Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Surge

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Technical data sheet

Surge protective device for data and information technology

Series protection device, 4-pole, 24 V version

MDP... D-24-T-10: Lightning barrier with test function; 24 V version

• Nominal load current 10 A


• Protection device for multi-wire systems
• Direct shield earthing and screwless connection terminals
• Space-saving width of just 8.7 mm
• Protection circuit testable with Life Control
• High bandwidth to 100 MHz
• UL-listed (4DG1)

Application: Universal use on 35 mm DIN profile rail in any standard distribution housing.
Type Highest Highest Number Connec- Pack. Weight Item No.
continuous continuous of poles tion pcs kg/100 pcs.
voltage voltage system
AC DC
Dimensions V V
MDP-4 D-24-T-10 20 28 4 Terminal 1 7,200 5098433

Connection options MDP-4 D-24-T-10


Maximum continuous voltage AC V UC 20
Maximum continuous voltage DC V UC 28
Category Type 1+2+3 / D1+C2+C1
Lightning protection zone LPZ 0→3
Number of poles 4
Rated current A IL 10
Series resistance per wire —
Impulse durability wire-wire C1: 0,5 kV / 0,25 kA (8/20µs)
Total discharge current (8/20) kA 10
Total discharge current (10/350) kA D1: 2
Protection level wire-wire V <70
Protection level wire-earth V <800
Frequency range 0 - 100 MHz
Temperature range °C ϑ -40-+80
Installation type DIN rail
Connection system Terminal
Protection rating IP20
Shielding connection available Yes
Shield connection Direct
Connection cross-section, flexible mm² 0,14-2,5
Connection cross-section, multi-wire mm² 0,14-1,5
Connection cross-section rigid mm² 0,14-2,5
Earthing via: DIN rail
Testing standard IEC 61643-21
Approvals UL

1 OBO | 6/2018