levelups_series
levelups_series
levelups_series
LEVELUPS SERIES
10 - 20 KVA
Companion Manuals
For more info about this device and its options, please visit www.makelsan.com.tr
Updates
Shipment
Carrying vehicles or handling accessories must have enough features and characteristics to carry
UPS’s weight.
Be more careful of sudden movements, especially when batteries are inside of cabinet.
CONTENTS
This manual must be read before installing the UPS. The device can be installed and started only
by Makelsan authorized personnel.
Installation or start-up by unauthorized personal may cause damage to the device and serious
injury or death.
Warning:
THE UPS MUST BE USED WITH GROUND CONNECTION.
Service-Maintenance
All servicing and maintenance is done internally. All parts in the device can be serviced and
replaced only by a trained technician.
Battery terminal voltages can be at hazardous levels (450Vdc). Nobody except trained personnel
should touch batteries.
Batteries must not be thrown into fire. The damaged batteries and batteries with completed life
cycle must not be thrown to nature. For the collection and disposal batteries must delivered to
MAKELSAN authorized technicians or to the foundations which are authorized for collecting
waste batteries by the Ministry of Environment.
Clearance
There is no any air inlet or outlet grill on the left or right sides of our 10-20 kVA UPS. All air goes
in to UPS from the front and is evacuated from the rear through fans. There must be spaces at
least 1 meter for UPS's front side and 1,2 meter at the back side. Should not be permanent or
temporary use within the limits specified. Otherwise, the UPS performance will decrease.
Access
Operator reaches UPS via front panel on 10-20 kVA UPS. Therefore, enough area must be left for
operator. Also, UPS can be intervened in the back of it for service and maintenance. Because of
this reason, enough area for personal must be left at the rear side of UPS.
1.3 Storage
UPS should be kept in a room or area where is protected from excessive moisture and heat
before commissioning. UPS and battery cabinets must be kept in the original packaging.
WARNING:
Unused batteries must be charged at regular intervals. This time interval
are determined by the battery supplier. Charging can be performed
periodically by connecting to a proper mains for a while.
1.4 Shipment
Carrying vehicles must have be equipped properly and have features and characteristics
sufficient to carry UPS.
The 10-20kVA UPS are delivered on the pallet sized 87x55x140 mm (WxDxH). The height of
device together with pallet is approximately 200mm. The pallet measurements are given
below..
Cabinet is equipped with four-wheel. In this way, it can be placed by moving easily. These wheels
are to be used on smooth surfaces only.
The front wheels of UPS must be locked after positioning properly. The rear side wheels are
fixed.
Be more careful of sudden movements, especially when batteries are inside of cabinet.
2 PRODUCT DESCRIPTION
General View
490mm
Front View
1 LCD Display
3 EPO button
4 Menu Keys
5 Mimic Diagram
Rear View
5 Mains Switch
7 Ground Connection
11 Output Breaker
Electrical Connection
The UPS is connected to the mains voltage through the CB1 breaker. As DC bus is ramped up, the
rectifier starts to operate. Rectifier converts the AC mains to DC voltage and charges the
batteries. When the mains voltage is not available, the necessary the DC bus voltage is generated
with use of the battery voltage. DC DC bus voltage is then converted to mains synchronized AC
voltage by the inverter. This is a high quality voltage. Generated AC power is applied to loads
through the static semi-conductor switches and output (load) breakers.
When maintenance or repair is needed, before the Input (CB1) and Output switches (CB3) are
put to the open circuit (OFF) position, the device must be switched to static bypass mode (please
see 4.1.3.2). Consequently the maintenance switch (CB2) is put to the position closed circuit
(ON). After that first Output breaker (CB3), then Input switches (CB1) are turned OFF
respectively.
Some blocks are named as “static switches” as can be seen above. These blocks consist of inverse
parallel connected thyristors. Controlled by the main board control unit (DSP) these switches
provide feeding of the loads through either mains or inverters. The loads are supplied through
inverter during the normal operating mode. Therefore, Inverter static switches are active if
there are no problems with the system.
System provides the loads to be fed smooth and seamless by mains or inverter. In order to
manage this process at minimum risk, UPS synchronizes the inverter output and static (mains)
bypass as phase and frequency. Therefore, Inverter frequency can be considered same with
mains as long as it is within frequency limit.
User can switch between mains and inverter by using front panel. When the inverter is ready,
while the loads are fed through the bypass line, in case of either power failure or if mains values
are out of tolerances, the loads automatically will be fed through the inverter.
The user can activate the maintenance bypass and all the loads will be fed through the mains
without manipulations from the main panel. After that the input and the output fuses can be
turned to the OFF position.
NOT: When the inverter is not ready the loads are fed through the bypass line. Loads are not
protected against the mains failure, power spikes and other mains problems.
In the external battery cabinets the battery temperature is measured and detected by
"temperature sensor”. UPS adjusts battery charge parameters according to the detected
temperature. These parameters can be easily adjusted via LCD or TELNET interface by
authorized personnel of MAKELSAN. UPS adjusts battery charge parameters according to the
temperature detected by the sensor.
LevelUps series is on-line double conversion device. Our products operate in the following
modes:
Online Mode
Battery Mode
Bypass Mode
Auto Restart
Maintenance Mode
In this mode, UPS feeds the load through the inverters. Rectifier unit is fed by the AC mains
power. Inverter and battery charge units are fed by DC supply generated by rectifier unit.
When the mains voltage is bad the UPS runs on battery mode. UPS feeds the critical load through
the inverter; the energy is obtained from batteries.
In case when UPS is overloaded or if inverter cannot generate a quality AC output due to any
problem and if bypass voltage and frequency values are within the limits, the loads will be fed
from the static bypass source (mains). UPS without interruption switches from inverter to AC
source (mains) via static transfer switches. The inverter source and mains must be synchronized
in order to manage smooth switching. If inverter output and mains are not synchronized,
switching may take up to 15 msec, varying according to load type.
In case of any failure of the mains, UPS will continue feeding the critical loads until the batteries
will reach the end of discharge voltage level. UPS will be working until the batteries are drained
and then will shutdown. When mains are restored to normal conditions UPS automatically will
start its operation, in the period determined by the user. UPS continues to operate in normal
(online) mode as long as the mains values are within desired limits. For LevelUps Series, this
feature is not activated in the initial factory set-up.
On the maintenance mode loads are switched to the maintenance bypass line with a breaker, so
that the UPS can be serviced without cutting off the power to loads. The breaker is in full
conformity with capacity of loads.
Constant current at 1/10 rate of the battery capacity is applied to battery, until it reaches the
float voltage.
Float Charge
Depending on the battery discharge current the 1/3 of the battery energy is charged at this level.
With this level of charging batteries are kept ready for use at maximum capacity. For lead-acid
batteries, this voltage varies between values 2.2-2.35 V/cell. This voltage may differ slightly with
temperature adaptation. Option of setting this coefficient is provided with our UPS, we
recommend using the temperature sensor.
While the system is operating in the battery mode, if battery voltage has dropped below the
discharge level UPS shuts down and stops taking energy from the batteries. This value varies
between 1.6-1.75 V/cell for Lead-Acid batteries, and between 0.9-1.1 V / cell for Ni-Cd batteries.
While the system operates on battery (stored) mode, according to actual loads, if the battery
capacity drops below 40% of its value, device will give audible and visible alarms. This value is
adjustable and can be set by user between 20%-70%.
The auto battery test discharges 10% of the battery energy in a user defined period. Default is 90
days. Test reports the battery condition as good, weak or replace. Results of the latest test can be
seen on the battery screen from the status menu.
This test command can be given from front panel monitor, via TELNET interface, via RS232
smart communication or via UPSMAN (SNMP, see the options).
The purpose of the battery test is to check if the batteries can supply the minimum back-up time
needed in case of mains failure. We recommend checking the test results on the regular basis.
User panel consists of mimic diagram, LCD screen, EPO button and menu keys. The UPS can be
controlled via this panel.
5 Battery module
MAIN SCREEN
Manufacturer – Device Name
Date - Time Control Menu
Load Status as Percent Status Menu
Battery Charge Status as Percent Setup Menu
Remaining Back up (Autonomy) Time Logging Menu
UPS Mode – Actual Alarms Service Menu
Main Menu Titles
MAINS BATTERY
Frequency Voltage
Current Current
Voltage Temperature
Apparent Power BYPASS Charge Percentage
Frequency WARNINGS
Active Power Remaining Back up
Power Factor Current Actual
(Autonomy) Time
Voltage Alarms
Last Test Result
Next Test Date
OUTPUT TEMPERATURE INVERTER
Frequency Rectifier Voltage
Current Inverter Current
Active DEVICE INFORMATION
Voltage Ambient
Active Power Power Software Versions
Battery
Reactive Power Serial No
Bypass
Power Factor Appearant Power
Choke
Apparent Power Voltage
Load Percentage Frequency
Crest Factor Serial Arm x Battery Quantities
Battery Capacity
Note: Batteries must be fully charged and kept floating for at least 1 hour before applying the
quick battery tests.
Batteries must be fully charged and kept in floating mode for at least 5 hours before performing
the battery tests.
Battery tests are performed by directing the power to the mains, independently from the loads.
If the mains values change during the test and are out of limits, the test will be canceled.
Status > Battery >menu timers shows the remaining time to the next test.
If “Stop Battery Test” command is chosen, UPS cancels the battery test and returns the
previous operating mode.
Mains
UP, I, F Voltage, current and frequency of each phase (phase-neutral)
S, P, PF Active power, apparent power and power factor of each phase
Output
UP, I , F Voltage, current and frequency of each phase (phase-neutral)
S, P, PF Active power, apparent power and power factor of each phase
L, CF Load percent of each phase and crest factor
Bypass
UP, I, F Voltage, current and frequency of each phase (phase-neutral)
Battery
Mode UPS operation mode
U, I, °C Charging voltage, current and temperature.
Charge % Charge percentage.
Autonomy Time Remaining back-up (autonomy) time
Last Test Result Capacity and status according to the last test results
Next Test Date Next test date, time and remaining time for test
Temperature
°C,°C,°C,°C,°C Rectifier, inverter, charger, ambient, battery and thyristor temperatures
Inverter
U, I, P Voltage(phase-neutral), current and appearant power of each phase
Alarms
Alarms Actual UPS alarms
Device Information
____ -____-___-___ Inverter, rectifier, CPLD, front panel software version
------------------- UPS serial no
KVA, V/Hz Apparent power, instantaneous output voltage (phase-neutral),
instantaneous output frequency
_x__ , Ah Parallel battery arm number x Serial battery arm number Battery
capacity adjusted in UPS
Auto restart
In battery mode, the device turns off
at the end of battery discharge. Auto-restart
can be used to restart the UPS automatically
when the mains are restored.
Turn on auto-restart and set the time to
define when the device will be started after
the normal values of the mains are restored.
Screen
Change the screen contrast to make it
more visible on different environmental
conditions.
Beeper
Turn the beeper sound on/off.
Language
Set the menu language.
Communication
Set the protocol for the RS232 connection.
The options are SEC and TELNET
3 INSTALLATION
3.1 Single Module Installation
This section contains the warnings and control actions that must be performed before the UPS
start-up. Additionally, you will find here important information about the UPS cabins
transportation, positioning and connections.
3.1.1 Warnings
Battery Hazard
Proper safety gear must be used to protect the skin and the eyes from electrical arcs.
Batteries with leakage must never be used and must be replaced. Defected batteries must be
uninstalled and transported to the destruction points with safety precautions taken.
Battery ingredients are hazardous. In case of contact with battery ingredients, rinse the skin
with water, and consult a physician if irritation occurs.
Remove any metal accessories (ring, watch, etc.) before working on the device.
UPS needs three phase and four cable (+ground) supply system for input. This supply system
type is confirmed as IEC60364-3 standards. Optionally UPS have transformers which have
ability to convert from 3 cables to 4 cable system. If IT AC power distribution system will be
installed, 4 pole-circuit breaker systems must be used. More detailed explanations can be
found in the IEC60364-3 standards titles.
Before installation of the device the following control actions must be taken, these first and most
important steps will secure the accurate operation of the product.
Check if any damage was done to the device during transportation. Report any damages
instantly.
Make sure that model power rating is right. Check the device label for the actual power
rating.
3.1.3 Positioning
The device and the batteries are designed for the indoor use. Keep the device in a cool and dry
place, with the air flow, humidity and temperature values must be within the specified range.
In the LevelUps 10- 20 KVA Series, fresh air enters the device from the front and goes out from
the fans on the rear side of the device. Care must be taken in order not to cover the air entrance
and exit spots. UPS must be positioned on a place where it is protected from water etc. contact
risks.
If the area is dusty, optional filters must be used for such environment. These filters usage must
be done as per instructions document.
Below given cooling values must be provided to reach the maximum level of performance of UPS
and batteries
10-20 kVA UPS can be configured by 62 pcs 4,5 Ah, 7 Ah or 9Ah standard as following.
The 7/9 Ah and 4.5 Ah batteries positioning can be seen at the following table;
Batteries should be used in the environment with uniform temperature conditions. Temperature
is a major factor in determining the battery life and capacity. The operating temperature for
batteries recommended by battery manufacturers is 20-25 °C. Operating above this range will
reduce the battery life while operation below this range will reduce the battery capacity, as a
result the expected backup time might not be obtained while autonomy. Please keep batteries
away from heat sources and main air inlets. Pay attention and observe the following points.
Especially, for the external cabinet batteries system of UPS, fuses must definitely be used. These
fuses must be mounted as close as possible to the batteries. This closeness will increase the
electrical operation safety.
External battery cabinet and battery room applications are given below as an example. The
application form may vary according to the customer.
Carrying vehicles or handling accessories must have enough features and characteristics to
carry UPS’s weight.
Cabinet is equipped with four-wheel. Thanks to this feature, it can be moved easily. These
wheels must be used only on smooth surfaces.
The front side wheels of UPS must be locked after positioning properly. The back side wheels are
fixed. Be more careful of sudden movements, especially when batteries are inside of cabinet.
Makelsan strictly recommends a distribution board for the UPS outputs. Proper fuses and
breakers must be used in such distribution board. A-B type fuses or magnetic breakers are
recommended if the load is suitable.
To protect the AC inputs, thermal magnetic breakers or V type breakers must be installed on the
distribution board.
Over current protecting must be installed on mains input distribution board and fuses must be
chosen 135% higher rated than the ones given in the table below. Fuses must be C-type.
Ground leakages flow to the ground through the EMI filters on the input and the output of the
UPS. Makelsan recommends the use of 700mA rated relays for handling leakage currents.
Full load input and output currents must be reviewed for proper cabling and fuse selection.
It should be noted that with non-linear loads, neutral current may rise up to 1.5 times the phase
current.
Ground cable must be connected directly to ground line and must be kept as short as possible.
Typical ground cable cross sections are 4mm2 for 10 kVA, 6 mm2 for 15 kVA and 10 mm2 for 20
kVA ratings. The length of the cable must not be over 5 meters.
All electrical connections of the UPS are made from the front side of the device.
ATTENTION! 3 pole-circuit breakers (switch) are used for the input and
output of UPS, Neutral line must not be interrupted.
2. Unscrew and remove the metal board on the rear side of the device.
4. Make sure that the circuit breakers are off. The use of these circuit breakers are explained on
the operation section.
R to INPUT L1,
S to INPUT L2,
T to INPUT L3,
N(Neutral) to INPUT N.
Use the cable clips to stabilize the cables when the connections are done.
WARNING: Make sure that the loads are isolated from the UPS output if they
are
not ready to be connected.
WARNING: Make sure that the cables are connected properly before UPS is
started. Additionaly, check if there is galvanic isolation transformers at
input of UPS and consider the local directions.
WARNING: Check the grounding before starting the UPS. Wrong works or
grounding on UPS or other devices of installaton may be hazardous. Wrong
works and grounding may damage UPS and another system on the
installation.
You can find explanations about installation procedures and connections of internal and
external batteries in this section.
2. Make sure that the batteries are connected properly in series and parallel.
3. Reach the –BAT labeled cable inside the UPS and connect it to the negative battery
terminal.
4. Reach the +BAT labeled cable inside the UPS and connect it to the positive battery
terminal.
Avoid short circuit in the batteries. Short circuited batteries are hazardous
to human health and environment!
Internal battery temperature is monitored by the NTC connected to the J26 socket of the main
board. Refer to the options section for external battery monitoring.
You can find details about how to configure external batteries above under “External Batteries
Configuration” title.
The information about connection of external batteries and UPS is given in this section.
Avoid short circuiting batteries . Short circuit the batteries can damage you
and your environment!
8. Make sure that the polarities are connected correctly by checking battery connections for the
last time.
12. Check if there is appropriate battery voltages to the battery input terminals by proper
measuring device.
External battery cable selection is determined by application. Fuses which are recommended for
UPS and battery cabinet are given. To connect to these type fuses, the lowest diameter cables are
suggested.
Please, refer to standard called EN 50525-2-31(VDE 0100-430) in this subject. The selection
should be such that the cable will allow at most 0.5 Vdc decreasing.
"External Battery Temperature Measurement Kit" is used for optimization according to battery
temperatures, batteries use is optimized according to temperature.
MAKELSAN UPS have standard or optional connections of advanced external battery cabinet,
environmental monitoring, control panels and various intelligent monitoring.
The product which you have bought can be operated in parallel; however, this feature is offered
as an option. Please contact your dealer for parallel operation.
In case of need for redundancy or more power, LevelUps series can be operated in parallel up to
quantity 8 (eight). A schematic diagram which shows two UPS connected in parallel can be seen
below.
Input and output of more than one UPS are connected to each other; but definitely each battery
group is different from another, batteries cannot be used in common. The following points
should be considered while placement of UPS in parallel system and their electrical connections
are made:
The UPSs which are connected in parallel must be from the same series and must have
Devices must be running on the same firmware, if not, old firmware must be updated.
Devices must be located as close possible as to each other (max. 6 x 110 cm paralleling
cables.)
UPS must be connected in parallel on the distribution panel an phases must be connected
Each UPS must have their own battery set, batteries cannot be used for more than one
Power input and output cables from the device to the distribution board must be equal in
Connect the parallel cable as shown in figure below. Only use the cables provided by Makelsan.
4 OPERATION
4.1 Operation Procedure
You can find informations about circuit breaker, first start-up , types of UPS operation tests ,
turning UPS off , EPO and RS232 serial communication system in this section.
There are four circuit breakers on the rear side of the device.
These are used for the AC input, maintenance bypass, output and the battery connections
respectively.
AC input voltage will be applied directly to loads through CB2. In this way, maintenance
purposed switching is done properly. If UPS is actived while it is working thanks to auxilary
short circuit info located in CB3, mains makes the bypass static switches actived. The system will
be switched to maintenance mode smoothly.
CB3 is used to connect or seperate AC voltage that come from static switches to the loads on
UPS.
3. Turn input circuit breaker (CB1) ON. If there is an external bypass input, put the external
bypass switch (CB5) to position closed circuit (ON)
5. Check the UPS has switched to normal operation mode, via mimic diagram LEDs and LCD
panel.
After all these steps, check that load is fed through inverter static switches via mimic diagram. In
a contrary situation, check UPS total and phase loads. The UPS gives audio alerts in an overload
condition, without feeding critical AC loads.
After first start-up check device operation by switching between the foperation. asdfasd modes
manually.
Turn CB1 OFF. This action cuts off the mains voltage and the UPS starts operating on battery
mode. Turn CB1 back ON again if everything is ok.
Use the front panel to switch the device to static bypass mode. Check the mimic panel to make
sure that the device has switched to bypass mode.
NOTE: UPS will not switch to bypass mode if the inverter voltage is out of limits or there is and
overload or overtemperature situation.
Use the front panel to switch the device to online mode. Check the mimic panel to make sure that
the device has switched to online mode.
NOTE: the UPS will not switch to normal mode if the inverter voltage is out of limits, or there is
an over load or over temperature situation.
WARNING: Make sure that the inverter output is synchronous with the
maintenance bypass line before switching to maintenance bypass mode.
Otherwise there is a possibility of cutting off the load power for a short
while.
Use the front panel to switch the device to static bypass mode. Check the
mimic panel to make sure that the device has switched to bypass mode.
WARNING:
3. Check if the the UPS has switched to bypass mode, via mimic diagram LEDs and LCD panel.
4. Turn OFF respectively the output(CB3), battery (CB4), outer battery (CB5) and input (CB1) .
WARNING :
Make sure that there are no critical loads on the UPS output before
performing a complete shutdown.
By pressing the EPO button, the device respectively turns the rectifier, the booster and the
inverter OFF. If the output breaker turn off option is set, the UPS completely disconnects from
the system.
LevelUps series has an RS-232 interface which supports SEC and TELNET protocol as standard.
This interface is fully isolated and safe. UPS can be monitored remotely via a computer (PC) or
SNMP by using this protocol. This connection works with all kinds of options.
5 EXPLANATIONS of LOGGING
UPS will beep when any problem is detected. You can see the first information about the
situation on the front monitor panel. This may not be enough most of the time. In this case, you
can see the following warnings by using log screen.
Event Explanations
RS232 Start
1 UPS was started by RS232 communication software.
Command
RS232 Stop
2 UPS was stopped by RS232 communication software.
Command
After the batteries discharge totally, UPS restarted itself automatically after the
3 Auto Restart mean time which adjusted that follows the mains getting back to normal
values.
Batteries’ voltage has gone below cut off voltage value while UPS was
9 End Of Discharge
operating on the battery mode.
UPS has operated at overload more than time limit adjusted.The Loads will be
10 Overload Timeout
transferred to bypass line.
Battery test has completed.You can see the all results via front panel status
11 End of Battery Test
menu..
Test was aborted manually or by UPS since the criterias were not provided
12 Batt. Test Aborted
during battery test.
Manuel Switch To Static switchs directions were changed manually to the bypass line via UPS
13
BYP command menu.
Bypass voltage value is out of limit while UPS was operating on the bypass
23 Bypass Voltage Bad mode.UPS will switch to normal mode if temperature and load status are
normal.If not ,UPS will stop.
Bypass frequency value is out of limit while UPS was operating on the bypass
24 Bypass Freq. Bad mode.UPS will switch to normal mode if temperature and load status are
normal.If not ,UPS will stop.
25 Coil Overtemp Over temperature is observed for UPS’ inverter and rectifier coils.
Inverter voltage is out of limit. Load will be transferred to bypass line ,when
Inverter Voltage
26 inverter voltage gets back to normal values,UPS will switch to normal mode
Bad
again.
Output load value is over %105, overloading counter will start to count , If UPS
27 Overload is on normal mode , the charging will be stopped until load value gets back to
normal.
28 Maint. BYP. Sw. Off Maintenance bypass switch is deactivated.
Ambient Nor.
29 UPS ambient temperature has got back to allowed limit values.
Temp.
30 Mains Voltage Nor. Mains voltage is in the limited values , UPS will switch to normal mode.
Inverter Nor. Inverter temperature is in the limited values .If load and temperature values
31
Temp. are normal, UPS will switch to normal mode.
Rectifier temperature is in the limited values .If load and temperature values
32 PFC Nor. Temp.
are normal, UPS will switch to normal mode.
34 STS Nor. Temp. Temperature of Static transfer switches is in the allowed limit.
Bypass Voltage
35 Bypass voltage is within defined limits.
Nor.
36 Bypass Freq. Nor. Bypass frequency is within defined limits.
37 Coil Normal temp. UPS inverter or rectifier coil temperature has got back to normal values.
Inverter Volt.
38 Inverter voltage is in the limited values , UPS will switch to normal mode.
Norm.
39 Normal Load Output load is under %100 , If charging was OFF , It will be ON .
BYP Thyr.L1 Short
40 UPS has detected short circuit at bypass L1 thyristor.UPS will shut down.
C.
BYP Thyr.L2 Short
41 UPS has detected short circuit at bypass L2 thyristor.UPS will shut down.
C.
42 BYP Thyr.L3 Short C UPS has detected short circuit at bypass L3 thyristor.UPS will shut down.
UPS Thyr.L1 Short
43 UPS has detected short circuit at inverter L1 thyristor.UPS will shut down.
C.
UPS Thyr.L2 Short
44 UPS has detected short circuit at inverter L2 thyristor.UPS will shut down.
C.
UPS Thyr.L3 Short
45 UPS has detected short circuit at inverter L3 thyristor.UPS will shut down.
C.
UPS Thyr.L1 Open UPS has detected that inverter L1 thyristor can not be activated.Load will be
46
C. transferred to bypass line.
UPS Thyr.L2 Open UPS has detected that inverter L2 thyristor can not be activated.Load will be
47
C. transferred to bypass line.
UPS Thyr.L3 Open UPS has detected that inverter L3 thyristor can not be activated.Load will be
48
C. transferred to bypass line.
BYP Thyr.L1 Open UPS has detected that bypass L1 thyristor can not be activated.Load will be
49
C. transferred to inverter line.
BYP Thyr.L2 Open UPS has detected that bypass L2 thyristor can not be activated.Load will be
50
C. transferred to inverter line.
BYP Thyr.L3 Open UPS has detected that bypass L3 thyristor can not be activated.Load will be
51
C. transferred to inverter line.
One or more of UPSs which operate in paralel mode do not match in phase
52 Parl. Phs. Rot. Err.
sequence.
53 Battery Start Starting through battery command has been given to UPS .
54 Parl. Start Error One or more of UPSs which operate in paralel mode could not start to operate.
55 Inverter Fault UPS couldn't prepare the inverter voltage.
56 Output Off Static transfer switches all disabled. The loads can not be energized.
UPS is operating in the normal mode,load are energized through rectifier –
57 Normal Mode
inverter line.
UPS is operating in the battery mode,load are energized through battery –
58 Battery Mode
inverter line.
59 Bypass Mode UPS is operating in the bypass mode,load are energized through bypass line.
Maint. Bypass UPS is operating in the maintenance bypass mode,load are energized through
60
Mode maintenance bypass line.
2 or more UPS are operating in power sharing mode. Load is fed through UPSs’
61 Parallel Mode
inverter lines.
UPS has switched to battery test mode,loads are energized through rectifier-
62 Test Mode
battery- inverter line as source sharing.
Manual Switch to
63 Switching to inverter(normal) mode command has been given via front panel.
UPS
Output Voltage Output voltage is detected during the period of starting UPS .UPS has been
64
Error stopped.
Abnormal stuation is detected during the moment of rectifier operating.UPS
65 PFC Stop Cmd.
has stopped itself.
Manuel Start
66 Start command is given via UPS command menu.
Command
Manuel Stop
67 Stop command is given via UPS command menu.
Command
68 UPS Stopped UPS has been stopped.
UPS has switched to bypass mode so many times i a short period,UPS will be
69 Bypass Problem
shut down.
Parameters
70 Device-related parameters were changed on the service menu
Changed
71 Batterys Changed Battery replacement date has been changed.battery statistics will be reset.
Load impact The load which can not be handled by inverter is activated. Loads will be
72
Transfer transferred to bypass line.
UPS which is operating in paralel mode has been given a command to change
73 Parallel Command
the status of static switches.
No P.CAN Bus Slave UPS which is operating in paralel mode can’t reach to master UPS from
74
Comm. CAN bus.If UPS is operating,will be shut down.
Ext. Start UPS which is operating in paralel mode has been given a command to start up
75
Command by another (master) UPS.
Ext. Stop UPS which is operating in paralel mode has been given a command to stop by
76
Command another (master) UPS.
UPS which is operating in paralel mode has been given a command to transfer
77 Ext. Switch To BYP.
the load to bypass line.
UPS which is operating in paralel mode has been given a command to transfer
78 Ext. Switch To UPS
the load to inverter line.
Slave UPS which is operating in paralel mode has detected a failure of input
79 Parallel Comm. FE.
current sharing.
Inverter voltage reached needed value after UPS is started up. UPS can feed the
80 Inverter OKEY
loads through inverter.
81 Batt. Temp. Err. Battery temperature is out of defined limits, batteries can be damaged.
Technical Specifications
Input
Input Voltage Range 220/380 VAC - %15 + %18 3P + N + PE
Input Power Factor At Full Load > 0,99
Input Frequency Range 45-65 Hz (Selectable)
Output
Output Voltage Range 220/380 VAC 3P + N ± 1% Static, ± 1% Dynamic
Efficiency Up to %96
50Hz ±0,5% synchronous with the network, 50Hz ±
Output Frequency Range
0,2% Battery Mode
Lineer Load <%2
Output THD (THDv)
Non-Lineer Load <%6
Crest Factor (CF) 3:1
Overload Capacity At %125 load 10 min. , at %150 load 1 min.
www.makelsan.com.tr
Headquarter: İstanbul Deri Organize Sanayi Bölgesi 2. Yol I -5 Parsel 34956 Tuzla/ İstanbul
Tel : 0216 428 65 80
Faks : 0216 327 51 64
e-mail : makelsan@makelsan.com.tr
Izmir Branch: Halkapınar Mah. 1348 Sok. 2AE Keremoğlu İş Merkezi Yenişehir – İzmir
Tel : 0232 469 47 00
Faks : 0232 449 47 00
e-mail : izmir@makelsan.com.tr
Headquarter: İstanbul Deri Organize Sanayi Bölgesi 2. Yol I -5 Parsel 34956 Tuzla/
İstanbul
Tel : 0216 428 65 80
Fax : 0216 327 51 64
E-mail : makelsan@makelsan.com.tr
İzmir Office : Halkapınar Mah. 1348 Sok. 2AE Keremoğlu İş Merkezi Yenişehir – İzmir
Tel : 0232 469 47 00
Fax : 0232 449 47 00
E-mail : izmir@makelsan.com.tr