Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Lucy Switchgear Scimitar Brochure 2013

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Scimitar SFRMU

Fused Ring Main Units up to 17.5kV


with automation and remote control options

providing intelligent solutions


Scimitar
Fused Ring Main Units type SFRMU
providing intelligent solutions

Available up to 17.5kV, the SF6 insulated Fused Ring Additional Safety Features
Main unit is designed for harsh and demanding
environment applications. The units are fully • Intuitive single line mimic diagram and mechanical
type-tested at KEMA and IPH test laboratories and indicators for safe operation
built to the highest standards to meet stringent • Internal arc protection
customer requirements thereby offering maximum
operator safety. • Cable termination boxes are located at the side and rear of
unit, away from operator
The key features of the range are: • Fully interlocked switching mechanism and cable
box covers
• Fully sealed, environment independent fuse compartment
mounted in air outside an SF6 filled tank • Padlocking facility for switching mechanism to prevent
unauthorised operation
• Compact and fully extensible range
• Anti reflex mechanism to prevent switch opening under
• Free standing and transformer mounted options fault conditions
• No on-site SF6 gas handling for installation of • Separate Earth and test facility in accordance with IEC
extensible units and IEC requirements
• Easy integration with SCADA network for remote • Voltage presence indication system for live cable indication
operation and control (Neon indicators)
• Motorisation for remote control
• Hermetically sealed stainless steel switching chamber
Accessories
• Up to IP54 for indoor and outdoor use
• Remote tripping of fuse switch
• Remote operation of ring switches
• Auxiliary switches
• Neon live line indicators
• Phase comparison facilities
• Castell interlocks
• Interlocks for safe operation
• Earth fault indicators
• Fuse blown indication
Scimitar 2x SFRMU

To find our more about Scimitar, visit:


www.lucyswitchgear.com
Operation
Mechanism:
The operating mechanisms are of the independent
manual spring charged type for both main and earth
switches, ensuring that speed of operation is not reliant
on the operator.

Ring Switches:
The fault make, load break ring switches can be
manoeuvred into any one of the three positions: ‘ON’,
‘OFF’ or ‘CIRCUIT EARTH’. A stainless steel tank contains
SF6 gas in which the switch contacts operate.

Fuse Switch:
This consists of an HV Fuse with a series connected fault
make, load break switch also having three positions,
‘ON’, ‘OFF’ and ‘TRANSFORMER EARTH ON’. A separate
independent manually operated spring mechanism
guarantees constant contact operation speed.

The ‘ON’ to ‘OFF’ sequence is achieved either by manual


tripping of the spring mechanism or by the action of
any of the fuse link striker pins following the rupture of
a fuse.

Robustness
At its core, the SFRMU has a stainless steel switching tank
which is seam welded to ensure excellent structural integrity.
The zinc coated steel outer cladding is electrostatically painted Scimitar SFRMU Freestanding
then oven cured in order to confer the qualities required to
resist extreme climatic conditions.

Scimitar SFRMU TM Transformer Mounted


Transformer Protection
The fuse switch combinations are suitable for protecting
transformers up to 1500kVA. DIN fuses 442mm in length
and up to 160A rating can be fitted. Alternatively, DIN fuses
292mm in length can also be accommodated if required.
Scimitar SFRMU
Electrical Performance

Type RMU Fuse Switch


Extensibility Extensible and Non Extensible Extensible
Product SFRMU SFS1E

Rated Voltage 12 kV / 15.5kV 17.5kV 12 kV / 15.5kV 17.5kV
Ring Switch
Rated Current 630A 400A
Making Capacity (Main/Earth) 62.5kA Pk 54.6kA Pk
Breaking Capacity (Main) 630A 400A
Short Time Withstand (Main/Earth) 25kA/1s 21kA/1s
Basic Impulse Level 95kV P 95kV Pk

Fuse Switch
Rated Current 200A
Making Current (Main/Earth) 62.5kA Pk 54.6kA Pk 62.5kA Pk 54.6kA Pk
Breaking Capacity (Main) 20kA
Short Time Withstand (Earth) 3.15kA/1s
Basic Impulse Level 95kV Pk

General
Rated Frequency 50/60Hz
Minimum Operating Temperature -25°C to +55°C
IP Rating IP33 (IP54)
Weight 430kg
Filling Pressure 0.4 Bar G
Minimum Gas Pressure 0.05 Bar G
Standards IEC 60420, 60265-1, 60694, 60298

Dimensions
Height 1660mm 1429mm
Width 1000mm 650mm
Depth 940mm

Lucy Switchgear worldwide offices

Lucy Middle East FZE Lucy Switchgear Arabia Co. Ltd. Lucy Asia Pacific Sdn Bhd
PO Box 17335, Jebel Ali, Dubai, Novotel Business Centre, L13A-03-03A, PJX-HM Shah Tower,
United Arab Emirates P.O. Box 35340, Dammam 31488, No16A Jalan Persiaran Barat,
Tel: +97 148 129 999 Saudi Arabia 46050 Petaling Jaya, Selangor, Malaysia
Fax: +97 148 129 900 Tel: +966 3 8147 910 Tel: +603 74910700
Email: salesme@lucyswitchgear.com Fax: +966 3 8147 914 Fax: +603 79316923
Email: salessa@lucyswitchgear.com Email: salesmy@lucyswitchgear.com
Lucy Switchgear Ltd.
Howland Road, Thame, Oxfordshire, Lucy Switchgear (South Africa) Lucy Electric (Beijing) Co. Ltd.
OX9 3UJ, United Kingdom Unit 2, Cranberry Industrial Park, Cranberry Street 卢西电器(北京)有限公司
Tel: +44 1844 267 267 General Laser Park, Honeydew, 2170, South Africa 北京市朝阳区东三环北路霞光里
Tel: +44 1844 267 222 Sales Tel: +27 11 025 7490 18号佳程广场A座1122室
Fax: +44 1844 267 223 Fax: +27 11 794 3277 邮编: 100027
Email: salesuk@lucyswitchgear.com Email: salesza@lucyswitchgear.com 电话: +86 1059 231 176
传真: +86 1059 231 177
Postal Address:
电子邮件: salescn@lucyswitchgear.com
P.O. Box 1078, Honeydew, 2040

To find our more about us, visit: