Electrical Drawings
Electrical Drawings
Electrical Drawings
Scale: AS NOTED
7-11 #1034883 / 37318
Date: 02/24/16 20908 ROSCOE BLVD
CANOGA PARK, CA 91304
Drawn By: NP
E0.0
Checked By: NP
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Description
LANDLORD.
ROSCOE BLVD 2. SEE OTHER PLANS FOR ALL INTERIOR WORK WITHIN TENANT
SPACE.
Date
CONDUIT ROUTING, DEVICE LOCATION TYPE AND COLOR OF PAINT
TO BE USED TO MATCH EXISTING SURROUNDING OR SURFACES.
Rev. #
4. ALL EXTERIOR PENETRATIONS SHALL BE WEATHERPROOF
SEALED.
DeSOTO AVENUE
AS NOTED
02/24/16
NP
NP
15385
Checked By:
1 ELECTRICAL
SITE PLAN
Drawn By:
1" = 40'-0"
Scale:
Job#:
Date:
SHEET:
E0.1
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Description
2. PROVIDE ARC FLASH LABELING AS REQUIRED PER NEC 110.16
Date
INSTALLED BY GC.
Rev. #
PANEL SCHEDULES
20908 ROSCOE BLVD
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E02 - PANEL SCHEDULES AND ONE-LINE DIAGRAM.dwg, E11, 4/27/2016 8:04:37 AM, npatena
(E) 1
225A
SEE TABLE 3P
BELOW (NIC)
(E)
FEEDER
(N) (NIC)
PANEL (E)
C (NIC) (E)75KVA
240-120/208V,
(N) If =5.79KA
PANEL 1 (NIC)
A
SEE TABLE (E)
BELOW FEEDER (E) UTILITY
AIC=10KA
(NIC) COMPANY
FEED
AS NOTED
02/24/16
15385
NP
NP
(E)
Checked By:
(E) M
Drawn By:
400A
SEE TABLE 3P
BELOW (E) (E) (E) (E) (E)
MAIN
Scale:
SPACE SPACE SPACE 300A 225A
Job#:
Date:
3P 3P
(N) (N) (N) (N)
PANEL PANEL PANEL TVSS
B L S /SPD
(E) MAIN SWITCHBOARD "SWBD"
AIC=10KA AIC=10KA AIC=10KA 2 1
If = 24.0KA (PER LADWP KEVN R
DIEM DESIGN) AIC = 30.0 KA
(N) PC OUTDOOR
RELAY PHOTOCELL
PANEL SYMBOL LEGEND
BREAKER
FUSE
SWITCH
14
3 ELECTRICAL NOTES:
1 1 1 1 E1.0 1. ALL RECEPTACLES SERVED FROM PANEL "S" SHALL BE OF THE ISOLATED
19 KEYNOTES - POWER GROUND TYPE. ALL CIRCUITS SHALL CONTAIN A HOT, NEUTRAL, GROUND
(N) (N) (N) (N) SEE SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION. AND ISOLATED GROUND CONDUCTOR.
B-9 PNL PNL PNL PNL 1
8 +93" A B S C 2. ISOLATED GROUND (IG) 20 AMP CIRCUIT, FLUSH MOUNT QUAD PLATE WITH
DEVICES SHALL BE NEMA 5-20 UNLESS NOTED OTHERWISE. TYP OF
J 2 ORANGE RECEPTACLES.
4 S-23 120V-20A CIRCUITS.
EXTERIOR SIGNAGE J-BOX. COORDINATE FINAL LOCATION WITH 2A. ISOLATED GROUND (IG) 20 AMP DUPLEX CIRCUIT FOR ATM.
HALLWAY
Description
2 2 +96" 3
19 AFF SIGNAGE CONTRACTOR AND CONSTRUCTION MANAGER. RUN
E1.0
1 1 TYP. BACKROOM B-19,21,23 EXTERIOR BUILDING SIGNS THROUGH PHOTOCELL DRIVEN 3.
J RATED TERMINATIONS AND CONDUCTOR INSULATION. CONTRACTOR SHALL
(N) (N) CONTACTOR. PROVIDE PAD-LOCKABLE BREAKER FOR MAINTENANCE.
B-1 PNL RELAY S-30 FIELD VERIFY EQUIPMENT TEMPERATURE RATINGS OF ALL TERMINATIONS
3 ENERGY MANAGEMENT ENCLOSURE PROVIDED BY OTHERS, PROVIDE AND ADJUST CONDUCTOR SIZES PER NEC 110.14(C)
L PNL 7 4
120V DEDICATED CIRCUIT ONLY.
8 J J J J J E1.0 RECEPTACLE FOR ATM SIGN. VERIFY LOCATION WITH CONSTRUCTION 4. ALL WIRING IS COPPER. REFER TO ELECTRICAL SPECIFICATIONS FOR
1 5 FURTHER INFORMATION.
A7 A7 A7 C-25,27,29 MANAGER PRIOR TO COMMENCEMENT OF WORK.
+42" 11 +42" +42" 11
19 19 WINDOW RECEPTACLES, MOUNT FLUSH IN CEILING, TYP. PER NEC 5. WORK STATION RECEPTACLE FOR TASK LIGHTING AND TRAINING
1 A7 6 COMPUTER.
+42" +42" 21 23 19
OFFICE
Date
+42" L14-50 18 18 +42" TELEPHONE BOARD: 4'X8'X1" FIRE TREATED PLYWOOD PAINTED WHITE.
7 6. ISOLATED GROUND (IG) 20 AMP CIRCUIT FOR STORE COMPUTER, FLUSH
2 18 PROVIDE WITH (1) #6 CU. GROUND FOR PER TELE. CO. REQUIREMENTS. MOUNT FACE PLATE FOR DUPLEX RECEPTACLE WHICH RECEIVES PLUG
12 MOUNT RECEPTACLE ADJACENT TO OR ABOVE TELEPHONE BOARD, DO
B-2 C-10,12 C-10,12 18 L14-30 FROM UPS (BATTERY BACKUP) AND FUTURE PERIPHERALS.
E1.0 B-6 B-25 B-6 C-6,8 NOT MOUNT BELOW. PROVIDE (1) 2"C UP TO MALL MAIN TEL BACKBOARD.
+42" L6-20 L6-20 C-26,28 6-20
Rev. #
20 +42" +42" +42" FIELD VERIFY. 7. ALL WALL MOUNTED RECEPTACLES SHALL BE 18" A.F.F FROM BOTTOM.
MEN'S WOMEN'S 31
UNLESS NOTED OTHERWISE.
+42" C-34,36 CONTRACTOR TO PROVIDE DISCONNECT SWITCH EQUAL TO EATON
B-9 8
B330AN WITH LOCAKBLE ENCLOSURE MODE NO. B330BG. 8. QUAD RECEPTACLE FOR SECURITY EQUIPMENT. RECEPTACLE RECEIVES
+93" C-10,12 THE FOLLOWING EQUIPMENT PLUGS:
B17 B15 C-14,16
J J REFER TO EVAPORATOR COIL WIRING DETAIL #5.
+42" +42" 9 A. VCR
DRY
S-17 15
S-19 S-1
S-24 3 J L-31
+154"
S-24
S-13 S-7
L-14
9 8 S-25
A-5 TYP. 6 21
FLR J CLG
MTD
15
E1.0 10
J
4
18 C-30,32 A-19
TYP.
17 L-17,19,21
5 6
18 C-18,20 J J 19
23 8 S-2 B-9
J
L-4 CLG B-14 19 CLG +93"
17
A-14
NOTE: MONEY ORDER AND
A-4 J L-22 J
3
WP/GFCI +94" L-33,35
LOTTO CORDS TO BE RAN
22 S-3 (ABOVE
IN SAME GROMMET. 16 1P/30A/NF 3 ROOF)
AS NOTED
02/24/16
15385
NP
NP
NEMA-3R
Checked By:
Drawn By:
Scale:
Job#:
Date:
CEILING
CONDUIT PENETRATION CONDUIT AT CEILING PENETRATION
SEALED WITH SILICONE FILLED WITH SEALANT
SEALANT
CONDUIT AND WIRING TO PANEL
CONDUIT AND WIRING TO FURNISHED BY OWNER, INSTALLED BY G.C.
NEXT JUNCTION BOX ON COOLER/FREEZER BOX CEILING
SAME SYSTEM
CEILING MOUNTED WP JUNCTION BOX
WITH THREADED HUBS AND GASKETED
NOTE 8 COVERPLATE
CEILING S-4
NOTE 2A TYPICAL COIL S-8 NOTE 6
S-2 SYMBOL LEGEND
PROVIDE CEILING MOUNTED MANUAL INSTALL LIGHTING
TWO-POLE SWITCH IN WEATHERPROOF OVERRIDE SWITCH
TELEPHONE/ SPECIAL RECEPTACLE
ENCLOSURE. PROVIDED BY EMS.
ROUTER S-12 REF EMS1.0 DATA OUTLET (SEE NEMA CONFIG)
NOTE 6
S-10 J JUNCTION BOX
NOTE 9 FUSED DISCONNECT
NOTE 5
5'-8"
CONNECTION TO COIL BY GC
HP RATED SW. EQUAL TO
2'-10"
TYP.
120 V RECEPTACLE,
CEILING MOUNT DUPLEX EATON B230AN OR B330AN
FOR 3 POLE
NOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE.
DESK 120 V RECEPTACLE, PANEL BOARD
SIMPLEX
E1.0
DOUBLE DUPLEX
REFER TO ARCH INTERIOR OFFICE
MGR'S OFFICE WIRING ATM WIRING 5 EVAPORATOR COIL WIRING FUEL E-STOP
4 (NOTE: NOT ALL SYMBOLS ARE USED)
3 WORKSTATION WIRING
ELEVATIONS FOR EXACT DIMENSIONS
2 N.T.S.
N.T.S. N.T.S.
N.T.S.
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
ADJACENT TENANT
N.I.C.
HALLWAY
BACKROOM CDC /
TOTES
Description
LOCKERS
Date
MEN'S WOMEN'S
SANDWICH CASE EMERGENCY
EXIT ONLY
Rev. #
CONDIMENTS
PENETRATION PLAN
ELECTRICAL SLAB
20908 ROSCOE BLVD
P1 ROLLER
GRILLS
P1 P1
COOLER
VAULT
ADJACENT TENANT
N.I.C.
P1
P2
MERCHANDISE
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E11 - ELECTRICAL SLAB PENETRATION PLAN.dwg, ., 4/27/2016 8:06:14 AM, npatena
SALES
36'-6"
35'-6"
P1
P2
29'-1"
28'-2"
14'-6"
13'-6"
28'-0"
20'-6"
NOVELTY
19'-6"
ATM
25'-0"
31'-4"
40'-2"
40'-8"
AS NOTED
02/24/16
15385
NP
NP
1 ELECTRICAL
SLAB PENETRATION PLAN
1/4" = 1'-0"
Checked By:
Drawn By:
Scale:
Job#:
Date:
UNDERGROUND CONDUIT SCHEDULE
CONDUIT
DESIGNATOR SIZE NOTE
P1 3/4" REFER TO E 1.0 FOR ELECTRICAL CIRCUITS. VERIFY LOCATION IS ACCEPTABLE AND FREE OF OBSTACLES PRIOR TO TRENCHING.
P2 1" REFER TO E 1.3 FOR DATA CIRCUITS. VERIFY LOCATION IS ACCEPTABLE AND FREE OF OBSTACLES PRIOR TO TRENCHING.
SHEET:
E1.1
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
GENERAL NOTES:
1. CONTRACTOR TO PROVIDE UNIT SMOKE DETECTION FOR HVAC SHUT DOWN. PROVIDE ALL REQUIRED CONNECTION
2. GFCI TYPE RECEPTACLE. PROVIDE WITH 'IN-USE' W.P. COVER EQUAL TO REDDOT #CKPM.
Description
KEYNOTES - POWER HVAC/R
Date
NEMA-3R
CONDENSER SEE SCHEMATIC WIRING DIAGRAM ON THIS SHEET
25 AF 3
3 UNIT
COND. 3 EQPT. SEE SHEET E2.0 FOR CONNECTION. EXHAUST FAN PROVIDED BY
COND. 4
Rev. #
FOR 841 LANDLORD.
EQPT 3 FOR
EQPT SEE SHEET E0.2 FOR FEEDER AND CIRCUIT INFORMATION
A-4 105 5
306
WP/GFCI
ON ROOF
1
HVAC/R PLAN
ELECTRICAL
1
1
A-4 RTU-2
WP/GFCI
ON ROOF
C-7,9,11
5
3P/60A/F
3P/60A/F NEMA-3R
NEMA-3R RTU-1 50 AF
40 AF 5
C-1,3,5
C-19,21,23
2
60AS
40 AF
COND.
FOR
WALK-IN
COOLER
CONDENSER
UNIT EQPT.
125
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E12 - ELECTRICAL HVAC-R PLAN.dwg, ., 4/27/2016 8:06:32 AM, npatena
(FREEZER)
CONDENSER
UNIT EQPT.
869(ICE
MERCHANDIZER)
AS NOTED
02/24/16
15385
NP
NP
ELECTRICAL HVAC-R PLAN
1 1/4" = 1'-0"
Checked By:
Drawn By:
Scale:
Job#:
Date:
FOR EQPT 841 FOR EQPT 306 FOR EQPT 105, 125, & 869 FOR WALK-IN COOLER
#8
FEEDER AND CIRCUITING
PER PLAN FEEDER AND CIRCUITING FEEDER AND CIRCUITING FEEDER AND CIRCUITING
* NEMA PER PLAN PER PLAN PER PLAN ABOVE
#8 L14-20
#10 #10
2
* NEMA 60AS
#10
L14-30
INDOOR OUTDOOR
SHEET:
EQUIPMENT SCHEMATIC WIRING DIAGRAM
NTS
E1.2
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Description
ABOVE WORKSTATION BACKROOM CDC / 1
TOTES 4. MONEY ORDER CABLES. D-4.
4
OFFICE 3
E1.3
5. CASH REGISTER CABLES, D-1 & D-2. TWO CATEGORY 5 CABLES FROM SALES
AREA CASH REGISTERS INTO ONE DUPLEX CATEGORY 5 RECEPTACLE
COVER PLATE.
Date
CEILING TILE (MAY NEED TO MOVE LATER). 100' IN TOTAL LENGTH WITH
POST MIX SLURPEE EXTRA COILED AT FEMALE JACK
ICED ICED
5 COFFEE TEA 6.2 CAT6 RJ45 FEMALE JACK CENTER OF SALES FLOOR SUSPENDED ABOVE
CEILING TILE (MAY NEED TO MOVE LATER). 100' IN TOTAL LENGTH WITH
MEN'S WOMEN'S
Rev. #
E1.3 EXTRA COILED AT FEMALE JACK.
SANDWICH CASE EMERGENCY
6.3 CAT6 RJ45 FEMALE JACK IN RECEPTACLE 84" ABOVE FLOOR - CENTER OF
EXIT ONLY WALK-IN COOLER.
7-ELEVEN, INC.
DEGREE ANGLES PERPENDICULAR OR PARALLEL TO JOISTS. COORDINATE
ATM WIRING
2 N.T.S. ROLLER
GRILLS
ADJACENT TENANT
VIEW MONITOR: ROUTE CONDUIT BACK TO VIDEO RECORDING
2
EQUIPMENT LOCATED IN MANAGER'S OFFICE. COORDINATE LOCATION
10"x10" J-BOX IN SPACE WITH SECURITY SYSTEM INSTALLER. REFER TO LOW VOLTAGE RISER
ABOVE WORKSTATION DIAGRAM FOR WIRING REQUIREMENTS.
TELEPHONE BOARD: 4'X4'X3/4" PLYWOOD WITH (1) #6 CU.
(1) 1"C TO ATM 6 3
GROUND FOR FUTURE USE MOUNTED ABOVE 4'X4'X3/4"
N.I.C.
SEE NOTE PLYWOOD WITH (1) #6 CU. GROUND PER TELE. CO.
(1) 1"C TO ATG 6.3 D-1 REQUIREMENTS. MOUNT RECEPTACLE ADJACENT TO OR
(FUELING ONLY) ABOVE TELEPHONE BOARD, DO NOT MOUNT BELOW.
D-3
(1) 3"C TO (1) 1"C TO SECURITY CAMERA:ROUTE CONDUIT BACK TO VIDEO RECORDING
TELEPHONE BOARD MANAGER'S OFFICE 4
EQUIPMENT LOCATED IN MANAGER'S OFFICE. COORDINATE LOCATION
4 WITH SECURITY SYSTEM INSTALLER.
CEILING (1) 1"C TO ACCESS
POINT- WALK IN
MERCHANDISE NOT USED.
(1) 3"C TO 10"x10" J-BOX ABOVE J 5
COOLER
SALES COUNTER. STUB OUT (2)
2"C INTO SALES COUNTER SALES ROUTE WIRING FOR DATA DEVICES UNDER SLAB, RE: 1/E1.1
(1) 1"C TO ACCESS 6
POINT-SALES FLOOR 6 MOUNT +12'AFF, ROUTE CONDUIT BACK TO VIDEO RECORDING
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E13 - LOW VOLTAGE FLOOR PLAN.dwg, ., 4/27/2016 8:06:46 AM, npatena
7
D-2 EQUIPMENT LOCATED IN MANAGER'S OFFICE. COORDINATE LOCATION
WITH CONSTRUCTION MANAGER AND SECURITY SYSTEM INSTALLER.
NOTE 7 AP-6.1
NOTE 11 AP-6.2 D-4
AP-6.3 3" CONDUIT TO
J-BOX BELOW D-6
ROUTER ROUTER
INSTALL LIGHTING J
OVERRIDE SWITCH
D-1,D-2 & 2 T-30 PV LINK
T-49/50 T-30 PROVIDED BY EMS.
D-4 D-8
T-39 REF EMS1.0 T-49/50
D-6 (IF USED)
D-7
E1.3
5'-8"
2
4'-0"
NOVELTY
10"x10" J-BOX
2'-10"
TYP.
4
ATM
J
TYPICAL WORKSTATION ELEVATION. MAY NEED
MODIFICATION PER ACTUAL CONDITIONS.
4 WORKSTATION
WIRING
AS NOTED
02/24/16
15385
NP
NP
1 LOW
N.T.S. VOLTAGE FLOOR PLAN
1/4" = 1'-0"
Checked By:
Drawn By:
Scale:
Job#:
Date:
(1) 1"C TO WORKSTATION
(1) 1"C TO VIDEO CAMERAS
(1) 1"C TO TELEPHONE
(1) 2"C TO SALES COUNTER BOARD
(1) 2"C
CEILING SECURITY
ALARM DATA PHONES
PANEL DESIGNATION LINE CONDUIT SIZE FROM TO DESIGNATION LINE CONDUIT SIZE FROM TO
D-1 COMPUTER AT IN SLAB 1" 10" X 10" J-BOX @ SALES AREA T-49/50 STORE VOICE LINE, THROUGH 1" TELEPHONE BOARD BACK ROOM 10" X 10"
REGISTER #1 WORKSTATION AREA LOCATED AT SALES CONDUIT J-BOX & THEN TO
AREA, MGR'S OFFICE FRONT SALES
(1) 1"C D-2 COMPUTER AT IN SLAB 1" 10" X 10" J-BOX @ SALES AREA
& RIS WORK STATION. COUNTER
REGISTER #2 WORKSTATION AREA
NOTE 3 D-3 HOLD-UP BUTTON IN SLAB 1" MGRS OFFICE SALES AREA - T-30 MONEY ORDER, LONG THROUGH 1" TELEPHONE BOARD TO FRONT SALES
T-49/50 REGISTER #1 DISTANCE CARDS CONDUIT RIS, FROM RIS 10" X 10" COUNTER
T-39 (FAX) (LDC) AND EBT (FOOD TO SALES
CAMERA SIGNAL THROUGH CEILING 10" X 10" J-BOX @ STAMP PROGRAM)
WORKSTATION AREA
T-39 FAX LINE AT RIS THROUGH 1" TELEPHONE BOARD ABOVE WORKSTATION
D-4 MONEY ORDER IN SLAB 1" 10" X 10" J-BOX @ WORKSTATION CONDUIT CLG TO RIS 10" X 10"
DESK WORKSTATION AREA
T-75 V-COM LINE THROUGH 1" TELEPHONE BOARD ATM LOCATION
D-5 ATG THROUGH CONDUIT 1" ISP DESK - ATG MONITOR (ELECTRIC ROOM) CONDUIT
TO ELECTRIC ROOM FUEL TANKS
T-68/72 SECURITY LINE/ 1" TELEPHONE BOARD TO RIS TELEPHONE BOARD
D-6 LOTTO THROUGH CONDUIT 1" 10" X 10" J-BOX @ SALES AREA POLICE/ FIRE LOCATED 10" X 10", TO MGR'S OFFICE OUTLET
REFER TO ARCH INTERIOR OFFICE IN SLAB WORKSTATION AREA AT TELEPHONE BOARD & REG #1
ELEVATIONS FOR EXACT DIMENSIONS D-7 ATM THROUGH OVERHEAD 1" 10" X 10" J-BOX @ VCOM WALL T-63/64 PAY TELEPHONES SEE SITE 1" TELEPHONE BOARD SEE SITE PLAN
CONDUIT WORKSTATION AREA SHARED REVENUE PLAN
NOTE: ALL DATA LINES TRAVEL FROM DEMARC THROUGH 3" CONDUIT TO 10" X 10" J-BOX IN CEILING, DOWN TELEPHONES
THROUGH WALL INTO 10" X 10" J-BOX BEHIND RIS DESK. SHEET:
NOTE: ALL PHONE LINES TRAVEL FROM DEMARC THROUGH 3" CONDUIT TO 10" X 10" J-BOX MOUNTED ABOVE ISP.
INTERCOM
EMS D-19 EMS D-19
+
+
VIEW MONITOR V-1 (1) RG59 (1)12.2 REGISTER #1 D1.1 TO D1.4 T-39 SALES CTR MOM
4
ANALYTICS CAMERA V-7 REGISTER #3 D8.1 TO D8.4 T-39 SALES CTR FAX
1 LOW
1/4" = 1'-0"
PANIC BUTTON D-3 (1)18.2 ACCESS POINT AP-6.3 T-39 ATM
REG#1 CNTR SECURITY V-2 ACCESS POINT AP-6.2
REG#2 CNTR SECURITY V-3 ACCESS POINT AP-6.1
3
LOTTO D-6
VOICE T-49/50
VOLTAGE RISER DIAGRAM
ATM
INTERCOM
BY FUELING CONTRACTOR.
SALES COUNTER
Scale: AS NOTED
7-11 #1034883 / 37318
Date: 02/24/16 20908 ROSCOE BLVD
CANOGA PARK, CA 91304
Drawn By: NP
E1.4
Checked By: NP
LOW VOLTAGE DETAILS
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
KEYNOTES - LIGHTING
OCCUPANCY SENSOR 'A', PER DETAIL NO.2 ON
1 SHEET E2.1.
DEVICE PART OF LIGHTING CONTROL SYSTEM.
2 SEE SHEET E-3.2
LOW VOLTAGE SWITCH FOR MANUAL
3 RAISE/LOWER OVERRIDE DIMMING CONTROL.
Description
PROVIDE WITH REQUIRED ENGRAVING FOR
SWITCH LEGS.
6 13W LED COOLER DOOR LIGHTS PROVIDED AND
3 2 4 INSTALLED BY COOLER DOOR MANUFACTURER,
E.C. TO PROVIDE WIRING FOR COOLER/
A1 A1 FREEZER DOOR LIGHTS AND CONNECT TO
MANUFACTURER SUPPLIED JUNCTION BOX.
Date
PROVIDE REQUIRED SWITCH PACK AND
6 CONNECTION
6
Rev. #
2
A1 A1 PROVIDE SWITCH 'G' FOR WALK-IN COLLER
7 LIGHT AND SWITCH 'H' FOR COOLER DOOR
LIGHTS.
6f 6f 6
LIGHTING PLAN
A1 A1
6f 6f
L-8
L-6
6
2 3 2
6
A1 A1 A1 A1 A1 HALLWAY
A1 A1 A1 A1 A1 A1
6
BACKROOM
6f 6f 6f 6f 6f
2 8d 8d 8d 8d 8d 8d
6 6
2 2
3 2
8
D2 D2
8a MEN'S 8 WOMEN'S
8b 8b
1 1 8
A1 A1 A1 A1 A1
8c 8c 8c 8c 8c
A1 A1
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E20 - LIGHTING PLAN.dwg, ., 4/27/2016 8:07:30 AM, npatena
8c 8c
A1 A1 A1 A1 A1 A1
7 L-11,13
8c 8c 8c 8c 8c 8c
8c
A1 A1 A1 A1 A1 A1
8c 8c 8c 8c 8c 8c
COOLER 3
VAULT
7
AS NOTED
02/24/16
15385
NP
NP
A1 A1 A1 A1 A1 A1
5
8c 8c 8c 8b 8b
Checked By:
8b
Drawn By:
Scale:
Job#:
Date:
EXTENTS OF
DAY LIT AREA
A1 A1
A1 A1 A1 A1
MERCHANDISE
8c 8c 8c 8b 8b 8b
SALES b
2
TYP.
4
A1 A1
7 A1 A1 A1 A1
L-18
8c 8c 8c 8b 8b 8b
A1 A1 A1
8c 8a 8a
8
EXTENTS OF L2 8
a DAY LIT AREA
2
SHEET:
1 LIGHTING
PLAN
1/4" = 1'-0" E2.0
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Description
LT FAN RECESSED 1/4HP@120V MOTOR, COMMERCIAL GRADE - WHITE CALIFORNIA
TROFFER TITLE 24 COMPLIANT. ALL TO
Line Black White BE PROVIDED AND INSTALLED BY G.C.
Blue
Date
Ground LEVITON
Rev. #
PROVIDE 2 PER SIDE.
GC TO PROVIDE WHEN ARCHITECTURAL FINISHES.
NOTE: RESTROOM SET TO 10 MINUTES.
BACKROOM AND OFFICES SET TO 20 MINUTES. REQUIRED BY CODE.
3. CONTRACTOR TO NOTE THE ENTIRE LIGHTING
BACKROOM WITH HIDDEN AREAS SET TO 30 MINUTES. CONTROL WHICH INCLUDES SWITCHING, DIMMING
AND DAY LIGHT HARVESTING IS DONE THRU LOW
LAY IN CEILING GRID VOLTAGE WIRING. DIMMING SYSTEM USES PURPLE
rev. 8/2012
7-ELEVEN, INC.
MANUFACTURER AS REQUIRED BY CODE AS PART OF
Neutral
AS NOTED
02/24/16
15385
NP
NP
Checked By:
rev. 8/2012
N
Drawn By:
L-2
Scale:
Job#:
Date:
EMS SYSTEM LIGHTING
CONTROL SIGNAL
(REF EMS1.0)
4 LIGHTING
N.T.S.
CONTACTOR
SHEET:
E2.1
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E23 - EGRESS PHOTOMETRICS.dwg, ., 4/27/2016 8:08:37 AM, npatena
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
1
1/4" = 1'-0"
EGRESS LIGHTING
Scale: AS NOTED
7-11 #1034883 / 37318
Date: 02/24/16 20908 ROSCOE BLVD
CANOGA PARK, CA 91304
Drawn By: NP
E2.3
Checked By: NP
EGRESS LIGHTING
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
ELECTRICAL SPECIFICATION
INTRODUCTION 3.5.1.1 SINGLE POLE SWITCHES: 3.7.4 FUSES, EQUIPMENT:
THE CONTRACTING FOR INSTALLATION OF THE ELECTRICAL SYSTEM WILL BE ACCOMPLISHED IN THE FIELD AT THE SINGLE POLE WALL SWITCHES SHALL BE SIMILAR AND EQUIVALENT; TO "LEVITON" EQUIPMENT FUSES, IF REQUIRED, SHALL BE OF THE DUAL ELEMENT, TIME DELAY VARIETY
DIVISION LEVEL. THESE SPECIFICATIONS ARE TO AID IN PREPARATION OF DIVISION LEVEL STORE PLANS AND CONTRACT #CS120-2W 20A, 120-277VAC TOGGLE SWITCH (WHITE) WITH COVERPLATE FOR SINGLE AS INDICATED ON PLANS. FUSES FOR HVAC/REFRIGERATION SHALL BE SIMILAR AND EQUIVALENT
DOCUMENTS. IN CASE OF A CONFLICT BETWEEN THIS SPECIFICATION AND THE CONTRACT DOCUMENTS PROVIDED BY GANG OR (WHITE) COVERPLATE FOR DOUBLE GANG. TO COOPER BUSSMANN FUSE TYPE LPN-RK-SP, CLASS RK1 FOR THE APPROPRIATE AMPERAGE.
THE DIVISION CONSTRUCTION MANAGER, THE DIVISION'S PLANS AND SPECIFICATIONS SHALL PREVAIL.
3.5.1.2 3-WAY SWITCHES: 3.8 SPD SHALL BE PROVIDED BY GRAYBAR.
Description
DEFINITIONS
THE FOLLOWING DEFINITIONS APPLY TO THIS PROJECT. 3-WAY SWITCHES SHALL BE SIMILAR AND EQUIVALENT TO "BRYANT" #4503-I 20A, 3.9 CONDUCTORS:
120-277VAC 3-WAY SWITCH (WHITE HANDLE) AND (WHITE) COVERPLATE FOR
FURNISH - TO SUPPLY THE MATERIAL NECESSARY TO PERFORM THE TASK. SINGLE GANG OR (WHITE) COVERPLATE FOR DOUBLE GANG. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN, UNO. MINIMUM CONDUCTOR SIZE SHALL BE
INSTALL - TO SUPPLY THE LABOR NECESSARY TO COMPLETE THE TASK. #12 AWG. CONDUCTORS #10 AWG AND LARGER SHALL BE STRANDED. INSULATION TYPE SHALL
PROVIDE - TO FURNISH AND INSTALL MATERIAL AND LABOR TO COMPLETE THE TASK. 3.5.1.3 SINGLE THROW, DOUBLE POLE EVAPORATOR SWITCH CONFORM WITH N.E.C. OR MANUFACTURER REQUIREMENTS. LIGHT FIXTURES SOMETIME REQUIRE
90 DEGREE WIRE. FOR THE PARTICULIAR APPLICATION. USE TYPE THWN IN WETR LOCATIONS.
1. SCOPE SINGLE THROW, DOUBLE POLE SWITCHES SHALL BE SIMILAR AND EQUIVALENT TO "BRYANT"
#30322D 120-600VAC NEMA 3R ENCLOSED AC MANUAL MOTOR CONTROLLER/DISCONNECT. 3.9.1 NM CABLE (ROMEX) SHALL NOT BE USED.
1.1 E.C. TO PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT (U.N.O.) REQUIRED TO EXECUTE WORK PER NEC AND
Date
ALL APPLICABLE ELECTRICAL CODES IN FORCE AT THE TIME OF PROJECT COMPLETION. 3.9.2 ALUMINUM CONDUCTORS SHALL NOT BE USED U.N.O.
3.5.2 NOT USED
1.2 THIS WORK INCLUDES, BUT IS NOT LIMITED TO: ELECTRICAL SERVICE AND DISTRIBUTION SYSTEMS, PANELBOARDS, 3.9.3 METAL-CLAD CABLE (MC) SHALL BE PERMITTED FOR USE AS BRANCH CIRCUITS
DISCONNECT SWITCHES, LIGHTING FIXTURES, POWER AND CONTROL WIRING WITH FINAL CONNECTIONS TO ALL 3.5.3 CONVENIENCE OUTLET (20A):
IN WALL, CEILING OR CABINETRY.
EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM.
Rev. #
20A CONVENIENCE OUTLETS SHALL BE SIMILAR AND EQUIVALENT TO "LEVITON" #CR20-W
2 POLE, 3 WIRE, 20 A 125V, DUPLEX GROUNDING RECEPTACLE WITH (WHITE) COVERPLATE 4. TESTING AND INSPECTION
1.3 E.C. TO VERIFY TYPE OF POWER SERVICE AVAILABLE (UNDERGROUND OR OVERHEAD) AND
MAXIMUM SHORT CIRCUIT CURRENT PRIOR TO SUBMITTING A PROPOSAL. SIMILAR AND EQUIVALENT TO "LEVITON" #88003 FOR SINGLE DUPLEX OR "LEVITON"
#88016 FOR DOUBLE DUPLEX (QUAD). 4.1 TESTING:
1.4 E.C. TO VERIFY TYPE OF TELEPHONE SERVICE AVAILABLE (UNDERGROUND OR OVERHEAD) 4.1.1 THE E.C. SHALL TEST, PRIOR TO ENERGIZING FOR THE FIRST TIME,
PRIOR TO SUBMITTING A PROPOSAL. 3.5.4 OUTLET, ISOLATED GROUND (20A):
ELECTRICAL GENERAL
CANOGA PARK, CA 91304
WITH (WHITE) COVERPLATE.
7-ELEVEN, INC.
(HIGH LEG) SHALL BE BALANCED AS CLOSELY AS POSSIBLE.
2. INSTALLATION
SPECIFICATIONS
3.5.6 NOT USED
4.2 INSPECTION:
2.1 THE INSTALLATION SHALL COMPLY WITH ALL LAWS IN EFFECT AT THE TIME OF CONSTRUCTION APPLYING TO
ELECTRICAL INSTALLATION, AND WITH THE REGULATIONS OF THE NEC, WHERE SUCH REGULATIONS DO NOT 3.5.7 SAFETY SWITCHES:
E.C. SHALL FURNISH AT THE COMPLETION OF THE PROJECT OR
CONFLICT WITH THE LAWS IN EFFECT, AND WITH THE PUBLIC UTILITY COMPANY FURNISHING THE SERVICE. EACH INSPECTION POINT OF THE PROJECT, AN INTERMEDIATE OR FINAL INSPECTION
SAFETY SWITCHES SHALL BE UL APPROVED GENERAL DUTY SAFETY SWITCHES WITH LOCK OFF
HANDLES SIMILAR AND EQUIVALENT TO THOSE MANUFACTURED BY "SQUARE-D". SWITCHES CERTIFICATE FROM THE LOCAL INSPECTING AUTHORITY.
2.1.1 THE E.C. SHALL UPGRADE THESE SPECIFICATIONS AS REQUIRED TO MEET COMPLIANCE WITH ALL
APPLICABLE CODES IN EFFECT; HOWEVER, WHERE THESE SPECIFICATIONS MAKE STIPULATIONS OVER AND WILL BE FUSIBLE OR NON-FUSIBLE AS INDICATED ON PLANS/LOCAL CODES AND WILL BE NEMA
TYPE 1 FOR INDOOR (DRY) INSTALLATION OR A NEMA TYPE 3R ENCLOSURE FOR OUTDOOR 4.3 PERFORMANCE REQUIRED:
ABOVE THE MINIMUM REQUIREMENTS OF APPLICABLE CODES, THE CONTRACTOR SHALL NOT DOWN-GRADE
THESE SPECIFICATIONS TO MINIMUM CODE REQUIREMENTS WITHOUT PRIOR WRITTEN APPROVAL FROM INSTALLATION. FUSED SWITCHES SHALL HAVE REJECTION STYLE FUSE HOLDERS TO MATCH
LPN-RK CLASS RK1 FUSES. 4.3.1 ALL EQUIPMENT AND FIXTURES SHALL BE PROPERLY CONNECTED WITH
7-ELEVEN. ADEQUATE POWER AND CHECKED THOROUGHLY FOR PROPER OPERATION.
2.2 E.C. SHALL PROVIDE ALL REQUIRED ELECTRICAL CONDUIT AND WIRING FOR ALL MOTORS, MOTOR STARTERS 3.5.8 NOT USED
4.3.2 ALL EXPOSED EQUIPMENT SHALL BE INSTALLED AS PER DRAWINGS AND IS
AND ELECTRICAL CONTROLS, U.N.O. E.C. SHALL MAKE ALL LINE VOLTAGE ELECTRICAL CONNECTIONS AS SUBJECT TO INSPECTION FOR WORKMAN-LIKE APPEARANCE.
REQUIRED FOR HVAC SYSTEMS. 3.5.9 PHOTO CELL (OUTDOOR):
ELECTRONIC LIGHT SENSOR SHALL BE THE TORK EPC-1. ENCLOSED IN A LEXAN HOUSING 5. INDUSTRY-STANDARDS
2.3 E.C. SHALL INSTALL THE CONNECTIONS TO ALL RECEPTACLES, SALES COUNTERS,
GONDOLAS AND FINAL CONNECTIONS TO ALL FIXTURES AFTER FIXTURES ARE IN PLACE. WITH A 1/2" CONDUIT MOUNTING AND 180 DEGREE SWIVEL. INSTALL IN A WEATHER
TIGHT JUNCTION BOX ON THE ROOF PER MANUFACTURER'S RECOMMENDATIONS. SET 5.1 THE FOLLOWING IS A LIST OF ABBREVIATIONS USED IN THE ELECTRICAL NOTES AND
SENSOR TO 100 FOOT-CANDLE LEVEL. SPECIFICATIONS.
2.4 E.C. SHALL VERIFY EXACT LOCATION OF ALL SIGNS WITH 7-ELEVEN REPRESENTATIVE. PROVIDE ALL CONDUITS AND
WIRES WITH STUB-UPS AS DIRECTED BY THE 7-ELEVEN CORPORATION AND INSTALL FINAL CONNECTIONS AS NEC.....................NATIONAL ELECTRIC CODE, REF. COVERSHEET FOR APPLICABLE VERSION
REQUIRED. 3.5.9.1 LIGHTING CONTROLLER (OUTDOOR LIGHTING CONTROL):
NEMA..................NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
THE LIGHTING CONTROLLER SHALL BE THE TORK LC-200 IN A NEMA 1 ENCLOSURE. UL........................UNDERWRITERS LABORATORIES, INC.
2.5 WIRING HVAC...................HEATING, VENTILATING AND AIR CONDITIONING
THE LC-200 IS USED IN CONJUNCTION WITH THE TORK EPC-1 PHOTOCELL. LIGHTING
CONTROLLER HAS A 2 TO 100 FOOT-CANDLE LIGHT ADJUSTMENT. IEEE......................INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
2.5.1 ALL WORK SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER. THE E.C. SHALL GFCI.....................GROUND FAULT CIRCUIT INTERRUPTER
CONTACT THE 7-ELEVEN CORPORATION REPRESENTATIVE SHOULD THIS PLAN REQUIRE MODIFICATION TO AIC.......................AMPERES INTERRUPTING CAPACITY
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E30 - ELECTRICAL GENERAL SPECIFICATIONS.dwg, E3.0, 4/27/2016 8:08:51 AM, npatena
2.5.4 THE E.C. SHALL ENSURE THAT CIRCUIT AMPACITY AND SHORT CIRCUIT/OVERLOAD PROTECTION IS THE PHOTOCELL BYPASS SWITCH SHALL BE A "BRYANT" #4801-L SINGLE POLE LOCK
APPROPRIATE FOR THE EQUIPMENT BEING INSTALLED. UL LISTING CONDITIONS SHALL BE OBSERVED. TYPE 15A 120-277 VOLT SWITCH WITH KEY #6006 AND COVERPLATE (WHITE).
NOTE: NO SUBSTITUTION SHALL BE PERMITTED UNLESS THE E.C. CAN PROVE TO THE 7-ELEVEN
2.5.5 TO COMPLY WITH NEC/UL LISTING CONDITIONS, ROOFTOP UNITS MAY BE SHOWN WITH FUSED CORPORATION REPRESENTATIVE THAT THE PROPOSED SUBSTITUTE WILL OPERATE WITH
DISCONNECT SWITCHES: "BRYANT" KEY #6006. THE KEY SHALL BE TURNED OVER TO THE 7-ELEVEN CORPORATION
REPRESENTATIVE AT ACCEPTANCE (NOT LEFT IN SWITCH, CASH REGISTER, ETC.).
2.5.5.1 ALL FUSES SERVING MOTOR LOADS WILL BE OF THE DUAL ELEMENT TYPE.
3.5.12 HEAT TRACE - FREEZER PIPE FREEZE PROTECTION (WHEN REQUIRED):
2.5.5.2 DUE TO DIFFERENT INTERRUPTING CHARACTERISTICS, PANELBOARD CIRCUIT BREAKERS MAY BE
RATED HIGHER THAN THE DUAL ELEMENT FUSES THEY SUPPLY TO ENSURE SUFFICIENT STARTING HEATING CABLE: FURNISH RAYCHEM 5XL1-CR WITH RAYCLIC-PC ELECTRICAL CONNECTION. XL
CURRENT. TRACE BY TYCO THERMAL CONTROLS, LLC. FOR EXTRA INFORMATION CONCERNING HEAT TRACE
SYSTEM CONTACT DAN PETERSEN WITH INDUSTRIAL HEATER (901-382-4761).
2.5.6 WIRE SIZES LISTED ARE MINIMUM. CONDUCTORS SHALL BE SELECTED SUCH THAT THE MAXIMUM VOLTAGE
DROP (AT FULL LOAD AMPS) SHALL NOT EXCEED THE FOLLOWING GUIDELINES: CIRCUIT BREAKER: PROVIDE SQUARE 'D' Q0120EPD OR EQUIVALENT GFCI CIRCUIT BREAKER WITH
30mA TRIP.
2.5.6.1 PANEL FEEDERS --2% OF CIRCUIT VOLTAGE AT SERVICE.
NOTE: MECHANICAL CONTRACTOR TO INSTALL SELF REGULATING HEATING CABLE PER
2.5.6.2 ALL BRANCH LOADS--3% OF CIRCUIT VOLTAGE AT SERVICE. MANUFACTURER'S REQUIREMENTS ON CONDENSATE DRAIN LINES INSIDE FREEZER BOXES THAT
ARE TO OPERATE AT OR BELOW 32 DEGREES F.
2.5.6.3 TOTAL VOLTAGE DROP (SERVICE TO LOAD)--5% OF CIRCUIT VOLTAGE AT SERVICE.
3.6 SERVICE/DISTRIBUTION EQUIPMENT:
2.5.7 SPECIAL NOTES ON SERVICES:
PANEL AND DISTRIBUTION PANEL SHALL BE SQUARE 'D'. ALL SWITCH GEAR TO BE FURNISHED FROM
2.5.7.1 120/208V, 3-PHASE, WYE GRAYBAR, U.N.O. FOR PRICING AND PLACING ORDERS, CONTACT `7-ELEVEN' FOR THE APPROPRIATE
THE E.C. SHALL CHECK THE REQUIREMENTS OF ALL EQUIPMENT AND WILL INSTALL SALES DEPARTMENT.
AUTOTRANSFORMERS (BUCK AND BOOST TRANSFORMERS) AS REQUIRED.
AS NOTED
02/24/16
15385
3.6.1 MAIN POWER SWITCHES
NP
NP
2.5.8 THE E.C. SHALL PROVIDE DEDICATED CIRCUITS WITH ISOLATED GROUND FOR ALL CIRCUITS
ORIGINATING FROM PANEL S. THE PURITY OF THE ISOLATED GROUND SHALL BE MAINTAINED BY USING ONLY THE MAIN PANEL POWER SWITCHES/CIRCUIT BREAKERS SHALL BE SQUARE 'D' TYPE I LINE, RATED AT 65,000
INSULATED GROUNDING CONDUCTORS AND ISOLATED GROUND. THE GROUNDING CONDUCTOR FOR THE . A.I.C. (MIN.) SWITCHES OR CIRCUIT BREAKERS SHALL BE LISTED AS INDICATED ON PLANS.
ISOLATED GROUND SHALL NOT MAKE ELECTRICAL CONTACT WITH THE COMMON EQUIPMENT GROUND OR
NOTE: PANEL RATINGS REQUIRED FOR HIGHER AIC REQUIREMENTS SHALL BE PRESENTED TO THE
Checked By:
ANY ITEM CONNECTED TO THE COMMON EQUIPMENT GROUND (I.E. CONDUITS, "J"-BOXES, SWITCH BOXES,
ETC.) AT ANY POINT OTHER THAN AT THE SERVICE GROUNDING TERMINAL. SEE NEC 250.96(B). DISTRIBUTOR FOR MODIFICATIONS TO THE GEAR SUBMITTAL.
Drawn By:
2.6 WHEN REQUIRED, E.C. TO ENSURE INTEGRITY OF FIRE RATED WALLS WHERE ELECTRICAL EQUIPMENT 3.6.2 PANELBOARDS:
Scale:
PENETRATES WALLS. SEAL PER SPECIFICATIONS FOR FIRE STOPPING.
Job#:
Date:
SQUARE 'D' PANELBOARDS USED IN SERIES WITH I-LINE CIRCUIT BREAKERS AND FITTED
2.7 ALL PENETRATIONS THROUGH EXTERIOR WALLS ARE TO BE MADE WITH LB CONDULETS OF THE APPROPRIATE WITH SQUARE 'D' BRANCH CIRCUIT BREAKERS ARE AS INDICATED ON PLANS.
SIZE PER NEC. ALL PENETRATIONS ARE TO BE SEALED PER NEC. HORIZONTAL OR VERTICAL SUPPORTS FOR USE AN APPROPRIATE SQUARE 'D' CIRCUIT BREAKER WITH EACH PANEL. CIRCUIT
RACEWAYS ARE TO COMPLY WITH NEC. WIRE TIES ARE NOT TO BE USED, U.N.O. BREAKERS SHALL BE TYPE QOXXX-"QO"-FRAME
3. MATERIALS: 3.6.2.1 PANEL 'F', IF REQUIRED, SHALL BE FED BY A SQUARE 'D' BREAKER WITH SHUNT TRIP
AND SHALL BE WIRED FOR EMERGENCY SHUT DOWN.
ALL MATERIALS AND DEVICES SHALL BE UL APPROVED AND SHALL CONFORM TO THE STANDARDS OF NEMA, NEC,
AND IEEE. 3.6.2.2 UPON COMPLETION OF WORK, E.C. SHALL PROVIDE A TYPED DIRECTORY IN EACH
PANELBOARD. INCLUDE SYSTEM VOLTAGE, PHASING, CIRCUIT NUMBERING AND DESCRIPTIONS.
3.1 LIGHT FIXTURES: PER SCHEDULE ON ELECTRICAL PLAN.
3.6.3 WIREWAY:
3.2 RACEWAYS: ALL CONDUIT SHALL BE EITHER RIGID STEEL OR ELECTRICAL METALLIC TUBING (EMT). FOR IN SLAB
AND UNDERGROUND INSTALLATIONS, PVC OR RIGID STEEL SHALL BE USED. REFER TO FUELING SHEETS FOR THE WIREWAY SHALL BE SIMILAR AND EQUIVALENT TO "SQUARE D COMPANY" WIREWAY WITH
APPROVED FUELING SYSTEMS CONDUIT. INSTALL PER NEC. APPROPRIATE FITTING FOR THE PARTICULAR INSTALLATION. E.C. SHALL SIZE TO INSTALLATION
IN ACCORDANCE WITH NEC, GOOD PRACTICE AND CODES IN EFFECT AT TIME OF
3.3 FITTINGS AND BUSHINGS:ALL REQUIRED BENDS, FITTINGS, JUNCTION BOXES, ETC., WHETHER OR NOT THEY ARE INSTALLATION.
SHOWN ON THE DRAWINGS, SHALL BE INSTALLED TO SATISFY ALL APPLICABLE ELECTRICAL CODES AND STANDARDS 3.7
OF GOOD PRACTICE. ALL CONDUCTORS ENTERING/LEAVING A CONDUIT OR RACEWAY SHALL BE AFFORDED OVERCURRENT/SHORT CIRCUIT PROTECTIVE DEVICES:
ABRASION PROTECTION BY AN ADEQUATE BUSHING OR OTHER APPROVED MEANS.
3.7.1 PANELBOARD BRANCH/FEEDER CIRCUIT BREAKERS:
3.4 OUTLET BOXES: SHALL BE STANDARD, STAMPED GALVANIZED STEEL BOXES; "J"-BOXES AND OUTLET BOXES USED AS
A PULL BOX SHALL BE PROVIDED WITH A SUITABLE COVER OF SAME MATERIAL AS BOX. ALL DOWNSTREAM BREAKERS MUST BE SQUARE 'D' TO MAINTAIN SERIES LISTING. IF
FUSIBLE DISCONNECTS ARE USED, SQUARE 'D' PANEL BOARDS AND CIRCUIT BREAKERS
3.5 WIRING DEVICES: SHALL BE USED.
INSTALL ON EACH AND EVERY OUTLET BOX, A WIRING DEVICE AND/OR COVERPLATE, ALL AS INDICATED BY SYMBOL 3.7.2 GROUND FAULT CIRCUIT INTERRUPTER (GFCI) BREAKERS:
ON THE DRAWINGS.
GROUND FAULT CIRCUIT INTERRUPTER (GFCI) TYPE CIRCUIT BREAKERS SHALL BE
3.5.1 WALL SWITCHES: SIMILAR TO THE PANELBOARD CIRCUIT BREAKERS BUT WITH GROUND FAULT
PROTECTION WITH MATCHING A.I.C. RATING. GFCI BREAKERS SHALL BE UL
APPROVED AS CLASS A DEVICES IN ACCORDANCE WITH UL STANDARD #943.
Description
AN NRTL ACCEPTABLE TO AUTHORITIES HAVING
JURISDICTION. OTHERWISE INDICATED. 2. COATING THICKNESS: 0.040 INCH, MINIMUM. 1. TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS
4. MOUNTING: SPECIFIC MOUNTING HEIGHTS THAT REDUCE
1. LM79 TESTS LEDFIXTURES: WHERE LED TYPE IS 5. VOICE AND DATA COMMUNICATION OUTLET: TWO E.
HEADROOM ARE INDICATED.
SPECIFIED. MODULAR, KEYED, COLOR-CODED, RJ-45 JACKS FOR a. SENSOR: SUITABLE FOR MOUNTING IN ANY POSITION
ON A STANDARD OUTLET BOX. F.
UTP CABLE 2. TO PROVIDE FOR EASE OF DISCONNECTING THE
2. LER TESTS FLUORESCENT FIXTURES: WHERE LER IS EQUIPMENT WITH MINIMUM INTERFERENCE TO OTHER
b. RELAY: EXTERNALLY MOUNTED THROUGH A 1/2-INCH G. LFMC: FLEXIBLE STEEL CONDUIT WITH PVC JACKET AND
F. PREFABRICATED MULTIOUTLET ASSEMBLIES. INSTALLATIONS.
KNOCKOUT IN A STANDARD ELECTRICAL ENCLOSURE.
1. TWO-PIECE SURFACE METAL RACEWAY, WITH H. 3. TO ALLOW RIGHT OF WAY FOR PIPING AND CONDUIT
3. LER TESTS HID FIXTURES: WHERE LER IS SPECIFIED, FACTORY-WIRED MULTIOUTLET HARNESS. 5. TIME-DELAY AND SENSITIVITY ADJUSTMENTS:
INSTALLED AT REQUIRED SLOPE.
Date
RECESSED AND CONCEALED BEHIND HINGED DOOR.
2. COMPONENTS SHALL BE PRODUCTS FROM SINGLE 1. CONDUIT FITTINGS FOR HAZARDOUS (CLASSIFIED) 4. SO CONNECTING RACEWAYS, CABLES, WIREWAYS,
B. LATERAL LIGHT DISTRIBUTION PATTERNS: COMPLY WITH MANUFACTURER DESIGNED FOR USE AS A B. OUTDOOR MOTION SENSORS (PIR).
CABLE TRAYS, AND BUSWAYS WILL BE CLEAR OF
COMPLETE, MATCHING ASSEMBLY OF RACEWAYS 1. PERFORMANCE REQUIREMENTS: SUITABLE FOR OBSTRUCTIONS AND OF THE WORKING AND ACCESS
DISTRIBUTION PATTERNS INDICATED FOR LUMINAIRES.
Rev. #
AND RECEPTACLES. OPERATION IN AMBIENT TEMPERATURES RANGING 2. FITTINGS FOR EMT: SPACE OF OTHER EQUIPMENT.
C. METAL PARTS: FREE OF BURRS AND SHARP CORNERS a. MATERIAL: STEEL. B. COORDINATE INSTALLATION OF REQUIRED SUPPORTING
AND EDGES. 1.13 FUSES
b. TYPE: COMPRESSION. DEVICES AND SET SLEEVES IN CAST-IN-PLACE
D. SHEET METAL COMPONENTS: CORROSION-RESISTANT A. CARTRIDGE FUSES. 2. OPERATION: TURN LIGHTS ON WHEN SENSING CONCRETE, MASONRY WALLS, AND OTHER STRUCTURAL
ALUMINUM UNLESS OTHERWISE INDICATED. FORM AND INFRARED ENERGY CHANGES BETWEEN I. NON METAL CONDUITS, TUBING, AND FITTINGS. COMPONENTS AS THEY ARE CONSTRUCTED.
ELECTRICAL MATERIAL
CANOGA PARK, CA 91304
RELAMPING WITHOUT USE OF TOOLS. DESIGNED TO 1.
7-ELEVEN, INC.
MARKED FOR INTENDED LOCATION AND APPLICATION. WEATHERPROOF ELECTRICAL ENCLOSURE. E. THE CONTRACTOR SHALL PROVIDE ALL WORK REQUIRED
PREVENT DOORS, FRAMES, LENSES, DIFFUSERS, AND
SPECIFICATIONS
OTHER COMPONENTS FROM FALLING ACCIDENTALLY 2. NRTL COMPLIANCE: LUMINAIRES FOR HAZARDOUS c. TIME-DELAY AND SENSITIVITY ADJUSTMENTS: HEREUNDER TO MAKE A COMPLETE AND WORKING
DURING RELAMPING AND WHEN SECURED IN OPERATING LOCATIONS SHALL BE LISTED AND LABELED FOR RECESSED AND CONCEALED BEHIND HINGED DOOR. WIREWAYS INSTALLED OUTDOORS SHALL BE LISTED
INSTALLATION, INCLUDING OWNER PROVIDED
POSITION. DOORS SHALL BE REMOVABLE FOR CLEANING INDICATED CLASS AND DIVISION OF HAZARD BY AN
4. BYPASS SWITCH: OVERRIDE THE ON FUNCTION IN EQUIPMENTS.
OR REPLACING LENSES. DESIGNED TO DISCONNECT NRTL. QUALIFIED TESTING AGENCY, AND MARKED FOR
CASE OF SENSOR FAILURE. INTENDED LOCATION AND APPLICATION F. ALL PHASES OF THE PROJECT SHALL BE CONSTRUCTED
BALLAST WHEN DOOR OPENS. 3. FM GLOBAL COMPLIANCE: LUMINAIRES FOR
5. AUTOMATIC LIGHT-LEVEL SENSOR: ADJUSTABLE AND INSTALLED IN ACCORDANCE WITH THESE
G. EXPOSED HARDWARE MATERIAL: STAINLESS STEEL. HAZARDOUS LOCATIONS SHALL BE LISTED AND D. BOXES, ENCLOSURES, AND CABINETS.
FROM 1 TO 20 FC; KEEP LIGHTING OFF DURING SPECIFICATIONS AND THE APPROVED CONSTRUCTION
LABELED FOR INDICATED CLASS AND DIVISION OF
H. PLASTIC PARTS: HIGH RESISTANCE TO YELLOWING AND DAYLIGHT HOURS. 1. GENERAL REQUIREMENTS FOR BOXES, ENCLOSURES, DRAWINGS. IF THERE IS ANY CONFLICT BETWEEN THIS
HAZARD BY FM GLOBAL.
OTHER CHANGES DUE TO AGING, EXPOSURE TO HEAT, AND CABINETS: BOXES, ENCLOSURES, AND CABINETS DOCUMENT AND THE DRAWINGS, THE DRAWING(S) SHALL
AND UV RADIATION. 4. 6. DETECTOR SENSITIVITY: DETECT OCCURRENCES OF INSTALLED IN WET LOCATIONS SHALL BE LISTED FOR GOVERN AND THE ENGINEER SHALL BE NOTIFIED. UNDER
6-INCH-MINIMUM MOVEMENT OF ANY PORTION OF A USE IN WET LOCATIONS. NO CIRCUMSTANCE SHALL CONTRACTOR TO DEVIATE
I. LIGHT SHIELDS: METAL BAFFLES, FACTORY INSTALLED 5. HUMAN BODY THAT PRESENTS A TARGET OF NOT FROM PLANS WITHOUT WRITTEN OR REVISED DRAWINGS
AND FIELD ADJUSTABLE, ARRANGED TO BLOCK LIGHT LESS THAN 36 SQ. IN.. E. METAL FLOOR BOXES. FROM ENGINEER OR RESPONSIBLE PARTY.
6. RATED LAMP LIFE OF 35,000 HOURS.
DISTRIBUTION TO INDICATED PORTION OF NORMALLY 1. CAST METAL, FULLY ADJUSTABLE. METAL FLOOR
7. LAMPS DIMMABLE FROM 100 PERCENT TO 0 PERCENT 7. DETECTION COVERAGE: UP TO 35 FEET, WITH A FIELD
ILLUMINATED AREA OR FIELD. BOXES SHALL BE LISTED AND LABELED AS DEFINED IN
OF MAXIMUM LIGHT OUTPUT. OF VIEW OF 90 DEGREES. G. THE CONTRACTOR SHALL BE PAY ALL REQUIRED
5. LIGHTING FIXTURE MOUNTED SENSOR: SUITABLE BUILDING PERMIT FEES AS PART OF BID PRICE.
8. INTERNAL DRIVER AND BALLAST. MARKED FOR INTENDED LOCATION AND APPLICATION.
INSPECTION SHALL ALSO BE PART OF CONTRACTORS
OR 277-V AC. F. HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND RRESPONSIBILITY.CONTRACTOR TO SECURE
WIRING. NECESSARY PERMITS PRIOR TO START OF ANY WORK.
1.15 EMERGENCY AND EXIT LIGHTING
1.9 SWITCHBOARDS 1. BOXES AND HANDHOLES FOR USE IN UNDERGROUND E. GOVERNING CODES AND STANDARDS SHALL BE THE
A. ELECTRICAL COMPONENTS, DEVICES, AND SYSTEMS SHALL BE DESIGNED AND IDENTIFIED AS BASIS OF ALL INSTALLATION. ANY AMBIGUITIES OR
A. FRONT-CONNECTED, FRONT-ACCESSIBLE
ACCESSORIES: LISTED AND LABELED AS DEFINED IN CONSTRUCTION COORDINATION SHALL BE ADDRESSED
SWITCHBOARDS.
APPLICATION. PRIOR TO ANY ROUGH-IN WORK. APPROVED DRAWINGS
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E31 - ELECTRICAL MATERIAL SPECIFICATION.dwg, E3.1, 4/27/2016 8:09:01 AM, npatena
FOR INTENDED LOCATION AND APPLICATION. 1. MAIN DEVICES: FIXED, INDIVIDUALLY MOUNTED. AND OR PERMITTED PERMITS SHALL NOT BE
2. BOXES INSTALLED IN WET AREAS SHALL BE LISTED CONSTRUED AS LICENSE TO CONSTRUCT WORK NOT
B. NRTL COMPLIANCE: FABRICATE AND LABEL EMERGENCY 2. BRANCH DEVICES: PANEL MOUNTED. CONFORMING WITH THE GOVERNING CODES AND
LIGHTING UNITS, EXIT SIGNS, AND BATTERIES TO QUALIFIED TESTING AGENCY, AND MARKED FOR
3. SECTIONS FRONT AND REAR ALIGNED. STANDARDS, AND SHALL NOT RELIEVE THE THE
INTENDED LOCATION AND APPLICATION. CONTRACTOR FROM COMPLYING WITH THE GOVERNING
C. B. BUSSING. CODES, PLANS, AND SPECIFICATIONS.
1.5 SLEEVES AND SLEEVE SEALS
D. 1. TINNED PLATTED COPPER, CONTINUOUS RATED F. CONTRACTOR TO COORDINATE ANY PLANED FOR ANY
AMPERAGE PER DESIGN DRAWINGS. A. SLEEVES. TYPE OF SERVICE DISRUPTION WITH OWNER 10
E. WORKING DAYS. CONTRACTOR TO PROCEED WITH THE
1.
F. INTERNAL TYPE EMERGENCY POWER UNIT: 1.10 PANELBOARDS SERVICE DISRUPTION UPON RECEIPT OF WRITTEN
SELF-CONTAINED, MODULAR, BATTERY-INVERTER UNIT, APPROVAL BY OWNER. ANY UN-PLANNED SERVICE
C. BUSSING. DISRUPTION SHALL BE RESTORED AS SOON AS
2. CAST-IRON PIPE SLEEVES: CAST OR FABRICATED
COMPATIBLE WITH BALLAST. 1. COPPER, CONTINUOUS RATED AMPERAGE PER "WALL PIPE," EQUIVALENT TO DUCTILE-IRON POSSIBLE.
DESIGN DRAWINGS. PRESSURE PIPE, WITH PLAIN ENDS AND INTEGRAL
1. EMERGENCY CONNECTION: OPERATE ONE LAMP(S) WATERSTOP UNLESS OTHERWISE INDICATED.
CONTINUOUSLY AT AN OUTPUT OF 1100 LUMENS
1.11 CIRCUIT BREAKERS B. SLEEVE-SEAL SYSTEMS.
EACH UPON LOSS OF NORMAL POWER OR 50% OF PART 2 - PRODUCTS
RATED LUEMN OUTPOUT OF AN LED TYPE LUMINAIRE.. A. FIXED CIRCUIT-BREAKER WITH FULL-FUNCTION, 1. SEALING ELEMENTS: EPDM RUBBER INTERLOCKING
CONNECT UNSWITCHED CIRCUIT TO ELECTRONIC TRIP UNITS WITH TRIP INDICATORS, AND LINKS SHAPED TO FIT SURFACE OF PIPE. INCLUDE 1.1 CONDUCTORS AND CABLES
BATTERY-INVERTER UNIT AND SWITCHED CIRCUIT TO FIELD-ADJUSTABLE SETTINGS FOR ALL BREAKERS 225 TYPE AND NUMBER REQUIRED FOR PIPE MATERIAL
FIXTURE BALLAST. AMPERE AND HIGHER. A. COPPER CONDUCTORS: COMPLY WITH
AND SIZE OF PIPE.
2. OPERATION: RELAY AUTOMATICALLY TURNS LAMP ON B. MOLDED-CASE CIRCUIT BREAKER RATED LESS THAN 225 C. SLEEVE-SEAL FITTINGS.
WHEN POWER-SUPPLY CIRCUIT VOLTAGE DROPS TO AMPERE. B. CONDUCTOR INSULATION: COMPLY WITH
80 PERCENT OF NOMINAL VOLTAGE OR BELOW. LAMP 1. MANUFACTURED PLASTIC, SLEEVE-TYPE,
AUTOMATICALLY DISCONNECTS FROM BATTERY 1. THERMAL-MAGNETIC CIRCUIT BREAKERS: INVERSE WATERSTOP ASSEMBLY MADE FOR EMBEDDING IN
WHEN VOLTAGE APPROACHES DEEP-DISCHARGE TIME-CURRENT ELEMENT FOR LOW-LEVEL CONCRETE SLAB OR WALL. UNIT SHALL HAVE 1.2 GROUNDING AND BONDING
LEVEL. WHEN NORMAL VOLTAGE IS RESTORED, OVERLOADS, AND INSTANTANEOUS MAGNETIC TRIP PLASTIC OR RUBBER WATERSTOP COLLAR WITH
ELEMENT FOR SHORT CIRCUITS. A. GROUND BUS BAR.
RELAY DISCONNECTS LAMPS FROM BATTERY, AND CENTER OPENING TO MATCH PIPING OD.
BATTERY IS AUTOMATICALLY RECHARGED AND 1. PREDRILLED RECTANGULAR BARS OF ANNEALED
FLOATED ON CHARGER 1.12 WIRING DEVICES 1.6 VIBRATION AND SEISMIC CONTROLS COPPER, 1/4 BY 4 INCHES IN CROSS SECTION, WITH
A. STRAIGHT-BLADE RECEPTACLES. 9/32-INCH HOLES SPACED 1-1/8 INCHES APART.
A. VIBRATION ISOLATORS. STAND-OFF INSULATORS FOR MOUNTING SHALL
1.16 LIGHTING POLES AND STANDARDS
1. 1. RESILIENT MATERIAL: OIL- AND WATER-RESISTANT
AS NOTED
02/24/16
15385
NP
NP
A. DELEGATED DESIGN: ENGAGE A QUALIFIED
NEOPRENE PAD
PROFESSIONAL ENGINEER, TO DESIGN POLE
FOUNDATION AND POLE POWER SYSTEM. 2. SPRING ISOLATORS: FREESTANDING, LATERALLY B. GROUNDING ELECTRODES.
B. ISOLATED-GROUND, DUPLEX CONVENIENCE STABLE, OPEN-SPRING ISOLATORS.
B. SEISMIC PERFORMANCE: FOUNDATION AND POLE SHALL RECEPTACLES FOR SALES AREASAND FOR INFORMATION 1. CHEMICAL-ENHANCED GROUNDING ELECTRODES:
Checked By:
WITHSTAND THE EFFECTS OF EARTHQUAKE MOTIONS TECHNOLOGY LOADS. B. SEISMIC-RESTRAINT DEVICES COPPER TUBE, STRAIGHT OR L-SHAPED, CHARGED
WITH NON-HAZARDOUS ELECTROLYTIC CHEMICAL
Drawn By:
1. STRAIGHT BLADE; EQUIPMENT GROUNDING 1. GENERAL REQUIREMENTS FOR RESTRAINT SALTS.
1. THE TERM "WITHSTAND" MEANS "THE SYSTEM WILL CONTACTS SHALL BE CONNECTED ONLY TO THE COMPONENTS: RATED STRENGTHS, FEATURES, AND
Scale:
REMAIN IN PLACE WITHOUT SEPARATION OF ANY GREEN GROUNDING SCREW TERMINAL OF THE APPLICATION REQUIREMENTS SHALL BE AS DEFINED
Job#:
Date:
1.3 HANGERS AND SUPPORTS
PARTS WHEN SUBJECTED TO THE SEISMIC FORCES DEVICE AND WITH INHERENT ELECTRICAL ISOLATION IN REPORTS BY AN AGENCY ACCEPTABLE TO
FROM MOUNTING STRAP. ISOLATION SHALL BE AUTHORITIES HAVING JURISDICTION. A. SUPPORT, ANCHORAGE, AND ATTACHMENT
OPERATIONAL AFTER THE SEISMIC EVENT." INTEGRAL TO RECEPTACLE CONSTRUCTION AND NOT COMPONENTS.
2. COMPONENT IMPORTANCE FACTOR: 1.5. DEPENDENT ON REMOVABLE PARTS. 1.7 IDENTIFICATION MATERIALS 1. STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH
C. GFCI RECEPTACLES. A. POWER RACEWAY IDENTIFICATION MATERIALS. MFMA-4, FACTORY-FABRICATED COMPONENTS FOR
C. STRUCTURAL CHARACTERISTICS: COMPLY WITH AASHTO
FIELD ASSEMBLY.
LTS-6-M. 1. STRAIGHT BLADE, NON-FEED-THROUGH TYPE. 1.
LETTERS FOR LEGEND AND FOR MINIMUM LENGTH OF B. RACEWAY AND CABLE SUPPORTS.
D. DEAD LOAD: WEIGHT OF LUMINAIRE AND ITS HORIZONTAL 2.
AND VERTICAL SUPPORTS, LOWERING DEVICES, AND COLOR FIELD FOR EACH RACEWAY SIZE. 1.
SUPPORTING STRUCTURE, APPLIED ACCORDING TO B. WARNING LABELS AND SIGNS.
AASHTO LTS-6-M. 3. INCLUDE INDICATOR LIGHT THAT SHOWS WHEN THE C. STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND
GFCI HAS MALFUNCTIONED AND NO LONGER 1. RESTRAINTS.
E. LIVE LOAD: SINGLE LOAD OF 500 LBF DISTRIBUTED PROVIDES PROPER GFCI PROTECTION.
ACCORDING TO AASHTO LTS-6-M. 2. BAKED-ENAMEL WARNING SIGNS. PREPRINTED 1.
C. TWIST-LOCKING RECEPTACLES. ALUMINUM SIGNS, PUNCHED OR DRILLED FOR BLACK AND GALVANIZED.
F. WIND LOAD: PRESSURE OF WIND ON POLE AND FASTENERS, WITH COLORS, LEGEND, AND SIZE
LUMINAIRE, CALCULATED AND APPLIED ACCORDING TO 1. D. MECHANICAL-EXPANSION ANCHORS.
REQUIRED FOR APPLICATION.
AASHTO LTS-6-M. 1. INSERT-WEDGE-TYPE, ZINC-COATED STEEL, FOR USE
C. EQUIPMENT IDENTIFICATION LABELS. IN HARDENED PORTLAND CEMENT CONCRETE WITH
1. BASIC WIND SPEED FOR CALCULATING WIND LOAD
FOR POLES EXCEEDING 50 FEET IN HEIGHT IS 100 D. WALL PLATES. 1. SCREW-ON, ENGRAVED, LAMINATED ACRYLIC OR TENSION, SHEAR, AND PULLOUT CAPACITIES
MPH. MELAMINE LABEL: ADHESIVE BACKED, WITH WHITE APPROPRIATE FOR SUPPORTED LOADS AND BUILDING
1. PLATE-SECURING SCREWS: METAL WITH HEAD MATERIALS IN WHICH USED.
LETTERS ON A DARK-GRAY BACKGROUND. MINIMUM
a. WIND IMPORTANCE FACTOR: 1.0. COLOR TO MATCH PLATE FINISH.
LETTER HEIGHT SHALL BE 3/8 INCH
b. MINIMUM DESIGN LIFE: 50 YEARS. 2. MATERIAL FOR FINISHED SPACES: 0.035-INCH-THICK, 1.4 RACEWAYS AND BOXES
1.8 LIGHTING CONTROL DEVICES A. METAL CONDUITS, TUBING, AND FITTINGS.
c. VELOCITY CONVERSION FACTOR: 1.0. STAINLESS STEEL.
A. INDOOR PHOTOELECTRIC SWITCHES. 1. METAL CONDUITS, TUBING, AND FITTINGS SHALL BE
G. STEEL POLESCARTRIDGE. 3.
STAINLESS STEEL. 1. OPERATION: UNLESS OTHERWISE INDICATED, TURN
1. LIGHTS (AND OR EXHAUST FAN) ON WHEN COVERED QUALIFIED TESTING AGENCY, AND MARKED FOR
STEEL WITH A MINIMUM YIELD OF 46,000 PSIG; 4. AREA IS OCCUPIED AND OFF WHEN UNOCCUPIED; INTENDED LOCATION AND APPLICATION.
ONE-PIECE CONSTRUCTION UP TO 40 FEET IN HEIGHT STAINLESS STEEL WITH SPRING-LOADED LIFT COVER, WITH A TIME DELAY FOR TURNING LIGHTS OFF,
WITH ACCESS HANDHOLE IN POLE WALL. SHEET:
AND LISTED AND LABELED FOR USE IN WET AND DAMP ADJUSTABLE OVER A MINIMUM RANGE OF 1 TO 15
2. SHAPE: ROUND, TAPERED
MOUNTING PROVISIONS: BUTT FLANGE FOR BOLTED
LOCATIONS.
E. FLOOR SERVICE FITTINGS.
MINUTES.
2. SENSOR OUTPUT: CONTACTS RATED TO OPERATE E3.1
1. TYPE: MODULAR, FLUSH-TYPE, DUAL-SERVICE UNITS
SUITABLE FOR WIRING METHOD USED.
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Description
REQUIREMENT PER CALIFORNIA ENERGY CODE SECTION 130.1(c); EXCEPTION N01.,
'WHERE THE LIGHTING IS SERVING AN AREA THAT IS IN CONTINUOUS, 24 HOURS A
DAY/365 DAYS PER YEAR' .
Date
LUTRON OR NOVITAS.
Rev. #
AS NOTED
02/24/16
15385
NP
NP
Checked By:
Drawn By:
Scale:
Job#:
Date:
SHEET:
E3.2
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E41 - INDOOR-TITLE-24.dwg, Layout1, 4/27/2016 8:09:55 AM, npatena
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Scale: AS NOTED
7-11 #1034883 / 37318
Date: 02/24/16 20908 ROSCOE BLVD
CANOGA PARK, CA 91304
Drawn By: NP
E4.1
Checked By: NP
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E42 - INDOOR-TITLE-24.dwg, Layout1, 4/27/2016 8:10:04 AM, npatena
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Scale: AS NOTED
7-11 #1034883 / 37318
Date: 02/24/16 20908 ROSCOE BLVD
CANOGA PARK, CA 91304
Drawn By: NP
E4.2
Checked By: NP
I:\projects\15385\Design\300 Permit & Construction Documents\Electrical\15385 - E43 - LIGHT_FIXTURE.dwg, Layout1, 4/27/2016 8:10:12 AM, npatena
DocuSign Envelope ID: 2EB784E8-7630-4D5F-8FC0-F10979006C94
Scale: AS NOTED
7-11 #1034883 / 37318
Date: 02/24/16 20908 ROSCOE BLVD
CANOGA PARK, CA 91304
Drawn By: NP
E4.3
Checked By: NP