3.3 KV, 550 KVA STATIONERY DIESEL ENGINE DRIVEN GENERATOR SET
SCOPE:
These Technical Specifications cover the equipment and materials for the DG Sets, their
testing and inspection, delivery at site, all preparatory works, assembling, installation and
adjustments, commissioning, final testing, putting into operation and handing over of the complete
system along with required permissions and AMC for 2 years after warranty. Tenderer may visit SCCL
site before submitting their tender.
The engine shall be of standard design of the original manufacturers, operating with High
Speed diesel oil corresponding to IS-1460-1995 up to latest amendment. It should be 4
stroke cycles, 12 Cylinder, water cooled, naturally aspirated/ turbo charged (as per IS standard),
developing suitable BHP for giving a power rating as per ISO 8528- Part-1 in KVA at the load
terminals of alternator at 1500 rpm at actual site conditions.
The engine shall be capable for delivering specified Prime Power rating at variable loads for
PF of 0.8 lag with 10% overload available in excess of specified output for one hour in every 12 hours.
The average load factor of the engine over period of 24 hours shall be 0.85 (85%) for prime power
output.
The engine shall conform to IS:10000/ ISO 3046/ BS:649/ BS 5514 amended up to date.
The engine shall be fitted with following accessories subject to the design of the
Manufacturer and as per IS standards (delete whichever is not applicable) :
It shall be fed through engine driven fuel pump. A replaceable element of fuel filter shall be
suitably located to permit easy servicing. The daily service tank shall be complete with
necessary supports, gauges, connecting pipe work etc. Pipe sealant should be used for
sealing for all connections.
Exhaust System:
Exhaust Piping: All M.S. Pipes for exhaust lines shall be conforming to relevant IS.
(a) Exhaust gas piping as per site requirement with silencer (in IS 2002, 6mm thick), running
from the exhaust manifold shall be provided with required number of Bends, Flanges, Elbows,
rain protection hoods and MS angle supports etc. and shall be insulated with Resin bonded
mineral wool / fibre glass and 22 SWG Al sheet Cladding and Exhaust Chimney.
Cooling System:
System should be designed for ambient temperature of 50 Deg.C.
Coolant should be used mixed with additive (in suitable proportion) as per
Manufacturer recommendation . Radiator fan flow should be free from any obstruction.
-3-
2. ALTERNATOR:
Synchronous Alternator
Self excited, screen protected, self regulated, brush less alternator, Horizontal foot
mounted in Double bearing construction suitable for the following:
Type of Bearing and lubrication arrangement: Anti friction bearings with Permanently
Lubricated Sealed Type
Standard : IS 4722 & IEC:34 as amended upto date.
Alternator should be able to deliver output rating at actual site conditions.
Standards
The alternator shall be in accordance with the following standards as are applicable.
Performance:
Voltage dip shall not exceed 20% of the rated voltage for any step load or transient
load as per ISO 8528 (Part-1).
The generator shall preferably be capable of withstanding a current equal to 1.5 times
the rated current for a period of not more than 15 seconds as required vide clause
14.1.1 of IS 4722:1992.
3. SWITCHGEAR:
3 pole, 3.3 KV, 400 Amps, 500 MVA, 25 kA, Electrically operated Draw-out type Sheet Steel
enclosure Vacuum Circuit Breaker with Under Voltage, over-current and short circuit release,
240 volts AC motor, Closing Coil, 24 V DC Shunt Trip Coil with 4 NO + 4 NC Auxiliary contacts
with in-built surge suppressors, for DG incoming side, provided with earth leakage relay (to limit
and trip at a fault current of 50 amps, Mechanical ON/OFF, push buttons and GENSET
ON,/OFF, TRIP on Fault Indication Lamp, TRIP CIRCUIT HEAALTHY - Test Button and
indication lamp and RYB indication lamp on the front of the panel.
The circuit breaker shall have distinct positions for 'Connect', 'Disconnect' and 'Test' and all
safety features and interlocks to protect the user from Electric Shock and one mechanical
EMERGENCY TRIP switch.
4. CONTROL PANEL
Electronic Modular Panel - Floor mounted using environmentally sealed, solid state
microprocessor based module for engine control and AC metering in 14 SWG (min) CRCA
sheet steel enclosure with IP 52 protection or latest.
The control panel shall be built to have the following provisions and features;
a) Trip / stop LED Indicators for Low Oil Pressure, High Water Temperature, over current,
under Voltage, over Voltage, and emergency stop.
b) Energized to run or shutdown fuel control systems.
c) Back lit Display LCD digital readout for Engine oil pressure, engine rpm, system DC
volts, Engine running hours, generator AC volts, generator AC amps, and generator
frequency, System diagnostic codes.
d) Digital Ammeter, Voltmeter, Kilowatt-hour meter, Power Factor meter of suitable rating.
e) Ammeter – Voltmeter phase selector switch.
f) Emergency - stop push button
g) Indicator / display test switch
h) Voltage adjust potentiometer
i) Four spare inputs for use by the user
j) Speed adjust potentiometer or any latest
k) Electronic Protection relay unit with programmable trip level setting to safe guard
against -
Over-voltage
Under - Voltage
Over - frequency
Under – frequency
-5-
Over current
Reverse Power
Battery Over-Voltage
Battery Under-Voltage
The above functions may be achieved in a single unit or multiple units as per design.
l) Earth fault relay for tripping duly limiting the fault current to 50 amps as per CEA -2010
or latest
m) Alarm module for all faults
n) Synchronizing panel
o) Digital Tachometer, Hour meter
p) Battery charge condition indicator
q) 230V LED lights inside the panel for panel illumination with suitable controls.
r) Door interlock switch for preventing opening of the doors of power module and control
panel while power on.
s) Controls, Indications and Push Buttons for
i. Breaker ON Indication
ii. Breaker OFF Indication
iii. Engine START Push Button
iv. Engine STOP push Button
v. Fault Accept / Reset Push Button
vi. Speed Raise / Lower Switch.
The MTS shall comply with IEC or equivalent international standard. The separately mounted
generator control cubicle and MTS panel shall be of sheet steel vermin proof with lockable
hinged front doors.
A circuit breaker and Manual transfer switch should be provided rated for full load of the
current (+ 10% overload).
The alternator and control panel shall be provided with suitable cable entry boxes ( as per
SCCL Drawing enclosed) for terminating 3 cores, PVC Double Wired armored cables
Alternator terminal box to suit trench / duct layout.
7. STARTING SYSTEM
2. Batteries and battery charger: A set of maintenance free 24 Volts Lead Acid Batteries
for smooth starting of the Genset. Static Battery charger with Trickle / boost mode, auto
/ manual selector switch with DC ammeter and DC voltmeter shall be part of the
system.
-6-
8. BASE FRAME
The mounting base frame for the generator set shall be of sturdy fabricated welded
construction with adequate size MS channel.
9. Common Bed Plate: Engine and alternator shall be directly coupled by means of
flexible coupling as per manufacturer standard design and both units shall be mounted
on a common bed plate together with all auxiliaries to ensure perfect alignment of
engine and alternator with minimum vibrations. The bed plate shall be suitable for
installation on suitable anti-vibration mounting system.
10. PAINTING
The surface of the generator set and all other sub-assemblies / Metallic parts shall be
painted with Epoxy based paint of sufficient thickness for protection against corrosion
after 7 tank pre-treatment.
Diesel generators housing shall have fire detection system suitable for use in an area
containing diesel fuel. The fire detection system shall cut off the fuel supply from the
tank in the event of a fire. The fire detection system shall operate an alarm system. The
system shall meet the requirements of fire regulations.
The design, construction and operation of the Genset and components shall conform to
/ exceed relevant National and International standards.
a) All power cables with copper conductor between DG and panel and all control cables-30 Mts.
Minimum, 40 X 6 mm Copper and 40 X 6 mm GI strips for earthing purpose of about 40 Mts
each shall form part of the supply for each DG set.
b) All piping / Hoses between the fuel tank and the DG set. Shall be supplied with each DG set.
c) Hand operated fuel barrel pump shall be part of supply of each DG set.
d) Set of tools with tool box suitable for normal maintenance and repair work for each DG set shall
be part of the supply.
e) Anti vibration Mounts shall be provided for each DG set as part of the supply..
1. Air circuit breakers, contactors, energy meters , panel meters, Selector switches, protective
relays, auxiliary relays, power fuses (DIN type), control fuses with bases BS type, push buttons,
Indicator lamps (LED cluster type) : L&T / SEIMENS / C&S, ASHIDA/ GE/MIMEC, BCH/LG/
ABB/ MECO.
7. Batteries EXIDE/AMARON/HITACHI/BOSCH/HBL
15. DOCUMENTATION
The suppliers have to submit all statutory approvals like NOC from Pollution Control Board,
Approval of Chief Electrical Inspector to Govt. AP for Installation drawings and Installation work
from electricity Board etc. with each DG set.
General arrangement drawings of control panel, battery charger along with foundation plans,
overall dimensions, front view etc. Fuel tank drawing with mounting arrangement.
Schematic wiring diagram for the control panel, battery charger along with the complete bill of
materials (makes, rating, range, size, accuracy class etc. and control cable details.
The supplier has to depute their Technical representatives for Installation and commissioning of
the DG sets.
17. WARRANTY
The Generator sets and all the accessories shall be guaranteed for a period of 24 months from
the date of commissioning.
The supplier give two weeks advance intimation to enable the SCCL to depute representative
for witnessing the acceptance and routine tests.
The tender shall include terms and conditions for Annual Maintenance Contract for a period of
2 years commencing immediately after the initial Warranty Period of 24 months. Tenderer
shall quote separately for CMC charges value of which will be considered for evaluation.
L1 status for each generator set shall be attained by taking combined value of price of
each generator and its CMC.
-8-
SCOPE OF AMC:
a. Firm’s Service Engineer will make 12 visits in a year at site at intervals each not exceeding 40
days.
b. During service visit the service engineer will inspect the DG set and carry out various checks
and adjustments.
c. During CMC all parts except engine oil and diesel will be in the firm’s scope.
d. All necessary skilled and un-skilled Labour, Tools, Stores, Lifting and Moving facility for
completion of the job will be provided by SCCL
e. In addition to carrying out normal checking, adjustment and minor repairs, firm’s service
engineer should acquaint SCCL technical staff, responsible for the normal operation and
maintenance of the engine, with Dos and Don’ts of correct operation and maintenance and the
watch points for trouble-shooting.
f. Services offered under this contract will be in accordance with the Original manufacturer’s
standard service instruction practice to maintain the DG Set in healthy operating condition.
h. All visits should be acknowledged by signing the service report on the same day.
i. Payment terms: CMC payment will be done monthly on satisfactory service letter
b) List of previous supplies executed and performance reports from actual users.
GM(E&M) WSs&EM
ANNEXURE -I
Schedule of Technical particulars to be submitted by Tenderer
I. Engine
1. Make
2. Model/ISS reference
3. No. of cylinders
4. Rated R.P.M.
5. Method of Starting
6. Aspiration Method
7. BHP
8. Lub. Oil recommended
II. Alternator
1. Make
2. Enclosure Details
3. Full Load output in KVA
4. Full Load output in KW at 0.8 PF
1. Make
Signature of Tenderer
SPECIFICATIONS FOR
3.3 KV, 750 KVA STATIONERY DIESEL ENGINE DRIVEN GENERATOR SET
SCOPE:
These Technical Specifications cover the equipment and materials for the DG Sets, their
testing and inspection, delivery at site, all preparatory works, assembling, installation and
adjustments, commissioning, final testing, putting into operation and handing over of the complete
system along with required permissions and AMC for 2 years after warranty. Tenderer may visit SCCL
site before submitting their tender.
The engine shall be of standard design of the original manufacturers, operating with High
Speed diesel oil corresponding to IS-1460-1995 up to latest amendment. It should be 4
stroke cycles, 12 Cylinder, water cooled, naturally aspirated/ turbo charged (as per IS standard),
developing suitable BHP for giving a power rating as per ISO 8528- Part-1 in KVA at the load
terminals of alternator at 1500 rpm at actual site conditions.
The engine shall be capable for delivering specified Prime Power rating at variable loads for
PF of 0.8 lag with 10% overload available in excess of specified output for one hour in every 12 hours.
The average load factor of the engine over period of 24 hours shall be 0.85 (85%) for prime power
output.
The engine shall conform to IS:10000/ ISO 3046/ BS:649/ BS 5514 amended up to date.
The engine shall be fitted with following accessories subject to the design of the
Manufacturer and as per IS standards (delete whichever is not applicable) :
It shall be fed through engine driven fuel pump. A replaceable element of fuel filter shall be
suitably located to permit easy servicing. The daily service tank shall be complete with
necessary supports, gauges, connecting pipe work etc. Pipe sealant should be used for
sealing for all connections.
Exhaust System:
Exhaust Piping: All M.S. Pipes for exhaust lines shall be conforming to relevant IS.
(a) Exhaust gas piping as per site requirement with silencer (in IS 2002, 6mm thick), running
from the exhaust manifold shall be provided with required number of Bends, Flanges, Elbows,
rain protection hoods and MS angle supports etc. and shall be insulated with Resin bonded
mineral wool / fibre glass and 22 SWG Al sheet Cladding and Exhaust Chimney.
Cooling System:
System should be designed for ambient temperature of 50 Deg.C.
Coolant should be used mixed with additive (in suitable proportion) as per
Manufacturer recommendation . Radiator fan flow should be free from any obstruction.
-3-
2. ALTERNATOR:
Synchronous Alternator
Self excited, screen protected, self regulated, brush less alternator, Horizontal foot
mounted in Double bearing construction suitable for the following:
Type of Bearing and lubrication arrangement: Anti friction bearings with Permanently
Lubricated Sealed Type
Standard : IS 4722 & IEC:34 as amended upto date.
Alternator should be able to deliver output rating at actual site conditions.
Standards
The alternator shall be in accordance with the following standards as are applicable.
Performance:
Voltage dip shall not exceed 20% of the rated voltage for any step load or transient
load as per ISO 8528 (Part-1).
The generator shall preferably be capable of withstanding a current equal to 1.5 times
the rated current for a period of not more than 15 seconds as required vide clause
14.1.1 of IS 4722:1992.
3. SWITCHGEAR:
3 pole, 3.3 KV, 400 Amps, 500 MVA, 25 kA, Electrically operated Draw-out type Sheet Steel
enclosure Vacuum Circuit Breaker with Under Voltage, over-current and short circuit release,
240 volts AC motor, Closing Coil, 24 V DC Shunt Trip Coil with 4 NO + 4 NC Auxiliary contacts
with in-built surge suppressors, for DG incoming side, provided with earth leakage relay (to limit
and trip at a fault current of 50 amps, Mechanical ON/OFF, push buttons and GENSET
ON,/OFF, TRIP on Fault Indication Lamp, TRIP CIRCUIT HEAALTHY - Test Button and
indication lamp and RYB indication lamp on the front of the panel.
The circuit breaker shall have distinct positions for 'Connect', 'Disconnect' and 'Test' and all
safety features and interlocks to protect the user from Electric Shock and one mechanical
EMERGENCY TRIP switch.
One Neutral Grounding resistor designed and rated to restrict the Fault current to 50
Amps shall be provided. The NGR shall be housed in a cubicle and will be Stainless
Steel or Cu-Ni alloy. The rating of the NGR shall be for 10 seconds duty with
temperature rise limitation of 3750 C.
4. CONTROL PANEL
Electronic Modular Panel - Floor mounted using environmentally sealed, solid state
microprocessor based module for engine control and AC metering in 14 SWG (min) CRCA
sheet steel enclosure with IP 52 protection or latest.
The control panel shall be built to have the following provisions and features;
t) Trip / stop LED Indicators for Low Oil Pressure, High Water Temperature, over current,
under Voltage, over Voltage, and emergency stop.
u) Energized to run or shutdown fuel control systems.
v) Back lit Display LCD digital readout for Engine oil pressure, engine rpm, system DC
volts, Engine running hours, generator AC volts, generator AC amps, and generator
frequency, System diagnostic codes.
w) Digital Ammeter, Voltmeter, Kilowatt-hour meter, Power Factor meter of suitable rating.
x) Ammeter – Voltmeter phase selector switch.
y) Emergency - stop push button
z) Indicator / display test switch
aa) Voltage adjust potentiometer
bb) Four spare inputs for use by the user
cc) Speed adjust potentiometer or any latest
-5-
dd) Electronic Protection relay unit with programmable trip level setting to safe guard
against -
Over-voltage
Under - Voltage
Over - frequency
Under – frequency
Over current
Reverse Power
Battery Over-Voltage
Battery Under-Voltage
The above functions may be achieved in a single unit or multiple units as per design.
ee) Earth fault relay for tripping duly limiting the fault current to 50 amps as per CEA -2010
or latest
ff) Alarm module for all faults
gg) Synchronizing panel
hh) Digital Tachometer, Hour meter
ii) Battery charge condition indicator
jj) 230V LED lights inside the panel for panel illumination with suitable controls.
kk) Door interlock switch for preventing opening of the doors of power module and control
panel while power on.
ll) Controls, Indications and Push Buttons for
j. Breaker ON Indication
vii. Breaker OFF Indication
viii. Engine START Push Button
ix. Engine STOP push Button
x. Fault Accept / Reset Push Button
xi. Speed Raise / Lower Switch.
The MTS shall comply with IEC or equivalent international standard. The separately mounted
generator control cubicle and MTS panel shall be of sheet steel vermin proof with lockable
hinged front doors.
A circuit breaker and Manual transfer switch should be provided rated for full load of the
current (+ 10% overload).
The alternator and control panel shall be provided with suitable cable entry boxes ( as per
SCCL Drawing enclosed) for terminating 3 cores, PVC Double Wired armored cables
Alternator terminal box to suit trench / duct layout.
7. STARTING SYSTEM
3. Batteries and battery charger: A set of maintenance free 24 Volts Lead Acid Batteries
for smooth starting of the Genset. Static Battery charger with Trickle / boost mode, auto
/ manual selector switch with DC ammeter and DC voltmeter shall be part of the
system.
-6-
8. BASE FRAME
The mounting base frame for the generator set shall be of sturdy fabricated welded
construction with adequate size MS channel.
9. Common Bed Plate: Engine and alternator shall be directly coupled by means of
flexible coupling as per manufacturer standard design and both units shall be mounted
on a common bed plate together with all auxiliaries to ensure perfect alignment of
engine and alternator with minimum vibrations. The bed plate shall be suitable for
installation on suitable anti-vibration mounting system.
10. PAINTING
The surface of the generator set and all other sub-assemblies / Metallic parts shall be
painted with Epoxy based paint of sufficient thickness for protection against corrosion
after 7 tank pre-treatment.
Diesel generators housing shall have fire detection system suitable for use in an area
containing diesel fuel. The fire detection system shall cut off the fuel supply from the
tank in the event of a fire. The fire detection system shall operate an alarm system. The
system shall meet the requirements of fire regulations.
The design, construction and operation of the Genset and components shall conform to
/ exceed relevant National and International standards.
f) All power cables with copper conductor between DG and panel and all control cables-30 Mts.
Minimum, 40 X 6 mm Copper and 40 X 6 mm GI strips for earthing purpose of about 40 Mts
each shall form part of the supply for each DG set.
g) All piping / Hoses between the fuel tank and the DG set. Shall be supplied with each DG set.
h) Hand operated fuel barrel pump shall be part of supply of each DG set.
i) Set of tools with tool box suitable for normal maintenance and repair work for each DG set shall
be part of the supply.
j) Anti vibration Mounts shall be provided for each DG set as part of the supply..
4. Air circuit breakers, contactors, energy meters , panel meters, Selector switches, protective
relays, auxiliary relays, power fuses (DIN type), control fuses with bases BS type, push buttons,
Indicator lamps (LED cluster type) : L&T / SEIMENS / C&S, ASHIDA/ GE/MIMEC, BCH/LG/
ABB/ MECO.
7. Batteries EXIDE/AMARON/HITACHI/BOSCH/HBL
15. DOCUMENTATION
The suppliers have to submit all statutory approvals like NOC from Pollution Control Board,
Approval of Chief Electrical Inspector to Govt. AP for Installation drawings and Installation work
from electricity Board etc. with each DG set.
General arrangement drawings of control panel, battery charger along with foundation plans,
overall dimensions, front view etc. Fuel tank drawing with mounting arrangement.
Schematic wiring diagram for the control panel, battery charger along with the complete bill of
materials (makes, rating, range, size, accuracy class etc. and control cable details.
The supplier has to depute their Technical representatives for Installation and commissioning of
the DG sets.
17. WARRANTY
The Generator sets and all the accessories shall be guaranteed for a period of 24 months from
the date of commissioning.
The supplier give two weeks advance intimation to enable the SCCL to depute representative
for witnessing the acceptance and routine tests.
The tender shall include terms and conditions for Annual Maintenance Contract for a period of
2 years commencing immediately after the initial Warranty Period of 24 months. Tenderer
shall quote separately for CMC charges value of which will be considered for evaluation.
L1 status for each generator set shall be attained by taking combined value of price of
each generator and its CMC.
-8-
SCOPE OF AMC:
i. Firm’s Service Engineer will make 12 visits in a year at site at intervals each not exceeding 40
days.
j. During service visit the service engineer will inspect the DG set and carry out various checks
and adjustments.
k. During CMC all parts except engine oil and diesel will be in the firm’s scope.
l. All necessary skilled and un-skilled Labour, Tools, Stores, Lifting and Moving facility for
completion of the job will be provided by SCCL
m. In addition to carrying out normal checking, adjustment and minor repairs, firm’s service
engineer should acquaint SCCL technical staff, responsible for the normal operation and
maintenance of the engine, with Dos and Don’ts of correct operation and maintenance and the
watch points for trouble-shooting.
n. Services offered under this contract will be in accordance with the Original manufacturer’s
standard service instruction practice to maintain the DG Set in healthy operating condition.
p. All visits should be acknowledged by signing the service report on the same day.
i. Payment terms: CMC payment will be done monthly on satisfactory service letter
f) List of previous supplies executed and performance reports from actual users.
GM(E&M) WSs&EM
ANNEXURE -I
Schedule of Technical particulars to be submitted by Tenderer
I. Engine
1. Make
2. Model/ISS reference
3. No. of cylinders
4. Rated R.P.M.
5. Method of Starting
6. Aspiration Method
7. BHP
8. Lub. Oil recommended
9. Lub. Oil pressure
10. Qty. of lub. oil required
11. Time required for starting
II. Alternator
1. Make
2. Enclosure Details
3. Full Load output in KVA
2. Type
1. Make
Signature of Tenderer
SPECIFICATIONS FOR
550V, 750 KVA STATIONERY DIESEL ENGINE DRIVEN GENERATOR SET
SCOPE:
These Technical Specifications cover the equipment and materials for the DG Sets, their
testing and inspection, delivery at site, all preparatory works, assembling, installation and
adjustments, commissioning, final testing, putting into operation and handing over of the complete
system along with required permissions and AMC for 2 years after warranty. Tenderer may visit SCCL
site before submitting their tender.
The engine shall be of standard design of the original manufacturers, operating with High
Speed diesel oil corresponding to IS-1460-1995 up to latest amendment. It should be 4
stroke cycles, 12 Cylinder, water cooled, naturally aspirated/ turbo charged (as per IS standard),
developing suitable BHP for giving a power rating as per ISO 8528- Part-1 in KVA at the load
terminals of alternator at 1500 rpm at actual site conditions.
The engine shall be capable for delivering specified Prime Power rating at variable loads for
PF of 0.8 lag with 10% overload available in excess of specified output for one hour in every 12 hours.
The average load factor of the engine over period of 24 hours shall be 0.85 (85%) for prime power
output.
The engine shall conform to IS:10000/ ISO 3046/ BS:649/ BS 5514 amended up to date.
The engine shall be fitted with following accessories subject to the design of the
Manufacturer and as per IS standards (delete whichever is not applicable) :
It shall be fed through engine driven fuel pump. A replaceable element of fuel filter shall be
suitably located to permit easy servicing. The daily service tank shall be complete with
necessary supports, gauges, connecting pipe work etc. Pipe sealant should be used for
sealing for all connections.
Exhaust System:
Exhaust Piping: All M.S. Pipes for exhaust lines shall be conforming to relevant IS.
(a) Exhaust gas piping as per site requirement with silencer (in IS 2002, 6mm thick), running
from the exhaust manifold shall be provided with required number of Bends, Flanges, Elbows,
rain protection hoods and MS angle supports etc. and shall be insulated with Resin bonded
mineral wool / fibre glass and 22 SWG Al sheet Cladding and Exhaust Chimney.
Cooling System:
System should be designed for ambient temperature of 50 Deg.C.
Coolant should be used mixed with additive (in suitable proportion) as per
Manufacturer recommendation . Radiator fan flow should be free from any obstruction.
-3-
2. ALTERNATOR:
Synchronous Alternator
Self excited, screen protected, self regulated, brush less alternator, Horizontal foot
mounted in Double bearing construction suitable for the following:
Type of Bearing and lubrication arrangement: Anti friction bearings with Permanently
Lubricated Sealed Type
Standard : IS 4722 & IEC:34 as amended upto date.
Alternator should be able to deliver output rating at actual site conditions.
Standards
The alternator shall be in accordance with the following standards as are applicable.
Performance:
Voltage dip shall not exceed 20% of the rated voltage for any step load or transient
load as per ISO 8528 (Part-1).
The generator shall preferably be capable of withstanding a current equal to 1.5
times the rated current for a period of not more than 15 seconds as required vide
clause 14.1.1 of IS 4722:1992.
3. SWITCHGEAR:
Power Module:
4 Pole, 1250Amps, Electrically operated Draw-out type Air Circuit Breaker with
over-current and short circuit release, 240 Volts AC Motor, UV Coil, 24 V DC
Shunt Trip Coil with 4 NO+ 4NC Auxiliary Contacts for DG Incoming side,
provided with earth leakage relay (to limit and trip at a fault current of 750
milliamps), GENSET ON, LOAD ON, TRIP Indication Lamp, TRIP CIRCUIT
HEALTHY -Test Button and indication Lamp and RYB indication Lamp on the
front of the panel.
The circuit breaker shall have distinct positions for 'Connect', 'Disconnect' and 'Test' and all
safety features and interlocks to protect the user from Electric Shock and one mechanical
EMERGENCY TRIP switch.
4. CONTROL PANEL
Electronic Modular Panel - Floor mounted using environmentally sealed, solid state
microprocessor based module for engine control and AC metering in 14 SWG (min) CRCA
sheet steel enclosure with IP 52 protection or latest.
The control panel shall be built to have the following provisions and features;
mm) Trip / stop LED Indicators for Low Oil Pressure, High Water Temperature, over
current, under Voltage, over Voltage, and emergency stop.
nn) Energized to run or shutdown fuel control systems.
oo) Back lit Display LCD digital readout for Engine oil pressure, engine rpm, system DC
volts, Engine running hours, generator AC volts, generator AC amps, and generator
frequency, System diagnostic codes.
pp) Digital Ammeter, Voltmeter, Kilowatt-hour meter, Power Factor meter of suitable
rating.
qq) Ammeter – Voltmeter phase selector switch.
rr) Emergency - stop push button
ss) Indicator / display test switch
tt) Voltage adjust potentiometer
uu) Four spare inputs for use by the user
vv) Speed adjust potentiometer or any latest
ww) Electronic Protection relay unit with programmable trip level setting to safe guard
against -
Over-voltage
Under - Voltage
Over - frequency
Under – frequency
-5-
Over current
Reverse Power
Battery Over-Voltage
Battery Under-Voltage
The above functions may be achieved in a single unit or multiple units as per
design.
xx) Earth fault relay for tripping duly limiting the fault current to 50 amps as per CEA -
2010 or latest
yy) Alarm module for all faults
zz) Synchronizing panel
aaa) Digital Tachometer, Hour meter
bbb) Battery charge condition indicator
ccc) 230V LED lights inside the panel for panel illumination with suitable controls.
ddd) Door interlock switch for preventing opening of the doors of power module and
control panel while power on.
eee) Controls, Indications and Push Buttons for
k. Breaker ON Indication
xii. Breaker OFF Indication
xiii. Engine START Push Button
xiv. Engine STOP push Button
xv. Fault Accept / Reset Push Button
xvi. Speed Raise / Lower Switch.
The MTS shall comply with IEC or equivalent international standard. The separately
mounted generator control cubicle and MTS panel shall be of sheet steel vermin proof with
lockable hinged front doors.
A circuit breaker and Manual transfer switch should be provided rated for full load of the
current (+ 10% overload).
The alternator and control panel shall be provided with suitable cable entry boxes ( as per
SCCL Drawing enclosed) for terminating 3 cores, PVC Double Wired armored cables
Alternator terminal box to suit trench / duct layout.
7. STARTING SYSTEM
4. Batteries and battery charger: A set of maintenance free 24 Volts Lead Acid
Batteries for smooth starting of the Genset. Static Battery charger with Trickle /
boost mode, auto / manual selector switch with DC ammeter and DC voltmeter
shall be part of the system.
-6-
8. BASE FRAME
The mounting base frame for the generator set shall be of sturdy fabricated welded
construction with adequate size MS channel.
9. Common Bed Plate: Engine and alternator shall be directly coupled by means of
flexible coupling as per manufacturer standard design and both units shall be
mounted on a common bed plate together with all auxiliaries to ensure perfect
alignment of engine and alternator with minimum vibrations. The bed plate shall be
suitable for installation on suitable anti-vibration mounting system.
10. PAINTING
The surface of the generator set and all other sub-assemblies / Metallic parts shall
be painted with Epoxy based paint of sufficient thickness for protection against
corrosion after 7 tank pre-treatment.
Diesel generators housing shall have fire detection system suitable for use in an
area containing diesel fuel. The fire detection system shall cut off the fuel supply
from the tank in the event of a fire. The fire detection system shall operate an alarm
system. The system shall meet the requirements of fire regulations.
The design, construction and operation of the Genset and components shall
conform to / exceed relevant National and International standards.
k) All power cables with copper conductor between DG and panel and all control cables-30
Mts. Minimum, 40 X 6 mm Copper and 40 X 6 mm GI strips for earthing purpose of about
40 Mts each shall form part of the supply for each DG set.
l) All piping / Hoses between the fuel tank and the DG set. Shall be supplied with each DG
set.
m) Hand operated fuel barrel pump shall be part of supply of each DG set.
n) Set of tools with tool box suitable for normal maintenance and repair work for each DG set
shall be part of the supply.
o) Anti vibration Mounts shall be provided for each DG set as part of the supply..
7. Air circuit breakers, contactors, energy meters , panel meters, Selector switches, protective
relays, auxiliary relays, power fuses (DIN type), control fuses with bases BS type, push
buttons, Indicator lamps (LED cluster type) : L&T / SEIMENS / C&S, ASHIDA/
GE/MIMEC, BCH/LG/ ABB/ MECO.
7. Batteries EXIDE/AMARON/HITACHI/BOSCH/HBL
15. DOCUMENTATION
The suppliers have to submit all statutory approvals like NOC from Pollution Control Board,
Approval of Chief Electrical Inspector to Govt. AP for Installation drawings and Installation
work from electricity Board etc. with each DG set.
General arrangement drawings of control panel, battery charger along with foundation
plans, overall dimensions, front view etc. Fuel tank drawing with mounting arrangement.
Schematic wiring diagram for the control panel, battery charger along with the complete bill
of materials (makes, rating, range, size, accuracy class etc. and control cable details.
The supplier has to depute their Technical representatives for Installation and
commissioning of the DG sets.
17. WARRANTY
The Generator sets and all the accessories shall be guaranteed for a period of 24 months
from the date of commissioning.
The supplier give two weeks advance intimation to enable the SCCL to depute
representative for witnessing the acceptance and routine tests.
The tender shall include terms and conditions for Annual Maintenance Contract for a
period of 2 years commencing immediately after the initial Warranty Period of 24 months.
Tenderer shall quote separately for CMC charges value of which will be considered
for evaluation. L1 status for each generator set shall be attained by taking combined
value of price of each generator and its CMC.
-8-
SCOPE OF AMC:
q. Firm’s Service Engineer will make 12 visits in a year at site at intervals each not exceeding
40 days.
r. During service visit the service engineer will inspect the DG set and carry out various
checks and adjustments.
s. During CMC all parts except engine oil and diesel will be in the firm’s scope.
t. All necessary skilled and un-skilled Labour, Tools, Stores, Lifting and Moving facility for
completion of the job will be provided by SCCL
u. In addition to carrying out normal checking, adjustment and minor repairs, firm’s service
engineer should acquaint SCCL technical staff, responsible for the normal operation and
maintenance of the engine, with Dos and Don’ts of correct operation and maintenance and
the watch points for trouble-shooting.
v. Services offered under this contract will be in accordance with the Original manufacturer’s
standard service instruction practice to maintain the DG Set in healthy operating condition.
x. All visits should be acknowledged by signing the service report on the same day.
i. Payment terms: CMC payment will be done monthly on satisfactory service letter
j) List of previous supplies executed and performance reports from actual users.
2. Model/ISS reference
3. No. of cylinders
4. Rated R.P.M.
5. Method of Starting
6. Aspiration Method
7. BHP
8. Lub. Oil recommended
II. Alternator
1. Make
2. Enclosure Details
3. Full Load output in KVA
4. Full Load output in KW at 0.8 PF
1. Make
2. Type
1. Make
Signature of Tenderer