Dis21 Mho v1.0
Dis21 Mho v1.0
Dis21 Mho v1.0
characteristics;
function block description
CONTENTS
DIS21_HV
UL1
UL2
UL3 Z_CALC MHO SELECT
Binary
IL1 outputs
IL2
IL3
3Io_par
Measured
Binary
FAULT values
inputs
I_COND LOCATOR
Parameters PSD
HSOC
SOFT
Z_CALC calculates the impedances (R+jX) of the six measuring current loops:
three phase-phase loops,
three phase-ground loops.
MHO compares the calculated impedances with the setting values of the five MHO
characteristics. The result is the decision for all six measuring loops and for all five circles if
the impedance is within the MHO circle.
SELECT is the phase selection algorithm for all five zones to decide which decision is caused
by a faulty loop and to exclude the false decisions in healthy loops.
I_COND calculates the current conditions necessary for the impedance calculation and for
the phase selection logic.
PSD is the module that detects power swings and generates out-of-step trip command,
influencing the distance protection function.
FAULT LOCATOR calculates the distance to fault after the trip command.
HSOC SOTF is a high-speed overcurrent protection function for the switch-onto-fault logic.
For simplicity, the influence of the zero sequence current of the parallel line is not considered
in these equations.
Fault Calculation of Z Other possible calculation
U L 2 U L3
Z L 2L3 ZL1L2 , ZL2L3 , ZL3L1
L1L2L3(N) I L 2 I L3 ZL1N , ZL2N , ZL3N
U L1 U L 2
L1L2 Z L1L 2
I L1 I L 2
U L 2 U L3
Z L 2L3
L2L3 I L 2 I L3
U L 3 U L1
L3L1 Z L3 L1
I L 3 I L1
U L1 U L 2
L1L2N Z L1L 2 ZL1N , ZL2N
I L1 I L 2
U L 2 U L3
L2L3N
Z L 2L3 ZL2N , ZL3N
I L 2 I L3
U L 3 U L1
L3L1N Z L3 L1 ZL3N, , Z L1N
I L 3 I L1
U L1
L1N Z L1N
I L1 3I o K N
U L2
L2N Z L2N
I L2 3I o K N
U L3
L3N Z L3N
I L3 3I o K N
Table 1-1 Formulas for the calculation of the impedance to fault
The central column of Table 1-1 Formulas for the calculation of the impedance to fault
contains the correct formula for calculation. The formulas referred to in the right-hand-side
column yield the same correct impedance value.
In Table 1-1:
Z o Z1 1 Zo
KN 1
3Z1 3 Z1
is the complex earth fault compensation factor.
Table 1-1 shows that the formula containing the complex earth fault compensation factor
yields the correct impedance value in case of phase-to-earth faults only; the other formula
can be applied in case of phase-to-phase faults without ground. In case of other kinds of
faults (three-phase (-to-earth), phase-to-phase-to-earth) both formulas give the correct
impedance value if the appropriate voltages and currents are applied.
The separation of the two types of equations is based on the presence or absence of the
earth (zero sequence) current. In case of a fault involving the earth (on a solidly grounded
network), and if the earth current is over a certain level, the formula containing the complex
earth fault compensation factor will be applied to calculate the correct impedance, which is
proportional to the distance-to-fault.
It can be proven that if the setting value of the complex earth fault compensation factor is
correct, the appropriate application of the formulas in Table 1-1 will always yield the positive
sequence impedance between the fault location and the relay location.
For the equivalent impedance elements of the fault loop on the figure above, the following
differential equation can be written:
di
u Ri L
dt
If current and voltage values sampled at two separate sampling points in time are substituted
in this equation, two equations are derived with the two unknown values R and L, so they can
be calculated.
This basic principle is realized in the algorithm by substituting the sampled values of the line-
to-line voltages for u and the difference of two phase currents in case of two- or three-phase
faults without ground for i. For example, in case of an L2L3 fault:
d (i L 2 i L 3 )
u L2 u L3 R1 (i L 2 i L3 ) L1
dt
In case of a phase-to-earth fault, the sampled phase voltage and the phase current modified
by the zero sequence current have to be substituted:
d
u L1 R1 (i L1 R 3io R 3iop ) L1 (i L1 L 3io L 3iop )
dt
Where
R1 is the positive sequence resistance of the line or cable section between the fault
location and the relay location,
L1 is the positive sequence inductance of the line or cable section between the fault
location and the relay location,
L1 is the faulty phase,
3io =iL1+iL2+iL3 is the sampled value of the zero sequence current of the protected line,
3iop =iL1p+iL2p+iL3p is the sampled value of the zero sequence current in parallel line,
and
Ro R1
R
3R1
Lo L1 X o X1
L
3L1 3X1
Rm
R
3R1
Lm Xm
L
3L1 3X 1
Rm is the real part of the mutual impedance between the protected and the parallel line,
Lm is the mutual inductance between the protected and the parallel line.
The formula above shows that the factors for multiplying the R and L values contain different
“ ” and “β” factors but they are real (not complex) numbers.
The applied numerical method is solving the differential equation of the faulty loop, based on
three consecutive samples.
To achieve a better filtering effect, Fourier basic harmonic components are substituted for the
components of the differential equations.
Z_CALC V
IL1
IV
IL2 III
IL3 II
I
3Iop
ZL1_CALC RL1+j XL1
RL2+j XL2
UL1 RL3+j XL3
ZL2_CALC
UL2
UL3 ZL3_CALC
Binary V
inputs IV
III
II
Parameters
I
ZL3L1_CALC
The inputs are the sampled values and Fourier components of:
the three phase voltages,
the three phase currents,
the (3Iop) zero sequence current of the parallel line,
binary inputs,
parameters.
The binary inputs are signals influencing the operation of the distance protection function.
These signals are the results of logic equations graphically edited by the user.
Enumerated parameters
Floating-point parameters
The outputs are the calculated positive-sequence impedances (R+jX) of the six measuring
current loops and, as different zero sequence current compensation factors can be set for the
individual zones, the impedances are calculated for each zone separately:
Impedances of the three phase-phase loops,
Impedances of the three phase-ground loops.
Z_CALC includes six practically identical software modules for impedance calculation:
The three routines of the phase group are activated by phase voltages, phase
currents and the zero sequence current calculated from the phase current and the
zero sequence currents of the parallel line, as measured in a dedicated input.
The three routines for the phase-to-phase loops get line-to-line voltages calculated
from the sampled phase voltages and they get differences of the phase currents.
They do not need zero sequence currents for the calculation.
The calculated impedances are analogue outputs of the distance protection function. They
serve the purpose of checking possibility at commissioning.
CURRENT_OK Calc_A
NOT
AND
VTS_BLOCK NOT
Calc_B
VOLT_OK_HIGH AND
NOT
Calc_C
VOLT_OK_LOW
AND
MEM_AVAIL
NOT Calc_D
AND
Calc_E
AND
NOT
Calc_F
AND
HEALTHY_PHASE_AVAIL
AND Calc_G
SOFT_COND OR
P_SOFT_Zn AND
Calc_H
AND
P_nondir NOT
The decision needs logic parameter settings and, additionally, internal logic signals.
The explanation of these signals is as follows:
Parameter Explanation
P_SOTF_Zn This logic parameter is true if the “switch-onto-fault” logic is enabled
for Zone_n, (where n=1…5), i.e., DIS21_SOTFMd_EPar_ (SOTF
Zone) is selected for “Zone n” (where n=1…5).
P_nondir This logic parameter is true if offset MHO is programmed, i.e., the
DIS21_Zn_EPar_( Operation Zonen) parameter (where n=1…5) is
set to “Offset” for the individual zones.
Table 1-6 Enumerated parameters for the Z_CALC module
The outputs of the scheme of Figure 1-2 are calculation methods applied for impedance
calculation for the individual zones.
If the CURRENT_OK status signal is false, the current is very small, therefore no fault is
possible. In this case, the impedance is set to extreme high values and no further calculation
is performed:
R=1000000, X=1000000.
The subsequent decisions are performed if the current is sufficient for the calculation.
If the CURRENT_OK status signal is true and the VOLT_OK_HIGH status signal is true as
well, then the current is suitable for calculation and the voltage is sufficient for the
directionality decision. In this case, normal impedance calculation is performed based on the
sampled currents and voltages. (The calculation method - the function ”f”- is explained later.)
R, X=f(u, i)
If the CURRENT_OK status signal is true but the VOLT_OK_HIGH status signal is false or
there are voltage swings, the directionality decision cannot be performed based on the
available voltage signals temporarily. In this case, if the voltage is above a minimal level (in
the range of possible capacitive voltage transformer swings), then the VOLT_OK_LOW status
is “true”, the magnitude of R and X is calculated based on the actual currents and voltages
but the direction of the fault (the +/- sign of R and X) must be decided based on the voltage
value stored in the memory 80 ms earlier. (The high voltage level setting assures that during
the secondary swings of the voltage transformers, no distorted signals are applied for the
decision). This procedure is possible only if there are stored values in the memory for 80 ms
and these values were sampled during a healthy period.
R, X=f(u, i) direction = f(Umem, i) /in the first 35 ms/
After 35 ms (when the secondary swings of the voltage transformers decayed), the directional
decision returns to the measured voltage signal again:
R, X=f(u, i) direction = f(u, i) /after 35 ms/
R=abs(R), X=abs(X)
Calculation method Calc(H):
If the voltage is not sufficient for a directional decision and no stored voltage samples are
available, and if the “switch-onto-fault” logic is not enabled, then the impedance is set to a
high value:
R=1000500, X=1000500
The calculated R1 and X1= L1 co-ordinate values define six points on the complex
impedance plane for the six possible measuring loops. These impedances are the positive
sequence impedances. The protection compares these points with the MHO characteristics
of the distance protection, shown in Figure 1-3.
jX
Zone Z
-R Load R Load
Load Angle
R
Zone ZRev
Figure 1-3 The MHO characteristics of the distance protection function on the
complex plane
If a measured impedance point is inside the MHO circle, the algorithm generates the true
value of the related output binary signal.
The calculated impedance values are compared one by one with the setting values of the
MHO characteristics. This procedure is shown schematically in Figure 1-4.
The procedure is processed for each line-to-ground loop and for each line-to-line loop. Then
this is repeated for all five impedance stages. The result is the setting of 6 x 5 status
variables, which indicate that the calculated impedance is within the processed MHO circle,
meaning that the impedance stage has started.
I.
II.
III.
V IV.
IV V.
III
RL1+j XL1 V
RL2+j XL2 IV
RL3+j XL3
III
II
I
ZL1_n
V ZL2_n
ZL3_n
IV
ZL1L2_n
III ZL2L3_n
II ZL3L1_n
I
RL1L2+j XL1L2
RL2L3+j XL2L3
RL3L1+j XL3L1
Parameters
Input values
The input values are calculated by the module Z_CALC.
Output values
Output values Zones Explanation
The impedance in the fault loop L1N is inside the MHO
ZL1_n 1…5
characteristics
The impedance in the fault loop L2N is inside the MHO
ZL2_n 1…5
characteristics
The impedance in the fault loop L3N is inside the MHO
ZL3_n 1…5
characteristics
The impedance in the fault loop L1L2 is inside the MHO
ZL1L2_n 1…5
characteristics
The impedance in the fault loop L2L3 is inside the MHO
ZL2L3_n 1…5
characteristics
The impedance in the fault loop L3L1 is inside the MHO
ZL3L1_n 1…5
characteristics
Table 1-10 The output status signals of the MHO module
The parameters needed in the MHO circle evaluation procedure of the distance protection
function are explained in the following tables.
Enumerated parameters
Parameter name Title Selection range Default
Parameters to select directionality of the individual zones:
Operation Off
DIS21_Z1_EPar_ Off, Forward, Backward
Zone1
Operation Off
DIS21_Z2_EPar_ Off, Forward, Backward, Offset
Zone2
Operation Off
DIS21_Z3_EPar_ Off, Forward, Backward, Offset
Zone3
Operation Off
DIS21_Z4_EPar_ Off, Forward, Backward, Offset
Zone4
Operation Off
DIS21_Z5_EPar_ Off, Forward, Backward, Offset
Zone5
Table 1-11 Enumerated parameters for the MHO logic
Integer parameters
Parameter name Title Unit Min Max Step Default
Definition of the load angle of the polygon characteristic:
DIS21_LdAng_IPar_ Load Angle deg 0 45 1 30
Definition of the line angle:
DIS21_LinAng_IPar_ Line Angle deg 0 90 1 75
Table 1-12 Integer parameters for the MHO logic
Floating point parameters
Parameter name Title Dimension Min Max Default
Setting values of the characteristics for the five zones individually:
DIS21_Z1X_FPar Zone1 Z ohm 0.1
0.01 200
320 10
DIS21_Z2X_FPar Zone2 Z ohm 0.01
0.1 200
320 10
DIS21_Z3X_FPar Zone3 Z ohm 0.01
0.1 200
320 10
DIS21_Z4X_FPar Zone4 Z ohm 0.1
0.01 200
320 10
DIS21_Z5X_FPar Zone5 Z ohm 0.01
0.1 200
320 10
DIS21_Z2R_FPar Zone2 ZRev** ohm 0.01
0.1 200
320 10
DIS21_Z3R_FPar Zone3 ZRev** ohm 0.01
0.1 200
320 10
DIS21_Z4R_FPar Zone4 ZRev** ohm 0.01
0.1 200
320 10
DIS21_Z5R_FPar Zone5 ZRev** ohm 0.01
0.1 320
200 10
DIS21_LdR_FPar R Load ohm 0.01
0.1 200
320 10
** Active only if “Operation Zone 2…5” is set to “Offset”. Zone 1can not be set for offset
characteristics.
Table 1-13 Floating point parameters for the MHO logic
In case of faults, the calculated impedance value for the faulty loop is inside a MHO circle. If
the fault is near the relay location, the impedances in the loop containing the faulty phase can
also be inside the characteristic circle. To ensure selective tripping, phase selection is
needed. This chapter explains the operation of the phase selection logic.
The binary inputs are signals influencing the operation of the distance protection function.
These signals are the results of logic equations graphically edited by the user.
Timer parameters
Parameter name Title Unit Min Max Step Default
Time delay for the zones individually
Zone1 Time
DIS21_Z1Del_TPar_ ms 0 60000 1 0
Delay
Zone2 Time
DIS21_Z2Del_TPar_ ms 0 60000 1 400
Delay
Zone3 Time
DIS21_Z3Del_TPar_ ms 0 60000 1 800
Delay
Zone4 Time
DIS21_Z4Del_TPar_ ms 0 60000 1 2000
Delay
Zone5 Time
DIS21_Z5Del_TPar_ ms 0 60000 1 2000
Delay
Table 1-19 Timer parameters of the distance protection function
The processing of diagrams in the following figures is sequential. If the result of one of them is
true, no further processing is performed.
In Figure 1-5 and in the subsequent figures “n = 1…5” means that the logic is repeated for all
five zones.
ZL1L2_n Z_3Ph_start_n_
OR
ZL2L3_n
ZL3L1_n
DIS21_cIL1_GrI AND
DIS21_cIL2_GrI
DIS21_cIL3_GrI
OR AND
Figure 1-6 explains the detection of a phase-to-phase fault between phases “L1” and “L2”:
no fault is detected in the previous sequential tests,
the start of the MHO impedance logic in loop “L1L2” and loop “L1L2” detects the
lowest reactance, and
“OR” relation of the following logic states:
o no zero sequence current above the limit and no start of the MHO logic in
another phase-to-phase loop, or
o in the presence of a zero sequence current
start of the MHO impedance logic in loops “L1” and ”L2” individually
as well, or
the voltage is small in the faulty “L1L2” loop and the currents in both
phases involved are above the setting limit.
The “L1L2” fault detection resets only if none of the “L1L2” line-to-line, “L1N” or “L2N” loops
detect fault any longer.
Z_3Ph_start_n
NOT
ZL1L2_n
AND
ZL1L2_eq_minLL
n
DIS21_cIo_GrI AND ZL1L2_Start_n_
NOT AND OR OR
ZL2L3_n AND
NOT
ZL1_n
ZL2_n AND OR
UL1L2_It_5V
DIS21_cIL1_GrI
DIS21_clL2_GrI
OR AND
Figure 1-7 and Figure 1-8 show a similar logic for loops “L2L3” and “L3L1”, respectively.
Z_3Ph_start_n
OR NOT
ZL1L2_start_n
ZL2L3_n
AND
ZL2L3_eq_minLL
ZL3L1_n AND
NOT
ZL2_n
ZL3_n AND OR
UL2L3_It_5V
DIS21_cIL2_GrI
DIS21_clL3_GrI
OR AND
Z_3Ph_start_n
ZL1L2_start_n OR NOT
ZL2L3_start_n
ZL3L1_n
AND
ZL3L1_eq_minLL
ZL1L2_n AND
NOT
ZL3_n
ZL1_n AND OR
UL3L1_It_5V
DIS21_cIL3_GrI
DIS21_clL1_GrI
OR AND
Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL1_start_n
ZL1_n
ZL1_eq_minLN AND
DIS21_cIo_GrI
DIS21_cIL1_GrI
minLN_Lt_minLL
L
Figure 1-9 L1N fault detection in Zone “n” (n=1…5)
Figure 1-10 and Figure 1-11 show similar logic for loops “L2” and “L3” respectively.
Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL1_start_n
ZL2_start_n
ZL2_n
ZL2_eq_minLN
AND
DIS21_cIo_GrI
DIS21_cIL2_GrI
minLN_It_minLL
Z_3Ph_start_n
ZL1L2_start_n NOT
ZL2L3_start_n OR
ZL3L1_start_n
ZL2_start_n ZL2_start_n
ZL3_n
ZL3_eq_minLN
AND
DIS21_cIo_GrI
DIS21_cIL3_GrI
minLN_It_minLL
Figure 1-12 shows how the signals are processed for the output signals of the distance
protection function.
DIS21_Zn_Epar_eq_Off
OR NOT
DIS21_Zn_Blk_GrO_
AND DIS21_ZnStL1_GrI
Z_3Ph_start_n
ZL1L2_start_n
ZL3L1_start_n OR
ZL1_start_n
DIS21_ZnStL2_GrI
AND
ZL2L3_start_n OR
ZL2_start_n
AND DIS21_ZnStL3_GrI
OR
ZL3_start_n DIS21_ZnSt_GrI
OR
DIS21_ZnTr_GrI
AND DELAY
DIS21_ZnSt_BPar
NOT
DIS21_ZnDel_TPar
Figure 1-12 Output signals of the distance protection function for Zone “n” (n=1…5)
The operation of the distance protection may be blocked either by parameter setting
(DIS21_Zn_EPar_eq_Off) or by binary input (DIS21_Zn_Blk_GrO_)
Starting in phase L1 if this phase is involved in the fault (DIS21_ZnStL1_GrI),
Starting in phase L2 if this phase is involved in the fault (DIS21_ZnStL2_GrI),
Starting in phase L2 if this phase is involved in the fault (DIS21_ZnStL3_GrI),
General start if any of the phases is involved in the fault (DIS21_ZnSt_GrI),
A trip command (DIS21_ZnTr_GrI) is generated after the timer Zn_Delay has expired.
This timer is started if the zone is started and it is not assigned to “Start signal only”,
using the parameter DIS21_ZnSt_BPar. The time delay is set by the timer parameter
DIS21_ZnDel_TPar.
Figure 1-13 shows the method of post-processing the binary output signals to generate
general start signals for the phases individually and separately for zones 2 to 5.
DIS21_Z1StL1_GrI DIS21_GenStL1_GrI
OR
DIS21_Z2StL1_GrI DIS21_Z25StL1_GrI
DIS21_Z3StL1_GrI
DIS21_Z4StL1_GrI OR
DIS21_Z5StL1_GrI
DIS21_Z1StL2_GrI DIS21_GenStL2_GrI
OR
DIS21_Z2StL2_GrI DIS21_Z25StL2_GrI
DIS21_Z3StL2_GrI
OR
DIS21_Z4StL2_GrI
DIS21_Z5StL2_GrI
DIS21_Z1StL3_GrI DIS21_GenStL3_GrI
OR
DIS21_Z2StL3_GrI DIS21_Z25StL3_GrI
DIS21_Z3StL3_GrI
OR
DIS21_Z4StL3_GrI
DIS21_Z5StL3_GrI
Figure 1-13 General start in the phase-to-ground loops separately for Zones 2 to 5
The separate phase identification signals for Zones 2-5 are not published.
Table 1-27 The binary output status signals of the current conditions module
Integer parameters
Parameter name Title Unit Min Max Step Default
Definition of minimal current enabling impedance calculation:
IPh Base
DIS21_Imin_IPar_ % 10 30 1 20
Sens
Definition of zero sequence current characteristic enabling impedance calculation in phase-to-
earth loops:
IRes Base
DIS21_IoBase_IPar_ % 10 50 1 10
Sens
DIS21_IoBias_IPar_ IRes Bias % 5 30 1 10
Table 1-28 Integer parameters for the current conditions module
The current is considered to be sufficient for impedance calculation if it is above the level set
by parameter DIS21_Imin_IPar_.
To decide the presence or absence of the zero sequence current, biased characteristics are
applied (see Figure 1-14). The minimal setting current DIS21_IoBase_IPar_ (Io Base sens.)
and a percentage biasing DIS21_IoBias_IPar_ (IRes bias) must be set. The biasing is applied
for the detection of zero sequence current in the case of increased phase currents.
3Io/In*100%
Isum/In=( Ia + Ib + Ic )/In
X
DIS21_Xin_FPar
Stable swing
Stable swing
Out of Step
R
DIS21_Rin_FPar
The binary output status signals of the power swing detection function.
Binary output signals Signal title Explanation
Distance function power swing signals generated by the PSD module
DIS21_PSDDet_GrI_ PSD Detect Signal for power swing detection
DIS21_OutTr_GrI_ OutOfStep Trip Signal for out-of-step tripping condition
Signal for very slow power swing
DIS21_PSDslow_GrI_ VerySlow Swing
detection
Table 1-29 The binary output status signals of the power swing detection function
All these binary signals can serve as binary inputs for the graphic equations, to be
programmed by the user.
The binary inputs are signals influencing the operation of the distance protection function.
These signals are the results of logic equations graphically edited by the user. E.g., the
DIS21_PSDBlk_GrO_ signal can be programmed using these inputs to block the power swing
detection.
Table 1-31 The enumerated parameters of the power swing detection function
Boolean parameters for the individual zones to be blocked by the Power Swing Detection
(PSD) function:
Parameter name Title Default Explanation
DIS21_Z1St_BPar_ PSD Block Z1 0 1 for Zone1 to be blocked by PSD
DIS21_Z2St_BPar_ PSD Block Z2 0 1 for Zone2 to be blocked by PSD
DIS21_Z3St_BPar_ PSD Block Z3 0 1 for Zone3 to be blocked by PSD
DIS21_Z4St_BPar_ PSD Block Z4 0 1 for Zone4 to be blocked by PSD
DIS21_Z5St_BPar_ PSD Block Z5 0 1 for Zone5 to be blocked by PSD
Table 1-32 The Boolean parameters of the distance protection function
Integer parameters
Parameter name Title Unit Min Max Step Default
Definition of the ratio of the outside and inside rectangles of the characteristics for power swing
detection:
DIS21_RRat_IPar_ PSD R_out/R_in % 120 160 1 130
DIS21_XRat_IPar_ PSD X_out/X_in % 120 160 1 130
Table 1-33 The integer parameters of the power swing detection function
Timer parameters
Parameter name Title Unit Min Max Step Default
DIS21_PSDDel_TPar_ PSD Time Delay ms 10 1000 1 40
DIS21_PSDSlow_TPar_ Very Slow Swing ms 100 10000 1 500
DIS21_PSDRes_TPar_ PSD Reset ms 100 10000 1 500
DIS21_OutPs_TPar_ OutOfStep Pulse ms 50 10000 1 150
Table 1-35 The timer parameters of the power swing detection function
DIS21_PSD_EPar_eq_Off
NOT
PSD_det_L1
AND OnDelay
ZL1_Within_Margs
DIS21_PSDDet_TPar
PSD_det_L2
AND OnDelay
ZL2_Within_Margs
DIS21_PSDDet_TPar
AND PSD_det_L3
OnDelay
ZL3_Within_Margs
DIS21_PSDDet TPar
Figure 1-16 shows that power swing is detected in the individual phases if the measured
impedance (Phase-to-ground loop for Zone1) is within the margins of the PSD characteristics
for the time span, given with parameter DIS21_PSDDel_TPar_.
PSD_det_L1_
PSD_det_L2_ OR
PSD_det_L3_ cont1->
AND
DIS21_PDS_EPar_eq_1of3 OR
AND
DIS21_PDS_EPar_eq_2of3 AND
AND OR
DIS21_PDS_EPar_eq_3of3
AND
AND
AND
<-cont1 DIS21_PSDDet_GrI
DIS21_PSDRes_TPar RESET
AND
NOT
DIS21_PSDBlk_GrO
Jump_det_ NOT
NOT
AND DIS21_PSDSlow_GrI
OnDelay RESET
DIS21_PSDSlow_TPar
DIS21_PSDRes_TPar
Figure 1-17 Power swing detection and slow power swing detection
According to Figure 1-17, the power swings in the individual phases result in a power swing
state only if the combination of the phases corresponds to the parameter setting
DIS21_PSD_EPar (which can be 1 out of 3, 2 out of 3, 3 out of 3).
The function can be blocked using the enumerated parameter DIS21_PSD_EPar_ if it is set
to “Off”. The function can be blocked using the user-programmable graphic output status
DIS21_PSDBlk_GrO_.
DIS21_PSD _Epar_eq_Off
NOT
AND
ZL1_Jump
Jump_det
RESET
AND OR
ZL2_Jump
AND
ZL3_Jump
DIS21_PSDRes_TPar
Figure 1-18 shows that if impedance jump is detected (i.e., the change of the reactance and
resistance values between two consecutive samples is greater than ¼ of the PSD margin
setting) in any of the phases, then the “Jump_det” condition is true for the “reset” time.
The impedance jump is an internal signal. If during power swings the impedance “jumps”, this
means a fault during the swings and the power swing state must be terminated. (See Figure
1-17.)
DIS21_PSD _Epar_eq_Off
NOT
RS OuOfStep_L1
AND
ZL1_Instable
OuOfStep_L2
AND RS
ZL2_Instable
OuOfStep_L3
AND RS
ZL3_Instable
DIS21_Out _Epar_eq_Off
Jump_det OR NOT
DIS21_PSDSlow_GrI_
If the swings are instable, the sign of the resistive component of the impedance at entrance is
opposite to the sign of the resistance calculated at leaving the characteristics. Figure 1-19
shows that “Out-of-step condition” is detected in the individual phases if instable state is
measured (i.e., the sign of the resistive component is opposite if the impedance enters and if
it exits the PSD characteristics). The function can be disabled using the enumerated
parameter DIS21_PSD_EPar_ if it is set to “Off”. This function also resets if the out-of-step
function is disabled by the parameter DIS21_Out_EPar_ by setting it to “Off”, or an
impedance jump is detected (“Jump_det”) according to Figure 1-18 or a slow swing is
detected (see “DIS21_PSDslow_GrI_” on Figure 1-17 above).
In this case, the algorithm can generate the out-of-step tripping condition DIS21_OutTr_GrI_.
The duration of this impulse is determined by the parameter DIS21_OutPs_TPar_.
All these binary output signals can serve as binary inputs for the graphic equations, to be
programmed by the user.
OutOfSTep_L1_
OutOfSTep_L2_ OR
OutOfSTep_L3_ Cont2->
AND
DIS21_PDS_EPar_eq_1of3 OR
AND
DIS21_PDS_EPar_eq_2of3 AND
AND OR
DIS21_PDS_EPar_eq_3of3 AND
AND
AND
DIS21_OutTr_GrI
<-Cont2 AND
IMP
DIS21_OutPs_TPar
DIS21_PSDBlk_GrO NOT
According to Figure 1-20, the out-of-step conditions in the individual phases can result in an
out-of-step trip command impulse only if the combination of the phases corresponds to the
parameter setting DIS21_PSD_EPar (which can be 1 out of 3, 2 out of 3, 3 out of 3).
The duration of the trip command can be set using the parameter DIS21_OutPs_TPar_.
The high-speed overcurrent protection function operates if a sampled value of the phase
current is above the setting value.
The binary input is a signal influencing the operation of the distance protection function. This
signal is the result of logic equations graphically edited by the user.
The parameters of the SOTF function are explained in the following tables.
Enumerated parameters
Parameter name Title Selection range Default
Parameter for selecting one of the zones or “high speed overcurrent protection” for the “switch-
onto-fault” function:
SOTF Off,Zone1,Zone2,Zone3,Zone4,Zone5
DIS21_SOTFMd_EPar _ Zone1
Zone ,HSOC
Table 1-39 The enumerated parameters of the SOTF function
Integer parameters
Parameter name Title Unit Min Max Step Default
Definition of the overcurrent setting for the switch-onto-fault function, for the case where the
DIS21_SOTFMd_EPar_ (SOTF Zone) parameter is set to “HSOC”:
DIS21_SOTFOC_IPar_ SOTF Current % 10 1000 1 200
Table 1-40 The integer parameters of the SOTF logic
DIS21_SOFTCond_GrI
DIS21_Z1St _GrI AND
DIS21_SOTFMd_EPar_eq_Zone1
SOFT_HSOC_START AND
DIS21_SOTFMd_EPar_eq_HSOC
Number of zones 5
Rated current In 1/5A, parameter setting
Rated voltage Un 100/200V, parameter setting
Current effective range 20 – 2000% of In ±1% of In
Voltage effective range 2-110 % of Un ±1% of Un
Impedance effective range
In=1A 0.1 – 200 Ohm ±5%
In=5A 0.1 – 40 Ohm
48 Hz – 52 Hz ±5%
Zone static accuracy
49.5 Hz – 50.5 Hz ±2%
Zone angular accuracy ±3 °
Operate time Typically 25 ms ±3 ms
Minimum operate time <20 ms
Reset time 16 – 25 ms
Reset ratio 1.1
Table 1-43 Technical data of the 5-zone distance protection
The parameters of the distance protection function are explained in the following tables.
Enumerated parameters
Parameter name Title Selection range Default
Parameters to select directionality of the individual zones:
Operation Off
DIS21_Z1_EPar_ Off, Forward, Backward
Zone1
Operation Off
DIS21_Z2_EPar_ Off, Forward, Backward, Offset
Zone2
Operation Off
DIS21_Z3_EPar_ Off, Forward, Backward, Offset
Zone3
Operation Off
DIS21_Z4_EPar_ Off, Forward, Backward, Offset
Zone4
Operation Off
DIS21_Z5_EPar_ Off, Forward, Backward, Offset
Zone5
Parameters for power swing detection:
Operation Off,1 out of 3, 2 out of 3, 3 out of 3
DIS21_PSD_EPar_ 1 out of 3
PSD
Parameter enabling “out-of-step” function:
Oper
DIS21_Out_EPar_ Off, On Off
OutOfStep
Parameter for selecting one of the zones or “high speed overcurrent protection” for the
“switch-onto-fault” function:
SOTF Off, Zone1, Zone2, Zone3, Zone4,
DIS21_SOTFMd_EPar _ Zone1
Zone Zone5, HSOC
Table 1-45 The enumerated parameters of the distance protection function
Boolean parameters for the individual zones to generate trip command (0) or to indicate
starting only (1):
Parameter name Title Default Explanation
DIS21_Z1St_BPar_ Zone1 Start Only 0 0 for Zone1 to generate trip command
DIS21_Z2St_BPar_ Zone2 Start Only 0 0 for Zone2 to generate trip command
DIS21_Z3St_BPar_ Zone3 Start Only 0 0 for Zone3 to generate trip command
DIS21_Z4St_BPar_ Zone4 Start Only 0 0 for Zone4 to generate trip command
DIS21_Z5St_BPar_ Zone5 Start Only 0 0 for Zone5 to generate trip command
Table 1-46 The Boolean parameters of the distance protection function
Boolean parameters for the individual zones to be blocked by the Power Swing Detection
(PSD) function (1):
Parameter name Title Default Explanation
DIS21_Z1St_BPar_ PSD Block Z1 0 1 for Zone1 to be blocked by PSD
DIS21_Z2St_BPar_ PSD Block Z2 0 1 for Zone2 to be blocked by PSD
DIS21_Z3St_BPar_ PSD Block Z3 0 1 for Zone3 to be blocked by PSD
DIS21_Z4St_BPar_ PSD Block Z4 0 1 for Zone4 to be blocked by PSD
DIS21_Z5St_BPar_ PSD Block Z5 0 1 for Zone5 to be blocked by PSD
Table 1-47 The Boolean parameters of the distance protection function
Integer parameters
Parameter name Title Unit Min Max Step Default
Definition of minimal current enabling impedance calculation:
DIS21_Imin_IPar_ IPh Base Sens % 10 30 1 20
Definition of zero sequence current characteristic enabling impedance calculation in phase-to-
earth loops:
DIS21_IoBase_IPar_ IRes Base Sens % 10 50 1 10
DIS21_IoBias_IPar_ IRes Bias % 5 30 1 10
Definition of the load angle of the polygon characteristic:
DIS21_LdAng_IPar_ Load Angle deg 0 45 1 30
Definition of the line angle:
DIS21_LinAng_IPar_ Line Angle deg 0 90 1 75
Definition of the ratio of the characteristics for power swing detection:
DIS21_RRat_IPar_ PSD R_out/R_in % 120 160 1 130
DIS21_XRat_IPar_ PSD X_out/X_in % 120 160 1 130
Definition of the overcurrent setting for the switch-onto-fault function, for the case where the
DIS21_SOTFMd_EPar_ (SOTF Zone) parameter is set to “HSOC”:
DIS21_SOTFOC_IPar_ SOTF Current % 10 1000 1 200
Table 1-48 The integer parameters of the distance protection function
Timer parameters
Parameter name Title Unit Min Max Step Default
Time delay for the zones individually:
DIS21_Z1Del_TPar_ Zone1 Time Delay ms 0 60000 1 0
DIS21_Z2Del_TPar_ Zone2 Time Delay ms 0 60000 1 400
DIS21_Z3Del_TPar_ Zone3 Time Delay ms 0 60000 1 800
DIS21_Z4Del_TPar_ Zone4 Time Delay ms 0 60000 1 2000
DIS21_Z5Del_TPar_ Zone5 Time Delay ms 0 60000 1 2000
Parameters for the power swing detection function:
DIS21_PSDDel_TPar_ PSD Time Delay ms 10 1000 1 40
DIS21_PSDSlow_TPar_ Very Slow Swing ms 100 10000 1 500
DIS21_PSDRes_TPar_ PSD Reset ms 100 10000 1 500
DIS21_OutPs_TPar_ OutOfStep Pulse ms 50 10000 1 150
Table 1-50 The timer parameters of the distance protection function
The binary inputs are signals influence the operation of the distance protection function.
These signals are the results of logic equations graphically edited by the user.
Binary input signals Signal title Explanation
Blocking signal due to error in the voltage
DIS21_VTS_GrO_ Block from VTS
measurement
DIS21_Z1Blk_GrO_ Block Z1 Blocking of Zone 1
DIS21_Z2Blk_GrO_ Block Z2 Blocking of Zone 2
DIS21_Z3Blk_GrO_ Block Z3 Blocking of Zone 3
DIS21_Z4Blk_GrO_ Block Z4 Blocking of Zone 4
DIS21_Z5Blk_GrO_ Block Z5 Blocking of Zone 5
DIS21_PSDBlk_GrO_ Block PSD Blocking signal for power swing detection
Status signal indicating switching-onto-fault
DIS21_SOTFCond_GrO_ SOTF COND.
condition
Table 1-52 The binary input signals of the distance protection function
The function block of the distance protection function is shown in Figure 1-22. This block
shows all binary input and output status signals that are applicable in the graphic logic editor.
Figure 1-22 The function block of the distance protection function with MHO
characteristic