SP-5000F Control System Instructions
SP-5000F Control System Instructions
SP-5000F Control System Instructions
Operation Instruction
2013.7
I
installation, commissioning and maintenance. The installation, commissioning and maintenance must be
fulfilled by qualified personnel who has passed through the special training.
The instruction has the copyright protection and is forbidden to be excerpted, reprinted and copied for
one section or whole contents without permission. If the contents has some modifications, please forgive us
without further notices.
II
Precautions for Safety
Receiving Confirmation
Caution
If the integrated elevator controller is damaged or there is lack of components, please don’t install
it.
Otherwise, there will be danger of injury.
Installation
Caution
In the process of carrying, please hold up the bottom of the housing.
Otherwise, there will be danger that the main body of the integrated elevator controller will
come off, people will get injured and the integrated elevator controller will get damaged.
Please install on incombustible objects like metal.
Otherwise it may cause fire.
Please install on objects that have enough weight capacity.
Otherwise, there will be danger that the main body of the integrated elevator controller will come
off, people will get injured and the integrated elevator controller will get damaged.
Please don’t install the controller in such environment that liquids like water or rain drops will
splash on it.
Otherwise the integrated elevator controller will get damaged.
When you install the controller and braking resistor for the same cabinet, please set cooling fan or
other cooling device so that the temperature of supply air will remain below 45℃.
Otherwise ,there will be fire or other accidents due to overheat.
Please don’t install in the place where there are inflammable or explosive gases or near where
there is combustible goods.
Otherwise ,there will be danger of fire or explosion.
Please don’t drop such conductive objects as metal inside the controller.
Otherwise, there is danger of fire or that the controller will be damaged.
Wiring
Danger
Before wiring, please confirm if mains input is in the off state.
Otherwise there is danger of electric shock and fire.
Only the qualified electrical engineer can perform the wiring.
Otherwise there is danger of electric shock and fire.
Please be sure that the PE protective grounding terminal is connected to earth reliably.
Otherwise there will be electric shock and fire。
After the wiring of emergency stop circuit, please check if it is in proper state.
Otherwise there will be danger of injuries.
Please don’t touch the conductor of the output terminal with bare hands or let output wire contact
housing. Please don’t make output wire short out.
Otherwise there will be electric shock and open circuit, and it is very dangerous.
Please confirm if the power voltage of AC main circuit is in line with the rated voltage of
integrated elevator controller.
Otherwise there will be danger of electric shock and fire, and that controller will be damaged.
Please don’t carry out withstand voltage test on integrated elevator controller.
Otherwise the semiconductor components will be damaged.
III
Please connect braking resistor according to the wiring diagram.
Otherwise there is danger of fire.
Please tighten the terminal screw according to the specified torque.
Otherwise there is danger of fire.
Please don’t connect power to output terminal U,V and W.
Otherwise the controller will get damaged.
Please don’t connect capacitor or LC/RC filter to output circuit.
Otherwise the controller will get damaged.
Please don’t make short circuit between terminal B1 and terminal B2.
Otherwise there is danger of fire or explosion.
Trial operation
Danger
Please don’t turn on the power until you confirm front(terminal) housing has been installed. Once
power is on, please don’t disassemble the housing,
Otherwise, there is danger of electric shock.
When choosing retrial at fault, please keep away from motor and linkage machine for the reason
that when warning stops suddenly, the motor will restart abruptly.
Otherwise, there is danger of injuries.
Please prepare additional urgent stop switch(stop switch is effective only after it has been set
functionally).
Otherwise, there is danger of injuries.
Please confirm that running signals has been cut off before resetting warning.
Otherwise, there is danger of injuries.
During operation, please don’t check signals and operate incorrectly.
Otherwise, there is danger of injuries and it may damage the controller.
Caution
Please don’t touch cooling fin or braking resistor as it will produce high temperature.
Otherwise there is danger of scalding or electric shock.
Please don’t touch braking resistor.
Otherwise there is danger of electric shock.
Proper setting for integrated elevator controller has been made in the factory, please don’t change
it at your disposal, especially in operation.
Otherwise the controller will be damaged.
IV
Contents
Chapter 1 Product Information ................................................................................................................ 1
1.1 Appearance and Dimensions of Integrated Controller .......................................................... 1
1.2 Model specification .................................................................................................................... 4
1.3 Specifications ............................................................................................................................. 6
1.4 Installation Attention Items ...................................................................................................... 8
Chapter 2 Integrated Controller Wiring Instruction .............................................................................. 9
2.1 control system and main circuit wiring .................................................................................... 9
2.2 Main control board terminals wiring and instruction ......................................................... 12
2.3 The type and specifications of PG extend card ..................................................................... 17
2.4 Main control circuit wire specifications and wiring principle .............................................. 18
Chapter 3 SP5000F system function ....................................................................................................... 19
3.1 Function table .......................................................................................................................... 19
3.2 Function instruction ................................................................................................................ 20
Chapter 4 Hand-held operator and menu .............................................................................................. 26
4.1 Hand-held operator .................................................................................................................... 26
4.2 Manual programmer and total menu ....................................................................................... 27
4.3 Operating diagram ..................................................................................................................... 29
4.4 Total menu of manual programmer .......................................................................................... 31
4.5 Monitor interface........................................................................................................................ 32
4.6 Control system menu list ........................................................................................................... 32
4.7 Drive system menu list ............................................................................................................... 53
4.8 General set menu list .................................................................................................................. 75
4.9 Factory set menu list .................................................................................................................. 82
Chapter 5 Elevator Adjustment .............................................................................................................. 91
5.1 Summary of Elevator adjustment .......................................................................................... 91
5.2 Peripheral circuit inspection ................................................................................................... 91
5.3 Check after power on ............................................................................................................... 92
5.4 Motor self-learning .................................................................................................................. 93
5.5 Low speed adjustment............................................................................................................. 97
5.6 Shaft self-learning ................................................................................................................... 97
5.7 High speed adjustment........................................................................................................... 101
5.8 Leveling precision adjustment............................................................................................... 104
Chapter 6 Fault or Prompt Information .............................................................................................. 105
6.1. Ordinary problem analysis ................................................................................................... 105
6.2. Faults or Prompt Information .............................................................................................. 105
6.3 Alarm display and countermeasure of frequency converter ............................................. 121
Chapter 7 SP5000F-CB Car Instruction Board................................................................................... 125
7.1 Car instruction board & car extend board introduction .................................................... 125
7.2 Car instruction board & car extend board .......................................................................... 125
7.3 Car Call extended board SP5000F-CK ................................................................................ 133
Chapter 8 SP5000F Hall call board instruction ................................................................................... 134
8.1 Landing call board ................................................................................................................... 134
8.2 Landing call board outline and wiring function .................................................................... 134
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
(200V class)
(400V class)
Figure 1.1 SP5000F integrated controller appearance
1
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
2
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
3
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
70 42 42 30
Min resistance adapter(Ω)
Rated voltage rated
Single phase 220V(+10%,-10%) 50/60HZ(+5%,-5%)
frequency
Admissible voltage
Power +10%,-15%
fluctuation range
Admissible frequency
±5%
fluctuation range
Circuit breaker (A) 20 30 50 75
Contactor (A) 20 20 30 50
15 20 30 50
Filter
1.42 1.06 0.7 0.42
Table1.1 Specifications of 200V level model
Model SP5000F― 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075
Driver capacity code 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075
Max. applicable motor power (KW) 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Output power (KVA) 11 14 21 26 31 37 50 61 63 98 130
Rated output current (A) 14 18 27 34 41 48 65 80 96 128 165
Choice of braking (W) 800 1000 1500 2000 4000 4800 6000 12800 16000 20000 20000
resistor(W) ( Ω) 100 75 50 40 32 20 16 13.6 13 13 13
Min. applicable resistance value (Ω) 39 39 26 26 20 20 13 11 11 11 11
Rated voltage
Three-phase 350、380、400、420V 50/60Hz
rated frequency
Admissible
voltage +10%,-15%
Power
fluctuation range
Admissible
frequency ±5%
fluctuation range
Circuit breaker (A) 20 30 50 60 75 100 100 150 150 200 300
Contactor(A) 20 20 30 50 50 50 80 100 100 160 250
Filter 15 20 30 40 50 80 100 120 160 180 180
Table1.2 Specifications of 400V level model
4
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Nameplate Instruction
The side of integrated controller has the nameplate recording the driver type, input and output
parameters, machine body number etc. For example, three-phase AC 400V 11KW type:
MODEL: SP5000F-4011Y
INPUT: Input power parameter
OUTPUT: Driver output parameter
SER NO: Machine body number
MASS: Weight
5
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
1.3 Specifications
The specifications of SP5000F series integrated elevator controller are as followed.
Table 1.3 Specifications table
Item Content
Full collective selective control, two elevators duplex control,
Elevator control mode
three to eight elevators group control
Elevator speed scope 0.5~4m/s
Max. floors 64 floors
Basic Passenger elevator, residential elevator, bed elevator,
Applicable elevator type
Characters panoramic elevator, freight elevator
Geared machine, gearless permanent magnet synchronous
Applicable host machine
machine
Communication mode CAN bus serial communication
Leveling accuracy ≤3mm
Control mode Space vector PWM (SVPWM) closed loop vector control
Carrier frequency 10KHz ( 5~15KHz adjustable)
Speed control range 1:1000
Speed control accuracy ±0.05% (25℃±10℃)
Speed response 30Hz
Torque limit Yes (setup by parameter)
Torque accuracy ±5%
Frequency control range 0~120Hz
Frequency accuracy Given Value :±0.01% (-10℃~+40℃)
Frequency given
Given Value:0.01Hz
resolution
Drive Output frequency
control 0.01Hz
resolution
characters Over-load ability 150%rated current 60S;180%rated current 10S
Start-up moment 180%rated current 0Hz
Acceleration/Deceleratio
0.001~600s
n time
No-load start-up compensation, storage battery operation,
self-study, load compensation, cooling fan control, base
locking, torque limit, given CAN communication,
acceleration/deceleration time, S curve for accelerate and
Main control function
deceleration, the supervision of if the host machine current is
effectively blocked during parking, internal braking, PG
frequency division output, automatically retry if having faults,
automatically reset if having faults, parameter copy.
Optical Coupler input
Insulation DC24V
control power
Relay output control
Insulation DC24V
power
Low voltage Optical
Coupler insulation 24 ways switching value, rated load 7mA/DC24V
input
High voltage Optical
Input/output 2 ways switching value, rated load 8mA/AC110V
Coupler insulation input
control
Programmable relay 12 ways switching value,1NO, contact capacity 5A/30VDC、
interface
output 5A/250VAC
CAN communication 4 ways, (parallel connection or group control, hall call,
interface operating panel and remote wireless supervision)
Serial communication
2 ways, digital operator interfaces
interface
RS232 communication
2 ways, upper computer supervision and programming interface
interface
485 communication 3 ways
6
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
interface
USB interface 1ways
Internet interface 1ways
Digital operator LCD(Chinese and English)
Display Supervision software Menu, parameter value, status, variable sequence, digital
interface oscilloscopes etc.
Instantaneous over
Stop at above 200% of rated output current.
current protection
Fuse protection Stop at fuse burnout
Stop at 150% of rated current 60S, or stop at 180% of rated
Overload protection
current 10S
Stop when voltage of main loop DC bus bar is higher than
Overvoltage protection
780V(400V grade).
Stop when voltage of main loop DC bus bar is lower than
Under voltage protection
380V(400V grade).
Cooling fin overheat
Use thermostat to protect.
protection
IPM Protection for over current, overheat, short circuit, under
IPM internal protection
voltage
Motor protection Through electronic the mister to protect
Impacting inhibition loop
Through contactor feedback protection
fault protection
Main Protect when exceeding the setting value of maximum
Over-speed protection
protection permitted speed
functions Speed deviation
Protect when the speed deviation exceeds the permitted value
protection
PG fault protection Protect when PG is disconnected or in wrong phase
Self-learning protection Protect if the motor parameter is abnormal during self-learning
Open-phase protection Protect if input /output open phase during operation
Door interlock fault Protect if the door interlock disconnects in operation
Fault in urgent stop loop Protect if the urgent stop loop disconnects in operation
After issuing the switching off command, do not receive the
Contracting brake faults
response signals of the switching off.
Door zone signal faults Protect if the door zone signals is abnormal.
Output contactor faults Protect if the output connector is abnormal.
Operation time protection Protect if the single operation time exceeds the limit value
Floor position counter
Protect if the floor position counter is in fault .
faults
Communication
Protect if the communication interference fault happens.
interference faults
Well self-learning faults Protect if well self-learning fault happens.
Protection level C: enclosed type; O: open type
Structure Cooling method Forced air cooling
Installation method Flush type in cabinet or suspension type installation
Environment temperature -10℃~+40℃
Environment humidity 5~95%RH,without dews
Storage temperature -20℃~+60℃
Operating
Indoor (none of corrosion gas, inflammable gas, dirts and
environment Operating location
straight sunlight)
Elevation above sea level Under 1000M
Vibration 10~20Hz,<9.8m/S²\u65307X20~50Hz, <2m/S²
7
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
8
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
9
Wiring should be complied with the following drawing. When using the digital operator to operate, the 1 2 3 4
SP5000F Series Elevator Integrated Controller
1 3 5 ENCODER 6b 2a 3b 5a 4b 4a 7b 1a 2b 6a 1b 7a 5b 3a
KM0
B2
b
a
SP5000F integrated controller
BR
12 34567
10
PG-02 PG-01
B1
1 2 3 4 5 6 7 8 91 01 11 21 31 41 5 1 2 3 4 5
11
12
13
14
15
U V W E
1
KM1
3 5
2.1.1 Main circuit wiring diagram
1
main output contactor
10
6
1
7
2
8
3
9
4
B B
ENCODER PIN-inverter PIN 2 4 6
DB15
Notice:
KM1
61 62 1.The diameter of the wire connected to close point on
12V
U1
B-
C+
C-
A+
A-
GND
B+
+5V
SIN+
SIN-
COS+
COS-
A+
0V
A-
Shanghai Sumpo Electric
V1
7 1(5 1) 7 2(5 2) contactor KM1 must be 2.5mm.
W1
1 2V
2a
1a
7b
2b
A+
B+
If we use self-locking contactor,do not connect the
5a
4b
4a
6b
3a
3b
7a
6a
0V
3.Choose either of tw o PG cards.
wire in the dotted line; M
If we use asynchronous motor,do not connect the 4. Power w ire shield layer,encoder wire shield layer,controller
A wire in the dotted line. shell and motor shell all connect to PE. A
11
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
fire and service off signal s can be gathered by basi c st ati on landi ng call board , but m ai n board gather si gnal s first
24 V-(0V)
D D
22
Figure 2.4 Main control board wiring diagram definition and function description of main
D7-8
22
2
2
2
2
24 V-(0V) 24 V+
2
2
JP1.6
KCZ KMZ KQZ ST XF 8KW 7KW UPS B ZS KBZ KM1 K M0 KSA KMS
PTC 6KW 4KW 5KW 3KW 2KW 1KW
1
SQP SQU
1
1
1
21
21
813
812
814
D7-5 D7-4
A D1 -7 A D1 -1 1
B 2-2 B 2-3 B 2-4 B 2-6 B 2-5 B 2-7
A 1-7 A 1-11
CZ MZ QZ PZ S1 W S2 W S3 W S4W S5 W S6 W
J5.7 J5.6 J5.5 J5.4 J5.3 J5.2 J5.1 J4.7 J4.6 J4.5 J4.4 J4.3 J4.2 J4.1 J3.7 J3.6 J3.5 J3.4 J3.3 J3.2 J3.1 J2.7 J2.6 J2.5 J2.4 J2.3 J2.2 J2.1 J1.4 J1.3 J1.2 J1.1
X28 X27 X26 X25 X24 X23 X22 X21 X20 X19 X18 X17 X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 V- V- V+ V+
J1
J3
J5
J4
J2
relevelling
up force switch 3
up force switch 2
up force switch
lower limit
upper limit
lightload
emergency run
brake check
inspection signal
nverter driven comm unication port overload
levelling
J8
J7
standby
Sumpo Integrated elevator controller SP5000F
13
J9
CAN4H
CAN4H
CAN4L
CAN4L
CAN1H
CAN1L
J17.1 COM 6
J16.1 COM 5
GND
GND
GND
B X34- X34+ X33- X33+ Y16 Y15 COM7 Y14B Y14A Y13B Y13A Y12B Y12A B
Y10
Y11
Y8
Y9
J6.4 J6.3 J6.2 J6.1 J19 .3 J19 .2 J19 .1 J18.6 J18 .5 J18 .4 J18 .3 J18 .2 J18 .1
J17.2
J16.2
J12.3
J12.2
J12.1
J11.3
J11.2
J11.1
J17 .3
J16 .3
J13 .3
J13 .2
J13 .1
24 V- 24 V+
A2 A2 A1 A1 A1 A2
Shanghai Sumpo Electric
TXCH2
TXCL2
TXCH3
TXCL3
KSA KMS KM1 KBZ KM0
TXCL1
TXCH1
RC RC KZD RC
A1 A1 A2 RC A2 RC A2 RC A1
V- J1.4 0V
J12.3 0V
J13.1 CANBUS3 TXCH3
J13 Terminal J13 J13.2 communication TXCL3 Group port
J13.3 0V
COM5 J16.1 COM5
Terminal J16 AC250V/3A
Y8 J16.2 Relay output standby
DC30V/3A
Y9 J16.3 standby
COM6 J17.1 COM6
Terminal J17 AC250V/3A
Y10 J17.2 Relay output standby
DC30V/3A
Y11 J17.3 standby
Y12A J18.1 fire return back to AC250V/3A
Relay output
Y12B J18.2 base landing DC30V/3A
Y13A Terminal J18 J18.3 AC250V/3A
Relay output main input control
Y13B J18.4 DC30V/3A
Y14A J18.5 AC250V/3A
Relay output Brake auxiliary
Y14B J18.6 DC30V/3A
COM7 J19.1 COM7
Terminal J19 AC250V/3A
Y15 J19.2 Relay output brake
DC30V/3A
Y16 J19.3 Main output control
16
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
17
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
communication port
Elevator car internal
port
Communication
External calling
18
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Optional function
Service floor switch for group control
1 IC card user management 11
elevator
2 Housing monitoring 12 Nudging
3 Motor temperature protection 13 VIP floor service
Operation for handicapped in operation
4 Voice stop announcement 14
cabinet
5 Earthquake function 15 Peak service
6 Independent control of front and back door 16 Arrival forecast lamp outside the hall
7 Time-sharing service 17 Arrival chime outside the hall
8 Re-leveling after the door opening 18 Double outside call at the same floor
9 Group control dispatching operation 19 Skip floor display
10 Opening door in advance
19
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Note:
The standard functions are product’s standard configured function,and the optional functions are specially
provided software service.
20
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
22
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
23
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Optional function
IC card user Only holding the card, the passengers can arrive the
1
management authorized floor.
Through the communication lines, the control system will
be connected with the terminals in control room, displaying
2 Housing monitoring
the floor position of elevator, operation direction, fault
conditions and etc.
Motor When system detects motor temperature overheating, the
3
temperature protection elevator will be stopped provisionally.
Voice stop During the elevator operation, the elevator will make the
4
announcement voice announcement automatically for the operation
If the earthquake happens, the earthquake detection
equipment will act. One of contacting signal of this
equipment will output to SDS system. The SDS system will
5 Earthquake function
control the elevator even in operation. The elevator will
stop at the nearest floor, then open the door and stop
operation.
The front and back door (front and back doors operation
panel, the front and back doors call box exist) independent
control operation: on the level floor, if there is the floor
register in back door calling box (or back door command),
the elevator will stop and open the back door; if there is the
Independent control floor register from front door calling box (or front door
6
of front and back door command), the elevator will stop and open the front door;
If there are commands from two sides, the elevator will
open the two doors. Similarly, in case of the floor opened,
if pushing the button for back door calling box, the back
door will be opened; if pushing the button of front door
calling box, the front door will be opened.
It can be flexible to set the time-sharing service time
7 Time-sharing service
segment and corresponding time-sharing service floor.
When elevator docks at the landing, a large number of
passengers and cargo come in and out. The leveling will
fluctuate because of the elastic deformation of steel wire
Re-leveling after the
8 rope and rubber. This will bring inconvenience for pass
door opening
angers and cargo to come in and out. In this time, the
system allows run automatically at the speed of
re-leveling to leveling position.
Multiple elevators transmit data(can bus), calculating the
Group control
9 most effective and fast mode configured to respond the
dispatching operation
calling from outer hall.
Under elevator automatic operating condition, the speed
Opening door in
10 will be less than 0.1 m/s during stopping, and door zone
advance
signals is effective. In this condition, through the door
24
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
25
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
26
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Figure 4-2
As shown in the preceding figure,the three buttions are PRG,UP and SET. The functions of
the three buttons are as follows:
PRG: Press this button in any state to display the current function group number.
You can press the UP button to change the function group number.
UP: Press this button to increase the function group number.
FA to FC. You can press the UP button to display them in turn. In addition, in special
function code group menu, you can input simple references by using the UP button.
SET: In the function code group menu, press this button to enter the menu of the function
code group.
In special function code group menu, after you input a simple reference and press this
button to save the setting, the display will return to the F0 menu by default.
The function code groups displayed on the keypad are described as follows:
1. F0: display of floor and running direction
The F0 menu is displayed on the keypad by default upon power-on. The first 7-segment
LED indicates the running direction, while the last two 7-segment LEDs indicate the current
floor number of the elevator.
When the elevator stops, the first 7-segment LED has no display. When the elevator
runs, the first 7-segment LED blinks to indicate the running direction.
When a system fault occurs, the 7-segment LEDs automatically display the fault code
and blink. If the fault is reset automatically, the F0 menu is displayed.
2. F1: command input of the running floor
After you enter the F1 menu, the 7-segment LEDs display the bottom floor (F6-01). You
can press the UP button to set the destination floor within the range of lowest to top and
then press the SET button to save the setting. The elevator runs to the destination floor,
and the display automatically switches over to the F0 menu at the same time.
3. F2: fault reset and fault code display
After you enter the F2 menu, the 7-segment LEDs display "0". You can press the UP
button to change the setting to 1 or 2.
Display "1": If you select this value and press the SET button, the system fault is reset.
Then, the display automatically switches over to the F0 menu.
Display "2": If you select this value and press the SET button, the 7-segment LEDs
display the 11 fault codes and occurrence time circularly. You can press the PRG button
to exit.
27
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Figure 4.2(1)
Press the “Enter” key to enter the interface (Figure 4.3), then enter into the total menu (Figure 4.4), the
28
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
total menu is divided main controller unit, drive unit, common set, factory set, pushing “up” or “down” can
switch up and down.
◆ Operating diagram
The following are the diagram for unlocking/deciphering
The password setting and modification are on the same interface. Any system parameter setting is
needed to input the password at first. If there is no operation by hand-held operator over 10 minutes,
the password is needed to input again, and then can continue setting the parameters.
If it is needed to modify the password, path: “special parameter” => “Modify the user password”=>
“Old password”. Press “Up”/“Down”to choose the number, press “Enter”to confirm, “Esc”for cancel.
After inputting the old password, press “Enter”, on the page, it will prompt to input the new password.
The user should remember the new password solidly. Before each modification of password, it is
necessary to input the new password.
The detailed manipulation for password setting is as following picture:
29
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Cur 0F 10.00m/s
auto stop
Goal 0F 0
00/00 00:00
Enter
mainbo unit
driver unit
general set
factory set
New password
******
Enter
System time
User password
System password
System service
Language selec
Retype password
******
User
Enter
password
Enter
Return main
User password
meue
******
Succeed!
30
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
2-a.user param
2-b.prog param
parameter set 2-c.spec param
2-d.self learn
Main
unit
system fault Er01~ER50
****online help****
1.first motor then well learn.
help 2.first reset then motor learn.
3.well/motor learn enter inspection operation.
VER:SUMPO-V1.0
A1.DH environm
A.environ
A2.DC environm
syst A3.extended fu
C1.Acc/dec tim
C.curve
C2.Acc/dec cur
sequen C3.Operatio TS
Monitoring Driver
unit D.frequen
interface D2.01.FMAX
comm
E.elevator E1.motor V/F E5.ASR charact
par E2.motor para E6.torque comp
J1.frequency D
J.terminal TF J2.torque comp
J3.counter
1.port para
2.run para
monterboard 3.run curv
4.commissio
C.curve sequen
General
set
drive part D.frequen comm
L.protect fum
1.monter self l
self-learn 2.shaft self l
user password
factory
set
system password
system service
language selec
31
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
32
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
33
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
34
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Y04 undefined □
Y05 undefined □
Y06 undefined □
Y07 undefined □
Y08 standby □
Y09 standby □
Y10 standby □
Y11 standby □
Y12 fire return back to base landing □
Y13 main input control □
Y14 Brake auxiliary □
Y15 brake □
Y16 main output control □
main board output state
Y01: □□□□□□
Y07: □□□□□□
Y13: □□□□
35
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
36
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
。。。。。。 。。。
59: 0.00 0.00
Every floor pulse:
01: 00 00
03: 00 00
05: 00 00
07: 0 0
09: 0 0
11: 0 0
13: 0 0
15: 0 0
。。。。。。 。。。
59: 0 0
37
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
38
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
floor time
19.up arrival gong
0.0-10.0 0
output
20.down arrival gong
0.0-10.0 0
output
21.up arrival gong
0.0-10.0 1.0
hold
22.down arrival gong
0.0-10.0 1.0
hold
23.arrival gong output
0.0-10.0 0.0
time
24.arrival gong
0.0-10.0 1.0
holding time
25.group control
return back to 0.0-600 00
main floor
26.group control lift
10.0-100 30
block delay
27.open door 2
0.0-250 20
holding time
13.X13 Undefined
Main input
14.X14
feedback
Main output
15.X15
feedback
16.X16 Brake feedback
17.X17 Brake check
18.X18 Emergency run
19.X19 Undefined
20.X20 Undefined
21.X21 Undefined
22.X22 Undefined
23.X23 Fire
24.X24 service off
Earthquake
25.X25
detection
26.X26 Undefined
27.X27 Undefined
28.X28 Undefined
40
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
10.Y10 Undefined
11.Y11 Undefined
12.Y12 Lighting arrangement
41
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
42
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Back door
landing call
44
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
45
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
units)
23 floor display(tens、 0-9 A-Z 23
units)
24 floor display(tens、 0-9 A-Z 24
units)
25 floor display(tens、 0-9 A-Z 25
units)
26 floor display(tens、 0-9 A-Z 26
units)
27 floor display(tens、 0-9 A-Z 27
units)
28 floor display(tens、 0-9 A-Z 28
units)
29 floor display(tens、 0-9 A-Z 29
units)
30 floor display(tens、
0-9 A-Z 30
units)
31 floor display(tens、
0-9 A-Z 31
units)
32 floor display(tens、
0-9 A-Z 32
units)
33 floor display(tens、
0-9 A-Z 33
units)
34 floor display(tens、
0-9 A-Z 34
units)
35 floor display(tens、
0-9 A-Z 35
units)
36 floor display(tens、
0-9 A-Z 36
units)
37 floor display(tens、
0-9 A-Z 37
units)
38 floor display(tens、
0-9 A-Z 38
units)
39 floor display(tens、
0-9 A-Z 39
units)
40 floor display(tens、
0-9 A-Z 40
units)
41 floor display(tens、
0-9 A-Z 41
units)
42 floor display(tens、
0-9 A-Z 42
units)
43 floor display(tens、
0-9 A-Z 43
units)
44 floor display(tens、
0-9 A-Z 44
units)
45 floor display(tens、 0-9 A-Z 45
47
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
units)
46 floor display(tens、
0-9 A-Z 46
units)
47 floor display(tens、
0-9 A-Z 47
units)
48 floor display(tens、
0-9 A-Z 48
units)
49 floor display(tens、
0-9 A-Z 49
units)
50 floor display(tens、
0-9 A-Z 50
units)
51 floor display(tens、
0-9 A-Z 51
units)
52 floor display(tens、
0-9 A-Z 52
units)
53 floor display(tens、
0-9 A-Z 53
units)
54 floor display(tens、
0-9 A-Z 54
units)
55 floor display(tens、
0-9 A-Z 55
units)
56 floor display(tens、
0-9 A-Z 56
units)
57 floor display(tens、
0-9 A-Z 57
units)
58 floor display(tens、
0-9 A-Z 58
units)
59 floor display(tens、
0-9 A-Z 59
units)
60 floor display(tens、
0-9 A-Z 60
units)
48
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
open time
Automatically
0-23 00:00
close time
Forenoon peak
0-23 08:00
period
Forenoon time
0-60 0 unit:hour
range
Forenoon stop
1-64 1 unit:floor
floor
Noon peak
0-23 11:00
period
Noon time
0-60 0 unit:hour
range
Noon stop
1-64 1 unit:floor
floor
Afternoon
0-23 17:00
peak period
Afternoon time
0-60 0 unit:hour
range
Afternoon stop
1-64 1 unit:floor
floor
Start floor of
0-64 0
special floor 1
End floor of
0-64 0
special floor 1
Service start
time of special 0-23 00:00
floor 1
Service off
time of special 0-23 00:00
floor 1
Start floor of
0-64 0
special floor 2
End floor of
0-64 0
special floor 2
Service start
time of special 0-23 00:00
floor 2
Service off
time of special 0-23 00:00
floor 2
Help
Menu display
****online help****
1. Motor self-learn then host way self-learn
2. Restore then self-learn when motor self-learn
3. Only in inspection state can host way/motor self-learn.
Version:SUMPO-V1.0
51
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
26. front door open signal 27. front door close signal
28. front door open limit 29. front door close limit
30. front door light curtain shoe 31. back door open limit
32. back door close limit 33. back door light curtain shoe
34. over load 35. full load
36. under load 37. no load
38. attendant 39. bypass
40. VIP 41. fire operation signal
42. earthquake function 43. door close delay button
44. attendant down going
45. attendant up going orientation
orientation
46. brake detection 47. emergency operation
48. door transfer switch 49. pre-open door
50. re-level up 51. re-level down
52
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
53
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
U2.07. PG pulse change rate Used for evaluate the interference degree to PG signal 1Pls
U2.08. PG(PG2) pulse counter Used for count input pulse number when position servo control 0%
U2.09. UVW state Current UVW state 0
actual positioning
U2.10. 0
deviation
U2.11. operation state unused state indication for inverter operating 0
U2.12. ED% Duty ratio of opened brake unit 0
U2.13. Operation state current operation state 0
54
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Parameter Minimum
Name Description
NO. unit
U4.01. Fault record Current happened fault record ~
U4.02. Frequency command Frequency command when current fault happened 0.01Hz
U4.03. Output frequency Output frequency when current fault happened 0.01Hz
U4.04. Feedback frequency Feedback frequency when current fault happened 0.01Hz
U4.05. Output current Output current when current fault happened 0.0A
Command torque (relative rated output torque%) when current
U4.06. Command torque 0.0%
fault happened
U4.07. Output voltage Output voltage when current fault happened 0V
U4.08. DC bus bar voltage DC bus bar voltage when current fault happened 0V
U4.09. Radiator temperature Radiator temperature when current fault happened 0℃
U4.10. I/O terminal state Input/output terminal state when current fault happened
U4.11. F1 input voltage Terminal F1input voltage when current fault happened
U4.12. F2 input voltage Terminal F2 input voltage when current fault happened
U4.13. Operation state Operation state when current fault happened
U4.14. ASR state ASR state when current fault happened
U4.15. Auxiliary information Auxiliary information of current alarm 0℃
55
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
T. System operation
Control mode
Param Total
Set Storage No magnetic
eter Name Description Default
range mode V/F sensor magnetic Vector current flux
NO. flux servo vector
vector vector
vector
Motor parameter
self-learning/hoi
stway parameter
selr-learning
0:Line
resistance of
static type
1:Line
0,1,2,
T1-03 Self learning resistance of 0 ☆ ○ ○ ○ ○ ○ ○
3
rotation type
2:Magnetic pole
position static
type
3:Magnetic pole
position rotation
type
absolute value
5:Multi-ring
absolute value
6:Magnetic
encoder
57
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
4:PID
5:Special for
main shaft
6:Retain 1
7:Retain 2
8:Retain 3
9:Retain 4
10:Escalator
11:Elevator
12:Door machine
13:Door brake
(Extended
A3.02. function) 0~99 0 ☆ ○ ○ ○ ○ ○ ○
enable word
B. Application parameter
Control mode
Param Total
Set Storage No magnetic
eter Name Description Default magnetic Vector current
range mode V/F sensor flux
NO. flux servo vector
vector vector
vector
Setting input
method of
operation
Operation
command
B1.01. command 0,1,2 2 ☆ ◎ ◎ ◎ ◎ ◎ ◎
0:Operator
selection
1:Outer terminal
control
2:Serial port
Setting input
method of
operation mode
Operation 0:Forward and
B1.02. mode reverse direction 0,1,2 0 ☆ ◎ ◎ ◎ ◎ ◎ ◎
selection 1:Three wire
system
2:Enable
direction
0: Inertance stop
1: Deceleration
stop
2: Time-limited
deceleration stop
Stop mode 0,1,2,
B1.03. 3: Zero speed 0 ☆ ○ ○ ○ ○ ○ ○
selection 3,4
(locked)/non-
zero speed (free
slide)
4: (Full fields)
DC brake stop
Setting input
method of
operation
commands
Frequency 0:Manipulator 0,1,2,
B1.04. command 1:External 3,4,5, 2 ☆ ◎ ◎ ◎ ◎ ◎ ◎
selection terminal control 6
2:Analog
quantity dynamic
following
3:Analog
58
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
quantity
command
following
4:Extend card
5:Torque given
6:Location
following
The command
for setting
frequency is
chosen through
analog quantity
signal path in
given analog port
0:Analog port 1
1:Analog port 2
Analog
2:Analog port 3 0,1,2,
command(S
B1.05. 3:Analog port 1+ 3,4,5, 5 ☆ ◎ ◎ ◎ ◎ ◎ ◎
election of
Analog port 2 6,7,8
given mode)
4:Extend
command 1
5:Extend
command 2
6:Extend
command 3
7:Extend
command 4
8:Pulse given
Reverse 0:Enable reverse 0,1
B1.07 forbidden 1:Forbid reverse 1 ☆ ◎ ◎ ◎ ◎ ◎ ◎
selection
In case of startup
the load with
Startup larger inertia,
B1.10 (DWELL) motor into stall 0.00~ 0.00 Hz ○ ○ ○ ○ ○ ○ ○
frequency condition can be 2.50
prevented by
transient holding
output frequency.
Startup 0.00~
B1.11 (DWELL) 2.50 0.00S ○ ○ ○ ○ ○ ○ ○
time
Before decision
of motor
Startup electrified, if or
B1.13 position not to choose the 0,1 0 ☆ ○ ○ ○ ○ ○ ○
locking position locked.
0:Invalid
1:Effective
0:Forward
Motor rotary
B1-15 direction direction 0,1 0 ☆ ○ ○ ○ ○ ○ ○
1:Reversed
direction
Permit 400V
Lower class driver
operating under
B1-16 voltage
operation AC220V power 0,1 0 ☆ ○ ○ ○ ○ ○ ○
enable input:
0:invalid
1:effective
59
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
60
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Gradually
disconnecting
Output (stop)
the power off 0.00~
C3-06 transition 0.00S ◎ ○ ○ ○ ○ ○ ○
transition time 2.50
time
for motor output
torque
Output 0.00~
C3-07 0.20S ◎ ○ ○ ○ ○ ○ ○
action delay 2.50
62
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
63
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
64
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
65
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
(Encoder)
deviating 0.0~35
H5.07. 0.0 ☆ × × × × ◎ ◎
electric 9.9
angle
67
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Setting the
No-load
compensation
down going 0.0~
J2.03. torque during 0.0% ○ × × ○ ○ ○ ○
compensation 100.0
motor reversed
(torque)
dragging
Setting the
Full load up
compensation
going 0.0~
J2.04. torque during 0.0% ○ × × ○ ○ ○ ○
compensation 100.0
motor fore ward
(torque)
dragging
Setting the
Full load
compensation
down going 0.0~
J2.05. torque during 0.0% ○ × × ○ ○ ○ ○
compensation 100.0
motor reversed
(torque)
braking
Setting the
compensation
torque direction
Startup during the
compensation motor startup
J2.06. 0,1 1 ○ × × ○ ○ ○ ○
(torque) 0:up going fore
direction ward direction
1:up going
reversed
direction
68
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
of ℃
0:no protection
1:freely sliding
stop
2:Deceleration
stop
3:Unusual
deceleration stop
4:Only warn
If the maximum
frequency is
100%, during the
Speed loss deviation of
protection feedback and
threshold command speed
L4.02. 1~50 10% ○ × × ○ ○ ○ ○
value are to much
(frequency) more, the
% protection action
threshold value
will be set with
the unit of %.
Setting action
time of the
Speed loss protection when
0.01~
L4.03. protection speed deviation 0.50S ○ × × ○ ○ ○ ○
2.50
time is too large with
the unit of
second.
The selection for
motor overspend
action
0:no protection
Overspread 1:freely sliding
0,1,2,3,
L4.04. protection stop 1 ○ × × ○ ○ ○ ○
4
function 2:Deceleration
stop
3:Unusual
deceleration stop
4:Only warn
If the maximum
Overspend frequency is
protection 100%, the
threshold threshold value
L4.05. 1~120 105% ○ × × ○ ○ ○ ○
value for overspend
(frequency) protection action
% will be set with
the unit of %.
The action time
Over speed for overspend
0.01~
L4.06. protection protection will be 0.1 ○ × × ○ ○ ○ ○
2.50
time set with the unit
of second.
speed lose
speed lose prevention
prevention function in driver
L4.07. 0,1 0 ○ × × ○ ○ ○ ○
function in acceleration
acceleration 0:invalid
1:valid(stop
71
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
accelerate when
overpass value
L408. accelerate
again after
current
restored.)
Set speed loss
speed lose
prevention
prevention
function in driver 50~
L4.08. threshold 150% ○ × × ○ ○ ○ ○
rated current 200
value% in
100% and unit
acceleration
of %.
set speed loss
speed loss
prevention
prevention
function in driver
L4.09. limiting 0~100 50% ○ × × ○ ○ ○ ○
rated current
value% in
100% and unit
acceleration
of %.
speed lose
speed loss prevention
prevention function in driver
L4.10. 0,1 0 ○ × × ○ ○ ○ ○
function in steady speed
running 0:invalid
1:valid
set speed loss
speed lose
prevention
prevention
function in driver 50~
L4.11. threshold 160% ○ × × ○ ○ ○ ○
rated current 200
value% in
100% and unit
running
of %.
speed lose
prevention
function in driver
speed loss
deceleration
prevention
L4.12 0:invalid 0,1 0 ○ × × ○ ○ ○ ○
function in
1:Valid After
deceleration
validly set, driver
braking unit does
not work.
72
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Encoder
0:Invalid
L5.01. disconnection 0,1 1 ○ × × ○ ○ ○ ○
1:Effective
protection
PG phase
stagger 0:invalid
L5.02. 0,1 0 ○ × × ○ ○ ○ ○
protection 1:valid
function
0:no protection
1:freely sliding
Z phase stop
detection 2:Deceleration 0,1,2,
L5.03. 0 ○ × × ○ ○ ○ ○
operation to stop 3,4
adjust errors 3:Unusual
deceleration
stop
when Z phase
adjust, send
error pulse to
threshold value
Z phase
and
detection
continuously
L5.04. threshold 0.1~25 0.5 ☆ × × ○ ○ ○ ○
exceed detection
value to
times, then
adjust errors
driver do Z
phase adjust
error protection
( display JE)
Z phase
detection time
L5.05. 1~100 3 ○ × × ○ ○ ○ ○
to adjust
errors
4:Only warn
Input phase The voltage
default threshold of
L6.02. (protection)
voltage
input open-phase 1~100
protection will 20V ○ ○ ○ ○ ○ ○ ○
(threshold be set with the
value) unit of V.
Driver output
Output open-phase
L6.03. open-phase protection 0,1 0 ○ ○ ○ ○ ○ ○ ○
protection 0:Invalid
1:Effective
The selection of
Electric output leakage
L6.04. leakage
protection
protection to
earth 0,1 0 ○ ○ ○ ○ ○ ○ ○
enable 0:Invalid
1:Effective
Storage method:According to the parameter modification condition, it can be divided into the following 3
storage methods:
◎:It can be modified under any conditions
○ :If the driver is on operation condition, the parameters can not be modified. If the driver is on ready
condition, the parameters can be modified.
☆:If the driver is on operation condition, the parameters can not be modified. If the driver is on ready
condition, the parameters can be modified. And if the modified driver is on not ready condition, pressing
the STOP key is necessary to make the driver enter in ready condition, and then the driver can operate
continuously.
Control mode:The parameter in the table indicates if it has influence on the corresponding control modes
or not.
◎:It must be set accurately. The parameter should be set as the system corresponding values. If not, the
system can not operate normally.
○ :Having influence. The parameter has certain influence on the control function and operating condition,
but the setting value can not influence the system normal operation.
×:No influence. Under this control mode, no matter what value is set for this parameter, it will not make
any influence to system.
Note:Control mode without PGV/F can be briefly called: V/F
Control mode without PG magnetic flux vector can be briefly called: No sense vector
Asynchronous motor with PG magnetic flux vector control mode can be briefly called: magnetic flux
vector
Asynchronous motor with PG current vector control mode can be briefly called: current vector
Permanent magnet synchronous motor with PG current vector control mode can be briefly called:
synchronous current vector
Permanent magnet synchronous motor with PG magnetic flux vector control mode can be briefly called:
synchronous magnetic flux vector
74
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
76
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
16.X16 Undefined
17.X17 open door button
18.X18 close door button
19.X19 Undefined
20.X20 Undefined
78
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Setting the
needed
deceleration
(particular) time at
C1.09 deceleration emergency
stop stop
time from 100%
0.1~
20.0 2.0S ◎ ○ ○ ○ ○ ○ ○
time of maximum
output
frequency to
0% .
Setting the
automatically
switching
acceleration t
time frequency,
The
C1.10 time switch multi-function
Acceleration
input
0~
300.00 0.00Hz ◎ × × × × × ×
“acceleration
time selection”
will be in
preference to
automatically
switching.
Setting the
automatically
switching
deceleration
time frequency,
Deceleration The
multi-function 0~
C1.11 time input 300.00 0.00Hz ◎ × × × × × ×
switching “deceleration
time selection”
will be in
preference to
automatically
switch.
80
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
81
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
(FMAX) output
frequency
82
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
83
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Setting action
time of the
Speed loss protection when 0.01~
L4.03. protection speed deviation 0.50S ○ × × ○ ○ ○ ○
time is too large with 2.50
the unit of
second.
The selection for
motor overspend
action
0:no protection
Overspread 1:freely sliding 0,1,2,3,
L4.04. protection stop 1 ○ × × ○ ○ ○ ○
function 2:Deceleration 4
stop
3:Unusual
deceleration stop
4:Only warn
If the maximum
Overspend frequency is
protection 100%, the
threshold threshold value
L4.05. value for overspend 1~120 105% ○ × × ○ ○ ○ ○
(frequency) protection action
% will be set with
the unit of %.
speed lose
prevention
function in driver
speed lose acceleration
prevention 0:invalid
L4.07. function in 1:valid(stop 0,1 0 ○ × × ○ ○ ○ ○
acceleration accelerate when
overpass value
L408. accelerate
again after
current restored.)
speed lose
speed loss prevention
prevention function in driver
L4.10. function in steady speed 0,1 0 ○ × × ○ ○ ○ ○
running 0:invalid
1:valid
84
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
85
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Motor rated
E2.05 Range:0.00-600.0Hz default:50.00
frequency
Motor rated rotated
E2.06 Range:1-36000RPM default:1450
speed
Motor no-load
E2.07 Range:0.1-500.0 default:10.5
current
Motor rated speed
E2.08 Range:0.10-20.00Hz default:1.50
difference
H5.01 PG pulse counts Range:100-20000 default:1387
PG phase sequence 0:During motor fore ward rotation, A phase lead
H5.03
1:During motor fore ward rotation, B phase lead
(Encoder) deviating
H5.07 electric Range:0.0-359.9 default:0.0
angle
87
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
88
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Parameter
Factory set
NO.
1. system time
2. modify user password
3. modify system password
4. system information
5. language choose
4.8.2 The second menu
89
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
90
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
2. Encoder inspection
The feedback pulse signals of encoder are the important guarantee for system to realize the accurate control.
It should be checked carefully before adjustment.
1) Encoder installation is stable and wiring is reliable.
2) The signal lines of encoder should be separately laid with high voltage circuit in slot to prevent
the interference.
3) It is better to introduce the encoder wiring from the encoder into the control cabinet. If the wire is
not long enough and need more wires, the extension part should use shielded wire and the
connection with the encoder’ original wire should be better welded joint with electric iron.
4) The shielding layer of encoder is required to be safety connected to earth at the end of controller
(in order to avoid interference, it is only connected to earth at one end) .
3. Power checking
It is necessary to check the user’s power before the system is power on. The voltage between every power
phase should be in 380V±15%. Unbalance rate in each phase should be no more than 3%.
1) The input of main control should be DC24V. The input voltage between GND should be
DC24V±15%.
2) The specification of main input wire and general switch capacity should comply with the
requirements.
Note:If the system input voltage exceeds the allowable value, it will bring the devastating consequences.
So attention is required in inspection. Pay attention to the positive pole and negative pole of DC power. If
there is phase missing in the system power input part, please don’t operate the elevator.
94
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
95
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Take dynamic self-learning in synchrony machine no-load situation as example, the specific operation of
hand operator is as following figure:
96
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
Elevator speed
L1(m) L2 L3(mm) L4(mm)
(m/s)
0.5 0.8 80-100 130-150
0.63 1.0 80-100 130-150
1.0 1.5 80-100 130-150
1.5 2.25 1.5 80-100 130-150
1.75 2.62 1.5 80-100 130-150
2 3.00 1.5 80-100 130-150
2.5 3.75 1.5 80-100 130-150
3 4.50 1.5 80-100 130-150
3.5 5.25 1.5 80-100 130-150
4 6.00 1.5 80-100 130-150
(2)The default length of leveling inductor plate is 200mm,the correct installation is: First, make the car
door sill and the hall door sill on the same level. Second, install the leveling on one side of the car top.
Third, install inductor plate in the middle of photoelectric switch.
Note:
(1)If the elevator speed is lower than 1.75m/s, just need to install one deceleration switch.
(2) For the different drive units, the deceleration distance L1 has a few differences.
(3) Before the shaft self-learning, the installation dimensions should be surely correct; after the
self-learning finished, if the installation dimensions need adjustment, the shaft self-learning will be
restarted.
(4) The above mentioned distances are only for reference, they also need adjustment according to different
condition on the scene.
99
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
X16 Brake ● 〇
X17 Brake detection ● 〇
4. Enter the menu ”Main Board—6.Self-learn” to start shaft parameters self-learning. The elevator will go
up at inspection speed. You can see the floor number and the pulse number is increasing. In this process, the
system can automatically learn the positions of each leveling and all switches. When the car touch the
upper forced deceleration switch, it will stop. Now the prompt ”Learn Successful” will be displayed in the
operator which means the self-learning is finished successfully. If shaft self-learning is unsuccessful, the
adjustment prompt is as following table:
Shaft self-learning prompt Solution
1. Not in INSP Switch to inspection state
2. Un Leveling, Touch Low-Limit Solve the problem according to step 3.
Exists over-rushing or staying phenomenon,
3. Un Leveling, Touch Up-Limit
which decrease the maintenance frequency
The setting of total floors is inconsistent with the
4. Total Floors Too Small
actual condition or the photoelectric switch signal
The setting of total floors is inconsistent with the
5. Total Floors Too Big
actual condition or the photoelectric switch signal
6. Learning Invalid not complying with the self-learning condition
Note:
1. Parameter have learned save in main controller board, so if change main controller board, it must
self-learn again.
2. if adjust leveling baffle, up/down forced deceleration switch, inverter max output frequency, or the total
floor number is changed, it also need to hoist way self-learn again.
The effect on the riding feeling by the machine part generally can be caused in the following
conditions :
(1) Check the worm wheel and worm rod of dragging machine.
(2) The perpendicularity of elevator rail effects not only for the leveling vibration but also for the
perpendicularity vibration during elevator operation.
(3) The elevator running quality is related to the car rail shoe. If want to achieve better PMT testing
curve, you should do car static balance and car dynamic balance .Let car rail shoe bear the least
resistance, and achieve elevator quality of running.
(4) The counterweight rail shoe’s miss-verticality and bearing resistance affect elevator’s
comfortable feeling too.
(5) Brake affect elevator’s starting and stopping dramatically.
(6) It can affect elevator comfortable feeling that the joint between the motor and dragging machine
loose or fray.
(7) The unbalanced pull of elevator steel rope is the epicenter of the tremor.
102
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
(8) The shock absorption tray of car roof, car bottom and dragging machine bottom all affect elevator
running quality.
The parameter chosen also have effects to riding feeling. The inappropriate parameter setting
can cause the elevator perpendicularity vibration.
There are mainly two kinds of parameters will affect the feeling.
(1)PI parameters:according to PI control theory,large proportion gain value is good for sensitivity
of close-loop controlling, but too large value will cause vibration. Shorter integration time lead to
faster system response speed, but if the time is too short, the vibration will be aggravated. The most
suitable method is: increase the proportion gain until the vibration occurs, then carefully decrease
the value just until the vibration disappears. The close-loop is in most suitable state now.
●Acceleration/deceleration
According to the actual condition of elevator operation, referring the curve figure 5.5 to modify the
relative parameters.
Figure 5.5
Curve S has 6 stages. The smaller value is, slower and gentler curve is, better comfortable feeling is.
●Noise
Increase carrier frequency appropriately can eliminate noise. But it cannot too large, or it will
affect the overload capacity of inverter. Increase the setting of carrier frequency A2.02, can eliminate
electromagnetism noise. But, too large carrier frequency will affect the overload capacity of inverter.
104
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
alarm
display content reason lift fault and treatment
code
1.Inspect safety switch in
safety circuit, like scram 1. Lift does not run, include inspection running, auto,
button, speed limiter attendant, bypass, firefighting, full load, lack lift,
switch. emergency etc.
safety circuit
E1 2. safe contactor 2. not response any floor calling, include landing
disconnect
feedback point and safe call, car call, machine room call, group control,
circuit high- pressure remote etc calling.
checkpoint in main board 3. restore after safe circuit connected
all disconnect
safe contactor feedback 1. Lift immediately repeal the running signal
safe circuit
point and safe circuit stopping, like direction, section speed, enabling,
E2 disconnect during
high-pressure checkpoint brake, main output etc.
running
disconnect at the same 2. repeal any floor calling signal
105
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
time during lift running, 3. not response any floor calling, include landing
inspect safe circuit call, car call, machine room call, group control,
remote etc calling.
4. Restore after two all have disconnected. At this
time, if it just at the door, the output open door
restore to normal, if it does not at the door area,
lift meets the running condition, crawl to find the
door area.
safe contactor feedback
1. Lift does not run, include inspection running, auto,
safe contactor point and safe circuit
attendant, bypass, firefighting, full load, lack lift,
feedback point or high-pressure checkpoint
emergency etc.
high-pressure only one work state
E3 2. not response any floor calling, include landing
checkpoint fault before start Inspect safe
call, car call, machine room call, group control,
(safe adhesion circuit high-pressure and
remote etc calling.
fault) low-pressure check
3. restore after power off or press scram button.
circuit
1. Lift immediately repeal the running signal
stopping, like direction, section speed, enabling,
When lift is running, one
have faults when brake, main output etc.
of safe contactor
safe contactor 2. repeal any floor calling signal
feedback point and safe
feedback point or 3. Not response any floor calling, include landing
circuit high-pressure
high-pressure call, car call, machine room call, group control,
E4 checkpoint disconnect.
check running remote etc calling.
Inspect safe circuit
(safe running 4. Restore after power off or press scram button. At
high-pressure and
adhesion fault) this time, if it just at the door, the output open door
low-pressure check
restore to normal, if it does not at the door area,
circuit.
lift meets the running condition, crawl to find the
door area.
Before lift start, door
1. Lift does not run, include inspection running, auto,
lock contactor feedback
attendant, bypass, firefighting, full load, lack lift,
door lock point(door lock feedback
emergency etc.
feedback or and car feedback)and
E5 2. Not response any floor calling, include landing
high-pressure high-pressure
call, car call, machine room call, group control,
check adhesion checkpoint:not
remote etc calling.
disconnect
3. Restore after power off or press scram button.
simultaneously in open
106
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
statenot connect
simultaneously in close
state inspect door lock
high and low pressure
inspection circuit
1. Lift does not run, include inspection running, auto,
when output door open:
attendant, bypass, firefighting, full load, lack lift,
door has opened(door
emergency etc.
open limit signal work)
2. Not response any floor calling, include landing
door lock while door lock do not
E6 call, car call, machine room call, group control,
adhesion break off(door lock, car
remote etc calling.
feedback, door lock
3. Restore after power off or press scram button.
high-pressure check all
the same treatment when open back door, but
inspect door lock circuit
nspect back door open limit
when output door open:
Door open limit signal
does not work, while
door lock disconnect
1. Keep lift door open output until repeal, then close
(back)door open (door lock, car door
according to close command.
E7 limit does not feedback, door lock
2. The same treatment when open back door, but
work high-pressure check);the
inspect back door open limit
same treatment when
output back door open.
inspect door switch limit
signal
door open limit signal
does not work, while
Continuously output door open 3 times, every time
door lock does not
keeps 8s, if it still not open, the current floor will not
disconnect (door lock,
open door open door, lift auto response other floors calling
E8 car door feedback, door
hampered signal. Consequence priority, open door when reach
lock high-pressure
other floors. If not calling signal, auto go to the nearest
check);
floor stop.
inspect door lock circuit
and door limit
107
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
One of door lock (door 1. Lift open and close door abnormally. Open and
lock, car door feedback, close door still abnormally after repeat open and close
close door door lock high-pressure 3times. Stop auto open and close door, but still can
E9
hampered check) and door close open and close manually.
limit inspect door lock 2. If there has car calling again, repeat the execution
circuit and door limit step as 1.
109
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
output main output when 1. Repeat output main output 3 times, every waiting
lift start, inspect no main time is 0.5s, if still cannot close, then stop output.
E16 main output fault output feedback in 0.5s 2. When start in inspection state, start if main output
Inspect main output feedback signal has restored, do not need to power off
feedback contactor or press scram button.
1. Lift immediately stop, repeal the running signal
stopping, like direction, section speed, enabling, brake,
main output etc.
2. repeal any floor calling signal
interrupt main interrupt main output 3. not response any floor calling, include landing call,
E17 output during lift feedback during lift car call, machine room call, group control, remote etc
running running calling.
4. At this time, if it just at the door, the output open
door restore to normal, if it does not at the door area,
lift meets the running condition, crawl to find the door
area.
1. In static state, before lift start running, inspect brake
lift stop while brake
Brake feedback contactor adhesion, forbid running, repeal any calling
E18 contactor does not
fault signal, not response any calling signal.
release
2. Restore after power off or press scram button.
repeal brake when lift
in inspection and
1. Lift immediately repeals the running signal
automatic or other
stopping, like direction, enabling, main output etc.
running way(attendant,
E19 brake adhesion Forbid running, repeal any calling signal, not response
firemen, full load,
any calling signal. Forbid running.
bypass, return back to
Restore after power off or press scram button
base etc.), brake does not
release adhesion
1. Lift Repeat output main output 3 times, every
Brake waiting time is 0.5s, if still cannot close, then stop
Lift output brake,
inspection output.
E20 inspection no brake
fault(open brake 2. When start in inspection state, start if brake
feedback signal in 0.5s.
fault) feedback signal has restored, do not need to power off
or press scram button.
interrupt brake interrupt brake during 1. Lift immediately repeals the running signal
E21
during running lift running stopping, like direction, section speed, enabling, brake,
110
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
111
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
113
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
cause disturbance or otherwise it will collect too many door area signal.
joggling. Because different lifts’ speed is different, time that
high speed lift pass door area will be very short, so the
holding time will not be too long, otherwise the
normal door area signal will be leached. Take pulse
count collected by door area as reference, convert door
area length by pulse count, and compare the setting
door area baffle length, if the difference is too big,
then it is interference.
1. When lift stop, up forced deceleration 1
disconnect, keep the floor number unchangeably, lift
cannot up run, if it does not in the door area, crawl to
find door area. If lift is running at the interlayer, up
forced deceleration 1 disconnect, decelerate and crawl
Disconnect up forced
up forced to find door area to open, display of floor number is
deceleration 1; lift is in
E35 deceleration unchangeable. Lift cannot up run, it can down run and
the middle layer
switch 1 fault go slow speed.
2. After connecting signal, up run to find door
area(self-learning section speed) until touch up forced
deceleration 1, then decelerate and go in crawl speed
to find door area, until up limitation disconnect and
floor is revised.
1. When lift stop, up forced deceleration 2
disconnect, keep the floor number unchangeably, lift
cannot up run, if it does not in the door area, crawl to
find door area. If lift is running at the interlayer, up
forced deceleration 2 disconnect, decelerate and crawl
Disconnect up forced
up forced to find door area to open, display of floor number is
deceleration 2; lift is in
E36 deceleration unchangeable. Lift cannot up run, it can down run and
the middle layer
switch 2 fault go slow speed.
2. After connecting signal, up run to find door
area(self-learning section speed) until touch up forced
deceleration 2, then decelerate and go in crawl speed
to find door area, until up limitation disconnect and
floor is revised.
E37 up forced Disconnect up forced 1. When lift stop, up forced deceleration 2
114
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
deceleration deceleration 3; lift is in disconnect, keep the floor number unchangeably, lift
switch 3 fault the middle layer cannot up run, if it does not in the door area, crawl to
find door area. If lift is running at the interlayer, up
forced deceleration 2 disconnect, decelerate and crawl
to find door area to open, display of floor number is
unchangeable. Lift cannot up run, it can down run and
go slow speed.
2. After connecting signal, up run to find door
area(self-learning section speed) until touch up forced
deceleration 2, then decelerate and go in crawl speed
to find door area, until up limitation disconnect and
floor is revised.
1. When lift stop, down forced deceleration 1
disconnect, keep the floor number unchangeably, lift
cannot down run, if it does not in the door area, crawl
to find door area. If lift is running at the interlayer,
down forced deceleration 1 disconnect, decelerate and
down forced Disconnect down crawl to find door area to open, display of floor
E38 deceleration forced deceleration 1; lift number is unchangeable. Lift cannot down run, it can
switch 1 fault is in the middle layer up run and go slow speed.
2. After connecting signal, down run to find door
area(self-learning section speed) until touchdown
forced deceleration 1, then decelerate and go in crawl
speed to find door area, until down limitation
disconnect and floor is revised.
1. When lift stop, down forced deceleration 2
disconnect, keep the floor number unchangeably, lift
cannot down run, if it does not in the door area, crawl
to find door area. If lift is running at the interlayer,
down forced Disconnect down forced down forced deceleration 2 disconnect, decelerate and
E39 deceleration deceleration 2; lift is in crawl to find door area to open, display of floor
switch 2 fault the middle layer number is unchangeable. Lift cannot down run, it can
up run and go slow speed.
2. After connecting signal, down run to find door
area(self-learning section speed) until touchdown
forced deceleration 1, then decelerate and go in crawl
115
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
116
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
117
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
When up limit
Adjust up forced
deceleration length,
lengthening properly
according to speed. If it
up forced
is too short, it will cause
E62 deceleration too
short that lift cannot decelerate
because deceleration
distance too short in split
situation, so that cause
lift to rush to the summit.
The current floor door baffle cannot block two door
Door inspection Two door switch no
E63 fault switch at the same time(please installation of door
overlap position
switch) or lack one door switch
Main input check main input
E64 adhesion
contactor
120
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
121
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
PG disconnection PG disconnects.
There are frequency output PG connecting lines fault
PGO
commands of driver but not No power supply for PG
receive the PG pulse signals Incorrect PG voltage setting
Function setting conflict One analog input value has been cited by
OPE7
of analog terminals several functions.
Changing the extended mode leads to the
OPE8 Extended parameter over-scope
extended parameter over-scope
Extended parameter setting
OPE9
fault
OPF External operation fault
No contents in operator
Operator internal parameter
ERR4 Operator internal parameter content is not
content fault
complete
Fault in operator writing During the motor operation, the operator
ER3
parameter collection period performs digital writing collection function
PG self-checking fault
The followings are the auxiliary code fault analysis during PG self-checking.
Table 6.2 PG self-checking fault alarm (corresponding to the auxiliary code or parameter)
124
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
206
3.5*4
196
TX16 TX15 TX14 TX13 TX12 TX11 TX10 TX9 TX8 TX7 TX6 TX5 TX4 TX3 TX2 TX1
J2 J1
U18
100
110
J11
J7 J8
CN17
J9 J10
J6 J5 J4 J3
V+ TXL TXH V- TY12C COM5 TY12 COM4 TY11 TY10 TY9 TY8 TY7 TY6 TY5 COM3 TY4 TY3 COM2 TY2 TY1 COM1
125
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
126
1 2 3 4
24V-
D1-9 D3-9
D6-2 D2-7 D 4-7
D D
direct run
overload
VIP
C 3 3 C
Door op en button
J10 J9
door close output
SP5000F-CB 2
3
2
3
4 4
in parking
127
J8 J7
buzzor
COM1 TY1 TY2 COM2 TY3 TY4 TY7 COM4 TY8 TY9 TY12 COM5 V- TXH TXL V+
J3.1 J3.2 J3.3 J3.4 J3.5 J3.6 J4.4 J4.9 J4.5 J4.6 J5.1 J5.2 J6.4 J6.3 J6.2 J6.1
CM1 GM1 KM1 CM2 GM2 KM2 BZ 24V+ BL DL JN 24V+ 24V- TXCH1 TXCL1 24V+
X 2-2 X4-12
X1-7 X1-8 X1-6 X2-3 X2-1 X4-7
B DX4 -1 2 B
DX1 -7 DX1 -8 DX1 -6 D X2 -2 DX2 -3 D X2 -1 D8-10 DX4 -7
Design Audit Technics SP6000-F3 elevator control system schematic diagram Version:V1.00
Check Approval Date 2010.04.12 car board wire connection page: 05
1 2 3 4
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
7.2.3 car instruction board circuit terminal definition & function description
Car instruction board circuit terminals is classifying as power,optical coupler isolated input and
Signal
No. terminal Type Function Note
logic
OFF/nor
optical
X1 J1.1 operator mally
coupler input
open
OFF/nor
optical
X2 J1.2 Direct run mally
coupler input
open
OFF/nor normally
optical mally open
X3 J1.3 overloaded
coupler input open /normally
closed
OFF/nor normally
optical mally open
X4 J1.4 Full loaded
coupler input open /normally
closed
OFF/nor normally
Terminal J1
optical mally open
X5 J1.5 Light loaded
coupler input open /normally
closed
OFF/nor normally
optical mally open
X6 J1.6 front door open limit
coupler input open /normally
closed
OFF/nor normally
optical mally open
X7 J1.7 Front door close limit
coupler input open /normally
closed
OFF/nor normally
optical mally open
X8 J1.8 Front door light baffle
coupler input open /normally
closed
normally
OFF/nor
optical open
X9 J2.1 rear door open limit mally
coupler input /normally
open
closed
Terminal J2
normally
OFF/nor
optical open
X10 J2.2 Rear door close limit mally
coupler input /normally
open
closed
128
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
normally
OFF/nor
optical open
X11 J2.3 Rear door light baffle mally
coupler input /normally
open
closed
normally
OFF/nor
optical open
X12 J2.4 VIP mally
coupler input /normally
open
closed
normally
OFF/nor
optical open
X13 J2.5 Open door button 2 mally
coupler input /normally
open
closed
OFF/nor
optical
X14 J2.6 mally
coupler input
open
OFF/nor
optical
X15 J2.7 mally
coupler input
open
OFF/nor
optical
X16 J2.8 mally
coupler input
open
129
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
J10 J10.3
Rear door close button
J10.4
130
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
There are 16 photoelectric isolation input port distributed on J1 & J2, the sketch map as follow:
VCC
24 V
X1~X16
Input gathering port mainly consists of switching variable input; its characteristic is as follow:
input point Qty 16
shielding 800m
permitted wire length
non-shielding 600m
7.2.4 landing call button & indicator
The landing call button signal & button output indicator are distributed between CN1 and CN16. It can
control 16 floors normally. It can expand to 64 floors. The landing call button signal is switch contact
signal. The buttons of door open/close & indicator are distributed between J7 and J10. The input
characteristic is as follow:
shielding 800m
permitted wire length
Non-shielding 600m
131
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
+24V
+24V +5V
3
10k
1A 1k
300
5
2 I/O
4
+5
SW-PB
12
0V
The landing call button output indicator is open collector output. The maximum load current is
The wiring diagram CN1-CN16(landing calls button & indicator plug-in) & J7-J10(door open/close
4 4
3 3
2 2
1 1
132
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
the above diagram. You need to add 1 expansion board if total building storey is 16-32. If total building
storey is above 32, 2 expansion board is needed and so on. But the maximum storey is 64.
90
3.5*4
85
J11 J12
133
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
When landing call board set floor address, and main controller set this floor as stop floor, landing call
board will collect button signal and send button input signal to main controller board. Set some floors as
non-stop by parameter set. Landing call board of not-stop floors will not collect button input signal, and not
output responding signal. If button get stuck after press and cannot restore to home position and time
overpass 20s, landing call board will ignore this calling signal automatically, to make sure lift normal
operation.
158
151
CN6
CN7
CN1
CN4
ISP programmable port
2 1
address DIP
CN5
ST
SDZ XDZ
2
3
4
1
V+ TXL TXH V-
63 47
fire
CN2
XF
2
3
4
1
CN3
DOWN
135
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
switch power
J1.1 POWER DC24V
supply
J1.2 Communication port TXL CANBUS
J1
J1.3 Communication port TXH CANBUS
switch power
J1.4 POWER 0V
supply
CN1.1 output up run button positive
CN1.2 output Down run button positive
switching variable
CN1 CN1.3 up run button
input OFF/normally
switching variable open
CN1.4 up run button
input
CN2.1 output Down run button positive
CN2.2 output Down run button positive
switching variable
CN2 CN2.3
input OFF/normally
Down run button
switching variable open
CN2.4
input
switching variable
CN3.1
input OFF/normally
CN3 Fire mode input
switching variable open
CN3.2
input
switching variable
CN4.1
input OFF/normally
CN4 service off input
switching variable open
CN4.2
input
switching variable
CN5 CN5
input ISP Program port
switching variable
CN6.1
input OFF/normally
CN6 Up bell input
switching variable open
CN6.2
input
switching variable
CN7.1
input OFF/normally
CN7 Down bell input
switching variable open
CN7.2
input
S1.1 Address setting
S1
S1.2 Test setting
136
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
setting is showed by station(absolutely storey).When address setting is zero, the landing call can be used as a car call board in
car. Landing call board address setting step: firstly, turn switch S1.1 to “ON” status, the landing call board will show S0,
secondly please press the landing call board 'up button’, the address will increase and display will change from S0 in turn to
S1、S2、S3……; also when you press ‘down button’, the address will decrease. Press ‘up/down button’ to set current floor, then
switch off DIP S1.1 to turn off power of landing call board, then restart power.
Please remember 1-bit DIP switch must be 'ON’ status only if bottom landing call board to have the impedance matching
effect. On power off status, the resist value of 2 communication lines of landing call communication ports must be 60Ω.
direction. When landing call board starts power, if address setting is zero, it will display character‘S0’, which tells landing
call boards can be used as car call boards. If address setting is a binary value, it will show character “s x”; such as address
setting is 3,it will display‘S3’,which tells the landing call board is used as a car call board on third station. A few seconds
after the landing call powered on,it will display normally. If there is no communication, landing call display will be off.
During normal running, landing call board will display current floor (actual floor) and running direction. If lift runs error,
landing call board will alternatively blink error code and current floor number. For example, #3 error will be a blink “E 3”. If
there are a few errors occur at the same time, the minimum error code number will show first.
137
Shanghai Sumpo Electric SP5000F Series Elevator Integrated Controller
4 4
3 3
2 2
1 1
139
SP5000F Series Integrated Control System Instruction
Operation Instruction
Te c h n i c i a n s i n e l e v a t o r d e s i g n , i n s t a l l a t i o n , c o m m i s s i o n i n g , m a i n t e n a n c e a n d
technical support related with the product should carefully study this instruction,
and please appropriately retain it for future reference.
Postcode: 201703
Fax:+86-21-69755902
Email:sales@sumpo-lift.com
In the same time of the product improvement, if there are modification for system function and relative
documents, we reserves the right to amend the relevant content without prior notice
July, 2013