New Cosmos V3 Manual EN
New Cosmos V3 Manual EN
New Cosmos V3 Manual EN
Model V3
Instruction Manual
Read this instruction manual to ensure safe and correct operation and to prevent possible accidents.
The indicator unit, Model V3, is used as a part of a gas detection/alarm system that detects various gases
including combustible gases. Usually, the system consists of one alarm unit (Model VAS or VAL, which
both have alarm functions such as a buzzer) and several indicator units. Each indicator unit is connected to
a gas detector (or gas detector head) which is installed on site. The gas detector measures a gas
concentration, converts it into electric signals and sends them to the indicator unit.
When the gas detector detects a leak of a target gas or a decrease in the oxygen concentration, the
indicator unit will display the gas concentration on bar graph meter. If the gas concentration goes beyond
the limit, the indicator unit will alarm by turning on alarm lamps, and the alarm unit will alarm by
intermittent sounds.
Periodical maintenance and inspection are crucial for maintaining the reliability of this indicator unit. Be
sure to conduct the maintenance and inspection on a regular basis as described in this manual.
The V3 indicator units are categorized into the following four groups, according to the specifications of
the gas detectors connected.
Wiring and adjustment methods partly vary depending on the group. The group is specified for its
applicable wiring and adjustment methods in this manual. Follow the wiring and adjustment methods
applicable to your indicator unit. Note that a combination of V3 indicator unit, Type M and metal housing,
Model V-SC-4A is CE-certified product.
-1-
2. Precautions
• To ensure proper use, read this manual carefully before using this indicator unit.
• Follow all applicable laws and regulations when using this indicator unit.
WARNING
To prevent electric shock, ensure that the indicator unit is correctly grounded.
If there is a gas leak alarm, take the necessary measures specified by your company.
This indicator unit is not explosion-protected equipment. Ensure that it is installed in a non-hazardous
area.
CAUTION
0 Only qualified personnel should perform necessary works including installation and wiring in
accordance with the applicable engineernig standards for electrical installation.
Do not disassemble or modify the indicator unit, or alter its structure or electric circuits as this may
compromise the performance of the indicator unit.
This indicator unit is not a drip-proof device. Ensure that the indicator unit is kept clear of water or
moisture.
Follow all applicable laws and regulations when using this indicator unit.
-2-
3. Package Contents
The standard package contains the following components. Check that all the components are contained in
the package before using this indicator unit. If any component is damaged, defective or missing, please
contact us.
Standard Package
Component Quantity
Indicator Unit 1
Fuse (1.0 A) 1
Component Quantity
Metal Housing 1
Screw 2
Component Quantity
As per system
Partition Board*2
configuration
As per system
Clamp with Two Fixing Screws
configuration
As per system
Flat Cable Assembly*3
configuration
As per system
Reset Relay Terminal*4
configuration
*2: Necessary when multiple metal housings are installed adjacent to one
another.
*3: Special cable used to connect indicator units, alarm unit and/or reset relay
terminal.
*4: Necessary for cancelling alarm without using the alarm unit.
-3-
4. System Configurations
(1) Typical System Configuration for Group 1 (Type: Hv, Cv, Tv)
Type Hv Type Hv
Type Cv Type Cv
Type Tv Type Tv
Analog Output
Recorder
Instrument Panel
Instrument Panel Terminal Block
Ground
OUT
P
E
Ground
GAS IN
Ground
* 6-core if a flow rate
signal is used
-4-
(2) Typical System Configuration for Group 2 (Type: O, D)
Analog Output
Recorder
Zener Barrier
Instrument Panel
Instrument Panel Terminal Block
Single Class-A
Ground Grounding
2-core Shield Cable *
4-core Shield Cable 2-core Shield Cable
OUT
P
E
Ground GAS IN Ground
Ground
* 5-core shield cable if a flow
rate signal is used.
-5-
(3) Typical System Configuration for Group 3 (Type: M)
Metal Housing
Alarm Unit Indicator Indicator
VAS Unit, V3 Unit, V3
Type M Type M
Analog Output
Recorder
OUT
P
GAS IN
-6-
(4) Typical System Configuration for Group 4 (Type: Hi, Ci, Ti)
Analog Ooutput
Recorder
Instrument Panel
Instrument panel terminal block
Ground
OUT
P
E
Ground
GAS IN
Ground
-7-
5. Outer Appearance and Component Names
4 7 8
12
1
10 9 11 13
2 3 5 6
-8-
2
3
1
4
6
7
8 11
10 12
-9-
6. Installation
WARNING
This indicator unit is not explosion-protected equipment. Ensure that it is installed in a
non-hazardous area.
CAUTION
Install this indicator unit at an easily accessible location where the it is constantly monitored by an
attendant, convenient for taking emergency procedures and giving instructions in the event of an
alarm.
Install the indicator unit at a location free of vibration, electrical noises, or high humidity.
Do not install the indicator unit in the vicinity of radiofreqency emitting devices.
(1) When you prepare a panel to amount metal housings with indicator/alarm units by yourself, take the
following steps.
Prepare a panel (1.6 to 6 mm thick) and cut out a square hole on it. Refer to the drawing below for the
cut-out size.
38.5 × n + d
d: Allowable tolerance.
60 or more
n = 1 to 10 d=3
n = 11 to 15 d=4
n = 16 to 20 d=5
n = 21 to 25 d=6
n = 26 to 30 d=7
Panel Cut Size (Unit: mm)
Note: Keep 60mm or more between two square holes for two-stage installation.
Panel
Top View
- 10 -
(3) Insert the metal housing(s) in the front side of the panel through the square cutout.
When installing more than one metal housing, insert a partition board between each pair of metal
housings.
Metal Housing
Metal Housing
Partition Board
Panel Panel
Installation of One Metal Housing Installation of More than One Metal Housing
(4) Secure each metal housing to the panel by tightening two screws with a minus driver as shown in the
drawing below.
When installing more than one metal housing, tighten the screws until there is no gap between the metal
housings and partition boards, while moving the metal housings toward the center.
Panel
Screw
Metal Housing
Screw
Side View
(5) Adjust the position of the clamps and firmly tighten the fixing screws into the panel until there is no gap
between the metal housing and the clamp.
- 11 -
7. Wiring Connections
On the back side of the metal housing are two rows of an 8-way terminal block. Use this terminal block to
connect the indicator unit to a gas detector, power source, and external control devices. Note that this
terminal block is compact in size and is therefore not suitable for external wiring. Establish a separate
terminal block using M3-size round solderless terminals (outer dimension of 6.4 or less) to accommodate
such wiring.
To connect the indicator unit to an alarm unit, use the connectors included in the standard package and a flat
cable assembly (optional).
1–AT
9 1
2–Z2
To Alarm Unit
10 2
3–AS
11 3
4–AR Connector
12 4
5–BZ 13 5
6–Z1 14 6
7– 15 7
16 8
8–
Terminal
Connector
Term
inal Metal Housing: V-SC-4A Metal Housing: V-SC-1
No.
1 P (+) Power source P (+) Power source
2 N (–) 24VDC N (–) 24VDC
3 PA (+) Pump power output PA (+) Pump power output
4 PB (–) 24VDC PB (–) 24VDC
5 A (F) A (F)
6 B B
Gas detector Gas detector
7 C C
8 D D
9 AC2 2nd-stage alarm ZC Common
“Open” or “closed” during
10 ZA2 normal operation *1 ZA2 nd
2 -stage alarm
Contact
11 ZC1 1st-stage alarm ZB2 1c contact Contact output
output
“Open” or “closed” during 100VAC, 1A
100VAC, 1A
12 ZA1 normal operation *1 24VDC, 1A
ZA1 1st-stage alarm 24VDC, 1A
13 TC Trouble alarm ZB1 1c contact
“Open” or “closed” during
14 TZ normal operation *1 TZ Trouble 1a contact
15 G (+) G (+)
Analog output Analog output
16 H (–) H (–)
*1: As per metal housing specifications.
Figure 7. Terminal and Connector Pin Assignment
・ Output terminals (Nos.3 and 4) are only used for connecting a suction-type gas detector
MEMO with a built-in 24VDC pump and NOT a 100VAC pump.
・ Do not use the pump power output for any purpose other than to supply power to
suction-type gas detectors.
- 12 -
7-1. Connection with Gas Detectors
CAUTION
Ensure that the cables are connected correctly by referring to the marking between the indicator
unit and the gas detector.
Make sure that cables are connected as far away from the electric power line as possible.
When wiring a gas detector at a hazardous location, be sure to us explosion-proof wiring. Refer to
the insturction manual for the gas detector for the installation of explosion-proof wiring.
Figures 8, 9, and 10 show the connections between metal housings and gas detectors. Make sure that the
number on the tag number plate of the indicator unit and the number on the loop number sticker of the gas
detector match before connecting.
Connect the pump power source for suction-type gas detectors (pump power source 24 VDC) to the
terminals PA (+) and PB (-) (Terminal Nos.3 and 4).
MEMO Refer to the instruction manual of the gas detector for information on cable length.
(1) Typical Wiring Connection with Gas Detectors for Group 1 (Type: Hv, Cv, Tv)
3 3 3
4 4 4
Indicator Unit 5 5 5
6 6 6
7 7 7 Instrument Panel
8 8 8
Instrument Panel
Terminal Block B C D E PA PB B C D E PA PB F B C D E
Gas Detector B C D PA PB B C D PA PB F B C D
E (+) (–) E (+) (–) E
- 13 -
(2) Typical Wiring Connection with Gas Detectors for Group 2 (Type: O, D)
3 3 3
4 4 4
Indicator Unit 5 5 5
6 6 6
7 7 7
8 8 8
Instrument Panel
Single Class-A
Grounding
Instrument Panel
Terminal Block Zener
C D E PA PB F C D E 11 12 E
Barrier
BT-150
C D E
Gas Detector
C D E PA PB F C D E C D E
E (+) (–) E E
E E
- 14 -
(3) Typical Wiring Connection with Gas Detectors for Group 3 (Type: M)
3 3
4 4
Indicator Unit 5 5
6 6
7 7 Instrument Panel
8 8
Instrument Panel
Terminal Block P N G E P N G F E
Gas Detector P N G H E P N G H F N E
(+) (–) (+) (–)
Diffusion-type Suction-type
*"F is for a gas detector with a
built-in flow sensor only.
- 15 -
(4) Typical Wiring Connection with Gas Detectors for Group 4 (Type: Hi, Ci, Ti)
3 3
4 4
Indicator Unit 5 5
6 6
7 7 Instrument Panel
8 8
Instrument Panel
A B C D E PA PB A B C D E
Terminal Block
Gas Detector A B C D PA PB A B C D
E (+) ( – ) E
Diffusion-type Suction-type
(Pump Power Source 24VDC)
- 16 -
7-2. Connection with Alarm Unit
Connect indicator units to an alarm unit by using flat cable assemblies (optional).
The number of connectors on the flat cable assembly (FAS-1) is equivalent to the total number of indicator
units and an alarm unit to be connected. Connect these connectors to the connectors on the rear sides of the
metal housings.
When indicator units are mounted in two stages, a flat cable assembly (FAS-2) with two flat cable assembly
connectors (FAS-3) is required to connect the top and bottom stages. In this case, the number of connectors
required for a flat cable assembly (FAS-1) is equivalent to the total number of indicator units and an alarm
unit plus one for each stage.
Connectors
Rear Side of
Alarm Unit
Rear Sides of
Indicator Units
- 17 -
7-3. Connection with Power Source
A 24 VDC power source needs to be connected between the terminals P (+) and N (-) (Terminal Nos.1 and
2). If 24 VDC is not available, connect to a special VPW-type power source unit (sold separately) for use
with 100 VAC commercially-available power source.
CAUTION
When a large number of units are employed, monitor the current capacity and voltage drop of the
wiring cables while connecting.
Make sure that the polarities are correct.
Common
9
Common 2nd-stage N/O Input Type
9
Annunciators
10 10
2nd-stage 2nd-stage
N/C Input Type
11 11 Annunciators
1st-stage 1st-stage
To Control
12 Devices 12
1st-stage N/O Input Type
13 Annunciators
13
Control Power
- 18 -
7-5. Connection with Analog Output
Analog signals ranging from 4 to 20 mA, depending on the gas concentration, are transmitted from the
terminals (Nos.15 and 16). The polarities (Nos.15 and 16) are + and –, respectively.
A recorder or PLC is connected to the analog output terminals, as necessary.
Indicator Unit
+
15
- 19 -
7-6. Connection with Instrument Panel Reset Switch
A flat cable assembly (FAS-1) and a reset relay terminal (optional) are required to connect reset signals to
the reset switch on the instrument panel without using an alarm unit.
The reset relay terminal is installed by removing the screws of the metal housing on the right of the panel’s
rear side. The number of connectors attached to flat cable assemblies (FAS-1) is equivalent to the number of
indicator units plus one. Attach the flat cable assemblies to the connectors on the rear side of the metal
housings and the reset relay terminal.
MEMO For an external reset operation using an alarm unit, refer to the instruction manual for the
alarmu unit.
Metal Housing
Install the terminal by removing these screws.
Flat Cable Assembly
(FAS-1)
To Reset Switch
9
9 1
1
10
10 2
2
11
11 3
3 Clamp
12
12 4
4
13
13 5
5
14 6
14 6
15 7
15 7
16 8
16 8 Reset
AS
AR
N
a) Semi-lock Type
To Power Source Terminal N
Buzzer Stop
AS
AR Reset
N
b) Full-lock Type
To Power Source Terminal N
- 20 -
8. Operating Procedures
8-1. Start-up Operation
Important
The start-up operation should be carried out by New Cosmos authorized personnel. Please contact us
for the start-up operation. Checks and adjustments performed at start-up (e.g., zero/span adjustments,
operational checks using actual gas) are extremely important for the reliability of gas detection/alarm
systems, and accuracy of adjustment is crucial. Moreover, use of actual gas (e.g., combustible gas,
toxic gas) is extremely hazardous.
CAUTION
Before turning on the unit, refer to Section 7 “Wiring Connections” on page 12 to check that all
the components are connected correctly. Also check your delivery specifications, if you have
received it.
Do the following steps to operate the indicator after making sure that the power source voltage and the
wiring are correct.
(1) Power-on
Turn the power switch to the on position. The POWER lamp (green) will begin flashing and the
warm-up operation will begin.
Once the warm-up operation is completed, the indicator unit is ready for normal operation.
If further adjustment is necessary, refer to 8-2 “Maintenance Mode”.
- 21 -
8-2. Maintenance Mode
During the maintenance mode, the alarm contact output and the alarm function of the alarm unit are
disabled. Set the indicator unit in the maintenance mode to make adjustments, check the alarm function
using the TEST buttons, or perform an operational check using actual gas.
There are two types of maintenance modes in this indicator unit: Maintenance Mode 1 and Maintenance
Mode 2. The differences between the two modes are described in the table below:
<3> To exit the maintenance mode, press and hold the MNT button until the MNT lamp turns off.
- 22 -
8-3. Adjustment Procedures
(1) Flow Rate Adjustment
When a suction-type gas detector is connected, make sure that the center of the sphere of the flow meter
of the gas detector aligns with the red line. If not, adjust the flow with the gas detector. For details, refer
to the instruction manual of the gas detector.
(2) Modes
<1> Release of Mode Lock
Before starting manual zero/span/other adjustments, the mode lock should be released.
The unlock procedure is given below.
-Unlock Procedure-
1. Press and hold the HIGH button (more than 3 seconds).
2. Press the ADJ button.
3. Press the LOW button.
4. Press the HIGH button.
When the mode lock is released, the POWER lamp (green) will begin flashing rapidly.
MEMO The mode lock cannot be released during the test mode.
To use the test mode (page 28) while the mode lock is released, cancel the test mode
once, then release the lock to re-enter the test mode.
- 23 -
<2> Mode Selection (How to select the mode)
Release the mode lock so that the mode can be selected. Pull and remove the indicator unit out of
the metal housing to locate five LEDs (Nos.1-5) on the left side of the indicator unit. The number
printed next to each LED represents the corresponding main mode (1 to 5). Only one LED is on at a
time. The light in these LEDs moves from left to right or vice versa by turning the multi-functional
switch backward/forward. Select the desired main mode by turning the switch.
Press up the switch once. The TROBULE lamp on the front side of the indicator unit will turn on.
The five lamps on the front TORUBLE, ALARM”, ALARM, MNT and TEST, represent their
corresponding sub-modes. Refer to Table 1 for more details.
The sub-mode can be changed by pressing up the multi-functional switch. Select the desired
sub-mode by pressing it up. (e.g. When 1 is selected for main mode and the TROUBLE lamp is on,
Mode 1-1 is selected.)
Press and hold the switch until the POWER lamp will go off for a few seconds. The current setting
is saved. The Power lamp starts flashing.
- 24 -
The table below lists the main modes and sub-modes that can be selected. Refer to the following pages for
the use and adjustment procedures for them.
To lock the current settings, press up and hold the multi-functional switch.
Main mode Function Sub-mode Lamp Status
1 Coarse zero adjustment TROUBLE lamp is on.
2 Fine zero adjustment ALARM 2 lamp is on.
3 Span adjustment ALARM 1 lamp is on.
Input 4 For Groups 1, 2, and 3: MNT lamp is on.
1
Adjustment One-man maintenance (span adjustment)
For Group 4:
Fine span adjustment
5 One-touch zero adjustment TEST lamp is on.
1 Zero adjustment TROUBLE lamp is on.
2 Span adjustment ALARM 2 lamp is on.
Analog Output 3 Selection of 4-20 mA/1-5 V ALARM 1 lamp is on.
2
Adjustment 4 Analog output adjustment for Maintenance MNT lamp is on.
Mode 2
5 Analog output adjustment for initial delay TEST lamp is on.
1 ――― ―――
For 2 ――― ―――
3 Manufacturer 3 ――― ―――
Use only 4 ――― ―――
5 ――― ―――
1 Setting the alarm set point TROUBLE lamp is on.
2 Heater current adjustment ALARM 2 lamp is on.
Other 3 Switching the intensity level of the LED ALARM 1 lamp is on.
4
Adjustment bar graph meter between ‘high’ and ‘low’.
4 Display of linear data (for reference only) MNT lamp is on.
5 ――― ―――
1 ――― ―――
For 2 ――― ―――
5 Manufacturer 3 ――― ―――
Use only 4 ――― ―――
5 ――― ―――
- 25 -
(3) Checking and adjusting the current of sensor heater (for Groups 1 and 4 only)
Pull the panel lock knob to remove the indicator unit from the metal housing. Connect a voltmeter
having a high internal resistance (min.100 kΩ) to the test terminal of the heater, which is located at the
top of the indicator unit. Measure the heater current. A standard resistor (1Ω) is installed in between the
(+) and (-) test terminals. Therefore, for example, if the measured voltage is 180 mV, it means the current is
180 mA. A heater current sticker is attached on the right side of the indicator unit. Check that the measured
current is ±2 mA of the value specified in the sticker. If the measured current is out of the specified range,
enter Mode 4-2 (heater current adjustment), and turn the multi-functional switch forward or backward to
adjust the heater current so that it will be within the specified range. To save the current settings, press up
and hold the multi-functional switch until the POWER lamp goes off.
Heater Current Sticker Voltmeter
Heater Current
Test Terminal
CAUTION
• When making a zero adjustment, always make sure that the air around the gas detector is clean.
Proper adjustments cannot be performed in gas atomosphere.
- 26 -
<1> One-touch Zero Adjustment (Perform manual zero adjustment for Group 4, which has no one-touch
zero adjustment function. Refer to <2>-B for the procedure.)
Make sure that the atmosphere in the vicinity of the gas detector is gas-free, and press and hold the
ADJ button on the front panel until the POWER lamp turns off. The POWER lamp will temporarily
turn off, and the zero adjustment procedure will begin. Once the adjustment is completed, the
POWER lamp flashes once. If the zero adjustment fails, the POWER lamp slowly flashes three times.
If the adjustment is unsuccessful, perform a manual zero adjustment described in <2> below.
One-touch zero adjustment is also available by using Mode 1-5. (Press up and hold the
multi-functional switch to lock the current settings after the adjustment with Mode 1-5.)
Make sure that the atmosphere in the vicinity of the gas detector is gas-free. Select Mode 1-1
(coarse zero adjustment) or Mode 1-2 (fine zero adjustment) Turn the multi-functional switch
forward or backward to adjust the value of the bar graph meter to “0.”
When the adjustment is completed, press up and hold the multi-functional switch until the
POWER lamp turns off. The set value will be saved. Be sure to perform this step each time the
adjustment is completed. To cancel the adjusted value, either press up the multi-functional switch
once or press the LOW button before pressing up and holding the multi-functional switch. The
setting will be cancelled.
- 27 -
To perform a span adjustment after completing the zero adjustment, press up the multi-functional
switch once to select Mode 1-3 (span adjustment) and make the adjustment by following the
procedure in <3> below.
To perform setting and adjustment in a different mode, press the LOW button on the front side of
the indicator unit. The current mode will end and another mode can be selected.
To complete the adjustment procedure, press and hold the HIGH button on the front side of the
indicator unit. The currently selected mode will be locked and normal operation will resume.
Make sure that no gas is found in the vicinity of the gas detector. Turn the multi-functional switch
forward or backward to adjust the bar graph meter until the TEST lamp turns on.
Once the adjustment is completed, press up and hold the multi-functional switch until the
POWER lamp turns off. The set value will be saved. Be sure to perform this step each time the
adjustment is completed. To cancel the adjusted value, either press up the multi-functional switch
once or press the LOW button before pressing up and holding the multi-functional switch. The
setting will be cancelled.
Refer to Table 1, “List of Modes” on page 25, and select Mode 1-2 (fine zero adjustment).
Make sure that no gas is found in the vicinity of the gas detector. Turn the multi-functional switch
forward or backward to adjust the value of the bar graph meter to “0.”
Once the adjustment is completed, press up and hold the multi-functional switch until the
POWER lamp turns off. The set value will be saved. Be sure to perform this step each time the
adjustment is completed.
To perform a span adjustment after completing the zero adjustment, press up the multi-functional
switch once to select Mode 1-3 (span adjustment) and make the adjustment by following the
procedure in <3> below.
- 28 -
<3> Span Adjustment
<3>-A. Span Adjustment for One-man Maintenance (not available for Group 4. Perform the span
adjustment in <3>-2)
Span adjustment for one-man maintenance is a function that allows one operator to perform the
span adjustment using the peak hold function by doing the following steps.
1. Set the indicator unit to the maintenance mode (page 22) and release the mode lock by
following the procedure in (2) <1> on page 23.
2. Refer to Table 1, “List of Modes” on page 25, and set the indicator unit to Mode 1-4 (span
adjustment for one-man maintenance).
3. First decide the target value to be set by span adjustment. A red line is now shown on the bar
graph meter. Using the multi-functional switch, adjust the position of this red line according to
the concentration of the target gas to be detected by the gas detector. Once the value is decided,
save the value by pressing up and holding the multi-functional switch until the POWER lamp
turns off.
4. Once the span-adjusted value is saved, the current gas concentration and the red line indicating
the set value will be shown. The gas concentration bar is shown in green except the peak value,
which is shown in orange. Once this display is shown, introduce the gas into the gas detector.
When the gas is no longer supplied, the concentration level will drop, but the peak value will
remain as the orange line.
5. If the red and orange lines are not aligned, press up and hold the multi-functional switch until
the POWER lamp turns off. The red line will turn into an orange line. Span adjustment is now
completed.
Red line turns into an orange line.
- 29 -
6. Finally, if you desire to enter the other mode and make other setting, press the LOW button on
the front side of the indicator unit. If not, press and hold the HIGH button to complete the
procedure.
<3>-B. Span Adjustment to be Performed by at Least Two Operators (for Groups 1-4)
Introduce the calibration gas to the gas detector. Once the display on the bar graph meter
stabilizes, select Mode 1-3 (span adjustment) and adjust the value to the correct value
corresponding to the calibration gas by using the multi-functional switch. (Refer to the instruction
manual for the gas detector for details on how to inject gas into the gas detector.)
Once the adjustment is completed, press up and hold the multi-functional switch until the
POWER lamp turns off. The set value will be saved. Be sure to perform this step each time the
adjustment is completed.
Select Mode 1-4 (fine span adjustment) and adjust the value of the bar graph meter to the correct
value corresponding to the calibration gas by using the multi-functional switch.
Once the adjustment is completed, press up and hold the multi-functional switch until the
POWER lamp turns off. The set value will be saved. Be sure to perform this step each time the
adjustment is completed.
- 30 -
(6) Zero/span Adjustments for Analog Output
Follow the procedure in (2) <1> on page 23 to release the mode lock.
As per Table 1 on page 25, enter Mode 2-1 for zero adjustment and Mode 2-2 for span adjustment, and
connect a tester to the terminals (Nos.15 and 16) on the rear side of the metal housing.
Once the mode is entered, an analog output under the current zero or span adjustment is shown. If the
reading is not 4 mA or 20 mA, turn the multi-functional switch forward or backward to make
necessary adjustments. Once the adjustment is completed, press up and hold the multi-functional
switch until the POWER lamp turns off. The set value will be saved.
Using the same procedure, the analog output for Maintenance Mode 2 can be set (Mode 2-4). Make
adjustment for your purpose if necessary.
<2> Press the TEST button on the indicator unit to enter the test mode. Use a stick with a round tip for
pressing this button. Once the test mode is entered, the bar graph meter switches to the test level
display.
Change the test level by using the HIGH/LOW buttons on the front side of the indicator unit.
<3> Before exiting the test mode, be sure to set the test level below the alarm set point; when the test
mode is entered again, the test level set during the previous test mode will be kept. Then press the
TEST button to cancel the test mode. The test mode is also cancelled if no operation is performed for
10 minutes.
<4> If the maintenance mode has been selected, press the MNT button for about 3 seconds after the
operational check to resume normal operation.
DANGER
Be sure to cancel the maintenance mode after completing the operational check in the test mode. If
the maintenance mode is kept, the alarm contact output and the output to the alarm unit will not
function even if the gas detector detects the target gas at a concentration above the alarm set point.
- 31 -
CAUTION
When the alarm function is checked in the test mode, the analog output, alarm contact output,
and the output to the alarm unit are also enabled (but not in the maintenance mode). Thus, if the
alarm contact output is used to interlock an external device, be sure to release the interlock in
advance. Be sure to notify all personnel of the start of the inspection.
To disable the alarm contact output and the output to the alarm unit, refer to 8-2, “Maintenance
Mode” on page 22.
- 32 -
(9) Operation of Trouble Alarm
Check that the trouble alarm will be activated when the connection for the terminal (No.8) (D) on
the rear side of the metal housing is removed. To stop the trouble alarm, reconnect the cable wire.
CAUTION
Since the operational check of the trouble alarm is performed while the power is turned on, there is
a risk of electric shock. Do not perform this check since it has already been performed at the time
of shipping.
DANGER
When performing an operational check using actual gas, such as combustible gas that has a risk of
explosion or a toxic gas harmful to human health, incorrect handling may be extremely hazardous.
Make sure that qualified and experienced personnel or our company’s operators perform the check.
CAUTION
Be sure to check the power capacity of your facility as the high-intensity display consumes higher
electricity.
- 33 -
(12) Deactivation of Zero Suppression and Pre-calibration Functions
Press and hold the TEST button. While holding the button down, the calibration function is deactivated.
Note: Use a stick with a round tip to press the TEST button.
Even though the TEST button is pressed during Mode 1-1, Mode 1-2 or Mode 1-3, the
MEMO test mode will not be activated.
- 34 -
8-4. Instructions on Alarm Functions
<1> When the bar on the bar graph meter exceeds the 1st-stage alarm set point (or falls below the alarm set point
if it is the lower limit), the bar graph display will turn orange. The 1st-stage ALARM lamp (red) will begin
flashing and the 1st-stage alarm contact output will be activated.
<2> When the bar on the bar graph meter exceeds the 2nd-stage alarm set point (or falls below the alarm set
point if it is the lower limit), the bar graph display will turn red. The 1st-stage ALARM lamp (red) and the
2nd-stage ALARM lamp (red) will begin flashing and the 1st-stage alarm contact output and the 2nd-stage
alarm contact output will be activated.
DANGER
When the indicator unit begins to sound an alarm, stay calm and check that there is no fire in the
vicinity. Do not touch any electric switches under any circumstances. Sparks from turning the
switch on or off may cause ignition.
WARNING
If there is a gas leak alarm, take the necessary measures specified by your company.
- 35 -
<3> When your indicator unit is “double range type” (Optional),
The “double-range type” indicator unit monitors the gas concentration in two ranges, low and high.
The unit indicates the gas concentration in 0 to 10% LEL for low range and 0 to 100% LEL for high range.
The unit normally shows the concentration in low range. When the gas concentration reaches the
maximum in low range, the TEST/RANGEx10 lamp will turn on and the unit will automatically change the
indication to show the concentration in high range. When the gas concentration drops below the
maximum value (full scale value) of the low range, the TEST/RANGEx10 lamp will turn off and the unit
will automatically change the indication to show the concentration in low range.
When the TEST button is pressed, the test mode will be started and the TEST/RANGEx10 lamp will start
flashing.
“TEST/RANGE×10” “TEST/RANGE×10”
Lamp is off Lamp turns on.
- 36 -
8-5. How to Stop Alarm
The reset button and the buzzer stop button on the alarm unit or the control panel are used to stop an
alarm. Note that the procedure to clear the alarm varies depending on the alarm mode.
a) When the self-holding type indicator units and the full-lock type alarm unit are used,
<1> Press the buzzer stop button on the alarm unit. The ALARM lamp (red) on the indicator unit will turn on.
<2> Once the bar on the bar graph meter falls below the alarm set point, press the reset button on the alarm unit.
The LED bar will turn green when the 1st- and 2nd-stage alarms are cleared. The ALARM lamp on the
indicator unit (red) will turn off and the alarm contact output will be stopped.
Alarm Indicator/ Indicator Unit Indicator Unit Alarm Unit Alarm Unit
Contact ALARM Lamp Alarm Contact ALARM Lamp Buzzer
Status/Operation (red) Output (red)
When the alarm is activated Flashing Activated On Intermittent
When the buzzer stop button
is pressed (the reset button is On Activated On Deactivated
not pressed yet)
When the reset button is
Off Deactivated Off Deactivated
pressed (to clear the alarm)
b) When the self-holding type indicator units and the semi-lock type alarm unit are used
<1> Press the reset button on the alarm unit. The ALARM lamp (red) on the indicator unit will turn on.
<2> Once the bar on the bar graph meter falls below the alarm set point, the LED bar will turn green
automatically (1st- and 2nd-stage alarms will be cleared), the ALARM lamp (red) will turn off and the
alarm contact output will be stopped.
Alarm Indicator/ Indicator Unit Indicator Unit Alarm Unit Alarm Unit
Contact ALARM Lamp Alarm Contact ALARM Lamp Buzzer
Status/Operation (red) Output (red)
When the alarm is activated Flashing Activated On Intermittent
When the reset button is
pressed and the bar is above On Activated On Deactivated
the alarm set point
The bar drops below the alarm
Off Deactivated Off Deactivated
set point (alarm is canceled)
- 37 -
8-6. Trouble Alarm
The trouble indicators and the trouble alarm output will be activated when the indicator unit detects any
problem, such as a decrease in the gas concentration level detected by the gas detector or a decrease in the
flow rate of the suction-type gas detector with a built-in flow sensor. Check the cause of the problem and
take necessary steps.
When the trouble alarm is activated, the alarm unit will sound a continuous beep. Press the buzzer stop
button on the alarm unit (or the reset button if your alarm unit is semi-lock type) to stop the buzzer.
Indicator Unit Indicator Unit Indicator Unit Alarm Unit Alarm Unit
POWER Lamp TROUBLE TROUBLE TROUBLE Buzzer
(Green) Lamp Alarm Contact Lamp
(Yellow) Output (Yellow)
When the
Continuous
trouble alarm On Flashing Activated On
beep
activates.
From the time
the buzzer stop
button (or reset
button) is On Flashing Activated On Deactivated
pressed until the
problem is
fixed.
Starts flashing
when the
warm-up
operation begins,
and turns on
The problem is when it is
Off Cancelled Off Deactivated
fixed. completed.
(When the flow
rate recovers to
normal levels, it
turns on
immediately.)
- 38 -
-Troubleshooting-
-
Take the fuse out of the fuse holder and ensure that it has not blown. If not, investigate for other cause(s)
and take appropriate actions.
Location of
Possible Cause LED Lamp Status Corrective Action
Trouble
Take the fuse out of the fuse holder,
remove the cause of excessive
current, and replace it with a new one.
Blown Fuse All lamps: Off
(Refer to Section 5 “Outer
Appearance and Component Names”)
Problem in
indicator unit
If the power voltage falls to 18.0 V or
below, the trouble alarm will sound.
Drop in power POWER lamp: On
Make sure that the power voltage is
voltage TROUBLE lamp: Flashing
24.0 V±10%.
*Applicable only to suction-type gas detectors with a flow sensor that emit low flow rate signals.
If none of the above causes is applicable, or the problem is not fixed after action has been taken, consult
our authorized representative.
- 39 -
9. Maintenance and Inspection
(1) Routine Check
Perform routine check given in the table below.
CAUTION
Checking the alarm function by pressing the TEST button activates the analog output, alarm
contact output, and output to the alarm unit (does not activate in the maintenance mode). For
this reason, if the alarm contact output is used to interlock an external device, release the
interlock beforehand. Also, notify all personnel of the inspection before starting it.
The circuitry check (with the TEST button) on the alarm must be done more than once a
month, and the check on detection and alarm must be done more than once a year in
accordance with the applicable safety rules for liquefied petroleum gas and high-pressure
gases.
- 40 -
10. Before Requesting Repair
Before requesting repairs, check the following: If any problems occur with your unit, check the following
before requesting repairs.
If the symptom persists after performing the action above, or the problem is not listed in the table above,
contact our authorized representative for repair.
- 41 -
11. Specifications
Item Description
Product Name Indicator Unit (for gas detection/alarm system)
Model V3
Detection Method As per specifications of gas detector
Number of Alarm Stages 2 stages
Indicator 3-colored LED bar graph meter (50 segments)
Target Gas As per specifications of gas detector
Indication Range As per specifications
A la r m S et Ran g e As per specifications
As per specifications of gas detector
A la r m A ccu rac y ・Combustible gas: ±25% of the alarm set point under the same conditions
・Toxic gas: ±30% of the alarm set point under the same conditions.
As per specifications of gas detector
・Combustible gas: 30 seconds or less for the concentration that is 1.6 times as high
as the alarm set point
Delay Time
・Toxic gas: 60 seconds or less for the concentration that is 1.6 times as high as the
alarm set point
(excluding delay time caused by piping length)
ALARM lamps: Flashes when alarm occurs; continuously lit by reset operation,
Alarm Indication
Two types available, self- holding type and auto-recovery type.
1st-stage, 2nd-stage, trouble, no-voltage contact output
“Open” or “closed” under the normal operation; normally excited or non-excited
Alarm Contact
modes available for some specifications
(Contact capacity: 100VAC 1A, 24VDC; 1A resistance load)
A n alo g Ou tp u t 4-20 mA (standard), 1-5V (optional)
Power Source 24 VDC ± 10% (24 VDC ± 6V for some gas detectors connected)
Approx. 5.0W for power source 24V; power-saving display mode; gas detectors for
V2 model (Groups 1, 2, and 3)
Approx. 4.0W for power source 24V; power-saving display mode; gas detectors for
V1 model (Group 4)
Power Consumption
Approx. 7.0W for power source 24V + 6V; high-intensity display mode; gas
detectors for V2 model (Groups 1, 2, and 3)
Approx. 5.0W(for power source 24V + 6V; high-intensity display mode; gas
detectors for V1 model (Group4)
Dimensions W36 x H144 x D70mm (excluding metal housing and projections)
Weight Approx.150g (excluding metal housing)
Operating temperature range: -10 to +40°C (no drastic temperature change)
Operating Conditions Operating humidity range:10 to 90 %RH (no drastic humidity change and no
condensation)
Connection Method By cable connectors
Installation Method To be installed to a metal housing or a wall-mounted gas detection/alarm system
Protection Rating IP2X in mounted condition
The above specifications are subject to change without notice for improvement.
The customized specifications, if available, precede the standard specifications listed above.
- 42 -
12. Warranty
New Cosmos warrants its product to be free from defects in material and workmanship during normal use
and service for a period of one (1) year from the date of purchase. If the indicator unit is found to be
detective or malfunctions during the warranty period although it is used in accordance with the instruction
manual and specifications, we will provide repair service according to the warranty policy. For details, refer
to the warranty policy.
We are not responsible for any claims or damages resulting from the use of the product in a manner
inconsistent with this manual and intended purpose of the product.
Detection range The range of the target gas concentration subject to display and alarm
activation.
Alarm accuracy The difference between the alarm set point and the detected gas
concentration at which the alarm begins to sound, or the percentage
obtained by dividing said difference by the alarm set point and multiplying
the value by 100.
Delay time Time required for an alarm to be issued after the gas whose concentration
is higher (or lower) than the alarm set point reaches the gas detector.
Operating temperature and The ranges of temperature and humidity in which the gas detection/alarm
humidity ranges system can perform its intended functions.
Explosion-protected Structure to prevent electrical equipment from becoming a source of
construction ignition that causes the surrounding explosive atmosphere to ignite.
Calibration gas Gas used to calibrate the gas detection/alarm system.
Alarm set point Preset gas concentration value at which the alarm will be activated.
Maintenance and inspection Works to ensure the intended performance of the equipment.
- 43 -
Revision History
Edition No. Date Revision
GAE-041 May 2012 00
We welcome your input. If you have any comments, please contact New Cosmos or our authorized
representatives. Our Contact information is given below.
Contact Information
Distributor Manufacturer
New Cosmos Electric Co., Ltd.
2-5-4 Mitsuya-naka, Yodogawa-ku
Osaka 432-0036, Japan
Phone 81-6-6309-1505
Fax 81-6-6308-0371
Email e-info@new-cosmos.co.jp
http://www.new-cosmos.co.jp