Timer Omron H3CA-A
Timer Omron H3CA-A
Timer Omron H3CA-A
Ordering Information
■ TIMERS
Add the supply voltage to the part number when you order ON-delay only timers H3CA-8 and H3CA-8H. For example,
H3CA-8H-AC/100/110/120.
■ ACCESSORIES
ACCESSORIES, continued
Note: *Operation mode selector not included with ON-delay only models.
Specifications
Part number H3CA-A H3CA-FA H3CA-8H H3CA-8
Supply AC 24 to 240 V, 50/60 Hz 24 V, 100/110/120 V, 200/220/240 V; 50/60 Hz
voltage DC 12 to 240 V 12 V, 24 V, 48 V, 110 V, (permissible ripple
factor: 20% max. using single-phase, full-
wave rectified power sources)
Operating voltage 90 to 110% of rated voltage
Power AC 4 VA 10 VA
consumption DC 2W 2W
Timing 8 field-selectable modes: ON-delay, Repeat ON-delay only
functions cycle, Signal Interval/OFF-delay, Signal ON-/
OFF-delay, Signal OFF-delay (I and II),
Interval and Cycle
Start, reset, gate inputs No voltage No voltage – –
Control Type Time limit SPDT SPDT DPDT
output Instantaneous – SPDT –
Max. load 3 A, 250 VAC (p.f. = 1)
Min. load 10 mA, 5 VDC
Repeat accuracy ±0.3%, ±0.05 sec (includes variation due to voltage and temperature changes)
Setting error ±0.5%, ±0.05 sec
Resetting system Power-OFF, external and self-reset Power-OFF
Resetting time 0.5 sec max. 0.1 sec max.
Indicators Time Remaining (LCD bar graph), Output Status (LCD message)
Materials Plastic case
Mounting Panel, track, surface
Connections 11-pin round socket Terminal screws 8-pin round socket
Specification table continued on the next page.
2
H3CA H3CA
SPECIFICATIONS, continued
Part number H3CA-A H3CA-FA H3CA-8H H3CA-8
Weight 110 g (3.9 oz) 190 g (6.7 oz) 110 g (3.9 oz)
Approvals UL/CSA/SEV
Operating ambient temperature -10° to 55°C (14° to 131°F)
Humidity 35 to 85% RH
Vibration Mechanical durability 10 to 55 Hz; 0.75 mm (0.03 in) double amplitude
Malfunction durability 10 to 55 Hz; 0.5 mm (0.02 in) double amplitude
Shock Mechanical durability 20 G
Malfunction durability 10 G
Variation due to voltage change See "Repeat Accuracy"
Variation due to temperature change See "Repeat Accuracy"
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength 2,000 VAC, 50/60 Hz for 1 minute between current-carrying and non-current-carrying parts
and between contact and control circuit
1,000 VAC, 50/60 Hz for 1 minute between non-continuous contacts
Service life Mechanical 10 million operations minimum (under no load, at 1,800 operations/hour)
Electrical 100,000 operations minimum at maximum ratings
Engineering Data
■ ELECTRICAL SERVICE LIFE
10,000
7,000
Electrical operations (thousands)
5,000
3,000
1,000
700
24 VDC L/R = 7 ms
500
24 VDC p.f.= 1
300
100
70 250 VAC p.f. = 0.4 250 VAC p.f.= 1
50
0 1 2 3
Load current
3
H3CA H3CA
Timing Charts
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
■ H3CA-A, H3CA-FA
Mode A ON-Delay
Reset 3-7
(X-B1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
(AC/DC)
Power
t = set time Rt = reset time t-a = less than set time
Signal Start
Time-out
indicator
Remaining
time indicator
(AC/DC) t = set time t-a = less than set time
Power
Signal Start
Control 9 - 11
Reset signal output NO (15-18)
Time-out
indicator
Remaining
time indicator
(AC/DC) t = set time t-a = less than set time
Power
4
H3CA H3CA
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
The start terminals are connected. Timing starts when power is Power 2 - 10
applied. The output relay will be OFF for the set time and then ON (A1-A2)
for the set time. This cycle will be repeated until a reset input is
applied or power is disconnected. Start 3-6
(X-C1)
Reset 3-7
(X-B1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
(AC/DC) time indicator
Power
t = set time t-a = less than set time
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
(AC/DC)
Power
t = set time t-a = less than set time
5
H3CA H3CA
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Mode E Interval
Signal Start
Control 9 - 11
Reset signal output NO (15-18)
Time-out
indicator
Remaining
time indicator
t = set time t-a = less than set time
(AC/DC)
Power
Reset 3-7
(X-B1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
(AC/DC) time indicator
Power
t = set time t-a = less than set time
The start terminals are connected. Timing starts when power is Power 2 - 10
applied. The output relay will be OFF for the set time and then (A1-A2)
ON for the set time. The timer is reset when power is discon-
nected or a reset input is applied. Start 3-6
(X-C1)
Reset 3-7
(X-B1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
(AC/DC)
Power t = set time t-a = less than set time
6
H3CA H3CA
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Signal Start
Control 9 - 11
Reset signal output NO (15-18)
Time-out
indicator
Remaining
time indicator
(AC/DC) t = set time t-a = less than set time
Power
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
t = set time t-a = less than set time
(AC/DC)
Power
Reset 3-7
(X-B1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
(AC/DC) Remaining
Power time indicator
7
H3CA H3CA
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
■ H3CA-8
Power (7 - 2)
Time-limit
contact NC (1 - 4)
Time-limit
Timed Timed contact NO (1 - 3)
contact contact
Time-limit
contact NC (8 - 5)
Time-limit
Power
contact NO (8 - 6)
circuit
Remaining
time indicator
Time-out
indicator
t = set time Rt = reset time
■ H3CA-8H
Power (7 - 2)
Time-limit
contact NC (8 - 5)
Instantaneous Timed Time-limit
contact contact contact NO (8 - 6)
Instantaneous
contact NC (1 - 4)
Power Instantaneous
circuit contact NO (1 - 3)
Remaining
time indicator
Time-out
indicator
t = set time Rt = reset time
Dimensions
Unit: mm (inch)
Panel cutout
■ TIMERS 45 (1.97)
(1.77) 50
H3CA-A 89 (3.50)
11 78
0.7 45
5 6 63.7 13.6
(1.77)
50
(1.97)
44.8
48 (1.76)
(1.89)
H3CA-FA
5 Mounting holes
8.5 8.5 7.5
7.5
60
(2.36)
75 58 35
(2.95) 35
(1.38)
L
8
H3CA H3CA
H3CA-8, H3CA-8H
89 (3.50) Panel cutout
11 78 50
0.7
56 63.7 13.6 45 (1.97)
(1.77)
45
44.8 (1.77)
48
(1.89) (1.76)
50
(1.97)
48 75.4
(1.89) (2.97)
■ ACCESSORIES
P2CF-08-E Finger Safe Terminal Type
Conforming to VDE0106/P100
Eight
M3.5 x 7.5 sems 5 4.5
7.8
(0.18)
(0.31)
40±0.2 19
50 max. 20.3
(1.97)
21.5 max
40±0.2 30
50 max.
(1.97) 31.2 max
9
H3CA H3CA
Y92A-48G Finger Safe Terminal for P3G(A)
Conforming to VDE0106/P100
Twelve, 6.4 dia. holes
47.7
34 48 x 48
x 4.47
16.5
27.6
47.4
Adapter installs behind the panel. It is ideal for side by side installation. Use P3GA-11 or P3G-08 sockets.
Panel cutout
0.5 R
15 Mounting panel 45
max.
Y92F-30 Socket (1.77)
45
58
(1.77)
(2.28)
Note: Recommended
panel thickness
is 1 to 3.2 mm.
48
(1.89) 91.4
11 (3.59)
Charcoal gray panel adapter installs through panel front. Timer fits bezel, rear of timer clips to adapter.
Use P3GA-11 or P3G-08 sockets. Panel cutout
Mounting panel
Two 4.5 diameter mounting
holes for panel adapter
Socket 0.5 R
max.
88 45
(3.46) ±0.15
10
H3CA H3CA
Charcoal gray panel adapter installs through panel front. Timer face fits bezel, rear of timer clips to adapter. Use P3GA-11 or P3G-08.
55
68 (2.16)
58 45
(2.28) (2.68)
43 91.4
11 (3.59)
50
Connections
Part Input terminal numbers (no-voltage only) Power supply terminal numbers Output terminal numbers
number Gate Start Reset Check COM AC (common), DC- AC (hot), DC+ Type COM NC NO
H3CA-A 5 6 7 4 3 2 10 Timed contact 11 8 9
H3CA-FA D1 C1 B1 E1 X A2 A1 Timed contact 15 16 18
H3CA-8H – – – – – 2 7 Instantaneous 1 4 3
Timed contact 8 5 6
H3CA-8 – – – – – 2 7 Timed contact 1 4 3
Timed contact 8 5 6
11
H3CA H3CA
Resistance 1 KΩ max.
Residual voltage 1 V max. when the contact makes
Contact material Gold-plated contacts recommended
H3CA-A
• Start input contact between terminals 3 and 6.
• Reset input contact between terminals 3 and 7.
• Gate input contact between terminals 3 and 5.
H3CA-FA
• Check input contact between terminals 3 and 4.
H3CA-FA
• Start input contact between terminals X and C1. • Reset • Start • Gate
• • • • •
Check
input
Power
+ –
Control 9 - 11
output NO (15-18)
12
H3CA H3CA
■ CHECK INPUT
t-a
Power 2 - 10
ON-Delay Operation (A1-A2)
Start 3-6
When a no-voltage input signal is applied to the timer during (X-C1)
the lapse of a set time, the remaining set time will become 0 Check 3-4
and the timer will enter the next control state. Also, while the (X-E1)
Check Signal is applied, the elapsed time measurement of the Reset 3-7
set time is not performed. The Check input is especially useful (X-B1)
where ON-delay override may be desirable. Control 9 - 11
output NO (15-18)
t - a = less than set time
Installation
■ PROPER INPUT CONNECTIONS (H3CA-A, H3CA-FA)
↑
The neutral or common of the power supply is connected 2 (A2)
to terminal 2 (A2) of the timer. Terminal 10 (A1) should be •
connected to the "hot" or positive of the power supply. Do Input contact H3CA-A 8 ......•
not apply voltage to Check, Gate, Start and Reset inputs. Power (H3CA-FA) Load
supply
•• 9 •
These are no-voltage type inputs. AC or DC 4, 5, 6, 7
11
C, G, S, R
10 (A1)
■ PROPER OUTPUT CONNECTIONS
↓
Design your control circuit using the output relay contacts to
switch the load. Never switch a load with the contact that
is being used as an input signal. The timer's circuitry may
be damaged.
■ PARALLEL CONNECTIONS
Parallel connection of two or more Omron Timers is possible Reset
as shown by the diagram to the right.
5 6 7
Start
This will allow the simultaneous start or restart of multiple 4 8
H3CA-A
timers using a single switch for the Start Input and a single Com 3 9
Timer
switch for the Reset Input. 2
1 11
10
13
H3CA H3CA
Operation
■ SELECTING TIME RANGE
Use the rightmost pushwheel switch to select the Time unit Timing range
time range. Use the three center pushwheel 0.1 s 0.1 to 99.9 seconds
switches to select the time setting between 000 s 1 to 999 seconds
and 999. For ranges with 0.1 time units, the 0.1 m 0.1 to 99.9 minutes
decimal point is assumed to be between middle Operation Time unit m 1 to 999 minutes
and right digits. mode selector
selector* 0.1 h 0.1 to 99.9 hours
h 1 to 999 hours
10 h 10 to 9990 hours
Time setting switches
■ CAUTIONS
Do not change the time unit or time range while the timer is
in operation. Otherwise, the timer may malfunction or be
damaged. Be sure to turn off the power supply to the timer
before changing any of the selections.
Mounting
■ PANEL MOUNTING
Using Y92F-30 Adapter
Insert the timer through the panel cutout. Push the
➚
Y92F-30 adapter from the rear of the timer as far forward
toward the panel as possible. Wire the P3G❑-❑❑ socket,
then push it onto the rear of the timer. Then, tighten the two
retaining screws. To release the adapter, lift the tab at the
rear of the adapter.
14
H3CA H3CA
Install the H3CA timer, face first, into the back Mounting tabs
Panel
side of the Y92F-70 or Y92F-71 adapter so the
bezel fits snugly. Be sure the retaining clips at the
back of the adapter fit into the slots on either side
of the timer. Compress the top and bottom tabs
of the adapter then push the adapter through the Retaining clips
front side of the panel cutout. Be sure the tabs for timer
extend after installation for a
secure fit.
■ TRACK MOUNTING
H3CA-FA with Built-In Track Adapter
Mounting Removal
First hook part "A" on the rear of the Pull the latch "C" with a flat-blade
timer onto an edge of the track. Then, screwdriver and remove the timer
press the timer in direction "B" until the from the mounting track.
latch on the bottom rear of the timer
locks securely.
P2CF-❑❑ Socket
Mounting Removal
The P2CF-❑❑ socket has two hooks Pull the latch on the socket with a flat-blade
that secure the timer to the socket. screwdriver and remove the timer and socket
Be sure to allow at least 20 mm as one unit.
(0.79 in) clearance above and below
the socket to gain access and to
release the hooks for servicing and
maintenance. Insert timer into the
socket. Latch hooks. Then clip rear
of the socket to the track. Push the
bottom onto the track until the latch
hooks securely.
NOTE: DIMENSIONS ARE SHOWN IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
15