Locomotive: Service Manual
Locomotive: Service Manual
Locomotive: Service Manual
LOCOMOTIVE 6
SERVICE MANUAL
ELECTRICAL EQUIPMENT
123455 6-1
Section 6
Electrical power from the main generator is distributed All low voltage direct current electricity required during
to traction motor mounted in the trucks. Each motor is locomotive operation comes from the auxiliary
geared to a pair of wheels, with the gear ratio selected generator. This current is used for battery charging and
for the type of service intended. The motors are cooled for excitation of the I)14 alternator as well as for
by means of an external blower located in the energizing control circuits and actuating electrical
locomotive unit and mechanically driven from the
engine.
123455 6-2
Section 6
switchgear. The auxiliary generator is a self-excited located outside of the stator. Motor and fan rotating
machine that uses residual magnetism for initial speed are directly proportional to the AC frequency of
excitation. To hold voltage at a constant 74 volts, a the D14 alternator which in turn is dependent upon
static type voltage regulator is used in the field engine speed.
excitation circuit. The regulator is packaged as a plug-in
circuit module VR, and is provided with a voltage
adjustment for battery charging purposes.
123455 6-3
Section 6
123455 6-4
Section 6
used by the operator of the locomotive. The air brake dynanlic brake rheostat, which is part of' the controller
valves and handles are at the left side of the stand, with assembly. Mechanical interlocking prevents the
the controller assembly to the right. Various gauges and dynamic brake handle from being moved out of the
indicating lights are located above the controller, and OFF position unless the throttle is at IDLE: and the
various operating switches are adjacent to it or below. reverser handle is positioned for either forward or
reverse operation.
CONTROLLER ASSEMBLY, Fig. 6-9
CAUTION: During transfer from power operation to
The controller contains the three main operating dynamic braking, the throttle must be held
handles: throttle, reverser, and dynamic brake. in IDLE for 10 seconds before moving the
Nameplates identify each handle. and the positions of dynamic brake handle to the SET UP
the throttle and dynamic brake handles are indicated in position. This is to allow time for decay of
illuminated windows located directly above those magnetic flux and preclude a sudden surge
handles. The controller assembly is hinged to the of braking effort with possible train run-in
control stand, and can be swung down for maintenance or motor flashover.
and troubleshooting.
Throttle Handle
The throttle is the middle handle on the controller
panel. It is moved from right to left to increase engine
speed and power. The handle grip is somewhat out of
round, with the flattened surfaces horizontal to
distinguish it from the dynamic brake handle, which has
its flattened surfaces vertical. The throttle has nine
detent positions: IDLE, and I through 8 plus a STOP
position which is obtained by pulling the handle
outward and moving it to the right beyond IDLE to stop
all engines ill a locomotive consist. Mechanical
interlocking prevents the throttle handle from being
moved out of" IDLE when the dynamic brake handle is
advanced to SET H' or beyond. car when the reverser
handle is centered and removed from the controller.
Reverser Handle
Fig. 6-9 - Locomotive Controller With Handles
Positioned For Dynamic Braking The reverser handle is the lowest handle on the
controller panel. It has three detent positions: left,
Dynamic Brake Handle centered. and right. When the handle is moved to the
right toward the short hood end of the locomotive.
A separate handle is provided for control of dynamic circuits are set up for the locomotive to move in that
brakes. It is uppermost on the controller panel and is direction. When the handle is moved to the left. toward
moved from left to right to increase braking effort. The the long hood end of the locomotive, circuits are set up
handle grip is somewhat out of round with the flattened for movement in that direction. With the reverser
surfaces vertical to distinguish it from the throttle handle centered. mechanical interlocking prevents
handle, which has its flattened surfaces horizontal. The movement of the dynamic brake handle, but the throttle
brake handle has two detent positions: OFF and SET handle can be moved to increase engine speed. In such
UP, and an operating range through which the handle case power will not be applied to the traction motors.
moves freely without notching. The handle is in the but a load test may be made if the proper circuit setup is
OFF notch when positioned fully left. The SI:T UP made.
position is one notch to the right of OFF. When the
handle is moved to the right out of the SET UP notch, it The reverser handle is centered all(] removed from the
can then be moved without notching to positions 1 panel to lock the throttle in IDLI:: position and the
through FULL 8 to increase the signal from the dynamic brake handle in OFF position.
123455 6-5
Section 6
LOAD CURRENT INDICATING METER The indicating light assembly consists of a rectangular
aluminum plate with six 1/2" drilled holes to accept
This meter indicates current through the No. traction holders for grooved-base subminiature lamps. Limiting
motor. Since all motors will carry approximately equal resistors of high wattage are also affixed to the plate.
current, main generator current will be three times the The lamp holders form the front part of the press-to-test
meter indication during series-parallel operation, and assemblies, and a printed circuit board equipped with
six times the indication during full parallel. The meter Faston tabs is connected to the backs of the switches.
indicates from zero to 1500 amperes during power The tabs are wired to appropriate locomotive circuits.
operation, with a red zone indicating maximum allow-
able continuous motor current, beginning at 1050 Translucent phenolic lens caps, either white or colored,
amperes. and identified by black block letters, fit over the lamps
and into the switch assemblies. When finger pressure is
On units equipped with dynamic brakes, the meter has a applied to the lens caps, the switches close to test the
dial with the zero point located at top center. During lamps. A fiberglass guard formed to accept and retain
power operation the meter needle moves clockwise the lens caps is bolted to the aluminum plate to
from zero to indicate increasing motor current. During complete the indicating light assembly.
dynamic braking the meter needle moves
counterclockwise from zero to indicate increasing NOTE: A delay of about one second occurs between
dynamic braking current. pressing the indicating lens cap and
illunnination of the indicator.
AIR SYSTEM GAUGES
WHEEL SLIP light indicates moderate to severe wheel
Duplex gauges provide indication of various air brake slip, locked sliding wheels, or circuit difficulty.
system pressures. Depending upon conditions, the light will flash
intermittently or come on and go off at regular
INDICATING LIGHTS PANEL, Fig. 6-10 intervals.
Indicating lights alert the locomotive operator of NOTE: On locomotives equipped with locked wheel
various operating conditions. The panel assembly is detecting equipment and an LW module, a
located adjacent to the upper left corner of the locked wheel will cause the WHEEL SLIP light
controller. It has provision for six press-to-test lights to light and remain lit and the alarm bell to
(three basic, and from one to three additional as sound. In addition, LOCK WHEEL indications
required by the use of special equipment on the independent of the wheel slip protective circuits
locomotive). are provided.
123455 6-6
Section 6
GROUND RESET AND ATTENDANT CALL WARNING: On units not equipped for automatic self
PUSHBUTTONS loading, the main generator will he open
circuit during a load test setup unless an
These pushbuttons are located at the lower portion of external loading resistor grid is connected.
the control stand.
During CIRCUIT CHECK position of the
test switch, tile generator field circuit
SAND No. 1 TRUCK SWITCH
breaker must he in off position to prevent
excitation of the main generator.
This switch provides continuous sanding at the leading
wheels of the locomotive.
Do not return the test switch to NORMAL
position until the throttle is in IDLE
BRAKE VALVE HANDLES position.
The upper handle controls the automatic or train brakes.
HV GRD/FAULT Light
The lower handle controls the independent or
locomotive brakes.
Indicates that an electrical path to ground has occurred,
or that a group of five diodes in the main generator has
ELECTRICAL CABINETS failed. The light is held on until a reset button is pressed
or an automatic reset is made on locomotives so
HIGH VOLTAGE CABINET, Figs. 6-11 and 6-12 equipped.
The high voltage cabinet houses the majority of the NO BATT CHARGE NO POWER Light
locomotive electrical switchgear and static devices. The
front of the cabinet forms the rear wall of the Indicates that no AC power is being delivered from the
locomotive cab, and the rear of the cabinet forms one auxiliary alternator to a voltage sensing relay. This may
wall of the central air compartment of the locomotive. be due to a tripped generator field circuit breaker,
engine shutdown, alternator failure, or failure of the DC
The lower front portion of the electrical cabinet houses auxiliary generator which excites the alternator. If the
heavy duty switchgear used to connect the main light is on for reasons other than engine shutdown,
generator to the traction motors. Devices that sense engine speed and power are reduced to idle conditions.
current and voltage are generally located in this portion
of the cabinet. HOT ENGINE Light
ENGINE CONTROL PANEL, Fig. 6-13 Indicates that engine coolant temperature is excessive.
Engine speed and power are automatically reduced to a
The engine control panel contains various switches and lower level until proper temperature is restored.
warning lights. Brief descriptions of the switch and
123455 6-7
Section 6
123455 6-8
Section 6
123455 6-9
Section 6
123455 6 - 10
Section 6
GOVERNOR SHUTDOWN Light units. Tire switch must be properly positioned in all
units of a consist.
Accompanied by engine shutdown for one of the
following reasons: ISOLATION SWITCH
1. Excessively hot lube oil. This switch allows any unit in a locomotive consist to
be "taken off' the line" regardless of the control signals
This type of shutdown will normally be preceded from tile controlling unit. Tire switch has two positions.
by a hot engine light indication. No other
indication is given except an extremely hot 1. START/STOP/ISOLATE: Position
condition of the engine and cooling system. Do
not attempt to restart the engine until it has been Must be in this position before the engine can be
allowed to cool down and an engine inspection started, but tile unit will not develop power.
has been made by qualified personnel. However, it' a controlling unit of a multiple unit
consist is isolated, all trailing units will still
2. Low engine oil pressure. respond to tile controls of the controlling unit.
Low oil level, or failure of the lube oil pump may It is recommended that the isolation switch be
bring about this type of shutdown. The low oil placed in this position before stopping the engine,
plunger on the engine governor will protrude, but the switch in no way negates any engine
with no other fault indication given. stopping switch or device.
unit consist or to cut out a faulty dynamic braking CIRCUIT BREAKER PANEL, Fig. 6-14
system while allowing operation under power.
The following circuit breakers must be closed for
LIGHT SWITCHES locomotive operation.
Fig. 6-14 - Switch And Fuse Panel And Circuit Breaker Panel
123455 6 - 12
Section 6
Single pole breaker protects the field circuit to the Two-pole breaker for radio circuits.
auxiliary generator.
AUTO WATER DRAIN
MODULE CONTROL
On special order the cooling system will drain
Two-pole breaker protects low voltage DC circuits to automatically when coolant temperature in the area of
control modules. the cab heaters approaches freezing. This two-pole
breaker protects the circuits.
REV CONTROL
A.T.C.
Two-pole breaker protects motor operated switchgear
motor circuit. Two-pole breaker protects automatic train control
circuits.
AC CONTROL
UTILITIES
Two-pole breaker protects circuit supplying D14 AC
Protects miscellaneous special equipment.
power to control modules, various transductors, and the
no voltage relay NVR. SWITCH AND FUSE PANEL, Fig. 6-14
NOTE: There is no alternator field fuse. The D14 field
BRAKE TRANS. CONTROL
is connected directly across the output of the
Two-pole breaker protects motor operated switchgear DC auxiliary generator in order to minimize
motor circuit. any voltage drop in the cabling and thus
maintain full D14 excitation and ensure rapid
GENERATOR FIELD fan motor starting. If a short circuit appears
across the output of the auxiliary generator, the
Two-pole breaker protects circuit supplying D14 AC
machine being self excited will not support the
power to the main generator controlled rectifier SCR.
short. Voltage will come down and the machine
will not be harmed. A "no power" alarm will be
AUXILIARY GENERATOR
given, and engine speed and power will be
On special order this single pole breaker is used in reduced to idle condition.
place of the auxiliary generator fuse.
FUSE TEST EQUIPMENT
FILTER BLOWER MOTOR A fuse test block and test lamp are provided, with a
switch to test the lamp. Always test fuses before
Two-pole breaker protects the inertial filter exhaust
installing them.
blower motor circuit.
GROUND RELAY CUTOUT SWITCH
The following circuit breakers are placed on as
The purpose of the ground relay cutout switch is to
required.
eliminate the ground protective relay from locomotive
circuits during certain shop maintenance inspections.
CAB HTR.
The switch is a three-pole device, with one pole
Two pole breaker protects cab heater fan motor circuit. performing the cutout function. The other poles prevent
locomotive operation with the ground relay cut out.
LIGHTS
AUXILIARY GENERATOR FUSE
Two-pole breaker protects the various light circuits.
A 150 ampere fuse is installed to protect the basic
HDLTS.
auxiliary generator. A 250 ampere fuse is used for the
heavy duty auxiliary generator.
Two-pole breaker protects the headlight circuits.
123455 6 - 13
Section 6
CAUTION: The 250 ampere fuse is the same physical 1. Hot Engine
size as the higher rated starting fuse. Do
not interchange the fuses. 2. Engine Air Filter Plugged.
A 400 ampere fuse is installed to protect the starting 4. Excitation Limit Operated.
motors. The fuse is in use only during engine cranking.
Units with dynamic brakes provide additional
CAUTION: On some locomotives the cranking motors indications.
are connected in parallel and require an
800 ampere starting fuse. Do not install an 5. Grid Overcurrent.
800 ampere fuse in locomotives with
cranking motors connected in series. 6. Motor Overexcitation.
MAIN BATTERY KNIFE SWITCH 7. Grid Open Circuit. (Operative only on units with
extended range brakes.)
This switch connects the battery to the locomotive low
voltage system. The switch must always be closed On special order the following indication may be
during locomotive operation. It may be opened during applied.
shop inspections and locomotive layover.
8. Grid Blower Failure.
CIRCUIT MODULES, Fig. 6-15
9. Dynamic Brake Ground.
Each circuit module contains components and wiring
for one or more locomotive control functions. The DE CIRCUIT MODULE - Extended Range Brake
components are mounted on one or more circuit boards. Control
All circuit boards are of the same size, and terminals on
the boards are placed on a common grid pattern. The During dynamic braking a signal from the brake control
boards are fitted with receptacle strips arranged in a rheostat is compared at the SB module with the main
vertical plane, and as the board is inserted into generator feedback signal from the PF module. Main
guideways and fully seated, the receptacles mate with generator excitation is regulated as a result of this
pins that are connected to terminal strips. Cabinet comparison and main generator regulation results in
wiring completes the circuit connection. motor field and braking current regulation. During
extended range dynamic braking the feedback signal
Face plates and handles are attached to the circuit from the PF module is compared also with a signal
boards, and test points are located on the face plates. In from brake current transductor BCT, and when the BCT
addition to the test points the face plates may contain signal falls below the PF feedback signal (indicating
test buttons and lights. less dynamic braking grid current than called for by
braking lever position) the DE circuits operate to
AN CIRCUIT MODULE, Fig. 6-16 -Fault Annunciator energize a grid shorting contactor. The grid shorting
contactor decreases total dynamic braking grid
The annunciator records, by means of latching relays resistance, and more current flows in the grids.
and lights, faults or abnormal operating conditions that
occur during locomotive operation. Once lit, the The DE circuit module also compares the BCT signal
annunciator lights will stay on until a guarded reset with the brake rheostat signal during extended range
switch is operated by a qualified maintenance man. braking. When the BCT signal exceeds the level called
Correction of a fault or resetting of protective devices for by the brake rheostat, a DE circuit activates the
does not reset the annunciator. brake regulator circuit in the DR module and holds
dynamic braking current at a maximum established by
The basic annunciator provides the following braking handle position.
indications.
123455 6 - 14
Section 6
123455 6 - 15
Section 6
123455 6 - 16
Section 6
The response of the main generator and the main WO CIRCUIT MODULE Wheel Speed Sensing
generator control system is so fast that sudden changes
in the level of reference voltage would result in rough The wheel overspeed module WO consists of
train handling. The RC module makes use of an RC essentially two E-1 type relay circuits. The circuits are
(resistance-capacitance) circuit to smooth out power energized by a signal proportional to main generator
changes even though an abrupt change in reference voltage and are restrained (reverse biased) by a signal
signal occurs. proportional to main generator current.
SA CIRCUIT MODULE - Sanding One circuit (the RA relay circuit) is adjusted to indicate
a wheel overspeed condition, and acts as a backup to
The sanding circuit module is designed to accommodate the wheel slip system to protect against four-axle
a variety of sanding circuits selected by the railroads. A simultaneous wheel slip.
timing circuit is part of the module. It provides for time
delay sanding when a wheel slip is signaled. The test
button on the module is used to check time delay
sanding.
123455 6 - 17
Section 6
The second circuit (the RB relay circuit) is energized at correction is based upon a level value of wheel slip
mid-range speed to recalibrate the excitation regulation signal rather than a rate of change.
system and wheel slip system. The system allows a high
level of main generator excitation during train starting, The WS module is provided with a test button that is
then recalibrates the generator excitation module GX to operative with the unit isolated or with the throttle in
allow a safe level of continuous excitation. The wheel idle. When the test switch is operated a green light on
slip module WS is recalibrated to compensate for the the face of the module indicates with a high degree of
higher inertial forces at the wheels during slip at high probability that the wheel slip system is functioning
track speeds. properly. A red test lamp indicates that the WS module
is faulty.
VR CIRCUIT MODULE - Voltage Regulator
TEST PANEL, Fig 6-17
The locomotive low voltage system and equipment are
designed for operation on 74 volt DC power supplied The test panel located in the module compartment
by the auxiliary generator. This voltage must be kept contains terminals and receptacles that provide an easy
constant regardless of changes in engine (and generator) place to read significant test voltages during operation
speed. or test. The test selector switch has the following
positions.
The voltage regulator is used in the auxiliary generator
field excitation circuit and functions to vary excitation
as needed to hold output voltage constant despite speed
changes. This device functions entirely automatically
and should never be disturbed during operation. The
regulator utilizes solid state electronic components to
regulate auxiliary generator voltage. The regulator does
this by rapidly turning the generator field circuit on and
off. Time "on" in relation to time"off" establishes
auxiliary generator voltage. The regulator is called a
static voltage regulator because with the exception of a
starting relay it uses no moving parts.
123455 6 - 18
Section 6
123455 6 - 19
Section 6
Acts to supress a transient generated upon GFC COR; MOTOR CUTOUT RELAY
contactor dropout.
On units equipped for motor cutout the contacts of this
CCR, CRL; COMPRESSOR RELAYS relay perform a variety of functions to ensure proper
operation with a traction motor cut out. This involves
On units equipped with synchronization of all disabling a "P" power contactor and certain wheel slip
compressors in a consist, the compressor relays in all control circuits, changing the slope and position of
units of the consist are energized when the main air power control lines, and providing circuits around the
reservoir pressure in any unit falls below a preset level. interlocks that are not positioned because the related
The compressor relays in the individual units will motor is cut out.
remain energized until all reservoir pressures build up
to the normal level. CR; RECTIFIERS
123455 6 - 20
Section 6
CR37
Blocks backfeed from the SA module test circuit to the
governor overriding solenoid ORS.
CR41
Blocks rate control capacitor discharge through the T11
Module.
CR45
Blocks backfeed from ORS circuit.
123455 6 - 21
Section 6
Fig. 6-20 - Dynamic Brake Grid Shorting Contactor It is the function of the EQP relay to drop out the
generator field contactor GFC when protective devices
volts up to 350 and currents up to 2400. Contactor operate to back up faulty regulating devices. EQP
operation is controlled by the DE module and pilot dropout can occur through operation of the following:
relays.
1. DP circuit module brake warning and motor field
DGT; DYNAMIC GRID TRANSDUCTOR protective relays.
This transductor is constructed of the same basic parts 2. Through pickup of the excitation limit relay of
as the wheel slip transductors, but in addition is the EL circuit module.
equipped with a spool to accept and firmly hold several
turns of a cables leading to braking grid fan motors. In 3. Through pickup of the WO module RA relay
the event of a stalled fan or motor, or an open in the when wheel overspeed is sensed.
motor circuit, currents at the transductor create an
unbalance. The unbalance is sensed at the DG circuit 4. Through dropout of the generator field decay
module, and the braking power contactor is locked out. relay that is piloted by the ground relay.
A reset button on the DG circuit module will reset the
lockout after the fault has been corrected. All of the above accomplish rough regulation to enable
the locomotive to get over the road to a maintenance
DPI, 2, 3; DYNAMIC BRAKE PILOT RELAYS point. On the basic locomotive none of the devices lock
These relays are controlled by the extended range in after pickup. However, on special order the ground
dynamic brake control circuit module DE. They pilot relay can be made to latch after a specific number or a
the extended range dynamic brake power contactors DC specific rate of GR operations.
I , 2, and 3.
ER; ENGINE RUN RELAY
DPIA; AUXILIARY PILOT RELAY The function of the engine run relay is to set up control
Establish grid current control during extended range circuits to the governor speed setting solenoids.
dynamic braking. Units with extended range dynamic Therefore, if the engine run relay is de-energized by
brakes and no DP 1 A relay are equipped for full range placing the engine run switch in the OFF position or by
grid current control. operation of safety devices, the diesel engine will not
123455 6 - 22
Section 6
run above idle speed. Throttle response relays in the TH appropriate position. Contacts of the relay make or
module will, however, still respond to throttle position. break circuits using local control current to actuate
On the basic locomotive the engine run switch on the heavy duty motor driven transfer switches. The transfer
locomotive control stand must be in the on position switches establish the direction of high voltage main
before the engine run relay can be energized. On special generator current flow through traction motor fields.
order the engine run switch may be eliminated. On such Crossover wires at each of the jumper cable receptacles
units, operator's control of the engine run relay is between units of a consist are so arranged that whatever
provided by the isolation switch and the ground relay the makeup of the consist, the appropriate relays in
cutout switch only. trailing units will be energized.
This switch is located in a water manifold on the Use of this contactor relieves the fuel primeengine start
equipment rack. It senses engine water temperature and switch of fuel pump motor current load. Pickup and
picks up to indicate excessive temperature. Upon dropout of the fuel pump contactor are piloted by the
pickup it turns on the HOT ENGINE light and fuel pump control relay FPCR.
energizes the TH relay which operates to reduce engine
speed and power. Contacts of ETS also protect against FPCR; FUEL PUMP CONTROL RELAY
failure of other temperature sensing switches by
providing a backup feed to a cooling fan contactor. When the fuel prime engine start switch FP/ES is
placed in the START position, the FPCR is energized.
FCT; FIELD CURRENT TRANSDUCTOR FPCR contacts pick up to provide a holding circuit for
FPCR and to establish a circuit between the FPC coil
This transductor consists of two toroidal iron cores, and the auxiliary generator side of the battery charging
each with a 1000 turn test winding is also common to rectifier when the FP/ES switch is released. FPCR con-
both cores. The cores and windings are completely tacts also enable the circuit to the engine run relay ER
enclosed and hermetically sealed. D14 AC is impressed and set up the engine shutdown circuit to the governor
upon the windings, and a hole in the molded enclosure "D" solenoid.
admits a cable carrying current through the transductor
and to the generator field. When field current reaches a FPR; FUEL PUMP RELAY
specific level, output from the transductor causes the
GX module to go into a blocking state. Control current The primary purpose of the fuel pump relay is to
ceases to flow in the SE module (sensor) control provide the locomotive operator with the means of
windings and generator excitation is reduced. shutting off the fuel pump from a switch on the control
stand. Before the engine is running, the relay performs
FC1, 2; COOLING FAN CONTACTORS, no function, but it must be picked up to set up the fuel
Fig. 6-21 pump contactor circuit.
The cooling fan contactors operate to supply D14 AC CAUTION: The control and fuel pump switch must
power to the radiator cooling fan motors. They are always remain in the ON position while
controlled by temperature switches mounted in a water the engine is running. If an engine shuts
manifold on the equipment rack. down from lack of fuel, damage to the
engine injectors is possible.
FOR; DIRECTIONAL RELAY, FORWARD
123455 6 - 23
Section 6
FUSE, RADIATOR FAN MOTOR, Fig. 6-21 If an inspection reveals a single blown fuse, remove and
discard both fuses used to protect the motor. This is
These 200 ampere bolted lug-type fuses protect against done because the second fuse, while not indicated as
the following: blown, will in all probability be degraded and will blow
open the next time the fan is called upon to start.
1. Locked motor due to bearing seizure or icebound fan
blades. CAUTION: If for some reason a single fuse is to be
removed, always remove the other fuse to
2. Single phase motor windings. completely isolate the motor.
123455 6 - 24
Section 6
GPT; GENERATOR POTENTIAL maintain engine speed with regulation of power at the
TRANSFORMER(S) correct level for a given speed.
The ground relay is held in its tripped position by a Fig. 6-22 - Load Regulator
mechanical latch in the relay, It is reset by either
manually pressing the ground relay reset button on the LTT; LOAD TEST TRANSFER SWITCHES,
control stand or by an automatic reset device on Fig. 6-23
locomotives so equipped. The automatic resetting
devices also provide a reset lockout that prevents When the test panel switch is rotated to the LOAD
further resetting after a specific number of resets or TEST position, these switches operate to connect the
after a specific number of resets within a specific time main generator to the dynamic braking resistor grids.
period. They are located toward the back of the electrical
cabinet and are applied on special order when automatic
IPS; INDEPENDENT PRESSURE SWITCH load testing is desired.
Application of the locomotive air brake during extended MB: MOTOR BRAKE TRANSFER SWITCH,
range dynamic braking will actuate this switch and will Fig. 6-24
nullify extended range dynamic braking. This is done to
prevent the possibility of sliding wheels. This switchgear is used to transfer circuits from the
power mode of operation to the dynamic braking mode
LR; LOAD REGULATOR, Fig. 6-22 on locomotives so equipped. The device is made up of
motor driven gang operated switches rated at 1200
The load regulator is a plate type rheostat driven by a amperes and 1500 volts. There can be from two to six
hydraulically operated vane motor. A pilot valve in the double-pole double-throw switches per device. Being
engine governor controls a flow of engine oil under motor driven, once the switch is positioned, it will not
pressure to drive the vane motor clockwise or drop out. A positive feed is required to move the
counterclockwise through a maximum arc of about 300 contacts. When they do move, all poles operate
degrees, thereby positioning the rheostat brush arm and together, and a single interlock suffices to indicate the
regulating the output of the main generator by varying a position of all switches. This increases interlock
signal to a system that controls excitation of the gener- availability and allows complete protective
ator field. Control of generator field excitation results in interlocking.
control of the load on the engine. Load control of the
engine by the governor permits the governor to
123455 6 - 25
Section 6
123455 6 - 26
Section 6
123455 6 - 27
Section 28
ORS; OVERRIDING SOLENOID however, during normal operation current and voltage
values are far less when the power contactor opens. The
This solenoid is located within the engine governor. contactors are equipped with continuous duty series
When energized it operates the load regulator pilot electro-magnetic blowout and arc chutes that
valve, and causes governor oil pressure to drive the load accomplish arc blowout without arcing to ground. The
regulator to minimum field position. arc chutes are positive latching. They cannot be
misapplied, and power contactor interlocks will not
ORS is energized when protective devices operate, and function if the arc chute is removed. Contact tips are
during transition on units that require transition. A test trifurcated (the movable tip is made up of three
button on the TH module provides the means for movable fingers) for greater contact surface and are
checking governor control of the load regulator by made of alloy material with good conductivity that
energizing ORS. resists oxidation and erosion and maintains a low
operating temperature.
PCR: PNEUMATIC CONTROL RELAY
These contactors are energized and closed to connect all
The function of the pneumatic control relay is to reduce of the traction motors in full parallel with the main
engine speed and power to idle when an emergency or generator. Auxiliary contacts perform various functions
penalty application of the brakes occurs. in control circuits.
Contacts of the pneumatic control switch are normally This limiting resistor is installed to protect the auxiliary
closed in the circuit to the magnet coil of the pneumatic generator and battery charging circuit against high
control relay. When a penalty or emergency application currents in the event that the battery has a very low
of the air brakes occurs the PCS switch operates to charge.
interrupt the circuit to PCR. Engine speed and power go
to idle. When control of the air brakes is recovered, RE-DB; DYNAMIC BRAKING RESISTORS
PCS drops out, and PCR will pick up if the throttle is at
idle position. The faceplate type dynamic braking rheostat RH50
employes this resistor assembly to extend the capability
P_: POWER CONTACTORS, Fig. 6-27 of the rheostat.
Power contactors are rated at 1200 amperes 1500 volts RE; RESISTORS RE1
continuous, and can successfully interrupt current at
this value repeatedly without damage; Provides limiting resistance between the SCR assembly
and the AR 10 field during dynamic braking. This is
done to obtain improved control of the low field current
required during dynamic braking.
RE2
RE3A - B
RE4A - B
Fig. 6-27 - Power Contactor
Wheel slip relay WSR bridge circuit resistors.
123455 6 - 28
Section 6
123455 6 - 29
Section 6
power control system signals the amount of power that transfer switches will therefore not open while they are
SCR sends to the generator field. carrying current.
TA, TB; TEMPERATURE SWITCHES In the event of a locked-sliding wheel set, pickup of
WL contacts opens the wheel slip circuit feed to the
These switches are located in a manifold on the governor ORS coil. This is to prevent driving the load
equipment rack. They sense engine water temperature regulator near minimum field position where it would
and operate to activate cooling fan contactors. be held by wheel slip rate circuits, thus preventing the
required WL pickup and wheel slip light indications.
THL; THROTTLE LIMIT RELAY
WST; WHEEL SLIP TRANSDUCTORS
When for any reason a hot engine occurs, the engine
temperature switch ETS contacts close to sound the The transductor consists of two coils wound on
alarm bell, turn on the hot engine light on the engine independent iron cores. The coils are in series across an
control panel, and energize the THL relay coil. THL alternating current source - the D14 alternator. Cables
contacts turn on the hot engine light on the annunciator, carrying traction motor current pass within the frame of
and acts to reduce engine speed and power to the iron cores. The current in the cables is normally of
accomplish engine cooling if the hot engine was caused equal value and in opposite direction. When wheel slip
by a transient condition. If the hot engine was due to an occurs the currents are unbalanced, causing a change in
engine or system fault, the hot engine condition may magnetic fluxes in the cores. This results in a decrease
persist until engine shutdown is brought about by in the impedance of the coils and the impedance change
engine protective devices. is seen as a wheel slip signal at the WS module.
When the pressure drop across the combined filter across the carbody mounted inertial filters plus the
reaches 14 inches of water, the switch operates to engine air filter.
provide a signal to the AN module.
Electrical Cabinet
HOSE STEMS FOR
MANOMETER CONNECTION This hose stem opens directly to the inside of the
electrical cabinet. It is used to measure the pressure
Three hose stems are provided at the front of the drop across the electrical cabinet filters.
electrical cabinet.
Inertial Filters
Air Filters - Engine Plus Inertials
This opening is piped to the blower inlet side of the This opening is piped to the central air compartment. It
engine air filter. It is used to measure the pressure drop is used to measure the pressure drop across the carbody
inertial filters.
123455 6 - 31