E 8384 Yen
E 8384 Yen
E 8384 Yen
! NOTICE
Installation, start-up and on-site operation of the positioner are described in the Mounting
and Operating Instructions u EB 8384-5.
! DANGER ! NOTICE
Hazardous situations which, if not avoided, Property damage message or malfunction
will result in death or serious injury
Note
! WARNING Additional information
Hazardous situations which, if not avoided,
could result in death or serious injury
Tip
Recommended action
2 KH 8384-5 EN
Contents
1 Introduction...................................................................................................8
2 Design and principle of operation...................................................................9
2.1 Application type...........................................................................................10
2.2 Additional equipment....................................................................................11
2.3 Configuration using TROVIS-VIEW.................................................................12
2.4 Communication............................................................................................12
3 FOUNDATION™ fieldbus block model...........................................................12
4 Initialization and zero calibration of the positioner........................................13
5 Resetting the positioner................................................................................14
6 Status classification and condensed state.......................................................15
7 Block model.................................................................................................15
7.1 Resource Block (RES).....................................................................................15
7.2 Transducer Blocks..........................................................................................16
7.3 Advanced Positioner Transducer Block (AO TRD).............................................17
7.4 Function blocks.............................................................................................18
7.4.1 Analog Output Function Block (AO FB)...........................................................18
7.4.2 Proportional Integral Derivative Function Block (PID)........................................22
7.4.3 Discrete Input Function Block (DI1 FB + DI2 FB)................................................24
8 Other parameters.........................................................................................26
8.1 Link Objects.................................................................................................26
8.2 LAS Functionality..........................................................................................26
9 Parameter lists.............................................................................................27
9.1 Resource Block (RES).....................................................................................28
9.2 Advanced Positioner Transducer Block (AO TRD).............................................43
9.3 Analog Output Function Block (AO FB)...........................................................83
9.4 Analog Input Function Block (AI FB)................................................................91
9.5 Proportional Integral Derivative Function Block (PID)........................................99
9.6 Discrete Output Function Block (DO FB)........................................................115
9.7 Discrete Input Function Block (DI1 FB + DI2 FB)..............................................121
KH 8384-5 EN 3
Firmware revisions (Communication K)
K 1.21
• "Device not initialized" diagnostic alarm: the diagnostic alarm “Device not initialized” is
generated when the positioner is not initialized and the condensed state is set to “Maintenance
alarm”.
• Leakage sensor at binary input 2: The connection of a leakage sensor at binary input 2 (by
selecting LEAKAGE SENSOR in CONFIG_BINARY_INPUT2 parameter of the AO Transducer
Block) causes:
• Information specified in XD_ERROR_EXT parameter in the AO Transducer Block and the
generation of a diagnostic alarm which is logged
• The state of the binary input is reported in BINARY_INPUT2 parameter in the AO Transducer
Block
The connection of a leakage sensor at binary input 2 (by selecting LEAKAGE SENSOR in
CONFIG_BINARY_INPUT2 parameter of the AO Transducer Block) causes:
• Information specified in XD_ERROR_EXT parameter in the AO Transducer Block and the
generation of a diagnostic alarm which is logged
• The state of the binary input is reported in BINARY_INPUT2 parameter in the AO Transducer
Block
• Display of the operating range FINAL_VALUE_RANGE: the correction of the operating range
FINAL_VALUE_RANGE over on-site operation of the positioner (Code 8/9) is also transferred
over fieldbus in firmware version K 1.21 and higher.
• De-energized internal solenoid valve: a masking allows to set whether a de-energized internal
solenoid valve generates an AO block error, resulting in a block alarm.
• SOLENOID_SELECT parameter: the SOLENOID_SELECT parameter in firmware K 1.21 and
higher allows to set whether a "Maintenance now" block error of the AO Transducer Block results
in an output error in the AO Function Block.
• TOT_VALVE_TRAV_LIM parameter: new range: 1000 to 990 000 000
K 1.22
• Operating range FINAL_VALUE_RANGE: the operating range FINAL_VALUE_RANGE of the AO
Transducer Block is compared on entering it with TRANSM_PIN_POS.
If the TRANSM_PIN_POS parameter is changed, the positioner checks whether the setting and
unit match the current operating range FINAL_VALUE_RANGE. If this is not the case, the FINAL_
VALUE_RANGE parameter is set to 0 to 100 %.
• VALVE_TYPE parameter: the parameter of the AO Transducer Block is set depending on the
selected PIN_POS. The last setting is kept when VALVE_TYPE is set to OFF.
• FINAL_VALUE parameter: the output value is scaled with FINAL_VALUE_ RANGE in firmware
K 1.22 and higher and not as previously with XD_SCALE.
• Display of O/S mode in AO Transducer Block: if the AO Transducer Block is set to O/S mode,
this is indicated in the positioner display by MAN/AUTO.
K 1.23
Internal revisions
4 KH 8384-5 EN
Firmware revisions (Communication K)
K 1.24
• BUS_ADDRESS parameter: the bus address has the default setting of 248.
• Device type: in the delivered state, the device is configured as a basic device.
K 1.25
Internal revisions
K 2.01
• Additional function blocks: 2x DO (Discrete Output), 1x IS (Input Selector), 1x MAI (Multiple
Analog Input), 1x MAO (Multiple Analog Output).
• New functions: the following new functions are implemented in the DO Function Block (Discrete
Output):
• Discrete analysis of on/off valves
• Start partial stroke test (PST)
• Start and reset the data logger
• Resetting the diagnosis
• Stop diagnosis
• Move to fail-safe position
• Lock on-site operation
• Action on fault detection: If the AO Transducer Block is in O/S mode and the condensed state
changes to "Maintenance alarm", the following actions can be started:
• Hold last value
• Move valve to fail-safe position
• Move to a predefined fault state value
K 2.02
Partial stroke test (PST): configuration of the partial stroke test (PST) over the FF parameters is no
longer possible. Configuration over the TROVIS-VIEW software is still possible.
K 2.03
Partial stroke test (PST): configuration of the partial stroke test (PST) over the FF parameters is no
longer possible. Configuration over the TROVIS-VIEW software is still possible. The partial stroke test
can be started over the binary input BI2.
K 2.04
Internal revisions
K 2.05
Internal revisions
K 2.06
Process control system: new firmware compatible with Honeywell Experion® control system.
Communication: improved communication of valve positions smaller than –0.9 %.
K 2.07
Testing device functioning: monitoring of internal device communication has been added to the cyclic
testing of the device functions.
KH 8384-5 EN 5
Firmware revisions (Communication K)
K 2.08
Internal communication interface redesigned: the permissible clock frequency of communication calls
between the internal device controllers has been optimized.
K 3.01
• Certified according to ITK 6.2.0
• Diagnostics specification according to FF-912
• Function block added: AI (Analog Input)
• Function blocks removed: MAI (Multiple Analog Input), MAO (Multiple Analog Output), IS (Input
Selector)
K 3.05
Internal communication interface redesigned: the permissible clock frequency of communication calls
between the internal device controllers has been optimized.
K 3.06
Fail-safe position reliably maintained even when the positioner is not connected to the process control
system.
6 KH 8384-5 EN
KH 8384-5 EN 7
Introduction
1 Introduction
This document is based upon:
− Fieldbus FOUNDATION™ Specification "Function Block Application Process Part 1 – 3"
Revision 1.7 (FF-890 to FF-892)
− Fieldbus FOUNDATION™ Specification "Positioner Transducer Block" Revision 3.0 (FF-906)
8 KH 8384-5 EN
Design and principle of operation
KH 8384-5 EN 9
Design and principle of operation
The positioner communicates and is powered using IEC 61158-2 transmission technology
conforming to FOUNDATION™ fieldbus specification.
As a standard feature, the positioner comes with a binary input used to signalize process in-
formation over the FOUNDATION™ fieldbus network.
The extended EXPERTplus diagnostics are integrated into the positioner. They provide infor-
mation on the positioner and generate diagnostic and status messages, which allow faults to
be pinpointed quickly.
AUTO mode The positioner uses the set point to Discrete analysis of the set point The
position the valve. The valve position valve position (current position) in %
(current position) appears in % on the and O/C (Open/Close) appear in
display. alternating sequence on the display.
MAN mode The positioner follows the set point given over local operation.
Note
− Depending on the application type, certain diagnostic functions cannot be performed or
analyzed (u EB 8389 on EXPERTplus valve diagnostics).
− In manual mode, an on/off valve can be moved past 100 % of the nominal range (with the
closed position for AIR TO OPEN) or below 0 % of the nominal range (with the closed posi-
tion for AIR TO CLOSE).
10 KH 8384-5 EN
Design and principle of operation
! NOTICE
The manual set point is also reset to 0 % after the solenoid valve is activated!
A different manual set point must be entered again (Code 1).
In this version, the rotary shaft of the positioner carries an adjustable tag which actuates the
built-in proximity switch.
Leakage sensor
By upgrading the positioner with a leakage sensor, it is possible to detect seat leakage when
the valve is in the closed position.
Binary inputs
Binary input BI1 (14)
As a standard feature, the positioner comes with a binary input used to signalize process in-
formation over the FOUNDATION™ fieldbus network.
Binary input BI2 (15)
This binary input BI2 is optional. It is an active input which is powered by the positioner to
connect a floating contact. The switching state of the floating contact can be indicated over
the FOUNDATION™ fieldbus network.
Note
The binary inputs are configured in the DI Function Blocks.
KH 8384-5 EN 11
FOUNDATION™ fieldbus block model
2.4 Communication
The positioner is controlled completely by digital signal transmission according to
FOUNDATION™ fieldbus specification.
Data are transmitted over the bus using digital, bit-synchronous Manchester coding at a
Baud rate of 31.25 kbit/s over twisted-pair wires according to IEC 61158-2.
Note
If complex functions are started in the positioner, which require a long calculation time or
lead to a large quantity of data being saved in the volatile memory of the positioner, the alert
'busy' is issued over the DD. This alert is not an error message and can be simply confirmed.
12 KH 8384-5 EN
Initialization and zero calibration of the positioner
KH 8384-5 EN 13
Resetting the positioner
Note
Read the corresponding section on starting up the positioner in the Mounting and Operating
Instructions u EB 8384-5.
14 KH 8384-5 EN
Status classification and condensed state
7 Block model
Several parameters can only be changed in certain modes (see Read/write capability in the
parameter description). In this case, not the actual mode is decisive, but the target mode.
KH 8384-5 EN 15
Block model
Note
All time specifications in the Resource Block are specified in the unit of 1/32 ms according to
the FOUNDATION™ fieldbus Specification Version 1.7.
In the Device Description Library supplied by Fieldbus FOUNDATION™ upon which the device
description of Type 3730-5 is also based, these parameters are incorrectly specified as the
unit of ms. The specified values supplied by the device are, however, always to be interpreted
as the unit of 1/32 ms.
The Transducer Blocks DI TRD and DO TRD are implemented according to the
FOUNDATION™ fieldbus specification and do not contain any manufacturer-specific
parameters.
16 KH 8384-5 EN
Block model
KH 8384-5 EN 17
Block model
Control valve
FINAL_VALUE Set point of upstream AO Function Block (control valve)
FINAL_POS_VALUE Valve position after rescaling
WORKING_SP Set point after scaling, characterization, end position function
(corresponds to the controlled variable of the control algorithm)
WORKING_POS Actual valve position
READBACK_SELECT Select parameter which is issued to READBACK of the AO Function
Block
On/off valve
FINAL_VALUE_D Discrete set point of upstream DO Function Block
FINAL_POS_VALUE_D Discrete valve position after taking the direction of action into account
WORKING_SP_D Set point after taking the direction of action into account (corresponds
to the set point of the control algorithm)
WORKING_POS_D Actual discrete valve position
18 KH 8384-5 EN
AO FB
MODE Scaling Characteristic
KH 8384-5 EN
CAS_IN MODE=AUTO FINAL_VALUE SIGNAL_ACTION
Control valve FVR End position function
READBACK
SetFailSafePos
DO FB
OUT_D MODE=AUTO MODE FINAL_VALUE_D SIGNAL_ACTION
Open/close (on/off)
DI FB
WORKING_SP_D WORKING_SP
OUT_D
RB_SELECT
Characteristic
FINAL_POS_VALUE End position function SIGNAL_ACTION
19
Block model
Block model
20 KH 8384-5 EN
Block model
XD_SCALE
100 %
READBACK
OUT
0% PV_SCALE
0 ˚C
SP PV
SP_LO_LIM<=SP<=SP_HI_LIM
RCAS_IN
MODE_BLK OUT
MODE_BLK
PV, XD scaling PV (manual)
READBACK XD_SCALE, PV_SCALE
KH 8384-5 EN 21
Block model
22 KH 8384-5 EN
Block model
− Derivative component:
In controlled systems with long delay times, e.g. in temperature control loops, it is better
to use the derivative component RATE of the controller. Using the derivative component
RATE, the output variable is calculated depending on the rate of change of the set point
deviation.
An OUT value is generated from the calculated ouput value based on the OUT_SCALE,
OUT_HI_LIM and OUT_LO_LIM parameters. It can be forwarded to a downstream function
block.
The status of the OUT value can be influenced by the STATUS_OPTS parameter depending
on the status of the input variables of the PID Function Block. As a result, the fault state of a
following output block can be activated, for example.
The BYPASS parameter allows the internal set point to pass directly through to the output val-
ue. The FF_VAL input value allows feedforward control, while TRK_IN_D and TRK_VAL allow
the direct tracking of the out value.
Fault State
MODE_BLK SELECT_DO1
FSTATE_TIME
FSTATE_VALVUE_D
SP_D
CAS_IN_D IO_OPTS
RCAS_IN_D OUT_D Open/close application 1)
Inverted
MAN Start VST (Valve Stroke Test)
Reset diagnosis
Reset/stop diagnosis
IO_OPTS
1)
Only supports DO1 Function
PV_D READBACK_D
Inverted Block
KH 8384-5 EN 23
Block model
24 KH 8384-5 EN
Block model
SELECT_DI1...2
PV_D
Bin2
Simulate Optional Filter
MGV CHANNEL
SIMULATE_D Invert PV_FTIME
POS_D Output Out_D
FIELD_VAL_D
Condensed State
MODE Alarms
DISC
AO Transducer
BINARY_INPUT_2
CONFIG_BINARY_INPUT_2
KH 8384-5 EN 25
Other parameters
8 Other parameters
The Stale Counter serves to judge the "quality" of a process variable received over a config-
ured cyclic connection (publisher/subscriber connection).
These connections are used to transfer the process variable linked amongst the various func-
tion blocks. For this purpose, the upstream block (publisher) sends the process variable over
the bus at scheduled times. The downstream block(s) (subscriber) responds at the scheduled
times. The blocks that are to receive data monitor whether a valid value exists at the sched-
uled time. A value is valid if it exists with the status "Good" at the scheduled time.
The Stale Counter defines how many "Bad" (stale) values can be accepted in sequence be-
fore the Fault State of the block is activated.
This monitoring function is deactivated by setting the Stale Counter to zero.
26 KH 8384-5 EN
Parameter lists
9 Parameter lists
Legend
The parameter index is listed in brackets following the parameter name in the following ta-
bles.
ALL O/M/A/CAS/RCAS
NA Not analyzed
Note
Values/settings in square brackets [ ] are default settings.Resource Block (RES)
KH 8384-5 EN 27
Parameter lists
28 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 29
Parameter lists
30 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 31
Parameter lists
32 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 33
Parameter lists
34 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 35
Parameter lists
36 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 37
Parameter lists
• [COND.STATE + VST] · Current condensed state and start of the VST (Valve Stroke Test).
See setting in VST_MODE parameter in the AO TRD Block.
SELECT_DO_1 · Purpose of the DO1 Function Block
Note: For firmware K 3.05 and higher, read the footnote 1) at the end of the parameter
description.
• DO1 O/C · On/off service
• [VST] · Start of the VST (Valve Stroke Test). See setting in VST_MODE parameter in the AO
TRD Block.
• RESET DIAG · Reset diagnosis (resetting of statistical information and tests, the
classification of status messages and logging remain saved)
• RESET LOGGER · Reset logging
• F.-SAFE · Move to fail-safe position
• DLOG · Data logger (0 Start; 1 Stop)
• LOG WRITE PR · Lock on-site operation (LOCAL_OP_ENA)
• DIAGNOSIS · Reset/stop diagnosis
1 Reset diagnosis
2 Reset logging
3 Stop diagnosis
4 Enable/start diagnosis
SELECT_DO_2 · Purpose of the DO2 Function Block
Note: For firmware K 3.05 and higher, read the footnote 1) at the end of the parameter
description.
• VST · Start of the VST (Valve Stroke Test). See setting in VST_MODE parameter in the AO
TRD Block.
• RESET DIAG · Reset diagnosis (resetting of statistical information and tests, the
classification of status messages and logging remain saved)
• RESET LOGGER · Reset logging
• [F.-SAFE] · Move to fail-safe position
• DLOG · Data logger (0 Start; 1 Stop)
• LOG WRITE PR · Lock on-site operation (LOCAL_OP_ENA)
• DIAGNOSIS · Reset/stop diagnosis
1 Reset diagnosis
2 Reset logging
3 Stop diagnosis
4 Enable/start diagnosis
38 KH 8384-5 EN
Parameter lists
1) The following applies to the configuration of the DO1 and DO2 Transducer Blocks:
• Both DO1 and DO2 Transducer Blocks must be set to the O/S mode.
• The fail-safe position must not be active.
• The two transducer blocks must have different configurations in SELECT_DO_1 and
SELECT_DO_2.
RES: SET_FSTATE (29)
Storage class D; read/write capability r/w; supported modes O/A
Activation of the fault state in the AO Function Block
RES: SHED_RCAS (26)
Storage class S; read/write capability r/w; supported modes O/A
Monitoring time to check connection between fieldbus host system and PID Function Block in
RCAS mode
When the monitoring time has elapsed, the PID Function Block switches from RCAS to the
mode selected in the SHED_OPT parameter.
• [640000 · ms]
RES: SHED_ROUT (27)
Storage class S; read/write capability r/w; supported modes O/A
Monitoring time to check connection between fieldbus host system and PID Function Block in
ROUT mode
When the monitoring time has elapsed, the PID Function Block switches from ROUT to the
mode selected in the SHED_OPT parameter.
• [640000 · ms]
RES: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes O/A
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each block.
Note: These data are neither checked nor processed by the Resource Block.
RES: ST_REV (1)
Storage class N; read capability r
Static revision number
Note: The revision number is incremented with each change of a static parameter in the
block.
KH 8384-5 EN 39
Parameter lists
40 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 41
Parameter lists
42 KH 8384-5 EN
Parameter lists
Index Parameters
60 FD_OFFSPEC_PRI
61 FD_MAINT_PRO
62 FD_CHECK_PRI
63 FD_SIMULATE
64 FD_RECOMMEN_ACT
65 FIRMWARE_REVISION
66 HW_REVISION
67 DEVICE_SER_NUM
68 DEVICE_CERTIFICATION
69 DESCRIPTOR
70 DEVICE_MESSAGE
71 DEVICE_PRODUCT_NUM
72 TEXT_INPUT_1
73 TEXT_INPUT_2
74 TEXT_INPUT_3
75 TEXT_INPUT_4
76 TEXT_INPUT_5
77 READING_DIRECTION
78 BUS_ADDRESS
79 LOCAL_OP_ENA
80 SELECT_USAGE_IO
81 CONDENSED_STATE
82 DIAG_CLS
84 ALL_ACTIVE_STATUS_MESSAGES
KH 8384-5 EN 43
Parameter lists
44 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 45
Parameter lists
46 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 47
Parameter lists
48 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 49
Parameter lists
50 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 51
Parameter lists
52 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 53
Parameter lists
54 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 55
Parameter lists
56 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 57
Parameter lists
58 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 59
Parameter lists
60 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 61
Parameter lists
62 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 63
Parameter lists
64 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 65
Parameter lists
66 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 67
Parameter lists
68 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 69
Parameter lists
70 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 71
Parameter lists
72 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 73
Parameter lists
74 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 75
Parameter lists
76 KH 8384-5 EN
Parameter lists
3 xd_error_ext_3
• Reset comm. controller
• Attachment unit disturbed
• Bin 2 deactivated
• Reset appl. controller
• FF parameter
• Mode unequal AUTO
• Temperature exceeding
14 Air Supply
15 Actuator Spring
16 Shifting Working Range
17 Friction
18 Leakage Pneumatic
19 Limit Working Range
20 Inner Leakage
21 External Leakage
22 Observing End Position
23 Connection Positioner Valve
24 Working Range
25 Temperature Error
26 PST/FST Status
27 Open Close Status
AO TRD: XD_FSTATE_OPT (32)
Storage class S; read/write capability r/w; supported modes O/M/A
Action on fault detection in AO TRD
• [Hold last value]
• Fail-safe position
• Fault state value (XD_FSTATE_VAL)
AO TRD: XD_FSTATE_VAL (31)
Storage class S; read/write capability r/w; supported modes O/M/A
Fault state value to which the valve moves when the AO Transducer Block is in the O/S
mode and the action on fault detection has been selected in the XD_OOS_OPTS
parameter.
• 0 … 100 %, [0 %]
KH 8384-5 EN 77
Parameter lists
78 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 79
Parameter lists
80 KH 8384-5 EN
Parameter lists
69 HYSTERESIS 24 POS_ALERT_HI
98 INTERNAL_TEMP_MAX 77 PST_BREAKOUT_TIME
97 INTERNAL_TEMP_MIN 78 PST_BREAKOUT_TIMEOUT
99 INTERNAL_TEMP_UNITS 85 PST_COMPLETION_TIMEOUT
KH 8384-5 EN 81
Parameter lists
82 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 83
Parameter lists
84 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 85
Parameter lists
• FAULT STATE TO VALUE · FSTATE_VAL is used as the set point when the failure action is
triggered (see FSTATE_VAL, FSTATE_TIME)
• USE FAULT STATE VALUE ON RESTART · FSTATE_VAL is used as the set point upon
restarting until a valid value has been entered.
• TARGET TO MAN IF FAULT STATE ACTIVATED · When failure action is triggered, the
target mode is set to MAN and the original target mode is lost. The block remains in
MAN mode after failure action has been left until the user sets it to the desired operating
mode.
• USE PV FOR BKCAL_OUT · The PV process value is fed back at BKCAL_OUT instead of
the working process value. If the OUT READBACK option is activated in the FEATURES_
SEL Resource Block parameter, BKCAL_OUT feeds back the current valve position.
AO FB: MODE_BLK (5)
Storage class N; read/write capability r/w; supported modes ALL
Operating mode
– Target Mode Code 48 A0
– Actual Mode (read only) Code 48 A1
– Permitted Mode
– Normal Mode (read only)
• O/S · The AO Function Block is not executed. The last value or the value determined
during an active fault processing is issued at the OUT parameter.
• MAN · The output value of the AO Function block can be entered manually by the
operator over the OUT parameter.
• AUTO · The set point entered by the operator is used over the SP parameter upon
execution of the AO Function Block.
• CAS · The AO Function Block receives the set point directly from an upstream function
block over the CAS_IN parameter for internal calculation of the out value. The AO
Function Block is implemented.
• RCAS · The AO Function Block receives the set point directly from the fieldbus host
system over the RCAS_IN parameter for internal calculation of the out value. The AO
Function Block is implemented.
AO FB: OUT (9)
Storage class N; read/write capability r/w; supported modes M/O
Out value of the AO Function Block (value, limit and status) Code 48 A6/7
• Range of OUT_SCALE ±10 %; unit of the XD_SCALE parameter group
Note: The OUT value can be entered manually when the MAN mode is selected in the
MODE_BLK parameter.
86 KH 8384-5 EN
Parameter lists
AO FB: PV (7)
Storage class D; read capability r
Process variable of the function block (value and status)
• Unit from the XD_SCALE parameter group.
Note: If the OUT READBACK option is activated in the FEATURES_SEL resource block
parameter, PV contains the current valve position (corresponding to FINAL_POSITION_
VALUE).
AO FB: PV_SCALE (11)
Storage class S; read/write capability r/w; supported modes O
Range of the process variable (PV) (start, end, unit and decimal point)
• 0 to 100 %
AO FB: RCAS_IN (26)
Storage class N; read/write capability r/w; supported modes ALL
Analog set point for internal calculation of the out value (value and status)
The RCAS_IN value is provided by the fieldbus host system.
Note: This parameter is only active in RCAS mode.
AO FB: RCAS_OUT (28)
Storage class D; read capability r
Analog set point after applying the ramp function (value and status)
The RCAS_OUT value is provided to the fieldbus host system to perform back-calculations
in case of control mode changes or limited signals.
Note: This parameter is only active in RCAS mode.
AO FB: READBACK (16)
Storage class D; read capability r
Current valve position determined from the FINAL_POSITION_VALUE of the associated
Transducer Block
• Unit from the XD_SCALE parameter group.
KH 8384-5 EN 87
Parameter lists
88 KH 8384-5 EN
Parameter lists
AO FB: SP (8)
Storage class N; read/write capability r/w; supported modes O/M/A
Set point w in AUTO mode Code 48 A4/5
• Value and range from PV_SCALE ±10 %; unit of PV_SCALE
AO FB: SP_HI_LIM (20)
Storage class S; read/write capability r/w; supported modes ALL
Upper set point limit
• Value and range from PV_SCALE ±10 %, [100 %]
Note: Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.
AO FB: SP_LO_LIM (21)
Storage class S; read/write capability r/w; supported modes ALL
Lower set point limit
• Value and range from PV_SCALE ±10 %, [0 %]
Note: Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.
AO FB: SP_RATE_DN (18)
Storage class S; read/write capability r/w; supported modes ALL
Set point downward rate limit in AUTO mode
• [3402823466 x 1038]
Note: If '0' is entered, the set point is used.
The speed limitation for output blocks is active in AUTO and CAS modes.
AO FB: SP_RATE_UP (19)
Storage class S; read/write capability r/w; supported modes ALL
Set point upward rate limit in AUTO mode
• [3402823466 x 1038]
Note: If '0' is entered, the set point is used.
The speed limitation for output blocks is active in AUTO and CAS modes.
AO FB: ST_REV (1)
Storage class N; read capability r
Static revision number (AO Function Block)
Note: The revision number is incremented with each change of a static parameter in the
block.
KH 8384-5 EN 89
Parameter lists
90 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 91
Parameter lists
92 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 93
Parameter lists
94 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 95
Parameter lists
96 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 97
Parameter lists
98 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 99
Parameter lists
100 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 101
Parameter lists
102 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 103
Parameter lists
104 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 105
Parameter lists
106 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 107
Parameter lists
108 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 109
Parameter lists
110 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 111
Parameter lists
112 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 113
Parameter lists
114 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 115
Parameter lists
116 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 117
Parameter lists
118 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 119
Parameter lists
120 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 121
Parameter lists
122 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 123
Parameter lists
124 KH 8384-5 EN
Parameter lists
KH 8384-5 EN 125
Parameter lists
126 KH 8384-5 EN
KH 8384-5 EN 127
KH 8384-5 EN
2023-05-03 · English