PB 02245 Manual
PB 02245 Manual
PB 02245 Manual
System Manual
English
1 PureBallast 3.1 System
manual
The PureBallast 3.1 is available in several sizes, defined by the system’s max treatment rated
capacity (TRC). The TRC is included in the system name and the title of each system manual.
The basic document describing the system is the connection list, and the therein stated flow chart.
Those documents are included in the system manual, chapter 6, Installation description and
drawings.
The tables in this document lists the PureBallast systems with reference to the system manual
describing them and the connection list and flow chart defining them.
There are two versions of PureBallast. The USCG version use flow control to be compliant with
USCG legislation. The USCG HP (high performance) have double reactor capacity which allows
treatment at full capacity at all time.
Flowchart
Component Manufacturer Model (Size according to connection list)
legend
Filter:
Automatic ACB-xx-yy, 20 µm mesh (xx=935 – 9200, yy=
self-cleaning Filtrex DN200 - DN600)
filter
PT201-71
Pressure sensor Jumo MIDAS S07
& -72
UV reactor
UV reactor, 300 or,
UV reactor Wallenius Water UV reactor, 600 or,
UV reactor, 1000
Medium pressure UV lamp, 3 kW for UV reactor
UV lamp 170, 300 and 600
Wallenius Water
Medium pressure UV lamp, 6 kW for UV reactor
1000
Lamp sleeve Wallenius Water Synthetic Quartz 9000738 02
UV-TECHNIK, SUV 20.2 Y2 C 40° 1000 W/m² or,
QT201-50 UV sensor IL Metronic SUV 20.2 Y2 C 40° 3000 W/m² for UV reactor
Sensortechnik GmbH 1000
Temperature, Bimetal Temp. Switch 60.8301
TS201-60 JUMO
switch
Thermometer, Dtrans Temp. probe 90.2815
TT201-33 JUMO
resistance
Vibration limit
LS201-29 PEPPERL+FUCHS Vibracon LVL-A7
switch
- Ifm IN5225, Inductive pos. sensor
V201-19 & -Air Torque Spa AT range, Actuator
Valve
-20
-ARI Armaturen ARI –GESA, Lugged valve
Valves:
- Siemens SIPART PS2, Positioner
Flow control - Air Torque Spa AT range, Actuator
V201-8
valve
- ARI Armaturen ARI –GESA, Lugged valve
V201-3, Filter inlet, outlet, - Rotech ALB ACR3.., Pos. switch box
-9, -32 & by-pass, & Start - Air Torque Spa AT range, Actuator
V403-35 up cooling valve - ARI Armaturen ARI –GESA, Lugged valve
Filter backflush - Air Torque Spa AT range, Actuator
V309-1
valve - ARI Armaturen ARI –GESA, Lugged valve
- Rotech ALB ACR3.., Pos. switch box
- Air Torque Spa AT range, Actuator
V212-31 By-pass valve
- Rotork ILG-D series, Handwheel
- ARI Armaturen ARI –GESA, Lugged valve
Flow meter:
Endress+Hauser Promag 50W1F,
FIT201-1 Flow transmitter
or Siemens Sitrans F, Magflo MAG 5100W
System pressure Transmitter:
Flowchart
Component Manufacturer Model (Size according to connection list)
legend
Flowchart
Component Manufacturer Model
legend
Pressure
PT201-16 JUMO MIDAS S07
transmitter
Cleaning in Place (CIP) unit:
CIP cleaning
Alfa Laval 595087
module
CIP cleaning
Alfa Laval Alpacon Descalant Offshore
liquid
Lamp Drive Cabinet (LDC):
Lamp Drive
Alfa Laval LDC 3.1
Cabinet
Control Cabinet:
Control Cabinet Alfa Laval CC 3.1
System Description 2
Printed 2018
Alfa Laval reserves the right to make changes at any time without prior notice.
Any comments regarding possible errors and omissions or suggestions for improvement of this
publication would be gratefully appreciated.
Copies of this publication can be ordered from your local AlfaLaval company.
Published by: : Alfa Laval Tumba AB
SE-147 80 Tumba, Sweden
Telephone: +46 8 530 650 00
Telefax: +46 8 530 310 40
2 Safety information 7
2.1 General safety information 7
2.2 Specif c safety information 7
2.3 Personnel requirements 9
2.4 Warning signs used in the manual 9
3 Environmental issues 11
3.1 Unpacking 11
3.2 Other materials 11
3
1 Introduction
This chapter contains general safety and environmental information, personnel requirements and
explanations of symbols used for the PureBallast system.
Book No.9028195 02 5
1 Introduction
2 Safety information
This section contains safety information. This information must be read and understood before the
system is installed, operated and maintained.
• The PureBallast system is not Ex proofed and must not be installed in areas where an explosive
atmosphere may occur.
• Use the equipment only for the purpose and parameter range specified by Alfa Laval.
• Use only Alfa Laval genuine spare parts.
• Always read and follow the documentation that is included in shipment of components and
spare parts regarding handling, safety and disposal.
• Mobile cell phones must not be switched on within an area of 1 meter from an open cabinet door.
• Before installation, read applicable sections in chapter 6. Installation instruction and drawings.
• Before operation, read the Preparations and conditions section for applicable instructions in
chapter 3. Operating instructions and control system description.
2.2 Specif c safety information
The following safety information apply for the areas and components below. This information is also
stated in the Preparations and conditions section for applicable instructions.
• Before maintenance, read the Preparations and conditions section for applicable instructions in
chapter 7. Service manual. Essential safety information is stated before instruction to routines
that might involve any danger.
• Before maintaining the PureBallast system, the following valves must be locked in closed
position: V201-3, V201-9, and V201-8.
• Components must be lifted using correct lifting tools (such as a fork-lift truck, a crane) and tackle
with a load capacity greater than the weight of the component. See the Technical data section
on page for information about weight. Any complementary lifting instructions must be followed.
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
UV reactor safety items
Book No.9028195 02 7
2.2 Specific safety information 2 Safety information
• UV lamps and quartz sleeves are fragile and can easily become damaged. Exercise great
care when handling them. Do not apply vibrations or shock to the UV lamp. This can cause
breakage and shorten lamp life. Broken glass/quartz can also cause severe cuts. Always use
protective eye glasses and clean cotton gloves when handling UV lamps and quartz glass
sleeves. See Material data sheet / UV lamp in chapter 6.
• UV lamps are stored according to local regulations.
• Before installation, check that the UV lamps and quartz sleeves are not broken.
• Depressurize reactors and allow equipment to cool down completely before disassembling. Hot
water may escape from the reactor when removing the drain plug.
• Never handle UV lamps before they are completely cooled down. A hot UV lamp is under
high internal pressure, and the risk of bursting exists. A hot lamp could also cause a burn
if it is touched.
• The reactor must not be under pressure when dismounting the UV lamps.
• UV lamps radiate ultraviolet radiation when lit. Only operate the UV lamp when correctly
installed inside the reactor with end caps properly closed.
• UV lamps contain a small amount of mercury (less than 0.2 grams per lamp) and must be
handled and disposed of with care. Used lamps UV can be handled and disposed of in the same
way as fluorescent lamps. Please refer to national regulations. If a UV lamp has accidentally
been broken, mercury could be spilt. Remove mercury with a special tool such as a syringe
(or use pure sulphure to bind the mercury for easy collection).
• Do not allow mercury to come in contact with your eyes or skin. Do not inhale mercury fumes.
• Free mercury must be kept in an airtight bottle, and must be disposed of according to
national regulations.
• In case of having inhaled mercury fumes, consult a doctor and follow medical instructions.
• Operation and/or manual start of the UV lamps is only allowed when there is water in the reactor
(indicated by level switch LS201-29), and the water temperature is below 60 °C. Improper
operation could seriously damage the equipment and injure personnel.
• Manual operation of LPS, may only be performed after cable connection. If not hazardous
situation may arise which, if not avoided, will result in death or serious injury.
• Before maintenance of the LDC: Switch off the PureBallast system and disconnect it from the
power supply. The LDC contains a fan, which can cause injury if in operation.
Flow meter safety items
• Actuators must not be pressurized at any time during installation as it may result in injury.
• Lock valve in closed position before maintenance.
CIP safety items
• CIP liquid: Risk for eye and skin irritation. Avoid contact with eyes and wear protective
gloves. Follow general rules when handling of cleaning agents regarding ventilation, personal
protection etc.
• Before disassembling the pump, the pneumatic hoses must be disconnected, and the extension
pipe must be removed and blocked.
• Always wear protective eye glasses and gloves while working on the pump.
• See Safety data sheet / CIP liquid in chapter 6.
8 Book No.9028195 02
2 Safety information 2.4 Warning signs used in the manual
• Control panels may only be cleaned when set in wipe mode. This is to prevent unintended
functions from being triggered by buttons pressed during cleaning.
• Temperature switch, temperature transmitter and level switch. The external surface may be hot.
Care must be taken to avoid possible burns.
2.3 Personnel requirements
The PureBallast system must be operated, installed, maintained and repaired by persons trained for
respective type of work. All persons using and working with the system must know the emergency
stopping procedures.
Personnel installing, maintaining or repairing components must be of one of the following categories:
DANGER
!
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
NG
WARNI
!
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
ON
CAUTI
!
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
NOTE
NOTE indicates a potentially hazardous situation which, if not avoided, may result in property damage.
Book No.9028195 02 9
2.4 Warning signs used in the manual 2 Safety information
3 Environmental issues
This section contains general rules regarding environmental issues. However, local rules and
regulations should be consulted for detailed handling of each material.
3.1 Unpacking
• Packing material consists of wood, plastics, cardboard boxes and in some cases metal straps.
• Wood and cardboard boxes can be reused, recycled or used for energy recovery.
• Plastics should be recycled or burnt at a licensed waste incineration plant.
• Metal straps should be sent for material recycling.
3.2 Other materials
• Rubber and plastics should be burnt at a licensed waste incineration plant. If not available they
should be disposed to a suitable licensed land fill site.
• Metal parts should be sent to a licensed handler for material recycling.
• Seal rings should be disposed of in a licensed land fill site. Check the local regulations.
• Worn out or defected electronic components should be sent to a licensed handler for material
recycling.
• The operator panel contain the following components with substances that might be hazardous
to health and the environment: lithium battery, electrolytic capacitor and display. They shall
be recycled according to local regulations.
• Used lithium batteries from the control unit are considered hazardous waste and should be
disposed of accordingly.
• Used UV lamps can be handled and disposed of in the same way as fluorescent lamps. Please
refer to national regulations.
• Used quarts sleeves should be disposed of as ordinary glass.
Book No.9028195 02 11
Chapter: 2. System description
System manual — PureBallast 3.1 1000
USCG
2 Process overview 9
2.1 IMO and USCG mode 9
2.1.1 When to use the different modes 9
2.1.2 Flow control and power optimization 9
2.2 Start-up 12
2.3 Ballasting 13
2.3.1 Backflush 14
2.3.2 Ballast after-treatment (CIP) 15
2.4 Deballasting 16
2.4.1 Deballast after-treatment (CIP) 16
3.3 Filter 24
3.3.1 Filter working principle 24
3.3.2 Filter description 24
3.3.3 Backflushing for different dirt loads 27
3
3.5 Control cabinet and control system 30
3.5.1 Control system 31
3.5.2 Main control panel 31
3.5.3 Remote control panel (optional) 32
3.5.4 Remote interface (optional) 33
4
1 Introduction
This contains general information about the PureBallast system and its components.
Book No.9028195 02 5
1.1 Components overview 1 Introduction
1. Control cabinet
2. Lamp drive cabinet (LDC)
3. CIP (cleaning-in-place) module
4. UV reactor
5. Ballast water outlet
6. Control valve
7. Flow meter
8. Sampling point
9. Filter
10. Ballast water inlet
Not in illustration:
6 Book No.9028195 02
1 Introduction 1.3 Abbreviations
The UV lamps are powered by the LDC (via LPSs, lamp power supplies). The UV reactor has
one dedicated LDC.
Flow is monitored by the flow meter and regulated by the control valve. The control valve also
regulates pressure during backflushing of the filter.
The UV reactors are cleaned using the CIP (cleaning-in-place) module, which first rinse the UV
reactor with technical water / potable water, and then circulates CIP liquid through the UV reactor.
At the end of the process the UV reactor and thefilter (filter preservation) is filled with technical
water / potable water from the CIP.
The complete system and ongoing processes is controlled and monitored from the control cabinet.
Control can also be performed from remote control panels and the ship’s ISCS, via the remote
interface.
The bypass valve makes it possible to bypass the entire system, for example to secure ballast
operation if the system is not functioning. The valve is controlled from the ISCS (integrated ship
control system).
1.3 Abbreviations
The table below is a list of abbreviations used in this manual.
Abbreviation Explanation
AOT reactor Previous name for UV reactor. AOT stands for Advanced oxidation
technology.
Book No.9028195 02 7
1.3 Abbreviations 1 Introduction
Abbreviation Explanation
Ex Explosion-proof
UV Ultra violet
UV reactor The main component, where the water is treated using UV light.
UVR UV reactor
8 Book No.9028195 02
2 Process overview
This section gives an overview of the main processes performed by PureBallast. In the flow chart
illustrations, involved pipes are marked in bold.
Before starting a process, the operator must choose if the operation shall be run in IMO or USCG
mode, depending on location and destination. Mode is set using a function button in the control
system.
2.1.1.1 IMO
2.1.1.2 USCG
• ballast when the destination port is within US waters, regardless of starting point.
• deballast within US waters.
The illustration below show flow control and power optimization depending on the UV intensity,
together with the compliant limit.
Book No.9028195 02 9
2.1 IMO and USCG mode 2 Process overview
IMO mode
UVI_IMO1000
USCG mode
UVI_USCG1000
Compliant limit: When UVI falls below compliant limit, the operation continues but does not fulfill
the type approval certificate. A warning and a common alarm is issued and a log is written to the
event log. The operator must take action according to the ballast water plan to stop the operation or
to continue operation and not comply with type approval certificate.
10 Book No.9028195 02
2 Process overview 2.1 IMO and USCG mode
In USCG mode, the flow is regulated to be as high as possible to fully treat the water. Between UVI
value a and b, the flow is regulated be between 50 % and 100 % of full flow capacity. The higher
UVI value (cleaner water) the the higher flow.
In IMO mode, the flow is always 100 % above compliant limit. But when UVI falls below the
compliant limit, the flow is decreased to maximum 50 %.
The purpose is to save power by dimming the lamps to minimum power required to fully treat the
water. Power is regulated when the UVI in the water is between c and d (see graph above). The
power output is regulated between 50 % and 100 % of full power.
• Start-up and the first two minutes of ballast/deballast: The UV lamps are lit to 100 % to ensure
treatment before values from the UV sensor are stable.
• Pause: UV lamps are dimmed to 50 % during pause and lit to 100 % for two minutes when
process is resumed.
• Stop: UV lamps are lit to 100 % for 10 seconds before they are stopped. This will prolong
the life of the lamps.
• Stripping: The lamps are lit to 100 % during the complete stripping process. This to have an
efficient treatment of the deballast water when it is mixed with the driving water, which has
not been treated at ballast.
• Low UV intensity: See Flow control above.
• Broken UV lamp: See Operation with broken UV lamp below.
If a UV lamp breaks, the ongoing process continues but does not fulfill the type approval certificate.
The flow is decreased to 80 % in IMO mode or 50 % in USCG mode of max flow and the UV
lamps are lit to 100 %. This is done so that the treatment shall correspond to the type approval
requirements. A warning and an additional common alarm is issued and a log is written to the
event log.
If a lamp breaks during operation, the operator will have to decide to stop the operation or to
continue operation and not comply with type approval certificate. After process is finished, it will not
be allowed to start a new process untill the broken lamp has been changed.
Book No.9028195 02 11
2.2 Start-up 2 Process overview
2.2 Start-up
Ballasting and deballasting begins with a start-up phase. There must be available power for
the system. If power management is integrated, this will be confirmed automatically. If power
management is not integrated, this is confirmed manually.
During start-up, the UV lamps are warmed up for 90 seconds. Cooling water is pumped through the
UV reactor to secure that the UV lamps are not overheated. The temperature transmitter and level
switch secure that there is water in the UV reactor and that the UV lamps are sufficiently cooled. If
not, an alarm is issued and the system is shut down.
2 Startup Filtrex
12 Book No.9028195 02
2 Process overview 2.3 Ballasting
2.3 Ballasting
After the start-up, when the lamps are ready, the operator is requested to start the ballast pump.
The ballast water is pumped from the sea chest to the filter, that removes larger particles and
organisms. This also reduces the amount of sediment build-up in the ballast water tanks. The
organisms and sediments caught in the filter is flushed overboard via regular filter backflush
operations. The water is finally led to the UV reactor, which produces radicals and UV light that
breaks down and neutralize the organisms.
2 BallastFiltrex
Ballasting
Book No.9028195 02 13
2.3 Ballasting 2 Process overview
2 BackflushFiltrex
Filter backflush
14 Book No.9028195 02
2 Process overview 2.3 Ballasting
We recommend that a CIP process is performed within the same ecological zone or in international
waters (200 nautical miles from the base line). This will avoid untreated water from the UV reactor
and the filter to enter a different ecological zone.
First, the UV reactor is rinsed with technical water / potable water. Then the cleaning-in-place (CIP)
module circulates a biodegradable solution through the UV reactor to remove seawater scaling.
After the cleaning is finished, the UV reactor is filled with technical water / potable water to preserve
the UV reactor and prevent scaling, algae growth etc. Finally, the filter filled with technical water
/ potable water to prevent scaling and algea growth. The cleaning liquid is reused between the
cleaning operations.
2 CIP Filtrex
Book No.9028195 02 15
2.4 Deballasting 2 Process overview
2.4 Deballasting
After the start-up, when the lamps are ready, the operator is requested to start the ballast pump.
The water passes through the UV reactor, but the filter is bypassed since the water has already
been filtered during ballasting. The reason for treating the water a second time during deballasting
is to secure that the treatment is fully effective. The minor part of the organisms, which were only
injured during ballast, will be rendered totally harmless during the deballast.
The process flow and power optimization are controlled in the same way as during ballasting.
2 DeballastFiltrex
Deballasting
16 Book No.9028195 02
2 Process overview 2.5 Tank stripping
After the start-up, when the lamps are ready, the operator is requested to start a stripping pump.
Pump used can either be a dedicated stripping pump or a ballast water pump. The flow controll is
controlled to be 1/3 of certified flow but power optimization is not active. Number of UV reactors
used during stripping is set in a parameter, to adapt to lower flow during stripping.
If a stripping eductor (not part of Alfa Laval’s scope of supply) is used it must be installed before the
PureBallast system. Minium flow for deballast water includes the driving water.
Also, the water used in the stripping process, must be filtered from particles larger than
approximately 5 mm. The sieve is not part of Alfa Laval’s scope of supply. Procedures to dispose
of sediments from the sieve must be included in the vessel’s ballast water management plan. See
also chapter 3. Operating instructions and control system description, section Stripping.
2 StrippingFiltrex
Stripping
Book No.9028195 02 17
2.6 Ballast water handling in the event of 2 Process overview
malfunction
If the system malfunction in connection with general cargo operation, ballast and deballast
operations should be avoided.
The procedures concerning emergency and malfunction of the ballast water treatment system
should be implemented in the ships Ballast water management plan.
18 Book No.9028195 02
3 System components
description
This section gives an introduction to the most important PureBallast system components and
their functions in the system.
3.1 UV reactor
The main part of PureBallast is the UV reactor in combination with a lamp drive cabinet (LDC)
giving power to the UV lamps in the UV reactor. The LDC does not need to be placed in close
relation to the UV reactor.
The UV light breaks the DNA chain resulting in an internal connection (T+T) making it impossible for
the micro organisms to reproduce.
2 UVtreatment
Destruction of DNA
There are no chemical substances added to the process, and there are no toxic residuals created.
Since the water is not affected chemically there are no environmental impact, and the process does
not influence corrosion in any way.
Book No.9028195 02 19
3.1 UV reactor 3 System components description
The UV lamps get very warm, so they must be cooled whenever they are lit. To secure that there is
water in the reactor when the lamps are lit, each reactor is equipped with a level switch. The level
switch also secures that enough CIP liquid is pumped into the reactor during the CIP process. To
secure that the lamps are adequately cooled by the ballast water, each UV reactor has a threefold
heat protection:
• The temperature transmitter sends information to the control system. The UV reactor is shut
down at 60 °C.
• The temperature transmitter sends information to a safety relay in the LDC. The UV reactor is
shut down at 62.5 °C.
• The temperature switch automatically shuts down the UV reactor at 65 °C.
A UV sensor monitors the UV lamp efficiency in relation to the water transmittance inside the UV
reactor. Based on this input, the power to the UV lamps are regulated between 50 and 100 % of full
capacity. The UV lamps will be dimmed to lowest possible level, where they are still effective.
Note, that the lamps are always lit with full effect during start-up and the first two minutes of full
ballast to secure full efficiency independent of transmittance. The lamps are also turned up to full
effect for 10 seconds before stop and normal shut down. This method will prolong the UV lamp life
time.
The illustration below show the main components for the UV reactor.
20 Book No.9028195 02
3 System components description 3.2 Lamp drive cabinet (LDC)
UV reactor
Book No.9028195 02 21
3.2 Lamp drive cabinet (LDC) 3 System components description
The humidity in the cabinet is monitored by a liquid sensor. If a leakage from the heat exchanger
is detected, a warning is issued, the reactor is shut down and the cooling water inlet valve to
the LDC is shut.
The LDC can be placed up to 150 meters (cable length) from the UV reactor. The main breaker
cut the power to the LDC and the UV reactor.
22 Book No.9028195 02
3 System components description 3.2 Lamp drive cabinet (LDC)
2 LDC
1. Fan
2. Heat exchanger
3. Lamp power supplies (LPS)
4. Fuses
5. Cooling water inlet and outlet
6. Main breaker
7. Status lights and reset button
Book No.9028195 02 23
3.3 Filter 3 System components description
3.3 Filter
2 FilterFiltrex
1. Geared motor
2. Relief valve
3. Backlflush outlet
4. Backflush pump
5. Drain plug
6. Ballast water inlet
7. Adaptor plate to change flange standard and/or
diameter (in some systems)
8. Junction box (Not included in the skid version
of PureBallast)
9. Ballast water outlet
24 Book No.9028195 02
3 System components description 3.3 Filter
To secure efficient filtration, the filter performs a self-rinsing backflush operation at time set intervals
or when triggered by indication of dirt in the filter. Pressure drop over the filter is monitored by
pressure transmitters on the filter inlet and outlet. Dirt is detected by an increased differential
pressure drop caused by particles in the filter. When the differential pressure reaches a parameter
set value, an automatic backflush operation starts.
The backflushing does not interrupt the filtration process, since only a part of the filter element area
is cleaned. The areas that are not cleaned at a specific time continues the filtration of the ballast
water. It is also possible to start backflush manually from the control system.
Book No.9028195 02 25
3.3 Filter 3 System components description
Step 1: Filtration
The water enters from the inlet flange (A) and flows through a
pre-filter and then through the filter element (1) from the inside to
the outside. The filtered dirt is trapped on the inside of the filter
element. The filtered water passes the chamber (D) and out from
the filter through the outlet flange (B) and is lead to the UV reactor.
A. Inlet
B. Outlet
D. Chamber
1. filter element
2. Motor
3. Nozzle (standing still during filtration)
2 FilterFiltrationFtrx
At backflush, the motor (2) starts to drives the nozzle (3). At the
same time, the backflush valve (6) opens.
The nozzle rotates inside the filter element. The dirt on the inside
of the filter element (1) is cleaned by a high-efficacy backflush flow
in front of the nozzle. The backflush flow uses filtered water from
the chamber (D) to clean the filter from the outside to the inside.
The water, together with the dirt, is lead via the nozzle through the
duct (5) and out via the backflush valve (6).
All areas of the filter element that is not in front of the nozzle are
filtering the water as in step 1: The water flows from the inlet (A)
through the filter element and out through the outlet (B).
A. Inlet 2 FilterBackflushFtrx
B. Outlet
D. Chamber
1. filter element
2. Motor
3. Nozzle seen from the side (rotating during backflush)
26 Book No.9028195 02
3 System components description 3.3 Filter
6. Backflush valve
In water with low dirt load, the backflush cycle is started by the time trigger (default: every 30
minutes). As long as the pressure is below the differential pressure trigger (0.50 bar), there is no
need for the pressure triggered backflush. See examples below.
6 Dirtload1 Filtrex
6 Dirtload2 Filtrex
In more dirty waters the backflush cycle will be triggered when pfilter reaches 0.5 bar, which indicates
dirt in the filter.
After each backflush, the backflush timer is reset. The filter will be backflushed again after 30
minutes or when ∆pfilterreaches 0.5 bar, whichever comes first.
In the example below, three backflushes are triggered due to high differential pressure over the filter.
After that, there is not so much dirt build up, so the next backflush is performed after 30 minutes.
Book No.9028195 02 27
3.3 Filter 3 System components description
6 Dirtload3 Filtrex
In conditions with heavy dirt load, the system can perform continuous backflushes to keep the filter
clean. If the filter preforms one backflush, and the differential pressure trigger a new backflush
within a parameter set time, the filter will perform continuous backflushes for a parameter set time
to clean the filter thoroughly. After the continuous backflush time, a check is made to make sure
that the differential pressure is below 80 % of the backflush trigger pressure. If not, the backflush
continues until this is true.
Also, the 0.5 limit might be exceeded. In this case the self rinsing cycle will run continuously
until the problem is solved and the pressure has returned below 0.5 bar. It is OK that the flow
momentarily fluctuates in an irregular curve, but it is important that the curve stabilizes.
In the example below, a series of backflushes are performed (approx. every 4 minute). After that
the pressure rises above 0.5 where the filter is backflushed constantly. After that, the normal
control is resumed, where thefilter backflush is triggered by pressure (2 times) or by time (last
backflush in the example).
6 Dirtload4 Filtrex
Over time, the filter element will undergo a long term build-up of particles that are not removed
by backflushing. One effect of this is that “normal” pressure will increase over time. Therefore,
the maintenance schedule state that the filter element shall be inspected and manually cleaned
once a year.
The extent of the long term dirt build-up is dependent on the water conditions. In the great majority
of cases this will not cause any problems – cleaning once a year is enough. But in exceptional
cases (vessels trading very muddy waters) it might be necessary to clean the filter element more
28 Book No.9028195 02
3 System components description 3.4 CIP (cleaning-in-place) module
often. If the pressure triggered backflushing is performed with short intervals, we suggest that the
filter element is manually cleaned more often than once year.
During a cleaning cycle, the CIP module rinse the reactor with technical water / potable water and
circulates a CIP liquid through the UV reactor. The low-pH CIP liquid removes scaling, calcium
chlorides, metal ion build-up and chemical fouling on the lamps’ quartz glass sleeves. After finished
cycle, the liquid is returned to the CIP module tank; the CIP liquid is reusable for a great number of
cycles. The sequence is finalized by filling the UV reactor with technical water / potable water. A
backflow preventer secures that no CIP liquid is mixed with the technical water / potable water.
To secure that there is enough CIP liquid for the process, the level switch in the reactor indicates
when it is filled with CIP liquid. To prevent intrusion of water in the technical water / potable water
system, a backflow preventer is used in the CIP module.
• Pump P320-1 circulates the CIP liquid in the UV reactor and fills it with technical water /
potable water.
• Pump P321-5 drains water (sea and technical water / potable water) overboard from the
reactor, via the drain line.
Book No.9028195 02 29
3.5 Control cabinet and control system 3 System components description
2 CIP module
CIP module
1. Deaeration valve
2. Valve block
3. Regulator
4. Pump (CIP liquid)
5. Backflow preventer
6. Pump (reactor drain)
7. Tank for CIP liquid
The control cabinet functions as a single point of contact for signal cables to and from the vessel.
Examples of integration: Remote interface integration and power management system (PMS).
Remote interface will allow control of PureBallast from the vessel’s ISCS and PMS integration will
allow automatic verification that there is enough power to run an operation. If not integrated, the
operator must verify this manually. Also integration with other external components (not part of Alfa
Laval’s scope of supply), such as GPS or booster pumps, are done to the control cabinet.
30 Book No.9028195 02
3 System components description 3.5 Control cabinet and control system
2 CC
Control cabinetpanel.
The control system store all alarms and relevant events for at least 24 months. The memory has
a vast safety margin but when it is full, data will be deleted starting with the oldest logs. Logged
information can be exported to a USB memory stick.
There are three alternative ways to monitor and control PureBallast: Main panel, remote control
panel (optional) and remote interface (optional).
If two PureBallast systems are installed on a vessel, two control systems are needed.
Book No.9028195 02 31
3.5 Control cabinet and control system 3 System components description
2 CC
2 RCP
32 Book No.9028195 02
3 System components description 3.6 Main valves
Note that Alfa Laval does not supply the graphical user interface to handle PureBallast in the
ISCS, only the means to enable the integration.
2 RI
PureBallast control system’s main control panel integrated with the ISCS. The interface is only an example.
• Inlet valves: The inlet valves directs the water flow from the vessel’s ballast water system into
the PureBallast system. Different valves are used during ballast and deballast.
- System and f lter inlet valve (201–3): Inlet valve to PureBallast during ballast. The valve
directs the water flow through the PureBallast filter.
- Filter outlet valve (V201–32): The valve directs the water flow from the filter to the UV
reactor during ballast.
- Inlet valve (201–9): Inlet valve to PureBallast during deballast. The valve directs the water
to PureBallast, but bypass the filter, since the water was filtered during ballasting.
• Control valve (V201–8): The valve have the following functions:
- Automatic regulation to maintain flow during operation so it does not exceed selected
certified maximum flow. Regulation is based on input from the flow meter.
- Automatic regulation to maintain pressure needed to perform backflush of the filter.
Regulation is based on input from the pressure transmitter.
- Outlet valve from the PureBallast system to the vessel’s ballast water system after treatment.
Book No.9028195 02 33
3.9 Sampling devices 3 System components description
• PureBallast bypass valve (V212–31): Makes it possible to completely bypass the PureBallast
system. The valve is solely operated from the ISCS, but the valve positioning is (and must be)
indicated in the PureBallast control system. When PureBallast is bypassed, an event is written
to the event log. The valve is equiped with a handwheel for manual operation. The component
is optional to be included in Alfa Laval’s scope of supply.
• Cooling water inlet valve (V403-35): Supplies cooling water to the reactor to secure cooling of
the lamps and prevent overheating during start-up.
3.7 Flow meter
The flow meter (FIT201–1) monitors the process-flow during operation. It has two main functions:
• It monitor that the flow within the PureBallast system does not exceed its certified flow. If the
certified flow is exceeded a warning is issued.
• Via the flow transmitter, mounted on the flow sensor, it sends valuable data to the PureBallast
control system, where it is displayed. Example of information: Current flow and data about
total amount of treated ballast water.
The flow meter consists of two main parts: A flow sensor, which is a pipe with four electrodes
detecting the flow. On top of the pipe, the flow transmitter housing is mounted. The flow transmitter
monitors the flow and transmits the information to the PureBallast control system.
• Pressure transmitter(PT201-16): Send current pressure information to the control system. The
control system use the information to take actions accordingly, for example issue warnings, shut
down the system or adjusting the control valve to obtain optimal pressure during filter backflush.
• Pressure gauge (PI201-18): Analogue displayed of current pressure.
• Needle valve (V201-15): Enables connection of external instruments for calibration.
• Safety valve (RV201): Relief of over pressure.
3.9 Sampling devices
The two sampling devices (Q201.1 and Q201.2) make it possible to take water samples to test the
water. One sampling device is installed before the water is treated and one after the water is
treated. This enables comparative tests of treated and untreated water. The component is optional
to be included in Alfa Laval’s scope of supply.
34 Book No.9028195 02
Chapter: 3. Operating instructions and control system description
System manual — PureBallast 3.1 1000
USCG
3
3.8 Page 3.2 – Trend (1 h) 37
3.9 Page 3.3 – Trend (1 h) - TT201-33 37
3.10 Page 3.4 – Trend (1 h) - TT401-2 37
3.11 Page 3.5 – Trend (1 h) - Power
optimization 37
3.12 Page 3.7 – Trend (15 min) - External feed
optimization 37
3.13 Page 3.8 – UVR 1-3 UV optimization 38
3.14 Page 4.1 – System info 39
3.15 Page 4.2 – PLC controller I/O 42
3.16 Page 4.3 – Operation timers 43
3.17 Page 4.4 Operation timers UVR 45
3.18 Page 4.5 – Remote interface 1 46
3.19 Page 4.6 – Remote interface 2 47
3.20 Page 4.7 – Log box 1 48
3.21 Page 4.9 – LPS overview 49
3.22 Page 5.1–5.7 – Parameter pages 51
3.23 Popup windows 51
3.23.1 UVR popup 51
3.23.2 Filter popup 56
4
4 Operating instructions 59
4.1 Log in 59
4.2 Perform ballast 59
4.3 Perform deballast 61
4.4 Perform tank stripping 62
4.5 Pause ballast / deballast / stripping 63
4.6 Heel (internal transfer) 64
4.7 Backf ush f lter manually 65
4.8 CIP clean UV reactor after ballast /
deballast / stripping 65
4.9 Attend to alarms 66
4.10 Shut down and deactivate system 68
4.11 Reset system after shut down 69
4.12 Operate components manually 70
4.13 Operate UV lamps manually 71
4.14 Set ship specif c component ID 72
4.15 Export control system event log f les 73
4.16 Backup control system settings 75
4.17 Restore control system settings 75
4.18 Set control panel IP address 76
4.19 Set remote control panel
communication 77
4.20 Set remote interface communication 79
4.21 Test remote interface communication 79
4.22 Simulate power request 81
4.23 Update control system softwares 82
4.24 Calibrate the control panel’s touch
screen sensibility 82
4.25 Fine tune f ow control 82
4.25.1 Calibrate pressure controlled regulation 82
4.25.2 Calibrate external feed control (optional) 84
5
5 List of logged information 87
5.1 Event log 87
6
1 Introduction
The control system is used to operate and monitor the PureBallast system. It also contains
functions for setting parameters, saving log files etc.
This chapter describes the control system. It includes general description of the control system
pages, step-by-step instructions and a process description with detailed information about the
components (valves, motors, pumps etc) involved in each step of respective process.
• The input flow to the PureBallast system shall be as close as possible to the flow that has been
selected for an operation. This will reduce the stress and wear of the control valve.
• During process, the control system requests that vessel valves are opened/closed. The
valves are outside the PureBallast system control. But the control system needs feedback
(opened/closed) during process. Status can either be confirmed manually in a popup or
automatically, if feedback signals are integrated via the remote interface option or via hard wire.
Please note:
- When overboard valves are requested to be opened/closed, this means that all valves
leading the flow from the PureBallast via one of the following pipes must be opened/closed:
201, 309 and 403 and 404. During CIP process, 460.1 must be opened.
Book No.9028195 02 7
1.1 Preparations and conditions 1 Introduction
However, in some cases there is a risk that ballast water is not treated according to requirements,
or contaminated by untreated water.
• Water was ballasted with IMO mode, when the destination port is within US waters.
• PureBallast was bypassed (Alarm A33, 66, 67 and 68)
• Operation with higher flow rate than certified (Warning W12)
• System not CIP cleaned within time (Warning W140)
• Operation with one or more non-functioning lamp (Warning W130, W131)
• UV intensity lower than limit stated in the type approval certificate (Warning W151, W152,
W154).
• The ballast water is contaminated by untreated water from other pipes, i.e. there are living
organisms in the water. Even a very small amount of water, a few hundred liters, can
contaminate a ballast tank and cause non-compliance during a compliance test. It is therefore
important that PureBallast is always used for operation. The reason for this can be
If the ballast water is not fully treated or contaminated by untreated water, a ballast water exchange
must be performed, making sure that the tanks and pipes (including dead ends) are flushed and
replaced with with treated water.
1.1.2 Stripping
Stripping can be performed to empty the ballast tanks. The first time a ballast tank is stripped,
PureBallast must be bypassed.
The stripping process is basically the same as a deballast process with the following difference: A
stripping eductor (or a stripping pump) should be used to secure enough flow in the system.
8 Book No.9028195 02
1 Introduction 1.1 Preparations and conditions
We recommend that the driving water alone (without the ballast water flow from the tank) fulfils the
minimum flow requirement for deballast operation. This will minimize the risk of shut down due to
low flow when flow of ballast water is uneven.
If external component signal for heeling mode is integrated between PureBallast and the vessel’s
ISCS, ongoing process will be paused and resumed automatically. The user is notified of started
and stopped heeling via warnings, and the event is logged.
If no external signal is integrated, the ongoing process must be paused manually. During pause,
cooling water is flushed through the UV reactor to cool the UV lamps. After completed heeling,
the operator must resume the paused process.
In PureBallast, a deballast process is run with the vessel’s ballast valves positioned so that the
• pump takes water from a ballast water tank with treated water and
• the water flow is directed either overboard or to another ballast tank.
Run the process for enough time so all water in the piping is treated. Time for this depends on pipe
size and length on board.
Book No.9028195 02 9
1.1 Preparations and conditions 1 Introduction
2 Introduction to the control
system
This section describes different login levels, overview of the system interface and how to navigate
and operate the control system.
Guest N/A Default mode of control system. This level is not password protected.
AlfaLaval N/A Full access. Password only available for Alfa Laval personnel.
Book No.9028195 02 11
2.2 Control of PureBallast 2 Introduction to the control system
The information below is only valid if remote control panels and/or remote interface is installed.
To switch command from one panel to another, you log in to the new panel. This is only possible by
using the same or higher login level as used in the active control panel. When control is about to be
changed from one panel to another, the following will happen:
• The inactive control panel will display a popup message informing that another control panel is
active (some one else is logged in). The popup gives the alternative to cancel or to continue. If
continue is chosen, control is swithced from the first panel to the new panel.
• The active panel will display a popup message informing that another the panel is inactive
and that control is taken by another panel.
On each control panel it is possible to see which panel that is active and which login level that is
used. A panel alias can be entered to clarify where the panel is installed, for example pump room,
bridge etc. See instruction Set control panel IP address on page 76. This information is visible in
the upper right corner of the system according to syntax: login level@control panel.
3 ActivePanel
It is only possible to switch command between control panel and ISCS from a PureBallast control
panel. This is done by using the Local and Remote buttons, when logged in as Operator or higher.
Control status (local or remote) is indicated by a green light under the button that corresponds to
the system currently in command. In the ISCS, control status can be indicated by using the status
signal dedicated to this. It is recommended that this signal is implemented in the ISCS.
12 Book No.9028195 02
2 Introduction to the control system 2.2 Control of PureBallast
When remote interface is activated, PureBallast can only be controlled from the ISCS. It possible
to access the same pages and perform the same operations from the ISCS as for login level
Operator (to the extent that the systems are integrated. However, the following two tasks can only
be performed from a (any) control panel: Set parameters and switch control between control
panel(s) and ISCS.
When remote interface is activated, the panel(s) can only be used to monitor the system, export log
files and switch control between PureBallast control panel(s) and ISCS.
The PureBallast system manual does not give any information about how to run PureBallast from
the remote interface. This is due to the fact that the remote interface is custom-made. Please
refer to the vessel specific manual.
PureBallast can be operated from ISCS when the conditions below are met:
• The remote interface must be correctly installed, according to Remote interface implementation
guide.
• Remote interface must be activated (parameter p132) and communication settings must be
correct (parameter p700 – p704).
• The Test mode button must be deactivated (no checkmark on the button) in control system
page 4.5 Remote interface 1.
• Remote control must be activated. Check that the green lamp is lit under the Remote button
on the control panel. If not, press the button. The system must be in Standby mode to toggle
between local and remote operation.
Operation
• Heartbeat is updating. See that address 06 and 77 are updating in control system page 4.5
Remote interface 1.
• There must be no active alarms for the UV reactors to be used during operation. Always check
the alarm list (page 2.1 Alarm list in the control system) before operation.
• The UV reactor must be in standby mode.
Book No.9028195 02 13
2.3 Overview of the screen 2 Introduction to the control system
The control system use a touch screen, where you tap the screen to “click” or drag objects. Do not
use sharp objects to touch the screen. When the screen is left idle it will go to screensaving mode.
Time is set in page 4.1 System info. The screen is activated again by touching it once. The touch
will not activate any button that might be placed where you touch.
The illustration below shows the main areas and function buttons on the screen.
3 1.1 USCG
Tabs: The top and side tabs are used to choose which page to display in the screen. Pages are
referred to as a number and a name, for example 2.1 Alarm list. The first number refers to selected
top tab, counted from left to right. The second number refers to selected side tab, counted from top
to bottom. Selected tabs are indicated by a white color.
Top tabs: Contain the main function areas of the control system: Overview, alarm lists, trend
indication, system information and parameters.
Side tabs: Contain sub pages for the area selected in the top tab. Available side tabs change
depending on which function area that have been selected in the top tab.
Popup windows: Are used to display or enter detailed information. It is possible to move a popup
by touching the name bar and drag it. A popup is closed either by touching confirming entered
information by touching a function button (OK, Conf rm, etc.) or the X icon in the top right corner
(data is not saved).
14 Book No.9028195 02
2 Introduction to the control system 2.3 Overview of the screen
Data entry f elds: A white field indicates that it is possible to enter data. When the field is touched,
a keyboard is displayed, which is used to enter information. Enter data is confirmed by touching the
Enter button. To close the keyboard without saving data, touch the Esc button.
Tables: Individual table rows, for example an alarm, can be selected by pressing them. Column
widths can be adjusted. Press the column border in the head area and hold the finger on the screen.
Function buttons: Function buttons are used for main processes and control of the system. They
are placed att the bottom of the screenare and are always visible, but only available when colored
dark blue. Some buttons are dependent on parameters. For example, the Remote and Local
buttons are only visible if remote interface is activated.
Status indication – Button color: The buttons appear in different colors, indicating status:
Blue The function is enabled.
Grey The function is disabled, for example if higher login level is required for the
function.
Status indication – Button light: After a function button is pressed, a light under the button is lit
to indicate status for the activated function:
Yellow Command will be processed when possible in the data work flow.
Button Description
3 StopBut
Book No.9028195 02 15
2.3 Overview of the screen 2 Introduction to the control system
Button Description
3 CIPbut
Activate operation from control panels, instead of remote interface (if option
is used). The button is only enabled in standby mode.
3 LocalButton
3 RemoteBut
Sets the control system in manual mode, which enables manual operation
of the system and its components. When activated, the light flashes yellow.
The button is displayed for login level Advanced operator or higher. For
3 EnableManual detailed information see Manual mode on page 109.
3 WhipeBut
Activate night light for the panel. Night light makes the panel less bright.
Toggles between night light and day light.
3 NightBut Degree of brightness, is set in the Night light level field in page 4.1 System
info.
16 Book No.9028195 02
2 Introduction to the control system 2.3 Overview of the screen
Button Description
IMObut
USCGbut
Alarms and warnings for components are displayed in the flow chart and popups:
Active alarm.
3 Alarm
Active warning.
3 Warning
Book No.9028195 02 17
2.3 Overview of the screen 2 Introduction to the control system
3 Detailed page descriptions
This section describes the pages used for operation. Note that this section does not cover the
parameter pages. Please refer to chapter 4. Parameters.
The main areas are the Status box and the Flow chart.
3 1.1 USCG
Book No.9028195 02 19
3.1 Page 1.1 – Overview 3 Detailed page descriptions
Process and sub process Process: Ongoing process. Can be standby, ballast, deballast
and CIP.
Time Remaining time for the ongoing sub process in the upper right
corner.
Processed volume (m3) Amount of water processed during ongoing process. Value
remain until next process is started.
Certif ed f ow (m3/h) Certified flow (m3/h) selected for operation. The information is
updated after the warm up time has passed and a UV reactor
is used for process. This is also the flow the system is aiming
to keep.
Current f ow (m3/h) Water flow in the system, indicated by flow transmitter FIT201-1.
The system aims for the selected flow minus parameter p111
Undershoot certified flow, which can be set as a safety margin.
Ballast pump Status indication for balast water pump (not part of Alfa Laval’s
scope of supply).
Status indication
3 PumpReq
Green, blinking = Request sent. Popup message “Confirm
ballast pump started” is displayed. (The popup is not displayed
if the component feedback is integrated with the control system.)
Green = Feed back that pump is running, either via hard wired
feedback, remote interface or the confirmation popup.
Overboard valve(s) Status indication for overboard valve(s), and other relevant
valves for the process (not part of Alfa Laval’s scope of supply).
20 Book No.9028195 02
3 Detailed page descriptions 3.1 Page 1.1 – Overview
Status indication
Green = Feed back that valve is open, either via hard wired
feedback, remote interface or the confirmation popup.
Grey = Closed.
Relevant information regarding ongoing process and component status can be monitored directly
in the flow chart. Flow in pipes is indicated by coloring of the pipes and component status are
displayed by color indications. Pressure, flow and control valve opening percentage are displayed
directly on component.
Detailed information about components can be monitored in popups (by tapping the component):
UV reactor see page 51; filter see page 56. CIP open page 1.3 CIP status, see page 25). The popup
contain status for sub components, for example valves, motors and UV lamps in the UV reactor.
UVR cooling water pump (P403–1) is only displayed if it is used and activated in the parameter
pages.
In manual mode (login level Advanced operator or higher) it is also possible to operate components
manually: If a component is pressed, a popup window is displayed from which the component
can be operated.
Status indication
Mixed colors = Mixed water, for example ballast water and technical water
/ potable water.
Book No.9028195 02 21
3.1 Page 1.1 – Overview 3 Detailed page descriptions
Status information for bypass valve(s) V212–31 and external bypass valves
(not part of Alfa Laval’s scope of supply). These valves are operated from the
ISCS, due to safety reasons.
3 P309
3 Manual1
22 Book No.9028195 02
3 Detailed page descriptions 3.2 Page 1.2 – UVR and flow selection
Normally, flow is handled from page 1.1 Overview, and this page is used during commissioning and
faultfinding when it is necessary to start individual UV reactors.
The main areas of the page are the Flow selection, UVR selection and Status.
3 1.2 USCG
Book No.9028195 02 23
3.2 Page 1.2 – UVR and flow selection 3 Detailed page descriptions
Elements Description
Modify button Enables active selection of individual UV reactors. When pressed, the
buttons for respective UV reactor turns blue and are possible to use.
UVR 1, 2, 3 button One row for respective installed UV reactor with current status indicated
in the columns.
Status indication:
3.2.3 Status
The area displays current status for the flow:
Elements Description
Current f ow Ballast water flow in the system, indicated by flow transmitter FIT201-1.
Certif ed f ow Maximum allowed flow as set in Flow setpoint or limited by the number of
UV reactors selected in UVR selection popup. If a smaller filter is installed,
the ballast flow can be lower than the UV reactor capacity.
The information is updated after the warm up time has elapsed and a UV
reactor is used for process. (Before that it is not used for treatment, and
therefore not part of the certified flow.)
24 Book No.9028195 02
3 Detailed page descriptions 3.3 Page 1.3 – CIP status
3 1.3 USCG
Book No.9028195 02 25
3.3 Page 1.3 – CIP status 3 Detailed page descriptions
Row Content
Process and sub Process: Ongoing process. Can be standby, ballast, deballast and CIP.
process
Sub process: Sub steps of ongoing process, for example “Start-up” during
Ballast process.
Row Content
Filter preservation This row indicate status and time for the filter preservation process, that
starts after completed CIP. During filter preservation, the CIP fills the filter
with technical water / potable water for preservation purpose.
Total Total estimated time for a complete CIP process including filter preservation.
Column Content
CIP error Red square: Indicates that there is an active alarm for the component.
Check alarms on page 2.1 – Alarm list.
Status indication
Yellow = CIP required. During ongoing CIP process, yellow indicates that
the UV reactor is waiting for CIP process to start.
26 Book No.9028195 02
3 Detailed page descriptions 3.3 Page 1.3 – CIP status
Column Content
Estimated time Time remaining CIP time. If CIP process has not been started, total time is
displayed. During CIP process, the time is counting down continuously.
The CIP process takes about 25 minutes , if default parameters are used.
Required CIP Time before a CIP process must be performed after ballast or deballast.
countdown The time disappears when the CIP process is ready. Time is displayed for
the UVR with shortest time left to required CIP.
Book No.9028195 02 27
3.4 Page 1.4 – Power request 3 Detailed page descriptions
3 1.4 USCG
Column Content
Process and sub Process: Ongoing process. Can be standby, ballast, deballast and CIP.
process
Sub process: Sub steps of ongoing process, for example “Start-up” during
Ballast process.
Max power Maximum power consumption for the number of selected UV reactors. The
consumption value is updated when a process is started.
Measured power Power consumption during process. Value calculated based on number
consumption of used UV reactors.
28 Book No.9028195 02
3 Detailed page descriptions 3.4 Page 1.4 – Power request
Power status
Column Content
Pure Ballast always asks for power before the UV lamps are lit during ballast
or deballast start-up. When a request has been sent, the vessels power
management performs a power check before the generator is started.
Book No.9028195 02 29
3.4 Page 1.4 – Power request 3 Detailed page descriptions
The page can also be used to troubleshoot the power management system integration by sending
and checking each signal.
Buttons Content
Request Press to manually simulate request for a power step. The button is
displayed for login level Advanced operator or higher.
Set run Press to manually simulate run signal for a power step. The button is
displayed for login level Advanced operator or higher.
30 Book No.9028195 02
3 Detailed page descriptions 3.5 Page 2.1 – Alarm list
- A = Alarms stop the ongoing process, which can be restarted after the problem has been
attended to.
- W = Warnings are notification of a status change, request for action or a problem that must be
attended to. Warnings allow the process to continue.
For detailed information about alarms and warnings see chapter 5. Alarms and faultfinding.
3 2.1 USCG
The main areas of the page are the Alarm list and the Function buttons:
Book No.9028195 02 31
3.5 Page 2.1 – Alarm list 3 Detailed page descriptions
Column Content
Text Descriptive alarm text written as: Area-Alarm type AlarmID Alarmtext.
Example: UVR2 A138 Error in LDC cabinet.
Acknow- The time the alarm/warning was acknowledged. The alarm/warning remains
ledged time in the alarm list until the causing condition is resolved. For example a high
temperature alarm will remain visible, until the temperature is below the limit
value for the alarm/warning.
The table below shows status indication for alarms and warnings in the alarm list.
Button Function
Ack selected Acknowledge selected alarm (row). Press a row to indicate it, and press the
button to acknowledge it.
32 Book No.9028195 02
3 Detailed page descriptions 3.6 Page 2.2 – Alarm history
3 2.2 USCG
Column Content
Text Same as in Page 2.1 Alarm list.
Normal time The time the value that caused the alarm returned to normal.
Book No.9028195 02 33
3.7 Page 3.1 – Trend (15 min) 3 Detailed page descriptions
3 3.1 USCG
Trends can be plotted for the following components (identified by item number) and key values:
Filter diff. pressure Bar Differential pressure over filter, indicated by pressure
transmitter 201–71 and 201–72.
34 Book No.9028195 02
3 Detailed page descriptions 3.7 Page 3.1 – Trend (15 min)
Y axis: The scale and unit used for the Y axis is set in the Settings popup for respective component.
For details, see the Component area section below.
Settings Press the button to make settings for the component’s curve. Settings are
button done in a popup.
3 TrendCurveSet1Nr
1: Press (not slide) the top right button to display or hide trend curve in the
diagram. A green I indicate displayed, and a grey O indicates not displayed.
2: Press the entry field to change start and stop value for the components Y
axis scale (when this component’s scale setting is used).
3: Press this button to use this component’s scale setting in the diagram.
4. Press the entry field to enter number of decimals in the component area, or
use the - - or ++ buttons to increase or decrease.
Book No.9028195 02 35
3.7 Page 3.1 – Trend (15 min) 3 Detailed page descriptions
Value Current value for the component is displayed in the gray field. (This
corresponds to the diagram.)
Buttons Content
Export long- Export trend curve history as a csv file. The file can be sent to Alfa Laval for
term trend advanced trouble shooting.
data to USB
Insert a USB memory in USB panel port on the cabinet door. Press Export
long-term data to USB button. Wait for the message “Exporting database
table …” to disappear. The file has been downloaded to the USB memory,
in a folder named DatabaseExport.
History mode Only available for page 3.1. Press the button to display this popup:
3 TrendCurveTime
Press one time unit (year, moth, day etc) and then press – or + to set time.
36 Book No.9028195 02
3 Detailed page descriptions 3.12 Page 3.7 – Trend (15 min) - External
feed optimization
See page 3.1 Trend (15 min.) for information about function, fields and buttons.
See page 3.1 Trend (15 min.) for information about function, fields and buttons.
See page 3.1 Trend (15 min.) for information about function, fields and buttons.
See page 3.1 Trend (15 min.) for information about function, fields and buttons. See chapter 2.
System description, section Power optimization for details.
• UVR UV setpoint: The UV intensity the system is aiming to attain by increasing or decreasing
power effect to the LPS controlling the dimming of the UV lamps. The setpoint is based on
actual transmittance and is updated every 15 seconds.
• UV measurement: Actual UV intensity (W/m2) measured by UV sensor QT201–50. If intensity
is lower or higher than needed, the power to LPS will increase or decrease to attain setpoint
for UV intensity.
• Power output: Actual LPS power to UV lamps. The power is adjusted to attain the setpoint for
UV intensity based on measured water transmittance. Output is adjusted based on input from
UV sensor QT201–50. Power can be 50–100 %.
3.12 Page 3.7 – Trend (15 min) - External feed
optimization
The page is used to display the trend curves for detailed data valid for the external feed.
Book No.9028195 02 37
3.13 Page 3.8 – UVR 1-3 UV optimization 3 Detailed page descriptions
We recommend that page 3.1 is used to monitor external feed trend curves. This page is mainly
used for advanced trouble shooting.
The external feed is used to fine tune the control of the flow that comes to PureBallast. It works as
an addition to the flow controlled by the control valve (V201-8).
38 Book No.9028195 02
3 Detailed page descriptions 3.14 Page 4.1 – System info
3 4.1 USCG
HMI info CPU: Control panel’s usage of the central processor unit (CPU) in
percent of total capacity and temperature (°C). The control panel will
shut down when the CPU reaches 100 °C.
Used storage: PLC flash card’s used storage in percent and MB.
Storage used for the event and alarm log.
iX version: N/A.
Book No.9028195 02 39
3.14 Page 4.1 – System info 3 Detailed page descriptions
Setup button: Opens popup to set IP address for the main panel and
the remote control panels (optional). Requires login level AlfaLaval.
HMI date and time UTC Date and time: Set and synchronize date and time. (If parameter
p160 is activated, date and time is is retrieved from GPS with RMC
protocoll instead. Requires login level Advanced operator.
Set button: Set time and date for the main control panel. Remote
control panels are updated with this time within 15 minutes after
syncronization.
HMI Backlight Screen saver timeout: Defines time before the panel is set to
screen save mode. This is set individually per control panel.
Night light level: Defines percent of full light for the night light
mode. Night light is activated by the Night function button.
PLC Info CPU temperature (°C): Temperature of the central processor unit
(CPU) in the PLC.
40 Book No.9028195 02
3 Detailed page descriptions 3.14 Page 4.1 – System info
Backup and restore Settings to/from USB panel: Export and inport information to the
USB panel port on the cabinet door.
Set default button: Set all parameter values to the default values.
Requires login level Advanced operator.
Export log f les Export button: Opens the Export log f les popup to export (copy)
event log files and alarm list.
Remote control panels Remote control panels button: Open a popup used for setting IP
addresses for remote control panels (optional). See instruction Set
control panel IP address on page 76.
Book No.9028195 02 41
3.15 Page 4.2 – PLC controller I/O 3 Detailed page descriptions
Note that this page is only intended for Alfa Laval’s personnel and only visible and available for
login level AlfaLaval.
42 Book No.9028195 02
3 Detailed page descriptions 3.16 Page 4.3 – Operation timers
3 4.3 USCG
Row Unit
Book No.9028195 02 43
3.16 Page 4.3 – Operation timers 3 Detailed page descriptions
Row Unit
44 Book No.9028195 02
3 Detailed page descriptions 3.17 Page 4.4 Operation timers UVR
3 4.4 USCG
UVR 1–3: Total runtime for the UV lamps in Lap time for installed UV lamps, since
Lamps on respective UV reactor. the counter was reset after previous
reset at UV lamp change.
Book No.9028195 02 45
3.18 Page 4.5 – Remote interface 1 3 Detailed page descriptions
For detailed information about addresses, information and format, see chapter 6. Installation
description and drawings, section Remote interface integration (optional).
3 4.5 USCG
Test mode Activates test mode. Communication can be sent between the
ISCS and PureBallast’s PLC without actually affecting the control
system (start process etc). To send information, enter desired
digits in the entry field.
46 Book No.9028195 02
3 Detailed page descriptions 3.19 Page 4.6 – Remote interface 2
For detailed information about addresses, information and format, see chapter 6. Installation
description and drawings, section Remote interface integration (optional).
3 4.6 USCG
Book No.9028195 02 47
3.20 Page 4.7 – Log box 1 3 Detailed page descriptions
3 4.7 USCG
Column Content
Conf guration Select configuration number by entering a number or using the arrow buttons.
nr Signal status and Configuration are displayed for selected configuration
number.
Signal setting
48 Book No.9028195 02
3 Detailed page descriptions 3.21 Page 4.9 – LPS overview
Column Content
Conf guration This is the definition of which signal that should be active to constitute a
bypass/heeling. Tap the checkbox to select or unselect it.
Book No.9028195 02 49
3.21 Page 4.9 – LPS overview 3 Detailed page descriptions
Column Content
Lamp OK Status: Green = UV lamp lit and LPS is OK. Red = LPS in fault state.
Voltage fault Status: Red = Too low incoming power to the LPS.
Air temp fault Status: Red = Temperature in LPS is higher than 45°C.
If a sum alarm is issued for an LPS, an alarm icon is shown for the last LPS
with an alarm. The icon disapears when the alarm is acknowledged.
3 Alarm
50 Book No.9028195 02
3 Detailed page descriptions 3.23 Popup windows
It is possible to lock a popup, so it remains open, even if you change page. Press the pin icon to
lock and unlock the popup.
Grey = Unlocked. Blue = Locked.
3 PopLock
3 PopLockBlue
In manual mode (login level Advanced operator or higher) it is also possible to operate components
manually. If the component is pressed, a popup window is displayed from which the sub
components can be operated. Operation of UV lamps in LPS control popup requires login level
Advanced operator. LDC cooling water pump (P401–1) is only displayed if it is used and activated
in the parameter pages.
Book No.9028195 02 51
3.23 Popup windows 3 Detailed page descriptions
Component Description
Grey = Off.
Yellow = Starting.
Green = Started.
Valves For status indications, see Status indication – Component color in section
Flow chart on page 21.
52 Book No.9028195 02
3 Detailed page descriptions 3.23 Popup windows
LDC status
Component Description
Open the LPS control popup, which enables manual operation of individual
UV lamps. Requires login level Advanced operator to see the button and
3 LPSctrlbut
manual mode open the popup. See LPS control popup and instruction
Operate UV lamps manually on page 71.
Open the LPS status popup, which gives an overview of status for UV
lamps and LPSs.
3 LPS StatusBut
Fan speed Fan rotation in percent of full effect. Fan effect is based on need for cooling.
Water temperature Temperature of incoming cooling water to the LDC cabinet indicated by
TT401–1.
Heat exchanger Indicates if the valve for LDC cooling water (SV401–51) is open.
valve Status indication: Green = Open. No indication = Closed.
P401–1 Cooling Indicates if the LDC cooling water pump is running or not. The pump is
water pump running if the cabinet needs cooling, based on temperature.
Status indication: Green = Running. No indication = Not running.
The popup is used for to manually start the UV lamps in the UV reactor. See instruction Operate
UV lamps manually on page 71. The popup is displayed when the LPS control button is pressed
in the UVR popup. Requires login level Advanced operator to see the button and that manual
mode is activated to open the popup.
The UV reactor is equipped with 16 UV lamps. In each lamp drive cabinet (LDC) is 16 lamp power
supplies (LPS) that supplies power to one UV lamp each. The lamps can be operated individually in
manual mode.
DANGER
!
• Manual start of the UV lamps is only allowed (and possible) when there is water in the UV
reactor (indicated by level switch LS201-29), and the water temperature is below 60 °C. All
necessary items – cooling water flow, water temperature, and power management – must be
supervised and verified by the authorized trained personnel operating the system. Improper
operation of this function could seriously damage the equipment and injure personnel.
Book No.9028195 02 53
3.23 Popup windows 3 Detailed page descriptions
Component Description
UVR number Information is displayed for the UV reactor selected in the UVR number
field.
Enables manual operation of the LPSs to light the UV lamps. The button is
displayed for login level Advanced operator or higher. The button enables
3 LPS Manual
manual lcontrol of UV lamps.
LPS 1–16 Press one button (1–16) to start or stop UV lamp 1–16 manually, controlled
by the LPS.
Status indication:
Start all LPS, and thereby all lamps for the UV reactor. Requires that the
Manual mode button is pressed.
3 LPS StartAll
Stops all LPS, and thereby all lamps for the UV reactor.
3 LPS StopAll
The popup gives detailed information about UV intensity for UV reactors and power for LPSs. The
information is mainly used for advanced trouble shooting by Alfa Laval’s personnel.
54 Book No.9028195 02
3 Detailed page descriptions 3.23 Popup windows
LPS status
Component Description
UVR Information is displayed for the UV reactor selected in the UVR number
field.
LPS fail safe Displays if LPSs is active and powered on. UV lamps can only be lit if an
LPS is active. When a critical alarm (e.g. no water in the UV reactor) is
issued, the fail safe function inactivates the LPSs and cut the power.
LPS 1–16 Actual effect from each LPS to respective UV lamp. Green = LPS/Lamp
on. Gray = LPS/Lamp off.
Power optimization
Book No.9028195 02 55
3.23 Popup windows 3 Detailed page descriptions
Component Description
Power output Setpoint for LPS power output (50-100 %). This is how much power the
system is set to maintain.
The power is adjusted so that the UV lamps are lit to the effect needed
to attain
Manual power Manually set effect to LPS. Requires that the system is set in manual
output mode.
In manual mode (login level Advanced operator or higher) it is also possible to operate components
manually. If the component is pressed, a popup window is displayed from which the sub component
can be operated. When manual mode is deactivated the system will return to standby mode: All
manually operated components will return to their status prior to the manual operation.
56 Book No.9028195 02
3 Detailed page descriptions 3.23 Popup windows
Component Description
Diff. pressure Indicates differential pressure over the ilter (PT201–71 minus
PT201–72). When the pressure reach the value set in parameter p305,
a backflush is triggered.
Pipes, valves, motor For status indications, see Status indication – Component color in
and pump section Flow chart on page 21.
Book No.9028195 02 57
3.23 Popup windows 3 Detailed page descriptions
4 Operating instructions
This section contains step-by-step instructions for operating the PureBallast system. Please read
and follow the preparations and conditions carefully, as well as any danger or warning notes.
• Control system pages used in the instructions: See section Control system — Detailed page
descriptions.
• Login levels required for different procedures: See section Login levels on page 11.
• Detailed information about components (valves, motors, pumps etc) involved in each step the
process. See section Detailed process description.
4.1 Log in
Follow the steps below
1. Press the expand button on the Log in tab in the top right corner of the screen.
Result: The log in menu is displayed.
2. Press the expand button on the left drop down menu to display available users. Press desired
user.
Result: A keyboard is displayed.
3. Enter password and press Enter. (See section Login levels on page 11.)
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• All valves leading flow to and from PureBallast must be opened. They are not operated by
PureBallast.
• Flow must have been selected before a process can be started, either manually or automatically.
See Flow selection on page 19.
• There must be available power for the system. If power management is integrated, this will
be handled automatically. If power management is not integrated, confirm available power
manually.
Book No.9028195 02 59
4.2 Perform ballast 4 Operating instructions
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Ballast start-up starts, with cooling water cooling the lamps during warm-up.
3. Wait for the message “Confirm ballast pump started”. Start the pump and then press the
button in the popup to confirm the action. Note! This component is outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
Result: Cooling stops and ballasting starts.
4. When desired amount of water has been processed, press the function button Stop.
To get a smooth stop, the flow from the ballast pump can be reduced, but not more than 50 %.
Result: Ongoing process is stopped and the lamps are switched off. An automatic filter
backflush is performed.
5. Wait for the message “Close valves ...”. Close relevant valves and then press the button in
the popup to confirm the action. Note! These valves are outside outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
6. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
CIPpop
60 Book No.9028195 02
4 Operating instructions 4.3 Perform deballast
NOTE
A CIP cleaning process must be f nished within the time stated in the popup (30 hours from the f rst operation
after the previous CIP process). Therefore consider the time for CIP process. A CIP process takes about 25
minutes , if default parameters are used. If no CIP process is performed within the time limit an entry is made in
the control system log f le. Operations after the warning does not fullf ll the type approval certif cate.
Note that it is possible to run operations during the 30 hours. Complete status information regarding CIP is
displayed in page 1.3 CIP status. A CIP process is started manually according to instruction CIP clean UVR
after ballast / deballast on page 65.
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• All valves leading flow to and from PureBallast must be opened. They are not operated by
PureBallast.
• Flow must have been selected before a process can be started, either manually or automatically.
See Flow selection on page 19.
• There must be available power for the system. If power management is integrated, this will
be handled automatically. If power management is not integrated, confirm available power
manually.
Follow the steps below:
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Deballast start-up starts, with cooling water cooling the lamps during warm-up.
3. Wait for the message “Confirm ballast pump started”. Start the pump and then press the
button in the popup to confirm the action. Note! This component is outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
Result: Cooling stops and deballasting starts.
4. When desired amount of water has been processed, press the function button Stop.
To get a smooth stop, the flow from the ballast pump can be reduced, but not more than 50 %.
Result: Ongoing process is stopped and the lamps are switched off.
5. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
6. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Book No.9028195 02 61
4.4 Perform tank stripping 4 Operating instructions
CIPpop
NOTE
A CIP cleaning process must be f nished within the time stated in the popup (30 hours from the f rst operation
after the previous CIP process). Therefore consider the time for CIP process. A CIP process takes about 25
minutes , if default parameters are used. If no CIP process is performed within the time limit an entry is made in
the control system log f le. Operations after the warning does not fullf ll the type approval certif cate.
Note that it is possible to run operations during the 30 hours. Complete status information regarding CIP is
displayed in page 1.3 CIP status. A CIP process is started manually according to instruction CIP clean UVR
after ballast / deballast on page 65.
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• All valves leading flow to and from PureBallast must be opened. They are not operated by
PureBallast.
• Stripping function must be activated in parameter p170.
• There must be available power for the system. If power management is integrated, this will
be handled automatically. If power management is not integrated, confirm available power
manually.
Follow the steps below:
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Deballast start-up starts, with cooling water cooling the lamps during warm-up.
62 Book No.9028195 02
4 Operating instructions 4.5 Pause ballast / deballast / stripping
3. Wait for the message “Confirm strip pump started”. Start the pump and then press the button
in the popup to confirm the action. Note! This component is outside the PureBallast system
control. (The popup is not displayed if the component feedback is integrated with the control
system.)
Result: Cooling stops and stripping starts.
4. When desired amount of water has been stripped, press the function button Stop.
Result: Ongoing process is stopped and the lamps are switched off.
5. Wait for the message “Stop stripping water pump”. Stop the pump and then press the button
in the popup to confirm the action. Note! This component is outside the PureBallast system
control. (The popup is not displayed if the component feedback is integrated with the control
system.)
6. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
CIPpop
NOTE
A CIP cleaning process must be f nished within the time stated in the popup (30 hours from the f rst operation
after the previous CIP process). Therefore consider the time for CIP process. A CIP process takes about 25
minutes , if default parameters are used. If no CIP process is performed within the time limit an entry is made in
the control system log f le. Operations after the warning does not fulf ll the type approval certif cate.
Note that it is possible to run operations during the 30 hours. Complete status information regarding CIP is
displayed in page 1.3 CIP status. A CIP process is started manually according to instruction CIP clean UVR
after ballast / deballast on page 65.
Book No.9028195 02 63
4.6 Heel (internal transfer) 4 Operating instructions
• This is only possible in sub process full ballast or full deballast. This is indicated by the lit
Pause button.
• Allowed in sub process full stripping if activated in parameter (p170). After defined time, the
paused process is stopped.
• Allowed length of a pause is parameter set (p138). After defined time, the paused process
is stopped.
Follow the steps below:
2. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Ongoing process is paused. The UV lamps remains on at reduced power and cooling
water is run through the UV reactor to cool the lamps. Pause mode is indicated by yellow light
under the Pause button and blinking yellow under the function button Ballast, Deballast or
Strip.
5. Wait for the message “Confirm ballast pump started”. Start the pump and press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: The process is resumed.
• This requires that a signal for heeling mode is integrated between PureBallast and the vessel’s
ISCS.
• This is only possible in sub process standby, full ballast and full deballast.
• Allowed length of heeling is parameter set (p138). After defined time, the system is stopped.
Follow the steps below:
1. Activate heeling from ISCS, which means that a heeling signal is sent to PureBallast.
64 Book No.9028195 02
4 Operating instructions 4.8 CIP clean UV reactor after ballast
/ deballast / stripping
2. In PureBallast: Wait for the message “Stop ballast water pump”. Note! This component is
outside the PureBallast system control. (The popup is not displayed if the component feedback
is integrated with the control system.)
Note: If you you need the ballast pump for heeling, confirm the request without stopping the
ballast water pump.
Result: System goes to heeling mode (ongoing process is paused). The UV lamps remains
on at reduced power and cooling water is run through the UVR to avoid overheating of the
lamps. During heeling, the yellow light under the Pause button is lit and the yellow light under
the function button Ballast or Deballast is blinking.
5. Wait for the message “Confirm ballast pump started”. Start the pump and press the button in
the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
Result: The process is resumed.
If system shut down is activated during the CIP process, the CIP liquid is drained to the CIP tank.
Water in the UV reactors is drained overboard.
• The system must be in standby mode. This means that this operation cannot be executed
during ballast or deballast.
Book No.9028195 02 65
4.9 Attend to alarms 4 Operating instructions
• We recommend that a CIP process is performed within the same ecological zone or in
international waters (200 nautical miles from the base line). This will avoid untreated water from
the UVR and the filter to enter a different ecological zone.
• Complete status information regarding CIP is displayed in page 1.4 CIP status. The page
displays remaining time for ongoing CIP cycles, remaining time before individual UV reactors
are required to be CIP:ed etc.
• If a ballast operation has been performed since the last CIP process, the process is completed
with a filter preservation, where the filter is filled up with technical water / potable water.
Follow the steps below:
2. Wait for the message “Open valves ...”. Open relevant valves and then press button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: The CIP process starts. The CIP process takes about 25 minutes , if default
parameters are used.
Note: If CIP process is started after a process the CIP process will start after 2 minutes, when
the UV lamps have been cooled.
3. Wait for the message “Close valves ...”. Close relevant valves and then press button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
An alarm or warning is indicated by a audible signal and that the icon on the alarm list tab is blinking:
3 Alarm
• Alarms will shut down ongoing process and disable start of process.
• Warnings are information to the operator and will not shut down ongoing or disable start
of process.
• An alarm or warning will activate the alarm buzzer (sound and light) on the cabinet. The sound
is silenzed by touching the buzzer, but note that the alarm is not acknowledged by this.
66 Book No.9028195 02
4 Operating instructions 4.9 Attend to alarms
NG
WARNI
!
• Never reset an alarm without first finding and attending to the problem.
• Requires login level Operator or higher.
• For color indication of alarms. See page 32.
Follow the steps below:
3. If the process continues: Consider if the process shall be terminated. Take action to eliminate
what has caused the alarm.
4. After the problem has been dealt with Press the Ack all button to acknowledge all alarms, or
press the alarm row and press Ack selected button to acknowledge only this alarm.
Result: The alarm will change color to indicate change of status. See section Page 2.1 Alarm
list in this chapter. The acknowledge time is updated, and the Normal time will be updated
when the problem is resolved.
Book No.9028195 02 67
4.10 Shut down and deactivate system 4 Operating instructions
PureBallast will shut down if the system loose power (intentionally or unintentionally) or if an alarm
is issued. Alarm has alarm ID beginning with an “A”.
Events at shutdown:
One of the following methods can be used to abort any ongoing operation and stop the system:
68 Book No.9028195 02
4 Operating instructions 4.11 Reset system after shut down
Action Method
3StopButtonBlue
System stop Press the Stop button (2) on the control cabinet door.
Result: Ongoing process is stopped and valves are returned to starting
position as fast as possible. Note: The power is still on.
System stop If an external system stop button has been installed and integrated, it
(External button) will function as the system stop above.
The system may only be reset after the reason for shut down is known. If the reason is not known,
follow the instruction Attend to alarms.
Manual on control cabinet: Turn the main breaker (1) and acknowledge the alarm in the control
system. Release the button on the control cabinet.
Automatic in LDC: Follow the instruction below if a reactor has been shut down by temperature
switch TS201-60 (alarm A137) or if the cabinet or system has been shut down by a blackout or
electrical faults in the cabinet:
1. Make sure that the main breaker (A) on the LDC door is turned on.
2. Press the blue reset button (B) on the LDC door (when the reactor has cooled down or when
the power is back on).
3. Acknowledge all alarm related to the shut down in the control system.
Book No.9028195 02 69
4.12 Operate components manually 4 Operating instructions
Valves are recommended to be operated via the PureBallast control system. It is also possible to
open/close them manually according to instruction in chapter 7. Service manual, section Operate
valves manually.
70 Book No.9028195 02
4 Operating instructions 4.13 Operate UV lamps manually
3 PopValve
4. Press (not slide) the Hand button icon to enable manual operation of the component.
Result: The open and closed buttons turn blue for operation. A hand icon is also displayed on
the component in the popup and the flow chart to indicate that it is manually operated.
5. Operate the component using the open/run (left) and closed/not running (right) buttons in
the popup.
6. Press Hand button to stop manual mode for the component and the X button to close the popup.
or
Press the X button to close the popup and let the component remain in manually set status.
The popup is closed, and a hand icon is displayed by the component to indicate it is manually
operated.
NGE R
! DA
• Manual start of the UV lamps is only allowed (and possible) when there is water in the UV
reactor (indicated by level switch LS201-29), and the water temperature is below 60 °C. All
necessary items – cooling water flow, water temperature, and power management – must be
supervised and verified by the authorized trained personnel operating the system. Inappropriate
operation of this function could seriously damage the equipment and injure personnel.
Book No.9028195 02 71
4.14 Set ship specific component ID 4 Operating instructions
1. Go to page 1.1 Overview. Press the Manual function button to activate manual mode.
4. Open, in stated order, the following valves to fill the UV reactor with water: 201-19, 404-36
and 403-35.
Result: The UV reactor is now filled with water through the cooling water line 403.
5. Wait until the UV reactor is filled with water, indicated by the level switch (LS201–29) turning
green.
7. Press the Manual mode button to enable manual operation of the UV lamps.
9. If desired, the UV lamps can be dimmed manually: Press the LPS status button in the UV
reactor popup. Press the Manual output filed, and enter desired percentage between 50
and 100 %. The LPS will give the entered percentage of full effect to the UV lamps. This is
indicated in the Power output field.
• If remote control panels (option) are used, enterd IDs will be displayed on all panels.
• Requires login level Advanced operator.
Follow the steps below:
72 Book No.9028195 02
4 Operating instructions 4.15 Export control system event log files
3 ShipIDComp
Information to be Description
exported
Event log The event log includes all important events in the PureBallast system. The
log also include components connected via the log box. Intended to be
used mainly by service technicians.
Event log - Contains a selection of the complete event log, relevant to comply with
Certif cate the IMO regulations.
Alarms and A list of all alarms and warnings that has been issued from the control
warnings system. Intended to be used mainly by service technicians.
For specific information about logged events, see section List of logged information on page 87.
Book No.9028195 02 73
4.15 Export control system event log files 4 Operating instructions
• Events are only copied, hence they will remain in the control system.
• The log and alarm files are stamped with the system name and serial number entered in page
4.5 Installation parameters.
• The easiest way of reading the log file is to use the program Visualog, but the file can also
be read in Exel.
Follow the steps below:
3 ExportLog
3. Wait for message: Insert USB in PLC. Insert a USB memory in USB PLC port on the cabinet
door.
4. Chose one of the following alternatives to decide time interval for the information to be copied:
• Recommended: Accept suggested default time interval in the Start and End fields. Default
start date is the oldest file in the system, and default end date is today’s date.
• Select the Specify time interval box, and enter desired interval in the Start and End fields.
5. Press one of the following function buttons: Events or Alarms. (The Update export is only
used when updating softwares.)
Result: The information is copied to the USB memory indicated by a green checkmark on
the button during copying.
74 Book No.9028195 02
4 Operating instructions 4.17 Restore control system settings
6. Wait for the message "Export OK" to appear. If desired, export next category of events using
the function buttons.
Result: A folder named PureBallast has been saved to the USB. It contains two sub folders:
Alarm and Event. The folder corresponding to your export choices contains a CSV file.
4. Wait for the OK / Close button to turn blue again. If the backup was successful, the last line
shall state "Backup done".
Result: A folder named PureBallast backup has been saved containing the backup files.
Book No.9028195 02 75
4.18 Set control panel IP address 4 Operating instructions
• This method shall not be used to restore parameter settings after software update.
• If you do not wish to update a certain type of setting, remove the specific file from the USB
memory before inserting the USB memory in the USB panel port on the cabinet door.
• Remove the file Parameters.csv from the USB before following this instruction.
Follow the steps below
3. Press the Restore button in page section Backup and restore, Settings to/from HMI USB.
Result: A popup is displayed and the process is started.
5. Read the second last line in popup: If the restore was successful, it shall state "Restore done".
8. The control panel must be rebooted. At the rear side of the control panel: Pull out the power
cable from the 24V DC port, and insert it again.
76 Book No.9028195 02
4 Operating instructions 4.19 Set remote control panel communication
3 IPaddress
Enter the IP address according to the list below. Also check that correct setting is done for Port
2 in the Port 2 tab.
3 IPaddress
5. Press OK.
6. Reboot the panel to update communication with the new IP address. Make sure that the new
IP address is displayed on page 4.1 System info.
7. Repeat this instruction for all installed control panels, both main and remote control panels, if
installed.
8. Follow the instruction Set remote control panel communication to activate remote control panel.
Book No.9028195 02 77
4.19 Set remote control panel communication 4 Operating instructions
• All remote control panels must be on and connected with an Ethernet cable.
Follow the steps below:
1. On the main panel in the control cabinet: Go to page 4.1 System info.
3 RCP communication
5. Press the Panel alias field for the new control panel. Use the keyboard to enter a name, for
example the location it is placed.
Note: Panel alias for all control panels shall be entered (with the same wording) in all panels
to be displayed in a correct way.
If remote control panels are not used, any added control panels shall be deleted from the list.
78 Book No.9028195 02
4 Operating instructions 4.21 Test remote interface communication
To delete a connected panel: Select it a panel in the hand side and press the delete (X) button. If a
keyboard is displayed, pres Esc to remove it.
2. Set parameters to match ISCS’s RTU server data according to the information in chapter 4.
Parameters, section 5.7 – Remote interface.
Test communication
1. Go to page 4.5 Remote interface 1. Make sure that the system is not in test mode (no
checkmark on the button). If not, press the Test mode button to deactivate it. Make sure that
Local operation is activated. If not, press the Local function button.
2. Check that the heartbeat signal is updated in both systems (06 and 77). Also check that values
are read from the PureBallast system, for example temperature (address 116 and 117).
This will confirm that the systems communicate.
Values are entered and displayed in the control system as actual values, but are sent to ISCS using
the binary numeral system. This information is found in group Data to ISCS and Cmd/status to
ISCS on page 4.5 Remote interface 1, and is indicated by a unit (m3, hour, second, kW etc).
The following addresses does not display correct values in page 4.5:
• 50 Process volume
• 114/124/134 UV reactor temperature for UV reactor 1, 2 and 3
• 115/125/135 LDC water temperature for UV reactor 1, 2 and 3
Book No.9028195 02 79
4.21 Test remote interface communication 4 Operating instructions
• 52 System pressure
• 63 Filter differential pressure
• 64 Filter inlet pressure V201–71 (Hydac filter)
• 65 Filter outlet pressure V201–72 (Hydac filter)
• 66 V201-8 setpoint
• 57058. Current time
For detailed information, see the directory of addresses.
2. Enter actual values in the in the input field for the address to send simulated information to
the ISCS. Information in decimal form, for example processed volume, is written as actual
values. Information in binary form, for example command status, is written as a bit pattern.
The key for the bit pattern is found in chapter 6. Installation description and drawings, section
System interfaces.
3. Make sure that values and status information is displayed correspondingly in the ISCS.
In the ISCS, activate input commands corresponding to the addresses displayed in page 4.5. (Note
that address 06 does not need to be tested; it was tested at the beginning of this procedure.)
2. Make sure that the command is received in page 4.5. Use the directory of addresses to see
that the bit pattern is updated correctly.
3. In the control panel, restore all changed values after the communication test. If not, commands
might be executed involuntarily, when the system is set to online again. Most important is that
address 001 displays ”00000000”.
Alarms and warnings are tested by simulation in control page 4.5 Remote interface 1 and 4.6
Remote interface 2. Use the alarm list to identify addresses and bit patterns for the alarms.
You want to simulate alarm W40 (Process pressure too low). When you find W40 in the table, you
use the column heading to see which address the alarm shall be sent to and the row heading to
see which bit in the bit pattern that shall be high. For W40 the signal shall be sent to address
902, and bit 12 shall be high.
Translate the bit to a bit pattern: Bit 12 is the 13th digit from the right (the first digit from
right is counted as zero, second digit counted as 1 etc). This gives the following bit pattern:
0010000000000000.
80 Book No.9028195 02
4 Operating instructions 4.22 Simulate power request
1. Enter the desired bit pattern in the input field for the address.
3. If common alarm and warnings are used, make sure that address 70:7 and 70:8 are updated.
It is only necessary to check this for the first alarm.
6. Press the Test mode button to set the system in online mode (no check mark on the button).
Press the Remote function button if you want to activate remote control.
2. Press the hand button in the Request column for a row with power step for desired number of
UV reactors. For details, see description of page 1.4 – Power request.
3. Press the Request button for the row to simulate power request signal.
Result: Status is updated to “Requested” in the Request column.
7. Press the Set run button to deactivate the simulate running signal.
Book No.9028195 02 81
4.25 Fine tune flow control 4 Operating instructions
1. Pull out the power cable from the 24V DC port on the rear side of the control panel. And
then reconnect the power cable.
For remote control panels: Use the Power button to turn off, and then turn on the power.
2. Wait for a sandglass to appear and disappear. When it appears again, press a finger on the
screen and hold it there for approximately 20 seconds.
Note: Keep holding the finger on the screen even when the panel turns white with a red
message “Welcome to ...”.
3. Wait for the screen to turn completely white with a message “Tap anywhere on the screen
within 10 seconds”. Release the finger and tap once on the screen.
During backflush, the control valve is PID regulated based on input from the pressure transmitter
PT201-16 to maintain stable pressure for efficient backflush. Desired pressure is defined in
parameter p304.
82 Book No.9028195 02
4 Operating instructions 4.25 Fine tune flow control
The purpose is to adjust the movement of V201-8 when it changes from flow controlled regulation to
pressure controlled regulation which it does during backflushing of the filter. The first goal is that
the valve travels as fast as possible to a steady position where it creates required pressure (as
defined in parameter p304).
The second goal is to shorten the time from backflush trigger to start of actual backflush. This is
done by shortening the time in p310 (Backflush initial delay) that is done after the movement of
V201-8 has been calibrated.
This instruction shall be read together with the example after the instruction.
1. Perform a backflush.
2. Open page 3.1 Trend (15 min) and analyze the trend curve for V201-8.
Before the backflush, the valve shall move as fast as possible to a steady position where it
creates required pressure. If not, parameter p166 shall be adjusted.
3. Adjust parameters, and perform a new backflush.
4. See if the curve has improved. Repeat until satisfactory result has been achieved.
5. See if the time between backflush initiation and backflush can be shortened . If possible, adjust
parameter p310. See parameter p310 in the example below.
Example
In this example, five backflushes are performed. After the first four backflushes, the PID parameters
where changed for pressure regulation to adjust the movement of the control valve V201-8 before
the backflush.
The illustration is taken from page 3.1 Trend (15 min). Backflush is indicated by the movement
of the backflush valve 309-1 (pink line) and the movement of control valve V201-8 is indicated
by the blue line.
1st backflush Parameter p166 is set to 0.30. But it takes too long time for V201-8 to get into
position to create desired pressure (1). The curve slops downwards in a long bend,
which means that it takes time for V201-8 to find correct position.
2nd backflush Parameter p166 was adjusted to 0.6. This made the valve movement much faster
in the beginning, shown by the steep curve at the beginning. But then a more
slow regulation starts, shown by the soft slope (2). This was a change for the
better, but not enough.
3rd backflush Parameter p166 was increased to 1.2 which resulted in a satisfactory valve
movement (3): A fast movement, followed by a minor adjustment. A small
overcompensation can be noted (curve goes too low), that might be adjusted by
decreasing the value to 1.1.
Book No.9028195 02 83
4.25 Fine tune flow control 4 Operating instructions
4th backflush During the first backflushes, parameter p310 was set to 60 seconds. The parameter
defines time between a backflush is triggered and it actually starts. But now, when
V201-8 is calibrated, this time can be shortened. Before the fourth backflush
parameter p310 is set to 15 seconds. The shortened time span is indicated by
the braces in the illustration.
5th backflush No parameter was changed. This backflush is only showed to confirm that the
parameter setting is OK and that the curve (5) for V201-8 is basically the same as
for backflush three and four (3 and 4).
3 CalibExample
When the flow in the system is too high, PureBallast’s control valve V201-8 will close to reduce flow.
If the V201-8 closes more than a parameter set degree, the control system sends a signal requesting
the ballast pump to reduce the speed (and so the flow). When the flow is reduced, V201-8 can open.
Valve V201-8 operates (open/closes) in a range between a parameter set value (p157) and 100 %,
where default is 70 %. Within this range, flow is regulated by V201-8 without cavitation.
84 Book No.9028195 02
4 Operating instructions 4.25 Fine tune flow control
This instruction shall be read together with the example after the instruction.
1. Start a ballast process. Wait untill the system is in mode Full ballast. Listen for cavitation
noises at V201-8.
If cavitation, go to step 2. It not, go to step 5.
2. Go to page 5.2 main parameters 2.
3. Increase parameter p157 in steps of 5 % at a time. After each change, wait until the parameter
change take effect (a couple of minutes). Listen for cavitation noises at V201-8. Note: The
effect can not be observed during backflush, since the external feed function is disabled.
4. Stop raising when the noises from cavitation stops.
5. Look at the movement of V201-8. If the movement is continuously changing and the curve is
unstable, parameter p156 must be adjusted. The goal is to get a smooth regulation with long
and steady curves.
6. Increase parameter p156 in steps of 1 second per % at a time. After each change, wait until the
parameter change take effect (a couple of minutes).
7. Stop when the regulation curve flattens out and the trend curve is long and smooth. See
exemple below.
8. Stop the process.
9. Start another ballast operation. Verify settings during startup and process.
10. Perform a manual backflush. Verify settings during and after backflush.
Note: When the backflush is done, V201-8 is closed under 70 % (defined in parameter p157).
The external feed control signal is lowered to request less flow from the pump, so that V201-8
can open. Less flow is needed after the backflush, since the the filter is clean.
11. Stop the process.
12. Start a deballast. Verify settings during startup and process.
Example
In this example, parameter p156 External feed change rate is adjusted to get a stable regulation.
Area 1 Parameter p156 was set to 2 s / % when process was started. The curves for
V201-8 (blue) and external feed (black) signal are chasing each other. The reason
is that the request signal changes too fast which makes V201-8 compensate, which
affects the signal in return.
Area 2 Parameter p156 is raised to 6 seconds which makes the request signal change
more slowly, which results in a smooth movement of V201-8 when regulating the
external flow.
Book No.9028195 02 85
4.25 Fine tune flow control 4 Operating instructions
3 CalibExampleExtFeed
86 Book No.9028195 02
5 List of logged information
Alarm history and important events are logged in the control system. The log also include
components connected via the log box (optional).
The control system store all alarms and relevant events for at least 24 months. The memory has
a vast safety margin but when it is full, data will be deleted starting with the oldest data. Logged
information can be exported to a USB memory stick. See Export control system log files on page 73.
The GPS stamp column indicates if the event is stamped with GPS position (Y=yes, N=no). All
events relevant to the IMO certificate are GPS stamped
Book No.9028195 02 87
5.1 Event log 5 List of logged information
310 E-stop N
320 Power tuned on. PureBallast has been powered off for N
[x]days:[y]hrs:[z]min
Time of how long the power has been switched off
88 Book No.9028195 02
5 List of logged information 5.1 Event log
Book No.9028195 02 89
5.1 Event log 5 List of logged information
90 Book No.9028195 02
5 List of logged information 5.1 Event log
5010 Log box: V01 Closed position change: [value]. 1=Closed. 0=Not N
closed.
5011 Log box: V01 Open position change: [value]. 1=Open. 0=Not open. N
5020 Log box: V02 Closed position change: [value]. 1=Closed. 0=Not N
closed.
5021 Log box: V02 Closed position change: [value]. 1=Closed. 0=Not N
closed.
Book No.9028195 02 91
5.1 Event log 5 List of logged information
6 Detailed process description
This section gives a detailed description of the PureBallast processes. The processes are divided
into three main processes, with sub processes, with indications of automatic and manually initiated
steps.
• Ballast
• Deballast
• CIP
• Deactivate system
• Change flow
• Manual mode.
Book No.9028195 02 93
6.2 Ballast process 6 Detailed process description
3 BallastProcess
2. Request from control system to open overboard (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
3. Overboard valve opened by operator and confirmed in control system. (Handled automatic, if
external component signal is enabled.)
Component activities:
94 Book No.9028195 02
6 Detailed process description 6.2 Ballast process
5. UV lamp warming
Component activities:
• Start UV lamps (100 %). If all lamps are not lit within p212, process is stopped.
• Start counter: UV lamp runtime.
• Start LDC fan.
• Set V201-8 (control valve) to 50 %.
7. Time p210 after all lamps are lit: Request from control system to start ballast water pump
(outside PureBallast system). (Handled automatic, if external component signal is enabled.)
8. Ballast water pump started by operator and confirmed in control system. If not confirmed
within 20 seconds, lamp power is reduced to 50 %. If not confirmed within p141 (including the
20 seconds), process is stopped.
1. Component activities:
Book No.9028195 02 95
6.2 Ballast process 6 Detailed process description
• Start automatic control of control valve (V201-8) based on input from the pressure transmitter
• Start filter motor M709-43.
• Start backflush pump P309–1 (optional)
• After p319 seconds, open V309-1
2. Filter backflush is performed for p308 seconds.
Component activities:
• Stop M709-43
• Close V309-1
• Stop backflush pump P309–1 (optional)
• Start automatic control of control valve (V201-8) based on input from the flow meter.
3. Differential pressure check. If necessary, the process is repeated.
1. Operator pause the ballast process manually. Pause can also be initiated by an external signal,
for example when heeling is initiated from the ISCS. In this case, the process is resumed
automatically when the heeling signal is deactivated.
2. Set V201-8 (control valve) to parameter (p113) set opening percent.
3. Request from control system to stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
4. BW pump stopped by operator and confirmed in control system. Component activities:
6.
Resume ballasting
Operator resumes the ballast process manually.
Component activities:
96 Book No.9028195 02
6 Detailed process description 6.2 Ballast process
7. Request from control system to start ballast water pump” (outside PureBallast system).
(Handled automatic, if external component signal is enabled.)
8. BW pump started by operator and confirmed in control system. (Handled automatic, if external
component signal is enabled.)
Book No.9028195 02 97
6.3 Deballast process 6 Detailed process description
3 DeBallastProcess
98 Book No.9028195 02
6 Detailed process description 6.3 Deballast process
5. UV lamp warming
Component activities when power has been granted:
• Start UV lamps (100 %). If all lamps are not lit within p212, process is stopped.
• Start counter: UV lamp runtime.
• Start LDC fan.
• Set V201-8 (control valve) to 50 %.
8. Time p210 after all lamps are lit: Request from control system to start ballast water pump
(outside PureBallast system). (Handled automatic, if external component signal is enabled.)
9. BW pump started by operator and confirmed in control system. If not confirmed within 20
seconds, lamp power is reduced to 50 %. If not confirmed within p141 (including the 20
seconds), process is stopped.
Component activities:
Book No.9028195 02 99
6.3 Deballast process 6 Detailed process description
1. Operator pause the deballast process manually. Pause can also be initiated by an external
signal, for example when heeling is initiated from the ISCS. In this case, the process is resumed
automatically when the heeling signal is deactivated.
Component activities:
4. Resume deballasting
Operator resume the deballast process manually.
Component activities:
5. Request from control system to start ballast water pump” (outside PureBallast system).
(Handled automatic, if external component signal is enabled.)
6. BW pump started by operator and confirmed in control system.
Component activities:
3 StrippingProcess
5. UV lamp warming
Component activities when power has been granted:
• Start UV lamps (100 %). If all lamps are not lit within p212, process is stopped.
• Start counter: UV lamp runtime.
• Start LDC fan.
• Open V201-20 (reactor outlet)
• Set V201-8 (control valve) to 50 %.
8. Time p210 after all lamps are lit: Request from control system to start stripping pump (outside
PureBallast system). (Handled automatic, if external component signal is enabled.)
9. Stripping pump started by operator and confirmed in control system. If not confirmed within
20 seconds, lamp power is reduced to 50 %. If not confirmed within p141 (including the
20 seconds), process is stopped.
Component activities:
1. Component activities when minimum process flow established (p172), indicated by FIT201-1:
1. Operator adjusts the certified flow manually from the control system.
2. Component activities:
4. Resume stripping
Operator resume the stripping process manually.
Component activities:
5. Request from control system to start stripping pump” (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
3 CIPprocess
• - Stop P321-5
- Close V571-1 (CIP, deaeration valve)
- Close V460-2 (CIP, drain valve)
- Close V321–2 (UV reactor, upper CIP return valve)
- Close V320–4 (UV reactor, lower CIP return valve).
1.
Component activities:
1. Component activities:
2. Component activities when UV reactor is empty, indicated by LS201-29 + drain time (p200):
6.5.8 Repeat
When CIP process is done for the first UV reactor, the remaining UV reactors with status CIP
required are processed in the same way.
1.
Component activities when all required UV reactors are processed:
• - Open V310-1
- Open V309-1
- Start M709-43.
2. Component activities after the filter is filled:
• - Stop M709-43
- Close V309-1
- Close V310-1.
3. Request from control system to close overboard valve (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
4. Overboard valve closed by operator and confirmed in control system.
• Requires login level 2. The Manual mode button is only displayed for login level 2.
• Flow in pipes is not indicated in flow chart.
• Can only be activate from standby mode.
• No automatic processes can be run.
If another operator take over command by logging in on another control panel, manual mode is
deactivated, and the system returns to standby.
1.1 Introduction
This is a quick guide to the most common routines performed in the PureBallast control system.
More detailed instructions are found in the PureBallast manual.
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• Flow must have been selected before a process can be started. If the Auto button is selected
(checkmark) maximum flow is automatically selected, and flow can only be changed during
process according to instruction Change ballast / deballast / stripping flow. If parameter the
Auto button is deselected (no checkmark) last selected flow is used. Otherwise, flow is selected
on page 1.1 Overview or 1.2 UVR and flow selection.
1.2 Ballast, deballast and stripping
Follow the steps below
3. Wait for the message “Open valves ...”. Open relevant valves and then press the button in
the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
4. Wait for the message “Confirm ballast pump started”. Start the pump and then press the button
in the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
5. When desired amount of water has been processed, press the function button Stop to end
the process.
6. Wait for the message “Close valves ...” and “Stop ballast water pump”. Handle accordingly.
(The popups are not displayed if the component feedback is integrated with the control system.)
1.4 CIP clean UVR 1 Quick guide to PureBallast operations
7. Wait for the ”Start CIP” popup. Choose to start a CIP or wait maximum the time stated in
the popup.
CIPpop
An alarm is indicated by a audible signal and by a blinking warning icon in the control panel.
• Never reset an alarm without first finding and attending to the problem.
Follow the steps below:
3. If the process have stopped: Take action to eliminate what has caused the alarm.
4. If the alarm is caused by a faulty UVR module, the ballast/deballast process has to be restarted
with another UVR according to the Perform ballast instruction.
5. If the process continues: Consider if the process shall be terminated. Take action to eliminate
what has caused the alarm.
Press the Ack selected or Ack all button after the problem has been dealt with.
• The system must be in standby mode. This means that this operation cannot be executed
during ballast or deballast.
• Complete status information regarding CIP is displayed in page 1.4 CIP status. The page
displays remaining time for ongoing CIP cycles, remaining time before individual UVRs are
required to be CIP:ed etc.
1 Quick guide to PureBallast operations 1.5 Export control system log files
3. Wait for the message “Open valves ...”. Open relevant valves and then press button in the
popup to confirm the action.
Result: The automatic CIP cycle starts. The CIP cycle takes about 25 minutes per UVR.
4. Wait for the message “Confirm overboard valve closed”. Close the valve and then press button
in the popup to confirm the action.
3. Wait for message: Insert USB in PLC. Insert a USB memory in USB PLC port on the cabinet
door.
4. Chose one of the following alternatives to decide time interval for the information to be copied:
• Accept suggested default time interval in the Start and End fields. Default start date is the
oldest file in the system, and default end date is today’s date.
• Select the Specify time interval box, and enter desired interval in the Start and End fields.
5. Press one of the following function buttons: Events, Cert events or Alarms.
Result: The information is copied to the USB memory indicated by a green checkmark on
the button during copying.
6. Wait for the message "Export OK" to appear. If desired, export next category of events using
the function buttons.
Result: A folder named PureBallast has been downloaded. It contains three sub folders:
Alarm, Cert and Event. The folder corresponding to your export choice contains a CSV file.
3
1 Introduction
This chapter contains information about parameters in the control system and parameter controlled
compoents. It covers:
Book No.9028195 02 5
1 Introduction
2 Control system parameters
This section describes all parameters set in the PureBallast control system.
NOTE
No icon Parameter should normally be left alone. If there are specific reasons, the
parameter may be changed.
p000 Parameters in bold can only be changed by login level AlfaLaval. Parameters
in normal text can be changed by login level Advanced operator.
Book No.9028195 02 7
2.1 Introduction to parameters and parameter 2 Control system parameters
settings
2. To see allowed range (maximum and minimum values) and change setting, press the blue
button (with the parameter ID). A button pair is displayed.
4 ParaIntervalSet
Press the ≤ ≥ sign to display range. Entered parameter value must be within defined setting
range.
4 MinMax
4. Enter the setting and confirm by touching the Enter button. To close the keyboard without
saving data, touch the Esc button.
If the parameter is set with a drop down menu, select desired choice by touching the value.
Result: The setting is saved directly, it is now safe to leave the page.
8 Book No.9028195 02
2 Control system parameters 2.2 Page 5.1 – Main parameters 1
4 5.1 USCG
p100 High pressure, 7.00 1–10 bar Setpoint for shut down due to high
shutdown trigger pressure at PT201-16. Default value
(PT201-16) shall be used for standard system.
p101 High pressure, 6.00 0–10 bar Setpoint for warning due to high pressure
warning trigger at PT201-16. Default value shall be used
(PT201-16) for standard system.
Book No.9028195 02 9
2.2 Page 5.1 – Main parameters 1 2 Control system parameters
p103 Low pressure, 0.1 -1–2 bar Setpoint for warning due to low pressure
warning trigger at PT201-16.
(PT201–16)
p104 Pressure range 0 to N/A bar Defines range for pressure transmitter
for PT201–16 10 PT201–16. Set according to range
printed on the transmitter.
4 Must Alternatives:
0 to 10
-1 to 15
p113 Min % open for 20 10–100 % During ballast and deballast, valve
V201-8 V201–8 handles the automatic pressure
and flow control.
p116 Low flow shut 10 10–90 % Set point for shut down due to low flow,
down limit defined as percent of UVR capacity.
(FIT201-1)
4 MustNot
p117 Max delay of CIP 6 0–24 hrs Define max delay, in hours, before a CIP
cycle, hours process must be performed after ballast
or deballast.
4 MustNot
p118 Max delay of CIP 1 0–30 day Define max delay, in days, before a CIP
cycle, days process must be performed after ballast
or deballast.
4 MustNot
p119 Valve travelling 5 1–10 sec Maximum time for V201–8 to go from
time for 201-8 opened to closed, and vice versa, before
a warning is issued.
10 Book No.9028195 02
2 Control system parameters 2.2 Page 5.1 – Main parameters 1
p120 Flow PID 0.30 0.00 N/A Defines proportional gain (Pf) value used
proportional gain – for PID regulation of V201–8 during
10.00 ballast and deballast.
p121 Flow PID integral 7.00 0–100 sec Defines integral time (If) value used for
time PID regulation of V201–8 during ballast
and deballast.
p122 Flow PID 0.0 0.0–100.0N/A Defines derivate gain (Df) value used for
derivative gain PID regulation of V201–8 during ballast
and deballast.
p138 Timeout: Time 5 1–30 min Defines maximum time a ballast and
in Pause before deballast process can be manually
going to Stop paused. After defined time, the process
is stopped.
p140 Timeout: Request 5 1–30 min Time the control system will wait for
"Open overboard confirmation signal from ISCS, hard
valve" wire or manually in popup before
displaying message that operation was
not performed.
p141 Timeout: Request 1 1–3 min Time the control system will wait for
"Start BW confirmation signal from ISCS, hard wire
pump/strip pump" or manually in popup. After that the
process is stopped.
p143 Timeout: Power 60 1–300 sec Time the control system will wait for
granted signal not confirmation signal from ISCS that the
received operation was performed.
Book No.9028195 02 11
2.3 Page 5.2 – Main parameters 2 2 Control system parameters
4 5.2 USCG
p128 Max time 60 15–240 Sec Define max delay before the system
communication shuts down after communication is
loss PLC/remote lost between the PLC and the remote
interface interface (optional). The value must be
greater than the heartbeat signal interval
defined in the ISCS.
12 Book No.9028195 02
2 Control system parameters 2.3 Page 5.2 – Main parameters 2
p129 Booster pump Not N/A Drop Defines if an LDC cooling water pump
(P401-1) for LDC used list or closed cooling unit is used to create
cooling water sufficient cooling water flow to the LDC.
4 Must Alternatives:
– Not used.
– External: Pump started by signal
from PureBallast control cabinet: Power
supply with over current protection
relay and contactors and are handled
externally.
– Internal: Pump completely controlled
from PureBallast control cabinet:
Start signal and power supply with
over current protection relays and
contactors from control cabinet. It is still
possible to connect pumps according to
configuration 1.
p130 Booster pump Not N/A Drop Defines if an UVR cooling water pump
(P403-1) for used list is used to create sufficient cooling water
reactor cooling flow to the UV reactor.
water
4 Must Alternatives:
– Not used.
– External: Pump started by signal
from PureBallast control cabinet: Power
supply with over current protection
relay and contactors and are handled
externally.
– Internal: Pump completely controlled
from PureBallast control cabinet:
Start signal and power supply with
over current protection relays and
contactors from control cabinet. It is still
possible to connect pumps according to
configuration 1.
Book No.9028195 02 13
2.3 Page 5.2 – Main parameters 2 2 Control system parameters
p132 Remote interface Not N/A Drop Defines if remote interface (optional) is
via modubus used list used and connected via modbus.
p135 External system Not N/A Drop Defines if an external system stop button
stop used list (or signal) is installed.
p137 Hide Pause Acti- N/A Drop Defines if the Pause button is visible or
button vated list hidden in the control system. If activated,
the button is hidden.
14 Book No.9028195 02
2 Control system parameters 2.3 Page 5.2 – Main parameters 2
p160 GPS time Acti- N/A Drop Only valid if RMC protocol is used for
synchronization vated list GPS integration.
via RMC-protocol
If activated, time and date in the control
system is retrieved from vessel’s GPS.
p161 Time interval for 1.0 0.1 – Min. Time interval to update the amount (m3)
log event 331 60.0 of ballast water treated in log file.
p162 Time interval for 1.0 0.1 – Min. Time interval to update the amount (m3)
log event 341 60.0 of deballast water treated in log file.
p163 Additional bypass Not N/A Drop Defines if an additional bypass valve is
signal 1 used list used. The signal gives information if the
valve is opened during process, so that
PureBallast is bypassed.
4 Must
p164 Additional bypass Not N/A Drop Defines if a second additional bypass
signal 2 used list valve is used. The signal gives
information if the valve is opened during
process, so that PureBallast is bypassed.
4 Must
p165 Additional bypass Not N/A Drop Defines if a third additional bypass valve
signal 3 used list is used. The signal gives information if
the valve is opened during process, so
that PureBallast is bypassed.
4 Must
Book No.9028195 02 15
2.3 Page 5.2 – Main parameters 2 2 Control system parameters
p166 Pressure PID 0.60 0.00 – N/A Defines proportional gain (Pf) value used
proportional gain 10.00 for PID regulation of V201–8 during
backflush.
p167 Pressure PID 7.0 0.0 – sec Defines integral time (If) value used
integral time 100.0 for PID regulation of V201–8 during
backflush.
p168 Pressure PID 0.0 0.0 – N/A Defines derivate gain (Df) value used
derivate gain 100.0 for PID regulation of V201–8 during
backflush.
4 MustNot
p172 Minimum flow 10 7–90 % Set point for shut down due to low flow,
when stripping defined as percent of certified flow.
(FIT201–1)
4 MustNot
16 Book No.9028195 02
2 Control system parameters 2.3 Page 5.2 – Main parameters 2
p173 Stripping certified Not N/A Drop Defines maximum flow during stripping.
for full flow used list
If Activated: Max flow during stripping
is 1000 m3/h per UVR used (which is
4 Must defined in parameter p171).
Book No.9028195 02 17
2.4 Page 5.3 – UVR parameters 2 Control system parameters
4 5.3 USCG
p200 Timeout: UV 2 1–10 min Time the control system will wait for
reactor draining confirmation that an UV reactor is
drained before an alarm is issued.
Recommended setting: Approximately 1
4 Must minute more than actual drain time.
p201 Timeout: Reactor 2 1–10 min Time the control system will wait for
cooling water confirmation that cooling water has filled
(LS201-29) the UV reactor before an alarm is issued.
4 Must
4 MustNot
p204 Low temp, -2 -5–40 ºC Setpoint for low water temperature alarm,
alarm trigger indicated by temperature transmitter in
(TT201-33) the UV reactor.
4 MustNot
18 Book No.9028195 02
2 Control system parameters 2.4 Page 5.3 – UVR parameters
p206 Alarm delay for 5 0–10 sec Delay before alarm is issued after
sensor TT201-33 setpoint temperature (p202 and p204) is
reached.
p208 Timeout: CIP 5 1–15 min Setpoint for max time to fill an UV reactor
fluid fill-up time with CIP liquid during CIP process before
UV reactor an alarm is issued.
p210 UV lamp warm-up 90 0–90 sec Warm up time for UV lamps before full
time ballast, deballast or stripping starts.
4 MustNot
p211 UV lamp cooling 300 180–600 sec Cooling time for UV lamps after ballast
time or deballast.
4 MustNot
p212 Timeout: UV 70 10–70 sec Time the control system will wait for
lamp ignition confirmation signal that UV lamps are
ignited. If no lamps are ignited or if
less lamps than set in parameter p213
4 MustNot are ignited, the UV reactor will be
automatically stopped.
4 MustNot
p215 Alarm delay for 5 0–10 sec Delay before shutdown when there is no
LS201-29 water in an UV reactor, indicated by level
switch in UV reactor (LS201-29).
4 MustNot
p216 Timeout: Fluid 5 2–10 min Setpoint for max time to fill an UV reactor
fill-up time UV with technical water / potable water
reactor during CIP process before an alarm is
issued.
Book No.9028195 02 19
2.4 Page 5.3 – UVR parameters 2 Control system parameters
p231 Cabinet 40.0 20.0 – °C Setpoint for LDC cooling fan regulation.
temperature 60.0 When the temperature is below setpoint,
low threshold the fan is running at 30 % of full effect.
(TT401-2)
4 MustNot At setpoint the fan effect is increased
proportional to temperature from 30 % up
to 100 % at temperature set in p232.
p232 Cabinet 45.0 20.0 – °C Setpoint for running the LDC cooling fan
temperature 60.0 at 100 %.
high threshold
(TT401-2)
4 MustNot
p234 UV control 0.10 0.00 – N/A Defines proportional gain (Pf) value used
proportional gain 100.00 for PID regulation of UV lamp effect.
p235 UV control 15 0–100 sec Defines integral time (If) value used for
integral time PID regulation of UV lamp effect.
4 MustNot
20 Book No.9028195 02
2 Control system parameters 2.5 Page 5.4 – Filter parameters
4 5.4 USCG
p300 High filter 3 1–10 bar Setpoint for shut down due to high
diff. pressure differential pressure over the filter.
shutdown trigger
4 MustNot
p301 High filter 1.5 0.0- bar Setpoint for high pressure warning,
differential 2.0 indicated by pressure transmitter in the
pressure, filter.
warning trigger
4 MustNot
Book No.9028195 02 21
2.5 Page 5.4 – Filter parameters 2 Control system parameters
p304 Pressure 2.50 1.00– bar Defines desired pressure for efficient
setpoint during 5.00 backflushing.
backflush
When a backflush is triggered, control
4 Must valve V201–8 will regulate to obtain this
pressure. After time set in parameter
p310 the backflush will start, regardless of
if the pressure has been reached.
p305 Backflush 0.50 0.00– bar Setpoint for automatic start of filter
trigger, 2.00 backflush due to dirt in the filter, indicated
differential by high differential pressure over filter
pressure (PT201-71 and PT201-72).
22 Book No.9028195 02
2 Control system parameters 2.5 Page 5.4 – Filter parameters
p310 Backflush initial 5 0–60 sec Defines how long time that should pass
delay from a backflush is triggered until is
actually started.
p311 Backflush delay 2.0 0.0– sec Defines for how many seconds the
(p305 during x 10.0 differential pressure defined in p305 must
sec). last, before automatic backflush starts.
p313 Differential 5 0–30 sec Time constant for low pass filter used for
pressure the differential pressure over the filter.
measurement The low pass filter is used to smoothen
filter the effect of sudden changes in differential
pressure (primarily pressure peaks after
completed backflush).
p315 Filter type 500 100 – m3/h Parameter p314 should be set before this
6000 parameter. Available alternatives depend
on selection in p314.
Book No.9028195 02 23
2.5 Page 5.4 – Filter parameters 2 Control system parameters
4 Must Alternatives:
-1 to 9
-1 to 15
p318 Backflush pump Not N/A Drop Defines if an LDC cooling water pump
(P309–1) used list (optional) is used to create sufficient
backflush flow in pipe 309.
4 Must Alternatives:
– Not used.
– External: Pump started by signal from
PureBallast control cabinet: Power supply
with over current protection relay and
contactors and are handled externally.
– Internal: Pump completely controlled
from PureBallast control cabinet: Start
signal and power supply with over current
protection relays and contactors from
control cabinet. It is still possible to
connect pumps according to configuration
1.
p323 Backflush pump Not N/A Drop Defines if the backflush pump is used
during filter used list during filter preservation (when the water
preservation is drained from the filter via pipe 309 and
filled with new water via pipe 310.2. The
backflush pump should not be used if the
filter is emptied.
24 Book No.9028195 02
2 Control system parameters 2.6 Page 5.5 – CIP parameters
4 5.5 USCG
p400 CIP cycle time 15 1–60 min Duration of circulation of CIP liquid
during a CIP process.
4 MustNot
Book No.9028195 02 25
2.7 Page 5.6 – Installation parameters 2 Control system parameters
4 5.6 USCG
System name N/A N/A N/A Possibility to enter a system name for
the system, for example Vessel name
when logged in as login level Advanced
operator or higher. If two systems is
4 Must installed information about starbord and
port side.
fisk
26 Book No.9028195 02
2 Control system parameters 2.7 Page 5.6 – Installation parameters
4 Must
p112 Maximum flow 1200 0– m3/h The parameter shall be set according to
(FIT201-1) 3300 pipe dimension for the flow meter pipe.
p213 Allowed number 0 0–1 No. If more lamps than set in this parameter
of failed UV are broken, it is not allowed to start a
lamps per UV new operation.
reactor
4 MustNot If a UV lamp fails during ongoing
operation, the flow is set 80 % in IMO
mode and 50 % in USCG mode of flow
capacity. The UV lamps are lit to 100 %.
Book No.9028195 02 27
2.7 Page 5.6 – Installation parameters 2 Control system parameters
p217 UV reactor size 300 N/A Drop Defines size of the UV reactor, defined
(m3/h) list as max capacity (m3/h).
Alternatives: 300, 600 and 1000.
4 Must
p150 Ex proof system Not N/A Drop Defines if the Ex proof version of
used list PureBallast is installed. This affects
both installation and control system.
p151 Ex-I barrier fault Not N/A Drop Defines if alarm for barrier box is
used list activated.
28 Book No.9028195 02
2 Control system parameters 2.7 Page 5.6 – Installation parameters
p180 USCG system Not N/A Drop Defines if the system is an USCG
used list system according to the system plate
on the control cabinet. If activated, it
is possible to run the system in USCG
4 Must mode and IMO mode. This is changed
by the IMO and USCG function buttons.
p181 USCG high Not N/A Drop Defines if the high performance version
performance used list of PureBallast is activated.
(HP)
Defines if the system is an USCG HP
4 Must system according to the system plate
on the control cabinet. If activated, it
is possible to run the system in USCG
mode and IMO mode. This is changed
by the IMO and USCG function buttons.
p500 Log box Not N/A Drop Defines if the log box (optional ) is
used list installed to monitor and log external
valves and pumps, that are not part of
Alfa Laval’s scope of supply.
4 Must
Book No.9028195 02 29
2.8 Page 5.7 – Remote interface 2 Control system parameters
4 5.7 USCG
Parameters for the ISCS modbus RTU server data shall be set according to the information below.
p700 Interface type RS485 N/A Drop Defines communication (cable) type
list used for communication between the
ISCS and PureBallast.
30 Book No.9028195 02
2 Control system parameters 2.8 Page 5.7 – Remote interface
p701 Baud rate 9600 N/A Drop Defines baud rate in bits per second.
list
The parameter can be changed, but
it is not recommended. Note, that the
information must be the same in ISCS
and PureBallast control system.
p703 Data bits 8 N/A Drop Defines data bits per character.
list
Alternatives: 7 or 8.
4 MustNot
4 MustNot
Book No.9028195 02 31
2.8 Page 5.7 – Remote interface 2 Control system parameters
3 Lamp power supply (LPS)
parameters
This section describes the parameters settings for the LPSs installed in the lamp drive cabinet (LDC).
DIP switch settings are made for each LPS for individual identification.
Switch 1-3 shall always be in position off. Switch 4-8 is set to identify the individual LPS according
to the table below. Only position ON is indicated. For empty cells in the table, the switch shall be
in position OFF.
LPS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1–16
SW 1
SW 2
SW 3
SW 4 ON
SW 5 ON ON ON ON ON ON ON ON
SW 6 ON ON ON ON ON ON ON ON
SW 7 ON ON ON ON ON ON ON ON
SW 8 ON ON ON ON ON ON ON ON
Example
Book No.9028195 02 33
3.2 Change DIP switch setting 3 Lamp power supply (LPS) parameters
4 LPSdip
NGE R
! DA
• Switch off the main breaker on the LDC door. The LPS has high voltage/power (600 V) inside
and on the lamp power connector, even when UV lamps are not lit.
• The LDC contains a fan, which can cause injury if in operatoin.
Follow the steps below
1. Unscrew the plastic lid (1) over the DIP switches on the fron of the LPS.
34 Book No.9028195 02
3 Lamp power supply (LPS) parameters 3.2 Change DIP switch setting
7 LPSdip
2. Use a small screw driver to change position of the swithces according to the table under
instruction DIP switch settings.
Book No.9028195 02 35
3.2 Change DIP switch setting 3 Lamp power supply (LPS) parameters
4 Fuse settings for filter motor
and installed (optional) pump
motors
Follow this instruction to change the fuse settings for filter motor M709–43 (F2) and installed
(optional) pump motors P401-1 (F3), P309-1 (F4) and P403-1 (F5) in the control cabinet.
1. On the filter motor and installed (optional) pump motors: Find area on the mark plate where
information is displayed for the frequency used for the system (50 or 60 Hz).
3. Look at interval for Imax amp setting (A), also stated as an interval.
4. Make an estimation for Imax amp setting, so that it “match” the voltage in the range from
min to max.
7. Check that the setting is correct according to the LEDs. Compare to the table below.
4 FuseSettingBoosterPumps
Book No.9028195 02 37
4 Fuse settings for filter motor and installed
(optional) pump motors
5 Flow transmitter parameters
Book No.9028195 02 39
Chapter: 5. Alarms and faultfinding
System manual — PureBallast 3.1 1000
USCG
3
1 Introduction
This chapter covers information about alarms and warnings, together with information about how
to solve the problems causing the alarms to trip. The chapter also contains a list of solutions for
problems that may occur, but that is not indicated by any system.
• control system
• lamp power supply (LPS)
• flow meter (with fault finding instruction)
• I/O system and X20 modules.
See chapter 3. Operating instructions and control system description to find information about
the alarm pages and how to attend to alarms.
Book No.9028195 02 5
1 Introduction
2 List of alarms and warnings
This section lists all alarms and warnings related to the PureBallast system.
Alarms
All alarms are displayed in the control panel’s page 2.1 Alarm list and are sorted in order of
occurrence; most recent alarm at the top of the list.
Book No.9028195 02 7
2.1 Control system 2 List of alarms and warnings
Column in Description
table
- A = Alarms stop the ongoing process, which can be restarted after the
problem has been attended to.
- W = Warnings are notification of a status change or a problem. Warnings
allow the process to continue.
Alarm text / The text displayed in the control system. Note that UV reactor number is
Problem indicated by “x” in the table, instead of the actual UV reactor number. In the
control system alarm text, the actual UV reactor number is stated for the UV
reactor concerned.
For problems not indicated by an alarm, the text gives a general explanation
of a problem that can occur.
Trigger / Trigger: Source of the alarm or warning, identified by the input sensor’s item
Parameter number or equivalent.
Parameter: The parameter controlling the alarm, when applicable.
Delay: Time before the alarm is activated after the condition of the alarm is met.
Comments: Additional information or explanations.
8 Book No.9028195 02
2
Alarms and warnings — PureBallast control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A01 Process Trigger: PT201-16 Delay: 30 sec. Ballast water pump Check pressure and flow from
Book No.9028195 02
pressure too Parameter: p100 gives too high ballast pump(s). If the pressure
high (PT201- Comment: Pressure pressure. exceeds set value: Adjust incoming
16). Automatic transmitter PT201-16 pressure to PureBallast.
stop. indicates pressure
higher than set in Valves in the system Control that correct valves are
parameter p100. after pressure functioning and opened for current
List of alarms and warnings
9
Control system
10
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A03 Process Trigger: PT201-16 Delay: 30 sec. Signal missing 1. Check fuse F45 in Control
pressure or pressure cabinet to see what circuit
signal missing Comment: Error transmitter PT201-16 caused the fuse trip.
(PT201-16). in system pressure malfunction.
2. Use the circuit diagram to
Control system
W04 Process Trigger: PT201-16 Delay: 30 sec. See possible cause See A01.
pressure Parameter: p101 for A01.
too high Comment: Pressure
(PT201-16). higher than parameter
set limit.
List of alarms and warnings
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A10 Process flow Trigger: FIT201-1. Delay: 5 sec. Signal missing or flow 1. Check fuse F45 in Control
signal missing Parameter: N/A transmitter FIT201-1 cabinet to see what circuit
(FIT201-1). Comment: Error in malfunction. caused the fuse trip.
Book No.9028195 02
system flow sensor.
2. Use the circuit diagram to
check the fuse setting, adjust
according to figures in circuit
diagram if necessary and reset
fuse.
List of alarms and warnings
transmitter display,
message error)
11
Control system
12
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W12 Process Trigger: FIT201–1 Delay: 30 sec. Flow rate higher than Reduce the incoming ballast water
flow higher Parameter: N/A certified flow. See flow to the PureBallast system.
than certified Comment: An field Certified flow in
(FIT201-1). additional common page 1.1 Overview.
Reduce flow! alarm signal is issued.
Note: Operation
continues but is not
compliant and does not Wrong setting in See chapter 4. Parameters, section
fullfil tequirements FIT201-1. Flow transmitter.
for treatment of
ballast water. Act Flow sensor See section Flow meter on page
according to ballast malfunctions. 53.
water management
plan.
A13 Process flow too Trigger: FIT201–1 Delay: 20 sec. Flow too low. • Increase flow.
low (FIT201-1). Parameter: p116
• Make sure the ballast water
Automatic stop. Comment: If flow
is less than set in from the ballast pump is
directed to PureBallast. When
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
Valves in ballast Control that correct valves are
system closed. opened for current process.
See chapter 3. Operating
instructions and control system
description, section Detailed
process description.
List of alarms and warnings
A14 Process Trigger: FIT201-1 Comment: Triggered Control valve V201–8 See alarm A17.
flow too low Parameter: p116 if flow defined in p116 malfunctions.
during start-up is not established
(FIT201-1). within 60 seconds after Flow too low. See alarm A13.
Automatic stop. ballast water pump is
started.
2.1
13
Control system
14
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A17 Valve error Trigger: Limit switch Delay: 25 sec. Fuse tripped. 1. Check fuses F43 in control
(V201-3). GS201-3. cabinet to see what circuit
Parameter: N/A. Comment: Error on caused the fuse trip.
valve V201–3.
2. Check relay K1 and K2 on
Control system
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
Too long 1. Follow the instruction Adjust
opening/closing time valve traveling speed in chapter
(valve travel time) 7. Service manual.
2. Adjust exhaust valves on
List of alarms and warnings
actuator.
3. Check that instrument air
pressure is according to
requirements in chapter 6.
Installation description and
drawings, section Connection
list.
A19 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause Check relay K7 and K8 on module
(201-32) GS201-32. for A17. X10.
2.1
15
Control system
16
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A23 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause Check relay K5 and K6 on module
(V201-9). GS201-9. for A17. X10.
Parameter: N/A. Comment: Error on
valve V201–9.
Control system
A25 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause
(V404-35) GS201-35. for A17.
Parameter: N/A. Comment: Error on
valve V201–35.
A29 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause
(V201-8). GS201-8. for A17.
Parameter: N/A. Comment: Error on
control valve V201–8. • Sensor error. 1. Check open indication in the
Shows open all pneumatic positioner.
the time.
2. Check fuses F43 in control
• Signal error 4–20 cabinet to see what circuit
mA. caused the fuse trip.
3. Check relay K3 on module X10.
4. Use the Control cabinet /
Circuit diagram to check the
fuse setting, adjust according
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
The air filters on Clean the filter on the possitioner.
V201-8 might be
clogged.
A33 Bypass valve is The valve has been If not opened intentionally, close
List of alarms and warnings
A35 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause
(V212-31). GS212-31. for A17.
Parameter: N/A Comment: Shutdown
of all steps except CIP.
The alarm does not
prevent completion or
start of CIP process.
2.1
17
Control system
18
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W40 Process Trigger: Pressure Delay: 2 sec. Ballast water pump Check that pressure and flow
pressure too transmitter: gives too low from ballast pump(s) is according
low (PT201-16). PT201-16. pressure. to requirements in chapter 6.
Parameter: p103. Installation description and
Control system
A48 System stop Trigger: Stop button Delay: None. Process has been
activated (Stop on control cabinet stopped. NOTE
button). Parameter: N/A
Find out the reason why the process
has been stopped before releasing the
button and starting another process.
2
A49 System stop Trigger: Stop button Delay: None See A48.
activated during on control cabinet
CIP (Stop Parameter: N/A
button).
A50 System stop Trigger: External Delay: None. Process has been
activated stop button on control stopped by external NOTE
(External stop cabinet (or signal). stop button or signal
button). Parameter: p135 from the ISCS Find out the reason why the process
(integrated ship has been stopped before releasing the
control system). button and starting another process.
List of alarms and warnings
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
stop button). Parameter: p135
W58 Fuse tripped in Trigger: Control Delay: None. Possible reasons: 1. Check fuse F43–F45 in control
control cabinet. cabinet. • cabinet to see what circuit
Parameter: N/A caused the fuse trip.
• short circuit
List of alarms and warnings
A66 Additional Trigger: External Delay: 2 sec. The valve has been If not opened intentionally, close
bypass valve system. opened manually or the valve.
1 is open. Parameter: p163 Comment: If the valve via the ISCS.
(not controlled by
PureBallast) is opened,
any ongoing process
is stopped. A new
process can not be
started.
2.1
19
Control system
20
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A69 Remote system Trigger: External Delay: 2 sec. PureBallast is If valve is not opened intentionally,
reports system system. bypassed via the close the valve.
is bypassed. Parameter: ISCS.
Control system
A71 Ballast water Trigger: Control Delay: Set in Faulty connection of Check that all electrical connections
pump is system timer. parameter p141. signal cable. are OK. Check that the signal
not running. Parameter: p141. wiring is according to information in
Automatic stop. Comment: Feed back chapter 6. Installation description
signal “BW pump is and drawings, section Control
running” is deactivated cabinet / interconnection diagram.
A72 Stripping pump Trigger: Control Delay: Set in See possible cause
not running. system timer. parameter p141. for A71.
Automatic stop. Parameter: p141.
2
Comment: Feed
back signal “Stripping
pump is running” is
deactivated
A75 Overboard valve Trigger: Control Delay: Set in See possible cause
is not open. system timer. parameter p140. for A71.
Automatic stop. Parameter: p140
Comment: Feedback
“overboard valve is
OPEN”.
List of alarms and warnings
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A77 Error on all Trigger: UV reactors Delay: None An active alarm exist Check control sytem page 2.1
operating Parameter: N/A on all installed UV Alarm list in control panel for
UVR:s. Comment: All reactors. It can be the related alarms.
Book No.9028195 02
Automatic stop. UV reactors are same error for all UV
deactivated. reactors, or different
errors.
A79 Power is Trigger: Control Delay: Set in Power management Investigate if the reasons for not
not granted. system timer. parameter p143. master system not granting power is outside the
Automatic stop. Parameter: p127. granting power . PureBallast system.
List of alarms and warnings
Comment: No
power steps have Feedback signal from See A71.
been granted within power management
parameter set time. master is faulty. Check signal transmission to/from
PureBallast corresponds to
the specifications in chapter
6. Installation description and
drawings, section Control cabinet /
interconnection diagram.
W80 Power is not Trigger: Power Delay: None. See possible cause
fully granted. management system. for A79.
Flow capacity Parameter: p127. Comment: Not all
reduced. requested power steps Not enough power Continue process with lower flow
are granted. Triggered has been granted. capacity or try later.
2.1
if number or requested
power steps does
not match number of
granted power steps.
21
Control system
22
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W82 Heeling mode Trigger: Heeling Delay: None. Heeling mode has
requested (internal transfer) been activated by
by operator. requested in control Comment: The system external system.
Automatic system. is set in pause mode.
Control system
W83 Heeling mode Trigger: Heeling Delay: None. See possible cause
cancelled (internal transfer) not for W82.
by operator. requested in control Comment: Process
Process system. is resumed after being
resumed. Parameter: N/A phased during heeling.
A91 PLC lost Trigger: Control Delay: 60 sec. Panel is switched off 1. Switch on the panel.
communication system PLC. or faulty.
2. Restart the panel. See problem
with all control Parameter: N/A Comment: After
1 B in the general problems list
panels. 60 seconds of lost
on page .
communication,
ongoing process is 3. Replace if faulty.
stopped in a controlled
way and the system Wrong software Check that the HMI and PLC
is shut down. This version software have the save program
message is visible in version. This is visible in control
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
control panel / Circuit diagram and
in chapter 6. Installation description
and drawings.
W92 Main control Trigger: Control Delay: 30 sec. Master panel is See A91.
panel lost system PLC. switched off or faulty.
List of alarms and warnings
A93 Heart beat Trigger: Control Delay: Set in To operate PureBallast when communication is down,
signal from system PLC. parameter p128. follow the steps below:
remote interface Parameter: p132
is not updating. Comment: After 1. Set the system to Local mode: Press the Local button
communication is on the control panel.
lost between ISCS
2. Run the system from the control panel. Note that you
and PLC, ongoing
will need to confirm two messages from the control
process is stopped in a
panel during operation: "Confirm ballast pump started"
controlled way and the
and "Confirm overboard valve open".
system is shut down.
3. Restore these settings when the communication is
2.1
23
Control system
24
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
remote interface integration, you
can disregard this alarm. If not
deactivate the test mode again in
4.5 Remote interface 1.
Control system
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
(not switched).
lost.
W95 PLC battery low. Trigger: Control Delay: 10 sec. The voltage in the Replace PLC battery in the control
system PLC. battery in the control cabinet.
Parameter: N/A system PLC is too
low.
W96 GPS signal not Trigger: Control Delay: 5 sec. Faulty electrical Check that the signal wiring
valid. system PLC. connection. is according to in chapter 6.
Parameter: p160 Installation description and
2.1
25
Control system
26
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W97 PLC error in Trigger: N/A Delay: 2 sec. Error in module. Check the LED error indication for
control cabinet. Parameter: N/A the electronic modules in the LDC.
See section I/O system and X20
modules on page 56.
Control system
W100 UVR [x]: UVR Trigger: UVR Delay: Set in High temperature • Check that the inlet valves
temp too high temperature parameter p206. due to obstacles or (V201-19.x, V403-35) and
(TT201-33). transmitter TT201-33. error in one or more outlet valves (V201-20.x,
UVR shutdown. Parameter: p202 Comment: If components involved. 404-36.x) open properly by
temperature rises operating them manually.
above parameter set See the instruction Operate
value, the UV reactor components manually
will shutdown. in chapter 3. Operating
instructions and control system
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
TT201-33.x Replace transmitter TT201–33
malfunction. according to instruction in
chapter 7. Service manual
section Temperature switch and
temperature transmitter.
List of alarms and warnings
W101 UVR [x]: UVR Trigger: UVR Delay: Set in See possible cause
temp too low temperature parameter p206. for W100.
(TT201-33). transmitter TT201-33.
UVR shutdown. Parameter: p204. Ballast water too cold; See to that incoming water is
temperature below 0 warmer than 0 C°.
C°.
W102 UVR [x]: Trigger: UVR Delay: Set in parameter Signal missing 1. Check fuse F42 in LDC to see
UVR temp temperature p206. or transmitter what circuit caused the fuse
signal missing transmitter TT201-33 TT201-33.x trip.
(TT201-33). error. malfunction.
2. Use the circuit diagram to
UVR shutdown.
Parameter: N/A. check the fuse setting, adjust
according to figures in circuit
diagram if necessary and reset
fuse.
2.1
27
Control system
28
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W107 UVR [x]: LDC Trigger: LDC Delay: 15 sec. No cooling water to Check that cooling water supply
cooling water temperature the heat exchanger. (401) is within specification in
temp too high transmitter TT401. chapter 6. Installation description
(TT401–1). Parameter: p214 and drawings, section Connection
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
W109 UVR [x]: Trigger: LDC Delay: 5 sec. Signal missing or 1. Check fuse F42 in LDC to see
LDC cabinet temperature transmitter TT401 what circuit caused the fuse
temp missing transmitter TT401–1. malfunction. trip.
(TT401–1). Parameter: N/A
2. Use the circuit diagram for the
List of alarms and warnings
29
Control system
30
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W111 LDC air Trigger: Delay: 15 sec. LDC faulty. Check 2. Alarm list in control panel
temperature too Temperature for related alarms.
high (TT401–2) transmitter TT401–2.
Parameter: p238 Faulty fan. Check electrical and mechanical
problems, and attend to.
W113 LDC cabinet Trigger: Delay: 5 sec. Signal missing or flow 1. Check fuse F42 in Control
temperature Temperature transmitter TT401-2 cabinet to see what circuit
missing transmitter TT401–2. malfunction. caused the fuse trip.
(TT401–2) Parameter: N/A
2. Use the circuit diagram to
check the fuse setting, adjust
according to figures in circuit
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
damaged.
6. Replace transmitter FIT201-27.
7. Restart the process from the
beginning.
List of alarms and warnings
W116 UVR [x]: UVR Trigger: Level sensor Delay: Set in Signal missing or 1. Check fuse F42 in LDC to see
fluid level LS201-29. parameter p215. sensor LS201-29.x which circuit that caused the
signal missing Parameter: N/A malfunction. fuse trip.
(LS201-29).
2. Check relay KS02.
3. Use the circuit diagrams for the
LDC to check the fuse setting,
adjust according to figures in
circuit diagram if necessary and
reset fuse.
4. Use the circuit diagrams for
the LDC and UV reactor to
locate the component or find
the reason that caused the fuse
trip and attend to it.
5. Check cables to the level switch
LS201-29.x. See drawing UVR
/ Circuit diagram and Control
cabinet / Circuit diagram
2.1
in chapter 6. Installation
description and drawings.
31
Control system
32
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W117 UVR [x]: UVR Trigger: Level sensor Delay: Set in No fluid in UV reactor. 1. Control that correct valves are
fluid missing LS201-29. parameter p215. opened for current process. See
(LS201–29) in Parameter: N/A Detailed process description
manual mode Comment: The UV in chapter 3. Operating
reactor is shut down. instructions and control system
Prevents start of LPS description.
(UV lamps) in manual
mode. 2. Check that the flow is equal
through all UV reactors and that
the UVR.x is not clogged.
3. Restart the process from the
beginning.
2
W118 UVR [x]: CIP Trigger: Level sensor Delay: Set in No fluid in UV reactor 1. Check that valves V320-2,
flow missing LS201-29. parameter p208. “x”. LS201-29.x V320-4.x, V321-4 and 321-2.x
(LS201-29). Parameter: p208 is indicating dry open and close correctly.
condition.
2. Check that pump P320-1
is functioning correctly. See
problem 6D−6I in the general
problems list on page .
List of alarms and warnings
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
in chapter 3. Operating
instructions and control system
description.
Note that the manual operations
are password-protected and
must only be performed by
List of alarms and warnings
Too low level in CIP Refill the tank with CIP liquid. See
tank. instruction Change and refill CIP
liquid in chapter 7. Service manual.
33
Control system
as no fluid in UV
reactor.
34
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W119 UVR [x]: No Trigger: Level sensor Delay: Set in No liquid in UV reactor 1. Check that pressure flushing
freshwater LS201-29. parameter p208. “x”. LS201-29.x water in pipe 310 is according
filling in UVR Parameter: p216 is indicating dry to requirements in chapter 6.
(LS201-29). condition. Installation description and
Control system
W120 UVR [x]: UVR Trigger: Level sensor Delay: Set in Fluid in UV reactor Restart the process from the
was not drained LS201-29. parameter p200. “x”. LS201-29.x beginning.
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
opened for current process. Also
control that pump P321–5 is
functioning.
Book No.9028195 02
W122 UVR [x]: Fuse Trigger: LDC cabinet Delay: 1 sec. Fuse in LDC has Check fuse F42–43 in LDC cabinet
tripped in LDC for UVR tripped or has been to see what circuit caused the fuse
cabinet. Parameter: N/A switched off. trip. Check according to bullets.
35
Control system
36
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W126 UVR [x]: MCB Trigger: LCD x-1 Delay: 1 sec. Motor circuit breaker 1. See LPS alarms in section
tripped in LDC Parameter: N/A (MCB) for an LPS in Lamp power supply (LPS) on
cabinet. Comment: UVR.x has tripped or page 52.
MCB=Motor circuit has been switched
2. Check Q101–Q116 in LDC and
Control system
W128 UVR [x]: LDC Q117 Delay: 5 sec. Motor circuit breaker Check Q117 in LDC.
cabinet fan (MCB) F1 in control
alarm cabinet has tripped
or has been switched
off.
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W129 UVR [x]: LDC Trigger: Water Delay: 5 sec. Leakage in cooling Repair.
cabinet water sensor LS below water piping.
alarm. heat exchanger in Dry wet areas in the cabinet.
Book No.9028195 02
LDC. Remove the sensor and dry it with
Parameter: N/A paper.
W130 UVR [x]: LPS Trigger: Lamp power Delay: 5 sec. • LPS malfunction. Check LED indication on the LPS
sum alarm. supply in UV reactors that triggered the alarm. See LPS
• Number of broken
LDC. alarms in section Lamp power
UV lamps exeeds
Parameter: N/A supply (LPS) on page 52.
number set in
parameter p213. Check which lamps that are broken
in column Lamp OK in page 4.9
LPS overview.
W131 UVR [x]: UV Trigger: Lamp power Delay: 5 sec. One or more UV lamp Check which lamps that are broken
system failure. supply. is broken. in column Lamp OK in 4.9 LPS
Too many failed Parameter: p213. Comment: UV reactor overview.
lamps. is deactivated.
2.1
37
Control system
38
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
water management
plan.
W132 Estimated UV Trigger: UV reactor Delay: 1 sec. Lifetime for UV Recommended to change all lamps
lamp lifetime lap time. lamps are too after 3000 hours of operation.
Control system
A137 UVR [x]: To high Trigger: TS201-60 Delay: 1 sec. No flow in UV reactor See W100.
temperature Parameter: N/A or too low flow.
(TS201-60 Comment: UV reactor After problem has been attended
tripped) and/or is deactivated. to, the LDC needs to be reset.
LDC powered
off. Reset LDC
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
connection. is according to electrical
drawings.
• Check that all electrical
Book No.9028195 02
connections are OK and that
the electrical wiring is not
damaged.
A138 UVR [x]: PLC Trigger UV reactor x. Delay: 2 sec. Error in module. Check the LED error indication for
List of alarms and warnings
W140 CIP schedule Trigger: Control Delay: Set in CIP not performed Control CIP status on 1.3 CIP
timer elapsed system timer. parameter p117 and after operation. status in control system.
Start CIP! Parameter: N/A. p118.
Start CIP process.
Comment: CIP has not
been performed within
parameter set time limit
after (de)ballast.
Note: Operation
continues but is not
compliant and does not
fullfil tequirements
for treatment of
ballast water. Act
according to ballast
water management
2.1
plan.
39
Control system
40
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
the component.
List of alarms and warnings
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W152 UVR [x]: UV Trigger: UV sensor Delay: 30 sec. Note: Operation continues, but
intensity low. QT201-50. does not fulfill the type approval
System flow Comment: The flow certificate. Act according to ballast
Book No.9028195 02
reduced. is reduced when UV water plan.
intensity (W/m2) is
below 252 according to See chapter 2. System overview,
IMO legislation. Power section Power optimization.
is set to 100% and the
flow is reduced to 50 Water is dirty or have Check water.
List of alarms and warnings
%. low UV transmittance.
It is also possible to fill the reactor
Note: Operation with technical water / potable water
continues but is not to rule out dirty water as reason for
compliant and does not the warning.
fullfil the requirements
for treatment of Quartz sleeves dirty. Run CIP process, and try again.
ballast water. Act
according to ballast If problem remains, check and
water management clean quarts sleeves according to
plan. instruction Replace UV lamp and
quartz sleeves in chapter 7.
Comment: An
additional common Old UV lamps. Check runtime on 4.3 Timers in
alarm signal is issued. control system. Change if old.
Lamps loose effect when maximum
Note: See chapter runtime has been exceeded.
3. Operating
instructions and control Transmitter Test the UV sensor:
system description, QT201-50.x 1. Stop the process and restart
2.1
41
Control system
42
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W153 UVR [x]: UV Trigger: UV reactor. Delay: 30 sec. See chapter 2. System overview,
lamp broken. Parameter: p213 section Operation with broken UV
System flow Comment: If a UV lamp.
reduced. lamp fails during
Control system
ongoing operation,
the flow is set 80 % in
IMO mode and 50 %
in USCG mode of flow
capacity.
Comment:
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
below compliance
limit (W/m2): 772 and
252 in IMO mode.
Book No.9028195 02
At this stage power
is 100% and flow is
reduced to 50 %.
Note: Operation
List of alarms and warnings
W161 UVR [x]: LPS Trigger: LPS Delay: 1 sec. Faulty connection of Check the three cable connectors
communication Parameter: N/A electricity or signal on the LPS .
error. UVR cable.
shutdown.
Wrong LPS setting. Check that the DIP switches
are correctly set for every LPS.
2.1
43
Control system
44
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W163 UVR [x]: Lamp Trigger: LPS in UV Delay: 20 sec. Broken UV lamp. Change according to instruction in
error feedback reactor’s LDC. chapter 7. Service manual.
from LPS. Parameter: N/A Comment: No lamp
feedback when it is Faulty connection of Check UV lamp power cable.
Control system
W164 UVR [x]: LPS Trigger: LPS in UV Delay: 20 sec. Faulty LPS. Check 4.9 LPS power overview
error feedback reactor’s LDC. and LED indication on the LPS
from LPS. Parameter: N/A Comment: No LPS that triggered the alarm. See LPS
feedback when it is alarms in section Lamp power
requested to start its supply (LPS) on page 52.
lamp. UV reactor is
deactivated If the power is on but there are
no indication, the LPS is probably
broken.
W165 UVR [x]: LPS in Trigger: LPS in UV Delay: 5 sec. One or more of the Check 4.9 LPS power overview
fault state. reactor’s LDC. below: and LED indication on the LPS
Parameter: N/A Comment: UV reactor that triggered the alarm. See LPS
is deactivated. • Air temp fault alarms in section Lamp power
• Driver fault supply (LPS) on page 52.
Note: Operation
continues but is not • Fan fault During commissioning: Alfa
2
compliant and does not Laval can run a process with one
fullfil tequirements • Heat sink fault
faulty LPS, to be able to fulfill
for treatment of • System fault commissioning. Parameter p213
ballast water. Act (Allowed nr. of failed UV lamps) is
according to ballast • Voltage fault
set to 1. Parameter must be reset
water management • Broken UV lamp to 0. Operation with faulty LPS
plan. or lamps does not fulfill the type
approval certificate.
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
W170 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause
(V201–19) GS201–19. for A17.
Comment: UV reactor
Parameter: N/A is deactivated.
List of alarms and warnings
W171 Valve error Trigger: Limit switch Delay: 25 sec. See possible cause
(V201–20) GS201–20. for A17.
Comment: UV reactor
Parameter: N/A is deactivated.
W180 LDC ring Trigger: LDC. Delay: 1 sec. Faulty connection of Check that the power link (LAN)
redundancy signal cable cable from the control cabinet (in a
error Parameter: N/A loop to all LDCs) and back is OK.
45
Control system
46
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
for systems with three
Filtrex filter and flow
3000.
W306 Filter differential Trigger: Pressure Delay: 2 sec. Filter is clogged. Backflush manually from control
pressure too transmitter PT201-71 system. If not sufficient, clean
List of alarms and warnings
47
Control system
48
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
drawings.
5. Check that all electrical
connections are OK and that
the electrical wiring is not
damaged.
6. Replace faulty transmitter.
7. Restart the process from the
beginning.
W308 Filter pressure Trigger: Pressure Delay: 30 sec. Signal missing 1. Check fuse F42 in LDC to see
signal missing transmitter or component which circuit that caused the
(PT201-71) PT201-71. Comment: Alarm malfunction. fuse trip.
Parameter: p314. deactivated in Standby.
2. Use the circuit diagram to
check the fuse setting, adjust
according to figures in circuit
diagram if necessary and reset
fuse.
2
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
the component.
A315 Diff pressure too Trigger: Pressure Delay: 5 sec. See W306.
high. Automatic transmitter PT201-71
shutdown. and PT201-72. Comment: Pressure
Parameter: p300. transmitters indicates
pressure higher than
set in p300.
2.1
49
Control system
50
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A501 Log box error Trigger: Log box Delay: 10 sec. Wrong setting. 1. Check that parameter p500 is
(optional). activated in the control system.
Parameter: p500.
2. Acknowledge the alarm in the
control system, to be able to
Control system
Book No.9028195 02
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Book No.9028195 02
cable gland.)
Fuse in the log box Check fuse F02 and F03 in the log
has tripped or has box.
been switched off.
List of alarms and warnings
W502 External bypass Trigger: Log box Delay: 10 sec. See A33.
is open (optional).
Parameter: p500. Comment: If
detected by bypass
configuration in 4.7
Log box.
51
Control system
2.2 Lamp power supply (LPS) 2 List of alarms and warnings
5 LPSledG
5 LPSledY
• LPS temperature too high (> 50° C).
• LPS fan faulty.
Lamp error. Possible causes:
5 LPSledR
• Two lamp ignition failures.
• Broken UV lamp.
• Loose cables to UV lamp.
Lamp on.
5 LPSledB
5 LPSledB2
• Faulty DIP switch setting on one or more LPS. This fault occur after a 10 seconds
delay after start.
• Voltage on the fail safe is missing.
52 Book No.9028195 02
2 List of alarms and warnings 2.3 Flow meter
4 Display lines
2. Restart.
3. If the problem cannot be detected or corrected, the flowmeter, its transmitter or display must be
replaced. Follow the instruction in chapter 7 Service manual , section Replace display and fuse.
Book No.9028195 02 53
2.3 Flow meter 2 List of alarms and warnings
The table below explains errors displayed on the flow meter display.
5 Flash
$ = fault message
! = notice message
EMPTY PIPE = Type of error, e.g. measuring tube is only partly filled or completely empty
03:00:05 = duration of error occurrence (in hours, minutes and seconds)
#401 = error number
Error number: System error (device error) has occurred
No. 001 – 399
No. 501 – 699
Error number: Process error (application error) has occurred
No. 401 - 499
54 Book No.9028195 02
2 List of alarms and warnings 2.4 Level switch
351 to 354 S: CURRENT Current output: flow is out of 1. Change the upper or lower
RANGE n range. limit setting, as applicable.
!: # 351 to 354 2. Increase or reduce flow, as
applicable
401 EMPTY PIPE Measuring tube partially filled 1. Check the process conditions
$: # 401 or empty of the plant
2. Fill the measuring tube
Red Blinking Error: Internal sensor error or sensor Replace the component.
corroded.
Book No.9028195 02 55
2.5 I/O system and X20 modules 2 List of alarms and warnings
All modules are identified on the front, for example “X20 DO 6529” in the illustration below. To the
right, the stat indication LEDs are visible, for example “r, e, X, I” in the illustration below.
5X20
56 Book No.9028195 02
2 List of alarms and warnings 2.5 I/O system and X20 modules
NOTE
• Note that all status indications are not valid for all modules.
• The meaning of a status indication might vary for some modules. These variations are specified
in the Description column.
• Module BC0083, CP3585 and IF1082-2 are described in separate tables below the generic
table.
The table contains the following columns and information:
Book No.9028195 02 57
2.5 I/O system and X20 modules 2 List of alarms and warnings
58 Book No.9028195 02
2 List of alarms and warnings 2.5 I/O system and X20 modules
Module BC0083
Book No.9028195 02 59
2.5 I/O system and X20 modules 2 List of alarms and warnings
Module CP3585
60 Book No.9028195 02
2 List of alarms and warnings 2.5 I/O system and X20 modules
Module IF1082-2
The status/error light is a green/red dual LED. The interface can be operated in two moedes: Either
in Powerlink V mode or as an Ethernet TCP/IP interface. Status light depends on mode. For
TCP/IP mode, only SE green is valid.
Book No.9028195 02 61
2.5 I/O system and X20 modules 2 List of alarms and warnings
Module DI9371
62 Book No.9028195 02
3 List of problems and solutions
This section contains problems that can occur, but is not indicated by an alarm.
Book No.9028195 02 63
64
3.1
Problem Description Possible cause What to do?
ID
1A The system does not start. Main breaker Q1 on control Turn on the breaker and measure that incoming 24 V DC to
The control panel does and LDC cabinet turned off, the control panel is present.
not light up. or power not connected to the
control panel.
General problems
Fuse F42 tripped. 1. Check fuse F42 in control cabinet to see what circuit
caused the fuse trip.
2. Use the circuit diagram to check the fuse setting, adjust
according to figures in circuit diagram if necessary and
reset fuse.
3. Use the circuit diagram to locate the component or find the
reason that caused the fuse trip and attend to it.
Fuse F41 in control cabinet 1. Check fuse F41 in control cabinet to see what circuit
tripped. caused the fuse trip.
2. Use the circuit diagram to check the fuse setting, adjust
according to figures in circuit diagram if necessary and
reset fuse.
3
Control panel error due to Let the panel dry and try again.
damp.
Book No.9028195 02
List of problems and solutions
3
1B Control panel is not Abnormal operating condition. 1. Restart the control panel: Cut the power by removing the
displaying a normal page. power cable at the back of the control panel. Wait 30
seconds, and reconnect the cable again.
Book No.9028195 02
2. Restart the entire PureBallast system: Cut the power by
switching of the main breaker on the control cabinet. Wait
30 seconds, and switch on the main breaker again.
3. If panel is not OK, it is probably broke and needs to be
replaced. Replace the component.
List of problems and solutions
Wrong software version Check that the HMI and PLC software have the save program
version. This is visible in control system page 4.1 System info .
HMI software problem Re-load the HMI software according to the software Release
note.
1C PureBallast can not be Communication is broken See the What to do column for alarm A93.
controlled or monitored between ISCS and PLC.
from the ISCS’ graphical
user interface via the
remote interface (optional)
5 PanelCommunicationError
These messages can appear alone or in combination. The message does not appear in remote control panels (option).
65
66
3.1
Problem Description Possible cause What to do?
ID
Book No.9028195 02
List of problems and solutions
3 List of problems and solutions 3.2 Filter
3.2 Filter
Book No.9028195 02 67
68
3.2
5A Backflush sequence Pressure transmitters Dismantle the component and inspect/rinse.
starting error (general) PT201–71 and PT201–72
may be faulty.
Filter
Pressure transmitters
PT201–71 and PT201–72 Error with the pressure gauge Dismantle the component and inspect/attend to.
may be faulty. electric switches.
Valves for air pressure to valve Open the valve (ball cock) connected to V309-1.
V309-1 are closed.
5B Excessive backflushing The filter house is not properly Deaerate using the deaeration valve V201-50 on the filter lid.
or long backflushing deaerated.
sequences (general)
Damaged filter element. Check filter element for damage. Replace if necessary.
Large obstructions have Open the filter and remove the obstructions. See chapter 7.
entered the filter. Service manual, section Filter.
Book No.9028195 02
3 List of problems and solutions 3.3 CIP
3.3 CIP
Book No.9028195 02 69
70
3.3
6A Insufficient pump capacity Leakage in air hoses or Locate leakage and attend to.
(general). sealings.
CIP
Air pressure too low due to Adjust setting with the manual valve under the valve block on
incorrect setting on valve block the CIP module.
on CIP.
The diaphragm in the CIP pump Examine the pump. See chapter 7. Service manual, section
is broken. Repair CIP pump.
Pump is clogged. Examine the pump. See chapter 7. Service manual, section
Repair CIP pump.
6B Too high consumption Leakage in the CIP tank, CIP Locate leakage and attend to.
of CIP liquid (> 1 cm/UV pump, pipes or UV reactor.
reactor cycle).
6C CIP liquid is not returned Insufficient pump capacity 1. Increase airflow to the pump to increase pump capacity
to CIP tank. (P321-5). with the manual valve under the valve block on the CIP
module.
2. Check that pump P321-5 is functioning correctly. See
problem 6D−6I in this chapter.
6D CIP pump does not run • The air pressure is to low Examine the pump and attend to problem. See chapter 7.
Service manual, section Test CIP pump.
• The air connection is
blocked
• Muffler is blocked
• Air valve is defect
• Dirt in the pump chamber
• Diaphragm breakdown
List of problems and solutions
Book No.9028195 02
3
6E CIP pump runs irregularly • Valve balls are blocked Examine the pump and attend to problem.
• Sealings are defect in air
valve or center block
• Diaphragm breakdown
Book No.9028195 02
6F Insufficient CIP pump • Suction connection blocked Examine the pump and attend to problem.
suction or not tight.
• Muffler is blocked
• Valve balls are blocked or
damaged
List of problems and solutions
6G Bad flow or pressure in • Pressure fall in incoming air Examine the pump and attend to problem.
CIP pump
• Suction or air connection
blocked
• Muffler is blocked
• Air valve is defect
• Valve balls worn out/broken
• Air in liquid Diaphragm
breakdown
6H CIP pump leakage Screws on the housing not Tighten the screws.
properly fastened
71
CIP
3.4 Valve V201–8 3 List of problems and solutions
72 Book No.9028195 02
3
8A Signal change has no effect on Faulty air supply Check air supply to the valve and tubing to the actuator.
the actuator position See chapter 7. Service manual, section Proportional
valve for instructions regarding the proportional valve.
Book No.9028195 02
8B Signal change results in actuator Connection or signal problem • Check coupling between proportional valve and
running to end positions actuator.
• Check input signal.
Signal and positioning problems. • Inaccurate positioning. Adjust position sensor. See chapter 7. Service manual,
List of problems and solutions
8C
section Calibrate positioner on V201-8.
• Input signal fluctuates.
Check electric connection.
3.4
Valve V201–8
73
Chapter: 6. Technical data and drawings
System manual — PureBallast 3.1 1000
USCG
2 Technical data 7
2.1 Water and f ow requirements 7
2.2 Power requirements 8
2.3 System pressure 9
2.4 Pressure requirements — Backf ush 10
2.4.1 Calculate backflush parameter setting 11
4 Drawings 15
4.1 Graphic symbols used in drawings 16
4.2 General drawings 17
4.2.1 Flow chart 18
4.2.2 Connection list 20
4.2.3 Electrical system layout (2 pages) 26
4.2.4 Instrument air distribution 28
4.2.5 Quality specification / Instrument air 29
4.2.6 Quality specification / Technical water / potable
water 30
4.2.7 Quality specification / CIP liquid 31
4.2.8 Material data sheet / UV lamp 32
4.2.9 Safety data sheet / CIP liquid 42
3
4.3 Dimension drawings including technical
data 50
4.3.1 UV reactor (previously called AOT reactor) 50
4.3.2 Filter 51
4.3.3 CIP module (2 pages) 52
4.3.4 Flow transmitter FIT201-1 54
4.3.5 Pressure monitoring device 6 bar system (Incl.
PT201-16, PI201-18, RV201 and 201-15) 55
4.3.6 Pressure monitoring device high pressure system
(Incl. PT201-16, PI201-18, RV201 and 201-15) 56
4.3.7 Valve V201-3 and V201-9 57
4.3.8 Valve V201-32 and V403-35 58
4.3.9 Valve V212-31 (Optional in scope of supply) 59
4.3.10 Control valve V201-8 61
4.3.11 Backflush valve V309-1 62
4.3.12 Sampling device Q201.1 and Q201.2 (3 pages)
(Optional in scope of supply) 63
4.3.13 Lamp drive cabinet (LDC) 66
4.3.14 Control cabinet 67
4.3.15 Remote control panel (Optional) 68
4.3.16 Log box (Optional) 69
4.3.17 Transformer (Optional) 70
4.3.18 Air filter / Filter regulator 71
4.3.19 Additional pumps (Optional) 72
4.3.20 Closed cooling unit, LDC / Dimension drawing
(Optional) 75
4.3.21 UV reactor and LDC / Lamp power cable 76
4
1 Introduction
This chapter contains technical information about PureBallast together with mechanical and
electrical drawings.
Data Value
Book No.9028195 02 5
1.1 Ship specific information 1 Introduction
2 Technical data
This section states technical data for the complete PureBallast system and for individual
components. In some cases references are given to data in drawings included in this chapter.
Water requirements
Ballast water Used for cooling UV lamps in the UV reactor during start-up. Pipe
403 is recommended to be connected to the vessel’s sea water
cooling system or dedicated UV cooling water pump (P403-1) for UV
reactor cooling. Booster pump is not part of Alfa Laval’s scope of
supply.
Book No.9028195 02 7
2.2 Power requirements 2 Technical data
Flow requirements
Pipe 309
Pipe 310.1
Pipe 401
Pipe 403
8 Book No.9028195 02
2 Technical data 2.3 System pressure
IP rating >IP44
LDC — Heat dissipation Heat transfer from/to the LDC is depending on ambient temperature.
The need for cooling the area where the LDC is placed, is therefore
dependent on ambient temperature.
At an ambient temperature of
Power to UV reactor.
Book No.9028195 02 9
2.4 Pressure requirements — Backflush 2 Technical data
0–9 bar.
Instrument air 5.5 – 8.0 bar to operate valves and CIP pumps. For
detailed requirements, see
With backf ush pump : 1.7 bar. For details, see table below.
Without backf ush pump : If backflush pump P309 is not used, pressure drop in pipe 309 ( p309)
must be calculated and added according to the table blow.
Note This pressure will overcome pressure drop for PureBallast components and ensure filter
backflush. Piping is not included.
≤ 0.5 Max differential pressure over the filter during ballast operation. When
the differential pressure reaches 0.5 bar due to dirt in the filter, a
backflush is started automatically.
p309 If a backflush pump P309 is not used, pressure drop in pipe 309 must
be calculated and added to secure effcient backflush. This is vessel
specific and must be calculated using required flow in pipe 309:
95 m3/h.
The result of this calculation is used to set parameter p304, crucial for
the backflush. See Calculate backflush parameter setting below.
10 Book No.9028195 02
2 Technical data 2.5 PureBallast components
Total The ballast water pump must deliver pressure at filter inlet, covering
total pressure drop over PureBallast.
• Reduce the total pressure drop by reducing p309. This can, for
example, be done by increasing the pipe diameter or by reducing
the number of bends etc in pipe 309.
• Upgrade ballast water pump or impeller.
• Use a backflush pump, if not already done.
Without, the setting must be calculated according to below. With backflush pump, a fixed value is
used.
For detailed information, see dimension drawings in section Dimension drawings including technical
data on page 50.
Book No.9028195 02 11
2.5 PureBallast components 2 Technical data
Tank volume (l) 250. Note: Total tank volume is 300, but shall
only be filled to max 250.
12 Book No.9028195 02
3 Control system integration
It is possible to is integrate PureBallast with the vessels ISCS as an option. The purpouse is to
monitor and controll external components on the vessel to make a more smooth integration.
For remote integration, please refer to the following documents, together with the Electrical dwg
- CC.
• Design and installation guide for information about remote control panels, power management
system, external components and GPS integration.
• Remote interface implementation guide
• Logbox installation guide.
Book No.9028195 02 13
3 Control system integration
4 Drawings
This section contains drawings for the PureBallast system. It is divided into three main parts:
• General drawings – overall and principle information for system layout (pipes, components,
electricity, air and water).
• Dimension drawing – detailed component information (dimensions, sizes etc).
• Electrical drawings – detailed electric information (circuit diagrams, cable lists etc).
See the Contents section at the beginning of this chapter to get an overview of included drawings.
Book No.9028195 02 15
4.1 Graphic symbols used in drawings 4 Drawings
573644
16 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 17
4.2 General drawings 4 Drawings
9025598
18 Book No.9028195 02
4 Drawings 4.2 General drawings
9033711
Book No.9028195 02 19
4.2 General drawings 4 Drawings
9025986_Page_1
20 Book No.9028195 02
4 Drawings 4.2 General drawings
9025986_Page_2
Book No.9028195 02 21
4.2 General drawings 4 Drawings
9025986_Page_3
22 Book No.9028195 02
4 Drawings 4.2 General drawings
9025986_Page_4
Book No.9028195 02 23
4.2 General drawings 4 Drawings
9025986_Page_5
24 Book No.9028195 02
4 Drawings 4.2 General drawings
9033710
Book No.9028195 02 25
Book No.9028195 02
Drawings
6+,36<67(0
9HVVHOFRQWUROV\VWHP (OHFWULFDOSRZHU
:
1RWH:$'$OID/DYDOFDEOHPXVWEHXVHG
GLVWULEXWLRQFHQWUDO
:
$ : 9$&+]SKDVH /'&Q:$'DUHV\VWHPVL]HGHSHQGHQW 3RZHUSHU/'&FDELQHWDQGUHFRPHQGHG:QFDEOHVL]H
: 895VL]H :$ [ N:[PPð
4
5HDFWRU
5HDFWRU
:% :%
:& :&
& :' :'
Electrical system layout (2 pages)
,1 287 ,1 287
*1' *1'
9025754_1
: :
'
1RWH,I/'&FRQQHFW
:WR/'&287
: :QRWQHHGHG
(
:
General drawings
: : : : : : : : : : : : : :
3( 3( 3(
*6 *1' *1' )LOWHU *6 *6 *6 *6 *6
&,3XQLW 0 0 0 ),7 37
a a a
9 9 9 9 9 9 ),7 37
) %\SDVVYDOYH 0 0 0
2SWLRQ 2SWLRQ 2SWLRQ
3XPSV RSWLRQDO
&XUUHQWSDJH
4.2.3
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH SDJH
(G 6(78*1+ 3XUH%DOODVW
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.2 (OHFWULFDOV\VWHPOD\RXW &XUUHQWSDJH
26
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
27
General drawings
&DEOHRYHUYLHZ $OID:DOOB)B )(1
$ 0LQFURVVVHFWLRQ
&DEOHQDPH 6RXUFH IURP 7DUJHW WR FDEOHW\SH DOOFRQGXFWRUV IXQFWLRQWH[W
>PP@
: 6+,36<67(0 && 3RZHUFDEOHDUPRXUHG N: 3XPSGHSHQGHQW
: && /'&,1 /$1&$7H6KLHOGHGRUEHWWHU 0D[P
: /'&287 /'&,1 /$1&$7H6KLHOGHGRUEHWWHU 0D[P
: && /'&287 /$1&$7H6KLHOGHGRUEHWWHU 0D[P
: 6LJQDOFDEOH )HHGEDFN RSHQFORVHVLJQDOIRUE\SDVVYDOYH
4.2
9025754_2
:' /'& 895 $/)$/$9$/ 0D[0
:' /'& 895 $/)$/$9$/ 0D[0
: && ),/7(5 3RZHUFDEOHDUPRXUHG
: && ),/7(5 6LJQDOFDEOHVKLHOGHG [
'
: && &,3 6LJQDOFDEOH
: && 5&3 /$1&$7H6KLHOGHGRUEHWWHU 0D[P
:) 0XOWLPRGHILEHUXP ,IPRUHWKDQPXVHILEHUFDEOH
: 6+,36<67(0 5&3 3RZHU6XSSO\ [ 9'&9 $PS
: 6+,36<67(0 5&3 3RZHU6XSSO\ [ 9'&9 $PS
: 6LJQDOFDEOHVKLHOGHG [
: && 5, 6LJQDOFDEOHVKLHOGHG [
: && ),7 6LJQDOFDEOHVKLHOGHG [
: && 9 6LJQDOFDEOH
( : && 9 6LJQDOFDEOHVKLHOGHG [
: && 9 6LJQDOFDEOH
: && 0 3RZHUFDEOHDUPRXUHG
: && 0 3RZHUFDEOHDUPRXUHG
: && 0 3RZHUFDEOHDUPRXUHG
: && 37 6LJQDOFDEOHVKLHOGHG [
: && 9 6LJQDOFDEOH
Book No.9028195 02
: && 9 6LJQDOFDEOH
: && 9 6LJQDOFDEOH
)
Drawings
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH SDJH
(G 6(78*1+ 3XUH%DOODVW
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
4.2 General drawings 4 Drawings
9010001
28 Book No.9028195 02
4 Drawings 4.2 General drawings
553407
Book No.9028195 02 29
4.2 General drawings 4 Drawings
590773
30 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 31
594956
4.2 General drawings 4 Drawings
32 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 33
4.2 General drawings 4 Drawings
34 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 35
4.2 General drawings 4 Drawings
36 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 37
4.2 General drawings 4 Drawings
38 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 39
4.2 General drawings 4 Drawings
40 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 41
4.2 General drawings 4 Drawings
42 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 43
4.2 General drawings 4 Drawings
44 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 45
4.2 General drawings 4 Drawings
46 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 47
4.2 General drawings 4 Drawings
48 Book No.9028195 02
4 Drawings 4.2 General drawings
Book No.9028195 02 49
4.3 Dimension drawings including technical 4 Drawings
data
50 Book No.9028195 02
9003516
4 Drawings 4.3 Dimension drawings including technical data
4.3.2 Filter
Book No.9028195 02
9024508 51
4.3 Dimension drawings including technical 4 Drawings
data
9004714_p1
52 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9004714_p2
Book No.9028195 02 53
4.3 Dimension drawings including technical 4 Drawings
data
54 Book No.9028195 02
9024584
4 Drawings 4.3 Dimension drawings including technical data
Book No.9028195 02
9015501
55
4.3 Dimension drawings including technical 4 Drawings
data
56 Book No.9028195 02
9011457
4 Drawings 4.3 Dimension drawings including technical data
9007178
Book No.9028195 02 57
4.3 Dimension drawings including technical 4 Drawings
data
9007180
58 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9007176
Book No.9028195 02 59
4.3 Dimension drawings including technical 4 Drawings
data
9008461
60 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9007182
Book No.9028195 02 61
4.3 Dimension drawings including technical 4 Drawings
data
9025645
62 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
590066 2
64 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
590066 3
Book No.9028195 02 65
4.3 Dimension drawings including technical 4 Drawings
data
9011945
66 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9012103
Book No.9028195 02 67
4.3 Dimension drawings including technical 4 Drawings
data
9012094
68 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9002906
Book No.9028195 02 69
4.3 Dimension drawings including technical 4 Drawings
data
9029115
70 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9018092
Book No.9028195 02 71
4.3 Dimension drawings including technical 4 Drawings
data
9019602
72 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9019614
Book No.9028195 02 73
4.3 Dimension drawings including technical 4 Drawings
data
9025762
74 Book No.9028195 02
4 Drawings 4.3 Dimension drawings including technical data
9033706
Book No.9028195 02 75
4.3 Dimension drawings including technical 4 Drawings
data
9007280
76 Book No.9028195 02
4 Drawings 4.4 Electrical drawings
'
&
$
%
(
)
'DWH
(;7 &&
6833/<9$&
/ 5 / 5
/ [
0D[IXVH$
/ 6 / 6
/ : 4
1DPH
/ 7 / 7
/
&&
3( 3(
3( 3( 3(
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
/'& &&
2*:+ 2*:+
2* 2*
*1:+ *1:+
&$7H6)873
5HSODFHPHQWRI
3XUH%DOODVW
&211(&7,21
,17(5)$&(
%8 %8
),567/'&
:/$1
%8:+ %8:+
; ;
*1 *1
%1:+ %1:+
%1 %1
6+ 6+
6+ 6+
5HSODFHGE\
/'& &&
2*:+ 2*:+
2* 2*
&XUUHQWSDJH
*1:+ *1:+
&$7H6)873
&211(&7,21
,17(5)$&(
%8 %8
/$67/'&
:/$1
%8:+ %8:+
; ;
*1 *1
,QWHUFRQQHFWLRQGLDJUDP
%1:+ %1:+
%1 %1
&&
6+ 6+
6+ 6+
6+,36<67(0 &&
'RFXPHQW1R
[
306,17(5)$&(
&XVWRPHUGHVFULSWLRQ
:
8 [ ;
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_23
Book No.9028195 02 77
4.4 Electrical drawings 4 Drawings
SDJH
3UHY
'
&
$
%
(
)
[
306,17(5)$&(
'DWH
6+,36<67(0 &&
:
8 [ ;
1DPH
&&
6+ 6+
3( 3(
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
6+,36<67(0 &&
%%
;.
$
&&
%%
5HSODFHPHQWRI
3XUH%DOODVW
;.
$
8 &&
[
306,17(5)$&(
%%
:
$
;.
[
&&
%%
;.
$
5HSODFHGE\
6+,36<67(0 &&
8 ;
&XUUHQWSDJH
&&
6+ 6+
3( 3(
,QWHUFRQQHFWLRQGLDJUDP
&&
6+,36<67(0 &&
[
'RFXPHQW1R
(;7(51$/
:
6,*1$/6
8 [ ;
&XVWRPHUGHVFULSWLRQ
&&
6+ 6+
3( 3(
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_24
78 Book No.9028195 02
4 Drawings 4.4 Electrical drawings
SDJH
3UHY
'
&
$
%
(
)
7DUJHW WR 6RXUFH IURP
0RGLILFDWLRQ
'DWH
6+,36<67(0 &&
%%
;.
$
1DPH
&&
%%
;.
$
2ULJLQDO
$SSU
(G
'DWH
&&
%%
6(78-$'
6(78-$'
;.
$
&&
[ %%
;.
(;7(51$/
:
6,*1$/6
$
8 [ &&
5HSODFHPHQWRI
3XUH%DOODVW
%%
;.
$
&&
%%
;.
$
&&
%%
;.
5HSODFHGE\
$
&&
%%
;.
$
&&
&XUUHQWSDJH
6+ 6+
3( 3(
,QWHUFRQQHFWLRQGLDJUDP
),/7(5-% &&
[
),/7(502725
%1 %1
&&
/
:
6833/<
%. %.
/
; *< [ *< ;
/
*1<( *1<(
3( 3(
6+ 6+
'RFXPHQW1R
),/7(5-% &&
$ $
[[
),/7(56,*1$/6
% %
$ : $
&XVWRPHUGHVFULSWLRQ
; % [ % ;
$ $
% %
$ $
% %
6+ 6+
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_25
Book No.9028195 02 79
4.4 Electrical drawings 4 Drawings
SDJH
3UHY
'
&
$
%
(
)
'DWH
&,3 &&
$
%
1DPH
$
%
$
&,3&211(&7,21
[ ;
2ULJLQDO
$SSU
(G
'DWH
%
$
:
6(78-$'
6(78-$'
[
%
$
&20
&,3 &&
3(
5HSODFHPHQWRI
3XUH%DOODVW
3( 3( 3(
6+ 6+
3(
5&3 &&
2*:+ 2*:+
5HSODFHGE\
2* 2*
5(027(&21752/3$1(/
*1:+ *1:+
/$1&211(&7,21
%8 &$7H6)873 %8
%8:+ : %8:+
; *1 *1 ;
&XUUHQWSDJH
%1:+ %1:+
%1 %1
6+ 6+
6+
6+ 6+
6+ 6+
,QWHUFRQQHFWLRQGLDJUDP
&&
[
5(027(3$1(/
237,&$/),%(5
&211(&7,21
5&3 &&
287
5; :) 5;
,1
6: 7; 7; 6:
,1 287
'RFXPHQW1R
&&
$ $
[[
*36,17(5)$&(
D
&211(&7,21
% %
237,21$/
E :
$ $
&XVWRPHUGHVFULSWLRQ
[ ;
% %
6+ 6+
6+ 6+'
5(027(,17(5)$&(
[[
&211(&7,21
6+,36<67(0 &&
237,21$/
$ : $
56
5, % [ % ;
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_26
80 Book No.9028195 02
4 Drawings 4.4 Electrical drawings
SDJH
3UHY
'
&
$
%
(
)
7DUJHW WR 6RXUFH IURP
0RGLILFDWLRQ
'DWH
6+,36<67(0 &&
5(027(,17(5)$&(
$ $
[[ ;
&211(&7,21
237,21$/
: (;7
56
1DPH
% %
5, [
&&
6+ 6+
6+' ;
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
(;7 &&
[[
6<67(0:$7(5
$ $
:
),7
% %
)/2:
),7 $ [ $ ;
5HSODFHPHQWRI
3XUH%DOODVW
% %
&&
6+ 6+
3( 3(
(;7 &&
5HSODFHGE\
;
&/26(23(1
[
&&
:
9
%%
9 ;.
$
&XUUHQWSDJH
&&
$ ;.
6+ 6+
3(
,QWHUFRQQHFWLRQGLDJUDP
&&
(;7 &&
$ $
[[
;
% %
:
9
&/26(
9 &&
[
$ $
%%
% % ;.
$
'RFXPHQW1R
&&
6+ 6+
3( 3(
&XVWRPHUGHVFULSWLRQ
(;7 &&
&/26(23(1
;
[
: &&
9
9
%%
;.
$
&&
$ ;.
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_27
Book No.9028195 02 81
4.4 Electrical drawings 4 Drawings
SDJH
3UHY
'
&
$
%
(
)
'DWH
0 &&
[
06833/<
%1 %1
/
/
%. : %.
0 ;
1DPH
*< [ *<
/
*1<( *1<(
3( 3(
6+ 6+
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
0 &&
[
06833/<
%1 %1
/
/
%. : %.
0 *< [ *< ;
/
5HSODFHPHQWRI
3XUH%DOODVW
*1<( *1<(
3( 3(
6+ 6+
0 &&
[
06833/<
%1 %1
/
5HSODFHGE\
/
%. : %.
0 *< [ *< ;
/
*1<( *1<(
3( 3(
6+ 6+
&XUUHQWSDJH
6<67(035(6685(
[[
(;7 &&
:
37
$ $
,QWHUFRQQHFWLRQGLDJUDP
37 % [ % ;
&&
$ $
% %
&&
6+ 6+
3( 3(
(;7 &&
'RFXPHQW1R
&/26(23(1
;
[
&&
:
9
%%
9 ;.
&XVWRPHUGHVFULSWLRQ
$
&&
$ ;.
6+ 6+
3(
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_28
82 Book No.9028195 02
4 Drawings 4.4 Electrical drawings
SDJH
3UHY
'
&
$
%
(
)
7DUJHW WR 6RXUFH IURP
0RGLILFDWLRQ
&/26(23(1
'DWH
(;7 &&
%%
[
$
;.
:
9
1DPH
&&
9
$ ;.
&&
2ULJLQDO
$SSU
(G
'DWH
6+ 6+
3( 3( 3(
6(78-$'
6(78-$'
(;7 &&
&/26(23(1
;
5HSODFHPHQWRI
3XUH%DOODVW
[
&&
:
9
%%
9 ;.
$
&&
$ ;.
6+ 6+
3(
5HSODFHGE\
23(5$7,21)(('%$&.
6+,36<67(0 &&
[
6+,36<67(0
:
9
&XUUHQWSDJH
8
[
;
&&
,QWHUFRQQHFWLRQGLDJUDP
6+ 6+
3( 3(
&&
6+,36<67(0 &&&211(&7,21
(;7 &&
23(5$7,21)(('%$&.
[
: ;
9
'RFXPHQW1R
9
&&
6+ 6+
3( 3( 3(
&XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_29
Book No.9028195 02 83
Book No.9028195 02
Drawings
$
4
6RXUFH IURP
6+
%
:
[
&
6+
7DUJHW WR
3(
'
9
(;7
(
Electrical drawings
)
9
&/26(23(1
&XUUHQWSDJH 5,
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
9025776_31
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
4.4
84
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
,QWHUFRQQHFWLRQGLDJUDP &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
85
Electrical drawings
3RZHUFRQGXFWRUVVKDOOEHEODFN
,QVXODWHGHQGIHUUXOHVVKDOOEHXVHGXSWRPPð
PPðDQGXSXVHSLQRUULQJFDEOHOXJ
6WDQGDUG,3&:+0$$$&ODVV
$
6LJQDOFRQGXFWRUVVKDOOEHEOXHPPð
4 4 4
$ $ $
,! ,! ,! ,! ,! ,! ,! ,! ,!
&
&
'
4.4
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
%.
%.
%.
PPð
PPð
PPð
%.
%.
%.
%.
%.
%.
%.
%.
%.
%
PPð
PPð
PPð
%.
%.
%.
.
'
&
4
.
.
.
Control cabinet / Circuit diagram
)
.
.
.
7
7
7
&
9025776_ 1
PPð
PPð
PPð
%.
%.
%.
'
;
: 3(
(;732:(56833/<
[ : %. %1 *< *1<(
6833/<9$& [
0D[IXVH$ / 5 / 6 / 7 3( ),/7(502725
3( 6833/<
),/7(5-%
; / / / 3(
(
:0 %. %1 *< *1<(
*
),/7(502725
6833/<
0
(;7 / / / 3(
9$&+]
/ / / 3(
3KDVH
0
0
0D[N$
3RZHUFRQVXPSWLRQLVSXPSRSWLRQGHSHQGHQW
Book No.9028195 02
5HFRPHQGHGIXVH$
)
),/7(502725
Drawings
6833/< 0
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVW && SDJH
4.4.2
(G 6(78-$' &&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&RQWUROFDELQHW &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
4
$
$
$
$
.
.
.
4
4
$
4
PPð
PPð
PPð
%.
%.
%.
PPð
PPð
PPð
PPð
PPð
PPð
%.
%.
%.
%.
%.
%.
.6
'
%
. . .
' ' '
) ) ) ) ) ) )
& & & & & & &
$ $ $
&
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
%.
%.
%.
%.
%.
%.
%.
%.
%.
9025776_ 2
$ $ $ $
. . . .
0 $ 0 $ 0 $ 0 $
'
; ; ;
3( 3( 3(
: %1 %. *< *1<( : %1 %. *< *1<( : %1 %. *< *1<(
;
[ [ [
(
06833/< 06833/< 06833/<
0
0
0
/ / / 3( / / / 3( / / / 3(
Electrical drawings
0
0 0
0 0
0
& % % %
& % % %
& % % %
$ % & &
,1&/8'(',)%2267(53803 237,21 ,1&/8'(',)%2267(53803 237,21 ,1&/8'(',)%2267(53803 237,21
)
%2267(53803 %2267(53803 %2267(53803
0 0
&XUUHQWSDJH
0
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&RQWUROFDELQHW &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4.4
86
4 Drawings 4.4 Electrical drawings
SDJH
3UHY
'
&
$
%
(
)
0RGLILFDWLRQ
3RZHUVXSSO\
4
4
4
9$
XQLW
7
)
'DWH
(OHFWURQLFIXVH
PPð PPð
/2$'
$&
%8 %8
/
,&
6(75(6(7
$&
67$786
PPð
1DPH
*1'
/
1&
%8
$&
/
PPð
;
%8
%XVEDU
%XVEDU
PPð PPð
2ULJLQDO
$SSU
(G
'DWH
3(
*1<( *1<(
3(
$
3(
6(78-$'
6(78-$'
.6
'&2.
,,1
6:
5HSODFHPHQWRI
3XUH%DOODVW
)
(OHFWURQLFIXVH
/2$'
,&
6(75(6(7
67$786
*1'
1&
;
%XVEDU
5HSODFHGE\
;
; $
$ 23
; .6
&XUUHQWSDJH
9'&SRZHU
(OHFWURQLFIXVH
/2$'
;
,&
6(75(6(7
&&
67$786
*1' $
1&
;
;
.6
+
4
'RFXPHQW1R
)
6:
)
&XVWRPHUGHVFULSWLRQ
(OHFWURQLFIXVH
/2$'
,&
6(75(6(7
67$786
*1'
1&
;
;
;
&XUUHQWSDJH
&&
;
3%
$
SDJH
1H[W
9025776_ 3
Book No.9028195 02 87
4.4 Electrical drawings 4 Drawings
SDJH
3UHY
'
&
$
%
(
)
$
0RGLILFDWLRQ
% 5;&3
(
'DWH
$
,)
,)
% 5;,)
(
1DPH
$
% 5;,)
(
2ULJLQDO
$SSU
(G
'DWH
$
6(78-$'
6(78-$'
% 5;,)
(
,QVWDOOHGLIUHPRWHLQWHUIDFH RSWLRQ
$
% 5;',
)
5HSODFHPHQWRI
3XUH%DOODVW
$
% 5;',
)
$
% 5;',
)
5HSODFHGE\
$
% 5;$,
)
$
&XUUHQWSDJH
% 5;$2
$
$
% 5;36
3/&OD\RXW
$
&&
$
% 5;'2
$
$
% 5;'2
$
'RFXPHQW1R
$
% 5;'2
$
$
&XVWRPHUGHVFULSWLRQ
% 5;'2
$
$
% 5;'2
$
$
% 5;'2
$
&XUUHQWSDJH
&&
3%
SDJH
1H[W
9025776_ 4
88 Book No.9028195 02
89
Electrical drawings
;
;
;
;
;
;
;
$
23
&RQWUROSDQHO 6: &20 9$ 9%
/DQ$ /DQ%
86% 86% ; ; ; ;
4.4
,1 287
7' 5'
86%
%
:)
:/$1 2SWLFILEHUFDEOHPXOWLPRGH
86%
&$7H6)873 FDEOH [P 5; 7;
'RRU
5; 7;
5&3
:)
&
&&
9025776_ 5
'
:/$1 :/$1
&$7H6)873 &$7H6)873 FDEOH
;
$ ; ; ; ; ; ; ,) ,)
5-
& 9'& 9'& *1' 9'& 9'& *1' ,) ,)
6+
( (WKHUQHW (3/
,) ,)
:
;&3 ; &$7H6)873
86% 5(027(&21752/3$1(/
,),)
/$1&211(&7,21 2*:+ 2* *1:+ %8 %8:+ *1 %1:+ %1 6+
56
,)
7;' 5;' *1' 86% 86% 6+/' 6+/'
; ; ; ,) ,) ; ;
9 6+
Book No.9028195 02
86%
5&3
:
)
Drawings
86%
&&
'RRU
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&&38 &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
;
;
:
:
4
$
/'&
/'&
6+ 6+
%
2*:+
2*:+
*1:+
*1:+
%1:+
%1:+
%8:+
%8:+
:/$1 :/$1
2*
2*
*1
*1
%1
%1
%8
%8
&$7H6)873 &$7H6)873
&
; ;
9025776_ 6
6+ 6+
5- 5-
'
:/$1 :/$1
&$7H6)873 FDEOH &$7H6)873 FDEOH
(
$
&
Electrical drawings
(3/ (3/
,) ,)
) ;,)
),567/'&
,17(5)$&(
&211(&7,21
/$67/'&
,17(5)$&(
&211(&7,21
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&,QWHUIDFH &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4.4
90
91
Electrical drawings
*36
,17(5)$&(
$
D E 6+
4.4
%
:
6LJQDO
FDEOH
VKLHOGHG
6+
$
%
[[
&
9025776_ 7
;
9,36&'68%0 6+'
6+
'
:
&$%/('68%
(
$
& 6+/' 7;'5HV 5;''$7$ 5HV *1' 9P$ 7;'?5HV 5;'?'$7$ 5HV
Book No.9028195 02
5656
) ;,)
Drawings
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&*36LQWHUIDFH &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
6+,36<67(0
$ 5,
4
%
:
6LJQDO
FDEOH
VKLHOGHG
& [[ $ $ % % 6+
9025776_ 8
;
9,36&'68%0 6+'
5,FRQQHFWLRQ
7HUP '$7$
6+ 7HUP 6LJQDOJQG
'
: 7HUP '$7$?
&$%/('68%
5,FRQQHFWLRQ
7HUP 7['
7HUP 5['
7HUP 6LJQDOJQG
7HUP 7['?
7HUP 5['?
(
$ 'HIDXOWFRQQHFWLRQ
&
Electrical drawings
92
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
93
Electrical drawings
.6
)
;
;
$
4.4
%
4 ) ) ) )
$ & & & &
&
4
9025776_ 9
$
'
4
$
(
$
& ', ', ', ', ', ', ', ', ', ', ', ',
Book No.9028195 02
) ;',
Drawings
6<67(06723)520
6$)(7<5(/$<.6
'&)86(
$/$50
06&2021
)86($/$50
),/7(502725
$/$50
0
$/$50
0
$/$50
&XUUHQWSDJH
0
$/$50
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&'LJLWDOLQSXW &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
(;7
9
9
9
9 9 9 9 9
2SHQ 2SHQ 2SHQ 2SHQ
$
4
3(
3(
3(
3(
2SHQ
2SHQ 2SHQ 2SHQ 2SHQ
&ORVH &ORVH &ORVH &ORVH &ORVH
%
3(
3(
: : $ % $ % : : : :
6LJQDO 6LJQDO 6LJQDO 6LJQDO 6LJQDO 6LJQDO
FDEOH FDEOH 3( FDEOH FDEOH FDEOH FDEOH
VKLHOGHG 3(
[ [[ [ [ [ [
;
;
;
;
;
;
;
;
;
;
&
; ;
&
; ;
%% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $
%% .
;
9025776_10
; .
%%
. . . . . . . . . . . .
'
%%
; .
%%
; ;
(
:
: (
[ %. %1 5' 2* <( *1 %8 97 [ %. %1 5' 2*
Electrical drawings
$
& ', ', ', ', ', ', ', ', ', ', ', ',
) ;',
9
&/26(23(1
9
&/26(
9
&/26(23(1
&XUUHQWSDJH
9
&/26(23(1
9
&/26(23(1
9
&/26(23(1
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 3/&'LJLWDOLQSXW &XUUHQWSDJH
94
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
95
Electrical drawings
6+,36<67(0
(;$03/(&211(&7,21
$
4.4
%
: :
6LJQDO 6LJQDO
FDEOH FDEOH
VKLHOGHG VKLHOGHG
[ [
;
& ;
&
; ;
%% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $ %% $
%%
;.
9025776_11
.
. . . . . . . . . . . .
'
%%
.
;
;
(
:
( :
[ <( *1 %8 97 [ %. %1 5' 2* <( *1 %8 97
$
& ', ', ', ', ', ', ', ', ', ', ', ',
Book No.9028195 02
) ;',
Drawings
(;7(51$/
6<67(06723
(;7(51$/
%<3$6623(1
(;7(51$/
%<3$6623(1
(;7(51$/
%<3$6623(1
(;7(51$/
)(('%$&.
%:3803581
(;7(51$/
)(('%$&.
29(5%2$5'
&XUUHQWSDJH
9$/9(23(1
+((/,1*02'( (;7(51$/
)(('%$&.
675,33,1*3803581
306
*5$17('
306
*5$17('
306
*5$17('
306
*5$17('
&20021
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&'LJLWDOLQSXW &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
(;7
),7 37 37 37
6,* 6,*
$
3(
'& '&
'& '&
4
%
: %1 %8 :+ %. : %1 %8 :+ %.
: $ $ % % : % $
0)6 0)6
6LJQDO 6LJQDO
[ [
FDEOH FDEOH
VKLHOGHG VKLHOGHG
[[ [[
;
),/7(5-%
&
9025776_12
:
6LJQDO
FDEOH
'
VKLHOGHG
[[ % $ % $
; ;
%XVEDU %XVEDU
; ;
(
;
Electrical drawings
;
$
& $,, $,8 $,8, $,, $,8 $,8, $,, $,8 $,8, $,, $,8 $,8,
) ;$,
),7
6<67(0:$7(5
)/2:
37
6<67(035(6685(
&XUUHQWSDJH
37
35(6685(6(1625
37
35(6685(6(1625
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 3/&$QDORJLQSXW &XUUHQWSDJH
96
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
97
Electrical drawings
$ $ ;$2
&
3$: 3$: $28, 3$: 3$: $28,
4.4
%
&XUUHQWP$ 0D[ORDG
; /RDG
; /RDG
; ;
&
9025776_13
:
6LJQDO
FDEOH
VKLHOGHG
'
[
(
9
9
(;7
6+,36<67(0
Book No.9028195 02
)
Drawings
9 ([WIHHG
DQDORJXHRXW
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&$QDORJRXWSXW &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
$ $ ;36
&
4
9,2 9,2 *1'
.
'
% .
'
.
'
&
(6 .
'
9025776_14
'
.6
6 6 6 6 6
&
%
$ $ 0
(
Electrical drawings
;
;
$
;
;
)
32:(5
6833/<
&XUUHQWSDJH
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 3/&3RZHUVXSSO\ &XUUHQWSDJH
98
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
99
Electrical drawings
$ $ ;'2
&
'2 '2 '2 '2 '2 '2 '2 '2 '2 '2 '2 '2
PLQPPð
4.4
;
%
;
; 3( 3(
5'
0
0
)DQ
&
%/
+
.6
;
9025776_15
[ [
[
'
:
6LJQDO
FDEOH
[
PLQPPð
(
&,3 $ % $ % $ % $ % $
3( 3(
;
Book No.9028195 02
&20 &20 &20 &20 &20 &20 &20 &20 &20
)
Drawings
$ $ ;'2
&
4
12 &20 12 &20 12 &20 12 &20 12 &20 12 &20
%
;
&
3(
3(
9025776_16
'
:
6LJQDO
FDEOH
VKLHOGHG
[
(
Electrical drawings
6+,36<67(0
)
306
5(4
306
5(4
306
5(4
&XUUHQWSDJH
306
5(4
&20021
306
581
306
581
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
100
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&'LJLWDORXWSXW &XUUHQWSDJH
101
Electrical drawings
$ $ ;'2
&
12 &20 12 &20 12 &20 12 &20 12 &20 12 &20
4.4
; $
%
%XVEDU
;
;
&
9025776_17
'
:
6LJQDO
FDEOH
VKLHOGHG
[
(
6+,36<67(0
9
9
9
9
9
9
9
9
Book No.9028195 02
)
Drawings
306
581
306
581
&20021
9
&XUUHQWSDJH
$ $ ;'2
&
4
12 &20 12 &20 12 &20 12 &20 12 &20 12 &20
$
%
;
; ;
&
3(
3(
9025776_18
: $ % :
6LJQDO 6LJQDO
FDEOH FDEOH
'
VKLHOGHG VKLHOGHG
[[ [
),/7(5-%
; 3(
: %8 %. %1 :+ *<
( 0)6
[
(;7
Electrical drawings
)
6+,36<67(0
9
),/7(5
%$&.:$6+
9$/9(
&XUUHQWSDJH
&20021
:$51,1*
&20021
$/$50
5(48(67/'&
%2267(53
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
102
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&'LJLWDORXWSXW &XUUHQWSDJH
103
Electrical drawings
$ $ ;'2
&
12 &20 12 &20 12 &20 12 &20 12 &20 12 &20
4.4
%
;
&
9025776_19
:
'
: '
6LJQDO
FDEOH
VKLHOGHG
[
(
Book No.9028195 02
) 6+,36<67(0 6+,36<67(0
Drawings
5(48(67$27
%2267(53
5(48(6767$57
%:3803
5(48(67
23(129(5%2$5'
9$/9(
&XUUHQWSDJH
385(%$//$67
581
5(48(6767$57
675,33,1*3803
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&'LJLWDORXWSXW &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
$ $ ;'2
&
4
$ &20 $ &20 $ &20 $ &20 $ &20 $ &20
%
;
.6
'
&
9025776_20
:
'
%
;
)
)
)
(
Electrical drawings
)
6+,36<67(0
5(48(67),/7(5
%$&.)/3
&XUUHQWSDJH
104
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&'LJLWDORXWSXW &XUUHQWSDJH
105
Electrical drawings
$
4.4
%
;.
;.
;.
&
9025776_21
; 3(
3(
'
: :
6LJQDO 6LJQDO
FDEOH FDEOH
[ [
(;7 6+,36<67(0
9 8
2SHQ
(
&ROVH
3(
3(
)%VLJQDOWRVKLSVV\VWHP
2SHQ
)%VLJQDOWRVKLSVV\VWHP
&ORVH 9'&IRU)%VLJQDOIURPVKLSVV\VWHP
9
9'&IRUSLORWYDOYHIURPVKLSVV\VWHP
Book No.9028195 02
)
Drawings
9
)(('%$&.
&21752/&$%,1(7
9
23(5$7,21)(('%$&.
6+,36<67(0 &&&211(&7,21
&XUUHQWSDJH
9
23(5$7,21)(('%$&.
6+,36<67(0
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
%\SDVVFRQWURO%\SDVVYDOYHFRQQHFWLRQ &XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4
Book No.9028195 02
Drawings
$OID:DOOB)B
WRWKHH[WHQWH[SUHVVO\DJUHHGXSRQ
7KLVGRFXPHQWPD\FRQVWLWXWHD
FRQWUDFWXDOREOLJDWLRQRQWKH
&DEOHVXVHGVKRXOGEHVKLSERDUGFDEOHVGHVLJQHG
SDUWRI$OID/DYDO$%RQO\
$
12 7<3( 6RXUFH IURP ,16758&7,21 7DUJHW WR 5(0$5.
DFFRUGLQJWR,(&
4
%
: [ && ;. 6+,36<67(0 8 [ SURGXFHUV1H[DQV6ZHGHQ
7KLVGRFXPHQWDQGLWVFRQWHQWVLVRZQHGE\$OID/DYDO$% SXEO DQGSURWHFWHGE\ODZVJRYHUQLQJLQWHOOHFWXDOSURSHUW\DQGWKHUHWRUHODWHGULJKWV:LWKRXWOLPLWLQJDQ\ULJKWV
9025776_30
: [ && ; 0 0 [
: [[ && ; 66& (;7 37 [
Control cabinet / Cable list
5(0$5.6
[ )HHGEDFN RSHQFORVHVLJQDOIRUE\SDVVYDOYH [[[FDQEHLQWHJUDWHGLQVDPHFDEOH
Electrical drawings
4.4.3
3UHY 'DWH 'RFXPHQW1R 3% 1H[W
SDJH
(G 6(78-$' 3XUH%DOODVW && &&
SDJH
106
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
4.4 0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ &DEOHOLVW &XUUHQWSDJH
4 Drawings 4.4 Electrical drawings
'
&
$
%
(
)
'DWH
(;7 /'&
/ 5 / 5
/ [ /
32:(56833/<
/ 6 / 6
/ : / 4
1DPH
/ 7 / 7
/ /
/'&
3( 3(
3( 3( 3(
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
$27 /'&
5HSODFHPHQWRI
3XUH%DOODVW
)LOWHUW\SH
[
6,*1$/&$%/(
;$
:$
;
$27 /'&
6+ 6+
-%$ 3( 3( 3(
5HSODFHGE\
$27 /'&
&XUUHQWSDJH
,QWHUFRQQHFWLRQGLDJUDP
/'&
[
6,*1$/&$%/(
;$ ;
:%
'RFXPHQW1R
$27 /'&
6+ 6+
-%$ 3( 3( 3(
&XVWRPHUGHVFULSWLRQ
$27 /'&
[
/$03&$%/(
:$
;% ;
&XUUHQWSDJH
/'&
3%
SDJH
1H[W
581770_18
Book No.9028195 02 107
4.4 Electrical drawings 4 Drawings
SDJH
3UHY
'
&
$
%
(
)
'DWH
$27 /'&
[
/$03&$%/(
;% :$ ;
1DPH
$27 /'&
6+ 6+
-%% 3( 3( 3(
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
$27 /'&D
5HSODFHPHQWRI
3XUH%DOODVW
)LOWHUW\SH
[
/$03&$%/(
;%
:%
;
$27 /'&
6+ 6+
-%% 3( 3( 3(
5HSODFHGE\
$27 /'&E
&XUUHQWSDJH
[
/$03&$%/(
;%
:&
;
,QWHUFRQQHFWLRQGLDJUDP
/'&
$27 /'&D
6+ 6+
-%% 3( 3( 3(
'RFXPHQW1R
$27 /'&E
[
&XVWRPHUGHVFULSWLRQ
/$03&$%/(
;%
:'
;
$27 /'&E
6+ 6+
-%% 3( 3( 3(
&XUUHQWSDJH
/'&
3%
SDJH
1H[W
581770_19
6LJQDOFRQGXFWRUVVKDOOEH
EOXHPPð
; / / / /
6XSSO\EORFN / / / /
$
/ / / /
/ /
PPð
PPð
PPð
/ /
%.
%.
%.
/ /
PPð
PPð
PPð
%.
%.
4.4
,!! ,!! ,!! ) ) ,!! ,!! ,!! ,!! ,!! ,!!
3(
%
Lamp Drive Cabinet (LDC) / Circuit diagram
PPð
PPð
PPð
PPð
PPð
PPð
PPð
=
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
%.
%.
%.
%.
%.
%.
%.
%.
%.
%.
%.
%.
/ / /
%.
%.
%.
*1<(
(0&ILOWHU
/2$'
/,1(
/ / /
&
7
7
7
; 8 9 : 3(
PPð
PPð
PPð
%.
%.
%.
*1<(
0 ./
3(
4 )DQ
;7 / / / SKDVH
/, 0 0
'
W V a
6,
W V
,,
/2&
/ / /
./ ./
1& &20 *1' 9
( :
%8
<(
(;732:(56833/<
[
32:(56833/< / 5 / 6 / 7 3(
;
(;7
/ / / 3(
9$&
;
;
;
;
;
;
;
;
;
Book No.9028195 02
+]SKDVH
E
E
E
D
D
D
(OHFWULFDOSRZHU
GLVWULEXWLRQFHQWUDO
4
4
4
$
;
$
$
4
4
4
4
4
4
Drawings
)
4.4.5
5&3
6833/<9$& 6833/<
44
&XUUHQWSDJH
)$1&,5&8,7 6833/<
44
6833/<
44
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVW /'& SDJH
581770_1
(G 6(78-$' /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3RZHUVXSSO\ODPSGULYHFDELQHW &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
;
4
;
4
;
4
$
4
/ / /
/ / /
/ / /
4 4 4
$ $ $
,! ,! ,! ,! ,! ,! ,! ,! ,!
%
%
&
3( 3( 3(
%
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
*1<(
*1<(
*1<(
:+
:+
:+
%1
%1
%1
%.
%.
%.
: : :
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
*1<(
*1<(
*1<(
&
:+
:+
:+
%1
%1
%1
%.
%.
%.
/36 /36 /36 /36 /36 /36
& / / / 3( & / / / 3( & / / / 3( & / / / 3( & / / / 3( & / / / 3(
/DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387
SRZHU SRZHU SRZHU SRZHU SRZHU SRZHU
VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387
3( 3( 3( 3( 3( 3(
'
: : : : : :
/36 /36 /36 /36 /36 /36
[ [ [ [ [ [
(
;
;
;
;
;
Electrical drawings
;
;
;
;
D
D
D
D
:$ :%
/36FDEOH /36FDEOH
[ [
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
)
$
$27 ;%
&XUUHQWSDJH
%
$27 ;%
D
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
110
3XUH%DOODVW
581770_2
(G 6(78-$' /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3RZHUVXSSO\ODPSGULYHFDELQHW
111
Electrical drawings
;
4
;
4
;
4
$
4 4
$ $
4.4
,! ,! ,! ,! ,! ,!
&
&
3( 3(
%
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
*1<(
*1<(
:+
:+
%1
%1
%.
%.
: :
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
*1<(
*1<(
&
:+
:+
%1
%1
%.
%.
/36 /36 /36 /36
& / / / 3( & / / / 3( $ / / / 3( $ / / / 3(
/DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387
SRZHU SRZHU SRZHU SRZHU
VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387
3( 3( 3( 3(
'
: : : :
/36 /36 /36 /36
[ [ [ [
(
;
;
;
;
;
;
;
;
;
;
;
;
;
E
E
E
E
;%
;%
;%
;%
:&
/36FDEOH
Book No.9028195 02
[
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
Drawings
)
D
&XUUHQWSDJH
&
$27 ;%
E
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVW /'& SDJH
581770_3
(G 6(78-$' /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3RZHUVXSSO\ODPSGULYHFDELQHW &XUUHQWSDJH D
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
;
4
;
4
;
4
$
4
4 4 4
$ $ $
,! ,! ,! ,! ,! ,! ,! ,! ,!
'
'
'
3( 3( 3(
%
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
*1<(
*1<(
*1<(
:+
:+
:+
%1
%1
%1
%.
%.
%.
: : :
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
PPð
*1<(
*1<(
*1<(
&
:+
:+
:+
%1
%1
%1
%.
%.
%.
/36 /36 /36 /36 /36 /36
$ / / / 3( $ / / / 3( $ / / / 3( $ / / / 3( $ / / / 3( $ / / / 3(
/DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387 /DPS ,1387
SRZHU SRZHU SRZHU SRZHU SRZHU SRZHU
VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387 VXSSO\ 287387
3( 3( 3( 3( 3( 3(
'
: : : : : :
/36 /36 /36 /36 /36 /36
[ [ [ [ [ [
(
;
;
;
;
;
Electrical drawings
D
D
D
D
;%
;%
;%
;%
:'
/36FDEOH
[
/$03
/$03
/$03
/$03
/$03
/$03
/$03
/$03
)
D
E
&XUUHQWSDJH
'
$27 ;%
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
112
3XUH%DOODVW
581770_4
(G 6(78-$' /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH E
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3RZHUVXSSO\ODPSGULYHFDELQHW
4 Drawings 4.4 Electrical drawings
SDJH
3UHY
'
&
$
%
(
)
E
0RGLILFDWLRQ
9$
)
)
)
7
)
PPð
'DWH
(OHFWURQLFIXVH
$&
%8
/
/2$'
,&
$&
6(75(6(7
/
67$786 PPð
*1'
$&
1& %8
1DPH
/
%XVEDU
%XVEDU
;
:$
3(
VKLHOGHG
3(
[
6LJQDO
FDEOH
2ULJLQDO
$SSU
(G
'DWH
3(
;
$
.
6(78-$'
6(78-$'
.6
XQLW
3RZHUVXSSO\
.
'&2.
.
$
,,1
$27 :$
$
$
.6
5HSODFHPHQWRI
3XUH%DOODVW
)LOWHUW\SH
.6
;
PPð
%8
[
[
'RRU
32:(521
:KLWH
+ /6
.
6 +
.
5HSODFHGE\
.
.6
&XUUHQWSDJH
.
)
.
(OHFWURQLFIXVH
/2$'
9'&SRZHU
,&
6(75(6(7
/'&
67$786
*1'
1&
:%
VKLHOGHG
[
6LJQDO
FDEOH
;
;
$
'RFXPHQW1R
$
$
$27 :%
%
+
$
+
*6
$
*6
$
*6
$
*6
$
&XUUHQWSDJH
/'&
3%
SDJH
1H[W
581770_5
'
&
$
%
(
)
0RGLILFDWLRQ
'DWH
1DPH
2ULJLQDO
$SSU
(G
'DWH
6(78-$'
6(78-$'
$
5HSODFHPHQWRI
3XUH%DOODVW
)LOWHUW\SH
% 5;%&
(
,)
,)
$
% 5;36
$
$
5HSODFHGE\
% 5;&6
)
$
% 5;',
)
&XUUHQWSDJH
$
% 5;',
)
3/&OD\RXW
/'&
$
% 5;'2
$
$
% 5;$,
)
$
% 5;$2
'RFXPHQW1R
$
$
% 5;$7
)
&XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
/'&
3%
SDJH
1H[W
581770_6
&&
;
;
:
:
$
&&
&&
4.4
6+ 6+
%
2*:+
2*:+
*1:+
*1:+
%1:+
%1:+
%8:+
%8:+
:/$1 :/$1
2*
2*
*1
*1
%1
%1
%8
%8
&$7H6)873 &$7H6)873
&
; ;
6+ 6+
5- 5-
'
:/$1 :/$1
&$7H6)873 &$7H6)873
(
$
& 5- 5-
(3/ (3/
,) ,)
Book No.9028195 02
;%&
Drawings
)
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVW /'& SDJH
581770_7
(G 6(78-$' /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&%XV &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
&
$
;36
$
4
;
;
;
)
3/&32:(5 3/&
6833/< &20021
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
116
3XUH%DOODVW
581770_8
(G 6(78-$' /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&3RZHUVXSSO\
117
Electrical drawings
:+%17ZLVWHG:LUHV
/36 /36 /36 /36 /36 /36 /36 /36
E& E& E& E& E& E& D& D& PD[PPWXUQ
:+ %1 %1 %1 %1 %1 %1 %1
$
%1 :+ :+ :+ :+ :+ :+ :+
*1' *1' *1' *1' *1' *1' *1' *1'
*1 *1 *1 *1 *1 *1 *1 *1
/36
<( <( <( <( <( <( <( <(
4.4
/36 /36 /36 /36 /36 /36 /36 /36
. & & & & & & D& D&
(
:+ %1 %1 %1 %1 %1 %1 %1
%1 :+ :+ :+ :+ :+ :+ :+
&
*1' *1' *1' *1' *1' *1' *1' *1'
. *1 *1 *1 *1 *1 *1 *1 *1
)
<( <( <( <( <( <( <( <(
[
'
;
;
(
: :+ *1' %1
$
Book No.9028195 02
& 7[' 5[' *1' 7[' 5[' *1'
;&6 56
Drawings
)
02'%86
&211(&7,21
/36
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVW /'& SDJH
581770_9
(G 6(78-$' /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&,QWHUIDFH &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
;
;
;
$
4
4
%
:
% /6
,
4 ,,
%
/LTXLG/HDNDJH ',3
3RLQW6HQVRU 6:,7&+
6(77,1*
4
1&
%
0ƻ
& 4
D%
4
D%
4
E%
'
4
E%
4
E%
.6
.6
)
;
(
Electrical drawings
$ ;
& ( ( ( ( ( ( ( (
', ', ', ', ', ', ', ',
)
;', 0XOWLOLQH ;
/6
76
7(03+,*+ )86($/$50
/3606
$/$50&,5&8,7 )$1$/$50 :$7(5$/$50
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_10
118
(G 6(78-$' 3XUH%DOODVW /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&'LJLWDOLQSXW
119
Electrical drawings
$
4.4
%
.6
;
;
;
;
&
'
(
Book No.9028195 02
$ ;
& ( ( ( ( ( ( ( (
', ', ', ', ', ', ', ',
Drawings
)
;', 0XOWLOLQH ;
923(1 9&/26( 923(1 9&/26( 76
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_11
(G 6(78-$' 3XUH%DOODVW /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&'LJLWDOLQSXW &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
&
$
$
4
;'2
'2 '2 '2 '2 '2 '2 '2 '2 '2 '2 '2 '2
%
&
;
'
: %8 %.
0
.
$ [ +HDW
H[FKDQJH
. +
YDOYH
& $ *UHHQ [
/$0321
'RRU
(
Electrical drawings
;
+
6
;
;
;
;
;
;
)
$&7,9$7(/36 89/$0321 62/(12,'9$/9( 9 9 9
&XUUHQWSDJH
9 9
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_12
120
(G 6(78-$' 3XUH%DOODVW /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&'LJLWDORXWSXW
121
Electrical drawings
;
;
$
4.4
%
&
'
(
$
Book No.9028195 02
& $,, $,8 $,8, $,, $,8 $,8, $,, $,8 $,8, $,, $,8 $,8,
;$,
Drawings
)
896(1625
,1387
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_13
(G 6(78-$' 3XUH%DOODVW /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&$QDORJLQSXW &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
$ $ ;$2
4
&
$2, $28 $28, $2, $28 $28, $2, $28 $28, $2, $28 $28,
%
&
'
(
Electrical drawings
;
;
)
)$1&21752/
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_14
122
(G 6(78-$' 3XUH%DOODVW /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3/&$QDORJRXWSXW
123
Electrical drawings
;
;
;
;
$
4.4
&
. 287
3:5
77 77
[ [ [ [ 9'&
'
; $ % 3(
:
[ :+ 5'
;
;
.6
.6
(
$
Book No.9028195 02
& 6HQVRU 6HQVH 6HQVRU 6HQVRU 6HQVH 6HQVRU 6HQVRU 6HQVH 6HQVRU 6HQVRU 6HQVH 6HQVRU
;$7
Drawings
)
/'&$,5 /'&+($7(;&+$1*( $27
7(03(5$785( :$7(57(03
&XUUHQWSDJH
7(03(5$785(,1387
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_15
(G 6(78-$' 3XUH%DOODVW /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
3/&7HPSLQSXW &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
$
4
.
)
%
.
.
;
;
;
;
&
.6 77 76 /6 /6
$ $ $ $ 9 9 2 2 7 7 7 7 , , , ,
'
, , , , 0 0 0 0 2 2 2 2
76 76 /6 /6
;
(
Electrical drawings
$ [ $
6 . 6 .
) & $ ) [ $ $
5(6(7
'RRU
)
$
$
$
+
;
+
;
&XUUHQWSDJH
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_16
124
(G 6(78-$' 3XUH%DOODVW /'&
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 6DIHW\UHOD\FLUFXLW
125
Electrical drawings
$OID:DOOB)B
WRWKHH[WHQWH[SUHVVO\DJUHHGXSRQ
7KLVGRFXPHQWPD\FRQVWLWXWHD
FRQWUDFWXDOREOLJDWLRQRQWKH
&DEOHVXVHGVKRXOGEHVKLSERDUGFDEOHVGHVLJQHG
SDUWRI$OID/DYDO$%RQO\
$
12 7<3( 6RXUFH IURP ,16758&7,21 7DUJHW WR 5(0$5.
DFFRUGLQJWR,(&
: [ /'& 4 (;7 [ )ODPHUHWDUGHQWDFFRUGLQJWR,(&
:$ [ /'& ; $27 ;$ [ )LUHUHWDUGHQWDFFRUGLQJWR,(&
:% [ /'& ; $27 ;$ [ +DORJHQIUHHDFFRUGLQJWR,(& ,(&
:$ [ /'& ; ,1)250/(1*7+ $27 ;%
)OH[LEOHLQVXODWLQJVOHHYLQJDFFRUGLQJWR,(&
:% [ /'& ; ,1)250/(1*7+ $27 ;%
4.4
%
SURGXFHUV1H[DQV6ZHGHQ
7KLVGRFXPHQWDQGLWVFRQWHQWVLVRZQHGE\$OID/DYDO$% SXEO DQGSURWHFWHGE\ODZVJRYHUQLQJLQWHOOHFWXDOSURSHUW\DQGWKHUHWRUHODWHGULJKWV:LWKRXWOLPLWLQJDQ\ULJKWV
UHODWHGWRWKLVGRFXPHQWQRSDUWRIWKLVPD\EHFRSLHGUHSURGXFHGRUWUDQVPLWWHGLQDQ\IRUPRUE\DQ\PHDQV HOHFWURQLFPHFKDQLFDOSKRWRFRS\LQJUHFRUGLQJRU
:KHUH66&LVLQGLFDWHGLWVKRXOGEHDVLJQDOVKLHOGHGFDEOH
ZLWKWKHVKLHOGSURSHUO\FRQQHFWHGWRHDUWKDVVKRZQLQWKH
HOHFWULFDOGUDZLQJV
5HFRPHQGDWLRQRIYROWDJHFODVV
Lamp Drive Cabinet (LDC) / Cable list
5DWHGYROWDJHRISRZHUFDEOHVN9
& 5DWHGYROWDJHRILQVWUXPHQWDWLRQFDEOHVPLQ9
[&DEOHQRWLQFOXGHGLQ$OID/DYDOGHOLYHU\
'
(
WKHVHHNLQJRIFULPLQDOSURVHFXWLRQ
5(0$5.6
[ )HHGEDFN RSHQFORVHVLJQDOIRUE\SDVVYDOYH [[[FDQEHLQWHJUDWHGLQVDPHFDEOH
[ 6\VWHPVL]HGHSHQGDQW PLQ[PD[[ [[[FDQEHLQWHJUDWHGLQVDPHFDEOH
[ 6\VWHPVL]HGHSHQGDQW PLQFRPPRQDODUP [[[FDQEHLQWHJUDWHGLQVDPHFDEOH
[ 6KLHOGHG&$7HRUEHWWHUPXOWLPRGHILEHUXP 5-FRQWDFW :Q RUILEHU/&FRQWDFW :Q)
Book No.9028195 02
[ &DEOHFURVVVHFWLRQGHSHQGRQOHQJWKDQGFODVVVRFLHW\UHJXODWLRQV
,IPRUHWKDQRQH/'&:QFRQQHFWVEHWZHHQFDELQHWV :Q7\SH/$1&$7H6)873
Drawings
)
4.4.6
&XUUHQWSDJH $27
3UHY 'DWH )LOWHUW\SH 'RFXPHQW1R 3% 1H[W
SDJH
/'& SDJH
581770_20
(G 6(78-$' 3XUH%DOODVW /'&
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&DEOHOLVW &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
4.4 Electrical drawings 4 Drawings
'
&
$
%
(
)
'DWH
9$/9(
9
1DPH
*1<( *1<(
3(
3(
2ULJLQDO
$SSU
(G
'DWH
$27 $27
6(78021$
6(78021$
%1 [ %1
23(1&/26(
)(('%$&.
:+ :*6 :+
9 %8 %8 *6
%. %.
5HSODFHPHQWRI
3XUH%DOODVWSURMHFW
(3/$1
9$/9(
9
*1<( *1<(
3(
3(
5HSODFHGE\
$27 $27
%1 [ %1
23(1&/26(
)(('%$&.
:+ :*6 :+
&XUUHQWSDJH
9 %8 %8 *6
%. %.
,QWHUFRQQHFWLRQGLDJUDP
$27
$27 $27
[
/(9(/6:,7&+
%1 %1
:+ : :+
/6 %8 %8
%. %.
'RFXPHQW1R
$27 $27
%1 [ %1
75$160,77(5
:+ : :+
7(03
77
&XVWRPHUGHVFULSWLRQ
%8 %8
%. %.
6(1625
:+ :+
89
47
%8 %8
7RWDOQRRISDJHV
$27
3%
SDJH
1H[W
126
581771_5
Book No.9028195 02
4 Drawings 4.4 Electrical drawings
SDJH
3UHY
'
&
$
%
(
)
7DUJHW WR 6RXUFH IURP
0RGLILFDWLRQ
[
'DWH
%. %.
89
47
1DPH
[
$27 $27
2ULJLQDO
$SSU
(G
'DWH
:
6:,7&+
%1 %1
7(03
76 :+ :+
6(78021$
6(78021$
%8 %8
%. %.
5HSODFHPHQWRI
3XUH%DOODVWSURMHFW
(3/$1
9$/9(
9
*1<( *1<(
3(
3(
5HSODFHGE\
9$/9(
9
*1<( *1<(
3(
3(
&XUUHQWSDJH
,QWHUFRQQHFWLRQGLDJUDP
9$/9(
$27
9
*1<( *1<(
3(
3(
'RFXPHQW1R
&XVWRPHUGHVFULSWLRQ
7RWDOQRRISDJHV
$27
3%
SDJH
1H[W
581771_6
;
;
;
;
/'&$
/'&%
/'&&
/'&'
/'&
/'&
/'&D
/'&E
$
4
-%%
% ;%
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:$
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
:%
&
UV reactor / Circuit diagram
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
'
% % % % % % % % % % % % % % % %
/$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03 /$03
(
Electrical drawings
)
/'&
&XUUHQWSDJH
4.4.8
3UHY 'DWH (3/$1 'RFXPHQW1R 3% 1H[W
SDJH
$27 SDJH
128
3XUH%DOODVWSURMHFW
581771_1
(G 6(78021$ $27
4.4 $SSU 6(78021$ &XVWRPHUGHVFULSWLRQ
7RWDOQRRISDJHV
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ 3RZHUVXSSO\$27
129
Electrical drawings
/'&
;
$
/'&
$
-%$
4.4
;$
%
&
: %1 :+ %8 %. : %1 :+ : %1 :+ %8 %.
0 0 0
[ [ [
'
(
77 76 47
Ĭ
Book No.9028195 02
Drawings
)
7(03(5$785(
75$160,77(5
7(03(5$785(
&XUUHQWSDJH
6:,7&+
89
6(1625
3UHY 'DWH (3/$1 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVWSURMHFW $27 SDJH
581771_2
(G 6(78021$ $27
$SSU 6(78021$ &XVWRPHUGHVFULSWLRQ
&RQWUROFLUFXLW$27 $ 7RWDOQRRISDJHV
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
/'&
%
/'&
$
4
-%$
% ;$
[ + [ +
89/$03 32:(5
[ 21 [ 21
*5((1 :+,7(
3(
&
3( 3( 3( 3( 3(
*6
*6
%1 %8 %. *1<( *1<( *1<( *1<( *1<( %1 :+ %8 %. %1 :+ %8 %.
: : : : : : :*6 :*6
' 0 0)6 0)6 0)6 0)6 0)6 0 0
[ [ [
(
Electrical drawings
3( 3( 3( 3( 3(
/ $ / $ / $ / $
0$; 0,1
$ $
32:(5 )$,/85( :(7 $ $
21 )/$6+,1* 6(1625
*5((1 5(' <(//2:
/6 9 9 9 9 9 9*6 9*6
)
9$/9( 9$/9( 9$/9( 9$/9( 9$/9( 23(1&/26( 23(1&/26(
/(9(/6:,7&+ )(('%$&. )(('%$&.
&XUUHQWSDJH
3UHY 'DWH (3/$1 'RFXPHQW1R 3% 1H[W
SDJH
$27 SDJH
130
3XUH%DOODVWSURMHFW
581771_3
(G 6(78021$ $27
4.4 $SSU 6(78021$ &XVWRPHUGHVFULSWLRQ
7RWDOQRRISDJHV
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ &RQWUROFLUFXLW$27 %
131
Electrical drawings
$OID:DOOB)B
WRWKHH[WHQWH[SUHVVO\DJUHHGXSRQ
7KLVGRFXPHQWPD\FRQVWLWXWHD
FRQWUDFWXDOREOLJDWLRQRQWKH
&DEOHVXVHGVKRXOGEHVKLSERDUGFDEOHVGHVLJQHG
SDUWRI$OID/DYDO$%RQO\
$
12 7<3( 6RXUFH IURP ,16758&7,21 7DUJHW WR 5(0$5.
DFFRUGLQJWR,(&
: 0)6 $27 $27 9 )ODPHUHWDUGHQWDFFRUGLQJWR,(&
:*6 [ $27 *6 $27 9*6 )LUHUHWDUGHQWDFFRUGLQJWR,(&
: 0)6 $27 $27 9 +DORJHQIUHHDFFRUGLQJWR,(& ,(&
:*6 [ $27 *6 $27 9*6
)OH[LEOHLQVXODWLQJVOHHYLQJDFFRUGLQJWR,(&
: [ $27 $27 /6
4.4
%
: 0)6 $27 $27 9 SURGXFHUV1H[DQV6ZHGHQ
7KLVGRFXPHQWDQGLWVFRQWHQWVLVRZQHGE\$OID/DYDO$% SXEO DQGSURWHFWHGE\ODZVJRYHUQLQJLQWHOOHFWXDOSURSHUW\DQGWKHUHWRUHODWHGULJKWV:LWKRXWOLPLWLQJDQ\ULJKWV
(
5(0$5.6
WKHVHHNLQJRIFULPLQDOSURVHFXWLRQ
Book No.9028195 02
[ &DEOHFURVVVHFWLRQGHSHQGRQOHQJWKDQGFODVVVRFLHW\UHJXODWLRQV
,IPRUHWKDQRQH/'&:QFRQQHFWVEHWZHHQFDELQHWV :Q7\SH/$1&$7H
Drawings
)
4.4.9
&XUUHQWSDJH
3UHY 'DWH (3/$1 'RFXPHQW1R 3% 1H[W
SDJH
3XUH%DOODVWSURMHFW $27 SDJH
581771_7
(G 6(78021$ $27
$SSU 6(78021$ &XVWRPHUGHVFULSWLRQ
&DEOHOLVW 7RWDOQRRISDJHV
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
6LJQDOFRQGXFWRUVFDQEHPPðLIQRWRWKHUZLVHVWDWHG
6LJQDOFRQGXFWRUVVKDOOEHEOXHLIQRWRWKHUZLVHVWDWHG
,QVXODWHGHQGIHUUXOHVVKDOOEHXVHG
$
4
23
7RXFKSDQHO
4.4.10 Remote control panel (optional) / Circuit diagram
5LQJIRU0
3(
9'&9 $ /$1$ /$1%
*1'
%
86% &20
5
6
2Q2II
'RRU
:86%
&
+
'RRU 2SWLRQDO
6: &20 9$ 9% 9'& P$
86% [ [
'RRU
[ :/$1 ; ; ; ;
/&,1 /&287
&$7H6)873 7' 5'
'
*1<( PPð
*1<( PPð
7; 5;
:/$1 &RQQHFWWR23/$1$
&$7H6)873 LI6:LVQRWSUHVHQW
;
5-
(
; 3( 6+
PPð
9
*1<(
6+
Electrical drawings
:
(;7 3( 3( &&
9 9 5LQJIRU0 5LQJIRU0
9'&
PPð
: :)
*1<(
P
)
5LQJIRU0
&XUUHQWSDJH
3UHY 6(78-$' 'DWH 'RFXPHQW1R 5&3 1H[W
SDJH
5&3 SDJH
132
(G 6(78-$' 5&3
9015558
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
??ORFDOVHWXILOHVDOIDODYDORUJ?'HSDUWPHQWB6(78?6.?3&%DOODVW?(OHFWULF3?3URMHFWV?$OID/DYDO??HOO 5&3
133
Electrical drawings
$
7
6RXUFH IURP
4.4
8 9 : 3(
4.4.11 Transformer (optional) / Interconnection diagram
/ 5
/ 7
/ 6
%
:
[
&
;
/ 5
/ 7
/ 6
7DUJHW WR
/ / / 3(
'
([W
Book No.9028195 02
Drawings
)
&URVVVHFWLRQGHSHQGVRQ
VKLSVYROWDJHDQGSRZHU
RI3XUH%DOODVWV\VWHP
&XUUHQWSDJH
3UHY 'DWH (3/$1 'RFXPHQW1R 7UDQVIRUPHU 1H[W
SDJH SDJH
9028912_2
(G 6(78-$' 7UDQIRUPHU
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
,QWHUFRQQHFWLRQGLDJUDP &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Book No.9028195 02
Drawings
$
4
%
9WR3XUH%DOODVWV\VWHP
4.4.12 Transformer (optional) / Circuit diagram
8 9 :
7 %ROWVLQVLGHWUDQVIRUPHUFDVLQJ
&
3(
8 9 :
:
[
&URVVVHFWLRQGHSHQGVRQ / 5 / 6 / 7
VKLSVYROWDJHDQGSRZHU
' RI3XUH%DOODVWV\VWHP
(;7
9$&+]3KDVH
6KLSVSRZHU
/ / / 3(
5 6 7
(
Electrical drawings
)
&XUUHQWSDJH
3UHY 'DWH (3/$1 'RFXPHQW1R 7UDQVIRUPHU 1H[W
SDJH SDJH
9028912_1
134
(G 6(78-$' 7UDQIRUPHU
4.4 $SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&XUUHQWSDJH
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\ &RQQHFWLRQ
135
Electrical drawings
$OID:DOOB)B
WRWKHH[WHQWH[SUHVVO\DJUHHGXSRQ
7KLVGRFXPHQWPD\FRQVWLWXWHD
FRQWUDFWXDOREOLJDWLRQRQWKH
&DEOHVXVHGVKRXOGEHVKLSERDUGFDEOHVGHVLJQHG
SDUWRI$OID/DYDO$%RQO\
$
12 7<3( 6RXUFH IURP ,16758&7,21 7DUJHW WR 5(0$5.
DFFRUGLQJWR,(&
: [ 7 ([W ; )ODPHUHWDUGHQWDFFRUGLQJWR,(&
)LUHUHWDUGHQWDFFRUGLQJWR,(&
+DORJHQIUHHDFFRUGLQJWR,(& ,(&
)OH[LEOHLQVXODWLQJVOHHYLQJDFFRUGLQJWR,(&
4.4
2WKHUHTXLYDOHQWDQGDSSURYHGFDEOHVPD\EHXVHG
&DEOHDUHDVDUHFDOFXODWHGZLWKFRUUHFWLRQIDFWRU
&RGHGHVLJQDWLRQVIRUFDEOHVREWDLQDEOHWKURXJKFDEOH
RWKHUZLVH RUIRUDQ\SXUSRVHZLWKRXWWKHH[SUHVVHGSHUPLVVLRQRI$OID/DYDO$OID/DYDOZLOOHQIRUFHLWVULJKWVUHODWHGWRWKLVGRFXPHQWWRWKHIXOOHVWH[WHQWRIWKHODZLQFOXGLQJ
%
SURGXFHUV1H[DQV6ZHGHQ
7KLVGRFXPHQWDQGLWVFRQWHQWVLVRZQHGE\$OID/DYDO$% SXEO DQGSURWHFWHGE\ODZVJRYHUQLQJLQWHOOHFWXDOSURSHUW\DQGWKHUHWRUHODWHGULJKWV:LWKRXWOLPLWLQJDQ\ULJKWV
:KHUH66&LVLQGLFDWHGLWVKRXOGEHDVLJQDOVKLHOGHGFDEOH
UHODWHGWRWKLVGRFXPHQWQRSDUWRIWKLVPD\EHFRSLHGUHSURGXFHGRUWUDQVPLWWHGLQDQ\IRUPRUE\DQ\PHDQV HOHFWURQLFPHFKDQLFDOSKRWRFRS\LQJUHFRUGLQJRU
ZLWKWKHVKLHOGSURSHUO\FRQQHFWHGWRHDUWKDVVKRZQLQWKH
HOHFWULFDOGUDZLQJV
5HFRPHQGDWLRQRIYROWDJHFODVV
5DWHGYROWDJHRISRZHUFDEOHVN9
& 5DWHGYROWDJHRILQVWUXPHQWDWLRQFDEOHVPLQ9
4.4.13 Transformer (optional) / Cable list
[&DEOHQRWLQFOXGHGLQ$OID/DYDOGHOLYHU\
'
(
5(0$5.6
WKHVHHNLQJRIFULPLQDOSURVHFXWLRQ
Book No.9028195 02
[ &DEOHFURVVVHFWLRQGHSHQGRQOHQJWKDQGFODVVVRFLHW\UHJXODWLRQV
,IPRUHWKDQRQH/'&:QFRQQHFWVEHWZHHQFDELQHWV :Q7\SH/$1&$7H6)873
Drawings
)
&XUUHQWSDJH
3UHY 'DWH (3/$1 'RFXPHQW1R 7UDQVIRUPHU 1H[W
SDJH SDJH
9028912_3
(G 6(78-$' 7UDQIRUPHU
$SSU 6(78-$' &XVWRPHUGHVFULSWLRQ
&DEOHOLVW &XUUHQWSDJH
4
0RGLILFDWLRQ 'DWH 1DPH 2ULJLQDO 5HSODFHPHQWRI 5HSODFHGE\
Chapter: 7. Service manual
System manual — PureBallast 3.1 1000
USCG
2 Maintenance schedule 9
2.1 Calibration schedule 11
2.2 Recommended spare parts on board 13
2.3 Serial number information 13
2.3.1 Indicating serial number 13
2.3.2 Example 14
4 UV reactor 23
4.1 Safety information 23
4.2 Replace UV lamp and quartz sleeve 25
4.2.1 Disassemble UV lamp 25
4.2.2 Disassemble quartz sleeve 28
4.2.3 Assemble quartz sleeve 28
4.2.4 Check for leaks after quartz sleeve assembly 29
4.2.5 Assemble UV lamp 29
3
4.3 Dismount and mount lamp power
supply (LPS) 30
4.4 Test LPS installation 32
5 Filter 33
5.1 Remove f lter cover and f lter element 36
5.2 Mount f lter element and f lter cover 38
5.3 Clean f lter element and pre-f lter 38
6 CIP module 41
6.1 Change and ref ll CIP liquid 41
6.1.1 Change CIP liquid 43
6.1.2 Refill CIP liquid 43
7 Flow meter 51
7.1 Replace display and fuse 51
8 Valve actuator 53
8.1 Preparations and conditions 54
8.1.1 Tightening torques for actuators 54
4
8.2 Dismount actuator 55
8.3 Mount actuator on valve 55
8.4 Change direction of actuator – without
position sensor (V404–36, V320–4 and
V321–2) 57
8.5 Change direction of actuator – with
switch box (V201–3, V201–9, V201–32,
V212–31 and V403–35) 58
8.6 Change direction of actuator – with
position sensor (201-19 and 201–20) 58
8.7 Change direction of actuator – with
positioner (201–8) 60
8.8 Mount pilot valve on actuator 60
8.9 Adjust valve end position 61
8.10 Adjust valve traveling speed 62
8.11 Calibrate positioner on V201-8 64
8.12 Adjust cam position on V201-8 68
9 Ball valve 69
9.1 Replace seals in ball valve 69
10 Level switch 71
10.1 Mount level switch 71
10.2 Dismount level switch 72
10.3 Test level switch 72
12 Control panel 75
12.1 Clean control panel 75
12.2 Replace control panel 75
cabinet (LDC) 79
1 Introduction
This chapter contains information and instructions about how to service the PureBallast system.
Instructions are sorted per component. The chapter is opened with a maintenance schedule
covering checks and services that must be performed with specified intervals.
NGE R
! DA
• Before maintaining the PureBallast system, the power supply must be switched off, to avoid
accidental starts. See instruction Shut down and deactivate system in chapter 3. Operating
instructions and control system description.
NOTE
• All maintenance and calibration activities must be recorded in the vessel’s maintenance log.
This is required by the ballast water convention. It is therefore recommended that the activities
in the maintenance and callibration schedules below are entered in the vessel’s general
maintenance system.
• Always read and follow the documentation that are included in shipment of components and
spare parts regarding handling, safety and disposal.
• Electrical welding requirements: Connect the welding unit’s negative lead (work lead) to the
component you will weld, close to the welding area.
• Before maintaining the PureBallast system, the following valves must be locked in closed
position: V201-3, V201-9, and V201-8. See instruction Lock valve in closed position on page 20.
• Follow local regulations for electrical installation and grounding (earthing).
• Follow rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
• Point of contact: To order service or spare parts, contact your local Alfa Laval office. For
more information, see www.alfalaval.com.
Book No.9028195 02 7
1.1 Preparations and conditions 1 Introduction
2 Maintenance schedule
Follow this maintenance schedule to secure performance, safety and durability of the system and
its components. The schedule is sorted per component. The table refers to instructions usable
when performing the respective action.
General Testrun the Once a month. See 3. Operating If the system, for
system: Run a instructions and some reason, is not
ballast and/or control system operated by normal
deballast process. description. ballast operations,
Follow up with a it needs to be run
CIP process. Manual operation to verify that it is in
of valves: See good condition.
Note: If system is chapter 7. Service
used, but certain manual, section This will also
valves are not Valves. exercise the valves,
used, for example actuators and other
V212–31, those components to
should be opened keep them in good
and closed condition.
manually. For
relief valves,
see Calibration
schedule.
Book No.9028195 02 9
2 Maintenance schedule
CIP liquid pH value check. Every 3rd months, See Change CIP
whichever comes liquid.
first.
CIP liquid level Rule of thumb: See Change CIP If the CIP liquid
check. Once every 3 liquid or Refill CIP level is low but the
months. liquid. pH value is below
Depending 3, CIP liquid and
on number of water can be added
UV reactor to fill up the liquid
and ballasting level in the tank.
frequency, the liquid Note: pH value
check might have to must be checked
be performed more afterwards to
regularly. secure correct pH
value.
10 Book No.9028195 02
2 Maintenance schedule 2.1 Calibration schedule
1. Connect a calibrated portable ultrasonic flow meter close to the flow meter.
2. Establish flow in the system.
3. Compare value indicated in control system and measure equipment.
Pressure 2. Connect them to an external pressure point and apply higher pressure
transmitter: than approved.
(RV201) 3. Make sure that they relief pressure.
Book No.9028195 02 11
2.1 Calibration schedule 2 Maintenance schedule
Pressure 3. Compare values indicated for the three transmitters in control system
transmitter and measure equipment.
(PT201-16)
4. Open 403-35 from the control system, and compare again.
Pressure gauge PT201-16
(PI201-18)
5. Open V403-35 to apply pressure to the system.
Pressure service
valve (PT201-15) 6. Adjust handle on PT201-16 to establish pressure to measure point.
7. Compare value indicated in control system and measure equipment.
PI201-18
UV reactor 1. Depressurize and drain the reactor: Remove the drain plug at the bottom
components of the UV reactor.
Temperature TT201–33
transmitter
2. Dismount the transmitter and place in water with known temperature
(TT201-33)
(calibrated measure instrument).
Temperature 3. Compare value indicated in the control system and measure equipment.
switch (TS201-
60) TS201-60
Level switch 4. Dismount the switch and place in water with temperature < 65 ˚C.
(LS201-29) 5. Check that alarm A137 is displayed in the control system.
LS201-29
Temperature Place a calibrated thermometer inside the cabinet and compare after 30
transmitter in minutes.
LDC (TT401)
12 Book No.9028195 02
2 Maintenance schedule 2.3 Serial number information
UV reactor
CIP module
Filter
Serial numbers shall be used at error reporting and other contacts where a specific component is
discussed.
Book No.9028195 02 13
2.3 Serial number information 2 Maintenance schedule
• Serial number for the complete PureBallast system. See label on the side of the control cabinet.
• Serial number for the component in question. If the component is installed on, or in, another
component, the number for the mother component shall be stated.
• Item number for the component. The item number identifies a unique component in the system.
It begins with a letter abbreviation indicating the component type, for example: LS (level switch),
P (pump) and PI (pressure gauge). A complete list of abbreviations is found in chapter 6.
Installation description and drawings, section Connection list.
2.3.2 Example
If the level switch is faulty, the following information shall be stated:
14 Book No.9028195 02
2 Maintenance schedule 2.4 Placing of serial numbers
UV reactor
7 AOT Snr
Book No.9028195 02 15
2.4 Placing of serial numbers 2 Maintenance schedule
Filter
7 FilterSnr Filtrex
NOTE
7 LDC sernr
16 Book No.9028195 02
2 Maintenance schedule 2.4 Placing of serial numbers
NOTE
Flow meter
NOTE
Book No.9028195 02 17
2.4 Placing of serial numbers 2 Maintenance schedule
3 Operate valves manually
This section covers instructions on how to open, close and lock/unlock valves manually.
Avoid operating valves manually. Valves are normally operated from page 1.1 Overview in
the control system (manual mode). See chapter 3. Operating instructions and control system
description for instruction.
1. Identify which button (illustrated on page 47) on the valve block that controls the valve. The
lower button operates the inner hose under the valve block, and vice versa. Also see the
sticker under the valve block.
2. Press the button on the valve body with a screw driver to operate the valve.
Position 0 Closed (default position). If the position screw is in position 0 and the valve is
closed, it can be manually opened. But if the position screw is in position 0 and
the valve is opened, it cannot be manually closed.
Position 1 Opened.
1. If there is limited access to the screw, it is possible to remove the DIN connector.
Book No.9028195 02 19
3.3 Lock valve in closed position 3 Operate valves manually
4. When done, turn back the screw to position 0. If the DIN connector was removed, connect it
again.
• Note that the end positions of the end stop bolts are factory adjusted and must not be readjusted.
Follow the steps below
1. Set the valve to closed position from the control system. Control the position indicator, to make
sure. The yellow position indicator is in line with the valve throttle (indicating open when
the position indicator is in line with the pipe).
2. Disconnect power and instrument air. Verify that the valve is not under pressure.
3. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Measure exactly how far out the end stop bolt (4) is from a reference surface, for example the
actuator house. Make a note of the distance. This information is needed when unlocking
the valve.
5. Open the locking bolt (3) and turn them a couple of turns.
6. Screw the end stop bolt (4) to its bottom position and tighten the locking bolt.
20 Book No.9028195 02
3 Operate valves manually 3.4 Unlock valve
8. Slide the safety cover over the end bolts and lock the safety cover with the pad lock.
• Note that the end positions of the end stop bolts are factory adjusted and must not be readjusted.
Follow the steps below
1. Disconnect all power and instrument air. Verify that the valve is not under pressure.
2. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Adjust the end stop bolt (4) to the same position (distance from reference surface) as before
locking the valve, according to the notes made during locking.
NOTE
• It is important to adjust the ends stop bolt to the correct position. Otherwise the actuator
may be damaged.
5. Tighten the locking bolt (3).
Book No.9028195 02 21
3.4 Unlock valve 3 Operate valves manually
7. Slide the safety cover in position over the end stop bolts. Lock the safety cover with the pad
lock.
22 Book No.9028195 02
4 UV reactor
NGE R
! DA
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• Always lock valve V201–9, V201–3 and V201–8 if you open the UV reactor in some way.
See Lock valve in closed position on page .
• UV lamps radiate ultraviolet radiation when lit. Only operate the UV lamp when correctly
installed inside the UV reactor with end caps properly closed.
• Never dismount or handle UV lamps before they are completely cooled down. A hot UV lamp is
under high internal pressure, and the risk of bursting exists. A hot lamp could also cause a
burn if it is touched.
• Before installation, check that the UV lamps and quartz sleeves are not broken.
• UV lamps and quartz sleeves are fragile and can easily become damaged. Exercise great care
when handling them. Do not apply vibrations or shock to the UV lamp. This can cause breakage
and shorten lamp life. Broken glass/quartz can also cause severe cuts. Always use protective
eye glasses and clean cotton gloves when handling UV lamps and quartz glass sleeves.
Book No.9028195 02 23
4.1 Safety information 4 UV reactor
NGE R
! DA
• UV lamps contain a small amount of mercury (less than 0.2 grams per lamp) and must be
handled and disposed of with care. Used lamps UV can be handled and disposed of in the same
way as fluorescent lamps. Please refer to national regulations. If a UV lamp has accidentally
been broken, mercury could be spilt. Remove mercury with a special tool such as a syringe
(or use pure sulphure to bind the mercury for easy collection).
• Do not allow mercury to come in contact with your eyes or skin. Do not inhale mercury fumes.
• Free mercury must be kept in an airtight bottle, and must be disposed of according to
national regulations.
• In case of having inhaled mercury fumes, consult a doctor and follow medical instructions.
24 Book No.9028195 02
4 UV reactor 4.2 Replace UV lamp and quartz sleeve
7 AOTexploded2
1. Cap
2. Cap nut
3. Bush
4. O-ring (inside bush)
5. Cable connector
6. Allen screw
7. Glass socket
8. O-ring
9. UV lamp
10. Quartz sleeve
• The PureBallast system must be turned off, and the power disconnected.
• After UV lamps have been changed, the runtime must be reset in page control system page 4.4
Operation timers UVR 1–3. Requires login level Advanced operator.
Book No.9028195 02 25
4.2 Replace UV lamp and quartz sleeve 4 UV reactor
• Wait at least 10 minutes after completed ballast or deballast process, to allow the UV reactor
to cool down to ambient temperature. If the UV lamps are hot they are under internal positive
pressure and may burst if broken.
NG
WARNI
!
• The UV reactor must not be under pressure when dismounting the UV lamps.
NG
WARNI
!
• Burn hazard: UV lamps can be hot and cause burns.
Follow the steps below
1. Unscrew the cap nuts (2) holding the caps (1). There is one nut on each side of the UV reactor
per UV lamp. If required, use a screwdriver on the nut, gently tapping with a hammer to release.
2. Carefully disconnect the two cable connectors (5) in both ends of the UV lamp (9).
7UVlampConnection
Carefully draw out the UV lamp (9) with the electric cable, by holding the electric cables in
both ends. When pulled out, only hold the UV lamp by the ceramic ends. Immediately after
removal, place the old lamp in the new lamp’s protective cover.
If required, use a screwdriver to press on the ceramic end of the lamp inside the bush on the
other side while carefully pulling the electric cable at the other end.
26 Book No.9028195 02
4 UV reactor 4.2 Replace UV lamp and quartz sleeve
7UVBushScrewdriver
5. If the quartz sleeves is not broken, mount the new UV lamp according to the instruction
Assemble UV lamp on page 29. If broken, follow the instruction Disassemble quartz sleeve
below.
Book No.9028195 02 27
4.2 Replace UV lamp and quartz sleeve 4 UV reactor
1. Close the UV reactor inlet (V201-19.n) and outlet (V201-20.n) valves from the control system
set in manual mode.
4. Disassemble the UV lamp according to the instruction Disassemble UV lamp on page 25.
5. Loosen the three Allen screws (6) of the glass socket (7) on both sides; just a few turns to
release them.
6. Unscrew the Allen screws completely at one side. Carefully remove the glass socket, to avoid
breaking the quartz sleeve. Then remove the glass socket on the other side.
7. Remove the O-rings (8) on both sides. The O-rings are firmly stuck in their seat, and will be
damaged during removal, but shall be replaced at assembly. Use an angled or hooked O-ring
tool to loosen and remove the O-ring. Be careful to avoid to break the glass.
If the O-ring is hard to remove, try the following:
– Moisten the O-ring with acetone or denatured alcohol.
– Loose the O-ring in a couple of places before removing it.
– Perforate the O-ring to get a good grip.
9. Carefully clean the surface and remove any small parts, for example glass or rubber.
2. Check the condition of the glass socket O-rings. If needed, replace them with new O-rings.
28 Book No.9028195 02
4 UV reactor 4.2 Replace UV lamp and quartz sleeve
3. Wet the O-rings (8) with water and some soap and slip them over respective side of the
quartz sleeve.
Check that the O-ring are positioned evenly on both sides. If not, they may be damaged
and cause leaks.
The O-rings shall not be pressed into position, the glass socket will press them into position
when fastened later.
4. Check the condition of the screws. They must be waxed to to avoid seizing.
Carefully mount the glass sockets on both sides on the quartz sleeve. Fasten the glass sockets
with three Allen screws, but do not tighten the screws.
7QuartzSleeve
5. Once the Allen screws (6) are evenly entered, carefully tighten them evenly to a torque of 7 Nm.
8. Follow the instruction Check for leaks after quartz sleeve assembly.
1. Pressurize the UV reactor with water to between 2 and 4 bar (0.2 and 0.4 MPa).
Book No.9028195 02 29
4.3 Dismount and mount lamp power supply 4 UV reactor
(LPS)
• A leakage check must have been performed according to the instruction Check for leaks after
quartz sleeve assembly.
• New heat resistant O-rings must be used in the two bushes. Always replace used O-rings.
• Keep the UV lamp in its protective cover as long as possible. Do not touch the glass of the
lamp; hold the lamp by its ceramic end parts.
• Glass sockets and bushes must be dry and clean before mounting.
• After UV lamps hav e been changed, the runtime must be reset in control system page 4.4
Operation timers UVRs.
Follow the steps below
1. Mount the new heat resistent O-rings in the two lamp bushes (3).
5. Make sure that the connection is clean to ensure good electric connection (no rust, burning or
fading on the connectors). Reconnect the two cable connectors for the UV lamp.
7UVlampConnection
6. Mount the UV lamp caps and tighten the cap nut at both ends of the UV lamp, by hand only.
Make sure that the electric cable is is not squeezed between the cap and the bush when the
cap is mounted. Slack can be pushed into the bush.
7. Control the control system page 3.1 Alarm list, to make sure there is no alarm when after
the the lamp power supply is on.
30 Book No.9028195 02
4 UV reactor 4.3 Dismount and mount lamp power
supply (LPS)
NG
WARNI
!
• Switch off the main breaker on the LDC door. The LPS has high voltage/power (600 V)
inside and on the lamp power connector, even when UV lamps are not lit.
• The LDC contains a fan, which can cause injury if in operation.
Follow the steps below
7 LPSmaint
1. Dismount LPS
Release two power connectors at the bottom of the LPS and the signal cable connector
at the top.
2. Loosen the nuts at the bottom (1) and the top (2) of the two rods holding the LPS. If necessary,
loosen nuts for adjacent LPS.
NOTE
Make sure not to drop the washer into the LPS. It may cause short circuit.
4. Mount LPS
Set the DIP switches on the LPS according to chapter 4. Parameters, section Lamp power
supply (LPS) parameters.
6. Reconnect the three connectors. Make sure the connectors sit tight.
Book No.9028195 02 31
4.4 Test LPS installation 4 UV reactor
9. Switch on the main breaker on the LDC door and check that both LPS:s function correctly
according to instruction Test LPS installation below.
NG
WARNI
!
• This instruction must be performed after cable connection. If not hazardous situation may arise
which, if not avoided, will result in death or serious injury.
NGE R
! DA
• Before operating the UV reactor, make sure that there is water in the UV reactor.
Follow the steps below
2. Check that there is water in the UV reactor(s) (LS201-29). Check the LED on the level switch:
Steady yellow light indicates that there is water in the UV reactor.
3. Switch on the main breaker on the LDC door. Switch on the power to the UV reactor using the
switches on the breaker cabinet(s).
4. Start UV lamps one by one from the control system (set to manual mode). Make sure that the
UV lamps are lit. This is checked in the UV reactor popup and on the LPS.
Note: It can take up to 90 seconds for the lamp to start.
5. Check LEDs on the LPS and the alarm list in the control system. Make sure that no alarms
have been triggered by the LPS.
32 Book No.9028195 02
5 Filter
• Disconnect the power to the filter, using the main switch on the control cabinet.
• Always lock valve V201–3 and V201–32 if you open the filter. See Lock valve in closed position
on page .
• Only perform maintenance and servicing work when the filter is cooled, depressurized and
drained.
• Shut off the air supply to the filter.
• Visually inspect gasket during maintenance. Replace if necessary.
• Lifting device is needed for this instruction.
Filter cover and element weight (kg): 285.
M4 3
M6 7
M8 12
M10 18
M12 25
M14 35
M16 45
M18 60
M20 75
M22 90
M24 105
Book No.9028195 02 33
5 Filter
34 Book No.9028195 02
7 FiltrexExploded
5 Filter
1 Gear reducer
2 Gear shaft
3 Electric motor
4 Thrust bearing flange fixing bolt
5 Gear reducer flange / cover fixing bolt
6 Thrust bearing
7 Backflush shaft bushing gasket
7a Backflush shaft bushing asket
8 Filter vent plug
9 Filter cover
10 Cover bolt
11 Backflush shaft bushing
12 Filter element fixing bolt
13 Filter cover gasket
14 Filter body
15 Filter element
16 Backflush nozzle
17 Filter element gasket
18 Backflush shaft bushing
19 Filter drain plug
20 Backflush line gasket
22 Pressure transmitter
29 Junction box
30 Backflush nozzle support
31 Backflush nozzle fixing bolt
32 Backflush nozzle support gasket
33 Base frame
34 Base frame fixing bolt
40 Ring spear
41 Thrust bearing upper flange
42 Thrust bearing lower flange
43 Seeger
44 Cover lifting lug
45 Rotation indicator
70 Nameplate
80 Prefilter
Book No.9028195 02 35
5.1 Remove filter cover and filter element 5 Filter
1. Close the following valves: V201-3, V201-32, and V310-2 according to the instruction in
the Operate valves manually on page 19.
3. Remove the motor (using a lifting device, if necessary). Be careful not to harm the motor
fitting when lifting it from it’s seat.
7 FilterMotor
4. Remove the cover bolts (10) and the lifting lugs (44).
5. Screw two filter cover bolts in the lifting lugs holes until the cover raises slightly from the filter
house.
7 LiftingBolt
36 Book No.9028195 02
5 Filter 5.1 Remove filter cover and filter element
6. Remove the cover bolts and fasten the lifting lugs in their holes again.
7 LiftingLug
7. Fasten a lifting device in the lifting lugs and lift the filter cover (9) with the filter element carefully
out of the filter.
Note: The filter should be lifted in one continuous movement, without sudden jerks – even if
the filter element is slightly stuck in the filter house.
9. Remove bolts to the bottom shaft support that holds the shaft inside the filter element (15).
Remove it carefully.
10. Remove the seeger ring (43) from the backflush shaft bushing (11).
7 FiltrexSeeger
11. Pull out the backflush shaft bushing. If it is stuck, give a couple of light blows with a wooden
hammer on the top of the shaft to release it.
Book No.9028195 02 37
5.3 Clean filter element and pre-filter 5 Filter
13. Unscrew the four Allen screws inside the element to loosen the filter cover.
7 FiltrexAllenS
15. Lift the pre-filter (80) from the bottom of the filter house.
Note:
• Clean the upper inside of the house. The area where the gasket meet the housing should
be clean.
• No force should be used to fit the filter element in the filter house or to fit the motor in its seat.
• Check the gaskets. Replace if necessary.
• Fill up the filter with technical water / potable water after it is mounted.
• There is not need to de-air the filter when it is filled up.
5.3 Clean f lter element and pre-f lter
Follow this instruction to clean the filter element. At the same time, check that the filter element
is in good condition.
• Alpacon descalant offshore may be used as cleaning agent. See Safety data sheet / CIP liquid
in chapter 6. Installation description and drawings.
• Mixing ratio for Alpacon descalant offshore is 1 part concentrated Alpacon descalant to 20 parts
technical water / potable water. Follow this mixing ratio, regardless of recommendation on label.
• Alpacon descalant offshore storage temperature: 0 °C to +55 °C.
38 Book No.9028195 02
5 Filter 5.3 Clean filter element and pre-filter
NG
WARNI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves and goggles.
Follow rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
NG
WARNI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• The pH value should be approximately 2.0–3.0.
• Proceed with the utmost caution when transporting, assembling, disassembling and cleaning
the filter element.
Follow the steps below
1. Follow the instructions Remove filter element (page 36) to remove the filter element.
4. Soak the filter element in the cleaning agent with the opening facing upwards. Leave it to soak
for 1–4 hours. Let the element dip dry before next step.
5. Place the element in so it does not fall over when cleaning it.
6. Spray the filter element with water (60–80 °C) from the outside, using a flat nozzle. Note: If a
high-pressure cleaner is used, the pressure must not exceed a maximum of 15 bar. If a cleaner
with higher capacity is used, compensate by increasing the distance, minimum 30 cm.
7. Blow the filter element with instrument air (with 10 micron filter or finer), from the outside.
8. Inspect the filter element from the outside with a magnifier to make sure that it is clean. If
needed, repeat the procedure. This time it is enough to let the element soak for 5 minutes.
10. Put the filter element gasket back. Reassemble the rest of the filter.
Book No.9028195 02 39
5.3 Clean filter element and pre-filter 5 Filter
6 CIP module
ON
CAUTI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves and goggles.
Follow rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
ON
CAUTI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• Max tightening torque for bolts on flanges: 20 Nm.
• The instructions requires pH test equipment (paper indicator or pH meter). This is not a part of
Alfa Laval’s scope of supply.
• The pH value should be between 2.0 and 3.0. From the beginning, the pH value is approximately
2.0. When the pH value rises to 3.0 the cleaning liquid must be changed.
• Mixing ratio for Alpacon descalant offshore is 1 part concentrated Alpacon descalant offshore to
20 parts technical water / potable water. Follow this mixing ratio, regardless of recommendation
on label.
• The CIP tank shall be filled with maximum 250 liters. Min and max filling of CIP liquid can
be read on the CIP tank.
• Alpacon descalant offshore storage temperature: 0 °C to +55 °C.
• Used CIP liquid may contain residues from the cleaning process that can potentially have an
impact on the environment, although this impact is regarded as very small. There are no
transport restrictions.
• Used CIP liquid is drained to one of the following: drain, waste or sludge tank. Do not drain to
bilge. Handle according to local regulations.
• When performing these routines, consider the need for service kits. See Spare parts catalogue.
Book No.9028195 02 41
6.1 Change and refill CIP liquid 6 CIP module
7 CIP
CIP module
42 Book No.9028195 02
6 CIP module 6.1 Change and refill CIP liquid
1. If the drain valve (3) is connected to tank, follow the sub steps below. Otherwise, go to step 2.
a. Open the manual drain valve V460-3 under the CIP tank.
b. Wait for the tank to be totally drained. Then close the drain valve.
2. If the drain valve is not connected to the tank, the steps below can be followed. This operation
requires login level Advanced operator or higher.
a. Open valve V230–11 manually. Open V320-2, V460-2 and V321–3 from the control panel.
Start pump P321-5 (3) and P320-1 (4).
b. Wait for the tank to be totally drained. Then stop the pumps and close the valves in
reversed order. Go to step 3.
3. Open the cap (1) on top of the CIP tank.
4. Fill the tank with technical water / potable water as described below:
6. Measure the pH value in the tank to secure that it is approximately 2.0. If not, adjust the
proportions: If the pH value is too high, add more CIP cleaning agent. Measure again.
7. Go to control system page 4.3 – Operation timers. Make a note of the number of UV reactors
that has been CIPed since last time the CIP liquid was changed. Press the Reset button for
“Total number CIP:ed reactors”. Requires login level Advanced operator. If this is done each
time the CIP liquid is changed, it is possible to build up experience on how many UV reactors it
is possible to CIP before it is time to change CIP liquid.
1. Measure the pH value in the tank. Based on the pH value, estimation must be done regarding
the proportions between Alpacon descalant offshore and water. Note that the mixing ratio is
stated under Preparations and conditions above.
2. Mix the cleaning agent with water separately. The result will get better than if mixed mix in
the tank.
3. Pour the mixed CIP liquid into the tank. Do not fill over Max indication on the tank.
4. Measure the pH value in the tank to secure that it is approximately 2.0. If not, adjust the
proportions: If the pH value is still too high, the CIP liquid must be changed. See the Change
CIP liquid instruction in this chapter.
Book No.9028195 02 43
6.2 Repair CIP pump 6 CIP module
ON
CAUTI
!
• Always wear protective eye glasses and gloves while working on the pump.
NG
WARNI
!
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• Before disassembling the pump, the pneumatic hoses must be disconnected, and the extension
pipe must be removed and blocked.
• Drain the pump from liquids.
• The pump should be placed horizontally on a work bench.
7 CIP pump
44 Book No.9028195 02
6 CIP module 6.2 Repair CIP pump
1. Remove the CIP pump from the CIP module and place it on a work bench.
3. Place the pump on the side that still has the nuts (the pump lays on the nuts) on a stable ground.
5. Carefully lift up the suction and discharge connections (13). You have the centre block (12)
and one of the housings with pin screws (14) left.
6. Upend the pump and carefully pull out the pin screws (14). Be careful not to damage the
diaphragms (15).
1. Put the house wall with the flat side down on a plane surface.
4. Place one of the pin screws on the inside (behind) the valve ball stopper on the lower valve
seat (21). Carefully pull out the valve seat in the housing.
5. Remove the valve ball (23) from the valve seat, buy using a pin screw: Press out the valve ball
stopper (22), which will release the valve ball.
Book No.9028195 02 45
6.2 Repair CIP pump 6 CIP module
• Have backup spares of the sealing (36) and backup O-ring (47). There is a risk that these parts
get damaged during this operation.
Follow the steps below
1. Press the diaphragms (15) to their neutral position (both have the same distance to the
centre block).
2. Hold one of the diaphragms (15) and unscrew the other. Then pull out the remaining diaphragm
with the diaphragm shaft (16).
3. Disassemble the circlips (27) which keep the air valve (61) on its place.
4. Press out the air valve. A wood shaft of a hammer can be used. Be careful not to damage the
sealing edges towards the diaphragm or the air valve.
5. If the shaft sealings (36) seem to be worn out, carefully remove them with a pointed tool.
2. Apply some soft soap solution on the air valve O-rings (30).
3. Push the air valve (61) into the housing. Make sure that the O-rings (30) remain in the right
position. Put the circlip (27) on the other side.
4. Put the diaphragm (15) with shaft (16) into the centre block. Screw the next diaphragm (15)
onto the shaft (16) and fix the holes.
1. Make sure that the O-rings (18) are placed on the in/outlet (13) before assembling of pump.
3. Make sure all pin screws (14) have one nut (37) and one washer (38) each. Nut should only be
put on one or two threads.
4. Put all the pin screws through the housing and then turn the housing so it rests on the nuts.
46 Book No.9028195 02
6 CIP module 6.5 Repair valve block
5. Put the centre block (12) to the housing with screws through the centre block. Be careful not to
damage the diaphragms.
6. Place suction and discharge connections (13) in their positions in the housing. Be careful not
to damage the O-rings (18).
7. Put the second housing (11) onto the pin screws (14). Make sure that suction/discharge
connections are in right direction. Be careful with the O-rings.
8. Fasten the nuts (37) crosswise by hand, with or without washers depending on how much of
the thread comes out. Turn the nuts gently with a tool to close the pump. If some of the nuts
were fastened without washer, unscrew those and put washers underneath. After a few weeks
operation a follow up draft of the nuts is recommended.
1. Open valves V320-2 and V460-2 from the control system, and V230–11 manually. Start
pump P321-5 (4) and P320-1 (4).
2. Observe if the motors sound and functions OK. If not, check installation and connections and
attend to and test again.
• The valve bodies does not have individual placing, they can be placed in any order.
DANGER
!
• Always disconnect the PureBallast system from the power and air supply before disassembling,
and secure it from being switched on.
Book No.9028195 02 47
6.5 Repair valve block 6 CIP module
7 Valve block
Valve block
1. Remove the scresw holding the valve bodies (2) and the signal plate (4).
4. Attach a new sealing on the new valve body and fasten the valve body to the valve block.
48 Book No.9028195 02
6 CIP module 6.5 Repair valve block
2. Attach the cables according to electrical drawing Control cabinet / interconnection diagram in
chapter 6. Installation description and drawings.
2. Operate the service air according to instruction Open and close valves manually (CIP valves)
on page 19 to blow out the dust.
1. Connect the hoses according to the signal plate (4) on the valve block.
Book No.9028195 02 49
6.5 Repair valve block 6 CIP module
7 Flow meter
• Flow sensor: A pipe with four electrodes detecting the flow. On top of the pipe, there is a
terminal box, where the flow transmitter is mounted.
• Flow transmitter: Monitors and transmits information to the PureBallast control system.
• The flow sensor and flow transmitter are pre-assembled from factory, and the parameters
are pre-set.
NG
WARNI
!
• Risk of electric shock! Exposed components carry dangerous voltages.
Make sure that the power supply is switched off before you remove the cover of the electronics
compartment.
Follow the steps below
Book No.9028195 02 51
7.1 Replace display and fuse 7 Flow meter
4. Remove the screws and remove the cover from the electronics compartment.
5. Remove the power supply board. Insert a suitable tool into the hole, provided for the purpose
and pull the board clear of its holder.
Replacing the device fuse on the power supply board (step 5–6)
1. Protective cap
2. Device fuse
7 Re-assembly
Re-assembly
52 Book No.9028195 02
8 Valve actuator
Valve actuator with switch box for position feedback to control system
1. Switch box
2. Bracket
3. Actuator
4. Pilote valve
5. Bracket - Used for valves with dimension 400
6. Coupling with position indicator - Used for valves
with dimension 400
7. DIN connector
8. Position indicator
Book No.9028195 02 53
8.1 Preparations and conditions 8 Valve actuator
7 Actuator
1. Safety cover
2. Pad lock
3. Lower position for indicator screw
4. Upper position for indicator screw — with screw
5. Position indicator
6. Center screw
7. Bracket
8. Puck
9. Locking bolt
10. End stop bolt.
54 Book No.9028195 02
8 Valve actuator 8.3 Mount actuator on valve
M5 05–06
M6 10–11
M8 23–25
M10 48–52
M12 82–86
M14 132–138
M16 200–210
M20 390–410
1. Remove the DIN connector to disconnect the power. Let the air connection remain.
Result: Valve goes to closed position (due to the air connection). The yellow indicators on the
puck shows position of valve: closed. The yellow position indicators are in line with the valve
throttle (indicating closed when the position indicators are in opposite line with the pipe).
2. Disconnect the air hose to the pilot valve. Verify that the actuator is not pressurized. Always
use caution and double-check that ports 2 and 4 are vented and are free from any accessory
and/or device.
3. If the actuator have a switch box at the top: Loosen the four screws holding the switch box to
the actuator. Remove the switch box together with its bracket.
4. Loosen the four hexagonal screws holding the actuator to the valve.
5. If the actuator is mounted on the valve with a bracket and coupling (dimension 400): Loosen
the screws holding the bracket to the valve. Make sure not to loose the coupling between the
valve and actuator when lifting the actuator.
Book No.9028195 02 55
8.3 Mount actuator on valve 8 Valve actuator
ON
CAUTI
!
• The actuator must not be pressurized at any time during installation as it may result in injury.
• The valve must be in closed position.
• The valve position must not be adjusted during the routine.
• The utmost cleanliness is required during air supply connection to the actuator, that is, the
connecting pipe thread, fittings and seals must be clean and dirt-free.
• Before fitting onto the valve, make sure the actuator/valve is correctly orientated, depending on
which direction of rotation is required.
Follow the steps below
1. Note the position of the groove (2) of the valve stem (3). It indicates the position of the valve
throttle. The illustration shows a square variant, but octagonal versions exist.
7 ValveStem
2. Make sure that the lock pin (inside the valve stem) only travels in the allowed sector (1) and
that it does not pass the opening (5).
3. If the actuator is mounted on the valve with a bracket and coupling (dimension 400): First fit
the coupling on the valve stem. Make sure that the red position indicator on the coupling is in
line with the pipe when the valve is open.
4. Fit the actuator onto the valve stem (or the coupling). The actuator may only be positioned in
even 90° intervals in relation to the valve. It is not allowed to adjust the position by turning the
actuator by hand after it is fitted on the valve stem.
5. Mount the actuator on the valve with the four hexagonal screws. For each screw, one washer
and one spring washer shall be used. Tighten with torque according to the table Tightening
torques for actuators on page 54.
56 Book No.9028195 02
8 Valve actuator 8.4 Change direction of actuator – without
position sensor (V404–36, V320–4 and V321–2)
6. If the actuator have a switch box at the top: Make sure that the yellow position indicator under
the switch box is in line with the throttle (according to the groove in the valve stem). The yellow
position indicator shall be in line with the valve throttle (indicating open when the position
indicator is in line with the pipe). If not, remove the position indicator, turn it 90° and refit it.
Mount the switch box with the bracket on the actuator, using the four bolts.
8. Operate the valve to make sure it operates in the desired direction of rotation.
3. Note the position of the groove of the valve stem. It indicates the position of the valve throttle.
5. Unscrew the center screw (4) holding the puck (6) and a bracket (5).
7 ActDirectWithout
6. Lift the puck (6), rotate it 90° and fasten it with the center screw (4) and bracket (5).
Book No.9028195 02 57
8.6 Change direction of actuator – with 8 Valve actuator
position sensor (201-19 and 201–20)
7. Make sure that the yellow position indicators (3) is in line with the throttle (according to the
groove in the valve stem). The yellow position indicators shall be in line with the valve throttle
(indicating open when the position indicator is in line with the pipe). If not, remove the position
indicators, turn them 90° and refit.
3. Before mounting the switch box, change the position of the yellow position indicator, so it
is in line with the throttle.
This instruction is valid for the following valves: V201-19 and V201-20 on the UV reactor.
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 55.
Put the actuator on a work bench.
58 Book No.9028195 02
8 Valve actuator 8.6 Change direction of actuator – with position
sensor (201-19 and 201–20)
2. Disconnect the DIN connector (2) from the coil: First loosen the screw (1), and then pull up
the connector.
7 DisconDINcon
3. Unscrew the center screw (6) holding the puck (8) and a bracket (7).
7 DirActPosSnsr
4. Lift the puck (8), rotate it 90° so that one position indicator (5) with a screw is in contact with the
position sensor. Fasten the puck with the center screw (6) and bracket (7).
5. Move the screw on yellow position indicator to the top position and move the screw on black
position indicator to the bottom position.
6. Make sure that the position sensor have a maximum distance of 1 mm from the puck (7). The
position sensor and the position indicator screws must be close to give a signal. If not, loosen
the screws and adjust the position. Tighten the screws to fixate the position.
7. Fit the actuator onto the valve stem in its new position according to instruction Mount actuator
on valve on page 55.
Book No.9028195 02 59
8.8 Mount pilot valve on actuator 8 Valve actuator
8. Make sure that the yellow indicator (5) in line with the valve throttle according to the groove in
the valve stem.
11. Check that the installation is OK, by making sure that the A1 LED is lit on the position sensor
(visible from the side).
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 55.
2. Fit the actuator onto the valve stem in its new position and mount it on the valve with the four
hexagonal screws. For each screw, one washer and one spring washer shall be used. Tighten
with torque according to the table Tightening torques for actuators on page 54.
3. The position indicator scale shall be correct, but make sure that the scale still indicates correct
opening percent according to the valve throttle position. If not, loosen the four bolts to the
bracket holding the switch box. Lift it and turn the scale so it is correct.
4. Refit the switch box. Make sure that the peg on the scale fits to the carrier on the puck
mounted on the actuator.
60 Book No.9028195 02
8 Valve actuator 8.9 Adjust valve end position
7 MountPilote
1. Check that the O-rings are fitted on the pilot valve, on the side facing the actuator.
2. Fit the pilot valve on in the actuator, so that the pin on the actuator fits the hole on the pilot
valve. The throttle valves (2 and 4) shall be directed downwards.
3. Mount the pilot valve with two Allen screws in the holes (1).
5. Fit the DIN connector (5) on the coil, including gasket. Then fasten the connector with the
screw (6).
Book No.9028195 02 61
8.10 Adjust valve traveling speed 8 Valve actuator
7 576075_lock_manual
1. Note the exact position of the position indicator for reference after adjustment.
2. Open the padlock (2) on the actuator and remove the safety cover (1).
Result: Two sets of bolts are displayed. The right set adjusts closing position and the left
set adjusts open position.
4. Adjust end position by turning the end stop blot (4) with small turns.
– Clockwise decrease the end position.
– Counterclockwise increase the end position.
NOTE
6. Tighten the locking bolt (3) to fixate the position of the end stop bolt (4).
62 Book No.9028195 02
8 Valve actuator 8.10 Adjust valve traveling speed
7 AdjustTravel
1. Operate the valve manually to check traveling speed according to the instruction in the Operate
valves manually on page 19.
Book No.9028195 02 63
8.11 Calibrate positioner on V201-8 8 Valve actuator
7 201-8Positioner4
7 201-8Positioner
64 Book No.9028195 02
8 Valve actuator 8.11 Calibrate positioner on V201-8
1. Make sure that the transmission ratio selector (6) is set to 90° according to sticker on the
component. If not: Adjust by pressing the bar with a screw driver.
2. Make sure that the Arrestor device wheel (1) is set to 90°. If not: Adjust by turning.
4. Make sure that Menu 1 is displyaed. If not: Press HAND button repeatedly until it is.
Make sure that “turn” is displayed in the menu. If not: press + or – repeatedly until it is.
Note: Do not choose “– turn”.
7 201-8Positioner2
- Use a screw driver to loosen the yellow locking wheel (counter clockwise).
- Turn the adjustment wheel (5) by hand until a 0 is displayed between the “d” and the “U” as
shown in the illustration. Normally this is when the value in the screen is close to 0.
7 201-8Positioner3
Book No.9028195 02 65
8.11 Calibrate positioner on V201-8 8 Valve actuator
10. Press the hand button for 5 seconds until a number or “VER” is displayed, then let go of the
button.
Result: “MAN” is displayed”.
66 Book No.9028195 02
8 Valve actuator 8.11 Calibrate positioner on V201-8
Trouble shooting
- Reset to factory settings: Press HAND button repeatedly until menu 50 is displayed.
- Press + button until “oCAY” is displayed.
- Restart instruction Calibrate positioner on V201-8 from step 4.
- Set the parameters according to Alfa Laval software settings. See table above.
Book No.9028195 02 67
8.12 Adjust cam position on V201-8 8 Valve actuator
Hint: A multimeter can be used to indicate position of the cam wheels, if it is hard to hear the click
from the micro switch, or if it is inconvenient to see valve position in control panel. Connect a
multimeter to connection point 41 and 42 in the positioner.
3. Close it to approximately 10 %.
4. On the positioner: Adjust both cam wheels to same position. Cam wheels are above the
adjustment wheel (5) on page 64.
5. Turn the cam wheels in any direction until it valve indicates steady green in the control panel.
Miltimeter indicate circuit closed.
6. Turn the cam wheel slowly counter clock wise until you hear a click from the micro switch in
the positioner. Stop directly after the click. Stop directly after the multimeter changes to
indicate circuit open.
7. Check that the valve is indicated as open (steady green) in the control panel.
Result 2: Valve indicated as red. Cam wheels are in wrong position, for example due to the
wheels been turned too much after the click). Miltimeter indicate circuit open. Repeat from
step 2 until setting is OK.
68 Book No.9028195 02
9 Ball valve
7 BallV
32 = 1¼ 20–25 Nm 14.3 Nm
inches
Book No.9028195 02 69
9.1 Replace seals in ball valve 9 Ball valve
2. With the valve in the open position (lever to be parallel to the axis of the pipe), remove all the
body bolts (19) except one.
3. Loosen the nut (20) on the remaining bolt. Swing the body outside the pipe.
5. Replace seals (5, 6, 7, 9, 10, and 24). They are available in a spare parts kit for the ball valve.
6. Mount in reverse order. The body bolts of the valve should be tightened evenly. Tighten
one-side snugly, then the one diagonally across. Repeat for the other bolts, bringing them all
down tightly in sequence. Make sure the maximum tightening torque is observed according
to the table above:
70 Book No.9028195 02
10 Level switch
This section contains information about the level switch LS201-29 installed in the UV reactor. For
information about status indications, see chapter 5. Alarms and faultfinding, section Level switch.
7LS Component
Level switch
NOTE
2. Seal the level switch with lock tight or equivalent pipe seal.
4. Identify the sensor align mark (▼) on the component. Make sure that it is positioned on the
upper side of the level switch.
Book No.9028195 02 71
10.3 Test level switch 10 Level switch
5. Complete the seal carefully by tightening the component with a spanner. Use the spanner on
the hexagon flats, but not on the level switch body.
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the level switch body.
3. Remove the level switch and remove the old seal from the threads.
1. Make sure that the component i powered (the green LED shall be lit).
2. Hold a magnet to the test point indicated on the on the level switch, indicated below.
7LS Test
3. Make sure the level switch reacts to the magnet. The component is OK if the green and
yellow LED is lit.
72 Book No.9028195 02
11 Temperature switch and
temperature transmitter
This section contains information about the temperature switch TS201-60 and the temperature
transmitter TT201–33 installed in the UV reactor. The two components are similar in design, so
the same instructions can be used.
7 TS and TT
NOTE
1. Seal the component’s threads using lock tight or equivalent pipe seal.
3. Tighten the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
Book No.9028195 02 73
11.2 Dismount temperature switch / 11 Temperature switch and temper-
temperature transmitter ature transmitter
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
3. Remove the level switch and remove the old seal from the threads.
74 Book No.9028195 02
12 Control panel
NOTE
• Control panels may only be cleaned when set in wipe mode. This is to prevent unintended
functions from being triggered by buttons pressed during cleaning.
Preparations and conditions
• Never use aggressive solvents, chemicals, scouring agents, pressurized air or steam jet.
Follow the steps below
2. Clean the display and surrounding front cover with a soft cloth and mild detergent. Do not
spray detergent directly on the control panel.
Book No.9028195 02 75
12.2 Replace control panel 12 Control panel
13 Remote control panel
(optional)
This section covers information on how to mount and connect the remote control panel. The remote
control panel is either ordered with a mounting plate (for installations in wall, worktop etc) or an IP
protective back cover (for installation on stand etc).
• Remote control panel is mounted according to according to drawing Remote control panel /
Dimension drawing. Note the clearance area.
• Use a 24 VDC power cable with minimum cross section of 0.75 mm2, preferably halogen free
and flexible.
• Connect power cable to terminal X1 in remote control panel.
• Communication cable (W501) between the remote control panel and control cabinet can be
either Ethernet or fiber. Cable requirements and connection points below:
- Ethernet cable – Type: Cat 5e (or better), shielded. Max length: 100 meters. One remote
control panel: From terminal X2 in remote control panel s to terminal X13 in the control
cabinet. Two From terminal X2 in second remote control panel to either switch SW1 in
control cabinet or to switch SW1 in the first remote control panel.
- Fiber cable – Type: Multi-mode fiber cable with LC connector. Max length: 500 meters.
From remote control panel’s switch SW1 to switch SW1 in control cabinet.
See Remote control panel / Circuit diagram on page .
Book No.9028195 02 77
13.1 Mount and connect remote control panel 13 Remote control panel (optional)
14 Control cabinet and lamp
drive cabinet (LDC)
1. Hold down the plastic clip on the top of the terminal block and pivot the block towards you.
7IO1_X025002A
3. Hold down the triangle on the top of the I/O board and loosen the board.
7IO2_X025003A
Book No.9028195 02 79
14.1 Disassemble and assemble I/O system 14 Control cabinet and lamp drive cabinet (LDC)
4. Pull the board straight out (otherwise it can fasten in one of its guides).
7IO3_X025004A
5. Compare the part number of the new I/O board to the old board, to make sure it is correct.
6. If changing more than one board at a time, check with the electrical diagram to ensure that
the boards are mounted in the right places.
7. Mount the new I/O board by pressing it straight into place. Make sure the board is firmly in
place, otherwise it will be impossible to mount the cable terminal.
7IO4_X025005A
8. Remount the terminal block. Make sure the clip on the bottom of the block fastens properly in
place on the axel on the bus holder.
7IO5_X025007A
80 Book No.9028195 02
14 Control cabinet and lamp drive cabinet 14.2 Cable gland installation – General cables
(LDC)
9. Pivot the terminal block on the axel until the clip on the terminal block top fastens into place in
the I/O board.
7IO6_X025006A
1. Lubricate the inside surfaces of the frame with Roxtec Assembly Gel or equivalent, specially
in the corners.
7 Cable1
4. Peel off layers until you achieve a 0.1-1.0 mm gap between the two module halves when
held against the cable.
Book No.9028195 02 81
14.2 Cable gland installation – General cables 14 Control cabinet and lamp drive cabinet (LDC)
7 Cable2
7 Cable3
5. Lubricate all modules thoroughly, both on the inside and the outside surfaces.
7 Cable4
6. Insert the modules from the back of the frame opening. If possible, start with the largest
modules.
7 Cable5
82 Book No.9028195 02
14 Control cabinet and lamp drive cabinet 14.3 Cable gland installation – Power
(LDC) cable to LDC
7. Tighten the compression unit firmly to seal the frame. Maximum 10 Nm. A good indication is
when the lubrication is squeezed out between the modules.
7 Cable6
1. Adapt the seal to the cable by removing layers from the halves. The halves may not differ by
more than one layer.
7 LDC gland1
2. Achieve an approximate 0.1–1 mm gap between the halves when testing against the cable.
There shall be a visual gap.
7 LDC gland2
3. Lubricate thoroughly on the inside surfaces and sparsely on the outside of the seal.
Book No.9028195 02 83
14.5 Install IFS-confstick in safety relay KS1 14 Control cabinet and lamp drive cabinet (LDC)
in LDC
7 LDC gland8
5. Tighten the Allen screws crosswise. The seal will compress and seal the transit.
This check should be performed in LDC, control cabinet, UVR junction box.
1. Turn off power to PureBallast from the vessel’s switch board, to make it currentless. Where
applicable, turn off power to the individual cabinet.
2. Make a random check of approximately 10 % the cables in different areas of the cabinet.
- Make sure that the cables are fastened with sufficiently tightened screws.
- If one cable is loose, check all cables connected to this component / component of the
same type.
- Note: Be careful not to tighten the screws so that the cables are damaged.
14.5 Install IFS-confstick in safety relay KS1 in LDC
Follow this instruction to install a new IFS confstick in the safety relay. This is done when the IFS
confstick is broke or when a new safety relay is installed.
84 Book No.9028195 02
14 Control cabinet and lamp drive cabinet 14.5 Install IFS-confstick in safety relay
(LDC) KS1 in LDC
7 KS1
2. Insert the new IFS confstick in the safety module. The IFS confstick can only be inserted in
one way.
3. Switch on the power to the LDC. Wait until the safety relay has initialized (all four status LEDs
light up once during initialization).
4. The safety relay now detects that a new IFS confstick has been inserted. The LED "CONF"
is flashing.
7. Reinsert the IFS confstick while holding down the Conf rm button.
8. Release the Conf rm button when IFS confstick has been inserted. The safety relay will start
an initialization with the new configuration.
Book No.9028195 02 85
.
2 Control cabinet 6
2.1 Cabinet 10
2.2 I/O module 12
2.3 Relay module 14
2.4 Wire set 16
6 UV Reactor EN 46
6.1 UV reactor EN 48
6.2 Junction box, A side 50
6.3 Junction box 52
6.4 Valve, EN DN350 54
6.5 Valve 56
7 Filter, ACB-999-350 58
7.1 Filter, ACB-999-350 60
7.2 Junction box 62
8 Valve V309-1 64
3
11 Valve V201-32 and 403-35 70
15 CIP module 78
15.1Pump P320-1 and P321-5 82
15.2Valve 84
15.3Valve block 86
4
1 Important information
1 Important information
• State number of ordered parts. Note that the quantity in the tables do not states number of parts
delivered (only the how many of that parts that are included in the mother component).
• Safeguard your commitment to quality by always using genuine Alfa Laval spare parts.
Remember, Alfa Laval cannot accept responsibility for the failure of separator equipped with
non-original spare parts. We guarantee the quality and reliability of our products.
• When ordering, refer to part number listed in this catalogue and serial number, described in
chapter 7. Service manual, section Serial number information.
2 Control cabinet
Machine unit number or
Subassembly description
9025738-
Ref Part No Description -80 Notes
Quantity
1 9012086 83 Cabinet 1 See page 10
2 9006851 01 Software, PLC, PB3.0 1
3 9006852 01 Software, panel 1
4 592122 03 HMI Panel wide without co 1
8 221891 04 Lock nut 12
9 223101 47 Washer 12
10 582212 148 End stop (clip fix) 14
11 582212 122 Terminal block 3
12 582212 13 End plate 3
13 9019135 03 Contactor AF09Z 1 K2
13.1 9019138 01 Over current prot. Relay Ex 1 F2
14 9019135 03 Contactor AF09Z 1 K3
14.1 9019138 01 Over current prot. Relay Ex 1 F3
15 9014707 01 Power supply unit 1
16 9004299 04 Fuse 4
17 582212 67 Terminal, PIT 2,5-3PV 7
17.1 582212 71 Plug In Bridge, FBS 3-5BU 1
18 582212 63 Terminal D-PIT 2,5-3L 1
19 9019135 04 Contactor AF16Z 1 K4
19.1 9019138 03 Over current prot. Relay Ex 1 F4
20 9019135 04 Contactor AF16Z 1 K5
20.1 9019138 02 Over current prot. Relay Ex 1 F5
21 9025840 80 I/O module 1 See page 12
22 582212 147 Patch panel 2
23 582212 91 VIP-2, D 9SUB 1
24 9019186 05 Terminal, PT 4-PE/3L 4
25 582212 102 Terminal PITTB 2,5 PE 1
26 9019186 06 End cover, D-PT 4-PE/3L 1
27 582212 104 Terminal PITTB 2,5 42
29 582212 67 Terminal, PIT 2,5-3PV 4
30 582212 63 Terminal D-PIT 2,5-3L 1
31 582212 168 Separating plate 2
32 582212 123 Power terminal block, 1
33 9002362 80 Relay module 3 See page 14
34 593724 03 Distance screw 4
35 582221 90 PE Connection bar 1 245mm
36 594009 03 Screw 2
37 582212 206 Bar holder 3
38 582212 15 PE/SC Bar 1 500mm
39 594009 02 Screw 3
40 582212 207 Cable clamp 10
41 9006814 01 Cable channel 100x80 1
42 583556 17 Cable channel 40x80 1
43 583556 16 Cable channel 40x80 2
44 9003522 06 Cable channel, 25x80 1
45 9003522 07 Cable channel, 25x80 2
48 223101 47 Washer 2
49 221851 05 Cap nut 2
50 9019186 07 Safety relays, PSR-MC30 1
51 221701 03 Screw 16
52 591103 67 Emergency stop 1
54 9011552 01 Buzzer 1
56 582212 155 Socket with USB 2
59 9025837 01 Switch OT63FT3 1
59.1 591103 37 Breaker handles 1
59.2 9025837 02 Shroud OTS63T3 2
61 9006853 01 Fan 1
62 9006854 01 Air outlet 1
63 595361 02 Cable seal 2
3029A
3029A
2.1 Cabinet
Machine unit number or
Subassembly description
9012086-
Ref Part No Description -83 Notes
Quantity
2 9012091 81 Door 1
4 26556 Spring washer 6
5 9025887 01 Mounting plate 1
6 587276 02 Washer 16
7 221891 05 Hexagon lock nut 12
8 221716 01 Screw 4
10 593778 01 Latch, housing 1
11 593779 01 Latch, insert 1
12 593991 01 Latch 1
13 9003013 01 Rod Guide 2
14 9003024 02 Rod for latching 2
15 593780 01 Key 1
17 223107 34 Spring washer 4
18 221891 04 Lock nut 4
20 593254 01 Retaining ring 1
21 221711 19 Screw 1
22 593282 01 Washer 1
23 221803 02 Nut 2
24 223101 73 Washer 1
25 593239 01 Nut 1
26 581688 01 Bracket 4
27 594488 01 Washer 4
28 221711 16 Screw 8
29 223101 47 Washer 8
30 221891 04 Lock nut 8
31 587276 02 Washer 6
32 70560 Washer 6
33 221891 05 Hexagon lock nut 6
34 9014753 01 Piano hinge 1
35 9014815 01 Cover panel 1
36 598571 01 Torx head pan screw M4 8
37 221851 18 Cap nut 8
38 223101 31 Washer 4
39 9015118 01 Mounting spacer hole thro 2
40 9015117 01 Mounting spacer single ta 2
41 9012093 01 Magnet 4
42 9015123 01 Torx head pan screw M5 4
44 587276 01 Washer 2
45 223101 47 Washer 2
46 221891 04 Lock nut 2
2878A
3030A
2724A
2377A
2874A
3009A
3009A
3.1.1 Cabinet
Machine unit number or
Subassembly description
9011952-
Ref Part No Description -80 Notes
Quantity
1 9011951 80 Cabinet 1 See page 26
2 9012193 01 Mounting plate 1
3 587276 02 Washer 18
4 221891 05 Hexagon lock nut 10
5 221716 01 Screw 8
6 9015611 01 Sheet 1
7 223101 47 Washer 4
8 221891 04 Lock nut 4
10 223101 47 Washer 6
11 221891 04 Lock nut 6
13 592005 15 DIN-rail, 35x15 1
14 9003565 03 DIN-rail, 35x15 1
15 9003565 02 DIN-rail, 35x15 1
16 223101 47 Washer 17
17 221891 04 Lock nut 14
18 583556 20 Cable channel 40x80 1
19 583556 19 Cable channel 40x80 1
20 583556 21 Cable channel 40x80 1
21 583556 04 Cable channel 1
22 586056 07 Cable channel 60x80 1
34 223101 47 Washer 13
35 221851 05 Cap nut 13
37 9004212 01 Inlet duct 1
38 9004213 01 Protection 1
39 221891 02 Nut 4
40 223101 16 Washer 4
41 594009 02 Screw 4
42 9003390 01 Bracket, fan 1
43 9006316 01 Cover, fan 1
44 223101 47 Washer 9
45 221030 10 Screw 9
46 591889 01 Cable tie mount 3
50 9003030 01 Drawing Pocket 1
51 223101 47 Washer 2
52 221803 02 Nut 2
53 9014585 01 Sheet, LPS 1
54 9014554 01 Sheet, LPS 1
55 594009 05 Screw 8
56 9002947 01 Yoke 18
57 9002942 01 Stud bolt 36
61 9006322 01 Sheet 1
62 221030 02 Screw 36
63 223101 47 Washer 72
64 221891 04 Lock nut 36
65 9015616 01 Sheet 1
66 70560 Washer 2
67 221891 05 Hexagon lock nut 1
68 221716 01 Screw 1
2881A
3.1.2 Cabinet
Machine unit number or
Subassembly description
9011951-
Ref Part No Description -80 Notes
Quantity
3 9008903 05 Washer 12
4 221035 51 Screw 12
5 9014640 01 Door, RH 1
6 9014642 01 Door, LH 1
9 223101 47 Washer 12
10 221803 02 Nut 12
15 9003075 01 Sheet 2
16 593254 01 Retaining ring 2
17 9003410 01 Sheet, heat exchanger 1
18 221030 10 Screw 9
19 223101 47 Washer 2
20 9003401 01 Sheet, heat exchanger 1
21 221030 10 Screw 3
22 223101 47 Washer 3
23 9003186 01 Plug 1
29 591874 04 Seal 1 Upper LPS rack, left
30 591874 06 Seal 1 Upper LPS rack, right
34 9014759 01 Sheet, EMC 1
49 9014762 01 Handle 1
50 9016266 01 Rod for latching 2
50.1 9016270 01 Rod adapter 4
51 9016268 01 Rod guide 8
52 9014732 01 Three point lock 1
53 9014735 01 Handle 1
54 9016266 02 Rod for latching 2
54A 9003024 01 Rod for latching 1
55 593780 01 Key 1
56 9003114 02 Cable gland 1
57 9003113 01 Cable seal 1
58 223101 41 Washer, 4,3x9x0,8 10
59 221891 02 Nut 10
64 9003031 01 Condensation outlet 2 Cabinet floor and heat exchanger floor
65 9003186 02 Plug 3
66 9008424 01 Protection 9
67 9003089 02 Vibration damper 2
68 223101 49 Washer 13x24x2,5 2
69 221726 10 Screw 2
2882A
2880A
2870A
2871A
2872A
2873A
2377A
2875A
4.1 Cover
Machine unit number or
Subassembly description
9011943-
Ref Part No Description -80 Notes
Quantity
1 9011944 01 Cover 1
2 594488 01 Washer 4
3 581688 01 Bracket 4
4 221711 16 Screw 8
5 223101 47 Washer 8
6 221891 04 Lock nut 8
7 589569 79 Cable Gland - M25 2
8 589569 35 Counter nut M25 2
9 589569 48 Cable Gland - M16 2
10 589569 33 Counter nut M16 2
11 587276 02 Washer 2
12 70560 Washer 2
13 221891 05 Hexagon lock nut 2
2883A
3021A
6 UV Reactor EN
Machine unit number or
Subassembly description
9002700-
Ref Part No Description -83 Notes
Quantity
1 9002699 81 UV reactor EN 1 See page 48
2 9010984 81 Junction box, A side 1 Valves, sensors & feed back
See page 50
3 9010987 80 Junction box 1 Lamp cables
See page 52
4 221803 02 Nut 8
5 223101 32 Washer 8
7 9001357 03 Sensor AT201-50 1
8 9014966 69 Valve, EN DN350 1 V201-19
See page 54
8.1 9014966 69 Valve, EN DN350 1 V201-20
See page 54
9 260192 01 Screw 32
10 223101 39 Washer 32
12 9006325 02 Thermometer, resistance 1 TT201-33
13 9006324 02 Temperature, switch 1 TS201-60
14 558663 04 Gasket washer 2
15 594171 01 Limit switch (vibration) 1 LS201-29
16A 9010631 99 Cable (valves and signals)
18 526350 05 Plug 1
19 558663 03 Gasket washer 2
20 594413 80 Valve 1 V320-4
See page 56
20.1 594413 80 Valve 1 V321-2
See page 56
20.2 594413 80 Valve 1 V404-36
See page 56
21 2210463 23 Screw 12
22 223101 37 Washer 12
23 9006822 01 Relief valve, 6 bar 1 RV201-23
24 597049 01 Coupling, elbow 90 1
25 594707 02 Pipe 1
26 581534 01 Distributor 1
27 260321 25 Hexagon screw 2
28 592304 01 Plug 1
29 592304 02 Plug, 1/4 1
30 552801 50 Push-on connector 5
31 9004638 01 Clamp 1
32 2210296 02 Screw 1
33 223101 33 Washer 2
34 221803 03 Nut 1
35A 9011226 99 Cable (UV lamp to junction box)
37 595272 01 Tube, 6x1 mm 4
38 558710 02 Air Hose Nipple 5
63 598571 02 Torx head pan screw M4 4
64 526336 04 Nipple 1
70 597044 03 Cable 2 PE, junction box - reactor
71 597044 04 Cable 1 PE, AOT reactor - hull.
74 223101 32 Washer 3
81 221803 26 Nut 4
82 223101 41 Washer, 4,3x9x0,8 4
83 221031 22 Screw 3
93 593301 02 Insulating washer 32
94 593300 04 Insulating sleeve 32
Z 9009521 80 Lamp, spare set Includes UV lamps and 2 O-rings.
Z0.1 594645 82 Quartz sleeve set Includes Quartz sleeve and 2 O-rings.
2688A
6.1 UV reactor EN
Machine unit number or
Subassembly description
9002699-
Ref Part No Description -81 Notes
Quantity
3 66169 Drive screw 8
6 9003326 01 Glass socket 32
7 221711 13 Screw 96
8 9002009 81 Lamp bush 32
9 9004878 80 Cap 32
10 9002860 01 Nut 32
20 221711 23 Screw 16
22 221041 02 Screw 16
23 223101 61 Washer 24
24 221036 01 Screw 4
25 223101 33 Washer 20
27 67141 Screw 8
28 9003662 01 Plate 1
29 2210296 02 Screw 1
30 223101 31 Washer 2
31 9003672 01 Upper bracket 2
32 221036 19 Screw 8
33A 9004889 01 Lifting bracket 1
33B 556465 01 Label 1
34 221041 03 Screw 4
35 221803 29 Nut 4
38 9009416 01 Cable rail 2
39 221031 21 Screw 8
40 223101 32 Washer 12
41 221803 28 Nut 6
43 9010633 01 Screw, hexagon socket 2
Z 9009521 80 Lamp, spare set
Z0.1 594645 82 Quartz sleeve set
2685A
2800A
2888A
2867A
6.5 Valve
Machine unit number or
Subassembly description
594413-
Ref Part No Description -80 Notes
Quantity
1 590037 01 Valve, DN32 1
2 576075 21 Air actuator, SR101 1
3 576071 01 Pilot valve 1
4 585976 01 Coil, 24 V DC 1
5 594410 01 Valve connector 1
6 583012 01 Throttle valve, 1/4 2
Z 576075 71 Actuator spare part kit, DA/SR 101 1
2330A
7 Filter, ACB-999-350
Machine unit number or
Subassembly description
9023678-
Ref Part No Description -60 Notes
Quantity
1 9023658 60 Filter, ACB-999-350 1 See page 60
2 591090 04 Flange 1 1/4" 1
3 526337 08 Reducing hexagon nipple 1
5 221711 07 Screw 2
6 9024168 01 Elbow union 2
7 526337 02 Reducing hexagon nipple 2
8 1767267 01 Needle valve 2
9 9017973 01 Pressure transmitter 2
13 526336 04 Nipple 1
14 9006822 03 Relief valve, 10 bar 1
15 561094 06 Straight coupling 1
16 9019487 02 Tube 1
19 9023647 83 Gear motor 1
20 221046 01 Screw 4
22 9024155 01 Bracket 1
23 7007238 01 Screw 4
24 9012246 80 Junction box 1 See page 62
25 221711 25 Screw 4
25.1 223101 32 Washer 4
25.2 221803 28 Nut 4
26 9026074 01 Cable bracket 1
27 221711 07 Screw 2
28 223101 32 Washer 2
29 9026072 01 Bracket 1
30 221711 07 Screw 2
31 221711 13 Screw 1
32 223101 32 Washer 3
33 587276 01 Washer 1
34 9025165 02 Cable 1
40 1270001 Lifting instruction 1
3040A
3044A
2866A
8 Valve V309-1
3023A
3034A
2710A
2714A
2716A
2712A
3035A
15 CIP module
2558A
2558A
2606A
15.2 Valve
Machine unit number or
Subassembly description
9002825-
Ref Part No Description -80 Notes
Quantity
1 9002825 01 Valve 1
Z 9003574 01 O-ring
2609A
2607A
2780A
2709A
3036A
2981A
3039A
+ Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
9014704 80 20 48 9019186 05 6 24
9014707 01 6 15 9019186 06 6 26
9014707 01 20 38 9019186 07 6 50
9014732 01 26 52 9019487 02 58 16
9014735 01 26 53 9019604 01 92 1
9014736 01 80 67 9019609 02 94 1
9014747 01 78 24 9019944 01 94 Z
9014748 01 78 25 9019944 02 92 Z
9014753 01 10 34 9023647 83 58 19
9014759 01 26 34 9023658 60 58 1
9014762 01 26 49 9024155 01 58 22
9014815 01 10 35 9024168 01 58 6
9014833 01 21 60 9024205 08 60 4
9014966 69 46 8 9024205 16 60 10
9014966 69 46 8.1 9024205 24 60 12
9014979 01 40 1 9024205 32 60 31
9015117 01 10 40 9024205 40 60 34
9015118 01 10 39 9024206 08 60 8
9015123 01 10 42 9024206 16 60 19
9015197 82 21 86 9024206 24 60 87
9015525 03 54 27 9024207 08 60 30
9015557 80 40 37 9024208 08 60 40
9015611 01 24 6 9024209 08 60 43
9015616 01 24 65 9024210 08 60 44
9015692 01 38 16 9024593 07 76 1
9015704 01 38 3 9025145 01 76 Z
9015704 02 38 4 9025145 02 76 Z0.1
9015704 03 38 5 9025165 02 58 34
9015704 04 38 17 9025753 01 66 12
9016266 01 26 50 9025837 01 6 59
9016266 02 26 54 9025837 02 6 59.2
9016268 01 26 51 9025840 80 6 21
9016270 01 26 50.1 9025887 01 10 5
9016593 01 40 3.1 9026072 01 58 29
9017973 01 58 9 9026074 01 58 26
9018092 01 96 1 9029781 01 74 10.2
9018092 02 96 2 9030002 80 76 Z0.2
9018092 03 96 3 9034058 80 74 9
9018092 99 96 Z 9037347 01 88 8B
9018543 63 66 2
9018543 64 64 1
9018653 05 66 1
9019135 03 6 13
9019135 03 6 14
9019135 04 6 19
9019135 04 6 20
9019138 01 6 13.1
9019138 01 6 14.1
9019138 02 6 20.1
9019138 03 6 19.1