E 8384 Yen

Download as pdf or txt
Download as pdf or txt
You are on page 1of 128

KH 8384-5 EN

Translation of original instructions

Type 3730-5 Electropneumatic Positioner


Communication: FOUNDATION­­­­™ fieldbus

Firmware version K 3.0x

Edition October 2022


The mounting and operating instructions for the devices are included in
the scope of delivery. The latest documentation is available on our website
at www.samsongroup.com > Service & Support > Downloads >
Documentation.

! NOTICE
Installation, start-up and on-site operation of the positioner are described in the Mounting
and Operating Instructions u EB 8384-5.

Definition of signal words

! DANGER ! NOTICE
Hazardous situations which, if not avoided, Property damage message or malfunction
will result in death or serious injury

Note
! WARNING Additional information
Hazardous situations which, if not avoided,
could result in death or serious injury
Tip
Recommended action

2 KH 8384-5 EN
Contents

1 Introduction...................................................................................................8
2 Design and principle of operation...................................................................9
2.1 Application type...........................................................................................10
2.2 Additional equipment....................................................................................11
2.3 Configuration using TROVIS-VIEW.................................................................12
2.4 Communication............................................................................................12
3 FOUNDATION™ fieldbus block model...........................................................12
4 Initialization and zero calibration of the positioner........................................13
5 Resetting the positioner................................................................................14
6 Status classification and condensed state.......................................................15
7 Block model.................................................................................................15
7.1 Resource Block (RES).....................................................................................15
7.2 Transducer Blocks..........................................................................................16
7.3 Advanced Positioner Transducer Block (AO TRD).............................................17
7.4 Function blocks.............................................................................................18
7.4.1 Analog Output Function Block (AO FB)...........................................................18
7.4.2 Proportional Integral Derivative Function Block (PID)........................................22
7.4.3 Discrete Input Function Block (DI1 FB + DI2 FB)................................................24
8 Other parameters.........................................................................................26
8.1 Link Objects.................................................................................................26
8.2 LAS Functionality..........................................................................................26
9 Parameter lists.............................................................................................27
9.1 Resource Block (RES).....................................................................................28
9.2 Advanced Positioner Transducer Block (AO TRD).............................................43
9.3 Analog Output Function Block (AO FB)...........................................................83
9.4 Analog Input Function Block (AI FB)................................................................91
9.5 Proportional Integral Derivative Function Block (PID)........................................99
9.6 Discrete Output Function Block (DO FB)........................................................115
9.7 Discrete Input Function Block (DI1 FB + DI2 FB)..............................................121

KH 8384-5 EN 3
Firmware revisions (Communication K)
K 1.21
• "Device not initialized" diagnostic alarm: the diagnostic alarm “Device not initialized” is
generated when the positioner is not initialized and the condensed state is set to “Maintenance
alarm”.
• Leakage sensor at binary input 2: The connection of a leakage sensor at binary input 2 (by
selecting LEAKAGE SENSOR in CONFIG_BINARY_INPUT2 parameter of the AO Transducer
Block) causes:
• Information specified in XD_ERROR_EXT parameter in the AO Transducer Block and the
generation of a diagnostic alarm which is logged
• The state of the binary input is reported in BINARY_INPUT2 parameter in the AO Transducer
Block
The connection of a leakage sensor at binary input 2 (by selecting LEAKAGE SENSOR in
CONFIG_BINARY_INPUT2 parameter of the AO Transducer Block) causes:
• Information specified in XD_ERROR_EXT parameter in the AO Transducer Block and the
generation of a diagnostic alarm which is logged
• The state of the binary input is reported in BINARY_INPUT2 parameter in the AO Transducer
Block
• Display of the operating range FINAL_VALUE_RANGE: the correction of the operating range
FINAL_VALUE_RANGE over on-site operation of the positioner (Code 8/9) is also transferred
over fieldbus in firmware version K 1.21 and higher.
• De-energized internal solenoid valve: a masking allows to set whether a de-energized internal
solenoid valve generates an AO block error, resulting in a block alarm.
• SOLENOID_SELECT parameter: the SOLENOID_SELECT parameter in firmware K 1.21 and
higher allows to set whether a "Maintenance now" block error of the AO Transducer Block results
in an output error in the AO Function Block.
• TOT_VALVE_TRAV_LIM parameter: new range: 1000 to 990 000 000
K 1.22
• Operating range FINAL_VALUE_RANGE: the operating range FINAL_VALUE_RANGE of the AO
Transducer Block is compared on entering it with TRANSM_PIN_POS.
If the TRANSM_PIN_POS parameter is changed, the positioner checks whether the setting and
unit match the current operating range FINAL_VALUE_RANGE. If this is not the case, the FINAL_
VALUE_RANGE parameter is set to 0 to 100 %.
• VALVE_TYPE parameter: the parameter of the AO Transducer Block is set depending on the
selected PIN_POS. The last setting is kept when VALVE_TYPE is set to OFF.
• FINAL_VALUE parameter: the output value is scaled with FINAL_VALUE_ RANGE in firmware
K 1.22 and higher and not as previously with XD_SCALE.
• Display of O/S mode in AO Transducer Block: if the AO Transducer Block is set to O/S mode,
this is indicated in the positioner display by MAN/AUTO.
K 1.23
Internal revisions

4 KH 8384-5 EN
Firmware revisions (Communication K)
K 1.24
• BUS_ADDRESS parameter: the bus address has the default setting of 248.
• Device type: in the delivered state, the device is configured as a basic device.
K 1.25
Internal revisions
K 2.01
• Additional function blocks: 2x DO (Discrete Output), 1x IS (Input Selector), 1x MAI (Multiple
Analog Input), 1x MAO (Multiple Analog Output).
• New functions: the following new functions are implemented in the DO Function Block (Discrete
Output):
• Discrete analysis of on/off valves
• Start partial stroke test (PST)
• Start and reset the data logger
• Resetting the diagnosis
• Stop diagnosis
• Move to fail-safe position
• Lock on-site operation
• Action on fault detection: If the AO Transducer Block is in O/S mode and the condensed state
changes to "Maintenance alarm", the following actions can be started:
• Hold last value
• Move valve to fail-safe position
• Move to a predefined fault state value
K 2.02
Partial stroke test (PST): configuration of the partial stroke test (PST) over the FF parameters is no
longer possible. Configuration over the TROVIS-VIEW software is still possible.
K 2.03
Partial stroke test (PST): configuration of the partial stroke test (PST) over the FF parameters is no
longer possible. Configuration over the TROVIS-VIEW software is still possible. The partial stroke test
can be started over the binary input BI2.
K 2.04
Internal revisions
K 2.05
Internal revisions
K 2.06
Process control system: new firmware compatible with Honeywell Experion® control system.
Communication: improved communication of valve positions smaller than –0.9 %.
K 2.07
Testing device functioning: monitoring of internal device communication has been added to the cyclic
testing of the device functions.

KH 8384-5 EN 5
Firmware revisions (Communication K)
K 2.08
Internal communication interface redesigned: the permissible clock frequency of communication calls
between the internal device controllers has been optimized.
K 3.01
• Certified according to ITK 6.2.0
• Diagnostics specification according to FF-912
• Function block added: AI (Analog Input)
• Function blocks removed: MAI (Multiple Analog Input), MAO (Multiple Analog Output), IS (Input
Selector)
K 3.05
Internal communication interface redesigned: the permissible clock frequency of communication calls
between the internal device controllers has been optimized.
K 3.06
Fail-safe position reliably maintained even when the positioner is not connected to the process control
system.

6 KH 8384-5 EN
KH 8384-5 EN 7
Introduction

1 Introduction
This document is based upon:
− Fieldbus FOUNDATION™ Specification "Function Block Application Process Part 1 – 3"
Revision 1.7 (FF-890 to FF-892)
− Fieldbus FOUNDATION™ Specification "Positioner Transducer Block" Revision 3.0 (FF-906)

Type 3730-5 Positioner


The microprocessor-controlled positioner compares the set point cyclically transmitted over
the FOUNDATION™ fieldbus network to the travel or opening angle of the control valve and
issues a corresponding output signal pressure.
Special features:
− Link Master Capability
− Simple attachment to all common linear actuators with interface for SAMSON direct attach-
ment, NAMUR rib or valves with rod-type yokes according to IEC 60534-6-1 or to rotary
actuators according to VDI/VDE 3845
− Any desired mounting position of the positioner
− One-knob, menu-driven operation
− Automatic start-up
− LCD easy to read in any mounted position due to selectable reading direction
− Integrated EXPERTplus diagnostics suitable for throttling and on/off valves and with addi-
tional partial stroke test for valves in safety-instrumented systems
− Classified status messages acc. to NAMUR Recommendation NE 107
− Online changing of control parameters
− Automatic zero monitoring
− Calibrated travel sensor without gears susceptible to wear
− Permanent storage of parameters (protected against power failure)
− Adjustable output pressure limitation
− Activatable tight-closing function
− Binary input for DC voltage signals
− Certified according to IEC 61508/SIL

8 KH 8384-5 EN
Design and principle of operation

2 Design and principle of operation


The positioner is mounted on pneumatic control valves and is used to assign the valve posi-
tion (controlled variable x) to the control signal (set point w). The positioner compares the
control signal of a control system to the travel or rotational angle of the control valve and is-
sues a signal pressure (output variable y) for the pneumatic actuator.
The positioner mainly consists of an electric travel sensor system, an analog i/p converter
with a downstream air capacity booster and the electronics with the microcontroller.
When a set point deviation occurs, the actuator is either vented or filled with air. If neces-
sary, the signal pressure change can be slowed down by a volume restriction. The signal
pressure supplied to the actuator can be limited by software or on site to 1.4, 2.4 or 3.7 bar.
The fixed flow regulator ensures a constant air flow to the atmosphere, which is used to flush
the inside of the positioner housing and to optimize the air capacity booster. The i/p convert-
er is supplied with a constant upstream pressure by the pressure regulator to compensate for
any fluctuations in the supply pressure.

20 Serial 16 1 Control valve


Interface 2 Travel sensor
13 mm 3 PD controller
%
S 15 BE2 4 A/D converter
4 5 5 Microcontroller
19 BE1 6 i/p converter
14
7 Air capacity booster
8 Pressure regulator
w 9 Flow regulator
24V DC
PD 10 Volume restriction
x 2 11 11* Inductive limit contact
17 18 3
12* Solenoid valve
G G 13 IEC 61158-2 interface
12 module
14 Binary input BI1 (passive)
6
9 15* Binary input BI2 (active)
16 Display
17* Actuation of solenoid valve
8 1 18* Electrical insulation
y 19 D/A converter
Q 10 x
7 20 Communication interface
* Options

Fig. 1: Functional diagram

KH 8384-5 EN 9
Design and principle of operation

The positioner communicates and is powered using IEC 61158-2 transmission technology
conforming to FOUNDATION™ fieldbus specification.
As a standard feature, the positioner comes with a binary input used to signalize process in-
formation over the FOUNDATION™ fieldbus network.
The extended EXPERTplus diagnostics are integrated into the positioner. They provide infor-
mation on the positioner and generate diagnostic and status messages, which allow faults to
be pinpointed quickly.

2.1 Application type


The application types 'Control valve' and 'On/off valve' are available. The manual mode
(MAN) and the automatic mode (AUTO) can be selected with both application types.
Depending on the application type selected, the positioner responds differently in automatic
mode (AUTO) .
Control over FOUNDATION™ fieldbus is performed over the AO Function Block (control
valve) and over the DO1 Function Block (on/off valve). The application type can be entered
in the Resource Block over the SELECT_DO_1 parameter or at the positioner using Code
49 - h0.
Control valve Open/close (on/off) valve

AUTO mode The positioner uses the set point to Discrete analysis of the set point The
position the valve. The valve position valve position (current position) in %
(current position) appears in % on the and O/C (Open/Close) appear in
display. alternating sequence on the display.
MAN mode The positioner follows the set point given over local operation.

Note
− Depending on the application type, certain diagnostic functions cannot be performed or
analyzed (u EB 8389 on EXPERTplus valve diagnostics).
− In manual mode, an on/off valve can be moved past 100 % of the nominal range (with the
closed position for AIR TO OPEN) or below 0 % of the nominal range (with the closed posi-
tion for AIR TO CLOSE).

10 KH 8384-5 EN
Design and principle of operation

2.2 Additional equipment


Solenoid valve
If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p con-
verter is vented to the atmosphere. The positioner can no longer operate and the control
valve moves to the fail-safe position determined by the actuator, regardless of the set point.

! NOTICE
The manual set point is also reset to 0 % after the solenoid valve is activated!
A different manual set point must be entered again (Code 1).

Inductive limit contact

In this version, the rotary shaft of the positioner carries an adjustable tag which actuates the
built-in proximity switch.

External position sensor


In this version, only the sensor is mounted to the control valve. The positioner is located sepa-
rately from the valve. The connection of x and y signals to the valve is established by cable
and piping for air (only without inductive limit contact).

Leakage sensor
By upgrading the positioner with a leakage sensor, it is possible to detect seat leakage when
the valve is in the closed position.

Binary inputs
Binary input BI1 (14)
As a standard feature, the positioner comes with a binary input used to signalize process in-
formation over the FOUNDATION™ fieldbus network.
Binary input BI2 (15)
This binary input BI2 is optional. It is an active input which is powered by the positioner to
connect a floating contact. The switching state of the floating contact can be indicated over
the FOUNDATION™ fieldbus network.

Note
The binary inputs are configured in the DI Function Blocks.

KH 8384-5 EN 11
FOUNDATION™ fieldbus block model

2.3 Configuration using TROVIS-VIEW


The positioner can be configured with SAMSON's TROVIS-VIEW Software.
The positioner has for this purpose a serial interface to allow the RS-232 or USB port of a
computer to be connected to it using an adapter cable.
The TROVIS-VIEW software enables the user to easily configure the positioner as well as view
process parameters online.

2.4 Communication
The positioner is controlled completely by digital signal transmission according to
FOUNDATION™ fieldbus specification.
Data are transmitted over the bus using digital, bit-synchronous Manchester coding at a
Baud rate of 31.25 kbit/s over twisted-pair wires according to IEC 61158-2.

Note
If complex functions are started in the positioner, which require a long calculation time or
lead to a large quantity of data being saved in the volatile memory of the positioner, the alert
'busy' is issued over the DD. This alert is not an error message and can be simply confirmed.

3 FOUNDATION™ fieldbus block model


All the functions and data of the positioner are assigned to various block types in
FOUNDATION™ fieldbus. Each block type covers a different range of tasks. In the SAMSON
Type 3730-5 Positioner, the following block types are implemented:

12 KH 8384-5 EN
Initialization and zero calibration of the positioner

Resource Block (RES)


The Resource Block (RES) describes characteristics of the fieldbus device, such as the device
name, manufacturer number and serial number. There is only one Resource Block in a de-
vice.

Function Blocks (FB)


Function Blocks are responsible for the way a FOUNDATION™ fieldbus device works. A
FOUNDATION™ fieldbus application can be configured by linking the input and output
parameters of Function Blocks.
The Type 3730-5 Positioner includes the following Function Blocks:
− 1x Analog Output Function Blocks (AO FB); execution time: 30 ms
− 1x Analog Input Function Blocks (AI FB); execution time: 30 ms
− 2x Discrete Output Function Blocks (DO FB); execution time: 30 ms
− 2x Discrete Input Function Blocks (DI FB); execution time: 20 ms
− 1x Proportional Integral Derivative Function Block (PID); execution time: 40 ms

Transducer Blocks (TRD)


Each AI or AO Function Block has a Transducer Block which contains all data and de-
vice-specific parameters to link the device to the process value (sensor or final control ele-
ment).
The following Transducer Blocks (corresponding to the Function Blocks) are implemented:
− 1x Advanced Positioner Transducer Block (AO TRD)
− 1x Analog Input Transducer Block (AI TRD)
− 2x Discrete Output Transducer Blocks (DO TRD)
− 2x Discrete Input Transducer Blocks (DI TRD)

4 Initialization and zero calibration of the positioner


Both an initialization and a zero calibration can be started over the XD_COMMAND param-
eter of the AO Transducer Block. The relevant parameters for a MAX/NOM initialization and
the diagnostic functions of EXPERTplus are listed below (u EB 8389).
− APPLICATION_TYPE_OC_CONTROL (application type)
− INIT_METHOD (initialization method)

KH 8384-5 EN 13
Resetting the positioner

− TRANS_PIN_POS (follower pin position)


− RATED_TRAVEL (required rated travel for NOM initialization)
− PRESSURE_LIMIT (pressure limit setting)
− SELECT_EMERGENCY_MODE (E (setting when the travel sensor is defective)
− DEVICE_CHARACTERISTIC (C (settings for actuator and other accessories)
MODEL (actuator with or without spring-return mechanism)
BOOSTER (pneumatic volume booster)
STUFFING_BOX (packing to seal the plug stem to the atmosphere)
XD_COMMAND ("Start Initialization“)
XD_COMMAND_STATE (initialization status)

Note
Read the corresponding section on starting up the positioner in the Mounting and Operating
Instructions u EB 8384-5.

5 Resetting the positioner


The start-up and diagnostic data (in Code 36 Std) can be reset over the XD_COMMAND
(41) parameter of the AO Transducer Block.
The device data are reset and the function blocks connected to the values given in the
FOUNDATION™ fieldbus specification using the DEFAULTS value in the RESTART (16)
parameter of the Resource Block (RES).
A warm start of the positioner is performed using the PROCESSOR value in the RESTART (16)
parameter of the Resource Block (RES).
The entire diagnostic data as well as the individual messages and histograms are reset over
the RESET_STATUS_MESSAGE_DIAG (147) parameter of the AO Transducer Block.

14 KH 8384-5 EN
Status classification and condensed state

6 Status classification and condensed state


All status messages are classified in the positioner to report an error that has occurred. The
status classification can be changed over the DIAG_CLS parameter.
To provide a better overview, the classified messages are summarized in a condensed state
(CONDENSED_STATE (81) in the Resource Block). Besides the CONDENSED_STATE parame-
ter, the condensed state can be issued to the discrete output OUT_D of the DI Function Blocks
(DI1 + DI2).
Possible condensed states include:
0 OK
1 Maintenance required The positioner still performs its control task (with restrictions). A
maintenance demand or above average wear has been determined.
The wear tolerance will soon be exhausted or is reducing at a faster
rate than expected. Maintenance is necessary in the medium term.
2 Maintenance The positioner still performs its control task (with restrictions). A
demanded maintenance demand or above average wear has been determined.
The wear tolerance will soon be exhausted or is reducing at a faster
rate than expected. Maintenance is necessary in the short term.
3 Maintenance alarm The positioner cannot perform its control task due to a functional fault
in the positioner itself or in one of its peripherals or an initialization has
not yet been successfully completed.
7 Function check Test or calibration procedures are performed in the positioner. The
positioner is temporarily unable to perform its control task as long as
the procedure is taking place.

7 Block model
Several parameters can only be changed in certain modes (see Read/write capability in the
parameter description). In this case, not the actual mode is decisive, but the target mode.

7.1 Resource Block (RES)


The Resource Block contains all the data that identify the device. It is similar to an electronic
device tag. Resource Block parameters include device type, device name, manufacturer ID,
serial number as well as parameters that affect the behavior of all other blocks of the device.

KH 8384-5 EN 15
Block model

See page 27 for parameter list.

Note
All time specifications in the Resource Block are specified in the unit of 1/32 ms according to
the FOUNDATION™ fieldbus Specification Version 1.7.
In the Device Description Library supplied by Fieldbus FOUNDATION™ upon which the device
description of Type 3730-5 is also based, these parameters are incorrectly specified as the
unit of ms. The specified values supplied by the device are, however, always to be interpreted
as the unit of 1/32 ms.

7.2 Transducer Blocks


Transducer Blocks link the function blocks to the input and output variables of a field device.
For example, the DI Function Blocks are linked to the physical binary inputs, an internal sole-
noid valve, the current valve position or the condensed state of the positioner. This link to the
various Transducer Blocks is made over the CHANNEL parameter of the individual function
blocks. The table below shows how CHANNEL is assigned to the function block:
CHANNEL Function block
1 AO
2 AI
3 DI1
4 DI2
5 DO1
6 DO2

The Transducer Blocks DI TRD and DO TRD are implemented according to the
FOUNDATION™ fieldbus specification and do not contain any manufacturer-specific
parameters.

16 KH 8384-5 EN
Block model

7.3 Advanced Positioner Transducer Block (AO TRD)


The Advanced Positioner Transducer Block (AO TRD) contains an output value from an up-
stream Analog Output Function Block. This value is used to position a control valve. The block
contains parameters to adapt the positioner to the actuator and valve as well as for valve
start-up and diagnostics.

Action on fault detection


The action on fault detection for the "Maintenance alarm" state in the condensed state can be
configured in the XD_FSTATE_OPT parameter as follows:
− Hold last value
− Move to fail-safe position
− Move to fault state value XD_FSTATE_VAL
The action on fault detection to transfer to the O/S mode can be configured in the XD_OOS_
OPT parameter as follows:
− Hold last value
− Move to fail-safe position
− Move to fault state value XD_FSTATE_VAL
The AO Transducer Block (AO TRD) can still set an output error in the AO Function Block. For
this purpose, the following events to activate an output error can be configured in the
ALARM_OPTION parameter.
− No (never)
− Local Override (when the AO TRD is in the LOCAL OVERRIDE mode, i.e. the positioner is
set locally in the SAFE mode or an internal solenoid valve is activated)
− MAN (when the AO TRD is in MAN mode)
− Block alarm (when the AO TRD has a MAINTENANCE NOW block error)
− AO TRD fault state (when the action on fault detection is active)
− AO O/S set fault state (when the AO Function Block in the O/S mode, the valve is
moved to the FSTATE_VAL of the AO Function Block)

KH 8384-5 EN 17
Block model

Parameter description (Fig. 5)

Control valve
FINAL_VALUE Set point of upstream AO Function Block (control valve)
FINAL_POS_VALUE Valve position after rescaling
WORKING_SP Set point after scaling, characterization, end position function
(corresponds to the controlled variable of the control algorithm)
WORKING_POS Actual valve position
READBACK_SELECT Select parameter which is issued to READBACK of the AO Function
Block
On/off valve
FINAL_VALUE_D Discrete set point of upstream DO Function Block
FINAL_POS_VALUE_D Discrete valve position after taking the direction of action into account
WORKING_SP_D Set point after taking the direction of action into account (corresponds
to the set point of the control algorithm)
WORKING_POS_D Actual discrete valve position

See page 44 for parameter list.

7.4 Function blocks

7.4.1 Analog Output Function Block (AO FB)


The AO Function Block processes an analog signal from an upstream block (e.g. PID Function
Block) to an output value that can be used for the downstream Transducer Block (e.g. valve
positioner). It contains scaling functions and ramp functions as well as other functions. The
generated OUT value is forwarded over CHANNEL to the downstream Transducer Block.
The AO Function Block contains its set point SP depending on the mode (MODE_BLK)
− Manually entered SP (AUTO)
− Directly from an upstream function block (CAS_IN)
− Directly from a fieldbus host system (RCAS_IN)
An internal working process value PV is generated from SP, while taking into account:

18 KH 8384-5 EN
AO FB
MODE Scaling Characteristic

KH 8384-5 EN
CAS_IN MODE=AUTO FINAL_VALUE SIGNAL_ACTION
Control valve FVR End position function
READBACK

SetFailSafePos

DO FB
OUT_D MODE=AUTO MODE FINAL_VALUE_D SIGNAL_ACTION
Open/close (on/off)

DI FB
WORKING_SP_D WORKING_SP

OUT_D

Discrete valve position


1 Valve closed

Fig. 5: Advanced Positioner Transducer Block (AO TRD)


2 Valve open
3 Intermediate position

FINAL_POS_VALUE_D SIGNAL_ACTION WORKING_POS_D WORKING_POS

RB_SELECT

Characteristic
FINAL_POS_VALUE End position function SIGNAL_ACTION

19
Block model
Block model

− SP_HI_LIM (upper set point limit)


− SP_LO_LIM (lower set point limit)
− SP_RATE_DN (set point downward rate limit in AUTO mode)
− SP_RATE_UP (set point upward rate limit in AUTO mode)
− PV_SCALE (range of the process variable (PV) (start, end, unit and decimal point))
The OUT value is generated, while taking into account:
− XD_SCALE (range of the OUT value (start, end, unit and decimal point))
− IO_OPTS (determines the input/output action of the AO TRD, e.g. action on fault detec-
tion)

Action on fault detection


Action on fault detection taken during a communication fault (BAD status)
− The last valid value is used by default.
− By selecting FAULT STATE TO VALUE in the IO_OPTS parameter, the valve moves to the
fault state value FSTATE_VAL configured in the AO Function Block.
− FSTATE_TIME defines the length of time that the AO Function Block will wait to activate
the fault state.
Action on fault detection in OUT OF SERVICE (O/S) mode
− After the AO Function Block has moved to O/S mode, the last valid output value is kept
by default.
− By selecting "AO O/S set fault state" in the ALARM_OPTION parameter of AO TRD, the
valve moves to the fault state value FSTATE_VAL configured in the AO Function Block.
− FSTATE_TIME defines the length of time that the AO Function Block will wait to activate
the fault state.

See page 84 for parameter list.

20 KH 8384-5 EN
Block model

XD_SCALE

100 %

READBACK

OUT

0% PV_SCALE
0 ˚C

SP PV

SP_LO_LIM<=SP<=SP_HI_LIM
RCAS_IN

Set point lim- Set point PV, XD Output


it SP ramps scaling behavior OUT
SP
SP_HI_LIM SP_RATE_DN XD_SCALE IO_OPTS
CAS_IN

SP_LO_LIM SP_RATE_UP PV_SCALE

MODE_BLK OUT
MODE_BLK
PV, XD scaling PV (manual)
READBACK XD_SCALE, PV_SCALE

Fig. 2: Analog Output Function Block (AO FB)

KH 8384-5 EN 21
Block model

7.4.2 Proportional Integral Derivative Function Block (PID)


A PID Function Block contains the input channel processing, the proportional-integral-deriva-
tive (PID) control loop and the analog output channel processing.
The configuration of the PID Function Block (PID controller) depends on the automation task.
Simple control loops, control loops with feedforward control, cascade control and cascade
controls with limitation in combination with another controller function block can be imple-
mented.
The following options are available for data processing within the PID Function Block (PID
controller): signal scaling and limiting, mode control, feedforward control, override tracking,
alarm limit detection and signal status propagation.
The PID Function Block (PID controller) can be used for various automation strategies. The
block has a flexible control algorithm that can be configured to match the application.
The PID Function Block receives its set point depending on the mode (MODE_BLK) from the
input variables CAS_IN, RCAS_IN or SP. An internal working set point is generated based
on PV_SCALE, SP_HI_LIM, SP_LO_LIM, SP_RATE_UP and SP_RATE_DN.
The block receives the process value over the IN input variable which is used to generate the
process variable PV, taking into account the PV_SCALE and the filter of the first order PV_
FTIME.
These values are fed to the internal PID algorithm. This algorithm consists of a proportional,
an integral and a derivative component. The output value is calculated from the set point SP
and the process variable PV resulting from the set point deviation.
The single PID components are included in the calculation of the output value as follows:
− Proportional component:
The proportional component reacts immediately and directly when the set point SP or the
process variable PV changes. The output variable is changed by the proportional factor
GAIN. This change corresponds to the set point deviation multiplied by the gain factor. If
a controller works only with a proportional component, the control loop has a steady-
state error signal.
− Integral component:
The set point deviation resulting from the calculation of the output variable using the pro-
portional component is integrated over the integral component of the controller until it is
negligible. The integral function corrects the output variable depending on the size and
duration of the set point deviation. If the value for the integration time RESET is set to ze-
ro, the controller works as a P or PD controller. The influence of the integral component
on the control loop increases when the value of the integration time RESET is reduced.

22 KH 8384-5 EN
Block model

− Derivative component:
In controlled systems with long delay times, e.g. in temperature control loops, it is better
to use the derivative component RATE of the controller. Using the derivative component
RATE, the output variable is calculated depending on the rate of change of the set point
deviation.
An OUT value is generated from the calculated ouput value based on the OUT_SCALE,
OUT_HI_LIM and OUT_LO_LIM parameters. It can be forwarded to a downstream function
block.
The status of the OUT value can be influenced by the STATUS_OPTS parameter depending
on the status of the input variables of the PID Function Block. As a result, the fault state of a
following output block can be activated, for example.
The BYPASS parameter allows the internal set point to pass directly through to the output val-
ue. The FF_VAL input value allows feedforward control, while TRK_IN_D and TRK_VAL allow
the direct tracking of the out value.

See page 100 for parameter list.

Fault State
MODE_BLK SELECT_DO1
FSTATE_TIME
FSTATE_VALVUE_D

SP_D
CAS_IN_D IO_OPTS
RCAS_IN_D OUT_D Open/close application 1)
Inverted
MAN Start VST (Valve Stroke Test)

Reset diagnosis

OUT_D Reset message logger

Set to fail-safe position


MODE_BLK Simulate
Start data logger
SIMULATE_D Set local op. write protection

Reset/stop diagnosis
IO_OPTS
1)
Only supports DO1 Function
PV_D READBACK_D
Inverted Block

Fig. 3: Proportional Integral Derivative Function Block (PID)

KH 8384-5 EN 23
Block model

7.4.3 Discrete Input Function Block (DI1 FB + DI2 FB)


The DI Function Block processes single discrete signals and provides them to other function
blocks over the OUT_D parameter. The positioner has two DI Function Blocks which provide
the options listed in following. The application type is set over the SELECT_DI_1…2 parame-
ters of the Resource Block.
− 5 – 30 VDC (DI1)
As a standard feature, the positioner comes with a contact input to analyze binary volt-
age signals (terminals 87 and 88). The DI1 Function Block analyzes the state of the con-
tact and issues it over OUT_D.
− Floating contact (DI2)
The positioner can be fitted with an optional binary input to analyze a floating contact
(terminals 85 and 86). The DI2 Function Block analyzes the state of the contact and issues
it over OUT_D.
When a pressure sensor (leakage sensor) is connected, its switching state can be issued
as a diagnostic alarm in the XD_ERROR_EXT parameter of the AO Transducer Block and
logged. In this case, the 'Actively Open – Ext. Leak. Sens.' or 'Actively Closed – Ext.
Leak. Sens.' option must be activated in CONFIG_BINARY_INPUT2. Additionally, the
switching state of the binary input is issued in the BINARY_INPUT2 parameter of the AO
Transducer Block.
− Int. solenoid valve (DI1, DI2)
In this setting, the current switching state of the optional internal solenoid valve is ana-
lyzed and issued over OUT_D. '0' indicates a de-energized solenoid valve (U <
15 V DC) and '1' an energized solenoid valve (U > 19 V DC).
− Discr. final valve position (DI1, DI2)
In this setting, the current discrete valve position is issued over OUT_D. The values are as-
signed as follows:
0 Device not initialized
1 Valve closed
2 Valve open
3 Valve in intermediate position

24 KH 8384-5 EN
Block model

− Condensed State (DI1, DI2)


In this setting, the current condensed state according to NAMUR Recommendation
NE 107 is issued over OUT_D. The status messages are assigned to the discrete value as
follows:
0 No message
1 Maintenance required
2 Maintenance demanded
3 Maintenance alarm
7 Function check

See page 122 for parameter list.

SELECT_DI1...2

PV_D
Bin2
Simulate Optional Filter
MGV CHANNEL
SIMULATE_D Invert PV_FTIME
POS_D Output Out_D
FIELD_VAL_D
Condensed State

MODE Alarms
DISC

AO Transducer

BINARY_INPUT_2

CONFIG_BINARY_INPUT_2

Fig. 4: Discrete Input Function Block (DI1 FB + DI2 FB)

KH 8384-5 EN 25
Other parameters

8 Other parameters
The Stale Counter serves to judge the "quality" of a process variable received over a config-
ured cyclic connection (publisher/subscriber connection).
These connections are used to transfer the process variable linked amongst the various func-
tion blocks. For this purpose, the upstream block (publisher) sends the process variable over
the bus at scheduled times. The downstream block(s) (subscriber) responds at the scheduled
times. The blocks that are to receive data monitor whether a valid value exists at the sched-
uled time. A value is valid if it exists with the status "Good" at the scheduled time.
The Stale Counter defines how many "Bad" (stale) values can be accepted in sequence be-
fore the Fault State of the block is activated.
This monitoring function is deactivated by setting the Stale Counter to zero.

8.1 Link Objects


Link Objects are used to link the inputs and outputs of the function blocks (configurable cyclic
connections).
A maximum of 22 Link Objects can be configured for each positioner.

8.2 LAS Functionality


The number of links and schedules that can be used is matched to the requirements of stan-
dard process control systems available on the market.
The positioner functioning as an LAS can support the following:
− 2 schedules
− 2 subschedules
− 5 sequences per subschedule
− 48 elements per sequence
In the delivered state, the device is configured as a basic device.

26 KH 8384-5 EN
Parameter lists

9 Parameter lists
Legend
The parameter index is listed in brackets following the parameter name in the following ta-
bles.

Storage class S Static parameter


D Dynamic parameter
N Non-volatile parameter

Read/write capability r Read capability


w Write capability

Access O O/S (out of service) mode


M MAN mode
A AUTO mode
CAS Cascade mode
RCAS External cascade mode

ALL O/M/A/CAS/RCAS
NA Not analyzed

Other operating LO Local override mode


modes: ROUT External output mode

Note
Values/settings in square brackets [ ] are default settings.Resource Block (RES)

KH 8384-5 EN 27
Parameter lists

RES: ACK_OPTIONS (38)


Storage class S; read/write capability r/w; supported modes O/A
Automatic alarm acknowledgement
• Resource Block
• [UNDEFINED] · No selection
• DISC ALM · Write protection was changed
• BLOCK ALM · Block alarm
Note: The alarm is broadcast to the fieldbus host system, but not acknowledged by it.
RES: ALARM_SUM (37)
Storage class S; read/write capability r/w; supported modes O/A
Current status of process alarms in the Resource Block
• DISC ALM · Write protection was changed
• BLOCK ALM · Block alarm
Note: The process alarms can also be deactivated in this parameter group.
RES: ALERT_KEY (4)
Storage class S; read/write capability r/w; supported modes O/A
ID number of the plant section
• 1 to 255, [0]
Used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device (error
alarm).
RES: ALL_ACTIVE_STATUS_MESSAGES (84)
Storage class S; read/write capability r/w
Active status or error messages of the diagnositics
RES: BLOCK_ALM (36)
Storage class D; read capability r
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.

28 KH 8384-5 EN
Parameter lists

RES: BLOCK_ERR (6)


Storage class D; read capability r
Active block errors  Code 48 S2
• SIMULATE ACTIVE · Simulation jumper active, simulation possible
• OUT OF SERVICE · Block mode is out of service
• LOST STATIC DATA · Data loss in EEPROM
• DEVICE NEEDS MAINTENANCE SOON · Maintenance required soon. This message
triggers a block alarm (BLOCK_ALM) in the Resource Block.
• DEVICE NEEDS MAINTENANCE NOW · Maintenance required now. This message
triggers a block alarm (BLOCK_ALM) in the Resource Block.
Note: The assignment of error or diagnostic alarms to the desired function block is made
using the ERROR_OPTION parameters in the Transducer Block.
RES: BUS_ADDRESS (78)
Storage class D; read capability r
Bus address  Code 46
• 0 to 255, [248]
RES: CLR_FSTATE (30)
Storage class D; read/write capability r/w; supported modes O/A
Deactivation of the fault state of the AO Function Block
RES: CONDENSED_STATE (81)
Storage class D; read capability r
Displays the current condensed state according to NAMUR Recommendation NE 107
RES: CONFIRM_TIME (33)
Storage class S; read/write capability r/w; supported modes O/A
Confirmation time for event report
If the device does not receive a confirmation within this period of time, the event report is
sent again.
• [640000 ms]
RES: CYCLE_SEL (20)
Storage class S; read/write capability r/w; supported modes O/A
Block execution method determined by the fieldbus host system
• [Scheduled]
• Block Execution · Block execution completed
• Manuf Specific · Not analyzed
Note: The execution method is selected directly in the fieldbus host system.

KH 8384-5 EN 29
Parameter lists

RES: CYCLE_TYPE (19)


Storage class S; read capability r
Block execution method supported by the device
• Scheduled
• Block Execution · Block execution completed
RES: DD_RESOURCE (9)
Storage class S; read capability r
Source of the device description in the device
Note: If no device description is available in the device, zero is displayed.
RES: DD_REV (13)
Storage class S; read capability r
Revision number of the device description
RES: DESCRIPTOR (69)
Storage class S; read/write capability r/w; supported modes O/A
Any desired text to describe the application. The text is saved in the field device.
• Max. 32 characters, [no text]
RES: DEVICE_CERTIFICATION (68)
Storage class N; read capability r
Certification · Specifies whether explosion protection certificates are available for the
Type 3730-5.
RES: DEVICE_MESSAGE (70)
Storage class N; read/write capability r/w; supported modes O/A
Any desired text. The text is saved in the field device.
• Max. 32 characters, [no text]
RES: DEVICE_PRODUCT_NUM (71)
Storage class N; read capability r
Article code of the positioner as assigned by the manufacturer
RES: DEVICE_SER_NUM (67)
Storage class N; read capability r
Serial number of the positioner
RES: DEV_REV (12)
Storage class S; read capability r
Revision number of the positioner

30 KH 8384-5 EN
Parameter lists

RES: DEV_TYPE (11)


Storage class S; read capability r
Type number of the positioner (decimal number)
• In this case: Type 3730-5
RES: DIAG_CLS (82)
Storage class S; read/write capability r/w
Classification of diagnostic, status or error messages
RES: FAULT_STATE (28)
Storage class N; read capability r
Status of the fault state of the Analog Output Function Block
RES: FD_CHECK_ACTIVE (46)
Storage class D; read/write capability r
Active error messages with the 'Function check' status
RES: FD_CHECK_ALM (58)
Storage class D; read/write capability r
Active, not suppressed diagnostic messages with the 'Function check' status
RES: FD_CHECK_MAP (50)
Storage class S; read/write capability r/w
Classification of diagnostic messages with the 'Function check' status
RES: FD_CHECK_MASK (54)
Storage class S; read/write capability r/w
Activation/deactivation of diagnostic messages with the 'Function check' status
RES: FD_CHECK_PRI (62)
Storage class S; read/write capability r/w
Determines the priority of diagnostic messages with the 'Function check' status
RES: FD_FAIL_ACTIVE (43)
Storage class D; read/write capability r
Active error messages with the 'Maintenance alarm' status
RES: FD_FAIL_ALM (55)
Storage class D; read/write capability r
Active, not suppressed diagnostic messages with the 'Maintenance alarm' status

KH 8384-5 EN 31
Parameter lists

RES: FD_FAIL_MAP (47)


Storage class S; read/write capability r/w
Classification of diagnostic messages with the 'Maintenance alarm' status
RES: FD_FAIL_MASK (51)
Storage class S; read/write capability r/w
Activation/deactivation of diagnostic messages with the 'Maintenance alarm' status
RES: FD_FAIL_PRI (59)
Storage class S; read/write capability r/w
Determines the priority of diagnostic messages with the 'Maintenance alarm' status
RES: FD_MAINT_ACTIVE (45)
Storage class D; read/write capability r
Active error messages with the 'Maintenance demanded' status
RES: FD_MAINT_ALM (57)
Storage class D; read/write capability r
Active, not suppressed diagnostic messages with the 'Maintenance demanded' status
RES: FD_MAINT_MAP (49)
Storage class S; read/write capability r/w
Classification of diagnostic messages with the 'Maintenance demanded' status
RES: FD_MAINT_MASK (53)
Storage class S; read/write capability r/w
Activation/deactivation of diagnostic messages with the 'Maintenance demanded' status
RES: FD_MAINT_PRI (61)
Storage class S; read/write capability r/w
Determines the priority of diagnostic messages with the 'Maintenance demanded' status
RES: FD_OFFSPEC_ACTIVE (44)
Storage class D; read/write capability r
Active error messages with the 'Out of specification' status
RES: FD_OFFSPEC_ALM (56)
Storage class D; read/write capability r
Active, not suppressed diagnostic messages with the 'Out of specification' status

32 KH 8384-5 EN
Parameter lists

RES: FD_OFFSPEC_MAP (48)


Storage class S; read/write capability r/w
Classification of diagnostic messages with the 'Out of specification' status
RES: FD_OFFSPEC_MASK (52)
Storage class S; read/write capability r/w
Activation/deactivation of diagnostic messages with the 'Out of specification' status
RES: FD_OFFSPEC_PRI (60)
Storage class S; read/write capability r/w
Determines the priority of diagnostic messages with the 'Out of specification' status
RES: FD_RECOMMEN_ACT (64)
Storage class D; read/write capability r
Recommended action
RES: FD_SIMULATE (63)
Storage class S; read/write capability r/w
Simulation of diagnostic messages
RES: FD_VER (42)
Storage class S; read/write capability r
Field diagnostic specification version
• [1]
RES: FEATURES (17)
Storage class S; read capability r
Additional functions supported by the device, see FEATURES_SEL
RES: FEATURES_SEL (18)
Storage class S; read/write capability r/w; supported modes O/A
Selects the additional functions supported by the device
• REPORTS · Fieldbus host system needs to acknowledge receipt of the event report.
• HARD W LOCK · Write lock switch hardware is assessed.
• FAULTSTATE · Fault state can be triggered (see SET_FSTATE/CLR_FSTATE).
• OUT READBACK · Current valve position issued in the PV parameter of the Analog
Function Block (otherwise in SP parameter).
Note: If the AO Function Block is not to move to the MAN mode when the forced venting
function is activated or the solenoid valve is triggered, deactivate this option.

KH 8384-5 EN 33
Parameter lists

RES: FIRMWARE_REVISION (65)


Storage class N; read capability r
Firmware version for communication and control
RES: FREE_SPACE (24) · This parameter is not supported.

RES: FREE_TIME (25) · This parameter is not supported.

RES: GRANT_DENY (14)


Storage class D; read/write capability r/w; supported modes NA
Grant or deny a fieldbus host system access to the field device
Note: This parameter is not analyzed by Type 3730-5.
RES: HARD_TYPES (15)
Storage class S; read capability r
Types of input and output signals (hardware) available for the device
• [Scalar Output] · Scalable analog output variable
• Scalar Input · Scalable analog input variable
• Discrete Output
• Discrete Input
RES: HW_REVISION (66)
Storage class S; read capability r
Hardware release for electronics and mechanics
RES: ITK_VER (41)
Storage class S
Version of the Interoperability Tester Kit on which the interoperablity testing is based.
RES: LIM_NOTIFY (32)
Storage class S; read/write capability r/w; supported modes O/A
Number of unconfirmed event reports simultaneously supported by the device.
• 0 to [40]
RES: LOCAL_OP_ENA (79)
Storage class N; read/write capability r/w; supported modes O/A
Locks on-site operation

34 KH 8384-5 EN
Parameter lists

RES: MANUFAC_ID (10)


Storage class S; read capability r
Manufacturer ID
• [0 x 00E099] · SAMSON AG
RES: MAX_NOTIFY (31)
Storage class S; read capability r
Number of unconfirmed event reports simultaneously supported by the device.
• [40]
RES: MEMORY_SIZE (22) · This parameter is not supported.

RES: MIN_CYCLE_T (21)


Storage class S; read capability r
Shortest cycle time that the device can perform.
• [8000 · ms]
RES: MODE_BLK (5)
Storage class N; read/write capability r/w; supported modes O/A
Mode of the Resource Block
– Target Mode  Code 48 S0
– Actual Mode (read only)  Code 48 S1
– Permitted Mode
– Normal Mode (read only)
• AUTO · The execution of the function blocks (AO and PID) is enabled.
• O/S · The execution of the function blocks (AO and PID) is stopped. These blocks go out
of service (O/S mode).
RES: NV_CYCLE_T (23)
Storage class S; read capability r
Time interval in which device data are stored to the non-volatile memory.
Note: Non-volatile data are saved immediately after transmission.

KH 8384-5 EN 35
Parameter lists

RES: READING_DIRECTION (77)


Storage class D; read/write capability r/w; supported modes O/A
Reading direction  Code 2
The reading direction of the display is turned by 180°
• [Pneum. connection right]
• Pneum. connection left
RES: RESTART (16)
Storage class D; read/write capability r/w; supported modes O/A
Resetting the positioner
• RUN · Normal operating status
• RESOURCE (setting not supported)
• DEFAULTS · Resets device data and interconnection of function blocks to the values defined
in the FF specification.
• PROCESSOR · Soft reset of the device, processor restart
RES: RS_STATE (7)
Storage class D; read capability r
Current operating status of the Resource Block
• ONLINE · Normal operating state; the function block is in AUTO mode.
• STANDBY · The Resource Block is in O/S mode.
• ONLINE LINKING · The configured links between the function blocks have not been
established yet.
RES: SELECT_USAGE_IO (80)
Storage class N; read/write capability r/w; supported modes O
SELECT_DI_1 · Data for processing in the DI1 Function Block
• [5-30 VDC] · State of the standard binary contact BI1 (terminals +87/–88)
0 Input voltage Ue < 3 V DC
1 Input voltage Ue > 5 V DC
• INT.SOL.VLVE · Switching state of the internal solenoid valve
0 Solenoid valve de-energized (U < 15 V DC)
1 Solenoid valve energized (U > 19 V DC)

36 KH 8384-5 EN
Parameter lists

• DIS.F.VLVE.POS · Current valve position as discrete information


0 Device not initialized
1 Current valve position < x %
2 Current valve position > x %
3 Intermediate position
Note: The limits for < x % and > x % are set in FINAL_POSITION_VALUE_LIMITS [0.5;
99.5]
• COND.STATE · Current condensed state
0 OK
1 Maintenance required
2 Maintenance demanded
3 Maintenance alarm
7 Function check
SELECT_DI_2 · Data for processing in the DI2 Function Block
• FI_CONTACT · State of the standard binary contact BI2 (terminal +85/–86)
0 Floating contact open
1 Floating contact closed
• INT.SOL.VLVE · Switching state of the internal solenoid valve
0 Solenoid valve de-energized (U < 15 V DC)
1 Solenoid valve energized (U > 19 V DC)
• DIS.F.VLVE.POS · Current valve position as discrete information
0 Device not initialized
1 Current valve position < x %
2 Current valve position > x %
3 Intermediate position
Note: The limits for < x % and > x % are set in FINAL_POSITION_VALUE_LIMITS [0.5;
99.5]
• COND.STATE · Current condensed state
0 OK
1 Maintenance required
2 Maintenance demanded
3 Maintenance alarm
7 Function check

KH 8384-5 EN 37
Parameter lists

• [COND.STATE + VST] · Current condensed state and start of the VST (Valve Stroke Test).
See setting in VST_MODE parameter in the AO TRD Block.
SELECT_DO_1 · Purpose of the DO1 Function Block
Note: For firmware K 3.05 and higher, read the footnote 1) at the end of the parameter
description.
• DO1 O/C · On/off service
• [VST] · Start of the VST (Valve Stroke Test). See setting in VST_MODE parameter in the AO
TRD Block.
• RESET DIAG · Reset diagnosis (resetting of statistical information and tests, the
classification of status messages and logging remain saved)
• RESET LOGGER · Reset logging
• F.-SAFE · Move to fail-safe position
• DLOG · Data logger (0 Start; 1 Stop)
• LOG WRITE PR · Lock on-site operation (LOCAL_OP_ENA)
• DIAGNOSIS · Reset/stop diagnosis
1 Reset diagnosis
2 Reset logging
3 Stop diagnosis
4 Enable/start diagnosis
SELECT_DO_2 · Purpose of the DO2 Function Block
Note: For firmware K 3.05 and higher, read the footnote 1) at the end of the parameter
description.
• VST · Start of the VST (Valve Stroke Test). See setting in VST_MODE parameter in the AO
TRD Block.
• RESET DIAG · Reset diagnosis (resetting of statistical information and tests, the
classification of status messages and logging remain saved)
• RESET LOGGER · Reset logging
• [F.-SAFE] · Move to fail-safe position
• DLOG · Data logger (0 Start; 1 Stop)
• LOG WRITE PR · Lock on-site operation (LOCAL_OP_ENA)
• DIAGNOSIS · Reset/stop diagnosis
1 Reset diagnosis
2 Reset logging
3 Stop diagnosis
4 Enable/start diagnosis

38 KH 8384-5 EN
Parameter lists

1) The following applies to the configuration of the DO1 and DO2 Transducer Blocks:
• Both DO1 and DO2 Transducer Blocks must be set to the O/S mode.
• The fail-safe position must not be active.
• The two transducer blocks must have different configurations in SELECT_DO_1 and
SELECT_DO_2.
RES: SET_FSTATE (29)
Storage class D; read/write capability r/w; supported modes O/A
Activation of the fault state in the AO Function Block
RES: SHED_RCAS (26)
Storage class S; read/write capability r/w; supported modes O/A
Monitoring time to check connection between fieldbus host system and PID Function Block in
RCAS mode
When the monitoring time has elapsed, the PID Function Block switches from RCAS to the
mode selected in the SHED_OPT parameter.
• [640000 · ms]
RES: SHED_ROUT (27)
Storage class S; read/write capability r/w; supported modes O/A
Monitoring time to check connection between fieldbus host system and PID Function Block in
ROUT mode
When the monitoring time has elapsed, the PID Function Block switches from ROUT to the
mode selected in the SHED_OPT parameter.
• [640000 · ms]
RES: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes O/A
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each block.
Note: These data are neither checked nor processed by the Resource Block.
RES: ST_REV (1)
Storage class N; read capability r
Static revision number
Note: The revision number is incremented with each change of a static parameter in the
block.

KH 8384-5 EN 39
Parameter lists

RES: TAG_DESC (2)


Storage class S; read/write capability r/w; supported modes O/A
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
RES: TEST_RW (8)
Storage class D; read/write capability r/w; supported modes O/A
This parameter is required for conformity tests only and is not relevant for normal operation.
RES: TEXT_INPUT_1 (72) to TEXT_INPUT_5 (76)
Storage class N; read/write capability r/w; supported modes O/A
Any text
• Max. 32 characters, [no text]
RES: UPDATE_EVT (35)
Storage class D; read capability r
Indicates whether static data have been changed, including date and time stamp
RES: WRITE_ALM (40)
Storage class D; read/write capability r/w; supported modes O/A
Status of write protection alarm
Note: The alarm is triggered when write protection is deactivated.
RES: WRITE_LOCK (34)
Storage class S; read/write capability r/w; supported modes O/A
Status of the write protection switch  Code 47
• LOCKED · Write protection activated
• NOT LOCKED · Write protection deactivated
Note: The write-lock can be activated by setting Code 47 to ON: device data can only be
read over FOUNDATION™ fieldbus communication, but not overwritten.
The write-lock can be deactivated by setting Code 47 to OFF: device data can be
overwritten over FOUNDATION™ fieldbus communication.

40 KH 8384-5 EN
Parameter lists

RES: WRITE_PRI (39)


Storage class S; read/write capability r/w; supported modes O/A
Behavior upon a write-lock alarm (WRITE_ALM parameter)
• [0] · The write-lock alarm is not processed
• 1 · The write-lock alarm is not broadcast to the fieldbus host system.
• 2 · Reserved for block alarms
• 3 to 7 · The write-lock alarm is issued to notify the operator with the corresponding
priority: (3 = low, 7 = high)
• 8 to 15 · The write-lock alarm is issued as a critical alarm with the corresponding priority:
(8 = low, 15 = high)

KH 8384-5 EN 41
Parameter lists

Index and parameter assignment: Resource Block

Index Parameters Index Parameters


0 RESOURCE_BLOCK_2 30 CLR_FSTATE
1 ST_REV 31 MAX_NOTIFY
2 TAG_DESC 32 LIM_NOTIFY
3 STRATEGY 33 CONFIRM_TIME
4 ALERT_KEY 34 WRITE_LOCK
5 MODE_BLK 35 UPDATE_EVT
6 BLOCK_ERR 36 BLOCK_ALM
7 RS_STATE 37 ALARM_SUM
8 TEST_RW 38 ACK_OPTION
9 DD_RESOURCE 39 WRITE_PRI
10 MANUFAC_ID 40 WRITE_ALM
11 DEV_TYPE 41 ITK_VER
12 DEV_REV 42 FD_VER
13 DD_REV 43 FD_FAIL_ACTIVE
14 GRANT_DENY 44 FD_OFFSPEC_ACTIVE
15 HARD_TYPES 45 FD_MAINT_ACTIVE
16 RESTART 46 FD_CHECK_ACTIVE
17 FEATURES 47 FD_FAIL_MAP
18 FEATURE_SEL 48 FD_OFFSPEC_MAP
19 CYCLE_TYPE 49 FD_MAINT_MAP
20 CYCLE_SEL 50 FD_CHECK_MAP
21 MIN_CYCLE_T 51 FD_FAIL_MASK
22 MEMORY_SIZE 52 FD_OFFSPEC_MASK
23 NV_CYCLE_T 53 FD_MAINT_MASK
24 FREE_SPACE 54 FD_CHECK_MASK
25 FREE_TIME 55 FD_FAIL_ALM
26 SHED_RCAS 56 FD_OFFSPEC_ALM
27 SHED_ROUT 57 FD_MAINT_ALM
28 FAULT_STATE 58 FD_CHECK_ALM
29 SET_FSTATE 59 FD_FAIL_PRI

42 KH 8384-5 EN
Parameter lists

Index Parameters
60 FD_OFFSPEC_PRI
61 FD_MAINT_PRO
62 FD_CHECK_PRI
63 FD_SIMULATE
64 FD_RECOMMEN_ACT
65 FIRMWARE_REVISION
66 HW_REVISION
67 DEVICE_SER_NUM
68 DEVICE_CERTIFICATION
69 DESCRIPTOR
70 DEVICE_MESSAGE
71 DEVICE_PRODUCT_NUM
72 TEXT_INPUT_1
73 TEXT_INPUT_2
74 TEXT_INPUT_3
75 TEXT_INPUT_4
76 TEXT_INPUT_5
77 READING_DIRECTION
78 BUS_ADDRESS
79 LOCAL_OP_ENA
80 SELECT_USAGE_IO
81 CONDENSED_STATE
82 DIAG_CLS
84 ALL_ACTIVE_STATUS_MESSAGES

KH 8384-5 EN 43
Parameter lists

9.1 Advanced Positioner Transducer Block (AO TRD)


AO TRD: ACT_FAIL_ACTION (38)
Storage class S; read/write capability r/w
The fail-safe action of the actuator in the event of a supply air failure is detected
automatically during initialization.
• Air to open (in 0 % position)
• Air to close (in 100 % position)
AO TRD: ACT_MAN_ID (39)
Storage class S; read/write capability r/w; supported modes O/M/A
Actuator manufacturer
Identifies the manufacturer of the actuator associated with the positioner
AO TRD: ACT_MODEL_NUM (40)
Storage class S; read/write capability r/w; supported modes O/M/A
Type of the actuator associated with the positioner
AO TRD: ACT_SN (41)
Storage class S; read/write capability r/w; supported modes O/M/A
Serial number of the actuator associated with the positioner
AO TRD: ALARM_OPTION (101)
Storage class S; read/write capability r/w
Alarm setting to activate an output error in AO Function Block
• No (never) · No
• Local Override · Alarm triggered when the AO TRD is in the LOCAL OVERRIDE mode,
i.e. the positioner is set locally in the SAFE mode or an internal solenoid valve is
activated.
• MAN · Alarm triggered when AO TRD is in MAN mode.
• Block Alarm · Alarm triggered when the AO TRD has a MAINTENANCE NOW block
error
• AO TRD fault state · Alarm triggered when the fault state is active.
• AO O/S set fault state · Alarm triggered when the AO Function Block in the O/S mode,
the valve is moved to the FSTATE_VAL of the AO Function Block.

44 KH 8384-5 EN
Parameter lists

AO TRD: ALERT_KEY (4)


Storage class S; read/write capability r/w
ID number of the plant section
• 1 to 255, [0]
May be used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device (error
alarm).
AO TRD: ANALYSIS_OPEN_CLOSE (147)
Storage class D; read capability r
Statistical information > Open/Close
Reference analysis and the last two test analyses (u EB 8389 (EXPERTplus valve
diagnostics)
• TIME_STAMP_RISING/FALLING
• BREAK_AWAY_TIME_RISING/FALLING
• TRANSIT_TIME_RISING/FALLING
• VALVE_END_POSITION_RISING/FALLING
AO TRD: APPLICATION_TYPE_OC_CONTROL (144)
Storage class S; read/write capability r/w; supported modes O/M/A
Application type (valve)
• Control Valve
• Open/Close (on/off) Valve
AO TRD: AUTOMATIC_TEST_STATUS (175)
Storage class S; read/write capability r/w; supported modes O/M/A
Status of active test: drive signal diagram steady (d1 test)
Drive signal diagram hysteresis (d2 test)
Static characteristic (d3 test)
Partial stroke test (PST) (d4 test)
AO TRD: BINARY_INPUT_2 (111)
Storage class D; read capability r
State of DI2 Function Block
The value issued depends on CONFIG_BINARY_INPUT_2.

KH 8384-5 EN 45
Parameter lists

AO TRD: BLOCKING_POSITION (124)


Storage class S; read/write capability r/w; supported modes O/M/A
Blocking position  Code 35
Distance to CLOSED position (0 % position)
Note: Only necessary with SUB initialization mode.
AO TRD: BLOCK_ALM (8)
Storage class D; read/write capability r/w
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
AO TRD: BLOCK_ERR (6)
Storage class D; read capability r
Active block errors  Code 48 S2
• SIMULATE ACTIVE · Simulation jumper active, simulation possible
• OUT OF SERVICE · Block mode is out of service
• LOST STATIC DATA · Data loss in EEPROM
• DEVICE NEEDS MAINTENANCE SOON · Maintenance required soon. This message
triggers a block alarm (BLOCK_ALM) in the AO TRD Block.
• DEVICE NEEDS MAINTENANCE NOW · Maintenance required now. This message
triggers a block alarm (BLOCK_ALM) in the AO TRD Block.
Note: The assignment of error or diagnostic alarms to the desired function block is made
using the ERROR_OPTION parameters in the Transducer Block.
AO TRD: CHARACTERIZATION (91)
Storage class S; read/write capability r/w; supported modes O/M/A
Characteristic selection  Code 20
1 Linear
2 Equal percentage
3 Equal percentage reverse
4 SAMSON butterfly linear
5 SAMSON butterfly equal percentage
6 VETEC rotary linear
7 VETEC rotary equal percentage
8 Segmented ball valve linear
9 Segmented ball valve (equal) percentage
10 User defined
Definition using AO TRD (CUSTOM_CURVE_XY_FLOAT (63))

46 KH 8384-5 EN
Parameter lists

AO TRD: CLOSED_POS_DEADBAND (61)


Storage class S; read/write capability r/w
Zero limit [%]  Code 48 d5
AO TRD: CLOSED_POS_SHIFT (62)
Storage class N; read capability r
Lower end position shift
AO TRD: CLOSING_DIRECTION (121)
Storage class S; read/write capability r/w; supported modes O/M/A
Closing direction  Code 34
Lever's direction of rotation for travel pick-off which causes the CLOSED position (0 %
position) of the control valve to be reached.
Note: Only necessary with SUB initialization mode.
AO TRD: CONFIG_BINARY_INPUT_2 (110)
Storage class S; read/write capability r/w; supported modes O/M/A
Sets the logical state of DI2
• [NOT EVALUATED]
• ACTIVELY OPEN
• ACTIVELY CLOSED
• ACTIVELY OPEN – LEAKAGE SENSOR
• ACTIVELY CLOSED – LEAKAGE SENSOR
Note: The parameter is processed by the BINARY_INPUT_2 parameter. The parameter
settings do not depend on DI2 Transducer Block.
AO TRD: COUNTER_INIT_START (138)
Storage class D; read capability r
The total number of initializations that have been performed since the last reset  Code
48 d4
AO TRD: CUSTOM_CURVE_DESCRIPTION (63) · This parameter is not supported.

AO TRD: CUSTOM_CURVE_XY_FLOAT (65)


Storage class S; read/write capability r/w; supported modes O/M/A
Enter the user-defined characteristic

KH 8384-5 EN 47
Parameter lists

AO TRD: CYCLE_CNTR (33)


Storage class D; read capability r
Number of measured cycles since the counter was last reset
AO TRD: CYCLE_CNTR_LIM (76)
Storage class S; read/write capability r/w; supported modes O/M/A
Maximum cycle counter limit for user-defined settings (selected through Stuffing box/
Other)
AO TRD: DEPTXE (173)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Characteristic of the lower end position
AO TRD: DEPTXR (174)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reference characteristic of the lower end position
AO TRD: DEVIATION_DEADBAND (21)
Storage class S; read/write capability r/w; supported modes O/M/A
Tolerance band relating to the operating range  Code 190
• 1 to 10.0 %, [5.0 %]
AO TRD: DEVIATION_MAX (105)
Storage class D; read capability r
Max. set point deviation of the positioner that has occurred
AO TRD: DEVIATION_MIN (104)
Storage class D; read capability r
Min. set point deviation of the positioner that has occurred
AO TRD: DEVIATION_TIME (22)
Storage class S; read/write capability r/w; supported modes O/M/A
Lag time (resets active control loop monitoring)
• 1 to 240 s, [10 s]
A control loop error is reported when entered lag time (DEVIATION_TIME) is exceeded
and the set point deviation is not within the entered tolerance band (DEVIATION_
DEADBAND).
Note: The DEVIATION_TIME value is determined during initialization from the minimum
transit time.

48 KH 8384-5 EN
Parameter lists

AO TRD: DEVIATION_VALUE (23)


Storage class D; read capability r
Set point deviation e  Code 39
AO TRD: DEVICE_INIT_STATE (120)
Storage class D; read capability r
Indicates whether the device has been initialized.
AO TRD: DEVICE_STATUS_INIT (121)
Storage class D; read capability r
Status of initialization in progress
AO TRD: DIAG_LEVEL (132)
Storage class D; read capability r
Existing diagnostic level: EXPERTplus
AO TRD: DIAG_REFLAUF_INFO (176)
Storage class S; read capability r
Status of the reference tests in progress
AO TRD: DIAG_RESET_AFTER_TIME (142)
Storage class S; read/write capability r/w; supported modes O/M/A
Time until the next single reset of the diagnosis
AO TRD: DIAG_RESET_AFTER_TIMEOUT (143)
Storage class S; read capability r
Time remaining until the next single reset of the diagnosis
AO TRD: DSKV1 (194) to DSKV4 (197)
Storage class D; read capability r
Tests/Static characteristic
Measured valve position x values of the characteristic
AO TRD: DSKW1 (198) to DSKW4 (201)
Storage class D; read capability r
Tests/Static characteristic
Measured set point w values of the characteristic

KH 8384-5 EN 49
Parameter lists

AO TRD: DSXHTW (191)


Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test)
Measured valve position x values of the characteristic of the last performed test
AO TRD: DSXSTR (182)
Storage class D; read capability r
Tests > Drive signal diagram steady (d1 test)
Measured valve position x values of the reference characteristic
AO TRD: DSXSTW (184)
Storage class D; read capability r
Tests > Drive signal diagram steady (d1 test)
Measured valve position x values of the characteristic of the last performed test
AO TRD: DSYHTR (189)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test)
Measured valve position x values of the reference characteristic
AO TRD: DSYHTW (190)
Storage class D; read capability r
Statistical information > Drive signal diagram > Hysteresis
Mean values of drive signal changes (long-term monitoring)
AO TRD: DSYSK (157)
Storage class D; read capability r
Statistical information > Drive signal diagram > Steady
Measured values of the characteristic, drive signal (short-term monitoring)
AO TRD: DSYSL (156)
Storage class D; read capability r
Statistical information > Drive signal diagram > Steady
Measured values of the characteristic, drive signal (long-term monitoring)
AO TRD: DSYSS (158)
Storage class D; read capability r
Statistical information > Drive signal diagram > Steady
Shows last ten measured drive signal values (belonging to DIAGR_VALVE_POS_STAT_
SHORT)

50 KH 8384-5 EN
Parameter lists

AO TRD: DSYSTR (181)


Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test)
Measured drive signal y values of the reference characteristic
AO TRD: DSYSTW (183)
Storage class D; read capability r
Tests > Drive signal diagram steady (d1 test)
Measured drive signal y values of the reference characteristic
AO TRD: DVPSS (159)
Storage class D; read capability r
Statistical information > Drive signal diagram > Steady
Shows last ten measured valve position values (belonging to DIAGR_STELL_Y_STAT_
SHORT)
AO TRD: EHM (136)
Storage class D; read capability r
Operating hours counter
• ELAPSED_HOURS_TOTAL · Device switched on
• ELAPSED_HOURS_IN_CLOSED_LOOP
• ELAPSED_HOURS_SWITCHED_ON_SINCE_INIT · Device switched on since last
initialization
• ELAPSED_HOURS_IN_CLOSED_LOOP_SINCE_INIT · Device in closed-loop operation
since last initialization
AO TRD: END_POS_TREND_REF_DRIVE_SIG_REF (168)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reference value of the lower end position (drive signal y)
AO TRD: END_POS_TREND_REF_TIME_REF (167)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reference value of the lower end position (time stamp)
AO TRD: END_POS_TREND_REF_VALUES_REF (166)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reference value of the lower end position (valve position x)

KH 8384-5 EN 51
Parameter lists

AO TRD: EPTRDS (171)


Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reading of the last 30 lower end positions (drive signal y)
AO TRD: EPTRT (170)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reading of the last 30 lower end positions (time stamp)
AO TRD: EPTRV (169)
Storage class D; read capability r
Statistical information > Trend of travel end position > Lower end position
Reading of the last 30 lower end positions (valve position x)
AO TRD: EVENT_LOGGING_1 (139)
EVENT_LOGGING_2 (140)
Storage class D; read capability r
• EVENT_LOGGING_1: indicates event logs 0 – 14 with the time they were recorded
• EVENT_LOGGING_2: indicates event logs 15 – 29 with the time they were recorded
AO TRD: FINAL_POSITION_VALUE (18)
Storage class D; read capability r
Current valve position after taking rescaling into account
AO TRD: FINAL_POSITION_VALUE_D (50)
Storage class D; read capability r
Current discrete valve position after taking the direction of action into account
AO TRD: FINAL_POSITION_VALUE_LIMITS (131)
Storage class S; read/write capability r/w
Limit of the valve position (FINAL_POSITION_VALUE)
• FINAL_POSITION_VALUE_LIMITS
• FINAL_POSITION_VALUE_HIGH_LIMIT
• FINAL_POSITION_VALUE_LOW_LIMIT
This variable is sent to the AO Transducer Block directly from the valve

52 KH 8384-5 EN
Parameter lists

AO TRD: FINAL_VALUE (14)


Storage class S; read/write capability r/w; supported modes O/M
Positioning value TRD
FINAL_VALUE contains the positioning value received from the upstream AO Function
Block.
Scaling over FINAL_VALUE_RANGE
AO TRD: FINAL_VALUE_CUTOFF_HI (16)
Storage class S; read/write capability r/w; supported modes O/M/A
Setpoint cutoff increase  Code 15
• 50 to 100 %, [100 %]
If the set point exceeds the entered value, the valve is moved towards the end position
(corresponding to 100 % of the output value). To do so, the actuator is either completely
filled with air or completely vented depending on the fail-safe action.
Note: The function is deactivated by entering –2.5 %.
NOTICE The control valve moves to its final end position as this function causes the
actuator to be either fully vented or filled with air. Restrictions determined by the travel
range or travel stop function do not apply. Deactivate this function if excessive thrust may
arise as a result.
AO TRD: FINAL_VALUE_CUTOFF_HI_ON (123)
Storage class S; read/write capability r/w; supported modes O/M/A
Enable setpoint cutoff increase  Code 15
AO TRD: FINAL_VALUE_CUTOFF_LO (17)
Storage class S; read/write capability r/w; supported modes O/M/A
Setpoint cutoff decrease  Code 14
• 0 to 50 %, [1 %]
If the set point falls below the entered value, the valve is moved towards the end position
(corresponding to 0 % of the output value). To do so, the actuator is either completely filled
with air or completely vented depending on the fail-safe action.
Note: The function is deactivated by entering 0 %.
NOTICE The control valve moves to its final end position as this function causes the
actuator to be either fully vented or filled with air. Restrictions determined by the travel
range or travel stop function do not apply. Deactivate this function if excessive thrust may
arise as a result.
AO TRD: FINAL_VALUE_CUTOFF_LO_ON (122)
Storage class S; read/write capability r/w; supported modes O/M/A
Enable setpoint cutoff decrease  Code 14

KH 8384-5 EN 53
Parameter lists

AO TRD: FINAL_VALUE_D (49)


Storage class S; read/write capability r/w; supported modes O/M
Discrete set point of upstream DO1 Function Block
AO TRD: FINAL_VALUE_RANGE (15)
Storage class S; read/write capability r/w; supported modes O
Travel/angle range
• FINAL VALUE RANGE EU_100 · Travel/angle range end  Code 9
• FINAL VALUE RANGE EU_0 · Travel/angle range start  Code 8
• FINAL VALUE RANGE UNITS_INDEX · Unit
• FINAL VALUE RANGE DECIMAL · Decimal point
Note: FINAL_VALUE is sent to the AO Transducer Block directly from an upstream AO
Function Block.
The FINAL_VALUE_RANGE operating range is compared on entering it with TRANS_PIN_
POS. If the TRANS_PIN_POS parameter is changed, the positioner checks whether the
setting and unit match the current operating range FINAL_VALUE_RANGE. If this is not the
case, the FINAL_VALUE_RANGE operating range is set to 0 to 100 %.
AO TRD: FRICTION (68)
Storage class N; read capability r
Determined friction in percent
AO TRD: FRICTION_LIMITS (265)
Storage class S; read/write capability r/w; supported modes O/M/A
Upper/lower friction limits
• FRICTION_LIMIT_UP, 0 to 1000 % [200 %]
• FRICTION_LIMIT_DOWN, 0 to 1000 % [50 %]
AO TRD: FRICTION_UNITS (67) · This parameter is not supported.

AO TRD: FST_BREAKOUT_TIME (86)


Storage class S; read capability r
Breakaway time determined during the last full stroke test (FST)
AO TRD: FST_BREAKOUT_TIMEOUT (87)
Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the full stroke test (FST): maximum breakaway time
• 0.0 to 25000.0 s, [7.5 s]

54 KH 8384-5 EN
Parameter lists

AO TRD: FST_COMPLETION_TIMEOUT (90)


Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the full stroke test (FST): maximum test duration (user-defined)
• 0.0 to 25000.0 s, [30.0 s]
AO TRD: FST_DIAGR_E1 (257) to FST_DIAGR_E4 (260)
Storage class D; read capability r
Statistical information > Data logger: Measured set point deviation (e) values
AO TRD: FST_DIAGR_TIME1 (245) to FST_DIAGR_TIME4 (248)
Storage class D; read capability r
Tests > Full stroke test (FST): Measured time (t) values
AO TRD: FST_DIAGR_W1 (253) to FST_DIAGR_W4 (256)
Storage class D; read capability r
Statistical information > Data logger: Measured set point (w) values
AO TRD: FST_DIAGR_X1 (249) to FST_DIAGR_X4 (252)
Storage class D; read capability r
Statistical information > Data logger: Measured valve position (x) values
AO TRD: FST_DIAGR_Y1 (261) to FST_DIAGR_Y4 (264)
Storage class D; read capability r
Statistical information > Data logger: Measured drive signal (y) values
AO TRD: FST_DISPLAY (238)
Storage class D; read capability r
Information on the full stroke test (FST)
• FST_PROGRESS_FLAG · Current progress of the test
• FST_STATUS_PST · Status (successful/not successful)
• FST_NUMBERS_OF_TESTS · Number of full stroke tests performed
• FST_SETTINGS_MIN_SCAN_RATE · Recommended min. scan rate
• FST_SETTINGS_DURATION_TEST · Expected duration of test

KH 8384-5 EN 55
Parameter lists

AO TRD: FST_MEAS_DATA1 (239) to FST_MEAS_DATA3 (241)


Storage class D; read capability r
Measured data assessment of the full stroke test (FST)
FST_MEAS_DATA1 (271) = Current test
FST_MEAS_DATA2 (272) = First measured data assessment saved
FST_MEAS_DATA3 (273) = Second measured data assessment saved
• FST_TIME_STAMP · Time stamp for this test
• FST_OVERSHOOT_RISING · Overshoot (rising)
• FST_DEAD_TIME_RISING · Dead time (rising)
• FST_T63_RISING · T63 (rising)
• FST_T98_RISING · T98 (rising)
• FST_RISE_TI_RISING · Rise time (rising)
• FST_SETTL_TI_RISING · Settling time (rising)
• FST_OVERSHOOT_FALLING · Overshoot (falling)
• FST_DEAD_TI_FALLING · Dead time (falling)
• FST_T68_FALLING · T63 (falling)
• FST_T98_FALLING · T98 (falling)
• FST_RISE_T_FALLING · Rise time (falling)
• FST_SETTL_T_FALLING · Settling time (falling)
AO TRD: FST_RAMP_RATE (88) · This parameter is not supported.

AO TRD: FST_SETTINGS (237)


Storage class D; read/write capability r/w; supported modes O/M/A
Settings for the full stroke test (FST)
• FST_TOL_LIMIT_RESPONSE · Tolerance limit for step start/end values
• FST_ACTIV_RAMP_FUNCTION · Activate ramp function
• FST_RAMP_TIME_RISING · Ramp time (rising)
• FST_RAMP_TIME_FALLING · Ramp time (falling)
• FST_SETTLING_TIME · Settling time before starting test
• FST_SCAN_RATE
AO TRD: FST_STRK_TRAV_TIMEOUT (89)
Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the full stroke test (FST): perm. time until step end 0.0 to 25000
s, [15.0 s]

56 KH 8384-5 EN
Parameter lists

AO TRD: FST_TEST_INFO (235)


Storage class D; read capability r
Current status of the full stroke test (FST)
AO TRD: FST_TEST_STAT1 (274) to FST_TEST_STAT3 (276)
Storage class D; read capability r
Status of the full stroke test (FST)
FST_TEST_STAT1 (274) = Current test
FST_TEST_STAT2 (275) = First saved status
FST_TEST_STAT3 (276) = Second saved status
• FST_NO_TEST_AVAILABLE · No test available
• FST_MAX_TIME_EXCEEDED · Max. test duration exceeded
• FST_TEST_MANUA_CANCEL · Test canceled manually
• FST_OUT_OF_MEMORY · Measured data memory full
• FST_ABO_INT_SOL_VALVE · Canceled due to internal solenoid valve/forced venting
• FST_PRESSURE_FRICTION · Canceled due to supply air/friction
• FST_CURRENT_TOO_LOW · Test canceled, insufficient current
AO TRD: HIST (135)
Storage class D; read capability r
Reading in hours (or part thereof)
• HIS_T_ZEIT_MIN_TEMPERATURE · Operating hours counter: lowest temperature inside
the positioner
• HIS_T_ZEIT_MAX_TEMPERATURE · Operating hours counter: highest temperature inside
the positioner
• TEMP_PERIOD_TIME_LOW · Time the temperature remained below –40 °C (–40 °F)
• TEMP_PERIOD_TIME_HIGH · Time the temperature remained above +80 °C (+176 °F)
AO TRD: HISTOGR_X_SCAN_RATE (150)
Storage class D; read/write capability r/w; supported modes O/M/A
Statistical information > Short-term valve position x histogram: measured values and mean
value
AO TRD: HISTOGR_X_SHORT (149)
Storage class D; read capability r
Statistical information > Short-term valve position x histogram: scan rate to record valve
positions

KH 8384-5 EN 57
Parameter lists

AO TRD: HXL (148)


Storage class D; read capability r
Statistical information > Long-term valve position x histogram: measured values, mean
value, number of measuring points and observation period
AO TRD: HYSTERESIS (69) · This parameter is not supported.

AO TRD: HYST_SHORT_DIFF_Y (163)


Storage class D; read capability r
Statistical information > Drive signal diagram > Hysteresis: last ten measured values of
drive signal difference (y) (belonging to HYST_VALVE_POS)
AO TRD: HYST_VALVE_POS (164)
Storage class D; read capability r
Statistical information > Drive signal diagram > Hysteresis: last ten measured values of
valve position (belonging to HYST_SHORT_DIFF_Y)
AO TRD: IDENT_OPTIONS (108)
Storage class D; read capability r
Options (additional equipment)
• 1 Internal solenoid valve
• 2 Binary input 1
• 3 Binary input 2
• 4 Inductive limit contact
• 5 Leakage sensor
• 6 External position sensor
AO TRD: INIT_METHOD (116)
Storage class S; read/write capability r/w
Initialization mode  Code 6
• 0 Maximum range (MAX)
• 1 Nominal range (NOM)
• 2 Manually selected range (MAN)
• 3 Substitute calibration (SUB)
• 4 Zero calibration

58 KH 8384-5 EN
Parameter lists

AO TRD: INIT_WITH_REF_TEST (117)


Storage class S; read/write capability r/w
Record diagnostic reference tests during initialization.
• Yes
• [No]
AO TRD: INTERNAL_TEMP (96)
Storage class D; read capability r
Current temperature inside the positioner
AO TRD: INTERNAL_TEMP_MAX (98)
Storage class D; read capability r
Highest temperature measured inside the positioner
AO TRD: INTERNAL_TEMP_MIN (97)
Storage class D; read capability r
Lowest temperature measured inside the positioner
AO TRD: INTERNAL_TEMP_UNITS (99)
Storage class S; read/write capability r/w; supported modes O/M/A
Unit of temperature inside the positioner: [°C], °F
AO TRD: KP_STEP (127)
Storage class S; read/write capability r/w
Proportional-action coefficient Kp level  Code 17
Note: This parameter can only be read over FOUNDATION fieldbus. The value is recorded
during initialization.
AO TRD: LIMIT_VALUE_TIME_ANALYSIS (145)
Storage class S; read/write capability r/w; supported modes O/M/A
Statistical information > Open/close: time limit for difference between reference value and
currently recorded value
Determines at which value a message is generated.
• 0.0 to 30.0 s, [0.6 s]
AO TRD: LIMIT_VALUE_TRAVEL_ANALYSIS (146)
Storage class S; read/write capability r/w; supported modes O/M/A
Statistical information > Open/close: travel limit for difference between reference value
and currently recorded value
Determines at which value a message is generated.
• 0.0 … 100.0 %, [0.3 %]

KH 8384-5 EN 59
Parameter lists

AO TRD: LOGGING_MGV (106)


Storage class S; read/write capability r/w; supported modes O/M/A
Logging of the solenoid valve active (error control)
• [Yes]
• No
AO TRD: LS_ALARM_INFORMATION (306)
Storage class D; read capability r
Leakage sensor: alarm information
AO TRD: LS_ALARM_LIMIT_1 (270) to LS_ALARM_LIMIT_3 (272)
Storage class S; read/write capability r/w
Leakage sensor
LS_ALARM_LIMIT_1 (307) = First alarm limit in dB
LS_ALARM_LIMIT_2 (308) = Second alarm limit in dB
LS_ALARM_LIMIT_3 (309) = Third alarm limit in dB
AO TRD: LS_ALARM_RELEASE (304)
Storage class S; read/write capability r/w; supported modes O/M/A
Leakage sensor: alarm triggering
• No alarm release · No alarm triggering
• Average level at tight-closing · Mean sound level when tight closing
• [Average of current/last tight-closing] · Mean of current/last tight closing
• Moving average short-term histogram · Rolling mean from short-term histogram
• Moving average long-term histogram · Rolling mean from long-term histogram
AO TRD: LS_LEAKAGE_LEVEL (266)
Storage class D; read capability r
Leakage sensor: sensor level in dB
AO TRD: LS_SELECT_ALARM_LIMITS (268)
Storage class S; read/write capability r/w; supported modes O/M/A
Leakage sensor: alarm limits
• [Factory setting (reference test)]
• Alarm limit of repetition test
• User defined alarm limit

60 KH 8384-5 EN
Parameter lists

AO TRD: LS_TEST_INFORMATION (273)


Storage class D; read capability r
Leakage sensor: test status
AO TRD: MIN_CLEARANCE_NEW_LOGGING_MGV (107)
Storage class S; read/write capability r/w; supported modes O/M/A
Minimum time interval until logging of the internal solenoid valve restarts (error control)
AO TRD: MODE_BLK (5)
Storage class S; read/write capability r/w
Operating mode
– Target Mode  Code 48 t0
– Actual Mode (read only)  Code 48 t1
– Permitted Mode
– Normal Mode (read only)
• AUTO · A positioning value is calculated from the output value received from the AO
Function Block and the control valve is positioned accordingly.
• O/S · The positioning value from the AO Function Block is not used. The control valve is
moved to its mechanical fail-safe position entered in ACT_FAIL_ACTION. The mode is
also changed to O/S when the forced venting function is activated.
• MAN · The positioning value (FINAL_VALUE) can be entered manually (reading at the
positioner: and )
• LO · AO TRD switches to LO mode if the positioner is switched to the MAN mode on
site.
AO TRD: NO_OF_ZERO_POINT_ADJ (137)
Storage class D; read capability r
Number of zero calibrations performed since the last initialization  Code 48 d3
AO TRD: OPTI_SUB_INIT (119)
Storage class S; read/write capability r/w; supported modes O/M/A
Optimizes edges of substitute calibration
• ON
• [OFF]

KH 8384-5 EN 61
Parameter lists

AO TRD: PCC (207)


Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the partial stroke test (PST)
• PST_ACT_X_CONTROL · Activation of x cancellation condition
• PST_X_CONTROL_VALUE · x control value
• PST_ACT_DELTA_Y_MONI · Activation of y cancellation condition
• PST_DELTA_Y_MONI_VAL · delta y-monitoring value
• PST_TOL_BAND_CONTROL · Activate PST tolerance band monitoring
• PST_TOL_BAND · PST tolerance band
AO TRD: PMD1 (209) to PMD3 (211)
Storage class D; read capability r
Measured data assessment of the partial stroke test (PST)
PMD1 (209) = Current test
PMD2 (210) = First measured data assessment saved
PMD3 (211) = Second measured data assessment saved
• PST_TIME_STAMP · Time stamp for this test
• PST_OVERSHOOT_RISING · Overshoot (rising)
• PST_DEAD_TIME_RISING · Dead time (rising)
• PST_T63_RISING · T63 (rising)
• PST_T98_RISING · T98 (rising)
• PST_RISE_TI_RISING · Rise time (rising)
• PST_SETTL_TI_RISING · Settling time (rising)
• PST_OVERSHOOT_FALLING · Overshoot (falling)
• PST_DEAD_TI_FALLING · Dead time (falling)
• PST_T68_FALLING · T63 (falling)
• PST_T98_FALLING · T98 (falling)
• PST_RISE_T_FALLING · Rise time (falling)
• PST_SETTL_T_FALLING · Settling time (falling)
• PST_DELTA_Y · delta y-monitoring (repetition value)
AO TRD: POSITIONER_MODEL (112)
Storage class D; read capability r
Positioner type

62 KH 8384-5 EN
Parameter lists

AO TRD: POS_ALERT_HI (24)


Storage class S; read/write capability r/w; supported modes O/M/A
User-defined high limit which sets the high limit bit in WORKING_ POS when the value is
exceeded.
• [100 %]
AO TRD: POS_ALERT_LO (25)
Storage class S; read/write capability r/w; supported modes O/M/A
User-defined low limit which sets the low limit bit in WORKING_ POS when the value falls
below the limit.
• [0 %]
AO TRD: POS_DEADBAND (70) · This parameter is not supported.

AO TRD: POS_FEATURES (55)


Storage class D; read capability r
Parameter groups supported by AO TRD
AO TRD: PRESSURE_LIMIT (125)
Storage class S; read/write capability r/w
Pressure limit  Code 16
• [OFF]
• 3.7 bar
• 2.4 bar
• 1.4 bar
AO TRD: PROTOKOLL_BSZ_START (141)
Storage class D; read capability r
Display the time since first start-up (operating hours counter)
AO TRD: PST_AUTOSTART_READ (203)
Storage class D; read capability r; supported modes O/M/A
Time until the next automatically performed partial stroke test (Auto PST)
AO TRD: PST_BREAKOUT_TIME (77)
Storage class N; read capability r
Breakaway time determined during the last partial stroke test (PST)

KH 8384-5 EN 63
Parameter lists

AO TRD: PST_BREAKOUT_TIMEOUT (78)


Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the partial stroke test (PST): maximum breakaway time
AO TRD: PST_COMPLETION_TIMEOUT (85)
Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the partial stroke test (PST): maximum test duration (user-
defined)
AO TRD: PST_DIAGR_E1 (227) to PST_DIAGR_E4 (230)
Storage class D; read capability r
Statistical information > Data logger: Measured set point deviation (e) values
AO TRD: PST_DIAGR_TIME1 (215) to PST_DIAGR_TIME4 (218)
Storage class D; read capability r
Tests > Partial stroke test (PST): Measured time (t) values
AO TRD: PST_DIAGR_W1 (223) to PST_DIAGR_W4 (226)
Storage class D; read capability r
Statistical information > Data logger: Measured set point (w) values
AO TRD: PST_DIAGR_X1 (219) to PST_DIAGR_X4 (222)
Storage class D; read capability r
Statistical information > Data logger: Measured valve position (x) values
AO TRD: PST_DIAGR_Y1 (231) to PST_DIAGR_Y4 (234)
Storage class D; read capability r
Statistical information > Data logger: Measured drive signal (y) values
AO TRD: PST_DISPLAY (208)
Storage class D; read capability r
Information on the partial stroke test (PST)
• PST_PROGRESS_FLAG · Current progress of the test
• PST_MIN_VALUE_Y_CONTROL · delta y-monitoring (repetition value)
• PST_DELTA_Y_MONI_REF_VAL · delta y-monitoring reference value
• PST_STATUS_PST · Status (successful/not successful)
• PST_NUMBERS_OF_TESTS · Number of partial stroke tests performed
• PST_RECOMMENDED_SCAN_RATE · Recommended min. scan rate
• PST_DURATION_OF_TEST · Expected duration of test
• PST_TESTMODE_ACTUAL · Current PST mode

64 KH 8384-5 EN
Parameter lists

AO TRD: PST_INITIAL_START_TIME (79) · This parameter is not supported.

AO TRD: PST_INTERVAL (80)


Storage class S; read/write capability r/w; supported modes O/M/A
Time until the automatic partial stroke test starts (PST_TESTMODE_TARGET must be set to
'PST Auto')
AO TRD: PST_OPTIONS (81) · This parameter is not supported.

AO TRD: PST_RAMP_RATE (82) · This parameter is not supported.

AO TRD: PST_SETTINGS (206)


Storage class D; read/write capability r/w; supported modes O/M/A
Settings of partial stroke test (PST)
• PST_STEP_START · Start value for step response
• PST_STEP_END · End value for step response
• PST_LIMIT_STEP_RESPONSE · Tolerance limit for step start/end values
• PST_ACTIVATION_RAMP_FUNCTION · Activate ramp function
• PST_ACTIVATION_RAMP_FUNCTION · Activate ramp function
• PST_RAMP_TIME_RISING · Ramp time (rising)
• PST_RAMP_TIME_FALLING · Ramp time (falling)
• PST_SETTLING_TIME_BEFORE_TEST · Settling time before starting test
• PST_SCAN_RATE
• PST_STEP_RESPONSE · Number of step responses
AO TRD: PST_STRK_TRAV (83)
Storage class S; read capability r
Step height during partial stroke test (PST)
AO TRD: PST_STRK_TRAV_TIMEOUT (84)
Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the partial stroke test (PST): perm. time until step end

KH 8384-5 EN 65
Parameter lists

AO TRD: PST_TESTMODE_TARGET (202)


Storage class D; read/write capability r/w; supported modes O/M/A
Target PST testing mode
• [PST Man]
• PST Auto
AO TRD: PST_TEST_INFO (204)
Storage class D; read capability r
Current status of the partial stroke test (PST)
AO TRD: PST_TEST_STAT1 (212) to PST_TEST_STAT3 (214)
Storage class D; read capability r
Status of the partial stroke test (PST)
PST_TEST_STAT1 (212) = Current test
PST_TEST_STAT2 (213) = First saved status
PST_TEST_STAT3 (214) = Second saved status
• PST_TEST_START
• PST_NO_TEST_AVAILABLE · No test available
• PST_X_CANCEL · x cancellation
• PST_Y_CANCEL · y cancellation
• PST_TOL_BAND_EXCEEDED
• PST_MAX_TIME_EXCEEDED · Max. test duration exceeded
• PST_TEST_MANUA_CANCEL · Test canceled manually
• PST_OUT_OF_MEMORY · Measured data memory full
• PST_ABO_INT_SOL_VALVE · Canceled due to internal solenoid valve/forced venting
• PST_PRESSURE_FRICTION · Canceled due to supply air/friction
• PST_W_STEP_TOO_HIGH · Set point difference, step start too high
• PST_ABORT_REF_CHANGED · Test canceled, set point too high
• PST_CURRENT_TOO_LOW · Test canceled, insufficient current
AO TRD: RATED_TRAVEL (26)
Storage class S; read/write capability r/w
Nominal range  Code 5
• 0 to 255.9 mm, [15.0 mm]
Note: The unit [mm] or [degrees] depends on the VALVE_TYPE parameter.

66 KH 8384-5 EN
Parameter lists

AO TRD: READBACK_SELECT (35)


Storage class S; read/write capability r/w
Select current or actual valve position for the READBACK parameter
• [FINAL_POSITION_VALUE]
• WORKING_POS
AO TRD: REFLAUF_VOLLST (177)
Storage class D; read capability r
Reference tests completed
AO TRD: RESET_STATUS_MESSAGE_DIAG (134)
Storage class D; read/write capability r/w
Select reset command
• Single error message
• Trends, histograms, test diagrams
• PST/FST parameters and measured values
• Logging
• All recorded diagnostic data (except for reference graphs and logging)
AO TRD: SELECT_EMERGENCY_MODE (126)
Storage class S; read/write capability r/w
Behavior upon failure/defective travel sensor
• Open-loop control based on saved characteristic
• Move to defined fail-safe position
AO TRD: SELO (109)
Storage class S; read/write capability r/w; supported modes O/M/A
Display/change installed options that are not automatically detected (IDENT_LIMIT_
SWITCHES, IDENT_EXT_LEAKAGE_SENSOR, IDENT LEAKAGE DETECTION, IDENT_EXT_
POS_SENSOR)
AO TRD: SET_FAIL_SAFE_POS (114)
Storage class S; read/write capability r/w
Set fail-safe position
• NOT ACTIVE
• SET FAIL-SAFE POSITION
• CLEAR FAIL-SAFE POSITION
Note: The fail-safe position is indicated on the positioner display by a blinking 'S'.

KH 8384-5 EN 67
Parameter lists

AO TRD: SIGNAL_ACTION (34)


Storage class S; read/write capability r/w; supported modes O/M/A
Direction of action of the set point w in relation to the travel/angle x  Code 7
AO TRD: SKR (192)
Storage class D; read capability r
Tests > Static characteristic: display
• STAT_KENNL_R_TEST_INFO · Current status of the test
• STAT_KENNL_R_STEP_HEIGHT · Step height
• STAT_KENNL_R_MIN_DEAD_BAND · Smallest dead band measured
• STAT_KENNL_R_AVERAGE_DEAD_BAND · Average dead band measured
• STAT_KENNL_R_MAX_DEAD_BAND · Largest dead band measured
• STAT_KENNL_R_PROGRESS_FLAG · Current progress of the test
AO TRD: SKW (193)
Storage class S; read/write capability r/w
Tests > Static characteristic: enter values
• STAT_KENNL_W_START_VALUE · Start value of valve position x
• STAT_KENNL_W_END_VALUE · End value of valve position x
• STAT_KENNL_W_DELAY_TIME · Delay time after step
• STAT_KENNL_W_TURN_BACK_VALUES · Number of measured values recorded before
changing the testing direction
AO TRD: SSAF (133)
Storage class D; read/write capability r/w
Execute/end various EXPERTplus tests
• Reference tests (d1, d2)
• Data logger
• Tests (d1 to d6 and d9)
AO TRD: STOP_HI (27)
Storage class S; read/write capability r/w; supported modes O/M/A
Travel/angle upper limit  Code 11
• 50 … 120 %, [100 %]
Note: The characteristic is not adapted. The tight-closing function has priority.

68 KH 8384-5 EN
Parameter lists

AO TRD: STOP_LO (28)


Storage class S; read/write capability r/w; supported modes O/M/A
Travel/angle lower limit  Code 10
• 0.0 … 49.9 %, [0.0 %]
Note: The characteristic is not adapted. The tight-closing function has priority.
AO TRD: STOP_HI_POS_ON (130)
Storage class S; read/write capability r/w; supported modes O/M/A
Enable travel/angle upper limit  Code 11
• [ON]
• OFF
AO TRD: STOP_LO_POS_ON (129)
Storage class S; read/write capability r/w; supported modes O/M/A
Enable travel/angle lower limit  Code 10
• ON
• [OFF]
AO TRD: STRATEGY (3)
Storage class S; read/write capability r/w
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note: These data are neither checked nor processed by the AO Transducer Block.
AO TRD: STROKE_TIME_CLOSED (71)
Storage class S; read capability r
Minimum transit time CLOSED  Code 41
Time [s] required by the system (positioner, actuator and valve) to move through the rated
travel/angle in the direction to close the valve (0 % position)
The value is measured during initialization.
AO TRD: STROKE_TIME_CLOS_LIM (92)
Storage class S; read/write capability r/w
Required transit time CLOSED  Code 22
Time required to move through the operating range when the valve closes.

KH 8384-5 EN 69
Parameter lists

AO TRD: STROKE_TIME_OPEN (72)


Storage class S; read capability r
Minimum transit time OPEN  Code 40
Time [s] required by the system (positioner, actuator and valve) to move through the rated
travel/angle in the direction to open the valve (100 % position)
The value is measured during initialization.
AO TRD: STROKE_TIME_OPEN_LIM (93)
Storage class S; read/write capability r/w
Required transit time OPEN  Code 21
Time required to move through the operating range when the valve opens.
AO TRD: STR_DEVICE_CHARACTERISTIC (113)
Storage class S; read/write capability r/w; supported modes O/M/A
Specific positioner data
• MODEL · Actuator type
• ATTACHMENT (actuator)
• BOOSTER · Volume booster (actuator)
• ACTUATOR_SIZE · Effective actuator area
• SIGNAL_PRESSURE_LOWER_VALUE (actuator)
• SIGNAL_PRESSURE_UPPER_VALUE (actuator)
• SUPPLY_PRESSURE
• FLOW_DIRECTION1 (valve)
• STUFFING_BOX · Packing (valve)
• CYCLE_CNTR_LIM1SEALING_EDGE · Leakage class (valve)
• PRESSURE_BALANCING (valve)
• FLOW_CHARACTERISTIC (valve)
• NOM_DIAMETER · Size standard (valve)
• NOM_DIAMETER_DN (valve)
• KVS_VALUE · KVS coefficient (valve)
• KVS_UNIT
• SEAT_DIAM_VALVE · Seat bore diameter (valve)
• LENGTH_UNITS
• PRESSURE_UNIT

70 KH 8384-5 EN
Parameter lists

AO TRD: ST_REV (1)


Storage class S; read capability r
Static revision number
Note: The revision number is incremented with each change of a static parameter in the
block.
AO TRD: SUB_MOD_INIT (118)
Storage class D; read capability r
Indicates whether the initialization was performed in SUB mode (substitute calibration).
AO TRD: TAG_DESC (2)
Storage class S; read/write capability r/w
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
AO TRD: THRESHOLD_END_POS_RECORDING (207)
Storage class D; read/write capability r/w
Statistical information > Trend of travel end position
Recording threshold
AO TRD: TRANSDUCER_DIRECTORY (9) · This parameter is not supported.

AO TRD: TRANSDUCER_STATE (102)


Storage class D; read capability r
State of the Transducer Block  Code 48 t2
11 See operating mode
12 Solenoid valve active · Forced venting active
13 Lower travel limit active
14 Upper travel limit active
15 End position < active · Tight-closing of the valve
16 End position > active · Maximum open position of the valve
17 Fail-safe position active
18 Normal operation
AO TRD: TRANSDUCER_TYPE (10)
Storage class D; read capability r
Indicates the type of transducer. “Standard Advanced Positioner Valve” in this case.

KH 8384-5 EN 71
Parameter lists

AO TRD: TRANSDUCER_TYPE_VER (11)


Storage class D; read capability r
Transducer Block for positioner according to Specification FF-90
AO TRD: TRANSM_PIN_POS (115)
Storage class S; read/write capability r/w
Pin position  Code 4
AO TRD: TRAVEL_ACCUM (29)
Storage class D; read capability r
Total valve travel: totaled double valve travel  Code 23
AO TRD: TRAVEL_ACCUM_DEADBAND (73) · This parameter is not supported.

AO TRD: TRAVEL_ACCUM_LIM (94) · This parameter is not supported.

AO TRD: TRAVEL_ACCUM_UNITS (95) · This parameter is not supported.

AO TRD: TRAVEL_UNITS (30)


Storage class S; read/write capability r/w; supported modes O/M/A
Unit of valve travel according to Table TN-016
• [%] or [°], in the event that the positioner is not initialized
AO TRD: TRIP_TIMEOUT (74) · This parameter is not supported.

AO TRD: TV_STEP (128)


Storage class S; read/write capability r/w
Derivative-action time TV (step)  Code 18
Note: This parameter can only be read over FOUNDATION fieldbus. The value is recorded
during initialization.
AO TRD: UPDATE_EVT (7)
Storage class D; read/write capability r/w
Indicates whether static data have been changed, including date and time stamp.
AO TRD: VALVE_MAN_ID (42)
Storage class S; read/write capability r/w; supported modes O/M/A
Manufacturer of the valve on which the positioner is mounted.

72 KH 8384-5 EN
Parameter lists

AO TRD: VALVE_MODEL_NUM (43)


Storage class S; read/write capability r/w; supported modes O/M/A
Model of the valve on which the positioner is mounted.
AO TRD: VALVE_SN (44)
Storage class S; read/write capability r/w; supported modes O/M/A
Serial number of the valve on which the positioner is mounted.
AO TRD: VALVE_TYPE (45)
Storage class S; read/write capability r/w; supported modes O/M/A
Type of valve
-/- · Undefined (treated as a globe valve)
• [LINEAR] · (control valves with straight moving plug, e.g. globe valves)
• ROTARY · (control valves with rotating closure members, e.g. part-turn, etc.)
• OTHER · (treated as a globe valve)
Note: The Type 3730-5 differentiates merely between linear and rotary valves,
“UNINITIALIZED“ and “OTHER“ are treated as globe valves
AO TRD: VST_COMMAND (56)
Storage class D; read/write capability r/w; supported modes M/A
Start/abort the partial stroke test (PST)/full stroke test (FST)
AO TRD: VST_DETAILED_RESULT (60) · This parameter is not supported.

AO TRD: VST_MODE (57)


Storage class S; read/write capability r/w; supported modes O/M/A
VST (Valve Stroke Test) to be performed
• Deactivated
• [PST (partial stroke test)]
• FST (full stroke test)
AO TRD: VST_PAUSE (58)
Storage class S; read/write capability r/w; supported modes O/M/A
Waiting time after the first step until the second step starts
• 0.1 … 240.0 s, [2.0 s]
AO TRD: VST_RESULT (59)
Storage class N; read capability r
Indicates that the result of the last PST/FST (successful/not successful)

KH 8384-5 EN 73
Parameter lists

AO TRD: WORKING_POS (19)


Storage class D; read capability r
Actual valve position in %
AO TRD: WORKING_POS_D (51)
Storage class D; read capability r
Actual discrete valve position
AO TRD: WORKING_SP (20)
Storage class N; read capability r
Set point after scaling, characterization and the end position function
Corresponds to the set point of the control algorithm for the AO Function Block (Control
valve mode).
AO TRD: WORKING_SP_D (52)
Storage class N; read capability r
Discrete set point after taking the direction of action into account
Corresponds to the set point of the control algorithm for the DO Function Block (Open/
Close mode).
AO TRD: XD_CAL_DATE (47)
Storage class S; read/write capability r/w; supported modes O/M/A
Time of last calibration
AO TRD: XD_CAL_LOC (46)
Storage class S; read/write capability r/w; supported modes O/M/A
Place of last calibration
AO TRD: XD_CAL_WHO (48)
Storage class S; read/write capability r/w; supported modes O/M/A
Person who performed last calibration

74 KH 8384-5 EN
Parameter lists

AO TRD: XD_COMMAND (36)


Storage class D; read/write capability r/w
Parameters to start device-specific procedures
• No test, normal operation
• Start with default values
• Start Initialization
• Abort Initialization
• Start Zero Point adjustment
• Abort Zero Point adjustment
• Search device
AO TRD: XD_COMMAND_FLAGS (75) · This parameter is not supported.

AO TRD: XD_COMMAND_STATE (37)


Storage class D; read capability r
Initialization status
AO TRD: XD_ERROR (12)
Storage class D; read capability r
Error listed in the AO Transducer Block
• NONE (0) · No error
• UNSPECIFIED ERROR · · Unspecified (device not initialized, initialization or zero
calibration in progress or total valve travel exceeded)
• GENERAL ERROR · General device error
• CALIBRATION ERROR · Zero point, internal control loop or initialization error, reference
test canceled  Code 81
• CONFIGURATION ERROR · Parameter or characteristic faulty
• ELECTRONICS FAILURE · i/p converter (Code 64), hardware (Code 65), bus connection
• MECHANICAL FAILURE
• DATA INTEGRITY ERROR · Check sum error
• ALGORITHM ERROR · Dynamic values outside range

KH 8384-5 EN 75
Parameter lists

AO TRD: XD_ERROR_EXT (103)


Storage class D; read capability r
Extended errors listed in the AO Transducer Block
1 xd_error_ext_1
• Device not initialized
• Int. solenoid valve active
• Tot.valve travel limit exc.
• Control loop  Code 57
• Zero point  Code 58
• Autocorrection  Code 59
• Fatal error  Code 60
• Extended diagnostics  Code 79
• x > range  Code 50
• Delta x < range  Code 51
• Attachment  Code 52
• Init. time exceeded  Code 53
• Init./int. solenoid valve  Code 54
• Travel time too short  Code 55
• Pin position/safety switch  Code 56
• Test or calibration running
2 xd_error_ext_2
• x-signal  Code 62
• i/p-converter  Code 64
• Hardware  Code 65
• Control parameter  Code 68
• Poti parameter  Code 69
• Adjustment parameter  Code 70
• General parameter  Code 71
• Internal device error 1  Code 73
• No emergency mode  Code 76
• Program load error  Code 77
• Options parameter  Code 78
• Info parameter  Code 75
• Data memory  Code 66
• Control calculation  Code 67
• Reference test aborted  Code 81

76 KH 8384-5 EN
Parameter lists

3 xd_error_ext_3
• Reset comm. controller
• Attachment unit disturbed
• Bin 2 deactivated
• Reset appl. controller
• FF parameter
• Mode unequal AUTO
• Temperature exceeding
14 Air Supply
15 Actuator Spring
16 Shifting Working Range
17 Friction
18 Leakage Pneumatic
19 Limit Working Range
20 Inner Leakage
21 External Leakage
22 Observing End Position
23 Connection Positioner Valve
24 Working Range
25 Temperature Error
26 PST/FST Status
27 Open Close Status
AO TRD: XD_FSTATE_OPT (32)
Storage class S; read/write capability r/w; supported modes O/M/A
Action on fault detection in AO TRD
• [Hold last value]
• Fail-safe position
• Fault state value (XD_FSTATE_VAL)
AO TRD: XD_FSTATE_VAL (31)
Storage class S; read/write capability r/w; supported modes O/M/A
Fault state value to which the valve moves when the AO Transducer Block is in the O/S
mode and the action on fault detection has been selected in the XD_OOS_OPTS
parameter.
• 0 … 100 %, [0 %]

KH 8384-5 EN 77
Parameter lists

AO TRD: XD_FSTATE_VAL_D (53)


Storage class S; read/write capability r/w; supported modes O/M/A
Discrete fault state value to which the valve moves when the AO Transducer Block is in the
O/S mode and the action on fault detection has been selected in the XD_OOS_OPTS
parameter.
• [0], 10 - 0 %1 - 100 %
AO TRD: XD_OOS_OPT (54)
Storage class S; read/write capability r/w; supported modes O/M/A
Action when the AO Transducer Block is in the O/S mode
• [Hold last value]
• Fail-safe position
• Fault state value (XD_FSTATE_VAL)
AO TRD: Y_HYST_MIN_TIME_DISTANCE (160)
Storage class S; read/write capability r/w; supported modes O/M/A
Statistical information > Drive signal diagram > Hysteresis
Time until test (d5) is repeated
• 0 to 24 h, [1 h]
AO TRD: Y_HYST_TESTINFO (162)
Storage class D; read capability r
Statistical information > Drive signal diagram hysteresis (d5 test): test status
AO TRD: Y_HYST_TEST_INFO (186)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test): test status
AO TRD: Y_HYST_TEST_PROGRESS (187)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test): progress of test in %
AO TRD: Y_HYST_TEST_TIME_STAMP (185)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test): time stamp for reference value recording
AO TRD: Y_HYST_TOLERANCE_BAND (161)
Storage class D; read/write capability r/w; supported modes O/M/A
Statistical information > Drive signal diagram > Hysteresis
Tolerance band of test (d5) (the test is canceled when the value leaves the tolerance band)

78 KH 8384-5 EN
Parameter lists

AO TRD: Y_STAT_TEST_INFO (179)


Storage class D; read capability r
Tests > Drive signal diagram steady (d1 test)
Current test status
AO TRD: Y_STAT_TEST_PROGRESS (180)
Storage class D; read capability r
Tests > Drive signal diagram steady (d1 test)
Current test progress
AO TRD: Y_STAT_TEST_TIME_STAMP (178)
Storage class D; read capability r
Tests > Drive signal diagram steady (d1 test)
Time stamp for reference value recording

Index and parameter assignment: AO TRD


Index Parameters Index Parameters
38 ACT_FAIL_ACTION 138 COUNTER_INIT_START
39 ACT_MAN_ID 63 CUSTOM_CURVE_DESCRIPTION
40 ACT_MODEL_NUM 65 CUSTOM_CURVE_XY_FLOAT
41 ACT_SN 33 CYCLE_CNTR
101 ALARM_OPTION 76 CYCLE_CNTR_LIM
4 ALERT_KEY 173 DEPTXE
147 ANALYSIS_OPEN_CLOSE 174 DEPTXR
144 APPLICATION_TYPE_OC_CONTROL 21 DEVIATION_DEADBAND
175 AUTOMATIC_TEST_STATUS 105 DEVIATION_MAX
111 BINARY_INPUT_2 104 DEVIATION_MIN
124 BLOCKING_POSITION 22 DEVIATION_TIME
8 BLOCK_ALM 23 DEVIATION_VALUE
6 BLOCK_ERR 120 DEVICE_INIT_STATE
91 CHARACTERIZATION 121 DEVICE_STATUS_INIT
61 CLOSED_POS_DEADBAND 132 DIAG_LEVEL
62 CLOSED_POS_SHIFT 176 DIAG_REFLAUF_INFO
121 CLOSING_DIRECTION 142 DIAG_RESET_AFTER_TIME
110 CONFIG_BINARY_INPUT_2 143 DIAG_RESET_AFTER_TIMEOUT

KH 8384-5 EN 79
Parameter lists

Index Parameters Index Parameters


194 DSKV1 16 FINAL_VALUE_CUTOFF_HI
195 DSKV2 123 FINAL_VALUE_CUTOFF_HI_ON
196 DSKV3 17 FINAL_VALUE_CUTOFF_LO
197 DSKV4 122 FINAL_VALUE_CUTOFF_LO_ON
198 DSKW1 49 FINAL_VALUE_D
199 DSKW2 15 FINAL_VALUE_RANGE
200 DSKW3 68 FRICTION
201 DSKW4 265 FRICTION_LIMITS
191 DSXHTW 67 FRICTION_UNITS
182 DSXSTR 86 FST_BREAKOUT_TIME
184 DSXSTW 87 FST_BREAKOUT_TIMEOUT
189 DSYHTR 90 FST_COMPLETION_TIMEOUT
190 DSYHTW 257 FST_DIAGR_E1
157 DSYSK 258 FST_DIAGR_E2
156 DSYSL 259 FST_DIAGR_E3
158 DSYSS 260 FST_DIAGR_E4
181 DSYSTR 245 FST_DIAGR_TIME1
183 DSYSTW 246 FST_DIAGR_TIME2
159 DVPSS 247 FST_DIAGR_TIME3
136 EHM 248 FST_DIAGR_TIME4
168 END_POS_TREND_REF_DRIVE_SIG_ 253 FST_DIAGR_W1
REF 254 FST_DIAGR_W2
167 END_POS_TREND_REF_TIME_REF 255 FST_DIAGR_W3
166 END_POS_TREND_REF_VALUES_REF 256 FST_DIAGR_W4
171 EPTRDS 249 FST_DIAGR_X1
170 EPTRT 250 FST_DIAGR_X2
169 EPTRV 251 FST_DIAGR_X3
139 EVENT_LOGGING_1 252 FST_DIAGR_X4
140 EVENT_LOGGING_2 261 FST_DIAGR_Y1
18 FINAL_POSITION_VALUE 262 FST_DIAGR_Y2
50 FINAL_POSITION_VALUE_D 263 FST_DIAGR_Y3
131 FINAL_POSITION_VALUE_LIMITS 264 FST_DIAGR_Y4
14 FINAL_VALUE

80 KH 8384-5 EN
Parameter lists

Index Parameters Index Parameters


238 FST_DISPLAY 272 LS_ALARM_LIMIT_3
239 FST_MEAS_DATA1 304 LS_ALARM_RELEASE
240 FST_MEAS_DATA2 266 LS_LEAKAGE_LEVEL
241 FST_MEAS_DATA3 268 LS_SELECT_ALARM_LIMITS
88 FST_RAMP_RATE 273 LS_TEST_INFORMATION
237 FST_SETTINGS 107 MIN_CLEARANCE_NEW_
89 FST_STRK_TRAV_TIMEOUT LOGGING_MGV

235 FST_TEST_INFO 5 MODE_BLK

274 FST_TEST_STAT1 137 NO_OF_ZERO_POINT_ADJ

275 FST_TEST_STAT2 119 OPTI_SUB_INIT

276 FST_TEST_STAT3 207 PCC

135 HIST 209 PMD1

150 HISTOGR_X_SCAN_RATE 210 PMD2

149 HISTOGR_X_SHORT 211 PMD3

148 HXL 112 POSITIONER_MODEL

69 HYSTERESIS 24 POS_ALERT_HI

163 HYST_SHORT_DIFF_Y 25 POS_ALERT_LO

164 HYST_VALVE_POS 70 POS_DEADBAND

108 IDENT_OPTIONS 55 POS_FEATURES

116 INIT_METHOD 125 PRESSURE_LIMIT

117 INIT_WITH_REF_TEST 141 PROTOKOLL_BSZ_START

96 INTERNAL_TEMP 203 PST_AUTOSTART_READ

98 INTERNAL_TEMP_MAX 77 PST_BREAKOUT_TIME

97 INTERNAL_TEMP_MIN 78 PST_BREAKOUT_TIMEOUT

99 INTERNAL_TEMP_UNITS 85 PST_COMPLETION_TIMEOUT

127 KP_STEP 227 PST_DIAGR_E1

145 LIMIT_VALUE_TIME_ANALYSIS 228 PST_DIAGR_E2

146 LIMIT_VALUE_TRAVEL_ANALYSIS 229 PST_DIAGR_E3

106 LOGGING_MGV 230 PST_DIAGR_E4

306 LS_ALARM_INFORMATION 215 PST_DIAGR_TIME1

270 LS_ALARM_LIMIT_1 216 PST_DIAGR_TIME2

271 LS_ALARM_LIMIT_2 217 PST_DIAGR_TIME3


218 PST_DIAGR_TIME4

KH 8384-5 EN 81
Parameter lists

Index Parameters Index Parameters


223 PST_DIAGR_W1 34 SIGNAL_ACTION
224 PST_DIAGR_W2 192 SKR
225 PST_DIAGR_W3 193 SKW
226 PST_DIAGR_W4 133 SSAF
219 PST_DIAGR_X1 27 STOP_HI
220 PST_DIAGR_X2 28 STOP_LO
221 PST_DIAGR_X3 129 STOP_LO_POS_ON
222 PST_DIAGR_X4 3 STRATEGY
231 PST_DIAGR_Y1 71 STROKE_TIME_CLOSED
232 PST_DIAGR_Y2 92 STROKE_TIME_CLOS_LIM
233 PST_DIAGR_Y3 72 STROKE_TIME_OPEN
234 PST_DIAGR_Y4 93 STROKE_TIME_OPEN_LIM
208 PST_DISPLAY 113 STR_DEVICE_CHARACTERISTIC
79 PST_INITIAL_START_TIME 1 ST_REV
80 PST_INTERVAL 118 SUB_MOD_INIT
81 PST_OPTIONS 2 TAG_DESC
82 PST_RAMP_RATE 207 THRESHOLD_END_POS_RECORDING
206 PST_SETTINGS 9 TRANSDUCER_DIRECTORY
83 PST_STRK_TRAV 102 TRANSDUCER_STATE
84 PST_STRK_TRAV_TIMEOUT 10 TRANSDUCER_TYPE
202 PST_TESTMODE_TARGET 11 TRANSDUCER_TYPE_VER
204 PST_TEST_INFO 115 TRANSM_PIN_POS
212 PST_TEST_STAT1 29 TRAVEL_ACCUM
213 PST_TEST_STAT2 73 TRAVEL_ACCUM_DEADBAND
214 PST_TEST_STAT3 94 TRAVEL_ACCUM_LIM
26 RATED_TRAVEL 95 TRAVEL_ACCUM_UNITS
35 READBACK_SELECT 30 TRAVEL_UNITS
177 REFLAUF_VOLLST 74 TRIP_TIMEOUT
134 RESET_STATUS_MESSAGE_DIAG 128 TV_STEP
126 SELECT_EMERGENCY_MODE 7 UPDATE_EVT
109 SELO 42 VALVE_MAN_ID
114 SET_FAIL_SAFE_POS 43 VALVE_MODEL_NUM

82 KH 8384-5 EN
Parameter lists

Index Parameters Index Parameters


44 VALVE_SN 37 XD_COMMAND_STATE
45 VALVE_TYPE 12 XD_ERROR
56 VST_COMMAND 103 XD_ERROR_EXT
60 VST_DETAILED_RESULT 32 XD_FSTATE_OPT
57 VST_MODE 31 XD_FSTATE_VAL
58 VST_PAUSE 53 XD_FSTATE_VAL_D
59 VST_RESULT 54 XD_OOS_OPT
19 WORKING_POS 160 Y_HYST_MIN_TIME_DISTANCE
51 WORKING_POS_D 162 Y_HYST_TESTINFO
20 WORKING_SP 186 Y_HYST_TEST_INFO
52 WORKING_SP_D 187 Y_HYST_TEST_PROGRESS
47 XD_CAL_DATE 185 Y_HYST_TEST_TIME_STAMP
46 XD_CAL_LOC 161 Y_HYST_TOLERANCE_BAND
48 XD_CAL_WHO 179 Y_STAT_TEST_INFO
36 XD_COMMAND 180 Y_STAT_TEST_PROGRESS
75 XD_COMMAND_FLAGS 178 Y_STAT_TEST_TIME_STAMP

KH 8384-5 EN 83
Parameter lists

9.2 Analog Output Function Block (AO FB)


AO FB: ALERT_KEY (4)
Storage class S; read/write capability r/w; supported modes O/M/A
ID number of the plant section
• 1 to 255, [0]
May be used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device (error
alarm).
AO FB: BKCAL_OUT (25)
Storage class D; read capability r
Analog output value for upstream block (value and status)
BKCAL_OUT is passed on to the BKCAL_IN parameter of the upstream function block for
cascade control. It prevents integral windup of the controller and thus ensures bumpless
switching between operating modes.
AO FB: BLOCK_ALM (30)
Storage class D; read capability r
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
AO FB: BLOCK_ERR (6)
Storage class D; read capability r
Active block error  Code 48 A8
• OUT OF SERVICE
• CONFIGURATION_ERROR
• INPUT FAILURE PV · Position feedback has bad status e.g. because the Transducer Block
is in the O/S mode.
• OUTPUT FAILURE · OUT value cannot be issued, e.g. because the Transducer Block is not
initialized or in the LO mode.
AO FB: CAS_IN (17)
Storage class N; read/write capability r/w; supported modes ALL
Analog set point, adopted from an upstream function block (value and status)
 Code 48 A2/A3

84 KH 8384-5 EN
Parameter lists

AO FB: CHANNEL (22)


Storage class S; read/write capability r/w; supported modes O
Assignment of the output of AO Function Block and the logical hardware channels
(Transducer Block).
• [3]
Note: Set CHANNEL to 3 to start up the AO Function Block. This allows it to be assigned to
AO TRD.
AO FB: FSTATE_TIME (23)
Storage class S; read/write capability r/w; supported modes ALL
Fault state time [s]
Time between an error in the set point valid for the AO Function Block in the current
operating mode is detected and failure action is triggered.
• [0]
Note: Failure action is triggered if the error persists after this time has elapsed. The fault
state of the AO Function Block is determined in the IO_OPTS parameter of this block.
AO FB: FSTATE_VAL (24)
Storage class S; read/write capability r/w; supported modes ALL
Fault state value for the AO Function Block when failure action is triggered.
• Value and range from PV_SCALE ±10 %, [0]
Note: The value is used if the FAULT STATE TO VALUE option is selected in the IO_OPTS
parameter.
AO FB: GRANT_DENY (13) · This parameter is not supported.

AO FB: IO_OPTS (14)


Storage class S; read/write capability r/w; supported modes O
Selects the input/output behavior of the AO Function Block.
• SP-PV TRACK IN MAN · SP tracks PV in MAN mode (Actual Mode)
• SP-PV TRACK IN LO · SP tracks PV in LO mode (Actual Mode)
• SP TRACK RETAINED TARGET · SP tracks RCAS_IN or CAS_IN depending on the preset
target mode in LO or MAN mode (actual mode). This option has priority over SP-PV
TRACK IN MAN/LO.
• INCREASE TO CLOSE · Inverts the output value to the Transducer Block (corresponds to
the direction of action)

KH 8384-5 EN 85
Parameter lists

• FAULT STATE TO VALUE · FSTATE_VAL is used as the set point when the failure action is
triggered (see FSTATE_VAL, FSTATE_TIME)
• USE FAULT STATE VALUE ON RESTART · FSTATE_VAL is used as the set point upon
restarting until a valid value has been entered.
• TARGET TO MAN IF FAULT STATE ACTIVATED · When failure action is triggered, the
target mode is set to MAN and the original target mode is lost. The block remains in
MAN mode after failure action has been left until the user sets it to the desired operating
mode.
• USE PV FOR BKCAL_OUT · The PV process value is fed back at BKCAL_OUT instead of
the working process value. If the OUT READBACK option is activated in the FEATURES_
SEL Resource Block parameter, BKCAL_OUT feeds back the current valve position.
AO FB: MODE_BLK (5)
Storage class N; read/write capability r/w; supported modes ALL
Operating mode
– Target Mode  Code 48 A0
– Actual Mode (read only)  Code 48 A1
– Permitted Mode
– Normal Mode (read only)
• O/S · The AO Function Block is not executed. The last value or the value determined
during an active fault processing is issued at the OUT parameter.
• MAN · The output value of the AO Function block can be entered manually by the
operator over the OUT parameter.
• AUTO · The set point entered by the operator is used over the SP parameter upon
execution of the AO Function Block.
• CAS · The AO Function Block receives the set point directly from an upstream function
block over the CAS_IN parameter for internal calculation of the out value. The AO
Function Block is implemented.
• RCAS · The AO Function Block receives the set point directly from the fieldbus host
system over the RCAS_IN parameter for internal calculation of the out value. The AO
Function Block is implemented.
AO FB: OUT (9)
Storage class N; read/write capability r/w; supported modes M/O
Out value of the AO Function Block (value, limit and status)  Code 48 A6/7
• Range of OUT_SCALE ±10 %; unit of the XD_SCALE parameter group
Note: The OUT value can be entered manually when the MAN mode is selected in the
MODE_BLK parameter.

86 KH 8384-5 EN
Parameter lists

AO FB: PV (7)
Storage class D; read capability r
Process variable of the function block (value and status)
• Unit from the XD_SCALE parameter group.
Note: If the OUT READBACK option is activated in the FEATURES_SEL resource block
parameter, PV contains the current valve position (corresponding to FINAL_POSITION_
VALUE).
AO FB: PV_SCALE (11)
Storage class S; read/write capability r/w; supported modes O
Range of the process variable (PV) (start, end, unit and decimal point)
• 0 to 100 %
AO FB: RCAS_IN (26)
Storage class N; read/write capability r/w; supported modes ALL
Analog set point for internal calculation of the out value (value and status)
The RCAS_IN value is provided by the fieldbus host system.
Note: This parameter is only active in RCAS mode.
AO FB: RCAS_OUT (28)
Storage class D; read capability r
Analog set point after applying the ramp function (value and status)
The RCAS_OUT value is provided to the fieldbus host system to perform back-calculations
in case of control mode changes or limited signals.
Note: This parameter is only active in RCAS mode.
AO FB: READBACK (16)
Storage class D; read capability r
Current valve position determined from the FINAL_POSITION_VALUE of the associated
Transducer Block
• Unit from the XD_SCALE parameter group.

KH 8384-5 EN 87
Parameter lists

AO FB: SHED_OPT (27)


Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the monitoring time (see SHED_RCAS in the Resource Block)
Monitoring of the connection between fieldbus host system and AO Function Block in RCAS
mode. When the monitoring time has elapsed, AO Function Block switches from the RCAS
mode to the selected operating mode.
The action to be taken after the fault state ends is also determined.
• [UNINITIALIZED]
• NORMAL SHED_NORMAL RETURN · On failure of remote connection, change to next
possible mode until RCAS mode is restored.
• NORMAL SHED_NO RETURN · On failure of remote connection, change to next
possible mode. The block remains in this mode.
• SHED TO AUTO_NORMAL RETURN · On failure of remote connection, change to AUTO
mode until RCAS mode is restored.
• SHED TO AUTO_NO RETURN · On failure of remote connection, change to AUTO
mode. No attempt is made to restore the mode and the block remains in AUTO mode.
• SHED TO MANUAL_NORMAL RETURN · On failure of remote connection, change to
MAN mode until RCAS mode is restored.
• SHED TO MANUAL_NO RETURN · On failure of remote connection, change to MAN
mode. No attempt is made to restore the mode and the block remains in MAN mode.
• SHED TO RETAINED TARGET_ NORMAL RETURN · On failure of remote connection, the
block attempts to attain the retained target mode until RCAS mode is restored.
• SHED TO RETAINED TARGET_NO RETURN · On failure of remote connection, the block
sets the target mode to the retained target mode.
Note: This parameter is only active in RCAS mode in the AO Function Block.
If the value is set to UNINITIALIZED, the AO Function Block cannot be placed in the RCAS
mode.
AO FB: SIMULATE (10)
Storage class D; read/write capability r/w; supported modes ALL
Simulation of the process variable PV of the block (value and status)  Code 48 F3
Note: During simulation, OUT is not transmitted to the Transducer Block; the block retains
the last valid value received before simulation was activated.
The simulation can only be activated when SIMULATE ACTIVE is set in the BLOCK_ERR
parameter of the Resource Block.

88 KH 8384-5 EN
Parameter lists

AO FB: SP (8)
Storage class N; read/write capability r/w; supported modes O/M/A
Set point w in AUTO mode  Code 48 A4/5
• Value and range from PV_SCALE ±10 %; unit of PV_SCALE
AO FB: SP_HI_LIM (20)
Storage class S; read/write capability r/w; supported modes ALL
Upper set point limit
• Value and range from PV_SCALE ±10 %, [100 %]
Note: Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.
AO FB: SP_LO_LIM (21)
Storage class S; read/write capability r/w; supported modes ALL
Lower set point limit
• Value and range from PV_SCALE ±10 %, [0 %]
Note: Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.
AO FB: SP_RATE_DN (18)
Storage class S; read/write capability r/w; supported modes ALL
Set point downward rate limit in AUTO mode
• [3402823466 x 1038]
Note: If '0' is entered, the set point is used.
The speed limitation for output blocks is active in AUTO and CAS modes.
AO FB: SP_RATE_UP (19)
Storage class S; read/write capability r/w; supported modes ALL
Set point upward rate limit in AUTO mode
• [3402823466 x 1038]
Note: If '0' is entered, the set point is used.
The speed limitation for output blocks is active in AUTO and CAS modes.
AO FB: ST_REV (1)
Storage class N; read capability r
Static revision number (AO Function Block)
Note: The revision number is incremented with each change of a static parameter in the
block.

KH 8384-5 EN 89
Parameter lists

AO FB: STATUS_OPTS (15)


Storage class S; read/write capability r/w; supported modes O
Status options to determine status handling and processing
• [UNINITIALIZED]
• PROPAGATE FAULT BACKWARD · Status of the Transducer Block is passed on to the
upstream block over the status of BKCAL_OUT.
AO FB: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes ALL
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note: These data are neither checked nor processed by the AO Function Block.
AO FB: TAG_DESC (2)
Storage class S; read/write capability r/w; supported modes ALL
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
AO FB: UPDATE_EVT (29)
Storage class D; read capability r
Indicates whether static block data have been changed, including date and time stamp
AO FB: XD_SCALE (12)
Storage class S; read/write capability r/w; supported modes O
Range of the OUT value (start, end, unit and decimal point)
• 0.0 to 100.0 %; specified in [%], [mm] or [degrees]
Note: When [%] is used, the OUT value is based on the scale of 100 %. In case of [mm]
(with globe valves) or [degrees] (with rotary valves), the OUT value corresponds to the
value set in the RATED_TRAVEL parameter in the Transducer Block which is scaled as
100 %.

90 KH 8384-5 EN
Parameter lists

Index and parameter assignment: AO Function Block


Index Parameters Index Parameters
1 ST_REV 16 READBACK
2 TAG_DESC 17 CAS_IN
3 STRATEGY 18 SP_RATE_DN
4 ALERT_KEY 19 SP_RATE_UP
5 MODE_BLK 20 SP_HI_LIM
6 BLOCK_ERR 21 SP_LO_LIM
7 PV 22 CHANNEL
8 SP 23 FSTATE_TIME
9 OUT 24 FSTATE_VAL
10 SIMULATE 25 BKCAL_OUT
11 PV_SCALE 26 RCAS_IN
12 XD_SCALE 27 SHED_OPT
13 GRANT_DENY 28 RCAS_OUT
14 IO_OPTS 29 UPDATE_EVT
15 STATUS_OPTS 30 BLOCK_ALM

KH 8384-5 EN 91
Parameter lists

9.3 Analog Input Function Block (AI FB)


AI FB: ACK_OPTION (23)
Read/write capability r/w; supported modes ALL
Automatic alarm acknowledgement (AI Function Block)
• [UNDEFINED] · No selection
• HI_HI_ALM · High-high alarm
• HI_ALM · High pre-alarm
• LO_LO_ALM · Low-low alarm
• LO_ALM · Low pre-alarm
• DV_HI_ALM · Limit alarm for upper set point deviation
• DV_LO_ALM · Limit alarm for lower set point deviation
• BLOCK ALM · Block alarm
Note: The alarm is broadcast to the fieldbus host system, but not acknowledged by it.
AI FB: ALARM_HYS (24)
Read/write capability r/w; supported modes ALL
Hysteresis for the low and high alarm limits
• 0 to 50 %, [0.5 %]
The alarm conditions remain active as long as the measured value remains within the
hysteresis. The hysteresis value has an effect on the following alarm limits of the AI
Function Block:
HI_HI_LIM; HI_LIM; LO_LO_LIM; LO_LIM; DV_HI_LIM; DV_LO_LIM
Note: The hysteresis value is a percentage of the PV_SCALE range in the AI Function Block.
AI FB: ALARM_SUM (22)
Read capability r
Current status of process alarms in the AI Function Block
• HI_HI_ALM · Violation of the high-high alarm
• HI_ALM · Violation of the high pre-alarm
• LO_LO_ALM · Violation of the low-low alarm
• LO_ALM · Violation of the low pre-alarm
• DV_HI_ALM · Violation of the limit alarm for upper set point deviation
• DV_LO_ALM · Violation of the limit alarm for lower set point deviation
• BLOCK ALM · Block alarm
Note: The process alarms can also be deactivated in this parameter group.

92 KH 8384-5 EN
Parameter lists

AI FB: ALERT_KEY (4)


Read/write capability r/w; supported modes ALL
ID number of the plant section
• 1 to 255, [0]
Used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device (error
alarm).
AI FB: BLOCK_ALM (21)
Read capability r
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
AI FB: BLOCK_ERR (6)
Read capability r
Active block error for AI Function Block
• OUT OF SERVICE
• CONFIGURATION_ERROR
AI FB: CHANNEL (15)
Storage class S; read/write capability r/w; supported modes O
Assignment of the output of AI Function Block and the logical hardware channels
(Transducer Block).
• [2]
Note: Set CHANNEL to 2 to start up the AI Function Block. This allows it to be assigned to
AI TRD.
AI FB: FIELD_VAL (19)
Read capability r
Measured value of the Transducer Block in the PV_SCALE unit
AI FB: GRANT_DENY (12) · This parameter is not supported.

AI FB: HI_ALM (34)


Read capability r
Alarm for the high pre-alarm limit (HI_LIM) including details on the date and time as well
as the value at which the alarm is triggered.
• Unit of PV_SCALE

KH 8384-5 EN 93
Parameter lists

AI FB: HI_HI_ALM (33)


Read capability r
Alarm for the high-high alarm limit (HI_HI_LIM) including details on the date and time as
well as the value at which the alarm is triggered.
• Unit of PV_SCALE
Note: Additionally, the active alarm can be confirmed manually in this parameter group.
AI FB: HI_HI_LIM (26)
Read/write capability r/w; supported modes ALL
High-high alarm limit (HI_HI_ALM)
• Range and unit of PV_SCALE
If PV exceeds this limit, the alarm state parameter HI_HI_ALM is issued.
AI FB: HI_HI_PRI (25)
Read/write capability r/w; supported modes ALL
Behavior upon exceeding the high-high alarm limit HI_HI_LIM
• [0] · The violation of the high-high alarm limit is not analyzed.
• 1 · No notification upon violation of the high-high alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the high-high alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the high-high alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
AI FB: HI_LIM (28)
Read/write capability r/w; supported modes ALL
Alarm limit for the high pre-alarm HI_ALM
• Range and unit of PV_SCALE, [3402823466 x 1038]
If PV exceeds this limit, the alarm state parameter HI_ALM is issued.

94 KH 8384-5 EN
Parameter lists

AI FB: HI_PRI (27)


Read/write capability r/w; supported modes ALL
Behavior upon exceeding the high pre-alarm limit HI_LIM
• [0] · The violation of the high pre-alarm limit is not analyzed.
• 1 · No notification upon violation of the high pre-alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the high pre-alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the high pre-alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
AI FB: IO_OPTS (13)
Storage class S; read/write capability r/w; supported modes O
LOW CUTOFF · The output is set to '0' at a value below LOW CUTOFF.
UNITS CONVERSION · Channel value is converted into the XD_SCALE unit.
AI FB: L_TYPE (16)
Storage class S; read/write capability r/w; supported modes M/O
Determines whether the measured values from the AI Function Block can be directly used
(Direct), whether the value exist in different units and must be converted (Indirect) or
whether the square root must be calculated (Ind Sqr Root).
AI FB: LO_ALM (35)
Read capability r
Alarm for the low pre-alarm limit (LO_LIM) including details on the date and time as well
as the value at which the alarm is triggered.
• Unit of PV_SCALE
AI FB: LO_LIM (30)
Read/write capability r/w; supported modes ALL
Alarm limit for the low pre-alarm LO_ALM
• Range and unit of PV_SCALE, [–3402823466 x 1038]
If PV falls below this limit, the alarm state parameter LO_ALM is issued.
AI FB: LO_LO_ALM (36)
Read capability r
Alarm for the low-low alarm limit (LO_LO_LIM) including details on the date and time as
well as the value at which the alarm is triggered.
• Unit of PV_SCALE
Note: Additionally, the active alarm can be confirmed manually in this parameter group.

KH 8384-5 EN 95
Parameter lists

AI FB: LO_LO_LIM (32)


Read/write capability r/w; supported modes ALL
Alarm limit for the low-low alarm LO_LO_ALM
• Range and unit of PV_SCALE, [–3402823466 x 1038]
If PV falls below this limit, the alarm state parameter LO_LO_ALM is issued.
AI FB: LO_LO_PRI (31)
Read/write capability r/w; supported modes ALL
Behavior upon falling below the low-low alarm limit LO_LO_LIM
• [0] · The violation of the low-low alarm limit is not analyzed.
• 1 · No notification upon violation of the low-low alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the low-low alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the low-low alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
AI FB: LO_PRI (29)
Read/write capability r/w; supported modes ALL
Behavior upon falling below the low pre-alarm limit LO_LIM
• [0] · The violation of the low pre-alarm limit is not analyzed.
• 1 · No notification upon violation of the low pre-alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the low pre-alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the low pre-alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
AI FB: LOW_CUT (17)
Storage class S; read/write capability r/w; supported modes ALL
Limit used when the root function is applied.

96 KH 8384-5 EN
Parameter lists

AI FB: MODE_BLK (5)


Storage class S; read/write capability r/w; supported modes ALL
Operating mode of AI Function Block
– Target Mode
– Actual Mode (read only)
– Permitted Mode
– Normal Mode (read only)
• AUTO · The analog input value (FIELD_VAL) is processed by the function block and
issued as OUT.
• MAN · The output value of the AI Function block can be entered manually by the
operator over the OUT parameter.
• O/S · The AI Function Block is not executed. The last value is issued at the output OUT.
AI FB: OUT (8)
Read/write capability r/w; supported modes M
Primary analog value calculated as the result of the function's execution
• Output value in the OUT_SCALE unit
AI FB: OUT_SCALE (11)
Storage class S; read/write capability r/w; supported modes O
Range of the analog OUT value (start, end, unit and decimal point)
• [0 to 100 %]
AI FB: PV (7)
Read capability r
Process variable of the function block (value and status)
• Unit from the XD_SCALE parameter group.
AI FB: PV_FTIME (18)
Storage class S; read/write capability r/w; supported modes ALL
Time constant of a single exponential filter for PV
AI FB: SIMULATE (9)
Read/write capability r/w; supported modes ALL
Simulation · Discrete input value (FIELD_VAL) with status
Note: The simulation can only be activated if it is enabled at the positioner (Code 48 F3)
and in the function block.

KH 8384-5 EN 97
Parameter lists

AI FB: ST_REV (1)


Read capability r
Static revision number (AO Function Block)
Note: The revision number is incremented with each change of a static parameter in the
block.
AI FB: STATUS_OPTS (14)
Storage class S; read/write capability r/w; supported modes ALL
Status options to determine status handling and processing
• PROPAGATE FAULT FORWARD · In the event of sensor failure, the corresponding status
is passed on to the downstream function blocks without generating an alarm.
• UNCERTAIN IF LIMITED · The measured value is set to the UNCERTAIN status if the
measured value is limited.
• BAD IF LIMITED · The measured value is set to the BAD status if the measured value is
limited.
• UNCERTAIN IF MAN MODE · The measured value is set to the UNCERTAIN status if the
mode is set to MAN.
AI FB: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes ALL
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note: These data are neither checked nor processed by the AI Function Block.
AI FB: TAG_DESC (2)
Storage class S; read/write capability r/w; supported modes ALL
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
AI FB: UPDATE_EVT (20)
Read capability r; supported modes ALL
Indicates whether static block data have been changed, including date and time stamp
AI FB: XD_SCALE (10)
Storage class S; read/write capability r/w; supported modes O
Range of the OUT value (start, end, unit and decimal point)
• 0.0 to 100.0 %; specified in [%]

98 KH 8384-5 EN
Parameter lists

Index and parameter assignment: AI Function Block

Index Parameters Index Parameters


1 ST_REV 19 FIELD_VAL
2 TAG_DESC 20 UPDATE_EVT
3 STRATEGY 21 BLOCK_ALM
4 ALERT_KEY 22 ALARM_SUM
5 MODE_BLK 23 ACK_OPTION
6 BLOCK_ERR 24 ALARM_HYS
7 PV 25 HI_HI_PRI
8 OUT 26 HI_HI_LIM
9 SIMULATE 27 HI_PRI
10 XD_SCALE 28 HI_LIM
11 OUT_SCALE 29 LO_PRI
12 GRANT_DENY 30 LO_LIM
13 IO_OPTS 31 LO_LO_PRI
14 STATUS_OPTS 32 LO_LO_LIM
15 CHANNEL 33 HI_HI_ALM
16 L_TYPE 34 HI_ALM
17 LOW_CUT 35 LO_ALM
18 PV_FTIME 36 LO_LO_ALM

KH 8384-5 EN 99
Parameter lists

9.4 Proportional Integral Derivative Function Block (PID)


PID FB: ACK_OPTIONS (46)
Storage class S; read/write capability r/w; supported modes ALL
Automatic alarm acknowledgement (PID Function Block)
• [UNDEFINED] · No selection
• HI_HI_ALM · High-high alarm
• HI_ALM · High pre-alarm
• LO_LO_ALM · Low-low alarm
• LO_ALM · Low pre-alarm
• DV_HI_ALM · Limit alarm for upper set point deviation
• DV_LO_ALM · Limit alarm for lower set point deviation
• BLOCK ALM · Block alarm
Note: The alarm is broadcast to the fieldbus host system, but not acknowledged by it.
PID FB: ALARM_HYS (47)
Storage class S; read/write capability r/w; supported modes ALL
Hysteresis for the high and low alarm limits
• 0 to 50 %, [0.5 %]
The alarm conditions remain active as long as the measured value remains within the
hysteresis. The hysteresis value has an effect on the following alarm limits of the PID
Function Block:
HI_HI_LIM; HI_LIM; LO_LO_LIM; LO_LIM; DV_HI_LIM; DV_LO_LIM
Note: The hysteresis value is a percentage of the PV_SCALE range in the PID Function
Block.
PID FB: ALARM_SUM (45)
Storage class S/D; read/write capability r/w; supported modes ALL
Current status of process alarms in the PID Function Block
• HI_HI_ALM · Violation of the high-high alarm
• HI_ALM · Violation of the high pre-alarm
• LO_LO_ALM · Violation of the low-low alarm
• LO_ALM · Violation of the low pre-alarm
• DV_HI_ALM · Violation of the limit alarm for upper set point deviation
• DV_LO_ALM · Violation of the limit alarm for lower set point deviation
• BLOCK ALM · Block alarm
Note: The process alarms can also be deactivated in this parameter group.

100 KH 8384-5 EN
Parameter lists

PID FB: ALERT_KEY (4)


Storage class S; read/write capability r/w; supported modes ALL
ID number of the plant section
• 1 to 255, [0]
May be used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device (error
alarm).
PID FB: BAL_TIME (25)
Storage class S; read/write capability r/w; supported modes ALL
Integral-action component windup
Time constant to counteract the windup (calculated out value > OUT_HI_LIM or < OUT_
LO_LIM) of the integral-action component.
• [0]
Note: If value is '0', windup is removed immediately.
PID FB: BKCAL_HYS (30)
Storage class S; read/write capability r/w; supported modes ALL
Hysteresis value for out value range limits (OUT_HI_LIM and OUT_LO_LIM)
• 0 to 50 %, [0.5 %]
If the calculated out value violates the range defined by the limits, the violation is indicated
in the OUT parameter and passed on to the following blocks.
The range violation remains active as long as the calculated out value does not exceed or
fall below the hysteresis value.
PID FB: BKCAL_IN (27)
Storage class N; read/write capability r/w; supported modes ALL
Analog input value (value and status)
BKCAL_IN is adopted by the BKCAL_OUT parameter of the downstream function block for
cascade control. This value ensures bumpless switching between operating modes by
tracking the output.
PID FB: BKCAL_OUT (31)
Storage class D; read capability r
Analog output value (value and status)
BKCAL_OUT is passed on to the BKCAL_IN parameter of the upstream function block for
cascade control. It prevents integral windup of the controller and thus ensures bumpless
switching between operating modes.

KH 8384-5 EN 101
Parameter lists

PID FB: BLOCK_ALM (44)


Storage class D; read/write capability r/w; supported modes ALL
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
PID FB: BLOCK_ERR (6)
Storage class D; read capability r
Active block error  Code 48 P8
• OUT OF SERVICE · Block mode is out of service
• CONFIGURATION ERROR
PID FB: BYPASS (17)
Storage class S; read/write capability r/w; supported modes M/O
Activates calculation of the out value through the PID control algorithm
• UNINITIALIZED · Same as ON
• [OFF] · Bypass deactivated: the out value determined by the PID control algorithm is
issued over the OUT parameter.
• ON · Bypass activated: the value of the set point SP is issued directly over the OUT
parameter.
Note: UNINITIALIZED causes the function block to remain in O/S mode. To activate the
bypass (ON setting), the bypass must be enabled in the control options (CONTROL_OPTS
parameter).
PID FB: CAS_IN (18)
Storage class N; read/write capability r/w; supported modes ALL
Analog set point (value and status)  Code 48 P2/3
CAS_IN is adopted from an upstream function block.
PID FB: CONTROL_OPTS (13)
Storage class S; read/write capability r/w; supported modes O
Control options to determine the automation strategy
• [NONE]
• BYPASS ENABLE
• DIRECT ACTING
• TRACK ENABLE · Tracking enabled
• TRACK IN MANUAL · Tracking in MAN mode
• PV FOR BKCAL_OUT · Value and status of PV used for BKCAL_OUT
• NO OUT LIMITS IN MANUAL · No output limits in MAN mode

102 KH 8384-5 EN
Parameter lists

PID FB: DV_HI_ALM (64)


Storage class D; read/write capability r/w; supported modes ALL
Alarm for the upper set point deviation (DV_HI_LIM) including details on the date and time
as well as the value at which the alarm is triggered.
Note: Additionally, the active alarm can be confirmed manually in this parameter group.
PID FB: DV_HI_LIM (57)
Storage class S; read/write capability r/w; supported modes ALL
Limit for the upper set point deviation
• [3402823466 x 1038]
If the controlled variable exceeds the set point by this value, the pre-alarm DV_HI_ALM is
issued.
PID FB: DV_HI_PRI (56)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the upper set point deviation (DV_HI_LIM)
• [0] · The violation of the limit for the upper set point deviation is not analyzed.
• 1 · No notification upon violation of the limit for the upper set point deviation
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the limit for the upper set point deviation is issued to notify the
operator with the corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the limit for the upper set point deviation is issued as a critical
alarm with the corresponding priority: (8 = low, 15 = high)
PID FB: DV_LO_ALM (65)
Storage class D; read capability r
Alarm for the lower set point deviation (DV_LO_LIM) including details on the date and time
as well as the value at which the alarm is triggered.
Note: Additionally, the active alarm can be confirmed manually in this parameter group.
PID FB: DV_LO_LIM (59)
Storage class S; read/write capability r/w; supported modes ALL
Limit for the lower set point deviation
• [–3402823466 x 1038]
If the controlled variable is smaller than the set point by this value, the pre-alarm DV_LO_
ALM is issued.

KH 8384-5 EN 103
Parameter lists

PID FB: DV_LO_PRI (58)


Storage class S; read/write capability r/w; supported modes ALL
Behavior upon falling below the lower set point deviation (DV_LO_LIM)
• [0] · The violation of the limit for the lower set point deviation is not analyzed.
• 1 · No notification upon violation of the limit for the lower set point deviation
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the limit for the lower set point deviation is issued to notify the
operator with the corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the limit for the lower set point deviation is issued as a critical
alarm with the corresponding priority: (8 = low, 15 = high)
PID FB: FF_GAIN (42)
Storage class S; read/write capability r/w; supported modes M/O
Feedforward gain
• [0]
Note: The feedforward gain is multiplied with the input value (FF_VAL). The result is added
to the OUT value.
PID FB: FF_SCALE (41)
Storage class S; read/write capability r/w; supported modes M/O
Measuring range of FF_VAL input value (lower and upper limits, unit and decimal point)
• [0 to 100 %]
PID FB: FF_VAL (40)
Storage class N; read/write capability r/w; supported modes ALL
Feedforward control input value (value and status)
• Range and unit of FF_SCALE
Note: The input value is multiplied with the feedward gain FF_GAIN. The result is added to
the OUT value.
PID FB: GAIN (23)
Storage class S; read/write capability r/w; supported modes ALL
Proportional-action coefficient
• [1.0]
Note: The parameter must be set to a value not equal to 0; otherwise, a configuration
error is set in the BLOCK_ERR parameter and the block is set to 'Out of service' (O/S)
mode.
PID FB: GRANT_DENY (12) · This parameter is not supported.

104 KH 8384-5 EN
Parameter lists

PID FB: HI_ALM (61)


Storage class D; read capability r
Alarm for the high pre-alarm limit (HI_LIM) including details on the date and time as well
as the value at which the alarm is triggered.
• Unit of PV_SCALE
PID FB: HI_HI_ALM (60)
Storage class D; read/write capability r/w
Alarm for the high-high alarm limit (HI_HI_LIM) including details on the date and time as
well as the value at which the alarm is triggered.
• Unit of PV_SCALE
Note: Additionally, the active alarm can be confirmed manually in this parameter group.
PID FB: HI_HI_LIM (49)
Storage class S; read/write capability r/w; supported modes ALL
High-high alarm limit (HI_HI_ALM)
• Range and unit of PV_SCALE, [3402823466 x 1038]
If PV exceeds this limit, the alarm state parameter HI_HI_ALM is issued.
PID FB: HI_HI_PRI (48)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the high-high alarm limit HI_HI_LIM
• [0] · The violation of the high-high alarm limit is not analyzed.
• 1 · No notification upon violation of the high-high alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the high-high alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the high-high alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
PID FB: HI_LIM (51)
Storage class S; read/write capability r/w; supported modes ALL
Alarm limit for the high pre-alarm HI_ALM
• Range and unit of PV_SCALE, [3402823466 x 1038]
If PV exceeds this limit, the alarm state parameter HI_ALM is issued.

KH 8384-5 EN 105
Parameter lists

PID FB: HI_PRI (50)


Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the high pre-alarm limit HI_LIM
• [0] · The violation of the high pre-alarm limit is not analyzed.
• 1 · No notification upon violation of the high pre-alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the high pre-alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the high pre-alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
PID FB: IN (15)
Storage class N; read/write capability r/w; supported modes ALL
Analog controlled variable x (value and status)
PID FB: LO_ALM (62)
Storage class D; read capability r
Alarm for the low pre-alarm limit (LO_LIM) including details on the date and time as well
as the value at which the alarm is triggered.
• Unit of PV_SCALE
PID FB: LO_LIM (53)
Storage class S; read/write capability r/w
Alarm limit for the low pre-alarm LO_ALM
• Range and unit of PV_SCALE, [–3402823466 x 1038]
If PV falls below this limit, the alarm state parameter LO_ALM is issued.
PID FB: LO_LO_ALM (63)
Storage class D; read capability r
Alarm for the low-low alarm limit (LO_LO_LIM) including details on the date and time as
well as the value at which the alarm is triggered.
• Unit of PV_SCALE
Note: Additionally, the active alarm can be confirmed manually in this parameter group.
PID FB: LO_LO_LIM (55)
Storage class S; read/write capability r/w; supported modes ALL
Alarm limit for the low-low alarm LO_LO_ALM
• Range and unit of PV_SCALE, [–3402823466 x 1038]
If PV falls below this limit, the alarm state parameter LO_LO_ALM is issued.

106 KH 8384-5 EN
Parameter lists

PID FB: LO_LO_PRI (54)


Storage class S; read/write capability r/w; supported modes ALL
Behavior upon falling below the low-low alarm limit LO_LO_LIM
• [0] · The violation of the low-low alarm limit is not analyzed.
• 1 · No notification upon violation of the low-low alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the low-low alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the low-low alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
PID FB: LO_PRI (52)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon falling below the low pre-alarm limit LO_LIM
• [0] · The violation of the low pre-alarm limit is not analyzed.
• 1 · No notification upon violation of the low pre-alarm limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the low pre-alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
• 8 to 15 · The violation of the low pre-alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)

KH 8384-5 EN 107
Parameter lists

PID FB: MODE_BLK (5)


Storage class S; read/write capability r/w; supported modes ALL
Operating mode
– Target Mode  Code 48 P0
– Actual Mode (read only)  Code 48 P1
– Permitted Mode
– Normal Mode (read only)
• O/S · The PID algorithm of the block is not executed. The last value or the determined
value during an active fault processing is issued at the OUT parameter.
• MAN · The output value of the function block can be entered manually by the operator
over the OUT parameter.
• AUTO · The set point entered by the operator is used over the SP parameter upon
execution of the PID Function Block.
• CAS · The PID Function Block receives the set point directly from an upstream function
block over the CAS_IN parameter for internal calculation of the out value. The PID
Function Block is implemented.
• RCAS · The PID Function Block receives the set point directly from the fieldbus host
system over the RCAS_IN parameter for internal calculation of the out value. The PID
Function Block is implemented.
• ROUT · The PID Function Block receives the out value directly from the fieldbus host
system over the ROUT_IN parameter. The out value is issued again over the OUT
parameter without the internal PID algorithm being executed.
PID FB: OUT (9)
Storage class S; read/write capability r/w; supported modes O/M
Out value of the PID Function Block (value, limit and status)  Code 48 P6/7
• Range OUT_SCALE ±10 %, unit of XD_SCALE
Note: The OUT value can be entered manually when the MAN mode is selected in the
MODE_BLK parameter.
PID FB: OUT_HI_LIM (28)
Storage class S; read/write capability r/w; supported modes ALL
Upper limit for analog OUT value
• Range OUT_SCALE ±10 %, unit of OUT_SCALE, [100]
PID FB: OUT_LO_LIM (29)
Storage class S; read/write capability r/w; supported modes ALL
Lower limit for analog OUT value
• Range OUT_SCALE ±10 %, unit of OUT_SCALE, [0]

108 KH 8384-5 EN
Parameter lists

PID FB: OUT_SCALE (11)


Storage class S; read/write capability r/w; supported modes O
Range of the analog OUT value (start, end, unit and decimal point)
• [0 to 100 %]
PID FB: PV (7)
Storage class D; read capability r
Process variable for block execution (value and status)
• Unit of PV_SCALE
PID FB: PV_FTIME (16)
Storage class S; read/write capability r/w; supported modes ALL
Filter time constant [s] of the first-order digital filter
• [0]
This time is required for 63 % of a change in the controlled variable at input IN to take
effect in the value of PV.
PID FB: PV_SCALE (10)
Storage class S; read/write capability r/w; supported modes O
Range of the process variable (PV) (start, end, unit and decimal point)
• [0 to 100 %]
PID FB: RATE (26)
Storage class S; read/write capability r/w; supported modes ALL
Time constant [s] for differential function
• [0]
PID FB: RCAS_IN (32)
Storage class N; read/write capability r/w; supported modes ALL
Analog set point for internal calculation of the out value (value and status)
RCAS_IN is provided by the fieldbus host system.
Note: This parameter is only active in RCAS mode.
PID FB: RCAS_OUT (35)
Storage class D; read capability r
Analog set point after applying the ramp function (value and status)
RCAS_OUT value is provided to the fieldbus host system to perform back-calculations in
case of control mode changes or limited signals.
Note: This parameter is only active in RCAS mode.

KH 8384-5 EN 109
Parameter lists

PID FB: RESET (24)


Storage class S; read/write capability r/w
Time constant for integral function
• [3402823466 x 1038] (maximum possible value)
Note: The cold start value or '0' switches off the integral function.
PID FB: ROUT_IN (33)
Storage class N; read/write capability r/w; supported modes ALL
Out value (value and status)
ROUT_IN is provided by the fieldbus host system.
Note: This parameter is only active in ROUT mode.
PID FB: ROUT_OUT (36)
Storage class D; read capability r
Analog set point (value and status) read over the ROUT_IN parameter
ROUT_OUT value is provided to the fieldbus host system to perform back-calculations in
case of control mode changes or limited signals.
Note: This parameter is only active in ROUT mode.
PID FB: SHED_OPT (34)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the monitoring time (SHED_RCAS parameter in the RES block)
while checking the connection between the fieldbus host system and the PID Function Block
in RCAS or ROUT.
When the monitoring time has elapsed, PID Function Block switches from RCAS or ROUT
to the selected operating mode. The action to be taken after the fault state ends is also
determined.
• [UNINITIALIZED]
• NORMAL SHED_NORMAL RETURN · On failure of remote connection, change to next
possible mode until RCAS or ROUT mode is restored.
• NORMAL SHED_NO RETURN · On failure of remote connection, change to next
possible mode. The block remains in this mode.

110 KH 8384-5 EN
Parameter lists

• SHED TO AUTO_NORMAL RETURN · On failure of remote connection, change to AUTO


mode until RCAS or ROUT mode is restored.
• SHED TO AUTO_NO RETURN · On failure of remote connection, change to AUTO
mode. No attempt is made to restore the mode and the block remains in AUTO mode.
• SHED TO MANUAL_NORMAL RETURN · On failure of remote connection, change to
MAN mode until RCAS or ROUT mode is restored.
• SHED TO MANUAL_NO RETURN · On failure of remote connection, change to MAN
mode. No attempt is made to restore the mode and the block remains in MAN mode.
• SHED TO RETAINED TARGET_ NORMAL RETURN · On failure of remote connection, the
block attempts to attain the retained target mode until RCAS or ROUT mode is restored.
• SHED TO RETAINED TARGET_NO RETURN · On failure of remote connection, the block
sets the target mode to the retained target mode.
Note: This parameter is only active in RCAS and ROUT modes in the PID Function Block. If
the value is set to UNINITIALIZED, the PID Function Block cannot be placed in the RCAS or
ROUT mode.
PID FB: SP (8)
Storage class N; read/write capability r/w; supported modes O/M/A
Set point w in AUTO mode (value and status)  Code 48 P4/5
• Value and range from PV_SCALE ±10 %
PID FB: SP_HI_LIM (21)
Storage class S; read/write capability r/w; supported modes ALL
Upper set point limit
• Value and range from PV_SCALE ±10 %, [100]
Note: Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.
PID FB: SP_LO_LIM (22)
Storage class S; read/write capability r/w; supported modes ALL
Lower set point limit
• Value and range from PV_SCALE ±10 %, [0]
Note: Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.

KH 8384-5 EN 111
Parameter lists

PID FB: SP_RATE_DN (19)


Storage class S; read/write capability r/w; supported modes ALL
Set point downward rate limit in AUTO mode
• [3402823466 x 1038]
Note: if '0' is entered, the set point is used. Speed limitation for control blocks is only
active in AUTO mode.
PID FB: SP_RATE_UP (20)
Storage class S; read/write capability r/w; supported modes ALL
Set point upward rate limit in AUTO mode
• [3402823466 x 1038]
Note: if '0' is entered, the set point is used. Speed limitation for control blocks is only
active in AUTO mode.
PID FB: ST_REV (1)
Storage class S; read capability r
Static revision number (PID)
Note: The revision number is incremented with each change of a static parameter in the
block.
PID FB: STATUS_OPTS (14)
Storage class S; read/write capability r/w; supported modes O
Status options to determine status handling and processing
• [UNINITIALIZED]
• IFS IF BAD IN · Fault state of the downstream AO Function Block is triggered when the
controlled variable IN changes the status to BAD.
• IFS IF BAD CAS_IN · Fault state of the downstream AO Function Block is triggered when
the external set point CAS_IN changes the status to BAD.
• USE UNCERTAIN AS GOOD · The UNCERTAIN status is used as GOOD
• TARGET IN MANUAL IF BAD IN · Transition to MAN mode if the controlled variable
changes the status to BAD
PID FB: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes ALL
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note: These data are neither checked nor processed by the PID Function Block.

112 KH 8384-5 EN
Parameter lists

PID FB: TAG_DESC (2)


Storage class S; read/write capability r/w; supported modes ALL
User-specific text for identification and assignment of the block
• Max. 32 characters, [no text]
PID FB: TRK_IN_D (38)
Storage class N; read/write capability r/w; supported modes ALL
Discrete input that activates external output tracking (value and status)
Mode is changed to LO after tracking has been activated. The output value at OUT
assumes the value defined by the TRK_VAL input.
PID FB: TRK_SCALE (37)
Storage class S; read/write capability r/w; supported modes O/M
Range for external tracking value (TRK_VAL) (start, end, unit and decimal point)
• [0 to 100 %]
PID FB: TRK_VAL (39)
Storage class N; read/write capability r/w; supported modes ALL
Analog input for external tracking (value and status)
TRK_VAL is read from another function block.
PID FB: UPDATE_EVT (43)
Storage class D; read capability r
Indicates whether static data have been changed, including date and time stamp.

KH 8384-5 EN 113
Parameter lists

Index and parameter assignment: PID Function Block

Index Parameters Index Parameters


0 – 31 BKCAL_OUT
1 ST_REV 32 RCAS_IN
2 TAG_DESC 33 ROUT_IN
3 STRATEGY 34 SHED_OPT
4 ALERT_KEY 35 RCAS_OUT
5 MODE_BLK 36 ROUT_OUT
6 BLOCK_ERR 37 TRK_SCALE
7 PV 38 TRK_IN_D
8 SP 39 TRK_VAL
9 OUT 40 FF_VAL
10 PV_SCALE 41 FF_SCALE
11 OUT_SCALE 42 FF_GAIN
12 GRANT_DENY 43 UPDATE_EVT
13 CONTROL_OPTS 44 BLOCK_ALM
14 STATUS_OPTS 45 ALARM_SUM
15 IN 46 ACK_OPTIONS
16 PV_FTIME 47 ALARM_HYS
17 BYPASS 48 HI_HI_PRI
18 CAS_IN 49 HI_HI_LIM
19 SP_RATE_DN 50 HI_PRI
20 SP_RATE_UP 51 HI_LIM
21 SP_HI_LIM 52 LO_PRI
22 SP_LO_LIM 53 LO_LIM
23 GAIN 54 LO_LO_PRI
24 RESET 55 LO_LO_LIM
25 BAL_TIME 56 DV_HI_PRI
26 RATE 57 DV_HI_LIM
27 BKCAL_IN 58 DV_LO_PRI
28 OUT_HI_LIM 59 DV_LO_LIM
29 OUT_LO_LIM 60 HI_HI_ALM
30 BKCAL_HYS 61 HI_ALM

114 KH 8384-5 EN
Parameter lists

Index Parameters Index Parameters


62 LO_ALM 64 DV_HI_ALM
63 LO_LO_ALM 65 DV_LO_ALM

KH 8384-5 EN 115
Parameter lists

9.5 Discrete Output Function Block (DO FB)


DO FB: ALERT_KEY (4)
Storage class S; read/write capability r/w; supported modes ALL
ID number of the plant section
• 1 to 255, [0]
Used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device
(error alarm).
DO FB: BKCAL_OUT_D (21)
Storage class D; read capability r
Discrete output value for upstream block (value and status)
BKCAL_OUT_D is passed on to the BKCAL_IN parameter of the upstream function block
for cascade control. It prevents integral windup of the controller and thus ensures
bumpless switching between operating modes.
DO FB: BLOCK_ALM (26)
Storage class D; read capability r
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
DO FB: BLOCK_ERR (6)
Storage class D; read capability r
Active block error Code 48 A8
• OUT OF SERVICE
• CONFIGURATION_ERROR
DO FB: CAS_IN_D (17)
Storage class N; read/write capability r/w; supported modes ALL
Discrete set point from upstream function block (value and status)
DO FB: CHANNEL (18)
Storage class S; read/write capability r/w; supported modes O
Assignment of the output of DO Function Block and the logical hardware channels
(Transducer Block).
• [6] in DO1 FB and [7] in DO2 FB
Note: Set CHANNEL to 6 to start up the DO1 Function Block. This allows it to be assigned
to DO1 TRD. Set CHANNEL to 7 to start up the DO2 Function Block. This allows it to be
assigned to DO2 TRD.

116 KH 8384-5 EN
Parameter lists

DO FB: FSTATE_TIME (19)


Storage class S; read/write capability r/w; supported modes ALL
Fault state time [s]
Time between an error in the set point valid for the DO Function Block in the current
operating mode is detected and failure action is triggered.
• [0]
Note: Failure action is triggered if the error persists after this time has elapsed.
The fault state of the DO Function Block is determined in the IO_OPTS parameter of this
block.
DO FB: FSTATE_VAL_D (20)
Storage class S; read/write capability r/w; supported modes ALL
Fault state value for the DO Function Block when failure action is triggered.
• Value and range from PV_SCALE ±10 %, [0]
Note: The value is used if the FAULT STATE TO VALUE option is selected in the IO_OPTS
parameter.
DO FB: GRANT_DENY (13) · This parameter is not supported.

DO FB: IO_OPTS (14)


Storage class S; read/write capability r/w; supported modes O
Selects the input/output behavior of the DO Function Block.
• INVERTIERT · Inversion of SP_D
• SP-PV TRACK IN MAN · SP tracks PV in MAN mode (Actual Mode)
• SP-PV TRACK IN LO · SP tracks PV in LO mode (Actual Mode)
• SP TRACK RETAINED TARGET · SP tracks RCAS_IN or CAS_IN depending on the preset
target mode in LO or MAN mode (actual mode). This option has priority over SP-PV
TRACK IN MAN/LO.
• FAULT STATE TO VALUE · FSTATE_VAL_D is used as the set point when the failure action
is triggered (see FSTATE_VAL_D, FSTATE_TIME)
• USE FAULT STATE VALUE ON RESTART · FSTATE_VAL_D is used as the set point upon
restarting until a valid value has been entered.
• TARGET TO MAN IF FAULT STATE ACTIVATED · When failure action is triggered, the
target mode is set to MAN and the original target mode is lost. The block remains in
MAN mode after failure action has been left until the user sets it to the desired
operating mode.
• USE PV FOR BKCAL_OUT · The PV_D process value is fed back at BKCAL_OUT instead
of the working process value.

KH 8384-5 EN 117
Parameter lists

DO FB: MODE_BLK (5)


Storage class N; read/write capability r/w; supported modes ALL
Operating mode of DO Function Block
– Target Mode
– Actual Mode (read only)
– Permitted Mode
– Normal Mode (read only)
• AUTO · The discrete set point entered by the operator is used over the SP_D parameter
upon execution of the DO Function Block.
• MAN · The discrete output value of the DO Function Block can be entered manually by
the operator over the OUT_D parameter.
• CAS · The DO Function Block receives the discrete set point directly from an upstream
function block over the CAS_IN_D parameter for internal processing of the out value.
The DO Function Block is implemented.
• RCAS · The DO Function Block receives the discrete set point directly from the fieldbus
host system over the RCAS_IN_D parameter for internal processing of the out value. The
DO Function Block is implemented.
• O/S · The DO Function Block is not executed. The last value or the determined value
during an active fault processing is issued at the OUT_D parameter.
DO FB: OUT_D (9)
Storage class S; read/write capability r/w; supported modes O/M
Out value of the DO Function Block (value, limit and status)
• Range of OUT_SCALE ±10 %; unit of the XD_SCALE parameter group
Note: The OUT value can be entered manually when the MAN mode is selected in the
MODE_BLK parameter.
DO FB: PV_D (7)
Storage class D; read capability r
Discrete process variable used to execute the module (value and status)
DO FB: PV_STATE (11)
Storage class S; read/write capability r/w; supported modes ALL
Status of PV_D and SP_D parameters
DO FB: RCAS_IN_D (22)
Storage class N; read/write capability r/w; supported modes ALL
Discrete set point for internal calculation of the out value (value and status)
RCAS_IN_D value is provided by the fieldbus host system.
Note: This parameter is only active in RCAS mode.

118 KH 8384-5 EN
Parameter lists

DO FB: RCAS_OUT_D (24)


Storage class D; read capability r
Discrete set point after applying the ramp function (value and status)
The RCAS_OUT_D value is provided to the fieldbus host system to perform back-
calculations in case of control mode changes or limited signals.
Note: This parameter is only active in RCAS mode.
DO FB: READBACK_D (16)
Storage class D; read capability r
Current discrete valve position
• 0: 0 %1: 100 %
• 2: Intermediate position (0.5 % < x < 99.5 %)
DO FB: SHED_OPT (23)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the monitoring time (see SHED_RCAS in the Resource Block)
Monitoring of the connection between fieldbus host system and DO Function Block in
RCAS mode. When the monitoring time has elapsed, DO Function Block switches from the
RCAS mode to the selected operating mode.
The action to be taken after the fault state ends is also determined.
• [UNINITIALIZED]
• NORMAL SHED_NORMAL RETURN · On failure of remote connection, change to next
possible mode until RCAS mode is restored.
• NORMAL SHED_NO RETURN · On failure of remote connection, change to next
possible mode. The block remains in this mode.
• SHED TO AUTO_NORMAL RETURN · On failure of remote connection, change to
AUTO mode until RCAS mode is restored.
• SHED TO AUTO_NO RETURN · On failure of remote connection, change to AUTO
mode. No attempt is made to restore the mode and the block remains in AUTO mode.
• SHED TO MANUAL_NORMAL RETURN · On failure of remote connection, change to
MAN mode until RCAS mode is restored.
• SHED TO MANUAL_NO RETURN · On failure of remote connection, change to MAN
mode. No attempt is made to restore the mode and the block remains in MAN mode.
• SHED TO RETAINED TARGET_ NORMAL RETURN · On failure of remote connection,
the block attempts to attain the retained target mode until RCAS mode is restored.
• SHED TO RETAINED TARGET_NO RETURN · On failure of remote connection, the block
sets the target mode to the retained target mode.
Note: This parameter is only active in RCAS mode in the DO Function Block.
If the value is set to UNINITIALIZED, the DO Function Block cannot be placed in the RCAS
mode.

KH 8384-5 EN 119
Parameter lists

DO FB: SIMULATE_D (10)


Storage class D; read/write capability r/w; supported modes ALL
Simulation of the process variable PV_D of the block (value and status)
Note: During simulation, OUT_D is not transmitted to the Transducer Block; the block
retains the last valid value received before simulation was activated. The simulation can
only be activated when SIMULATE ACTIVE is set in the BLOCK_ERR parameter of the
Resource Block.
DO FB: SP_D (8)
Storage class N; read/write capability r/w; supported modes O/M/A
Discrete set point (reference variable) in AUTO mode
DO FB: ST_REV (1)
Storage class N; read capability r
Static revision number
Note: The revision number is incremented with each change of a static parameter in the
block.
DO FB: STATUS_OPTS (15)
Storage class S; read/write capability r/w; supported modes O
Options for status handling
• UNCERTAIN as GOOD · The status of OUT is set to GOOD if the status of the input
value IN_x is UNCERTAIN.
• UNCERTAIN IF MAN MODE · The status of OUT is set to UNCERTAIN if the actual
mode is set to MAN.
DO FB: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes ALL
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note: These data are neither checked nor processed by the DO Function Block.
DO FB: TAG_DESC (2)
Storage class S; read/write capability r/w; supported modes ALL
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]

120 KH 8384-5 EN
Parameter lists

DO FB: UPDATE_EVT (25)


Storage class D; read capability r
Indicates whether static block data have been changed, including date and time stamp
DO FB: XD_STATE (12)
Storage class S; read/write capability r/w; supported modes ALL
Status of OUT_D and READBACK_D parameters

Index and parameter assignment: DO Function Block

Index Parameters Index Parameters


0 – 14 IO_OPTS
1 ST_REV 15 STATUS_OPTS
2 TAG_DESC 16 READBACK_D
3 STRATEGY 17 CAS_IN_D
4 ALERT_KEY 18 CHANNEL
5 MODE_BLK 19 FSTATE_TIME
6 BLOCK_ERR 20 FSTATE_VAL_D
7 PV_D 21 BKCAL_OUT_D
8 SP_D 22 RCAS_IN_D
9 OUT_D 23 SHED_OPT
10 SIMULATE_D 24 RCAS_OUT_D
11 PV_STATE 25 UPDATE_EVT
12 XD_STATE 26 BLOCK_ALM
13 GRANT_DENY

KH 8384-5 EN 121
Parameter lists

9.6 Discrete Input Function Block (DI1 FB + DI2 FB)


DI FB: ACK_OPTIONS (21)
Storage class S; read/write capability r/w; supported modes O/M/A
Automatic alarm acknowledgement (DI Function Block)
• [UNDEFINED] · No selection
• BLOCK ALM · Block alarm
• DISC ALM · Write protection was changed
Note: The alarm is broadcast to the fieldbus host system, but not acknowledged by it.
DI FB: ALARM_SUM (20)
Storage class S/D; read/write capability r/w; supported modes O/M/A
Current status of process alarms in the DI Function Block
• BLOCK ALM · Block alarm
• DISC ALM · Write protection was changed
Note: The process alarms can also be deactivated in this parameter group.
DI FB: ALERT_KEY (4)
Storage class S; read/write capability r/w; supported modes O/M/A
ID number of the plant section
• 1 to 255, [0]
Used by the fieldbus host system to sort alarms and events.
Note: '0' is not permissible and will be rejected when transferring data to the device (error
alarm).
DI FB: BLOCK_ALM (19)
Storage class D; read capability r
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
DI FB: BLOCK_ERR (6)
Storage class D; read capability r
Active block error Code 48 I6 for DI1, Code 48 L6 for DI2
• OUT OF SERVICE
• CONFIGURATION_ERROR

122 KH 8384-5 EN
Parameter lists

DI FB: CHANNEL (15)


Storage class S; read/write capability r/w; supported modes O
Assignment of the output of DI Function Block and the logical hardware channels (Transducer
Block) [1] in DI1 Function Block and [2] in DI2 Function Block
Note: Set CHANNEL to 1 to start up the DI1 Function Block. This allows it to be assigned to
DI1 TRD. Set CHANNEL to 2 to start up the DI2 Function Block. This allows it to be assigned
to DI2 TRD.
DI FB: DISC_ALM (24)
Storage class D; read capability r
Discrete alarm (status, time and date of alarm, value that triggered the alarm)
The value entered in DISC_LIM parameter is exceeded.
Note: Additionally, the active alarm can be confirmed manually in this parameter group.
DI FB: DISC_LIM (23)
Storage class S; read/write capability r/w; supported modes O/M/A
Limit for discrete alarm
• [0], 1
DI FB: DISC_PRI (22)
Storage class S; read/write capability r/w; supported modes O/M/A
Alarm configuration (behavior on reaching the DISC_LIM limit)
• [0] · The violation of the limit is not analyzed.
• 1 · No notification upon violation of the limit
• 2 · Reserved for block alarms
• 3 to 7 · The violation of the limit is issued to notify the operator with the corresponding
priority: (3 = low, 7 = high)
DI FB: FIELD_VAL_D (17)
Storage class N; read capability r
Discrete input variable of the DI Function Block (value and status)  Code 48 I2/3 for DI1,
Code 48 L2/3 for DI2
DI FB: GRANT_DENY (12) · This parameter is not supported.

DI FB: IO_OPTS (13)


Storage class S; read/write capability r/w; supported modes O
Selects the input/output behavior of the DI Function Block.
• INVERT · Sets a logic NOT operation between the input FIELD_VAL_D and output OUT_D.

KH 8384-5 EN 123
Parameter lists

DI FB: MODE_BLK (5)


Storage class N; read/write capability r/w; supported modes O/M/A
Operating mode
– Target Mode (Code 48 t4 for DI1  Code 48 t7 for DI2)
– Actual Mode (read only)
– Permitted Mode
– Normal Mode (read only)
• O/S · The DI Function Block is not executed. The last value is issued at the output OUT_D.
• MAN · The output value of the DI Function Block can be entered manually by the operator
over the OUT_D parameter.
• AUTO · The binary input value (FIELD_VAL_D) is processed by the function block and
issued as OUT_D.
DI FB: OUT_D (8)
Storage class S; read/write capability r/w; supported modes O/M
Discrete output variable (value and status)  Code 48 I4/5 for DI1  Code 48 L4/5 for
DI2
DI FB: PV_D (7)
Storage class D; read capability r
Indicates the discrete state (including status) used for the function block.
Note: In AUTO mode, the PV_D parameter is identical with output OUT_D.
DI FB: PV_FTIME (16)
Storage class S; read/write capability r/w; supported modes O/M/A
Filter time constant [s] of the digital filter until a binary state at the input of the function block
is adopted in the PV_D parameter.
• [0]
DI FB: SIMULATE_D (9)
Storage class S; read/write capability r/w; supported modes O/M/A
Simulation: Input of the discrete input value (FIELD_VAL_D) with status
Note: The simulation can only be activated if it is enabled at the positioner (Code 48 F3)
and in the function block.

124 KH 8384-5 EN
Parameter lists

DI FB: STATUS_OPTS (14)


Storage class S; read/write capability r/w; supported modes O
Status options to determine status handling and processing
• [UNINITIALIZED]
• PROPAGATE FAIL FWD · Fault state is passed on to the downstream block
DI FB: STRATEGY (3)
Storage class S; read/write capability r/w; supported modes O/M/A
Permits strategic grouping and thus faster processing of blocks
[0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each block.
Note: These data are neither checked nor processed by the DI Function Block.
DI FB: ST_REV (1)
Storage class N; read capability r
Static revision number (DI)
Note: The revision number is incremented with each change of a static parameter in the
block.
DI FB: TAG_DESC (2)
Storage class S; read/write capability r/w; supported modes O/M/A
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
DI FB: UPDATE_EVT (18)
Storage class D; read capability r
Indicates whether static block data have been changed, including date and time stamp

KH 8384-5 EN 125
Parameter lists

Index and parameter assignment: DI Function Block


Index Parameters Index Parameters
0 – 14 STATUS_OPTS
1 ST_REV 15 CHANNEL
2 TAG_DESC 16 PV_FTIME
3 STRATEGY 17 FIELD_VAL_D
4 ALERT_KEY 18 UPDATE_EVT
5 MODE_BLK 19 BLOCK_ALM
6 BLOCK_ERR 20 ALARM_SUM
7 PV_D 21 ACK_OPTIONS
8 OUT_D 22 DISC_PRI
9 SIMULATE_D 23 DISC_LIM
12 GRANT_DENY 24 DISC_ALM
13 IO_OPTS

126 KH 8384-5 EN
KH 8384-5 EN 127
KH 8384-5 EN

2023-05-03 · English

SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507
samson@samsongroup.com · www.samsongroup.com