Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Dis21 v2.0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

FUNCTION BLOCK DESCRIPTION

Distance protection
ANSI: 21, IEC: Z<

DOCUMENT ID: PP-13-22004


VERSION: 2.0
PROTECTION, AUTOMATION AND
2019-12-16, BUDAPEST CONTROL FOR POWER INDUSTRY
VERSION INFORMATION

VERSION INFORMATION

VERSION DATE MODIFICATION COMPILED BY


Preliminary 2009-10-30 Preliminary version, without technical information Petri
2010-06-18 Technical information added Petri
2010-10-05 Naming revision Csipke
1.0 2010-11-11 First edition Petri
1.1 2013-01-28 Earth-fault detection characteristic modified Petri
Figure of the power swing detection logic
1.2 2013-05-24 Petri
corrected
PSD characteristics figures updated, added
information for the Fault Locator; technical data
2.0 2019-12-16 updated according to IEC 60255-121:2014 Erd s
New chapter: function block overview, testing
notes added; new design

2 Distance protection
www.protecta.hu
CONTENTS

CONTENTS

1 Operation principle ................................................................................................................ 5


1.1 Structure of the distance protection algorithm ............................................................... 6
1.2 The impedance calculation (Z_CALC) .......................................................................... 8
1.2.1 Principle of operation ............................................................................................. 8
1.2.2 General method of calculation of the impedances of the fault loops .................. 10
1.2.3 The principal scheme of the impedance calculation ........................................... 12
1.2.4 Internal logic of the impedance calculation ......................................................... 14
1.2.5 The impedance calculation methods ................................................................... 16
1.3 The polygon characteristics (POLY) ........................................................................... 18
1.3.1 Impedance characteristics of the distance protection ......................................... 18
1.4 The phase selection logic (SELECT) and timing ........................................................ 21
1.4.1 Three-phase fault detection ................................................................................. 22
1.4.2 Detection of “L1L2”, “L2L3”, “L3L1” faults ........................................................... 23
1.4.3 Detection of “L1N”, “L2N”, “L3N” faults ................................................................ 26
1.5 The current condition of the distance protection function (I_COND) .......................... 29
1.6 The power swing detection (PSD) .............................................................................. 30
1.7 The distance-to-fault calculation (FAULT LOCATOR) ................................................ 34
1.8 The high-speed overcurrent protection function with switch-onto-fault logic (HSOC
SOTF) 35
1.9 The on-line measured values of the distance protection function ............................... 36
2 Overview ............................................................................................................................. 37
2.1 Settings ........................................................................................................................ 38
2.1.1 Parameters .......................................................................................................... 38
2.1.2 Characteristics ..................................................................................................... 42
2.2 Function I/O ................................................................................................................. 44
2.2.1 Analogue inputs ................................................................................................... 44
2.2.2 Analogue outputs (measurements) ..................................................................... 44
2.2.3 Binary input signals (graphed output statuses) ................................................... 44
2.2.4 Binary output signals (graphed input statuses) ................................................... 45
2.2.5 On-line data ......................................................................................................... 46
2.2.6 Events .................................................................................................................. 47
2.2.7 Indication of the fault direction and loop in each Zone ........................................ 48
2.3 Technical data ............................................................................................................. 50
2.3.1 Notes for testing .................................................................................................. 50

3 Distance protection
www.protecta.hu
USED SYMBOLS

USED SYMBOLS

Additional information

Useful information for settings.

Important part for proper usage.

4 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1 Operation principle
The distance protection function provides main protection for overhead lines and cables of solidly
grounded networks. Its main features are as follows:

• A full-scheme system provides continuous measurement of impedance separately in


three independent phase-to-phase measuring loops as well as in three independent
phase-to-earth measuring loops.
• The complex earth fault compensation factor is applied for correct impedance measuring
on single-phase-to-earth fault.
• Analogue input processing is applied to the zero sequence current of the parallel line.
• Impedance calculation is conditional of the values of phase currents being sufficient. The
current is considered to be sufficient for impedance calculation if it is above the level set
by parameter(s).
• To decide the presence or absence of the zero sequence current, biased characteristics
are applied.
• Full-scheme faulty phase identification by minimum impedance detection.
• Five independent distance protection zones are configured.
• The operating decision is based on polygon-shaped characteristics.

• Load encroachment characteristics can be selected,


• The directional decision is dynamically based on:
o measured loop voltages if they are sufficient for decision,
o healthy phase voltages if they are available for asymmetrical faults,
o voltages stored in the memory if they are available,
• The operation of any zones is non-directional if it is optionally selected.
• The distance protection function can operate properly if CVT is applied as well.
• Non-directional impedance protection function or high speed OC protection function is
applied in case of switch-onto-fault.
• Distance-to-fault evaluation is implemented (fault locator function).
• Binary input signals and conditions can influence the operation:
o blocking/enabling
o VT failure signal
• Integrated high-speed overcurrent back-up function is also implemented.
• The power swing detection function can block the distance protection function in case of
stable swings, or it can generate a trip command if the system operates out of step.

5 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.1 Structure of the distance protection algorithm


Figure 1-1 shows the structure of the 5-zone HV Distance protection (DIS21_HV) algorithm.

DIS21_HV
UL1
UL2
Z_CALC POLY SELECT
UL3 Binary
IL1 outputs
IL2
IL3
3Io_par
Measured
Binary
FAULT values
inputs
I_COND LOCATOR

Parameters PSD

HSOC
SOTF

Figure 1-1 Structure of the distance protection algorithm

The inputs are


• the Fourier components of three phase voltages,
• the Fourier components of three phase currents,
• the Fourier components of (3Iop) the zero sequence current of the parallel line,
• binary inputs,
• parameters.

The outputs are


• the binary output status signals,
• the measured values for displaying.

The software modules of the distance protection function are as follows:

Z_CALC calculates the impedances (R+jX) of the six measuring current loops:
• three phase-phase loops,
• three phase-ground loops.

POLY compares the calculated impedances with the setting values of the five polygon
characteristics. The result is the decision for all six measuring loops and for all five polygons if the
impedance is within the polygon.

SELECT is the phase selection algorithm for all five zones to decide which decision is caused by
a faulty loop and to exclude the false decisions in healthy loops.

6 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

I_COND calculates the current conditions necessary for the impedance calculation and for the
phase selection logic.

PSD is the module that detects power swings and generates out-of-step trip command,
influencing the distance protection function.

FAULT LOCATOR calculates the distance to fault after the trip command.

HSOC SOTF is a high-speed overcurrent protection function for the switch-onto-fault logic.

The following description explains the details of the individual components.

7 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.2 The impedance calculation (Z_CALC)


1.2.1 Principle of operation
The distance protection continuously measures the impedances in the six possible fault loops.
The calculation is performed in the phase-to-phase loops based on the line-to-line voltages and
the difference of the affected phase currents, while in the phase-to-earth loops the phase voltage
is divided by the phase current compounded with the zero sequence current. These equations
are summarized in Table 1-1 for different types of faults. The result of this calculation is the
positive sequence impedance of the fault loop, including the positive sequence fault resistance
at the fault location.
For simplicity, the influence of the zero sequence current of the parallel line is not considered in
these equations.

Table 1-1 Formulas for the calculation of the impedance to fault


FAULT CALCULATION OF Z OTHER POSSIBLE CALCULATION
U L 2 − U L3
Z L 2 L3 = ZL1L2 , ZL2L3 , ZL3L1
L1L2L3(N) I L 2 − I L3 ZL1N , ZL2N , ZL3N

U L1 − U L 2
L1L2 Z L1L 2 =
I L1 − I L 2
U − U L3
Z L 2 L3 = L2
L2L3 I L 2 − I L3

U L3 − U L1
L3L1 Z L3L1 =
I L3 − I L1
U −U L2
L1L2N Z L1L 2 = L1 ZL1N , ZL2N
I L1 − I L 2
U − U L3
Z L 2 L3 = L2
L2L3N I L 2 − I L3 ZL2N , ZL3N

U L3 − U L1
L3L1N Z L3L1 = ZL3N, , ZL1N
I L3 − I L1
U L1
L1N Z L1N =
I L1 + 3I o K N
U L2
L2N Z L2 N =
I L 2 + 3I o K N
U L3
L3N Z L3 N =
I L 3 + 3I o K N

The central column of Table 1-1 contains the correct formula for calculation. The formulas
referred to in the right-hand-side column yield the same correct impedance value. In this column:

Z o − Z1 1  Z o 
KN = =  − 1
3Z1 3  Z1 
is the complex earth fault compensation factor. Note that this is the base of the principle behind
the algorithm; the actual earth fault compensation factor is defined by using different parameters
in the function (see Chapter 1.2.2)

8 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Table 1-1 shows that the formula containing the complex earth fault compensation factor yields
the correct impedance value in case of phase-to-earth faults only; the other formula can be
applied in case of phase-to-phase faults without ground. In case of other kinds of faults (three-
phase (-to-earth), phase-to-phase-to-earth) both formulas give the correct impedance value if the
appropriate voltages and currents are applied.
The separation of the two types of equations is based on the presence or absence of the earth
(zero sequence) current. In case of a fault involving the earth (on a solidly grounded network),
and if the earth current is over a certain level, the formula containing the complex earth fault
compensation factor will be applied to calculate the correct impedance, which is proportional to
the distance-to-fault.
It can be proven that if the setting value of the complex earth fault compensation factor is correct,
the appropriate application of the formulas in Table 1-1will always yield the positive sequence
impedance between the fault location and the relay location.

9 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.2.2 General method of calculation of the impedances of the fault


loops

Figure 1-2 Equivalent circuit of the fault loop

For the equivalent impedance elements of the fault loop on the figure above, the following
differential equation can be written:
di
u = Ri + L
dt
If the real and the imaginary components of current and voltage phasors are substituted in this
equation, two equations are derived with the two unknown values R and L, so they can be
calculated.
This basic principle is realized in the algorithm by substituting the phasor components of the line-
to-line voltages for u and the difference of two phase currents in case of two- or three-phase
faults without ground for i. For example, in case of an L2L3 fault:

d (i L 2 − i L 3 )
u L 2 − u L 3 = R1 (i L 2 − i L 3 ) + L1
dt
In case of a phase-to-earth fault, the phasor components of the phase voltage and the phase
current modified by the zero sequence current have to be substituted:
d
u L1 = R1 (i L1 +  R 3io +  R 3iop ) + L1 (i L1 +  L 3io +  L 3iop )
dt
Where
R1 is the positive sequence resistance of the line or cable section between the fault location
and the relay location,
L1 is the positive sequence inductance of the line or cable section between the fault
location and the relay location,
L1 is the faulty phase,
3io =iL1+iL2+iL3 is the phasor component of the zero sequence current of the protected
line,
3iop =iL1p+iL2p+iL3p is the phasor component of the zero sequence current in parallel line,
and

10 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Ro − R1
R =
3R1
Lo − L1 X o − X 1
L = =
3L1 3X1
Rm
R =
3R1
Lm X
L = = m
3L1 3 X 1

Rm is the real part of the mutual impedance between the protected and the parallel line,
Lm is the mutual inductance between the protected and the parallel line.
The formula above shows that the factors for multiplying the R and L values contain different “”
and “ ” factors but they are real (not complex) numbers.
The applied numerical method is solving the differential equation of the faulty loop, based on three
consecutive samples.

11 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.2.3 The principal scheme of the impedance calculation


Figure 1-3 shows the principal scheme of the impedance calculation Z_CALC
Z_CALC V
I L1
IV
I L2 I II
I L3 II
I
3Iop
ZL1_CALC RL1+j XL1
RL2+j XL2
UL1 RL3+j XL3
ZL2_CALC
UL2
UL3 ZL3_CALC

Binary V
inputs IV
I II
II
Parameters
I

ZL1 L2 _CALC RL1 L2 +j XL1 L2


RL 2L3 +j XL 2L3
ZL2L3_CALC RL 3L1 +j XL 3L1

ZL3 L1 _CALC

Figure 1-3 Principal scheme of the impedance calculation Z_Calc


The inputs are the Fourier components of:
• the three phase voltages,
• the three phase currents,
• the (3Iop) zero sequence current of the parallel line,
• binary inputs,
• parameters.
The binary inputs are signals influencing the operation of the distance protection function. These
signals are the results of logic equations graphically edited by the user.

Table 1-2 Binary input signals for the impedance calculation


BINARY INPUT SIGNAL SIGNAL TITLE EXPLANATION
Blocking signal due to error
in voltage measurement
DIS21_VTS_GrO_ Block from VTS
(Output of the user-defined
graphic equation)
Status signal indicating
switching-onto-fault
DIS21_SOTFCond_GrO_ SOTF COND. condition (Output of the
user-defined graphic
equation)

Table 1-3 Enumerated parameters for the impedance calculation


PARAMETER NAME TITLE SELECTION RANGE DEFAULT
Parameters to select directionality of the individual zones:
Operation
DIS21_Z1_EPar_ Off, Forward, Backward Off
Zone1
Operation
DIS21_Z2_EPar_ Off, Forward, Backward, NonDirectional Off
Zone2
Operation
DIS21_Z3_EPar_ Off, Forward, Backward, NonDirectional Off
Zone3

12 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Operation
DIS21_Z4_EPar_ Off, Forward, Backward, NonDirectional Off
Zone4
Operation
DIS21_Z5_EPar_ Off, Forward, Backward, NonDirectional Off
Zone5
Parameter for selecting one of the zones or “high speed overcurrent protection” for the “switch-
onto-fault” function:
SOTF Off, Zone1, Zone2, Zone3, Zone4,
DIS21_SOTFMd_EPar_ Zone1
Zone Zone5, HSOC

Table 1-4 Floating point parameters for the impedance calculation


PARAMETER NAME TITLE DIM. MIN MAX STEP DEFAULT
DIS21_Z1aX_FPar_ Zone1 (Xo-X1)/3X1 0 5 0.01 1
DIS21_Z1aR_FPar_ Zone1 (Ro-R1)/3R1 0 5 0.01 1
DIS21_a2X_FPar_ Par.Line Xom/3X1 0 5 0.01 0
DIS21_a2R_FPar_ Par.Line Rom/3R1 0 5 0.01 0
DIS21_Z2aX_FPar_ Zone2 (Xo-X1)/3X1 0 5 0.01 1
DIS21_Z2aR_FPar_ Zone2 (Ro-R1)/3R1 0 5 0.01 1
DIS21_Z3aX_FPar_ Zone3 (Xo-X1)/3X1 0 5 0.01 1
DIS21_Z3aR_FPar_ Zone3 (Ro-R1)/3R1 0 5 0.01 1
DIS21_Z4aX_FPar_ Zone4 (Xo-X1)/3X1 0 5 0.01 1
DIS21_Z4aR_FPar_ Zone4 (Ro-R1)/3R1 0 5 0.01 1
DIS21_Z5aX_FPar_ Zone5 (Xo-X1)/3X1 0 5 0.01 1
DIS21_Z5aR_FPar_ Zone5 (Ro-R1)/3R1 0 5 0.01 1

The outputs are the calculated positive-sequence impedances (R+jX) of the six measuring
current loops and, as different zero sequence current compensation factors can be set for the
individual zones, the impedances are calculated for each zone separately:
• Impedances of the three phase-phase loops,
• Impedances of the three phase-ground loops.

Table 1-5 The measured (calculated) values of the Z_CALC module


MEASURED VALUE DIM. EXPLANATION
Measured positive sequence impedance in the L1N loop, using
RL1+j XL1 ohm
the zero sequence current compensation factor for zone 1
Measured positive sequence impedance in the L2N loop, using
RL2+j XL2 ohm
the zero sequence current compensation factor for zone 1
Measured positive sequence impedance in the L3N loop, using
RL3+j XL3 ohm
the zero sequence current compensation factor for zone 1
RL1L2+j XL1L2 ohm Measured positive sequence impedance in the L1L2 loop
RL2L3+j XL2L3 ohm Measured positive sequence impedance in the L2L3 loop
RL3L1+j XL3L1 ohm Measured positive sequence impedance in the L3L1 loop

Z_CALC includes six practically identical software modules for impedance calculation:
• The three routines of the phase group are activated by phase voltages, phase currents
and the zero sequence current calculated from the phase current and the zero sequence
currents of the parallel line, as measured in a dedicated input.
• The three routines for the phase-to-phase loops get line-to-line voltages calculated from
the phase voltages and they get differences of the phase currents. They do not need zero
sequence currents for the calculation.

The calculated impedances are analogue outputs of the distance protection function. They serve
the purpose of checking possibility at commissioning.

13 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.2.4 Internal logic of the impedance calculation


Figure 1-4 shows the internal logic of the impedance calculation.

CURRENT_OK Calc_A
NOT
AND
VTS_BLOCK NOT
Calc_B
VOLT_OK_HIGH AND

NOT
Calc_C
VOLT_OK_LOW AND
MEM_AVAIL

NOT Calc_D
AND

Calc_E
AND
NOT

Calc_F
AND
HEALTHY_PHASE_AVAIL

AND Calc_G
SOFT_COND OR
P_SOFT_Zn AND
Calc_H
AND
P_nondir
NOT

Figure 1-4 Z_CALC internal logic

The decision needs logic parameter settings and, additionally, internal logic signals.
The explanation of these signals is as follows:

Table 1-6 Enumerated parameters for the Z_CALC module


PARAMETER EXPLANATION
This logic parameter is true if the “switch-onto-fault” logic is enabled
P_SOTF_Zn for Zone_n, (where n=1…5), i.e., SOTF Zone is selected for “Zone n”
(where n=1…5).
This logic parameter is true if no directionality is programmed, i.e., the
P_nondir Operation Zonen parameter (where n=1…5) is set to
“NonDirectional” for the individual zones.

Table 1-7 Binary signals for the Z_CALC module


INPUT STATUS SIGNAL EXPLANATION
The current is suitable for impedance calculation in the processed
loop. This status signal is generated within the Z_CALC module
CURRENT_OK
based on the parameter IPh Base Sens and in case of phase-ground
loops on parameters IRes Base Sens and IRes Bias
VTS Block Binary blocking signal due to error in the voltage measurement
The loop voltage is above the predefined higher limit (35% of the loop
VOLT_OK_HIGH nominal value). This status signal is generated within the Z_CALC
module.
The loop voltage is above the predefined lower limit (5% of the loop
VOLT_OK_LOW nominal value) but below the predefined higher limit (35% of the loop
nominal value). In this case the directional element should use the

14 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

voltage phasor components for 35 ms period stored in the memory


because the secondary swings of the capacitive voltage divider distort
the sampled voltage values. This status signal is generated within the
Z_CALC module.
This status signal is true if the voltage memory is filled up with
MEM_AVAIL available samples above the defined limit for 120 ms. This status
signal is generated within the Z_CALC module.
This status signal is true if there are healthy phase voltages (in case
HEALTHY_PHASE_
of asymmetrical faults) that can be applied to directional decision.
AVAIL
This status signal is generated within the Z_CALC module.
This status signal is true if the algorithm detected switch-onto-fault
conditions, and the binary input signal
SOTF_COND
DIS21_SOTFCond_GrO_ (SOTF COND.) is programmed by the
user to logic “1”, using the graphic equation editor.

The outputs of the scheme of Figure 1-4 are calculation methods applied for impedance
calculation for the individual zones.

Table 1-8 Calculation methods applied in the Z_CALC module


CALCULATION METHOD EXPLANATION
No current is available, the impedances are supposed to be higher
Calc(A) than the possible maximum setting values
R=1000000 mΩ, X=1000000 mΩ
The currents and voltages are suitable for the correct impedance
Calc(B) calculation and directional decision
R, X=f(u, i)
The currents are suitable, but the voltages are in the range of the
CVT swings, so during the first 35 ms the directional decision is
Calc(C) based on pre-fault voltages stored in the memory
R, X=f(u, i) direction = f(Umem, i) /in the first 35 ms/
R, X=f(u, i) direction = f(u, i) /after 35 ms/
The currents are suitable, but the voltages are too low. The directional
Calc(D) decision is based on pre-fault voltages stored in the memory
R, X=f(u, i) direction = f(max{R(Umem, i), X(Umem,i)})
The currents are suitable, but the voltages are in the range of the
CVT swings and there are no healthy voltages stored in the memory
but because of asymmetrical faults, there are healthy voltages.
Calc(E) Therefore, during the first 35 ms the directional decision is based on
healthy voltages
R, X=f(u, i) direction = f(Uhealthy, i) /in the first 35 ms/
R, X=f(u, i) direction = f(u, i) /after 35 ms/
The currents are suitable, but the voltages are too low, there are no
pre-fault voltages stored in the memory but because of asymmetrical
Calc(F) faults, there are healthy voltages. Therefore, the directional decision
is based on healthy voltages
R, X=f(u, i) direction = f(Uhealthy, i)
If no directional decision is required or in case of prescribed SOTF
logic the fault was caused by a switching, then the decision is based
Calc(G)
on the absolute value of the impedance (forward fault is supposed)
R=abs(R), X=abs(X)
If the decision is not possible (no voltage, no pre-fault voltage, no
healthy phase voltage but directional decision is required), then the
Calc(H)
impedance is set to a value above the possible impedance setting
R=1000500 mΩ, X=1000500 mΩ

15 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.2.5 The impedance calculation methods


The short explanation of the internal logic for the impedance calculation is as follows:

Calculation method Calc(A):


If the CURRENT_OK status signal is false, the current is very small, therefore no fault is possible.
In this case, the impedance is set to extreme high values and no further calculation is performed:
R=1000000, X=1000000.
The subsequent decisions are performed if the current is sufficient for the calculation.

Calculation method Calc(B):


If the CURRENT_OK status signal is true and the VOLT_OK_HIGH status signal is true as well,
then the current is suitable for calculation and the voltage is sufficient for the directionality
decision. In this case, normal impedance calculation is performed based on the currents and
voltages. (The calculation method - the function ”f”- is explained later.)
R, X=f(u, i)

Calculation method Calc(C):


If the CURRENT_OK status signal is true but the VOLT_OK_HIGH status signal is false or there
are voltage swings, the directionality decision cannot be performed based on the available voltage
signals temporarily. In this case, if the voltage is above a minimal level (in the range of possible
capacitive voltage transformer swings), then the VOLT_OK_LOW status is “true”, the magnitude
of R and X is calculated based on the actual currents and voltages but the direction of the fault
(the +/- sign of R and X) must be decided based on the voltage value stored in the memory 120
ms earlier. (The high voltage level setting assures that during the secondary swings of the voltage
transformers, no distorted signals are applied for the decision). This procedure is possible only if
there are stored values in the memory for 120 ms and these values were sampled during a healthy
period.
R, X=f(u, i) direction = f(Umem, i) /in the first 35 ms/
After 35 ms (when the secondary swings of the voltage transformers decayed), the directional
decision returns to the measured voltage signal again:
R, X=f(u, i) direction = f(u, i) /after 35 ms/

Calculation method Calc(D):


If the voltage is below the minimal level, then the VOLT_OK_LOW status is “false” but if there are
voltage samples stored in the memory for 120 ms, then the direction is decided based on the sign
either of the real part of the impedance or that of the imaginary part of the impedance, whichever
is higher.
R, X=f(u, i) direction = f(max{R(Umem, i), X(Umem,i)})

Calculation method Calc(E):


The currents are suitable, but the voltages are in the range of the CVT swings, there are no pre-
fault voltages stored in the memory but because of asymmetrical faults, there are healthy phase
voltages. Therefore, during the first 35 ms the directional decision is based on healthy voltages
R, X=f(u, i) direction = f(Uhealthy, i) /in the first 35 ms/
R, X=f(u, i) direction = f(u, i) /after 35 ms/
The positive and negative sequence components of the voltage and current system are composed
and used to determine the direction of the fault.

16 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Calculation method Calc(F):


The currents are suitable, but the voltages are too low, there are no pre-fault voltages stored in
the memory but because of asymmetrical faults, there are healthy voltages. Therefore, the
directional decision is based on healthy voltages
R, X=f(u, i) direction = f(Uhealthy, i)
The directional decision is described in calculation method Calc(E).

Calculation method Calc(G):


If no directional decision is required or in case of prescribed SOTF logic and the fault was caused
by a switching, then the decision is based on the absolute value of the impedance (forward fault
is supposed)
R=abs(R), X=abs(X)

Calculation method Calc(H):


If the voltage is not sufficient for a directional decision and no stored voltage samples are
available, and if the “switch-onto-fault” logic is not enabled, then the impedance is set to a high
value:
R=1000500 mΩ, X=1000500 mΩ

17 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.3 The polygon characteristics (POLY)


1.3.1 Impedance characteristics of the distance protection
The calculated R1 and X1=L1 co-ordinate values define six points on the complex impedance
plane for the six possible measuring loops. These impedances are the positive sequence
impedances. The protection compares these points with the „polygon” characteristics of the
distance protection, shown in Figure 1-5 The main setting values of R and X refer to the positive
sequence impedance of the fault loop, including the positive sequence fault resistance of the
possible electric arc and, in case of a ground fault, the positive sequence resistance of the tower
grounding as well. (When testing the device using a network simulator, the resistance of the fault
location is to be applied to match the positive sequence setting values of the characteristic lines.)

jX

Angle 2nd Quad


Zone Reduct Angle

Zone X

Load Angle
Line Angle

R Load
Angle 4th Quad

Zone R

Figure 1-5 The polygon characteristics of the distance protection function on the
complex plane

If a measured impedance point is inside the polygon, the algorithm generates the true value of
the related output binary signal.

The calculated impedance values are compared one by one with the setting values of the polygon
characteristics. This procedure is shown schematically in Figure 1-6.

The procedure is processed for each line-to-ground loop and for each line-to-line loop. Then this
is repeated for all five impedance stages. The result is the setting of 6 x 5 status variables, which
indicate that the calculated impedance is within the processed polygon, meaning that the
impedance stage has started.

18 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

I.
II.
III.
V IV.
IV V.

III

RL1+j XL1 V
RL2+j XL2 IV
RL3+j XL3
III
II
I
ZL1_n
V
ZL2_n
ZL3_n
IV
ZL1L2_n
III ZL2L3_n
II ZL3L1_n
I

RL1L2+j XL1L2
RL2L3+j XL2L3
RL3L1+j XL3L1

Parameters

Figure 1-6 POLY logic

Input values
The input values are calculated by the module Z_CALC.

Table 1-9 The input impedances of the POLY module


INPUT VALUES ZONES EXPLANATION
Calculated impedance in the fault loop L1N using parameters
RL1+j XL1 1…5
of the zones individually
Calculated impedance in the fault loop L2N using parameters
RL2+j XL2 1…5
of the zones individually
Calculated impedance in the fault loop L3N using parameters
RL3+j XL3 1…5
of the zones individually
Calculated impedance in the fault loop L1L2 using parameters
RL1L2+j XL1L2 1…5
of the zones individually
Calculated impedance in the fault loop L2L3 using parameters
RL2L3+j XL2L3 1…5
of the zones individually
Calculated impedance in the fault loop L3L1 using parameters
RL3L1+j XL3L1 1…5
of the zones individually

19 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Table 1-10 The output status signals of the POLY module


OUTPUT VALUES ZONES EXPLANATION
ZL1_n 1…5 The impedance in the fault loop L1N is inside the characteristics
ZL2_n 1…5 The impedance in the fault loop L2N is inside the characteristics
ZL3_n 1…5 The impedance in the fault loop L3N is inside the characteristics
ZL1L2_n 1…5 The impedance in the fault loop L1L2 is inside the characteristics
ZL2L3_n 1…5 The impedance in the fault loop L2L3 is inside the characteristics
ZL3L1_n 1…5 The impedance in the fault loop L3L1 is inside the characteristics

The parameters needed in the polygon evaluation procedure of the distance protection function
are explained in the following tables.

Table 1-11 The enumerated parameters of the POLY logic


PARAMETER NAME TITLE SELECTION RANGE DEFAULT
Parameters to select directionality of the individual zones:
DIS21_Z1_EPar_ Operation Zone1 Off, Forward, Backward Off
DIS21_Z2_EPar_ Operation Zone2 Off, Forward, Backward, NonDirectional Off
DIS21_Z3_EPar_ Operation Zone3 Off, Forward, Backward, NonDirectional Off
DIS21_Z4_EPar_ Operation Zone4 Off, Forward, Backward, NonDirectional Off
DIS21_Z5_EPar_ Operation Zone5 Off, Forward, Backward, NonDirectional Off

Table 1-12 The integer parameters of the POLY logic


PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
Definition of the polygon characteristic angle in the 4 th quadrant of the impedance plane:
DIS21_dirRX_IPar_ Angle 2nd Quad deg 0 30 1 15
Definition of the polygon characteristic angle in the 2 nd quadrant of the impedance plane:
DIS21_dirXR_IPar_ Angle 4th Quad deg 0 30 1 15
Definition of the zone reduction angle of the polygon characteristic on the impedance plane:
DIS21_Cut_IPar_ Zone Reduct Angle deg 0 40 1 0
Definition of the load angle of the polygon characteristic:
DIS21_LdAng_IPar_ Load Angle deg 0 45 1 30
Definition of the line angle:
DIS21_LinAng_IPar_ Line Angle deg 45 90 1 75

Table 1-13 The floating point parameters of the POLY logic


PARAMETER NAME TITLE DIMENSION MIN MAX STEP DEFAULT
R and X setting values for the five zones individually:
DIS21_Z1R_FPar Zone1 R ohm 0.1 320
200 0.01 10
DIS21_Z2R_FPar Zone2 R ohm 0.1 320
200 0.01 10
DIS21_Z3R_FPar Zone3 R ohm 0.1 200
320 0.01 10
DIS21_Z4R_FPar Zone4 R ohm 0.1 320
200 0.01 10
DIS21_Z5R_FPar Zone5 R ohm 0.1 320
200 0.01 10
DIS21_Z1X_FPar Zone1 X ohm 0.1 200
320 0.01 10
DIS21_Z2X_FPar Zone2 X ohm 0.1 320
200 0.01 10
DIS21_Z3X_FPar Zone3 X ohm 0.1 320
200 0.01 10
DIS21_Z4X_FPar Zone4 X ohm 0.1 320
200 0.01 10
DIS21_Z5X_FPar Zone5 X ohm 0.1 200
320 0.01 10
DIS21_LdR_FPar R Load ohm 0.1 200
320 0.01 10

20 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.4 The phase selection logic (SELECT) and timing


In case of faults, the calculated impedance value for the faulty loop is inside a polygon. If the fault
is near the relay location, the impedances in the loop containing the faulty phase can also be
inside the polygon. To ensure selective tripping, phase selection is needed. This chapter explains
the operation of the phase selection logic.
The binary inputs are signals influencing the operation of the distance protection function. These
signals are the results of logic equations graphically edited by the user.

Table 1-14 Binary input signals influencing the phase selection logic
BINARY INPUT SIGNALS SIGNAL TITLE EXPLANATION
DIS21_Z1Blk_GrO_ Block Z1 Blocking of Zone 1
DIS21_Z2Blk_GrO_ Block Z2 Blocking of Zone 2
DIS21_Z3Blk_GrO_ Block Z3 Blocking of Zone 3
DIS21_Z4Blk_GrO_ Block Z4 Blocking of Zone 4
DIS21_Z5Blk_GrO_ Block Z5 Blocking of Zone 5
Status signal indicating switching-
DIS21_SOTFCond_GrO_ SOTF COND.
onto-fault condition

Table 1-15 Binary input signals from the POLY logic


BINARY INPUT
EXPLANATION
SIGNALS
ZL1_n Calculated impedance for loop L1 is inside the polygon of Zone “n” (n=1…5)
ZL2_n Calculated impedance for loop L2 is inside the polygon of Zone “n” (n=1…5)
ZL3_n Calculated impedance for loop L3 is inside the polygon of Zone “n” (n=1…5)
ZL1L2_n Calculated impedance for loop L1L2 is inside the polygon of Zone “n” (n=1…5)
ZL2L3_n Calculated impedance for loop L2L3 is inside the polygon of Zone “n” (n=1…5)
ZL3L1_n Calculated impedance for loop L3L1 is inside the polygon of Zone “n” (n=1…5)

Table 1-16 Binary output of the phase selection logic


BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
Distance Zone 1
DIS21_Z1St_GrI_ Start Z1 General start of Zone1
DIS21_Z1StL1_GrI_ Z1 Start L1 Start in phase L1 of Zone1
DIS21_Z1StL2_GrI_ Z1 Start L2 Start in phase L2 of Zone1
DIS21_Z1StL3_GrI_ Z1 Start L3 Start in phase L3 of Zone1
DIS21_Z1Tr_GrI_ Trip Z1 Trip command generated in Zone1
Distance Zone 2 similar to Zone 1
Distance Zone 3 similar to Zone 1
Distance Zone 4 similar to Zone 1
Distance Zone 5 similar to Zone 1

Table 1-17 Enumerated parameters of the distance protection function


PARAMETER NAME TITLE SELECTION RANGE DEFAULT
Parameters to select directionality of the individual zones:
DIS21_Z1_EPar_ Operation Zone1 Off, Forward, Backward Off
DIS21_Z2_EPar_ Operation Zone2 Off, Forward, Backward, NonDirectional Off
DIS21_Z3_EPar_ Operation Zone3 Off, Forward, Backward, NonDirectional Off
DIS21_Z4_EPar_ Operation Zone4 Off, Forward, Backward, NonDirectional Off
DIS21_Z5_EPar_ Operation Zone5 Off, Forward, Backward, NonDirectional Off

21 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Table 1-18 Boolean parameters of the phase selection logic


PARAMETER NAME TITLE DEFAULT EXPLANATION
DIS21_Z1St_BPar_ Zone1 Start Only 0 0 for Zone1 to generate trip command
DIS21_Z2St_BPar_ Zone2 Start Only 0 0 for Zone2 to generate trip command
DIS21_Z3St_BPar_ Zone3 Start Only 0 0 for Zone3 to generate trip command
DIS21_Z4St_BPar_ Zone4 Start Only 0 0 for Zone4 to generate trip command
DIS21_Z5St_BPar_ Zone5 Start Only 0 0 for Zone5 to generate trip command

Table 1-19 Timer parameters of the distance protection function


PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
Time delay for the zones individually
DIS21_Z1Del_TPar_ Zone1 Time Delay ms 0 60000 1 0
DIS21_Z2Del_TPar_ Zone2 Time Delay ms 40 60000 1 400
DIS21_Z3Del_TPar_ Zone3 Time Delay ms 40 60000 1 800
DIS21_Z4Del_TPar_ Zone4 Time Delay ms 40 60000 1 2000
DIS21_Z5Del_TPar_ Zone5 Time Delay ms 40 60000 1 2000

Zone1 timer starts at the rising edge of its start signal, whereas the timer of the other zones
contains the time of the detection algorithm as well, therefore their minimum value is 40 ms.

1.4.1 Three-phase fault detection


The processing of diagrams in the following figures is sequential. If the result of one of them is
true, no further processing is performed.

Figure 1-7 shows that if


• all three line-line loops of the polygon impedance logic have stated and
• the currents in all three phases are above the setting limit,
then a three-phase fault is detected, and no further check is performed. The three-phase fault
detection resets only if none of the three line-to-line loops detect fault any longer.

In Figure 1-7 and in the subsequent figures “n = 1…5” means that the logic is repeated for all five
zones.

ZL1L2_n Z_3Ph_start_n_
OR
ZL2L3_n
ZL3L1_n
DIS21_cIL1_GrI AND
DIS21_cIL2_GrI
DIS21_cIL3_GrI

OR AND

Figure 1-7 Three-phase fault detection in Zone “n” (n=1..5)

Table 1-20 Three-phase start of the distance protection function


OUTPUT STATUS SIGNALS ZONES EXPLANATION
Three-phase start of the distance protection function in
Z_3Ph_start_n n=1…5
zone “n”

22 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Table 1-21 Inputs needed to decide the three-phase start of the function
INPUT STATUS SIGNALS ZONES EXPLANATION
The calculated impedance of fault loop L1L2 is within
ZL1L2_n n=1…5
the zone characteristic
The calculated impedance of fault loop L2L3 is within
ZL2L3_n n=1…5
the zone characteristic
The calculated impedance of fault loop L3L1 is within
ZL3L1_n n=1…5
the zone characteristic
The current in phase L1 is sufficient for impedance
DIS21_cIL1_GrI n=1…5
calculation
The current in phase L2 is sufficient for impedance
DIS21_cIL2_GrI n=1…5
calculation
The current in phase L3 is sufficient for impedance
DIS21_cIL3_GrI n=1…5
calculation

1.4.2 Detection of “L1L2”, “L2L3”, “L3L1” faults


Figure 1-8 explains the detection of a phase-to-phase fault between phases “L1” and “L2”:
• no fault is detected in the previous sequential tests,
• the start of the polygon impedance logic in loop “L1L2” and loop “L1L2” detects the lowest
reactance, and
• “OR” relation of the following logic states:
o no zero sequence current above the limit and no start of the polygon logic in
another phase-to-phase loop, or
o in the presence of a zero sequence current
▪ start of the polygon impedance logic in loops “L1” and ”L2” individually
as well, or
▪ the voltage is small in the faulty “L1L2” loop and the currents in both
phases involved are above the setting limit.
The “L1L2” fault detection resets only if none of the “L1L2” line-to-line, “L1N” or “L2N” loops detect
fault any longer.

In Figures Figure 1-8, Figure 1-9 and Figure 1-10:


minLL = Minimum(ZL1L2, ZL2L3, ZL3L1)

Z_3Ph_start_n NOT

ZL1L2_n AND
ZL1L2_eq_mi

DIS21_cIo_GrI NOT AND OR AND OR ZL1L2_Start

AND
ZL2L3_n NOT

ZL1_n AND OR
ZL2_n
UL1L2_It_5V
DIS21_cIL1_GrI
DIS21_clL2_GrI

OR AND

Figure 1-8 L1L2 fault detection in Zone “n” (n=1..5)

23 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Figure 1-9 and Figure 1-10 show a similar logic for loops “L2L3” and “L3L1”, respectively.

Z_3Ph_start_n OR NOT
ZL1L2_start_n
ZL2L3_n AND
ZL2L3_eq_mi

DIS21_cIo_GrI NOT AND OR AND OR ZL2L3_Start

AND
ZL3L1_n NOT

ZL2_n AND OR
ZL3_n
UL2L3_It_5V
DIS21_cIL2_Gr
DIS21_clL3_Gr

OR AND

Figure 1-9 L2L3 fault detection in Zone “n” (n=1..5)

Z_3Ph_start_
ZL1L2_start_n
n OR NOT
ZL2L3_start_n
ZL3L1_n AND
ZL3L1_eq_mi

DIS21_cIo_GrI AND
NOT AND OR OR ZL3L1_Start

AND
ZL1L2_n NOT

ZL3_n AND OR
ZL1_n
UL3L1_It_5V
DIS21_cIL3_Gr
DIS21_clL1_Gr

OR AND

Figure 1-10 L3L1 fault detection in Zone “n” (n=1..5)

Table 1-22 Phase-to-phase loop start of the distance protection function


OUTPUT STATUS SIGNALS ZONES EXPLANATION
L1L2 loop start of the distance protection function
L1L2_Start_n n=1…5
in zone “n”
L2L3 loop start of the distance protection function
L2L3_Start_n n=1…5
in zone “n”
L3L1 loop start of the distance protection function
L3L1_Start_n n=1…5
in zone “n”

24 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Table 1-23 Inputs needed to decide phase-to-phase loop start of the distance protection
function
INPUT STATUS SIGNALS ZONES EXPLANATION
Z_3Ph_start_n n=1…5 Outputs of the previous decisions
ZL1L2_Start_n n=1…5 Outputs of the previous decisions
ZL2L3_Start_n n=1…5 Outputs of the previous decisions
The calculated impedance of fault loop L1L2 is
ZL1L2_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L2L3 is
ZL2L3_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L3L1 is
ZL3L1_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L1L2 is the
ZL1L2_equ_minLL n=1…5
smallest one
The calculated impedance of fault loop L2L3 is the
ZL2L3_ equ_minLL n=1…5
smallest one
The calculated impedance of fault loop L3L1 is the
ZL3L1_ equ_minLL n=1…5
smallest one
The calculated impedance of fault loop L1N is
ZL1_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L2N is
ZL2_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L3N is
ZL3_n n=1…5
within the zone characteristic
The current in phase L1 is sufficient for impedance
DIS21_cIL1_GrI
calculation
The current in phase L2 is sufficient for impedance
DIS21_cIL2_GrI
calculation
The current in phase L3 is sufficient for impedance
DIS21_cIL3_GrI
calculation
The zero sequent current component is sufficient
DIS21_cIo_GrI_
for earth fault calculation
UL1L2_Lt_5V The L1L2 voltage is less than 5V
UL3L3_Lt_5V The L2L3 voltage is less than 5V
UL3L2_Lt_5V The L3L1 voltage is less than 5V

25 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.4.3 Detection of “L1N”, “L2N”, “L3N” faults


Figure 1-11 explains the detection of a phase-to-ground fault in phase “L1”:
• no fault is detected in the previous sequential tests,
• start of the polygon impedance logic in loop “L1N”,
• the minimal impedance is measured in loop “L1N”,
• no start of the polygon logic in another phase-to-ground loop,
• the zero sequence current above the limit,
• the current in the phase involved is above the setting limit,
• the minimal impedance of the phase-to-ground loops is less then the minimal impedance
in the phase-to-phase loops.

In Figure 1-11, Figure 1-12 and Figure 1-13:


minLN = Minimum(ZL1N, ZL2N, ZL3N)

Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL1_start_n
ZL1_n
ZL1_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL1_GrI
minLN_Lt_minLL
L
Figure 1-11 L1N fault detection in Zone “n” (n=1..5)

Figure 1-12 and Figure 1-13 show similar logic for loops “L2” and “L3” respectively.

Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL1_start_n
ZL2_start_n
ZL2_n
ZL2_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL2_GrI
minLN_It_minLL

Figure 1-12 L2N fault detection in Zone “n” (n=1..5)

Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL2_start_n
ZL2_start_n
ZL3_n
ZL3_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL3_GrI
minLN_It_minLL

Figure 1-13 L3N fault detection in Zone “n” (n=1..5)

26 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

Table 1-24 Phase-to-ground loop start of the distance protection function


OUTPUT STATUS
ZONES EXPLANATION
SIGNALS
ZL1_Start_n n=1…5 L1N loop start of the distance protection function in zone “n”
ZL2_Start_n n=1…5 L2N loop start of the distance protection function in zone “n”
ZL3_Start_n n=1…5 L3N loop start of the distance protection function in zone “n”

Table 1-25 Inputs needed to decide Phase-to-ground loop start of the distance protection
function
INPUT STATUS SIGNALS ZONES EXPLANATION
ZL1L2_Start_n n=1…5 Outputs of the previous decisions
ZL2L3_Start_n n=1…5 Outputs of the previous decisions
ZL3L1_Start_n n=1…5 Outputs of the previous decisions
ZL1_Start_n n=1…5 Outputs of the previous decisions
ZL2_Start_n n=1…5 Outputs of the previous decisions
The calculated impedance of fault loop L1 is the
ZL1_equ_minLN n=1…5
smallest one
The calculated impedance of fault loop L2 is the
ZL2_ equ_minLN n=1…5
smallest one
The calculated impedance of fault loop L3 is the
ZL3_ equ_minLN n=1…5
smallest one
The calculated impedance of fault loop L1N is within
ZL1_n n=1…5
the zone characteristic
The calculated impedance of fault loop L2N is within
ZL2_n n=1…5
the zone characteristic
The calculated impedance of fault loop L3N is within
ZL3_n n=1…5
the zone characteristic
The current in phase L1 is sufficient for impedance
DIS21_cIL1_GrI n=1…5
calculation
The current in phase L2 is sufficient for impedance
DIS21_cIL2_GrI n=1…5
calculation
The current in phase L3 is sufficient for impedance
DIS21_cIL3_GrI n=1…5
calculation
The zero sequence current component is sufficient for
DIS21_cIo_GrI n=1…5
impedance calculation in LN loops

Figure 1-14 shows how the signals are processed for the output signals of the distance protection
function.
DIS21_Zn_Epar_eq_Off
OR NOT
DIS21_Zn_Blk_GrO_

AND DIS21_ZnStL1_GrI
Z_3Ph_start_n
ZL1L2_start_n
ZL3L1_start_n OR
ZL1_start_n
DIS21_ZnStL2_GrI
AND

ZL2L3_start_n OR
ZL2_start_n
AND DIS21_ZnStL3_GrI

OR
ZL3_start_n DIS21_ZnSt_GrI
OR

DIS21_ZnTr_GrI
AND DELAY
DIS21_ZnSt_BPar
NOT

DIS21_ZnDel_TPar

Figure 1-14 L3N fault detection in Zone “n” (n=1..5)

27 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

• The operation of the distance protection may be blocked either by parameter setting
(DIS21_Zn_EPar_eq_Off) or by binary input (DIS21_Zn_Blk_GrO_)
• Starting in phase L1 if this phase is involved in the fault (DIS21_ZnStL1_GrI),
• Starting in phase L2 if this phase is involved in the fault (DIS21_ZnStL2_GrI),
• Starting in phase L2 if this phase is involved in the fault (DIS21_ZnStL3_GrI),
• General start if any of the phases is involved in the fault (DIS21_ZnSt_GrI),
• A trip command (DIS21_ZnTr_GrI) is generated after the timer Zn_Delay has expired.
This timer is started if the zone is started and it is not assigned to “Start signal only”, using
the parameter DIS21_ZnSt_BPar. The time delay is set by the timer parameter
DIS21_ZnDel_TPar.

Figure 1-15 shows the method of post-processing the binary output signals to generate general
start signals for the phases individually and separately for zones 2 to 5.

DIS21_Z1StL1_GrI DIS21_GenStL1_GrI
OR

DIS21_Z2StL1_GrI DIS21_Z25StL1_GrI
DIS21_Z3StL1_GrI OR
DIS21_Z4StL1_GrI
DIS21_Z5StL1_GrI

DIS21_Z1StL2_GrI DIS21_GenStL2_GrI
OR

DIS21_Z2StL2_GrI DIS21_Z25StL2_GrI
DIS21_Z3StL2_GrI
DIS21_Z4StL2_GrI OR
DIS21_Z5StL2_GrI

DIS21_Z1StL3_GrI DIS21_GenStL3_GrI
OR

DIS21_Z2StL3_GrI DIS21_Z25StL3_GrI
DIS21_Z3StL3_GrI OR
DIS21_Z4StL3_GrI
DIS21_Z5StL3_GrI

Figure 1-15 General start in the phase-to-ground loops separately for Zones 2-to 5

The binary output status signals of the distance protection function.

Table 1-26 General phase identification of the distance protection function


BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
Distance Phase identification
DIS21_GenStL1_GrI_ GenStart L1 General start in phase L1
DIS21_GenStL2_GrI_ GenStart L2 General start in phase L2
DIS21_GenStL3_GrI_ GenStart L3 General start in phase L3

The separate phase identification signals for Zones 2-5 are not published.

28 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.5 The current condition of the distance protection function


(I_COND)
The distance protection function can operate only if the current is sufficient for impedance
calculation. Additionally, a phase-to-ground fault is detected only if there is sufficient zero
sequence current. This function performs these preliminary decisions.

Table 1-27 The binary output status signals of the current conditions module
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
Distance function start conditions generated by the I_COND module (these signals are not
published)
The zero sequent current component is
DIS21_cIo_GrI_ Io condition
sufficient for earth fault calculation
The current in phase L1 is sufficient for
DIS21_cIL1_GrI_ I L1 condition
impedance calculation
The current in phase L2 is sufficient for
DIS21_cIL2_GrI_ I L2 condition
impedance calculation
The current in phase L3 is sufficient for
DIS21_cIL3_GrI_ I L3 condition
impedance calculation

Table 1-28 Integer parameters for the current conditions module


PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
Definition of minimal current enabling impedance calculation:
DIS21_Imin_IPar_ IPh Base Sens % 10 30 1 20
Definition of zero sequence current characteristic enabling impedance calculation in phase-to-
earth loops:
DIS21_IoBase_IPar_ IRes Base Sens % 10 50 1 10
DIS21_IoBias_IPar_ IRes Bias % 5 30 1 10

The current is considered to be sufficient for impedance calculation if it is above the level set by
parameter IPh Base Sens.
To decide the presence or absence of the zero sequence current, biased characteristics are
applied (see Figure 1-16). The minimal setting current IRes Base Sens and a percentage biasing
IRes Bias must be set. The biasing is applied for the detection of zero sequence current in the
case of increased phase currents.
3Io/In*100%

IRes Base IRes Bias[%]*Imax/In


sens [%]

Imax/In=Max(Ia,Ib,Ic )/In

Figure 1-16 Percentage characteristic for earth-fault detection

29 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.6 The power swing detection (PSD)


Power swings can be stable, or they can result in an out-of-step operation. Accordingly, the power
swing detection function can block the distance protection function in case of stable swings, or it
can generate a trip command if the system operates out of step (see Figure 1-17).
The characteristics are affected by the load encroachment settings: if the load setting (R Load)
is lower than the setting of the inner rectangle, then the rectangle will be distorted according to
the encroachment characteristic. According to this, the outer rectangle will be modified as well.

X
PSD Xinner
Stable swing

Stable swing
Out of Step
R
PSD Rinner
(original characteristic)

R Load
(distorted characteristic
because of load setting)

Ratio of the outer characteristics set by:


PSD R_out/R_in
PSD X_out/X_in

Figure 1-17 Characteristics of the power swing detection function

Table 1-29 The binary output status signals of the power swing detection function
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
Distance function power swing signals generated by the PSD module
DIS21_PSDDet_GrI_ PSD Detect Signal for power swing detection
DIS21_OutTr_GrI_ OutOfStep Trip Signal for out-of-step tripping condition
DIS21_PSDslow_GrI_ VerySlow Swing Signal for very slow power swing detection

All these binary signals can serve as binary inputs for the graphic equations, to be programmed
by the user.

The binary inputs are signals influencing the operation of the distance protection function. These
signals are the results of logic equations graphically edited by the user. E.g., the
DIS21_PSDBlk_GrO_ signal can be programmed using these inputs to block the power swing
detection.

Table 1-30 The binary input signals of the power swing detection function
BINARY INPUT SIGNALS SIGNAL TITLE EXPLANATION
DIS21_PSDBlk_GrO_ Block PSD Blocking signal for power swing detection

30 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

The parameters of the power swing detection function are explained in the following tables.

Table 1-31 The enumerated parameters of the power swing detection function
PARAMETER NAME TITLE SELECTION RANGE DEFAULT
Parameters for power swing detection (with out-of-step detection) concerning the number of the
involved phases:
DIS21_PSD_EPar_ Operation PSD Off,1 out of 3, 2 out of 3, 3 out of 3 Off
Parameter enabling “out-of-step” function:
DIS21_Out_EPar_ Oper. OutOfStep Off, On Off

Parameters for the individual zones to be blocked by the power swing detection (PSD) function:

Table 1-32 The boolean parameters of the power swing detection function
PARAMETER NAME TITLE DEFAULT EXPLANATION
DIS21_ PSDBlk1_BPar_ PSD Block Z1 0 1 for Zone1 to be blocked by PSD
DIS21_ PSDBlk2_BPar_ PSD Block Z2 0 1 for Zone2 to be blocked by PSD
DIS21_ PSDBlk3_BPar_ PSD Block Z3 0 1 for Zone3 to be blocked by PSD
DIS21_ PSDBlk4_BPar_ PSD Block Z4 0 1 for Zone4 to be blocked by PSD
DIS21_ PSDBlk5_BPar_ PSD Block Z5 0 1 for Zone5 to be blocked by PSD

Table 1-33 The integer parameters of the power swing detection function
PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
Definition of the ratio of the outside and inside rectangles of the characteristics for power swing
detection:
DIS21_RRat_IPar_ PSD R_out/R_in % 120 160 1 130
DIS21_XRat_IPar_ PSD X_out/X_in % 120 160 1 130

Table 1-34 The floating point parameters of the power swing detection function
PARAMETER NAME TITLE DIM. MIN MAX STEP DEFAULT
X and R setting of the internal rectangle of the characteristics:
DIS21_Xin_FPar PSD Xinner ohm 0.1 200 0.01 10
DIS21_Rin_FPar PSD Rinner ohm 0.1 200 0.01 10

Table 1-35 The timer parameters of the power swing detection function
PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
DIS21_PSDDel_TPar_ PSD Time Delay ms 10 1000 1 40
DIS21_PSDSlow_TPar_ Very Slow Swing ms 100 10000 1 500
DIS21_PSDRes_TPar_ PSD Reset ms 100 10000 1 500
DIS21_OutPs_TPar_ OutOfStep Pulse ms 50 10000 1 150

31 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

DIS21_PSD_EPar_eq_Off
NOT
S Q PSD_det_L1
AND OnDelay
ZL1_Within_Margs R
DIS21_PSDDet_TPar

ZL1 out of characteristics


S Q PSD_det_L2
AND OnDelay R
ZL2_Within_Margs
DIS21_PSDDet_TPar

ZL2 out of characteristics

AND S Q PSD_det_L3
OnDelay
ZL3_Within_Margs R
DIS21_PSDDet TPar

ZL3 out of characteristics

Figure 1-18 Power swing detection in the individual phases

Figure 1-18 shows that power swing is detected in the individual phases if the measured
impedance (Phase-to-ground loop for Zone1) is within the margins of the PSD characteristics for
the time span, given with parameter PSD Time Delay.

PSD_det_L1_
PSD_det_L2_ OR
PSD_det_L3_ Cont1→
DIS21_PSD_EPar_eq_1of3 AND OR
AND
DIS21_PSD_EPar_eq_2of3 AND

AND OR

DIS21_PSD_EPar_eq_3of3
AND
AND

AND

Cont1 RESET DIS21_PSDDet_GrI


DIS21_PSDRes_TPar AND
NOT
DIS21_PSDBlk_GrO
Jump_det_ NOT
NOT
DIS21_PSDSlow_GrI
AND
OnDelay RESET
DIS21_PSDSlow_TPar
DIS21_PSDRes_TPar

Figure 1-19 Power swing detection and slow power swing detection

According to Figure 1-19 , the power swings in the individual phases result in a power swing state
only if the combination of the phases corresponds to the parameter setting Operation PSD (which
can be 1 out of 3, 2 out of 3, 3 out of 3).

32 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

The function can be blocked using the enumerated parameter Operation PSD if it is set to “Off”.
The function can be blocked using the user-programmable graphic output status
DIS21_PSDBlk_GrO_.
This part of the function has two output status signals:
• DIS21_PSDDet_GrI_ to detect power swings. For instance, the user has the possibility
to block one or more distance protection zones during power swings using the
DIS21_Zn_Blk_GrO_ output status of the graphic equation editor.
• DIS21_PSDslow_GrI_ to detect slow power swings. This status has signaling purposes
only.

DIS21_PSD _Epar_eq_Off
NOT
AND
ZL1_Jump
Jump_det
RESET
AND OR
ZL2_Jump

AND
ZL3_Jump
DIS21_PSDRes_TPar

Figure 1-20 Impedance jump detection


Figure 1-20 shows that if impedance jump is detected (i.e., the change of the reactance and
resistance values between two consecutive samples is greater than ¼ of the PSD margin setting)
in any of the phases, then the “Jump_det” condition is true for the “reset” time.
The impedance jump is an internal signal. If during power swings the impedance “jumps”, this
means a fault during the swings and the power swing state must be terminated. (see Figure 1-19)

DIS21_PSD _Epar_eq_Off
NOT
AND RS OuOfStep_L1
ZL1_Instable

OuOfStep_L2
AND RS
ZL2_Instable

OuOfStep_L3
AND RS
ZL3_Instable

DIS21_Out _Epar_eq_Off
Jump_det OR NOT
DIS21_PSDSlow_GrI_

Figure 1-21 Out-of-step condition detection in the individual phases

If the swings are instable, the sign of the resistive component of the impedance at entrance is
opposite to the sign of the resistance calculated at leaving the characteristics. Figure 1-21 shows
that “Out-of-step condition” is detected in the individual phases if instable state is measured (i.e.,
the sign of the resistive component is opposite if the impedance enters and if it exits the PSD
characteristics). The function can be disabled using the enumerated parameter Operation PSD
if it is set to “Off”. This function also resets if the out-of-step function is disabled by the parameter
Oper OutOfStep by setting it to “Off”, or an impedance jump is detected (“Jump_det”) according
to Figure 1-20 or a slow swing is detected (see “DIS21_PSDslow_GrI_” on Figure 1-19 above).
In this case, the algorithm can generate the out-of-step tripping condition DIS21_OutTr_GrI_. The
duration of this impulse is determined by the parameter OutOfStep Pulse.

33 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

The “very slow swing” condition DIS21_PSDslow_GrI_ is generated if the duration of measuring
the impedance within the rectangle is longer than the parameter setting Very Slow Swing.
All these binary output signals can serve as binary inputs for the graphic equations, to be
programmed by the user.

OutOfSTep_L1
OutOfSTep_L2_ OR
OutOfSTep_L3 Cont2→
AND OR
DIS21_PDS_EPar_eq_1of3
AND

DIS21_PDS_EPar_eq_2of3 AND

AND OR

DIS21_PDS_EPar_eq_3of3 AND
AND

AND

DIS21_OutTr_GrI
Cont2 IMP AND

DIS21_OutPs_TPar
DIS21_PSDBlk_GrO NOT

Figure 1-22 Out-of-step trip command generation


According to Figure 1-22, the out-of-step conditions in the individual phases can result in an out-
of-step trip command impulse only if the combination of the phases corresponds to the parameter
setting Operation PSD (which can be 1 out of 3, 2 out of 3, 3 out of 3).
The duration of the trip command can be set using the parameter OutOfStep Pulse.

1.7 The distance-to-fault calculation (FAULT LOCATOR)


The distance protection function selects the faulty loop impedance (its positive sequence
component) and calculates the distance to fault based on the measured positive sequence
reactance and the total reactance of the line. This reference value is given as a parameter setting
Line Reactance. The calculated percentage value facilitates displaying the distance in kilometers
if the total length of the line is correctly set by the parameter Line Length.

The fault locator works only for the faults detected in Zone1 or Zone2 only.

Table 1-36 The floating point parameters


PARAMETER NAME TITLE DIM. MIN MAX STEP DEFAULT
DIS21_Lgth_FPar_ Line Length km 0.1 1000 0.01 100
DIS21_LReact_FPar_ Line Reactance ohm 0.1 200 0.01 10

34 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

1.8 The high-speed overcurrent protection function with


switch-onto-fault logic (HSOC SOTF)
The switch-onto-fault protection function can generate an immediate trip command if the function
is enabled and switch-onto-fault condition is detected. The condition of the operation can be the
non-directional starting signal of any distance protection zone as it is selected by a dedicated
parameter, or it can be the operation of the high-speed overcurrent protection function.

The high-speed overcurrent protection function operates if a sampled value of the phase current
is above the setting value.

Table 1-37 The binary output status signals of the SOTF function
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
SOTF function
The distance protection function
DIS21_SOTFTr_GrI_ SOTF Trip generated a trip command caused by
switching onto fault

The binary input is a signal influencing the operation of the distance protection function. This
signal is the result of logic equations graphically edited by the user.

Table 1-38 The binary input signals of the SOTF function


BINARY INPUT SIGNALS SIGNAL TITLE EXPLANATION
Status signal indicating switching-onto-
DIS21_SOTFCond_GrO_ SOTF COND.
fault-condition

The parameters of the SOTF function are explained in the following tables.

Table 1-39 The enumerated parameters of the SOTF logic


PARAMETER NAME TITLE SELECTION RANGE DEFAULT
Parameter for selecting one of the zones or “high speed overcurrent protection” for the “switch-
onto-fault” function:
Off, Zone1, Zone2, Zone3, Zone4,
DIS21_SOTFMd_EPar _ SOTF Zone Zone1
Zone5, HSOC

Parameters for the individual zones to be blocked by the power swing detection (PSD) function:

Table 1-40 The integer parameters of the SOTF logic


PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
Definition of the overcurrent setting for the switch-onto-fault function, for the case where the
DIS21_SOTFMd_EPar_ (SOTF Zone) parameter is set to “HSOC”:
DIS21_SOTFOC_IPar_ SOTF Current % 10 1000 1 200

35 Distance protection
www.protecta.hu
OPERATION PRINCIPLE

DIS21_SOFTCond_GrI
DIS21_Z1St _GrI AND
DIS21_SOTFMd_EPar_eq_Zone1

DIS21_Z2St _GrI AND


DIS21_SOTFMd_EPar_eq_Zone2 DIS21_SOTFTr_GrI
OR
OR
DIS21_Z3St _GrI AND
DIS21_SOTFMd_EPar_eq_Zone3

DIS21_Z4St _GrI AND


DIS21_SOTFMd_EPar_eq_Zone4

DIS21_Z5St _GrI AND


DIS21_SOTFMd_EPar_eq_Zone5

SOTF_HSOC_START AND
DIS21_SOTFMd_EPar_eq_HSOC

Figure 1-23 The internal logic of the SOTF function

In this diagram, the additional binary input signals:

Table 1-41 The binary input signals of the SOTF logic


BINARY INPUT SIGNALS SIGNAL TITLE EXPLANATION
Started state of the distance protection
DIS21_Z1St_GrI Z1 Start
Zone1 (non-directional)
Started state of the distance protection
DIS21_Z2St_GrI Z2 Start
Zone2 (non-directional)
Started state of the distance protection
DIS21_Z3St_GrI Z3 Start
Zone3 (non-directional)
Started state of the distance protection
DIS21_Z4St_GrI Z4 Start
Zone4 (non-directional)
Started state of the distance protection
DIS21_Z5St_GrI Z5 Start
Zone5 (non-directional)
SOTF_HSOC_START Started state of the HSOC function

1.9 The on-line measured values of the distance protection


function
Table 1-42 The measured values of the distance protection function
NAME TITLE EXPLANATION
DIS21_HTXkm_OLM_ Fault location Measured distance to fault in kilometers
DIS21_HTXohm_OLM_ Fault react. Measured reactance to fault
DIS21_L1N_R_OLM_ L1N loop R Measured positive sequence resistance in L1N loop
DIS21_L1N_X_OLM_ L1N loop X Measured positive sequence reactance in L1N loop
DIS21_L2N_R_OLM_ L2N loop R Measured positive sequence resistance in L2N loop
DIS21_L2N_X_OLM_ L2N loop X Measured positive sequence reactance in L2N loop
DIS21_L3N_R_OLM_ L3N loop R Measured positive sequence resistance in L3N loop
DIS21_L3N_X_OLM_ L3N loop X Measured positive sequence reactance in L3N loop
DIS21_L12_R_OLM_ L12 loop R Measured positive sequence resistance in L12 loop
DIS21_L12_X_OLM_ L12 loop X Measured positive sequence reactance in L12 loop
DIS21_L23_R_OLM_ L23 loop R Measured positive sequence resistance in L23 loop
DIS21_L23_X_OLM_ L23 loop X Measured positive sequence reactance in L23 loop
DIS21_L31_R_OLM_ L31 loop R Measured positive sequence resistance in L31 loop
DIS21_L31_X_OLM_ L31 loop X Measured positive sequence reactance in L31 loop

36 Distance protection
www.protecta.hu
OVERVIEW

2 Overview
The graphic appearance of the function block of the 5 zone HV distance protection function is
shown on Figure 2-1.

Figure 2-1 Graphic appearance of the function block of the distance protection function

37 Distance protection
www.protecta.hu
OVERVIEW

2.1 Settings
2.1.1 Parameters
The parameters are listed as they are seen on the local or remote HMI.

Table 2-1 Parameters of the distance function


TITLE DIM RANGE STEP DEFAULT EXPLANATION
General parameters
Definition of the minimal current
IPh Base Sens % 10 – 30 1 20 enabling the impedance
calculation
1st part of the of the zero
sequence current characteristic
IRes Base Sens % 10 – 50 1 10
enabling impedance calculation in
phase-to-earth loops
Slope of the zero sequence
current characteristic enabling
IRes Bias % 5 – 30 1 10
impedance calculation in phase-
to-earth loops
Definition of the polygon
Angle 2nd Quad deg 0 – 30 1 15 characteristic angle in the 2nd
quadrant of the impedance plane
Definition of the polygon
Angle 4th Quad deg 0 – 30 1 15 characteristic angle in the 4th
quadrant of the impedance plane
Line Angle deg 45 – 90 1 75 Definition of the line angle
L parallel line coupling factor
where Xom is the imaginary part
Par. Line Xom/3X1 - 0.00 – 5.00 0.01 0.00
of the mutual impedance between
the protected and the parallel line
R parallel line coupling factor
where Rom is the real part of the
Par. Line Rom/3R1 - 0.00 – 5.00 0.01 0.00
mutual impedance between the
protected and the parallel line
Data for the Fault Locator
Line Length km 0.1 – 1000.0 0.1 100.0
Reactance (X) of the line. The
fault locator is using the reactance
Line Reactance Ohm 0.01 10.00
of the fault and the line to
calculate the distance.
Load encroachment
Definition of the load angle of the
Load Angle deg 1 30
polygon characteristic
R Load ohm 0.01 10.00 Load encroachment setting
Specific parameters of each zone
Off, Forward, Selection of directionality for
Operation Zone1 - - Off
Backward Zone1
FALSE for Zone1 to generate trip
Zone1 Start Only - FALSE, TRUE - FALSE
command
TRUE for Zone1 to be blocked by
PSD Block Z1 - FALSE, TRUE - FALSE
PSD
Definition of the polygon
Zone Reduct Angle ohm 0 – 40 1 40 characteristic’s zone reduction
angle on the impedance plane
R setting for Zone1 in secondary
Zone1 R ohm 0.1 – 200.00
0.01 320.00 0.01 10.00 value. The characteristic crosses
the R axis at this point)

38 Distance protection
www.protecta.hu
OVERVIEW

X setting for Zone1 in secondary


Zone1 X ohm 0.1 – 200.00
0.01 320.00 0.01 10.00
value
L zero sequence current
Zone1 (Xo-X1)/3X1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone1
R zero sequence current
Zone1 (Ro-R1)/3R1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone1
Delay of Zone1: the time between
Zone1 Time Delay msec 0 – 60000 1 0 the rising edges of the Start and
Trip signals of Zone1
Off, Forward,
Selection of directionality for
Operation Zone2 - Backward, - Off
Zone2
NonDirectional
FALSE for Zone2 to generate trip
Zone2 Start Only - FALSE, TRUE - FALSE
command
TRUE for Zone2 to be blocked by
PSD Block Z2 - FALSE, TRUE - FALSE
PSD
R setting for Zone2 in secondary
Zone2 R ohm 0.10 – 200.00
0.01 320.00 0.01 10.00 value. The characteristic crosses
the R axis at this point)
X setting for Zone2 in secondary
Zone2 X ohm 0.01 – 200.00
0.10 320.00 0.01 10.00
value
L zero sequence current
Zone2 (Xo-X1)/3X1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone2
R zero sequence current
Zone2 (Ro-R1)/3R1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone2
Delay of Zone2: the timer runs
Zone2 Time Delay msec 40 – 60000 1 400 from the emergence of the fault to
the Trip signal
Off, Forward,
Selection of directionality for
Operation Zone3 - Backward, - Off
Zone3
NonDirectional
FALSE for Zone3 to generate trip
Zone3 Start Only - FALSE, TRUE - FALSE
command
TRUE for Zone3 to be blocked by
PSD Block Z3 - FALSE, TRUE - FALSE
PSD
R setting for Zone3 in secondary
Zone3 R ohm 0.10 – 200.00
0.01 320.00 0.01 10.00 value. The characteristic crosses
the R axis at this point)
X setting for Zone3 in secondary
Zone3 X ohm 0.10 – 200.00
0.01 320.00 0.01 10.00
value
L zero sequence current
Zone3 (Xo-X1)/3X1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone3
R zero sequence current
Zone3 (Ro-R1)/3R1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone3
Delay of Zone3: the timer runs
Zone3 Time Delay msec 40 – 60000 1 800 from the emergence of the fault to
the Trip signal
Off, Forward,
Selection of directionality for
Operation Zone4 - Backward, - Off
Zone4
NonDirectional
FALSE for Zone4 to generate trip
Zone4 Start Only - FALSE, TRUE - FALSE
command
TRUE for Zone4 to be blocked by
PSD Block Z4 - FALSE, TRUE - FALSE
PSD
R setting for Zone4 in secondary
Zone4 R ohm 0.10 – 320.00
0.01 200.00 0.01 10.00 value. The characteristic crosses
the R axis at this point)
X setting for Zone4 in secondary
Zone4 X ohm 0.10 – 200.00
0.01 320.00 0.01 10.00
value

39 Distance protection
www.protecta.hu
OVERVIEW

L zero sequence current


Zone4 (Xo-X1)/3X1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone4
R zero sequence current
Zone4 (Ro-R1)/3R1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone4
Delay of Zone4: the timer runs
Zone4 Time Delay msec 40 – 60000 1 2000 from the emergence of the fault to
the Trip signal
Off, Forward,
Selection of directionality for
Operation Zone5 - Backward, - Off
Zone5
NonDirectional
FALSE for Zone5 to generate trip
Zone5 Start Only - FALSE, TRUE - FALSE
command
TRUE for Zone5 to be blocked by
PSD Block Z5 - FALSE, TRUE - FALSE
PSD
R setting for Zone5 in secondary
Zone5 R ohm 0.10 – 200.00
0.01 320.00 0.01 10.00 value. The characteristic crosses
the R axis at this point)
X setting for Zone5 in secondary
Zone5 X ohm 0.10 – 200.00
0.01 320.00 0.01 10.00
value
L zero sequence current
Zone5 (Xo-X1)/3X1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone5
R zero sequence current
Zone5 (Ro-R1)/3R1 - 0.00 – 5.00 0.01 1.00
compensation factor for Zone5
Delay of Zone5: the timer runs
Zone5 Time Delay msec 40 – 60000 1 400 from the emergence of the fault to
the Trip signal
Parameters of the switch-onto-fault (SOTF) logic (see Chapter 1.8)
Off, Zone1, Zone2, The SOTF will be active for the
SOTF Zone - Zone3, Zone4, - Zone1 start in the selected zone (non-
Zone5, HSOC directional).
Definition of the overcurrent
setting for the switch-onto-fault
SOTF Current % 10 – 1000 1 200 function, for the case where the
SOTF Zone parameter is set to
“HSOC”
Parameters of the power swing detection (PSD) logic (see Chapter 1.6)
Enabling the powers swing
Off, 1 out of 3,
detection (with out-of-step
Operation PSD - 2 out of 3, - Off
capability) concerning the number
3 out of 3
of the involved phases
Oper OutOfStep - Off, On - Off Enabling the out-of-step function
Ratio of the R values of the
outside and inside rectangles of
PSD R_out/R_in % 120 – 160 1 130
the characteristics for power
swing detection
Ratio of the X values of the
outside and inside rectangles of
PSD X_out/X_in % 120 – 160 1 130
the characteristics for power
swing detection
X setting of the internal rectangle
PSD Xinner Ohm 0.10 – 200.00 0.01 10.00
of the characteristics
R setting of the internal rectangle
PSD Rinner Ohm 0.10 – 200.00 0.01 10.00
of the characteristics
If the impedance vector stays
within the two margins of the PSD
PSD Time Delay msec 10 – 1000 1 40 characteristics at least for this
time, the PSD detection signal is
generated

40 Distance protection
www.protecta.hu
OVERVIEW

The “very slow swing” condition is


generated if the duration of
Very Slow Swing msec 100 – 10000 1 500 measuring the impedance within
the rectangle is longer than the
setting
Setting for delaying the drop-off of
the PSD detection, very slow
PSD Reset msec 100 – 10000 1 500
swing detection and jump
detection signals
Length of the pulse generated by
OutOfStep Pulse msec 50 – 10000 1 150
the out-of-step function

41 Distance protection
www.protecta.hu
OVERVIEW

2.1.2 Characteristics
The function uses a 5-zone quadrilateral characteristic with load encroachment (see Figure 2-2).
jX

Angle 2nd Quad


Zone Reduct Angle

Zone X

Load Angle
Line Angle

R Load
Angle 4th Quad

Zone R

Figure 2-2 The polygon characteristics of the distance protection function on the
complex plane

Earth-fault detection is based on a 1-slope biased characteristic, see Figure 2-3.


3Io/In*100%

IRes Base IRes Bias[%]*Imax/In


sens [%]

Imax/In=Max(Ia,Ib,Ic )/In

Figure 2-3 Percentage characteristic for earth-fault detection

42 Distance protection
www.protecta.hu
OVERVIEW

Power swing and out-of-step detection is based on the characteristic shown in Figure 2-4.

PSD Xinner X
Stable swing

Stable swing

Out of Step
R

PSD Rinner
(original characteristic)

R Load

Load Angle

Ratio of the outer characteristics related to the inner one is set by:
• PSD R_out/R_in
• PSD X_out/X_in
The load encroachment setting for the polygon inside is the same as for the
distance characteristic:
• R Load
• Load Angle
The polygon outside can be calculated by shifting the load encroachment
points parallel to the „R” axis, by the ratio
• PSD R_out/R_in

Figure 2-4 Characteristics of the power swing detection function

43 Distance protection
www.protecta.hu
OVERVIEW

2.2 Function I/O


This section describes briefly the analogue and digital inputs and outputs of the function block.

2.2.1 Analogue inputs


The function uses the following analogue signals as inputs:
• Sampled values of the three phase voltages
• Sampled values of the three phase currents
• Sampled values of the zero sequence current of the parallel line
• Basic Fourier components of the three phase voltages
• Basic Fourier components of the three phase currents
• Basic Fourier component of the zero sequence current of the parallel line
• Calculated line-to-line values the three phase voltages
• Calculated positive, negative and zero sequence values the three phase voltages
• Calculated line-to-line values the three phase currents
• Calculated positive, negative and zero sequence values the three phase currents

2.2.2 Analogue outputs (measurements)


The measured values of the differential protection function are listed in the table below.

Table 2-2 The measured analogue values of the 5-zone HV distance protection function
MEASURED VALUE DIMENSION EXPLANATION
Calculated distance of the last fault cleared in
Fault location km
Zone1 or Zone2
Measured reactance of the last fault cleared in
Fault react. ohm
Zone1 or Zone2
L1N loop R ohm Currently measured resistance in the L1N loop
L1N loop X ohm Currently measured reactance in the L1N loop
L2N loop R ohm Currently measured resistance in the L2N loop
L2N loop X ohm Currently measured reactance in the L2N loop
L3N loop R ohm Currently measured resistance in the L3N loop
L3N loop X ohm Currently measured reactance in the L3N loop
L12 loop R ohm Currently measured resistance in the L12 loop
L12 loop X ohm Currently measured reactance in the L12 loop
L23 loop R ohm Currently measured resistance in the L23 loop
L23 loop X ohm Currently measured reactance in the L23 loop
L31 loop R ohm Currently measured resistance in the L31 loop
L31 loop X ohm Currently measured reactance in the L31 loop

2.2.3 Binary input signals (graphed output statuses)


The conditions of the inputs are defined by the user, applying the graphic equation editor (logic
editor). The part written in bold is seen on the function block in the logic editor.

Table 2-3 The binary input signals of the 5-zone HV distance protection function
BINARY INPUT SIGNAL EXPLANATION
Output status of a graphic equation defined by the user to
DIS21_VTS_GrO_ disable the function. Only the measurements work and are
displayed.
DIS21_Z1Blk_GrO_ Block Zone1
DIS21_Z2Blk_GrO_ Block Zone2
DIS21_Z3Blk_GrO_ Block Zone3
DIS21_Z4Blk_GrO_ Block Zone4
DIS21_Z5Blk_GrO_ Block Zone5
DIS21_PSDBlk_GrO_ Block the Power Swing Detection function
The SOTF logic is active while this input is active (see
DIS21_SOTFCond_GrO_
Chapter 1.8).

44 Distance protection
www.protecta.hu
OVERVIEW

2.2.4 Binary output signals (graphed input statuses)


The binary output status signals of the differential protection function. Parts written in bold are
seen on the function block in the logic editor.

Table 2-4 The binary output status signals of the 5-zone HV distance protection function
BINARY OUTPUT SIGNAL SIGNAL TITLE EXPLANATION
DIS21_GenStL1_GrI_ GenStart L1 General start in phase L1
DIS21_GenStL1_GrI_ GenStart L2 General start in phase L2
DIS21_GenStL1_GrI_ GenStart L3 General start in phase L3
The distance protection function generated a
DIS21_SOTFTr_GrI_ SOTF Trip
trip command caused by switching onto fault
Zone1 output signals
DIS21_Z1St_GrI_ Z1 Start General start of Zone1
DIS21_Z1StL1_GrI_ Z1 Start L1 Start in phase L1 of Zone1
DIS21_Z1StL2_GrI_ Z1 Start L2 Start in phase L2 of Zone1
DIS21_Z1StL3_GrI_ Z1 Start L3 Start in phase L3 of Zone1
DIS21_Z1Tr_GrI_ Z1 Trip Trip signal generated in Zone1
Zone2 output signals
DIS21_Z2St_GrI_ Z2 Start General start of Zone2
DIS21_Z2StL1_GrI_ Z2 Start L1 Start in phase L1 of Zone2
DIS21_Z2StL2_GrI_ Z2 Start L2 Start in phase L2 of Zone2
DIS21_Z2StL3_GrI_ Z2 Start L3 Start in phase L3 of Zone2
DIS21_Z2Tr_GrI_ Z2 Trip Trip signal generated in Zone2
Zone3 output signals
DIS21_Z3St_GrI_ Z3 Start General start of Zone3
DIS21_Z3StL1_GrI_ Z3 Start L1 Start in phase L1 of Zone3
DIS21_Z3StL2_GrI_ Z3 Start L2 Start in phase L2 of Zone3
DIS21_Z3StL3_GrI_ Z3 Start L3 Start in phase L3 of Zone3
DIS21_Z3Tr_GrI_ Z3 Trip Trip signal generated in Zone3
Zone4 output signals
DIS21_Z4St_GrI_ Z4 Start General start of Zone4
DIS21_Z4StL1_GrI_ Z4 Start L1 Start in phase L1 of Zone4
DIS21_Z4StL2_GrI_ Z4 Start L2 Start in phase L2 of Zone4
DIS21_Z4StL3_GrI_ Z4 Start L3 Start in phase L3 of Zone4
DIS21_Z4Tr_GrI_ Z4 Trip Trip signal generated in Zone4
Zone5 output signals
DIS21_Z5St_GrI_ Z5 Start General start of Zone5
DIS21_Z5StL1_GrI_ Z5 Start L1 Start in phase L1 of Zone5
DIS21_Z5StL2_GrI_ Z5 Start L2 Start in phase L2 of Zone5
DIS21_Z5StL3_GrI_ Z5 Start L3 Start in phase L3 of Zone5
DIS21_Z5Tr_GrI_ Z5 Trip Trip signal generated in Zone5
Power swing detection function output signals
DIS21_PSDDet_GrI_ PSD Detect Signal for power swing detection
DIS21_OutTr_GrI_ OutOfStep Trip Signal for out-of-step tripping condition
DIS21_PSDslow_GrI_ VerySlow Swing Signal for very slow power swing detection

45 Distance protection
www.protecta.hu
OVERVIEW

2.2.5 On-line data


Visible values on the on-line data page:

Table 2-5 The displayed on-line data of the 5-zone HV distance protection function
SIGNAL TITLE DIMENSION EXPLANATION
Calculated distance of the last fault cleared in Zone1
Fault location km
or Zone2
Measured reactance of the last fault cleared in Zone1
Fault react. ohm
or Zone2
L1N loop R ohm Currently measured resistance in the L1N loop
L1N loop X ohm Currently measured reactance in the L1N loop
L2N loop R ohm Currently measured resistance in the L2N loop
L2N loop X ohm Currently measured reactance in the L2N loop
L3N loop R ohm Currently measured resistance in the L3N loop
L3N loop X ohm Currently measured reactance in the L3N loop
L12 loop R ohm Currently measured resistance in the L12 loop
L12 loop X ohm Currently measured reactance in the L12 loop
L23 loop R ohm Currently measured resistance in the L23 loop
L23 loop X ohm Currently measured reactance in the L23 loop
L31 loop R ohm Currently measured resistance in the L31 loop
L31 loop X ohm Currently measured reactance in the L31 loop
GenStart L1 - General start in phase L1
GenStart L2 - General start in phase L2
GenStart L3 - General start in phase L3
The distance protection function generated a trip
SOTF Trip -
command caused by switching onto fault
Z1 Direction - Direction setting of Zone1 when it started
Z1 FaultLoop - Impedance loop of the fault was detected in in Zone1
Z1 Start - General start of Zone1
Z1 Start L1 - Start in phase L1 of Zone1
Z1 Start L2 - Start in phase L2 of Zone1
Z1 Start L3 - Start in phase L3 of Zone1
Z1 Trip - Trip signal generated in Zone1
Z2 Direction - Direction setting of Zone2 when it started
Z2 FaultLoop - Impedance loop of the fault was detected in in Zone2
Z2 Start - General start of Zone2
Z2 Start L1 - Start in phase L1 of Zone2
Z2 Start L2 - Start in phase L2 of Zone2
Z2 Start L3 - Start in phase L3 of Zone2
Z2 Trip - Trip signal generated in Zone2
Z3 Direction - Direction setting of Zone3 when it started
Z3 FaultLoop - Impedance loop of the fault was detected in in Zone3
Z3 Start - General start of Zone3
Z3 Start L1 - Start in phase L1 of Zone3
Z3 Start L2 - Start in phase L2 of Zone3
Z3 Start L3 - Start in phase L3 of Zone3
Z3 Trip - Trip signal generated in Zone3
Z4 Direction - Direction setting of Zone4 when it started
Z4 FaultLoop - Impedance loop of the fault was detected in in Zone4
Z4 Start - General start of Zone4
Z4 Start L1 - Start in phase L1 of Zone4
Z4 Start L2 - Start in phase L2 of Zone4
Z4 Start L3 - Start in phase L3 of Zone4
Z4 Trip - Trip signal generated in Zone4
Z5 Direction - Direction setting of Zone5 when it started
Z5 FaultLoop - Impedance loop of the fault was detected in in Zone5
Z5 Start - General start of Zone5

46 Distance protection
www.protecta.hu
OVERVIEW

Z5 Start L1 - Start in phase L1 of Zone5


Z5 Start L2 - Start in phase L2 of Zone5
Z5 Start L3 - Start in phase L3 of Zone5
Z5 Trip - Trip signal generated in Zone5
PSD Detect - Signal of detected power swing
OutOfStep Trip - Signal of out-of-step tripping condition
VerySlow Swing - Signal of detected very slow power swing

2.2.6 Events
The following events are generated in the event list, as well as sent to SCADA according to the
configuration.

Table 2-6 Events of the 5-zone HV distance protection function


EVENT VALUE EXPLANATION
Z1 Start off, on General start of Zone1
Z1 Trip off, on Trip signal generated in Zone1
N/A, L1-N, L2-N,
Impedance loop of the fault was
Z1 FaultLoop L3-N, L1-L2, L2-L3,
detected in in Zone1
L3-L1, L1-L2-L3
Z2 Start off, on General start of Zone2
Z2 Trip off, on Trip signal generated in Zone2
N/A, L1-N, L2-N,
Impedance loop of the fault was
Z2 FaultLoop L3-N, L1-L2, L2-L3,
detected in in Zone2
L3-L1, L1-L2-L3
Z3 Start off, on General start of Zone3
Z3 Trip off, on Trip signal generated in Zone3
N/A, L1-N, L2-N,
Impedance loop of the fault was
Z3 FaultLoop L3-N, L1-L2, L2-L3,
detected in in Zone3
L3-L1, L1-L2-L3
Z4 Start off, on General start of Zone4
Z4 Trip off, on Trip signal generated in Zone4
N/A, L1-N, L2-N,
Impedance loop of the fault was
Z4 FaultLoop L3-N, L1-L2, L2-L3,
detected in in Zone4
L3-L1, L1-L2-L3
Z5 Start off, on General start of Zone5
Z5 Trip off, on Trip signal generated in Zone5
N/A, L1-N, L2-N,
Impedance loop of the fault was
Z5 FaultLoop L3-N, L1-L2, L2-L3,
detected in in Zone5
L3-L1, L1-L2-L3
The SOTFCond input of the function
SOTF condition off, on
block is active.
The distance protection function
SOTF Trip off, on generated a trip command caused by
switching onto fault
Start L1 off, on General start in phase L1
Start L2 off, on General start in phase L2
Start L3 off, on General start in phase L3
The zero sequent current component
Start Neut off, on
is sufficient for earth fault calculation
PSD Detect off, on Power swing is detected
OutOfStep Trip off, on Out-of-step tripping condition is active
Calculated distance of the last fault
Fault Loc. km [measured distance]
cleared in Zone1 or Zone2

47 Distance protection
www.protecta.hu
OVERVIEW

2.2.7 Indication of the fault direction and loop in each Zone


There are internal status variables created to indicate the direction and the fault loop in the zones.
These variables are defined as integer statuses, which can be browsed in the EuroCAP program
to have them displayed.

Table 2-7 The displayed on-line data of the 5-zone HV distance protection function
INTEGER STATUS TITLE VALUE EXPLANATION

0: unknown Integer status signal indicating the


DIS21_Z1Dir_ISt_ Z1 Direction 1: forward direction of the measured
2: backward impedance in Zone1

0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z1Loop_ISt_ Z1 FaultLoop
4: L1-L2 of the fault detected in Zone1.
5: L2-L3
6: L3-L1
7: L1-L2-L3

0: unknown Integer status signal indicating the


DIS21_Z2Dir_ISt_ Z2 Direction 1: forward direction of the measured
2: backward impedance in Zone2

0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z2Loop_ISt_ Z2 FaultLoop
4: L1-L2 of the fault detected in Zone2.
5: L2-L3
6: L3-L1
7: L1-L2-L3

0: unknown Integer status signal indicating the


DIS21_Z3Dir_ISt_ Z3 Direction 1: forward direction of the measured
2: backward impedance in Zone3

0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z3Loop_ISt_ Z3 FaultLoop
4: L1-L2 of the fault detected in Zone3.
5: L2-L3
6: L3-L1
7: L1-L2-L3

0: unknown Integer status signal indicating the


DIS21_Z4Dir_ISt_ Z4 Direction 1: forward direction of the measured
2: backward impedance in Zone4

0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z4Loop_ISt_ Z4 FaultLoop
4: L1-L2 of the fault detected in Zone4.
5: L2-L3
6: L3-L1
7: L1-L2-L3

48 Distance protection
www.protecta.hu
OVERVIEW

0: unknown Integer status signal indicating the


DIS21_Z5Dir_ISt_ Z5 Direction 1: forward direction of the measured
2: backward impedance in Zone5

0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z5Loop_ISt_ Z5 FaultLoop
4: L1-L2 of the fault detected in Zone5.
5: L2-L3
6: L3-L1
7: L1-L2-L3

49 Distance protection
www.protecta.hu
OVERVIEW

2.3 Technical data


The technical data are based on the function block testing according to the directives of the
IEC 60255-121:2014 standard.

Table 2-8 Technical data of the 5-zone HV distance protection


FUNCTION VALUE
Number of zones 5
Rated current (In) 1/5A, parameter setting
Rated voltage (Un) 100/200V phase to phase, parameter setting
Effective range – current 50% – 2000% In
Operating range – current 10% – 5000% In
Effective range – voltage 10% – 130% Un
Operating range – voltage 0% – 130% Un
Effective and operating range – frequency
fn = 50 Hz 49Hz – 51Hz
fn = 60 Hz 58.8Hz – 61.2Hz
Impedance effective setting range (may
differ from the technical setting range of
the parameters)
Un = 57,74V; In = 1A 0.1 –200Ω
Un = 57,74V; In = 5A 0.1 – 40Ω
Characteristic accuracy X
Un = 57,74V In = 1A; fn = 50 Hz ± 1,6 %
Un = 57,74V In = 1A; fn = 60 Hz ± 1,8 %
Characteristic accuracy R
Un = 57,74V In = 1A; fn = 50 Hz ± 3,6 %
Un = 57,74V In = 1A; fn = 60 Hz ± 2,8 %
Basic directional accuracy ± 0,9°
Operate time (Zone 1) 27ms ± 8ms
Min. operate time 19 ms
Time delay accuracy (t = 30 sec) ± 2,7 ms
Reset time 68 ms
Reset ratio 1.1

2.3.1 Notes for testing


XRIO file is available for the function for setting up the tests easily and correctly.
Normally in the EuroProt+ devices the trip contacts are assigned to the Trip Logic function block,
and not to the protection function blocks. Because of this the testing personnel must make sure
that the Trip Logic is switched on (‘Operation’ parameter is set to other than ‘Off’) before starting
the testing, otherwise there will be no physical trip on the relay.
The set delays are to be evaluated as follows:
• Zone1: the delay is between the rising edges of the Start and Trip signal
• Zone2-5: the delay is between the injection of the fault and the Trip signal, so the setting
must be at least 35-40 ms (lower value will not result in lower operation times in these
zones)
By default, either output (AutoSOTF or ManSOTF) of the external “SOTF Condition” function block
is connected to the SOTFCond input of the Distance protection function block. See its description
on the Protecta webpage for more information (Switch-onto-fault preparation function). Before
testing, it is advised to check its logical connections to see what circumstances cause SOTF
operation in the Distance protection function.
The fault locator works only for the faults detected in Zone1 or Zone2 only.

50 Distance protection
www.protecta.hu
OVERVIEW

Earth fault compensation factors (when xrio file is not used):


The formula of the earth fault compensation factors is as follows
• R = (R0-R1)/3R1 for the resistance and
• L = (X0-X1)/3X1 for the reactance
Performing secondary injection to test the distance protection requires proper settings in the test
equipment as well. When using Omicron or ISA relay testers, please use the RE/RL and XE/XL
mode for earth fault compensation factor definition. These will correspond to the above formulas:
RE/RL =(R0-R1)/3R1 = R

XE/XL = (X0-X1)/3X1 = L

These data are needed to calculate the necessary factors. It is not possible to calculate the factors
using only the complex earth fault compensation factor.

51 Distance protection
www.protecta.hu

You might also like