Jin Xiu Unitary Controller Operation Manual

CONTENTS
.Display and Operation Overview .....................................................................................4
1.
1.1 Specification of the Controller Panel...............................................................................4
1.1.1 Display Content Summary........................................................................................4
1.1.2 Initial Display Example ............................................................................................4
1.1.3 Display Backlight Control ........................................................................................5
1.2. Description of Key Functions .........................................................................................5
1.3 Operation Menu ...............................................................................................................7
2. General Setting Menu..........................................................................................................8
2.1 Time Program(Only for UB4334SCH/EN)................................................................8
2.1.1 System Time Setting .................................................................................................8
2.1.2 Day Time Schedul Setting ........................................................................................9
2.2. How to Setting ..............................................................................................................11
2.2.1 Fan State Setting .....................................................................................................11
2.2.2 Parameters Setting ..................................................................................................11
2.2.3 The Setting of the Device Running Mode ..............................................................12
2.2.4 Display Contents Setting.........................................................................................13
2.2.5 Device Running State .............................................................................................15
2.3. Alarm ............................................................................................................................15
2.3.1 Alarm Signals..........................................................................................................15
2.3.2 Sensor Abnormality ................................................................................................15
2.3.3 Timeout Alarm (Only for UB2221CH/EN、UB4334SCH/EN) ............................15
2.3.4 Alarm Elimination ..................................................................................................16
2.4 System Information........................................................................................................16
2.4.1 Restore the factory default setting ..........................................................................16
2.4.2 Software Version and Manufacture Date................................................................17
3. Advanced Configuration Menu ........................................................................................18
3.1 Advanced Configuration Interface.................................................................................18
3.2 Configuration Items and Parameters..............................................................................18
3.2.1 Application Selection..............................................................................................18
3.2.2 Restriction on Display and View ............................................................................18
3.2.3 Restriction on Mode Modification..........................................................................18
3.2.4 Multi-temperature Sensor Settings .........................................................................19
3.2.5 Temperature Sensor Types .....................................................................................19

1
3.2.6 UI input compensation............................................................................................19
3.2.7 Alarm Input Selection .............................................................................................20
3.2.8 Analog Output Selection.........................................................................................20
3.2.9 Digital Output Selection .........................................................................................21
3.2.10 Normal Low-temperature Protection ....................................................................21
3.2.11 Dehumidification and cooling priorities ...............................................................21
3.3 Trouble Handling ...........................................................................................................21
3.3.1 Sensors Abnormlity Handling.................................................................................21
3.3.2 Alarm Input Handling .............................................................................................21
3.3.3 Winter Mode and Summer Mode ...........................................................................22
3.3.4 Running and Standby..............................................................................................22
3.4 Example of Typical Control...........................................................................................23
3.4.1 PID heating / cooling, humidification / dehumidification control..........................23
3.4.2 Single (multi)-level heating / cooling control.........................................................23
3.4.3 Single (multi)-level auxiliary output control ..........................................................23
Appendix I: Description of Configuration Items and Configuration Parameters...........24
UB1211CH/EN ...................................................................................................................24
UB2204CH/EN ....................................................................................................................28
UB2221CH/EN ....................................................................................................................32
UB4334SCH/EN..................................................................................................................38
Appendix II: Application Example ......................................................................................49

2
This product operation manual is prepared for sales staff, technical engineers and end user to learn
how to operate and config the controller on their own requirments.

There are three chapters in this manual: Chapter One is about display and operation overview;
Chapter Two, Gernaral Setting Manual, is for product sales person and end user to make them understand
basic function selection and gernaral setting method, such as changing the set point, switching the running
mode, switching the display mode and the time settings, etc. Chapter Three is Advanced Configuration
Menu. Advanced Configuration Menu is for technical staff and field supporting engineers in installation,
commission and servise to guide them in configuring various parameters of the controller.

We don’t recommend end user to enter Advanced Configuration Menu. Some uncorrect operation
or configuration erro may make the system damage.

We have another separate document “Jin Xiu Unitary Controller Application Introduction” is
about the detail introduction of different application program model build in the controller. Some
description in the instruction could be your reference.

3
.Display and Operation Overview
1.
1.1 Specification of the Controller Panel

Figure 1-1 Display Screen

1.1.1 Display Content Summary

Figure 1-1-1 Display Content Summary

1.1.2 Initial Display Example

Figure 1-1-2 UB1211EN & UB2204EN Initial Display Example

4
Figure 1-1-3 UB2221EN Initial Display Example Figure 1-1-4 UB4334SEN Initial Display Example

Note: The controller Initial displays depends on the last operation settings. Above figures are just examples
for your reference.

1.1.3 Display Backlight Control


The controller provides display backlight function to ensure the users operate easily in dim or low-light
intensity environment. When display backlight is off, press any key will only light up backlight and will
not perform the other function. Display backlight will turn off automatically if there is no key operation
within 15 seconds.

1.2. Description of Key Functions

Figure 1-2-1 Function Keys

The role of Function Key 1 includes: Winter or Summer mode selection, Copy, Clear
The role of Function Key 2 includes: Switch, Set, Enter
The role of Function Key 1 includes: Display, Enter, Exit
To the different models of the controller, the role of Function Keys is not totally same. Please view
“Function Key Description” for the details.

Function Key Description:

UB1211CH/EN
Function Function Function
State Key 1 Key 2 Key 3 Up and Down Keys
Initial Interface Mode Set Display Switch display items

5
Change the Set Point Enter Change the value of the set point
Change the Display
Mode Enter Display
Change the System
Mode Mode Enter
Change the present valueof the
Output State Mode Set Display output device
Check the Set Point Mode Set Display
Change the configuration
Configuration State Mode② Enter③ Exit① parameters
Restore the Original Change the configuration
Settings Enter parameters

UB2204CH/EN
Function Function Function
State Key 1 Key 2 Key 3 Up and Down Keys
Initial Interface Mode Set Display Switch display items
Change the Set
Point Enter Change the value of the set point
Change the
Display Mode Enter Display
Change the
System Mode Mode Enter
Change the present valueof the
Output State Mode Set Display output device
Check the Set
Point Mode Set Display
Configuration Change the configuration
State Mode Enter Exit① parameters
Restore the Change the configuration
Original Settings Enter parameters

UB2221CH/EN
Function Function Function
State Key 1 Key 2 Key 3 Up and Down Keys
Initial Interface Mode Set Display Switch display items
Change the Set
Point Swith Enter Change the value of the set point
Change the
Display Mode Enter Display
Change the
System Mode Mode Enter
Change the present valueof the
Output State Mode Set Display output device
Switch the set parameters of
Check the Set display temperature and relative
Point Mode Set Display humidity
Configuration Change the configuration
State Mode Enter Exit① parameters
Restore the Change the configuration
Original Settings Enter parameters

6
UB4334SCH/EN
Function Function Function
State Key 1 Key 2 Key 3 Up and Down Keys
Initial Interface Mode Set Display Switch display items
Change the Set
Point Swith Enter Change the value of the set point
Change the
Display Mode Enter Display
Change the
System Mode Mode Enter
Change the present valueof the
Output State Mode Set Display output device
Switch the set-point parameters
Check the Set of display temperature, relative
Point Mode Set Display humidity and pressure
Select set time, date and fixed
Setting state Set Exit① time
Time Setting Swith Enter Change the hours and minutes
Time Setting Enter Change the date
Choose Date in
the Time Setting Copy Set Exit Change the date
Copy in the Time
Setting Set Enter Change the date
Set in the Time
Setting Clear Set Enter Change the time setting
Configuration Change the configuration
State Mode Enter Exit① parameters
Restore the Change the configuration
Original Settings Enter parameters
1. Press the Mode key for 3 seconds to switch on the schedule.
2. Press the Set key for 3 seconds to enter the setting state.

Note:
①If the operator exit configuration state without saving, the configuration parameters will not be saved
automatically.
②If a new application is selected, then the Mode key will not be valid until the ENTER key is pressed.
③It is used to save the configuration parameters. If the configuration parameters are not changed, the
ENTER key is invalid.
④Pressing the Function Key 1(Mode) and the Function Key 2(Set) at the same time to enter the
configuration state.
⑤Pressing the Function Key 1(Mode) and the Function Key 3(Display) at the same time to enter the
factory default settings.

1.3 Operation Menu


According to the different users and the different setting contents, this menu separate into two parts:
General Setting Menu and Advanced Configuration Menu. General Setting Menu is for end user operation,
which can generally operate on the controller, such as changing the set point, switching the running mode,
switching the display mode and the time settings, etc.
Advanced Configuration Menu is for technical staff and field supporting engineers in installation,
commission and servise when they need configure various parameters of the controller.

7
2. General Setting Menu
(Only for UB4334SCH/EN)
2.1 Time Program( )
2.1.1 System Time Setting

2.1.1.1 Set System time


(1) In the Initial display, press the Function Key 2 (Set) for 3 seconds to enter the setting interface, shown
in Figure 2-1-1

Figure 2-1-1 the Setting Interface

(2) Press up and down keys to select the time setting item, press the Function Key 2 (Set) to enter the time
setting state, shown in Figure 2-1-2

Figure 2-1-2 the Time Setting Interface

(3)Press the Function Key 2 (Switch) to select the setting hours (0 ~ 23) or minutes (0 ~ 59), selected
setting items will flash.
(4)Press Enter after selecting the time value by up and down keys, to go back to the setting interface
(Figure 2-1-1).

2.1.1.2 Set the System Date

(1) In the initial display, press the Function Key 2 (Set) for 3 seconds to enter the setting interface, shown
in Figure 2-1-1

(2) Press up and down keys to select the date setting item, press the Function Key 2 (Set) to enter the
date setting interface, shown in Figure 2-1-3

8
Figure 2-1-3 the Date Setting Interface

(3)Press up and down keys to select the current date, and selected setting items will flash.

(4)Press Enter after selecting the date value by up and down keys, to go back to the setting interface
(Figure 2-1-1).

2.1.1.3 Clock Abnormality


If abnormality occurs to the clock when the controller starts, the controller will automatically enter the
time setting interface, shown in Figure 2-1-2.

2.1.2 Day Time Schedul Setting

The controller provides a schedule setting for four periods a day and seven days a week:

Period 1 is for the system on;


Period 2 is for the system off;
Period 3 is for the system on;
Period 4 is for the system off.

Schedule setting function can be enabled and disabled. When the schedule function is enabled, controller
will start or not start automatically according to schedule settings. When the schedule function is disabled,
the controller will start after powering on.

2.1.2.1 Modify /Creat the Day Time Schedule


⑴ In the state shown in Figure 2-1-1, select the schedule setting item by up and down keys, press the
Function Key 2 (Set) to enter the schedule setting state, shown in Figure 2-1-4.

Figure 2-1-4 the schedule Setting Interface

⑵ Press up and down keys to select the desired date, the selected date will flash.

9
⑶ Press the Function Key 2 (Set) to enter the time configuring interface, shown in Figure 2-1-5. 4 periods
of time can be configured within one day, but the periods can not be overlapped one after another.

Figure 2-1-5 the time configuring Interface

⑷ Press up and down keys to change the time value, resolution is 15 minutes. Press for 3 seconds to speed
up changing. When the value becomes the same as the time value of next period, it will not change.
⑸ Press the Function Key 3(Enter) to confirm or click the Function Key 2 (Set) for 4 times to exit the
time configuring interface and return the schedule setting interface, shown in Figure 2-1-4. The
configuration of schedule will be saved automatically.
⑹ In Figure 2-1-4, press Exit key to return the setting interface (shown in Figure 2-1-1).

2.1.2.2 Delete the Day Time Schedule


In the interface shown in Figure 2-1-5, press the Function Key 1(Clear) to clear up the Period information,
the deleted Period will no longer available.

Note: The first Period of Monday can not be deleted.

2.1.2.3 Copy the Day schedule


In the schedule setting interface shown in Figure 2-1-4, you can press the Function Key 1(Copy) to enter
the copy function interface as shown in Figure 2-1-6. Press up and down keys to select the date to copy, the
date chosen will flash. Press the Function Key 3(Enter) to copy the desired schedule information to the
currently selected date, and then automatically return to the schedule setting interface, as shown in Figure
2-1-4.

Figure 2-1-6 the Copy Function Interface

10
2.2. How to Setting
2.2.1 Fan State Setting
When the controller power on, it can automatically recieve the DI signal which comes from the fan. When
the fan state is on and running nomally, the “Run” icon will appear on the upper-left corner of the display
and when the fan is off, the “Run” icon disappears.

2.2.2 Parameters Setting

2.2.2.1 Set Point Sequence


In the initial display, press the Function Key 2 (Set) to enter the setting interface (shown in Figure 2-2-1),
the items can be switched among temperature, relative humidity and pressure. Different models of
controller will have different set point sequences.

Figure 2-2-1 the Parameters Setting Interface

2.2.2.2 Temperature Parameters Setting


⑴ Range of Temperature Parameters Setting:
Temperature of Supply Air 10℃ ~ 40℃
Temperature of Return Air 18℃ ~ 32℃
⑵ In the parameters setting interface, press the Function Key 2(Switch) to select the temperature setting.
⑶ Press up / down key and the temperature setpoint will increased or decreased by 0.5℃ each time. Press
up / down keys for 3 seconds to speed up changing. The up / down key will no longer work when the upper
/ lower limits is reached.
⑷ confirm the temperature setpoint by pressing the Function Key 3(Enter) shown in Figure 2-2-1 or wait
for 15 seconds to exit the setting state.

2.2.2.3 Relative Humidity Parameters Setting (Only for UB2221、UB4334SCH/EN)


⑴ The Range of Relative Humidity Parameters Setting: 20%RH ~ 80%RH.
⑵ In the parameters setting interface (shown in Figure 2-2-1), press the Function Key 2(Switch) to select
the relative humidity setting.
⑶ Press up / down key and the humidity setpoint is increased or decreased by 1.0%RH each time. Press
for 3 seconds to speed up changing. The up / down key will no longer work when the upper / lower limits
is reached.
⑷ Confirm the relative humidity setpoint by pressing the Function Key 3(Enter) shown in Figure 2-2-1 or
wait for 15 seconds to exit the setting state.

2.2.2.4 Pressure Parameters Setting (Only for UB4334SCH/EN)


⑴ The Range of Pressure Parameters Setting: 100Pa ~ 2500Pa.
⑵ In the parameters setting interface (shown in Figure 2-2-1), press the Function Key 2(Switch) to select
the pressure setting.
⑶ Press up / down key and the pressure setpoint is increased or decreased by 25Pa each time. Press for 3
seconds to speed up changing. The up / down key will no longer work when the upper / lower limits is
reached.
⑷ confirm the pressure setpoint by pressing the Function Key 3(Enter) shown in Figure 2-2-1 or wait for
15 seconds to exit the setting state.

11
2.2.3 The Setting of the Device Running Mode

Device Running modes are including: summer, winter, manual and automatic. In the general setting menu,
only winter and summer mode can selectable.
⑴ In initial display, press the Function Key 1(Mode) to enter the system mode setting interface, as shown
in Figure 2-2-2.

Figure 2-2-2 the Mode Setting Interface

⑵ Press the Function Key 1(Mode) to switch between the Summer and Winter Mode; as shown in Figure
2-2-3.

Figure 2-2-3 the Mode Display Interface

⑶ Press the Function Key 3(Enter) or wait for 3 seconds to exit the system running mode setting.

Only when the mode setting completed and exited the mode setting interface, the controller will accept and
switch automatically to the current mode. The controller will maintain last mode before exiting current
setting process.


Note:
1. If the device running mode has been set (configuration item 3 is 0 or 1) in the Advanced
Configuration Menu, then it can not be set in the General Setting Menu, then the mode key is
disabled.

2. For Model UB2221CH/EN, UB4334SCH/EN controller, when constant temperature and humidity
control module is selected, the running mode can not be changed in the General Setting Menu. Icon
"Auto" appears in the automatic mode interface (Figure 2-2-4).

Figure 2-2-4 the Automatic Mode Interface

3. If "manual" state has been set in the Advanced Configuration Menu (please refer to Appendix
configuration item 100, and the parameter is set to be 1), then in the General Setting Menu, the icon
"Manual" is displayed fixedly in the mode box, mode key is disabled, shown in Figure 2-2-5.

12
Figure 2-2-5 the Manual Mode Interface

2.2.4 Display Contents Setting


Display contents are including: present value, output and set point.
⑴ In initial display, press the Function Key 3(Display) to enter the display contents setting interface
(Figure 2-2-6).

Figure 2-2-6 the Display Contents Setting Interface

⑵ Press the Function Key 3(Display) to switch the display contents among the “Present Value”, “OutPut”
and “Set Point” (Figure 2-2-7).

Figure 2-2-7 the Display Switching Interface

In Present Value display mode, you can press up and down keys to switch among Return Air , Supply Air
and Outdoor Air display values.

In OutPut display mode, you can press up and down keys to view the output value of different devices, as
shown in Figure 2-2-8. Different models with different application may have different output devices.

Figure 2-2-8 the Output Value of Different Devices in the Display

13
In Set Point display mode, you can press up and down keys to switch the display of set humidity and
pressure. This function is only available in UB4334SCH/EN.

⑶ Confirm the display contents by pressing the Function Key 2(Enter) or wait for 3 seconds to save and
exit the display contents setting state (Figure 2-2-6).

Only when the display contents setting completed and exited the mode setting interface, the controller will
accept and switch to the current mode automatically. The controller will maintain last mode before exiting
current setting process.

Note: :
1. If the Display Contents has been set as “Present Value” in the Advanced Configuration Menu (please
refer to Appendix Configuration Item 02, and the parameter is set to be 01), then the display item will be
the Present Value constantly, the display contents can not be changed in the General Setting Menu, and the
display contents setting function is diasbled, as is shown in Figure 2-2-9.

Figure 2-2-9

2. If the Display Contents has been set as “Set Point” in the Advanced Configuration Menu (please refer to
Appendix Configuration Item 02, and the parameter is set to be 02), then the display item will be the Set
Point constantly, the display contents can not be changed in the General Setting Menu, and the display
contents setting function is diasbled, as is shown in Figure 2-2-10.
.

Figure 2-2-10

3. If the Display Contents has been set as “Present Value or Set Point” in the Advanced Configuration
Menu (please refer to Appendix Configuration Item 02, and the parameter is set to be 03), then the display
item will be switched between the two display value in the General Setting Menu, as is shown in Figure 2-
2-11.

Figure 2-2-11

Note:
① UB2204CH/EN (in Appendix Configuration Item 04, the parameter is set to be 03) can display
the outside air temperature.
② UB4334SCH/EN (in Appendix Configuration Item 04, the parameter is set to be 03) can display
the outside air temperature as well as the outside air humidity.

14
2.2.5 Device Running State
According to the state of controlled devices, the controller can automatically show four kinds of system
states, namely heating, cooling, humidifying and dehumidifying, as shown in Figure 2-2-12.

Figure 2-2-12
Different models with different application may display one or two of the four kinds of state. Controller
will not display the device state when in manual mode or sensor abnormal.

2.3. Alarm
2.3.1 Alarm Signals
Controller provides four kinds of alarm display according to different alarm signal, namely fan alarm, filter
alarm, low temperature alarm and smoke alarm. When the alarm signal disappears, the corresponding
alarm display will cleared, as shown in Figure 2-3-1.

Figure 2-3-1

Note: Please refer to Appendix configuration item 13 and select one or two of the four kinds of alarm
signal. Only Model UB4334SCH/EN can support two kinds of alarm signal.

2.3.2 Sensor Abnormality


⑴ Normal Operation Range:
Temperature of Return Air 0℃ ~ 50℃
Temperature of Supply Air 0℃ ~ 50℃
Outdoor Temperature -30℃ ~ 50℃(NTC10K)
-40℃ ~ 50℃(NTC20K,PT1000)
Indoor temperature setting range 18℃ ~ 32℃
Relative Humidity(Non-Condensing) 0%RH ~ 100%RH
Pressure 0Pa ~ 2500Pa
CO2 0ppm ~ 2000ppm

⑵ When present value of the sensor is over the controller display range, if it is in Present Value display
mode, the display will as ‘---.-’. In ‘Preset Value’, ‘OutPut’, ’Set Point’ display mode, the name of
abnormal sensor will flash, as shown in Figure 2-3-2. When the sensor returns to the normal state, the
display will recover.

Figure 2-3-2 the Sensor abnormality

、UB4334SCH/EN)
2.3.3 Timeout Alarm (Only for UB2221CH/EN、
For the constant temperature and humidity device, when the temperature or humidity present value does
not reach the range of set point in a certain period of time, the temperature or humidity present value will
flash. When the temperature or humidity reaches the set point range, the display will recover.

15
Note: the timeout period, the temperature and humidity range can be set in the Advanced Configuration
Menu. Please refer to Appendix Configuration Item 57, 58 and 59. For UB4334SCH/EN, please refer to
Appendix Configuration Item 41 for alarm output.

2.3.4 Alarm Elimination


When the alarm signals disappear, the alarm display will be automatically removed.

2.4 System Information


2.4.1 Restore the factory default setting

2.4.1.1 Restore the factory default setting manually


⑴ In the initial display, press the Function Key 1(Mode) and the Function Key 3 (Display) at the same
time for 3 seconds to enter to restoring factory default setting interface, as shown in Figure 2-4-1. The
code number on the upper-left corner is the configuration items, and the center code is the configuration
parameters.

Figure 2-4-1 Restoring Original Configuration Interface


⑵ Press up / down key to switch the configuration parameters. 0 is not to restore the factory default
setting, 1 is to restore the factory default setting and restore the default values of all parameters.

⑶ After the parameters is selected, press the Function Key 3 (Enter) to exit the interface.

After selecting the parameter 1 to restore the factory default setting and exiting, the controller will
automatically reset.

2.4.1.2 Restore the factory default setting automatically


⑴ If any unexpected abnormality occurs while running, the controller will automatically reset to and enter
the abnormality recovery interface, as shown in Figure 2-4-2.

Figure 2-4-2 the Abnormality Recovery Interface

⑵ Only press the Function Key 3 (Enter) to restore the factory default setting.

16
2.4.2 Software Version and Manufacture Date
In the Advanced Configuration Menu, select the configuration item 300 and 301 to view the software
version and manufacture date of the controller, as shown in Figure 2-4-3 and 2-4-4.

Figure 2-4-3 the Controller Software Version Interface Figure 2-4-4 the Manufacture Date Interface

17
3. Advanced Configuration Menu

3.1 Advanced Configuration Interface


In the initial display, press the Function Key 1(Mode) and the Function Key 2(Set) at the same time to
enter the Advanced Configuration Menu (as shown in Figure 3-1-1)

Figure 3-1-1 the Advanced Configuration Menu Interface

The configuration items can be seen on the upper-left corner of the advanced configuration menu interface.
The big font numbers in the middle are the configuration parameters. The configuration items and
parameters have different meanings according to the different model controllers, to see the Description
Table of Configuration Items and Configuration Parameters for detail.

Press the Function Key 1(Mode) can switch the configuration items; press up and down keys can select the
configuration parameters under the corresponding configuration items; press the Function Key 2(Enter)
can save the configuration parameters; press the Function Key 3(Exit) can return the initial display.

3.2 Configuration Items and Parameters


3.2.1 Application Selection

The configuration item 01 is used to sellect the application module. The Specification of each application
program module can be seen in the separate manul "Application Description".

3.2.2 Restriction on Display and View

The configuration item 02 is used to set the values which the end users are allowed to view in the
display, the corresponding configuration parameters as below:
00:All (preset value, set point, output)
01: Preset Value Only
02: Set Point Only
03: Present Value and Set Point

3.2.3 Restriction on Mode Modification

This function applies to non-constant temperature and humidity device and it will unavailable in
the application 4.4 and 3.3.

18
The configuration item 03 is used to set the working mode of controller, the corresponding
configuration parameters as below:
00:: Summer Mode Only
01:: Winter Mode Only
02::Summer Mode or Winter Mode

3.2.4 Multi-temperature Sensor Settings

The configuration item 04 is used for temperature Sensor Settings, and only for models
UB2204CH/EN and UB4334SCH/EN:
UB2204CH/EN, UI1 and UI2 conncet to temperature sensors;
UB4334SCH/EN, UI1 and UI3 conncet to temperature sensors.

Configuration parameters as follows:


:The second temperature sensor is disabled
00:
:The average of first temperature sensor and second temperature sensor
01:
:The second temperature sensor can connect CTR22 or CTR23, CTR23-H (Room temperature
02:
wall module) adjustable set point, and the limits to the remote set point selection range can be
made within the controller.
03: The second temperature sensor serves as the outdoor temperature sensor, and to compensate
the set point by means as follows:
Configuration item 47, parameter Wcomp: the summer and winter compensation switching point;
Configuration item 48, parameter Su: the summer temperature compensation ratio;
Configuration item 49, parameter Wi: the winter temperature compensation ratio;
Parameter Twork: working setpoint temperature.
When the outdoor temperature Tout< Wcomp, the winter temperature compensation is
implemented.
When the outdoor temperature Tout> Wcomp, the summer temperature compensation is
implemented.
The calculation of summer compensation: working setpoint temperature Twork=setpoint TS
(Tout-Wcomp)* Su% Su: range 95% ~ -95%
The calculation of winter compensation: working setpoint temperature Twork=setpoint TS
(Wcomp-Tout)* Wi % Wi: range 35.0% ~ -35.0%.

3.2.5 Temperature Sensor Types


In this Advanced Configuration Menu, the temperature sensor types can be selected by setting the
configuration items and parameters:
For UB2204CH/EN controller, configuration items are 05 and 06;
For UB4334SCH/EN controller, configuration items are 05 and 07.

The corresponding configuration parameters are:


:NTC20K
00:
:PT1000
01:
:NTC10K
02:

Note:Jin Xiu controller can only support these three types of temperature sensors.

3.2.6 UI input compensation


This controller supports input compensation function. To select the configuration items 09, 10, 11,
and 12 can compensate the input.

19
As for temperature sensor input, set the unit of the compensation value as Celsius degrees. E.g.:
press up and down keys to set the compensation value as -1.5, and then the actual temperature
minus 1.5 degrees Celsius is regarded as the preset temperature.
As for humidity sensor input, set the unit of the compensation value as percentage. E.g.: press up
and down keys to set the compensation value as -1.5, and then the actual humidity minus 1.5% is
regarded as the preset humidity.
As for CO2 sensor input, set the unit of the compensation value as PPM.
As for pressure sensor input, set the unit of the compensation value as Pa.

3.2.7 Alarm Input Selection

Select the configuration item 13 can set the type of the alarm input.
Model UB1211CH/EN, UB2204CH/EN and UB2221CH/EN support single alarm input, including
the following configuration parameters:
:Filter alarm
00:
:Fan alarm
01:
:Smoke alarm
02:
:Low temperature alarm
03:

Model UBS4334CH/EN controller supports multi-alarm input. Note: The contents of the DI point
alarm are fixed, the alarm content and point position set by the related configuration parameters are as
follows, it should be careful to access to the right sensor when wiring.
00::DI2 Filter alarm; DI3 Fan alarm
01::DI2 Filter alarm; DI3 Smoke alarm
02::DI2 Filter alarm; DI3 Low temperature alarm
03::DI2 Fan alarm; DI3 Smoke alarm
04::DI2 Fan alarm; DI3 Low temperature alarm
05::DI2 Smoke alarm; DI3 Low temperature alarm

3.2.8 Analog Output Selection


When the controller’s each analog output load is greater than 500 ohms, voltage mode should be
enabled and corresponding mode output range should be configured.

In this Advanced Configuration Menu, select the configuration item 18 to set as 0 (voltage mode),
and the configuration item 19, 21, and 23 to set the analog output range. The corresponding configuration
parameters are as follow:
00::0 ~ 10V (0%-0V, 100%-10V)
01::2 ~ 10V (0%-2V, 100%-10V)
02::10 ~ 0V (0%-10V, 100%-0V)
03::10 ~ 2V (0%-10V, 100%-2V)
When the controller’s each analog output load is less than 500 ohms, current mode should be
enabled and corresponding mode output range should be configured.

In the Advanced Configuration Menu, select the configuration item 18 to set as 1 (current mode),
and the configuration item 20, 22, and 24 to be set the analog output range. The corresponding
configuration parameters are as follow:
00::4 ~ 20mA (0%-4mA, 100%-20mA)
01::20 ~ 4mA (0%-20mA, 100%-4mA)

Note: The controller only supports that all the AOs are same voltage mode or same current mode.

20
3.2.9 Digital Output Selection
All of the Digital output types can be configured as positive or negative logic output through 25,
26, 27 and 28 configuration items.

Open Logic Close Logic


:negative logic Output
00: Open 24VAC, 500mA Max
:positive logic Output
01: 24VAC, 500mA Max Open

3.2.10 Normal Low-temperature Protection


The controller can set the minimun openning of heating valve (the minimum output PI) in the
winter mode to provide low-temperature protection for heating valve with PI responding. When the
calculated PI value is below the minimum set point of PI, it will maintain the minimum set point of PI.
Select the configuration item 35, and press up / down key to set the minimum opening of the
heating valve.
The configuration item 35 defaults to be 20%, namely, the minimum output of the heating valve in
winter is 20%.

3.2.11 Dehumidification and cooling priorities


This function is available in UB2221CH/EN and UB4334SCH/EN.
As for the temperature, humidity double-loop control, dehumidification and cooling PI output can
be selected via configuration item 50. The corresponding configuration parameters are as follow:
:Humidity PI output
00:
:Maximum of humidity PI and temperature PI
01:
:Minimum of humidity PI and temperature PI
02:
:Temperature PI output
03:
Apply to cooling valve, and when dehumidification PI output is greater than cooling PI output, the
controller will activate the re-heat function, and if the present temperature is below the set point, the
heating output will be started.

3.3 Trouble Handling


3.3.1 Sensors Abnormlity Handling
The valid range of sensor input is shown in the table below. When the actual value is over the
valid range, the controller will display an abnormal message and shut down output.

Note: When the adjustable input set point is between the maximum and minimum, it will not result in
abnormality.

Sensor Low-temperature limit High-temperature limit


Temperature Sensor of
0°C 50°C
Return Air
Temperature Sensor of
0°C 50°C
Supply Air
Outdoor Temperature
-40°C (-30 for NTC10K) 50°C
Sensor
Humidity Sensor 0%RH 100%RH
Pressure Sensor 0Pa 2,500Pa
CO2 Sensor 0PPM 2,000PPM
Indoor Temperature
18°C 32°C
Setting (CTR series)

3.3.2 Alarm Input Handling

21
Filter alarm: When the alarm input is configured to be filter alarms, and the corresponding DI
and COM are closed, LCD will display “Filter ” alarm.
Fan alarm: When the alarm input is configured to be fan alarms, and the corresponding DI and
COM are closed, LCD will display “Fan” alarm.
Smoke alarm: When the alarm input is configured to be smoke alarms, and the corresponding DI
and COM are closed, LCD will display “Smoke” alarm.
Smoke alarm chain (only Model UB4334CH/EN): If the fan detects smoke alarm in the running
time, the controller will turn off fans and air valves.
Low temperature alarm: When the alarm input is configured to be low temperature alarms, and the
corresponding DI and COM are closed, LCD will display “Low temperature” alarm.
Low temperature alarm interlock: If the controller detects low-temperature alarm when working in
the winter mode, the controller will adjust the output of heating valve to the maximum.

Note (only Model UBS4334CH/EN): If the fan is running when the low temperature alarm is detected, the
controller should turn off fans and damper oderly.

Control deviation alarm: For the constant temperature and humidity control, if the present value
deviates from the setting range (which can be adjusted according to the configuration item 57 and 58) for a
long time (the time can be adjusted according to the configuration item 59), the controller will display
deviation alarm. When the deviation drops back within the error range, the alarm will be automatically
removed.
According to the system default, with the present temperature and humidity, if the controller
exceeds the temperature set point by ±3 ℃ (configuration item 57) or humidity set point by ±10%
(configuration item 58) within 60 seconds (configuration item 59), then controller will display deviation
alarm. If the present temperature and humidity return to the temperature set point ±3 ℃ (configuration
item 57) and the humidity set point ± 10% (configuration item 58), then the deviation alarm will be
automatically removed.

3.3.3 Winter Mode and Summer Mode

In winter mode:
Normal low-temperature protection means that when the normal low-temperature protection (the
users can set it via configuration item 35) is not 0, the cooling valve and humidification valve output is
prohibited, and the heating valve is allowed to output; when the normal low-temperature protection is 0,
the cooling valve, humidification valves and heating valve are allowed to output.
Low-temperature alarm enables the cooling valve and humidification valve output to be prohibited,
maximizes the output of heating valve and turns off fans and damper orderly.

In summer mode:
Normal low-temperature protection is disabled, and the cooling valve, humidification valves and
heating valve are allowed to output.
Low-temperature alarm is disabled.

3.3.4 Running and Standby


As for Model UB4334SCH/EN, when the controller is running (no smoke alarm or low temperature
alarm), the dampers and fans are opened; when it is detected that the fans are running efficiently, the
controller is then automatically controlled according to the temperature and humidity. When the controller
is in standby state, the automatic control of the temperature and humidity is stopped, the fan is closed;
when it is detected that the fans are running invalidly, the air valve will be closed.
As for Model UB1121 CH/EN, UB2204 CH/EN and UB4334SCH/EN, when it is detected that the
fans are running efficiently, the controller is then automatically controlled according to the temperature
and humidity. When it is detected that the fans are running invalidly, the automatic control of the
temperature and humidity will be stopped.

22
3.4 Example of Typical Control
3.4.1 PID heating / cooling, humidification / dehumidification control

3.4.2 Single (multi)-level heating / cooling control

3.4.3 Single (multi)-level auxiliary output control

23
Appendix I: Description of Configuration Items and Configuration Parameters
In the following table, Y indicates that the configuration items in this application can be configured, and N indicates that the configuration items in this application
can not be configured.

UB1211CH/EN
Configuration
Configuration Configuration Parameter and Parameter Application Application Application Application Application Application Remark
Item configuration Content Description Default 1.1 1.2 1.3 1.4 1.5 1.6
01- Application 1.1
02 -Application 1.2
03 - Application 1.3
01 01 Y Y Y Y Y Y
Application Selection 04 - Application 1.4
05 - Application 1.5
06 - Application 1.6
00 - All
01 - Only the present value
02 02 - Only the set value 00 Y Y Y Y Y Y
Display Mode Selection
03 - The present and set
value
00 - Only summer
03 System Mode Selection 01 - Only winter 02 Y Y Y Y Y Y
02 - Summer and winter
00 - NTC20K
UI1 Temperature
05 01 - PT1000 00 Y Y Y Y Y Y
Sensor Type
02 - NTC10K
09 UI1 Temperature -5.0 - –5.0℃ 0.0 Y Y Y Y Y Y
Compensation
-4.9 - –4.9℃
……
0.0 - 0℃
……
4.9 - 4.9℃

24
5.0 - 5.0℃
00 - Filter alarm
01 - Fan alarm
13 Alarm Type 00 Y Y Y Y Y Y
02 - Smoke alarm
03 - Low temperature alarm
Voltage\Current Mode 00 - Voltage mode
18 00 Y Y Y Y Y Y
Selection 01 - Current mode
00 – 0~10V When the con
figuration ite
01 – 2~10V
m 18 (Voltage
02 – 10~0V \Current Mod
AO1 Voltage Output
19 00 Y Y Y Y Y Y e Selection) is
Mode
set as 00, the
03 – 10~2V configuration
item 19 will b
e valid.
00 - 4~20mA When the con
figuration ite
m 18 (Voltage
\Current Mod
AO1 Current Output
20 00 Y Y Y Y Y Y e Selection) is
Mode 01 – 20~4mA set as 01, the
configuration
item 20 will b
e valid.
00 - NC
25 DO1 Mode 01 Y Y Y Y Y Y
01 – NO
0.0 - 0.0℃
1.0 – 1.0℃
…… The default
29 Temperature Control P The default The default The default The default The default
4.0 – 4.0℃ is 10 ℃
is 10 ℃ is 10 ℃ is 4 ℃ is 4 ℃ is 4 ℃
……
50.0 – 50.0℃
30 Temperature Control I 0 - 0s The
default is The default The default The default The default The default
15 - 15s
30s is 30s is 30s is 600s is 600s is 600s
30 - 30s

25
...
105 - 105s
120 - 120s
135 - 135s
150 - 150s
...
585 - 585s
600 - 600s
615 - 615s
...
1200 - 1200s
0.0 - 0.0℃
0.5 - 0.5℃
1.0 - 1.0℃
……
31 Temperature dead 1.0 Y Y Y Y Y Y
Range 1.5 - 1.5℃
……
3.5 - 3.5℃
4.0 - 4.0℃
0.0 - 0%
5.0 - 5%
The Minimum Usage of ...
Water Valve under
35 20.0 – 20% 20.0 Y Y N Y Y N
Normal Low-
temperature Protection ...
45.0 – 45%
50.0 – 50%
00 - Only AO( DO alarm)
Temperature Control 01 - AO + DO (Auxiliary
36 output) 00 Y N N Y N N
Mode Selection
02 - Only DO (AO is
disabled)
37 Auxiliary Output 0.0 - 0% 65.0 Y N N Y N N When the con
Switch (dead range figuration ite
5.0 - 5%

26
10%) ... m 36 (Temper
ature Control
65.0 – 65%
Mode Selecti
... on) is set as 0
95.0 – 95% 1, the configu
ration item 37
100.0 - 100% will be valid.
00 - Automatic
100 Manual\Automatic 00 Y Y Y Y Y Y
Mode Selection 01 - Manual
0.0 - 0% When the con
Y Y figuration ite
10.0 – 10%
(the param (the parame m 100 (Manu
…… eters selecti ters selectio al\Automatic
50.0 – 50% on from the n from the Mode Selecti
101 0.0 Y Y Y Y
AO1 Manual Output configurati configurati on) is set as 0
……
on item 36 on item 36 1, the configu
90.0 – 90% is not equal is not equal ration item 10
2) 2) 1 will be vali
100.0 - 100%
d.
00 When the con
figuration ite
m 100 (Manu
al\Automatic
Mode Selecti
201 00 Y Y Y Y Y Y
DO1 Manual Output 01 on) is set as 0
1, the configu
ration item 20
1 will be vali
d.
300 Y Y Y Y Y Y
Software Version
301 Y Y Y Y Y Y
Production Date
00 - Not restore the original
settings
500 00 Y Y Y Y Y Y
Manufacture Date 01 - Restore the original
settings

27
UB2204CH/EN
Configuration Configuration
Configuration Parameter and Parameter Application Application Application Application
Item Description Description Default 2.1 2.2 2.3 2.4 Remark
01 - Application 2.1
02 - Application 2.2
01 Application Selection 01 Y Y Y Y
03 - Application 2.3
04 - Application 2.4
00 - All
01 - Only the present
value
02 00 Y Y Y Y
Display Mode 02 - Only the set value
03 - The present and
set value
00 - Only summer
03 01 - Only winter 02 Y Y Y Y
System Mode 02 - Summer and
winter
00 - Disabled
01 - Temperature
Multi-Temperature average
04 00 Y Y Y Y
Sensor Setting 02 - Remote setting
03 - Temperature
compensation
00 - NTC20K
UI1 Temperature
05 01 - PT1000 00 Y Y Y Y
Sensor Type
02 - NTC10K
00 - NTC20K
When the configuration item 04
01 - PT1000
UI2 Temperature (Multi-Temperature Sensor
06 00 Y Y Y Y
Sensor Type Setting) is set as 01 or 03, the
02 - NTC10K configuration item 06 will be
valid.
09 -5.0 - –5.0℃ 0.0 Y Y Y Y
UI1 Temperature
-4.9 - –4.9℃
Compensation
……

28
0.0 - 0℃
……
4.9 - 4.9℃
5.0 - 5.0℃
-5.0 - –5.0℃
-4.9 - –4.9℃
…… When the configuration item 04
UI2
(Multi-Temperature Sensor
10 UI2 Temperature 0.0 - 0℃ 0.0 Y Y Y Y
Setting) is set as 00, the
Compensation
…… configuration item 10 will be
4.9 - 4.9℃ valid.
5.0 - 5.0℃
00 - Filter alarm
01 - Fan alarm
13 02 - Smoke alarm 00 Y Y Y Y
Alarm Type
03 - Low temperature
alarm
00 – NC
25 01 Y Y Y Y
DO1 Mode 01 – NO
00 – NC
26 01 Y Y Y Y
DO2 Mode 01 – NO
00 – NC
27 01 Y Y Y Y
DO3 Mode 01 – NO
00 – NC
28 01 Y Y Y Y
DO4 Mode 01 – NO
0.0 - 0.0℃
1.0 – 1.0℃
……
29 N The default N The default is
Temperature Control P 4.0 – 4.0℃ is 10 ℃ 4℃
……
50.0 – 50.0℃
30 0 - 0s N N
Temperature Control I The default The default is
15 - 15s

29
30 - 30s is 30s 600s
...
105 - 105s
120 - 120s
135 - 135s
150 - 150s
...
585 - 585s
600 - 600s
615 - 615s
...
1200 - 1200s
0.0 - 0℃
0.5 - 0.5℃
1.0 - 1.0℃
The First Stage ……
32 0.5 Y N Y N
Temperature dead 2.0 - 2.0℃
Range
……
3.5 - 3.5℃
4.0 - 4.0℃
0.0 - 0℃
0.5 - 0.5℃
1.0 - 1.0℃
The Second Stage ……
33 0.5 Y N Y N
Temperature dead 2.0 - 2.0℃
Range
……
3.5 - 3.5℃
4.0 - 4.0℃
34 0.0 - 0℃ 1 Y N Y N
Interstage Offset
1.0 - 1℃
2.0 - 2℃
3.0 - 3℃
4.0 - 4℃

30
5.0 - 5℃
0,0 - 0℃
1.0 - 1℃
When the configuration item 4
…… (Multi-Temperature Sensor
Compensation
47 15.0 – 15℃ 15 Y Y Y Y Setting) is set as 03, the
Switching Point
…… configuration item 47 will be
valid.
49.0 – 49℃
50.0 – 50℃
-95.0 - -95.0%
-90.0 - -90.0%
When the configuration item 4
…… (Multi-Temperature Sensor
48 15.0 – 15.0% 15.0 Y Y Y Y Setting) is set as 03, the
Summer Compensation
configuration item 48 will be
……
valid.
90.0 – 90.0%
95.0 – 95.0%
-35.0 - -35.0%
-30.0 - -30.0%
When the configuration item 4
…… (Multi-Temperature Sensor
49 -5.0 - -5.0% -5.0 Y Y Y Y Setting) is set as 03, the
Winter Compensation
configuration item 49 will be
……
valid.
30.0 – 30.0%
35.0 – 35.0%
00 -
100 Manual\Automatic 00 Y Y Y Y
Mode Selection 01 -
00 When the configuration item 100
(Manual\Automatic Mode
201 00 Y Y Y Y Selection) is set as 01, the
DO1 Manual Output 01 configuration item 201 will be
valid.
00
When the configuration item 100
(Manual\Automatic Mode
202 DO2 Manual Output 00 Y Y Y Y
01 Selection) is set as 01, the
configuration item 202 will be
valid.

31
00 When the configuration item 100
(Manual\Automatic Mode
203 DO3 Manual Output 00 Y Y Y Y Selection) is set as 01, the
01 configuration item 203 will be
valid.
00 When the configuration item 100
(Manual\Automatic Mode
204 DO4 Manual Output 00 Y Y Y Y Selection) is set as 01, the
01 configuration item 204 will be
valid.
300 Y Y Y Y
Software Version
301 Y Y Y Y
Production Date
00 - Not restore the
original settings
500 00 Y Y Y Y
Manufacture Date 01 - Restore the
original settings

UB2221CH/EN
Configuration Configuration Parameter Configuration Application Application Application Application Application
Item Description and Description Parameter Default 3.1 3.2 3.3 3.4 3.5 Remark
01 - Application 3.1
02 - Application 3.2
01 03 - Application 3.3 01 Y Y Y Y Y
Application Selection
04 - Application 3.4
05 - Application 3.5
00 - All
01 - Only the present
value
02 00 Y Y Y Y Y
Display Mode 02 - Only the set value
03 - The present and set
value
00 - Only summer
03 01 - Only winter 02 Y Y N Y Y
System Mode
02 - Summer and winter

32
00 - NTC20K
05 UI1 Temperature 01 - PT1000 00 Y Y Y Y Y
Sensor Type 02 - NTC10K
-5.0 - –5.0℃
-4.9 - –4.9℃
……
09 UI1 Temperature 0.0 - 0℃ 0 Y Y Y Y Y
Compensation
……
4.9 - 4.9℃
5.0 - 5.0℃
–10.0 - –10.0%
–9.9 - –9.9%
UI2 ……
10 UI2 Temperature 0,0 - 0% 0 Y Y Y Y Y
Compensation
……
9.9 - 9.9%
10.0 – 10.0%
00 - Filter alarm
01 - Fan alarm
13 02 - Smoke alarm 00 Y Y Y Y Y
Alarm Type
03 - Low temperature
alarm
Voltage\Current Mode 00 - Voltage mode
18 00 Y Y Y Y Y
Selection 01 - Current mode
00 - 0~10V When the configur
ation item 18 (Volt
01 - 2~10V
age\Current Mode
19 AO1 Voltage Output 02 - 10~0V 00 Y Y Y Y Y Selection) is set as
Mode 00, the configurati
03 - 10~2V on item 19 will be
valid.
00 - 4~20mA When the configur
ation item 18 (Volt
20 AO1 Current Output 00 Y Y Y Y Y
01 - 20~4mA age\Current Mode
Mode
Selection) is set as

33
01, the configurati
on item 20 will be
valid.
00 - 0~10V When the configur
ation item 18 (Volt
01 - 2~10V
age\Current Mode
21 AO2 Voltage Output 02 - 10~0V 00 Y Y Y Y Y Selection) is set as
Mode 00, the configurati
03 - 10~2V on item 21 will be
valid.
00 - 4~20mA When the configur
ation item 18 (Volt
age\Current Mode
AO2 Current Output
22 00 Y Y Y Y Y Selection) is set as
Mode 01 - 20~4mA 01, the configurati
on item 22 will be
valid.
00 – NC
25 01 Y Y Y Y Y
DO1Mode 01 ~ NO
0.0 - 0.0℃
1.0 – 1.0℃
……
29 The default The default The default The default is The default
Temperature Control P 4.0 – 4.0℃ is 4 ℃ is 4 ℃ is 4 ℃ 10 ℃ is 10 ℃
……
50.0 – 50.0℃
30 0 - 0s
Temperature Control I The default The default The default The default is The default
15 - 15s
is 600s is 600s is 600s 30s is 30s
30 - 30s
...
105 - 105s
120 - 120s
135 - 135s
150 - 150s
...
585 - 585s
600 - 600s
615 - 615s

34
...
1200 - 1200s
0.0 - 0%
5.0 - 5%
The Minimum Usage of
Water Valve under ...
35 Normal Low- 20.0 – 20% 20.0 Y Y N Y Y
temperature Protection
...
45.0 – 45%
50.0 – 50%
0%
1.0 - 1%
……
39 Humidity Control P 10.0 Y Y Y Y Y
10.0 – 10%
……
20.0 – 20%
0 - 0s
15 - 15s
30 - 30s
...
105 - 105s
120 - 120s
40 Humidity Control I 135 - 135s The default The default The default The default is The default
150 - 150s is 600s is 600s is 600s 30s is 30s
...
585 - 585s
600 - 600s
615 - 615s
...
1200 - 1200s
00 – AO2(Humidifying) +
41 DO Function Selection 00 Y N N Y N
DO(Alarm output)
01 – AO2(Humidifying) +
DO(auxiliary heating)

35
02 – AO2(Humidifying) +
DO(auxiliary cooling/
dehumidifying)
03 – AO2(Humidifying) +
DO(auxiliary
Humidifying)
04 - DO (AO2)
Humidifying(AO2 is
disabled)

As for application
0.0 - 0% 3.1 and 3.4: when t
5.0 - 5% he configuration it
Auxiliary Output
…… em 41 (DO Functi
42 Switch (dead range 10.0 Y N Y Y N
on Selection) is set
10%) 10.0 – 10% as 00 and 04, the c
…… onfiguration item 4
45.0 – 45% 2 will be valid.

50.0 – 50%
0.0 - 0%
0.5 - 0.5% As for application
3.1 and 3.4: when t
1.0 - 1% he configuration it
…… em 41 (DO Functi
43 Humidity Dead Range 5.0 Y Y N Y Y
5.0 - 5% on Selection) is set
as 04, the configur
…… ation item 43 will
9.5 - 9.5% be valid.
10.0 – 10%
00 - Only dehumidifying
01 - Maximum of
dehumidifying and
Dehumidification and
cooling
50 Cooling Priority 01 Y Y Y Y Y
02 - Minimum of
dehumidifying and
cooling
03 - Only cooling
57 Temperature 0.0 - 0℃ 3.0 N N Y N N
Overranging
1.0 - 1℃

36
Alarm(constant ……
temperature and
3.0 - 3℃
humidity)
……
4.0 - 4℃
5.0 - 5℃
0.0 - 0%
5.0 - 5%
Humidity Overranging ……
Alarm(constant
58 10.0 – 10% 10.0 N N Y N N
temperature and
humidity) ……
15.0 – 15%
20.0 – 20%
30 - 30s
Overranging Alarm 60 - 60s
Delay(constant
59 120 - 120s 60 N N Y N N
temperature and
humidity) 160 - 160S
320 - 320S
00 - Automatic
100 Manual\Automatic 00 Y Y Y Y Y
Mode Selection 01 - Manual
0.0 - 0%
When the configur
10.0 – 10%
ation item 100 (Ma
…… nual\Automatic M
101 AO1 Manual Output 50.0 – 50% 0 Y Y Y Y Y ode Selection) is se
…… t as 01, the configu
ration item 101 wil
90.0 – 90% l be valid.
100.0 - 100%
102 AO2 Manual Output 0.0 - 0% 0 Y Y Y Y Y When the configur
(the (DO function ation item 100 (Ma
10.0 – 10%
parameters selection is nual\Automatic M
…… selection not equal 4) ode Selection) is se
50.0 – 50% from the t as 01, the configu
…… configuration ration item 102 wil
item 41 is l be valid.
90.0 – 90%

37
100.0 - 100% not equal 4)
00 When the configur
ation item 100 (Ma
nual\Automatic M
201 00 Y Y Y Y Y ode Selection) is se
DO1 Manual Output 01 t as 01, the configu
ration item 201 wil
l be valid.
300 Y Y Y Y Y
Software Version
301 Y Y Y Y Y
Production Date
00 - Not restore the
original settings
500 00 Y Y Y Y Y
Manufacture Date 01 - Restore the original
settings

UB4334SCH/EN
Configuration Configuration
Configuration Parameter and Parameter Application Application Application Application Application Application Application
Item Description Description Default 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Remark
01 - Application 4.1
02 - Application 4.2
03 - Application 4.3
01 04 - Application 4.4 01 Y Y Y Y Y Y Y
Application Selection
05 - Application 4.5
06 - Application 4.6
07 - Application 4.7
00 - All
01 - Only the present
02 value 00 Y Y Y Y Y Y Y
Display Mode
02 - Only the set value
03 - The present and

38
set value
00 - Only summer
03 01 - Only winter 02 Y Y Y N Y Y Y
System Mode 02 - Summer and
winter
00 - Disabled
01 - Temperature
Multi-Temperature average
04 00 Y Y Y Y Y Y Y
Sensor Setting 02 - Remote setting
03 - Temperature
compensation
00 - NTC20K
05 UI1 Temperature 01 - PT1000 00 Y Y Y Y Y Y Y
Sensor Type
02 - NTC10K
00 - NTC20K When the configur
ation item 04 (Mul
01 - PT1000
ti-Temperature Sen
UI3 Temperature
07 00 Y Y Y Y Y Y Y sor Setting) is set a
Sensor Type
02 - NTC10K s 01 or 03, the conf
iguration item 07
will be valid.
-5.0 - –5.0℃
-4.9 - –4.9℃
UI1 ……
09 UI1 Temperature 0.0 - 0℃ 0.0 Y Y Y Y Y Y Y
Compensation
……
4.9 - 4.9℃
5.0 - 5.0℃
–10.0 - –10.0%
–9.9 - –9.9%
UI2 ……
10 UI2 Temperature 0,0 - 0% 0.0 Y Y Y Y Y Y Y
Compensation
……
9.9 - 9.9%
10.0 – 10.0%

39
-5.0 - –5.0℃
-4.9 - –4.9℃ When the configur
ation item 04 (Mul
UI3 …… ti-Temperature Sen
11 UI3 Temperature 0.0 - 0℃ 0.0 Y Y Y Y Y Y Y sor Setting) is not s
Compensation …… et as 00, the config
uration item 11 wil
4.9 - 4.9℃ l be valid.
5.0 - 5.0℃
–10.0 - – –10.0 - – –10.0 - –
-300Pa -200PPM -300Pa -200PPM
10.0% 10.0% 10.0%
–9.9 - – –9.9 - – –9.9 - –
-297Pa -198PPM -297Pa -198PPM
9.9% 9.9% 9.9%
UI4 …… …… …… …… …… …… ……
12 UI4 Temperature
0,0 - 0% 0Pa 0ppm 0,0 - 0% 0,0 - 0% 0Pa 0ppm
Compensation
…… …… …… …… …… …… ……
9.9 - 9.9% 297Pa 198PPM 9.9 - 9.9% 9.9 - 9.9% 297Pa 198PPM
10.0 - 10.0 - 10.0 -
300P 200PPM 300P 200PPM
10.0% 10.0% 10.0%
00 - Filter + Fan
01 - Filter + Smoke
02 - Filter + Low
Temperature
13 00 Y Y Y Y Y Y Y
Alarm Type 03 – Fan+ Smoke
04 – Fan+ Low
Temperature
05 - Smoke +Low
Temperature
00 - Voltage mode
18 Voltage\Current Mode 00 Y Y Y Y Y Y Y
Selection 01 - Current mode
00 – 0~10V When the configur
ation item 18 (Volt
01 - 2~10V
age\Current Mode
19 AO1 Voltage Output 02 - 10~0V 00 Y Y Y Y Y Y Y Selection) is set as
Mode 00, the configurati
03 - 10~2V on item 19 will be
valid.
20 00 - 4~20mA 00 Y Y Y Y Y Y Y

40
AO1 Current Output When the configur
Mode ation item 18 (Volt
age\Current Mode
01 - 20~4mA Selection) is set as
01, the configurati
on item 20 will be
valid.
00 - 0~10V When the configur
ation item 18 (Volt
01 - 2~10V
age\Current Mode
AO2 Voltage Output 02 - 10~0V
21 00 Y Y Y Y Y Y Y Selection) is set as
Mode
00, the configurati
03 - 10~2V on item 21 will be
valid.
00 - 4~20mA When the configur
ation item 18 (Volt
age\Current Mode
AO2 Current Output
22 00 Y Y Y Y Y Y Y Selection) is set as
Mode 01 - 20~4mA 01, the configurati
on item 22 will be
valid.
00 - 0~10V When the configur
ation item 18 (Volt
01 - 2~10V
age\Current Mode
AO3 Voltage Output 02 - 10~0V
23 00 Y Y Y Y Y Y Y Selection) is set as
Mode
00, the configurati
03 - 10~2V on item 23 will be
valid.
00 - 4~20mA When the configur
ation item 18 (Volt
age\Current Mode
AO3 Current Output
24 00 Y Y Y Y Y Y Y Selection) is set as
Mode 01 - 20~4mA 01, the configurati
on item 24 will be
valid.
00 – NC
25 01 Y Y Y Y Y Y Y
DO Mode 01 – NO
00 – NC
26 01 Y Y Y Y Y Y Y
DO2 Mode 01 – NO
27 00 – NC 01 Y Y Y Y Y Y Y

41
DO3 Mode 01 – NO
00 – NC
28 01 Y Y Y Y Y Y Y
DO4 Mode 01 – NO
0.0 - 0.0℃
1.0 – 1.0℃
……
29 The default The default The default The default The default The default The default
Temperature Control P 4.0 – 4.0℃ is 4 ℃ is 4 ℃ is 4 ℃ is 4 ℃ is 10 ℃ is 10 ℃ is 10 ℃
……
50.0 – 50.0℃
0 - 0s
15 - 15s
30 - 30s
...
105 - 105s
120 - 120s
135 - 135s
30 The default The default The default The default The default The default The default
Temperature Control I 150 - 150s is 600s is 600s is 600s is 600s is 30s is 30s is 30s
...
585 - 585s
600 - 600s
615 - 615s
...
1200 - 1200s
0.0 - 0%
5.0 - 5%
...
Normal Low-
35 20.0 - 20% 20.0 Y Y Y N Y Y Y
temperature Protection
...
45.0 - 45%
50.0 - 50%
39 Humidity Control P 0% 10.0 Y Y Y Y Y Y Y
1.0 - 1%

42
……
10.0 - 10%
……
20.0 - 20%
0 - 0s
15 - 15s
30 - 30s
...
105 - 105s
120 - 120s
135 - 135s
40 Humidity Control I The default The default The default The default The default The default The default
150 - 150s is 600s is 600s is 600s is 600s is 30s is 30s is 30s
...
585 - 585s
600 - 600s
615 - 615s
...
1200 - 1200s
00 – Alarm output As for application
01 - Auxiliary heating 4.4, this item may
41 DO Function Selection 02 - Auxiliary cooling 00 Y Y Y Y Y Y Y be set as 04, DO is
being overtime alar
03 - Auxiliary
m output.
Humidifying
0.0 - 0%
0.5 - 0.5% When the configur
1.0 - 1% ation item 41 (DO
Function Selectio
……
43 Humidity dead Range 5.0 N N Y N N N Y n) is not set as 03, t
5.0 - 5% he configuration it
…… em 43 will be vali
d.
9.5 - 9.5%
10.0 - 10%
45 the First Stage Dead 10.0 - 10% 30.0 Y Y Y Y Y Y Y
range of Auxiliary
15.0 - 15%

43
Output ……
30.0 - 30%
……
45.0 - 45%
50.0 - 50%
30.0 - 30%
35.0 - 35%
the Second Stage Dead ……
46 range of Auxiliary 60.0 - 60% 60.0 Y Y Y Y Y Y Y
Output
……
95.0 - 95%
100.0 - 100%
0,0 - 0℃
1.0 - 1℃ When the configur
ation item 4 (Mult
…… i-Temperature Sen
Compensation
47 15.0 - 15℃ 15.0 Y Y Y Y Y Y Y sor Setting) is set a
Switching Point
s 03, the configurat
……
ion item 47 will be
49.0 - 49℃ valid.
50.0 - 50℃
-95.0 - -95.0%
When the configur
-90.0 - -90.0%
ation item 4 (Mult
…… i-Temperature Sen
48 15.0 - 15.0% 15.0 Y Y Y Y Y Y Y sor Setting) is set a
Summer Compensation
s 03, the configurat
……
ion item 48 will be
90.0 - 90.0% valid.
95.0 - 95.0%
49 -35.0 - -35.0% -5.0 Y Y Y Y Y Y Y When the configur
Winter Compensation ation item 4 (Mult
-30.0 - -30.0%
i-Temperature Sen
…… sor Setting) is set a
-5.0 - -5.0% s 03, the configurat
ion item 49 will be
……
valid.
30.0 - 30.0%

44
35.0 - 35.0%
00 - Only
dehumidifying
01 - Maximum of
Dehumidification and dehumidifying and
50 Cooling Priority cooling 01 Y Y Y Y Y Y Y
02 - Minimum of
dehumidifying and
cooling
03 - Only cooling
30 - 30s
60 - 60s
51 Fan Start-up Delay 120 - 120s 60 Y Y Y Y Y Y Y
180 - 180S
330 - 330S
30 - 30s
60 - 60s
52 Fan Stop Delay 120 - 120s 60 Y Y Y Y Y Y Y
180 - 180S
330 - 330S
0 - 0Pa
25 – 25Pa
……
53 Converter P 20.0 N Y N N N Y N
500 - 500Pa
……
2500 - 2500Pa
0 - 0s
1 - 1s
2 - 2s
54 …… 30 N Y N N N Y N
Converter I
30 - 30s
……
5000 - 5000s
55 CO2 Concentration 0 - 0ppm 400 N N Y N N N Y

45
When fully closing new 100 - 100ppm
air valve
……
400 - 400ppm
……
1200 - 1200ppm
800 - 800ppm
900 - 900ppm
CO2 Concentration ……
56 1600 N N Y N N N Y
When fully opening 1600 - 1600ppm
new air valve
……
2000 - 2000ppm
0.0 - 0℃
1.0 - 1℃
Temperature
Overranging ……
57 Alarm(constant 3.0 - 3℃ 3.0 N N N Y N N N
temperature and
……
humidity)
4.0 - 4℃
5.0 - 5℃
0.0 - 0%
5.0 - 5%
Humidity Overranging ……
Alarm(constant
58 10.0 - 10% 10.0 N N N Y N N N
temperature and
humidity) ……
15.0 - 15%
20.0 - 20%
30 - 30s
Overranging Alarm 60 - 60s
Delay(constant
59 120 - 120s 60 N N N Y N N N
temperature and
humidity) 160 - 160S
320 - 320S
00 - Automatic
100 Manual\Automatic 0 Y Y Y Y Y Y Y
Mode Selection 01 - Manual

46
0.0 - 0%
When the configur
10.0 - 10%
ation item 100 (Ma
…… nual\Automatic M
101 50.0 - 50% 0.0 Y Y Y Y Y Y Y ode Selection) is se
AO1 Manual Output
…… t as 01, the configu
ration item 101 wil
90.0 - 90% l be valid.
100.0 - 100%
0.0 - 0%
10.0 - 10% When the configur
ation item 100 (Ma
…… nual\Automatic M
102 AO2 Manual Output 50.0 - 50% 0.0 Y Y Y Y Y Y Y ode Selection) is se
…… t as 01, the configu
ration item 102 wil
90.0 - 90% l be valid.
100.0 - 100%
0.0 - 0%
10.0 - 10% When the configur
…… ation item 100 (Ma
nual\Automatic M
103 AO3 Manual Output 50.0 - 50% 0.0 Y Y Y Y Y Y Y
ode Selection) is se
…… t as 01, the configu
90.0 - 90% ration item 103 wil
l be valid.
100.0 - 100%
00 When the configur
ation item 100 (Ma
nual\Automatic M
201 00 Y Y Y Y Y Y Y ode Selection) is se
DO1 Manual Output 01 t as 01, the configu
ration item 201 wil
l be valid.
00 When the configur
ation item 100 (Ma
nual\Automatic M
202 DO2 Manual Output 00 Y Y Y Y Y Y Y ode Selection) is se
01 t as 01, the configu
ration item 202 wil
l be valid.
203 DO3 Manual Output 00 00 Y Y Y Y Y Y Y When the configur

47
ation item 100 (Ma
nual\Automatic M
ode Selection) is se
01
t as 01, the configu
ration item 203 wil
l be valid.
00 When the configur
ation item 100 (Ma
nual\Automatic M
204 DO4 Manual Output 00 Y Y Y Y Y Y Y ode Selection) is se
01 t as 01, the configu
ration item 204 wil
l be valid.
300 Y Y Y Y Y Y Y
Software Version
301 Y Y Y Y Y Y Y
Production Date
00 - Not restore the
original settings
500 00 Y Y Y Y Y Y Y
Manufacture Date 01 - Restore the
original settings

48
Appendix II: Application Example
Model UB1121CH/EN- application 1.1, 1.4
24VAC
EGND

DO-1

AO-1
COM

COM

COM

COM

COM
DI-1

DI-2

UI-1

Model UB1121CH/EN- application 2, 5


24VAC
EGND

DO-1

AO-1
COM

COM

COM

COM

COM
DI-1

DI-2

UI-1

Model UB1121CH/EN - application 3, 6


24VAC
EGND

DO-1

AO-1
COM

COM

COM

COM

COM
DI-1

DI-2

UI-1

49
Model UB2204CH/EN - application 1, 3

Model UB2204CH/EN - application 2, 4

50
Model UB2221CH/EN - application 1, 4

Model UB4334SCH/EN – application 2, 3, 5


24VAC
EGND
COM

COM

COM

COM

COM
DO-1

AO-1

AO-2
DI-1

DI-2

UI-1

UI-2

24VAC 24VAC

220VAC

报警输入 温度传感器湿度传感器

风机运行状态检测

电加湿器

Model UB4334SCH/EN – application 1, 4, 5

51
Model UB4334SCH/EN – application 2, 6

24VAC

20VDC
EGND

DO-1

DO-2
DO-3

DO-4

AO-1

AO-2

AO-3
COM

COM

COM

COM

COM

COM

COM

COM
DI-1

DI-2
DI-3

UI-1

UI-2
UI-3

UI-4
24VAC 24VAC

220VAC

风机运行状态检测
温度传感器
湿度传感器
VSD
变频器
温度传感器(室外)
报警输入1 压力传感器
风机
/
电加湿器
风阀
报警输入2

/ /

/ /

Model UB4334SCH/EN – application 3, 7

As for more functions of the various models of different application modules, please refer to
“Introduction of Application".