5tbuk04 Bujv SD 720 El DWG 10105

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

N

KEY PLAN
Q
NOTES:
1. CONTAINMENT ARE SIZED BASED ON THE CABLES AS PER THE
DESIGN AND ACTUAL REQUIREMENTS
2. COORDINATION ON SITE TO BE CONDUCTED WITH THE ARCHITECT,
INTERIOR DESIGN, AV & SIGNAGE SPECIALISTS, BOWLING
EQUIPMENT SPECIALIST (AIDA) AND CLIENT BY OUR ELECTRICAL
SPECIALIST
3. THE SHOWN CONTAINMENT SYSTEM INCLUDES ALL THE REQUIRED
ACCESSORIES
4. ALL CONTAINMENT ARE SIZED WITH 40% SPARE CAPACITY, AND IN
COMPLIANCE WITH LATEST REGULATION/REQUIREMENTS.
5. THE CONTAINMENT FOR THE TELECOM/IT CABLING ARE SELECTED
TAKING INTO ACCOUNT THE BENDING RADIUS OF THE HORIZONTAL
CABLING.
6. ALL CONTAINMENTS TO BE CORRECTLY EARTHED.
7. FIRE RATED MATERIALS ARE USED TO PROPERLY CLOSE ANY
OPENINGS FOR THE CONTAINMENT.
37
––––––
39
––––––
41
––––––
42
–––––– ––––––
43 8. FOR ALL PENETRATIONS FOR CONTAINMENT WILL BE FIRE SEALED
AND AS PER FIRE CONSULTANTS REQUIREMENTS SIGNED OFF BY
X1 X1 X1 X1 X1 THE ARCHITECT, ENGINEER AND THE CLIENT.
9. METALLIC CONDUITS ARE USED FOR EXPOSED CEILING AREAS.
10. DIFFERENT SUPPORT SYSTEM (OTHER THAN THE ONE SUPPORTS
THE CEILING) WILL BE USED FOR ALL SERVICES WITHIN THE CEILING
VOIDS.
11. ACCESS FOR MAINTENANCE IS CONSIDERED FOR ALL CABLE
TRAYS RUNNING THROUGH VOID SPACE.
12. ALL ELECTRICAL CONTAINMENTS HAVE AN INDEPENDANT
DEDICATED SUPPORT FIXED TO SLAB.
13. GI CONDUITS IS USED FOR ANY EXPOSED NSTALLATION.
14. ELECTRICAL SPECIALIST FOR MORE DETAILS IS TO READ & General Notes
IMPLEMENT THIS DRAWING IN CONJUNCTION WITH ALL ELECTRICAL 1. UNLESS OTHERWISE INDICATED, ALL DIMENSIONS ARE IN MILLIMETERS AND
INSTALLATIONS AND SCHEMATICS/RISERS. LEVELS IN METERS.
15. ALL INVERT REFERENCES ARE FROM 00-GFL-FFL(-230) / 772.050 2. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE RELEVANT
ARCHITECTURAL, LANDSCAPE, CIVIL,STRUCTURAL, MECHANICAL and ELECTRICAL
16. MINIMUM 300 MM CLEARANCE BETWEEN LV AND ELV
AND TELECOMMUNICATION ENGINEERING DOCUMENTS
CONTAINMENT & PROJECT SPECIFICATIONS.
750
3. ALL DIMENSIONS ARE TO BE CHECKED AND VERIFIED PRIOR TO THE
COMMENCEMENT OF CONSTRUCTION ON SITE.DRAWINGS MUST NOT BE SCALED.
ONLY WRITTEN OR CONSOLIDATED DIMENSIONS SHALL BE USED.

400
AT
––––––
400 mmx100 mm
LV CABLE TRAY FOR MCC-01
BOT=3385mm FROM 00-GFL (-230) / 772.050

Y1 Legends
SYMBOLS DESCRIPTION
300 mmx100 mm
SUNSHADED CABLE TRAY FOR MECH EQP.
BOT=22485mm FROM 00-GFL (-230) / 772.050

2970
150 mmx100 mm 200 mmx100 mm
BOT=22455mm FROM 00-GFL (-230) / 772.050 SUNSHADED CABLE TRAY FOR MECH EQP. DITRIBUTION BOARD
BOT=22455mm FROM 00-GFL (-230) / 772.050
FOR OU-01 FOR DH-02
H=22500mm 32A 150 mmx100 mm
SUNSHADED CABLE TRAY FOR MECH EQP.
H=22890mm
BOT=22565mm FROM 00-GFL (-230) / 772.050
100A SUB MAIN DISTRIBUTION BOARD

AS
–––––– CABLE TRUNKS SEPARATION MOTOR CONTROL CENTER

Y1
1865 4865

IT. 32A 2290 1765 LIGHTING


ROOM
FOR DH-01
CONTROL LIGHTING CONTROL PANEL

1520
H=22635mm
5030

FOR AHU-01 32A 32A 300 mmx100 mm 1- XXA


H=22500mm SUNSHADED CABLE TRAY FOR MECH EQP.
CCTV TPN ISOLATOR, XX: DENOTES FOR AMPER RATING
BOT=22485mm FROM 00-GFL (-230) / 772.050

ICT ACS
ELEC. BMS XXA

1200
SPN ISOLATOR , XX: DENOTES FOR AMPER RATING
ACCESS TO COMPRESSOR ROOM FOR FAHU-01 SUPPLY FAN
H=22535mm
150 50 50 50
ELV CABLE TUNK XXA WEATHER PROOF (IP56/IP65) TPN ISOLATOR, XX:
DENOTES FOR AMPER RATING

1200
XXA WEATHER PROOF (IP56/IP65) SPN ISOLATOR , XX:
300 mmx100 mm
SUNSHADED CABLE TRAY FOR MECH EQP.
NORMAL DENOTES FOR AMPER RATING
KITCHEN 9385
BOT=22485mm FROM 00-GFL (-230) / 772.050
LIGHTING
ELV RACK (TYPE INDICATED ON

1200
32A 2-
DRAWING)
NORMAL CBS
POWER + CABLE TRAY FOR POWER CABLES
FOR FAHU-01 EXHAUST FAN
UPS (SIZE AS MENTIONED)

1200
H=22535mm
TO BE COORDINATED WITH LANDLORD

100 50 50 CABLE TRUNKING (STAINLESS STEEL) FOR


KITCHEN EQUIPMENTS(SIZE AS MENTIONED)
EMERGENCY CABLE TRUNK

1200
300 mmx100 mm MEDIUM CABLE TRUNKING FOR LIFE
SUNSHADED CABLE TRAY FOR MECH EQP. SAFETY (SIZE AS MENTIONED)
BOT=22485mm FROM 00-GFL (-230) / 772.050

3- MEDIUM CABLE TRUNKING FOR SMALL

1200
POWER AND LIGHTING (SIZE AS MENTIONED)
32A PAVA
BGM MEDIUM CABLE TRUNKING (ELV & BMS)

AQ REFRESHMENTS
(SIZE AS MENTIONED)

980
50 50

365
–––––– 32A TWO COMPARTMENT AV TRUNKING(LV&ELV)

Y1 FOR ECOLOGY UNIT


H=22875mm LIFE SAFETY CABLE TRUNK (SIZE AS MENTIONED)

FOR EXF-01 4- FA SYSTEM LOOP WITH CONDUITS SPECIAL TRUNKING


H=22755mm
(SIZE AS MENTIONED)

3990
2010 6365

150 mmx100 mm

2815
BOT=3385mm FROM 00-GFL (-230) / 772.050

FOR MAHU-1

FOR DH-03
80A H=22575mm

H=22580mm

32A
REFRENCE DRAWINGS
150 mmx100 mm
150 mmx100 mm
SUNSHADED CABLE TRAY FOR MECH EQP.
BOT=3385mm FROM 00-GFL (-230) / 772.050 SUNSHADED CABLE TRAY FOR MECH EQP.
BOT=3385mm FROM 00-GFL (-230) / 772.050
S.N DESCRIPTION DRAWING NO. REV
GROUND LEVEL-PRIMARY CONTAINMENT ROUTS & DISTRIBUTION BOARD
1 5TBUK04- TNEC- FC- 720- EL- DWG- 60004 A
LOCATIONS LAYOUT

1 Cable schedule for CT going to Bowling Roof (400x100mm) 2

3
ROOF LEVEL-PRIMARY CONTAINMENT ROUTS & DISTRIBUTION BOARD
LOCATIONS LAYOUT
ELECTRICAL SERVICES SCHEMATIC DIAGRAM
5TBUK04- TNEC- FC- 720- EL- DWG- 60005

5TBUK04-TNEC-FC-720-EL-DWG-60003
A

A
DINING

AP
––––––
Y1
00 SHOP DRAWINGS ISSUED FOR RA SB 13.07.2024
APPROVAL
Rev Description Apvr Chk'd Date

DINING Client

Programme Managment Organization

AO
––––––
Design Consultant
Y1

Main Contractor

Sub Contractor

ARCADE AREA

AN
–––––– Project Title
Y1
TABUK ENTERTAINMENT COMPLEX

Drawing Title

BOWLING
BOWLING ROOF LEVEL PLAN LAYOUT
(OVERALL) - PRIMARY CONTAINEMENT &
DISTRIUTION BOARD
Approved Seal Date

SB 16/07/24

Drawn By Checked

VZ RA

Model File Ref: Scale A1(594X841) Revison No

5TBUK04-BUJV-SD-720-EL-MOD-00001 As Indicated 00

Drawing No

5TBUK04-BUJV-SD-720-EL-DWG-10105