DATA SHEET Revision: 3

36994_ds Date: 09.02.2021


Doc. number: 172-X01675-144-47-ES-004 Comp.: DD
Page 1 of 4 Appr.: CD

EXCITATION
TRANSFORMER
DATA SHEET

ABB
ABB Switzerland Ltd.

Certified
19-Feb-2021

IA,IAPI,4200 Adrian Borboa

Customer: ABB Switzerland

Project: Collahuasi P172 Quinto Molino

Product: Excitation transformer

Performed technical standard: IEC

Sr. n°.: 36994

Tag. n°: 144-ML-1022-XF4

Revision n° Revision note Date: Comp.:


0 First issue 13.11.2020 GD
1 Updated after comments 09.12.2020 GD
2 Updated after comments 21.01.2021 DD
3 Updated after comments 09.02.2021 DD

C:\mdm_arealocale\36994_ds.doc/
DATA SHEET Revision: 3
36994_ds Date: 09.02.2021
Doc. number: 172-X01675-144-47-ES-004 Comp.: DD
Page 2 of 4 Appr.: CD

Transformer’s characteristics
Manufacturer Specialtrasfo S.p.A
Place of manufacturing Agrate Brianza (MB) - Italy
Type Oil-immersed excitation transformers
Construction Type Conservator type
Tank enclosure/material Bolted cover / Carbon steel painted
Rated power at design air temperature 640 kVA
Rated frequency 50 Hz (±2.4Hz)
Number of phases 3
Windings Primary Side Delta
Windings Secondary Side star
Vector group Dy5
Primary Side voltage 3450 V
Secondary Side voltage (off load) 800 V
Primary Side current 107.1 A
Secondary Side current 462 A
No load losses 1300 W
On load losses 7500 W @75°C
Impedance voltage 4% at 640kVA
Duty cycle Continuous operation at 485,2 A secondary current;
505 A, 6x 30 s per hour
Sound pressure level ≤ 62 dB(A) @ 1m
Winding material Copper
Cooling method KNAN – Class A
Installation Indoor
Altitude @4400masl
Ambient temperature -15°C / +40 °C
Area Classification Safe Area
Design life 25 years
Painting color RAL 5017
Painting schedule & color C4 - ISO12944-5 (2018)

C:\mdm_arealocale\36994_ds.doc/
DATA SHEET Revision: 3
36994_ds Date: 09.02.2021
Doc. number: 172-X01675-144-47-ES-004 Comp.: DD
Page 3 of 4 Appr.: CD

Insulation
Insulation method Oil
Oil type Silicon oil
Insulation class A
Average winding temperature rise @4400masl 55 °K
Top oil temperature rise @4400masl 50 °K
Average winding temperature rise @sea level 46 °K
Top oil temperature rise @sea level 41 °K

Primary Side: @4400masl


Highest system voltage 3.6 kV
AC power frequency withstands voltage 10 kV
Lightning impulse withstand voltage 40 kV
Bushing type Porcelain type class 12/28/75kV creepage 295mm
HV Cable box (material & IP) with bottom cable entry - Carbon Steel/IP65
- Non magnetic gland plate (undrilled) and top cable
entry (cable glands not scope of supply)

Secondary Side: @4400masl


Highest system voltage 1.1 kV
AC power frequency withstands voltage 3 kV
Lightning impulse withstand voltage -
Bushing type Porcelain type class 3.6/10/40; creepage 90mm
LV Cable box (material & IP) with bottom cable entry - Carbon Steel/IP65
- Non magnetic gland plate (undrilled) and top cable
entry (cable glands not scope of supply)

Auxiliary Terminal Box: IP65


Cable entry: bottom

Painting: C4 – ISO 12944-5 (2018)


NDFT: 120÷160 µm (approx.)
Final color: RAL 5017

C:\mdm_arealocale\36994_ds.doc/
DATA SHEET Revision: 3
36994_ds Date: 09.02.2021
Doc. number: 172-X01675-144-47-ES-004 Comp.: DD
Page 4 of 4 Appr.: CD

Instrumentation
• no. 3 primary porcelain bushings on transformer cover
• no. 4 surge arresters (Neptune configuration) Rated voltage: 3.75 kV, MCOV: 3 kV, Creepage
distance: 380 mm, Brand: Raychem. (TBC)
• no. 3 secondary porcelain bushings on transformer cover
• IP65 HV/LV cable boxes with non magnetic gland plate supplied undrilled and either top cable entry (cable
glands not scope of supply)
• Copper bars and bushing plate silver plated
• Electrostatic screen between primary and secondaries
• Cooling fins (corrugated tank)
• Oil conservator fitted with filling cap and drain valve
• Oil level gauge with low and max level alarm contact
• Silica gel breather
• Buchholz relay with 2NC alarm and 2NC trip contacts fitted with shut-off butterfly valves
• Dial-type top-oil thermometer with 2 NO/NC alarm and trip 2NO/NC contacts
• no.1 thermal image for primary winding temperature indication with 2 NO/NC alarm and trip 2NO/NC
contacts equipped with PT100 for remote connection
• no.1 PT100 for top oil for remote connection
• Pressure relief valve with 2NC trip contact
• IP 65 terminal box for auxiliary circuits
• Bi-directional rollers (flanged wheel type)
• no. 2 earthing terminals for main tank (located on opposite sides)
• Set of drain, oil treatment (lower+upper) and sampling valves
• Set of lifting lugs (for core and coils and for complete unit), jacking pads and hauling eyes
• Thermometer pocket
• no.1 diagram-type rating plate in English and Spanish

Dimensions (approx)
l 2300 mm
w 2100 mm
h 2100 mm

Weights (approx)
Oil weight 850 kg
Total weight 3600 kg

C:\mdm_arealocale\36994_ds.doc/