HEC0500PA - 2016 - E - v04

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Specification and Manual

Customer :
Description : Air Conditioner for Equipment (Through Wall Mounting)
Customer Part No. : Rev.:
Delta Model No. : HEC0500PA Rev :
Sample Date Code:
Sample Issue Date :

Please send one copy of this specification back after you


signed approval for production pre-arrangement

Approved by :

Date :

DELTA ELECTRONICS, INC.


252, SHANG YING ROAD, KUEI SAN TEL : 886-(0)3-3591968
TAOYUAN CITY 333, TAIWAN FAX : 886-(0)3-3591991
Part no. :
Delta model no. : HEC0500PA

Table of content

Description.......................................................................................................................................... 3

Packing & Shipping ........................................................................................................................... 3

Safety Notes....................................................................................................................................... 3

1. Product Instruction .................................................................................................................... 7


1-1. General Description .......................................................................................................... 7
1-2. Main Feature & Model Number ....................................................................................... 7
1-3. Dimension........................................................................................................................... 9
1-4. Mounting Panel Cutout ................................................................................................... 10
1-5. Configuration & Maintenance ........................................................................................ 11
1-6. Thermal and Airflow ........................................................................................................ 12

2 Electrical Specification ........................................................................................................... 13


2-1. Indicator & Connector ..................................................................................................... 13
2-2 Protection........................................................................................................................... 14

3. Environmental Condition ........................................................................................................ 15

4. Reliability Table ........................................................................................................................ 16

5. Safety Certification .................................................................................................................. 16

6. Accessory ................................................................................................................................. 16

7. Parameters Table .................................................................................................................... 17


7-1. System Setup................................................................................................................... 17
7-2. Alarm Logs & Fault Processing ..................................................................................... 18

8. Installation Notice .................................................................................................................... 20

9. Warranty ................................................................................................................................... 20

10. Reclaim ..................................................................................................................................... 20

Page 2
Part
P no. :
Delta
D model no. : HE
EC0500PA

Descripttion
This d
document is i an installlation and the charac cteristics of
o Delta HE
ECX1P serries. Before e
installling the un
nit, please read this manual th horoughly, and follow wing the instructionss
contained in it. The docu ument is tthe exclusive properrty of Delta ta Electronnics, Inc. it
should d not be distributed,
d reproduce ed, or any
y other form mat withouut prior perrmission of
Delta.. Specifications are subject
s to cchange witthout noticee.

Packing & Shipp


ping
Duringg handling g or transpo ort, air con
nditioner must
m be kep pt in upwarrd positionn, “NOT”
inverted, flat, orr subject to
o excessive e tilt and collision.
c Thhe air condditioner is a precision
n
instrument; it shhould be handled and d transporrted with ca are. Do nnot stand on o the boxx,
ace heavy objects on
or pla o top of tthe box. Pay P attentiion to the below ico ons on the e
packaage.

If air cconditioner is toppled


d, slanted or dropped, follow th hese stepss: a. stand unit up for
12 ho ours to ennsure refriggerant pre
essure stab bility, b. po
ower on thhe unit an nd execute e
self-teest to makee sure no alarm
a conddition, c. keep the air conditionner runningg for 1 hour
to ma ake sure there is no abnormal
a a
acoustic no oise.

Safety N
Notes
Pleasse read the e safety nootes carefu
ully before installing the
t air connditioner, and be sure e
to install it corre
ectly. After completin g installation, check that the uunit operate
es properlyy
duringg start-up operation.
o
Meaning of WAR RNING and CAUTIO ON notices::

W
Warning:
F
Failure to fo
ollow these
e instructio
ons properlly may result in persoonal injury or loss of
liffe.

C
Caution:
F
Failure to observe
o th
hese instru
uctions pro
operly may
y result in property damage
d or
p
personal injjury, whichh may be s erious dep
pending on the circum
mstance.

Page 3
Part no. :
Delta model no. : HEC0500PA

Warning:
1. Installation work and electrical wiring should be done only by qualified personnel in
accordance with all applicable codes, standards and national wiring regulations.

2. Use this unit only in the manner intended by the manufacturer. If you have questions,
please contact the manufacturer.

3. Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shock or fire.

4. Make sure that all wiring is secured, that specified wires are used, and there there is no
strain on the terminal connections or wires.

5. If refrigerant gas leaks during installation, ventilate the area immediately. Do not directly
touch refrigerant that has leaked from refrigerant pipes or other areas, as there is a
danger of frostbite.

6. Before serving or cleaning unit, switch power off and disconnect power supply.

7. When cutting or drilling into wall or ceiling, do not damage electrical wiring or hidden
utilities.

8. Be sure to use only the specified accessories and parts to complete installation.

9. Protective grounding connection: The enclosure must be grounded at the protective


ground terminal. Use 2.5 mm2 (14 AWG) wire and use spring washer to avoid loosening.

10. The air conditioner should not be accessible to the general public.

11. The installation must contain a device to disconnect all poles of the air conditioner from
the power supply. The contact distance in all poles must be 3 mm minimum.

12. To reduce the risk of electrical shock: Means for disconnection must be incorporated in
the fixed wiring in accordance with the wiring rules.

13. This appliance is intended for use only by qualified personnel.

Page 4
Part no. :
Delta model no. : HEC0500PA

Caution :
1. Install the air conditioner on a wall or door strong enough to withstand the weight of the
unit.

2. Do not allow a child to mount onto the outdoor unit. Avoid placing any object on it.

3. Do not block the air inlets or exits.

4. Do not install the air conditioner at any place where there is a danger or flammable gas
leakage.

5. Arrange the drain to ensure complete drainage.

6. To avoid injury, do not touch the air inlet or aluminum fins of the unit.

7. Watch your step at the time of fin cleaning or air conditioner inspection.

8. Do not topple the air conditioner while moving or in storage.

9. The hole in the bottom of the air conditioner should be connected to a sealed container
through a drain pipe.

10. This appliance is not to be used by any persons with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have been given
proper supervision or instruction.

11. Children should be prevented from playing with the appliance.

Page 5
Part no. :
Delta model no. : HEC0500PA

Specification for Approval


Customer :
Description : Air conditioner for Equipment with 500 W Rated Cooling Capacity (Through
Wall Mounting)
Customer P/N : Rev. :
Delta model no. : HEC0500PA Rev. :
Sample revision. : Date Code :
Sample issue date : Quantity : one sets

INTERNAL EXTERNAL

Page 6
Part no. :
Delta model no. : HEC0500PA

1. Product Instruction

1-1. General Description


HEC0500PA is a DC air conditioner with 48 VDC power input, it is designed for IP55
sealed outdoor telecom cabinet to provide stable and optimum internal conditions for
equipment and avoid hotspot inside the cabinet.

HEC X1 P A - XXX
(1) (2) (3) (4) (5)

No Item Digit Specification


(1) Product Message HEC Compressor Air Conditioner
(2) Cooling Capacity X1 X1=0500
(3) Operation Voltage P DC 48V for door
(4) Product Version A N/A
(5) Customer ID XXX N/A

1-2. Main Feature & Model Number


Dimensions, Weight & Mounting method
Dimension (H x W x D) (without flange) mm (inch) 545 x 320 x 170 (21.5 x 12.6 x 6.7)
Application Outdoor
Weight Kg (lbs) 16.0 (35.3)
Mounting Method Door/Side
Color (optional) RAL7035
Environmental Protection & Performance
Operating Temperature Range °C (°F) -10 to +55 (+14 to +131)
External : 0~100% RH
Operating Humidity
Internal: 0~80% RH
Storage Temperature °C (°F) -40 to +70 (-40 to +158)
Storage Relative Humidity RH 5~95%
Refrigerant R134a, 285 g±10 g
Protection for Dust ,Wind and Water (External) IEC 60529 /GR487 IP55 / GR487
Noise (1m) dB-A 61
Operating Status N/A LED Indicator / Display Board
Cooling Capacity & Operational Data
Rated Cooling Capacity at L35/L35 W (Btu/hr) 550 (1800)
Rated Cooling Current A 3.5
3
Rated Internal Airflow (L35/L35) m /h (CFM) 230 (135)
3
Rated External Airflow (L35/L35) m /h (CFM) 150 (90)

Page 7
Part no. :
Delta model no. : HEC0500PA

Power & Range


Input Voltage VDC 48
Max. Operating DC Current A 8.3
Alarm N/A Dry Contact Output
Key Components
Controller Built-in Smart Controller
Fans Delta High Efficiency Blowers
Compressor Rotary, DC

Page 8
Part no. :
Delta model no. : HEC0500PA

1-3. Dimension

mm (inch)

(1) Material : Case SGCC Sheet


(2) Finish : Power paint 75~120um,
(3) Color : RAL 7035
(4) Dimension tolerance:
X.X [X.XX] : ± 1.0mm [0.04”]
X.XX [X.XXX] : ± 0.3mm [0.012”]

Page 9
Part no. :
Delta model no. : HEC0500PA

1-4. Mounting Panel Cutout

Outside

Gasket

Inside

CL

mm (inch)

Page 10
Part no. :
Delta model no. : HEC0500PA

1-5. Configuration & Maintenance


Make sure the air conditioner surface sealed with mounting flange to avoid water
penetrates into shelter through mounting interface. It is suggested to use gaskets
sticking on the mounting flange and seal the gap between flange and cabinet with
silicone gel during installation. There should be NO any gap surround gaskets to avoid
water penetrates into enclosure.
The air conditioner is composed as the following key components: they are chassis,
cover, controller, heat exchanger, blowers and compressor etc. It is “not” recommended
that the user replace the compressor, evaporator, and the condenser by themselves; it
may damage the system and getting injured.

NO. Q'TY DESCRIPTION


1 1 Case Chassis
2 1 Case Cover
3 1 Control Board
4 1 DC Power Board
5 1 Compressor
6 1 Condenser
7 1 Evaporator
8 1 External Fan
9 1 Internal Fan

In order to assure the air conditioner running at optimal condition, the condenser should
be cleaned once annually at least; user can clean the condenser with water directly. The
external side fan blade can also be cleaned with normal pressure water if there is dust
accumulation. Please do not use strong water jet to impact the center of fan and the
surface of condenser.
The bottom hole of the air conditioner should be connected to a sealed container through
a drainpipe, please clear drain holes when the maintenance. Please also notice that:

1. Check wires are connected correctly, and the insulation is not cracking or broken.

2. Use Self-test to check the unit running correctly or not. And the supplied air of internal
side should be as cooled air.

Page 11
Part no. :
Delta model no. : HEC0500PA

3. Do not wipe the product with organic solvent, volatile substances like toluene or
gasoline, it will destroy the powder-coated surface.

4. Turn off the power before maintaining.

5. Please turn off power and remove dry contact connector while non-operating for a long
time.

6. If any abnormal acoustic noise from air conditioner happened, please turn off the
product and contact with customer services.

7. The refrigerant is environmental friendly product of R134a. Little refrigerant leakage (< 5
g/ year) is allowed for application. If refrigerant leakage seriously, please turn off the
power and wait for at least 2 hours to make sure the refrigerant fully exhaust. Please
also contact the services to replace spare parts.

8. The compressor electrical protecting cover is sealed with silicon for IP55 requirement.
Please do not dismantle the sealed cover or will lose the quality assurance of the
compressor.

1-6. Thermal and Airflow


Internal and external air flow circulation is shown in below diagram. Counter flow design
prevents mixing of internal and external air flows, but waste heat can still be dissipated
from cabinet to the ambient outside air. An internal temperature sensor has been placed
in the return air stream to provide reliable temperature measurement, and for safe
operation.
The heated air inside the cabinet will be cooled by the evaporator. Waste heat absorbed
by the refrigerant will be dissipated through the condenser at the external side.

Page 12
Part no. :
Delta model no. : HEC0500PA

2 Electrical Specification
2-1. Indicator & Connector
 Power Supply & Alarm Connector

Pin Description Cable wire size Pin 5 Pin 1


1 DC 14 AWG
2 -48 V 14 AWG
3 N/A N/A
-48V DC
4 Alarm+ COM.
5 Alarm- N.C or N.O

 System alarm default setup

Note: Customers can setup the N.O or N.C by themselves when any alarm happen
through display board (d1.6 Dry-contact Setup).

• Specification:
Contact rating: 60 Vdc, 100 mA
• Normal:
PIN 3 and PIN 4 dry contact output close
• Any alarms happening:
PIN 4 and PIN 5 dry contact output open

 Case Grounding

Page 13
Part
P no. :
Delta
D model no. : HE
EC0500PA

 P
Panel operration

• A: Diisplay:

Indica
ates the tem
mperature inside the cabinet orr system p arametric setup.

• B: LE
ED indicato
or:

Pow
wer:
 When the
e system p
powers on, the LED will
w be solidd green.

 If LED ind
dicates ala
arm, the nu
umber of fla
ashes helpps identify root
r cause.

mp.:
Com

 When the
e compresssor is runn
ning norma
ally, the LED
D will be solid green.

 If the system goes iinto self-te


est mode, the LED wiill flash gre
een.

Fan (In):

 When the g normally, the LED w


e inner fan is running will be solid
d green.

Fan (Out):

 When the
e outer fan
n is running
g normally, the LED w
will be solid
d green.

• C: Tou
uchpad co
ontrols:
 ↑: UP or increase
i
 ↓: DOWN N or decrea
ase
 SET: Parametric seetup
 ON/OFF ESC: Pow wer on/off or
o back

2-2 Protec
ction
 O
Over Curre
ent Protec
ction:
DC powwer board: 20 A

 O
Over Temp
perature Protection:
P :
o
DC pow
wer board: 95 ± 4 C

Page 14
4
Part no. :
Delta model no. : HEC0500PA

 Under Voltage Protection:


DC power board: 40 ± 1.4 VDC

 Reverse Polarity:
Allow reverse voltage: 42 ~ 58 VDC

 Short Ckt:
If compressor UVW short for any both phase the compressor will not operate.

 Compressor H/T Protection:


Tcomp ≧ 105 oC

 Eva L/T Protection:


TEVA < 0 oC

 Power on Delay for Fans & Compressor:

3. Environmental Condition
 Operating Temperature
-10 °C ~ +55 °C (14 °F ~ 131 °F)

 Storage Temperature
-40 °C ~ +70 °C (-40°F ~ 158 °F)

 Operation Humidity
External air loop: 0 ~ 100 % RH
Internal air loop: 0 ~ 80 % RH, non-condensing

 Ingress Protection Rating


IP55 (IEC60529) on external side
GR487 on external side

Page 15
Part no. :
Delta model no. : HEC0500PA

4. Reliability Table
Test item Condition
High temperature IEC 60068-2-2
Low temperature IEC 60068-2-1
High temp. / High humidity IEC 60068-2-3
Temperature cycle IEC 60068-2-14 test Nb
Vibration ETSI 300 019-1-4 CLASS 4.1
Ingress protection (external side) IEC 60529 IP55 / GR487
Salt fog test (external side) IEC 60068-2-11 severity 4 , 6cycles
Package bump IEC 60068-2-29

5. Safety Certification
TUV, CE

6. Accessory
• Power and Alarm Cable
Pin Description Cable wire size
1 DC 14 AWG PIN1(+)
2 -48 V 14 AWG PIN2(-)

3 N/A N/A
4 Alarm(COM.) 24 AWG
5 Alarm(N.C or N.O) 24 AWG

Page 16
Part
P no. :
Delta
D model no. : HE
EC0500PA

7. Para
ameters Table
7-1. Syste
em Setup

Item System Parameter


P Deffault Ran
nge
d1.1 S
System Verrsion 2.5
2 N//A
d1.2 A
Alarm Logss 0.0
0 N//A
d1.3 In
nside over--temp. Settup 0 oC
60 40 oC - 70 oC
d1.4 A
Auto Self-T
Test Functio
on Ena
able Enable/Disable
d1.5 R
Recovery Default
D N/A
N N//A
d1.6 P
Photo Coup
pler Norma
al Status Clo
ose Close//Open
d1.7 P
Password 000 000~
~999
d1.8 S
System Re--lock N/A
N N//A
d2.1 T
Target temp
perature 0 oC
30 25 oC - 40 oC

Page 17
7
Part no. :
Delta model no. : HEC0500PA

7-2. Alarm Logs & Fault Processing

• Alarm Indicators
Flash Times
LV1 Alarm LV2 Alarm Alarm Code
(Power Led)
Compressor 3-min Protection
-- -- Compressor Power Protection --
Low-Temp Startup Protection
Eva Temperature Protection 2.1
Comp-out Temperature Protection 2.2
Temperature Abnormal
2 PWB Temperature Protection 2.3
Alarm
IPM Temperature Protection 2.4
Amb Temperature Protection 2.5
Amb Temperature Sensor 3.1
Eva Temperature Sensor 3.2

Temperature Sensor Cond Temperature Sensor 3.3


3
Fault Comp-Out Temperature Sensor 3.4
PWB Temperature Sensor 3.5
IPM Temperature Sensor 3.6
Indoor Fan 4.1
4 Fan Fault
Outdoor Fan 4.2
EEPROM 5.1
5 Controller Fault Current Sensor 5.2
DC-Bus Voltage 5.3
Power Board 6.1
Startup Fail 6.2
6 Cooling System Fault
IPM Over Current 6.3
Compressor Lack Phase 6.4

Page 18
Part no. :
Delta model no. : HEC0500PA

• Fault Analysis and Processing

Fault State Analysis of the Reasons Solutions


• Check the power supply and
• Power failure or no
Power on, and the the electric circuit.
power.
cabinet temperature • Re-set the target temperature
• The target temperature is
is too high but the air according to the system
higher than inside
conditioner is not requirement.
temperature.
working • Please contact Delta or
• System failure.
authorized Delta service agent.
• The air conditioner • Check the heating load of the
The air conditioner is capacity is not match the system.
running but the load of the system. • Ensure the air conditioner is
cabinet temperature • The ambient operating in correct
is still high, no temperature is too high. temperature range.
obvious cooling • Low efficiency of the • Clean the condenser.
effect. condenser. • Please contact Delta or
• Other system failure authorized Delta service agent.
• Re-set the target temperature
The air conditioner • The inside temperature
according to the system
stop operating, and is lower than the target
requirement.
there is no alarm temperature.
• Please contact Delta or
signal. • Other system failure.
authorized Delta service agent.

Page 19
Part no. :
Delta model no. : HEC0500PA

8. Installation Notice
Check the surrounding obstacles to make sure the product get enough space for air
circulate.

9. Warranty
Delta Electronics, Inc warrants one year (twelve months) from the date of shipment, this
warranty covers customer below application: Customer follows Delta specification to
install and operate the product. The product and any parts do not be modified (including
both mechanical and electrical modification) by customer themselves .This warranty
cover only repair, replacement or refund for defective Delta products does not include
any loss of data or any costs associated with determining the source of system
problems, costs for transportation, removal or reinstallation of equipment or labor for
repairs or replacement made in the field.

10. Reclaim
At the end of the unit working life, the produce must not be disposed of as urban waste.
It must be taken to a special local authority differentiated waste collection center or to a
dealer providing this service.