PI142F - Winding 06
Stamford industrial generators meet the requirements of Dedicated Single Phase generators have 4 ends brought
BS EN 60034 and the relevant section of other out to the terminals, which are mounted at the non-drive
international standards such as BS5000, VDE 0530, end of the generator. A sheet steel terminal box contains
NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. provides ample space for the customers' wiring and gland
Other standards and certifications can be considered on arrangements. Alternative terminal boxes are available for
request. customers who want to fit additional components in the
terminal box.
VOLTAGE REGULATOR
SHAFT & KEYS
AS480 AVR fitted as STANDARD
All generator rotors are dynamically balanced to better
With this self-excited system the main stator provides than BS6861:Part 1 Grade 2.5 for minimum vibration in
power via the AVR to the exciter stator. The high operation. Two bearing generators are balanced with a
efficiency semi-conductors of the AVR ensure positive half key.
build-up from initial low levels of residual voltage.
The exciter rotor output is fed to the main rotor through a INSULATION / IMPREGNATION
three-phase full-wave bridge rectifier. The rectifier is
APPROVED DOCUMENT
protected by a surge suppressor against surges caused, The insulation system is class 'H'.
for example, by short circuit or out-of-phase paralleling. All wound components are impregnated with materials and
The AS480 will support limited accessories, RFI processes designed specifically to provide the high build
suppession remote voltage trimmer and for the P1 range required for static windings and the high mechanical
only a 'droop' Current Transformer (CT) to permit parallel strength required for rotating components.
operation with other ac generators.
The AVR is can be fitted to either side of the generator in QUALITY ASSURANCE
its own housing in the non-drive end bracket.
Generators are manufactured using production
Excitation Boost System (EBS) (OPTIONAL) procedures having a quality assurance level to BS EN ISO
9001.
The EBS is a single, self-contained unit, attached to the
non-drive end of the generator. The stated voltage regulation may not be maintained in
The EBS unit consists of the Excitation Boost Controller the presence of certain radio transmitted signals. Any
(EBC) and an Excitation Boost Generator (EBG). Under change in performance will fall within the limits of Criteria
fault conditions, or when the generator is subjected to a 'B' of EN 61000-6-2:2001. At no time will the steady-state
large impact load such as a motor starting, the generator voltage regulation exceed 2%.
voltage will drop. The EBC senses the drop in voltage
and engages the output power of the EBG. This DE RATES
additional power feeds the generator’s excitation system,
supporting the load until breaker discrimination can All values tabulated on page 7 are subject to the following
remove the fault or enable the generator to pick up a reductions
motor and drive the voltage recovery.
5% when air inlet filters are fitted.
WINDINGS & ELECTRICAL PERFORMANCE 3% for every 500 metres by which the operating altitude
exceeds 1000 metres above mean sea level.
All generator stators are wound to 2/3 pitch. This 3% for every 5°C by which the operational ambient
eliminates triplen (3rd, 9th, 15th …) harmonics on the temperature exceeds 40°C.
voltage waveform and is found to be the optimum design Note: Requirement for operating in an ambient exceeding
for trouble-free supply of non-linear loads. The 2/3 pitch 60°C must be referred to the factory.
design avoids excessive neutral currents sometimes
seen with higher winding pitches, when in parallel with 5% For reverse rotation
the mains. A fully connected damper winding reduces (Standard rotation CW when viewed from DE)
oscillations during paralleling. This winding, with the 2/3
pitch and carefully selected pole and tooth designs,
ensures very low waveform distortion. NB Continuous development of our products entitles us
to change specification details without notice, therefore
they must not be regarded as binding.
2
PI142F
WINDING 06
CONTROL SYSTEM STANDARD AS480 AVR (SELF EXCITED)
VOLTAGE REGULATION ± 1.0 %
SUSTAINED SHORT CIRCUIT SELF EXCITED MACHINES DO NOT SUSTAIN A SHORT CIRCUIT CURRENT
CONTROL SYSTEM AS480 AVR WITH OPTIONAL EXCITATION BOOST SYSTEM (EBS)
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVE (page 6)
3
PI142F
Winding 06
APPROVED DOCUMENT
4
PI142F
Winding 06
Locked Rotor Motor Starting Curves
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
APPROVED DOCUMENT
5
0
0 5 10 15 20 25 30 35
LOCKED ROTOR kVA
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 4 8 12 16 20 24 28 32 36
LOCKED ROTOR kVA
5
PI142F
Winding 06
Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on series connection.
WITH EBS FITTED
10000
SYMMETRICAL
CURRENT (Amps)
ASYMMETRICAL
1000
APPROVED DOCUMENT
100
0.001 0.01 TIME (secs)
0.1 1 10
Voltage Factor
220V X 1.00
230V X 1.05
240V X 1.09
6
PI142F
Winding 06
60Hz RATINGS
Cont. F - 105/40°C
APPROVED DOCUMENT
Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Class - Temp Rise
1.0pf 1.0pf 1.0pf 1.0pf
Series (V) 220 230 240 220 230 240 220 230 240 220 230 240
Parallel (V) 110 115 120 110 115 120 110 115 120 110 115 120
kVA 21.4 21.4 21.4 23.8 23.8 23.8 25.7 25.7 25.7 26.2 26.2 26.2
kW 21.4 21.4 21.4 23.8 23.8 23.8 25.7 25.7 25.7 26.2 26.2 26.2
Efficiency (%) 80.6 80.9 81.1 80.7 81.0 81.3 80.7 81.0 81.3 80.7 81.0 81.3
kW Input 26.6 26.5 26.4 29.5 29.4 29.3 31.8 31.7 31.6 32.5 32.3 32.2
DIMENSIONS
7
APPROVED DOCUMENT
www.cumminsgeneratortechnologies.com
PI142F-06-TD-EN-SG-A