KV Series
Expansion Unit Instruction Manual
CONTENTS
Safety Precautions ....................................................................................... 1
Precautions on Regulations and Standards ........................................................ 2
Inspection and Maintenance ........................................................................ 3
Specifications ............................................................................................... 4
KV-E4X/E8X/E16X (Expansion input unit) ................................................... 5
KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P) (Expansion output unit) .............. 8
KV-E4XR/E4XT(P) (Expansion I/O unit) .................................................... 13
Installation environment ............................................................................. 16
Installation position ..................................................................................... 16
Installation procedure ................................................................................. 17
Cautions on wiring for each unit ................................................................. 18
Contact protection ..................................................................................... 19
Connecting KV Series Expansion Units ..................................................... 20
Dimensions ................................................................................................ 22
Metal fixture for screw tightening ............................................................... 23
WARRANTIES AND DISCLAIMERS .......................................................... 24
SAFETY PRECAUTIONS
This instruction manual describes the operation and function of the KV.
Read this manual carefully to ensure safe use and maximum performance
from your KV.
Symbols
The following symbols alert you to important messages. Be sure to read
these messages carefully.
WARNING
Failure to follow instruction may lead to injury. (electric shock,
burn, etc.)
CAUTION Failure to follow instructions may lead to product damage.
Note: Provides additional information on proper operation.
General Precautions
• Do not use this product for the purpose to protect a human body or a part
of human body.
• This product is not intended for use as explosion-proof product. Do not
use this product in a hazardous location and/or potentially explosive
atmosphere.
• At startup and during operation of the Ladder Builder for KV, be sure to
monitor the functions and performance of the KV Sereis basic unit and the
KV CPU.
• We recommend that you take substantial safety measures to avoid any
damage in the event a problem occurs.
• Do not open or modify the KV or use it in any way other than described in
the specifications.
• When the KV is used in combination with other instruments, functions and
performance may be degraded, depending on operating conditions and
the surrounding environment.
96M13742
1
PRECAUTIONS ON REGULATIONS AND STANDARDS
CE and UKCA Markings
KEYENCE Corporation has confirmed that this product complies with the essential
requirements of the applicable EU Directive(s) and UK regulations, based on the
following specifications. Be sure to consider the following specifications when using
this product in the Member States of European Union and in the United Kingdom.
EMC Directive (CE) and Electromagnetic Compatibility Regulations (UKCA)
• Applicable Standard EMI: (BS)EN61131-2, Class A
EMS: (BS)EN61131-2
When using a relay output type unit (whose model name ends with "R"),
connect spark killers having the appropriate withstand voltage against the
load to the output terminals in parallel to contacts (because the unit
discharges when a relay contact becomes open and noise is generated). In
our experiments, we use the following models of spark killers.
XEB0101 0.1 µF-10 Ω manufactured by OKAYA DENKI SANGYO
The following 1-turn ferrite core is added to the AC power input circuit of the
KV-40AR/T, the KV-24AR/T and to the DC power input circuit of the KV-
40DR/T.
ZCAT3035-1330 manufactured by TDK
Remarks: These specifications do not give any guarantee that the end-
product with this product incorporated complies with the essential require-
ments of EMC Directive and Electromagnetic Compatibility Regulations. The
manufacturer of the end-product is solely responsible for the compliance on
the end-product itself according to EMC Directive and Electromagnetic
Compatibility Regulations.
Low-Voltage Directive (CE) and Electrical Equipment (Safety) Regulations (UKCA)
The Low-voltage Directive is applied to Relay output type only.
• Applicable standard (BS)EN61010-1
(BS)EN61010-2-201
• Over voltage category II
• Use insulated type crimp-style terminals.
• For wiring materials, use lead wires whose sheath is 0.4 mm or more.
• The KV Series is allowed to be installed in a front installation only.
(Spacers for expansion units are not available.)
• When installing this product, it must be installed in an enclosure (Industrial
control panel) with IP 54 or higher.
• For wiring to the Power input terminal, Input terminal block and Output
Terminal block, use stranded copper wire having a gage of AWG#16 to
#24. The tightening torque is 0.5 N•m.
• Indoor use only.
• Install at an altitude of 2000 m or less.
2
INSPECTION AND MAINTENANCE
Inspection
While basic units and other units have been used for a long period of time,
the connector connection area may become loose, the battery may wear out,
or another nonconformity may occur in operation.
To avoid any nonconformities, inspect the basic units, other units, and the
wiring periodically. The major inspection items are as follows.
• Check to ensure that the connector is not disconnected or loose.
• Check to ensure that terminals on terminal plates are not loose.
• Check to ensure that the wiring cables among units and each equipment
are not damaged.
Maintenance
While basic units and other units have been used for a long period of time,
dirt will adhered. Wipe off any collected dirt with a clean, dry cloth.
Wipe off any dust and dirt that has collected on small and narrow portions
with cotton swabs.
Be sure to turn off the power before starting any inspection or maintenance.
3
SPECIFICATIONS
Item Specifications
AC power type DC power type
Power supply type KV-10AR/AT(P) KV-16AR/AT(P) KV-10DR/DT(P) KV-16DR/DT(P)
Basic KV-24AR/AT(P) KV-40AR/AT(P) KV-24DR/DT(P) KV-40DR/DT(P)
Input supply voltage units 100 to 240 V AC (± 10%) 24 V DC (+10%, -20%)
Allowable
Less than 40 ms Less than 2 ms
instantaneous time
KV-10AR/DR: 100 mA or less KV-10AT/DT: 80 mA or less KV-10ATP/DTP: 85 mA or less
KV-16AR/DR: 120 mA or less KV-16AT/DT: 90 mA or less KV-16ATP/DTP: 100 mA or less
Basic units
KV-24AR/DR: 140 mA or less KV-24AT/DT: 100 mA or less KV-24ATP/DTP: 105 mA or less
KV-40AR/DR: 180 mA or less KV-40AT/DT: 120 mA or less KV-40ATP/DTP: 130 mA or less
Internal current
consumption KV-E4X: 20 mA or less KV-E8X: 25 mA or less KV-E16X: 35 mA or less
(converted into Expansion KV-E4T: 25 mA or less KV-E8T(P): 40 mA or less KV-E16T: 60 mA or less
24 V DC value) units
KV-E4R: 40 mA or less KV-E8R: 70 mA or less KV-E16TP: 70 mA or less
KV-E4XT(P): 30 mA or less KV-E4XR: 45 mA or less KV-E16R: 110 mA or less
KV-D20 Operator interface panel: 60 mA or less
Others
KV-P3E(01) Handheld programmer: 65 mA or less
0 to +50°C (32 to 122°F), No freezing
Surrounding air temperature
0 to +45°C (32 to 113°F) [KV-P3E(01)], No freezing
Relative humidity 35 to 85%, No condensation
Ambient storage
-20 to +70°C (-4.0 to 158°F), No freezing
temperature
1,500 V AC for 1 minute
Withstand voltage (Between power terminal and I/O terminals
as well as between entire external terminals and case)
1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by noise simulator)
Noise resistance
In conformance with EN standard (EN61000-4-2/-3/-4/-6)
In conformance to JIS C0041, 150 m/s2 (150 G),working time: 11 ms,
Impact resistance
twice in each of X, Y and Z axis directions
10 to 55 Hz, double amplitude: 1.5 mm or less, 2 hours in each of X, Y and
Vibration resistance
Z axis directions (1 G or less when attached to DIN rail)
50 MΩ or more
Insulation resistance (Between power terminal and I/O terminals as well as
between entire external terminals and case by 500 V DC megohmmeter)
Operating atmosphere No excessive dust or corrosive gases allowed.
KV-10AR: Approx. 250 g KV-10DR: Approx. 150 g KV-16AR: Approx. 300 g
KV-16DR: Approx. 190 g KV-24AR: Approx. 350 g KV-24DR: Approx. 240 g
KV-40AR: Approx. 450 g KV-40DR: Approx. 330 g KV-10AT(P): Approx. 240 g
Basic units
KV-10DT(P): Approx. 140 g KV-16AT(P): Approx. 280 g KV-16DT(P): Approx. 180 g
KV-24AT(P): Approx. 330 g KV-24DT(P): Approx. 210 g KV-40AT(P): Approx. 410 g
Weight KV-40DT(P): Approx. 280 g
KV-E4X: Approx. 80 g KV-E8X: Approx. 100 g KV-E16X: Approx. 130 g
Expansion KV-E4T: Approx. 80 g KV-E8T(P): Approx. 100 g KV-E16T(P): Approx. 130 g
units KV-E4R: Approx. 100 g KV-E8R: Approx. 130 g KV-E16R: Approx. 190 g
KV-E4XT(P): Approx. 100 g KV-E4XR: Approx. 120 g
Others KV-P3E(01): Approx. 230 g
4
KV-E4X/E8X/E16X (EXPANSION INPUT UNIT)
Part names and functions
1. Input terminal block
C1 1 3 IN
0 2
0 1
2. Input indicator lamps
READY
/ERROR 2 3
2. Input indicator lamps
V2 V4
V1 V3 V5 IN
Input specifications
Model KV-E4X KV-8EX KV-E16X
Unit type 4-point input 8-point input 16-point input
Number of inputs 4 8 16
External connection method Terminal plate
Maximum input rating 26.4 V DC
Input voltage 24 V DC, 5.3 mA
Minimum ON voltage 19 V
Maximum OFF current 2 mA
Input impedance 4.3 kΩ
Common method 4 points/common
Input time constant
For both rising (OFF ➞ ON) and falling (ON ➞ OFF) operations,
(Changed in two steps by special
10 ms: 10 ms ± 20%, 10 µs: 10 µs ± 20%
utility relays 2609 to 2612)
➮ For more about the general specifications, refer to "Specifications" on page 4.
5
Terminal layout drawings and input circuit diagrams
KV-E4X (4-point expansion input unit)
■ Terminal layout drawing ■ Input circuit diagram
Sensor
C1 1 3
Three-wire
Three-wire
Three-wire
Three-wire
Photocoupler
tipe
tipe
tipe
tipe
4.3 KΩ insulation
Internal circuit
0 2 0 to 3
Blue
Blue
Blue
Blue
Black
Black
Black
Black
Brown
Brown
Brown
Brown
510 Ω
C1
C1 1 3
• V1 to V5 are short-
circuited inside
0 2
(so they can be used as
a relay terminal block).
Internal Circuit
V2 V4
V2 V4
V1 V3 V5
V1 V3 V5
Three-wire
Three-wire
Three-wire
Photocoupler
tipe
tipe
tipe
tipe
4.3 KΩ insulation
0 to 3
Internal circuit
0 2 V1 4 to 7
Black
Black
Black
Black
Blue
Blue
Blue
Blue
Brown
Brown
Brown
Brown
510 Ω
C1
C2
C1 1 V2
3
• C1 and C2 are each
0 2
V1
independent.
• V1 to V2 and V3 to V4 are
short-circuited inside
respectively (so they can
be used as relay terminal
Internal Circuit plates).
4 6 V3
C2 5 7 V4
4 6
V3
C2 5 7
V4
Brown
Brown
Brown
Brown
Black
Black
Black
Black
Blue
Blue
Blue
Blue
Three-wire
Three-wire
Three-wire
Three-wire
tipe
tipe
tipe
tipe
Sensor
6
C3
C1
8
0
9
1
10
3
11
C2
12
5
C4 13
6
14
7
15
■ Terminal layout drawing
Blue Blue
C3
C1
Three-wire Three-wire
KV-E16X (16-point expansion input unit)
Brown Brown
8
0
tipe tipe
Black Black
Blue Blue
Three-wire Three-wire
Brown Brown tipe
1
tipe
4 to 7
0 to 3
12 to 15
8 to 11
C4
C3
C2
C1
Black Black
Blue Blue
Three-wire Three-wire
tipe Brown Brown tipe
2
10
Black Black
4.3 KΩ
Blue Blue
510 Ω
Three-wire Three-wire
tipe Brown Brown tipe
3
11
Black Black
Blue Blue
C2
C4
Sensor
Sensor
Three-wire Three-wire
Brown Brown
4
tipe tipe
Black 12 Black
Internal Circuit
Blue Blue
Three-wire Three-wire
insulation
■ Input circuit diagram
Photocoupler
Black Black
Blue Blue
Three-wire Three-wire
Internal circuit tipe Brown Brown tipe
6
14
Black Black
Blue Blue
Three-wire Three-wire
tipe Brown Brown tipe
7
15
Black Black
7
KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P)
(EXPANSION OUTPUT UNIT)
Part names and functions
1. Output terminal block
C1 1 3 OUT
0 2
0 1
2. Output indicator lamps
READY
/ERROR 2 3
2. Output indicator lamps
V2 V4
V1 V3 V5 OUT
8
Output specifications
KV-E4R/E8R/E16R (Relay output type)
Model KV-E4R KV-E8R KV-E16R
Unit type 4-point relay output 8-point relay output 16-point relay output
Number of outputs 4 8 16
Output type Relay
External connection method Terminal plate
Rated load voltage 250 V AC/30 V DC 2 A (inductive load) 4 A (resistive load)
Rated output current 2A/point (inductive load) 4 A/point (resistive load) 4A/common
ON resistance 50 mΩ or less
Common method 4 points/common
Rising operation time (OFF ➞ ON) 10 ms or less
Falling operation time (ON ➞ OFF) 10 ms or less
Electrical: 100,000 times or more (20 times/min)
Relay service life
Mechanical: 20,000,000 times or more
Relay replacement Not allowed
0 2
C1 1 3
0 2
Internal circuit
V2 V4
V2 V4
V1 V3 V5
V1 V3 V5
0 to 3
Internal circuit
C1
9
KV-E8R (8-point expansion output unit (relay output type))
■ Terminal layout drawing ■ Output circuit diagram
C1 1 3 V2
0 to 3
0 2 V1 4 to 7
Internal circuit
C1 1 3
V2
0 2
C1
V1
C2
4 6 V3
4 6 V3
C2 5 7 V4
C2 5 7 V4
0 2 4 6
C1 1 3 C2 5 7
0 2 4 6
Internal circuit
8 10 12 14
C3 9 11 C4 13 15
0 to 3 8 10 12 14
4 to 7
Internal circuit
8 to 11
C3 9 11 C4 13 15
12 to15
C1
C2
C3
C4
• C1 and C4 are each independent.
10
Output specifications
KV-E4T/E8T(P)/E16T(P) (Transistor output type(NPN/PNP))
Model KV-E4T KV-E8T(P) KV-E16T(P)
Unit type 4-point transistor output 8-point transistor output 16-point transistor output
Number of outputs 4 8 16
Output type Transistor (NPN)/(PNP)
External connection method Terminal plate
Rated load voltage 30 V DC
Rated output current 0.5 A/point(NPN), 0.3 A/point(PNP)
Leak current in OFF status 100 µA or less
Residual voltage in ON status 0.8 V or less
Common method Shared inside
Rising operation time (OFF ➞ ON) 50 µs or less
Falling operation time (ON ➞ OFF) 250 µs or less
C1 1 3
0 2
C1 1 3
0 2
Internal circuit
V2 V4 V2 V4
V1 V3 V5 V1 V3 V5
Insulating
power
supply
Internal 0 to 3
circuit
C1
11
KV-E8T(P) (8-point expansion output unit (transistor output type))
■ Terminal layout drawing ■ Output circuit diagram
*1 NPN
C1 1 3 V2
Insultating
0 2 V1 power
supply
C1 1 3 V2 Internal 0 to 7
circuit
0 2 V1
C1
C2
C2
C1
Internal circuit
4 6 V3
C2 5 7 V4 4 6 V3 0 to 7
Insultating
power
supply
C2 5 7 V4
• V1 to V2 and V3 to V4 are
*1
short-circuited inside (so
they can be used as relay
terminal plates).
*1 For KV-E8TP
0 2 4 6
C1 1 3 C2 5 7
0 2 4 6
Internal circuit
8 10 12 14
C3 9 11 C4 13 15 8 10 12 14
C3 9 11 C4 13 15
NPN PNP
Insultating C4 * *
power C3
supply
C2
0 to 15 C1
Internal
Internal circuit
circuit
* For KV-E16TP
C1 0 to 15
C2 Insultating
C3 power
supply
C4
12
KV-E4XR/E4XT(P) (EXPANSION I/O UNIT)
Part names and functions
1. Input terminal block
C1 X1 X3 V2 IN
X0 X2 V1
3. Input indicator lamps
0 1 2 3
READY
/ERROR 0 1 2 3
Y0 Y2 V3
C2 Y1 Y3 V4 OUT
Input specifications
Item Specifications
External connection method Terminal plate
Maximum input rating 26.4 V DC
Input voltage 24 V DC, 5.3 mA
Minimum ON voltage 19 V
Maximum OFF current 2 mA
Input impedance 4.3 kΩ
Common method 4 points/common
Input time constant For both rising (OFF ➞ ON) and falling (ON ➞ OFF) operations,
(Changed in two steps by special 10 ms: 10 ms ± 20%
utility relays 2609 to 2612) 10 µs: 10 µs ± 20%
➮ For more about the general specifications, refer to "Specifications" on page 4.
13
Output specifications
KV-E4XR (Relay output type)
Item Specifications
Output type Relay
External connection method Terminal plate
Rated load voltage 250 V AC/30 V DC 2 A (inductive load) 4 A(resistive load)
Rated output current 2A/point (inductive load) 4A/point (resistive load) 4A/common
ON resistance 50 mΩ or less
Common method 4 points/common
Rising operation time (OFF ➞ ON) 10 ms or less
Falling operation time (ON ➞ OFF) 10 ms or less
Relay service life Electrical: 100,000 times or more (20 times/min), Mechanical: 20,000,000 times or more
Relay replacement Not allowed
V1 X2 X0
V2 X3 X1 C1
Photocoupler
4.3 KΩ insulation Internal circuit
X0 to X3
Brown
Brown
Brown
Brown
510 Ω
Black
Black
Black
Black
Blue
Blue
Blue
Blue
C1
Three-wire
Three-wire
Three-wire
Three-wire
Y0 Y2 V3
tipe
tipe
tipe
tipe
C2 Y1 Y3 V4
• V1 to V2 and V3 to V4 are
Sensor short-circuited inside
(so they can be used as
relay terminal plates).
■ Output circuit diagram
Internal circuit
Y0 to Y3
Internal circuit
Y0 Y2 V3
C2
C2 Y1 Y3 V4
14
KV-E4XT(P) (Transistor output type)
Item Specifications
Output type Transistor (NPN)/(PNP)
External connection method Terminal plate
Rated load voltage 30 V DC
Rated output current 0.5 A/point (NPN), 0.3 A/point (PNP)
Leak current in OFF status 100 µA or less
Residual voltage in ON status 0.8 V or less
Common method 4 points/common
Rising operation time (OFF ➞ ON) 50 µs or less
Falling operation time (ON ➞ OFF) 250 µs or less
C1 X1 X3 V2 Internal Circuit
X0 X2 V1
V1 X2 X0
V2 X3 X1 C1
Photocoupler
4.3 KΩ insulation
Internal circuit
X0 to X3
Brown
Brown
Brown
Brown
510 Ω
Black
Black
Black
Black
Blue
Blue
Blue
Blue
C1
Three-wire
Three-wire
Three-wire
Three-wire
Y0 Y2 V3
tipe
tipe
tipe
tipe
C2 Y1 Y3 V4
Sensor • V1 to V2 and V3 to V4 are
short-circuited inside (so
they can be used as relay
terminal plates).
Internal Y0 to Y3
circuit
Y0 to Y3
Y0 Y2 V3 C2 Insultating
power
supply
C2 Y1 Y3 V4
* For KV-E4XTP
15
INSTALLATION ENVIRONMENT
• Locations exposed to direct sunlight
• Locations whose ambient temperature is outside the allowable range of 0
to +50°C (32 to 122°F)
• Locations whose ambient humidity is outside the allowable range of 35 to
85% RH
• Locations subject to drastic temperature change where condensation may
occur
• Locations with corrosive or flammable gases
• Locations with excessive dust, salt, iron powder, or soot
• Locations subject to direct vibrations and impacts
• Locations subject to splashes of water, oil, chemicals, etc.
• Locations where a strong magnetic or electrical field is generated
CAUTION
Units are made of synthetic resin. If the unit surface touches a solvent
with a strong dissolving force, it could melt. Keep such solvents away
from the units.
INSTALLATION POSITION
Installation direction
When attaching a unit inside a panel, install the unit so that the front face
(equipped with the access window, communication ports, etc.) faces front or
upward.
Installation on ceiling
Correct Incorrect
Correct*
* See page 3.
Incorrect
16
INSTALLATION PROCEDURE
This section describes how to attach a connected unit directly to a panel, to
a DIN rail, or to a DIN rail with an expansion unit spacer.
■ Attaching a unit directly to a panel
Attach a metal fixture for screw tightening to a KV Series basic unit with set
screws. Then, attach the basic unit with a metal fixture directly to the panel.
17
Attaching the spacer to the expansion unit
Insert the upper claw of the spacer into the upper groove of the expansion
unit and press the lower claw of the spacer until you hear a click.
Sliding tabs
DIN rail
WARNING
During operation and shortly after power OFF, this equipment is heated up.
Don’t touch it to avoid a burn.
18
■ When I/O signal lines cannot be separated from the wiring for power
In such a case, perform grounding on the KV side using batch-shielded
cables. (In some environments, grounding should be performed on the
reverse side of the KV.)
KV Shielded cable
Sensor
Input
RL
Output
24 V DC Ground
■ Terminal
The terminal screws used are M3. When performing wiring with crimp-style
terminals, use the following ones.
6.0 maximum 6.0 maximum
M3
CONTACT PROTECTION
If inductive loads such as clutches, motors, and solenoids are used, a rush
current may flow when the load power supply is turned on, or a counter
electromotive voltage may be generated when the load power supply is shut
down. The rush current and the counter electromotive voltage can contribute
considerably to shortening the service life of the contacts. To prevent this
from happening, provide a contact protection circuit.
Contact protection circuit examples
For AC load 1 For DC load 1
Contact Contact
a b Contact
Contact
Zener diode
Varistor
19
Note 1: Use a load coil whose rating is less than the contact capacity.
Note 2: Use a diode whose peak inverse voltage is 10 times or more the circuit voltage
and whose forward current is not less than the load current.
Note 3: Individually attach diodes, varistors, and CR circuits directly to the relay coil
terminal.
Expansion Expansion
cable (60 mm) cable (300 mm)
20
CAUTION
Connection methods
1. Peel off the tape stuck to the right side of the basic
unit.
21
DIMENSIONS
■ KV-E4X/E8X/E16X (Expansion inut unit)
Front view (KV-E4X) Front view (KV-E8X) Front view (KV-E16X) Side view
35.4 90
4 4
38 45 65
43.5
■ KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P) (Expansion output unit)
Front view (KV-E4x) Front view (KV-E8x) Front view (KV-E16x) Side view
35.4 90
4 4
38 45 65
43.5
■ KV-E4XR/E4XT(P) (Expansion I/O unit)
Front view Side view
35.4 90
4 4
45
43.5
■ Expansion unit spacer*
OP-35342 OP-35343 OP-35344
Spacer for 4-point Spacer for 8-point Spacer for 16-point
expansion unit expansion unit expansion unit Side view
ø4.0 ø4.0 ø4.0
28 35 55
38 45 65
25.3 4
* See page 3. 66
22
METAL FIXTURE FOR SCREW TIGHTENING
■ KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P)
(Expansion output unit)
■ KV-E4X/E8X/R16X (Expansion I/O unit)
■ KV-E4XR/E4XT(P) (Expansion I/O unit)
OP-35349 4-ø5.0
(mounting hole)
Main unit
mounting hole*
(2 positions) 99 111
25
38 t=2
23
WARRANTIES AND DISCLAIMERS
KEYENCE, at its sole option, will refund, repair or replace at no charge any
defective Products within 1 year from the date of shipment. Unless stated
otherwise herein, the Products should not be used internally in humans, for
human transportation, as safety devices or fail-safe systems. EXCEPT FOR
THE FOREGOING, ALL EXPRESS, IMPLIED AND STATUTORY
WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OF
PROPRIETARY RIGHTS, ARE EXPRESSLY DISCLAIMED. KEYENCE
SHALL NOT BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL,
CONSEQUENTIAL OR OTHER DAMAGES, EVEN IF DAMAGES RESULT
FROM THE USE OF THE PRODUCTS IN ACCORDANCE WITH ANY
SUGGESTIONS OR INFORMATION PROVIDED BY KEYENCE. In some
jurisdictions, some of the foregoing warranty disclaimers or damage limitations
may not apply.
E 1101-3