options hot to activate the access lock:
InteliConfig - Lock Access button

InteliVision 5.2 - Administration (page 106) screen


InteliSCADA - lock button

General commands for Access lock can be found in List of commands and arguments (page 324)

5.4.3 Alarm Management


Alarms purpose is to indicate occurrence of unwanted situation such as unexpected opening of breaker,
generator overvoltage etc. But in certain situations, we use alarms as a way to visualize information that affects
current behavior of the controller.
The controller evaluates two levels of alarms. Level 1 – yellow alarm – is a non-critical alarm that is only
informative and does not take any action regarding the BESS control. Level 2 – red alarm – represents a critical
situation, where an action must be taken to prevent damage of the BESS or technology.

InteliNeo 6000 1.5.0 Global Guide 122


One alarm of level 1 and one alarm of level 2 can be assigned to each binary input
Multiple protections can be assigned on each analog input.
There are also Controller integrated protections (page 125) with Fixed Protection States (page
1179).
Each alarm is written to the Alarmlist (page 125).
Each alarm causes a record to be written into the history log.
Each alarm activates the Alarm and Horn output.
Each alarm can cause sending of a SMS message or an email.

Image 5.54 Analog input alarm evaluation principle

Alarm states
An alarm can have following states:
Active alarm: the alarm condition persists, alarm delay has elapsed.
Inactive alarm: the alarm condition has disappeared, but the alarm has not been confirmed.
Confirmed alarm: the alarm condition persists, but the alarm has already been confirmed.

Image 5.55 Alarm List

Visual interpretation of alarm is decided by terminal side. Commonly for active alarms whole row background
is colored (yellow/red/blue). Inactive alarms have transparent background color and text is colored
(yellow/red/blue)

InteliNeo 6000 1.5.0 Global Guide 123


Alarm types
The controller recognize 3 basic types of the alarm. Each type of alarm is paired with specific types of Protection
types (page 198).

Alarm Level 1
The level 1 alarm indicates that a value or parameter is out of normal limits, but has still not reached critical level.
This alarm does not cause any actions regarding the BESS control. For whole list see Alarms level 1 (page
1245)

Alarm Level 2
The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached. For
whole list see Alarms level 2 (page 1278)
Note: It is not possible to start the BESS if any red level protection is active or not confirmed.

IMPORTANT: The BESS can start by itself after acknowledging the alarms if there is no longer an
active red alarm and the controller is in AUTO mode!

Sensor fail detection (Fls)


If the measured resistance on an analog input exceeds the valid range, a sensor fail will be detected and a
sensor fail message will appear in the Alarmlist (page 125). The valid range is defined by the most-left (RL)
and most-right (RH) points of the sensor characteristic ±12.5% from RH-RL.
Note: Sometimes there can be problem with lower limit of valid range which can be counted as negative
number. In this case the lower limit is set as one half of the RL point of the sensor curve characteristic.

Image 5.56 Sensor fail detection principle

Remote alarm messaging


The controller can sends emails at the moment when a new alarm appears in the Alarmlist (page 125) or new
event is written in Event History (page 145). The message will contain a copy of the Alarmlist (page 125) or
reasons from Event History (page 145). To enable this function, adjust setpoints Sd Message (page 687), Wrn

InteliNeo 6000 1.5.0 Global Guide 124


Message (page 688), or PVBO Message (page 687) to ON. Also enter a valid email address to the setpoints,
E-mail Address 1 (page 683), E-mail Address 2 (page 684), E-mail Address 3 (page 684), or E-mail
Address 4 (page 684).
The list of all supported terminals shows the table below:

Terminal Event message Alarm messages (Subgroup: Messages Settings (page 685))
RS485 NO NO
USB NO NO
Ethernet YES YES

Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a new
alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms
ECU alarms

Controller integrated protections


An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Al, Hst, ALI,
PVBO). Then the alarm name follows. In some cases the prefix can be omitted.

User configured protections


An alarm message in the alarmlist begins with a prefix, which represents the protection type (e.g. Wrn, Al, Hst,
ALI). Protection type and alarm name are selected by user during the Configuration of protections in
InteliConfig (page 205). Then the alarm name follows.

ECU alarms
The ECU alarms are received from the Electronic Control Unit. The alarms are represented by the Diagnostic
Trouble Code, which contains information about the subsystem where the alarm occurred, the alarm type and the
alarm occurrence counter.
The most common fault codes are translated into text form. Other fault codes are displayed as a numeric code
and the ECU fault codes list must be used to determine the reason.

5.4.4 AMF Function


IMPORTANT: This chapter is relevant only for MPTM application.

For the InteliNeo6000 the AMF function is used only for automatic Mains failure and healthy detection. There is
no emergency start related to the technology when Mains fails because it is expected that renewables and BESS
are already running.
Related setpoints are:

AMF Timers AMF Settings


Mains Stabilization Delay (page 535) MCB Logic (page 367)
MCB Close Delay (page 535)

InteliNeo 6000 1.5.0 Global Guide 125


Mains failure detection
The Mains is considered as faulty when one or more of the following conditions are valid:
The Mains voltage is out of the limits given by the setpoints Mains <V (page 527) (Mains <<V (page
528)) and Mains >V (page 523)Mains >V (page 523)(Mains >>V (page 524)) for a time period longer
than Mains <V Delay (page 527) respectively Mains >V Delay (page 523) (Mains <<V Delay (page
529), Mains >>V Delay (page 525)).
The Mains voltage unbalance is out of limit given by setpoint Mains V Unbalance (page 530) for a time
period longer than Mains V Unbalance Delay (page 530).
The Mains frequency is out of the limits given by the setpoints Mains <f (page 533) (Mains <<f (page
534)) and Mains >f (page 531) (Mains >>f (page 532)) for a time period longer than Mains <f Delay
(page 533) respectively Mains >f Delay (page 531) (Mains <<f Delay (page 534), Mains >>f Delay
(page 532)).
The MCB close command was not successful and the alarm Wrn MCB Fail (page 1254) is present in the
alarmlist.
Alarm ALI Mains Ph Rotation Opposite (page 1275) is active.

Healthy Mains detection


The Mains is considered to be healthy when all of following conditions are valid:
The Mains voltage is within the limits given by the setpoints Mains <V (page 527) (Mains <<V (page
528)) and Mains >V (page 523)Mains >V (page 523)(Mains >>V (page 524)).
The mains voltage unbalance is within the limits given by the setpoint Mains V Unbalance (page 530).
The Mains frequency is within the limits given by the setpointsMains <f (page 533) (Mains <<f (page
534)) and Mains >f (page 531) (Mains >>f (page 532)).
The alarm Wrn MCB Fail (page 1254) is not present in the alarmlist.
Alarm ALI Mains Ph Rotation Opposite (page 1275) is not active.

5.4.5 Breaker Control


The following power switches are controlled by the controller:
The BESS Circuit Breaker or contactor – BCB
The PV Circuit Breaker or contactor – PVCB (breaker for renewables)
The Mains Circuit Breaker or contactor – MCB (see the chapter MCB special requirements (page 127))
The Neutral Contactor Breaker - NCB (see the chapter Neutral Contactor Breaker (page 129))
The closing of PVCB and BCB breakers is limited by precharge type of used inverters. It is expected that AC
precharge type is always used for the PV so the PVCB can be closed (synchronized) only if the bus is healthy
(there is AC voltage on the bus). The BESS inverter can use AC or DC precharge. For the AC option the
conditions are the same as for the PV. For the DC option the BCB can be closed to the dead bus or
synchronized to the healthy bus. See more information in the chapter BESS Precharge Types (page 245).
It is possible to use either a motorized circuit breaker or contactor. Below is a list of available control outputs
that should fit all types of contactors or breakers. The following rules must be kept to when designing the
wiring of power switches:
The control outputs must be configured and wiring of the power switches must be provided in such a way,
that the controller has full control over the breakers – i.e. the controller can open and close the breaker at
any time.

InteliNeo 6000 1.5.0 Global Guide 126


The breaker must respond within max. 2 seconds to a close and open command. Special attention should
be paid to opening of motorized circuit breakers, as it could take more than 2 seconds on some types. In
such cases it is necessary to use an undervoltage coil for fast opening.
After opening the breaker, there is internal delay for another closing of breaker. Delay is 6 seconds - 5
seconds for OFF coil and 1 second for UV coil. After these 6 seconds, breaker can be closed again. For
opening of breaker there is no delay.

Breaker control outputs

An output for control of a contactor. Its state represents the breaker position requested
Close/Open by the controller. The breaker must react within 2 seconds to a close or open command,
otherwise an alarm is issued.
An output giving a 2 second pulse in the moment the breaker has to be closed. The
ON coil
output is intended for control of close coils of circuit breakers.
An output giving a pulse in the moment the breaker has to be opened. The pulse lasts
OFF coil until the feedback deactivates, but at least for 2 seconds. The output is intended for
control of open coils of circuit breakers.
The BCB UV coil output is active the whole time the BESS is running. The MCB and
PVCB UV coil output is active when the controller is switched on. The output is
UV coil
deactivated for at least 2 seconds in the moment the breaker has to be switched off. The
output is intended for cont rol of undervoltage coils of circuit breakers.

Image 5.57 Breaker control outputs

MCB special requirements


If a contactor is used on the MCB position, it is recommended that the wiring be provided in such a way
that the contactor will be normally closed and will open if the logical binary output MCB CLOSE/OPEN
(PAGE 1090) closes. This behavior is called "negative logic" and can be adjusted by the setpoint MCB
Logic (page 367). The negative logic will prevent accidental opening of the MCB when the controller is
switched off.

InteliNeo 6000 1.5.0 Global Guide 127


Breaker fail detection
Breaker fail detection is based on binary output breaker close/open comparing with binary input breaker
feedback. If breaker feedback is not configured and breaker control mode is internal, the alarm will be activated
always because the change of the breaker close/open will not be followed by breaker feedback.
There is an exception for the MCB breaker. If the breaker feedback indicates the MCB has unexpectedly opened
without any command given by the breaker close/open the controller will accept it and following behavior will
depend on Mains condition. The MCB breaker stay opened if Mains fails or is closed if Mains is healthy.
There are three different alarm types, see following diagrams.
When binary output breaker close/open is in steady state and breaker feedback is changed the breaker
fail is detected immediately without delay and alarm Stp BCB Fail (page 1290) is issued. The alarm is
issued also after 500 ms when there is mismatch of LBI BCB FEEDBACK (PAGE 991) and LBI BCB
FEEDBACK NEGATIVE (PAGE 992) . Except opening of MCB.

Image 5.58 Breaker fail - breaker close/open in steady position - open

Image 5.59 Breaker fail - breaker close/open in steady position - close

When binary output breaker close/open is opened, there is 2 seconds waiting time for feedback If
feedback doesn't match, the alarm Sd BCB Fail To Open (page 1291)/Wrn MCB Fail To Open (page
1256) is issued.

InteliNeo 6000 1.5.0 Global Guide 128


Image 5.60 Breaker fail - breaker close/open opens

When binary output breaker close/open is closed there is 2 seconds waiting time for feedback. If the
feedback doesn't match the output, close/open is opened and closed again after delay defined by setpoint
Delay Between Closing Attempts (page 370). If feedback doesn't match after second try and 2 seconds
delay elapsed, the alarm Sd BCB Fail To Close (page 1291)/Wrn MCB Fail To Close (page 1255) is
issued.

Image 5.61 Breaker fail - breaker close/open closes

Note: In case of using both feedbacks (standard and negative), both of them have to be in correct position,
otherwise breaker fail is issued after 500 ms.

A new alarm ALI GCB Closing Is Blocked (page 1) is activated in case Setpoint BCB Control Mode
(page 369) is set to Internal and any of following generator protections are switched to Disabled
Generator <f Protection
Generator >f Protection
Generator <V Protection
Generator >V and >>V Protection (both overvoltage must be disabled)
Short Circuit Protection

Neutral Contactor Breaker


Note: This chapter is common for Gen-sets and BESS.

InteliNeo 6000 1.5.0 Global Guide 129


The neutral contactor is used to connect the neutral wire (N) with the protective wire (PE) in a TN-S system. This
connection is used to ground the parasitic capacities and inductions and at one moment there can be only one
connection like this in the whole electric circuit. So, once the Site is connected to the Mains, the Site NCB must
be opened because the Mains has its own grounding.
For the MINT application there are two possible ways how to use the NCB. The first option is having a NCB for
each unit in the system, the second option is having one common NCB for all units in the system. The setpoint
#Neutral Contactor Control (page 362) is used to choose if EACH or COMMON behavior of the NCB will be
used.
For the MPTM application the NCB works like there is one common NCB for whole MPTM system.
Note: The information mentioned in the breaker control outputs and fail detection chapters above are not
related to the NCB breaker. The NCB has only one avialable output (Close/Open) and only basic NCB fail
detection without repeated command for breaker closing.

EACH
The EACH option should be used if each Gen-set has its own neutral contactor. The NCB CLOSE/OPEN (PAGE
1094) output on each Gen-set is given by an internal algorithm, which ensures, that always exactly one Gen-
set connected to the bus with the lowest CAN address has the neutral contactor closed.
Four-pole MCB, MGCB, and GCBs have to be used in this case - all running Gen-sets that are not
connected to the bus have their own NCB closed.
The output is always opened while the Gen-set is not running.
The output is always opened while the MCB + MGCB (only for MGCB application) + GCB are closed
(Genset is running parallel to Mains).
The output is closed while the Gen-set is running and at least one Generator Ph-Ph voltage exceeds 85%
of the nominal voltage. It opens when the generator voltage in all phases drops below 50% of the nominal
voltage.

Image 5.62 NCB wired for each Gen-set

InteliNeo 6000 1.5.0 Global Guide 130


COMMON
The COMMON option should be used if there is only one common neutral contactor for the whole site. The
NCB CLOSE/OPEN (PAGE 1094) outputs from all controllers are combined together and the combined signal is
used to control the breaker. If at least one Gen-set in the site is running and has a proper voltage, the neutral
contactor is closed.
Four-pole MCB, MGCB, and three-pole GCBs have to be used in this case - all running Gen-sets
with open GCB (not connected to the bus) must be connected to the common neutral contactor.
The output is always opened while the Gen-set is not running.
The output is always opened while the MCB + MGCB (only for MGCB application) are closed.
The output is closed while the Gen-set is running and at least one Generator Ph-Ph voltage exceeds 85%
of the nominal voltage. It opens when the generator voltage in all phases drops below 50% of the nominal
voltage.

Image 5.63 One common NCB wired for all Gen-sets

Note: LBI NCB FEEDBACK (PAGE 1015) and LBO NCB CLOSE/OPEN (PAGE 1094) has to be configured for
proper functionality.

Note: For both option the MGCB is taken in account only if there is any extra breaker between GCB and the
MCB.

5.4.6 CAN Bus Log


This function is used to log communication between the CU, ECU, and I/O modules on the CAN line. These logs
can be shared with our technical support and used for solving specific problems. The CAN Bus Log uses CAN2B
(page 19) which should be physicality connected to the observed CAN. The CAN2B (page 19) will works as
another device on the CAN line and it is necessary to do wiring in accordance with rules for wiring the CAN line.
IMPORTANT: The bus must be wired in linear form with termination resistors at both ends. No
nodes are allowed except on the controller terminals.

InteliNeo 6000 1.5.0 Global Guide 131


IMPORTANT: The CAN bus log works only if CAN Intercontroller Communication Redundancy is
not used.

To activate the CAN bus log function, go to the Tools in InteliConfig and press the button CAN Bus Log to open
the settings. You need to log in as at least a level 2 user. In the settings, you will choose the Output directory in
your PC, the Logging option (CAN for modules + communication speed or type of the Intercontroller CAN), and
press Start. The Logging status will be changed from Logging is stopped to Logging is running.

5.4.7 CAN Intercontroller Communication


CAN Intercontroller Communication is used for sharing information (data needed for regulations, power
management, shared signals, etc.) between ComAp controllers via CAN interface.
This communication is present on ⑧ CAN2A (page 46). In case of using CAN Intercontroller Communication
Redundancy (page 132), then the redundant communication is present on ⑦ CAN2B (page 46) .
The communication can run in different modes. Select your required mode by setpoint CAN Intercontroller
Comm Mode (page 397). The mode is changed only during powering up of the controller and actual mode is
stored in value CAN Intercontroller Comm Mode (page 888). In case that there is a mismatch between the
setpoint and the value, alarm ALI CAN Mode Inconsistency (page 1271) is activated. Restart the controller to
change the communication mode to the selected mode and to get rid of the alarm.
For easy detection of empty CAN you can set CAN Intercontroller Empty Check (page 398) to Enabled. Wrn
CAN2 Empty (page 1250) is activated every time when controller doesn't see any other controller connected via
⑧ CAN2A (page 46) and ⑦ CAN2B (page 46) (if the redundancy is used).
IMPORTANT: Options 64C CAN FD or 32C CAN FD or 8C CAN FD are compatible only with
controllers which support the CAN FD communication. Set correct mode by setpoint CAN
Intercontroller Comm Mode (page 397) otherwise controller will not communicate with each other.

Relevant setpoints
CAN Controller Address (page 392)
CAN Intercontroller Comm Mode (page 397)
Usage
Power Management (page 274)
Power Management (page 274)
Power Management (page 274)
Power Management (page 274)
MINT - Load Sharing, Var Sharing, and Shared signals

CAN Intercontroller Communication Redundancy


IMPORTANT: This is a premium function which requires SW Key in order to be used!

This function duplicates whole Intercontroller communication, which is on CAN2A (page 19) and sends it via
CAN2B (page 19).
The same wiring principles apply to CAN2B (page 19) as to CAN2A (page 19) (see CAN bus wiring (page
71)).

InteliNeo 6000 1.5.0 Global Guide 132


Step by step guide
Note: Following steps have to be done for each controller in the system.

1. Insert the SW Key (page 388) for CAN Intercontroller Redundancy


2. Restart the controller
3. Check the value SW Key Feature List (page 891) - CAN Intercontroller Redundancy has to be
enabled
4. Switch the setpoint CAN Intercontroller Comm Redund (page 396) to Enabled
5. Restartthe controller
6. Check that the value CAN Intercontroller Comm Redundancy (page 888) is Enabled
In case of mismatch between the value CAN Intercontroller Comm Redundancy (page 888) and the setpoint
CAN Intercontroller Comm Redund (page 396), alarm ALI Redundant CAN Error (page 1273) is raised.
In case of inconsistency of data on ⑧ CAN2A (page 46) and ⑦ CAN2B (page 46) line, alarm Wrn Redundant
CAN inconsistency (page 1264) is activated
In case of attempt to use this function without of valid SW Key alarm Wrn SW Key CAN Redundancy Error
(page 1267) is activated. See chapter SW Key Features (page 219) for more information.
Note: It is also possible to use CAN Intercontroller Communication Redundancy if there is a ComAp
controller in the system, wich does not support this feature (e.g. IM1010 + IG1000 + IGS-NT generation
controller). The redundancy will work (for the IG1000 and IM1010 controllers), but there will be Wrn
Redundant CAN inconsistency (page 1264) alarm active (because of the IGS-NT controller which doesn't
support the redundancy).

5.4.8 CAN1 ECU/IO Modules Splitting


This function allows the user to change the behavior of CAN1 communication terminals.
In default configuration:
CAN1A terminal is used for communication with ECU and IO Modules.
CAN1B terminal is used for Hot Swap Redundancy (page 160)

InteliNeo 6000 1.5.0 Global Guide 133


Image 5.64 Hot Swap Redundancy connection

If the setpoint CAN1 ECU/IOModules Split (page 402) is enabled, the behavior of CAN1A terminal is changed:
CAN1A terminal can be used only for communication with ECU
CAN1B terminal can be used only for communication with IO Modules

IMPORTANT: In case that CAN1 ECU/IOModules Split (page 402) is enabled, the Hot Swap
Redundancy (page 371) is disabled (and vice versa).

Image 5.65 CAN1 ECU/IO Modules Split connection

Note: The splitting of CAN1 enables to prevent overloading the bus line.

InteliNeo 6000 1.5.0 Global Guide 134


5.4.9 Configuration Lock
The Configuration lock function allows the user to lock the the Controller Configuration by the password and
encrypt the PLC data. The Controller Configuration can be locked by the checkbox Configuration Lock inside of
the Controller Configuration next to the button Consistency check. Once the checkbox is hit, the user will be
asked for the password, after this step all PLC data will be encrypted. Once the user will try access to the locked
Controller Configuration, the InteliConfig will automatically ask the user for the password. If the correct password
is submitted the Controller Configuration will be unlocked and PLC data decrypt. Without correct password the
user cannot open the Controller Configuration and see configuration in it.

Image 5.66 Configuration lock

5.4.10 Configuration Override


There may appear a situation, when controller reprogramming is not possible for some reason. The typical
example is a situation, when the controller is configured to be always in Remote AUT mode. So, the controller
cannot be switched to OFF mode to change the configuration. To enable controller configuration change in these
cases, the InteliNeo 6000 is offering a DIP switch located under the front cover of the controller. If the switch is
enabled the controller configuration is forced to the invalid state so it is possible to upgrade the controller's FW or
import new configuration. The older controllers are using the boot jumper to do the same thing and it is called
"Boot Jumper Programming" or "Unsuccessful Controller Programming".

Process of configuration overriding


Remove front cover of InteliNeo 6000
Enable the DIP switch
Restart the controller
Connect to the controller via InteliConfig
Log-in as level 3 user
Go to the Control and Import new configuration (button Configuration Import)
Disable the DIP switch
Restart the controller

InteliNeo 6000 1.5.0 Global Guide 135


Image 5.67 Location of the DIP switch for Configuration override

5.4.11 Control Groups


Note: This chapter is relevant for all ComAp controllers working in Multiple Island-Parallel operation.

The physical group of the controllers (i.e. the site) can be separated into smaller logical groups, which can work
independently even if they are interconnected by the CAN2 bus. The logical groups are intended to reflect the
real topology of the site when the site is divided into smaller groups separated from each other by bus-tie
breakers. If the bus-tie breakers are closed the sub-groups have to work as one large group (system) and if the
bus-tie breakers are open, the sub-groups have to work independently.
The group which the particular controller belongs to is adjusted by the Control Group (page 516). Use
the default setting 1 with all controllers, if there is no bus-tie breaker.
The information which groups are currently linked together is being distributed via the CAN. Each
controller can provide information about one BTB breaker. The breaker position is detected by the input
function GroupLink (i.e. this input is to be connected to the breaker feedback).
The two groups which are connected together by the BTB, are defined with parameters Group Link L
(page 517) and Group Link R (page 517).
Controller sends via CAN2A (page 19) (CAN2B (page 19)) bus information that controllers from groups
Group Link L and Group Link R are linked together.
If external BTB is used (there is no CAN communication between external BTB and other controllers) or in
case of redudant information about BTB position is required , the Group link function in any ComAp
controller can be used. If the LBI GROUP LINK (PAGE 1004) is activated the controller will send information
to all controllers on CAN that the groups defined by setpoints Group Link L (page 517) and Group Link
R (page 517) are connected together.
A history record is written into every controller that is affected by the group link whenever the BTB is
closed / opened (control groups are linked / unlinked).
Note: The "group link" function is independent on the group, where the controller itself belongs to. The controller
can provide "group link" information about any two groups and it may not belong to one of the groups.

All controllers in linked groups cooperate with each other and perform Power Management, Load sharing
and VAr sharing together. Thementioned functions are performed independently in each group, when the
groups are separated.

InteliNeo 6000 1.5.0 Global Guide 136


Example: 4 controllers separated by a BTB breaker into two groups of 2. The BTB position is detected by
the controllers 2 and 3. The reason, why there are 2 controllers used for detection of the BTB position, is to
have a redundant source of the group link information, if the primary source (controller) is switched off.

Image 5.68 Example of control groups

Once the BTB breaker is closed, the control groups 2 and 3 become new group 2+3. Power management, Load
sharing and VAr sharing are performed within newly established group 2+3. Merging of the groups may result in
a BESS/BESS stopping, if power management evaluates that available Actual Reserve is high enough to stop a
BESS/BESS.

5.4.12 Crash Dump


Crash dump is new functionality which allows controller to collect and store important information related to
controller's failure before the controller is restarted. These information are stored in controller's nonvolatile
memory for later evaluation and easier solution of a problem.

Collecting crash dump


To collect Crash Dump from the controller, you need to connect to the controller using InteliConfig either via USB
(page 112) or Ethernet (page 113).
Log in as user with administrator rights.

In top right corner click wrench icon and select "Collect logs".
InteliConfig begins to collect Crash Dump data from the controller and also adds its own crash logs. User
is informed about the ongoing process in InteliConfig, before prompt to save *.zip file appears.

InteliNeo 6000 1.5.0 Global Guide 137


Image 5.69 Crash Dump Collection

Note: It is recommended to use connection via Ethernet to reduce time required for data collection.

IMPORTANT: This action may take significantly long period.

Contacting TSUP with crash dump


After collection of Crash Dump, you shall contact TSUP. To help resolve your issue:
Send description of the issue from your side of view
Send approximated time of the event
Send Crash Dump data collected in *.zip file

5.4.13 Distributed Power Management Signals


Note: This chapter is relevant for all ComAp controllers working in Multiple Island-Parallel operation.

Note: In case the InteliNeo6000 cooperates with controllers which CAN Intercontroller Comm Mode (page
397) doesn't support 64C CAN FD, the maximum units in power management is 32.

Signals which are considered to be visible the same way for every controller on CAN. Synchronization of these
signals is the internal part of the Power management function.
Basic principle:
For every signal, there is a LBI with the same function as the signal.
If the LBI is not configured on any input (physical binary, virtual in PLC etc.), its value is taken from CAN
and the value is not being shared back on CAN.
If the LBI is configured, its value is taken from the input and the value is shared on CAN.
The relevant function is activated only by the state of the signal, which is configured on LBI. That
means that function cannot be activated by the state of relevant CAN signal.
In case of the collision, there is a predefined behavior. If any controller with configured LBI receives a
logical "1", it then activates the signal on CAN.
Distributed Power Management Signals are shared only in the scope of logical Control Groups (page
136). If you merge Control Groups together (GROUP LINK (PAGE 1004)), signals are applied in both groups.
The BTB controller is used to connect the groups together. When the Bus Tie Breaker is closed the BTB
informs appropriate controllers that their groups has been connected.

InteliNeo 6000 1.5.0 Global Guide 138


Description for the BESS/Microgrid
Distributed signal Description for Mains controller
controller (MINT application)
LBI GENERIC GENSET Accepted only in controllers
START/STOP (PAGE 1004) is the belonging to the same logical
request to start the group (part group.
of the system). It is shared to Accepted only in controllers where
System Start/Stop LBO System Start/Stop and the Distributed signal is not
distributed trough CAN2A configured.
(page 19) or CAN2B (page 19) If the Distributed signal is
to the controllers in the same
configured to any binary input
group.
(physical or virtual), the signal is
automatically shared to other
Min Run Power 1, controllers via CAN2A (page 19) or
2, 3 CAN2B (page 19) as CAN
Distributed signal.
N/A
If distributed signal is shared on
Load Reserve 1, 2, CAN2A (page 19) or CAN2B
3, 4 (page 19) by more sources, it is
accepted from any of them.
The Mains controller set this
Accepted only in controllers
signal on whenever there is a
belonging to the same logical group
closed path between the Mains
as the source Mains Controller only.
MCB Feedback and the Load side.
Accepted only in controllers where
The signal is shared only inside
the Distributed signal is not
the logical group (or
configured.
interconnected logical groups).

InteliNeo 6000 1.5.0 Global Guide 139


Distributed
Scheme for Mains + Gen-set/Microgrid controllers
signal

System
Start/Stop

Min Run
Power 1, 2, 3

Load Res 1,
2, 3, 4

Sharing of multiple Logical Binary Input (LBI) functions is critical for power management system operation,
because several power management functionality require simultaneous activation of LBI functions in controllers,
which are involved in power management operation. It can be done either automatically using CAN2A (page 19)
(CAN2B (page 19)) bus link between controllers or using dedicated LBI functions.
These LBI functions are shared automatically:
System Start/Stop
Min Run Power Act
Load Res Active
MCB Feedback
The following rules applies to the automatic sharing of the selected signals between Mains / Gen-set /
Microgrid controllers.

InteliNeo 6000 1.5.0 Global Guide 140


1. LBI state is automatically shared via CAN2A (page 19) (CAN2B (page 19)) bus, if corresponding LBI
function is not configured in a controller.
Example: Logical input Remote Start/Stop is configured with a controller. State of the signal is
automatically transmitted to other controllers via CAN2A (page 19) (CAN2B (page 19)) bus as System
Start/Stop.

Image 5.70 Distributed signals case 1

2. LBI state received from CAN2A (page 19) (CAN2B (page 19)) bus is automatically used, if corresponding
LBI function is not configured in a controller.
Example: LBI Remote Start/Stop is not configured with a controller, but automatically shared System
Start/Stop is received from CAN2A (page 19) (CAN2B (page 19)) bus. Controller follows state of the
shared LBI signal then.

Image 5.71 Distributed signals case 1&2

InteliNeo 6000 1.5.0 Global Guide 141


3. LBI state received from CAN2A (page 19) (CAN2B (page 19)) bus is not used, if corresponding LBI
function is configured in a controller.
Example: LBI Remote Start/Stop is configured with a controller. Controller follows only state of signal
linked with the Remote Start/Stop function. The function is not activated by a shared System Start/Stop
signal.

Image 5.72 Distributed signals case 3

InteliNeo 6000 1.5.0 Global Guide 142


4. LBI function state transmitted via CAN2A (page 19) (CAN2B (page 19)) bus is used only by controllers,
which are in the same group as controller, which is source of the shared signal. Signal coming from controller
in a different group is accepted only if the “source controller” group is linked with the “receiving controller”
group.

Image 5.73 Distributed signals case 4

5. LBI function can be configured with multiple controllers, which transmit through CAN2A (page 19) (CAN2B
(page 19)) bus state of the function. Or function applies to the function evaluation in controllers, in which the
function is not configured. It means that function is activated by shared signal coming from any controller (rule
4. applies).

5.4.14 E-STOP
The E-Stop is mainly used for emergency stop of the BESS but it is also used as power supply for binary outputs
1 and 2. These binary outputs are designated for some essential functions and they are internally wired as "safe".
It means, that their deactivation is directly binded with the dedicated Input ㉓ E-STOP (page 47) (not evaluated
as the LBI in the controller). These outputs are fully configurable and in the default configuration are used for the
BESS Run Request.
The emergency stop circuit must be secured.
No accidental activation on the PCB can disable the operation of the emergency stop.
The power supply of the associated binary outputs (BOUT1 and BOUT2) is supplied by the ㉓ E-STOP
(page 47) input, not by the + battery voltage.

InteliNeo 6000 1.5.0 Global Guide 143


Note: There is no difference in the way of configuration of all binary outputs. Binary output BO2
(BESS Run Request) is intended for this function (not dedicated).

The CU is measuring actual input voltage of the E-STOP which activation level depends on the actual controller
supply voltage (battery voltage). The E-STOP is activated if input voltage drops below approximately 60 % of the
Controller supply voltage.

Image 5.74 SW principle of E-STOP

If the input voltage of E-stop is higher than high comparison level (for ex. higher than 80% of the supply
voltage), then E-stop is not activated.
If the input voltage of E-stop is lower than low comparison level (for ex. lower than 60% of the supply
voltage), then E-stop is activated.
If the input voltage of E-stop is located somewhere between low and high comparison levels (for ex.
between 60 and 80 %of the supply voltage, then E-stop binary value will stay on its previous state (means
E-stop binary value will not change).
Visualization on CU screen
1
㉓ E-STOP (page 47) has voltage - state is OK, BO1 and BO2 can be activated
0
㉓ E-STOP (page 47) has no voltage - E-STOP (page 1280) is active, BO1 and BO2 cannot be
activated
For wiring information see E-Stop on page 66.

InteliNeo 6000 1.5.0 Global Guide 144


5.4.15 Event History
The history log is an area in the controller’s non-volatile memory that records “snapshots” of the system at
moments when important events occur. The history log is important especially for diagnostics of failures and
problems. When the history file is full, the oldest records are removed.
Each record has the same structure and contains:
The event which caused the record (e.g. Overfrequency alarm, undervoltage alarm, MCB closed, BCB
closed, etc.).
The date and time when it was recorded.
All important data values like frequency, kW, voltages, etc. from the moment that the event occurred.
The number of events is fixed to 1000 lines.
Values are recorded based on actual column selected, on special events values are recorded in text form.
Special events:
When the user logs in

Modifying a setpoint

Fault Reset

Horn Reset

Start/Stop

Configurable history
It is possible to configure the columns (values) which will be displayed in the History window. The
configuration can be found in the Controller Configuration → Others → History. See the picture below.

Image 5.75 Configurable history

In the left part of the configuration window there are all available binary and analog values (columns) which
can be configured to history event log. In the right side of the configuration window there is a table with all
already configured columns. By buttons Add and Remove in the middle of the configuration window or by

InteliNeo 6000 1.5.0 Global Guide 145


double click on value in the left / right part of the configuration, it is possible to add / remove any analog or
binary value to / from the history event log.
Under the table with already configured values there are buttons for the operations. By the buttons Move up
and Move down it is possible to change the position of the history columns so you can sort all columns
according to your priorities. Next to these buttons there are buttons for export and import data so you can
import history columns configuration from another controller. And it is also possible to change the
abbreviation for each history column. In the down part of the configuration window there is a progress bar
which shows how much memory for history events is used. For one history record maximum 499 Bytes can
be used.
In the next chapter are shown history columns used in the default archive.

InteliNeo 6000 1.5.0 Global Guide 146


Default history columns
Category Column Name Value Unit
Info Mode Controller Mode (page 885) -
Controller I/O VBat Battery Voltage (page 867) V
Pwr BESS P (page 707) kW
Pwr1 BESS P L1 (page 707) kW
Pwr2 BESS P L2 (page 707) kW
Pwr3 BESS P L3 (page 707) kW
Q BESS Q (page 708) kVAr
Q1 BESS Q L1 (page 708) kVAr
Q2 BESS Q L2 (page 708) kVAr
Q3 BESS Q L3 (page 708) kVAr
PF BESS Power Factor (page 710) -
LChr BESS Load Character (page 710) -
PF1 BESS Power Factor L1 (page 710) -
LCh1 BESS Load Character L1 (page 710) -
PF2 BESS Power Factor L2 (page 710) -
BESS LCh2 BESS Load Character L2 (page 711) -
PF3 BESS Power Factor L3 (page 711) -
LCh3 BESS Load Character L3 (page 711) -
Gfrq BESS Frequency (page 713) Hz
Vg1 BESS Voltage L1-N (page 713) V
Vg2 BESS Voltage L2-N (page 713) V
Vg3 BESS Voltage L3-N (page 713) V
Vg12 BESS Voltage L1-L2 (page 713) V
Vg23 BESS Voltage L2-L3 (page 714) V
Vg31 BESS Voltage L3-L1 (page 714) V
IL1 BESS Current L1 (page 715) A
IL2 BESS Current L2 (page 715) A
IL3 BESS Current L3 (page 715) A
IEFC Earth Fault Current (page 716) A

InteliNeo 6000 1.5.0 Global Guide 147


Category Column Name Value Unit
Mfrq Mains/Bus Frequency (page 839) Hz
Vm1 Mains/Bus Voltage L1-N (page 839) V
Vm2 Mains/Bus Voltage L2-N (page 839) V
Vm3 Mains/Bus Voltage L3-N (page 840) V
Vm12 Mains/Bus Voltage L1-L2 (page 840) V
Vm23 Mains/Bus Voltage L2-L3 (page 840) V
Mains/Bus
Vm31 Mains/Bus Voltage L3-L1 (page 840) V
Im Mains L1 Current (page 842) A
PwrM Mains Import P (page 842) kW
Qm Mains Import Q (page 843) kVAr
PFm Mains PF (page 845) -
LChm Mains Load Character (page 845) -
Pld Load P (page 828) kW
Qld Load Q (page 828) kVAr
Load
PFld Load Power Factor (page 828) -
LCld Load Character (page 828) -
Ain1 CU-AIN-01 (page 867) -
Ain2 CU-AIN-02 (page 867) -
Ain3 CU-AIN-03 (page 868) -
Controller I/O Ain4 CU-AIN-04 (page 868) -
BIN Binary Inputs (page 868) -
ESTP E-STOP (page 869) -
BOUT Binary Outputs (page 869) -
Frequency/Load Control SRO Frequency Regulator Output (page 862) V
Voltage/PF Control VRO Voltage Regulator Output (page 866) V
Forced Values Status FVST Forced Value Status (page 890) -
PoF P Over Frequency Curve (page 829) %
PuF P Under Frequency Curve (page 830) %
Qum Q(Um) Curve (page 830) kVAr
QrUl Qref/Ulim Curve (page 830) kVAr
Q(P) Q(P) Curve (page 831) kVAr
Grid Codes
PFp PF(P) Curve (page 831) -
Red1 Load Reduction 1 Occurrence (page 832) -
Red2 Load Reduction 2 Occurrence (page 832) -
Red3 Load Reduction 3 Occurrence (page 832) -
Red4 Load Reduction 4 Occurrence (page 833) -

InteliNeo 6000 1.5.0 Global Guide 148


Category Column Name Value Unit
Prio Engine Priority (page 856) -
ResA Actual Reserve (page 856) kW
TRPN Running Nominal Power Of All (page 859) kW
Power Management
APN Available Nominal Power (page 859) kW
Minimal Running Nominal Power (page
Pmin kW
859)

Premortem History
The fast history running in background is mirrored into the controller history records when a second level alarm
occurs. Premortem history contains the same values in the history as the configuration done by configuration
tool. When any new alarm appears for the second time, only the new history records are added into the controller
history log. Premortem History is filled in to internal buffer (16kB) and number of premortem records depends on
how many history columns is configured. Example: for default History columns it can be up to 85 premortem
records, for maximal History columns can be saved in to buffer at least 32 records.
The time of the premortem history is adjustable by a setpoint Premortem History Period (page 631)

5.4.16 Exercise Timers


Mode Once 151
Mode Daily 152
Mode Weekly 153
Monthly mode 154
Mode Short period 156
The exercise (general-purpose) timers in controller are intended for scheduling of any operations such as e.g.
periodic tests of the BESS, scheduled transfer of the Load to the BESS prior to an expected disconnection of the
Mains etc. These timers can be also used in the PLC.
The function of each timer can be changed by respective Timer Function setpoint. The functions which are
supposed to change the Controller Mode requires controller running in AUTO mode. The following timer
functions are available:
Disabled - The Timer is disabled.
Manual On - The Timer is disabled but his binary output is activated (can be used for testing purposes).
No Func - There is no any other function, only binary output of the Timer is activated once the condition is
fulfilled.
Mode OFF - The binary output of the Timer is internally connected to the Remote OFF binary input.
The activation condition of each Timer is configured via respective Timer Setup setpoint.
Each Timer has its LBO Exercise Timer which is closed regardless of chosen timer function once the Timer is
activated. If the CU is switched off when the Timer should be activated, the Timer will be activated immediately
after the CU is switched on if the Timer condition is still fulfilled. The LBO is activated always when the Timer
should be activated e.g. even when controller is in different mode than AUTO.
See the list of related setpoints and LBOs below.

Related setpoints for choosing of the timer function: Related setpoints for the timer setup:
Timer 1 Function (page 633) Timer 1 Setup (page 634)

InteliNeo 6000 1.5.0 Global Guide 149


Timer 2 Function (page 635) Timer 2 Setup (page 636)
Timer 3 Function (page 637) Timer 3 Setup (page 638)
Timer 4 Function (page 639) Timer 4 Setup (page 640)
Timer 5 Function (page 641) Timer 5 Setup (page 642)
Timer 6 Function (page 643) Timer 6 Setup (page 644)
Timer 7 Function (page 645) Timer 7 Setup (page 646)
Timer 8 Function (page 647) Timer 8 Setup (page 648)
Timer 9 Function (page 649) Timer 9 Setup (page 650)
Timer 10 Function (page 651) Timer 10 Setup (page 652)
Timer 11 Function (page 653) Timer 11 Function (page 653)
Timer 12 Function (page 655) Timer 12 Setup (page 656)

Related LBOs:
Exercise Timer 1 (page 1077) Exercise Timer 7 (page 1078)
Exercise Timer 2 (page 1077) Exercise Timer 9 (page 1079)
Exercise Timer 3 (page 1077) Exercise Timer 9 (page 1079)
Exercise Timer 4 (page 1078) Exercise Timer 10 (page 1079)
Exercise Timer 5 (page 1078) Exercise Timer 11 (page 1080)
Exercise Timer 6 (page 1078) Exercise Timer 12 (page 1080)
Exercise Timer 7 (page 1078)
Exercise Timer 9 (page 1079)

Related Values:
Exercise Timer 1 (page 902) Exercise Timer 7 (page 904)
Exercise Timer 2 (page 903) Exercise Timer 9 (page 1079)
Exercise Timer 3 (page 903) Exercise Timer 9 (page 904)
Exercise Timer 4 (page 903) Exercise Timer 10 (page 905)
Exercise Timer 5 (page 903) Exercise Timer 11 (page 905)
Exercise Timer 6 (page 904) Exercise Timer 12 (page 905)

InteliNeo 6000 1.5.0 Global Guide 150


Note: This manual shows step by step guide only for Timer 1 setup because the procedure is same for the all
timers.

Available modes of each timer:


This is a single shot mode. The timer will be activated only once at preset date/time for
Once
preset duration.
The timer is activated every "x-th" day. The day period "x" is adjustable. Weekends can be
Daily excluded. E.g. the timer can be adjusted to every 2nd day excluding Saturdays and
Sundays.
The timer is activated every "x-th" week on selected weekdays. The week period "x" is
Weekly
adjustable. E.g. the timer can be adjusted to every 2nd week on Monday and Friday.
The timer is activated every "x-th" month on the selected day. The requested day can be
Monthly selected either as "y-th" day in the month or as "y-th" weekday in the month. E.g. the timer
can be adjusted to every 1st month on 1st Tuesday.
Short The timer is repeated with adjusted period (hh:mm). The timer duration is included in the
period period.

Mode Once
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.

Image 5.76 Mode Once - InteliConfig

InteliNeo 6000 1.5.0 Global Guide 151


In timer mode select Once. In timer settings adjust date and time of occurrence of timer. Also adjust the duration
of timer.

Set-up via external display


Navigate to the Scheduler setpoint group. Select the function of timer via Timer 1 Function (page 633) setpoint.
Then go to Timer 1 Setup (page 634) and press enter button.
Note: Use left and right arrow to move in a single row. Use up and down arrow to adjust time or date. Use
enter button for confirmation.

6 back to Exercise Timers

Mode Daily
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634)
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.

Image 5.77 Daily mode - InteliConfig

In timer mode select Repeat. In repetition type select Daily. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th day of repetition
and behavior of timer on weekends.
Example: On image example first start of timer will be 2015-01-01 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 3rd day at 12:00 for 5 minutes including weekends.

InteliNeo 6000 1.5.0 Global Guide 152


Set-up via external display
Navigate to the Scheduler setpoint group. Select the function of timer via Timer 1 Function (page 633) setpoint.
Then go to Timer 1 Setup (page 634) and press enter button.
Select mode Repeat and confirm it. After that, you will set the first occurrence date, time of occurrence and
duration. Select Daily occurrence, set amount of days between occurrences and decide which behavior shall be
applied during weekends.
Note: Use left and right arrow to move in a single row. Use up and down arrow to adjust time or date. Use
enter button for confirmation.

6 back to Exercise Timers

Mode Weekly
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.

Image 5.78 Mode Weekly - InteliConfig

In timer mode select Repeat. In repetition type select Weekly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th week of repetition
and days when timer should be active.
Example: On image example first start of timer will be 2015-01-12 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 2nd week on Monday, Wednesday and Friday at 12:00 for 5 minutes.

InteliNeo 6000 1.5.0 Global Guide 153


Set-up via external display
Navigate to the Scheduler setpoint group. Select the function of timer via Timer 1 Function (page 633) setpoint.
Then go to Timer 1 Setup (page 634) and press enter button. Select mode Repeat and confirm it. After that, you
will set the first occurrence date, time of occurrence and duration. Select Weekly occurrence, set amount of
weeks between occurrences and select days which will be timer triggered (use arrows left, right for
activating/deactivating of day and arrow up, down for moving to another day).
Note: Use left and right arrow to move in a single row. Use up and down arrow to adjust time or date. Use
enter button for confirmation.

6 back to Exercise Timers

Monthly mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.

There are two types of monthly repetition. First of them is based on repeating one day in month.

Image 5.79 Mode Monthly - InteliConfig

In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition and the x-th day of repetition. Than select the x-th month of repetition.
Example: On image example first start of timer will be 2015-01-02 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 2nd day in 2nd month at 12:00 for 5 minutes.

InteliNeo 6000 1.5.0 Global Guide 154


Second type of monthly repetition is based on repeating days in week in month.

Image 5.80 Mode Monthly - InteliConfig

In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition, the x-th week of repetition and days in week. Than select the x-th month of repetition.
Example: On image example first start of timer will be 2015-01-05 at 12:00. Duration will be 5 minutes.
Timer will be again activated every 2nd week in 2nd month on Monday, Wednesday and Friday at 12:00
for 5 minutes.

Set-up via external display


There are two types of monthly repetition. First of them is based on repeating one day in month.
Navigate to the Scheduler setpoint group. Select the function of timer via Timer 1 Function (page 633) setpoint.
Then go to Timer 1 Setup (page 634) and press enter button. Select mode Repeat and confirm it. After that, you
will set the first occurrence date, time of occurrence and duration. Select Monthly occurrence, then Daily and
choose which day in a month will be timer triggered. Set amount of months between occurrences and confirm the
selection
Second type of monthly repetition is based on repeating days in week in month.
Navigate to the Scheduler setpoint group. Select the function of timer via Timer 1 Function (page 633) setpoint.
Than go to Timer 1 Setup (page 634) and press enter button. Select mode Repeat and confirm it. After that, you
will set the first occurrence date, time of occurrence and duration. Select Monthly occurrence, then Weekly and
choose which week and week days in a month will be timer triggered. Set amount of months between
occurrences and confirm the selection
Note: Select mode Repeat and confirm it. After that, you will set the first occurrence date, time of occurrence and
duration.

6 back to Exercise Timers

InteliNeo 6000 1.5.0 Global Guide 155


Mode Short period
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup
(page 634).
Note: Setpoint Timer 1 Setup (page 634) is visible only if setpoint Timer 1 Function (page 633) has any
other value than disabled.

Image 5.81 Mode Short period - InteliConfig

In timer mode select Repeat. In repetition type select Short period. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the interval of repetition
(shorter than 1 day).
Example: On image example first start of timer will be 2015-01-01 at 12:00. Duration will be 1 hours.
Timer will be again activated every 4th hour for 1 hour.

Set-up via external display


Navigate to the Scheduler setpoint group. Select the function of timer via Timer 1 Function (page 633) setpoint.
Then go to Timer 1 Setup (page 634) and press enter button. Select mode Repeat and confirm it. After that, you
will set the first occurrence date, time of occurrence and duration. Select Period occurrence, then set period of
repetition (shorter than 1 day).
Note: Select mode Repeat and confirm it. After that, you will set the first occurrence date, time of occurrence and
duration.

6 back to Exercise Timers

InteliNeo 6000 1.5.0 Global Guide 156


5.4.17 Firewall
The firewall function allows to restrict the access to the controller application services (ComAp/TCP server,
MODBUS/TCP server etc.), to the specific computers, or networks using Ethernet 1 (page 19) and Ethernet 2
(page 19) ports. The firewall can be enabled by the setpoint IP Firewall in the Group: ETH Interface 1 - Trusted
(page 406) and Group: ETH Interface 2 - Untrusted (page 412). The firewall settings is made in the
InteliConfig: Control → Controller Configuration → Others → Firewall.
Example:
Adress: 192.168.1.0
Netmask: 255.255.255.0
Port: 23
Any computer with IP address from the network range 192.168.1.0 - 192.168.1.255 can connect to
ComAp/TCP server (= connect to the controller with InteliConfig via Ethernet).

Example:
Adress: 192.168.1.100
Netmask: 255.255.255.255
Port: 502
Only the single computer with IP address 192.168.1.100 can connect to MODBUS/TCP server

IMPORTANT: When enabling the firewall, If the rules are not set up properly and the connection is
made remotely, loss of connection can happen.

InteliNeo 6000 1.5.0 Global Guide 157


5.4.18 Forced Value
This function allows forcing of preconfigured value into selected setpoints via activation of LBI. Each LBI can
force only one value into one setpoint. There are 32 LBIs - FORCED VALUE INPUT 01 (PAGE 997) ... FORCED VALUE
INPUT 32 (PAGE 1003). You can see current states of all LBIs in value Forced Value Status (page 890).
Setpoints for which is Forced Value already configured are marked with gray arrow in InteliConfig and on display.
Note: LBIs can be renamed during configuration. We suggest you to rename them based on used function.

IMPORTANT: You cannot change value of setpoint which has active Forced Value function.

Force Value Indication


If the setpoint is forced by another setpoint then the icon (double right arrow) is displayed just behind the
setpoint value.
Green Icon - Forcing is active
Grey Icon - Force Value is set to the specific setpoint and forcing is inactive
InteliVision 5.2

Image 5.82 : Force Value and Protected Setpoint Indication

InteliConfig

Image 5.83 : Force Value Indication in InteliConfig

Note: Setpoints that are currently being forced their arrow turns to green color and they also have the option
for writing of different value manually disabled.

Forced Value Priority


One setpoint can have multiple configured Forced Values which are ordered from highest to lowest
priority (1 .. 32). In case of conflict highest priority value, which is valid, is used.
In case that Forced Value is out of setpoint's range, value is capped by either maximal or minimal limit or
respective setpoint.

InteliNeo 6000 1.5.0 Global Guide 158


In case that Forced Value is invalid (see Invalid flag (page 691)), another active Forced Value is used
based on priority order. If there is not any other active (or configured) Forced Value which could be used,
the setpoint keeps it's value.
If the setpoint is forced by another setpoint then the icon (double right arrow) is displayed just behind the
setpoint value.
Green Icon - Forcing is active
Grey Icon - Force Value is set to the specific setpoint and forcing is inactive
InteliVision 5.2

Image 5.84 : Force Value and Protected Setpoint Indication in IV 5.2

InteliConfig

Image 5.85 : Force Value Indication in Inteli Config

Note: Setpoints that are currently being forced their arrow turns to green color and they also have the option
for writing of different value manually disabled.

Configuration of Forced Value


Forced Value can be configured only via InteliConfig during standard configuration of the controller and only for
selected setpoints. Setpoints to which Forced Value can apply are marked with flag button. Clicking that button
opens pop-up window containing all already configured Forced Values conditions. Priority of configured Forced
Values is given by order and is descendent - first row has highest priority.

InteliNeo 6000 1.5.0 Global Guide 159


Source from which is setpoint going to be forced. Source has to have same resolution and
dimension as target setpoint.
Name of LBI which activates the Forced Value
Note: This can be also changed in Controller Configuration - Functions

Used trigger which is connected wit Forcing LBI.

List of already configured Forced Values for specific setpoint. First row has highest priorit.

Options for adding, removing and editing Forced Values and options for changing order.

5.4.19 Hot Swap Redundancy


Essential signals and wiring diagram 161
Hot Swap – step by step 163

IMPORTANT: This is a premium function which requires SW Key in order to be used!

Hot Swap Redundancy is a feature designed to increase the reliability of the control system. Its principle is
based on the fact that the control system consists of two pair controllers, "MASTER" and "BACKUP". The
BACKUP controller is ready to take over the control of the BESS anytime when MASTER controller fails.
Assumptions: We assume that both pair controllers have the same information about the controlled system that
they obtain through their inputs and communication lines. This information is supplemented by so-called
synchronization data, which the MASTER controller sends via the Hot Swap Synchronization Line. The second
fundamental assumption is that both controllers have the same configuration in terms of control functions.
Detection of failure of the pair controller and speed of the transition: The BACKUP controller evaluates
the competence of the MASTER controller via a heartbeat signal. Due to its high frequency BACKUP is able to
detect MASTER failure quickly enough to be able to respond in a way that the entire system does not register the
transition to BACKUP at all. This usually happens approximately in 3 ms. The LBO Hot Swap Heart Beat of
MASTER controller must be interconnected with the LBI Hot Swap Heart Beat Detect of the pair BACKUP
controller and vice versa. So, both controllers monitor each other and they are ready to respond accordingly.

InteliNeo 6000 1.5.0 Global Guide 160


Essential signals and wiring diagram
Note: This is a set of recommendations to ensure maximum reliability of the Hot Swap system. The actual
configuration may vary from case to case.

Image 5.86 Wiring diagram and recommended connection

Polarity of binary inputs: The polarity of the Hot Swap Heartbeat pulse signal requires that the controller
binary inputs has to be set to the "Pull Down" configuration.

Hot Swap Heartbeat and other control signals


Hot Swap Heartbeat - The LBO HOT SWAP HEARTBEAT (PAGE 1083) of MASTER controller must be
interconnected with the LBI HOT SWAP HEARTBEAT DETECT (PAGE 1005) of the pair BACKUP controller
and vice versa.
Hot Swap Switch - The function of Hot Swap necessarily requires the configuration of the LBO HOT
SWAP SWITCH (PAGE 1083) signal on the armature of relay Km / Kb , which ensures turn over or
disconnection of technology inputs / outputs and communication lines. It is possible to use multiple pole
relays and combine more control signals together or use a number of independent relays powered by a
common physical output of the controller. Then it is necessary to keep the maximum permissible load of
one output, or to divide the LBO HOT SWAP SWITCH (PAGE 1083) function among several physical binary
outputs. Alternatively use one central Hot Swap Switch relay designed to supply all other control relays.
The Hot Swap functionality necessarily requires the configuration of the LBI HOT SWAP CTRL BLOCK
(PAGE 1005) input on both paired controllers. The input is to be handled by the LBO HOT SWAP SWITCH

InteliNeo 6000 1.5.0 Global Guide 161


(PAGE 1083) signal of the pair controller and ensures the switching of the controller that has been
evaluated as defective to a state where it cannot effect the technology control.

Interconnection of inputs and outputs of Hot Swap pair controllers


Configuration of inputs to polarity "Pull Down" in combination, where inputs and outputs of controllers are
interconnected further requires galvanic separation with optocouplers or connection of anti-series diodes
to controller outputs. For more information see Binary Inputs (page 64) and Binary Outputs (page 65).

Powering
We recommend a 24V power supply system for the Hot Swap system. The MASTER and BACKUP
controllers should be powered from an independent source.

Binary inputs
The binary inputs (with the exception of the control binary inputs of the Hot Swap function) always lead to
both pair controllers at the same time, in the same position without the need of separation by relays. It is
recommended to separate the inputs by diodes to avoid wrong input activation when one controller is
switched off - see Binary Inputs on page 64.
The binary inputs must be set to "Pull Down" polarity on both controllers.

Binary outputs
It is strongly recommend to connect the binary outputs controlling the technology via a pair of relays with a
disconnecting function. This ensures that a controller that is defective cannot disturb the operation of the
application under any circumstances.

Analog inputs
The analog inputs must be connected via paired relays with a switching function. The exception is the
configuration where the analog inputs are set as voltage 0-10 V.

Analog outputs
The analog outputs controlling the technology, namely AOUT1 and AOUT2, must be connected via a pair
of relays with a switching function.

Communication lines
Technological lines CAN1A (ECU and I/O modules), CAN2A (Intercontroller Communication), CAN2B
(Rendundant Intercontroller Communication). These lines are recommended to be connected to both pair
controllers via relays with disconnecting function.
The ETHERNET 3 (technology line with function Modbus Client) is connected to both controllers in the
classic way at the same time. The IP address of the pair controllers on this line must be different. In the
case of using the hotswap function, it will happen that when the master controller fails, backup controller
will start taking care of the device on the modbus. Hotswap function is only possible if the Modbus master
is connected via Ethernet (TCP). Both controllers read the same values ​via modbus, but only one writes.
At the moment of switching to backup controller, the roles of writing and controlling are changed.
Terminal lines ETHERNET 1, ETHERNET 2 are connected to both controllers in the classic way at the
same time.
RS485 (Modbus Server/Master communication) is connected to both controllers in the classic way at the
same time. Both pair controllers has different device address on this line. In case of connection via RS485

InteliNeo 6000 1.5.0 Global Guide 162


there is no possibility to use hotswap. It is not possible to read from two devices and write at the same
time.
Note: In complex applications (e.g. InteliMains performing the Load Control of the system) where Hot Swap
recovery during the run of the gensets is required, it is recommended to wire essential signals (e.g. LBI
Remote Start/Stop) physically. Synchronization of CAN2A/CAN2B lines after the recovery is not as fast as
using physical signals.

Hot Swap Synchronisation Line


MASTER AND BACKUP has to be interconnected via so called Hot Swap Synchronisation Line. Actually
it is point to point interconnecting of CAN1B communication ports via this synchronization is performed.
Even in the event of a failure of this line, BACKUP is ready to take control of the system, but a completely
smooth transition can no longer be guaranteed.

Display
The Hot Swap system does not support a common display for both paired controllers. Each controller is
equipped with its own display.

Fault Reset
The Fault Reset button signal is propagated from the controller which is currently in active role to the
controller which is currently in listening mode via the Hot Swap Synchronisation Line.

Alternative configuration with disconnection of the MASTER controller from the


power supply:
Wiring and configuration described above is recommended however it may follow the specific
requirements of the installation. Instead of using disconnecting relays, it is also possible to disconnect the
MASTER controller completely from the power supply. However, the shutdown of the MASTER controller
is then bit slower and there is a higher risk of unwanted intervention of the faulty MASTER controller in the
control process. In this case, it is not possible to perform a system recovery without a hard reset of both
controllers at one time. We do not recommend this connection, however, the above recommended
connection can be extended by disconnecting the MASTER controller from the power supply.
6 back to Hot Swap Redundancy

Hot Swap – step by step


If we have a ready HW configuration according to the diagram, we can proceed to put the Hot Swap function into
operation. In this chapter, we will walk you through all the steps to run up the Hot Swap system and explain how
to solve several problems that you could be heading.
The configuration and commissioning of the Hot Swap system:
1. SW key
a. The Hot Swap function is conditioned by software licence - SW Key. The apropriate SW Key must be
inserted to the setpoint SW Key (page 388).
2. Base configuration
a. Check that the signals LBO HOT SWAP HEARTBEAT (PAGE 1083) and LBI HOT SWAP HEARTBEAT
DETECT (PAGE 1005) are properly configured – crosswired between MASTER and BACKUP.

InteliNeo 6000 1.5.0 Global Guide 163


b. It is also necessary to configure the LBO HOT SWAP SWITCH (PAGE 1083) signal and the LBI HOT
SWAP CTRL BLOCK (PAGE 1005) signal to the corresponding binary output / input - again crosswired
between MASTER and BACKUP.
c. These signals can be configured for any binary output and binary input of the controller (they must
not be configured on peripheral or virtual modules). The binary inputs must be configured in "Pull
Down" mode. This polarity must then be taken into account when designing the entire control
system. Failure to comply with this configuration causes that the Hot Swap function is not working
and it is Disabled.
d. If any mandatory LBI or LBO is not correctly configured the alarm Wrn Hot Swap Configuration
Incorrect (page 1252) is activated.
3. Setting of the setpoints
a. Set the setpoint Hot Swap Redundancy (page 371) = Master on the controller that is to perform the
MASTER role, and set this setpoint = Backup on the controller in the BACKUP role. MASTER and
BACKUP share the same address, set the setpoint CAN Controller Address (page 392) in the
same way. Pay attention, changing the settings of all the above setpoints will not take effect until both
controllers are power cycled. Verify the configuration and settings by setting the system to the
"default state", ie the MASTER controls the system, the BACKUP is ready to take over the control.
b. In case of using two sets of I/O modules (modules redundancy), set the setpoint Hot Swap
Redundancy (page 371) = Master + Modules Redundancy for MASTER controller and Backup +
Modules Redundancy for BACKUP controller. The rest stays the same as above.
4. From the point of view of the control system
We want the hot swap system to behave as one device - one control system. For this reason, we set the
CAN Address on the Intercontroller CAN line Setpoint CAN Controller Address (page 392) on the
MASTER and on the BACKUP controller identically. This ensures a smooth transition in terms of Load /
Var sharing, Powermanagement and virtual peripheries. On the contrary, from the point of view of
monitoring, it is necessary to distinguish both devices from each other. The address for Monitoring via
RS485 is set using the setpoint Terminal Comm Address (page 393). This communication line is
therefore permanently connected to both controllers and it is not necessary to switch it over the pair
controllers.
5. Resetting the Hot Swap System to the default state
It is possible to reset the system by power-cycling of both controllers. Disconnect the power supply from
both pair controllers, first connect the power supply to the MASTER controller, then connect the power
supply to the BACKUP controller. If the base configuration is OK, the alarmilist on the MASTER or
BACKUP should not contain any alarm related to Hot Swap. Check the value Hot Swap Redundancy
Status (page 892), to confirm that the Hot Swap system is in the default state. The basic check of the
default state can be easily performed by changing the Controller Mode on MASTER controller. Controller
mode can be changed only from the MASTER controller. BACKUP then only reflects this state and it is not
possible to change its Controller Mode directly.
6. Hot Swap Recovery
If the Wrn Master Controller Failed (page 1254) or Wrn Backup Controller Failed (page 1249) alarm
is present in the Alarmlist of one of the controllers, it means that the pair controller was not detected
correctly according to the Hot Swap Heartbeat signal. The cause is probably a faulty configuration or
wrong wiring. Check the wiring and configuration of the LBO HOT SWAP HEARTBEAT (PAGE 1083) and LBI
HOT SWAP HEARTBEAT DETECT (PAGE 1005) signals. If everything is OK, reset the Hot Swap system. This
can be achieved without the need to restart both controllers using the LBI HOT SWAP RECOVERY (PAGE

InteliNeo 6000 1.5.0 Global Guide 164


1006). The LBI responds to the edge, so a pulse needs to be applied to inputs of the both controllers at
one time.
7. Performing the Hot Swap function
If the Hot Swap system is in the default state, we will perform a Hot Swap function test. Interrupt the Hot
Swap Heart Beat signal leading from the MASTER to BACKUP. The alarm Wrn Master Controller
Failed (page 1254) appears in the alarm list of the BACKUP controller and BACKUP actively takes over
the control of the system. In all consequences it means that:
a. BACKUP activates the LBO HOT SWAP SWITCH (PAGE 1083), which controls all relays according to
the diagram. The MASTER is disconnected from all critical lines and signals and the other signals
(Analog inputs and Analog Outputs) are switched to the BACKUP controller. At the same time, with
this signal, the Master controller is switched to the so-called Listening Mode using its LBI HOT SWAP
CTRL BLOCK (PAGE 1005). This mode ensures that the MASTER will be silenced on the CAN
communication lines and thus will not collide with the data that is already being sent by BACKUP for
this purpose.
b. At this point, BACKUP switches from listening mode to Talking Mode, thus representing the Hot
Swap system on CAN communication lines.
c. Have a look at value Hot Swap Redundancy Status. The individual signals now correspond to a
situation where the system has successfully entered a state where BACKUP is in the role of who
controls the system.
Note: In case of using two sets of I/O modules (modules redundancy): Failure of one of the Master’s CAN
modules causes the Hot Swap – the Backup controller takes over the control of the system.
Failure of one of the Backup’s CAN modules causes: Master considers Backup to be dead (therefore the
Backup is no longer available for the Hot Swap function).

8. Smooth transition to Backup


When the BESS is running or is loaded while the MASTER controller fails, then the BACKUP should take
over the control of the BESS smoothly without any bumbs on the frequency, voltage and power values,
even in dynamic states such as loading, unloading or ongoing synchronization. BACKUP will ensure a
smooth transition in the following aspects:
a. ECU communication
b. Serving of CAN peripheral modules
c. Serving of virtual peripheries - Distributed and Shared signals
d. Communication on Intercontroller line - Load Sharing / Var Sharing
9. Hot Swap Synchronization Line
The states of the state automat, Controller Mode, and controller outputs are synchronized via the Hot
Swap Synchronization Line between MASTER and BACKUP controller. In case of synchronization failure
on the Hot Swap Synchronisation Line, BACKUP loses data needed for the smooth transition. If this
happens, BACKUP is internally switched to Emergency Manual mode, where it is still able to take over
control of the system, but a smooth transition can not be guaranteed. The failure of the Hot Swap
Synchronisation Line is accompanied by the following alarms:
a. Wrn Hot Swap Data Synchro Fail (page 1253) - takes place on both the MASTER and the
BACKUP controller in the event of a communication failure on this line. This status is also indicated in
the Hot Swap Redundancy Status value.
b. Wrn Backup Not Ready (page 1249) - This status is indicated by MASTER in the alarm list and in
the value Hot Swap Redundancy Status. This means that BACKUP has an announced 2nd level

InteliNeo 6000 1.5.0 Global Guide 165


alarm, while MASTER does not have such an alarm. Thus, BACKUP is unable to take over control of
BESS. This is a marginal issue that might be caused due to the wrong configuration.
10. Shared setpoints
All setpoints prefixed by "#" character - Due to the identical CAN address of the MASTER and the
BACKUP controller, there is a problem with writing Shared setpoints and it takes these consequences. If
we consider that the Hot Swap system is in the default state then:
a. Inserting a shared setpoint to the BACKUP controller will not be reflected in any of the other
controllers on the CAN (even not in its pair MASTER controller).
b. Inserting a shared setpoint in the MASTER controller will be reflected in all controllers on the CAN
except for its paired BACKUP controller.
IMPORTANT: Ensuring the synchronity of shared setpoints must be ensured by the
operator!

11. Time synchronization


Synchronizing shared setpoints, changing the Time setpoint will not be reflected throughout the system.
Therefore, time synchronization must again be ensured by the operator. With the advantage it is possible
to use the function of time synchronization via SNTP server. This ensures that each controller
synchronizes the exact time independently of the other controllers.
6 back to Hot Swap Redundancy

5.4.20 I/O Configuration


Binary Inputs 167
Binary Outputs 167
Analog Inputs 168
Analog Outputs 169
Functions Configuration 170
Protections Configuration 170
Transfer I/O Configuration 170
Remove I/O Configuration 171

Note: This is only quick illustration for I/O configuration, see the InteliConfig manual for more information
about configuration via PC tool InteliConfig.

InteliNeo 6000 1.5.0 Global Guide 166


Image 5.87 I/O Configuration window

A. Device tree – contains groups of devices with inputs/outputs to configure


B. Configuration panel – the list of available inputs/outputs related to device tree selection
C. Tool bar
Expand All Details - Expands the configuration part of all inputs/outputs
Transfer IO Configuration - see Transfer I/O Configuration on page 170
Remove IO Configuration - see Remove I/O Configuration on page 171

Binary Inputs
The configuration of the binary input consists of:
1. Name - the name identification of the binary input
2. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)
3. Functions - the set of functions see Functions Configuration on page 170
4. Protections - the set of protections see Protections Configuration on page 170

Image 5.88 Binary input configuration

Binary Outputs
The configuration of the binary output consists of:

InteliNeo 6000 1.5.0 Global Guide 167


1. Name - the identification name of the binary output
2. Source - the source value for the binary output
3. Contact Type - represents the default state of output (Normally Open/Normally Closed)
4. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)
5. Protections - the set of protections see Protections Configuration on page 170

Image 5.89 Binary output configuration

Analog Inputs
The configuration of the analog input consists of:
1. Name - the identification name of the analog input
2. Sensor - sensor used for the analog input see Sensor Curves on page 216
3. Dimension - dimension used for analog input (Can be set directly in form if the electronic sensor is
configured, otherwise it can be set in sensor configuration.)
4. Resolution - resolution used for analog input (Can be set directly in form if the electronic sensor is
configured, otherwise it can be set in sensor configuration.)
5. Sensor Range - range used for linear sensor (Range for measured values is defined by Offset + Sensor
Range)
6. Offset - offset used for linear sensor
7. Bargraph 0% - lower bargraph limit displayed on the controller display
8. Bargraph 100% - upper bargraph limit displayed on the controller display
9. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)
10. History Abbreviation - shortcut used in the History.
11. Functions - the collection of functions see Functions Configuration on page 170
12. Protections - the collection of protections see Protections Configuration on page 170

InteliNeo 6000 1.5.0 Global Guide 168


Image 5.90 Analog input configuration using linear sensor

Image 5.91 Analog input configuration using user sensor

Analog Outputs
The configuration of the analog output consists of:
1. Source - the source value for the analog output
2. Output Curve - definition of the transferring output curve
a. The output curve is not available if the "No Conversion" parameter is checked.
3. No Conversion - Define whether the source value is converted by the output curve or not
4. PWM Frequency - setting of the PWM frequency
a. The PWM frequency can be set only if the output curve is a type of PWM.
5. ECU Value - electronic control unit value, available only for ECU devices (otherwise disabled)

Image 5.92 Analog output configuration

IMPORTANT: Output Curves are in Int16 format (range -32768 to 32767). Therefore if the source
value is a decimal value, the range is reduced accordingly.

Example: When BESS Frequency (page 713) (0.001 resolution) is used as a source value, it has to be
converted to a lower resolution in PLC (e.g. 0.01) in order to work correctly. Otherwise the upper level of
the curve's input would be cut to 32.767.

InteliNeo 6000 1.5.0 Global Guide 169


Functions Configuration
It is possible to assign more functions (Logical Binary Inputs) to the specific input (BIN, AIN)

Add new function to the input

Remove function from the input


For the binary input functions the contact type for each function can be set

- Normally Closed/Normally Open

Each function (LBI) has the link to the help through button

Protections Configuration
It is possible to assign one level 1 and level 2 protection to the specific input or output (BINT, BOUT, AIN).

Add new protection

Remove protection

Edit protection
For more information about protections see Protections on page 197

Transfer I/O Configuration


This functionality offers to transfer the whole input/output configuration to another compatible input/output in
the same category. The icon for transfer is available in the bottom toolbar.
After clicking on the transfer icon is displayed window for selecting the target input/output. Offered are only
compatible inputs/outputs of the same category. When the required input/output is selected and confirmed by
the OK button, the transfer operation starts.
Note: The configuration is transferred completely (functions, protections, sensor, PLC configuration) except
Modbus definition.

InteliNeo 6000 1.5.0 Global Guide 170


Image 5.93 The window for selecting the target for I/O configuration transfer

Remove I/O Configuration


This functionality offers to remove the whole input/output configuration. The icon for remove is available in
the bottom toolbar. The name of input/output is after remove set to "Not Used".
Note: The configuration is removed completely (functions, protections, sensor, PLC configuration) except
Modbus definition.

5.4.21 Load Shedding


The Load Shedding is controlled disconnection of less important load groups when the object consumption is too
high.

Load shedding stages


The Load Shedding function consists of 8 stages which are numbered 1-8. Stages are disconnected in
ascending order up to the last configured stage. Reconnecting of stages is in descending order and starts with
higher configured stage. Stage is considered as configured when respective Load Shedding Output is
configured. Highest activated load shedding stage is stored in value Load Shedding Status (page 885).

Load shedding outputs

Stage LBO
Stage 1 LOAD SHEDDING STAGE 1 (PAGE 1085)
Stage 2 LOAD SHEDDING STAGE 2 (PAGE 1085)-
Stage 3 LOAD SHEDDING STAGE 3 (PAGE 1086)
Stage 4 LOAD SHEDDING STAGE 4 (PAGE 1086)
Stage 5 LOAD SHEDDING STAGE 5 (PAGE 1086)
Stage 6 LOAD SHEDDING STAGE 6 (PAGE 1087)
Stage 7 LOAD SHEDDING STAGE 7 (PAGE 1087)
Stage 8 LOAD SHEDDING STAGE 8 (PAGE 1087)

How the load shedding controls the load shedding outputs


The Load Shedding function can be used if Controller Mode (page 385) != OFF.
Activation of the function is adjusted via setpoint Load Shedding Active (page 601). Function could be active
when:
Entering Breaker state (page 886) = IslOper/MultIslOp - all stages are disconnected.
Change from Breaker state (page 886) = ParalOper/MultParOp
to Breaker state (page 886) = IslOper/MultIslOp - all stages are disconnected.
During Breaker state (page 886) = IslOper/MultIslOp - only one stage is disconnected/reconnected at a
moment
Decisive level for disconnecting of load is adjusted via setpoint Power Load Shedding Level (page 603) and
the minimal delay between two disconnections is adjusted via setpoint Power Load Shedding Delay (page
604). When relative BESS P (page 707) exceeds Power Load Shedding Level (page 603) and delay Power
Load Shedding Delay (page 604) elapsed from last disconnection of stage, another stage is disconnected.

InteliNeo 6000 1.5.0 Global Guide 171


Image 5.94 Load shedding

Reconnection of load
Disconnected load can be also reconnected. Reconnecting of stages is in descending order and begins with
highest disconnected stage. Behavior of this function is adjusted via setpoints Auto Load Reconnection (page
602), Power Load Reconnection Level (page 604) and Load Reconnection Delay (page 602).

Manual reconnection
Conditions:
Setpoint Auto Load Reconnection (page 602) = Manual
LBI MANUAL LOAD RECONNECTION (PAGE 1011) has to be configured
When relative BESS P (page 707) drops below Power Load Reconnection Level (page 604) rising edge of
LBI MANUAL LOAD RECONNECTION (PAGE 1011) reconnects the highest disconnected stage.
Note: Setpoint Load Reconnection Delay (page 602) is not considered

Image 5.95 Manual Load reconnection

InteliNeo 6000 1.5.0 Global Guide 172


Auto reconnection
Conditions:
Setpoint Auto Load Reconnection (page 602) = Auto
When relative BESS P (page 707) drops below Power Load Reconnection Level (page 604) and delay Load
Reconnection Delay (page 602) elapsed from last reconnecting of stage, another stage is reconnected.

Image 5.96 Auto Load reconnection

5.4.22 Loss of Mains (Decoupling) Protections


Vector shift
The vector shift function is the fast protection for Mains decoupling (loss of Mains). It monitors the Load angle of
the BESSand if it gets changed dramatically, the protection is issued. The Vector shift is evaluated from the
Mains/Bus Voltage L1-N (page 839).
Protection is enabled via setpoint Vector Shift Protection (page 593) . Limit of protection is adjusted via
setpoint Vector Shift Limit (page 518). When protection is activated, the breaker is opened. Which breaker is
opened is adjusted via setpoint Vector Shift/ROCOF CB Selector (page 522). Maximal value of vector shift is
represented by value Max Vector Shift (page 848).
Note: VectorShift protection gets active (is unblocked) right 500 ms after the condition for activation of protection
gets fulfilled = when Controller goes to parallel to Mains operation (When Vector Shift Protection = PARALLEL
ONLY) or when MCB gets closed (when Vector shift protection = Enabled).

The settings can lead to these situations:

MCB BCB
Vector Vector Shift
STATUS STATUS
Shift/ROCOF CB Protection Action
(PAGE (PAGE
Selector (page 522) (page 593)
1092) 1060)
Enabled or Opens MCB or BCB based on
1 1 MCB or BCB Parallel Only(no Vector Shift/ROCOF CB Selector
influence) (page 522)
Enabled or
MCB or BCB (no No action (BCB stays always
0 1 Parallel Only(no
influence) closed)
influence)
MCB or BCB (no
1 0 Parallel Only No action (MCB stays closed)
influence)

InteliNeo 6000 1.5.0 Global Guide 173


MCB BCB
Vector Vector Shift
STATUS STATUS
Shift/ROCOF CB Protection Action
(PAGE (PAGE
Selector (page 522) (page 593)
1092) 1060)
1 0 MCB Enabled Opens MCB
1 0 BCB Enabled No action (MCB stays closed)

If a vector shift is detected and consequently the MCB is opened, however Mains voltage and frequency remain
in limits, the MCB is then closed again (synchronized) as the Mains is evaluated as healthy.
If a vector shift is detected and consequently the BCB is opened, however Mainsvoltage and frequency remain in
limits, the BCB is then closed again (synchronized) immediately (no delay).

ROCOF
The Rate of Change of Frequency function is the fast protection for Mains decoupling (loss of Mains). It monitors
the change of frequency and if it gets changed dramatically, the protection is issued.
There are in total 4 independent ROCOF protections devided to 2 kinds.

Common behavior
Protections are enabled/disabled by setpoints ROCOF1 Protection (page 594), ROCOF2 Protection (page
595), ROCOF3 Protection (page 596) and ROCOF4 Protection (page 597).

Vector Shift/ROCOF CB
Option Behavior
Selector (page 522)
MCB Protection is reactivated with closing of MCB
Enabled
BCB Protection is reactivated with closing of BCB
Parallel Protection is reactivated with entering Parallel Operation
Not relevant
Only Mode Breaker state (page 886) = ParalOper

Sample based ROCOF


These protections are based on controller's sampling. This means that protection is evaluated after certain
amount of samples have been obtained by the controller.
ROCOF1 Protection (page 594)
Protection is evaluated from last ROCOF1 Windows Length (page 518) samples. If ROCOF1 (page
852) is over ROCOF1 df/dt (page 519), breaker selected by Vector Shift/ROCOF CB Selector (page
522) is opened. Maximal measured ROCOF, from start of evaluation, is stored in Max ROCOF1 (page
853).

Time based ROCOF


These protections are based on specified time period. This means that protection is evaluated from all samples
that have been received in that period.
ROCOF2 Protection (page 595)
Protection is evaluated from samples received in last ROCOF2 Windows Length (page 519) period. If
ROCOF2 (page 853) is over ROCOF2 df/dt (page 520), breaker selected by Vector Shift/ROCOF CB
Selector (page 522) is opened. Maximal measured ROCOF, from start of evaluation, is stored in Max
ROCOF2 (page 854).

InteliNeo 6000 1.5.0 Global Guide 174


ROCOF3 Protection (page 596)
Protection is evaluated from samples received in last ROCOF3 Windows Length (page 520) period. If
ROCOF3 (page 854) is over ROCOF3 df/dt (page 521), breaker selected by Vector Shift/ROCOF CB
Selector (page 522) is opened. Maximal measured ROCOF, from start of evaluation, is stored in Max
ROCOF3 (page 855).
ROCOF4 Protection (page 597)
Protection is evaluated from samples received in last ROCOF4 Windows Length (page 521) period. If
ROCOF4 (page 855) is over ROCOF4 df/dt (page 522), breaker selected by Vector Shift/ROCOF CB
Selector (page 522) is opened. Maximal measured ROCOF, from start of evaluation, is stored in Max
ROCOF4 (page 856).

5.4.23 Mains Import Measurement


This functionality is available only when the Application Mode (page 885) = MPTM. The Mains measurement
can be measured by dedicated CT terminals or by analog inputs, and it is divided to Mains Measurement P
(page 364) and Mains Measurement Q (page 365). The Mains Measurement P has to be enabled for proper
work of active power Import/Export. The both measurements has to be enabled for proper work of reactive power
Import/Export and power factor control.
IMPORTANT: The Earth Fault Current Protection (page 592) and Mains Import Measurement
shares same physical input ⑰ AUX CURRENT (page 47) . At one moment this input can be used
only for one purpose. The protection will work only if Mains Measurement P (page 364) and Mains
Measurement Q (page 365) != Mains CT.

Mains Measurement P
If Mains Measurement P (page 364) = Mains CT then Mains Import P (page 842) is counted from the
current which is measured on ⑰ AUX CURRENT (page 47) .
If Mains Measurement P (page 364) = Analog Input then Mains Import P (page 842) is taken from LAI
MAINS MEASUREMENT P (PAGE 1124). Mains current can still be measured if Mains Measurement Q
(page 365) = Mains CT.
If Mains Measurement P (page 364) = None then Mains Import P (page 842) is not counted because
there is no current measurement. This affects load transfering.
Note: When Mains Measurement P (page 364) is set to None or Analog Input (and LAI MAINS
MEASUREMENT P (PAGE 1124) is not configured or has invalid value) alarm Wrn Load IMP/EXP Fail (page
1253) is activated if Import/Export P is required and alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated
if Import/Export Q is required.

MainsMeasurement Q
If Mains Measurement Q (page 365) = MainsCT then Mains Import Q (page 843) is counted from the
current which is measured on ⑰ AUX CURRENT (page 47) .
If Mains Measurement Q (page 365) = Analog Input then Mains Import Q (page 843) is taken from the
LAI MAINS MEASUREMENT P (PAGE 1124). Mains current can be still measured if Mains Measurement P
(page 364) = Mains CT.
If Mains Measurement Q (page 365) = None then Mains Import Q (page 843) is not counted because
there is no current measurement. This affects load transferring.

InteliNeo 6000 1.5.0 Global Guide 175


Note: When Mains Measurement Q (page 365) is set to None or Analog Input (and LAI MAINS
MEASUREMENT P (PAGE 1124) is not configured or has invalid value) alarm Wrn Wrn PF/Q IMP/EXP Fail
(page 1258) is activated if Import/Export Q is required.

5.4.24 Modbus Client (Master)


The Controller InteliNeo 6000 is equipped by the function of Modbus Client (Master). Actually it means that
controller can play the role of the device which initiate the modbus communication, i.e. controller can ask and
command other devices being in role of modbus server (slave). In standard terms role of modbus client (master)
on modbus TCP or RTU. The communication protocol with server device is a matter of configuration.

Modbus Client (Master) configuration step by step


Controller is able to communicate with up to 16 devices at one time. The modbus server device is configured like
the ECU module, it is part of Multi ECU configuration. Modbus server devices uses the same pool (resources) for
the inputs and outputs as standard ECUs. All modbus server devices share the common pool of inputs and
outputs which is limited on 256 Binary Inputs, 256 Binary Outputs, 288 Analog Inputs and 64 Analog Outputs

Modbus Server Devices Predefined by ComAp


ComAp offers several predefined Modbus Server Devices. These devices can be found in Standard ECU list
(i.e. under Inverters – Photovoltaic).

Once the device is added into the configuration there are the same options for extending the definitions of
inputs and outputs configuration as for user device. All custom inputs and outputs will be always signed by "
(User)" suffix after the name of the signal. This is the way how to recognize custom definitions from ComAp
definitions which can not be edited and how to prevent creating duplicity signals by user definitions.

User defined Modbus Server Devices

1. Adding Modbus Server Device


Open the Controller Configuration in InteliConfig, go to section Modules, and click on Add New Module in
ECU section. Then under Electronic Control Unit select ECU list - Standard and choose User device -

InteliNeo 6000 1.5.0 Global Guide 176


Modbus - Modbus User Device to define your own device definition. Then confirm the settings by pressing
the button Add Module. Now your modbus server device is added into the configuration.

2. Modbus Server Device Settings


Once the device was added into the configuration you need to edit its setting such as number of each type of
Inputs/Outputs, Device Address, etc. Keep in mind that all devices uses inputs and outputs from the limited
pool common with ECU. Inserting the "Device address" is required for both Connection Types (Modbus RTU
or Modbus TCP).

3. MODBUS Registers (Datapoints) definition


Open the section MODBUS registers for editing or creating new registers (datapoints). The list of registers is
actually a set of definitions belonging to your specific device and has no direct connection to specific control
signals in the controller. So, you can create large set of registers without any limitation. Register definitions for

InteliNeo 6000 1.5.0 Global Guide 177


all devices are integrated into the configuration and uploaded into the controller. Therefore there is no need to
share the "original Modbus Device List" containing all registers, when editing the configuration which was not
created in your computer.

Block of registers reading


As modbus protocol allows reading of block of registers using one operation Modbus Master functionality
offers this option. If possible using of this operation is strongly recommended to decrees the numbers of polls
in modbus communication. The block reading is a matter of the configuration in InteliConfig. It allows to merge
more datapoints into the group or to define each input datapoint directly under this group. The Gropu
eperation (modbus function) is then defined by the first datapoint which was added (or created) inside this
group. Configuration tool automatically construct the modbus poll operation based on the renge of register
adresses inside this group.

Write on change option


For writing operation it is possible to define the Refresh Type parameter which offers these options:
Periodically - The writing operations is performed every period based on the settings of Refresh Rate
parameter regardless the real change of the output which is to be written.
On Change - The write operation is only performed on change of output value.
On Change & Periodically - The Write operation is always performed on change as same as
periodically. This allows to set relatively slow refresh rate but accept the change of the output at the same
time.

InteliNeo 6000 1.5.0 Global Guide 178


4. Configuration of Inputs And Outputs
Now, when the definition of your Modbus Server Device was created, go to section I/O Configuration and
assign the specified registers to inputs and outputs. Then assign the functions for inputs and outputs. You can
select from the list of standard logical signals or use your inputs and outputs in the PLC configuration.

InteliNeo 6000 1.5.0 Global Guide 179


5. Clonning of The Modbus Server Device
When using more then one instance of a specific Modbus Server Device in one configuration, or when
needed the Modbus Server Device definition for configuration of another controller, there is a way how to
Export and Import the definitions. Go to section MODBUS registers in Modules and select the icon for
exporting data.

Insert the name and select the target folder for exporting data. You will be informed about successful
exporting of your device definition.

After that select the icon for importing data in a new configuration.

Select one of your Modbus Server Device definition files and Import it into the configuration for a new instance
of your device.

5.4.25 Multiple ECU


InteliNeo 6000 allows you to configure, monitor and control multiple Electronic Control Units (ECUs), such as
Breakers and Modbus modules. At this moment there are 16 ECU slots available, each slot can contain one
ECU/Modbus Master which settings can be separately configured. ECU can be configured via InteliConfig
(Control → Configuration → Modules → Electronic Control Unit).
In order to ensure proper functionality you shall pay extra attention to the ECU settings. ECU address has to be
always unique whereas Controller address is required to be set to the same value as CAN Controller Address
(page 392) of the Controller Unit that sends commands frames to this ECU. Aftertreatment can be enabled only
for one ECU, enable it by using a check box.
ECU I/O can be configured in I/O Configuration.

InteliNeo 6000 1.5.0 Global Guide 180


Controller objects related to ECU
ECU
LBO Alarm
Slot
1 ECU 1 COMM FAIL (PAGE 1069) ECU 1 Comm Fail (page 1341)
2 ECU 2 COMM FAIL (PAGE 1069) ECU 2 Comm Fail (page 1341)
3 ECU 3 COMM FAIL (PAGE 1069) ECU 3 Comm Fail (page 1341)
4 ECU 4 COMM FAIL (PAGE 1070) ECU 4 Comm Fail (page 1342)
5 ECU 5 COMM FAIL (PAGE 1070) ECU 5 Comm Fail (page 1342)
6 ECU 6 COMM FAIL (PAGE 1070) ECU 6 Comm Fail (page 1343)
7 ECU 7 COMM FAIL (PAGE 1070) ECU 7 Comm Fail (page 1343)
8 ECU 8 COMM FAIL (PAGE 1070) ECU 8 Comm Fail (page 1343)
9 ECU 9 COMM FAIL (PAGE 1070) ECU 9 Comm Fail (page 1344)
ECU 10 COMM FAIL (PAGE
10 ECU 10 Comm Fail (page 1344)
1071)
ECU 11 COMM FAIL (PAGE
11 ECU 11 Comm Fail (page 1344)
1071)
ECU 12 COMM FAIL (PAGE
12 ECU 12 Comm Fail (page 1345)
1071)
ECU 13 COMM FAIL (PAGE
13 ECU 13 Comm Fail (page 1345)
1071)
ECU 14 COMM FAIL (PAGE
14 ECU 14 Comm Fail (page 1346)
1071)
ECU 15 COMM FAIL (PAGE
15 ECU 15 Comm Fail (page 1346)
1071)
ECU 16 COMM FAIL (PAGE
16 ECU 16 Comm Fail (page 1346)
1072)

For each ECU there is LBO which gets activated when communication issue with respective ECU is detected.
For easier detection whether all configured ECUs are communicating, there is LBO ECU COMM OK (PAGE 1074).
During detected communication issue an alarm is issued for respective ECU.
All protections which evaluation depends on values from the ECU with communication error are blocked in order
to pervent showing of invalid protections in the Alarm list.

5.4.26 Operating Modes


The operating mode can be selected by pressing Left and Right buttons on the front panel/display, by
changing the Controller Mode (page 385) setpoint, or by activating respective LBI.
Note: If the setpoint is configured as password-protected, the correct password must be entered prior to
attempting to change the mode.

The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
Remote OFF (page 1027)
Remote MAN (page 1027)

InteliNeo 6000 1.5.0 Global Guide 181


Remote AUTO (page 1026)
If the respective input is active the controller will change the mode to the respective position according to the
active input. If multiple inputs are active, the mode will be changed according to priorities of the inputs. The
priorities match the order in the list above. If all inputs are deactivated, the mode will return to the original position
given by the setpoint.
Another chapter related to the Operating modes is in the Operator Guide see Basic operating modes
description on page 111.

Switching Control Mode


Controller recognize two possible ways to change mode:
Setpoint
Controller mode is selected by Setpoint Controller Mode (page 385). Change of this setpoint will change
controller mode. Terminals such as InteliConfig, InteliSCADA or Displays uses this setpoint to change
controller mode, but they use their own visualization for it.
MODBUS can be used to change this setpoint as well.

LBI
Dedicated LBIs to change mode have higher priority than the setpoint. When LBI is activated th setpoint is
unchanged.
When all LBIs are deactivated controller mode is changed to one that is in Setpoint Controller Mode (page
385).

Signalization of Control Mode


Controller offers two kinds of signalization:
Value
Current controller mode is always show in Value Controller Mode (page 885).

LBO
There is a dedicated LBO for each mode.
MODE OFF (PAGE 1094)
MODE MAN (PAGE 1093)
MODE AUTO (PAGE 1093)

OFF
Start of the BESS is blocked, the controller will stay in Not Ready state, and starting command cannot be issued.
If the BESS is already running, it is not possible to switch directly to the OFF mode. Firstly you have to stop the
BESS and after that switch to the OFF mode.
For MPTM application, if Mains is healthy and MCB is opened, then MCB is automatically closed after the delay
given by setpoint MCB Close Delay.

No Power management function will be performed. The buttons MCB ON/OFF , BCB ON/OFF , START
, and STOP including the appropriate binary inputs for external buttons are not active.

Note: When BESS is running, it is not possible to switch the controller to OFF mode.

InteliNeo 6000 1.5.0 Global Guide 182


MAN
The BESS can be started and stopped manually using the START and STOP buttons (or external buttons wired
to the appropriate binary inputs) if no 2nd level alarm is active. When the BESS is running and BESS parameters
are in the limits, BCB can be closed to a dead bus or synchronization can be started by the BCB button.
The MCB (in case of MPTM application) can be closed and opened manually using the MCB button, if Mains is
present. MCB can be opened manually after Mains failure (it is not tripped in case of Mains failure).
Opening and closing of breakers depends on the setpoint CB Control In MAN Mode (page 362).
Controller does not respond to external signals and/or conditions. The BESS is fully in manual control; there is no
automatic way to stop it (except protections). The BESS stays running until STOP button is pressed. Controller
does not take place in Power Management (page 274) in MINT application.
No AMF or Power management function will be performed.

AUTO
BESS is controlled based on external signal (GENERIC GENSET START/STOP (PAGE 1004) ) or by conditions (Peak
shaving, Power management system, etc.). When one condition deactivates the BESS does not stop if another
condition for automatic starts is active. System Start/Stop can be received from other controllers via Intecontroller
Communication.
The controller does not respond to the buttons START, STOP, MCB ON/OFF, and BCB ON/OFF.
If peak shaving stop condition occurs, but GENERIC GENSET START/STOP (PAGE 1004) is active, BESS stays
running.
IMPORTANT: If a red alarm is present and the controller is in the AUT mode, the BESS can start by
itself after all red alarms become inactive and are acknowledged (fault reset is pressed)! To avoid
this situation, adjust the setpoint Fault Reset To Manual (page 386) to the Enabled position.

IMPORTANT: BESS will start if at least one external signal or condition is fulfilled.

5.4.27 PLC - Programmable Logic Controller


List of available PLC blocks 185
PLC Editor 186
PLC logic execution rules 192
PLC monitor 193
Other functions 195

The Programmable Logic Controller (PLC) built into the ComAp controllers is generally a simple process unit
used for the automation of processes. The major benefit of the PLC is you don’t need any extra control
devices in your control system. The PLC is tightly integrated with the standard line of controllers. That allows
the PLC editor to be a seamless experience directly in the programming software. Flexibility is at the core of
ComAp's software design and the PLC meets both simple and complex application requirements while using
the same intuitive interface. PLC Editor is a powerful tool that helps you to create your own PLC scheme. It
has a user-friendly graphical interface which makes it easy to use.
ComAp PLC Editor has been developed to help you deal with even the most demanding applications. It
allows you to add control logic, additional alarm functions, or even new features to meet complex or unique
requirements. This easy-to-use PLC Editor means you can customize the way the controller works to match
the application precisely without compromise or limitation.

InteliNeo 6000 1.5.0 Global Guide 183


Intuitive design, visual programming, and easy modification.
All PLC function blocks can be moved both horizontally and vertically.
Color-coded and linked to relevant functions.
Blocks can be organized to reflect the real process flow.
Groups of blocks can be separated on each sheet to form sub-sets within the design.
Detailed descriptions of inputs and outputs come complete with useful hints

Image 5.97 PLC Editor - main page

InteliNeo 6000 1.5.0 Global Guide 184


List of available PLC blocks
In the table below you can find all available PLC blocks.

Group PLC blocks Number of blocks


OR/AND (page 1193) 255
Logical
XOR/RS (page 1195) 255
Comp Delay (page 1196) 16
Comparators Comp Hyst (page 1197) 32
Comp Win (page 1198) 32
Delay (page 1199) 48
Time functions
Timer (page 1201) 8
AxB/C±D (page 1204) 32
Math Operations Interpolation (page 1203) 16
Math Fc. (page 1205) 48
PID (page 1207) 4
Regulators
Up/Down Ctrl Block (page 1211) 8
Inc/Dec (page 1214) 4
LowPassFlt (page 1215) 8
Ramp functions Mov Avg (page 1216) 8
Ramp (page 1217) 8
Up/Down (page 1218) 4
Analog Switch 8 (page 1220) 32
Bit Sum 16 (page 1222) 4
Circuit Breaker (page 1224) 8
Comp. 4 (page 1229) 8
Comp. 16 (page 1230) 8
Convert (page 1227) 16
Counter (page 1228) 8
Decomp. 4 (page 1231) 8
Others
Decomp. 16 (page 1232) 8
Differ (page 1234) 4
Heartbeat (page 1235) 16
Hold (page 1237) 4
PF Conv (page 1238) 4
Poly Appx (page 1240) 4
PWR Calc (page 1241) 4
Validator (page 1244) 16
For more information about PLC blocks go to the chapter PLC (page 1191)
6 back to PLC - Programmable Logic Controller

InteliNeo 6000 1.5.0 Global Guide 185


PLC Editor
Toolbar 186
Working with sheets 186
Blocks Selection Tree 187
Adding PLC blocks 188
PLC Block Configuration 188
Define inputs and outputs 190
Creating wires 191
The PLC Editor is available in InteliConfig Control tab: use Control → Controller Configuration → PLC Editor.

Toolbar
In the upper part of the PLC editor panel there is a toolbar with buttons for working with PLC blocks and PLC
sheets.

Operations PLC Sheets


Select all elements in sheets Add and remove sheets
Unselect all selected elements Move selected sheet down and up
Delete all selected elements Import sheet
Rerote selected items - wiring optimization Export selected sheet
Delete whole content of currently selected sheet Expand and Colapse all sheets
Others
Enable/Disable hints

6 back to PLC Editor

Working with sheets


PLC editor supports working with multiple sheets. You can add or delete sheets and move them up and down.
Every sheet can be also renamed by double-click on sheet name "Sheet 1". Each sheet can be re-sized
according to your needs by dragging the sheet edges. InteliConfig also supports importing and exporting of
the individual sheet.
Note: The number of PLC blocks on one PLC sheet is limited to 30 blocks.

InteliNeo 6000 1.5.0 Global Guide 186


Image 5.98 Adjusting PLC sheet

6 back to PLC Editor

Blocks Selection Tree


On the left side of PLC Editor panel is available PLC blocks selection tree. Blocks are grouped into groups of
similar functionality next to the name of each block the number of used /available blocks of that type is
indicated in brackets.

Image 5.99 Blocks selection treet

6 back to PLC Editor

InteliNeo 6000 1.5.0 Global Guide 187


Adding PLC blocks
Adding PLC block is using simple and intuitive drag and drop system. Follow the procedure below to add PLC
block.
Select required PLC block by LMB (left mouse button) from the list of available PLC blocks on the left side
and drag it into the sheet.
Connect the block inputs and outputs by drawing wires in the sheet. It is also possible to connected inputs
and outputs via properties of selected PLC block.
Note: To delete PLC block just click on it and press delete button. Also delete selection function can be used.

Note: To see context help for selected PLC block just press F1 button.

Image 5.100 Adding PLC blocks

6 back to PLC Editor

PLC Block Configuration


Double-click on the block by LMB (left mouse button) to invoke the configuration panel specific for each block
type. In general, the definition of the block inputs and outputs is accompanied by some settings of block
properties. See PLC (page 1191) for more information about blocks.

InteliNeo 6000 1.5.0 Global Guide 188


Selecting the Inverted input check box means using negated input when evaluating the block.
Selecting the Inverted output check box means issuing a negated output value after the block has been
internally evaluated.
The binary values can be either controller Values, Setpoints or PLC binary outputs.
The analog values can be either controller Values, Setpoints, PLC analog outputs or entered as direct
constant block values. Non-numeric Setpoint values (e.g. IP address) cannot be used.
If a variable (binary signal) is connected via wire, the connection appears directly in the field - otherwise
the variable (binary signal) can be set using the dialog invoked by the '...' button.
Specific properties of the block (e.g. function type, mode of operation, etc.) can be set in the
corresponding panel object (list box, check box).
If the block has a variable number of inputs, the '+' button (in the upper left corner) adds an additional input
(channel) up to the maximum number of channels. Use 'X' button to remove a channel.
Note: If the constants are used (i.e. set by block configuration dialog) they cannot be changed dynamically
during PLC execution.

6 back to PLC Editor

InteliNeo 6000 1.5.0 Global Guide 189


Define inputs and outputs

Image 5.101 PLC Inputs and Outputs

Inputs
Sheet inputs are located at the left side of a sheet. Follow the procedure below to add or edit an input.
Double-click on a free input position or existing input to add new input or edit the existing one.
Select the source for the input.
If you create a binary input, you can select a source from following categories:
Bin. Values - this category contains all binary values available in the controller as binary inputs, logical
binary outputs etc.
PLC Outputs - You can connect any PLC Output to another PLC Input.
If you create an analog input, you can select a source from following categories:
Ana. Values - this category contains all analog values available in the controller as analog inputs,
electrical values, values from ECU etc.
All Setpoints - this category contains all setpoints of the controller except the dedicated PLC setpoints.
Names, resolutions and dimensions of these setpoints can not be modified.

Image 5.102 PLC Inputs

InteliNeo 6000 1.5.0 Global Guide 190


Outputs
Sheet outputs are located at the right side of a sheet. Follow the procedure below to add or edit an output.
Double-click on a free output position to add new sheet output (binary or analog).
Draw the wire from the PLC block output to the PLC output on the right side of the sheet.
Doubleclick on an already created output to open it's configuration.
Use the button + Connect to connect the PLC output onto a controller output terminal or a logical binary
input.
Use the button - Disconnect to disconnect the PLC output from a controller output terminal or a logical
binary input.
Note: PLC block output has to be connected to the PLC output to enable configuration of the PLC output.

Note: It is necessary to click on the Connect button after selecting the output. Otherwise PLC output is not
connected to output.

Image 5.103 PLC Outputs

6 back to PLC Editor

Creating wires
Wires can be created between PLC inputs and PLC block inputs, PLC block outputs nad PLC block inputs, or
PLC block outputs and PLC outputs.
Follow the procedure below to create wire.
Locate the mouse pointer over the starting point of the wire (dot). If the area under the mouse pointer is a
connection point, the connection point changes to bold dot.
Press and hold the left mouse button and drag the wire to the destination of required connection point
(from dot to dot connection). If you point over a valid connection point, the connection point changes to
bold dot.

InteliNeo 6000 1.5.0 Global Guide 191


Release the left mouse button to create a wire between the two points (dots). The wire is routed
automatically.
Note: It is possible to make connection only between the outputs and inputs with the same type of value
(binary or analog). Binary values are marked by black dot, analog values are marked with green dot.

Note: To delete wire just click on it and press delete button. Also delete selection function can be used.

IMPORTANT: In case that values on inputs have different decimal numbers than the values are
converted and the name of block is displayed as red in the PLC Monitor. It is strongly
recommended to fix the configuration = use the signals/values with the same range and decimal
numbers.

Image 5.104 Wiring PLC blocks

6 back to PLC Editor


6 back to PLC - Programmable Logic Controller

PLC logic execution rules


The PLC program is executed every 100 ms (this time is given by the PLC controller system integration) and
cannot be changed. PLC execution starts automatically after the ComAp controller is powered on and the
firmware initialization is completed. Of course the PLC program can only be executed with valid configuration
and/or valid SW key(s) for using the Extended PLC blocks.
The inital values for PLC inputs are given by the respective signals (e.g. actual power value) or determined by the
specific PLC block settings.
PLC blocks are executed in the order of the block numbers (Item numbers), that appear in each block. Block
numbers are assigned automatically according to the block position on the sheet based on the following scheme.

InteliNeo 6000 1.5.0 Global Guide 192


Image 5.105 PLC execution logic

IMPORTANT: Please always check that the blocks are ordered correctly, especially if you use direct
feedbacks from outputs to inputs within one sheet. Wrong order may lead to incorrect results!

The execution order is Item 1 → Item 2 → Item 3, so in the second case the AND block evaluation will use
Timer block output before the update.

PLC monitor
PLC monitor is a powerful tool for monitoring your PLC. Just click on PLC Monitor button on main InteliConfig
page to see you PLC in the run time. The refresh rate is given by the system integration. The PLC Monitor is
available in InteliConfig Control tab.
PLC monitor supports working with multiple controllers - on the left side of the panel there is a selection tree for
choosing the desired controller for PLC monitoring.

InteliNeo 6000 1.5.0 Global Guide 193


Image 5.106 PLC Monitor panel with multiple controllers

Note: In the PLC Monitor it is not possible to modify the PLC, not even the position of the blocks.

Active binary inputs, outputs and wires are blue, analog inputs, outputs and values are green. The values of
analog signals (as well as constants set in the blocks configuration) are also visible.

Image 5.107 PLC Monitor sheet with invalid value

Note: If the analog signal have an invalid value, the red "####" string is displayed and the connecting wire is
also red.

The PLC monitor also supports multi-sheet monitoring - individual sheets can be hidden/expanded using the
button in the top title bar.

InteliNeo 6000 1.5.0 Global Guide 194


Image 5.108 PLC Monitor with multiple sheets

6 back to PLC - Programmable Logic Controller

Other functions
Consistency check
This performs a check of the PLC schematic
for the validity of the block interconnection = all inputs that are in internal design rules marked as
mandatory are connected and/or configured
for the consistency of the dimensions (setting attribute Dimension) and the number of decimal place
(setting attribute Resolution) at both ends of the interconnection wire

Image 5.109 Consistency Check valid output

Use this function during the design phase to check if all inputs and outputs of PLC block are connected
properly, and the design is consistent. The check is also performed automatically when the configuration may
be written to controller.
If the Consistency Check detect any problems, all findings will be displayed in the message window.

Image 5.110 Consistency Check report output

InteliNeo 6000 1.5.0 Global Guide 195


Message Meaning Remedy
Connected wire is not Probably Resolution and/or Use correct Resolution and/or
supported for function block Dimension mismatch on Dimension on both ends of
(Item X) the wire wire
Mandatory inputs of the
Not connected connector/s for Connect and/or configure all
block are not connected /
function block (item X) mandatory inputs
configured
Some connectors which must Probably Resolution and/or Use correct Resolution and/or
have same unit or resolution Dimension mismatch on Dimension on both ends of
are different for function block the wire or on Inputs and/or wire of between block inputs
(Item X) Output and output

Note: The Consistency Check checks whole configuration so it can report findings outside the PLC
configuration.

Delete whole content of sheet


Use this function to delete the whole content of sheet (including blocks, wires, inputs, outputs, etc...).
IMPORTANT: The sheet content is deleted immediately, without confirmation dialog (and there is
not any Undo or Redo button)!

Hints
Use this function to enable or disable quick hints for blocks (controller help is not affected by this function).
Note: Each PLC block has help which is opened by selecting the block and pressing "F1".

5.4.28 Power Formats And Units


InteliNeo 6000 allows users to choose from several Power Formats that affect dimensions in which values and
some setpoints are interpreted or adjusted. Power formats and units can be changed with InteliConfig in the
following way. Control tab → Controller configuration → Others tab → Units/Power format
Power formats are available in decimal and non decimal format. Units can be changed to metric or US units.

Units
Metric 20 °C 10.0 bar 11.4 l/h
US 68 °F 145 psi 3.01 gph

Power Format
Small 0.1 kW / kVA / kVAr 1V
Standard 1 kW / kVA / kVAr 1V
Large HV 0.01 MW / MVA / MVAr 0.01 kV
Large LV 0.01 MW / MVA / MVAr 1V

Note: Range of some setpoints and values is changed significantly when different Power Formats are selected.
Affected setpoint are displayed during selection of power format.

InteliNeo 6000 1.5.0 Global Guide 196


5.4.29 Protections
Protection types 198
Protection activation 200
Protection blocking 200
Fixed protections 200
User protections 205
Protection states 210

InteliNeo 6000 combines Fixed protections (page 200) with User protections (page 205) which allows
users to configure their own protections to any analog or binary input. Multiple protections can be configured
on each analog input, number of configured protections are not limited. Only one protection of 1st level
and/or one protection of 2nd level can be configured on logical binary output. The maximum number of
configured User protections (page 205) is limited to 200. The maximum number of configured fast User
protections (page 205) is limited to 50.

InteliNeo 6000 1.5.0 Global Guide 197


Protection types
Level 1 Protections
LBO COMMON ALARM LEVEL 1 (PAGE 1066)

LBO COMMON ALARM ACTIVE LEVEL 1 (PAGE 1065)

Action: CB open

Action: BESS stop

SD Override blocking

Alarm List +
History Alarm List
Name Warning Alarm Only History Record
Record Only Indication
Indication
Abbreviation Wrn Al Hst ALI AHI
Alarm List indication

History record

Fault Reset needed

LBO Alarm activation

LBO Horn activation


COMMON COMMON
COMMON
ALARM HISTORY
Common LBO WARNING
ONLY (PAGE RECORD
(PAGE 1068)
1066) (PAGE 1066)

InteliNeo 6000 1.5.0 Global Guide 198


Level 2 Protections
LBO COMMON ALARM LEVEL 2 (PAGE 1066); except Mains Protection

LBO COMMON ALARM ACTIVE LEVEL 2 (PAGE 1065) ; except Mains Protection

Shutdown Mains PVCB Open


Name Shutdown Slow Stop
Override Protection
Abbreviation Sd Sd Stp MP PVBO
Alarm List indication

History record

Fault Reset needed

Action: CB open

Action: BESS stop

SD Override blocking

LBO Alarm activation

LBO Horn activation


COMMON
COMMON
COMMON SLOW COMMON MAINS COMMON
SHUTDOWN
Common LBO SHUTDOWN STOP PROTECTION PVCB OPEN
OVERRIDE
(PAGE 1067) (PAGE (PAGE 1066) (PAGE 1067)
(PAGE 1067)
1067)

6 back to Protections

InteliNeo 6000 1.5.0 Global Guide 199


Protection activation
The table below shows the availability of conditions for analog and binary values

Type Name of activation Protection is activated if value is


Over Limit over limit
Over Limit+Fls over limit or in fault state
Analog Under Limit under limit
Under Limit+Fls under limit or in fault state
Fls only in fault state
True logical 1
TrueOrFls logical 1 or in fault state*
Binary
False logical 0
FalseOrFls logical 0 or in fault state*

* Fault state can occur if there is loss of communication with configured CAN module.
6 back to Protections

Protection blocking
It is possible to configure one Protection Blocking to any User protections (page 205). This function is used to
block certain protections when their function is unwanted or meaningless. Each user protection has an option to
set the blocking condition.
The blocking conditions can be also applied on the Fixed protections (page 200).

General protections
Each of the LBI Protection Force Disable 1 is paired with an option of protection condition "Force Block 1–3" and
can be used for Blocking / Disabling of protections, however on user defined protections the option causes
protection Blocking instead of Disabling.

Run only protections


Each of the setpoint Run Only Block Delay 1 (page 443) is paired with an option of protection condition "Run
Only Block Delay 1–3". The protection
6 back to Protections

Fixed protections
Some selected fixed protections has an option to DISABLE the protection.
The setting is done by using the setpoint which is associated to the fixed protection. Each setpoint offers these
options.

Setpoint options
Alarms Fixed Protection States
Enable Protection is enabled
Disable Protection is disabled
PROTECTION FORCE DISABLE 1 (PAGE 1016)
Disabling of the protection can be forced by LBI
PROTECTION FORCE DISABLE 2 (PAGE 1017)

InteliNeo 6000 1.5.0 Global Guide 200


Setpoint options
Alarms Fixed Protection States
PROTECTION FORCE DISABLE 3 (PAGE 1017)

BESS Voltage Protections


Protection Alarms / Protection name Fixed Protection States
Sd BESS >>V L1-N (page 1281)
Sd Mains/Bus >>V L2-N (page 1281)
BESS >>V Protection Sd BESS >>V L3-N (page 1282) FIXED PROTECTIONS STATES 2
(page 575) WRN BESS >>V L1-L2 (page 1282) (PAGE 1181)
WRN BESS >>V L2-L3 (page 1282)
WRN BESS >>V L3-L1 (page 1282)
Sd BESS >V L1-N (page 1283)
Sd BESS >V L2-N (page 1283)
FIXED PROTECTIONS STATES 2
Sd BESS >V L3-N (page 1283)
BESS >V (page 574) (PAGE 1181)
Sd BESS >V L1-L2 (page 1283)
Sd BESS >V L2-L3 (page 1284)
Sd BESS >V L3-L1 (page 1284)
Sd BESS <V L1-N (page 1284)
Sd BESS <V L2-N (page 1284)
FIXED PROTECTIONS STATES 2
BESS <V Protection Sd BESS <V L3-N (page 1285)
(PAGE 1181)
(page 576) Sd BESS <V L1-L2 (page 1285)
Sd BESS <V L2-L3 (page 1285)
Sd BESS <V L3-L1 (page 1285)
Sd BESS V Unbalance Ph-N (page
FIXED PROTECTIONS STATES 2
BESS V Unbalance 1286)
(PAGE 1181)
Protection (page 576) Sd BESS V Unbalance Ph-Ph (page
1286)

BESS Frequency Protections


Protection Alarms / Protection name Fixed Protection States
FIXED PROTECTIONS STATES 2
BESS >f Protection (page
Sd BESS >f (page 1286) (PAGE 1181)
584)

FIXED PROTECTIONS STATES 2


BESS <f Protection (page
Sd BESS <f (page 1286) (PAGE 1181)
585)

InteliNeo 6000 1.5.0 Global Guide 201


BESS Load & Current Protections
Protection Alarms / Protection name Fixed Protection States
Short Circuit Protection FIXED PROTECTIONS STATES 4
PVBO Short Circuit (page 1288)
(page 571) (PAGE 1183)
IDMT BESS >A FIXED PROTECTIONS STATES 4
Sd IDMT BESS >A (page 1287)
Protection (page 571) (PAGE 1183)
BESS Current Unbalance Sd BESS Current Unbalance (page FIXED PROTECTIONS STATES 2
Protection (page 573) 1287) (PAGE 1181)
IDMT Overload FIXED PROTECTIONS STATES 4
Sd IDMT Overload (page 1287)
Protection (page 570) (PAGE 1183)

BESS Other Protections


Protection Alarms / Protection name Fixed Protection States
Earth Fault Current Sd IDMT Earth Fault Current (page FIXED PROTECTIONS STATES 4
Protection (page 592) 1287) (PAGE 1183)
Phase Rotation (page
384)
Note: This protection
monitors phases rotation
and compares it with
Phase Rotation (page ALI BESS Ph Rotation Opposite (page
-
384), in case of 1273)
inconsistency, proper
alarm is activated

Note: This protection can't


be disabled.
Inverted Phase
Note: This protection
monitors phases inversion
and in case of ALI BESS Ph L1 Inverted (page 1272)
inconsistency of all ALI BESS Ph L2 Inverted (page 1272) -
phases, proper alarm is
ALI BESS Ph L3 Inverted (page 1272)
activated

Note: This protection can


not be disabled.

InteliNeo 6000 1.5.0 Global Guide 202


Bus Voltage Protections
Protection Alarms / Protection name Fixed Protection State
Bus V Unbalance Protection
Behavior of protection is adjusted via
setpoints BESS V Unbalance (page
454) and BESS V Unbalance Delay
(page 454) When relative difference
between bus voltages is over setpoint
BESS V Unbalance (page 454) for time Mains/Bus V Unbalance
longer than BESS V Unbalance Delay Ph-N (page 1321) FIXED PROTECTIONS STATES
(page 454) history record "Bus V
Mains/Bus V Unbalance 3 (PAGE 1182)
Unbalance Ph-N" or/and "Bus V
Ph-Ph (page 1321)
Unbalance Ph-Ph" is written to the
history.
IMPORTANT: Behavior of this protection
is influenced by setpoint Connection
type (page 378).

Note: This protection can not be disabled.

Bus Other Protections


Protection Alarms / Protection name Fixed Protection State
FIXED PROTECTIONS STATES
Stp Bus Meas Error (page
Bus Meas Error (page 590) 4 (PAGE 1183)
1290)

Mains Voltage Protections


Protection Alarms / Protection name Fixed Protection States
Mains/Bus >>V L1-N (page 1305)
Mains/Bus >>V L2-N (page 1306)
Mains >>V Protection Mains/Bus >>V L3-N (page 1307) FIXED PROTECTIONS STATES 3
(page 579) Mains/Bus >>V L1-L2 (page 1307) (PAGE 1182)
Mains/Bus >>V L2-L3 (page 1308)
Mains/Bus >>V L3-L1 (page 1309)
Mains/Bus >V L1-N (page 1301)
Mains/Bus >V L1-N (page 1301)
FIXED PROTECTIONS STATES 2
Mains/Bus >V L2-N (page 1301)
Mains >V Protection (PAGE 1181)
Mains/Bus >V L3-N (page 1302)
(page 577) FIXED PROTECTIONS STATES 3
Mains/Bus >V L1-L2 (page 1303)
(PAGE 1182)
Mains/Bus >V L2-L3 (page 1304)
Mains/Bus >V L3-L1 (page 1304)
Mains <V Protection Mains/Bus <V L1-N (page 1310) FIXED PROTECTIONS STATES 2
(page 581) Mains/Bus <V L2-N (page 1310) (PAGE 1181)

InteliNeo 6000 1.5.0 Global Guide 203


Mains Voltage Protections
Protection Alarms / Protection name Fixed Protection States
Mains/Bus <V L3-N (page 1311)
Mains/Bus <V L1-L2 (page 1312) FIXED PROTECTIONS STATES 3
Mains/Bus <V L2-L3 (page 1313) (PAGE 1182)
Mains/Bus <V L3-L1 (page 1313)
Mains/Bus <<V L1-N (page 1314)
Mains/Bus <<V L2-N (page 1315)
Mains <V Protection Mains/Bus <<V L3-N (page 1316) FIXED PROTECTIONS STATES 3
(page 582) Mains/Bus <<V L1-L2 (page 1316) (PAGE 1182)
Mains/Bus <<V L2-L3 (page 1317)
Mains/Bus <<V L3-L1 (page 1318)
Mains/Bus V Unbalance Ph-N (page FIXED PROTECTIONS STATES 2
Mains V Unbalance 1321) (PAGE 1181)
Protection (page 583) Mains/Bus V Unbalance Ph-Ph (page FIXED PROTECTIONS STATES 3
1321) (PAGE 1182)

Mains Frequency Protections


Fixed Protection
Protection Alarms / Protection name
States
FIXED PROTECTIONS
Mains >>f Protection
Mains/Bus >>f (page 1319) STATES 3 (PAGE
(page 587)
1182)
FIXED PROTECTIONS
Mains >f Protection
Mains/Bus >f (page 1319) STATES 3 (PAGE
(page 586)
1182)
Frequency
FIXED PROTECTIONS
Mains <f Protection
Mains/Bus <f (page 1320) STATES 3 (PAGE
(page 588)
1182)
FIXED PROTECTIONS
Mains <<f Protection
Mains/Bus <<f (page 1320) STATES 3 (PAGE
(page 589)
1182)

Loss of Mains Protections


Protection Alarms / Protection name Fixed Protection States
Vector Shift Protection FIXED PROTECTIONS STATES 4
Hst Vector Shift (page 1278)
(page 593) (PAGE 1183)
ROCOF1 Protection
Hst ROCOF 1 (page 1277) -
(page 594)
ROCOF2 Protection
Hst ROCOF2 (page 1277) -
(page 595)

InteliNeo 6000 1.5.0 Global Guide 204


Loss of Mains Protections
Protection Alarms / Protection name Fixed Protection States
ROCOF3 Protection
Hst ROCOF3 (page 1277) -
(page 596)
ROCOF4 Protection
Hst ROCOF4 (page 1278) -
(page 597)

Grid Codes Protections


Protection Alarms / Protection name Fixed Protection States
Mains 10min Avg >V FIXED PROTECTIONS STATES 2
-
Protection (page 580) (PAGE 1181)
Mains Params/MP
FIXED PROTECTIONS STATES 1
Synchronization (page AHI SyncNotAllowed (page 1276)
(PAGE 1180)
536)
Q&U Protection (page FIXED PROTECTIONS STATES 1
Wrn Q&U Protection (page 1262)
558) (PAGE 1180)
Pave (page 569) Hst Pave (page 1277) -
Dynamic Support (page FIXED PROTECTIONS STATES 1
VRT Protection Trip (page 1349)
561) (PAGE 1180)

User protections
Source upon which the protection is configured can be selected. It can be any analog value or binary state.

Source
Analog values Binary states
Analog inputs Binary inputs
Controller, Modules Controller, Modules, ECU, Shared I/O
Values Modbus server, Modbus Master
ECU, Measured values, Application, Binary outputs
PLC, Shared I/O PLC
Modbus server, Modbus Master Protection states
Statistics LBOs

Configuration of protections in InteliConfig


Control tab → Controller configuration → Protections tab → Analog / Binary protections

InteliNeo 6000 1.5.0 Global Guide 205


Select the desired protections to be configured (Analog protections / Binary protections).

Add protection by clicking on the icon

Delete selected protection by clicking on the icon.

Edit selected protection by clicking on the icon.

InteliNeo 6000 1.5.0 Global Guide 206


Adding analog protection

Selecting the input source see User protections on page 205

Selecting the protection type see Protection types on page 198

Text input for Alarm / History message

Selecting the protection activation see Protection activation on page 200

Selecting the block type see Protection blocking on page 200

Selecting if the occurrence of a protection is recorded every time or only once after a Fault
Reset.

Selecting the evaluation period

InteliNeo 6000 1.5.0 Global Guide 207


If Protection State is checked the protection is then shown in the Values in the group User
Protection States.
Selecting the input for limit.
Setpoints must have the correct resolution and dimension as protection source value.
Existing setpoint
New user setpoint
Existing user setpoint
Prefix is added to the name based on protection type / level
Selecting the input for delay.
Setpoints must have the correct resolution 0.1 and dimension [s]
Existing setpoint
New user setpoint
Existing user setpoint
Prefix is added to the name based on protection type / leve

InteliNeo 6000 1.5.0 Global Guide 208


Adding binary protection

Selecting the input source see User protections on page 205

Selecting the protection type see Protection types on page 198

Text input for Alarm / History message

Selecting the protection activation see Protection activation on page 200

Selecting the block type see Protection blocking on page 200

InteliNeo 6000 1.5.0 Global Guide 209


Selecting if the occurence of a protection is recorded every time or only once after a Fault
Reset.

If Protection State is checked the protection is then shown in setpoints under the group User
setpoints.

Selecting the input for delay.


Setpoints must have the correct resolution 0.1 and dimension [s]
Existing setpoint
New user setpoint
Existing user setpoint

6 back to Protections

Protection states
Protection states is a new feature introduced inInteliNeo 6000, which helps with better management of alarms.
Until now, you could only use LBO ALARM (PAGE 1053) which did not specify what is going on. Protection states
work in similar way, like any other LBO. The difference is, that protection state gets active only when there is
specific alarm present in the alarm list. Thanks to this, you can create PLC logic, which will react to specific
alarms only.

Fixed protection states


Important Fixed protections (page 200) have a protection state. The protection state is (usually) named exactly
as the alarm. Fixed protection states are in a group of 32.
Protection states groups:
FIXED PROTECTIONS STATES 1 (PAGE 1180)
FIXED PROTECTIONS STATES 2 (PAGE 1181)
FIXED PROTECTIONS STATES 3 (PAGE 1182)
FIXED PROTECTIONS STATES 4 (PAGE 1183)
FIXED PROTECTIONS STATES 5 (PAGE 1184)
FIXED PROTECTIONS STATES 6 (PAGE 1185)
FIXED PROTECTIONS STATES 7 (PAGE 1186)

User protections states


During the Configuration of protections in InteliConfig (page 205), you can decide whether you want to add
user protection state for the protection. The name is exactly same as the alarm's message.
When you're adding user protection state, it will try to fill in gaps (if there are any present) in an actual list of User
Protection States (page 1188), if there is no gap, it will be automatically added to the end. User protection
states are in a group of 32 with maximally 10 groups i.e. 320 user protection states are available.
Note: Group of User protection states is showed only when there is at least 1 protection state in it.

6 back to Protections

InteliNeo 6000 1.5.0 Global Guide 210


5.4.30 Pulse Counters
InteliNeo 6000 has 4 internal counters 2 of them are physically configured to the specific binary inputs which
makes them faster than another 2 "slow" pulse counters which are using LBIs. Value of the each pulse counter is
increased by one step whenever the number of pulses counted reaches the value of setpoint Conversion
Coefficient Pulse. The fast pulse counters are able to count reliably pulses longer than 10 ms ON / 10 ms OFF
whereas the "slow" pulse counters are able to count reliably pulses longer than 200 ms ON / 200 ms OFF.

Conversion setpoint Value Binary Input


Conversion Coeff. Fast Pulse 1 (page Fast Pulse Counter 1 (page
BI9
390) 883)
Conversion Coeff. Fast Pulse 2 (page Fast Pulse Counter 2 (page
BI10
390) 884)
Conversion Coefficient Pulse 1 (page PULSE COUNTER 1 (PAGE
Pulse Counter 1 (page 884)
391) 1018)
Conversion Coefficient Pulse 2 (page PULSE COUNTER 2 (PAGE
Pulse Counter 2 (page 884)
391) 1018)

Note: Value of the internal counters remains even if the controller is unplugged from power.

Note: Counter counts leading edges.

InteliNeo 6000 1.5.0 Global Guide 211


5.4.31 PV Inverter Slots
This chapter deals with the integration of PV and possibly WT into a microgrid system. For applications with
InteliNeo6000 with a larger range of PV usage, it is typical that PV is integrated into the system using multiple
inverters. InteliNeo6000 then communicates with individual inverters independently, obtains data from them and
commands them.
The set of signals from each inverter always has the same format for PV looks like this:

Image 5.111 PV Invertor Slots configuration

InteliNeo 6000 1.5.0 Global Guide 212


Image 5.112 Aggregated values from all PV slots and individual values of each PV slot

Each of these sets can be seen as a separate channel (slot) through which InteliNeo6000 aggregates signals
from individual inverters as PV quantities. InteliNeo6000 supports up to 16 PV inverters in this way. The
configuration, i.e. the binding of these LAI values to the datapoints read from the individual inverters, must be
done manually (the binding is done automatically only in case of a single PV inverter configuration).
Aggregation of all acquired signals into common quantities is already automatic and therefore it is not
necessary to aggregate the common quantities using user logic in the PLC. The common PV quantities can
then be monitored in the controller as PV Aggregated quantities. Incidentally, the quantities integrated by the
individual PV channels can also be monitored in the PV quantity group.

In the case of WT support, the situation is very similar. InteliNeo6000 supports up to 8 WT inverters. The
system aggregates the total quantities of all data which are available. Thus, even just one channel (slot) is
enough to provide valid data. If the device, that is configured to a particular slot, is not communicating, is out
of service or in error (device error and subsequent inability to supply to the common bus is detected by LBI PV
X operable), then its values are simply not included in the aggregated data.

InteliNeo 6000 1.5.0 Global Guide 213


Communication with InteliGateway 300
InteliNeo6000 allows up to 16 Modbus devices to be connected directly via the integrated Modbus Client
(Master) (page 176) function. In certain cases (if it is necessary to connect more modbus devices than 16), there
is the possibility to provide communication with InteliNeo6000 via the InteliGateway 300 (page 32)
communication bridge (gateway). In this case, the aggregation of common data from multiple PV inverters takes
place on the InteliGateway 300 (page 32) side. The acquired data then enters into InteliNeo6000 via the
inverter slots (LBIs and LAIs) as if it were a single PV inverter. The InteliGateway 300 (page 32) in this case
works as a data concentrator and virtualizes multiple inverters into a single PV system.
More information about InteliGateway 300 (page 32) is available at this link: inteligateway-300
6 back to PV Inverter Slots

InteliNeo 6000 1.5.0 Global Guide 214


5.4.32 SD Card Storage
IMPORTANT: Only SanDisk Industrial XI microSD Cards (vendor order codes SDSDQAF3–xxxG-
XI) are currently supported.

Note: 16 GB Industrial memory card is also available in ComAp portfolio (ComAp product number
OT1C16GBXQX)

The controller is equipped with a ⑤ SD Card (page 46) slot for a possibility of storing large amount of data.

Formatting process

IMPORTANT: It is strongly recommended to perform the formatting of SD Card in OFF mode.

Alarm ALI SD Card Formatting/Mounting (page 1274) is displayed during the formatting process.
After changing the setpoint SD Card File System (page 401) to Format, the controller checks whether the
inserted SD card is supported - ALI SD Card Not Compatible (page 1273) alarm is displayed if it is not. If the
formatting is not successful, the value SD Card Status (page 889) shows Formatting Failed, the alarm ALI
SD Card Not Compatible (page 1273) is activated, and controller will not try formatting process again SD Card
File System (page 401) is automatically set to Mounted).
If the formatting is successful, the SD Card File System (page 401) is automatically changed to Mounted and
the card is ready for operation.

Mounting the SD Card


For enabling the SD card functions, setpoint SD Card File System (page 401) has to be set to option Mount.
IMPORTANT: It is strongly recommended to perform the mounting of SD Card in OFF mode.

Alarm ALI SD Card Formatting/Mounting (page 1274) is displayed during the mounting process.
In case that it is not possible to read or write to the SD Card, alarm Wrn SD Card Failed (page 1265) is
activated. The alarm is also activated in case the SD card is not inserted. See the value SD Card Status (page
889) for further information about the fail.
Alarm ALI SD Card Full (page 1274) is displayed if value SD Card Free Space drops below 10 %.
In case that the card has a wrong file system, alarm Wrn SD Card File System Failed (page 1265) is displayed.
Therefore formatting process should be performed again.

Unmounting the SD Card


If the setpoint SD Card File System (page 401) is set to Unmount, the controller is able to detect the SD card,
but it will not do any reading or writing of the data. The SD Card Status (page 889) will show Unmount, and in
case the card is still in the slot, the alarm ALI SD Card In Slot (page 1274) is issued.

Long term history


If an SD Card is successfully mounted, the controller is able to store history records onto the SD Card. This
function is activated by adjusting setpoint Long Term History (page 401) to Enabled.
Long Term History data are stored in folder named "HISTORY_SN" wheren SN is serial number of respective
controller that stored the data. Inside this folder there is another folder named "YYMMDDhhmmss" which is
created at the moment of switching the setpoint Long Term History (page 401) to Enabled. Inside this folder
you may find two files:

InteliNeo 6000 1.5.0 Global Guide 215


SN_YYMMDDhhmmss.hist - which contains history records.
SN_YYMMDDhhmmss.cfg - which contains important related data required in order to elaborate history
records.

Reading the data


1. Download the history records files from your SD card into the PC.
2. Open the InteliConfig, go to Tools and select Long Term History.
3. In the opened window choose the Input directory (destination of the SN_YYMMDDhhmmss.hist file) and
Output directory.
4. Choose Delimiter parameter and press Start.
5. The file containing the readable data should be created at the Output directory when conversion is
finished.

5.4.33 Sensor Curves


Default sensor curves
There are 16 default resistive curves available. The following table provides information on minimum/maximum
values of respective sensors. Actual values especially of temperature curves may differ.

Curve Min X [Ω] Max X [Ω] Min Y Max Y Units Y


General line 1 0 1 0 1 Ω
General line 2 0 1 0 1 Ω
General line 3 0 1 0 1 Ω
General line 4 0 1 0 1 Ω
General line 5 0 1 0 1 Ω
General line 6 0 1 0 1 Ω
General line 7 0 1 0 1 Ω
General line 8 0 1 0 1 Ω
General line 9 0 1 0 1 Ω
General line 10 0 1 0 1 Ω
General line 11 0 1 0 1 Ω
General line 12 0 1 0 1 Ω
General line 13 0 1 0 1 Ω
General line 14 0 1 0 1 Ω
General line 15 0 1 0 1 Ω
General line 16 0 1 0 1 Ω

Note: Curves can be modified via InteliConfig. In InteliConfig are also prepared some standard curves.

Sensor curve HW configuration


InteliNeo 6000 analog inputs allows you to select Input HW type. Three HW configuration options are available:

InteliNeo 6000 1.5.0 Global Guide 216


0-15 kΩ
0-10 V
0-20 mA passive
Setup controller analog input in this way to use other than the default HW configuration (0-15 kΩ):
1. Start with a sensor configuration and select requested HW configuration

2. Use the adjusted sensor with an analog input and the requested HW configuration will be used with the analog
input automatically. There is no need to use a jumper, configured Input HW type is used by controller
automatically.

InteliNeo 6000 1.5.0 Global Guide 217


5.4.34 Service Timers
Maintenance timers
There are 4 maintenance timers which are used as counters which are counting down months and BESS running
hours. How much months / BESS running hours will be counted down is setup by the setpoints Maintenance
Timer Interval / Maintenance Timer RunHours. The actual state of the timer is visible in the values Maintenance
Timer RunHoursOnce / Maintenance Timer Interval. Once any timer reach zero value (days / running hours) the
alarm Maintenance Timer RunHours/ Maintenance Timer Interval will be activated together with the LBO AL
Maintenance. The type of the alarm (Wrn / Sd) can be defined by the setpoint Maintenance Timer Protection.
Each timer has its Setpoints, Values, Alarms and LBOs according to the table below.

Maintenance Timers Maintenance Timers Maintenance Timers Maintenance Timers


1 2 3 4
Maintenance Timer Maintenance Timer Maintenance Timer Maintenance Timer
1 RunHours (page 2 RunHours (page 3 RunHours (page 4 RunHours (page
656) 658) 659) 661)
Maintenance Timer Maintenance Timer Maintenance Timer Maintenance Timer
Setpoints 1 Interval (page 2 Interval (page 3 Interval (page 4 Interval (page
657) 658) 660) 661)
Maintenance Timer Maintenance Timer Maintenance Timer Maintenance Timer
1 Protection (page 2 Protection (page 3 Protection (page 4 Protection (page
657) 659) 660) 662)
Maintenance Timer Maintenance Timer Maintenance Timer Maintenance Timer
1 RunHours (page 2 RunHours (page 3 RunHours (page 4 RunHours (page
881) 881) 882) 882)
Values
Maintenance Timer Maintenance Timer Maintenance Timer Maintenance Timer
1 Interval (page 2 Interval (page 3 Interval (page 4 Interval (page
881) 882) 882) 883)
Maintenance 1 Maintenance 2 Maintenance 3 Maintenance 4
RunHours (page RunHours (page RunHours (page RunHours (page
1322) 1323) 1324) 1324)
Alarms
Maintenance 1 Maintenance 2 Maintenance 3 Maintenance 4
Interval (page Interval (page Interval (page RunHours (page
1322) 1323) 1323) 1324)
AL Maintenance 1 AL Maintenance 2 AL Maintenance 3 AL Maintenance 4
LBOs
(page 1052) (page 1052) (page 1052) (page 1052)

Running hours counters


There are 8 running hours counters. One counter is used as a basic running hours counter and it is incrementing
whenever the BESS is turned on. The other two counters are conditioned so they are incrementing when the
condition is fulfilled. The condition is fulfilled once the proper LBI is activated. See the table below.

Running Hours Conditioned Hours Counter 1 Conditioned Hours Counter 2


Running Hours Conditioned Running Hours 1 Conditioned Running Hours 2
Values
(page 880) (page 880) (page 880)

InteliNeo 6000 1.5.0 Global Guide 218


Universal Hours Counter 1 Universal Hours Counter 2
LBI N/A
(page 995) (page 995)

5.4.35 Sunrise/Sunset
Based on GPS coordinates, date and actual timezone can controller calculate real sunrise and sunset time.
This functionality is enabled/disabled by setpoint Sunrise/Sunset Function (page 631) and works in all
controller modes. Setpoint Sunrise/Sunset Latitude (page 632) and setpoint Sunrise/Sunset Longtitude
(page 632) are automatically set from GPS module. If coordinates are valid. they will be written on the rising
edge of LBI SUNRISE/SUNSET HOME POSITION (PAGE 1029). Otherwise, these setpoints need to be set
manually. Values Sunrise Time (page 901), Sunset Time (page 902), Time To Sunrise (page 902),
Time To Sunset (page 902) are calculated from setpoints Sunrise/Sunset Latitude (page 632) and
Sunrise/Sunset Longtitude (page 632). LBO DAY/NIGHT (PAGE 1069) is active during the day (between
Sunrise and Sunset Time).

5.4.36 Sunspec
SunSpec is an application-layer communications protocol designed to achieve interoperability between
Distributed Energy Resource (DER) components and smart grid applications. SunSpec has not static Modbus
registers, it uses block of registers in predefined order, but for each device is necessary to calculate Modbus
address. Register blocks are in row (where first ends, second starts).

5.4.37 System Start/Stop


There is a LBI GENERIC GENSET START/STOP (PAGE 1004) that is used to start and stop BESS remotely in AUT
mode.
In case of using System Start/Stop functionality with multiple controllers proper configuration of the system is
necessary to ensure correct operation. For the system using just CAN wiring no physical wiring of binary logic is
needed to share the starting and stopping signal into all controllers in the same group. LBI GENERIC GENSET
START/STOP (PAGE 1004) should be configured in one "master" controller which will be used to control starting
and stopping of other controllers in the group. All controllers with configured LBI GENERIC GENSET START/STOP
(PAGE 1004) will be started only if their LBI is activated.

5.4.38 SW Key Features


The controller offers premium features which are unlocked by software key.
The SW key is stored in setpoint SW Key (page 388) which is protected against rewriting during configuration
update. Value SW Key Feature List (page 891) contains actual list of features which requires SW key in order
to be used. When there is logical 1 respective function is unlocked and can be used without of limitation.
Note: Each SW Key is unique and valid only for specific serial number of a controller.

Using of SW Key
Insert your SW Key into setpoint SW Key (page 388)
Restart the controller
Check value SW Key Feature List (page 891) whether functions were unlocked

InteliNeo 6000 1.5.0 Global Guide 219


Note: Please contact technical support in case that functions which were supposed to get unlocked after
inserting the SW key did not get unlocked

List of SW Key Features


SW Key Feature More information Order Code
CAN Intercontroller Communication Redundancy
CAN bus redundancy SKREDCAN201
(page 132)

Hot Swap Redundancy Hot Swap Redundancy (page 160) SKHOTSWAP01

IMPORTANT: Activation of deep Sea CAN software key will replace ComAp communication protocol
on intercontroller CAN line. This will prevent communication to ComAp controllers connected via
CAN2.

5.4.39 Universal Genset support


UGS (Universal Genset Support) is a feature that allows for the integration of gensets with third-party
generator controllers to operate in parallel with a microgrid controlled by InteliNeo 6000. This solution allows
InteliNeo to recognize and observe gensets connected over Modbus to optimize the penetration of DER
(distributed energy resources) to generators without the replacement of the original controller provided they
meet the prerequisites of this function.
InteliNeo 6000 supports 16 genset controllers in the following applications:
Off-grid: InteliNeo 6000 + UGS
On & Off-Grid: InteliMains + InteliNeo 6000 + UGS

IMPORTANT: Combining third-party genset controllers via Universal Genset Support in IN6000
and IN5500 with InteliGen/InteliSys over CAN communication within one system is NOT
RECOMMENDED.

There can be only one control unit inside the system integrating UGS. That is, single Neo with UGS active
within a system.
For systems where UGS is used with InteliMains, the slip synchronization method in InteliMains is
required for reverse synchronization. Refer to InteliMains Global Guide for on-grid application.
The total group power supported by UGS is limited to 32.8 MW.
All gensets must operate on a common bus.

InteliNeo 6000 1.5.0 Global Guide 220


Image 5.113 Example of Universal Genset Support with InteliNeo 5500/6000 & InteliMains

Start/Stop Request & Power Management with BESS


With UGS feature active, all setpoints previously related to Power Management like operation based on
priority and load reserve-based start/stop will apply to UGS instead of BESS in InteliNeo.
It means that the BESS together with PV system will be used as the primary source and always used first to
support the loads. Genset is only called to start when the load reserve in the BESS is not able to cover the
actual settings or when the BESS SOC is low.

Generator Controller Requirements


For the operation of Universal Genset Support in InteliNeo 5500 & 6000, the gensets are expected to have
the following functionalities:
Fitted with parallelling and synchronization controllers of the same model/ manufacturer.
Must have grid forming capability when operating in Island-mode.
Genset controllers must have their own load-sharing and VAr-sharing capability in Island-mode.
Genset controllers must respond to communication signal via AIN/BIN or Modbus TCP/ RTU (preferred)
Ability to conduct forward synchronization - genset incomer must be fitted with a Generator Circuit Breaker
(GCB) with control for synchronizing if paralleling with another VF source such as BESS.

Communication
InteliNeo 6000 controllers have a Modbus client onboard that can interface over RTU or ethernet to third-party
generator controllers, which will operate in a Modbus server position.
IMPORTANT: For UGS, values need to be written periodically and repeatedly by InteliNeo Modbus
client to genset controllers. Users must check that the relevant Modbus registers can be written
long-term without damage to the device memory.

For communication between third-party genset controller and InteliNeo 6000, the genset controller can be
integrated into the configuration of InteliNeo via the ECU library as a User Defined Modbus device or selected
from the list of available devices.

InteliNeo 6000 1.5.0 Global Guide 221


Once the UG is set up as an ECU module, manually assign logical input and output as below based on your
desired application.
Off-grid: Refer to table Off-Grid Logical Input/Outputs below.
On & Off-Grid: Refer to tables Off-Grid Logical Input/Outputs and On-Grid Logical Input/Outputs
below.

Off-Grid Logical Input/Outputs


Read/ Signal
Value Connected To Description
Write Type

LAI: Uni Gen The format (resolution) of this value must correspond to
Actual Active Power P, kW R Analog 1…16 Actual the Power Format selected in InteliNeo (0,1 kW, 1kW, 0,01
P MW).
LAI: Uni Gen The format (resolution) of this value must correspond to
Actual Reactive Power Q, kVar R Analog 1…16 Actual the Power Format selected in InteliNeo (0,1 kVAr, 1kVAr,
Q 0,01 MVAr).
LAI: Uni Gen The format (resolution) of this value must correspond to
Nominal Power Rating, kW R Analog 1…16 the Power Format selected in InteliNeo (0,1 kW, 1kW, 0,01
Nominal P MW).
GCB closed - GCB Connected to LBI: Uni Gen
This is information about the UG GCB status. This signal is
the bus and Loaded (in load R Binary 1…16 GCB
supposed to be active anytime the GCB is closed.
sharing) Closed
Genset Loaded - GCB Connected
LBI: Uni Gen This signal notifies InteliNeo that UG loading process has
to the bus but genset is not in soft R Binary
1…16 Loaded finished or is not in unloading process.
load/soft unload process.
This signal is crucial for safe operation if the UG is
supposed to perform energizing of the dead bus. In
InteliNeo it is used as signal blocking closing of the BCB to
the dead bus. InteliNeo propagates this information to all
LBI: Uni Gen other controllers in the system. The closing of the breaker
Closing GCB to dead bus R Binary 1…16 GCB to the dead bus is blocked in all the controllers within the
Closing system until this signal is active.Important: InteliNeo does
not propagate this information towards to other UGS. UGS
must manage this function themselves within the group. It
is strongly recommended to use the hard wiring of this
signal between InteliNeo and UG.
UG Run Request is influenced by Power Management
(Load demand start/Stop) in AUTO mode and is issued
Value: Uni
only if the system needs to start UGS to cover the
UG Run Request W Binary Gen 1…16
requested load reserve.
Run Request
This signal is connected to LBI Universal Genset
Start/Stop must be configured.
This signal is crucial for safe operation in case that UGS is
enabled to close its GCB to the dead bus and make it
energized. The InteliNeo generates a 200ms long pulse
Value: Uni
any time when any controller in the system is about to
Gen 1…16
Block GCB from closing W Binary close the CB to the dead bus. This information must be
Stop GCB
used in UGS to prevent the closing of the GCB to the dead
Closing
bus. It is strongly recommended to hardwire this signal
between InteliNeo and UGS. This signal is connected to
LBI Uni Gen 1...16 GCB Closed.

InteliNeo 6000 1.5.0 Global Guide 222


Read/ Signal
Value Connected To Description
Write Type

This value is aggregated to the Gen kWh statistic and all


LAI: Uni Gen
Run-time, kWh R Analog other interval statistical values: Gen Annual kWh, Gen
1…16 kWh
Monthly KWh, Gen Weekly KWh, Gen Daily kWh.
This value is aggregated to the Fuel Used statistic and all
LAI: Uni Gen
Fuel R Analog other interval statistical values: Fuel Annual, Fuel Monthly,
1…16 Fuel
Fuel Weekly, Fuel Daily.
LBI: BESS
Remote
Start/Stop Allow to starting/stopping the BESS and UGs
Start/Stop Request R/W Binary
LBI: Universal independently via InteliNeo.
Genset
Start/Stop

On-Grid Logical Input/Outputs


Read/ Signal
Value Connected To Description
Write Type

MCB Status
Feedback – inform
This signal requests UG to switch to P/Q control mode based on
genset it is in
W Binary LBO: MCB Status MCB status signaling on-grid operation. In the UG it should be
parallel to mains
connected to the MCB feedback input.
and operate in P-Q
mode
This LBO is used if UGS is to be reversely synchronized to the
Mains. InteliMains cannot influence UGS directly, so we need to use
the slip synchronization process.LBO Reverse Sync in InteliMains
Frequency offset LBO: Reverse
makes the UGs run with certain slip frequency, and InteliNeo writes
request/nominal W ANA/BIN Synchronization in
offset to the Nominal Frequency setpoint or sends Binary input to
frequency setpoint InteliMains
switch the nominal frequency to the offset value. Configuration must
be via DISTIN/DISTOut modules for sharing this information
between InteliMains and InteliNeo.
This value is to be used as total baseload active power request for
Value: Uni Gen
the group of universal gensets. This value is also distributed to all
Requested P (rel. Requested P or
W Analog universal genset channels as baseload P for each genset e.g. Uni
% / abs kW) Uni Gen Relative
Gen 1 Requested P. Alternatively, it can be associated with the
Requested P
relative value: Uni Gen Relative Requested P.
This value is to be used as total baseload reactive power request for
Value: Uni Gen
the group of universal gensets. This value is also distributed to all
Requested Q (rel. Requested Q or
W Analog universal genset channels as baseload Q for each genset e.g. Uni
% / abs kW) Uni Gen Relative
Gen 1 Requested Q. Alternatively, it can be associated with the
Requested Q
relative value: Uni Gen Relative Requested Q.

Setpoints
When the Universal Gensets (UG) are connected to InteliNeo with setpoint "Universal Genset Address", UG
is recognized as a virtual source in the system. The information about this virtual genset, recognized as a
singular group, can be seen in all genset related information inside the system like CAN 16, CAN 32, GL 16,
GL 32, Reg 16, Reg 32 Values.
Setpoint Group Setpoint Name Recommended Value Description

Universal A unique numerical value must be set for UGS function to be active
Communication Set value +1 to InteliNeo
Genset and recognized as virtual genset by InteliNeo.Values> Universal
Settings Controller Address
Address Gensets will only be visible once this setpoint ≠ OFF.

InteliNeo 6000 1.5.0 Global Guide 223


Note: For InteliNeo 5500, if SW key is missing and Universal Genset Address setpoint ≠ OFF, there will be a
warning in InteliConfig.

Values & Statistics


Values of UGS are collected through each separate channel and displayed as values in Universal Genset
Group. InteliNeo makes an aggregation of the data from each channel to aggregated values - available in
Values in the Group Universal Gensets.

5.4.40 User Buttons


User Buttons can be used to assign function of user's choice to button on the External display (page 79) or like
remote switch. There are 32 user buttons and the behavior of each of them can be adjusted by it's relative
setpoint.
Each setpoint has these options:

Option Description

COMMAND The relative User Button is controlled by command from External display (page 79).
The relative User Button is controlled manually via the setpoint. Value of the user button
MAN OFF
is still 0.
The relative User Button is controlled manually via the setpoint. Value of the user button
is still 1.
MAN ON
Note: You should always switch from MAN ON to MAN OFF before switching to
COMMAND, otherwise value of the User Button will be 1 until command is received.

Commands
If relative setpoint is set to COMMAND, the User Button will react to commands sent via button from External
display (page 79). Type of command is selected during controller configuration in Screen Editor.
There are following commands:

Command Description
While this command is selected, pressing the button negate the actual value of the user
ON/OFF
button
While this command is selected, pressing the button sets the actual value of the user
ON
button to 1.

InteliNeo 6000 1.5.0 Global Guide 224


Note: Will not have any effect if the value is already 1.
While this command is selected, pressing the button sets the actual value of the user
OFF button to 0.
Note: Will not have any effect if the value is already 0.
While this command is selected, pressing the button sets the actual value of the user
Pulse ON button to 1 for 200 ms.
Note: The command reacts only to rising edge of the button.

See list of MODBUS comands in chapter List of commands and arguments (page 324).

Configuration of user button command


To configure Command on User Button, navigate to Configuration in InteliConfig

Select Screen Editor tab

Select Status bar

Add "Button CMD", for example to position

Select required user button and COMMAND

InteliNeo 6000 1.5.0 Global Guide 225


5.4.41 User Management And Data Access Control
Types of interfaces 226
User accounts 227
Managing accounts 229
Account break protection 231
Access to controller data 232
Accessing, monitoring and controlling the device via any communication interface require an user to be
logged-in.
When a task (read data, write data , control) is to be performed the access level of the user who is
currently logged-in must be higher or equal to the access level required for the particular task.
User must have user account defined by the administrator of the controller before the user can log-in into
the controller and perform monitoring, control or configuration tasks.

Types of interfaces
The controller communication interfaces are split into three categories according to what kind of environment the
interface is exposed.
Trusted
Are USB Type B (page 19) and in the default configuration Ethernet 1 (page 19) terminals.
It is expected that these interfaces are operated locally inside a closed environment / infrastructure where
additional measures against misuse or attack take place (e.g. physical access limitation).
Due to nature of this interface less strict cyber-security rules apply at it and that is why Implicit account is
introduced here to make working with the controller simpler.
Untrusted
Is in the default configuration Ethernet 2 (page 19) terminal.
This interface is a general-purpose one and it is expected that it may be exposed to public networks, such
as Internet, which are not under control of the entity operating the controller.
Thus, strict cyber-security rules apply for this type of interface.
The correct user account with password has to be used in order to connect to the controller.
This interface can be also used for SMTP and SNMP protocols.
Modbus
Is in the default configuration Ethernet 3 (page 19) terminal.
This interface is used for Modbus Client (Master) (page 176) or server.
It is expected that this interface is operated locally inside a closed environment / infrastructure where
additional measures against misuse or attack take place (e.g. physical access limitation).
Due to nature of this interface and fact that it is not possible to use it for connection to the controller, less
strict cyber-security rules apply at it.

Connections to ethernet interfaces


Either ComAp clients (InteliConfig, WebSupervisor, WinScope, InteliVision displays, etc.) or Modbus clients
can connect to the controller's ethernet interfaces. Number of possible connections is listed in the table below.

InteliNeo 6000 1.5.0 Global Guide 226


Type of interface ComAp clients Modbus clients
Trusted 6 3
Untrusted 8 3
Modbus 0 3

Example: If Ethernet 1 (page 19) = Trusted, Ethernet 2 (page 19) = Trusted, Ethernet 3 (page 19) =
Trusted, then it is possible to connect 6 ComAp clients and 3 Modbus clients on all three ports in sum.

Example: If Ethernet 1 (page 19) = Trusted, Ethernet 2 (page 19) = Untrusted, Ethernet 3 (page 19) =
Modbus client, then 6 ComAp clients and 3 Modbus clients can be connected to Ethernet 1 (page 19), 8
ComAp clients and 3 Modbus clients can be connected to Ethernet 2 (page 19) and 3 Modbus clients can
be connected to Ethernet 3 (page 19).

6 back to User Management And Data Access Control

User accounts
User account must be created in the controller by administrator before the particular user can login to the
controller.
Note: User accounts must be created for each controller separately and manually. It is not possible to transfer
the accounts from one controller to another.

User account has following properties:

Consists of 6-15 alphanumeric characters, must contain at least 1 letter. This


Username
is the main identifier of the particular user account.
Consists of 6-15 alphanumeric characters, must contain at least 1 letter and 1
Password digit. This is the password that is used together with user name to
authenticate (log-in).
Optional 4-digit identification string which can be used for simplified login at
User identifier (UID) trusted interfaces (e.g. from InteliVision display when connected via Ethernet
1 (page 19)).
PIN 4-digit “password” to be used together with UID.
Access level Determines Access to controller data (page 232)
Role mask Determines Access to controller data (page 232)

User login
To login to the controller the username and password must be provided into the login form of the
application (InteliConfig (page 22), WebSupervisor (page 22), External display (page 79) etc.).
Alternatively, at trusted interfaces, it is possible to login using UID and PIN instead of username and
password. This method of login is designed to simplify the login procedure at devices without alphanumeric
keyboard (e.g. InteliVision).
Note: The controller is featured with a protection against brute force attack to user account credentials. For
details please refer to the - Account break protection (page 231)

InteliNeo 6000 1.5.0 Global Guide 227


Changing password and PIN
The password and/or PIN for currently logged user can be changed. The user must be logged with username and
password even if PIN has to be changed.

Implicit account
There is one implicit user account in the system. This user account can not be deleted. This account is
automatically logged in at a trusted interfacewhile communication channel is open and there is not any other
user logged in. The account is fixedly assigned to role 1.

Production mode
The Production mode is intended to simplify manufacturing process for OEMs. While production mode is active
the implicit user is fixedly member of role 0 (administrator role) and alarm Wrn Production Mode (page 1) is
displayed. Practically it means that while production mode is active it is possible to perform any operation with the
controller without any user needed to login.
WARNING: Production mode must be disabled before the controller is put into regular operation.

Note: Production mode can be turned off either from InteliConfig or from InteliVision 5.2.

Factory default accounts


Each controller comes from the production with one factory default administrator account having following
credentials:
Username: “administrator”
Password: <serial number of the controller>
This account is member of role with index 0 (administrator role)
When the controller is being configured for operation the desired user accounts including the administrator
account should be created and then the factory default account must be deleted.
The controller issues warning alarm Wrn Default Password (page 1251) all the time the above default account
(username and password) is present in the controller.
IMPORTANT: Adjust the backup e-mail address before you delete the default administrator account. This
address is used as second authentication factor in password reset request and the password reset action
code will be sent to this and only this e-mail address.

Administrator account
There may be multiple accounts which are members of the administrator role. There must always remain at least
one account with administrator role.
Note: there must always remain at least one administrator account in the system. The controller will not allow
deleting last administrator account.

Reset accounts to factory default


If credentials (username and/or password) for administrator account are lost, it is possible to reset all user
accounts to the factory default state.
1. Connect InteliConfig to the controller

InteliNeo 6000 1.5.0 Global Guide 228


2. Read the Password Reset Request Code (PRRC)

3. You may disconnect from the InteliConfig now


4. Put the PRRC code into the “IntelliBot” application at https://www.comap-control.com/support or e-mail the
code to support@comap-control.com.
5. A unique, one-time Password Reset Action Code (PRAC) will be sent to the backup e-mail address adjusted in
the controller.
6. Connect via InteliConfig to the controller again
7. Enter the Password Reset Action Code into the appropriate form

8. Now the user accounts are in factory default state


6 back to User Management And Data Access Control

Managing accounts
User accounts can be managed from InteliConfig while an online connection to the controller is established. The
right to manage accounts is explicitly and fixedly given only to administrator role (index 0). This right can not be
granted to any other role. The administrator must be logged with username/password and is prompted to re-enter
accounts password before the user management dialog is opened.
IMPORTANT: The total available number of accounts in the controller is 30.

InteliNeo 6000 1.5.0 Global Guide 229


Adding account
Click on “+” button in the lower left corner of the user management window, then provide the account properties
as described in User accounts (page 227).
Note: Rules for the User accounts (page 227) credentials apply and some items are optional

Deleting account
Select the account that has to be deleted and click on “-“ button in the lower left part of the user management
window.
Note: you can not delete your own administrator account unless there is another administrator account present
in the controller.

Deleting account properties


Select the account that has to be deleted and click on “-“ button in the lower left part of the user management
window. Then modify the desired property or properties. You can modify one or more properties at once.

InteliNeo 6000 1.5.0 Global Guide 230


Note: It is not possible to change user name or UID. Instead of this create a new account with the required
changes and delete the original one.

6 back to User Management And Data Access Control

Account break protection


The controller is protecting the user accounts against breaking by a brute-force attack, i.e against breaking into
the controller by fast repeating attempts to login with credentials generated from the range of all possible
combinations.
If the account break protection detects a possible attack and blocks an account or interface the alarm Wrn Brute
Force Protection Active (page 1250) is activated. The alarm can be used to send an active message (e.g. e-
mail) to inform about that situation The detailed behavior of the controller depends on situation.

Password protection
1. If an user performs five consecutive attempts to login using username/password, providing correct
username but incorrect password, the respective user account is blocked for a time period of 1
minute. The attempts count regardless of the interface from which it is performed.
2. During the blocking period it is not possible to login with the respective account (username) from any
interface even if correct password is provided.
3. After the blocking period elapsed next attempt to login with the respective account (username) is possible.
If this attempt fails again the account is blocked again, now for period of 2 minutes.
4. The points 1-3 repeats further, the blocking period is multiplied by 2 in each next cycle. However, the
maximal blocking time is 20 minutes, the blocking time is never higher.

PIN protection
If an user performs ten consecutive attempts to login using UID/PIN, providing correct UID but incorrect PIN,
the user account is permanently blocked for login using UID/PIN. The user must login with username/password
and change the PIN to unblock this login method again.

Interface protection
If anyone performs twenty consecutive attempts to login via one particular interface (e.g.Ethernet 1 (page
19)) and does not neither provide a valid username nor a valid uid the respective interface is blocked for 2
minutes. During this period it is not possible to use that interface for any login. The blocking period is not
progressive in this case.

InteliNeo 6000 1.5.0 Global Guide 231


6 back to User Management And Data Access Control

Access to controller data


Every request for reading data from the controller or writing data into it requires an user to be logged and that
user must have access rights higher or equal to the role defined for the particular object and operation.
Access right is the relation between an User and an Object inside the controller.
There are 10 roles with indexes 0..9 in the system.
Role 0 is administrator role. All objects/commands are fixedly assigned to this role.
Roles 1..7 are configurable roles. Each communication object/command can be assigned independently
to each of these roles.
Role 8 is Modbus client. Each communication object/command can be assigned to this role.
Role 9 is SNMP Manager. Each communication object/command can be assigned to this role.

Note:
Modbus and SNMP clients do not have implicit access to all objects. The access is limited by mapping
tables present in configuration. So, successful writing of an object require that object 1) to be present in
the respective mapping table, 2) to be assigned to the respective role.
Example: If a setpoint X shall be adjustable by Modbus this setpoint must be 1) mapped to a holding
register, 2) assigned to role 8.

Reading data
For each object the Access right "Read" (R) is fixedly granted to each role*. That means reading of data (except
some system objects) is available for any user.

Writing data
For each object the Access right "Write" (W) can be granted to one or more roles (indexes 1..9). For each object
the Access right "Write" (W) is fixedly granted to administrator role (index 0).

Special situations
There are several operations that require administrator role:
Programming firmware
Programming configuration
Managing user accounts. This right can not be granted to any other role.

6 back to User Management And Data Access Control

5.4.42 User Setpoints


Controller allows user to create their own setpoints, groups and subrgroups. You can also edit and delete the
created setpoints/groups/subgroups and choose a group in which the setpoint or subgroup will be located.
Number of setpoints created by user is limited to 2047. The Comm. object number (CO) can be found via
InteliConfig (Tools tab → Generate Cfg image (COM)). User setpoints can be used to manage User protections
and PLC.

InteliNeo 6000 1.5.0 Global Guide 232


Add Groups/Subrgoups or User setpoint

Delete selected Groups/Subrgoups or User setpoint

Edit selected Groups/Subrgoups or User setpoint

Image 5.114 User setpoints tab in InteliConfig

Image 5.115 Setting parameters of Group/Subgroup

InteliNeo 6000 1.5.0 Global Guide 233


Image 5.116 Setting parameters of an user setpoint

Contents of the user Group/subrgroup


Max. 32 characters
Name Note: Does not consider duplicities (It is possible to have groups/subgroups with the
same name, but it is not recommended.)
Type Group type can be Group or Subgroup.
If you are creating a subgroup, parent group must be selected from created groups,
Parent group
except for exceptions.

Contents of the user setpoint


Max. 32 characters
Name Note: Does not consider duplicities (It is possible to have setpoints with the same
name, but it is not recommended.)
Can be chosen from a list or
Dimension
User can create their own with a limit of 32 characters.
Resolution Max. 4 decimal place
Range of the data type INT32 (restricted by resolution).
Low Limit Value is set as a constant (can not be set as setpoint).
Max. value cannot exceed High Limit.
Range of the data type INT32 (restricted by resolution).
High Limit Value is set as a constant (can not be set as setpoint).
Min. value cannot be lower than Low Limit.
Default value Must be in range between Low and High Limit (restricted by resolution).
Group Group in which setpoint will be shown.
Subgroup SubGroup in which setpoint will be shown.

InteliNeo 6000 1.5.0 Global Guide 234


Available groups and subgroups
The user setpoint can be put into some selected groups and subgroups.
Note: Setpoint is always added as last in selected subgroup.
List of available groups and it's subgroups:
Group Subgroup
Process control User setpoints
Basic Settings User setpoints
BESS Settings User setpoints
BESS Protections
BESS Protections
User setpoints
Protections User setpoints
Mains Protections
Mains Settings
User setpoints
Grid Codes User setpoints
Power Management User setpoints
User setpoints User setpoints
Analog Protections Analog Protections 1 – Analog Protections 8

5.4.43 Voltage Phase Sequence Detection


Controller detects phase sequence on both voltage terminals. This protection is important after controller
installation to avoid wrong voltage phase connection. The phase sequence is adjusted via setpoint Phase
Rotation (page 384).
6 back to General Functions

5.5 Application related functions


5.5.1 Application & System Variability 237
5.5.2 BESS Charging/Discharging Control 239
5.5.3 BESS Forced power 241
5.5.4 BESS Operation States 241
5.5.5 BESS Output Control 244
5.5.6 BESS Precharge Types 245
5.5.7 BESS Stabilization 246
5.5.8 BESS/PV PF/Q Control 247
5.5.9 Connecting To Load 248
5.5.10 Curtailment Counter 254
5.5.11 Multiple Island Operation 256
5.5.12 Output Control – Frequency/Load 256
5.5.13 Output Control - Voltage/PF 259
5.5.14 Parallel To Mains Operation - MINT Application 261
5.5.15 Parallel To Mains Operation - MPTM Application 263
5.5.16 Power Management 274

InteliNeo 6000 1.5.0 Global Guide 235


5.5.17 PV Curtailment 295
5.5.18 Regulation Loops 295

Functions directly related to the Microgrid application are described in this chapter.
6 back to Controller setup

InteliNeo 6000 1.5.0 Global Guide 236


5.5.1 Application & System Variability
The Microgrid site may consist of various elements such as BESS, renewables (PV/wind mills), Mains, and
Generators. Each site is different and the InteliNeo 6000 is a solution for most system variants.
The InteliNeo 6000 is not in position of the "master" controller, but it closely cooperates with all controllers in-site
so the InteliNeo 6000 can offer various statistics related to BESS, renewables, and Gen-sets. The HMI, visibility
of setpoints and values are changed based on settings defined by the setpoints in the Subgroup: System
Variability (page 372). The HMI also shows power flows through the system including information about power
from Mains and Gen-set controllers. The user can easily observe how the system operates with power, see the
pictures below.

Image 5.117 MINT HMI - PV, BESS, Gen-sets and Mains

Image 5.118 MINT HMI - actual power flow information

InteliNeo 6000 1.5.0 Global Guide 237


BESS
The main purpose of the InteliNeo 6000 is control the BESS, but it can still be used in case when the BESS is not
installed. In this case the setpoint BESS (page 372) should be set to Not Installed option and the following
groups will be hidden.
Note: This settings is related to the MINT and MPTM applications.

Setpoints Values
Group: BESS (page 707)
Group: BESS settings (page 434)
Group: Frequency/Load Control (page
Group: BESS Protections (page 570)
861)
Group: Frequency/Load Control (page 466)
Group: Voltage/PF Control (page 864)
Group: Voltage/PF Control (page 479)
The BESS statistics in the Group:
The most of the setpoints in the Group: BESS
Statistics (page 870)
Protections (page 446)
Group: Synchronization (page 485)

PV
The controller directly controls only the PVCB, the Modbus Client (Master) (page 176) is used to interact with
the PV inverter. In case there are not any renewables installed or the controller should not use any functions
related to the renewables the setpoint PV (page 372) should be set to Not Installed option and the following
groups will be hidden.
Note: This settings is related to the MINT and MPTM applications.

Setpoints Values
Group: PV Settings (page 460) Group: PV (page 718)
The PV statistics in the Group: Statistics (page 870)

Gensets
The controller is not used to control Gen-sets in any way, instead the Gen-set controllers must be used. In case
the Gen-sets are not part of the system the setpoint Gensets (page 373) should be set to Not Installed option.
The HMI will be changed and Gen-sets statistics in the Group: Statistics (page 870) will be hidden.
Note: This settings is related only to the MINT application.

Mains
In case the system is working as island microgrid the setpoint Mains (page 373) should be set to Not Installed
option and Mains will be removed from the HMI.
Note: This settings is related only to the MINT application.

InteliNeo 6000 1.5.0 Global Guide 238


5.5.2 BESS Charging/Discharging Control
This function allows managing of the charging process (storage of energy from the bus = Mains / Gen-sets /
renewables) and discharging process(providing stored energy to the load) of the BESS. There are two LBIs
which can be used to Enable/Disable charging and discharging process: LBI BATT CHARGE ENABLE (PAGE
989) and LBI BATT DISCHARGE ENABLE (PAGE 989). If both LBIs for charging and discharging are activated,
the battery cycling is applied. The battery will be cycling between charging/discharging targets given by
setpoints SOC Low Target (page 440) and SOC High Target (page 439)).
The source for the BESS active power output request can be selected by the Setpoint BESS P request
source (page 436). There are three types of sources:
Analog: The controller receives a BESS P REQUEST (PAGE 1116) from the LAI BESS P REQUEST (PAGE
1116). This LAI is used as a direct BESS Power Request.
Setpoint: The value of BESS P REQUEST (PAGE 1116) is given by setpoints BESS Charge Power (page
436) or BESS Discharge Power (page 437).
Balance: The BESS P REQUEST (PAGE 1116) is calculated using internal controller's algorithms. This
calculation maintain the balance of energy flow trough the system. For example, in OFF Grid application
the battery is only charged using the excess power in the system. Any extra Gen-set power is not required
to charge.
Note: All sources are influenced by LBIs mentioned above. When LBI BATT CHARGE ENABLE (PAGE 989) is
not active the Charge Request is unavailable. In case the LBI BATT DISCHARGE ENABLE (PAGE 989) is not
active, the discharge request is not available. If both LBIs are activated at the same time, the discharge
process has a higher priority.

BATT CHARGE ENABLE BATT DISCHARGE ENABLE BESS P Request


Charge/Discharge
(PAGE 989) (PAGE 989) Source
0 0 Blocked 0
BESS Discharge Power
0 1 Discharge
(page 437)
BESS Charge Power
1 0 Charge
(page 436)
BESS Discharge Power
1 1 Battery cycling
(page 437)

Variable Max Power Output


The active power of charging and discharging is primarily given by the setpoint Nominal power (page 375).
But in some cases the BESS cannot work on this power level. In these cases the variable maximal power
output is used and the maximal charging/discharging power is limited according the LAIs BESS MAX
CHARGE P (PAGE 1116) and BESS MAX DISCHARGE P (PAGE 1115).
These LAIs are used to limit BESS charging/discharging no matter what source/algorithm is used for the
BESS Required P Target (page 861) calculation. This function also affects calculations in the functions PV
Curtailment (page 295) and Dynamic Spinning Reserve (page 277).

InteliNeo 6000 1.5.0 Global Guide 239


Load Control Balance - Calculation of BESS P Request
The Power output of the BESS is controlled in way to consume excess or support deficit of power in the
system. The power balance of the system is given by equation:
Gen P Min (page 465) + PV Actual P (page 719) - Load P (page 828) = - BESS P (page 707)
Priority is to produce minimum power from Gen-sets (diesel), however in long term the Gen-sets have to
operate on some certain minimal power level. This level is given by the setpoint Gen P Min (page 465).
Excess of the power in the system is consumed by the BESS until it is running on -100% of its nominal
power, than the Gen-sets have to leave the Gen P Min (page 465) and ramp down. The function PV
Curtailment (page 295) can be used to limit output power of the PV inverter in order to keep the Gen-sets
running on their Gen P Min (page 465).
Deficit of power is firstly covered by the BESS until it is running on 100 % of its nominal power, then Gen-
sets start helping the BESS to cover the load.
If SOC is low or BESS cannot discharging for any reason, then the BESS output is limited to 0 and the
power demand has to be covered by Genset.

State of Charge
The charging and discharging process of the BESS also depends on the State Of Charge (SOC). When the
value BESS SOC (page 716) reach limit given by the setpoint SOC Low Target (page 440) the discharging
process is stopped and the LBO SOC DISCHARGE DISABLED (PAGE 1106) is activated. When the value BESS
SOC (page 716) reach limit given by the setpoint SOC High Target (page 439) the charging process is
stopped and the LBO SOC CHARGE DISABLED (PAGE 1106)is activated. The charging/discharing process can
be activated again after the value BESS SOC (page 716) leave the hysteresis which are defined by the
setpoints SOC Low Hysteresis (page 440) and SOC High Hysteresis (page 439). So, once the SOC
Actual reach the low target then the BESS cannot be discharged anymore until the BESS is cahrged at least
on the level of SOC Hysterezis.
Note: Charging and discharging is influenced all the time by the LBIs BATT CHARGE ENABLE (PAGE 989) and
BATT DISCHARGE ENABLE (PAGE 989).

Note: All relative setpoints/values are related to the LAI/Value BESSCAPACITY (PAGE 1115)BESS Nominal
Capacity (page 716).

In the picture below you can see the red and orange (Sd and Wrn) alarm areas. The aopropirate alarm is
activated when SOC Actual trips the SOC alarm level given by setpoints in the Subgroup: SOC Protection
(page 598). The green area is Safety Operation Area and SOC targets should be placed in it. The battery
should cycle between these targets in the green area.

Image 5.119 State of charge

InteliNeo 6000 1.5.0 Global Guide 240


Daily Battery Cycles Control
The number of battery cycles per day can be limited by the setpoint Max Battery Cycles Per Day (page
441). In one day the statistic value Batt. Charging Cycles (page 873) cannot be increased more times than
the setpoint Max Battery Cycles Per Day (page 441) specifies. If the daily number of battery cycles is
reached the LBO DAILY BATT CYCLES REACHED (PAGE 1068) and ALI Daily Battery Cycles Reached (page
1271) are activated and the battery cannot be discharged anymore. On the given day only battery charging is
allowed. One day is counted from midnight to midnight, so the LBO and alarm are deactivated at the earliest
midnight.
Note: Usually one charging cycle is defined as complete discharge of fully charged battery or a series of
partial drains equal to the battery’s capacity.

5.5.3 BESS Forced power


The BESS can require specific Power Limitations which occurs in certain situations. In order to use this limitation,
Forced power condition has to be fulfilled.

Forced power condition


Forced Power Condition of the BESS is applied to prevent overloading or reverse power of any unit in the system
connected to the bus. If the power of the system is too low or too high the controller which is not included in Load
Sharing (for example CU using local baseload) with the lowest priority, will be forced to increase or decrease
power according to the Load Sharing. The system always needs to keep at least one unit running on Load
Sharing line, so the system is capable of reacting to the changes in the load.
For InteliNeo6000 the BESS is running in "variable local baseload". It means that the controller controls charging
or discharging of the BESS independently on Load Sharing. The priority is to keep the BESS in this state, but if
the power of the system cannot be handled, the BESS is forced to join Load Sharing. The first case when the
BESS is forced to join Load Sharing can be when Gen-sets power goes under Gen P Min (page 465) and the
function PV Curtailment (page 295) is disabled or the PV power is already reduced to the minimum. The other
case can be when Gen-sets are overloaded and PV is already running on its maximum.

5.5.4 BESS Operation States


BESS state machine

Init Initialization of the controller. The application is not active yet.


BESS is not ready to start.
NotReady
Example: When shutdown alarm is active or unit is in OFF mode.
Ready BESS is ready to run.
Prestart Prestart sequence in process, PRESTART (PAGE 1098) output is closed.
Starting BESS is starting until LBI Ready To Load is activated or timer BESS Start TO elapsed.
BESS is started and prepared to be precharged in case of AC precharge or it is already
Running precharged in case of DC precharge. See the chapter BESS Precharge Types (page
245).
Soft load BESS power is ramping up
Loaded BESS is running at nominal frequency and BCB FEEDBACK (PAGE 991) is closed.

InteliNeo 6000 1.5.0 Global Guide 241


Soft unld BESS power is ramping down
Stop.
Stop
Example: Automatic or manual stop command was issued.
Shutdown Shut-down alarm activated.
EMERGENCY MAN (PAGE 996)BESS operation.
EmergMan
Example: Used for bypass the controller and BESS manual start.

Electric state machine

Init Initialization of the controller. The application is not active yet.


MCB is opened (LBO MCB CLOSE/OPEN (PAGE 1090) is not active and LBI MCB
FEEDBACK (PAGE 1012) is not active either) and BCB is opened (LBO BCB
BrksOff
CLOSE/OPEN (PAGE 1055) is not active and LBI BCB FEEDBACK (PAGE 991) is not
active either).
IslOper Island operation: MCB is opened and LBO BCB is closed.
Island operation: MCB is opened , any other GCB is not closed, and LBO BCB is
SingleIslOper
closed.
RevSync This state is active during synchronization via MCB.
Synchro BESS is synchronizing (MCB is closed, BCB is opened).
BESS is in passive synchronization mode, breaker close command will be issued
Synchro Perm
once synchronization windows is matched.
BESS is synchronizing, breaker close command will be issued once synchronization
Synchro Run
window is matched.
Mains Fails: this state is active when LBO MAINS/BUS HEALTHY (PAGE 1090) is
MainsFlt
deactivated.
ValidFlt State activated after Emergency start del.
Init Initialization of the controller. The application is not active yet.
Island operation: MCB is opened , any other GCB is not closed, and LBO BCB is
SingleIslOper
closed.

Init Initialization of the controller. The application is not active yet.


MCB is opened (LBO MCB CLOSE/OPEN (PAGE 1090) is not active and LBI MCB
FEEDBACK (PAGE 1012) is not active either) and BCB is opened (LBO BCB
BrksOff
CLOSE/OPEN (PAGE 1055) is not active and LBI BCB FEEDBACK (PAGE 991) is not
active either).
IslOper Island operation: MCB is opened, any other BCB is closed, and LBO BCB is closed.
Island operation: MCB is opened , any other BCB is not closed, and LBO BCB is
SingleIslOper
closed.
ShoreOperation: LBO MAINS/BUS HEALTHY (PAGE 1090) is active, MCB is closed and
ShoreOper
BCB is opened.
BESS is in parallel with shore (MAINS/BUS HEALTHY (PAGE 1090) is active and MCB+
ParalOper
BCB are closed)

InteliNeo 6000 1.5.0 Global Guide 242


RevSync This state is active during synchronization via MCB.
Synchro BESS is synchronizing (MCB is closed, BCB is opened).
Reserved Not used. Item is placed due compatibility reason.
Reserved Not used. Item is placed due compatibility reason.
Reserved Not used. Item is placed due compatibility reason.
MultIslOp Island operation: MCB is opened, any other BCB is closed, and LBO BCB is closed.
BESS is in parallel with mains (MAINS/BUS HEALTHY (PAGE 1090) is active and MCB +
MultParOp
BCB are closed)
EmergMan EMERGENCY MAN (PAGE 996)BESS operation.
StrUpSync Not used. Item is placed due compatibility reason.
DCCB
Precharging activated around PVCB
Precharging
DCCB OK Breaker aligned with request and its feedback.

InteliNeo 6000 1.5.0 Global Guide 243


5.5.5 BESS Output Control
In general there are two types of output control of the BESS inverter. It depends on what input can be send to
the BESS inverter as request. One option is that the inverter accept only P-Q request, another option is U-f
request or both. Because each option has its requirements and limits the LBI BESS OUTPUT CONTROL MODE
U-F/P-Q (PAGE 994) is used to choose what output control method will be used by InteliNeo6000 controller.

P-Q Output Control


In this case the input request for the BESS inverter output is given by active and reactive power. The active
and reactive power request is given by the controller's values BESS Required P (page 861) and BESS
Required Q (page 865) in case of absolute values, or BESS Required Relative P (page 862) and
BESS Required Relative Q (page 865) in case of relative values.
The BESS inverter using this output control method is able to work only in Grid Supporting mode because it
cannot control voltage and frequency level on it's output. In this case the BESS cannot be connected to the
grid without Mains/Gen-sets. It is not possible to close BCB if there is not healthy voltage on the bus.
Note: The AC precharge type should be used because the controller cannot use active synchronization
properly (it cannot control voltage and frequency levels). See the chapter BESS Precharge Types (page
245) for more information.

Note: If the BESS is connected to the Grid alone after Gen-set/Mains is disconnected, the BCB is opened
because of anti islanding protection (Hst BESS Anti Islanding (page 1280)).

U-f Output Control


In this case the input request for the BESS inverter output is given by frequency and voltage. The frequency
and voltage request is given by the controller's values Frequency Regulator Output (page 862) and
Voltage Regulator Output (page 866).
The BESS inverter using this output control method is able to work in Grid Forming mode because it can
control voltage and frequency level on it's output. In this case the BESS can be connected to the grid without
Mains/Gen-sets. The BCB can be closed to the dead bus if DC precharge type is used.

Note: The values described above are send to the BESS inverter via Modbus Client (Master) (page 176)
function for both cases.

U-f Output Control with droop


The controller of BESS (Battery Energy Storage System) generates the values for control of the BESS output.
Specific BESS as devices requires the different approach of control in u-f mode and it means it requires the
control inputs in different format. InteliNeo offers the most typical formats of values dedicated for BESS output
control. It provides control values for both active and reactive requirement.
For Active Power and Frequency control these values specificaly are: BESS Frequency Required (page
862), BESS Frequency Offset (page 862), BESS P Required (page 863)
All these values are calculated based on the Frequency regulator output and definition of the droop settings of
the BESS. It uses the Setpoint: BESS Frequency Droop Slope (page 468) for calculation. This Setpoint has
to be set acordingly to the actual BESS (PCS) frequency droop slope settings.
For Reactive Power and Voltage control these values specificaly are: BESS Voltage Required (page
866), BESS Voltage Offset (page 866), BESS Q Required % (page 867)

InteliNeo 6000 1.5.0 Global Guide 244


All these values are calculated based on the Voltage regulator output and definition of the droop settings of
the BESS. It uses the Setpoint: BESS Voltage Droop Slope (page 481) for calculation. This Setpoint has to
be set acordingly to the actual BESS (PCS) voltage droop slope settings.

5.5.6 BESS Precharge Types


This function allows adjustment of the BESS pre-charging type. There is the Setpoint BESS Precharge Type
(page 435) which enables the selection of AC or DC precharge of an inverter. This is a very influential factor
in determining the ability of an inverter to generate alternating voltage at its output.
InteliNeo supports two methods of BESS starting sequences. The selection of the appropriate method is
determined by how the battery inverter (PCS) DC circuit BCS connects to the battery before the inverter
connects to an energized AC bus. For the battery and PCS DC circuit to be connected via an internal DC
contactor, both must have the same DC voltage. Providing the additional potential required by the PCS is
called a 'precharge' procedure where the PCS DC circuit is charged either internally by its DC bus (batteries)
or from the AC side. This is known as 'DC precharge' or 'AC precharge', respectively.
Controller forces the user to configure all the necessary inputs, outputs and safety setpoints before the ES
can be fully utilized. If something is not configured correctly, Alarm Sd ES Configuration Incorrect.

Necessary configured inputs and outputs:

DC Precharge
DC precharge start sequence applies to PCS with the ability to black start itself from the DC bus of the
batteries.
InteliNeo uses two signals to coordinate DC precharge, the LBO PRECHARGE REQUEST (PAGE 1099) and
LBI PRECHARGE FINISHED (PAGE 1016). Both signals are mandatory.
Once the internal DC contactor between batteries and PCS are closed, the inverter can energize its AC
output.
LBI INVERTER START DISABLED (PAGE 1006) is to be sent once the precharge procedure has been
finished.
Controller then waits for confirmation LBI BESS READY TO LOAD (PAGE 995) (if this LBI is configured as
not all battery inverters have an idle mode), or the BESS is ready once the period set in Timer BESS
Ready To load elapses (only if LBI BESS READY TO LOAD (PAGE 995) is not configured).
BESS protections unlocks and BCB can be closed to allow BESS to energize the dead bus.

AC Precharge
AC precharge start sequence applies to PCS that requires energization from the AC side to close the internal
DC circuit to the batteries. The AC bus must be healthy with voltage and frequency within the acceptable
range of the PCS.
InteliNeo uses two signals to coordinate AC precharge, the LBO PRECHARGE REQUEST (PAGE 1099) and
LBI PRECHARGE FINISHED (PAGE 1016). Both signals are mandatory.
AC precharge starts by closing the BCB to the bus. The inverter must be able to moderate the inrush
current when connected to the AC bus via the BCB.
Once the DC voltage for the batteries and PCS are level and the internal DC circuit is closed, the
precharge of the inverter is complete.
InteliNeo provides LBO Inverter Run Request to the inverter to begin operation.

InteliNeo 6000 1.5.0 Global Guide 245


InteliNeo waits for confirmation LBI BESS READY TO LOAD (PAGE 995) (if this LBI is configured), or the
BESS is ready once the period set in Timer BESS Ready To load elapses (only if LBI BESS READY TO
LOAD (PAGE 995) is not configured).
BESS protections unlocks and inverter starts running unless postponed by the LBI INVERTER START
DISABLED (PAGE 1006). If LBI Inverter Start Disabled is configured, the inverter and controller stays ready
but idle until LBO INVERTER RUN REQUEST (PAGE 1084) is received.
Once inverter is running, InteliNeo has direct control of P and Q output of BESS. Since the bus was
energized by some other AC voltage source at the beginning, the BESS is operating in grid supporting
mode.
Note: There can be other limitations for the precharge type given by the BESS Output Control (page
244)method.

5.5.7 BESS Stabilization


IMPORTANT: This chapter is relevant only if BESS Precharge Type (page 435) is set to DC option.

When theBESS start is finished, the BESS goes into the stabilization phase. There are two timers (setpoints) in
this phase:
Minimal Stabilization Time (page 441) starts to count down just after the idle period has finished. BESS
voltage and frequency are not checked (respective protections are not evaluated) and the BCB cannot be
closed even if the BESS voltage and frequency are within limits.
Maximal Stabilization Time (page 442) starts to count down just after the idle period has finished. BESS
voltage and frequency are not checked (respective protections are not evaluated) but, opposite to the
previous timer, the BCB can be closed if BESS voltage and frequency are within limits.
In situations where the BCB is closed automatically (AUTO mode), the closing of BCB or starting of
synchronization will occur in the first moment when the BESS voltage and frequency will get into limits and the
Minimal Stabilization Time (page 441) has already elapsed.
In the event that the BESS voltage or frequency are not within limits within the Maximal Stabilization Time
(page 442) period, the appropriate protection(s) will be activated and the BESS will be cooled down and stopped.
Note: The limits for the BESS voltage and frequency are given by setpoints in the Group: BESS settings (page
434).

Note: The value of the Minimal Stabilization Time (page 441) setpoint has to be lower than the value of
Maximal Stabilization Time (page 442) setpoint.

InteliNeo 6000 1.5.0 Global Guide 246


5.5.8 BESS/PV PF/Q Control
PV PF/Q Control
In the parallel with mains operation or PV PF/Q regulation is realized using the setpoint PV Power Factor
Request (page 460). This setpoints defines the constant PF which is required from PV inverter. In the island
operation the PID PLC block should be used to regulate PF/Q of the PV so the Gen-sets has the constant PF.
In case the system has the BESS the value of the Required PF/Q which is defined by the setpoint PV Power
Factor Request (page 460) is sent to the PV inverter using the Modbus Client (Master) (page 176)
function.

BESS PF/Q Control


The PF/Q Controll of the BESS is regulated according to the setpoint BESS Q request source (page 438).
There are two types of sources:
Analog: The reactive power is regulated according to the the LAI BESS Q REQUEST (PAGE 1116). This
LAI is used as a direct BESS Reactive Power Request.
Balance: The PF of the BESS is regulated using internal calculation so the BESS covers reactive power
peaks so Gen-sets (system) has the constant PF which is defined by the setpoint Gensets PF Required
(page 438).
The PF/Q regulation is limited by the apparent power of the BESS. The Capability L (page 973) and
Capability C (page 974) curves are used to circle area regulation defined as:
2 2
√(BESS P Actual + BESS Q Required ) = S BESS < Smax

Regulations in the Grid Forming Mode


MINT with IM 1010 controller
#System PF Control PTM (page 358) = VAr Sharing
PF/Q Regulation Type (page 358) = Base PF/Q Control or Import/Export PF/Q Control
The PV and BESS (no matter what source is set by the setpoint) will cover part of the PF/Q Request and
the Gen-sets will cover the rest.
MINT without IM 1010 controller
#System PF Control PTM (page 358) = Base PF or Base Q
The PV and BESS (no matter what source is set by the setpoint) will cover part of the PF/Q Request
and the Gen-sets will cover the rest.
PF/Q Regulation Type (page 358) = Base PF/Q Control
The PV will cover part of the PF/Q Request and the Gen-sets will cover the rest.
The BESS will cover part of the PF/Q Request only if LAI is used as source.

InteliNeo 6000 1.5.0 Global Guide 247


5.5.9 Connecting To Load
BESS 248
PV 248
Connecting To Dead Bus 249
Synchronization 249

BESS
Before connecting of the BESS to the load the LBI GENERIC GENSET START/STOP (PAGE 1004) must be activated
in case of AUT mode or start button must be pressed in case of MAN mode.
The connection of the BESS to the bus/load differs according to the setpoint BESS Precharge Type (page 435).
In case the AC option is set, the BCB breaker can be closed immediately after the BESS is in the running phase.
No stabilization time is counted because the inverter with AC precharge is not able to generate AC voltage on its
output without being connected to the healthy bus. In this case the synchronization and connecting to the
deadbus options are not available.
In case the DC option is set , connecting of the BESS to the load is same as for the Gen-set. See the text below.
When the BESS Stabilization (page 246) phase is finished, the BESS can be connected to the load. The
command for connecting the BESS to the load is issued either automatically (AUTO mode) or manually by
pressing the BCB button. The following conditions must be valid:
The BESS is running and the Minimal Stabilization Time (page 441) timer has elapsed.
The BESS voltage and frequency are within limits.

Note: The frequency governor and AVR must be adjusted properly to achieve these limits as the controller does
not perform any regulation and the regulation outputs have constant values given by the Voltage Regulator
Bias (page 480) and Frequency Governor Bias (page 467) setpoints.

Connecting to load depends on the state of MCB FEEDBACK (PAGE 1012) and on the measured bus voltage. In
case the Load is without power (bus voltage is below 2 % of nominal voltage and MCB is opened) the
Connecting To Dead Bus (page 249) is applied, in other case the Synchronization (page 249) process is
needed.

PV
The connection of the PV to the bus/load is not related to the LBI GENERIC GENSET START/STOP (PAGE 1004) or
start button in any way. Instead the LBO PV/WT RUN REQUEST (PAGE 1100) is activated always when the CU is
in the AUT or MAN mode and the controller expect activation of the LBI PV Operable. It is expected that PV
inverter is always using AC precharge so the PVCB can be closed once the LBI is active an the bus is healthy. So
in this point behavior is the same as it is for the BESS with AC precharge. The PVCB cannot be closed to the
deadbus or synchronized because PV inverter is not able to generate AC voltage on its own.
Connecting Mains to Load
Connecting to load depends on application, for BCB application it depends on the state of BCB FEEDBACK (PAGE
991) and on the measured bus voltage. In case of MCB application depends only on measured bus voltage. In
case the Load is without power (bus voltage is below 2 % of nominal voltage or BCB is opened) the connecting to
dead bus is applied, in other case the synchronization process (reverse synchronization) is needed. See more
information about synchronization process in chapter Synchronization (page 249).
Connecting to load (closing BTB) depends on the measured Bus Left and Bus Right voltage. In case one of the
side of BTB is without power (Bus Left or Bus Right voltage is below 2 % of nominal voltage) the connecting to

InteliNeo 6000 1.5.0 Global Guide 248


dead bus is applied, in other case the synchronization process is needed. See more information about
synchronization process in chapter Synchronization (page 249).

Connecting To Dead Bus


MPTM
If the MCB is open, the bus bar is considered as dead and the BCB is closed without synchronization.

MINT
The measured bus voltage is taken in account, it must be below 2% of the nominal bus voltage together with the
open MCB (evaluated by LBI MCB Feedback (page 1012) or internally via CAN intercontroller communication if
the LBI is not configured), and also others BCB have to be opened, to close the BCB without synchronization.
Note: If the group of / multiple BESSs have to start simultaneously and connect to the empty bus bar, there is an
internal logic to prevent closing of more BCBs to the bus bar at the same moment without synchronization. One
of the BESSs will close the BCB, the others will wait and then they will synchronize to the first one.

IMPORTANT: The function described above works only if all controllers can see each other on
CAN intercontroller line. You can use Emergency Droop function to detect missing controller
on CAN.

Note: There also is a protection of “Bus power loss sensing”. The “Bus Measure Error” is detected in MINT
application when the voltage on the controller’s bus terminals is out of limits 20 seconds after:
BCB (own) was closed in MAN or AUT mode
MCB (feedback) was closed in AUT mode
Any other BCB in power management group (on CAN bus) was closed.
The alarm is activated after 20s. However, the BCB (own) closing is blocked immediately for safety reasons. This
protection can avoid e.g. potential direct closing of BCB while the controller’s bus conductors are unintentionally
unplugged from the terminals.

Synchronization
Synchronization Process 249
Synchronization Types 251

Synchronization Process
Behavior of synchronization process depends on, which breaker is used for synchronization and on which
Controller Mode (page 385) is controller switched to.
Note: When the controller starts to synchronize and the main measuring screen is displayed, it will be
automatically changed to the synchroscope screen for the entire duration of synchronization. The screen will
also show value Voltage Match 321 to inform you better about synchronization process. After synchronization
the synchroscope screen is automatically changed back to the main measuring screen. It is also possible to
change screens manually (arrows up and down) after displaying the synchroscope screen. In this case there is
no automatic return to the main measuring screen after synchronization is finished.

Voltage match 321


This value consists of 3 bits which are filled separately with logical 0 or logical 1 based on Mains/Bus Voltage and
BESS Voltage of respective phases during synchronization.
Note: Based on Connection type (page 378) this value may either relates to Ph-N or to Ph-Ph values.

InteliNeo 6000 1.5.0 Global Guide 249


Connection type (page 378) Relates to
3Ph4Wire
High Leg D Ph-Ph
3Ph3Wire
SplitPhase
Ph-N
MonoPhase
1st Bit, logical 1 when:

2nd Bit, logical 1 when:

3rd Bit, logical 1 when:

IMPORTANT: Bits are counted from right to left!

Synchronization via BCB in AUTO mode


BESS synchronization to the Mains (common bus bar) via BCB (available for MPTM and MINT):
If the Mains (bus) voltage or the Mains (bus) frequency gets out of the limits then the synchronization
continues until the Mains fail is confirmed. Then:
In MPTM - MCB is opened and BCB is closed.
In MINT - Stp Bus Meas Error (page 1290) alarm is issued.
If the BESS voltage or frequency gets out of the limits during the synchronization the synchronization
process is interrupted. The synchronization starts again when BESS parameters are restored. The
Synchronization Timeout (page 486) starts to be counted down again.
If the Synchronization Timeout (page 486) elapses alarm Stp Synchronization Fail (page 1294) is
issued.

Synchronization via BCB in MAN mode


BESS synchronization to the Mains (common bus bar) via BCB (available for MPTM and MINT:
Behavior is exactly the same as in AUTO mode - but the synchronization does not start again
automatically when parameters of the BESS gets out of limits and back. The breaker control button must
be pressed again.
When the BCB button is pressed during the synchronization, then the synchronization process is
interrupted.

InteliNeo 6000 1.5.0 Global Guide 250


Synchronization via MCB in AUTO mode
BESS synchronization to the Mains via MCB (available only for MPTM):
if the Mains voltage or the Mains frequency gets out of the limits during synchronization, then the
synchronization process is interrupted and can continue again when Mains parameters gets restored).
if the BESS voltage or frequency gets out of the limits during the synchronization, the synchronization
process continues until the BESSparameters fail is confirmed.
If the synchronization timeout gets elapsed the Wrn Reverse Synchronization Fail (page 1265)
protection gets active and BCB stays closed. Synchronization is stopped.

Synchronization via MCB in MAN mode


BESS synchronization to the Mains via MCB (available only for MPTM):
Behavior is exactly the same as in AUTO mode - but the synchronization does not start again
automatically when parameters of the Mains gets out of limits and back. The breaker control button must
be pressed again.
When the MCB button is pressed during the synchronization, then the synchronization process is
interrupted.
6 back to Synchronization

Synchronization Types
There are two types of synchronization. Type of synchronization is adjusted via setpoint Synchronization Type
(page 485).

Phase Match
The phase match synchronization consists of voltage matching and frequency/angle matching. The maximum
duration of synchronization is given by the setpoint Synchronization Timeout (page 486). If the
synchronization is not successful within this period of time, the Stp Synchronization Fail (page 1294) alarm will
be issued.

Voltage matching
The BESS voltage is regulated to match the Mains/Bus voltage with tolerance given by the setpoint Voltage
Window (page 486). The regulation is adjusted by the setpoints Voltage Gain (page 482) and Voltage Int
(page 482).

Frequency/angle matching
The BESS frequency is regulated to match the Mains/Bus frequency first. The frequency regulation loop is active
(setpoints Frequency Gain (page 469) and Frequency Int (page 470)). Once the frequency is matched, the
regulation loop is switched to match the angle (setpoint Angle Gain (page 470)). When the angle is matched
with tolerance +/- Phase Window (page 487) for a time given by the setpoint Dwell Time (page 487) and the
voltage is matched too, then the BCB or MCB is closed.
Note: The matching loop will continue to run even if the BCB or MCB close command has been already issued
until the controller receives BCB FEEDBACK (PAGE 991)/MCB FEEDBACK (PAGE 1012) or Sd BCB Fail To Close
(page 1291)/Wrn MCB Fail To Close (page 1255) alarm occurs. After the feedback has been received, the
control loops are switched to load and power factor loops respectively to load and power factor sharing.

InteliNeo 6000 1.5.0 Global Guide 251


Slip Synchronization
The slip synchronizing is based on frequency/angle matching. The maximum duration of synchronizing is given
by the setpoint Synchronization Timeout (page 486). If the synchronizing is not successful within this period of
time, the Stp Synchronization Fail (page 1294) alarm will be issued.
The BESS frequency is regulated to match the Mains/Bus frequency + Slip Frequency (page 488) value and
the window is set by setpoint Slip Frequency Window (page 488). When the BESS frequency reaches
(Mains/Bus Frequency + Slip frequency) value regulation loop is stopped (output is frozen at the actual value). If
the BESS frequency reMains inside the window for the time longer than setpoint Dwell Time (page 487) the
controller will allow BCB or MCB closing. The controller calculates periodically so called preclosing angle (based
on the actual value Slip Frequency (page 717) and CB closing delay given by the setpoints BCB Latency
(page 488) or MCB Latency (page 489)). When the preclosing angle is reached the controller issues CB closing
command. The breaker will close and CB feedback confirms that to the controller. When the breaker is closed the
controller goes to parallel and activates regulation loops again (parallel to Mains regulation loop).

Image 5.120 Slip synchronization

Whenever the BESS Frequency (page 713) leaves off the Slip Frequency Window (page 488) (either
because of BESS Frequency (page 713), Mains/Bus Frequency (page 839) or setpoint Slip Frequency
Window (page 488) changes) the controller will reactivate frequency regulation loop and try to reach the target
value again. The Synchronization Timeout (page 486) timer runs regardless of this while whole slip
synchronization process is repeated. If the BESS Frequency (page 713) reaches the target frequency again the
regulations are frozen and if the BESS Frequency (page 713) remains in the window for the time longer than
setpoint Dwell Time (page 487) the controller will continue in the standard sequence as seen in the previous
case. *If the Synchronization Timeout (page 486) elapses the controller will immediately stop synchronization
and issue alarm Stp Synchronization Fail (page 1294).

InteliNeo 6000 1.5.0 Global Guide 252


Image 5.121 Slip synchronization

The window is limited by the actual measured Mains/Bus Frequency (page 839) if one of the window limits is
below this value (e.g. for setting where setpoint Slip Frequency (page 717) is set to 0.1Hz and setpoint Slip
Frequency Window (page 488) is set to 0.5Hz).

Image 5.122 Slip synchronization

Slip synchronization has a dead band. When the dead band is reached the frequency regulation is disabled.
Once it is disabled it will be enabled again only when the frequency goes out of the slip frequency window. Dead
band is introduced to allow the controller to detect the match.

InteliNeo 6000 1.5.0 Global Guide 253


Image 5.123 Slip synchonization - deadband

Note: Due to the nature of this function it is possible that in limit cases the controller will regulate the BESS
frequency outside of protection limits. Example: Mains/Bus frequency is high but within its protection limits (e.g.
50.9 Hz, limit is 51 Hz). Slip Frequency (page 488) is set to 0.5Hz. This will cause regulation loop of the
controller can push the BESS frequency to 51.4 Hz and eventually the controller will issue overfrequency alarm.
It is recommended to set the setpoint Slip Frequency (page 488) as low as possible that still enables succesfull
synchronization. This minimizes the risk of this problem happening. Furthermore when slip synchronization is
used it is recommended to set Mains/Bus Frequency protection limits to more rigid values than the BESS
frequency protection limits. In this case the setpoint Slip Frequency (page 488) can be set to 0.1Hz and the
Mains/Bus Frequency overfrequency protection limit is set to 50.9Hz instead of 51Hz. This will ensure that
problematic state cannot be reached.

6 back to Synchronization

5.5.10 Curtailment Counter


The Curtailment Counter is a crucial component of the microgrid controller, tasked with quantifying and
reporting energy losses attributed to curtailment in a photovoltaic (PV) system. Curtailment, in this context,
refers to the controlled reduction of energy generation to prevent grid overload or under-utilization. This
function calculates and reports the energy loss resulting from curtailment within the PV system.
How it Works:
1. Estimating Potential Energy: Using data from the irradiation sensors and the PV array area values, the
controller calculates the area of each array. It then multiplies this area by the irradiation data from sensors
1 to 4 to determine the potential PV output of each array.
2. Measuring Actual Energy: The controller measures the actual energy produced by each PV array within
the microgrid. This measurement typically relies on data from PV inverters or other monitoring devices.

InteliNeo 6000 1.5.0 Global Guide 254


3. Curtailment Energy Calculation: The energy lost due to curtailment is determined by calculating the
difference between the potential energy output (calculated in step 1) and the actual energy output
(measured in step 2) for each PV array.

Inputs
These sensors provide data on the amount of sunlight received at different points within the microgrid.
IRRADIATION OF PV ARRAY 1 (PAGE 1122)
IRRADIATION OF PV ARRAY 2 (PAGE 1122)
IRRADIATION OF PV ARRAY 3 (PAGE 1123)
IRRADIATION OF PV ARRAY 4 (PAGE 1123)

PV Arrays and Their Areas


The area of each array is determined by the respective setpoint value, and this area is further multiplied by
the irradiation data from sensors 1 through 4 to calculate the potential PV output of each array.
PV Array Area 1 (page 461)
PV Array Area 2 (page 461)
PV Array Area 3 (page 461)
PV Array Area 4 (page 462)

Corrections
Output of Each particular PV Array in kW can be corrected using the offset which is defined setpoints:
PV Calib. Offset 1 (page 462)
PV Calib. Offset 2 (page 462)
PV Calib. Offset 3 (page 463)
PV Calib. Offset 4 (page 463)

Statistical Outputs
PV Total Curtailed kWh (page 871)
PV Curtailed Annual kWh (page 871)
PV Curtailed Monthly kWh (page 871)
PV Curtailed Weekly kWh (page 872)
PV Curtailed Daily kWh (page 872)

Curtailed Power
PV Max P (page 720)
PV Curtailed P (page 721)
PV Curtailed P Relative (page 721)

These statistical outputs provide valuable insights into the efficiency of the microgrid's PV system, enabling
operators and system administrators to make informed decisions to optimize energy utilization and
curtailment strategies within the microgrid.

InteliNeo 6000 1.5.0 Global Guide 255


Curtailment - Ramp Up / Down
The PV output request is directly influenced by the Value: Curtailment Output (page 772). This Value says
what is the maximal allowed PV output. Normally it is kept on the value 100% if there is no need to limit the PV
output. If the system needs to curtail the PV, then it does it using this value. The dynamic of the curtailment
output change is given by the settings of regulation loops of curtailment function. However the maximal rate of
change of Curtailment Output is limited by Setppoint: PV/WT Ramp Up (page 465) and Setpoint PV/WT
Ramp Down (page 466). These Setpoints says what is the duration of change from 0 to 100 % of the ramp.

5.5.11 Multiple Island Operation


This chapter describes the situation where the BESS and multiple Gen-sets are running parallel to each other
but not with mains. This situation will occur either when:
The common bus bar is dead due to opened MCB or there is no mains at all and the BESS and group of
Gen-sets has been connected to the bus, or
The group was running parallel to mains and the MCB has been opened.

IMPORTANT: The controller in MINT application does not control the MCB! Only the MCB position is
evaluated from the binary input MCB FEEDBACK (PAGE 1012) and the position is the basic source of
information for switching between island and parallel to mains operation. If MCB Feedback is not
configured the state is automatically shared via intercontroller CAN.

Note: The following description is common for Gen-set and BESS only in case the BESS Precharge Types
(page 245) is set to DC. Otherwise the BESS cannot synchronize and it must be firstly precharged by closing
the BCB and connecting dead output of the inverter to the healthy bus.

If the bus bar is empty, the first Gen-set/BESS will close its GCB/BCB without synchronization. Following Gen-
sets will synchronize to the already energized bus bar. In the event that multiple Gen-sets start simultaneously
and the bus bar is empty, the system will prevent closing of multiple GCBs to the bus bar without synchronization.
Instead of this, one of the Gen-sets/BESS will close the GCB/BCB and energize the bus bar and the others will
wait and then synchronize to the bus bar.
When a stop command is received, e.g. from the power management or binary input GENERIC GENSET
START/STOP (PAGE 1004) is deactivated or the STOP button is pressed, the GCB/BCB will be opened, the BESS
will be stopped and Gen-sets will go to cool down phase.
Behavior of controllers is adjusted via Power Management (page 274) settings. Please see this chapter for
more information.

5.5.12 Output Control – Frequency/Load


The frequency control output is used to control the frequency or the power of the BESS. The frequency
regulation, load regulation and load sharing are realized through the frequency control. The Frequency Request
is internal value of the regulator which is transformed to range -10 .. 10 V based on setpoints Frequency
Governor Low Limit (page 467) and Frequency Governor High Limit (page 467). This value of frequency
request is then transformed to request which comes out of the controller. The analog or binary pulse outputs can
be send to the BESS inverter via MOBDUS client (master) function.
Analog output
ECU speed control
Binary pulse control

InteliNeo 6000 1.5.0 Global Guide 256


Frequency control outputs
Analog Output
The frequency regulator of the BESS is controlled by the analog signal from controller. Please see the chapter
Analog Outputs (page 70)
The direction of frequency regulation required by frequency regulator of the BESS is given by the setpoint
Frequency Regulator Character (page 466). A full range change of the frequency governor output (from
Frequency Governor Low Limit (page 467) to Frequency Governor High Limit (page 467)) should cause 5-
10% change of the BESS frequency (Frequency Governor Low Limit (page 467) ~ 95% Nominal Frequency
(page 384), Frequency Governor Bias (page 467) ~ 100%Nominal Frequency (page 384), Frequency
Governor High Limit (page 467) ~ 105% Nominal Frequency (page 384)).
IMPORTANT: Frequency governor has to be adjusted for optimum performance before
Frequency/Load control adjusting. Check BESS phase sequence before the first BCB connection.

Binary pulse control


The internal Frequency Request is transformed to Up/Down pulse control. These pulses get out of the controller
via binary outputs FREQUENCY UP (PAGE 1081) and FREQUENCY DOWN (PAGE 1081). Length of pulses
FREQUENCY UP (PAGE 1081) and FREQUENCY DOWN (PAGE 1081) depends on the difference of the actual
frequency and requested frequency (actual power and requested power) and on the parameter Tau Frequency
Governor Actuator (page 468). Tau Frequency Governor Actuator (page 468) defines the pulse duration
which is needed for the regulator of BESS inverter to regulatefrom minimal position to the maximal position. The
Maximum length of pulses is limited to 5 s, the minimal length of pulses is limited to 150 ms and minimal length
between the pulses is 200 ms.

Frequency/Load Control Adjustment


IMPORTANT: Prior to Frequency/Load control adjustment, the Voltage/PF control has to be adjusted.

Frequency & Synchronization Adjustment


Frequency and Angle control loop is active during synchronization process.
1. Set Frequency Gain (page 469) to 0 and start the BESS in MAN Mode.
2. Set the BESS frequency by Frequency Governor Bias (page 467), Frequency Governor Low Limit
(page 467) and Frequency Governor High Limit (page 467) to achieve frequency according to setpoint
Nominal Frequency (page 384).
3. Increase Frequency Gain (page 469) to unstable frequency control and decrease value by 30 % to
insure stable performance.
4. Adjust Frequency Int (page 470) to stable (fast and smooth) frequency control.
5. Set Angle Gain (page 470) to 0 and start the synchronization by pressing BCB ON/OFF button. To stop
synchronization press again BCB ON/OFF .
6. Synchroscope movement on the controller measure screen should slow down and stop (in any position,
because Angle Gain (page 470) control is off).
7. Set Angle Gain (page 470). Synchroscope on the controller measure screen should move slowly and
stop in “up“ position. Set Angle Gain (page 470) to unstable value (synchroscope swings) and decrease
value by 30 % to insure stable performance.
8. Now your speed regulation loop setup is done.

InteliNeo 6000 1.5.0 Global Guide 257


Load Control Adjustment

MINT application
Load control loop is active in parallel to Mains mode only (MCB FEEDBACK (PAGE 1012) is closed). Switch off
other parts of the system (BESSs) while adjusting.
1. Set #System Baseload (page 355) setpoint to 30 % of one BESS.
2. Set Load Gain (page 471) to the same value as Angle Gain (page 470) and Load Int (page 471) to 0.
3. Start theBESS in MAN Mode, press BCB ON/OFF button to synchronize and close BESS to Mains.
4. When BCB is closed, BESS load slowly increases to the #System Baseload (page 355) value. Check
that BESS power is positive (CT polarity).
5. Increase Load Int (page 471) to unstable load control and decrease value by 30 % to insure stable
performance. When Load Int (page 471) factor is set to zero BESS load can differ from required
#System Baseload (page 355).
6. To adjust and optimize Load Int (page 471) change #System Baseload (page 355) several times
between 30 and 70 % of Nominal power (page 375).
7. When BESS is running under full load check if
a. Speed regulator output voltage value is not limited (it does not reach Frequency Governor Low
Limit (page 467) or Frequency Governor High Limit (page 467)).
b. Speed governor actuator is not mechanically limited or operates in a small section of the throttle
range.
8. Now your Load regulation loop setup is done.

MPTM application
Load control loop is active in parallel to Mains mode only (MCB FEEDBACK (PAGE 1012) is closed).
1. Set Load Control PTM Mode (page 352) = BASELOAD, BESS P request source (page 436) =
Setpoint, BESS Charge Power (page 436)/BESS Discharge Power (page 437) setpoint to 30 %
Nominal power (page 375) of BESS and activate LBI BATT CHARGE ENABLE (PAGE 989)/BATT
DISCHARGE ENABLE (PAGE 989).
2. Set Load Gain (page 471) to the same value as Angle Gain (page 470). Set Load Int (page 471) to
zero.
3. Start the BESS in MAN Mode, press BCB ON/OFF button to synchronize and close BESS to Mains.
4. When BCB is closed, BESS load slowly increases to BESS Charge Power (page 436)/BESS Discharge
Power (page 437) value.
5. Increase Load Gain (page 471) to unstable load control and decrease value by 30 % to insure stable
performance. When Load Int (page 471) factor is set to zero BESS load can differ from required
BESS Charge Power (page 436)/BESS Discharge Power (page 437).
6. To adjust and optimize Load Int (page 471) change BESS Charge Power (page 436)/BESS Discharge
Power (page 437) several times between 30 and 70 % of Nominal power (page 375). Usually setting
Load Int (page 471) to 100% gives optimal performance.
7. When BESS is running under full load check if speed governor output voltage value is not limited (it does
not reach Frequency Governor Low Limit (page 467) or Frequency Governor High Limit (page
467)).
8. Now your Load regulation loop setup is done.

InteliNeo 6000 1.5.0 Global Guide 258


5.5.13 Output Control - Voltage/PF
The voltage control output is used to control the voltage or the power factor of the Gen-set. The voltage
regulation, PF regulation and VAr sharing are realized through the voltage control. The Voltage Request (page
866) is internal value of the regulator which is transformed to range -10 .. 10 V based on setpoints Voltage
Regulator Low Limit (page 480) and Voltage Regulator High Limit (page 480) and stored in value Voltage
Regulator Output (page 866). This value is transformed to a request which comes out of the controller. The
analog or binary pulse outputs can be send to the BESS inverter via MOBDUS client (master) function.

Voltage control outputs


Analog output
The voltage regulator of the BESS is controlled by the analog signal from controller. Please see the chapter
Analog Outputs (page 70)
The direction of voltage regulation required by voltage regulator of the BESS is given by the setpoint Voltage
Regulator Character (page 479). A full range change of the voltage regulator (from Voltage Regulator Low
Limit (page 480) to Voltage Regulator High Limit (page 480)) should cause 5-10% change of the voltage
(Voltage Regulator Low Limit (page 480) ~ 95% of BESS Nominal Voltage Ph-N (page 380), Voltage
Regulator Bias (page 480) ~ 100% BESS Nominal Voltage Ph-N (page 380), Voltage Regulator High Limit
(page 480) ~ 105% of BESS Nominal Voltage Ph-N (page 380)).

Binary pulse control


The internal Voltage Request (page 866) is transformed to Up/Down pulse control. These pulses get out of the
controller via binary outputs VOLTAGE UP (PAGE 1110) and VOLTAGE DOWN (PAGE 1109). Length of pulses
VOLTAGE UP (PAGE 1110) and VOLTAGE DOWN (PAGE 1109) depends on the difference of actual voltage and
requested voltage (actual reactive power and requested reacted power, actual PF and requested PF) and on the
parameter Tau Voltage Regulator Actuator (page 481). Tau Voltage Regulator Actuator (page 481)
defines the pulse duration which is needed for the regulator of BESS inverter to regulatefrom minimal position to
the maximal position. The Maximum length of pulses is limited to 5 s, the minimal length of pulses is limited to
150 ms and minimal length between the pulses is 200 ms.

Voltage/PF control adjustment


Voltage Adjustment
1. Set Voltage Gain (page 482), Voltage Int (page 482) to 0 and Voltage Regulator Bias (page 480) to
the half of expected applicable range.
2. Start the BESS in MAN Mode without load.
3. Change Voltage Regulator Bias (page 480) to 0% and 100% to check BESS voltage control range
(typically ± 10 % of BESS Nominal Voltage Ph-N (page 380)).
4. Set the BESS voltage by Voltage Regulator Bias (page 480), Voltage Regulator High Limit (page
480) and Voltage Regulator Low Limit (page 480) to achieve voltage according to setpoint BESS
Nominal Voltage Ph-N (page 380).
5. Increase Voltage Gain (page 482) to unstable voltage control and decrease value by 30 % to insure
stable performance.
6. Adjust Voltage Int (page 482) to stable (fast and smooth) voltage control and change Voltage Regulator
Bias (page 480) back to value which should correspond to the BESS Nominal Voltage Ph-N (page

InteliNeo 6000 1.5.0 Global Guide 259


380).
7. Now your voltage regulation loop setup is done.

PF Adjustment

MINT application
Power factor control loop is active in parallel to mains mode only (MCB FEEDBACK (PAGE 1012) is closed). Switch
off other parts of the system (Gen-sets) while adjusting.
1. Set PF Gain (page 483) to the same value as parameters Voltage Gain (page 482) and Voltage Int
(page 482) to 0.
2. Set #System Baseload (page 355) = 30 % of Nominal power (page 375) and #System Power Factor
(page 360) = 1.0.
3. Start and synchronize the BESS in MAN Mode by pressing BCB ON/OFF.
4. When running in parallel to mains loaded on 30%, increase slowly PF Gain (page 483) to unstable point
and then decrease the value by 30 % to insure stable performance.
5. Increase Load Int (page 471) to unstable load control and decrease value by 30 % to insure stable
performance. When Load Int (page 471) factor is set to zero BESS load can differ from required
#System Power Factor (page 360).
6. Now your PF/Q regulation loop setup is done.

MPTM application
Power factor control loop is active in parallel to mains mode only (MCB FEEDBACK (PAGE 1012) is closed).
1. Set the same values to PF Gain (page 483) and PF Int (page 483) as in the chapter Voltage
Adjustment (page 259) for parameters Voltage Gain (page 482) and Voltage Int (page 482).
2. Set BESS Charge Power (page 436)/BESS Discharge Power (page 437) = 30 % of Nominal power
(page 375) and Base Power Factor (page 359) = 1.0.
3. Start and synchronize the BESS in MAN Mode by pressing BCB ON/OFF.
4. When running in parallel to mains loaded on 30%, increase slowly PF Gain (page 483) to unstable point
and then decrease the value by 30 % to insure stable performance.
5. Adjust PF Int (page 483) (usually setting to 100% gives optimal performance).
6. Now your PF/Q regulation loop setup is done.
Note: To judge optimal adjusting of the power factor induce BESS power jumps by Voltage Regulator Bias
(page 480) change or by BESS Charge Power (page 436)/BESS Discharge Power (page 437) change.

InteliNeo 6000 1.5.0 Global Guide 260


5.5.14 Parallel To Mains Operation - MINT Application
This chapter describes the situation where the BESS and multiple Gen-sets are running parallel to Mains. This
situation will occur when the common bus bar is connected to the Mains (MCB FEEDBACK (PAGE 1012) is
present) and the BESS and group of Gen-sets has been connected to the bus. If the bus bar is healthy, all Gen-
sets/BESS will synchronize to the already energized bus bar.
IMPORTANT: The controller in MINT application does not control the MCB! Only the MCB position is
evaluated from the binary input MCB FEEDBACK (PAGE 1012) and the position is the basic source of
information for switching between island and parallel to Mains operation. If MCB Feedback is not
configured the state is automatically shared via intercontroller CAN.

The InteliNeo6000 Load and PF/Q control is different from Gen-set controllers. It is expected that renewables
(PV) and BESS should run with maximal priority so the Load Sharing is applied only in some critical cases. Se the
chapters BESS Charging/Discharging Control (page 239), BESS/PV PF/Q Control (page 247), and PV
Curtailment (page 295) for more information.

Ramping the power


Power up
Ramp up starts when value BESS Required P Target (page 861) is increased above value BESS Required P
(page 861). The first phase of the Parallel To Mains operation is the ramp of the BESS up to the desired power
level derived from the BESS Charging/Discharging Control (page 239). The speed of the ramp is given by the
setpoint Load Ramp (page 477). The setpoint adjusts the ramp time for a change from Ramp Start Level
(page 478) to 100 % of Nominal power (page 375)/Installed Power (page 375) of the BESS.
Note: Setpoints Ramp Start Level (page 478) and Load Ramp (page 477) are related to Installed Power
(page 375) only if Installed Power (page 375) != OFF, otherwise they relate to Nominal power (page 375).

Power down
Ramp down starts when value BESS Required P Target (page 861) drops, value BESS Required P (page
861) is ramped from BESS P (page 707) down to the new value of BESS Required P Target (page 861) based
on Load Ramp (page 477). Setpoint Load Ramp (page 477) determines how long it shall take to ramp down
from Nominal power (page 375)/Installed Power (page 375) of the BESS to 0 kW.

Soft unload
When BCB is about to be opened (BCB open command or stop command have been received), controller uses
Soft Unload Ramp (page 479) for ramp BESS P (page 707) to Generator Unload BCBOpen Level (page
476). Setpoint Soft Unload Ramp (page 479) determines how long it shall take to ramp down from Nominal
power (page 375)/Installed Power (page 375) of the gen-set to 0 kW.
6 back to Parallel To Mains Operation - MINT Application

Load control
If MCB FEEDBACK (PAGE 1012) is active (parallel to Mains operation) the load of Gen-set group is controlled to
reach the power defined by setpoint #System Baseload (page 355) or by Load Sharing line. If the setpoint
#System Load Control PTM (page 354) = Load Shar the system load is regulated by the InteliMains supervisor
controller, otherwise the load is controlled locally in each controller by load control regulation loop. The regulation
loop is adjusted via setpoints Load Gain (page 471) and Load Int (page 471).
Current Load control mode is always showed in System Load Control (page 863) value (SPTM only).

InteliNeo 6000 1.5.0 Global Guide 261


Baseload
Baseload ensures that the BESS keeps certain BESS P (page 707), which is given by BESS Required P (page
861). BESS Required P (page 861) is ramped to BESS Required P Target (page 861) using Load Ramp
(page 477).
If #System Load Control PTM (page 354)is set to Baseload the BESS Required P Target (page 861) is given
by:
If Load Request Source (page 353) = Setpoint, BESS Required P Target (page 861) = #System
Baseload (page 355).
If Load Request Source (page 353) = Analog External Value, BESS Required P Target (page 861) is
equal to value from LAI LOAD CONTROL: ANEXT BASELOAD (PAGE 1121) .
Note: In case LAI LOAD CONTROL: ANEXT BASELOAD (PAGE 1121) is not configured or has Invalid flag (page
691), the setpoint source is used instead of AIN.

Load Shar
If #System Load Control PTM (page 354) is Load Shar the system Load is controlled by InteliMains controller.
Note: Mains controller plays active role in case of load control only in case that the sepoint #System Load
Control PTM (page 354) is set to Load sharing . If this setpoint is set to Baseload the load control is controlled
from gen-set controllers and their load control loops.

InteliNeo 6000 offers 2 modes for controlling of load. Load control ensures that the system keeps the certain
Actual Active Power In PM (page 858) value in parallel to Mains operation MCB STATUS (PAGE 1092) and
BCB STATUS (PAGE 1060) are closed, i.e. Breaker state (page 886) = ParalOper and at least one gen-set is
excited.
6 back to Parallel To Mains Operation - MINT Application

PF/Q control
If MCB FEEDBACK (PAGE 1012) is active (Parallel To Mains Operation) the PF/Q of Gen-set is controlled to reach
the PF/Q defined by setpoint #System Power Factor (page 360)/#System Base Q (page 361).Var Sharing
line is used automatically if Load Sharing is active or while island operation. If the setpoint #System PF Control
PTM (page 358) = Var Shar the system PF/Q is regulated by the InteliMains supervisor controller, otherwise the
load is controlled locally in each controller by var control regulation loop. The regulation loop is adjusted via
setpoints PF Gain (page 483) and PF Int (page 483).
Current PF/Q control mode is always showed in System PF/Q Control (page 864) value (SPTM only).

Base PF/Q Control


Base PF/Q Control ensures that the Gen-set keeps certain BESS Q (page 708) to provide required BESS
Power Factor (page 710).

Base PF
#System PF Control PTM (page 358) has to be adjusted to Base PF. The BESS Required PF (page 865) with
BESS Required PF Character (page 865) are based on:
PF/Q Request Source (page 357) = Setpoint, requested PF is given by the Setpoint #System Power
Factor (page 360) or
PF/Q Request Source (page 357) = Analog External Value, requested PF is given by value from LAI PF
CONTROL: ANEXT BASE PF (PAGE 1124).

InteliNeo 6000 1.5.0 Global Guide 262


Note: Alarm Wrn PF Control Fail (page 1258) is activated if LAI PF CONTROL: ANEXT BASE PF (PAGE 1124)
is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Base Q
#System PF Control PTM (page 358) has to be adjusted to Base Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by #System
Base Q (page 361) or
PF/Q Request Source (page 357) = Analog External Value, BESS Required Q (page 865) is given by
value from LAI Q Control: ANEXT Base Q (page 1147).
Note: Alarm Wrn Q Control Fail (page 1261) is activated if LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is
not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Var Shar
If #System PF Control PTM (page 358) is Var Shar the Gen-set PF/Q is controlled by InteliMains controller.
6 back to Parallel To Mains Operation - MINT Application

5.5.15 Parallel To Mains Operation - MPTM Application

After the BESS has been synchronized to the mains, the parallel to mains operation follows.
The InteliNeo6000 Load and PF/Q control is different from Gen-set controllers. It is expected that renewables
(PV) and BESS should run with maximal priority so the Load Sharing is applied only in some critical cases. Se the
chapters BESS Charging/Discharging Control (page 239), BESS/PV PF/Q Control (page 247), and PV
Curtailment (page 295) for more information.

Ramping the power


IMPORTANT: Power ramping may be affected by Grid Codes (page 299) if any of them is enabled.

Power up
The first phase of the parallel to mains operation is the ramp of the BESS up to the desired power level. Ramp up
starts when value BESS Required P Target (page 861) rises. If the BCB has been just closed, value BESS
Required P (page 861) is ramped from Ramp Start Level (page 478) up to the new value of BESS Required P
Target (page 861) based on Load Ramp (page 477), otherwise is value BESS Required P (page 861) ramped
from BESS P (page 707). Setpoint Load Ramp (page 477) determines how long it shall take to ramp up from 0
kW to Installed Power (page 375) of the BESS.
Note: Ramp Start Level (page 478) and Load Ramp (page 477) are related to Installed Power (page 375)
only if Installed Power (page 375) != OFF, otherwise they relate to Nominal power (page 375).

InteliNeo 6000 1.5.0 Global Guide 263


Examples Description
Nominal Power = 100 kW
Installed Power = OFF
BCB gets closed, Required P is ramped from 10 kW
Ramp Start Level = 10 %
to 50 kW in 4 s.
Load Ramp = 10 s
Baseload = 50 kW
Nominal Power = 100 kW
Installed Power = OFF BCB is closed, BESS P = 50 kW, Baseload is
Ramp Start Level = 10 % changed to 70 kW. Required P is ramped from 50
Load Ramp = 10 s kW to 70 kW in 2 s.
Baseload = 70 kW
Nominal Power = 200 kW
Installed Power = 100 kW
BCB gets closed, Required P is ramped from 10 kW
Ramp Start Level = 10 %
to 50 kW in 4 s.
Load Ramp = 10 s
Baseload = 50 kW

Power down
Ramp down starts when value BESS Required P Target (page 861) drops, value BESS Required P (page
861) is ramped from BESS P (page 707) down to the new value of BESS Required P Target (page 861) based
on Load Ramp (page 477). Setpoint Load Ramp (page 477) determines how long it shall take to ramp down
from Installed Power (page 375) of theBESS to 0 kW.
Note: Setpoint Load Ramp (page 477) is related to Installed Power (page 375) only if Installed Power (page
375) != OFF, otherwise it relates to Nominal power (page 375).

Soft unload
When BCB is about to be opened (BCB open command or stop command have been received), controller uses
for ramping BESS P (page 707) to Generator Unload BCBOpen Level (page 476). Setpoint determines how
long it shall take to ramp down from Installed Power (page 375) of the BESS to 0 kW.
Note: Setpoint Load Ramp (page 477) is related to Installed Power (page 375) only if Installed Power (page
375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to Parallel To Mains Operation - MPTM Application

Load control
InteliNeo 6000 offers 2 modes for controlling of load. Load control ensures that the BESS keeps the certain
BESS P (page 707) value in parallel to Mains operation MCB STATUS (PAGE 1092) and BCB STATUS (PAGE
1060) are closed, i.e. Breaker state (page 886) = ParalOper.
Current Load control mode is always showed in the value System Load Control (page 863).

Baseload
Baseload ensures that the BESS keeps certain BESS P (page 707), which is given by BESS Required P (page
861). BESS Required P (page 861) is ramped to BESS Required P Target (page 861) using Load Ramp
(page 477) or actual active ramp based on Grid Codes (page 299).

InteliNeo 6000 1.5.0 Global Guide 264


Load Control PTM Mode (page 352) has to be adjusted to Baseload and BESS Required P Target (page
861) is given by:
If BESS P request source (page 436) = Setpoint, BESS Required P Target (page 861) =
BESS Charge Power (page 436)/BESS Discharge Power (page 437) while LBI BATT CHARGE
ENABLE (PAGE 989)/BATT DISCHARGE ENABLE (PAGE 989) is active.
Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).

If Load Request Source (page 353) = Analog External Value, BESS Required P Target (page 861) is
equal to value from LAI LOAD CONTROL: ANEXT BASELOAD (PAGE 1121).
Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).

Note: In case LAI LOAD CONTROL: ANEXT BASELOAD (PAGE 1121) is not configured or has Invalid flag (page
691), function is evaluated as if Load Request Source (page 353) = Setpoint.

Import/Export
Import/Export ensures that the Gen-set regulates its BESS P (page 707) to keep certain Mains Import P (page
842). BESS P (page 707) is given by BESS Required P (page 861) which is ramped to BESS Required P
Target (page 861) using Load Ramp (page 477) or actual active ramp based on Grid Codes (page 299).
Load Control PTM Mode (page 352) has to be adjusted to Import/Export and BESS Required P Target (page
861) is given by:
If Load Request Source (page 353) = Setpoint, Mains Import P (page 842) = Import Load (page
355).
Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).

If Load Request Source (page 353) = Analog External Value, Mains Import P (page 842) is equal to
value from LAI LOAD CONTROL: ANEXT IMP/EXP LOAD (PAGE 1122).
Note: Alarm Wrn Load IMP/EXP Fail (page 1253) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).

Note: BESS Required P Target (page 861), (Mains Import P (page 842)) can be lower/higher in case of
applied Grid Codes (page 299), BESS Forced power (page 241).

Note: In case LAI LOAD CONTROL: ANEXT IMP/EXP LOAD (PAGE 1122) is not configured or has Invalid flag
(page 691), function is evaluated as if Load Request Source (page 353) = Setpoint.

6 back to Parallel To Mains Operation - MPTM Application

PF/Q Control
PF Control 266
PF(Pm) 267
Q Control 267
Q(Um) 268

InteliNeo 6000 1.5.0 Global Guide 265


Q(P) 269
Qref/Ulim 270
InteliNeo 6000 offers 6 modes for controlling of PF/Q. PF/Q control ensures that the BESS keeps a certain BESS
Power Factor (page 710) or BESS Q (page 708) (based on selected mode) in parallel to Mains operation MCB
STATUS (PAGE 1092) and BCB STATUS (PAGE 1060) are active, i.e. Breaker state (page 886) = ParalOper.
In case that the BESS Q (page 708) is out of tolerance given by Q Deadband (page 564), Q Ramp (page 564)
is used.
Current PF/Q control mode is always showed in System PF/Q Control (page 864).

PF Control
PF Control ensures that the Gen-set keeps certain BESS Q (page 708) to provide required BESS Power Factor
(page 710). To enable this control, adjust PF/Q Control PTM Mode (page 356) to PF Control.

Base PF
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF Control BASE and
PF/Q Request Source (page 357) = Setpoint, requested PF is given by the Setpoint #System
Power Factor (page 360) or
PF/Q Request Source (page 357) = Analog External Value, requested PF is given by value from LAI
PF CONTROL: ANEXT BASE PF (PAGE 1124).
Note: Alarm Wrn PF Control Fail (page 1258) is activated if LAI PF CONTROL: ANEXT BASE PF (PAGE 1124)
is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Import/Export PF
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF Control IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, requested Mains PF (page 845) is given by Import
Power Factor (page 359) or
PF/Q Request Source (page 357) = Analog External Value, Mains PF (page 845) is given by value
from LAI PF CONTROL: ANEXT IMP/EXP PF (PAGE 1125).
Note: Alarm Wrn PF Control Fail (page 1258) is activated if LAI PF CONTROL: ANEXT IMP/EXP PF (PAGE
1125) is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page
357) = Setpoint.

Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).

6 back to PF/Q Control

InteliNeo 6000 1.5.0 Global Guide 266


PF(Pm)
BESS Q (page 708) is automatically adjusted to correspond with predefined PF upon change of BESS P (page
707). The predefined PF is adjusted by application curve PF(P) (PAGE 970). To enable this control, adjust PF/Q
Control PTM Mode (page 356) to PF(Pm).

Base PF(Pm)
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF (Pm) BASE and
PF/Q Request Source (page 357) = Setpoint, requested PF is given by PF(P) (PAGE 970) curve in x-
axe range 0 to 100 %. Actual value of the curve is stored in PF(P) Curve (page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn PF(Pm) Fail (page 1259) is
immediately activated because this control mode does not support external analog value. Power is
controlled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn PF(Pm) Fail (page 1259) is activated if PF(P) (PAGE 970) curve is not configured or invalid.
Power is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.

Import/Export PF(Pm)
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = PF (Pm) IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, requested Mains PF (page 845) is given by PF(P)
(PAGE 970) curve in x-axe range -100 to 100 %. Actual value of the curve is stored in PF(P) Curve
(page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn PF(Pm) Fail (page 1259) is
immediatelly activated because this control mode does not support external analog value. Power is
controlled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn PF(Pm) Fail (page 1259) is activated if PF(P) (PAGE 970) curve is not configured or invalid.
Power is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.

Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).

6 back to PF/Q Control

Q Control
BESS Power Factor (page 710) is adjusted to reach BESS Required Q (page 865). To enable this control,
adjust PF/Q Control PTM Mode (page 356) to Q Control.

InteliNeo 6000 1.5.0 Global Guide 267


Base Q
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q Control BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by Base Q
(page 360) or
PF/Q Request Source (page 357) = Analog External Value, BESS Required Q (page 865) is given
by value from LAI Q Control: ANEXT Base Q (page 1147).
Note: Alarm Wrn Q Control Fail (page 1261) is activated if LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is
not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Import/Export Q
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q Control IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by Import Q
(page 361) or
PF/Q Request Source (page 357) = Analog External Value, Mains Import Q (page 843) is given by
value from LAI Q CONTROL: ANEXT IMP/EXP Q (PAGE 1147).
Note: Alarm Wrn Q Control Fail (page 1261) is activated if LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is
not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).

6 back to PF/Q Control

Q(Um)
BESS Q (page 708) is automatically adjusted to correspond with predefined BESS Required Q (page 865)
upon change of relative Mains voltage. The predefined BESS Required Q (page 865) is adjusted by application
curve Q(UM) (PAGE 967) To enable this control, adjust PF/Q Control PTM Mode (page 356) to Q(Um).

Base Q(Um)
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q(Um) BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by Q(UM)
(PAGE 967) curve. The curve can be offset horizontally by Q(Um) 0 Reference (page 565) and in case
of Mains Voltage changes too fast, there is Q(Um) Deadband (page 565). Actual value of the curve is

InteliNeo 6000 1.5.0 Global Guide 268


stored in Q(Um) Curve (page 830) Or
PF/Q Request Source (page 357) = Analog External Value, BESS Required Q (page 865) is still
given by Q(UM) (PAGE 967) curve, but the horizontal offset is given by value of LAI Q(UM): 0 REF
ANEXT BASE Q (PAGE 1148)System PF/Q Control (page 864) Q(Um) Deadband (page 565) can
also be applied. Actual value of the curve is stored in Q(Um) Curve (page 830).
Note: Alarm Wrn Q(Um) Fail (page 1263) is activated if LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148) is not
configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Import/Export Q(Um)
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required PF
(page 865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864) = Q(Um) IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by Q(UM) (PAGE
967) curve. The curve can be offset horizontally by Q(Um) 0 Reference (page 565) and in case of too
fast Mains Voltage changes, there is Q(Um) Deadband (page 565). Actual value of the curve is stored
in Q(Um) Curve (page 830). Or
PF/Q Request Source (page 357) = Analog External Value, Mains Import Q (page 843) is given by
Q(UM) (PAGE 967) curve, but the horizontal offset is given by value of LAI Q(UM): 0 REF ANEXT
IMP/EXP Q (PAGE 1149)System PF/Q Control (page 864) Q(Um) Deadband (page 565) can also be
applied. Actual value of the curve is stored in Q(Um) Curve (page 830).
Note: Alarm Wrn Q(Um) Fail (page 1263) is activated if LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148) is not
configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page 357) =
Setpoint.

Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).

6 back to PF/Q Control

Q(P)
BESS Q (page 708) is automatically adjusted to correspond with predefined BESS Required Q (page 865)
based on BESS P (page 707). The predefined BESS Required Q (page 865) is adjusted by application curve Q
(P) (PAGE 969) To enable this control, adjust PF/Q Control PTM Mode (page 356) to Q(P).

Base Q(P)
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Q (page 708) is based
on:
System PF/Q Control (page 864) = Q(P) BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by Q(P) (PAGE
969) curve in x-axe range 0 to 100 %. To prevent oscilation use Q(P) Deadband (page 567) Actual

InteliNeo 6000 1.5.0 Global Guide 269


value of the curve is stored in Q(P) Curve (page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn Q(P) Fail (page 1262) is
immediately activated because this control mode does not support external analog value. Power is
controled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn Q(P) Fail (page 1262) is activated if Q(P) (PAGE 969) curve is not configured or invalid. Power
is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.

Import/Export Q(P)
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required Q
(page 865)is based on:
System PF/Q Control (page 864) = Q(P) IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by Q(P) (PAGE
969) curve in x-axe range -100 to 100 %. To prevent oscilation use Q(P) Deadband (page 567) Actual
value of the curve is stored in Q(P) Curve (page 831). Or
PF/Q Request Source (page 357) = Analog External Value, alarm Wrn Q(P) Fail (page 1262) is
immediately activated because this control mode does not support external analog value. Power is
controled as if PF/Q Request Source (page 357) = Setpoint.
Note: Alarm Wrn Q(P) Fail (page 1262) is activated if Q(P) (PAGE 969) curve is not configured or invalid. Power
is controlled as if PF/Q Control PTM Mode (page 356) = PF Control.

Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).

6 back to PF/Q Control

Qref/Ulim
BESS Q (page 708) is automatically adjusted to correspond with predefined BESS Required Q (page 865)
upon change of relative Mains voltage. The predefined BESS Required Q (page 865) is adjusted by application
curve QREF/ULIM (PAGE 968). To enable this control, adjust PF/Q Control PTM Mode (page 356) to Qref/Ulim.

Base Qref/Ulim
PF/Q Regulation Type (page 358) has to be adjusted to Base PF/Q Control. The BESS Required PF (page
865) with BESS Required PF Character (page 865) are based on:
System PF/Q Control (page 864)= Qref/Ulim BASE and
PF/Q Request Source (page 357) = Setpoint, BESS Required Q (page 865) is given by QREF/ULIM
(PAGE 968) curve. The curve can be offset vertically by Qref/Pnom Shift (page 566) and in case of too
fast Mains Voltage changes, there is Qref/Ulim Deadband (page 566) Actual value of the curve is
stored in Qref/Ulim Curve (page 830). Or
PF/Q Request Source (page 357) = Analog External Value, BESS Required Q (page 865) is still
given by QREF/ULIM (PAGE 968) curve, but the horizontal offset is given by value of LAI QREF/ULIM:

InteliNeo 6000 1.5.0 Global Guide 270


ANEXT QREF/PNOM B Q (PAGE 1150)System PF/Q Control (page 864) Qref/Ulim Deadband (page
566) can also be applied. Actual value of the curve is stored in Qref/Ulim Curve (page 830).
Note: Alarm Wrn Qref/Ulim Fail (page 1263) is activated if LAI QREF/ULIM: ANEXT QREF/PNOM B Q (PAGE
1150) is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page
357) = Setpoint.

Import/Export Qref/Ulim
PF/Q Regulation Type (page 358) has to be adjusted to Import/Export PF/Q Control. The BESS Required Q
(page 865) is based on:
System PF/Q Control (page 864) = Qref/Ulim IMP/EXP and
PF/Q Request Source (page 357) = Setpoint, Mains Import Q (page 843) is given by QREF/ULIM
(PAGE 968) curve. The curve can be offset vertically by Qref/Pnom Shift (page 566) and in case of too
fast Mains Voltage changes, there is Qref/Ulim Deadband (page 566) Actual value of the curve is
stored in Qref/Ulim Curve (page 830). Or
PF/Q Request Source (page 357) = Analog External Value, Mains Import Q (page 843) is given by
QREF/ULIM (PAGE 968) curve, but the offset is given by value of LAI QREF/ULIM: ANEXT QREF/PNOM
I/E Q (PAGE 1151)System PF/Q Control (page 864) Qref/Ulim Deadband (page 566) can also be
applied. Actual value of the curve is stored in Qref/Ulim Curve (page 830).
Note: Alarm Wrn Qref/Ulim Fail (page 1263) is activated if LAI QREF/ULIM: ANEXT QREF/PNOM I/E Q (PAGE
1151) is not configured or has Invalid flag (page 691). Power is controlled as if PF/Q Request Source (page
357) = Setpoint.

Note: Alarm Wrn PF/Q IMP/EXP Fail (page 1258) is activated if:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and LAI MAINS MEASUREMENT P (PAGE 1124) is either
not configured or has Invalid flag (page 691).
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and LAI MAINS MEASUREMENT Q (PAGE 1124) is
either not configured or has Invalid flag (page 691).

6 back to PF/Q Control


6 back to Parallel To Mains Operation - MPTM Application

Transfers of load
Type of transfer of load between mains and BESS and vice versa is adjusted via setpoints Transfer BESS To
Mains (page 475) and Transfer Mains To BESS (page 474).

InteliNeo 6000 1.5.0 Global Guide 271


Types of transfers

Transfer of the load from BESS to mains and vice versa without parallel work and
Open synchronization (one breaker opens and second is closed - checking feedbacks). The
setpoint Open Transfer Min Break (page 473) sets the minimal duration of break.
Transfer of the load from BESS to mains and vice versa with synchronization and
parallel work. The maximal time of parallel work is given by setpoint Close Transfer
Close Only
Max Duration (page 473).
In case of synchronization fail, MCB stays close and BESS is stopped.
Transfer of the load from BESS to mains and vice versa with synchronization and
parallel work. The time of parallel work is given by setpoint Close Transfer Max
Close Primarily
Duration (page 473).
In case of synchronization fail, open transfer is done.
Transfer of the load from BESS to mains and vice versa with parallel work and soft
loading/unloading of the BESS. This function is proceeded like the closed transfer, but
there is time limitation of loading/unloading of the BESS adjusted via setpoint Load
Ramp (page 477). The transfer is succeed only when the BESS is fully
Soft Transfer
loaded/unloaded (level of load when mains is considered as unloaded - BESS is loaded
is adjusted via setpoint Mains Unload MCB Open Window (page 476)), level of load
when BESS is considered as unloaded is adjusted via setpoint Generator Unload
BCBOpen Level (page 476)).

Transfer of load in MAN mode


Behavior of transfer of load in MAN mode is adjusted via setpoint CB Control In MAN Mode (page 362). For
details see the setpoint description.

Transfer of load in AUTO mode


Behavior of transfer of load in AUTO mode is affected by binary inputs FORCE ISLAND (PAGE 997), FORCE
PARALLEL (PAGE 997) and GENERIC GENSET START/STOP (PAGE 1004).
When more binary inputs are activated at the same time, their priority is shown in the list below:
FORCE ISLAND (PAGE 997) (highest priority).
GENERIC GENSET START/STOP (PAGE 1004).
FORCE PARALLEL (PAGE 997) (lowest priority).

Note: AMF function has the highest priority (if it is enabled).

InteliNeo 6000 1.5.0 Global Guide 272


Logical binary input AUTO mode
When activated:
starts BESS

FORCE ISLAND (PAGE the transfer of load from mains to BESS is done
997) When deactivated:
the transfer of load from BESS to mains is done
stopping of the BESS
When activated:
starts BESS
GENERIC GENSET if mains parameters ok - synchronize, run in parallel
START/STOP (PAGE
if mains parameters not ok - run in island
1004)
When deactivated:
unloading (if BESS was in parallel) and stopping of the BESS
When activated:
check mains parameters - if not ok no action, if ok the procedure follows
starts the BESS, synchronize, parallel operation
FORCE PARALLEL
in case of mains fail - BESS is stopped (if AMF function is disabled,
(PAGE 997)
otherwise it goes to island operation)
When deactivated:
unloading and stopping of the BESS

Type of transfer of load between mains and BESS and vice versa is adjusted via setpoints Transfer BESS To
Mains (page 475) and Transfer Mains To BESS (page 474).
6 back to Parallel To Mains Operation - MPTM Application

InteliNeo 6000 1.5.0 Global Guide 273


5.5.16 Power Management
Role of InteliNeo6000 in Power management 274
Basic power management 275
Principle of power management 275
Load reserve 276
Dynamic Spinning Reserve 277
Starting sequence 278
Stopping sequence 279
Absolute power management 280
Relative power management 282
Priorities 285
Priority auto swap 286
Minimal running power 293

IMPORTANT: Power management is relevant only for MINT application.

IMPORTANT: The Mains and BESS will take part of the power management (will be active) only if the
controller is in AUTO mode!

The Power management function decides how many BESSs should run and selects particular BESSs to run. The
power management is applicable in cases multiple BESSs run in parallel to Mains or in the island operation. The
function is based on the load evaluation in order to provide enough of available running power. Since it allows the
system to start and stop BESSs based on the load demand, it can vastly improve the system fuel efficiency. In
other words, an additional BESS starts when the load of the system raises above certain level. The additional
BESS stops, when the load of the system drops down below a certain level. The process of determining BESS
start and stop is done in each controller; there is no "master slave" system. Therefore, the system is very robust
and resistant to failures of any unit in the system. Each of the controllers can be switched off without influencing
the whole system. Except the situation the respective BESS is not available for the power management.
The power management evaluates so called Load reserve (page 276). The load reserve is calculated as
difference between actual load and nominal power of running BESSs. The reserve is calculated as absolute
value (in kW / kVA) or relatively to the nominal power of BESS(s) (in %). The setpoint #Power Management
Mode (page 491) is used to select the absolute or relative mode.
The Load Reserve can be influenced by the Dynamic Spinning Reserve (page 277) which is used to provide
the system with extra power (running BESSs) in case of anticipated output drop of a renewable source of energy.
The function Priority auto swap (page 286) focuses on efficient run of BESS in regards to running hours and
BESS size (power).
IMPORTANT: The function of the controller is designed to handle the maximum sum of nominal
power at 32000 kW (or 3200,0 with decimal number).

Example: There are 20 BESSs each with 1000 kW of nominal power. The sum of the nominal power is
20000 kW. Therefore the decimal power format in 0.1 kW cannot be used because the sum exceeds
32000. Therefore power format in kW needs to be chosen.

Role of InteliNeo6000 in Power management


The Power management are the principles (rules) which the system decides whether it is necessary to start or
stop other resources to cover the current consumption and the required load reserve. Power management is a

InteliNeo 6000 1.5.0 Global Guide 274


distributed logic and each controller makes decisions autonomously based on commonly shared information.
InteliNeo6000 in the MINT application is part of the ComAp ecosystem and behaves according to the general
rules of power management. It provides reserve in the form of unused power capacity from the BESS according
to the valid conditions of the Power Management function (AUT mode, Power management setpoint Enabled)
and also according to the conditions specific to the BESS battery storage. Specifically, it depends on whether the
battery is in a state where the discharge request can be accepted. This is based on the conditions of the BESS
Charging/Discharging Control (page 239), or according to the status of the LBI BATT DISCHARGE ENABLE
(PAGE 989). One of the important parametrers evaluated in power management is a priority of the source (Gen-
set, BESS).
To ensure the automatic change between the zero diesel mode based on the actual renewables output, load
conditions, SOC of the battery and required reserve, it is recommended to keep the Priority setpoint in the
InteliNeo6000 set to "1". Then if gen-sets have higher priority number ("2", "3", ...) it is possible to smoothly
change the mode of operation between gen-sets Running/Stopped. The output of the renewable sources served
by InteliNeo6000 and integrated in the system can undirectly effect the power management due to the load
reserve increase/decrease request. This principle is based on the Dynamic Spinning Reserve (page 277).
6 back to Power Management

Basic power management


The setpoint Power Management (page 489) enables and disables the BESS to be active within the power
management and makes automatic load dependent starts and stops. If the power management is disabled, the
start and stop of the BESS do not depend on the load of the group. If the BESS remains in AUTO mode, the
running condition depends only on the Logical binary inputs GENERIC GENSET START/STOP (PAGE 1004).
The Logical binary input GENERIC GENSET START/STOP (PAGE 1004) requests the system to start or stop. If the
input is not active, the system stops with delay #System Stop Delay (page 494) after the input has been
deactivated and will not start again if in AUTO mode. If the input is activated again, the delay #System Start
Delay (page 494) starts to count down. Once the delay elapsed, the system is activated and can be started by
the power management. In other words, the power management is activated only if the Logical binary inputs
GENERIC GENSET START/STOP (PAGE 1004) is activated, the option of setpoint Power Management (page 489)
= Enabled and the AUTO mode is selected.
Note: The Mains performs load and VAR sharing whenever it is connected to the bus bar i.e. it is independent on
whether the controller is in AUTO or MAN mode or whether the power management is active or not.

Function of power management can be temporarily blocked after GENERIC GENSET START/STOP (PAGE 1004)
activation a count down of #System Start Delay (page 494). The delay is given by setpoint Power
Management Delay (page 490). In this delay all BESSs where power management is enabled are running. After
this period elapses, only the BESSs needed according to the Power Management calculation stay running and
the rest is stopped.
6 back to Power Management

Principle of power management


Internal conditions based on remaining load reserves and priorities are evaluated once a delay is elapsed. If the
load reserve is insufficient the Mains is started after delay given by the setpoint #Next Engine Start Delay (page
510) is elapsed. Once the Mains runs the controller evaluates stopping conditions based on load reserves and
priorities. If the reserve is sufficient enough to stop a particular Mains, it is stopped after delay given by the
setpoint #Next Engine Stop Delay (page 511) is elapsed. All the time the system stop condition – i.e. the
Logical binary inputs GENERIC GENSET START/STOP (PAGE 1004) deactivated – is evaluated as well. Once the

InteliNeo 6000 1.5.0 Global Guide 275


delay given by the setpoint #System Stop Delay (page 494) has elapsed all BESSs in AUTO mode are
stopped. Following figure depicts the system activation and deactivation logic.

Setpoint #Overload Next Start Delay (page 514) is used in case that #Overload Next Start Protection (page
513) is enabled and BESSs are running at #Overload Next Start Level (page 513) or more of their nominal
power.
6 back to Power Management

Load reserve
The power management is based on the load reserve concept. The load reserve is defined as a difference of the
running nominal power of the group within power management and the total load of the system. In the
InteliNeo6000 controller the running nominal power is given by the actual power of the renewables (if they are
used) and by the nominal power of the BESS. There are two ways how to determine the load reserve. The
absolute power management allows the system to keep the load reserve higher or equal to value in kW given by
a relevant setpoint. The relative power management assures that load reserve is kept higher or equal to relative
portion in % of the nominal power of the group given by a relevant setpoint. Depending of the situation, load
reserves are calculated differently in two cases:

InteliNeo 6000 1.5.0 Global Guide 276


Island operation

Reserve Actual Reserve Start condition Stop condition


ARstrt = ∑PgNom - ∑PgAct ARstrt < ARstp >
Absolute kW
ARstp = ∑Pg*Nom - ∑PgAct #LoadResStrt #LoadResStop
RRstrt = [(∑PgNom - ∑PgAct) / ∑PgNom].100% RRstrt < RRstp >
Relative %
RRstp = [(∑Pg*Nom - ∑PgAct) / ∑Pg*Nom].100% #%LdResStrt #%LdResStop

Parallel to Mains operation

Reserve Actual Reserve Start condition Stop condition


ARstrt = ∑PgNom - BaseLoad ARstrt < ARstp >
Absolute kW
ARstp = ∑Pg*Nom - BaseLoad #LoadResStrt #LoadResStop
RRstrt = [(∑PgNom - BaseLoad) / ∑PgNom].100% RRstrt < RRstp >
Relative %
RRstp = [(∑Pg*Nom - BaseLoad) / ∑Pg*Nom].100% #%LdResStrt #%LdResStop

List of abbreviations:
ARstrt .. Actual Absolute reserve in kW or kVA - for BESS start calculation.
ARstp .. Actual Absolute reserves in kW or kVA - for BESS stop calculation.
RRstrt .. Actual Relative reserve in % - for BESS start calculation.
RRstp .. Actual Relative reserves in % - for BESS stop calculation.
ΣPgNom .. Sum of Nominal power of all Mains on the bus.
ΣPg*Nom .. Sum of Nominal power of all Mains on the bus apart of the one, which is going to be stopped.
ΣPgAct .. Sum of Actual power of all Mains on the bus = system load.
BaseLd .. Baseload is given by the setpoint #System Baseload (page 355)

Note: System starting sequences may be very different due to their complexity (i.e. Mains which do not take part
in power management, various nominal powers etc.). Each system should be considered individually.

6 back to Power Management

Dynamic Spinning Reserve


The values Dynamic Spinning Reserve (page 857) and Dynamic Spinning Reserve Offset (page 857) are
used to affect power management operation in case of anticipated output drop of a renewable source of energy.
It enables to shift the load reserve start level and load reserve stop level for power management. The value
Dynamic Spinning Reserve (page 857) is added to required load reserve given by setpoints #Starting Load
Reserve 1 (page 497) and #Stopping Load Reserve 1 (page 498) (according to actual load reserve set 1, 2, 3
or 4). The value Dynamic Spinning Reserve Offset (page 857) is added only to required stopping load reserve
given by setpoints #Stopping Load Reserve 1 (page 498) (according to actual load reserve set 1, 2, 3 or 4) to
create some dynamic offset between starting and stopping load reserve.
The InteliNeo6000 controller can provide the values Dynamic Spinning Reserve (page 857) and Dynamic
Spinning Reserve Offset (page 857) on the CAN line based on option selected in the setpoint Dynamic
Spinning Reserve Source.
In case the function is Disabled the InteliNeo6000 is not calculating and providing Dynamic Spinning
Reserve (page 857) and Dynamic Spinning Reserve Offset (page 857) at all.

InteliNeo 6000 1.5.0 Global Guide 277


In case option External Analog Value is used the InteliNeo6000 receives these values from the LAIs
DYNAMIC SPINNING RESERVE (PAGE 1120) and DYNAMIC SPINNING RESERVE OFFSET (PAGE 1120) and its
provide them via CAN line to the Gen-set controllers.
In case option Internal Calculation is selected the DYNAMIC SPINNING RESERVE OFFSET (PAGE 1120) is
received from LAI and DYNAMIC SPINNING RESERVE (PAGE 1120) is calculated according to the fallowing
formula:
DSR [kW] = Solar Coverage Ratio (page 496) * PV Actual P (page 719) + Nominal power (page
375) - BESS MAX DISCHARGE P (PAGE 1115)
If the BESS is in the state when it cannot be discharged (LBI BESS Discharging Enable = false) the
only first part of the formula is used for the DSR calculation.
If the setpoint Dynamic Spinning Reserve (page 857) is enabled the InteliNeo6000 controller also participate
on DSR in the same way as Gen-set controllers. But the main idea of renewables is to run with the maximal
priority. So, in this case the Microgrid site will not react on Load Reserve + DSR starting because it should
already run. In InteliNeo6000 controller this setpoint should be used only to have the same calculation of Load
Reserve and DSR as rest of controllers in group.
6 back to Power Management

Starting sequence
As written above, the power management is based on the load evaluation in order to provide enough of available
running power. An additional Mains starts when the load of the system raises above certain level to keep the load
reserve big enough. Following figure depicts the situation when an additional Mains is requested to join the
already running Mains(s) to the bus.

Image 5.124 Start sequence of power management

InteliNeo 6000 1.5.0 Global Guide 278


As shown above, the load of the system has increased above the level defined by the start condition – i.e. the
load reserve is not sufficient as required by the appropriate setpoint. Further explanation is provided in chapters
Absolute power management (page 280) and Relative power management (page 282).
The level is illustrated by the green dashed line. If the load reserve keeps insufficient for longer time than defined
by the setpoint #Next Engine Start Delay (page 510), the next BESS is actually started. The standard starting
sequence follows. Once the synchronization procedure is done, the BCB breaker is closed and the BESS power
is ramping up. Once loaded, the system load reserve is raised and becomes sufficient again. Please note the
sum of nominal power of all BESSs on the bus is increased by the nominal power of the additional BESS.
6 back to Power Management

Stopping sequence
As it is written above, the power management is based on the load evaluation in order to provide enough of
available running power. An additional BESS stops when the load of the system drops below certain level to
avoid inefficient run of the BESS. Following figure depicts the situation when a BESS is requested to stop due to
the power management.

Image 5.125 Stopping sequence of power management

As shown above, the system load has decreased below the level defined by the stop condition – i.e. the load
reserve is over a limit given by the appropriate setpoint. Further explanation is provided in chapters Absolute
power management (page 280) and Relative power management (page 282).
The level is illustrated by the red dashed line. If the load reserve keeps over this limit for longer time than defined
by setpoint #Next Engine Stop Delay (page 511), the next BESS is actually requested to stop. Once the BESS
is unloaded, the BCB breaker is opened. Please note the sum of nominal power of all BESSs on the bus is
decreased by the nominal power of the stopped BESS. The cooling sequence follows before the BESS is actually
stopped. The BESS is ready to be started if the system load increases again.

InteliNeo 6000 1.5.0 Global Guide 279


6 back to Power Management

Absolute power management


The power management based on absolute load reserves can be successfully used in cases the load portions
are similar to the BESS capacity or even bigger. The goal of the absolute reserve mode is to provide the same
load reserve all the time independently on how many BESSs are currently running. The mode perfectly fits for
industrial plants with large loads.
The absolute power management guarantees adjustable load reserve in kW. This mode is active when #Power
Management Mode (page 491) is set to ABS [kW] mode.

Image 5.126 Power management based on absolute load reserve

Example: An example of absolute power management is shown on the figure below. There are three
BESSs with following choice of setpoints:

InteliNeo 6000 1.5.0 Global Guide 280


#Starting
#Power #Priority #Stopping
Nominal Power Load
BESS management Priority Auto Load
power management Reserve
mode Swap Reserve X
X
BESS
200 kW Enabled ABS (kW) 1 Disabled 100 kW 125 kW
#1
BESS
500 kW Enabled ABS (kW) 2 Disabled 100 kW 125 kW
#2
BESS
1 000 kW Enabled ABS (kW) 3 Disabled 100 kW 125 kW
#3

Image 5.127 Absolute power management example

As it is shown on both figures above, the additional BESS is added once the actual load reserve is below the level
given by the appropriate setpoint of load reserve. The additional BESS is removed once the actual load reserve
is above the level set by appropriate setpoint of load reserve.

InteliNeo 6000 1.5.0 Global Guide 281


The green dashed line depicts the value of load at which the additional BESS is requested to start. This value of
the load value is linked with the setpoint #Starting Load Reserve 1 (page 497) (or other selected reserve set) in
following way:
Sum of nominal power for start - #Starting Load Reserve 1 (page 497) (or other selected reserve set) = value of
load when additional BESS requested to start (e.g.: 700 kW – 100 kW = 600 kW).
The red dashed line depicts the value of load at which the additional BESS is requested to stop. This value of the
load value is linked with the setpoint #Stopping Load Reserve 1 (page 498) (or other selected reserve set) in
following way:
Sum of nominal power for stop - #Stopping Load Reserve 1 (page 498) (or other selected reserve set) = value
of load when additional BESS requested to stop (e.g.: 700 kW – 125 kW = 575 kW).
There are 2 sets of setpoints for starting and stopping BESSs in absolute power management.
#Starting Load Reserve 1 (page 497) and #Stopping Load Reserve 1 (page 498)
#Starting Load Reserve 2 (page 500) and #Stopping Load Reserve 2 (page 501) considered if binary
input LOAD RES 2 ACTIVE (PAGE 1008) is activated
Note: All controllers cooperating together in Power management must have the same load reserve set selected.

Relative power management


The power management based on relative load reserves perfectly fits to those applications with such load
portions connected to the group at once are much lower than the BESS nominal power. This mode helps to
achieve the maximal lifetime of the BESSs, as they can be operated within optimal load range. The maximal size
of the load connected at once depends on number of actually working BESSs. The more BESSs are connected
to the bus bar the bigger load portion can be connected at once.
The relative power management guarantees that the engines are not continuously loaded more than to a certain
level. This mode is active when #Power Management Mode (page 491) is set to REL [%] mode.

InteliNeo 6000 1.5.0 Global Guide 282


Image 5.128 Power management based on relative load reserve

Example: An example of relative power management is shown on the figure below. There are three
BESSs with following choice of setpoints:

#Starting
#Power #Priority #Stopping
Nominal Power Rel Load
BESS management Priority Auto Rel Load
power management Reserve
mode Swap Reserve X
X
BESS
200 kW Enabled REL (%) 1 Disabled 35 % 40 %
#1
BESS
500 kW Enabled REL (%) 2 Disabled 35 % 40 %
#2
BESS
1 000 kW Enabled REL (%) 3 Disabled 35 % 40 %
#3

InteliNeo 6000 1.5.0 Global Guide 283


Image 5.129 Relative power management example

As it is shown on both figures above, the additional BESS is added once the actual load reserve is below the level
given by the appropriate setpoint of load reserve. The additional BESS is removed once the actual load reserve
is above the level set by appropriate setpoint of load reserve.
The green dashed line depicts the value of load at which the additional BESS is requested to start. This value of
the load value is linked with the setpoint #Starting Rel Load Reserve 1 (page 499) (or other selected reserve
set) in following way:
(100 % - #Starting Rel Load Reserve 1 (page 499) (or other selected reserve set)) * Sum of Nominal power =
Value of load when additional BESS requested to start in kW (in % of nominal power), e.g.: (100 % – 35 %) * 700
kW = 455 kW (65 % of nominal power).
The red dashed line depicts the value of load at which the additional BESS is requested to stop. This value of the
load value is linked with the setpoint #Stopping Rel Load Reserve 1 (page 499) (or other selected reserve set)
in following way:

InteliNeo 6000 1.5.0 Global Guide 284


(100 % - #Stopping Rel Load Reserve 1 (page 499) (or other selected reserve set)) * Sum of Nominal power =
Value of load when additional BESS requested to stop in kW (in % of nominal power), e.g.: (100 % – 40 %) * 700
kW = 420 kW (60 % of nominal power).
There are 2 sets of setpoint for starting and stopping BESSs in relative power management.
#Starting Rel Load Reserve 1 (page 499) and #Stopping Rel Load Reserve 1 (page 499)
#Starting Rel Load Reserve 2 (page 502) and #Stopping Rel Load Reserve 2 (page 502) considered
if binary input LOAD RES 2 ACTIVE (PAGE 1008) is activated
Note: All controllers cooperating together in Power management must have the same load reserve set selected.

6 back to Power Management

Priorities
The priority of the BESS within the group is given by the setpoint Priority (page 492). Lower number represents
"higher" priority, i.e. a BESS with lower number starts before another one with higher number. In other words, the
setpoint Priority (page 492) means order in which BESSs are started and connected to the bus. An example is
shown on the figure below. There are four BESSs with following choice of setpoints:

#Starting
#Power #Priority #Stopping
Nominal Power Load
BESS management Priority Auto Load
power management Reserve
mode Swap Reserve X
X
BESS
200 kW Enabled ABS (kW) 4 Disabled 50 kW 70 kW
#1
BESS
200 kW Enabled ABS (kW) 3 Disabled 50 kW 70 kW
#2
BESS
200 kW Enabled ABS (kW) 2 Disabled 50 kW 70 kW
#3
BESS
200 kW Enabled ABS (kW) 1 Disabled 50 kW 70 kW
#4

InteliNeo 6000 1.5.0 Global Guide 285


Image 5.130 Example of priorities in power management

By choosing the setpoint Priority (page 492) = 1, the BESS #4 is running all the time in the example shown on
the figure above (AUTO mode selected, Power management enabled and LBI GENERIC GENSET START/STOP
(PAGE 1004) activated).
The LBI TOP PRIORITY (PAGE 1030) can be used to force priority 0 into the setpoint Priority (page 492). Priority 0
is the "highest" one, which means the BESS will be running all the time while the power management is switched
on.
If more than one BESS have the same priority, they will act as "one big" BESS. There are methods of automatic
optimization of the priorities to achieve specific behavior of the group such as equalizing engine hours of the
BESSs or selection of optimal BESSs to run according to their size and current load demand.
6 back to Power Management

Priority auto swap


As stated in the chapter Priorities (page 285), the operator is able to select the order of BESS starting. There is
also the option of automatic priority selection. The controllers are sharing data concerning the running hours and
all important information relevant to the actual load. Thanks to the Automatic priority swapping function the
controllers choose the BESS(s) to be running with consideration of their running hours and the actual load.

InteliNeo 6000 1.5.0 Global Guide 286


The running hours equalization function keeps a constant maximal difference of BESS’s running hours. The
efficient function keeps running only the BESSs with suitable nominal power to avoid inefficient fuel consumption
or BESS overload.
Note: The Automatic priority swapping function does not change the setpoint Priority (page 492). The function
sets the order of BESSs by virtual values “engine priority”.

Run hours equalization


The BESSs engine priorities are automatically swapped to balance engine running hours. In other words, the
controllers compare running hours of each BESS and select BESS(s) to run in order to maintain constant
maximal difference of running hours. Up to 32 controllers are supported. This function is activated via setpoint
#Priority Auto Swap (page 493) = RUN HOURS.
The value of running hours which is used in run hours equalization is calculated by following formula:
RHE = Running Hours (page 880) - Run Hours Base (page 514)
RHE is considered value for running hours equalization, Running Hours (page 880) is a cumulative sum of run
hours available in statistic values of the controller, Run Hours Base (page 514) is a setpoint. This setpoint may
be used in the case of BESSs with different runs hours are intended to be set at the same initial point (e.g. a new
BESS and a used BESS after retrofit maintenance inspection).
The Running hours equalization function compares RHE value of each controller in the group. Once the
difference between RHE of individual controllers is higher than #Run Hours Max Difference (page 515) (i.e.
#Run Hours Max Difference (page 515) + 1), the BESS(s) with the lowest RHE is/are started.
Example: The system structure and its settings is shown on the figure below.

Image 5.131 Example of the system

3 cases are considered:


Case #1: 2 Gen-sets available
Case #2: 3 Gen-sets available with same initial RHE.
Case #3: 3 Gen-sets available with different initial RHE.

Case #1:
BESS 1 running hours = 250 -> running hours considered in RHE = 100 (150 - Run Hours Base (page
514))

InteliNeo 6000 1.5.0 Global Guide 287


BESS 2 running hours = 450 -> running hours considered in RHE = 200 (250 - Run Hours Base (page
514))
Both BESSs have the same nominal power of 700 kW. Originally, priority of BESSs was G1 = 2, G2 = 1. Load
demand in this example is constant and it is 500 kW (i.e. only one engine is running at any time). In this case, the
controllers set the engine priority of the BESS 1 to 1 because it has the lowest considered RHE and the
difference between RHE2 (i.e. considered RHE of BESS 2) and RHE1 is higher than #Run Hours Max
Difference (page 515) that is set to 10h.

Run hours #RunHoursBase RHE


BESS #1 250 150 100
BESS #2 450 250 200

The BESS 1 runs for 100 hours to equalize the RHE of both BESSs. The BESS 1 keeps running until the
difference between RHE1 and RHE2 exceeds #Run Hours Max Difference (page 515) (i.e. 10h). The BESS 1
runs 100 + #Run Hours Max Difference (page 515) + 1 = 100 + 10 + 1 = 111 hours. After 111 hours the BESSs
2 has the lowest RHE and the difference between RHE1 and RHE2 is higher than #Run Hours Max Difference
(page 515). The BESS 2 runs 11 hours to equalize the RHE of both BESSs and then additional #Run Hours
Max Difference (page 515) + 1 hours (i.e. 11 + 10 + 1 = 22 hours). The evaluation of RHE1 and RHE2 is shown
on the figure below.

Image 5.132 Run hours equalization - case #1

Step 0 1 2 3 4 5
RHE1 100 211 211 233 233 255
RHE2 200 200 222 222 244 244
Run G1 (ΔRHE1) 0 111 0 22 0 22
Run G2 (ΔRHE2) 0 0 22 0 22 0

From the example of the case #1, it can be concluded that the BESSs are swapped after the duration determined
by following formula:
SwapTime = Second lowest considered running hours – Current lowest considered running hours + #Run Hours
Max Difference (page 515) +1

InteliNeo 6000 1.5.0 Global Guide 288


Case #2:
BESS 1 running hours = 0 -> running hours considered in RHE = 0 (0-RunHoursBase)
BESS 2 running hours = 0 -> running hours considered in RHE = 0 (0-RunHoursBase)
BESS 3 running hours = 0 -> running hours considered in RHE = 0 (0-RunHoursBase)
Each BESS has the same RHE = 0 h. By applying the SwapTime formula, we get the run time of BESS 1 before
next swapping:
SwapTimeG1 = 0 – 0 + 10 + 1 = 11
Similar way, we get the run time of BESS 2 before next swapping:
SwapTimeG2 = 11 – 11 + 10 + 1 = 11
Finally, we get the run time of BESS 3 before next swapping:
SwapTimeG2 = 11 – 0 + 10 + 1 = 22
Please refer to figure below to understand the evaluation of RHE of BESSs in this particular case.

Image 5.133 Run hours equalization - case #2

step 0 1 2 3 4 5 6 7 8 9 10 11 12 13
RHE1 0 11 11 11 11 33 33 33 33 55 55 55 55 77
RHE2 0 0 11 11 22 22 33 33 44 44 55 55 66 66
RHE3 0 0 0 22 22 22 22 44 44 44 44 66 66 66
Run G1
0 11 0 0 0 22 0 0 0 22 0 0 0 22
(ΔRHE1)
Run G2
0 0 11 0 11 0 11 0 11 0 11 0 11 0
(ΔRHE2)
Run G3
0 0 0 22 0 0 0 22 0 0 0 22 0 0
(ΔRHE3)

Case #3:
BESS 1 running hours = 250 -> running hours considered in RHE = 100 (150-RunHoursBase)
BESS 2 running hours = 450 -> running hours considered in RHE = 200 (250-RunHoursBase)
BESS 3 running hours = 750 -> running hours considered in RHE = 250 (500-RunHoursBase)
The BESS 1 has the lowest RHE1 = 100 h. By applying the SwapTime formula, we get the run time of BESS 2
before next swapping:

InteliNeo 6000 1.5.0 Global Guide 289


SwapTimeG1 = 200 – 100 + 10 + 1 = 111
Till the step 5, the evaluation of the BESS swapping is the same as in the case #1, just BESS 1 and BESS 2
involve. In the step 6 the BESS 2 can run only 17 hours (previously 22 hours) because the BESS 3 involves. The
evaluation of RHE1, RHE2 and RHE3 is shown on the figure below.

Image 5.134 Run hours equalization - case #3

step 0 1 2 3 4 5 6 7 8 9 10 11 12 13
RHE1 100 211 211 232 233 255 255 255 272 272 272 288 288 288
RHE2 200 200 222 222 244 244 261 261 261 277 277 277 294 294
RHE3 250 250 250 250 250 250 250 266 266 266 283 283 283 299
Run G1
(ΔRHE 0 111 0 22 0 22 0 0 17 0 0 16 0 0
1)
Run G2
(ΔRHE 0 0 22 0 22 0 17 0 0 16 0 0 17 0
2)
Run G3
(ΔRHE 0 0 0 0 0 0 0 16 0 0 17 0 0 16
3)

Note: Setting #Run Hours Max Difference (page 515) = 5 does not mean that BESSs swap every 5 hours. The
Swap time is determined by the formula stated above. Please read the entire chapter Running hours
equalization for better understanding.

Note: In the case #Run Hours Max Difference (page 515) is set to 0 and all BESS in the group are at the same
initial point (RHE are equal), the BESS swapping happens every hour.

Efficiency
The BESSs engine priorities are automatically swapped to best fit to the actual load demand (load demand swap
- LDS). Also engine running hours are taken to the calculation (run hours equalization - RHE). This function is
activated via setpoint #Priority Auto Swap (page 493) = Efficiency.
The BESSs which should be currently running with actual load are shown in the values Actual Power Band 32
(page 860) and Actual Power Band 64 (page 860). The BESSs which should be running after #Power Band

InteliNeo 6000 1.5.0 Global Guide 290


Change Up Delay (page 515) or #Power Band Change Down Delay (page 516) elapsed, if load is increased
or decreased, are shown in the values Next Power Band 32 (page 860) and Next Power Band 64 (page 861).
Algorithm of function:
In the first step, the BESSs are sorted according to their nominal power.
In the second step, the BESSs with the same nominal power are sorted according to their RHE
The BESS(s) with nominal power which fits the most actual load demand are chosen. From those with
same nominal power, the BESS(s) with lowest RHE are chosen. Selection formula:
#Power Management Mode (page 491) = ABS (kW)
Nominal power of BESS > actual load demand + #Starting Load Reserve 1 (page 497)
#Power Management Mode (page 491) = REL (%)
Nominal power of BESS > (actual load demand × 100)/(100 - #Starting Rel Load Reserve 1
(page 499))
If two or more BESSs are available for taking over the load always the one with the lowest CAN address is
chosen.
If load demand is higher than nominal power of the biggest BESS, this one is fixed and the whole process
repeats from point the third bullet.
Example: The system structure and its settings is shown on the figure below.

Image 5.135 Example of the system

Following table provide an example of BESS selection in function of system load evaluation. The table is an
example of Efficiency priority optimization function (#Power Management Mode (page 491) = ABS (kW) and
#Starting Load Reserve 1 (page 497) = 20 kW).

Total Running
System Relative load
Running BESSs Description power within PM
Load [kW] of BESSs [%]
[kW]
40 5 100 40
60 5 100 60
5 2 start
80 LDS 300 26
2 [0h] 5 stop

InteliNeo 6000 1.5.0 Global Guide 291


Total Running
System Relative load
Running BESSs Description power within PM
Load [kW] of BESSs [%]
[kW]
100 2 [10h] 200 50
120 2 [20h] 200 60
2 [30h] 3 start
120 RHE Swap 400 30
3 [10h] 2 stop
120 3 [20h] 200 60
140 3 [30h] 200 70
3 [40h] 1 start
180 LDS 500 36
1 3 stop
200 1 300 67
240 1 300 80
1
280 5 start Gen#5 joins (LDS) 400 70
5
1
340 400 85
5
1
4 start
380 5 LDS + RHE Swap 600 63
5 stop
4 [20h]
1
400 500 80
4
1
440 500 88
4
1
480 4 5 start Gen#5 joins (LDS) 600 80
5
1
540 4 600 90
5
1
4 2 start
580 LDS 800 73
5 5 stop
2 [30h]
1
600 4 700 86
2
1
640 4 700 91
2
1
680 5 start Gen#5 joins (LDS) 800 85
4

InteliNeo 6000 1.5.0 Global Guide 292


Total Running
System Relative load
Running BESSs Description power within PM
Load [kW] of BESSs [%]
[kW]
2
5
1
4
740 800 93
2
5
1
4
3 start
780 2 LDS 1000 78
5 stop
5
3 [40h]
1
4
800 900 89
2
3
1
4
840 900 93
2
3
1
4
880 2 5 start Gen#5 joins (LDS) 1000 88
3
5
1
4
940 2 1000 94
3
5

6 back to Power Management

Minimal running power


Minimum Running Power function is used to adjust a minimum value of the sum of nominal power of all running
Controllers. If the function is active, then the Controllers would not be stopped, although the reserve for stop is
fulfilled. Function is activated via logical binary input MIN RUN POWER ACT 1 (PAGE 1014), MIN RUN POWER ACT
2 (PAGE 1014) and MIN RUN POWER ACT 3 (PAGE 1015).

InteliNeo 6000 1.5.0 Global Guide 293


Image 5.136 Minimal running power

Setpoints #Min Run Power (page 509), #Min Run Power 2 (page 509) or #Min Run Power 3 (page 510) are
adjusted to 400 kW. Once the #Min Run Power (page 509), #Min Run Power 2 (page 509) or #Min Run
Power 3 (page 510) is activated, the available nominal running power has to be equal or higher to 400 kW. Even
if the load reserve is big enough to stop the Controller #2 (nominal power 500 kW), the Controller keeps running
as at least 400 kW has to be available. The Controller#1 (nominal power 200 kW) is not enough.
6 back to Power Management

InteliNeo 6000 1.5.0 Global Guide 294


5.5.17 PV Curtailment
This function allows to limit power generated by PV (renewable source) inverter. The PI regulation (setpoints
Gain (page 464) and Int (page 465)) is used to regulate relative power of PV if the setpoint Curtailment
(page 464) is Enabled, BESS is not present in the system or it cannot consume any more power from the
system and power of Gen-sets goes below Gen P Min (page 465). The power of the PV is regulated
according to the PI regulation loop until the power of Gen-sets is equal to Gen P Min (page 465). The
PI regulation loop is also used to increase power of the PV if the relative power of the Gen-sets is above the
Gen P Min (page 465) and PV is not already running on 100 % of its nominal power.
If the function Curtailment is Disabled the setpoint Gen P Min (page 465) is still used in the function Load
Control Balance - Calculation of BESS P Request (page 240) because the BESS can still react on power
excess. The LBO CURTAILMENT ENABLE (PAGE 1068) is activated always when the curtailment is used to
regulate power of the PV. The actual maximal power of the PV inverter in percents is shown by the value
Curtailment Output (page 772).
Note: The maximal charging power of the BESS depends on the LAI BESS MAX CHARGE P (PAGE 1116).

5.5.18 Regulation Loops


Regulation loops overview
Regulation loops overview

Related
Loop type Related setpoints Related Operation
applications
Unloaded Run
Frequency Gain (page 469)
Frequency MINT, MPTM Synchronization
Frequency Int (page 470)
Single Island
Unloaded Run
Voltage Gain (page 482)
Voltage MINT, MPTM Synchronization
Voltage Int (page 482)
Single Island
Angle
MINT, MPTM Angle Gain (page 470) Phase Match Synchronization
regulation
Load Gain (page 471)
Load MINT, MPTM Parallel To Mains
Load Int (page 471)
PF Gain (page 483)
PF control MINT, MPTM Parallel To Mains
PF Int (page 483)
Load Sharing Gain (page 472)
Load sharing MINT Multiple Island
Load Sharing Int (page 472)
VAr Sharing Gain (page 484)
VAr sharing MINT Multiple Island
VAr Sharing Int (page 484)

Voltage, PF, VAr sharing have one common output = Voltage Request (page 866). The value of this output is
always composed from the contribution of each of the regulation loop.
Each of the regulation loops is active in some certain time during the process, which is given by the state of the
electronic state machine. If no regulation loop is active the Frequency Regulator Output (page 862) and

InteliNeo 6000 1.5.0 Global Guide 295


Voltage Regulator Output (page 866) are kept on the levels given by setpoints Frequency Governor Bias
(page 467) and Voltage Regulator Bias (page 480).
Note: All regulation loops are PID, but only PI components are visible as setpoints.

MINT Regulation Loops

Loop type Description


The frequency loop is active in the first phase of synchronization when the BESS frequency is
regulated to match the Mains/bus frequency and in single-island operation. The loop can be
also active all the time (while the BESS is running without load at nominal frequency ), see the
Frequency
setpoint Frequency Regulation Loop (page 469).
The frequency regulation loop can be active after the Minimal Stabilization Time (page 441)
elapsed in case of DC precharge or after BESS is loaded in case of AC precharge.
The voltage regulation loop is active in the first phase of synchronization when the BESS
voltage is regulated to match the Mains/bus voltage and in single-island operation. The loop is
Voltage also active when BESS is running without load (GCB opened) after Minimal Stabilization
Time (page 441)elapsed in case of DC precharge or after BESS is loaded in case of
AC precharge.
Angle The differential angle control loop is active during the second phase of synchronization to
regulation match the gen/bus angle when phase match synchronization type is used.
The load regulation loop is active when BESS is running in parallel with Mains and during load
Load
transfers from Mains to BESS or vice versa.
PF control The PF/Q regulation loop is active when BESS is running in parallel with Mains.
Load
The load sharing loop is active only in multiple-island operation.
sharing
VAr sharing The VAr sharing loop is active only in multiple-island operation.

InteliNeo 6000 1.5.0 Global Guide 296


MPTM Regulation Loop

Loop type Description


The frequency loop is active in the first phase of synchronization when the BESS frequency is
regulated to match the Mains/bus frequency and in single-island operation. The loop can be
also active all the time (while the BESS is running without load at nominal frequency ), see the
Frequency
setpoint Frequency Regulation Loop (page 469).
The frequency regulation loop can be active after the Minimal Stabilization Time (page 441)
elapsed in case of DC precharge or after BESS is loaded in case of AC precharge.
The voltage regulation loop is active in the first phase of synchronization when the BESS
voltage is regulated to match the Mains/bus voltage, in single-island operation, and when
Voltage
BESS is running without load (GCB opened) after Minimal Stabilization Time (page
441)elapsed in case of DC precharge or after BESS is loaded in case of AC precharge.
Angle The differential angle control loop is active during the second phase of synchronization to
regulation match the gen/bus or Mains/bus angle when phase match synchronization type is used.
The load regulation loop is active when BESS is running in parallel with Mains and during load
Load
transfers from Mains to BESS or vice versa.
The PF control loop is active when BESS is running in parallel with Mains and during load
PF control
transfers from Mains to BESS or vice versa.

Adjustment of regulation loops


The regulation loops have two adjustable factors: P-factor and I-factor (except angle regulation loop, which has
P-factor only). The P-factor (gain) influences the stability and overshoot of the regulation loop and the I-factor
(int) influences the steady-state error as well as the settling time. See the picture below for typical responses of a
PI regulation loop.

Image 5.137 Typical responses of PI regulator

For manual tuning of a control loop use following method:


Set both the I-factor and P-factor to 0.
Increase the P-factor slightly until the system starts to oscillate.
Adjust the P-factor back to approx. one half of the value where the oscillations started.
Increase the I-factor slightly to achieve optimal resulting response.

InteliNeo 6000 1.5.0 Global Guide 297


IMPORTANT: Be ready to press emergency stop button in case the regulation loop would start to
behave unacceptable while it is being adjusted.

6 back to Application related functions

InteliNeo 6000 1.5.0 Global Guide 298


6 Grid Codes
6.1 What are Grid Codes 299
6.2 Testing of Grid Codes 299
6.3 Power Regulation Based On Over/Under Frequency 299
6.4 Power Regulation Based On Actual Mains Voltage 302
6.5 Load Reduction 303
6.6 Dynamic Support - VRT 304
6.7 P For Q 306
6.8 Q&U Protection 307
6.9 Synchronization & Connection Conditions 307
6.10 After Mains Trip Period 308
6.11 Pave 309
6.12 Moving Average 309
6.13 BESS Operation Area 310

6 back to Table of contents

6.1 What are Grid Codes


Grid Codes are technical specifications which defines the parameters a facility connected to a public electric
network has to meet to ensure safe, secure and economic proper functioning of the electric system. The facility
can be an power generation plant, a solar farm, or any other grid connected source.

6.2 Testing of Grid Codes


Grid Codes functions can be tested. To enable Grid Codes testing setpoint Grid Codes Test (page 536) has to
be Enabled. When testing mode is active, alarm Wrn Test UPQF (page 1268) is present in the alarmlist.
LAIs related to testing:
LAI TESTF (PAGE 1151)
LAI TESTP (PAGE 1152)
LAI TESTQ (PAGE 1152)
LAI TESTU (PAGE 1152)

6.3 Power Regulation Based On Over/Under


Frequency
In case of over/under frequency, BESS must be able to reduce/increase the BESS P (page 707).
To enable these functions, setpoint Power Over/Under Frequency (page 544) has to be Enabled.

6.3.1 Power reduction by over frequency - PoF


The BESS must be able to reduce BESS P (page 707) in Mains/Bus Frequency (page 839) - range of
<Nominal Frequency (page 384) + 0,2 Hz, Nominal Frequency (page 384) + 1,5 Hz>. When Mains/Bus
Frequency (page 839) is in range defined by PoF for time longer than Power Over/Under Frequency Delay
(page 544), power reduction will begin. If the Mains/Bus Frequency (page 839) is over Nominal Frequency
(page 384) + 1,5 Hz, BESS can disconnect from the mains.

InteliNeo 6000 1.5.0 Global Guide 299


Note: Power Over/Under Frequency (page 544) has to be Enabled, otherwise PoF is not applied.

Power reduction is defined by Application Curve POWER OVER FREQUENCY (PAGE 975) which shall be adjusted
according to this formula:

After Mains/Bus Frequency (page 839) reaches (Nominal Frequency (page 384) + 0,2 Hz), BESS P (page
707) is stored in Pmom (page 829) and from this value is the power decreased.
Power is decreased/increased based on ramp (BESS Required P (page 861) is ramped to BESS Required P
Target (page 861)) that is corresponding with actual active event.
Note: If representative priority setpoint of actual active event is adjusted to OFF, then BESS Required P
(page 861) is ramped to BESS Required P Target (page 861) based on Load Ramp (page 477).

Event Used Ramp


LBO EVENT MAINS FREQUENCY RISE (PAGE 1075) Mains Frequency Rise Ramp (page 547)
LBO EVENT MAINS FREQUENCY FALL (PAGE 1075) Mains Frequency Fall Ramp (page 548)

While power is reduced due to over frequency, LBO P OVER FREQUENCY ACTIVE (PAGE 1096) is closed.

PoF related settings


Setpoints Values
Power Over/Under Frequency (page 544) Pmom (page 829)
Power Over/Under Frequency Delay (page 544) P Over Frequency Curve (page 829)
Mains Frequency Rise Priority (page 547) BESS Required P (page 861)
Mains Frequency Rise Ramp (page 547) BESS Required P Target (page 861)
Mains Frequency Fall Priority (page 548) LBOs
Mains Frequency Fall Ramp (page 548) P OVER FREQUENCY ACTIVE (PAGE 1096)
Application Curves P OVER FREQUENCY CURVE INVALID (PAGE 1096)
POWER OVER FREQUENCY (PAGE 975) EVENT MAINS FREQUENCY RISE (PAGE 1075)
EVENT MAINS FREQUENCY FALL (PAGE 1075)
Grid Codes Test (page 536) = Enabled
LAI TESTF (PAGE 1151)
LAI TESTP (PAGE 1152)

6.3.2 Power increase by under frequency - PuF


The BESS must be able to increase BESS P (page 707) in Mains/Bus Frequency (page 839) range of
<Nominal Frequency (page 384) - 2,5 Hz, Nominal Frequency (page 384) - 0,2 Hz>. When Mains/Bus
Frequency (page 839) is in range defined by PuF for time longer than Power Over/Under Frequency Delay
(page 544), power increase will begin. If the Mains/Bus Frequency (page 839) is under Nominal Frequency
(page 384) - 2,5 Hz, BESS can disconnect from the mains.
Note: Power Over/Under Frequency (page 544) has to be Enabled, otherwise PuF is not applied.

Power increase is defined by Application Curve POWER UNDER FREQUENCY (PAGE 976) which shall be adjusted
according to this formula:

InteliNeo 6000 1.5.0 Global Guide 300


.
After Mains/Bus Frequency (page 839) drops bellow (Nominal Frequency (page 384) - 0,2 Hz), BESS P
(page 707) is stored in Pmom (page 829) and from this value is the power increased.
Power is decreased/increased based on ramp (BESS Required P (page 861) is ramped to BESS Required P
Target (page 861)) that is corresponding with actual active event.
Note: If representative priority setpoint of actual active event is adjusted to OFF, then BESS Required P
(page 861) is ramped to BESS Required P Target (page 861) based on Load Ramp (page 477).

Event Used Ramp


LBO EVENT MAINS FREQUENCY RISE (PAGE 1075) Mains Frequency Rise Ramp (page 547)
LBO EVENT MAINS FREQUENCY FALL (PAGE 1075) Mains Frequency Fall Ramp (page 548)

While power is increased due to under frequency, LBO P UNDER FREQUENCY ACTIVE (PAGE 1096) is closed.

PuF related settings


Setpoints Values
Power Over/Under Frequency (page 544) Pmom (page 829)
Power Over/Under Frequency Delay (page 544) P Over Frequency Curve (page 829)
Mains Frequency Rise Priority (page 547) BESS Required P (page 861)
Mains Frequency Rise Ramp (page 547) BESS Required P Target (page 861)
Mains Frequency Fall Priority (page 548) LBOs
Mains Frequency Fall Ramp (page 548) P UNDER FREQUENCY ACTIVE (PAGE 1096)
Application Curves P UNDER FREQUENCY CURVE INVALID (PAGE 1096)
POWER UNDER FREQUENCY (PAGE 976) EVENT MAINS FREQUENCY RISE (PAGE 1075)
EVENT MAINS FREQUENCY FALL (PAGE 1075)
Grid Codes Test (page 536) = Enabled
LAI TESTF (PAGE 1151)
LAI TESTP (PAGE 1152)

6.3.3 Return from over/under frequency


After Mains/Bus Frequency (page 839) returns into range (Nominal Frequency (page 384) - 0,2 Hz, Nominal
Frequency (page 384) + 0,2 Hz), EVENT RETURN OVER/UNDER FREQUENCY (PAGE 1076) begins.
The start of the event can be delayed by the setpoint Return Over/Under Frequency Delay (page 545), once
the delay timer is elapsed the LBO EVENT RETURN OVER/UNDER FREQUENCY (PAGE 1076) is closed for the period
given by the setpoint Return Over/Under Frequency Period (page 545). When the event is active, BESS
Required P (page 861) is always ramped to the BESS Required P Target (page 861) based on Return From
Over/Under Frequency Ramp (page 546).
Each Grid Code has its priority over the other Grid Codes. The priority of the Return from over/under frequency is
given by the setpoint Return From Over/Under Frequency Priority (page 546).
Note: If Return From Over/Under Frequency Priority (page 546) = OFF, then BESS Required P (page
861) is ramped to BESS Required P Target (page 861) based on Load Ramp (page 477).

InteliNeo 6000 1.5.0 Global Guide 301


6.4 Power Regulation Based On Actual Mains
Voltage
The BESS's BESS P (page 707) is regulated based on value +Mains/Bus Voltage Relative (page 841). In
case that +Mains/Bus Voltage Relative (page 841) is over 100 %, application curve P(Um) (page 971) is
activated and BESS P (page 707) becomes limited. Ramping of value BESS Required P (page 861) to BESS
Required P Target (page 861) is affected by setpoint P Ramp Filter (page 554).
There are two modes modes of this function.

6.4.1 P Instal (Um)


Setpoint P(Um) (page 553) has to be adjusted to P Instal (Um). This mode is then related to the setpoint
Installed Power (page 375). Maximal allowed BESS P (page 707) is calculated as:

P Instal (Um) related settings


Setpoints Values
Installed Power (page 375) P(Um) Curve (page 831)
P(Um) (page 553) LBOs
P Ramp Filter (page 554) EVENT P(UM) (PAGE 1076)
P(Um) Priority (page 555)
P(Um) Ramp (page 555) Grid Codes Test (page 536) = Enabled
Application Curves LAI TESTU (PAGE 1152)
P(UM) (PAGE 971)

6.4.2 P Actual (Um)


Setpoint P(Um) (page 553) has to be adjusted to P Instal (Um). This mode is then related to value Pmom
(page 829). Value Pmom (page 829) is filled with BESS P (page 707) at the moment of activation of this
function. Maximal allowed BESS P (page 707) is calculated as:

PuF related settings


Setpoints Values
P(Um) (page 553) Pmom (page 829)
P Ramp Filter (page 554) P(Um) Curve (page 831)
P(Um) Priority (page 555) LBOs
P(Um) Ramp (page 555) EVENT P(UM) (PAGE 1076)
Application Curves
Grid Codes Test (page 536) = Enabled
POWER UNDER FREQUENCY (PAGE 976)
LAI TESTU (PAGE 1152)

InteliNeo 6000 1.5.0 Global Guide 302


6.5 Load Reduction
The controller allows remote load control of the BESS. This mechanism is dedicated for purposes when utility
company wants to control the BESS's load on predefined load levels. To enable this function it is necessary to set
setpoint Load Reduction (page 549) to Enabled and activate the LBI LOAD REDUCTION ENABLE (PAGE 1007).
Each state of the Load Reduction is activated by the specific LBI Load Reduction and each LBI is connected with
the same named setpoint which adjust relative maximal power produced by the BESS. Or the maximal allowed
load of the BESS can be defined by the LAI LOAD REDUCTION (PAGE 1122). Always the lowest load defined by the
LAI or by LBIs is allowed. If more than 1 LBI Load Reduction is activated, then reduction with the smallest
setpoint value is applied. When any Load Reduction state is active the LBO LOAD REDUCTION ACTIVE (PAGE
1085) is closed.
Note: The LAI LOAD REDUCTION (PAGE 1122) allows the power reduction on the analog signal, but the statistic
will not be fulfilled.

The activation of the Load Reduction event is being signalized by closing the LBO EVENT LOAD REDUCTION (PAGE
1075). Once the LBO is closed the BESS Required P (page 861) will be ramped to the BESS Required P
Target (page 861) according to the ramp which maximum is given by the setpoint Installed Power (page 375)
or by the setpoint Nominal power (page 375) if the Installed Power is OFF. The duration of the whole ramp
(from the maximum to the 0) is given by the setpoint Load Reduction Ramp (page 552).
The event and LBO EVENT LOAD REDUCTION (PAGE 1075) stays active after deactivation of all LBIs until BESS
Required P (page 861) is ramped to the new unreduced BESS Required P Target (page 861) according to
Load Reduction Ramp (page 552). So, the event Load Reduction is active for both reducing and increasing the
power.
Each Grid Code has its priority over the other Grid Codes. The priority of the Load Reduction is given by the
setpoint Load Reduction Priority (page 551). If this priority is set to OFF, then BESS Required P (page 861)
will be ramped to the BESS Required P Target (page 861) according to the Load Ramp (page 477).
IMPORTANT: LBI LOAD REDUCTION ENABLE (PAGE 1007) has to be closed and setpoint Load Reduction
(page 549) has to be Enabled, otherwise Load Reduction is not activated by any of LBIs mentioned
bellow.

List of LBIs and related setpoints


LBI Setpoint
LOAD REDUCTION 1 (PAGE 1006) Load Reduction 1 (page 549)
LOAD REDUCTION 2 (PAGE 1006) Load Reduction 2 (page 550)
LOAD REDUCTION 3 (PAGE 1007) Load Reduction 3 (page 550)
LOAD REDUCTION 4 (PAGE 1007) Load Reduction 4 (page 551)

Example: When LBI LOAD REDUCTION 1 (PAGE 1006) is activated and setpoint Load Reduction 1 (page
549) = 50%, then BESS's load will be limited to 50% of Installed Power (page 375) or Nominal power
(page 375).

InteliNeo 6000 1.5.0 Global Guide 303


6.6 Dynamic Support - VRT
Dynamic Support keeps the BESS voltage during short Mains failures on medium or high voltage site for
unwanted disconnection of big power sources which could reduce Mains unbalances.
There are 4 kinds of Dynamic Support protections. To enable any of them setpoint Dynamic Support (page
561) != Disabled and behavior of the protections is adjusted via Dynamic Support Protection Type (page
561).
For a critical undervoltage there is special setpoint LVRT Level Severe (page 562) when relative mains voltage
drops bellow this limit, LBO LVRT SEVERE (PAGE 1089) is closed for at least 500 ms, no further action is taken.
Note: You can deactivate PF/Q regulation while VRT function is active, use setpoint Dynamic Support PF/Q
Control (page 562) to select whether Voltage Regulator Output (page 866) will be frozen at the moment of
activation of the VRT function.

Image 5.138 VRT - Under voltage failure

6.6.1 3-pole undervoltage failure ride through - LVRT-3ph


This protection is defined by LVRT 3-PHASE (PAGE 981) curve and requires all three phases to be below allowed
limit in order to activate the protection.
Relative value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839) and
Mains/Bus Voltage L3-N (page 840) to Mains/Bus Nominal Voltage Ph-N (page 381)
Relative value of Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page 840) and
Mains/Bus Voltage L3-L1 (page 840) to Mains/Bus Nominal Voltage Ph-Ph (page 381)
When the curve is tripped, LBO LVRTCURVETRIP (PAGE 1089) is closed, for at least 3 seconds, together with
LBO LVRT ACTIVE (PAGE 1089), which stays closed for whole time the protection is active. Proper alarm/history
record is activated based on Dynamic Support Protection Type (page 561).

InteliNeo 6000 1.5.0 Global Guide 304


Note: Mains <V Protection (page 581) and Mains <V Protection (page 582) are still being evaluated! In case
that LVRT 3-PHASE (PAGE 981) is not configured correctly or is missing, LBO LVRT 3-PHASE INVALID (PAGE
1089) is closed and the protection is not evaluated.

6.6.2 2-pole undervoltage failure ride through - LVRT-2ph


This protection is defined by LVRT 2-PHASE (PAGE 982) curve and requires at least two phases to be below
allowed limit in order to activate the protection.
Relative value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839) and
Mains/Bus Voltage L3-N (page 840) to Mains/Bus Nominal Voltage Ph-N (page 381)
Relative value of Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page 840) and
Mains/Bus Voltage L3-L1 (page 840) to Mains/Bus Nominal Voltage Ph-Ph (page 381)
When the curve is tripped, LBO LVRTCURVETRIP (PAGE 1089) is closed, for at least 3 seconds, together with
LBO LVRT ACTIVE (PAGE 1089), which stays closed for whole time the protection is active. Proper alarm/history
record is activated based on Dynamic Support Protection Type (page 561).
Note: Mains <V Protection (page 581) and Mains <V Protection (page 582) are still being evaluated! In case
that LVRT 2-PHASE (PAGE 982) is not configured correctly or is missing, LBO LVRT 2-PHASE INVALID (PAGE
1088) is closed and the protection is not evaluated.

6.6.3 1-pole undervoltage failure ride through - LVRT-1ph


This protection is defined by LVRT 1-PHASE (PAGE 983) curve and requires at least one phase to be below
allowed limit in order to activate the protection.
Relative value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839) and
Mains/Bus Voltage L3-N (page 840) to Mains/Bus Nominal Voltage Ph-N (page 381)
Relative value of Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page 840) and
Mains/Bus Voltage L3-L1 (page 840) to Mains/Bus Nominal Voltage Ph-Ph (page 381)
When the curve is tripped, LBO LVRTCURVETRIP (PAGE 1089) is closed, for at least 3 seconds, together with
LBO LVRT ACTIVE (PAGE 1089), which stays closed for whole time the protection is active. Proper alarm/history
record is activated based on Dynamic Support Protection Type (page 561).
Note: Mains <V Protection (page 581) and Mains <V Protection (page 582) are still being evaluated! In case
that LVRT 1-PHASE (PAGE 983) is not configured correctly or is missing, LBO LVRT 1-PHASE INVALID (PAGE
1088) is closed and the protection is not evaluated.

6.6.4 Overvoltage failure ride through - OVRT


This protection is defined by OVRT (PAGE 984) curve and requires at least one phase to be above allowed limit in
order to activate the protection.
Relative value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839) and
Mains/Bus Voltage L3-N (page 840) to Mains/Bus Nominal Voltage Ph-N (page 381)
Relative value of Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page 840) and
Mains/Bus Voltage L3-L1 (page 840) to Mains/Bus Nominal Voltage Ph-Ph (page 381)
When the curve is tripped, LBO OVRTCURVETRIP (PAGE 1095) is closed, for at least 3 seconds, together with
LBO OVRT ACTIVE (PAGE 1095), which stays closed for whole time the protection is active. Proper alarm/history
record is activated based on Dynamic Support Protection Type (page 561).

InteliNeo 6000 1.5.0 Global Guide 305


Note: Mains >V Protection (page 577) and Mains >>V Protection (page 579) are still being evaluated! In
case that OVRT (PAGE 984) is not configured correctly or is missing, LBO OVRT INVALID (PAGE 1095) is closed
and the protection is not evaluated.

6.6.5 Post VRT


If the Application Mode (page 885) = MPTM, the protection is activated once LBO OVRT ACTIVE (PAGE 1095)
or LBO LVRT ACTIVE (PAGE 1089) is closed for a period longer than 5 seconds and BESS's current is higher than
the nominal current. In this case, the LBO EVENT POST VRT (PAGE 1076) is closed and BESS P (page 707) is
decreased in order to keep circuit breakers closed. So, the BESS Required P (page 861) is ramped to the
BESS Required P Target (page 861) based on the ramp which maximum is given by the setpoint Installed
Power (page 375) or by the setpoint Nominal power (page 375) if the Installed Power is OFF and the duration
of the ramp is given by the setpoint Post VRT Ramp (page 563). The Post VRT is active for the maximal time
period of 60 seconds, after this period the standard Mains protection has to be evaluated.
If the Application Mode (page 885) = MINT the Post VRT can be activated only by activating the LBI POST VRT
(PAGE 1015). In this case, the Post VRT is activated (the LBO EVENT POST VRT (PAGE 1076) is closed) if BESS's
current is higher than the nominal current and the LBI is active.

6.7 P For Q
The Grid codes connection requirements, namely for the medium voltage system, require a possibility of BESS
BESS P (page 707) reduction in order to achieve required BESS Q (page 708).
The function is enabled/disabled by setpoint P For Q Limitation (page 556) and behavior is adjusted by P For
Q Deadband (page 556).
If relative value of BESS Required Q (page 865) will be over limit, BESS P (page 707) will be decreased to
reach BESS Required Q (page 865). To prevent oscilation of BESS P (page 707) adjust properly P For Q
Deadband (page 556).

6.7.1 UQ Area
UQ area defines maximal reachable BESS Q (page 708) based on actual Mains voltage (Um). This area is
adjusted by P FOR Q UQ L (PAGE 977) - inductive part, and P FOR Q UQ C (PAGE 978) - capacity part.
Note: Um is counted as average of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page
839) and Mains/Bus Voltage L3-N (page 840) related to Mains/Bus Nominal Voltage Ph-N (page 381).

The area is used while BESS P (page 707) = +-5% of Installed Power (page 375) and BESS P (page 707) can
be reduced only if the required BESS Q (page 708) is inside this area, otherwise LBO UQ-C AREA LIMIT (PAGE
1109) respectively LBO UQ-L AREA LIMIT (PAGE 1109) is closed and BESS P (page 707) is not reduced. In case
this is fulfilled, LBO P FOR Q ACTIVE (PAGE 1096) is closed and BESS P (page 707) begins to be reduced using
P For Q Ramp (page 557). LBO EVENT P FOR Q (PAGE 1076) is closed while P For Q Ramp (page 557) is
being used.
Note: P For Q Ramp (page 557) has priority given by P For Q Priority (page 557), different ramp with
higher priority can be active.

6.7.2 PQ Area
PQ area defines maximal reachable BESS Q (page 708) based on actual BESS P (page 707) related to
Installed Power (page 375). This area is adjusted by P FOR Q PQ L (PAGE 979) - inductive part, and P FOR Q
PQ C (PAGE 980) - capacity part.

InteliNeo 6000 1.5.0 Global Guide 306


The area is used while BESS P (page 707) is bellow Installed Power (page 375) and BESS P (page 707) can
be reduced only if the required BESS Q (page 708) is inside this area, otherwise LBO PQ-C AREA LIMIT (PAGE
1098) respectively LBO PQ-L AREA LIMIT (PAGE 1098) is closed and BESS P (page 707) is not reduced. In case
this is fulfilled, LBO P FOR Q ACTIVE (PAGE 1096) is closed and BESS P (page 707) begins to be reduced using
P For Q Ramp (page 557). LBO EVENT P FOR Q (PAGE 1076) is closed while P For Q Ramp (page 557) is
being used.
Note: P For Q Ramp (page 557) has priority given by P For Q Priority (page 557), different ramp with
higher priority can be active.

6.8 Q&U Protection


This protection watches behavior of the BESS in case of the drop of Mains Voltage and uses measurement
method of Symmetrical components (page 16).
BESS must be disconnected from the mains in case that Mains Voltage drops below a certain value of
Mains/Bus Nominal Voltage Ph-N (page 381) or Mains/Bus Nominal Voltage Ph-Ph (page 381) and BESS
is under excited.
The protection is enabled by setpoint Q&U Protection (page 558) and the behavior is adjusted by setpoints
Q&U < V (page 559), Q&U < Q (page 559), Q&U Protection Delay (page 560) and Q&U CB Selector (page
560).
When Mains/Bus Voltage L1-N (page 839) drops below relative limit given by Q&U < V (page 559) and at the
same time BESS Q (page 708) drops below limit given by Q&U < Q (page 559) minimally for period set by Q&U
Protection Delay (page 560), then breaker, selected by Q&U CB Selector (page 560), will be opened and
alarm Wrn Q&U Protection (page 1262) is activated.
Note: Breaker can not be reclosed if the alarm Wrn Q&U Protection (page 1262) is still present in alarm list.

6.9 Synchronization & Connection Conditions


Grid codes requires specific conditions to be fulfilled in order to synchronize BESS to the Mains. These
conditions take effect when BESS is running if setpoint Mains Params/MP Synchronization (page 536) =
Enabled.
This protection is checking mains voltage and frequency, if the parameters are not within limits, BESS is not
allowed to synchronize with the Mains. The alarm AHI SyncNotAllowed (page 1276) is activated and stays
active until the problem persists or BESS is stopped, then LBO SYNC TO MAINS ALLOWED (PAGE 1108) is
opened.
Note: This protection is evaluated only if BESS is running and is not synchronized with Mains.

6.9.1 Network connection/reconnection conditions


Synchronization is forbidden if:
Mains Params/MP Synchronization (page 536) = Enabled and
At least one of the Ph-N voltages such as Mains/Bus Voltage L1-N (page 839) or Ph-Ph voltages such
as Mains/Bus Voltage L1-L2 (page 840) (depends on the type of wiring) is out of the relative limit
adjusted by Mains Synchronization V Max (page 537) and Mains Synchronization V Min (page 537).
Mains/Bus Frequency (page 839) is out of the limit adjusted by Mains Synchronization f Max (page
538) and Mains Synchronization f Min (page 538).
Note: Alarm AHI SyncNotAllowed (page 1276) is active while synchronization is forbidden.

InteliNeo 6000 1.5.0 Global Guide 307


Note: Network connection/reconnection conditions after Mains Fail (page 308) has higher priority
while it is active.

6.9.2 Network connection/reconnection conditions after Mains


Fail
When the Mains Fail occurs (MAINS/BUS HEALTHY (PAGE 1090)) is opened), there is a requirement to prevent the
connection to the unstable mains. Timer After MP Synchronization Period (page 541) is activated and
synchronization to Mains is forbidden for this time (LBO SYNC TO MAINS ALLOWED (PAGE 1108) is opened and
alarm AHI SyncNotAllowed (page 1276) is active).
For Mains Params/MP Synchronization (page 536) = Enabled the synchronization is allowed only if all Mains
parameters are within the limit for the whole time of the After MP Synchronization Period (page 541).
All of the Ph-N voltages such as Mains/Bus Voltage L1-N (page 839) and Ph-Ph voltages such as
Mains/Bus Voltage L1-L2 (page 840) (depends on the type of wiring) have to be within the limit adjusted
by After MP Synchronization V Max (page 539) and After MP Synchronization V Min (page 540).
Mains/Bus Frequency (page 839) have to be within the limit adjusted by After MP Synchronization f
Max (page 540) and After MP Synchronization f Min (page 541).
Note: Timer After MP Synchronization Period (page 541) resets every time parameters are not within limits.

6.10 After Mains Trip Period


When the Mains returns from failure, it is recommended to load it slowly to prevent another failure. To activate
this function it is necessary to set setpoint After Mains Trip (page 542) to Enabled. Once the Mains is healthy
(LBO MAINS/BUS HEALTHY (PAGE 1090) is closed) and timer After MP Synchronization Period (page 541) is
elapsed or Mains Params/MP Synchronization (page 536) is disabled the LBO EVENT MAINS TRIP (PAGE
1076) is closed for time given by the setpoint After Mains Trip Period (page 542).
Note: Timer After Mains Trip Period (page 542) resets every time MAINS/BUS HEALTHY (PAGE 1090) re-
closes.

If the BESS starts to being unloaded in order to transfer Load to Mains and the LBO EVENT MAINS TRIP (PAGE
1076) is closed, the BESS Required P (page 861) will be ramped to the BESS Required P Target (page 861)
according to the ramp. So, the Mains is loaded according to the ramp which maximum is given by the setpoint
Installed Power (page 375) or by the setpoint Nominal power (page 375) if the Installed Power is OFF and the
duration of the ramp is given by the setpoint After Mains Trip Period Ramp (page 543).
Each Grid Code has its priority over the other Grid Codes. The priority of the After Mains Trip Period is given by
the setpoint After Mains Trip Period Priority (page 543).

InteliNeo 6000 1.5.0 Global Guide 308


6.11 Pave
The Pave function controls whether exported power to the grid is inside allowed range. The setpoint Pave
Protection (page 569) != Disabled in order to enable this function. Maximal allowed exported power is adjusted
by setpoint Pave (page 569). Exported power has to be measured in all 3 phases and preferably by using
InteliPro Sync and send via CAN Intercontroller Communication (page 132) to LAI PMOM (PAGE 1125). From
LAI PMOM (PAGE 1125) and setpoint Pave (page 569) is calculated value Pmom/Pave (page 832) which is used
in application curve P MOM/PAVE MAX (PAGE 972). When Pmom/Pave (page 832) is above the curve P
MOM/PAVE MAX (PAGE 972), LBO PAVE (PAGE 1097) is closed and if the value is above allowed limit for period
longer than is allowed by the application curve, the MCB is opened and alarm Hst Pave (page 1277) is
activated.
Note: When Pave Protection (page 569) != Disabled but LAI PMOM (PAGE 1125) is not configured or has
invalid value, LBO PAVE FLS (PAGE 1097) is closed.

Pave related settings


Setpoints Values
Pave Protection (page 569) Pmom/Pave (page 832)
Pave (page 569) LBOs
Application Curves PAVE (PAGE 1097)
P MOM/PAVE MAX (PAGE 972) PAVE FLS (PAGE 1097)
LAIs
PMOM (PAGE 1125)

6.12 Moving Average


The controller is measuring moving averages of selected values. This means that in specific time window is
measured value stored and average is counted from these data.
After reaching maximal amount of samples, i.e. value has been measured for whole required time, oldest sample
is always replaced with new sample.

6.12.1 10-minutes averages


These values hold average of corresponding physical quantity for last 10 minutes.

BESS P 10 min Avg


Calculation is started with closing BCB breaker and is stopped after the breaker opens. The calculation is stored
in value BESS P 10min Avg (page 717).
IMPORTANT: The value BESS P 10min Avg (page 717) is erased every time BCB breaker opens.

BESS Q 10 min Avg


Calculation is started with closing BCB breaker and is stopped after the breaker opens. The calculation is stored
in value BESS Q 10min Avg (page 718).
IMPORTANT: The value BESS Q 10min Avg (page 718) is erased every time BCB breaker opens.

BESS S 10 min Avg


Calculation is started with closing BCB breaker and is stopped after the breaker opens. The calculation is stored
in value BESS S 10min Avg (page 718).
IMPORTANT: The value BESS S 10min Avg (page 718) is erased every time BCB breaker opens.

InteliNeo 6000 1.5.0 Global Guide 309


Mains Voltage 10 min Avg
Calculation is carried out continuously whole time the controller is powered on. The calculation is made
separately for each phase and depends on setpoint Connection type (page 378).
Ph-Ph connection types uses values Mains Voltage 10min Avg L1-L2 (page 851), Mains Voltage 10min
Avg L2-L3 (page 851) and Mains Voltage 10min Avg L3-L1 (page 851).
Ph-N connection types uses values Mains Voltage 10min Avg L1-N (page 849), Mains Voltage 10min Avg
L2-N (page 849) and Mains Voltage 10min Avg L3-N (page 849).
IMPORTANT: The values mentioned above are erased when the controller is switched off.

6.12.2 1-minute averages


These values hold average of corresponding physical quantity for last 1 minute.

Mains Voltage 1 min Avg


Calculation is carried out continuously whole time the controller is powered on. The calculation is made
separately for each phase and depends on setpoint Connection type (page 378).
Ph-Ph connection types uses values Mains Voltage 1min Avg L1-L2 (page 851), Mains Voltage 1min Avg
L2-L3 (page 852) and Mains Voltage 1min Avg L3-L1 (page 852).
Ph-Pn connection types uses values Mains Voltage 1min Avg L1-N (page 850), Mains Voltage 1min Avg
L2-N (page 850) and Mains Voltage 1min Avg L3-N (page 850).
IMPORTANT: The values mentioned above are erased when the controller is switched off.

6.13 BESS Operation Area


It is possible to adjust the BESS operation area in more details, using application curves. The curves represent
inductive and capacitive halves of the PQ diagram.
Inductive operation area is adjusted by CAPABILITY L (PAGE 973) and if the required BESS Power Factor
(page 710) with BESS Load Character (page 710) = L are behind the limit, LBO BESS CAPABILITY L
LIMIT (PAGE 1064) is closed and actual power factor stays on the edge of the curve.
Inductive operation area is adjusted by CAPABILITY C (PAGE 974) and if the required BESS Power Factor
(page 710) with BESS Load Character (page 710) = C are behind the limit, LBO BESS CAPABILITY C
LIMIT (PAGE 1064) is closed and actual power factor stays on the edge of the curve.
IMPORTANT: The both Capability C and L curves have to be setup according to the Capability
curves of the worst (weakest) BESS in order to ensure right functionality of the whole system.

InteliNeo 6000 1.5.0 Global Guide 310


7 Communication
7.1 PC 311
7.2 Connection to 3rd party systems 314

6 back to Table of contents

7.1 PC
7.1.1 Direct communication 311
7.1.2 Remote communication 312

7.1.1 Direct communication


Computer can be connected to InteliNeo6000 via USB, RS485 or ethernet interface.

Connection via USB


USB A to B cable can be used for communication via USB ports. The InteliNeo6000 is using Human Interface
Devices (HID) protocol which support auto detection of the connected HW. The USB is not industrial interface
and it is not recommended to use it for long term purposes because of interference which can cause lost of
communication.

Image 6.1 Shielded USB type A cable is used

Connection via RS485


On board RS485 connector can be used for communication via RS485 connection. This interface uses
RS485 Modbus Mode (page 394) port of the controller. It is also possible to use RS485-USB convertor.

Image 6.2 Built-in RS485 is used

Image 6.3 RS485 and USB is used

InteliNeo 6000 1.5.0 Global Guide 311


Connection via Ethernet
Ethernet Cat5/Cat6 cable fitted with the RJ45 connector can be used for communication via Ethernet.
Controllers in local network are automatically detected byInteliConfig PC tool. For the direct connection it is
recommended to use Trusted (page 226) interface which is in default configured to port Ethernet 1 (page
19). This communication is more reliable than the USB because it is more robust against interference.

Image 6.4 Ethernet cable is used

Image 6.5 Onboard Ethernet cable is used

6 back to Communication

7.1.2 Remote communication


The InteliNeo6000 can be connected also remotely via built-in ethernet ports. For remote connection the
Untrusted (page 226) interface which is in default configured to port Ethernet 2 (page 19) should be used.

Ethernet LAN connection


Direct IP LAN connection is intended to be used to connect more than one controller at the same time while
controllers are connected to the local are network (LAN). For LAN connections, it is recommended to use
Trusted (page 226) interface which is in default configured to port Ethernet 1. If there is not any device which
would provide DHCP for the LAN the static (manual) IP address must be used.

Image 6.6 Ethernet LAN connection

InteliNeo 6000 1.5.0 Global Guide 312


Setting-up static IP address
This settings is related to Group: ETH Interface 1 - Trusted (page 406), Group: ETH Interface 2 -
Untrusted (page 412) and Group: ETH Interface 3 - Modbus (page 431) .
There are two basic ways how to setup static IP address for remote ethernet connection. The first way is to
switch the Ethernet to manual IP address mode. Adjust the setpoint IP Address Mode to Manual option. In this
moment values for related Ethernet port are immediately changed to the default or previously setup values of
setpoints IP Address, Subnet Mask, Gateway IP, DNS IP, etc. If you are using this Ethernet port for
connection to the controller you will lost the connection.
If this method is used several basic rules should be kept to avoid conflicts with the remaining network
infrastructure:
The static IP used in the controller must be selected in accordance with the local network in which the
controller is connected.
The static IP used in the controller must be excluded from the pool of addresses which is assigned by
DHCP server, which is in charge of the respective local network.
The local infrastructure must generally allow using devices with manually assigned IP addresses.
There must not be any other device using the same static IP address. This can be tested from a computer
connected to the same network using "ping <required_ip_address>" command issued from the command
line. The IP address is not occupied if there is not any response to the ping command.
Note: The list above contains only basic rules. Other specific restrictions/rules may take place depending on
the local network security policy, technology used, topology etc.

The second way is to switch the Ethernet to manual IP address mode. Adjust the setpoint IP Address Mode to
Manual option. In this moment values for related Ethernet port are immediately changed to values given by
the DHCP server for the LAN. If you are using this Ethernet port for connection to the controller you will lost
the connection. It is possible to configure the DHCP server to assign always the same IP address (i.e. static
IP address) to the particular controller according to it's MAC address.

Internet WAN connection


WAN connection is intended to be used to connect the controller using the internet. It is recommended to use
Ethernet 2 (untrusted interface) for remote connection using internet.

Image 6.7 Ethernet WAN connection

InteliNeo 6000 1.5.0 Global Guide 313


Public static IP
If public static IP connection is to be used from the Internet, the IP address, which is entered into the client
computer, must be static and public in scope of the Internet.
If the controller is connected to Internet via a local ethernet network then in most cases port forwarding must
be created from the public IP address of the network gateway to the local IP address of the controller at the
port specified for ComAp protocol. Different port numbers can be used to create multiple port forwarding rules
in the same local network.
6 back to Communication

7.2 Connection to 3rd party systems


7.2.1 SNMP 314
7.2.2 Modbus-RTU, Modbus/TCP 316

6 back to Communication

7.2.1 SNMP
SNMP is an UDP-based client-server protocol used for providing data and events into a supervisory system
(building management system). The controller plays the role of a "SNMP Agent" while the supervisory system
plays the role of a "SNMP Manager".
Supported versions – SNMP v1, SNMP v2c and SNMP v3
The SNMP Agent function is to be enabled by the setpoint SNMP Agent (page 426). The setpoints SNMP
RD Community String (page 427) and SNMP WR Community String (page 427) in the same group can
be used to customize the "community strings" for the read and write operations which have function like
"passwords". All requests sent from the SNMP Manager have to contain community string which match with
the community string adjusted in the controller otherwise the controller refuses the operation.

MIB table
The "MIB table" (Management Information Base) is a table which gives to the Manager description of all
objects provided by the Agent.
The MIB table is specific for each controller type and configuration
The MIB table is to be exported from the controller configuration using InteliConfig
Controllers with identical firmware and configuration share also identical MIB table, however if the
configuration and/or firmware is not identical the MIB table is different and must be exported separately for
each controller.
The root node of the MIB table of InteliLite controller is enterprises.comapProjekt.il, which is
1.3.6.1.4.1.28634.14. Under this node there are following sub-nodes :
Notifications group (SMI v2 only) contains definitions of all notification-type objects that the Agent may
send to the Manager.
GroupRdFix contains read-only objects that exist in all controller regardless of the firmware version/type
and configuration.
GroupRdCfg contains read-only objects that depend on the firmware version/type and configuration.
GroupWrFix contains read-write objects that exist in all controller regardless of the firmware version/type
and configuration.

InteliNeo 6000 1.5.0 Global Guide 314


GroupWrCfg contains read-write objects that depend on the firmware version/type and configuration.
GroupW contains write-only objects.
NotificationData group contains objects that are accessible only as bindings of the notification messages.

SMI version
In InteliConfig the MIB table may be exported in two different formats – SMI v1 and SMI v2. The format which
shall be used for export depends on the SNMP Manager and SMI version that it does support.
Typically, SMI v1 is used for SNMP v1 and vice versa, but it is not a rule and SMI v2 may be also used for
SNMP v1.

SNMP reserved objects

Name OID Access Data type Meaning


Writing: command argument
pfActionArgument groupWrFix.24550 read,write Gauge32 Reading: command return
value
pfActionCommand groupW.24551 write Integer32 Command code 1)
pfPassword groupW.24524 write Integer32 Password

1) For list of commands, arguments and description of the procedure of invoking commands see the
description of the MODBUS protocol.

SNMP notifications
Except the request-response communication model, in which the communication is controlled by the
Manager, there are also messages that the Agent sends without any requests. These messages are called
„Notifications“ and inform the Manager about significant events occurred in the Agent.
The controller can send notifications to two different SNMP Managers (two different IP addresses). The
addresses are to be adjusted in the Group: ETH Interface 2 - Untrusted (page 412) by the setpoints SNMP
Traps IP Address 1 (page 427) and SNMP Traps IP Address 2 (page 428). If the Manager address is not
adjusted the particular notification channel is off. The controller will send the notifications in format adjusted
by the setpoint SNMP Trap Format (page 426).
Each notification (kind of event) is identified by an unique identifier (Trap ID in SNMPv1 or Notification OID
in SNMPv2/v3). This unique identifier gives the specific meaning to the notification message, e.g.
Protection 1. level - Fuel Level - alarm activated.
All possible notifications and their identifiers are listed in the MIB table.
The notification message also contains controller name, serial number and textual description of the
event.

Operational events
This events are used for SNMP traps. See the list below:
Start commands
Start button
Remote start

InteliNeo 6000 1.5.0 Global Guide 315


Stop commands
Stop button
Remote stop
Breaker records
Load on Microgrid
Load on Mains
Others
Mains fail
Mains returned

7.2.2 Modbus-RTU, Modbus/TCP


To generate the Modbus register list, click on Generate Cfg Image (MODBUS) button in the Tools ribbon.

Modbus protocol is used for integration of the controller into a building management system or for remote
monitoring via 3rd party monitoring tools.
Modbus-RTU can be used via ⑮ RS 485 (page 47) . The serial speed for Modbus-RTU communication is
adjusted by the setpoint RS485 Modbus Speed (page 394) and the serial mode is adjusted by the
setpoint RS485 Modbus Mode (page 394). Only 1 client can be connected at once through this type of
connection.
Modbus/TCP (Modbus server) can be used with the Ethernet 1 (page 19) / Ethernet 2 (page 19) /
Ethernet 3 (page 19). Up to 3 clients can be connected simultaneously through each Ethernet interface.
The Modbus Server must be activated by the appropriate setpoint Modbus Server related to the
respective Ethernet interface. Timeout after which controller would terminate an inactive connection
(when client is not sending any requests) is set by setpoint ComAp Client Inactivity Timeout (page
679).

Note: Setpoint Modbus Client Inactivity Timeout (page 434) is common for both Ethernet 1 (page
19), Ethernet 2 (page 19) and Ethernet 3 (page 19) interfaces.

DO NOT READ ALARM LIST FROM MORE THAN 1 CLIENT! LOSS OF INFORMATION MAY OCCUR.

Modbus, Modbus/TCP protocol can be used simultaneously with direct Ethernet connection and the SNMP
agent.
Note: Recommended timeout for Modbus client is 300 ms.

IMPORTANT: Do not use setpoints for real-time control from super-ordinate systems. Frequent
repeated writing of setpoints would cause the history file getting overwritten and losing
important records.

InteliNeo 6000 1.5.0 Global Guide 316


IMPORTANT: The InteliNeo6000 is using same MAC address for all Ethernet ports so it is not
possible to use more than one Ethernet port in the same network. If you connect for example
Ethernet 1 and 2 to the same network the communication will breakdown.

In the image below you can see the topology using all 3 Ethernet ports. The ETH1 is used for Modbus Server,
connection of displays (IV5.2), or it can be also used for remote LAN connection. The ETH2 is used for
remote connection using the internet (WAN). The ETH3 is used for Modbus Client which is connected to the
LAN.
In the image below you can see the topology using all 3 Ethernet ports with one Modbus Client. The ETH1 is
used for connection of displays (IV5.2) or it can be also used for remote LAN connection. The ETH2 is used
for remote connection using the internet (WAN). The ETH3 is used for Modbus Server and Client which are
connected to the LAN with Modbus Devices.

Image 6.8 Advanced Ethernet Topology With One Modbus Client

In the image below you can see the topology using all 3 Ethernet ports with multiple Modbus Clients (CU 1 is
the first level client, CU 2 and CU 3 are second level clients). The ETH1 is used for Modbus Server,
connection of displays (IV5.2), or it can be also used for remote LAN connection. The ETH2 is used for
remote connection using the internet (WAN). The ETH3 is used for Modbus Clients which are connected
between CU 1 and other CUs, and between other CUs and Modbus Devices.

InteliNeo 6000 1.5.0 Global Guide 317


Image 6.9 Advanced Ethernet Topology With Multiple Modbus Clients

Note: The IP address of each device in the same network must vary.

Note: InteliVision 5.2 is used for illustrative purposes, the same wiring diagrams apply for all supported displays
mentioned in Displays (page 23).

Address space
The object address space is separated into several areas as described in the table below. The actual
mapping of specific controller data objects to specific Modbus addresses, which depends on configuration,
can be exported into a text file from the appropriate controller archive using InteliConfig. There are several
special registers with fixed meaning (reserved registers) which are listed in a separate table in this chapter.

Modbus MODICON object


Meaning Access Modbus function
address type
0000 .. Binary
Read only Discrete Inputs Read: 01, 02
0999 objects
1000 ..
Values Read only Input Registers Read: 03, 04
2999
3000 .. Read: 03, 04
Setpoints Read/Write Holding Registers
3999 Write: 06, 16
4200 .. Reserved Read/Write, depends on Input Registers Read: 03, 04
7167 registers each specific register Holding Registers Write: 06, 16

InteliNeo 6000 1.5.0 Global Guide 318


Configurable part of the map
The contents of the configurable part of the map is specified in the configuration table. It can be changed by
the customer as well as exported in a human-readable format using the configuration tool.

Discrete inputs
The discrete inputs are read-only objects located in the address range 0-999. The source ComAp objects for
discrete inputs can be:
Single bit of any value of any binary type.
Protection (e.g. 2nd-level protection of the state "xyz"). The input is high if the protection is active
regardless of if it is configured or not.

Input registers
The input registers are read-only numeric values located in the address range 1000-2999. The source
ComAp objects can be:
Any controller value of any data type. The mapping of the particular data type into registers is described in
Mapping data types to registers (page 319).

Holding registers
The holding registers are read-write numeric values located in the address range 3000-3999. The source
ComAp objects can be:
Any controller setpoint of a primitive data type. The mapping of the particular data type into registers is
described in Mapping data types to registers (page 319).
Note: Setpoint must be configured with access level 0 to allow writing it via MODBUS.

Mapping data types to registers


As there are multiple data types in the controller but only one data type in MODBUS (the register, which is 2
byte long), a mapping table is necessary to compose and decompose the MODBUS messages correctly.

Number of
Data type Meaning Data maping
registers
MSB = sign extension
Integer8 1-byte signed integer 1
LSB = value
MSB = 0
Unsigned8 1-byte unsigned integer 1
LSB = value
MSB = value, MSB
Integer16 2-byte signed integer 1
LSB = value, LSB
MSB = value, MSB
Unsigned16 2-byte unsigned integer 1
LSB = value, LSB
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
Integer32 4-byte signed integer 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
Unsigned32 4-byte unsigned integer 2 MSB1 = value, byte 3 (MSB)

InteliNeo 6000 1.5.0 Global Guide 319


Number of
Data type Meaning Data maping
registers
LSB1 = value, byte 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
MSB = 0
Binary8 8-bit binary value 1
LSB = value, bits 0-7
MSB = value, bits 8-15
Binary16 16-bit binary value 1
LSB = value, bits 0-7
MSB1 = value, bits 24-31
LSB1 = value, bits 16-23
Binary32 32-bit binary value 2
MSB2 = value, bits 8-15
LSB2 = value, bits 0-7
MSB = 0
Char 1-byte ASCII character 1
LSB = ASCII value of the character
MSB = 0
StrList Index into a list of strings 1
LSB = index into the list
MSB1 = ASCII value of the 1. character
LSB1 = ASCII value of the 2. character
Zero-terminated string of
ShortStr 8 MSB2 = ASCII value of the 3. character
max 15 ASCII characters.
LSB2 = ASCII value of the 4. character

MSB1 = ASCII value of the 1. character
LSB1 = ASCII value of the 2. character
Zero-terminated string of
LongStr 16 MSB2 = ASCII value of the 3. character
max 31 ASCII characters.
LSB2 = ASCII value of the 4. character

MSB1 = BCD (dd)
LSB1 = BCD (mm)
Date Date (dd-mm-yy) 2
MSB2 = BCD (yy)
LSB2 = 0
MSB1 = BCD (hh)
LSB1 = BCD (mm)
Time Time (hh-mm-ss) 2
MSB2 = BCD (ss)
LSB2 = 0
MSB1 = reserved for future use
LSB1 = reserved for future use
Alarm An item of the Alarmlist 27 MSB2 = Alarm level *)
LSB2 = Alarm status **)
MSB3 = alarm string ***)

InteliNeo 6000 1.5.0 Global Guide 320


Number of
Data type Meaning Data maping
registers
LSB3 = alarm string
MSB4 = alarm string
LSB5 = alarm string

*) 1 .. level 1 (yellow), 2 .. level 2 (red)
**) Bit0 – alarm is active, Bit1 – alarm is confirmed
***) String encoding is UTF-8

Error codes (exception codes)


Exception code is returned by the controller (server) if the query sent from the client could not be completed
successfuly.
The controller responds with the error codes in as follows:
01 – Ilegal function is returned if an incompatible type of operation is applied for a specific object, e.g. if
function 03 is applied to a binary object.
02 – illegal address is returned if the client tries to perform an operation with a object address that is not
related to any existing object or that is located inside an object which is composed by multiple addresses
(registers).
04 – device error is returned in all other errorneous situations. More detailed specification of the problem
can be consequently obtained by reading the registers 4205 – 4206.

Reserved registers
There are several registers with specific meaning. These registers are available in all controllers regardless of
the configuration.

Register Number of
Access Data type Meaning
addresses registers
4200 - 4201 2 read/write Time RTC Time in BCD code
4202 - 4203 2 read/write Date RTC Date in BCD code
Index of the language that is used for
4204 1 read/write Unsigned8 text data provided by Modbus (e.g.
alarmlist messages).
Last application error. To be read after
the device returns the exception code
4205 - 4206 2 read Unsigned32
04. It contains specific information about
the error.
Writing:command argument
4207 - 4208 2 read/write Unsigned32
Reading: command return value
4209 1 write Unsigned16 Command code
4010 1 - - Not implemented
4211 1 write Unsigned16 Password
4212 - 4213 2 read Unsigned32 Communication status

InteliNeo 6000 1.5.0 Global Guide 321


Register Number of
Access Data type Meaning
addresses registers
Reading: Number of items in the
Alarmlist
4214 1 read/write Unsigned8
Writing: Required record format, 0 = text
(default), 1 = binary
4215 - 4241 27 read Alarm 1. record in alarm list
4242 - 4268 27 read Alarm 2. record in alarm list
4269 - 4295 27 read Alarm 3. record in alarm list
4296 - 4322 27 read Alarm 4. record in alarm list
4323 - 4349 27 read Alarm 5. record in alarm list
4350 - 4376 27 read Alarm 6. record in alarm list
4377 - 4403 27 read Alarm 7. record in alarm list
4404 - 4430 27 read Alarm 8. record in alarm list
4431 - 4457 27 read Alarm 9. record in alarm list
4458 - 4484 27 read Alarm 10. record in alarm list
4485 - 4511 27 read Alarm 11. record in alarm list
4512 - 4538 27 read Alarm 12. record in alarm list
4539 - 4565 27 read Alarm 13. record in alarm list
4566 - 4592 27 read Alarm 14. record in alarm list
4593 - 4619 27 read Alarm 15. record in alarm list
4620 - 4646 27 read Alarm 16. record in alarm list
Remote start/Stop: Suplements the set
of starting requests in AUTO mode (e.g.
Remote Start/Stop. Set the coil to log1 to
4700 1 write Bool
start the BESS, set the coil to log0 to
stop the BESS. There are no conditions
in relation to user access settings.
5000 1 read/write Int16 RemoteControl2B 1 (page 938)
5001 1 read/write Int16 RemoteControl2B 2 (page 938)
5002 1 read/write Int16 RemoteControl2B 3 (page 939)
5003 1 read/write Int16 RemoteControl2B 4 (page 939)
5004 1 read/write Int16 RemoteControl2B 5 (page 939)
5005 1 read/write Int16 RemoteControl2B 6 (page 939)
5006 1 read/write Int16 RemoteControl2B 7 (page 940)
5007 1 read/write Int16 RemoteControl2B 8 (page 940)
5100 - 5101 2 read/write Int32 RemoteControl4B 1 (page 940)
5102 - 5103 2 read/write Int32 RemoteControl4B 2 (page 940)
5104 - 5105 2 read/write Int32 RemoteControl4B 3 (page 941)
5106 - 5107 2 read/write Int32 RemoteControl4B 4 (page 941)
5200 1 read/write Binary16 RemoteControlBin (page 941)

InteliNeo 6000 1.5.0 Global Guide 322


Alarmlist reading
An item of the Alarmlist has the following structure:

Byte Value Meaning


MSB 1 0 Always zero for reverse compatibility
0 ComAp Text
1 ComAp Binary
LSB 1
2 ECU Text
3 ECU Binary
0 Undefined
1 Level 1
MSB 2
2 Level 2
3 Sensor fail
0 Inactive
1 Active, Confirmed
LSB 2
2 Inactive, Unconfirmed
3 Active, Unconfirmed
If Alarm format = ComAp Text or ECU Text:

MSB 3 alarm string


LSB 3 alarm string
... ... ...
MSB 27 alarm string
LSB 27 alarm string
If Alarm format = ECU Binary:

MSB 3 FC[3]
error ID (SPN) high word
LSB 3 FC[2]
MSB 4 FC[1]
error ID (SPN) low word
LSB 4 FC[0]
MSB 5 0
LSB 5 FMI failure mode identifier
MSB 6 0
LSB 6 OC occurence
MSB 7 0
LSB 7 SRC_ADDR ECU address
MSB 8 0
LSB 8 SRC_IDX ECU unit index
If Alarm format = ComAp Binary:

InteliNeo 6000 1.5.0 Global Guide 323


Reason Text IDX*
MSB 3 REASON_TEXT_IDX[1]
*configuration-dependent, can be found in
exported data from InteliConfig (CFG
LSB 3 REASON_TEXT_IDX[0]
Image), table "AlarmReasonNames"

List of commands and arguments


IMPORTANT: Only commands configured with access level 0 can be invoked via Modbus.

"Commands" are used to invoke a specific action in the controller via the communication channel. The list of
available actions is in the table below. The general procedure of writing a command via Modbus is as follows:
1. Write the command argument into the registers 44208-44209 (register addresses 4207-4208). Use
function 16.
2. Write the command code into the register 44210 (register address 4209). Use function 6.
3. (Optional) Read the command return value from the registers 44208-44209 (register addresses 4207-
4208). Use function 3.
4. If the command was executed the return value is as listed in the table. If the command was accepted but
there was an error during execution the return value indicates the reason:
a. 0x00000001 – invalid argument
b. 0x00000002 – command refused (e.g. controller not in MAN, breaker can not be closed in the
specific situation etc.)

Command code Action Argument


BESS start* 0x01FE 0000
BESS cmd BESS stop* 0x02FD 0000
0x01 Fault reset* 0x08F7 0000
Horn reset* 0x04FB 0000
BCB toggle* 0x11EE 0000
Breaker cmd
BCB on 0x11EF 0000
0x02
BCB off 0x11F0 0000
MCB toggle* 0x12ED 0000
Breaker cmd
MCB on 0x12EE 0000
0x02
MCB off 0x12EF 0000
OFF Mode 0x0000 0000
Mode cmd
MAN Mode 0x0001 0000
0x03
AUTO Mode 0x0003 0000
Access lock Remove Access lock 0x0010 0000
0x197 Set Access lock 0x0020 0000

InteliNeo 6000 1.5.0 Global Guide 324


User Button 1: Pulse 0x000A 0000
User Button 1: ON/OFF 0x000B 0000
User Button 1: ON 0x000C 0000
User Button 1: OFF 0x000D 0000
User Button 2: Pulse 0x0014 0000
User Button 2: ON/OFF 0x0015 0000
User Button 2: ON 0x0016 0000
User Button 2: OFF 0x0017 0000
User Button 3: Pulse 0x001E 0000
User Button 3: ON/OFF 0x001F 0000
User Button 3: ON 0x0020 0000
User Button 3: OFF 0x0021 0000
User Button 4: Pulse 0x0028 0000
User Button 4: ON/OFF 0x0029 0000
User Button 4: ON 0x002A 0000
User Buttons 1 .. 8 User Button 4: OFF 0x002B 0000
0x0047 User Button 5: Pulse 0x0032 0000
User Button 5: ON/OFF 0x0033 0000
User Button 5: ON 0x0034 0000
User Button 5: OFF 0x0035 0000
User Button 6: Pulse 0x003C 0000
User Butto 6: ON/OFF 0x003D 0000
User Button 6: ON 0x003E 0000
User Button 6: OFF 0x003F 0000
User Button 7: Pulse 0x0046 0000
User Button 7: ON/OFF 0x0047 0000
User Button 7: ON 0x0048 0000
User Button 7: OFF 0x0049 0000
User Button 8: Pulse 0x0050 0000
User Button 8: ON/OFF 0x0051 0000
User Button 8: ON 0x0052 0000
User Button 8: OFF 0x0053 0000

InteliNeo 6000 1.5.0 Global Guide 325


User Button 9: Pulse 0x005A 0000
User Button 9: ON/OFF 0x005B 0000
User Button 9: ON 0x005C 0000
User Button 9: OFF 0x005D 0000
User Button 10: Pulse 0x0064 0000
User Button 10: ON/OFF 0x0065 0000
User Button 10: ON 0x0066 0000
User Button 10: OFF 0x0067 0000
User Button 11: Pulse 0x006E 0000
User Button 11: ON/OFF 0x006F 0000
User Button 11: ON 0x0070 0000
User Button 11: OFF 0x0071 0000
User Button 12: Pulse 0x0078 0000
User Button 12: ON/OFF 0x0079 0000
User Button 12: ON 0x007A 0000
User Buttons 9 .. 16 User Button 12: OFF 0x007B 0000
0x0048 User Button 13: Pulse 0x0082 0000
User Button 13: ON/OFF 0x0083 0000
User Button 13: ON 0x0084 0000
User Button 13: OFF 0x0085 0000
User Button 14: Pulse 0x008C 0000
User Butto 14: ON/OFF 0x008D 0000
User Button 14: ON 0x008E 0000
User Button 14: OFF 0x008F 0000
User Button 15: Pulse 0x0096 0000
User Button 15: ON/OFF 0x0097 0000
User Button 15: ON 0x0098 0000
User Button 15: OFF 0x0099 0000
User Button 16: Pulse 0x00A0 0000
User Button 16: ON/OFF 0x00A1 0000
User Button 16: ON 0x00A2 0000
User Button 16: OFF 0x00A3 0000

InteliNeo 6000 1.5.0 Global Guide 326


User Button 17: Pulse 0x00AA 0000
User Button 17: ON/OFF 0x00AB 0000
User Button 17: ON 0x00AC 0000
User Button 17: OFF 0x00AD 0000
User Button 18: Pulse 0x00B4 0000
User Button 18: ON/OFF 0x00B5 0000
User Button 18: ON 0x00B6 0000
User Button 18: OFF 0x00B7 0000
User Button 19: Pulse 0x00BE 0000
User Button 19: ON/OFF 0x00BF 0000
User Button 19: ON 0x00C0 0000
User Button 19: OFF 0x00C1 0000
User Button 20: Pulse 0x00C8 0000
User Button 20: ON/OFF 0x00C9 0000
User Button 20: ON 0x00CA 0000
User Buttons 17 .. 24 User Button 20: OFF 0x00CB 0000
0x00A8 User Button 21: Pulse 0x00D2 0000
User Button 21: ON/OFF 0x00D3 0000
User Button 21: ON 0x00D4 0000
User Button 21: OFF 0x00D5 0000
User Button 22: Pulse 0x00DC 0000
User Butto 22: ON/OFF 0x00DD 0000
User Button 22: ON 0x00DE 0000
User Button 22: OFF 0x00DF 0000
User Button 23: Pulse 0x00E6 0000
User Button 23: ON/OFF 0x00E7 0000
User Button 23: ON 0x00E8 0000
User Button 23: OFF 0x00E9 0000
User Button 24: Pulse 0x00F0 0000
User Button 24: ON/OFF 0x00F1 0000
User Button 24: ON 0x00F2 0000
User Button 24: OFF 0x00F3 0000

InteliNeo 6000 1.5.0 Global Guide 327


User Button 25 Pulse 0x00FA 0000
User Button 25 ON/OFF 0x00FB 0000
User Button 25 ON 0x00FC 0000
User Button 25 OFF 0x00FD 0000
User Button 26: Pulse 0x0104 0000
User Button 26: ON/OFF 0x010540 0000
User Button 26: ON 0x010640 0000
User Button 26: OFF 0x010740 0000
User Button 27: Pulse 0x0101E 0000
User Button 27: ON/OFF 0x010F 0000
User Button 27: ON 0x0110 0000
User Button 27: OFF 0x0111 0000
User Button 28: Pulse 0x0118 0000
User Button 28: ON/OFF 0x0119 0000
User Button 28: ON 0x011A 0000
Usser Buttons 25 .. 32 User Button 28: OFF 0x011B 0000
0x00A9 User Button 29: Pulse 0x0122 0000
User Button 29: ON/OFF 0x0123 0000
User Button 29: ON 0x0124 0000
User Button 29: OFF 0x0125 0000
User Button 30: Pulse 0x012C 0000
User Butto 30: ON/OFF 0x012D 0000
User Button 30: ON 0x012E 0000
User Button 30: OFF 0x012F 0000
User Button 31: Pulse 0x0136 0000
User Button 31: ON/OFF 0x0137 0000
User Button 31: ON 0x0138 0000
User Button 31: OFF 0x0139 0000
User Button 32: Pulse 0x0140 0000
User Button 32: ON/OFF 0x0141 0000
User Button 32: ON 0x0142 0000
User Button 32: OFF 0x0143 0000

* This action is an equivalent of pressing the front panel button

InteliNeo 6000 1.5.0 Global Guide 328


Modbus RTU examples
Reading of Battery voltage
Export table of values from InteliConfig

Table: Values
Allowed MODBUS functions: 03, 04
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
BatteryVoltag Controller
01036 8213 V Integer 2 1 0 400
e I/O

Request: (Numbers in Hex)


01 03 04 1D 00 01 15 3C
Register
address
Controller address Modbus function Number of registers CRC
041Dhex
1053dec

Response: (Numbers in Hex)


01 03 02 00 F0 B8 00
Length of data Data
Controller address Modbus function 02hex 00F0hex CRC
2 bytes read 240dec

We read value 240 from register 01036. From table of modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is 24.0 V.

InteliNeo 6000 1.5.0 Global Guide 329


Reading Nominal power
Export table of values from InteliConfig

Table: Values
Allowed MODBUS functions: 03, 04
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
Nominal Basic
01228 9018 kW Integer 2 0 0 32767
Power Settings

Request: (Numbers in Hex)


01 03 04 CC 00 01 45 05
Register address
Controller address Modbus function 04CChex Number of registers CRC
1228dec

Response: (Numbers in Hex)


01 03 02 00 C8 B9 D2
Length of data Data
Controller address Modbus function 02hex 00C8hex CRC
2 bytes read 200dec

Read nominal power is 200 kW.

InteliNeo 6000 1.5.0 Global Guide 330


Reading all binary inputs as modbus register

Table: Values
Allowed MODBUS functions: 03, 04
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
Binary Controller
01068 8235 Binary#2 2 0 - -
Inputs I/O

Request: (Numbers in Hex)


01 03 04 2C 00 01 44 F3
Register address
Controller address Modbus function 042Chex Number of registers CRC
1068dec

Response: (Numbers in Hex)


01 03 02 00 12 38 49
Length of data Data
Controller
Modbus function 02hex 0012hex CRC
address
2 bytes read 00010010bin

Binary inputs is 00010010. It means Binary input 2 and binary input 5 are active.
Note: You can use Modbus function 4 instead of 3, rest of data remain same (CRC differs).

InteliNeo 6000 1.5.0 Global Guide 331


Reading specific binary inputs

Table: Binaries
Allowed MODBUS functions: 01, 02
Addresses Source Name of Bit Name
C.O.#
Modbus Addr. = Value Value Bit # Activated by protection Group
State #
Prot. Addr. = State Name of State (s):
00000 Value 8235 Binary Inputs 0 BCB Feedback Controller I/O
00001 Value 8235 Binary Inputs 1 MCB Controller I/O
00002 Value 8235 Binary Inputs 2 BESS Ready To Load Controller I/O

We will read state of BCB Feedback binary input.

Request: (Numbers in Hex)


01 01 00 01 00 01 AC 0A
Register
address
Controller address Modbus function Number of registers CRC
0001hex
0001dec

Response: (Numbers in Hex)


01 01 01 01 90 48
Length of data Data
Controller address Modbus function 01hex 01hex CRC
1 byte read active

The readed data is 01, it means this binary input is active.


Note: You can use Modbus function 2 instead of 1, rest of data remains same (CRC differs).

InteliNeo 6000 1.5.0 Global Guide 332


Starting the BESS
User with access level 0 must have full access for BESS Cmd otherwise the command will not be invoked.

Table Reserved registers (page 321)


Register Number of
Access Data type Meaning
addresses registers
Writing:command argument
4207 - 4208 2 read/write Unsigned32 Reading: command return
value
4209 1 write Unsigned16 Command code

Table List of commands and arguments (page 324)


Action Command code Argument Return value
BESS start 0x01 0x01FE0000 0x000001FF
BESS stop 0x01 0x02FD0000 0x000002FE

Request 1/2: (Numbers in Hex)


01 10 10 6F 00 03 06
Modbus function Register address
Controller address Number of registers Data length in bytes
10hex = 16dec 106Fhex = 4207dec

Request 2/2: (Numbers in Hex)


01 FE 00 00 00 01 68 0B
Argument Command code CRC

Note: Command and argument may be written as one "packet" (function 16) or you can split it and write
argument (function 16) and after that write command code (function 6).

InteliNeo 6000 1.5.0 Global Guide 333


Nominal Power – writing

Table: Setpoints
Allowed MODBUS functions: 03, 04, 06, 16
Register
Com.Obj. Name Dimension Type Len Dec Min Max Group
(s)
Nominal Basic
03008 8276 kW Unsigned 2 0 1 5000
Power Settings

Request: (Numbers in Hex)


01 06 0B C0 00 64 8A 39
Data
Register address
Controller address Modbus function 0064hex = CRC
0BC0hex = 3008dec
100dec

Response: (Numbers in Hex)


01 06 0B C0 00 00 8B D2
Register address
Controller address Modbus function Allways zero CRC
0BC0hex = 3008dec

Writen setpoint nominal power is 100 kW.


CRC calculation
The check field allows the receiver to check the validity of the message. The check field value is the Cyclical
16 15 2
Redundancy Check (CRC) based on the polynomial x +x +x +1. CRC is counted from all message bytes
preceding the check field.
Online CRC calculator: http://www.lammertbies.nl/comm/info/crc-calculation.html Use CRC-16 (Modbus)
Write LSB first.
For writing nominal power 100 kW the CRC is calculated from this data: 01060BC00064hex
6 back to Connection to 3rd party systems

InteliNeo 6000 1.5.0 Global Guide 334


8 Technical data
Power supply
Power supply range 8-36 V DC
Power consumption 16 W
RTC battery Replaceable, type CR1632 3V
Fusing power 8A
Consumption 2.5 A Controller + 10 x 0.5 A BOUTs @ 8 V
Fusing E-STOP 1A
Max. Heat Dissipation 16 W

Operating conditions
Operating temperature -40 °C to +70 °C
Storage temperature -40 ˚C to +80 ˚C
25/55°C, 48hours,95 % non-condensing
Operating humidity (norm 60068-2-30)
(EN 60068-2-30)
Protection degree IP20
5-25 Hz, ± 1.6 mm
Vibration
25-100 Hz, a = 4 g
2
Shocks a = 500 m/s
Surrounding air temperature rating 70 °C.
Suitable for pollution degree 2.

AC Current measurement
3ph BESS current
Measurement inputs
1ph Mains current (Auxiliary current)
Measurement range 1A/5A
Maximum continuous current 2 A / 10 A
Allowed overload 18 A for 15 sec.
Accuracy ±3 mA / ±15 mA for 0.0 to 0.4 A / 0.0 to 2.0 A0.75 % of value for 0.4 to 1.0 A / 2.0 to 5.0 A
Frequency range 40-70 Hz (accuracy 0.002 %)
Input impedance 0.68 MΩ ph-ph , 0.34 MΩ ph-n

AC Voltage measurement
3ph-n BESS voltage
Measurement inputs
3ph-n Mains voltage
115 V ph-N / 200 V ph-ph
suitable also for VTs output
Measurement range
231 V ph-N / 400 V ph-ph
UL, cUL: 346 V ph-N / 600 V ph-ph
Linear measurement and protection
433 V ph-N / 750 V ph-ph
range (maximal voltage)
Accuracy 0.25 %
Frequency range 40-70 Hz (accuracy 0.002 %)
Input impedance 0.72 MΩ ph-ph , 0.36 MΩ ph-n
Upper-harmonics filtering Active Low-Pass filter, Cutoff frequency 3100Hz (-3bB)
Measurement category CAT III, overvoltage category III

E-Stop
Dedicated terminal for safe Emergency Stop input.
Physically disconnects BO 1 & BO 2 from power supply.

InteliNeo 6000 1.5.0 Global Guide 335


Binary inputs
Number 12, non-isolated
Close/Open 0-2 V DC close contact
indication 6-36 V DC open contact
Configurable Pull-up / Pull-down
Pulse input Bin 9 and 10 max. 50 Hz

Binary outputs
Number 12, non-isolated
Max. current 0.5 A
Switching to Positive supply terminal

Analog inputs
Number 4, switchable (R/U/I)
Range R = 0-10000 Ω; U = 0-10 V; I = 0-20 mA
R: 2 % from value for 0-250 Ω
R: 4% from value for 250-2500 Ω
Accuracy R: 6 % from value for 5000-10000 Ω
U: 1% from value ±100 mV
I: 1% from value ±200 uA

Analog output 1
Protection Reinforced isolation
Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
U: 1 % from value ±100 mV
Accuracy
I: 1 % from value ±200 uA

Analog output 2
Protection Basic isolation
Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
U: 1 % from value ±100 mV
Accuracy
I: 1 % from value ±200 uA

Communications
USB Device Basic isolation, USB type B
RS 485 Basic isolation
ETH1
ETH2 10/100 Mbit
ETH3
CAN 1A
CAN 2A Basic isolation, 1000/250/50 kbps
CAN 1B , nominal impedance 120 Ω
CAN 2B

Weight
Controller 750 g
Package 920 g

Controller handles 300 million records into the History, which represents roughly 1 record per second during 9,5 years. Shall be the History recording faster,
the controller lifetime will become smaller.

InteliNeo 6000 1.5.0 Global Guide 336


9 Appendix
9.1 Controller objects 337
9.2 Alarms 1245
9.3 Modules 1350

6 back to Table of contents

9.1 Controller objects


9.1.1 List of controller objects types
9.1.3 Setpoints 338
9.1.4 Values 691
9.1.5 Application Curves 966
9.1.6 Logical binary inputs 985
9.1.7 Logical binary outputs 1048
9.1.8 Logical analog inputs 1111
9.1.9 Fixed Protection States 1179
9.1.10 User Protection States 1188
9.1.11 PLC 1191

InteliNeo 6000 1.5.0 Global Guide 337


9.1.2 Renameable controller objects
It is possible to rename some controller objects in InteliConfig under Controller Configuration -> Others ->
User texts tab. The User texts include communication objects, group names, subgroup names, alarms, etc.
The user can name those objects according his needs.

9.1.3 Setpoints
What setpoints are:
Setpoints are analog, binary or special data objects which are used for adjusting the controller to the specific
environment. Setpoints are organized into groups according to their meaning. Setpoints can be adjusted from
the controller front panel, PC, MODBUS, etc.
All setpoints can be protected by a password against unauthorized changes. Password protection can be
assigned to the setpoints during the configuration procedure.
IMPORTANT: Do not write setpoints repeatedly (e.g. power control from a PLC by repeated
writing of baseload setpoint via Modbus). The setpoints are stored in FRAM memory, which is
14
designed to withstand up to 10 read/write cycles without risk of damage or data loss, but it may
become damaged, when the allowed number of reading/writing cycles is exceeded.

For full list of setpoints go to the chapter List of setpoints (page 340).

List of group of setpoints


Group: Process Control 351
Group: Basic settings 373
Group: Communication Settings 392
Group: Ethernet Port Configuration 403
Group: ETH Interface 1 - Trusted 406

InteliNeo 6000 1.5.0 Global Guide 338


Group: ETH Interface 2 - Untrusted 412
Group: ETH Interface 3 - Modbus 431
Group: BESS settings 434
Group: BESS Protections 446
Group: PV Settings 460
Group: WT Settings 463
Group: Frequency/Load Control 466
Group: Voltage/PF Control 479
Group: Synchronization 485
Group: Power Management 489
Group: Mains Settings 523
Group: Grid Codes 536
Group: BESS Protections 570
Group: Load Shedding 601
Group: User Buttons 612
Group: Scheduler 628
Group: Maintenance Timers 656
Group: Geo-Fencing 662
Group: Plug-In Modules 667
Group: CM-RS232-485 668
Group: CM-4G-GPS 672

InteliNeo 6000 1.5.0 Global Guide 339


List of setpoints

Group: Process Control 351 PVCB Control Mode 370


Subgroup: Application Selector 351 Delay Between Closing Attempts 370
Default Application Select 351 Subgroup: Controller Redundancy 371
Subgroup: Load Control 352 Hot Swap Redundancy 371
Load Control PTM Mode 352 Subgroup: System Variability 372
Load Request Source 353 BESS 372
#System Load Control PTM 354 PV 372
Import Load 355 WT 372
#System Baseload 355 Mains 373
Subgroup: PF/Q Control 356 Gensets 373
PF/Q Control PTM Mode 356 Group: Basic settings 373
PF/Q Request Source 357 Subgroup: Name 373
PF/Q Regulation Type 358 Controller Name 374
#System PF Control PTM 358 Subgroup: Power settings 374
Base Power Factor 359 Samax 374
Import Power Factor 359 Nominal power 375
#System Power Factor 360 Installed Power 375
Base Q 360 Subgroup: Current settings 376
Import Q 361 Nominal Current 376
#System Base Q 361 BESS CT Ratio Prim 376
Subgroup: Neutral Contactor 362 BESS CT Ratio Sec 377
#Neutral Contactor Control 362 Mains/Bus CT Ratio Prim / EFC 377
Subgroup: Process Limitation 362 Mains/Bus CT Ratio Sec / EFC 378
CB Control In MAN Mode 362 3Ph CT Location 378
Subgroup: Mains Import Measurement 364 Subgroup: Voltage settings 378
Mains Measurement P 364 Connection type 378
Mains Measurement Q 365 Evaluated Voltage Protections 379
Subgroup: Peak Shaving 365 BESS Nominal Voltage Ph-N 380
Peak Shaving 365 BESS Nominal Voltage Ph-Ph 380
Peak Shaving Start Level 366 Mains/Bus Nominal Voltage Ph-N 381
Peak Shaving Stop Level 366 Mains/Bus Nominal Voltage Ph-Ph 381
Peak Shaving Start/Stop Delay 367 BESS VT Ratio 381
Subgroup: Breaker Control 367 BESS Voltage Input Range Select 382
MCB Logic 367 Bus 382
MCB Control Mode 368 Bus Voltage Input Range 383
BCB Control Mode 369 Bus Dead Level 383

InteliNeo 6000 1.5.0 Global Guide 340


Subgroup: Phase Rotation 384 User sessions limit 400
Phase Rotation 384 Subgroup: SD Card Settings 401
Subgroup: Frequency settings 384 SD Card File System 401
Nominal Frequency 384 Long Term History 401
Subgroup: Controller settings 385 Subgroup: CAN1 ECU/IO Modules Split 402
Controller Mode 385 CAN1 ECU/IOModules Split 402
Power On Mode 385 Group: Ethernet Port Configuration 403
Fault Reset To Manual 386 Ethernet port 1 403
Horn Timeout 386 Ethernet port 2 404
Fail Safe Binary State 387 Ethernet port 3 405
Run Hours Source 387 Group: ETH Interface 1 - Trusted 406
SW Key 388 Subgroup: TCP/IP Settings 406

User Logging Record 388 IP Address Mode 406

Fuel Genset Consumption 388 IP Address 407

Subgroup: 389 Subnet Mask 407

Battery Undervoltage 389 Gateway IP 408

Battery Overvoltage 389 IP Firewall 408

Battery <> Voltage Delay 389 Subgroup: SNMP Settings 409

Subgroup: Pulse counters 390 SNMP Privacy Protocol 409

Conversion Coeff. Fast Pulse 1 390 SNMP Authentication Protocol 409

Conversion Coeff. Fast Pulse 2 390 SNMP Security Level 409

Conversion Coefficient Pulse 1 391 Subgroup: Modbus Server Settings 410

Conversion Coefficient Pulse 2 391 Modbus Server 410

Group: Communication Settings 392 Modbus Client Inactivity Timeout 410


Subgroup: Controller Address 392 Subgroup: ComAp Client Settings 411
CAN Controller Address 392 Direct Connection Port 411
Universal Genset Address 393 ComAp Client Inactivity Timeout 411
Terminal Comm Address 393 Group: ETH Interface 2 - Untrusted 412
Subgroup: RS485 Settings 394 Subgroup: TCP/IP Settings 412

RS485 Modbus Speed 394 IP Address Mode 412

RS485 Modbus Mode 394 IP Address 413

Subgroup: History Settings 395 Subnet Mask 413

LB/UART Log 395 Gateway IP 414

Subgroup: Intercontroller Settings 396 IP Firewall 414

CAN Intercontroller Comm Redund 396 DNS Mode 415

CAN Intercontroller Comm Mode 397 DNS IP Address 1 415

CAN Intercontroller Empty Check 398 DNS IP Address 2 416

Access Lock Mode 399 Subgroup: AirGate Settings 416

Automatic Access Lock Release 400 AirGate Connection 416


AirGate Address 417

InteliNeo 6000 1.5.0 Global Guide 341


AirGate Port 417 Subgroup: NTP Settings 431
Subgroup: Messages Settings 418 NTP Clock Synchronization 431
Event Message 418 NTP Server 431
Wrn Message 418 Group: ETH Interface 3 - Modbus 431
Al Message 418 Subgroup: TCP/IP Settings 431
Hst Message 419 IP Address Mode 431
ALI Message 419 IP Address 432
AHI Message 419 Subnet Mask 432
Sd Message 420 Gateway IP 433
Sd Override Message 420 Subgroup: Modbus Settings 434
Stp Message 421 Modbus Type 434
MP Message 421 Modbus Client Inactivity Timeout 434
PVBO Message 421 Group: BESS settings 434
E-mail Language 422 Subgroup: Inverter Precharge Settings 434

Subgroup: E-mail Settings 422 BESS Precharge Type 435

E-mail Address 1 422 BESSReady to Load TO 435

E-mail Address 2 422 Subgroup: BESS P Control 436

E-mail Address 3 423 BESS P request source 436

E-mail Address 4 423 BESS Charge Power 436

SMTP User Name 423 BESS Discharge Power 437

SMTP User Password 424 Gen P Min 437

SMTP Server Address 424 Subgroup: BESS Q Control 438

SMTP Sender Address 425 BESS Q request source 438

SMTP Encryption Type 425 Gensets PF Required 438

Subgroup: SNMP Settings 426 Subgroup: SOC Control 439

SNMP Agent 426 SOC High Target 439

SNMP Trap Format 426 SOC High Hysteresis 439

SNMP RD Community String 427 SOC Low Target 440

SNMP WR Community String 427 SOC Low Hysteresis 440

SNMP Traps IP Address 1 427 Subgroup: Battery Cycles 441

SNMP Traps IP Address 2 428 Max Battery Cycles Per Day 441

SNMP Engine User Name 428 Subgroup: Starting Timers 441

Subgroup: Modbus Server Settings 428 Minimal Stabilization Time 441

Modbus Server 428 Maximal Stabilization Time 442

Modbus Client Inactivity Timeout 429 Run Only Block Delay 1 443

Subgroup: ComAp Client Settings 429 Run Only Block Delay 2 444

Direct Connection 429 Run Only Block Delay 3 445

Direct Connection Port 430 Subgroup: Stopping Timers 445

ComAp Client Inactivity Timeout 430 Stop Time 445

InteliNeo 6000 1.5.0 Global Guide 342


Subgroup: Power Switch 446 PV Power Factor Request 460
Power Switch On 446 Subgroup: PV Areas 461
Power Switch Off 446 PV Array Area 1 461
Group: BESS Protections 446 PV Array Area 2 461
Subgroup: Overload Protection 446 PV Array Area 3 461
2POverload Start Evaluation Level 446 PV Array Area 4 462
2POverload Start Evaluation Delay 447 Subgroup: PV Calibration Offset 462
Subgroup: Current Protection 448 PV Calib. Offset 1 462
Short Circuit 448 PV Calib. Offset 2 462
Short Circuit Delay 449 PV Calib. Offset 3 463
IDMT BESS >A Delay 449 PV Calib. Offset 4 463
BESS Current Unbalance 450 Group: WT Settings 463
BESS Current Unbalance Delay 450 Subgroup: PF Control 463
Subgroup: Voltage Protection 451 WT Power Factor Request 463
BESS >V 451 Group: Curtailment 464
BESS >V Delay 452 Subgroup: Curtailment 464
BESS >>V 452 Curtailment 464
BESS >>V Delay 453 Gain 464
BESS <V 453 Int 465
BESS <V Delay 454 Gen P Min 465
BESS V Unbalance 454 Subgroup: PW/WT Ramp 465
BESS V Unbalance Delay 454 PV/WT Ramp Up 465
Subgroup: Frequency Protection 455 PV/WT Ramp Down 466
BESS >f 455 Group: Frequency/Load Control 466
BESS >f Delay 455 Subgroup: Frequency Control 466

BESS <f 456 Frequency Regulator Character 466

BESS <f Delay 456 Frequency Governor Bias 467

Subgroup: Bus Meas Error 457 Frequency Governor Low Limit 467

Bus Meas Error 457 Frequency Governor High Limit 467

Subgroup: Earth Fault Current Protection 457 Tau Frequency Governor Actuator 468

IDMT Earth Fault Current Sd 457 BESS Frequency Droop Slope 468

IDMT Earth Fault Current Delay 458 Subgroup: Regulation Loops 469

Subgroup: SOC Protection 458 Frequency Regulation Loop 469

BESS <f Delay 458 Frequency Gain 469

SOC High Alarm 459 Frequency Int 470

SOC Critical Low 459 Angle Gain 470

SOC Critical High 460 Load Gain 471

Group: PV Settings 460 Load Int 471


Subgroup: PF Control 460 Load Sharing Gain 472
Load Sharing Int 472

InteliNeo 6000 1.5.0 Global Guide 343


Subgroup: Load Transfer 473 Power Management Delay 490
Close Transfer Max Duration 473 #Power Management Mode 491
Open Transfer Min Break 473 Priority 492
Transfer Mains To BESS 474 #Priority Auto Swap 493
Transfer BESS To Mains 475 #System Start Delay 494
Generator Unload BCBOpen Level 476 #System Stop Delay 494
Mains Unload MCB Open Window 476 Subgroup: Dynamic Spinning Reserve 495
Load Ramp 477 Dynamic Spinning Reserve Source 495
Ramp Start Level 478 Dynamic Spinning Reserve 495
Soft Unload Ramp 479 Solar Coverage Ratio 496
Group: Voltage/PF Control 479 Wind Coverage Ratio 496
Subgroup: Voltage Control 479 Subgroup: Load Reserve Set 1 497
Voltage Regulator Character 479 #Starting Load Reserve 1 497
Voltage Regulator Bias 480 #Stopping Load Reserve 1 498
Voltage Regulator Low Limit 480 #Starting Rel Load Reserve 1 499
Voltage Regulator High Limit 480 #Stopping Rel Load Reserve 1 499
Tau Voltage Regulator Actuator 481 Subgroup: Load Reserve Set 2 500
BESS Voltage Droop Slope 481 #Starting Load Reserve 2 500
Subgroup: Regulation Loops 482 #Stopping Load Reserve 2 501
Voltage Gain 482 #Starting Rel Load Reserve 2 502
Voltage Int 482 #Stopping Rel Load Reserve 2 502
PF Gain 483 Subgroup: Load Reserve Set 3 503
PF Int 483 #Starting Load Reserve 3 503
VAr Sharing Gain 484 #Stopping Load Reserve 3 504
VAr Sharing Int 484 #Starting Rel Load Reserve 3 505
Group: Synchronization 485 #Stopping Rel Load Reserve 3 505
Subgroup: Synchronization 485 Subgroup: Load Reserve Set 4 506
Synchronization Type 485 #Starting Load Reserve 4 506
Synchronization Timeout 486 #Stopping Load Reserve 4 507
Voltage Window 486 #Starting Rel Load Reserve 4 508
BESS to Mains/Bus Phase Shift 486 #Stopping Rel Load Reserve 4 508
Phase Window 487 Subgroup: Minimal Running Power 509
Dwell Time 487 #Min Run Power 509
Slip Frequency 488 #Min Run Power 2 509
Slip Frequency Window 488 #Min Run Power 3 510
BCB Latency 488 Subgroup: Start/Stop Timing 510
MCB Latency 489 #Next Engine Start Delay 510
Group: Power Management 489 #Next Engine Stop Delay 511
Subgroup: Power Management Control 489 Subgroup: Slow Stop Protection 511
Power Management 489

InteliNeo 6000 1.5.0 Global Guide 344


#Slow Stop Delay 511 Mains <V Delay 527
Slow Stop Stay In Load Sharing 512 Mains <V Hys 528
Subgroup: Over Load Next Start Protection 513 Mains <<V 528
#Overload Next Start Protection 513 Mains <<V Delay 529
#Overload Next Start Level 513 Mains <<V Hys 529
#Overload Next Start Delay 514 Mains V Unbalance 530
Subgroup: Run Hours Equalization 514 Mains V Unbalance Delay 530
Run Hours Base 514 Subgroup: Mains Frequency Protection 531
#Run Hours Max Difference 515 Mains >f 531
Subgroup: Efficient Mode 515 Mains >f Delay 531
#Power Band Change Up Delay 515 Mains >f Hys 531
#Power Band Change Down Delay 516 Mains >>f 532
Subgroup: Group Settings 516 Mains >>f Delay 532
Control Group 516 Mains >>f Hys 532
Group Link L 517 Mains <f 533
Group Link R 517 Mains <f Delay 533
Group: Loss of Mains Protections 518 Mains <f Hys 533
Subgroup: Loss of Mains Protections 518 Mains <<f 534
Vector Shift Limit 518 Mains <<f Delay 534
ROCOF1 Windows Length 518 Mains <<f Hys 534
ROCOF1 df/dt 519 Subgroup: Mains Fault Timers 535
ROCOF2 Windows Length 519 Mains Stabilization Delay 535
ROCOF2 df/dt 520 MCB Close Delay 535
ROCOF3 Windows Length 520 Group: Grid Codes 536
ROCOF3 df/dt 521 Subgroup: Grid Codes Test 536
ROCOF4 Windows Length 521 Grid Codes Test 536
ROCOF4 df/dt 522 Subgroup: Mains Params/MP Synchronization 536
Vector Shift/ROCOF CB Selector 522 Mains Params/MP Synchronization 536
Group: Mains Settings 523 Mains Synchronization V Max 537
Subgroup: Mains Voltage Protections 523 Mains Synchronization V Min 537
Mains >V 523 Mains Synchronization f Max 538
Mains >V Delay 523 Mains Synchronization f Min 538
Mains >V Hys 524 Mains Synchronization Period 539
Mains >>V 524 After MP Synchronization V Max 539
Mains >>V Delay 525 After MP Synchronization V Min 540
Mains >>V Hys 525 After MP Synchronization f Max 540
Mains 10min Avg >V 526 After MP Synchronization f Min 541
Mains 10min Avg >V Delay 526 After MP Synchronization Period 541
Mains <V 527 Subgroup: After Mains Trip Period 542

InteliNeo 6000 1.5.0 Global Guide 345


After Mains Trip 542 Subgroup: Dynamic Support 561
After Mains Trip Period 542 Dynamic Support 561
After Mains Trip Period Priority 543 Dynamic Support Protection Type 561
After Mains Trip Period Ramp 543 Dynamic Support PF/Q Control 562
Subgroup: Power Over/Under Frequency 544 LVRT Level Severe 562
Power Over/Under Frequency 544 Post VRT Priority 563
Power Over/Under Frequency Delay 544 Post VRT Ramp 563
Return Over/Under Frequency Delay 545 Subgroup: Q Ramp 564
Return Over/Under Frequency Period 545 Q Ramp 564
Return From Over/Under Frequency Priority 546 Q Deadband 564
Return From Over/Under Frequency Ramp 546 Subgroup: Q(Um) 565
Mains Frequency Rise Priority 547 Q(Um) 0 Reference 565
Mains Frequency Rise Ramp 547 Q(Um) Deadband 565
Mains Frequency Fall Priority 548 Subgroup: Qref/Ulim 566
Mains Frequency Fall Ramp 548 Qref/Pnom Shift 566
Subgroup: Load Reduction 549 Qref/Ulim Deadband 566
Load Reduction 549 Subgroup: Q(P) 567
Load Reduction 1 549 Q(P) Deadband 567
Load Reduction 2 550 Subgroup: Soft Unload 567
Load Reduction 3 550 Soft Unload Priority 567
Load Reduction 4 551 Soft Unload Ramp 568
Load Reduction Priority 551 Subgroup: Pave 569
Load Reduction Ramp 552 Pave Protection 569
Subgroup: P(Um) 553 Pave 569
P(Um) 553 Group: BESS Protections 570
P Ramp Filter 554 Subgroup: Overload Protection 570
P(Um) Priority 555 IDMT Overload Protection 570
P(Um) Ramp 555 Subgroup: Current Protection 571
Subgroup: P For Q 556 Short Circuit Protection 571
P For Q Limitation 556 IDMT BESS >A Protection 571
P For Q Deadband 556 BESS Current Unbalance Protection 573
P For Q Priority 557 Subgroup: Voltage Protection 574
P For Q Ramp 557 BESS >V 574
Subgroup: Q&U Protection 558 BESS >>V Protection 575
Q&U Protection 558 BESS <V Protection 576
Q&U < V 559 BESS V Unbalance Protection 576
Q&U < Q 559 Mains >V Protection 577
Q&U Protection Delay 560 Mains >>V Protection 579
Q&U CB Selector 560 Mains 10min Avg >V Protection 580

InteliNeo 6000 1.5.0 Global Guide 346


Mains <V Protection 581 Apparent Power Load Shedding Level 605
Mains <V Protection 582 Apparent Power Load Shedding Delay 605
Mains V Unbalance Protection 583 Apparent Power Load Reconnection Level 606
Subgroup: Frequency Protection 584 Subgroup: Voltage Load Shedding 606
BESS >f Protection 584 Frequency Load Shedding 606
BESS <f Protection 585 Frequency Load Shedding Level 606
Mains >f Protection 586 Voltage Load Shedding Delay 607
Mains >>f Protection 587 Frequency Load Reconnection Level 607
Mains <f Protection 588 Subgroup: Battery SOC Load Shedding 607
Mains <<f Protection 589 Battery SOC Load Shedding 607
Subgroup: Bus Meas Error 590 Battery SOC Load Shedding Level 1
Bus Meas Error 590 Reconnection Level 608

Subgroup: Earth Fault Current Protection 591 Battery SOC Shedding Level 1 609

Earth Fault Current Protection 592 Battery SOC Shedding Level 1 Delay 609

Subgroup: Loss of Mains Protections 593 Battery SOC Shedding Level 2 610

Vector Shift Protection 593 Battery SOC Shedding Level 2 Delay 610

ROCOF1 Protection 594 Battery SOC Shedding Level 3 611

ROCOF2 Protection 595 Battery SOC Shedding Level 3 Delay 611

ROCOF3 Protection 596 Group: User Buttons 612

ROCOF4 Protection 597 Subgroup: User Buttons 612

Subgroup: SOC Protection 598 User Button 1 612

BESS <SOC Protection 598 User Button 2 612

BESS >SOC Protection 598 User Button 3 613

BESS <<SOC Protection 599 User Button 4 613

BESS >>SOC Protection 599 User Button 5 614

BESS SOC Not Configured 600 User Button 6 614

BESS SOC Not Available 600 User Button 7 615


User Button 8 615
Group: Load Shedding 601
Subgroup: Load Shedding 601 User Button 9 616

Load Shedding Active 601 User Button 10 616

Auto Load Reconnection 602 User Button 12 617

Load Reconnection Delay 602 User Button 13 618

Subgroup: Power Load Shedding 603 User Button 14 618

Power Load Shedding 603 User Button 15 619

Power Load Shedding Level 603 User Button 16 619

Power Load Shedding Delay 604 User Button 17 620

Power Load Reconnection Level 604 User Button 18 620

Subgroup: Apparent Load Shedding 605 User Button 19 621

Apparent Power Load Shedding 605 User Button 20 621


User Button 21 622

InteliNeo 6000 1.5.0 Global Guide 347


User Button 22 622 Timer 5 Setup 642
User Button 23 623 Subgroup: Timer 6 643
User Button 24 623 Timer 6 Function 643
User Button 25 624 Timer 6 Setup 644
User Button 26 624 Subgroup: Timer 7 645
User Button 27 625 Timer 7 Function 645
User Button 28 625 Timer 7 Setup 646
User Button 29 626 Subgroup: Timer 8 647
User Button 30 626 Timer 8 Function 647
User Button 31 627 Timer 8 Setup 648
User Button 32 627 Subgroup: Timer 9 649
Group: Scheduler 628 Timer 9 Function 649
Subgroup: Time & Date 628 Timer 9 Setup 650
Time 628 Subgroup: Timer 10 651
Date 628 Timer 10 Function 651
Time Stamp Period 628 Timer 10 Setup 652
Time Zone 629 Subgroup: Timer 11 653
DST Switching Mode 629 Timer 11 Function 653
Time Mode 630 Timer 11 Setup 654
DST Period Rule 630 Subgroup: Timer 12 655
Premortem History Period 631 Timer 12 Function 655
Subgroup: Sunrise/Sunset 631 Timer 12 Setup 656
Sunrise/Sunset Function 631 Group: Maintenance Timers 656
Sunrise/Sunset Latitude 632 Subgroup: Maintenance Timer 1 656
Sunrise/Sunset Longtitude 632 Maintenance Timer 1 RunHours 656
Subgroup: Timer 1 633 Maintenance Timer 1 Interval 657
Timer 1 Function 633 Maintenance Timer 1 Protection 657
Timer 1 Setup 634 Subgroup: Maintenance Timer 2 658
Subgroup: Timer 2 635 Maintenance Timer 2 RunHours 658
Timer 2 Function 635 Maintenance Timer 2 Interval 658
Timer 2 Setup 636 Maintenance Timer 2 Protection 659
Subgroup: Timer 3 637 Subgroup: Maintenance Timer 3 659
Timer 3 Function 637 Maintenance Timer 3 RunHours 659
Timer 3 Setup 638 Maintenance Timer 3 Interval 660
Subgroup: Timer 4 639 Maintenance Timer 3 Protection 660
Timer 4 Function 639 Subgroup: Maintenance Timer 4 661
Timer 4 Setup 640 Maintenance Timer 4 RunHours 661
Subgroup: Timer 5 641 Maintenance Timer 4 Interval 661
Timer 5 Function 641 Maintenance Timer 4 Protection 662

InteliNeo 6000 1.5.0 Global Guide 348


Group: Geo-Fencing 662 Connection Check IP3 675
Subgroup: Geo-Fencing 662 Subgroup: TCP/IP Settings 676
Geo-Fencing 662 DNS Mode 676
Subgroup: Position 663 DNS IP Address 1 676
Home Latitude 663 DNS IP Address 2 677
Home Longitude 663 IP Firewall 677
Subgroup: Fence 1 664 Subgroup: AirGate Settings 678
Fence 1 Protection 664 AirGate Connection 678
Fence 1 Radius 664 AirGate Address 678
Fence 1 Delay 665 Airgate Port 679
Subgroup: Fence 2 665 Subgroup: ComAp Client Settings 679
Fence 2 Protection 665 ComAp Client Inactivity Timeout 679
Fence 2 Radius 666 Direct Connection 680
Fence 2 Delay 666 Direct Connection Port 680
Group: CM-4G-GPS 667 Subgroup: E-mail Settings 681
Subgroup: RTC Synchronization 667 SMTP Server Address 681
Time Zone 667 SMTP Sender Address 681
Group: Plug-In Modules 667 SMTP User Name 682
Subgroup: Slot A 667 SMTP User Password 682
Slot A 667 SMTP Encryption 683
Subgroup: Slot B 667 E-mail Address 1 683
Slot B 667 E-mail Address 4 684
Group: CM-RS232-485 668 E-mail Address 3 684
Subgroup: COM1 Setting 668 E-mail Address 2 684
COM1 Mode 668 Subgroup: Messages Settings 685
COM1 Communication Speed 669 Telephone Number 1 685
COM1 Modbus Mode 669 Telephone Number 2 685
COM1 MODBUS Communication Speed 670 Telephone Number 3 686
Subgroup: COM2 Setting 670 Telephone Number 4 686
COM2 Mode 670 E-mail Language 687
COM2 Communication Speed 670 PVBO Message 687
COM2 Modbus Mode 671 Sd Message 687
COM2 MODBUS Communication Speed 671 Stp Message 688
Group: CM-4G-GPS 672 Wrn Message 688
Subgroup: Cellular Interface 672
Subgroup: GPS Settings 688
Internet Connection 672
GPS Tracking 688
Network Mode 672
Subgroup: RTC Synchronization 689
Access Point Name 672
Time Zone 689
Connection Check IP1 673
NTP Clock Sync 689
Connection Check IP2 674

InteliNeo 6000 1.5.0 Global Guide 349


NTP Server 690
GPS Clock Sync 690
6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 350


Group: Process Control

Subgroup: Application Selector

Default Application Select

Setpoint group Process Control Related FW 1.5.0


Range [units] MPTM / MINT [-]
Default value MINT Force value NO
Step [-]
Comm object 12157 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint selects default controller's application mode while any application LBI is not activated.
Current controller's application mode is stored in value Application Mode (page 885).
IMPORTANT: Controller Mode (page 885) has to be OFF, otherwise controller application
can not be changed.

Single parallel to mains application. The controller controls up to three breakers – a mains
MPTM breaker (MCB), BESS breaker (BCB), and/or PV breaker (PVCB). Feedbacks from all used
breakers are required.
Multiple island-parallel application without mains and multiple parallel application with mains.
MINT The controller controls up to two breakers – a BESS breaker and/or PV breaker. For parallel
to mains operation also mains breaker feedback is required.

Note: For more information about Applications, see chapter Applications overview (page 40).

Note: The controller also controls the NCB, check the chapter Breaker Control (page 126) for more
information about breakers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 351


Subgroup: Load Control

Load Control PTM Mode

Setpoint group Process Control Related FW 1.5.0


Range [units] Baseload / Imp / Exp [-]
Default value Baseload Force value YES
Step [-]
Comm object 8638 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the type of load control.

BESS produces amount of the power. Source or requested power is given by


setpoint Load Request Source (page 353) The rest of power is supplied from the
Mains or exported to the Mains. Even in baseload control mode can be the
Import/Export limited. This function can be activated by setpoint Import/Export
Limitation (page 1) = Enabled. Then the request for the power of the BESS
operating in baseload can be limited to prevent the Import/Export go below the
limit given by setpoint Import Load (page 355).
Example: Baseload = 1000 kW, load = 700 kW, Import load = 100. Then
Baseload
the Baseload request will be limited to 600 kW to prevent the Import power
go below 100 kW

Example: Baseload = 1000 kW, load = 700 kW, Import load = -100. Then
the Baseload request will be limited to 800 kW to prevent the Import power
go below -100 kW (actually it is limitation of the export).

The load of the BESS is controlled to keep constant level of base load of the whole
system. The level is adjusted by the setpoint #System Baseload (page 355).
BESS produces the certain amount of power to keep constant import/export from
Imp/Exp the Mains regardless the demand of the load. The source of requested
import/export is given by setpoint Load Request Source (page 353).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 352


Load Request Source

Setpoint group Process Control Related FW 1.5.0


Range [units] Setpoint / Analog External Value [-]
Default value Setpoint Force value YES
Step [-]
Comm object 20727 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts source type of requested load control.
Application Mode (page 885) = MPTM

Load Control PTM


Load Request Source Source
Mode (page 352)
BESS Charge Power (page
Baseload
Setpoint 436)/BESS Discharge Power (page 437)
Imp/Exp Import Load (page 355)
LOAD CONTROL: ANEXT BASELOAD (PAGE
Baseload
1121)
Analog External Value
LOAD CONTROL: ANEXT IMP/EXP LOAD
Imp/Exp
(PAGE 1122)
See Load control (page 264)Load control (page 261) for more information.
Application Mode (page 885) = MINT

Load Request Source Source


Setpoint #System Baseload (page 355)
Analog External Value LOAD CONTROL: ANEXT BASELOAD (PAGE 1121)
See Load control (page 261) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 353


#System Load Control PTM

Setpoint group Process Control Related FW 1.5.0


Range [units] Baseload / Load Shar [-]
Default value Baseload Force value NO
Step [-]
Comm object 8774 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Load control mode in parallel to Mains operation of the whole controller group.

The total power of the group is controlled to constant level given by the setpoint
#System Baseload (page 355). Each loaded unit takes equal part (relative to
their nominal power) from this requested value. The load is regulated locally in
Baseload
each controller by Load control regulation loop, load-sharing is not active. The
setpoint #System Baseload (page 355) is also used for determining which unit
have to run or not.
The load is controlled by the supervisor (IM1010) controller to share the total load
(given by the setpoint #System Baseload (page 355)) with other loaded units in
Load Shar
such a way, that all loaded units will be loaded at the same level (relative to their
nominal power). Load-sharing regulation loop is active.

Note: The Load Shar mode shall be used in case the supervisor (IM1010) controller is present in the
system. In systems without the supervisor (IM1010) controller the setpoint must be setup to the
Baseload option.

Note: The power factor (PF) is regulated to constant level given by the setpoint #System PF
Control PTM (page 358) in parallel to Mains operation and does not depend on active load control
mode.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 354


Import Load

Setpoint group Process Control Related FW 1.5.0


-32 000 .. 32 000 [kW] (depends on the selected Power Formats And Units (page
Range [units]
196))
0 kW (depends on the selected
Default value Power Formats And Units (page Force value NO
196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8641 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Defines actual imported (exported) active power in parallel to Mains operations in Import/Export mode or
the minimal imported (maximal exported) active power from the Mains in Baseload with I/E Limit mode.
The value from this Setpoint is used if:
Setpoint Load Control PTM Mode (page 352) = Import/Export or
Setpoint Load Control PTM Mode (page 352) = Baseload and Import/Export Limitation (page
1) = Enabled.
Note: If the value of the setpoint is >0 the power is imported from the Mains, if the setpoint value is
<0, then the power is exported to the Mains.

6 back to List of setpoints

#System Baseload

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 32 000 [kW] (depends on the selected Power Formats And Units (page 196))
1 000 kW (depends on the selected Power
Default value Force value NO
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8775 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Required total active power of the controller group in parallel to Mains operation in Baseload mode.
The value from this Setpoint is used if:
Setpoint #System Load Control PTM (page 354) = Baseload
See chapter Load control (page 261) for more information.
Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 355


Subgroup: PF/Q Control

PF/Q Control PTM Mode

Setpoint group Process Control Related FW 1.5.0


Range [units] PF Control / PF(Pm) / Q Control / Q(Um) / Q(P) / Qref / Ulim [-]
Default value PF Control Force value NO
Step [-]
Comm object 10120 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjust the type of PF/Q control.

The BESS Power Factor (page 710) is controlled according to preset required
PF Control
value. See PF Control (page 266)PF/Q control (page 262) for more information.
Grid Codes specific functionality where the power factor depends on the actual
PF(Pm) power of the BESS. See PF(Pm) (page 267)PF/Q control (page 262) for more
information.
The BESS Q (page 708) is controlled according to preset required value. See PF
Q Control
Control (page 266)PF/Q control (page 262) for more information.
Grid Codes specific functionality where the BESS Required Q (page 865) depends
on the mains voltage (Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage
Q(Um)
L2-N (page 839) and Mains/Bus Voltage L3-N (page 840)). See Q(Um) (page
268)PF/Q control (page 262) for more information.
Grid Codes specific functionality where the BESS Required Q (page 865) depends
Q(P) on the BESS P (page 707). See Q(P) (page 269)PF/Q control (page 262) for
more information.
Grid Codes specific functionality where the BESS Required Q (page 865) depends
on the mains voltage (Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage
Qref/Ulim L2-N (page 839) and Mains/Bus Voltage L3-N (page 840)) with a modified
behavior. See Qref/Ulim (page 270)PF/Q control (page 262) for more
information.

Actual selected control mode is available in System PF/Q Control (page 864).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 356


PF/Q Request Source

Setpoint group Process Control Related FW 1.5.0


Range [units] Setpoint / Analog External Value [-]
Default value Setpoint Force value YES
Step [-]
Comm object 16130 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjust the source type requested of PF/Q control.
Application Mode (page 885) = MPTM

PF/Q
PF/Q Regulation Type PF/Q Control PTM
Request Source
(page 358) Mode (page 356)
Source
Base Power Factor (page
PF Control
Base PF/ Q Control 359)
Q Control Base Q (page 360)
Setpoint
Import Power Factor (page
PF Control
Imp/Exp PF/ Q Control 359)
Q Control Import Q (page 361)
PF CONTROL: ANEXT BASE
PF Control
PF (PAGE 1124)
Base PF/ Q Control
Q CONTROL: ANEXT BASE Q
Q Control
Analog (PAGE 1147)
External Value PF CONTROL: ANEXT
PF Control
IMP/EXP PF (PAGE 1125)
Imp/Exp PF/ Q Control
Q CONTROL: ANEXT IMP/EXP
Q Control
Q (PAGE 1147)
See PF Control (page 266)PF/Q control (page 262) for more information.
Application Mode (page 885) = MINT

PF/Q
#System PF Control
Request Source
PTM (page 358)
Source
Base PF #System Power Factor (page 360)
Setpoint
Base Q #System Base Q (page 361)
Analog Base PF PF CONTROL: ANEXT BASE PF (PAGE 1124)
External Value Base Q Q CONTROL: ANEXT BASE Q (PAGE 1147)
See PF/Q control (page 262) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 357


PF/Q Regulation Type

Setpoint group Process Control Related FW 1.5.0


Range [units] Base PF/Q Control / Import/Export PF/Q Control [-]
Default value Base PF/Q Control Force value YES
Step [-]
Comm object 16131 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjust the regulation type of PF/Q control.

BESS produces requested amount of the power, i.e. Mains Import/Export is


Base PF/Q adjusted so BESS produces exactly requested power. See PF Control (page
Control 266)PF/Q control (page 262) for more information.

Mains Import/Export is exactly as requested, i.e. BESS power is adjusted to


Import/Export
fulfill Import/Export requirements. See PF Control (page 266)PF/Q control
PF/Q Control
(page 262) for more information.

6 back to List of setpoints

#System PF Control PTM

Setpoint group Process Control Related FW 1.5.0


Range [units] Base PF / Base Q / Var Shar [-]
Default value Base PF Force value NO
Step [-]
Comm object 8779 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Power factor control mode in parallel to Mains operation of the whole controller group.

PF of the BESS is controlled by their PF control loops to provide constant system


Base PF
power factor adjusted by setpoint #System Power Factor (page 360).
Var Shar PF of the BESS (reactive power) is controlled through the VAr sharing line.
Reactive power of the BESS is controlled by their Q control loops to provide
Base Q constant BESSs reactive power adjusted by setpoint #System Base Q (page
361).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 358


Base Power Factor

Setpoint group Process Control Related FW 1.5.0


Range [units] 0,001 .. 1,999 [-]
Default value 1 [-] Force value YES
Step 0,001 [-]
Comm object 8640 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Required BESS power factor when the BESS is running in parallel to the mains in PF Control BASE
mode.
The value from this Setpoint is used if:
Setpoint PF/Q Regulation Type (page 358) = Base PF/Q Control and
Setpoint PF/Q Control PTM Mode (page 356) = PF Control.
See chapter PF Control (page 266) for more information.

6 back to List of setpoints

Import Power Factor

Setpoint group Process Control Related FW 1.5.0


Range [units] 0,001 .. 1,999 [-]
Default value 1 [-] Force value NO
Step 0,001 [-]
Comm object 8642 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Defines required power factor in parallel to Mains operation in PF Control IMP/EXP mode.
The value from this Setpoint is used if:
Setpoint PF/Q Regulation Type (page 358) = Import/Export PF/Q Control and
Setpoint PF/Q Control PTM Mode (page 356) = PF Control.
See chapter PF Control (page 266)PF/Q control (page 262) for more information.
Note: If the setpoint value is >1 the Mains Load Character is C, if the setpoint value is <0 the Mains
Load Character is L.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 359


#System Power Factor

Setpoint group Process Control Related FW 1.5.0


Range [units] 0,60 .. 1,20 [-]
Default value 1,00 [-] Force value NO
Step 0,01 [-]
Comm object 8776 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Required total power factor of the controller group in parallel to Mains operation in PF Control BASE
mode.
The value from this Setpoint is used if:
Setpoint #System PF Control PTM (page 358) = Base PF

Note: If the setpoint value is >1 the BESS Load Character is C, if the setpoint value is <0 the BESS
Load Character is L.

Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.

6 back to List of setpoints

Base Q

Setpoint group Process Control Related FW 1.5.0


-32 000 .. 32 000 [kVAr] (depends on the selected Power Formats And Units
Range [units]
(page 196))
0 kVAr (depends on the selected Power
Default value Force value YES
Formats And Units (page 196))
Step 1 kVAr (depends on the selected Power Formats And Units (page 196))
Comm object 13026 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Required Gen-set reactive power in parallel to mains operation in Q Control BASE mode.
The value from this Setpoint is used if:
Setpoint PF/Q Regulation Type (page 358) = Base PF/Q Control and
Setpoint PF/Q Control PTM Mode (page 356) = Q Control.
See chapter Q Control (page 267) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 360


Import Q

Setpoint group Process Control Related FW 1.5.0


-32000 .. 32000 [kVAr]
Range [units]
(depends on the selected Power Formats And Units (page 196))
Default value 0 kVAr Force value NO
Step 1 kVAr (depends on the selected Power Formats And Units (page 196))
Comm object 14143 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Defines actual imported (exported) reactive power in parallel to Mains operations in Q Control IMP/EXP
Mode.
The value from this Setpoint is used if:
Setpoint PF/Q Regulation Type (page 358) = Import/Export PF/Q Control and
Setpoint PF/Q Control PTM Mode (page 356) = Q Control.
See chapter Q Control (page 267)PF/Q control (page 262) for more information.
Note: If the value of the setpoint is >0 the power is imported from the Mains, if the setpoint value is
<0, then the power is exported to the Mains.

6 back to List of setpoints

#System Base Q

Setpoint group Process Control Related FW 1.5.0


-32 000 .. 32 000 [kVAr] (depends on the selected Power Formats And Units
Range [units]
(page 196))
0 kVAr (depends on the selected Power
Default value Force value NO
Formats And Units (page 196))
Step 1 kVAr (depends on the selected Power Formats And Units (page 196))
Comm object 16407 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Required total reactive power of the controller group in parallel to Mains operation in Q Control BASE
mode.
The value from this Setpoint is used if:
Setpoint #System PF Control PTM (page 358) = Base Q

Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 361


Subgroup: Neutral Contactor

#Neutral Contactor Control

Setpoint group Process Control Related FW 1.5.0


Range [units] Each / Common [-]
Default value Each Force value NO
Step [-]
Comm object 9890 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint changes the behavior of binary output NCB CLOSE/OPEN (PAGE 1094) which is used for
neutral contactor control.
See more information in the chapter Neutral Contactor Breaker (page 129).
The EACH option should be used if each Gen-set and BESS has its own neutral contactor. The
NCB CLOSE/OPEN (PAGE 1094) output on each Gen-set and BESS is given by an internal
algorithm, which ensures, that always exactly one Gen-set or BESS connected to the bus with the
lowest CAN address has the neutral contactor closed.
The COMMON option should be used if there is only one common neutral contactor for the whole
site. The NCB CLOSE/OPEN (PAGE 1094) outputs from all controllers are combined together and
the combined signal is used to control the breaker. If at least one Gen-set or BESS in the site is
running and has a proper voltage, the neutral contactor is closed.
Note: LBI NCB FEEDBACK (PAGE 1015) and LBO NCB CLOSE/OPEN (PAGE 1094) has to be
configured for proper functionality.

Note: This setpoint is available only for the MINT application, in case of the MPTM application the
NCB automatically behaves like this setpoint is set to COMMON option.

Note: The # setpoints are shared with all controllers on site via intercontroller CAN line.

6 back to List of setpoints

Subgroup: Process Limitation

CB Control In MAN Mode

Setpoint group Process Control Related FW 1.5.0


Range [units] Full Ctrl / Aut Trans / Islnd Disl [-]
Default value Aut Trans Force value YES
Step [-]
Comm object 14962 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
The behavior of transition of load in MAN mode is adjusted via this setpoint.

InteliNeo 6000 1.5.0 Global Guide 362


No limitation of CB control in MAN mode (operator can close any breaker
Full Ctrl manually or evoke the synchronization and consequential operation in parallel to
Mains)
Operator can control both MCB or BCB breaker. However once transition is
evoked the controller performs the automatic transfer of the load (depends on
adjustment of setpoints Transfer BESS To Mains (page 475) and Transfer
Mains To BESS (page 474)).
Controller performs synchronization across MCB, if BCB is closed and MCB
button is pushed. Load transfer is done after synchronization and BCB is opened
automatically.
Controller performs synchronization across BCB , if MCB is closed and BCB
button is pushed. Load transfer is done after synchronization and MCB is opened
Aut Trans automatically.
It is also possible to open currently closed breaker and keep the load non-
energized. Then it is possible to close MCB or BCB to energize the load from a
healthy source.
Note: Parallel operation with Mains continues, if system already operates in
parallel with Mains and setting is changed to Aut Trans. It is necessary to push
MCB or BCB button to open a breaker.

Note: Open transfer is performed, if the Open option is selected with Transfer
BESS To Mains (page 475) or Transfer Mains To BESS (page 474)
Behaves like the full manual control but the Island operation is disabled.
Example: When MCB is opened and BCB is pressed, controller does not
Islnd Disl go to island.

Example: In parallel operation when MCB button is pressed, MCB is not


opened.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 363


Subgroup: Mains Import Measurement

Mains Measurement P

Setpoint group Process Control Related FW 1.5.0


Range [units] None / Mains CT / Analog Input [-]
Default value None Force value NO
Step [-]
Comm object 10599 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Defines source value of the Mains Import P (page 842).

The value Mains Import P (page 842) is not measured. The duration of the load
None transfer in direction Mains to BESS is given exactly by the setpoint Close
Transfer Max Duration (page 473).
The value Mains Import P (page 842) is measured via Mains CT which is located
Mains CT on phase L1. The load transfer in direction Mains to BESS is considered to be
finished when the Mains is unloaded under certain level.
The value Mains Import P (page 842) is measured via analog input, accordingly
Analog
LAI: MAINS MEASUREMENT P (PAGE 1124). The load transfer in direction Mains to
Input
BESS is considered to be finished when the Mains is unloaded under certain level.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 364


Mains Measurement Q

Setpoint group Process Control Related FW 1.5.0


Range [units] None / Mains CT / Analog Input [-]
Default value None Force value NO
Step [-]
Comm object 10598 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Defines source value of the Mains Import Q (page 843).

The value Mains Import Q (page 843) is not measured. The duration of the load
None transfer in direction Mains to BESS is given exactly by the setpoint Close
Transfer Max Duration (page 473).
The value Mains Import Q (page 843) is measured via Mains CT which is located
Mains CT on phase L1. The load transfer in direction Mains to BESS is considered to be
finished when the Mains is unloaded under certain level.
The value Mains Import Q (page 843) is measured via analog input, accordingly
Analog
LAI: MAINS MEASUREMENT Q (PAGE 1124). The load transfer in direction Mains to
Input
BESS is considered to be finished when the Mains is unloaded under certain level.

6 back to List of setpoints

Subgroup: Peak Shaving

Peak Shaving

Setpoint group Process Control Related FW 1.5.0


Range [units] Enabled / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 11601 Related applications SPTM​
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables peak shaving function.

The Peak shaving (page 1) function is active and its behaviour is set by setpoints
Enabled Peak Shaving Start Level (page 366), Peak Shaving Stop Level (page 366)
and Peak Shaving Start/Stop Delay (page 367).
The Peak shaving (page 1) function is BLOCKED and the start command can not
Disabled
be activated even the conditions for Peaks Shaving activation were fulfilled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 365


Peak Shaving Start Level

Setpoint group Process Control Related FW 1.5.0


Peak Shaving Stop Level (page 366) .. 32000 [kW]
Range [units]
(depends on the selected Power Formats And Units (page 196))
1000 kW (depends on the selected Power
Default value Force value YES
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8643 Related applications SPTM​
Config level Advanced
Only if Application Mode (page 885) = MPTM and Peak Shaving (page 365) =
Setpoint visibility
Enabled
Description
This setpoint starts BESS, when the value of the load consumption Load P (page 828) exceeds the
value given by this setpoint for the time of Peak Shaving Start/Stop Delay (page 367).
The BESS is synchronized to the Mains (kept in the parallel to the Mains) and the BESS power is
controlled according to the settings in the Groups Process Control and Speed/Load Control.
The BESS stays running until the conditions for Peak Shaving run are active. Conditions of deactivation
are given by the setpoint Peak Shaving Stop Level (page 366) and Peak Shaving Start/Stop Delay
(page 367).

6 back to List of setpoints

Peak Shaving Stop Level

Setpoint group Process Control Related FW 1.5.0


0 .. Peak Shaving Start Level (page 366) [kW]
Range [units]
(depends on the selected Power Formats And Units (page 196))
900 kW (depends on the selected Power
Default value Force value YES
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8644 Related applications SPTM​
Config level Advanced
Only if Application Mode (page 885) = MPTM and Peak Shaving (page 365) =
Setpoint visibility
Enabled
Description
This setpoint stops BESS, of the load consumption Load P (page 828) decreases under the value given
by this setpoint for the time of Peak Shaving Start/Stop Delay (page 367).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 366


Peak Shaving Start/Stop Delay

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 600 [s]
Default value 600 s Force value YES
Step 1s
Comm object 9989 Related applications SPTM​
Config level Advanced
Only if Application Mode (page 885) = MPTM and Peak Shaving (page 365) =
Setpoint visibility
Enabled
Description
Defines the delay of activation or deactivation of the Peak shaving (page 1).

The value of the load consumption Load P (page 828) exceeds the value given
Starts when
by the setpoint Peak Shaving Start Level (page 366).
The value of the load consumption Load P (page 828) decreases under the
Stop when
value given by the setpoint Peak Shaving Stop Level (page 366)

6 back to List of setpoints

Subgroup: Breaker Control

MCB Logic

Setpoint group Mains Settings Related FW 1.5.0


Range [units] Close-On / Close-Off [-]
Default value Close-Off Force value YES
Step [-]
Comm object 8444 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the behavior of LBO MCB CLOSE/OPEN (PAGE 1090) and LBI MCB FEEDBACK
(PAGE 1012).

When LBO MCB CLOSE/OPEN (PAGE 1090) is closed – LBI MCB


Close On
FEEDBACK (PAGE 1012) should be closed.
When LBO MCB CLOSE/OPEN (PAGE 1090) is closed – LBI MCB
Close Off
FEEDBACK (PAGE 1012) should be opened.

InteliNeo 6000 1.5.0 Global Guide 367


Image 7.1 Close-On

Image 7.2 Close-Off

Note: LBO MCB CLOSE/OPEN (PAGE 1090) as well as this setpoint is used only for contactors.

6 back to List of setpoints

MCB Control Mode

Setpoint group Process Control Related FW 1.5.0


Range [units] Internal / External [-]
Default value Internal Force value YES
Step [-]
Comm object 9873 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts control mode of MCB.

The MCB breaker is controlled by controller.


The controller accepts the opening of MCB from the external device (Mains
relay). When the MCB is opened externally then:
The event "MCB opened Externally" is recorded in history log
Internal
Controller starts to count down the MCB Close Delay and is going to be
closed to the MCB once it elapses.
Incorrect reaction of the MCB FEEDBACK (PAGE 1012) to internal MCB
Close/Open command causes Wrn MCB Fail (page 1254)

InteliNeo 6000 1.5.0 Global Guide 368


Controller does not control the MCB at all. The MCB is controlled externally,
when the MCB FEEDBACK (PAGE 1012) gets changed, then the event "MCB
Opened" or "MCB Closed" is recorded to the history log.
Controller always accepts the MCB FEEDBACK (PAGE 1012) without of issuing
External any alarm.
The controller informs the superordinate system about the status of the breaker
automaton using the signals
LBO FORWARD SYNCHRONIZATION (PAGE 1080)
LBO REVERSE SYNCHRONIZATION (PAGE 1105)

6 back to List of setpoints

BCB Control Mode

Setpoint group Process Control Related FW 1.5.0


Range [units] Internal / Follow / External [-]
Default value Internal Force value YES
Step [-]
Comm object 11771 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts control mode of BCB.

The breaker is controlled only from controller. Any unexpected change of BCB
FEEDBACK (PAGE 991) causes Stp BCB Fail (page 1290) immediately.
Internal
Incorrect reaction of the BCB FEEDBACK (PAGE 991) on internal BCB
Close/Open command causes Stp BCB Fail (page 1290)
BCB Openning BCB FEEDBACK (PAGE 991) = 0 is accepted from external
devices with history record "BCB Opened Externally".
Follow
Incorrect reaction of the BCB FEEDBACK (PAGE 991) to internal BCB
Close/Open command causes Stp BCB Fail (page 1290)
Controller does not control the BCB is controlled externally, when the BCB
FEEDBACK (PAGE 991) get changed, then the event "BCB Opened" or "BCB
Closed" is recorded to the history log.
Controller always accept the BCB FEEDBACK (PAGE 991) without of issuing
External any alarm.
When the Sd protection shuts down the BESS, the BCB stays closed. BCB
stays closed until it is opened externally.
IMPORTANT: BESS with closed BCB is not blocked against starting.

IMPORTANT: Anytime when the controller is synchronizing via BCB the External BCB
closing is being accepted in all BCB control modes.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 369


PVCB Control Mode

Setpoint group Process Control Related FW 1.5.0


Range [units] Internal / External [-]
Default value Internal Force value YES
Step [-]
Comm object 19451 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = PVCB
Description
This setpoint allows you to manage the circuit breaker in your PV system in three different ways: Internal,
Follow, and Not Installed.

The controller takes full control of the PV Circuit Breaker (PVCB), using its built-in
Internal
settings and logic. It doesn't listen to external commands; it operates by itself.
The controller still manages the PVCB, just like in "Internal" mode. However, it can
Follow
also listen to external command for opening the circuit breaker.
Not The PV Circuit Breaker isn't part of your system. In this case, the controller runs
Installed your PV system on its own, as if the PVCB doesn't exist.

6 back to List of setpoints

Delay Between Closing Attempts

Setpoint group Process Control Related FW 1.5.0


Range [units] 20 .. 60 [s]
Default value 20 [s] Force value NO
Step 1 [s]
Comm object 19883 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the delay between breaker closing attempts the controller performs when a breaker
is requested to be closed. Delay is one second longer than you set here due breaker's safety.
Example: If this setpoint is set to 10 seconds, the delay between another attempt to close the
breaker will be 11 seconds.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 370


Subgroup: Controller Redundancy

Hot Swap Redundancy

Setpoint group Process Control Related FW 1.5.0


Disabled / Master / Backup / Master + Modules Redundancy / Backup + Modules
Range [units]
Redundancy [-]
Default value Disabled Force value YES
Step -
Comm object 16716 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of Hot Swap Redundancy (page 160) function.

Disabled The Hot Swap Redundancy function is disabled.


The controller is expected to be used as Master controller in the hot swap
Master
function. One set of CAN modules for a Master-Backup pair is used.
The controller is expected to be used as Backup controller (redundant
Backup controller) in the hot swap function. One set of CAN modules for a Master-
Backup pair is used.
The controller is expected to be used as Master controller in the hot swap
Master + Modules
function. Separate set of CAN modules is used for each controller in a
Redundancy
Master-Backup pair.
The controller is expected to be used as Backup controller (redundant
Backup + Modules
controller) in the hot swap function. Separate set of CAN modules is used
Redundancy
for each controller in a Master-Backup pair.

Note: Hot Swap Redundancy function can be enabled only if you have correct SW Key (page 388).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 371


Subgroup: System Variability

BESS

Setpoint group Process Control Related FW 1.5.0


Range [units] Installed / Not Installed
Default value Installed Force value NO
Step [-]
Comm object 15918 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the topology of the Microgrid system. If the BESS is included in the system this
setpoint should be set to Installed. The visibility of the setpoints and values related to the BESS is
dependent on this setpoint.

6 back to List of setpoints

PV

Setpoint group Process Control Related FW 1.5.0


Range [units] Installed / Not Installed
Default value Installed Force value NO
Step [-]
Comm object 15916 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the topology of the Microgrid system. If the PV or any other renewable source is
included in the system this setpoint should be set to Installed. The visibility of the setpoints and values
related to the PV is dependent on this setpoint.

6 back to List of setpoints

WT

Setpoint group Process Control Related FW 1.5.0


Range [units] Installed / Not Installed
Default value Installed Force value NO
Step [-]
Comm object 19723 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the topology of the Microgrid system. If the WT or any other renewable source is

InteliNeo 6000 1.5.0 Global Guide 372


included in the system this setpoint should be set to Installed. The visibility of the setpoints and values
related to the WT is dependent on this setpoint.

6 back to List of setpoints

Mains

Setpoint group Process Control Related FW 1.5.0


Range [units] Installed / Not Installed
Default value Installed Force value NO
Step [-]
Comm object 15915 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the topology of the Microgrid system. If the Mains is included in the system this
setpoint should be set to Installed. The visibility of the setpoints and values related to the Mains is
dependent on this setpoint.

6 back to List of setpoints

Gensets

Setpoint group Process Control Related FW 1.5.0


Range [units] Installed / Not Installed
Default value Installed Force value NO
Step [-]
Comm object 20231 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the topology of the Microgrid system. If the Gen-sets are included in the system this
setpoint should be set to Installed. The visibility of the setpoints and values related to the Gen-sets is
dependent on this setpoint.

6 back to List of setpoints

Group: Basic settings

Subgroup: Name

InteliNeo 6000 1.5.0 Global Guide 373


Controller Name

Setpoint group Basic settings Related FW 1.5.0


Range [units] 0 .. 15 characters [-]
Default value InteliNeo6000 Force value NO
Step [-]
Comm object 8637 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
User defined name, used for the controller identification at remote phone or mobile connection.
Controller Name is maximally 15 characters long and can be entered using InteliConfig or from
controller’s configuration menu.

6 back to List of setpoints

Subgroup: Power settings

Samax

Setpoint group Basic settings Related FW 1.5.0


OFF; 0 .. 32000 [kVA] (depends on the selected Power Formats And Units (page
Range [units]
196))
200 kVA (depends on the selected
Default value Power Formats And Units (page Force value YES
196))
Step 1 kVA (depends on the selected Power Formats And Units (page 196))
Comm object 13208 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Maximal apparent power of the BESS.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 374


Nominal power

Setpoint group Basic settings Related FW 1.5.0


Range [units] 1 .. 32 000 [kW] (depends on the selected Power Formats And Units (page 196))
200 kW (depends on the selected Power
Default value Force value YES
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
MINT,
Comm object 8276 Related applications
MPTM
Config level Standard
Setpoint visibility Always
Description
Nominal power of the BESS.
BESS protections/functions such as IDMT Overload Protection (page 570) and 2POverload Start
Evaluation Level (page 446), etc are related to this setpoint.

6 back to List of setpoints

Installed Power

Setpoint group Basic settings Related FW 1.5.0


OFF; 1 .. Nominal power (page 375) [kW] (depends on the selected Power
Range [units]
Formats And Units (page 196))
Default value OFF Force value Yes
Step 1 [kW] (depends on the selected Power Formats And Units (page 196))
Related
Comm object 16183 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the maximum power agreed for parallel to mains mode i.e. Breaker state (page
886) = ParalOper/MultParOp.
This setpoint influences:
Load Shedding (page 171)
Generator Unload BCBOpen Level (page 476)
Grid Codes (page 299)

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 375


Subgroup: Current settings

Nominal Current

Setpoint group Basic settings Related FW 1.5.0


Range [units] 1 .. 10000 [A]
Default value 350A Force value YES
Step 1A
Comm object 8275 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Current limit for BESS current protections and maximal continuous BESS current. Nominal current can
be different from mains rated current value.

6 back to List of setpoints

BESS CT Ratio Prim

Setpoint group Basic settings Related FW 1.5.0


Range [units] 1 .. 15000 [A]
Default value 500A Force value NO
Step 1A
Comm object 8274 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the primary range of the current transformer used for the BESS current
measurement.
Note: The setpoint is applied on all three phases of the BESS current.

Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 376


BESS CT Ratio Sec

Setpoint group Basic settings Related FW 1.5.0


Range [units] /5A or /1A [-]
Default value /5A Force value NO
Step [-]
Comm object 10556 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the secondary range of the current transformer used for the BESS current
measurement.
Note: This setpoint is applied on all three phases of the BESS current.

Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1

6 back to List of setpoints

Mains/Bus CT Ratio Prim / EFC

Setpoint group Basic settings Related FW 1.5.0


Range [units] 1 .. 15000 [A]
Default value 300 A Force value YES
Step 1A
Comm object 8566 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for settings of primary CT ratio of Mains L1 Current (page 842) measurement,
which is used for Mains Import P (page 842) calculation for needs of Soft Unload function.
IMPORTANT: L1 Mains current must be measured otherwise the power will be calculated
wrongly.

Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 377


Mains/Bus CT Ratio Sec / EFC

Setpoint group Basic settings Related FW 1.5.0


Range [units] /1A or /5A [-]
Default value /5A Force value YES
Step [-]
Comm object 10557 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for settings of secondary CT ratio of Mains L1 Current (page 842) measurement,
which is used for Mains Import P (page 842) calculation for needs of Soft Unload function.
IMPORTANT: L1 Mains current must be measured otherwise the power will be calculated
wrongly.

Note: The CT is usually described by this definition: CT Ratio Prim / CT Ratio Sec: Example:
100/5, 500/5, 1000/1

6 back to List of setpoints

3Ph CT Location

Setpoint group Basic settings Related FW 1.5.0


Range [units] BESS/Mains
Default value BESS Force value YES
Step [-]
Comm object 11625 Related applications MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint is used to switch the 3 phase measurement point to be on Mains or BESS side. If
measurement is on the Mains Import three phases then the BESS Power is measured by 4th CT (AUX)
where the value is multiplied by 3.

6 back to List of setpoints

Subgroup: Voltage settings

Connection type

Setpoint group Basic settings Related FW 1.5.0


Range [units] 3ph4Wire / High Leg D / 3ph3Wire / SplitPhase / MonoPhase [-]
Default value 3Ph4Wire [-] Force value NO
Step [-]
Comm object 11628 Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 378


Config level Standard
Setpoint visibility Always
Description
This setpoint defines connection type of the installation.

3Ph4Wire Grounded Star (Grounded Wye) connection – 3PY


Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
High Leg D High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
SplitPhase Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)

6 back to List of setpoints

Evaluated Voltage Protections

Setpoint group Basic settings Related FW 1.5.0


Range [units] Both / Phase-Phase / Phase-Neutral [-]
Default value Both [-] Force value NO
Step [-]
Comm object 10647 Related applications MINT, MPTM
Config level Standard
Only in case Setpoint Connection type (page 378) is set to 3Ph4Wire / High
Setpoint visibility
Leg D / SplitPhase
Description
This setpoint defines which voltage protections are evaluated.
Example: Connection type (page 378) is 3Ph4Wire and Evaluated Voltage Protections
(page 379) is set to Phase-Phase, the voltage protections will be evaluated only from Phase-
Phase voltage, does not matter what is the Phase-Neutral voltage.

InteliNeo 6000 1.5.0 Global Guide 379


IMPORTANT: Controller Mode has to be OFF, otherwise Evaluated Voltage Protections
(page 379) can not be changed and the failure dialog window is issued.

6 back to List of setpoints

BESS Nominal Voltage Ph-N

Setpoint group Basic settings Related FW 1.5.0


Range [units] 10 .. 34641 [V]
Default value 231 V Force value YES
Step 1V
Comm object 8277 Related applications MINT, MPTM
Config level Standard
Only ifConnection type (page 378) != High Leg D or Connection type (page
Setpoint visibility
378) != MonoPhase
Description
Nominal BESS voltage (phase to neutral).
6 back to List of setpoints

BESS Nominal Voltage Ph-Ph

Setpoint group Basic settings Related FW 1.5.0


Range [units] 10 .. 60000 [V]
Default value 400 V Force value YES
Step 1V
Comm object 11657 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Nominal BESS voltage (phase to phase).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 380


Mains/Bus Nominal Voltage Ph-N

Setpoint group Basic settings Related FW 1.5.0


Range [units] 10 .. 34641 [V]
Default value 231 V Force value YES
Step 1V
Comm object 9888 Related applications MINT, MPTM
Config level Standard
Only ifConnection type (page 378) != High Leg D or Connection type (page
Setpoint visibility
378) != MonoPhase
Description
Nominal Mains/Bus voltage (phase to neutral).
6 back to List of setpoints

Mains/Bus Nominal Voltage Ph-Ph

Setpoint group Basic settings Related FW 1.5.0


Range [units] 10 .. 60000 [V]
Default value 400 V Force value YES
Step 1V
Comm object 9907 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Nominal Mains/Bus voltage (phase to phase).
6 back to List of setpoints

BESS VT Ratio

Setpoint group Basic settings Related FW 1.5.0


Range [units] 0.01 .. 6000.00 [V/V]
Default value 1.00 V/V Force value NO
Step 0.01 V/V
Comm object 20281 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the converting ratio of the voltage meas transformer used on ① BESS VOLTAGE
Note: This setpoint is applied on all three phases of BESS voltage.

InteliNeo 6000 1.5.0 Global Guide 381


Example:
No VT is in use - voltage conversion is 1/1
BESS VT Ratio = 1.00
VT 22kV/100V - voltage conversion is 22000/100
BESS VT Ratio = 220.00
VT 3.3kV/110V - voltage conversion is 3300/110
BESS VT Ratio = 30.00

6 back to List of setpoints

BESS Voltage Input Range Select

Setpoint group Basic settings Related FW 1.5.0


Range [units] 200V / 400V / 600V [-]
Default value 400 V Force value YES
Step [-]
Comm object 10662 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the range of Ph-Ph AC Voltage measurement settings (page 17) on the ① BESS
VOLTAGE .
Note: It is possible to accurately measure Ph-Ph voltage which is maximally 25 % above the selected
range. So the maximal accurately measured voltage for the controller is 433 V Ph-N / 750 V Ph-Ph
with the selected range 600 V.

Note: If MonoPhase wiring is used the ranges are approximately corresponding to 116 V, 231 V, and
346 V Ph-N.

IMPORTANT: The range has to be set to fit the expected range of the AC voltage.

6 back to List of setpoints

Bus

Setpoint group Basic settings Related FW 1.5.0


Range [units] 0.01 .. 6000.00 [V/V]
Default value 1.00 V/V Force value NO
Step 0.01 V/V
Comm object 20282 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the converting ratio of the voltage meas transformer used on ② MAINS/BUS
VOLTAGE

InteliNeo 6000 1.5.0 Global Guide 382


Note: This setpoint is applied on all three phases of Mains/Bus voltage.

Example:
No VT is in use - voltage conversion is 1/1
Bus VT Ratio = 1.00
VT 22kV/100V - voltage conversion is 22000/100
Bus VT Ratio = 220.00
VT 3.3kV/110V - voltage conversion is 3300/110
Bus VT Ratio = 30.00

6 back to List of setpoints

Bus Voltage Input Range

Setpoint group Basic settings Related FW 1.5.0


Range [units] 200V / 400V / 600V [-]
Default value 400 V Force value YES
Step [-]
Comm object 10663 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the range of Ph-Ph AC Voltage measurement settings (page 17) on the
② MAINS/BUS VOLTAGE.
Note: It is possible to accurately measure Ph-Ph voltage which is maximally 25 % above the selected
range. So, the maximal accurately measured voltage for the controller is 433 V Ph-N / 750 V Ph-Ph
with the selected range 600 V.

Note: If MonoPhase wiring is used the ranges are approximately corresponding to 116 V, 231 V, and
346 V Ph-N.

IMPORTANT: The range has to be set to fit the expected range of the AC voltage.

6 back to List of setpoints

Bus Dead Level

Setpoint group Basic settings Related FW 1.5.0


0.0 .. 13.0 [%] of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus
Range [units]
Nominal Voltage Ph-Ph (page 381)
6.5 % of Mains/Bus Nominal
Voltage Ph-N (page 381) and
Default value Force value NO
Mains/Bus Nominal Voltage
Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 14473 Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 383


Config level Advanced
Setpoint
Always
visibility
Description
This setpoint defines the percentage voltage level below which is Bus considered as dead.

6 back to List of setpoints

Subgroup: Phase Rotation

Phase Rotation

Setpoint group Basic settings Related FW 1.5.0


Range [units] Clockwise / Counterclockwise [-]
Default value Clockwise Force value YES
Step [-]
Comm object 15122 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjust the phase sequence of voltage terminals.

6 back to List of setpoints

Subgroup: Frequency settings

Nominal Frequency

Setpoint group Basic settings Related FW 1.5.0


Range [units] 33.00 .. 520.00 [Hz]
Default value 50,00 Hz Force value YES
Step 0.01 Hz
Comm object 8278 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Nominal frequency of system (usually 50 or 60 Hz).
IMPORTANT: While BESS is running, this setpoint can be changed only inside currently
selected range. The ranges are 45-54 Hz and 55-65 Hz.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 384


Subgroup: Controller settings

Controller Mode

Setpoint group Basic settings Related FW 1.5.0


Range [units] OFF / MAN / AUTO [-]
Default value OFF Force value NO
Step [-]
Comm object 8315 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint can be used for changing the controller’s mode remotely, e.g. via Modbus.
InteliConfig: Use the mode selector on the main screen for changing the mode from the front panel.
Display: Use mode selector by pressing (Right arrow) and (Left arrow). Confirm it by pressing (enter).

6 back to List of setpoints

Power On Mode

Setpoint group Basic settings Related FW 1.5.0


Range [units] Previous / OFF [-]
Default value Previous Force value NO
Step [-]
Comm object 13000 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts controller mode after power on of controller.

Previous Controller is switched into the last mode before power off.
OFF Controller is switched into OFF mode.

Note: Remote modes - In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint - controller mode is forced into mode selected via
LBI. After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 385


Fault Reset To Manual

Setpoint group Basic settings Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 9983 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
If this function is enabled, the controller will switch automatically to MAN mode when there is a red alarm
in the alarm list and fault reset button is pressed. This is a safety function that prevents the BESS starting
again automatically in specific cases when fault reset button is pressed.
Example: Controller is in AUTO mode, there is red inactive unconfirmed alarm, and fault reset
button is pressed. The BESS will start automatically if LBI GENERIC GENSET START/STOP (PAGE
1004) is active.

6 back to List of setpoints

Horn Timeout

Setpoint group Basic settings Related FW 1.5.0


Range [units] Disabled = 0; 1 .. 600; Horn Reset [s]
Default value 10 s Force value NO
Step 1s
Comm object 8264 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint affects horn's behavior.
Disabled Horn sound is disabled e.g. LBO HORN (PAGE 1082) is never activated
1 .. 600 [s] Timeout for LBO HORN (PAGE 1082). Output opens after this time elapses
Horn Reset LBO HORN (PAGE 1082) is active until button Horn Reset is pressed.

Note: Horn timeout starts again from the beginning if any new alarm appears before previous Horn
timeout has elapsed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 386


Fail Safe Binary State

Setpoint group Basic settings Related FW 1.5.0


Range [units] Log0 / Log1 / Last Valid State [-]
Default value Last Valid State Force value YES
Step [-]
Comm object 21215 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of all binary inputs while the received value is invalid (communication lost).
Changes of the setpoint will not be applied on peripherals which are already in fail safe binary state.

Log0 The value is logical zero.


Log1 The value is logical one.
Last Valid State The value is replaced by last valid state.

6 back to List of setpoints

Run Hours Source

Setpoint group Basic settings Related FW 1.5.0


Range [units] AUTO / ECU / INTERNAL [-]
Default value AUTO Force value YES
Step [-]
Comm object 13345 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts source for Running Hours (page 880).

Source is selected automatically between INTERNAL and ECU. ECU source is


AUTO
prioritized.
ECU Source is forced to be always ECU. ECU provides Running Hours (page 880).
Source is forced to be always INTERNAL. Controller provides Running Hours
INTERNAL
(page 880).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 387


SW Key

Setpoint group Basic settings Related FW 1.5.0


Range [units] 31 characters [-]
Default value AUTO Force value NO
Step [-]
Comm object 24258 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint is designed for SW Key which unlocks premium features.
Note: The controller has to be power cycled after inserting the SW Key.

6 back to List of setpoints

User Logging Record

Setpoint group Basic settings Related FW 1.5.0


Range [units] Enabled / Disabled
Default value Enabled Force value NO
Step [-]
Comm object 23885 Related applications MINT, MPTM
Config level Basic
Setpoint visibility Always
Description
This setpoint enables recording of user login in/out to the controller history.
Example: The fallowing records will be shown in the history if enabled: User with user index (0)
loegged in via ETH.

6 back to List of setpoints

Fuel Genset Consumption

Setpoint group Basic settings Related FW 1.5.0


Range [units] 0,0 .. 10 000,0 g/kWh
Default value 237,3 [g/kWh] Force value
Step 0,1 [g/kWh]
Comm object 23885 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
Fuel consumed by the Gen-set per 1 kWh.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 388


Subgroup:

Battery Undervoltage

Setpoint group BESS settings Related FW 1.5.0


Range [units] 8.0 V .. Battery Overvoltage (page 389) [V]
Default value 18.0 V Force value NO
Step 0.1 V
Comm object 8387 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Warning threshold for low battery/power supply voltage.
6 back to List of setpoints

Battery Overvoltage

Setpoint group BESS settings Related FW 1.5.0


Range [units] Battery Undervoltage (page 389) .. 40.0 [V]
Default value 36.0 V Force value NO
Step 0.1 V
Comm object 9587 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Warning threshold for high battery/power supply voltage.
6 back to List of setpoints

Battery <> Voltage Delay

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. 600 [s]
Default value 5s Force value NO
Step 1s
Comm object 8383 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Delay for which battery/power supply voltage can be out of range given by setpoints Battery
Undervoltage (page 389) and Battery Overvoltage (page 389). After this delay elapses, appropriate
alarm (Wrn Battery Undervoltage (page 1250) or Wrn Battery Overvoltage (page 1249)) is
activated.
6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 389


Subgroup: Pulse counters

Conversion Coeff. Fast Pulse 1

Setpoint group BESS settings Related FW 1.5.0


Range [units] OFF / 0 .. 65000 [-]
Default value OFF Force value YES
Step 1 [-]
Comm object 20307 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the rate of increasing of the Fast Pulse Counter 1 (page 883) which is physically
configured to binary input 9.
Set this setpoint to OFF to turn the function off. See the chapter Pulse Counters (page 211) for more
information.

6 back to List of setpoints

Conversion Coeff. Fast Pulse 2

Setpoint group BESS settings Related FW 1.5.0


Range [units] OFF / 0 .. 65000 [-]
Default value OFF Force value YES
Step 1 [-]
Comm object 20308 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the rate of increasing of the Fast Pulse Counter 2 (page 884) which is physically
configured to binary input 10.
Set this setpoint to OFF to turn the function off. See the chapter Pulse Counters (page 211) for more
information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 390


Conversion Coefficient Pulse 1

Setpoint group BESS settings Related FW 1.5.0


Range [units] OFF / 0 .. 65000 [-]
Default value OFF Force value NO
Step 1 [-]
Comm object 10994 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the rate of increasing of the "slow" Pulse Counter 1 (page 884) which is connected
with LBI PULSE COUNTER 1 (PAGE 1018).
Set this setpoint to OFF to turn the function off. See the chapter Pulse Counters (page 211) for more
information.

6 back to List of setpoints

Conversion Coefficient Pulse 2

Setpoint group BESS settings Related FW 1.5.0


Range [units] OFF / 0 .. 65000 [-]
Default value OFF Force value NO
Step 1 [-]
Comm object 10995 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the rate of increasing of the "slow" Pulse Counter 2 (page 884) which is connected
with LBI PULSE COUNTER 2 (PAGE 1018).
Set this setpoint to OFF to turn the function off. See the chapter Pulse Counters (page 211) for more
information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 391


Group: Communication Settings

Subgroup: Controller Address

CAN Controller Address

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 1 .. 64 [-]
Default value 1 [-] Force value NO
Step 1 [-]
Comm object 23999 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts Controller's CAN Address which is used for CAN Intercontroller Communication
(page 132).
This type of communication is used to share information between other ComAp controllers via CAN
interface (Communication peripherals (page 18)).
Note: Each controller connected via CAN has to have unique address, i.e. maximally 64 controllers
can be connected together.

Note: There is an exception, if the function Hot Swap Redundancy (page 160) is used, the Master
and Backup controllers has to have same address because they act like one controller unit for the
rest of the site.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 392


Universal Genset Address

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] OFF; 1 .. 64 [-]
Default value 0 Force value NO
Step 1
Comm object 23832 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This Setpoint has to be set to the specific address. The Universal Gensets will be then represented
across the whole system as a genset with this address.
It is recommended to set the Address as CAN Address of InteliNeo + 1. The default settings 0=OFF
means that the Universal Genset Support Function is not in use. The InteliNeo actually creates the virtual
genset inside the system. The information about this virtual genset can be observed in all genset related
information inside the system like CAN 16, CAN32, GL 16, GL 32, Reg 16, Reg 32 Values. Universal
genset is always located in the same group as InteliNeo which integrates it into the system.
6 back to List of setpoints

Terminal Comm Address

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 1 .. 32 [-]
Default value 1 [-] Force value NO
Step 1 [-]
Comm object 24019 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts Controller’s Terminal Address which is used for communication with other devices
using terminals ETH1, ETH2, and RS485 (Communication peripherals (page 18)). This type of
communication is used fore remote or local connection of the computer (InteliConfig), Display, Modbus
Server, etc.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 393


Subgroup: RS485 Settings

RS485 Modbus Speed

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Force value NO
Step [-]
Comm object 24141 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts communication speed ofModbus-RTU, Modbus/TCP (page 316).

6 back to List of setpoints

RS485 Modbus Mode

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 8N1 / 8N2 / 8E1 [-]
Default value 8N1 Force value NO
Step [-]
Comm object 24020 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts communication mode of Modbus-RTU, Modbus/TCP (page 316).

Possible options
8N1 8 data bits, 1 stop bit, no parity
8N2 8 data bits, 2 stop bits, no parity
8E1 8 data bits, 1 stop bit, even parity

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 394


Subgroup: History Settings

LB/UART Log

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 11327 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables/disables logging of connection/disconnection of each remote terminal. The record
is written to the history.
Note: The terminal is disconnected automatically after 1 min of inactivity and next communication
request from the same terminal is considered as a new connection. When logging is enabled in
certain conditions the history may be filled up with large number of records related to the
communication and important record may be overwritten quite fast.

Disabled Logging is disabled.


Logging is enabled. Connection/Disconnection over ETH1, ETH2 or USB
(Communication peripherals (page 18)) causes history log.
Enabled
Note: Connection over USB is recognized after reading of/writing to a
communication object.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 395


Subgroup: Intercontroller Settings

CAN Intercontroller Comm Redund

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Enabled / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24026 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables CAN Intercontroller Communication Redundancy (page 132).
Note: In case that there is a mismatch between this setpoint and actual state of ⑦ CAN2B (page 46)
alarm ALI Redundant CAN Error (page 1273) is activated.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 396


CAN Intercontroller Comm Mode

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] 32C / 16C / 8C / 64C CAN FD / 32C CAN FD / 8C CAN FD [-]
Default value 8C Force value NO
Step [-]
Comm object 24499 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects the mode of intercontroller communication. Options 32C or 8C are necessary to use
in order to ensure the communication between InteliNeo6000 and older controllers such as IGS-NT,
IG2GSC, IG200, IG500. Options 64C CAN FD, 32C CAN FD and 8C CAN FD are compatible only with
controllers which support the CAN FD communication.
Note: It is strongly recommended to use CAN FD modes if all controllers on-site support the CAN FD
communication.

Mode Arbitration Bit-Rate Data Bit-Rate Maximal Bus Length Max Bus Length With Repeater
32C 250 kbit 250 kbit 200 m 800 m
16C 125 kbit 125 kbit 400 m 1600 m
8C 50 kbit 50 kbit 900 m 3600 m
64C CAN FD 250 kb 2 Mbit 200 m Not tested
32C CAN FD 125 kb 1 Mbit 400 m Not tested
8C CAN FD 50 kb 400 kbit 900 m Not tested

IMPORTANT: All controllers communicating on common CAN have to use the same mode of
this setpoint.

IMPORTANT: All changes made to the setpoint takes effect after the restart of the controller.

Note: In case that there is a mismatch between this setpoint and value CAN Intercontroller Comm
Mode (page 888), alarm ALI CAN Mode Inconsistency (page 1271) is activated.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 397


CAN Intercontroller Empty Check

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Enabled / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 9921 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable CAN2 Intercontroller Empty Check.

Disabled Detection of CAN Intercontroller Empty Check is disabled.


Detection of CAN Intercontroller Empty Check is enabled. If controller does
Enabled not see any other controller on the⑧ CAN2A (page 46) or⑦ CAN2B (page
46) the Wrn CAN2 Empty (page 1250) will be activated.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 398


Access Lock Mode

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Optional/ Required[-]
Default value Optional Force value NO
Step [-]
Comm object 23842 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Switching the Access Lock mode of operation so that the lock can be forced to be used to control the
controller.
Option Optional = Locking the lock does not condition the ability to operate the machine, it only allows
you to cut off other users if necessary.

Unlocked The controller can be controlled by anyone


Locked The controller can only be operated by the owner of the lock

Option Required = The lock is required for control, i.e. I have to lock with my account to control the
controller.

Unlocked No one can control the controller


Locked The controller can only be operated by the owner of the lock

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 399


Automatic Access Lock Release

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled/ Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 23840 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Option to automatically unlock Access Lock if the owner of the lock is no longer logged into any active
session on the controller.

when the controller detects that the lock is locked but its owner is no longer
ENABLED
logged in any session, it automatically unlocks the lock
the lock remains locked regardless of whether the owner is logged in or not, it is
DISABLED
only unlocked manually (by the owner or administrator)

6 back to List of setpoints

User sessions limit

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled; 1 .. 10 [-]
Default value Disabled Force value NO
Step [-]
Comm object 23841 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
The number of concurrent sessions in which the same user is allowed to log in.
In the DISABLED state the controller behaves as it does in standard version, i.e. does not limit the
number of connections in which the same user is logged in. A user can log in with several connections at
the same time.
In the active state, each individual user can log into as many connections as is set by this setpoint.
Note: This feature does not apply to users in the administrator role and does not apply to the implicit
user.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 400


Subgroup: SD Card Settings

SD Card File System

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Unmount / Mount / Format [-]
Default value Unmount Force value NO
Step [-]
Comm object 23997 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint determines whether the SD card is mounted, unmounted, or should be formatted. After
formatting, the setpoint is automatically switched to the mount option. If the setpoint is set to unmount no
interaction with the SD card is allowed, the controller will only detect that the SD card is inserted.
IMPORTANT: This setpoint has to be set to Mount in order to allow any writing function to
the SD card.

6 back to List of setpoints

Long Term History

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 23995 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables/disables writing of long term history onto the SD card.
Note: Setpoint SD Card File System (page 401) - has to be adjusted to Mount.

Disabled Long Term History is not written onto the SD card.


Enabled Long Term History is written onto the SD card.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 401


Subgroup: CAN1 ECU/IO Modules Split

CAN1 ECU/IOModules Split

Communication
Setpoint group Related FW 1.5.0
Settings
Range [units] Disabled/Enabled
Default value Disabled Force value NO
Step -
Comm object 17339 Related applications MINT, MPTM
Config level Standard
Setpoint visibility When setpoint Hot Swap Redundancy (page 371) = Disabled
Description
This setpoint allows to change the behavior on CAN1 communication terminals.
By default, CAN1A terminal is used for communication with ECU and IO Modules, CAN1B terminal is
used for Hot Swap Redundancy (page 160). By enabling this setpoint, the CAN1A terminal can be
used only for ECU, the CAN1B can be used only for IO Modules.
Note: In case that CAN1 ECU/IOModules Split (page 402) is enabled, the Hot Swap Redundancy
(page 160) is disabled (and vice versa).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 402


Group: Ethernet Port Configuration

Ethernet port 1

Ethernet Port
Setpoint group Related FW 1.5.0
Configuration
Trusted Interface / Untrusted Interface / Modbus Interface / Trusted
Range [units]
Mirroring / Untrusted Mirroring / Modbus Mirroring [-]
Trusted
Default value Force value NO
Interface
Step [-]
Comm object 23873 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the interface type on ethernet slot 1.
Trusted Interface - It is expected that these interfaces are operated locally inside a closed
environment / infrastructure where additional measures against misuse or attack take place (e.g.
physical access limitation). Due to nature of this interface less strict cybersecurity rules apply at it and
that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted Interface - This interface is a general-purpose one and it is expected that it may be
exposed to public networks, such as Internet, which are not under control of the entity operating the
controller. Thus, strict cybersecurity rules apply for this type of interface.
Modbus Interface - This type of interface is used for Modbus communication. It is not possible to
connect to the controller using this interface.
Trusted Mirroring/Untrusted Mirroring/Modbus Mirroring - If mirroring mode is selected for a
socket, the switch will be configured that except sending traffic belonging normally to that socket, it
will also copy to that socket all traffic from other sockets assigned to the same network.
Note: Only one socket can be adjusted to mirroring function. If multiple sockets are adjusted to
mirroring function the alarm ALI Ethernet Port Inconsistency will be still displayed after the CU restart.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 403


Ethernet port 2

Ethernet Port
Setpoint group Related FW 1.5.0
Configuration
Trusted Interface / Untrusted Interface / Modbus Interface / Trusted Mirroring /
Range [units]
Untrusted Mirroring / Modbus Mirroring [-]
Default value Trusted Interface Force value NO
Step [-]
Comm object 23872 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the interface type on ethernet slot 2.
Trusted Interface - It is expected that these interfaces are operated locally inside a closed
environment / infrastructure where additional measures against misuse or attack take place (e.g.
physical access limitation). Due to nature of this interface less strict cybersecurity rules apply at it and
that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted Interface - This interface is a general-purpose one and it is expected that it may be
exposed to public networks, such as Internet, which are not under control of the entity operating the
controller. Thus, strict cybersecurity rules apply for this type of interface.
Modbus Interface - This type of interface is used for Modbus communication. It is not possible to
connect to the controller using this interface.
Trusted Mirroring/Untrusted Mirroring/Modbus Mirroring - If mirroring mode is selected for a
socket, the switch will be configured that except sending traffic belonging normally to that socket, it
will also copy to that socket all traffic from other sockets assigned to the same network.
Note: Only one socket can be adjusted to mirroring function. If multiple sockets are adjusted to
mirroring function the alarm ALI Ethernet Port Inconsistency will be still displayed after the CU restart.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 404


Ethernet port 3

Ethernet Port
Setpoint group Related FW 1.5.0
Configuration
Trusted Interface / Untrusted Interface / Modbus Interface / Trusted Mirroring /
Range [units]
Untrusted Mirroring / Modbus Mirroring [-]
Default value Modbus Interface Force value NO
Step [-]
Comm object 23871 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the interface type on ethernet slot 3.
Trusted Interface - It is expected that these interfaces are operated locally inside a closed
environment / infrastructure where additional measures against misuse or attack take place (e.g.
physical access limitation). Due to nature of this interface less strict cybersecurity rules apply at it and
that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted Interface - This interface is a general-purpose one and it is expected that it may be
exposed to public networks, such as Internet, which are not under control of the entity operating the
controller. Thus, strict cybersecurity rules apply for this type of interface.
Modbus Interface -This type of interface is used for Modbus communication. It is not possible to
connect to the controller using this interface.
Trusted Mirroring/Untrusted Mirroring/Modbus Mirroring - If mirroring mode is selected for a
socket, the switch will be configured that except sending traffic belonging normally to that socket, it
will also copy to that socket all traffic from other sockets assigned to the same network.
Note: Only one socket can be adjusted to mirroring function. If multiple sockets are adjusted to
mirroring function the alarm ALI Ethernet Port Inconsistency will be still displayed after the CU restart.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 405


Group: ETH Interface 1 - Trusted

Subgroup: TCP/IP Settings

IP Address Mode

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] Manual / Automatic / Disabled [-]
Default value Automatic Force value YES
Step [-]
Comm object 24063 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the method how the ethernet connection is adjusted on Ethernet 1 (page
19).

Manual: Manual: The Ethernet connection is fixed by means of the setpoints IP


Address (page 407), Subnet Mask (page 407), Gateway IP (page 408). This
method should be used for a classic Ethernet or internet connection. When this
type of connection opens, the controller is specified by its IP address. This
means that it would be inconvenient if the IP address were not fixed (static).
Automatic: The Ethernet connection settings is obtained automatically from the DHCP
server. The obtained settings is shown in related values. If the process of
obtaining the settings from the DHCP server is not successful, the values
000.000.000.000 are shown.
Disabled: The Ethernet terminal is disabled.

IMPORTANT: When the mode is switched from Automatic to Manual the TCP/IP settings
will be changed to the values in the related setpoints. In case you are using Ethernet 1 to
connect the CU you will be disconnected. Turn off the setpoint hiding function to
manually change the TCP/IP settings to same values obtained via DHCP so you will not be
disconnected when changing mode.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 406


IP Address

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.1.1 Force value NO
Step [-]
Comm object 24061 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 406) = Manual
Description
The setpoint is used to select the method how the IP Address is adjusted on Ethernet 1 (page 19).
If IP Address Mode (page 406) = Manual, this setpoint is used to adjust the IP address of the Ethernet
1 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 406) = Automatic this setpoint is inactive. The IP address is assigned by the
DHCP server.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

Subnet Mask

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 15 characters [-]
Default value 255.255.255.0 Force value NO
Step [-]
Comm object 24059 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
The setpoint is used to select the method how the Subnet Mask is adjusted on Ethernet 1 (page 19).
If IP Address Mode (page 406) = Manual, this setpoint is used to adjust the Subnet Mask. Ask your IT
specialist for help.
If IP Address Mode (page 406) = Automatic this setpoint is inactive. The Subnet Mask is assigned by
the DHCP server.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 407


Gateway IP

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.1.1 Force value NO
Step [-]
Comm object 24057 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 406) = Manual
Description
This setpoint is used to select the method how the Gateway IP is adjusted on Ethernet 1 (page 19) .
If IP Address Mode (page 406) = Manual, this setpoint is used to adjust the IP address of the gateway
of the network segment where the controller is connected.
If IP Address Mode (page 406) = Automatic this setpoint is used to display the gateway IP which has
been assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or the
internet.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

IP Firewall

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] Enabled / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24029 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints enables or disables the built-in Firewall (page 157) functionality for Ethernet 1 (page
19).

Disabled: The firewall function is switched off


Enabled: The firewall function is switched on.

IMPORTANT: Loss of connection can happen when enabling the firewall and using remote
connection via Internet

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 408


Subgroup: SNMP Settings

SNMP Privacy Protocol

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] DES / 3DES / AES128 / AES256 [-]
Default value AES128 Force value NO
Step [-]
Comm object 23856 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Selects SNMP v3 Privacy Protocol.

6 back to List of setpoints

SNMP Authentication Protocol

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] MD5 / SHA / SHA256[-]
Default value SHA Force value NO
Step [-]
Comm object 23857 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Selects SNMP v3 Authentication Protocol.

6 back to List of setpoints

SNMP Security Level

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] NONE/ AUTH-NOPRIV / AUTH-PRIV [-]
Default value NONE Force value NO
Step [-]
Comm object 23855 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Selects SNMP v3 security level. If NONE the agent will work in SNMP v2c mode..

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 409


Subgroup: Modbus Server Settings

Modbus Server

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24034 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables Modbus communication via Ethernet 1 (page 19).

6 back to List of setpoints

Modbus Client Inactivity Timeout

ETH Interface 1 -
Trusted
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
ETH Interface 3 -
Modbus
Range [units] 0 .. 65535 [s]
Default value 60 s Force value NO
Step 1s
Comm object 24097 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Modbus connection (TCP socket) is closed by controller, if a Modbus client does not communicate for
this time.
Note: This setpoint is shared with other Modbus Client Inactivity Timeout setpoints.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 410


Subgroup: ComAp Client Settings

Direct Connection Port

ETH Interface 1 -
Setpoint group Related FW 1.5.0
Trusted
Range [units] 0 .. 65535 [-]
Default value 23 [-] Force value YES
Step 1 [-]
Comm object 24035 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This port is used to listen for an incoming TCP connection on Ethernet 1 (page 19).

6 back to List of setpoints

ComAp Client Inactivity Timeout

ETH Interface 1 -
Setpoint group TrustedETH Interface 2 Related FW 1.5.0
- Untrusted
Range [units] 0 .. 65535 [s]
Default value 60 s Force value YES
Step 1s
Comm object 24098 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Connection (TCP socket) is closed by controller, if a client (e.g. InteliConfig) does not communicate for
this time. This timeout applies to both direct and AirGate connection.
Note: This setpoint is shared with ComAp Client Inactivity Timeout (page 411).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 411


Group: ETH Interface 2 - Untrusted

Subgroup: TCP/IP Settings

IP Address Mode

ETH Interface 2 -
Setpoint group Untrusted Related FW 1.5.0
Ethernet
Range [units] Manual / Automatic / Disabled [-]
Default value Automatic Force value NO
Step [-]
Comm object 24259 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the method how the ethernet connection is adjusted on Ethernet 2 (page
19).

Manual: The Ethernet connection is fixed by means of the setpoints IP Address (page
413), Subnet Mask (page 413), Gateway IP (page 414), DNS IP Address 1
(page 415), DNS IP Address 2 (page 416). This method should be used for a
classic Ethernet or internet connection. When this type of connection opens,
the controller is specified by its IP address. This means that it would be
inconvenient if the IP address were not fixed (static).
Automatic: The Ethernet connection settings is obtained automatically from the DHCP
server. The obtained settings is shown in related values. If the process of
obtaining the settings from the DHCP server is not successful, the values
000.000.000.000 are shown.
Disabled: The Ethernet terminal is disabled.

IMPORTANT: When the mode is switched from Automatic to Manual the TCP/IP settings
will be changed to the values in the related setpoints. In case you are using Ethernet 2 to
connect the CU you will be disconnected. Turn off the setpoint hiding function to
manually change the TCP/IP settings to same values obtained via DHCP so you will not be
disconnected when changing mode.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 412


IP Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.2.254 Force value NO
Step [-]
Comm object 24376 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
The setpoint is used to select the method how the IP Address is adjusted on Ethernet 2 (page 19).
If IP Address Mode (page 412) = Manual, this setpoint is used to adjust the IP address of the Ethernet
2 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 412) = Automatic this setpoint is inactive. The IP address is assigned by the
DHCP server.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

Subnet Mask

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 255.255.255.0 Force value NO
Step [-]
Comm object 24375 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
The setpoint is used to select the method how the Subnet Mask is adjusted on Ethernet 2 (page 19).
If IP Address Mode (page 412) = Manual this setpoint is used to adjust the Subnet Mask. Ask your IT
specialist for help with this setting.
If IP Address Mode (page 412) = Automatic this setpoint is inactive. The Subnet Mask is assigned by
the DHCP server.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 413


Gateway IP

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 192.168.2.1 Force value NO
Step [-]
Comm object 24373 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Manual
Description
This setpoint is used to select the method how the Gateway IP is adjusted.
If IP Address Mode (page 412) = Manual, this setpoint is used to adjust the Gateway IP address of the
Ethernet 2 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 412) = Automatic this setpoint is inactive. The Gateway IP address is
assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or Internet.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

IP Firewall

ETH Interface 2 -
Setpoint group Untrusted Related FW 1.5.0
Ethernet
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Related
Comm object 24092 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
This setpoints enables or disables the built-in Firewall (page 157) functionality for Ethernet 2 (page
19).

Disabled: The firewall function is switched off


Enabled: The firewall function is switched on.

IMPORTANT: Loss of connection can happen when enabling the firewall and using remote
connection via Internet

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 414


DNS Mode

ETH Interface 2 -
Setpoint group Untrusted Related FW 1.5.0
Ethernet
Range [units] Manual / Automatic [-]
Default value Automatic Force value
Step [-]
Comm object 24101 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 412) = Automatic
Description
This setpoint enables to enter DNS server addresses for Ethernet 2 (page 19) manually, even with the
IP Address Mode (page 412) set to Automatic.

Automatic: DNS server addresses are automatically obtained from a DHCP server.
DNS IP Address 1 (page 415) and DNS IP Address 2 (page 416) can be
adjusted manually. Use this option to resolve e.g. internet access policy related
Manual:
issue, if local DNS server addresses automatically obtained from a DHCP server
do not work

6 back to List of setpoints

DNS IP Address 1

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 8.8.8.8 Force value NO
Step [-]
Comm object 24362 Related applications MINT, MPTM
Config level Standard
Only if IP Address Mode (page 412) = Manual OR (IP Address Mode (page 412)
Setpoint visibility
= Automatic AND DNS Mode (page 415) = Manual)
Description
This setpoint allows to set DNS IP Address 1 for Ethernet 2 (page 19) manually.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 415


DNS IP Address 2

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 15 characters [-]
Default value 4.4.4.4 Force value NO
Step [-]
Comm object 24331 Related applications MINT, MPTM
Config level Standard
Only if IP Address Mode (page 412) = Manual OR (IP Address Mode (page 412)
Setpoint visibility
= Automatic AND DNS Mode (page 415) = Manual)
Description
This setpoint allows to set DNS IP Address 2 for Ethernet 2 (page 19) manually.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

Subgroup: AirGate Settings

AirGate Connection

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 24365 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables AirGate connection (page 116) function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 416


AirGate Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 31 characters [-]
Default value global.airgate.link Force value NO
Step [-]
Comm object 24364 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free
AirGate server provided by ComAp at global.airgate.link.

6 back to List of setpoints

AirGate Port

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 65535 [-]
Default value 54440 [-] Force value NO
Step 1 [-]
Comm object 24096 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This port is used for TCP communication with the AirGate server.
Note: Use port 5440 for standard ComAp AirGate service.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 417


Subgroup: Messages Settings

Event Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 18971 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Event Messages.

6 back to List of setpoints

Wrn Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8482 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Warning Messages.

6 back to List of setpoints

Al Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10567 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Alarm Only messages.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 418


Hst Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10568 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of History Record Only messages.

6 back to List of setpoints

ALI Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 18993 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Alarm List Indication messages.

6 back to List of setpoints

AHI Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 18994 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
XYZ.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 419


Sd Message

ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8484 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Shutdown Messages.

6 back to List of setpoints

Sd Override Message

ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 11413 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Shutdown Override Messages.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 420


Stp Message

Setpoint group Related FW 1.5.0


Ethernet
Range [units] Enabled/Disabled
Default value Enabled Force value
Step [-]
Comm object 8485 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of messages.

6 back to List of setpoints

MP Message

ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10117 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Mains Protection messages.

6 back to List of setpoints

PVBO Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10926 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of PVBO Messages.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 421


E-mail Language

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Depends on controller’s supported languages. [-]
Default value English Force value NO
Step [-]
Comm object 24299 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to set the language of Event, Warning, etc. e-mails.

6 back to List of setpoints

Subgroup: E-mail Settings

E-mail Address 1

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24298 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

E-mail Address 2

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24297 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 422


E-mail Address 3

Setpoint group ETH Interface 2 - Untrusted Related FW 1.5.0


Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24145 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

E-mail Address 4

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24144 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

SMTP User Name

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Related
Comm object 23877 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the username for the SMTP server. Leave the setpoint blank if the SMTP
server does not require authentication.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 423


SMTP User Password

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..15 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23876 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the password for the SMTP server. Leave the setpoint blank if the SMTP server
does not require authentication.

6 back to List of setpoints

SMTP Server Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value global.airgate.link:9925 Force value NO
Step [-]
Comm object 24093 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name (e.g. smtp.yourprovider.com) or IP address (e.g.
74.125.39.109) and port number (e.g. :9925) of the SMTP server. Ask your internet provider or IT
manager for this information.
Example: Enter the IP address "74.125.39.109" and port number "9925" as
"74.125.39.109:9925".

Note: You may use also any public SMTP server which does not require connection over SSL/TLS
channels.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 424


SMTP Sender Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23878 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter an existing email address into this setpoint. This address will be used as sender address in active
e-mails that will be sent from the controller.
Note: It is not needed to enter an existing email address, nevertheless valid email format needs to be
followed.

IMPORTANT: This item is obligatory when emails are configured.

6 back to List of setpoints

SMTP Encryption Type

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] NONE / SSL/TLS / STARTTLS [-]
Default value NONE Force value NO
Step [-]
Comm object 24076 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects encryption type for SMTP session.

NONE Session is without of any encryption.


SSL/TLS Encrypted channel is created first and only after that session is created.
Session is created without of encryption and after command STARTTLS it
STARTTLS
is switched to encrypted session.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 425


Subgroup: SNMP Settings

SNMP Agent

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / SNMP v1/v2c / SNMP v3 [-]
Default value Disabled Force value NO
Step [-]
Comm object 24336 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints Enables or disables Simple Network Management Protocol (SNMP) Agent.
Note: SNMP v3 has upgraded encryption, remote configuration, and security (extra setpoints are
available).

Note: It is supported only User-Based security model (USM, RFC-3414). View-based Access
Control Model (VACM, RFC-3415) is not supported.

6 back to List of setpoints

SNMP Trap Format

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] v1 Trap / v2 Notific / v2 Inform [-]
Default value v2 Inform Force value NO
Step [-]
Comm object 24136 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
This setpoint selects format of the SNMP trap messages.

v1 Trap SNMPv1 trap format is used


v2 Notific SNMPv2c Notification format is used
v2 Inform SNMPv2c Inform format is used
6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 426


SNMP RD Community String

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value public Force value NO
Step [-]
Comm object 24335 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
SNMP Community String only for reading.

6 back to List of setpoints

SNMP WR Community String

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value private Force value NO
Step [-]
Comm object 24334 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v1/v2c
Description
SNMP Community String for writing and reading.

6 back to List of setpoints

SNMP Traps IP Address 1

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 63 characters [-]
Default value - Force value NO
Step [-]
Comm object 24095 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
IP address 1 for receiving SNMP Traps. Leave this setpoint blank if SNMP traps should not be send.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 427


SNMP Traps IP Address 2

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Valid IP address [-]
Default value - Force value NO
Step [-]
Comm object 24094 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) != Disabled
Description
IP address 2 for receiving SNMP Traps. Leave this setpoint blank if SNMP traps should not be send.

6 back to List of setpoints

SNMP Engine User Name

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 31 characters [-]
Default value - Force value NO
Step [-]
Comm object 23851 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if SNMP Agent (page 426) = SNMP v3
Description
Defines SNMP v3 Engine User Name.

6 back to List of setpoints

Subgroup: Modbus Server Settings

Modbus Server

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24337 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enables or disables Modbus communication via Ethernet 2 (page 19).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 428


Modbus Client Inactivity Timeout

ETH Interface 1 -
Trusted
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
ETH Interface 3 -
Modbus
Range [units] 0 .. 65535 [s]
Default value 60 s Force value NO
Step 1s
Comm object 24097 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Modbus connection (TCP socket) is closed by controller, if a Modbus client does not communicate for
this time.
Note: This setpoint is shared with other Modbus Client Inactivity Timeout setpoints.

6 back to List of setpoints

Subgroup: ComAp Client Settings

Direct Connection

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 24099 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enable/disable direct connection of a ComAp client (e.g. InteliConfig) to the IP
address of the controller.
Note: For Direct connection the controller IP address must be reachable from the client IP
address.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 429


Direct Connection Port

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 65535 [-]
Default value 23 [-] Force value NO
Step 1 [-]
Comm object 24374 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This port is used to listen for an incoming TCP connection on Ethernet 2 (page 19).

6 back to List of setpoints

ComAp Client Inactivity Timeout

ETH Interface 1 -
Setpoint group TrustedETH Interface 2 Related FW 1.5.0
- Untrusted
Range [units] 0 .. 65535 [s]
Default value 60 s Force value YES
Step 1s
Comm object 24098 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Connection (TCP socket) is closed by controller, if a client (e.g. InteliConfig) does not communicate for
this time. This timeout applies to both direct and AirGate connection.
Note: This setpoint is shared with ComAp Client Inactivity Timeout (page 430).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 430


Subgroup: NTP Settings

NTP Clock Synchronization

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 24075 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to enable/disable synchronization of the controller's time with the exact time from a
NTP server.

6 back to List of setpoints

NTP Server

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 63 characters [-]
Default value pool.ntp.org Force value NO
Step [-]
Comm object 24074 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
NTP server address for time synchronization.
Note: Only valid IP address or domain can be inserted.

6 back to List of setpoints

Group: ETH Interface 3 - Modbus

Subgroup: TCP/IP Settings

IP Address Mode

ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] Manual / Automatic / Disabled [-]
Default value Automatic Force value NO
Step [-]
Comm object 24049 Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 431


Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint is used to select the method how the ethernet connection is adjusted on Ethernet 3 (page
19).

Manual: The Ethernet connection is fixed by means of the setpoints IP Address (page
432), Subnet Mask (page 432) and Gateway IP (page 433). This method
should be used for a classic Ethernet or internet connection. When this type of
connection opens, the controller is specified by its IP address. This means that
it would be inconvenient if the IP address were not fixed (static).
Automatic: The Ethernet connection settings is obtained automatically from the DHCP
server. The obtained settings is shown in related values. If the process of
obtaining the settings from the DHCP server is not successful, the values
000.000.000.000 are shown.
Disabled: The Ethernet terminal is disabled.

6 back to List of setpoints

IP Address

ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] 0 .. 15 characters [-]
Default value 192.168.3.254 Force value NO
Step [-]
Comm object 24047 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 431) = Manual
Description
The setpoint is used to select the method how the IP Address is adjusted on Ethernet 3 (page 19).
If IP Address Mode (page 431) = Manual, this setpoint is used to adjust the IP address of the Ethernet
3 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 431) = Automatic this setpoint is inactive. The IP address is assigned by the
DHCP server.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

Subnet Mask

ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] 0 .. 15 characters [-]
Default value 255.255.255.0 Force value NO

InteliNeo 6000 1.5.0 Global Guide 432


Step [-]
Comm object 24045 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 431) = Manual
Description
The setpoint is used to select the method how the Subnet Mask is adjusted on Ethernet 3 (page 19).
If IP Address Mode (page 431) = Manual this setpoint is used to adjust the Subnet Mask. Ask your IT
specialist for help with this setting.
If IP Address Mode (page 431) = Automatic this setpoint is inactive. The Subnet Mask is assigned by
the DHCP server.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

Gateway IP

ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] 0 .. 15 characters [-]
Default value 192.168.3.1 Force value NO
Step [-]
Comm object 24043 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if IP Address Mode (page 431) = Manual
Description
This setpoint is used to select the method how the Gateway IP is adjusted.
If IP Address Mode (page 431) = Manual, this setpoint is used to adjust the Gateway IP address of the
Ethernet 3 (page 19) interface of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 431) = Automatic this setpoint is inactive. The Gateway IP address is
assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or Internet.
Note: Only valid IP address can be inserted.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 433


Subgroup: Modbus Settings

Modbus Type

ETH Interface 3 -
Setpoint group Related FW 1.5.0
Modbus
Range [units] Modbus Client / Modbus Server / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 23868 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables the Modbus Client or Server on the Modbus Interface.

6 back to List of setpoints

Modbus Client Inactivity Timeout

ETH Interface 1 -
Trusted
ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
ETH Interface 3 -
Modbus
Range [units] 0 .. 65535 [s]
Default value 60 s Force value NO
Step 1s
Comm object 24097 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Modbus connection (TCP socket) is closed by controller, if a Modbus client does not communicate for
this time.
Note: This setpoint is shared with other Modbus Client Inactivity Timeout setpoints.

6 back to List of setpoints

Group: BESS settings

Subgroup: Inverter Precharge Settings

InteliNeo 6000 1.5.0 Global Guide 434


BESS Precharge Type

Setpoint group BESS settings Related FW 1.5.0


Range [units] AC / DC [-]
Default value AC Force value YES
Step [-]
Comm object 16428 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjust Controller's behavior during BESS Precharge Sequence.

The BESS inverter cannot produce AC voltage on its output without being
connected to the healthy bus. The BESS must be precharged by AC voltage
AC Precharge
for time given by the setpoint Precharge Time (page 1). The BCB is allowed
to be closed only if the bus is helthy.
The BCB is allowed to be closed and connect healthy output of the BESS to
DC Precharge the dead bus. But If the bus is healthy and output of the BESS inverter is dead,
BCB cannot be closed.

6 back to List of setpoints

BESSReady to Load TO

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. 3600 [s]
Default value 30 s Force value YES
Step 1s
Comm object 16478 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts maximal waiting time for LBI BESS READY TO LOAD (PAGE 995) after the Prestart
Time (page 1) elapsed. If the LBI BESS READY TO LOAD (PAGE 995) is not configured the BCB is closed
after this timer elapsed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 435


Subgroup: BESS P Control

BESS P request source

Setpoint group BESS settings Related FW 1.5.0


Range [units] Analog/Setpoint/Balance
Default value Setpoint Force value YES
Step
Comm object 20269 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints defines the source for the BESS power output request.
See more information in the chapter BESS Charging/Discharging Control (page 239).

The controller receives a BESS P REQUEST (PAGE 1116) from the LAI
Analog
BESS P REQUEST (PAGE 1116) which is used as direct BESS Power Request.
The value of BESS P REQUEST (PAGE 1116) is given by setpoints BESS Charge
Setpoint
Power (page 436) or BESS Discharge Power (page 437).
The BESS P REQUEST (PAGE 1116) is calculated using internal controller's
Balance
algorithms. This calculation maintain the balance of energy flow trough the system.

6 back to List of setpoints

BESS Charge Power

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. Nominal power (page 375) [kW]
Default value 100 kW Force value YES
Step 1 kW
Comm object 13930 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the required charge power during the charging process. Charging process is
displayed as negative power.
Note: Note: The setpoint is inactive when LBI BATT DISCHARGE ENABLE (PAGE 989) is not active.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 436


BESS Discharge Power

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. Nominal power (page 375) [kW]
Default value 100 kW Force value YES
Step 1 kW
Comm object 13931 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Alwaysl
Description
This setpoint defines the required discharge power during the discharging process. Discharging process
is displayed as positive power.
Note: Note: The setpoint is inactive when LBI BATT DISCHARGE ENABLE (PAGE 989) is not active.

6 back to List of setpoints

Gen P Min

Setpoint group Curtailment Related FW 1.5.0


Range [units] 0 .. 100 [%] of nominal power of Gen-sets running in PM
20 % of nominal power of
Default value Force value YES
Gen-sets running in PM
Step 1 % of nominal power of Gen-sets running in PM
Comm object 14384 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
In long term the Gen-sets have to operate on some minimal power level. This setpoint set the minimal
relative power level of Gen-sets working in power management.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 437


Subgroup: BESS Q Control

BESS Q request source

Setpoint group BESS settings Related FW 1.5.0


Range [units] Analog/Balance
Default value Balance Force value YES
Step
Comm object 20174 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints defines the source which will be used for PF/Q regulations.
See more information in the chapter BESS/PV PF/Q Control (page 247).

The reactive power is regulated according to the the LAI BESS Q REQUEST (PAGE
Analog
1116) which is used as direct BESS Power Request.
The PF of the BESS is regulated so the Gen-sets (system) has the constant PF
Balance
which is defined by the setpoint Gensets PF Required (page 438).

6 back to List of setpoints

Gensets PF Required

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0.001 .. 1.999
Default value 1.000 Force value YES
Step 0.001
Comm object 20173 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints defines the PF which is required from Gen-sets (system). The BESS will regulate its PF so
it covers peaks and the Gen-sets has constant PF.
Note: This setpoint applies only if the BESS Q request source (page 438) = Balance.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 438


Subgroup: SOC Control

SOC High Target

Setpoint group BESS settings Related FW 1.5.0


Range [units] 50 .. 100 [%] of BESS Nominal Capacity (page 716)
80 % of BESS Nominal
Default value Force value YES
Capacity (page 716)
Step 1 % of BESS Nominal Capacity (page 716)
Comm object 20266 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the relative maximal state of charge of the BESS. The value BESS SOC (page
716) cannot exceed this limit.
See the chapter State of Charge (page 240) for more information.

6 back to List of setpoints

SOC High Hysteresis

Setpoint group BESS settings Related FW 1.5.0


Range [units] 50 .. 80 [%] of BESS Nominal Capacity (page 716)
70 % of BESS Nominal
Default value Force value YES
Capacity (page 716)
Step 1 % of BESS Nominal Capacity (page 716)
Comm object 20268 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the relative level under which the value BESS SOC (page 716) must drop so the
charging process can be activated again .
See the chapter State of Charge (page 240) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 439


SOC Low Target

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. 50 [%] of BESS Nominal Capacity (page 716)
20 % of BESS Nominal
Default value Force value YES
Capacity (page 716)
Step 1 % of BESS Nominal Capacity (page 716)
Comm object 20265 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the relative minimal state of charge of the BESS. The value BESS SOC (page 716)
cannot drop under this limit.
See the chapter State of Charge (page 240) for more information.

6 back to List of setpoints

SOC Low Hysteresis

Setpoint group BESS settings Related FW 1.5.0


Range [units] 20 .. 50 [%] of BESS Nominal Capacity (page 716)
30 % of BESS Nominal
Default value Force value YES
Capacity (page 716)
Step 1 % of BESS Nominal Capacity (page 716)
Comm object 20267 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the relative level under which the value BESS SOC (page 716) must exceed so the
discharging process can be activated again .
See the chapter State of Charge (page 240) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 440


Subgroup: Battery Cycles

Max Battery Cycles Per Day

Setpoint group BESS settings Related FW 1.5.0


Range [units] OFF; 1 .. 250 [-]
Default value 2 Force value YES
Step 1
Comm object 20225 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to define the maximal daily number of battery cycles.
See the chapter Daily Battery Cycles Control (page 241) for more information.

6 back to List of setpoints

Subgroup: Starting Timers

Minimal Stabilization Time

Setpoint group BESS settings Related FW 1.5.0


Range [units] 1 .. Maximal Stabilization Time (page 442) [s]
Default value 2s Force value YES
Step 1s
Comm object 8259 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if BESS Precharge Type (page 435) = DC
Description
After the BESS has been started. The controller will wait for a period adjusted by this setpoint before
closing BCB, even if the BESS voltage and frequency are already in limits.
Note: This setpoint is relevant only if BESS Precharge Type (page 435) = DC.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 441


Maximal Stabilization Time

Setpoint group BESS settings Related FW 1.5.0


Range [units] Minimal Stabilization Time (page 441) .. 3600 [s]
Default value 10 s Force value YES
Step 1s
Comm object 8313 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if BESS Precharge Type (page 435) = DC
Description
After the BESS has been started. The BESS voltage and frequency must get within limits within this
period of time, otherwise an appropriate shutdown alarm (BESS voltage and/or frequency) is issued.
Note: This setpoint is relevant only if BESS Precharge Type (page 435) = DC.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 442


Run Only Block Delay 1

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 5.0 Force value YES
Step 0.1
Related
Comm object 10023 MINT, MPTM
applications
Config level Advanced
Setpoint visibility Always
Description
This setpoint influences the blocking condition if any protection is configured with blocking condition "Run
Only Block Delay 1". The protection blocking is based on the operating state of the BESS state machine.
Once the BESS state machine reaches the "Running" state, the protection with this blocking is unblocked
after this delay elapses.

Image 7.3 Run Only Block Delay 1

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 443


Run Only Block Delay 2

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 5.0 Force value YES
Step 0.1
Comm object 10024 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint influences the blocking condition if any protection is configured with blocking condition "Run
Only Block Delay 2". The protection blocking is based on the operating state of the BESS state machine.
Once the BESS state machine reaches the "Running" state, the protection with this blocking is unblocked
after this delay elapses.

Image 7.4 Run Only Block Delay 2

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 444


Run Only Block Delay 3

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0.0 .. 600.0
Default value 5.0 Force value YES
Step 0.1
Comm object 10025 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint influences the blocking condition if any protection is configured with blocking condition "Run
Only Block Delay 3". The protection blocking is based on the operating state of the BESS state machine.
Once the BESS state machine reaches the "Running" state, the protection with this blocking is unblocked
after this delay elapses.

Image 7.5 Run Only Block Delay 3

6 back to List of setpoints

Subgroup: Stopping Timers

Stop Time

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. 1200 [s]
Default value 60 s Force value YES
Step 1s
Comm object 9815 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
Under normal conditions the BESS must certainly stop within this period.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 445


Subgroup: Power Switch

Power Switch On

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. 32 000 [kW] (depends on the selected Power Formats And Units (page 196))
100 kW (depends on the selected Power
Default value Force value YES
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
MINT,
Comm object 11658 Related applications
MPTM
Config level Advanced
Setpoint visibility Only if LBO POWER SWITCH (PAGE 1098) is configured
Description
Threshold level for switching the LBO POWER SWITCH (PAGE 1098) on.

6 back to List of setpoints

Power Switch Off

Setpoint group BESS settings Related FW 1.5.0


Range [units] 0 .. 32 000 [kW] (depends on the selected Power Formats And Units (page 196))
50 kW (depends on the selected Power
Default value Force value YES
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
MINT,
Comm object 11659 Related applications
MPTM
Config level Advanced
Setpoint visibility Only if LBO POWER SWITCH (PAGE 1098) is configured
Description
Threshold level for switching the LBO POWER SWITCH (PAGE 1098) off.

6 back to List of setpoints

Group: BESS Protections

Subgroup: Overload Protection

2POverload Start Evaluation Level

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 100 .. 200 [%] of Nominal power (page 375)
150 % of Nominal
Default value Force value YES
power (page 375)
Step 1 % of Nominal power (page 375)
Comm object 8280 Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 446


Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the relative power level, where the thermal overload protection starts to be
evaluated. See setpoint IDMT Overload Protection (page 570)for complete explanation of the
protection.

Load Reaction time


level [s] 2POvrldStEvDel 5s
100 no reaction OverldStrtEval 150 %
110 no reaction
120 600
130 60
140 30
150 20
160 15
170 12
180 10
190 8.6
200 7.5
210 6.7
220 6
230 5.5
240 5
250 4.6
The reaction time of the thermal overload protection is not fixed and is specified by the parameter
2POverload Start Evaluation Delay (page 447).
Note: Maximum reaction time is 3600 s after this time the protection is tripped.

6 back to List of setpoints

2POverload Start Evaluation Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.1 .. 600.0 [s]
Default value 5.0 s Force value YES
Step 0.1 s
Comm object 8281 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the default delay for the thermal overload protection. See setpoint IDMT Overload

InteliNeo 6000 1.5.0 Global Guide 447


Protection (page 570) for complete explanation of the protection.

Load Reaction time


level [s]
2POvrldStEvDel 5s
100 no reaction
OverldStrtEval 150 %
110 no reaction
3600 (max.
120
value)
130 60
140 30
150 20
160 15
170 12
180 10
190 8.6
200 7.5
210 6.7
220 6
230 5.5
240 5
250 4.6
The reaction time of the thermal overload protection is not fixed; it depends on how much is the load
above the limit of 2POverload Start Evaluation Level (page 446). The higher is the load the shorter
the reaction time will be.

6 back to List of setpoints

Subgroup: Current Protection

Short Circuit

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 100 .. 500 [%] of Nominal Current (page 376)
150 % of Nominal Current (page
Default value Force value NO
376)
Step 1 % of Nominal Current (page 376)
Comm object 8282 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the relative current threshold level for Short Circuit Protection (page 571).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 448


Short Circuit Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.00 .. 10.00 [s]
Default value 0s Force value NO
Step 0.01 s
Comm object 9991 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint specifies the delay for Short Circuit Protection (page 571).

6 back to List of setpoints

IDMT BESS >A Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 1.0 .. 600.0 [s]
Default value 4.0 s Force value NO
Step 0.1 s
Comm object 8283 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the delay for IDMT BESS >A Protection (page 571).
IDMT curve shape selection. IDMT Overcurrent Delay is a reaction time of IDMT protection for 200%
overcurrent IBESS =2*Nominal Current (page 376)
IDMT is “very inverse” over current protection. Reaction time is not constant but depends on over current
level according to the following formula:

Note: Reaction time is limited to 3600 s = 60 minutes. IDMT protection is not active for Reaction time
values longer than 60 minutes.

IBESS is maximal value of all measured phases of BESS current.


Table 7.1 EXAMPLE of Reaction time for different over current levels
Overcurrent
Overcurrent IDMT Delay
≤ 100 % 101 % 110 %
0,2 s No action 20 s 2s
Reaction time 2s No action 200 s 20 s
20 s No action 2000 s 200 s

InteliNeo 6000 1.5.0 Global Guide 449


Image 7.6 IDMT Overcurrent Delay
6 back to List of setpoints

BESS Current Unbalance

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 1 .. 200 [%] of Nominal power (page 375)
50 % of Nominal
Default value Force value NO
power (page 375)
Step 1 % of Nominal power (page 375)
Comm object 8284 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Connection type (page 378) != MonoPhase
Description
This setpoint specifies the relative current threshold level for BESS Current Unbalance Protection
(page 573).

6 back to List of setpoints

BESS Current Unbalance Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 5.0 s Force value NO
Step 0.1 s
Comm object 8285 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Connection type (page 378) != MonoPhase
Description
This setpoint specifies the delay for BESS Current Unbalance Protection (page 573).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 450


Subgroup: Voltage Protection

BESS >V

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20818 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS >V Protection.
Protection is enabled. Behavior of protection is adjusted via setpoints BESS >VUndervoltage (page 1)
and BESS >V Delay (page 452). When BESS voltage exceeds limit set by BESS >VUndervoltage
(page 1) for time longer than BESS >V Delay (page 452) appropriate alarm is activated.

Value Alarm
BESS Voltage L1-N (page 713) Sd BESS >V L1-N (page 1283)
BESS Voltage L2-N (page 713) Sd BESS >V L2-N (page 1283)
BESS Voltage L3-N (page 713) Sd BESS >V L3-N (page 1283)
BESS Voltage L1-L2 (page 713) Sd BESS >V L1-L2 (page 1283)
BESS Voltage L2-L3 (page 714) Sd BESS >V L2-L3 (page 1284)
BESS Voltage L3-L1 (page 714) Sd BESS >V L3-L1 (page 1284)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 451


BESS >V Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.01 .. 600 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 8292 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the delay for BESS >V (page 574).

6 back to List of setpoints

BESS >>V

Setpoint group BESS Protections Related FW 1.5.0


Generator >V (page 1) .. 150 [%] of BESS Nominal Voltage Ph-N (page 380)
Range [units]
and BESS Nominal Voltage Ph-Ph (page 380)
150 % of BESS Nominal Voltage Ph-N
Default value (page 380) and BESS Nominal Force value YES
Voltage Ph-Ph (page 380)
1 % of BESS Nominal Voltage Ph-N (page 380) and BESS Nominal Voltage
Step
Ph-Ph (page 380)
Comm object 10013 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the relative voltage threshold level for BESS >>V Protection (page 575).
Note: BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713), BESS Voltage L3-N
(page 713), BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and BESS
Voltage L3-L1 (page 714) are used for this protection.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 452


BESS >>V Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.01 .. 600 [s]
Default value 0.10 s Force value YES
Step 0.01 s
Comm object 16416 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the delay for BESS >>V Protection (page 575).

6 back to List of setpoints

BESS <V

Setpoint group BESS Protections Related FW 1.5.0


20 .. 99 [%] of BESS Nominal Voltage Ph-N (page 380) and BESS Nominal
Range [units]
Voltage Ph-Ph (page 380)
90 % of BESS Nominal Voltage Ph-N
Default value (page 380) and BESS Nominal Force value YES
Voltage Ph-Ph (page 380)
1 % of BESS Nominal Voltage Ph-N (page 380) and BESS Nominal Voltage
Step
Ph-Ph (page 380)
Comm object 8293 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the relative voltage threshold level for BESS <V Protection (page 576).
Note: BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713), BESS Voltage L3-N
(page 713), BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and BESS
Voltage L3-L1 (page 714) are used for this protection.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 453


BESS <V Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.01 .. 600.00 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 16417 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the delay for BESS <V Protection (page 576).

6 back to List of setpoints

BESS V Unbalance

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 1 .. 200 [%]
Default value 10 % Force value YES
Step 1%
Comm object 8288 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Connection type (page 378) != MonoPhase
Description
This setpoint specifies the relative voltage threshold level for BESS V Unbalance Protection (page
576).

6 back to List of setpoints

BESS V Unbalance Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.01 .. 600.00 [s]
Default value 3.00 s Force value YES
Step 0.01 s
Comm object 8289 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Connection type (page 378) != MonoPhase
Description
This setpoint specifies the delay for BESS V Unbalance Protection (page 576).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 454


Subgroup: Frequency Protection

BESS >f

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.00 .. 50.00 [Hz]
Default value 1.50 Hz Force value YES
Step 0.01 Hz
Comm object 8296 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts maximal accepted frequency for BESS >f Protection (page 584).
IMPORTANT: When Application Mode (page 885) = MINT this setpoint also specifies the
maximal accepted frequency for Bus >f Protection.

Note: fmax = Nominal Frequency (page 384) + BESS >f

6 back to List of setpoints

BESS >f Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.01 .. 600.0 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 8297 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the delay for BESS >f Protection (page 584).
IMPORTANT: When Application Mode (page 885) = MINT this setpoint also specifies the
maximal accepted frequency for Bus >f Protection.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 455


BESS <f

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.00 .. 50.00 [Hz]
Default value 1.50 Hz Force value YES
Step 0.01 Hz
Comm object 14588 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts maximal accepted frequency for BESS <f Protection (page 585).
IMPORTANT: When Application Mode (page 885) = MINT this setpoint also specifies the
maximal accepted frequency for Bus <f Protection.

Note: fmin = Nominal Frequency (page 384) - BESS <f

6 back to List of setpoints

BESS <f Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.01 .. 600.0 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 16423 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the delay for BESS <f Protection (page 585).
IMPORTANT: When Application Mode (page 885) = MINT this setpoint also specifies the
maximal accepted frequency for Bus <f Protection.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 456


Subgroup: Bus Meas Error

Bus Meas Error

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 10558 Related applications MINT
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint enables or disables Bus Measurement Error protection.
Alarm Stp Bus Meas Error (page 1290) is activated if controller detects a mismatch between the
expected and currently measured voltage on the bus for period longer than 20 s. Mismatch means that
measured voltage is lower/higher than Bus Dead Level (page 383), although the controller receives
information about closed/opened breaker.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

Subgroup: Earth Fault Current Protection

IDMT Earth Fault Current Sd

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0 .. 1000 [A]
Default value 10 A Force value YES
Step 1 [A]
Comm object 11632 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the current threshold level for Earth Fault Current Protection (page 592).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 457


IDMT Earth Fault Current Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0.1 .. 600.0 [s]
Default value 0.1 s Force value YES
Step 0.1 s
Comm object 11633 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint specifies the delay for Earth Fault Current Protection (page 592).

6 back to List of setpoints

Subgroup: SOC Protection

BESS <f Delay

Setpoint group BESS Protections Related FW 1.5.0


Range [units] SOC Critical Low (page 459) .. 50 [%] of BESS Nominal Capacity (page 716)
Default value 10 % of BESS Nominal Capacity (page 716) Force value YES
Step 1 % of BESS Nominal Capacity (page 716)
Related MINT,
Comm object 20263
applications MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint specifies the relative state of charge threshold level for BESS <SOC Protection (page
598).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 458


SOC High Alarm

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 50 .. SOC Critical High (page 460) [%] of BESS Nominal Capacity (page 716)
90 % of
Default value BESS Nominal Force value YES
Capacity (page 716)
Step 1 % of BESS Nominal Capacity (page 716)
Comm object 20264 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint specifies the relative state of charge threshold level for BESS >SOC Protection (page
598).

6 back to List of setpoints

SOC Critical Low

Setpoint group BESS Protections Related FW 1.5.0


Range [units] 0 .. BESS <f Delay (page 458) [%] of BESS Nominal Capacity (page 716)
Default value 5 % of BESS Nominal Capacity (page 716) Force value YES
Step 1 % of BESS Nominal Capacity (page 716)
Related MINT,
Comm object 20261
applications MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint specifies the relative state of charge threshold level for BESS <<SOC Protection (page
599).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 459


SOC Critical High

Setpoint group BESS Protections Related FW 1.5.0


Range [units] SOC High Alarm (page 459) .. 120 [%] of BESS Nominal Capacity (page 716)
Default value 100 % of BESS Nominal Capacity (page 716) Force value YES
Step 1 % of BESS Nominal Capacity (page 716)
Related MINT,
Comm object 20262
applications MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint specifies the relative state of charge threshold level for BESS >>SOC Protection (page
599).

6 back to List of setpoints

Group: PV Settings

Subgroup: PF Control

PV Power Factor Request

Setpoint group PV Related FW 1.5.0


Range [units] 0.001 .. 1.999
Default value 1.000 Force value YES
Step 0.001
Comm object 20185 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Required power factor of the PV in parallel to mains operation.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 460


Subgroup: PV Areas

PV Array Area 1

Setpoint group PV Related FW 1.5.0


2
Range [units] 0 .. 32000 [m ]
Default value 0 Force value YES
Step 1
Comm object 19557 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Defines the area and target energy output for the PV array 1 and is associated with the LAI: IRRADIATION
OF PV ARRAY 1 (PAGE 1122).

6 back to List of setpoints

PV Array Area 2

Setpoint group PV Related FW 1.5.0


2
Range [units] 0 .. 32000 [m ]
Default value 0 Force value YES
Step 1
Comm object 19558 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Defines the area and target energy output for the PV array 2 and is associated with the LAI: IRRADIATION
OF PV ARRAY 2 (PAGE 1122).

6 back to List of setpoints

PV Array Area 3

Setpoint group PV Related FW 1.5.0


2
Range [units] 0 .. 32000 [m ]
Default value 0 Force value YES
Step 1
Comm object 19559 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Defines the area and target energy output for the PV array 3 and is associated with the LAI: IRRADIATION
OF PV ARRAY 3 (PAGE 1123).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 461


PV Array Area 4

Setpoint group PV Related FW 1.5.0


2
Range [units] 0 .. 32000 [m ]
Default value 0 Force value YES
Step 1
Comm object 19560 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Defines the area and target energy output for the PV array 4 and is associated with the LAI: IRRADIATION
OF PV ARRAY 4 (PAGE 1123).

6 back to List of setpoints

Subgroup: PV Calibration Offset

PV Calib. Offset 1

Setpoint group PV Related FW 1.5.0


Range [units] -32000 .. 32000 [kW]
Default value 0 Force value YES
Step 1
Comm object 19561 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This parameter represents the correction offset for PV Array 1 in kilowatts (kW). The value of this
correction can be either positive or negative and is used to correct the output of PV Array 1.

6 back to List of setpoints

PV Calib. Offset 2

Setpoint group PV Related FW 1.5.0


Range [units] -32000 .. 32000 [kW]
Default value 0 Force value YES
Step 1
Comm object 19562 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This parameter represents the correction offset for PV Array 2 in kilowatts (kW). The value of this
correction can be either positive or negative and is used to correct the output of PV Array 2.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 462


PV Calib. Offset 3

Setpoint group PV Related FW 1.5.0


Range [units] -32000 .. 32000 [kW]
Default value 0 Force value YES
Step 1
Comm object 19563 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This parameter represents the correction offset for PV Array 3 in kilowatts (kW). The value of this
correction can be either positive or negative and is used to correct the output of PV Array 3.

6 back to List of setpoints

PV Calib. Offset 4

Setpoint group PV Related FW 1.5.0


Range [units] -32000 .. 32000 [kW]
Default value 0 Force value YES
Step 1
Comm object 19564 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This parameter represents the correction offset for PV Array 4 in kilowatts (kW). The value of this
correction can be either positive or negative and is used to correct the output of PV Array 4.

6 back to List of setpoints

Group: WT Settings

Subgroup: PF Control

WT Power Factor Request

Setpoint group WT Settings Related FW 1.5.0


Range [units] 0.001 .. 1.999
Default value 1.000 Force value YES
Step 0.001
Comm object 19174 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Required power factor of the WT in parallel to mains operation.

InteliNeo 6000 1.5.0 Global Guide 463


6 back to List of setpoints

Group: Curtailment

Subgroup: Curtailment

Curtailment

Setpoint group Curtailment Related FW 1.5.0


Range [units] Enabled/Disabled
Default value Enabled Force value YES
Step
Comm object 20243 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints enables the function PV Curtailment (page 295) used to regulate power of the PV
according to the PI regulation loop when the actual power of Gen-sets goes below Gen P Min (page
465) or when SOC reaches the setpoint SOC High Target (page 439).

6 back to List of setpoints

Gain

Setpoint group Curtailment Related FW 1.5.0


Range [units] 0,0 .. 200,0 [-]
Default value 10,00 Force value YES
Step 0,01
Comm object 20245 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints adjust the gain factor of PI curtailment regulation.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 464


Int

Setpoint group Curtailment Related FW 1.5.0


Range [units] 0,10 .. 60,00 [-]
Default value 10,00 s Force value YES
Step 0,01 s
Comm object 20244 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints adjust the int factor of PI curtailment regulation.

6 back to List of setpoints

Gen P Min

Setpoint group Curtailment Related FW 1.5.0


Range [units] 0 .. 100 [%] of nominal power of Gen-sets running in PM
20 % of nominal power of
Default value Force value YES
Gen-sets running in PM
Step 1 % of nominal power of Gen-sets running in PM
Comm object 14384 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
In long term the Gen-sets have to operate on some minimal power level. This setpoint set the minimal
relative power level of Gen-sets working in power management.

6 back to List of setpoints

Subgroup: PW/WT Ramp

PV/WT Ramp Up

Setpoint group Curtailment Related FW 1.5.0


Range [units] OFF; 1 .. 1800 [s]
Default value 20 Force value YES
Step 1
Comm object 19603 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Defines the maximal rate of rise of the value Curtailment Output.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 465


PV/WT Ramp Down

Setpoint group Curtailment Related FW 1.5.0


Range [units] OFF; 1 .. 1800 [s]
Default value OFF Force value YES
Step 1
Comm object 19604 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Defines the maximal rate of fall of the value Curtailment Output.

6 back to List of setpoints

Group: Frequency/Load Control

Subgroup: Frequency Control

Frequency Regulator Character

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] Positive / Negative [-]
Default value Positive Force value YES
Step [-]
Comm object 9054 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects the characteristic of the Frequency Regulator Output (page 862). Adjust it
according to the behavior of the BESS inverter.

Raising the voltage on the BESS inverter regulator causes BESS frequency
Positive
to rise.
Raising the voltage on the BESS inverter regulator causes BESS frequency
Negative
to go down.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 466


Frequency Governor Bias

Setpoint group Speed/Load Control Related FW 1.5.0


Frequency Governor Low Limit (page 467) .. Frequency Governor High Limit
Range [units]
(page 467) [-]
Default value 0,00 V Force value YES
Step 0,01 V
Comm object 8656 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the initial voltage level for the Frequency Regulator Output (page 862). This level
is present on the output, if no speed or power regulation loop is active.

6 back to List of setpoints

Frequency Governor Low Limit

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] -10,00 .. Frequency Governor High Limit (page 467) [V]
Default value -10,00 V Force value YES
Step 0,01 V
Comm object 10115 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
The low limit of the Frequency Regulator Output (page 862).
Use this setpoint to adjust the regulator output range according to your BESS inverter regulator.

6 back to List of setpoints

Frequency Governor High Limit

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] Frequency Governor Low Limit (page 467) .. 10,00 [V]
Default value 10,00 V Force value YES
Step 0,01 V
Comm object 10559 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Upper limit of the speed Frequency Regulator Output (page 862).
Use this setpoint to adjust the regulator output range according to your BESS inverter regulator.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 467


Tau Frequency Governor Actuator

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 1,0 .. 300,0 [s]
Default value 10,0 s Force value YES
Step 0,1 s
Comm object 10784 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to adjust the transformation ratio of the Frequency Regulator Output (page 862)
to the pulses at the binary outputs FREQUENCY UP (PAGE 1081) and FREQUENCY DOWN (PAGE 1081).
Adjust the setpoint to the pulse duration which is needed for the regulator of BESS inverter to
regulatefrom minimal position to the maximal position.

6 back to List of setpoints

BESS Frequency Droop Slope

Frequency/Load
Setpoint group Related FW 1.5.0
Control
Range [units] 0 .. 20 [%]
Default value 2 Force value NO
Step 0.01
Comm object 19450 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the slope of the load droop correlation. The slope is set as a droop of frequency in
percentages of the requested system frequency (Nominal Frequency (page 384)) on the range of the
requested power from 0 to 100% of Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 468


Subgroup: Regulation Loops

Frequency Regulation Loop

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] Sync Only / All The Time [-]
Default value Sync Only Force value YES
Step [-]
Comm object 9891 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects when the frequency regulation loop is active.
SYNC ONLY: The frequency regulation loop is active only during synchronizing to match the
BESS, Mains, or Bus frequencies together. It is assumed that in all other situations where the
frequency is to be regulated the BESS governor maintains itself.
ALL THE TIME: This option activates the frequency regulation loop also while the BESS is
running without load and during the island operation. The controller maintains frequency at its
nominal value adjusted by setpoint Nominal Frequency (page 384).
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

Frequency Gain

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,00 .. 200,00 [-]
Default value 10,00 [-] Force value YES
Step 0,01 [-]
Comm object 8715 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the gain factor (P-factor) of the frequency control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 469


Frequency Int

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,10 .. 60,00 [s]
Default value 2,00 [s] Force value YES
Step 0,01 [s]
Comm object 8716 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the integration factor (I-factor) of the frequency control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

Angle Gain

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,00 .. 200,00 [-]
Default value 10,00 [-] Force value YES
Step 0,01 [-]
Comm object 8718 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for adjusting of the gain factor (P-factor) of the phase angle P-control loop.
Note: During synchronization, first the frequency loop is started to match the BESS frequency with
the Mains or bus and after that the phase angle loop is started to match the phase angle.

Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 470


Load Gain

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,00 .. 200,00 [-]
Default value 10,00 [-] Force value YES
Step 0,01 [-]
Comm object 8659 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the gain factor (P-factor) of the load control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

Load Int

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,10 .. 60,00 [s]
Default value 2,00 [s] Force value YES
Step 0,01 [s]
Comm object 8713 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the integration factor (I-factor) of the load control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 471


Load Sharing Gain

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,00 .. 200,00 [-]
Default value 10,00 [-] Force value YES
Step 0,01 [-]
Comm object 8725 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the gain factor (P-factor) of the load sharing control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

Load Sharing Int

Setpoint group Speed/Load Control Related FW 1.5.0


Range [units] 0,10 .. 60,00 [s]
Default value 2,00 [s] Force value YES
Step 0,01 [s]
Comm object 9035 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the integration factor (I-factor) of the load sharing control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 472


Subgroup: Load Transfer

Close Transfer Max Duration

Setpoint group Process Control Related FW 1.5.0


Range [units] < 0,1 = 0,0; 0,1 .. 600,0 [s]
Default value 5,0 s Force value YES
Step 0,1 s
Comm object 8661 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
The time of parallel work of BESS and Mains in close transition. Physical time of close transfer is always
longer than this setpoint (it takes time to detect the closing of the breaker, etc.).

6 back to List of setpoints

Open Transfer Min Break

Setpoint group Process Control Related FW 1.5.0


Range [units] < 0,1 = 0,0; 0,1 .. 600,0 [s]
Default value 1,0 s Force value YES
Step 0,1 s
Comm object 8303 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
Minimal duration of break in open transition when Transfer BESS To Mains (page 475) or Transfer
Mains To BESS (page 474) is chosen as open transfer.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 473


Transfer Mains To BESS

Setpoint group Process Control Related FW 1.5.0


Range [units] Open / Close Only / Close Prim / SoftTransf [-]
Default value SoftTransf Force value YES
Step [-]
Comm object 12969 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint defines the type of transfer of load from Mains to BESS.

Transfer of the load from Mains to BESS without parallel work and
synchronization (one breaker opens and second is closed - checking
Open
feedbacks). The setpoint Open Transfer Min Break (page 473) sets the
minimal duration of break.
Transfer of the load from Mains to BESS with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Only
Duration (page 473).
In case of synchronization fail, MCB stays close and BESS is stopped.
Transfer of the load from Mains to BESS with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Prim
Duration (page 473).
In case of synchronization fail, open transfer is done.
Transfer of the load from Mains to BESS with parallel work and soft loading of
the BESS. This function is proceeded like the closed transfer, but there is time
limitation of loading of theBESS adjusted via setpoint Load Ramp (page
SoftTransf
477). The transfer is succeed only when theBESS is fully loaded – Mains is
fully unloaded (level of load when Mains is considered as unloaded is adjusted
via setpoint Mains Unload MCB Open Window (page 476)).

Note: Close transfer of load is also affected by setpoint Mains Measurement P (page 364).

Note: The behavior of transition of load in MAN mode is adjusted via setpoint CB Control In MAN
Mode (page 362).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 474


Transfer BESS To Mains

Setpoint group Process Control Related FW 1.5.0


Range [units] Open / Close Only / Close Prim / SoftTransf [-]
Default value SoftTransf Force value YES
Step [-]
Comm object 14688 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint defines the type of transfer of load from BESS to Mains.

Transfer of the load from BESS to Mains without parallel work and
synchronization (one breaker opens and second is closed - checking
Open
feedbacks). The setpoint Open Transfer Min Break (page 473) sets the
minimal duration of break.
Transfer of the load from BESS to Mains with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Only
Duration (page 473).
In case of synchronization fail, BCB stays closed and BESS keeps running.
Transfer of the load from BESS to Mains with synchronization and parallel
work. The time of parallel work is given by setpoint Close Transfer Max
Close Prim
Duration (page 473).
In case of synchronization fail, open transfer is done.
Transfer of the load from BESS to Mains with parallel work and soft unloading
of the BESS. This function is proceeded like the closed transfer, but there is
time limitation of unloading of the BESS adjusted via setpoint Load Ramp
SoftTransf
(page 477). The transfer is succeed only when the BESS is fully unloaded
(level of load when BESS is considered as unloaded is adjusted via setpoint
Generator Unload BCBOpen Level (page 476)).

Note: The behavior of transition of load in SEM mode is adjusted via setpoint CB Control In MAN
Mode (page 362).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 475


Generator Unload BCBOpen Level

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 100 [%] of Nominal power (page 375) or Installed Power (page 375)
10 % of Nominal power (page 375) or
Default value Force value YES
Installed Power (page 375)
Step 1 % of Nominal power (page 375) or Installed Power (page 375)
Comm object 8547 Related applications MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the required value of the BESS P (page 707) related to Nominal power (page
375)/Installed Power (page 375) for opening the BCB breaker during unloading of the BESS.
Note: This setpoint is usually higher than 0 to prevent the BESS going to reverse power.

Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

Mains Unload MCB Open Window

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 100 [%] of Nominal power (page 375)
Default value 1 % of Nominal power (page 375) Force value YES
Step 1 % of Nominal power (page 375)
Comm object 14694 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the value which defines the level where the Mains is considered as unloaded. When
this window is reached and it is required to open MCB, the MCB will be opened and remaining load in the
window will be transfer to BESS.
IMPORTANT: If the window is set too high the Mains can be considered as unloaded
and MCB will be opened while there is not enough reserve power on BESS. This can
cause overload of BESS and blackout.

IMPORTANT: This window and the setpoint Minimal Power PTM (page 1) must be set in
the way where MCB opening will not be blocked by Minimal Power PTM level while all
available BESSs are running in Load Shar.

Note: This setpoint is window. It means that when you adjust this setpoint to 10%, there is window
from -10% to +10%. The reason is Import/Export function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 476


Load Ramp

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 600 [s]
Default value 200 s Force value YES
Step 1s
Comm object 8658 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the ramping time of BESS Required P (page 861) to BESS Required P Target
(page 861) while loading/unloading.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Example: Installed Power (page 375) = 20 kW, Load Ramp = 10 seconds. The ramp is changing
with speed 20 kW per 10 seconds (2 kW/s) to the zero value.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 477


Ramp Start Level

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 100 [%] of Nominal power (page 375) or Installed Power (page 375)
0 % of Nominal power (page 375)
Default value Force value YES
or Installed Power (page 375)
Step 1 % of Nominal power (page 375) or Installed Power (page 375)
Comm object 10912 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the load level at which the Load Ramp (page 477) starts after the BCB has been
closed.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 478


Soft Unload Ramp

Setpoint group Process Control Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16489 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the ramping time of the BESS Required P (page 861) to the BESS Required P
Target (page 861) while soft unloading when BCB is requested to be opened.
The Required P reach the zero value at the end of the timer. The ramping time is set for ΔP which is given
by the setpoint Installed Power (page 375) or by the setpoint Nominal power (page 375) if the
Installed Power is OFF.
Example: Installed Power (page 375) = 20 kW, Soft Unload Ramp = 10 seconds. The ramp is
changing with speed 20 kW per 10 seconds (2 kW/s) to the zero value.

Note: This setpoint is shared with Soft Unload Ramp (page 568)

6 back to List of setpoints

Group: Voltage/PF Control

Subgroup: Voltage Control

Voltage Regulator Character

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] Positive / Negative [-]
Default value Positive Force value YES
Step [-]
Comm object 9055 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects the characteristic of the Voltage Regulator Output (page 866). Adjust it according
to the behavior of the remote voltage input of the governor.

Raising the voltage on the remote voltage adjustment input causes the BESS
Positive
voltage to raise.
Raising the voltage on the remote voltage adjustment input causes the BESS
Negative
voltage to go down.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 479


Voltage Regulator Bias

Setpoint group Voltage/PF Control Related FW 1.5.0


Voltage Regulator Low Limit (page 480) .. Voltage Regulator High Limit (page
Range [units]
480) [V]
Default value 0,00 V Force value YES
Step 0,01 V
Comm object 8500 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the initial level for the Voltage Regulator Output (page 866). This level is present
on the output if no regulation loop is active.

6 back to List of setpoints

Voltage Regulator Low Limit

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] -10,00 .. Voltage Regulator High Limit (page 480) [V]
Default value -10,00 V Force value YES
Step 0,01 V
Comm object 14792 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Lower limit of the Voltage Regulator Output (page 866). Use this setpoint to adjust the governor output
range according to your governor type.

6 back to List of setpoints

Voltage Regulator High Limit

Setpoint group Synchronization Related FW 1.5.0


Range [units] Voltage Regulator Low Limit (page 480) .. 10,00 [V]
Default value 10,00 V Force value YES
Step 0,01 V
Comm object 14793 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Upper limit of the Voltage Regulator Output (page 866). Use this setpoint to adjust the governor output
range according to your governor type.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 480


Tau Voltage Regulator Actuator

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 1,0 .. 300,0 [s]
Default value 10,0 s Force value YES
Step 0,1 s
Comm object 10785 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to adjust the transformation ratio of the Voltage Regulator Output (page 866) to
the pulsesat the binary outputs VOLTAGE UP (PAGE 1110) and VOLTAGE DOWN (PAGE 1109).
Adjust the setpoint to the pulse duration which is needed for the regulator of BESS inverter to
regulatefrom minimal position to the maximal position.

6 back to List of setpoints

BESS Voltage Droop Slope

Frequency/Load
Setpoint group Related FW 1.5.0
Control
Range [units] 0 .. 20 [%]
Default value 1 Force value NO
Step 0.001
Comm object 19449 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the slope of the droop correlation. The slope is set as a droop of voltage in
percentages of the generator nominal voltage (BESS Nominal Voltage Ph-N (page 380)) on the range
of the requested reactive power from 0 to 100% of nominal reactive power (value of nominal reactive
power is not given by setpoint but it is calculated from setpoint BESS Nominal Voltage Ph-Ph (page
380) whilst the PF=0,8).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 481


Subgroup: Regulation Loops

Voltage Gain

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 0.00 .. 200.00 [-]
Default value 10.00 [-] Force value YES
Step 0.01 [-]
Comm object 8501 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the gain factor (P-factor) of the voltage control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

Voltage Int

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 0.10 .. 60.00 [s]
Default value 2.00 [s] Force value YES
Step 0.01 [s]
Comm object 8720 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the integration factor (I-factor) of the voltage control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 482


PF Gain

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 0.00 .. 200.00 [-]
Default value 10.00 [-] Force value YES
Step 0.01 [-]
Comm object 8503 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the gain factor (P-factor) of the PF control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

PF Int

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 0.10 .. 60.00 [s]
Default value 2.00 [s] Force value YES
Step 0.01 [s]
Comm object 8721 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the integration factor (I-factor) of the PF control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 483


VAr Sharing Gain

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 0.00 .. 200.00 [-]
Default value 10.00 [-] Force value YES
Step 0.01 [-]
Comm object 8777 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the gain factor (P-factor) of the VAr sharing control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

VAr Sharing Int

Setpoint group Voltage/PF Control Related FW 1.5.0


Range [units] 0.10 .. 60.00 [s]
Default value 2.00 [s] Force value YES
Step 0.01 [s]
Comm object 9036 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the integration factor (I-factor) of the VAr sharing control PI loop.
Note: See the chapter Regulation Loops (page 295) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 484


Group: Synchronization

Subgroup: Synchronization

Synchronization Type

Setpoint group Synchronization Related FW 1.5.0


Range [units] PhaseMatch / SlipSynchr [-]
Default value PhaseMatch Force value YES
Step [-]
Comm object 14802 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the type of Synchronization (page 249).
PhaseMatch
This type of synchronization is based on voltage and phase shift match. Limits are adjusted via
setpoints Voltage Window (page 486) and Phase Window (page 487). When voltage and phase
shift match the breaker close command is sent after Dwell Time (page 487) is elapsed.
SlipSynchr
This type of synchronization regulates the voltage to match Voltage Window (page 486) and BESS
Frequency (page 713) to match theMains/Bus Frequency (page 839) +Slip Frequency (page
488). When this frequency is reached, Dwell Time (page 487) starts to be counted down and when
elapses, breaker close command is sent.
IMPORTANT: The breaker close command is sent in advance due to breaker latency
which is set via setpoint BCB Latency (page 488) / MCB Latency (page 489).

Note: Synchronization is not allowed if there is any already synchronized Mains Controller in the
control group.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 485


Synchronization Timeout

Setpoint group Synchronization Related FW 1.5.0


Range [units] 1 .. 1800 [s] / No Timeout
Default value 60 s Force value YES
Step 1s
Comm object 8657 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the maximum duration of Synchronization (page 249).
Note: If this setpoint is adjusted to No Timeout then automatic restart of synchronization occurs
every 180s. This method helps to synchronize successfully even in difficult conditions.

6 back to List of setpoints

Voltage Window

Setpoint group Synchronization Related FW 1.5.0


Range [units] 0.0 .. 100.0 [%]
Default value 10.0 % Force value YES
Step 0.1 %
Comm object 8650 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the maximal AC Voltage difference between respective phases of Mains/Bus and
BESS for Synchronization (page 249). (BESS Voltage L1-N (page 713), Mains/Bus Voltage L1-N
(page 839), BESS Voltage L2-N (page 713),Mains/Bus Voltage L2-N (page 839), …)

6 back to List of setpoints

BESS to Mains/Bus Phase Shift

Setpoint group Synchronization Related FW 1.5.0


Range [units] -120 .. 120 [°]
Default value 0° Force value YES
Step 1°
Comm object 9578 Related applications MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to compensate phase shift which is caused by transformer.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 486


Phase Window

Setpoint group Synchronization Related FW 1.5.0


Range [units] 0 .. 90 [°]
Default value 10 ° Force value YES
Step 1°
Comm object 8652 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Synchronization Type (page 485) = PhaseMatch
Description
This setpoint adjusts the maximal Slip Angle (page 717) for Synchronization (page 249).
In order to disable breaker close command, adjust this setpoint to 0. Synchronization procedure will be
active for Synchronization Timeout (page 486) or until breaker is closed from an external device.

6 back to List of setpoints

Dwell Time

Setpoint group Synchronization Related FW 1.5.0


Range [units] 0,0 .. 25,0 [s]
Default value 0,3 s Force value YES
Step 0,1 s
Comm object 8653 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
The period of time that the phase angle difference must be within Phase Window (page 487) and
voltage difference within Voltage Window (page 486) before the breaker is closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 487


Slip Frequency

Setpoint group Synchronization Related FW 1.5.0


Range [units] -0,50 .. 0,50 [Hz]
Default value -0,25 Hz Force value YES
Step 0,01 Hz
Comm object 14798 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Synchronization Type (page 485) = SlipSynchr
Description
This setpoint adjusts the required BESS Frequency (page 713) during synchronization while
Synchronization Type (page 485) = SlipSynchr.
Note: Required BESS Frequency (page 713) = Mains/Bus Frequency (page 839) + Slip
Frequency.

6 back to List of setpoints

Slip Frequency Window

Setpoint group Synchronization Related FW 1.5.0


Range [units] 0,01 .. 0,50 [Hz]
Default value 0,15 Hz Force value YES
Step 0,01 Hz
Comm object 14799 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Synchronization Type (page 485) = SlipSynchr
Description
Window of slip frequency for slip synchronization (Synchronization Type (page 485) = SlipSynchr).

6 back to List of setpoints

BCB Latency

Setpoint group Synchronization Related FW 1.5.0


Range [units] 20 .. 1 000 [ms]
Default value 80 ms Force value YES
Step 1 ms
Comm object 14800 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Synchronization Type (page 485) = SlipSynchr
Description
Latency of BCB. This setpoint is enable, when Synchronization Type (page 485) has SlipSynchro
value. Synchronization Type (page 485) setting value of this setpoint.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 488


MCB Latency

Setpoint group Synchronization Related FW 1.5.0


Range [units] 20 .. 1 000 [ms]
Default value 80 ms Force value YES
Step 1 ms
Comm object 14801 Related applications MPTM
Config level Standard
Setpoint visibility Only if Synchronization Type (page 485) = SlipSynchr
Description
Latency of MCB.
IMPORTANT: This setpoint is enable, when Synchronization Type (page 485) has Split
Synchro value

6 back to List of setpoints

Group: Power Management

Subgroup: Power Management Control

Power Management

Setpoint group Power Management Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8551 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint is used to enable or disable the Power Management (page 274) function in this particular
controller.
Disabled - Function is disabled. Universal Genset is Started/Stopped only via LBI GENERIC
GENSET START/STOP (PAGE 1004).
Enabled - Function is enabled. Starting/Stopping of Universal Genset is affected by Power
Management (page 274) requirements.
IMPORTANT: Controller Mode (page 385) = AUTO, otherwise BESS is not controlled with
Power Management (page 274) function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 489


Power Management Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 3600 [s]
Default value 0s Force value YES
Step 1s
Comm object 12488 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
Setpoint defines delay of the Power Management (page 274). When GENERIC GENSET START/STOP
(PAGE 1004) signal is activated the Gen-sets are started. All Gen-sets (where Power Management
(page 489) is enabled) are started and stay running for time period specified by this parameter.
After this period elapses, only the unit(s) needed according to the Power Management calculation stay
running and the rest is stopped.
Example: This delay is useful, when you need to start gen-sets to an unknown load. Setting for
example 360s (6 minutes) and activating GENERIC GENSET START/STOP (PAGE 1004) will force all
gen-sets to start and run for 6 minutes despite of the power management setting.

Note: By setting “0” the Power Management function is enabled immediately.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 490


#Power Management Mode

Setpoint group Power Management Related FW 1.5.0


Range [units] ABS [kW] / ABS (kVA) / REL [%]
Default value ABS [kW] Force value NO
Step [-]
Comm object 9874 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint selects the Power Management (page 274) function mode.

The Power Management (page 274) is based on Actual Active Power In


ABS [kW] PM (page 858) and Nominal power (page 375) or Installed Power (page
375) of each unit.
The Power Management (page 274) is based on total running apparent
ABS (kVA)
power in PM and nominal apparent power.
The Power Management (page 274) is based on relative load, i.e. ratio of
REL [%] Actual Active Power In PM (page 858) to Nominal power (page 375) or
Installed Power (page 375).

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

Note: Setpoint shared throughout the system, is not applicable in InteliNeo.

Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 491


Priority

Setpoint group Power Management Related FW 1.5.0


Range [units] 1 .. 64 [-]
Default value 1 [-] Force value YES
Step 1 [-]
Comm object 8488 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the priority of the unit within the control group. A lower number represents a “higher”
priority, i.e. a Gen-set (Universal Genset) with lower number will start before another one with higher
number.
Note: If the binary input Top Priority (page 1030) is active, the unit gets the highest priority (0)
independent of the setpoint setting.

Note: If more than one unit have the same priority they will act as “one big” unit.

Note: The main idea of renewables is to run with the maximal priority. So it is expect the Microgrid
site will not be influenced by the power management because BESS and renewables shloud always
run.

Note: The setpoint is relevant with function Universal Genset in InteliNeo and does not affects the
BESS.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 492


#Priority Auto Swap

Setpoint group Power Management Related FW 1.5.0


Range [units] Disabled / RunHourEq / N/A Mode / Efficient [-]
Default value Disabled Force value NO
Step [-]
Comm object 10593 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint selects the optimization of Power Management (page 274) function.

Optimization is disabled. Priorities are given directly by the values adjusted in


Disabled
the setpoint Priority (page 492).
This method changes the Engine Priority (page 856) (not the setpoint
Priority (page 492)) to equalize running hours of the units or to keep
Run Hours Equal
maximal difference of running hours set by #Run Hours Max Difference
(page 515).
Power Management mode, which has been set via CAN2A (page 19)
N/A Mode
(CAN2B (page 19)), is not supported in this controller.
This method changes the Engine Priority (page 856) (not the setpoint
Priority (page 492)) to optimize which units are running according to their
Efficient Nominal power (page 375)/Installed Power (page 375), requested Load
reserve and Run Hours. For units with the same nominal power also run hour
equalization is being performed.

IMPORTANT: LBI Top Priority (page 1030) can be used only if #Priority Auto Swap =
Disabled.

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 493


#System Start Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 600 [s]
Default value 5s Force value NO
Step 1s
Comm object 8549 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the delay of the system activation after the LBI GENERIC GENSET START/STOP (PAGE
1004) has been activated.
Note: System Start Delay countdown is changed to 1 second for parallel operation (Bus is in parallel
with Mains).

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#System Stop Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 600 [s]
Default value 30 s Force value NO
Step 1s
Comm object 8550 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the delay of the system deactivation after the LBI GENERIC GENSET START/STOP
(PAGE 1004) has been deactivated.
Note: System Stop Delay countdown is changed to 1 second for parallel operation (Bus is in parallel
with Mains).

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 494


Subgroup: Dynamic Spinning Reserve

Dynamic Spinning Reserve Source

Setpoint group Power Management Related FW 1.5.0


Range [units] Disabled/External Analog Value/Internal Calculation
Default value Internal Calculation Force value YES
Step [-]
Comm object 20248 Related applications MINT
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the source for the function Dynamic Spinning Reserve (page 277).
Disabled: The CU is not calculating and providing Dynamic Spinning Reserve (page 857) and
Dynamic Spinning Reserve Offset (page 857) at all.
External Analog Value: The CU receives these values from the LAIs DYNAMIC SPINNING
RESERVE (PAGE 1120) and DYNAMIC SPINNING RESERVE OFFSET (PAGE 1120).
Internal Calculation: The DYNAMIC SPINNING RESERVE OFFSET (PAGE 1120) is received from LAI
and DYNAMIC SPINNING RESERVE (PAGE 1120) is calculated based on the actual power of
renewable sources and setpoints Solar Coverage Ratio (page 496) and Wind Coverage Ratio
(page 496).

6 back to List of setpoints

Dynamic Spinning Reserve

Setpoint group Power Management Related FW 1.5.0


Range [units] Enabled / Disabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 14126 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint is used to enable/disable use of the Dynamic Spinning Reserve (page 277) functionality
in power management.
Note: If enabled option is selected the InteliNeo6000 controller also participate on DSR in the same
way as Gen-set controllers setpoint should be used only to have the same calculation of Load
Reserve and DSR as rest of controllers in group.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 495


Solar Coverage Ratio

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 100 [%] of PV Actual P (page 719)
100 % of PV Actual P
Default value Force value YES
(page 719)
Step 1 % of PV Actual P (page 719)
Comm object 20247 Related applications MINT
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much percent from actual power of the PV (renewables) should be covered by
(counted in) Dynamic Spinning Reserve (page 277) in case Internal Calculation is used.

6 back to List of setpoints

Wind Coverage Ratio

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 100 [%] of WT Actual P (page 771)
100 % of WT Actual P
Default value Force value YES
(page 771)
Step 1 % of WT Actual P (page 771)
Comm object 19715 Related applications MINT
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much percent from actual power of the WT should be covered by (counted in)
Dynamic Spinning Reserve (page 277) in case Internal Calculation is used.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 496


Subgroup: Load Reserve Set 1

#Starting Load Reserve 1

Setpoint group Power Management Related FW 1.5.0


0 .. #Stopping Load Reserve 1 (page 498) [kW] (depends on the selected Power
Range [units]
Formats And Units (page 196))
60 kW (depends on the selected
Default value Power Formats And Units (page Force value NO
196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8489 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required minimal Actual Reserve (page 856) for Power Management (page 274)
function.
If Load Reserve Set 1 is activated and Actual Reserve (page 856) drops bellow this limit, next Source
will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
Note: If the absolute power management is selected, this setpoint (or the setpoints #Starting Load
Reserve 2 (page 500), #Starting Load Reserve 3 (page 503) or #Starting Load Reserve 4 (page
506) depending on which load reserve set is selected) determines also the number of Controllers
(that are part of the power management) which will start (according to their priority and nominal
power).

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 497


#Stopping Load Reserve 1

Setpoint group Power Management Related FW 1.5.0


#Starting Load Reserve 1 (page 497) .. 32000 [kW] (depends on the selected
Range [units]
Power Formats And Units (page 196))
110 kW (depends on the selected
Default value Force value NO
Power Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8491 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required maximal Actual Reserve (page 856) for Power Management (page
274) function.
If Load Reserve Set 1 is activated and Actual Reserve (page 856) rises over this limit, next Source will
be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
Note: The reserve for stop must be always adjusted higher than the reserve for start.

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 498


#Starting Rel Load Reserve 1

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. #Stopping Load Reserve 1 (page 498) [%]
Default value 60 % Force value NO
Step 1%
Comm object 10648 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required minimal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 1 is activated and Actual Relative Reserve (page 858) drops below this limit, next
Source will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#Stopping Rel Load Reserve 1

Setpoint group Power Management Related FW 1.5.0


Range [units] #Starting Rel Load Reserve 1 (page 499) .. 110 [%]
Default value 80 % Force value NO
Step 1%
Comm object 10652 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required maximal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 1 is activated and Actual Relative Reserve (page 858) rises over this limit, next
Source will be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 499


Subgroup: Load Reserve Set 2

#Starting Load Reserve 2

Setpoint group Power Management Related FW 1.5.0


0 .. #Stopping Load Reserve 2 (page 501) [kW] (depends on the selected Power
Range [units]
Formats And Units (page 196))
410 kW (depends on the selected
Default value Power Formats And Units (page Force value NO
196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8490 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required minimal Actual Reserve (page 856) for Power Management (page 274)
function.
If Load Reserve Set 2 is activated and Actual Reserve (page 856) drops bellow this limit, next Source
will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
Note: If the absolute power management is selected, this setpoint (or the setpoints #Starting Load
Reserve 2 (page 500), #Starting Load Reserve 3 (page 503) or #Starting Load Reserve 4 (page
506) depending on which load reserve set is selected) determines also the number of Controllers
(that are part of the power management) which will start (according to their priority and nominal
power).

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 500


#Stopping Load Reserve 2

Setpoint group Power Management Related FW 1.5.0


#Starting Load Reserve 2 (page 500) .. 32000 [kW] (depends on the selected
Range [units]
Power Formats And Units (page 196))
460 kW (depends on the selected
Default value Force value NO
Power Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8633 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required maximal Actual Reserve (page 856) for Power Management (page
274) function.
If Load Reserve Set 2 is activated and Actual Reserve (page 856) rises over this limit, next Source will
be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
Note: The reserve for stop must be always adjusted higher than the reserve for start.

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 501


#Starting Rel Load Reserve 2

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. #Stopping Rel Load Reserve 2 (page 502) [%]
Default value 60 % Force value NO
Step 1%
Comm object 10649 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required minimal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 2 is activated and Actual Relative Reserve (page 858) drops below this limit, next
Source will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#Stopping Rel Load Reserve 2

Setpoint group Power Management Related FW 1.5.0


Range [units] #Starting Rel Load Reserve 2 (page 502) .. 110 [%]
Default value 80 % Force value NO
Step 1%
Comm object 10653 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required maximal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 2 is activated and Actual Relative Reserve (page 858) rises over this limit, next
Source will be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 502


Subgroup: Load Reserve Set 3

#Starting Load Reserve 3

Setpoint group Power Management Related FW 1.5.0


0 .. #Stopping Load Reserve 3 (page 504) [kW] (depends on the selected Power
Range [units]
Formats And Units (page 196))
410 kW (depends on the selected
Default value Power Formats And Units (page Force value NO
196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8831 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required minimal Actual Reserve (page 856) for Power Management (page 274)
function.
If Load Reserve Set 3 is activated and Actual Reserve (page 856) drops bellow this limit, next Source
will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 503


#Stopping Load Reserve 3

Setpoint group Power Management Related FW 1.5.0


#Starting Load Reserve 3 (page 503) .. 32000 [kW] (depends on the selected
Range [units]
Power Formats And Units (page 196))
460 kW (depends on the selected
Default value Force value NO
Power Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8833 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required maximal Actual Reserve (page 856) for Power Management (page
274) function.
If Load Reserve Set 3 is activated and Actual Reserve (page 856) rises over this limit, next Source will
be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
Note: The reserve for stop must be always adjusted higher than the reserve for start.

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 504


#Starting Rel Load Reserve 3

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. #Stopping Rel Load Reserve 3 (page 505) [%]
Default value 60 % Force value NO
Step 1%
Comm object 10650 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required minimal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 3 is activated and Actual Relative Reserve (page 858) drops below this limit, next
Source will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#Stopping Rel Load Reserve 3

Setpoint group Power Management Related FW 1.5.0


Range [units] #Starting Rel Load Reserve 3 (page 505) .. 110 [%]
Default value 80 % Force value NO
Step 1%
Comm object 10654 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required maximal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 3 is activated and Actual Relative Reserve (page 858) rises over this limit, next
Source will be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 505


Subgroup: Load Reserve Set 4

#Starting Load Reserve 4

Setpoint group Power Management Related FW 1.5.0


0 .. #Stopping Load Reserve 4 (page 507) [kW] (depends on the selected Power
Range [units]
Formats And Units (page 196))
410 kW (depends on the selected
Default value Power Formats And Units (page Force value NO
196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8832 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required minimal Actual Reserve (page 856) for Power Management (page 274)
function.
If Load Reserve Set 4 is activated and Actual Reserve (page 856) drops bellow this limit, next Source
will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 506


#Stopping Load Reserve 4

Setpoint group Power Management Related FW 1.5.0


#Starting Load Reserve 4 (page 506) .. 32000 [kW] (depends on the selected
Range [units]
Power Formats And Units (page 196))
460 kW (depends on the selected
Default value Power Formats And Units (page Force value NO
196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 8834 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = ABS [kW]
Description
This setpoint adjusts required maximal Actual Reserve (page 856) for Power Management (page
274) function.
If Load Reserve Set 4 is activated and Actual Reserve (page 856) rises over this limit, next Source will
be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
Note: The reserve for stop must be always adjusted higher than the reserve for start.

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 507


#Starting Rel Load Reserve 4

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. #Stopping Rel Load Reserve 4 (page 508) [%]
Default value 60 % Force value NO
Step 1%
Comm object 10651 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required minimal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 4 is activated and Actual Relative Reserve (page 858) drops below this limit, next
Source will be started.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#Stopping Rel Load Reserve 4

Setpoint group Power Management Related FW 1.5.0


Range [units] #Starting Rel Load Reserve 4 (page 508) .. 110 [%]
Default value 80 % Force value NO
Step 1%
Comm object 10655 Related applications MINT
Config level Standard
Setpoint visibility Only if #Power Management Mode (page 491) = REL [%]
Description
This setpoint adjusts required maximal Actual Relative Reserve (page 858) for Power Management
(page 274) function.
If Load Reserve Set 4 is activated and Actual Relative Reserve (page 858) rises over this limit, next
Source will be stopped.
The currently active reserve set is selected by binary inputs LOAD RES 2 ACTIVE (PAGE 1008), LOAD RES
3 ACTIVE (PAGE 1009) and LOAD RES 4 ACTIVE (PAGE 1010). If none of these inputs is active the Load
Reserve Set 1 is selected.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 508


Subgroup: Minimal Running Power

#Min Run Power

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 65000 [kW] (depends on the selected Power Formats And Units (page 196))
210 kW (depends on the selected Power
Default value Force value NO
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 9584 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts required Minimal Running Nominal Power (page 859) of all sources and BESS if
Minimal Running Power 1 is chosen.
There are 3 Minimal Running Power options. This one is activated by LBI MIN RUN POWER ACT 1 (PAGE
1014).
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#Min Run Power 2

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 65000 [kW] (depends on the selected Power Formats And Units (page 196))
210 kW (depends on the selected Power
Default value Force value NO
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 9585 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts required Minimal Running Nominal Power (page 859) of Controllers and BESS if
Minimal Running Power 2 is chosen.
There are 3 Minimal Running Power options. This one is activated by LBI MIN RUN POWER ACT 2 (PAGE
1014).
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 509


#Min Run Power 3

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 65000 [kW] (depends on the selected Power Formats And Units (page 196))
210 kW (depends on the selected Power
Default value Force value NO
Formats And Units (page 196))
Step 1 kW (depends on the selected Power Formats And Units (page 196))
Comm object 9586 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts required Minimal Running Nominal Power (page 859) of Controllers and BESS if
Minimal Running Power 3 is chosen.
There are 3 Minimal Running Power options. This one is activated by LBI MIN RUN POWER ACT 3 (PAGE
1015).
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

Subgroup: Start/Stop Timing

#Next Engine Start Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 3 600 [s]
Default value 5s Force value NO
Step 1s
Comm object 8492 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the delay before next Gen-set is started after Actual Reserve (page 856) / Actual
Relative Reserve (page 858) drops bellow Starting Load Reserve of currently active Load Reserve Set.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 510


#Next Engine Stop Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 3600 [s]
Default value 20 s Force value NO
Step 1s
Comm object 8494 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the delay before next Gen-set is stopped after Actual Reserve (page 856) / Actual
Relative Reserve (page 858) rises over Stopping Load Reserve of currently active Load Reserve Set.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

Subgroup: Slow Stop Protection

#Slow Stop Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 600 [s]
Default value 60 s Force value NO
Step 1s
Comm object 8495 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts for how long the next Gen-set will suppress their own Slow Stop alarms to give
chance to another Controller to start and replace the defective one.
Note: If there is no Controller available to start, the Slow Stop alarms are not suppressed.

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 511


Slow Stop Stay In Load Sharing

Setpoint group Power Management Related FW 1.5.0


Range [units] Yes / No [-]
Default value No Force value NO
Step [-]
Comm object 16648 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint defines if the Source stays in loadsharing once the slow stop is initiated. The Slow Stop
protection takes an effect in Multiple Island as same as in Multiple parallel operation.

The Source with active Slow Stop protection regulates its power to value 20% of its
Nominal Power but only in if does not lead to overloading of other gensets or running
No them under 20%. Then it stays in load sharing. This mode is ended once the capacity of
other genset with lowest priority is available (load reserve is sufficient) or latest when
Slow Stop Delay elapsed.
The Source with active Slow Stop protection stay in load sharing until another gen-set is
Yes
connected to the bus or after the Slow Stop Delay is elapsed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 512


Subgroup: Over Load Next Start Protection

#Overload Next Start Protection

Setpoint group Power Management Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 14942 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint enables or disables Overload Next Start Protection. It makes the next Gen-set (in priority
order) to start when the load excises the value given by the setpoint #Overload Next Start Level (page
513) right after the delay #Overload Next Start Delay (page 514). #Overload Next Start Protection
requires Starting Load Reserve condition to be fulfilled in order to be used.

Disabled Protection is disabled.


Protection is enabled. If Actual Active Power In PM (page 858) of PM
Controllers related to Running Nominal Power In PM (page 859) is over
Enabled
#Overload Next Start Level (page 513), another Controller is started after
#Overload Next Start Delay (page 514).

IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

#Overload Next Start Level

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 100 [%] of Running Nominal Power In PM (page 859)
80 % of Running Nominal Power In
Default value Force value NO
PM (page 859)
Step 1 % of Running Nominal Power In PM (page 859)
Comm object 14941 Related applications MINT
Config level Standard
Setpoint visibility Only if #Overload Next Start Protection (page 513) = Enabled
Description
This setpoint adjusts the minimal load for #Overload Next Start Protection (page 513).
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 513


#Overload Next Start Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 5 [s]
Default value 1s Force value NO
Step 1s
Comm object 8493 Related applications MINT
Config level Standard
Setpoint visibility Only if #Overload Next Start Protection (page 513) = Enabled
Description
This setpoint adjusts the delay for #Overload Next Start Protection (page 513).
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

Subgroup: Run Hours Equalization

Run Hours Base

Setpoint group Power Management Related FW 1.5.0


Range [units] 0.0 .. 200000.0 [h]
Default value 0.0 h Force value YES
Step 0.1 h
Comm object 10600 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the correction of actual Running Hours (page 880).
RH = Running Hours (page 880) -Run Hours Base
Note: RH can not be adjusted below 0

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 514


#Run Hours Max Difference

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 65000 [h]
Default value 100 h Force value NO
Step 1h
Comm object 9919 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts the maximal difference between Running Hours (page 880) of Gen-sets in Power
Management (page 274) function if #Priority Auto Swap (page 493).
If the difference between Running Hours (page 880) is over this limit, priorities are swapped.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

Subgroup: Efficient Mode

#Power Band Change Up Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 3 600 [s]
Default value 10 s Force value NO
Step [s]
Comm object 8896 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint is used for adjusting the delay of changing the power band if the load demand rose above
the upper limit of the current power band. Setpoint is taken into account only if #Priority Auto Swap
(page 493) = Efficient.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 515


#Power Band Change Down Delay

Setpoint group Power Management Related FW 1.5.0


Range [units] 0 .. 3 600 [s]
Default value 10 s Force value NO
Step [s]
Comm object 10795 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint is used for adjusting the delay of changing the power band if the load demand drops below
the lower limit of the current power band. Setpoint is taken into account only if #Priority Auto Swap
(page 493) = Efficient.
IMPORTANT: This setpoint is shared via ⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) .
Change of this setpoint will be reflected in all controllers.

6 back to List of setpoints

Subgroup: Group Settings

Control Group

Setpoint group Power Management Related FW 1.5.0


Range [units] 1 .. 32 [-]
Default value 1 [-] Force value YES
Step 1 [-]
Comm object 10589 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint adjusts control group in which the particular source belongs to.
If there are no logical groups on the site, adjust this setpoint to 1. See more information in chapter
Control Groups (page 136).
Note: This control group settings are applied to BESS and/or Universal Gensets integrated via
InteliNeo.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 516


Group Link L

Setpoint group Power Management Related FW 1.5.0


Range [units] 1 .. 32 [-]
Default value 1 [-] Force value YES
Step 1 [-]
Comm object 10590 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
If the input GROUP LINK (PAGE 1004) of this particular controller is used to provide the "group link"
information for two Control groups (to get more information refer to the chapter Control Groups (page
136)). This setpoint is used to select which group is located at the left side of the group link breaker. (bus
tie breaker). If this particular controller is not used for the group link function, adjust this setpoint to 1.

6 back to List of setpoints

Group Link R

Setpoint group Power Management Related FW 1.5.0


Range [units] 1 .. 32 [-]
Default value 1 [-] Force value YES
Step 1 [-]
Comm object 10591 Related applications MINT
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
If the input GROUP LINK (PAGE 1004) of this particular controller is used to provide the "group link"
information for two Control groups (to get more information refer to the chapter Control Groups (page
136)). This setpoint is used to select which group is located at the right side of the group link breaker.
(bus tie breaker). If this particular controller is not used for the group link function, adjust this setpoint to 1.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 517


Group: Loss of Mains Protections

Subgroup: Loss of Mains Protections

Vector Shift Limit

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 1 .. 45 [°]
Default value 10 ° Force value YES
Step 1°
Comm object 9843 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Vector Shift Protection (page 593) is not Disabled
Description
This setpoint adjusts the threshold level for the Vector Shift Protection (page 593).
Note: To adjust this setpoint properly, check the value Max Vector Shift (page 848). The value is
available in InteliConfig, contains the maximal measured vector shift value since the BESS has been
synchronized to the mains and after opening of BCB or MCB it is "frozen". In normal conditions the
value should not be higher than 3 º and the most common setting of the threshold is about 7 º.

6 back to List of setpoints

ROCOF1 Windows Length

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 3 .. 30 [-]
Default value 5 Force value YES
Step 1 [-]
Comm object 9990 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF1 Protection (page 594) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF1 Protection (page 594).
It defines the number of periods of the Mains voltage in which the ROCOF protection is evaluated. The
higher length of the ROCOF window means less sensitive protection for short oscillations of the
frequency to both directions from the nominal value. Also, the delay of evaluation is higher.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 518


ROCOF1 df/dt

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 1.00 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 9844 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF1 Protection (page 594) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF1 Protection (page 594).

6 back to List of setpoints

ROCOF2 Windows Length

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.1 .. 2.5 [s]
Default value 0.5 s Force value YES
Step 0.1 s
Comm object 16137 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF2 Protection (page 595) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF2 Protection (page 595).
It defines the time interval for which the ROCOF protection is evaluated. The higher length of the ROCOF
window means less sensitive protection for short oscillations of the frequency to both directions from the
nominal value. Also, the delay of evaluation is higher.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 519


ROCOF2 df/dt

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 2.00 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 16141 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF2 Protection (page 595) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF2 Protection (page 595).

6 back to List of setpoints

ROCOF3 Windows Length

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.1 .. 2.5 [s]
Default value 1.0 s Force value YES
Step 0.1 s
Comm object 16138 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF3 Protection (page 596) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF3 Protection (page 596).
It defines the time interval for which the ROCOF protection is evaluated. The higher length of the ROCOF
window means less sensitive protection for short oscillations of the frequency to both directions from the
nominal value. Also, the delay of evaluation is higher.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 520


ROCOF3 df/dt

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 1.50 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 16142 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF3 Protection (page 596) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF3 Protection (page 596).

6 back to List of setpoints

ROCOF4 Windows Length

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.1 .. 2.5 [s]
Default value 2.0 s Force value YES
Step 0.1 s
Comm object 16139 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF4 Protection (page 597) is not Disabled
Description
This setpoint adjusts the time averaging level for the ROCOF4 Protection (page 597).
It defines the time interval for which the ROCOF protection is evaluated. The higher length of the ROCOF
window means less sensitive protection for short oscillations of the frequency to both directions from the
nominal value. Also, the delay of evaluation is higher.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 521


ROCOF4 df/dt

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] 0.01 .. 10.00 [Hz/s]
Default value 1.25 Hz/s Force value YES
Step 0.01 Hz/s
Comm object 16143 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if ROCOF4 Protection (page 597) is not Disabled
Description
This setpoint adjusts the trip level for ROCOF4 Protection (page 597).

6 back to List of setpoints

Vector Shift/ROCOF CB Selector

Loss of Mains
Setpoint group Related FW 1.5.0
Protection
Range [units] MCB / BCB [-]
Default value MCB Force value YES
Step [-]
Comm object 10552 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and
Vector Shift Protection (page 593)!= Disabled or
ROCOF1 Protection (page 594)!= Disabled or
Setpoint visibility
ROCOF2 Protection (page 595)!= Disabled or
ROCOF3 Protection (page 596)!= Disabled or
ROCOF4 Protection (page 597)!= Disabled .
Description
This setpoint adjusts which breaker will be opened when Vector Shift Protection (page 593), ROCOF1
Protection (page 594), ROCOF2 Protection (page 595), ROCOF3 Protection (page 596) or
ROCOF4 Protection (page 597) is detected.
Note: If the BCB is selected and a mains failure occurs the BCB will be opened immediately when
the vector shift or ROCOF is detected, however MCB will be also opened due to other mains
protections such as Mains <f Protection (page 588) or Mains <V Protection (page 581).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 522


Group: Mains Settings

Subgroup: Mains Voltage Protections

Mains >V

Setpoint group Mains Settings Related FW 1.5.0


100.0 .. Mains >>V (page 524) of Mains/Bus Nominal Voltage Ph-N (page 381)
Range [units]
and Mains/Bus Nominal Voltage Ph-Ph (page 381) [%]
110.0 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Nominal Force value YES
Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 8305 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the relative voltage threshold level for Mains >V Protection (page 577).
Note: Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839), Mains/Bus
Voltage L3-N (page 840), Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
840) and Mains/Bus Voltage L3-L1 (page 840) are used for this protection.

6 back to List of setpoints

Mains >V Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 8306 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains >V Protection (page 577).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 523


Mains >V Hys

Setpoint group Mains Settings Related FW 1.5.0


0.0 .. 30.0 [%] of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus
Range [units]
Nominal Voltage Ph-Ph (page 381)
0.0 [%] of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Force value NO
Nominal Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 14132 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains >V Protection (page 577).

6 back to List of setpoints

Mains >>V

Setpoint group Mains Settings Related FW 1.5.0


Mains >V (page 523) .. 130.0 [%] of Mains/Bus Nominal Voltage Ph-N (page
Range [units]
381) and Mains/Bus Nominal Voltage Ph-Ph (page 381)
120.0 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Nominal Force value YES
Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 11345 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the relative voltage threshold level for Mains >>V Protection (page 579).
Note: Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839), Mains/Bus
Voltage L3-N (page 840), Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
840) and Mains/Bus Voltage L3-L1 (page 840) are used for this protection.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 524


Mains >>V Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 0.10 s Force value YES
Step 0.01 s
Comm object 11347 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains >>V Protection (page 579).

6 back to List of setpoints

Mains >>V Hys

Setpoint group Mains Settings Related FW 1.5.0


0.0 .. 30.0 [%] of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus
Range [units]
Nominal Voltage Ph-Ph (page 381)
0.0 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Force value YES
Nominal Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 14133 Related applications MPTM
Config level Standard
Setpoint
Only if Application Mode (page 885) = MPTM
visibility
Description
This setpoint adjusts the hysteresis for return from Mains >>V Protection (page 579).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 525


Mains 10min Avg >V

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 100.0 .. 150.0 [%] of Mains/Bus Nominal Voltage Ph-Ph (page 381)
110.0 % of Mains/Bus Nominal
Default value Force value YES
Voltage Ph-Ph (page 381)
Step 0.1 % of Mains/Bus Nominal Voltage Ph-Ph (page 381)
Comm object 13795 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the relative voltage threshold level for Mains 10min Avg >V Protection (page
580).

6 back to List of setpoints

Mains 10min Avg >V Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 0s Force value YES
Step 0.01 s
Comm object 16898 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoints adjust delay for Mains 10min Avg >V Protection (page 580).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 526


Mains <V

Setpoint group Mains Settings Related FW 1.5.0


Mains <<V (page 528) .. 99.0 [%] of Mains/Bus Nominal Voltage Ph-N (page
Range [units]
381) and Mains/Bus Nominal Voltage Ph-Ph (page 381)
60 % of Mains/Bus Nominal Voltage Ph-
Default value N (page 381) and Mains/Bus Nominal Force value YES
Voltage Ph-Ph (page 381)
1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 8307 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the relative voltage threshold level for Mains <V Protection (page 581).
Note: Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839), Mains/Bus
Voltage L3-N (page 840), Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
840) and Mains/Bus Voltage L3-L1 (page 840) are used for this protection.

6 back to List of setpoints

Mains <V Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 1.50 s Force value YES
Step 0.01 s
Comm object 8308 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains <V Protection (page 581).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 527


Mains <V Hys

Setpoint group Mains Settings Related FW 1.5.0


0.0 .. 50.0 [%] of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus
Range [units]
Nominal Voltage Ph-Ph (page 381)
0.0 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Force value YES
Nominal Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 14130 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains <V Protection (page 581).

6 back to List of setpoints

Mains <<V

Setpoint group Mains Settings Related FW 1.5.0


10.0 .. Mains <V (page 527) [%] of Mains/Bus Nominal Voltage Ph-N (page
Range [units]
381) and Mains/Bus Nominal Voltage Ph-Ph (page 381)
30.0 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Nominal Force value YES
Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 11346 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the relative voltage threshold level for Mains <V Protection (page 582).
Note: Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page 839), Mains/Bus
Voltage L3-N (page 840), Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
840) and Mains/Bus Voltage L3-L1 (page 840) are used for this protection.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 528


Mains <<V Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 0.10 s Force value YES
Step 0.01 s
Comm object 11348 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains <V Protection (page 582).

6 back to List of setpoints

Mains <<V Hys

Setpoint group Mains Settings Related FW 1.5.0


0.0 .. 50.0 [%] of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus
Range [units]
Nominal Voltage Ph-Ph (page 381)
0.0 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Force value YES
Nominal Voltage Ph-Ph (page 381)
0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 14131 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains <V Protection (page 582).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 529


Mains V Unbalance

Setpoint group Mains Settings Related FW 1.5.0


1 .. 200 [%] of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus
Range [units]
Nominal Voltage Ph-Ph (page 381)
10 % of Mains/Bus Nominal Voltage
Default value Ph-N (page 381) and Mains/Bus Force value YES
Nominal Voltage Ph-Ph (page 381)
1 % of Mains/Bus Nominal Voltage Ph-N (page 381) and Mains/Bus Nominal
Step
Voltage Ph-Ph (page 381)
Comm object 8446 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the relative voltage threshold level for Mains V Unbalance Protection (page
583).

6 back to List of setpoints

Mains V Unbalance Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 2.00 s Force value YES
Step 0.01 s
Comm object 8447 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains V Unbalance Protection (page 583).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 530


Subgroup: Mains Frequency Protection

Mains >f

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 ..Mains >>f (page 532) [Hz]
Default value 1.50 Hz Force value YES
Step 0.01 Hz
Comm object 8310 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts maximal accepted frequency for Mains >f Protection (page 586).

6 back to List of setpoints

Mains >f Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 1000.00 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 16632 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains >f Protection (page 586).

6 back to List of setpoints

Mains >f Hys

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 2.50 [Hz]
Default value 0.00 Hz Force value YES
Step 0.01 Hz
Comm object 14134 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains >f Protection (page 586).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 531


Mains >>f

Setpoint group Mains Settings Related FW 1.5.0


Range [units] Mains >f (page 531) .. 10.00 [Hz]
Default value 2.50 Hz Force value YES
Step 0.01 Hz
Comm object 11349 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts maximal accepted frequency for Mains >>f Protection (page 587).

6 back to List of setpoints

Mains >>f Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 1000.00 [s]
Default value 0.00 s Force value YES
Step 0.01 s
Comm object 16628 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains >>f Protection (page 587).

6 back to List of setpoints

Mains >>f Hys

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 2.50 [Hz]
Default value 0.00 Hz Force value YES
Step 0.01 Hz
Comm object 16076 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains >>f Protection (page 587).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 532


Mains <f

Setpoint group Mains Settings Related FW 1.5.0


Range [units] Mains <<f (page 534) .. 0.00 [Hz]
Default value -1.50 Hz Force value YES
Step 0.01 Hz
Comm object 14587 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts minimal accepted frequency for Mains <f Protection (page 588).

6 back to List of setpoints

Mains <f Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 1000.00 [s]
Default value 5.00 s Force value YES
Step 0.01 s
Comm object 16633 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains <f Protection (page 588).

6 back to List of setpoints

Mains <f Hys

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 2.50 [Hz]
Default value 0.00 Hz Force value YES
Step 0.01 Hz
Comm object 14135 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains <f Protection (page 588).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 533


Mains <<f

Setpoint group Mains Settings Related FW 1.5.0


Range [units] -10.00 .. Mains <f (page 533) [Hz]
Default value -2.50 Hz Force value YES
Step 0.01 Hz
Comm object 16483 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts maximal accepted frequency for Mains <<f Protection (page 589).

6 back to List of setpoints

Mains <<f Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 1000.00 [s]
Default value 0.00 s Force value YES
Step 0.01 s
Comm object 16630 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint specifies the delay for Mains <<f Protection (page 589).

6 back to List of setpoints

Mains <<f Hys

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.00 .. 2.50 [Hz]
Default value 0.00 Hz Force value YES
Step 0.01 Hz
Comm object 16555 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the hysteresis for return from Mains <<f Protection (page 589).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 534


Subgroup: Mains Fault Timers

Mains Stabilization Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.0 .. 60.0 [s]
Default value 1.0 s Force value YES
Step 0.1 s
Comm object 14435 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the time that Mains parameters need to remain within limits of voltage and
frequency protections before the return to Mains is initiated. This delay is active only when the BCB is not
closed and the load is not powered from the BESS or PV. After this delay elapsed, the procedure
continues by counting down the MCB Close Delay (page 535).
6 back to List of setpoints

MCB Close Delay

Setpoint group Mains Settings Related FW 1.5.0


Range [units] 0.0 .. 60.0 [s]
Default value 5.0 s Force value YES
Step 0.1 s
Comm object 8389 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the delay before MCB is closed after Mains returns.
6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 535


Group: Grid Codes

Subgroup: Grid Codes Test

Grid Codes Test

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value NO
Step [-]
Comm object 14129 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables simulation mode for some Grid Codes and Q(Um) regulation:
Power Regulation Based On Over/Under Frequency (page 299)
P For Q (page 306)
While this setpoint is Enabled, alarm Wrn Test UPQF (page 1268) is active.

6 back to List of setpoints

Subgroup: Mains Params/MP Synchronization

Mains Params/MP Synchronization

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16636 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables Synchronization & Connection Conditions (page 307).

Disabled Synchronization & Connection Conditions (page 307) is disabled.


Enabled Synchronization & Connection Conditions (page 307) is enabled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 536


Mains Synchronization V Max

Setpoint group Grid Codes Related FW 1.5.0


Mains Synchronization V Min (page 537) .. 130 [%] of Mains/Bus Nominal
Range [units]
Voltage Ph-Ph (page 381)
110 % of Mains/Bus Nominal
Default value Force value YES
Voltage Ph-Ph (page 381)
Step 1 % of Mains/Bus Nominal Voltage Ph-Ph (page 381)
Comm object 13012 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts maximal accepted Mains/Bus Voltage for Network connection/reconnection
conditions (page 307).

6 back to List of setpoints

Mains Synchronization V Min

Setpoint group Grid Codes Related FW 1.5.0


10 .. Mains Synchronization V Max (page 537) [%] of Mains/Bus Nominal
Range [units]
Voltage Ph-Ph (page 381)
90 % of Mains/Bus Nominal
Default value Force value YES
Voltage Ph-Ph (page 381)
Step 1 % of Mains/Bus Nominal Voltage Ph-Ph (page 381)
Comm object 13013 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts minimal accepted Mains/Bus Voltage for Network connection/reconnection
conditions (page 307).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 537


Mains Synchronization f Max

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0.00 .. 2.00 [Hz]
Default value 0.20 Hz Force value YES
Step 0.01 Hz
Comm object 13014 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts maximal accepted Mains/Bus Frequency (page 839) for Network
connection/reconnection conditions (page 307).

6 back to List of setpoints

Mains Synchronization f Min

Setpoint group Grid Codes Related FW 1.5.0


Range [units] -3.00 .. 0.00 [Hz]
Default value -3.00 Hz Force value YES
Step 0.01 Hz
Comm object 14586 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts minimal accepted Mains/Bus Frequency (page 839) for Network
connection/reconnection conditions (page 307) .

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 538


Mains Synchronization Period

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 600 s Force value YES
Step 1s
Comm object 13017 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts period for which is active Network connection/reconnection conditions (page
307) after LBO MAINS/BUS HEALTHY (PAGE 1090) gets closed again.
Note: This period resets every time LBO MAINS/BUS HEALTHY (PAGE 1090) recloses.

6 back to List of setpoints

After MP Synchronization V Max

Setpoint group Grid Codes Related FW 1.5.0


After MP Synchronization V Min (page 540) .. 130 [%] of Mains/Bus Nominal
Range [units]
Voltage Ph-Ph (page 381)
110 % of Mains/Bus Nominal
Default value Force value YES
Voltage Ph-Ph (page 381)
Step 1 % of Mains/Bus Nominal Voltage Ph-Ph (page 381)
Comm object 16393 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts maximal accepted Mains/Bus Voltage for Network connection/reconnection
conditions after Mains Fail (page 308).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 539


After MP Synchronization V Min

Setpoint group Grid Codes Related FW 1.5.0


10 .. After MP Synchronization V Max (page 539) [%] of Mains/Bus Nominal
Range [units]
Voltage Ph-Ph (page 381)
95 % of Mains/Bus Nominal
Default value Force value YES
Voltage Ph-Ph (page 381)
Step 1 % of Mains/Bus Nominal Voltage Ph-Ph (page 381)
Comm object 16394 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts minimal accepted Mains/Bus Voltage for Network connection/reconnection
conditions after Mains Fail (page 308).

6 back to List of setpoints

After MP Synchronization f Max

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0.00 .. 2.00 [Hz]
Default value 0.10 Hz Force value YES
Step 0.01 Hz
Comm object 16395 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts maximal accepted Mains/Bus Frequency (page 839) for Network
connection/reconnection conditions after Mains Fail (page 308).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 540


After MP Synchronization f Min

Setpoint group Grid Codes Related FW 1.5.0


Range [units] -3.00 .. 0.00 [Hz]
Default value -0.10 Hz Force value YES
Step 0.01 Hz
Comm object 16396 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts minimal accepted Mains/Bus Frequency (page 839) for Network
connection/reconnection conditions after Mains Fail (page 308).

6 back to List of setpoints

After MP Synchronization Period

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 600 s Force value YES
Step 1s
Comm object 16397 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Mains Params/MP
Setpoint visibility
Synchronization (page 536) = Enabled
Description
This setpoint adjusts period for which is active Network connection/reconnection conditions after
Mains Fail (page 308) after LBO MAINS/BUS HEALTHY (PAGE 1090) gets closed again.
Note: This period resets every time LBO MAINS/BUS HEALTHY (PAGE 1090) recloses.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 541


Subgroup: After Mains Trip Period

After Mains Trip

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16637 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables After Mains Trip Period (page 308).

Disabled After Mains Trip Period (page 308) is disabled


Enabled After Mains Trip Period (page 308) is enabled

6 back to List of setpoints

After Mains Trip Period

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 3600 [s]
Default value 1200 s Force value YES
Step 1s
Comm object 14601 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and After Mains Trip (page 542) =
Setpoint visibility
Enabled
Description
This setpoint adjusts the period for how long is After Mains Trip Period active and LBO EVENT MAINS TRIP
(PAGE 1076) is closed. The period starts once the Mains is healthy (LBO MAINS/BUS HEALTHY (PAGE
1090) is closed) and timer After MP Synchronization Period (page 541) is elapsed or Mains
Params/MP Synchronization (page 536) is disabled.
Note: This period resets every time LBO EVENT MAINS TRIP (PAGE 1076) re-closes.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 542


After Mains Trip Period Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 7 [-] Force value YES
Step 1 [-]
Comm object 14491 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts the priority of After Mains Trip Period Ramp (page 543) which is used while LBO
EVENT MAINS TRIP (PAGE 1076) is closed.
Note: Smaller number means higher priority, i.e. 0 has the highest priority.

6 back to List of setpoints

After Mains Trip Period Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16487 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and After Mains Trip (page 542) =
Setpoint visibility
Enabled
Description
This setpoint adjusts ramping time of the BESS Required P (page 861) to the BESS Required P
Target (page 861) if the LBO EVENT MAINS TRIP (PAGE 1076) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by After Mains Trip Period Priority (page 543).
Example: Installed Power (page 375) = 20 kW, After Mains Trip Period Ramp = 10 seconds.
The ramp is changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 543


Subgroup: Power Over/Under Frequency

Power Over/Under Frequency

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16631 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables Power Regulation Based On Over/Under Frequency (page 299).

Disabled Power Regulation Based On Over/Under Frequency (page 299) is disabled


Enabled Power Regulation Based On Over/Under Frequency (page 299) is enabled

6 back to List of setpoints

Power Over/Under Frequency Delay

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0.0 .. 2.0 [s]
Default value 0.2 s Force value YES
Step 0.1 s
Comm object 16186 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts behavior of Power Regulation Based On Over/Under Frequency (page 299)
and defines minimal period for which Mains/Bus Frequency (page 839) has to be inside of PoF/PuF
range.
This setpoint adjusts delay for activation of Power regulation based on over frequency/under frequency.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 544


Return Over/Under Frequency Delay

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 0s Force value YES
Step 1s
Comm object 16886 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint defines the delay for Return Over/Under Frequency function. After this delay elapsed the
LBO EVENT RETURN OVER/UNDER FREQUENCY (PAGE 1076) is closed.

6 back to List of setpoints

Return Over/Under Frequency Period

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 3600 [s]
Default value 600 s Force value YES
Step 1s
Comm object 16900 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts the period for how long is Return Over/Under Frequency active and LBO EVENT
RETURN OVER/UNDER FREQUENCY (PAGE 1076) is closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 545


Return From Over/Under Frequency Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 2 [-] Force value YES
Step 1 [-]
Comm object 15152 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts the priority of Return From Over/Under Frequency Ramp (page 546) which is
used while LBO EVENT RETURN OVER/UNDER FREQUENCY (PAGE 1076) is closed.
Note: Smaller number means higher priority, i.e. 0 has the highest priority.

6 back to List of setpoints

Return From Over/Under Frequency Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16491 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts ramping time of BESS Required P (page 861) to BESS Required P Target (page
861) if LBO EVENT RETURN OVER/UNDER FREQUENCY (PAGE 1076) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by Return From Over/Under Frequency Priority (page 546)
Example: Installed Power (page 375) = 20 kW, Return From Over/Under Frequency Ramp = 10
seconds. The ramp is changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 546


Mains Frequency Rise Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 4 [-] Force value YES
Step 1 [-]
Comm object 14488 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts Mains Frequency Rise Ramp (page 547) which is used while LBO EVENT MAINS
FREQUENCY RISE (PAGE 1075) is closed.
Note: Smaller number means higher priority, i.e. 0 has the highest priority.

6 back to List of setpoints

Mains Frequency Rise Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16484 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts ramping time of BESS Required P (page 861) to BESS Required P Target (page
861) if LBO EVENT MAINS FREQUENCY RISE (PAGE 1075) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by Mains Frequency Rise Priority (page 547)
Example: Installed Power (page 375) = 20 kW, Mains Frequency Rise Ramp = 10 seconds. The
ramp is changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 547


Mains Frequency Fall Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 5 [-] Force value YES
Step 1 [-]
Comm object 14489 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts the priority of Mains Frequency Fall Ramp (page 548) which is used while LBO
EVENT MAINS FREQUENCY FALL (PAGE 1075) is closed.
Note: Smaller number means higher priority, i.e. 0 has the highest priority.

6 back to List of setpoints

Mains Frequency Fall Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 5s Force value YES
Step 1s
Comm object 16485 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Power Over/Under
Setpoint visibility
Frequency (page 544) = Enabled
Description
This setpoint adjusts ramping time of BESS Required P (page 861) to BESS Required P Target (page
861) if LBO EVENT MAINS FREQUENCY FALL (PAGE 1075) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by Mains Frequency Fall Priority (page 548).
Example: Installed Power (page 375) = 20 kW, Mains Frequency Fall Ramp = 10 seconds. The
ramp is changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 548


Subgroup: Load Reduction

Load Reduction

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16638 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables Load Reduction (page 303).

Disabled Load Reduction (page 303) is disabled


Enabled

Note: LBI Load Reduction Enable (page 1007) has to be closed, otherwise this Setpoint has no
effect.

6 back to List of setpoints

Load Reduction 1

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 100 [%] of Installed Power (page 375) or Nominal power (page 375)
100 % of Installed Power (page 375) or
Default value Force value YES
Nominal power (page 375)
Step 0.1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 16132 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Load Reduction (page 549) =
Setpoint visibility
Enabled
Description
This setpoint adjusts maximal allowed load of BESS while LBI LOAD REDUCTION 1 (PAGE 1006) is closed.
Always the lowest load defined by the LAI LOAD REDUCTION (PAGE 1122) or by LBIs, LOAD REDUCTION 1
(PAGE 1006), LOAD REDUCTION 2 (PAGE 1006), etc. is allowed.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 549


Load Reduction 2

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 100 [%] of Installed Power (page 375) or Nominal power (page 375)
60 [%] of Installed Power (page 375) or
Default value Force value YES
Nominal power (page 375)
Step 0.1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 16133 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Load Reduction (page 549) =
Setpoint visibility
Enabled
Description
This setpoint adjusts maximal allowed load of BESS while LBI LOAD REDUCTION 2 (PAGE 1006) is closed.
Always the lowest load defined by the LAI LOAD REDUCTION (PAGE 1122) or by LBIs, LOAD REDUCTION 1
(PAGE 1006), LOAD REDUCTION 2 (PAGE 1006), etc. is allowed.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

Load Reduction 3

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 100 [%] of Installed Power (page 375) or Nominal power (page 375)
30 % of Installed Power (page 375) or
Default value Force value YES
Nominal power (page 375)
Step 0.1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 16134 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Load Reduction (page 549) =
Setpoint visibility
Enabled
Description
This setpoint adjusts maximal allowed load of BESS while LBI LOAD REDUCTION 3 (PAGE 1007) is closed.
Always the lowest load defined by the LAI LOAD REDUCTION (PAGE 1122) or by LBIs, LOAD REDUCTION 1
(PAGE 1006), LOAD REDUCTION 2 (PAGE 1006), etc. is allowed.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 550


Load Reduction 4

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 100 [%] of Installed Power (page 375) or Nominal power (page 375)
10 %of Installed Power (page 375) or
Default value Force value YES
Nominal power (page 375)
Step 0.1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 16135 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Load Reduction (page 549) =
Setpoint visibility
Enabled
Description
This setpoint adjusts maximal allowed load of BESS while LBI LOAD REDUCTION 4 (PAGE 1007) is closed.
Always the lowest load defined by the LAI LOAD REDUCTION (PAGE 1122) or by LBIs, LOAD REDUCTION 1
(PAGE 1006), LOAD REDUCTION 2 (PAGE 1006), etc. is allowed.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

Load Reduction Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 3 [-] Force value YES
Step 1 [-]
Comm object 14490 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Load Reduction (page 549) =
Setpoint visibility
Enabled
Description
This setpoint adjusts the priority of Load Reduction Ramp (page 552) which is used while LBO EVENT
LOAD REDUCTION (PAGE 1075) is closed.
Note: Smaller number means higher priority, i.e. 0 has the highest priority.

Note: If priority is set to OFF, Load Reduction Ramp (page 552) is not applied.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 551


Load Reduction Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 5s Force value YES
Step 1s
Comm object 16486 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Load Reduction (page 549) =
Setpoint visibility
Enabled
Description
This setpoint adjusts the ramping time of the BESS Required P (page 861) to the BESS Required P
Target (page 861) if the LBO EVENT LOAD REDUCTION (PAGE 1075) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by After Mains Trip Period Priority (page 543).
Example: Installed Power (page 375) = 20 kW, Load Reduction Ramp = 10 seconds. The ramp
is changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 552


Subgroup: P(Um)

P(Um)

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / P Instal (Um) / P Actual (Um)
Default value Disabled Force value YES
Step -
Comm object 16567 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables and selects mode of Power Regulation Based On Actual Mains
Voltage (page 302).

Power Regulation Based On Actual Mains Voltage (page 302) is


Disabled
disabled.
Power Regulation Based On Actual Mains Voltage (page 302) is
enabled. Function is evaluated according to P(Um) (page 971) curve and the
P Instal (Um)
reduction is based on the setpoint Installed Power (page 375). Value Pmom
(page 829) is not used in this case.
Power Regulation Based On Actual Mains Voltage (page 302) is
enabled. Function is evaluated according to P(Um) (page 971) curve and the
P Actual (Um)
reduction is based on the actual value of BESS P (page 707).Value Pmom
(page 829) is used in this case.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 553


P Ramp Filter

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled
Default value Disabled Force value YES
Step -
Comm object 16634 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and P(Um) (page 553) !=
Setpoint visibility
Disabled
Description
This setpoint enables/disables PT1 filtering for P(Um) Ramp (page 555) during ramping of BESS
Required P (page 861) to BESS Required P Target (page 861).

PT1 filtering is disabled.

Disabled

Pt1 filtering is enabled

Enabled

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 554


P(Um) Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254 / OFF [-]
Default value 11 [-] Force value YES
Step 1 [-]
Comm object 15153 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM and P(Um) (page 553) != Disabled
Description
This setpoint adjusts priority of P(Um) Ramp (page 555) which is used while LBO EVENT P(UM) (PAGE
1076) is closed.
Note: Smaller number means higher priority, e.i. 0 has highest priority.

6 back to List of setpoints

P(Um) Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 s
Default value 60 s Force value YES
Step 1s
Comm object 16492 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM and P(Um) (page 553) != Disabled
Description
This setpoint adjusts ramping time of BESS Required P (page 861) to BESS Required P Target (page
861) if LBO EVENT P(UM) (PAGE 1076) is closed. The ramping behavior is affected by P Ramp Filter
(page 554) which can enable the PT1 filtering.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by P(Um) Priority (page 555).
Example: Installed Power (page 375) = 20 kW, P(Um) Ramp = 10 seconds. The ramp is
changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 555


Subgroup: P For Q

P For Q Limitation

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 14481 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables P For Q (page 306).

Disabled P For Q (page 306) is disabled


Enabled P For Q (page 306) is enabled

6 back to List of setpoints

P For Q Deadband

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 100 [%] of Installed Power (page 375) or Nominal power (page 375)
1 % of Installed Power (page 375)
Default value Force value YES
or Nominal power (page 375)
Step 1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 14486 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and P For Q Limitation (page
Setpoint visibility
556) = Enabled
Description
This setpoint adjusts the sensitive of P For Q (page 306) function. Use it to prevent oscillation of BESS
P (page 707).
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 556


P For Q Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 6 [-] Force value YES
Step 1 [-]
Comm object 14492 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and P For Q Limitation (page
Setpoint visibility
556) = Enabled
Description
This setpoint adjusts the priority of P For Q Ramp (page 557) which is used while LBO EVENT P FOR Q
(PAGE 1076) is closed.
Note: Smaller number means higher priority, i.e. 0 has the highest priority.

Note: If priority is set to OFF, P For Q Ramp (page 557) is not applied.

6 back to List of setpoints

P For Q Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16488 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and P For Q Limitation (page
Setpoint visibility
556) = Enabled
Description
This setpoint adjusts ramping time of BESS Required P (page 861) to BESS Required P Target (page
861) if LBO EVENT P FOR Q (PAGE 1076) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by P For Q Priority (page 557)
Example: Installed Power (page 375) = 20 kW, P For Q Ramp = 10 seconds. The ramp is
changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 557


Subgroup: Q&U Protection

Q&U Protection

Setpoint group Grid Codes Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 14519 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables Q&U Protection (page 307).

Protection is enabled. Behavior of protection is adjusted via setpoints Q&U < V


(page 559), Q&U < Q (page 559), Q&U Protection Delay (page 560) and
Q&U CB Selector (page 560). When relative value of Mains/Bus Voltage L1-
N (page 839) drops bellow Q&U < V (page 559) of Mains/Bus Nominal
Enabled
Voltage Ph-N (page 381) value BESS Q (page 708) is bellow Q&U < Q (page
559) for period longer than Q&U Protection Delay (page 560), alarm Wrn
Q&U Protection (page 1262) is activated and breaker selected by Q&U CB
Selector (page 560) is opened.
Disabled Protection is disabled.
Protection
Protection is enabled or disabled by the state of LBI PROTECTION FORCE
Force Disable
DISABLE 1 (PAGE 1016).
1
Protection
Protection is enabled or disabled by the state of LBI PROTECTION FORCE
Force Disable
DISABLE 2 (PAGE 1017).
2
Protection
Protection is enabled or disabled by the state of LBI PROTECTION FORCE
Force Disable
DISABLE 3 (PAGE 1017).
3

Note: This protection is evaluated only if Application Mode (page 885) = MPTM and Breaker state
(page 886) = ParalOper.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 558


Q&U < V

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 70.0 .. 100.0 [%] of Mains/Bus Nominal Voltage Ph-N (page 381)
85.0 % of Mains/Bus Nominal
Default value Force value YES
Voltage Ph-N (page 381)
Step 0.1 % of Mains/Bus Nominal Voltage Ph-N (page 381)
Comm object 14137 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Q&U Protection (page 558) !=
Setpoint visibility
Disabled
Description
This setpoint adjusts minimal relative required Mains/Bus Voltage L1-N (page 839) for Q&U
Protection (page 558).

6 back to List of setpoints

Q&U < Q

Setpoint group Grid Codes Related FW 1.5.0


-32000 .. 32000 [kVAr] (depends on the selected Power Formats And Units
Range [units]
(page 196))
Default value 0 kVAr Force value YES
Step 1 kVAr (depends on the selected Power Formats And Units (page 196))
Comm object 14139 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Q&U Protection (page 558) !=
Setpoint visibility
Disabled
Description
This setpoint adjusts minimal relative required BESS Q (page 708) for Q&U Protection (page 558).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 559


Q&U Protection Delay

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0.00 .. 600.00 [s]
Default value 0.40 s Force value YES
Step 0.01 s
Comm object 16078 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Q&U Protection (page 558) !=
Setpoint visibility
Disabled
Description
This setpoint adjusts reaction delay for Q&U Protection (page 558).

6 back to List of setpoints

Q&U CB Selector

Setpoint group Grid Codes Related FW 1.5.0


Range [units] MCB / BCB [-]
Default value BCB Force value YES
Step [-]
Comm object 16079 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Q&U Protection (page 558) !=
Setpoint visibility
Disabled
Description
This setpoint adjusts which breaker opens in case that Q&U Protection (page 558) is activated.

MCB When Q&U Protection (page 558) is activated, MCB breaker opens.
BCB When Q&U Protection (page 558) is activated, BCB breaker opens.

Note: Reclosing of breaker is forbidden if Wrn Q&U Protection (page 1262) is present in the alarm list.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 560


Subgroup: Dynamic Support

Dynamic Support

Setpoint group Grid Codes Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2
Range [units]
/ Protection Force Disable 3 [-]
Default value Disabled Force value YES
Step [-]
Comm object 14136 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables Dynamic Support - VRT (page 304) defined by >V and <V ride through
curves. The standard mains protections are still active.

Protection is enabled. Behavior of protection is adjusted


via application curves LVRT 3-phase (page 981), LVRT
Enabled
2-phase (page 982), LVRT 1-phase (page 983) and
OVRT (page 984).
Disabled Protection is disabled.
Protection is enabled or disabled by the state of LBI
Protection Force Disable 1
PROTECTION FORCE DISABLE 1 (PAGE 1016).
Protection is enabled or disabled by the state of LBI
Protection Force Disable 2
PROTECTION FORCE DISABLE 2 (PAGE 1017).
Protection is enabled or disabled by the state of LBI
Protection Force Disable 3
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

Dynamic Support Protection Type

Setpoint group Grid Codes Related FW 1.5.0


Range [units] No Protection / History Record / Warning / Mains Protection [-]
Default value Mains Protection Force value YES
Step [-]
Comm object 16559 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Dynamic Support (page 561)
Setpoint visibility
!= Disabled
Description
This setpoint adjusts protection type of Dynamic Support (page 561).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 561


Dynamic Support PF/Q Control

Setpoint group Grid Codes Related FW 1.5.0


Range [units] Active / Stopped [-]
Default value Active Force value YES
Step [-]
Comm object 16569 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Dynamic Support (page 561)
Setpoint visibility
!= Disabled
Description
This setpoint adjusts behavior of Voltage Regulator Output (page 866) while Dynamic Support - VRT
(page 304) is active.

Active Voltage Regulator Output (page 866) is still being regulated


Voltage Regulator Output (page 866) is frozen at the moment of activation
Stopped
the VRT function.

6 back to List of setpoints

LVRT Level Severe

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0,0 .. 100,0 [%] of relative Mains Voltage
50,0 % of relative
Default value Force value YES
Mains Voltage
Step 0,1 % of relative Mains Voltage
Comm object 16564 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Dynamic Support (page 561)
Setpoint visibility
!= Disabled
Description
This setpoint adjusts critical undervoltage. If relative Mains Voltage drops bellow this limit, LBO LVRT
SEVERE (PAGE 1089) is closed for at least 500 ms.
6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 562


Post VRT Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 2 [-] Force value YES
Step 1 [-]
Comm object 14503 Related applications MINT, MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Dynamic Support (page 561)
Setpoint visibility
!= Disabled
Description
This setpoint adjusts priority of Post VRT Ramp (page 563) which is used while LBO EVENT POST VRT
(PAGE 1076) is closed.

6 back to List of setpoints

Post VRT Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16490 Related applications MINT, MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Dynamic Support (page 561)
Setpoint visibility
!= Disabled
Description
This setpoint adjusts ramping time of BESS Required P (page 861) to BESS Required P Target (page
861) if LBO EVENT POST VRT (PAGE 1076) is closed.
The ramping time is set for ΔP which is given by the setpoint Installed Power (page 375) or by the
setpoint Nominal power (page 375) if the Installed Power is OFF.
Priority of this ramp is given by Post VRT Priority (page 563).
Example: Installed Power (page 375) = 20 kW, Post VRT Ramp = 10 seconds. The ramp is
changing with speed 20 kW per 10 seconds (2 kW/s).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 563


Subgroup: Q Ramp

Q Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 1 .. 60 [s]
Default value 10 s Force value YES
Step 1s
Comm object 16151 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts ramping time of BESS Required Q (page 865) from actual value to the new one
while PF/Q Control PTM Mode (page 356) = Q Control.This ramp is activated in case the BESS
Required Q (page 865) cross the limit defined by the setpoint Q Deadband (page 564).
See PF/Q Control (page 265)PF/Q control (page 262) for more information.

6 back to List of setpoints

Q Deadband

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0,0 .. 5,0 [%] of BESS Q (page 708)
Default value 2,0 % of BESS Q (page 708) Force value YES
Step 0,1 % of BESS Q (page 708)
Comm object 16150 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint prevents oscillation of BESS P (page 707) while PF/Q Control PTM Mode (page 356) =
Q Control.In case the BESS Required Q (page 865) cross the limit defined by this setpoint Q Ramp
(page 564) is activated.
See PF/Q Control (page 265)PF/Q control (page 262) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 564


Subgroup: Q(Um)

Q(Um) 0 Reference

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 75 .. 125 [%] of Q(Um) (page 967)
Default value 100 % of Q(Um) (page 967) Force value YES
Step 1 % of Q(Um) (page 967)
Comm object 16125 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts horizontal offset of Q(Um) (page 967) curve.
See Q(Um) (page 268)PF/Q control (page 262) for more information.

6 back to List of setpoints

Q(Um) Deadband

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0.0 .. 5,0 [%] of BESS Q (page 708)
Default value 0,0 % of BESS Q (page 708) Force value YES
Step 0,1 % of BESS Q (page 708)
Comm object 14127 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint prevents oscillation of BESS P (page 707) while PF/Q Control PTM Mode (page 356) =
Q(Um).In case the voltage cross the limit defined by this setpoint, the new value of BESS Required Q
(page 865) is calculated according to Q(Um) (page 967) curve.
See Q(Um) (page 268)PF/Q control (page 262) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 565


Subgroup: Qref/Ulim

Qref/Pnom Shift

Setpoint group Grid Codes Related FW 1.5.0


Range [units] -33 .. 33 [%] of Qref/Ulim (page 968)
Default value 0 % of Qref/Ulim (page 968) Force value YES
Step 1 % of Qref/Ulim (page 968)
Comm object 16128 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts vertical offset of Qref/Ulim (page 968) curve.
See Qref/Ulim (page 270)PF/Q control (page 262) for more information.

6 back to List of setpoints

Qref/Ulim Deadband

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0,0 .. 5,0 [%] of BESS Q (page 708)
Default value 0,0 % of BESS Q (page 708) Force value YES
Step 0,1 % of BESS Q (page 708)
Comm object 16129 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint prevents oscillation of BESS P (page 707) while PF/Q Control PTM Mode (page 356) =
Qref/Ulim.In case the voltage cross the limit defined by this setpoint, the new value of BESS Required Q
(page 865) is calculated according to Qref/Ulim (page 968) curve.
See Qref/Ulim (page 270)PF/Q control (page 262) for more information.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 566


Subgroup: Q(P)

Q(P) Deadband

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0,0 .. 5,0 [%] of BESS Q (page 708)
Default value 0,0 % of BESS Q (page 708) Force value YES
Step 0,1 % of BESS Q (page 708)
Comm object 16126 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint prevents oscillation of BESS P (page 707) while PF/Q Control PTM Mode (page 356) =
Q(P). In case the voltage cross the limit defined by this setpoint, the new value of BESS Required Q
(page 865) is calculated according to Q(P) (page 969) curve.
See Q(P) (page 269)PF/Q control (page 262) for more information.

6 back to List of setpoints

Subgroup: Soft Unload

Soft Unload Priority

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 254; OFF [-]
Default value 1 [-] Force value YES
Step 1 [-]
Comm object 14493 Related applications MINT, , SPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts priority of Soft Unload Ramp (page 568) which is used while LBO EVENT SOFT
UNLOAD (PAGE 1077) is closed.
Note: Smaller number means higher priority, e.i. 0 has highest priority.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 567


Soft Unload Ramp

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 0 .. 1800 [s]
Default value 60 s Force value YES
Step 1s
Comm object 16489 Related applications MINT, , SPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the ramping time of the BESS Required P (page 861) to the BESS Required P
Target (page 861) while soft unloading when BCB is requested to be opened.
The Required P reach the zero value at the end of the timer. The ramping time is set for ΔP which is given
by the setpoint Installed Power (page 375) or by the setpoint Nominal power (page 375) if the
Installed Power is OFF.
Example: Installed Power (page 375) = 20 kW, Soft Unload Ramp = 10 seconds. The ramp is
changing with speed 20 kW per 10 seconds (2 kW/s) to the zero value.

Note: This setpoint is shared with Soft Unload Ramp (page 479)

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 568


Subgroup: Pave

Pave Protection

Setpoint group Grid Codes Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Disabled Force value YES
Step [-]
Comm object 16649 Related applications MPTM
Config level Standard
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables/disables Pave (page 309) function.

Protection is enabled. Behavior of protection is adjusted via


Enabled
setpoint Pave (page 569).
Disabled Protection is disabled.
Protection is enabled or disabled by the state of LBI
Protection Force Disable 1
PROTECTION FORCE DISABLE 1 (PAGE 1016).
Protection is enabled or disabled by the state of LBI
Protection Force Disable 2
PROTECTION FORCE DISABLE 2 (PAGE 1017).
Protection is enabled or disabled by the state of LBI
Protection Force Disable 3
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

Pave

Setpoint group Grid Codes Related FW 1.5.0


Range [units] 1 .. 32000 [kW] (depends on the selected Power Formats And Units (page 196))
Default value 1 kW Force value YES
Step 1 kW
Comm object 16544 Related applications MPTM
Config level Standard
Only if Application Mode (page 885) = MPTM and Pave Protection (page 569)
Setpoint visibility
!= Disabled
Description
This setpoint defines the maximum exported power agreed with the grid.
According to this setpoint and LAI PMOM (PAGE 1125) is calculated value Pmom/Pave (page 832) which
is used in application curve P MOM/PAVE MAX (PAGE 972). It is used by the Pave (page 309) function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 569


Group: BESS Protections

Subgroup: Overload Protection

IDMT Overload Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 13231 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables IDMT Overload Protection.
Behavior of protection is adjusted via setpoints 2POverload Start Evaluation Level (page 446) and
2POverload Start Evaluation Delay (page 447). This protection activates alarm Sd IDMT Overload
(page 1287).
The reaction time is calculated by this formula:

IMPORTANT: If this protection is disabled, the BCB cannot be closed.

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

InteliNeo 6000 1.5.0 Global Guide 570


6 back to List of setpoints

Subgroup: Current Protection

Short Circuit Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-] [-]
Default value Enabled Force value YES
Step [-]
Comm object 15665 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables Short Circuit Protection.
Behavior of protection is adjusted via setpoints Short Circuit Protection (page 571) and Short Circuit
Delay (page 449). When value of BESS Current L1 (page 715), BESS Current L2 (page 715) and
BESS Current L3 (page 715) related to Nominal Current (page 376) cross over Short Circuit (page
448) for time longer than Short Circuit Delay (page 449) alarm PVBO Short Circuit (page 1288) is
activated.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

IDMT BESS >A Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 15666 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables IDMT BESS >A Protection.
Behavior of protection is adjusted via setpoints IDMT BESS >A Delay (page 449). This protection
activates alarm Sd IDMT BESS >A (page 1287).
The reaction time is calculated by this formula:

InteliNeo 6000 1.5.0 Global Guide 571


IBESS = Maximum (BESS Current L1 (page 715)andBESS Current L1 (page 715)
Note: Reaction time is limited to 3600 s = 60 minutes. IDMT protection is not active for Reaction time
values longer than 60 minutes.

Overcurrent
Overcurrent IDMT Delay
≤100 % 101 % 110 %
0.2 s No action 20 s 2s
Reaction Time
2s No action 200 s 20 s
20 s No action 2000 s 200 s

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 572


BESS Current Unbalance Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 15667 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS Current Unbalance Protection.
Protection is enabled. Behavior of protection is adjusted via setpoints BESS Current Unbalance (page
450) and BESS Current Unbalance Delay (page 450). When relative difference between BESS
currents is over setpoint BESS Current Unbalance (page 450) for time longer than BESS Current
Unbalance Delay (page 450)alarm Sd BESS Current Unbalance (page 1287) is activated.
IMPORTANT: Behavior of this protection is influenced by setpoint Connection type (page
378)

Connection
type (page Compared values (maximum difference)
378)
3Ph4Wire
High Leg D
(BESS Current L1 (page 715),BESS Current L1 (page 715)
3Ph3Wire
SplitPhase
MonoPhase No protection is evaluated.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 573


Subgroup: Voltage Protection

BESS >V

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20818 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS >V Protection.
Protection is enabled. Behavior of protection is adjusted via setpoints BESS >VUndervoltage (page 1)
and BESS >V Delay (page 452). When BESS voltage exceeds limit set by BESS >VUndervoltage
(page 1) for time longer than BESS >V Delay (page 452) appropriate alarm is activated.

Value Alarm
BESS Voltage L1-N (page 713) Sd BESS >V L1-N (page 1283)
BESS Voltage L2-N (page 713) Sd BESS >V L2-N (page 1283)
BESS Voltage L3-N (page 713) Sd BESS >V L3-N (page 1283)
BESS Voltage L1-L2 (page 713) Sd BESS >V L1-L2 (page 1283)
BESS Voltage L2-L3 (page 714) Sd BESS >V L2-L3 (page 1284)
BESS Voltage L3-L1 (page 714) Sd BESS >V L3-L1 (page 1284)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 574


BESS >>V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20817 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS >>V Protection..
Behavior of protection is adjusted via setpoints BESS >>V (page 452) and BESS >>V Delay (page
453). When BESS voltage exceeds limit set by BESS >>V (page 452) for time longer than BESS >>V
Delay (page 453) appropriate alarm is activated.

Value Alarm
BESS Voltage L1-N (page 713) Sd BESS >>V L1-N (page 1281)
BESS Voltage L2-N (page 713) Sd Mains/Bus >>V L2-N (page 1281)
BESS Voltage L3-N (page 713) Sd BESS >>V L3-N (page 1282)
BESS Voltage L1-L2 (page 713) WRN BESS >>V L1-L2 (page 1282)
BESS Voltage L2-L3 (page 714) WRN BESS >>V L2-L3 (page 1282)
BESS Voltage L3-L1 (page 714) WRN BESS >>V L3-L1 (page 1282)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 575


BESS <V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20819 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS <V Protection.
Behavior of protection is adjusted via setpoints BESS <V (page 453) and BESS <V Delay (page 454)
When BESS voltage drops below limit set by BESS <V (page 453) for time longer than BESS <V Delay
(page 454) appropriate alarm is activated.

Value Alarm
BESS Voltage L1-N (page 713) Sd BESS <V L1-N (page 1284)
BESS Voltage L2-N (page 713) Sd BESS <V L2-N (page 1284)
BESS Voltage L3-N (page 713) Sd BESS <V L3-N (page 1285)
BESS Voltage L1-L2 (page 713) Sd BESS <V L1-L2 (page 1285)
BESS Voltage L2-L3 (page 714) Sd BESS <V L2-L3 (page 1285)
BESS Voltage L3-L1 (page 714) Sd BESS >V L3-L1 (page 1284)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

BESS V Unbalance Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 15669 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description

InteliNeo 6000 1.5.0 Global Guide 576


This setpoint enables or disables BESS V Unbalance Protection.
Behavior of protection is adjusted via setpoints BESS V Unbalance (page 454) and BESS V
Unbalance Delay (page 454). When relative difference between BESS voltages is over setpoint BESS
V Unbalance (page 454) for time longer than BESS V Unbalance Delay (page 454) alarm Sd BESS V
Unbalance Ph-N (page 1286) or Sd BESS V Unbalance Ph-Ph (page 1286) is activated.
IMPORTANT: Behavior of this protection is influenced by setpoint Connection type (page
378)

Connection
type (page Compared values (maximum difference)
378)
BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS
Voltage L3-N (page 713)
3Ph4Wire OR
BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and
BESS Voltage L3-L1 (page 714)
BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and
High Leg D
BESS Voltage L3-L1 (page 714)
BESS Voltage L1-L2 (page 713), BESS Voltage L2-L3 (page 714) and
3Ph3Wire
BESS Voltage L3-L1 (page 714)
BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS
SplitPhase
Voltage L3-N (page 713)
MonoPhase No protection is evaluated.
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

Mains >V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20806 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables or disables Mains >V Protection.

InteliNeo 6000 1.5.0 Global Guide 577


Behavior of protection is adjusted via setpoints Mains >V (page 523), Mains >V Delay (page 523) and
Mains >V Hys (page 524). When Mains voltage exceeds limit set by Mains >V (page 523) for period
longer than Mains >V Delay (page 523) relevant history records is written to the history and MCB is
opened if:
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains >V can have hysteresis set by Mains >V Hys (page 524).

Value History Record


Mains/Bus Voltage L1-N (page 839) MAINS/BUS >V L1-N (PAGE 1301)
Mains/Bus Voltage L2-N (page 839) MAINS/BUS >V L2-N (PAGE 1301)
Mains/Bus Voltage L3-N (page 840) MAINS/BUS >V L3-N (PAGE 1302)
Mains/Bus Voltage L1-L2 (page 840) MAINS/BUS >V L1-L2 (PAGE 1303)
Mains/Bus Voltage L2-L3 (page 840) MAINS/BUS >V L2-L3 (PAGE 1304)
Mains/Bus Voltage L3-L1 (page 840) MAINS/BUS >V L3-L1 (PAGE 1304)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 578


Mains >>V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20805 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables or disables Mains >>V Protection.
Behavior of protection is adjusted via setpoints Mains >>V (page 524), Mains >>V Delay (page 525)
and Mains >>V Hys (page 525). When Mains voltage exceeds limit set by Mains >>V (page 524) for
period longer than Mains >>V Delay (page 525) relevant history records is written to the history and
MCB is opened if:
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains >>V can have hysteresis set by Mains >>V Hys (page 525).

Value History Record


Mains/Bus Voltage L1-N (page 839) MAINS/BUS >>V L1-N (PAGE 1305)
Mains/Bus Voltage L2-N (page 839) MAINS/BUS >>V L2-N (PAGE 1306)
Mains/Bus Voltage L3-N (page 840) MAINS/BUS >>V L3-N (PAGE 1307)
Mains/Bus Voltage L1-L2 (page 840) MAINS/BUS >>V L1-L2 (PAGE 1307)
Mains/Bus Voltage L2-L3 (page 840) MAINS/BUS >>V L2-L3 (PAGE 1308)
Mains/Bus Voltage L3-L1 (page 840) MAINS/BUS >>V L3-L1 (PAGE 1309)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 579


Mains 10min Avg >V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 13233 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables or disables Mains 10min Avg >V Protection.
Behavior of protection is adjusted via setpoint Mains 10min Avg >V (page 526). When measured value
exceeds limit set by Mains 10min Avg >V (page 526) and the Mains 10min Avg >V Delay (page 526)
is elapsed the relevant history records is written to the history and MCB is opened if:
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO

Value History Record


Mains Voltage 10min Avg L1-N (page 849) MP Mains 10minAvg >V L1-N
Mains Voltage 10min Avg L2-N (page 849) MP Mains 10minAvg >V L2-N
Mains Voltage 10min Avg L3-N (page 849) MP Mains 10minAvg >V L3-N
Mains Voltage 10min Avg L1-L2 (page 851) MP Mains 10minAvg >V L1-L2
Mains Voltage 10min Avg L2-L3 (page 851) MP Mains 10minAvg >V L2-L3
Mains Voltage 10min Avg L3-L1 (page 851) MP Mains 10minAvg >V L3-L1
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 580


Mains <V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20807 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables or disables Mains <V Protection.
Behavior of protection is adjusted via setpoints Mains <V (page 527), Mains <V Delay (page 527) and
Mains <V Hys (page 528). When Mains voltage drops bellow limit set by Mains <V (page 527) for
period longer than Mains <V Delay (page 527) relevant history records is written to the history and MCB
is opened if:
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains <V can have hysteresis set by Mains <V Hys (page 528).

Value History Record


Mains/Bus Voltage L1-N (page 839) MAINS/BUS <V L1-N (PAGE 1310)
Mains/Bus Voltage L2-N (page 839) MAINS/BUS <V L2-N (PAGE 1310)
Mains/Bus Voltage L3-N (page 840) MAINS/BUS <V L3-N (PAGE 1311)
Mains/Bus Voltage L1-L2 (page 840) MAINS/BUS <V L1-L2 (PAGE 1312)
Mains/Bus Voltage L2-L3 (page 840) MAINS/BUS <V L2-L3 (PAGE 1313)
Mains/Bus Voltage L3-L1 (page 840) MAINS/BUS <V L3-L1 (PAGE 1313)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 581


Mains <V Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20808 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables or disables Mains <<V Protection.
Behavior of protection is adjusted via setpoints Mains <<V (page 528), Mains <<V Delay (page 529)
and Mains <<V Hys (page 529). When Mains voltage drops bellow limit set by Mains <<V (page 528)
for period longer than Mains <<V Delay (page 529) relevant history records is written to the history and
MCB is opened if:
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains <<V can have hysteresis set by Mains <<V Hys (page 529).

Value History Record


Mains/Bus Voltage L1-N (page 839) MAINS/BUS <<V L1-N (PAGE 1314)
Mains/Bus Voltage L2-N (page 839) MAINS/BUS <<V L2-N (PAGE 1315)
Mains/Bus Voltage L3-N (page 840) MAINS/BUS <<V L3-N (PAGE 1316)
Mains/Bus Voltage L1-L2 (page 840) MAINS/BUS <<V L1-L2 (PAGE 1316)
Mains/Bus Voltage L2-L3 (page 840) MAINS/BUS <<V L2-L3 (PAGE 1317)
Mains/Bus Voltage L3-L1 (page 840) MAINS/BUS <<V L3-L1 (PAGE 1318)
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 582


Mains V Unbalance Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20798 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint enables or disables Mains V Unbalance Protection.
Behavior of protection is adjusted via setpoints Mains V Unbalance (page 530) and Mains V
Unbalance Delay (page 530). When relative difference between Mains current is over setpoint Mains V
Unbalance (page 530) for time longer than Mains V Unbalance Delay (page 530) alarm Mains/Bus
V Unbalance Ph-N (page 1321) or Mains/Bus V Unbalance Ph-Ph (page 1321) is activated.
IMPORTANT: Behavior of this protection is influenced by setpoint Connection type (page
378)

Connection type
Compared values (maximum difference)
(page 378)
Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page
839) and Mains/Bus Voltage L3-N (page 840)
3Ph4Wire OR
Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
840) and Mains/Bus Voltage L3-L1 (page 840)
Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
High Leg D
840) and Mains/Bus Voltage L3-L1 (page 840)
Mains/Bus Voltage L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page
3Ph3Wire
840) and Mains/Bus Voltage L3-L1 (page 840)
Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N (page
SplitPhase
839) and Mains/Bus Voltage L3-N (page 840)
MonoPhase No protection is evaluated.

List of History Records


Mains V Unbalance Ph-N
Mains V Unbalance Ph-Ph
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 583


Subgroup: Frequency Protection

BESS >f Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20809 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS >f Protection.
Behavior of protection is adjusted via setpoints BESS >f (page 455) and BESS >f Delay (page 455).
When BESS Frequency (page 713) exceeds maximal accepted frequency for period longer than BESS
>f Delay (page 455) alarm Sd BESS >f (page 1286) is activated.
Note: fmax = Nominal Frequency (page 384) + BESS >f (page 455)

Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 584


BESS <f Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20810 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS <f Protection.
Behavior of protection is adjusted via setpoints BESS <f (page 456) and BESS <f Delay (page 456).
When BESS Frequency (page 713) drops below minimal accepted frequency for period longer than
BESS <f Delay (page 456) alarm Sd BESS <f (page 1286) is activated.
Note: fmin = Nominal Frequency (page 384) + BESS <f (page 456)

Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).
IMPORTANT: If this protection is disabled, the BCB cannot be closed.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 585


Mains >f Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20802 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the behavior Mains >f Protection.
Behavior of protection is adjusted via setpoints Mains >f (page 531), Mains >f Delay (page 531) and
Mains >f Hys (page 531). When Mains/Bus Frequency (page 839) exceeds maximal accepted
frequency for period longer than Mains >f Delay (page 531)alarm MAINS/BUS >F (PAGE 1319) is
activated.
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains >f can have hysteresis set by Mains >f Hys (page 531).
Note: fmax = Nominal Frequency (page 384) + Mains >f (page 531)

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 586


Mains >>f Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20801 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the behavior Mains >>f Protection.
Behavior of protection is adjusted via setpoints Mains >>f (page 532), Mains >>f Delay (page 532) and
Mains >>f Hys (page 532). When Mains/Bus Frequency (page 839) exceeds maximal accepted
frequency for period longer than Mains >>f Delay (page 532) alarm MAINS/BUS >>F (PAGE 1319) is
activated.
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains >>f can have hysteresis set by Mains >>f Hys (page 532).
Note: fmax = Nominal Frequency (page 384) + Mains >>f (page 532)

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 587


Mains <f Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20803 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the behavior Mains <f Protection.
Behavior of protection is adjusted via setpoints Mains <f (page 533), Mains <f Delay (page 533) and
Mains <f Hys (page 533). When Mains/Bus Frequency (page 839) drops bellow minimal accepted
frequency for period longer than Mains <f Delay (page 533) alarm MAINS/BUS <F (PAGE 1320) is
activated.
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains <f can have hysteresis set by Mains <f Hys (page 533).
Note: fmin = Nominal Frequency (page 384) - Mains <f (page 533)

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 588


Mains <<f Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20804 Related applications MPTM
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MPTM
Description
This setpoint adjusts the behavior Mains <<f Protection.
Behavior of protection is adjusted via setpoints Mains <<f (page 534), Mains <<f Delay (page 534) and
Mains <<f Hys (page 534). When Mains/Bus Frequency (page 839) drops bellow minimal accepted
frequency for period longer than Mains <<f Delay (page 534) alarm MAINS/BUS <<F (PAGE 1320) is
activated.
Controller Mode (page 385) = OFF
Controller Mode (page 385) = MAN
and Breaker state (page 886) = ParalOper
Controller Mode (page 385) = AUTO
Return from Mains <<f can have hysteresis set by Mains <<f Hys (page 534).
Note: fmin = Nominal Frequency (page 384) - Mains <<f (page 534)

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 589


Subgroup: Bus Meas Error

Bus Meas Error

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 10558 Related applications MINT
Config level Advanced
Setpoint visibility Only if Application Mode (page 885) = MINT
Description
This setpoint enables or disables Bus Measurement Error protection.
Alarm Stp Bus Meas Error (page 1290) is activated if controller detects a mismatch between the
expected and currently measured voltage on the bus for period longer than 20 s. Mismatch means that
measured voltage is lower/higher than Bus Dead Level (page 383), although the controller receives
information about closed/opened breaker.
Setpoint options:
Enabled / Disabled : Protection is enabled / disabled .
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 590


Subgroup: Earth Fault Current Protection

InteliNeo 6000 1.5.0 Global Guide 591


Earth Fault Current Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 10180 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables Earth Fault Current Protection.
Bbehavior is adjusted via setpoints IDMT Earth Fault Current Sd (page 457) and IDMT Earth Fault
Current Delay (page 458). When the protection is triggered the alarm Sd IDMT Earth Fault Current
(page 1287) is activated.
The reaction time is calculated by this formula:

Igen = Maximum (BESS Current L1 (page 715), BESS Current L2 (page 715), BESS Current L3
(page 715))
Example:
IDMT Earth Fault Current Sd (page 457) = 10 A

Igen [A]
Delay [s]
≤10 A 11 A 20 A
0.1 No Reaction 1 0.1
Reaction Time
1 No Reaction 10 1
[s]
10 No Reaction 100 10

InteliNeo 6000 1.5.0 Global Guide 592


IMPORTANT: The Earth Fault Current Protection and Mains Import Measurement (page
175) shares same physical input ⑰ AUX CURRENT (page 47) . At one moment this input
can be used only for one purpose. The protection will work only if Mains Measurement P
(page 364) and Mains Measurement Q (page 365) != Mains CT.

Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

Subgroup: Loss of Mains Protections

Vector Shift Protection

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Parallel Only / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 10551 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables the function of the built-in Vector Shift protection.
Behavior of protection is adjusted via setpoints Vector Shift Limit (page 518) and Vector Shift/ROCOF
CB Selector (page 522). When measured vector shift on Mains/Bus Voltage L1-N (page 839) is over
the Vector Shift Limit (page 518), breaker specified in Vector Shift/ROCOF CB Selector (page 522)
is opened and history record Vector Shift is written to the history.
Note: If a vector shift is detected and consequently the MCB is opened, however Mains voltage and
frequency remain in limits, the MCB is reclosed again after Mains Return Delay (page 1), as the
Mains is evaluated as healthy.

Enabled Protection is always active while MCB is closed.


Protection is active only if Breaker state (page 886) = ParalOper i.e. MCB and
Parallel Only
BCB are closed.
Disabled Protection is disabled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 593


ROCOF1 Protection

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Parallel Only / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 9840 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables the function of the built-in ROCOF1 Protection.
Behavior of protection is adjusted via setpoints ROCOF1 Windows Length (page 518), ROCOF1 df/dt
(page 519) and Vector Shift/ROCOF CB Selector (page 522).
When measured ROCOF1 (page 852) on Mains/Bus Frequency (page 839) is over ROCOF1 df/dt
(page 519) in respective period given by ROCOF1 Windows Length (page 518), breaker specified in
Vector Shift/ROCOF CB Selector (page 522) is opened and history record ROCOF is written to the
history. Maximal ROCOF is stored in Max ROCOF1 (page 853) which is reset every time when the
breaker is closed again.
Note: If a ROCOF is detected and consequently the MCB is opened, however Mains voltage and
frequency remain in limits, the MCB is reclosed again after MCB Close Delay (page 535), as the Mains is
evaluated as healthy.

Enabled Protection is always active while MCB is closed.


Protection is active only if Breaker state (page 886) = ParalOper i.e. MCB and
Parallel Only
BCB are closed.
Disabled Protection is disabled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 594


ROCOF2 Protection

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Parallel Only / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16145 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables the function of the built-in ROCOF2 Protection.
Behavior of protection is adjusted via setpoints ROCOF2 Windows Length (page 519), ROCOF2 df/dt
(page 520) and Vector Shift/ROCOF CB Selector (page 522).
When measured ROCOF2 (page 853) on Mains/Bus Frequency (page 839) is over ROCOF2 df/dt
(page 520) in respective time given by ROCOF2 Windows Length (page 519), breaker specified in
Vector Shift/ROCOF CB Selector (page 522) is opened and history record ROCOF is written to the
history. Maximal ROCOF is stored in Max ROCOF2 (page 854) which is reset every time when the
breaker is closed again.
Note: If a ROCOF is detected and consequently the MCB is opened, however Mains voltage and
frequency remain in limits, the MCB is reclosed again after MCB Close Delay (page 535), as the Mains
is evaluated as healthy.

Enabled Protection is always active while MCB is closed.


Protection is active only if Breaker state (page 886) = ParalOper i.e. MCB
Parallel Only
and BCB are closed.
Disabled Protection is disabled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 595


ROCOF3 Protection

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Parallel Only / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16146 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables the function of the built-in ROCOF3 Protection.
Behavior of protection is adjusted via setpoints ROCOF3 Windows Length (page 520), ROCOF3 df/dt
(page 521) and Vector Shift/ROCOF CB Selector (page 522).
When measured ROCOF3 (page 854) on Mains/Bus Frequency (page 839) is over ROCOF3 df/dt
(page 521) in respective time given by ROCOF3 Windows Length (page 520), breaker specified in
Vector Shift/ROCOF CB Selector (page 522) is opened and history record ROCOF is written to the
history. Maximal ROCOF is stored in Max ROCOF3 (page 855) which is reset every time when the
breaker is closed again.
Note: If a ROCOF is detected and consequently the MCB is opened, however Mains voltage and
frequency remain in limits, the MCB is reclosed again after MCB Close Delay (page 535), as the Mains
is evaluated as healthy.

Enabled Protection is always active while MCB is closed.


Protection is active only if Breaker state (page 886) = ParalOper i.e. MCB and
Parallel Only
BCB are closed.
Disabled Protection is disabled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 596


ROCOF4 Protection

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Parallel Only / Disabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 16147 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables the function of the built-in ROCOF4 Protection.
Behavior of protection is adjusted via setpoints ROCOF4 Windows Length (page 521), ROCOF4 df/dt
(page 522) and Vector Shift/ROCOF CB Selector (page 522).
When measured ROCOF4 (page 855) on Mains/Bus Frequency (page 839) is over ROCOF4 df/dt
(page 522) in respective time given by ROCOF4 Windows Length (page 521), breaker specified in
Vector Shift/ROCOF CB Selector (page 522) is opened and history record ROCOF is written to the
history. Maximal ROCOF is stored in Max ROCOF4 (page 856) which is reset every time when the
breaker is closed again.
Note: If a ROCOF is detected and consequently the MCB is opened, however Mains voltage and
frequency remain in limits, the MCB is reclosed again after MCB Close Delay (page 535), as the Mains
is evaluated as healthy.

Enabled Protection is always active while MCB is closed.


Protection is active only if Breaker state (page 886) = ParalOper i.e. MCB
Parallel Only
and BCB are closed.
Disabled Protection is disabled.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 597


Subgroup: SOC Protection

BESS <SOC Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20260 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if the setpoint BESS (page 372) = Installed
Description
This setpoint enables or disables BESS <SOC Protection. When BESS SOC (page 716) exceeds limit
set by the setpoint BESS <f Delay (page 458) the alarm Wrn SOC Low Alarm (page 1266).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

BESS >SOC Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20259 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if the setpoint BESS (page 372) = Installed
Description
This setpoint enables or disables BESS >SOC Protection. When BESS SOC (page 716) exceeds limit
set by the setpoint SOC High Alarm (page 459) the alarm Wrn SOC High Alarm (page 1266).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 598


BESS <<SOC Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20258 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if the setpoint BESS (page 372) = Installed
Description
This setpoint enables or disables BESS <<SOC Protection. When BESS SOC (page 716) exceeds limit
set by the setpoint SOC Critical Low (page 459) the alarm Sd SOC Critical Low (page 1288).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

BESS >>SOC Protection

Setpoint group BESS Protections Related FW 1.5.0


Enabled / Disabled / Protection Force Disable 1 / Protection Force Disable 2 /
Range [units]
Protection Force Disable 3 [-]
Default value Enabled Force value YES
Step [-]
Comm object 20257 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if the setpoint BESS (page 372) = Installed
Description
This setpoint enables or disables BESS >>SOC Protection. When BESS SOC (page 716) exceeds limit
set by the setpoint SOC Critical High (page 460) the alarm Sd SOC Critical High (page 1288).
Setpoint options:
Enabled / Disabled: Protection is enabled / disabled.
Protection Force Disable 1 / 2 / 3: Protection is enabled or disabled by the state of LBI
PROTECTION FORCE DISABLE 1 (PAGE 1016) / PROTECTION FORCE DISABLE 2 (PAGE 1017) /
PROTECTION FORCE DISABLE 3 (PAGE 1017).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 599


BESS SOC Not Configured

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Disabled
Default value Enabled Force value YES
Step [-]
Comm object 19646 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables configuration of BESS SOC.

6 back to List of setpoints

BESS SOC Not Available

Setpoint group BESS Protections Related FW 1.5.0


Range [units] Enabled / Disabled
Default value Enabled Force value YES
Step [-]
Comm object 19647 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables or disables BESS SOC.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 600


Group: Load Shedding

Subgroup: Load Shedding

Load Shedding Active

Setpoint group Load Shedding Related FW 1.5.0


Range [units] Disabled / Island only / IsL+Trip paral / All the time [-]
Default value Disabled Force value YES
Step [-]
Comm object 11001 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Allways
Description
This setpoint adjusts the activation of the Load Shedding (page 171) function.
Disabled – Function is disabled.
Island only – Function is active when Breaker state (page 886) = IslOper or Breaker state
(page 886) = MultIslOp.
Load shedding outputs (page 171) are closed/opened one by one in island operations
All Load shedding outputs (page 171) are closed at once when the BESS comes into the
island operation if MCB and BCB were opened -> BESS started -> BCB closed.
IsL+Trip paral – Function behaves same as Load Shedding Active = Island only and adds load
shedding when Breaker state (page 886) is changed from ParalOper/MultParOp to
IslOper/MultIslOp .
Load shedding outputs (page 171) are closed/opened one by one in island operations
All Load shedding outputs (page 171) are closed at once when the BESS changes into
island operation state in this way: MCB and BCB were opened -> BESS started -> BCB closed.
All Load shedding outputs (page 171) are closed at once when the BESS changes into
island operation state in this way: MCB and BCB were closed -> MCB opened.
All the time – Function is active regardless of Breaker state (page 886).
All Load shedding outputs (page 171) are never tripped at once when BCB is closed into
parallel operation.
All Load shedding outputs (page 171) are tripped at once when BCB is closed into island
operation.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 601


Auto Load Reconnection

Setpoint group Load Shedding Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 9649 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint enables/disables Automatic Load Shedding (page 171).

Rising edge of LBI MANUAL LOAD RECONNECTION (PAGE 1011) lowers the load
Disabled reduction stage by one while BESS P (page 707) drops under Power Load
Reconnection Level (page 604).
Load reduction stage is lowered by one when BESS P (page 707) drops under
Enabled Power Load Reconnection Level (page 604) and period of Load Reconnection
Delay (page 602) elapsed from last load reduction stage lowering.

6 back to List of setpoints

Load Reconnection Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0..600 [s]
Default value 10 s Force value YES
Step 1s
Comm object 8893 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the delay between load reconnection during Load Shedding (page 171) function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 602


Subgroup: Power Load Shedding

Power Load Shedding

Setpoint group Load Shedding Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 19681 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
Enables or Disables the Power Load Shedding function.
6 back to List of setpoints

Power Load Shedding Level

Setpoint group Load Shedding Related FW 1.5.0


Power Load Reconnection Level (page 604) .. 200 [%] of Installed Power
Range [units]
(page 375) or Nominal power (page 375)
80 % of Installed Power (page 375) or
Default value Force value YES
Nominal power (page 375)
Step 1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 8884 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts decisive level for load disconnection during Load Shedding (page 171) function.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 603


Power Load Shedding Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.0..600.0 [s]
Default value 10 s Force value YES
Step 1s
Comm object 8887 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the delay between load disconnections during Load Shedding (page 171)
function.

6 back to List of setpoints

Power Load Reconnection Level

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0 .. 20 [%] of Installed Power (page 375) or Nominal power (page 375)
20 % of Installed Power (page
Default value 375) or Nominal power (page Force value YES
375)
Step 1 % of Installed Power (page 375) or Nominal power (page 375)
Comm object 8890 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the decisive level between load reconnection during Load Shedding (page 171)
function.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 604


Subgroup: Apparent Load Shedding

Apparent Power Load Shedding

Setpoint group Load Shedding Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 19682 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
Enables or Disables the Current Load Shedding function.

6 back to List of setpoints

Apparent Power Load Shedding Level

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 20 .. 200 [%] of Nominal power (page 375)
Default value 80 % of Nominal power (page 375) Force value YES
Step 1 % of Nominal power (page 375)
Comm object 8885 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts decisive level for current disconnection during Load Shedding (page 171)
function.

6 back to List of setpoints

Apparent Power Load Shedding Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 10 s Force value YES
Step 1s
Comm object 8888 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the delay between load disconnections during Load Shedding (page 171)
function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 605


Apparent Power Load Reconnection Level

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0 .. 20 [%] of Nominal power (page 375)
20 % of Nominal power (page
Default value Force value YES
375)
Step 1 % of Nominal power (page 375)
Comm object 8891 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the decisive level between load reconnection during Load Shedding (page 171)
function.

6 back to List of setpoints

Subgroup: Voltage Load Shedding

Frequency Load Shedding

Setpoint group Load Shedding Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 19683 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
Enables or Disables the Voltage Load Shedding function.
6 back to List of setpoints

Frequency Load Shedding Level

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 20 .. 200 [%] of Nominal power (page 375)
Default value 80 % of Nominal power (page 375) Force value YES
Step 1 % of Nominal power (page 375)
Comm object 8886 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) != Disabled
Description
This setpoint adjusts decisive level for voltage disconnection during Load Shedding (page 171)
function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 606


Voltage Load Shedding Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.0..600.0 [s]
Default value 10 s Force value YES
Step 1s
Comm object 8889 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the delay between load disconnections during Load Shedding (page 171)
function.

6 back to List of setpoints

Frequency Load Reconnection Level

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0 .. 20 [%] of Nominal power (page 375)
20 % of Nominal power (page
Default value Force value YES
375)
Step 1 % of Nominal power (page 375)
Comm object 8892 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
This setpoint adjusts the decisive level between load reconnection during Load Shedding (page 171)
function.

6 back to List of setpoints

Subgroup: Battery SOC Load Shedding

Battery SOC Load Shedding

Setpoint group Load Shedding Related FW 1.5.0


Range [units] Disabled / Enabled [-]
Default value Disabled Force value YES
Step [-]
Comm object 19684 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Always
Description
Enables or Disables the Frequency Load Shedding function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 607


Battery SOC Load Shedding Level 1 Reconnection Level

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.00 .. Battery SOC Shedding Level 1 (page 609) [Hz]
Default value 0.50 [Hz] Force value YES
Step 0.01 [Hz]
Comm object 19686 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
Frequency Load Reconnection Level specifies the threshold value for reconnection of the shedded load.
Load reconnection can be either automatic or manual based on the value of Auto Load Reconnection
Enabled or Disabled respectively.

Load shedding LBO is deactivated if and only if the Source Frequency remains
Enabled smaller than the specified value for the duration given by the setpoint Battery SOC
Shedding Level 1 Delay (page 609).
Load is reconnected only if rising edge on LBI MANUAL LOAD RECONNECTION (PAGE
1011) is received and the Source Frequency is smaller than Frequency Load
Disabled
Reconnection Level, Battery SOC Shedding Level 1 Delay (page 609) is
disregarded.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 608


Battery SOC Shedding Level 1

Setpoint group Load Shedding Related FW 1.5.0


Battery SOC Load Shedding Level 1 Reconnection Level (page 608) .. 5.00
Range [units]
[Hz]
Default value 1.00 [Hz] Force value YES
Step 0.01 [Hz]
Comm object 19688 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) != Disabled
Description
Battery SOC Load Shedding is a function which prevents the deeper/faster discharging of the BESS.
It uses the same load shedding outputs like Power or Frequency load shedding, but it works only for
first three stages LBO LOAD SHEDDING STAGE 1 (PAGE 1085), LBO LOAD SHEDDING STAGE 2 (PAGE
1085), LBO LOAD SHEDDING STAGE 3 (PAGE 1086).
The Stage 1 is tripped if the SOC Level (Value BESS SOC (page 716)) gets under the limit given by
setpoint Battery SOC Shedding Level 1 at least for time Battery SOC Shedding Level 1 Delay
(page 609). The Load Shedding Stage 1 is deactivated (the LBO LOAD SHEDDING STAGE 1 (PAGE
1085) is inactive) once the SOC rise over the Battery SOC Load Shedding Level 1 Reconnection
Level (page 608) for time given by setpoint Load Reconnection Delay (page 602).

6 back to List of setpoints

Battery SOC Shedding Level 1 Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 10 s Force value YES
Step 1s
Comm object 19687 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
Battery SOC Load Shedding is a function which prevents the deeper/faster discharging of the BESS.
It uses the same load shedding outputs like Power or Frequency load shedding, but it works only for
first three stages LBO LOAD SHEDDING STAGE 1 (PAGE 1085), LBO LOAD SHEDDING STAGE 2 (PAGE
1085), LBO LOAD SHEDDING STAGE 3 (PAGE 1086).
The Stage 1 is tripped if the SOC Level (Value BESS SOC (page 716)) gets under the limit given by
setpoint Battery SOC Shedding Level 1 at least for time Battery SOC Shedding Level 1 Delay
(page 609). The Load Shedding Stage 1 is deactivated (the LBO LOAD SHEDDING STAGE 1 (PAGE
1085) is inactive) once the SOC rise over the Battery SOC Load Shedding Level 1 Reconnection
Level (page 608) for time given by setpoint Load Reconnection Delay (page 602).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 609


Battery SOC Shedding Level 2

Setpoint group Load Shedding Related FW 1.5.0


Battery SOC Load Shedding Level 1 Reconnection Level (page 608) .. 5.00
Range [units]
[Hz]
Default value 1.00 [Hz] Force value YES
Step 0.01 [Hz]
Comm object 18580 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) != Disabled
Description
Battery SOC Load Shedding is a function which prevents the deeper/faster discharging of the BESS.
It uses the same load shedding outputs like Power or Frequency load shedding, but it works only for
first three stages LBO LOAD SHEDDING STAGE 1 (PAGE 1085), LBO LOAD SHEDDING STAGE 2 (PAGE
1085), LBO LOAD SHEDDING STAGE 3 (PAGE 1086).
The Stage 2 is tripped if the SOC Level (Value BESS SOC (page 716)) gets under the limit given by
setpoint Battery SOC Shedding Level 2 at least for time Battery SOC Shedding Level 2 Delay
(page 610). The Load Shedding Stage 2 is deactivated (the LBO LOAD SHEDDING STAGE 2 (PAGE
1085) is inactive) once the SOC rise over the Battery SOC Shedding Level 1 (page 609) for time
given by setpoint Load Reconnection Delay (page 602).

6 back to List of setpoints

Battery SOC Shedding Level 2 Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 10 s Force value YES
Step 1s
Comm object 18582 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
Battery SOC Load Shedding is a function which prevents the deeper/faster discharging of the BESS.
It uses the same load shedding outputs like Power or Frequency load shedding, but it works only for
first three stages LBO LOAD SHEDDING STAGE 1 (PAGE 1085), LBO LOAD SHEDDING STAGE 2 (PAGE
1085), LBO LOAD SHEDDING STAGE 3 (PAGE 1086).
The Stage 2 is tripped if the SOC Level (Value BESS SOC (page 716)) gets under the limit given by
setpoint Battery SOC Shedding Level 2 at least for time Battery SOC Shedding Level 2 Delay
(page 610). The Load Shedding Stage 2 is deactivated (the LBO LOAD SHEDDING STAGE 2 (PAGE
1085) is inactive) once the SOC rise over the Battery SOC Shedding Level 1 (page 609) for time
given by setpoint Load Reconnection Delay (page 602).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 610


Battery SOC Shedding Level 3

Setpoint group Load Shedding Related FW 1.5.0


Battery SOC Load Shedding Level 1 Reconnection Level (page 608) .. 5.00
Range [units]
[Hz]
Default value 1.00 [Hz] Force value YES
Step 0.01 [Hz]
Comm object 18581 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) != Disabled
Description
Battery SOC Load Shedding is a function which prevents the deeper/faster discharging of the BESS.
It uses the same load shedding outputs like Power or Frequency load shedding, but it works only for
first three stages LBO LOAD SHEDDING STAGE 1 (PAGE 1085), LBO LOAD SHEDDING STAGE 2 (PAGE
1085), LBO LOAD SHEDDING STAGE 3 (PAGE 1086).
The Stage 2 is tripped if the SOC Level (Value BESS SOC (page 716)) gets under the limit given by
setpoint Battery SOC Shedding Level 3 at least for time Battery SOC Shedding Level 3 Delay
(page 611). The Load Shedding Stage 3 is deactivated (the LBO LOAD SHEDDING STAGE 3 (PAGE
1086) is inactive) once the SOC rise over the Battery SOC Shedding Level 2 (page 610) for time
given by setpoint Load Reconnection Delay (page 602).

6 back to List of setpoints

Battery SOC Shedding Level 3 Delay

Setpoint group Load Shedding Related FW 1.5.0


Range [units] 0.0 .. 600.0 [s]
Default value 10 s Force value YES
Step 1s
Comm object 18583 Related applications MINT, MPTM
Config level Advanced
Setpoint visibility Only if Load Shedding Active (page 601) is not Disabled
Description
Battery SOC Load Shedding is a function which prevents the deeper/faster discharging of the BESS.
It uses the same load shedding outputs like Power or Frequency load shedding, but it works only for
first three stages LBO LOAD SHEDDING STAGE 1 (PAGE 1085), LBO LOAD SHEDDING STAGE 2 (PAGE
1085), LBO LOAD SHEDDING STAGE 3 (PAGE 1086).
The Stage 1 is tripped if the SOC Level (Value BESS SOC (page 716)) gets under the limit given by
setpoint Battery SOC Shedding Level 1 at least for time Battery SOC Shedding Level 1 Delay
(page 609). The Load Shedding Stage 1 is deactivated (the LBO LOAD SHEDDING STAGE 1 (PAGE
1085) is inactive) once the SOC rise over the Battery SOC Load Shedding Level 1 Reconnection
Level (page 608) for time given by setpoint Load Reconnection Delay (page 602).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 611


Group: User Buttons

Subgroup: User Buttons

User Button 1

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20826 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 1 which is part of User Buttons (page 224).

COMMAND User Button 1 is controlled by command from External display (page 79).
Value of the User Button 1 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 1 is still 0.

6 back to List of setpoints

User Button 2

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20827 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 2 which is part of User Buttons (page 224).

COMMAND User Button 2 is controlled by command from External display (page 79).
Value of the User Button 2 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 2 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 612


User Button 3

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20828 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 3 which is part of User Buttons (page 224).

COMMAND User Button 3 is controlled by command from External display (page 79).
Value of the User Button 3 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 3 is still 0.

6 back to List of setpoints

User Button 4

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20829 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 4 which is part of User Buttons (page 224).

COMMAND User Button 4 is controlled by command from External display (page 79).
Value of the User Button 4 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 4 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 613


User Button 5

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20830 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 5 which is part of User Buttons (page 224).

COMMAND User Button 5 is controlled by command from External display (page 79).
Value of the User Button 5 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 5 is still 0.

6 back to List of setpoints

User Button 6

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20831 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 6 which is part of User Buttons (page 224).

COMMAND User Button 6 is controlled by command fromExternal display (page 79).


Value of the User Button 6 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 6 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 614


User Button 7

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20832 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 7 which is part of User Buttons (page 224).

COMMAND User Button 7 is controlled by command from External display (page 79).
Value of the User Button 7 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 7 is still 0.

6 back to List of setpoints

User Button 8

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20833 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 8 which is part of User Buttons (page 224).

COMMAND User Button 8 is controlled by command from External display (page 79).
Value of the User Button 8 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 8 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 615


User Button 9

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20834 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 9 which is part of User Buttons (page 224).

COMMAND User Button 9 is controlled by command from External display (page 79).
Value of the User Button 9 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 9 is still 0.

6 back to List of setpoints

User Button 10

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20835 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 10 which is part of User Buttons (page 224).

COMMAND User Button 10 is controlled by command from External display (page 79).
Value of the User Button 10 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 10 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 616


User Button 11
Setpoint group User Buttons Related FW 1.5.0
Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20836 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 11 which is part of User Buttons (page 224).

COMMAND User Button 11 is controlled by command from External display (page 79).
Value of the User Button 11 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 11 is still 0.

6 back to List of setpoints

User Button 12

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20837 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 12 which is part of User Buttons (page 224).

COMMAND User Button 12 is controlled by command from External display (page 79).
Value of the User Button 12 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 12 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 617


User Button 13

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20838 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 13 which is part of User Buttons (page 224).

COMMAND User Button 13 is controlled by command from External display (page 79).
Value of the User Button 13 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 13 is still 0.

6 back to List of setpoints

User Button 14

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20839 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 14 which is part of User Buttons (page 224).

COMMAND User Button 14 is controlled by command from External display (page 79).
Value of the User Button 14 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 14 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 618


User Button 15

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20840 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 15 which is part of User Buttons (page 224).

COMMAND User Button 15 is controlled by command from External display (page 79).
Value of the User Button 15 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 15 is still 0.

6 back to List of setpoints

User Button 16

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20841 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 16 which is part of User Buttons (page 224).

COMMAND User Button 16 is controlled by command from External display (page 79).
Value of the User Button 16 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 16 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 619


User Button 17

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20842 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 17 which is part of User Buttons (page 224).

COMMAND User Button 17 is controlled by command from External display (page 79).
Value of the User Button 17 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 17 is still 0.

6 back to List of setpoints

User Button 18

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20843 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 18 which is part of User Buttons (page 224).

COMMAND User Button 18 is controlled by command from External display (page 79).
Value of the User Button 18 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 18 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 620


User Button 19

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20844 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 19 which is part of User Buttons (page 224).

COMMAND User Button 19 is controlled by command from External display (page 79).
Value of the User Button 19 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 19 is still 0.

6 back to List of setpoints

User Button 20

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20845 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 20 which is part of User Buttons (page 224).

COMMAND User Button 20 is controlled by command from External display (page 79).
Value of the User Button 20 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 20 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 621


User Button 21

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20846 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 21 which is part of User Buttons (page 224).

COMMAND User Button 21 is controlled by command from External display (page 79).
Value of the User Button 21 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 21 is still 0.

6 back to List of setpoints

User Button 22

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20847 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 22 which is part of User Buttons (page 224).

COMMAND User Button 22 is controlled by command from External display (page 79).
Value of the User Button 22 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 22 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 622


User Button 23

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20848 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 23 which is part of User Buttons (page 224).

COMMAND User Button 23 is controlled by command from External display (page 79).
Value of the User Button 23 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 23 is still 0.

6 back to List of setpoints

User Button 24

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20849 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 24 which is part of User Buttons (page 224).

COMMAND User Button 24 is controlled by command from External display (page 79).
Value of the User Button 24 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 24 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 623


User Button 25

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20850 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 25 which is part of User Buttons (page 224).

COMMAND User Button 25 is controlled by command from External display (page 79).
Value of the User Button 25 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 25 is still 0.

6 back to List of setpoints

User Button 26

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20851 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 26 which is part of User Buttons (page 224).

COMMAND User Button 26 is controlled by command from External display (page 79).
Value of the User Button 26 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 26 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 624


User Button 27

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20852 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 27 which is part of User Buttons (page 224).

COMMAND User Button 27 is controlled by command from External display (page 79).
Value of the User Button 27 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 27 is still 0.

6 back to List of setpoints

User Button 28

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20853 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 28 which is part of User Buttons (page 224).

COMMAND User Button 28 is controlled by command from External display (page 79).
Value of the User Button 28 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 28 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 625


User Button 29

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20854 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 29 which is part of User Buttons (page 224).

COMMAND User Button 29 is controlled by command from External display (page 79).
Value of the User Button 29 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 29 is still 0.

6 back to List of setpoints

User Button 30

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20855 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 30 which is part of User Buttons (page 224).

COMMAND User Button 30 is controlled by command from External display (page 79).
Value of the User Button 30 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 30 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 626


User Button 31

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20856 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 31 which is part of User Buttons (page 224).

COMMAND User Button 31 is controlled by command from External display (page 79).
Value of the User Button 31 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 31 is still 0.

6 back to List of setpoints

User Button 32

Setpoint group User Buttons Related FW 1.5.0


Range [units] COMMAND / MAN ON / MAN OFF [-]
Default value COMMAND Force value YES
Step [-]
Comm object 20857 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts behavior of User Button 32 which is part of User Buttons (page 224).

COMMAND User Button 32 is controlled by command from External display (page 79).
Value of the User Button 32 is still 1.
Note: You should always switch from MAN ON to MAN OFF before
MAN ON
switching to COMMAND, otherwise value of the User Button 1 will be 1 until
command is received.
MAN OFF Value of the User Button 32 is still 0.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 627


Group: Scheduler

Subgroup: Time & Date

Time

Setpoint group Scheduler Related FW 1.5.0


Range [units] HH:MM:SS [-]
Default value 0:0:0 Force value NO
Step [-]
Comm object 24554 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Real time clock adjustment.
6 back to List of setpoints

Date

Setpoint group Scheduler Related FW 1.5.0


Range [units] YYYY-MM-DD [-]
Default value 2017-01-01 Force value NO
Step [-]
Comm object 24553 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Actual date adjustment.
6 back to List of setpoints

Time Stamp Period

Setpoint group Scheduler Related FW 1.5.0


Range [units] Off / 1 .. 240 [min]
Default value 60 min Force value YES
Step 1 min
Comm object 8979 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Time interval for periodic history records.
Note: History record is made only when BESS is running.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 628


Time Zone

Scheduler; CM-4G-
Setpoint group Related FW 1.5.0
GPS
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 Force value NO
Step [-]
Comm object 24366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information
about sending time, which may result in confusion when the respective problem actually occurred.

6 back to List of setpoints

DST Switching Mode

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Auto / Manual
Default value Disabled Force value NO
Step [-]
Comm object 20250 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoints is used to enable or disable daylight saving time.
AUTO - activation / deactivation of the DST, and changing of the RTC Time value accordingly is
performed automatically by the controller. The user always sees valid local time without any action
from his side.
MANUAL - activation, and deactivation of the DST is performed manually by the user via the
setpoint Time mode. Changing of the RTC Time value accordingly is then performed
automatically by the controller. So the user does not need to readjust the RTC time, he only needs
to select the proper Time Mode (page 630).
DISABLED - Time mode is fixedly set to STD and the function does not perform any changes of
RTC time.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 629


Time Mode

Setpoint group Scheduler Related FW 1.5.0


Range [units] STD / DST
Default value STD Force value NO
Step [-]
Comm object 20249 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if DST Switching Mode = Manual
Description
In manual DST Switching Mode (page 629) this input is used to adjust the actual time mode. If DST
Switching Mode is set to any other option, this input is not taken into account.
6 back to List of setpoints

DST Period Rule

Setpoint group Scheduler Related FW 1.5.0


Range [units] Australia / Chile / Europe / Mexico / New Zealand / Paraguay / US/Canada
Default value Europe Force value NO
Step [-]
Comm object 20251 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if DST Switching Mode = Auto
Description
Selection of the rule that will be applied for the calculation of the DST validity period.
6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 630


Premortem History Period

Setpoint group Scheduler Related FW 1.5.0


Range [units] 100 ms, 300 ms, 500 ms, 1 s, 3 s
Default value 3s Force value YES
Step [-]
Comm object 14044 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint adjusts the period with which premortem history (fast history) records are written.
Note: There is always buffer for 60 records, no matter what the period is.

The fast history running in background is mirrored into the controller history records when a second level
alarm occurs. Alarms that initialized flipping of the post-mortem history are: Shut down (SD), Slow stop
(STP), Overspeed, Short Current, Breaker open & cool-down (BOC), Low power (LOP), Off load (OFL).
Premortem history contains the same values in the history as the configuration done by configuration tool
(GenConfig, InteliConfig). When any new alarm (SD, BOC, LOP, OFL, STP, Overspeed, short current)
appears for the second time, only the new history records are added into the controller history log.

6 back to List of setpoints

Subgroup: Sunrise/Sunset

Sunrise/Sunset Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value Disabled Force value NO
Step N/A [-]
Comm object 20210 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables the Sunrise/Sunset function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 631


Sunrise/Sunset Latitude

Setpoint group Scheduler Related FW 1.5.0


Range [units] [° N]
Default value -90 ° N Force value YES
Step 0,0001 ° N
Comm object 20214 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Sunrise/Sunset Function (page 631) = Enabled
Description
This setpoint is automatically set, if the coordinates from the GPS module are valid. From this setpoint
and the setpoint Sunrise/Sunset Longtitude (page 632) are calculated values in function
Sunrise/Sunset.

6 back to List of setpoints

Sunrise/Sunset Longtitude

Setpoint group Scheduler Related FW 1.5.0


Range [units] [° E]
Default value -180 ° E Force value YES
Step 0,0001 ° E
Comm object 20213 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Sunrise/Sunset Function (page 631) = Enabled
Description
This setpoint is automatically set, if the coordinates from the GPS module are valid. From this setpoint
and the setpoint Sunrise/Sunset Latitude (page 632) are calculated values in function Sunrise/Sunset.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 632


Subgroup: Timer 1

Timer 1 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15358 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 1. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 1 Setup (page 634).
Once the Timer is activated the LBO EXERCISE TIMER 1 (PAGE 1077) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 633


Timer 1 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10969 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 1 Function (page 633) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 1. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 634


Subgroup: Timer 2

Timer 2 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disabled [-] Force value YES
Step [-]
Comm object 15359 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 2. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 2 Setup (page 636).
Once the Timer is activated the LBO EXERCISE TIMER 2 (PAGE 1077) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 635


Timer 2 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10970 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 2 Function (page 635) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 2. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 636


Subgroup: Timer 3

Timer 3 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15360 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 3. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 3 Setup (page 638).
Once the Timer is activated the LBO EXERCISE TIMER 3 (PAGE 1077) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 637


Timer 3 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10971 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 3 Function (page 637) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 3. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 638


Subgroup: Timer 4

Timer 4 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15361 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 4. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 4 Setup (page 640).
Once the Timer is activated the LBO EXERCISE TIMER 4 (PAGE 1078) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 639


Timer 4 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10973 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 4 Function (page 639) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 4. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 640


Subgroup: Timer 5

Timer 5 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15362 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 5. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 5 Setup (page 642).
Once the Timer is activated the LBO EXERCISE TIMER 5 (PAGE 1078) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 641


Timer 5 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10974 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 5 Function (page 641) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 5. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 642


Subgroup: Timer 6

Timer 6 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15363 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 6. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 6 Setup (page 644).
Once the Timer is activated the LBO EXERCISE TIMER 6 (PAGE 1078) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 643


Timer 6 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10975 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 6 Function (page 643) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 6. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 644


Subgroup: Timer 7

Timer 7 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15364 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 7. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 7 Setup (page 646).
Once the Timer is activated the LBO EXERCISE TIMER 7 (PAGE 1078) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 645


Timer 7 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10976 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 7 Function (page 645) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 7. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 646


Subgroup: Timer 8

Timer 8 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15365 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 8. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 8 Setup (page 648).
Once the Timer is activated the LBO EXERCISE TIMER 8 (PAGE 1079) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 647


Timer 8 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10977 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 8 Function (page 647) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 8. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 648


Subgroup: Timer 9

Timer 9 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 9. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 9 Setup (page 650).
Once the Timer is activated the LBO EXERCISE TIMER 9 (PAGE 1079) is closed regardless of chosen timer
function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 649


Timer 9 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10978 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 9 Function (page 649) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 9. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 650


Subgroup: Timer 10

Timer 10 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15367 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 10. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 10 Setup (page 652).
Once the Timer is activated the LBO EXERCISE TIMER 10 (PAGE 1079) is closed regardless of chosen
timer function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 651


Timer 10 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10979 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 10 Function (page 651) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 10. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 652


Subgroup: Timer 11

Timer 11 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15368 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 11. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 11 Setup (page 654).
Once the Timer is activated the LBO EXERCISE TIMER 11 (PAGE 1080) is closed regardless of chosen
timer function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 653


Timer 11 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10980 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 11 Function (page 653) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 11. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 654


Subgroup: Timer 12

Timer 12 Function

Setpoint group Scheduler Related FW 1.5.0


Range [units] Disabled / Manual On / No Func / Mode OFF [-]
Default value Disable Force value YES
Step [-]
Comm object 15369 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines and enables the function of the Timer 12. The functions which are supposed to
change the Controller Mode requires controller running in AUTO mode. The activation condition of the
Timer is configured via setpoint Timer 12 Setup (page 656).
Once the Timer is activated the LBO EXERCISE TIMER 12 (PAGE 1080) is closed regardless of chosen
timer function. If the CU is switched off when the Timer should be activated, the Timer will be activated
immediately after the CU is switched on if the Timer condition is still fulfilled.
IMPORTANT: The LBO is activated always when the Timer should be activated e.g. even
when controller is in different mode than AUTO.

IMPORTANT: In case that Timer 1, Timer 2, etc. should be activated at the same time, the
Timer with selected higher priority function is executed.

Disabled The Timer is disabled.


Manual On The Timer is disabled but his binary output is activated (can be used for testing
purposes).
No Func There is no any other function, only binary output of the Timer is activated once the
condition is fulfilled.
Mode OFF The binary output of the Timer is internally connected to the Remote OFF binary
input.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 655


Timer 12 Setup

Setpoint group Scheduler Related FW 1.5.0


Range [units] N/A [-]
Default value N/A [-] Force value NO
Step N/A [-]
Comm object 10981 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if Timer 12 Function (page 655) is not Disabled or Manual On
Description
Use this setpoint to setup the exercise Timer 12. See Exercise Timers (page 149) for step by step
manual.

6 back to List of setpoints

Group: Maintenance Timers

Subgroup: Maintenance Timer 1

Maintenance Timer 1 RunHours

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 9999 [h] / Disabled
Default value Disabled Force value NO
Step 1h
Comm object 13853 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much BESS running hours (Running Hours (page 880)) needs to be counted
down by the maintenance timer until value Maintenance Timer 1 RunHours (page 881) reach zero and
alarm Maintenance 1 RunHours (page 1322) with LBO AL MAINTENANCE 1 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 10 000 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 656


Maintenance Timer 1 Interval

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 36 [mo] / Disabled
Default value Disabled Force value NO
Step 1 mo
Comm object 20583 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much months needs to be counted down by the maintenance timer until value
Maintenance Timer 1 Interval (page 881) reach zero and alarm Maintenance 1 Interval (page 1322)
with LBO AL MAINTENANCE 1 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 37 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

Maintenance Timer 1 Protection

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] Warning / Stp [-]
Default value Warning Force value NO
Step [-]
Comm object 20586 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines type of the maintenance timer alarm (Wrn / Stp) for both setpoints / alarms
Maintenance Timer 1 RunHours (page 656) / Maintenance 1 RunHours (page 1322) and
Maintenance Timer 1 Interval (page 657) / Maintenance 1 Interval (page 1322).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 657


Subgroup: Maintenance Timer 2

Maintenance Timer 2 RunHours

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 9999 [h] / Disabled
Default value Disabled Force value NO
Step 1h
Comm object 13854 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much BESS running hours (Running Hours (page 880)) needs to be counted
down by the maintenance timer until value Maintenance Timer 2 RunHours (page 881) reach zero and
alarm Maintenance 2 RunHours (page 1323) with LBO AL MAINTENANCE 2 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 10 000 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

Maintenance Timer 2 Interval

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 36 [mo] / Disabled
Default value Disabled Force value NO
Step 1 mo
Comm object 20584 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much months needs to be counted down by the maintenance timer until value
Maintenance Timer 2 Interval (page 882) reach zero and alarm Maintenance 2 Interval (page 1323)
with LBO AL MAINTENANCE 2 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 37 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 658


Maintenance Timer 2 Protection

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] Warning / Stp [-]
Default value Warning Force value NO
Step [-]
Comm object 20587 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines type of the maintenance timer alarm (Wrn / Stp) for both setpoints / alarms
Maintenance Timer 2 RunHours (page 658) / Maintenance 2 RunHours (page 1323) and
Maintenance Timer 2 Interval (page 658) / Maintenance 2 Interval (page 1323).

6 back to List of setpoints

Subgroup: Maintenance Timer 3

Maintenance Timer 3 RunHours

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 9999 [h] / Disabled
Default value Disabled Force value NO
Step 1h
Comm object 13855 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much BESS running hours (Running Hours (page 880)) needs to be counted
down by the maintenance timer until value Maintenance Timer 3 RunHours (page 882) reach zero and
alarm Maintenance 3 RunHours (page 1324) with LBO AL MAINTENANCE 3 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 10 000 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 659


Maintenance Timer 3 Interval

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 36 [mo] / Disabled
Default value Disabled Force value NO
Step 1 mo
Comm object 20585 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much months needs to be counted down by the maintenance timer until value
Maintenance Timer 3 Interval (page 882) reach zero and alarm Maintenance 3 Interval (page 1323)
with LBO AL MAINTENANCE 3 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 37 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

Maintenance Timer 3 Protection

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] Warning / Stp [-]
Default value Warning Force value NO
Step [-]
Comm object 20588 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines type of the maintenance timer alarm (Wrn / Stp) for both setpoints / alarms
Maintenance Timer 3 RunHours (page 659) / Maintenance 3 RunHours (page 1324) and
Maintenance Timer 3 Interval (page 660) / Maintenance 3 Interval (page 1323).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 660


Subgroup: Maintenance Timer 4

Maintenance Timer 4 RunHours

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 9999 [h] / Disabled
Default value Disabled Force value NO
Step 1h
Comm object 13856 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much BESS running hours (Running Hours (page 880)) needs to be counted
down by the maintenance timer until value Maintenance Timer 4 RunHours (page 882) reach zero and
alarm Maintenance 4 RunHours (page 1324) with LBO AL MAINTENANCE 4 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 10 000 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

Maintenance Timer 4 Interval

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] 1 .. 36 [mo] / Disabled
Default value Disabled Force value NO
Step 1 mo
Comm object 20291 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines how much months needs to be counted down by the maintenance timer until value
Maintenance Timer 4 Interval (page 883) reach zero and alarm Maintenance 4 Interval (page 1324)
with LBO AL MAINTENANCE 4 (PAGE 1052) are activated.
Once the alarm is activated the timer continue counting down to negative values. The value 37 will
disable the Maintenance Timer function and the counter value disappears from controllers statistics.
Note: Setpoint itself does not change during countdown of timer.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 661


Maintenance Timer 4 Protection

Setpoint group Maintenance Timers Related FW 1.5.0


Range [units] Warning / Stp [-]
Default value Warning Force value NO
Step [-]
Comm object 20290 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint defines type of the maintenance timer alarm (Wrn / Stp) for both setpoints / alarms
Maintenance Timer 4 RunHours (page 661) / Maintenance 4 RunHours (page 1324) and
Maintenance Timer 4 Interval (page 661) / Maintenance 4 Interval (page 1324).

6 back to List of setpoints

Group: Geo-Fencing

Subgroup: Geo-Fencing

Geo-Fencing

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] Disable/Enable/LBI Enable
Default value Disable Force value
Step
Comm object 11681 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
This setpoint enables or disables geo-fencing function.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 662


Subgroup: Position

Home Latitude

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] -90,0000..90,0000 []
Default value 0,0000 Force value
Step 0,0001
Comm object 14606 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed.
Description
This setpoint adjust latitude of "home" position. Home is position where BESS should runs. Positions on
north hemisphere have positive value, position on south hemisphere have negative value.
Note: This value with Home Latitude are used for counting Fence Radius 1 and Fence Radius 2.

Note: This value can be also obtained automatically via logical binary input Geo Home Position. In
case of activation of this binary input for at least 2 seconds, setpoint will be adjusted automatically
from actual coordinates from GPS signal.

6 back to List of setpoints

Home Longitude

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] -180,0000..180,0000 []
Default value 0,0000 Force value
Step 0,0001
Comm object 14607 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
This setpoint adjust longitude of "home" position. Home is position where BESS should runs. Positions
on east hemisphere have positive value, position on west hemisphere have negative value.
Note: This value with Home Longitude are used for counting Fence Radius 1 and Fence Radius 2.

Note: This value can be also obtained automatically via logical binary input Geo Home Position. In
case of activation of this binary input for at least 2 seconds, setpoint will be adjusted automatically
from actual coordinates from GPS signal.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 663


Subgroup: Fence 1

Fence 1 Protection

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] HistRecOnl/Wrn/Sd/BOC
Default value HistRecOnl Force value
Step
Comm object 14610 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
Protection type for geo-fencing 1 protection. Fence of circle area is adjusted by setpoint Fence 1 Radius
(page 664). Delay for protection is adjusted by setpointFence 1 Delay (page 665).
Protection Types:
HistRecOnl: Position of BESS is only measured and displayed on the LCD screen but not used for
protection. History record is made if position is out of Fence 1 Radius (page 664).
Wrn: Position of gen-set is used for warning protection only. Protection is activated when position of
the gen-set is out of Fence 1 Radius (page 664).
Sd: Position of BESS is used for shutdown protection. Protection is activated when position of the
BESS is out of Fence 1 Radius (page 664).
BOC:Position of gen-set is used for BOC (Breaker Open and Cooling) protection. Protection is
activated when position of the BESS is out of Fence 1 Radius (page 664).
Note: Protection is activated also when GPS signal is lost for Fence 1 Delay (page 665).

6 back to List of setpoints

Fence 1 Radius

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] 0..99,9 [km]
Default value 0 km Force value
Step 0,1 km
Comm object 11677 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
Radius for circle area 1. When the BESS leaves this area,Fence 1 Protection (page 664) is activated
afterFence 1 Delay (page 665).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 664


Fence 1 Delay

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] 0..3600 [s]
Default value 0s Force value
Step 1s
Comm object 11682 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
Delay for Fence 1 Protection (page 664).

6 back to List of setpoints

Subgroup: Fence 2

Fence 2 Protection

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] HistRecOnl/Wrn/Sd/BOC
Default value HistRecOnl Force value
Step
Comm object 14611 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
Protection type for geo-fencing 1 protection. Fence of circle area is adjusted by setpoint Fence 2 Radius
(page 666). Delay for protection is adjusted by setpointFence 2 Delay (page 666).
Protection Types:
HistRecOnl: Position of BESS is only measured and displayed on the LCD screen but not used for
protection. History record is made if position is out of Fence 2 Radius (page 666).
Wrn: Position of BESS is used for warning protection only. Protection is activated when position of the
BESS is out of Fence 2 Radius (page 666).
Sd: Position of BESS is used for shutdown protection. Protection is activated when position of the
BESS is out of Fence 2 Radius (page 666).
BOC:Position of BESS is used for BOC (Breaker Open and Cooling) protection. Protection is
activated when position of the BESS is out of Fence 1 Radius (page 664).
Note: Protection is activated also when GPS signal is lost forFence 2 Delay (page 666).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 665


Fence 2 Radius

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] 0..99,9 [km]
Default value 0 km Force value
Step 0,1 km
Comm object 14608 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
Radius for circle area 1. When the BESS leaves this area,Fence 1 Protection (page 664) is activated
afterFence 1 Delay (page 665).

6 back to List of setpoints

Fence 2 Delay

Setpoint group Geo-Fencing Related FW 1.5.0


Range [units] 0..3600 [s]
Default value 0s Force value
Step 1s
Comm object 14609 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant modules is installed.
Description
Delay forFence 2 Protection (page 665).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 666


Group: CM-4G-GPS

Subgroup: RTC Synchronization

Time Zone

Scheduler; CM-4G-
Setpoint group Related FW 1.5.0
GPS
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 Force value NO
Step [-]
Comm object 24366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information
about sending time, which may result in confusion when the respective problem actually occurred.

6 back to List of setpoints

Group: Plug-In Modules

Subgroup: Slot A

Slot A

Setpoint group Plug-In Modules Related FW 1.5.0


Range [units] ENABLED / DISABLED [-]
Default value ENABLED Force value NO
Step [-]
Comm object 24280 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot A.

6 back to List of setpoints

Subgroup: Slot B

Slot B

Setpoint group Plug-In Modules Related FW 1.5.0


Range [units] ENABLED / DISABLED [-]

InteliNeo 6000 1.5.0 Global Guide 667


Default value ENABLED Force value NO
Step [-]
Comm object 24279 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot B.
6 back to List of setpoints

Group: CM-RS232-485

Subgroup: COM1 Setting

COM1 Mode

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Force value NO
Step [-]
Comm object 24522 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM1 channel.

Direct InteliConfig communication protocol via serial cable.


MODBUS MODBUS protocol.
DualSlave Dual operation protocol – slave function
DualMaster Dual operation protocol – master function

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 668


COM1 Communication Speed

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] 9600 / 19200 / 38400 / 57600 / 115200[bps]
Default value 57600 bps Force value NO
Step [-]
Comm object 24341 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
Setpoint visibility
668)
Description
If the direct mode is selected on COM1 channel, the direct communication speed of controller part of line
can be adjusted here. Speed of second part of line has to be adjusted to the same value.

6 back to List of setpoints

COM1 Modbus Mode

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] 8N1 / 8N2 / 8E1 [-]
Default value 8N1 Force value NO
Step [-]
Comm object 23867 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjusts communication mode of Modbus-RTU.

Possible options
8N1 8 data bits, 1 stop bit, no parity
8N2 8 data bits, 2 stop bits, no parity
8E1 8 data bits, 1 stop bit, even parity

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 669


COM1 MODBUS Communication Speed

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Force value NO
Step [-]
Comm object 24477 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
Setpoint visibility
668)
Description
If the MODBUS mode is selected on COM1 channel, the MODBUS communication speed can be adjusted
here.

6 back to List of setpoints

Subgroup: COM2 Setting

COM2 Mode

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Force value NO
Step [-]
Comm object 24451 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM2 channel.

Direct InteliConfig communication protocol via serial cable.


MODBUS MODBUS protocol.
DualSlave Dual operation protocol – slave function
DualMaster Dual operation protocol – master function

6 back to List of setpoints

COM2 Communication Speed

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] 9600 / 19200 / 38400 / 57600 / 115200[bps]
Default value 57600 bps Force value NO
Step [-]
Comm object 24340 Related applications MINT, MPTM
Config level Standard

InteliNeo 6000 1.5.0 Global Guide 670


Only if relevant module is installed + conditioned by the setpoint COM2 Mode (page
Setpoint visibility
670)
Description
If the direct mode is selected on COM2 channel, the direct communication speed of controller part of line
can be adjusted here. Speed of second part of line has to be adjusted to the same value.

6 back to List of setpoints

COM2 Modbus Mode

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] 8N1 / 8N2 / 8E1 [-]
Default value 8N1 Force value NO
Step [-]
Comm object 23866 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjusts communication mode of Modbus-RTU.

Possible options
8N1 8 data bits, 1 stop bit, no parity
8N2 8 data bits, 2 stop bits, no parity
8E1 8 data bits, 1 stop bit, even parity

6 back to List of setpoints

COM2 MODBUS Communication Speed

Setpoint group CM-RS232-485 Related FW 1.5.0


Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Force value NO
Step [-]
Comm object 24420 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
If the MODBUS mode is selected on COM2 channel, the MODBUS communication speed can be adjusted
here.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 671


Group: CM-4G-GPS

Subgroup: Cellular Interface

Internet Connection

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Enabled / Disabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 24315 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust the communication mode of module.

6 back to List of setpoints

Network Mode

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 2G / 3G / 4G / Automatic [-]
Default value Automatic Force value NO
Step [-]
Comm object 24132 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjusts preferred connection type of CM-4G-GPS module.

6 back to List of setpoints

Access Point Name

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 0 .. 31 characters [-]
Default value internet Force value NO
Step [-]
Comm object 24363 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
APN (Access Point Name) of the network, provided by GSM operator.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 672


Connection Check IP1

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] [-]
Default value "empty" Force value NO
Step [-]
Comm object 23978 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
IP address of reliable server in the internet.
To provide maximal reliability of wireless cellular connection the module is equipped with function that
periodically checks the data connection over the cellular network is working.
This function is based on periodical sending of ICMP messages (known as "ping") to reliable servers in the
internet and checking of their responses. If there is not any response received from any of the servers (at
least one setpoint Connection Check IP1, IP2, IP3 is filled with IP address) for certain time period, the
cellular connection is considered as non-working and the module will close and reestablish the
connection.
If all three servers are not defined (setpoints Connection Check IP1, IP2, IP3 have empty addresses) then
the cellular connection check is disabled

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 673


Connection Check IP2

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] [-]
Default value "empty" Force value NO
Step [-]
Comm object 23977 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
IP address of reliable server in the internet.
To provide maximal reliability of wireless cellular connection the module is equipped with function that
periodically checks the data connection over the cellular network is working.
This function is based on periodical sending of ICMP messages (known as "ping") to reliable servers in the
internet and checking of their responses. If there is not any response received from any of the servers (at
least one setpoint Connection Check IP1, IP2, IP3 is filled with IP address) for certain time period, the
cellular connection is considered as non-working and the module will close and reestablish the
connection.
If all three servers are not defined (setpoints Connection Check IP1, IP2, IP3 have empty addresses) then
the cellular connection check is disabled

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 674


Connection Check IP3

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] [-]
Default value "empty" Force value NO
Step [-]
Comm object 23976 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
IP address of reliable server in the internet.
To provide maximal reliability of wireless cellular connection the module is equipped with function that
periodically checks the data connection over the cellular network is working.
This function is based on periodical sending of ICMP messages (known as "ping") to reliable servers in the
internet and checking of their responses. If there is not any response received from any of the servers (at
least one setpoint Connection Check IP1, IP2, IP3 is filled with IP address) for certain time period, the
cellular connection is considered as non-working and the module will close and reestablish the
connection.
If all three servers are not defined (setpoints Connection Check IP1, IP2, IP3 have empty addresses) then
the cellular connection check is disabled

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 675


Subgroup: TCP/IP Settings

DNS Mode

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Automatic / Manual [-]
Default value Automatic Force value NO
Step [-]
Comm object 23988 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables to enter DNS server addresses manually, even with the Internet Connection (page
672) set to Automatic.

Automatic DNS server addresses automatically obtained from a DHCP server are used
DNS IP Address 1 (page 676) and DNS IP Address 2 (page 677) can be
adjusted manually. Use this option to resolve e.g. internet access policy related
Manual
issue, if local DNS server addresses automatically obtained from a DHCP server
do not work

6 back to List of setpoints

DNS IP Address 1

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Valid IP address [-]
Default value 8.8.8.8 Force value NO
Step [-]
Comm object 24314 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
The setpoint is used to select the method how the DNS Address 1 is adjusted.
If DNS Mode (page 676) is MANUAL this setpoint is used to adjust the domain name server (DNS), which
is needed to translate domain names in email addresses and server names into correct IP addresses.
If DNS Mode (page 676) is AUTOMATIC this setpoint is inactive. The DNS server IP address is assigned
by the DHCP server.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 676


DNS IP Address 2

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Valid IP address [-]
Default value 8.8.8.8 Force value NO
Step [-]
Comm object 23986 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
The setpoint is used to select the method how the DNS Address 2 is adjusted.
If DNS Mode (page 676) is FIXED this setpoint is used to adjust the domain name server (DNS), which is
needed to translate domain names in email addresses and server names into correct IP addresses.
If DNS Mode (page 676) is AUTOMATIC this setpoint is inactive. The DNS server IP address is assigned
by the DHCP server.

6 back to List of setpoints

IP Firewall

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] ENABLED / DISABLED [-]
Default value DISABLED Force value NO
Step [-]
Comm object 23959 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoints enables to switch on the built-in Firewall functionality.

DISABLED The firewall function is switched off


The firewall function is switched on, use InteliConfig to setup the firewall rules
ENABLED
(configuration card Others – Firewall)

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 677


Subgroup: AirGate Settings

AirGate Connection

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Disabled/ Enabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 23968 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
This setpoint enable or disable AirGate connection via CM-4G-GPS.

DISABLED: Only SMS are sent. Internet-enabled SIM card is not required. AirGate is not used.
ENABLED This mode uses the "AirGate" service. Internet-enabled SIM card must be used.
The AirGate server address is adjusted by the setpoint AirGate Address (page
678).

IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.

6 back to List of setpoints

AirGate Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0 .. 31 characters [-]
Default value global.airgate.link Force value NO
Step [-]
Comm object 24364 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free
AirGate server provided by ComAp at global.airgate.link.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 678


Airgate Port

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 1 .. 65535 [-]
Default value 54440 Force value NO
Step 1
Comm object 24091 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
This port is used for TCP communication with the AirGate server.
Note: Use port 54440 for standard ComAp AirGate service.

6 back to List of setpoints

Subgroup: ComAp Client Settings

ComAp Client Inactivity Timeout

ETH Interface 1 -
Setpoint group TrustedETH Interface 2 Related FW 1.5.0
- Untrusted
Range [units] 0 .. 65535 [s]
Default value 60 s Force value YES
Step 1s
Comm object 24098 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Connection (TCP socket) is closed by controller, if a client (e.g. InteliConfig) does not communicate for
this time. This timeout applies to both direct and AirGate connection.
Note: This setpoint is shared with ComAp Client Inactivity Timeout (page 679).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 679


Direct Connection

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Disabled / Enabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 23961 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this to enable/disable direct connection of a ComAp client (e.g. InteliConfig) to the IP address of the
controller.
Note: For Direct connection the controller IP address must be reachable from the client IP address.

6 back to List of setpoints

Direct Connection Port

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 1 .. 65535 [-]
Default value 23 Force value NO
Step [-]
Comm object 23960 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This port is used to listen for an incoming TCP connection if Direct Connection is ENABLED.
6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 680


Subgroup: E-mail Settings

SMTP Server Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value global.airgate.link:9925 Force value NO
Step [-]
Comm object 23962 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for entering the domain name (e.g. smtp.yourprovider.com) or IP address (e.g.
74.125.39.109) or number of port (with colon like a first mark) of the SMTP server. Ask your internet
provider or IT manager for this information.
Note: You may use also any public SMTP server which does not require connection over SSL/TLS
channels.

6 back to List of setpoints

SMTP Sender Address

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23884 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter an existing email address into this setpoint. This address will be used as sender address in active
e-mails that will be sent from the controller.
Note: It is not needed to enter an existing email address, nevertheless valid email format needs to be
followed.

IMPORTANT: This item is obligatory when emails are configured.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 681


SMTP User Name

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..31 characters [-]
Default value [-] Force value NO
Step [-]
Related
Comm object 23883 MINT, MPTM
applications
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the username for the SMTP server. Leave the setpoint blank if the SMTP
server does not require authentication.

6 back to List of setpoints

SMTP User Password

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..15 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 23882 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to enter the password for the SMTP server. Leave the setpoint blank if the SMTP server
does not require authentication.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 682


SMTP Encryption

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] NONE / SSL/TLS / STARTTLS [-]
Default value NONE Force value NO
Step [-]
Comm object 23965 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint selects encryption type for SMTP session.

NONE Session is without of any encryption.


SSL/TLS Encrypted channel is created first and only after that session is created.
Session is created without of encryption and after command STARTTLS it
STARTTLS
is switched to encrypted session.

6 back to List of setpoints

E-mail Address 1

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24298 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 683


E-mail Address 4

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24144 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

E-mail Address 3

Setpoint group ETH Interface 2 - Untrusted Related FW 1.5.0


Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24145 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

E-mail Address 2

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] 0..63 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24297 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Enter a valid e-mail address where event and alarm messages will be sent.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 684


Subgroup: Messages Settings

Telephone Number 1

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 0 .. 31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24296 Related applications MINT, MPTM
Config level Standard
Setpoint visibility (missing or bad snippet)
Description
Enter in this setpoint a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call)
or the full international format beginning with a "+" character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.

6 back to List of setpoints

Telephone Number 2

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 0 .. 31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24295 Related applications MINT, MPTM
Config level Standard
Setpoint visibility (missing or bad snippet)
Description
Enter in this setpoint a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call)
or the full international format beginning with a "+" character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 685


Telephone Number 3

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 0 .. 31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24143 Related applications MINT, MPTM
Config level Standard
Setpoint visibility (missing or bad snippet)
Description
Enter in this setpoint a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call)
or the full international format beginning with a "+" character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.

6 back to List of setpoints

Telephone Number 4

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] 0 .. 31 characters [-]
Default value [-] Force value NO
Step [-]
Comm object 24142 Related applications MINT, MPTM
Config level Standard
Setpoint visibility (missing or bad snippet)
Description
Enter in this setpoint a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call)
or the full international format beginning with a "+" character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 686


E-mail Language

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Depends on controller’s supported languages. [-]
Default value English Force value NO
Step [-]
Comm object 24299 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
Use this setpoint to set the language of Event, Warning, etc. e-mails.

6 back to List of setpoints

PVBO Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 10926 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of PVBO Messages.

6 back to List of setpoints

Sd Message

ETH Interface 2 -
Untrusted
Setpoint group Related FW 1.5.0
CM-4G-GPS
Ethernet
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8484 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Shutdown Messages.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 687


Stp Message

Setpoint group Related FW 1.5.0


Ethernet
Range [units] Enabled/Disabled
Default value Enabled Force value
Step [-]
Comm object 8485 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of messages.

6 back to List of setpoints

Wrn Message

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] Enabled / Disabled [-]
Default value Enabled Force value YES
Step [-]
Comm object 8482 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint enables or disables sending of Warning Messages.

6 back to List of setpoints

Subgroup: GPS Settings

GPS Tracking

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Enabled / Disabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 23975 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
If GPS tracking is enabled the module sends position/speed data to the controller with period 10 s.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 688


Subgroup: RTC Synchronization

Time Zone

ETH Interface 2 -
Setpoint group Related FW 1.5.0
Untrusted
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 Force value YES
Step [-]
Comm object 24366 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information
about sending time, which may result in confusion when the respective problem actually occurred.

6 back to List of setpoints

NTP Clock Sync

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] DISABLED / ENABLED [-]
Default value DISABLED Force value NO
Step [-]
Comm object 23964 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint is used to enable/disable controller time synchronization with exact time from an NTP server.
The period of synchronization is 1 hour or when the cotnroller is reset or when the setpoint is reset
(Enabled->Disabled->Enabled).

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 689


NTP Server

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] [-]
Default value pool.ntp.org Force value NO
Step [-]
Comm object 23963 Related applications MINT, MPTM
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
NTP server address.

6 back to List of setpoints

GPS Clock Sync

Setpoint group CM-4G-GPS Related FW 1.5.0


Range [units] Enabled / Disabled [-]
Default value Enabled Force value NO
Step [-]
Comm object 23974 Related applications MINT, MPTM
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
Connection (page 672)
Description
This setpoint is used to enable/disable synchronization of the controller's time with the exact time from
GPS.
The module sends UTC timestamp to the controller after reset/power on and then in period of 60 minutes.

6 back to List of setpoints

InteliNeo 6000 1.5.0 Global Guide 690


9.1.4 Values
What values are:
Values (or quantities) are analog or binary data objects, measured or computed by the controller, that are
intended for reading from the controller screen, PC, MODBUS, etc. Values are organized into groups
according to their meaning.
For full list of values go to the chapter List of values (page 693)

Invalid flag
If valid data is not available for a particular value, the invalid flag is set to it. This situation may be due to the
following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as “####” in InteliConfig and on the controller screen. If such a
value is read out via MODBUS, it will contain the data 32768 in the case of signed values and 65535 in the
case of unsigned values.

List of group of values


Group: BESS 707
Group: PV 718
Group: WT 771
Group: Universal Gensets 785
Group: Renewables 823
Group: Hybrid System 825
Group: Gensets 826
Group: Mains 827
Group: Load 828
Group: Grid Codes 829
Group: Mains/Bus 839
Group: Power Management 856
Group: Frequency/Load Control 861
Group: Voltage/PF Control 864
Group: Controller I/O 867
Group: Statistics 870
Group: Info 885
Group: User Buttons 897
Group: Log Bout 898
Group: Scheduler 901
Group: Ethernet 906

InteliNeo 6000 1.5.0 Global Guide 691


Group: PLC 916
Group: Remote Control 938
Group: DIST-IN 1-32 942
Group: DIST-IN 33-64 949
Group: SH Modules 956
Group: Virtual Shared OUT 964

InteliNeo 6000 1.5.0 Global Guide 692


List of values

Group: BESS 707 BESS V Unbalance Ph-Ph 715


BESS P 707 BESS Current L1 715
BESS P L1 707 BESS Current L2 715
BESS P L2 707 BESS Current L3 715
BESS P L3 707 BESS Current Unbalance 716
BESS Q 708 Earth Fault Current 716
BESS Q L1 708 BESS Nominal Capacity 716
BESS Q L2 708 BESS SOC 716
BESS Q L3 708 BESS Temperature 717
BESS S 709 Slip Frequency 717
BESS S L1 709 Slip Angle 717
BESS S L2 709 BESS P 10min Avg 717
BESS S L3 709 BESS Q 10min Avg 718
BESS Power Factor 710 BESS S 10min Avg 718
BESS Load Character 710 Group: PV 718
BESS Power Factor L1 710 Subgroup: PV Aggregated 718
BESS Load Character L1 710 PV Nominal P 718
BESS Power Factor L2 710 PV Actual P 719
BESS Load Character L2 711 PV Actual Q 719
BESS Power Factor L3 711 PV Actual S 719
BESS Load Character L3 711 PV Actual Power Factor 719
BESS Voltage THD L1 711 PV Actual Load Character 720
BESS Voltage THD L2 712 PV Power Factor Request 720
BESS Voltage THD L3 712 Curtailment Output 720
BESS Current THD L1 712 Subgroup: PV Curtailment Counter 720
BESS Current THD L2 712 PV Max P 720
BESS Current THD L3 712 PV Curtailed P 721
BESS Frequency 713 PV Curtailed P Relative 721
BESS Voltage L1-N 713 Total Curtailed PV kWh Rel 721
BESS Voltage L2-N 713 Annual Curtailed PV kWh Rel 722
BESS Voltage L3-N 713 Monthly Curtailed PV kWh Rel 722
BESS Voltage L1-L2 713 Weekly Curtailed PV kWh Rel 722
BESS Voltage L2-L3 714 Daily Curtailed PV kWh Rel 723
BESS Voltage L3-L1 714 Subgroup: PV 1 723
BESS Voltage 714 PV 1 Nominal P 723
BESS V Unbalance Ph-N 714 PV 1 Actual P 723

InteliNeo 6000 1.5.0 Global Guide 693


PV 1 Actual Q 723 Subgroup: PV 7 732
PV 1 Actual S 724 PV 7 Nominal P 732
PV 1 Actual Power Factor 724 PV 7 Actual P 732
PV 1 Actual Load Character 724 PV 7 Actual Q 732
Subgroup: PV 2 724 PV 7 Actual S 733
PV 2 Nominal P 724 PV 7 Actual Power Factor 733
PV 2 Actual P 725 PV 7 Actual Load Character 733
PV 2 Actual Q 725 Subgroup: PV 8 733
PV 2 Actual S 725 PV 8 Nominal P 733
PV 2 Actual Power Factor 725 PV 8 Actual P 734
PV 2 Actual Load Character 726 PV 8 Actual Q 734
Subgroup: PV 3 726 PV 8 Actual S 734
PV 3 Nominal P 726 PV 8 Actual Power Factor 734
PV 3 Actual P 726 PV 8 Actual Load Character 735
PV 3 Actual Q 726 Subgroup: PV 9 735
PV 3 Actual S 727 PV 9 Actual P 735
PV 3 Actual Power Factor 727 PV 9 Nominal P 735
PV 3 Actual Load Character 727 PV 9 Actual Q 735
Subgroup: PV 4 727 PV 9 Actual S 736
PV 4 Nominal P 727 PV 9 Actual Power Factor 736
PV 4 Actual P 728 PV 9 Actual Load Character 736
PV 4 Actual Q 728 Subgroup: PV 10 736
PV 4 Actual S 728 PV 10 Nominal P 736
PV 4 Actual Power Factor 728 PV 10 Actual P 737
PV 4 Actual Load Character 729 PV 10 Actual Q 737
Subgroup: PV 5 729 PV 10 Actual S 737
PV 5 Nominal P 729 PV 10 Actual Power Factor 737
PV 5 Actual P 729 PV 10 Actual Load Character 738
PV 5 Actual Q 729 Subgroup: PV 11 738
PV 5 Actual S 730 PV 11 Nominal P 738
PV 5 Actual Power Factor 730 PV 11 Actual P 738
PV 5 Actual Load Character 730 PV 11 Actual Q 738
Subgroup: PV 6 730 PV 11 Actual S 739
PV 6 Nominal P 730 PV 11 Actual Power Factor 739
PV 6 Actual P 731 PV 11 Actual Load Character 739
PV 6 Actual Q 731 Subgroup: PV 12 739
PV 6 Actual S 731 PV 12 Nominal P 739
PV 6 Actual Power Factor 731 PV 12 Actual P 740
PV 6 Actual Load Character 732 PV 12 Actual Q 740

InteliNeo 6000 1.5.0 Global Guide 694


PV 12 Actual S 740 PV 18 Nominal P 748
PV 12 Actual Power Factor 740 PV 18 Actual P 749
PV 12 Actual Load Character 741 PV 18 Actual Q 749
Subgroup: PV 13 741 PV 18 Actual S 749
PV 13 Nominal P 741 PV 18 Actual Power Factor 749
PV 13 Actual P 741 PV 18 Actual Load Character 750
PV 13 Actual Q 741 Subgroup: PV 19 750
PV 13 Actual S 742 PV 19 Nominal P 750
PV 13 Actual Power Factor 742 PV 19 Actual P 750
PV 13 Actual Load Character 742 PV 19 Actual Q 750
Subgroup: PV 14 742 PV 19 Actual S 751
PV 14 Nominal P 742 PV 19 Actual Power Factor 751
PV 14 Actual P 743 PV 19 Actual Load Character 751
PV 14 Actual Q 743 Subgroup: PV 20 751
PV 14 Actual S 743 PV 20 Nominal P 751
PV 14 Actual Power Factor 743 PV 20 Actual P 752
PV 14 Actual Load Character 744 PV 20 Actual Q 752
Subgroup: PV 15 744 PV 20 Actual S 752
PV 15 Nominal P 744 PV 20 Actual Power Factor 752
PV 15 Actual P 744 PV 20 Actual Load Character 753
PV 15 Actual Q 744 Subgroup: PV 21 753
PV 15 Actual S 745 PV 21 Nominal P 753
PV 15 Actual Power Factor 745 PV 21 Actual P 753
PV 15 Actual Load Character 745 PV 21 Actual Q 753
Subgroup: PV 16 745 PV 21 Actual S 754
PV 16 Nominal P 745 PV 21 Actual Power Factor 754
PV 16 Actual P 746 PV 21 Actual Load Character 754
PV 16 Actual Q 746 Subgroup: PV 22 754
PV 16 Actual S 746 PV 22 Nominal P 754
PV 16 Actual Power Factor 746 PV 22 Actual P 755
PV 16 Actual Load Character 747 PV 22 Actual Q 755
Subgroup: PV 17 747 PV 22 Actual S 755
PV 17 Nominal P 747 PV 22 Actual Power Factor 755
PV 17 Actual P 747 PV 22 Actual Load Character 756
PV 17 Actual Q 747 Subgroup: PV 23 756
PV 17 Actual S 748 PV 23 Nominal P 756
PV 17 Actual Power Factor 748 PV 23 Actual P 756
PV 17 Actual Load Character 748 PV 23 Actual Q 756
Subgroup: PV 18 748 PV 23 Actual S 757

InteliNeo 6000 1.5.0 Global Guide 695


PV 23 Actual Power Factor 757 PV 29 Actual P 765
PV 23 Actual Load Character 757 PV 29 Actual Q 765
Subgroup: PV 24 757 PV 29 Actual S 766
PV 24 Nominal P 757 PV 29 Actual Power Factor 766
PV 24 Actual P 758 PV 29 Actual Load Character 766
PV 24 Actual Q 758 Subgroup: PV 30 766
PV 24 Actual S 758 PV 30 Nominal P 766
PV 24 Actual Power Factor 758 PV 30 Actual P 767
PV 24 Actual Load Character 759 PV 30 Actual Q 767
Subgroup: PV 25 759 PV 30 Actual S 767
PV 25 Nominal P 759 PV 30 Actual Power Factor 767
PV 25 Actual P 759 PV 30 Actual Load Character 768
PV 25 Actual Q 759 Subgroup: PV 31 768
PV 25 Actual S 760 PV 31 Nominal P 768
PV 25 Actual Power Factor 760 PV 31 Actual P 768
PV 25 Actual Load Character 760 PV 31 Actual Q 768
Subgroup: PV 26 760 PV 31 Actual S 769
PV 26 Nominal P 760 PV 31 Actual Power Factor 769
PV 26 Actual P 761 PV 31 Actual Load Character 769
PV 26 Actual Q 761 Subgroup: PV 32 769
PV 26 Actual S 761 PV 32 Nominal P 769
PV 26 Actual Power Factor 761 PV 32 Actual P 770
PV 26 Actual Load Character 762 PV 32 Actual Q 770
Subgroup: PV 27 762 PV 32 Actual S 770
PV 27 Nominal P 762 PV 32 Actual Power Factor 770
PV 27 Actual P 762 PV 32 Actual Load Character 771
PV 27 Actual Q 762 Group: WT 771
PV 27 Actual S 763 Subgroup: WT Aggregated 771
PV 27 Actual Power Factor 763 WT Nominal P 771
PV 27 Actual Load Character 763 WT Actual P 771
Subgroup: PV 28 763 WT Actual Q 771
PV 28 Nominal P 763 WT Actual S 772
PV 28 Actual P 764 WT Actual Power Factor 772
PV 28 Actual Q 764 WT Actual Load Character 772
PV 28 Actual S 764 Curtailment Output 772
PV 28 Actual Power Factor 764 Subgroup: WT 1 773
PV 28 Actual Load Character 765 WT 1 Nominal P 773
Subgroup: PV 29 765 WT 1 Actual P 773
PV 29 Nominal P 765 WT 1 Actual Q 773

InteliNeo 6000 1.5.0 Global Guide 696


WT 1 Actual S 773 WT 7 Nominal P 782
WT 1 Actual Power Factor 774 WT 7 Actual P 782
WT 1 Actual Load Character 774 WT 7 Actual Q 782
Subgroup: WT 2 774 WT 7 Actual S 782
WT 2 Nominal P 774 WT 7 Actual Power Factor 783
WT 2 Actual P 774 WT 7 Actual Load Character 783
WT 2 Actual Q 775 Subgroup: WT 8 783
WT 2 Actual S 775 WT 8 Nominal P 783
WT 2 Actual Power Factor 775 WT 8 Actual P 783
WT 2 Actual Load Character 775 WT 8 Actual Q 784
Subgroup: WT 3 776 WT 8 Actual S 784
WT 3 Nominal P 776 WT 8 Actual Power Factor 784
WT 3 Actual P 776 WT 8 Actual Load Character 784
WT 3 Actual Q 776 Group: Universal Gensets 785
WT 3 Actual S 776 Subgroup: Universal Genset Aggregated 785
WT 3 Actual Power Factor 777 Uni Gen Nominal P 785
WT 3 Actual Load Character 777 Uni Gen Actual P 785
Subgroup: WT 4 777 Uni Gen Actual Q 785
WT 4 Nominal P 777 Uni Gen Actual S 785
WT 4 Actual P 777 Uni Gen Actual Power Factor 786
WT 4 Actual Q 778 Uni Gen Actual Load Character 786
WT 4 Actual S 778 Uni Gen Requested P 786
WT 4 Actual Power Factor 778 Uni Gen Requested Q 786
WT 4 Actual Load Character 778 Uni Gen Relative Requested P 787
Subgroup: WT 5 779 Uni Gen Relative Requested Q 787
WT 5 Nominal P 779 Subgroup: Uni Gen 1 787
WT 5 Actual P 779 Uni Gen 1 Nominal P 787
WT 5 Actual Q 779 Uni Gen 1 Actual P 787
WT 5 Actual S 779 Uni Gen 1 Actual Q 788
WT 5 Actual Power Factor 780 Uni Gen 1 Actual S 788
WT 5 Actual Load Character 780 Uni Gen 1 Actual Power Factor 788
Subgroup: WT 6 780 Uni Gen 1 Actual Load Character 788
WT 6 Nominal P 780 Uni Gen 1 Requested P 789
WT 6 Actual P 780 Uni Gen 1 Requested Q 789
WT 6 Actual Q 781 Uni Gen 1 Binary Outputs 789
WT 6 Actual S 781 Subgroup: Uni Gen 2 790
WT 6 Actual Power Factor 781 Uni Gen 2 Nominal P 790
WT 6 Actual Load Character 781 Uni Gen 2 Actual P 790
Subgroup: WT 7 782 Uni Gen 2 Actual Q 790

InteliNeo 6000 1.5.0 Global Guide 697


Uni Gen 2 Actual S 790 Uni Gen 6 Actual Q 799
Uni Gen 2 Actual Power Factor 791 Uni Gen 6 Actual S 799
Uni Gen 2 Actual Load Character 791 Uni Gen 6 Actual Power Factor 800
Uni Gen 2 Requested P 791 Uni Gen 6 Actual Load Character 800
Uni Gen 2 Requested Q 791 Uni Gen 6 Requested P 800
Uni Gen 2 Binary Outputs 792 Uni Gen 6 Requested Q 800
Subgroup: Uni Gen 3 792 Uni Gen 6 Binary Outputs 801
Uni Gen 3 Nominal P 792 Subgroup: Uni Gen 7 801
Uni Gen 3 Actual P 792 Uni Gen 7 Nominal P 801
Uni Gen 3 Actual Q 792 Uni Gen 7 Actual P 801
Uni Gen 3 Actual S 793 Uni Gen 7 Actual Q 801
Uni Gen 3 Actual Power Factor 793 Uni Gen 7 Actual S 802
Uni Gen 3 Actual Load Character 793 Uni Gen 7 Actual Power Factor 802
Uni Gen 3 Requested Q 793 Uni Gen 7 Actual Load Character 802
Uni Gen 3 Requested P 794 Uni Gen 7 Requested P 802
Uni Gen 3 Binary Outputs 794 Uni Gen 7 Requested Q 803
Subgroup: Uni Gen 4 794 Uni Gen 7 Binary Outputs 803
Uni Gen 4 Nominal P 794 Subgroup: Uni Gen 8 803
Uni Gen 4 Actual P 794 Uni Gen 8 Nominal P 803
Uni Gen 4 Actual Q 795 Uni Gen 8 Actual P 803
Uni Gen 4 Actual S 795 Uni Gen 8 Actual Q 804
Uni Gen 4 Actual Power Factor 795 Uni Gen 8 Actual S 804
Uni Gen 4 Actual Load Character 795 Uni Gen 8 Actual Power Factor 804
Uni Gen 4 Requested P 796 Uni Gen 8 Actual Load Character 804
Uni Gen 4 Requested Q 796 Uni Gen 8 Requested P 805
Uni Gen 4 Binary Outputs 796 Uni Gen 8 Requested Q 805
Subgroup: Uni Gen 5 796 Uni Gen 8 Binary Outputs 805
Uni Gen 5 Nominal P 796 Subgroup: Uni Gen 9 805
Uni Gen 5 Actual P 797 Uni Gen 9 Nominal P 805
Uni Gen 5 Actual Q 797 Uni Gen 9 Actual P 806
Uni Gen 5 Actual S 797 Uni Gen 9 Actual Q 806
Uni Gen 5 Actual Power Factor 797 Uni Gen 9 Actual S 806
Uni Gen 5 Actual Load Character 798 Uni Gen 9 Actual Power Factor 806
Uni Gen 5 Requested P 798 Uni Gen 9 Actual Load Character 807
Uni Gen 5 Requested Q 798 Uni Gen 9 Requested P 807
Uni Gen 5 Binary Outputs 798 Uni Gen 9 Requested Q 807
Subgroup: Uni Gen 6 799 Uni Gen 9 Binary Outputs 807
Uni Gen 6 Nominal P 799 Subgroup: Uni Gen 10 808
Uni Gen 6 Actual P 799 Uni Gen 10 Nominal P 808

InteliNeo 6000 1.5.0 Global Guide 698


Uni Gen 10 Actual P 808 Uni Gen 14 Nominal P 817
Uni Gen 10 Actual Q 808 Uni Gen 14 Actual P 817
Uni Gen 10 Actual S 808 Uni Gen 14 Actual Q 817
Uni Gen 10 Actual Power Factor 809 Uni Gen 14 Actual S 817
Uni Gen 10 Actual Load Character 809 Uni Gen 14 Actual Power Factor 818
Uni Gen 10 Requested P 809 Uni Gen 14 Actual Load Character 818
Uni Gen 10 Requested Q 809 Uni Gen 14 Requested P 818
Uni Gen 10 Binary Outputs 810 Uni Gen 14 Requested Q 818
Subgroup: Uni Gen 11 810 Uni Gen 14 Binary Outputs 819
Uni Gen 11 Nominal P 810 Subgroup: Uni Gen 15 819
Uni Gen 11 Actual P 810 Uni Gen 15 Nominal P 819
Uni Gen 11 Actual Q 810 Uni Gen 15 Actual P 819
Uni Gen 11 Actual S 811 Uni Gen 15 Actual Q 819
Uni Gen 11 Actual Power Factor 811 Uni Gen 15 Actual S 820
Uni Gen 11 Actual Load Character 811 Uni Gen 15 Actual Power Factor 820
Uni Gen 11 Requested P 811 Uni Gen 15 Actual Load Character 820
Uni Gen 11 Requested Q 812 Uni Gen 15 Requested P 820
Uni Gen 11 Binary Outputs 812 Uni Gen 15 Requested Q 821
Subgroup: Uni Gen 12 812 Uni Gen 15 Binary Outputs 821
Uni Gen 12 Nominal P 812 Subgroup: Uni Gen 16 821
Uni Gen 12 Actual P 812 Uni Gen 16 Nominal P 821
Uni Gen 12 Actual Q 813 Uni Gen 16 Actual P 821
Uni Gen 12 Actual S 813 Uni Gen 16 Actual Q 822
Uni Gen 12 Actual Power Factor 813 Uni Gen 16 Actual S 822
Uni Gen 12 Actual Load Character 813 Uni Gen 16 Actual Power Factor 822
Uni Gen 12 Requested P 814 Uni Gen 16 Actual Load Character 822
Uni Gen 12 Requested Q 814 Uni Gen 16 Requested P 823
Uni Gen 12 Binary Outputs 814 Uni Gen 16 Requested Q 823
Subgroup: Uni Gen 13 814 Uni Gen 16 Binary Outputs 823
Uni Gen 13 Nominal P 814 Group: Renewables 823
Uni Gen 13 Actual P 815 REN Nominal P 823
Uni Gen 13 Actual Q 815 REN Actual P 824
Uni Gen 13 Actual S 815 REN Actual Q 824
Uni Gen 13 Actual Power Factor 815 REN Actual S 824
Uni Gen 13 Actual Load Character 816 REN Actual Power Factor 824
Uni Gen 13 Requested P 816 REN Actual Load Character 825
Uni Gen 13 Requested Q 816 Group: Hybrid System 825
Uni Gen 13 Binary Outputs 816 Total P 825

Subgroup: Uni Gen 14 817 Total Q 825

InteliNeo 6000 1.5.0 Global Guide 699


Total S 825 Load Reduction 2 hrs Last Month 835
Total PF 826 Load Reduction 2 min Last Month 835
Total Load Character 826 Load Reduction 2 hrs Accumulated 835
Group: Gensets 826 Load Reduction 2 min Accumulated 836
Gensets P 826 Load Reduction 3 hrs Actual Month 836
Gensets Q 826 Load Reduction 3 min Actual Month 836
Gensets Power Factor 827 Load Reduction 3 hrs Last Month 836
Gensets Load Character 827 Load Reduction 3 min Last Month 837
Group: Mains 827 Load Reduction 3 hrs Accumulated 837
Mains Import P Monitoring 827 Load Reduction 3 min Accumulated 837
Mains Import Q Monitoring 827 Load Reduction 4 hrs Actual Month 837
Group: Load 828 Load Reduction 4 min Actual Month 838
Load P 828 Load Reduction 4 hrs Last Month 838
Load Q 828 Load Reduction 4 min Last Month 838
Load Power Factor 828 Load Reduction 4 hrs Accumulated 838
Load Character 828 Load Reduction 4 min Accumulated 839
Group: Grid Codes 829 Group: Mains/Bus 839
Grid Codes Version 829 Mains/Bus Frequency 839
Pmom 829 Mains/Bus Voltage L1-N 839
Test Frequency 829 Mains/Bus Voltage L2-N 839
P Over Frequency Curve 829 Mains/Bus Voltage L3-N 840
P Under Frequency Curve 830 Mains/Bus Voltage L1-L2 840
Q(Um) Curve 830 Mains/Bus Voltage L2-L3 840
Qref/Ulim Curve 830 Mains/Bus Voltage L3-L1 840
Q(P) Curve 831 Mains/Bus Voltage 840
PF(P) Curve 831 Mains/Bus V Unabalance Ph-N 841
P(Um) Curve 831 Mains/Bus V Unbalance Ph-Ph 841
Pmom/Pave 832 +Mains/Bus Voltage 841
Load Reduction 1 Occurrence 832 +Mains/Bus Voltage Relative 841
Load Reduction 2 Occurrence 832 Mains L1 Current 842
Load Reduction 3 Occurrence 832 Mains L1 Current 842
Load Reduction 4 Occurrence 833 Mains L2 Current 842
Load Reduction 1 hrs Actual Month 833 Mains L2 Current 842
Load Reduction 1min Actual Month 833 Mains Import P 842
Load Reduction 1 hrs Last Month 833 Mains P L1 843
Load Reduction 1 min Last Month 834 Mains P L2 843
Load Reduction 1 hrs Accumulated 834 Mains P L3 843
Load Reduction 1 min Accumulated 834 Mains Import Q 843
Load Reduction 2 hrs Actual Month 834 Mains Import Q L1 843
Load Reduction 2 min Actual Month 835

InteliNeo 6000 1.5.0 Global Guide 700


Mains Import Q L2 844 ROCOF4 855
Mains Import Q L3 844 Max ROCOF4 856
Mains/BusMainsBus Left Import S 844 Group: Power Management 856
Mains S L1 844 Engine Priority 856
Mains S L2 844 Actual Reserve 856
Mains S L3 845 Start Reserve 857
Mains PF 845 Stop Reserve 857
Mains Load Character 845 Dynamic Spinning Reserve 857
Mains Power Factor L1 845 Dynamic Spinning Reserve Offset 857
Mains Load Character L1 846 Actual Relative Reserve 858
Mains Power Factor L2 846 Start Relative Reserve 858
Mains Load Character L2 846 Stop Relative Reserve 858
Mains Power Factor L3 846 Actual Active Power In PM 858
Mains Load Character L3 847 Actual Reactive Power In PM 858
Mains Voltage THD L1 847 Running Nominal Power In PM 859
Mains Voltage THD L2 847 Running Nominal Power Of All 859
Mains Voltage THD L3 847 Available Nominal Power 859
Mains Current THD L1 848 Minimal Running Nominal Power 859
Mains Current THD L2 848 Actual Power Band 32 860
Mains Current THD L3 848 Actual Power Band 64 860
Max Vector Shift 848 Next Power Band 32 860
Mains Voltage 10min Avg L1-N 849 Next Power Band 64 861
Mains Voltage 10min Avg L2-N 849 Group: Frequency/Load Control 861
Mains Voltage 10min Avg L3-N 849 BESS Required P Target 861

Mains Voltage 1min Avg L1-N 850 BESS Required P 861

Mains Voltage 1min Avg L2-N 850 BESS Required Relative P 862

Mains Voltage 1min Avg L3-N 850 Frequency Regulator Output 862

Mains Voltage 10min Avg L1-L2 851 BESS Frequency Required 862

Mains Voltage 10min Avg L2-L3 851 BESS Frequency Offset 862

Mains Voltage 10min Avg L3-L1 851 BESS P Required 863

Mains Voltage 1min Avg L1-L2 851 System Load Control 863

Mains Voltage 1min Avg L2-L3 852 Group: Voltage/PF Control 864

Mains Voltage 1min Avg L3-L1 852 System PF/Q Control 864

ROCOF1 852 BESS Required Q 865

Max ROCOF1 853 BESS Required Qrel Lim 865

ROCOF2 853 BESS Required Relative Q 865

Max ROCOF2 854 BESS Required PF 865

ROCOF3 854 BESS Required PF Character 865

Max ROCOF3 855 Voltage Regulator Output 866


Voltage Request 866

InteliNeo 6000 1.5.0 Global Guide 701


BESS Voltage Required 866 Batt. Charge Daily kWh 876
BESS Voltage Offset 866 Hours Of Silent 876
BESS Q Required % 867 Carbon Offset Equivalent 876
Group: Controller I/O 867 Gen kWh 877
Battery Voltage 867 Gen Annual kWh 877
CU-AIN-01 867 Gen Daily kWh 877
CU-AIN-02 867 Gen Monthly kWh 877
CU-AIN-03 868 Gen Weekly kWh 877
CU-AIN-04 868 Fuel Used 878
Binary Inputs 868 Fuel Annual 878
E-STOP 869 Fuel Monthly 878
Binary Outputs 869 Fuel Weekly 878
Group: Statistics 870 Fuel Daily 878
PV kWh 870 PCC kWh 879
PV Annual kWh 870 PCC kVArh 879
PV Monthly kWh 870 PCC kVAh 879
PV Weekly kWh 870 Mains kWh 879
PV Daily kWh 871 Mains kVArh 880
Maximal PV kWh 871 Running Hours 880
PV Total Curtailed kWh 871 Conditioned Running Hours 1 880
PV Curtailed Annual kWh 871 Conditioned Running Hours 2 880
PV Curtailed Monthly kWh 871 Num Starts 881
PV Curtailed Weekly kWh 872 Maintenance Timer 1 RunHours 881
PV Curtailed Daily kWh 872 Maintenance Timer 1 Interval 881
WT kWh 872 Maintenance Timer 2 RunHours 881
WT Annual kWh 872 Maintenance Timer 2 Interval 882
WT Monthly kWh 873 Maintenance Timer 3 RunHours 882
WT Weekly kWh 873 Maintenance Timer 3 Interval 882
WT Daily kWh 873 Maintenance Timer 4 RunHours 882
Batt. Charging Cycles 873 Maintenance Timer 4 Interval 883
Batt. Discharge kWh 874 Num E-Stops 883
Batt. Discharge Annual kWh 874 Shutdowns 883
Batt. Discahrge Month kWh 874 Fast Pulse Counter 1 883
Batt. Discharge Week kWh 874 Fast Pulse Counter 2 884
Batt. Discharge Daily kWh 875 Pulse Counter 1 884
Batt. Charge kWh 875 Pulse Counter 2 884
Batt. Charge Annual kWh 875 Group: Info 885
Batt. Charge Month kWh 875 Application Mode 885
Batt. Charge Week kWh 876 Controller Mode 885

InteliNeo 6000 1.5.0 Global Guide 702


Load Shedding Status 885 Log Bout 4 898
BESS state 886 Log Bout 5 898
Breaker state 886 Log Bout 6 899
Timer Text 886 Log Bout 7 899
Connection Type 886 Log Bout 8 899
Timer Value 886 Log Bout 9 899
ID String 887 Log Bout 10 899
FW Version 887 Log Bout 11 900
Application 887 Log Bout 12 900
FW Branch 887 Log Bout 13 900
CAN Intercontroller Comm Mode 888 Log Bout 14 900
CAN Intercontroller Comm Redundancy 888 Log Bout 15 900
SD Card Status 889 Group: Scheduler 901
SD Card Capacity 889 Time 901
SD Card Free Space 889 Date 901
History Lifetime 890 Time Mode 901
Forced Value Status 890 Sunrise Time 901
SW Key Feature List 891 Sunset Time 902
Hot Swap Redundancy Status 892 Time To Sunrise 902
CAN16 893 Time To Sunset 902
CAN32 893 Exercise Timer 1 902
CAN48 893 Exercise Timer 2 903
CAN64 894 Exercise Timer 3 903
Reg16 894 Exercise Timer 4 903
Reg32 894 Exercise Timer 5 903
Reg48 895 Exercise Timer 6 904
Reg64 895 Exercise Timer 7 904
Gen Loaded 16 895 Exercise Timer 8 904
Gen Loaded 32 896 Exercise Timer 9 904
Gen Loaded 48 896 Exercise Timer 10 905
Gen Loaded 64 896 Exercise Timer 11 905
SPI Module A 897 Exercise Timer 12 905
SPI Module B 897 Group: Ethernet 906
Group: User Buttons 897 Subgroup: Ethernet Port Status 906
User Buttons 897 ETH Port 1 Status 906

Group: Log Bout 898 ETH Port 2 Status 906


Log Bout 1 898 ETH Port 3 Status 907
Log Bout 2 898 Subgroup: Trusted Interface 907
Log Bout 3 898 MAC Address 907

InteliNeo 6000 1.5.0 Global Guide 703


Current IP Address 907 PLC-AOUT 15 918
Current Subnet Mask 908 PLC-AOUT 16 919
Current Gateway 908 PLC-AOUT 17 919
ETH Interface Status 908 PLC-AOUT 18 919
Subgroup: Untrusted Interface 908 PLC-AOUT 19 919
MAC Address 908 PLC-AOUT 20 919
Current IP Address 909 PLC-AOUT 21 920
Current Subnet Mask 909 PLC-AOUT 22 920
Current Gateway 909 PLC-AOUT 23 920
Primary DNS 909 PLC-AOUT 24 920
Secondary DNS 910 PLC-AOUT 25 920
ETH Interface Status 910 PLC-AOUT 26 921
AirGate Status 911 PLC-AOUT 27 921
AirGate ID 911 PLC-AOUT 28 921
AirGate Servicing Node 912 PLC-AOUT 29 921
Last E-mail Result 913 PLC-AOUT 30 921
Subgroup: Modbus Interface 914 PLC-AOUT 31 922
MAC Address 914 PLC-AOUT 32 922
Current IP Address 914 PLC-AOUT 33 922
Current Subnet Mask 914 PLC-AOUT 34 922
Current Gateway 915 PLC-AOUT 35 922
Primary DNS 915 PLC-AOUT 36 923
Secondary DNS 915 PLC-AOUT 37 923
ETH Interface Status 915 PLC-AOUT 38 923
Group: PLC 916 PLC-AOUT 39 923
PLC-AOUT 1 916 PLC-AOUT 40 923
PLC-AOUT 2 916 PLC-AOUT 41 924
PLC-AOUT 3 916 PLC-AOUT 42 924
PLC-AOUT 4 916 PLC-AOUT 43 924
PLC-AOUT 5 916 PLC-AOUT 44 924
PLC-AOUT 6 917 PLC-AOUT 45 924
PLC-AOUT 7 917 PLC-AOUT 46 925
PLC-AOUT 8 917 PLC-AOUT 47 925
PLC-AOUT 9 917 PLC-AOUT 48 925
PLC-AOUT 10 917 PLC-AOUT 49 925
PLC-AOUT 11 918 PLC-AOUT 50 925
PLC-AOUT 12 918 PLC-AOUT 51 926
PLC-AOUT 13 918 PLC-AOUT 52 926
PLC-AOUT 14 918 PLC-AOUT 53 926

InteliNeo 6000 1.5.0 Global Guide 704


PLC-AOUT 54 926 PLC-BOUT 29 934
PLC-AOUT 55 926 PLC-BOUT 30 934
PLC-AOUT 56 927 PLC-BOUT 31 934
PLC-AOUT 57 927 PLC-BOUT 32 935
PLC-AOUT 58 927 PLC Resource 1 935
PLC-AOUT 59 927 PLC Resource 2 935
PLC-AOUT 60 927 PLC Resource 3 935
PLC-AOUT 61 928 PLC Resource 4 935
PLC-AOUT 62 928 PLC Resource 5 936
PLC-AOUT 63 928 PLC Resource 6 936
PLC-AOUT 64 928 PLC Resource 7 936
PLC-BOUT 1 928 PLC Resource 8 936
PLC-BOUT 2 929 PLC Resource 9 936
PLC-BOUT 3 929 PLC Resource 10 937
PLC-BOUT 4 929 PLC Resource 11 937
PLC-BOUT 5 929 PLC Resource 12 937
PLC-BOUT 6 929 PLC Resource 13 937
PLC-BOUT 7 930 PLC Resource 14 937
PLC-BOUT 8 930 PLC Resource 15 938
PLC-BOUT 9 930 PLC Resource 16 938
PLC-BOUT 10 930 Group: Remote Control 938
PLC-BOUT 11 930 RemoteControl2B 1 938
PLC-BOUT 12 931 RemoteControl2B 2 938
PLC-BOUT 13 931 RemoteControl2B 3 939
PLC-BOUT 14 931 RemoteControl2B 4 939
PLC-BOUT 15 931 RemoteControl2B 5 939
PLC-BOUT 16 931 RemoteControl2B 6 939
PLC-BOUT 17 932 RemoteControl2B 7 940
PLC-BOUT 18 932 RemoteControl2B 8 940
PLC-BOUT 19 932 RemoteControl4B 1 940
PLC-BOUT 20 932 RemoteControl4B 2 940
PLC-BOUT 21 932 RemoteControl4B 3 941
PLC-BOUT 22 933 RemoteControl4B 4 941
PLC-BOUT 23 933 RemoteControlBin 941
PLC-BOUT 24 933 Group: DIST-IN 1-32 942
PLC-BOUT 25 933 Binary inputs 1 1-8 942

PLC-BOUT 26 933 Binary inputs 1 9-16 942

PLC-BOUT 27 934 Binary inputs 1 17-24 943

PLC-BOUT 28 934 Binary inputs 1 25-32 943

InteliNeo 6000 1.5.0 Global Guide 705


DISTAIN-1 1 944 SHBOUT-4 960
DISTAIN-1 2 944 SHBOUT-5 961
DISTAIN-1 3 944 SHBOUT-6 961
DISTAIN-1 4 945 SHAIN-1 1 962
Binary inputs 2 1-8 945 SHAIN-1 2 962
Binary inputs 2 9-16 946 SHAIN-1 3 962
Binary inputs 2 17-24 946 SHAIN-1 4 962
Binary inputs 2 25-32 947 SHAIN-2 1 963
DISTAIN-2 1 947 SHAIN-2 2 963
DISTAIN-2 2 948 SHAIN-2 3 963
DISTAIN-2 3 948 SHAIN-2 4 963
DISTAIN-2 4 948 Group: Virtual Shared OUT 964
Group: DIST-IN 33-64 949 Binary outputs 1-8 964
Binary inputs 33 1-8 949 Binary outputs 9-16 964
Binary inputs 33 9-16 949 Binary outputs 17-24 965
Binary inputs 33 17-24 950 Binary outputs 25-32 965
Binary inputs 33 25-32 950 6 back to Controller objects
DISTAIN-33 1 951
DISTAIN-33 2 951
DISTAIN-33 3 951
DISTAIN-33 4 952
Binary inputs 34 1-8 952
Binary inputs 34 9-16 953
Binary inputs 34 17-24 953
Binary inputs 34 25-32 954
DISTAIN-34 1 954
DISTAIN-34 2 955
DISTAIN-34 3 955
DISTAIN-34 4 955
Group: SH Modules 956
SHBIN-1 956
SHBIN-2 956
SHBIN-3 957
SHBIN-4 957
SHBIN-5 958
SHBIN-6 958
SHBOUT-1 959
SHBOUT-2 959
SHBOUT-3 960

InteliNeo 6000 1.5.0 Global Guide 706


Group: BESS

BESS P

Value group Value Group BESS Related FW 1.5.0


Units kW
Comm object 8202 Related applications MINT, MPTM
Description
Active power of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS P L1

Value group Value Group BESS Related FW 1.5.0


Units kW
Comm object 8524 Related applications MINT, MPTM
Description
Active power of the L1 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS P L2

Value group Value Group BESS Related FW 1.5.0


Units kW
Comm object 8525 Related applications MINT, MPTM
Description
Active power of the L2 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS P L3

Value group Value Group BESS Related FW 1.5.0


Units kW
Comm object 8526 Related applications MINT, MPTM
Description
Active power of the L3 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 707


BESS Q

Value group Value Group BESS Related FW 1.5.0


Units kVAr
Comm object 8203 Related applications MINT, MPTM
Description
Reactive power of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS Q L1

Value group Value Group BESS Related FW 1.5.0


Units kVAr
Comm object 8527 Related applications MINT, MPTM
Description
Reactive power of the L1 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS Q L2

Value group Value Group BESS Related FW 1.5.0


Units kVAr
Comm object 8528 Related applications MINT, MPTM
Description
Reactive power of the L2 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS Q L3

Value group Value Group BESS Related FW 1.5.0


Units kVAr
Comm object 8529 Related applications MINT, MPTM
Description
Reactive power of the L3 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 708


BESS S

Value group Value Group BESS Related FW 1.5.0


Units kVA
Comm object 8565 Related applications MINT, MPTM
Description
Apparent power of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS S L1

Value group Value Group BESS Related FW 1.5.0


Units kVA
Comm object 8530 Related applications MINT, MPTM
Description
Apparent power of the L1 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS S L2

Value group Value Group BESS Related FW 1.5.0


Units kVA
Comm object 8531 Related applications MINT, MPTM
Description
Apparent power of the L2 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS S L3

Value group Value Group BESS Related FW 1.5.0


Units kVA
Comm object 8532 Related applications MINT, MPTM
Description
Apparent power of the L3 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 709


BESS Power Factor

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 16156 Related applications MINT, MPTM
Description
Power factor of the BESS.

6 back to List of values

BESS Load Character

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 8395 Related applications MINT, MPTM
Description
Load character of the BESS.
L = inductive load, C = capacitive load, and R = resistive load (BESS Power Factor (page 710) = 1).

6 back to List of values

BESS Power Factor L1

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 16160 Related applications MINT, MPTM
Description
Power factor of the L1 phase of the BESS.

6 back to List of values

BESS Load Character L1

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 8626 Related applications MINT, MPTM
Description
Load character of the L1 phase of the BESS.
L = inductive load, C = capacitive load, and R = resistive load (BESS Power Factor L1 (page 710) = 1).

6 back to List of values

BESS Power Factor L2

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 16161 Related applications MINT, MPTM
Description
Power factor of the L2 phase of the BESS.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 710


BESS Load Character L2

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 8627 Related applications MINT, MPTM
Description
Load character of the L2 phase of the BESS.
L = inductive load, C = capacitive load, and R = resistive load (BESS Power Factor L2 (page 710) = 1).

6 back to List of values

BESS Power Factor L3

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 16162 Related applications MINT, MPTM
Description
Power factor of the L3 phase of the BESS.

6 back to List of values

BESS Load Character L3

Value group Value Group BESS Related FW 1.5.0


Units [-]
Comm object 8628 Related applications MINT, MPTM
Description
Load character of the L3 phase of the BESS.
L = inductive load, C = capacitive load, and R = resistive load (BESS Power Factor L3 (page 711) = 1).

6 back to List of values

BESS Voltage THD L1

Value group Value Group BESS Related FW 1.5.0


Units %
Comm object 16052 Related applications MINT, MPTM
Description
This value represents Voltage Total Harmonic Distortion (page 18) of BESS Voltage L1-N (page
713).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 711


BESS Voltage THD L2

Value group Value Group BESS Related FW 1.5.0


Units %
Comm object 16053 Related applications MINT, MPTM
Description
This value represents Voltage Total Harmonic Distortion (page 18) of BESS Voltage L2-N (page
713).

6 back to List of values

BESS Voltage THD L3

Value group Value Group BESS Related FW 1.5.0


Units %
Comm object 16054 Related applications MINT, MPTM
Description
This value represents Voltage Total Harmonic Distortion (page 18) of BESS Voltage L3-N (page
713).

6 back to List of values

BESS Current THD L1

Value group Value Group BESS Related FW 1.5.0


Units %
Comm object 16056 Related applications MINT, MPTM
Description
This value represents Current Total Harmonic Distortion (page 18) of BESS Current L1 (page 715).

6 back to List of values

BESS Current THD L2

Value group Value Group BESS Related FW 1.5.0


Units %
Comm object 16057 Related applications MINT, MPTM
Description
This value represents Current Total Harmonic Distortion (page 18) of BESS Current L2 (page 715).

6 back to List of values

BESS Current THD L3

Value group Value Group BESS Related FW 1.5.0


Units %
Comm object 16058 Related applications MINT, MPTM
Description
This value represents Current Total Harmonic Distortion (page 18) of BESS Current L3 (page 715).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 712


BESS Frequency

Value group Value Group BESS Related FW 1.5.0


Units Hz
Comm object 20799 Related applications MINT, MPTM
Description
This is the value of BESS Frequency.

6 back to List of values

BESS Voltage L1-N

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 8192 Related applications MINT, MPTM
Description
Voltage of the L1 phase of the BESS.

6 back to List of values

BESS Voltage L2-N

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 8193 Related applications MINT, MPTM
Description
Voltage of the L2 phase of the BESS.

6 back to List of values

BESS Voltage L3-N

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 8194 Related applications MINT, MPTM
Description
Voltage of the L3 phase of the BESS.

6 back to List of values

BESS Voltage L1-L2

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 9628 Related applications MINT, MPTM
Description
Phase to phase voltage between the L1 and L2 phases of the BESS.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 713


BESS Voltage L2-L3

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 9629 Related applications MINT, MPTM
Description
Phase to phase voltage between the L2 and L3 phases of the BESS.

6 back to List of values

BESS Voltage L3-L1

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 9630 Related applications MINT, MPTM
Description
Phase to phase voltage between the L3 and L1 phases of the BESS.

6 back to List of values

BESS Voltage

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 10645 Related applications MINT, MPTM
Description
Average value of all voltage phases of the BESS.

6 back to List of values

BESS V Unbalance Ph-N

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 10548 Related applications MINT, MPTM
Description
This value contains the maximum difference of values BESS Voltage L1-N (page 713), BESS Voltage
L2-N (page 713), BESS Voltage L3-N (page 713) at a given moment.
Note: Difference of the values and the evaluation of the protection is influenced by the setpoint
Connection type (page 378).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 714


BESS V Unbalance Ph-Ph

Value group Value Group BESS Related FW 1.5.0


Units V
Comm object 17336 Related applications MINT, MPTM
Description
This value contains the maximum difference of values BESS Voltage L1-L2 (page 713), BESS Voltage
L2-L3 (page 714), BESS Voltage L3-L1 (page 714) at a given moment.
Note: Difference of the values and the evaluation of the protection is influenced by the setpoint
Connection type (page 378).

6 back to List of values

BESS Current L1

Value group Value Group BESS Related FW 1.5.0


Units A
Comm object 8198 Related applications MINT, MPTM
Description
Current of the L1 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS Current L2

Value group Value Group BESS Related FW 1.5.0


Units A
Comm object 8199 Related applications MINT, MPTM
Description
Current of the L2 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

BESS Current L3

Value group Value Group BESS Related FW 1.5.0


Units A
Comm object 8200 Related applications MINT, MPTM
Description
Current of the L3 phase of the BESS.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 715


BESS Current Unbalance

Value group Value Group BESS Related FW 1.5.0


Units A
Comm object 10550 Related applications MINT, MPTM
Description
This value contains the maximum difference of values BESS Current L1 (page 715), BESS Current L2
(page 715) and BESS Current L3 (page 715).
Note: Difference of the values and the evaluation of the protection is influenced by the setpoint
Connection type (page 378).

6 back to List of values

Earth Fault Current

Value group Value Group BESS Related FW 1.5.0


Units A
Comm object 15381 Related applications MINT, MPTM
Description
Measured fault value for evaluation of Earth Fault Current Protection (page 592).
Note: This value is filled with 0 all the time if Application Mode (page 885) = MPTM and Mains
Measurement P (page 364) = CT.

6 back to List of values

BESS Nominal Capacity

Value group Value Group BESS Related FW 1.5.0


Units kWh
Comm object 15859 Related applications MINT, MPTM
Description
This value shows nominal capacity of the Energy Storage.

6 back to List of values

BESS SOC

Value group Value Group BESS Related FW 1.5.0


Units %
Comm
15857 Related applications MINT, MPTM
object
Description
Actual state of charge of the Energy Storage.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 716


BESS Temperature

Value group Value Group BESS Related FW 1.5.0


Units °C
Comm
15861 Related applications MINT, MPTM
object
Description
Actual BESS temperature.

6 back to List of values

Slip Frequency

Value group Mains/Bus Related FW 1.5.0


Units Hz
Comm object 8224 Related applications MINT, MPTM
Description
Slip frequency during synchronization.

6 back to List of values

Slip Angle

Value group Mains/Bus Related FW 1.5.0


Units °
Comm object 8225 Related applications MINT, MPTM
Description
Slip angle during synchronization.

6 back to List of values

BESS P 10min Avg

Value group Value Group BESS Related FW 1.5.0


Units kW
Comm object 16073 Related applications MPTM
Description
This value contains 10-minutes average of BESS P (page 707).
See 10-minutes averages (page 309) for more information.
Note: This value can be also switched into one decimal see Power Formats And Units (page
196).Value is reset to 0 with opening of BCB.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 717


BESS Q 10min Avg

Value group Value Group BESS Related FW 1.5.0


Units kVAr
Comm object 16080 Related applications MPTM
Description
This value contains 10-minutes average of BESS Q (page 708).
See 10-minutes averages (page 309) for more information.
Note: This value can be also switched into one decimal see Power Formats And Units (page
196).Value is reset to 0 with opening of BCB.

6 back to List of values

BESS S 10min Avg

Value group Value Group BESS Related FW 1.5.0


Units kVA
Comm object 16081 Related applications MPTM
Description
This value contains 10-minutes average of BESS S (page 709).
See 10-minutes averages (page 309) for more information.
Note: This value can be also switched into one decimal see Power Formats And Units (page
196).Value is reset to 0 with opening of BCB.

6 back to List of values

Group: PV

Subgroup: PV Aggregated

PV Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
15596 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverters.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 718


PV Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
15594 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverters.

6 back to List of values

PV Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
15595 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverters.

6 back to List of values

PV Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
15891 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverters.

6 back to List of values

PV Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
20162 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverters.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 719


PV Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
15678 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverters.

6 back to List of values

PV Power Factor Request

Value group Voltage/PF Control Related FW 1.5.0


Units [-]
Comm object 20184 Related applications MINT, MPTM
Description
This value shows the actual PF request required from the PV inverters.

6 back to List of values

Curtailment Output

Value group PV Related FW 1.5.0


Units % of PV Nominal P (page 718)
Comm
14364 Related applications MINT, MPTM
object
Description
This value shows maximal percentage power which can be provided by the output of the PV inverter in
case the PV Curtailment (page 295) function is used.

6 back to List of values

Subgroup: PV Curtailment Counter

PV Max P

Value group PV Related FW 1.5.0


Units kW
Comm
19553 Related applications MINT, MPTM
object
Description
The total potential PV output across all arrays.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 720


PV Curtailed P

Value group PV Related FW 1.5.0


Units kW
Comm
19554 Related applications MINT, MPTM
object
Description
The value of actual curtailed power.

6 back to List of values

PV Curtailed P Relative

Value group PV Related FW 1.5.0


Units kW
Comm
19555 Related applications MINT, MPTM
object
Description
This value represents the ratio of actual curtailed power (PV Curtailed P (page 721)) to the total
potential PV output (PV Max P (page 720)).

6 back to List of values

Total Curtailed PV kWh Rel

Value group PV Related FW 1.5.0


Units %
Comm
18711 Related applications MINT, MPTM
object
Description
This is a statistic value related to the Curtailment Counter functionality. It has meaning of the relative
value of curtailed energy compared to the PV arrays potential output. Actually it says how big part of the
PV energy was wasted due to the curtailment.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 721


Annual Curtailed PV kWh Rel

Value group PV Related FW 1.5.0


Units %
Comm
18712 Related applications MINT, MPTM
object
Description
This is a statistic value related to the Curtailment Counter functionality. It has meaning of the relative
value of curtailed energy compared to the PV arrays potential output. Actually it says how big part of the
PV energy was wasted due to the curtailment in interval of one year. This Value is reset together every
new year begin.

6 back to List of values

Monthly Curtailed PV kWh Rel

Value group PV Related FW 1.5.0


Units %
Comm
18713 Related applications MINT, MPTM
object
Description
This is a statistic value related to the Curtailment Counter functionality. It has meaning of the relative
value of curtailed energy compared to the PV arrays potential output. Actually it says how big part of the
PV energy was wasted due to the curtailment in interval of one month. This Value is reset together every
new month begin.

6 back to List of values

Weekly Curtailed PV kWh Rel

Value group PV Related FW 1.5.0


Units %
Comm
18714 Related applications MINT, MPTM
object
Description
This is a statistic value related to the Curtailment Counter functionality. It has meaning of the relative
value of curtailed energy compared to the PV arrays potential output. Actually it says how big part of the
PV energy was wasted due to the curtailment in interval of one week. This Value is reset together every
new week begin (Sunday midnight).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 722


Daily Curtailed PV kWh Rel

Value group PV Related FW 1.5.0


Units %
Comm
18715 Related applications MINT, MPTM
object
Description
This is a statistic value related to the Curtailment Counter functionality. It has meaning of the relative
value of curtailed energy compared to the PV arrays potential output. Actually it says how big part of the
PV energy was wasted due to the curtailment in interval of one day. This Value is reset together every
new day begin (midnight).

6 back to List of values

Subgroup: PV 1

PV 1 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19879 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 1.

6 back to List of values

PV 1 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19878 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 1.

6 back to List of values

PV 1 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19877 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 1.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 723


PV 1 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19876 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 1.

6 back to List of values

PV 1 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19875 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 1.

6 back to List of values

PV 1 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19874 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 1.

6 back to List of values

Subgroup: PV 2

PV 2 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19873 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 2.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 724


PV 2 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19872 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 2.

6 back to List of values

PV 2 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19871 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 2.

6 back to List of values

PV 2 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19870 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 2.

6 back to List of values

PV 2 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19869 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 2.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 725


PV 2 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19868 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 2.

6 back to List of values

Subgroup: PV 3

PV 3 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19867 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 3.

6 back to List of values

PV 3 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19866 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 3.

6 back to List of values

PV 3 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19865 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 3.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 726


PV 3 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19864 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 3.

6 back to List of values

PV 3 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19863 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 3.

6 back to List of values

PV 3 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19862 Related applications (missing or bad snippet)
object
Description
This value represents actual load character of the PV inverter 3.

6 back to List of values

Subgroup: PV 4

PV 4 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19861 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 4.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 727


PV 4 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19860 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 4.

6 back to List of values

PV 4 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19859 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 4.

6 back to List of values

PV 4 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19858 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 4.

6 back to List of values

PV 4 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19857 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 4.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 728


PV 4 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19856 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 4.

6 back to List of values

Subgroup: PV 5

PV 5 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19855 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 5.

6 back to List of values

PV 5 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19854 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 5.

6 back to List of values

PV 5 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19853 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 5.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 729


PV 5 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19852 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 5.

6 back to List of values

PV 5 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19851 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 5.

6 back to List of values

PV 5 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19850 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 5.

6 back to List of values

Subgroup: PV 6

PV 6 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19849 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 6.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 730


PV 6 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19848 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 6.

6 back to List of values

PV 6 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19847 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 6.

6 back to List of values

PV 6 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19846 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 6.

6 back to List of values

PV 6 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19845 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 6.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 731


PV 6 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19844 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 6.

6 back to List of values

Subgroup: PV 7

PV 7 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19843 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 7.

6 back to List of values

PV 7 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19842 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 7.

6 back to List of values

PV 7 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19841 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 7.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 732


PV 7 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19840 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 7.

6 back to List of values

PV 7 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19839 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 7.

6 back to List of values

PV 7 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19838 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 7.

6 back to List of values

Subgroup: PV 8

PV 8 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19837 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 8.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 733


PV 8 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19836 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 8.

6 back to List of values

PV 8 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19835 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 8.

6 back to List of values

PV 8 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19834 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 8.

6 back to List of values

PV 8 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19833 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 8.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 734


PV 8 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19832 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 8.

6 back to List of values

Subgroup: PV 9

PV 9 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19830 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 9.

6 back to List of values

PV 9 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19831 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 9.

6 back to List of values

PV 9 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19829 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 9.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 735


PV 9 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19828 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 9.

6 back to List of values

PV 9 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19827 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 9.

6 back to List of values

PV 9 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19826 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 9.

6 back to List of values

Subgroup: PV 10

PV 10 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19825 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 10.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 736


PV 10 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19824 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 10.

6 back to List of values

PV 10 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19823 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 10.

6 back to List of values

PV 10 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19822 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 10.

6 back to List of values

PV 10 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19821 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 10.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 737


PV 10 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19820 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 10.

6 back to List of values

Subgroup: PV 11

PV 11 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19819 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 11.

6 back to List of values

PV 11 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19818 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 11.

6 back to List of values

PV 11 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19817 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 11.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 738


PV 11 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19816 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 11.

6 back to List of values

PV 11 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19815 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 11.

6 back to List of values

PV 11 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19814 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 11.

6 back to List of values

Subgroup: PV 12

PV 12 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19813 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 12.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 739


PV 12 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19812 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 12.

6 back to List of values

PV 12 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19811 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 12.

6 back to List of values

PV 12 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19810 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 12.

6 back to List of values

PV 12 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19809 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 12.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 740


PV 12 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19808 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 12.

6 back to List of values

Subgroup: PV 13

PV 13 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19807 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 13.

6 back to List of values

PV 13 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19806 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 13.

6 back to List of values

PV 13 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19805 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 13.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 741


PV 13 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19804 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 13.

6 back to List of values

PV 13 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19803 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 13.

6 back to List of values

PV 13 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19802 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 13.

6 back to List of values

Subgroup: PV 14

PV 14 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19801 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 14.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 742


PV 14 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19800 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 14.

6 back to List of values

PV 14 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19799 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 14.

6 back to List of values

PV 14 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19798 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 14.

6 back to List of values

PV 14 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19797 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 14.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 743


PV 14 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19796 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 14.

6 back to List of values

Subgroup: PV 15

PV 15 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19795 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 15.

6 back to List of values

PV 15 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19794 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 15.

6 back to List of values

PV 15 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19793 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 15.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 744


PV 15 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19792 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 15.

6 back to List of values

PV 15 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19791 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 15.

6 back to List of values

PV 15 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19790 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 15.

6 back to List of values

Subgroup: PV 16

PV 16 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
19789 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 16.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 745


PV 16 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
19788 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 16.

6 back to List of values

PV 16 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
19787 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 16.

6 back to List of values

PV 16 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
19786 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 16.

6 back to List of values

PV 16 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
19785 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 16.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 746


PV 16 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
19784 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 16.

6 back to List of values

Subgroup: PV 17

PV 17 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18591 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 17.

6 back to List of values

PV 17 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18596 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 17.

6 back to List of values

PV 17 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18595 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 17.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 747


PV 17 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18594 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 17.

6 back to List of values

PV 17 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18593 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 17.

6 back to List of values

PV 17 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18592 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 17.

6 back to List of values

Subgroup: PV 18

PV 18 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18597 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 18.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 748


PV 18 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18602 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 18.

6 back to List of values

PV 18 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18601 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 18.

6 back to List of values

PV 18 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18600 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 18.

6 back to List of values

PV 18 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18599 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 18.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 749


PV 18 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18598 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 18.

6 back to List of values

Subgroup: PV 19

PV 19 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18603 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 19.

6 back to List of values

PV 19 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18608 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 19.

6 back to List of values

PV 19 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18607 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 19.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 750


PV 19 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18606 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 19.

6 back to List of values

PV 19 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18605 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 19.

6 back to List of values

PV 19 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18604 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 19.

6 back to List of values

Subgroup: PV 20

PV 20 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18609 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 20.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 751


PV 20 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18614 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 20.

6 back to List of values

PV 20 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18613 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 20.

6 back to List of values

PV 20 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18612 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 20.

6 back to List of values

PV 20 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18611 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 20.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 752


PV 20 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18610 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 20.

6 back to List of values

Subgroup: PV 21

PV 21 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18615 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 21.

6 back to List of values

PV 21 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18620 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 21.

6 back to List of values

PV 21 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18619 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 21.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 753


PV 21 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18618 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 21.

6 back to List of values

PV 21 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18617 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 21.

6 back to List of values

PV 21 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18616 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 21.

6 back to List of values

Subgroup: PV 22

PV 22 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18621 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 22.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 754


PV 22 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18626 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 22.

6 back to List of values

PV 22 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18626 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 22.

6 back to List of values

PV 22 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18624 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 22.

6 back to List of values

PV 22 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18623 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 22.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 755


PV 22 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18622 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 22.

6 back to List of values

Subgroup: PV 23

PV 23 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18627 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 23.

6 back to List of values

PV 23 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18632 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 23.

6 back to List of values

PV 23 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18631 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 23.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 756


PV 23 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18630 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 23.

6 back to List of values

PV 23 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18629 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 23.

6 back to List of values

PV 23 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18628 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 23.

6 back to List of values

Subgroup: PV 24

PV 24 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18633 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 24.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 757


PV 24 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18638 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 24.

6 back to List of values

PV 24 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18637 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 24.

6 back to List of values

PV 24 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18636 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 24.

6 back to List of values

PV 24 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18635 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 24.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 758


PV 24 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18634 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 24.

6 back to List of values

Subgroup: PV 25

PV 25 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18639 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 25.

6 back to List of values

PV 25 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18644 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 25.

6 back to List of values

PV 25 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18643 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 25.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 759


PV 25 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18642 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 25.

6 back to List of values

PV 25 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18641 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 25.

6 back to List of values

PV 25 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18640 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 25.

6 back to List of values

Subgroup: PV 26

PV 26 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18645 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 26.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 760


PV 26 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18650 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 26.

6 back to List of values

PV 26 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18649 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 26.

6 back to List of values

PV 26 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18648 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 26.

6 back to List of values

PV 26 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18647 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 26.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 761


PV 26 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18646 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 26.

6 back to List of values

Subgroup: PV 27

PV 27 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18651 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 27.

6 back to List of values

PV 27 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18656 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 27.

6 back to List of values

PV 27 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18655 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 27.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 762


PV 27 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18654 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 27.

6 back to List of values

PV 27 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18653 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 27.

6 back to List of values

PV 27 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18652 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 27.

6 back to List of values

Subgroup: PV 28

PV 28 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18657 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 28.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 763


PV 28 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18662 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 28.

6 back to List of values

PV 28 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18661 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 28.

6 back to List of values

PV 28 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18660 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 28.

6 back to List of values

PV 28 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18659 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 28.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 764


PV 28 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18658 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 28.

6 back to List of values

Subgroup: PV 29

PV 29 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18663 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 29.

6 back to List of values

PV 29 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18668 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 29.

6 back to List of values

PV 29 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18667 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 29.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 765


PV 29 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18666 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 29.

6 back to List of values

PV 29 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18665 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 29.

6 back to List of values

PV 29 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18664 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 29.

6 back to List of values

Subgroup: PV 30

PV 30 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18669 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 30.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 766


PV 30 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18674 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 30.

6 back to List of values

PV 30 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18673 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 30.

6 back to List of values

PV 30 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18672 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 30.

6 back to List of values

PV 30 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18671 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 30.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 767


PV 30 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18670 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 30.

6 back to List of values

Subgroup: PV 31

PV 31 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18675 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 31.

6 back to List of values

PV 31 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18680 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 31.

6 back to List of values

PV 31 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18679 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 31.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 768


PV 31 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18678 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 31.

6 back to List of values

PV 31 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18671 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 31.

6 back to List of values

PV 31 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18676 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 31.

6 back to List of values

Subgroup: PV 32

PV 32 Nominal P

Value group PV Related FW 1.5.0


Units kW
Comm
18681 Related applications MINT, MPTM
object
Description
This value shows nominal power of PV inverter 32.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 769


PV 32 Actual P

Value group PV Related FW 1.5.0


Units kW
Comm
18686 Related applications MINT, MPTM
object
Description
Actual active power produced by PV inverter 32.

6 back to List of values

PV 32 Actual Q

Value group PV Related FW 1.5.0


Units kVAr
Comm
18685 Related applications MINT, MPTM
object
Description
Actual reactive power produced by PV inverter 32.

6 back to List of values

PV 32 Actual S

Value group PV Related FW 1.5.0


Units kVA
Comm
18684 Related applications MINT, MPTM
object
Description
Actual apparent power produced by PV inverter 32.

6 back to List of values

PV 32 Actual Power Factor

Value group PV Related FW 1.5.0


Units [-]
Comm
18683 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of PV inverter 32.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 770


PV 32 Actual Load Character

Value group PV Related FW 1.5.0


Units [-]
Comm
18682 Related applications MINT, MPTM
object
Description
This value represents actual load character of the PV inverter 32.

6 back to List of values

Group: WT

Subgroup: WT Aggregated

WT Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19735 Related applications MINT, MPTM
object
Description
This value shows nominal power of Wind Turbines.

6 back to List of values

WT Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19734 Related applications MINT, MPTM
object
Description
Actual active power produced by Wind Turbines.

6 back to List of values

WT Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19733 Related applications MINT, MPTM
object
Description
Actual reactive power produced by Wind Turbines.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 771


WT Actual S

Value group WT Related FW 1.5.0


Units [-]
Comm
19732 Related applications MINT, MPTM
object
Description
Actual apparent power produced by Wind Turbines.

6 back to List of values

WT Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19731 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the Wind Turbines.

6 back to List of values

WT Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19730 Related applications MINT, MPTM
object
Description
This value represents actual load character of the Wind Turbines.

6 back to List of values

Curtailment Output

Value group PV Related FW 1.5.0


Units % of PV Nominal P (page 718)
Comm
14364 Related applications MINT, MPTM
object
Description
This value shows maximal percentage power which can be provided by the output of the PV inverter in
case the PV Curtailment (page 295) function is used.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 772


Subgroup: WT 1

WT 1 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19783 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 1.

6 back to List of values

WT 1 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19782 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 1.

6 back to List of values

WT 1 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19781 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 1.

6 back to List of values

WT 1 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19780 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 1.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 773


WT 1 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19779 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 1.

6 back to List of values

WT 1 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19778 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 1.

6 back to List of values

Subgroup: WT 2

WT 2 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19777 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 2.

6 back to List of values

WT 2 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19776 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 2.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 774


WT 2 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19775 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 2.

6 back to List of values

WT 2 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19774 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 2.

6 back to List of values

WT 2 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19773 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 2.

6 back to List of values

WT 2 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19772 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 2.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 775


Subgroup: WT 3

WT 3 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19771 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 3.

6 back to List of values

WT 3 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19770 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 3.

6 back to List of values

WT 3 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19769 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 3.

6 back to List of values

WT 3 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19768 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 3.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 776


WT 3 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19767 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 3.

6 back to List of values

WT 3 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19766 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 3.

6 back to List of values

Subgroup: WT 4

WT 4 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19765 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 4.

6 back to List of values

WT 4 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19764 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 4.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 777


WT 4 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19763 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 4.

6 back to List of values

WT 4 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19762 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 4.

6 back to List of values

WT 4 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19761 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 4.

6 back to List of values

WT 4 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19760 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 4.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 778


Subgroup: WT 5

WT 5 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19759 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 5.

6 back to List of values

WT 5 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19758 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 5.

6 back to List of values

WT 5 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19757 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 5.

6 back to List of values

WT 5 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19756 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 5.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 779


WT 5 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19755 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 5.

6 back to List of values

WT 5 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19754 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 5.

6 back to List of values

Subgroup: WT 6

WT 6 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19753 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 6.

6 back to List of values

WT 6 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19752 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 6.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 780


WT 6 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19751 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 6.

6 back to List of values

WT 6 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19750 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 6.

6 back to List of values

WT 6 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19749 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 6.

6 back to List of values

WT 6 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19748 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 6.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 781


Subgroup: WT 7

WT 7 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19747 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 7.

6 back to List of values

WT 7 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19746 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 7.

6 back to List of values

WT 7 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19745 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 7.

6 back to List of values

WT 7 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19744 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 7.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 782


WT 7 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19743 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 7.

6 back to List of values

WT 7 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19742 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 7.

6 back to List of values

Subgroup: WT 8

WT 8 Nominal P

Value group WT Related FW 1.5.0


Units kW
Comm
19741 Related applications MINT, MPTM
object
Description
This value shows nominal power of WT 8.

6 back to List of values

WT 8 Actual P

Value group WT Related FW 1.5.0


Units kW
Comm
19740 Related applications MINT, MPTM
object
Description
Actual active power produced by WT 8.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 783


WT 8 Actual Q

Value group WT Related FW 1.5.0


Units kVAr
Comm
19739 Related applications MINT, MPTM
object
Description
Actual reactive power produced by WT 8.

6 back to List of values

WT 8 Actual S

Value group WT Related FW 1.5.0


Units kVA
Comm
19738 Related applications MINT, MPTM
object
Description
Actual apparent power produced by WT 8.

6 back to List of values

WT 8 Actual Power Factor

Value group WT Related FW 1.5.0


Units [-]
Comm
19737 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of the WT 8.

6 back to List of values

WT 8 Actual Load Character

Value group WT Related FW 1.5.0


Units [-]
Comm
19736 Related applications MINT, MPTM
object
Description
This value represents actual load character of the WT 8.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 784


Group: Universal Gensets

Subgroup: Universal Genset Aggregated

Uni Gen Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18919 Related applications MINT, MPTM
Description
This Value is aggregated as sum of Nominal Power values of all Uni Gens connected to the bus (with
GCB closed).

6 back to List of values (page 1)

Uni Gen Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18918 Related applications MINT, MPTM
Description
This Value is aggregated as sum of Actual Active Power values of all Uni Gens.

6 back to List of values (page 1)

Uni Gen Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18917 Related applications MINT, MPTM
Description
This Value is aggregated as sum of Actual Reactive Power values of all Uni Gens.

6 back to List of values (page 1)

Uni Gen Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18916 Related applications MINT, MPTM
Description
This Value is aggregated Actual Apparent Power values of all Uni Gens.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 785


Uni Gen Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18915 Related applications MINT, MPTM
Description
This Value specify the actual Power Factor of the group of all UGs and is calculated as Uni Gen Actual P/
Uni Gen Actual S.

6 back to List of values (page 1)

Uni Gen Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18914 Related applications MINT, MPTM
Description
This Value specify the character of the load from perspective of the group of Uni Gens.

6 back to List of values (page 1)

Uni Gen Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18865 Related applications MINT, MPTM
Description
This Value is intended for direct Active Power control of the group of Uni Gens in on-grid application
(Mains parallel operation). Uni Gens should be able to accept this value as a Baseload for the whole
group and distribute the power request among all the units in the system equally.

6 back to List of values (page 1)

Uni Gen Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18954 Related applications MINT, MPTM
Description
This Value is intended for direct Reactive Power control of the group of Uni Gens in on-grid application
(Mains parallel operation). Uni Gens should be able to accept this value as a Base Q for the whole group
and distribute the power request among all the units in the system equally.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 786


Uni Gen Relative Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18953 Related applications MINT, MPTM
Description
This Value is intended for direct Active Power control of the group of Uni Gens in on-grid application
(Mains parallel operation) and it is calculated accordingly to the Uni Gen Nominal P an Uni Gen
Requested P. Uni Gens should be able to accept the relative request for the active power and this value
can be sent directly to each particular Uni Gen.

6 back to List of values (page 1)

Uni Gen Relative Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18952 Related applications MINT, MPTM
Description
This Value is intended for direct Reactive Power control of the group of Uni Gens in on-grid application
(Mains parallel operation) and it is calculated accordingly to the Uni Gen Nominal P (Nominal P is taken
in account instead of Nominal S) an Uni Gen Requested Q. Uni Gens should be able to accept the
relative request for the reactive power and this value can be sent directly to each particular Uni Gen.

6 back to List of values (page 1)

Subgroup: Uni Gen 1

Uni Gen 1 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18955 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI Uni UNI GEN 01 NOMINAL P (PAGE 1154).

6 back to List of values (page 1)

Uni Gen 1 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18849 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 01 ACTUAL P (PAGE 1153).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 787


Uni Gen 1 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18833 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 01 ACTUAL Q (PAGE 1153).

6 back to List of values (page 1)

Uni Gen 1 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18817 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 1 Actual P (page 787) and Uni Gen 1 Actual Q (page
788).

6 back to List of values (page 1)

Uni Gen 1 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18936 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 1 Actual P (page 787) and Uni Gen 1 Actual S (page
788).

6 back to List of values (page 1)

Uni Gen 1 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18920 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 1 Actual P (page 787) and Uni Gen 1 Actual Q (page
788).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 788


Uni Gen 1 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18882 Related applications MINT, MPTM
Description
This Value is intended for direct Active Power control of the one specific Uni Gen in on-grid application
(Mains parallel operation).

6 back to List of values (page 1)

Uni Gen 1 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18866 Related applications MINT, MPTM
Description
This Value is intended for direct Reactive Power control of the one specific UG in on-grid application
(Mains parallel operation).

6 back to List of values (page 1)

Uni Gen 1 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18898 Related applications MINT, MPTM
Description
This is the binary value included two specific binary outputs. Uni Gen 1 Run Request and Uni Gen 1
Stop GCB Closing.
Uni Gen 1 Run Request: This signal is associated with the LBI GENERIC GENSET START/STOP (PAGE
1004). This LBI is used to put the Uni Gens in operation. It is accepted in MAN and in AUT mode. The
Uni Gen Run Request is influence by Power Management (Load demand Start/Stop) in AUT mode
and is issued only if the system needs to start Uni Gens to cover the requested load reserve. In the
Uni Gen it should be connected to the Genset Run Request signal.
Uni Gen 1 Stop GCB Closing: This signal is crucial for safe operation in case that Uni Gen is
enabled to closed it’s GCB to the dead bus and make it energized. The InteliNeo generates 200 ms
long pulse anytime when any controller in the system is about to close the CB to the dead bus. This
information has to be used in Uni Gen to prevent the closing the GCB to the dead bus. It is strongly
recommended to use the hard wiring of this signal between InteliNeo and Uni Gen. In the Uni Gen it
should be connected to input GCB closing Block.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 789


Subgroup: Uni Gen 2

Uni Gen 2 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18956 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 02 NOM P (PAGE 1155).

6 back to List of values (page 1)

Uni Gen 2 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18850 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 02 ACTUAL P (PAGE 1154).

6 back to List of values (page 1)

Uni Gen 2 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18834 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 02 ACTUAL Q (PAGE 1154).

6 back to List of values (page 1)

Uni Gen 2 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18818 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 2 Actual P (page 790) and Uni Gen 2 Actual Q (page
790).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 790


Uni Gen 2 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18937 Related applications (missing or bad snippet)
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 2 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18921 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 2 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18883 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 2 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18867 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 791


Uni Gen 2 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18899 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 3

Uni Gen 3 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18957 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 03 NOM P (PAGE 1156).

6 back to List of values (page 1)

Uni Gen 3 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18851 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 03 ACTUAL P (PAGE 1155).

6 back to List of values (page 1)

Uni Gen 3 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18835 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 03 ACTUAL Q (PAGE 1155).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 792


Uni Gen 3 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18819 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 3 Actual P (page 792) and Uni Gen 3 Actual Q (page
792).

6 back to List of values (page 1)

Uni Gen 3 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18938 Related applications (missing or bad snippet)
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 3 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18922 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 3 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18868 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 793


Uni Gen 3 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18884 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 3 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18900 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 4

Uni Gen 4 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18958 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 04 NOM P (PAGE 1157).

6 back to List of values (page 1)

Uni Gen 4 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18852 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 04 ACTUAL P (PAGE 1156).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 794


Uni Gen 4 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18836 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 04 ACTUAL Q (PAGE 1157).

6 back to List of values (page 1)

Uni Gen 4 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18820 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 4 Actual P (page 794) and Uni Gen 4 Actual Q (page
795).

6 back to List of values (page 1)

Uni Gen 4 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18939 Related applications (missing or bad snippet)
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 4 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18923 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 795


Uni Gen 4 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18885 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 4 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18869 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 4 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18901 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 5

Uni Gen 5 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18959 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 05 NOM P (PAGE 1159).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 796


Uni Gen 5 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18853 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 05 ACTUAL P (PAGE 1158).

6 back to List of values (page 1)

Uni Gen 5 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18837 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 05 ACTUAL Q (PAGE 1158).

6 back to List of values (page 1)

Uni Gen 5 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18821 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 5 Actual P (page 797) and Uni Gen 5 Actual Q (page
797).

6 back to List of values (page 1)

Uni Gen 5 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18940 Related applications (missing or bad snippet)
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 797


Uni Gen 5 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18924 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 5 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18886 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 5 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18870 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 5 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18902 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 798


Subgroup: Uni Gen 6

Uni Gen 6 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18960 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 06 NOM P (PAGE 1160).

6 back to List of values (page 1)

Uni Gen 6 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18854 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 06 ACTUAL P (PAGE 1159).

6 back to List of values (page 1)

Uni Gen 6 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18838 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 06 ACTUAL Q (PAGE 1159).

6 back to List of values (page 1)

Uni Gen 6 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18822 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 6 Actual P (page 799) and Uni Gen 6 Actual Q (page
799).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 799


Uni Gen 6 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18941 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 6 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18925 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 6 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18887 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 6 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18871 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 800


Uni Gen 6 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18903 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 7

Uni Gen 7 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18961 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 07 NOM P (PAGE 1161).

6 back to List of values (page 1)

Uni Gen 7 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18855 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 07 ACTUAL P (PAGE 1160).

6 back to List of values (page 1)

Uni Gen 7 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18839 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 07 ACTUAL Q (PAGE 1160).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 801


Uni Gen 7 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18823 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 7 Actual P (page 801) and Uni Gen 7 Actual Q (page
801).

6 back to List of values (page 1)

Uni Gen 7 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18942 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 7 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18926 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 7 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18888 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 802


Uni Gen 7 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18872 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 7 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18904 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 8

Uni Gen 8 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18962 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 08 NOM P (PAGE 1162).

6 back to List of values (page 1)

Uni Gen 8 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18856 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 09 ACTUAL P (PAGE 1163).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 803


Uni Gen 8 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18840 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 08 ACTUAL Q (PAGE 1162).

6 back to List of values (page 1)

Uni Gen 8 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18824 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 8 Actual P (page 803) and Uni Gen 8 Actual Q (page
804).

6 back to List of values (page 1)

Uni Gen 8 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18943 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 8 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18927 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 804


Uni Gen 8 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18889 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 8 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18873 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 8 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18905 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 9

Uni Gen 9 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18963 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 09 NOM P (PAGE 1164).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 805


Uni Gen 9 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18857 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 09 ACTUAL P (PAGE 1163).

6 back to List of values (page 1)

Uni Gen 9 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18841 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 09 ACTUAL Q (PAGE 1163).

6 back to List of values (page 1)

Uni Gen 9 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18825 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 9 Actual P (page 806) and Uni Gen 9 Actual Q (page
806).

6 back to List of values (page 1)

Uni Gen 9 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18944 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 806


Uni Gen 9 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18928 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 9 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18890 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 9 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18874 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 9 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18906 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 807


Subgroup: Uni Gen 10

Uni Gen 10 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18964 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 10 NOM P (PAGE 1165).

6 back to List of values (page 1)

Uni Gen 10 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18858 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 10 ACTUAL P (PAGE 1164).

6 back to List of values (page 1)

Uni Gen 10 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18842 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 10 ACTUAL Q (PAGE 1164).

6 back to List of values (page 1)

Uni Gen 10 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18826 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 10 Actual P (page 808) and Uni Gen 10 Actual Q
(page 808).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 808


Uni Gen 10 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18945 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 10 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18929 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 10 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18891 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 10 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18875 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 809


Uni Gen 10 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18907 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 11

Uni Gen 11 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18965 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 11 NOM P (PAGE 1166).

6 back to List of values (page 1)

Uni Gen 11 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18859 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 11 ACTUAL P (PAGE 1165).

6 back to List of values (page 1)

Uni Gen 11 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18843 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 11 ACTUAL Q (PAGE 1165).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 810


Uni Gen 11 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18827 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 11 Actual S (page 811) and Uni Gen 11 Actual Q
(page 810).

6 back to List of values (page 1)

Uni Gen 11 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18946 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 11 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18930 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 11 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18892 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 811


Uni Gen 11 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18876 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 11 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18908 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 12

Uni Gen 12 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18966 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 12 NOM P (PAGE 1167).

6 back to List of values (page 1)

Uni Gen 12 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18860 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 12 ACTUAL P (PAGE 1166).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 812


Uni Gen 12 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18844 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 12 ACTUAL Q (PAGE 1167).

6 back to List of values (page 1)

Uni Gen 12 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18828 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 12 Actual P (page 812) and Uni Gen 12 Actual Q
(page 813).

6 back to List of values (page 1)

Uni Gen 12 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18947 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 12 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18931 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 813


Uni Gen 12 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18893 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 12 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18877 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 12 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18909 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 13

Uni Gen 13 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18967 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 13 NOM P (PAGE 1169).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 814


Uni Gen 13 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18861 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 13 ACTUAL P (PAGE 1168).

6 back to List of values (page 1)

Uni Gen 13 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18845 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 13 ACTUAL Q (PAGE 1168).

6 back to List of values (page 1)

Uni Gen 13 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18829 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 13 Actual P (page 815) and Uni Gen 13 Actual Q
(page 815).

6 back to List of values (page 1)

Uni Gen 13 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18948 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 815


Uni Gen 13 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18932 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 13 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18894 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 13 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18878 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 13 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18910 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 816


Subgroup: Uni Gen 14

Uni Gen 14 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18968 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 14 NOM P (PAGE 1170).

6 back to List of values (page 1)

Uni Gen 14 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18862 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 14 ACTUAL P (PAGE 1169).

6 back to List of values (page 1)

Uni Gen 14 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18846 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 14 ACTUAL Q (PAGE 1169).

6 back to List of values (page 1)

Uni Gen 14 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18830 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 14 Actual P (page 817) and Uni Gen 14 Actual Q
(page 817).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 817


Uni Gen 14 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18949 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 14 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18933 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 14 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18895 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 14 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18879 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 818


Uni Gen 14 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18911 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 15

Uni Gen 15 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18969 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 15 NOM P (PAGE 1171).

6 back to List of values (page 1)

Uni Gen 15 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18863 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 15 ACTUAL P (PAGE 1170).

6 back to List of values (page 1)

Uni Gen 15 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18847 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 15 ACTUAL Q (PAGE 1170).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 819


Uni Gen 15 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18831 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 15 Actual P (page 819) and Uni Gen 15 Actual Q
(page 819).

6 back to List of values (page 1)

Uni Gen 15 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18950 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 15 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18934 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 15 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18896 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 820


Uni Gen 15 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18880 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 15 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18912 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Subgroup: Uni Gen 16

Uni Gen 16 Nominal P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18970 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 16 NOM P (PAGE 1172).

6 back to List of values (page 1)

Uni Gen 16 Actual P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18864 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 16 ACTUAL P (PAGE 1171).

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 821


Uni Gen 16 Actual Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18848 Related applications MINT, MPTM
Description
This Value is a product of reading via LAI UNI GEN 16 ACTUAL Q (PAGE 1172).

6 back to List of values (page 1)

Uni Gen 16 Actual S

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18832 Related applications MINT, MPTM
Description
This Value is calculated internally from Uni Gen 16 Actual P (page 821) and Uni Gen 16 Actual Q
(page 822).

6 back to List of values (page 1)

Uni Gen 16 Actual Power Factor

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18951 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 16 Actual Load Character

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18935 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

InteliNeo 6000 1.5.0 Global Guide 822


Uni Gen 16 Requested P

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18897 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 16 Requested Q

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18881 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Uni Gen 16 Binary Outputs

Value group Universal Gensets Related FW 1.5.0


Units [-]
Comm object 18913 Related applications MINT, MPTM
Description
XYZ.

6 back to List of values (page 1)

Group: Renewables

REN Nominal P

Value group Renewables Related FW 1.5.0


Units kW
Comm
19729 Related applications MINT, MPTM
object
Description
This value shows nominal power of all renewables in the system.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 823


REN Actual P

Value group Renewables Related FW 1.5.0


Units kW
Comm
19728 Related applications MINT, MPTM
object
Description
Actual active power produced by all renewables in the system.

6 back to List of values

REN Actual Q

Value group Renewables Related FW 1.5.0


Units kVAr
Comm
19727 Related applications MINT, MPTM
object
Description
Actual reactive power produced by all renewables in the system.

6 back to List of values

REN Actual S

Value group Renewables Related FW 1.5.0


Units kVA
Comm
19726 Related applications MINT, MPTM
object
Description
Actual apparent power produced by all renewables in the system.

6 back to List of values

REN Actual Power Factor

Value group Renewables Related FW 1.5.0


Units [-]
Comm
19725 Related applications MINT, MPTM
object
Description
This value represents the actual power factor of all renewables in the system.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 824


REN Actual Load Character

Value group Renewables Related FW 1.5.0


Units [-]
Comm
19729 Related applications MINT, MPTM
object
Description
This value represents actual load character of all renewables in the system.

6 back to List of values

Group: Hybrid System

Total P

Value group Renewables Related FW 1.5.0


Units kW
Comm
20169 Related applications MINT, MPTM
object
Description
Total power produced by the Microgrid System.

6 back to List of values

Total Q

Value group Renewables Related FW 1.5.0


Units kVAr
Comm
20168 Related applications MINT, MPTM
object
Description
Total reactive power produced by the Microgrid System.

6 back to List of values

Total S

Value group Renewables Related FW 1.5.0


Units kVA
Comm
20167 Related applications MINT, MPTM
object
Description
Total apparent power produced by the Microgrid System.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 825


Total PF

Value group Renewables Related FW 1.5.0


Units
Comm
20166 Related applications MINT, MPTM
object
Description
This value represents the total power factor of the Microgrid System.

6 back to List of values

Total Load Character

Value group Renewables Related FW 1.5.0


Units
Comm
20165 Related applications MINT, MPTM
object
Description
This value represents the total load character of the Microgrid System.

6 back to List of values

Group: Gensets

Gensets P

Value group Gensets Related FW 1.5.0


Units [-]
Comm object 20183 Related applications MINT, MPTM
Description
This value represents the total power of all running Gen-sets.

6 back to List of values

Gensets Q

Value group Gensets Related FW 1.5.0


Units [-]
Comm object 20182 Related applications MINT, MPTM
Description
This value represents the reactive power of all running Gen-sets.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 826


Gensets Power Factor

Value group Gensets Related FW 1.5.0


Units [-]
Comm object 20181 Related applications MINT, MPTM
Description
This value represents the total power factor of all running Gen-sets.

6 back to List of values

Gensets Load Character

Value group Gensets Related FW 1.5.0


Units [-]
Comm object 20180 Related applications MINT, MPTM
Description
This value represents the total character of all running Gen-sets.

6 back to List of values

Group: Mains

Mains Import P Monitoring

Value group Mains Related FW 1.5.0


Units kW
Comm object 20172 Related applications MINT, MPTM
Description
Imported apparent power [kW] from Mains.

6 back to List of values

Mains Import Q Monitoring

Value group Mains Related FW 1.5.0


Units kVAr
Comm object 20171 Related applications MINT, MPTM
Description
Imported reactive power [kVAr] from Mains.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 827


Group: Load

Load P

Value group Load Related FW 1.5.0


Units kW
Comm object 10601 Related applications MINT, MPTM
Description
Load's active power.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

Load Q

Value group Load Related FW 1.5.0


Units kVAr
Comm object 10644 Related applications MINT, MPTM
Description
Load's reactive power.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

Load Power Factor

Load Load Related FW 1.5.0


Units [-]
Comm object 16158 Related applications MINT, MPTM
Description
Load's power factor.

6 back to List of values

Load Character

Value group Load Related FW 1.5.0


Units [-]
Related
Comm object 9026 MINT, MPTM
applications
Description
Load's character. "L" means inductive load, "C" is capacitive and "R" is resistive load (Load Power
Factor (page 828) = 1).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 828


Group: Grid Codes

Grid Codes Version

Value group Grid Codes Related FW 1.5.0


Units [-]
Comm object 16869 Related applications MPTM
Description
This value shows the Grid Codes module version.

6 back to List of values

Pmom

Value group Grid Codes Related FW 1.5.0


Units kW
Comm object 13019 Related applications MPTM
Description
This value contains BESS P (page 707) at the moment of start of either Power Regulation Based On
Over/Under Frequency (page 299) or Power Regulation Based On Actual Mains Voltage (page
302). This value is used for calculations.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

Test Frequency

Value group Grid Codes Related FW 1.5.0


Units Hz
Comm object 16614 Related applications MPTM
Description
This value contains frequency for testing of Grid Codes (page 299). Grid Codes Test (page 536) has
to be Enabled and alarm Wrn Test UPQF (page 1268) active. The value is filled as Nominal
Frequency (page 384) + value from LAI TESTF (PAGE 1151).

6 back to List of values

P Over Frequency Curve

Value group Grid Codes Related FW 1.5.0


Units %
Comm object 16185 Related applications MPTM
Description
This value contains actual y-axe value of POWER OVER FREQUENCY (PAGE 975) curve while LBO P OVER
FREQUENCY ACTIVE (PAGE 1096) is closed, otherwise it has Invalid flag (page 691).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 829


P Under Frequency Curve

Value group Grid Codes Related FW 1.5.0


Units %
Comm object 16184 Related applications MPTM
Description
This value contains actual y-axe value of POWER UNDER FREQUENCY (PAGE 976) curve while LBO P
UNDER FREQUENCY ACTIVE (PAGE 1096) is closed, otherwise it has Invalid flag (page 691).

6 back to List of values

Q(Um) Curve

Value group Grid Codes Related FW 1.5.0


Units kVAr
Comm object 13168 Related applications MPTM
Description
This value contains target of required reactive power based on Q(UM) (PAGE 967) curve while PF/Q
Control PTM Mode (page 356) = Q(Um) and Breaker state (page 886) = ParalOper, otherwise it has
Invalid flag (page 691).
See Q(Um) (page 268)PF/Q control (page 262) for more information.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

Qref/Ulim Curve

Value group Grid Codes Related FW 1.5.0


Units kVAr
Comm object 16149 Related applications MPTM
Description
This value contains target of required reactive power based on Qref/Ulim (page 968) curve while PF/Q
Control PTM Mode (page 356) = Qref/Ulim and Breaker state (page 886) = ParalOper, otherwise it
has Invalid flag (page 691).
See Qref/Ulim (page 270)PF/Q control (page 262)for more information.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 830


Q(P) Curve

Value group Grid Codes Related FW 1.5.0


Units kVAr
Comm object 16127 Related applications MPTM
Description
This value contains target of required reactive power based on Q(P) (PAGE 969) curve while PF/Q
Control PTM Mode (page 356) = Q(P) and Breaker state (page 886) = ParalOper, otherwise it has
Invalid flag (page 691).
See Q(P) (page 269)PF/Q control (page 262) for more information.
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

PF(P) Curve

Value group Grid Codes Related FW 1.5.0


Units kVAr
Comm object 13636 Related applications MPTM
Description
This value contains target of required power factor based on PF(P) (PAGE 970) curve while PF/Q
Control PTM Mode (page 356) = PF(P) and Breaker state (page 886) = ParalOper, otherwise it
has Invalid flag (page 691).
See PF(Pm) (page 267)PF/Q control (page 262) for more information.

6 back to List of values

P(Um) Curve

Value group Grid Codes Related FW 1.5.0


Units kW
Comm object 16568 Related applications MPTM
Description
This value contains actual value of P(Um) (page 971) curve while Power Regulation Based On Actual
Mains Voltage (page 302) is active.
The value is either related to value Pmom (page 829) or Installed Power (page 375) based on selected
mode of P(Um) (page 553).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 831


Pmom/Pave

Value group Grid Codes Related FW 1.5.0


Units kW
Comm object 16545 Related applications MPTM
Description
This value contais actual ratio of LAI PMOM (PAGE 1125) to Pave (page 569) and is used by application
curve P Mom/Pave Max (page 972).

6 back to List of values

Load Reduction 1 Occurrence

Value group Grid Codes Related FW 1.5.0


Units [-]
Comm object 16089 Related applications MPTM
Description
This value contains cumulative amount of occurrence of closed LBI LOAD REDUCTION 1 (PAGE 1006).
See Load Reduction (page 303) for more information.
Note: This value is never reset, you can change its value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 2 Occurrence

Value group Grid Codes Related FW 1.5.0


Units [-]
Comm object 16090 Related applications MPTM
Description
This value contains cumulative amount of occurrence of closed LBI LOAD REDUCTION 2 (PAGE 1006).
See Load Reduction (page 303) for more information.
Note: This value is never reset, you can change its value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 3 Occurrence

Value group Grid Codes Related FW 1.5.0


Units [-]
Comm object 16091 Related applications MPTM
Description
This value contains cumulative amount of occurrence of closed LBI LOAD REDUCTION 3 (PAGE 1007).
See Load Reduction (page 303) for more information.
Note: This value is never reset, you can change its value via "Set Statistics" in InteliConfig.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 832


Load Reduction 4 Occurrence

Value group Grid Codes Related FW 1.5.0


Units [-]
Comm object 16092 Related applications MPTM
Description
This value contains cumulative amount of occurrence of closed LBI LOAD REDUCTION 4 (PAGE 1007).
See Load Reduction (page 303) for more information.
Note: This value is never reset, you can change its value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 1 hrs Actual Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16103 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 1 (PAGE 1006) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

Load Reduction 1min Actual Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16107 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 1 (PAGE 1006) in actual month.
Note: Data are moved to Last Month every 1st day of month at 0:00.

6 back to List of values

Load Reduction 1 hrs Last Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16111 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 1 (PAGE 1006) in last month.
st
Note: Data are replaced with the value Load Reduction 1 hrs Actual Month (page 833) every 1
day of month at 0:00.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 833


Load Reduction 1 min Last Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16115 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 1 (PAGE 1006) in last month.
st
Note: Data are replaced with the value Load Reduction 1min Actual Month (page 833) every 1
day of month at 0:00.

6 back to List of values

Load Reduction 1 hrs Accumulated

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16093 Related applications MPTM
Description
This value contains accumulated hours of active LBI LOAD REDUCTION 1 (PAGE 1006) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 1 min Accumulated

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16094 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 1 (PAGE 1006) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 2 hrs Actual Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16104 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 2 (PAGE 1006) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 834


Load Reduction 2 min Actual Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16108 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 2 (PAGE 1006) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

Load Reduction 2 hrs Last Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16112 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 2 (PAGE 1006) in last month.
st
Note: Data are replaced with the value Load Reduction 2 hrs Actual Month (page 834) every 1
day of month at 0:00.

6 back to List of values

Load Reduction 2 min Last Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16116 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 2 (PAGE 1006) in last month.
st
Note: Data are replaced with the value Load Reduction 2 min Actual Month (page 835) every 1
day of month at 0:00.

6 back to List of values

Load Reduction 2 hrs Accumulated

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16095 Related applications MPTM
Description
This value contains accumulated hours of active LBI LOAD REDUCTION 2 (PAGE 1006) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 835


Load Reduction 2 min Accumulated

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16096 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 2 (PAGE 1006) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 3 hrs Actual Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16105 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 3 (PAGE 1007) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

Load Reduction 3 min Actual Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16109 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 3 (PAGE 1007) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

Load Reduction 3 hrs Last Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16113 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 3 (PAGE 1007) in last month.
st
Note: Data are replaced with the value Load Reduction 3 hrs Actual Month (page 836) every 1
day of month at 0:00.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 836


Load Reduction 3 min Last Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16117 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 3 (PAGE 1007) in last month.
st
Note: Data are replaced with the value Load Reduction 3 min Actual Month (page 836) every 1
day of month at 0:00.

6 back to List of values

Load Reduction 3 hrs Accumulated

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16097 Related applications MPTM
Description
This value contains accumulated hours of active LBI LOAD REDUCTION 3 (PAGE 1007) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 3 min Accumulated

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16098 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 3 (PAGE 1007) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

Load Reduction 4 hrs Actual Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16106 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 4 (PAGE 1007) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 837


Load Reduction 4 min Actual Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16110 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 4 (PAGE 1007) in actual month.
st
Note: Data are moved to Last Month every 1 day of month at 0:00.

6 back to List of values

Load Reduction 4 hrs Last Month

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16114 Related applications MPTM
Description
This value contains total hours of active LBI LOAD REDUCTION 4 (PAGE 1007) in last month.
st
Note: Data are replaced with the value Load Reduction 4 hrs Actual Month (page 837) every 1
day of month at 0:00.

6 back to List of values

Load Reduction 4 min Last Month

Value group Grid Codes Related FW 1.5.0


Units min
Comm object 16118 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 4 (PAGE 1007) in last month.
st
Note: Data are replaced with the value Load Reduction 4 min Actual Month (page 838) every 1
day of month at 0:00.

6 back to List of values

Load Reduction 4 hrs Accumulated

Value group Grid Codes Related FW 1.5.0


Units h
Comm object 16099 Related applications MPTM
Description
This value contains accumulated hours of active LBI LOAD REDUCTION 4 (PAGE 1007) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 838


Load Reduction 4 min Accumulated

Grid
Value group Related FW 1.5.0
Codes
Units min
Comm object 16100 Related applications MPTM
Description
This value contains minutes (up to 59) of active LBI LOAD REDUCTION 4 (PAGE 1007) from last reset of
this value.
Note: You can reset this value via "Set Statistics" in InteliConfig.

6 back to List of values

Group: Mains/Bus

Mains/Bus Frequency

Value group Mains/Bus Related FW 1.5.0


Units Hz
Comm object 20800 Related applications MINT, MPTM
Description
Frequency of Mains/Bus.

6 back to List of values

Mains/Bus Voltage L1-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 8195 Related applications MINT, MPTM
Description
Value of Mains/Bus voltage on phase 1.

6 back to List of values

Mains/Bus Voltage L2-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 8196 Related applications MINT, MPTM
Description
Value of Mains/Bus voltage on phase 2.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 839


Mains/Bus Voltage L3-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 8197 Related applications MINT, MPTM
Description
Value of Mains/Bus voltage on phase 3.

6 back to List of values

Mains/Bus Voltage L1-L2

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 9631 Related applications MINT, MPTM
Description
Value of Mains/Bus phase to phase voltage between L1 and L2 phases.

6 back to List of values

Mains/Bus Voltage L2-L3

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 9632 Related applications MINT, MPTM
Description
Value of Mains/Bus phase to phase voltage between L2 and L3 phases.

6 back to List of values

Mains/Bus Voltage L3-L1

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 9633 Related applications MINT, MPTM
Description
Value of Mains/Bus phase to phase voltage between L3 and L1 phases.

6 back to List of values

Mains/Bus Voltage

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 10666 Related applications MINT, MPTM
Description
Average value of all Mains/BusVoltage phases.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 840


Mains/Bus V Unabalance Ph-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 10549 Related applications MINT, MPTM
Description
This value contains the maximum difference of values Mains/Bus Voltage L1-N (page 839),
Mains/Bus Voltage L2-N (page 839), Mains/Bus Voltage L3-N (page 840) at a given moment.
Note: Difference of the values and the evaluation of the protection is influenced by the setpoint
Connection type (page 378).

6 back to List of values

Mains/Bus V Unbalance Ph-Ph

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 17337 Related applications MINT, MPTM
Description
This value contains the maximum difference of values Mains/Bus Voltage L1-L2 (page 840),
Mains/Bus Voltage L2-L3 (page 840), Mains/Bus Voltage L3-L1 (page 840) at a given moment.
Note: Difference of the values and the evaluation of the protection is influenced by the setpoint
Connection type (page 378).

6 back to List of values

+Mains/Bus Voltage

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16615 Related applications MINT, MPTM
Description
Value of +Mains/Bus voltage measured by Symmetrical components (page 16)

6 back to List of values

+Mains/Bus Voltage Relative

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16616 Related applications MINT, MPTM
Description
Value of +Mains/Bus voltage measured by Symmetrical components (page 16) which is related to
Mains/Bus Nominal Voltage Ph-N (page 381) or Mains/Bus Nominal Voltage Ph-Ph (page 381).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 841


Mains L1 Current

Value group Mains/Bus Related FW 1.5.0


Units A
Comm object 8208 Related applications MPTM
Description
Mains' current.
Note: This value is filled with 0 all the time if Mains Measurement P (page 364) != CT.

6 back to List of values

Mains L1 Current

Value group Mains/Bus Related FW 1.5.0


Units A
Comm object 8801 Related applications MINT, MPTM
Description
Current of the L1 phase of the Mains/Bus.

6 back to List of values

Mains L2 Current

Value group Mains/Bus Related FW 1.5.0


Units A
Comm object 8802 Related applications MINT, MPTM
Description
Current of the L2 phase of the Mains/Bus.

6 back to List of values

Mains L2 Current

Value group Mains/Bus Related FW 1.5.0


Units A
Comm object 8803 Related applications MINT, MPTM
Description
Current of the L3 phase of the Mains/Bus.

6 back to List of values

Mains Import P

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8703 Related applications MPTM
Description
Imported active power [kW] from Mains.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 842


Mains P L1

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8805 Related applications MINT, MPTM
Description
Imported active power [kW] from L1 phase of the Mains.

6 back to List of values

Mains P L2

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8806 Related applications MINT, MPTM
Description
Imported active power [kW] from L2 phase of the Mains.

6 back to List of values

Mains P L3

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8807 Related applications MINT, MPTM
Description
Imported active power [kW] from L3 phase of the Mains.

6 back to List of values

Mains Import Q

Value group Mains/Bus Related FW 1.5.0


Units kVAr
Comm object 8704 Related applications MPTM
Description
Imported reactive power [kVAr] from Mains.

6 back to List of values

Mains Import Q L1

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8808 Related applications MINT, MPTM
Description
Imported reactive power [kVAr] from L1 phase of the Mains.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 843


Mains Import Q L2

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8809 Related applications MINT, MPTM
Description
Imported reactive power [kVAr] from L2 phase of the Mains.

6 back to List of values

Mains Import Q L3

Value group Mains/Bus Related FW 1.5.0


Units kW
Comm object 8810 Related applications MINT, MPTM
Description
Imported reactive power [kVAr] from L3 phase of the Mains.

6 back to List of values

Mains/BusMainsBus Left Import S

Value group Mains/Bus Related FW 1.5.0


Units kVA
Comm object 8811 Related applications MINT, MPTM
Description
Imported apparent power [kVA] from Mains.

6 back to List of values

Mains S L1

Value group Mains/Bus Related FW 1.5.0


Units kVA
Comm object 8812 Related applications MINT, MPTM
Description
Imported apparent power [kVA] from L1 phase of the Mains.

6 back to List of values

Mains S L2

Value group Mains/Bus Related FW 1.5.0


Units kVA
Comm object 8813 Related applications MINT, MPTM
Description
Imported apparent power [kVA] from L2 phase of the Mains.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 844


Mains S L3

Value group Mains/Bus Related FW 1.5.0


Units kVA
Comm object 8814 Related applications MINT, MPTM
Description
Imported apparent power [kVA] from L3 phase of the Mains.

6 back to List of values

Mains PF

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 16157 Related applications MPTM
Description
Power factor of the Mains.

6 back to List of values

Mains Load Character

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 8709 Related applications MPTM
Description
Character of Mains load. "L" means inductive load, "C" is capacitive and "R" is resistive load (Mains PF
(page 845) = 1).
Load character of the Mains.
L = inductive load, C = capacitive load, and R = resistive load (Mains PF (page 845) = 1).

6 back to List of values

Mains Power Factor L1

Value
Mains/Bus Related FW 1.5.0
group
Units [-]
Comm
20580 Related applications MINT, MPTM
object
Description
Power factor of the L1 phase of the Mains/Bus.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 845


Mains Load Character L1

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 8818 Related applications MINT, MPTM
Description
Load character of the L1 phase of the Mains.
L = inductive load, C = capacitive load, and R = resistive load (Mains Power Factor L1 (page 845) = 1).

6 back to List of values

Mains Power Factor L2

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 20581 Related applications MINT, MPTM
Description
Power factor of the L2 phase of the Mains/Bus.

6 back to List of values

Mains Load Character L2

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 8819 Related applications MINT, MPTM
Description
Load character of the L2 phase of the Mains.
L = inductive load, C = capacitive load, and R = resistive load (Mains Power Factor L2 (page 846) = 1).

6 back to List of values

Mains Power Factor L3

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 20582 Related applications MINT, MPTM
Description
Power factor of the L3 phase of the Mains/Bus.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 846


Mains Load Character L3

Value group Mains/Bus Related FW 1.5.0


Units [-]
Comm object 8820 Related applications MINT, MPTM
Description
Load character of the L3 phase of the Mains.
L = inductive load, C = capacitive load, and R = resistive load (Mains Power Factor L3 (page 846) = 1).

6 back to List of values

Mains Voltage THD L1

Value group Mains/Bus Related FW 1.5.0


Units %
Comm object 16060 Related applications MINT, MPTM
Description
This value represents Voltage Total Harmonic Distortion (page 18) Mains/Bus Voltage L1-N (page
839).

6 back to List of values

Mains Voltage THD L2

Value group Mains/Bus Related FW 1.5.0


Units %
Comm object 16061 Related applications MINT, MPTM
Description
This value represents Voltage Total Harmonic Distortion (page 18) of Mains/Bus Voltage L2-N
(page 839).

6 back to List of values

Mains Voltage THD L3

Value group Mains/Bus Related FW 1.5.0


Units %
Comm object 16062 Related applications MINT, MPTM
Description
This value represents Voltage Total Harmonic Distortion (page 18) of Mains/Bus Voltage L3-N
(page 840).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 847


Mains Current THD L1

Value group Mains/Bus Related FW 1.5.0


Units %
Comm object 16064 Related applications MPTM
Description
This value represents Current Total Harmonic Distortion (page 18) of Mains L1 Current (page 842).

6 back to List of values

Mains Current THD L2

Value group Mains/Bus Related FW 1.5.0


Units %
Comm object 16065 Related applications MPTM
Description
This value represents Current Total Harmonic Distortion (page 18) of .

6 back to List of values

Mains Current THD L3

Value group Mains/Bus Related FW 1.5.0


Units %
Comm object 16066 Related applications MINT, MPTM
Description
This value represents Current Total Harmonic Distortion (page 18) of .

6 back to List of values

Max Vector Shift

Value group Mains/Bus Related FW 1.5.0


Units °
Comm object 9847 Related applications MINT, MPTM
Description
Maximal measured value of Vector shift (page 173) of the Mains. It is reset to zero always when:
Vector Shift Protection (page 593) = Parallel Only - controller goes to parallel toMains
operation
Vector Shift Protection (page 593) = Enabled - MCB gets closed

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 848


Mains Voltage 10min Avg L1-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16651 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L1-N (page 839).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 10min Avg L2-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16652 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L2-N (page 839).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 10min Avg L3-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16653 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L3-N (page 840).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 849


Mains Voltage 1min Avg L1-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16654 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L1-N (page 839).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 1min Avg L2-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16655 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L2-N (page 839).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 1min Avg L3-N

Value Group
Value group Related FW 1.5.0
Mains/Bus
Units V
Comm object 16656 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L3-N (page 840).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 850


Mains Voltage 10min Avg L1-L2

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16082 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L1-L2 (page 840).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 10min Avg L2-L3

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16083 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L2-L3 (page 840).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 10min Avg L3-L1

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16084 Related applications MPTM
Description
This value contains 10-minutes average of Mains/Bus Voltage L3-L1 (page 840).
See 10-minutes averages (page 309) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 1min Avg L1-L2

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16085 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L1-L2 (page 840).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 851


Mains Voltage 1min Avg L2-L3

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16086 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L2-L3 (page 840).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

Mains Voltage 1min Avg L3-L1

Value group Mains/Bus Related FW 1.5.0


Units V
Comm object 16087 Related applications MPTM
Description
This value contains 1-minute average of Mains/Bus Voltage L3-L1 (page 840).
See 1-minute averages (page 310) for more information.
Note: Value is reset when controller is switched off.

6 back to List of values

ROCOF1

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 9848 Related applications MINT, MPTM
Description
This value contains actual rate of change of frequency measured by ROCOF1 Protection (page 594).
See ROCOF (page 174) for more information.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 852


Max ROCOF1

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 10049 Related applications MINT, MPTM
Description
This value contains maximal rate of change of frequency measured by ROCOF1 Protection (page 594)
since the protection got active.
See ROCOF (page 174) for more information.

Setting Reset of value


Vector Shift/ROCOF CB
When MCB closes.
ROCOF1 Protection Selector (page 522) = MCB
(page 594) = Enabled Vector Shift/ROCOF CB
When BCB closes.
Selector (page 522) = BCB
ROCOF1 Protection After entering parallel operation
(page 594) = Parallel (Breaker state (page 886) =
Only ParalOper)

6 back to List of values

ROCOF2

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 16153 Related applications MINT, MPTM
Description
This value contains actual rate of change of frequency measured by ROCOF2 Protection (page 595).
See ROCOF (page 174) for more information.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 853


Max ROCOF2

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 16163 Related applications MINT, MPTM
Description
This value contains maximal rate of change of frequency measured by ROCOF2 Protection (page 595)
since the protection got active.
See ROCOF (page 174) for more information.

Setting Reset of value


Vector Shift/ROCOF CB
When MCB closes.
ROCOF2 Protection Selector (page 522) = MCB
(page 595) = Enabled Vector Shift/ROCOF CB
When BCB closes.
Selector (page 522) = BCB
ROCOF2 Protection After entering parallel operation
(page 595) = Parallel (Breaker state (page 886) =
Only ParalOper)

6 back to List of values

ROCOF3

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 16154 Related applications MINT, MPTM
Description
This value contains actual rate of change of frequency measured by ROCOF3 Protection (page 596).
See ROCOF (page 174) for more information.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 854


Max ROCOF3

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 16164 Related applications MINT, MPTM
Description
This value contains maximal rate of change of frequency measured by ROCOF3 Protection (page 596)
since the protection got active.
See ROCOF (page 174) for more information.

Setting Reset of value


Vector Shift/ROCOF CB
When MCB closes.
ROCOF3 Protection Selector (page 522) = MCB
(page 596) = Enabled Vector Shift/ROCOF CB
When BCB closes.
Selector (page 522) = BCB
ROCOF3 Protection After entering parallel operation
(page 596) = Parallel (Breaker state (page 886) =
Only ParalOper)

6 back to List of values

ROCOF4

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 16155 Related applications MINT, MPTM
Description
This value contains actual rate of change of frequency measured by ROCOF4 Protection (page 597).
See ROCOF (page 174) for more information.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 855


Max ROCOF4

Value group Mains/Bus Related FW 1.5.0


Units Hz/s
Comm object 16165 Related applications MINT, MPTM
Description
This value contains maximal rate of change of frequency measured by ROCOF4 Protection (page 597)
since the protection got active.
See ROCOF (page 174) for more information.

Setting Reset of value


Vector Shift/ROCOF CB
When MCB closes.
ROCOF4 Protection Selector (page 522) = MCB
(page 597) = Enabled Vector Shift/ROCOF CB
When BCB closes.
Selector (page 522) = BCB
ROCOF4 Protection After entering parallel operation
(page 597) = Parallel (Breaker state (page 886) =
Only ParalOper)

6 back to List of values

Group: Power Management

Engine Priority

Value group Power Management Related FW 1.5.0


Units -
Comm object 8624 Related applications MINT
Description
This value shows current priority number of the unit. It corresponds to the setpoint Priority (page 492)
except following situations:
If at least one of binary inputs TOP PRIORITY (PAGE 1030) is configured on some source and is
active
#Priority Auto Swap (page 493) is active

6 back to List of values

Actual Reserve

Value group Power Management Related FW 1.5.0


Units kW
Comm object 15805 Related applications MINT
Description
Actual absolute reserve in Power Management (page 274).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 856


Start Reserve

Value group Power Management Related FW 1.5.0


Units kW
Comm object 15806 Related applications MINT
Description
Required minimal Actual Reserve (page 856) for starting of next unit in the Power Management (page
274).

6 back to List of values

Stop Reserve

Value group Power Management Related FW 1.5.0


Units kW
Comm object 15807 Related applications MINT
Description
Required maximal Actual Reserve (page 856) for stopping of next unit in the Power Management
(page 274).

6 back to List of values

Dynamic Spinning Reserve

Value group Power Management Related FW 1.5.0


Units kW
Comm object 15673 Related applications MINT
Description
The value Dynamic Spinning Reserve is added to required load reserve given by setpoints #Starting
Load Reserve 1 (page 497) and #Stopping Load Reserve 1 (page 498) (according to actual load
reserve set 1, 2, 3 or 4) to shift the actual load reserve settings in dynamic way.

6 back to List of values

Dynamic Spinning Reserve Offset

Value group Power Management Related FW 1.5.0


Units kW
Comm object 15674 Related applications MINT
Description
The value Dynamic Spinning Reserve Offset is added only to required stopping load reserve given by
setpoints #Stopping Load Reserve 1 (page 498) (according to actual load reserve set 1, 2, 3 or 4) to
create some dynamic offset between starting and stopping load reserve.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 857


Actual Relative Reserve

Value group Power Management Related FW 1.5.0


Units %
Comm object 10788 Related applications MINT
Description
Actual relative reserve in Power Management (page 274).

6 back to List of values

Start Relative Reserve

Value group Power Management Related FW 1.5.0


Units %
Comm object 10786 Related applications MINT
Description
Required minimal Actual Relative Reserve (page 858) for starting of next unit in the Power
Management (page 274).

6 back to List of values

Stop Relative Reserve

Value group Power Management Related FW 1.5.0


Units %
Comm object 10787 Related applications MINT
Description
Required maximal Actual Relative Reserve (page 858) for stopping of next unit in the Power
Management (page 274).

6 back to List of values

Actual Active Power In PM

Value group Power Management Related FW 1.5.0


Units kW
Comm object 10657 Related applications MINT
Description
Actual value of active power from all controllers running in Power Management (page 274).

6 back to List of values

Actual Reactive Power In PM

Value group Power Management Related FW 1.5.0


Units kVAr
Comm object 10656 Related applications MINT
Description
Actual value of reactive power from all controllers running in Power Management (page 274).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 858


Running Nominal Power In PM

Value group Power Management Related FW 1.5.0


Units kW
Comm object 10999 Related applications MINT
Description
Actual nominal power of all running controllers on inter-controller CAN in Power Management (page
274).

6 back to List of values

Running Nominal Power Of All

Value group Power Management Related FW 1.5.0


Units kW
Comm object 10658 Related applications MINT
Description
Actual nominal power of all running controllers on inter-controller CAN.

6 back to List of values

Available Nominal Power

Value group Power Management Related FW 1.5.0


Units kW
Comm object 10998 Related applications MINT
Description
Available nominal power of all controllers on inter-controller CAN in Power Management (page 274).

6 back to List of values

Minimal Running Nominal Power

Value group Power Management Related FW 1.5.0


Units kW
Comm object 10012 Related applications MINT
Description
Actual minimal nominal power of all Controllers, which are running.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 859


Actual Power Band 32

Value group Power Management Related FW 1.5.0


Units [-]
Comm object 8974 Related applications MINT
Description
Required state of the Controllers with CAN address between 1 .. 32 in the actual power band of Power
Management (page 274).
Log 0: Controller should be stopped
Log 1: Controller should be running

Note: Actual power band = group of Controllers which should be running with actual load.

Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.

6 back to List of values

Actual Power Band 64

Value group Power Management Related FW 1.5.0


Units [-]
Comm object 16690 Related applications MINT
Description
Required state of the Gen-sets with CAN address between 33 .. 64 in the actual power band of Power
Management (page 274).
Log 0: Gen-set should be stopped
Log 1: Gen-set should be running

Note: Actual power band = group of Gen-sets which should be running with actual load.

Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.

6 back to List of values

Next Power Band 32

Value group Power Management Related FW 1.5.0


Units -
Comm object 8975 Related applications MINT
Description
Required state of the Gen-sets with CAN address between 1 .. 32 in the next power band of Power
Management (page 274).
Log 0: Gen-set should be stopped if load is decreased
Log 1: Gen-set should be started if load is increased

Note: Next power band = group of Gen-sets which should be running after load change.

Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 860


Next Power Band 64

Value group Power Management Related FW 1.5.0


Units -
Comm object 16691 Related applications MINT
Description
Required state of the Gen-sets with CAN address between 33 .. 64 in the next power band of Power
Management (page 274).
Log 0: Gen-set should be stopped if load is decreased
Log 1: Gen-set should be started if load is increased

Note: Next power band = group of Gen-sets which should be running after load change.

Note: Value is taken into account only if #Priority Auto Swap (page 493) = Efficient.

6 back to List of values

Group: Frequency/Load Control

BESS Required P Target

Frequency/Load
Value group Related FW 1.5.0
Control
Units kW
Comm object 8663 Related applications MINT, MPTM
Description
This value shows required active power at the end of ramping.

6 back to List of values

BESS Required P

Frequency/Load
Value group Related FW 1.5.0
Control
Units kW
Comm object 13105 Related applications MINT, MPTM
Description
This value shows required active power relative to the ramping procedure i.e. required active power right
now.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 861


BESS Required Relative P

Frequency/Load
Value group Related FW 1.5.0
Control
Units % of Nominal power (page 375)
Comm object 15900 Related applications MINT, MPTM
Description
Relative value of required power of the BESS.

6 back to List of values

Frequency Regulator Output

Frequency/Load
Value group Related FW 1.5.0
Control
Units V
Comm object 9052 Related applications MINT, MPTM
Description
This is the actual voltage on the frequency regulator output of the controller.
In case the Analog Output (page 257) is switched to PWM mode, the relation is:
10 V = ~100 % PWM.
-10 V = 0 % PWM

6 back to List of values

BESS Frequency Required

Frequency/Load
Value group Related FW 1.5.0
Control
Units Hz
Comm object 19446 Related applications MPTM
Description
Requested BESS frequency in Hz.

6 back to List of values

BESS Frequency Offset

Frequency/Load
Value group Related FW 1.5.0
Control
Units Hz
Comm object 19447 Related applications MPTM
Description
Relative value of requested power of the BESS.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 862


BESS P Required

Frequency/Load
Value group Related FW 1.5.0
Control
Units %
Comm object 19448 Related applications MPTM
Description
Relative request for BESS kW/Hz output in %.

6 back to List of values

System Load Control

Frequency/Load
Value group Related FW 1.5.0
Control
Units [-]
Comm object 10792 Related applications MPTM
Description
This value contains the actual LoadControl mode that the BESS is currently using. This value may differ
from setpoint Load Control PTM Mode (page 352) which contains requested Load Control mode.
List of possible states:

None The system is not operating.


Island The system operates in the Island mode.
The system operates in Baseload mode which is adjusted by the setpoint
BESS Charge Power (page 436)/BESS Discharge Power (page 437)
Baseload
while LBI BATT CHARGE ENABLE (PAGE 989)/BATT DISCHARGE ENABLE
(PAGE 989) is active.
The system operates in Baseload mode with import/export limitation.
Requested load is adjusted by the setpoint BESS Charge Power (page
Baseload with I/E
436)/BESS Discharge Power (page 437) while LBI BATT CHARGE
Limit
ENABLE (PAGE 989)/BATT DISCHARGE ENABLE (PAGE 989) is active but it
is limitated by the setpoint Import Load (page 355).
The system operates in Import/Export mode which is adjusted by the
Import/Export
setpoint Import Load (page 355).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 863


Group: Voltage/PF Control

System PF/Q Control

Value group Voltage/PF Control Related FW 1.5.0


Units [-]
Comm object 10793 Related applications MPTM
Description
This value contains the actual PF/Q Control mode that the BESS is currently using. This value may differ
from setpoint PF/Q Control PTM Mode (page 356) which contains requested PF/Q Control mode.
List of possible states:

None The system is not operating.


Island The system operates in the Island mode.
The system operates in PF Control mode which is adjusted by the setpoint #System Power Factor
PF Control BASE
(page 360).
The system operates in PF(Pm) mode which is adjusted by the application curve PF(P) (PAGE 970) in
PF(Pm) BASE
x-axe range 0 to 100%.
The system operates in Q Control mode which is adjusted by the setpoint #SYSTEM BASE Q (PAGE
Q Control BASE
361).
The system operates in Q(Um) mode which is adjusted by the application curve Q(UM) (PAGE 967)
Q(Um) BASE
with possible offset by the setpoint Q(UM) 0 REFERENCE (PAGE 565).
The system operates in Q(P) mode which is adjusted by the application curve Q(P) (PAGE 969) in x-
Q(P) BASE
axe range 0 to 100%.
The system operates in Qref/Ulim mode which is adjusted by the application curve QREF/ULIM (PAGE
Qref/Ulim BASE
968) with possible offset by the setpoint QREF/PNOM SHIFT (PAGE 566).
The system operates in PF Control mode which is adjusted by the setpoint IMPORT POWER FACTOR
PF Control IMP/EXP
(PAGE 359).
The system operates in PF(Pm) mode which is adjusted by the application curve PF(P) (PAGE 970) in
PF(Pm) IMP/EXP
x-axe range -100 to 100%.
Q Control IMP/EXP The system operates in Q Control mode which is adjusted by the setpoint IMPORT Q (PAGE 361).
The system operates in Q(Um) mode which is adjusted by the application curve Q(UM) (PAGE 967)
Q(Um) IMP/EXP
with possible offset by the setpoint Q(UM) 0 REFERENCE (PAGE 565).
The system operates in Q(P) mode which is adjusted by the application curve Q(P) (PAGE 969) in x-
Q(P) IMP/EXP
axe range -100 to 100%.
The system operates in Qref/Ulim mode which is adjusted by the application curve QREF/ULIM (PAGE
Qref/Ulim IMP/EXP
968) with possible offset by the setpoint QREF/PNOM SHIFT (PAGE 566).
The system operates in PF Control mode which is adjusted by the LAI PF CONTROL: ANEXT BASE PF
PF Control ANEXT BASE
(PAGE 1124).
The system operates in Q Control mode which is adjusted by the LAI Q CONTROL: ANEXT BASE Q
Q Control ANEXT BASE
(PAGE 1147).
The system operates in Q(Um) mode which is adjusted by the application curve Q(UM) (PAGE 967)
Q(Um) ANEXT BASE
with possible offset by the LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148).
The system operates in Qref/Ulim mode which is adjusted by the application curve QREF/ULIM (PAGE
Qref/Ulim ANEXT BASE
968) with possible offset by the LAI QREF/ULIM: ANEXT QREF/PNOM B Q (PAGE 1150).
The system operates in PF Control mode which is adjusted by the LAI PF CONTROL: ANEXT IMP/EXP
PF Control ANEXT IMP/EXP
PF (PAGE 1125).
The system operates in Q Control mode which is adjusted by the LAI Q(UM): 0 REF ANEXT IMP/EXP Q
Q Control ANEXT IMP/EXP
(PAGE 1149).
The system operates in Q(Um) mode which is adjusted by the application curve Q(UM) (PAGE 967)
Q(Um) ANEXT IMP/EXP
with possible offset by the LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148).
The system operates in Qref/Ulim mode which is adjusted by the application curve QREF/ULIM (PAGE
Qref/Ulim ANEXT IMP/EXP
968) with possible offset by the LAI QREF/ULIM: ANEXT QREF/PNOM I/E Q (PAGE 1151).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 864


BESS Required Q

Value group Voltage/PF Control Related FW 1.5.0


Units kVAr
Comm object 12877 Related applications MINT, MPTM
Description
Required reactive power.

6 back to List of values

BESS Required Qrel Lim

Value group Voltage/PF Control Related FW 1.5.0


Units %
Comm object 13169 Related applications MINT, MPTM
Description
Required relative reactive power.

6 back to List of values

BESS Required Relative Q

Value group Voltage/PF Control Related FW 1.5.0


Units %
Comm object 15901 Related applications MINT, MPTM
Description
Relative value of required reactive power of the BESS.

6 back to List of values

BESS Required PF

Value group Voltage/PF Control Related FW 1.5.0


Units [-]
Comm object 16159 Related applications MINT, MPTM
Description
Required Power Factor.

6 back to List of values

BESS Required PF Character

Value group Voltage/PF Control Related FW 1.5.0


Units [-]
Comm object 9033 Related applications MINT, MPTM
Description
Required Power Factor Character.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 865


Voltage Regulator Output

Value group Voltage/PF Control Related FW 1.5.0


Units V
Comm object 9053 Related applications MINT, MPTM
Description
This is the actual voltage on the voltage governor output of the controller.
In case the Analog Output (page 257) is switched to PWM mode, the relation is:
10 V = ~100 % PWM.
-10 V = 0 % PWM

6 back to List of values

Voltage Request

Value group Voltage/PF Control Related FW 1.5.0


Units %
Comm object 14997 Related applications MINT, MPTM
Description
This value contains the voltage control signal expressed in % for internal Voltage Request of internal
Voltage Regulator.

6 back to List of values

BESS Voltage Required

Value group Voltage/PF Control Related FW 1.5.0


Units V
Comm object 19443 Related applications MINT, MPTM
Description
Requested BESS output Voltage in V.

6 back to List of values

BESS Voltage Offset

Value group Voltage/PF Control Related FW 1.5.0


Units %
Comm object 19444 Related applications MINT, MPTM
Description
Requested offset from the BESS nominal output Voltage in V (positive or negative).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 866


BESS Q Required %

Value group Voltage/PF Control Related FW 1.5.0


Units %
Comm object 19445 Related applications MINT, MPTM
Description
Relative value of requested reactive power of the BESS.

6 back to List of values

Group: Controller I/O

Battery Voltage

Value group Controller I/O Related FW 1.5.0


Units V
Comm object 8213 Related applications MINT, MPTM
Description
Controller's supply voltage.

6 back to List of values

CU-AIN-01

Value group Controller I/O Related FW 1.5.0


Units Configurable
Comm object 9155 Related applications MINT, MPTM
Description
This is the value of the analog input 1 of the controller.
Note: Name of this value is changed according to the controller configuration.

6 back to List of values

CU-AIN-02

Value group Controller I/O Related FW 1.5.0


Units Configurable
Comm object 9156 Related applications MINT, MPTM
Description
This is the value of the analog input 2 of the controller.
Note: Name of this value is changed according to the controller configuration.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 867


CU-AIN-03

Value group Controller I/O Related FW 1.5.0


Units Configurable
Comm object 9157 Related applications MINT, MPTM
Description
This is the value of the analog input 3 of the controller.
Note: Name of this value is changed according to the controller configuration.

6 back to List of values

CU-AIN-04

Value group Controller I/O Related FW 1.5.0


Units Configurable
Comm object 9158 Related applications MINT, MPTM
Description
This is the value of the analog input 4 of the controller.
Note: Name of this value is changed according to the controller configuration.

6 back to List of values

Binary Inputs

Value group Controller I/O Related FW 1.5.0


Units [-]
Comm object 8235 Related applications MINT, MPTM
Description
States of the binary inputs of the controller.
01. CU-BIN-01
02. CU-BIN-02
03. CU-BIN-03
04. CU-BIN-04
05. CU-BIN-05
06. CU-BIN-06
07. CU-BIN-07
08. CU-BIN-08
09. CU-BIN-09
10. CU-BIN-10
11. CU-BIN-11
12. CU-BIN-12
Note: Names are changed based on names of representative binary inputs. See Default
configuration (page 118) to see default binary inputs names.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 868


E-STOP

Value group Controller I/O Related FW 1.5.0


Units [-]
Comm object 15780 Related applications MINT, MPTM
Description
Value of ㉓ E-STOP (page 47) .
Log .1 - E-STOP has voltage - alarm E-STOP (page 1280) is inactive
Log. 0 - E-STOP has no voltage - alarm E-STOP (page 1280) is active

6 back to List of values

Binary Outputs

Value group Controller I/O Related FW 1.5.0


Units [-]
Comm object 8239 Related applications MINT, MPTM
Description
State of the binary outputs of the controller.
01. CU-BOUT-01
02. CU-BOUT-02
03. CU-BOUT-03
04. CU-BOUT-04
05. CU-BOUT-05
06. CU-BOUT-06
07. CU-BOUT-07
08. CU-BOUT-08
09. CU-BOUT-09
10. CU-BOUT-10
11. CU-BOUT-11
12. CU-BOUT-12
Note: Names are changed based on names of representative binary outputs. See Default
configuration (page 118) to see default binary outputs names.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 869


Group: Statistics

PV kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15575 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the PV (renewables). The value is obtained by
counting the active power (PV Actual P (page 719)) of the PV.

6 back to List of values

PV Annual kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15576 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the PV (renewables) per year. The value is
obtained by counting the active power (PV Actual P (page 719)) of the PV.

6 back to List of values

PV Monthly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15577 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the PV (renewables) per month. The value is
obtained by counting the active power (PV Actual P (page 719)) of the PV.

6 back to List of values

PV Weekly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15578 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the PV (renewables) per week. The value is
obtained by counting the active power (PV Actual P (page 719)) of the PV.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 870


PV Daily kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15579 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the PV (renewables) per day. The value is
obtained by counting the active power (PV Actual P (page 719)) of the PV.

6 back to List of values

Maximal PV kWh

Value group Statistics Related FW 1.5.0


Units [-]
Comm object Related applications MINT, MPTM
Description
XYZ.

6 back to List of values

PV Total Curtailed kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 19548 Related applications MINT, MPTM
Description
The total energy lost due to curtailment across all PV arrays.

6 back to List of values

PV Curtailed Annual kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 19549 Related applications MINT, MPTM
Description
The energy lost due to curtailment over the course of a year.

6 back to List of values

PV Curtailed Monthly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 19550 Related applications MINT, MPTM
Description
Monthly energy losses due to curtailment.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 871


PV Curtailed Weekly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 19551 Related applications MINT, MPTM
Description
Weekly energy losses due to curtailment.

6 back to List of values

PV Curtailed Daily kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 19552 Related applications MINT, MPTM
Description
Daily energy losses due to curtailment.

6 back to List of values

WT kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15834 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the WT. The value is obtained by counting the
active power (WT Actual P (page 771)) of the WT.

6 back to List of values

WT Annual kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15835 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the WT per year. The value is obtained by
counting the active power (WT Actual P (page 771)) of the WT.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 872


WT Monthly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15836 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the WT per month. The value is obtained by
counting the active power (WT Actual P (page 771)) of the WT.

6 back to List of values

WT Weekly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15837 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the WT per week. The value is obtained by
counting the active power (WT Actual P (page 771)) of the WT.

6 back to List of values

WT Daily kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15838 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the WT per day. The value is obtained by
counting the active power (WT Actual P (page 771)) of the WT.

6 back to List of values

Batt. Charging Cycles

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 20230 Related applications MINT, MPTM
Description
This statistical value shows the charging cycles of the BESS. It is incremented together with LAI BATTERY
CHARGING CYCLES (PAGE 1115) which is the input for this value.
Note: Usually one charging cycle is defined as complete discharge of fully charged battery or a
series of partial drains equal to the battery’s capacity.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 873


Batt. Discharge kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15829 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh provided by the BESS to the system. The value is obtained
by counting the positive active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Discharge Annual kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15830 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh provided by the BESS to the system per year. The value is
obtained by counting the positive active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Discahrge Month kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15831 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh provided by the BESS to the system per month. The value
is obtained by counting the positive active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Discharge Week kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15832 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh provided by the BESS to the system per week. The value is
obtained by counting the positive active power (BESS P (page 707)) of the BESS.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 874


Batt. Discharge Daily kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15833 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh provided by the BESS to the system per day. The value is
obtained by counting the positive active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Charge kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15824 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh consumed by the BESS from the system. The value is
obtained by counting the negative active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Charge Annual kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15825 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh consumed by the BESS from the system per year. The
value is obtained by counting the negative active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Charge Month kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15826 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh consumed by the BESS from the system per month. The
value is obtained by counting the negative active power (BESS P (page 707)) of the BESS.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 875


Batt. Charge Week kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15827 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh consumed by the BESS from the system per week. The
value is obtained by counting the negative active power (BESS P (page 707)) of the BESS.

6 back to List of values

Batt. Charge Daily kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15828 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh consumed by the BESS from the system per day. The
value is obtained by counting the negative active power (BESS P (page 707)) of the BESS.

6 back to List of values

Hours Of Silent

Value group Statistics Related FW 1.5.0


Units h
Comm object 20130 Related applications MINT, MPTM
Description
This statistical value is showing diesel-off operation compared to total hours in hours.

6 back to List of values

Carbon Offset Equivalent

Value group Statistics Related FW 1.5.0


Units t
Comm object 19897 Related applications MINT, MPTM
Description
This statistical value is showing saved CO2 produced by diesel/gas genset per generated kWh by
alternative source of energy in tons.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 876


Gen kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15580 Related applications MINT, MPTM
Description
This statistical value is showing the total sum of energy in kWh.

6 back to List of values

Gen Annual kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15581 Related applications MINT, MPTM
Description
This statistical value is showing the sum of energy in kWh per year.

6 back to List of values

Gen Daily kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15584 Related applications MINT, MPTM
Description
This statistical value is showing the sum of energy in kWh per day.

6 back to List of values

Gen Monthly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15582 Related applications MINT, MPTM
Description
This statistical value is showing the sum of energy in kWh per month.

6 back to List of values

Gen Weekly kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 15583 Related applications MINT, MPTM
Description
This statistical value is showing the sum of energy in kWh per week.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 877


Fuel Used

Value group Statistics Related FW 1.5.0


Units l
Comm object 15585 Related applications MINT, MPTM
Description
This statistical value is showing the total fuel consumption from all gensets in litres.

6 back to List of values

Fuel Annual

Value group Statistics Related FW 1.5.0


Units l
Comm object 15586 Related applications MINT, MPTM
Description
This statistical value is showing the fuel consumption from all gensets in litres per year.

6 back to List of values

Fuel Monthly

Value group Statistics Related FW 1.5.0


Units l
Comm object 15587 Related applications MINT, MPTM
Description
This statistical value is showing the fuel consumption from all gensets in litres per month.

6 back to List of values

Fuel Weekly

Value group Statistics Related FW 1.5.0


Units l
Comm object 15588 Related applications MINT, MPTM
Description
This statistical value is showing the fuel consumption from all gensets in litres per week.

6 back to List of values

Fuel Daily

Value group Statistics Related FW 1.5.0


Units l
Comm object 15589 Related applications MINT, MPTM
Description
This statistical value is showing the fuel consumption from all gensets in litres per day.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 878


PCC kWh

Value group Statistics Related FW 1.5.0


Units kWh
Comm object 8205 Related applications MINT, MPTM
Description
This statistical value is showing the total kWh produced by the BESS. The value is obtained by counting
the active power (BESS P (page 707)) of the BESS.

6 back to List of values

PCC kVArh

Value group Statistics Related FW 1.5.0


Units kVArh
Comm object 8539 Related applications MINT, MPTM
Description
This statistical value is showing the total kVArh produced by the BESS. The value is obtained by counting
the reactive power (BESS Q (page 708)) of the BESS.

6 back to List of values

PCC kVAh

Value group Statistics Related FW 1.5.0


Units kVAh
Comm object 13663 Related applications MINT, MPTM
Description
This statistical value is showing the total kVAh produced by the BESS. The value is obtained by counting
the apparent power (BESS S (page 709)) of the BESS.

6 back to List of values

Mains kWh

Value group Statistics Related FW 1.5.0


Units kVAh
Comm object 11025 Related applications MPTM
Description
Counter of Mains Import P (page 842), when the value is negative
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 879


Mains kVArh

Value group Statistics Related FW 1.5.0


Units kVArh
Comm object 11026 Related applications MPTM
Description
Counter of Mains Import Q (page 843), when the value is negative
Note: This value can be also switched into one decimal see Power Formats And Units (page 196).

6 back to List of values

Running Hours

Value group Statistics Related FW 1.5.0


Units hours
Comm object 8206 Related applications MINT, MPTM
Description
BESS operation hours counter. The BESS hours are incremented in the controller while the BESS is
running. Source of running hours is adjusted via setpoint Run Hours Source (page 387).

6 back to List of values

Conditioned Running Hours 1

Value group Statistics Related FW 1.5.0


Units hours
Comm object 20292 Related applications MINT, MPTM
Description
This value contains counted hours while corresponding LBI is active.

6 back to List of values

Conditioned Running Hours 2

Value group Statistics Related FW 1.5.0


Units hours
Comm object 20293 Related applications MINT, MPTM
Description
This value contains counted hours while corresponding LBI is active.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 880


Num Starts

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 8207 Related applications MINT, MPTM
Description
BESS start commands counter. The counter is increased only by 1 even if the particular start command
will take more than one attempt.

6 back to List of values

Maintenance Timer 1 RunHours

Value group Statistics Related FW 1.5.0


Units hours
Comm object 11616 Related applications MINT, MPTM
Description
Countdown running hours until next maintenance. Initial value can be set in Maintenance Timer 1
RunHours (page 656).

6 back to List of values

Maintenance Timer 1 Interval

Value group Statistics Related FW 1.5.0


Units hours
Comm object 16387 Related applications MINT, MPTM
Description
Countdown days until next maintenance. Initial value can be set in Maintenance Timer 1 Interval (page
657).

6 back to List of values

Maintenance Timer 2 RunHours

Value group Statistics Related FW 1.5.0


Units hours
Comm object 11617 Related applications MINT, MPTM
Description
Countdown running hours until next maintenance. Initial value can be set in Maintenance Timer 2
RunHours (page 658).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 881


Maintenance Timer 2 Interval

Value group Statistics Related FW 1.5.0


Units hours
Comm object 16388 Related applications MINT, MPTM
Description
Countdown days until next maintenance. Initial value can be set in Maintenance Timer 2 Interval (page
658).

6 back to List of values

Maintenance Timer 3 RunHours

Value group Statistics Related FW 1.5.0


Units hours
Comm object 11618 Related applications MINT, MPTM
Description
Countdown running hours until next maintenance. Initial value can be set in Maintenance Timer 3
RunHours (page 659).

6 back to List of values

Maintenance Timer 3 Interval

Value group Statistics Related FW 1.5.0


Units hours
Comm object 16389 Related applications MINT, MPTM
Description
Countdown days until next maintenance. Initial value can be set in Maintenance Timer 3 Interval (page
660).

6 back to List of values

Maintenance Timer 4 RunHours

Value group Statistics Related FW 1.5.0


Units hours
Comm object 11619 Related applications MINT, MPTM
Description
Countdown running hours until next maintenance. Initial value can be set in Maintenance Timer 4
RunHours (page 661).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 882


Maintenance Timer 4 Interval

Value group Statistics Related FW 1.5.0


Units hours
Comm object 20288 Related applications MINT, MPTM
Description
Countdown days until next maintenance. Initial value can be set in Maintenance Timer 4 Interval (page
661).

6 back to List of values

Num E-Stops

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 11195 Related applications MINT, MPTM
Description
This value counts amount of BESS shutdowns which are triggered by E-STOP (page 1280) or
Emergency Stop (page 1280).
Note: Value is incremented only if BESS was running during alarm activation.

6 back to List of values

Shutdowns

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 11196 Related applications MINT, MPTM
Description
This counter counts occurrences of a Shutdown (page 1280) alarm which actually shutdowns the
BESS. If 2 shutdown alarms are received at the same time, this value is increased only by 1.
Note: This value does not count occurrences of E-STOP (page 1280) and Emergency Stop (page
1280). These are counted separately in Num E-Stops (page 883).

6 back to List of values

Fast Pulse Counter 1

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 20303 Related applications MINT, MPTM
Description
This is the Statistic value of the Fast Pulse Counter 1 which is physically configured to binary input 9.
Change the conversion rate via setpoint Conversion Coeff. Fast Pulse 1 (page 390).
See the chapter Pulse Counters (page 211) for more information.
Note: The Value can be set via InteliConfig in the interface "Set Statistics".

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 883


Fast Pulse Counter 2

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 20304 Related applications MINT, MPTM
Description
This is the Statistic value of the Fast Pulse Counter 2 which is physically configured to binary input 10.
Change the conversion rate via setpoint Conversion Coeff. Fast Pulse 2 (page 390).
See the chapter Pulse Counters (page 211) for more information.
Note: The Value can be set via InteliConfig in the interface "Set Statistics".

6 back to List of values

Pulse Counter 1

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 10986 Related applications MINT, MPTM
Description
This is the Statistic value of the Pulse Counter 1 which is connected with LBI PULSE COUNTER 1 (PAGE
1018). Change the conversion rate via setpoint Conversion Coefficient Pulse 1 (page 391).
See the chapter Pulse Counters (page 211) for more information.
Note: The Value can be set via InteliConfig in the interface "Set Statistics".

6 back to List of values

Pulse Counter 2

Value group Statistics Related FW 1.5.0


Units [-]
Comm object 10987 Related applications MINT, MPTM
Description
This is the Statistic value of Pulse the Counter 2 which is connected with LBI PULSE COUNTER 2 (PAGE
1018). Change the conversion rate via setpoint Conversion Coefficient Pulse 2 (page 391).
See the chapter Pulse Counters (page 211) for more information.
Note: The Value can be set via InteliConfig in the interface "Set Statistics".

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 884


Group: Info

Application Mode

Value group Info Related FW 1.5.0


Units [-]
Comm object 14446 Related applications MINT, MPTM
Description
This value reflects which application is used for the controller at the moment.
The application is selected based on setpoint Default Application Select (page 351), LBI APPLICATION
MINT (PAGE 989) and APPLICATION MPTM (PAGE 989)

LBI APPLICATION LBI APPLICATION LBI APPLICATION


Application Mode
MINT (PAGE 989) MPTM (PAGE 989) SPI (PAGE 1)
Based on Default
0 0 0 Application Select (page
351)
0 1 0 MPTM
1 0 0 MINT
1 1 0 MPTM

IMPORTANT: Application Mode can be changed only if Controller Mode (page 885) = OFF.

6 back to List of values

Controller Mode

Value group Info Related FW 1.5.0


Units [-]
Comm object 9887 Related applications MINT, MPTM
Description
Controller mode.

6 back to List of values

Load Shedding Status

Value group Info Related FW 1.5.0


Units [-]
Comm object 9591 Related applications MINT, MPTM
Description
This value contains actual active highest stage of Load shedding stages (page 171). Value has range
from 0 to 8 , where 0 means no load shedding stage is active.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 885


BESS state

Value group Info Related FW 1.5.0


Units [-]
Comm object 9244 Related applications MINT, MPTM
Description
This value contains actualBESS state message.

6 back to List of values

Breaker state

Value group Info Related FW 1.5.0


Units [-]
Comm object 9245 Related applications MINT, MPTM
Description
This value contains actual breaker state message.

6 back to List of values

Timer Text

Value group Info Related FW 1.5.0


Units [-]
Comm object 10040 Related applications MINT, MPTM
Description
This value contains actual timer text message.

6 back to List of values

Connection Type

Value group Info Related FW 1.5.0


Units [-]
Comm object 12944 Related applications MINT, MPTM
Description
This value contains name of currently selected connection type, which is adjusted via Connection type
(page 378).

6 back to List of values

Timer Value

Value group Info Related FW 1.5.0


Units [MM:SS]
Comm object 14147 Related applications MINT, MPTM
Description
This value contains time of active timer which is counted down, name of the timer is in value Timer Text
(page 886).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 886


ID String

Value group Info Related FW 1.5.0


Units [-]
Comm object 24501 Related applications MINT, MPTM
Description
Name of controller which is used in InteliConfig in command bar.

6 back to List of values

FW Version

Value group Info Related FW 1.5.0


Units [-]
Comm object 24339 Related applications MINT, MPTM
Description
Major and minor firmware version number.

6 back to List of values

Application

Value group Info Related FW 1.5.0


Units [-]
Comm object 8480 Related applications MINT, MPTM
Description
The value contains actual application in controller.

6 back to List of values

FW Branch

Value group Info Related FW 1.5.0


Units [-]
Comm object 8707 Related applications MINT, MPTM
Description
The value contains actual branch of firmware in controller.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 887


CAN Intercontroller Comm Mode

Value group Info Related FW 1.5.0


Units [-]
Comm object 23969 Related applications MINT, MPTM
Description
This value contains actual mode of CAN Intercontroller Communication (page 132).
Note: In case that there is a mismatch between this value and setpoint CAN Intercontroller Comm
Mode (page 397), alarm ALI CAN Mode Inconsistency (page 1271) is activated.

6 back to List of values

CAN Intercontroller Comm Redundancy

Value group Info Related FW 1.5.0


Units [-]
Comm object 23970 Related applications MINT, MPTM
Description
This value informs if CAN Intercontroller communication Redundancy is enabled or not.
Note: In case that there is a mismatch between this value and setpoint CAN Intercontroller Comm
Mode (page 397), alarm ALI CAN Mode Inconsistency (page 1271) is activated.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 888


SD Card Status

Value group Info Related FW 1.5.0


Units [-]
Comm object 20589 Related applications MINT, MPTM
Description
This value shows the actual status of the SD Card.

Value Meaning
Mount In Progress The SD Card is being booted.
Not Inserted There is no SD Card in the SD card slot detected.
The SD card is inserted but the setpoint SD Card File System
Unmount
(page 401) is set to Unmount option.
Ready To Use SD Card is mounted and ready to be used.
Format Required The wrong file system format of the SD Card is detected.
Formatting The formatting process of the SD Card is active.
Formatting Failed The formatting process failed.
Write Protected It is not possible to write data on SD Card (Read Only mode).
Used SD Card is not supported (wrong parameters of the SD
Not Supported
card).
This status is used for any other errors which are not covered by
Error
the states above.

6 back to List of values

SD Card Capacity

Value group Info Related FW 1.5.0


Units [GB]
Comm object 20026 Related applications MINT, MPTM
Description
This value provides information about SD Card storage capacity in GB.

6 back to List of values

SD Card Free Space

Value group Info Related FW 1.5.0


Units [%]
Comm object 20027 Related applications MINT, MPTM
Description
This value shows relative free space of SD Card storage.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 889


History Lifetime

Value group Info Related FW 1.5.0


Units [%]
Comm object 20284 Related applications MINT, MPTM
Description
This value shows the lifetime usage of non-volatile memory which is used for storing of history records.
Please refer to the table below for detailed information.

Value [%] Meaning


-1 Memory's lifetime usage can not be obtained.
10 Memory's lifetime usage is between 0-10%.
20 Memory's lifetime usage is between 11-20%..
30 Memory's lifetime usage is between 21-30%.
40 Memory's lifetime usage is between 31-40%.
50 Memory's lifetime usage is between 41-50%.
60 Memory's lifetime usage is between 51-60%.
70 Memory's lifetime usage is between 61-70%.
80 Memory's lifetime usage is between 71-80%.
90 Memory's lifetime usage is between 81-90%.
100 Memory's lifetime usage is between 91-100%.
110 Memory's lifetime usage is over 100 %. The memory may fail.

6 back to List of values

Forced Value Status

Value group Info Related FW 1.5.0


Units [-]
Comm object 20544 Related applications MINT, MPTM
Description
This value contains list of all 32 LBIs for Forced Value (page 158). Logical 1 means that the respective
LBI is currently activated.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 890


SW Key Feature List

Value group Info Related FW 1.5.0


Units [-]
Comm object 20591 Related applications MINT, MPTM
Description
This value contains list of premium features which are unlocked by SW key. Logical 1 means that the
feature is activated and can be used without of restrictions.
1. CAN Intercontroller Redundancy
2. Modbus Master
3. Hot Swap Redundancy
4. PLC Extended
5. Variable Speed BESS

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 891


Hot Swap Redundancy Status

Value group Info Related FW 1.5.0


Units [-]
Comm object 16887 Related applications MINT, MPTM
Description
This value contains list of status bits related to Hot Swap Redundancy. If Hot Swap Redundancy (page
371) = Master, at least one of the bits 01-04 is active, bits 05-08 are never active. If Hot Swap
Redundancy (page 371) = Backup, at least one of the bits 05-08 is active, bits 01-04 are never active. If
Hot Swap Redundancy (page 371) = Disabled, none of the bits is active.

Master: Backup this controller is the master


Alive the master is receiving heartbeat from backup
this controller is the master

Master: Backup the master is considered to be dead by the backup controller


Control the master is forced to the listening mode
the backup is controlling
this controller is the master
Master: Ready to
the master is alive
Control
the master is controlling/the master is ready to control

Master: Data this controller is the master


Synchro Fail the master is not receiving data from backup

Backup: Master this controller is the backup


Alive the backup is receiving heartbeat from master
this controller is the backup

Backup: Master the backup is considered to be dead by the master controller


Control the backup is forced to the listening mode
the master is controlling
this controller is the backup
Backup: Ready
the backup is alive
to Control
the backup is controlling/the backup is ready to control

Backup: Data this controller is the backup


Synchro Fail the backup is not receiving data from master

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 892


CAN16

Value group Info Related FW 1.5.0


Units [-]
Comm object 8546 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <1,16>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - this controller receives messages from the controller with specific CAN address
Log. 0 - this controller does not receive messages from the controller with specific CAN address

6 back to List of values

CAN32

Value group Info Related FW 1.5.0


Units [-]
Comm object 8827 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <17,32>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - this controller receives messages from the controller with specific CAN address
Log. 0 - this controller does not receive messages from the controller with specific CAN address

6 back to List of values

CAN48

Value group Info Related FW 1.5.0


Units [-]
Comm object 16684 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <33,48>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - this controller receives messages from the controller with specific CAN address
Log. 0 - this controller does not receive messages from the controller with specific CAN address

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 893


CAN64

Value group Info Related FW 1.5.0


Units [-]
Comm object 16685 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <49,64>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - this controller receives messages from the controller with specific CAN address
Log. 0 - this controller does not receive messages from the controller with specific CAN address

6 back to List of values

Reg16

Value group Info Related FW 1.5.0


Units [-]
Comm object 11081 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <1,16>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is in the same group (is connected to the same bus).
Log. 0 - controller with this CAN address is NOT in the same group (is NOT connected to the
same bus).

6 back to List of values

Reg32

Value group Info Related FW 1.5.0


Units [-]
Comm object 11082 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <17,32>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is in the same group (is connected to the same bus).
Log. 0 - controller with this CAN address is NOT in the same group (is NOT connected to the
same bus).

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 894


Reg48

Value group Info Related FW 1.5.0


Units [-]
Comm object 16688 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <33,48>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is in the same group (is connected to the same bus).
Log. 0 - controller with this CAN address is NOT in the same group (is NOT connected to the
same bus).

6 back to List of values

Reg64

Value group Info Related FW 1.5.0


Units [-]
Comm object 16689 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <49,64>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is in the same group (is connected to the same bus).
Log. 0 - controller with this CAN address is NOT in the same group (is NOT connected to the
same bus).

6 back to List of values

Gen Loaded 16

Value group Info Related FW 1.5.0


Units [-]
Comm object 10196 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <1,16>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is currently loaded
Log. 0 - controller with this CAN address is currently not loaded

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 895


Gen Loaded 32

Value group Info Related FW 1.5.0


Units [-]
Comm object 10197 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <17,32>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is currently loaded
Log. 0 - controller with this CAN address is currently not loaded

6 back to List of values

Gen Loaded 48

Value group Info Related FW 1.5.0


Units [-]
Comm object 16686 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <33,48>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is currently loaded
Log. 0 - controller with this CAN address is currently not loaded

6 back to List of values

Gen Loaded 64

Value group Info Related FW 1.5.0


Units [-]
Comm object 16687 Related applications MINT
Description
This value contains binary information about controllers connected via CAN2A (page 19) and/or CAN2B
(page 19) with CAN Controller Address (page 392) = <49,64>. Each bit represent controller with the
same CAN address as number of the bit.
Log. 1 - controller with this CAN address is currently loaded
Log. 0 - controller with this CAN address is currently not loaded

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 896


SPI Module A

Value group Info Related FW 1.5.0


Units [-]
Comm object 14447 Related applications MINT, MPTM
Description
Detected Plug-in module in the slot A.

6 back to List of values

SPI Module B

Value group Info Related FW 1.5.0


Units [-]
Comm object 14448 Related applications MINT, MPTM
Description
Detected Plug-in module in the slot B.

6 back to List of values

Group: User Buttons

User Buttons

Value group User Buttons Related FW 1.5.0


Units [-]
Comm object 20743 Related applications MINT, MPTM
Description
State of User Buttons (page 224).

1. User Button 1 11. User Button 11 21. User Button 21 31. User Button 31
2. User Button 2 12. User Button 12 22. User Button 22 32. User Button 32
3. User Button 3 13. User Button 13 23. User Button 23
4. User Button 4 14. User Button 14 24. User Button 24
5. User Button 5 15. User Button 15 25. User Button 25
6. User Button 6 16. User Button 16 26. User Button 26
7. User Button 7 17. User Button 17 27. User Button 27
8. User Button 8 18. User Button 18 28. User Button 28
9. User Button 9 19. User Button 19 29. User Button 29
10. User Button 10 20. User Button 20 30. User Button 30

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 897


Group: Log Bout

Log Bout 1

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9143 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 2

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9144 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 3

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9145 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 4

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9146 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 5

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9147 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 898


Log Bout 6

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9148 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 7

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9149 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 8

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 9150 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 9

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11896 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 10

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11897 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 899


Log Bout 11

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11898 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 12

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11899 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 13

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11900 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 14

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11901 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

Log Bout 15

Value group Log Bout Related FW 1.5.0


Units [-]
Comm object 11902 Related applications MINT, MPTM
Description
State of binary outputs.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 900


Group: Scheduler

Time

Value group Scheduler Related FW 1.5.0


Units HH:MM:SS
Related
Comm object 24554 MINT, MPTM
applications
Description
Shows setup time.

6 back to List of values

Date

Value group Scheduler Related FW 1.5.0


Units DD.MM.YYYY
Comm object 24553 Related applications MINT, MPTM
Description
Shows setup date.

6 back to List of values

Time Mode

Value group Scheduler Related FW 1.5.0


Units [-]
Related
Comm object 20252 MINT, MPTM
applications
Description
Shows setup time mode.
STD - Standard zone time (e.g GMT+1 for Prague)
DST - Daylight Saving Time = STD+1 (e.g. GMT+2 for Prague)

6 back to List of values

Sunrise Time

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
20223 Related applications MINT, MPTM
object
Description
This value indicates the time until sunrise.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 901


Sunset Time

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
20221 Related applications MINT, MPTM
object
Description
This value indicates the time until sunset.

6 back to List of values

Time To Sunrise

Value group Scheduler Related FW 1.5.0


Units [min]
Comm
19046 Related applications MINT, MPTM
object
Description
This value shows remaining time until sunrise.

6 back to List of values

Time To Sunset

Value group Scheduler Related FW 1.5.0


Units [min]
Comm
19047 Related applications MINT, MPTM
object
Description
This value shows remaining time until sunset.

6 back to List of values

Exercise Timer 1

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19664 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 1.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 902


Exercise Timer 2

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19665 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 2.

6 back to List of values

Exercise Timer 3

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19666 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 3.

6 back to List of values

Exercise Timer 4

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19667 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 4.

6 back to List of values

Exercise Timer 5

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19668 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 5.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 903


Exercise Timer 6

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19669 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 6.

6 back to List of values

Exercise Timer 7

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19670 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 7.

6 back to List of values

Exercise Timer 8

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19671 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 8.

6 back to List of values

Exercise Timer 9

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19672 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 9.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 904


Exercise Timer 10

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19673 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 10.

6 back to List of values

Exercise Timer 11

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19674 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 11.

6 back to List of values

Exercise Timer 12

Value group Scheduler Related FW 1.5.0


Units [hh:mm.ss]
Comm
19675 Related applications MINT, MPTM
object
Description
Value for Exercise Timer 12.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 905


Group: Ethernet

Subgroup: Ethernet Port Status

ETH Port 1 Status

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24050 Related applications MINT, MPTM
Description
This value reflects what communication mode is used on the Ethernet Port 1.

Link Down There is no connected cable to the Ethernet Port (socket) or the cable is broken.
10- HD 10 Mbit Half-Duplex
10- FD 10 Mbit Full-Duplex
100- HD 100 Mbit Half-Duplex
100- FD 100 Mbit Full-Duplex

Note: Note: At one time the Half-Duplex can only send or receive the information whereas Full-
Duplex can do both at once.

6 back to List of values

ETH Port 2 Status

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24088 Related applications MINT, MPTM
Description
This value reflects what communication mode is used on the Ethernet Port 2.

Link Down There is no connected cable to the Ethernet Port (socket) or the cable is broken.
10- HD 10 Mbit Half-Duplex
10- FD 10 Mbit Full-Duplex
100- HD 100 Mbit Half-Duplex
100- FD 100 Mbit Full-Duplex

Note: Note: At one time the Half-Duplex can only send or receive the information whereas Full-
Duplex can do both at once.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 906


ETH Port 3 Status

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24064 Related applications MINT, MPTM
Description
This value reflects what communication mode is used on the Ethernet Port 3.

Link Down There is no connected cable to the Ethernet Port (socket) or the cable is broken.
10- HD 10 Mbit Half-Duplex
10- FD 10 Mbit Full-Duplex
100- HD 100 Mbit Half-Duplex
100- FD 100 Mbit Full-Duplex

Note: Note: At one time the Half-Duplex can only send or receive the information whereas Full-
Duplex can do both at once.

6 back to List of values

Subgroup: Trusted Interface

MAC Address

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 23834 Related applications MINT, MPTM
Description
MAC address of the controller's trusted interface.

6 back to List of values

Current IP Address

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24060 Related applications MINT, MPTM
Description
Current IP address of the Ethernet 1 (page 19) interface.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 907


Current Subnet Mask

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24058 Related applications MINT, MPTM
Description
Current subnet mask of the Ethernet 1 (page 19) interface.

6 back to List of values

Current Gateway

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24056 Related applications MINT, MPTM
Description
Current gateway address the Ethernet 1 (page 19) communication.

6 back to List of values

ETH Interface Status

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24062 Related applications MINT, MPTM
Description
Current status.of the Ethernet 1 (page 19) communication.

6 back to List of values

Subgroup: Untrusted Interface

MAC Address

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24333 Related applications MINT, MPTM
Description
MAC address of the controller's untrusted interface.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 908


Current IP Address

Value group Ethernet Related FW 1.5.0


Units [-]
Related
Comm object 24184 MINT, MPTM
applications
Description
Current IP address of the Ethernet 2 (page 19) interface.

6 back to List of values

Current Subnet Mask

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24183 Related applications MINT, MPTM
Description
Current subnet mask of the Ethernet 2 (page 19) interface.

6 back to List of values

Current Gateway

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24182 Related applications MINT, MPTM
Description
Current IP gateway address of the Ethernet 2 (page 19) communications.

6 back to List of values

Primary DNS

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24181 Related applications MINT, MPTM
Description
Current domain name server of the Ethernet 2 (page 19) interface.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 909


Secondary DNS

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24100 Related applications MINT, MPTM
Description
Backup domain name server of the Ethernet 2 (page 19) interface.

6 back to List of values

ETH Interface Status

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24180 Related applications MINT, MPTM
Description
Current status of the Ethernet 2 (page 19) communication.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 910


AirGate Status

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24007 Related applications MINT, MPTM
Description
Diagnostic code for AirGate connection. Helps with troubleshooting.
IMPORTANT: If the AirGate key in the Access Administration is empty the controller will
not connect to the AirGate despite the function is enabled. Access Administration is
available in Tools of the InteliConfig.

Code Value Description


Not trying to connect to AirGate. This is initial value of the
0 Not defined
status.
1 Waiting to connect Waiting for the next attempt to connect to a node.
Resolving the domain name of the node to which it is
2 Resolving
attempting to connect.
3 Connecting Attempting to estabilish TCP link to the node.
4 Creating secure channel Encrypted channel is being negotiated.
5 Registration Encrypted channel has been estabilished.
6 Connected, inoperable AirGate server has not sent an authorization yet.
AiGate server authorized the connection and the AirGate
7 Connected, operable
connection is up and running.
The service is enabled but suspended due to empty
8 Suspended, empty key
AirGate key.

6 back to List of values

AirGate ID

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24345 Related applications MINT, MPTM
Description
Identification string generated by AirGate server for the purpose of establishing communication via
InteliConfig or any other supported PC tool.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 911


AirGate Servicing Node

Value group Info Related FW 1.5.0


Units [-]
Comm object 24010 Related applications MINT, MPTM
Description
This value displays the IP address to Servicing node to which is controller connected in order to use
AirGate connection.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 912


Last E-mail Result

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 24332 Related applications MINT, MPTM
Description
Result of last email, which was sent by controller.

Code Description
0 Email was successfully sent.
1 SIMCom declined connection request.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
4 Maximum transmitted data length not defined.
5 No response from SMTP server.
6 Command to SMTP server not sent.
7 Did not receive data from SMTP server.
8 HELO command was refused.
9 EHLO command was refused.
10 SMTP server does not support 8-bit encoding.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
18 SMTP server rejected email data.
19 SMTP server rejected email data.
20 QUIT command was refused.
21 There is no valid server IP address.
22 Process of sending email aborted.
23 Closing connection error.
24 Failed to accept server response after connection is established.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
27 Email address can???t be read.
28 Error during encoding process.
29 Error during HMAC MD5 encoding process.
30 There is no attempt for sending email yet.

InteliNeo 6000 1.5.0 Global Guide 913


31 Cannot resolve SMTP server's IP address.
32 Error while reading CO 24327 (base64 email data)
33 Problem with authorization type (i.e. smtp.gmail.com support only STARTTLS)
34 SMTP server does not support STARTTLS command.
35 STARTTLS command was refused.
36 There is a problem during TLS handshake process.

6 back to List of values

Subgroup: Modbus Interface

MAC Address

Value group Ethernet Related FW 1.5.0


Units [-]
Comm object 23833 Related applications MINT, MPTM
Description
MAC address of the controller's Modbus interface.

6 back to List of values

Current IP Address

ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24046 Related applications MINT, MPTM
Description
Current IP address of the Ethernet 3 (page 19) interface.

6 back to List of values

Current Subnet Mask

ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24044 Related applications MINT, MPTM
Description
Current subnet mask of the Ethernet 3 (page 19) interface.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 914


Current Gateway

ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24042 Related applications MINT, MPTM
Description
Current IP gateway address of the Ethernet 3 (page 19) communications.

6 back to List of values

Primary DNS

ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24039 Related applications MINT, MPTM
Description
Current domain name server of the Ethernet 3 (page 19) interface.

6 back to List of values

Secondary DNS

ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24037 Related applications MINT, MPTM
Description
Backup domain name server of the Ethernet 3 (page 19) interface.

6 back to List of values

ETH Interface Status

ETH Interface 3 -
Value group Related FW 1.5.0
Modbus
Units [-]
Comm object 24048 Related applications MINT, MPTM
Description
Current status of the Ethernet 3 (page 19) communication.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 915


Group: PLC

PLC-AOUT 1

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21248 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 2

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21249 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 3

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21250 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 4

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21251 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 5

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21252 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 916


PLC-AOUT 6

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21253 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 7

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21254 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 8

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21255 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 9

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21256 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 10

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21257 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 917


PLC-AOUT 11

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21258 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 12

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21259 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 13

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21260 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 14

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21261 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 15

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21262 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 918


PLC-AOUT 16

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21263 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 17

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21264 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 18

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21265 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 19

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21266 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 20

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21267 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 919


PLC-AOUT 21

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21268 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 22

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21269 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 23

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21270 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 24

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21271 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 25

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21272 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 920


PLC-AOUT 26

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21273 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 27

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21274 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 28

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21275 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 29

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21276 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 30

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21277 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 921


PLC-AOUT 31

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21278 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 32

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21279 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 33

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21280 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 34

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21281 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 35

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21282 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 922


PLC-AOUT 36

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21283 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 37

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21284 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 38

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21285 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 39

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21286 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 40

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21287 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 923


PLC-AOUT 41

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21288 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 42

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21289 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 43

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21290 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 44

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21291 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 45

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21292 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 924


PLC-AOUT 46

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21293 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 47

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21294 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 48

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21295 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 49

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21296 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 50

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21297 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 925


PLC-AOUT 51

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21298 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 52

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21299 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 53

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21300 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 54

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21301 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 55

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21302 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 926


PLC-AOUT 56

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21303 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 57

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21304 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 58

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21305 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 59

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21306 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 60

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21307 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 927


PLC-AOUT 61

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21308 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 62

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21309 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 63

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21310 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-AOUT 64

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21311 Related applications MINT, MPTM
Description
State of analog output of PLC.

6 back to List of values

PLC-BOUT 1

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10424 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 928


PLC-BOUT 2

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10425 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 3

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10426 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 4

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10427 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 5

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10428 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 6

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10429 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 929


PLC-BOUT 7

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10430 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 8

Value group PLC Related FW 1.5.0


Units [-]
Related
Comm object 10431 MINT, MPTM
applications
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 9

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10432 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 10

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10433 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 11

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10434 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 930


PLC-BOUT 12

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10435 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 13

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10436 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 14

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10437 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 15

Value group PLC Related FW 1.5.0


Units [-]
Comm object 10438 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 16

Value group PLC Related FW 1.5.0


Units [-]
Related
Comm object 10439 MINT, MPTM
applications
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 931


PLC-BOUT 17

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14570 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 18

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14571 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 19

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14572 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 20

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14573 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 21

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14574 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 932


PLC-BOUT 22

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14575 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 23

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14576 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 24

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14577 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 25

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14578 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 26

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14579 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 933


PLC-BOUT 27

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14580 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 28

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14581 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 29

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14582 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 30

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14583 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC-BOUT 31

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14584 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 934


PLC-BOUT 32

Value group PLC Related FW 1.5.0


Units [-]
Comm object 14585 Related applications MINT, MPTM
Description
State of binary outputs of PLC.

6 back to List of values

PLC Resource 1

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21216 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 2

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21217 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 3

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21218 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 4

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21219 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 935


PLC Resource 5

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21220 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 6

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21221 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 7

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21222 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 8

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21223 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 9

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21224 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 936


PLC Resource 10

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21225 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 11

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21226 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 12

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21227 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 13

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21228 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 14

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21229 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 937


PLC Resource 15

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21230 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

PLC Resource 16

Value group PLC Related FW 1.5.0


Units [-]
Comm object 21231 Related applications MINT, MPTM
Description
Internal value of PLC block.

6 back to List of values

Group: Remote Control

RemoteControl2B 1

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16671 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

RemoteControl2B 2

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16672 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 938


RemoteControl2B 3

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16673 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

RemoteControl2B 4

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16674 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

RemoteControl2B 5

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16675 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

RemoteControl2B 6

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16676 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 939


RemoteControl2B 7

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16677 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

RemoteControl2B 8

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16678 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int16.

6 back to List of values

RemoteControl4B 1

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16679 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int32.

6 back to List of values

RemoteControl4B 2

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16680 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int32.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 940


RemoteControl4B 3

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16681 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int32.

6 back to List of values

RemoteControl4B 4

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16682 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Int32.

6 back to List of values

RemoteControlBin

Value group Remote Control Related FW 1.5.0


Units -
Comm object 16683 Related applications MINT, MPTM
Description
This value contains user data written over Modbus-RTU, Modbus/TCP (page 316). Data type of this
value is Binary16.

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 941


Group: DIST-IN 1-32

Binary inputs 1 1-8

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 13301 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 1.
Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 1
2. DISTBIN-1 2
3. DISTBIN-1 3
4. DISTBIN-1 4
5. DISTBIN-1 5
6. DISTBIN-1 6
7. DISTBIN-1 7
8. DISTBIN-1 8

6 back to List of values

Binary inputs 1 9-16

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 20890 Related applications MINT, MPTM
Description
This value contains second 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module
1.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 9
2. DISTBIN-1 10
3. DISTBIN-1 11
4. DISTBIN-1 12
5. DISTBIN-1 13
6. DISTBIN-1 14
7. DISTBIN-1 15
8. DISTBIN-1 16

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 942


Binary inputs 1 17-24

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 16741 Related applications MINT, MPTM
Description
This value contains third 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 1.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 17
2. DISTBIN-1 18
3. DISTBIN-1 19
4. DISTBIN-1 20
5. DISTBIN-1 21
6. DISTBIN-1 22
7. DISTBIN-1 23
8. DISTBIN-1 24

6 back to List of values

Binary inputs 1 25-32

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 16805 Related applications MINT, MPTM
Description
This value contains fourth 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 1.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 1.
1. DISTBIN-1 25
2. DISTBIN-1 26
3. DISTBIN-1 27
4. DISTBIN-1 28
5. DISTBIN-1 29
6. DISTBIN-1 30
7. DISTBIN-1 31
8. DISTBIN-1 32

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 943


DISTAIN-1 1

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20955 Related applications MINT, MPTM
Description
This value contains data of first distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-1 2

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20956 Related applications MINT, MPTM
Description
This value contains data of second distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-1 3

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20957 Related applications MINT, MPTM
Description
This value contains data of third distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 944


DISTAIN-1 4

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20958 Related applications MINT, MPTM
Description
This value contains data of fourth distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

Binary inputs 2 1-8

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 13302 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 2.
Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 1
2. DISTBIN-2 2
3. DISTBIN-2 3
4. DISTBIN-2 4
5. DISTBIN-2 5
6. DISTBIN-2 6
7. DISTBIN-2 7
8. DISTBIN-2 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 945


Binary inputs 2 9-16

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 20891 Related applications MINT, MPTM
Description
This value contains second 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module
2.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 9
2. DISTBIN-2 10
3. DISTBIN-2 11
4. DISTBIN-2 12
5. DISTBIN-2 13
6. DISTBIN-2 14
7. DISTBIN-2 15
8. DISTBIN-2 16

6 back to List of values

Binary inputs 2 17-24

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 16742 Related applications MINT, MPTM
Description
This value contains third 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 2.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 17
2. DISTBIN-2 18
3. DISTBIN-2 19
4. DISTBIN-2 20
5. DISTBIN-2 21
6. DISTBIN-2 22
7. DISTBIN-2 23
8. DISTBIN-2 24

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 946


Binary inputs 2 25-32

Value group DIST-IN 1-32 Related FW 1.5.0


Units [-]
Comm object 16806 Related applications MINT, MPTM
Description
This value contains fourth 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 2.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 2.
1. DISTBIN-2 25
2. DISTBIN-2 26
3. DISTBIN-2 27
4. DISTBIN-2 28
5. DISTBIN-2 29
6. DISTBIN-2 30
7. DISTBIN-2 31
8. DISTBIN-2 32

6 back to List of values

DISTAIN-2 1

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20959 Related applications MINT, MPTM
Description
This value contains data of first distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 947


DISTAIN-2 2

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20960 Related applications MINT, MPTM
Description
This value contains data of second distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-2 3

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20961 Related applications MINT, MPTM
Description
This value contains data of third distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-2 4

Value group DIST-IN 1-32 Related FW 1.5.0


Units Based on configuration
Comm object 20962 Related applications MINT, MPTM
Description
This value contains data of fourth distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 948


Group: DIST-IN 33-64

Binary inputs 33 1-8

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 25858 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 33.
Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 1
2. DISTBIN-33 2
3. DISTBIN-33 3
4. DISTBIN-33 4
5. DISTBIN-33 5
6. DISTBIN-33 6
7. DISTBIN-33 7
8. DISTBIN-33 8

6 back to List of values

Binary inputs 33 9-16

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 20922 Related applications MINT, MPTM
Description
This value contains last 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 33.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 9
2. DISTBIN-33 10
3. DISTBIN-33 11
4. DISTBIN-33 12
5. DISTBIN-33 13
6. DISTBIN-33 14
7. DISTBIN-33 15
8. DISTBIN-33 16

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 949


Binary inputs 33 17-24

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 16773 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 33.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 17
2. DISTBIN-33 18
3. DISTBIN-33 19
4. DISTBIN-33 20
5. DISTBIN-33 21
6. DISTBIN-33 22
7. DISTBIN-33 23
8. DISTBIN-33 24

6 back to List of values

Binary inputs 33 25-32

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 16837 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 33.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 33.
1. DISTBIN-33 25
2. DISTBIN-33 26
3. DISTBIN-33 27
4. DISTBIN-33 28
5. DISTBIN-33 29
6. DISTBIN-33 30
7. DISTBIN-33 31
8. DISTBIN-33 32

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 950


DISTAIN-33 1

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21083 Related applications MINT, MPTM
Description
This value contains data of first distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 33.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-33 2

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21084 Related applications MINT, MPTM
Description
This value contains data of second distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 33.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-33 3

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21085 Related applications MINT, MPTM
Description
This value contains data of third distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 33.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 951


DISTAIN-33 4

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21086 Related applications MINT, MPTM
Description
This value contains data of fourth distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 33.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

Binary inputs 34 1-8

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 20859 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 34.
Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 1
2. DISTBIN-34 2
3. DISTBIN-34 3
4. DISTBIN-34 4
5. DISTBIN-34 5
6. DISTBIN-34 6
7. DISTBIN-34 7
8. DISTBIN-34 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 952


Binary inputs 34 9-16

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 20923 Related applications MINT, MPTM
Description
This value contains last 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 34.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 9
2. DISTBIN-34 10
3. DISTBIN-34 11
4. DISTBIN-34 12
5. DISTBIN-34 13
6. DISTBIN-34 14
7. DISTBIN-34 15
8. DISTBIN-34 16

6 back to List of values

Binary inputs 34 17-24

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 16774 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 34.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 17
2. DISTBIN-34 18
3. DISTBIN-34 19
4. DISTBIN-34 20
5. DISTBIN-34 21
6. DISTBIN-34 22
7. DISTBIN-34 23
8. DISTBIN-34 24

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 953


Binary inputs 34 25-32

Value group DIST-IN 33-64 Related FW 1.5.0


Units [-]
Comm object 16838 Related applications MINT, MPTM
Description
This value contains first 8 Binary Inputs of distributed binary inputs from DIST-IN (page 33) module 34.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

Received data are from Controller Unit with CAN Controller Address (page 392) = 34.
1. DISTBIN-34 25
2. DISTBIN-34 26
3. DISTBIN-34 27
4. DISTBIN-34 28
5. DISTBIN-34 29
6. DISTBIN-34 30
7. DISTBIN-34 31
8. DISTBIN-34 32

6 back to List of values

DISTAIN-34 1

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21087 Related applications MINT, MPTM
Description
This value contains data of first distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 34.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 954


DISTAIN-34 2

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21088 Related applications MINT, MPTM
Description
This value contains data of second distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 34.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-34 3

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21089 Related applications MINT, MPTM
Description
This value contains data of third distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 34.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

DISTAIN-34 4

Value group DIST-IN 33-64 Related FW 1.5.0


Units Based on configuration
Comm object 21090 Related applications MINT, MPTM
Description
This value contains data of fourth distributed analog input from DIST-IN (page 33) module which are
received from Controller Unit with CAN Controller Address (page 392) = 34.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 8C CAN FD!

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 955


Group: SH Modules

SHBIN-1

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10572 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary inputs from SHBIN module 1.
1. SHBIN-1 1
2. SHBIN-1 2
3. SHBIN-1 3
4. SHBIN-1 4
5. SHBIN-1 5
6. SHBIN-1 6
7. SHBIN-1 7
8. SHBIN-1 8

6 back to List of values

SHBIN-2

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10573 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary inputs from SHBIN module 2.
1. SHBIN-2 1
2. SHBIN-2 2
3. SHBIN-2 3
4. SHBIN-2 4
5. SHBIN-2 5
6. SHBIN-2 6
7. SHBIN-2 7
8. SHBIN-2 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 956


SHBIN-3

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10574 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary inputs from SHBIN module 3.
1. SHBIN-3 1
2. SHBIN-3 2
3. SHBIN-3 3
4. SHBIN-3 4
5. SHBIN-3 5
6. SHBIN-3 6
7. SHBIN-3 7
8. SHBIN-3 8

6 back to List of values

SHBIN-4

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10575 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary inputs from SHBIN module 4.
1. SHBIN-4 1
2. SHBIN-4 2
3. SHBIN-4 3
4. SHBIN-4 4
5. SHBIN-4 5
6. SHBIN-4 6
7. SHBIN-4 7
8. SHBIN-4 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 957


SHBIN-5

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11341 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary inputs from SHBIN module 5.
1. SHBIN-5 1
2. SHBIN-5 2
3. SHBIN-5 3
4. SHBIN-5 4
5. SHBIN-5 5
6. SHBIN-5 6
7. SHBIN-5 7
8. SHBIN-5 8

6 back to List of values

SHBIN-6

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11342 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary inputs from SHBIN module 6.
1. SHBIN-6 1
2. SHBIN-6 2
3. SHBIN-6 3
4. SHBIN-6 4
5. SHBIN-6 5
6. SHBIN-6 6
7. SHBIN-6 7
8. SHBIN-6 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 958


SHBOUT-1

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10576 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary outputs from SHBOUT module 1.
1. SHBOUT-1 1
2. SHBOUT-1 2
3. SHBOUT-1 3
4. SHBOUT-1 4
5. SHBOUT-1 5
6. SHBOUT-1 6
7. SHBOUT-1 7
8. SHBOUT-1 8

6 back to List of values

SHBOUT-2

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10577 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary outputs from SHBOUT module 2.
1. SHBOUT-2 1
2. SHBOUT-2 2
3. SHBOUT-2 3
4. SHBOUT-2 4
5. SHBOUT-2 5
6. SHBOUT-2 6
7. SHBOUT-2 7
8. SHBOUT-2 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 959


SHBOUT-3

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10578 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary outputs from SHBOUT module 3.
1. SHBOUT-3 1
2. SHBOUT-3 2
3. SHBOUT-3 3
4. SHBOUT-3 4
5. SHBOUT-3 5
6. SHBOUT-3 6
7. SHBOUT-3 7
8. SHBOUT-3 8

6 back to List of values

SHBOUT-4

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10579 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary outputs from SHBOUT module 4.
1. SHBOUT-4 1
2. SHBOUT-4 2
3. SHBOUT-4 3
4. SHBOUT-4 4
5. SHBOUT-4 5
6. SHBOUT-4 6
7. SHBOUT-4 7
8. SHBOUT-4 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 960


SHBOUT-5

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11343 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary outputs from SHBOUT module 5.
1. SHBOUT-5 1
2. SHBOUT-5 2
3. SHBOUT-5 3
4. SHBOUT-5 4
5. SHBOUT-5 5
6. SHBOUT-5 6
7. SHBOUT-5 7
8. SHBOUT-5 8

6 back to List of values

SHBOUT-6

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11344 Related applications MINT, MPTM
Description
This value contains Binary Inputs of shared binary outputs from SHBOUT module 6.
1. SHBOUT-6 1
2. SHBOUT-6 2
3. SHBOUT-6 3
4. SHBOUT-6 4
5. SHBOUT-6 5
6. SHBOUT-6 6
7. SHBOUT-6 7
8. SHBOUT-6 8

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 961


SHAIN-1 1

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10584 Related applications MINT, MPTM
Description
This value contains data of first shared analog input from SHAOUT module 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

SHAIN-1 2

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10585 Related applications MINT, MPTM
Description
This value contains data of second shared analog input from SHAOUT module 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

SHAIN-1 3

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10586 Related applications MINT, MPTM
Description
This value contains data of third shared analog input from SHAOUT module 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

SHAIN-1 4

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 10587 Related applications MINT, MPTM
Description
This value contains data of fourth shared analog input from SHAOUT module 1.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 962


SHAIN-2 1

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11390 Related applications MINT, MPTM
Description
This value contains data of first shared analog input from SHAOUT module 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

SHAIN-2 2

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11391 Related applications MINT, MPTM
Description
This value contains data of second shared analog input from SHAOUT module 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

SHAIN-2 3

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11392 Related applications MINT, MPTM
Description
This value contains data of third shared analog input from SHAOUT module 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

SHAIN-2 4

Value group SH Modules Related FW 1.5.0


Units [-]
Comm object 11393 Related applications MINT, MPTM
Description
This value contains data of fourth shared analog input from SHAOUT module 2.
IMPORTANT: This value is received (and visible) only when it is configured with sensor
type "Electronic".

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 963


Group: Virtual Shared OUT

Binary outputs 1-8

Value group Virtual Shared OUT Related FW 1.5.0


Units [-]
Comm object 13333 Related applications MINT, MPTM
Description
This value contains first 8 Binary Outputs of distributed binary outputs from DIST-OUT (page 34)
module.
1. DISTBOUT 1
2. DISTBOUT 2
3. DISTBOUT 3
4. DISTBOUT 4
5. DISTBOUT 5
6. DISTBOUT 6
7. DISTBOUT 7
8. DISTBOUT 8

6 back to List of values

Binary outputs 9-16

Value group Virtual Shared OUT Related FW 1.5.0


Units [-]
Comm object 20954 Related applications MINT, MPTM
Description
This value contains second 8 Binary Outputs of distributed binary outputs from DIST-OUT (page 34)
module.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

1. DISTBOUT 9
2. DISTBOUT 10
3. DISTBOUT 11
4. DISTBOUT 12
5. DISTBOUT 13
6. DISTBOUT 14
7. DISTBOUT 15
8. DISTBOUT 16

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 964


Binary outputs 17-24

Value group Virtual Shared OUT Related FW 1.5.0


Units [-]
Comm object 16870 Related applications MINT, MPTM
Description
This value contains third 8 Binary Outputs of distributed binary outputs from DIST-OUT (page 34)
module.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

1. DISTBOUT 17
2. DISTBOUT 18
3. DISTBOUT 19
4. DISTBOUT 20
5. DISTBOUT 21
6. DISTBOUT 22
7. DISTBOUT 23
8. DISTBOUT 24

6 back to List of values

Binary outputs 25-32

Value group Virtual Shared OUT Related FW 1.5.0


Units [-]
Comm object 16871 Related applications MINT, MPTM
Description
This value contains fourth 8 Binary Outputs of distributed binary outputs from DIST-OUT (page 34)
module.
IMPORTANT: This value is supported only when CAN Intercontroller Comm Mode (page
397) = 64C CAN FD or 32C CAN FD or 8C CAN FD!

1. DISTBOUT 25
2. DISTBOUT 26
3. DISTBOUT 27
4. DISTBOUT 28
5. DISTBOUT 29
6. DISTBOUT 30
7. DISTBOUT 31
8. DISTBOUT 32

6 back to List of values

InteliNeo 6000 1.5.0 Global Guide 965


9.1.5 Application Curves
List of Application Curves
Q(Um) 967
Qref/Ulim 968
Q(P) 969
PF(P) 970
P(Um) 971
P Mom/Pave Max 972
Capability L 973
Capability C 974
Power Over Frequency 975
Power Under Frequency 976
P For Q UQ L 977
P For Q UQ C 978
P For Q PQ L 979
P For Q PQ C 980
LVRT 3-phase 981
LVRT 2-phase 982
LVRT 1-phase 983
OVRT 984

6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 966


Q(Um)

Related FW 1.5.0 Related applications MPTM


App Curve ID 0
Description
This curve is used during Q(Um) (page 268)PF/Q control (page 262) power control.
X-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Y-axe is relative value of BESS Required Q (page 865) to Samax (page 374).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


60.00 33
96.00 33
100.00 0
104.00 -33
140.00 -33

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 967


Qref/Ulim

Related FW 1.5.0 Related applications MPTM


App Curve ID 1
Description
This curve is used during Qref/Ulim (page 270)PF/Q control (page 262) power control.
X-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381)
Y-axe is relative value of BESS Required Q (page 865) to Samax (page 374).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


60.00 33
94.00 33
96.00 0
100.00 0
104.00 -33
140.00 -33

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 968


Q(P)

Related FW 1.5.0 Related applications MPTM


App Curve ID 2
Description
This curve is used during Q(P) (page 269)PF/Q control (page 262) power control.
X-axe is relative value of BESS P (page 707) to Installed Power (page 375) (or Nominal power (page
375) in case Installed Power (page 375) = OFF).
Y-axe is relative value of BESS Required Q (page 865) to Samax (page 374).
Default values

X-axe [%] Y-axe [%]


-100.00 33
-90.00 33
-60.00 5
-50.00 0
-10.00 0
0.00 0
10.00 0
50.00 0
60.00 -5
90.00 -33
100.00 -33

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 969


PF(P)

Related FW 1.5.0 Related applications MPTM


App Curve ID 3
Description
This curve is used during PF(Pm) (page 267)PF/Q control (page 262) power control.
X-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381)
Y-axe is BESS Required PF (page 865) in combination with BESS Required PF Character (page
865).
Default values

X-axe [%] Y-axe [-]


-100.00 1.050
-80.00 1.050
-50.00 1.000
-20.00 0.950
0.00 0.950
20.00 0.950
50.00 1.000
80.00 1.050
100.00 1.050

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 970


P(Um)

Related FW 1.5.0 Related applications MPTM


App Curve ID 16
Description
This curve is used during Power Regulation Based On Actual Mains Voltage (page 302).
X-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Y-axe is relative value of BESS Required P Target (page 861) to Installed Power (page 375) or
Pmom (page 829) based on P(Um) (page 553).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


60.00 0
100.00 0
110.00 0
112.00 -100
120.00 -100

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 971


P Mom/Pave Max

Related FW 1.5.0 Related applications MPTM


App Curve ID 17
Description
This curve is used during Pave (page 309) function.
X-axe is time in seconds
Y-axe is value of LAI PMOM (PAGE 1125) related to setpoint Pave (page 569)
Default values

X-axe [s] Y-axe [-] X-axe [s] Y-axe [-]


0.00 1.670 2.00 1.125
0.80 1.670 2.40 1.125
0.90 1.603 2.80 1.082
1.00 1.543 3.20 1.054
1.10 1.489 3.60 1.035
1.20 1.440 4.00 1.023
1.30 1.396 4.40 1.015
1.40 1.357 4.80 1.010
1.50 1.321 5.20 1.007
1.60 1.289 5.60 1.004
1.70 1.260 6.00 1.002
1.80 1.234 7.00 1.001
2.00 1.190 10.00 1.000

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 972


Capability L

Related FW 1.5.0 Related applications MINT, MPTM


App Curve ID 4
Description
This curve defines BESS Operation Area (page 1) within which it can deliver reactive power
continuously without overheating while BESS Load Character (page 710) = L.
X-axe is relative value of BESS P (page 707) to Nominal power (page 375).
Y-axe is relative value of BESS Q (page 708) to Samax (page 374).
Note: The samax value is counted from Nominal Current (page 376) and BESS Nominal Voltage Ph-
N (page 380) (or BESS Nominal Voltage Ph-Ph (page 380)) in case that Samax (page 374) = OFF.
Default values

X-axe [%] Y-axe [%]


-10 0
0 0
100 106
102 106

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 973


Capability C

Related FW 1.5.0 Related applications MINT, MPTM


App Curve ID 5
Description
This curve defines BESS Operation Area (page 1) within which it can deliver reactive power
continuously without overheating while BESS Load Character (page 710) = C.
X-axe is relative value of BESS P (page 707) to Nominal power (page 375).
Y-axe is relative value of BESS Q (page 708) to Samax (page 374).
IMPORTANT: The Capability C curve have to be setup according to the Capability curve of
the worst (weakest) BESS in order to ensure right functionality of the whole system.

Note: The samax value is counted from Nominal Current (page 376) and BESS Nominal Voltage Ph-
N (page 380) (or BESS Nominal Voltage Ph-Ph (page 380)) in case that Samax (page 374) = OFF.
Default values

X-axe [%] Y-axe [%]


-10 0
0 0
100 -60
102 -60

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 974


Power Over Frequency

Related FW 1.5.0 Related applications MPTM


App Curve ID 6
Description
This curve is used duringPower reduction by over frequency - PoF (page 299).
X-axe is Δf = Mains/Bus Frequency (page 839) - Nominal Frequency (page 384).
Y-axe is relative value of BESS Required P (page 861) to Installed Power (page 375) (or Nominal
power (page 375) in case Installed Power (page 375) = OFF).
Note: Δf has to be higher than 0.
Default values

X-axe [Hz] Y-axe [%]


0.000 0.00
0.200 0.00
1.500 -52.00
2.700 -100.00

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 975


Power Under Frequency

Related FW 1.5.0 Related applications MPTM


App Curve ID 7
Description
This curve is used duringPower increase by under frequency - PuF (page 300).
X-axe is Δf = Mains/Bus Frequency (page 839) - Nominal Frequency (page 384).
Y-axe is relative value of BESS Required P (page 861) to Installed Power (page 375) (or Nominal
power (page 375) in case Installed Power (page 375) = OFF).
Note: Δf has to be lower than 0.
Default values

X-axe [Hz] Y-axe [%]


-2.700 100.00
-2.500 92.00
-0.200 0.00
0.000 0.00

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 976


P For Q UQ L

Related FW 1.5.0 Related applications MPTM


App Curve ID 8
Description
This curve is used to define UQ area where the BESS can operate during P For Q (page 306) while
BESS Load Character (page 710) = L.
X-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Y-axe is relative value of BESS Required Q (page 865) to Samax (page 374).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


0.00 00
90.00 00
90.00 33
107.50 33
110.00 0
200.00 0

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 977


P For Q UQ C

Related FW 1.5.0 Related applications MPTM


App Curve ID 9
Description
This curve is used to define UQ area where the BESS can operate during P For Q (page 306) while
BESS Load Character (page 710) = C.
X-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Y-axe is relative value of BESS Required Q (page 865) to Samax (page 374).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


0.00 00
90.00 00
92.50 -33
110.00 -33
110.00 0
200.00 0

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 978


P For Q PQ L

Related FW 1.5.0 Related applications MPTM


App Curve ID 10
Description
This curve is used to define PQ area where the BESS can operate during P For Q (page 306) while
BESS Load Character (page 710) = L.
X-axe is relative value of BESS P (page 707) to Installed Power (page 375) (or Nominal power (page
375) in case Installed Power (page 375) = OFF).
Y-axe is relative value of BESS Q (page 708) to Installed Power (page 375).(or Nominal power (page
375) in case Installed Power (page 375) = OFF).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


0.00 0
9.00 2
10.00 2
10.00 10
20.00 33
100.00 33

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 979


P For Q PQ C

Related FW 1.5.0 Related applications MPTM


App Curve ID 11
Description
This curve is used to define PQ area where the BESS can operate during P For Q (page 306) while
BESS Load Character (page 710) = C.
X-axe is relative value of BESS P (page 707) to Installed Power (page 375) (or Nominal power (page
375) in case Installed Power (page 375) = OFF).
Y-axe is relative value of BESS Q (page 708) to Installed Power (page 375).(or Nominal power (page
375) in case Installed Power (page 375) = OFF).
Note: Umains is average value of Mains/Bus Voltage L1-N (page 839), Mains/Bus Voltage L2-N
(page 839) and Mains/Bus Voltage L3-N (page 840).
Default values

X-axe [%] Y-axe [%]


0.00 0
9.00 -5
10.00 -5
10.00 -10
20.00 -33
100.00 -33

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 980


LVRT 3-phase

Related FW 1.5.0 Related applications MPTM


App Curve ID 12
Description
This curve is used during Dynamic Support - VRT (page 304). All of Mains/Bus Voltage L1-N (page
839), Mains/Bus Voltage L2-N (page 839) and Mains/Bus Voltage L3-N (page 840) has to be under
Mains/Bus Nominal Voltage Ph-N (page 381) to activate LVRT.
X-axe is time for which values have to be over the limit.
Y-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Default values

X-axe [s] Y-axe [%]


0.00 30.0
0.15 30.0
0.70 70.0
1.50 70.0
60.00 85.0
60.00 90.0
61.00 90.0

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 981


LVRT 2-phase

Related FW 1.5.0 Related applications MPTM


App Curve ID 13
Description
This curve is used during Dynamic Support - VRT (page 304). At least 2 of Mains/Bus Voltage L1-N
(page 839), Mains/Bus Voltage L2-N (page 839) and Mains/Bus Voltage L3-N (page 840) has to be
under Mains/Bus Nominal Voltage Ph-N (page 381) to activate LVRT.
X-axe is time for which values have to be over the limit.
Y-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Default values

X-axe [s] Y-axe [%]


0.00 30.0
0.22 30.0
0.22 60.0
0.70 60.0
1.50 75.0
3.00 75.0
3.00 85.0
60.00 85.0
60.00 90.0
61.00 90.0

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 982


LVRT 1-phase

Related FW 1.5.0 Related applications MPTM


App Curve ID 14
Description
This curve is used during Dynamic Support - VRT (page 304). At least 1 of Mains/Bus Voltage L1-N
(page 839), Mains/Bus Voltage L2-N (page 839) and Mains/Bus Voltage L3-N (page 840) has to be
under Mains/Bus Nominal Voltage Ph-N (page 381) to activate LVRT.
X-axe is time for which values have to be over the limit.
Y-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Default values

X-axe [s] Y-axe [%]


0.00 30.0
0.15 30.0
0.15 70.0
0.70 70.0
1.50 85.0
60.00 85.0
60.00 90.0
61.00 90.0

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 983


OVRT

Related FW 1.5.0 Related applications MPTM


App Curve ID 15
Description
This curve is used during Dynamic Support - VRT (page 304). At least 1 of Mains/Bus Voltage L1-N
(page 839), Mains/Bus Voltage L2-N (page 839) and Mains/Bus Voltage L3-N (page 840) has to be
over Mains/Bus Nominal Voltage Ph-N (page 381) to activate LVRT.
X-axe is time for which values have to be over the limit.
Y-axe is relative value of Umains to Mains/Bus Nominal Voltage Ph-N (page 381).
Default values

X-axe [s] Y-axe [%]


0.00 125.0
0.10 125.0
0.10 120.0
5.00 120.0
5.00 115.0
60.00 115.0
60.00 110.0
61.00 110.0

Default appearance

6 back to Application Curves

InteliNeo 6000 1.5.0 Global Guide 984


9.1.6 Logical binary inputs
What Logical binary inputs are:
Logical binary inputs are inputs for binary values and functions.

Alphabetical groups of Logical binary inputs


LBI: A 989
LBI: B 989
LBI: C 995
LBI: E 996
LBI: F 996
LBI: G 1004
LBI: H 1005
LBI: I 1006
LBI: L 1006
LBI: M 1010
LBI: N 1015
LBI: P 1015
LBI: R 1026
LBI: S 1027
LBI: T 1029
LBI: U 1030
LBI: W 1046

For full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically (page 986).

InteliNeo 6000 1.5.0 Global Guide 985


Logical binary inputs alphabetically

LBI: A 989 Forced Value Input 11 999 Load Reduction 1 1006


Application MINT 989 Forced Value Input 12 999 Load Reduction 2 1006
Application MPTM 989 Forced Value Input 13 999 Load Reduction 3 1007
LBI: B 989 Forced Value Input 14 1000 Load Reduction 4 1007
BATT Discharge Enable 989 Forced Value Input 15 1000 Load Reduction Enable 1007
BATT Charge Enable 989 Forced Value Input 16 1000 Load Res 2 Active 1008
BCB Button 990 Forced Value Input 17 1000 Load Res 3 Active 1009
BCB Disable 990 Forced Value Input 18 1000 Load Res 4 Active 1010
BCB Feedback 991 Forced Value Input 19 1001 LBI: M 1010
BCB Feedback Negative 992 Forced Value Input 20 1001 Mains Fail Block 1010
BCB Secondary Feedback Forced Value Input 21 1001 Manual Load
Negative 993 Reconnection 1011
Forced Value Input 22 1001
BCB Secondary Feedback 994 MCB Button 1011
Forced Value Input 23 1001
BESS Output Control MCB Disable 1011
Forced Value Input 24 1002
Mode U-f/P-Q 994 MCB Feedback 1012
Forced Value Input 25 1002
BESS Ready To Load 995 MCB Feedback Negative 1013
Forced Value Input 26 1002
BESS Remote Start/Stop 995 Min Run Power Act 1 1014
Forced Value Input 27 1002
LBI: C 995 Min Run Power Act 2 1014
Forced Value Input 28 1002
Universal Hours Counter 1 995
Forced Value Input 29 1003 Min Run Power Act 3 1015
Universal Hours Counter 2 995
Forced Value Input 30 1003 LBI: N 1015
LBI: E 996 NCB Feedback 1015
Forced Value Input 31 1003
ECU Key Switch 996
LBI: P 1015
Forced Value Input 32 1003
Emergency MAN 996 Post VRT 1015
LBI: G 1004
Emergency Stop 996 Precharge Finished 1016
Generic Genset
LBI: F 996 Protection Force Disable
Start/Stop 1004
Fault Reset Button 996 1 1016
Group link 1004
Force Island 997 Protection Force Disable
Geo Home Position 1004
Force Parallel 997 2 1017
Geo-Fencing Enable 1004
Forced Value Input 01 997 Protection Force Disable
LBI: H 1005
Forced Value Input 02 997 3 1017
Horn Reset Button 1005
Forced Value Input 03 997 Pulse Counter 1 1018
Hot Swap Ctrl Block 1005
Forced Value Input 04 998 Pulse Counter 2 1018
Hot Swap Heartbeat
Forced Value Input 05 998 PV 01 Operable 1018
Detect 1005
Forced Value Input 06 998 PV 02 Operable 1018
Hot Swap Recovery 1006
Forced Value Input 07 998 PV 03 Operable 1018
LBI: I 1006
Forced Value Input 08 998 PV 04 Operable 1019
Inverter Start Disabled 1006
Forced Value Input 09 999 PV 05 Operable 1019
LBI: L 1006
Forced Value Input 10 999 PV 06 Operable 1019

InteliNeo 6000 1.5.0 Global Guide 986


PV 07 Operable 1019 Start Button 1028 Uni Gen 08 Loaded 1037
PV 08 Operable 1019 Stop Button 1029 Uni Gen 08 Ready 1038
PV 09 Operable 1020 Sunrise/Sunset Home Uni Gen 09 GCB Closed 1038
PV 10 Operable 1020 Position 1029 Uni Gen 09 GCB Closing 1038
PV 11 Operable 1020 Synchronization Disabled1029 Uni Gen 09 Loaded 1038
PV 12 Operable 1020 LBI: T 1029 Uni Gen 09 Ready 1039
PV 13 Operable 1020 TEST ROCOF 1029 Uni Gen 10 GCB Closed 1039
PV 14 Operable 1021 Test Vector Shift 1029 Uni Gen 10 GCB Closing 1039
PV 15 Operable 1021 Top Priority 1030 Uni Gen 10 Loaded 1039
PV 16 Operable 1021 LBI: U 1030 Uni Gen 10 Ready 1040
Uni Gen 01 GCB Closed 1030
PV 17 Operable 1021 Uni Gen 11 GCB Closed 1040
Uni Gen 01 GCB Closing 1030
PV 18 Operable 1021 Uni Gen 11 GCB Closing 1040
Uni Gen 01 Loaded 1030
PV 19 Operable 1022 Uni Gen 11 Loaded 1040
Uni Gen 01 Ready 1031
PV 20 Operable 1022 Uni Gen 11 Ready 1041
Uni Gen 02 GCB Closed 1031
PV 21 Operable 1022 Uni Gen 12 GCB Closed 1041
Uni Gen 02 GCB Closing 1031
PV 22 Operable 1022 Uni Gen 12 GCB Closing 1041
Uni Gen 02 Loaded 1031
PV 23 Operable 1022 Uni Gen 12 Loaded 1041
Uni Gen 02 Ready 1032
PV 24 Operable 1023 Uni Gen 12 Ready 1042
Uni Gen 03 GCB Closed 1032
PV 25 Operable 1023 Uni Gen 13 GCB Closed 1042
Uni Gen 03 GCB Closing 1032
PV 26 Operable 1023 Uni Gen 13 GCB Closing 1042
Uni Gen 03 Loaded 1032
PV 27 Operable 1023 Uni Gen 13 Loaded 1042
Uni Gen 03 Ready 1033
PV 28 Operable 1023 Uni Gen 13 Ready 1043
Uni Gen 04 GCB Closed 1033
PV 29 Operable 1024 Uni Gen 14 GCB Closed 1043
Uni Gen 04 GCB Closing 1033
PV 30 Operable 1024 Uni Gen 14 GCB Closing 1043
Uni Gen 04 Loaded 1033
PV 31 Operable 1024 Uni Gen 14 Loaded 1043
Uni Gen 04 Ready 1034
PV 32 Operable 1024 Uni Gen 14 Ready 1044
Uni Gen 05 GCB Closed 1034
PVCB Button 1024 Uni Gen 15 GCB Closed 1044
Uni Gen 05 GCB Closing 1034
PVCB Disable 1025 Uni Gen 15 GCB Closing 1044
Uni Gen 05 Loaded 1034
PVCB Feedback 1025 Uni Gen 15 Loaded 1044
Uni Gen 05 Ready 1035
PVCB Feedback Uni Gen 15 Ready 1045
Negative 1026 Uni Gen 06 GCB Closed 1035
Uni Gen 16 GCB Closed 1045
LBI: R 1026 Uni Gen 06 GCB Closing 1035
Uni Gen 16 GCB Closing 1045
Remote AUTO 1026 Uni Gen 06 Loaded 1035
Uni Gen 16 Loaded 1045
Remote MAN 1027 Uni Gen 06 Ready 1036
Uni Gen 16 Ready 1046
Remote OFF 1027 Uni Gen 07 GCB Closed 1036
LBI: W 1046
LBI: S 1027 Uni Gen 07 GCB Closing 1036 WT 01 Operable 1046
Sd Override 1027 Uni Gen 07 Loaded 1036 WT 02 Operable 1046
Soft Bus Energize 1028 Uni Gen 07 Ready 1037 WT 03 Operable 1046
Soft Unload Enable 1028 Uni Gen 08 GCB Closed 1037 WT 04 Operable 1046
Start Blocking 1028 Uni Gen 08 GCB Closing 1037

InteliNeo 6000 1.5.0 Global Guide 987


WT 05 Operable 1047
WT 06 Operable 1047
WT 07 Operable 1047
WT 08 Operable 1047
6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 988


LBI: A

Application MINT

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1007
Description
Activation of this binary input switches the controller Application Mode (page 885) to MINT.
IMPORTANT: The Controller Mode (page 885) has to be OFF, otherwise controller application
can not be changed.

Note: This binary input has lower priority than LBI APPLICATION MPTM (PAGE 989).

6 back to Logical binary inputs alphabetically

Application MPTM

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1006
Description
Activation of this binary input switches the controller Application Mode (page 885) to MPTM.
IMPORTANT: The Controller Mode (page 885) has to be OFF, otherwise controller application
can not be changed.

Note: This binary input has higher priority than LBI APPLICATION MINT (PAGE 989).

6 back to Logical binary inputs alphabetically

LBI: B

BATT Discharge Enable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1106
Description
This logical input enables discharging process of the battery.

6 back to Logical binary inputs alphabetically

BATT Charge Enable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1105
Description
This logical input enables charging process of the battery.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 989


BCB Button

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 193
Description

Binary input has the same function as BCB button on an External display (page 79)Internal display.

6 back to Logical binary inputs alphabetically

BCB Disable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 62
Description
This function is used to prevent BCB closing and opening.
If the input is active during synchronizing, the controller will continue synchronizing without
issuing the BCB closing command until the input is deactivated or Sync timeout is elapsed.
If the input is active and the BCB button is pressed in MAN mode to close the BCB to dead bus,
the BCB will not be closed until the input is deactivated and the BCB button pressed again.
If the input is active and the BCB should be closed to dead bus automatically, the BCB will not be
closed until the input is deactivated.
If the input is active and the BCB is already closed, the breaker will not open automatically. BCB
can be opened with BCB Button (or the corresponding command).

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 990


BCB Feedback

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 63
Description
Use this input to indicate whether the BESS circuit breaker is opened or closed.

Image 7.7 BCB Feedback 1

Image 7.8 BCB Feedback 2

This input is used for connection of the normally open feedback contact from the generator circuit
breaker or contactor. If the input is active, the controller will consider the BCB as closed and vice versa.
If the feedback does not respond to a change of the control output LBO BCB CLOSE/OPEN (PAGE
1055) within time adjusted in Setpoint Waiting For Breaker Feedback (page 1), and it was
already last attempt the specific alarm based on current breaker position is issued.
If the feedback changes it's position unexpectedly without any command given by the control
output, the Alarm Stp BCB Fail (page 1290) will be issued immediately.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 991


BCB Feedback Negative

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 64
Description
Use this input to indicate whether the BESS circuit breaker is opened or closed.
This input is used for connection of the normally closed feedback contact from the generator circuit
breaker or contactor. This input is optional and if it is configured, it must be always in inverse position to
the normally open input LBI BCB FEEDBACK (PAGE 991). Maximal allowed time the both inputs are in the
same position is 500ms, after this time the Alarm Stp BCB Fail (page 1290) is issued.

Image 7.9 BCB Feedback Negative 1

Image 7.10 BCB Feedback Negative 2

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 992


BCB Secondary Feedback Negative

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 982
Description
Use this input to indicate whether the BESS circuit breaker is opened or closed.
This input is logically inverted against LBI BCB SECONDARY FEEDBACK (PAGE 994).

Image 7.11 BCB Feedback Secondary Negative 1

Image 7.12 BCB Feedback Secondary Negative 2

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 993


BCB Secondary Feedback

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 548
Description
Use this input to indicate whether the BESS circuit breaker is opened or closed.

Image 7.13 BCB Feedback 1

Image 7.14 BCB Feedback 2

6 back to Logical binary inputs alphabetically

BESS Output Control Mode U-f/P-Q

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1109
Description
This logical input is used to choose what BESS Output Control (page 244) method will be used. By
default (log 0) the U-f option is used.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 994


BESS Ready To Load

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 121
Description
Activation of this LBI signalizes that BESS is ready to be loaded. Once this LBI gets active and the BESS
finished the stabilization phase, BESS state (page 886) goes to Running.
If this LBI is configured and it is not activated before BESSReady to Load TO (page 435)
elapsed the alarm Sd Start Fail (page 1289) is activated.
If this LBI is not configured the BCB is closed after BESSReady to Load TO (page 435)
elapsed.
Note: BCB can be closed only when this LBI is active and has to be configured.

Note: There is no BCB control limitation when BCB Control Mode (page 369) = External.

6 back to Logical binary inputs alphabetically

BESS Remote Start/Stop

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1396
Description
This LBI is accepted in AUT mode and it makes the BESS running and connected to the bus
unconditionally in relation to power management.

6 back to Logical binary inputs alphabetically

LBI: C

Universal Hours Counter 1

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1094
Description
This binary input is used as customer condition for the value Conditioned Running Hours 1 (page
880).

6 back to Logical binary inputs alphabetically

Universal Hours Counter 2

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1095
Description
This binary input is used as customer condition for the value Conditioned Running Hours 2 (page
880).

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 995


LBI: E

ECU Key Switch

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 951
Description
Activation of this binary input activates LBO ECU POWER RELAY (PAGE 1074) without starting of the
BESS. This can be used for reading electronic control unit values when BESS does not run.

6 back to Logical binary inputs alphabetically

Emergency MAN

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 45
Description
This input is designed to allow the BESS and breakers to be controlled externally (not by the controller).
This feature can be useful in case of some failure, which disables the BESS and breakers to be
controlled by the controller, but the BESS itself is operational.
The controller behaves in the following way:
Stops all functions regarding the BESS andbreaker control, deactivates all outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not activated if nonzero speed is
detected.
When the input is deactivated, the controller takes control according to the situation in the
moment of deactivation, i.e. the BESS remains running loaded if it was running and BCB was
closed in the moment the input was deactivated.

6 back to Logical binary inputs alphabetically

Emergency Stop

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 40
Description
When this binary input is activated, BESS is immediately stopped, binary outputs are disconnected and
alarm Emergency Stop (page 1280) is activated.

6 back to Logical binary inputs alphabetically

LBI: F

Fault Reset Button

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 191
Description

Binary input has the same function as Fault Reset button on an External display (page 79)Internal
display.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 996


Force Island

Related FW 1.5.0 Related applications , MPTM


LBI ID 787
Description
Activation of this LBI starts the BESS and forces island operation. Transfer method of the load from
Mains is adjusted via setpoint Transfer Mains To BESS (page 474).

6 back to Logical binary inputs alphabetically

Force Parallel

Related FW 1.5.0 Related applications , MPTM


LBI ID 786
Description
Activation of this LBI starts the BESS and forces parallel operation if MAINS/BUS HEALTHY (PAGE 1090) is
closed. Island operation is not allowed while this LBI is closed.

6 back to Logical binary inputs alphabetically

Forced Value Input 01

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 19
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 02

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 20
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 03

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 21
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 997


Forced Value Input 04

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 22
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 05

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 23
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 06

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 24
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 07

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 25
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 08

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 26
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 998


Forced Value Input 09

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 27
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 10

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 28
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 11

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 29
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 12

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 30
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 13

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 31
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 999


Forced Value Input 14

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 32
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 15

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 33
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 16

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 34
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 17

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 839
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 18

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 840
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1000


Forced Value Input 19

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 841
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 20

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 842
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 21

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 843
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 22

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 844
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 23

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 845
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1001


Forced Value Input 24

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 846
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 25

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 847
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 26

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 848
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 27

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 849
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 28

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 850
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1002


Forced Value Input 29

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 851
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 30

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 852
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 31

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 853
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

Forced Value Input 32

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 854
Description
This LBI is used for activation of preconfigured Forced Value (page 158) to setpoint.
Note: This LBI can be renamed during configuration.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1003


LBI: G

Generic Genset Start/Stop

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 38
Description
Use this input to start and stop the BESS in AUTO mode. This information is shared to all controllers in
the same group connected to the master controller via CAN.
The LBI Generic Genset Start/Stop is accepted in the MAN or in the AUT mode and is distributed to
all channels as Uni Gen 1..16 Run Request value. The Run Request is conditioned by the Power
management function. If this signal is not used in configuration, the internal command shared via
intercontroller line is taken in account (e.g. System Start/Stop issued by InteliMains).

6 back to Logical binary inputs alphabetically

Group link

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 59
Description
This input is used for logical connection and disconnection of two BESS groups selected with setpoints
Group Link L (page 517) and Group Link R (page 517). If the input is active, then the two selected
groups will perform Power Management (page 274), load sharing and Var sharing together as one
large group.
Note: This function is independent on the group which the particular controller belongs to, i.e. the
controller can provide linking function e.g. for groups 3,4 although it belongs to group 2.

6 back to Logical binary inputs alphabetically

Geo Home Position

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 219
Description
This binary input can be used to adjust home position of BESS. In case that binary input is active,
setpoints Home Latitude (page 663) and Home Longitude (page 663) are adjusted automatically from
actual coordinates from GPS signal.
Note: Input has to be activated for at least 2 seconds.

6 back to Logical binary inputs alphabetically

Geo-Fencing Enable

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 218
Description
This binary input enables or disables Fence 1 Protection (page 664) and Fence 2 Protection (page
665) if Geo-Fencing (page 662) is adjusted to value "LBI Enable".

InteliNeo 6000 1.5.0 Global Guide 1004


6 back to Logical binary inputs alphabetically

LBI: H

Horn Reset Button

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 192
Description

Binary input has the same function as Horn reset button on an External display (page 79)Internal
display.

6 back to Logical binary inputs alphabetically

Hot Swap Ctrl Block

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1047
Description
This LBI is used to detect if this controller is considered to be dead by the second Hot Swap
Redundancy (page 160) controller.
If the LBI is activated this controller is considered to be dead and it is forced to the listening mode. The
controller in listening mode does not send any messages to other controllers but only reads what is being
transmitted. This LBI has to be physically wired to the LBO HOT SWAP SWITCH (PAGE 1083) of the second
Hot Swap Redundancy (page 160) controller.
Note: If both Master and Backup controllers are alive, the Master is in control and the Backup is
automatically in the listening mode. This LBI is used only to force the listening mode on controller
which is considered to be dead by the second controller.

IMPORTANT: This input has to be configured to physical input of the controller.

IMPORTANT: This input has to be configured on both Master and Backup controllers.

6 back to Logical binary inputs alphabetically

Hot Swap Heartbeat Detect

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1037
Description
This LBI is used for detection that the second Hot Swap Redundancy (page 160) is alive.
This LBI has to be physically wired to the LBO HOT SWAP HEARTBEAT (PAGE 1083) of the second Hot
Swap Redundancy (page 160) controller. If the Heartbeat signal is not received, this controller
activates LBO Hot Swap Switch (page 1083).
IMPORTANT: This input has to be configured to physical input of the controller.

IMPORTANT: This input has to be configured on both Master and Backup controllers.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1005


Hot Swap Recovery

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1048
Description
This binary input is used to recover the Hot Swap Redundancy (page 160) system in case of Wrn
Master Controller Failed (page 1254) or Wrn Backup Controller Failed (page 1249) alarm is present
in the Alarm list.
Note: If warnings remains after the recovery, the wiring and configuration should be checked.

6 back to Logical binary inputs alphabetically

LBI: I

Inverter Start Disabled

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1185
Description
This LBI can be used to keep the BESS in idle operation.

6 back to Logical binary inputs alphabetically

LBI: L

Load Reduction 1

Related FW 1.5.0 Related applications MPTM


LBI ID 544
Description
This LBI activates Load Reduction (page 303) if setpoint Load Reduction (page 549) = Enabled and
LBI LOAD REDUCTION ENABLE (PAGE 1007) is closed. Load/power of the BESS is limited by the setpoint
Load Reduction 1 (page 549).
Note: If more than 1 Load Reduction LBIs are closed, Load Reduction with smallest value in setpoint is
chosen.

6 back to Logical binary inputs alphabetically

Load Reduction 2

Related FW 1.5.0 Related applications MPTM


LBI ID 545
Description
This LBI activates Load Reduction (page 303) if setpoint Load Reduction (page 549) = Enabled and
LBI LOAD REDUCTION ENABLE (PAGE 1007) is closed. Load/power of the BESS is limited by the setpoint
Load Reduction 2 (page 550).
Note: If more than 1 Load Reduction LBIs are closed, Load Reduction with smallest value in setpoint is
chosen.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1006


Load Reduction 3

Related FW 1.5.0 Related applications MPTM


LBI ID 546
Description
This LBI activates Load Reduction (page 303) if setpoint Load Reduction (page 549) = Enabled and
LBI LOAD REDUCTION ENABLE (PAGE 1007) is closed. Load/power of the BESS is limited by the setpoint
Load Reduction 3 (page 550).
Note: If more than 1 Load Reduction LBIs are closed, Load Reduction with smallest value in setpoint is
chosen.

6 back to Logical binary inputs alphabetically

Load Reduction 4

Related FW 1.5.0 Related applications MPTM


LBI ID 547
Description
This LBI activates Load Reduction (page 303) if setpoint Load Reduction (page 549) = Enabled and
LBI LOAD REDUCTION ENABLE (PAGE 1007) is closed. Load/power of the BESS is limited by the setpoint
Load Reduction 4 (page 551).
Note: If more than 1 Load Reduction LBIs are closed, Load Reduction with smallest value in setpoint is
chosen.

6 back to Logical binary inputs alphabetically

Load Reduction Enable

Related FW 1.5.0 Related applications MPTM


LBI ID 615
Description
This LBI enables Load Reduction (page 303) while it is closed.
Note: Setpoint Load Reduction (page 549) has to be Enabled, otherwise this LBI has no effect.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1007


Load Res 2 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 49
Description
This input is used to activate the load reserve set #2 (learn more about load reserve in the chapter Power
Management (page 274)) instead of the set #1, which is active by default. The set #2 is adjusted by
setpoints:
#Starting Load Reserve 2 (page 500) and #Stopping Load Reserve 2 (page 501) if the power
management is switched to absolute mode
#Starting Rel Load Reserve 2 (page 502) and #Stopping Rel Load Reserve 2 (page 502) if
the power management is switched to relative mode.
IMPORTANT: All controllers cooperating together in Power management must have the same
load reserve set selected.

Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1008


Load Res 3 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 50
Description
This input is used to activate the load reserve set #3 (learn more about load reserve in the chapter Power
Management (page 274)) instead of the set #1, which is active by default. The set #3 is adjusted by
setpoints:
#Starting Load Reserve 3 (page 503) and #Stopping Load Reserve 3 (page 504) if the power
management is switched to absolute mode
#Starting Rel Load Reserve 3 (page 505) and #Stopping Rel Load Reserve 3 (page 505) if
the power management is switched to relative mode.
IMPORTANT: All controllers cooperating together in Power management must have the same
load reserve set selected.

Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1009


Load Res 4 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 51
Description
This input is used to activate the load reserve set #4 (learn more about load reserve in the chapter Power
Management (page 274)) instead of the set #1, which is active by default. The set #4 is adjusted by
setpoints:
#Starting Load Reserve 4 (page 506) and #Stopping Load Reserve 4 (page 507) if the power
management is switched to absolute mode
#Starting Rel Load Reserve 4 (page 508) and #Stopping Rel Load Reserve 4 (page 508) if
the power management is switched to relative mode.
IMPORTANT: All controllers cooperating together in Power management must have the same
load reserve set selected.

Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus.

6 back to Logical binary inputs alphabetically

LBI: M

Mains Fail Block

Related FW 1.5.0 Related applications MPTM


LBI ID 622
Description
This logical input simulates healthy Mains even if the Mains parameters are not OK.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1010


Manual Load Reconnection

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 60
Description
This input is used for manual reconnection of the last disconnected part of the load, if the load has
dropped below the setpoint Power Load Reconnection Level (page 604). This works only if automatic
reconnection is disabled, i.e. the setpoint Auto Load Reconnection (page 602) = Disabled.

6 back to Logical binary inputs alphabetically

MCB Button

Related FW 1.5.0 Related applications MPTM


LBI ID 194
Description

This binary input has the same function as MCB button on an External display (page 79)Internal
display.

6 back to Logical binary inputs alphabetically

MCB Disable

Related FW 1.5.0 Related applications MPTM


LBI ID 124
Description
This binary input is used to prevent MCB closing and opening.
If the input is active during synchronizing, the controller will continue synchronizing without
issuing the MCB closing command until the input is deactivated or Sync timeout is elapsed.
If the input is active and the MCB Button is pressed in MAN mode to close the MCB to dead bus,
the MCB will not be closed until this input is deactivated and the MCB Button is pressed again.
If the input is active and the MCB is to be closed to dead bus automatically, the MCB will not be
closed until this input is deactivated.
If the input is active and MCB is already closed, the breaker will not open.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1011


MCB Feedback

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 65
Description
Use this input to indicate whether the Mainsmains circuit breaker is opened or closed.

Image 7.15 MCB Feedback 1

Image 7.16 MCB Feedback 2

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1012


MCB Feedback Negative

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 66
Description
Use this input to indicate whether the Mainsmains circuit breaker is opened or closed.
This input is logically inverted against LBI MCB FEEDBACK (PAGE 1012).

Image 7.17 MCB Feedback 1

Image 7.18 MCB Feedback 2

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1013


Min Run Power Act 1

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 52
Description
This input is used to activate the function Minimal running power #1, which is adjusted by setpoint #Min
Run Power (page 509).
Note: The default value of minimal running power, which takes place while none of the inputs Min Run
Power x Act, is 0 kW.

Note: If more then one binary input for Min Run Power is activated, the one with the higher index has
higher priority and it is used.

IMPORTANT: All controllers cooperating together in Power management must have the same
minimal running power selected.

Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus. See the diagram of such
distribution in the description of the input LOAD RES 2 ACTIVE (PAGE 1008).

6 back to Logical binary inputs alphabetically

Min Run Power Act 2

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 53
Description
This input is used to activate the function Minimal running power #2, which is adjusted by setpoint #Min
Run Power 2 (page 509).
Note: The default value of minimal running power, which takes place while none of the inputs Min Run
Power x Act, is 0 kW.

Note: If more then one binary input for Min Run Power is activated, the one with the higher index has
higher priority and it is used.

IMPORTANT: All controllers cooperating together in Power management must have the same
minimal running power selected.

Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus. See the diagram of such
distribution in the description of the input LOAD RES 2 ACTIVE (PAGE 1008).

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1014


Min Run Power Act 3

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 54
Description
This input is used to activate the function Minimal running power #3, which is adjusted by setpoint #Min
Run Power 3 (page 510).
Note: The default value of minimal running power, which takes place while none of the inputs Min Run
Power x Act, is 0 kW.

Note: If more then one binary input for Min Run Power is activated, the one with the higher index has
higher priority and it is used.

IMPORTANT: All controllers cooperating together in Power management must have the same
minimal running power selected.

Note: It is possible to use virtual peripheries for distribution of the binary signal from one physical switch
connected to one controller to all other controllers over the CAN bus. See the diagram of such
distribution in the description of the input LOAD RES 2 ACTIVE (PAGE 1008).

6 back to Logical binary inputs alphabetically

LBI: N

NCB Feedback

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 67
Description
This input is used for connection of feedback contact from the neutral contactor. If the input is active, the
controller will consider the neutral contactor as closed and vice versa. See also the setpoint #Neutral
Contactor Control (page 362) which is used for selecting of the NCB mode (Each / Common).

6 back to Logical binary inputs alphabetically

LBI: P

Post VRT

Related FW 1.5.0 Related applications MPTM


LBI ID 955
Description
Activation of this LBI activates Post VRT (page 306) if at least one of BESS Current L1 (page 715),
BESS Current L2 (page 715) or BESS Current L3 (page 715) is over Nominal Current (page 376).
Note: This is the only way to activate Post VRT function in MINT application, signal shall be sent from
the IM controller.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1015


Precharge Finished

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1171
Description
This signal is to be used as a confirmation, that the DC circuit inside the BESS is closed (the battery is
connected to the DC circuit of the inverter).
It is actually the feedback of the DC relay situated between the battery and the inverter. State of this relay
can be monitored using the LBO DC Circuit closed which just simply mirror the information about the DC
circuit state.
This LBI relates to the BESS start sequence decribed in BESS Precharge Types (page 245).

6 back to Logical binary inputs alphabetically

Protection Force Disable 1

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 16
Description
Activation of this LBI disables selected protections.
Proper history record is written to the history log.
Protection Force Disable 1 active
Protection Force Disable 1 inactive

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1016


Protection Force Disable 2

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 17
Description
Activation of this LBI disables selected protections.
Proper history record is written to the history log.
Protection Force Disable 2 active
Protection Force Disable 2 inactive

6 back to Logical binary inputs alphabetically

Protection Force Disable 3

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 18
Description
Activation of this LBI disables selected protections.
Proper history record is written to the history log.
Protection Force Disable 3 active
Protection Force Disable 3 inactive

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1017


Pulse Counter 1

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 87
Description
This is the input of the "slow" Pulse Counters (page 211) function which is connected with LBI PULSE
COUNTER 1 (PAGE 1018).

6 back to Logical binary inputs alphabetically

Pulse Counter 2

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 88
Description
This is the input of the "slow" Pulse Counters (page 211) function which is connected with LBI PULSE
COUNTER 2 (PAGE 1018).

6 back to Logical binary inputs alphabetically

PV 01 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1103
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 02 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1121
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 03 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1122
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1018


PV 04 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1123
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 05 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1124
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 06 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1125
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 07 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1126
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 08 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1127
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1019


PV 09 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1128
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 10 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1129
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 11 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1130
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 12 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1131
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 13 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1132
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1020


PV 14 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1133
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 15 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1134
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 16 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1134
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 17 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1398
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 18 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1399
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1021


PV 19 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1103
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 20 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1401
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 21 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1402
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 22 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1403
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 23 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1404
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1022


PV 24 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1405
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 25 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1406
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 26 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1407
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 27 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1408
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 28 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1409
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1023


PV 29 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1410
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 30 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1411
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 31 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1412
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PV 32 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1413
Description
This logical input is used to detect whether the PV inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

PVCB Button

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1114
Description
Binary input has the same function as PVCB button.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1024


PVCB Disable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1104
Description
This function is used to prevent PVCB closing and opening.
If the input is active during synchronizing, the controller will continue synchronizing without issuing
the PVCB closing command until the input is deactivated or Sync timeout is elapsed.
If the input is active and the PVCB button is pressed in MAN mode to close the PVCB to dead bus,
the PVCB will not be closed until the input is deactivated and the PVCB button pressed again.
If the input is active and the PVCB should be closed to dead bus automatically, the PVCB will not
be closed until the input is deactivated.
If the input is active and the PVCB is already closed, the breaker will not open.

6 back to Logical binary inputs alphabetically

PVCB Feedback

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1101
Description
Use this input to indicate whether the PV circuit breaker is opened or closed.

Image 7.19 PVCB Feedback 1

Image 7.20 PVCB Feedback 2

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1025


PVCB Feedback Negative

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1102
Description
Use this input to indicate whether the PV circuit breaker is opened or closed.
This input is logically inverted against LBI PVCB FEEDBACK (PAGE 1025).

Image 7.21 PVCB Feedback Negative 1

Image 7.22 PVCB Feedback Negative 2

6 back to Logical binary inputs alphabetically

LBI: R

Remote AUTO

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 620
Description
The controller is switched to the AUTO mode when this binary input is closed. When opens controller is
switched back to previous mode.
This binary input has the lowest priority from Remote OFF / MAN / AUTO / binary inputs
Remote control priority:
Remote OFF (Highest priority)
Remote MAN
Remote AUTO (Lowest Priority)

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1026


Remote MAN

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 618
Description
The controller is switched to the MAN mode when this binary input is closed. When opens controller is
switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote MAN
Remote AUTO (Lowest Priority)

6 back to Logical binary inputs alphabetically

Remote OFF

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 617
Description
The controller is switched to the OFF mode when this binary input is closed. When opens controller is
switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote MAN
Remote AUTO (Lowest Priority)

6 back to Logical binary inputs alphabetically

LBI: S

Sd Override

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 44
Description
If this input is active, all alarms except Emergency Stop (page 1280)and E-STOP (page 1280) are
suppressed. The suppressed alarms will be displayed in the alarm list, but they will not take effect
regarding the BESS control.
Note: Wrn Override All Sd (page 1256) is indicated in the alarm list if Sd Override mode is active to
inform the operator that the BESS is not protected.

Note: User protections (page 205) with protection type Shutdown Override (page 199) are also NOT
suppressed.

IMPORTANT: MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE BESS!

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1027


Soft Bus Energize

Related FW 1.5.0 Related applications MINT,


LBI ID 1192
Description
This logical input should be used to soft energize the dead bus (load, transformer) while the DC
precharge is used. During the start sequence when precharge is finished the BCB is firstly closed to the
dead bus and then the LBO INVERTER RUN REQUEST (PAGE 1084) is activated. If the inverter supports
the voltage ramp up, the bus should be energized with limited inrush current.

6 back to Logical binary inputs alphabetically

Soft Unload Enable

Related FW 1.5.0 Related applications MINT,


LBI ID 1049
Description
In case the communication with other controllers is lost, the soft unload is being proceeded only if this
logical binary input is active. If this input is not active the BCB is opened immediately after the stop
request is detected or the BCB button is pressed.
Note: This function is used when there is any non-detected unit which is able to take over the load of the
BESS which is being unloaded.

6 back to Logical binary inputs alphabetically

Start Blocking

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 68
Description
Start of the BESS is blocked if this binary input gets active before Start command is issued. While start is
blocked, alarm ALI Start Blocking (page 1276) is active.
Note: Activation of this LBI while BESS is already running (or is about to be started) has no effect.

6 back to Logical binary inputs alphabetically

Start Button

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 189
Description

Binary input has the same function as Start Button on an External display (page 79)Internal display.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1028


Stop Button

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 190
Description

Binary input has the same function as Stop Button on an External display (page 79)Internal display.

6 back to Logical binary inputs alphabetically

Sunrise/Sunset Home Position

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1120
Description
Rising edge on this input make the setpoint Sunrise/sunset Latitude and Sunrise/Sunset Longitude
synchronized with the current position received from the GPS plug-in module (only if valid and available).

6 back to Logical binary inputs alphabetically

Synchronization Disabled

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 277
Description
This binary input is used to disable the forward and reverse synchronization process so the controller
won't attempt to close breaker(s) if synchronization would be needed.This LBI is useful if user want to set
the additional condition for start of the synchronization.

6 back to Logical binary inputs alphabetically

LBI: T

TEST ROCOF

Related FW 1.5.0 Related applications MINT


LBI ID 1116
Description
A rising edge on this LBI triggers the same event in the controller as the actual ROCOF 1 protection trip.

6 back to Logical binary inputs alphabetically

Test Vector Shift

Related FW 1.5.0 Related applications MINT


LBI ID 1117
Description
A rising edge on this LBI triggers the same event in the controller as the actual Vector Shift protection trip.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1029


Top Priority

Related FW 1.5.0 Related applications MINT


LBI ID 199
Description
If this input is active, the controller will have the highest priority in the group independent of the setpoint
Priority (page 492).
IMPORTANT: This binary input can be used only if setpoint #Priority Auto Swap (page 493) =
Disabled.

6 back to Logical binary inputs alphabetically

LBI: U

Uni Gen 01 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1335
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 01 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1351
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 01 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1372
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1030


Uni Gen 01 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1319
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 02 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1336
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 02 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1352
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 02 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1373
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1031


Uni Gen 02 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1320
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 03 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1337
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 03 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1353
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 03 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1374
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1032


Uni Gen 03 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1321
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 04 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1338
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 04 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1354
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 04 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1375
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1033


Uni Gen 04 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1322
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 05 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1339
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 05 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1355
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 05 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1376
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1034


Uni Gen 05 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1323
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 06 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1340
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 06 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1356
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 06 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1377
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1035


Uni Gen 06 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1324
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 07 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1341
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 07 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1357
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 07 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1378
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1036


Uni Gen 07 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1325
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 08 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1342
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 08 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1358
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 08 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1379
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1037


Uni Gen 08 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1326
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 09 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1343
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 09 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1359
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 09 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1380
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1038


Uni Gen 09 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1327
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 10 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1344
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 10 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1360
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 10 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1381
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1039


Uni Gen 10 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1328
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 11 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1345
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 11 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1361
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 11 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1382
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1040


Uni Gen 11 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1329
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 12 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1346
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 12 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1362
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 12 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1383
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1041


Uni Gen 12 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1330
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 13 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1347
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 13 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1363
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 13 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1384
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1042


Uni Gen 13 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1331
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 14 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1348
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 14 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1364
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 14 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1385
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1043


Uni Gen 14 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1332
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 15 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1349
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 15 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1365
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 15 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1386
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1044


Uni Gen 15 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1333
Description
Currently not associated with any specific logic. It is not expected to be used in configuration.

6 back to Logical binary inputs alphabetically

Uni Gen 16 GCB Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1350
Description
This is information about the UniGen´s GCB status. This signal is supposed to be active anytime when
the GCB is closed..

6 back to Logical binary inputs alphabetically

Uni Gen 16 GCB Closing

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1366
Description
This signal is crucial for safe operation if the Uni Gen is supposed to perform energizing of the dead bus.
In InteliNeo it is used as signal blocking closing of the BCB to the dead bus.
InteliNeo propagates this information to all other controllers in the system. The closing of the breaker to
the dead bus is blocked in all the controllers within the system until the signals is active.
IMPORTANT: InteliNeo does not propagate this information towards to other Uni Gens.
Uni Gens has to manage this function themselves. It is strongly recommended to use the
hard wiring of this signal between InteliNeo and Uni Gen.

6 back to Logical binary inputs alphabetically

Uni Gen 16 Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1387
Description
This signal is important to say to the InteliNeo that Uni Gen loading process has finished or is not in
unloading process. If this information is not available and can’t be directly read from the Uni Gen it has to
be constructed in the internal PLC as result of inverse logic based on readings Uni Gen in Soft Loading /
Soft Unloading.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1045


Uni Gen 16 Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1334
Description
Currently not associated with any specific logic. It is not expected to bue used in configuration.

6 back to Logical binary inputs alphabetically

LBI: W

WT 01 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1136
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

WT 02 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1137
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

WT 03 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1138
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

WT 04 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1139
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1046


WT 05 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1140
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

WT 06 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1141
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

WT 07 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1142
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

WT 08 Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBI ID 1143
Description
This logical input is used to detect whether the WT inverter is operable or not. If it is not activated the
PVCB cannot be closed.

6 back to Logical binary inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1047


9.1.7 Logical binary outputs
What Logical binary outputs are:
Logical binary outputs are outputs for binary values and functions.

Alphabetical groups of Logical binary outputs


LBO: A 1052
LBO: B 1055
LBO: C 1065
LBO: D 1068
LBO: E 1069
LBO: F 1080
LBO: G 1081
LBO: H 1082
LBO: I 1084
LBO: K 1084
LBO: L 1085
LBO: M 1090
LBO: N 1094
LBO: O 1095
LBO: P 1096
LBO: R 1105
LBO: S 1106
LBO: U 1109
LBO: V 1109
LBO: W 1110

For full list of Logical binary outputs go to the chapter Logical binary outputs alphabetically (page 1049).

InteliNeo 6000 1.5.0 Global Guide 1048


Logical binary outputs alphabetically

LBO: A 1052 BESS Parallel Oper 1065 ECU 11 Comm Fail 1071
Access Locked 1052 BESS Ready To Load 1065 ECU 12 Comm Fail 1071
AL Maintenance 1 1052 LBO: C 1065 ECU 13 Comm Fail 1071
AL Maintenance 2 1052 Common Alarm Active ECU 14 Comm Fail 1071
AL Maintenance 3 1052 Level 1 1065 ECU 15 Comm Fail 1071
AL Maintenance 4 1052 Common Alarm Active ECU 16 Comm Fail 1072
Level 2 1065
Alarm 1053 ECU 17 Comm Fail 1072
Common Alarm Level 1 1066
Alarm BESS Frequency 1053 ECU 18 Comm Fail 1072
Common Alarm Level 2 1066
Alarm BESS Overcurrent 1053 ECU 19 Comm Fail 1072
Common Alarm Only 1066
Alarm BESS Voltage 1053 ECU 20 Comm Fail 1072
Common History Record 1066
Alarm Flashing 1053 ECU 21 Comm Fail 1072
Common Mains
Alarm BESS 1054 ECU 22 Comm Fail 1073
Protection 1066
Alarm BESS Frequency 1054 ECU 23 Comm Fail 1073
Common PVCB Open 1067
Alarm BESS Voltage 1054 ECU 24 Comm Fail 1073
Common Shutdown 1067
All Available Gen-sets ECU 25 Comm Fail 1073
Common Shutdown
Run 1054 ECU 26 Comm Fail 1073
Override 1067
Any GCB Closed 1055 ECU 27 Comm Fail 1073
Common Slow Stop 1067
Any Other GCB Closed 1055 ECU 28 Comm Fail 1074
Common Warning 1068
LBO: B 1055 ECU Comm OK 1074
Curtailment Enable 1068
BCB Button Echo 1055
ECU Power Relay 1074
LBO: D 1068
BCB Close/Open 1055
Daily Batt Cycles ECU Run Stop 1074
BCB Close/Open
Reached 1068 Energized 1075
Secondary 1056
DC Circuit Closed 1068 Engines Swapped 1075
BCB OFF Coil 1057
Deadbus 1068 Event Load Reduction 1075
BCB OFF Coil Secondary 1058
Day/Night 1069 Event Mains Frequency
BCB ON Coil 1059
LBO: E 1069 Fall 1075
BCB ON Coil Secondary 1060
ECU Comm Fail 1069 Event Mains Frequency
BCB Status 1060 Rise 1075
ECU 1 Comm Fail 1069
BCB Primary Status 1061 Event Mains Trip 1076
ECU 2 Comm Fail 1069
BCB Secondary Status 1061 Event P for Q 1076
ECU 3 Comm Fail 1069
BCB UV Coil 1061 Event P(Um) 1076
ECU 4 Comm Fail 1070
BCB UV Coil Secondary 1063 Event Post VRT 1076
ECU 5 Comm Fail 1070
BESS Active 1063 Event Return Over/Under
ECU 6 Comm Fail 1070
BESS Capability C Limit 1064 Frequency 1076
ECU 7 Comm Fail 1070
BESS Capability L Limit 1064 Event Soft Unload 1077
ECU 8 Comm Fail 1070
BESS Healthy 1064 Exercise Timer 1 1077
ECU 9 Comm Fail 1070
BESS In Loadsharing 1064 Exercise Timer 2 1077
ECU 10 Comm Fail 1071

InteliNeo 6000 1.5.0 Global Guide 1049


Exercise Timer 3 1077 Load Shedding Stage 5 1086 P Under Frequency
Exercise Timer 4 1078 Load Shedding Stage 6 1087 Active 1096

Exercise Timer 5 1078 Load Shedding Stage 7 1087 P Under Frequency


Curve Invalid 1096
Exercise Timer 6 1078 Load Shedding Stage 8 1087
Pave 1097
Exercise Timer 7 1078 Loaded 1088
Pave FLS 1097
Exercise Timer 8 1079 Logical 0 1088
Peak Shaving Active 1097
Exercise Timer 9 1079 Logical 1 1088
Peripheral Module Comm
Exercise Timer 10 1079 LVRT 1-phase Invalid 1088
Fail 1097
Exercise Timer 11 1080 LVRT 2-phase Invalid 1088
Power Switch 1098
Exercise Timer 12 1080 LVRT 3-phase Invalid 1089
PQ-C Area Limit 1098
LBO: F 1080 LVRT Active 1089
PQ-L Area Limit 1098
FltRes Button Echo 1080 LVRT Severe 1089
Prestart 1098
Forward Synchronization 1080 LVRTCurveTrip 1089
Precharge 1099
Frequency Down 1081 LBO: M 1090
Precharge Request 1099
Frequency Up 1081 Mains/Bus Healthy 1090
Process Power Limitation 1099
LBO: G 1081 Manual Ready 1090
PV Operable 1099
GPS Coordinates MCB Button Echo 1090
Detected 1081 PV/WT Run Request 1100
MCB Close/Open 1090
GridCodes Power PVCB Button Echo 1100
MCB OFF Coil 1091
Limitation 1081 PVCB Close/Open 1100
MCB ON Coil 1092
LBO: H 1082 PVCB OFF Coil 1101
MCB Status 1092
Heartbeat 1082 PVCB ON Coil 1102
MCB UV Coil 1093
Horn 1082 PVCB Status 1103
Mode AUTO 1093
Horn Flashing 1082 PVCB UV Coil 1104
Mode MAN 1093
HornRes Button Echo 1082 LBO: R 1105
Mode OFF 1094
Hot Swap Heartbeat 1083 Ready 1105
LBO: N 1094
Hot Swap Switch 1083 Reverse Synchronization 1105
NCB Close/Open 1094
HW AC Voltage ROCOF 1 Active 1105
Not In Auto 1094
Measurement Error 1083 ROCOF 2 Active 1105
Not Ready 1094
LBO: I 1084 ROCOF 3 Active 1105
Not Used 1094
In Synchronism 1084 ROCOF 4 Active 1106
LBO: O 1095
Initialized 1084
LBO: S 1106
Operational 1095
Inverter Run Request 1084 Sd Override 1106
OVRT Active 1095
LBO: K 1084 SOC Discharge Disabled 1106
OVRT Invalid 1095
kWh Pulse 1084 SOC Charge Disabled 1106
OVRTCurveTrip 1095
LBO: L 1085 Soft Load 1106
Load Reduction Active 1085 LBO: P 1096
Soft Unload 1107
P for Q Active 1096
Load Shedding Stage 1 1085
Start Blocked 1107
P Over Frequency Active 1096
Load Shedding Stage 2 1085
Start Button Echo 1107
P Over Frequency Curve
Load Shedding Stage 3 1086
Invalid 1096 Starting 1107

InteliNeo 6000 1.5.0 Global Guide 1050


Stop Button Echo 1107
Stopping 1108
Sync To Mains Allowed 1108
System Ready 1108
System Reserve OK 1108
LBO: U 1109
UQ-C Area Limit 1109
UQ-L Area Limit 1109
LBO: V 1109
Vector Shift Active 1109
Voltage Down 1109
Voltage Up 1110
LBO: W 1110
WT Operable 1110
6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 1051


LBO: A

Access Locked

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2480
Description
This output is closed when the function Access lock (page 121) is activated and it can be used to block
any LBIs which are required to be locked.

6 back to Logical binary outputs alphabetically

AL Maintenance 1

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2211
Description
This output is active when alarm Maintenance 1 RunHours (page 1322) or Maintenance 1 Interval
(page 1322) is present in the alarm list.

6 back to Logical binary outputs alphabetically

AL Maintenance 2

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2212
Description
This output is active when alarm Maintenance 2 RunHours (page 1323) or Maintenance 2 Interval
(page 1323) is present in the alarm list.

6 back to Logical binary outputs alphabetically

AL Maintenance 3

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2213
Description
This output is active when alarm Maintenance 3 RunHours (page 1324) or Maintenance 3 Interval
(page 1323) is present in the alarm list.

6 back to Logical binary outputs alphabetically

AL Maintenance 4

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2650
Description
This output is active when alarm Maintenance 4 RunHours (page 1324) or Maintenance 4 Interval
(page 1324) is present in the alarm list.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1052


Alarm

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2
Description
The output is designed to be used as external alarm indication such as a red bulb in the control room etc.
The output is active when at least one unconfirmed alarm is present in the alarmlist and remains active
until confirmation of alarm.

6 back to Logical binary outputs alphabetically

Alarm BESS Frequency

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1266
Description
This output is active when at least 1 protection caused by BESS >f Protection (page 584) or BESS <f
Protection (page 585) is active.

6 back to Logical binary outputs alphabetically

Alarm BESS Overcurrent

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 109
Description
This output is active while at least one of the following overcurrent protection is active Short Circuit
Protection (page 571) or IDMT BESS >A Protection (page 571).

6 back to Logical binary outputs alphabetically

Alarm BESS Voltage

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1263
Description
This output is active when at least 1 alarm caused by BESS >>V Protection (page 575), BESS >V
(page 574) or BESS <V Protection (page 576) is present in the alarmlist.

6 back to Logical binary outputs alphabetically

Alarm Flashing

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 28
Description
This is the flashing alternative of the output ALARM (PAGE 1053), i.e. the output flashes with 1 Hz period
while the output Alarm is closed.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1053


Alarm BESS

Related FW 1.5.0 Related applications MPTM


LBO ID 197
Description
This output is active when at least 1 protection caused by Mains >>V Protection (page 579), Mains >V
Protection (page 577) or Mains <V Protection (page 581), Mains <V Protection (page 582), Mains
>>f Protection (page 587), Mains >f Protection (page 586), Mains <f Protection (page 588), Mains
<<f Protection (page 589) is active.

6 back to Logical binary outputs alphabetically

Alarm BESS Frequency

Related FW 1.5.0 Related applications MPTM


LBO ID 1271
Description
This output is closed when at least 1 protection caused by Mains >>f Protection (page 587) Mains >f
Protection (page 586), Mains <f Protection (page 588) or Mains <<f Protection (page 589) is active.

6 back to Logical binary outputs alphabetically

Alarm BESS Voltage

Related FW 1.5.0 Related applications MPTM


LBO ID 1270
Description
This output is closed when at least 1 protection caused by Mains >>V Protection (page 579) Mains >V
Protection (page 577), Mains <V Protection (page 581) or Mains <V Protection (page 582) is
active.

6 back to Logical binary outputs alphabetically

All Available Gen-sets Run

Related FW 1.5.0 Related applications MINT


LBO ID 122
Description
This output is closed when all available BESSs within the Control Group (page 516) are loaded.
Note: BESS is available if Power Management (page 489) = Enabled, Controller Mode (page 885) =
AUTO and there is not present Alarms level 2 (page 1278) in the alarmlist.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1054


Any GCB Closed

Related FW 1.5.0 Related applications MINT


LBO ID 222
Description
This output is active when a GCB of any controller connected via ⑧ CAN2A (page 46) and/or ⑦ CAN2B
(page 46) is closed.
Note: This function works on CAN16 (page 893) - CAN64 (page 894) values, therefore it ignores
Control Groups (page 136).

6 back to Logical binary outputs alphabetically

Any Other GCB Closed

Related FW 1.5.0 Related applications MINT


LBO ID 1827
Description
This output is active when a GCB of any other controller connected via ⑧ CAN2A (page 46) and/or
⑦ CAN2B (page 46) is closed.
Note: This function works on CAN16 (page 893) - CAN64 (page 894) values, therefore it ignores
Control Groups (page 136).

6 back to Logical binary outputs alphabetically

LBO: B

BCB Button Echo

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 35
Description
This output is closed for 1s every time BCB Button is pressed.
That means:
BCB button is pressed on the controller front panel or
BCB button is pressed on any of external local/remote terminals or
BCB close/open command is received via communication line

6 back to Logical binary outputs alphabetically

BCB Close/Open

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 41
Description
The output controls the primary BESS circuit breaker. Its state represents the breaker position
requested by the controller.
If the feedback does not respond to a change within 2 seconds to a close or open command and it was
already the last attempt, an specific alarm based on the current breaker position is issued.

InteliNeo 6000 1.5.0 Global Guide 1055


Image 7.23 BCB Close command

6 back to Logical binary outputs alphabetically

BCB Close/Open Secondary

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1058
Description
The output controls the secondary BESS circuit breaker. Its state represents the breaker position
requested by the controller.
If the feedback does not respond to a change within time adjusted in 2 seconds to a close or open
command and it was already the last attempt, an specific alarm based on the current breaker position is
issued.

Image 7.24 BCB Close command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1056


BCB OFF Coil

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 43
Description
The output is intended for opening of primary BESS circuit breaker.
The output gives a pulse in the moment the breaker has to be opened. The pulse lasts until the feedback
deactivates, but at least for 2 seconds, when circuit breaker has to open with pause 1 second between
each pulse. If the LBI BCB FEEDBACK (PAGE 991) does not match after second pulse elapses, Alarm Sd
BCB Fail To Open (page 1291) Wrn MCB Fail To Open (page 1256) is issued.

Image 7.25 BCB OFF Coil command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1057


BCB OFF Coil Secondary

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1068
Description
The output is intended for opening of secondary BESS circuit breaker.
The output gives a pulse in the moment the breaker has to be opened. The pulse lasts until the feedback
deactivates, but at least for 2 seconds, when circuit breaker has to open with pause 1 second between
each pulse. If the LBI BCB SECONDARY FEEDBACK NEGATIVE (PAGE 993) does not match after second
pulse elapses, Alarm Stp BCB Secondary Fail To Open (page 1294) is issued.

Image 7.26 BCB OFF Coil command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1058


BCB ON Coil

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 42
Description
The output is intended for control of close coil of primary BESS circuit breaker.
The output gives at least 2 second pulse in the moment the breaker has to be closed. The pause
between attempts is 3 seconds.
When the last attempt elapses and LBI BCB FEEDBACK (PAGE 991) does not match Alarm Sd BCB Fail
To Close (page 1291) is issued.

Image 7.27 BCB ON Coil close command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1059


BCB ON Coil Secondary

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1067
Description
The output is intended for control of close coil of secondary BESS circuit breaker.
The output gives at least 2 second pulse in the moment the breaker has to be closed. The pause
between attempts is 3 seconds

Image 7.28 BCB ON Coil close command

6 back to Logical binary outputs alphabetically

BCB Status

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 84
Description
This output indicates the BCB position as it is internally considered by the controller.
The position is based on BCB FEEDBACK (PAGE 991) and BCB FEEDBACK NEGATIVE (PAGE 992).
In case that only positive feedback is used, this output mirrors the feedback.
In case that both feedbacks are used and
Feedbacks match each other - the output indicates BCB position according to feedbacks.
Feedbacks do not match each other - output indicates last position when feedbacks matched.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1060


BCB Primary Status

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2541
Description
This output indicates the Primary BCB position as it is internally considered by the controller.
The position is based on BCB FEEDBACK (PAGE 991) and BCB FEEDBACK NEGATIVE (PAGE 992).
In case that only BCB FEEDBACK (PAGE 991) is used, this output mirrors the input.
In case that both BCB FEEDBACK (PAGE 991) and BCB FEEDBACK NEGATIVE (PAGE 992) are used
and
Feedbacks match - output indicates BCB position according to feedbacks.
Feedbacks do not match - output indicates last position when feedbacks matched.

6 back to Logical binary outputs alphabetically

BCB Secondary Status

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2542
Description
This output indicates the Secondary BCB position as it is internally considered by the controller.
The position is based on BCB SECONDARY FEEDBACK (PAGE 994) and BCB SECONDARY FEEDBACK
NEGATIVE (PAGE 993).
In case that only BCB SECONDARY FEEDBACK (PAGE 994) is used, this output mirrors the input.
In case that both BCB SECONDARY FEEDBACK (PAGE 994) and BCB SECONDARY FEEDBACK
NEGATIVE (PAGE 993) are used and
Feedbacks match - output indicates BCB position according to feedbacks.
Feedbacks do not match - output indicates last position when feedbacks matched.

6 back to Logical binary outputs alphabetically

BCB UV Coil

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 44
Description
The output is intended for control of undervoltage coil of primary BESS circuit breaker.
The output is closed after the BESShas been started, min stab time has elapsed and the BESS voltage
and frequency have got into limits.BCB closing command is blocked for 1 sec after the UV coil has been
closed to allow the breaker's mechanical system to get ready for closing. The output is opened for 2
seconds when the BCB has to open.
The output is closed again and remains closed while the BESS voltage and frequency are within limits if
the Running phase follows after the opening of the BCB (e.g. in MAN). The output remains open if the
Cooling phase follows after the opening of the BCB.

InteliNeo 6000 1.5.0 Global Guide 1061


Image 7.29 BCB UV Coil close command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1062


BCB UV Coil Secondary

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1069
Description
The output is intended for control of undervoltage coil of secondary BESS circuit breaker.
The output is closed after the BESShas been started, min stab time has elapsed and the BESS voltage
and frequency have got into limits.BCB closing command is blocked for 1 sec after the UV coil has been
closed to allow the breaker's mechanical system to get ready for closing. The output is opened for 2
seconds when the BCB has to open.

Image 7.30 BCB UV Coil close command

6 back to Logical binary outputs alphabetically

BESS Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 60
Description
This output is closed at the beginning of the Prestart Time (page 1) period and opens when BESS is
stopped.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1063


BESS Capability C Limit

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1427
Description
This output is closed when the BESS Required PF (page 865) (while BESS Required PF Character
(page 865) = C) or BESS Required Q (page 865) is out of capacitive limits in which is the BESS allowed
to run.
Limits are given by adjusting the CAPABILITY C (PAGE 974).

6 back to Logical binary outputs alphabetically

BESS Capability L Limit

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1428
Description
This output is closed when the BESS Required PF (page 865) (while BESS Required PF Character
(page 865) = L) or BESS Required Q (page 865) is out of inductive limits in which is the BESS allowed
to run.
Limits are given by adjusting the CAPABILITY L (PAGE 973).

6 back to Logical binary outputs alphabetically

BESS Healthy

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 77
Description
This output is closed while BESS is running and its parameters (voltage & frequency) are considered as
healthy, i.e. within limits.

6 back to Logical binary outputs alphabetically

BESS In Loadsharing

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2699
Description
This output is active always when the BESS is forced to join the Load Sharing due to Forced power
condition (page 241).

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1064


BESS Parallel Oper

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 459
Description
This output is active always when the BESS is running in parallel operation with any Gen-set, Mains, or
PV (renewable source of energy).

6 back to Logical binary outputs alphabetically

BESS Ready To Load

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 58
Description
The output is closed when the BESS is ready to be loaded (conditions below are fulfilled).
In case of DC precharge is used and there are not any external conditions the BCB breaker can be
closed.
In case of AC precharge is used the BCB breaker cannot be closed until healthy bus is detected.
BESS is running
LBI BESS READY TO LOAD (PAGE 995) is closed or BESSReady to Load TO (page 435)
elapsed if the LBI is not configured
Minimal Stabilization Time (page 441) elapsed (DC precharge only)
Stabilization phase finished (DC precharge only)
BESS's Voltage & Frequency (DC precharge only)
Must be within limits if BCB is opened
Can be out of limits for the time specified by a protection delay if BCB is closed

6 back to Logical binary outputs alphabetically

LBO: C

Common Alarm Active Level 1

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 13
Description
This output is closed when there is at least one Alarms level 1 (page 1245) in the alarmlist.

6 back to Logical binary outputs alphabetically

Common Alarm Active Level 2

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 15
Description
This output is closed when there is at least one Alarms level 2 (page 1278) in the alarmlist.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1065


Common Alarm Level 1

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 14
Description
This output is closed when there is at least one unconfirmed Alarms level 1 (page 1245) in the
alarmlist.

6 back to Logical binary outputs alphabetically

Common Alarm Level 2

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 16
Description
This output is closed when there is at least one unconfirmed Alarms level 2 (page 1278) in the
alarmlist.

6 back to Logical binary outputs alphabetically

Common Alarm Only

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 11
Description
This output is closed when there is at least one alarm of type Alarm Only (page 1269) present in the
alarmlist.

6 back to Logical binary outputs alphabetically

Common History Record

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 12
Description
This output is closed for 1 second every time alarm of type History Record Only (page 1277) occurs.
Note: When any History Record alarm is activated the history record is logged into history.

6 back to Logical binary outputs alphabetically

Common Mains Protection

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 10
Description
This output is closed when there is at least one active alarm of type Mains Protection (page 199).
Note: When any Mains Protection alarm is activated the Mains fail is signalized and AMF Function
(page 125) is started if it is enabled.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1066


Common PVCB Open

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 187
Description
This output is closed when there is at least one alarm of type PV Breaker Open (page 1297) present in
the alarmlist.

6 back to Logical binary outputs alphabetically

Common Shutdown

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 4
Description
This output is closed when there is at least one active alarm of type Shutdown (page 1280) present in
the alarmlist.
Note: When any MainsShutdown alarm is activated the BCB opens and BESS stops immediately.

6 back to Logical binary outputs alphabetically

Common Shutdown Override

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 251
Description
This output is closed 2 seconds after there is at least one alarm of type Shutdown Override (page 199)
present in the alarmlist.
Note: When any Sd Override alarm is activated the BCB opens and BESS stops immediately. This
protection type can not be blocked (overridden) by active LBI (function) SD OVERRIDE (PAGE 1027).

6 back to Logical binary outputs alphabetically

Common Slow Stop

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5
Description
This output is closed when there is at least one alarm of type Slow Stop (page 1290) present in the
alarmlist.
Note: When any Stp alarm is activated and there is another BESS that is currently not running
loaded and it is Ready for Power management the controller will wait for #Slow Stop Delay (page
511) and than starts unloading if it is possible. If there is no other BESS in such state the controller
starts unloading immediately without the delay.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1067


Common Warning

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 3
Description
This output is closed when there is at least one alarm of type Warning (page 1248) present in the
alarmlist.

6 back to Logical binary outputs alphabetically

Curtailment Enable

Related FW 1.5.0 Related applications MPTM


LBO ID 2691
Description
This output is active when the function curtailment is used to regulate power of the PV.

6 back to Logical binary outputs alphabetically

LBO: D

Daily Batt Cycles Reached

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2704
Description
This output is active always when the number of daily battery cycles is reached.

6 back to Logical binary outputs alphabetically

DC Circuit Closed

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2784
Description
This LBO is a miror of the LBI PRECHARGE FINISHED (PAGE 1016). It is active all the time when DC circuit
of the BESS is closed.

6 back to Logical binary outputs alphabetically

Deadbus

Related FW 1.5.0 Related applications MINT,


LBO ID 2675
Description
This output is active when the Bus is considered to be dead (Bus voltage is below relative value set by
the setpoint Bus Dead Level (page 383)).

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1068


Day/Night

Related FW 1.5.0 Related applications MINT,


LBO ID 5931
Description
This LBO is active during the day.(If the current time is between Sunrise Time and Sunset Time)

6 back to Logical binary outputs alphabetically

LBO: E

ECU Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 114
Description
This output is closed when there is no communication with at least one configured ECU.

6 back to Logical binary outputs alphabetically

ECU 1 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1998
Description
This output is closed when there is no communication with ECU configured in ECU slot 1.

6 back to Logical binary outputs alphabetically

ECU 2 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1999
Description
This output is closed when there is no communication with ECU configured in ECU slot 2.

6 back to Logical binary outputs alphabetically

ECU 3 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2000
Description
This output is closed when there is no communication with ECU configured in ECU slot 3.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1069


ECU 4 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2001
Description
This output is closed when there is no communication with ECU configured in ECU slot 4.

6 back to Logical binary outputs alphabetically

ECU 5 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2002
Description
This output is closed when there is no communication with ECU configured in ECU slot 5.

6 back to Logical binary outputs alphabetically

ECU 6 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2003
Description
This output is closed when there is no communication with ECU configured in ECU slot 6.

6 back to Logical binary outputs alphabetically

ECU 7 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2004
Description
This output is closed when there is no communication with ECU configured in ECU slot 7.

6 back to Logical binary outputs alphabetically

ECU 8 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2005
Description
This output is closed when there is no communication with ECU configured in ECU slot 8.

6 back to Logical binary outputs alphabetically

ECU 9 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2006
Description
This output is closed when there is no communication with ECU configured in ECU slot 9.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1070


ECU 10 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2007
Description
This output is closed when there is no communication with ECU configured in ECU slot 10.

6 back to Logical binary outputs alphabetically

ECU 11 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2008
Description
This output is closed when there is no communication with ECU configured in ECU slot 11.

6 back to Logical binary outputs alphabetically

ECU 12 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2009
Description
This output is closed when there is no communication with ECU configured in ECU slot 12.

6 back to Logical binary outputs alphabetically

ECU 13 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2010
Description
This output is closed when there is no communication with ECU configured in ECU slot 13.

6 back to Logical binary outputs alphabetically

ECU 14 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2011
Description
This output is closed when there is no communication with ECU configured in ECU slot 14.

6 back to Logical binary outputs alphabetically

ECU 15 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2012
Description
This output is closed when there is no communication with ECU configured in ECU slot 15.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1071


ECU 16 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2013
Description
This output is closed when there is no communication with ECU configured in ECU slot 16.

6 back to Logical binary outputs alphabetically

ECU 17 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5766
Description
This output is closed when there is no communication with ECU configured in ECU slot 17.

6 back to Logical binary outputs alphabetically

ECU 18 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5768
Description
This output is closed when there is no communication with ECU configured in ECU slot 18.

6 back to Logical binary outputs alphabetically

ECU 19 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5769
Description
This output is closed when there is no communication with ECU configured in ECU slot 19.

6 back to Logical binary outputs alphabetically

ECU 20 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5770
Description
This output is closed when there is no communication with ECU configured in ECU slot 20.

6 back to Logical binary outputs alphabetically

ECU 21 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5771
Description
This output is closed when there is no communication with ECU configured in ECU slot 21.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1072


ECU 22 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5772
Description
This output is closed when there is no communication with ECU configured in ECU slot 22.

6 back to Logical binary outputs alphabetically

ECU 23 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5773
Description
This output is closed when there is no communication with ECU configured in ECU slot 23.

6 back to Logical binary outputs alphabetically

ECU 24 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5774
Description
This output is closed when there is no communication with ECU configured in ECU slot 24.

6 back to Logical binary outputs alphabetically

ECU 25 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5775
Description
This output is closed when there is no communication with ECU configured in ECU slot 25.

6 back to Logical binary outputs alphabetically

ECU 26 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5776
Description
This output is closed when there is no communication with ECU configured in ECU slot 26.

6 back to Logical binary outputs alphabetically

ECU 27 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5777
Description
This output is closed when there is no communication with ECU configured in ECU slot 27.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1073


ECU 28 Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 5778
Description
This output is closed when there is no communication with ECU configured in ECU slot 28.

6 back to Logical binary outputs alphabetically

ECU Comm OK

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 347
Description
This output is closed when all configured ECUs are communicating without any issue.

6 back to Logical binary outputs alphabetically

ECU Power Relay

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 116
Description
This output should be used for control of “keyswitch” input of an ECU. If the particular ECU does not have
keyswitch or a similar input, it can be used for control of DC power for the ECU.
The output closes together with PRESTART (PAGE 1098) and remains closed for the entire duration that
the BESS is running. It is opened at the moment that the BESS is stopped.
IMPORTANT: This LBO also affects evaluation of ECU Communication Fail alarms. With
configured LBO ECU Power Relay, these alarms are evaluated only when this LBO is active.
Without configured LBO ECU Power Relay, these alarm are evaluated all the time.

Note: This output can be also activated by LBI ECU KEY SWITCH (PAGE 996). In that case alarms related
to ECU Communication Fail alarms are not evaluated.

6 back to Logical binary outputs alphabetically

ECU Run Stop

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 958
Description
Signal for starting and stopping of ECU.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1074


Energized

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 67
Description
The output is designed to be used as an indication that the BESS is running. The out remains closed until
BESS stop.

6 back to Logical binary outputs alphabetically

Engines Swapped

Related FW 1.5.0 Related applications MINT


LBO ID 208
Description
When the master controller (controller with the lowest Controller Address) swaps priority of two
Controllers, the master controller generates 100 ms pulse with the output. The output works with the
setpoint #Priority Auto Swap (page 493) if it is setup to Run Hours Equal.

6 back to Logical binary outputs alphabetically

Event Load Reduction

Related FW 1.5.0 Related applications MPTM


LBO ID 1434
Description
This output is closed when Load Reduction Ramp (page 552) is in use.
See Load Reduction (page 303) for more information.

6 back to Logical binary outputs alphabetically

Event Mains Frequency Fall

Related FW 1.5.0 Related applications MPTM


LBO ID 1433
Description
This output is closed when Mains Frequency Fall Ramp (page 548) is in use.
See Power increase by under frequency - PuF (page 300) for more information.

6 back to Logical binary outputs alphabetically

Event Mains Frequency Rise

Related FW 1.5.0 Related applications MPTM


LBO ID 1432
Description
This output is closed when Mains Frequency Rise Ramp (page 547) is in use.
See Power reduction by over frequency - PoF (page 299) for more information.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1075


Event Mains Trip

Related FW 1.5.0 Related applications MPTM


LBO ID 1435
Description
This output is closed when the Grid Code function After Mains Trip Period is in an active state.
It is closed once the timer After MP Synchronization Period (page 541) is elapsed until the timer After
Mains Trip Period (page 542) is elapsed. Once the BESS starts to being unloaded and this output is
closed the Mains will be loaded slowly according to the After Mains Trip Period Ramp (page 543).

6 back to Logical binary outputs alphabetically

Event P for Q

Related FW 1.5.0 Related applications MPTM


LBO ID 1436
Description
This output is closed when P For Q Ramp (page 557) is in use.
See P For Q (page 306) for more information.

6 back to Logical binary outputs alphabetically

Event P(Um)

Related FW 1.5.0 Related applications MPTM


LBO ID 1786
Description
This output is closed when BESS P (page 707) and BESS Required P Target (page 861) are limited
due to Power Regulation Based On Actual Mains Voltage (page 302).

6 back to Logical binary outputs alphabetically

Event Post VRT

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1438
Description
This output is closed when Post VRT Ramp (page 563) is in use.
See Dynamic Support - VRT (page 304) for more information.

6 back to Logical binary outputs alphabetically

Event Return Over/Under Frequency

Related FW 1.5.0 Related applications MPTM


LBO ID 1785
Description
This output is closed when Return From Over/Under Frequency Ramp (page 546) is in use.
See Return from over/under frequency (page 301) for more information.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1076


Event Soft Unload

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1437
Description
This output is closed when Soft Unload Ramp (page 568) is in use.

6 back to Logical binary outputs alphabetically

Exercise Timer 1

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1250
Description
This output is closed when the Exercise timer 1 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 1 (page 633) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 2

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1251
Description
This output is closed when the Exercise timer 2 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 2 (page 635) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 3

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1946
Description
This output is closed when the Exercise timer 3 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 3 (page 637) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1077


Exercise Timer 4

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1947
Description
This output is closed when the Exercise timer 4 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 4 (page 639) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 5

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1948
Description
This output is closed when the Exercise timer 5 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 5 (page 641) subgroup.

6 back to Logical binary outputs alphabetically

Exercise Timer 6

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1949
Description
This output is closed when the Exercise timer 6 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 6 (page 643) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 7

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1950
Description
This output is closed when the Exercise timer 7 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 7 (page 645) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1078


Exercise Timer 8

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1951
Description
This output is closed when the Exercise timer 8 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 8 (page 647) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 9

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2630
Description
This output is closed when the Exercise timer 9 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 9 (page 649) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 10

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2631
Description
This output is closed when the Exercise timer 10 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 10 (page 651) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1079


Exercise Timer 11

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2632
Description
This output is closed when the Exercise timer 11 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 11 (page 653) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

Exercise Timer 12

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2633
Description
This output is closed when the Exercise timer 12 is activated. The output can be used to make periodic
tests of the BESS, breakers, any external logic etc. and its activation depends on the setpoints in the
Subgroup: Timer 12 (page 655) subgroup.
Note: If more than one timer is active at the same time, timer with selected higher priority function is
applied.

6 back to Logical binary outputs alphabetically

LBO: F

FltRes Button Echo

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 30
Description
This output provides 1 s pulse when:

Fault Reset button is pressed on an External display (page 79)Internal display.


Fault Reset command is received via communication line
LBI FAULT RESET BUTTON (PAGE 996) is activated.

6 back to Logical binary outputs alphabetically

Forward Synchronization

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 68
Description
This output is closed when forward synchronization is active (synchronization via BCB breaker) and
opens when LBO BCB STATUS (PAGE 1060) closes.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1080


Frequency Down

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 57
Description
This output together with the complementary output FREQUENCY UP (PAGE 1081) are designed for
frequency and power control of the BESS where the BESS inverter regulator does not support analogue
control.

6 back to Logical binary outputs alphabetically

Frequency Up

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 56
Description
This output together with the complementary output FREQUENCY DOWN (PAGE 1081) are designed for
frequency and power control of the BESS where the BESS inverter regulator does not support analogue
control.

6 back to Logical binary outputs alphabetically

LBO: G

GPS Coordinates Detected

Related FW 1.5.0 Related applications MINT,


LBO ID 5930
Description
This LBO is active if the GPS coordinates obtained from the GPS module are valid..

6 back to Logical binary outputs alphabetically

GridCodes Power Limitation

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2365
Description
This output is closed when power is reduced due to Grid Codes requirements:
Power reduction by over frequency - PoF (page 299)
Load Reduction (page 303)
P For Q (page 306)
Dynamic Support - VRT (page 304)

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1081


LBO: H

Heartbeat

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 81
Description
This output toggles on/off in a period of 500 ms whenever the controller is switched on and functional.

6 back to Logical binary outputs alphabetically

Horn

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1
Description
This output is closed when any Alarms (page 1245) is activated and stays closed until:

Fault reset is pressed

Horn reset is pressed


Horn Timeout (page 386) elapses

6 back to Logical binary outputs alphabetically

Horn Flashing

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 29
Description
This is the flashing alternative of the output HORN (PAGE 1082), i.e. the output flashes with 1 Hz period
while the output Horn is closed.

6 back to Logical binary outputs alphabetically

HornRes Button Echo

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 31
Description
This output is closed for 1 s every time Horn Reset Button is pressed.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1082


Hot Swap Heartbeat

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2447
Description
This output is used to inform the second Hot Swap Redundancy (page 160) controller about the fact
that this controller is alive.
This LBO has to be physically wired to the LBI HOT SWAP HEARTBEAT DETECT (PAGE 1005) of the second
Hot Swap Redundancy (page 160) controller. If the signal is not sent, the second controller activates
LBO HOT SWAP SWITCH (PAGE 1083).
IMPORTANT: This output has to be configured to physical output of the controller.

IMPORTANT: This output has to be configured on both Master and Backup controllers.

6 back to Logical binary outputs alphabetically

Hot Swap Switch

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2469
Description
This output is activated when the LBI HOT SWAP HEARTBEAT DETECT (PAGE 1005) of this controller do
not receive the LBO HOT SWAP HEARTBEAT (PAGE 1083) signal from the second Hot Swap
Redundancy (page 160) controller.
This output is used as control signal for switches / switch disconnectors that are used to disconnect
specific terminals of the second Hot Swap Redundancy (page 160) controller. It is also used as
physical input for LBI HOT SWAP CTRL BLOCK (PAGE 1005) of the second controller.
IMPORTANT: This output has to be configured to physicall output of the controller.

IMPORTANT: This output has to be configured on both Master and Backup controllers.

6 back to Logical binary outputs alphabetically

HW AC Voltage Measurement Error

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2560
Description
This logical binary output is activated once the wrong 3V3 reference voltage is detected.
It is recommended to use it to activate user protection which will open MCB/BCB and turn off the BESS to
prevent any damage to the BESS, load or Mains.
IMPORTANT: This LBO only works on HW revision D and higher.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1083


LBO: I

In Synchronism

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 80
Description
This output is closed during synchronization when Slip Angle, Slip Frequency and Voltages are inside
required windows.
Required windows are:
Slip Angle (page 717) between BESS and Bus Voltage is within range given by Phase Window
(page 487) for time longer than Dwell Time (page 487). Required if Synchronization Type
(page 485) = PhaseMatch.
Slip Frequency (page 717) between between BESS and Bus Frequency is withing range given
by Slip Frequency Window (page 488) for time longer than Dwell Time (page 487). Required if
Synchronization Type (page 485) = SlipSynchr.
Voltage difference between BESS and Bus voltage in all phases must be lower or equal to
Voltage Window (page 486) for time longer than Dwell Time (page 487). Required always.

6 back to Logical binary outputs alphabetically

Initialized

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1222
Description
This output is activated after the controller is initialized. It can be used to block some PLC logic blocks
while controller initialization is being proceeded.

6 back to Logical binary outputs alphabetically

Inverter Run Request

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2268
Description
This output is closed when Prestart Time (page 1) elapses and is opened when inverter is turned off.

6 back to Logical binary outputs alphabetically

LBO: K

kWh Pulse

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 206
Description
This output is active for 100 ms every time the Genset kWh is increased by one.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1084


LBO: L

Load Reduction Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1245
Description
This output is closed when Load Reduction (page 303) is active.

6 back to Logical binary outputs alphabetically

Load Shedding Stage 1

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 51
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by this LBO is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

Load Shedding Stage 2

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 52
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1085


Load Shedding Stage 3

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 53
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically


Load Shedding Stage 4
Related FW 1.5.0 Related applications MINT, MPTM
LBO ID 452
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

Load Shedding Stage 5

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 453
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1086


Load Shedding Stage 6

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 454
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

Load Shedding Stage 7

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 455
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

Load Shedding Stage 8

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 456
Description
This is an output of Load Shedding (page 171).
The load shedding outputs are activated in the order 1, 2, 3, …, X.
The load shedding outputs are deactivated in the order X, …, 3, 2, 1.
The load disconnected by LBO LOAD SHEDDING STAGE 1 (PAGE 1085) is the least essential load.

Note: X is the highest configured Load shedding outputs (page 171).

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1087


Loaded

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 72
Description
This output is closed while the BESS is loaded.
Note: Output is opened when BESS starts unloading or opens the BCB without of unloading.

6 back to Logical binary outputs alphabetically

Logical 0

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 26
Description
Logical binary output which is still in logical 0.

6 back to Logical binary outputs alphabetically

Logical 1

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 27
Description
Logical binary output which is still in logical 1.

6 back to Logical binary outputs alphabetically

LVRT 1-phase Invalid

Related FW 1.5.0 Related applications MPTM


LBO ID 2352
Description
This output is closed if any value on the y-axis of the LVRT 1-PHASE (PAGE 983) curve is equal to or
higher than 100% or when the curve is not configured.

6 back to Logical binary outputs alphabetically

LVRT 2-phase Invalid

Related FW 1.5.0 Related applications MPTM


LBO ID 2353
Description
This output is closed if any value on the y-axis of the LVRT 2-PHASE (PAGE 982) curve is equal to or
higher than 100% or when the curve is not configured.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1088


LVRT 3-phase Invalid

Related FW 1.5.0 Related applications MPTM


LBO ID 2354
Description
This output is closed if any value on the y-axis of the LVRT 3-PHASE (PAGE 981) curve is equal to or
higher than 100% or when the curve is not configured.

6 back to Logical binary outputs alphabetically

LVRT Active

Related FW 1.5.0 Related applications MPTM


LBO ID 2313
Description
This output is closed while LVRT Protection is active and stays closed for at least 500 ms.
See Dynamic Support - VRT (page 304) for more information.

6 back to Logical binary outputs alphabetically

LVRT Severe

Related FW 1.5.0 Related applications MPTM


LBO ID 2317
Description
This output is closed while BESS Voltage drops under level adjusted by LVRT Level Severe (page 562)
and stays closed for at least 500 ms.
See Dynamic Support - VRT (page 304) for more information.
Note: BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS Voltage L3-N
(page 713) is considered.

6 back to Logical binary outputs alphabetically

LVRTCurveTrip

Related FW 1.5.0 Related applications MPTM


LBO ID 2315
Description
This output is closed when the BESS Voltage drops below the line of LVRT curve and opens when the
BESS Voltage rises above the line of LVRT curve. This output is always closed at least for 3 seconds.
Note: LVRT 1-PHASE (PAGE 983), LVRT 2-PHASE (PAGE 982) and LVRT 3-PHASE (PAGE 981) are
considered.

Note: BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS Voltage L3-N
(page 713) are considered.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1089


LBO: M

Mains/Bus Healthy

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 78
Description
This output is closed while Mains/Bus parameters (voltage & frequency) are considered as healthy, i. e.
within limits.

Application Mode Setting of Limits


BESS >>V (page 452) BESS >f (page 455)
MINT Generator >V (page 1) BESS <f (page 456)
BESS <V (page 453)
Mains >>V (page 524) Mains >>f (page 532)
Mains >V (page 523) Mains >f (page 531)
MPTM
Mains <<V (page 528) Mains <<f (page 534)
Mains <V (page 527) Mains <f (page 533)

6 back to Logical binary outputs alphabetically

Manual Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1258
Description
This output is active when Controller Mode (page 885) = MAN and the BESS is stopped and it is
possible to start it. i.e. no red alarm is activated or SD OVERRIDE (PAGE 1027) is active (Output READY
(PAGE 1105) is active).

6 back to Logical binary outputs alphabetically

MCB Button Echo

Related FW 1.5.0 Related applications MPTM


LBO ID 34
Description
This output is closed for 1 s every time MCB Button is pressed.

6 back to Logical binary outputs alphabetically

MCB Close/Open

Related FW 1.5.0 Related applications MPTM


LBO ID 45
Description
The output controls the Mainsmains circuit breaker. Its state represents the breaker position requested
by the controller.
If the feedback does not respond in 2 seconds and it was already the last attempt the specific alarm

InteliNeo 6000 1.5.0 Global Guide 1090


based on the current breaker position is issued.

Image 7.31 MCB Close command

6 back to Logical binary outputs alphabetically

MCB OFF Coil

Related FW 1.5.0 Related applications MPTM


LBO ID 47
Description
The output is intended for opening of Mainsmains circuit breaker.
The output provides pulses, which length is 2 seconds when breaker has to open with pause 1 second
between each pulse. If the LBI MCB FEEDBACK (PAGE 1012) does not match after second pulse elapses
Alarm Wrn MCB Fail To Open (page 1256) is issued.

Image 7.32 MCB OFF Coil command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1091


MCB ON Coil

Related FW 1.5.0 Related applications MPTM


LBO ID 46
Description
The output is intended for control of close coil of Mainsmains circuit breaker.
The output provides pulse, which length is 2 seconds and the pause between attempts is 3 seconds.

Image 7.33 MCB ON Coil close command

6 back to Logical binary outputs alphabetically

MCB Status

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 85
Description
This output indicates the MCB position as it is internally considered by the controller. The position is
based on MCB FEEDBACK (PAGE 1012) and MCB FEEDBACK NEGATIVE (PAGE 1013).
In case that only MCB FEEDBACK (PAGE 1012) is used, this output mirrors the input.
In case that both MCB FEEDBACK (PAGE 1012) and MCB FEEDBACK NEGATIVE (PAGE 1013) are
used and
Feedback match - output indicates MCB position according to feedbacks.
Feedback do not match - output indicates last position when feedbacks matched.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1092


MCB UV Coil

Related FW 1.5.0 Related applications MPTM


LBO ID 48
Description
The output is intended for control of undervoltage coil of Mainsmains circuit breaker.
The output is closed while Mains values are within limits. Breaker closing command is blocked for 1 sec
after the UV coil has been closed to allow the breaker mechanical system to get ready for closing. The
output is opened for 2 seconds when the breaker has to open.

Image 7.34 MCB UV Coil close command

6 back to Logical binary outputs alphabetically

Mode AUTO

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 19
Description
This output is active whenever Controller Mode (page 885) = AUTO, i.e. when LBO NOT IN AUTO (PAGE
1094) is opened.

6 back to Logical binary outputs alphabetically

Mode MAN

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 18
Description
This output is active whenever Controller Mode (page 885) = MAN.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1093


Mode OFF

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 17
Description
This output is active whenever Controller Mode (page 885) = OFF.

6 back to Logical binary outputs alphabetically

LBO: N

NCB Close/Open

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 50
Description
Neutral circuit breaker Close/Open output controls the BESS neutral circuit breaker. It is intended for
contactors – provides a continual active signal if NCB should be closed.

6 back to Logical binary outputs alphabetically

Not In Auto

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1248
Description
This output is closed whenever Controller Mode (page 885) != AUTO, i.e. when LBO MODE AUTO
(PAGE 1093) is opened.

6 back to Logical binary outputs alphabetically

Not Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 63
Description
This output is closed when the BESS is not operable and is not ready to be started.
Closed if:
Controller Mode (page 885) = OFF
LBI START BLOCKING (PAGE 1028) is closed

6 back to Logical binary outputs alphabetically

Not Used

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 286
Description
Output has no function.
6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1094


LBO: O

Operational

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 61
Description
This output is closed when the BESS is ready for operation or is currently in operation.

6 back to Logical binary outputs alphabetically

OVRT Active

Related FW 1.5.0 Related applications MPTM


LBO ID 2314
Description
This output is closed while OVRT Protection is active and stays closed for at least 500 ms.
See Dynamic Support - VRT (page 304) for more information.

6 back to Logical binary outputs alphabetically

OVRT Invalid

Related FW 1.5.0 Related applications MPTM


LBO ID 2351
Description
This output is closed if any value on the y-axis of theOVRT (PAGE 984) curve is equal to or higher than
100% or when the curve is not configured.

6 back to Logical binary outputs alphabetically

OVRTCurveTrip

Related FW 1.5.0 Related applications MPTM


LBO ID 2316
Description
This output is closed when the BESS Voltage rises above the line of OVRT (PAGE 984) curve and opens
when the BESS Voltage drops bellow the line of OVRT (PAGE 984) curve.
This output is always closed at least for 3 seconds.
Note: BESS Voltage L1-N (page 713), BESS Voltage L2-N (page 713) and BESS Voltage L3-N
(page 713) are considered.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1095


LBO: P

P for Q Active

Related FW 1.5.0 Related applications MPTM


LBO ID 1546
Description
This output is closed when BESS P (page 707) is reduced in order to achieve BESS Required Q (page
865).
Note: Output is opened if there is another reduction active.

6 back to Logical binary outputs alphabetically

P Over Frequency Active

Related FW 1.5.0 Related applications MPTM


LBO ID 1183
Description
This output is closed when the BESS P (page 707) starts to be forced to increase due to Power
reduction by over frequency - PoF (page 299).

6 back to Logical binary outputs alphabetically

P Over Frequency Curve Invalid

Related FW 1.5.0 Related applications MPTM


LBO ID 2196
Description
This output is closed when POWER OVER FREQUENCY (PAGE 975) curve is not configured.

6 back to Logical binary outputs alphabetically

P Under Frequency Active

Related FW 1.5.0 Related applications MPTM


LBO ID 2115
Description
This output is closed when the BESS P (page 707) starts to be forced to increase due to Power
increase by under frequency - PuF (page 300).

6 back to Logical binary outputs alphabetically

P Under Frequency Curve Invalid

Related FW 1.5.0 Related applications MPTM


LBO ID 2197
Description
This output is closed when POWER UNDER FREQUENCY (PAGE 976) curve is not configured.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1096


Pave

Related FW 1.5.0 Related applications MPTM


LBO ID 2248
Description
This output is closed when value Pmom/Pave (page 832) is above the curve P Mom/Pave Max (page
972) and stays closed for 5 seconds.

6 back to Logical binary outputs alphabetically

Pave FLS

Related FW 1.5.0 Related applications MPTM


LBO ID 2249
Description
This output is closed when Pave Protection (page 569) != Disabled and LAI PMOM (PAGE 1125) is either
not configured or has invalid value.

6 back to Logical binary outputs alphabetically

Peak Shaving Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2118
Description
This output is closed when Peak shaving (page 1) is activated.

6 back to Logical binary outputs alphabetically

Peripheral Module Comm Fail

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 115
Description
This output is closed when there is no communication with at least one configured peripheral module.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1097


Power Switch

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 290
Description
This is an output from the Power switch function. The behavior of the switch depends on the adjustment
of the setpoints Power Switch On (page 446) and Power Switch Off (page 446)
When the dummy load function is used the switching ON of Power switch is blocked while the BESS isn’t
running and is allowed 30 s after start of the BESS.
The Power Switch is activated when BESS P (page 707) reach relative On Level which is related to the

Image 7.35 Power Switch Example

Note: Setpoints Power Switch On (page 446) and Power Switch Off (page 446) are invisible until
configuration of this LBO.

6 back to Logical binary outputs alphabetically

PQ-C Area Limit

Related FW 1.5.0 Related applications MPTM


LBO ID 2244
Description
This output is closed when the BESS Required Q (page 865) is outside the P FOR Q PQ C (PAGE 980).
See P For Q (page 306) for more information.

6 back to Logical binary outputs alphabetically

PQ-L Area Limit

Related FW 1.5.0 Related applications MPTM


LBO ID 2243
Description
This output is closed when the BESS Required Q (page 865) is outside the P FOR Q PQ L (PAGE 979).
See P For Q (page 306) for more information.

6 back to Logical binary outputs alphabetically

Prestart

Related FW 1.5.0 Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 1098


LBO ID 36
Description
This output can be used for control of any device, which has to be activated just before BESS start. The
output is closed for time period of Prestart Time (page 1) and opens 100 ms before the BESS state
(page 886) = Starting .

6 back to Logical binary outputs alphabetically

Precharge

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2783
Description
This LBO relates to the BESS start sequence decribed in BESS Precharge Types (page 245).
State of precharge.

6 back to Logical binary outputs alphabetically

Precharge Request

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2782
Description
This LBO relates to the BESS start sequence decribed in BESS Precharge Types (page 245).
This LBO initiates the BESS start sequence as a request to get the BESS to the precharge state. The
precharge sequence is considered to be finished once the LBI PRECHARGE FINISHED (PAGE 1016) gets
active. Both signals are mandatory for correct operation.

6 back to Logical binary outputs alphabetically

Process Power Limitation

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2241
Description
This output is closed while BESS P (page 707) is being reduced due to: Import/Export Limitation
(page 1) = Enabled.

6 back to Logical binary outputs alphabetically

PV Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2753
Description
This LBO is active if at least one of PV 01 OPERABLE (PAGE 1018) is operable

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1099


PV/WT Run Request

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2690
Description
This output is used to signalize run request of the PV inverter and it is closed all the time when the CU is
not in the OFF mode.

6 back to Logical binary outputs alphabetically

PVCB Button Echo

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2710
Description
This output is closed for 1 s every time PVCB Button is pressed.

6 back to Logical binary outputs alphabetically

PVCB Close/Open

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2685
Description
The output controls the PV circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 2 seconds to a close or open command, otherwise an alarm Wrn
PVCB Fail (page 1260) is activated.

Image 7.36 PVCB Close command

Image 7.37 Repeated PVCB Close command

InteliNeo 6000 1.5.0 Global Guide 1100


6 back to Logical binary outputs alphabetically

PVCB OFF Coil

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2687
Description
The output is intended for control of open coil of PVCB circuit breaker. The output gives a pulse in the
moment the breaker has to be opened. The pulse lasts until the feedback deactivates, but at least for 2
seconds.

Image 7.38 PVCB OFF Coil command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1101


PVCB ON Coil

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2686
Description
The output is intended for control of close coil of PVCB circuit breaker. The output gives at least 2 second
pulse in the moment the breaker has to be closed.

Image 7.39 PVCB ON Coil close command

InteliNeo 6000 1.5.0 Global Guide 1102


Image 7.40 Repeated PVCB ON coil close command

6 back to Logical binary outputs alphabetically

PVCB Status

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2689
Description
This output indicates the PVCB position as it is internally considered by the controller.
The position is based on PVCB FEEDBACK (PAGE 1025) and PVCB FEEDBACK NEGATIVE (PAGE 1026).
In case that onlyPVCB FEEDBACK (PAGE 1025) is used, this output mirrors the input.
In case that both PVCB FEEDBACK (PAGE 1025) and PVCB FEEDBACK NEGATIVE (PAGE 1026) are
used and
Feedbacks match - output indicates PVCB position according to feedbacks.
Feedbacks do not match - output indicates last position when feedbacks matched.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1103


PVCB UV Coil

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2688
Description
The output is intended for control of undervoltage coil of PV circuit breaker. The output is active the whole
time when the controller is switched on. The output is deactivated for at least 2 seconds in the moment the
breaker has to be switched off.

Image 7.41 PVCB UV Coil close command

Image 7.42 PVCB UV Coil open command

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1104


LBO: R

Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 62
Description
This output is closed when the BESS is stopped and it is possible to start it.
No Alarms level 2 (page 1278) present in the alarmlist
LBI SD OVERRIDE (PAGE 1027) is opened

6 back to Logical binary outputs alphabetically

Reverse Synchronization

Related FW 1.5.0 Related applications MPTM


LBO ID 69
Description
The output is closed when reverse synchronization is active (synchronization via MCB breaker) and
opens when LBO MCB STATUS (PAGE 1092) closes.

6 back to Logical binary outputs alphabetically

ROCOF 1 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1005
Description
This output is closed for 3 seconds when ROCOF1 Protection (page 594) is activated.

6 back to Logical binary outputs alphabetically

ROCOF 2 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2724
Description
This output is closed for 3 seconds when ROCOF2 Protection (page 595) is activated.

6 back to Logical binary outputs alphabetically

ROCOF 3 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2725
Description
This output is closed for 3 seconds whenROCOF1 Protection (page 594) is activated.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1105


ROCOF 4 Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2726
Description
This output is closed for 3 seconds when ROCOF4 Protection (page 597) is activated.

6 back to Logical binary outputs alphabetically

LBO: S

Sd Override

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 962
Description
The output is closed if SD OVERRIDE (PAGE 1027) input is active and opened if SD OVERRIDE (PAGE 1027)
input is inactive. This output is usually used to send information about SD OVERRIDE (PAGE 1027) input
into ECU.

6 back to Logical binary outputs alphabetically

SOC Discharge Disabled

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2701
Description
This output is active when state of charge of the BESS is too low and BESS cannot be discharged
anymore.

6 back to Logical binary outputs alphabetically

SOC Charge Disabled

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2700
Description
This output is active when state of charge of the BESS is too high and BESS cannot be charged
anymore.

6 back to Logical binary outputs alphabetically

Soft Load

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 71
Description
This output is closed when BCB closes and BESS is being soft loaded via Load Ramp (page 477). Later
change of BESS P (page 707) does not close this output again.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1106


Soft Unload

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 73
Description
This LBO is active while controller perform soft unloading.
This output is closed when BCB is requested to be opened and BESS is being soft unloaded via Soft
Unload Ramp (page 568).

6 back to Logical binary outputs alphabetically

Start Blocked

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 1226
Description
This output is closed while start of the BESS is blocked due to at least one of these reasons:
LBI START BLOCKING (PAGE 1028) is closed
Application Mode (page 885) = MPTM, Controller Mode (page 885) = AUTO, LBO MAINS/BUS
HEALTHY (PAGE 1090) is opened and LBI FORCE PARALLEL (PAGE 997) is closed

6 back to Logical binary outputs alphabetically

Start Button Echo

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 33
Description
This output is closed for 1 s every time Start Button is pressed.

6 back to Logical binary outputs alphabetically

Starting

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 65
Description
This output is closed at the beginning of the Prestart Time (page 1) period and opens after starting
phase is finished or when Sd Start Fail (page 1289) alarm is activated.

6 back to Logical binary outputs alphabetically

Stop Button Echo

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 32
Description
This output is closed for 1 s every time Stop Button is pressed.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1107


Stopping

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 75
Description
This output i closed during stopping sequence after stop command is received and opens after the BESS
is considered to be stopped.

6 back to Logical binary outputs alphabetically

Sync To Mains Allowed

MPTM
Related FW 1.5.0 Related applications

LBO ID 1057
Description
This output is closed when synchronization to the mains is allowed or Breaker state (page 886) =
ParalOper.
See Synchronization & Connection Conditions (page 307) for more information.

6 back to Logical binary outputs alphabetically

System Ready

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 86
Description
This output is closed if the controller group has enough capacity to fulfill the requested power reserve. If
the output is opened, then the group has not enough capacity to fulfill the reserve even if all the units will
run.
Note: Fulfilled reserve means that Available Nominal Power (page 859) is above the Minimal
Running Nominal Power (page 859)

6 back to Logical binary outputs alphabetically

System Reserve OK

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 87
Description
This output is closed when Actual Reserve (page 856) is higher than the Start Reserve (page 857).

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1108


LBO: U

UQ-C Area Limit

Related FW 1.5.0 Related applications MPTM


LBO ID 2246
Description
This output is closed when the BESS Required Q (page 865) is outside the P FOR Q UQ C (PAGE 978).
See P For Q (page 306) for more information.

6 back to Logical binary outputs alphabetically

UQ-L Area Limit

Related FW 1.5.0 Related applications MPTM


LBO ID 2245
Description
This output is closed when the BESS Required Q (page 865) is outside the P FOR Q UQ L (PAGE 977).
See P For Q (page 306) for more information.

6 back to Logical binary outputs alphabetically

LBO: V

Vector Shift Active

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 93
Description
This output is closed for 3 seconds when Vector Shift Protection (page 593) is activated.

6 back to Logical binary outputs alphabetically

Voltage Down

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 55
Description
This output together with the complementary output VOLTAGE UP (PAGE 1110) are designed for voltage
and power factor control of the BESS, where the BESS inverter regulator does not support analogue
control.

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1109


Voltage Up

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 54
Description
This output together with the complementary output VOLTAGE DOWN (PAGE 1109) are designed for
voltage and power factor control of the BESS, where the BESS inverter regulator does not support
analogue control.

6 back to Logical binary outputs alphabetically

LBO: W

WT Operable

Related FW 1.5.0 Related applications MINT, MPTM


LBO ID 2754
Description
This LBO is active if at least one of WT 01 OPERABLE (PAGE 1046) is operable

6 back to Logical binary outputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1110


9.1.8 Logical analog inputs
What Logical analog inputs are:
Logical analog inputs are inputs for analog values.

Alphabetical groups of Logical analog inputs


LAI: B 1115
LAI: C 1117
LAI: D 1120
LAI: I 1120
LAI: L 1121
LAI: M 1123
LAI: P 1124
LAI: Q 1147
LAI: T 1151
LAI: U 1153
LAI: W 1173

For full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically (page 1112).

InteliNeo 6000 1.5.0 Global Guide 1111


Logical analog inputs alphabetically

LAI: B 1115 Irradiation of PV Array 1 1122 PV 06 Actual Q 1129


Battery Discharge kWh 1115 Irradiation of PV Array 2 1122 PV 06 kWh 1129
Battery Charge kWh 1115 Irradiation of PV Array 3 1123 PV 06 Nominal P 1129
Battery Charging Cycles 1115 Irradiation of PV Array 4 1123 PV 07 Actual P 1129
BESSCapacity 1115 LAI: M 1123 PV 07 Actual Q 1129
BESS Max Discharge P 1115 Mains Import PV 07 kWh 1130
BESS Max Charge P 1116 P Monitoring 1123 PV 07 Nominal P 1130
BESS P Request 1116 Mains Import PV 08 Actual P 1130
Q Monitoring 1123
BESS Q Request 1116 PV 08 Actual Q 1130
Mains Measurement P 1124
BESS SOC 1116 PV 08 kWh 1130
Mains Measurement Q 1124
BESS Temperature 1116 PV 08 Nominal P 1130
LAI: P 1124
LAI: C 1117 PV 09 Actual P 1131
PF Control: ANEXT Base
Cold Temp 1 1117 PV 09 Actual Q 1131
PF 1124
Cold Temp 2 1117 PV 09 kWh 1131
PF Control: ANEXT
Cold Temp 3 1117 PV 09 Nominal P 1131
Imp/Exp PF 1125
Cold Temp 4 1118 PV 10 Actual P 1131
Pmom 1125
Cold Temp 5 1118 PV 10 Actual Q 1131
PV 01 Actual P 1125
Cold Temp 6 1118 PV 10 kWh 1132
PV 01 Actual Q 1125
Cold Temp 7 1119 PV 10 Nominal P 1132
PV 01 kWh 1126
Cold Temp 8 1119 PV 11 Actual P 1132
PV 01 Nominal P 1126
Cold Temp 9 1119 PV 11 Actual Q 1132
PV 02 Actual P 1126
Cold Temp 10 1120 PV 11 kWh 1132
PV 02 Actual Q 1126
LAI: D 1120 PV 11 Nominal P 1132
PV 02 kWh 1126
Dynamic Spinning PV 12 Actual P 1133
PV 02 Nominal P 1126
Reserve 1120
PV 03 Actual P 1127 PV 12 Actual Q 1133
Dynamic Spinning
PV 03 Actual Q 1127 PV 12 kWh 1133
Reserve Offset 1120
PV 03 kWh 1127 PV 12 Nominal P 1133
LAI: I 1120
PV 03 Nominal P 1127 PV 13 Actual P 1133
Irradiation of PV Array 1 1120
PV 04 Actual P 1127 PV 13 Actual Q 1133
Irradiation of PV Array 2 1121
PV 04 Actual Q 1127 PV 13 kWh 1134
Irradiation of PV Array 3 1121
PV 04 kWh 1128 PV 13 Nominal P 1134
Irradiation of PV Array 4 1121
PV 04 Nominal P 1128 PV 14 Actual P 1134
LAI: L 1121
Load Control: ANEXT PV 05 Actual P 1128 PV 14 Actual Q 1134
Baseload 1121 PV 05 Actual Q 1128 PV 14 kWh 1134
Load Control: ANEXT PV 05 kWh 1128 PV 14 Nominal P 1134
Imp/Exp Load 1122 PV 05 Nominal P 1128 PV 15 Actual P 1135
Load Reduction 1122 PV 06 Actual P 1129 PV 15 Actual Q 1135

InteliNeo 6000 1.5.0 Global Guide 1112


PV 15 kWh 1135 PV 25 Actual Q 1141 Qref/Ulim: ANEXT
PV 15 Nominal P 1135 PV 25 kWh 1142 Qref/Pnom B Q 1150

PV 16 Actual P 1135 PV 25 Nominal P 1142 Qref/Ulim: ANEXT


Qref/Pnom I/E Q 1151
PV 16 Actual Q 1135 PV 26 Actual P 1142
LAI: T 1151
PV 16 kWh 1136 PV 26 Actual Q 1142
TestF 1151
PV 16 Nominal P 1136 PV 26 kWh 1142
TestP 1152
PV 17 Actual P 1136 PV 26 Nominal P 1142
TestQ 1152
PV 17 Actual Q 1136 PV 17 Actual P 1143
TestU 1152
PV 17 kWh 1136 PV 27 Actual Q 1143
LAI: U 1153
PV 17 Nominal P 1136 PV 27 kWh 1143
Uni Gen 01 Actual P 1153
PV 18 Actual P 1137 PV 27 Nominal P 1143
Uni Gen 01 Actual Q 1153
PV 18 Actual Q 1137 PV 28 Actual P 1143
Uni Gen 01 Fuel 1153
PV 18 kWh 1137 PV 28 Actual Q 1143
Uni Gen 01 kWh 1153
PV 18 Nominal P 1137 PV 28 kWh 1144
Uni Gen 01 Nominal P 1154
PV 19 Actual P 1137 PV 28 Nominal P 1144
Uni Gen 02 Actual P 1154
PV 19 Actual Q 1137 PV 29 Actual P 1144
Uni Gen 02 Actual Q 1154
PV 19 kWh 1138 PV 29 Actual Q 1144
Uni Gen 02 Fuel 1154
PV 19 Nominal P 1138 PV 29 kWh 1144
Uni Gen 02 kWh 1155
PV 20 Actual P 1138 PV 29 Nominal P 1144
Uni Gen 02 Nom P 1155
PV 20 Actual Q 1138 PV 30 Actual P 1145
Uni Gen 03 Actual P 1155
PV 20 kWh 1138 PV 30 Actual Q 1145
Uni Gen 03 Actual Q 1155
PV 20 Nominal P 1138 PV 30 kWh 1145
Uni Gen 03 Fuel 1156
PV 21 Actual P 1139 PV 30 Nominal P 1145
Uni Gen 03 kWh 1156
PV 21 Actual Q 1139 PV 31 Actual P 1145
Uni Gen 03 Nom P 1156
PV 21 kWh 1139 PV 31 Actual Q 1145
Uni Gen 04 Actual P 1156
PV 21 Nominal P 1139 PV 31 kWh 1146
Uni Gen 04 Actual Q 1157
PV 22 Actual P 1139 PV 31 Nominal P 1146
Uni Gen 04 Fuel 1157
PV 22 Actual Q 1139 PV 32 Actual P 1146
Uni Gen 04 kWh 1157
PV 22 kWh 1140 PV 32 Actual Q 1146
Uni Gen 04 Nom P 1157
PV 22 Nominal P 1140 PV 32 kWh 1146
Uni Gen 05 Actual P 1158
PV 23 Actual P 1140 PV 32 Nominal P 1146
Uni Gen 05 Actual Q 1158
PV 23 Actual Q 1140 LAI: Q 1147
Uni Gen 05 Fuel 1158
PV 23 kWh 1140 Q Control: ANEXT Base
Q 1147 Uni Gen 05 kWh 1158
PV 23 Nominal P 1140
Q Control: ANEXT Uni Gen 05 Nom P 1159
PV 24 Actual P 1141
Imp/Exp Q 1147 Uni Gen 06 Actual P 1159
PV 24 Actual Q 1141
Q(Um): 0 Ref ANEXT Uni Gen 06 Actual Q 1159
PV 24 kWh 1141
Base Q 1148 Uni Gen 06 Fuel 1159
PV 24 Nominal P 1141
Q(Um): 0 Ref ANEXT Uni Gen 06 kWh 1160
PV 25 Actual P 1141 Imp/Exp Q 1149 Uni Gen 06 Nom P 1160

InteliNeo 6000 1.5.0 Global Guide 1113


Uni Gen 07 Actual P 1160 Uni Gen 14 Nom P 1170 WT 07 Nominal P 1177
Uni Gen 07 Actual Q 1160 Uni Gen 15 Actual P 1170 WT 08 Actual P 1177
Uni Gen 07 Fuel 1161 Uni Gen 15 Actual Q 1170 WT 08 Actual Q 1178
Uni Gen 07 kWh 1161 Uni Gen 15 Fuel 1171 WT 08 kWh 1178
Uni Gen 07 Nom P 1161 Uni Gen 15 kWh 1171 WT 08 Nominal P 1178
Uni Gen 08 Actual P 1161 Uni Gen 15 Nom P 1171 6 back to Controller objects
Uni Gen 08 Actual Q 1162 Uni Gen 16 Actual P 1171
Uni Gen 08 Fuel 1162 Uni Gen 16 Actual Q 1172
Uni Gen 08 kWh 1162 Uni Gen 16 Fuel 1172
Uni Gen 08 Nom P 1162 Uni Gen 16 kWh 1172
Uni Gen 09 Actual P 1163 Uni Gen 16 Nom P 1172
Uni Gen 09 Actual Q 1163 LAI: W 1173
Uni Gen 09 Fuel 1163 WT 01 Actual P 1173
Uni Gen 09 kWh 1163 WT 01 Actual Q 1173
Uni Gen 09 Nom P 1164 WT 01 kWh 1173
Uni Gen 10 Actual P 1164 WT 01 Nominal P 1173
Uni Gen 10 Actual Q 1164 WT 02 Actual P 1173
Uni Gen 10 Fuel 1164 WT 02 Actual Q 1174
Uni Gen 10 kWh 1165 WT 02 kWh 1174
Uni Gen 10 Nom P 1165 WT 02 Nominal P 1174
Uni Gen 11 Actual P 1165 WT 03 Actual P 1174
Uni Gen 11 Actual Q 1165 WT 03 Actual Q 1174
Uni Gen 11 Fuel 1166 WT 03 kWh 1174
Uni Gen 11 kWh 1166 WT 03 Nominal P 1175
Uni Gen 11 Nom P 1166 WT 04 Actual P 1175
Uni Gen 12 Actual P 1166 WT 04 Actual Q 1175
Uni Gen 12 Actual Q 1167 WT 04 kWh 1175
Uni Gen 12 Fuel 1167 WT 04 Nominal P 1175
Uni Gen 12 kWh 1167 WT 05 Nominal P 1175
Uni Gen 12 Nom P 1167 WT 05 Actual Q 1176
Uni Gen 13 Actual P 1168 WT 05 Actual P 1176
Uni Gen 13 Actual Q 1168 WT 05 kWh 1176
Uni Gen 13 Fuel 1168 WT 06 Actual P 1176
Uni Gen 13 kWh 1168 WT 06 Actual Q 1176
Uni Gen 13 Nom P 1169 WT 06 kWh 1176
Uni Gen 14 Actual P 1169 WT 06 Nominal P 1177
Uni Gen 14 Actual Q 1169 WT 07 Actual P 1177
Uni Gen 14 Fuel 1169 WT 07 Actual Q 1177
Uni Gen 14 kWh 1170 WT 07 kWh 1177

InteliNeo 6000 1.5.0 Global Guide 1114


LAI: B

Battery Discharge kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 427
Description
This LAI defines the amount of discharged energy from the BESS and it is used as source for statistic
values.

6 back to Logical analog inputs alphabetically

Battery Charge kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 426
Description
This LAI defines the amount of charged energy to the BESS and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

Battery Charging Cycles

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 428
Description
This analog input is used as source for the statistic value Batt. Charging Cycles (page 873) and for the
function Daily Battery Cycles Control (page 241).

6 back to Logical analog inputs alphabetically

BESSCapacity

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 370
Description
Capacity of the BESS.

6 back to Logical analog inputs alphabetically

BESS Max Discharge P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 425
Description
This LAI defines maximal allowed discharge power of the BESS.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1115


BESS Max Charge P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 424
Description
Maximal allowed charging power of the BESS.

6 back to Logical analog inputs alphabetically

BESS P Request

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 420
Description
LAI is used for adjusting BESS Power Request while Charging / Discarding process.

6 back to Logical analog inputs alphabetically

BESS Q Request

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 429
Description
LAI is used for adjusting BESS Reactive Power Request while Charging / Discarding process.

6 back to Logical analog inputs alphabetically

BESS SOC

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 368
Description
This LAI is used to monitor actual state of charge of the BESS.

6 back to Logical analog inputs alphabetically

BESS Temperature

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 371
Description
This LAI is used as input for temperature of the BESS.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1116


LAI: C

Cold Temp 1

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 56
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 1.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

Cold Temp 2

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 57
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 2.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

Cold Temp 3

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 58
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 3.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1117


Cold Temp 4

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 59
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 4.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

Cold Temp 5

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 341
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 5.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

Cold Temp 6

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 342
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 6.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1118


Cold Temp 7

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 343
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 7.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

Cold Temp 8

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 344
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 8.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

Cold Temp 9

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 418
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 9.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1119


Cold Temp 10

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 419
Description
This LAI is used for compensation of thermocouple temperature measurement. It is used when there is a
significant temperature difference between on-board terminal and a module terminal (such as Inteli
AIN8TC). This input compensate the CAN module configured with address (index) 10.
Note: The compensation is only for thermocouples without internal compensation "Thermo (nc) …" (not
cold junction compensation).

6 back to Logical analog inputs alphabetically

LAI: D

Dynamic Spinning Reserve

Related FW 1.5.0 Related applications MINT


LAI ID 192
Description
This LAI is used as source of the value Dynamic Spinning Reserve (page 857).

6 back to Logical analog inputs alphabetically

Dynamic Spinning Reserve Offset

Related FW 1.5.0 Related applications MINT


LAI ID 233
Description
This LAI is used as source of the value Dynamic Spinning Reserve Offset (page 857).

6 back to Logical analog inputs alphabetically

LAI: I

Irradiation of PV Array 1

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 544
Description
This parameter represents the irradiation data for PV Array 1, providing information about the amount of
sunlight received at the specific location within the microgrid.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1120


Irradiation of PV Array 2

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 545
Description
This parameter represents the irradiation data for PV Array 2, offering insights into the amount of sunlight
received at the specific location within the microgrid.

6 back to Logical analog inputs alphabetically

Irradiation of PV Array 3

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 546
Description
This parameter provides irradiation data for PV Array 3, indicating the amount of sunlight received at the
specific location within the microgrid.

6 back to Logical analog inputs alphabetically

Irradiation of PV Array 4

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 547
Description
This parameter offers irradiation data for PV Array 4, providing information about the amount of sunlight
received at the specific location within the microgrid.

6 back to Logical analog inputs alphabetically

LAI: L

Load Control: ANEXT Baseload

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 1
Description
This LAI is source value for control of Active Power if Load Request Source (page 353) = Analog
External Value.
The Baseload is active if
MINT: #System Load Control PTM (page 354) = Baseload
MPTM: Load Control PTM Mode (page 352) = Baseload

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1121


Load Control: ANEXT Imp/Exp Load

Related FW 1.5.0 Related applications MPTM


LAI ID 2
Description
This LAI is source value for control of Active Power if Load Request Source (page 353) = Analog
External Value.
The Import/Export is active if Load Control PTM Mode (page 352) = Import/Export.

6 back to Logical analog inputs alphabetically

Load Reduction

Related FW 1.5.0 Related applications MPTM


LAI ID 193
Description
This LAI adjusts maximal allowed load of the BESS while Setpoiont LOAD REDUCTION (PAGE 549) is
Enabled and LBI LOAD REDUCTION ENABLE (PAGE 1007) is closed.
Always the lowest load defined by this LAI or by LBIs, LOAD REDUCTION 1 (PAGE 1006), LOAD REDUCTION
2 (PAGE 1006), etc. is allowed.
Note: The value of this setpoint relates to Installed Power (page 375) only if Installed Power
(page 375) != OFF, otherwise it relates to Nominal power (page 375).

6 back to Logical analog inputs alphabetically

Irradiation of PV Array 1

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 544
Description
This parameter represents the irradiation data for PV Array 1, providing information about the amount of
sunlight received at the specific location within the microgrid.

6 back to Logical analog inputs alphabetically

Irradiation of PV Array 2

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 545
Description
This parameter represents the irradiation data for PV Array 2, offering insights into the amount of sunlight
received at the specific location within the microgrid.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1122


Irradiation of PV Array 3

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 546
Description
This parameter provides irradiation data for PV Array 3, indicating the amount of sunlight received at the
specific location within the microgrid.

6 back to Logical analog inputs alphabetically

Irradiation of PV Array 4

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 547
Description
This parameter offers irradiation data for PV Array 4, providing information about the amount of sunlight
received at the specific location within the microgrid.

6 back to Logical analog inputs alphabetically

LAI: M

Mains Import P Monitoring

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 430
Description
This analog input is used as source for monitoring of Mains active power import which is used in
calculations.

6 back to Logical analog inputs alphabetically

Mains Import Q Monitoring

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 431
Description
This analog input is used as source for monitoring of Mains reactive power import which is used in
calculations.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1123


Mains Measurement P

Related FW 1.5.0 Related applications MPTM


LAI ID 5
Description
This LAI is designed for Mains Import Measurement (page 175), when Mains Measurement P (page
364) = Analog Input. Value from this input is used in load transfer from Mains to BESS.
Load transfer is considered to be finished when this value is lower than Mains Unload MCB Open
Window (page 476)

6 back to Logical analog inputs alphabetically

Mains Measurement Q

Related FW 1.5.0 Related applications MPTM


LAI ID 6
Description
This LAI is designed for Mains Import Measurement (page 175), when Mains Measurement Q (page
365) = Analog Input. Value from this input is used in load transfer from Mains to BESS.
Load transfer is considered to be finished when this value is lower than Mains Unload MCB Open
Window (page 476)

6 back to Logical analog inputs alphabetically

LAI: P

PF Control: ANEXT Base PF

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 3
Description
This LAI is a source value for control of the Power Factor if PF/Q Request Source (page 357) = Analog
External Value .
The Base PF is active if
MINT: #System PF Control PTM (page 358) = Base PF
MPTM: PF/Q Control PTM Mode (page 356) = PF Control and PF/Q Regulation Type (page
358) = Base PF/Q Control

Analog value Cos phi factor


<0.600 0.6L
0.600 .. 1.000 0.6L .. 1.00
1.001 .. 1.200 0.99C .. 0.80C

Note: Always use a three decimal number for this LAI. Thus the range for this LAI is 0.600 to 1.200.

Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, alarm Wrn PF Control Fail (page 1258) is activated.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1124


PF Control: ANEXT Imp/Exp PF

Related FW 1.5.0 Related applications MPTM


LAI ID 4
Description
This LAI is a source value for control of the Power Factor if PF/Q Request Source (page 357) = Analog
External Value.
The Import/Export PF is active if PF/Q Control PTM Mode (page 356) = PF Control and PF/Q
Regulation Type (page 358) = Import/Export PF/Q Control.

Analog value Cos phi factor


<0.600 0.6L
0.600 .. 1.000 0.6L .. 1.00
1.001 .. 1.200 0.99C .. 0.80C

Note: Always use a three decimal number for this LAI.

Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, alarm Wrn PF Control Fail (page 1258) is activated.

6 back to Logical analog inputs alphabetically

Pmom

Related FW 1.5.0 Related applications MPTM


LAI ID 340
Description
This LAI is used for receiving exported power measured in all 3 phases and is used during Pave (page
309) function. The value can be received via CAN Intercontroller Communication (page 132) from
InteliPro Sync, InteliPro, InteliMains or connected to physical analog input.

6 back to Logical analog inputs alphabetically

PV 01 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 358
Description
This LAI is designed to monitor actual power of the PV 1.

6 back to Logical analog inputs alphabetically

PV 01 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 359
Description
This LAI is designed to monitor actual reactive power of the PV 1.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1125


PV 01 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 361
Description
This LAI defines the amount of energy produced by PV 1 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 01 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 360
Description
This LAI is used to define nominal power of the PV 1 used in the system.

6 back to Logical analog inputs alphabetically

PV 02 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 449
Description
This LAI is designed to monitor actual power of the PV 2.

6 back to Logical analog inputs alphabetically

PV 02 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 464
Description
This LAI is designed to monitor actual reactive power of the PV 2.

6 back to Logical analog inputs alphabetically

PV 02 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 479
Description
This LAI defines the amount of energy produced by PV 2 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 02 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 434
Description
This LAI is used to define nominal power of the PV 2 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1126


PV 03 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 450
Description
This LAI is designed to monitor actual power of the PV 3.

6 back to Logical analog inputs alphabetically

PV 03 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 465
Description
This LAI is designed to monitor actual reactive power of the PV 3.

6 back to Logical analog inputs alphabetically

PV 03 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 480
Description
This LAI defines the amount of energy produced by PV 3 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 03 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 435
Description
This LAI is used to define nominal power of the PV 3 used in the system.

6 back to Logical analog inputs alphabetically

PV 04 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 451
Description
This LAI is designed to monitor actual power of the PV 4.

6 back to Logical analog inputs alphabetically

PV 04 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 466
Description
This LAI is designed to monitor actual reactive power of the PV 4.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1127


PV 04 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 481
Description
This LAI defines the amount of energy produced by PV 4 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 04 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 436
Description
This LAI is used to define nominal power of the PV 4 used in the system.

6 back to Logical analog inputs alphabetically

PV 05 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 452
Description
This LAI is designed to monitor actual power of the PV 5.

6 back to Logical analog inputs alphabetically

PV 05 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 467
Description
This LAI is designed to monitor actual reactive power of the PV 5.

6 back to Logical analog inputs alphabetically

PV 05 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 482
Description
This LAI defines the amount of energy produced by PV 5 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 05 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 437
Description
This LAI is used to define nominal power of the PV 5 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1128


PV 06 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 453
Description
This LAI is designed to monitor actual power of the PV 6.

6 back to Logical analog inputs alphabetically

PV 06 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 468
Description
This LAI is designed to monitor actual reactive power of the PV 6.

6 back to Logical analog inputs alphabetically

PV 06 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 483
Description
This LAI defines the amount of energy produced by PV 6 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 06 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 438
Description
This LAI is used to define nominal power of the PV 6 used in the system.

6 back to Logical analog inputs alphabetically

PV 07 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 454
Description
This LAI is designed to monitor actual power of the PV 7.

6 back to Logical analog inputs alphabetically

PV 07 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 469
Description
This LAI is designed to monitor actual reactive power of the PV 7.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1129


PV 07 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 484
Description
This LAI defines the amount of energy produced by PV 7 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 07 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 439
Description
This LAI is used to define nominal power of the PV 7 used in the system.

6 back to Logical analog inputs alphabetically

PV 08 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 455
Description
This LAI is designed to monitor actual power of the PV 8.

6 back to Logical analog inputs alphabetically

PV 08 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 470
Description
This LAI is designed to monitor actual reactive power of the PV 8.

6 back to Logical analog inputs alphabetically

PV 08 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 485
Description
This LAI defines the amount of energy produced by PV 8 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 08 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 440
Description
This LAI is used to define nominal power of the PV 8 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1130


PV 09 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 456
Description
This LAI is designed to monitor actual power of the PV 9.

6 back to Logical analog inputs alphabetically

PV 09 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 471
Description
This LAI is designed to monitor actual reactive power of the PV 9.

6 back to Logical analog inputs alphabetically

PV 09 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 486
Description
This LAI defines the amount of energy produced by PV 9 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 09 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 441
Description
This LAI is used to define nominal power of the PV 9 used in the system.

6 back to Logical analog inputs alphabetically

PV 10 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 457
Description
This LAI is designed to monitor actual power of the PV 10.

6 back to Logical analog inputs alphabetically

PV 10 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 472
Description
This LAI is designed to monitor actual reactive power of the PV 10.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1131


PV 10 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 487
Description
This LAI defines the amount of energy produced by PV 10 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 10 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 442
Description
This LAI is used to define nominal power of the PV 10 used in the system.

6 back to Logical analog inputs alphabetically

PV 11 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 458
Description
This LAI is designed to monitor actual power of the PV 11.

6 back to Logical analog inputs alphabetically

PV 11 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 473
Description
This LAI is designed to monitor actual reactive power of the PV 11.

6 back to Logical analog inputs alphabetically

PV 11 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 488
Description
This LAI defines the amount of energy produced by PV 11 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 11 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 443
Description
This LAI is used to define nominal power of the PV 11 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1132


PV 12 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 459
Description
This LAI is designed to monitor actual power of the PV 12.

6 back to Logical analog inputs alphabetically

PV 12 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 474
Description
This LAI is designed to monitor actual reactive power of the PV 12.

6 back to Logical analog inputs alphabetically

PV 12 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 489
Description
This LAI defines the amount of energy produced by PV 12 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 12 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 444
Description
This LAI is used to define nominal power of the PV 12 used in the system.

6 back to Logical analog inputs alphabetically

PV 13 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 460
Description
This LAI is designed to monitor actual power of the PV 13.

6 back to Logical analog inputs alphabetically

PV 13 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 475
Description
This LAI is designed to monitor actual reactive power of the PV 13.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1133


PV 13 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 490
Description
This LAI defines the amount of energy produced by PV 13 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 13 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 445
Description
This LAI is used to define nominal power of the PV 13 used in the system.

6 back to Logical analog inputs alphabetically

PV 14 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 461
Description
This LAI is designed to monitor actual power of the PV 14.

6 back to Logical analog inputs alphabetically

PV 14 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 476
Description
This LAI is designed to monitor actual reactive power of the PV 14.

6 back to Logical analog inputs alphabetically

PV 14 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 491
Description
This LAI defines the amount of energy produced by PV 14 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 14 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 446
Description
This LAI is used to define nominal power of the PV 14 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1134


PV 15 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 462
Description
This LAI is designed to monitor actual power of the PV 15.

6 back to Logical analog inputs alphabetically

PV 15 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 477
Description
This LAI is designed to monitor actual reactive power of the PV 15.

6 back to Logical analog inputs alphabetically

PV 15 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 492
Description
This LAI defines the amount of energy produced by PV 15 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 15 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 447
Description
This LAI is used to define nominal power of the PV 15 used in the system.

6 back to Logical analog inputs alphabetically

PV 16 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 463
Description
This LAI is designed to monitor actual power of the PV 16.

6 back to Logical analog inputs alphabetically

PV 16 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 478
Description
This LAI is designed to monitor actual reactive power of the PV 16.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1135


PV 16 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 493
Description
This LAI defines the amount of energy produced by PV 16 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 16 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 448
Description
This LAI is used to define nominal power of the PV 16 used in the system.

6 back to Logical analog inputs alphabetically

PV 17 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 673
Description
This LAI is designed to monitor actual power of the PV 17.

6 back to Logical analog inputs alphabetically

PV 17 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 689
Description
This LAI is designed to monitor actual reactive power of the PV 17.

6 back to Logical analog inputs alphabetically

PV 17 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 705
Description
This LAI defines the amount of energy produced by PV 17 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 17 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 657
Description
This LAI is used to define nominal power of the PV 17 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1136


PV 18 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 674
Description
This LAI is designed to monitor actual power of the PV 18.

6 back to Logical analog inputs alphabetically

PV 18 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 478
Description
This LAI is designed to monitor actual reactive power of the PV 18.

6 back to Logical analog inputs alphabetically

PV 18 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 706
Description
This LAI defines the amount of energy produced by PV 18 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 18 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 658
Description
This LAI is used to define nominal power of the PV 18 used in the system.

6 back to Logical analog inputs alphabetically

PV 19 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 675
Description
This LAI is designed to monitor actual power of the PV 19.

6 back to Logical analog inputs alphabetically

PV 19 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 691
Description
This LAI is designed to monitor actual reactive power of the PV 19.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1137


PV 19 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 707
Description
This LAI defines the amount of energy produced by PV 19 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 19 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 659
Description
This LAI is used to define nominal power of the PV 19 used in the system.

6 back to Logical analog inputs alphabetically

PV 20 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 676
Description
This LAI is designed to monitor actual power of the PV 20.

6 back to Logical analog inputs alphabetically

PV 20 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 692
Description
This LAI is designed to monitor actual reactive power of the PV 20.

6 back to Logical analog inputs alphabetically

PV 20 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 708
Description
This LAI defines the amount of energy produced by PV 20 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 20 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 660
Description
This LAI is used to define nominal power of the PV 20 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1138


PV 21 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 677
Description
This LAI is designed to monitor actual power of the PV 21.

6 back to Logical analog inputs alphabetically

PV 21 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 693
Description
This LAI is designed to monitor actual reactive power of the PV 21.

6 back to Logical analog inputs alphabetically

PV 21 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 709
Description
This LAI defines the amount of energy produced by PV 21 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 21 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 661
Description
This LAI is used to define nominal power of the PV 21 used in the system.

6 back to Logical analog inputs alphabetically

PV 22 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 678
Description
This LAI is designed to monitor actual power of the PV 22.

6 back to Logical analog inputs alphabetically

PV 22 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 694
Description
This LAI is designed to monitor actual reactive power of the PV 22.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1139


PV 22 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 710
Description
This LAI defines the amount of energy produced by PV 22 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 22 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 662
Description
This LAI is used to define nominal power of the PV 22 used in the system.

6 back to Logical analog inputs alphabetically

PV 23 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 679
Description
This LAI is designed to monitor actual power of the PV 23.

6 back to Logical analog inputs alphabetically

PV 23 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 695
Description
This LAI is designed to monitor actual reactive power of the PV 23.

6 back to Logical analog inputs alphabetically

PV 23 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 711
Description
This LAI defines the amount of energy produced by PV 23 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 23 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 663
Description
This LAI is used to define nominal power of the PV 23 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1140


PV 24 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 680
Description
This LAI is designed to monitor actual power of the PV 24.

6 back to Logical analog inputs alphabetically

PV 24 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 696
Description
This LAI is designed to monitor actual reactive power of the PV 24.

6 back to Logical analog inputs alphabetically

PV 24 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 712
Description
This LAI defines the amount of energy produced by PV 24 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 24 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 664
Description
This LAI is used to define nominal power of the PV 24 used in the system.

6 back to Logical analog inputs alphabetically

PV 25 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 681
Description
This LAI is designed to monitor actual power of the PV 25.

6 back to Logical analog inputs alphabetically

PV 25 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 697
Description
This LAI is designed to monitor actual reactive power of the PV 25.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1141


PV 25 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 713
Description
This LAI defines the amount of energy produced by PV 25 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 25 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 665
Description
This LAI is used to define nominal power of the PV 25 used in the system.

6 back to Logical analog inputs alphabetically

PV 26 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 682
Description
This LAI is designed to monitor actual power of the PV 26.

6 back to Logical analog inputs alphabetically

PV 26 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 698
Description
This LAI is designed to monitor actual reactive power of the PV 26.

6 back to Logical analog inputs alphabetically

PV 26 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 714
Description
This LAI defines the amount of energy produced by PV 26 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 26 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 666
Description
This LAI is used to define nominal power of the PV 26 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1142


PV 17 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 683
Description
This LAI is designed to monitor actual power of the PV 27.

6 back to Logical analog inputs alphabetically

PV 27 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 699
Description
This LAI is designed to monitor actual reactive power of the PV 27.

6 back to Logical analog inputs alphabetically

PV 27 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 715
Description
This LAI defines the amount of energy produced by PV 27 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 27 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 667
Description
This LAI is used to define nominal power of the PV 27 used in the system.

6 back to Logical analog inputs alphabetically

PV 28 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 684
Description
This LAI is designed to monitor actual power of the PV 28.

6 back to Logical analog inputs alphabetically

PV 28 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 700
Description
This LAI is designed to monitor actual reactive power of the PV 28.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1143


PV 28 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 716
Description
This LAI defines the amount of energy produced by PV 28 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 28 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 668
Description
This LAI is used to define nominal power of the PV 28 used in the system.

6 back to Logical analog inputs alphabetically

PV 29 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 685
Description
This LAI is designed to monitor actual power of the PV 29.

6 back to Logical analog inputs alphabetically

PV 29 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 701
Description
This LAI is designed to monitor actual reactive power of the PV 29.

6 back to Logical analog inputs alphabetically

PV 29 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 717
Description
This LAI defines the amount of energy produced by PV 29 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 29 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 669
Description
This LAI is used to define nominal power of the PV 29 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1144


PV 30 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 686
Description
This LAI is designed to monitor actual power of the PV 30.

6 back to Logical analog inputs alphabetically

PV 30 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 702
Description
This LAI is designed to monitor actual reactive power of the PV 30.

6 back to Logical analog inputs alphabetically

PV 30 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 718
Description
This LAI defines the amount of energy produced by PV 30 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 30 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 670
Description
This LAI is used to define nominal power of the PV 30 used in the system.

6 back to Logical analog inputs alphabetically

PV 31 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 687
Description
This LAI is designed to monitor actual power of the PV 31.

6 back to Logical analog inputs alphabetically

PV 31 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 703
Description
This LAI is designed to monitor actual reactive power of the PV 31.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1145


PV 31 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 719
Description
This LAI defines the amount of energy produced by PV 31 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 31 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 671
Description
This LAI is used to define nominal power of the PV 31 used in the system.

6 back to Logical analog inputs alphabetically

PV 32 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 688
Description
This LAI is designed to monitor actual power of the PV 32.

6 back to Logical analog inputs alphabetically

PV 32 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 704
Description
This LAI is designed to monitor actual reactive power of the PV 32.

6 back to Logical analog inputs alphabetically

PV 32 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 720
Description
This LAI defines the amount of energy produced by PV 32 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

PV 32 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 672
Description
This LAI is used to define nominal power of the PV 32 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1146


LAI: Q

Q Control: ANEXT Base Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 171
Description
This LAI is a source value for control of the Power Factor if PF/Q Request Source (page 357) = Analog
External Value .
The Base Q is active if
MINT: #System PF Control PTM (page 358) = Base Q
MPTM: PF/Q Control PTM Mode (page 356) = Q Control and PF/Q Regulation Type (page
358) = Base PF/Q Control
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, alarm Wrn Q Control Fail (page 1261) is activated.

6 back to Logical analog inputs alphabetically

Q Control: ANEXT Imp/Exp Q

Related FW 1.5.0 Related applications MPTM


LAI ID 195
Description
This LAI is a source value for control of the Power Factor if PF/Q Request Source (page 357) = Analog
External Value.
The Import/Export Q is active if PF/Q Control PTM Mode (page 356) = Q Control and PF/Q Regulation
Type (page 358) = Import/Export PF/Q Control.
Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, alarm Wrn Q Control Fail (page 1261) is activated.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1147


Q(Um): 0 Ref ANEXT Base Q

MINT,
Related FW 1.5.0 Related applications
MPTM
LAI ID 326
Description
This LAI is used to shift Q(UM) (PAGE 967) curve left or right if PF/Q Control PTM Mode (page 356) = Q
(Um), PF/Q Request Source (page 357) = Analog External Value and PF/Q Regulation Type (page
358) = Base PF/Q Control.

Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range alarm Wrn Q(Um) Fail (page 1263) is activated.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1148


Q(Um): 0 Ref ANEXT Imp/Exp Q

Related FW 1.5.0 Related applications MPTM


LAI ID 327
Description
This LAI is used to shift Q(UM) (PAGE 967) curve left or right if PF/Q Control PTM Mode (page 356) = Q
(Um), PF/Q Request Source (page 357) = Analog External Value and PF/Q Regulation Type (page
358) = Import/Export PF/Q Control.

Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range alarm Wrn Q(Um) Fail (page 1263) is activated.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1149


Qref/Ulim: ANEXT Qref/Pnom B Q

Related FW 1.5.0 Related applications MPTM


LAI ID 328
Description
This LAI is used to shift part of the QREF/ULIM (PAGE 968) curve up or down if PF/Q Control PTM Mode
(page 356) = Qref/Ulim, PF/Q Request Source (page 357) = Analog External Value and PF/Q
Regulation Type (page 358) = Base PF/Q Control.

Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range, alarm Wrn Qref/Ulim Fail (page 1263) is activated.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1150


Qref/Ulim: ANEXT Qref/Pnom I/E Q

Related FW 1.5.0 Related applications MPTM


LAI ID 329
Description
This LAI is used to shift part of the QREF/ULIM (PAGE 968) curve up or down if PF/Q Control PTM Mode
(page 356) = Qref/Ulim, PF/Q Request Source (page 357) = Analog External Value and PF/Q
Regulation Type (page 358) = Import/Export PF/Q Control.

Note: If all setpoints are adjusted as mentioned above and Breaker state (page 886) = ParalOper, but
this LAI is not configured, or is out of sensor range, alarm Wrn Qref/Ulim Fail (page 1263) is activated.

6 back to Logical analog inputs alphabetically

LAI: T

TestF

Related FW 1.5.0 Related applications MPTM


LAI ID 194
Description
This LAI is used for adjusting mains frequency while Testing of Grid Codes (page 299) function is
enabled. Value received via this input is stored in Test Frequency (page 829) as Nominal Frequency
(page 384) + value of this input.
Note: Setpoint Grid Codes Test (page 536) has to be Enabled and alarm Wrn Test UPQF (page
1268) has to be active, otherwise this LAI has no effect.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1151


TestP

Related FW 1.5.0 Related applications MPTM


LAI ID 231
Description
This LAI is used for adjusting generator's active power while Testing of Grid Codes (page 299)
function is enabled.
Note: Setpoint Grid Codes Test (page 536) has to be Enabled and alarm Wrn Test UPQF (page
1268) has to be active, otherwise this LAI has no effect.

6 back to Logical analog inputs alphabetically

TestQ

Related FW 1.5.0 Related applications MPTM


LAI ID 232
Description
This LAI is used for adjusting generator's reactive power while Testing of Grid Codes (page 299)
function is enabled.
Note: Setpoint Grid Codes Test (page 536) has to be Enabled and alarm Wrn Test UPQF (page
1268) has to be active, otherwise this LAI has no effect.

6 back to Logical analog inputs alphabetically

TestU

Related FW 1.5.0 Related applications MPTM


LAI ID 385
Description
This LAI is used for adjusting generator's active power while Testing of Grid Codes (page 299)
function is enabled.
Value received via this input is considered as relative value of Mains Voltage Ph-N related to Mains/Bus
Nominal Voltage Ph-N (page 381) or as relative value of Mains Voltage Ph-Ph related to Mains/Bus
Nominal Voltage Ph-Ph (page 381) based on Connection type (page 378).
Note: Setpoint Grid Codes Test (page 536) has to be Enabled and alarm Wrn Test UPQF (page
1268) has to be active, otherwise this LAI has no effect.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1152


LAI: U

Uni Gen 01 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 589
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 1 Actual
P (page 787) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 01 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 605
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
1 Actual Q (page 788) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 01 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 641
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 01 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 621
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1153


Uni Gen 01 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 573
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 1 Nominal P (page 787)
and is aggregated to the value Uni Gen Nominal Power. The format (resolution) of this input has to
correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 02 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 590
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 2 Actual
P (page 790) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 02 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 606
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
2 Actual Q (page 790) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 02 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 642
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1154


Uni Gen 02 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 622
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 02 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 574
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 2 Nominal P (page 790)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 03 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 591
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 3 Actual
P (page 792) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 03 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 607
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
3 Actual Q (page 792) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1155


Uni Gen 03 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 653
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 03 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 623
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 03 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 578
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 3 Nominal P (page 792)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 04 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 592
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 4 Actual
P (page 794) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1156


Uni Gen 04 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 608
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
4 Actual Q (page 795) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 04 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 644
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 04 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 624
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 04 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 576
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 4 Nominal P (page 794)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1157


Uni Gen 05 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 593
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 5 Actual
P (page 797) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 05 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 609
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
5 Actual Q (page 797) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 05 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 645
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 05 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 625
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1158


Uni Gen 05 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 577
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 5 Nominal P (page 796)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 06 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 594
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 6 Actual
P (page 799) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 06 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 610
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
6 Actual Q (page 799) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 06 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 646
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1159


Uni Gen 06 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 626
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 06 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 578
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 6 Nominal P (page 799)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 07 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 595
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 7 Actual
P (page 801) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 07 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 611
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
7 Actual Q (page 801) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1160


Uni Gen 07 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 647
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 07 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 627
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 07 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 579
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 7 Nominal P (page 801)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 08 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 596
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 8 Actual
P (page 803) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1161


Uni Gen 08 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 612
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
8 Actual Q (page 804) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 08 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 648
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 08 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 628
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 08 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 580
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 8 Nominal P (page 803)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1162


Uni Gen 09 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 597
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 9 Actual
P (page 806) and is aggregated to the value Uni Gen Actual P (page 785). The format (resolution) of
this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 09 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 613
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
9 Actual Q (page 806) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 09 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 649
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 09 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 629
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1163


Uni Gen 09 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 581
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 9 Nominal P (page 805)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 10 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 598
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 10
Actual P (page 808) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

Uni Gen 10 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 614
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
10 Actual Q (page 808) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 10 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 650
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1164


Uni Gen 10 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 630
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 10 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 582
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 10 Nominal P (page 808)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 11 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 599
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 11
Actual P (page 810) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

Uni Gen 11 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 615
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
11 Actual Q (page 810) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1165


Uni Gen 11 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 651
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 11 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 631
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 11 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 583
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 11 Nominal P (page 810)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 12 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 600
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 12
Actual P (page 812) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1166


Uni Gen 12 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 616
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
12 Actual Q (page 813) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 12 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 652
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 12 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 632
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 12 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 584
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 12 Nominal P (page 812)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1167


Uni Gen 13 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 601
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 13
Actual P (page 815) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

Uni Gen 13 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 617
7Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
13 Actual Q (page 815) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 13 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 653
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 13 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 633
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1168


Uni Gen 13 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 585
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 13 Nominal P (page 814)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 14 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 602
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 14
Actual P (page 817) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

Uni Gen 14 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 618
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
14 Actual Q (page 817) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 14 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 654
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1169


Uni Gen 14 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 634
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 14 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 586
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 14 Nominal P (page 817)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 15 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 603
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 15
Actual P (page 819) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

Uni Gen 15 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 619
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
15 Actual Q (page 819) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1170


Uni Gen 15 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 655
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 15 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 635
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 15 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 587
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 15 Nominal P (page 819)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

Uni Gen 16 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 604
Description
This LAI is intended for reading of actual value of the active power of each particular universal Genset
inside the Universal Gensets group. The actual power is then propagated to the Value Uni Gen 16
Actual P (page 821) and is aggregated to the value Uni Gen Actual P (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01
MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1171


Uni Gen 16 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 620
Description
This LAI is intended for reading of actual value of the reactive power of each particular universal Genset
inside the Universal Gensets group. The actual reactive power is then propagated to the Value Uni Gen
16 Actual Q (page 822) and is aggregated to the value Uni Gen Actual Q (page 785). The format
(resolution) of this input has to correspond to the Power Format selected in InteliNeo (0,1 kVAr, 1 kVAr,
0,01 MVAr).

6 back to Logical analog inputs alphabetically

Uni Gen 16 Fuel

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 656
Description
This LAI is intended for reading of fuel used volume consumed by the Universal Gensets. The kWh from
each particular Universal Genset is aggregated to the common valueFuel Used (page 878) in statistics
values. This value is used for calculation of interval kWh statistic values. The format and dimension of
this value depends on selected Unit Format in InteliConfig (Metric / US).

6 back to Logical analog inputs alphabetically

Uni Gen 16 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 636
Description
This LAI is intended for reading of energy produced by the Universal Gensets. The kWh from each
particular Universal Genset is aggregated to the common value Gen kWh (page 877) in statistics
values. This value is used for calculation of interval kWh statistic values.

6 back to Logical analog inputs alphabetically

Uni Gen 16 Nom P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 588
Description
This LAI is intended for reading of nominal power of each particular universal Genset inside the Universal
Gensets group. The nominal power is then propagated to the Value Uni Gen 16 Nominal P (page 821)
and is aggregated to the value Uni Gen Nominal P (page 785). The format (resolution) of this input has
to correspond to the Power Format selected in InteliNeo (0,1 kW, 1 kW, 0,01 MW).

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1172


LAI: W

WT 01 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 502
Description
This LAI is designed to monitor actual power of the WT 1.

6 back to Logical analog inputs alphabetically

WT 01 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 510
Description
This LAI is designed to monitor actual reactive power of the WT 1.

6 back to Logical analog inputs alphabetically

WT 01 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 518
Description
This LAI defines the amount of energy produced by WT 1 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

WT 01 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 494
Description
This LAI is used to define nominal power of the WT 1 used in the system.

6 back to Logical analog inputs alphabetically

WT 02 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 503
Description
This LAI is designed to monitor actual power of the WT 2.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1173


WT 02 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 511
Description
This LAI is designed to monitor actual reactive power of the WT 2.

6 back to Logical analog inputs alphabetically

WT 02 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 519
Description
This LAI defines the amount of energy produced by WT 2 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

WT 02 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 495
Description
This LAI is used to define nominal power of the WT 2 used in the system.

6 back to Logical analog inputs alphabetically

WT 03 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 504
Description
This LAI is designed to monitor actual power of the WT 3.

6 back to Logical analog inputs alphabetically

WT 03 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 512
Description
This LAI is designed to monitor actual reactive power of the WT 3.

6 back to Logical analog inputs alphabetically

WT 03 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 520
Description
This LAI defines the amount of energy produced by WT 3 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1174


WT 03 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 496
Description
This LAI is used to define nominal power of the WT 3 used in the system.

6 back to Logical analog inputs alphabetically

WT 04 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 505
Description
This LAI is designed to monitor actual power of the WT 4.

6 back to Logical analog inputs alphabetically

WT 04 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 513
Description
This LAI is designed to monitor actual reactive power of the WT 4.

6 back to Logical analog inputs alphabetically

WT 04 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 521
Description
This LAI defines the amount of energy produced by WT 4 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

WT 04 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 497
Description
This LAI is used to define nominal power of the WT 4 used in the system.

6 back to Logical analog inputs alphabetically

WT 05 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 498
Description
This LAI is used to define nominal power of the WT 5 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1175


WT 05 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 514
Description
This LAI is designed to monitor actual reactive power of the WT 5.

6 back to Logical analog inputs alphabetically

WT 05 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 506
Description
This LAI is designed to monitor actual power of the WT 5.

6 back to Logical analog inputs alphabetically

WT 05 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 522
Description
This LAI defines the amount of energy produced by WT 5 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

WT 06 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 507
Description
This LAI is designed to monitor actual power of the WT 6.

6 back to Logical analog inputs alphabetically

WT 06 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 515
Description
This LAI is designed to monitor actual reactive power of the WT 6.

6 back to Logical analog inputs alphabetically

WT 06 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 523
Description
This LAI defines the amount of energy produced by WT 6 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1176


WT 06 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 499
Description
This LAI is used to define nominal power of the WT 6 used in the system.

6 back to Logical analog inputs alphabetically

WT 07 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 508
Description
This LAI is designed to monitor actual power of the WT 7.

6 back to Logical analog inputs alphabetically

WT 07 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 516
Description
This LAI is designed to monitor actual reactive power of the WT 7.

6 back to Logical analog inputs alphabetically

WT 07 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 524
Description
This LAI defines the amount of energy produced by WT 7 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

WT 07 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 500
Description
This LAI is used to define nominal power of the WT 7 used in the system.

6 back to Logical analog inputs alphabetically

WT 08 Actual P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 509
Description
This LAI is designed to monitor actual power of the WT 8.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1177


WT 08 Actual Q

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 517
Description
This LAI is designed to monitor actual reactive power of the WT 8.

6 back to Logical analog inputs alphabetically

WT 08 kWh

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 525
Description
This LAI defines the amount of energy produced by WT 8 and is used as a source for statistic values.

6 back to Logical analog inputs alphabetically

WT 08 Nominal P

Related FW 1.5.0 Related applications MINT, MPTM


LAI ID 501
Description
This LAI is used to define nominal power of the WT 8 used in the system.

6 back to Logical analog inputs alphabetically

InteliNeo 6000 1.5.0 Global Guide 1178


9.1.9 Fixed Protection States
List of Fixed Protection States
Fixed Protections States 1 1180
Fixed Protections States 2 1181
Fixed Protections States 3 1182
Fixed Protections States 4 1183
Fixed Protections States 5 1184
Fixed Protections States 6 1185
Fixed Protections States 7 1186
Fixed Protections States 8 1187

6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 1179


Fixed Protections States 1

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20744
Description
This is a group of fixed protection states.
List of protection states by bits:
1. Wrn Brute Force Protection Active (page 1250)
2. Wrn Redundant CAN inconsistency (page 1264)
3. Wrn CAN2 Empty (page 1250)
4. Wrn SHBIN Collision (page 1349)
5. Wrn SHAIN Collision (page 1347)
6. ALI GCB Closing Is Blocked (page 1)
7. Not Used
8. Not Used
9. Not Used
10. Not Used
11. Not Used
12. Not Used
13. Not Used
14. Not Used
15. Not Used
16. Wrn Battery Undervoltage (page 1250)
17. Wrn Battery Overvoltage (page 1249)
18. Wrn SD Card Failed (page 1265)
19. Wrn Long Term History Fail (page 1254)
20. Not Used
21. Not Used
22. Not Used
23. Wrn Override All Sd (page 1256)
24. Wrn Load IMP/EXP Fail (page 1253)
25. Wrn PF/Q IMP/EXP Fail (page 1258)
26. Wrn PF Control Fail (page 1258)
27. Wrn Q Control Fail (page 1261)
28. Wrn Q(Um) Fail (page 1263)
29. Wrn Qref/Ulim Fail (page 1263)
30. Wrn Q(P) Fail (page 1262)
31. Wrn PF(Pm) Fail (page 1259)
32. Wrn P(Um) Fail (page 1257)

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1180


Fixed Protections States 2

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20745
Description
This is a group of fixed protection states.
List of protection states by bits:
1. Sd BESS >V L1-N (page 1283)
2. Sd BESS >V L2-N (page 1283)
3. Sd BESS >V L3-N (page 1283)
4. Sd BESS >V L1-L2 (page 1283)
5. Sd BESS >V L2-L3 (page 1284)
6. Sd BESS >V L3-L1 (page 1284)
7. Sd BESS >>V L1-N (page 1281)
8. Sd Mains/Bus >>V L2-N (page 1281)
9. Sd BESS >>V L3-N (page 1282)
10. WRN BESS >>V L1-L2 (page 1282)
11. WRN BESS >>V L2-L3 (page 1282)
12. WRN BESS >>V L3-L1 (page 1282)
13. Sd BESS <V L1-N (page 1284)
14. Sd BESS <V L2-N (page 1284)
15. Sd BESS <V L3-N (page 1285)
16. Sd BESS <V L1-L2 (page 1285)
17. Sd BESS <V L2-L3 (page 1285)
18. Sd BESS <V L3-L1 (page 1285)
19. Sd BESS V Unbalance Ph-N (page 1286)
20. Sd BESS V Unbalance Ph-Ph (page 1286)
21. Sd BESS >f (page 1286)
22. Sd BESS <f (page 1286)
23. Not Used
24. Not Used
25. Sd IDMT Overload (page 1287)
26. PVBO Short Circuit (page 1288)
27. Sd IDMT BESS >A (page 1287)
28. Sd IDMT Earth Fault Current (page 1287)
29. Sd BESS Current Unbalance (page 1287)
30. ALI BESS Ph Rotation Opposite (page 1273)

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1181


Fixed Protections States 3

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20746
Description
This is a group of fixed protection states.
List of protection states by bits:
1. Emergency Stop (page 1280)
2. Not Used
3. Not Used
4. Not Used
5. Wrn Stop Fail (page 1267)
6. Wrn SOC Low Alarm (page 1266)
7. Wrn SOC High Alarm (page 1266)
8. Sd SOC Critical Low (page 1288)
9. Sd SOC Critical High (page 1288)
10. Not Used
11. Wrn Frequency Regulation Limit (page 1252)
12. Wrn Voltage Regulation Limit (page 1268)
13. Stp Synchronization Fail (page 1294)
14. Wrn Reverse Synchronization Fail (page 1265)
15. Stp BCB Fail (page 1290)
16. Stp BCB Secondary Fail (page 1292)
17. Sd NCB Fail (page 1288)
18. Not Used
19. Not Used
20. Not Used
21. Not Used
22. Not Used
23. Not Used
24. Not Used
25. Not Used
26. Not Used
27. Not Used
28. Not Used
29. Not Used
30. Not Used
31. Not Used
32. Not Used

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1182


Fixed Protections States 4

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20747
Description
This is a group of fixed protection states.
1. Mains/Bus >V L1-N (page 1301)
2. Mains/Bus >V L2-N (page 1301)
3. Mains/Bus >V L3-N (page 1302)
4. Mains/Bus >V L1-L2 (page 1303)
5. Mains/Bus >V L2-L3 (page 1304)
6. Mains/Bus >V L3-L1 (page 1304)
7. Mains/Bus >>V L1-N (page 1305)
8. Mains/Bus >>V L2-N (page 1306)
9. Mains/Bus >>V L3-N (page 1307)
10. Mains/Bus >>V L1-L2 (page 1307)
11. Mains/Bus >>V L2-L3 (page 1308)
12. Mains/Bus >>V L3-L1 (page 1309)
13. Mains Avg >V L1-N (page 1296)
14. Mains Avg >V L2-N (page 1296)
15. Mains Avg >V L3-N (page 1296)
16. Mains Avg >V L1-L2 (page 1296)
17. Mains Avg >V L2-L3 (page 1297)
18. Mains Avg >V L3-L1 (page 1297)
19. Mains/Bus <V L1-N (page 1310)
20. Mains/Bus <V L2-N (page 1310)
21. Mains/Bus <V L3-N (page 1311)
22. Mains/Bus <V L1-L2 (page 1312)
23. Mains/Bus <V L2-L3 (page 1313)
24. Mains/Bus <V L3-L1 (page 1313)
25. Mains/Bus <<V L1-N (page 1314)
26. Mains/Bus <<V L2-N (page 1315)
27. Mains/Bus <<V L3-N (page 1316)
28. Mains/Bus <<V L1-L2 (page 1316)
29. Mains/Bus <<V L2-L3 (page 1317)
30. Mains/Bus <<V L3-L1 (page 1318)
31. Mains/Bus V Unbalance Ph-Ph (page 1321)
32. Mains/Bus V Unbalance Ph-N (page 1321)

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1183


Fixed Protections States 5

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20748
Description
This is a group of fixed protection states.
List of protection states by bits:
1. Mains/Bus >f (page 1319)
2. Mains/Bus >>f (page 1319)
3. Mains/Bus <f (page 1320)
4. Mains/Bus <<f (page 1320)
5. ALI Mains Ph Rotation Opposite (page 1275)
6. ALI Bus Ph Rotation Opposite (page 1270)
7. Wrn MCB Fail (page 1254)
8. Stp Bus Meas Error (page 1290)
9. Wrn SD Card File System Failed (page 1265)
10. Wrn Test UPQF (page 1268)
11. AHI SyncNotAllowed (page 1276)
12. Wrn P for Q Fail (page 1257)
13. Wrn Q&U Protection (page 1262)
14. Wrn VRT Protection Trip (page 1349)
15. MP VRT Protection Trip (page 1349)
16. Wrn Soft Transfer Fail (page 1267)
17. Not Used
18. Not Used
19. Not Used
20. Not Used
21. Not Used
22. Not Used
23. Not Used
24. Not Used
25. Not Used
26. Not Used
27. Not Used
28. Not Used
29. Not Used
30. Not Used
31. Not Used
32. Not Used

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1184


Fixed Protections States 6

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20749
Description
This is a group of fixed protection states.
List of protection states by bits:
1. ECU 1 Comm Fail (page 1341)
2. ECU 1 Comm Fail (page 1341)
3. ECU 2 Comm Fail (page 1341)
4. ECU 2 Comm Fail (page 1341)
5. ECU 3 Comm Fail (page 1341)
6. ECU 3 Comm Fail (page 1341)
7. ECU 4 Comm Fail (page 1342)
8. ECU 4 Comm Fail (page 1342)
9. ECU 5 Comm Fail (page 1342)
10. ECU 5 Comm Fail (page 1342)
11. ECU 6 Comm Fail (page 1343)
12. ECU 6 Comm Fail (page 1343)
13. ECU 7 Comm Fail (page 1343)
14. ECU 7 Comm Fail (page 1343)
15. ECU 8 Comm Fail (page 1343)
16. ECU 8 Comm Fail (page 1343)
17. ECU 9 Comm Fail (page 1344)
18. ECU 9 Comm Fail (page 1344)
19. ECU 10 Comm Fail (page 1344)
20. ECU 10 Comm Fail (page 1344)
21. ECU 11 Comm Fail (page 1344)
22. ECU 11 Comm Fail (page 1344)
23. ECU 12 Comm Fail (page 1345)
24. ECU 12 Comm Fail (page 1345)
25. ECU 13 Comm Fail (page 1345)
26. ECU 13 Comm Fail (page 1345)
27. ECU 14 Comm Fail (page 1346)
28. ECU 14 Comm Fail (page 1346)
29. ECU 15 Comm Fail (page 1346)
30. ECU 15 Comm Fail (page 1346)
31. ECU 16 Comm Fail (page 1346)
32. ECU 16 Comm Fail (page 1346)

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1185


Fixed Protections States 7

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20750
Description
This is a group of fixed protection states.
List of protection states by bits:
1. Wrn Alarm e-mail 1 Fail (page 1248)
2. Wrn Alarm e-mail 2 Fail (page 1248)
3. Wrn Alarm e-mail 3 Fail (page 1248)
4. Wrn Alarm e-mail 4 Fail (page 1248)
5. Wrn SNMP TRAP 1 Fail (page 1265)
6. Wrn SNMP TRAP 2 Fail (page 1266)
7. Wrn Maintenance 1 RunHours (page 1322)
8. Maintenance 1 RunHours (page 1322)
9. Wrn Maintenance 2 RunHours (page 1323)
10. Maintenance 2 RunHours (page 1323)
11. Wrn Maintenance 3 RunHours (page 1324)
12. Maintenance 3 RunHours (page 1324)
13. Wrn Maintenance 4 RunHours (page 1324)
14. Maintenance 4 RunHours (page 1324)
15. Wrn Maintenance 1 Interval (page 1322)
16. Maintenance 1 Interval (page 1322)
17. Wrn Maintenance 2 Interval (page 1323)
18. Maintenance 2 Interval (page 1323)
19. Wrn Maintenance 3 Interval (page 1323)
20. Maintenance 3 Interval (page 1323)
21. Wrn Maintenance 4 Interval (page 1324)
22. Maintenance 4 Interval (page 1324)
23. Wrn MCB Fail To Open (page 1256)
24. Wrn MCB Fail To Close (page 1255)
25. Sd BCB Fail To Open (page 1291)
26. Sd BCB Fail To Close (page 1291)
27. Stp BCB Secondary Fail To Open (page 1294)
28. Stp BCB Secondary Fail To Close (page 1293)
29. ALI SD Card Not Compatible (page 1273)
30. ALI SD Card In Slot (page 1274)
31. ALI SD Card Full (page 1274)
32. ALI SD Card Formatting/Mounting (page 1274)

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1186


Fixed Protections States 8

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20751
Description
This is a group of fixed protection states.
List of protection states by bits:
1. Wrn ECU 17 Comm Fail
2. Sd ECU 17 Comm Fail
3. Wrn ECU 18 Comm Fail
4. Sd ECU 18 Comm Fail
5. Wrn ECU 19 Comm Fail
6. Sd ECU 19 Comm Fail
7. Wrn ECU 20 Comm Fail
8. Sd ECU 20 Comm Fail
9. Wrn ECU 21 Comm Fail
10. Sd ECU 21 Comm Fail
11. Wrn ECU 22 Comm Fail
12. Sd ECU 22 Comm Fail
13. Wrn ECU 23 Comm Fail
14. Sd ECU 23 Comm Fail
15. Wrn ECU 24 Comm Fail
16. Sd ECU 24 Comm Fail
17. Wrn ECU 25 Comm Fail
18. Sd ECU 25 Comm Fail
19. Wrn ECU 26 Comm Fail
20. Sd ECU 26 Comm Fail
21. Wrn ECU 27 Comm Fail
22. Sd ECU 27 Comm Fail
23. Wrn ECU 28 Comm Fail
24. Sd ECU 28 Comm Fail
25. Wrn ECU 29 Comm Fail
26. Sd ECU 29 Comm Fail
27. Wrn ECU 30 Comm Fail
28. Sd ECU 30 Comm Fail
29. Wrn ECU 31 Comm Fail
30. Sd ECU 31 Comm Fail
31. Wrn ECU 32 Comm Fail
32. Sd ECU 32 Comm Fail

6 back to Fixed Protection States

InteliNeo 6000 1.5.0 Global Guide 1187


9.1.10 User Protection States
List of User Protection States
User Protections States 1 1189
User Protections States 2 1189
User Protections States 3 1189
User Protections States 4 1189
User Protections States 5 1189
User Protections States 6 1190
User Protections States 7 1190
User Protections States 8 1190
User Protections States 9 1190
User Protections States 10 1190

6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 1188


User Protections States 1

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20759
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 2

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20760
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 3

Related FW 1.5.0 5Related applications MINT, MPTM


Comm object 20761
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 4

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20762
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 5

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20763
Description
This is a group of user protection states.

6 back to User Protection States

InteliNeo 6000 1.5.0 Global Guide 1189


User Protections States 6

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20764
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 7

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20765
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 8

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20766
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 9

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20767
Description
This is a group of user protection states.

6 back to User Protection States

User Protections States 10

Related FW 1.5.0 Related applications MINT, MPTM


Comm object 20768
Description
This is a group of user protection states.

6 back to User Protection States

InteliNeo 6000 1.5.0 Global Guide 1190


9.1.11 PLC
List of PLC blocks
Group: Logical functions 1193
OR/AND 1193
XOR/RS 1195
Group: Comparators 1196
Comp Delay 1196
Comp Hyst 1197
Comp Win 1198
Group: Time functions 1199
Delay 1199
Timer 1201
Group: Math operations 1203
Interpolation 1203
AxB/C±D 1204
Math Fc. 1205
Group: Regulators 1207
PID 1207
Up/Down Ctrl Block 1211
Group: Ramp functions 1214
Inc/Dec 1214
LowPassFlt 1215
Mov Avg 1216
Ramp 1217
Up/Down 1218
Group: Other functions 1220
Analog Switch 8 1220
Bit Sum 16 1222
Circuit Breaker 1224
Convert 1227
Counter 1228
Comp. 4 1229
Comp. 16 1230
Decomp. 4 1231
Decomp. 16 1232
Differ 1234
Heartbeat 1235
Hold 1237

InteliNeo 6000 1.5.0 Global Guide 1191


PF Conv 1238
Poly Appx 1240
PWR Calc 1241
Validator 1244
6 back to Controller objects

InteliNeo 6000 1.5.0 Global Guide 1192


Group: Logical functions

OR/AND

PLC group Logical functions

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 1

Inputs

Input Type Negation Range Function


Input 1 Binary Yes 0/1 Input 1
Input 2 Binary Yes 0/1 Input 2
Input 3 Binary Yes 0/1 Input 3 (optional)
Input 4 Binary Yes 0/1 Input 4 (optional)
Input 5 Binary Yes 0/1 Input 5 (optional)
Input 6 Binary Yes 0/1 Input 6 (optional)
Input 7 Binary Yes 0/1 Input 7 (optional)
Input 8 Binary Yes 0/1 Input 8 (optional)
Outputs

Output Type Negation Range Function


Output Binary Yes 0/1 Result of the logical operation
Description
The block performs logical operation OR / AND of 2 - 8 binary operands. The inputs as well as the output
can be inverted.

Function OR Function AND


Input 1 Input 2 Output Input 1 Input 2 Output
0 0 0 0 0 0
0 1 1 0 1 0
1 0 1 1 0 0
1 1 1 1 1 1

There have to be at least 2 inputs every time. There may be up to 8 inputs configured.

InteliNeo 6000 1.5.0 Global Guide 1193


Image 7.43 Configuration of OR/AND block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1194


XOR/RS

PLC group Logical functions

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 39

Inputs

Input Type Negation Range Function


Input 1..2 Binary Yes 0/1 Inputs 1..2
Outputs

Output Type Negation Range Function


Output Binary Yes 0/1 Result of the logical operation
Description
The block performs logical (boolean) XOR operation of two binary operands or several variants of the RS
flipflop function. Both Inputs and Output can be inverted.

Function type XOR


Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 0

The result of XOR operation between two binary inputs (Input 1 and Input 2) is defined by table below.

Function type RS
R-latch S-latch E-latch JK-latch
Input 2 (R) Input 1 (S)
Q
-1 -1 -1 -1
0 0 Q Q Q Q
0 1 1 1 1 1
1 0 0 0 0 0
-1 -1
1 1 0 1 Q NOT(Q )
-1
The Q denotes the state of the RS block output in the last evaluation cycle.
The block Output value is given by the selected RS flip-flop variant evaluation:
R-latch: When both inputs (R, S) are set the Reset input is dominant.
S-latch: When both inputs (R, S) are set the Set input is dominant.
E-latch: When both inputs (R, S) are set the previous output is preserved.
JK-latch: When both inputs (R, S) are set the block output is negated.
The block has the setting for the variant functions of the RS flip-flop circuit. This setting is

InteliNeo 6000 1.5.0 Global Guide 1195


available in the block configuration dialog (i.e. it is done in the configuration and cannot be
changed dynamically while the PLC is running).

Image 7.44 Configuration of XOR/RS block

6 back to List of PLC blocks

Group: Comparators

Comp Delay

PLC group Comparators


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 46
Inputs

Input Type Negation Range Function


32 32
Input 1 Analog No -2 .. 2 Compared value
32 32
Input 2 Analog No -2 .. 2 Comparation level
Delay Analog No 0.0 .. 3000.0 [s] Comparative delay
Outputs

Output Type Negation Range Function


Output Binary Yes 0/1 Comparator output
Description
This PLC block compares the Input value with the Reference comparison level using the selected
Relation. The Output will switch on if the Input is equal/higher/smaller/etc. than the Reference
comparison level for a time longer than the Delay. All Relation operations between the Input and the
Reference are described in the table below.

Relation Name
">" (default) greater than
">=" greater than equal
"==" equal
"<=" less than equal
"<" less than

InteliNeo 6000 1.5.0 Global Guide 1196


Image 7.45 Configuration of Comp Delay block

6 back to List of PLC blocks

Comp Hyst

PLC group Comparators


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 3
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Compared value

32 32 Comparative level for


Input ON Analog No -2 .. 2
switching on

32 32 Comparative level for


Input OFF Analog No -2 .. 2
switching off
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Comparator output
Description
TThe block compares the Input value with two comparison levels I-ON and I-OFF. The evaluation of the
block depends on whether the I-ON level is higher than the I-OFF level or vice versa.

Image 7.46 Different On and Off levels

InteliNeo 6000 1.5.0 Global Guide 1197


Image 7.47 Configuration of Comp Hyst block

6 back to List of PLC blocks

Comp Win

PLC group Comparators


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 18
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Compared value
32 32
Input HIGH Analog No -2 .. 2 Upper window limit
32 32
Input LOW Analog No -2 .. 2 Lower window limit
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Comparator output
Description
The block output is switched on whenever the input value is in the range defined by Lo and Hi levels.

Image 7.48 Principle of delay

InteliNeo 6000 1.5.0 Global Guide 1198


Image 7.49 Configuration of Comp Time block

Note: All inputs and can be constants or values from controller.

6 back to List of PLC blocks

Group: Time functions

Delay

PLC group Time functions

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 33

Inputs

Input Type Negation Range Function


Input Binary No 0/1 Input signal to be delayed
Delay of the rising edge resp.
Input time 0 .. 214 748 364,7
Analog No pulse length generated by rising
up [s, m, h]
edge of the input
Delay of the falling edge resp.
Input time 0 .. 214 748 364,7
Analog No pulse length generated by falling
down [s, m, h]
edge of the input
Resets the output to logical 0. The
output remains in logical 0 until
Input reset Binary No 0/1 new rising edge appears on Input
(when Input reset is deactivated
already)
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Output signal
Description
This block can operate in two operating modes (Delay mode, Pulse mode) = the block mode is defined by
the Pulse on edge checbox option - if checked, the Pulse mode is active.
Delay mode - the rising edge at the Output is generated with a delay of the Input time up lenght
when arising edge is detected on the Input. A falling edge at the Output is generated with a delay
of the Input time down length when a falling edge is detected on the Input. If the delayed falling

InteliNeo 6000 1.5.0 Global Guide 1199


edge at the Output arrived before the delayed rising edge, then no pulse would be generated at
the Output.
Pulse mode - a pulse of Input time up length is generated at the Output when a rising edge is
detected, a pulse of Input time down length is generated at the Output when a falling edge is
detected.
Note: Because of 100 ms tact, the analog inputs are limited to resolution 0,1 s.

Note: If Input time up or Input time down value is <0, this input is internally set to zero.

Note: Use Pulse on edge option to choose between delay and pulse mode.

Image 7.50 Delay modes principles

Image 7.51 Configuration of Delay block

InteliNeo 6000 1.5.0 Global Guide 1200


6 back to List of PLC blocks

Timer

PLC group Time functions

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 38

Inputs

Input Type Negation Range Function


The timer runs only if this input
Run Binary No 0/1
is active or not connected
This input reloads the timer to
Reload Binary No 0/1
the initial value
Reload
Analog No 0,0 .. 214 748 364,7 [s] Initial value of the timer
value
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Timer output
Analog value that shows Actual Timer Value
Actual
Lowest available value from:
Timer Analog No N/A
Value <PLC Resource 1 (page 935) to
PLC Resource 16 (page 938)>
Description
The block performs countdown Timer according to the selected Timer mode and actual inputs values.
The Timer mode could be selected as:
ComAp timer mode = if the Timer block is to generate a periodic signal at its Output
Timer mode TP = if the Timer block is to generate a pulse signal of defined width at its Output
Timer mode TON = if the Timer block is to delay the rising edge of the Input by a defined time.
Timer mode TOFF = if the Timer block is to delay the falling edge of the Iutput by a defined time.
Timer mode ComAp
The Timer is counting down only when the Run is on and Reset is off. It is also reset to the Reload
value if it reaches 0 or Reset is enabled. The state of the binary Output is negated whenever the
Timer value is zero.

Timer mode TP

InteliNeo 6000 1.5.0 Global Guide 1201


The Timer counts down when Run is on.The Reset accepts only the rising edge and is required to
load the Reload value to the actual Timer value. The Output is set as long as the Actual Timer Value
is not equal to 0 (the countdown is in progress).

Timer mode TON


The Timer starts counting down with the rising edge of Run. The falling edge of Run, like the rising
edge of Reset, reloads the Reload value to actual Timer value. The Output is set when the Actual
Timer Value is 0 (the countdown is finished).

Timer mode TOF


The Timer starts counting down with the falling edge of the Run. The rising edge of Run, like the rising
edge of Reset, reloads the Reload value to actual Timer value. The Output is set if the Actual Timer
Value is not equal to 0 (the countdown is in progress).

Image 7.52 Configuration of Timer block

InteliNeo 6000 1.5.0 Global Guide 1202


Note: For ComAp Timer mode: if you want the Output to start at logic 0, check the First down option.
Otherwise, the Output will start at logical 1.

IMPORTANT: For ComAp Timer mode: if no inputs are connected and the First down option
is not checked, the Output is active.

6 back to List of PLC blocks

Group: Math operations

Interpolation

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 34

Inputs

Input Type Range Function


32 32
Input Analog -2 .. 2 Input value
32 32
X1 Analog -2 .. 2 Low X limit of definition
32 32
X2 Analog -2 .. 2 High X limit of definition
32 32
Y1 Analog -2 .. 2 Low Y limit of definition
32 32
Y2 Analog -2 .. 2 High Y limit of definition
Outputs

Output Type Range Function


Output Analog Y1 .. Y2 Transformed value
Out of Range Binary 0/1 Closed when input is out of range <X1, X2>
Data Invalid Binary 0/1 Closed when value on analog output is invalid
Description
This block performs a linear transformation of the input. The transformation function is defined by two
pairs of points [X1, Y1] and [X2, Y2]. If the Input lies inside of the interval <X1, X2> the Output is given
by the conversion. If the Input is lying outside of this interval, Output is saturated either on high or low
limit given by Y1 or Y2 and Out of Range is closed. If any of the inputs gets invalid, Data Invalid is closed
and Output is set to invalid value. The Output, Y1, Y2 has resolution and dimension based on settings of
the block. The resolution and dimensions of the X1 and X2 is same as resolution of the Input.

InteliNeo 6000 1.5.0 Global Guide 1203


Image 7.53 Principle of Interpolation

Image 7.54 Configuration of Interpolation block

6 back to List of PLC blocks

AxB/C±D

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 51

Inputs

Input Abbr. Type Range Function


32 32
Input A A Analog -2 -1 .. +2 -1 First multiplicant
32 32
Input B B Analog -2 -1 .. +2 -1 Second multiplicant
32 32
Input C C Analog -2 -1 .. +2 -1 Divider
32 32
Input D D Analog -2 -1 .. +2 -1 Additive term (optional)
Outputs

InteliNeo 6000 1.5.0 Global Guide 1204


Output Abbr. Type Range Function

Output O Binary
32 32
-2 -1 .. +2 -1 Result of the
operation
Set when Output is out of
Data
Err Binary 0/1 range or when dividing by zero
invalid
occurrs
Description
The block realizes the mathematical operation AxB/C±D. The operation ± is selected by Function
typeselector. In case of any invalid data on any of the inputs, the Output is set to invalid value and Data
Invalid is closed. The Output has resolution and dimension based on setting of the block.

Image 7.55 Configuration of Math AxB/C±D block

6 back to List of PLC blocks

Math Fc.

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 17

Inputs

InteliNeo 6000 1.5.0 Global Guide 1205


Input Type Negation Range Function
32 32
Input 1 Analog No -2 .. 2 Input 1
32 32
Input 2 Analog No -2 .. 2 Input 2
32 32
Input 3 Analog No -2 .. 2 Input 3
32 32
Input 4 Analog No -2 .. 2 Input 4
32 32
Input 5 Analog No -2 .. 2 Input 5
32 32
Input 6 Analog No -2 .. 2 Input 6
32 32
Input 7 Analog No -2 .. 2 Input 7
32 32
Input 8 Analog No -2 .. 2 Input 8
Outputs

Output Type Negation Range Function

32 32 Result of the mathematical


Output Analog No -2 .. 2
operation
Description
This block performs basic mathematical operations of 2 to 8 operands based on selected function.All
invalid inputs are ignored. If any configured input contains an invalid value and at least one configured
input is valid, the output has value counted from only valid configured inputs based on the selected
function. If all configured inputs are invalid output has an invalid value.
The Output has a Resolution and Dimension according to the block settings.

Function Output
ADD - Addition Input 1 + Input 2 + … + Input N
SUB - Substraction Input 1 - Input 2 - … - Input N
|SUB| - Absolute value of substraction ABS(Input 1 - Input 2 - … - Input N)
AVG - Average Input 1 + Input 2 + … + Input N) / N
MIN - Minimal value MIN(Input 1, Input 2, … ,Input N)
MAX - Maximal value MAX(Input 1, Input 2, … ,Input N)

Note: In case of AVG operation type the N is number of inputs with valid value.

InteliNeo 6000 1.5.0 Global Guide 1206


Image 7.56 Configuration of Math Fc. block

6 back to List of PLC blocks

Group: Regulators

PID

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 41

Inputs

InteliNeo 6000 1.5.0 Global Guide 1207


Input Type Negation Range Function

32 32 Actual (controlled) value


Input Value Analog No -2 .. 2
"process value".
Requested 32 32 Required value "setpoint
Analog No -2 .. 2
Value value".
When PID Enable is not true
or there is an invalid value on
the Input Value of the
PID Enable Binary Yes 0/1 controller the output of the PID
block has a Init Value. If this
input is not connected the
controller is enabled.
Gain of the controller K. The
value 0 turns the controller off.
Negative values are not
Gain Analog No -100,00 .. 100,00
allowed, use the Reverse
Output parameter for such a
purpose.
Integration time constant of
Int Analog No 0,00 .. 120,00 s the controller Ti. The value 0
disables the integrating part.
Derivation time constant of the
Der Analog No 0,00 .. 4,00 s controller Td. The value 0
disables the derivating part.
The output value is in the Init
Value mode when PID Enable
is not active or there is an
invalid value on the Input
Value of the controller. The Init
Init Value Analog No -10 000 .. 10 000 Value is not limited by the Low
Limit and High Limit. Output
value in the Init mode is given
in a whole range of regulator
output (from -10 000 to 10
000).
Evaluation period (decimation
factor of default PLC period =
100ms). The period should be
adjusted according to the
Period Analog No 0,1 - 3250,0 s
response speed of the
system, e.g. longer period for
slower systems, a shorter
period for faster systems.
Reverse Binary Yes 0/1 Reverse Output:

InteliNeo 6000 1.5.0 Global Guide 1208


off - higher controller output →
higher process value (default)
Output
on - higher controller output →
lower process value
This value defines the low limit
Low Limit Analog No -10 000 .. 10 000 (minimum) of the controller
output.
This value defines the high
High Limit Analog No -10 000 .. 10 000 limit (maximum) of the
controller output.
FeedForward 32 32
Analog No -2 .. 2 Feedforward control value.
Value
Feedforward control value
FeedForward ±38 ±38
Analog No -3,4 .. 3,4 weight Wff (default 0 %) [Float
Weight
data type]
Controller output value in
MANual mode. There is a
difference to the Init Value
(inactive PID block) = manual
Manual Value Analog No -10 000 .. 10 000
value is available only while
the PID Enable is true and is
limited by the High Limit and
Low Limit.
Manual Mode:
off - AUTomatic mode
MANual Mode Binary Yes 0/1
(default)
on - MANual mode
Outputs

Output Type Negation Range Function


Process value (controller output)
Output Analog No -10 000 .. 10 000
"control value".
Output Derivation of controller output
Analog No -10 000 .. 10 000
Velocity "speed of control value".
Control Control deviation (= "requested
Analog No -10 000 .. 10 000
Deviation value" - "actual value").
Out Low Controller output reaches the Low
Binary Yes 0/1
Limit Limit.
Out High Controller output reaches the High
Binary Yes 0/1
Limit Limit.
Description
The PID block is a PID controller, created by combining a proportional, an integration and a derivative
controller together (all forming the feed-back controller) with an optional forward control path (intended
for the feedforward control).

InteliNeo 6000 1.5.0 Global Guide 1209


The main purpose of using a PID controller is to eliminate the entry control deviation by changing the
output control value (also called the manipulated value). The Control Deviation is evaluated as the
difference between the Requested Value (setpoint value) and the Input Value (process value). If the
controller is operating in automatic mode (MANual mode input is inactive), the action value is calculated
according to the control law equation. In the case of manual control (MAN mode input is active), the value
of the Manual Value is used instead. In both cases, the Output value is limited by the Low Limit and High
Limit limit values.
The PID block features::
Standard controller parameters (ISA Form).
Limitation of the control (process) value (block output).
Adjustable evaluation period.
Feed-forward input (with feed-forward gain parameter).
AUT/MAN switch with manual setpoint value.
RACT switch (reversing of control value polarity).
The function of the PID controller can be disabled by the PID Enable. While the regulator is disabled, the
output is set to a Init Value.
Note: Negative values of Gain are not allowed, use the Reverse Output input for such a purpose.

Note: There is a difference between Init Value (inactive PID block) and Manual Value - Manual Value
is available only while the PID Enable is true, MAN mode is enabled and is limited by the High Limit
and low Limit.

Rules for re-calculation


Parameter ComAp ISA form ComAp → ISA form ISA form → ComAp
isa_gain = comap_gain / comap_gain = isa_gain *
Gain [%] [-]
100.0 100.0
Int [%] [s] isa_int = 100 / comap_int comap_int = 100 / isa_int
Der [%] [s] isa_der = comap_der * 0.06 comap_der = isa_der / 0.06

InteliNeo 6000 1.5.0 Global Guide 1210


Image 7.57 Configuration of PID block

6 back to List of PLC blocks

Up/Down Ctrl Block

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 42

InteliNeo 6000 1.5.0 Global Guide 1211


Inputs

Input Type Negation Range Function


-10 000 .. Control value (Input) = obviously velocity
Input Value Analog No
10 000 output of antecedent PID control block.
Control deviation (= "requested value" -
Control -10 000 .. "actual value") of antecedent block (usually
Analog No
deviation 10 000 PID controller). Works with Deadband
parameter.
When U/D Enable is not true or there is an
invalid value on the Input Value of the block,
U/D Enable Binary Yes 0/1 both the outputs (Output Up or Output Down)
has a value off. If this input is not connected
the controller is enabled.
Period of evaluation (decimation factor of
default PLC period 100ms). The time interval
between the start time of one pulse to start
0,1 ..
Period Analog No time of the next pulse. The period should be
3250,0 s
adjusted according to the Actuator Time and
shouldn't be shorter than the antecedent PID
controller evaluation period.
It is time that the actuator (servo, etc.) needs
Actuator 0,1 ..
Analog No for changing its position from fully closed to
Time 3250,0 s
fully open.
The minimum amount of time a relay is
Min On 0,1 ..
Analog No allowed to be closed (Output Up or Output
Time 3250,0 s
Down is on).
The minimum amount of time a relay is
Min Off 0,1 .. opened (Output Up or Output Down is off)
Analog No
Time 3250,0 s during the constant switching control range.
This time could be zero.
Deadband range (of input Control deviation,
-10 000 .. presumed symmetrical interval) → both
Deadband Analog No
10 000 outputs (Output Up or Output Down) are
inactive (off).
Antecedent controller output reaches the
Low Limit Binary Yes 0/1
Low Limit.
Antecedent controller output reaches the
High Limit Binary Yes 0/1
High Limit.

InteliNeo 6000 1.5.0 Global Guide 1212


In MANual mode force the SCU to activate
Manual Up Binary Yes 0/1
(Manual Down must be inactive) Output Up.
Manual In MANual mode force the SCU to activate
Binary Yes 0/1
Down (Manual Up must be inactive) Output Down.
Manual Mode:
MANual
Binary Yes 0/1 off - AUTomatic mode (default)
Mode
on - MANual mode
Outputs

Output Type Negation Range Function


Output Up Binary Yes 0/1 Actuator control - Raise
Output
Binary Yes 0/1 Actuator control - Lower
Down
Description
The PLC block performs the function of Up/Down Control Unit (Relay Control block) with binary outputs
Up/Down and adjustable regulation period. The function of the block can be disabled by the binary input
U/D Enable. The Input signal corresponds to the speed (velocity = the change of the action variable)
output of the primary controller (Output Velocity of the PID block). The input signal value is expected in
range <-10000; +10000>.
If the Deadband parameter is non-zero, the switching of the outputs (Output Up or Output Down) is
suppressed for input signal Control Deviation smaller than the value of Deadband. The remaining
switching pulse length is still maintained for future evaluation.
If inputs Low Limit or High Limit (primary controller output reaches its limits - due to this the Input signal is
zero), the remaining pulse time is maintained accordingly to perform appropriate output (Output Up or
Output Down) switching.
By activating the binary input MAN, the inputs Manual Up or Manual Down are respected on the outputs
(Output Up or Output Down) - when both the Manual Up or Manual Down is active, both the outputs
Output Up and Output Down are inactive.
Use case:
The U/D Ctrl block (Up/Down relay Control block) is intended for use as an output stage of the
primary controller, converting its analog control action to up/down outputs (PWM controlled).
Block parameters are therefore set according to the characteristics of the actuator connected
onward.
The PID block and U/D Ctrl block connected together thus forms PID controller with relay contrlled
Up / Down outputs.
The U/D Ctrl block itself could also act as converting block from analog value to PWM modulated
signals.
If the U/D Ctrl block is operating in MANual mode, the manual setting of respective outputs
(Output Up / Output Down) is possible.

InteliNeo 6000 1.5.0 Global Guide 1213


Image 7.58 Configuration of Up/Down Ctrl Block

6 back to List of PLC blocks

Group: Ramp functions

Inc/Dec

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 22

Inputs

Input Type Negation Range Function


Rising edge increase value of Output
Increment Binary No 0/1
by 1
Risinge edge decrease value of
Decrement Binary No 0/1
Output by 1
Rising edge resets Output to Default
Reset Binary No 0/1

32 32
Maximum Analog No -2 .. 2 Maximum value of Output
32 32
Default Analog No -2 .. 2 Initial value of Output
Outputs

InteliNeo 6000 1.5.0 Global Guide 1214


Output Type Negation Range Function
32
Output Analog No -2 .. Maximum Output value
Description
The block increments/decrements Output based on rising edge on Increment/Decrement.
If the Increment and Decrement edges arrive simultaneously, the Output value does not change.
If the counter value is at Maximum and incrementation is coming, the counter will be 0 again.
If the counter value is at 0 and decrementing is coming, the counter will have be at Maximum.
The Output can be reset by rising edge on Reset.
The Output has a Resolution and Dimension according to the block settings.
Note: If both the inputs Increment and Decrement are active, the Output value is not changed.

IMPORTANT: When the controller is powered off the Output value is not preserved.

Image 7.59 Configuration of Inc/Dec block

6 back to List of PLC blocks

LowPassFlt

PLC group
Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 40
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Input Value
Time Constant of the
Tau Analog No 0,0 .. 60,0 [s]
filter
Outputs

Output Type Negation Range Function


32 32
Output Analog No -2 .. 2 Filtered Input
Description

InteliNeo 6000 1.5.0 Global Guide 1215


The block performs the function of the first-order low pass filter. Typical usage of this function is filtering
of a value whose instantaneous value fluctuates rapidly around its mean, which is changing slower. The
Output has resolution and dimension based on setting of the block.

Image 7.60 Configuration of LowPassFlt block

6 back to List of PLC blocks

Mov Avg

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 7

Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Input Value
Filter Filter length = length of
Analog No 1 .. 16
Length sample train
Sampling Time interval between
Analog No 0,1 .. 3600,0 [s]
Period samples
Reset (clearing) of filter
Reset Binary No 0/1
internal memory
Filter processing enable
(If this input is not
Enable Binary No 0/1
connected the block is
enabled.)
Outputs

Output Type Negation Range Function


32 32
Output Analog No -2 .. 2 Filtered Input
Description
The block calculates the arithmetic mean of the N most recent samples of the input value with a
selectable sampling interval. The filter uses sample train (sequence of successive samples) for
computation of the filtered value as arithmetic average of N last samples of the input value. The simple

InteliNeo 6000 1.5.0 Global Guide 1216


average computation is used: Typical usage of this function is filtering of a value whose instantaneous
value fluctuates rapidly around its mean, which is changing slower. The Output has resolution and
dimension based on setting of the block.

Image 7.61 Configuration of Moving Average block

6 back to List of PLC blocks

Ramp

PLC group
Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 19
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Value to be ramped
Maximal rising rate of the
32 32 Output per second /minute
Up Analog No -2 .. 2
(based on Time unit
setting)
Maximal lowering rate of the
32 32 Output per second/minute
Down Analog No -2 .. 2
(based on Time unit
setting)
Outputs

Output Type Negation Range Function


32 32
Output Analog No -2 .. 2 Ramped value
Description
This block limits maximal rate of change of Output. The maximal rates Up and Down are adjustable
separately and ramping is based on enabled ramps. Time base of the Up/Down rate is defined by Time
unit setting. The Output has resolution and dimension based on setting of the block.

InteliNeo 6000 1.5.0 Global Guide 1217


Function Description
Enabled Up Output can be ramped only up.
Enabled Down Output can be ramped only down.
Enabled Up/Down Output can be ramped up and down.

Image 7.62 Configuration of Ramp block

6 back to List of PLC blocks

Up/Down

PLC group

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 20

Inputs

Input Type Negation Range Function


Limit 32 32
Analog No -2 .. 2 First limit of Output
Low
Limit 32 32
Analog No -2 .. 2 Second limit of Output
High
Resets Output to Default
Reset Binary No 0/1
Output Value when active
Speed 32 32 Rising rate of Output per
Analog No -2 .. 2
Up second

InteliNeo 6000 1.5.0 Global Guide 1218


Speed 32 32 Lowering rate of Output
Analog No -2 .. 2
Down per second
Up Binary No 0/1 Activates rising of Output
Activates lowering of
Down Binary No 0/1
Output
Default
32 32
Output Analog No -2 .. 2 Initial value of Output
Value
Outputs

Output Type Negation Range Function


Output Analog No Limit 1 .. Limit 2 Output value
Description
This block works as an analog ramp controlled by binary inputs Up and Down with a defined rate of
increase/decrease.
The ramp speed is adjusted by Speed Up and Speed Down.
Time unit of the speed of change is defined by Time unit setting.
The Output limitation is set by Limit 1 and Limit 2. The default value of Output is set by Default Output
Value.
Activate Reset to reset Output to Default Output Value. The Output has resolution and dimension
based on setting of the block.
IMPORTANT: If both the inputs Up and Down are active, the Output is set to Default
Output Value.

InteliNeo 6000 1.5.0 Global Guide 1219


Image 7.63 Configuration of Up/Down block

6 back to List of PLC blocks

Group: Other functions

Analog Switch 8

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

Inputs

Input Type Negation Range Function


32 32
Input 1 Analog No -2 .. 2 Input value 1
32 32
Input 2 Analog No -2 .. 2 Input value 2

32 32 Input value 3
Input 3 Analog No -2 .. 2
(optional)
32 32
Input 4 Analog No -2 .. 2 Input value 4

InteliNeo 6000 1.5.0 Global Guide 1220


(optional)

32 32 Input value 5
Input 5 Analog No -2 .. 2
(optional)

32 32 Input value 6
Input 6 Analog No -2 .. 2
(optional)

32 32 Input value 7
Input 7 Analog No -2 .. 2
(optional)

32 32 Input value 8
Input 8 Analog No -2 .. 2
(optional)
Input SW 1 Binary No 0/1 Switch input 1
Input SW 2 Binary No 0/1 Switch input 2
Input SW 3 Binary No 0/1 Switch input 3
Outputs

Output Type Negation Range Function


Switch output
32 32
Output Analog No -2 .. 2 according to the SW 1,
SW 2 and SW 3
Description
The block works as an analog multiplexer. The output value could be selected from up to 8 inputs
according to the 'Input SW 3', 'Input SW 2' and 'Input SW 1' state is appropriate input value copied to the
output, see the table below.

Input SW 3 Input SW 2 Input SW 1 Output


0 0 0 Input 1
0 0 1 Input 2
0 1 0 Input 3
0 1 1 Input 4
1 0 0 Input 5
1 0 1 Input 6
1 1 0 Input 7
1 1 1 Input 8

InteliNeo 6000 1.5.0 Global Guide 1221


Image 7.64 Configuration of Analog Switch 8 block

6 back to List of PLC blocks

Bit Sum 16

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 53

Inputs

Input Type Negation Range Function


Input 1 Binary Yes 0/1 Input 1
Input 2 Binary Yes 0/1 Input 2
Input 3 Binary Yes 0/1 Input 3 (optional)
Input 4 Binary Yes 0/1 Input 4 (optional)
Input 5 Binary Yes 0/1 Input 5 (optional)

InteliNeo 6000 1.5.0 Global Guide 1222


Input 6 Binary Yes 0/1 Input 6 (optional)
Input 7 Binary Yes 0/1 Input 7 (optional)
Input 8 Binary Yes 0/1 Input 8 (optional)
Input 9 Binary Yes 0/1 Input 9 (optional)
Input 10 Binary Yes 0/1 Input 10 (optional)
Input 11 Binary Yes 0/1 Input 11 (optional)
Input 12 Binary Yes 0/1 Input 12 (optional)
Input 13 Binary Yes 0/1 Input 13 (optional)
Input 14 Binary Yes 0/1 Input 14 (optional)
Input 15 Binary Yes 0/1 Input 15 (optional)
Input 16 Binary Yes 0/1 Input 16 (optional)
Outputs

Output Type Negation Range Function


Output value = sum of active inputs
Output 1 Analog No 0 .. Max [-]
(InputX has value true)
Output value = sum of inactive inputs
Output 0 Analog No 0 .. Max [-]
(InputX has value false)
Description
The PLC block performs active/inactive inputs summation and it gives analog value output as a summary
of activated Binary input signals or vice versa as secondary analog output summary of deactivated
Binary input signals.

InteliNeo 6000 1.5.0 Global Guide 1223


Image 7.65 Configuration of Bit Sum 16 block

6 back to List of PLC blocks

Circuit Breaker

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 58

Inputs

Input Abbr. Type Range Function


According to the Close/Open value
Close/Open C/O Binary 0/1 the circuit breaker closes/opens
(level control)
The rising edge of the Close signal
Close Close Binary 0/1
forces the breaker to close (edge

InteliNeo 6000 1.5.0 Global Guide 1224


control)
The rising edge of the Open signal
Open Open Binary 0/1 forces the breaker to open (edge
control)
Feedback from breaker (aux.)
Feedback FB Binary 0/1
contactor
Negative Feedback NFB Binary 0/1 Inverted Feedback
Disabled Dis Binary 0/1 Control (closing) disabled
Breaker (spring) charged (has
Charged Chrg Binary 0/1
tension)
Outputs

Output Abbr. Type Range Function


ON Coil ON Binary 0/1 On (switching) coil
OFF Coil OFF Binary 0/1 Off (tripping) coil
UV Coil UV Binary 0/1 Under voltage coil
Output Close/Open C/O Binary 0/1 Close / Open signal
Status Close/Open Status Binary 0/1 State of circuit breaker control
Fail to Close FtC Binary 0/1 Failed to close
Description
This block performs general Circuit Breaker (CB) control based on the state machine principle.
Inputs
Close/Open: Input for level control of breaker close/open control. Since the block contains a state
machine and the possibility of impulse (edge) control is required, an edge response is also
introduced for level control as well, i.e., the rising edge is interpreted as a CB Close request and a
falling edge as a CB Open request.
Close: The request to switch on (Close CB) - minimum pulse length is 200 ms - manual issue,
edge responsive.
Open: The request to switch off (Open CB) - minimum pulse length is 200 ms - manual issue,
edge responsive.
Feedback: Feedback from auxiliary breaker contacts, not required to configure. (If not configured,
the mismatch between requested and breaker state is not evaluated; it is assumed that the
breaker is currently in the desired state).
Feedback Negative: It is not required to be configured together with the CBFeedback input.
However, if Feedback Negative is configured, the Feedback input must be configured too. Then,
not only the mismatch between the desired state and the feedback is always evaluated, but also
the mismatch between the two feedbacks.
Disable: If the CB is disconnected (opened), the Disable input will blocks its switching (closing). If
the CB has already been switched on, this input does not open it. It is not necessary to configure
this input = if the input is not configured, it is evaluated as inactive.
Charged: This input has the same function (but in inverse logic) as CBDisabled, it is used only in
conjunction with information about the breaker spring tension. Configuration of the input is not
required; if the input is not configured, it is evaluated as active.

InteliNeo 6000 1.5.0 Global Guide 1225


Outputs
ON Coil: Switching signal for ON (closing) CB coil - pulse lenght of 5 sec (the feedback
confirmation is expected within this 5 sec).
OFF Coil: Tripping signal for OFF (opening) CBcoil - pulse lenght of 5 sec (the feedback
confirmation is expected within this 5 sec).
UV Coil: Level signal for UV (under voltage) CB coil = remains on till the CB should be opened.
Output Close/Open: Request signal for closing/opening the circuit breaker (level control).
Status Close/Open: Information about the breaker status based on the evaluation of the
Feedback and/or Feedback Negative signals.
Failed To Close: In case of a failed attempt to close the CB (second attempt), a 5s pulse is
generated at the output. A user protection may be configured on it.
Failed To Open: In case of a failed attempt to open the CB, a 5s pulse is generated at the output.
A user protection may be configured on it.
Other Fail: Information about other non-correlated CB events (states). A 5s pulse is generated at
the breaker output in the event of a mismatch between Feedback and Feedback Negative
and/or where Feedback is lost or, conversely, Feedback is set in a situation where a change in
CB state is unexpected.

Image 7.66 Configuration of Circuit Breaker block

« back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1226


Convert

PLC group Others


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 52
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Input value
Outputs

Output Type Negation Range Function

32 32 Converted Input
Output Analog No -2 .. 2
value
The attribute of
Output Binary Yes 0/1 invalid data on
output
Description
The block converts the Input based on selected resolution and dimension, and reflects it to the Output.
Dimension is converted based on user configuration without any extra recalculation. Resolution is
converted and recalculation is used.
Example: If the input is 100,5 W and the convert block is used to convert dimensions to kW with
resolution 1, the output shows 101 kW.

Note: Conversion is done to Integer32, if the input value is out of Integer32 range, output value is set to
invalid status and error output is activated.

Image 7.67 Configuration of Convert block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1227


Counter

PLC group Others


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 13
Inputs

Input Type Negation Range Function


Input at which the edges
Input Count Up Binary No 0/1
are counted

32 Counter value limit for


Input Preset Limit Analog No 0 .. 2
activation of the output
Input Clear Binary No 0/1 Reset input
Outputs

Output Type Negation Range Function


Output is activated when the counter value
Output Binary No 0/1
exceeds the limit
Analog value that shows Actual Counter
Actual Value
Counter Analog No N/A Lowest available value from:
Value <PLC Resource 1 (page 935) to
PLC Resource 16 (page 938)>
Description
The block works as a counter of edges (selectable rising, falling or both) with reset input and adjustable
counting limit. The maximal counter value is 2 147 483 647. The counter value is lost when the controller
is switched off. The output is activated when the counter value is equal to or higher than Input Preset
Limit and stays active until the block reset is done using Input Clear. Activating of the Input Clear resets
the counter value to 0 and deactivates the output. Holding the Input Clear active blocks the counting.
IMPORTANT: The counter value is lost when the controller is switched off.

Image 7.68 Configuration of the Counter block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1228


Comp. 4

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 49

Inputs

Input Type Negation Range Function


Bit 0,4,8,12,16,20,24,28 -
Input 1 Binary Yes 0/1
according to selected group of bits.
Bit 1,5,9,13,17,21,25,29 -
Input 2 Binary Yes 0/1
according to selected group of bits.
Bit 2,6,10,14,18,22,26,30 -
Input 3 Binary Yes 0/1
according to selected group of bits.
Bit 3,7,11,15,19,23,27,31 -
Input 4 Binary Yes 0/1
according to selected group of bits.
Outputs

Output Type Negation Range Function


-2 147 483 647 .. 2 147 483 Value to be
Output Analog No
647 "composed" to bits
Description
The block converts selected input bits to analog form and provides the output analog value.The resulting
quad of bits is placed in the Output value within the selected bit range (Bits).

Image 7.69 Configuration of Comp. 4 block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1229


Comp. 16

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 50

Inputs

Input Type Negation Range Function


According to selected group of
Input 1 Binary Yes 0/1
bits.
According to selected group of
Input 2 Binary Yes 0/1
bits.
... ... ... ... ...
According to selected group of
Input 15 Binary Yes 0/1
bits.
According to selected group of
Input 16 Binary Yes 0/1
bits.
Outputs

Output Type Negation Range Function


-2 147 483 647 .. 2 147 483 Value to be
Output Analog No
647 "decomposed" to bits
Description
The block converts selected input bits to analog form and provides the output analog value.It is possible
to select lower bits 0-15 or upper bits 16-31 so it is possible to compose 32 bit value by using of two
composers.

InteliNeo 6000 1.5.0 Global Guide 1230


Image 7.70 Configuration of Comp. 16 block

6 back to List of PLC blocks

Decomp. 4

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 24

Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Value to be "decomposed" to bits
Outputs

Output Type Negation Range Function


Bit 0,4,8,12,16,20,24,28 -
Output 1 Binary Yes 0/1
according to selected group of bits.
Bit 1,5,9,13,17,21,25,29 -
Output 2 Binary Yes 0/1
according to selected group of bits.

InteliNeo 6000 1.5.0 Global Guide 1231


Bit 2,6,10,14,18,22,26,30 -
Output 3 Binary Yes 0/1
according to selected group of bits.
Bit 3,7,11,15,19,23,27,31 -
Output 4 Binary Yes 0/1
according to selected group of bits.
Description
The block converts the input analog value to binary form and provides selected bits as binary
outputs.The input four bits are selected by bit range selection (Bits).

Image 7.71 Configuration of Decomp. 4 block

6 back to List of PLC blocks

Decomp. 16

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 48

Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Value to be "decomposed" to bits
Outputs

InteliNeo 6000 1.5.0 Global Guide 1232


Output Type Negation Range Function
According to selected group of
Output 1 Binary Yes 0/1
bits.
According to selected group of
Output 2 Binary Yes 0/1
bits.
... ... ... ... ...
According to selected group of
Output 15 Binary Yes 0/1
bits.
According to selected group of
Output 16 Binary Yes 0/1
bits.
Description
The block converts the input analog value to binary form and provides selected bits as binary outputs.It is
possible to select lower bits 0-15 or upper bits 16-31 so it is possible to decompose 32 bit value by using
of two decomposers.

Image 7.72 Configuration of Decomp. 16 block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1233


Differ

PLC group Others


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 55
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 -1 .. +2 -1 Input value
Clear Binary Yes 0/1 Clear (reset) internalvalues
Sampling Sampling period (interval
Analog No 0,1 - 3600,0 s
Interval between samples)
Outputs

Output Type Negation Range Function


Difference-by-Time of Input
/ 32 32
Analog No -2 -1 .. +2 -1 values evaluated over four
Difference
samples
The Input value sample
32 32 delayed one step (given by
Z-1 Analog No -2 -1 .. +2 -1
the sampling interval
parameter)
Description
The block performs difference-by-time evaluation of analog input. Internally the block have memory for 4
consecutive values (sample train), a one-step delayed sample is available at output Z-1. The time
interval between the samples is a block parameter and is selected by the user during the block
configuration. The sampling interval can be multiple of 0,1 sec only.
Output is calculated from four successive internal values based on this equation :

Image 7.73 Configuration of the Differ block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1234


Heartbeat

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 43

Inputs

Input Type Negation Range Function


Incoming binary (rising) edge leads to
reset Heartbeat counter. If there is
Input 1 Binary Yes 0/1 configured Input 2, the Reset action is
dependent on the selected operation
between inputs 1 and 2 (OR/ XOR).
The optional input signal, if it is
configured, the Reset action is
Input 2 Binary Yes 0/1
dependent on the selected operation
between inputs 1 and 2 (OR / XOR).
HeartBeat checking/counting period
(max. approx. 100 min). It should be at
Checking
Analog No 0,2 .. 6500,0 s least twice the incoming checked signal
Period
period (at least 2 PLC execution
periods).
Reset Active value of this input clear output to
Binary Yes 0/1
Output default (off) value.
Heartbeat block enable. When Enable is
not active or there is an invalid value on
Input 1 of the block, the output (Output)
Enable Binary Yes 0/1 has a value off, the internal Heartbeat
counter is reset to the default value. If
this input is not connected the block is
enabled.
Outputs

Output Type Negation Range Function


Output Binary Yes 0/1 Output value
Description
The PLC block performs Heart Beat signal checking.
The Checking Period parameter specifies both the Heart Beat checking period and the reload value
of the internal counter. The resolution of the counter is 0,1 seconds.
The internal counter is re-set to the Checking Period value in the cases (Reset Action):
The Enable input is false.
The internal counter reaches the zero value.
The Heart Beat check operation is valid:
On Input 1 is detected rising edge (only Input 1 is configured) or on the Input 2 is detected rising

InteliNeo 6000 1.5.0 Global Guide 1235


edge (only Input 2 is configured).
Both Input 1 and Input 2 are configured:
OR mode:
If the rising edge is detected either on Input 1 or Input 2.
XOR mode:
If the rising edge is detected on Input 1 and followed by detecting the falling edge on Input
2.
If the falling edge is detected on Input 2 and followed by detecting the rising edge on Input
1.
The above conditions must be met before the counter counts down to zero to ensure that the
incoming heartbeat signal is live. The Output binary signal is set (on) if the internal counter counts
down to zero. If the Reset Output input is configured and the input is active (Reset Output is set), the
Output is cleared to the default (off) value. If the Reset Output input is not configured, the Output can
be cleared by any successful check operation described above.
If the Enable input is configured and the input is inactive (Enable is reset), the internal counter is
reloaded to the Checking Period value, counting stops and the Output is cleared to default (off) value.
If the Enable input is not configured or the input is active (Enable is set), the internal counter is
counting down and the Heart Beat checking functionality is excuted.

Image 7.74 Configuration of Heartbeat block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1236


Hold

PLC group Others


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 37
Inputs

Input Type Negation Range Function


32 32
Input Analog No -2 .. 2 Input value
Hold Binary No 0/1 Input triggering the function
Outputs

Output Type Negation Range Function


32 32
Output Analog No -2 .. 2 Hold output
Description
The block is holding Input value based on value of Hold and selected mode. The Output has resolution
and dimension based on setting of the block.

Mode Description
The block behaves like analog memory. Input Hold behaves like the reload trigger and
Edge
reacts on rising edge. The initial value of the Output after restart of the controller is 0.
The block is like a mirror of the Input while the Hold is inactive. The value of Output is
Level
latched at the last value while Hold is active.

Image 7.75 Principle of the Hold modes

InteliNeo 6000 1.5.0 Global Guide 1237


Image 7.76 Configuration of the Hold block

6 back to List of PLC blocks

PF Conv

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 57

Inputs

Input Abbr. Type Range Function


Input Power 32 32
* PF Analog -2 -1 .. +2 -1 Power Factor
factor
PF ASCII annotation:
32 32 "L" = inductive, lagging; "R" =
Input Character Char Analog -2 -1 .. +2 -1
resistive; "C" = capacitive,
leading
Outputs

Output Abbr. Type Range Function


Output Power 32 32
PF Analog -2 -1 .. +2 -1 Power Factor
Factor
PF ASCII annotation:
32 32 "L" = inductive, lagging; "R" =
Output Character Char Analog -2 -1 .. +2 -1
resistive; "C" = capacitive,
leading
Load type indication: 0 =
32 32
Output Load Type Type Analog -2 -1 .. +2 -1 inductive, lagging; 1 =
capacitive, leading
32 32
Data Invalid Err Analog -2 -1 .. +2 -1 Ramped value
Description
This block perform format conversion of Input Power Factor to Output Power Factor format. The
conversion type is set using the Conversion option.
There are three power factor formats:

InteliNeo 6000 1.5.0 Global Guide 1238


ComAp1 format: power factor value in the range <0,000 ; 2,000>
• value in the interval <0,000; 1,000) denotes the lagging (L) power factor
• value in the interval (1,000; 2,000> denotes the leading (C) power factor
• value 1,000 denotes the resistive (R) power factor
ComAp2 format: power factor value in the range <0,000; 1,000> + additional load character value
{'L', 'R', 'C'} = 8 bit character
• value in the interval <0,000; 1,000) + 'L' character denotes the lagging (L) power factor
• value in the interval <0,000; 1,000) + 'C' denotes the leading (C) power factor
• value 1,000 + 'R' character denotes the resistive (R) power factor
R = 82 ASCII / L = 76 ASCII / C = 67 ASCII
EEI format: power factor value in the range <-1,000 ; 1,000>
• value in the interval <-1,000; 0,000) denotes the lagging (L) power factor
• value in the interval (0,000; 1,000> denotes the leading (C) power factor
• value 0,000 denotes the resistive (R) power factor
The following figure explains the relations between the power factor formats used.

Image 7.77 Power factor formats ranges

The Output has a Resolution and Dimension according to the block settings.

InteliNeo 6000 1.5.0 Global Guide 1239


Image 7.78 Configuration of PfConv block

« back to List of PLC blocks

Poly Appx

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 47

Inputs

Input Type Negation Range Function


32 32
Input 1 Analog Yes -2 .. 2 Input value
Low Limit Analog Yes Same as Input Low limit of output value
High Limit Analog Yes Same as Input High limit of output value
Outputs

Output Type Negation Range Function

32 32 Result of the polynomial


Output Analog No -2 .. 2
approximation of input value.
Description
The PLC block performs the polynomial approximation function of the input variable by calculating a
polynomial (up to 6th order). The result is limited by lower and upper bound parameters (limitation) and
passed to the output variable.

InteliNeo 6000 1.5.0 Global Guide 1240


Image 7.79 Configuration of Polynomial Approximation block

6 back to List of PLC blocks

PWR Calc

PLC group Others

Related FW 1.5.0

Related applications MINT, MPTM

PLC Block ID 56

Inputs

Input Abbr. Type Range Function


Input Active 32 32
P Analog -2 -1 .. +2 -1 Active power
Power
Input Reactive 32 32
Q Analog -2 -1 .. +2 -1 Reactive power
Power
Input Apparent 32 32
S Analog -2 -1 .. +2 -1 Apparent power
Power
Input Power 32 32
PF Analog -2 -1 .. +2 -1 Power factor
Factor

32 32 Load type (0 = inductive,


Input Load Type Type Binary -2 -1 .. +2 -1
lagging; 1 = capacitive, leading)
Outputs

InteliNeo 6000 1.5.0 Global Guide 1241


Output Abbr. Type Range Function
Output Active 32 32
P Analog -2 -1 .. +2 -1 Active power
Power
Output Reactive 32 32
Q Analog -2 -1 .. +2 -1 Reactive power
Power
Output Apparent 32 32
S Analog -2 -1 .. +2 -1 Apparent power
Power
Output Power 32 32
PF Analog -2 -1 .. +2 -1 Power Factor
Factor
Output Deformed 32 32 Deformed Power (only with all
D Analog -2 -1 .. +2 -1
Power powers P, Q, S are provided)
32 32
Data Invalid Err Binary -2 -1 .. +2 -1 Data invalid
Description
The block calculates the output power variable values from the selected input values (for example: needs
of Q and PF from provided P and S). The calculation type is set using the Calculation option, the
calculation of the remaining output values is performed if the necessary 2 analog inputs are set correctly.
Note: The Power Factor input value is expected in the ComAp PF1 format (value in the range <0,000 ;
2,000>) with following meaning:
• value in the interval <0,000; 1,000) denotes the lagging (L) power factor
• value in the interval (1,000; 2,000> denotes the leading (C) power factor
• value 1,000 denotes the resistive (R) power factor

The Output has a Resolution and Dimension according to the block settings.
Note: The block performs the Resolution conversion.

Oper P Q S PF D
In
P,Q
P Q not valid
Out
S,PF
In
P,S
P S not valid
Out
Q, PF
In
P,PF
P PF not valid
Out
Q,S

InteliNeo 6000 1.5.0 Global Guide 1242


In
Q,S
Q S not valid
Out
P,PF
In
Q,PF
Q PF not valid
Out
P,S
In
P,Q,S
P Q S
Out
D,PF

Image 7.80 Configuration of PWR Calc block

« back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1243


Validator

PLC group Others


Related FW 1.5.0
Related applications MINT, MPTM
PLC Block ID 54
Inputs

Input Type Negation Range Function


32 32
Validate Analog No -2 -1 .. +2 -1 Input value
32 32
Replace Analog No -2 -1 .. +2 -1 Replacement value
Force Binary Yes 0/1 Forcing of replacement
Outputs

Output Type Negation Range Function


Output set to Validate or Replace
32 32
Output Analog No -2 -1 .. +2 -1 based on the value of Validate
and/or Force inputs
Validate input has an invalid
Invalid Binary Yes 0/1
value
Description
Block checks (validate) if the input value has a valid value (i.e. is not marked with Invalid Flag). The
Output value is determined according to the following rules:

Function Validate
Input Validate Input Force Output O Output Err
Valid value 0 Validate 0
Invalid value 0 Replace 1
Valid value 1 Replace 0
Invalid value 1 Replace 1

Image 7.81 Configuration of Validator block

6 back to List of PLC blocks

InteliNeo 6000 1.5.0 Global Guide 1244


9.2 Alarms
What alarms are:
The controller evaluates two levels of alarms. For more information see Alarm Management on page 122.

9.2.1 Alarm levels in the controller


9.2.2 Alarms level 1 1245
9.2.3 Alarms level 2 1278
9.2.4 Other alarms 1298

9.2.2 Alarms level 1


What alarms level 1 are:
The level 1 alarm indicates that a value or parameter is out of normal limits, but has still not reached critical
level.

InteliNeo 6000 1.5.0 Global Guide 1245


List of alarms level 1

Warning 1248 Wrn P(Um) Fail 1257 Alarm Only 1269


Wrn Alarm e-mail 1 Fail 1248 Wrn PF Control Fail 1258 Alarm List Indication 1269
Wrn Alarm e-mail 2 Fail 1248 Wrn PF/Q IMP/EXP Fail 1258 ALI Bus Ph L1 Inverted 1269
Wrn Alarm e-mail 3 Fail 1248 Wrn PF(Pm) Fail 1259 ALI Bus Ph L2 Inverted 1270
Wrn Alarm e-mail 4 Fail 1248 Wrn PVCB Fail To Close 1259 ALI Bus Ph L3 Inverted 1270
Wrn Backup Controller Wrn PVCB Fail To Open 1260 ALI Bus Ph Rotation
Failed 1249 Opposite 1270
Wrn PVCB Fail 1260
Wrn Backup Not Ready 1249 ALI BCB Closing Is
Wrn Q Control Fail 1261
Wrn Battery Overvoltage 1249 Blocked 1271
Wrn Q&U Protection 1262
Wrn Battery ALI CAN Mode
Wrn Q(P) Fail 1262
Undervoltage 1250 Inconsistency 1271
Wrn Q(Um) Fail 1263
Wrn Brute Force ALI Daily Battery Cycles
Wrn Qref/Ulim Fail 1263 Reached 1271
Protection Active 1250
Wrn Redundant CAN ALI BESS Ph L1 Inverted 1272
Wrn CAN2 Empty 1250
inconsistency 1264
Wrn Default Password 1251 ALI BESS Ph L2 Inverted 1272
Wrn RTC Battery Flat 1264
Wrn ECU Communication ALI BESS Ph L3 Inverted 1272
Wrn Reverse
Fail 1251 ALI BESS Ph Rotation
Synchronization Fail 1265
Wrn Event e-mail 1 Fail 1251 Opposite 1273
Wrn SD Card Failed 1265
Wrn Event e-mail 2 Fail 1251 ALI Redundant CAN
Wrn SD Card File System Error 1273
Wrn Event e-mail 3 Fail 1252 Failed 1265
ALI SD Card Not
Wrn Event e-mail 4 Fail 1252 Wrn SNMP TRAP 1 Fail 1265 Compatible 1273
Wrn Frequency Wrn SNMP TRAP 2 Fail 1266 ALI SD Card In Slot 1274
Regulation Limit 1252
Wrn SOC High Alarm 1266 ALI SD Card Full 1274
Wrn Hot Swap
Wrn SOC Low Alarm 1266 ALI SD Card
Configuration Incorrect 1252
Wrn Soft Transfer Fail 1267 Formatting/Mounting 1274
Wrn Hot Swap Data
Synchro Fail 1253 Wrn Stop Fail 1267 ALI Mains Ph L1 Inverted 1275

Wrn Load IMP/EXP Fail 1253 Wrn SW Key CAN ALI Mains Ph L2 Inverted 1275
Redundancy Error 1267 ALI Mains Ph L3 Inverted 1275
Wrn Long Term History
Fail 1254 Wrn SW Key Hot Swap ALI Mains Ph Rotation
Error 1267 Opposite 1275
Wrn Master Controller
Failed 1254 Wrn Test UPQF 1268 ALI Start Blocking 1276
Wrn MCB Fail 1254 Wrn Unsupported PMS ALI Wrong Power Format 1276
Mode 1268
Wrn MCB Fail To Close 1255 Alarm List + History
Wrn Universal Genset Indication 1276
Wrn MCB Fail To Open 1256
Overflow 1268 AHI SyncNotAllowed 1276
Wrn Override All Sd 1256
Wrn Voltage Regulation
History Record Only 1277
Wrn Password reset e- Limit 1268
mail addr is not set 1257 Hst Pave 1277
Wrong PLC Configuration1269
Wrn P for Q Fail 1257 Hst ROCOF 1 1277

InteliNeo 6000 1.5.0 Global Guide 1246


Hst ROCOF2 1277
Hst ROCOF3 1277
Hst ROCOF4 1278
Hst Vector Shift 1278
6 back to Alarms

InteliNeo 6000 1.5.0 Global Guide 1247


Warning

Wrn Alarm e-mail 1 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Alarm e-mail 1 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 815
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted by setpoint E-mail Address 1 (page 683) and email
Description
wasn’t send.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn Alarm e-mail 2 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Alarm e-mail 2 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 816
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted by setpoint E-mail Address 2 (page 684) and email
Description
wasn’t send.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn Alarm e-mail 3 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Alarm e-mail 3 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 817
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted by setpoint E-mail Address 3 (page 684) and email
Description
wasn’t send.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn Alarm e-mail 4 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Alarm e-mail 4 Fail
Alarm evaluated All the time

InteliNeo 6000 1.5.0 Global Guide 1248


Related applications MINT, MPTM
Alarm ID 818
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted by setpoint E-mail Address 4 (page 684) and email
Description
wasn’t send.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn Backup Controller Failed

Alarm Type Warning (page 198)


Alarmlist message Wrn Backup Controller Failed
Alarm evaluated Only if Hot Swap Redundancy (page 371) != Disabled
Related applications MINT, MPTM
Alarm ID 1289
This alarm is activated on Hot Swap Redundancy (page 160) master
Description controller when master controller does not detect the HOT SWAP HEARTBEAT
(PAGE 1083) signal from backup.

6 back to List of alarms level 1

Wrn Backup Not Ready

Alarm Type Warning (page 198)


Alarmlist message Wrn Backup Not Ready
Alarm evaluated Only if Hot Swap Redundancy (page 371) = Master
Related applications MINT, MPTM
Alarm ID 1146
This alarm is related to the Hot Swap Redundancy (page 160). It is activated
when the BACKUP controller has announced any 2nd level alarm while the
Description MASTER controller does not indicate such alarm.
In this case, the BACKUP is unable to take over the control if Master controller
fails. This is a marginal issue and may be caused due to wrong configuration.

6 back to List of alarms level 1

Wrn Battery Overvoltage

Alarm Type Warning (page 198)


Alarmlist message Wrn Battery Overvoltage
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 941
This alarm is activated when Battery Voltage (page 867) is over Battery
Overvoltage (page 389) for period longer than Battery <> Voltage Delay
Description
(page 389).
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

InteliNeo 6000 1.5.0 Global Guide 1249


6 back to List of alarms level 1

Wrn Battery Undervoltage

Alarm Type Warning (page 198)


Alarmlist message Wrn Battery Undervoltage
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 940
This alarm is activated when Battery Voltage (page 867) is bellow Battery
Undervoltage (page 389) for period longer than Battery <> Voltage Delay
Description
(page 389).
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

Wrn Brute Force Protection Active

Alarm Type Warning (page 198)


Alarmlist message Wrn Brute Force Protection Active
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1237
This alarm is activated when account break protection detects possible attack
and at least one account is blocked according to Account break protection
(page 231) rules.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).
Note: In case that the alarm stays active even that it should already be
Description inactive, do the following to get rid of it:
1. Disconnect all peripheries (displays, ethernet, etc.)
2. Wait for 20 minutes - the alarm should become inactive
3. Connect with InteliConfig using USB - Quick connection
4. Acknowledge the alarm

6 back to List of alarms level 1

Wrn CAN2 Empty

Alarm Type Warning (page 198)


Alarmlist message Wrn CAN Intercontroller Empty
Alarm evaluated Only if CAN Intercontroller Empty Check (page 398) = Enabled
Related applications MINT, MPTM
Alarm ID 46
This alarm is activated when controller is alone on Intercontroller CAN
(⑧ CAN2A (page 46) and/or ⑦ CAN2B (page 46) ) and setpoint CAN
Description
Intercontroller Empty Check (page 398) = Enabled.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

InteliNeo 6000 1.5.0 Global Guide 1250


6 back to List of alarms level 1

Wrn Default Password

Alarm Type Warning (page 198)


Alarmlist message Wrn Default Credentials
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1071
This alarm is active until the default password for administrator account is
Description
changed.
6 back to List of alarms level 1

Wrn ECU Communication Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn ECU Communication Fail
With configured LBO ECU POWER RELAY (PAGE 1074) - only when this LBO is
Alarm evaluated active.
Without configured LBO ECU POWER RELAY (PAGE 1074) - all the time
Related applications MINT, MPTM
This alarm occurs when an ECU is configured, but the communication with the
Description
ECU is not established or has dropped out.
6 back to List of alarms level 1

Wrn Event e-mail 1 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Event e-mail 1 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 734
The alarm indicates that there was a request to send an event email to email
Description address which is adjusted by setpoint E-mail Address 1 (page 683) and email
wasn’t send.
6 back to List of alarms level 1

Wrn Event e-mail 2 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Event e-mail 2 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 735
The alarm indicates that there was a request to send an event email to email
Description address which is adjusted by setpoint E-mail Address 2 (page 684) and email
wasn’t send.

InteliNeo 6000 1.5.0 Global Guide 1251


6 back to List of alarms level 1

Wrn Event e-mail 3 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Event e-mail 3 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 736
The alarm indicates that there was a request to send an event email to email
Description address which is adjusted by setpoint E-mail Address 3 (page 684) and email
wasn’t send.
6 back to List of alarms level 1

Wrn Event e-mail 4 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Event e-mail 4 Fail
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 737
The alarm indicates that there was a request to send an event email to email
Description address which is adjusted by setpoint E-mail Address 4 (page 684) and email
wasn’t send.
6 back to List of alarms level 1

Wrn Frequency Regulation Limit

Alarm Type Warning (page 198)


Alarmlist message Wrn Frequency Regulation Limit
Alarm evaluated While BESS is running
Related applications MINT, MPTM
Alarm ID 151
This alarm is activated when Frequency Regulator Output (page 862) stays
close to Frequency Governor Low Limit (page 467) or Frequency
Description Governor High Limit (page 467) for at least 2 seconds and will remain active
as long as the cause is present.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 1

Wrn Hot Swap Configuration Incorrect

Alarm Type Warning (page 198)


Alarmlist message Wrn Hot Swap Configuration Incorrect
Only if Hot Swap Redundancy (page 371) != Disabled and Wrn SW Key Hot
Alarm evaluated
Swap Error (page 1267) is not present in the alarmlist
Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 1252


Alarm ID 1465
This alarm is activated when Hot Swap Redundancy (page 160) is missing
the correct configuration of mandatory LBI and LBO.
List of mandatory objects:
LBI HOT SWAP CTRL BLOCK (PAGE 1005)

Description LBI HOT SWAP HEARTBEAT DETECT (PAGE 1005)


LBO HOT SWAP SWITCH (PAGE 1083)
LBO HOT SWAP HEARTBEAT (PAGE 1083)

IMPORTANT: All mandatory objects have to be configured to physical


input/output of the controller.

6 back to List of alarms level 1

Wrn Hot Swap Data Synchro Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Hot Swap Data Synchro Fail
Alarm evaluated Only if Hot Swap Redundancy (page 371) != Disabled
Related applications MINT, MPTM
Alarm ID 1426
This alarm is activated when communication between Hot Swap Redundancy
(page 160) master and backup controllers failed.This can be caused because
Description
of wrong configuration or wiring. While this alarm is active the backup controller
doesn't have the data which needs for the smooth transition.

6 back to List of alarms level 1

Wrn Load IMP/EXP Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Load IMP/EXP Fail
Alarm evaluated Only if Application Mode (page 885) = MPTM
Related applications MINT, MPTM
Alarm ID 1448
This alarm is active when Load Control PTM Mode (page 352) = Imp/Exp but
Mains Measurement P is unavailable.
When this alarm is active, load is controlled as if Load Control PTM Mode
(page 352) = Baseload.
Alarm is caused by:
Description Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and
LAI MAINS MEASUREMENT P (PAGE 1124) is not configured
Value from LAI Mains Measurement P (page 364) has Invalid flag
(page 691)
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

InteliNeo 6000 1.5.0 Global Guide 1253


6 back to List of alarms level 1

Wrn Long Term History Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Long Term History Fail
Alarm evaluated Only when Long Term History (page 401) = Enabled
Related applications MINT, MPTM
Alarm ID 1281
This alarm is activated when Long Term History (page 401) = Enabled but for
Description any reason it is not possible to write the history onto the SD card.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

Wrn Master Controller Failed

Alarm Type Warning (page 198)


Alarmlist message Wrn Master Controller Failed
Alarm evaluated Only if Hot Swap Redundancy (page 371) != Disabled
Related applications MINT, MPTM
Alarm ID 1288
This alarm is activated on Hot Swap Redundancy (page 160) backup
Description controller when backup controller does not detect the HOT SWAP HEARTBEAT
(PAGE 1083) signal from master.

6 back to List of alarms level 1

Wrn MCB Fail

Alarm Type Warning (page 198)


Alarmlist
Wrn MCB Fail
message
Alarm
Only if MCB Control Mode (page 368) = Internal
evaluated
Related
MPTM
applications
Alarm ID 90
This alarm is activated when there is a problem with position of the circuit breaker.
LBI MCB FEEDBACK (PAGE 1012) does not match expected position given by
LBO MCB CLOSE/OPEN (PAGE 1090).
There is a mismatch between LBI MCB FEEDBACK (PAGE 1012) and MCB
FEEDBACK NEGATIVE (PAGE 1013).
Description
Self-opening of breaker with Mains parameters without limits – not
considered as fault, MCB open command is issued when Mains fails according to
the setpoint MCB Opens On (page 1).
Self-closing of breaker with Mains parameters with limits – not considered
as fault, MCB close command is issued after MCB Close Delay (page 535).

InteliNeo 6000 1.5.0 Global Guide 1254


Image 7.82 MCB Fail

This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

Wrn MCB Fail To Close

Alarm Type Warning (page 198)


Alarmlist
Wrn MCB Fail To Close
message
Alarm
Only if MCB Control Mode (page 368) = Internal
evaluated
Related
MPTM
applications
Alarm ID 1553
This alarm is activated when there is a problem with circuit breaker position while
closing.
LBO MCB CLOSE/OPEN (PAGE 1090) closed but LBI MCB FEEDBACK (PAGE
Description
1012) did not closed in 2 seconds.
Self-closing of breaker with Mains parameters with limits – not considered
as fault, MCB close command is issued when Mains fails.

InteliNeo 6000 1.5.0 Global Guide 1255


Image 7.83 MCB Fail To Close

This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn MCB Fail To Open

Alarm Type Warning (page 198)


Alarmlist
Wrn MCB Fail To Open
message
Alarm
Only if MCB Control Mode (page 368) = Internal
evaluated
Related
MPTM
applications
Alarm ID 1552
This alarm is activated when there is a problem with circuit breaker position while
opening.
LBO MCB CLOSE/OPEN (PAGE 1090) opened but LBI MCB FEEDBACK (PAGE
1012) did not opened in 2 seconds.
Self-opening of breaker with Mains parameters without limits - not
considered as fault, MCB open command is issued when Mains fails .

Description

Image 7.84 MCB Fail To Open

This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn Override All Sd

Alarm Type Warning (page 198)

InteliNeo 6000 1.5.0 Global Guide 1256


Alarmlist message Override All Sd
Alarm evaluated Only if LBI SD OVERRIDE (PAGE 1027) is configured
Related applications MINT, MPTM
Alarm ID 674
This alarm is activated when LBI SD OVERRIDE (PAGE 1027) is closed.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn Password reset e-mail addr is not set

Alarm Type Warning (page 198)


Alarmlist message Wrn Password reset e-mail addr is not set
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1292
This alarm is active when password reset e-mail address is not filled. Fill out the
Description
password reset e-mail via InteliConfig to remove this alarm.
6 back to List of alarms level 1

Wrn P for Q Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn P for Q Fail
Alarm evaluated Only when P For Q Limitation (page 556) = Enabled
Related applications MPTM
Alarm ID 1106
This alarm indicates P for Q Fail which can be caused by wrongly configured
curves:
P FOR Q UQ C (PAGE 978)

Description P FOR Q UQ L (PAGE 977)


P FOR Q PQ C (PAGE 980)
P FOR Q PQ L (PAGE 979)
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184)

6 back to List of alarms level 1

Wrn P(Um) Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn P(Um) Fail
Alarm evaluated Only if P(Um) (page 553) != Disabled
Related applications MPTM
Alarm ID 1255
This alarm indicates Power Regulation Based On Actual Mains Voltage
Description
(page 302) fail. Application Curve P(Um) (page 971) is either not configured or

InteliNeo 6000 1.5.0 Global Guide 1257


invalid.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn PF Control Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn PF Control Fail
Only when PF/Q Request Source (page 357) = Analog External Value, PF/Q
Control PTM Mode (page 356) = PF Control and Breaker state (page 886) =
Alarm evaluated
ParalOper

Related applications MINT, MPTM


Alarm ID 1053
This alarm indicates PF Control Fail which can be caused by:
If PF/Q Regulation Type (page 358) = Base PF/Q Control
LAI PF CONTROL: ANEXT BASE PF (PAGE 1124) is not configured
Value from LAI PF CONTROL: ANEXT BASE PF (PAGE 1124) is out of
sensor range (i.e. "###")
If PF/Q Regulation Type (page 358)
Description LAI PF CONTROL: ANEXT IMP/EXP PF (PAGE 1125) is not configured
Value from LAI PF CONTROL: ANEXT IMP/EXP PF (PAGE 1125) is
out of sensor range (i.e. "###")
When this alarm is active, BESS Required PF (page 865) is taken from Base
Power Factor (page 359) or Import Power Factor (page 359), based on
setpoints setting.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

Wrn PF/Q IMP/EXP Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn PF/Q IMP/EXP Fail
Alarm evaluated Only if Application Mode (page 885) = MPTM
Related applications MINT, MPTM
Alarm ID 1054
This alarm is active when PF/Q Regulation Type (page 358) = Import/Export
PF/Q Control but Mains Measurement P or Q is unavailable.
When this alarm is active, PF/Q is controlled as if PF/Q Regulation Type
(page 358) = Base PF/Q Control.
Description
Alarm is caused by:
Mains Measurement P (page 364) = None
Mains Measurement P (page 364) = Analog Input and
LAI MAINS MEASUREMENT P (PAGE 1124) is not configured

InteliNeo 6000 1.5.0 Global Guide 1258


Value from LAI Mains Measurement P (page 364) has Invalid flag
(page 691)
Mains Measurement Q (page 365) = None
Mains Measurement Q (page 365) = Analog Input and
LAI MAINS MEASUREMENT Q (PAGE 1124) is not configured
Value from LAI Mains Measurement Q (page 365) has Invalid flag
(page 691)
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

Wrn PF(Pm) Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn PF(Pm) Fail
Alarm evaluated Only when PF/Q Control PTM Mode (page 356) = PF(Pm)
Related applications MPTM
Alarm ID 1048
This alarm indicates PF(Pm) Control Fail which can be caused by:
PF/Q Request Source (page 357) = Analog External Value and
Breaker state (page 886) = ParalOper
Note: Function is evaluated as PF/Q Request Source (page 357) =
Setpoint

Description curve is not available in configuration - evaluated during controller


initialization only
Note: Function is evaluated as PF/Q Control PTM Mode (page 356) =
PF Control

curve has changed resolution


This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn PVCB Fail To Close

Alarm Type Warning (page 198)


Alarmlist
Wrn PVCB Fail To Close
message
Alarm
Only if MCB Control Mode (page 368) = Internal
evaluated
Related
MINT, MPTM
applications
Alarm ID 1591
This alarm is activated when there is a problem with circuit breaker position while
Description closing.
LBO PVCB CLOSE/OPEN (PAGE 1100) closed but LBI PVCB FEEDBACK (PAGE

InteliNeo 6000 1.5.0 Global Guide 1259


1025) did not closed in 2 seconds.

Image 7.85 PVCB Fail To Close

6 back to List of alarms level 1

Wrn PVCB Fail To Open

Alarm Type Warning (page 198)


Alarmlist
Wrn PVCB Fail To Open
message
Alarm
Only if MCB Control Mode (page 368) = Internal
evaluated
Related
MINT, MPTM
applications
Alarm ID 1590
This alarm is activated when there is a problem with circuit breaker position while
opening.
LBO PVCB CLOSE/OPEN (PAGE 1100) opened but LBI PVCB FEEDBACK (PAGE
1025) did not opened in 2 seconds.

Description

Image 7.86 PVCB Fail To Open

6 back to List of alarms level 1

Wrn PVCB Fail

Alarm Type Warning (page 198)


Alarmlist
Wrn PVCB Fail
message

InteliNeo 6000 1.5.0 Global Guide 1260


Alarm
Only if MCB Control Mode (page 368) = Internal
evaluated
Related
MINT, MPTM
applications
Alarm ID 1589
This alarm is activated when there is a problem with position of the circuit breaker.
LBI PVCB FEEDBACK (PAGE 1025) does not match expected position given by
LBO PVCB CLOSE/OPEN (PAGE 1100).
There is a mismatch between LBI PVCB FEEDBACK (PAGE 1025) and PVCB
FEEDBACK NEGATIVE (PAGE 1026).

Description

Image 7.87 PVCB Fail

6 back to List of alarms level 1

Wrn Q Control Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Q Control Fail
Only when PF/Q Request Source (page 357) = Analog External Value, PF/Q
Alarm evaluated Control PTM Mode (page 356) = Q Control and Breaker state (page 886) =
ParalOper
Related applications MINT, MPTM
Alarm ID 1049
This alarm indicates Q Control Fail which can be caused by:
Description
If PF/Q Regulation Type (page 358)

InteliNeo 6000 1.5.0 Global Guide 1261


LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is not configured
Value from LAI Q CONTROL: ANEXT BASE Q (PAGE 1147) is out of
sensor range (i.e. "###")
If PF/Q Regulation Type (page 358)
LAI Q CONTROL: ANEXT IMP/EXP Q (PAGE 1147) is not configured
Value from LAI Q CONTROL: ANEXT IMP/EXP Q (PAGE 1147) is out
of sensor range (i.e. "###")
When this alarm is active, BESS Required Q (page 865) is taken from Base Q
(page 360) or Import Q (page 361), based on setpoints setting.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn Q&U Protection

Alarm Type Warning (page 198)


Alarmlist message Wrn Q&U Protection
Only when Q&U Protection (page 558) = Enabled and Breaker state (page
Alarm evaluated
886) = ParalOper
Related applications MPTM
Alarm ID 584
This alarm indicates activeQ&U Protection (page 558). At least one actual
mains voltage value is lower than allowed relative ratio (Uactual/Unominal) set
Description by Q&U < V (page 559) and value BESS Q (page 708) is lower than Q&U < Q
(page 559) for longer time then Q&U Protection Delay (page 560).
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184)

6 back to List of alarms level 1

Wrn Q(P) Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Q(P) Fail
Only when PF/Q Control PTM Mode (page 356) = Q(P) and at least one Gen-
Alarm evaluated
set is excited
Related applications MPTM
Alarm ID 1051
This alarm indicates Q(P) Control Fail which can be caused by:
PF/Q Request Source (page 357) = Analog External Value and
Breaker state (page 886) = ParalOper
Note: Function is evaluated as PF/Q Request Source (page 357) =
Description Setpoint

Q(P) (PAGE 969) curve is not available in configuration - evaluated


during controller initialization only.
Note: Function is evaluated as PF/Q Control PTM Mode (page 356) =
PF Control

InteliNeo 6000 1.5.0 Global Guide 1262


Q(P) (PAGE 969) curve has changed resolution
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn Q(Um) Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Q(Um) Fail
Alarm evaluated Only if PF/Q Control PTM Mode (page 356) = Q(Um)
Related applications MPTM
Alarm ID 1050
This alarm indicates Q(Um) Control Fail which can be caused by:
If PF/Q Request Source (page 357) = Analog External Value and
Breaker state (page 886) = ParalOper
If PF/Q Regulation Type (page 358) = Base PF/Q Control
LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148) is not configured

Value LAI Q(UM): 0 REF ANEXT BASE Q (PAGE 1148) is out of


sensor range (i.e. "###")
If PF/Q Regulation Type (page 358) = Import/Export PF/Q Control
LAI Q(UM): 0 REF ANEXT IMP/EXP Q (PAGE 1149) is not
configured
Description
Value LAI Q(UM): 0 REF ANEXT IMP/EXP Q (PAGE 1149) is out of
sensor range (i.e. "###")
Note: In both cases is the function evaluated as PF/Q Request
Source (page 357) = Setpoint

Q(UM) (PAGE 967) curve is not available in configuration - evaluated


during controller initialization only.
Note: Function is evaluated as PF/Q Control PTM Mode (page 356) =
PF Control

Q(UM) (PAGE 967) curve has changed resolution


This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn Qref/Ulim Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Qref/Ulim Fail
Only if PF/Q Control PTM Mode (page 356) = Qref/Ulim and at least one Gen-
Alarm evaluated
set is excited
Related applications MPTM
Alarm ID 1052
Description This alarm indicates Qref/Ulim Control Fail which can be caused by:

InteliNeo 6000 1.5.0 Global Guide 1263


If PF/Q Request Source (page 357) = Analog External Value and
Breaker state (page 886) = ParalOper
If PF/Q Regulation Type (page 358) = Base PF/Q Control
LAI QREF/ULIM: ANEXT QREF/PNOM B Q (PAGE 1150) is not
configured
Value LAI QREF/ULIM: ANEXT QREF/PNOM B Q (PAGE 1150) is
out of sensor range (i.e. "###")
If PF/Q Regulation Type (page 358) = Import/Export PF/Q Control
LAI QREF/ULIM: ANEXT QREF/PNOM I/E Q (PAGE 1151) is not
configured
Value LAI QREF/ULIM: ANEXT QREF/PNOM I/E Q (PAGE 1151) is
out of sensor range (i.e. "###")
Note: In both cases is the function evaluated as PF/Q Request
Source (page 357) = Setpoint

QREF/ULIM (PAGE 968) curve is not available in configuration - evaluated


during controller initialization only.
Note: Function is evaluated as PF/Q Control PTM Mode (page 356) =
PF Control

QREF/ULIM (PAGE 968) curve has changed resolution


This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn Redundant CAN inconsistency

Alarm Type Warning (page 198)


Alarmlist message Wrn Redundant CAN inconsistency
Alarm evaluated Only when CAN Intercontroller Comm Redund (page 396) = Enabled
Related applications MINT, MPTM
Alarm ID 1079
This alarm is issued when there is inconsistency between CAN2A (page 19)
Description and CAN2B (page 19).
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

Wrn RTC Battery Flat

Alarm Type Warning (page 198)


Alarmlist message Wrn RTC Battery Flat
Alarm evaluated Only during power-on of the controller
Related applications MINT, MPTM
Alarm ID 42
This alarm indicates that the controller detected a flat RTC Battery during
Description
power-on. The RTC battery is considered to be flat if its voltage drops bellow 2.8

InteliNeo 6000 1.5.0 Global Guide 1264


V. To remove this alarm follow the Backup battery replacement (page 81).

6 back to List of alarms level 1

Wrn Reverse Synchronization Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Reverse Synchro Fail
Alarm evaluated Only if LBO REVERSE SYNCHRONIZATION (PAGE 1105) is closed
Related applications MINT, MPTM
Alarm ID 93
This alarm is activated when Reverse Synchronization fails. Reverse
Description Synchronization is activated when synchronization is done over MCB breaker.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 1

Wrn SD Card Failed

Alarm Type Warning (page 198)


Alarmlist message Wrn SD Card Fail
Alarm evaluated Only when Long Term History (page 401) = Mount or Format
Related applications MINT, MPTM
Alarm ID 1280
This alarm is activated when it is not possible to read or write to the SD card.
The alarm is also displayed in case that the setpoint SD Card File System
(page 401) is set to Mount or Format but the SD card is not inserted. This alarm
Description
will not be activated if the card is not compatible (ALI SD Card Not Compatible
(page 1273) is active).
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

Wrn SD Card File System Failed

Alarm Type Warning (page 198)


Alarmlist message Wrn SD Card File System Failed
Alarm evaluated Only when Long Term History (page 401) = Mount
Related applications MINT, MPTM
Alarm ID 1639
This alarm is activated when there is a wrong file system on the SD Card.
Description The alarm is not activated if the SDcard is not compatible.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

Wrn SNMP TRAP 1 Fail

Alarm Type Warning (page 198)

InteliNeo 6000 1.5.0 Global Guide 1265


Alarmlist message Wrn SNMP TRAP 1 Fail
Only when SNMP Agent (page 426) = Enabled and SNMP Traps IP Address
Alarm evaluated
1 (page 427) is set.
Related applications MINT, MPTM
Alarm ID 823
This alarm is activated if sending of SNMP trap to IP address set by SNMP
Description Traps IP Address 1 (page 427) failed.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn SNMP TRAP 2 Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn SNMP TRAP 2 Fail
Only when SNMP Agent (page 426) = Enabled and SNMP Traps IP Address
Alarm evaluated
2 (page 428) is set.
Related applications MINT, MPTM
Alarm ID 824
This alarm is activated if sending of SNMP trap to IP address set by SNMP
Description Traps IP Address 2 (page 428) failed.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Wrn SOC High Alarm

Alarm Type Warning (page 198)


Alarmlist message Wrn SOC High Alarm
Alarm evaluated Only if BESS (page 372) = Installed
Related applications MINT, MPTM
Alarm ID 1595
This alarm is activated by BESS >SOC Protection (page 598).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 1

Wrn SOC Low Alarm

Alarm Type Warning (page 198)


Alarmlist message Wrn SOC Low Alarm
Alarm evaluated Only if BESS (page 372) = Installed
Related applications MINT, MPTM
Alarm ID 1594
This alarm is activated by BESS <SOC Protection (page 598).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1266


Wrn Soft Transfer Fail

Alarm Type Warning (page 198)


Alarmlist message Wrn Soft Transfer Fail
Alarm evaluated During transition of load
Related applications MPTM
Alarm ID 852
This alarm is activated when loading/unloading was not finished in time Load
Description Ramp (page 477) +10%.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184)

6 back to List of alarms level 1

Wrn Stop Fail

Alarm Type Warning (page 198)


Alarmlist
Wrn Stop Fail
message
Alarm
Only when BESS should be stopped
evaluated
Related
MINT, MPTM
applications
Alarm ID 48
This alarm is activated when BESS is expected to be stopped but there is at least one
symptom such as too high voltage or frequency which is not fulfilled.
Description
Note: BESS cannot be started while this alarm is active.

This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 1

Wrn SW Key CAN Redundancy Error

Alarm Type Warning (page 198)


Alarmlist message Wrn SW Key CAN Redundancy Error
Alarm evaluated Only when CAN Intercontroller Comm Redund (page 396) = Enabled
Related applications MINT, MPTM
Alarm ID 1463
This alarm is activated when there is an attempt to enable premium feature
Description CAN Intercontroller Communication Redundancy (page 132) without of
valid SW Key (page 388).

6 back to List of alarms level 1

Wrn SW Key Hot Swap Error

Alarm Type Warning (page 198)


Alarmlist message Wrn SW Key Hot Swap Error
Alarm evaluated Only if Hot Swap Redundancy (page 371) != Disabled

InteliNeo 6000 1.5.0 Global Guide 1267


Related applications MINT, MPTM
Alarm ID 1461
This alarm is activated when there is an attempt to enable premium feature Hot
Description
Swap Redundancy (page 160) without valid SW Key (page 388).

6 back to List of alarms level 1

Wrn Test UPQF

Alarm Type Warning (page 198)


Alarmlist message Wrn Test UPQF
Alarm evaluated All the time
Related applications MPTM
Alarm ID 583
This alarm has informative meaning. It indicates, that Test mode for U, P, Q and
Description f is enabled, i.e. Grid Codes Test (page 536) = Enabled.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184)

6 back to List of alarms level 1

Wrn Unsupported PMS Mode

Alarm Type Warning (page 198)


Alarmlist message Wrn Unsupported PMS Mode
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1044
This alarm is active if setpoint #Power Management Mode (page 491) = N/A
Description
Mode.
6 back to List of alarms level 1

Wrn Universal Genset Overflow

Alarm Type Warning (page 198)


Alarmlist message Wrn Universal Genset Overflow
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 2691
The sum of active power or Nominal Power of all universal gensets
implemented via InteliNeo exceeded the maximal limit which is 32000 kW
Description
(3200,0 kW or 320,00 MW according to selected power format). The proper
power format should be used to prevent this situation.

6 back to List of alarms level 1

Wrn Voltage Regulation Limit

Alarm Type Warning (page 198)


Alarmlist message Wrn Voltage Regulation Limit

InteliNeo 6000 1.5.0 Global Guide 1268


Alarm evaluated While BESS is running
Related applications MINT, MPTM
Alarm ID 152
This alarm is issued when Voltage Regulator Output (page 866) stays close
to Voltage Regulator Low Limit (page 480) or Voltage Regulator High
Description Limit (page 480) for at least 2 seconds and will remain active as long as the
cause is present.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 1

Wrong PLC Configuration

Alarm Type Warning (page 198)


Alarmlist message Wrong PLC Configuration
Alarm evaluated Always
Related applications MINT, MPTM
Alarm ID 41
This alarm is activated when the PLC - Programmable Logic Controller
(page 183) configuration is invalid.Once the alarm is active the whole PLC does
Description
not work. This alarm will be active until the PLC configuration is not fixed and
the archive is written to the controller.

6 back to List of alarms level 1

Alarm Only

Alarm List Indication

ALI Bus Ph L1 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Bus Ph L1 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 928
Description This alarm is activated when Bus Phase L1 is inverted.

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1269


ALI Bus Ph L2 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Bus Ph L2 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 929
Description This alarm is activated when Bus Phase L2 is inverted.

6 back to List of alarms level 1

ALI Bus Ph L3 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Bus Ph L3 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 930
Description This alarm is activated when Bus Phase L3 is inverted.

6 back to List of alarms level 1

ALI Bus Ph Rotation Opposite

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Bus Ph Rotation Opposite
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 847
This alarm is activated when controller detects wrong phase rotation, e.g.
Phase Rotation (page 384) is set to Clockwise and actual rotation is
Description
Counterclockwise, on the Bus side.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1270


ALI BCB Closing Is Blocked

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI BCB Closing Is Blocked
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 2339
Alarm is active in case the BCB breaker is blocked due to some of the
generator protections being disabled:
BESS <f Protection (page 585)

Description BESS >f Protection (page 584)


BESS <V Protection (page 576)
BESS >V (page 574) and BESS >>V Protection (page 575)
Short Circuit Protection (page 571)

6 back to List of alarms level 1

ALI CAN Mode Inconsistency

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI CAN Mode Inconsistency
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1291
This alarm is active when there is mismatch between setpoint CAN
Intercontroller Comm Mode (page 397) and value CAN Intercontroller
Description Comm Mode (page 888).
After changing the setpoint CAN Intercontroller Comm Mode (page 397), it is
needed to power cycle the controller to get rid of the alarm.

6 back to List of alarms level 1

ALI Daily Battery Cycles Reached

Alarm Type Warning (page 198)


Alarmlist message ALI Daily Battery Cycles Reached
Alarm evaluated Only if BESS (page 372) = Installed
Related applications MINT, MPTM
Alarm ID 1605
This alarm is activated if number of daily battery cycles specified by the setpoint
Description
Max Battery Cycles Per Day (page 441) is reached.

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1271


ALI BESS Ph L1 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALIBESS Ph L1 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 922
This alarm is activated whenBESS Phase L1 is inverted.
Note: Inverted phase means that "cold" end of Gen wiring which should be
Description connected to the neutral is swapped with "hot" end which should be
connected to the Load and Voltage measurement. In this case the CU see
inverted voltage phasor.

6 back to List of alarms level 1

ALI BESS Ph L2 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALIBESS Ph L2 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 923
This alarm is activated whenBESS Phase L2 is inverted.
Note: Inverted phase means that "cold" end of Gen wiring which should be
Description connected to the neutral is swapped with "hot" end which should be
connected to the Load and Voltage measurement. In this case the CU see
inverted voltage phasor.

6 back to List of alarms level 1

ALI BESS Ph L3 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI BESS Ph L3 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 924
This alarm is activated when BESS Phase L3 is inverted.
Note: Inverted phase means that "cold" end of Gen wiring which should be
Description connected to the neutral is swapped with "hot" end which should be
connected to the Load and Voltage measurement. In this case the CU see
inverted voltage phasor.

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1272


ALI BESS Ph Rotation Opposite

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI BESS Ph Rotation Opposite
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 154
This alarm is activated when controller detects wrong phase rotation, e.g.
Phase Rotation (page 384) is set to Clockwise and actual rotation is
Description
Counterclockwise, on the BESS side.
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 1

ALI Redundant CAN Error

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Redundant CAN Error
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1290
This alarm is active when Value CAN Intercontroller Comm Redundancy
(page 888) and Setpoint CAN Intercontroller Comm Redund (page 396)
Description does not match.
After changing the setpoint CAN Intercontroller Comm Redund (page 396),
it is needed to power cycle the controller to get rid of the alarm.

6 back to List of alarms level 1

ALI SD Card Not Compatible

Alarm Type Alarm List Indication (page 198)


Alarmlist
ALI SD Card Not Compatible
message
Alarm evaluated Only when Long Term History (page 401) = Mount or Format
Related
MINT, MPTM
applications
Alarm ID 1610
This alarm is activated when the value SD Card Status (page 889) shows Status:
Not Supported.
Description Alarm is active all the time until the card is unmounted, or a compatible card is
inserted.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1273


ALI SD Card In Slot

Alarm Type Alarm List Indication (page 198)


Alarmlist
ALI SD Card In Slot
message
Alarm evaluated Only when Long Term History (page 401) = Unmount
Related
MINT, MPTM
applications
Alarm ID 1611
This alarm is activated when SD Card File System (page 401) is set to Unmount
Description but SD Card is detected in the slot.
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

ALI SD Card Full

Alarm Type Alarm List Indication (page 198)


Alarmlist
ALI SD Card Full
message
Alarm evaluated Only when Long Term History (page 401) = Mount
Related
MINT, MPTM
applications
Alarm ID 1621
This alarm is activated if value SD Card Free Space (page 889) drops below 10 %.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

ALI SD Card Formatting/Mounting

Alarm Type Alarm List Indication (page 198)


Alarmlist
ALI SD Card Formating/Mounting
message
Alarm evaluated Only when Long Term History (page 401) = Mount or Format
Related
MINT, MPTM
applications
Alarm ID 1638
This alarm is activated when the process of mounting or formatting is active.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1274


ALI Mains Ph L1 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Mains Ph L1 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 925
Description This alarm is activated when Mains Phase L1 is inverted.
6 back to List of alarms level 1

ALI Mains Ph L2 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Mains Ph L2 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 926
Description This alarm is activated when Mains Phase L2 is inverted.
6 back to List of alarms level 1

ALI Mains Ph L3 Inverted

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Mains Ph L3 Inverted
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 927
Description This alarm is activated when Mains Phase L3 is inverted.
6 back to List of alarms level 1

ALI Mains Ph Rotation Opposite

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Mains Ph Rotation Opposite
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 158
This alarm is activated when controller detects wrong phase rotation, e.g.
Phase Rotation (page 384) is set to Clockwise and actual rotation is
Description
Counterclockwise, on the Mains side.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1275


ALI Start Blocking

Alarm Type Alarm List Indication (page 198)


Alarmlist
ALI Start Blocking
message
Alarm evaluated Only if LBI START BLOCKING (PAGE 1028) is configured
Related
MINT, MPTM
applications
Alarm ID 56
This alarm is active if LBI START BLOCKING (PAGE 1028) is closed before BESS is
Description
started.
6 back to List of alarms level 1

ALI Wrong Power Format

Alarm Type Alarm List Indication (page 198)


Alarmlist message ALI Wrong Power Format
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 149
This alarm is activated when there is inconsistency of Power Formats And
Description Units (page 196) on any controller which is connected via CAN2A (page 19) or
CAN2B (page 19).

6 back to List of alarms level 1

Alarm List + History Indication

AHI SyncNotAllowed

Alarm Type Alarm List + History Record Indication (page 198)


Alarmlist message AHI SyncNotAllowed
When MAINS/BUS HEALTHY (PAGE 1090) = 1 and Mains Params/MP
Alarm evaluated
Synchronization (page 536) = Enabled
Related applications MPTM
Alarm ID 452
This alarm is activated when synchronization of BESS with Mains is blocked by
Description Synchronization & Connection Conditions (page 307).
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184)

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1276


History Record Only

Hst Pave

Alarm Type History Record Only (page 198)


Alarmlist message Hst Pave
Alarm evaluated Only if Pave Protection (page 569) != Disabled
Related applications MPTM
Alarm ID 1078
This alarm is activated when value Pmom/Pave (page 832) is equal to or
Description bigger than 1 for period longer that is allowed by application curve P Mom/Pave
Max (page 972) and MCB gets opened.

6 back to List of alarms level 1

Hst ROCOF 1

Alarm Type History Record Only (page 198)


Alarmlist message Hst ROCOF 1
Only if ROCOF1 Protection (page 594) = Enabled or (ROCOF1 Protection
Alarm evaluated
(page 594) = Parallel Only and MCB FEEDBACK (PAGE 1012) is active)
Related applications MINT, MPTM
Alarm ID 851
This alarm is activated by ROCOF1 Protection (page 594).
Note: There are 4 ROCOF Protections which can be enabled.

ROCOF1 Protection (page 594)


Description
ROCOF2 Protection (page 595)
ROCOF3 Protection (page 596)
ROCOF4 Protection (page 597)

6 back to List of alarms level 1

Hst ROCOF2

Alarm Type History Record Only (page 198)


Alarmlist message Hst ROCOF2
Only if ROCOF2 Protection (page 595) = Enabled or (ROCOF2 Protection
Alarm evaluated
(page 595) = Parallel Only and MCB FEEDBACK (PAGE 1012) is active)
Related applications MINT, MPTM
Alarm ID 1112
Description This alarm is activated by ROCOF2 Protection (page 595)

6 back to List of alarms level 1

Hst ROCOF3

Alarm Type History Record Only (page 198)


Alarmlist message Hst ROCOF3

InteliNeo 6000 1.5.0 Global Guide 1277


Only if ROCOF3 Protection (page 596) = Enabled or (ROCOF3 Protection
Alarm evaluated
(page 596) = Parallel Only and MCB FEEDBACK (PAGE 1012) is active)
Related applications MINT, MPTM
Alarm ID 1113
Description This alarm is activated by ROCOF3 Protection (page 596)

6 back to List of alarms level 1

Hst ROCOF4

Alarm Type History Record Only (page 198)


Alarmlist message Hst ROCOF4
Only if ROCOF4 Protection (page 597) = Enabled or (ROCOF4 Protection
Alarm evaluated
(page 597) = Parallel Only and MCB FEEDBACK (PAGE 1012) is active)
Related applications MINT, MPTM
Alarm ID 1114
Description This alarm is activated by ROCOF4 Protection (page 597)

6 back to List of alarms level 1

Hst Vector Shift

Alarm Type History Record Only (page 198)


Alarmlist message Hst Vector Shift
Only if Vector Shift Protection (page 593) = Enabled or (Vector Shift
Alarm evaluated Protection (page 593) = Parallel Only and MCB FEEDBACK (PAGE 1012) is
closed)
Related applications MINT, MPTM
Alarm ID 850
Description This alarm is activated when Vector shift (page 173) is detected.

6 back to List of alarms level 1

9.2.3 Alarms level 2


What alarms level 2 are:
The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached.

InteliNeo 6000 1.5.0 Global Guide 1278


List of alarms level 2

Shutdown 1280 PVBO Short Circuit 1288


Emergency Stop 1280 Sd SOC Critical High 1288
E-STOP 1280 Sd SOC Critical Low 1288
Hst BESS Anti Islanding 1280 Sd Start Fail 1289
Sd DC Circuit Close Fail 1281 Slow Stop 1290
Sd ECU Communication Stp Bus Meas Error 1290
Fail 1281 Stp BCB Fail 1290
Sd BESS >>V L1-N 1281 Sd BCB Fail To Close 1291
Sd Mains/Bus >>V L2-N 1281 Sd BCB Fail To Open 1291
Sd BESS >>V L3-N 1282 Stp BCB Secondary Fail 1292
WRN BESS >>V L1-L2 1282 Stp BCB Secondary Fail
WRN BESS >>V L2-L3 1282 To Close 1293
WRN BESS >>V L3-L1 1282 Stp BCB Secondary Fail
Sd BESS >V L1-N 1283 To Open 1294

Sd BESS >V L2-N 1283 Stp Synchronization Fail 1294

Sd BESS >V L3-N 1283 Mains Protection 1296

Sd BESS >V L1-L2 1283 Mains Avg >V L1-N 1296

Sd BESS >V L2-L3 1284 Mains Avg >V L2-N 1296

Sd BESS >V L3-L1 1284 Mains Avg >V L3-N 1296

Sd BESS <V L1-N 1284 Mains Avg >V L1-L2 1296

Sd BESS <V L2-N 1284 Mains Avg >V L2-L3 1297

Sd BESS <V L3-N 1285 Mains Avg >V L3-L1 1297

Sd BESS <V L1-L2 1285 PV Breaker Open 1297


PVBO PV Anti Islanding 1297
Sd BESS <V L2-L3 1285
PVBO PV Not Operable 1297
Sd BESS <V L3-L1 1285
Sd BESS >f 1286 6 back to Alarms

Sd BESS <f 1286


Sd BESS V Unbalance
Ph-N 1286
Sd BESS V Unbalance
Ph-Ph 1286
Sd BESS Current
Unbalance 1287
Sd IDMT Earth Fault
Current 1287
Sd IDMT BESS >A 1287
Sd IDMT Overload 1287
Sd NCB Fail 1288

InteliNeo 6000 1.5.0 Global Guide 1279


Shutdown

Emergency Stop

Alarm Type Shutdown (page 199)Shutdown (page 199)


Alarmlist message Emergency Stop
Alarm evaluated Only if EMERGENCY STOP (PAGE 996) is configured
Related applications MINT, MPTM
Alarm ID 44
This alarm is activated by LBI EMERGENCY STOP (PAGE 996). The BESS shuts
down in the moment the input is activated and starting is blocked until the input
is deactivated and fault reset is pressed.
Note: Use red emergency button placed on the switchboard door and connect
it to a binary input of the controller. Then configure the function EMERGENCY
Description
STOP (PAGE 996) to that binary input. It is recommended to use NC contact of
the button.

Note: The MCB control is not affected by this alarm.

This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

E-STOP

Alarm Type Shutdown (page 199)


Alarmlist message E-STOP
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 853
Alarm is activated when dedicated E-STOP (page 143) input is not closed. The
Description BESS shuts down in the moment the input is opened and starting is blocked
until the input is closed and fault reset is pressed.

6 back to List of alarms level 2

Hst BESS Anti Islanding

Alarm Type History Record


Alarmlist message Hst BESS Anti Islanding
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1602
This alarm is activated at the moment when there is no grid forming source of
Description power such as Mains or Gen-set on the Bus and the BESS is controlled by P-Q
method (grid support mode).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1280


Sd DC Circuit Close Fail

Alarm Type Warning (page 198)


Alarmlist message Sd DC Circuit Close Fail
Alarm evaluated
Related applications MINT, MPTM
Alarm ID 1655
This alarm gets active anytime when the BESS DC circuit is expected to be
Description closed but the LBI PRECHARGE FINISHED (PAGE 1016) gets inactive (DC circuit is
opened) unexpectedly.

6 back to List of alarms level 1

Sd ECU Communication Fail

Alarm Type Shutdown (page 199)


Alarmlist message Sd ECU Communication Fail
With configured LBO ECU POWER RELAY (PAGE 1074) - Only when this LBO is
Alarm evaluated active
Without configured LBO ECU POWER RELAY (PAGE 1074) - All the time
Related applications MINT, MPTM
This alarm occurs when an ECU is configured, but the communication with the
Description
ECU is not established or has dropped out.
6 back to List of alarms level 2

Sd BESS >>V L1-N

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS >>V L1-N
Alarm evaluated Only if BESS >>V Protection (page 575) != Disabled
Related applications MINT, MPTM
Alarm ID 1098
This alarm is activated by BESS >>V Protection (page 575).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd Mains/Bus >>V L2-N

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS >>V L2-N
Alarm evaluated Only if BESS >>V Protection (page 575) != Disabled
Related applications MINT, MPTM
Alarm ID 1099
This alarm is activated by BESS >>V Protection (page 575).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1281


Sd BESS >>V L3-N

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS >>V L3-N
Alarm evaluated Only if BESS >>V Protection (page 575) != Disabled
Related applications MINT, MPTM
Alarm ID 1100
This alarm is activated by BESS >>V Protection (page 575).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

WRN BESS >>V L1-L2

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS >>V L1-L2
Alarm evaluated Only if BESS >>V Protection (page 575) != Disabled
Related applications MINT, MPTM
Alarm ID 1101
This alarm is activated by BESS >>V Protection (page 575).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

WRN BESS >>V L2-L3

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS >>V L2-L3
Alarm evaluated Only if BESS >>V Protection (page 575) != Disabled
Related applications MINT, MPTM
Alarm ID 1102
This alarm is activated by BESS >>V Protection (page 575).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

WRN BESS >>V L3-L1

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS >>V L3-L1
Alarm evaluated Only if BESS >>V Protection (page 575) != Disabled
Related applications MINT, MPTM
Alarm ID 1103
This alarm is activated by BESS >>V Protection (page 575).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1282


Sd BESS >V L1-N

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >V L1-N
Alarm evaluated Only if BESS >V (page 574) != Disabled
Related applications MINT, MPTM
Alarm ID 98
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS >V L2-N

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >V L2-N
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 99
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS >V L3-N

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >V L3-N
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 100
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS >V L1-L2

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >V L1-L2
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 107
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1283


Sd BESS >V L2-L3

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >V L2-L3
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 108
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS >V L3-L1

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >V L3-L1
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 109
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS <V L1-N

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <V L1-N
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 95
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS <V L2-N

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <V L2-N
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 96
This alarm is activated by BESS >V (page 574).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1284


Sd BESS <V L3-N

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <V L3-N
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 97
This alarm is activated by BESS <V Protection (page 576).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS <V L1-L2

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <V L1-L2
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 104
This alarm is activated by BESS <V Protection (page 576).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS <V L2-L3

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <V L2-L3
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 105
This alarm is activated by BESS <V Protection (page 576).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS <V L3-L1

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <V L3-L1
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 106
This alarm is activated by BESS <V Protection (page 576).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1285


Sd BESS >f

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS >f
Alarm evaluated Only if BESS >f Protection (page 584) != Disabled
Related applications MINT, MPTM
Alarm ID 121
This alarm is activated by BESS >f Protection (page 584).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS <f

Alarm Type Shutdown (page 199) Warning (page 198)


Alarmlist message Sd BESS <f
Alarm evaluated Only if BESS >f Protection (page 584) != Disabled
Related applications MINT, MPTM
Alarm ID 120
This alarm is activated by BESS <f Protection (page 585).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS V Unbalance Ph-N

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS V Unbalance Ph-N
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 589
This alarm is activated by BESS V Unbalance Protection (page 576).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd BESS V Unbalance Ph-Ph

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS V Unbalance Ph-Ph
Alarm evaluated Only if BESS >V (page 574)!= Disabled
Related applications MINT, MPTM
Alarm ID 588
This alarm is activated by BESS V Unbalance Protection (page 576).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1286


Sd BESS Current Unbalance

Alarm Type Shutdown (page 199)


Alarmlist message Sd BESS Current Unbalance
Alarm evaluated Only if BESS Current Unbalance Protection (page 573) != Disabled
Related applications MINT, MPTM
Alarm ID 591
This alarm is activated by BESS Current Unbalance Protection (page 573).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd IDMT Earth Fault Current

Alarm Type Shutdown (page 199)


Alarmlist message Sd IDMT Earth Fault Current
Alarm evaluated Only if Earth Fault Current Protection (page 592) != Disabled
Related applications MINT, MPTM
Alarm ID 598
This alarm is activated by Earth Fault Current Protection (page 592).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd IDMT BESS >A

Alarm Type Shutdown (page 199)


Alarmlist message Sd IDMT BESS >A
Alarm evaluated While BESS is loaded, if IDMT BESS >A Protection (page 571) != Disabled
Related applications MINT, MPTM
Alarm ID 597
This alarm is activated by IDMT BESS >A Protection (page 571).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd IDMT Overload

Alarm Type Shutdown (page 199)


Alarmlist message Sd IDMT Overload
Alarm evaluated Only if IDMT Overload Protection (page 570) != Disabled
Related applications MINT, MPTM
Alarm ID 147
This alarm is activated by IDMT Overload Protection (page 570).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1287


Sd NCB Fail

Alarm Type Shutdown (page 199)


Alarmlist message Sd NCB Fail
Alarm evaluated Only if NCB FEEDBACK (PAGE 1015) is configured
Related applications MINT, MPTM
Alarm ID 148
This alarm is activated when LBI NCB FEEDBACK (PAGE 1015) does not match
Description expected position given by LBO NCB CLOSE/OPEN (PAGE 1094).
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

PVBO Short Circuit

Alarm Type Shutdown (page 199)


Alarmlist message PVBO Short Circuit
Alarm evaluated Only if Short Circuit Protection (page 571) != Disabled
Related applications MINT, MPTM
Alarm ID 595
This alarm is activated by Short Circuit Protection (page 571).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 2 (PAGE 1181).

6 back to List of alarms level 2

Sd SOC Critical High

Alarm Type Shutdown (page 199)


Alarmlist message Sd SOC Critical High
Alarm evaluated Only if BESS (page 372) = Installed
Related applications MINT, MPTM
Alarm ID 1597
This alarm is activated by BESS >>SOC Protection (page 599).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

Sd SOC Critical Low

Alarm Type Shutdown (page 199)


Alarmlist message Sd SOC Critical Low
Alarm evaluated Only if BESS (page 372) = Installed
Related applications MINT, MPTM
Alarm ID 1596
This alarm is activated by BESS <<SOC Protection (page 599).
Description
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1288


Sd Start Fail

Alarm Type Shutdown (page 199)


Alarmlist message Sd Start Fail
Alarm evaluated During starting of BESS
Related applications MINT, MPTM
Alarm ID 55
This alarm is activated after attempt to start BESS failed (BESS Start TO
Description elapsed).
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1289


Slow Stop

Stp Bus Meas Error

Alarm Type Slow Stop (page 199)


Alarmlist message Stp Bus Meas Error
Alarm evaluated Bus Meas Error (page 590) != Disabled
Related applications MINT, MPTM
Alarm ID 143
This protection is activated in case that voltage mismatch on Bus side is
detected for longer than 20 seconds.The mismatch is detected according to the
conditions below:
Own BCB was closed
MCB FEEDBACK (PAGE 1012) was detected (physically or via CAN2) →
Breaker State = MultParOp, MAINS/BUS HEALTHY (PAGE 1090) is active
and Controller Mode (page 385) = AUTO
Description
Any other controller in Control Group (page 516) closed BCB

Note: Alarm is activated after 20 s, but BCB closing is blocked


immediately.

BTB connected another Control Group with MCB Feedback or controller


with closed BCB
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 2

Stp BCB Fail

Alarm Type Slow Stop (page 199)


Alarmlist
Stp BCB Fail
message
Alarm
Only if BCB Control Mode (page 369) != External
evaluated
Related
MINT, MPTM
applications
Alarm ID 91
This alarm is activated when there is a problem with position of the circuit breaker.

Description

InteliNeo 6000 1.5.0 Global Guide 1290


Image 7.88 BCB Fail

This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

Sd BCB Fail To Close

Alarm Type Slow Stop (page 199)


Alarmlist
Sd BCB Fail To Close
message
Alarm
Only if BCB Control Mode (page 369) != External
evaluated
Related
MINT, MPTM
applications
Alarm ID 1555
This alarm is activated when there is a problem with circuit breaker position while
closing.
LBO BCB CLOSE/OPEN (PAGE 1055) closed but LBI BCB FEEDBACK (PAGE 991)
did not closed in Waiting For Breaker Feedback (page 1) seconds.

Description

Image 7.89 BCB Fail To Close

This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 2

Sd BCB Fail To Open

Alarm Type Slow Stop (page 199)

InteliNeo 6000 1.5.0 Global Guide 1291


Alarmlist
Sd BCB Fail To Open
message
Alarm
Only if BCB Control Mode (page 369) != External
evaluated
Related
MINT, MPTM
applications
Alarm ID 1554
This alarm is activated when there is a problem with circuit breaker position while
opening.
LBO BCB CLOSE/OPEN (PAGE 1055) opened but LBI BCB FEEDBACK (PAGE
991) did not opened in 2 seconds.

Description

Image 7.90 BCB Fail To Open

This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 2

Stp BCB Secondary Fail

Alarm Type Slow Stop (page 199)


Alarmlist
Stp BCB Secondary Fail
message
Only if LBI BCB SECONDARY FEEDBACK (PAGE 994) or LBI BCB SECONDARY
Alarm FEEDBACK NEGATIVE (PAGE 993) or BCB CLOSE/OPEN SECONDARY (PAGE 1056) is
evaluated configured

Related
MINT, MPTM
applications
Alarm ID 451
This alarm is activated when there is a problem with position of the circuit breaker.
LBI BCB SECONDARY FEEDBACK (PAGE 994) does not match expected position
Description given by LBO BCB CLOSE/OPEN SECONDARY (PAGE 1056).
There is a mismatch between LBI BCB SECONDARY FEEDBACK (PAGE 994) and
BCB SECONDARY FEEDBACK NEGATIVE (PAGE 993).

InteliNeo 6000 1.5.0 Global Guide 1292


Image 7.91 BCB Secondary Fail

This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

Stp BCB Secondary Fail To Close

Alarm Type Slow Stop (page 199)


Alarmlist
Stp BCB Secondary Fail To Close
message
Only if LBI BCB SECONDARY FEEDBACK (PAGE 994) or LBI BCB SECONDARY
Alarm FEEDBACK NEGATIVE (PAGE 993) or BCB CLOSE/OPEN SECONDARY (PAGE 1056) is
evaluated configured

Related
MINT, MPTM
applications
Alarm ID 1557
This alarm is activated when there is a problem with circuit breaker position while
closing.
Description LBO BCB CLOSE/OPEN SECONDARY (PAGE 1056) closed but LBI BCB
SECONDARY FEEDBACK (PAGE 994) did not closed in Waiting For Breaker
Feedback (page 1) seconds.

InteliNeo 6000 1.5.0 Global Guide 1293


Image 7.92 BCB Secondary Fail To Close

This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 2

Stp BCB Secondary Fail To Open

Alarm Type Slow Stop (page 199)


Alarmlist
Stp BCB Secondary Fail To Open
message
Only if LBI BCB SECONDARY FEEDBACK (PAGE 994) or LBI BCB SECONDARY FEEDBACK
Alarm
NEGATIVE (PAGE 993) or BCB CLOSE/OPEN SECONDARY (PAGE 1056) is configured
evaluated

Related
MINT, MPTM
applications
Alarm ID 1556
This alarm is activated when there is a problem with circuit breaker position while
opening.
LBO BCB CLOSE/OPEN SECONDARY (PAGE 1056) opened but LBI BCB
SECONDARY FEEDBACK (PAGE 994) did not opened in 2 seconds.

Description

Image 7.93 BCB Secondary Fail To Open

This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 2

Stp Synchronization Fail

Alarm Type Slow Stop (page 199)

InteliNeo 6000 1.5.0 Global Guide 1294


Alarmlist message Stp Synchronization Fail
Alarm evaluated During synchronization
Related applications MINT, MPTM
Alarm ID 94
This alarm is activated if the synchronization fails, e.g. Synchronization
Description Timeout (page 486) elapses.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1295


Mains Protection

Mains Avg >V L1-N

Alarm Type Mains Protection (page 199)


Alarmlist message Mains Avg >V L1-N
Alarm evaluated Only if Mains 10min Avg >V (page 526) != Disabled
Related applications MPTM
Alarm ID 1466
This alarm is activated by Mains 10min Avg >V (page 526) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 2

Mains Avg >V L2-N

Alarm Type Mains Protection (page 199)


Alarmlist message Mains Avg >V L2-N
Alarm evaluated Only if Mains 10min Avg >V (page 526) != Disabled
Related applications MPTM
Alarm ID 1467
This alarm is activated by Mains 10min Avg >V (page 526) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 2

Mains Avg >V L3-N

Alarm Type Mains Protection (page 199)


Alarmlist message Mains Avg >V L3-N
Alarm evaluated Only if Mains 10min Avg >V (page 526) != Disabled
Related applications MPTM
Alarm ID 1468
This alarm is activated by Mains 10min Avg >V (page 526) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 2

Mains Avg >V L1-L2

Alarm Type Mains Protection (page 199)


Alarmlist message Mains Avg >V L1-L2
Alarm evaluated Only if Mains 10min Avg >V (page 526) is not Disabled
Related applications MPTM
Alarm ID 1144
This alarm is activated by Mains 10min Avg >V (page 526) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1296


Mains Avg >V L2-L3

Alarm Type Mains Protection (page 199)


Alarmlist message Mains Avg >V L2-L3
Alarm evaluated Only if Mains 10min Avg >V (page 526) is not Disabled
Related applications MPTM
Alarm ID 1145
This alarm is activated by Mains 10min Avg >V (page 526) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 2

Mains Avg >V L3-L1

Alarm Type Mains Protection (page 199)


Alarmlist message Mains Avg >V L3-L1
Alarm evaluated Only if Mains 10min Avg >V (page 526) is not Disabled
Related applications MPTM
Alarm ID 1146
This alarm is activated by Mains 10min Avg >V (page 526) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 2

PV Breaker Open

PVBO PV Anti Islanding

Alarm Type PV Braker Open


Alarmlist message PVBO PV Anti Islanding
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1593
This alarm is activated at the moment when there is no grid forming source of
Description power such as Mains, Gen-set, or BESS controlled by U-f method on the Bus
and the PV inverter is alone on the Bus.

6 back to List of alarms level 2

PVBO PV Not Operable

Alarm Type PV Braker Open


Alarmlist message PVBO PV Not Operable
Alarm evaluated All the time
Related applications MINT, MPTM
Alarm ID 1592
This alarm is activated when the PV is not operable because its inverter is in the
Description
fault state.

6 back to List of alarms level 2

InteliNeo 6000 1.5.0 Global Guide 1297


9.2.4 Other alarms

InteliNeo 6000 1.5.0 Global Guide 1298


List of other alarms

Mains/Bus >V L1-N 1301 DISTIN 01 1325 DISTIN 41 1335


Mains/Bus >V L2-N 1301 DISTIN 02 1325 DISTIN 42 1335
Mains/Bus >V L3-N 1302 DISTIN 03 1325 DISTIN 43 1335
Mains/Bus >V L1-L2 1303 DISTIN 04 1325 DISTIN 44 1335
Mains/Bus >V L2-L3 1304 DISTIN 05 1326 DISTIN 45 1336
Mains/Bus >V L3-L1 1304 DISTIN 06 1326 DISTIN 46 1336
Mains/Bus >>V L1-N 1305 DISTIN 07 1326 DISTIN 47 1336
Mains/Bus >>V L2-N 1306 DISTIN 08 1326 DISTIN 48 1336
Mains/Bus >>V L3-N 1307 DISTIN 09 1327 DISTIN 49 1337
Mains/Bus >>V L1-L2 1307 DISTIN 10 1327 DISTIN 50 1337
Mains/Bus >>V L2-L3 1308 DISTIN 11 1327 DISTIN 51 1337
Mains/Bus >>V L3-L1 1309 DISTIN 12 1327 DISTIN 52 1337
Mains/Bus <V L1-N 1310 DISTIN 13 1328 DISTIN 53 1338
Mains/Bus <V L2-N 1310 DISTIN 14 1328 DISTIN 54 1338
Mains/Bus <V L3-N 1311 DISTIN 15 1328 DISTIN 55 1338
Mains/Bus <V L1-L2 1312 DISTIN 16 1328 DISTIN 56 1338
Mains/Bus <V L2-L3 1313 DISTIN 17 1329 DISTIN 57 1339
Mains/Bus <V L3-L1 1313 DISTIN 18 1329 DISTIN 58 1339
Mains/Bus <<V L1-N 1314 DISTIN 19 1329 DISTIN 59 1339
Mains/Bus <<V L2-N 1315 DISTIN 20 1329 DISTIN 60 1339
Mains/Bus <<V L3-N 1316 DISTIN 21 1330 DISTIN 61 1340
Mains/Bus <<V L1-L2 1316 DISTIN 22 1330 DISTIN 62 1340
Mains/Bus <<V L2-L3 1317 DISTIN 23 1330 DISTIN 63 1340
Mains/Bus <<V L3-L1 1318 DISTIN 24 1330 DISTIN 64 1340
Mains/Bus >f 1319 DISTIN 25 1331 DISTOUT 1341
Mains/Bus >>f 1319 DISTIN 26 1331 ECU 1 Comm Fail 1341
Mains/Bus <f 1320 DISTIN 27 1331 ECU 2 Comm Fail 1341
Mains/Bus <<f 1320 DISTIN 28 1331 ECU 3 Comm Fail 1341
Mains/Bus V Unbalance DISTIN 29 1332 ECU 4 Comm Fail 1342
Ph-N 1321 DISTIN 30 1332 ECU 5 Comm Fail 1342
Mains/Bus V Unbalance DISTIN 31 1332 ECU 6 Comm Fail 1343
Ph-Ph 1321 DISTIN 32 1332 ECU 7 Comm Fail 1343
Maintenance 1 Interval 1322 DISTIN 33 1333 ECU 8 Comm Fail 1343
Maintenance 1 RunHours 1322 DISTIN 34 1333 ECU 9 Comm Fail 1344
Maintenance 2 Interval 1323 DISTIN 35 1333 ECU 10 Comm Fail 1344
Maintenance 2 RunHours 1323 DISTIN 36 1333 ECU 11 Comm Fail 1344
Maintenance 3 Interval 1323 DISTIN 37 1334 ECU 12 Comm Fail 1345
Maintenance 3 RunHours 1324 DISTIN 38 1334 ECU 13 Comm Fail 1345
Maintenance 4 Interval 1324 DISTIN 39 1334 ECU 14 Comm Fail 1346
Maintenance 4 RunHours 1324 DISTIN 40 1334 ECU 15 Comm Fail 1346

InteliNeo 6000 1.5.0 Global Guide 1299


ECU 16 Comm Fail 1346
SHAIN 1 1347
SHAIN 2 1347
Wrn SHAIN Collision 1347
SHBIN 1 1347
SHBIN 2 1348
SHBIN 3 1348
SHBIN 4 1348
SHBIN 5 1348
SHBIN 6 1349
Wrn SHBIN Collision 1349
VRT Protection Trip 1349

6 back to Alarms

InteliNeo 6000 1.5.0 Global Guide 1300


Mains/Bus >V L1-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >V L1-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 125
This alarm is activated by Mains >V Protection (page 577).
This alarm is activated when Mains/Bus Voltage L1-N (page 839) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >V L2-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >V L2-N

InteliNeo 6000 1.5.0 Global Guide 1301


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 126
This alarm is activated by Mains >V Protection (page 577).
This alarm is activated when Mains/Bus Voltage L2-N (page 839) rises above
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >V L3-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >V L3-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 127
This alarm is activated by Mains >V Protection (page 577).
Description This alarm is activated when Mains/Bus Voltage L3-N (page 840) rises over
preset value.

InteliNeo 6000 1.5.0 Global Guide 1302


Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
(page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-N
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >V L1-L2

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >V L1-L2

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 131
This alarm is activated by Mains >V Protection (page 577).
This alarm is activated when Mains/Bus Voltage L1-L2 (page 840) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1303


Mains/Bus >V L2-L3

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >V L2-L3

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 132
This alarm is activated by Mains >V Protection (page 577).
This alarm is activated when Mains/Bus Voltage L2-L3 (page 840) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-L3
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >V L3-L1

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >V L3-L1

InteliNeo 6000 1.5.0 Global Guide 1304


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >V Protection (page 577)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 133
This alarm is activated by Mains >V Protection (page 577).
This alarm is activated when Mains/Bus Voltage L3-L1 (page 840) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over
GeneratorBus Right >V (page 1) for period
longer than BESS >V Delay (page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >>V L1-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >>V L1-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1080
This alarm is activated by Mains >>V Protection (page 579).
Description This alarm is activated when Mains/Bus Voltage L1-N (page 839) rises over
preset value.

InteliNeo 6000 1.5.0 Global Guide 1305


Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
(page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >>V L2-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >>V L2-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1082
This alarm is activated by Mains >>V Protection (page 579).
This alarm is activated when Mains/Bus Voltage L2-N (page 839) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
Description (page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1306


Mains/Bus >>V L3-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message M Mains/Bus >>V L3-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1084
This alarm is activated by Mains >>V Protection (page 579).
This alarm is activated when Mains/Bus Voltage L3-N (page 840) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
Description (page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-N
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
(page 452).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >>V L1-L2

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >>V L1-L2

InteliNeo 6000 1.5.0 Global Guide 1307


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1086
This alarm is activated by Mains >>V Protection (page 579).
This alarm is activated when Mains/Bus Voltage L1-L2 (page 840) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
Description (page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >>V L2-L3

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >>V L2-L3

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1088
This alarm is activated by Mains >>V Protection (page 579).
Description This alarm is activated when Mains/Bus Voltage L2-L3 (page 840) rises over
preset value.

InteliNeo 6000 1.5.0 Global Guide 1308


Application Mode
Behavior
(page 885)
Alarm is activated by Mains >V Protection
MPTM
(page 577)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-L3
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus >>V L3-L1

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >>V L3-L1

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >>V Protection (page 579)!=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1090
This alarm is activated by Mains >>V Protection (page 579).
This alarm is activated when Mains/Bus Voltage L3-L1 (page 840) rises over
preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains >>V Protection
MPTM
Description (page 579)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) rises over BESS >>V
(page 452) for period longer than BESS >>V
Delay (page 453).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1309


Mains/Bus <V L1-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <V L1-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 122
This alarm is activated by Mains <V Protection (page 581).
This alarm is activated when Mains/Bus Voltage L1-N (page 839) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <V L2-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <V L2-N

InteliNeo 6000 1.5.0 Global Guide 1310


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 123
This alarm is activated by Mains <V Protection (page 581).
This alarm is activated when Mains/Bus Voltage L2-N (page 839) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <V L3-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <V L3-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 124
This alarm is activated by Mains <V Protection (page 581).
Description This alarm is activated when Mains/Bus Voltage L3-N (page 840) drops
below preset value.

InteliNeo 6000 1.5.0 Global Guide 1311


Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
(page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-N
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <V L1-L2

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <V L1-L2

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 128
This alarm is activated by Mains <V Protection (page 581).
This alarm is activated when Mains/Bus Voltage L1-L2 (page 840) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1312


Mains/Bus <V L2-L3

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <V L2-L3

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 129
This alarm is activated by Mains <V Protection (page 581).
This alarm is activated when Mains/Bus Voltage L2-L3 (page 840) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-L3
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <V L3-L1

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <V L3-L1

InteliNeo 6000 1.5.0 Global Guide 1313


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 581) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 130
This alarm is activated by Mains <V Protection (page 581).
This alarm is activated when Mains/Bus Voltage L3-L1 (page 840) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 581)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <<V L1-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <<V L1-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1081
This alarm is activated by Mains <V Protection (page 582).
Description This alarm is activated when Mains/Bus Voltage L1-N (page 839) drops
below preset value.

InteliNeo 6000 1.5.0 Global Guide 1314


Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
(page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <<V L2-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <<V L2-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1083
This alarm is activated by Mains <V Protection (page 582).
This alarm is activated when Mains/Bus Voltage L2-N (page 839) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-N
(page 839) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1315


Mains/Bus <<V L3-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <<V L3-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1085
This alarm is activated by Mains <V Protection (page 582).
This alarm is activated when Mains/Bus Voltage L3-N (page 840) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-N
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-N (page 381) drops below BESS <V
(page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <<V L1-L2

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <<V L1-L2

InteliNeo 6000 1.5.0 Global Guide 1316


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1087
This alarm is activated by Mains <V Protection (page 582).
This alarm is activated when Mains/Bus Voltage L1-L2 (page 840) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L1-L2
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <<V L2-L3

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <<V L2-L3

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1089
This alarm is activated by Mains <V Protection (page 582).
Description This alarm is activated when Mains/Bus Voltage L2-L3 (page 840) drops
below preset value.

InteliNeo 6000 1.5.0 Global Guide 1317


Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
(page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L2-L3
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus <<V L3-L1

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <<V L3-L1

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <V Protection (page 582) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 1091
This alarm is activated by Mains <V Protection (page 582).
This alarm is activated when Mains/Bus Voltage L3-L1 (page 840) drops
below preset value.

Application Mode
Behavior
(page 885)
Alarm is activated by Mains <V Protection
MPTM
Description (page 582)
Protection is always active. Alarm is activated
when relative value of Mains/Bus Voltage L3-L1
(page 840) related to Mains/Bus Nominal
MINT
Voltage Ph-Ph (page 381) drops below BESS
<V (page 453) for period longer than BESS <V
Delay (page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1318


Mains/Bus >f

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus >f

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains >f Protection (page 586) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 135
This alarm is activated by Mains >f Protection (page 586).
This alarm is activated when Mains/Bus Frequency (page 839), rises over
preset value.

Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains >f Protection (page
MPTM
586)
Protection is always active. Alarm is activated
when Mains/Bus Frequency (page 839) rises
MINT
over BESS >f (page 455) for period longer than
BESS >f Delay (page 455).
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

Mains/Bus >>f

Alarm Type
Alarmlist message Mains/Bus >>f
Alarm evaluated Only if Mains >>f Protection (page 587) != Disabled
Related applications MPTM
Alarm ID 1092
This alarm is activated by Mains >>f Protection (page 587).
This alarm is activated when Mains/Bus Frequency (page 839), rises over
Description
preset value.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1319


Mains/Bus <f

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus <f

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains <f Protection (page 588) !=
MPTM
Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 134
This alarm is activated by Mains >f Protection (page 586).
This alarm is activated when Mains/Bus Frequency (page 839), drops below
preset value.

Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains <f Protection (page
MPTM
588)
Protection is always active. Alarm is activated
when Mains/Bus Frequency (page 839) drops
MINT
below BESS <f (page 456) for period longer than
BESS <f Delay (page 456).
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

Mains/Bus <<f

Alarm Type
Alarmlist message Mains/Bus <<f
Alarm evaluated Only if Mains <<f Protection (page 589) != Disabled
Related applications MINT, MPTM
Alarm ID 1093
This alarm is activated by Mains <<f Protection (page 589).
This alarm is activated when Mains/Bus Frequency (page 839), drops below
Description
preset value.
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1320


Mains/Bus V Unbalance Ph-N

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus V Unbalance Ph-N

Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains V Unbalance Protection (page
MPTM
583) != Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 593
This alarm is activated by Mains V Unbalance Protection (page 583)
This alarm is activated when relative difference between Mains/Bus Voltage
L1-N (page 839), Mains/Bus Voltage L2-N (page 839) or Mains/Bus
Voltage L3-N (page 840) rises over preset value.

Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains V Unbalance
MPTM
Protection (page 583)
Protection is always active. Alarm is activated
when relative difference between bus voltages
MINT rises over BESS V Unbalance (page 454) for
period longer than BESS V Unbalance Delay
(page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Mains/Bus V Unbalance Ph-Ph

Application Mode
Alarm Type
(page 885)
Alarm Type MPTM Mains Protection (page 199)
MINT History Record Only (page 198)

Alarmlist message Mains/Bus V Unbalance Ph-Ph

InteliNeo 6000 1.5.0 Global Guide 1321


Application Mode
Evaluated
(page 885)
Alarm evaluated Only if Mains V Unbalance Protection (page
MPTM
583) != Disabled
MINT All the time

Related applications MINT, MPTM


Alarm ID 592
This alarm is activated by Mains V Unbalance Protection (page 583)
This alarm is activated when relative difference between Mains/Bus Voltage
L1-L2 (page 840), Mains/Bus Voltage L2-L3 (page 840) or Mains/Bus
Voltage L3-L1 (page 840) rises over preset value.

Application Mode
Behavior
(page 885)
Description Alarm is activated by Mains V Unbalance
MPTM
Protection (page 583)
Protection is always active. Alarm is activated
when relative difference between bus voltages
MINT rises over BESS V Unbalance (page 454) for
period longer than BESS V Unbalance Delay
(page 454).
This alarm has FPS - FIXED PROTECTIONS STATES 4 (PAGE 1183).

6 back to List of alarms level 1

Maintenance 1 Interval

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 1 Interval (page 657) != Disabled
Related applications MINT, MPTM
Alarm ID 1072
This alarm is activated when setpoint Maintenance Timer 1 Interval (page
657) elapses i.e. the value Maintenance Timer 1 Interval (page 881) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Maintenance 1 RunHours

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Protection
Alarm evaluated Only if Maintenance Timer 1 RunHours (page 656) != Disabled
Related applications MINT, MPTM
Alarm ID 585

InteliNeo 6000 1.5.0 Global Guide 1322


This alarm is activated when setpoint Maintenance Timer 1 RunHours (page
656) elapses i.e. the value Maintenance Timer 1 RunHours (page 881) = 0
Description
and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Maintenance 2 Interval

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 2 Interval (page 658) != Disabled
Related applications MINT, MPTM
Alarm ID 1073
This alarm is activated when setpoint Maintenance Timer 2 Interval (page
658) elapses i.e. the value Maintenance Timer 2 Interval (page 882) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Maintenance 2 RunHours

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 2 Protection
Alarm evaluated Only if Maintenance Timer 2 RunHours (page 658) != Disabled
Related applications MINT, MPTM
Alarm ID 586
This warning is activated when setpoint Maintenance Timer 2 RunHours
(page 658) elapses i.e. the value Maintenance Timer 2 RunHours (page
Description
881) = 0 and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Maintenance 3 Interval

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 3 Interval (page 660) != Disabled
Related applications MINT, MPTM
Alarm ID 1074
This alarm is activated when setpoint Maintenance Timer 3 Interval (page
660) elapses i.e. the value Maintenance Timer 3 Interval (page 882) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1323


Maintenance 3 RunHours

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 3 Protection
Alarm evaluated Only if Maintenance Timer 3 RunHours (page 659) != Disabled
Related applications MINT, MPTM
Alarm ID 587
This warning is activated when setpoint Maintenance Timer 3 RunHours
(page 659) elapses i.e. the value Maintenance Timer 3 RunHours (page
Description
882) = 0 and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Maintenance 4 Interval

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 1 Interval
Alarm evaluated Only if Maintenance Timer 4 Interval (page 661) != Disabled
Related applications MINT, MPTM
Alarm ID 1519
This alarm is activated when setpoint Maintenance Timer 4 Interval (page
661) elapses i.e. the value Maintenance Timer 4 Interval (page 883) = 0 and
Description
lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

Maintenance 4 RunHours

Alarm Type Based on configuration (Warning (page 198)/Slow Stop (page 199))
Alarmlist message Wrn/Stp Maintenance 4 Protection
Alarm evaluated Only if Maintenance Timer 4 RunHours (page 661) or != Disabled
Related applications MINT, MPTM
Alarm ID 1518
This warning is activated when setpoint Maintenance Timer 4 RunHours
(page 661) elapses i.e. the value Maintenance Timer 4 RunHours (page
Description
882) = 0 and lasts until the setpoint is set to value > 0 or "Disabled".
This alarm has FPS - FIXED PROTECTIONS STATES 7 (PAGE 1186).

6 back to List of alarms level 1

InteliNeo 6000 1.5.0 Global Guide 1324


DISTIN 01

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 01
Alarm evaluated Only if DIST-IN 01 is configured
Related applications MINT, MPTM
Alarm ID 1156
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 1.

6 back to List of other alarms

DISTIN 02

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 02
Alarm evaluated Only if DIST-IN 02 is configured
Related applications MINT, MPTM
Alarm ID 1157
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 2.

6 back to List of other alarms

DISTIN 03

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 03
Alarm evaluated Only if DIST-IN 03 is configured
Related applications MINT, MPTM
Alarm ID 1158
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 3.

6 back to List of other alarms

DISTIN 04

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 04
Alarm evaluated Only if DIST-IN 04 is configured
Related applications MINT, MPTM
Alarm ID 1159
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 4.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1325


DISTIN 05

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 05
Alarm evaluated Only if DIST-IN 05 is configured
Related applications MINT, MPTM
Alarm ID 1160
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 5.

6 back to List of other alarms

DISTIN 06

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 06
Alarm evaluated Only if DIST-IN 06 is configured
Related applications MINT, MPTM
Alarm ID 1161
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 6.

6 back to List of other alarms

DISTIN 07

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 07
Alarm evaluated Only if DIST-IN 07 is configured
Related applications MINT, MPTM
Alarm ID 1162
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 7.

6 back to List of other alarms

DISTIN 08

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 08
Alarm evaluated Only if DIST-IN 08 is configured
Related applications MINT, MPTM
Alarm ID 1163
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 8.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1326


DISTIN 09

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 09
Alarm evaluated Only if DIST-IN 09 is configured
Related applications MINT, MPTM
Alarm ID 1164
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 9.

6 back to List of other alarms

DISTIN 10

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 10
Alarm evaluated Only if DIST-IN 10 is configured
Related applications MINT, MPTM
Alarm ID 1165
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 10.

6 back to List of other alarms

DISTIN 11

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 11
Alarm evaluated Only if DIST-IN 11 is configured
Related applications MINT, MPTM
Alarm ID 1166
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 11.

6 back to List of other alarms

DISTIN 12

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 12
Alarm evaluated Only if DIST-IN 12 is configured
Related applications MINT, MPTM
Alarm ID 1167
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 12.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1327


DISTIN 13

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 13
Alarm evaluated Only if DIST-IN 13 is configured
Related applications MINT, MPTM
Alarm ID 1168
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 13.

6 back to List of other alarms

DISTIN 14

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 14
Alarm evaluated Only if DIST-IN 14 is configured
Related applications MINT, MPTM
Alarm ID 1169
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 14.

6 back to List of other alarms

DISTIN 15

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 15
Alarm evaluated Only if DIST-IN 15 is configured
Related applications MINT, MPTM
Alarm ID 1170
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 15.

6 back to List of other alarms

DISTIN 16

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 16
Alarm evaluated Only if DIST-IN 16 is configured
Related applications MINT, MPTM
Alarm ID 1171
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 16.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1328


DISTIN 17

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 17
Alarm evaluated Only if DIST-IN 17 is configured
Related applications MINT, MPTM
Alarm ID 1172
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 17.

6 back to List of other alarms

DISTIN 18

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 18
Alarm evaluated Only if DIST-IN 18 is configured
Related applications MINT, MPTM
Alarm ID 1173
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 18.

6 back to List of other alarms

DISTIN 19

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 19
Alarm evaluated Only if DIST-IN 19 is configured
Related applications MINT, MPTM
Alarm ID 1174
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 19.

6 back to List of other alarms

DISTIN 20

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 20
Alarm evaluated Only if DIST-IN 20 is configured
Related applications MINT, MPTM
Alarm ID 1175
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 20.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1329


DISTIN 21

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 21
Alarm evaluated Only if DIST-IN 21 is configured
Related applications MINT, MPTM
Alarm ID 1176
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 21.

6 back to List of other alarms

DISTIN 22

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 22
Alarm evaluated Only if DIST-IN 22 is configured
Related applications MINT, MPTM
Alarm ID 1177
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 22.

6 back to List of other alarms

DISTIN 23

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 23
Alarm evaluated Only if DIST-IN 23 is configured
Related applications MINT, MPTM
Alarm ID 1178
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 23.

6 back to List of other alarms

DISTIN 24

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 24
Alarm evaluated Only if DIST-IN 24 is configured
Related applications MINT, MPTM
Alarm ID 1179
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 24.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1330


DISTIN 25

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 25
Alarm evaluated Only if DIST-IN 25 is configured
Related applications MINT, MPTM
Alarm ID 1180
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 25.

6 back to List of other alarms

DISTIN 26

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 26
Alarm evaluated Only if DIST-IN 26 is configured
Related applications MINT, MPTM
Alarm ID 1181
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 26.

6 back to List of other alarms

DISTIN 27

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 27
Alarm evaluated Only if DIST-IN 27 is configured
Related applications MINT, MPTM
Alarm ID 1182
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 27.

6 back to List of other alarms

DISTIN 28

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 28
Alarm evaluated Only if DIST-IN 28 is configured
Related applications MINT, MPTM
Alarm ID 1183
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 28.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1331


DISTIN 29

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 29
Alarm evaluated Only if DIST-IN 29 is configured
Related applications MINT, MPTM
Alarm ID 1184
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 29.

6 back to List of other alarms

DISTIN 30

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 30
Alarm evaluated Only if DIST-IN 30 is configured
Related applications MINT, MPTM
Alarm ID 1185
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 30.

6 back to List of other alarms

DISTIN 31

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 31
Alarm evaluated Only if DIST-IN 31 is configured
Related applications MINT, MPTM
Alarm ID 1186
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 31.

6 back to List of other alarms

DISTIN 32

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 32
Alarm evaluated Only if DIST-IN 32 is configured
Related applications MINT, MPTM
Alarm ID 1187
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 32.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1332


DISTIN 33

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 33
Alarm evaluated Only if DIST-IN 33 is configured
Related applications MINT, MPTM
Alarm ID 1344
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 33.

6 back to List of other alarms

DISTIN 34

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 34
Alarm evaluated Only if DIST-IN 34 is configured
Related applications MINT, MPTM
Alarm ID 1345
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 34.

6 back to List of other alarms

DISTIN 35

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 35
Alarm evaluated Only if DIST-IN 35 is configured
Related applications MINT, MPTM
Alarm ID 1346
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 35.

6 back to List of other alarms

DISTIN 36

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 36
Alarm evaluated Only if DIST-IN 36 is configured
Related applications MINT, MPTM
Alarm ID 1347
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 36.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1333


DISTIN 37

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 37
Alarm evaluated Only if DIST-IN 37 is configured
Related applications MINT, MPTM
Alarm ID 1348
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 37.

6 back to List of other alarms

DISTIN 38

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 38
Alarm evaluated Only if DIST-IN 38 is configured
Related applications MINT, MPTM
Alarm ID 1349
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 38.

6 back to List of other alarms

DISTIN 39

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 39
Alarm evaluated Only if DIST-IN 39 is configured
Related applications MINT, MPTM
Alarm ID 1350
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 39.

6 back to List of other alarms

DISTIN 40

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 40
Alarm evaluated Only if DIST-IN 40 is configured
Related applications MINT, MPTM
Alarm ID 1351
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 40.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1334


DISTIN 41

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 41
Alarm evaluated Only if DIST-IN 41 is configured
Related applications MINT, MPTM
Alarm ID 1352
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 41.

6 back to List of other alarms

DISTIN 42

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 42
Alarm evaluated Only if DIST-IN 42 is configured
Related applications MINT, MPTM
Alarm ID 1353
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 42.

6 back to List of other alarms

DISTIN 43

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 43
Alarm evaluated Only if DIST-IN 43 is configured
Related applications MINT, MPTM
Alarm ID 1354
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 43.

6 back to List of other alarms

DISTIN 44

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 44
Alarm evaluated Only if DIST-IN 44 is configured
Related applications MINT, MPTM
Alarm ID 1355
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 44.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1335


DISTIN 45

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 45
Alarm evaluated Only if DIST-IN 45 is configured
Related applications MINT, MPTM
Alarm ID 1356
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 45.

6 back to List of other alarms

DISTIN 46

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 46
Alarm evaluated Only if DIST-IN 46 is configured
Related applications MINT, MPTM
Alarm ID 1357
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 46.

6 back to List of other alarms

DISTIN 47

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 47
Alarm evaluated Only if DIST-IN 47 is configured
Related applications MINT, MPTM
Alarm ID 1358
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 47.

6 back to List of other alarms

DISTIN 48

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 48
Alarm evaluated Only if DIST-IN 48 is configured
Related applications MINT, MPTM
Alarm ID 1359
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 48.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1336


DISTIN 49

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 49
Alarm evaluated Only if DIST-IN 49 is configured
Related applications MINT, MPTM
Alarm ID 1360
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 49.

6 back to List of other alarms

DISTIN 50

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 50
Alarm evaluated Only if DIST-IN 50 is configured
Related applications MINT, MPTM
Alarm ID 1361
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 50.

6 back to List of other alarms

DISTIN 51

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 51
Alarm evaluated Only if DIST-IN 51 is configured
Related applications MINT, MPTM
Alarm ID 1362
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 51.

6 back to List of other alarms

DISTIN 52

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 52
Alarm evaluated Only if DIST-IN 52 is configured
Related applications MINT, MPTM
Alarm ID 1363
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 52.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1337


DISTIN 53

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 53
Alarm evaluated Only if DIST-IN 53 is configured
Related applications MINT, MPTM
Alarm ID 1364
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 53.

6 back to List of other alarms

DISTIN 54

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 54
Alarm evaluated Only if DIST-IN 54 is configured
Related applications MINT, MPTM
Alarm ID 1365
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 54.

6 back to List of other alarms

DISTIN 55

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 55
Alarm evaluated Only if DIST-IN 55 is configured
Related applications MINT, MPTM
Alarm ID 1366
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 55.

6 back to List of other alarms

DISTIN 56

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 56
Alarm evaluated Only if DIST-IN 56 is configured
Related applications MINT, MPTM
Alarm ID 1367
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 56.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1338


DISTIN 57

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 57
Alarm evaluated Only if DIST-IN 57 is configured
Related applications MINT, MPTM
Alarm ID 1368
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 57.

6 back to List of other alarms

DISTIN 58

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 58
Alarm evaluated Only if DIST-IN 58 is configured
Related applications MINT, MPTM
Alarm ID 1369
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 58.

6 back to List of other alarms

DISTIN 59

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 59
Alarm evaluated Only if DIST-IN 59 is configured
Related applications MINT, MPTM
Alarm ID 1370
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 59.

6 back to List of other alarms

DISTIN 60

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 60
Alarm evaluated Only if DIST-IN 60 is configured
Related applications MINT, MPTM
Alarm ID 1371
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 60.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1339


DISTIN 61

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 61
Alarm evaluated Only if DIST-IN 61 is configured
Related applications MINT, MPTM
Alarm ID 1372
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 61.

6 back to List of other alarms

DISTIN 62

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 62
Alarm evaluated Only if DIST-IN 62 is configured
Related applications MINT, MPTM
Alarm ID 1373
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 62.

6 back to List of other alarms

DISTIN 63

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 63
Alarm evaluated Only if DIST-IN 63 is configured
Related applications MINT, MPTM
Alarm ID 1374
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 63.

6 back to List of other alarms

DISTIN 64

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTIN 64
Alarm evaluated Only if DIST-IN 64 is configured
Related applications MINT, MPTM
Alarm ID 1375
This alarm is activated when DIST-IN data are not received from controller with
Description
CAN Controller Address (page 392) = 64.

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1340


DISTOUT

Alarm Type Based on configuration


Alarmlist message Wrn/Sd DISTOUT
Alarm evaluated Only if DIST-OUT is configured
Related applications MINT, MPTM
Description This alarm is activated when failure of virtual module DIST-OUT is detected.

6 back to List of other alarms

ECU 1 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 1
1. ECU with protection configured in ECU slot 1
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 1 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 945
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 1.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 2 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 2
1. ECU with protection configured in ECU slot 2
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 2 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 946
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 2.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 3 Comm Fail

Alarm Type Based on configuration

InteliNeo 6000 1.5.0 Global Guide 1341


Alarmlist message Name of ECU in ECU slot 3
1. ECU with protection configured in ECU slot 3
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 3 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 947
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 3.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 4 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 4
1. ECU with protection configured in ECU slot 4
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 4 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 948
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 4.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 5 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 5
1. ECU with protection configured in ECU slot 5
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 5 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 949
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 5.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

InteliNeo 6000 1.5.0 Global Guide 1342


6 back to List of other alarms

ECU 6 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 6
1. ECU with protection configured in ECU slot 6
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 6 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 950
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 6.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 7 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 7
1. ECU with protection configured in ECU slot 7
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 7 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 951
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 7.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 8 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 8
1. ECU with protection configured in ECU slot 8
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 8 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 1343


Alarm ID 952
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 8.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 9 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 9
1. ECU with protection configured in ECU slot 9
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 9 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 953
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 9.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 10 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 10
1. ECU with protection configured in ECU slot 10
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 10 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 954
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 10.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 11 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 11
1. ECU with protection configured in ECU slot 11
Alarm evaluated
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU

InteliNeo 6000 1.5.0 Global Guide 1344


COMMUNICATION FAIL BLOCK 11 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 955
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 11.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 12 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 12
1. ECU with protection configured in ECU slot 12
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 12 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 956
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 12.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 13 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 13
1. ECU with protection configured in ECU slot 13
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 13 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 957
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 13.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1345


ECU 14 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 14
1. ECU with protection configured in ECU slot 14
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 14 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 958
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 14.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 15 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 15
1. ECU with protection configured in ECU slot 15
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 15 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 959
This alarm is activated when there is no communication received from ECU
Description configured in ECU slot 15.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

ECU 16 Comm Fail

Alarm Type Based on configuration


Alarmlist message Name of ECU in ECU slot 16
1. ECU with protection configured in ECU slot 16
2. LBI ECU COMMUNICATION FAIL BLOCK (PAGE 1) and ECU
Alarm evaluated COMMUNICATION FAIL BLOCK 16 (PAGE 1) not activated
3. LBO ECU POWER RELAY (PAGE 1074) is closed or all the time when is
not configured
Related applications MINT, MPTM
Alarm ID 960
Description This alarm is activated when there is no communication received from ECU

InteliNeo 6000 1.5.0 Global Guide 1346


configured in ECU slot 16.
This alarm has FPS - FIXED PROTECTIONS STATES 3 (PAGE 1182).

6 back to List of other alarms

SHAIN 1

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHAIN 1
Alarm evaluated Only if SHAIN 1 is configured
Related applications MINT, MPTM
Alarm ID 36
This alarm is activated when shared analog inputs are not received from SHAIN
Description
module 1.

6 back to List of alarms level 1

SHAIN 2

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHAIN 2
Alarm evaluated Only if SHAIN 2 is configured
Related applications MINT, MPTM
Alarm ID 233
This alarm is activated when shared analog inputs are not received from SHAIN
Description
module 2.

6 back to List of alarms level 1

Wrn SHAIN Collision

Alarm Type Warning (page 198)


Alarmlist message Wrn SHAIN Collision
Alarm evaluated Only if SHIN 1 or SHAIN 2 module is configured
Related applications MINT, MPTM
Alarm ID 38
This alarm is activated when controller receives shared analog inputs of any
Description SHAIN module from more than just one controller.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

SHBIN 1

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHBIN 1
Alarm evaluated Only if SHBIN 1 is configured
Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 1347


Alarm ID 32
This alarm is activated when shared binary inputs are not received from SHBIN
Description
module 1.

6 back to List of alarms level 1

SHBIN 2

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHBIN 2
Alarm evaluated Only if SHBIN 2 is configured
Related applications MINT, MPTM
Alarm ID 33
This alarm is activated when shared binary inputs are not received from SHBIN
Description
module 2.

6 back to List of alarms level 1

SHBIN 3

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHBIN 3
Alarm evaluated Only if SHBIN 3 is configured
Related applications MINT, MPTM
Alarm ID 34
This alarm is activated when shared binary inputs are not received from SHBIN
Description
module 3.

6 back to List of alarms level 1

SHBIN 4

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHBIN 4
Alarm evaluated Only if SHBIN 4 is configured
Related applications MINT, MPTM
Alarm ID 35
This alarm is activated when shared binary inputs are not received from SHBIN
Description
module 4.

6 back to List of alarms level 1

SHBIN 5

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHBIN 5
Alarm evaluated Only if SHBIN 5 is configured
Related applications MINT, MPTM

InteliNeo 6000 1.5.0 Global Guide 1348


Alarm ID 216
This alarm is activated when shared binary inputs are not received from SHBIN
Description
module 5.

6 back to List of alarms level 1

SHBIN 6

Alarm Type Based on configuration


Alarmlist message Wrn/Sd SHBIN 6
Alarm evaluated Only if SHBIN 6 is configured
Related applications MINT, MPTM
Alarm ID 217
This alarm is activated when shared binary inputs are not received from SHBIN
Description
module 6.

6 back to List of alarms level 1

Wrn SHBIN Collision

Alarm Type Warning (page 198)


Alarmlist message Wrn SHBIN Collision
Alarm evaluated Only if at least one of SHBIN 1 to SHBIN 6 modules is configured
Related applications MINT, MPTM
Alarm ID 37
This alarm is activated when controller receives shared binary inputs of any
Description SHBIN module from more than just one controller.
This alarm has FPS - FIXED PROTECTIONS STATES 1 (PAGE 1180)

6 back to List of alarms level 1

VRT Protection Trip

Alarm Type Based on Dynamic Support Protection Type (page 561)


Alarmlist message Wrn/MP VRT Protection Trip
Only when Dynamic Support (page 561) = Enabled and and Breaker state
Alarm evaluated
(page 886) = ParalOper
Related applications MINT, MPTM
Alarm ID 1043
This alarm indicates active Dynamic Support (page 561) protection.
Description
This alarm has FPS - FIXED PROTECTIONS STATES 5 (PAGE 1184)

6 back to List of other alarms

InteliNeo 6000 1.5.0 Global Guide 1349


9.3 Modules
9.3.1 Plug-in modules
IMPORTANT: 2nd generation of InteliNeo 6000 controllers does not support new modules and 3rd
generation does not support all old modules.

The available communication plug-in modules are:


CM-RS232-485 – communication module for connection via RS232 or RS485 line
CM2-4G-GPS – communication module for connection via 4G
CM3-Ethernet – communication module for internet connection via Ethernet
The available extension plug-in modules are:
EM-BIO8-EFCP – extension module with 8 binary inputs/outputs and with earth fault current protection

Note: Controller has 2 plug-in module slots.

Supported combinations of plug-in modules


Module CM-Ethernet CM-4G-GPS CM-RS232-485 EM-BIO8-EFCP

CM-Ethernet

CM-4G-GPS

CM-RS232-485

EM-BIO8-EFCP

Communication modules
CM2-4G-GPS 1350

CM2-4G-GPS
CM2-4G-GPS plug-in module containing a GPS receiver and GSM/WCDMA/LTE modem which can work in
two modes of operation.

Image 7.94 CM2-4G-GPS module

InteliNeo 6000 1.5.0 Global Guide 1350


IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.

IMPORTANT: Operating temperature of module is from -30 °C to +75 °C.

Note: Cellular data service must be enabled in your SIM card by your mobile operator for successful
operation.

CM2-4G-GPS module works with:


WebSupervisor – internet-based remote monitoring solution
AirGate – powerful connection technology to make internet access as simple as possible
CM2-4G-GPS module also works like GPS locator. Geo-fencing function can be used with this module.

4G module types

If the anthenna is CELLULAR only and has 1 cable (OT1A4GXXMCX), it is connected to the 4G-MAIN
connector.
If the anthenna is CELLULAR only and has 2 cables, cables are connected to the 4G-MAIN or 4G-DIV
connectors (does not matter which cable to which connector).
If the anthenna is a combination of CELLULAR/GPS and has 2 cables (OT1A4GGPSCX), then cable
"4G/LTE" needs to be connected to the 4G-MAIN connector and "GPS" cable to the GPS connector.
If the anthenna is a combination of CELLULAR/GPS and has 3 cables (OT2A4GGPSCX), then cables
"4G/LTE" need to be connected to the 4G-MAIN and 4G-DIV connectors (does not matter which cable to
which connector) and "GPS" cable to the GPS connector.
Note: Type of the cable is labeled on its side.

Technical data
General
Width × Height × Depth 73.8 × 50.3 × 15
Weight ~35 g
Power supply 8-36 V DC
Power consumption 1.7 W
Peak power consumption 10 W
Operating temperature -30 ˚C to +70 ˚C
Storage temperature -40 ˚C to +80 ˚C

InteliNeo 6000 1.5.0 Global Guide 1351


GNSS
Antenna interface SMA female, 2.8 V / 20 mA
Antenna type Active

Cellular
2G (GSM/GPRS/EDGE) Quad band,
850/900/1800/1900 MHz
3G (UMTS/HSPA+) Seven band, 800
(BdXIX) / 850 (BdV) / 900 (BdVIII) / AWS
(BdIV) / 1800 (BdIX) / 1900 (BdII) /
Supported networks and frequency bands
2100MHz (BdI)
4G (LTE) Twelve band, 700 (Bd12 <MFBI
Bd17>, Bd28) 800 (Bd18, Bd19, Bd20) 850
(Bd5) / 900 (Bd8) / AWS (Bd4) / 1800 (Bd3)
/ 1900 (Bd2) / 2100 (Bd1) / 2600MHz (Bd7)
Antenna interface 2x SMA female (Main and Diversity)

SIM card settings


SIM card must be adjusted as follows:
SMS service enabled
Packet data (Internet access) enabled (when required for the selected mode of operation)
PIN code security disabled

How to start using CM2-4G-GPS module


You will need a controller, CM2-4G-GPS module, antenna and SIM card with SMS and packet data
service.
Note: Make sure that your SIM supports the packet data network type you want to use. – i.e. if you want to
use the module in LTE (4G) network you have to confirm with the operator that the particular SIM card
supports 4G network.

Contact your mobile operator for getting packet data APN (APN = Access Point Name), username and
password.
Example: APN Name = "internet", UserName = [blank], Password = [blank].

Make sure SIM card does not require PIN code. Use any mobile phone to switch the SIM PIN security off.
Place the SIM card into slot on CM2-4G-GPS card
Connect the antenna to Cellular module antenna connector.
If you want to use the built-in GPS receiver, also connect an active GPS antenna to the GPS antenna
connector.
Switch off the controller.
Insert CM2-4G-GPS module into controller
Power up the controller.
Select the mode of CM2-4G-GPS module by adjusting setpoint Internet Connection (page 672).
Activate CM2-4G-GPS module by switching the setpoint Internet Connection (page 672) to enabled.

InteliNeo 6000 1.5.0 Global Guide 1352


Enter correct APN Name, APN User Name and APN User Password in controller's setpoint group CM-4G-
GPS which is accessible by PAGE button from any measurement screen on controller. Setpoints can be
set on controller’s front panel keyboard or by InteliConfig.
Enter correct Access Point Name (this information is provided by Mobile Operator). Setpoint can be set
on controller's front panel or by InteliConfig.
Switch the controller off and on.
Wait for approx 2 – 4 minutes for first connection of the system to AirGate. AirGate will automatically
generate the AirGate ID value. Then navigate to measurement screens where you will find signal strength
bar and AirGate ID identifier.

Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Install package to computer or open PSI to install it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate
firmware you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is re-established again automatically when the
update process is finished.

Extension modules
EM-BIO8-EFCP 1353

EM-BIO8-EFCP
EM-BIO8-EFCP is optional plug-in card. Through this card, the controller can accommodate one AC current
(CT) measuring input (1A or 5A input) and up to 8 binary inputs or outputs. In InteliConfig PC configuration
tool it is possible to easily choose whether particular I/O will be binary input or output.

Image 7.95 EM-BIO8-EFCP interface

InteliNeo 6000 1.5.0 Global Guide 1353


Note: This protection is active ONLY when Engine is running.

IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.

IMPORTANT: Earth fault current measurement is supported by controller only in slot A.

Image 7.96 Overview of EM-BIO8-EFCP

Image 7.97 EM-BIO8-EFCP wiring

EM-BIO8-EFCP technical data

Power supply
Power supply range 8-36 VDC
40 mA / 8 VDC
27 mA / 12 VDC
Power consumption
22 mA / 24 VDC
19 mA / 36 VDC

InteliNeo 6000 1.5.0 Global Guide 1354


Binary inputs
Number Up to 8, non-isolated
Close/Open 0-2 VDC close contact
indication >6 VDC open contact

Binary outputs
Number Up to 8 , non-isolated
Max. current 0,5A
Switching to positive supply terminal

Current measuring input


Number of inputs 2
Nominal input current 1A/5A
Load (CT output impedance) < 0,1
Max measured current from CT 10 A
Current measurement
2% from Nominal current
tolerance
Max peak current from CT 150 A / 1 s
Max continuous current 10 A

Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Install package to computer or open PSI to install it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate
firmware you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is re-established again automatically when the
update process is finished.

9.3.2 CAN modules


Supported combinations of modules 1355
Module's protections 1356
Theory of binary inputs and outputs 1357
Extension modules 1361

Supported combinations of modules


The maximal number of CAN modules is limited by the number of the controller's generic modules. Once the
physical module is configured, it allocates necessary generic modules. So, it is possible to configure as many
CAN modules as many generic modules are available. The maximum number of CAN modules is also limited

InteliNeo 6000 1.5.0 Global Guide 1355


by the number of addresses (indexes) that can be configured for each type of the generic module. CAN
modules and generic modules share indexes.
Example: If you configure Inteli IO8/8 module which is using 1x BI, BO, and AO generic module with index
(address) 1, any other module using same generic modules will not be able to be configured with index
(address) 1 (IGS-PTM, Inteli AIO9/1).

Each generic module has 8 "terminals" (inputs/outputs) and the InteliNeo 6000 has the following amount of
the generic modules:
AI generic: 10
AO generic: 8
BI generic: 16
BO generic: 12
In the table below, you can see how many generic modules are necessary for each CAN module and how
many indexes are available for each type of CAN module in the InteliNeo 6000.

Max number of
CAN Module AI generic AO generic BI generic BO generic
indexes
Inteli AIN8 10 1 0 0 0
Inteli IO 8/8 12 0 1 1 1
Inteli IO 16/0 8 0 1 2 0
IGL-RA15 4 0 0 0 2
IGS-PTM 4 1 1 1 1
Inteli AIO9/1 5 2 1 0 0
Inteli AIN8TC 10 1 0 0 0
I-AOUT8 4 0 1 0 0
IS-AIN8 10 1 0 0 0
IS-AIN8TC 10 1 0 0 0
IS-BIN16/8 7 0 0 2 1

Note: When configuring modules do not forget to let first 4 indexes free for modules which can't use high
addresses such as IGL-RA15, IGS-PTM, AIO9/1, I-AOUT8.

Note: Module Inteli IO8/8 has available AOUT only if it is configured with index number below 9 and Inteli
AIO9/1 has available AOUT only if it is configured with index number below 5.

Note: Module Inteli IO8/8 with older FW than 1.3.1.2 has available AOUT only if it is configured with index
number below 5.

Module's protections
Each configured CAN module can has it's own protection and protection state. For setup: connect the
controller via InteliConfig → Control → Controller Configuration → Modules → Module Settings.
Protection Upon Module Failure
None - No alarm will be activated if module fails. It is not possible to use the User Protection State.
Warning - Wrn alarm is activated if module fails.
Shutdown - Sd alarm is activated if module fails.

InteliNeo 6000 1.5.0 Global Guide 1356


Note: The name and color of the alarm is automatically generated according to the options Protection Upon
Module Failure, Module Name, and Module Index. The module name is automatically generated or
renamed by the user.

Protection State - If you check the check box the new User Protection State will be displayed in the User
Protection States group in the Values after the configuration is imported to the CU.
Note: The name of the User Protection State is automatically generated according to the options Protection
Upon Module Failure, Module Name, and Module Index. The module name is automatically generated or
renamed by the user.

Example: Wrn Inteli AIN8 10 = Warning upon module failure of the Inteli AIN8 module with index 10.

Theory of binary inputs and outputs


Binary inputs 1357
Binary outputs 1359
Type of the binary inputs/outputs of some configured modules using BINs or BOUTs can be changed via Inteli
Config. For setup: connect the controller via InteliConfig → Control → Controller Configuration → Modules →
Module Settings → Binary Inputs Type / Binary Outputs Type.
See the fallowing chapters for more details.

Binary inputs

Pull Down
The pull-down logic is used when it is required to ensure that the logical value of inputs settles at the expected
logical level whenever external devices are turned off, or they are at a high impedance state. It ensures that
input is at a defined low logic level when the connection with external devices is lost. In the controller
(module), the pull-down resistor is used to connect the input to the -BAT (0 V), so the log 0 (open state) is
represented by 0 V. This connection is used as prevention against fluctuations and an undefined state at the
input.
The principle of internal connection is shown in the picture below.
The bulb represents internal state of binary input.
In case the “COM” (+Ucc) is not connected to the input terminal “BIN” then the internal state is logical 0.
In case the “COM” (+Ucc) is connected to the input terminal “BIN” then the internal state is logical 1.

InteliNeo 6000 1.5.0 Global Guide 1357


Note: There is not any COM terminal on the controller, the wire is directly connected to the input terminal
"BIN", so if input signal is log 1 the +Ucc is directly connected to the "BIN".

Pull Up
The pull-up logic is used when it is required to establish an additional loop over the critical components while
making sure that the voltage is well-defined even when the switch is open. It ensures that input and wiring is
at a defined high logical level in the absence of an input signal. In the controller (module), the pull-up resistor
is used to connect the input to the +BAT (+Ucc), so the log 0 (open state) is represented by +Ucc. This
connection is used as prevention against fluctuations and an undefined state at the input.
The principle of internal connection is shown in the picture below.
The bulb represents internal state of binary input.
In case the input terminal “BIN” (+Ucc) is not connected to the “COM” (GND) then the internal state is
logical 0.
In case the input terminal “BIN” (+Ucc) is connected to the “COM” (GND) then the internal state is logical
1.

InteliNeo 6000 1.5.0 Global Guide 1358


Note: There is not any COM terminal on the controller, the wire is directly connected to the input terminal
"BIN", so if input signal is log 1 the GND is directly connected to the "BIN".

6 back to Theory of binary inputs and outputs

Binary outputs

High side switch - HSS


The high side logic is used when load is permanently connected to the ground (GND) and when it is required
to ensure that the logical value of outputs settles at the expected logical level whenever the controller
(module) is turned off, or at a high impedance state. It ensures that external devices will not be randomly
activated when the connection is lost.
The principle of internal connection is shown in the picture below.
The bulb represents internal state of binary output.
By activating of binary output terminal (BOUT), the switch is closed, which causes connection of the load
to the VHS (Voltage High side) and +Ucc, so the external state of the load is logical 1.

InteliNeo 6000 1.5.0 Global Guide 1359


Low side switch - LSS
The low side logic is used when load is permanently connected to the voltage (+Ucc). In case module will be
turned off or the connection will be lost the external devices will be activated. It can be used as inverse logic
for the detection of the lost connection.
The principle of internal connection is shown in the picture below.
The bulb represents internal state of binary output.
By activating of binary output terminal (BOUT), the switch is closed, which causes connection of the load
to the ground (GND), so the external state of the load is logical 1.
Note: Because of safety reasons, the Low side switch is not supported in the InteliNeo 6000 controller. In
case you need BOUT to BIN logical communication between controllers using Pull Up BIN logic, you must
use an external module with LSS BOUT logic or any converter which converts the HSS controller's BOUT to
LSS. The solution above is not recommended! Try to reconsider your options and use the Pull Down BIN
logic.

InteliNeo 6000 1.5.0 Global Guide 1360


6 back to Theory of binary inputs and outputs

Extension modules
Inteli AIN8 1361
Inteli IO8/8 1367
IGL-RA15 1374
IGS-PTM 1379
Inteli AIO9/1 1384
Inteli AIN8TC 1389
I-AOUT8 1393
IS-AIN8 1397
IS-AIN8TC 1407
IS-BIN16/8 1411

Inteli AIN8
Inteli AIN8 module is extension module equipped with analog inputs and Impulse/RPM input. The module is
connected to controller by CAN1A (page 19) bus. It is possible to connect up to 10 Inteli AIN8 external units
to one controller.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.

InteliNeo 6000 1.5.0 Global Guide 1361


Image 7.98 Inteli AIN8

Image 7.99 Inteli AIN8 dimensions

Note: All dimensions are in mm.

InteliNeo 6000 1.5.0 Global Guide 1362


Terminals

Analog input 8 analog Inputs


CAN1 CAN1A (page 19) line
Power Power supply
CAN LED Tx, Rx Indication transmitted or received data
Status LED LED indication of correct function
CAN terminator Terminating CAN resistor (active in position “ON” - switch both switches)

IMPORTANT: Impulse input is not supported by the controller.

Analog inputs
8 channels
can be configured as:
resistor three wire input
current input
voltage input
All inputs can be configured to any logical function or protection.

Supported sensors

Sensors
PT100 [°C] (fix) PT100 [°F] (fix) +-1V 4-20mA passive 0-250 ohm
PT1000 [°C] (fix) PT1000 [°F] (fix) 0-2.4V 4-20mA active 0-2400 ohm
NI100 [°C] (fix) NI100 [°F] (fix) 0-5V 0-20mA passive 0-10k ohm
NI1000 [°C] (fix) NI1000 [°F] (fix) 0-10V +-20mA active

Note: It is also possible to use User Curves as sensor.

InteliNeo 6000 1.5.0 Global Guide 1363


CAN address
DIP switch determinates CAN address for analog inputs.

Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.

Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
4. Connect the unit with PC via RS232-null modem cable and AT-Link conv

5. Connect power supply of the module (status LED lights continuously)


6. Launch FlashPgr.exe PC software (version 4.2 or higher)
7. In FlashPrg program choose card Inteli AIN8 and load FW for the module
8. Set the proper COM port (connected with the unit) and press Start button
9. Wait till process is done (If the process doesn’t start – after 60 second the “Timeout” will be evaluated. In
this case please check:
You have proper connection with the unit
COM port selection is correct
Module has power supply, (no CAN bus connection, status LED lights continuously)
10. After successful programming disconnect AT-Link conv , remove TEST jumper and disconnect power
supply

InteliNeo 6000 1.5.0 Global Guide 1364


11. Connect power supply again (status LED should blinking)
12. Module FW is upgraded

LED indication

LED status Description


Dark Fw in module does not work correctly.
Flashing Module does not communicate with controller (in case non-zero CAN address).
Power supply is in the range and the communication between Inteli AIN8 and controller
works properly.
Lights
Or power supply is in range and zero CAN address is set. (in case zero CAN address
module doesn’t communicate with the controller).

Wiring
The following diagrams show the correct connection of sensors.
Terminator

Resistance sensor - 3 wires

Note: Ranges: Pt100, Pt1000, Ni100, Ni1000, 0 – 2400 Ω, 0 – 10 kΩ

InteliNeo 6000 1.5.0 Global Guide 1365


Resistance sensor - 2 wires

Note: Ranges: Pt100, Pt1000, Ni100, Ni1000, 0 – 2400 Ω, 0 – 10 kΩ

Current sensor - active

Note: Ranges: ±20 mA, 4 – 20 mA

Current sensor - passive

Note: Ranges: 0 – 20 mA, 4 – 20 mA

InteliNeo 6000 1.5.0 Global Guide 1366


Voltage sensor

Note: Ranges: ±1 V, 0 – 2,5 V, 0 – 5 V, 0 – 10 V

Technical data

General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 110x110x46 mm (4,3”x4,3”x1,8”)
Weight 221,5 grams

Analog inputs
Number of channels 8
Range 0-10 V
Voltage
Accuracy: ± 0,25 % of actual value + ± 25 mV
Range: ±20 mA
Current
Accuracy: ± 0,25 % of actual value + ± 50 µA
Range: 0- 10 kΩ
Resistive
Accuracy: ± 0,5 % of actual value + ± 2 Ω

6 back to Extension modules

Inteli IO8/8
Inteli IO8/8 module is an extension module equipped with binary inputs, binary outputs and analog outputs.
The module is connected to controller by CAN1A (page 19) bus.
Inteli IO8/8 is the name of the module, but it is possible to configure the module (by internal switch) to two
configurations:
Inteli IO8/8 - 8 binary inputs, 8 binary outputs and 2 analog outputs
Inteli IO16/0 - 16 binary inputs, 0 binary outputs and 2 analog outputs
It is possible to connect up to 12 Inteli IO8/8 or 8 Inteli IO 16/0 external units to one controller.

InteliNeo 6000 1.5.0 Global Guide 1367


The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.

Image 7.100 Inteli IO8/8

Image 7.101 Inteli IO8/8 dimensions

Note: All dimensions are in mm.

InteliNeo 6000 1.5.0 Global Guide 1368


Terminals

Binary inputs 8 binary inputs


Binary outputs 8 binary outputs (8 binary inputs)
Analog outputs 2 analog outputs
CAN1 CAN1A (page 19) line
Power Power supply
Binary inputs LEDs 8 LEDs for binary input indication
Binary outputs LEDs 8 LEDs for binary output indication
CAN LED Indication transmitted or received data
Status LED indication of correct function
CAN terminator Terminating CAN resistor (active in position “ON” - switch both switches)

Inputs and outputs


Binary inputs
8 channels
can be configured as:
pull up
pull down
All 8 inputs are configured to one type together.
All inputs can be configured to any logical function or protection.
Binary outputs

InteliNeo 6000 1.5.0 Global Guide 1369


8 channels
can be configured as:
High side switch
Low side switch
Always all 8 inputs are configured to one type (HSS/LSS) together. All 8 outputs can be modified to inputs by
switch on the PCB ( Inteli IO8/8 to Inteli IO16/0).
Analog outputs
2 channels
can be configured as:
voltage 0-10V
current 0-20mA
PWM (level 5V, with adjustable frequency from 200Hz to 2400Hz, with step 1Hz)
All inputs/outputs can be configured to any logical function or protection.

Output state check


Output state check function evaluates in real time the state of binary outputs and adjusted (required) state. In
case of failure (different state of required state and real state) history record and alarm are issued (type of the
alarm is set by “Protection upon module failure” - (No protection / Warning / Shutdown)).
This function is designed for short-circuit or other failure, which causes change of set state of binary output.

CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.

Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.

Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins

InteliNeo 6000 1.5.0 Global Guide 1370


4. Connect the unit with PC via RS232-null modem cable and AT-Link conv

5. Connect power supply of the module (status LED lights continuously)


6. Launch FlashPgr.exe PC software (version 4.2 or higher)
7. In FlashPrg program choose card Inteli IO8/8 and load FW for the module
8. Set the proper COM port (connected with the unit) and press Start button
9. Wait till process is done (If the process doesn’t start – after 60 second the “Timeout” will be evaluated. In
this case please check:
You have proper connection with the unit
COM port selection is correct
Module has power supply, (no CAN bus connection, status LED lights continuously)
10. After successful programming disconnect AT-Link conv , remove TEST jumper and disconnect power
supply
11. Connect power supply again (status LED should blinking)
12. Module FW is upgraded

LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set. When this LED is shining, then module is configured as 8 binary inputs and 8 binary outputs. When this
LED is dark, then the module is configured as 16 binary inputs.
LED at power connector - status LED

InteliNeo 6000 1.5.0 Global Guide 1371


LED status Description
Dark Fw in module does not work correctly.
Flashing Module does not communicate with controller (in case non-zero CAN address).
Power supply is in the range and the communication between Inteli IO8/8 and controller
works properly.
Lights
Or power supply is in range and zero CAN address is set. (in case zero CAN address
module doesn’t communicate with the controller).

Wiring
The following diagrams show the correct connection of inputs and outputs.
Binary inputs - pull up

There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the GND (-) - dashed line).
On lower picture is case of wiring between BIN2 and GND (-). Both ways are correct.
Binary inputs - pull down

There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the Ucc (+) - dashed line).
On lower picture is case of wiring between BIN2 and Ucc (+). Both ways are correct.

InteliNeo 6000 1.5.0 Global Guide 1372


Binary outputs - high side

When high side setting of outputs is chosen - binary output must be connected to the minus potential directly
Terminal VHS (voltage High side) has to be connected to positive potential directly. Maximal current of each
binary output is 500 mA. Size of fuse depends on load.
Binary outputs - low side

When low side setting of outputs is chosen - binary output must be connected to the plus potential of power
supply directly. Minus potential is connected internally - dashed line.
Analog outputs

Note: Limit of analog ground (AGND) is 100mA.

IMPORTANT: Terminator for analog output has special analog ground (AGND), which must not be
connected to the GND.

Technical data

General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C

InteliNeo 6000 1.5.0 Global Guide 1373


Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 110x110x46 mm (4,3”x4,3”x1,8”)
Weight 240 grams

Analog outputs
Number of channels 2
Range 0-10 V
Voltage Accuracy: ± 20 mV + ±0,5 % of actual value
Imax 5 mA
Range: 0-20 mA
Current Accuracy: ± 100 µA + ±0,5 % of actual value
Rmax 500 Ω
Level 5 V
PWM Frequency - adjustable 200÷2400 Hz
Imax 20 mA

Binary inputs
Number of channels 8 for Inteli IO8/8, 16 for Inteli IO16/0
Input resistance 4400 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact
6 to 36 V DC
indication

Binary outputs
Number of channels 8 for Inteli IO8/8, 0 for Inteli IO16/0
Max current 500 mA
Max switching voltage 36 V DC

6 back to Extension modules

IGL-RA15
Remote annunciator (IGL-RA15) is designed as an extension signaling unit. The module is connected to
controller by CAN1A (page 19) bus. It is possible to connect up to 4 IGL-RA15 external units to one
controller.
The unit is equipped with a fully configurable tri-color (red, orange, green) LED for intuitive operation
together with high functionality.

InteliNeo 6000 1.5.0 Global Guide 1374


Image 7.102 IGL-RA15

Image 7.103 IGL-RA15 dimensions

Terminals

Horn Horn
CAN CAN1A (page 19) line
Power Power supply

CAN address

Address Jumper A Jumper B


1 OPEN OPEN
5+6 CLOSED OPEN
Customer defined CLOSED CLOSED

SW changing of CAN1A (page 19) address is enabled only when both jumpers are closed. Any one of these
addresses (1+2 or 3+4 or 5+6 or 7+8) can be set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow

InteliNeo 6000 1.5.0 Global Guide 1375


Press Lamp test sixteen times
Set the address up by pressing Horn reset.
The number of red luminous LEDs means the CAN1A (page 19) addresses (two for addresses 1+2,
four for addresses 3+4, six for addresses 5+6 and eight for addresses 7+8)
Press Lamp test

LED indication
Each LED color is adjusted independently of controller output settings. If controller output 1 is set as
“Common Shutdown” it doesn’t mean red LED1 color for iGL-RA15. The LEDs color can by adjust by
following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
Press Horn reset to change the LED1 color (green, yellow, red)
Press Lamp test to switch to the next LED color adjusting
Continue to adjust all LEDs color
After LED15 color adjusting press three times Lamp test

Note: If there is no operator action during address setting, color adjusting or timeout setting, the unit returns
to normal operation without changes saving.

Status LED
The signals LEDs are handled like binary outputs. It means all what can be configured to binary outputs can
be also configured to the LEDs of IGL-RA15.

LED status Description


Lights Configured logical output is active on the controller
Dark green LED Configured logical output is not active on the controller
Configured logical output is not active on the controller and horn reset was
Dark yellow or red LED
pressed.
Configured logical output is not active on the controller and horn reset was still
Yellow or red LED blinks
not pressed.

Power LED

LED status Description


Blinking green The unit is OK and the communication to the master controller is OK.
Blinking red The unit is OK, but the communication to the master controller is not running.
Blinking yellow EEPROM check not passed OK after power on
Yellow Horn timeout or controller address adjustment

Horn setting
The horn output is activated if any of red or yellow LED is on. Output is on until pressing Horn reset or horn
timeout counts down. The timeout can by set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
Press Lamp test fifteen times

InteliNeo 6000 1.5.0 Global Guide 1376


Set the horn timeout by pressing Horn reset.
The number of green luminous LEDs means timeout in 10 s (none for disabling horn output, 1 for 10s
timeout, 2 for 10s timeout, 15 for disabling horn timeout).
Press Lamp test two times

Note: If there is no operator action during address setting, color adjusting or timeout setting, the unit returns
to normal operation without changes saving.

The horn is activated if:


Some of red or yellow LED lights up or
At the end of the extended lamp test. See chapter Lamp and horn test (page 1377)
The horn can be silenced:
By pressing horn reset button or
It silences automatically after adjusted time

Lamp and horn test


Pressing and holding lamp test button for less than 2 s execute the basic lamp test. All LEDs light up with the
configured colour. If the button is hold longer than 2 s, an extended test is started. Every LED is tested step-
by-step in green colour and then in red colour. The horn is activated at the end of the test. After that the unit
returns to normal operation. The horn can be silenced with horn reset.

Wiring

* use terminator resistor only when IGL-RA 15 is the last unit on the CAN1A bus.
Note: The shielding of the CAN bus cable has to be grounded at one point only!

Note: See the section Technical data (page 1378) for recommended CAN bus cable type

InteliNeo 6000 1.5.0 Global Guide 1377


Technical data

General data
Power supply 8 to 36 V DC
0.35-0.1A (+1Amax horn output) depends on supply
Current consumption
voltage
Protection IP65
Interface to controller CAN1A (page 19)
Humidity 85%
Storage temperature - 30 °C to + 80 °C
Operating temperature - 20 °C to + 70 °C
Dimensions (WxHxD) 180x120x55 mm
Weight 950 g

Horn output
Maximum current 1.0 A
Maximum switching voltage 36 V DC

CAN bus interface


Galvanic separated
Maximal CAN bus length 200 m
Speed 250 kbps
Nominal impedance 120 Ω
Cable type twisted pair (shielded)
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus
length
Nominal Velocity of Propagation min. 75 % (max. 4,4 ns/m)
2
Wire crosscut min.0,25 mm
Maximal attenuation (at 1 MHz) 2 dB/100m
Recommended Industrial Automation & Process Control Cables
3082A DeviceBus for Allen-Bradley DeviceNet
3083A DeviceBus for Allen-Bradley DeviceNet
3086A DeviceBus for Honeywell SDS
BELDEN (www.belden.com) 3087A DeviceBus for Honeywell SDS
3084A DeviceBus for Allen-Bradley DeviceNet
3085A DeviceBus for Allen-Bradley DeviceNet
3105A Paired EIA Industrial RS485 cable
Unitronic BUS DeviceNet Trunk Cable
Unitronic BUS DeviceNet Drop Cable
LAPP CABLE (www.lappcable.com)
Unitronic BUS CAN
Unitronic-FD BUS P CAN UL/CSA

InteliNeo 6000 1.5.0 Global Guide 1378


IMPORTANT: This module is not compatible with different than 250 kbps communication speed. If
the ECU module with 125 kbps communication speed is connected the whole system will
automatically switch to the 125 kbps, and IGL-RA15 module will stop communicating.

6 back to Extension modules

IGS-PTM
IGS-PTM module is extension module equipped with binary inputs, binary outputs, analog inputs and analog
output. The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to 4 IGS-
PTM external units to one controller.

Image 7.104 IGS-PTM

Image 7.105 IGS-PTM dimensions

InteliNeo 6000 1.5.0 Global Guide 1379


Terminals

Binary inputs 8 binary inputs


Analog inputs 4 analog inputs
Analog outputs 1 analog output
Binary outputs 8 binary outputs
CAN CAN1A (page 19) line
RS232-TTL Interface for programming
Power Power supply

Analog inputs
Analog inputs can be configured for:
Resistance measurement
Current measurement
Voltage measurement
The type of analog inputs is configured via jumpers RUI located on lower PCB.

RUI Analog input configuration


1-2 Resistance measuring
2-3 Current measuring
no jumper Voltage measuring

Supported sensors

Sensors
PT100 [°C] (fix) User curves
NI100 [°C] (fix) 0-100 mV
PT100 [°F] (fix) 0-2400 ohm
NI100 [°F] (fix) ±20 mA

InteliNeo 6000 1.5.0 Global Guide 1380


CAN address
Controller type selection
The type of controller to be used with IGS-PTM must be selected via jumper labeled IGS accessible at the
lower PCB.

IGS jumper Controller type


OPEN IL-NT, IC-NT
CLOSE IG-NT, IS-NT, InteliLite

Address configuration
If InteliLite controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labeled ADR1 and ADR2.

BIN BOUT AIN


ADR1 ADR2 ADR offset
module module module
Open Open 0 (default) 1 1 1
Close Open 1 2 2 2
Open Close 2 3 3 3
Close Close 3 4 4 4

Programing firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper BOOT. RESET jumper
is used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.

LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set.
LED at power connector - status LED

LED status Description


Dark No required power connected.
Quick flashing Program check failure.
One flash and pause Compensation fail.
Three flashes and
Compensation successful.
pause
Flashes There is no communication between IGS-PTM and the controller.
Power supply is in the range and communication between IGS-PTM and
Lights
controller properly works.

InteliNeo 6000 1.5.0 Global Guide 1381


Wiring
Binary inputs

Binary outputs

Resistance sensor

Note: Range: 0- 2400 Ω

IMPORTANT: Physical analog input range is 0-250 Ω. In sensor configuration in PC tool it is


necessary to chose 0-2400 Ω sensor HW type to ensure proper function of analog input.

Voltage sensor

Note: Range 0-100 mV

InteliNeo 6000 1.5.0 Global Guide 1382


Current sensor - passive

Note: Range: ± 0-20 mA

IMPORTANT: Physical analog input range is 0-20mA. In sensor configuration in PC tool it is


necessary to chose +- 20mA active sensor HW type to ensure proper function of analog input.

Analog outputs

Note: Range: 0 to 20 mA ± 0,33 mA

Technical data

General data
Power supply 8 to 36 V DC
Current consumption 100 mA at 24V ÷ 500 mA
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 95×96×43 mm (3.7’×3.8’×1.7’)

Analog inputs
Number of channels 4
Range 0-100 mV
Voltage
Accuracy: 1,5 % ± 1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0,5 ohm out of measured value
Range: 0- 250 Ω
Resistive
Accuracy: 1 % ± 2 ohm out of measured value

InteliNeo 6000 1.5.0 Global Guide 1383


Analog outputs
Number of channels 1
Range: 0 to 20 mA ± 0,33 mA
Current
Resolution 10 bit

Binary inputs
Number of channels 8
Input resistance 4700 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact
8 to 36 V DC
indication

Binary outputs
Number of channels 8
Max current 500 mA
Max switching voltage 36 V DC
Number of channels 8
Range 0-100 mV
Voltage
Accuracy: 1,5 % ± 1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0,5 ohm out of measured value
Range: 0- 250 Ω
Resistive
Accuracy: 1 % ± 2 ohm out of measured value

6 back to Extension modules

Inteli AIO9/1
Inteli AIO9/1 module is an extension module equipped with analog inputs and outputs – designed for DC
measurement. The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to
5 Inteli AIO9/1 external units to one controller.
The detection of communication speed is indicated by rapid flashing of status LED. Once the speed is
detected the module remains set for this speed even when the communication is lost. Renewal of
communication speed detection is done by resetting of the module.

InteliNeo 6000 1.5.0 Global Guide 1384


Image 7.106 Inteli AIO9/1

Image 7.107 Inteli AIO9/1 dimensions

InteliNeo 6000 1.5.0 Global Guide 1385


Terminals

ANALOG INPUT 9 channels


ANALOG OUTPUTS 1 channel
CAN CAN1 line
POWER Power supply
CAN LED Tx, Rx Indication transmitted or received data
Status LED LED indication of correct function
CAN terminator Terminating CAN resistor (active in position "ON")
TEST jumper Upgrade of SW
AT-LINK Connector for AT-LINK (Upgrade of SW)

Analog inputs
4 channels AIN1 – AIN4 can be configured as:
Sensor ±65V (determined for measurement of battery voltage)
4 channels AIN5 – AIN8 can be configured as:
Thermocouples – type J,K or L (in °C or °F)
Sensor ±75mV DC – (for connecting current shunts)
1 channel AIN9 can be configured as:
RTD (Pt1000, Ni1000)
Common resistance 0-2400Ω

InteliNeo 6000 1.5.0 Global Guide 1386


Analog outputs
1 channel AOUT1. Type of output:
0-10V DC
0-20mA
PWM (5 V, freq 2.4 Hz ÷2.4 kHz)
Analog output has 4-pins connector – GND and one pin for each type of output.
All analog inputs can be configured to any logical function or protection.

Supported sensors

Sensors
User curves ±65 V DC (fix linear) Thermocpl (nc) K [°C] (fix)
PT1000 [°C] (fix) ±75 mV (fix linear) Thermocpl (nc) L [°C] (fix)
NI1000 [°C] (fix) Thermocpl J [°C] (fix) Thermocpl (nc) J [°F] (fix)
PT1000 [°F] (fix) Thermocpl K [°C] (fix) Thermocpl (nc) K [°F] (fix)
NI1000 [°F] (fix) Thermocpl L [°C] (fix) Thermocpl (nc) L [°F] (fix)
0-2400 Ω (fix linear) Thermocpl (nc) J [°C] (fix)

Address and DIP switch setting


Address configuration
DIP switch determinates CAN address for analog inputs and outputs.
Programming Firmware
Firmware upgrade is available via AT-link (TTL). For programming it is necessary to close jumper TEST and
switch OFF and ON the power supply.
For programming use FlashProg PC tool version 4.4 or higher.

LED indication

LED status Description


Dark Fw in module does not work correctly.
Flashing Module does not communicate with controller (in case non-zero CAN address)
Fast flashing Detection of CAN communication speed
Power supply is in the range and the communication between Inteli AIN8TC and
controller works properly.
Lights
Or power supply is in range and zero CAN address is set. (in case zero CAN
address module doesn’t communicate with the controller)

InteliNeo 6000 1.5.0 Global Guide 1387


Wiring
The following diagrams show the correct connection of sensors.

Measuring resistance – AIN9


2 – wire measurement

Ranges: Pt1000, Ni1000, 0 – 2400 Ω.


Analog input 9 is determined for measuring resistance only.

Technical data

General data
Dimension (W × H × D) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 248 grams
CAN1 – galvanic separated from power
Interface to controller
supply and measurement,

Analog inputs (not electric separated)


9 channels
0-65 V ± 0.25 % of actual value + ± 120 mV
Measurement is not galvanic separated from
Range
AIN1-AIN4 – Voltage inputs power supply, but IN- is not interconnected with
GND – there is floating measurement.
Accuracy of ± 0,1 % of actual value + ± 100 µV (± 3 °C)

InteliNeo 6000 1.5.0 Global Guide 1388


measurement
Range ± 75 mV (nominal) (measurement up to ±80 mV)
AIN5-AIN8 – Voltage inputs Accuracy of ± 0.1 % of actual value + ± 75 µV
measurement Galvanic separated from power supply
Range 0- 2400 Ω
± 0.5 % of actual value + ± 4 Ω Pt1000, Ni1000 ±
AIN9 resistance input Accuracy of
2,5 °C
measurement
It is not galvanic separated from power supply.

Analog output
I 0-20mA /500Rmax. ± 1 % of actual value + ± 200 uA
U 0-10V ± 0.5 % of actual value + ± 50 mV
PWM – 5 V, 200 Hz-2.4kHz 15 mA max.
Galvanic separated from power supply

Galvanic
CAN bus is galvanic separated from the measurement and power supply
separation

Power supply 8 to 36 V DC
Protection IP20
Current consumption 150 mA at 24 V ÷ 400 mA at 8 V
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 80 °C

The product is fully supported in firmware IGS-NT 3.1.1 or higher.


For information about support of this module in IGS-NT fw branches and ID-DCU – please read New Feature
Lists.
6 back to Extension modules

Inteli AIN8TC
Inteli AIN8TC module is extension module equipped with 8 analog inputs dedicated for thermocouple sensors
only. The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to 10 Inteli
AIO9/1 external units to one controller.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.

InteliNeo 6000 1.5.0 Global Guide 1389


Image 7.108 Inteli AIN8TC

Image 7.109 Inteli AIN8TC dimensions

InteliNeo 6000 1.5.0 Global Guide 1390


Terminals

Analog input 8 analog Inputs


CAN CAN1A (page 19) line
Power Power supply
CAN LED Tx,
Indication transmitted or received data
Rx
Status LED LED indication of correct function
CAN terminator Terminating CAN resistor (active in position “ON” - switch both switches)

Analog inputs
8 channels
Can be configured as thermocouple sensors only
All inputs can be configured to any logical function or protection

Supported sensors

Sensors
Thermocpl J [°C] (fix) Thermocpl (nc) J [°C] (fix)
Thermocpl K [°C] (fix) Thermocpl (nc) K [°C] (fix)
Thermocpl L [°C] (fix) Thermocpl (nc) L [°C] (fix)
Thermocpl J [°F] (fix) Thermocpl (nc) J [°F] (fix)
Thermocpl K [°F] (fix) Thermocpl (nc) K [°F] (fix)
Thermocpl L [°F] (fix) Thermocpl (nc) L [°F] (fix)

InteliNeo 6000 1.5.0 Global Guide 1391


Note: “nc” means“ not cold junction compensation (by external sensor).In this case is used internal
temperature sensor on the PCB

CAN address
DIP switch determinates CAN address for analog inputs.

Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.

Programming firmware
Firmware is upgraded via AT-link (TTL). For programming it is necessary to close jumper TEST.
For programming FlashProg PC tool version 4.2 or higher must be used.

LED indication

LED status Description


Dark Fw in module does not work correctly.
Flashing Module does not communicate with controller (in case non-zero CAN address)
Fast flashing Detection of CAN communication speed
Power supply is in the range and the communication between Inteli AIN8TC and
controller works properly.
Lights
Or power supply is in range and zero CAN address is set. (in case zero CAN
address module doesn’t communicate with the controller)

Wiring
The following diagrams show the correct connection of sensors.
Thermocouple

InteliNeo 6000 1.5.0 Global Guide 1392


Terminator

Technical data

General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1A (page 19)
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 237.5 grams

Analog inputs
Number of channels 8, no galvanic separated
Range: ± 100 mV
Voltage Accuracy: ± 0.1 % of actual value + ± 100 µV
(± 3 °C)

6 back to Extension modules

I-AOUT8
I-AOUT8 is an extension unit with 8 analog outputs. Each analog output can be switched to
0 to 20 mA DC
0 to 10 V DC
PWM (Pulse With Modulation on 1,2 kHz)
The module is connected to controller by CAN1A (page 19) bus. It is possible to connect up to 4 I-AOUT8
external units to one controller. The corresponding module Address 1 to 4 (default 1) must be set on module
(by Adr.1 and Adr.2 jumpers) and in controller configuration. CAN1 terminating 120 ohm resistor jumper is
connected as default. AGND terminals are on the same potential.

InteliNeo 6000 1.5.0 Global Guide 1393


InteliNeo 6000 1.5.0 Global Guide 1394
Dimensions

Unit is 35 mm DIN rail mounted.

Connectors

POWER Power supply


CAN 1 CAN1 line
OUT1 - OUT8 Analog output
FLASH AT-link
J1 – J8 Output mode
A1, A2 CAN 1 address
CAN-R Terminating resistor

InteliNeo 6000 1.5.0 Global Guide 1395


BOOT Programming
RESET Programming / reset
Tx, Rx CAN 1data
ST Power/module state

Address and jumpers setting

CAN Address
The module CAN address is set by jumpers A1 and A2. Set module CAN address correspondingly to
configuration according table below.

CAN Address A1 A2
1 Open Open
2 Close Open
3 Open Close
4 Close Close

Table 7.2 Setting CAN address

Output mode
Follow the p – I – I – U symbols on the module sticker. There are two equivalent positions for current output.

AOUT Symbol Function

PWM
p
Pulse-Width-Modulation

l 0 to 20 mA DC

U 0 to 10 V DC

Table 7.3 Setting output mode

Programming firmware
Firmware upgrade is via AT-link (TTL). For programming it is necessary to close jumper BOOT. RESET
jumper is used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC
tool.

CAN1 termination
I-AOUT8 has own CAN terminating resistor (120 ohm). Close jumper CAN-R to connect terminating resistor
to CAN bus, open jumper CAN-R disconnecting terminating resistor.

InteliNeo 6000 1.5.0 Global Guide 1396


Wiring

PWM output
PWM output
1200 Hz

Current
Current output 0 to 20
output 0 to
mA DC
20 mA DC
Current
Current output 0 to 20
output 0 to
mA DC
20 mA DC
Voltage
Voltage output 0 to 10
output 0 to
V DC
10 V DC
Image 7.110 Possible output modes

Technical data

Dimension (W × H × D) 95 × 96 × 43 mm (3.7’ × 3.8’ × 1.7’)


Interface to controller CAN
Output 8 analog, no galvanic separation

Type of analog output


0 to 10V DC ± 1 % , max 5 mA DC
0 to 20 mA DC ± 1 % , max 500 Ω
PWM 1200 Hz, 5V DC level, max 10 mA DC

Power supply 8 to 36 V DC
Analog output refreshment 320 ms
Current consumption max 300 mA (100 mA at 24 V)
RS232 interface TTL, firmware upgrade via AT-link.
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2.5 W

6 back to Extension modules

IS-AIN8
IS-AIN8 is input extension module equipped with 8 analog inputs which can be configured to:
Resistor two wire input
Resistor three wire input
Current input

InteliNeo 6000 1.5.0 Global Guide 1397


Thermocouple input
Voltage input
All inputs can be configured to any logical function or protection. It is possible to connect up to 10 IS-AIN
external units to one controller. IS-AIN8 is connected to controller CAN1A (page 19) bus.
This module is compatible with MTU ECU-7 at communication speed 125 kbps when uploaded with firmware
1.2.0 and higher.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.

InteliNeo 6000 1.5.0 Global Guide 1398


Terminals

AIN1 – AIN8 8 analog inputs


CAN CAN1 line
POWER Power supply

InteliNeo 6000 1.5.0 Global Guide 1399


POWER State indication
Rx, Tx Data transmitted and received on CAN1 line
LDD CAN1 adress

Supported sensors

Sensors
PT100 [°C] (fix) PT100 [°F] (fix) +-1V 4-20mA passive 0-250 ohm
PT1000 [°C] (fix) PT1000 [°F] (fix) 0-2.4V 4-20mA active 0-2400 ohm
NI100 [°C] (fix) NI100 [°F] (fix) 0-5V 0-20mA passive 0-10k ohm
NI1000 [°C] (fix) NI1000 [°F] (fix) 0-10V +-20mA active

Note: It is also possible to use User Curves as sensor.

TC Sensors
Thermocpl J [°C] (fix) Thermocpl (nc) J [°C] (fix)
Thermocpl K [°C] (fix) Thermocpl (nc) K [°C] (fix)
Thermocpl L [°C] (fix) Thermocpl (nc) L [°C] (fix)
Thermocpl J [°F] (fix) Thermocpl (nc) J [°F] (fix)
Thermocpl K [°F] (fix) Thermocpl (nc) K [°F] (fix)
Thermocpl L [°F] (fix) Thermocpl (nc) L [°F] (fix)

Note: “nc” means“ not cold junction compensation (by external sensor).In this case is used internal
temperature sensor on the PCB

CAN Address
CAN 1 address is set by following procedure:
1. Press Address button during IS-AIN8 power supply on to switch to addressing mode.
2. Then repeatedly press or keep pressed address button to adjust required address according to controller
configuration.
3. After setting requested address, release the buttons and wait until the digits blink – it indicates writing of
the change address to EEPROM memory.

CAN 1 Address
1. IS-AIN8 1
2. IS-AIN8 2
3. IS-AIN8 3
4. IS-AIN8 4
5. IS-AIN8 5
6. IS-AIN8 6
7. IS-AIN8 7

InteliNeo 6000 1.5.0 Global Guide 1400


8. IS-AIN8 8
9. IS-AIN8 9
10. IS-AIN8 0

Table 7.4 Table of recommended CAN1 address setting

SW version check
Let suppose IS-AIN8 of SW version 1.4. Shortly press address button. Following sequence appears on the
display: number “1”, one second pause, number “4”, two second pause, number “1”, one second pause,
number “4”, two second pause and finally IS-AIN8 actual address. Error message (e.g. SD BOUT2) appears
on Controller screen when Binary input or output Address x is configured but corresponding unit is not
recognized (no message is received from CAN bus). Check IS configuration and corresponding external IS-
AIN8, IS-BIN8/16 unit address setting.

LED indication

Power LED Address LDD


Lighting Blink Lighting Blink
Power supply and CAN CAN1 address is adjusted
Displaying current Displaying current
address are with no different in IS-AIN8 and in
CAN1 address SW version
problems controller

Table 7.5 LED / LDD status

Tx Rx
Lighting Blink Lighting Blink
Any data are
Any data are transmitted Data are transmitted on the CAN1 Data are received
received on the
on the CAN1 line line on the CAN1 line
CAN1 line

Table 7.6 Tx/Rx LED status

Wiring

InteliNeo 6000 1.5.0 Global Guide 1401


Note: CAN bus line has to be terminated by 120 Ω resistors on the both ends.
For longer distances is recommended to connect CAN COM terminals between all controllers and cable
shielding to the ground in one point!External units can be connected on the CAN bus line in any order, but
line arrangement (no tails no star) is necessary.
Recommended CAN bus data cables see in Chapter Technical data.
IG-MU and IG-IB units are connected to CONTROLLER CAN2 bus.

Select sensor characteristic from the list or define user sensor characteristic in PC configuration tool.

Resistor sensor input – two wire connection.


Range 0 to 2400 Ω.
Pt100, Pt1000, Ni100, Ni1000
D terminal is shielding

Resistor sensor input – three wire connection.


Range 0 to 2400 Ω.
Pt100, Pt1000, Ni100, Ni1000 – recomended.
D terminal is shielding

Passive current sensor (current source is in IS-AIN8)


Range 0 to +20 mA or 4 to + 0 mA
D terminal is shielding

Active current sensor (current source is in sensor)


Range –20mA to +20 mA or 4 to +20 mA

D terminal is shielding

Thermocouple J, K, L D terminal is shielding


From IS-AIN8 hardware version 5.1 can be B terminal
grounded to frame

InteliNeo 6000 1.5.0 Global Guide 1402


Voltage input
Range 0 to + 2500 mV.
Voltage range is 0 to ±1000 mV.
D terminal is shielding

For 10 V input voltage range connects external


resistors R1, R2 and select sensor characteristic 10 V
R1=10 kΩ, R2=2.7 kΩ.
D terminal is shielding

Note: If the thermocouples are connected to IS-AIN8, appropriate jumpers must be removed (see rear
sticker). (jumpers are placed under the cover)

Cold Junction Compensation (CJC)


Cold junction compensation is also called reference junction compensation. When measuring temperature
using thermocouples, the reference terminal may not be held at 0°C, but at the surrounding temperature of
T1°C instead. Without any compensation, the thermocouple output will be changed (reduced) by T1°C. This
is compensated by adding potential difference to the IS-AIN8 corresponding to T1°C.

InteliNeo 6000 1.5.0 Global Guide 1403


2

Example 1 shows the correct temperature measurement. The 3rd metal (the cable between IS-AIN8 and
thermocouple) is connected in cold bath which temperature is 0°C. This is very difficult to provide in real
application.
Example 2 shows the correct temperature measurement. The 3rd metal (the cable between IS-AIN8 and
thermocouple) is connected in ambient environment which temperature is not 0°C, but T1°C. Resultant
temperature is correct, because is compensated by internal IS-AIN8 temperature sensor. The
temperature of IS-AIN8 and junction is the same T-T1+T1 (reduced and compensated by T1).
Example 3 shows the incorrect temperature measurement. The 3rd metal (the cable between IS-AIN8
and thermocouple) is connected in ambient environment which temperature is not 0°C, but T1°C.
Resultant temperature is T-T1 (reduced by T1). Internal IS-AIN8 compensation should not by used
because measures T2 temperature, not T1!
Example 4 shows the correct temperature measurement. The 3rd metal (the cable between IS-AIN8 and
thermocouple) is connected in ambient environment which temperature is not 0°C, but T1°C. Resultant
temperature is correct, because is compensated by external temperature sensor, T+T1 (reduced and
compensated by T1).

InteliNeo 6000 1.5.0 Global Guide 1404


Cold Junction Compensation (CJC) settings
Example 1 is not a practical in regard of ice bath. In this case should any of not compensated (nc) sensors
for analog input be selected base on used thermocouple.

Example 2 is a standard wiring between thermocouple sensor and IS-AIN8. IS-AIN8 is placed in the
same ambient temperature as thermocouple terminal; it means IS-AIN8’s internal temperature sensor
measures the same temperature as is on thermocouple terminal. In this case, could junction
compensation is done by IS-AIN8 itself. Any of standard (compensated) sensors should be selected.

Example 3 is a standard wiring between thermocouple sensor and IS-AIN8. Regardless selected type of
sensor the resultant temperature will be incorrect
Not compensated sensor – temperature T1 is not calculated
Compensated sensor – IS-AIN8 measures different T2 temperature, not T1
Example 4 External temperature T1sensor is included. Resultant temperature is correct if
Any of not compensated sensors (nc) is selected
External sensor has a function Cold Temp 1

InteliNeo 6000 1.5.0 Global Guide 1405


Note: LAI (logical analog input) Cold Temp 1 compensates every of 8 thermocouples inputs of IS-AIN8 on
address 1IS-AIN8 on address 2 – 10 is not compensated by this LAI Cold Temp1.
Any of non thermocouple configured input is not compensated anyway
Any of non thermocouple input with sensor adjusted as compensated is not compensated by external
compensation (IS-AIN8 compensates it itself)
IS-AIN8 on address 2 – 10 is not compensated by this LAI Cold Temp1.
LAI Cold Temp 2 compensates every of 8 thermocouples inputs of IS-AIN8 on address 2, etc.
Up to 32 (Cold Temp 1-4 times 8 analog input of IS-AIN8) may by compensated by external sensor.
Even only one external sensor may be configured for more than one LAI Cold Temp.

Technical data

Dimension (W × H × D) 146 × 160 × 46 mm (5.79’ × 6.6’ × 1.83’)


Interface to Controler CAN1
Analog inputs 8, galvanic separated from power supply, 16 bit *
Power supply 8 to 36 V DC
Current consumption 250 mA at 24 V
Protection front panel IP20
Humidity 95% without condensation
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2W

* each analog input can be software configured to:


Measuring range Accuracy
From To
Resistance 0Ω 2400 Ω ± 0.5 %
0Ω 250 Ω ± 1.0 %
Current Passive 0/4 mA 20 mA ± 0.5 %
Active 4 mA 20 mA ± 0.5 %
Active 0 mA ± 20 mA ± 0.5 %
Voltage Thermocouples J, K, L type ± 0.2 %
0 mV 100 mV ± 0.2 %
- 1000 mV + 1000 mV ± 0.5 %
0 mA 2500 mV ± 0.5 %

Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
EN 50081-1:94, EN 50081-2:96
Electromagnetic Compatibility
EN 50082-1:99, EN 50082-2:97

6 back to Extension modules

InteliNeo 6000 1.5.0 Global Guide 1406


IS-AIN8TC
IS-AIN8 is input extension module equipped with 8 analog inputs dedicated for thermocouple sensors only.
All inputs can be configured to any logical function or protection. It is possible to connect up to 10 IS-AIN8TC
external units to one controller. IS-AIN8TC is connected to controller CAN1A (page 19) bus.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication
speed detection is done by reset of the module.

InteliNeo 6000 1.5.0 Global Guide 1407


Terminals

AIN1 – AIN8 8 analog inputs


CAN CAN1 line
POWER Power supply
POWER State indication
Rx, Tx Data transmitted and received on CAN1 line
LDD CAN1 address

Supported sensors

Sensors
Thermocpl J [°C] (fix) Thermocpl (nc) J [°C] (fix)
Thermocpl K [°C] (fix) Thermocpl (nc) K [°C] (fix)
Thermocpl L [°C] (fix) Thermocpl (nc) L [°C] (fix)
Thermocpl J [°F] (fix) Thermocpl (nc) J [°F] (fix)
Thermocpl K [°F] (fix) Thermocpl (nc) K [°F] (fix)
Thermocpl L [°F] (fix) Thermocpl (nc) L [°F] (fix)

Note: “nc” means“ not cold junction compensation (by external sensor).In this case is used internal
temperature sensor on the PCB

CAN Address
CAN1 address is set by following procedure:

InteliNeo 6000 1.5.0 Global Guide 1408


1. Press Address button during IS-AIN8TC power supply on to switch to addressing mode.
2. Then repeatedly press or keep pressed address button to adjust required address according to controller
configuration.
3. After setting requested address, release the buttons and wait until the digits blink – it indicates writing of
the change address to EEPROM memory.

CAN11 Address
1. IS-AIN8TC 1
2. IS-AIN8TC 2
3. IS-AIN8TC 3
4. IS-AIN8TC 4
5. IS-AIN8TC 5
6. IS-AIN8TC 6
7. IS-AIN8TC 7
8. IS-AIN8TC 8
9. IS-AIN8TC 9
10. IS-AIN8TC 0
Table 7.7 Table of recommended CAN1 address setting

SW version check
Shortly press address button. Following sequence appears on the display: number “1”, one second pause,
number “4”, two second pause, number “1”, one second pause, number “4”, two second pause and finally IS-
AIN8TC actual address.
Error message (e.g. SD BOUT2) appears on Controller screen when Binary input or output Address x is
configured but corresponding unit is not recognized (no message is received from CAN bus). Check IS
configuration and corresponding external IS-AIN8TC, IS-BIN8/16 unit address setting.

LED indication

Power LED Address LDD


Lighting Blink Lighting Blink
Power supply and CAN CAN1 address is
Displaying current Displaying current SW
address are with no adjusted different in IS-
CAN1 address version
problems AIN8TC and in controller
Table 7.8 LED/LDD status

Tx Rx
Dark Blink Dark Blink
Any data are transmitted Data are transmitted on Any data are received Data are received on
on the CAN1 line the CAN1 line on the CAN1 line the CAN1 line
Table 7.9 Tx/Rx LED status

InteliNeo 6000 1.5.0 Global Guide 1409


Wiring

Note: CAN bus line has to be terminated by 120 ohm resistors on the both ends.
For longer distances is recommended to connect CAN COM terminals between all controllers and cable
shielding to the ground in one point!
External units can be connected on the CAN bus line in any order, but line arrangement (no tails no star) is
necessary.
Recommended CAN bus data cables see in Chapter Technical data.
IG-MU and IG-IB units are connected to CONTROLLER CAN2 bus.

Select sensor characteristic from the list or define user sensor characteristic in PC configuration tool.

Thermocouple J, K, L, D terminal is shielding

Cold Junction Compensation (CJC) settings


Please have a look at Cold Junction Compensation (CJC) (page 1403) IS-AIN8 chapter.

Technical data

Dimension (W × H × D) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)


Weight 237.5 grams
Interface to controller CAN1

Analog inputs (not electric separated) 8, no galvanic separated


Measuring ±100 mV
Accuracy ± 0.1 % of actual value + ± 100 µV (± 3 °C)

InteliNeo 6000 1.5.0 Global Guide 1410


Internal sensor for measuring cold junction - ±1 °C in temperature range -20 °C ÷ +70
Accuracy °C
CANbus is galvanic separated from the
measurement and power supply.
All analog inputs are galvanic separated
Galvanic separation
from power supply.
Analog inputs are not galvanic separated
between channels

Power supply 8 to 36 V DC
Protection IP20
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2W

6 back to Extension modules

IS-BIN16/8
IS-BIN16/8 is an extension module with 16 binary inputs (galvanic separated) and 8 binary output (galvanic
separated), 2 pulse inputs (frequency measurement or pulse counting). All I/O can be configured to any
logical function or protection. It is possible to connect up to 7 IS-BIN16/8 external units to one controller.
External modules IS-BIN16/8 is connected to controller CAN1A (page 19) bus. To operate external modules:
Connect all external modules to CAN1 bus line
On each module adjust I/O CAN1 address in the range of 1 to 7 for IS-BIN16/8 output, 1,3,5,7,9,11,13 for
IS-BIN18/8 inputs
In case of use generic module in configuration you can set CAN address from 1 – 12
In case of set 0 CAN address - inputs/ outputs are deactivated
Input output address is displayed on the front panel LCD’s
Use PC configuration tool to configure controller according external modules setting
IS-BIN16/8 module has two separate CAN1 addresses for binary inputs Group 1, Group 2 and binary output
Group (total three addresses). The CAN1 address for BI Group 1 and for BO Group 2 can be adjusted on the
IS-BIN16/8. The address for BI Group 2 is set automatically to the address following BI Group 1.
Note: CAN address 0 disables corresponding CAN message (Group data are not send).

InteliNeo 6000 1.5.0 Global Guide 1411


InteliNeo 6000 1.5.0 Global Guide 1412
Terminals

CAN CAN1 line


BINARY INPUTS 16 binary inputs
BINARY OUTPUT 8 binary output
RPM1, RPM2 2 frequency inputs
POWER Power supply
INPUTS LDD CAN address
OUTPUT LDD CAN address

CAN Address
CAN 1 address is setting by following procedure:
Press Address buttons (for INPUTS address and OUTPUT address) during IS-BIN8 power supply on to
switch to addressing mode.
Then repeatedly press or keep pressed address button to adjust required address according to
CONTROLLER configuration.
After setting requested address, release the buttons and wait until the digits blink – it indicates write the
changed address to EEPROM memory.

CAN 1 Address
Inputs Output
1. IS-BIN16/8 1 1
2. IS-BIN16/8 3 2
3. IS-BIN16/8 5 3

InteliNeo 6000 1.5.0 Global Guide 1413


4. IS-BIN16/8 7 4
5. IS-BIN16/8 9 5
6. IS-BIN16/8 11 6
7. IS-BIN16/8 16 7

Table 7.10 Table of recommended CAN1 address setting

SW version check
Let suppose IS-AIN8 of SW version 1.4. Shortly press address button. Following sequence appears on the
display: number “1”, one second pause, number “4”, two second pause, number “1”, one second pause,
number “4”, two second pause and finally IS-AIN8 actual address.
Error message (e.g. SD BOUT2) appears on Controller screen when Binary input or output Address x is
configured but corresponding unit is not recognized (no message is received from CAN bus). Check IS
configuration and corresponding external IS-AIN, IS-BIN unit address setting.

LED indication

Tx Rx
Dark Blink Light Dark Blink Light
Any data are Data are Any data are Data are
transmitted on the transmitted on the received on the received on the
CAN1 line CAN1 line CAN1 line CAN1 line

Table 7.11 Tx / Rx LED status

Wiring

Image 7.111 CAN bus line has to be terminated by 120 ohm resistors on the both ends.

Note: CAN bus line has to be terminated by 120 ohm resistors on the both ends.
For longer distances is recommended to connect CAN COM terminals between all controllers and cable
shielding to the ground in one point!
Recommended CAN bus data cables see in Chapter Technical data.
External units can be connected on the CAN bus line in any order, but line arrangement (no tails no star) is
necessary-
Recommended CAN bus data cables see in Chapter Technical data.

InteliNeo 6000 1.5.0 Global Guide 1414


Binary inputs
There are two groups of eight Binary inputs BI1 to BI8 and BI9 to BI16. Each group has a separate Common
terminal COM1 and COM2. The Common terminal can be connected to positive or negative pole – see
following drawing. Binary inputs are galvanically separated from IS-BIN16/8 power supply.
Note: See the Theory of binary inputs and outputs (page 1357) (Pull Up,Pull Down, High side switch,
Low side switch).

Binary inputs Common terminal is connected to Binary inputs common terminal is connected to
positive supply terminal, Binary inputs contacts are negative supply terminal, Binary inputs contacts are
closed to negative supply terminals. closed to positive supply terminals.

Input voltage range for opened contact is from 8 VDC to Power supply VDC. Input voltage range for closed
contact is from 0 to 2 VDC. Voltage level is defined between Binary input and Binary input COM terminal and
does not depend on “positive” or “negative” connection.
IMPORTANT: Impulse inputs are not supported by the controller.

Binary output
The Common terminal can be connected to positive or negative pole (HW3.0 only) – see following drawing.
Binary outputs are galvanic separated from IS-BIN16/8 power supply (have a look at technical data). The
maximum load values are 0.5 A / 36V for one output.

Binary output common terminal is connected to Binary output common terminal is connected to
negative supply terminal, Binary output contacts are positive supply terminal, Binary output contacts are
closed to positive supply terminals. closed to negative supply terminals.

InteliNeo 6000 1.5.0 Global Guide 1415


Power supply fusing
A (2) respectively (1) amp fuse should be connected in-line with the power to the controller and modules,
these items should never bee connected directly to the starting battery.
Take care for proper controller, extension units and relays power supply fusing. Fuse value and type depends
on number of connected devices and wire length.

Controller or unit Fuse


Controller T1A or T2A
IS-AIN8 T2A
IS-BIN16/8 T1A

Table 7.12 Recommended fuse (not fast) types

For more extension units use separate fusing according to the table above.
Controller power supply should never be connected to starter terminals.

Technical data

Dimension (W × H × D) 146 × 160 × 46 mm (5.79’ × 6.6’ × 1.83’)


Interface to controller CAN1

Binary inputs (galvanic separated)


Voltage level is defined between binary input and binary input COM terminal
Number of inputs 8+8
Input resistance 3000 Ω

InteliNeo 6000 1.5.0 Global Guide 1416


Input voltage range 0-36 VDC
Input voltage level for open contact 8 to Power supply VDC
Input voltage level for close contact 0 to 2 VDC

Frequency inputs* (for IS-CU only)


RPM1
Type of sensor Magnetic pick-up
Minimum input voltage 2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage 50 Veff
Maximum measured frequency 8 kHz (min. input voltage 6Vpk-pk), frequency mode
RPM2
Type of sensor Contact or Active sensor
Minimal pulse width 10 ms, integration mode
Maximum measured frequency 60 Hz, integration mode

Relays outputs (galvanic separated) only HW 3.0 (non galvanic separated) HW 2.1
Number of output 8
Maximum current 0.5A DC
Maximum switching voltage 36 VDC

Power supply 8 to 36 V DC
Protection front panel IP20
Current consumption 250 mA** at 24 V
Humidity 95% without condensation
Storage temperature -40 °C to +80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2W

Standard conformity
Number of output 8
Low Voltage Directive EN 61010-1:95 +A1:97
EN 50081-1:94, EN 50081-2:96
Electromagnetic Compatibility
EN 50082-1:99, EN 50082-2:97

*RPM1, RPM2 are available in IS-CU only **During powering up current can be up to 1.5A
6 back to Extension modules

InteliNeo 6000 1.5.0 Global Guide 1417