Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
98 views8 pages

ES25 Basler - en

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 8

Model

www.basler.com ES-25
+1 618.654.2341 (USA) Description
info@basler.com
Sync-Check Relay

INTRODUCTION
ES-25 sync-check relays monitor two ac circuits and provide a contact output when the two circuits are
synchronized. Typical application of the ES-25 involves supervision of an automatic or manual circuit breaker
closing scheme. The ES-25 offers true sync-check protection by monitoring the phase displacement and voltage
difference between two sources of single, dual, or three phase systems.

Warning!

READ THIS MANUAL. Read this manual before installing or operating your
ES series relay. Note all warnings, cautions, and notes in this manual as well
as on the product. Failure to follow warning and cautionary labels may result in
personal injury or property damage. Exercise caution at all times.
It is the responsibility of the user to ensure that this product is installed,
operated, and used for its intended function in the manner specified by this
manual or any protection provided by this product may be impaired.

OPTIONAL CLOSURE ON DEAD BUS


In applications requiring a continuous supply of power, the optional dead bus function enables connection of the
generator to the load during a loss of bus voltage.

RELAY CONTROLS
ES-25 controls include an adjustment for the acceptable phase angle difference and an adjustment for the
acceptable voltage difference. The phase angle difference setting is expressed in degrees of rotation and the
voltage difference setting is expressed as a percentage of the relay’s nominal input voltage rating.

RELAY OUTPUT CONTACTS AND INDICATORS


ES-25 relays are equipped with output contacts and LED indicators. Two form-C output contacts can be used for
annunciation or control. The output contacts change state and the Relay LED lights when the two relay inputs are
within the acceptable synchronization range. A continuously lit Power LED indicates the presence of adequate
generator sensing voltage and a flashing Power LED indicates any relay fault detected by internal diagnostics.

SPECIAL SYMBOLS
Special symbols are located on the ratings label on your ES series relay. These symbols are illustrated and
described in Table 1.
Table 1. Special Symbol Descriptions
Symbol Description

Caution, Refer to Instructions

Caution, Risk of Electric Shock

Instructions
Publication Revision Date Copyright

9500100997 H Nov 2023 2023


SPECIFICATIONS
Inputs
All units are self-powered by input voltage on GEN terminals 1 and 2.
Nominal voltage: 120 Vac, 208 Vac, 240 Vac,
380 Vac, 415 Vac, or 480 Vac
(For other nominal voltages, contact Basler Electric.)
Voltage Input
Operating Range: +25%, −30% of nominal rating
Frequency: 50 or 60 Hz
Burden: <2.5 VA
Overload Withstand: 2 times nominal for 3 s
Setpoint
Voltage Difference: Adjustable 5 to 30% of nominal
Dropout (Reset): Setpoint ±1% of Vnom
Repeatability: ±2% or ±1 V (whichever is greater)
Angle Difference: Adjustable 1 to 20°
Dropout (Reset): 0.5°
Repeatability: ±1°
Slip Frequency: <0.5 Hz
Dead Bus Pickup: Fixed at 8% of nominal
Dropout (Reset): Fixed at 9% of nominal
Repeatability: ±2% or ±1 V (whichever is greater)
Operating Time: <100 ms
Outputs
Output contact trip performance is in accordance with IEEE Std C37.90™-2005 and IEC 60255-1
Contact Type: Two form-C contacts per protective function
Make and Carry for Tripping Duty
30 A, 250 Vdc for 0.2 seconds per IEEE Std C37.90-2005 - IEEE Standard for Relays and Relay Systems
Associated with Electric Power Apparatus; 7 A continuous ac or dc
Break Resistive or Inductive
0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)
Environment
Operating Temperature: –40 to 70°C (–40 to 158°F)
Storage Temperature: –40 to 85°C (–40 to 185°F)
Temperature Coefficient: 0.02% of nominal per °C (200 ppm/°C)
Relative Humidity: ≤95%, non-condensing
Ingress Protection: IP50 Case, IP20 Terminals
Pollution: Degree 1
Insulation: Class II
Overvoltage: Category III
Physical
Terminals
Type: Compression screw
Wire Size: 0.5-3.3 mm2/20-12 AWG
Screw Torque: 4.4 to 5.3 in-lb
(0.5 to 0.6 N•m)
Mounting (HxD): DIN rail 1.38 x 0.29 inches
(35 x 7.5 mm) complies with IEC 60715
Size (WxHxD)
All ES-25 models are supplied in a wide case.
Wide Case: 3.93 x 2.75 x 4.38 inches
(100 x 70 x 111 mm)

Instructions
Publication Revision Date Page

9500100997 H Aug 2023 2 of 8


Weight
Wide Case: 1.10 lb (0.50 kg)
Applicable Standards
IEC
IEC 60255-1 Measuring relays and protection equipment – Part 1: Common requirements (includes all
referenced/normative IEC standards)
IEEE
IEEE Std C37.90™-2005 – For Relays and Relay Systems Associated with Electric Power Apparatus
IEEE Std C37.90.1™-2012 – For Surge Withstand Capability (SWC) Tests for Relays and Relay Systems
Associated with Electric Power Apparatus
IEEE Std C37.90.2™-2004 – For Withstand Capability of Relay Systems to Radiated Electromagnetic
Interference from Transceivers
IEEE Std C37.90.3™-2001 – For Electrostatic Discharge Tests for Protective Relays
Agency Compliance
UL
This product is listed to applicable Canadian and US safety standards and requirements by UL.
• UL 508
• UL 94 V-0
• CSA C22.2 No. 0
• CSA C22.2 No. 14
CE and UKCA Compliance
This product has been evaluated and complies with the relevant essential requirements set forth by the EU
legislation and UK Parliament.
EU directives:
• Low Voltage Directive (LVD) 2014/35/EU
• Electromagnetic Compatibility (EMC) 2014/30/EU
• Hazardous Substances (RoHS 2) 2011/65/EU
Harmonized standards used for evaluation:
• EN 50178
• EN 50581
• EN 60255-1
• EN 60255-26
• EN 60255-27
• IEC 61000-6-4
China RoHS
The following table serves as the declaration of hazardous substances for China in accordance with PRC
standard SJ/T 11364-2014. The EFUP (Environment Friendly Use Period) for this product is 40 years.

PRODUCT: ES-25

有害物质
Hazardous Substances
六价铬 多溴联苯 多溴二苯醚
铅 汞 镉 Hexavalent Polybrominated Polybrominated
零件名称 Lead Mercury Cadmium Chromium Biphenyls Diphenyl Ethers
Part Name (Pb) (Hg) (Cd) (Cr6+) (PBB) (PBDE)
金属零件
O O O O O O
Metal parts
聚合物
O O O O O O
Polymers

电子产品
X O O O O O
Electronics

Instructions
Publication Revision Date Page

9500100997 H Aug 2023 3 of 8


PRODUCT: ES-25

有害物质
Hazardous Substances
六价铬 多溴联苯 多溴二苯醚
铅 汞 镉 Hexavalent Polybrominated Polybrominated
零件名称 Lead Mercury Cadmium Chromium Biphenyls Diphenyl Ethers
Part Name (Pb) (Hg) (Cd) (Cr6+) (PBB) (PBDE)

电缆和互连配件
Cables & X O O O O O
interconnect
accessories

绝缘材料
O O O O O O
Insulation material

本表格依据 SJ/T11364 的规定编制。


O: 表示该有害物质在该部件所有均质材料中的含量均在 GB/T 26572 规定的限量要求以下。
X: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572 规定的限量要求。
This form was prepared according to the provisions of standard SJ/T11364.
O: Indicates that the hazardous substance content in all homogenous materials of this part is below the limit specified in standard
GB/T 26252.
X: Indicates that the hazardous substance content in at least one of the homogenous materials of this part exceeds the limit
specified in standard GB/T 26572.

OPERATION
ES-25 sync-check relays monitor two ac circuits and provide a contact output when the two circuits are
synchronized. Synchronization protection in the ES-25 relay is adjusted by controls marked Set (%V) and
Set (Deg). ES-25 relays are powered by input voltage on GEN terminals 1 and 2.
Set (%V) Control
The ES-25 Set (%V) control adjusts the synchronization voltage difference from 5 to 30% of the nominal input.
Set (Deg) Control
The ES-25 Set (Deg) control adjusts the synchronization voltage phase displacement from 1 to 20°.
Synchronization
When the voltage difference and phase displacement between the two sources are within the ranges established
by the Set (%V) and Set (Deg) controls, and the slip frequency is less than 0.5 Hz, synchronization occurs. This
condition energizes the relay output and lights the green Relay LED.
Close on Dead Bus Option
ES-25 relays with the Close On Dead Bus option (style 1xA1N1N0) allow a generator to energize a dead bus
when the monitored bus voltage is less than 8% of the nominal input.
Setting Example
An ES-25 relay with a nominal input rating of 120 Vac has the following settings:
• Set (%V) – 20%
• Set (Deg) – 10°
If the bus voltage is fixed at 120 Vac, the generator voltage must be between 96 Vac and 144 Vac, the phase
angles of the bus and generator voltage must be within 10° of each other, and the frequencies of the bus and
generator must be within 0.5 Hz for synchronization to occur.
Dropout due to voltage difference will occur if the difference between sensed bus and generator voltage
magnitudes increases above the 20% setpoint by 1% of nominal. Therefore, dropout occurs when the voltage
difference rises above 25.2 Vac.
120 Vnom (20% + 1%) = 25.2 Vac
Dropout due to phase angle difference will occur if the difference between sensed bus and generator voltage
phase angles increases above the 10° setpoint by more than 0.5°. Therefore, dropout occurs when the phase
angle difference rises above 10.5°.
When dropout occurs, the relay is de-energized and the green Relay LED extinguishes.

Instructions
Publication Revision Date Page

9500100997 H Aug 2023 4 of 8


INSTALLATION

Caution
Before commissioning, check the equipment ratings, operating instructions,
and installation instructions.

ES relays should be installed in a dry location where the ambient temperature remains within the operating
temperature range.
ES sync-check relays mount on standard DIN rails that comply with IEC 60715. Mounting involves hooking the
top edge of the cutout on the base of the case over one edge of the DIN rail. The opposite side of the cutout
containing the release clip is then pushed over the opposite side of the DIN rail. To remove or reposition the relay,
pull the release clip downward and move the relay as required. Figure 1 shows the dimensions of the ES-25 relay.
Relay connections should be made using wire that meets applicable codes and is properly sized for the
application. Figure 2 shows the sensing connections for the ES-25 relay.

Figure 1. Relay Dimensions

Note
When contact outputs are used to apply dc control voltage to inductive
windings, such as relay coils, a flyback diode in parallel with the
winding is recommended for EMI suppression. Failure to add such
EMI suppression can result in circuit damage.

Figure 2. ES-25 Sync-Check Relay Sensing Connections

Instructions
Publication Revision Date Page

9500100997 H Aug 2023 5 of 8


CALIBRATION
The calibration marks on the faceplate are provided only as guides. Proper calibration requires using an accurate
meter to monitor the voltage. Use the following procedure to calibrate your relay.
1. Adjust the Set (%V) and Set (Deg) controls fully counterclockwise (CCW).
2. Apply nominal voltage to the BUS and GEN terminals. These voltages must be in phase and have the same
frequency.
3. Adjust the voltage applied to the GEN terminals to the maximum or minimum level for synchronization.
4. Adjust the Set (%V) control clockwise (CW) until the relay energizes.
5. Apply nominal voltage to the BUS and GEN terminals. These voltages must be in phase and have the same
frequency.
6. Adjust the phase angle of the GEN voltage to the maximum or minimum synchronization angle.
7. Adjust the Set (Deg) CW until the relay energizes.

MAINTENANCE
ES relays require no maintenance. In the event that your relay requires repair, contact Basler Electric, Highland,
IL, USA for return authorization.

ORDERING INFORMATION
Figure 3 shows the ES style number identification chart.
Mounting accessories (DIN rails and DIN rail end stops) are available from Basler Electric. Table 2 lists the part
numbers for ordering.
Table 2. Mounting Accessories
Mounting Accessories Basler Part Number
DIN Rail, 3.0 inches (76 mm) wide 9323900001
DIN Rail, 5.5 inches (140 mm) wide 9323900002
DIN Rail, 8.0 inches (203 mm) wide 9323900003
DIN Rail, 39.4 inches (1,000 mm) wide 17366
DIN Rail End Stops 31761

Instructions
Publication Revision Date Page

9500100997 H Aug 2023 6 of 8


Figure 3. ES-25 Style Number Identification Chart

This device utilizes redistributable software code copyrighted by Freescale Semiconductor, Inc. The following copyright notice and
disclaimer are provided in this publication as required by the conditions for redistribution.
Copyright: 1997 - 2014 Freescale Semiconductor, Inc. All Rights Reserved.
Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are
met:
• Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.
• Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the
documentation and/or other materials provided with the distribution.
• Neither the name of Freescale Semiconductor, Inc. nor the names of its contributors may be used to endorse or promote products
derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND CONTRIBUTORS "AS IS" AND ANY EXPRESS OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE COPYRIGHT HOLDER OR CONTRIBUTORS BE LIABLE FOR
ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR
TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF
ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

Instructions
Publication Revision Date Page

9500100997 H Aug 2023 7 of 8


Instructions
Publication Revision Date Page

9500100997 H Aug 2023 8 of 8

You might also like