Fenwall Series35-72
Fenwall Series35-72
Fenwall Series35-72
35.72.01
APPLICATIONS
Construction Heaters n Ceramic Infrared Heaters n Black Body Infrared Heaters n Commercial Cooking Equipment n Any 120 VAC Gas Burner Application under 400K BTU
n
DESCRIPTION
The 35-72 is a 120 VAC direct spark ignition control for controlling a gas valve and igniting LP or natural gas on heating equipment that provides a 120 VAC operating voltage. The microprocessor circuit design provides precise, repeatable timing sequences for ignition times, purge times (pre- and inter-) along with multiple tries for ignition and flame sensing during pre-purge. Agency Certifications
Design certified by CSA International to CAN C22.2 #199-M89 and ANSI Z21.20 for Automatic Ignition Systems
Designed, developed and manufactured by Fenwal, these components integrate seamlessly providing maximum system performance.
www.fenwalcontrols.com
1-800-FENWAL-1
Page 1
Lockout Recovery
For lockout recovery, reset the thermostat below ambient temperature or remove the 120 VAC power supply for 5 seconds.
* The pre-purge is simply a delay to allow gas to dissipate from the combustion chamber. This control is not equipped with a combustion blower relay and therefore does not initiate a fan powered pre-purge.
Page 2 Series 35-72, 120 VAC Direct Spark Ignition Control www.fenwalcontrols.com 1-800-FENWAL-1
Terminal Designations
DESCRIPTION TERMINAL Single Spark and Sense
B. Gnd V1 L2 L1 Not Used V2 Burner Ground Valve Power Line Neutral 120 Vac Input (Hot) Valve Neutral
WIRE COLOR
Purple Brown White Black Yellow
#
!
S1
CAUTION:
Label all wires prior to disconnection when servicing the control. Wiring errors can cause improper and dangerous operation. A functional checkout of a replacement is recommended.
SPECIFICATIONS
Input Power
Input Current Drain Gas Valve Rating Operating Temperature Flame Sense Voltage Flame Sense Current Flame Failure Response Time Type of Gases Spark Rate Moisture Resistance
SIX PIN HEADER AMP PART NUMBER 644615-6 ON CIRCUIT BOARD. SEE PAGE 6 FOR MATCHING CONNECTORS AND WIRING HARNESSES.
102 to 138 VAC, 50/60 Hz 50mA @ 120 VAC, 60 Hz 1.5A @ 120 VAC -40F to +175F, -40C to +80C 45% of line voltage 1.0 microamp minimum 0.8 seconds maximum Natural, LP and manufactured Line frequency (50/60 Hz) Conformal coated to operate to 95% R.H. Potted to operate up to 100% R.H. See drawing on back page for details Integral stand-offs: 2.3 oz Potted: 6.1 oz
Size (LxWxH)
REMOTE SENSE
#
!
Weight
WARNING:
Operation outside specifications could result in failure of the Fenwal product and other equipment with injury or death to people and damage to property.
TROUBLESHOOTING GUIDE
Symptom
Control will not start up
Recommended Actions
A. Check wiring B. No voltage @ pin 4, check thermostat C. Check fuse/circuit breaker D. Faulty control, consult Fenwal A. Shorted electrode - re-establish 1/8 gap B. High voltage cable is disconnected C. Check wiring A. Valve coil open B. Valve wire disconnected C. Faulty control, check voltage @ pin 2 A. Check electrode position B. Check high voltage wire and connection C. Poor ground @ pin 1 D. Check flame current E. Check remote sensor wire on pin 7
Gas Valve on and no spark through TFI Spark on and gas valve off
SIX PIN HEADER AMP PART NUMBER 64415-7 ON CIRCUIT BOARD. SEE PAGE 6 FOR MATCHING CONNECTORS AND WIRING HARNESSES.
Flame during trial for ignition but no flame sense after trial for ignition
www.fenwalcontrols.com
1-800-FENWAL-1
Page 3
ACCESSORIES
Proper Electrode Location
Proper location of the electrode assembly is important for optimum system performance. It is recommended that the electrode assembly be mounted temporarily using clamps or other suitable means to check the system before permanently mounting the assembly. The electrode assembly should be located so that the tips are inside the flame envelope and about 1/2 inch (10 mm) above the base of the flame. See Figures 3a and 3b.
Figure 4a
#
!
CAUTIONS:
Ceramic insulators should not be in or close to the flame. Electrodes should have a gap spacing of 0.125 0.031 inch (3.12 0.81 mm). If this spacing is not correct, the assembly must be replaced. Exceeding the temperature limits can cause nuisance lockouts and premature electrode failure. Electrodes must be placed where they are not exposed to the appliance user in normal operation.
1. 2.
FLAME CURRENT CHECK: REMOTE SENSE To measure flame current, disconnect input voltage, then insert a 0-50 Micro Ampheres DC meter inline with flame sense wire per Figure 4b. Reconnect input voltage and initiate call for heat. After sparking is complete and flame is established meter should read 1.0 Micro Ampheres or higher while flame is established. If meter reads below "0" on the scale, meter leads are reversed. Disconnect power and reconnect meter leads for proper polarity. Figure 4b
3. 4.
Flame Sensing
Flame sensing is achieved using the principal of flame rectification. Flame rectification relies on current passing from ground through the flame to the sense rod. The minimum flame current necessary to keep the system from lockout is 1.0 Micro Ampheres DC. SINGLE SPARK AND SENSE Figure 3a
ITEM DESCRIPTION #
1 2 3 4 5 6 7 8 9
STANDARD MATERIAL
CSA rated at 1800F
FLAME CURRENT CHECK: SINGLE SPARK & SENSE To measure flame current, disconnect input voltage, then insert a 0-5 Micro Amphere DC meter and capacitor in series with the spark electrode per Figure 4a. Reconnect input voltage and initiate call for heat. After sparking is complete and flame is established meter should read 1.0 Micro Ampheres or higher while flame is established. If meter reads below "0" on the scale, meter leads are reversed. Disconnect power and reconnect meter leads for proper polarity.
Steel Cu Flashed Mounting Bracket Nickel Plated Steel 1/4 Q.C. High Voltage Terminal Nickel Plated Steel 3/16 Q.C. Flame Sense Terminal L-3 Steatite Spark, H.V. Ceramic Tube Sense Electrode Ceramic Tube L-3 Steatite Spring Steel Press Ring Kanthal D Flame Sense Electrode Kanthal D Ground Rod Spark Electrode, High Voltage Kanthal D
Steel Cu Flashed Nickel Plated Steel Nickel Plated Steel Alumina Alumina Spring Steel Kanthal APM Kanthal APM Kanthal APM
Page 4
www.fenwalcontrols.com
1-800-FENWAL-1
Electrode Assemblies
Providing over 1,000 configurations of spark electrodes and flame sense rods, Fenwal has a design for almost any application. The latest state-of-the-art wire forming and assembly equipment is used to accurately and efficiently produce high quality electrodes that deliver the hottest spark. The "Universal" electrodes depicted below are just a sampling of the 1,000 electrode styles available. These electrodes are designed for on-site customization. Cut and bend these to fit your application and then send the formed electrode back for Fenwal to detail or send us a print and we will provide you with a quote and samples. SPARK ELECTRODE WITH INTEGRAL REMOTE FLAME SENSE ROD
Part Number: 22-100000-593
www.fenwalcontrols.com
1-800-FENWAL-1
Page 5
To make your own harness select AMP connector housing P/N: 770849-6 and AMP housing terminal P/N: 770552-1
REMOTE SENSE
Part Number: 05-129893-0XX Part Number: 05-129893-1XX
1/4 FEMALE Q.C. FULLY INSULATED
To make your own harness select AMP connector housing P/N: 770849-7 and AMP housing terminal P/N: 770552-1
Page 6
www.fenwalcontrols.com
1-800-FENWAL-1
1. SILICONE RUBBER SUPRESSION TYPE: Resistive carbon coated fiberglass core prevents spark energy radiation from interfering with
other electronic systems. Select this wire type for applications where wire lengths are less than 36 and noise is a major concern.
SPECIFICATIONS: Voltage Rating 25 KVDC Agency Rating SAE J2031 Temperature Rating 200C (392F) Diameter 7mm (.27) Jacket Material Silicone Rubber over Fiberglass Braid
1/4 FEMALE Q.C. WITH SILICONE RUBBER BOOT RIGHT ANGLE SPARK PLUG WITH SILICONE RUBBER BOOT RIGHT ANGLE SPARK PLUG WITH SILICONE RUBBER BOOT
2. SILICONE RUBBER COPPER CONDUCTOR TYPE: Low resistance copper conductor transmits maximum spark energy. Select this
type when maximum energy or longer wire lengths are required and noise is not a major concern.
SPECIFICATIONS: Voltage Rating 25 KVDC Agency Rating UL Type 3257 Temperature Rating 250C (482F) Diameter 7mm (.27) Jacket Material Silicone Rubber
Part Number: 05-125948-0XX
3. TEFLON INSULATED TYPE: Low resistance copper conductor transmits maximum spark energy. Select this type for applications that have tight clearances and sharp bend radii.
SPECIFICATIONS: Voltage Rating 25 KVDC Agency Rating UL Type 1911 Temperature Rating 250C (482F) Diameter 2mm (.08) Jacket Material Teflon
www.fenwalcontrols.com
1-800-FENWAL-1
Page 7
HOW TO ORDER
Enclosure Configurations and Wiring Options 2 = Potted 4 = Integral Stand-offs
35 - 72 5 X 0 X - X X X
Trial for Ignition Time (TFI) (Figure 1) (Figure 2) Pre-Purge Time 0 = None 1 = 15 seconds 2 = 25 seconds 5 = 5 seconds Number of Ignition Trials, Flame Sense Method and Lock Out Reset Method 0 = 1 try, single spark and sense 1 = 1 try, remote sense 5 = 3 try, single spark and sense 6 = 3 try, remote sense Thermostat / power off reset Thermostat / power off reset Thermostat / power off reset Thermostat / power off reset
Inter-Purge Time 0 = None 1 = 15 seconds 2 = 25 seconds
or
Assemblies 8 = Assemblies (may consist of control, high voltage ignition wire, electrode and harness)
or
Non-Standard Configurations 9 = Non Standard Configuration A 9 in this location of the part number (i.e. 35-725 901 -113) identifies this configuration as a non-standard design. The part number does not follow the part numbering system. The 9XX is a sequential part number assigned by Fenwal. Consult factory for operating characteristics of this control.
MOST COMMON CONFIGURATIONS Fenwal offers any option variation listed in the above part number scheme along with customized configurations to meet your exact application requirements. Because of the numerous options available, models not listed in the table below are made to order. For quick-ship samples and quick-ship orders, please select a model from the table below.
Ignition Control Part Number Enclosure Type
Stand-Off 35-725200-501 35-725205-115 35-725400-501 35-725405-115 35-725201-501 35-725206-115 35-725401-501 35-725406-115 Potted
l l l l
Wiring
Multi-Pin
l l l l
Remote
15
30
10
15
l l l l
POTTED
Part Number: 35-72520X-XXX
INTEGRAL STAND-OFF
Part Number: 35-72540X-XXX
Figure 1
Figure 2
400 MAIN STREET, ASHLAND, MA 01721 TEL: (508) 881-2000 FAX: (508) 881-6729 www.fenwalcontrols.com
These instructions do not purport to cover all the details or variations in the equipment described, nor do they provide for every possible contingency to be met in connection with installation, operation and maintenance. All specifications subject to change without notice. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchasers purposes, the matter should be referred to KIDDE-FENWAL, Inc., Ashland, Massachusetts.
2001 Kidde-Fenwal
Printed in U.S.A.
CP
P/N 35.72.01
Rev AA 4/30/01
Page 8
www.fenwalcontrols.com