The document discusses guidelines for treating DDB oil used in oil-impregnated paper bushings, including the treatment process, acceptance criteria for incoming and treated oil, and safety/quality precautions.

The oil treatment process (filtering, degassing) aims to remove particles of a given size and remove humidity and dissolved gases from the oil to maintain the dielectric performance of the bushings.

The acceptance criteria for incoming DDB oil include specifications for parameters like density, viscosity, dielectric dissipation factor, breakdown voltage, and flash point based on IEC and ASTM standards.

Sub-PL Bushings Quality

T&D Products

T&D Products ITR sub-PL Bushings Technical Standard TS - 002 DDB Oil: treatment and acceptance criteria
Applicable to :
(*) : list

sub-Product Line (*) Unit (*)

: Bushings : All

Date of effectivity : June 2009 Approvals


Authorised Approved Giacomo Scuderi Alberto Lecchi Paolo Cardano Prepared Mario Occhipinti Name Sub-PL Bushings Transfer of Technology RPV Quality Manager RPV Technical Manager RPV Process Specialist Function G. Scuderi A. Lecchi P. Cardano M. Occhipinti Signature 04/06/2009 04/06/2009 04/06/2009 04/06/2009 Date

This document and any information therein contained are proprietary and confidential and must not be distributed, published, or more generally disclosed for any purpose whatsoever. Effectivity of paper copy should be checked prior to use.

Property of AREVA T&D

T&D Products

Technical Standard n

TS - 002

DDB Oil: Treatment and Acceptance Criteria

Draft for Rev 0

Issued 04/06/09

1/5

Sub-PL Bushings Quality

T&D Products

Distribution list
Supporting Function / Product Lines / Units Sub-Product Line Units Function Bushings sub-PL head Managing Directors Quality Managers Production Managers Technical Managers

Content
Item 1. 2. 3. 4. 5. Description Application Background Incoming Material Oil Treatment Quality Control after treatment Page 3 3 4 5 5

Modification records
Date Revision Modification

04/06/09

First Issue

This document and any information therein contained are proprietary and confidential and must not be distributed, published, or more generally disclosed for any purpose whatsoever. Effectivity of paper copy should be checked prior to use.

Property of AREVA T&D

T&D Products

Technical Standard n

TS - 002

DDB Oil: Treatment and Acceptance Criteria

Draft for Rev 0

Issued 04/06/09

2/5

Sub-PL Bushings Quality

T&D Products

1.

Application This instruction provides guidelines on the DDB oil treatment and the relevant acceptance criteria. DDB oil is used for the Oil Impregnated Paper bushings (OIP). This instruction is applicable in all Units in AREVA T&D. The criteria specified shall be achieved by means of suitable equipment, which shall be defined, operated and maintained under the local Unit responsibility.

2.

Background The DDB oil used in OIP bushings is an insulating oil based on synthetic aromatic hydrocarbons. The dielectric performance of the OIP bushing is heavily impacted by the oil quality; besides the basic oil specific characteristics, the particle contents and the humidity content are the main factors to be controlled. The oil treatment process (filtering, degassing) has the purpose of removing the particles of a given size removing the humidity and the gas dissolved in the oil The machines and equipment to achieve such levels shall be properly designed and maintained.

____________________________________________________________
Safety precautions Operators shall be trained and authorized to operate on the equipment. They shall use / wear the necessary PPE, as defined by the local EHS policy. The equipment shall be under proper maintenance and condition. Environmental precautions Oil leakages shall be avoided. A suitable maintenance and verification program on the oil equipment shall be performed, to prevent possible oil leakages. Specific instructions and trained personnel shall be available. Quality precautions This activity requires that: equipment must be managed with a regular maintenance program. measuring instruments shall be calibrated. operators shall be qualified.

This document and any information therein contained are proprietary and confidential and must not be distributed, published, or more generally disclosed for any purpose whatsoever. Effectivity of paper copy should be checked prior to use.

Property of AREVA T&D

T&D Products

Technical Standard n

TS - 002

DDB Oil: Treatment and Acceptance Criteria

Draft for Rev 0

Issued 04/06/09

3/5

Sub-PL Bushings Quality

T&D Products

3.

Incoming material The general oil characteristics are specified by IEC 60867 Specification for unused insulating liquids based on synthetic aromatic hydrocarbons. The DDB oil shall be purchased only from approved suppliers; the technical specification is reported in Table 1.

Table 1: Specification of the DDB oil

The oil is supplied either in drums or as bulk material (from tank truck). The Supplier shall provide a Test Certificate for each delivery, where some minimum information shall be reported see Table 2.
DDB OIL ACCEPTANCE CRITERIA
Parameter Density @ 15C Kinematic Viscosity @ 40C DDF - Dielectric Dissipation Factor @ 90C (tanDelta) Volume resistivity @ 90 C Breakdown Voltage Flash Point Method min. ISO 12185 ASTM D1298 ISO 3104 ASTM D445 IEC 60247 ASTM D924 IEC 60093 ASTM D1169 IEC 60156 ISO 2719 ASTM D93 100 40 130 0,850 4 Criteria max. 0,880 4,5 210
-3

Unit kg/dm cSt T Ohm cm kV C


3

Table 2: Test Certificate parameters

This document and any information therein contained are proprietary and confidential and must not be distributed, published, or more generally disclosed for any purpose whatsoever. Effectivity of paper copy should be checked prior to use.

Property of AREVA T&D

T&D Products

Technical Standard n

TS - 002

DDB Oil: Treatment and Acceptance Criteria

Draft for Rev 0

Issued 04/06/09

4/5

Sub-PL Bushings Quality

T&D Products

The characteristics reported on the Certificate shall be verified on a sample basis; frequency of the sample measurements are decided locally, minimum every year; the measurements can be done either internally (if the local Unit has the necessary instruments) or by an authorized external laboratory.

4.

Oil treatment The incoming oil is normally stored in tanks, provided with a dehydrating breather. The oil treatment system provides the Unit with a suitable amount of treated oil, e.g. oil which can be used to feed the impregnation system. Such treated oil can be normally kept circulating in a closed loop, heated, filtered and under vacuum. Temperature: 50 to 60 C Vacuum: < 0,1 mbar

5.

Quality Control after treatment The treated oil can be used for impregnation if the criteria reported in Table 3 are met.

QUALITY CONTROL ON DDB OIL


Parameter Water content Breakdown voltage DDF - Dielectric Dissipation Factor @ 90C (tanDelta) Volume resistivity @ 90 C Method min. IEC 60814 IEC 60156 IEC 60247 ASTM D924 IEC 60093 ASTM D1169 100 70 210
-3

Criteria max. 7

Unit ppm kV T Ohm cm

Table 3: Quality Control parameters

This document and any information therein contained are proprietary and confidential and must not be distributed, published, or more generally disclosed for any purpose whatsoever. Effectivity of paper copy should be checked prior to use.

Property of AREVA T&D

T&D Products

Technical Standard n