Dis21 v2.0
Dis21 v2.0
Dis21 v2.0
Distance protection
ANSI: 21, IEC: Z<
VERSION INFORMATION
2 Distance protection
www.protecta.hu
CONTENTS
CONTENTS
3 Distance protection
www.protecta.hu
USED SYMBOLS
USED SYMBOLS
Additional information
4 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
1 Operation principle
The distance protection function provides main protection for overhead lines and cables of solidly
grounded networks. Its main features are as follows:
5 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
DIS21_HV
UL1
UL2
Z_CALC POLY SELECT
UL3 Binary
IL1 outputs
IL2
IL3
3Io_par
Measured
Binary
FAULT values
inputs
I_COND LOCATOR
Parameters PSD
HSOC
SOTF
Z_CALC calculates the impedances (R+jX) of the six measuring current loops:
• three phase-phase loops,
• three phase-ground loops.
POLY compares the calculated impedances with the setting values of the five polygon
characteristics. The result is the decision for all six measuring loops and for all five polygons if the
impedance is within the polygon.
SELECT is the phase selection algorithm for all five zones to decide which decision is caused by
a faulty loop and to exclude the false decisions in healthy loops.
6 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
I_COND calculates the current conditions necessary for the impedance calculation and for the
phase selection logic.
PSD is the module that detects power swings and generates out-of-step trip command,
influencing the distance protection function.
FAULT LOCATOR calculates the distance to fault after the trip command.
HSOC SOTF is a high-speed overcurrent protection function for the switch-onto-fault logic.
7 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
U L1 − U L 2
L1L2 Z L1L 2 =
I L1 − I L 2
U − U L3
Z L 2 L3 = L2
L2L3 I L 2 − I L3
U L3 − U L1
L3L1 Z L3L1 =
I L3 − I L1
U −U L2
L1L2N Z L1L 2 = L1 ZL1N , ZL2N
I L1 − I L 2
U − U L3
Z L 2 L3 = L2
L2L3N I L 2 − I L3 ZL2N , ZL3N
U L3 − U L1
L3L1N Z L3L1 = ZL3N, , ZL1N
I L3 − I L1
U L1
L1N Z L1N =
I L1 + 3I o K N
U L2
L2N Z L2 N =
I L 2 + 3I o K N
U L3
L3N Z L3 N =
I L 3 + 3I o K N
The central column of Table 1-1 contains the correct formula for calculation. The formulas
referred to in the right-hand-side column yield the same correct impedance value. In this column:
Z o − Z1 1 Z o
KN = = − 1
3Z1 3 Z1
is the complex earth fault compensation factor. Note that this is the base of the principle behind
the algorithm; the actual earth fault compensation factor is defined by using different parameters
in the function (see Chapter 1.2.2)
8 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Table 1-1 shows that the formula containing the complex earth fault compensation factor yields
the correct impedance value in case of phase-to-earth faults only; the other formula can be
applied in case of phase-to-phase faults without ground. In case of other kinds of faults (three-
phase (-to-earth), phase-to-phase-to-earth) both formulas give the correct impedance value if the
appropriate voltages and currents are applied.
The separation of the two types of equations is based on the presence or absence of the earth
(zero sequence) current. In case of a fault involving the earth (on a solidly grounded network),
and if the earth current is over a certain level, the formula containing the complex earth fault
compensation factor will be applied to calculate the correct impedance, which is proportional to
the distance-to-fault.
It can be proven that if the setting value of the complex earth fault compensation factor is correct,
the appropriate application of the formulas in Table 1-1will always yield the positive sequence
impedance between the fault location and the relay location.
9 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
For the equivalent impedance elements of the fault loop on the figure above, the following
differential equation can be written:
di
u = Ri + L
dt
If the real and the imaginary components of current and voltage phasors are substituted in this
equation, two equations are derived with the two unknown values R and L, so they can be
calculated.
This basic principle is realized in the algorithm by substituting the phasor components of the line-
to-line voltages for u and the difference of two phase currents in case of two- or three-phase
faults without ground for i. For example, in case of an L2L3 fault:
d (i L 2 − i L 3 )
u L 2 − u L 3 = R1 (i L 2 − i L 3 ) + L1
dt
In case of a phase-to-earth fault, the phasor components of the phase voltage and the phase
current modified by the zero sequence current have to be substituted:
d
u L1 = R1 (i L1 + R 3io + R 3iop ) + L1 (i L1 + L 3io + L 3iop )
dt
Where
R1 is the positive sequence resistance of the line or cable section between the fault location
and the relay location,
L1 is the positive sequence inductance of the line or cable section between the fault
location and the relay location,
L1 is the faulty phase,
3io =iL1+iL2+iL3 is the phasor component of the zero sequence current of the protected
line,
3iop =iL1p+iL2p+iL3p is the phasor component of the zero sequence current in parallel line,
and
10 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Ro − R1
R =
3R1
Lo − L1 X o − X 1
L = =
3L1 3X1
Rm
R =
3R1
Lm X
L = = m
3L1 3 X 1
Rm is the real part of the mutual impedance between the protected and the parallel line,
Lm is the mutual inductance between the protected and the parallel line.
The formula above shows that the factors for multiplying the R and L values contain different “”
and “ ” factors but they are real (not complex) numbers.
The applied numerical method is solving the differential equation of the faulty loop, based on three
consecutive samples.
11 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Binary V
inputs IV
I II
II
Parameters
I
ZL3 L1 _CALC
12 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Operation
DIS21_Z4_EPar_ Off, Forward, Backward, NonDirectional Off
Zone4
Operation
DIS21_Z5_EPar_ Off, Forward, Backward, NonDirectional Off
Zone5
Parameter for selecting one of the zones or “high speed overcurrent protection” for the “switch-
onto-fault” function:
SOTF Off, Zone1, Zone2, Zone3, Zone4,
DIS21_SOTFMd_EPar_ Zone1
Zone Zone5, HSOC
The outputs are the calculated positive-sequence impedances (R+jX) of the six measuring
current loops and, as different zero sequence current compensation factors can be set for the
individual zones, the impedances are calculated for each zone separately:
• Impedances of the three phase-phase loops,
• Impedances of the three phase-ground loops.
Z_CALC includes six practically identical software modules for impedance calculation:
• The three routines of the phase group are activated by phase voltages, phase currents
and the zero sequence current calculated from the phase current and the zero sequence
currents of the parallel line, as measured in a dedicated input.
• The three routines for the phase-to-phase loops get line-to-line voltages calculated from
the phase voltages and they get differences of the phase currents. They do not need zero
sequence currents for the calculation.
The calculated impedances are analogue outputs of the distance protection function. They serve
the purpose of checking possibility at commissioning.
13 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
CURRENT_OK Calc_A
NOT
AND
VTS_BLOCK NOT
Calc_B
VOLT_OK_HIGH AND
NOT
Calc_C
VOLT_OK_LOW AND
MEM_AVAIL
NOT Calc_D
AND
Calc_E
AND
NOT
Calc_F
AND
HEALTHY_PHASE_AVAIL
AND Calc_G
SOFT_COND OR
P_SOFT_Zn AND
Calc_H
AND
P_nondir
NOT
The decision needs logic parameter settings and, additionally, internal logic signals.
The explanation of these signals is as follows:
14 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
The outputs of the scheme of Figure 1-4 are calculation methods applied for impedance
calculation for the individual zones.
15 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
16 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
17 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
jX
Zone X
Load Angle
Line Angle
R Load
Angle 4th Quad
Zone R
Figure 1-5 The polygon characteristics of the distance protection function on the
complex plane
If a measured impedance point is inside the polygon, the algorithm generates the true value of
the related output binary signal.
The calculated impedance values are compared one by one with the setting values of the polygon
characteristics. This procedure is shown schematically in Figure 1-6.
The procedure is processed for each line-to-ground loop and for each line-to-line loop. Then this
is repeated for all five impedance stages. The result is the setting of 6 x 5 status variables, which
indicate that the calculated impedance is within the processed polygon, meaning that the
impedance stage has started.
18 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
I.
II.
III.
V IV.
IV V.
III
RL1+j XL1 V
RL2+j XL2 IV
RL3+j XL3
III
II
I
ZL1_n
V
ZL2_n
ZL3_n
IV
ZL1L2_n
III ZL2L3_n
II ZL3L1_n
I
RL1L2+j XL1L2
RL2L3+j XL2L3
RL3L1+j XL3L1
Parameters
Input values
The input values are calculated by the module Z_CALC.
19 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
The parameters needed in the polygon evaluation procedure of the distance protection function
are explained in the following tables.
20 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Table 1-14 Binary input signals influencing the phase selection logic
BINARY INPUT SIGNALS SIGNAL TITLE EXPLANATION
DIS21_Z1Blk_GrO_ Block Z1 Blocking of Zone 1
DIS21_Z2Blk_GrO_ Block Z2 Blocking of Zone 2
DIS21_Z3Blk_GrO_ Block Z3 Blocking of Zone 3
DIS21_Z4Blk_GrO_ Block Z4 Blocking of Zone 4
DIS21_Z5Blk_GrO_ Block Z5 Blocking of Zone 5
Status signal indicating switching-
DIS21_SOTFCond_GrO_ SOTF COND.
onto-fault condition
21 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Zone1 timer starts at the rising edge of its start signal, whereas the timer of the other zones
contains the time of the detection algorithm as well, therefore their minimum value is 40 ms.
In Figure 1-7 and in the subsequent figures “n = 1…5” means that the logic is repeated for all five
zones.
ZL1L2_n Z_3Ph_start_n_
OR
ZL2L3_n
ZL3L1_n
DIS21_cIL1_GrI AND
DIS21_cIL2_GrI
DIS21_cIL3_GrI
OR AND
22 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Table 1-21 Inputs needed to decide the three-phase start of the function
INPUT STATUS SIGNALS ZONES EXPLANATION
The calculated impedance of fault loop L1L2 is within
ZL1L2_n n=1…5
the zone characteristic
The calculated impedance of fault loop L2L3 is within
ZL2L3_n n=1…5
the zone characteristic
The calculated impedance of fault loop L3L1 is within
ZL3L1_n n=1…5
the zone characteristic
The current in phase L1 is sufficient for impedance
DIS21_cIL1_GrI n=1…5
calculation
The current in phase L2 is sufficient for impedance
DIS21_cIL2_GrI n=1…5
calculation
The current in phase L3 is sufficient for impedance
DIS21_cIL3_GrI n=1…5
calculation
Z_3Ph_start_n NOT
ZL1L2_n AND
ZL1L2_eq_mi
AND
ZL2L3_n NOT
ZL1_n AND OR
ZL2_n
UL1L2_It_5V
DIS21_cIL1_GrI
DIS21_clL2_GrI
OR AND
23 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Figure 1-9 and Figure 1-10 show a similar logic for loops “L2L3” and “L3L1”, respectively.
Z_3Ph_start_n OR NOT
ZL1L2_start_n
ZL2L3_n AND
ZL2L3_eq_mi
AND
ZL3L1_n NOT
ZL2_n AND OR
ZL3_n
UL2L3_It_5V
DIS21_cIL2_Gr
DIS21_clL3_Gr
OR AND
Z_3Ph_start_
ZL1L2_start_n
n OR NOT
ZL2L3_start_n
ZL3L1_n AND
ZL3L1_eq_mi
DIS21_cIo_GrI AND
NOT AND OR OR ZL3L1_Start
AND
ZL1L2_n NOT
ZL3_n AND OR
ZL1_n
UL3L1_It_5V
DIS21_cIL3_Gr
DIS21_clL1_Gr
OR AND
24 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Table 1-23 Inputs needed to decide phase-to-phase loop start of the distance protection
function
INPUT STATUS SIGNALS ZONES EXPLANATION
Z_3Ph_start_n n=1…5 Outputs of the previous decisions
ZL1L2_Start_n n=1…5 Outputs of the previous decisions
ZL2L3_Start_n n=1…5 Outputs of the previous decisions
The calculated impedance of fault loop L1L2 is
ZL1L2_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L2L3 is
ZL2L3_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L3L1 is
ZL3L1_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L1L2 is the
ZL1L2_equ_minLL n=1…5
smallest one
The calculated impedance of fault loop L2L3 is the
ZL2L3_ equ_minLL n=1…5
smallest one
The calculated impedance of fault loop L3L1 is the
ZL3L1_ equ_minLL n=1…5
smallest one
The calculated impedance of fault loop L1N is
ZL1_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L2N is
ZL2_n n=1…5
within the zone characteristic
The calculated impedance of fault loop L3N is
ZL3_n n=1…5
within the zone characteristic
The current in phase L1 is sufficient for impedance
DIS21_cIL1_GrI
calculation
The current in phase L2 is sufficient for impedance
DIS21_cIL2_GrI
calculation
The current in phase L3 is sufficient for impedance
DIS21_cIL3_GrI
calculation
The zero sequent current component is sufficient
DIS21_cIo_GrI_
for earth fault calculation
UL1L2_Lt_5V The L1L2 voltage is less than 5V
UL3L3_Lt_5V The L2L3 voltage is less than 5V
UL3L2_Lt_5V The L3L1 voltage is less than 5V
25 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL1_start_n
ZL1_n
ZL1_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL1_GrI
minLN_Lt_minLL
L
Figure 1-11 L1N fault detection in Zone “n” (n=1..5)
Figure 1-12 and Figure 1-13 show similar logic for loops “L2” and “L3” respectively.
Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL1_start_n
ZL2_start_n
ZL2_n
ZL2_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL2_GrI
minLN_It_minLL
Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL2_start_n
ZL2_start_n
ZL3_n
ZL3_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL3_GrI
minLN_It_minLL
26 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Table 1-25 Inputs needed to decide Phase-to-ground loop start of the distance protection
function
INPUT STATUS SIGNALS ZONES EXPLANATION
ZL1L2_Start_n n=1…5 Outputs of the previous decisions
ZL2L3_Start_n n=1…5 Outputs of the previous decisions
ZL3L1_Start_n n=1…5 Outputs of the previous decisions
ZL1_Start_n n=1…5 Outputs of the previous decisions
ZL2_Start_n n=1…5 Outputs of the previous decisions
The calculated impedance of fault loop L1 is the
ZL1_equ_minLN n=1…5
smallest one
The calculated impedance of fault loop L2 is the
ZL2_ equ_minLN n=1…5
smallest one
The calculated impedance of fault loop L3 is the
ZL3_ equ_minLN n=1…5
smallest one
The calculated impedance of fault loop L1N is within
ZL1_n n=1…5
the zone characteristic
The calculated impedance of fault loop L2N is within
ZL2_n n=1…5
the zone characteristic
The calculated impedance of fault loop L3N is within
ZL3_n n=1…5
the zone characteristic
The current in phase L1 is sufficient for impedance
DIS21_cIL1_GrI n=1…5
calculation
The current in phase L2 is sufficient for impedance
DIS21_cIL2_GrI n=1…5
calculation
The current in phase L3 is sufficient for impedance
DIS21_cIL3_GrI n=1…5
calculation
The zero sequence current component is sufficient for
DIS21_cIo_GrI n=1…5
impedance calculation in LN loops
Figure 1-14 shows how the signals are processed for the output signals of the distance protection
function.
DIS21_Zn_Epar_eq_Off
OR NOT
DIS21_Zn_Blk_GrO_
AND DIS21_ZnStL1_GrI
Z_3Ph_start_n
ZL1L2_start_n
ZL3L1_start_n OR
ZL1_start_n
DIS21_ZnStL2_GrI
AND
ZL2L3_start_n OR
ZL2_start_n
AND DIS21_ZnStL3_GrI
OR
ZL3_start_n DIS21_ZnSt_GrI
OR
DIS21_ZnTr_GrI
AND DELAY
DIS21_ZnSt_BPar
NOT
DIS21_ZnDel_TPar
27 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
• The operation of the distance protection may be blocked either by parameter setting
(DIS21_Zn_EPar_eq_Off) or by binary input (DIS21_Zn_Blk_GrO_)
• Starting in phase L1 if this phase is involved in the fault (DIS21_ZnStL1_GrI),
• Starting in phase L2 if this phase is involved in the fault (DIS21_ZnStL2_GrI),
• Starting in phase L2 if this phase is involved in the fault (DIS21_ZnStL3_GrI),
• General start if any of the phases is involved in the fault (DIS21_ZnSt_GrI),
• A trip command (DIS21_ZnTr_GrI) is generated after the timer Zn_Delay has expired.
This timer is started if the zone is started and it is not assigned to “Start signal only”, using
the parameter DIS21_ZnSt_BPar. The time delay is set by the timer parameter
DIS21_ZnDel_TPar.
Figure 1-15 shows the method of post-processing the binary output signals to generate general
start signals for the phases individually and separately for zones 2 to 5.
DIS21_Z1StL1_GrI DIS21_GenStL1_GrI
OR
DIS21_Z2StL1_GrI DIS21_Z25StL1_GrI
DIS21_Z3StL1_GrI OR
DIS21_Z4StL1_GrI
DIS21_Z5StL1_GrI
DIS21_Z1StL2_GrI DIS21_GenStL2_GrI
OR
DIS21_Z2StL2_GrI DIS21_Z25StL2_GrI
DIS21_Z3StL2_GrI
DIS21_Z4StL2_GrI OR
DIS21_Z5StL2_GrI
DIS21_Z1StL3_GrI DIS21_GenStL3_GrI
OR
DIS21_Z2StL3_GrI DIS21_Z25StL3_GrI
DIS21_Z3StL3_GrI OR
DIS21_Z4StL3_GrI
DIS21_Z5StL3_GrI
Figure 1-15 General start in the phase-to-ground loops separately for Zones 2-to 5
The separate phase identification signals for Zones 2-5 are not published.
28 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
Table 1-27 The binary output status signals of the current conditions module
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
Distance function start conditions generated by the I_COND module (these signals are not
published)
The zero sequent current component is
DIS21_cIo_GrI_ Io condition
sufficient for earth fault calculation
The current in phase L1 is sufficient for
DIS21_cIL1_GrI_ I L1 condition
impedance calculation
The current in phase L2 is sufficient for
DIS21_cIL2_GrI_ I L2 condition
impedance calculation
The current in phase L3 is sufficient for
DIS21_cIL3_GrI_ I L3 condition
impedance calculation
The current is considered to be sufficient for impedance calculation if it is above the level set by
parameter IPh Base Sens.
To decide the presence or absence of the zero sequence current, biased characteristics are
applied (see Figure 1-16). The minimal setting current IRes Base Sens and a percentage biasing
IRes Bias must be set. The biasing is applied for the detection of zero sequence current in the
case of increased phase currents.
3Io/In*100%
Imax/In=Max(Ia,Ib,Ic )/In
29 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
X
PSD Xinner
Stable swing
Stable swing
Out of Step
R
PSD Rinner
(original characteristic)
R Load
(distorted characteristic
because of load setting)
Table 1-29 The binary output status signals of the power swing detection function
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
Distance function power swing signals generated by the PSD module
DIS21_PSDDet_GrI_ PSD Detect Signal for power swing detection
DIS21_OutTr_GrI_ OutOfStep Trip Signal for out-of-step tripping condition
DIS21_PSDslow_GrI_ VerySlow Swing Signal for very slow power swing detection
All these binary signals can serve as binary inputs for the graphic equations, to be programmed
by the user.
The binary inputs are signals influencing the operation of the distance protection function. These
signals are the results of logic equations graphically edited by the user. E.g., the
DIS21_PSDBlk_GrO_ signal can be programmed using these inputs to block the power swing
detection.
Table 1-30 The binary input signals of the power swing detection function
BINARY INPUT SIGNALS SIGNAL TITLE EXPLANATION
DIS21_PSDBlk_GrO_ Block PSD Blocking signal for power swing detection
30 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
The parameters of the power swing detection function are explained in the following tables.
Table 1-31 The enumerated parameters of the power swing detection function
PARAMETER NAME TITLE SELECTION RANGE DEFAULT
Parameters for power swing detection (with out-of-step detection) concerning the number of the
involved phases:
DIS21_PSD_EPar_ Operation PSD Off,1 out of 3, 2 out of 3, 3 out of 3 Off
Parameter enabling “out-of-step” function:
DIS21_Out_EPar_ Oper. OutOfStep Off, On Off
Parameters for the individual zones to be blocked by the power swing detection (PSD) function:
Table 1-32 The boolean parameters of the power swing detection function
PARAMETER NAME TITLE DEFAULT EXPLANATION
DIS21_ PSDBlk1_BPar_ PSD Block Z1 0 1 for Zone1 to be blocked by PSD
DIS21_ PSDBlk2_BPar_ PSD Block Z2 0 1 for Zone2 to be blocked by PSD
DIS21_ PSDBlk3_BPar_ PSD Block Z3 0 1 for Zone3 to be blocked by PSD
DIS21_ PSDBlk4_BPar_ PSD Block Z4 0 1 for Zone4 to be blocked by PSD
DIS21_ PSDBlk5_BPar_ PSD Block Z5 0 1 for Zone5 to be blocked by PSD
Table 1-33 The integer parameters of the power swing detection function
PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
Definition of the ratio of the outside and inside rectangles of the characteristics for power swing
detection:
DIS21_RRat_IPar_ PSD R_out/R_in % 120 160 1 130
DIS21_XRat_IPar_ PSD X_out/X_in % 120 160 1 130
Table 1-34 The floating point parameters of the power swing detection function
PARAMETER NAME TITLE DIM. MIN MAX STEP DEFAULT
X and R setting of the internal rectangle of the characteristics:
DIS21_Xin_FPar PSD Xinner ohm 0.1 200 0.01 10
DIS21_Rin_FPar PSD Rinner ohm 0.1 200 0.01 10
Table 1-35 The timer parameters of the power swing detection function
PARAMETER NAME TITLE UNIT MIN MAX STEP DEFAULT
DIS21_PSDDel_TPar_ PSD Time Delay ms 10 1000 1 40
DIS21_PSDSlow_TPar_ Very Slow Swing ms 100 10000 1 500
DIS21_PSDRes_TPar_ PSD Reset ms 100 10000 1 500
DIS21_OutPs_TPar_ OutOfStep Pulse ms 50 10000 1 150
31 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
DIS21_PSD_EPar_eq_Off
NOT
S Q PSD_det_L1
AND OnDelay
ZL1_Within_Margs R
DIS21_PSDDet_TPar
AND S Q PSD_det_L3
OnDelay
ZL3_Within_Margs R
DIS21_PSDDet TPar
Figure 1-18 shows that power swing is detected in the individual phases if the measured
impedance (Phase-to-ground loop for Zone1) is within the margins of the PSD characteristics for
the time span, given with parameter PSD Time Delay.
PSD_det_L1_
PSD_det_L2_ OR
PSD_det_L3_ Cont1→
DIS21_PSD_EPar_eq_1of3 AND OR
AND
DIS21_PSD_EPar_eq_2of3 AND
AND OR
DIS21_PSD_EPar_eq_3of3
AND
AND
AND
Figure 1-19 Power swing detection and slow power swing detection
According to Figure 1-19 , the power swings in the individual phases result in a power swing state
only if the combination of the phases corresponds to the parameter setting Operation PSD (which
can be 1 out of 3, 2 out of 3, 3 out of 3).
32 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
The function can be blocked using the enumerated parameter Operation PSD if it is set to “Off”.
The function can be blocked using the user-programmable graphic output status
DIS21_PSDBlk_GrO_.
This part of the function has two output status signals:
• DIS21_PSDDet_GrI_ to detect power swings. For instance, the user has the possibility
to block one or more distance protection zones during power swings using the
DIS21_Zn_Blk_GrO_ output status of the graphic equation editor.
• DIS21_PSDslow_GrI_ to detect slow power swings. This status has signaling purposes
only.
DIS21_PSD _Epar_eq_Off
NOT
AND
ZL1_Jump
Jump_det
RESET
AND OR
ZL2_Jump
AND
ZL3_Jump
DIS21_PSDRes_TPar
DIS21_PSD _Epar_eq_Off
NOT
AND RS OuOfStep_L1
ZL1_Instable
OuOfStep_L2
AND RS
ZL2_Instable
OuOfStep_L3
AND RS
ZL3_Instable
DIS21_Out _Epar_eq_Off
Jump_det OR NOT
DIS21_PSDSlow_GrI_
If the swings are instable, the sign of the resistive component of the impedance at entrance is
opposite to the sign of the resistance calculated at leaving the characteristics. Figure 1-21 shows
that “Out-of-step condition” is detected in the individual phases if instable state is measured (i.e.,
the sign of the resistive component is opposite if the impedance enters and if it exits the PSD
characteristics). The function can be disabled using the enumerated parameter Operation PSD
if it is set to “Off”. This function also resets if the out-of-step function is disabled by the parameter
Oper OutOfStep by setting it to “Off”, or an impedance jump is detected (“Jump_det”) according
to Figure 1-20 or a slow swing is detected (see “DIS21_PSDslow_GrI_” on Figure 1-19 above).
In this case, the algorithm can generate the out-of-step tripping condition DIS21_OutTr_GrI_. The
duration of this impulse is determined by the parameter OutOfStep Pulse.
33 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
The “very slow swing” condition DIS21_PSDslow_GrI_ is generated if the duration of measuring
the impedance within the rectangle is longer than the parameter setting Very Slow Swing.
All these binary output signals can serve as binary inputs for the graphic equations, to be
programmed by the user.
OutOfSTep_L1
OutOfSTep_L2_ OR
OutOfSTep_L3 Cont2→
AND OR
DIS21_PDS_EPar_eq_1of3
AND
DIS21_PDS_EPar_eq_2of3 AND
AND OR
DIS21_PDS_EPar_eq_3of3 AND
AND
AND
DIS21_OutTr_GrI
Cont2 IMP AND
DIS21_OutPs_TPar
DIS21_PSDBlk_GrO NOT
The fault locator works only for the faults detected in Zone1 or Zone2 only.
34 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
The high-speed overcurrent protection function operates if a sampled value of the phase current
is above the setting value.
Table 1-37 The binary output status signals of the SOTF function
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
SOTF function
The distance protection function
DIS21_SOTFTr_GrI_ SOTF Trip generated a trip command caused by
switching onto fault
The binary input is a signal influencing the operation of the distance protection function. This
signal is the result of logic equations graphically edited by the user.
The parameters of the SOTF function are explained in the following tables.
Parameters for the individual zones to be blocked by the power swing detection (PSD) function:
35 Distance protection
www.protecta.hu
OPERATION PRINCIPLE
DIS21_SOFTCond_GrI
DIS21_Z1St _GrI AND
DIS21_SOTFMd_EPar_eq_Zone1
SOTF_HSOC_START AND
DIS21_SOTFMd_EPar_eq_HSOC
36 Distance protection
www.protecta.hu
OVERVIEW
2 Overview
The graphic appearance of the function block of the 5 zone HV distance protection function is
shown on Figure 2-1.
Figure 2-1 Graphic appearance of the function block of the distance protection function
37 Distance protection
www.protecta.hu
OVERVIEW
2.1 Settings
2.1.1 Parameters
The parameters are listed as they are seen on the local or remote HMI.
38 Distance protection
www.protecta.hu
OVERVIEW
39 Distance protection
www.protecta.hu
OVERVIEW
40 Distance protection
www.protecta.hu
OVERVIEW
41 Distance protection
www.protecta.hu
OVERVIEW
2.1.2 Characteristics
The function uses a 5-zone quadrilateral characteristic with load encroachment (see Figure 2-2).
jX
Zone X
Load Angle
Line Angle
R Load
Angle 4th Quad
Zone R
Figure 2-2 The polygon characteristics of the distance protection function on the
complex plane
Imax/In=Max(Ia,Ib,Ic )/In
42 Distance protection
www.protecta.hu
OVERVIEW
Power swing and out-of-step detection is based on the characteristic shown in Figure 2-4.
PSD Xinner X
Stable swing
Stable swing
Out of Step
R
PSD Rinner
(original characteristic)
R Load
Load Angle
Ratio of the outer characteristics related to the inner one is set by:
• PSD R_out/R_in
• PSD X_out/X_in
The load encroachment setting for the polygon inside is the same as for the
distance characteristic:
• R Load
• Load Angle
The polygon outside can be calculated by shifting the load encroachment
points parallel to the „R” axis, by the ratio
• PSD R_out/R_in
43 Distance protection
www.protecta.hu
OVERVIEW
Table 2-2 The measured analogue values of the 5-zone HV distance protection function
MEASURED VALUE DIMENSION EXPLANATION
Calculated distance of the last fault cleared in
Fault location km
Zone1 or Zone2
Measured reactance of the last fault cleared in
Fault react. ohm
Zone1 or Zone2
L1N loop R ohm Currently measured resistance in the L1N loop
L1N loop X ohm Currently measured reactance in the L1N loop
L2N loop R ohm Currently measured resistance in the L2N loop
L2N loop X ohm Currently measured reactance in the L2N loop
L3N loop R ohm Currently measured resistance in the L3N loop
L3N loop X ohm Currently measured reactance in the L3N loop
L12 loop R ohm Currently measured resistance in the L12 loop
L12 loop X ohm Currently measured reactance in the L12 loop
L23 loop R ohm Currently measured resistance in the L23 loop
L23 loop X ohm Currently measured reactance in the L23 loop
L31 loop R ohm Currently measured resistance in the L31 loop
L31 loop X ohm Currently measured reactance in the L31 loop
Table 2-3 The binary input signals of the 5-zone HV distance protection function
BINARY INPUT SIGNAL EXPLANATION
Output status of a graphic equation defined by the user to
DIS21_VTS_GrO_ disable the function. Only the measurements work and are
displayed.
DIS21_Z1Blk_GrO_ Block Zone1
DIS21_Z2Blk_GrO_ Block Zone2
DIS21_Z3Blk_GrO_ Block Zone3
DIS21_Z4Blk_GrO_ Block Zone4
DIS21_Z5Blk_GrO_ Block Zone5
DIS21_PSDBlk_GrO_ Block the Power Swing Detection function
The SOTF logic is active while this input is active (see
DIS21_SOTFCond_GrO_
Chapter 1.8).
44 Distance protection
www.protecta.hu
OVERVIEW
Table 2-4 The binary output status signals of the 5-zone HV distance protection function
BINARY OUTPUT SIGNAL SIGNAL TITLE EXPLANATION
DIS21_GenStL1_GrI_ GenStart L1 General start in phase L1
DIS21_GenStL1_GrI_ GenStart L2 General start in phase L2
DIS21_GenStL1_GrI_ GenStart L3 General start in phase L3
The distance protection function generated a
DIS21_SOTFTr_GrI_ SOTF Trip
trip command caused by switching onto fault
Zone1 output signals
DIS21_Z1St_GrI_ Z1 Start General start of Zone1
DIS21_Z1StL1_GrI_ Z1 Start L1 Start in phase L1 of Zone1
DIS21_Z1StL2_GrI_ Z1 Start L2 Start in phase L2 of Zone1
DIS21_Z1StL3_GrI_ Z1 Start L3 Start in phase L3 of Zone1
DIS21_Z1Tr_GrI_ Z1 Trip Trip signal generated in Zone1
Zone2 output signals
DIS21_Z2St_GrI_ Z2 Start General start of Zone2
DIS21_Z2StL1_GrI_ Z2 Start L1 Start in phase L1 of Zone2
DIS21_Z2StL2_GrI_ Z2 Start L2 Start in phase L2 of Zone2
DIS21_Z2StL3_GrI_ Z2 Start L3 Start in phase L3 of Zone2
DIS21_Z2Tr_GrI_ Z2 Trip Trip signal generated in Zone2
Zone3 output signals
DIS21_Z3St_GrI_ Z3 Start General start of Zone3
DIS21_Z3StL1_GrI_ Z3 Start L1 Start in phase L1 of Zone3
DIS21_Z3StL2_GrI_ Z3 Start L2 Start in phase L2 of Zone3
DIS21_Z3StL3_GrI_ Z3 Start L3 Start in phase L3 of Zone3
DIS21_Z3Tr_GrI_ Z3 Trip Trip signal generated in Zone3
Zone4 output signals
DIS21_Z4St_GrI_ Z4 Start General start of Zone4
DIS21_Z4StL1_GrI_ Z4 Start L1 Start in phase L1 of Zone4
DIS21_Z4StL2_GrI_ Z4 Start L2 Start in phase L2 of Zone4
DIS21_Z4StL3_GrI_ Z4 Start L3 Start in phase L3 of Zone4
DIS21_Z4Tr_GrI_ Z4 Trip Trip signal generated in Zone4
Zone5 output signals
DIS21_Z5St_GrI_ Z5 Start General start of Zone5
DIS21_Z5StL1_GrI_ Z5 Start L1 Start in phase L1 of Zone5
DIS21_Z5StL2_GrI_ Z5 Start L2 Start in phase L2 of Zone5
DIS21_Z5StL3_GrI_ Z5 Start L3 Start in phase L3 of Zone5
DIS21_Z5Tr_GrI_ Z5 Trip Trip signal generated in Zone5
Power swing detection function output signals
DIS21_PSDDet_GrI_ PSD Detect Signal for power swing detection
DIS21_OutTr_GrI_ OutOfStep Trip Signal for out-of-step tripping condition
DIS21_PSDslow_GrI_ VerySlow Swing Signal for very slow power swing detection
45 Distance protection
www.protecta.hu
OVERVIEW
Table 2-5 The displayed on-line data of the 5-zone HV distance protection function
SIGNAL TITLE DIMENSION EXPLANATION
Calculated distance of the last fault cleared in Zone1
Fault location km
or Zone2
Measured reactance of the last fault cleared in Zone1
Fault react. ohm
or Zone2
L1N loop R ohm Currently measured resistance in the L1N loop
L1N loop X ohm Currently measured reactance in the L1N loop
L2N loop R ohm Currently measured resistance in the L2N loop
L2N loop X ohm Currently measured reactance in the L2N loop
L3N loop R ohm Currently measured resistance in the L3N loop
L3N loop X ohm Currently measured reactance in the L3N loop
L12 loop R ohm Currently measured resistance in the L12 loop
L12 loop X ohm Currently measured reactance in the L12 loop
L23 loop R ohm Currently measured resistance in the L23 loop
L23 loop X ohm Currently measured reactance in the L23 loop
L31 loop R ohm Currently measured resistance in the L31 loop
L31 loop X ohm Currently measured reactance in the L31 loop
GenStart L1 - General start in phase L1
GenStart L2 - General start in phase L2
GenStart L3 - General start in phase L3
The distance protection function generated a trip
SOTF Trip -
command caused by switching onto fault
Z1 Direction - Direction setting of Zone1 when it started
Z1 FaultLoop - Impedance loop of the fault was detected in in Zone1
Z1 Start - General start of Zone1
Z1 Start L1 - Start in phase L1 of Zone1
Z1 Start L2 - Start in phase L2 of Zone1
Z1 Start L3 - Start in phase L3 of Zone1
Z1 Trip - Trip signal generated in Zone1
Z2 Direction - Direction setting of Zone2 when it started
Z2 FaultLoop - Impedance loop of the fault was detected in in Zone2
Z2 Start - General start of Zone2
Z2 Start L1 - Start in phase L1 of Zone2
Z2 Start L2 - Start in phase L2 of Zone2
Z2 Start L3 - Start in phase L3 of Zone2
Z2 Trip - Trip signal generated in Zone2
Z3 Direction - Direction setting of Zone3 when it started
Z3 FaultLoop - Impedance loop of the fault was detected in in Zone3
Z3 Start - General start of Zone3
Z3 Start L1 - Start in phase L1 of Zone3
Z3 Start L2 - Start in phase L2 of Zone3
Z3 Start L3 - Start in phase L3 of Zone3
Z3 Trip - Trip signal generated in Zone3
Z4 Direction - Direction setting of Zone4 when it started
Z4 FaultLoop - Impedance loop of the fault was detected in in Zone4
Z4 Start - General start of Zone4
Z4 Start L1 - Start in phase L1 of Zone4
Z4 Start L2 - Start in phase L2 of Zone4
Z4 Start L3 - Start in phase L3 of Zone4
Z4 Trip - Trip signal generated in Zone4
Z5 Direction - Direction setting of Zone5 when it started
Z5 FaultLoop - Impedance loop of the fault was detected in in Zone5
Z5 Start - General start of Zone5
46 Distance protection
www.protecta.hu
OVERVIEW
2.2.6 Events
The following events are generated in the event list, as well as sent to SCADA according to the
configuration.
47 Distance protection
www.protecta.hu
OVERVIEW
Table 2-7 The displayed on-line data of the 5-zone HV distance protection function
INTEGER STATUS TITLE VALUE EXPLANATION
0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z1Loop_ISt_ Z1 FaultLoop
4: L1-L2 of the fault detected in Zone1.
5: L2-L3
6: L3-L1
7: L1-L2-L3
0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z2Loop_ISt_ Z2 FaultLoop
4: L1-L2 of the fault detected in Zone2.
5: L2-L3
6: L3-L1
7: L1-L2-L3
0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z3Loop_ISt_ Z3 FaultLoop
4: L1-L2 of the fault detected in Zone3.
5: L2-L3
6: L3-L1
7: L1-L2-L3
0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z4Loop_ISt_ Z4 FaultLoop
4: L1-L2 of the fault detected in Zone4.
5: L2-L3
6: L3-L1
7: L1-L2-L3
48 Distance protection
www.protecta.hu
OVERVIEW
0: N/A
1: L1-N
2: L2-N
3: L3-N Indication of the impedance loop
DIS21_Z5Loop_ISt_ Z5 FaultLoop
4: L1-L2 of the fault detected in Zone5.
5: L2-L3
6: L3-L1
7: L1-L2-L3
49 Distance protection
www.protecta.hu
OVERVIEW
50 Distance protection
www.protecta.hu
OVERVIEW
XE/XL = (X0-X1)/3X1 = L
These data are needed to calculate the necessary factors. It is not possible to calculate the factors
using only the complex earth fault compensation factor.
51 Distance protection
www.protecta.hu