Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Tse 14 04 PM 2600 Plsa D El DTL 00003

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTES

1. THIS DRAWING IS THE COPYRIGHT OF SALFO KSA & PLANET OVERSEAS CONSULTANTS AND
MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE ABOVE CONSULTANT'S
AUTHORITY.
COVER 2. DO NOT SCALE FROM THE DRAWINGS.
3. ALL DIMENSIONS AND LEVELS ARE IN METRES UNLESS NOTED OTHERWISE. ALL DIMENSIONS
TO BE VERIFIED ON SITE & APPROVED BY THE ENGINEER.
HOLD DOWN CLAMP 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT
1 ARCHITECTURAL, STRUCTURAL,MECHANICAL, ELECTRICAL AND CIVIL DRAWINGS AND ALL
CANTILEVER BRACKET
- RELEVANT SECTIONS OF THE SPECIFICATIONS.
SPLICE PLATE

HEX BOLT, NUT & FLAT


FLAT PLATE WASHER (M8x20)
COVER

TRAY

U-CLAMP PLATE

1 EARTH BAR INSTALLATION DETAIL WITH DUAL INCOMERS 2 COVER STRIP CLAMP 3 TYPICAL SMOKE AND HEAT DETECTOR INSTALLATION
- NTS - - NTS
NTS

LEGEND

900
320mm
245mm METALLIC TAPE CLIP SIMILAR TO FURSE (CP210-H)
25 X 3mm BARE COPPER TAPE AT EVERY 1000mm INTERVAL
MULTI POINT

210mm
135mm
1m/2m AIR ROD
160mm PARAPET
SPU-GF-01

AIR TERMINAL BASE


ROOF

Ø32mm CDP H/L


NON METALLIC DC TAPE CLIP(SIMILAR TO FURSE-CP050-H) CONDENSATE DRAIN PAN
AT AN INTERVAL OF 500 MM MTR APART

EXT.WALL

PVC COVERED COPPER TAPE (TC125/50)


USED AS DOWN CONDUCTOR RUNNING OUT
SIDE WALL

4 WALL GALVANIZED STEEL PERFORATED CABLE TRAY INSTALLATION 5 CONCRETE INSPECTION PIT
- - NTS
NTS

CONDENSING UNIT
GROUND FLOOR

5HOLE EARTH BAR


USED AS TEST LINK
REFERENCE DOCUMENTS
50x50x6mm ANGLE DOCUMENT TITLE DOCUMENT NR
INSPECTION PIT
(FOR LOCK)
FURSE
ELECTRICAL CONNECTION LAYOUT - PM2600 TSE-14-04-PM-2600-PLSA-D-EL-LAY-00001...00028
DISCONNECTING LINK STUD POWER SINGLE LINE DIAGRAM - PM2600 TSE-14-04-PM-2600-PLSA-D-EL-SLD-00001...00008
INSULATOR 50x50x6mm ANGLE
PVC COVERED COPPER CLAMP GENERAL INSTALLATION DETAIL - PM2600 TSE-14-04-PM-2600-PLSA-D-EL-DTL-00001...00002
TAPE (TC125/50) RUNNING
1CX70mm2 Y/G CABLE M12 CHEMICAL
TO PIT
GROUNDING TERMINAL TO BE CONNECTED TO
EARTHING LOOP ANCHOR BOLT
KEYMAP
SOLID COPPER EARTH ROD
17.2X3000mm

SPIKE N
MOUNTING BASE

8 TYPICAL DOWN CONDUCTOR DETAILS LIGHTNING PROTECTION 9 SPLIT UNIT INSTALLATION DETAIL
- NTS - NTS

6 EARTH BAR WITH TWO DISCONNECT LINK 7 SURFACE MOUNTED LUMINAIRE INSTALLATION
- NTS - NTS

00 29/07/24 DETAILED DESIGN MR MA MP


REV DATE ISSUE, SCOPE OF REVISION PREP. CHECKED APPR.
CLIENT:

ROYAL COMMISSION FOR RIYADH CITY


Green Riyadh Project, Saudi Arabia

PROJECT:
TSE SUPPLY FOR GREEN RIYADH PROGRAMME
CONSTRUCTION OF TSE NETWORK FOR GREEN RIYADH PPROGRAMME
Preliminary Design of TSE LOT4 - PM
PROJECT MANAGEMENT CONSULTANT:

ILF CONSULTING ENGINEERS SAUDI ARABIA


PRINCE MUHAMMAD BIN ABDULAZIZ ROAD, OLAYA DISTRICT, BUILDING NO. 3074
OLAYA TOWERS, TOWER B, 11TH FLOOR. RIYADH 11433, SAUDI ARABIA

ENGINEERING CONTRACTOR:

DRAWING TITLE:
DETAILED DESIGN OF PM2600
TYPICAL INSTALLATION DETALS

10 PANEL BOARD-SURFACE MOUNTED 11 TYPICAL MOUNTING OF RECEPTACLE OUTLET 12 TYPICAL MOUNTING OF LIGHTING SWITCHES 13 FIRE EXTINGUISHER - WALL MOUNTED
- NTS - NTS
- NTS - NTS SCALE: PROJECT: DOCUMENT NUMBER: REV: SHEET

NTS 12021 TSE-14-04-PM-2600-PLSA-D-EL-DTL-00003 00 01 OF 01