SENGKANG GTCC-BLOCK 1

DATA SHEET FOR UNINTERRUPTIBLE POWER


SUPPLIES (UPS)

DATA SHEET FOR UNINTERRUPTIBLE POWER SUPPLIES


(UPS)
SENGKANG GTCC-BLOCK 1

A01 Issued For Review Dhanar DK 25-Nov-2020 Koko Y 25-Nov-2020 Fifin Arifin
Rev Reason for Issue Author Date Checked Date Approved Date

STATUS CODE: A: Issued For Review


B: Issued For Approval
C: Approved
D: As Built

DISTRIBUTION:
DC : Original
All Engineer : Controlled Copy
QS : Controlled Copy

! This document is copyright and Document Number


shall not be reproduced without the
permission of PT. Energi Sengkang
SKPP-E-DS-UPS-2021-01
Sengkang Combined Cycle Power Plant Block #1, Patila - Wajo
Data Sheet for Uninterruptible Power Supplies - Sengkang GTCC Block 1

Table of Contents
ATTACHMENT 1
125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 1 .................... 3

ATTACHMENT 2
125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 2 .................... 4

ATTACHMENT 3
24VDC UNINTERRUPTABLE POWER SUPPLIES (UPS) ......................................................... 5

SKPP-E-DS-UPS-2021-01 Page | 2
Sengkang Combined Cycle Power Plant Block #1, Patila - Wajo
Data Sheet for Uninterruptible Power Supplies - Sengkang GTCC Block 1

ATTACHMENT 1
125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 1

SKPP-E-DS-UPS-2021-01 Page | 3
DATA SHEET
125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 1

No. DESCRIPTION REQUIREMENT / SPEC VENDOR'S RESPONSE


1 GENERAL SPECIFICATION
STANDARD AND LABEL IEC
UPS STANDARD IEC 62040 (All part)
TEMPERATURE RANGE 0 …..+40OC (For Operation)
INSTALLATION ALTITUDE ≥ 1000 m ASL
RELIABILITY MTBF ≥ 185000 Hours
2 SYSTEM CONFIGURATION Redundant consist of 2X100% UPS BLOCK , consist of :
A. 2 X 100% Rectifier with isolation transformer min. 6 pulse; THDI ≤ 28%
B. 2 X 100% PWM Inverter with IGBT's
C. 1 unit of bypass transformer
D. 2 Unit of DC Distribution Board and 1 unit of AC Distribution Board
E. 2 unit of Outgoing to "existing Battery"
3 ELECTRIC SPECIFICATION
RECTIFIER (19BTL10 - 19BTM10)
Input - Voltage and Freq 3x400 VAC ± 15% , 50 Hz ± 5%
Input - Min. Power (Current) 68.4 KVA (160 Upstream protection)
Output - Voltage 125 VDC (Max. 144 VDC) ; Ripple voltage ≤ 2% rms with connected battery
Output - Total current 365 A
Output - Rated Icc 35 kA
BYPASS MAINS (19BRU30)
Input - Voltage and Freq 1x230 VAC ± 10% , 50 Hz ± 5% - 1 phase and 2 wires
Bypass nominal power 30 KVA
Upstream protection Fuse or MCCB (250A -35 kA)
INVERTER (19BRU10 - 19BRU20)
Input DC voltage 125 VDC (96 -157 VDC)
Output voltage 1x230 VAC ± 1% , 50 Hz ± 0.1%, 2 Wires
Output Rating 30 KVA ( 0.7 Ind… 0.9 Cap) -
Transient voltage recovery ≤ 25ms to ±1 %
Overload Capabilty 125% x I-output For 10 min; 150% x I-output For 1 min;
Short Circuit 200% x I-output For 100ms
Distortion Factor Total at linear load : < 4%, Individual Harmonics : < 3 % ; at non-linear load: < 8% OR (VTA)
INTERNAL WIRING Halogen-free, flame retardant and non toxic.
OVERALL EFFICIENCY > 80 %
SPACE HEATERS In UPS, incoming / Bypass panels
125 VDC DB (19BUA01, 19BUA02) (subject to existing)
Input 3P 250A, 2AX, NO, NC : 2 units
Output 2A,2P DC-MCB +PE : 3 Units 16A,2P DC-MCB +PE : 8 units
4A,2P DC-MCB +PE : 5 units 25A,2P DC-MCB +PE : 1 units
10A,2P DC-MCB +PE : 1 unit 80A,2P DC-MCB +PE : 1 units
230 VAC DB (19BRA10) (subject to existing)
Input Fuse 240V, 160A (outgoing Inverter) : 2units Fuse 660V, 350A (outgoing bypass) : 2 units
Output 2A, 2P MCB + PE : 8 units 6A, 2P MCB + PE : 1 unit
4A, 2P MCB + PE : 4 units 10A,2P MCB + PE : 3 units
4 OPERATING AND COMMUNICATION
RECTIFIER -PARAMETERS Float Charge : 133.8 V; Boost Charge: 144V Current Limitation Battery : VTA
Low Battery Voltage: Warning: 109 V ; Shutdown: 96 V
INVERTER- PARAMETERS DC Voltage High - Warning : 139V - Shutdown: 150V
Synchronization range: ± 0.5/1/2/4/6/8 %
Slewrate: 0.5/1/2/4/8 Hz/sec Setting : 4 Hz/sec
CONTROL AND MONITORING It's shall be based on Microprocessor controlled system logic with real time fault analysis
able recording and memorisation of the last events..
Having Battery management system (temperature sensor) and also able to test capacity of
Battries.
INDICATION Front-panel with mimic diagram and detailed LED Indication
EXTERNAL CONNECTION Yes, fail safe open/close contacts
(Common fault, and also individual alarm battery operation, external bypass contactor,
inhibition external bypass, etc,)
COMMUNICATION INTERFACE Yes, minimum MODBUS TCP (VTA)
5 MECHANICAL SPECIFICATION Free standing cabinet - Front door, side and rear removable
PROTECTION CLASS min. 30 (close door) ; IP 20 / NEMA 1 (Open door)
Bottom cable entry
VENTILATION Self-Contained blowers, air inlet in front below, outlet on the top
Notes
1. BATTERY (Existing) Lead Acid : FIAMM - TYPE SMBF9 (900 AH)
No's of Cells 60 pcs - Mounted on a steel rack.
Autonomy 120 Min at load 30 kva, 0.8 pf
SINGLE LINE DIAGRAM

GENERAL ARRANGEMENT
Sengkang Combined Cycle Power Plant Block #1, Patila - Wajo
Data Sheet for Uninterruptible Power Supplies - Sengkang GTCC Block 1

ATTACHMENT 2
125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 2

SKPP-E-DS-UPS-2021-01 Page | 4
DATA SHEET
125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 2

No. DESCRIPTION REQUIREMENT / SPEC VENDOR'S RESPONSE


1 GENERAL SPECIFICATION
STANDARD AND LABEL IEC
UPS STANDARD IEC 62040 (All part)
TEMPERATURE RANGE 0 …..+40OC (For Operation)
INSTALLATION ALTITUDE ≥ 1000 m ASL
RELIABILITY MTBF ≥ 185000 Hours
2 SYSTEM CONFIGURATION consist of :
A. 1 X 100% Rectifier with isolation transformer min. 6 pulse; THDI ≤ 28%
B. 1 X 100% PWM Inverter with IGBT's
C. 1 unit of Bypass transformer
D. 1 unit of AC Distribution Board
E. 1 unit of Outgoing to "existing Battery"
3 ELECTRIC SPECIFICATION
RECTIFIER (11BTL10)
Input - Voltage and Freq 3x400 VAC ± 15% , 50 Hz ± 5%
Input - Min. Power (Current) 27.2 KVA (63A upstream protection)
Output - Voltage 125 VDC (Max. 144 VDC) ; Ripple voltage ≤ 2% rms with connected battery
Output - Total current 145 A
Output - Rated Icc 35 kA
BYPASS MAINS (11BRA10)
Input - Voltage and Freq 1x230 VAC ± 10% , 50 Hz ± 5% - 1 phase and 2 wires
Bypass nominal power 5 KVA
Upstream protection Fuse or MCCB (40A -35 kA)
INVERTER (11BRU10)
Input DC voltage 125 VDC (96 -157 VDC)
Output voltage 1x230 VAC ± 1% , 50 Hz ± 0.1%, 2 Wires
Output Rating 5 KVA ( 0.7 Ind… 0.9 Cap) -
Transient voltage recovery ≤ 25ms to ±1 %
Overload Capabilty 125% x I-output For 10 min; 150% x I-output For 1 min;
Short Circuit 200% x I-output For 100ms
Distortion Factor Total at linear load : < 4%, Individual Harmonics : < 3 % ; at non-linear load: < 8% OR (VTA)
INTERNAL WIRING Halogen-free, flame retardant and non toxic.
OVERALL EFFICIENCY >75 %
SPACE HEATERS In UPS, incoming / Bypass panels
230 VAC DB (11BRA10) (subject to existing)
Input Fuse 240V, 63A (F021, At outgoing Inverter) Fuse 660V, 350A (F028, At outgoing bypass)
Output 2A, 2P MCB + PE : 3 Units 6A, 2P MCB + PE : 9 Units
4A, 2P MCB + PE : 1 Unit (For metering)
4 OPERATING AND COMMUNICATION
RECTIFIER -PARAMETERS Float Charge : 133.8 V; Boost Charge: 135V Current Limitation Battery : VTA
Low Battery Voltage: Warning: 109 V ; Shutdown: 96 V
INVERTER- PARAMETERS DC Voltage High - Warning : 139V - Shutdown: 150V
Synchronization range: ± 0.5/1/2/4/6/8 %
Slewrate: 0.5/1/2/4/8 Hz/sec Setting : 4 Hz/sec
CONTROL AND MONITORING It's shall be based on Microprocessor controlled system logic with real time fault analysis
able recording and memorisation of the last events..
Having Battery management system (temperature sensor) and also able to test capacity of
Battries.
INDICATION Front-panel with mimic diagram and detailed LED Indication
EXTERNAL CONNECTION Yes, fail safe open/close contacts
(Common fault, and also individual alarm battery operation, external bypass contactor,
inhibition external bypass, etc,)
COMMUNICATION INTERFACE Yes, minimum MODBUS TCP (VTA)

5 MECHANICAL SPECIFICATION Free standing cabinet - Front door, side and rear removable
PROTECTION CLASS min. 30 (close door) ; IP 20 / NEMA 1 (Open door)
Bottom cable entry
VENTILATION Self-Contained blowers, air inlet in front below, outlet on the top
Notes
1. BATTERY (Existing) Lead Acid : FIAMM - TYPE 2 // 6PMF300 (600 AH)
No's of Cells 60 pcs - Mounted on a steel rack.
Autonomy 360 Min at load 3 kva, 0.8 pf
SINGLE LINE DIAGRAM

GENERAL ARRANGEMENT

Notes:
Existing dimension is about 800 x 2200 x 600 mm,; Vendor to consider the available space
Sengkang Combined Cycle Power Plant Block #1, Patila - Wajo
Data Sheet for Uninterruptible Power Supplies - Sengkang GTCC Block 1

ATTACHMENT 3
24VDC UNINTERRUPTABLE POWER SUPPLIES (UPS)

SKPP-E-DS-UPS-2021-01 Page | 5
DATA SHEET
24 VDC UNINTERRUPTABLE POWER SUPPLIES (UPS) / BATTERY CHARGER - TYPE 3

No. DESCRIPTION REQUIREMENT / SPEC VENDOR'S RESPONSE


1 GENERAL SPECIFICATION
STANDARD AND LABEL IEC
UPS STANDARD IEC 62040 (All part)
TEMPERATURE RANGE 0 …..+40OC (For Operation)
INSTALLATION ALTITUDE ≥ 1000 m ASL
RELIABILITY MTBF ≥ 100000 Hours
2 SYSTEM CONFIGURATION Redundant consist of 2 DC UPS BLOCK (2 x 18 KVA) consist of
A. 2 X 100% Rectifier with isolation transformer min. 6 pulse; THDI ≤ 28%
B. 4 unit of DC Distribution Board (Or VTA)
C. 2 unitS of Outgoing to "existing Battery"
3 ELECTRIC SPECIFICATION
RECTIFIER (19BTQ10 - 19BTR10)
Input - Voltage and Freq 3x400 VAC ± 15% , 50 Hz ± 5%
Input - Min. Power (Current) 7.3 KVA (16A upstream protection)
Output - Voltage 24 VDC (Max. 28.8 VDC) ; Ripple voltage ≤ 2% rms with connected battery
Output - Total current 100 A
Output - Overload 150% for 2 sec
INTERNAL WIRING Halogen-free, flame retardant and non toxic.
OVERALL EFFICIENCY >84 %
SPACE HEATERS In rectifier paneL
24 VDC DB (subject to existing)
(19BUE, 19BUF, 19BUG01, 19BUG02)
Input At outgoing Rectifier
Output 19BUE
10A, 2P MCB + PE : 1 Units 32A, 2P MCB + PE : 3 Units
25A, 2P MCB + PE : 8 Units
19BUF
25A, 2P MCB + PE : 8 Units 32A, 2P MCB + PE : 3 Units
19BUG01
2A, 2P MCB + PE : 4 Units 10A, 2P MCB + PE : 1 Units
4A, 2P MCB + PE : 3 Units 16A, 2P MCB + PE : 1 Units
19BUG02
2A, 2P MCB + PE : 12 Units 4A, 2P MCB + PE : 4 Units

4 OPERATING AND COMMUNICATION


RECTIFIER -PARAMETERS Float Charge : 26.8 V; Boost Charge: 28.8 V -8 hours, Current limitation : VTA
Low Battery Voltage: Warning: 21.6 V ; Shutdown: 19.2 V
CONTROL AND MONITORING It's shall be based on Microprocessor controlled system logic with real time fault analysis
able recording and memorisation of the last events..
Having Battery management system (temperature sensor) and also able to test capacity of
Battries.
INDICATION Front-panel with mimic diagram and detailed LED Indication
EXTERNAL CONNECTION Yes, fail safe open/close contacts
(Common fault, and also individual alarm : battery operation, etc)

COMMUNICATION INTERFACE Yes, minimum MODBUS TCP (VTA)

5 MECHANICAL SPECIFICATION Free standing cabinet - Front door, side and rear removable
PROTECTION CLASS min. 30 (close door) ; IP 20 / NEMA 1 (Open door)
Bottom cable entry
VENTILATION Self-Contained blowers, air inlet in front below, outlet on the top
Notes
1. BATTERY (Existing) Lead Acid : FIAMM - TYPE SMBF8 (800 AH)
No's of Cells 12 pcs - Mounted on a steel racK
Autonomy 120 Minutes
SINGLE LINE DIAGRAM

GENERAL ARRANGEMENT

Notes:
Existing dimension is about 3725 x 1800 x 800 mm,; Vendor to consider the available space