2CDC111015D0201
2CDC111015D0201
2CDC111015D0201
Characteristics
Single-function OFF-delay timer with auxiliary voltage
One device includes 10 time ranges, from 0.05 s to 300 h, for the adjustment of the time delay
2 c/o contacts
1
2CDC 251 113 F0004
2nd c/o contact can be selected as instantaneous contact (front-face sliding switch)
7
Volt-free (dry) control contact
2
Starting the time delay is possible
6
- via an external control contact
5
3 LEDs for status indication
4
Width 22.5 mm
8
3
Approvals
CT-AHS
a cULus
1 10 selectable time ranges, b GL
from 0.05 s to 300 h e GOST
2 Potentiometer with direct f CCC
reading scale for the fine
adjustment of the time delay
3 Sliding switch to set the Marks
2nd c/o contact as an
g CE
instantaneous contact
c C-Tick
4 U/T: green LED -
Supply voltage (LED flashes
during timing)
Order data
5 R1: red LED -
Output relay 1 energized Type Supply voltage Order code
6 R2: red LED - CT-AHS 24 V, 42-48V AC/DC, 110-240 V AC 1SVR 430 113 R0200
Output relay 2 energized
7 Circuit diagram
Order data (Accessories)
8 Marker label
Description Order code
Adapter for screw mounting on panel 1SVR 430 029 R0100
Sealable cover 1SVR 430 005 R0100
Marker label 1SVR 366 017 R0100
Application
The CT-S range timers are designed for use in industrial applications. They operate over a universal
range of supply voltages and a large time delay range, within compact dimensions. The easy-to-set
front-face potentiometers, with direct reading scales, provide accurate time delay adjustment.
Operating mode
The CT-AHS with 2 c/o contacts offers 10 time ranges, from 0.05 s to 300 h. The time delay range is
rotary switch selectable on the front of the unit. The fine adjustment of the time delay is made via an
internal potentiometer, with a direct reading scale, on the front of the unit.
Timing is displayed by a flashing green LED labelled U/T.
1
Electronic timer CT-AHS
OFF-delayed with 2 c/o contacts
Data sheet
Function diagram
B OFF-delay (Delay on break)
This function requires continuous supply voltage at terminals A1/B1/B2-A2 for timing.
Timing is controlled by a volt-free control contact, connected to terminals Y1-Z2. If the control contact
is closed, the output relays energize. If the control contact is opened, the selected time delay starts
(minimum control pulse length is 20 ms). The green LED flashes during timing. When the time delay is
complete, the output relays de-energize and the flashing green LED turns steady.
If control contact Y1-Z2 closes before the time delay is complete, the time delay is reset and the output
relays remain energized.
If the front-face sliding switch is set to the “Inst.” position, the 2nd c/o contact energizes immediately
upon application of the supply voltage.
A1/B1/B2-A2
Connection diagram
B CT-AHS
A1 15 B1
2CDC 252 103 F0005
Y1 Z2 25 21
25
B1 A1 15 21
B2 A2 16 18 26 28
22 24
28 24 26 22 B2
18 16 A2
2
Electronic timer CT-AHS
OFF-delayed with 2 c/o contacts
Data sheet
Wiring notes
A1
Z2 Y1
230 V / AC
24 V / DC
Y1 Z2
A2
Proximity switch
Y1
N L-
Y1
A2
Proximity switch
L-
Z2 X1
X1
A1
Z2 X1 Y1
pause timing /
time storage
start timing
Y1 Z2
A2
Y1 Z2
N/L-
3
Electronic timer CT-AHS
OFF-delayed with 2 c/o contacts
Data sheet
Technical Data
Input circuits
Supply voltage A1-A2 110-240 V AC
B1-A2 24 V AC/DC
B2-A2 42-48 V AC/DC
Power consumption 110-240 V AC approx. 2.5-12 VA
24 V AC/DC approx. 0.5 VA/W
42-48 V AC/DC approx. 1.8 VA/W
Supply voltage tolerance -15...+10 %
Supply voltage frequency AC/DC Version DC or 50/60 Hz
AC Version 50/60 Hz
Control contact connections volt-free (dry) Y1-Z2 start timing external
Minimum control pulse length 20 ms
Non-load voltage at the control contacts 10-40 V DC (no galvanic separation to
supply circuit)
Max. current in the control circuit 1 mA
Max. cable length to the control inputs 50 m
Duty time 100 %
Timing circuit
Time ranges 0.05 s - 300 h 1) 0.05-1 s
2) 0.15-3 s
3) 0.5-10 s
4) 1.5-30 s
5) 5-100 s
6) 15-300 s
7) 1.5-30 min
8) 15-300 min
9) 1.5-30 h
10) 15-300 h
Recovery time < 50 ms
Repeat accuracy (constant parameters) < 0.2 %
Timing error within the supply voltage tolerance range < 0.008 % / % d U
Timing error within operating temperature range < 0.07 % / °C
Indication of operational states
Supply voltage / timer green LED steady / flashing while timing
1st / 2nd output relay energized red LED / red LED
Output circuits 15-16/18, 25(21)-26(22)/28(24)
Number of contacts Relays, 2 c/o contacts,2nd c/o contact
selectable as instantaneous contact
Contact material AgCdO
Related voltage acc. to VDE 0110, IEC 60947-1 250 V
Maximum switching voltage 250 V AC, 250 V DC
Rated switching current acc. to IEC 60947-5-1 AC-12 (resistive) 230 V 4A
AC-15 (inductive) 230 V 3A
DC-12 (resistive) 24 V 4A
DC-15 (inductive) 24 V 2A
Maximum lifetime mechanical 30 x 106 switching cycles
electrical (AC-12, 230 V, 4 A) 0.1 x 106 switching cycles
Short circuit proof, max. fuse rating n/c 10 A fast, operating class gL
n/o 10 A fast, operating class gL
General data
Enclosure width 22.5 mm
length 78.0 mm
depth 100.0 mm
Wire size fine-strand with wire end ferrule 2 x 0.75 - 2.5 mm2 (18-14 AWG)
fine-strand without wire end ferrule
rigid 2 x 0.5 - 4 mm2 (20-12 AWG)
Weight approx. 150 g (5.3 oz)
Mounting position any
Degree of protection enclosure / terminals IP50 / IP20
Temperature operating -20...+60 °C
storage -40...+85 °C
4
Electronic timer CT-AHS
OFF-delayed with 2 c/o contacts
Data sheet
5
Electronic timer CT-AHS
OFF-delayed with 2 c/o contacts
Data sheet
AC load (resistive)
V
100
80
60
50
40
30
20
10
0.1 0.2 0.5 1 2 4 6 10
I A
DC load (resistive)
V
300 2CDC 252 193 F0205
V 200
100
80
60
50
40
30
20
10
0.1 0.2 0.5 1 2 4 6 10
I A
0.9
0.8
F
0.7
0.6
0.5
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
9
8
N
5
4
3
2
104
1 2 3 4 5 6 7 8
I A
Dimensional drawings
Dimensions in mm
109,5 4.31“ 22,5
.886“
102 4.02“
2CDC 252 188 F0005
78 3.07“
100 3.94“
6
Electronic timer CT-AHS
OFF-delayed with 2 c/o contacts
Data sheet
4,5
.394”
.886”
22,5
10
60 2.36”
7 .275”
front-to-back
size 107
Sealable cover
2CDC 252 186 F0005
3A11
.315”
8
20
.787”
Marker label
7
Printed in the Federal Republik of Germany (08/05)
Druckschrift-Nummer. 2CDC 111 015 D0201