5335
2 - W i r e Tr a n s m i t t e r
with HART® Protocol

No. 5335V113-IN
F r o m s e r. n o . 1 0 0 9 2 4 0 0 0

BR
INMETRO OCP-0029

SIGNALS THE BEST


DK PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturud-
sving, og alle produkter opfylder de strengeste internationale stan-
darder. Vores motto »Signals the Best« er indbegrebet af denne
filosofi – og din garanti for kvalitet.

UK PR electronics A/S offers a wide range of analogue and digital


signal conditioning modules for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Modules. You can trust our products
in the most extreme environments with electrical noise, vibrations
and temperature fluctuations, and all products comply with the
most exacting international standards. »Signals the Best« is the
epitome of our philosophy – and your guarantee for quality.

FR PR electronics A/S offre une large gamme de produits pour le


traite­ment des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afficheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.

DE PR electronics A/S verfügt über ein breites Produktprogramm


an analogen und digitalen Signalverarbeitungsmodule für die in­
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Überein­stimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
1101
2-WIRE TRANSMITTER
WITH HART® PROTOCOL

PRetop 5335

CONTENTS
EC declaration of conformity.............................................. 2
Application.......................................................................... 3
Technical characteristics..................................................... 3
Mounting / installation......................................................... 3
Applications......................................................................... 4
Order: 5335......................................................................... 5
Electrical specifications....................................................... 5
Connections........................................................................ 9
Block diagram..................................................................... 10
Programming....................................................................... 11
Connection of transmitters in multidrop mode................... 13
Mechanical specifications................................................... 13
Mounting of sensor wires.................................................... 13
Appendix............................................................................. 15
ATEX Installation Drawing - 5335A................................... 15
ATEX Installation Drawing - 5335D.................................. 15
IECEx installation drawing - 5335D.................................. 15
FM Installation Drawing No. 5300Q502........................... 15
CSA Installation Drawing No. 533XQC03........................ 15
INMETRO Instruções de Segurança................................ 15

5 335V113-IN 1
EC declaration of conformity
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde

hererby declares that the following product:


Type: 5335
Name: 2-Wire transmitter with HART® protocol

is in conformity with the following directives and standards:

The EMC Directive 2004/108/EC and later amendments


EN 61326-1 : 2006

For specification of the acceptable EMC performance level, refer to the


electrical specifications for the module.

The ATEX Directive 94/9/EC and later amendments


EN 60079-0 : 2006, EN 60079-11 : 2007,
EN 60079-15 : 2005 and EN 60079-26 : 2007
EN 61241-0 : 2006 and EN 61241-11 : 2006
ATEX certificate: KEMA 03ATEX1508 X (5335A)
ATEX certificate: KEMA 03ATEX1537 (5335D)

Notified body
KEMA Quality B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands

Rønde, 18 December 2009 Kim Rasmussen


Manufacturer’s signature

2 5335V113-IN CONTENTS
2-WIRE TRANSMITTER
WITH HART® PROTOCOL
PRetop 5335
• RTD, TC, Ohm, or mV input
• Extremely high measurement accuracy
• HART® communication
• Galvanic isolation
• For DIN form B sensor head mounting
Application
• Linearised temperature measurement with Pt100...Pt1000, Ni100...Ni1000, or
TC sensor.
• Difference or average temperature measurement of 2 resistance or TC sensors.
• Conversion of linear resistance variation to a standard analogue current
signal, for instance from valves or Ohmic level sensors.
• Amplification of a bipolar mV signal to a standard 4...20 mA current signal.
• Connection of up to 15 transmitters to a digital 2-wire signal with HART®
communication.
Technical characteristics
• Within a few seconds the user can program PR5335 to measure temperatures
within all ranges defined by the norms.
• The RTD and resistance inputs have cable compensation for 2-, 3- and 4-wire
connection.
• The 5335 has been designed according to strict safety requirements and is
thus suitable for application in SIL 2 installations.
• Continuous check of vital stored data for safety reasons.
• Sensor error detection according to the guidelines in NAMUR NE 89.
Mounting / installation
• For DIN form B sensor head mounting. In non-hazardous areas the 5335 can
be mounted on a DIN rail with the PR fitting type 8421.
• NB: As Ex barrier for 5335D we recommend 5106B.

CONTENTS 5 335V113-IN 3
Applications
2-wire installation
RTD to 4...20 mA in control room

V+

+
+
-

-
mA

2-wire installation
TC to 4...20 mA in control room
+

V+
+
+
-

-
-

mA

2-wire installation
Resistance to 4...20 mA in control room

V+
+
+
-

mA

2-wire installation
mV to 4...20 mA in control room
+

V+
+
+
-

-
-

mA

Difference or average 2-wire installation


RTD, TC or mV in control room
- +
2

- +
V+
2 1
+
+

2
-

- +
-

1
1

mA
- +

4 5335V113-IN CONTENTS
Order: 5335

Type Version

5335 Standard :A
CSA, FM, ATEX & IECEx :D

Electrical specifications
Specifications range:
-40°C to +85°C
Common specifications:
Supply voltage, DC
Standard............................................... 8.0...35 V
CSA, FM, ATEX & IECEx....................... 8.0...30 V
Isolation voltage, test / operation................ 1.5 kVAC / 50 VAC
Warm-up time............................................... 30 s
Communications interface........................... HART® and Loop Link
Signal / noise ratio....................................... min. 60 dB
Response time (programmable)................... 1...60 s
EEprom error check..................................... < 10 s
Signal dynamics, input................................. 22 bit
Signal dynamics, output.............................. 16 bit
Calibration temperature............................... 20...28°C

Accuracy, the greater of general and basic values:


General values
Absolute Temperature
Input type accuracy coefficient
All ≤ ±0.05% of span ≤ ±0.005% of span / °C

CONTENTS 5 335V113-IN 5
Basic values
Basic Temperature
Input type accuracy coefficient
Pt100 and Pt1000 ≤ ±0.1°C ≤ ±0.005°C/°C
Ni100 ≤ ±0.2°C ≤ ±0.005°C/°C
Lin. R ≤ ±0.1 Ω ≤ ±5 mW / °C
Volt ≤ ±10 µV ≤ ±0.5 µV / °C
TC type:
E, J, K, L, N, T, U ≤ ±0.5°C ≤ ±0.025°C / °C
TC type:
B, R, S, W3, W5 ≤ ±1°C ≤ ±0.1°C / °C

EMC immunity influence...................................... < ±0.1% of span


Extended EMC immunity:
NAMUR NE 21, A criterion, burst........................ < ±1% of span
Effect of supply voltage variation................. < 0.005% of span / VDC
Vibration....................................................... IEC 60068-2-6 Test FC
Lloyd’s specification no. 1........................... 4 g / 2...100 Hz
Max. wire size............................................... 1 x 1.5 mm2 stranded wire
Relative humidity.......................................... < 95% RH (non-cond.)
Dimensions................................................... Ø 44 x 20.2 mm
Protection degree (enclosure / terminals).... IP68 / IP00
Weight.......................................................... 50 g
Electrical specifications, input:
Max. offset................................................... 50% of selec. numerical max. value
RTD and linear resistance input:
RTD Min. Max. Min.
type value value span Standard
Pt100 -200°C +850°C 10°C IEC 60751
Ni100 -60°C +250°C 10°C DIN 43760
Lin. R 0W 7000 W 10 W -----
Cable resistance per wire (max.).................. 5Ω
Sensor current.............................................. nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire)................................................... < 0.002 Ω/Ω
Sensor error detection................................. Yes
Short circuit detection.................................. If 0% > 30 Ω

6 5335V113-IN CONTENTS
TC input:
Min. Max. Min.
Type temperature temperature span Standard
B +400°C +1820°C 100°C IEC584
E -100°C +1000°C 50°C IEC584
J -100°C +1200°C 50°C IEC584
K -180°C +1372°C 50°C IEC584
L -100°C +900°C 50°C DIN 43710
N -180°C +1300°C 50°C IEC584
R -50°C +1760°C 100°C IEC584
S -50°C +1760°C 100°C IEC584
T -200°C +400°C 50°C IEC584
U -200°C +600°C 50°C DIN 43710
W3 0°C +2300°C 100°C ASTM E988-90
W5 0°C +2300°C 100°C ASTM E988-90
Cold junction compensation........................ < ±1.0°C
External CJC with Ni100 or Pt100............... -40 ≤ Tamb. ≤ 135°C
Sensor error detection................................. Yes
Sensor error current:
When detecting..................................... nom. 33 μA
Else....................................................... 0 μA
Short circuit detection.................................. If 0% > 5 mV
Voltage input:
Measurement range..................................... -800...+800 mV
Min. span...................................................... 2.5 mV
Input resistance............................................ 10 MΩ
Current output:
Signal range................................................. 4...20 mA
Min. signal range.......................................... 16 mA
Updating time............................................... 440 ms
(660 ms for diff.)
Fixed output signal....................................... Between 4 and 20 mA
Output signal at EEprom error..................... ≤ 3.5 mA
Load resistance............................................ ≤ (Vsupply - 8) / 0.023 [Ω ]
Load stability................................................ < ±0.01% of span / 100 Ω
Sensor error detection:
Programmable.............................................. 3.5...23 mA
Namur NE43 Upscale................................ 23 mA
Namur NE43 Downscale............................ 3.5 mA
Of span = Of the presently selected range

CONTENTS 5 335V113-IN 7
Ex appoval - 5335A:
KEMA 03ATEX1508 X................................... II 3 GD Ex nA [nL] IIC T6...T4 or
II 3 GD Ex nL IIC T6...T4 or
II 3 GD Ex nA [ic] IIC T6...T4 or
II 3 GD Ex ic IIC T6...T4
ATEX Installation Drawing No............... 5335QA02

Ex / I.S. approvals - 5335D:


ATEX KEMA 03ATEX1537............................ II 1 G Ex ia IIC T4 or T6
II 1 D Ex iaD
Max. amb. temperature for T1...T4.............. 85°C
Max. amb. temperature for T5 and T6 . ...... 60°C
ATEX, applicable in zone.............................. 0, 1, 2, 20, 21 or 22
ATEX Installation Drawing No............... 5335QE01
IECEx KEM 10.0083..................................... Ex ia IIC T4...T6 Ga
Ex ia IIIC T135°C...T80°C Da
IECEx Installation Drawing No.............. 5335QE01
FM, applicable in.......................................... IS, Class I, Div. 1, Group A, B, C, D
IS, Class I, Zone 0, AEx ia IIC
FM Installation Drawing No.................. 5300Q502
CSA, applicable in........................................ IS, Class I, Div. 1, Group A, B, C, D,
Ex ia IIC
IS, Class I, Zone 0, AEx ia IIC
CSA Installation Drawing No................ 533XQC03
INMETRO 09/UL-BRCO-0002..................... BR-Ex ia IIC T4 or T6 or
-40°C ≤ Tamb. ≤ +85°C, or
-40°C ≤ Tamb. ≤ +60°C

Marine approval:
Det Norske Veritas, Ships & Offshore.......... Standard for Certification No. 2.4
GOST R approval:
VNIIM & VNIIFTRI, Cert. no.......................... See www.prelectronics.com
Observed authority requirements: Standard:
EMC 2004/108/EC....................................... EN 61326-1
ATEX 94/9/EC............................................... EN 60079-0, EN 60079-11,
EN 60079-15 and EN 60079-26
EN 61241-0 and EN 61241-11
IECEx............................................................ IEC 60079-0, -11, 26, IEC 61241-11
FM................................................................ 3600, 3611, 3610
CSA, CAN / CSA.......................................... C22.2 No. 157, E60079-11, UL 913
INMETRO..................................................... IEC 60079-0 and IEC 60079-11

8 5335V113-IN CONTENTS
Connections
Input:
RTD, 2-wire RTD, 3-wire RTD, 4-wire TC, internal CJC
3 4 5 6 3 4 5 6 3 4 5 6 3 4 5 6

- +

TC, external CJC mV Resistance, 2-wire Resistance, 3-wire


3 4 5 6 3 4 5 6 3 4 5 6 3 4 5 6

- +
- +

TC, difference TC, difference


RTD, difference or average, or average,
Resistance, 4-wire or average with internal CJC with external CJC
3 4 5 6 3 4 5 6 3 4 5 6 3 4 5 6
+

+ 2 -

2 1 2 1 + 1 -
-

mV, difference
or average Output: 2-wire installation
3 4 5 6 1 2

2 1
+

+ mA -
-

CONTENTS 5 335V113-IN 9
Block diagram

8.0...35 VDC

4...20 mA
Supply +

Supply -
mA
1

2
Ex circuit, only 5335D

0. . . 1 6
mA
Comm.
4 mA

D/A
Supply +
8.0...35 VDC
1

E E P RO M
mV RTD, lin. R TC
CPU

- wire Ext. 4 mA
4 3 2 CJC
6

5 33 5
5

Ex circuit, only 5335D


+ +
Int.
CJC CPU Comm.

mV M UX PGA A/D
- -
4
A/D

D/A
3
Input gnd. 0. . . 1 6
mA
E E P RO M
Supply -
PGA

2 mA
4...20 mA
5 33 5
M UX
CJC
Int.
6
5

4
3
Input gnd.
TC

-
CJC
Ext.
RTD, lin. R

3 2
- wire
4
mV

-
mV

10 5335V113-IN CONTENTS
Programming
PRetop 5335 can be configured in the following 3 ways:
1. With PR electronics A/S’ communications interface Loop Link and PReset PC
configuration software.

2. With a HART® modem and PReset PC configuration software.

3. With a HART® communicator with PR electronics A/S’ DDL driver.

1: Loop Link
For programming please refer to the drawing below and the help functions in
PReset.
Loop Link is not approved for communication with modules installed in
hazardous (Ex) areas.

Receiving
Equipment
Disconnect
1 +Vsupply
Red * Yellow Input
2
Black * Green

PRetop 5335

Connector

08:30:00
n Language Option
Output Communicatio
File Product Input PRetop 5331
2004-8-10
Date:
Serial no: 043201594
Tag no: PRelectronics

Analog output
Analog input Output type: 4 - 20mA
Pt100 DIN/IEC
Input type: Sensor error: Upscale
0.00 - 50.00 C
Input range:
3-wire
Connection:

Loop
------

5909 - USB
Cold junction comp:
1.00 sec
Response time:

Link 5905 - RS232

* Connected only for


on-line programming

CONTENTS 5 335V113-IN 11
2: HART® modem
For programming please refer to the drawing below and the help functions in
PReset.
Receiving
Equipment

1 +Vsupply

2 Input

Rload > 250 Ω, < 1100 Ω

P Ret op 5 335

08: 30: 0 0
u n i c a ti o n L an g u ag e O p t i o n
ut O ut put C om m
F i l e P ro d u ct I n p P R e t op 53 31
1 99 4- 8 - 10
D a te :
S e r ia l no : 9 43 20 15 94
Ta g no : PRe le ct r on ic s

An al og o ut pu t
An al og i np ut 4 - 20 mA
Ou t pu t ty p e:
P t 1 00 D I N/ I E C

HART® modem
In pu t t yp e: S e ns o r er r or : U ps c a le
0 . 00 - 50 . 00 C
In pu t r an ge :
3 - w ir e
C o nn ec t io n:
p : ----- -
Co ld ju nc t io n co m
1 . 00 s ec
Re sp on s e ti me :

3: HART® communicator
For programming please refer to the drawing below. To gain access to product-
specific commands, the HART® communicator must be loaded with the
PR electronics A/S DDL driver. This can be ordered either at the HART®
Communica­tion Foundation or at PR electronics A/S.

Receiving
area Safe area Equipment

1 +Vsupply

2 Input

Rload > 250 Ω, < 1100 Ω

P Ret op 5 335

12 5335V113-IN CONTENTS
Connection of transmitters in
multidrop mode
The HART® communicator or a PC modem can be connected accross AB or BC.

+ + A
PRetop PRetop PRetop
5335 5335 5335
Power
supply

- B
Max. 15 transmitters
Rload > 250 Ω, < 1100 Ω
R
C
-
The outputs of max. 15 transmitters can be connected in parallel for a digital
HART® communication on 2-wires.
Before it is connected, each transmitter must be configured with a unique number
from 1 to 15. If 2 transmitters are configured with the same number, both will
be excluded. The transmitters must be programmed for multidrop mode (with
a fixed output signal of 4 mA). Maximum current in the loop is therefore 60 mA.
The communication is either by means of a HART® communicator or a HART®
modem.
The PReset PC configuration software can configure the individual transmitter
for multidrop mode and provide it with a unique polling address.

Mechanical specifications Mounting of sensor wires

Wires must be mounted between the metal


plates.

CONTENTS 5 335V113-IN 13
14 5335V113-IN CONTENTS
Appendix

ATEX Installation Drawing - 5335A

ATEX Installation Drawing - 5335D

IECEx installation drawing - 5335D

FM Installation Drawing No. 5300Q502

CSA Installation Drawing No. 533XQC03

INMETRO Instruções de Segurança

CONTENTS 5 335V113-IN 15
5335QA02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

ATEX Installation drawing


5335
For safe installation of 5335A the following must be observed. The module shall only be installed
by qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

ATEX Certificate KEMA 03ATEX 1508X

Marking II 3 GD Ex nA [nL] IIC T6..T4


II 3 GD Ex nL IIC T6..T4

II 3 GD Ex nA [ic] IIC T6..T4


II 3 GD Ex ic IIC T6..T4

Standards EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-15 : 2005

T4: -40 ≤ Ta ≤ 85ºC Terminal: 3,4,5,6 Terminal: 1,2 Terminal: 1,2


T6: -40 ≤ Ta ≤ 60ºC Ex nA Ex nL or Ex ic

Uo: 9.6 V U ≤ 35 VDC Ui = 35 VDC


Io: 28 mA I = 4 - 20 mA Li = 10 μH
Po: 67 mW Ci = 1.0 nF
Lo: 45 mH
Co: 28 μF

Special conditions for safe use

For use in a potentially explosive atmosphere of flammable gasses, vapours or mists, the
transmitter shall be mounted in an enclosure providing a degree of protection of at least IP54 in
accordance with EN60529.

For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure
providing a degree of protection of at least IP6X in accordance with EN60529. The surface
temperature of the enclosure shall be determined after installation of the transmitter.

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.

Revision date: Version Revision Page:


2009-09-29 V1R0 1/1

16 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

ATEX Installation drawing


5335
For safe installation of 5335D the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

ATEX Certificate KEMA 03ATEX 1537

Marking II 1 G Ex ia IIC T6..T4


II 1 D Ex iaD

Standards EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-26 : 2007,


EN 61241-0 : 2006, EN 61241-11 : 2006

Hazardous area
Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area

T4: -40 ≤ Ta ≤ 85ºC T105 ºC


T6: -40 ≤ Ta ≤ 60ºC T80 ºC

Terminal: 3,4,5,6 6
Uo: 9.6 VDC
Io: 28 mA 5 1+
Po: 67 mW
Lo: 35 mH 4 2 -
Co: 3.5μF
3 5335D
Barrier

Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF

Revision date: Version Revision Page:


2010-05-28 V2R0 1/2

CONTENTS 5 335V113-IN 17
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Installation notes.

The sensor circuit is not infallibly galvanically isolated from the supply output circuit. However,
the galvanic isolation between the circuits is capable of withstanding a test voltage of 500 VAC
during 1 minute.

In a potentially explosive gas atmosphere, the transmitter shall be mounted in an enclosure in


order to provide a degree of protection of at least IP20 according to EN 60529.

If the transmitter is installed in an explosive atmosphere requiring the use of equipment of


category 1G and if the enclosure is made of aluminium, it must be installed such, that even in
the event of rare incidents, ignition sources due to impact and friction, sparks are excluded; if
the enclosure is made of non-metallic materials, electrostatic charging shall be avoided.

For installation in a potentially explosive dust atmosphere, the following instructions apply:

The transmitter shall be mounted in a metal enclosure form B according to DIN 43729 that is
providing a degree of protection of at least IP6X according to EN 60529, that is suitable for the
application and correctly installed.

Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.

The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm.

Revision date: Version Revision Page:


2010-05-28 V2R0 2/2

18 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

IECEx Installation drawing


For safe installation of 5335D or 5336D the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.

IECEx Certificate IECEx KEM.10.0083

Marking Ex ia IIC T6..T4 Ga


Ex ia IIIC T85ºC – T135ºC Da

Standards IEC60079-11:2006, IEC60079-0: 2007


IEC60079-26: 2006, IEC61241-11:2005

Hazardous area
Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area

T4: -40 ≤ Ta ≤ 85ºC


T6: -40 ≤ Ta ≤ 45ºC

Terminal: 3,4,5,6 6
Uo: 9.6 VDC
Io: 28 mA 5 1+
Po: 67 mW
Lo: 35 mH 4 2 -
Co: 3.5 μF
3 5335D
5336D
Barrier

Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF

Revision date: Version Revision Page:


2010-05-28 V2R0 1/2

CONTENTS 5 335V113-IN 19
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Installation notes.

The transmitter is only approved for mounting in an enclosure form B according to DIN 43729,
or equivalent.

If the transmitter is installed in an explosive atmosphere requiring equipment protection level


Ga, and if the enclosure is made of aluminium, it must be installed such, that even in the event
of rare incidents, ignition sources due to impact and friction, sparks are excluded; if the
enclosure is made of non-metallic materials, electrostatic charging shall be avoided.

For installation in a potentially explosive dust atmosphere, the following instructions apply:

The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is
providing a degree of protection of at least IP6X according to IEC60529, that is suitable for the
application and correctly installed.

Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.

For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.

The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm.

Revision date: Version Revision Page:


2010-05-28 V2R0 2/2

20 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

FM Installation drawing 5335Q502

Model 5331C, 5331D, 5333C and 5333D

Hazardous (Classified) Location Non Hazardous Location


Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G or Associated Apparatus
Class I, Zone 0, IIC or Barrier
+ with
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
entity Parameters:
T6: -40 to + 60 deg. Celcius
UM < 250V
- Voc or Uo < Vmax or Ui
Terminal 1 , 2 Isc or Io < Imax or Ii
Vmax or Ui: 30 V Po < Pi
Imax or Ii: 120 mA Ca or Co > Ci + Ccable
Pmax or Pi: 0.84 W 1 2 La or Lo > Li + Lcable
Ci: 1 nF
Li:10 uH

Terminal 3,4,5,6 6 3 This device must not be


Only passive, or non-energy connected to any associated
storing devices such as RTD's
5 4
apparatus which uses or
and Thermocouples may be generates more than 250 VRMS
connected.
SENSOR

Model 5335C, 5335D


Hazardous (Classified) Location Non Hazardous Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G or Associated Apparatus
Class I, Zone 0, IIC or Barrier
+ with
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
entity Parameters:
T6: -40 to + 60 deg. Celcius
UM < 250V
- Voc or Uo < Vmax or Ui
Terminal 1 , 2 Isc or Io < Imax or Ii
Vmax or Ui: 30 V Po < Pi
Imax or Ii: 120 mA Ca or Co > Ci + Ccable
Pmax or Pi: 0.84 W 1 2 La or Lo > Li + Lcable
Ci: 1 nF
Li:10 uH

Terminal 3,4,5,6 6 3 This device must not be


Vt or Uo: 9.6 V connected to any associated
5 4
It or Io: 28 mA apparatus which uses or
Pt or Po: 67.2 mW generates more than 250 VRMS
Ca or Co: 3.5 uF
La or Lo: 35 mH SENSOR

Revision date: Version Revision Page:


2010-05-28 V2R0 1/2

CONTENTS 5 335V113-IN 21
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

The entity concept

The Transmitter must be installed according to National Electrical Code


(ANSI-NFPA 70).

When installed in Class II locations the Transmitter shall be installed in an enclosure with a specified
ingress protection of IP6X according to IEC 60529 and dust-tight conduit seals must be used.

Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY
CONCEPT. This concept permits interconnection of approved transmitters, meters and other devices in
combinations which have not been specifically examined by FM, provided that the agency's criteria are
met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority having
jurisdiction over the installation.

The entity concept criteria are as follows:

The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(VMAX) and current Ii(IMAX), and maximum power Pi(Pmax), which the device can
receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and
current (Io or ISC or It) and the power Po which can be delivered by the barrier.

The sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the
interconnecting wiring must be less than the capacitance (Ca) which can be safely connected to the
barrier.

The sum of the maximum unprotected inductance (Li) for each intrinsically device and the interconnecting
wiring must be less than the inductance (La) which can be safely connected to the barrier.

The entity parameters Uo,VOC or Vt and Io,ISC or It, and Ca and La for barriers are provided by the barrier
manufacturer.

Revision date: Version Revision Page:


2010-05-28 V2R0 2/2

22 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

CSA Installation Drawing 533XQC03.


5331D, 5333D and 5335D transmitters are intrinsically safe in Zone 0 Group IIC or Class I,
Division1, Group A,B,C,D when installed according to Installation Drawing.

1. Connections with separate power supply and receiver


Output: Standard 4 – 20 mA loop

Receiving
Instrument

- +
Separate Power -
Supply Intrinsically safe Non
+ Barrier Parameters. hazardous
Location
Uo(Voc) =< 30V max 250V
Io(Isc) =< 120mA
Po =< 0,84 W
CSA approved
Barrier Co(Ca)>Sum(Ci+Ccable)
Lo(La)>Sum(Li+Lcable)

+ -
5331D or Terminal: 1-2
Ambient temperature limits 5333D or Ui(Vmax) = 30V
T4:-40 to + 85 deg. Celcius 5335D Ii(Imax) = 120mA
T6:-40 to + 60 deg. Celcius Pi = 0.84W
Ci = 1 nF
Li = 10 uH

5331D or Terminal: 3,4,5,6 Hazardous


Only passive, or non-energy Locations /
1 2 5333D
storing devices such as Sécurité
RTD's and Thermocouples Intrinséque
6 3 may be connected.

5 4 5335D Terminal: 3,4,5,6


Uo(Voc) = 9,6V
Io(Isc) = 28mA
SENSOR Po = 67,2mW
Co(Ca) = 3,5uF
Lo(La) = 35mH

Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the
Canadian Electrical Code (CEC).

Revision date: Version Revision Page:


2010-05-28 V2R0 1/2

CONTENTS 5 335V113-IN 23
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

2. Connection with power supply and barrier built into receiver


Output: Standard 4 – 20 mA loop

Transmitter
Intrinsically safe Power Supply
Barrier Parameters. built into
CSA approved
Uo(Voc) =< 30V Receiving
Io(Isc) =< 120mA Instrument Non-
Po(Pmax) =< 0,84 W hazardous
location
Ca>Sum(Ci)+Ccable max 250 V
La>Sum(Li)+Lcable
+ -

5331D or Terminal: 1-2


Ambient temperature limits 5333D or Ui(Vmax) = 30V
T4: -40 to + 85 deg. Celcius 5335D Ii(Imax) = 120mA
T6: -40 to + 60 deg. Celcius Pi = 0.84W
Ci = 1 nF
1 2 Li = 10 uH
Hazardous
Terminal: 3,4,5,6
6 3 5331D or Locations /
Only passive, or non-energy
5333D Sécurité
5 4 storing devices such as
Intrinséque
RTD's and Thermocouples
may be connected.
SENSOR
Terminal: 3,4,5,6
5335D
Uo(Voc) = 9,6V
Io(Isc) = 28mA
Po = 67,2mW
Co(Ca) = 3,5uF
Lo(La) = 35mH

Warning:
Substitution of components may impair intrinsic safety.
The Transmitters must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC).

Revision date: Version Revision Page:


2010-05-28 V2R0 2/2

24 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

5335D: Instruções de Segurança

Instalação Ex:
Para a instalação segura do transmissor 5335D em áreas classificadas, deve-se observar o seguinte:
O módulo necessita ser instalado somente por pessoal qualificado e que tenham familiaridade com
normas internacionais, diretivas e normalização aplicadas à estas áreas.

O ano de fabricação do instrumento pode ser obtido, observando-se os primeiros dois dígitos do seu
número de série.

O circuito do sensor não está com isolação galvânica total em relação ao circuito de entrada. Todavia a
isolação galvânica entre os circuitos é capaz de suportar teste de voltagem de 500 Vac durante 1 minuto.

O transmissor precisa ser montado em um invólucro com um grau de proteção pelo menos IP-20.

Em atmosferas explosivas compostas por misturas de ar / poeira:

O transmissor somente poderá ser instalado em uma atmosfera potencialmente explosiva composta por
poeira combustível se estiver montado no interior de um invólucro metálico forma B de acordo com a
norma DIN 43729 com um grau de proteção pelo menos IP-6X de acordo com a norma IEC 60529, que
seja adequado para esta aplicação e corretamente instalado.

As entradas dos cabos e outras barreiras a serem utilizadas devem ser adequadas e corretamente
instaladas.

Onde a temperatura ambiente for ≥60ºC, devem ser utilizados cabos resistentes ao calor que resistam pelo
menos 20K acima da temperatura ambiente.

Se o invólucro onde o transmissor está montado for feito de alumínio e instalado em Zona 0, 1 ou Zona
20,21 ou 22, este não deve conter mais do que 6% do seu peso total de magnésio e titânio.

Acessórios adicionais ao invólucro devem ser projetados e/ou instalados de tal modo que até mesmo
eventos de rara incidência , fontes de ignição causadas por impactos e faíscas por fricção sejam
excluídas.

Revision date: Version Revision Page:


2010-05-28 V2R0 1/2

CONTENTS 5 335V113-IN 25
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM

Ex ia IIC T6 / T4 T80°C...T105°C
Temp. amb. máxima T1...T4 ............... 85°C
Temp. amb. máxima T5 e T6 .............. 60°C
Aplicável em Zona ............................... 0, 1, 2, 20, 21 ou 22

Dados Ex / I.S.:
Sinal de saída / alimentação , terminal 1 e 2:
Ui.......................................................... : 30 VDC
Ii ........................................................... : 120 mADC
Pi.......................................................... : 0,84 W
Li .......................................................... : 10 µH
Ci.......................................................... : 1,0 nF
Entrada do sensor, terminais 3, 4, 5 e 6:
Uo ........................................................ : 9,6 VDC
Io .......................................................... : 28 mA
Po......................................................... : 67 mW
Lo ......................................................... : 35 mH
Co ........................................................ : 3,5 µF

Revision date: Version Revision Page:


2010-05-28 V2R0 2/2

26 5335V113-IN CONTENTS
Displays Programmable displays with a wide
selection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearisation, scaling,
and difference measurement functions for programming
via PReset software.
Ex interfaces Interfaces for analogue and digital
signals as well as HART® signals between sensors / I/P
converters / frequency signals and control systems in Ex
zone 0, 1 & 2 and for some modules in zone 20, 21 & 22.

Isolation Galvanic isolators for analogue and


digital signals as well as HART® signals. A wide product
range with both loop-powered and universal isolators
featuring linearisation, inversion, and scaling of output
signals.
Temperature A wide selection of transmitters for DIN
form B mounting and DIN rail modules with analogue
and digital bus communication ranging from application-
specific to universal transmitters.

Universal PC or front programmable modules with


universal options for input, output and supply. This range
offers a number of advanced features such as process
calibration, linearisation and auto-diagnosis.
 www.prelectronics.fr
 sales@prelectronics.fr

 www.prelectronics.de
 sales@prelectronics.de

 www.prelectronics.es
 sales@prelectronics.es

 www.prelectronics.it
 sales@prelectronics.it

 www.prelectronics.se
 sales@prelectronics.se

 www.prelectronics.co.uk
 sales@prelectronics.co.uk

 www.prelectronics.com
 sales@prelectronics.com

 www.prelectronics.org.cn
 sales@prelectronics.org.cn

Head office
Denmark www.prelectronics.com
PR electronics A/S sales@prelectronics.dk
Lerbakken 10 tel. +45 86 37 26 77
DK-8410 Rønde fax +45 86 37 30 85

You might also like