Sequence Cont. Manual PDF
Sequence Cont. Manual PDF
Sequence Cont. Manual PDF
535e/08/96
INTRODUCTION
The flame signal current indicator consists of a five stage 4. Mounting and Electrical Installation
LED display which shows the signal current continuously.
An indication of the strength of the flame signal current is At the base:
therefore always given. Fluctuations in the monitoring - 3 earth terminals, with an additional tag for the burner
sensitivity can be noticed at an early stage, earth.
and appropriate corrective action can be - 3 neutral terminals, with a fixed internal through connection
taken. to the neutral input, terminal 8.
If the infra-red flicker detector IRD 820 or - 2 separate slide-in plates and 4 fixed, threaded knockouts
920 is employed, the flame signal current (PG 11 thread) as well as a wiring opening from below, to
indicator on the control box is not facilitate wiring of the base.
relevant. In this case, the IRD - A keyed fit ensures that the wrong control box type cannot
indicator is the decisive indication be fitted to the base. The corresponding control box
of flame signal strength. designation is shown in lettering on the base.
Flame signal current indicator
General:
- Can be mounted in any position, insulated as per IP 44
2. Burner Control standard (unaffected by water spray). The control box and
detector probes should not however be subjected to
- Burners can be operated with or without post-purge. excessive vibration. With the UVZ 780 ultra-violet sensor,
This varies according to model (see technical data) care should be taken to ensure that a good electrical
and is activated when the burner motor is connected to contact to the burner exists via the metal flange.
terminal 19. - If an ionisation electrode is used, appropriate protective
- Air damper operation is monitored to ensure the nominal measures are required in order to avoid contact with the
air volume during pre-purge and in the starting position electrode while installation work is being carried out.
before fuel is released. If confirmation of the damper Trouble-free operation with this type of flame detection is
positions "MIN" and "MAX" is not received, the control not possible if a voltage of over 25 volts is measured
box start sequence is interrupted. between neutral and earth. In this case, provision must be
- The air proving switch is checked for corrrect operation made for a separate isolating transformer.
before the start, and air pressure is monitored during pre- - The maximum lengths for the detector probe cables,
purge as well as during normal operation. In normal use, depending on the type of cable installed, are listed in the
switch contacts with a rating of 6A/220V are sufficient. technical data and must be adhered to without fail. Laying
Additional switch contacts which are to be monitored can the cables parallel to mains cabling over long distances
be connected between terminal 18 and the air proving should be avoided, and the use of multiple core cable is
TMG 740-3
switch working contact. In this case, jumper II on the also not permitted.
underside of the control box should be cut.
2
WIRING DIAGRAMS IRD CONNECTION
blue Kl. 8
IRD 1020 black Kl. 1
brown Kl. 20
Ph 220/240V ~
max. 10A rapid
6A slow GW
HS RT
ST
GLT
4 19 3 20 1 2 5 6 21 13 14 15 16 17 18 12 9 10 11 7 8
IS
M M1 PV V1 LW SA
IRD
R
Z UV SV V2
N
Program-
display
Start
blue
blue
orange
Sz SV yellow Sz PV
red
Sz V1
green
Betrieb
black
4 19 3 20 1 2 5 6 21 13 14 15 16 17 18 12 9 10 Terminal No.
TMG 740-3
3
COMMISSIONING AND MAINTENANCE 2. Routine Checks
BLUE beginning doesn’t start - no power, break in control circuit, air proving switch not in
resting position
continuous ventilation - end switch "MAX" air damper doesn’t operate
line lockout - air proving switch doesn’t switch over or is too late
end continuous ventilation - end switch "ignition position", air damper doesn’t operate
anywhere lockout - stray light
RED end lockout - no flame signal current or too weak after end of second
safety interval (double fuel feed burner)
GREEN end lockout - loss of flame during operation, air pressure too low
BLACK end lockout - stray light due to burning on, UVZ sensor tube reached end
of life and activates shutoff, defect in flame detector circuit
A test baseplate is available for checking the burner control box functions (model designation UP 7520, item no. 18601)
TMG 740-3
4
BURNER 1- OR 2-STAGE
Ph 220/240V ~
max. 10A rapid
GW
6A slow
HS RT
ST
GLT
4 19 3 20 1 2 5 6 21 13 14 15 16 17 18 12 9 10 11 7 8
IS
M M1 V1 LW SA
IRD
R
Z UV V2
N
Ph 220/240V ~
max. 10A rapid GW
6A slow
HS RT
ST
GLT
4 19 3 20 1 2 5 6 21 13 14 15 16 17 18 12 9 10 11 7 8
IS
M M1 LW SA
IRD V1
R
Z UV SV V2
N
2 NOZZLE BURNER
Ph 220/240V ~
max. 10A rapid
GW
6A slow
HS RT
ST
GLT
4 19 3 20 1 2 5 6 21 13 14 15 16 17 18 12 9 10 11 7 8
IS
M M1 PV V1 LW SA
IRD
R
TMG 740-3
Z UV V2
N
5
SCHEMATIC DIAGRAMM
10A
PH ts 1
GAS ST AIR
HS ts 3
RT
20 9 10 17 18 16 ts 2
I rm1
A
II
B
rs1 13 C
D
G1 14 E
NTC1 - G rm2
RM F
+ C2 C
3 G
RF 18 2 H
L N 15 I
1 5
B R5 R6 K
7 8 E A F
rf3 L
16
9 M
R1 R2 rs2 D rf1 P rm3 N
S O
P
12 I
D1 Q
rf2 K M r t
C1 bl blau or gb rot gn sw
10 R3 R4 Sy
11 17
O M ts1 = Pilot valve safety interval
SA
R
RS
Q
ts2 = Start valve safety interval
ts3 = Main valve 1 safety interval
1 7 11 8 21 5 6 2 19 14 15 4 12 13 3
max.
min.
max.
UV SA GL
IS LM
R M I = cut for monitoring of the iguition spork
V2 SV V1 PV M BM M BM Z
N
II = cut for additional switch contacts
PG 11
138
42 96
75
25
30.5
ø22
102
26
102
r 40
51
22
30
4
8
28
102
80
51
36 10
M4 48
ORDERING INFORMATION
ITEM DESIGNATION ITEM NO.
Burner control box Type TMG 740-3 Mod. 32-32 08211
Socket Socket TMG 70205
Insert plate PG-plate 70502
optional Cable entry plate 70501
Flame detector UVZ 780 white 18814
or UVZ 780 blue 18812
or UVZ 780 red 18813
Flame detector IRD 820 16201
Flame detector IRD 1020 end-on viewing 16522
Flame detector IRD 1020 side-on left 16523
Flame detector IRD 1020 side-on right 16521
IRD mounting flange IRD Holder M93 59093
Flame detector cable 3-wire, 0.6 m 7236001
The above ordering information refers to the standard version.
Special versions are also included in our product range. Specifications subject to change without notice.