2 - W i r e Tr a n s m i t t e r
with HART® Protocol
No. 5335V113-IN
F r o m s e r. n o . 1 0 0 9 2 4 0 0 0
BR
INMETRO OCP-0029
PRetop 5335
CONTENTS
EC declaration of conformity.............................................. 2
Application.......................................................................... 3
Technical characteristics..................................................... 3
Mounting / installation......................................................... 3
Applications......................................................................... 4
Order: 5335......................................................................... 5
Electrical specifications....................................................... 5
Connections........................................................................ 9
Block diagram..................................................................... 10
Programming....................................................................... 11
Connection of transmitters in multidrop mode................... 13
Mechanical specifications................................................... 13
Mounting of sensor wires.................................................... 13
Appendix............................................................................. 15
ATEX Installation Drawing - 5335A................................... 15
ATEX Installation Drawing - 5335D.................................. 15
IECEx installation drawing - 5335D.................................. 15
FM Installation Drawing No. 5300Q502........................... 15
CSA Installation Drawing No. 533XQC03........................ 15
INMETRO Instruções de Segurança................................ 15
5 335V113-IN 1
EC declaration of conformity
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
Notified body
KEMA Quality B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
2 5335V113-IN CONTENTS
2-WIRE TRANSMITTER
WITH HART® PROTOCOL
PRetop 5335
• RTD, TC, Ohm, or mV input
• Extremely high measurement accuracy
• HART® communication
• Galvanic isolation
• For DIN form B sensor head mounting
Application
• Linearised temperature measurement with Pt100...Pt1000, Ni100...Ni1000, or
TC sensor.
• Difference or average temperature measurement of 2 resistance or TC sensors.
• Conversion of linear resistance variation to a standard analogue current
signal, for instance from valves or Ohmic level sensors.
• Amplification of a bipolar mV signal to a standard 4...20 mA current signal.
• Connection of up to 15 transmitters to a digital 2-wire signal with HART®
communication.
Technical characteristics
• Within a few seconds the user can program PR5335 to measure temperatures
within all ranges defined by the norms.
• The RTD and resistance inputs have cable compensation for 2-, 3- and 4-wire
connection.
• The 5335 has been designed according to strict safety requirements and is
thus suitable for application in SIL 2 installations.
• Continuous check of vital stored data for safety reasons.
• Sensor error detection according to the guidelines in NAMUR NE 89.
Mounting / installation
• For DIN form B sensor head mounting. In non-hazardous areas the 5335 can
be mounted on a DIN rail with the PR fitting type 8421.
• NB: As Ex barrier for 5335D we recommend 5106B.
CONTENTS 5 335V113-IN 3
Applications
2-wire installation
RTD to 4...20 mA in control room
V+
+
+
-
-
mA
2-wire installation
TC to 4...20 mA in control room
+
V+
+
+
-
-
-
mA
2-wire installation
Resistance to 4...20 mA in control room
V+
+
+
-
mA
2-wire installation
mV to 4...20 mA in control room
+
V+
+
+
-
-
-
mA
- +
V+
2 1
+
+
2
-
- +
-
1
1
mA
- +
4 5335V113-IN CONTENTS
Order: 5335
Type Version
5335 Standard :A
CSA, FM, ATEX & IECEx :D
Electrical specifications
Specifications range:
-40°C to +85°C
Common specifications:
Supply voltage, DC
Standard............................................... 8.0...35 V
CSA, FM, ATEX & IECEx....................... 8.0...30 V
Isolation voltage, test / operation................ 1.5 kVAC / 50 VAC
Warm-up time............................................... 30 s
Communications interface........................... HART® and Loop Link
Signal / noise ratio....................................... min. 60 dB
Response time (programmable)................... 1...60 s
EEprom error check..................................... < 10 s
Signal dynamics, input................................. 22 bit
Signal dynamics, output.............................. 16 bit
Calibration temperature............................... 20...28°C
CONTENTS 5 335V113-IN 5
Basic values
Basic Temperature
Input type accuracy coefficient
Pt100 and Pt1000 ≤ ±0.1°C ≤ ±0.005°C/°C
Ni100 ≤ ±0.2°C ≤ ±0.005°C/°C
Lin. R ≤ ±0.1 Ω ≤ ±5 mW / °C
Volt ≤ ±10 µV ≤ ±0.5 µV / °C
TC type:
E, J, K, L, N, T, U ≤ ±0.5°C ≤ ±0.025°C / °C
TC type:
B, R, S, W3, W5 ≤ ±1°C ≤ ±0.1°C / °C
6 5335V113-IN CONTENTS
TC input:
Min. Max. Min.
Type temperature temperature span Standard
B +400°C +1820°C 100°C IEC584
E -100°C +1000°C 50°C IEC584
J -100°C +1200°C 50°C IEC584
K -180°C +1372°C 50°C IEC584
L -100°C +900°C 50°C DIN 43710
N -180°C +1300°C 50°C IEC584
R -50°C +1760°C 100°C IEC584
S -50°C +1760°C 100°C IEC584
T -200°C +400°C 50°C IEC584
U -200°C +600°C 50°C DIN 43710
W3 0°C +2300°C 100°C ASTM E988-90
W5 0°C +2300°C 100°C ASTM E988-90
Cold junction compensation........................ < ±1.0°C
External CJC with Ni100 or Pt100............... -40 ≤ Tamb. ≤ 135°C
Sensor error detection................................. Yes
Sensor error current:
When detecting..................................... nom. 33 μA
Else....................................................... 0 μA
Short circuit detection.................................. If 0% > 5 mV
Voltage input:
Measurement range..................................... -800...+800 mV
Min. span...................................................... 2.5 mV
Input resistance............................................ 10 MΩ
Current output:
Signal range................................................. 4...20 mA
Min. signal range.......................................... 16 mA
Updating time............................................... 440 ms
(660 ms for diff.)
Fixed output signal....................................... Between 4 and 20 mA
Output signal at EEprom error..................... ≤ 3.5 mA
Load resistance............................................ ≤ (Vsupply - 8) / 0.023 [Ω ]
Load stability................................................ < ±0.01% of span / 100 Ω
Sensor error detection:
Programmable.............................................. 3.5...23 mA
Namur NE43 Upscale................................ 23 mA
Namur NE43 Downscale............................ 3.5 mA
Of span = Of the presently selected range
CONTENTS 5 335V113-IN 7
Ex appoval - 5335A:
KEMA 03ATEX1508 X................................... II 3 GD Ex nA [nL] IIC T6...T4 or
II 3 GD Ex nL IIC T6...T4 or
II 3 GD Ex nA [ic] IIC T6...T4 or
II 3 GD Ex ic IIC T6...T4
ATEX Installation Drawing No............... 5335QA02
Marine approval:
Det Norske Veritas, Ships & Offshore.......... Standard for Certification No. 2.4
GOST R approval:
VNIIM & VNIIFTRI, Cert. no.......................... See www.prelectronics.com
Observed authority requirements: Standard:
EMC 2004/108/EC....................................... EN 61326-1
ATEX 94/9/EC............................................... EN 60079-0, EN 60079-11,
EN 60079-15 and EN 60079-26
EN 61241-0 and EN 61241-11
IECEx............................................................ IEC 60079-0, -11, 26, IEC 61241-11
FM................................................................ 3600, 3611, 3610
CSA, CAN / CSA.......................................... C22.2 No. 157, E60079-11, UL 913
INMETRO..................................................... IEC 60079-0 and IEC 60079-11
8 5335V113-IN CONTENTS
Connections
Input:
RTD, 2-wire RTD, 3-wire RTD, 4-wire TC, internal CJC
3 4 5 6 3 4 5 6 3 4 5 6 3 4 5 6
- +
- +
- +
+ 2 -
2 1 2 1 + 1 -
-
mV, difference
or average Output: 2-wire installation
3 4 5 6 1 2
2 1
+
+ mA -
-
CONTENTS 5 335V113-IN 9
Block diagram
8.0...35 VDC
4...20 mA
Supply +
Supply -
mA
1
2
Ex circuit, only 5335D
0. . . 1 6
mA
Comm.
4 mA
D/A
Supply +
8.0...35 VDC
1
E E P RO M
mV RTD, lin. R TC
CPU
- wire Ext. 4 mA
4 3 2 CJC
6
5 33 5
5
mV M UX PGA A/D
- -
4
A/D
D/A
3
Input gnd. 0. . . 1 6
mA
E E P RO M
Supply -
PGA
2 mA
4...20 mA
5 33 5
M UX
CJC
Int.
6
5
4
3
Input gnd.
TC
-
CJC
Ext.
RTD, lin. R
3 2
- wire
4
mV
-
mV
10 5335V113-IN CONTENTS
Programming
PRetop 5335 can be configured in the following 3 ways:
1. With PR electronics A/S’ communications interface Loop Link and PReset PC
configuration software.
1: Loop Link
For programming please refer to the drawing below and the help functions in
PReset.
Loop Link is not approved for communication with modules installed in
hazardous (Ex) areas.
Receiving
Equipment
Disconnect
1 +Vsupply
Red * Yellow Input
2
Black * Green
PRetop 5335
Connector
08:30:00
n Language Option
Output Communicatio
File Product Input PRetop 5331
2004-8-10
Date:
Serial no: 043201594
Tag no: PRelectronics
Analog output
Analog input Output type: 4 - 20mA
Pt100 DIN/IEC
Input type: Sensor error: Upscale
0.00 - 50.00 C
Input range:
3-wire
Connection:
Loop
------
5909 - USB
Cold junction comp:
1.00 sec
Response time:
CONTENTS 5 335V113-IN 11
2: HART® modem
For programming please refer to the drawing below and the help functions in
PReset.
Receiving
Equipment
1 +Vsupply
2 Input
P Ret op 5 335
08: 30: 0 0
u n i c a ti o n L an g u ag e O p t i o n
ut O ut put C om m
F i l e P ro d u ct I n p P R e t op 53 31
1 99 4- 8 - 10
D a te :
S e r ia l no : 9 43 20 15 94
Ta g no : PRe le ct r on ic s
An al og o ut pu t
An al og i np ut 4 - 20 mA
Ou t pu t ty p e:
P t 1 00 D I N/ I E C
HART® modem
In pu t t yp e: S e ns o r er r or : U ps c a le
0 . 00 - 50 . 00 C
In pu t r an ge :
3 - w ir e
C o nn ec t io n:
p : ----- -
Co ld ju nc t io n co m
1 . 00 s ec
Re sp on s e ti me :
3: HART® communicator
For programming please refer to the drawing below. To gain access to product-
specific commands, the HART® communicator must be loaded with the
PR electronics A/S DDL driver. This can be ordered either at the HART®
Communication Foundation or at PR electronics A/S.
Receiving
area Safe area Equipment
1 +Vsupply
2 Input
P Ret op 5 335
12 5335V113-IN CONTENTS
Connection of transmitters in
multidrop mode
The HART® communicator or a PC modem can be connected accross AB or BC.
+ + A
PRetop PRetop PRetop
5335 5335 5335
Power
supply
- B
Max. 15 transmitters
Rload > 250 Ω, < 1100 Ω
R
C
-
The outputs of max. 15 transmitters can be connected in parallel for a digital
HART® communication on 2-wires.
Before it is connected, each transmitter must be configured with a unique number
from 1 to 15. If 2 transmitters are configured with the same number, both will
be excluded. The transmitters must be programmed for multidrop mode (with
a fixed output signal of 4 mA). Maximum current in the loop is therefore 60 mA.
The communication is either by means of a HART® communicator or a HART®
modem.
The PReset PC configuration software can configure the individual transmitter
for multidrop mode and provide it with a unique polling address.
CONTENTS 5 335V113-IN 13
14 5335V113-IN CONTENTS
Appendix
CONTENTS 5 335V113-IN 15
5335QA02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
For use in a potentially explosive atmosphere of flammable gasses, vapours or mists, the
transmitter shall be mounted in an enclosure providing a degree of protection of at least IP54 in
accordance with EN60529.
For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure
providing a degree of protection of at least IP6X in accordance with EN60529. The surface
temperature of the enclosure shall be determined after installation of the transmitter.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
16 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Hazardous area
Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area
Terminal: 3,4,5,6 6
Uo: 9.6 VDC
Io: 28 mA 5 1+
Po: 67 mW
Lo: 35 mH 4 2 -
Co: 3.5μF
3 5335D
Barrier
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF
CONTENTS 5 335V113-IN 17
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Installation notes.
The sensor circuit is not infallibly galvanically isolated from the supply output circuit. However,
the galvanic isolation between the circuits is capable of withstanding a test voltage of 500 VAC
during 1 minute.
For installation in a potentially explosive dust atmosphere, the following instructions apply:
The transmitter shall be mounted in a metal enclosure form B according to DIN 43729 that is
providing a degree of protection of at least IP6X according to EN 60529, that is suitable for the
application and correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm.
18 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Hazardous area
Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area
Terminal: 3,4,5,6 6
Uo: 9.6 VDC
Io: 28 mA 5 1+
Po: 67 mW
Lo: 35 mH 4 2 -
Co: 3.5 μF
3 5335D
5336D
Barrier
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF
CONTENTS 5 335V113-IN 19
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Installation notes.
The transmitter is only approved for mounting in an enclosure form B according to DIN 43729,
or equivalent.
For installation in a potentially explosive dust atmosphere, the following instructions apply:
The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is
providing a degree of protection of at least IP6X according to IEC60529, that is suitable for the
application and correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm.
20 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
CONTENTS 5 335V113-IN 21
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
When installed in Class II locations the Transmitter shall be installed in an enclosure with a specified
ingress protection of IP6X according to IEC 60529 and dust-tight conduit seals must be used.
Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY
CONCEPT. This concept permits interconnection of approved transmitters, meters and other devices in
combinations which have not been specifically examined by FM, provided that the agency's criteria are
met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority having
jurisdiction over the installation.
The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(VMAX) and current Ii(IMAX), and maximum power Pi(Pmax), which the device can
receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and
current (Io or ISC or It) and the power Po which can be delivered by the barrier.
The sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the
interconnecting wiring must be less than the capacitance (Ca) which can be safely connected to the
barrier.
The sum of the maximum unprotected inductance (Li) for each intrinsically device and the interconnecting
wiring must be less than the inductance (La) which can be safely connected to the barrier.
The entity parameters Uo,VOC or Vt and Io,ISC or It, and Ca and La for barriers are provided by the barrier
manufacturer.
22 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Receiving
Instrument
- +
Separate Power -
Supply Intrinsically safe Non
+ Barrier Parameters. hazardous
Location
Uo(Voc) =< 30V max 250V
Io(Isc) =< 120mA
Po =< 0,84 W
CSA approved
Barrier Co(Ca)>Sum(Ci+Ccable)
Lo(La)>Sum(Li+Lcable)
+ -
5331D or Terminal: 1-2
Ambient temperature limits 5333D or Ui(Vmax) = 30V
T4:-40 to + 85 deg. Celcius 5335D Ii(Imax) = 120mA
T6:-40 to + 60 deg. Celcius Pi = 0.84W
Ci = 1 nF
Li = 10 uH
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the
Canadian Electrical Code (CEC).
CONTENTS 5 335V113-IN 23
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Transmitter
Intrinsically safe Power Supply
Barrier Parameters. built into
CSA approved
Uo(Voc) =< 30V Receiving
Io(Isc) =< 120mA Instrument Non-
Po(Pmax) =< 0,84 W hazardous
location
Ca>Sum(Ci)+Ccable max 250 V
La>Sum(Li)+Lcable
+ -
Warning:
Substitution of components may impair intrinsic safety.
The Transmitters must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC).
24 5335V113-IN CONTENTS
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Instalação Ex:
Para a instalação segura do transmissor 5335D em áreas classificadas, deve-se observar o seguinte:
O módulo necessita ser instalado somente por pessoal qualificado e que tenham familiaridade com
normas internacionais, diretivas e normalização aplicadas à estas áreas.
O ano de fabricação do instrumento pode ser obtido, observando-se os primeiros dois dígitos do seu
número de série.
O circuito do sensor não está com isolação galvânica total em relação ao circuito de entrada. Todavia a
isolação galvânica entre os circuitos é capaz de suportar teste de voltagem de 500 Vac durante 1 minuto.
O transmissor precisa ser montado em um invólucro com um grau de proteção pelo menos IP-20.
O transmissor somente poderá ser instalado em uma atmosfera potencialmente explosiva composta por
poeira combustível se estiver montado no interior de um invólucro metálico forma B de acordo com a
norma DIN 43729 com um grau de proteção pelo menos IP-6X de acordo com a norma IEC 60529, que
seja adequado para esta aplicação e corretamente instalado.
As entradas dos cabos e outras barreiras a serem utilizadas devem ser adequadas e corretamente
instaladas.
Onde a temperatura ambiente for ≥60ºC, devem ser utilizados cabos resistentes ao calor que resistam pelo
menos 20K acima da temperatura ambiente.
Se o invólucro onde o transmissor está montado for feito de alumínio e instalado em Zona 0, 1 ou Zona
20,21 ou 22, este não deve conter mais do que 6% do seu peso total de magnésio e titânio.
Acessórios adicionais ao invólucro devem ser projetados e/ou instalados de tal modo que até mesmo
eventos de rara incidência , fontes de ignição causadas por impactos e faíscas por fricção sejam
excluídas.
CONTENTS 5 335V113-IN 25
5335QE01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Ex ia IIC T6 / T4 T80°C...T105°C
Temp. amb. máxima T1...T4 ............... 85°C
Temp. amb. máxima T5 e T6 .............. 60°C
Aplicável em Zona ............................... 0, 1, 2, 20, 21 ou 22
Dados Ex / I.S.:
Sinal de saída / alimentação , terminal 1 e 2:
Ui.......................................................... : 30 VDC
Ii ........................................................... : 120 mADC
Pi.......................................................... : 0,84 W
Li .......................................................... : 10 µH
Ci.......................................................... : 1,0 nF
Entrada do sensor, terminais 3, 4, 5 e 6:
Uo ........................................................ : 9,6 VDC
Io .......................................................... : 28 mA
Po......................................................... : 67 mW
Lo ......................................................... : 35 mH
Co ........................................................ : 3,5 µF
26 5335V113-IN CONTENTS
Displays Programmable displays with a wide
selection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearisation, scaling,
and difference measurement functions for programming
via PReset software.
Ex interfaces Interfaces for analogue and digital
signals as well as HART® signals between sensors / I/P
converters / frequency signals and control systems in Ex
zone 0, 1 & 2 and for some modules in zone 20, 21 & 22.
www.prelectronics.de
sales@prelectronics.de
www.prelectronics.es
sales@prelectronics.es
www.prelectronics.it
sales@prelectronics.it
www.prelectronics.se
sales@prelectronics.se
www.prelectronics.co.uk
sales@prelectronics.co.uk
www.prelectronics.com
sales@prelectronics.com
www.prelectronics.org.cn
sales@prelectronics.org.cn
Head office
Denmark www.prelectronics.com
PR electronics A/S sales@prelectronics.dk
Lerbakken 10 tel. +45 86 37 26 77
DK-8410 Rønde fax +45 86 37 30 85