Scale 1:20: Notes

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTES:

1. ALL DIMENSIONS IN MILLIMETRES.

2. REINSTATEMENT TO COMPLY WITH


REQUIREMENTS OF THE RELEVANT LOCAL
AUTHORITY.

3. END DUCTS TO BE IN LINE.

B 4. ALL MATERIALS AND WORKMANSHIP TO


BE IN ACCORDANCE WITH THE NRA
-
SPECIFICATION FOR ROADWORKS, MAY 2005
& SUBSEQUENT REVISIONS.

5. REINFORCED CONCRETE TO BE MINIMUM


WALL OPENINGS 450x325 MAX. ACTUAL SIZE GRADE C32/40 TO I.S.EN 206. SULPHATE
TO BE FORMED TO SUIT DUCT ENTRIES. VOIDS
RESISTING CEMENT TO BE USED WHERE
TO BE SEALED AND SURFACES MADE GOOD
WITH CLASS 1 MORTAR.
AGGRESSIVE SOIL CONDITIONS APPLY,
REFER TO TABLE 6.1 OF B.S. 8110.

6. CARRIAGEWAY COVERS AND FRAMES TO


BE TO B.S. EN 124.
A
GALVANISED STEP IRONS TO BE FITTED IN ALL
- BOXES DEEPER THAN 700mm POSITIONED AT
7. ALL COVERS SHALL HAVE 'ESB' LOGO
THE END REMOTE FROM ANY SIDE ENTRY
DUCT OR AS DIRECTED BY THE ENGINEER,
INCORPORATED IN THEM TO THE APPROVAL
AND AWAY FROM THE SUMP. OF THE ENGINEER.

8. STEP IRONS TO BE HOT DIPPED


PLAN GALVANISED TO B.S. 729 AND POSITIONED
AS SHOWN ON ANY CHAMBER DEEPER
Scale 1:20 THAN 700mm ON THE END REMOTE FROM
ANY SIDE ENTRY DUCT.

1:3 CEMENT/SAND BED AND


HAUNCH TO COVER FRAME 9. BRICKWORK TO BE CLASS B
CAVANAGH 'RHINO' E600 COVER, EDGE
ENGINEERING. BEDS AND JOINTS TO BE
OF COVER/GRATING FRAME TO BE
COATED WITH BITUMEN BEFORE PLACING CLASS 1 MORTAR.
SEAL JOINT WITH HOT BITUMEN TOPPED WITH
OF MASTIC ASPHALT CARRAIGEWAY SURFACE
FINE SAND (25mm WIDE x 3mm Thk.)

SAW CUT JOINT IN EXISTING SURFACING


AND PAINT WITH BITUMEN BEFORE C16/20 MASS CONCRETE (240kg/m ³
LAYING MASTIC ASPHALT MIN. CEMENT CONTENT) 450mm FOOTWAYS

MASTIC ASPHALT WITH ROLLED IN 14mm 1-4 COURSES OF CLASS B ENGINEERING 600mm NON-ESTATE ROADS

COATED STONE CHIPPINGS IN BRICK (AS AGREED WITH ENGINEER) TO (DUBLIN CITY COUNCIL)
ACCORDANCE WITH BS1447. AREA TO 750mm CARRAIGEWAYS
I.S. 91 WITH 1:3 CEMENT/SAND MORTAR DUCT SEPARATION TO
BE SWEPT CLEAN OF DEBRIS & WATER BEDS, 10mm MAX THICKNESS BE 25mm LATERALLY
BEFORE LAYING MASTIC ASPHALT AND VERTICALLY

MIN. DEPTH 25mm CEMENT/SAND SCREED


(1:3) WITH 25mm FALL TO GRATING 254x254mm GALVANISED
1:25 FALL STEEL SUMP GRATING

254x254mm GALVANISED
STEEL SUMP GRATING
PIPE TO B.S. 4660

50mm THICK CONCRETE BLINDING

TO B.S. 4660

SECTION A SECTION B
- -

Scale 1:20 Scale 1:20

COPYRIGHT C ESB
Client Production Unit
All rights reserved. No part of this work may be modified, reproduced or copied in any form or by any means - graphic, electronic or mechanical,
ORIEL WINDFARM LIMITED Civil, Environmental and Renewable Engineering including photocopying, recording, taping or used for any purpose other than its designated purpose, without the written permission of ESB.

Drawing Title DRAWN PRODUCED VERIFIED APPROVED APPROVAL DATE


002
ADDED DIMENSIONS & SCALES
Project COMMUNICATIONS CHAMBER N.BELL N.BELL R.DOYLE M.HOGAN 01/02/24
M.HOGAN
001 21/08/23 SHEET SIZE UPDATED TO A2 NB NB RD RD
CLIENT REF No. OF SHTS SIZE SCALE
ORIEL WIND FARM PROJECT GENERAL ARRANGEMENT
000 11/07/23 FIRST ISSUE NB NB RD RD AS STATED
TC225560 1/1 A2
Rev. Date Revision Description Drn.Prod.Ver. App.
Contract SHEET REV
Drawing Number
Purpose of issue - Preliminary unless indicated

Client Approval Planning X Tender Construction As-built


PE605-D027-071-002-002