SERIES 35-53: Features
SERIES 35-53: Features
SERIES 35-53: Features
FEATURES
Optional combustion blower relay with selectable postpurge
System diagnostic LED indicator
Multiple tries for ignition (TFI)
Automatic reset 1 hour after lockout
Custom TFI, prepurge and interpurge timings
Remote or local flame sensing
Software conforms to UL 1998 requirements
Safe start
Heavy conformal coating
APPLICATIONS
Recreational Vehicles (including boats/marine)
Infrared Paving Repair Equipment
Outdoor Torches and Lanterns
Battery Powered Furnaces & Appliances
SPECIFICATIONS
Design certified to ANSI Z21.20-1998 and CAN/CSA C22.2 Tries for Ignition One or three try versions available
No. 199-M89 - Report # C2180012 Trial for Ignition Period 5.0, 7.0, 10.0, or 25.0 seconds available
/SENSE
pre-purge delay. After the pre-purge delay the gas valve is energized and
sparks commence for the trial for ignition period.
When flame is detected during the trial for ignition, sparking stops and
the gas valve remains energized. The thermostat, airflow switch and main
burner flame are constantly monitored to assure that the system continues
to operate properly. When the thermostat is satisfied and the demand
WARNING: The 35-53 uses voltages of shock hazard potential.
for heat ends, the main valve is de-energized immediately, and after the Wiring and initial operation must be done by a qualified service technician.
post-purge period the blower is turned off.
attempt. The control will attempt two additional ignition trials before BLO * Blower 1/4 Q.C. Terminal - -
going into lockout after which the valve relay will remain de-energized AIR * Airflow Switch 6 Pin Edge Connector 1 Red
and the blower will turn off after a five minute delay. TH * Thermostat 6 Pin Edge Connector 2 Orange
SINGLE TRIAL MODEL NC NC Contact 6 Pin Edge Connector 3 Blue
Should the main burner fail to light, or flame is not detected during V1 Gas Valve 6 Pin Edge Connector 4 Brown
the trial for ignition period, the control will go into lockout. The valve TEST/SENSE Local Sense Unused 5 -
will be turned off immediately and the blower will turn off after a five Remote Sense 6 Pin Edge Connector 5 Black
minute delay.
GND Ground 6 Pin Edge Connector 6 Yellow
Recovery from lockout requires a manual reset by either resetting the
thermostat or removing 12 volt power for a period of 5 seconds. * Air terminal provides +12 VDC power for models without
blower control DWR, BLO and TH terminals are not used.
If the thermostat is still calling for heat after one hour the control will
automatically reset and attempt to ignite the burner again. CAUTION: Label all wires prior to disconnection when servicing
the control. Wiring errors can cause improper and dangerous operation.
Flame Failure A functional checkout of a replacement is recommended.
If the established flame signal is lost while the burner is operating, the WARNING: Operation outside specifications could result in failure
control will respond within 0.8 seconds. On re-cycle models, the gas of the Fenwal product and other equipment with injury or death to
valve is de-energized and a new interpurge and TFI sequence will people and damage to property.
begin. On optional re-ignition models, the gas valve will stay energized
and the HV spark will be energized for a trial for ignition period to TROUBLESHOOTING GUIDE
attempt to relight the burner. If the burner does not light the control will
de-energize the gas valve. Multi-try models will make two more SYMPTOM RECOMMENDED ACTIONS
1. Dead A. Miswired
attempts to relight the burner. If the burner does not relight the control
B. Transformer/battery bad
will go into lockout as noted above in "Failure to light. If flame is C. Fuse/circuit breaker bad
re-established, normal operation resumes. D. No voltage @ PWR or AIR
E. Bad control
Combustion Airflow Problems A. Miswired or failed air flow switch
2. Thermostat on -
No blower output B. Bad thermostat no voltage @ TH
If the airflow signal is lost, or the hi-limit opens during heat mode, the
C. Bad control
gas valve is immediately de-energized and the blower stays on. If the 3. Airflow Switch input okay
switch closes again, a normal ignition sequence will resume. If not and A. Miswired
but no trial for ignition
this condition persists for more than five minutes, the control will enter after purge delay B. Bad control
lockout with the blower off. A. Shorted electrode
4. Valve on, no spark B. Open HV cable
MOUNTING AND WIRING C. Miswired
D. Bad control
The 35-53 is not position sensitive and can be mounted vertically A. Valve coil open
or horizontally. The control may be mounted on any surface and B. Open valve wire
5. Spark on, no valve C. Bad control
fastened with #6 sheet metal screws. Secure the control in an area
that will experience a minimum of vibration and remain below the (check voltage between V1 & GND)
maximum ambient temperature of 80C (175F). A. Bad electrode
6. Flame okay during TFI, B. Bad HV wire
no flame sense (after TFI) C. Poor ground at burner
D. Bad control (check flame current)
ELECTRODE ASSEMBLIES
With over 1,000 configurations of spark electrodes and flame sense rods,
Fenwal has a design for almost any application. The latest state-of-the-art
wire forming and assembly equipment is used to accurately and efficiently
produce high quality electrodes that deliver the hottest spark. The
"Universal" electrodes depicted below are just a sampling of the 1,000
electrode styles available. These electrodes are designed for on-site
customization. Cut and bend these to fit your application and then send
the formed electrode back for Fenwal to detail or send us a print and
will provide you with a quote and samples.
REMOTE SENSE WITH BLOWER RELAY REMOTE SENSE WITHOUT BLOWER RELAY
DIMENSIONS
CASE AND COVER INTEGRAL STAND-OFF
Figure 1: Figure 2:
CONTROL CONFIGURATION
35 - 53 X XXX -XXX Description
Blower Relay Trial for Ignition Time (TFI)
0 = None 1 = 5 seconds 3 = 7 seconds
5 = Combustion Blower Relay 5 = 10 seconds 7 = 25 seconds
Configurations Inter-Purge Time
5 = Standard Model, Recycle on Flame Loss 0 = None 1 = 15 seconds
8 = Aftermarket Kit (may consist of control, high voltage 3 = 25 seconds
ignition wire,electrode and harness) Pre-Purge Time
9 = Non Standard Configuration 0 = None 3 = 25 seconds
1 = 15 seconds
A 9 in this location of the part number (i.e. 35-53 5 901 -113)
identifies this configuration as a non-standard design. The Number of Ignition Trials
and Flame Sense Method
part number does not follow the part numbering system.
0 = 1 try, local sense
The 9XX is a sequential part number assigned by Fenwal.
1 = 1 try, remote sense
Consult factory for operating characteristics of this control.
5 = 3 tries, local sense
6 = 3 tries, remote sense
Enclosure Configurations and Wiring Options
0 = Covered Module
5 = Integral Standoffs
400 MAIN STREET, ASHLAND, MA 01721 These instructions do not purport to cover all the details or variations in the equipment described, nor do they
TEL: (508) 881-2000 FAX: (508) 881-6729 provide for every possible contingency to be met in connection with installation, operation and maintenance.
www.fenwalcontrols.com All specifications are subject to change without notice. Should further information be desired or should
particular problems arise which are not covered sufficiently for the purchasers purposes, the matter should
2008 Kidde-Fenwal Printed in U.S.A. TAG be referred to KIDDE-FENWAL, Inc., Ashland, Massachusetts.
P/N 35.53.02 3/21/05