MSData Report
MSData Report
Refrigerant: R410a
Application: unit for IT and NON-IT cooling applications, with the exception of human comfort cooling
WORKING CONDITIONS
PERFORMANCE / FEATURES
The performances are obtained through theoretical calculations and they are therefore subject to the consequent variations.
The performances refer to the standard unit set as in the present report. Other possible options or modifications made on request could affect the final
performances.
1 /2
Schneider Electric - Calculation program "UNICALC" vers. 3.8.0 (user profile) - Refer to Schneider Electric cooling FAT Method Statement for further
details
3/6/2018
TWIN COOL PRECISION AIR CONDITIONING UNIT
Refrigerant: R410a
Application: unit for IT and NON-IT cooling applications, with the exception of human comfort cooling
Condenser sound pressure level at 5 m in free field (with legs) 56.5 - dB(A)
Condenser sound pressure level at 5 m in free field (without 60.6 - dB(A)
Chilled water flow rate - 4979 l/h
Chilled water flow rate - 1.4 l/s
Total water side pressure drop - 15.0 kPa
3-way valve pressure drop - 5.1 kPa
Coil pressure drop - 9.9 kPa
Sound pressure level at 2 m in free field (downflow) 57.3 dB(A)
PERFORMANCE OF OPTIONS
DIMENSIONS
The performances are obtained through theoretical calculations and they are therefore subject to the consequent variations.
The performances refer to the standard unit set as in the present report. Other possible options or modifications made on request could affect the final
performances.
Schneider Electric - Calculation program "UNICALC" vers. 3.8.0 (user profile) - Refer to Schneider Electric cooling FAT Method Statement for further
details
2 /2 3/6/2018