DRAFT

DRAFT

From SLD
LT Panel, LOCATION: GROUND FLOOR, FEED ROOM: Transformer page-1
Breaker Phase Phase Load in KW
Main Incoming Earth Size Number of
CKT REF. MCCB/MCB Neutral Load Type Point Reference Watt Per Point Location Total Watt Remarks
Ckt. (re) Points/ Pcs
Rat/Amp Size(rm) R Y B

630A MCCB Future


RYB1 Spare Spare 0 0 - 0 0.00 0.00 0.00
set:320A extension

1000A
250A MCCB Fire Hydrant Fire Pump
MCCB, RYB2
set:200A
4x120.0 1x70.0
Pump
Fire Hydrant Pump 1 93000
room
93000 31.00 31.00 31.00

set: 700A
Main
630A MCCB
RYB3 4x300.0 1x150.0 Distribution MDB 1 232140 Ground Floor 232140 78.12 78.13 75.79
set:504A
Panel

Total Phase Load/KW= 109.12 109.13 106.79


Total Connected Load= 325.04 KW Page No-1

From SLD
MDB, LOCATION: SUB STATION, FEED ROOM: LT PANEL, REF: RYB-03. and from Generator (400kVA) page-1
Breaker Phase Phase Load in KW
Main Incoming Earth Size Number of
CKT REF. MCCB/MCB Neutral Load Type Point Reference Watt Per Point Location Total Watt Remarks
Ckt. (re) Points/ Pcs
Rat/Amp Size(rm) R Y B
500A MCCB
RYB1 4x300 1x150 PFI PFI 1 0 0 0 0.00 0.00 0.00
set:450
MCCB 630A 400A MCCB
RYB2 4x150 1x95 FMDB FMDB-01 1 229295 Ground Floor 229295 77.38 77.32 74.59
set:320
(set:504A) X 2,
(interlocked) RYB3 10A TP 4x4.0 1x4.0 SDB SDB-Security Post 1 2745 Security Post 2745 0.74 0.81 1.20

Total Phase Load/KW= 78.12 78.13 75.79


Total Connected Load= 232.04 KW Page No-1
DRAFT
DRAFT

From SLD
FMDB-01, LOCATION: GROUND FLOOR, FEED ROOM: MDBl, REF: RYB-02. page-2
Breaker Phase
Main Earth Size Number of Phase Load in KW
CKT REF. MCCB/MCB Neutral Load Type Point Reference Watt Per Point Location Total Watt Remarks
Incoming Ckt. (re) Points/ Pcs
Rat/Amp Size(rm) R Y B
63A MCCB
RYB1 4x16.0 1x16.0 DB-1 DB-01 1 28370 Ground Floor 28370 9.34 9.21 9.82
Set at 50A
100A MCCB
RYB2 4x25.0 1x16.0 DB-2 DB-02 1 28373 Ist Floor 28373 9.76 9.28 9.34
Set at 70A
100A MCCB
RYB3 4x25.0 1x16.0 DB-3 DB-03 1 38786 2nd Floor 38786 14.43 12.36 12.00
Set at 70A
100A MCCB
RYB4 4x25.0 1x16.0 DB-4 DB-04 1 36770 3rd Floor 36770 12.49 12.38 11.90
Set at 70A
100A MCCB
RYB5 4x25.0 1x16.0 DB-5 DB-05 1 40850 4th Floor 40850 13.75 13.85 13.25
Set at 70A
MCCB 400A 25A MCCB
RYB6 4x16.0 1x16.0 DB-6 DB-06 1 16540 5th Floor 16540 5.40 5.80 5.34
(set:320A) Set at 15A
63A MCCB
RYB7 4x25.0 1x16.0 DB-7 DB-07 1 33198 Utility Shed 33198 11.00 11.05 11.148
Set at 44A
RYB8 100A MCCB Spare Spare 1 0 - 0 0.00 0.00 0.00
Sample office room
RYB9 16A TP 4X6.0 1x6.0 Exhaust Fan EXH.101---EXH.104 4 746 Ground Floor
2984 0.99 0.99 0.99
L.101---L.108
R10 6A SP 2X4.0 Light, Fan F.101
8 (L)+1(F) 18 (L)+80(F) Ground Floor 144(L) + 80(F) 0.22
B11 10A SP 2X4.0 1x4.0 Power Socket PS.101---PS.104 4 200 Ground Floor 800 0.80
Y12 10A SP 2X4.0 1x4.0 Sewing Machine SM.101---SM.106 6 400 Ground Floor 2400 2.40

Total Phase Load/KW= 77.38 77.32 74.59


Total Connected Load= 229.295 KW Page No-2

From SLD
SDB-03, LOCATION: WEST,LINE NO-01, 3rd FLOOR, FEED ROOM: DB-04, REF: RYB-01. page-9
Phase
Main Breaker MCB Earth Size Number of Phase Load in KW
CKT REF. Neutral Load Type Point Reference Watt Per Point Location Total Watt Remarks
Incoming Ckt. Rat/Amp (re) Points/Pcs
Size(rm) R Y B
West Side ,
B1 2A SP 2X2.5 Light L.325---L.335 11 18 198 0.198
Line no-1
R2 6A SP 2X4.0 1x4.0 Sewing Machine SM.347---SM.352 6 350 " 2100 2.1
B3 6A SP 2X4.0 1x4.0 Sewing Machine SM.353---SM.358 6 350 " 2100 2.1
MCB RYB4 6A TP 3X4.0 1x4.0 Exhaust Fan Exh.309---Exh.310 2 1125 " 2250 0.75 0.75 0.75

16A Y5 6A SP 2X4.0 1x4.0 Sewing Machine SM.359---SM.363 5 350 " 1750 1.75
Y6 2A SP 2X2.5 Light L.336---L.346 11 18 " 198 0.198
TP RYB7 6A TP 2X4.0 Ceiling Fan F.301-F.310
10
(R-3, Y-5, B-2)
70 " 700 0.21 0.35 0.14
Total Phase Load/KW= 3.06 3.048 3.188
Total Connected Load 9.296 KW Page No-17