Professional Documents
Culture Documents
TD2010 000629
TD2010 000629
terminals.
Abstract— This paper presents an over-voltage attenuation In order to reduce the transient over-voltages problems, some
performance analysis of RC clampers and surge arresters during devices, as RC clampers and surge arresters, should be
transients caused by switching off a no load transformer applied employed. Some qualitative advantages and disadvantages of
to an arc furnace. A Brazilian Industry actual system was arc furnace transformer over-voltage protection methods are
simulated using the Matlab/Simulink software. The simulation presented in [5].
results indicate that the adequate use of RC clampers can reduce
The main goal of this paper is to analyze the performance of
the arresters operations and practically eliminates the re-strikes
and repetitive transient over-voltages when using vacuum circuit the RC clampers and surge arresters in an arc furnace
breakers to switch the arc furnace transformer. transformer and transformers switches. The methodology used
is the digital simulations using the Matlab/Simulink software
Key-Words – arc furnace transformer, chopping level current, [6]. The calculation of RC clamper parameters is based on [7].
transient over-voltages, vacuum circuit breaker re-striking. Another benefit of this study is the clues to specify the
vacuum circuit breaker with enough dielectric strength, in
I. NOMENCLATURE order to avoid the re-strikes. In section III, a brief description
of the system studied is made. In section IV the simulation
VpPG: Phase-to-Ground Peak Voltage at HV Arc Furnace
results are plotted and a summary table of the over-voltages is
Transformer terminals (kV and PU Values)
shown. The main conclusions are presented in section V.
VpPP: Phase-to-Phase Peak Voltage at HV Arc Furnace
Transformer terminals (kV and PU Values)
III. THE SYSTEM STUDIED
VpCB: Contact Peak Voltage and Voltage variation in time of
Main Circuit Breaker (kV, PU and kV/ms Values) The actual system chosen to study the transient over-voltages
EAPG: Energy dissipated on Phase-to-Ground Surge Arrester is a 114 MVA arc furnace transformer, installed in a Brazilian
(Joules) Industry. The single line diagram of the system is plotted in
EAPP: Energy dissipated on Phase-to-Phase Surge Arrester Fig. 1. In this application, the circuit breaker should only
(Joules) switch off when the electrode is out of the furnace, i.e., at no
load transformer operation.
II. INTRODUCTION
Electrical System: 15
Line Current of Main Circuit Breaker
Cables: 5
Cable 1: From the main substation to the 34.5 kV arc furnace
Current (A)
switchgear: 0
Resistance = 0.00802Ω, Inductance = 0.0339mH,
Capacitance = 0.5672 μF; -5
Phase A (kV)
Phase-to-phase connected: ABB – POLIM H40, residual
voltage 98 kV at 1kA peak, wave 30x60 μS. 0
-100
RC clampers: (calculations based on [6], considering the 0 0.005 0.01 0.015 0.02 0.025 0.03
100
expected peak phase-to-ground voltage due the no load
Phase B (kV)
26.67kV/ms
switching equal 70.4 kV) 0
Resistance = 200 Ω, Capacitance = 0.125 μF.
-100
0 0.005 0.01 0.015 0.02 0.025 0.03
• With the surge arresters and with RC clampers at arc Fig. 3 – System without RC clampers and without Surge Arresters
furnace transformer terminals
• With the surge arresters and with the RC clampers at arc Phase-to-Ground Voltage at HV Arc Furnace Transformer terminals
terminals. 80
60
40
2 to 5 plot the circuit breaker line currents and voltages across -20
Phase-to-Phase Voltage at HV Arc Furnace Transformer terminals Phase-to-Phase Voltage at HV Arc Furnace Transformer terminals
150 150
100 100
50 50
Voltage (kV)
Voltage (kV)
0 0
-50 -50
-100 -100
-150 -150
0 0.005 0.01 0.015 0.02 0.025 0.03 0 0.005 0.01 0.015 0.02 0.025 0.03
Time (s) Time (s)
Fig. 5 – System without RC clampers and without Surge Arresters Fig. 8 – System without RC clampers and with Surge Arresters
Energy (Joules)
Contacts Voltage of Main Circuit Breaker Phase A
100
192kV/ms 1.5
Phase A (kV)
0
1
-100
0 0.005 0.01 0.015 0.02 0.025 0.03
0.5
100
Phase B Phase C
Phase B (kV)
18.76kV/ms
0 0
0 0.005 0.01 0.015 0.02 0.025 0.03
Time (s)
-100
0 0.005 0.01 0.015 0.02 0.025 0.03
Fig. 9 – System without RC clampers and with Surge Arresters
100
Phase C (kV)
200kV/ms
Energy Dissipated on Phase-to-Phase Surge Arresters
0
300
-100
0 0.005 0.01 0.015 0.02 0.025 0.03 250
Time (s) Phases C-A
200
Fig. 6 – System without RC clampers and with Surge Arresters
Energy (Joules)
150
Phase-to-Ground Voltage at HV Arc Furnace Transformer terminals
100
100
80
60
50
Phases B-C
40 Phases A-B
20 0
Voltage (kV)
-20
Fig. 10 – System without RC clampers and with Surge Arresters
-40
-60
In this case, the surge arresters clamps the phase-to-ground
-80
and phase-to-phase voltages at arresters residual voltage levels
-100
0 0.005 0.01 0.015
Time (s)
0.02 0.025 0.03
(close to 69 kV for the phase-to-ground arresters and close to
98 kV for the phase-to-phase arresters), as showed in Figs. 7
Fig. 7 – System without RC clampers and with Surge Arresters
and 8. As consequence, the breaker contacts voltages are
reduced from approximately 76 kV to 50 kV. Phase-to-phase
arresters absorb energy levels greater the phase-to-ground
4
ones. It can be noticed that, in this case, only the arresters 150
Phase-to-Phase Voltage at HV Arc Furnace Transformer Terminals
Voltage (kV)
system with the surge arresters and with the RC clampers only 0
Energy (Joules)
3
Contacts Voltage of Main Circuit Breaker
100 2.5
Phase A (kV)
27.5kV/ms
2
0
1.5
-100
0 0.005 0.01 0.015 0.02 0.025 0.03 1
100
0.5 Phase B Phase C
Phase B (kV)
11.8kV/ms
0 0
0 0.005 0.01 0.015 0.02 0.025 0.03
Time (s)
-100
0 0.005 0.01 0.015 0.02 0.025 0.03
Fig. 14 – System with RC clampers only at transformer terminals
100
Phase C (kV)
28.67kV/ms
0 Energy Dissipated on Phase-to-Phase Surge Arresters
30
Phases C-A
-100
0 0.005 0.01 0.015 0.02 0.025 0.03 25
Time (s)
20
Fig. 11 – System with RC clampers only at transformer terminals
Energy (Joules)
15
Phase-to-Ground Voltage at HV Arc Furnace Transformer Terminals
100
10
80
60
5
0
20 0 0.005 0.01 0.015 0.02 0.025 0.03
Voltage (kV)
Time (s)
0
-60
The connection of the RC clampers at transformer and
-80
circuit breaker terminals clamp the phase-to-phase and the
phase-to-ground voltages at levels less than the residual
-100
0 0.005 0.01 0.015
Time (s)
0.02 0.025 0.03 voltages of the surge arresters. So, none arrester discharged.
-7
Contacts Voltage of Main Circuit Breaker x 10 Energy Dissipated on Phase-to-Ground Surge Arresters
100 3
Phase A (kV) 13.33kV/ms
0 2.5
-100
0 0.005 0.01 0.015 0.02 0.025 0.03 2
Energy (Joules)
100
Phase B (kV)
6.85kV/ms
1.5
0
Phase A
-100 1
0 0.005 0.01 0.015 0.02 0.025 0.03
100
0.5
Phase C (kV)
14.1kV/ms
0 Phase B Phase C
0
0 0.005 0.01 0.015 0.02 0.025 0.03
-100 Time (s)
0 0.005 0.01 0.015 0.02 0.025 0.03
Time (s)
Fig. 19 – System with Surge Arresters and RC clampers at Transformer
Fig. 16 – System with Surge Arresters and RC clampers at Transformer and Circuit Breaker terminals
and Circuit Breaker terminals
-3
x 10 Energy Dissipated on Phase-to-Phase Surge Arresters
3
Phase-to-Ground Voltage at HV Arc Furnace Transformer terminals
100
80 2.5
60 Phases C-A
2
40
Energy (Joules)
20
Voltage (kV)
1.5
-20 1
-40
0.5
-60
Phases B-C Phases A-B
-80
0
0 0.005 0.01 0.015 0.02 0.025 0.03
-100 Time (s)
0 0.005 0.01 0.015 0.02 0.025 0.03
Time (s)
Fig. 20 – System with Surge Arresters and RC clampers at Transformer
Fig. 17 – System with Surge Arresters and RC clampers at Transformer and Circuit Breaker terminals
and Circuit Breaker terminals
The summary of the results obtained from figures 2 to 20 is
150
Phase-to-Phase Voltage at HV Arc Furnace Transformer terminals
shown at Table I. With this data is possible to specify properly
surge arresters and vacuum circuit breaker.
100
TABLE I
50
MAXIMUM VOLTAGE AT SEVERAL POINTS OF THE CIRCUITS STUDIED
System
VpPG* VpPP** VpCB* EAPG EAPP
Voltage (kV)
Configuration
0
Without RC
76kV
clampers and 84kV 145kV
2.7pu - -
-50 without surge 2.98pu 2.97pu
143kV/ms
arrester
Without RC
-100 50kV
clampers and 58.5kV 88.5kV
1.77pu 1.5 J 222 J
with surge 2.07pu 1.81pu
200kV/ms
-150
0 0.005 0.01 0.015 0.02 0.025 0.03 arrester
Time (s) With surge
arresters and
46kV
Fig. 18 – System with Surge Arresters and RC clampers at Transformer with RC 51kV 85,5kV
1.63pu 3.10-3 J 25 J
and Circuit Breaker terminals clampers only 1.81pu 1.75pu
28.67kV/ms
at transformer
terminals
With surge
arrester and
RC clampers 45kV
41kV 70.5kV
at transformer 1.60pu 1.10-7 J 2.10-3 J
1.45pu 1.44pu
and circuit 14.1kV/ms
breaker
terminals
6