Automatic Transfer Switch: Owner's Manual
Automatic Transfer Switch: Owner's Manual
Automatic Transfer Switch: Owner's Manual
Owners Manual
ATS Service Entrance HS Type Transfer Switch Models: 005036-0, 100 Amp, 250 Volts and 004945-1, 200 Amp, 250 Volts
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be
Also read the instructions and information on install, operate or service this equipment.the transfer switch. Replace any decal or labeltags, decals, and labels that may be affixed to that SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to shall be by means of suitable electric system utilityutility distribution system whentransfer equipment so as to isolate theLegally Required from the generator is operating (Article 701 DANGER! Connection of a generator to an electrical system normally supplied by an electric Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these means may result in damage to generator and may result in injury or death to utility workers due to backfeed of electrical energy. Generac Power Systems, Inc., hereafter referred to as the manufacturer, cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique chosen does not render the transfer switch unsafe. Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows: Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows: out important safety infor This symbol points followed, could endanger mation that, if not personal safety and/or property.
This symbol points out potential explosion hazard. This symbol points out potential fire hazard. This symbol points out potential electrical shock
hazard.
GENERAL HAZARDS
Any AC generator that is used for backup power if a NORMAL (UTILITY) power source failure occurs, must be isolated from the NORMAL (UTILITY) power source by means of an approved transfer switch. Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers, due to backfeed of electrical energy. Improper or unauthorized installation, operation, service or repair of the equipment is extremely dangerous and may result in death, serious personal injury, or damage to equipment and/or personal property. Extremely high and dangerous power voltages are present inside an installed transfer switch. Any contact with high voltage terminals, contacts or wires will result in extremely hazardous, and possibly LETHAL, electric shock. DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF .
DANGER
After this heading, read instructions that, if not strictly complied with, will result in personal injury, including without limitation, death, or property damage.
After this heading, read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property. NOTE: After this heading, read explanatory statements that require special emphasis. These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Table of Contents
Competent, qualified personnel should install, operate and service this equipment. Adhere strictly to local, state and national electrical and building codes. When using this equipment, comply with regulations the National Electrical Code (NEC), CSA Standard; C22.1 Canadian Electric Code and Occupational Safety and Health Administration (OSHA) have established. Never handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT. Jewelry conducts electricity and wearing it may cause dangerous electrical shock. Remove all jewelry (such as rings, watches, bracelets, etc.) before working on this equipment. If work must be done on this equipment while standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats. Never work on this equipment while physically or mentally fatigued. Keep the transfer switch enclosure door closed and bolted at all times. Only qualified personnel should be permitted access to the switch interior. In case of an accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor but AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help. When an automatic transfer switch is installed for a standby generator set, the generator engine may crank and start at any time without warning. To avoid possible injury that might be caused by such sudden start-ups, the systems automatic start circuit must be disabled before working on or around the generator or transfer switch. For that purpose, a SAFETY DISCONNECT is provided inside the transfer switch. Always set that switch to its OFF position before working on the equipment. Then place a DO NOT OPERATE tag on the transfer switch and on the generator. Remove the Negative (Neg) or () battery cable.
Section 3 Operation.......................................................4
3.1 Functional Tests & Adjustments .............................. 4 3.2 Manual Operation .................................................... 4 3.2.1 Close to Normal Source Side ........................ 5 3.2.2 Close to Emergency Source Side ................... 5 3.2.3 Return to Normal Source Side ...................... 5 3.3 Voltage Checks......................................................... 6 3.4 Generator Tests Under Load ................................... 6
4 5 6 7 8
Installation Diagram ....................................7 Electrical Data ...............................................8 Exploded Views & Parts Lists ..................12 Notes .............................................................16 Warranty ...................................... Back Cover
For authorized service, reference the dealer locator number found in the generator owners manual.
1
1.1
INTRODUCTION
This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect application, or improper procedures. Every effort has been expended to make sure that the contents of this manual are both accurate and current. The manufacturer, however, reserves the right to change, alter or otherwise improve the product at any time without prior notice.
1.2
EQUIPMENT DESCRIPTION
LOAD LUGS (T1 & T2)
The automatic transfer switch is used for transferring electrical load from a UTILITY (NORMAL) power source to an EMERGENCY (STANDBY) power source. Such a transfer of electrical loads occurs automatically when the UTILITY power source has failed or is substantially reduced and the EMERGENCY source voltage and frequency have reached an acceptable level. The transfer switch prevents electrical feedback between two different power sources (such as the UTILITY and EMERGENCY sources) and, for that reason, codes require it in all standby electric system installations. The transfer switch consists of a transfer mechanism, service disconnect circuit breaker, a relay control, fuses, and a terminal strip for connection of sensing wires. This transfer switch is suitable for use as service entrance equipment.
This transfer switch is for use in optional standby systems only. This transfer switch is suitable for use on a circuit capable of 10,000 rms symmetrical amperes, 240 VAC maximum.
This transfer switch is suitable for control of motors, electric discharge lamps, tungsten filament and electric heating equipment where the sum of motor full load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of the switch rating.
2
1.3
A DATA DECAL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA DECAL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property.
Section 2 Installation
GTS HS Type Transfer Switch
When requesting information or ordering parts for this equipment, make sure to include all information from the DATA DECAL. Record the Model and Serial numbers in the space provided below for future reference.
2.3
MOUNTING
Mounting dimensions for the transfer switch enclosure are in this manual. Enclosures are typically wall-mounted. See Installation Diagram, Section 5.
MODEL # SERIAL #
install Handle transfer switches carefully when switch ing. Do not drop the switch. Protect the against impact at all times, and against construction grit and metal chips. Never install a transfer switch that has been damaged. This transfer switch is mounted in a NEMA 3R enclosure. It can be mounted outside or inside and should be based on the layout of installation, convenience and proximity to the utility supply and load center. Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit.
1.4
The standard switch enclosure is a National Electrical Manufacturers Association (NEMA) 3R type. NEMA 3R type enclosures primarily provide a degree of protection against falling rain and sleet and is undamaged by the formation of ice on the enclosure.
1.5
Before installing, operating or servicing this equipment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all SAFETY RULES to prevent accidents and/or damage to the equipment. The manufacturer recommends that a copy of the SAFETY RULES are posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equipment. Two publications that outline the safe use of transfer switches are the following: NFPA 70; National Electrical Code UL 1008, STANDARD FOR SAFETY-AUTOMATIC TRANSFER SWITCHES
2.4
Make sure to turn OFF both the UTILITY power (NORMAL) and EMERGENCY ( STANDBY)
supplies before trying to connect power source and load lines to the transfer switch. Supply voltages are extremely high and dangerous. Contact with such high voltage power supply lines causes extremely hazardous, possibly lethal, electrical shock. Wiring diagrams and electrical schematics are provided in this manual. Two suggested installation methods are shown. One for new installations and/or retrofit and one for retrofit. NOTE: All installations must comply with national, state and local codes. It is the responsibility of the installer to perform an installation that will pass the final electrical inspection. The utility supply connection is made at the circuit breaker terminals. The generator supply and customer load connections are made at the transfer switch mechanism, inside the switch enclosure.
2.1
INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the factory. Installing the switch includes the following procedures: Mounting the enclosure. Connecting power source and load leads. Connecting the generator sensing and transfer relay circuits. Connecting any auxiliary contact (if needed) Testing functions.
2.2
UNPACKING
Carefully unpack the transfer switch. Inspect closely for any damage that might have occurred during shipment. The purchaser must file with the carrier any claims for loss or damage incurred while in transit. Check that all packing material is completely removed from the switch prior to installation.
Section 3 Operation
ATS HS Type Transfer Switch
Conductor sizes must be adequate to handle the maximum current to which they will be subjected to, based on the 75C column of tables, charts, etc. used to size conductors. The installation must comply fully with all applicable codes, standards and regulations. Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire brush. All power cables must enter the enclosure through the knockouts. If not using the knockouts, entry must be at or below knockouts. If ALUMINUM conductors are used, apply corrosion inhibitor to conductors. Tighten terminal lugs to the torque values as noted in Section 1.2.2, and on the decal located on the inside of the door. After tightening terminal lugs, carefully wipe away any excess corrosion inhibitor.
NOTE: When this ATS is used with an air-cooled generator, the LOAD 1 and LOAD 2 wires are not used.
3.1
Following transfer switch installation and interconnection, inspect the entire installation carefully. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regulations. When absolutely certain the installation is proper and correct, complete a functional test of the system.
torque wrench to tighten the conduc Use abeing sure not to overtighten, or damage tors, to the switch base could occur. If not tightened enough, a loose connection would result, causing excess heat which could damage the switch base. Connect power source load conductors to clearly marked transfer mechanism terminal lugs as follows 1. Connect UTILITY (NORMAL) power source cables to circuit breaker. 2. Connect EMERGENCY (STANDBY) source power cables to transfer switch terminals E1, E2. 3. Connect customer LOAD leads to switch terminals T1, T2. Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes. Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.
Performinfunctional tests in the exact order presented this manual, or damage could be done
to the switch. IMPORTANT: Before proceeding with functional tests, read and make sure all instructions and information in this section are understood. Also read the information and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.
3.2
MANUAL OPERATION
DANGER
load. Do NOT manually transfer underall power sourcDisconnect transfer switch from es by approved means, such as the main circuit breaker(s). A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows: 1. Turn the generators AUTO/OFF/MANUAL switch to OFF . 2. Turn OFF both UTILITY (service disconnect circuit breaker) and EMERGENCY (generator main line to circuit breaker) power supplies to the transfer switch. 3. Turn the GENERATOR DISCONNECT SWITCH to the OFF position. 4. Note position of transfer mechanism main contacts by observing the moveable contact carrier arm. This can be viewed through the long narrow slot in the inside cover of the ATS. The top of the moveable contact carrier arm is yellow to be easily identified. Manual operation handle in the UP position LOAD terminals (T1, T2) are connected to UTILITY terminals (N1, N2).
2.5
Control system interconnections consist of N1 and N2, T1 and T2, and leads 23 and 194. Control system interconnection leads must be run in a conduit that is separate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:
MAXIMUM WIRE LENGTH 460 feet (140m) 461 to 730 feet (223m) 731 to 1,160 feet (354m) 1,160 to 1,850 feet (565m)
4
RECOMMENDED WIRE SIZE No. 18 AWG. No. 16 AWG. No. 14 AWG. No. 12 AWG.
Section 3 Operation
ATS HS Type Transfer Switch
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
the Do not use excessive force when operatingbe transfer switch manually or damage could done to the manual handle.
Section 3 Operation
ATS HS Type Transfer Switch
3.3
VOLTAGE CHECKS
NOTE: Do NOT proceed until generator AC output voltage and frequency are correct and within stated limits. If the no-load voltage is correct but no-load frequency is incorrect, the engine governed speed may require adjustment. If no-load frequency is correct but voltage is not, the voltage regulator may require adjustment.
1. Turn ON the UTILITY power supply to the transfer switch using the service disconnect circuit breaker.
DANGER
PROCEED WITH CAUTION. THE TRANSFER SWITCH IS NOW ELECTRICALLY HOT. CONTACT
2. WITH LIVE TERMINALS RESULTS IN EXTREMELY HAZARDOUS AND POSSIBLY FATAL ELECTRICAL SHOCK. With an accurate AC voltmeter, check for correct voltage. Measure across ATS terminal lugs N1 and N2. Also check N1 to NEUTRAL and N2 to NEUTRAL. When certain that UTILITY supply voltage is correct and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL position. The generator should crank and start. Let the generator stabilize and warm up at noload for at least five minutes. Turn the GENERATOR DISCONNECT SWITCH to the ON position. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position.
3.4
3.
4. 5. 6. 7.
DANGER
WITH CAUTION. PROCEEDVOLTAGE IS NOW GENERATOR OUTPUT BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK. 8. With an accurate AC voltmeter and frequency meter, check the no-load, voltage and frequency. Measure across ATS terminal lugs E1 to E2. Also check E1 to NEUTRAL and E2 to NEUTRAL.
a. b. c. d. Frequency ....................................... 60-62 Hertz Terminals E1 to E2 ........................ 240-246 VAC Terminals E1 to NEUTRAL............. 120-123 VAC Terminals E2 to NEUTRAL............. 120-123 VAC
9. Set the generators main circuit breaker (CB1) to its OFF or OPEN position. 10. Set the AUTO/OFF/MANUAL switch to the OFF position to shut down the generator.
1. Set the generator's main circuit breaker to its OFF or OPEN position. 2. Manually actuate the transfer switch main contacts to their EMERGENCY (STANDBY) position. Refer to Manual Operation (Section 3.2). 3. To start the generator, set the AUTO/OFF/ MANUAL switch to MANUAL. When engine starts, let it stabilize for a few minutes. 4. Turn the generator's main circuit breaker to its ON or CLOSED position. The generator now powers all LOAD circuits. Check generator operation under load as follows: Turn ON electrical loads to the full rated wattage/amperage capacity of the generator. DO NOT OVERLOAD. With maximum rated load applied, check voltage and frequency across transfer switch terminals E1 and E2. Voltage should be greater than 230VAC and frequency should be greater than 59 Hertz. Let the generator run under rated load for at least 30 minutes. With unit running, listen for unusual noises, vibration, overheating, etc., that might indicate a problem. 5. When checkout under load is complete, set main circuit breaker of the generator to its OFF or OPEN position. 6. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO/ OFF/MANUAL switch to its OFF position. 7. Move the switch's main contacts back to their UTILITY position. For example, LOAD connected to UTILITY power supply. Refer to Manual Operation (Section 3.2). Handle and operating lever of transfer switch should be in UP position. 8. Turn on the utility power supply to transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads. 9. Set the generator's AUTO/OFF/MANUAL switch to its AUTO position. 10. Set the GENERATOR DISCONNECT SWITCH to the ON position. The system is now set for fully automatic operation.
271mm[10.67"]
26.5mm[1.04"]
0A6599tv
0A6599tv
597mm[23.50"]
561mm[22.09"
34mm[1.34"]
179.5mm[7.07"] KNOCKOUT SUITABLE FOR 1", 1-1/4", 1-1/2" CONDUIT SIZE 3 PLACES
KNOCKOUT SUITABLE FOR 3/4" & 1" CONDUIT SIZE KNOCKOUT SUITABLE FOR 1", 1-1/4", 1-1/2" CONDUIT SIZE 324mm[12.76"]
8
IF ATS IS USED AS SERVICE ENTRANCE DEVICE A BONDING JUMPER WILL NEED TO BE INSTALLED SIZED TO MEET NATIONAL & LOCAL CODES.
T2 E1
NOTE: INSTALLATION TO BE DONE BY A LICENSED ELECTRICIAN AND MUST MEET ALL NATIONAL, STATE AND LOCAL ELECTRICAL CODES.
GROUND BAR
22 33
11 44
E1
E2
GROUND BAR
N1 N2
DISCONNECT BONDING CONNECTION IN PANELBOARD *-WIRES T1 & T2 NOT USED ON AIR COOLED UNITS AND SOME LIQUID COOLED UNITS
194
NEUTRAL BAR
IF ATS IS USED AS SERVICE ENTRANCE DEVICE A BONDING JUMPER WILL NEED TO BE INSTALLED SIZED TO MEET NATIONAL & LOCAL CODES.
E2 T2 E1
NOTE: INSTALLATION TO BE DONE BY A LICENSED ELECTRICIAN AND MUST MEET ALL NATIONAL, STATE AND LOCAL ELECTRICAL CODES.
22 33
11 44
E1
E2
N1 N2 T1 * T2 * 23 194
*-WIRES T1 & T2 NOT USED ON AIR COOLED UNITS AND SOME LIQUID COOLED UNITS
NEUTRAL BAR
RETROFIT
GROUND BAR
PANELBOARD
10
11
HCTIWS GNITAR
22473-S 1-4X20STL
22473-S 1-4X20STL
YLBMESSA LENAP LORTNOC HTIW ESU ROF SI HCTIWS A1425E0# RO 7110E0# R0 0448D0# RO 6201C0# REPPOC ROF ELBATIUS ERA SGUL SLANIMRET LLA GNITAR c 57 TSAEL TA FO ERIW MUNIMUULA RO
.IW ,AHSEKUAW
REBMUN LAIRES
REBMUN LEDOM
EGATLOV METSYS
Replace with UL listed fuse of same type and rating 600 Volt, 5 amp.
0D3587
A
SWITCH LEVER
52
A
TERM. XB2 TERM. XB1
63378-T
53
B
D2806-T 30A, 600V
E1 B B
63378-T
21 11 12
63378-T 63378-T
31 1
47822-T
E-05884
NEUTRAL
(OPTIONAL)
WARNING
CUSTOMER CONNECTIONS
0A6599tv 0A6599tv
8 14
22473-S 1-4X20STL
22473-S 1-4X20STL
P/N 0A2595
B 13
36
9
TERMINAL TIGHTENING TORQUE 45 INCH-POUNDS
34 28 !
35
DECAL DETAILS VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED (NOT TO SCALE) 24 7 19
DETAIL "A"
34
0E9999
0E3485
9 35
40 41 42 29
ENCLOSURE
DETAIL A
0E3484
23
49
63378-T
63378-T
12
50 17 ! 6 44 32 22
0A6599tv 0A6599tv 0A6599tv 0A6599tv
0C4449A-RS 0A9457
19 26 11 12 31
DETAIL A-A
(POWER TERMINAL LUG ASSY)
NOTE: TIGHTEN ITEM #43: 24-30 IN/LBS
48
18 27 !
TERM. XA2 SWITCH XA TERM. XA3
63378-T
TERM. XA1
44
A
SWITCH LEVER TERM. XB3 SWITCH XB
46 43
54
DETAIL B-B
51
NOTE: ASSEMBLE SENSING WIRE RING TERMINALS SO CLEARANCE IS GIVEN FOR ACCESS TO LOWER LUG SCREWS.
LISTED
R
US
5
64NL
30 8 37 37 38
QTY. 2 ITEM #37's BELOW SUBPLATE QTY. 1 ITEM #37 ABOVE SUBPLATE 4 PLACES
20
INSIDE OF COVER
0C8308
45
18
PART NO.
0C2237 0E7886H 0E7890 0E9906 063378 0D3728 0E9999 049813 0E6523 063617 0D2806 073590A 047822 0A1661 0C4449 090388 0E1473 0E9907 0E1477 0F0668 0E3070 0E9734 0E3484 0E3485 067210A 0A9457 0D3587 0A2595 0F0776 081221 045764 074908 066849B 0C3992 026579 0E7213 022473 022097 0E9987 0E6193 064526 0E6155 036933 077033 0C8308 022152 0912970085 0912970086 095282 0F2710 066849 0E6303 0E6303A 0E6303C
QTY.
1 1 1 1 8 1 1 4 1 1 2 4 1 2 1 2 1 1 1 1 1 REF 1 1 1 1 1 1 1 1 6 2 2 2 2 2 8 4 1 1 2 1 6 6 1 6 1 1 1 1 4 1 1 1
DESCRIPTION
TRANSFER SW-HSB 100A 2P 250V CB 0100A 2P 240V S BQ2 LB BRKT CB MTG BACK BRACKET, DISCONNECT SWITCH 100A HOLDER, CABLE TIE SWITCH TOG SPST 15A @ 125V DECAL SERVICE DISCONNECT SWITCH NUT HEX M6 X 1.0 G8 YEL CHR GROUND BAR (5)4-14 AWG CONN RELAY PNL 12VDC DPDT 10A@240VA FUSEBLOCK 30A 600V 2POS W/SQ FUSE 5A X BUSS BLOCK TERM 20A 7 X 6 X 1100V RIVET POP .156 X .675 AL ASSY-NTRL BL 150-200A SCREW HHTT M6-1.0 X 12 ZINC WELDMENT TRANSFER SWITCH BOX COVER INSIDE XFER SWITCH BOX COVER TRANSFER SWITCH BOX DECALTRANSFER SWITCH SUBPLT XFER SW HSB DECAL SWITCH RATING DECAL WARN MANUAL OPER HANDLE DECAL SERVICE DISCONNECT DECAL GROUND LUG (NOT SHOWN) DECAL NEUTRAL DECAL FUSE REPLACEMENT DECAL TERMINAL STRIP DECAL TEST SEQ. 2P TS HS 3R DECAL-UL LIST HSB SCREW HHTT M4-0.7 X 8 BP SCREW HHTT M5-0.8 X 10 BP SCREW HHTT M5-0.8 X 8 BP SCREW HHTT M4-0.7 X 16 BP WASHER SHAKEPROOF EXT #8 STEEL SCREW THUMB 1/4-20 X 1/2 W/SHLD WASHER FLAT 1/4-M6 ZINC WASHER LOCK M6-1/4 WIRE HARNESS HSB (NOT SHOWN) BRACKET ARM EXTENDER SCREW HWHS #6-25 X 3/8 ZNC ARM EXTENDER PIN SCREW PPHM #10-32 X 3/8 LUG SLDLSS 1/0-#14X9/16 AL/CU DECAL TERMINAL SHOCK HAZARD WASHER LOCK #10 WIRE ASSY 2AWG 100A 2-P T/S N1A WIRE ASSY 2AWG 100A 2-P T/S N2A DECAL LIVE-CIRCUIT DECAL XFER SWITCH DATA SE 100A SCREW HHTT M5-0.8 X 16 WIRE A WIRE B WIRE E1
*** SUPPLIED WITH WIRE HARNESS ITEM #39 ** SUPPLIED WITH TRANSFER SWITCH (ITEM #1)
13
16
15
31 2 3
55
17 52 19
OR ALUUMINUM WIRE OF AT LEAST 75 c RATING ALL TERMINALS LUGS ARE SUITABLE FOR COPPER #0C1026 OR #0D8440 0R #0E0117 OR #0E5241A SWITCH IS FOR USE WITH CONTROL PANEL ASSEMBLY WAUKESHA, WI. GENERAC POWER SYSTEMS, INC.
53
26
0C4449A-T
0A6599tv 0A6599tv
33
NOTE:LOCATE HOLE IN BUSBAR UNDER BALL END OF SCREW TIGHTENING TORQUE 250 IN-LBS
120/240
22473-S 1-4X20STL
22473-S 1-4X20STL
0F2712
0C4449A-RS
0A9457
SYSTEM VOLTAGE
MODEL NUMBER
SERIAL NUMBER
22
10 11 12 31 46 7 27 18
Replace with UL listed fuse of same type and rating 600 Volt, 5 amp. 0D3587
63378-T
31
4
D2806-E 30A, 600V
22097-S 1/4 STL 1-4X20STL 22473-S
37
38
43
A
UTILITY (C1 & VR1)
56 5 6 6 38 38 44
TORQUE ITEM #6 TO 72 IN-LBS.
47 1
D2806-T 30A, 600V
63378-T
45
21
30A, 600V D2806-S
E1
30
B
63378-T 63378-T 63378-T 63378-T
11
48850-E
12
31
47822-T
50
LISTED
R
C
NOTE WIRE ORIENTATION
US
WARNING
NEUTRAL
(OPTIONAL)
64NL
P/N 0A2595
32
22097-S 1/4 STL 22473-S 1-4X20STL 22473-S 1-4X20STL
CUSTOMER CONNECTIONS
0A6599tv 0A6599tv 0A6599tv
32 36
37
37
38
QTY. 2 ITEM #37's BELOW SUBPLATE QTY. 1 ITEM #37 ABOVE SUBPLATE 4 PLACES
9 43 38 8 37 7
34
35 13 28 14 48
DETAIL "A"
DECAL DETAILS VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED (NOT TO SCALE) 24
S-37422 LTS02X4-1
BUSBAR SWITCH
19
51 34
0E9999
40
41
42 29
INSIDE OF COVER
35
ENCLOSURE
DETAIL A
(GROUND LUG ASSEMBLY)
0E3484
23
0C8308
54
49
18
14
ITEM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 * 43 * 44 * 45 * 46 47 48 49 50 51 52 53 54 55 56
PART NO.
0D9618 0E3628 0E3664 0E3553 0E3375 0F1252 036656 022127 0E6523 063617 0D2806 073590A 047822 0A1661 0C4449A 090388 0E1473 0E9989 0E1477 0F0668 0E3070 0E3477 0E3484 0E3485 067210A 0A9457 0D3587 0A2595 0E7109 063378 045764 049813 074908 0C3992 026579 0E7213 022473 022097 0E9987 0E6193 064526 0E6155 0E6032 0E6033 0E6034 0E6303 0E6303A 0E6303B 0C8308 081221 0E9999 0E9988 0D3728 095282 0F2712 066849
QTY.
1 1 1 2 4 4 2 2 1 1 2 4 1 2 1 2 1 1 1 1 1 REF 1 1 1 1 1 1 1 8 8 5 2 2 2 2 14 10 1 1 2 1 2 2 2 1 1 1 1 1 1 1 1 1 1 5
DESCRIPTION
TRANSFER SW-HSB 200A 2P 250V CIRCUIT BREAKER 0200A 2P 120/240V S QN BASE QN CIRCUIT BREAKER BUSBAR 200A HSB XFER SW LUG SLDLSS 250-#6 AL/CU SCREW BHSC 1/4-20 X 3/8 SCREW SHC 1/4-20 X 1 G8.8 NZ NUT HEX 1/4-20 STEEL GROUND BAR (5)4-14 AWG CONN RELAY PNL 12VDC DPDT 10A@240VA FUSEBLOCK 30A 600V 2POS W/SQ FUSE 5A X BUSS BLOCK TERM 20A 7 X 6 X 1100V RIVET POP .156 X .675 AL ASSY-NTRL BL150-200A SCREW HHTT M6-1.0 X 12 ZINC WELDMENT TRANSFER SWITCH BOX COVER INSIDE XFER SWITCH BOX COVER TRANSFER SWITCH BOX DECALTRANSFER SWITCH SUBPLT XFER SW HSB DECAL SWITCH RATING DECAL WARN MANUAL OPER HANDLE DECAL SERVICE DISCONNECT DECAL GROUND LUG (NOT SHOWN) DECAL NEUTRAL DECAL FUSE REPLACEMENT DECAL TERMINAL STRIP DECAL TEST SEQ.2P TS HS 3R HOLDER CABLE TIE SCREW HHTT M4-0.7 X 8 BP NUT HEX M6 X 1.0 G8 YEL CHR SCREW HHTT M5-0.8 X 10 BP SCREW HHTT M4-0.7 X 16 BP WASHER SHAKEPROOF EXT #8 STEEL SCREW THUMB 1/4-20 X 1/2 W/SHLD WASHER FLAT 1/4-M6 ZINC WASHER LOCK M6-1/4 WIRE HARNESS HSB (NOT SHOWN) BRACKET ARM EXTENDER SCREW HWHS #6-25 X 3/8 ARM EXTENDER PIN 90 DEGREE UP SPADE CONNECTOR 90 DEGREE DN SPADE CONNECTOR STRAIGHT SPADE CONNECTOR WIRE A WIRE B WIRE E1 DECAL TERMINAL SHOCK HAZARD DECAL-UL LIST HSB DECAL-SERVICE DISCONNECT SWITCH BRACKET SERVICE SWITCH TOBBLE SWITCH, SERVICE DECAL LIVE-CIRCUIT DECAL XFER SWITCH DATA SE 200A SCREW HHTT M5-0.8 X 16
Section 7 Notes
ATS HS Type Transfer Switch
Section 7 Notes
ATS HS Type Transfer Switch
Section 8 Warranty
ATS HS Type Transfer Switch
Revision F (07/21/05)
Printed in U.S.A.