ACI 318-19 Code Implementation - 112222
ACI 318-19 Code Implementation - 112222
ADAPT-Builder
This Technical Note details the requirements of ACI318-19 for design of concrete floor systems, with
emphasis on post-tensioning and their implementation in the ADAPT Builder Platform programs.
The implementation follows the ACI Code‘s procedure of calculating a “Demand,” referred to as “design
value” for each design section, and a “Resistance,” for the same section, referred to as “design
capacity.” “Design value” and “design capacity” are generic terms that apply to displacements as well as
actions. For each loading condition, or instance defined in ACI Code, the design is achieved by making
the “resistance” exceed the associated demand “Design Value”. Where necessary, reinforcement is
added to meet this condition.
In each instance, the design consists of one or more of the following checks:
Bending of section
Punching shear (two-way shear)
Beam shear (one-way shear)
Minimum reinforcement
In the following, the values in square brackets “[ ]” are defaults of the program. They can be changed by
the user.
REFERENCES
1. ACI-318-19
1
Copyright ADAPT Corporation 2019
Technical Note
601
MATERIAL AND MATERIAL FACTORS
Concrete2
Cylinder strength at 28 days, as specified by the user
f’c = characteristic compressive cylinder strength at 28 days [psi, MPa]
Parabolic stress/strain curve with the maximum stress at f’ c and maximum strain at 0.003. Strain
at limit of proportionality is not defined.
Modulus of elasticity of concrete is automatically calculated and displayed by the program using
f’c, wc, and the following relationship3 of the code. User is given the option to override the code
value and specify a user defined substitute.
𝐸 =𝑤 .
33 𝑓′ US
𝐸 =𝑤 .
0.043 𝑓′ SI
Where,
Ec = modulus of elasticity at 28 days [psi, MPa]
f’c = characteristic cylinder strength at 28 days [psi; MPa]
wc = density of concrete [150 lb/ft3; 2400 kg/m3]
Nonprestressed Steel4
Bilinear stress/strain diagram with the horizontal branch at f y
Modulus of elasticity (Es) is user defined [29000 ksi; 200,000 MPa]
No limit has been set for the ultimate strain of the mild steel in analysis and design
2
ACI318-19, Section 22.2.2.3
3
ACI318-19, Section 19.2.2.1
4
ACI318-19, Section 20.2.2.1 and 20.2.2.2
2
Technical Note
601
Prestressing Steel
A bilinear stress-strain curve is assumed
Modulus of elasticity is user defined [28000 ksi; 190,000 MPa
LOADING
Selfweight determined based on geometry and unit weight of concrete, and other loads are user
defined.
SERVICEABILITY
Load combinations
Total load combinations:
DL+1.0 LL+1.0 PT
The above combinations are the default settings of the program. User has the option to change them or
create additional load combinations for service evaluation.
Stress checks5
Code stipulated stress limitations are used as the default allowables. However, the user can edit
the default values.
5
ACI318-19, Section 24.5
3
Technical Note
601
“Total load” condition:
o Concrete
Maximum compressive stress 0.60 f’c. If calculated stress at any location
exceeds the allowable, the program identifies the location graphically on the
screen and notes it in its tabular reports.
The maximum allowable hypothetical tensile stress for one-way slabs and
beams depends on the selection of design in one of the three classes of
uncracked (U), transition (T) or cracked (C):
The program does not explicitly handle Class C. For one-way slabs and beams
designed for Class C, additional serviceability requirements are required per
Table R24.5.2.1 and are not defaulted to in the software when allowable stress
settings are based on Class C. The user should modify stiffness properties and
ensure proper cracked deflection combinations are considered to meet the
necessary requirements.
For two-way slabs design only Class U (uncracked) is permitted:
o Nonprestressed Reinforcement
None specified - no check made
o Prestressing steel
None specified - no check made
The program does not explicitly handle Class C. For one-way slabs and beams
4
Technical Note
601
designed for Class C, additional serviceability requirements are required per
Table R24.5.2.1 and are not defaulted to in the software when allowable stress
settings are based on Class C. The user should modify stiffness properties and
ensure proper cracked deflection combinations are considered to meet the
necessary requirements.
ADAPT uses 6 𝑓 [𝑈𝑆], 0.5 𝑓 [𝑆𝐼] as its default for two-way systems
ADAPT uses 7.5 𝑓 [𝑈𝑆], 0.62 𝑓 [𝑆𝐼] as its default for one-way systems
o Nonprestressed Reinforcement
None specified – no check made
o Prestressing steel
None specified - no check made
STRENGTH
Load combinations6
The following are the load combinations for gravity design of floor systems
D +1.0 Hyp
1.2 D + 1.6 L + 0.5 (Lr or S or R) + 1.0 Hyp
1.2 D + 1.6 (Lr or S or R) + 1.0 L + 1.0 Hyp
The program designates reserved (default) load cases Dead and Live load. Therefore, loads
classified as Lr, S and R should be input as additional load cases by the user.
It uses code specified formulas for the determination of stress in prestressing steel at strength
limit state (fse). The rigorous design is based on strain compatibility, which is applied to bonded
prestessed systems in ADAPT when the ACI code is used
6
ACI318-19, Section 5.3.1
7
ACI318-19, Section 22.2.1
5
Technical Note
601
Material and Stresses
The stress-strain relationship of the materials used is shown in Fig. 1 for the general case.
Figure 1
At ultimate condition the stresses are idealized using the following assumptions and
relationships:
Concrete
where:
𝛽 = 0.85 − 0.05 𝑓 − 4000 /1000 ≥ 0.65 US
𝛽 = 0.85 − 0.05 𝑓 − 28 /7 ≥ 0.65 SI
6
Technical Note
601
Figure 2
Non-Prestressed Reinforcement
The stress-strain relationship for rebar is idealized as shown in Figure 1b. If the strain in
concrete at the location of the rebar is less than the elastic limit of the rebar material, the
rebar will not develop its yield stress. In this case, the calculation uses the stress obtained
from the stress-strain diagram of the rebar material.
Prestressing
The stress developed in the prestressing steel at nominal strength is given by f ps. If the
effective stress in prestressing (fse) (after allowance for short- and long-term losses) is not
less than 0.5*fpu, the ACI simplified relationships may be used to estimate fps.
For grouted tendons, the code uses a parameter λp, for the calculation of stress in
prestressing steel at strength limit state. λp is a constant depending on the material of
prestressing tendon.
Geometry
The general geometry of the section considered is shown in Fig. 3 for a T-section. Inverted L or
rectangular sections are treated as special conditions of a T-section in which one, or both of
the overhangs are reduced to zero. I-sections at ultimate strength are also treated as T-
sections since the contribution of concrete in tension zone is disregarded.
7
Technical Note
601
Figure 3
𝑀 < 𝛷𝑀
𝑐 = 0.375𝑑
𝑎 =𝛽 𝑐
In a somewhat similar manner, the Canadian code (CSA-A23.3), the British code
(BS 8110), and the European code (EC2) implement the ductility requirement
8
Technical Note
601
by limiting the maximum depth of the neutral axis (c) to a fraction of d or h.
Based on the threshold specified for the depth of the neutral axis (c), prior
to triggering a reduction in the strength reduction factor (ɸ), six design
conditions are identified. These are illustrated in Fig. 5.
Case 1 is the condition in which the available prestressing is in excess of that required to resist the
design moment, Mu, with adequate ductility (c < 0.375dt). Clearly, the section is satisfactory as is. No
additional rebar is required.
In Case 2, the available prestressing is not adequate to resist the design moment M u. Rebar As is
required to supplement the prestressing Aps. The combined areas of Aps and As result in (a < amax). The
larger circle shown in the figure around the rebar represents the maximum area of rebar (A s,max) that
would bring the section to its ductility threshold of (a = amax ).
By increasing the applied moment of Case 2, a condition is reached for which the prestressing and the
maximum rebar derived from the ductility relationships are no longer adequate to develop the
required design capacity ɸMn. In this case, the balance of design capacity must be generated by a force
couple resulting from addition of tension and compression rebar. Generally, the area
of the added compression steel (A’s) will be equal to the added tension steel in excess of As,max. The
exception is when the bars are positioned such that one or both of them would not yield.
In Case 4, the amount of available prestressing is excessive, in that (c > 0.375 d t ). As a result the ductility
threshold is exceeded. The section can still be considered a satisfactory design, provided that the design
moment (Mu) is less than the design capacity of the compression zone of the section. The design
capacity of the compression zone is determined with the depth of the neutral axis assumed at c max. The
relationships are (Figs. 6 and 7):
𝑎 𝑎
𝛷 𝑀 = 𝛷 𝐶 (𝑑 − 2) + 𝐶 (𝑑 − 𝑑 ) + 𝐶 (𝑑 − 2)
For a T-section where “a” falls in the stem use the following formula:
9
Technical Note
601
𝑎 ℎ
𝛷 𝑀 = 𝛷 𝐶 (𝑑 − 2) + 𝐶 (𝑑 − 𝑑 ) + 𝐶 (𝑑 − 2 )
In the above relationships, Cs refers to the component of the force from the compression steel, if
available.
As in Case 4, the design capacity of the compression zone, ɸMn, is not adequate to resist the design
moment, Mu. That is to say Mu > ɸMn. In this case, rebar must be added to the compression zone.
The design capacity of the section is based on the force developed in the compression zone with a max.
The expressions in the section “Relationships” below apply. The following gives the compression force in
its expanded form.
𝐶 = 𝐴′ ∗ 𝑓 + 0.85(0.5𝑏𝛽 𝑑 − 𝐴 )𝑓′
Case 6 is one in which the prestressing alone is in excess of that required to satisfy a max criterion, and the
maximum compression rebar permissible. An acceptable design can be achieved by resisting the excess
moment through addition of rebar for equal tension and compression forces such as to maintain the
expressions in the section “Relationships” below.
10
Technical Note
601
Figure 4
o Relationships
For given geometry, material properties, and amount of prestressing, the
design is achieved by obtaining the minimum amount of rebar that develops
the required design capacity, ɸMn.
The forces at the strength limit state are defined in Figs. 6 and 7.
Tension equals compression, T = C, where:
𝑇 =𝑇 +𝑇
𝑇 =𝐴 𝑓
𝑇 =𝐴 𝑓
𝐶 =𝐶 +𝐶 +𝐶
𝐶 = 0.85(𝑏 ∗ 𝑎 − 𝐴 )𝑓′
𝐶 =𝐴 𝑓
𝐶 = 0.85 𝑏 − 𝑏 ∗ 𝑎 ∗ 𝑓′
𝑀 < 𝛷𝑀
𝑐 < 0.375𝑑
11
Technical Note
601
to the compression zone is represented by an equivalent compressive force
located at the height of the centroid of overhang’s compression block. The
force developed by the overhang is:
𝐶𝑓 = 0.85 𝑏𝑓 − 𝑏 ∗ 𝑎 ∗ 𝑓′𝑐
𝑀 ≥ 1.2𝑀
Where,
Mcr = cracking moment = S*(fp + ft)
S = section modulus
fp = stress due to post-tensioning
ft = tensile strength of the concrete
Figure 5
8
ACI318-19, Section 7.6.2.1
12
Technical Note
601
Figure 6
Figure 7
One-way Shear9
o The design is based on the following:
𝛷𝑉 ≥ 𝑉
𝑉 =𝑉 +𝑉
where,
Vn = factored shear resistance
Vu = factored shear force due to design loads
Vc = shear resistance attributed to the concrete
Vs = shear resistance provided by shear reinforcement
bw = width of the web [in]
d = effective shear depth [in]
𝑓′ ≤ 100𝑝𝑠𝑖, 8.3 𝑀𝑃𝑎
9
ACI318-19, Section 22.5
10
ACI318-19, Section 22.5.5
13
Technical Note
601
𝑉𝑐 = 2λ 𝑓′ + 𝑏 𝑑 US
𝑉𝑐 = 0.17λ 𝑓′ + 𝑏 𝑑 SI
𝑉𝑐 = 8λ λ(𝜌 ) /
𝑓′ + 𝑏 𝑑 US
𝑉𝑐 = 0.66λ λ(𝜌 ) /
𝑓′ + 𝑏 𝑑 SI
Where,
𝑉𝑐,max = 5λ 𝑓′ 𝑏 𝑑
𝑁
≤ 0.05 𝑓′𝑐
6𝐴
= a modification factor for concrete strength
1 for normal weight concrete
0.85 for sand light-weight concrete
0.75 for all-light-weight concrete
𝜆 = ≤1
Prestressed members
𝑉𝑑
𝑉 = 0.6𝜆 𝑓′ + 700 𝑏 𝑑
𝑀
2𝜆 𝑓′ 𝑏 𝑑 ≤ 𝑉 ≤ 5𝜆 𝑓′ 𝑏 𝑑
Where ≤1
14
Technical Note
601
o Shear reinforcement, Av11
If 𝑉 − 𝛷𝑉 > 𝑉 , 12
shear is excessive. Revise the section or
increase the concrete strength
Where 𝑉 , =
𝑉, = 8 𝑓′ 𝑏 𝑑 US
𝑉, = 0.66 𝑓′ 𝑏 𝑑 SI
( )
If 𝑉 > 𝛷𝑉 𝐴 14 = ≥𝐴 ,
Nonprestressed members:
𝐴 , = 0.75 𝑓′ ≥ 50 US
𝐴 , = 0.062 𝑓′ ≥ 0.35 SI
Prestressed members:
Where,
s = longitudinal spacing of vertical stirrups [in,mm].
fyt = characteristic strength of the stirrup [psi, MPa]
11
ACI318-19, Section 22.5.8.5
12
ACI318-19, Section 22.5.1.2
13
ACI318-19, Section 9.6.3.4
14
ACI318-19, Section 22.5.8.5.3
15
Technical Note
601
US: Sv,max =
d/2 ≤24in if (𝑉 − 𝛷𝑉 ) < 𝛷4 𝑓′𝑐 𝑏𝑤 𝑑
d/4 ≤12in if 𝛷4 𝑓′ 𝑏 𝑑 < (𝑉 − 𝛷𝑉 ) < 𝛷8 𝑓′ 𝑏 𝑑
SI: Sv,max =
d/2 ≤600 mm if (𝑉 − 𝛷𝑉 ) < 𝛷0.33 𝑓′𝑐 𝑏𝑤 𝑑
d/4 ≤300mm if 𝛷0.33 𝑓′ 𝑏 𝑑 < (𝑉 − 𝛷𝑉 ) < 𝛷0.66 𝑓′ 𝑏 𝑑
Prestressed members:
US: Sv,max =
0.75h ≤24in if (𝑉 − 𝛷𝑉 ) < 𝛷4 𝑓′𝑐 𝑏𝑤 𝑑
0.375h ≤12in if 𝛷4 𝑓′ 𝑏 𝑑 < (𝑉 − 𝛷𝑉 ) < 𝛷8 𝑓′ 𝑏 𝑑
SI: Sv,max =
0.75h ≤600mm if (𝑉 − 𝛷𝑉 ) < 𝛷0.33 𝑓′𝑐 𝑏𝑤 𝑑
0.375h ≤300mm if 𝛷0.33 𝑓′ 𝑏 𝑑 < (𝑉 − 𝛷𝑉 ) < 𝛷0.66 𝑓′ 𝑏 𝑑
Two-way shear
o Categorization of columns
Based on the geometry of the floor slab at the vicinity of a column, each
column is categorized into to one of the following options:
1. Interior column: Each face of the column is at least four times the slab
thickness away from a slab edge
2. Edge column: One side of the column normal to the axis of the moment
is less than four times the slab thickness away from the slab edge
3. Corner column: Two adjacent sides of the column are less than four
times the slab thickness from slab edges parallel to each
4. End column: One side of the column parallel to the axis of the moment
is less than four times the slab thickness from a slab edge
In cases 2, 3 and 4, the column is assumed to be at the edge of the slab,
however, the software shear design contains a user option to extend the
section the modeled free edge of the slab. When this option is not used, the
15
ACI318-19, Section 9.7.6.2.2
16
Technical Note
601
overhang of the slab beyond the face of the column is not included in the
calculations. Hence, the analysis performed is somewhat conservative.
o Stress calculation16
The maximum factored shear stress is calculated for several critical
perimeters around the columns based on the combination of the direct
shear and moment:
𝑉 𝛾𝑀 𝑐
𝑣 = +
𝐴 𝐽
𝑉 𝛾𝑀 𝑐′
𝑣 = +
𝐴 𝐽
Where,
Vu = absolute value of the direct shear and
Mu = absolute value of the unbalanced column moment about the
center
of geometry of the critical section
c and c’ = distances from centroidal axis of critical section to the
perimeter of
the critical section in the direction of the analysis
A = area of concrete of assumed critical section,
γ = ratio of the moment transferred by shear and
Jc = moment of inertia of the critical section about the axis of
moment.
1. Interior column:
𝐴 = 2(𝑏 + 𝑏 )𝑑
16
ACI318-19, Section 8.4.4.2
17
“Concrete Q&A – Checking Punching Shear Strength by the ACI Code,” Concrete International, November 2005, pp 76.
17
Technical Note
601
𝑏
𝑐=
2
𝑏 𝑑 𝑑𝑏 𝑏 𝑏 𝑑
𝐽 = + +
6 6 2
1
𝛾 =1−
2 𝑏
1+
3 𝑏
𝑀 = 𝑎𝑏𝑠(𝑀 , )
𝐴 = (2𝑏 + 𝑏 )𝑑
𝑏
𝑐=
2𝑏 + 𝑏
𝑏 𝑑 𝑑𝑏 𝑏
𝐽 = + + 2𝑏 𝑑 −𝑐 + 𝑏 𝑑𝑐
6 6 2
1
𝛾 =1−
2 𝑏
1+
3 𝑏
𝑐
𝑀 = 𝑎𝑏𝑠 𝑀 , −𝑉 𝑏 −𝑐−
2
3. Corner Column:
𝐴 = (𝑏 + 𝑏 )𝑑
𝑏
𝑐=
2𝑏 + 2𝑏
𝑏 𝑑 𝑑𝑏 𝑏
𝐽 = + +𝑏 𝑑 −𝑐 + 𝑏 𝑑𝑐
12 12 2
1
𝛾 =1−
2 𝑏
1+
3 𝑏
𝑐
𝑀 = 𝑎𝑏𝑠 𝑀 , −𝑉 𝑏 −𝑐−
2
𝐴 = (𝑏 + 2𝑏 )𝑑
𝑏
𝑐=
2
18
Technical Note
601
𝑏 𝑑 𝑑𝑏
𝐽 = + + 2𝑏 𝑑𝑐
12 12
1
𝛾 =1−
2 𝑏
1+
3 𝑏
𝑀 = 𝑎𝑏𝑠 𝑀 ,
o Allowable stress18:
For nonprestressed member and prestressed member where columns are
less than 4hs from a slab edge:
⎧ 4λ λ 𝑓′ ⎫
⎪ ⎪
𝑣 = 𝑚𝑖𝑛 2+ λ λ 𝑓′ US
⎨ ⎬
⎪ 2+ λ λ 𝑓′ ⎪
⎩ ⎭
⎧ 0.33λ𝑠 λ 𝑓′𝑐 ⎫
⎪
⎪ ⎪
⎪
𝑣 = 𝑚𝑖𝑛 0.17 1 + λ𝑠 λ 𝑓′𝑐 SI
⎨ ⎬
⎪
⎪0.083 2 + ⎪
λ𝑠 λ 𝑓′𝑐 ⎪
⎩ ⎭
Where,
β = the ratio of the larger to the smaller side of the critical section
f’c = the strength of the concrete
αs = 40 for interior columns
= 30 for edge and end columns
= 20 for corner columns
bo = the perimeter of the critical section.
2
λ = 𝑑 ≤1
1+
10
For prestressed members where columns are more than 4hs from a slab edge:
𝑣 = 𝛽 λ 𝑓′𝑐 + 0.3𝑓𝑝𝑐 + 𝑉
18
ACI318-19, Section 22.6.5
19
Technical Note
601
Where,
Where,
αs = 40 for interior columns
= 30 for edge and end columns
= 20 for corner columns
b0 = the perimeter of the critical section
fpc = the average value of fpc for the two directions ≤ 500
psi (3.5 MPa) ≥ 125 psi (0.9 MPa)
Vp = the factored vertical component of all prestress forces
crossing the critical section. ADAPT conservatively
assumes it as zero.
𝑓′ ≤ 70 𝑝𝑠𝑖 , 0.5 𝑀𝑃𝑎
o Critical sections19
The closest critical section to check the stresses is d/2 from the face of the
column where ‘d’ is the effective depth of the slab or drop panel/cap.
Subsequent sections checked are located d/2 away from the previous critical
section. The program checks rectilinear critical sections to the location
where no reinforcement is required. At that same critical section, the
program then checks the least critical section (octagonal-shaped) for stress.
If the calculated stress exceeds the code-required limit
𝑣 = 𝛷 2λ 𝑓′ US
𝑐
𝑣 = 𝛷 0.17λ 𝑓′ SI
𝑐
19
ACI318-19, Section 8.4.4 & 22.6.4
20
ACI318-19, Section 22.6.5
20
Technical Note
601
For stirrups21:
𝛷𝑣 , = 𝛷 6 𝑓′ US
= 𝛷 0.5 𝑓′ SI
22
For studs :
𝛷𝑣 , = 𝛷 8 𝑓′ US
= 𝛷 0.66 𝑓′ SI
Where φv is the shear factor and vn,max is the maximum shear stress that can
be carried out by the critical section including the stresses in shear
reinforcement.
Stress check is performed until no shear reinforcement is required. For drop
panels or caps, stresses are checked within the drop panel or cap until the
stress is less than the permissible stress and then checked outside the drop
panel or cap region until the stress is less than the permissible value. In the
case of a drop cap, if the first critical section at 0.5d from face of column
(where ‘d’ is calculated from the depth of the drop cap) is located beyond
the drop cap, the program uses the effective depth calculated for the slab
for all critical sections checked.
Vu shall not exceed23:
𝑣 = 𝛷 2λ 𝑓′ US
𝑣 = 𝛷 0.17λ 𝑓′ SI
at the critical section located d/2 outside the outermost line of shear
reinforcement that surround the column.
o Shear reinforcement
Where needed, shear reinforcement is provided according to the
following24:
( )
𝐴 = ( )
21
ACI318-19, Section 22.6.6.3
22
ACI318-19, Section 22.6.6.3
23
ACI318-19, Section 22.6.6.1
24
ACI318-19, Section 22.6.7 & 22.6.8
21
Technical Note
601
For studs25: 𝐴 ≥ 𝐴 , =
Where26,
𝑣 = 2λ 𝑓′ [𝑈𝑆], 0.17λ 𝑓′ [𝑆𝐼] for stirrups
𝑐 𝑐
𝑣 ≤ 𝛷 2λ 𝑓′ US
𝑐
𝑣 ≤ 𝛷 0.17λ 𝑓′ SI
𝑐
𝐴
𝑁 _ =
𝐴 _
𝑢
𝐷𝑖𝑠𝑡 _ =
𝑁 _
The first layer of stirrups is provided at d/2 from the column face and the successive
layers are at d/2 from the previous layer. The spacing between the adjacent stirrup
legs in the first line of shear reinforcement shall not exceed 2d measured in a
direction parallel to the column face.27
If shear studs are used, the number of shear studs per rail (Nshear_studs) and the
distance between the studs (Distshear_studs) are given by:
𝐴
𝑁 _ =
𝐴 _ 𝑁
25
ACI318-19, Section 22.6.8.3
26
ACI318-19, Section 22.6.6.1
27
ACI318-19, Section 8.7.6.3
22
Technical Note
601
𝑑
𝐷𝑖𝑠𝑡 _ =
2𝑁 _
The spacing between the column face and the first peripheral line of shear
reinforcement shall not exceed d/2. The spacing between adjacent shear
reinforcement elements, measured on the perimeter of the first peripheral line of
shear reinforcement, shall not exceed 2d. The spacing between peripheral lines of
shear reinforcement, measured in a direction perpendicular to any face of the
column, shall be constant28.
The default graphical and tabular output for stirrup or heads stud reinforcement
report number of studs or vertical stirrup legs at a distance from face of column.
Multiple quantities and spacings may be reported (e.g. 10@2”, 5@4”, 10@8”). The
program gives an option for the reinforcement to be reported as uniform. In the
case this option is used, the program calculates the total length for which
reinforcement is required based on the default layout and applies the minimum
spacing to this length. (e.g. 60@2”).
The program gives the option to utilize and limit the code required spacing29
between stud rails and adds enough rails per column side to meet this requirement.
𝑣 ≥ 3.5 𝑓′
(𝑣 − 𝛷 𝑣 )𝑢𝑠
𝐴 =
𝛷 𝑓 sin (𝛼)
INITIAL CONDITION
28
ACI318-19, Section 8.7.6.3
29
ACI318-19, Section 8.7.7.1.2
30
ACI318-19, Section 18.14.5.1
23
Technical Note
601
Load combinations
o ADAPT uses the following default values. User can modify these values.
o 1.0 SW +1.15 PT
Allowable stresses31
o Tension:
At ends of simply supported members: 6 𝑓′ [𝑈𝑆], 0.5 𝑓′ [𝑆𝐼]
All others (program default): 3 𝑓′ [𝑈𝑆], 0.25 𝑓′ [𝑆𝐼]
o Compression: 0.6𝑓′
If the tensile stress exceeds the threshold, reinforcement is added in the tensile zone
Reinforcement
o Reinforcement will be provided for initial condition if tensile stress exceeds allowable stress. Rebar
is provided based on ACI code and will be placed on tension side:
𝑁
𝐴 =
0.5𝑓
Where:
As = Area of reinforcement
Nc = tensile force in the concrete based on the uncracked section
fy = Yield Stress of the steel but not more than 60 ksi
DETAILING
Reinforcement requirement and placing
o Nonprestressed member:
Minimum tension rebar
• Beam32:
𝐴 , = > US
.
.
𝐴 , = > SI
where,
bw = width of the web [in,mm]
fy,max = 80,000 psi
For statically determinate members with flange in tension:
bw = minimum of {2bw, width of the flange} [in,mm]
Minimum rebar requirement will be waived if As provided is at least 1/3 greater than
31
ACI318-19, Section 24.5.3
32
ACI318-19, Section 9.6.1 & 9.6.2
24
Technical Note
601
that required by analysis.
Slab33:
𝐴 , = 0.0018𝐴
𝑠 = min (5ℎ, 18𝑖𝑛) US
𝑠 = min (5ℎ, 450𝑚𝑚) SI
o Prestressed member:
One way system with unbonded tendon:
𝐴 , = 0.004𝐴
Where,
Act = Area of the part of cross-section between the flexural tension face and the center
of gravity of cross-section
𝑁
𝐴 , =
0.5𝑓
𝐴 , = 0.00075𝐴
• Where Acf = larger gross cross-sectional area of the design strips in two orthogonal
directions
33
ACI318-19, Section 7.6.1, 7.6.2, 8.6.1, 8.6.2
25
Technical Note
601
APPENDIX
This appendix includes additional information directly relevant to the design of concrete structures, but
not of a type to be included in the program.
Effective width of the flange34
o For T-Beams
Effective overhanging flange width on each side of web is the smallest of:
• Ln/8
• 8 times the flange thickness
• ½ of the clear distance to the next web – not checked in program
o For L-Beams
Effective overhanging flange width on each side is the smallest of:
• Ln/12
• 6 times the flange thickness
• ½ of the clear distance to the next web – not checked in program
Analysis
o Arrangement of loads35:
o Continuous beams and one-way slabs:
factored dead load on all spans with full factored live load on two adjacent spans
factored dead load on all spans with full factored live load on alternate spans
o Two-way slabs36:
If the ratio of live over dead load exceeds 0.75, live load is skipped as in the following
combination:
• factored dead load on all spans with 3/4th of the full factored live load on the
panel and on alternate panels; and
• factored dead load on all spans with 3/4th of the factored live load on adjacent
panels only.
Redistribution of moment37
o Redistribution is only permitted when the net tensile strain, t, is not less than 0.0075.
o Percentage of redistribution = 1000t% ≤ 20% where t = net tensile strain in extreme layer
of longitudinal tension steel at nominal strength.
Deflection
o Maximum permissible computed deflections are based on Table 24.2.238.
34
ACI318-19, Section 6.3.2
35
ACI318-19, Section 6.4
36
ACI318-19, Section 6.4
37
ACI318-19, Section 6.6.5
38
ACI318-19, Section 24.2.2
26
Technical Note
601
NOTATION
27
Technical Note
601
Ɛp strain in tendons at centroid
Ɛ’s strain in compressive steel at centroid
modification factor reflecting the mechanical properties of the concrete
ɸ strength reduction factor
µ ductility factor
ρ ratio of nonprestressed tension reinforcement = As/b*dr
ρ’ ratio of nonprestressed compression reinforcement = As’/b*dr
ρp ratio of prestressed reinforcement = Aps/b*dp;
ω ρ*fv/f’c;
ω’ ρ’*fv/f’c;
ωp ρp*fps/f’c
28