Ecsbc Guide
Ecsbc Guide
Ecsbc Guide
Chapter 0: Definitions 1
Chapter 1: Purpose 20
Chapter 2: Scope 21
Content
Chapter 3: Approach to Compliance 25
Chapter 4: Sustainable Sites & Planning 27
Chapter 5: Building Envelope 30
Chapter 6: Comfort System and Controls 45
Chapter 7: Lighting and Controls 55
Chapter 8: Electrical and Renewable Energy Systems 69
Chapter 9: Water Management and Controls 76
Chapter 10: Waste Management 87
Chapter 11: Indoor Environment Quality 92
Chapter 12: Whole Building Performance 102
Appendix 1: Default Values for Typical Constructions 139
Appendix 2: Climate Zone Map of India 148
Appendix 3: Air-Side Economizer Acceptance Procedures 150
Appendix 4: Controls And Internet of Things 151
Appendix 5: Commissioning of Building Systems 154
Appendix 6: Sustainable Materials 155
Appendix 7: Power Quality 179
Definitions
point multiplied with its respective area is divided with
This section defines specific terms, abbreviations, and the total area.
acronyms for the purposes of this code. These 𝛴(𝐷𝑎𝑡𝑎 𝑝𝑜𝑖𝑛𝑡 𝑋 𝑎𝑟𝑒𝑎)
definitions apply to all sections. Any terms not defined 𝐴𝑊𝐴 =
𝑇𝑜𝑡𝑎𝑙 𝑎𝑟𝑒𝑎
here should be interpreted according to their Astronomical time control: an automatic time
commonly accepted meanings in the context in which control that makes an adjustment for the length of the
they appear. day as it varies over the year.
A Automatic Control Device: a device capable of
Above grade area (AGA): AGA is the cumulative floor automatically turning loads off and on without manual
area of all the floor levels of a building that are above intervention.
the ground level. Ground level shall be as defined in Authority having jurisdiction: the agency or agent
building site plan. A floor level is above grade if one- responsible for enforcing this code.
third of the total external surface area of only the said
B
floor level is above the ground level.
Backflow: The flow of water or other liquids, mixtures,
Accredited independent laboratory: testing
or substances into the distributing pipes of a potable
laboratory not affiliated with producer or consumer of
supply of water from any sources other than its
goods or products tested at the laboratory and
intended source. See Back- Siphonage, Back-Pressure
accredited by national or international organizations
Backflow.
for technical competence.
Balancing, air system: adjusting airflow rates
Addition: an extension or increase in floor area or
through air distribution system devices, such as fans
height of a building outside of the existing building
and diffusers, by manually adjusting the position of
envelope.
dampers, splitters vanes, extractors, etc., or by using
Air conditioning and condensing units serving automatic control devices, such as constant air volume
computer rooms: air conditioning equipment that or variable air volume boxes.
provides cooling by maintaining space temperature
Balancing, hydronic system: adjusting water flow
and humidity within a narrow range. Major application
rates through hydronic distribution system devices,
is in data centers where dissipating heat generated by
such as pumps and coils, by manually adjusting the
equipment takes precedence over comfort cooling for
position valves, or by using automatic control devices,
occupants.
such as automatic flow control valves.
Alternate Water Source: Non-potable source of water
Ballast: unit inserted between the supply and one or
that includes gray water, on-site treated water,
more discharge lamps which by means of inductance,
harvested rainwater, and reclaimed (recycled) water
capacitance or resistance, single or in combination,
from sewage treatment plant.
serves mainly to limit the current of the lamp(s) to the
Alteration: any change, rearrangement, replacement, required value. It may also include means for
or addition to a building or its systems and equipment; transforming from the supply voltage and
any modification in construction or building arrangements which help to provide starting voltage
equipment. and preheating current, prevent cold starting, reduce
Area weighted average (AWA) method: AWA stroboscopic effect, correct the power factor and
method is based on the concept of weighted arithmetic suppress radio interference.
mean where instead of each data point contributing
Definitions
Boiler: a self-contained low-pressure appliance for Building grounds lighting: lighting provided through
supplying steam or hot water a building’s electrical service for parking lot, site,
Brownfield Site: Real property or the expansion, roadway, pedestrian pathway, loading dock, and
redevelopment, or reuse of which may be complicated security applications
by the presence or possible presence of a hazardous Building material: any element of the building
substance, pollutant, or contaminant. envelope through which heat flows and that heat is
Building or building complex or complex: a included in the component U-factor calculations other
structure wholly or partially enclosed within exterior than air films and insulation
walls, or within exterior and party walls, and a roof, Built up area (BUA): sum of the covered areas of all
affording shelter to persons, animals, or property. floors of a building, other than the roof, and areas
Building complex means a building or group of covered by external walls and parapet on these floors.
buildings constructed in a contiguous area for 24-hour Business Building: Business building
business, commercial, institutional, healthcare, operated and occupied for more than 12 hours on each
hospitality purposes or assembly buildings under the weekday. Intensity of occupancy may vary.
single ownership of individuals or group of individuals
Bar: 1 Bar pressure is equivalent to 1 kg/cm² or 10 m
or under the name of a co-operative group society or
of water column.
on lease and sold as shops or office space or space for
other commercial purposes, having a connected load of
100 kW or contract demand of 120 kVA and above. Backflow: The flow of water or other liquids, mixtures,
Building, base: includes building structure, building or substances into the distributing pipes of a potable
envelope, common areas, circulation areas, parking, supply of water from any sources other than its
basements, services area, plant room and its intended source. See Back- Siphonage, Back-Pressure
supporting areas and, open project site area. Backflow.
Building, core and shell: buildings where the Bio digestor: Biogas digestor uses natural anaerobic
developer or owner will only provide the base building decomposition of organic matter under controlled
and its services. conditions to convert organic waste into manure.
Building, existing: a building or portion thereof that Black Water: Wastewater from toilet, bidet, urinals,
was previously occupied or approved for occupancy by kitchen sink, bed pan sink or similar contaminated
the authority having jurisdiction. sources.
Definitions
the construction materials for the building envelope, Contaminant: Any substance, that is potentially
roof, wall, floor, slab-on-grade floor, opaque door, hazardous to human health or the environment and is
vertical fenestration, skylight present in the environment at concentrations above its
Coefficient of Performance (COP) – cooling: the natural or background concentration.
ratio of the rate of heat removal to the rate of energy Contamination: An impairment of the quality of the
input, in consistent units, for a complete refrigerating potable water that creates an actual hazard to the
system or some specific portion of that system under public health through poisoning or through the spread
designated operating conditions of disease by sewage, industrial fluids, or waste. Also
Coefficient of Performance (COP) – heating: the defined as High Hazard.
ratio of the rate of heat delivered to the rate of energy Contract demand: the maximum demand in kilo Volt
input, in consistent units, for a complete heat pump Ampere (kVA) (within a consumer’s sanctioned load)
system, including the compressor and, if applicable, agreed to be supplied by the electricity provider or
auxiliary heat, under designated operating conditions utility in the agreement executed between the user and
Common area: areas within a building that are the utility or electricity provider.
available for use by all tenants in a building (i.e. Construction documents: drawings or documents,
lobbies, corridors, restrooms, etc.) containing information pertaining to building
Commercial building: a building or a part of building construction processes and approvals, building
or building complex which are used or intended to be materials and equipment specification, architectural
used for commercial purposes and classified as per the details etc. required by the authority having
time of the day the building is operational and sub jurisdiction.
classified, as per the functional requirements of its Controls or control device: manually operated or
design, construction, and use as per following details: automatic device or software to regulate the operation
a) Group I – 24 hours building covering Type A of building equipment
Hospitality, Type B Health Care and Type C Cool roof: roof with top layer of material that has high
Assembly, Type D Business and, solar reflectance and high thermal emittance
b) Group II – Regular building covering Type D properties. Cool roof surfaces are characterized by
Business, Type E Educational and Type F light colors so that heat can be rejected back to the
Shopping Complexes. environment.
Compliance documents: the forms specified in ECSBC Cumulative design EPI: energy performance index for
Rules and Regulations to record and check compliance a building having two or more different functional uses
with these rules. These include but are not limited to and calculated based on the area weighted average
EPI Ratio Compliance Report, Building Envelope (AWA) method
Compliance Form, Mechanical Systems Compliance D
Form and Permit Checklist, Lighting System Daylight area: the daylight illuminated floor area
Compliance Form and Permit Checklist and certificates under horizontal fenestration (skylight) or adjacent to
from Certified Energy Auditor for existing or proposed vertical fenestration (window), described as follows:
buildings.
(a) Horizontal Fenestration: the area under a skylight,
Connected load: the sum of the rated wattage of all monitor, or sawtooth configuration with an
equipment, appliances and devices to be installed in effective aperture greater than 0.001 (0.1%). The
the building or part of building or building complexes, daylight area is calculated as the horizontal
Definitions
configuration, or the distance to the nearest 1 window, whichever is least.
meter or higher opaque partition, or one-half the
distance to an adjacent skylight or vertical glazing,
whichever is least, as shown in the plan and Head height of the Vertical fenestration x DEF
section figures below.
1m
Plan
Skylight
1 m, or to nearest
opaque partition
Daylight Area
Ceiling height
opaque partition
H
Daylit Area
2H
level, with an interior light shelf at bottom of this
fenestration
Monitor
Dead band: the range of values within which a sensed
variable can vary without initiating a change in the
H Daylit Area controlled process.
1.5H 1.5H
Demand: maximum rate of electricity (kW)
consumption recorded for a building or facility during
(b) Vertical Fenestration: the floor area adjacent to a selected time frame.
side apertures (vertical fenestration in walls) with Demand control ventilation (DCV): a ventilation
an effective aperture greater than 0.06 (6%). The system capability that provides automatic reduction of
daylight area extends into the space perpendicular outdoor air intake below design rates when the actual
to the side aperture a distance equal to daylight occupancy of spaces served by the system is less than
extension factor (DEF) multiplied by the head design occupancy
height of the side aperture or till higher opaque Demand factor: is the ratio of the sum of the
partition, whichever is less. In the direction maximum demand of a system (or part of a system) to
parallel to the window, the daylight area extends a the total connected load on the system (or part of the
Definitions
Design conditions: specified indoor environmental Efficacy: the lumens produced by a lamp plus ballast
conditions, such as temperature, humidity and light system divided by the total watts of input power
intensity, required to be produced and maintained by (including the ballast), expressed in lumens per watt
a system and under which the system must operate Efficiency: performance at a specified rating condition
Distribution system: network or system comprising Efficiency, thermal: ratio of work output to heat input
controlling devices or equipment and distribution
Efficiency, combustion: efficiency with which fuel is
channels (cables, coils, ducts, pipes etc.) for delivery of
burned during the combustion process in equipment
electrical power or, cooled or heated water or air in
buildings. Emittance: the ratio of the radiant heat flux emitted by
a specimen to that emitted by a blackbody at the same
Domestic Sewage: The liquid and water-borne wastes
temperature and under the same conditions
derived from the ordinary living processes, free from
industrial wastes, and of such character as to permit Energy: power derived from renewable or non-
satisfactory disposal, without special treatment, into renewable resources to provide heating, cooling and
the public sewer or by means of a private sewage light to a building or operate any building equipment
disposal system. and appliances. It has various forms such as thermal
(heat), mechanical (work), electrical, and chemical that
may be transformed from one into another. Customary
Domestic Water: Potable water provided for unit of measurement is watts (W)
domestic purposes such as drinking, cooking and
Energy Efficiency Ratio (EER): the ratio of net cooling
supply to fixtures such as kitchen sink, washbasins,
capacity in watt to total rate of electric input in watts
shower, clothes washer and dishwasher.
under design operating conditions
Door: all operable opening areas, that are not more
Energy recovery system: equipment to recover
than one half glass, in the building envelope, including
energy from building or space exhaust air and use it to
swinging and roll-up doors, fire doors, and access
treat (pre-heat or pre-cool) outdoor air taken inside
hatches.
the building or space by ventilation systems
Door area: total area of the door measured using the
Envelope Performance Factor (EPF): value for the
rough opening and including the door slab and the
building envelope performance compliance option
frame.
calculated using the procedures specified in 4B.3.5 and
Drinking Water: Drinking water is water intended for 4B.3.5.1.1. For the purposes of determining building
human consumption for drinking and cooking envelope requirements the classifications are defined
purposes from any source. It includes water (treated or as follows:
untreated) supplied by any means for human
(a) Baseline Building EPF: envelope performance
consumption.
factor calculated for the Baseline Building
E using standardized requirements for walls,
Economizer, air: a duct and damper arrangement vertical fenestrations and roofs
with automatic controls that allow a cooling system to (b) Proposed Building EPF: the building envelope
supply outdoor air to reduce or eliminate the need for performance factor for the Proposed Building
mechanical cooling during mild or cold weather using proposed values for walls, vertical
Economizer, water: a system by which the supply air fenestrations and roofs
of a cooling system is cooled indirectly with water that
Definitions
Equipment, existing: equipment previously installed Utility, bore well, open well and bought out water for
in an existing building domestic use.
Equivalent SHGC: SHGC for a fenestration with a Fuel: a material that may be used to produce heat or
permanent external shading projection. It is calculated generate power by combustion
using the Projection Factor (PF) of the permanent Fuel utilization efficiency (FUE): a thermal efficiency
external shading projection and Shading Equivalent measure of combustion equipment like furnaces,
Factor (SEF) listed in §4B.3.1. boilers, and water heaters
Exemption: any exception allowed to compliance with G
ECSBC requirements
Gathering hall (Type of Assembly): any building, its
F lobbies, rooms and other spaces connected thereto,
Fan system power: sum of the nominal power primarily intended for assembly of people, but which
demand (nameplate W or HP) of motors of all fans that has no theatrical stage or permanent theatrical and/or
are required to operate at design conditions to supply cinematographic accessories and has gathering space
air from the heating or cooling source to the for greater or equal to 100 persons, for example, stand-
conditioned space(s) and return it to the point where alone dance halls, stand-alone night clubs, halls for
is can be exhausted to outside the building. incidental picture shows, dramatic, theatrical or
Fenestration: all areas (including the frames) in the educational presentation, lectures or other similar
building envelope that let in light, including windows, purposes having no theatrical stage except a raised
plastic panels, clerestories, skylights, glass doors that platform and used without permanent seating
are more than one-half glass, and glass block walls. arrangement; art galleries, community halls, marriage
halls, places of worship, museums, stand-alone lecture
(a) Skylight: a fenestration surface having a slope
halls, passenger terminals and heritage and
of less than 60 degrees from the horizontal
archaeological monuments, pool and billiard parlour,
plane. Other fenestration, even if mounted on
bowling alleys, community halls, courtrooms,
the roof of a building, is considered vertical
gymnasiums, indoor swimming pools, indoor tennis
fenestration.
court, any indoor stadium for sports and culture,
(b) Vertical fenestration: all fenestration other auditoriums
than skylights. Trombe wall assemblies,
Grade: finished ground level adjoining a building at all
where glazing is installed within 300 mm of a
exterior walls
mass wall, are considered walls, not
fenestration. Gray Water: Untreated wastewater that has not come
into contact with toilet waste, kitchen sink waste, or
Fenestration area: total area of the fenestration
similarly contaminated sources. Gray water includes
measured using the rough opening and including the
wastewater from bathtubs, showers, lavatories,
glazing, sash, and frame. For doors where the glazed
clothes washers, laundry tubs, dishwashers and
vision area is less than 50% of the door area, the
domestic RO reject water.
fenestration area is the glazed vision area. For all other
doors, the fenestration area is the door area. Guest room: any room or rooms used or intended to
be used by a guest for sleeping purposes
Finished floor level: level of floor achieved after
finishing materials have been added to the subfloor or H
rough floor or concrete floor slab. Habitable spaces: space in a building or structure
intended or used for working, meeting, living, sleeping,
Definitions
hardscape, such as dark, nonreflective pavement and standard or performance in a specified manner.
buildings, and its subsequent radiation to surrounding Lighted floor area, gross: gross area of lighted floor
areas. Other contributing factors may include vehicle spaces
exhaust, air conditioners, and street equipment. Tall
Lighting, decorative: lighting that is ornamental or
buildings and narrow streets reduce airflow and
installed for aesthetic effect. Decorative lighting shall
exacerbate the effect.
not include general lighting.
Hospitals and sanatoria (Healthcare): Any building
Lighting, emergency: battery backed lighting that
or a group of buildings under single management,
provides illumination only when there is a power
which is used for housing persons suffering from
outage and general lighting luminaries are unable to
physical limitations because of health or age and those
function.
incapables of self-preservation, for example, any
hospitals, infirmaries, sanatoria and nursing homes. Lighting, general: lighting that provides a
substantially uniform level of illumination throughout
HVAC system: equipment, distribution systems, and
an area. General lighting shall not include decorative
terminal devices that provide, either collectively or
lighting or lighting that provides a dissimilar level of
individually, the processes of heating, ventilating, or
illumination to serve a specialized application or
air conditioning to a building or parts of a building.
feature within such area.
Hyper Markets (Type F of Shopping Complex): large
Lighting system: a group of luminaires circuited or
retail establishments that are a combination of
controlled to perform a specific function.
supermarket and department stores. They are
considered as a one-stop shop for all needs of the Lighting power allowance:
customer. (a) Interior lighting power allowance: the
I maximum lighting power in watts allowed for
the interior of a building.
Infiltration: uncontrolled inward air leakage through
cracks and crevices in external surfaces of buildings, (b) Exterior lighting power allowance: the
around windows and doors due to pressure maximum lighting power in watts allowed for
differences across these caused by factors such as wind the exterior of a building.
or indoor and outside temperature differences (stack Lighting Power Density (LPD): maximum lighting
effect), and imbalance between supply and exhaust air power per unit area of a space as per its function or
systems building as per its classification.
Installed interior lighting power: power in watts of Low energy comfort systems: space conditioning or
all permanently installed general, task, and furniture ventilation systems that are less energy intensive then
lighting systems and luminaries. vapour compression-based space condition systems.
Integrated part-load value (IPLV): weighted average These primarily employ alternate heat transfer
efficiency of chillers measured when they are methods or materials (adiabatic cooling, radiation,
operating at part load conditions (less than design or desiccant, etc.), or renewable sources of energy (solar
100% conditions). It is more realistic measurement of energy, geo-thermal) so that minimal electrical energy
chillers efficiency during its operational life. input is required to deliver heating or cooling to
spaces.
Inventory: A complete list of items such as property,
goods in stock, or the contents of a building Luminaire: Equipment which distributes, filters or
transforms the light transmitted from one or more
Definitions
them to the supply.
Metered Faucet: A self-closing factory calibrated
Note: A luminaire with integral non-replaceable lamps faucet that dispenses a predetermined volume of water
is regarded as a luminaire, except that the tests are not for each cycle.
applied to the integral lamp or integral self-ballasted
Metering: practice of installing meters in buildings to
lamp.
acquire data for energy consumption and other
operational characteristics of individual equipment or
M several equipment grouped on basis of their function
Man-made daylight obstruction: any permanent (lighting, appliances, chillers, etc.). Metering is done in
man-made object (equipment, adjacent building) that buildings to monitor their energy performance.
obstructs sunlight or solar radiation from falling on a Mixed mode air-conditioned building: building in
portion or whole of a building’s external surface at any which natural ventilation is employed as the primary
point of time during a year is called as a man-made mode of ventilating the building, and air conditioning
sunlight obstructer. is deployed as and when required.
Manual (non-automatic): requiring personal Mixed use development: a single building or a group
intervention for control. Non-automatic does not of buildings used for a combination of residential,
necessarily imply a manual controller, only that commercial, business, educational, hospitality and
personal intervention is necessary. assembly purposes
Manufacturing processes: processes through which N
raw material is converted into finished goods for National Building Code 2016 (NBC): model building
commercial sale using machines, labor, chemical or code that provides guidelines for design and
biological processes, etc. construction of buildings. In this code, National
Manufacturer: company or person or group of Building Code 2016 refers to the latest version by the
persons who produce and assemble goods or Bureau of Indian Standards.
purchases goods manufactured by a third party in Natural daylight obstruction: any natural object, like
accordance with their specifications. tree, hill, etc., that obstructs sunlight from falling on
Mean temperature: average of the minimum daily part or whole of a building’s external surface at any
temperature and maximum daily temperature. point of time during a year and casts a shadow on the
Mechanical cooling: reducing the temperature of a building surface.
gas or liquid by using vapor compression, absorption, Naturally ventilated building: a building that does
and desiccant dehumidification combined with not use mechanical equipment to supply air to and
evaporative cooling, or another energy-driven exhaust air from indoor spaces. It is primarily
thermodynamic cycle. Indirect or direct evaporative ventilated by drawing and expelling air through
cooling alone is not considered mechanical cooling. operable openings in the building envelope.
Modeled Energy Performance Intensity (MEPI): Net Exposed Roof Area: Net exposed roof area = Total
MEPI of a building is estimated annual energy roof area – equipment area
consumption in kilowatt-hours per square meter area Non-cardinal directions: any direction which is not a
of the building (excluding unconditioned basement cardinal direction, i.e. perfect north, south, east, or
area, unconditioned refuge area, and stilt parking area) west, is termed as non-cardinal direction.
and calculated using a simulation program.
Definitions
cooking facilities, is provided for individuals. This
Organic waste converters (OWC): Machines that are
includes lodging rooms, inns, clubs, motels, no star
used to convert organic waste such as vegetable waste,
hotel and guest houses and excludes residential
meat waste, bakery waste, leaves, fruits and fruit skins,
apartments rented on a lease agreement of 4 months
and flowers into valuable compost that can be used for
or more. These shall also include any building in which
organic farming activities.
group sleeping accommodation is provided, with or
without dining facilities for persons who are not Orientation: the direction a building facade faces, i.e.,
members of the same family, in one room or a series of the direction of a vector perpendicular to and pointing
adjoining rooms under joint occupancy and single away from the surface of the facade. For vertical
management, for example, school and college fenestration, the two categories are north-oriented
dormitories, students, and other hostels and military and all other.
barracks. Outdoor (outside) air: air taken from the outside the
O building and has not been previously circulated
through the building.
Occupant/Occupancy sensor: a device that detects
the presence or absence of people within an area and Out-patient Healthcare (Type of Healthcare): any
causes lighting, equipment, or appliances to be building or a group of buildings under single
dimmed, or switched on or off accordingly. management, which is used only for treating persons
requiring treatment or diagnosis of disease but not
On-site electricity generation systems: systems
requiring overnight or longer accommodation in the
located at the building site that generate electricity,
building during treatment or diagnosis.
including, but not limited to, generators, combined
heat and power systems, fuel cells, and on-site Overcurrent: any current in excess of the rated
renewable energy systems. current of the equipment of the ampacity of the
conductor. It may result from overload, short circuit, or
On-site renewable energy: energy from renewable
ground fault.
resources harvested at the building site.
Overall Efficiency: Efficiency of motor and pump
Opaque assembly or opaque construction: surface
considered together.
of the building roof or walls other than fenestration
and building service openings such as vents and grills. Owner: a person, group of persons, company, trust,
institute, Registered Body, state or central Government
Opaque external wall: external wall composed of
and its attached or sub-ordinate departments,
materials which are not transparent or translucent,
undertakings and like agencies or organization in
usually contains the structural part of the building, and
whose name the property stands registered in the
supports the glazed façade. This type may be
revenue records for the construction of a building or
composed of one or more materials.
building complex
Open Gallery Mall (Type of Shopping Complex): a
P
large retail complex containing a variety of stores and
often restaurants and other business establishments Party wall: a firewall on an interior lot line used or
housed in a series of connected or adjacent buildings adapted for joint service between two buildings.
or in a single large building. The circulation area and Paved Areas: Paved area is an area that is paved with
atrium of the open gallery mall is an unconditioned concrete, asphalt, stone, brick, gravel, or other wearing
space and is open to sky. surface.
Definitions
place and is not portable or movable.
pH: pH is a figure expressing the acidity or alkalinity of
a solution on a logarithmic scale on which 7 is neutral,
lower values are more acid and higher values more
alkaline. The pH is equal to −log10 c, where c is the
hydrogen ion concentration in moles per liter.
Plenum: a compartment or chamber to which one or
more ducts are connected, that forms a part of the air
Pool: any structure, basin, or tank containing an
distribution system, and that is not used for occupancy
artificial body of water for swimming, diving, or
or storage.
recreational bathing. The terms include, but no limited
Plug loads: energy used by products that are powered to, swimming pool, whirlpool, spa, hot tub.
by means of an AC plug. This term excludes building
Post occupancy: The buyer of a property agrees to
energy that is attributed to major end uses specified in
allow the seller of the property to stay in the property
§ 5, § 6, § 7, § 8, § 9, § 11 (like HVAC, lighting, water
past the settlement date.
heating, etc.).
Potable Water: Water that is satisfactory for drinking,
Plumbing Appliance: Devices or equipment that are
culinary, and domestic purposes and that meets the
intended to perform a special plumbing function. Its
requirements of the Health Authority Having
operation and/or control may be dependent upon one
Jurisdiction.
or more energized components, such as motors,
controls, heating elements, or pressure or P&I Diagram: Piping & Instrument diagram is a detail
temperature-sensing elements. Such device or diagram which shows all the piping together with the
equipment shall be permitted to operate automatically equipment’s, instruments & control devices.
or manually by the user or operator. Potential daylit time: amount of time in a day when
there is daylight to light a space adequately without
using artificial lighting. Potential daylit time is fixed for
Plumbing Appurtenance: A device or assembly that
8 hours per day i.e. from 09:00 AM to 5:00 PM local
is an adjunct to the basic piping system and plumbing
time, resulting 2920 hours in total for all building types
fixtures. An appurtenance demands no additional
except for Type E-1 - Educational, which shall be
water supply, nor does it add any discharge load to a
analyzed for 7 hours per day i.e. from 08:00 AM to 3:00
fixture or the drainage system. It performs some useful
PM local time.
function in the operation, maintenance, servicing,
economy, or safety of the plumbing system. Primary inter-cardinal direction: any of the four
points of the compass, midway between the cardinal
Plumbing Fixture: An approved-type receptacle or
points; northeast, southeast, southwest, or northwest
device that is supplied with water or that receives
are called primary inter-cardinal direction.
liquid wastes and discharges such wastes into the
drainage system to which it may be directly or
indirectly connected.
Plumbing System: Includes water, building supply,
and distribution pipes; all plumbing fixtures, fittings,
appliances and appurtenances; all drainage and vent
Definitions
water heating.
Projection factor, overhang: It is the ratio of the
horizontal depth of the external shading projection to
the sum of the height of the fenestration and the
distance from the top of the fenestration to the bottom
of the farthest point of the external shading projection,
in consistent units. distribution system that includes a close circulation
Projection factor Right Fin(PFR)= C/(B+W) circuit designed to maintain usage temperatures in hot
water pipes near terminal devices (e.g., lavatory
Projection factor, side fin: It is the ratio of the
faucets, shower heads) in order to reduce the time
horizontal depth of the external shading projection to
required to obtain hot water when the terminal device
the distance from the window jamb to the farthest
valve is opened. The motive force for circulation is
point of the external shading projection, in consistent
either natural (due to water density variations with
units.
temperature) or mechanical (recirculation pump).
Projection factor Left Fin(PFL)= C/(A+W) Reclaimed (Recycled) Water: Non-potable water
generated, as a result of tertiary treatment of domestic
Projection factor Right Fin(PFR)= C/(B+W)
Black/Grey water that meets requirements of the
Projection Factor, overhang and side fin: average of Authority Having Jurisdiction for its intended uses.
ratio projection factor for overhang only and Remediation: The doing of any works, or carrying out
projection factor of side fin only. of any operations or taking of any steps in relation to a
Proposed Building: is consistent with the actual polluted site for the purpose of (a) identifying or
design of the building and complies with all the investigating or preventing or minimizing or
mandatory requirements of ECSBC. remedying or mitigating the adverse effects by reason
Proposed Design: a computer model of the proposed of which polluted site is such site; (b) restoring the
building, consistent with its actual design, which quality of environment, flora and fauna at the site to an
complies with all the mandatory requirements of acceptable level; and includes making of subsequent
ECSBC. inspections from time to time for the purpose of
keeping under review the condition of the site in
R
question, in the manner prescribed.
R-value (thermal resistance): the reciprocal of the
Renewable Energy Generating Zone: a contiguous or
time rate of heat flow through a unit area induced by a
semi-contiguous area, either on rooftop or elsewhere
unit temperature difference between two defined
within site boundary, dedicated for installation of
surfaces of material or construction under steady-state
renewable energy systems.
conditions. Units of R value are m2.K /W.
Renewable Energy Resources: energy from solar,
Readily accessible: capable of being reached quickly
wind, biomass or hydro, or extracted from hot fluid or
for operation, renewal, or inspections without
steam heated within the earth.
requiring those to whom ready access is requisite to
climb over or remove obstacles or to resort to portable Resort (Type of Hospitality): commercial
ladders, chairs, etc. In public facilities, accessibility establishments that provide relaxation and recreation
may be limited to certified personnel through locking over and above the accommodation, meals and other
covers or by placing equipment in locked rooms. basic amnesties. The characteristics of resort are as
below –
Definitions
iii. Comprises of 2 or more blocks of buildings complex containing a variety of stores and often
within the same site less than or equal to 3 restaurants and other business establishments housed
floors (including the ground floor). in a series of connected or adjacent buildings or in a
single large building. The circulation area and atrium
Reset: automatic adjustment of the controller set point
of the mall is an enclosed space covered completely by
to a higher or lower value.
a permanent or temporary structure.
Roof: the upper portion of the building envelope,
Simulation program: software in which virtual
including opaque areas and fenestration, that is
building models can be developed to simulate the
horizontal or tilted at an angle of less than 60° from
energy performance of building systems and
horizontal. This includes podium roof as well which are
daylighting analysis
exposed to direct sun rays.
Single-zone system: an HVAC system serving a single
Roof area, gross: the area of the roof measured from
HVAC zone.
the exterior faces of walls or from the centerline of
party walls Site-recovered energy: waste energy recovered at
the building site that is used to offset consumption of
S
purchased fuel or electrical energy supplies.
Sedimentation Basin: A sediment basin is a
Slab-on-grade floor: floor slab of the building that is
temporary pond built on a construction site to capture
in contact with ground and that is either above grade
eroded or disturbed soil that is washed off during
or is less than or equal to 300 mm below the final
rainstorms, and protect the water quality of a nearby
elevation of the nearest exterior grade. Solar energy
stream, river, lake, or bay. The sediment-laden soil
source: source of thermal, chemical, or electrical
settles in the pond before the runoff is discharged.
energy derived from direction conversion of incident
Service: the equipment for delivering energy from the solar radiation at the building site.
supply or distribution system to the premises served.
Solar Heat Gain Coefficient (SHGC): the ratio of the
Service water heating equipment: equipment for solar heat gain entering the space through the
heating water for domestic or commercial purposes fenestration area to the incident solar radiation. Solar
other than space heating and process requirements. heat gain includes directly transmitted solar heat and
Set point: the desired temperature (°C) of the heated absorbed solar radiation, which is then reradiated,
or cooled space that must be maintained by mechanical conducted, or convected into the space.
heating or cooling equipment. Solar Reflectance: ratio of the solar radiation
Sewage: Wastewater containing human excreta reflected by a surface to the solar radiation incident
(faeces and urine) as well as sources of black water and upon it.
grey water. Solar Reflective Index: A measure of the constructed
Shading Coefficient (SC): measure of thermal surface’s ability to stay cool in the sun by reflecting
performance of glazing. It is the ratio of solar heat gain solar radiation and emitting thermal radiation. It is
through glazing due to solar radiation at normal defined such that a standard black surface (initial solar
incidence to that occurring through 3 mm thick clear, reflectance 0.05, initial thermal emittance 0.90) has an
double-strength glass. Shading coefficient, as used initial SRI of 0, and a standard white surface (initial
herein, does not include interior, exterior, or integral solar reflectance 0.80, initial thermal emittance 0.90)
shading devices. has an initial SRI of 100. To calculate the SRI for a given
material, obtain its solar reflectance and thermal
Definitions
Space: an enclosed area within a building. The month of March to October within the same calendar
classifications of spaces are as follows for purpose of year. Units of measurement are watts per square meter
determining building envelope requirements: (W/m²) or kilowatt-hours per square meter per day
(a) Conditioned space: a cooled space, heated (kW•h/(m²•day)) (or hours/day).
space, or directly conditioned space. Super Market (Shopping Complex): supermarkets
(b) Semi-heated space: an enclosed space within a are large self-service grocery stores that offer
building that is heated by a heating system customers a variety of foods and household supplies.
whose output capacity is greater or equal to The merchandise is organized into an organized aisle
10.7 W/m2 but is not a conditioned space. format, where each aisle has only similar goods placed
together.
(c) Non-conditioned space: an enclosed space
within a building that is not conditioned space System: a combination of equipment and auxiliary
or a semi-heated space. Crawlspaces, attics, devices (e.g., controls, accessories, interconnecting
and parking garages with natural or means, and terminal elements) by which energy is
mechanical ventilation are not considered transformed so it performs a specific function such as
enclosed spaces. HVAC, service water heating, or lighting.
Sullage: Wastewater without faecal matter. Commonly System Efficiency: the system efficiency is the ratio of
known as Gray water. annual kWh electricity consumption of equipment of
water cooled chilled water plant (i.e. chillers, chilled
Star Hotels/motels (Star Hotel): any building or
and condenser water pumps, cooling tower) to chiller
group of buildings under single management and
thermal kWh used in a building.
accredited as a starred hotel by the Hotel and
Restaurant Approval and Classification Committee, System, existing: a system or systems previously
Ministry of Tourism, in which sleeping installed in an existing building.
accommodation, with or without dining facilities is T
provided. Tenant lease agreement: The formal legal document
Stand-alone Retail (Shopping Complex): a large entered into between a Landlord and a Tenant to
retail store owned or sublet to a single management reflect the terms of the negotiations between them;
which may offer customers a variety of products under that is, the lease terms have been negotiated and
self-branding or products of different brands. The agreed upon, and the agreement has been reduced to
single management shall have a complete ownership of writing. It constitutes the entire agreement between
all the spaces of the building and no space within the the parties and sets forth their basic legal rights.
building is further sold or sublet to a different Tenant leased area: area of a building that is leased to
management. tenant(s) as per the tenant lease agreement.
Baseline Design: a computer model of a hypothetical Terminal device: a device through which heated or
building, based on actual building design, that fulfils all cooled air is supplied to a space to maintain its
the mandatory requirements and minimally complies temperature. It usually contains dampers and heating
with the standardized requirements of ECSBC, as and cooling coils. Or a device by which energy form a
described in the Whole Building Performance method. system is finally delivered, e.g., registers, diffusers,
Story: portion of a building that is between one lighting fixtures, faucets, etc.
finished floor level and the next higher finished floor Tactile warning blocks: Tactile warning blocks
indicate an approaching potential hazard or a change
Definitions
intersections, doorways, etc. example, underground or elevated railways.
Theater or motion picture hall (Type of Assembly): Type 1 Ecolabel: Type I ecolabels are voluntary labels
any building primarily meant for theatrical or operatic that signify overall environmental preference of a
performances, and which has a stage, proscenium product or services based on life-cycle considerations
curtain, fixed or portable scenery or scenery loft, lights, that address multiple environmental criteria, which
mechanical appliances or other theatrical accessories are based on transparent standards for environmental
and equipment for example, theaters, motion picture preferability, verified by a qualified organization.
houses, auditoria, concert halls, television and radio U
studios admitting an audience and which are provided
Unconditioned buildings: building in which more
with fixed seats.
than 90% of spaces are unconditioned spaces.
Thermal block: a collection of one or more HVAC
Unconditioned space: mechanically or naturally
zones grouped together for simulation purposes.
ventilated space that is not cooled or heated by
Spaces need not be contiguous to be combined within
mechanical equipment.
a single thermal block.
Universities and all others coaching/training
Thermal comfort conditions: conditions that
institutions (Educational): a building or a group of
influence thermal comfort of occupants.
buildings, under single management, used for
Environmental conditions that influence thermal
imparting education to students numbering more than
comfort air and radiant temperature, humidity, and air
100 or public or private training institution built to
speed.
provide training/coaching etc.
Thermostat: device containing a temperature sensor
Used Water: Black or Grey water from fixtures or
used to automatically maintain temperature at a
appliances.
desirable fixed or adjustable set point in a space.
Useful Daylight Illuminance: percentage of annual
Tinted: (as applied to fenestration) bronze, green, or
daytime hours that a given point on a work plane
grey colouring that is integral with the glazing
height of 0.8 m above finished floor level receives
material. Tinting does not include surface applied films
daylight between 100 lux to 2,000 lux.
such as reflective coatings, applied either in the field or
during the manufacturing process. U-factor (Thermal Transmittance): heat
transmission in unit time through unit area of a
Topsoil: Topsoil is the upper layer of a soil profile,
material or construction and the boundary air films,
usually darker in colour (because of its higher organic
induced by unit temperature difference between the
matter content) and more fertile than subsoil, and
environments on each side. Unit of U value is W/m2.K.
which is a product of natural, biological and
environmental processes. V
Transformer: a static piece of apparatus with two or Variable Air Volume (VAV) system: HVAC system
more windings which, by electromagnetic induction, that controls the dry-bulb temperature within a space
transforms a system of alternating voltage and current by varying the volumetric flow of heated or cooled air
into another system of voltage and current usually of supplied to the space
different values and at the same frequency for the Vegetative roofs: also known as green roofs, they are
purpose of transmitting electrical power thin layers of living vegetation installed on top of
Transformer losses: electrical losses in a transformer conventional flat or sloping roofs.
that reduces its efficiency.
Definitions
way audio and video communication is supported
between two or more sites (refer Figure below). Both
audio (aural) and video (visual) communication are
supported in real time. The transfer and display of
information and data such as documents and
multimedia program materials may also be available
functions in a videoconference space.
Water heater: vessel in which water is heated and
Vermicomposting: It is a process in which withdrawn for use external to the system.
earthworms are used to convert organic materials into
Wastewater: Used water from plumbing fixtures or
humus-like material known as vermicompost.
similar equipment which may be a source of black or
Vision Windows: windows or area of large windows grey water.
that are primarily for both daylight and exterior views.
Wet Area: Areas such as bathroom, toilet, kitchen and
Typically, their placement in the wall is between 1
laundry where water is utilized at fixtures and
meter and 2.2 meter above the floor level.
appliances.
White Light Source: electrically operated product
W intended to emit, or, in the case of a non-incandescent
Wall: that portion of the building envelope, including light source, intended to be possibly tuned to emit,
opaque area and fenestration, that is vertical or tilted light, or both, with the following optical
at an angle of 60° from horizontal or greater. This characteristics:
includes above- and below-grade walls, between floor Chromaticity coordinates x and y in the range 0.270 <
spandrels, peripheral edges of floors, and foundation x < 0.530 and
walls.
2.3172 x2 + 2.3653 x – 0.2199 < y < − 2.3172 x2 + 2.3653
(a) Wall, above grade: a wall that is not below x – 0.1595
grade.
Z
(b) Wall, below grade: that portion of a wall in the
Zone, HVAC: a space or group of spaces within a
building envelope that is entirely below the
building with heating and cooling requirements that
finish grade and in contact with the ground.
are sufficiently similar so that desired conditions (e.g.,
Wall area, gross: the overall area off a wall including temperature) can be maintained throughout using a
openings such as windows and doors measured single sensor (e.g., thermostat or temperature sensor).
horizontally from outside surface to outside surface
Zone, Critical: a zone serving a process where reset of
and measured vertically from the top of the floor to the
the zone temperature set point during a demand shed
top of the roof. If roof insulation is installed at the
event might disrupt the process, including but not
ceiling level rather than the roof, then the vertical
limited to data centers, telecom and private branch
measurement is made to the top of the ceiling. The
exchange (PBX) rooms, and laboratories.
gross wall area includes the area between the ceiling
and the floor for multi-story buildings. Zone, non-critical: a zone that is not a critical zone.
Zone, Plumbing: A group of 8-10 adjacent floors
categorized as zone for a pumping system.
SI Unit IP Unit
Definitions
1 cmh 1.7 cfm
1 Pa 0.0040 inch of water gauge
1m 3.28 ft
1m 39.37 in
1mm 0.039 in
1 m2 10.76 ft2
1 W/ lin m 3.28 W/ ft
1 W/m2.K 0.1761 Btu/ h-ft2-°F
1 kW 1.34 hp
1 kW 3412.142 u/hr
kW Kilowatt of electricity
AFUE Annual fuel utilization efficiency kWr kilowatt of refrigeration
Definitions
BIS Bureau of Indian Standards kWh kilowatt-hour
Btu British thermal unit l/s liter per second
Btu/h British thermal units per hour LE luminous efficacy
Btu/h-ft2- British thermal units per hour per Lin linear
°F square foot per degree Fahrenheit
lin ft linear foot
BUA Built up area
lin m linear meter
C Celsius
Lm lumens
cmh cubic meter per hour
Lm/W lumens per watt
cm centimetre
LPD lighting power density
COP coefficient of performance
M meter
DEF daylight extent factor
Mm millimetre
EER energy efficiency ratio
m2 square meter
EPI energy performance index
m2.K/W square meter Kelvin per watt
F Fahrenheit
NBC National Building Code 2016
ft foot
Pa pascal
h hour
PF projection factor
h-ft2- hour per square foot per degree
°F/Btu Fahrenheit per British thermal unit R R-value (thermal resistance)
W/m.K watts per lineal meter per Kelvin RWH Rainwater Harvesting
Wh watthour S&L Standards and Labelling Program of
Definitions
BEE
BEP Best Efficiency Point
Solar PV Solar Photo-Voltaic panels
BMS Building Management System
SDG Sustainable Development Goal
BOD Biological Oxygen Demand
TDS Total Dissolved Solid
BWUE Bureau of Water Use Efficiency
TMV Thermostatic Mixing Valves
COD Chemical Oxygen Demand
TSS Total suspended Solids
COP Coefficient of Performance
VFD Variable Frequency Drive
CPCB Central Pollution Control Board
WBD Water Balance Diagram
CPHEEO Central Public Health & Environmental
Engineering Organization WPI Water Performance Index
IS Indian Standard
LPCD Litres per capita per day
Scope
is to provide norms and standards for energy
efficiency and its conservation, use of renewable
energy and other green building requirements for a
building. This Code also provides two additional sets
of incremental requirements for buildings to achieve
enhanced levels of energy efficiency and sustainability
that go beyond the minimum requirements.
Scope
Buildings intended for residential purposes are not for manufacturing processes, unless otherwise
covered under this Code. specified in the Code.
Scope
accommodation is provided in the schools,
purposes, except any building classified under colleges, or universities or coaching/ training
Health Care. Buildings and structures under institution, that portion of occupancy shall be
Hospitality shall include the following: classified as a No-star Hotel. Buildings and
I. No-star Hotels – like Lodging-houses, structures under Educational shall include
dormitories, no-star hotels/motels following types: Schools, All other types of
II. Resort institutes, e.g. college, university, training
III. Star Hotel institutes etc.
b) Health Care: Any building or part thereof, f) Shopping Complex: Any building or part
which is used for purposes such as medical or thereof, which is used as shops, stores,
other treatment or care of persons suffering market, for display and sale of merchandise,
from physical or mental illness, disease, or either wholesale or retail. Buildings like
infirmity; care of infants, convalescents, or shopping malls, stand-alone retails, open
aged persons, and for penal or correctional gallery malls, super markets, or hyper
detention in which the liberty of the inmates markets are included in this type.
is restricted. Health Care buildings ordinarily g) Mixed-use Building: In a mixed-use
provide sleeping accommodation for the building, each commercial part of a building
occupants. Buildings and structures like must be classified separately, and –
hospitals, sanatoria, out-patient healthcare, I. If a part of the mixed-use building
laboratories, research establishments, and has different classification and is less
test houses are included under this type. than 10% of the total above grade
c) Assembly: Any building or part of a building, floor area, the mixed-use building
where number of persons congregate or shall show compliance based on the
gather for amusement, recreation, social, building sub-classification having
religious, patriotic, civil, travel and similar higher percentage of above grade
purposes. Buildings like theatres or motion floor area.
picture halls, gathering halls, and transport II. If a part of the mixed-use building
buildings like airports, railway stations, bus has different classification and one
stations, and underground and elevated mass or more sub-classification is more
rapid transit system are included in this than 10% of the total above grade
group. floor area, the compliance
d) Business: Any building or part thereof which requirements for each sub-
is used for transaction of business, for classification, having area more than
keeping of accounts and records and similar 10% of above grade floor area of a
purposes, professional establishments, and mixed-use building shall be
service facilities. There are two subcategories determined by the requirements for
under Business – Daytime Business and 24- the respective building classification
hour Business. Unless otherwise mentioned, in Chapter 4 through Chapter 11.
Scope
A. Star Hotel
B. No Star Hotel
C. Resort
Scope
Hospitality
D. College
E. University
F. Institution
G. School
Educational
H. Hospital
Health Care
J. Shopping mall
M. Super Markets
Shopping Complex
N. Daytime use
Business
P. Multiplex
Q. Theatre
Assembly
Compliance
the buildings typologies shall follow any one of the c) Stilt Parking Area (𝑚2)
following methods in order to comply with the code: 2. To comply with the code through ICM, MEPI value
a) Integrative Compliance Method (ICM) shall be calculated using simulation as specified in
(Simulation approach) chapter 12 and its value rounded off to two decimal
b) Standardized Compliance Method (SCM) places in accordance with IS 2: 1960 “rules for
(Prescriptive approach) rounding off numerical values”.
3.2. Compliance Methods d) Percentage of Energy Saving (PES)
Buildings that fall under the scope of the code as The percentage of energy savings (PES) for a proposed
mentioned in Chapter 2, shall comply with the code by building represents the estimated energy savings
meeting all the mandatory requirements and any of the compared to a baseline building.
compliance methods mentioned in section 3.2.2. or 3.2.3. (𝑀𝐸𝑃𝐼𝐵𝑎𝑠𝑒𝑙𝑖𝑛𝑒 − 𝑀𝐸𝑃𝐼𝑃𝑟𝑜𝑝𝑜𝑠𝑒𝑑 )
𝑃𝐸𝑆 = ( ) ∗ 100
𝑀𝐸𝑃𝐼𝐵𝑎𝑠𝑒𝑙𝑖𝑛𝑒
3.2.1. Mandatory Requirements
Building shall comply with all mandatory requirements 1. Proposed Building shall be consistent with the
mentioned under section 4.2 through 11.2, irrespective actual design of the building and complies with all
of the compliance method. the mandatory requirements in addition to the
requirements mentioned in chapter 12.
3.2.2. Integrative Compliance Method 2. Baseline building shall have the same building floor
a) Requirement for ECSBC Compliance area, gross wall area and gross roof area as the
A building shall comply with the code using ICM if it proposed building and complies with the
meets the simulation requirements mentioned in the requirements of chapter 12.
section 12.2 & 12.3 and Table 3.1, in addition to 3. The PES of the building that demonstrate
meeting all the mandatory requirements (Refer Table compliance through ICM method shall not be
3.2). negative and shall refer to the compliance
requirements mentioned in section 12.6.
b) Requirements for ECSBC Plus and ECSBC Super
Compliance
Table 3.1: Compliance requirement under ICM (Whole building
A building shall comply with the code using ICM if it
method)
meets the simulation requirements mentioned in the
section 12.2 & 12.3 and table 3.1 meets the additional Building MEPI requirement Minimum
mandatory requirements mentioned in the section 4.3 Type PES
through 11.3 in addition to meeting all the mandatory requirement
requirements (Refer Table 3.2) ECSBC 𝑀𝐸𝑃𝐼𝐵𝑎𝑠𝑒𝑙𝑖𝑛𝑒 = 𝑀𝐸𝑃𝐼𝑃𝑟𝑜𝑝𝑜𝑠𝑒𝑑 NA
c) Modeled Energy Performance Intensity (MEPI) ECSBC 𝑀𝐸𝑃𝐼𝑃𝑟𝑜𝑝𝑜𝑠𝑒𝑑 < 𝑀𝐸𝑃𝐼𝐵𝑎𝑠𝑒𝑙𝑖𝑛𝑒 Section 12.6
Plus
1. The MEPI of a building is its annual energy
consumption in kilowatt-hour per square meter of Super 𝑀𝐸𝑃𝐼𝑃𝑟𝑜𝑝𝑜𝑠𝑒𝑑 < 𝑀𝐸𝑃𝐼𝐵𝑎𝑠𝑒𝑙𝑖𝑛𝑒 Section 12.6
ECSBC
the building. MEPI can be determined by:
𝑘𝑊ℎ
(𝑇𝑜𝑡𝑎𝑙 𝐴𝑛𝑛𝑢𝑎𝑙 𝐸𝑛𝑒𝑟𝑔𝑦 𝐶𝑜𝑛𝑠𝑢𝑚𝑝𝑡𝑖𝑜𝑛 (𝑦𝑒𝑎𝑟))
𝑀𝐸𝑃𝐼 =
𝑁𝑒𝑡 𝐵𝑢𝑖𝑙𝑡𝑈𝑝 𝐴𝑟𝑒𝑎 (𝑚2 )
Compliance
if it meets the standardized requirement
mentioned in the section 5.3 through 8.3, in d) Total System Efficiency
addition to meeting all the mandatory For projects using central chilled water plants,
requirements (Refer Table 3.3). the total system efficiency (TSE) approach can
2. ECSBC buildings that demonstrate compliance be used.. This approach may be used in place of
through SCM shall be deemed to have PES as the standardized requirement criteria of central
defined in section 12.5.3. chilled water plant side systems comprises
b) Requirement for ECSBC + & super ECSBC chillers, chilled water pumps, condenser water
Compliance pumps, and cooling tower fans Per this
1. A building shall comply with the code using approach, a building complies if the TSE
SCM if it meets the standardized thresholds are met as per table 6-25 maximum
requirements mentioned in the section 5.3 system efficiency threshold for ECSBC, ECSBC
through 8.3 and the additional mandatory Plus, and super ECSBC Buildings. Compliance
requirements mentioned in section 4.3 with other standardized requirement of
through 11.3, in addition to meeting all the section6.3, as applicable, shall be met.
mandatory requirements (Refer Table 3.3). e) Low Energy Comfort Systems
2. ECSBC Plus and Super ECSBC buildings that Low Energy Comfort Systems, is a simplified
demonstrate compliance through the SCM approach that provides projects using Low
shall be deemed to have PES as defined in Energy Comfort Systems an opportunity to
section 12.5.3. achieve improved compliance levels of ECSBC
c) Building Envelope Trade-off Method plus and super ECSBC. In addition to
To comply with the SCM the Building Envelope compliance with the applicable standardized
Trade-off Method can be used in place of the requirement of section 6.3, the projects must
standardized requirement of section 5.3.1, 5.3.2 meet the sum of cooling and heating
and 5.3.3. A building complies with the Code requirement using approved list of low energy
using the building envelope trade-off method if systems as per requirements specified in
section 6.3.13.
Table3.2: Section required to be followed for ECSBC, ECSBC plus and Super ECSBC compliance with Integrative Compliance Method
(ICM)
Compliance
Table 3.3: Section required to be followed for ECSBC, ECSBC plus and Super ECSBC compliance with Standardized Compliance
Method (SCM)
Mandatory Requirements for Additional Mandatory Requirements for Standardized Requirements for
ECSBC, ECSBC plus and Super
ECSBC, ECSBC plus and Super ECSBC ECSBC plus and Super ECSBC ECSBC
Section 4.2 Section 4.3
Section 5.2 Section 5.3
Section 6.2 Section 6.3
Section 7.2 Section 7.3
Section 8.2 Section 8.3
Section 9.2 Section 9.3
Section 10.2 Section 10.3
Section 11.2 Section 11.3
Compliance
this Code that shall apply to the entire building, lighting shutoff, occupancy sensors, and other
as if it were a new building. lighting controls; lamp efficacy for exterior lamps;
Exceptions to 3.3.2: d. Electrical Power: electric schedule showing
transformer losses, motor efficiencies, and power
When space conditioning is provided by existing systems
factor correction devices; electric check metering
and equipment, the existing systems and equipment need
and monitoring system.
not comply with this code. However, any new equipment
e. Renewable energy systems: system peak installed
installed must comply with specific requirements
capacity, technical specifications, solar zone area.
applicable to that equipment.
f. Sustainable Sites & Planning
3.4. Approved Compliance Tools g. Water Management and Controls
A building following the whole building performance h. Waste Management
method of chapter 12 or Total System Efficiency – i. Indoor Environment Quality and other relevant
Alternate compliance approach (section 6.3.12) shall parameters.
show compliance through energy simulation software 3.7. Supplemental Information
endorsed by BEE.
The authority having jurisdiction may require
3.5. Administrative Requirements supplemental information necessary to verify
Administrative requirements, including but not limited compliance with this code, such as calculations,
to, permit requirements, enforcement, interpretations, worksheets, compliance forms, manufacturer’s
claims of exemption, approved calculation methods, and literature, or other data.
rights of appeal are specified by the authority having
jurisdiction.
3.6. Compliance Documents
Construction drawings and specifications shall show all
pertinent data and features of the building, equipment,
and systems in sufficient detail to permit the authority
having jurisdiction to verify that the building complies
with the requirements of this code. Details shall include,
but are not limited to:
a. Building Envelope: opaque construction materials
and their thermal properties including thermal
conductivity, specific heat, density along with
thickness; fenestration U-factors, solar heat gain
coefficients (SHGC), visible light transmittance
(VLT) and building envelope sealing documentation;
overhangs and side fins, building envelope sealing
details;
b. Heating, Ventilation, and Air Conditioning: system
and equipment types, sizes, efficiencies, and
controls; economizers; variable speed drives; piping
insulation; duct sealing, insulation and location;
Building Envelope
and the Standardized requirements as specified in Standard for respective insulation type by an
section 5.3. accredited independent laboratory, and labelled or
certified by the manufacturer. For unrated products,
5.2 Mandatory Requirements use the default tables in Appendix A.
5.2.1 Fenestration (b) Solar Reflectance
(a) U-Factor Solar reflectance for the external opaque roof
U-factors shall be determined for the overall construction material shall be determined in
fenestration product (including the sash and frame) accordance with ASTM E903-96 by an accredited
in accordance with ISO-15099 by an accredited
independent laboratory and labelled by the
independent laboratory or labelled by the
manufacturer.
manufacturer. U-factors for sloped glazing and
skylights shall be determined at a slope of 20 degrees (c) Emittance
above the horizontal. For unrated products, see the Emittance for the external opaque roof construction
default value given in Appendix A of chapter 14.
shall be determined in accordance with ASTM E408-
(b) Solar Heat Gain Coefficient (SHGC) 71 (RA 2008) by an accredited independent
SHGC shall be determined for the overall single or laboratory, and labelled by the manufacturer.
multi glazed fenestration product (including the sash
5.2.3 Daylighting and Visual Comfort
and frame) in accordance with ISO-15099 by an
Compliance for daylighting may be demonstrated
accredited independent laboratory or labelled or
either with simulation using the Useful Daylight
certified by the manufacturer.
Simulation compliance path as defined in section
Notes: 5.2.3-(a) or through the Spatial Daylight Autonomy
Part as defined in section 5.2.3 (d). Compliance may
Exceptions to section 5.2.1-(a): also be demonstrated as per manual method in
1. Shading coefficient (SC) of the centre of glass section 5.2.3-(c). For Whole Building simulation, the
alone multiplied by 0.86 is an acceptable standard building shall be modelled with daylight
alternate for compliance with the SHGC sensors located within 6m from the building
requirements for the overall fenestration area. periphery.
2. Solar heat gain coefficient (SHGC) of the glass (a) Useful daylight illuminance
alone is an acceptable alternate for compliance Above grade floor areas shall meet the useful
with the SHGC requirements for the overall daylight illuminance (UDI) area requirements listed
fenestration product. in Table 5.1 for 90% of the potential daylit time in a
(c) Visible Light Transmittance (VLT) year. Exceptions to section 5.2.3 Assembly buildings
Visible light transmittance (VLT) shall be determined and other buildings where daylighting will interfere
for the fenestration product in accordance with ISO- with the functions of 50% (or more) of the building
15099 by an accredited independent laboratory or floor area, are exempted from meeting the
labelled by the manufacturer. For unrated products, requirements listed in Table 5.1.
VLT of the glass alone shall be derated by 10% for Table 5.1 Daylight Requirement
demonstrating compliance with the VLT
requirements for the overall fenestration product.
Building Envelope
ECSBC 30% and 0% shall be used for all vertical
Business, 40% 50% 60% surfaces of man-made and natural obstructers
Educational respectively.
V. Interior surface reflectance shall be modelled
No Star Hotel 30% 40% 50%
based on the actual material specification. If
Star Hotel
material specification is not available, the default
Healthcare
values in Table 5.2 shall be used.
Resort 45% 55% 65%
VI. Documentation requirement to demonstrate
Shopping Complex 10% 15% 20% compliance are:
i. Brief description of the project with
Assembly Exempted location, number of stories, space types,
hours of operation and software used.
(b) Useful Daylight Illumination (UDI) Simulation ii. Summary describing the results of the
Method analysis and output file from simulation
A software validated by an appropriate authority and tool outlining point wise compliance for the
approved by BEE shall be used to demonstrate analysis grid and compliance in percentage.
compliance through the UDI simulation method. iii. Explanation of any significant modelling
Buildings shall achieve illuminance level between assumptions made.
100 lux and 2,000 lux for the minimum percentage of iv. Explanation of any error messages noted in
floor area prescribed in Table 5.1 for at least 90% of the simulation program output.
the potential daylit time. v. Building floor plans, building elevations &
sections, and site plan with surrounding
Illuminance levels for all spaces enclosed by
building details (if modelled).
permanent internal partitions (opaque, translucent,
vi. Material reflectance, analysis grid size, total
or transparent) with height greater or equal to 2 m
number of grid size/resolution, total
from the finished floor, shall be measured as follows:
number of grid points.
I. Measurements shall be taken at a work plane
height of 0.8 m above the finished floor. The
Table 5.2 Default Values for Surface Reflectance
period of analysis shall be fixed for continuously
Surface Type Reflectance
minimum 8 hours per day between 7:00 AM to
5:00 PM IST, resulting in maximum 2,920 hours Wall or Vertical 50%
in total for all building types except for school. Internal Surfaces
Schools shall be analyzed for continuously Ceiling 70%
minimum 7 hours per day between 7:00 AM to
3:00 PM IST. Floor 20%
II. Available useful daylight across a space shall be
Furniture (permanent) 50%
measured based on point-by-point grid values.
UDI shall be calculated for at least one point for
each square meter of floor area.
III. Fenestration shall be modelled with actual
visible light transmission (VLT) as per the details
provided in the material specification sheet.
IV. All surrounding natural or man-made daylight
obstructions shall be modelled if the distance
between the façade of the building (for which
Building Envelope
percentage of above grade floor area meeting the UDI distance to an adjacent skylight or vertical
requirement for 90% of the potential daylit time in a glazing, whichever is least.
year. (iv) Glazed façades, with non-cardinal orientation,
shall be categorized under a particular cardinal
I. To calculate the daylit area: direction if its orientation is within ± 45 degrees
(i) In a direction perpendicular to the fenestration, of that cardinal direction.
multiply daylight extent factor (DEF) by the head (v) Daylit area overlap: For overlapping daylit areas
height of the fenestration or till an opaque such as windows on different orientations or in
partition higher than head height of the case of skylights the overlapping daylit area shall
fenestration, whichever is less. be subtracted from the sum of daylit area.
(ii) In the direction parallel to the fenestration, daylit
area extends a horizontal dimension equal to the Documentation requirement:
width of the fenestration plus either 1 meter on
each side of the aperture, or the distance to an (i) A separate architectural plan shall be prepared
opaque partition of 2 m high, or one-half the with all daylit areas marked on the floor plans.
distance to an adjacent fenestration, whichever is (ii) A summary shall be provided showing
least. compliance as per Table 5.1.
(iii) For skylights, calculate the horizontal dimension
in each direction equal to the top aperture
Table 5.4 Daylight Extent Factors (DEF) for Manually Calculating Daylight Area
Shading Latitude Window Type VLT < 0.3 VLT ≥0.3
No ≥15°N All 2.5 2.0 0.7 0.5 2.8 2.2 1.1 0.7
shading
or PF < window types
< 15°N 2.4 2.0 0.8 0.6 2.7 2.2 1.5 0.8
0.4
Shading All All 2.8 2.3 1.5 1.1 3.0 2.5 1.8 1.5
with PF latitudes
≥ 0.4 window types without
light shelf*
Window with light 3.0 2.5 1.8 1.6 3.5 3.0 2.1 1.8
shelf*
* To qualify as light shelf the internal projection shall meet the requirements specified under Exceptions to SHGC
requirements in Table 5.9 to Table 5.11.
Composite
dry
Hot and
humid
Warm and
Temperate
Cold
through table 5.12
Building Envelope
Table 5.6 Opaque Assembly Maximum U-factor (W/m2.K)
Requirements for ECSBC compliant Building
All building 0.26 0.26 0.26 0.26 0.20
types, except
below
Composite
dry
Hot and
humid
Warm and
e
Temperat
Cold
Assembly 0.20 0.20 0.20 0.20 0.20
Hospitality >
10,000 m2 AGA
All building types, 0.40 0.40 0.40 0.55 0.34
Table 5.4 Roof Assembly U-factor (W/m2.K) Requirements for except below
ECSBC+ Compliant Building No Star Hotel < 0.63 0.63 0.63 0.63 0.40
10,000 m2 AGA
Composite
dry
Hot and
humid
Warm and
Temperate
Cold
Business < 10,000 0.63 0.63 0.63 0.63 0.40
m2 AGA
School <10,000 m2 0.85 0.85 0.85 1.00 0.40
AGA
All Building 0.20 0.20 0.20 0.20 0.20
Types
Table 5.7 Opaque Assembly Maximum U-factor (W/m2.K)
Requirements for ECSBC+ Compliant Building
Table 5-5 Roof Assembly U-factor (W/m2.K) Requirements for
Composite
humid
Warm and
Temperate
Cold
SuperECSBC Building
Composite
dry
Hot and
humid
and
Warm
e
Temperat
Cold
humid
Warm and
Temperate
Cold
Composite
dry
Hot and
humid
Warm and
Temperate
Cold
efficiency levels, i.e. ECSBC, ECSBC+, and Super
ECSBC, shall comply with the following:
Building Envelope
1. Maximum allowable Window Wall Ratio Maximum U-factor 1.80 1.80 1.80 2.20 1.80
(WWR) is 40% (applicable to buildings showing (W/m².K)
compliance using the Standrdized Method, Maximum SHGC 0.20 0.20 0.20 0.20 0.62
Non-North
including Building Envelope Trade-off Method) Maximum SHGC 0.50 0.50 0.50 0.50 0.62
2. Minimum allowable Visible light transmittance North
(VLT) is 0.27 for latitude ≥ 15°N
Maximum SHGC 0.20 0.20 0.20 0.20 0.62
3. Assembly U-factor shall be determined for the North
overall fenestration product (including the sash for latitude < 15°N
and frame)
Vertical fenestration shall comply with the maximum Table 5.11 Vertical Fenestration U-factor and SHGC Requirements
for Super ECSBC buildings
Solar Heat Gain Coefficient (SHGC) and U-factor
requirements of Table5-13 for ECSBC buildings and
table 5.14 for ECSBC+ buildings and table 5.15 Super
ECSBC buildings. Vertical fenestration on non-
Composite
dry
Hot and
humid
Warm and
Temperate
Cold
cardinal direction, shall be categorized under a
particular cardinal direction if its orientation is
within ± 45° of that cardinal direction.
Maximum U-factor 1.80 1.80 1.80 2.20 1.80
Table 5.9 Vertical Fenestration Assembly U-factor and SHGC (W/m².K)
Requirements for ECSBC Buildings Maximum SHGC Non- 0.25 0.25 0.25 0.25 0.62
North
Maximum SHGC North 0.50 0.50 0.50 0.50 0.62
for latitude ≥ 15°N
Composite
dry
Hot and
humid
Warm and
Temperate
Cold
Building Envelope
each fin shall be considered. Other shading elevation is less than 0.25, including all
devices shall be modelled through the fenestration areas more than 1.0 meter above the
Whole Building Performance Method in floor level; and,
chapter 12. ii. An interior light shelf is provided at the bottom of
(ii) A shaded vertical fenestration on a non- this fenestration area, with a projection factor on
cardinal direction, shall be categorized interior side not less than:
either under a particular cardinal direction a. 1.0 for E-W, SE, SW, NE, and NW orientations
or a primary inter-cardinal direction if its b. 0.50 for S orientation, and
orientation is within the range of ±22.5o of c. 0.35 for N orientation when latitude is less than
the cardinal or primary inter-cardinal 15°N.
direction.
(iii) Any surrounding man-made or natural
sunlight obstructers shall be considered as a
permanent shading of PF equal to 0.4 if;
North-
North-
South-
South-
North
South
West
West
West
East
East
East
SEF
PF
Building Envelope
0.25 1.25 1.37 1.58 1.36 1.47 1.47 1.42 1.53
0.3 1.29 1.48 1.72 1.43 1.54 1.65 1.57 1.58
0.35 1.34 1.58 1.88 1.51 1.62 1.81 1.73 1.65
0.4 1.39 1.67 2.06 1.61 1.70 1.97 1.89 1.75
0.45 1.43 1.76 2.26 1.71 1.78 2.11 2.06 1.87
0.5 1.47 1.85 2.47 1.83 1.86 2.25 2.23 2.00
Overhang + Fins
North-
North-
South-
South-
North
South
West
West
West
East
East
East
SEF
PF
Building Envelope
0.25 1.38 1.33 1.30 1.34 1.42 1.41 1.37 1.42
0.3 1.44 1.42 1.35 1.42 1.49 1.46 1.41 1.52
0.35 1.50 1.50 1.42 1.50 1.57 1.52 1.47 1.63
0.4 1.56 1.59 1.50 1.59 1.66 1.59 1.54 1.73
0.45 1.61 1.67 1.59 1.69 1.76 1.67 1.61 1.84
0.5 1.67 1.76 1.68 1.80 1.87 1.75 1.70 1.94
Overhang + Fins
Building Envelope
Table 5.15 Skylight U-factor (W/m2.K) and SHGC
Table 5.14 U-factor (W/m2.K) Exemption Requirements for Requirements
Shaded Building Maximum U- Maximum
Climate
Building Clima Orientati Maxim Minim PF factor SHGC
Type te on um um VLT All climatic 4.25 0.35
zone Effectiv zones
e SHGC
Exception to section 5.3.4 Skylights in temporary
Unconditio All Non- 0.27 0.27 ≥0.4
ned excep North 0 roof coverings or awnings over unconditioned
buildings t cold for all spaces
or latitudes
unconditio and
ned spaces North
5.3.5 Building Envelope Trade-Off Method
for The building envelope complies with the code if the
latitude Envelope Performance Factor (EPF) of the Proposed
< 15°N
North 0.27 0.27 ≥0.0 Building is less than the EPF of the Standard Building, where
for the Standard Building exactly complies with the
latitude Standrdized requirements of building envelope. This
≥ 15°N
method shall not be used for buildings with WWR>40%.
5.3.4 Skylights Trade-off is not permitted for skylights. Skylights
Skylights shall comply with the maximum U-factor shall meet requirements of section 5.3.4. The envelope
and maximum SHGC requirements of Table 5.19. performance factor shall be calculated using the following
Skylight roof ratio (SRR), defined as the ratio of the equations.
total skylight area of the roof, measured to the
𝐸𝑃𝐹𝑅𝑜𝑜𝑓 = 𝑐𝑅𝑜𝑜𝑓 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
𝑛
𝐸𝑃𝐹𝑊𝑎𝑙𝑙 = 𝑐𝑊𝑎𝑙𝑙 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
𝑛 𝑛 𝑛
𝑆𝐻𝐺𝐶𝑤
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 = 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑁𝑜𝑟𝑡ℎ ∑ 𝑈𝑤 𝐴𝑤 + 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑁𝑜𝑟𝑡ℎ ∑ 𝐴𝑤 + 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑜𝑢𝑡ℎ ∑ 𝑈𝑤 𝐴𝑤
𝑆𝐸𝐹𝑤 ⬚
𝑤=1 𝑤=1 𝑤=1
𝑛 𝑛 𝑛
𝑆𝐻𝐺𝐶𝑤 𝑆𝐻𝐺𝐶𝑤
+ 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑜𝑢𝑡ℎ ∑ 𝐴𝑤 + 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝐸𝑎𝑠𝑡 ∑ 𝑈𝑤 𝐴𝑤 + 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝐸𝑎𝑠𝑡 ∑ 𝐴𝑤
𝑆𝐸𝐹𝑤 𝑆𝐸𝐹𝑤
𝑤=1 𝑤=1 𝑤=1
𝑛 𝑛
𝑆𝐻𝐺𝐶𝑤
+ 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑊𝑒𝑠𝑡 ∑ 𝑈𝑤 𝐴𝑤 + 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑊𝑒𝑠𝑡 ∑ 𝐴𝑤
𝑆𝐸𝐹𝑤
𝑤=1 𝑤=1
Whereas
EPFRoof Envelope performance factor for roofs. Other subscripts include walls and fenestration.
As, Aw The area of a specific envelope component referenced by the subscript "s" or for windows the subscript "w".
SHGCw The solar heat gain coefficient for windows (w).
SEFw A multiplier for the window SHGC that depends on the projection factor of an overhang or side fin.
Us The U-factor for the envelope component referenced by the subscript "s".
Building Envelope
Values of "c" are taken from table 5.18 through table 5.22 for Roofs 40.1 - 76.1 -
each class of construction. North
20.7 230.7 43.6 401.5
Windows
Table 5.16 Envelope Performance Factor Coefficients – South
20.1 347.1 43.9 546.4
Composite Climate Windows
Daytime Business, 24-hour Business, East
19.0 301.8 41.1 490.6
Educational, Hospitality, Health Windows
Shopping Complex Care, Assembly West
18.7 303.1 40.5 483.5
C factor C factor C factor C factor Windows
U-factor SHGC U-factor SHGC
Walls 24.3 - 48.1 - Table 5.19 Envelope Performance Factor Coefficients –
Roofs Temperate Climate
40.9 - 71.0 -
Daytime Business, 24-hour Business,
North Educational, Hospitality, Health
21.6 201.8 41.0 367.6
Windows Shopping Complex Care, Assembly
South C factor C factor C factor C factor
19.1 342.5 41.0 546.3
Windows U-factor SHGC U-factor SHGC
East Walls
18.8 295.6 38.4 492.2 17.2 - 39.1 -
Windows
West Roofs 32.3 - 76.1 -
19.2 295.4 38.3 486.1
Windows
North
12.6 201.4 32.3 338.41
Windows
Table 5.17 Envelope Performance Factor Coefficients – Hot South
11.8 287.3 31.9 448.52
and Dry Climate Windows
Daytime Business, 24-hour Business, East
11.2 300.0 29.9 470.35
Educational, Hospitality, Health Windows
Shopping Complex Care, Assembly West
10.9 303.4 30.0 462.64
C factor C factor C factor C factor Windows
U-factor SHGC U-factor SHGC
Walls 27.3 - 55.9 -
Roofs
Table 5-20 Envelope Performance Factor Coefficients – Cold
43.9 - 80.7 - Climate
North Daytime Business, 24-hour Business,
23.7 238.2 49.1 414.4
Windows Educational, Hospitality, Health
South Shopping Complex Care, Assembly
22.8 389.7 49.2 607.4
Windows C factor C factor C factor C factor
East U-factor SHGC U-factor SHGC
21.6 347.4 46.2 556.2
Windows Walls 36.3 - 30.7 -
West
21.7 354.1 46.0 560.8 Roofs
Windows 38.7 - 46.0 -
North
21.8 137.6 28.3 163.86
Table 5.18 Envelope Performance Factor Coefficients – Windows
Warm and Humid Climate South
20.8 114.3 21.7 295.24
Daytime Business, 24-hour Business, Windows
Educational, Hospitality, Health East
22.7 127.5 24.1 283.20
Shopping Complex Care, Assembly Windows
C factor C factor C factor C factor West
23.4 133.2 25.2 270.33
U-factor SHGC U-factor SHGC Windows
Walls 24.5 - 51.2 -
(a) Standard Building EPF Calculation (a) The Standard Building shall have the same
EPF of the Standard Building shall be calculated as building floor area, gross wall area and gross
follows: roof area as the Proposed Building. For mixed-
use building the space distribution between
The U-factor of each envelope component shall be Shading devices shall not be considered for
equal to the criteria from section5.3 for each class of calculating EPF for Standard Building (i.e. SEF=1).
Building Envelope
construction.
Building Envelope
A 1,000 m2 single story daytime use office building in Ahmedabad is trying to achieve ECSBC level compliance. Each side has
a band of windows, without shading. The materials for the envelope have already been selected, prior to opting for ECSBC
compliance. Their thermal properties are: roof assembly U-value= .4 W/m².K, external wall assembly U-value = .25 W/m².K,
glazing SHGC = .25, VLT = 0.27, area weighted U-value for glazing = 1.8 W/m².K. Dimensions of the building envelope are as
follows:
According to Appendix B, Ahmedabad falls under the hot and dry climate zone. To prove compliance through the
Standardised approach, U-factor, and SHGC must comply with requirements listed in table 5.7, 5-10, 5-13 and VLT and
window to wall ratio with requirements in section 5.3.3 for a daytime use building in the hot and dry climate zone. The table
below lists thermal properties of the building envelope components and the corresponding Standardised requirements for
ECSBC complaint buildings.
Building Envelope
Compliance through Building Envelope Trade-off method
Envelope performance factor (EPF) for the Standard Building and Proposed Building must be compared. As per the Building
Envelope Trade-off method, the envelope performance factor (EPF) shall be calculated using the following equations:
EPFTotal = EPFRoof + EPFWall + EPFFenest
Where,
𝑛
𝐸𝑃𝐹𝑅𝑜𝑜𝑓 = 𝐶𝑅𝑜𝑜𝑓 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
𝑛
𝐸𝑃𝐹𝑊𝑎𝑙𝑙 = 𝐶𝑊𝑎𝑙𝑙 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
𝑛
𝑛 𝑛
𝑆𝐻𝐺𝐶𝑤
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 = 𝐶1𝐹𝑒𝑛𝑒𝑠𝑡,𝑁𝑜𝑟𝑡ℎ ∑ 𝑈𝑤 𝐴𝑤 + 𝐶2𝐹𝑒𝑛𝑒𝑠𝑡,𝑁𝑜𝑟𝑡ℎ ∑ 𝐴 + 𝐶1𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑜𝑢𝑡ℎ ∑ 𝑈𝑤 𝐴𝑤
𝑆𝐸𝐹𝑤 𝑤
𝑤=1 𝑤=1
𝑤=1
𝑛 𝑛
𝑛
𝑆𝐻𝐺𝐶𝑤 𝑆𝐻𝐺𝐶𝑤
+ 𝐶2𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑜𝑢𝑡ℎ ∑ 𝐴 + 𝐶1𝐹𝑒𝑛𝑒𝑠𝑡,𝐸𝑎𝑠𝑡 ∑ 𝑈𝑤 𝐴𝑤 + 𝐶2𝐹𝑒𝑛𝑒𝑠𝑡,𝐸𝑎𝑠𝑡 ∑ 𝐴
𝑆𝐸𝐹𝑤 𝑤 𝑆𝐸𝐹𝑤 𝑤
𝑤=1
𝑤=1 𝑤=1
𝑛
𝑛
𝑆𝐻𝐺𝐶𝑤
+ 𝐶1𝐹𝑒𝑛𝑒𝑠𝑡,𝑊𝑒𝑠𝑡 ∑ 𝑈𝑤 𝐴𝑤 + 𝐶2𝐹𝑒𝑛𝑒𝑠𝑡,𝑊𝑒𝑠𝑡 ∑ 𝐴
𝑆𝐸𝐹𝑤 𝑤
𝑤=1
𝑤=1
Standard Building EPF will be derived from U-factors, SHGCs and VLTs of walls, roofs and fenestration Table 5.7, 5-10, 5-13
and section 5.3.3 for a daytime use building in the hot and dry climate zone. Values of C are from daytime Office building in
hot and dry climatic zone for each class of construction from Table 5.21. Since There is no shading for the windows, SEFw
will not be considered.
Step 1: Calculation of EPF Proposed Building from actual envelope properties
𝑛
𝐸𝑃𝐹𝑅𝑜𝑜𝑓,𝐴𝑐𝑡𝑢𝑎𝑙 = 𝐶𝑅𝑜𝑜𝑓 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
𝐸𝑃𝐹𝑊𝑎𝑙𝑙,𝐴𝑐𝑡𝑢𝑎𝑙 = 𝐶𝑊𝑎𝑙𝑙 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
Hence,
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝑁𝑜𝑟𝑡ℎ = 23.7 x 1.8 x 30 + 238.2 x 0.25 x 30 = 1,279.8 + 1,786.5 = 3,066.3
Building Envelope
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝑆𝑜𝑢𝑡ℎ = 22.8 x 1.8 x 30 + 389.7 x 0.25 x 30 = 1,231.2 + 2,922.75 = 4,153.95
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝐸𝑎𝑠𝑡 = 21.6 x 1.8 x 48 + 347.4 x 0.25 x 48 = 1,866.24 + 4,168.8 = 6,035.04
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝑊𝑒𝑠𝑡 = 21.7 x 1.8 x 48 + 354.1 x 0.25 x 48 = 1,874.88 + 4,249.2 = 6,124.08
Therefore,
𝐸𝑃𝐹𝐹e𝑛𝑒𝑠𝑡 = 19,379.37
𝐸𝑃𝐹𝑃𝑟𝑜𝑝𝑜𝑠𝑒𝑑 = 17,560 + 1,597.05 + 19,379.37 = 38,536.42
𝐸𝑃𝐹𝑅𝑜𝑜𝑓,𝐴𝑐𝑡𝑢𝑎𝑙 = 𝐶𝑅𝑜𝑜𝑓 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
𝐸𝑃𝐹𝑊𝑎𝑙𝑙,𝐴𝑐𝑡𝑢𝑎𝑙 = 𝐶𝑊𝑎𝑙𝑙 ∑ 𝑈𝑠 𝐴𝑠
𝑠=1
Now,
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝑁𝑜𝑟𝑡ℎ = 23.7 x 3.0 x 30 + 238.2 x 0.5 x 30 = 2,133 + 3,573 = 5,706
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝑆𝑜𝑢𝑡ℎ = 22.8 x 3.0 x 30 + 389.7 x 0.27 x 30 = 2,052 + 3,156.57 = 5,208.57
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝐸𝑎𝑠𝑡 = 21.6 x 3.0 x 48 + 347.4 x 0.27 x 48 = 3,110.4 + 4,502.3 = 7,612.7
𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 , 𝑊𝑒𝑠𝑡 = 21.7 x 3.0 x 48 + 354.1 x 0.27 x 48 = 3,124.8 + 4,589.14 = 7,713.94
Since 𝐸𝑃𝐹𝐵𝑎𝑠𝑒𝑙𝑖𝑛𝑒 > 𝐸𝑃𝐹𝑃𝑟𝑜𝑝𝑜𝑠𝑒𝑑 , therefore the building is compliant with ECSBC building envelope requirements.
System and Co
All HVAC equipment and systems and their controls equal to 600 m2
shall comply with the mandatory provisions of Section I. (c) Demand Control ventilation
6.2 and the Standardized requirement criteria detailed Mechanical ventilation systems serving Air
in section 6.3 for the respective building energy conditioning spaces shall have demand control
efficiency level. In case alternative compliance path of ventilation if they provide outdoor air greater than
total system efficiency or low energy systems is used 5400 m3/hr to the conditioned space.Such
for compliance, respective requirements of outdoor air supply to the space shall be through:
Section6.3.11 or Section6.3.12 and relevant criteria of 1. An air side economizer, or
Section 6.3 shall be complied. 2. Automatic modulating control of the outdoor
6.2. Mandatory Requirements air damper actuated through 𝐶𝑂2 sensors
mounted within the space (CO2 sensors shall
6.2.1. Ventilation
be mounted at breathing height level and shall
All habitable spaces shall be ventilated with outdoor be provided for any space greater than 50
air in accordance with the requirements of Section m2).
6.2.1 and guidelines specified in the National Building
Demand control ventilation (DCV) if employed,
Code 2016 or its subsequent revisions (Part 8:
shall ensure that outdoor air supply to the space
Building Services, Section 1: Lighting and Natural
meets the minimum ventilation requirement as
Ventilation, Subsection 5: Ventilation).
specified in NBC-2016 or its subsequent revisions.
Ventilated spaces shall be provided with outdoor air
Exception to 6.2.1-(c):
using one of the following:
1. Any space that has processes or operations that
(a) Natural Ventilation
generate dust, fumes, mists, vapours or gases
(b) Mechanical Ventilation
and are provided with mechanical exhaust.
(c) Mixed Mode Ventilation
2. Systems with exhaust air energy recovery.
a) Natural ventilation design requirements:
6.2.2. Space Conditioning Equipment
Naturally ventilated buildings shall meet the following
a) Chillers
requirements.
1. For ECSBC Compliance minimum BEE 2 Star
1. Comply with guideline provided for natural
ventilation in NBC. rated chillers shall be installed.
2. If the building has ceiling fans, they shall comply 2. At locations where cooling water and / or
with the requirements of BEE 4-star rating at the recycled water is available, water-cooled
minimum. chillers should be installed. Air-cooled
3. Air circulators, if provided, shall comply with IS systems or Hybrid configurations (Mix of
2997. Water Cooled and Air Cooled) should be used
4. Exhaust fans, if provided, shall comply IS 2312 in buildings with cooling load less then 530
with minimum efficiency requirements of fans kWr. For buildings with cooling load equal to
specified in Section 6.3.1. or greater than 530 kWr, the capacity of air-
cooled chiller shall be restricted to 33% of the
b) Mechanical ventilation & air quality design total installed chilled water plant capacity
requirement (excluding standby, if any). Local approving
Buildings that are ventilated using a mechanical authority / Authority Having Jurisdiction
ventilation system, either completely or in (AHJ) may require a higher percentage of air-
conjunction with natural ventilation systems, shall cooled chillers in a project depending on local
System and Co
Unitary (Window) and Split air-conditioners which d) Air Conditioning and Condensing Units serving
are non- ducted and have a capacity up to 10499 Wr Computer Rooms and other special
and light commercial air conditioners from 10500 to applications
18000 Wr ( All air cooled systems ) shall comply with
1. Air conditioning and condensing units serving
IS1391 Part 1 and Part 2 are shall meet or exceed the
computer rooms shall be of minimum energy
efficiency requirements as per BEE 3 Star rating.
efficiency as per the Table 6-3.
Ducted and Packaged air conditioners of capacity above 2. In respect of 24-hour operational areas such
3500 Wr shall comply with IS 8148 for both air cooled as server or battery rooms in otherwise 8 or
and water cooled systems and the minimum efficiency 12-hour occupancies, separate air
requirements shall be as per Table 6.1.Table 6.1 Minimum conditioning units shall be installed. These
Efficiency Requirements for Ducted Split and Packaged Air
units can act as standby units when the central
Conditioners in ECSBC Building
system is operational but can take over when
Cooling Water Cooled Air Cooled the central system is shut down. Similarly, in
Capacity (kWr)
areas where temperatures lower than those to
≤ 10.5 NA BEE 3 Star be maintained in other areas of the building
are required, such as operation theatres in
> 10.5 3.3 EER 2.8 EER
hospitals, separate condensing units shall be
Note: The EER values in Table 6.1 will be replaced by installed. This arrangement ensures that the
IEER values in respect of units of capacity more than central system can operate with higher
10500Wr when the BEE Star Labelling Program is made efficiency.
effective for this range. Minimum efficiency levels for Air
Table 6.3 Minimum Efficiency Requirements for Computer
Cooled as well as Water Cooled systems shall comply
Room Air Conditioners
with BEE 3 Star for ECSBC Buildings.
Equipment Net Sensible Minimum SCOP-127
type Cooling
Downflow Upflow
c) Variable Refrigerant Flow (VRF air- Capacity
conditioners) All types of
Variable Refrigerant Flow (VRF) systems shall be of the computer
All capacity 2.5 2.5
minimum efficiency requirements as specified in Table room Acs Air/
6-2 tested at the capacity rating condition as defined. Water/ Glycol
Rating conditions both at full load as well as part load a. Net Sensible cooling capacity = Total gross cooling
conditions shall be as per BIS Standard for VRF Air capacity - latent cooling capacity – Fan power
Conditioners which is under development. b. Sensible Coefficient of Performance (SCOP-127): A ratio
Table 6.2 Minimum Efficiency Requirement for VRF Air Conditioners calculated by dividing the net sensible cooling capacity in
for ECBC Building watts by the total power input in watts (excluding
For Heating or Cooling or Both reheater and dehumidifier) at conditions defined in
ASHRAE Standard 127-2012 Method of Testing for Rating
Type Size Category (kWr) ISEER (W/W) Computer and Data Processing Room Unitary Air
VRF Air <40 5.4 Conditioners)
Conditioners,
≥ 40 and < 70 5.5
Air Cooled
≥ 70 5.6
System and Co
supply of heating and cooling energy to the zone is
systems shall be achieved through any one of the
shut off or reduced to a minimum.
following methods:
II. Where separate heating and cooling equipment
1. Solar water heating system shall comply with IS serve the same temperature zone, temperature
12976 and shall be minimum BEE 3-star rated. controls shall be interlocked to prevent
2. Heat recovery systems using waste heat from air/ simultaneous heating and cooling.
water cooled condensers. III. Separate temperature control shall be installed in
3. Air to water or water to water heat pumps. each:
Note: The use of electric, gas, or oil-fired boilers shall be 1. Guest room of hotels and resorts,
discouraged in ECSBC buildings unless they are required 2. Room less than 30 m2 in business building.
for any process requirements and by-product steam or 3. Air-conditioned classroom, lecture room, and
by-product hot water is available for heating or reheat computer room of educational institutions.
purposes. 4. In-patient rooms and wards in healthcare
For service water heating in the building, please refer facilities.
to Section 9. c) Occupancy Controls
6.2.3. Controls Occupancy controls shall be installed at each zone level
To comply with the Code, buildings shall meet the to de-energize fresh air ventilation and/or air
requirements of Section (a) to (f) of 6.2.3. conditioning systems when the building, part of the
building, or individual zones served by that system are
a) Timeclock
not occupied (ex. hotel guest rooms, office cabins,
Mechanical cooling and heating systems in all conference rooms in different building typologies,
occupancies other than healthcare, shall be controlled classrooms, hospital rooms etc.)
by timeclocks that:
For operational reasons, if the HVAC equipment can't
1. Can start and stop the system under different be turned-off, the room temperature set-point shall be
schedules for at least three different day-types per automatically increased to a higher default value of
week, 27oC or higher for energy saving.
2. Include an accessible manual override that allows
d) Cooling Tower Fan Control
temporary operation of the system for up to 2
hours. Cooling towers in buildings with built up area greater
than 20,000 m2 and located in a place where the wet
Exceptions to 6.2.3-(a):
bulb temperature drops below 17oC shall have fan
Cooling and Heating systems of total capacity less than controls based on wet bulb logic capable to reduce fan
17.5 kWr. speed up to 50 Percent of the rated full speed.
b) Temperature Controls e) AHU Fan
Mechanical cooling and heating equipment in all Air Handling Units serving different zones of a building
buildings shall be installed with automatic controls to shall deploy fan speed modulation control to save
manage the temperature inside the conditioned zones. energy, using duct static pressure signal.
Each zone served by HVAC conditioning equipment
Exception to s6.2.3.e:
shall have individual temperature control for energy
saving. These controls shall comply with the following Air handling units with capacity less than 5000 m³/hr.
requirements:
System and Co
be provided with input from pressure transducers and Operating Temperature (ºC) Pipe size (mm)
close upon when:
< 40 ≥40
1. Fan shutdown
2. Served spaces are not in use. Insulation R value
(m2.K/W)
Exception to 6.2.3-(f):
Dampers shall not be provided in exhaust systems Heating System
serving kitchen exhaust hoods. >94°C and ≤121°C 1.1 1.3
6.2.4. Piping and Ductwork >60°C and ≤94°C 0.8 0.8
a) Piping Insulation >40°C and ≤60°C 0.5 0.9
Piping for heating, space conditioning, and service hot Cooling System
water systems shall meet the insulation requirements
>4.5°C and ≤15°C 0.9 1.0
listed in Table 6.4 through Table 6.6 . Insulation
exposed to weather shall be protected by aluminium < 4.5°C 1.1 1.3
sheet, painted canvas, or plastic cover. Cellular foam
Refrigerant Piping (Split systems)
insulation shall be protected as above or be painted
with water resistant paint. >4.5°C and ≤15°C 0.5 0.9
Where pipes are located within air-conditioned spaces < 4.5°C 1.1 1.3
or are buried in ground, the R Value indicated in Table Table 6.6 Insulation Requirements for Pipes in Super ECSBC
5.4 through 5.6 may be reduced by 0.2. Where pipes Buildings
are located outside the building and in direct exposure Operating Temperature (ºC) Pipe size (mm)
to weather, the R Values given in Tables 6.4 through 6.6
shall be increased by 0.2. < 40 ≥40
System and Co
Note:
Table 6.7 Ductwork Insulation (R value in m2. K/W)
Requirements Calculation of Baseline Fan Electric Input Power:
Duct Location Supply ducts Return ducts
Baseline fan is a conceptual fan whose power input is
Exterior R -1.4 R -0.6 predefined for a given duty point and can be used as
reference to calculate FEI of any fan.
Unconditioned R -0.6 None
Space Baseline Electric Power Input to motor = Href
Buried R -0.6 None /( Eref.trans x E ref.motor)
Where,
System and Co
(Primary and secondary pump (Primary and secondary pump
Secondary)
Table 6.11 Mechanical and Motor Efficiency Requirements for Secondary)
Fans in SuperWater
Condenser ECSBCPump
Buildings17.7 W/ kWr
System Fan Type Mechanical Motor
Pump Efficiency 70%
Type Efficiency Efficiency
(minimum)
(As per IS
Motor Efficiency (as per IE3 or better 12615)
IS 12615)
Air- Supply, 75 % IE 4
handling return and
unit exhaust
System and Co
11520 m³/hr.
tower Fans 28.3 °C WB outdoor
air b) Partial Cooling
Where required by Section 6.3.5-(a), economizers
shall be capable of providing partial cooling even when
Table 6.17 Cooling Tower fan Efficiency Requirements for
additional mechanical cooling is required to meet the
ECSBC+ Buildings
cooling load.
Equipment type Rating Condition Efficiency
c) Economizer Controls
Open circuit 37.8°C entering water 0.35 Air side economizer shall be equipped with controls.
cooling tower 32.2°C leaving water kW/(ltr-
1. That allow dampers to be sequenced with the
Fans for 28.3°C WB outdoor air sec.)
mechanical cooling equipment and not be
Chillers
controlled by only mixed air temperature.
≤530kWr
2. Capable of automatically reducing outdoor air
intake to the design minimum outdoor air quantity
when outdoor air intake will no longer reduce
Table 6.18 Cooling Tower fan Efficiency Requirements for
Super ECSBC Buildings cooling energy usage.
3. Capable of high-limit shutoff at 24 °C dry bulb
Equipment Rating Condition Efficiency temperature.
type
d) Testing of Economizers
Open circuit 35.6°C entering water 0.35
Air side economizers shall be tested in the field
cooling tower 30.0°C leaving water kW/(ltr- according to the requirements outlined in Appendix 3
Fans for 28.3°C WB outdoor air sec.) to ensure proper operation.
Chillers
Exception to 6.3.5.(d):
≤530kWr
Air side economizers that have been factory tested and
calibrated as per the procedures outlined in Appendix 3
to ensure proper operation and are duly certified by the
6.3.5. Economizer Authority Having Jurisdiction
a) Economizer 6.3.6. Variable Flow Hydronic System
For buildings with a built-up area exceeding 20,000
a) Variable Fluid Flow
m2, each cooling fan system shall include at least one
of the following: HVAC pumping systems having a total pump system
power exceeding 7.5 kW shall be designed for variable
1. An air economizer, capable of adjusting outside-air fluid flow and shall be capable of reducing pump flow
and return-air dampers to provide 50% of the rates to an extent which is equal to or less than the
design supply air volume as outside air. limit, where the limit is set by the greater of:
2. A water economizer, capable of providing 50% of
the expected system cooling load when outside air I. 50% of the design flow rate, or
temperatures is 10°C dry-bulb/7.2°C wet-bulb and II. The minimum flow required by the equipment
manufacturer for proper operation of the chillers
below.
Exception to 6.3.5.(a) b) Automatic shut off of Condenser water flow
1. Building in warm-humid climate zone. Water-cooled air-conditioning or heat pump units with
a circulation pump motor of 7.5 kW or more shall
System and Co
meet or exceed the efficiency requirements given in
shut off the water flow through the circuit and the
Table 6-22 through Table 6-24. VRF Air Conditioners
dedicated cooling tower fan as well whenever the
shall be rated for full load as well as part load
respective compressor is not in operation.
operating conditions in accordance with the BIS
Standard for VRF air conditioners which is currently in
6.3.7. Unitary, Split, Packaged Air-
draft form.
Conditioners
Unitary (Window AC) and Split air-conditioners, which
are non-ducted and have a capacity of up to 10499 Wr,
and light commercial air conditioners from 10500 to
18000 Wr, (all air-cooled systems), shall comply with
IS-1391 Part 1 and 2. They must also meet or surpass Table 6.22 Minimum Efficiency Requirements for VRF Air
the minimum efficiency requirements specified in conditioners for ECSBC Buildings
Table 6.19. Cooling Capacity (kWr) Efficiency
Table 6.19 Minimum Efficiency Requirements for Non-ducted For <40kWr 5.4 ISEER
Unitary & Split AC, light commercial air conditioners in
ECSBC+ and Super ECSBC Buildings
For ≥ 40kWr and <70kWr 5.5 ISEER
ECSBC Plus BEE 4 Star
Super ECSBC BEE 5 Star For ≥70kWr 5.6 ISEER
System and Co
automatically, based on outside temperature and plant room shall have controls capability to optimize
moved up to higher level within the defined comfort the performance of chillers, pumps and cooling tower
zone. fans and match chilled water demand and supply
b) AHU fan energy optimization: requirement on real-time basis.
System and Co
2. Desiccant cooling system
𝐴𝑛𝑛𝑢𝑎𝑙 𝐶ℎ𝑖𝑙𝑙𝑒𝑟 𝑝𝑙𝑎𝑛𝑡 Energy consumption (𝑘𝑊ℎ) 3. Solar air conditioning
=
Annual Chiller plant 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑖𝑜𝑛(kWrh) 4. Tri-generation (waste-to-heat)
5. Radiant cooling system
6. Ground source heat pump
a) Documentation Requirement
7. Adiabatic cooling system
Compliance shall be documented, and compliance 8. Under-floor Air distribution (UFAD) system
forms shall be submitted to the certifying authority
having judication. The information submitted shall Buildings with an approved low energy comfort
include, at a minimum, the following: system installed for more than 50 % of the sum of
cooling and heating capacity requirement of the
1. Summary describing the results of the analysis, building shall be deemed to be equivalent to ECSBC +
including the annual energy use (kWh) of chilled and those with more than 90 % shall be deemed to be
water plant (chillers, pumps and cooling tower) Super ECSBC Compliant subjected to meeting the
and annual chilled water use (kWh)for the documentation requirement as per 6.3.13-(a).
proposed design, and software used.
2. Brief description of the project with location, a) Documentation Requirement
number of stories, space types, conditioned and Compliance shall be documented and submitted to the
unconditioned areas, hours of operation. certifying authority having jurisdiction.
3. List of the energy-related building features of the Documentation shall include, at a minimum, the
proposed design. following:
4. List showing compliance with the mandatory
requirements of this code. I. Brief details of the low- energy comfort system.
5. The input and output report(s) from the type, capacity and efficiency.
simulation program including energy and chilled II. Details of compliance with mandatory and
water usage components: space cooling and heat standardized requirements specified in 6.3.13.
rejection equipment, and other HVAC equipment III. Comparison of installed capacity of the approved
(such as pumps). The output reports shall also low-energy comfort system as against the
show the number of hours any loads that are not conventional system with calculations for energy
met by the HVAC system in the proposed design. consumption of both the systems.
6. Explanation of any significant modelling
assumptions made.
7. Explanation of any error messages noted in the
simulation program output.
7.3.4 Installed Interior Lighting Power applications shall not exceed the lighting power
The installed interior lighting power calculated for limits specified in Table 7.7 for ECSBC Buildings,
compliance with Section 7.3 shall include total all Table 7.8 for ECSBC+ Buildings and
power consumption of the luminaires, except the Table 7.9 for Super ECSBC Buildings. Trade-offs
exemptions specified in Section 7.1. between applications are not permitted.
Exception to Section 7.3.3: If two or more Exception to exterior lighting power:
independently operating lighting systems in a space
are controlled to prevent simultaneous user a. Lighting integral to equipment or
instrumentation and installed by its
operation, the installed interior lighting power shall
manufacturer.
be based solely on the lighting system with the
b. Theatrical purposes only comprising of
highest power without compromising the lighting
performance, stage, film production, and video
quantity and quality. production.
(a) Luminaire Wattage c. Temporary lighting not permanently installed
1. The wattage of lighting equipment, when and can be removed or shifted whenever
required.
used to calculate either installed interior
d. Lighting for industrial activities namely
lighting power shall be determined in
manufacturing, material handling,
accordance with the following criteria:
transportation sites, and associated storage
2. The wattage of lighting equipment areas where lighting is equipped with hoods or
connected to supply voltage shall be the louvers for glare control.
manufacturers’ labelled rated wattage. e. Lighting for any monument of national
3. The wattage of lighting equipment with importance, national flag, statue/sculpture etc.
remote ballasts/drivers or similar devices
shall be the total input wattage of all
components and accessories in the system.
4. The wattage of all other miscellaneous
luminaire types not described in (i) or shall
be the rated wattage marked on the
luminaires and/or its packaging.
5. The wattage of lighting track, plug-in
busway, and flexible-lighting systems that
allow the addition and/ or relocation of
luminaires without altering the wiring of the
system shall be the highest of the specified
wattage of the luminaires included in the
system or 135 Watt per meter length of the
lighting system. Systems with integral
overload protection, such as fuses or circuit
Building Area Type LPD (W/m2) Building Area Type LPD (W/m2)
Office Building 7.37 Motion picture theater 5.06
Hospitals 9.70 Museum 6.60
Hotels /Motel 6.27 Post office 7.48
Shopping Mall 9.24 Religious building 7.81
University and Schools 8.25 Sports arena 7.80
Library 9.90 Transportation 6.60
Dining: bar lounge/leisure 8.80 Warehouse 5.28
Performing arts
Dining: cafeteria/fast food 8.25 9.68
theater
Dining: family 7.70 Police station 7.26
Dormitory 6.16 Workshop 10.23
Fire station 6.60 Automotive facility 8.69
Gymnasium 8.91 Convention center 7.48
Manufacturing facility 9.68 Parking garage 1.98
Table 7.2 Interior Lighting Power for ECSBC+ Buildings – Building Area Method for lighting system
Dining: bar
8 Warehouse 4.8
lounge/leisure
Building Area Type LPD (W/m2) Building Area Type LPD (W/m2)
Table 7.4 Interior Lighting Power for ECSBC Buildings – Space Function Method Base LPD without modifiers
Business
Enclosed 8.69 Open Plan 6.6
Healthcare
Emergency 15.73 Recovery 8.6
Hospitality
Hotel Dining 6.16 Hotel Lobby 5.72
Shopping Complex
Mall Concourse 6.71 For Family Dining 6.16
Audience SeatingArea)
Educational
Classroom/Lecture 8.47 Card File and 8.25
Cataloguing
Table 7.5 Interior Lighting Power for ECSBC+ Buildings – Space Function Method base LPD without modifiers
Business
Healthcare
Emergency 14.3 Recovery 7.0
Radiology/Imaging 7.3
Hospitality
Shopping Complex
Table 7.6 Interior Lighting Power for Super ECSBC Buildings – Space Function Method base LPD without modifiers
Business
Enclosed 5.4 Open Plan 5.4
HealthCare
Hospitality
Shopping Complex
Audience SeatingArea)
Educational
Assembly
Total loss values given in above table are applicable for thermal class E, B and F and have component of load
loss at reference temperature according to clause 17 of IS. An increase of 7% on total for thermal class H is
allowed.
1. Daily 99th percentile very short time (3s) values Maximum harmonic current distortion in percent of IL
shall be less than 1.5 times the values given in table
8.4. Individual harmonic orderb
69 kV < V ≤ 161 kV 1.5 2.5 a For h≤6, even harmonics are limited to 50% of the harmonic limites
1.0 1.5* shown in the table.
161 kV < V b Current distortions that result in a dc offset, e.g., half-wave converters,
2.0% THD where the cause is an HVDC terminal whose distortion, regardless of actual ISC/IL unless covered by other standards
effects are found to be attenuated at points in the with applicable scope.
network where future users may be connected. ISC = maximum short-circuit current at PCC.
IL = maximum demand load current at PCC under normal load operating
conditions.
Reference Standard: IEEE 519:2022
Maximum harmonic current distortion in percent Table 8.8: Energy Efficiency Requirements for UPS for ECSBC,
of IL ECSBC Plus ECSBC Super building
ECSBC Plus and Super ECSBC building shall fulfil the 1. ECSBC -Minimum 5% Building Electricity Peak
additional requirements listed in Table 8.9 and Table Demand load reduction capability
8.10 respectively. 2. ECSBC Plus 7.5 % Building Electricity Peak Demand
Table 8.9: Minimum Renewable Contribution towards meeting load reduction capability
Contract Demand in ECSBC Plus Building 3. Super ECSBC – 10 % Building Electricity Peak
Demand load reduction Capability.
Building Type Minimum Capacity to
be Installed in REGZ
All building types Minimum 7.5% of (e) Recommendations on Electric Vehicle
total Contract Demand Charging Infrastructure and Parking Spaces
Table 8.10: Minimum Renewable Contribution towards meeting 1. EV Charging Infrastructure:
Contract Demand in Super ECSBC Building Parking places in buildings shall be provided with EV
Charging infrastructure as per Central Electricity
Building Type Minimum Capacity to Authority (CEA) guidelines, CEA measures of safety
be Installed in REGZ regulations and Ministry of power consolidated
All Building types Minimum 15% of total guidelines & standards for EV charging infrastructure
Contract Demand
as applicable at the time of implementation.
If states having open access policy, the buildings shall
comply in meeting above demand by using combination I. CEA Measures Relating to Safety and Electric Supply,
of off-site green power procured from local energy Amendment Regulations, 2019
company along with on-site installed renewable energy II. CEA Technical Standards for Connectivity of
sources to meet the target mentioned above. Distributed Generation Resources, Amendment
Regulations, 2019
(b) Main Electrical Service Panel III. Ministry of Power Guidelines, Jan 2022
IV. BIS standards (IS 17017 series)
Minimum rating shall be displayed on the main
V. Battery Safety and Vehicle Safety standards for EV
electrical service panel. Space shall be reserved for the
as per regulations by Ministry of Heavy Industries.
installation of a circuit breaker for a future renewable
VI. Amendments to Model Building Bye-Laws 2016 for
electric installation.
EVCI, 2019
Ed ≤ 3,65 x Q x nd x Sav/1000 + 800 x tnr buildings. The energy classification values are as defined
E
in table 7 of IS 17515 – Part 3.
F Ed ≤ 5,47 x Q x nd x Sav/1000 + 1600 x tnr Note: If there are multiple escalators and /or moving
walks in a building with different classification as per
G Ed ≤ 5,47 x Q x nd x Sav/1000 + 1600 x tnr table above, then the one with lowest class shall be taken
for rating computation.
Escalator and /or Moving Walks: Energy calculations
Escalators and Moving walks shall have Variable
and classification for Escalators and Moving walks is
based on Table 7.12 of IS 17515 - Part 3 frequency drives, load and motion sensors for better
efficiency and Energy efficient lighting features and soft
start capabilities, Regenerative Drives shall be provided
to recycle energy. All signal/ signages used for these
equipment’s shall be of LED fixtures.
1. Gas Heaters: It is important to have an exhaust 3. Solar Systems: In an active solar water heating
system properly installed to take out CO (Carbon system, control systems are used to switch on a
Monoxide) which gets generated due to Gas circulation pump whenever energy gain is
burning and thermostat to control the water possible through solar collectors. Otherwise, it
temperature. automatically switches off the pump. A
differential thermostat is recommended as it
2. Heat Pumps: Controls shall be provided for the
optimizes the energy gain for the system. Use of
Heat Pump as follows:
Thermostatic Mixing Valves to avoid High
Temperature water going out from Solar Panels.
Table 9.3: Energy Consumption Calculation for Various Hot Water System
9.2.14 Swimming Pool Heating heated to more than 32°C shall have a pool cover with
a minimum insulation value of R-4.1.
All heated pools shall be provided with a vapour
retardant pool cover on the water surface. Pools Refer Table 9.3 for Energy consumption calculations.
For various Hot water systems.
Waste management
waste generated both during the construction phase items (plastic bottles, containers, packaging,
and post-occupancy to divert any waste from reaching stationary items, etc.), paper items
the landfills. The chapter consists of two parts – (newspapers, magazines, cardboard,
Construction Waste Management and Municipal Waste packaging, etc.), metal items (aluminum cans,
Management. used aluminum foil paper/tray, steel
containers, old metal utensils, pots, metal
Documentation demonstrating compliance must be
gardening accessories, etc.), glass items (glass
submitted for verification as prescribed in Section 10.4.
bottles, jars, utensils, etc.), Electronics items
All ECSBC, ECSBC Plus, Super ECSBC compliant (wires, computer accessories, fluorescents,
buildings shall conform to section 10.2. All ECSBC Plus lamps, other electronics, and electrical
and ECSBC Super compliant building shall confirm to devices/appliances).
section 10.3 in addition to section 10.2. b. Wet waste: Including but not limited to,
10.1.1 Classification of waste vegetable peels, used tea, fruits, food leftovers,
horticulture waste, etc. These are
biodegradable organic waste that can also be
1. Classification of construction waste
composted.
The waste generated during construction shall be
c. Sanitary waste: Including but not limited to,
classified but not limited to the following
used diapers, sanitary pads, sweat pads,
categories:
tampons, condoms, wipes, masks/ gloves, toilet
a. Non-Hazardous waste: Including but not
paper, bandages, swabs, and other personal
limited to Excavated earth excluding 150-200
hygiene products etc.
mm (6-8 inches) of the topsoil, Land clearing
d. Hazardous waste: Including but not limited to,
debris, Metals (Reinforcement bars, Metal
expired medicines, used syringes/needles,
beams/girders, Window/Door frames, nuts
chemical containers, broken glass, batteries,
and bolts, wires, etc.), Cement and Concrete,
etc.
Masonry materials (Bricks, AAC blocks, stone,
All ECSBC, ECSBC Plus, Super ECSBC compliant
any other masonry, etc.), Flooring, Ceiling,
buildings shall conform to section 10.2. All ECSBC
Roofing materials, Insulation materials,
Cladding materials (Tiles, stones, gypsum, etc.), Plus and ECSBC Super compliant building shall
Glass, Wood, etc. confirm to section 10.3 in addition to section 10.2.
b. Packaging waste: Including but not limited to 10.2 Additional Mandatory
cement bags, Wooden crates and pallets,
Requirements
Cardboard boxes, Plastic wrapping and shrink
wrap, Foam and bubble wrap, Strapping bands 10.2.1 Construction Waste Management
and steel wires, PE film or plastic sheeting, a) Segregation and Storage of Waste
Plastic or metal drums/buckets/containers,
Designated areas shall be provided within the
Corrugated plastic sheets, specialized
site/adjacent site for collection, segregation, and
packaging etc.
storage of segregated waste as per the
c. Construction Hazardous waste: Including but
classification of waste mentioned in section 10.2of
not limited to lead, tars, adhesives, sealants,
this code.
broken glass.
Note: No construction and demolition waste shall be
littered or deposited to prevent obstruction to the
2. Classification of post-occupancy waste:
Waste management
At least 50% (by either weight or volume) of non- recyclers/ Municipal Corporation.
hazardous waste generated, shall have to be
reused/repurposed/recycled/salvaged. (b) Organic Waste Treatment
Note: Some types of construction waste can be 1. Projects having built up area ≥5000 sq.m, an onsite
reused/repurposed on-site as fill material for designated area shall be provided to compost
levelling uneven terrain, filling excavated areas, or (manually or mechanically) at least 50% of
creating embankments, as a base or subbase projected organic waste (kitchen & horticulture)
material for road construction, for erosion control generated on post-occupancy. The waste
measures, constructing retaining walls, as bedding generation shall be calculated using the formula as
and backfill material for utility pipelines, etc. given in section 10.4 of this code.
2. Projects having built up area <5000 sq.m, the
c) Recycling of Packaging Waste
project authority may hand over the segregated
100% of the packaging recyclable waste, shall be organic waste to the concerned local body if the
handed over to manufacturers/ authorized municipality has a garbage pick-up mechanism in
recyclers or municipal entities for appropriate place. If such an arrangement is inadequate or
management and disposal. unavailable, the project authority shall engage a
d) Divert Construction Waste from Landfill professional waste management organisation to
pick up the segregated organic waste, where there
Ensure that all (100%) the construction waste (by
is no alternate arrangement for disposal of
either weight or volume) generated during the
biodegradable waste, Organic waste
construction process is either reused /
composter/Vermiculture pit with a minimum
repurposed/ salvaged on-site, diverted to recycling
capacity of 1.0 kg/150 sqm. of built-up area/day
facilities, or safely handed over to municipalities.
shall be installed & operated.
Diversion efforts shall be tracked throughout the
construction process. For sample calculation refer 10.3 Additional Mandatory
to section number section 10.4 of this code. Requirements
10.2.2 Post Construction Waste 10.3.1 Construction Waste Management
Management
Non-hazardous construction waste generated shall
a) Waste Collection Segregation and Storage have to be reused/repurposed /recycled/salvaged, to
A designated centralized waste collection area in comply with the requirements below:
each building shall be provided with at least four a) Requirements for ECSBC Plus Compliance
colour-coded waste bins from the categories (Dry
75%of non-hazardous waste generated is reused
Waste, Organic Waste, Sanitary Waste, Hazardous
/repurposed /recycled /salvaged.
Waste, E-waste). For calculation of waste
generation quantity and area required for storage, b) Requirements for Super ECSBC Compliance
refer to section 10.4 of this code. 95% of non-hazardous waste generated is reused
Note: /repurposed /recycled /salvaged.
1. A daily waste collection schedule should be
developed to collect the segregated waste from
each building and store at a designated
Waste management
to compost (manually or mechanically) to comply. The Inorganic waste generation = Total waste generation x
calculation shall be done to calculate the designated Inorganic waste percentage
area as per section 10.4.
Inorganic waste generation = 360 kg/day
a) Requirements for ECSBC Plus Compliance
75% of organic waste generated post-occupancy is 10.4.2 Calculation Of Area Requirement for
composted on-site. Storing Organic Waste
b) Requirements for ECSBC Super Compliance The volume required to store 1 kg of organic waste
depends on the density of the waste and how
95% of organic waste generated post-occupancy is compacted it is. Organic waste's density can vary based
composted on-site. on its composition, moisture content, and packing
10.4 Calculations and Formula method.
10.4.1 Example for Post Occupancy Waste Let's consider an example where the organic waste has
Generation a density of 0.5 kg/L. Remember that this is an
approximate value, as organic waste density typically
An office building having plinth area 30000 sq.m, with ranges from 0.2 kg/L to 0.8 kg/L, depending on the
an occupancy of 10 persons per 100 sqm. The specific waste composition.
recommended range of waste generation is between
0.1 to 0.2 kilograms per capita per day, comprises 40% To calculate the volume required:
organic waste and 60% inorganic waste.
Volume = Mass / Density
Calculation for estimation of waste generation:
Volume = 1 kg / 0.5 kg/L = 2 L
Step 1: Calculate the total number of occupants in the
office building: As a rule of thumb, 1000 litres require 1 cubic meter of
volume
𝑝𝑒𝑟𝑠𝑜𝑛
𝑃𝑙𝑖𝑛𝑡ℎ 𝑎𝑟𝑒𝑎 (𝑠𝑞𝑚) ∗ 𝑠𝑞𝑚
𝑇𝑜𝑡𝑎𝑙 𝑛𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 100 Then 2 L waste required = 0.002 m³
100
Total number of occupants = 3000 Nos. (For a thumb rule, it is calculated that 1 kg waste
required 0.002 m3)
Step 2: Calculate the total waste generation per day
Considering the upper range of the NBC guidelines: So, if the organic waste has a density of 0.5 kg/L, you
would need approximately 2 liters of volume to store 1
Total waste generation = Total number of occupants x kg of organic waste.
waste generation per capita
10.4.3 Organic Waste Calculation (Vermi
Total waste generation = 600 kg/day
Composting Method)
Step 3: Calculate the organic and inorganic waste
generation:
Table 10.1 : Organic waste calculation
Waste management
Total waste generated in 60 days = Daily waste generation x Retention time
Total waste Kg 14400
Calculate the volume of vermi beds required to handle this waste:
Total vermi bed volume required = Total waste / Storage density
Volume: m3 28.8
Calculate the total area of vermi beds required:
Vermi bed area = Vermi bed volume / Vermi bed depth 48.0
Length of vermi beds = Vermi bed area / Vermi bed width= 32.0
Hence, size of required pit/bed per cycle: 0.6m X 1.5m X 32m
Number of beds 2
Total area required for per day organic waste (m²) 96
Area (Sq.m) Required for Mandatory section 4.3.3 50% 48
Area (Sq.m) Required for Mandatory section 4.4.2 - a 75% 72
Area (Sq.m) Required for Mandatory section 4.4.2 - b 95% 91.2
Area provided on site for organic composting 93
Meeting the requirement 100%
Diverted
% Of
Classification Quantity Density(k Volume from Method of
Type of waste total
of waste (Kg) g/m3) (m3) landfills Diversion
waste1
(Kg)
As per CPCB 2016, new construction generates approx. 40-60 kg per sqm of built-up area
Total Construction waste Quantity 257621.5 (Considering 50 kg waste per sq.m of built-up area)
Reused/
Soil, Sand and Gravel 66981.6 26% 1600 41.86 66981.6 repurposed
on site
Reused/
Brick & Masonry 82438.9 32% 1900 43.39 82438.9 repurposed
on site
Non-
Reused/
Hazardous
Concrete 72134.0 28% 1200 60.11 72134.0 repurposed
on site
Sold to
Metals 15457.3 6% 7850 2.0 15457.3
recycler
Sold to
Wood 7728.6 3% 400 19.3 7728.6
recycler
Sold to
Packaging Others 7728.6 3% 7728.6
recycler
Handover To
Hazardous Bitumen 5152.4 2% 1040 5.0 5152.4 municipal
authority
% Of
Classification of waste as per ECSBC Provisions Quantity (Kg)
diversion
Non-Hazardous 244740.425
Waste management
Sent to recycling units 23185.9
Reused/ repurposed on site 221554.5
Hazardous 5152.43
To municipalities 5152.4
Packaging 7728.645
Sent to recycling units 7728.6
Minimization of Non-Hazardous waste (reused on site, to recycling units) 244740.4 100%
Recycling of packaging waste 7728.6 100%
Total waste diverted from landfills (Kg) 257621.5 100%
and Super ECSBC compliant building shall confirm to 1.0 <Met 23.0 ± 3.0 19.0 ± 4.0
section 11.3 in addition to section 11.2. ≤ 1.2
Table 11.4 Default sound insulation values of the different walls and Glazing.
7. Metal stud partition, 70 mm studs 600 mm centres, 2x12.5 mm plasterboard of minimum density 40-45
900Kg/m3 cavity filled with 50mm thick mineral wooleach side ,70 mm metal stud
8. 225 mm brickwork 215pprox.. density 440 kg/m2 with12mm thick plaster on both sides 45-50
9. Double Stud Metal stud partition, 70 mm studs placed 10mm apart and studs fixed at 600 mm centres,
2x12.5mm plasterboard of minimum density 900Kg/m3 cavityfilled with 2x 50mm thick mineral wool
each side of a metal stud
10. 200 mm block work 215pprox.. density 400Kg/m2with 15mm thick plaster on both sides
11. 100 mm block (high density 200 kg/m2) with 12 mmplaster on one side and 1x12.5 mm plasterboard on 50-55
metal frame with a 50 mm cavity filled with glass fibre/mineral wool on other side
12. Double Stud Metal stud partition, 70 mm studs placed 10mm apart and studs fixed at 600 mm centres,
2x12.5mm plasterboard of minimum density 990-1000Kg/m3 cavity filled with 2x 50mm thick mineral
wool each sideof a metal stud
Glazing combinations
The Transmission loss of Wooden, Metal Doors along with acoustical louvers are defined in the Table 11.5
Table 11.5: Transmission loss of wooden, metal door along with acoustical louvers.
a. Solid-core Wood Doors
TL (Transmission loss), DB
Solid-core wood door Solid-core wood door [ Solid-core wood door [
(24kg/m )]; no seals
2 (24kg/m2)]; Foam type (24kg/m )];
2
Description
around perimeter sealsaround perimeter Magnetic seals around
perimeter
STC 22 26 30
Rw
63 16 18 20
80 19 20 23
100 16 19 22
125 19 22 25
160 20 24 26
200 21 25 27
250 22 25 29
Frequency H
315 24 28 31
400 25 28 30
500 26 29 30
630 26 29 30
STC 17 28 32
Rw
63 12 21 21
80 14 23 23
100 11 21 22
125 13 21 24
160 14 24 24
Frequency Hz
200 14 24 27
250 15 25 28
315 15 24 27
400 16 25 29
500 16 25 30
630 17 26 31
800 17 26 31
1000 17 26 30
1600 18 29 31
2500 17 32 38
3150 19 33 40
4000 20 34 39
Depth of acoustical
Louver Single Blade 63 125 250 500 1000 2000 4000 8000
(mm)
100 5 4 5 6 9 13 14 13
150 6 6 8 10 14 18 16 15
300 6 7 10 12 18 18 14 13
600 7 9 12 24 31 33 29 30
S. Dw/NIC
N Building Type of space
SuperECSBC
o. ECSBC+ ECSBC
Table 12-1 Modeling Requirements for calculating proposed and Baseline design
Daytime occupancy
Automatic Control Device All Others
and area <300 m2
12.5.3 Compliance Thresholds for ECSBC Table 12.8 Minimum required Percentage Energy
compliant, ECSBC+ and Super ECSBC Buildings Savings (PES) respect to Energy Savings of ECSBC
building in Hot and Dry Climate
For buildings to qualify as ECSBC+ and
SuperECSBC Buildings, the WBP Method shall be
followed for the Baseline design as detailed above.
The proposed design for ECSBC+ and Super ECSBC Hot and Dry Climate
buildings shall meet the mandatory provisions of
5.2, 6.2, 7.2 and 8.2 and 9.2 ECBC+ Super ECBC
12.7 Schedules
24 Hours
24 Hours
Business
Business
Business
Business
Business
Business
Daytime
Daytime
Daytime
7 Days/
week
Corridor/ Lobby
Corridor/ Lobby
Meeting Room
Conference/
Conference/
Conference/
Conference/
Time Period
Meeting
Meeting
Meeting
Office/
Office
Office
Office
00:00-01:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
01:00-02:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
02:00-03:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
03:00-04:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
04:00-05:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
05:00-06:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
06:00-07:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
07:00-08:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 1 0
08:00-09:00 0.20 0.70 0.00 0.90 0.90 0.00 0.10 0.00 1 1
09:00-10:00 0.95 0.80 0.00 0.90 0.90 0.00 0.90 0.00 1 1
10:00-11:00 0.95 0.70 0.75 0.90 0.90 0.90 0.90 0.90 1 1
11:00-12:00 0.95 0.30 0.75 0.90 0.90 0.90 0.90 0.90 1 1
12:00-13:00 0.95 0.30 0.75 0.90 0.90 0.90 0.90 0.90 1 1
13:00-14:00 0.50 0.80 0.5 0.50 0.90 0.50 0.80 0.50 1 1
14:00-15:00 0.95 0.50 0.75 0.90 0.90 0.90 0.90 0.90 1 1
15:00-16:00 0.95 0.30 0.75 0.90 0.90 0.90 0.90 0.90 1 1
16:00-17:00 0.95 0.30 0.75 0.90 0.90 0.90 0.90 0.90 1 1
17:00-18:00 0.95 0.80 0.75 0.95 0.90 0.90 0.90 0.90 1 1
18:00-19:00 0.30 0.70 0.50 0.50 0.90 0.90 0.50 0.90 1 1
19:00-20:00 0.00 0.30 0.00 0.30 0.90 0.00 0.10 0.00 1 0
20:00-21:00 0.00 0.00 0.00 0.10 0.10 0.00 0.10 0.00 1 0
21:00-22:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
22:00-23:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
23:00-24:00 0.00 0.00 0.00 0.10 0.10 0.00 0.00 0.00 0 0
Office/ Corridor/
Corridor/ Lobby
Corridor/ Lobby
Conference/
Conference/
Conference/
Conference/
Time Period
Meeting
Meeting
Meeting
Meeting
Lobby/
Office
Office
Office
00:00-01:00 0.90 0.20 0.00 0.90 0.90 0.00 0.95 0.00 1
01:00-02:00 0.90 0.50 0.00 0.90 0.90 0.00 0.95 0.00 1
02:00-03:00 0.90 0.20 0.00 0.90 0.90 0.00 0.95 0.00 1
03:00-04:00 0.90 0.20 0.00 0.90 0.90 0.00 0.95 0.00 1
04:00-05:00 0.50 0.20 0.50 0.50 0.90 0.50 0.00 0.90 1
05:00-06:00 0.20 0.50 0.50 0.05 0.90 0.50 0.00 0.90 1
06:00-07:00 0.10 0.50 0.50 0.05 0.50 0.50 0.00 0.90 1
07:00-08:00 0.10 0.50 0.00 0.90 0.50 0.00 0.95 0.00 1
08:00-09:00 0.90 0.70 0.00 0.90 0.90 0.00 0.95 0.00 1
09:00-10:00 0.90 0.80 0.50 0.90 0.90 0.50 0.95 0.90 1
10:00-11:00 0.90 0.70 0.75 0.90 0.90 0.90 0.95 0.90 1
11:00-12:00 0.90 0.30 0.75 0.90 0.90 0.90 0.95 0.90 1
12:00-13:00 0.90 0.30 0.75 0.90 0.90 0.90 0.95 0.90 1
13:00-14:00 0.20 0.80 0.25 0.50 0.50 0.50 0.20 0.50 1
14:00-15:00 0.90 0.50 0.75 0.90 0.90 0.90 0.95 0.90 1
15:00-16:00 0.90 0.30 0.75 0.90 0.90 0.90 0.95 0.90 1
16:00-17:00 0.90 0.30 0.75 0.90 0.90 0.90 0.95 0.90 1
17:00-18:00 0.90 0.80 0.75 0.90 0.90 0.90 0.95 0.90 1
18:00-19:00 0.90 0.70 0.50 0.90 0.90 0.90 0.20 0.90 1
19:00-20:00 0.20 0.30 0.00 0.90 0.90 0.00 0.95 0.00 1
20:00-21:00 0.90 0.20 0.00 0.90 0.90 0.00 0.95 0.00 1
21:00-22:00 0.90 0.20 0.50 0.90 0.90 0.50 0.95 0.90 1
22:00-23:00 0.90 0.20 0.50 0.90 0.90 0.50 0.95 0.90 1
23:00-24:00 0.90 0.20 0.50 0.90 0.90 0.50 0.20 0.90 1
Business
Business
business
business
Daytime
Daytime
24-hour
24-hour
running
All time
Seating/Public
Exhibit Space
Exhibit Space
Exhibit Space
Conference
Conference
Conference
Meeting/
Meeting/
Meeting/
Time Period
Space
Space
Restoration
Restoration
Restoration
Exhibition
Exhibition
Exhibition
Exhibition
Time Period
Museum
Museum
Museum
Museum
Museum
Museum
Museum
Museum
00:00-01:00 0.00 0.00 0.10 0.10 0.00 0.00 0 0
Transport
Transport
Transport
Buildings
Buildings
Buildings
Buildings
Time Period
Gym
Gym
Gym
Gym
00:00-01:00 0.00 0.00 0.00 0.00 0.00 0.80 0 1
01:00-02:00 0.00 0.00 0.00 0.00 0.00 0.80 0 1
02:00-03:00 0.00 0.00 0.00 0.00 0.00 0.80 0 1
03:00-04:00 0.00 0.00 0.00 0.00 0.00 0.80 0 1
04:00-05:00 0.00 0.50 0.50 0.50 0.50 0.80 1 1
05:00-06:00 0.60 0.90 0.90 0.75 0.75 0.90 1 1
06:00-07:00 0.90 0.90 0.90 0.75 0.75 0.90 1 1
07:00-08:00 0.90 0.90 0.90 0.75 0.75 0.90 1 1
08:00-09:00 0.90 0.90 0.90 0.75 0.75 0.90 1 1
09:00-10:00 0.60 0.90 0.90 0.50 0.50 0.90 1 1
10:00-11:00 0.20 0.50 0.50 0.20 0.20 0.90 1 1
11:00-12:00 0.00 0.00 0.00 0.00 0.00 0.90 1 1
12:00-13:00 0.00 0.00 0.00 0.00 0.00 0.90 1 1
13:00-14:00 0.00 0.00 0.00 0.00 0.00 0.50 1 1
14:00-15:00 0.00 0.00 0.00 0.00 0.00 0.90 1 1
15:00-16:00 0.00 0.00 0.00 0.00 0.00 0.90 1 1
16:00-17:00 0.00 0.00 0.00 0.00 0.00 0.90 1 1
17:00-18:00 0.60 0.75 0.75 0.50 0.50 0.90 1 1
18:00-19:00 0.90 0.90 0.90 0.75 0.75 0.90 1 1
19:00-20:00 0.90 0.90 0.90 0.75 0.75 0.90 1 1
20:00-21:00 0.60 0.90 0.90 0.75 0.75 0.90 1 1
21:00-22:00 0.20 0.75 0.75 0.50 0.50 0.50 1 1
22:00-23:00 0.00 0.00 0.00 0.00 0.00 0.90 0 1
23:00-24:00 0.00 0.00 0.00 0.00 0.00 0.90 0 1
emergency & OT
emergency & OT
emergency & OT
In Patient & ICU
Public Spaces
Diagnostic,
Diagnostic,
Diagnostic,
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
00:00-01:00 0.9 0 0 0.5 0.1 0.1 0.5 0.05 0.4 0 0
01:00-02:00 0.9 0 0 0.4 0.1 0.1 0.5 0.05 0.4 0 0
02:00-03:00 0.9 0 0 0.4 0.1 0.1 0.5 0.05 0.4 0 0
03:00-04:00 0.9 0 0 0.4 0.1 0.1 0.5 0.05 0.4 0 0
04:00-05:00 0.9 0 0 0.4 0.1 0.1 0.5 0.05 0.4 0 0
05:00-06:00 0.9 0 0 0.4 0.1 0.1 0.5 0.05 0.4 0 0
06:00-07:00 0.9 0 0 0.5 0.1 0.1 0.5 0.1 0.4 0 0
07:00-08:00 0.9 0.1 0.1 0.7 0.5 0.2 0.5 0.3 0.7 0.7 0.7
08:00-09:00 0.9 0.5 0.3 0.7 0.9 0.2 0.9 0.9 0.9 0.9 0.9
09:00-10:00 0.9 0.95 0.9 0.95 0.9 0.2 0.9 0.9 0.9 0.9 0.9
10:00-11:00 0.9 0.95 0.9 0.95 0.9 0.2 0.9 0.9 0.9 0.9 0.9
11:00-12:00 0.9 0.95 0.5 0.95 0.9 0.2 0.9 0.9 0.9 0.9 0.9
12:00-13:00 0.9 0.95 0.2 0.95 0.9 0.2 0.9 0.9 0.9 0.9 0.9
13:00-14:00 0.9 0.95 0.5 0.95 0.9 0.2 0.9 0.5 0.9 0.9 0.9
14:00-15:00 0.9 0.95 0.9 0.95 0.9 0.2 0.9 0.9 0.9 0.9 0.9
15:00-16:00 0.9 0.95 0.9 0.95 0.9 0.2 0.9 0.9 0.9 0.9 0.9
16:00-17:00 0.9 0.95 0.9 0.95 0.3 0.2 0.9 0.9 0.6 0.6 0.9
17:00-18:00 0.9 0.7 0.9 0.95 0.3 0.7 0.9 0.9 0.6 0.6 0.9
18:00-19:00 0.9 0.5 0.5 0.95 0.3 0.9 0.9 0.5 0.6 0.6 0.6
19:00-20:00 0.9 0.3 0.5 0.95 0.3 0.9 0.9 0.5 0.6 0.6 0.6
20:00-21:00 0.9 0.1 0.5 0.7 0.3 0.9 0.5 0.3 0.6 0.6 0.6
21:00-22:00 0.9 0 0.1 0.7 0.3 0.9 0.5 0.2 0.6 0 0
22:00-23:00 0.9 0 0 0.5 0.3 0.7 0.5 0.1 0.6 0 0
23:00-24:00 0.9 0 0 0.5 0.1 0.1 0.5 0.05 0.4 0 0
Basement Ventilation
Water
Basement Lighting
Diagn, emerg, & OT
Building Summer
Building Winters
Elevators
OPD & Offices
Public Spaces
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
00:00-01:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
01:00-02:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
02:00-03:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
03:00-04:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
04:00-05:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
05:00-06:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
06:00-07:00 0 1 1 0 0.00 0.20 0.00 0.30 0.50 0.50
07:00-08:00 1 1 1 0 0.00 0.50 0.00 0.20 0.50 0.50
08:00-09:00 1 1 1 1 0.00 0.75 0.20 0.60 1.00 1.00
09:00-10:00 1 1 1 1 0.00 1.00 0.30 0.60 1.00 1.00
10:00-11:00 1 1 1 1 0.00 1.00 0.30 0.80 1.00 1.00
11:00-12:00 1 1 1 1 0.00 1.00 0.30 0.80 1.00 1.00
12:00-13:00 1 1 1 1 0.00 0.75 0.25 0.70 1.00 1.00
13:00-14:00 1 1 1 1 0.00 1.00 0.25 0.80 1.00 1.00
14:00-15:00 1 1 1 1 0.00 1.00 0.25 0.80 1.00 1.00
15:00-16:00 1 1 1 1 0.00 1.00 0.25 0.70 1.00 1.00
16:00-17:00 1 1 1 1 0.00 1.00 0.25 0.70 1.00 1.00
17:00-18:00 1 1 1 1 0.00 1.00 0.10 0.50 1.00 1.00
18:00-19:00 1 1 1 1 1.00 0.50 0.00 0.35 1.00 1.00
19:00-20:00 1 1 1 1 1.00 0.50 0.00 0.35 1.00 1.00
20:00-21:00 1 1 1 1 1.00 0.50 0.00 0.35 1.00 1.00
21:00-22:00 1 1 1 0 1.00 0.30 0.00 0.30 0.50 0.50
22:00-23:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
23:00-24:00 0 1 1 0 1.00 0.20 0.00 0.30 0.50 0.50
Diagnostic &
Diagnostic &
Diagnostic &
OPD & Back
Emergency
Emergency
Office
Office
Office
Lobby
6 days/
6 days/
6 days/
6 days/
6 days/
6 days/
week
week
week
week
week
week
week
00:00-01:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
01:00-02:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
02:00-03:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
03:00-04:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
04:00-05:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
05:00-06:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
06:00-07:00 0.00 0.20 0.20 0.10 0.10 0.00 0.00
07:00-08:00 0.10 0.20 0.20 0.50 0.30 0.50 0.00
08:00-09:00 0.50 0.30 0.20 0.90 0.90 0.95 0.95
09:00-10:00 0.80 0.90 0.90 0.90 0.90 0.95 0.95
10:00-11:00 0.80 0.90 0.90 0.90 0.90 0.95 0.95
11:00-12:00 0.80 0.90 0.90 0.90 0.90 0.95 0.95
12:00-13:00 0.80 0.90 0.50 0.90 0.90 0.95 0.95
13:00-14:00 0.80 0.90 0.20 0.90 0.50 0.95 0.95
14:00-15:00 0.80 0.90 0.50 0.90 0.90 0.95 0.95
15:00-16:00 0.80 0.90 0.90 0.90 0.90 0.95 0.95
16:00-17:00 0.80 0.90 0.90 0.90 0.90 0.95 0.95
17:00-18:00 0.80 0.90 0.90 0.90 0.95 0.95 0.95
18:00-19:00 0.80 0.90 0.50 0.90 0.95 0.95 0.95
19:00-20:00 0.80 0.90 0.50 0.90 0.30 0.95 0.95
20:00-21:00 0.20 0.65 0.20 0.90 0.30 0.80 0.80
21:00-22:00 0.20 0.20 0.20 0.50 0.20 0.00 0.00
22:00-23:00 0.00 0.00 0.00 0.30 0.00 0.00 0.00
23:00-24:00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
7 Days/
6 days/
6 days/
6 days/
6 days/
6 days/
6 days/
week
week
week
week
week
week
week
00:00-01:00 0.05 0 0.20 0.00 0.00 0.00 0.00
01:00-02:00 0.05 0 0.20 0.00 0.00 0.00 0.00
02:00-03:00 0.05 0 0.20 0.00 0.00 0.00 0.00
03:00-04:00 0.05 0 0.20 0.00 0.00 0.00 0.00
04:00-05:00 0.05 0 0.20 0.00 0.00 0.00 0.00
05:00-06:00 0.05 0 0.20 0.00 0.00 0.00 0.00
06:00-07:00 0.05 0 0.00 0.00 0.00 0.00 0.00
07:00-08:00 0.50 0 0.00 0.00 0.20 0.00 0.00
08:00-09:00 0.75 1 0.00 0.20 0.60 1.00 1.00
09:00-10:00 1.00 1 0.00 0.30 0.60 1.00 1.00
10:00-11:00 1.00 1 0.00 0.30 0.80 1.00 1.00
11:00-12:00 1.00 1 0.00 0.30 0.80 1.00 1.00
12:00-13:00 0.75 1 0.00 0.25 0.70 1.00 1.00
13:00-14:00 1.00 1 0.00 0.25 0.80 1.00 1.00
14:00-15:00 1.00 1 0.00 0.25 0.80 1.00 1.00
15:00-16:00 1.00 1 0.00 0.25 0.70 1.00 1.00
16:00-17:00 1.00 1 0.00 0.25 0.70 1.00 1.00
17:00-18:00 1.00 1 0.00 0.10 0.50 1.00 1.00
18:00-19:00 0.50 1 0.50 0.01 0.20 1.00 1.00
19:00-20:00 0.50 1 0.50 0.01 0.20 1.00 1.00
20:00-21:00 0.50 1 0.50 0.01 0.20 1.00 1.00
21:00-22:00 0.30 0 0.50 0.01 0.10 1.00 1.00
22:00-23:00 0.05 0 0.20 0.01 0.01 0.00 0.00
23:00-24:00 0.05 0 0.20 0.01 0.01 0.00 0.00
5 Days/
5 Days/
5 Days/
7 Days/
7 Days/
7 Days/
week
week
week
week
week
week
week
00:00-01:00 0.00 0 0 0 0.80 0.00 0.05
01:00-02:00 0.00 0 0 0 0.80 0.00 0.05
02:00-03:00 0.00 0 0 0 0.80 0.00 0.05
03:00-04:00 0.00 0 0 0 0.80 0.00 0.05
04:00-05:00 0.00 0 0 0 0.80 0.00 0.05
05:00-06:00 0.00 0 0 0 0.80 0.00 0.05
06:00-07:00 0.05 0 0 1 0.00 0.00 0.05
07:00-08:00 0.80 1 1 1 0.00 0.00 0.05
08:00-09:00 0.80 1 1 1 0.00 1.00 1.00
09:00-10:00 0.25 1 1 1 0.00 1.00 1.00
10:00-11:00 0.25 1 1 1 0.00 1.00 1.00
11:00-12:00 0.25 1 1 1 0.00 1.00 1.00
12:00-13:00 0.25 1 1 1 0.00 1.00 1.00
13:00-14:00 0.90 1 1 1 0.00 1.00 1.00
14:00-15:00 0.60 0 1 1 0.00 1.00 1.00
15:00-16:00 0.20 0 1 0 0.00 1.00 1.00
16:00-17:00 0.30 0 1 0 0.00 1.00 1.00
17:00-18:00 0.40 0 0 0 0.00 1.00 0.50
18:00-19:00 0.00 0 0 0 0.80 0.00 0.05
19:00-20:00 0.00 0 0 0 0.80 0.00 0.05
20:00-21:00 0.00 0 0 0 0.80 0.00 0.05
21:00-22:00 0.00 0 0 0 0.80 0.00 0.05
22:00-23:00 0.00 0 0 0 0.80 0.00 0.05
23:00-24:00 0.00 0 0 0 0.80 0.00 0.05
Back Office
Back Office
Back Office
Time Period
Corridor/
Corridor/
Student
Student
Student
Lobby
Lobby
Zone
Zone
Zone
00:00-01:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
01:00-02:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
02:00-03:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
03:00-04:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
04:00-05:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
05:00-06:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
06:00-07:00 0.00 0.00 0.00 0.00 0.20 0.00 0.00 0.00
07:00-08:00 0.70 0.00 0.90 0.90 0.70 0.90 0.35 0.35
08:00-09:00 0.90 0.90 0.20 0.90 0.90 0.50 0.95 0.95
09:00-10:00 0.90 0.90 0.20 0.90 0.90 0.50 0.95 0.95
10:00-11:00 0.90 0.90 0.20 0.90 0.90 0.50 0.95 0.95
11:00-12:00 0.20 0.90 0.90 0.20 0.90 0.90 0.20 0.95
12:00-13:00 0.90 0.90 0.20 0.90 0.90 0.50 0.95 0.95
13:00-14:00 0.90 0.20 0.50 0.90 0.30 0.50 0.95 0.40
14:00-15:00 0.00 0.90 0.90 0.00 0.90 0.90 0.00 0.95
15:00-16:00 0.00 0.90 0.50 0.00 0.90 0.90 0.00 0.95
16:00-17:00 0.00 0.90 0.50 0.00 0.90 0.50 0.00 0.95
17:00-18:00 0.00 0.50 0.00 0.00 0.30 0.00 0.00 0.25
18:00-19:00 0.00 0.00 0.00 0.00 0.10 0.00 0.00 0.00
19:00-20:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
20:00-21:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
21:00-22:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
22:00-23:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
23:00-24:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Basement Lighting
Student and Back office
Corridor/ Lobby
Student Area
Back Office
Time Period
7 days/
7 days/
5 days/
5 days/
7 days/
5 days/
7 days/
7 days/
7 days/
week
week
week
week
week
week
week
week
week
00:00-01:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
01:00-02:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
02:00-03:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
03:00-04:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
04:00-05:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
05:00-06:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
06:00-07:00 0.00 0.05 0 0 0 0 0.00 0.00 0.05
07:00-08:00 0.00 0.25 1 1 1 1 0.00 0.00 0.05
08:00-09:00 0.50 0.85 1 1 1 1 0.00 1.00 1.00
09:00-10:00 0.50 0.25 1 1 1 1 0.00 1.00 1.00
10:00-11:00 0.30 0.25 1 1 1 1 0.00 1.00 1.00
11:00-12:00 0.20 0.25 1 1 1 1 0.00 1.00 1.00
12:00-13:00 0.20 0.25 1 1 1 1 0.00 1.00 1.00
13:00-14:00 0.40 0.90 1 1 1 1 0.00 1.00 1.00
14:00-15:00 0.30 0.60 1 1 1 1 0.00 1.00 1.00
15:00-16:00 0.30 0.25 1 1 1 1 0.00 1.00 1.00
16:00-17:00 0.30 0.25 1 1 1 1 0.00 1.00 1.00
17:00-18:00 0.50 0.90 1 0 1 1 0.00 1.00 1.00
18:00-19:00 0.50 0.15 0 0 1 1 0.80 1.00 1.00
19:00-20:00 0.50 0.05 0 0 1 0 0.80 1.00 1.00
20:00-21:00 0.50 0.00 0 0 1 0 0.80 0.00 0.50
21:00-22:00 0.50 0.00 0 0 1 0 0.80 0.00 0.05
22:00-23:00 0.50 0.00 0 0 1 0 0.80 0.00 0.05
23:00-24:00 0.00 0.00 0 0 0 0 0.80 0.00 0.05
Computer Centre
Computer Centre
Computer Centre
Corridor/ Lobby
Corridor/ Lobby
Student Zone
Student Zone
Student Zone
Back Office
Back Office
Back Office
Library &
Library &
Library &
Time Period
5 Days/
5 Days/
5 Days/
5 Days/
5 Days/
7 Days/
5 Days/
5 Days/
5 Days/
7 Days/
7Days/
week
week
week
week
week
week
week
week
week
week
week
00:00-01:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
01:00-02:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
02:00-03:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
03:00-04:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
04:00-05:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
05:00-06:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
06:00-07:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.10
07:00-08:00 0.40 0.00 0.00 0.00 0.90 0.00 0.00 0.00 0.35 0.35 0.10
08:00-09:00 0.90 0.90 0.30 0.90 0.90 0.90 0.90 0.90 0.95 0.95 0.70
09:00-10:00 0.90 0.90 0.40 0.30 0.90 0.90 0.90 0.50 0.95 0.95 0.70
10:00-11:00 0.90 0.90 0.50 0.30 0.90 0.90 0.90 0.50 0.95 0.95 0.70
11:00-12:00 0.90 0.90 0.50 0.30 0.90 0.90 0.90 0.50 0.95 0.95 0.70
12:00-13:00 0.90 0.90 0.50 0.90 0.90 0.90 0.90 0.90 0.95 0.95 0.70
13:00-14:00 0.10 0.20 0.20 0.50 0.60 0.30 0.20 0.90 0.20 0.40 0.70
14:00-15:00 0.90 0.90 0.50 0.30 0.90 0.90 0.90 0.50 0.95 0.95 0.70
15:00-16:00 0.90 0.90 0.50 0.30 0.90 0.90 0.90 0.50 0.95 0.95 0.70
16:00-17:00 0.90 0.90 0.50 0.70 0.90 0.90 0.90 0.50 0.95 0.95 0.70
17:00-18:00 0.40 0.00 0.50 0.90 0.90 0.50 0.90 0.90 0.95 0.10 0.80
18:00-19:00 0.00 0.00 0.60 0.00 0.00 0.00 0.90 0.00 0.00 0.10 0.80
19:00-20:00 0.00 0.00 0.60 0.00 0.00 0.00 0.90 0.00 0.00 0.10 0.80
20:00-21:00 0.00 0.00 0.60 0.00 0.00 0.00 0.90 0.00 0.00 0.10 0.80
21:00-22:00 0.00 0.00 0.60 0.00 0.00 0.00 0.90 0.00 0.00 0.10 0.80
22:00-23:00 0.00 0.00 0.60 0.00 0.00 0.00 0.90 0.00 0.00 0.10 0.80
23:00-24:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.00
Hospitality
External
Basement Ventilation
Elevator
Basement Lighting
Lighting Service Hot Water (SHW)
Gu e s t
Laundry
Kitchen
rooms
Time Period
Days/
Days/
Days/
Days/
Days/
Week Days
Week Days
Weekends
Weekends
week
week
week
week
week
7
7
00:00-01:00 0.10 0.10 1.00 0.01 0.01 0.00 0.00 0.50 0.50
01:00-02:00 0.10 0.10 1.00 0.01 0.01 0.00 0.00 0.50 0.50
02:00-03:00 0.10 0.10 1.00 0.01 0.01 0.00 0.00 0.50 0.50
03:00-04:00 0.10 0.10 1.00 0.01 0.01 0.00 0.00 0.50 0.50
04:00-05:00 0.10 0.10 1.00 0.01 0.01 0.00 0.00 0.50 0.50
05:00-06:00 0.20 0.20 1.00 0.01 0.01 0.00 0.00 0.50 0.50
06:00-07:00 0.40 0.50 0.00 0.50 0.70 0.60 0.00 0.50 0.50
07:00-08:00 0.50 0.60 0.00 0.50 0.70 0.80 0.00 0.50 0.50
08:00-09:00 0.50 0.60 0.00 0.30 0.50 0.80 1.00 1.00 1.00
09:00-10:00 0.35 0.40 0.00 0.15 0.30 0.60 1.00 1.00 1.00
10:00-11:00 0.15 0.20 0.00 0.15 0.20 0.60 1.00 1.00 1.00
11:00-12:00 0.15 0.20 0.00 0.15 0.20 0.80 1.00 1.00 1.00
12:00-13:00 0.15 0.20 0.00 0.15 0.20 0.80 1.00 1.00 1.00
13:00-14:00 0.15 0.20 0.00 0.15 0.20 0.80 1.00 1.00 1.00
14:00-15:00 0.15 0.20 0.00 0.15 0.20 0.60 1.00 1.00 1.00
15:00-16:00 0.15 0.20 0.00 0.15 0.20 0.60 1.00 1.00 1.00
16:00-17:00 0.35 0.40 0.00 0.15 0.20 0.60 0.00 1.00 1.00
17:00-18:00 0.50 0.60 0.00 0.30 0.30 0.80 0.00 1.00 1.00
18:00-19:00 0.50 0.60 1.00 0.50 0.50 0.80 0.00 1.00 1.00
19:00-20:00 0.50 0.60 1.00 0.50 0.70 0.80 0.00 1.00 1.00
20:00-21:00 0.50 0.60 1.00 0.65 0.70 0.80 0.00 1.00 1.00
21:00-22:00 0.30 0.40 1.00 0.65 0.90 0.80 0.00 0.50 0.50
22:00-23:00 0.20 0.30 1.00 0.01 0.01 0.60 0.00 0.50 0.50
23:00-24:00 0.10 0.10 1.00 0.01 0.01 0.60 0.00 0.50 0.50
Banquet Room
Public Spaces
Conference/
Guest Room
Back Office
Restaurant
Kitchen
Lobby
Time Period
Week Days
Week Days
Week Days
Week Days
Week Days
Weekends
Weekends
Weekends
Weekends
Weekends
7 Days/
7 Days/
week
week
00:00-01:00 0.65 0.90 0.10 0.10 0.00 0.00 0.00 0.00 0.20 0.20 0.00 0.00
01:00-02:00 0.65 0.90 0.10 0.10 0.00 0.00 0.00 0.00 0.20 0.20 0.00 0.00
02:00-03:00 0.65 0.90 0.10 0.10 0.00 0.00 0.00 0.00 0.20 0.20 0.00 0.00
03:00-04:00 0.65 0.90 0.10 0.10 0.00 0.00 0.00 0.00 0.20 0.20 0.00 0.00
04:00-05:00 0.65 0.90 0.10 0.10 0.00 0.00 0.00 0.00 0.20 0.20 0.00 0.00
05:00-06:00 0.65 0.90 0.10 0.10 0.20 0.50 0.00 0.00 0.20 0.20 0.00 0.00
06:00-07:00 0.50 0.70 0.20 0.20 0.40 0.70 0.00 0.00 0.20 0.20 0.00 0.50
07:00-08:00 0.50 0.70 0.30 0.40 0.40 0.70 0.30 0.30 0.20 0.20 0.00 0.80
08:00-09:00 0.30 0.50 0.40 0.70 0.40 0.70 0.30 0.30 0.20 0.20 0.20 0.80
09:00-10:00 0.15 0.30 0.40 0.70 0.40 0.70 0.30 0.30 0.95 0.50 0.50 0.50
10:00-11:00 0.15 0.20 0.40 0.70 0.40 0.70 0.30 0.30 0.95 0.50 0.90 0.50
11:00-12:00 0.15 0.20 0.40 0.70 0.20 0.30 0.30 0.30 0.95 0.50 0.90 0.80
12:00-13:00 0.15 0.20 0.40 0.70 0.20 0.30 0.80 0.80 0.95 0.50 0.90 0.80
13:00-14:00 0.15 0.20 0.20 0.20 0.20 0.30 0.80 0.80 0.50 0.30 0.90 0.80
14:00-15:00 0.15 0.20 0.20 0.20 0.20 0.30 0.80 0.80 0.95 0.50 0.90 0.50
15:00-16:00 0.15 0.20 0.20 0.20 0.40 0.70 0.30 0.30 0.95 0.50 0.90 0.50
16:00-17:00 0.15 0.20 0.20 0.20 0.40 0.70 0.30 0.30 0.95 0.50 0.90 0.50
17:00-18:00 0.30 0.30 0.40 0.40 0.40 0.70 0.30 0.30 0.95 0.50 0.50 0.80
18:00-19:00 0.50 0.50 0.40 0.40 0.50 0.70 0.50 0.50 0.30 0.30 0.20 0.80
19:00-20:00 0.50 0.70 0.40 0.40 0.80 0.70 0.80 0.90 0.20 0.20 0.20 0.80
20:00-21:00 0.65 0.70 0.30 0.30 0.90 0.70 0.80 0.90 0.20 0.20 0.00 0.80
21:00-22:00 0.65 0.90 0.20 0.20 0.80 0.70 0.80 0.90 0.20 0.20 0.00 0.80
22:00-23:00 0.65 0.90 0.10 0.10 0.60 0.60 0.80 0.90 0.20 0.20 0.00 0.50
23:00-24:00 0.65 0.90 0.10 0.10 0.30 0.30 0.50 0.90 0.20 0.20 0.00 0.50
Hospitality – Lighting
Lighting Schedule
Banquet Room
Public Spaces
Conference/
Guest Room
Back Office
Restaurant
7 Days/ week
7 Days/ week
Week Days
Week Days
Week Days
Week Days
Week Days
Weekends
Weekends
Weekends
Weekends
Weekends
00:00-01:00 0.20 0.30 0.30 0.30 0.20 0.20 0.50 0.50 0.05 0.05 0.00 0.50
01:00-02:00 0.20 0.25 0.30 0.30 0.15 0.20 0.10 0.10 0.05 0.05 0.00 0.05
02:00-03:00 0.10 0.10 0.30 0.30 0.10 0.10 0.10 0.10 0.05 0.05 0.00 0.05
03:00-04:00 0.10 0.10 0.30 0.30 0.10 0.10 0.10 0.10 0.05 0.05 0.00 0.05
04:00-05:00 0.10 0.10 0.30 0.30 0.10 0.10 0.10 0.10 0.05 0.05 0.00 0.05
05:00-06:00 0.20 0.10 0.30 0.30 0.20 0.10 0.10 0.10 0.05 0.05 0.00 0.05
06:00-07:00 0.45 0.40 0.40 0.40 0.40 0.30 0.10 0.10 0.10 0.10 0.00 0.10
07:00-08:00 0.55 0.40 0.30 0.40 0.50 0.30 0.50 0.50 0.30 0.30 0.00 0.30
08:00-09:00 0.45 0.55 0.40 0.70 0.40 0.40 0.50 0.50 0.90 0.60 0.50 0.90
09:00-10:00 0.20 0.20 0.40 0.70 0.20 0.40 0.50 0.50 0.90 0.60 0.80 0.90
10:00-11:00 0.20 0.20 0.40 0.70 0.20 0.40 0.50 0.50 0.90 0.60 0.90 0.90
11:00-12:00 0.20 0.20 0.40 0.70 0.20 0.40 0.50 0.50 0.90 0.60 0.90 0.90
12:00-13:00 0.20 0.20 0.40 0.70 0.20 0.40 0.90 0.90 0.90 0.60 0.90 0.90
13:00-14:00 0.20 0.20 0.40 0.40 0.20 0.40 0.90 0.90 0.50 0.50 0.90 0.50
14:00-15:00 0.20 0.20 0.40 0.40 0.20 0.40 0.90 0.90 0.90 0.60 0.90 0.90
15:00-16:00 0.20 0.20 0.40 0.40 0.20 0.40 0.50 0.50 0.90 0.60 0.90 0.90
16:00-17:00 0.20 0.20 0.40 0.40 0.20 0.40 0.50 0.50 0.90 0.60 0.90 0.90
17:00-18:00 0.30 0.30 0.40 0.40 0.25 0.40 0.50 0.50 0.95 0.60 0.50 0.95
18:00-19:00 0.70 0.85 0.40 0.40 0.60 0.60 0.90 0.90 0.50 0.50 0.50 0.95
19:00-20:00 0.90 1.00 0.40 0.40 0.80 0.70 0.90 0.90 0.30 0.30 0.50 0.95
20:00-21:00 1.00 1.00 0.30 0.30 0.90 0.70 0.90 0.90 0.30 0.30 0.00 0.95
21:00-22:00 0.90 1.00 0.40 0.40 0.80 0.70 0.90 0.90 0.20 0.20 0.00 0.95
22:00-23:00 0.70 0.85 0.30 0.30 0.60 0.60 0.90 0.90 0.10 0.10 0.00 0.95
23:00-24:00 0.30 0.40 0.30 0.30 0.30 0.30 0.90 0.90 0.05 0.05 0.00 0.95
7 Days/ week
7 Days/ week
7 Days/ week
Week Days
Week Days
Week Days
Weekends
Weekends
Weekends
00:00-01:00 0.20 0.20 0.30 0.50 0.50 0.05 0.05 0.00 0.30
01:00-02:00 0.20 0.20 0.20 0.00 0.00 0.05 0.05 0.00 0.10
02:00-03:00 0.20 0.20 0.20 0.00 0.00 0.05 0.05 0.00 0.10
03:00-04:00 0.20 0.20 0.20 0.00 0.00 0.05 0.05 0.00 0.10
04:00-05:00 0.20 0.20 0.20 0.00 0.00 0.05 0.05 0.00 0.10
05:00-06:00 0.20 0.20 0.30 0.00 0.00 0.05 0.05 0.00 0.10
06:00-07:00 0.30 0.30 0.50 0.00 0.00 0.05 0.05 0.00 0.30
07:00-08:00 0.40 0.60 0.50 0.60 0.60 0.10 0.10 0.00 0.30
08:00-09:00 0.70 0.90 0.50 0.60 0.60 0.30 0.30 0.50 0.30
09:00-10:00 0.20 0.20 0.50 0.60 0.60 0.95 0.70 0.50 0.30
10:00-11:00 0.20 0.20 0.35 0.60 0.60 0.95 0.70 0.90 0.30
11:00-12:00 0.20 0.20 0.35 0.60 0.60 0.95 0.70 0.90 0.30
12:00-13:00 0.20 0.20 0.35 0.80 0.80 0.95 0.70 0.90 0.30
13:00-14:00 0.20 0.20 0.35 0.80 0.80 0.50 0.70 0.90 0.30
14:00-15:00 0.20 0.20 0.35 0.80 0.80 0.95 0.70 0.90 0.30
15:00-16:00 0.20 0.20 0.35 0.60 0.60 0.95 0.70 0.90 0.30
16:00-17:00 0.20 0.20 0.35 0.60 0.60 0.95 0.70 0.90 0.30
17:00-18:00 0.30 0.30 0.35 0.60 0.60 0.95 0.70 0.50 0.30
18:00-19:00 0.50 0.50 0.70 0.80 0.80 0.30 0.30 0.50 0.30
19:00-20:00 0.50 0.50 0.90 0.80 0.90 0.10 0.10 0.50 0.30
20:00-21:00 0.50 0.70 0.90 0.80 0.90 0.10 0.10 0.00 0.30
21:00-22:00 0.70 0.70 0.90 0.80 0.90 0.10 0.10 0.00 0.30
22:00-23:00 0.40 0.40 0.70 0.80 0.90 0.05 0.05 0.00 0.30
23:00-24:00 0.20 0.20 0.40 0.80 0.90 0.05 0.05 0.00 0.30
7 Days/
7 Days/
7 Days/
7 Days/
7 Days/
7 Days/
week
week
week
week
week
week
week
00:00-01:00 1 0 0 0 0 0 0
01:00-02:00 1 0 0 0 0 0 0
02:00-03:00 1 0 0 0 0 0 0
03:00-04:00 1 0 0 0 0 0 0
04:00-05:00 1 0 0 0 0 0 0
05:00-06:00 1 1 1 0 0 0 1
06:00-07:00 1 1 1 1 0 0 1
07:00-08:00 1 1 1 1 0 0 1
08:00-09:00 1 1 1 1 1 1 1
09:00-10:00 1 1 1 1 1 1 1
10:00-11:00 1 1 1 1 1 1 1
11:00-12:00 1 1 1 1 1 1 1
12:00-13:00 1 1 1 1 1 1 1
13:00-14:00 1 1 1 1 1 1 1
14:00-15:00 1 1 1 1 1 1 1
15:00-16:00 1 1 1 1 1 1 1
16:00-17:00 1 1 1 1 1 1 1
17:00-18:00 1 1 1 1 1 1 1
18:00-19:00 1 1 1 1 1 1 1
19:00-20:00 1 1 1 1 0 1 1
20:00-21:00 1 1 1 1 0 1 1
21:00-22:00 1 1 1 1 0 0 1
22:00-23:00 1 0 1 1 0 0 1
23:00-24:00 1 0 1 1 0 0 1
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
Weekends
Weekdays
00:00-01:00 0 0 0 1.00 1.00 1.00 0.20 0.20
01:00-02:00 0 0 0 0.50 0.00 0.05 0.05 0.20
02:00-03:00 0 0 0 0.50 0.00 0.05 0.05 0.05
03:00-04:00 0 0 0 0.50 0.00 0.05 0.05 0.05
04:00-05:00 0 0 0 0.50 0.00 0.05 0.05 0.05
05:00-06:00 0 0 0 0.50 0.00 0.05 0.05 0.05
06:00-07:00 0 0 0 0.00 0.00 0.05 0.05 0.05
07:00-08:00 0 0 0 0.00 0.00 0.05 0.10 0.10
08:00-09:00 0 0 0 0.00 0.00 0.05 0.10 0.10
09:00-10:00 0 1 1 0.00 1.00 1.00 0.20 0.20
10:00-11:00 1 1 1 0.00 1.00 1.00 0.40 0.40
11:00-12:00 1 1 1 0.00 1.00 1.00 0.70 0.70
12:00-13:00 1 1 1 0.00 1.00 1.00 0.70 0.80
13:00-14:00 1 1 1 0.00 1.00 1.00 0.70 0.95
14:00-15:00 1 1 1 0.00 1.00 1.00 0.70 0.95
15:00-16:00 1 1 1 0.00 1.00 1.00 0.70 0.95
16:00-17:00 1 1 1 0.00 1.00 1.00 0.70 0.95
17:00-18:00 1 1 1 0.00 1.00 1.00 0.80 0.95
18:00-19:00 1 1 1 1.00 1.00 1.00 0.80 0.95
19:00-20:00 1 1 1 1.00 1.00 1.00 0.80 0.95
20:00-21:00 1 1 1 1.00 1.00 1.00 0.80 0.95
21:00-22:00 0 1 1 1.00 1.00 1.00 0.80 0.80
22:00-23:00 0 1 1 1.00 1.00 1.00 0.50 0.60
23:00-24:00 0 1 1 1.00 1.00 1.00 0.30 0.40
Shopping Complex
Equipment
Special Zone
Special Zone
Special Zone
Corridors &
Corridors &
Atrium
Atrium
Retail
Retail
Retail
Time Period
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
Weekend
Weekend
Weekend
Weekday
Weekday
Weekday
00:00-01:00 0.00 0.00 0.00 0.10 0.00 0.00 0.05 0.05 0.05 0.05 0.05
01:00-02:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
02:00-03:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
03:00-04:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
04:00-05:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
05:00-06:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
06:00-07:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
07:00-08:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.05
08:00-09:00 0.00 0.00 0.00 0.00 0.00 0.00 0.05 0.05 0.05 0.05 0.50
09:00-10:00 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.05 0.50
10:00-11:00 0.40 0.40 0.40 0.40 0.20 0.20 0.50 0.50 0.40 0.90 0.90
11:00-12:00 0.60 0.60 0.60 0.60 0.30 0.50 0.95 0.50 0.60 0.90 0.90
12:00-13:00 0.60 0.70 0.60 0.70 0.50 0.70 0.95 0.50 0.60 0.90 0.90
13:00-14:00 0.60 0.90 0.60 0.90 0.50 0.70 0.95 0.50 0.60 0.90 0.90
14:00-15:00 0.70 0.90 0.70 0.90 0.50 0.70 0.95 0.50 0.60 0.90 0.90
15:00-16:00 0.70 0.90 0.70 0.90 0.50 0.80 0.95 0.50 0.40 0.90 0.90
16:00-17:00 0.70 0.90 0.70 0.90 0.50 0.80 0.95 0.70 0.40 0.90 0.90
17:00-18:00 0.70 0.90 0.70 0.90 0.50 0.80 0.95 0.95 0.40 0.90 0.90
18:00-19:00 0.90 0.95 0.90 0.95 0.60 0.95 0.95 0.95 0.80 0.90 0.90
19:00-20:00 0.90 0.95 0.90 0.95 0.60 0.95 0.95 0.95 0.80 0.90 0.90
20:00-21:00 0.90 0.95 0.90 0.95 0.60 0.95 0.95 0.95 0.80 0.50 0.90
21:00-22:00 0.00 0.00 0.40 0.40 0.60 0.95 0.05 0.50 0.80 0.05 0.90
22:00-23:00 0.00 0.00 0.30 0.30 0.60 0.95 0.05 0.30 0.80 0.05 0.90
23:00-24:00 0.00 0.00 0.10 0.10 0.30 0.95 0.05 0.30 0.80 0.05 0.90
Food Preparation
Food Preparation
Food Preparation
Food Preparation
Family Dining
Family Dining
Family Dining
Family Dining
Bar Lounge
Bar Lounge
Bar Lounge
Bar Lounge
Time Period
00:00-01:00 0.00 0.50 0.70 0.50 0.70 0.70 0.50 0.60 0.70 1 0 1
01:00-02:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
02:00-03:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
03:00-04:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
04:00-05:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
05:00-06:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
06:00-07:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
07:00-08:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
08:00-09:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0
09:00-10:00 0.00 0.20 0.00 0.00 0.50 0.00 0.00 0.60 0.00 0 0 0
10:00-11:00 0.20 0.50 0.00 0.50 0.70 0.00 0.60 0.70 0.00 0 1 0
11:00-12:00 0.20 0.80 0.00 0.50 0.90 0.00 0.60 0.70 0.00 1 1 0
12:00-13:00 0.70 0.80 0.00 0.90 0.90 0.00 0.80 0.70 0.00 1 1 0
13:00-14:00 0.70 0.80 0.00 0.90 0.90 0.00 0.80 0.70 0.00 1 1 0
14:00-15:00 0.70 0.80 0.00 0.90 0.90 0.00 0.80 0.70 0.00 1 1 0
15:00-16:00 0.20 0.50 0.00 0.50 0.70 0.00 0.60 0.40 0.00 1 1 0
16:00-17:00 0.20 0.30 0.00 0.50 0.50 0.00 0.60 0.40 0.00 1 1 1
17:00-18:00 0.20 0.30 0.50 0.50 0.50 0.70 0.60 0.40 0.70 1 1 1
18:00-19:00 0.50 0.50 0.70 0.90 0.70 0.80 0.80 0.40 0.70 1 1 1
19:00-20:00 0.80 0.90 0.80 0.90 0.90 0.80 0.80 0.70 0.70 1 1 1
20:00-21:00 0.80 0.90 0.80 0.90 0.90 0.80 0.80 0.70 0.70 1 1 1
21:00-22:00 0.80 0.90 0.80 0.90 0.90 0.80 0.80 0.70 0.70 1 1 1
22:00-23:00 0.80 0.90 0.80 0.90 0.90 0.80 0.80 0.70 0.70 1 1 1
23:00-24:00 0.50 0.50 0.80 0.90 0.90 0.80 0.80 0.40 0.70 1 1 1
Equipment
Basement Ventilation
Schedule
Schedule
Basement Lighting
Elevator Schedule
External Lighting
Occupancy
Schedule
Schedule
(On/Off)
Spaces
Retail &
All
All
Time Period Circulation
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
7 Days/ week
Weekends
Weekends
Weekdays
Weekdays
00:00-01:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
01:00-02:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
02:00-03:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
03:00-04:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
04:00-05:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
05:00-06:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
06:00-07:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.00 0.00 0.05
07:00-08:00 0.00 0.00 0.05 0.05 0 0.10 0.10 0.00 0.00 0.05
08:00-09:00 0.00 0.00 0.05 0.05 0 0.10 0.10 0.00 0.00 0.05
09:00-10:00 0.20 0.20 0.20 0.05 1 0.20 0.20 0.00 1.00 1.00
10:00-11:00 0.40 0.40 0.50 0.90 1 0.40 0.40 0.00 1.00 1.00
11:00-12:00 0.60 0.60 0.95 0.90 1 0.70 0.70 0.00 1.00 1.00
12:00-13:00 0.60 0.70 0.95 0.90 1 0.70 0.80 0.00 1.00 1.00
13:00-14:00 0.60 0.90 0.95 0.90 1 0.70 0.95 0.00 1.00 1.00
14:00-15:00 0.70 0.90 0.95 0.90 1 0.70 0.95 0.00 1.00 1.00
15:00-16:00 0.70 0.90 0.95 0.90 1 0.70 0.95 0.00 1.00 1.00
16:00-17:00 0.70 0.90 0.95 0.90 1 0.70 0.95 0.00 1.00 1.00
17:00-18:00 0.70 0.90 0.95 0.90 1 0.80 0.95 0.00 1.00 1.00
18:00-19:00 0.90 0.95 0.95 0.90 1 0.80 0.95 1.00 1.00 1.00
19:00-20:00 0.90 0.95 0.95 0.90 1 0.80 0.95 1.00 1.00 1.00
20:00-21:00 0.90 0.95 0.95 0.50 1 0.80 0.95 1.00 1.00 1.00
21:00-22:00 0.00 0.00 0.05 0.05 0 0.00 0.00 1.00 0.20 0.50
22:00-23:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
23:00-24:00 0.00 0.00 0.05 0.05 0 0.00 0.00 0.20 0.00 0.05
APPENDICES
from this section shall be applied to all outdoor
exposed surfaces.
A1.1 Procedure for Determining
Fenestration Product U-factor and Solar (g) Section 8.4.2 of ISO 15099 presents two
possible approaches for incorporating the
Heat Gain Coefficient
impacts of self-viewing surfaces on interior
Section 5.2.1-(a) and Section 5.2.1-(b) require that U- radiative heat transfer calculations. Products
factors and solar heat gain coefficients (SHGC) be shall use the method in Section 8.4.2.1 of ISO
determined for the overall fenestration product 15099 (Two-Dimensional Element to Element
(including the sash and frame) in accordance with ISO View Factor Based Radiation Heat Transfer
15099. Calculation). The alternate approach in Section
8.4.3 of ISO 15099 shall not be used.
In several cases, ISO 15099 suggests that individual
national standards will need to be more specific and in
A1.2 Default U-factors, Visible Light
other cases the ISO document gives users the choice of
two options. This section clarifies these specific issues as Transmittance and Solar Heat Gain
they are to be implemented for this code: Coefficients for Unrated Fenestration
Products
(a) Section 4.1 of ISO 15099: For calculating the
overall U-factor, ISO 15099 offers a choice All fenestration with U-factors, SHGC, or visible light
between the linear thermal transmittance transmittance determined, certified, and labeled in
(4.1.2) and the area weighted method (4.1.3). accordance ISO 15099 shall be assigned those values.
The area weighted method (4.1.3) shall be used.
A1.2.1 Unrated Vertical Fenestration.
(b) Section 4.2.2 of ISO 15099: Frame and divider
SHGC’s shall be calculated in accordance with For unrated vertical fenestration, both operable and
Section 4.2.2. The alternate approach in Section fixed, the glass VLT reported by manufacturer must
8.6 shall not be used. meet or exceed 0.37 (as it accounts for framing). The
SHGC values reported by glass manufacturer must meet
(c) Section 6.4 of ISO 15099 refers the issue of
material properties to national standards. or exceed the Standardized requirements in Table 5-9,
Material conductivities and emissivity shall be Table 5-10 and Table 5-11 for compliance.
determined in accordance with Indian
U-factors for unrated vertical fenestration, both
standards.
operable and fixed, shall be assigned as per Table A1.1.
(d) Section 7 of ISO 15099 on shading systems is
currently excluded.
Table A1.1: Defaults for Unrated Fenestration (Overall
(e) Section 8.2 of ISO 15099 addresses Assembly including the Sash and Frame)
environmental conditions. The following are
defined for India: Frame Type Glazing Type U-Factor
(W/m2.K)
For U-factor calculations: All frame types Single Glazing 7.1
Tin = 24 C Wood, vinyl, or fiberglass Double Glazing 3.4
Tout = 32 C frame or metal frame with (COG U value
thermal break >1.6 W/m2.K)
V = 3.35 m/s
Trm,out=Tout Wood, vinyl, or fiberglass Double Glazing 3.0
frame or metal frame with (COG U value
Trm,in=Tin thermal break <1.6 W/m2.K)
Is=0 W/m2
Metal and other frame Double Glazing 5.1
For SHGC calculations: type
Tin = 24 C
Tout = 32 C
V = 2.75 m/s A1.3 Typical Roof Constructions
Trm,out=Tout For calculating the overall U-factor of a typical roof
Trm,in=Tin construction, the U-factors from the typical wall
Is=783 W/m2 construction type and effective U-factor for insulation
(f) Section 8.3 of ISO 15099 addresses convective film shall be combined according to the following equation:
coefficients on the interior and exterior of the
window product. In Section 8.3.1 of ISO 15099,
APPENDICES
where
1
U TotalWall =
1 1
+
U TypicalWall U TyipcalInsulation
where
Description
APPENDICES
Specific
Density Conductivityb k, Resistance R,
Heat,
Board
Asbestos/cement board 1900 0.57 - 1
Cement board 1150 0.25 - 0.84
Fiber/cement board 1400 0.25 - 0.84
1000 0.19 - 0.84
400 0.07 - 1.88
300 0.06 - 1.88
Gypsum or plaster board 640 0.16 - 1.15
Oriented strand board (OSB) 9 to 11 mm 650 - 0.11 1.88
Oriented strand board (OSB) 12.7 mm 650 - 0.12 1.88
Plywood (douglas fir) 12.7 mm 460 - 0.14 1.88
Plywood (douglas fir) 15.9 mm 540 - 0.15 1.88
Plywood/wood panels 19.0 mm 550 - 0.19 1.88
Vegetable fiber board -
Sheathing, regular densitye 12.7 mm 290 - 0.23 1.3
Intermediate densitye .. 12.7 mm 350 - 0.19 1.3
Nail-base sheathinge 12.7 mm 400 - 0.19 1.3
Shingle backer 9.5 mm 290 - 0.17 1.3
Sound deadening board. 12.7 mm 240 - 0.24 1.26
Tile and lay-in panels, plain or acoustic 290 0.058 - 0.59
Laminated paperboard 480 0.072 - 1.38
Homogeneous board from repulped paper 480 0.072 - 1.17
Hardboarde
Medium density 800 0.105 - 1.3
High density, service-tempered 880 0.12 - 1.34
Grade and service grade
High density, standard-tempered grade 1010 0.144 - 1.34
Particleboarde
Low density 590 0.102 - 1.3
Medium density 800 0.135 - 1.3
High density 1000 0.18 - -
Underlayment 15.9 mm 640 - 1.22 1.21
Waferboard 700 0.072 - 1.88
Shingles
Asbestos/cement 1900 - 0.37 -
Wood, 400 mm, 190 mm exposure - - 0.015 1.3
Wood, double, 400 mm, 300 mm exposure - - 0.21 1.17
Wood, plus ins. backer board 8 mm - - 0.25 1.3
APPENDICES
Asphalt insulating siding (12.7 mm bed) - - 0.26 1.47
Hardboard siding 11 mm - - 0.12 1.17
Wood, drop, 200 mm 25 mm - - 0.14 1.17
Wood, bevel 200 mm, lapped13 mm - - 0.14 1.17
Wood, bevel 250 mm, lapped19 mm - - 0.18 1.17
Wood, plywood, lapped 9.5 mm - - 0.1 1.22
Aluminum, steel, or vinyl,j,k over sheathing Hollow-backed - - 0.11 1.22
Aluminum, steel, or vinyl,j,k over sheathing Insulating- - - 0.32 1.34
board-backed 9.5 mm
Aluminum, steel, or vinyl,j,k over sheathing Foil-backed 9.5 - - 0.52 -
mm
Architectural (soda-lime float) glass 2500 1 - 0.84
Building Membrane
Vapor-permeable felt - - 0.011 -
Vapor: seal, 2 layers of mopped 0.73 kg/m2 felt - - 0.21 -
Vapor: seal, plastic film - - Negligible -
Finish Flooring Materials
Carpet and rebounded urethane pad 19 mm 110 - 0.42 -
Carpet and rubber pad (one-piece) 9.5 mm 320 - 0.12 -
Pile carpet with rubber pad 9.5 to 12.7 mm 290 - 0.28 -
Linoleum/cork tile 6.4 mm 465 - 0.09 -
PVC/Rubber floor covering - 0.4 - -
Rubber tile 25 mm 1900 - 0.06 -
Terrazzo 25 mm - - 0.014 0.8
Insulating Materials
Blanket and battc,d
Glass-fiber batts 85 to 90 mm 10 to 14 0.043 - 0.84
Glass-fiber batts 50 mm 8 to 13 0.045 to 0.048 - 0.84
Mineral fiber 140 mm 30 0.036 - 0.84
Mineral wool, felted 16 to 48 0.04 - -
65 to 130 0.035 - -
Slag wool . 50 to 190 0.038 - -
255 0.04 - -
305 0.043 - -
350 0.048 - -
400 0.05 - -
Board and slabs
Cellular glass. 130 0.048 - 0.75
Cement fiber slabs, shredded wood 400 to 430 0.072 to 0.076 - -
with Portland cement binder
-
Cement fiber slabs, shredded wood 350 0.082 - 1.3
with magnesia oxysulfide binder
Glass fiber board 160 0.032 to 0.040 - 0.84
Expanded rubber (rigid) 70 0.032 - 1.67
Expanded polystyrene extruded (smooth skin) 25 to 40 0.022 to 0.030 - 1.47
APPENDICES
335 0.053 - -
Mineral fiberboard, wet-molded, acoustical tile. 370 0.061 - 0.59
Perlite board 160 0.052 - -
Polyisocyanurate, aged unfaced 25 to 35 0.020 to 0.027 - -
Polyisocyanurate, aged with facers 65 0.019 - 1.47
Phenolic foam board with facers, aged 65 0.019 - -
Loose fill
Cellulosic (milled paper or wood pulp) 35 to 50 0.039 to 0.045 - 1.38
Perlite, expanded 30 to 65 0.039 to 0.046 - 1.09
65 to 120 0.045 to 0.052 - -
120 to 180 0.052 to 0.061 - -
Mineral fiber (rock, slag, or glass)d approx. 95 to 130 mm 10 to 30 - 1.92 0.71
Mineral fiber (rock, slag, or glass)d approx. 170 to 220 mm 11 to 30 - 3.33 -
Mineral fiber (rock, slag, or glass)d approx. 190 to 250 mm 12 to 30 - 3.85 -
Mineral fiber (rock, slag, or glass)d approx. 260 to 350 mm 13 to 30 - 5.26 -
Mineral fiber (rock, slag, or glass)d 90 mm (closed sidewall 30 to 55 - 2.1 to 2.5 -
application)
Vermiculite, exfoliated 110 to 130 0.068 - 1.34
64 to 96 0.063 - -
Spray-applied
Cellulosic fiber 55 to 95 0.042 to 0.049 - -
Glass fiber 55 to 70 0.038 to 0.039 - -
Polyurethane foam (low density) 6 to 8 0.042 - 1.47
40 0.026 - 1.47
Polyurethane foam (low density) aged and dry 40 mm 30 - 1.6 1.47
Polyurethane foam (low density) 50 mm 55 - 1.92 1.47
Polyurethane foam (low density) 120 mm 30 - 3.69 -
Ureaformaldehyde foam, dry 8 to 20 0.030 to 0.032 - -
Roofing
Asbestos/cement shingles 1120 - 0.037 1
Asphalt (bitumen with inert fill) 1600 0.43 - -
1900 0.58 - -
2300 1.15 - -
Asphalt roll roofing 920 - 0.027 1.51
Asphalt shingles 920 - 0.078 1.26
Built-up roofing 920 - 0.059 1.47
Mastic asphalt (heavy, 20% grit) 950 0.19 - -
Reed thatch 270 0.09 - -
Roofing felt 2250 1.2 - -
Slate 13 mm - - 0.009 1.26
Straw thatch 240 0.07 - -
Wood shingles, plain and plastic-film-faced - - 0.166 1.3
Plastering Materials
Cement plaster, sand aggregate 1860 0.72 - 0.84
APPENDICES
Lightweight aggregate 720 - 0.056 -
Lightweight aggregate 720 - 0.066 -
Lightweight aggregate - - 0.083 -
Perlite aggregate 720 0.22 - 1.34
Sand aggregate 1680 0.81 - 0.84
Sand aggregate on metal lath 19 mm - - 0.023 -
Vermiculite aggregate 480 0.14 - -
600 0.2 - -
720 0.25 - -
840 0.26 - -
960 0.3 - -
Perlite plaster 400 0.08 - -
600 0.19 - -
Pulpboard or paper plaster 600 0.07 - -
Sand/cement plaster, conditioned 1560 0.63 - -
Sand/cement/lime plaster, conditioned 1440 0.48 - -
Sand/gypsum (3:1) plaster, conditioned 1550 0.65 - -
Masonry Materials
Masonry units
Brick, fired clay 2400 1.21 to 1.47 - -
2240 1.07 to 1.30 - -
2080 0.92 to 1.12 - -
1920 0.81 to 0.98 - 0.8
1760 0.71 to 0.85 - -
1600 0.61 to 0.74 - -
1440 0.52 to 0.62 - -
1280 0.43 to 0.53 - -
1120 0.36 to 0.45 - -
Clay tile, hollow 1 cell deep 75 mm - - 0.14 0.88
Clay tile, hollow 1 cell deep 100 mm - - 0.2 -
Clay tile, hollow 2 cells deep 150 mm - - 0.27 -
Clay tile, hollow 2 cells deep 200 mm - - 0.33 -
Clay tile, hollow 2 cells deep 250 mm - - 0.39 -
Clay tile, hollow 3 cells deep 300 mm - - 0.44 -
Lightweight brick 800 0.2 - -
770 0.22 - -
Concrete blocksh,i Limestone aggregate ~200 mm, 16.3 kg, - - - -
2200 kg/m3 concrete, 2 cores ..
Concrete blocksh,i Limestone aggregate ~200 mm, 16.3 kg, - - 0.37 -
2200 kg/m3 concrete with perlite-filled cores
Concrete blocksh,i Limestone aggregate ~300 mm, 25 kg, - - -
2200 kg/m3 concrete, 2 cores
Normal-weight aggregate (sand and gravel)~200 mm, 16 - - 0.20 to 0.17 0.92
kg, 2100 kg/m3 concrete, 2 or 3 cores ..
Normal-weight aggregate (sand and gravel)~200 mm, 16 - - 0.35 -
kg, 2100 kg/m3 with perlite-filled cores
APPENDICES
lightweight aggregate) ~200 mm, 13 kg, 1550 to 1800
kg/m3 concrete, 2 or 3 cores
Medium-weight aggregate (combinations of normal and - - 0.65 to 0.41 -
lightweight aggregate) ~200 mm, 13 kg, 1550 to 1800
kg/m3 with perlite-filled cores
Medium-weight aggregate (combinations of normal and - - 0.58 -
lightweight aggregate) ~200 mm, 13 kg, 1550 to 1800
kg/m3 with vermiculite-filled cores
Medium-weight aggregate (combinations of normal and - - 0.56 -
lightweight aggregate) ~200 mm, 13 kg, 1550 to 1800
kg/m3 with molded-EPS-filled (beads) cores
Medium-weight aggregate (combinations of normal and - - 0.47 -
lightweight aggregate) ~200 mm, 13 kg, 1550 to 1800
kg/m3 with molded EPS inserts in cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.34 to 0.29 -
pumice) ~150 mm, 7 1/2 kg, 1400 kg/m2concrete, 2 or 3
cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.74 -
pumice) ~150 mm, 7 1/2 kg, 1400 kg/m2with perlite-filled
cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.53 -
pumice) ~150 mm, 7 1/2 kg, 1400 kg/m2with vermiculite-
filled cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.56 to 0.33 0.88
pumice) 200 mm, 8 to 10 kg, 1150 to 1380 kg/m2 concrete
Low-mass aggregate (expanded shale, clay, slate or slag, - - 1.20 to 0.77 -
pumice) 200 mm, 8 to 10 kg, 1150 to 1380 kg/m2 concrete
with perlite-filled cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.93 to 0.69 -
pumice) 200 mm, 8 to 10 kg, 1150 to 1380 kg/m2 concrete
with vermiculite-filled cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.85 -
pumice) 200 mm, 8 to 10 kg, 1150 to 1380 kg/m2 concrete
with molded-EPS-filled (beads) cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.79 -
pumice) 200 mm, 8 to 10 kg, 1150 to 1380 kg/m2 concrete
with UF foam-filled cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.62 -
pumice) 200 mm, 8 to 10 kg, 1150 to 1380 kg/m2 concrete
with molded EPS inserts in cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 0.46 to 0.40 -
pumice) 300 mm, 16 kg, 1400 kg/m3,concrete, 2 or 3 cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 1.6 to 1.1 -
pumice) 300 mm, 16 kg, 1400 kg/m3,with perlite-filled
cores
Low-mass aggregate (expanded shale, clay, slate or slag, - - 1 -
pumice) 300 mm, 16 kg, 1400 kg/m3,with vermiculite-filled
cores
Stone, lime, or sand 2800 10.4 - -
Quartzitic and sandstone 2560 6.2 - -
2240 3.46 - -
1920 1.88 - 0.88
Calcitic, dolomitic, limestone, marble, and granite 2880 4.33 - -
2560 3.17 - -
2240 2.31 - -
1920 1.59 - 0.88
1600 1.15 - -
Gypsum partition tile .75 by 300 by 760 mm, solid - - 0.222 0.79
APPENDICES
Concretes
Sand and gravel or stone aggregate concretes (concretes 2400 1.4 to 2.9 - -
with >50% quartz or quartzite sand have conductivities in
2240 1.3 to 2.6 - 0.80 to 1.00
higher end of range)
2080 1.0 to 1.9 - -
Low-mass aggregate or limestone concretes 1920 0.9 to 1.3 - -
Low-mass aggregate or limestone concretes Expanded 1600 0.68 to 0.89 - 0.84
shale, clay, or slate; expanded slags ;cinders; pumice (with
1280 0.48 to 0.59 - 0.84
density up to 1600 kg/m3); scoria (sanded concretes have
conductivities in higher end of range) 960 0.30 to 0.36 - -
640 0.18 - -
Gypsum/fiber concrete (87.5% gypsum, 12.5% wood 800 0.24 - 0.84
chips)
Cement/lime, mortar, and stucco 1920 1.4 - -
1600 0.97 - -
1280 0.65 - -
Perlite, vermiculite, and polystyrene beads 800 0.26 to 0.27 - -
640 0.20 to 0.22 - 0.63 to 0.96
480 0.16 - -
320 0.12 - -
Foam concretes 1920 0.75 - -
1600 0.6 - -
1280 0.44 - -
1120 0.36 - -
Foam concretes and cellular concretes 960 0.3 - -
640 0.2 - -
320 0.12 - -
Aerated concrete (oven-dried) 430 to 800 0.2 - 0.84
Polystyrene concrete (oven-dried) 255 to 800 0.37 - 0.84
Polymer concrete 1950 1.64 - -
2200 1.03 - -
Polymer cement 1870 0.78 - -
Slag concrete 960 0.22 - -
1280 0.32 - -
1600 0.43 - -
2000 1.23 - -
Woods (12% moisture content)
Hardwoods - - - 1.63
Oak 660 to 750 0.16 to 0.18 - -
Birch 680 to 725 0.17 to 0.18 - -
Maple 635 to 700 0.16 to 0.17 - -
Ash 615 to 670 0.15 to 0.16 - -
Softwoods - - - 1.63
Southern pine 570 to 660 0.14 to 0.16 - -
Southern yellow pine 500 0.13 - -
Eastern white pine 400 0.1 - -
APPENDICES
Western red cedar 350 0.09 - -
West coast woods, cedars 350 to 500 0.10 to 0.13 - -
Eastern white cedar 360 0.1 - -
California redwood 390 to 450 0.11 to 0.12 - -
Pine (oven-dried) 370 0.092 - 1.88
Spruce (oven-dried) 395 0.1 - 1.88
aValues are for mean temperature of 24°C. Representative values for dry materials are intended as design (not specification) values for materials in normal use. Thermal
values of insulating materials may differ from design values depending on in-situ properties (e.g., density and moisture content, orientation, etc.) and manufacturing
variability. For properties of specific product, use values supplied by manufacturer or unbiased tests.
bSymbol λ also used to represent thermal conductivity.
cDoes not include paper backing and facing, if any. Where insulation forms boundary (reflective or otherwise) of airspace
dConductivity varies with fiber diameter. Batt, blanket, and loose-fill mineral fiber insulations are manufactured to achieve specified R-values, the most common of which
are listed in the table. Because of differences in manufacturing processes and materials, the product thicknesses, densities, and thermal conductivities vary over
considerable ranges for a specified R-value.
eValues are for aged products with gas-impermeable facers on the two major surfaces. An aluminum foil facer of 25 µm thickness or greater is generally considered
nonreflective; and on thickness, type, and application of insulating backing-board used. Values are averages for use as design guides, and were obtained from several
guarded hot box tests (ASTM Standard C236) or calibrated hot box (ASTM Standard C976) on hollow-backed types and types made using backing of wood fiber, foamed
plastic, and glass fiber. Departures of ±50% or more from these values may occur.
kVinyl specific heat = 1.0 kJ/(kg·K)
lSee Adams (1971), MacLean (1941), and Wilkes (1979). Conductivity values listed are for heat transfer across the grain. Thermal conductivity of wood varies linearly
with density, and density ranges listed are those normally found for wood species given. If density of wood species is not known, use mean conductivity value. For
extrapolation to other moisture contents, the following empirical equation developed by Wilkes (1979) may be used:
(1.874 × 10−2 + 5.733 × 10−4 𝑀)𝜌
𝑘 = 0.1791 +
1 + 0.01 𝑀
where ρ is density of moist wood in kg/m3, and M is moisture content in percent.
mFrom Wilkes (1979), an empirical equation for specific heat of moist wood at 24°C is
as follows:
(0.299 + 0.01 𝑀)
𝐶𝑝 = + ∆𝐶𝑝
(1 + 0.01 𝑀)
where Δcp accounts for heat of sorption and is denoted by
∆𝐶𝑝 = 𝑀(1.921 × 10−3 − 3.168 × 10−5𝑀)
where M is moisture content in percent by mass.
nBlank space in reference column indicates historical values from previous volumes of ASHRAE Handbook. Source of information could not be determined.
Appendix
Appendix
Amritsar Composite Lucknow Composite
Aurangabad Hot & Dry Ludhiana Composite
Bangalore Temperate Chennai Warm & Humid
Barmer Hot & Dry Manali Cold
Belgaum Warm & Humid Mangalore Warm & Humid
Bhagalpur Warm & Humid Mumbai Warm & Humid
Bhopal Composite Nagpur Composite
Bhubaneshwar Warm & Humid Nellore Warm & Humid
Bikaner Hot & Dry New Delhi Composite
Chandigarh Composite Panjim Warm & Humid
Chitradurga Warm & Humid Patna Composite
Dehradun Composite Pune Warm & Humid
Dibrugarh Warm & Humid Raipur Composite
Guwahati Warm & Humid Rajkot Composite
Gorakhpur Composite Ramgundam Warm & Humid
Gwalior Composite Ranchi Composite
Hissar Composite Ratnagiri Warm & Humid
Hyderabad Composite Raxaul Warm & Humid
Imphal Warm & Humid Saharanpur Composite
Indore Composite Shillong Cold
Jabalpur Composite Sholapur Hot & Dry
Jagdelpur Warm & Humid Srinagar Cold
Jaipur Composite Sundernagar Cold
Jaisalmer Hot & Dry Surat Hot & Dry
Jalandhar Composite Tezpur Warm & Humid
Jamnagar Warm & Humid Tiruchirappalli Warm & Humid
Jodhpur Hot & Dry Trivandrum Warm & Humid
Jorhat Warm & Humid Tuticorin Warm & Humid
Kochi Warm & Humid Udhagamandalam Cold
Kolkata Warm & Humid Vadodara Hot & Dry
Kota Hot & Dry Veraval Warm & Humid
Kullu Cold Vishakhapatnam Warm & Humid
Appendix
Prior to Performance Testing, verify and document
the following:
Sustainable Materials
Please refer to EN 15978 for the definitions.
A6. Sustainable Materials
Stages of assessment (as per EN 15978) CEN 2011.
A6.1 General
Product (A1-A3): The boundary for modules A1 to A3
ECSBC requires the buildings to report the embodied
covers the ‘cradle to gate’ processes for materials used
carbon in kgCO2-eq/Sqm. The reporting of the in the building. These numbers are typically declared
embodied carbon is limited to the A1-A3 life stage as as a sum of A1 to A3 by the manufacturers. Building
defined in EN 15978. developers can ask for these numbers when choosing
a building material. These numbers should be in
accordance with EN 15804. (CEN, 2019)
A6. 2 Purpose
The purpose of reporting embodied carbon as part of
the Energy Conservation and Sustainable Building
Code is to disclose the initial embodied carbon
emissions from the building construction materials
used in commercial buildings in India.
A6.3 Scope
a. Applicable to all buildings under the purview
of ECSBC
b. Applicable to building materials used in
structural systems and building envelop
systems namely all kinds of foundations,
retaining walls, substructure as part of the
structural system, superstructure such as but
not limited to beams, columns, sheer walls,
opaque and non-opaque structural and non-
structural external walls, structure for
mezzanine floors and loft floors, floors,
ceilings, roofs, staircases and ramps,
fenestration such windows, skylights and
ventilation openings.
A6.4 Exclusions
The approach does not include materials used in
electro-mechanical systems, plumbing systems,
firefighting systems, elevators, finishing materials A6.6 Method of calculation
including wall, floor and ceiling finishes, or any
other kind of non-structural elements such as Annexure-A contains the Comma Separated Value
railings, parapet walls, or built-in furniture. (CSV) Spreadsheet format. The fulfilment of
Sustainable Materials
Table A6.1 Introduction
Applicable to building materials used in structural systems and building envelop systems, namely all kinds of
foundations, retaining walls, substructures as part of the structural system, super structures such as but not limited
to beams, columns, sheer walls, opaque and non-opaque structural and non-structural external walls, structure for
mezzanine floors and loft floors, floors, ceilings, roofs, staircases and ramps, fenestration such windows, skylights and
ventilation openings.
The project for ECSBC compliance shall gather primary data for embodied energy of construction materials including
but not limited to the ones mentioned in the sheets. The system boundary is Cradle to Gate, i.e., unit processes A1 to
A3. The data for the same is required to be entered in sheets 'A1',' A2', and 'A3'.
The availability of Bill of Quantities (BoQ) and material supplier details is a must.
Sustainable Materials
Bill of Quantities:
Sheet meant for recording quantities of construction materials. In this sheet, the BoQ of
BoQ
multiple Sites may be entered in adjacent columns. For example, BoQ details of S1_B1 can
be added in columns B to I, and S2_B1 can be added in columns J to Q and so on.
A1_Extraction and Sheet for entering embodied energy/carbon attributed to 'Raw material extraction and
Procurement procurement'
Sheet for entering embodied energy/carbon attributed to 'Transport to manufacturing
A2_Transport
plant'
Sheet for presenting total embodied energy/carbon for stages A1 to A3. This sheet
contains tow categories of resultant embodied energy/carbon: a) it may be calculated
Sum of A1 to A3 using the data gathered in sheets A1 to A3 if data of that granularity is available), b) it may
be directly obtained from the manufacturer (if data of individual unit process granularity is
not available).
Building_ELE_CON Sheet for recording the annual electricity consumption of the building
Sheet for recording the dominant companies/manufacturers in that region. This may help
Prominent
when the material source is unknown and it is safe to assume that it may be from the
Manufacturers
companies having the highest market penetration.
Validation Tables Sheet contains background information used for creating drop downs for certain columns
Sustainable Materials
All Building: refers to an individual building block of the Site
Sustainable Materials
Indicates the source from which the material-related
data has been obtained. Please select from the available
options mentioned in the drop down:
Material Supplier
Make and Model data
Contractor/Designer
Source
Owner
Tender Document
Government DPR
Architectural Drawings
Indicates the availability of architectural drawings for the
Building. Data shall be selected from the drop down list
having the following options:
Building Drawings
Yes-Fully Available
Yes-Partly Available
Not Available
This cell contains the link to the digital file of
architectural drawings of the selected Building. The file
Building Layout (file) may be ".dwg" or in image format.
Please upload image/cad file of layout over Gdrive folder
and paste link here
Indicates the built up area of the building. In case more
Built up area
than one building configurations exist in the same site,
(sq. m)
please add its built up area in the next column.
Sustainable Materials
extracted and procured for producing, say, 1 MT (1 unit)
of the finished construction material.
Qty of Raw Material
Many manufacturers calculate the embodied
Extracted and Calculated
energy/carbon in reference to a certain qty of final
Procured
product. For example, in their annual sustainability
reports, cement manufacturers mention the embodied
carbon values per MT of cement.
Unit (RM) Refers to the measurement unit of Raw Materials Primary
Refers to the quantity of finished Construction Material
Reference Qty of for which the embodied energy data is being collected.
finished construction For example, the manufacturer might provide the MJ of Primary
material energy used in production of 1 MT cement. Thus, the
"qty of finishes construction material" would be 1 MT.
Refers to the measurement unit of finished construction
Unit (FCM) Primary
material
Refers to types of fuels used in the extraction and
Fuel Mix Primary
procurement processes
Refers to the energy consumed during the extraction and
Embodied Energy Primary
procurement processes
Indicates the unit in which embodied energy is reported.
Units shall be selected from the following drop down
Unit (EE) options: Primary
A1_Extraction and
MJ
Procurement,
kWh
A2_Transport, and
Refers to the carbon released during the extraction and
A3_Manufacturing Embodied Carbon Primary
procurement processes
Indicates the unit in which embodied energy is reported.
Units shall be selected from the following drop down
options:
Unit (EC) Primary
kg CO2 (assuming the emissions of rest of the GHG as 0)
kg CO2e (includes the emissions of other GHG like CH4
and N2O)
Refers to the source of the embodied energy/carbon
associated with raw material extraction and
procurement data. This data may be sourced from:
Material supplier
Source of Data Primary
Estimated from machine readings
Contractor/Designer
EPD
Company Annual Reports
Sustainable Materials
Derived data - refers to data that has been derived using
some kind of conversion factors. For example, if
embodied energy is available in MJ/cum and the density
is available, then it can be used to derive embodied
energy in MJ/kg
Data Type Calculated data - refers to the data which is
calculated/estimated through indirect means. For
example, if the total weight of coal used is not available,
but the generator capacity and the amount of time for
which the generator was running, and in how much time
does the generator exhaust all the coal is available. Then,
the amount of coal used can be calculated by multiplying
the time taken for all the coal to be exhausted and the
generator capacity, and dividing it by the time for which
the generator was running.
Please Note: In the A1_Extraction and Procurement sheet -
a) if embodied energy/carbon data at the process-level granularity is available,
then the data must be entered in columns C through U
b) if the combined embodied energy/carbon data of extraction and procurement is
available, then data must be entered in columns V to AC
Refers to the Manufacturer/Supplier of the Construction
Supplier/Manufacturer
Materials
Process: Raw Material This refers to the processes involved in mining the Raw
Primary
Extraction Components of Construction Materials
Refers to the processes involved in Raw Component
procurement.
Sustainable Materials
Raw Material May add raw materials for each of the construction Primary
materials, and number them in the following format: 1.1,
1.2, etc. where 1 is the sr. no. of the Construction
Material.
Refers to the resultant embodied energy calculated by
Calculated: Embodied
summing the values mentioned for raw material
Energy
extraction and procurement
Refers to the resultant embodied carbon calculated by
Calculated: Embodied
summing the values mentioned for raw material Calculated
Carbon
extraction and procurement
Distance between
Indicates the distance between the raw material
Extraction Site and Calculated
extraction site and manufacturing plant
Manufacturing Plant
Yes/No type of question. In case more than one vehicles
Were more than one
were used, the vehicle capacity, fuel mix, total fuel used
vehicle involved in Primary
for each of the cases must be added in columns
transport
underneath 'Vehicle 1', 'Vehicle 2' etc.
Refers to the category of vehicle, i.e., Light Duty Vehicle
Vehicle Category (LDV), Medium Duty Vehicle (MDV), or Heavy-Duty Primary
Vehicle (HDV)
Vehicle Capacity
Indicates the vehicles's capacity in tonnes Primary
(Tonne)
Vehicle Used: Make Indicates the manufacturer of the vehicle used Primary
Vehicle Used: Model Indicates the product/model of vehicle used Primary
This shall be calculated on the basis of total material
A2_Transport No. of trips required divided by the distance between the raw Primary
material extraction point and manufacturing plant
Indicates the fuel used for transportation. Data shall be
chosen from the following drop-down options:
Fuel Mix Petrol Calculated
Diesel
Coal
Total Fuel Used Indicates the total fuel consumed Primary
Refers to the measurement unit used to express the used
Unit (Fuel Use) Primary
fuel. For example, litres of petrol, MT of coal etc.
Refers to the alphabetic categorization assigned to
various production methods/technolologies available for
Sub-level Primary
Construction Materials.
Sustainable Materials
This is our nomenclature or identification given to the
Nomenclature Primary
building, in the format Airport Code_S1_B1.
Annual Electricity
This is the sum of electricity consumed across the year in
Consumption (unit: Primary
kWh (of the building)
Building ELE_CON kWh)
Year of data Indicates the year for which electricity data is presented Primary
This is the electricity consumed across two consecutive
Bimonthly Electricity
months in kWh (of the building). This data may be Primary
Consumption
entered in the respective month's column.
Address Column where the Building address must be entered Primary
Prominent
Primary
Manufacturer
Building Drawings
BoQ data source
Nomenclature
Built up Area
Built up Area
Longitude
Available
Available
Latitude
building
Address
(sq. m)
(sq. m)
Source
Sr. No.
Concret Concrete (M25) CONCRETE (includes concrete for slabs, columns, beams, staircases, roofs) Material
e (M30)
cum Unit
Qty(a)
Unit
Qty(b)
Functional Unit
(kg)
Qty(c)
Qty(a)
S2_B1
Raw Components
Unit
Qty(b)
Functional Unit
(kg)
b
Qty(a)
S3
Raw Components
Unit
Functional Unit
(kg)
Qty(c)
Qty(a)
S4
Raw Components
Unit
Qty(b)
Functional Unit
(kg)
Qty(c)
Qty(a)
Raw Components S5
Unit
Qty(b)
Functional Unit
(kg)
Qty(c)
164
Sustainable Materials
3.03.02 3.03.01 3.03 3.02 3.01 3 2.01 2
Block Masonry (Concrete Block Masonry (AAC Blocks) Brick Masonry (Burnt Clay Bricks) Walling Materials Mild Steel (used as reinforcement in RCC) STEEL
Blocks)
kg kg kg
Block Masonry (Concrete Block Masonry (AAC Blocks) Brick Masonry (Burnt Clay Bricks) Walling Materials Mild Steel (used as reinforcement in RCC) STEEL
Blocks)
kg kg kg
Block Masonry (Concrete Block Masonry (AAC Blocks) Brick Masonry (Burnt Clay Bricks) Walling Materials Mild Steel (used as reinforcement in RCC) STEEL
Blocks)
Block Masonry (Concrete Block Masonry (AAC Blocks) Brick Masonry (Burnt Clay Bricks) Walling Materials Mild Steel (used as reinforcement in RCC) STEEL
Blocks)
kg kg kg
Block Masonry (Concrete Block Masonry (AAC Blocks) Brick Masonry (Burnt Clay Bricks) Walling Materials Mild Steel (used as reinforcement in RCC) STEEL
Blocks)
kg kg kg
165
Sustainable Materials
4.02 4.01 4 3.04.05 3.04.04 3.04.03 3.04.02 3.04.01 3.04 3.03.03
Galvanized Iron Wires (for reinforcement) Aggregate Sand Cement EPS (mention thk) Thermoinsulated Concrete Block (200 mm thk)
kg kg kg kg kg kg
Galvanized Iron Wires (for reinforcement) Aggregate Sand Cement EPS (mention thk) Thermoinsulated Concrete Block (200 mm thk)
kg kg kg kg kg kg
Galvanized Iron Wires (for reinforcement) Aggregate Sand Cement EPS (mention thk) Thermoinsulated Concrete Block (200 mm thk)
Galvanized Iron Wires (for reinforcement) Aggregate Sand Cement EPS (mention thk) Thermoinsulated Concrete Block (200 mm thk)
kg kg kg kg kg kg
Galvanized Iron Wires (for reinforcement) Aggregate Sand Cement EPS (mention thk) Thermoinsulated Concrete Block (200 mm thk)
kg kg kg kg kg kg
166
Sustainable Materials
7.02 7.01 7 6.03 6.02 6.01 6 5 4.03
Steel frame casement UPVC windows Windows Wooden door Steel Jali door (for security) UPVC door (we are not counting hinges or any accessories) Doors Paint Ceiling Plaster
windows
Sr. No.
nos nos nos
1 1 1
kg kg
Steel frame casement UPVC windows Windows Wooden door Steel Jali door UPVC door (we are not counting hinges or any accessories) Doors Paint Ceiling Plaster
windows
nos nos nos
1
1 1 1
kg
2
kg kg
3
Steel frame casement UPVC windows Windows Wooden door Steel Jali door UPVC door (we are not counting hinges or any accessories) Doors Paint Ceiling Plaster
windows
nos nos nos
4
1 1 1
5
kg
Steel frame casement UPVC windows Windows Wooden door Steel Jali door UPVC door (we are not counting hinges or any accessories) Doors Paint Ceiling Plaster
windows
7
nos nos nos
8
Cold-rolled steel UPVC
kg
kg kg
9
Steel frame casement UPVC windows Windows Wooden door Steel Jali door UPVC door (we are not counting hinges or any accessories) Doors Paint Ceiling Plaster
10
windows
nos nos nos
1 1 1
kg
11
kg kg
12
167
Sustainable Materials
Thermoinsulated Concrete
Bonding Agent/Polymer
(used for AAC block
Sustainable Materials
Burnt Clay Bricks
Galvanised Iron
reinforcement)
Construction Materials
Aggregate
masonry)
Cement
Blocks
UPVC
Glass
Sand
EPS
Supplier/Manufacturer
Processes involved in
Raw Material Extraction
and Procurement
Raw Material
Qty of Raw Material
Extracted and Procured
Unit (RM)
Reference Qty of finished
construction material
Unit (FCM)
Fuel Mix
Embodied
Energy
Unit (EE)
Process:
Raw Embodied
Material Carbon
Extraction Unit (EC)
(A1.1)
Source of
Data
Data Type
Fuel Mix
Embodied
Energy
Unit (EE)
Process:
Raw Embodied
Material Carbon
Procurement Unit (EC)
(A1.2)
Source of
Data
Data Type
Sustainable Materials
(A1)
Unit (EE)
Total
Calculated Embodied
Carbon
Unit (EC)
Supplier/Manufacturer
Processes involved in
Raw Material Extraction
and Procurement
Raw Material
Qty of Raw Material
Extracted and Procured
Unit (RM)
Qty of finished
construction material for
which data is available
Unit (FCM)
Fuel Mix
Embodied
Energy
Processes: Unit (EE)
Raw Embodied
Material Carbon
Extraction
and Unit (EC)
Procurement Source of
Data
Data Type
Sr. No. 1 2 3 4 5 6 7 8 9 10 11 12
Sustainable Materials
Burnt Clay Bricks
Construction
Galvanised Iron
reinforcement)
Mild Steel (for
Materials
AAC Blocks
Aggregate
masonry)
Cement
Blocks
UPVC
Glass
Sand
EPS
Reference Qty
of final
Construction
Material for
which data is
collected
Unit (FCM)
Raw Materials
Qty of Raw
Material (1)
Unit (RM)
Distance
between
Extraction Site
and
Manufacturing
Plant (km)
Sustainable Materials
transport
used?
Source of Data
Data Type
Vehicle
Category
Vehicle
Capacity
(tonnes)
Vehicle Used:
Make
Vehicle Used:
Model
Vehicle
1 No. of trips
Fuel Mix
Total Fuel
Used
Embodied
Carbon
Unit (EC)
Vehicle
Category
Vehicle
Vehicle Capacity
2 (tonnes)
Vehicle Used:
Make
Sustainable Materials
No. of trips
Fuel Mix
Total Fuel
Used
Embodied
Carbon
Unit (EC)
Vehicle
Category
Vehicle
Capacity
(tonnes)
Vehicle Used:
Make
Vehicle Used:
Model
Vehicle
3 No. of trips
Fuel Mix
Total Fuel
Used
Embodied
Carbon
Unit (EC)
Vehicle Vehicle
4 Category
Sustainable Materials
Vehicle Used:
Make
Vehicle Used:
Model
No. of trips
Fuel Mix
Total Fuel
Used
Embodied
Carbon
Unit (EC)
Vehicle
Category
Vehicle
Capacity
(tonnes)
Vehicle Used:
Make
Vehicle Used:
Vehicle Model
5
No. of trips
Fuel Mix
Total Fuel
Used
Sub-level
Unit (EC)
Data Type
Unit (FCM)
Embodied
Manufacturer
Source of Data
Raw Components
Fuel Mix
fuel used
amount of
Variation in Method/Technology
1
AAC Blocks
2
Aggregate
3
b
Dry Process
6
EPS
7
Galvanised Iron
8
Glass
9
Thermoinsulated Concrete
Blocks
2
1
UPVC
174
Sustainable Materials
d Energy
Embodie
Sr. No.
A2
A1
Material
Material
Sub-level
Data Type
Unit (FCM)
Variation in
Manufacturer
Source of Data
Reference Qty of
final Construction
Method/Technology
Use)
Energy
Carbon
1
AAC Blocks
Unit (EE)
Unit (EC)
Unit (Fuel
Embodied
Embodied
2
Aggregate
Zig-Zag Kiln b
Down-Draught Kiln d
Dry Process b
Table A6.10: Sum of A1 to A3
EPS
6
Galvanised Iron
7
Glass
8
Furnace (BAF)
Electric Arc Furnace (EAF) b
Sand
10
UPVC
12
175
Sustainable Materials
A3
Sum of
A1 to A3
Sustainable Materials
Unit (EE)
A1
A2
Embodie A3
d Carbon Sum of
A1 to A3
Unit (EC)
Manufacturer
Source of Data
Data Age
Data Type
Reference Qty of
final Construction
Material
Unit (FCM)
Embodie
Combine
d Energy
d values
for unit Unit (EE)
processe Embodie
s A1 to d Carbon
A3
Unit (EC)
Bill of
Sustainable Materials
Quantit
Yes - Fully Yes - Partly
y (BoQ) Not Available
Available Available
Availab
le
BoQ Tender
Material Contractor/Desig Governm Architectural
data Owner Documen
Supplier ner ent DPR Drawings
source t
Make
and
Model Yes - Fully Yes - Partly
Not Available
Details Available Available
Availab
le
Make
and Tender
Material Contractor/Desig Governm Architectural
Model Owner Documen
Supplier ner ent DPR Drawings
Data t
Source
Buildin
Yes - Fully Yes - Partly
g Not Available
Available Available
Layout
Fuel Pe Di
Solar Wind Hydro
Mix Electricity Coal tro es
Energy Energy Energy
(A1) l el
Unit
MJ kWh
(EE)
Unit
kg CO2 kg CO2e
(EC)
Source Supplier/Ma Estimated from Contractor Company Sustainability
EPD
of Data nufacturer machine readings /Designer Report
Data
Measured Calculated Derived
Type
Unit
MT kg cum nos.
(RM)
Unit
MT kg cum nos.
(FCM)
Were
more
than
one Yes No
mode
of
transpo
Sustainable Materials
Vehicle
Categor LDV MDV HDV
y
Fuel
Petrol Diesel Coal
Mix
Unit
(Fuel Litres kg MT
Use)
Source Supplier/Ma Estimated from Contractor Company Sustainability
EPD
of Data nufacturer machine readings /Designer Report
Ju
Nov
Aug
Dec
Sep
Oct
Month Jan Feb Mar Apr May Jul
n
A7.2 Voltage Distortion a) Daily 99th percentile very short time (3s)
values shall be less than 1.5 times the values
At the main metering level of the building, utilities
given in table A7.1
and/or distribution system operators shall limit
line-to-neutral voltage harmonics as follows: b) Weekly 95th percentile short time (10 min)
values shall be less than the values given in table
A7.1
Table A7.1 – Voltage Distortion Limits
Technology
Implemented
Description Design Actual Design Actual to meet the Remarks
ECSBC
compliance
Total Total
Individual Individual
Bus voltage harmonic harmonic
harmonic harmonic
V at PCC distortion distortion
(%) h ≤ 50 (%) h ≤ 50
THD (%) THD (%)
V ≤ 1.0 kV 5 8
1 kV < V ≤
3 5
69 kV
69 kV < V ≤
1.5 2.5
161 kV
161 kV < V 1 1.5*
Note: High-voltage systems are allowed to have The limits in this sub clause shall be applicable to
up to 2.0% THD where the cause is an HVDC users connected to systems with the rated voltage
terminal whose effects are found to be at the PCC is from 120 V to above 161 kV. For
attenuated at points in the network where future individual nonlinear load, these limits are not
users may be connected. applicable. At the PCC (Point of Common
Coupling), users shall limit their harmonic
A7.3 Current Distortion
currents as specified.:
b) Weekly 99th percentile short time (10 min) Maximum allowable limit of current distortion for
harmonic currents shall be less than 1.5 times the system design shall comply to Table A7.2
value given in Tables A7.2, Table A7.3 and Table
A7.4
Table A7.2Current distortion limits for systems rated 120V through 69kV
ed
Implement
Tech.
Remarks
Descriptio
Design
Design
Design
Design
Design
Design
Actual
Actual
Actual
Actual
Actual
Actual
n
ISC/IL
2≤ h<11a
2≤ h<11a
11≤ h<17
11≤ h<17
17≤ h<23
17≤ h<23
23≤ h<35
23≤ h<35
35≤ h≤50
35≤ h≤50
TDD
TDD
<20C 4.0 2.0 1.5 0.6 0.3 5.0
20<50 7.0 3.5 2.5 1.0 0.5 8.0
50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<1000 12.0 5.5 5.0 2.0 1.0 15.0
>1000 15.0 7.0 6.0 2.5 1.4 20.0
a For h≤6 even harmonics are limited to 50% of ISC/IL unless covered by other standards with
the harmonic limits shown in the table. applicable scope.
Table A7.3: Current distortion limits for systems rated above 69 kV through 161kV
Remarks
Descriptio
Design
Design
Design
Design
Design
Design
Actual
Actual
Actual
Actual
Actual
Actual
n
ISC/IL
2≤ h<11a
2≤ h<11a
11≤ h<17
11≤ h<17
17≤ h<23
17≤ h<23
23≤ h<35
23≤ h<35
35≤ h≤50
35≤ h≤50
TDD
TDD
<20C 2.0 1.00 0.75 0.30 0.15 2.50
20<50 3.5 1.75 1.25 0.50 0.25 4.00
50<100 5.0 2.25 2.00 0.75 0.35 6.00
100<1000 6.0 2.75 2.50 1.00 0.50 7.50
>1000 7.5 3.50 3.00 1.25 0.70 10.00
a For h≤6 even harmonics are limited to 50% of ISC/IL unless covered by other standards with
the harmonic limits shown in the table. applicable scope.
Table A7.4- Current distortion limits for systems rated > 161 kV
Remarks
Descriptio
Design
Design
Design
Design
Design
Design
Actual
Actual
Actual
Actual
Actual
n
ISC/IL
2≤ h<11a
2≤ h<11a
11≤ h<17
11≤ h<17
17≤ h<23
17≤ h<23
23≤ h<35
23≤ h<35
35≤ h≤50
35≤ h≤50
TDD
TDD