DPS 4000 Series CAN Bus Pressure Transducer User Manual - GE ...
DPS 4000 Series CAN Bus Pressure Transducer User Manual - GE ...
DPS 4000 Series CAN Bus Pressure Transducer User Manual - GE ...
K296 Issue 1
ii DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual iii
Safety
To use this pressure transducer safely, you must use the data and
procedures in this publication. Use the pressure transducer only for the
specified applications (refer to section 1).
The warnings and cautions in this publication are as follows:
WARNING
• Do not interchange transducers between an oil system and a system
that uses fuel or gas. This can cause an explosion that can cause
death or injury, and/or damage to equipment.
• High pressures and temperatures are dangerous (refer to the
pressure limits in table 2-2). Be careful when you do work on
components connected to lines that have high pressures and heat.
Use the applicable protection and obey all safety precautions.
• Be careful when you do work on components with connections to an
electrical supply. When possible, do the work with the electrical
supply disconnected. Electrical shocks can cause death or injury.
CAUTION
• Until you are prepared to install the unit, keep it in the original
container with all the covers in position. The container and covers
prevent contamination and damage. When not in use, keep the
connections clean at all times, and put covers on the open
connections.
• Do not use high-pressure gas to remove dirt from the unit. This can
damage the sensor in the unit.
Before you start an operation or procedure in this publication, make sure that
you have the necessary skills (if necessary, with qualifications from an
approved training establishment). Follow good engineering practice at all
times.
Dangerous materials
There are no known dangerous materials used in this pressure transducer.
K296 Issue 1
iv DPS 4000 - User Manual
Technical support
For technical support, contact either the manufacturer or an approved
service agent (refer to section 5).
References
For more data, refer to these publications:
1. CANopen Application Layer and Communication Profile -
CiA Draft Standard DS-301 (Version 4.01)
2. CANopen Device Profile for Measurement Devices and Closed Loop
Controllers - CiA Draft Standard Proposal DSP-404 (Version 1.0)
3. CANopen Layer Setting Services and Protocol (LSS) -
CiA Draft Standard Proposal DSP-305 (Version 1.0)
4. CANopen Representation of SI Units and Prefixes -
CiA Draft Recommendation DRP-303-2 (Version 1.1)
Abbreviations
The abbreviations in this publication are as follows:
a Absolute (Pressure version)
ADC Analogue-to-Digital Converter
A/F Across the Flats (Dimension data)
AP Applied Pressure
ASCII American Standard Code for Information
Interchange
°C Celsius (Degrees)
CAN Controller Area Network
CANopen A set of standards that defines the operation of
devices across a CAN system.
K296 Issue 1
DPS 4000 - User Manual v
K296 Issue 1
vi DPS 4000 - User Manual
ms Millisecond
MΩ Megohm
NMT Network Management: One of the service
elements of the CAN Application Layer
NPT National Pipe Taper (a thread standard)
PDO Process Data Object
PIN Personal Identification Number
psi Pound-force per square inch
PV Process Value
SDO Service Data Object
SI Système International
S/N Serial Number
Tx Transmit
UNF Unified Fine (a thread standard)
VDC or Vdc Volts Direct Current
K296 Issue 1
DPS 4000 - User Manual vii
Table of Contents
Safety ......................................................................................................... iii
Dangerous materials ........................................................................ iii
Repair and maintenance ...........................................................................iv
Technical support .............................................................................iv
References ................................................................................................iv
Abbreviations .............................................................................................iv
Table of Contents ...................................................................................... vii
1. Introduction............................................................................................ 1-1
Applications ............................................................................................ 1-2
Summary of facilities .............................................................................. 1-2
Summary of the CANopen set of functions ............................................ 1-3
The pressure transducer you receive ..................................................... 1-3
2. Technical data ........................................................................................ 2-1
Physical data .......................................................................................... 2-1
Dimensions ................................................................................... 2-1
Weight .......................................................................................... 2-2
Compatible pressure media .......................................................... 2-2
Physical connections ..................................................................... 2-2
Performance data ................................................................................... 2-3
Pressure performance ................................................................... 2-3
Temperature performance ............................................................. 2-4
Accuracy – Pressure and temperature measurements ................. 2-4
Long-term stability ......................................................................... 2-4
Electrical data ......................................................................................... 2-5
Environmental data ................................................................................. 2-5
Pressure Equipment Directive ....................................................... 2-5
Electromagnetic Compatibility (EMC) ........................................... 2-5
Effects of vibration and shock ....................................................... 2-5
3. Installation data ..................................................................................... 3-1
Installation – An example CAN bus system ............................................ 3-1
Installation – Before you start ................................................................. 3-2
K296 Issue 1
viii DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual ix
K296 Issue 1
x DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 1-1
1. Introduction
The pressure transducers in the DPS 4000 series supply fast, accurate
pressure data through a Controller Area Network (CAN) bus interface.
These are the types of pressure transducer that are available:
• Gauge
• Absolute
• Differential
All the pressure transducers include these facilities:
• CANopen software standards
• Digital output
• CAN bus serial communications interface
• Isolated input/output.
K296 Issue 1
1-2 DPS 4000 - User Manual
Applications
The DPS 4000 series is for automated systems that use a CAN bus network
and CANopen software standards. The pressure transducers in the DPS
4000 series are ideal for automated systems that must have:
• A large amount of digital pressure data very quickly
• A high level of accuracy over a wide temperature range
• A sophisticated level of software control.
Summary of facilities
Because all the transducers in the DPS 4000 series use CANopen software
standards, each transducer includes a CANopen Object Dictionary. You can
use the CANopen Object Dictionary to do these primary tasks:
• Monitor the current pressure and temperature data.
• Tag the type of data. For example: Oil-mbar, H2O-mbar.
• Read the factory defined operating data. For example, the pressure
range, and the type of sensor.
• Set the update frequency for the pressure and temperature data.
• Set the pressure units. You can set SI units or you can set alternative
units.
• Monitor the current status.
• Read and set the last and next calibration date.
• Set new calibration values.
• Set local pressure and temperature limits for use with the internal
out-of-limit counters.
• Monitor the number of times the pressure is not in the specified limits.
• Monitor the number of times the temperature is not in the specified
limits.
• Restore all the factory default values for the CANopen Object
Dictionary.
You can use a standard CANopen software package to get access to the
contents of the CANopen Object Dictionary.
K296 Issue 1
DPS 4000 - User Manual 1-3
K296 Issue 1
1-4 DPS 4000 - User Manual
Make sure that the data is correct. The data below identifies the structure of
the ‘Ordering Information’:
1. The Model number. For example DPS4060:
DPS Basic Type Number
Code Pressure Type
40 Gauge or Absolute
41 Differential
K296 Issue 1
DPS 4000 - User Manual 2-1
2. Technical data
Physical data
Dimensions
Note:
All dimensions are in mm (not to scale).
(x ± 2): Identifies a dimension for versions
with the alternative electrical connection.
K296 Issue 1
2-2 DPS 4000 - User Manual
Weight
Type of transducer Electrical connection Nominal weight
Grams (g)
Gauge/Absolute 6-pin bayonet plug 180 g
Gauge/Absolute 6-core vented screened cable 215 g
Differential 6-pin bayonet plug 230 g
Differential 6-core vented screened cable 265 g
Physical connections
Table 2-1 supplies a nominal list of physical connections. For alternative
connections, speak to Technical support.
Table 2-1: Physical connections
Pressure connections Electrical connections
Male: G 1/8B (60° Internal cone) 6-Pin bayonet plug
Male: G 1/4B (60° Internal cone) 6-core vented screened cable
Male: G 1/4B (Flat end)
Male: 1/4" NPT
Male: 7/16" UNF
Male: M14 x 1.5 (to DIN 3863-8)
Female: G 1/4
Female: 1/4" NPT
K296 Issue 1
DPS 4000 - User Manual 2-3
Performance data
Pressure performance
These notes apply to table 2-2:
Pressure ranges: The table identifies the compensated pressure
ranges. This includes negative ranges (if you
specified this option – Maximum: - 1 bar) and the
zero-based ranges.
Over pressure limits: The transducers stay in calibration (with
negligible change) if you keep to the specified
limits.
For the differential pressure transducers, you
must keep to both the line pressure limits and the
over pressure limits.
Table 2-2: (Part of table) Pressure ranges and limits
Gauge pressure Absolute pressure Differential
transducers transducers pressure
transducers
Pressure mbar: 350, 700 mbar: 700 mbar: 350, 700
ranges bar: 1, 2, 3.5, 7, 10, bar: 1, 2, 3.5, 7, 10, bar: 1, 2, 3.5, 7, 10,
20, 35, 70 20, 35, 70 20, 35
Over Absolute vacuum Absolute vacuum Differential pressure
pressure limits to to from:
+4 x FS (maximum: +4 x FS (maximum: -2 x FS (maximum:
140 bar) 140 bar) -10 bar)
to
+4 x FS (maximum:
100 bar)
Pressure +4 x FS (maximum: Maximum: 200 bar Positive port:
containment 200 bar) +4 x FS (maximum:
limits 200 bar)
Negative port:
+4 x FS (maximum:
15 bar)
K296 Issue 1
2-4 DPS 4000 - User Manual
Temperature performance
Operating temperature range: - 40 °C to + 80 °C
Compensated temperature range: + 10 °C to + 60 °C
Note:
If you set the rate of new data to 100 Hz, this increases the noise level
for the data. The noise adds an uncertainty of 0.05% full-scale (FS) to
the accuracy figures in table 2-3.
Long-term stability
As a typical value, the long-term stability is better than 0.08% FS each year.
K296 Issue 1
DPS 4000 - User Manual 2-5
Electrical data
Power supply: 7.5 VDC to 30 VDC
Insulation resistance: Greater than 100 MΩ at 500 VDC:
- between the transducer body and all the
signal lines
- between the power supply lines and the CAN
bus data lines
Power consumption: Less than 1 Watt
Environmental data
Pressure Equipment Directive
Class of equipment: Pressure accessory, Category 1
K296 Issue 1
2-6 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 3-1
3. Installation data
This section supplies data to help you install the pressure transducer. When
you complete the installation, you can prepare the pressure transducer for
operation (refer to section 4).
CANopen
software
package
Identifies the signal line connections on the CAN bus (refer to table 3-1).
6-core cable connection - Cable screen to CAN_GND or an applicable earth
Represents the different pressure conditions in the example system.
Differential version only: + = High-pressure connection, - = Low-pressure
connection.
K296 Issue 1
3-2 DPS 4000 - User Manual
Installation – Procedures
WARNING
• Do not interchange transducers between an oil system and a system
that uses fuel or gas. This can cause an explosion that can cause
death or injury, and/or damage to equipment.
• High pressures and temperatures are dangerous (refer to the
pressure limits in table 2-2). Be careful when you do work on
components connected to lines that have high pressures and heat.
Use the applicable protection and obey all safety precautions.
• Be careful when you do work on components with connections to an
electrical supply. When possible, do the work with the electrical
supply disconnected. Electrical shocks can cause death or injury.
CAUTION
Until you are prepared to install the unit, keep it in the original container
with all the covers in position. The container and covers prevent
contamination and damage. When not in use, keep the connections clean at
all times, and put the covers on the open connections.
K296 Issue 1
DPS 4000 - User Manual 3-3
Electrical connections
Table 3-1 supplies the connection data for each type of electrical
connection.
Table 3-1: Electrical connections
6-Pin bayonet 6-core vented Data
plug screened cable
A Orange CAN_GND (CAN Ground)
B Red Positive supply
C White Negative supply
D Yellow CAN_H (CAN H bus line - dominant high)
E Blue CAN_L (CAN L bus line - dominant low)
F Black Not connected
Cable vent tube Used for gauge versions only. Connected to the
reference side of the silicon pressure sensor.
Cable screen Connected to the transducer body
Kevlar tape Yellow Kevlar tape. Breaking strain: 54 kg.
K296 Issue 1
3-4 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 4-1
4. Operation
The data that appears in this section includes:
• A description of the primary components in the pressure transducer
• The procedures to start and change the operation of the pressure
transducer
• The data available from the pressure transducer
Note:
0x identifies a hexadecimal value. Object 0x1800 02 = Index 0x1800,
Sub-index 0x02 (refer to appendix A).
K296 Issue 1
4-2 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 4-3
K296 Issue 1
4-4 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 4-5
K296 Issue 1
4-6 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 4-7
PV
Object 0x6100 01 Object 0x6130 01
Pressure Value Pressure Value
Y
Field Value X Process Value Y
(mbar) (pascal)
0 X FV
For a list of values you can use to get one of the alternative pressure units,
refer to appendix B.
K296 Issue 1
4-8 DPS 4000 - User Manual
You can reset the count when applicable. For example: after calibration.
K296 Issue 1
DPS 4000 - User Manual 4-9
You can reset the count when applicable. For example: after calibration.
You can reset the count when applicable. For example: after calibration.
K296 Issue 1
4-10 DPS 4000 - User Manual
You can reset the count when applicable. For example: after calibration.
K296 Issue 1
DPS 4000 - User Manual 5-1
5. Maintenance
WARNING
• High pressures and temperatures are dangerous (refer to the
pressure limits in table 2-2). Be careful when you do work on
components connected to lines that have high pressures and heat.
Use the applicable protection and obey all safety precautions.
• Be careful when you do work on components with connections to an
electrical supply. When possible, do the work with the electrical
supply disconnected. Electrical shocks can cause death or injury.
CAUTION
When not in use, keep the connections clean at all times, and put covers on
the open connections. The covers prevent contamination and damage.
You can do these maintenance tasks:
• Identify faults from the software
• Clean the unit
• Recalibrate the unit.
Note:
Druck can provide a calibration service that is traceable to
international standards.
You must return the unit to the supplier for these items:
• For all repairs
• For changes or upgrades to the internal software.
K296 Issue 1
5-2 DPS 4000 - User Manual
Maintenance – Cleaning
CAUTION
Do not use high-pressure gas to remove dirt from the unit. This can damage
the sensor in the unit.
1. If necessary, remove the unit.
2. Clean the unit with a lint-free cloth and a soft brush. If necessary,
make the cloth moist with a weak solution of detergent.
3. (For gauge versions with a 6-core vented screened cable) Make sure
that there is no blockage in the cable vent tube. If necessary, remove
the blockage.
4. Allow the unit to dry before you use it again.
K296 Issue 1
DPS 4000 - User Manual 5-3
Maintenance – Calibration
Druck supplies a calibration certificate with the pressure transducer. When
it is necessary to recalibrate the pressure transducer, use the procedure that
appears below (Druck recommends a minimum interval of once a year).
Note:
Druck can provide a calibration service that is traceable to
international standards.
Calibration – The equipment you need
Druck recommends that you use these items of equipment to calibrate the
unit:
• Pressure source - minimum accuracy: 0.05% of reading
• Digital thermometer - minimum accuracy: 1 °C
• A CANopen software package to get access to the contents of the
CANopen Object Dictionary (refer to appendix A).
Druck make a range of precision calibrators, pressure controllers,
dead-weight testers, and calibration software. Please refer to Druck for
further information on these products.
K296 Issue 1
5-4 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual 5-5
K296 Issue 1
5-6 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual A-1
Appendix A
DPS 4000 Series – CANopen Object Dictionary
This appendix contains data for the primary objects that appear in these
areas of the CANopen Object Dictionary:
• Communication Profile Area: 0x1000 – 0x1FFFF
• Manufacturer Specific Profile Area: 0x2000 – 0x2FFFF
• Standardised Device Profile Area: 0x6000 – 0x6FFFF
The data appears in a table with two parts. Part A identifies the structure of
the applicable object entries. Part B identifies some of the values and data
applicable to each object entry.
Note:
0x identifies a hexadecimal value.
R = Read, W=Write.
Refer to References for more data.
K296 Issue 1
A-2 DPS 4000 - User Manual
0x1000 / 0x1017
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x1000 0x00 Device Type 4 UNSIGNED32
0x1001 0x00 Error Register 1 UNSIGNED8
0x1005 0x00 COB-ID Sync message 4 UNSIGNED32
0x1008 0x00 Device Name 48 VIS_STNG48
0x100C 0x00 Guard Time 2 UNSIGNED16
0x100D 0x00 Life Time 1 UNSIGNED8
0x100E 0x00 Node Guarding ID 4 UNSIGNED32
0x1010 Store Parameters
0x00 No of entries 1 UNSIGNED32
0x01 Save All Parameters 4 UNSIGNED32
0x1011 Restore Parameters
0x00 Number of Entries 1 UNSIGNED32
0x01 Load All Parameters 4 UNSIGNED32
K296 Issue 1
DPS 4000 - User Manual A-3
0x1000 / 0x1017
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x1000 0x00 R 0x00020194 DSP404 Analogue Input
0x1001 0x00 R 0 No errors
0x1005 0x00 RW 0x080 ID 128, No SYNC generation
0x1008 0x00 R DPS4xx0 DK226v xx.xx
0x100C 0x00 RW 0 Error control: Off
0x100D 0x00 RW 0 Error control: Off
0x100E 0x00 RW 0x701 0x700 + Node ID = ID 1793
0x1010
0x00 R 1
0x01 R 0x00000002 Saves autonomously
0x1011
0x00 R 1
0x01 RW 0x00000001 0x64616F6C = doal (ASCII):
To reapply all the factory values.
0x1012 0x00 R 0x100 ID 256
0x1014 0x00 R 0x081 0x080 + Node ID = ID 129
0x1017 0x00 RW 0 Error control: Off
K296 Issue 1
A-4 DPS 4000 - User Manual
0x1018 / 0x1A00
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x1018 Identity
0x00 Number of Entries 1 UNSIGNED8
0x01 Vendor ID 4 UNSIGNED32
0x02 Product Code 4 UNSIGNED32
0x03 Revision Number 4 UNSIGNED32
0x04 Serial Number 4 UNSIGNED32
0x1200 Server SDO
0x00 Number of Entries 1 UNSIGNED8
0x01 COB-ID Client-Server 4 UNSIGNED32
0x02 COB-ID Server-Client 4 UNSIGNED32
0x1800 Transmit PDO
0x00 Number of Entries 1 UNSIGNED8
0x01 COB-ID 4 UNSIGNED32
0x02 Transmission Type 1 UNSIGNED8
0x05 Event Timer 2 UNSIGNED16
0x1A00 Transmit PDO Mapping
0x00 Number of Entries 1 UNSIGNED8
0x01 Mapping 1 4 UNSIGNED32
0x02 Mapping 2 4 UNSIGNED32
0x03 Mapping 3 4 UNSIGNED32
0x04 Mapping 4 4 UNSIGNED32
K296 Issue 1
DPS 4000 - User Manual A-5
0x1018 / 0x1A00
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x1018
0x00 R 4
0x01 R 0x00000050 DRUCK
0x02 R Model No. Example: 4160
0x03 R Revision No. Example: 0x00010001
0x04 R Serial No.
0x1200
0x00 R 2
0x01 R 0x601 0x600 + Node ID = ID 1537
0x02 R 0x581 0x580 + Node ID = ID 1409
0x1800
0x00 R 5
0x01 R 0x181 0x180 + Node ID = ID 385
0x02 RW 1 Transmit on every SYNC
0x05 RW 0 Not used
0x1A00
0x00 R 4
0x01 RW 0x61300120 Process Value (Pressure)
0x02 RW 0x20040020 Acquisition Time
0x03 RW 0x00000000 Not used
0x04 RW 0x00000000 Not used
K296 Issue 1
A-6 DPS 4000 - User Manual
0x2003 / 0x2206
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x2003 0x00 Current Time 6 TIME_OF_DAY
K296 Issue 1
DPS 4000 - User Manual A-7
0x2003 / 0x2206
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x2003 0x00 R 0 The current time
(usually set by 0x1012)
0x2004 0x00 R 0 The time the ADC supplied the
data (in ms after midnight)
0x2005 0x00 R 0
0x2006 0x00 RW 0 Count: More than the local limit
0x2007 0x00 RW 0 Count: Less than the local limit
0x2008 0x00 RW 0 Count: More than the local limit
0x2009 0x00 RW 0 Count: Less than the local limit
0x210A 0x00 RW 60 60 = 10 Hz (Rate of new data)
2 = 100 Hz (Rate of new data)
0x210B 0x00 RW 20 20 = 10 Hz (Rate of new data)
200 = 100 Hz (Rate of new data)
0x2200 0x00 RW 0 0 = No write access
4118 = Write access
0x2201 0x00 RW Year of calibration To write, refer to 0x2200
0x2202 0x00 RW Month of calibration To write, refer to 0x2200
0x2203 0x00 RW Day of calibration To write, refer to 0x2200
0x2204 0x00 RW Year of next calibration To write, refer to 0x2200
0x2205 0x00 RW Month of next calibration To write, refer to 0x2200
0x2206 0x00 RW Day of next calibration To write, refer to 0x2200
K296 Issue 1
A-8 DPS 4000 - User Manual
0x2207 / 0x2304
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x2207 0x00 Pressure Gain 4 REAL32
K296 Issue 1
DPS 4000 - User Manual A-9
0x2207 / 0x2304
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x2207 0x00 RW 1 Gain correction. To write, refer to
0x2200.
0x2208 0x00 RW 0 Offset correction in mbar. To
write, refer to 0x2200.
0x2209 0x00 RW 1 Gain in °C. To write, refer to
0x2200.
0x220A 0x00 RW 0 Offset in °C. To write, refer to
0x2200.
0x2300 0x00 R Minimum pressure Calibrated pressure value in mbar
(Minimum)
0x2301 0x00 R Maximum pressure Calibrated pressure value in mbar
(Maximum)
0x2302 0x00 R 0 = Absolute Mode of operation
128 = Gauge
255 = Differential
0x2303 0x00 R 100 Nominal interval for new data:
100 ms = 10 Hz operation
10 ms = 100 Hz operation
0x2304 0x00 RW [blank] Free-format text
Maximum: 10 characters
K296 Issue 1
A-10 DPS 4000 - User Manual
0x6100 / 0x6122
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x6100 Field Value – FP
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 4 REAL32
0x6101 Field Physical Units
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 4 UNSIGNED32
0x6110 Sensor Type
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 2 UNSIGNED16
0x6120 Input Scaling 1 FV – FP
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 4 REAL32
K296 Issue 1
DPS 4000 - User Manual A-11
0x6100 / 0x6122
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x6100
0x00 R 1
0x01 R 0 Pressure (Field Value)
0x6101
0x00 R 1
0x01 R 0xFD4E0000 = mbar Units for 0x6100 01
0x6110
0x00 R 1
0x01 R 90 Pressure Transducer
0x6120
0x00 R 1
0x01 RW 0 Scale-factor: Lower calibration
point = zero (Field Value)
0x6121
0x00 R 1
0x01 RW 0 Scale-factor: Lower calibration
point = zero (Process Value)
0x6122
0x00 R 1
0x01 RW 1 Scale-factor: Higher calibration
point = mbar (Field Value)
K296 Issue 1
A-12 DPS 4000 - User Manual
0x6123 / 0x6131
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x6123 Input Scaling 2 PV – FP
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 4 REAL32
K296 Issue 1
DPS 4000 - User Manual A-13
0x6123 / 0x6131
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x6123
0x00 R 1
0x01 RW 1 = mbar Scale-factor: Higher calibration
0.001 = bar point (Process Value)
0.0145038 = psi
0x6124
0x00 R 1
0x01 RW 0 Offset = 0
0x6125
0x00 R 1
0x01 RW 0x00000000 0x6F72657A = orez (ASCII):
To reset 0x6100 01 to zero.
0x6130
0x00 R 2
0x01 R 0 Pressure (Process Value)
0x02 R 0 Temperature (Process Value)
0x6131
0x00 R 2
0x01 RW 0xFD4E0000 = mbar Units for 0x6130 01
0x004E0000 = bar
0x00A00000 = psi
0x02 RW 0x002D0000 = °C Units for 0x6130 02
K296 Issue 1
A-14 DPS 4000 - User Manual
0x6148 / 0x6150
Table A-1 (Part A): Object Dictionary – Structure
Index Sub- Name Data Data Type
Index Size
0x6148 Span Start – FP
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 4 REAL32
0x02 Temperature Value 4 REAL32
0x6149 Span End – FP
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 4 REAL32
0x02 Temperature Value 4 REAL32
0x6150 Status
0x00 Number of Entries 1 UNSIGNED8
0x01 Pressure Value 1 UNSIGNED8
0x02 Temperature Value 1 UNSIGNED8
K296 Issue 1
DPS 4000 - User Manual A-15
0x6148 / 0x6150
Table A-1 (Part B): Object Dictionary – Values
Index Sub- Read / Default value Result + Data
Index Write (If applicable)
0x6148
0x00 R 2
0x01 RW 0 Local pressure limit (minimum)
0x02 RW 0 Local temperature limit (minimum)
0x6149
0x00 R 2
0x01 RW 0 Local pressure limit (maximum)
0x02 RW 0 Local temperature limit (maximum)
0x6150
0x00 R 2
0x01 R 0x00 Status: Local limits (Pressure)
0x02 R 0x00 Status: Local limits (Temperature)
K296 Issue 1
A-16 DPS 4000 - User Manual
K296 Issue 1
DPS 4000 - User Manual B-1
Appendix B
Data for the alternative pressure units
The basic operation of the pressure transducer uses mbar for the pressure
calculations. Druck uses the ‘Ordering Information’ that you supply to set the
default units for the pressure output. The default units are: mbar, bar, or psi.
Table B-1 supplies the values you can use to get an output in one of the
alternative pressure units.
Table B-1: (Part of table) Values to get alternative pressure units
Pressure units CANopen value (Units) Scale-factor
(Object: 0x6131 01) (Object: 0x6123 01)
mbar millibar 0xFD4E0000 1
bar bar 0x004E0000 0.001
Pa (N/m2) pascal (newton per 0x00220000 100
square metre)
hPa hectopascal 0x02220000 1
kPa kilopascal 0x03220000 0.1
Mpa Megapascal 0x06220000 0.0001
mmHg millimetre of mercury 0x00A00000 (Note) 0.7500616
cmHg centimetre of 0x00A00000 (Note) 0.07500616
mercury
mHg metre of mercury 0x00A00000 (Note) 0.0007500616
inHg inch of mercury 0x00A00000 (Note) 0.02953
kg/cm2 kilogram-force per 0x00A00000 (Note) 0.001019716
square centimetre
kg/m2 kilogram-force per 0x00A00000 (Note) 10.19716
square metre
mmH20 millimetre of water 0x00A00000 (Note) 10.19716
cmH20 centimetre of water 0x00A00000 (Note) 1.019716
mH20 metre of water 0x00A00000 (Note) 0.01019716
torr torr 0x00A00000 (Note) 0.7500616
K296 Issue 1
B-2 DPS 4000 - User Manual
K296 Issue 1