Aluminium Conductor Steel Supported (ACSS)-ACCC®


ACSS conductor consists of fully annealed strands of aluminium around a stranded steel core. In appearance,
ACSS conductors are essentially identical to standard ACSR conductors. ACSS is typically available in “Standard
Round Strand” construction or “Trapezoidal Aluminium Wire” construction with equal area or equal diameter
to conventional round wire construction. The steel core may be of High Strength (HS), Extra High Strength
(EHS), Ultra High Strength (UHS) steel, mischmetal or aluminium Clad Steel core.

APPLICATION
Sterlite® Aluminium Conductor Steel Supported (ACSS)
ACSS conductors can be used as a low loss solution, as part of efficient transmission networks. These conductors are
suitable for lines that transmit very high or fluctuating loads.

Ideal for Reconductoring & New Lines.


• Increase capacity of lines while maintaining Electrical clearance.
• Can be Deployed in Existing Structures or can reduce strain on structures, increasing life.
• 100% more capacity building towards future demands.

BENEFITS
• Improved self-damping characteristics and high degree of resistance to vibration fatigue.
• Can operate continuously at high temperatures up to 250°C with appropriate steel core coating v/s 100°C for
standard ACSR, hence can carry twice as much current as ACSR conductor.
• Less susceptible to Aeolian vibration fatigue due to very low mechanical load on the annealed aluminium wire.
• Requires conventional installation techniques.
• Allows for lower overall transmission cost.
EMPOWERING HUMANITY BY ADDRESSING THE TOUGHEST CHALLENGES OF ENERGY DELIVERY
TECHNICAL SPECIFICATIONS

ACSS/R ACSS/R ACSS/R ACSS/TW ACSS/TW ACSS/TW


PROPERTIES UNIT
HAWK DRAKE CURLEW HAWK DRAKE CURLEW

Appropriate 220 kV / 220 kV /


kV 132 kV 220 kV 132 kV 220 kV
System Voltage above above

Equivalent ACSR PANTHER ZEBRA MOOSE PANTHER ZEBRA MOOSE

Reference Standards ASTM B 856 ASTM B 857

Conductor diameter mm 21.77 28.13 31.62 20.07 25.65 28.70

Weight kg/km 976 1629.0 1981 975 1623. 1973

Ultimate tensile
KN 88.0 145.0 155 88.0 144.5 155
strength

DC resistance at
Ohm/km 0.1161 0.0696 0.0536 0.116 0.0695 0.0534
20°C temperature

Current carrying
capacity at
A 1212 1701 1986 1181 1651 1953
maximum operating
temperature (250)

Note: The Catalogue conductor Parameter are informative and can be customized as per Project Requirements.

Assumptions: Ampacity is calculated based on, 45°C ambient temperature, 0.56 m/s wind velocity, 0.8 as coefficient of
solar absorption, 0.45 as coefficient of emissivity and 1045 W/sq.m coefficient for solar radiation, 0 m Elevation.

Non-Specular (NS) Dull Finish Conductor can be available on special requirement.

Disclaimer:
* Parameters mentioned in the document are indicative and can vary subject to different standards
* Customizations are available on select products. Please indicate your interest by reaching out to the sales team