TWIN COOL PRECISION AIR CONDITIONING UNIT

Air conditioner model: TDTR1822A


Condenser model: CAP4002 Nr. of condensers: 1

Fan(s): Backward curved centrifugal motorfans

Unit power supply: 400/3ph/50Hz

Refrigerant: R410a

Application: unit for IT and NON-IT cooling applications, with the exception of human comfort cooling

WORKING CONDITIONS

Direct expansion Chilled Water


Dry bulb temperature 20.0 20.0 °C
Relative humidity 50 50 %
Wet bulb temperature 13.8 13.8 °C
Altitude a.s.l. 0 0 m
External static pressure 20 20 Pa
Outside air temperature 46.0 °C
Chilled water inlet temperature - 5.6 °C
Chill. water outlet temperature - 12.2 °C
Glycol percentage - 0 %
Freezing temperature - 0.0 °C

PERFORMANCE / FEATURES

Direct expansion Chilled Water


Compressor(s) ON 2 - -
Total cooling capacity 50.1 38.8 kW
Sensible cooling capacity 49.1 38.7 kW
SHR 98.0 99.9 %
EER (total cooling capacity/total system power consumpt.) 2.0 10.4 kW/kW
COP (Compressor Coefficient of Performance) 2.6 kW/kW
Room unit air flow rate 15775 15775 m³/h
Room unit air flow rate 4.4 4.4 m³/s
Discharge air temperature off unit 11.4 13.4 °C
Discharge air relative humidity off unit 83 74 %
Room unit absorbed power 23.3 3.7 kW
Number of fans 2 -
Fan(s) absorbed power 3.7 kW
Fan(s) electr. abs. 8.7 A
Fan(s) speed regulation 290 V
Compressor absorbed power 19.6 - kW
Compressor absorbed current 37.7 - A
Condenser air flow rate 31865 - m³/h
Condenser air flow rate 8.9 - m³/s
Condenser absorbed power 2.3 - kW
Condenser absorbed current 10.5 - A

The performances are obtained through theoretical calculations and they are therefore subject to the consequent variations.
The performances refer to the standard unit set as in the present report. Other possible options or modifications made on request could affect the final
performances.
1 /2
Schneider Electric - Calculation program "UNICALC" vers. 3.8.0 (user profile) - Refer to Schneider Electric cooling FAT Method Statement for further
details

3/6/2018
TWIN COOL PRECISION AIR CONDITIONING UNIT

Air conditioner model: TDTR1822A


Condenser model: CAP4002 Nr. of condensers: 1

Fan(s): Backward curved centrifugal motorfans

Unit power supply: 400/3ph/50Hz

Refrigerant: R410a

Application: unit for IT and NON-IT cooling applications, with the exception of human comfort cooling

Condenser sound pressure level at 5 m in free field (with legs) 56.5 - dB(A)
Condenser sound pressure level at 5 m in free field (without 60.6 - dB(A)
Chilled water flow rate - 4979 l/h
Chilled water flow rate - 1.4 l/s
Total water side pressure drop - 15.0 kPa
3-way valve pressure drop - 5.1 kPa
Coil pressure drop - 9.9 kPa
Sound pressure level at 2 m in free field (downflow) 57.3 dB(A)

PERFORMANCE OF OPTIONS

Direct expansion Chilled Water


HUMIDIFIERS
hourly capacity 8 l/h
Rated electrical power 6.0 kW
Rated electrical current 8.6 A
STANDARD ELECTRICAL HEATERS
Number of standard heaters 5 -
Total rated electrical power of heaters 15.0 kW
Total rated electrical current for heaters 21.7 A

DIMENSIONS

Direct expansion Chilled Water


Air Conditioner Unit
Height 1960 mm
Width 2170 mm
Depth 865 mm
Weight 714 kg
Condenser (Without legs)
Height 1350 mm
Width 3500 mm
Depth 720 mm

The performances are obtained through theoretical calculations and they are therefore subject to the consequent variations.
The performances refer to the standard unit set as in the present report. Other possible options or modifications made on request could affect the final
performances.
Schneider Electric - Calculation program "UNICALC" vers. 3.8.0 (user profile) - Refer to Schneider Electric cooling FAT Method Statement for further
details

2 /2 3/6/2018