Daikinoperacao
Daikinoperacao
Daikinoperacao
Group: Chiller
Date: 2019.01
New Part No.: Z8100316-01
Old Part No.: Z8100316-00
Table of Contents
1 Introduction ................................................................................................................ 2
2 Features of the Control Panel ................................................................................... 3
3 Definitions .................................................................................................................. 4
4 General Description ................................................................................................... 6
5 Control Panel.............................................................................................................. 7
5.1 Low Condenser Water Temperature Operation ................................................................ 7
6 Operating the Control System .................................................................................. 9
6.1 Interface Panel On/Off ..................................................................................................... 9
6.2 Start/Stop Unit .................................................................................................................. 9
6.3 Change Setpoints ............................................................................................................ 9
6.4 Alarms.............................................................................................................................. 9
6.5 Chiller Operation without the Operator Interface Panel .................................................... 9
7 Component Description .......................................................................................... 10
7.1 Human Machine Interface .............................................................................................. 10
7.2 Controller Description..................................................................................................... 10
7.3 Navigating ...................................................................................................................... 11
8 Unit Controller .......................................................................................................... 13
8.1 Unit Controller Setpoints ................................................................................................ 14
8.2 Unit Faults, Problems, Warnings .................................................................................... 15
8.3 Controller Functions ....................................................................................................... 16
8.4 Compressor Faults, Problems, Warnings ....................................................................... 17
8.5 Compressor Capacity Control ........................................................................................ 19
9 Compressor On-Board Controllers ........................................................................ 20
10 Human Machine Interface .................................................................................... 23
10.1 Navigation................................................................................................................... 23
10.2 Screen Descriptions .................................................................................................... 24
10.3 Main Screens .............................................................................................................. 24
10.4 View Screen................................................................................................................ 25
10.5 SET Screens............................................................................................................... 27
10.6 SYSTEM Screen......................................................................................................... 39
10.7 TREND Screens ......................................................................................................... 40
10.8 ACTIVE ALARM Screen ............................................................................................. 41
11 Controller Menu Screens ..................................................................................... 42
12 BAS Interface ........................................................................................................ 57
12.1 Modbus Protocol ......................................................................................................... 57
12.2 BACnet Protocol ......................................................................................................... 60
13 How To Download KTP1200 Touch Screen Data Record .................................. 65
13.1 How to download KTP1200 touch screen data record ................................................ 65
13.2 How to operate when touch screen normal power cut................................................. 66
13.3 How to operate when touch screen abnormal power cut ............................................. 66
1 Introduction
This manual provides setup, operating, and troubleshooting information for Daikin Magnitude™
centrifugal chillers with the MicroTech V controller.
! WARNING
Electric shock hazard. Improper handling of this equipment can cause personal injury or equipment damage. This
equipment must be properly grounded. Connections to and service of the MicroTech control panel must be performed
only by personnel that are knowledgeable in the operation of the equipment being controlled.
! CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can cause damage to the
components. Discharge any static electrical charge by touching the bare metal inside the control panel before performing
any service work. Never unplug any cables, circuit board terminal blocks, or power plugs while power is applied to the
panel.
NOTICE
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with this instruction manual, may cause interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in which case the owner will be required to
correct the interference at the owner’s own expense.
Daikin International disclaims any liability resulting from any interference or for the correction thereof.
Chiller Location
The chillers are intended only for installation in an indoor or weather protected area consistent with
the NEMA 1 rating on the chiller, controls, and electrical panels. Equipment room temperature for
operating and standby conditions is 40°F to 122°F (4.4°C to 50°C) with a maximum relative
humidity of 90% (non-condensing).
3 Definitions
Active Setpoint
The active setpoint is the parameter setting in effect at any given moment. This variation can occur
on setpoints that can be altered during normal operation. Resetting the chilled water leaving
temperature setpoint by one of several methods such as return water temperature is an example.
Active Capacity Limit
The active capacity setpoint is the setting in effect at any given moment. Any one of several
external inputs can limit a compressor’s capacity below its maximum value.
Active-Amp-Limit
Active amp limit is the actual amp limit imposed by an outside signal such as the load limit function.
Dead Band
The dead band is a set of values associated with a setpoint such that a change in the variable
occurring within the dead band causes no action from the controller. For example, if a temperature
setpoint is 44°F and it has a dead band of ± 0.2 degrees F, nothing will happen until the measured
temperature is less than 43.8°F or more than 44.2°F.
Discharge Superheat
Discharge superheat is calculated using the following equation:
Discharge Superheat = Discharge Temperature – Condenser Saturated Temperature
Error
In the context of this manual, “Error” is the difference between the actual value of a variable and the
target setting or setpoint.
Evaporator Approach
The evaporator approach is calculated for each circuit. The equation is as follows:
Evaporator Approach = LWT – Evaporator Saturated Temperature
Evap Hold-loading
This is a setpoint that establishes the minimum Suction Pressure to which the chiller is allowed to
go. It signals that the unit is at full load so the no further loading will occur that would lower the
pressure even further.
Evap Recirc (Evaporation Recirculation) Timer
A timing function, with a 30-second default, that holds off any reading of chilled water for the
duration of the timing setting. This delay allows the chilled water sensors to take a more accurate
reading of the chilled water temperature.
EXV
Electronic expansion valve, used to control the flow of refrigerant to the evaporator, controlled by
the circuit microprocessor.
Load Limit
An external signal from the Touch screen, or a 4-20mA signal that limits the compressor loading to
a designated percent of full load. Used to limit unit power input.
Load Balance
Load balance is a technique that equally distributes the total unit load between two or more running
compressors.
Low Pressure Hold (Inhibit) Setpoint
The psi Suction Pressure setting at which the controller will not allow further compressor loading.
“Hold” and “Inhibit” are used interchangeably.
4 General Description
Major Components
Figure4-1, Major Component Location
Power Panel
Evaporator Relief (Behind
Valve Evaporator)
Human Machine
Interface (HMI)
Unit Control Panel Electronic Expansion Valve
General Description
The centrifugal MicroTech V control system consists of a microprocessor-based controller in the
control panel, as well as on-board the compressors, providing monitoring and control functions
required for the controlled, efficient operation of the chiller. The system consists of the following
components:
• Human Machine Interface (HMI), one per unit-provides unit information and is the primary
setpoint input instrument. It has no control function.
• Unit Controller, controls unit functions and communicates with other auxiliaries. It is the
secondary location for setpoint input if, and only if, the HMI is inoperative.
• On-board compressor controller mounted on each compressor that monitors compressor
operation and controls bearing operation.
The operator can monitor all operating conditions by using the unit-mounted HMI. In addition to
providing all normal operating controls, the MicroTech V control system monitors equipment
protection devices on the unit and will take corrective action if the chiller is operating outside of its
normal design conditions. If a fault condition develops, the controller will shut a compressor, or the
entire unit, down and activate an alarm output. Important operating conditions at the time an alarm
condition occurs are retained in the controller’s memory to aid in troubleshooting and fault analysis.
The system is password protected and only allows access by authorized personnel. The operator
must enter the password into the touch screen (or one of the controller's keypad) before any
setpoints can be altered.
5 Control Panel
The unit controller, the HMI microprocessor, the unit and compressor on/off switches and other
minor components are mounted in the control panel. The switches are designated “I” for on and “O”
for off. The compressor on/off switch should only be used when an immediate stop is required
since the normal shut down sequence is bypassed.
The unit controller's function is acquiring and processing data relating to the chiller operation and
issueing instructions to various components to maintain controlled operation. The unit controller
also sends information to the HMI for graphic display. The controller has a 4x20 LCD display and
keys for accessing data and changing setpoints. If the HMI should become inoperable.The
controller LCD can display most of the same information as the HMI and can operate the chiller
independently if the HMI is not available.
5.1 Low Condenser Water Temperature Operation
When the ambient wet bulb temperature is lower than design, the entering condenser water
temperature can be allowed to fall to improve chiller performance. This is especially true of an
advanced design such as the Daikin Magnitude chiller that features variable compressor speed.
It is an engineering fact that as the compressor discharge pressure is reduced, the amount of
power to pump a given amount of gas also is reduced. The reduction can result in significant
energy savings.
6.4 Alarms
ALARM Button in the lower middle of any HMI screen is illuminated red if there is an alarm. If the
optional remote alarm is wired in, it too will be energized.
There are three types of alarms:
• Fault, equipment protection alarms that shut a unit or compressor off.
• Problem, limit alarms that limit compressor loading in response to an out-of-normal condition.
If the condition that caused a limit alarm is corrected, the alarm light will be cleared
automatically.
• Warning, notification only, no action taken by controller.
Any type will light the ALARM light. Procedures for dealing with alarms are shown below:
1. Press the alarm light button. This will go directly to the ACTIVE ALARMS screen.
2. The alarm description (with date stamp) will be shown.
3. Correct the condition causing the alarm.
4. Press the ‘Clear Alarm’button to clear the alarm from the controller. If the fault condition is not
fixed, the alarm will continue to be on and the unit will not be able to be restarted.
7 Component Description
7.1 Human Machine Interface
Human Machine Interface (HMI) is the primary device
for entering commands and entries into the control
system. (Settings can also be made directly into the
unit controller.) The HMI can also display controller
data and information on a series of graphic screens.
A single HMI is used per unit.
Selected information from the HMI panel can be down-
loaded via a USB port on HMI panel.
The HMI panel is mounted on a moveable arm to allow
placement in a convenient position for the operator.
There is a screen-saver programmed into the system.
The screen is reactivated by touching it anywhere.
7.2 Controller Description
Hardware Structure
The controller is fitted with a microprocessor for running the control program. There are terminals
for connection to the controlled devices (for example: solenoid valves, tower fans, pumps). The
program and settings are saved permanently in FLASH memory, preventing data loss in the event
of power failure without requiring a back-up battery.
The controller connects to other control boards, the on-board compressor microprocessors and the
HMI via a local communications network (RS485).
Keypad
A 4-line by 20-character/line liquid crystal display and 6-button keypad is mounted on the controller.
Its layout is shown below.
Figure7-1, Controller Keypad
MENU Key-to-Screen
Key Pathway
The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use:
• Scroll between data screens in the direction indicated by the arrows (default mode).
• Select a specific data screen in the menu matrix using dynamic labels on the right side of the
display such as ALARM, VIEW, etc (this mode is entered by pressing the MENU key). For ease
of use, a pathway connects the appropriate button to its respective label on the screen.
• Change field values in setpoint programming mode according to the following table:
LEFT key = Default RIGHT key = Cancel
UP key = Increase (+) DOWN key = Decrease (-)
These four programming functions are indicated by one-character abbreviation on the right side
of the display. This programming mode is entered by pressing the ENTER key.
7.3 Navigating
The menus are arranged in a matrix of screens across a top horizontal row. Some of these top-
level screens have sub-screens located under them.
There are two ways to navigate through the menu matrix to reach a desired menu screen.
1) One is to scroll through the matrix from one screen to another using the four ARROW keys.
2) Another way is to use shortcuts to work through the matrix hierarchy. From any menu screen,
a) Pressing the MENU key will take you to the top level of the hierarchy. The display will show
ALARM, VIEW, and SET as shown in Figure4. One of these choices can then be selected
by pressing the key connected to it via the pathway shown in the figure.
b) Depending on the top-level selected, a second level of screens will appear. For example,
selecting ALARM will go the next level of menus under ALARM (ALARM LOG or ACTIVE
ALARM). Selecting VIEW will go the next level of menus (VIEW COMPRESSOR STATUS,
VIEW UNIT STATUS, VIEW EVAPORATOR, or VIEW CONDENSER). Selecting SET will
go to a series of menus for looking at and changing setpoints.
c) After selecting this second level, the desired screen can be acquired using the arrow keys.
A typical final screen is shown below.
Pressing the MENU key from any menu screen will automatically return you to the MENU mode.
Figure7-2, Typical Menu Display and Keypad Layout
ARROW
Keys
MENU Key
ENTER Key
Menu Screens
A hierarchical menu structure is used to access the various screens. Each menu screen can have
one to four lines of information. Optionally, the last menu selection can access one of a set of
screens that can be navigated with the UP/DOWN arrow keys (see the scrolled menu structure
below). Menu selection is initiated by pressing the MENU key, which changes the display from a
data screen to a menu screen. Menu selections are then made using the arrow keys according to
labels on the right side of the display (the arrows are ignored). When the last menu item is selected,
the display changes to the selected data screen. An example follows showing the selection of the
“VIEW COMPRESSOR (n) screen. Suppose the initial screen is:
AL ARM LOG
(data)
After pressing the MENU button, the top-level menu
(data) screen will show:
(data)
← ALARM
→ VIEW After pressing the “VIEW” menu button, a menu
↑ SET screen will show:
↓
VIEW ← COMPRESSOR
→ UNIT After pressing the “COMPRESSOR” menu button,
↑ EVAPORATOR the selected data screen will show;
↓ CONDENSER
VIEW COMP (n) Where “n” is the number of the last viewed
(screen n data) COMPRESSOR screen. The arrow keys will
(screen n data) automatically return to the “scroll” mode at this
(screen n data) time. Different compressor screens can then be
selected with the UP/DOWN arrow keys.
8 Unit Controller
Table8-1, Unit Controller, Analog Inputs
# Description Signal Source Range
U1-UC Entering Condenser Water Temperature NTC Thermistor (10k@25°C) -58 to 212°F
U2-UC Economizer Pressure 0.5-4.5VDC 0 to 132psi
U3-UC Liquid Level 4-20 mA Current 0 to 100%
U4-UC Leaving Condenser Water Temperature NTC Thermistor (10k@25°C) -58 to 212°F
U5-UC Economizer Temperature NTC Thermistor (10k@25°C) -58 to 212°F
U6-UC 1# Air Inlet Pressure 0.5-4.5VDC 0 to 132psi
U7-UC 2# Air Inlet Pressure 0.5-4.5VDC 0 to 132psi
U8-UC 3# Air Inlet Pressure 0.5-4.5VDC 0 to 132psi
U9-UC Entering Evaporator Water Temperature NTC Thermistor (10k@25°C) -58 to 212°F
U10-UC Leaving Evaporator Water Temperature NTC Thermistor (10k@25°C) -58 to 212°F
U3-C.PCOE 4# Air Inlet Pressure 0.5-4.5VDC 0 to 132psi
Table8-2, Unit Controller, Digital Inputs
# Description Signal Signal
ID1-UC Unit OFF Switch 0 VAC (Stop) 24 VAC (Auto)
ID2-UC Remote Start/Stop 0 VAC (Stop) 24 VAC (Start)
ID3-UC Spared
ID4-UC Comp 1 Switch 0 VAC (Stop) 24 VAC (Start)
ID5-UC Comp 2 Switch 0 VAC (Stop) 24 VAC (Start)
ID6-UC Comp 3 Switch 0 VAC (Stop) 24 VAC (Start)
ID7-UC Comp 4 Switch 0 VAC (Stop) 24 VAC (Start)
ID8-UC Emergency Stop 0 VAC (Stop) 24 VAC (Start)
ID9-UC GFP Device1 0 VAC(No protect) 24 VAC(In Protect)
ID10-UC GFP Device2 0 VAC(No protect) 24 VAC(In Protect)
ID11-UC GFP Device3 0 VAC(No protect) 24 VAC(In Protect)
ID14-UC GFP Device4 0 VAC(No protect) 24 VAC(In Protect)
ID17-UC Evaporator Water Flow Switch 0 VAC (No Flow) 24 VAC (Flow)
ID18-UC Condenser Water Flow Switch 0 VAC (No Flow) 24 VAC (Flow)
RUN
Only when all the compressors were stopped, cutting off the main power to maintain any of the
compressors would be permitted. Before turn on the main power to the maintained compressor, all
other compressors of the chiller must be stopped.
MICROTECHCONTROL
BOXTERMINALS
(115V) (24V)
UTB1
GND PE 54
85 * REMOTE
POWER ON/OFF
* NOTE7 (NOTE5)
86
NEUTRAL
* NOTE10 70 *
H 80
MODESWITCH
O 55 * NOTE8
* COOLING C4 74 H
TOWER A
FOURTH 86 O
STAGE A C
STARTER 86 EP2
NOTE11
(NOTE6) * CHILLED
* NOTE10 EVAP. EWI-2 WATER
H 79 DELTA P. PUMP
* COOLING O ORFLOW STARTERS
C3 73 * NOTE8
TOWER SWITCH H
A
THIRD O
STAGE 70 A C
STARTER 78 EP1
EF1
77 NOTE11
* NOTE10 EF1 MJ NOTE11
EWI-1
H 76
* COOLING O
C2 75
TOWER A
SECOND
STAGE (NOTE6)
STARTER COND.
DELTA P. * NOTE9
H
ORFLOW
SWITCH O
* NOTE10 A C
H 70 CP2
* COOLING O
C1
TOWER A CF1 NOTE11
FIRST CWI-2
STAGE CF1 MJ NOTE11
STARTER
52
*COOLINGTOWERBYPASSVALUE 71 * CONDENSER
0-10 VDC WATER
71 PUMP
0-10 VDC STARTERS
:3303 *COOLINGTOWERVFD 53
81 * NOTE9
COMMON H
*ALARM RELAY
82(NO) (NOTE4) O
A
* NOTE4 A C
83(NC) CP1
84
POWER NOTE11
CWI-1
FORDCVOLTAGEAND4-20MA
EXCERPTFROM SCHEM.330387903 REV.0D CONNECTIONS(SEENOTE3)
FIELDCONNECTIONDIAGRAM
CENTRIFUGALUNITS FORDETAILSOFCONTROLREFERTO
UNITCONTROLSCHEMATIC330342103
COMPRESSORCONTROLSCHEMATIC 42203
LEGEND:330343003
* FIELDSUPPLIEDITEM
NOTE: Complete notes are on the following page.
Setpoint
Description
Range of
Settings
The above figure shows the Water screen with Leaving Water Temp setpoint selected. The various
setpoint groups are in a column on the right side of the screen. Each button contains a number of
setpoints grouped together by similar content. The WATER button (as shown) contains various
setpoints relating to water temperature setpoints.
NOTE: Some setpoints that do not apply to a particular unit application may still be listed on the
screen. They will be inactive and can be ignored.
The numbered buttons in the second from right column are pressed to select a particular setpoint.
The selected setpoint will appear in blue on the screen and a description of it (with the range of
available settings) will appear in the upper left-hand box.
A list of setpoints, their default value, their available setting range, and password authority are in
Table8-5.
Surge Temperature Limit 7 7℃ 1.1 ~ 13.9℃ NA At start, Surge Temp (ST) is compared to
this SP. Alarm at ST>2x SP.
88 ℃ 49 ~ 115 ℃
NA Max discharge temp to shut down
High Discharge Temp-Stop 6
compressor
77 ℃ 49 ~ 115 ℃
NA Sets discharge temp above which a forced
High Discharge Temp-Load 5
capacity increase occurs.
High Discharge Pressure-Stop 4 1048kPa 827 ~ 1200kpa M Max discharge pressure, stop compressor
Low Suction Pressure-Stop 3 180kPa 34 ~ 310 kPa T Min Suction pressure – stop compressor
Min Suction pressure – unload
Low Suction Pressure-Unload 2 200 kPa 41 ~ 310 kPa T
compressor
Low Suction Pressure-Inhibit 1 207 kPa 48 ~ 310 kPa T Min Suction pressure – inhibit loading
Min Position
@ Setpoint
(65°F)
0.0~5.5℃
Sets the temperature the leaving water must be
Stage Delta-T 4 0.6 M
above setpoint for next compressor to start.
Startup Delta-T 3 1.7℃ 0.0~5.6℃ O Degrees above setpoint for compressor to start.
Shutdown Delta-T 2 1.7℃ 0.0~1.7℃ O Degrees below setpoint for compressor to stop.
6.7℃ 3~18℃
Leaving Water
1 O Evaporator LWT setpoint in COOL mode
Temp-Cool
The SYSTEM screen is accessed by pressing SYSTEM from MAIN screen. While containing
information and activity buttons for the service technician, it also has valuable information for the
operator.
• The upper left corner contains compressor information such as number of starts and operating
hours and RLA for each compressor.
• Display software version.
• UNITS button allows selection of Inch-Pounds or Metric units of measure on the HMI.
• LANGUAGE allows toggling between the available languages.
• The Log In and Log Out button is used to access the Keyboard screen to enter a password.
℃
The Trend History Overview allows the user to view the various parameters listed on the right side
of the screen. The temperature scale in is on the left. Pressure in kPa and % RLA are
represented by the right-hand scale.
The Active Alarms screen is only accessible when an active alarm exists on the unit. Pressing the
ALARM button on any screen will access this screen.
Alarms are arranged in order of occurrence, with the most recent on top. Once the abnormal
condition is corrected, pressing the "Clear Alarm" key will clear the alarm.
The current active alarms (there may be more than one) are displayed. Note that the alarms are
FAULT (equipment protection control) that causes a rapid compressor shutdown, PROBLEM (limit
alarm) that will inhibit loading, or load or unload the compressor, and WARNING which is
information only and takes no action.
The date/time and cause of the alarm are displayed.
After eliminating the cause of the alarm, clear the alarm by pressing the Clear Alarm button. This
will clear the alarm from the register and allow the unit to restart after going through the start
sequence. The alarm notice will be deleted from the screen.
However, if the cause of the alarm is not remedied, the alarm is still active and the alarm message
will remain open. The unit will not begin its starting sequence.
The Bypass Valve value is “None” (in place of XXX%) if the Valve/VFD Control setpoint = None or
VFD Stage. The VFD Speed value shall be “None” if the Valve/VFD Control setpoint = None, Valve
Setpoint, or Valve Stage.
View Compressor Status
NOTE: In the following VIEW COMP screens, the #N field indicates which compressor (#1, or #2,)
is being viewed. There are two columns of menus, the first for compressor #1, the second for #2.
VIEW COMP#N (1)
State = RUN
% RLA = XXX %
Evap LWT =000.0°F
State settings can be OFF, START, INTLOK, HOLD, LOAD, UNLOAD, SHUTDOWN, STOP, and
ALARM as determined from the Comp State variable, the Load and Unload outputs, and the
presence of a compressor shutdown alarm.
VIEW COMP#N (2)psi VIEW COMP#N (3)TC Temp
Cond Press =XXXX BCMM PCB =XXX°F Backplane
Evap Press =XXXX =XXX°F
Lift Press = XXX VFD Assembly = XXX°F
View Alarms
ALARM LOG 01
Description
hh:mm:ss dd/mmm/yyyy
ALARM LOG 02 to 25
Description
hh:mm:ss dd/mmm/yyyy
ACTIVE ALARM
Time Date
Fault Description
Demand Limit settings can be OFF or ON as determined from the Demand Limit setpoint.
SET COMP#N SPs (2)
StageMode = NORMAL
StageSequence# =01
Max Comprs ON =02
Full Load timing is one of several “full load flags,” parameters that indicate a compressor is at full
load.
SET COMP# SP1 (5)
Lead Staging=XXX%
Nom Capacity=XXXXT
Hotgasbypass=XX%
! CAUTION
Only trained compressor technicians should set these setpoints.
Min Position @
Set Point
(60°F)
Additional fields can be edited by pressing the ENTER key until the desired field is selected. When
the last field is selected, pressing the ENTER key switches the display out of “edit” mode and
returns the arrow keys to “scroll” mode.
Alarms
When an alarm occurs, the alarm type, date, and time are stored in the active alarm buffer
corresponding to that alarm (viewed on the Alarm Active screens) and also in the alarm log buffer
(viewed on the Alarm Log screens). The active alarm buffers hold a record of the last occurrence of
each alarm and whether or not it has been cleared. The alarm can be cleared by pressing the Edit
key. A separate buffer is available for each alarm (High Discharge Pressure, Evaporator Freeze
Protect, etc.) The alarm history buffer holds a chronological account of the last 25 alarms of any
type.
Display Languages
Languages currently available are:
• English
Units of Measure
It is possible to select units of measure directly from the keypad. Systems available are:
• °F / psi: unit controller, touch screen
• °C / kPa: touch screen only
12 BAS Interface
The MicroTech V controller is available with the optional Open Choices feature, an exclusive
Daikin feature that provides easy integration with a building automation system (BAS). If the unit
will be tied into a BAS, the controller should have been purchased with the correct factory-installed
communication module. The modules can also be added in the field during or after installation.
If an interface module was ordered, one of the following BAS interface installation manuals was
shipped with the unit. Contact your local Daikin sales office for a replacement, if necessary.
Connection to Chiller
Connection to the chiller for all BAS protocols will be at the unit controller. An interface card will
have to be installed in the unit controller depending on the protocol being used.
Press “Close System” and “Start Center” window popup as following photo.
1) The USB disk can be unplug until the “Start Center” window popup.
2) After the copy of USB disk is completed, restore the USB disk to KTP1200 touch screen,
press “Start” button and back to chiller operation system.
13.2 How to operate when touch screen normal power cut
Due to KTP1200 touch screen comes with Linux OS, the safety power cut operation is
required to store the data record with lossless. It generates a large number of data record
archive when a long term chiller operation, it is most probably existing date record be
overwritten due to the archive “RT_COUNT flag” loss when the safety power cut operation
has not been taken.
Hence, it suggests carry out as per “Close System” procedure before chiller is required to
be power cut.
13.3 How to operate when touch screen abnormal power cut
If KTP1200 touch screen is power cut with irresistible conditions, after power reapplied, it
suggests carry out as per “Close System” procedure immediately to prevent existing data
record be overwritten and lost from happening.
The proper maintenance prolongs service life and enhances performance of the AC system.
The maintenance starts basically as the chiller starts. 3 to 4 weeks after the first start-up, it
must be overall inspected, followed by periodical maintenance.
McQuay provides diversified maintenance service according to different customer needs.
Contact Methods
★The printing may deviates from the real products, please refer to the real object when purchasing.
★All material is carefully reviewed. In case of any printing errors, McQuay bears no responsibility.
★Models, parameters and performance may change due to product improvement without further
notification. Please refer to the nameplate for detail.